White Rodgers Furnace 50A55 843 User Manual

50A55-843  
Universal Integrated Furnace Control  
INSTALLATION INSTRUCTIONS  
Operator: Save these instructions for future use!  
FAILURETOREADANDFOLLOWALLINSTRUCTIONSCAREFULLYBEFORE  
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL  
INJURY AND/OR PROPERTY DAMAGE.  
DESCRIPTION  
The 50A55-843 is an automatic gas interrupted ignition control These controls incorporate system fault analysis for quick gas  
that employs a microprocessor to continually monitor, analyze, flow shut-off, coupled with automatic ignition retry upon sensing  
and control the proper operation of the gas burner, inducer, and a fault correction.  
fan.  
Signals interpreted during continual surveillance of the thermo-  
stat and flame sensing element initiate automatic ignition of the  
burner, sensing of the flame, and system shut-off during normal  
operation.  
TRANE APPLICATION - Installer MUST read page 3 “Mounting and Wiring”  
PRECAUTIONS  
Installation should be done by a qualified heating and air  
conditioning contractor or licensed electrician.  
WARNING  
If in doubt about whether your wiring is millivolt, line, or low  
voltage, have it inspected by a qualified heating and air condi-  
tioning contractor or licensed electrician.  
Do not exceed the specification ratings.  
Allwiringmustconformtolocalandnationalelectricalcodesand  
Failure to comply with the following  
warnings could result in personal injury  
or property damage.  
ordinances.  
This control is a precision instrument, and should be handled  
carefully. Rough handling ordistortingcomponents could cause  
the control to malfunction.  
FIRE HAZARD  
Following installation or replacement, follow manufacturer’s  
recommended installation/service instructions to ensure proper  
operation.  
• Do not exceed the specified voltage.  
• Protect the control from direct contact with water  
(dripping, spraying, rain, etc.).  
• If the control has been in direct contact with water,  
replace the control.  
• Label all wires before disconnection when servic-  
ing controls. Wiring errors can cause improper  
and dangerous operation.  
CAUTION  
Do not short out terminals on gas valve or primary  
control. Short or incorrect wiring may damage the  
thermostat.  
• Route and secure wiring away from flame.  
SHOCK HAZARD  
• Disconnect electric power before servicing .  
• Ensure proper earth grounding of appliance.  
• Ensure proper connection of line neutral and line  
hot wires.  
CONTENTS  
Description ........................................................ 1  
Precautions ....................................................... 1  
Specifications .................................................... 2  
Installation ......................................................... 3  
Mounting & Wiring  
EXPLOSION HAZARD  
• Shut off main gas to appliance until installation is  
complete.  
Operation .......................................................... 6  
Mounting Hole Template .................................... 8  
White-Rodgers is a division  
of Emerson Electric Co.  
PART NO. 37-6265G  
Replaces 37-6265F  
0526  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
MOUNTING AND WIRING  
All wiring should be installed according to local and national  
electrical codes and ordinances.  
WARNING  
The control must be secured to an area that will experience a  
minimum of vibration and remain below the maximum ambient  
temperature rating of 175°F. The control is approved for mini-  
mum ambient temperatures of -40°F.  
FIRE HAZARD  
When mounting the control, any orientation is acceptable.  
Choose a location that will not damage, obstruct or place stress  
Do not exceed the specified voltage.  
Replace existing control with exact model and  
dash number.  
on the controls terminations, system wiring harness or system  
1
components. After finding a suitable location, drill four (4) ¦8  
holes for mounting control. To ensure proper mounting hole  
locations, there is a mounting hole template on page 8 of this  
instruction sheet. Detach the page with the template from the  
instruction sheet and apply it to the mounting location. When  
drilling the holes, take care so that the transformer, wiring  
harnessorothersystemcomponentsarenotdamaged. Four(4)  
#8 sheet metal screws are provided to complete the installation.  
Protect the control from direct contact with water  
(dripping, spraying, rain, etc.).  
Label all wires before disconnection when servic-  
ing controls. Wiring errors can cause improper  
and dangerous operation.  
Route and secure wiring away from flame.  
SHOCK HAZARD  
Refer to the wiring diagram and wiring table when connecting  
the 50A55 control to other components of the system.  
UL approved, 105°C rated 18 gauge, stranded, 2¦64thick insula-  
tion wire is recommended for all low voltage safety circuit  
connections. Refer to 50A55 specification sheet for recom-  
mended terminals to mate with those on the control.  
Disconnect electric power before servicing .  
Ensure proper earth grounding of appliance.  
Ensure proper connection of line neutral and line  
hot wires.  
EXPLOSION HAZARD  
Shut off main gas to appliance until installation is  
complete.  
UL approved 105°C rated 16 gauge min., stranded, 4¦64thick  
insulation wire is recommended for all line voltage connections.  
