Weil McLain Water Heater 105 User Manual

Gas-fired  
water boiler  
Ultra-80, -105, -155, -230 & -310  
• Installation  
• Startup  
• Maintenance  
• Parts  
with  
This manual must only be used by a qualified heating installer/service technician.  
Read all instructions, including this manual, the Ultra Control Supplement and the  
UltraVent Supplement,before installing. Perform steps in the order given.Failure  
to comply could result in severe personal injury, death or substantial property  
damage.  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
THE  
GAS-FIRED WATER BOILER, WITH PhD TECHNOLOGY  
3
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
Co n t e n t s  
How it works.................................................................................... 2–3  
Hazard definitions .............................................................................. 4  
Please read before proceeding ........................................................ 5  
1 Prepare boiler location .................................................................. 6  
2 Prepare boiler ................................................................................. 9  
3 Install water piping ....................................................................... 12  
4 Venting, combustion air & condensate line .............................. 19  
5 Gas piping ..................................................................................... 21  
6 Startup (Note 1) ................................................................................. 23  
7 Check-out/startup verification .................................................... 26  
8 Annual startup and general maintenance ................................ 28  
9 Replacement parts ....................................................................... 35  
10 Dimensions ................................................................................. 43  
11 Ratings ........................................................................................ 44  
Note 1:  
See Ultra Control Supplement for wiring and additional  
startup and operating information.  
Ha za rd d e fin it io n s  
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various  
risk levels or to important information concerning the life of the product.  
Indicates presence of hazards that will cause severe personal injury, death or substantial property  
damage.  
Indicates presence of hazards that can cause severe personal injury, death or substantial property  
damage.  
Indicates presence of hazards that will or can cause minor personal injury or property damage.  
Indicates special instructions on installation, operation or maintenance that are important but not  
related to personal injury or property damage.  
4
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
P le a s e re a d b e fo re p ro c e e d in g  
InstallerReadallinstructions, including  
this manual, the Ultra Control Supplement  
and Ultra Vent Supplement, before  
installing.Perform steps in the order given.  
Failure to adhere to the guidelines on this page can result in  
severe personal injury, death or substantial property  
damage.  
User — This manual is for use only by a  
qualified heating installer/service  
technician. Refer to Users Information  
Manual for your reference.  
Wh e n s e rvic in g b o ile r —  
To avoid electric shock,disconnect electrical supplybefore performing  
maintenance.  
User Have this boiler serviced/  
inspected by a qualified service technician,  
at least annually.  
To avoid severe burns, allow boiler to cool before performing  
maintenance.  
Failure to comply with the above could  
result in severe personal injury, death or  
substantial property damage.  
Bo ile r o p e ra t io n —  
Do not block flow of combustion or ventilation air to boiler.  
Should overheating occur or gas supply fail to shut off, do not turn  
off or disconnect electrical supply to circulator. Instead,shut off the  
gas supply at a location external to the appliance.  
The boiler contains ceramic fiber materials.  
Use care when handling these materials per  
instructions on page 29 of this manual.  
Failure to comply could result in severe  
personal injury.  
Do not use this boiler if any part has been under water.Immediately  
call a qualified service technician to inspect the boiler and to replace  
any part of the control system and any gas control that has been  
under water.  
Bo ile r w a t e r —  
When calling or writing about the boiler—  
Please have the boiler model number from  
the boiler rating label and the CP number  
from the boiler jacket.You may list the CP  
number in the space provided on the  
Installation and service certificate found on  
page 27.  
The Ultra heat exchanger is made of aluminum, and requires that  
system pH always be between 7.0 and 8.5 and water chemistry be  
checked.Chemical treatment may be necessary.See page 24 for details.  
Thoroughly flush the system (without boiler connected) to remove  
sediment. The high-efficiency heat exchanger can be damaged by  
build-up or corrosion due to sediment.  
Do not use petroleum-based cleaning or sealing compounds in boiler  
system. Gaskets and seals in the system may be damaged. This can  
result in substantial property damage.  
Consider piping and installation when  
determining boiler location.  
Any claims for damage or shortage in  
shipment must be filed immediately  
against the transportation company by the  
consignee.  
Do not use“homemade cures”orboiler patent medicines.Serious  
damage to boiler, personnel and/or property may result.  
Continualfresh make-up water willreduceboiler life. Mineralbuildup  
in heat exchanger reduces heat transfer, overheats the aluminum  
heat exchanger,and causes failure.Addition of oxygen carried in by  
make-up water can cause internal corrosion. Leaks in boiler or piping  
must be repaired at once to prevent make-up water.  
Do not add cold water to hot boiler. Thermal shock can cause heat  
exchanger to crack.  
Co m m o n w e a lt h o f Ma s s a c h u s e t t s  
Fre e ze p ro t e c t io n flu id s —  
NEVER use automotive or standard glycol antifreeze, even glycol made  
for hydronic systems. Use only freeze-protection fluids recommended in  
the Ultra Boiler Freeze Protection Supplement.  
When theboilerisinstalledwithin theCommonwealth  
of Massachusetts:  
This product must be installed by a licensed  
plumber or gas fitter.  
Follow all guidelines in the Ultra Boiler Freeze Protection Supplement.  
Thoroughly clean and flush any replacement boiler system that has used  
glycol before installing the new Ultra boiler.  
If antifreeze is used, a reduced pressure back-flow  
preventer device shall be used.  
5
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
1
Prepare boiler location  
Installations must comply w ith:  
Provide clearances:  
Local, state, provincial, and national codes, laws,  
regulations and ordinances.  
National Fuel Gas Code, ANSI Z223.1 – latest edition.  
Standard for Controls and Safety Devices for  
Automatically Fired Boilers, ANSI/ASME CSD-1,  
when required.  
Clearancesfrom combustiblematerials  
1. Hot water pipes — at least ½" from combustible  
materials.  
2. Vent pipe — at least 0.20" from combustible  
materials.  
3. See Figure 1 for other clearance minimums.  
National Electrical Code.  
Clearancesfor serviceaccess  
For Canada only: B149.1 or B149.2 Installation Code,  
CSA C22.1 Canadian Electrical Code Part 1 and any  
local codes.  
1. See Figure 1 for recommended service clearances. If  
you do not provide minimum clearances shown, it  
might not be possible to service the boiler without  
removing it from the space.  
The Ultra boiler gas manifold and controls  
met safe lighting and other performance  
criteria when boiler underwent tests  
specified in ANSI Z21.13 — latest edition.  
Ultra boilers, except the Ultra-310, may be  
wall mounted (using special wall mount  
kit) or floor mounted. No clearance is  
required at the rear of the unit, either for  
service or for clearance to combustible  
surfaces.  
Before locating the boiler, check:  
1. Check for nearby connection to:  
System water piping  
Venting connections  
Gas supply piping  
Electrical power  
Figure 1  
Clearances required  
2. Check area around boiler. Remove any combustible  
materials, gasoline and other flammable liquids.  
Failure to keep boiler area clear and free of  
combustible materials, gasoline and other  
flammable liquids and vapors can result in  
severe personal injury, death or substantial  
property damage.  
3. The Ultra boiler must be installed so that gas control  
system components are protected from dripping or  
spraying water or rain during operation or service.  
4. If new boiler will replace existing boiler,check for and  
correct system problems, such as:  
System leaks causing oxygen corrosion or heat  
exchanger cracks from hard water deposits.  
Incorrectly-sized expansion tank.  
