Weil McLain Water Heater C 1013 User Manual

C-1013  
Copyright© 2006  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Insufficient Hot Water - page 3  
- Undersized water heater  
- Boiler system improperly sized  
- Check component parts  
- Boiler operating temperature  
- Location of flow control devices  
- Air in system  
INSUFFICIENT  
HOT WATER  
Yes  
- Clean boiler system  
Excessive Water Temperature - page 6  
- Reduce Stacking  
EXCESSIVE DOMESTIC  
WATER TEMPERATURE  
Yes  
Yes  
Yes  
- Lowering boiler operating temperature  
- Relocating T-stat bulb  
- Reverse boiler piping  
- Install thermostatic mixing valve  
- Recirculation loop  
Boiler Relief Valve Lifting or Weeping - page 7  
- Undersized boiler expansion tank  
- Faulty boiler expansion tank  
- Simulate maximum expansion  
- Faulty boiler relief valve  
BOILER RELIEF  
VALVE LIFTING  
OR WEEPING  
- Faulty boiler fill valve  
- Inner tank leak  
T&P Relief Valve Lifting or Weeping - page 8  
- Undersized or missing domestic side expansion tank  
- Faulty domestic expansion tank  
TEMPERATURE/  
PRESSURE RELIEF  
VALVE LIFTING  
OR WEEPING  
- Faulty T&P relief valve  
- High domestic supply pressure  
- Possible water hammering or pressure spikes  
- Boiler operating temperature  
Water on the Floor - page 9  
- From sources other than the water heater  
- T&P valve lifting and discharging  
- Loose piping connections  
WATER FOUND ON  
THE FLOOR NEAR  
THE TANK  
Yes  
Yes  
Yes  
Top of Tank / Insulation Wet - page 10  
- From sources other than the water heater  
- Loose piping connections  
TOP OF TANK/  
INSULATION WET  
- Leakage from the drywell  
Water Smells / Taste Bad - page 11  
- Water smells like "rotten eggs"  
- Milky water  
WATER QUALITY  
PROBLEMS  
- Rusty discolored water  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Is the water heater undersized for the application? (Non-Warranty)  
- There are many methods of sizing various applications, i.e. ASHRAE sizing tables, or  
ASPE domestic water heating design manual, re-confirm the water demand required for  
the application.  
- Re-confirm the flow rates of the fixtures. Was the tank sized for shower heads at 2.0 gpm,  
when the actual heads are 5.0 gpm? Use a bucket and a stopwatch to determine fixture  
flow rates.  
- Evaluate the hot water usage pattern for a day. Is the peak demand unusually high for the  
application?  
- Has the demand for domestic hot water changed since the system was installed? A  
bathroom remodeling project with a newly installed whirlpool tub will drastically change  
the domestic water demand.  
Is the boiler system properly sized? (Non-Warranty)  
- Is the boiler providing the required output of BTU’s to meet the domestic water load?  
Blr Output BTU’s  
Domestic Demand gph=  
(Temp. Rise F x 8.33)  
Temp Rise ºF = Desired Temp.ºF - Incoming Temp.ºF  
8.33 = Density of Water lbs/gal. x 1 Btu/lbs ºF  
Example: A single family home with a 3.0 gpm shower fixture and a 150,000 Btu/hr output  
boiler capacity. Is the boiler capacity adequate to deliver 115ºF water for an extended period?  
150,000 Btu/hr  
= 277 gph  
Domestic Demand gph=  
[(115 F-50 F) x 8.33]  
The boiler capacity is capable of delivering 4.6 gpm continuously which is  
adequate for this application.  
Action Item:  
- Measure the BTU input to the boiler by clocking the gas meter or finding the oil flow rate  
based on nozzle size and pump pressure.  
- Does the hot water system need to be wired for domestic priority? For systems in which  
either the storage or BTU’s available are marginal, it is recommended to wire the domestic  
water heater in a priority manner.  
- Is the boiler piping to the water heater properly sized to allow the required flow rate for  
maximum BTU transfer? The temperature differential of the boiler supply and return  
water should be 20ºF to 30ºF.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
- Is the circulator between the boiler and the water heater properly sized to provide adequate  
flow for maximum BTU transfer?  
