| 
		 Mitsubishi Electronics Mitsubishi Digital Electronics Air Conditioner Muz Fd09na User Manual  | 
	
| 	
		 OUTDOOR UNIT   
					No. OBH498   
					HFC   
					utilized   
					SERVICE MANUAL   
					R410A   
					Wireless type   
					Models   
					MUZ-FD09NA   
					U1   
					MUZ-FD09NA-   
					MUZ-FD12NA   
					MUZ-FD12NA-   
					U1   
					Indoor unit service manual   
					MSZ-FD•NA Series (OBH497)   
					CONTENTS   
					1. TECHNICAL CHANGES ··································· 3   
					2. PART NAMES AND FUNCTIONS····················· 3   
					3. SPECIFICATION················································ 4   
					4. OUTLINES AND DIMENSIONS ························ 6   
					5. WIRING DIAGRAM············································ 7   
					6. REFRIGERANT SYSTEM DIAGRAM··············· 8   
					7. DATA·································································· 9   
					8. ACTUATOR CONTROL··································· 15   
					9. SERVICE FUNCTIONS ··································· 16   
					10. TROUBLESHOOTING····································· 16   
					11. DISASSEMBLY INSTRUCTIONS···················· 32   
					PARTS CATALOG (OBB498)   
					TM   
					NOTE:   
					RoHS compliant products have <G> mark on the spec name plate.   
				1 
					TECHNICAL CHANGES   
					MUZ-FD09NA   
					MUZ-FD12NA   
					MUZ-FD09NA -   
					MUZ-FD12NA -   
					U1   
					U1   
					1. New model   
					2 
					PART NAMES AND FUNCTIONS   
					MUZ-FD09NA   
					MUZ-FD12NA   
					Air inlet   
					Piping   
					Drain hose   
					Air outlet   
					Drain outlet   
					3 
				3 
					SPECIFICATION   
					Outdoor unit model   
					MUZ-FD09NA   
					MUZ-FD12NA   
					Cooling   
					1 
					Btu/h   
					Btu/h   
					Btu/h   
					W 
					W 
					W 
					9,000 (2,800~9,000)   
					10,900 (3,000~18,000)   
					12,500   
					12,000 (2,800~12,000)   
					13,600 (3,000~21,000)   
					13,600   
					Capacity   
					Rated (Minimum~Maximum)   
					Heating 47   
					Heating 17   
					1 
					2 
					Capacity Rated   
					Cooling   
					1 
					650 (160~650)   
					750 (150~2,400)   
					1,730   
					960 (160~960)   
					980 (150~2,400)   
					1,780   
					Power consumption   
					Rated (Minimum~Maximum)   
					Heating 47   
					Heating 17   
					Cooling   
					1 
					2 
					Power consumption Rated   
					1 
					EER   
					[SEER]   
					3 
					13.8 [23.0]   
					12.5 [22.0]   
					HSPF IV(V)   
					COP   
					4 
					Heating   
					Heating   
					10.55 (7.4)   
					10.55 (7.4)   
					1 
					4.30   
					4.10   
					External nish   
					Power supply   
					Munsell 3Y 7.8/1.1   
					208/230 , 1 , 60   
					V , phase , Hz   
					Max. fuse size (time delay)   
					Min. circuit ampacity   
					Fan motor   
					A 
					A 
					F.L.A   
					15   
					12   
					0.56   
					Model   
					SNB130FQAH   
					8.6   
					Compressor   
					R.L.A   
					L.R.A   
					10.8   
					Refrigerant control   
					Liner expansion valve   
					Cooling   
					Heating   
					dB(A)   
					dB(A)   
					48   
					49   
					48   
					49   
					Sound level   
					1 
					Defrost method   
					Dimensions   
					Reverse cycle   
					31-1/2   
					W 
					D 
					H 
					in.   
					in.   
					in.   
					Ib.   
					11-1/4   
					21-5/8   
					80   
					Weight   
					Remote controller   
					Control voltage (by built-in transformer) VDC   
					Refrigerant piping   
					Wireless type   
					12 - 24   
					Not supplied   
					1/4 (0.0315)   
					3/8 (0.0315)   
					Flared   
					Liquid   
					Gas   
					Indoor   
					Outdoor   
					in.   
					in.   
					Refrigerant pipe size   
					(Min. wall thickness)   
					Connection method   
					Flared   
					Height differ-   
					ence   
					Piping length ft.   
					ft.   
					40   
					Between the indoor &   
					outdoor units   
					65   
					Refrigerant charge (R410A)   
					Refrigeration oil (Model)   
					2 lb. 9 oz.   
					NE022   
					NOTE : Test conditions are based on ARI 210/240.   
					1 : Rating conditions (Cooling) — Indoor : 80 FDB, 67 FWB, Outdoor : 95 FDB, (75 FWB)Rated frequency   
					(Heating) — Indoor : 70 FDB, 60 FWB, Outdoor : 47 FDB, 43 FWB Rated frequency   
					2 :   
					(Heating) — Indoor : 70 FDB, 60 FWB, Outdoor : 17 FDB, 15 FWBMaximum frequency   
					4 
				Test condition   
					3, 4   
					Indoor air condition   
					Dry bulb (°F) Wet bulb (°F)   
					Outdoor air condition   
					Dry bulb (°F) Wet bulb (°F)   
					Mode   
					ARI   
					Test   
					"A" Cooling Steady State   
					at rated compressor Speed   
					80   
					67   
					95   
					(75)   
					"B-2" Cooling Steady State   
					at rated compressor Speed   
					80   
					80   
					80   
					80   
					70   
					70   
					70   
					70   
					70   
					70   
					67   
					67   
					67   
					67   
					60   
					60   
					60   
					60   
					60   
					60   
					82   
					82   
					67   
					87   
					47   
					17   
					62   
					47   
					35   
					35   
					(65)   
					(65)   
					(53.5)   
					(69)   
					43   
					SEER "B-1" Cooling Steady State   
					(Cooling) at minimum compressor Speed   
					Low ambient Cooling Steady State   
					at minimum compressor Speed   
					Intermediate Cooling Steady State   
					at Intermediate compressor Speed   
					5 
					Standard Rating-Heating   
					at rated compressor Speed   
					Low temperature Heating   
					at rated compressor Speed   
					15   
					Max temperature Heating   
					at minimum compressor Speed   
					56.5   
					43   
					HSPF   
					(Heating)   
					High temperature Heating   
					at minimum compressor Speed   
					Frost Accumulation   
					at rated compressor Speed   
					33   
					Frost Accumulation   
					at Intermediate compressor Speed   
					33   
					5 
					5 : At Intermediate compressor Speed   
					=("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".   
					OPERATING RANGE   
					(1) POWER SUPPLY   
					Rated voltage   
					Guaranteed Voltage   
					208/230 V   
					1 phase   
					60 Hz   
					Min.187 V 208 V 230 V Max.253 V   
					Outdoor unit   
					(2) OPERATION   
					Intake air temperature (°F)   
					Mode   
					Condition   
					Standard temperature   
					Maximum temperature   
					Minimum temperature   
					Maximum humidity   
					lndoor   
					78 %   
					Outdoor   
					DB   
					80   
					90   
					67   
					WB   
					67   
					73   
					DB   
					95   
					115   
					14   
					WB   
					— 
					— 
					— 
					Cooling   
					57   
					— 
					Standard temperature   
					Heating Maximum temperature   
					Minimum temperature   
					70   
					80   
					70   
					60   
					67   
					60   
					47   
					75   
					14   
					43   
					65   
					13   
					5 
				4 
					OUTLINES AND DIMENSIONS   
					Unit: inch   
					MUZ-FD09NA   
					MUZ-FD12NA   
					REQUIRED SPACE   
					Basically open 4 inch or more   
					without any obstruction in front   
					and on both sides of the unit.   
					15-3/4   
					Air in   
					Drain hole 1-5/8   
					Air in   
					1-9/16   
					2- 3/8 13/16 Oval hole   
					Air out   
					29/32   
					11-1/4   
					17/32   
					7/8   
					Open two sides of left,   
					right, or rear side.   
					handle   
					Liquid pipe :1/4 (flared)   
					Gas pipe :3/8 (flared)   
					11-29/32   
					6-23/32   
					5-15/16   
					19-11/16   
					31-1/2   
					2-23/32   
					6 
				5 
					WIRING DIAGRAM   
					MUZ-FD09NA MUZ-FD12NA   
					7 
				6 
					REFRIGERANT SYSTEM DIAGRAM   
					Unit:inch   
					MUZ-FD09NA   
					MUZ-FD12NA   
					4-way valve   
					Refrigerant pipe ø3/8   
					(with heat insulator)   
					Muffler   
					Outdoor heat   
					exchanger   
					temperature   
					thermistor   
					RT68   
					Stop valve   
					(with service port)   
					Outdoor   
					heat   
					Muffler   
					Discharge   
					temperature   
					thermistor   
					RT62   
					Flared connection   
					exchanger   
					Service   
					port   
					Ambient   
					temperature   
					thermistor   
					RT65   
					Compressor   
					Service   
					port   
					Defrost   
					thermistor   
					RT61   
					Capillary tube   
					O.D. 0.118 × I.D. 0.071   
					× 23-5/8   
					(ø3.0 × ø1.8   
					× 
					600)   
					Strainer   
					#100   
					Expansion   
					valve   
					Flared connection   
					Stop valve   
					R.V. coil   
					heating ON   
					cooling OFF   
					(with strainer)   
					Capillary tube   
					O.D. 0.118 × I.D. 0.079   
					× 9-7/16   
					(ø3.0 × ø2.0 × 240)   
					Refrigerant pipe 1/4   
					(with heat insulator)   
					Refrigerant flow in cooling   
					Refrigerant flow in heating   
					MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE   
					Refrigerant piping : ft   
					Piping size O.D : in   
					Model   
					Max. Length   
					Max. Height difference   
					B 
					Gas   
					3/8   
					Liquid   
					1/4   
					A 
					MUZ-FD09NA   
					MUZ-FD12NA   
					65   
					40   
					Indoor   
					unit   
					Max. Height   
					difference   
					B 
					Max. length   
					A 
					Outdoor unit   
					ADDITIONAL REFRIGERANT CHARGE (R410A:oz.)   
					NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.   
					Refrigerant piping length (one way) : ft   
					Model   
					Outdoor unit precharged   
					2 lb. 9 oz.   
					25   
					0 
					30   
					40   
					50   
					60   
					65   
					MUZ-FD09NA   
					MUZ-FD12NA   
					1.62   
					4.86   
					8.10   
					11.34   
					12.96   
					Calculation : X oz. = 1.62/ 5 oz./ ft x (Refrigerant piping length (ft) - 25)   
					NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.   
					8 
				7 DATA   
					MUZ-FD09NA MUZ-FD12NA   
					7-1. PERFORMANCE DATA   
					1) COOLING CAPACITY   
					Indoor air   
					Outdoor intake air DB temperature (˚F)   
					85 95 105   
					TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC   
					Model   
					IWB   
					(˚F)   
					71   
					67   
					63   
					75   
					115   
					11.0 6.9 0.58 10.3 6.5 0.63 9.7   
					6.1 0.68 9.0   
					6.8 0.65 8.4   
					7.6 0.62 7.7   
					5.6 0.72 8.3   
					6.4 0.69 7.7   
					6.9 0.66 7.0   
					5.2 0.75   
					5.8 0.72   
					6.3 0.69   
					MUZ-FD09NA   
					10.4 7.9 0.55 9.7   
					9.8 8.8 0.52 9.1   
					7.4 0.60 9.0   
					8.1 0.58 8.5   
					71   
					67   
					14.7 8.8 0.85 13.7 8.2 0.94 12.9 7.7 1.01 12.0 7.2 1.06 11.0 6.6 1.10   
					13.9 10.2 0.81 13.0 9.5 0.89 12.0 8.8 0.96 11.2 8.1 1.02 10.3 7.5 1.07   
					MUZ-FD12NA   
					63   
					13.1 11.3 0.77 12.1 10.5 0.85 11.3 9.7 0.92 10.3 8.9 0.98 9.4   
					8.1 1.02   
					NOTE : 1. IWB : Intake air wet-bulb temperature   
					TC : Total Capacity (x103 Btu/h)   
					SHC : Sensible Heat Capacity (x103 Btu/h)   
					TPC : Total Power Consumption (kW)   
					2. SHC is based on 80 ˚F of indoor Intake air DB temperature.   
					2) COOLING CAPACITY CORRECTIONS   
					Refrigerant piping length (one way : ft.)   
					25 (std.)   
					40   
					65   
					MUZ-FD09NA   
					MUY-FD12NA   
					1.0   
					0.954   
					0.878   
					3) HEATING CAPACITY   
					Indoor air   
					Outdoor intake air WB temperature (˚F)   
					35 43   
					Model   
					IDB   
					(˚F)   
					75   
					70   
					65   
					75   
					70   
					65   
					15   
					25   
					45   
					55   
					TC   
					6.3   
					6.7   
					6.9   
					7.9   
					8.4   
					8.6   
					TPC   
					0.56   
					0.54   
					0.52   
					0.73   
					0.71   
					0.68   
					TC   
					7.9   
					8.2   
					8.6   
					9.9   
					TPC   
					TC   
					9.4   
					TPC   
					0.73   
					0.71   
					0.69   
					0.96   
					0.93   
					0.91   
					TC   
					TPC   
					0.77   
					0.75   
					0.73   
					1.00   
					0.98   
					0.96   
					TC   
					TPC   
					0.78   
					0.77   
					0.74   
					1.02   
					1.00   
					0.97   
					TC   
					TPC   
					0.66   
					0.64   
					0.62   
					0.86   
					0.84   
					0.81   
					10.6   
					10.9   
					11.2   
					13.3   
					13.6   
					14.0   
					11.0   
					11.2   
					11.6   
					13.7   
					14.0   
					14.4   
					12.4   
					12.7   
					13.0   
					15.5   
					15.8   
					16.2   
					0.81   
					0.80   
					0.78   
					1.06   
					1.04   
					1.02   
					MUZ-FD09NA   
					MUZ-FD12NA   
					9.6   
					10.0   
					11.8   
					12.0   
					12.4   
					10.2   
					10.7   
					NOTE : 1. IDB : Intake air dry-bulb temperature   
					TC : Total Capacity (x103 Btu/h)   
					TPC : Total Power Consumption (kW)   
					2. Above data is for heating operation without any frost.   
					How to operate with fixed operational frequency of the compressor.   
					1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL   
					mode or EMERGENCY HEAT mode before starting to operate the air conditioner.   
					2. The compressor starts with operational frequency.   
					3. The fan speed of the indoor unit is High.   
					4. This operation continues for 30 minutes.   
					5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on   
					the remote controller.   
					9 
				7-2. PERFORMANCE CURVE   
					Cooling   
					MUZ-FD12NA   
					MUZ-FD09NA   
					SHF at rating condition = 0.76   
					SHF at rating condition = 0.73   
					= 307 CFM   
					= 350 CFM   
					Airflow   
					Airflow   
					Indoor   
					15   
					14   
					13   
					13   
					12   
					11   
					10   
					9 
					intak   
					Indoor intak   
					e air WB temperat   
					e air WB te   
					mperature (°F   
					ure   
					(°F)   
					12   
					11   
					10   
					9 
					) 
					71   
					67   
					63   
					71   
					67   
					63   
					8 
					7 
					1.2   
					1.1   
					1.0   
					0.9   
					0.8   
					0.7   
					71   
					67   
					63   
					rature (°F)   
					mpe   
					71   
					67   
					63   
					ure (°F)   
					0.7   
					0.6   
					0.5   
					mperat   
					WB te   
					WB te   
					e air   
					oor intak   
					Ind   
					oor intake air   
					Ind   
					65   
					75   
					85   
					95   
					105   
					115   
					65   
					75   
					85   
					95   
					105   
					115   
					Outdoor intake air DB temperature (°F)   
					Outdoor intake air DB temperature (°F)   
					Heating   
					MUZ-FD12NA   
					MUZ-FD09NA   
					= 381 CFM   
					65 70   
					75   
					Airflow   
					= 420 CFM   
					Airflow   
					20   
					18   
					12   
					10   
					65   
					70   
					75   
					16   
					14   
					12   
					8 
					6 
					10   
					8 
					6 
					75   
					70   
					65   
					1.1   
					1.0   
					0.9   
					0.8   
					0.6   
					0.4   
					75   
					70   
					65   
					0.8   
					0.7   
					0.6   
					15   
					25   
					35   
					45   
					55   
					15   
					25   
					35   
					45   
					55   
					Outdoor intake air WB temperature (°F)   
					Outdoor intake air WB temperature (°F)   
					This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships   
					between frequency and capacity.   
					10   
				7-3. CONDENSING PRESSURE   
					Cooling   
					Data is based on the condition of indoor humidity 50 %.   
					Air flow should be set to High speed.   
					MUZ-FD09NA   
					(PSIG)   
					580   
					540   
					500   
					(PSIG)   
					180   
					175   
					170   
					165   
					160   
					155   
					150   
					145   
					140   
					135   
					130   
					125   
					120   
					86   
					80   
					460   
					86   
					80   
					75   
					420   
					70   
					380   
					75   
					70   
					340   
					300   
					260   
					68 70   
					75   
					80   
					85   
					90   
					95   
					100 105(°F)   
					68 70   
					75   
					80   
					85   
					90   
					95   
					100 105(°F)   
					Outdoor ambient temperature   
					Outdoor ambient temperature   
					MUZ-FD12NA   
					(PSIG)   
					580   
					540   
					500   
					460   
					420   
					380   
					340   
					300   
					(PSIG)   
					180   
					175   
					170   
					165   
					160   
					155   
					150   
					145   
					140   
					135   
					130   
					125   
					120   
					86   
					80   
					75   
					70   
					86   
					80   
					75   
					70   
					260   
					68 70   
					75   
					80   
					85   
					90   
					95   
					100 105(°F)   
					68 70   
					75   
					80   
					85   
					90   
					95   
					100 105(°F)   
					Outdoor ambient temperature   
					Outdoor ambient temperature   
					11   
				Heating   
					Data is based on the condition of outdoor humidity 75 %.   