Lack of freeze protection in boiler water causing system  
and boiler to freeze and leak.  
6
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
1
Pre p a re b o ile r lo c a t io n  
(continued)  
Flooring and foundation  
Ultra boiler in same space with other gas or  
oil-firedappliances  
1. Follow the National Fuel Gas Code (U. S.) or CSA  
B149.1 and B149.2 (Canada) to size/verify size of the  
combustion/ventilation air openings into the space.  
Flooring  
The Ultra boiler is approved for installation on  
combustible flooring, but must never be installed on  
carpeting.  
The space must be provided with  
combustion/ventilation air openings  
correctly sized for all other appliances  
located in the same space as the Ultra boiler.  
Do not install boiler on carpeting even if  
foundation is used. Fire can result, causing  
severe personal injury, death or substantial  
property damage.  
Replace boiler jacket front door after  
servicing. The boiler front door must be  
securely fastened to the boiler to prevent  
boiler from drawing air from inside the  
boiler room. This is particularly important  
if the boiler is located in the same room as  
other appliances.  
Foundation  
Provide a solid foundation pad, at least 2 inches above  
the floor, if any of the following is true:  
floor can become flooded.  
the floor is dirt, sand, gravel or other loose material.  
the boiler mounting area is severely uneven or sloped.  
The minimum foundation size is:  
Failure to comply with the above warnings  
could result in severe personal injury,death  
or substantial property damage.  
Ultra-80 to -230: 24 inches wide x 20 inches deep.  
Ultra-310: 24 inches wide x 23 inches deep  
24 inches x 20 inches.Foundation may be of wood, brick  
or concrete (minimum 2 inches thick) construction.  
2. Size openings only on the basis of the other appliances  
in the space. No additional air opening free area is  
needed for the Ultra boiler because it takes its  
combustion air from outside(direct vent installation).  
If flooding is possible, elevate boiler sufficiently to prevent  
water from reaching boiler.  
Vent and air piping  
Residential garage installation  
The Ultra boiler requires a special vent system, designed  
for pressurized venting. Ultra boilers are rated ANSI  
Z21.13 Category IV (pressurized vent, likely to condense  
in the vent).  
Precautions  
Take the following special precautions when installing  
the boiler in a residential garage. If the boiler is located in  
a residential garage, per ANSI Z223.1, paragraph 5.1.9:  
You must also install air piping from outside to the boiler  
air intake adapter.The resultant installation is categorized  
as direct vent (sealed combustion). Note prevention of  
combustion air contamination on page 8 when  
considering vent/air termination.  
Mount the boiler with a minimum of 18 inches above  
the floor of the garage to the bottom of the boiler to  
ensure the burner and ignition devices will be no less  
than 18 inches above the floor.  
Locate or protect the boiler so it cannot be damaged  
by a moving vehicle.  
Vent and air must terminate near one another and may  
be vented vertically through the roof or out a side wall.  
You may use any of the vent/air piping methods covered  
in the Ultra Boiler Vent Supplement, included in the  
envelope assembly. Do not attempt to install the Ultra  
boiler using any other means.  
Provide air openings to room:  
Ultra boiler alone in boiler room  
Be sure to locate the boiler such that the vent and air  
piping can be routed through the building and properly  
terminated. The vent/air piping lengths, routing and  
1. No air ventilation openings into boiler room are  
needed when clearances around Ultra boiler are at  
least equal to the SERVICE clearances shown in  
Figure 1. For spaces that do NOT supply this  
clearance, provide two openings as shown in Figure 1.  
Each opening must provide 1 square inch free area  
per 1,000 Btuh of boiler input.  
7
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
1
Pre p a re b o ile r lo c a t io n  
(continued)  
Prevent combustion air  
contamination  
When removing a boiler from  
existing common vent system:  
Do not install the Ultra boiler into a  
common vent with any other appliance.  
This will cause flue gas spillage or appliance  
malfunction, resulting in possible severe  
personal injury, death or substantial  
property damage.  
Install air inlet piping for the Ultra boiler as described in  
the Ultra BoilerVent Supplement.Do not terminate vent/  
air in locations that can allow contamination of  
combustion air. Refer to Table 1 for products and areas  
which may cause contaminated combustion air.  
You must pipe combustion air to the boiler  
air intake. Ensure that the combustion air  
will not contain any of the contaminants  
below. Contaminated combustion air will  
damage the boiler, resulting in possible  
severe personal injury, death or substantial  
property damage. Do not pipe combustion  
air near a swimming pool, for example.  
Also avoid areas subject to exhaust fumes  
from laundry facilities. These areas will  
always contain contaminants.  
Failure to follow all instructions can result  
in flue gas spillage and carbon monoxide  
emissions, causing severe personal injury  
or death.  
At the time of removal of an existing boiler,the following  
steps shall be followed with each appliance remaining  
connected to the common venting system placed in  
operation, whiletheother appliancesremainingconnected  
to the common venting system are not in operation.  
a. Seal any unused openings in the common venting  
system.  
b. Visually inspect the venting system for proper size  
and horizontal pitch and determine there is no  
blockage or restriction, leakage, corrosion or other  
deficiencies which could cause an unsafe condition.  
Table 1 Corrosive contaminants and sources  
c. Test vent system — Insofar as is practical, close all  
building doors and windows and all doors between  
the space in which the appliances remaining  
connected to the common venting system are located  
and other spaces of the building. Turn on clothes  
dryers and any appliance not connected to the  
common venting system. Turn on any exhaust fans,  
such as range hoods and bathroom exhausts, so they  
will operate at maximum speed. Do not operate a  
summer exhaust fan. Close fireplace dampers.  
d. Place in operation the appliance being inspected.  
Follow the lighting instructions. Adjust thermostat  
so appliance will operate continuously.  
e. Test for spillage at draft hood relief opening after 5  
minutes of main burner operation. Use the flame of  
a match or candle, or smoke from a cigarette, cigar,  
or pipe.  
f. After it has been determined that each appliance  
remaining connected to the common venting system  
properly vents when tested as outlined herein, return  
doors, windows, exhaust fans, fireplace dampers, and  
any other gas-burning appliance to their previous  
conditions of use.  
Any improper operation of common venting system  
should be corrected so the installation conforms with  
theNationalFuelGasCode, ANSIZ223.1latest edition.  
Correct by resizing to approach the minimum size as  
determined using the appropriate tables in Part 11 of  
that code. Canadian installations must comply with  
B149.1 or B149.2 Installation Code.  
8
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
2
Prepare boiler  
Ultra-80-LPboilers are factory-equipped  
to operate on propane gas.  
Remove boiler from crate  
Cold weather handling — If boiler has been  
stored in a very cold location (below 0°F) before  
installation, handle with care until the plastic  
components come to room temperature.  
Figure 2  
Installing propane orifice (Ultra-105)  
1. The Ultra boiler is generally easier to handle and maneuver  
after removing from crate.  
2. After removing outer shipping carton from boiler,  
REMOVE jacket front door by loosening two knurled-  
head screws at lower front. Removing the door will prevent  
possible damage to the door during handling.  
3. To remove boiler from pallet (after removing jacket front  
door):  
a. Remove the four lag screws securing shipping brackets.  
b. Unscrew the two rear boiler legs and remove the  
shipping brackets.  
c. Replace legs.  
d. Discard the cardboard protector insert on the rear of  
the boiler.  
Do not drop boiler or bump jacket on floor or  
pallet. Damage to boiler can result.  