PIPE SIZE  
3/4"  
1"  
1 1/4"  
1 1/2"  
2"  
FLOW RATE  
3 to 7 gpm  
4 to 11 gpm  
6 to 16 gpm  
9 to 23 gpm  
15 to 40 gpm  
BTU'S TRANSFER  
50 to 100 MBH  
100 to 180 MBH  
160 to 300 MBH  
200 to 450 MBH  
300 to 650 MBH  
Check component parts  
- Is the domestic water thermostat functioning properly? With a electrical voltmeter check  
for continuity between terminals C and 1 on the snap-set connection.  
Action Item:  
1. Disconnect the snap-set connector on the water heater.  
2. Turn the thermostat knob to the highest setting - clockwise to initiate a call for heat.  
3. Check for continuity between terminals C and 1 (end connectors on the snap-set). On a  
call for heat, these contacts should be in the close position.  
4. Continue checking for continuity while turning the thermostat knob to the lowest setting  
- counter clockwise to satisfy the call for heat. The contacts should open, breaking the  
continuity.  
5. If any of these steps fail (1-4 above), replace the thermostat. (Warranty)  
For 30/40/60/80 - P/N 633-900-130 for 100/110/119/120 - P/N 635-100-010.  
6. Reconnect the snap-set.  
- Is the thermostat setting too low? If the thermostat setting is too low, the boiler may not  
have the opportunity to deliver the maximum BTU’s required to completely heat the  
entire volume of water stored in the tank.  
- During a call for heat by the water heater, does the boiler circulator begin pumping, does  
the zone valve open, does the boiler fire? Check every component in the system to ensure  
they are properly functioning.  
- Check the thermostat sensing bulb size and fit into the drywell. Some older units have a  
sensing bulb that is thinner and fits loose inside the drywell. The newer thermostats have a  
larger bulb which fits tighter in the drywell allowing better heat transfer for more accurate  
water temperature sensing.  
Action Item:  
- If the sensing bulb does not slide into the drywell; remove burrs from top 1 1/2” inside the  
drywell with a 3/8” drill.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
- What is the location of the thermostat bulb? A bulb inserted completely at the bottom of  
the drywell will initiate a quicker response for a call for heat. This is typically the position  
of the bulb required for applications in which there are large draws of domestic water.  
- Remove and examine the dip tube located in the cold water inlet. Replace if damaged. A  
broken or melted dip tube will cause the cold water to discharge across the top of the tank,  
thus short cycling the water heater.  
Check the operating temperature of the boiler (Non-Warranty)  
- If possible increase the boiler operating temperature to 200ºF.  
- Maintain a minimal temperature in the boiler during non-heating seasons. A boiler  
typically has a higher standby loss than the indirect water heater. After a long standby  
period, the colder boiler may absorb the stored energy within the water heater during the  
initial call for heat.  
Check location of flow control devices (Non-Warranty)  
- Lab tests have shown that during long standby periods the boiler piping can act as a  
thermal siphon and draw stored heat from the domestic water. Locate flow control devices  
(zone valve, spring check valves...) or heat trap loops in the boiler piping close to the water  
heater. Insulate all boiler piping to and from the water heater.  
Check for air in the system (Non-Warranty)  
- An air bound water heater or boiler will not circulate system water properly, resulting in a  
lack of heat transfer.  
Clean the boiler system (Non-Warranty)  
- A dirty boiler system can cause deposits to form on the outer wall of the inner tank, which  
insulates the tank, affecting the heat transfer. Clean the boiler system per the boiler’s  
manufacturer’s instructions.  
Action Item:  
- Install a strainer in the boiler piping on older installations or for systems prone to  
becoming dirty.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excessive water temperature is usually the result of stacking within the water  
heater. Stacking is the occurrence of various water temperatures layering within  
the water heater with the hottest water in the uppermost layer. This layering or  
stacking effect typically occurs during small draws of hot water (typically less  
than 25% of the storage capacity) which are long enough to create a call for heat  
on the thermostat, but are short enough not to deplete the stored energy within  
the tank. Excessive stacking can occur when frequent short to moderate draws  
are taken in quick succession. During this type of situation, the temperature of  
the domestic water can approach the temperature of the boiler water.  