					Air flow should be set to High speed.   
					Data is for heating operation without any frost.   
					MUZ-FD09NA   
					(PSIG)   
					400   
					(PSIG)   
					380   
					360   
					340   
					320   
					300   
					280   
					260   
					240   
					220   
					200   
					180   
					160   
					140   
					170   
					160   
					150   
					140   
					130   
					120   
					110   
					100   
					90   
					75   
					70   
					65   
					75   
					70   
					65   
					58Hz   
					58Hz   
					80   
					70   
					60   
					14   
					20 25 30 35 40 45 50 55 60 65 70(°F)   
					Outdoor ambient temperature   
					14 20 25 30 35 40 45 50 55 60 6570(°F)   
					Outdoor ambient temperature   
					MUZ-FD12NA   
					(PSIG)   
					400   
					(PSIG)   
					380   
					360   
					340   
					320   
					300   
					280   
					260   
					240   
					220   
					200   
					180   
					160   
					140   
					170   
					160   
					150   
					140   
					130   
					120   
					110   
					100   
					90   
					75   
					70   
					65   
					75   
					70   
					65   
					58Hz   
					58Hz   
					80   
					70   
					60   
					14   
					20 25 30 35 40 45 50 55 60 65 70(°F)   
					Outdoor ambient temperature   
					14 20 25 30 35 40 45 50 55 60 6570(°F)   
					Outdoor ambient temperature   
					12   
				7-4. STANDARD OPERATION DATA   
					Model   
					MSZ-FD09NA   
					MSZ-FD12NA   
					Item   
					Unit   
					Cooling   
					Heating   
					10,900   
					— 
					Cooling   
					Heating   
					13,600   
					— 
					Capacity   
					SHF   
					Btu/h   
					— 
					9,000   
					0.76   
					0.650   
					35   
					12,000   
					0.73   
					Input   
					kW   
					Hz   
					0.750   
					43   
					0.960   
					51   
					0.980   
					54   
					Rated frequency   
					Indoor unit   
					MSZ-FD09NA   
					MSZ-FD12NA   
					V,   
					phase,   
					Hz   
					Power supply   
					208/230 , 1 , 60   
					Input   
					kW   
					A 
					0.018   
					0.024   
					0.024   
					0.030   
					Fan motor current   
					Outdoor unit   
					0.19/0.17   
					0.25/0.23   
					0.25/0.23   
					0.32/0.29   
					MUZ-FD09NA   
					MUZ-FD12NA   
					V,   
					phase,   
					Hz   
					Power supply   
					208/230 , 1 , 60   
					Input   
					kW   
					A 
					0.632   
					0.726   
					0.936   
					0.950   
					Comp. current   
					2.96/2.68   
					3.39/3.06   
					4.40/3.97   
					4.43/4.01   
					Fan motor current   
					A 
					0.35/0.32   
					Condensing pressure   
					Suction pressure   
					PSIG   
					PSIG   
					˚F   
					376   
					154   
					143   
					112   
					51   
					355   
					108   
					144   
					108   
					46   
					402   
					148   
					161   
					117   
					51   
					392   
					104   
					159   
					115   
					45   
					Discharge temperature   
					Condensing temperature   
					Suction temperature   
					Comp. shell bottom temperature   
					Ref. pipe length   
					˚F   
					˚F   
					˚F   
					144   
					128   
					146   
					129   
					ft.   
					25   
					2 lb. 9 oz.   
					Refrigerant charge (R410A)   
					DB   
					Intake air temperature   
					WB   
					˚F   
					˚F   
					80   
					67   
					70   
					60   
					80   
					67   
					70   
					60   
					DB   
					Discharge air temperature   
					WB   
					˚F   
					59   
					100   
					— 
					56   
					105   
					— 
					˚F   
					56   
					54   
					Fan speed (High)   
					rpm   
					CFM   
					˚F   
					1,020   
					307 (Wet)   
					95   
					1,120   
					381   
					47   
					1,120   
					350 (Wet)   
					95   
					1,220   
					420   
					47   
					Airflow (High)   
					DB   
					Intake air temperature   
					WB   
					˚F   
					— 
					43   
					— 
					43   
					Fan speed   
					rpm   
					CFM   
					810   
					870   
					1,187   
					810   
					870   
					1,187   
					Airflow   
					1,102   
					1,102   
					13   
				7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY   
					MUZ-FD09NA   
					Correction of Cooling capacity   
					Correction of Cooling total input   
					Correction of Heating total input   
					Correction of Heating capacity   
					2.0   
					1.5   
					1.5   
					1.0   
					0.5   
					1.5   
					1.0   
					0.5   
					3.0   
					2.0   
					1.0   
					1.0   
					0.5   
					(Hz)   
					(Hz)   
					150   
					(Hz)   
					(Hz)   
					150   
					0 
					50   
					100   
					150   
					0 
					50   
					100   
					0 
					50   
					100   
					150   
					0 
					50   
					100   
					The operational frequency of compressor   
					The operational frequency of compressor The operational frequency of compressor   
					The operational frequency of compressor   
					MUZ-FD12NA   
					Correction of Cooling capacity   
					1.5   
					Correction of Cooling total input   
					Correction of Heating capacity   
					Correction of Heating total input   
					1.5   
					1.0   
					0.5   
					1.5   
					1.0   
					0.5   
					2.0   
					1.0   
					0.5   
					1.0   
					(Hz)   
					(Hz)   
					150   
					(Hz)   
					(Hz)   
					150   
					0 
					50   
					100   
					150   
					0 
					50   
					100   
					0 
					50   
					100   
					150   
					0 
					50   
					100   
					The operational frequency of compressor   
					The operational frequency of compressor The operational frequency of compressor   
					The operational frequency of compressor   
					7-6. TEST RUN OPERATION (How to operate fixed-frequency operation)   
					1. Press EMERGENCY OPERATION switch to COOL or HEAT mode (COOL : Press once, HEAT : Press twice).   
					2. Test run operation starts and continues to operate for 30 minutes.   
					3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.   
					4. Indoor fan operates at High speed.   
					5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor   
					varies).   
					6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on   
					remote controller.   
					14   
				8 
					ACTUATOR CONTROL   
					MUZ-FD09NA   
					MUZ-FD12NA   
					8-1. OUTDOOR FAN MOTOR CONTROL   
					The fan motor turns ON/OFF, interlocking with the compressor.   
					[ON] The fan motor turns ON 5 seconds before the compressor starts up.   
					[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.   
					5 seconds   
					15 seconds   
					ON   
					Compressor   
					OFF   
					ON   
					Outdoor fan   
					motor   
					OFF   
					8-2. R.V. COIL CONTROL   
					. . . . . . . . . . . . . . . . .   
					. . . . . . . . . . . . . . . . .   
					Heating   
					Cooling   
					ON   
					OFF   
					OFF   
					. . . . . . . . . . . . . . . . . . . .   
					Dry   
					NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.   
					<COOL>   
					<HEAT>   
					5 seconds   
					5 seconds   
					ON   
					OFF   
					Compressor   
					R.V.coil   
					ON   
					OFF   
					ON   
					OFF   
					Outdoor fan   
					motor   
					8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR   
					Actuator   
					Sensor   
					Purpose   
					Outdoor   
					fan motor   
					Indoor fan   
					motor   
					Compressor   
					LEV   
					R.V. coil   
					Discharge temperature thermistor   
					Indoor coil temperature thermistor   
					Protection   
					○ ○   
					Cooling : Coil frost prevention   
					Heating : High pressure protection   
					Cooling : High pressure protection   
					Heating : Defrosting   
					○ 
					○ ○   
					○ ○   
					○ ○ ○ ○ ○   
					Defrost thermistor   
					Fin temperature thermistor   
					Protection   
					○ 
					○ 
					Outdoor heat exchanger temperature thermistor   
					Ambient temperature thermistor   
					High pressure protection   
					Low ambient temperature operation   
					○ ○ ○   
					○ ○ ○   
					15   
				9 
					SERVICE FUNCTIONS   
					MUZ-FD09VA   
					MUZ-FD12VA   
					9-1. CHANGE IN DEFROST SETTING   
					Changing defrost finish temperature   
					<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board.   
					(Refer to 10-6-1.)   
					Jumper   
					Defrost finish temperature   
					41 °F (5 °C)   
					Soldered   
					(Initial setting)   
					JS   
					None   
					(Cut)   
					50 °F (10 °C)   
					9-2. PRE-HEAT CONTROL SETTING   
					PRE-HEAT CONTROL   
					When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside tempera-   
					ture. The pre-heat control prevents this interference. The pre-heat control turns ON when outside temperature is 68 °F (20   
					°C) or below. When pre-heat control is turned ON, compressor is energized. (about 50 W)   
					<JK> To activate the pre-heat control, cut the JK wire of the inverter P.C. board. (Refer to 10-6.1)   
					NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.   