1. With boiler on its back, remove jacket front door by  
removing two knurled head screws at lower front. Then  
lift door away from boiler.  
2. Disconnect the gas valve electrical plug.  
3. Remove the 4 screws securing gas valve inlet adapter to  
valve.  
4. Remove (3) TORX screws securing gas valve to venturi  
(Figure 2).  
5. Locate propane orifice disc from conversion kit bag.Verify  
that the stamping on the orifice disk matches the boiler  
size. Place orifice in the black rubber grommet in the side  
of the gas valve and secure in valve (Figure 2).  
Prepare for propane if operating  
on propane — Ultra-80 & -105  
Ultra-80: DO NOT apply the following  
instructions to conversion of Ultra-80 boilers.  
Follow the instructions provided with the  
optional propane conversion kit. The propane  
conversion kit is NOT included as standard  
equipment for the Ultra-80.  
Do not apply the following to conversion of a  
boiler already installed and connected to gas  
supply. For a boiler already installed, you must  
turn off gas supply, turn off power and allow  
boiler to cool before proceeding.You must also  
completely test the boiler after conversion to  
verifyperformanceasdescribed underStartup,”  
Section 6 of this manual. See separate natural  
to propane conversion instructions for  
conversion of an existing boiler.  
6. Reposition gas valve against venturi and replace (3) TORX  
screws securing valve to venturi. Secure gas valve inlet  
adapter to gas valve with 4 screws. Make sure the plastic  
hose is connected from gas valve to inlet elbow.  
Inspect the O-ring between the gas valve and  
gas valve inlet adapter block whenever they are  
disassembled. The O-ring must be in good  
condition and must be installed. Failure to  
comply will cause a gas leak, resulting in severe  
personal injury or death.  
You must install the propane orifice to fire the  
Ultra boiler on propane.Verify when installing  
that the orifice size marking matches boiler  
size. Failure to comply could result in severe  
personal injury, death or substantial property  
damage.  
7. DO NOT attempt to adjust gas valve outlet pressure.  
8. Connect gas valve electrical plug to valve terminals.  
9. After installation is complete, attach the propane  
conversion label (in conversion kit bag) next to the boiler  
rating plate.  
10. Replace jacket front panel.  
9
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
2
Prepare boiler  
(continued)  
Prepare for propane if operating  
on propane — Ultra-155 to -230  
Figure 2a Installing propane orifice (Ultra-155  
and Ultra-230)  
Ultra-80: DO NOT apply the following  
instructions to conversion of Ultra-80  
boilers. Follow the instructions provided  
with the optional propane conversion kit.  
The propane conversion kit is NOT  
included as standard equipment for the  
Ultra-80.  
Do not apply the following to conversion  
of a boiler already installed and connected  
to gas supply.For a boiler already installed,  
you must turn off gas supply, turn off  
power and allow boiler to cool before  
proceeding.You must also completely test  
the boiler after conversion to verify  
performance as described underStartup,”  
Section 6 of this manual. See separate  
natural to propane conversion instructions  
for conversion of an existing boiler.  
Ultra-310 boilers cannot be equipped for  
propane firing as of October, 2003.  
Propane capability should be available in  
2004.  
You must install the propane orifice to fire  
the Ultra boiler on propane. Verify when  
installing that the orifice size marking  
matchesboiler size. Failuretocomplycould  
result in severe personal injury, death or  
substantial property damage.  
Placing floor-mounted boilers  
1. Set boiler in place and check level.  
a. Adjust legs, if necessary to level boiler.  
Placing wall-mounted boilers  
1. With boiler on its back, remove jacket front door by  
removing two knurled head screws at lower front.  
Then lift door away from boiler.  
1. Ultra-80, -105, -155 and -230 boilers can be wall  
mounted. Use only the separately available Ultra  
boiler wall mounting kit and instructions. See  
WARNING below.  
2. Disconnect the gas valve electrical plug.  
The wall must be vertically plumb and  
capable of carrying the weight of the boiler.  
The operating weights are:  
3. Disconnect the gas line union below the gas valve.  
4. Remove(3) TORXscrewssecuringgasvalvetoventuri  
(Figure 2a).  
Ultra-80: 139 pounds.  
Ultra-105: 145 pounds.  
Ultra-155: 181 pounds.  
Ultra-230: 192 pounds.  
5. Locate propane orifice disc from conversion kit bag.  
Verify that the stamping on the orifice disk matches  
the boiler size. Place orifice in the black rubber  
grommet in the side of the gas valve and secure in  
valve (Figure 2).  
6. Reposition gas valve against venturi and replace (3)  
TORX screws securing valve to venturi. Reconnect  
gas line union.  
7. DO NOT attempt to adjust gas valve outlet pressure.  
8. Connect gas valve electrical plug to valve terminals.  
9. After installation is complete, attach the propane  
conversion label (in conversion kit bag) next to the  
boiler rating plate.  
Model Ultra-310 boilers are NOT designed  
for wall mounting.  
Wall mount Ultra boilers only usingWeil-  
McLain Ultra boiler wall-mounting kit and  
accompanying instructions. This kit is not  
supplied as standard equipment with the  
boiler, and must be purchased separately.  
Failure to comply with above could result  
in severe personal injury, death or  
substantial property damage.  
10. Replace jacket front panel.  
10  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
2
Prepare boiler  
(continued)  
Leaks must be repaired at once. Failure to  
do so can damage boiler, resulting in  
substantial property damage.  
Perform hydrostatic pressure test  
Pressure test boiler before permanently attaching water  
or gas piping or electrical supply.  
Do not use petroleum-based cleaning or  
sealing compounds in boiler system.  
Gaskets and seals in the system may be  
damaged. This can result in substantial  
property damage.  
Prepare boiler for test  
1. See Figure 3 for reference in following steps.  
2. Remove supply line tee* and ¾” street elbow from  
accessory bag. Pipe to boiler supply connection as  
shown. Use pipe dope sparingly. (*1" x 1" x ¾" tee  
with Ultra-80 to -230 or 1¼" x 1¼" x ¾" tee with  
Ultra-310)  
3. Temporarily plug the ¾" relief valve tapping in the  
street elbow with a ¾" NPT pipe plug.  
4. Connect a hose to boiler drain valve, the other end  
connected to a fresh water supply. Make sure hose  
can also be used to drain boiler after test.  
5. Connect a nipple and shutoff valve to system supply  
connection on the supply tee. This valve will be used  
to bleed air during the fill.(Valve and nipple are not  
included with boiler.)  
Drain and remove fittings  
1. Disconnect fill water hose from water source.  
2. Drain boiler through drain valve. Remove hose after  
draining.  
3. Remove nipples and valves unless they will remain  
for use in the system piping.  
4. Remove plug from relief valve street elbow. See  
section 3 (page 12) to install relief valve.  
Figure 3  
Hydrostatic test piping connections  
6. Connect a shutoff valve to system return connection.  
(Valve is not included with boiler.)  
7. To avoid getting water on boiler, you may want to  
pipe street elbows on top of shutoff valves and attach  
catch-buckets beneath.  
8. If convenient, install the boiler circulator and any  
other piping compatible with Figure 3 that would  
still allow bleeding air from shutoff valves. Follow  
guidelines in this manual for piping components,  
locations and sizing.  
Fill and pressure test  
1. Open the shutoff valves you installed on supply and  
return connections.  
2. Slowly open boiler drain valve and fresh water supply  
to fill boiler with water. The boiler will fill quickly  
because of its low water content.  