Refer to 50A55 specification sheet for recommended terminals  
to mate with those on the control.  
Afterinstallationorreplacement,followappliancemanufacturers  
recommended installation or service instructions to ensure  
proper operation.  
CAUTION  
Do not short out terminals on gas valve or primary  
control. Short or incorrect wiring may damage the  
thermostat.  
The 50A55 has only one serviceable partan automotive type  
fuse, which protects the low voltage transformer from damage  
if its output is short-circuited. If the fuse has opened up, remove  
whatever caused the short circuit and replace the fuse with only  
a 3 Amp automotive type fuse. If the fuse is not the cause of the  
controls problem, replace the entire 50A55 control. There are  
no other user serviceable parts.  
Additional jumper wires are included in this package and  
should be used if the original wiring does not reach the control  
after mounting. Refer to the furnace wiring diagram for proper  
connection of the wires.  
Amana/Goodman application - An additional wiring harness  
(WR 115-0223) is included in this package. If the control being  
replaced has a 2-pin (inducer/ignitor) connector, this wiring  
harness will adapt the furnace wiring to the 4-pin connector of  
the replacement control.  
Trane application - Jumper wire 151-2906 (provided with  
control) must be installed on the furnace from R01 to R02 of the  
12-pin connector.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL SYSTEM WIRING DIAGRAM  
HOT  
(LINE)  
NEUTRAL  
(LINE)  
120 VAC  
24 VAC CLASS II  
TRANSFORMER  
TH  
24 VAC  
50A55  
TR  
COOL  
HEAT  
PARK  
PARK  
LINE  
CIRCULATOR  
BLOWER  
XFMR  
EAC  
HUM  
IND  
IGN  
IND N  
IGN N  
INDUCER  
IGNITOR  
HUMIDIFIER  
CIR N  
LINE N  
XFMR N  
HUM N  
EAC N  
ELECTRONIC  
AIR CLEANER  
Y
W
G
R
Y
W
G
R
COMPRESSOR  
CONTACTOR  
50A55-843  
in other  
furnace(s)  
TWINNING  
APPLICATIONS  
ONLY  
THERMOSTAT  
C
TWIN*  
TWIN*  
PRESSURE SWITCH (N. O.)  
PS  
HLI  
HLO  
FP  
RO1  
GND  
RO2  
MV  
FLAME  
SENSOR  
PROBE  
HIGH LIMIT  
(N. C.)  
AUX. HIGH  
LIMIT (N. C.)  
ROLLOUT  
(N. C.)  
GAS  
VALVE  
MV  
TR  
TH  
LEGEND  
Low Voltage (24 VAC)  
Line Voltage (120 VAC)  
N. C. = Normally closed switch  
N. O. = Normally open switch  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL SYSTEM WIRING TABLE  
50A55  
TERMINAL  
TERMINAL  
SYSTEM COMPONENT  
CONNECTION  
TYPE  
W
G
R
Y
low voltage thermostat W terminal (or equivalent)  
low voltage thermostat G terminal (or equivalent)  
low voltage thermostat R terminal (or equivalent)  
low voltage thermostat Y terminal (or equivalent)  
(2nd wire from Y terminal goes to 24 VAC HOT side of  
compressor contactor coil)  
Terminal  
block with  
captive  
screws  
C
24 VAC COMMON side of compressor contactor coil  
one wire twinning terminal  
TWIN*  
MV (2 terminals)  
gas valve (both gas solenoids are connected in parallel)  
24 VAC transformer (low voltage COMMON side)  
24 VAC transformer (low voltage HIGH side)  
rollout switch OUTPUT  
TR  
TH  
RO1  
RO2  
12-pin  
rollout switch INPUT  
FP  
connector  
& harness  
flame sensor probe*  
PS  
pressure switch INPUT  
HLI  
high limit INPUT  
HLO  
high limit OUTPUT  
GND  
MUST BE RELIABLY GROUNDED TO CHASSIS  
(unused terminal)  
IND  
inducer HOT side  
4-pin  
connector  
& harness  
IGN  
ignitor HOT side  
IND N  
IGN N  
inducer NEUTRAL side  
ignitor NEUTRAL side  
COOL  
HEAT  
spade terminal circulator blower COOL SPEED terminal  
spade terminal circulator blower HEAT SPEED terminal  
PARK (2 terminals) spade terminal unused circulator blower terminals  
LINE  
spade terminal input voltage (120 VAC) HOT side  
spade terminal 24 VAC transformer line voltage HOT side  
spade terminal electronic air cleaner HOT side  
XFMR  
EAC (optional)  
HUM (optional)  
CIR N  
spade terminal humidifier HOT side  
spade terminal circulator blower NEUTRAL terminal  
spade terminal input voltage (120 VAC) NEUTRAL side  
spade terminal 24 VAC transformer line voltage NEUTRAL side  
spade terminal electronic air cleaner NEUTRAL side  
LINE N  
XFMR N  
EAC N (optional)  
HUM N (optional) spade terminal humidifier NEUTRAL side  
* The twinning feature is available only on models with six screw terminals; one of these terminals  
will be designated TWIN. All 50A55-843 controls used in twinning applications must have the  
TWINterminal.  