					10   
					TROUBLESHOOTING   
					MUZ-FD09NA MUZ-FD12NA   
					10-1. CAUTIONS ON TROUBLESHOOTING   
					1. Before troubleshooting, check the following   
					1) Check the power supply voltage.   
					2) Check the indoor/outdoor connecting wire for miswiring.   
					2. Take care of the following during servicing   
					1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after con-   
					firming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.   
					2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic   
					control P.C. board.   
					3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.   
					4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the   
					components.   
					5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.   
					Lead wiring   
					Housing point   
					3. Troubleshooting procedure   
					1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.   
					To make sure, check how many times the abnormality indication is flashing on and off before starting service work.   
					2) Before servicing check that the connector and terminal are connected properly.   
					3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the   
					components for bursting and discoloration.   
					4) Refer to 10-2. and 10-3.   
					16   
				10-2. FAILURE MODE RECALL FUNCTION   
					Outline of the function   
					This air conditioner can memorize the abnormal condition which has occurred once.   
					Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details   
					can be recalled.   
					This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.   
					1. Flow chart of failure mode recall function for the indoor/outdoor unit   
					Operational procedure   
					The cause of abnormality cannot be found because the abnormality doesn't recur.   
					Setting up the failure mode recall function   
					Turn ON the power supply.   
					<Preparation of the remote controller>   
					While pressing both OPERATION SELECT button and TOO COOL button on the   
					remote controller at the same time, press RESET button.   
					First, release RESET button.   
					And release the other two buttons after all LCD in operation display section of the   
					remote controller is displayed after 3 seconds.   
					1. Regardless of normal or ab-   
					normal condition, a short beep   
					is emitted once the signal is   
					received.   
					Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is   
					displayed) with the remote controller headed towards the indoor unit.   
					1 
					Does POWER lamp on the indoor unit blink at the interval of   
					Indoor unit is normal.   
					0.5 seconds?   
					But the outdoor unit might be abnormal because there are some abnor-   
					malities that can't be recalled with this way.   
					Confirm if outdoor unit is abnormal according to the detailed outdoor   
					unit failure mode recall function. (Refer to 10-2.2)   
					Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-   
					No   
					(OFF)   
					ted at the same timing as the blinking of POWER lamp.   
					2 
					Yes   
					(Blinks)   
					Judgment of indoor/outdoor abnormality   
					Before blinking, does POWER lamp stay ON for 3 seconds?   
					Stays ON for 3 seconds (without beep):   
					The outdoor unit is abnormal.   
					Yes   
					No   
					The indoor unit is abnormal.   
					The outdoor unit is abnormal.   
					Check the blinking pattern, and confirm the abnormal point with the indoor unit   
					failure mode table. (Refer to indoor unit service manual.)   
					Check the blinking pattern, and confirm the abnormal point with the   
					outdoor unit failure mode table. (Refer to 10-2.3)   
					Make sure to check at least two consecutive blinking cycles.   
					2 
					Make sure to check at least two consecutive blinking cycles.   
					3 
					Releasing the failure mode recall function   
					Release the failure mode recall function by the following procedures.   
					Turn OFF the power supply and turn it ON again.   
					Press RESET button of the remote controller.   
					Repair the defective parts.   
					Deleting the memorized abnormal condition   
					After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall   
					function" mentioned above.   
					Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)   
					with the remote controller headed towards the indoor unit.   
					Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.   
					Release the failure mode recall function according to "Releasing the failure mode recall function"   
					mentioned above.   
					NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.   
					2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.   
					2. Blinking pattern when the indoor unit is abnormal:   
					Blinking at 0.5-   
					second interval   
					Blinking at 0.5-   
					second interval   
					2.5-second OFF   
					2.5-second OFF   
					ON   
					OFF   
					Beeps   
					Beeps   
					Beeps   
					Repeated cycle   
					Repeated cycle   
					Repeated cycle   
					3.Blinking pattern when the outdoor unit is abnormal:   
					Blinking at 0.5-   
					second interval   
					Blinking at 0.5-   
					2.5-second OFF   
					3-second ON   
					second interval   
					2.5-second OFF   
					3-second ON   
					ON   
					OFF   
					No beep   
					Beeps   
					No beep   
					Beeps   
					Repeated cycle   
					Repeated cycle   
					Repeated cycle   
					17   
				2. Flow chart of the detailed outdoor unit failure mode recall function   
					Operational procedure   
					The outdoor unit might be abnormal.   
					Confirm if outdoor unit is abnormal according to the following procedures.   
					Confirm that the remote controller is in the failure mode recall function.   
					With the remote controller headed towards the indoor unit, press TOO   
					COOL or TOO WARM button to adjust the set temperature to 77 ˚F (25 ˚C).   
					1 
					1. Regardless of normal or abnormal condition, 2 short   
					beeps are emitted as the signal is received.   
					Does POWER lamp on the indoor unit blink at the   
					interval of 0.5 seconds?   
					Blinks: The outdoor unit is abnormal. Beep is emitted   
					No   
					at the same timing as the blinking of POWER   
					(OFF)   
					lamp.   
					2 
					Yes   
					(Blinks   
					) 
					The outdoor unit is abnormal.   
					Check the blinking pattern, and confirm the abnormal point with the out-   
					door unit failure mode table (10-2.3.).   
					The outdoor unit is normal.   
					Make sure to check at least two consecutive blinking cycles.   
					2 
					Releasing the failure mode recall function   
					Release the failure mode recall function by the following procedures.   
					Turn OFF the power supply and turn it ON again.   
					Press RESET button of the remote controller.   
					Release the failure mode recall function accord-   
					ing to the left mentioned procedure.   
					Repair the defective parts.   
					Deleting the memorized abnormal condition   
					After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall   
					function" (10-2.1.).   
					Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with   
					the remote controller headed towards the indoor unit.   
					Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.   
					Release the failure mode recall function according to "Releasing the failure mode recall function" men-   
					tioned above.   
					NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.   
					2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.   
					2.Blinking pattern when outdoor unit is abnormal:   
					Blinking at 0.5-   
					second interval   
					Blinking at 0.5-   
					second interval   
					2.5-second OFF   
					3-second ON   
					2.5-second OFF   
					3-second ON   
					ON   
					OFF   
					No beep   
					Repeated cycle   
					Beeps   
					No beep   
					Repeated cycle   
					Beeps   
					Repeated cycle   
					18   
				3. Outdoor unit failure mode table   
					Indoor/outdoor   
					unit failure   
					mode recall   
					function   
					Outdoor unit   
					failure mode   
					recall function   
					POWER lamp   
					(Indoor unit)   
					Abnormal point   
					LED indication   
					Condition   
					Correspondence   
					(Failure mode / protection) (Outdoor P.C. board)   
					OFF   
					None (Normal)   
					— 
					— 
					— 
					— 
					— 
					2-time flash   
					2.5 seconds   
					OFF   
					Outdoor power system   
					Overcurrent protection stop is   
					•Reconnect connectors.   
					continuously performed 3 times within •Refer to 10-5. "How   
					1 minute after the compressor gets   
					started.   
					to check inverter/   
					compressor".   
					•Check stop valve.   
					— 
					○ 
					○ 
					3-time flash   
					Discharge temperature   
					1-time flash every   
					Thermistor shorts or opens during   
					compressor running.   
					•Refer to 10-5.   
					2.5 seconds thermistor   
					OFF   
					2.5 seconds   
					"Check of outdoor   
					thermistors".   
					Defrost thermistor   
					Defective outdoor   
					thermistors can be   
					identified by checking   
					the blinking pattern of   
					LED.   
					Fin temperature thermistor   
					3-time flash   
					2.5 seconds OFF   
					○ 
					○ 
					P.C. board temperature   
					thermistor   
					4-time flash   
					2.5 seconds OFF   
					Ambient temperature   
					thermistor   
					2-time flash   
					2.5 seconds OFF   
					4-time flash   
					2.5 seconds   
					OFF   
					Overcurrent   
					11-time flash   
					Large current flows into intelligent   
					•Reconnect compressor   
					connector.   
					2.5 seconds OFF   
					power module.   
					•Refer to 10-5. "How   
					to check inverter/   
					compressor".   
					— 
					— 
					○ 
					○ 
					•Check stop valve.   
					Compressor synchronous   
					abnormality (Compressor   
					start-up failure protection)   
					12-time flash   
					2.5 seconds OFF   
					Waveform of compressor current is   
					distorted.   
					•Reconnect compressor   
					connector.   
					•Refer to 10-5. "How   
					to check inverter/   
					compressor".   
					5-time flash   
					2.5 seconds   
					OFF   
					Discharge temperature   
					Temperature of discharge temperature •Check refrigerant   
					thermistor exceeds 241 °F (116 °C),   
					compressor stops.   
					circuit and refrigerant   
					amount.   
					Compressor can restart if discharge   
					temperature thermistor reads 212 °F   
					(100 °C) or less 3 minutes later.   
					•Refer to 10-5. "Check   
					of LEV".   