3. When water reaches shutoff valves, close boiler drain  
valve.  
4. Close shutoff valves.  
5. Slowly reopen boiler drain valve until test pressure  
on the pressure/temperature gauge reaches at least  
45 psig, but no higher than 55 psig.  
6. Hold at test pressure for 10 minutes.  
Do not leave boiler unattended. A cold  
water fill could expand and cause excessive  
pressure,resulting in severe personal injury,  
death or substantial property damage.  
7. Make sure constant gauge pressure has been  
maintained throughout test. Check for leaks. Repair  
if found.  
11  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
3
In s t a ll w a t e r p ip in g  
Install relief valve  
General piping information  
1. Install relief valve in ¾" street elbow piped from boiler  
Additional controls,when required  
supply piping tee (Figure 3, page 11). Pipe the relief  
valve only as shown, in the location shown.  
The Ultra control module uses  
temperature sensors to provide both high  
limit protection and modulating  
temperature control. The control module  
also provides low water protection by  
sensing the temperature of the heat  
exchanger. Some codes/jurisdictions may  
require additional external controls for  
high limit and/or low water cutoff  
protection.  
2. Connect discharge piping to safe disposal location,  
following guidelines in theWARNING below.  
To avoid water damage or scalding due to  
relief valve operation:  
Discharge line must be connected to relief  
valve outlet and run to a safe place of  
disposal. Terminate the discharge line in a  
manner that will prevent possibility of  
severe burns or property damage should  
the valve discharge.  
Additional limit control:  
Following standard industry practices, if installation is  
to comply with ASME or Canadian requirements, an  
additional high temperature limit is needed. Consult local  
requirements for other codes/standards to determine if  
needed.  
Discharge line must be as short as possible  
and be the same size as the valve discharge  
connection throughout its entire length.  
1. Install additional high temperature limit constructed  
toprevent atemperaturesettingabove200°Fin system  
supply piping between boiler and isolation valve.  
(Note that the Ultra control module operating limit  
function shuts the boiler down at 190°F or Parameter  
4, whichever is lower.)  
Discharge line must pitch downward from  
the valve and terminate at least 6" above  
the floor drain where any discharge will be  
clearly visible.  
Thedischargelineshallterminateplain, not  
threaded, with a material serviceable for  
temperatures of 375 °F or greater.  
2. See Ultra Control Supplement for wiring.  
a. Iflimit controlistocauseaboiler hard lockout (requiring  
manual reset of Ultra control module), connect isolated  
contact to field control wiring terminals 6 and 8 as  
shown in wiring diagram.  
b. Otherwise, connect isolated contact between  
terminals 6 and 7 for a soft lockout (automatic reset).  
c. If using a manual reset limit control or wiring in the  
manual reset circuit, Parameter 4 should be no closer  
than 20°F to the limit control setting (i.e., no higher  
than 180°F for a 200°F limit setting, for example).  
Do not pipe the discharge to any place  
where freezing could occur.  
No shutoff valve shall be installed between  
therelief valveandboiler,or in thedischarge  
line. Do not plug or place any obstruction  
in the discharge line.  
Test the operation of the valve after filling  
and pressurizing system by lifting the lever.  
Make sure the valve discharges freely.If the  
valve fails to operate correctly, replace it  
with a new relief valve.  
Separate low water cutoff:  
A low water cutoff device is required when boiler is  
installed above piping level or by certain state or local  
codes or insurance companies. Consult local  
requirements to determine.  
Failure to comply with the above guidelines  
could result in failure of the relief valve to  
operate, resulting in possibility of severe  
personal injury, death or substantial  
property damage.  
1. If required, use a low water cutoff designed for water  
installations. Electrode probe-type is recommended.  
2. Purchase low water cutoff and install in tee in supply  
piping above boiler.  
3. See Ultra Control Supplement for wiring.  
a. Iflimit controlistocauseaboiler hard lockout (requiring  
manual reset of Ultra control module), connect isolated  
contact to field control wiring terminals 6 and 8 as  
shown in wiring diagram.  
b. Otherwise, connect isolated contact between  
terminals 6 and 7 for a soft lockout (automatic reset).  
Use two wrenches when tightening water  
piping at boiler, using one wrench to  
prevent the boiler return line or supply line  
from turning. Failure to support the boiler  
piping connections to prevent them from  
turning could cause damage to boiler  
components.  
Backflow preventer:  
Use backflow check valve in cold water supply as required  
by local codes.  
12  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
3
In s t a ll w a t e r p ip in g  
(continued)  
System water piping methods  
Figure 4  
Expansion tank piping  
All piping methods shown in this manual  
use primary/secondary connection to the  
boiler loop. These designs ensure proper  
flow through the Ultra boiler, for the most  
efficient and reliable operation of the boiler  
and the heating system. For other piping  
methods, consult your localWeil-McLain  
representative or refer to separate Ultra  
boiler piping guides.  
Wall-mounted boilers — Piping can exit  
bottom of boiler enclosure. See separate  
wall-mounting instructions for details.  
Expansion tank and make-up water  
1. Ensure expansion tank size will handle boiler and  
system water volume and temperature. Allow 3  
gallons for boiler and its piping.  
Undersized expansion tanks cause system  
water to be lost from relief valve and make-  
up water to be added through fill valve.  
Eventual boiler failure can result due to  
excessive make-up water addition.  
2. Tank must be located as shown in this manual, or  
following recognized design methods. See tank  
manufacturers instructions for details.  
3. Connect the expansion tank to the air separator only  
if the separator is on the suction side of the circulator.  
Always install the system fill connection at the same  
point as the expansion tank connection to the system.  
4. Most piping drawings in this manual show  
diaphragm expansion tanks. See Figure 4 for piping  
from air separator to expansion tank and make-up  
water line using a closed-type expansion tank.  
5. Most chilled water systems are piped using a closed-  
type tank, as shown in Figure 10, page 18.  
Circulators  
The boiler circulator (Taco 007 for Ultra-80 and -105;  
Taco 0011 for Ultra-155,-230,and -310) is shipped loose.  
Locate it either in the return or supply piping, as shown  
in the appropriate piping diagram in this manual.  
Diaphragm (or bladder)expansion tank  
DO NOT use the boiler circulator in any  
location other than the ones shown in this  
manual. The boiler circulator is selected to  
ensure adequate flow through the Ultra  
boiler. Failure to comply could result in  
unreliable performance and nuisance  
shutdowns from insufficient flow.  
1. (Figure 4) Always install an automatic air vent on  
top of the air separator to remove residual air from  
the system.  
Closed-typeexpansion tank  
1. See Figure 4, Alternate, for piping connections when  
using a closed-type expansion tank.  
2. Pitch any horizontal piping up towards tank 1 inch  
per 5 feet of piping. Connect to tank with at least ¾"  
piping to allow room for air to rise.  
Sizing space heat system piping  
1. See Figures 7 through 10, pages 15 – 18, for  
recommended piping. In all diagrams, the space  
heating system is isolated from the boiler loop by the  
primary/secondary connection.  
DO NOT install automatic air vents on  
closed-type expansion tank systems. Air  
must remain in the system and return to  
the tank to provide its air cushion. An  
automatic air vent would cause air to leave 2. Size the piping and components in the space heating  
system, resulting in water-logging the  
expansion tank.  
system using recognized design methods.  