Maximum recommended flame probe wire length is 36 inches.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
OPTION SWITCHES  
The option switches on the 50A55-843 control are used to  
determine the length of the cool delay-to-fan-off, heat delay-to-  
fan-on and heat delay-to-fan-off periods. The following table  
shows the time periods that will result from the various switch  
positions.  
If flame is detected, the delay-to-fan-on period begins. After the  
delay-to-fan-on period ends, the optional electronic air cleaner  
is energized and the circulator fan is energized at heat speed.  
When the thermostat is satisfied, the gas valve is de-energized.  
After proof of flame loss, the heat delay-to-fan-off period begins  
and the inducer blower remains energized to purge the system  
for 15 seconds. When the purge is complete, the inducer blower  
and humidifier are de-energized. After the delay-to-fan-off pe-  
riod ends, the circulator fan and electronic air cleaner are de-  
energized.  
OPTION SWITCH POSITIONS  
COOL delay-  
to-fan-off:  
Set switch  
#1  
Ifflame is not detected, both valvesare de-energized, theignitor  
is turned off, and the 50A55 control goes into the retryse-  
quence. The retrysequence provides a 60-second wait follow-  
ing an unsuccessful ignition attempt (flame not detected). After  
this wait, the ignition sequence is restarted with an additional 2  
seconds of ignitor warm-up time. If this ignition attempt is  
unsuccessful, one more retry will be made before the control  
goes into system lockout.  
45 sec.*  
90 sec.  
On  
Off  
HEAT delay-  
to-fan-on:  
Set switch  
#2  
30 sec.*  
45 sec.  
On  
Off  
If flame is detected, then lost, the 50A55 control will repeat the  
initial ignition sequence for a total of four recycles. After four  
unsuccessful recycleattempts, the control will go into system  
lockout.  
HEAT delay-  
to-fan-off:  
Set switch  
#3  
#4  
60 sec.  
90 sec.  
120 sec.  
180 sec.*  
On  
Off  
On  
Off  
On  
On  
Off  
Off  
If flame is established for more than 10 seconds after ignition,  
the 50A55 controller will clear the ignition attempt (or retry)  
counter. If flame is lost after 10 seconds, it will restart the ignition  
sequence. This can occur a maximum of five times before  
system lockout.  
* Factory setting  
During burner operation, a momentary loss of power of 50  
milliseconds or longer will de-energize the main gas valve.  
When power is restored, the gas valve will remain de-energized  
and a restart of the ignition sequence will begin immediately.  
HEAT MODE  
In a typical system, a call for heat is initiated by closing the  
thermostat contacts. This starts the 50A55 controls heating  
sequence. The inducer blower and optional humidifier are  
energized and the ignitor is powered within one second.  
A momentary loss of gas supply, flame blowout, or a shorted or  
openconditionintheflameprobecircuitwillbesensedwithin2.0  
seconds. The gas valve will de-energize and the control will  
restart the ignition sequence. Recycleswill beginand the burner  
will operate normally if the gas supply returns, or the fault  
condition is corrected, before the last ignition attempt. Other-  
wise, the control will go into system lockout.  
This controller has an adaptive algorithm that adjusts the dura-  
tion of the ignitor warm-up, to extend ignitor life. Upon initial  
application of power, the warm-up time is 17 seconds. The  
ignitor on-time will then be increased or decreased depending  
on whether or not flame isachieved. The warm-up time is limited  
to a maximum of 21 seconds. During the first 64 warm-up  
periods following power-up, the warm-up time may not be less  
than 17 seconds.  
If the control has gone into system lockout, it may be possible to  
reset the control by a momentary power interruption of one  
second or longer. Refer to SYSTEM LOCKOUT FEATURES.  
Upon a call for heat, if the warm-up time has not been locked, it  
willbedecreasedbyonesecond.Thisreductionoftheignitoron-  
time will continue until flame fails to be achieved (resulting in a  
retry).  
COOL MODE  
In a typical system, a call for cool is initiated by closing the  
thermostat contacts. This energizes the 50A55 control and the  
compressor. The cool delay-to-fan-on period begins. After the  
delay period ends, the optional electronic air cleaner is ener-  
gized, and the circulator fan is energized at cool speed. After the  
thermostat is satisfied, the compressor is de-energized and the  
cool mode delay-to-fan-off period begins. After the delay-to-fan-  
off period ends, the circulator fan and electronic air cleaner  
(optional) are de-energized.  