					— 
					— 
					— 
					— 
					○ 
					6-time flash   
					2.5 seconds   
					OFF   
					High pressure   
					Temperature of indoor coil thermistor •Check refrigerant   
					exceeds 158 °F (70 °C) in HEAT mode. circuit and refrigerant   
					Temperature of defrost thermistor   
					exceeds 158 °F (70 °C) in COOL   
					mode.   
					amount.   
					•Check stop valve.   
					○ 
					○ 
					7-time flash   
					Fin temperature/ P.C. board   
					7-time flash   
					2.5 seconds OFF   
					Temperature of fin temperature   
					•Check around outdoor   
					unit.   
					2.5 seconds temperature   
					OFF   
					thermistor on the inverter P.C. board   
					exceeds 167 ~ 176 °F (75 ~ 80 °C), or •Check outdoor unit air   
					temperature of P.C. board temperature passage.   
					thermistor on the inverter P.C. board   
					exceeds 158 ~ 167 °F (70 ~ 75 °C).   
					— 
					— 
					•Refer to 10-5. "Check   
					of outdoor fan motor".   
					8-time flash   
					2.5 seconds   
					OFF   
					Outdoor fan motor   
					Outdoor fan has stopped 3 times in a •Refer to 10-5. "Check   
					row within 30 seconds after outdoor   
					fan start-up.   
					of outdoor fan motor".   
					Refer to 10-5. "Check   
					of inverter P.C. board".   
					— 
					○ 
					○ 
					9-time flash   
					2.5 seconds   
					OFF   
					Nonvolatile memory data   
					5-time flash   
					2.5 seconds OFF   
					Nonvolatile memory data cannot be   
					read properly.   
					•Replace the inverter   
					P.C. board.   
					○ 
					10-time flash Discharge temperature   
					2.5 seconds   
					OFF   
					Temperature of discharge temperature •Refer to 10-5. "Check   
					thermistor has been 122 °F (50 °C) or of LEV".   
					— 
					less for 20 minutes.   
					•Check refrigerant   
					circuit and refrigerant   
					amount.   
					— 
					○ 
					○ 
					11-time flash DC voltage   
					8-time flash   
					DC voltage of inverter cannot be   
					detected normally.   
					•Refer to 10-5. "How   
					to check inverter/   
					compressor".   
					2.5 seconds   
					2.5 seconds OFF   
					OFF   
					— 
					Each phase current of   
					9-time flash   
					2.5 seconds OFF   
					Each phase current of compressor   
					cannot be detected normally.   
					compressor   
					12-time flash Overcurrent Compressor   
					2.5 seconds open-phase   
					OFF   
					10-time flash   
					2.5 seconds OFF   
					Large current flows into intelligent   
					power module (IPM).   
					The open-phase operation of   
					compressor is detected.   
					•Reconnect compressor   
					connector.   
					•Refer to 10-5. "How   
					to check inverter/   
					— 
					The interphase short out occurs in the compressor".   
					output of the intelligent power module   
					(IPM).   
					○ 
					○ 
					The compressor winding shorts out.   
					14-time flash Stop valve (Closed valve)   
					2.5 seconds   
					OFF   
					14-time flash   
					2.5 seconds OFF   
					Closed valve is detected by   
					compressor current.   
					•Check stop valve   
					○ 
					NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).   
					19   
				10-3. TROUBLESHOOTING CHECK TABLE   
					Abnormal point/   
					Condition   
					No.   
					Symptom   
					LED indication   
					Condition   
					Correspondence   
					Outdoor unit 1-time flash every Outdoor power sys- Overcurrent protection stop is continuously performed 3 times •Reconnect connector of compres-   
					does not oper- 2.5 seconds   
					ate.   
					tem   
					within 1 minute after the compressor gets started, or failure of sor.   
					restart of compressor has repeated 24 times.   
					1 
					•Refer to 10-5. "How to check in-   
					verter/ compressor".   
					•Check stop valve.   
					Outdoor thermistors Discharge temperature thermistor, fin temperature thermistor, •Refer to 10-5. "Check of outdoor   
					defrost thermistor, P.C. board temperature thermistor or ambi- thermistors".   
					ent temperature thermistor shorts or opens during compressor   
					running.   
					2 
					3 
					Outdoor control sys- Nonvolatile memory data cannot be read properly.   
					tem   
					•Replace inverter P.C. board.   
					(POWER lamp of the indoor unit lights up or flashes 7-time.)   
					6-time flash   
					Serial signal   
					Stop valve/   
					The communication fails between the indoor and outdoor unit •Refer to 10-5. "How to check   
					4 
					5 
					2.5 seconds OFF   
					for 3 minutes.   
					miswiring and serial signal error.   
					11-time flash   
					Closed valve is detected by compressor current.   
					•Check stop valve.   
					2.5 seconds OFF Closed valve   
					14-time flash Outdoor unit   
					2.5 seconds OFF (Other abnormality)   
					Outdoor unit is defective.   
					•Refer to 10-2.2. "Flow chart of the   
					detailed outdoor unit failure mode   
					recall function".   
					6 
					7 
					'Outdoor unit 2-time flash   
					Overcurrent protec- Large current flows into intelligent power module.   
					•Reconnect connector of compres-   
					stops and   
					2.5 seconds OFF tion   
					When overcurrent protection occurs within 10 seconds after sor.   
					restarts 3 min-   
					utes later' is   
					repeated.   
					compressor starts, compressor restarts after 15 seconds. •Refer to 10-5. "How to check in-   
					verter/compressor".   
					•Check stop valve.   
					3-time flash   
					Discharge tempera- Temperature of discharge temperature thermistor exceeds 241 •Check refrigerant circuit and refrig-   
					2.5 seconds OFF ture overheat protec- °F (116 °C), compressor stops. Compressor can restart if dis- erant amount.   
					8 
					9 
					tion   
					charge temperature thermistor reads 212 °F (100 °C) or less 3 •Refer to 10-5. "Check of LEV".   
					minutes later.   
					4-time flash   
					Fin temperature /P.C. Temperature of fin temperature thermistor on the heat sink ex- •Check around outdoor unit.   
					ceeds 167 ~ 176 °F (75 ~ 80 °C) or temperature of P.C. board •Check outdoor unit air passage.   
					2.5 seconds OFF board temperature   
					thermistor overheat temperature thermistor on the inverter P.C. board exceeds 158 •Refer to 10-5. "Check of outdoor   
					protection   
					~ 167 °F (70 ~ 75 °C).   
					fan motor".   
					5-time flash   
					High pressure pro-   
					Indoor coil thermistor exceeds 158 °F (70 °C) in HEAT mode. •Check refrigerant circuit and refrig-   
					10   
					11   
					2.5 seconds OFF tection   
					Defrost thermistor exceeds 158 °F (70 °C) in COOL mode.   
					erant amount.   
					•Check stop valve.   
					8-time flash   
					2.5 seconds OFF chronous abnormal-   
					ity   
					Compressor syn-   
					The waveform of compressor current is distorted.   
					•Reconnect connector of compres-   
					sor.   
					•Refer to 10-5. "How to check in-   
					verter/compressor".   
					10-time flash   
					2.5 seconds OFF   
					Outdoor fan motor   
					Outdoor fan has stopped 3 times in a row within 30 seconds   
					after outdoor fan start-up.   
					•Refer to 10-5. "Check of outdoor   
					fan motor.   
					•Refer to 10-5. "Check of inverter   
					P.C. board.   
					12   
					12-time flash   
					Each phase current Each phase current of compressor cannot be detected nor-   
					•Refer to 10-5. "How to check in-   
					verter/compressor".   
					13   
					14   
					15   
					2.5 seconds OFF of compressor   
					mally   
					13-time flash   
					2.5 seconds OFF   
					DC voltage   
					DC voltage of inverter cannot be detected normally.   
					•Refer to 10-5. "How to check in-   
					verter/compressor".   
					Outdoor unit 1-time flash   
					operates. 2.5 seconds OFF current protection   
					Frequency drop by Current from power outlet reaches the protection current, and The unit is normal, but check the   
					compressor frequency lowers.   
					following.   
					•Check if indoor filters are clogged.   
					•Check if refrigerant is short.   
					•Check if indoor/outdoor unit air cir-   
					culation is short cycled.   
					3-time flash   
					Frequency drop by Temperature of indoor coil thermistor exceeds 131 °F (55 °C)   
					2.5 seconds OFF high pressure pro-   
					tection   
					in HEAT mode, compressor frequency lowers.   
					16   
					17   
					Frequency drop by Indoor coil thermistor reads 46 °F (8 °C) or less in COOL   
					defrosting in COOL mode, compressor frequency lowers.   
					mode   
					4-time flash   
					Frequency drop by Temperature of discharge temperature thermistor exceeds 232 •Check refrigerant circuit and refrig-   
					2.5 seconds OFF discharge tempera- °F (111 °C), compressor frequency lowers.   
					ture protection   
					erant amount.   
					•Refer to 10-5. "Check of LEV".   
					•Refer to 10-5. "Check of outdoor   
					thermistors".   
					NOTE: 1. The location of LED is illustrated at the right figure. Refer to 10-6.1.   