13  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
3
In s t a ll w a t e r p ip in g  
(continued)  
Sizing DHW system piping  
When using the boiler for dedicated DHW  
applications, use the circulator supplied with  
the boiler (007 for Ultra-80/105; 0011 for  
Ultra-155/230/310) to circulate to the water  
heater except where higher flow rates may be  
required for the heater used. Use the following  
method to select a circulator for the water  
heater on combined space heating/DHW  
systems.  
circulators (Taco 007, 0011, 0012, 0013, 0014, B&G PL-36 or equivalent). Use  
these curves along with boiler pressure drop data from Table 2 to size the DHW  
piping and circulator. Or you can use Table 2 for a quick-selection method.  
3. Table 2 uses the available head from the circulators listed to help you select the  
right circulator.  
a. See Figure 5.  
b. H1 is the head loss across the boiler.  
c. H2 is the head loss across the DHW piping.  
d. H3: Table 2 subtracts H1 and H2 from the available head of the circulator. This  
gives the maximum value for H3, head loss across the water heater.  
1. Figure 5 shows recommended DHW piping, as shown in  
Figures 7 through 10, pages 15 – 18. All show direct  
connection of the DHW piping to the boiler because the  
boiler circulator shuts down during DHW operation.  
4. Procedure to select a circulator using Table 2:  
Step 1: From the water heater manufacturers data, find:  
• Required boiler water flow rate, GPM, at 180°F.  
• Pressure drop across the water heater at this flow rate, in feet water column.  
Step 2: Find your boiler model in Table 2. Select a flow rate in column 1 just  
larger than the required flow rate from step 1.  
2. Figure 6 shows the pump curves for suggested DHW  
Step 3: The value in column H3 must be larger than the water heater pressure  
drop from step 1.  
Figure 5  
DHW piping (seeTable 2 for approxi-  
mate head losses)  
Table 2  
Pipe sizing and head losses for DHW applications  
(H1=boiler head loss; H2=piping head loss; H3=maximum  
allowable head loss through water heater based on available head  
of circulator chosen; i.e., Taco 007, 0011, 0012, 0013 or 0014, Bell  
or Gossett PL-36)  
Figure 6  
Pump curves for typical circulators  
suggested for DHW loop  
14  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
3
In s t a ll w a t e r p ip in g  
(continued)  
Zoning with zone valves  
Figure 7  
Zone valve zoning plus optional  
DHW piping  
1. Connect boiler to system as shown in Figure 7 when  
zone valve zoning. The primary/secondary piping  
shown ensures the boiler loop will have sufficient  
flow. It also avoids applying the high head of the  
boiler circulator to the zone valves.  
2. When using a closed-type expansion tank, connect  
the expansion tank and make-up water piping as  
shown in Figure 4, page 13.  
3. ConnectDHW(domestichotwater) pipingtoindirect  
storage water heater as shown.  
The  
PhD Control Module turns off  
space heating during DHW heating. The  
boiler circulator will turn off, preventing  
hot water from circulating to the system.  
The flow/check valve shown on the boiler  
outlet piping prevents gravity circulation  
in the boiler loop during DHW heating.  
4. Controlling the system circulator  
a. To cycle the system circulator from the Ultra PhD  
control module, add a circulator relay wired to the  
boiler circulator terminals as shown in the Ultra Control  
Supplement.  
NOTE 1: To ensure adequate flow rate through the  
boiler,use the following pipe size on all boiler  
loop piping (connecting boiler to and from  
the primary/secondary connection, item 21):  
Ultra-80 or Ultra-105 – 1" or larger.  
Ultra-155 or -230 – 1¼" or larger.  
Ultra-310 – 1½" or larger.  
Use at least the minimum piping size above  
and pipe the boiler using only primary/  
secondary piping as shown. Failure to  
follow these guidelines could result in  
system problems.  
Legend  
Figure 7  
1
2
3
4
5
6
7
8
Ultra boiler  
10 Flow/check valves (with weighted seats to prevent gravity  
circulation)  
Indirect water heater (DHW), if used  
Boiler relief valve (see page 12 for piping details)  
Relief valve discharge piping (see page 12 for details)  
DHW circulator (see page 14 for suggested sizing)  
Isolation valves  
11 Purge/drain valves  
12 Boiler circulator  
13 Zone valves, typical  
20 Make-up water supply  
21 Primary/secondary connection  
System circulator  
Diaphragm (or bladder) type expansion tank (see page 12  
for piping of closed-type expansion tank, if used)  
9
Air separator [with automatic air vent only on systems  
using diaphragm (or bladder) type expansion tank]  
15  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
3
In s t a ll w a t e r p ip in g  
(continued)  
Zoning with circulators  
Figure 8  
Circulator zoning plus optional  
DHW piping  
1. Connect boiler to system as shown in Figure 8 when  
circulator zoning. Theboiler circulator cannot beused  
for a zone. It must supply only the boiler loop.  
2. Install a separate circulator for each zone.  
3. When using a closed-type expansion tank, connect  
the expansion tank and make-up water piping as  
shown in Figure 4, page 13.  
4. ConnectDHW(domestichotwater) pipingtoindirect  
storage water heater as shown.  
The  
PhD Control Module turns off  
space heating during DHW heating. The  
boiler circulator will turn off, preventing  
hot water from circulating to the system.  
The flow/check valve shown on the boiler  
outlet piping prevents gravity circulation  
in the boiler loop during DHW heating.  
NOTE 1: To ensure adequate flow rate through the  
boiler,use the following pipe size on all boiler  
loop piping (connecting boiler to and from  
the primary/secondary connection, item 21):  
Ultra-80 or Ultra-105 – 1" or larger.  
Ultra-155 or -230 – 1¼" or larger.  
Ultra-310 – 1½" or larger.  
Use at least the minimum piping size above  
and pipe the boiler using only primary/  
secondary piping as shown. Failure to  
follow these guidelines could result in  
system problems.  
Legend  
Figure 8  
1
2
3
4
5
6
7
8
Ultra boiler  
10 Flow/check valves (with weighted seats to prevent gravity  
circulation)  
Indirect water heater (DHW), if used  
Boiler relief valve (see page 12 for piping details)  
Relief valve discharge piping (see page 12 for details)  
DHW circulator (see page 14 for suggested sizing)  
Isolation valves  
11 Purge/drain valves  
12 Boiler circulator  
14 Zone circulators, typical  
20 Make-up water supply  
21 Primary/secondary connection  
System circulator  
Diaphragm (or bladder) type expansion tank (see page 12  
for piping of closed-type expansion tank, if used)  
9
Air separator [with automatic air vent only on systems  
using diaphragm (or bladder) type expansion tank]  
16  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
3
In s t a ll w a t e r p ip in g  
(continued)  
Radiant heating applications  
Figure 9  
Typical radiant heating system  
piping plus optional DHW  
1. The Ultra boiler is ideal for use in radiant heating. The Ultra boilers  
unique heat exchanger design allows it to work well even in condensing  
mode. So there is no need to regulate boiler return water temperature in  
radiant heating applications.  
2. Connect boiler to system as shown in Figure 9 for typical radiant heating  
applications. The primary/secondary piping shown ensures the boiler  
loop will have sufficient flow. Size the system piping and circulator to  
provide the flow and pressure drop needed for the radiant system.  
3. Add the high limit control (Figure 9, item 22) to ensure supply water  
temperature will not exceed the maximum allowable for the radiant  
system. Wirethislimit controlbetween lowvoltageterminalstrip terminals  
6 and 7.  
4. When using a closed-type expansion tank, connect the expansion tank  
and make-up water piping as shown in Figure 4, page 13.  