REMEMBER: All water heaters (direct and indirect) will stack.  
Reducing stacking within the tank (Non-Warranty)  
- Reduce the boiler operating temperature to 160ºF - 170ºF. This will limit the maximum  
domestic outlet water temperature during high stacking water usage.  
- Raise the thermostat sensing bulb higher in the drywell. This will reduce the frequency of  
thermostat calls for heat during small draws of hot water. However, it will reduce the  
quantity of available hot water during a deep draw by delaying the call for heat to the  
boiler.  
- Reverse the boiler side piping. The older installations have the boiler supply at the top of  
the water heater and return at the bottom. Reversing the piping, supply at the bottom and  
return at the top will:  
a) Result in lower tank stacking by having the hottest boiler water closer to the cooler  
incoming domestic water.  
b) Reduce the effect of “thermal overshoot” after the thermostat call for heat has been  
satisfied.  
c) Provide a more uniform hot water delivery temperature during moderate to deep  
draws (25% to 100% of the tank’s storage capacity). Reversing the boiler piping will  
not affect the performance of the water heater.  
Install thermostatic mixing valve  
- Installation of a thermostatic mixing valve will provide an uniform delivery temperature  
with minimal regard to water usage.  
Recirculation Loop  
- Installation of a properly sized recirculation loop not only provides prompt delivery of hot  
water, but it provides circulation and mixing of the water within the tank.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Is the expansion tank on the boiler side properly sized?  
- The additional quantity of boiler water contained in the outer tank must be considered  
when sizing the boiler side expansion tank.  
Weil-McLain Water Heater Model  
GOLD Plus 30  
GOLD/Ultra Plus 40  
Boiler Side Capacity Gal.  
5
6
GOLD/Ultra Plus 60  
8
GOLD/Ultra Plus 80  
8
Comm. PLUS 100 Series 2/Series 3  
Comm. PLUS 110  
Comm. PLUS 119/120  
8/14  
25  
43  
- Insufficient allowance for expansion on the boiler side can cause the boiler pressure relief  
valve to lift.  
Is the expansion tank defective, waterlogged or improperly charged?  
(Non-Warranty)  
- Check for failed gaskets or bladders, or a faulty Schraeder valve.  
- Use a tire gauge to check the charged pressure of the tank.  
Action Item:  
- Turn the boiler limit up to a higher setting and let the system run at a higher temperature.  
This will simulate maximum expansion in the boiler system.  
- If the boiler relief valve lifts and/or there is a significant increase in the boiler system  
pressure, the expansion tank is flooded or undersized.  
Is the boiler pressure relief valve functioning properly? (Non-Warranty)  
- Dirt and water deposits can accumulate under the valve seat.  
Check the boiler automatic fill valve for defects. (Non-Warranty)  
- Is the valve filling to the correct pressure?  
Check for possible ‘inner tank leak’ *reason code 054  
- If possible, isolate the Plus tank from the boiler system for an extended period of time.  
Observe the boiler system pressure during that time.  
* This may be a manufacturing defect. Please initiate a warranty claim with Weil-McLain  
noting the reason code listed.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Is there a thermal expansion tank installed on the domestic supply piping  
and is it properly sized? (Non-Warranty)  
- A thermal expansion tank is required if the domestic supply piping includes a backflow  
preventer or pressure reducing valve.  
- Ensure the potable water expansion tank is properly sized according to the water heater  
volume and supply pressure.  
- During long periods when there are no draws from the tank (i.e. overnight), the T&P  
relief valve may lift or weep due to thermal expansion, but may function properly during  
normal periods of tank draws.  
Is the expansion tank defective, water logged or improperly charged?  
(Non-Warranty)  
- Check for failed gaskets or bladders, or a faulty Schraeder valve.  
- Use a tire gauge to check the charged pressure of the tank.  
Is the temperature/pressure relief valve functioning properly?  
- Dirt and water deposits can accumulate under the valve seat.  
