Sanyo 18xls52 User Manual

SANYO AIR CONDITIONING PRODUCTS  
DUCTLESS SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS  
SPECIFICATIONS - SECTION 15700  
Covers Sanyo System Models > 18XS52, 18XLS52 (See plans for specified models & details)  
DUCTLESS SPLIT SYSTEM AIR CONDITIONERS - RECESSED CEILING MOUNT  
1) GENERAL SPECIFICATIONS  
Furnish & install a Sanyo manufactured Ductless, Split System Air Conditioner(s) consisting of an  
indoor recessed ceiling mounted evaporator/blower section with four (4) way airflow & matching  
outdoor condensing section. System(s) shall bear the ARI label showing that the system(s) is ARI  
210 or 240 & 270 Certified. Systems shall be listed by ETL Testing Laboratories and bear the  
ETL label. Matching systems shall meet or exceed the minimum, Federally mandated Seasonal  
Energy Efficiency Rating (SEER) of 10, as certified by the ARI testing programs. System(s)  
indoor & outdoor units will operate at sound levels equal to or below specified system(s) (see  
plans). Installation & Owners Manuals shall be provided with each system.  
Matching indoor & outdoor sections shall be connected by deoxidized, annealed refrigerant copper  
tubing, type “L”, cleaned & capped. All systems shall have flared refrigeration connections on  
both indoor & outdoor sections. Size & insulate tubing according to manufacturer’s specifications.  
System(s) indoor & outdoor sections shall be completely factory assembled & wired, with a pre-  
charge of refrigerant. A single power source shall provide voltage to both the outdoor & indoor  
units. Electrical wire & connections to outdoor section, and between indoor & outdoor section(s),  
shall be sized, installed & grounded by the installer in conformance with the National Electrical  
Code (N.E.C.), local codes, as well as, manufacturer’s instructions.  
System(s) shall be equipped with a microprocessor control system, utilizing an infrared remote  
controller with LCD display that provides access to all system functions, and transmits room  
conditions & programs to the indoor microprocessor every 3 minutes. Infrared remote controller  
shall be capable of operating system mounted up to 26’ from the indoor section, according to  
manufacturer’s recommendations & instructions. System(s) shall have the capability of continuous  
operation in the case of a lost or damaged remote controller, utilizing a factory installed, integral  
manual switch in conjunction with the system microprocessor.  
1A) System Infrared Remote Controller Functions will include: system mode selection,  
programmable temperature control, 24 hour programmable timer, one (1) hour off timer,  
automatic three (3) speed indoor fan speed control, constant fan speed selection, night setback  
mode, automatic sweep/flap control, user selectable room temperature sensor located on either  
infrared remote controller or indoor unit, multiple system control using a single controller.  
-1-  
with overload protection, permanent lubrication & multi-speed capability. Unit(s) shall contain a  
Printed Circuit Board (PCB) with a control circuit fuse & microprocessor, factory wired &  
mounted, that receives & processes all commands & transmissions from the system Infrared  
Remote Controller. Indoor unit(s) shall also contain an Operation Switch with visible lamps for  
operation, standby & timer functions, as well as, a system test switch & a manual ON/OFF switch.  
Unit(s) shall contain an air sensor thermistor, a coil freeze safety thermistor to prevent freeze-up, a  
factory installed light-duty condensate drain pump, drain pan, hose & fitting, and refrigeration line  
connections with flare nuts.  
Indoor section shall be provided with a factory assembled concentric supply & return air grille  
with a motorized louver/flap on each of the four (4) supply air openings. Motorized louvers/flaps,  
controlled by the infrared remote controller, shall provide automatic, full oscillating supply  
airflow, as well as being capable of being placed in a set, stationary position. Up to two (2) of the  
supply air openings may be closed for ceiling perimeter or corner mounting, and to utilize  
alternate plenum supply air option. Indoor Unit(s) will be furnished with an in-ceiling plenum,  
which surrounds the evaporator coil section. Plenum shall contain alternate supply air knockout(s)  
to allow for ducted airflow to a separate room. Unit(s) shall be capable of utilizing fresh, outside  
air up to a maximum of 20% of the rated CFM of the system, with the field installed, optional  
Fresh Air Intake Chamber manufactured by Sanyo. Unit(s) shall be furnished with long life (2,500  
hour), anti-mold, poly type washable air filters that can be easily removed without removing  
indoor unit casing. Indoor unit(s) shall be powered by voltage from the matching outdoor unit(s).  
4) AVAILABLE SANYO ACCESSORIES – Recessed Ceiling Mount Models  
Insulated Copper Line Sets, Condensate Pumps, Outdoor  
Section Wall Mounting Bracket, Hard Wired Remote Controller, and Fresh Air Intake Chamber.  
-3-  

Mtd Automobile Parts 357cc User Manual
Niles Audio Personal Emergency Reporting System Pers 2400b User Manual
Panasonic Cs W7dkr User Manual
Samsung Centralized Workflow Solution Scx 6545n User Manual
Sanyo C3632 User Manual
Shibaura N843l User Manual
Toshiba Air Conditioner Rav Sm806bt E User Manual
United States Stove 1321 User Manual
Whirlpool Acs802 User Manual
York Y33 User Manual