5. Connect DHW (domestic hot water) piping to indirect storage water  
heater as shown.  
The  
PhD Control Module turns off space heating during  
DHW heating. The boiler circulator will turn off, preventing  
hot water from circulating to the system. The flow/check valve  
shown on the boiler outlet piping prevents gravity circulation  
in the boiler loop during DHW heating.  
6. Controlling the system circulator  
a. To cycle the system circulator from the Ultra PhD control module, add a  
circulator relay wired to the boiler circulator terminals as shown in the Ultra  
Control Supplement  
7. Setting boiler outlet water target temperature.  
a. Follow procedure in Ultra Control Supplement to set space heating target  
temperature to the desired supply temperature for the system. For outdoor  
reset operation, install and connect the outdoor temperature sensor supplied  
with the boiler.  
NOTE 1: To ensure adequate flow rate through the boiler,use the following  
pipe size on all boiler loop piping (connecting boiler to and from  
the primary/secondary connection, item 21):  
Ultra-80 or Ultra-105 – 1" or larger.  
Use at least the minimum piping size at left  
and pipe the boiler using only primary/  
secondary piping as shown. Failure to  
follow these guidelines could result in  
system problems.  
Ultra-155 or -230 – 1¼" or larger.  
Ultra-310 – 1½" or larger.  
Legend  
Figure 9  
1
2
3
4
5
6
7
8
Ultra boiler  
10 Flow/check valves (with weighted seats to prevent gravity  
circulation)  
Indirect water heater (DHW), if used  
Boiler relief valve (see page 12 for piping details)  
Relief valve discharge piping (see page 12 for details)  
DHW circulator (see page 14 for suggested sizing)  
Isolation valves  
11 Purge/drain valves  
12 Boiler circulator  
13 Zone valves, when used (zoning may also be done using  
manifold-mounted valve actuators)  
20 Make-up water supply  
System circulator  
21 Primary/secondary connection  
Diaphragm (or bladder) type expansion tank (see page 12 for piping of closed-  
type expansion tank, if used)  
22 High limit temperature control, set to protect radiant tubing  
9
Air separator [with automatic air vent only on systems using diaphragm (or  
bladder) type expansion tank]  
17  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
3
In s t a ll w a t e r p ip in g  
(continued)  
Chilled water systems  
Figure 10 Chilled water system plus optional  
DHW piping  
1. Install boiler so that chilled medium is piped in parallel with the heating  
boiler. Use appropriate valves to prevent chilled medium from entering  
boiler. See Figure 10 for typical installation of balancing valve and check  
valve.  
2. The space heating system may be zoned with circulators if a separate  
circulator is supplied for the chilled water loop.  
3. If boiler is connected to heating coils located in air handling units where  
they can be exposed to refrigerated air, use flow control valves or other  
automatic means to prevent gravity circulation during cooling cycle.  
Follow these piping guidelines below to ensure chilled water  
does not enter the boiler loop.  
Chilled medium, if used, is piped in parallel with heating boiler  
as shown in Figure 10. Use appropriate valves to prevent chilled  
medium from entering boiler.  
If boiler is connected to heating coils located in air handling  
units where they can be exposed to refrigerated air, use flow  
control valves or other automatic means to prevent gravity  
circulation during cooling cycle.  
NOTE 1: To ensure adequate flow rate through the boiler,use the following  
pipe size on all boiler loop piping (connecting boiler to and from  
the primary/secondary connection, item 21):  
Ultra-80 or Ultra-105 – 1" or larger.  
Ultra-155 or -230 – 1¼" or larger.  
Ultra-310 – 1½" or larger.  
Use at least the minimum piping size above and pipe the boiler  
using only primary/secondary piping as shown. Failure to  
follow these guidelines could result in system problems.  
Legend  
Figure 10  
1
2
3
4
5
6
7
9
Ultra boiler  
12 Boiler circulator  
Indirect water heater (DHW), if used  
Boiler relief valve (see page 12 for piping details)  
Relief valve discharge piping (see page 12 for details)  
DHW circulator (see page 14 for suggested sizing)  
Isolation valves  
13 Zone valves, typical  
15 Closed-type expansion tank  
16 Water chiller  
17 Check valve  
18 Strainer  
System circulator  
19 Balancing valve  
Air separator (DO NOT use automatic air vents on systems fitted with closed-  
type tanks)  
20 Make-up water supply  
21 Primary/secondary connection  
10 Flow/check valves (with weighted seats to prevent gravity circulation)  
11 Purge/drain valves  
18  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
4
Venting, com bustion air & condensate line  
Install vent and combustion air  
piping  
Figure 11 Condensate trap assembly  
Ultra Boiler must be vented and supplied  
with combustion and ventilation air as  
described in Weil-McLain Ultra BoilerVent  
Supplement (included in envelope  
assembly). Ensure the vent and air piping  
and the combustion air supply comply  
with these instructions regarding vent  
system, air system and combustion air  
quality. See also Section 1 of this manual.  
Inspect finished vent and air piping  
thoroughly to ensure all are airtight and  
comply with the instructions provided and  
with all requirements of applicable codes.  
c. Apply a second coat of cement to both surfaces. Avoid  
Failure to provide a properly-installed vent  
using too much cement on sockets to prevent cement  
and air system will cause severe personal  
buildup inside.  
injury or death.  
d. With cement still wet, insert pipe into fitting, twisting  
¼ turn. Make sure pipe is fully inserted.  
e. Wipe excess cement from joint. Check joint to be sure  
a smooth bead of cement shows around the entire  
joint.  
Prepare condensate fittings  
5. See Figure 11.  
1. Remove PVC fittings and gasket from the accessories 6. Assemble the ½" PVC nipple to the PVC reducing  
bag.  
elbow as shown.  
2. Deburr and chamfer outside and inside of ½" x 1¼" 7. Allow joint to dry completely.Then slide gasket over  
PVC nipple to ensure even cement distribution when  
joining.  
3. Clean nipple ends and all fittings. Dry thoroughly.  
nipple as shown.  
8. Slide nipple through jacket condensate line hole to  
position as shown in Figure 13, page 20.  
4. For each joint in the condensate line, apply the 9. Cement the ½" tee to the protruding ½" nipple. Be  
following.Assemble parts ONLY in the order given.  
a. Apply primer liberally to both joint surfaces — pipe  
end and fitting socket.  
b. Whileprimer isstilldamp, lightlyapplyapprovedcement  
to both surfaces in a uniform coating.  
sure both nipple and reducing elbow finish upright.  
IMPORTANT: Firmly press the reducing elbow and  
the tee together while the cement sets to ensure the  
gasket is securely compressed. The gasket ensures the  
jacket enclosure is airtight at this location.  
19  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
4
Venting, com bustion air & condensate line  
(continued)  
Connect condensate drain  
Figure 12 Condensate drain — Ultra-80 & -105  
1. Remove condensate trap line from bag. Prepare and  
install per page 19.Secure to jacket by attaching PVC  
tee as shown in Figure 13.  
2. Slide trap line onto flue outlet condensate connection  
and PVC reducing elbow as shown in Figure 12, 13  
or 14. Secure with hose clamps.  
3. Connect condensate drain tubing to the ½" PVC tee  
and run to floor drain or condensate pump. Use ½"  
PVC or CPVC pipe; or 5/8" I.D. tubing.  
Use materials approved by the authority  
having jurisdiction. In the absence of other  
authority, PVC and CPVC pipe must  
complywith ASTMD1785, F441or D2665.  