Check the domestic supply pressure entering the water heater.  
(Non-Warranty)  
- If the pressure is over 70 psi, it is recommended to install a pressure reducing valve. This  
will prevent any pressure spikes or increases in pressure due to thermal expansion which  
may cause the T&P valve to lift or weep.  
Check the domestic system for possible sources of water hammering or  
pressure spikes.  
- Some appliances, such as clothes washers and dishwashers, utilize fast acting valves which  
may cause water hammering or pressure spikes through the domestic water system.  
Action Item:  
- Install water hammer arrestors as required per the manufacturer’s instructions, or install  
flexible connectors to isolate the tank from the domestic system.  
Check the operating temperature of the boiler.  
- If the boiler operating temperature is excessive, greater than 200ºF, stacking can occur in  
the inner tank raising the domestic water temperature close to the boiler operating  
temperature.  
Action Item:  
- Reduce the boiler operating temperature to 180ºF.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Is the source of water from the tank?  
- Check for possible water seepage through foundation cracks. Did the water appear after a  
heavy rain? (Non-Warranty)  
Is the source of water from the T&P relief valve?  
- Place a bucket under the discharge piping of the T&P relief valve and monitor it for a day  
or two. This is a procedure that can be done by the homeowner.  
- If the T&P relief valve is the source, refer to the T&P Relief Valve section of this guide.  
Check all connections – boiler connections, domestic connections…  
- Check all the boiler connections to the water heater. A build-up of corrosion is a sure sign  
of a leak. (Non-Warranty)  
- Check the boiler supply connections. Look at the welds where the spuds enter into the  
outer tank. These can be cracked by using excessive force when connecting piping. (Non-  
Warranty) If they are leaking and it is NOT related to an installation error or system  
problem—*reason code 057.  
- Check the domestic connections. Look at the welds where the spuds enter into the outer  
tank. Excessive water hammering in the domestic system may crack these welds. (Non-  
Warranty) If they are leaking and it is NOT related to an installation error or system  
problem.—*reason code 058.  
- Check the seal around the air vent for leaks.  
- Check the drywell for leaks.  
Action Item:  
- To replace the drywell use the Replacement Kit. (See chart on Page 15, 17, 19 or 21)  
- Apply sealant (i.e. Leaklok or Loctite) completely around threads in all applications.  
* This may be a manufacturing defect. Please initiate a warranty claim with Weil-McLain  
noting the reason code listed.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Is the source of water from the tank?  
- Check for possible overhead pipes leaking onto the tank. (Non-Warranty)  
Check all connections – boiler connections, air vent…  
- Check the connections to the water heater. Are they loose? A build-up of corrosion around  
joints is a sure sign of a leak. (Non-Warranty)  
- Check the seal around the air vent and drywell for leaks. Remove the drywell and check  
the O-ring gasket (if applicable) beneath it. (Non-Warranty) If they are leaking and it is  
not related to an installation error or system problem—*reason code 058.  
- Remove the thermostat sensing bulb from the drywell. If the bulb wet or is water visible at  
the top of the drywell?—*reason code 059.  
Action Item:  
- To replace the drywell use the Replacement Kit. (See chart on Page 15, 17, 19 or 21)  
- Apply sealant (i.e. Leaklok or Loctite) completely around threads in all applications.  
* This may be a manufacturing defect. Please initiate a warranty claim with Weil-McLain  
noting the reason code listed.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The hot water smells like “rotten eggs” (Non-Warranty)  
The most common cause of water to smell like “rotten eggs” is a non-toxic  
sulfate reducing bacteria. The bacteria usually enters into the water system  
through a break in the supply piping or during construction/maintenance of the  
supply piping. The bacteria survives in the water system by converting sulfate  
(SO4) in the water to hydrogen sulfide (H2S) gas. It is this gas that creates the  
“rotten egg” smell. The presence of hydrogen sulfide can also affect the taste of  
the water as well. Along with the stench caused by this bacteria, black deposits  
(which typically indicate pipe and/or fitting corrosion) may also appear in the  
water.  
WARNING!  
In extremely high concentrations, hydrogen sulfide gas can be toxic.  