					Inverter P.C. board(Parts side)   
					2. LED is lighted during normal operation.   
					The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF. Flashing   
					(Example) When the flashing frequency is “2”.   
					LED   
					Flashing →   
					0.5-second ON   
					0.5-second ON   
					2.5-second OFF   
					ON   
					2.5-second OFF   
					OFF   
					20   
				Abnormal point/   
					Condition   
					No.   
					18   
					Symptom   
					LED indication   
					Condition   
					Correspondence   
					Outdoor unit 7-time flash   
					Low discharge tem- Temperature of discharge temperature thermistor has been   
					operates. 2.5 seconds OFF perature protection 122 °F (50 °C) or less for 20 minutes.   
					•Refer to 10-5. "Check of LEV".   
					•Check refrigerant circuit and refrig-   
					erant amount.   
					8-time flash   
					PAM protection PAM: The overcurrent flows into IGBT (Insulated Gate Bipolar tran- This is not malfunction. PAM protec-   
					2.5 seconds OFF Pulse Amplitude   
					Modulation   
					sistor : TR821) or when the bus-bar voltage reaches 320 V or tion will be activated in the following   
					more, PAM stops and restarts.   
					cases;   
					19   
					20   
					1 Instantaneous power voltage drop   
					(Short time power failure)   
					2 When the power supply voltage is   
					high.   
					9-time flash   
					2.5 seconds OFF   
					Inverter check mode The connector of compressor is disconnected, inverter check •Check if the connector of the com-   
					mode starts.   
					pressor is correctly connected.   
					Refer to 10-5. "How to check   
					inverter/ compressor".   
					21   
				10-4. TROUBLE CRITERION OF MAIN PARTS   
					MUZ-FD09NA MUZ-FD12NA   
					Part name   
					Check method and criterion   
					Figure   
					Defrost thermistor   
					(RT61)   
					Measure the resistance with a tester.   
					Ambient temperature   
					thermistor (RT65)   
					Refer to 10-6. “Test point diagram and voltage”,1. “Inverter P.C.   
					board”, the chart of thermistor.   
					Outdoor heat ex-   
					changer temperature   
					thermistor (RT68)   
					Discharge tem-   
					perature thermistor   
					(RT62)   
					Measure the resistance with a tester. Before measurement, hold the   
					thermistor with your hands to warm it up.   
					Refer to 10-6. “Test point diagram and voltage”,1. “Inverter P.C.   
					board”, the chart of thermistor.   
					Fin temperature   
					thermistor (RT64)   
					Measure the resistance between terminals using a tester.   
					(Winding temperature : -4 ~ 104 °F (-20 ~ 40 °C))   
					WHT   
					2 
					RED BLK   
					3 
					1 
					W 
					Normal   
					U-V   
					U-W   
					V-W   
					Compressor   
					1.52 ~ 2.17 Ω   
					V 
					U 
					Measure the resistance between lead wires using a tester.   
					(Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))   
					WHT   
					RED BLK   
					2 
					3 
					1 
					Color of lead wire   
					Normal   
					Outdoor fan motor   
					R. V. coil (21S4)   
					W 
					RED – BLK   
					BLK – WHT   
					WHT – RED   
					11 ~ 16 Ω   
					V 
					U 
					Measure the resistance using a tester.   
					(Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))   
					Normal   
					970 ~ 1380 Ω   
					Measure the resistance using a tester.   
					(Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))   
					WHT   
					RED   
					ORN   
					LEV   
					Color of lead wire   
					WHT – RED   
					RED – ORN   
					YLW – BRN   
					BRN – BLU   
					Normal   
					Expansion valve coil   
					(LEV)   
					37 ~ 54 Ω   
					22   
				10-5. TROUBLESHOOTING FLOW   
					POWER lamp flashes 5-times.   
					Outdoor unit does not operate.   
					A How to check inverter/ compressor   
					Disconnect the connector (CN61) between   
					compressor and the intelligent power module   
					(IPM).   
					See 10-5. “Check of open phase”.   
					Replace the inverter P.C. board.   
					See 10-5. “Check of compressor”.   
					Check the voltage between terminals.   
					Are the voltages balanced?   
					Yes   
					No   
					Check the compressor.   
					B Check of open phase   
					●With the connector between the compressor and the intelligent power module disconnected,   
					activate the inverter and check if the inverter is normal by measuring the balance of voltage   
					between the terminals.   
					Output voltage 115 V   
					<< Operation method>>   
					Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the   
					indoor unit. (TEST RUN OPERATION : Refer to 7-6.)   
					<<Measurement point>>   
					at 3 points   
					BLK (U)-WHT (V)   
					BLK (U)-RED (W)   
					WHT(V)-RED (W)   
					9-time flash   
					Measure AC voltage between the   
					lead wires at 3 points.   
					2.5-second OFF   
					NOTE: 1. Output voltage varies according to power supply voltage.   
					2. Measure the voltage by analog type tester.   
					3. During this check, LED of the inverter P.C. board flashes 9 times. (Refer to 10-6.1.)   
					C Check of compressor   
					Refer to 10-5. “Check of compressor   
					winding”.   
					Is the compressor normal?   
					Replace the compressor.   
					No   
					No   
					Yes   
					Refer to 10-5. “Check of compressor   
					operation time”.   
					Does the compressor operate continuously?   
					Refer to 10-5. “Check of compressor start failure”.   
					Yes   
					OK.   
					23   
				D Check of compressor winding   
					●Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between   
					the compressor terminals.   
					<<Measurement point>>   
					at 3 points   
					BLK-WHT   
					BLK-RED   
					Measure the resistance between the lead wires at 3 points.   
					WHT-RED   
					<<Judgement>>   
					Refer to 10-4.   
					0[Ω] ················Abnormal [short]   
					Infinite[Ω] ·······Abnormal [open]   
					NOTE: Be sure to zero the ohmmeter before measurement.   
					E Check of compressor operation time   
					<<Judgement>>   
					0 second   
					●Connect the compressor and activate the inverter. Then measure   
					the time until the inverter stops due to over current.   
					<<Operation method>>   
					Start heating or cooling operation by pressing EMERGENCY   
					OPERATION switch on the indoor unit.   
					Compressor starts   
					1 second   
					Abnormal   
					(IPM failure)   
					(Compressor winding short)   
					2 seconds   
					(TEST RUN OPERATION : Refer to 7-6.)   
					<<Measurement>>   
					Measure the time from the start of compressor to the stop of   
					compressor due to overcurrent.   
					Abnormal   
					(Compressor lock out)   
					(Starting defect)   
					Abnormal   
					(Poor contact,)   
					(Outdoor P.C. board defect)   
					(Disconnected connector)   
					10 seconds   
					10 minutes   
					Abnormal   
					(Refrigerant circuit defect)   
					(Closed valve)   
					Normal   
					F Check of compressor start failure   
					Confirm that 1~4 is normal.   
					• Electrical circuit check   
					1.Contact of the compressor connector (including CN61)   
					2.Output voltage of inverter P.C. board and balance of them (See 10-5. )   
					3.Direct current voltage between DB61(+) and (-) on the inverter P.C. board   
					4.Voltage between outdoor terminal block S1-S2   
					Check the refrigerant circuit.   
					Check the stop valve.   
					Does the compressor run for 10 seconds or   
					more after it starts?   
					Yes   
					No   
					No   
					After the compressor is heated with a drier,   
					Replace the compressor.   
					does the compressor start?   
					1 
					Yes   
					1 
					Heat the compressor with   
					a drier for about 20 minutes.   
					Do not recover refrigerant   
					gas while heating.   
					Compressor start failure. Activate pre-heat control.   
					(Refer to 9-2. "PRE-HEAT CONTROL SETTING")   
					Heating part   
					24   
				POWER lamp flashes 6-time.   
					The thermistors in the outdoor unit are abnormal.   
					G Check of outdoor thermistors   
					Disconnect the connector of thermistor in the outdoor P.C. board (see   
					below table), and measure the resistance of thermistor.   
					Replace the thermistor except RT64. When RT64 is   
					abnormal, replace the inverter P.C. board.   
					Is the thermistor normal? (Refer to 10-6.1.)   
					No   
					Yes   
					Reconnect the connector of thermistor.   
					Turn ON the power supply and press EMERGENCY OPERATION switch.   
					Does the unit operate for 10 minutes or more   
					without showing thermistor abnormality?   
					Replace the inverter P.C. board.   
					No   
					Yes   
					OK.   
					(Cause is poor contact.)   
					Thermistor   
					Symbol   
					Connector, Pin No.   
					Board   
					Defrost   
					Discharge temperature   
					Fin temperature   
					RT61 Between CN641 pin1 and pin2   
					RT62 Between CN641 pin3 and pin4   
					RT64 Between CN642 pin1 and pin2   
					RT65 Between CN643 pin1 and pin2   
					Inverter P.C. board   
					Ambient temperature   
					Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3   
					H Check of R.V. coil   
					First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4.   
					In case CN721 is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector   
					although any signal is not being transmitted to R.V. coil.   
					Check if CN721 is connected.   