Cement and primer must comply with  
ASTM D2564 or F493. For Canada, use  
CSA or ULC certified PVC or CPVC pipe,  
fittings and cement.  
Figure 13 Condensate drain — Ultra-155 & -230  
(PVC tee installation shown applies  
to all models))  
4. Leave the top of the ½" tee OPEN. This is needed as a  
vacuum break.  
5. When installing a condensate pump, select one  
approved for use with condensing boilers and  
furnaces. The pump should have an overflow switch  
to prevent property damage from condensate spillage.  
6. Condensatefrom theUltraboiler willbeslightlyacidic  
(typically with a pH from 3.2 to 4.5). Install a  
neutralizing filter if required by local codes.  
The condensate line must remain  
unobstructed, allowing free flow of  
condensate. If condensate is allowed to  
freeze in the line or if the line is obstructed  
in any other manor, condensate can exit  
from the boiler tee, resulting in potential  
water damage to property.  
Figure 14 Condensate drain — Ultra-310  
20  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
5
Ga s p ip in g  
Connecting gas supply piping  
4. Purge all air from gas supply piping.  
5. Before placing boiler in operation, check boiler and  
its gas connection for leaks.  
1. Remove jacket front panel and refer to Figure 15 to  
pipe gas to boiler.  
a. Close manual main shutoff valve during any pressure  
testing at less than 13" w.c.  
b. Disconnect boiler and gas valve from gas supply piping  
during any pressure testing greater than 13" w.c.  
a. Install ground joint union for servicing, when required.  
b. Install manual shutoff valve in gas supply piping outside  
boiler jacket when required by local codes or utility  
requirements.  
c. In Canada — When using manual main shutoff valve,  
it must be identified by the installer.  
Do not check for gas leaks with an open  
flame — use bubble test. Failure to use  
bubble test or check for gas leaks can cause  
severe personal injury,death or substantial  
property damage.  
2. Wall-mounted boilers  
a. Refer to separate Ultra Boiler Wall-mounting  
instructions.  
b. Gas connection may enter from the bottom of boiler  
as explained in the Wall-mounting instructions.  
3. Support piping with hangers, not by boiler or its  
accessories.  
6. Use pipe dope compatible with propane gases. Apply  
sparingly only to male threads of pipe joints so that  
pipe dope does not block gas flow.  
Failure to apply pipe dope as detailed above  
can result in severe personal injury, death  
or substantial property damage.  
Figure 15 Connect gas supply piping  
DO NOT adjust or attempt to measure  
gas valve outlet pressure. The gas valve is  
factory-set for the correct outlet pressure.  
This setting is suitable for natural gas and  
propane, requiring no field adjustment.  
Attemptingtoalter or measurethegasvalve  
outlet pressure could result in damage to  
the valve, causing potential severe personal  
injury, death or substantial property  
damage.  
Ultra boilers are shipped ready to fire  
natural gas ONLY.(Exception: Ultra-80LP  
is propane-ready.) You must install the  
propane orifice if the boiler will be  
connected to propane. See page 9. Failure  
to comply could result in severe personal  
injury, death or substantial property  
damage.  
Use two wrenches when tightening gas piping at boiler,using one wrench to prevent the boiler gas line  
connection from turning. Failure to support the boiler gas connection pipe to prevent it from turning  
could damage gas line components.  
21  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
5
Ga s p ip in g  
(continued)  
Natural Gas:  
Propane Gas:  
Ultra boilers are shipped ready to fire  
Pipe sizing for natural gas  
natural gas ONLY (exception:Ultra-80-LP  
is propane-ready). You must install the  
propane orifice if the boiler will be  
connected to propane. See page 9. Failure  
to comply could result in severe personal  
injury, death or substantial property  
damage.  
1. Refer to Table 4for pipe length and diameter. Base on  
rated boiler input (divide by 1,000 to obtain cubic  
feet per hour).  
a. Table 4 is only for natural gas with specific gravity 0.60,  
with a pressure drop through the gas piping of 0.30"  
w.c.  
b. For additional gas pipe sizing information, refer to  
ANSI Z223.1 (or B149.1 or B149.2 for Canadian  
installations).  
Pipe sizing for natural gas  
1. Contact gas supplier to size pipes, tanks and 100%  
lockup gas pressure regulator.  
Natural gas supply pressure requirements  
1. Pressure required at gas valve inlet pressure port:  
Propanesupplypressurerequirements  
1. Adjust propane supply regulator provided by gas  
supplier for 13" w.c. maximum pressure.  
Maximum: 13" w.c. with no flow (lockup) or with  
boiler on  
Minimum: 5" w.c.with gas flowing (verify during boiler  
startup, while boiler is at high fire)  
2. Pressure required at gas valve inlet pressure port:  
Maximum: 13" w.c. with no flow (lockup) or with  
boiler on  
Minimum: 4" w.c.with gas flowing (verify during boiler  
startup, while boiler is at high fire)  
2. Install 100% lockup gas pressure regulator in supply  
line if inlet pressure can exceed 13" w.c. at any time.  
Adjust lockup regulator for 13" w.c.maximum.  
Table 4 Pipe capacity for 0.60 specific gravity natural gas  
Capacity of pipe for pipe size of:  
(Capacity in cubic feet gas per hour)  
Gas pipe  
length  
(feet)  
½"  
¾"  
1"  
1¼"  
1½"  
10  
20  
132  
92  
73  
63  
56  
45  
38  
31  
278  
190  
152  
130  
115  
93  
520  
350  
285  
245  
215  
175  
150  
120  
1050  
730  
590  
500  
440  
360  
305  
250  
1600  
1100  
860  
760  
670  
545  
460  
380  
30  
40  
50  
75  
100  
150  
79  
64  
22  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
6
S t a rt u p  
Check/control water chemistry  
2. Local codes may require back flow preventer or actual  
disconnect from city water supply.  
Do not use petroleum-based cleaning or sealing  
3. When using freeze protection fluid with automatic fill, install a  
water meter to monitor water make-up. Freeze protection fluid  
may leak before the water begins to leak, causing concentration  
to drop, reducing the freeze protection level.  
compounds in boiler system. Damage to elastomer  
seals and gaskets in system could occur,resulting in  
substantial property damage.  
Before filling the boiler and system with water,verify  
the following. Failure to comply could result in boiler  
failure or unreliable operation.  
Fill and test water system  
Water pH between 7.0 and 8.5  
1. Fill system only after ensuring the water meets the requirements  
of this manual.  
2. Close manual and automatic air vents and boiler drain valve.  
3. Fill to correct system pressure. Correct pressure will vary with  
each application.  
1. Maintain boiler water pH between 7.0 and 8.5. Check with  
litmus paper or have chemically analyzed by water treatment  
company.  
2. If pH differs from above, consult local water treatment  
company for treatment needed.  
a. Typical cold water fill pressure for a residential system is 12 psi.  
b. Pressure will rise when boiler is turned on and system water  
temperature increases. Operating pressure must never exceed 25 psig.  
Hardness less than 7 grains  
1. Consult local water treatment companies for unusually hard  
water areas (above 7 grains hardness).  
4. At initial fill and during boiler startup and testing, check system  
thoroughly for any leaks. Repair all leaks before proceeding  
further.  
Chlorine concentration less than 200 ppm  
Eliminate all system leaks. Continual fresh make-up  
water will reduce boiler life. Minerals can build up in  
sections, reducing heat transfer, overheating heat  
exchanger, and causing heat exchanger failure.  