In the event of a retry, the warm-up time will be increased by two  
seconds and locked in at that duration. Once the warm-up time  
is locked, it remains fixed until another call for heat results in a  
retry, in which case the warm-up time is again increased by two  
seconds and remains locked.  
In the event of two successive retry attempts, the warm-up time  
willbeunlockedandsetto21seconds. Ifflameisthenachieved,  
the warm-up time will begin adapting again with the next call for  
heat. If, however, this third attempt fails to achieve flame, the  
control will go into system lockout.  
MANUAL FAN ON MODE  
At the end of the ignitor warm-up time, both valves in the 36E  
manifold gas valve are opened. Flame must be detected within  
4 seconds.  
If the thermostat fan switch is moved to the ON position, the  
circulatorfan(coolspeed)andoptionalelectronicaircleanerare  
energized. When the fan switch is returned to the AUTO posi-  
tion, the circulator fan and electronic air cleaner (optional) are  
de-energized.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIAGNOSTIC FEATURES  
TWINNING INTERFACE  
The 50A55-843 control continuously monitors its own operation  
and the operation of the system. If a failure occurs, the LED will  
indicate a failure code as shown below. If the failure is internal  
to the control, the light will stay on continuously. In this  
case, the entire control should be replaced, as the control  
is not field-repairable.  
If the control has six screw terminals, one of which is  
designated TWIN, the control is equipped with a single wire  
twinning interface. If twinning is used, either control will  
process a call for heat, cool or fan as described above.  
However, after the heat-, cool-, or fan-on delay time expires,  
both units will energize the circulator blowers at the same  
time. Likewise, after the heat-, cool-, or fan-off delay time  
expires, both units will de-energize the circulator blowers at  
the same time. This allows for proper air flow to be obtained.  
To assure proper control operation, both controls must share  
a common transformer ground (TR).  
If the sensed failure is in the system (external to the control), the  
LED will flash in the following flash-pause sequences to indicate  
failure status (each flash will last approximately 0.25 seconds,  
and each pause will last approximately 2 seconds).  
1 flash, then pause  
System lockout  
To enable twinning, do the following.  
2 flashes, then pause  
3 flashes, then pause  
4 flashes, then pause  
5 flashes, then pause  
6 flashes, then pause  
Pressure switch stuck closed  
Pressure switch stuck open  
Open limit switch  
Open rollout switch  
115 Volt AC power reversed/Im-  
proper ground  
1. Power supplied to both furnaces must be from the same  
phase of the incoming 120 VAC power.  
2. Connect the TWIN screw terminals on the 50A55-843 of  
the furnaces to be twinned to each other using a single  
wire (14-22 AWG.).  
7 flashes, then pause  
Continuous flashing  
(no pause)  
Low flame sense signal  
Flame has been sensed when  
no flame should be present (no  
call for heat)  
SYSTEM LOCKOUT AND  
DIAGNOSTIC FEATURES  
The LED will also flash once at power-up.  
SYSTEM LOCKOUT FEATURES  
When system lockout occurs, the gas valve is de-energized, the  
circulator blower is energized at heat speed, and, if flame is  
sensed, the inducer blower is energized. The diagnostic indica-  
tor light will flash or glow continuously to indicate system status.  
(System lockout will never override the precautionary fea-  
tures.)  
To reset the control after system lockout, do one of the  
following:  
1. Interruptthecallforheatorcoolatthethermostatforatleast  
one second but less than 20 seconds (if flame is sensed  
with the gas valve de-energized, interrupting the call for  
heat at the thermostat will not reset the control).  
2. Interrupt the 24 VAC power at the control for at least one  
second.Youmayalsoneedtoresettheflamerolloutsensor  
switch.  
3. After one hour in lockout, the controlwill automatically reset  
itself.  
The Emerson logo is a  
trademark and a service mark  
of Emerson Electric Co.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
MOUNTING HOLE TEMPLATE  
MOUNTING HOLE TEMPLATE  
FOR MOUNTING HOLE LOCATIONS  
4.172 ± .007  
(2 plcs.)  
6.402 ± .010  
(2 plcs.)  
Refer to page 3 of the installation instructions for proper installation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Weider Home Gym 831150730 User Manual
Whirlpool Range FEP310E User Manual
White Rodgers Thermometer 7904 User Manual
White Sewing Machine 1300DE User Manual
Windmere Slow Cooker WSC200C User Manual
Winegard Satellite TV System SF 1000 User Manual
Yamaha Electronic Keyboard DX7 User Manual
Zanussi Fryer 285764 User Manual
Zanussi Refrigerator ZBA3224A User Manual
Z Microsystems Computer Monitor StarGate 20 User Manual