					Unit operates COOL mode even if it is set to HEAT mode.   
					Disconnect connector (CN61)   
					between the compressor and the   
					intelligent power module.   
					Turn ON the power supply and   
					press EMERGENCY OPERATION   
					switch twice (HEAT mode).   
					Is there 230 VAC between CN721 and   
					on the inverter P.C. board 3 minutes   
					after the power supply is turned ON?   
					Replace the inverter   
					P.C. board.   
					No   
					Yes   
					Replace the 4-way valve.   
					Unit operates HEAT mode even if it is set to COOL mode.   
					Disconnect connector (CN61)   
					between the compressor and the   
					intelligent power module.   
					Turn ON the power supply and   
					press EMERGENCY OPERATION   
					switch once (COOL mode).   
					Is there 230 VAC between CN721 and   
					on the inverter P.C. board 3 minutes   
					after the power supply is turned ON?   
					Replace the inverter   
					P.C. board.   
					Yes   
					No   
					Replace the 4-way valve.   
					25   
				Outdoor fan motor does not operate.   
					I Check of outdoor fan motor   
					Disconnect CN932 from the inverter P.C. board, and   
					measure the resistance of the outdoor fan motor.   
					Is the outdoor fan motor normal?   
					(Refer to 10-4.)   
					Replace the outdoor fan motor.   
					No   
					Yes   
					Replace the inverter P.C. board.   
					Inverter does not operate.   
					J Check of power supply   
					Disconnect the connector (CN61)   
					between compressor and intelligent   
					power module.   
					Turn ON power supply and press   
					EMERGENCY OPERATION switch.   
					Rectify indoor/ outdoor   
					connecting wire.   
					Yes   
					Is there voltage 208 / 230 VAC   
					between the indoor terminal   
					block S1 and S2?   
					Replace the indoor   
					electronic control P.C.   
					board.   
					Does POWER lamp on the indoor   
					unit light up?   
					No   
					No   
					No   
					Yes   
					Is there voltage 280 ~ 370 VDC   
					between DB61 (+) and DB61 (–) on   
					the inverter P.C. board?   
					Dose LED on the inverter P.C.   
					board light up or flash? (Refer   
					to 10-6.1.)   
					Replace the inverter   
					P.C. board.   
					Yes   
					(Refer to 10-6.1.)   
					Yes   
					No   
					280 ~ 370 VDC   
					If light up, OK.   
					If flash, refer to 10-3.   
					Check the electric parts in main circuit.   
					DB61   
					Inverter P.C. board   
					(Solder side)   
					26   
				Heating/Cooling does not work sufficiently.   
					K Check of LEV (Expansion valve)   
					Turn ON the power supply.   
					<Preparation of the remote controller>   
					While pressing both OPERATION SELECT button   
					and TOO COOL button on the remote controller at the   
					same time, press RESET button.   
					First, release RESET button.   
					And release the other two buttons after all LCD except   
					the set temperature in operation display ection of the   
					remote controller is displayed after 3 seconds.   
					Press OPERATE/STOP (ON/OFF) button of the remote   
					controller (the set temperature is displayed) with the   
					remote controller headed towards the indoor unit.   
					1 
					1. Regardless of normal or abnormal condition, a short beep   
					is emitted once the signal is received.   
					Expansion valve operates in full-opening direction.   
					Do you hear the expansion valve "click,   
					click·······"?   
					OK.   
					Do you feel the expansion valve vibrate   
					Yes   
					on touching it ?   
					No   
					Is LEV coil properly fixed to   
					the expansion valve?   
					Properly fix the LEV coil to the expansion valve.   
					No   
					Yes   
					Measure each voltage between connector   
					pins of CN724 on the inverter P.C. board.   
					1.Pin (-) — Pin (+)   
					2.Pin (-) — Pin (+)   
					Does the resistance of LEV   
					coil have the characteristics?   
					(Refer to 10-4.)   
					Replace the inverter P.C.   
					board.   
					3.Pin (-) — Pin (+)   
					4.Pin (-) — Pin (+)   
					Is there about 3 ~ 5 VAC between each?   
					NOTE: Measure the voltage by an analog   
					tester.   
					Yes   
					No   
					No   
					Replace the LEV coil.   
					Yes   
					Replace the expansion valve.   
					NOTE : After check of LEV, do the undermentioned operations.   
					1. Turn OFF the power supply and turn ON it again.   
					2. Press RESET button on the remote controller.   
					27   
				Outdoor fan motor does not operate, or stops immediately after starting up.   
					L Check of inverter P.C. board   
					Check the outdoor fan motor.   
					(Refer to10-5. .)   
					Is the fuse (F901) blown on the in-   
					verter P.C. board?   
					Yes   
					No   
					Inverter P.C. board   
					(Solder side)   
					Check the connection of the connectors   
					(CN932) of the outdoor fan motor.   
					If the connection is poor, make it correct.   
					CN932   
					Operate the outdoor unit by starting   
					EMERGENCY OPERATION.   
					Check the corresponding parts   
					following LED indication.   
					(Refer to 10-3.)   
					Check the LED indication on the in-   
					verter P.C. board.   
					Does the LED flash 10-time?   
					No   
					Yes   
					(10-time flash)   
					Replace the inverter P.C. board.   
					28   
				• Unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.   
					Indoor unit does not operate.   
					• POWER lamp flashes ON and OFF in every 0.5 seconds.   
					Outdoor unit doesn’t operate.   
					M How to check miswiring and serial signal error (outdoor unit does not work)   
					Turn OFF the power supply.   
					Is there rated voltage in the   
					Check the power supply.   
					power supply?   
					No   
					No   
					Yes   
					Turn ON the power supply.   
					Is there rated voltage between   
					outdoor terminal block S1 and   
					S2?   
					Yes   
					Check the wiring.   
					Press EMERGENCY OPERATION switch once.   
					Does AREA-L lamp light up? <Confirmation of   
					the power to the indoor unit>   
					No   
					No   
					Yes   
					Is there any miswiring,   
					poor contact, or wire   
					disconnection of the   
					indoor/outdoor connect-   
					ing wire?   
					Is serial signal error indicated 6 minutes later?   
					Yes   
					Correct them.   
					Yes   
					No   
					A 
					Turn OFF the power supply.   
					Check once more if the indoor/outdoor   
					connecting wire is not miswiring.   
					B 
					1. Miswiring may damage indoor electronic control P.C.   
					board during the operation.   
					Be sure to confirm the wiring is correct before the opera-   
					tion starts.   
					Short-circuit outdoor terminal block S2   
					and S3.   
					1 
					3. Be sure to check this within 3 minutes after turning ON.   
					After 3 minutes, LED blinks 6 times. Even when the   
					inverter P.C. board or the outdoor electronic control P.C.   
					board is normal, LED blinks 6 times after 3 minutes.   
					Turn ON the power supply.   
					Does the LED on the inverter P.C. board or   
					the outdoor electronic control P.C. board   
					repeat "3.6-second-OFF and 0.8-second-   
					Replace the inverter P.C. board or the out-   
					door electronic control P.C. board.   
					2 
					No   
					(Lighted   
					or not   
					ON quick blinking"?   
					3 
					2. Be careful to the residual   
					voltage of smoothing capacitor.   
					Yes   
					lighted)   
					Turn OFF the power supply.   
					Remove the short-circuit between   
					outdoor terminal block S2 and S3.   
					Turn ON the power supply.   
					Is there amplitude of 10 to 20 VDC   
					between outdoor terminal block S2 and   
					S3? <Confirmation of serial signal>   
					Yes   
					Is there any error of the in-   
					Replace the indoor/   
					outdoor connecting   
					wire.   
					door/outdoor connecting wire,   
					such as the damage of the wire,   
					intermediate connection, poor   
					contact to the terminal block?   
					No   
					A 
					No   
					Yes   
					• Turn OFF inverter-controlled lighting   
					equipment.   
					• Turn OFF the power supply and then   
					turn ON again.   
					• Press EMERGENCY OPERATION   
					switch.   
					Is there any error of the in-   
					door/outdoor connecting wire,   
					such as the damage of the wire,   
					intermediate connection, poor   
					contact to the terminal block?   
					No   
					Is there rated voltage between   
					indoor terminal block S1 and S2?   
					<Confirmation of power voltage>   
					Replace the indoor/   
					outdoor connecting   
					wire.   
					• Reinstall   
					No   
					Yes   
					either the unit   
					or the light   
					each other   
					Yes   
					away.   
					Is serial signal   
					error indicated 6   
					minutes later?   
					• Attach a filter   
					on remote   
					control receiv-   
					ing section   
					of the indoor   
					unit.   
					No   
					Yes   
					Replace the indoor electronic control P.C. board.   
					Be sure to release the failure-mode recall function   
					after checking.   
					B 
					29   
				N Electromagnetic noise enters into TV sets or radios   
					Is the unit grounded?   
					Yes   
					Ground the unit.   
					No   
					Is the distance between the antennas   
					and the indoor unit within 9.91 ft., or is   
					the distance between the antennas and   
					the outdoor unit within 9.91 ft.?   