However, the gas is detectable prior to reaching harmful levels.  
The bacteria will thrive in any water system under the following conditions:  
• High levels of sulfur in the water  
• Activated hydrogen in the water from cathodic reactions within the tank  
• Water with little or no dissolved oxygen  
• Storing the domestic water below 140ºF  
Other causes of smelly water:  
• Chlorides of magnesium and calcium gives water a bitter taste  
• Chloride of sodium will produce a salty tasting water  
• Sulfates above 50 ppm in the water gives the water a medicinal taste  
• Carbon dioxide in water with a low pH results in water that is fizzy  
• Iron and tannic waters will produce water with a bad taste and odor  
Action Item:  
- The treatment of this situation requires the water system to be shockchlorinated.  
Depending on the severity of the bacteria within the water system, several treatments may  
be needed.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hot water from the faucet appears milky (Non-Warranty)  
When water is initially drawn from the faucet it appears to be milky or  
cloudy, but it becomes clear after the water is allow to stand for several minutes.  
This is usually an indication that the water contains high levels of soluble gases  
such as oxygen, chlorine, carbon dioxide, hydrogen sulfide or others. As the  
water system pressure increases, the amount of gas that water can hold in a  
solution decreases. When air and gases are forced out of the heated water, the  
problem may be evident in one or both of the following conditions:  
• Gases, in the form of small bubbles, may make the water appear milky from the tap, but  
clear after several minutes when those bubbles will separate. Similar to the reaction that  
occurs as air bubbles form on the walls of a pan shortly before the water begins to boil.  
• The release of dissolved gas can also create air pockets and air locks in the water system  
piping. This can cause spurts of air or gases when opening the hot water faucet.  
There is generally no cure for milky water caused by dissolve gases, although  
it can be reduced with aerated faucets. In some applications, the amount of air  
and gases precipitating out of the water will reduced in time. It should be noted  
that these gases are not harmful to the end user.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Discolored water from the hot water faucet (Non-Warranty)  
The water from the hot water faucet appears discolored, either rusty, brown,  
black or yellow. Because the inner tank is stainless steel, which by its nature is  
resistant to corrosion, the problem is not tank related. The problem is usually a  
non-toxic iron reducing bacteria that is commonly found in soil, well water,  
water treatment plants and piping systems. The bacteria usually thrives in those  
systems in which the soluble iron exceeds 0.2 ppm. The bacteria will feed on the  
soluble iron in the water producing “rusty” color water as a by-product of the  
feeding process.  
Variables in which the bacteria can thrive in:  
• Elevated levels of iron and manganese in the water  
• Water with little or no dissolved oxygen  
• Water storage temperatures below 140ºF  
Items that can potentially increase the presence of the bacteria:  
• Water softeners  
• Well water  
• Long periods of no water movement  
Action Item:  
- The treatment of this situation requires the water system to be shockchlorinated.  
Depending on the severity of the bacteria within the water system, several treatments may  
be needed.  
Check the ph and the Chlorides of the water in both the inner (domestic) tank  
and the outer (boiler) tank. Ph must be between 6 and 8. The chloride must be  
less than 80mg/l. Note the ph and Chloride readings on the RGA Paperwork.  
Items that can affect the ph reading:  
1) Water Softeners  
2) Water treatment plants  
a) Cl ( Chlorides) added, especially during the summer  
b) Fl ( Fluorides) added in treatment in large cities  
3) Elevated levels of iron, manganese, and sulfur  
If the ph is out of range it has a big effect on the metal tanks, piping and heat  
transfer surfaces.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Weider Home Gym 831159720 User Manual
Whirlpool Clothes Dryer YWED5700SW0 User Manual
Whirlpool Microwave Oven W10238253A User Manual
Xerox Copier N4525 User Manual
Yamaha Stereo Amplifier AX 492, AX 592, AX 892 User Manual
Zanussi Dishwasher DCE 5655 User Manual
Zanussi Oven 238503 User Manual
Zanussi Refrigerator ZRT318W User Manual
Zanussi Washer ZWG 3142 User Manual
Zeki Tablet TBD753B User Manual