					Extend the distance between the antennas and   
					the indoor unit, and/or the antennas and the   
					outdoor unit.   
					Yes   
					No   
					Is the distance between the TV sets or   
					radios and the indoor unit within 3.28   
					ft., or is the distance between the TV   
					sets or radios and the outdoor unit   
					within 9.91 ft.?   
					Extend the distance between the TV sets and/or   
					radios and the indoor unit, or the TV sets or   
					radios and the outdoor unit.   
					Yes   
					No   
					Are the antennas damaged?   
					Is the coaxial cable damaged?   
					Is there any poor contact in the anten-   
					na wiring?   
					Replace or repair the antenna.   
					Replace or repair the coaxial cable.   
					Yes   
					Yes   
					No   
					Is the indoor/outdoor connecting wire   
					of the air conditioner and the wiring of   
					the antennas close?   
					Extend the distance between the indoor/outdoor   
					connecting wire of the air conditioner and the wir-   
					ing of the antennas.   
					No   
					Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength   
					or the installation condition (combination of specific conditions such as antennas or wiring).   
					Check the followings before asking for service.   
					1. Devices affected by the electromagnetic noise   
					TV sets, radios (FM/AM broadcast, shortwave)   
					2. Channel, frequency, broadcast station affected by the electromagnetic noise   
					3. Channel, frequency, broadcast station unaffected by the electromagnetic noise   
					4. Layout of ;   
					indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver   
					5. Electric field intensity of the broadcast station affected by the electromagnetic noise   
					6. Presence or absence of amplifier such as booster   
					7. Operation condition of air conditioner when the electromagnetic noise enters in   
					1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic   
					noise.   
					2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller   
					for power ON, and check for the electromagnetic noise.   
					3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the elec-   
					tromagnetic noise.   
					4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the   
					indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.   
					30   
				10-6. TEST POINT DIAGRAM AND VOLTAGE   
					1. Inverter P.C. board   
					MUZ-FD09NA MUZ-FD12NA   
					Smoothing   
					capacitor   
					(C62)   
					Smoothing   
					capacitor   
					(C63)   
					Smoothing   
					capacitor   
					(C61)   
					Fuse(F701)   
					250 V 3.15 A   
					DB61   
					Back side of unit   
					DC260 ~300 V   
					(-)   
					(+)   
					Fuse(F801)   
					AC 208 / 230 V   
					250 V 3.15 A   
					R.V.coil   
					(CN721)   
					208 / 230 VAC   
					Fuse(F901)   
					250 V 3.15 A   
					Output to   
					drive com-   
					pressor   
					(LDU,   
					AC208/230 V   
					LDV,   
					LDW)   
					Jumper wire   
					for pre-heat   
					control setting   
					(JK)   
					LEV   
					connector   
					(CN724)   
					Jumper wire for   
					changing defrost   
					setting (JS)   
					Front side of unit   
					Defrost thermistor(RT61)   
					Ambient temperature thermistor(RT65)   
					Outdoor heat exchanger temperature thermistor(RT68)   
					Fin temperature thermistor(RT64)   
					200   
					100   
					90   
					80   
					70   
					60   
					50   
					40   
					30   
					20   
					10   
					0 
					180   
					160   
					140   
					120   
					100   
					80   
					Discharge temperature thermistor(RT62)   
					700   
					600   
					500   
					400   
					300   
					200   
					100   
					0 
					60   
					40   
					20   
					0 
					32 50 68 86 104 122 140 158 176 194 212 230 248   
					32 50 68 86 104 122 140 158 176   
					-4   
					14 32 50 68 86 104   
					Temperature(°F)   
					Temperature(°F)   
					Temperature(°F)   
					31   
				11   
					DISASSEMBLY INSTRUCTIONS   
					<"Terminal with locking mechanism" Detaching points>   
					The terminal which has the locking mechanism can be detached as shown below.   
					There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.   
					The terminal without locking mechanism can be detached by pulling it out.   
					Check the shape of the terminal before detaching.   
					(1) Slide the sleeve and check if there is a locking lever or not.   
					(2) The terminal with this connector has the   
					locking mechanism.   
					Sleeve   
					Slide the sleeve.   
					Hold the sleeve, and   
					Pull the terminal while   
					pull out the terminal   
					slowly.   
					pushing the locking   
					lever.   
					Locking lever   
					Connector   
					11-1. MUZ-FD09NA MUZ-FD12NA   
					OPERATING PROCEDURE   
					NOTE : Turn OFF power supply before disassembling.   
					PHOTOS   
					1. Removing the cabinet   
					Photo 1   
					(1) Remove the screw fixing the service panel. (See   
					Photo 1.)   
					Screws   
					of the top   
					panel   
					(2) Pull down the service panel and remove it. (See Photo   
					1.)   
					(3) Remove the screws fixing the conduit cover. (See   
					Photo 2.)   
					Screw of the   
					cabinet   
					Screws of   
					the top panel   
					Back   
					panel   
					(4) Remove the conduit cover. (See Photo 2.)   
					(5) Disconnect the power supply wire and indoor/outdoor   
					connecting wire.   
					(6) Remove the screws fixing the top panel. (See Photo 1.)   
					(7) Remove the top panel. (See Photo 1.)   
					(8) Remove the screws fixing the cabinet.   
					(9) Remove the cabinet.   
					Screw of   
					the service   
					panel   
					(10) Remove the screws fixing the back panel.   
					(11) Remove the back panel.   
					Photo 2   
					Hooks   
					Screw of the   
					conduit cover   
					Screws of   
					Service   
					panel   
					the cabinet   
					Conduit plate   
					Conduit cover   
					32   
				OPERATING PROCEDURE   
					PHOTOS   
					2. Removing the inverter assembly, inverter P.C. board   
					(1) Remove the cabinet and panels. (Refer to 1.)   
					(2) Disconnect the lead wire to the reactor and the following   
					connectors;   
					Photo 3   
					Screws of the   
					relay panel   
					<Inverter P.C. board>   
					CN721 (R.V.coil)   
					CN932 (Fan motor)   
					CN641 (Defrost thermistor and discharge temperature ther-   
					mistor)   
					CN643 (Ambient temperature thermistor)   
					CN644 (Outdoor heat exchanger temperature thermistor)   
					CN724 (LEV)   
					(3) Remove the compressor connector (CN61).   
					(4) Remove the screws fixing the relay panel. (See Photo 3.)   
					(5) Remove the inverter assembly. (See Photo 4.)   
					(6) Remove the screw of the ground wire and screw of the   
					T.B.support. (See Photo 4.)   
					(7) Remove the inverter P.C. board from the inverter assembly.   
					Photo 4 (inverter assembly)   
					Inverter   
					P.C. board   
					Screw of the   
					T.B.support   
					Heat sink   
					T.B.support   
					3. Removing R.V. coil   
					(1) Remove the cabinet and panels. (Refer to 1.)   
					(2) Remove the R.V. coil. (See Photo 5.)   
					Screw of the   
					ground wire   
					4. Removing the discharge temperature thermistor,   
					defrost thermistor and outdoor heat exchanger tem-   
					perature thermistor.   
					Photo 5   
					R.V. coil   
					(1) Remove the cabinet and panels. (Refer to 1.)   
					(2) Pull out the discharge temperature thermistor from its hold-   
					er. (See Photo 5.)   
					(3) Pull out the defrost thermistor from its holder. (See Photo 6.)   
					(4) Pull out the outdoor heat exchanger temperature thermistor   
					from its holder. (See Photo 6.)   
					Discharge temperature thermistor   
					33   
				OPERATING PROCEDURE   
					PHOTOS   
					Photo 6   
					5. Removing outdoor fan motor   
					(1) Remove the cabinet and panels. (Refer to 1.)   
					(2) Disconnect the connectors for outdoor fan motor.   
					(3) Remove the propeller nut. (See Photo 7.)   
					(4) Remove the propeller. (See Photo 7.)   
					Outdoor heat   
					exchanger tempera-   
					ture thermistor   
					(5) Remove the screws fixing the fan motor. (See Photo 7.)   
					(6) Remove the fan motor.   
					6. Removing the compressor and 4-way valve   
					(1) Remove the cabinet and panels. (Refer to 1.)   
					(2) Remove the inverter assembly. (Refer to 2.)   
					(3) Recover gas from the refrigerant circuit.   
					NOTE: Recover gas from the pipes until the pressure   
					gauge shows 0 PSIG.   
					Defrost thermistor   
					Photo 7   
					Screws of the outdoor fan motor   
					(4) Detach the welded part of the suction and the discharge   
					pipe connected with compressor.   
					(5) Remove the nuts of compressor legs.   
					(6) Remove the compressor.   
					(7) Detach the welded part of pipes connected with 4-way   
					valve. (See Photo 8.)   
					Propeller nut   
					Propeller   
					Photo 8   
					Welded parts of 4-way valve   
					34   
				35   
				TM   
					HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN   
					Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD   
					Distributed in Jan. 2008. No. OBH498 7   
					Made in Japan   
					New publication, effective Jan. 2008   
					Specifications subject to change without notice.   
				 |