1. Filling with chlorinated fresh water should be acceptable since  
drinking water chlorine levels are typically less than 5 ppm.  
2. Do not use the boiler to directly heat swimming pool or spa  
water.  
3. Do not fill boiler or operate with water containing chlorine in  
excess of 200 ppm.  
5. The system may have residual substances that could affect  
water chemistry.After the system has been filled and leak tested,  
verify water pH and chlorine concentrations are acceptable.  
Clean system to remove sediment  
1. You must thoroughly flush the system (without boiler  
connected) to remove sediment. The high-efficiency heat  
exchanger can be damaged by buildup or corrosion due to  
sediment.  
2. For zoned systems, flush each zone separately through a purge  
valve. (If purge valves and isolation valves are not already  
installed, install them to properly clean the system.)  
Purge air from water system  
1. Purge air from system:  
a. Connect a hose to the purge valve (see purge/drain valves, item 11,  
in piping diagrams on pages 15 through 18. Route hose to an area  
where water can drain and be seen.  
b. Close the boiler or system isolation valve between the purge valve  
and fill connection to the system.  
c. Close zone isolation valves.  
d. Open quick-fill valve on cold water make-up line.  
e. Open purge valve.  
3. Flush system until water runs clean and you are sure piping is  
free of sediment.  
Test/replacefreezeprotectionfluid  
f. One zone at a time, open the isolation valves. Allow water to run  
through the zone, pushing out the air. Run until no noticeable air  
flow is present. Close the zone isolation valves and proceed with the  
next zone. Follow this procedure until all zones are purged.  
g. Close the quick-fill water valve and purge valve and remove the  
hose. Open all isolation valves. Watch that system pressure rises to  
correct cold-fill pressure.  
h. After the system has operated for a while, eliminate any residual air  
by using the manual air vents located throughout the system.  
i. If purge valves are not installed in system, open manual air vents in  
system one at a time, beginning with lowest floor. Close vent when  
water squirts out. Repeat with remaining vents.  
1. For systems using freeze protection fluids, follow guidelines in  
Ultra Boiler Freeze Protection Supplement.  
Freeze protection (when used)  
NEVER use automotive or standard glycol antifreeze,  
even glycol made for hydronic systems. Use only  
freeze-protection fluids recommended in the Ultra  
Boiler Freeze Protection Supplement. Follow all  
guidelines in the Freeze Protection Supplement, and  
thoroughly clean and flush any replacement boiler  
system that has used glycol before installing the new  
Ultra boiler.  
2. Open automatic air vent (diaphragm-type or bladder-type  
expansion tank systems only) one turn.  
3. Open other vents:  
1. Determine freeze protection fluid quantity using total system  
water content, following fluid manufacturerss instructions.  
Boiler water content is listed on page 43. Remember to include  
expansion tank water content.  
a. Starting on the lowest floor, open air vents one at a time until water  
squirts out.  
b. Repeat with remaining vents.  
4. Refill to correct pressure.  
23  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
6
S t a rt u p  
(continued)  
Check for gas leaks  
Final checks before starting boiler  
Before starting the boiler, and during initial operation, smell  
Read the Ultra Control Supplement to familiarize  
yourself with Ultra PhD control module operation.  
Read OperatingInstructionsin ControlSupplement  
for proper steps to start boiler.  
near the floor and around the boiler for gas odorant or any  
unusual odor. Remove boiler front door and smell interior of  
boiler enclosure. Do not proceed with startup if there is any  
indication of a gas leak. Repair any leak at once.  
Verify the boiler and system are full of water and all  
system components are correctly set for operation.  
DO NOT adjust or attempt to measure gas valve outlet pressure.  
The gas valve is factory-set for the correct outlet pressure. This  
setting is suitable for natural gas and propane, requiring no  
field adjustment. Attempting to alter or measure the gas valve  
outlet pressure could result in damage to the valve, causing  
potential severe personal injury,death or substantial property  
damage.  
Verify the preparation procedures of section 6,  
pages 23 and 24 have been completed.  
Fill vent condensate trap with water (by removing  
hose clamp and hose at PVC reducing elbow).  
Replace hose on PVC reducing elbow and tighten  
clamp.  
Propane boilers only — Your propane supplier mixes an  
odorant with the propane to make its presence detectable. In  
some instances, the odorant can fade, and the gas may no  
longer have an odor. Before startup (and periodically  
thereafter), have the propane supplier verify the correct odorant  
level in the gas.  
Verify electrical connections are correct and securely  
attached.  
Inspect vent piping and air piping for signs of  
deterioration from corrosion, physical damage or  
sagging.Verify air piping and vent piping are intact  
and correctly installed per Ultra Boiler Vent  
Supplement.  
Check thermostat circuit(s)  
1. Disconnect the two external wires connected to the boiler thermostat  
terminals (low voltage terminal strip terminals 5 and 6).  
2. Connect a voltmeter across these two incoming wires. Close each  
thermostat, zone valve and relay in the external circuit one at a time and  
check the voltmeter reading across the incoming wires.  
To start the boiler  
1. Turn OFF Power switch on Ultra display panel. Turn  
on power to boiler.  
2. Read and follow the Operating Instructions in the  
Ultra Control Supplement.  
3. There should NEVER be a voltage reading.  
4. If a voltage does occur under any condition, check and correct the external  
wiring. (This is a common problem when using 3-wire zone valves.)  
If boiler does not start correctly  
5. Once the external thermostat circuit wiring is checked and corrected if  
necessary, reconnect the external thermostat circuit wires to boiler low  
voltage terminal strip terminals 5 and 6. Allow the boiler to cycle.  
1. Check for loose connections, blown fuse or service  
switch off?  
2. Is external limit control (if used) open? Is boiler water  
temperature above 200 °F?  
Inspect/fill condensate system  
3. Is thermostat set below room temperature?  
4. Is gas turned on at meter or boiler?  
Inspect/check condensatelines and fittings  
5. Is incoming gas pressure less than 4" w.c.for natural  
gas or 5” w.c. for propane?  
1. Inspect the condensate drain line,condensate PVC fittings and condensate  
trap. (See page 20 for component locations.)  
6. Are parameters set correctly as instructed in the Ultra  
Control Supplement?  
2. Pour water into the top of the boilers ½" PVC condensate tee and check  
for any leaks in the condensate drain line or fittings. Repair any leaks.  
If none of the above corrects the problem, refer to  
Troubleshooting in the Ultra Control Supplement.  
Fill condensate trap with water  
1. Loosen the hose clamp securing the right end of the condensate trap to  
the PVC reducing elbow (see page 20).  
2. Slide the trap hose end off of the elbow.  
3. Fill the trap with fresh water to within a inch of the end of the hose.  
4. Replace trap hose on PVC reducing elbow and tighten the hose clamp.  
The condensate trap (page 3, item 23a) must be filled with water  
during all times of boiler operation to avoid flue gas emission  
from the condensate drain line. Failure to fill the trap could  
result in severe personal injury or death.  
24  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
6
S t a rt u p  
(continued)  
Check system and boiler  
Check flame & combustion  
1. Press and hold both the Ultra control panel “Mode” and “+” buttons  
simultaneously until“H”appears.  
Check water piping  
1. Check system piping for leaks. If found, shut down  
boiler and repair immediately. (SeeWARNINGS on  
page 23 regarding failure to repair leaks.)  
2. TheHin the first digit of the display means the boiler will operate at  
high fire when the blower speed reaches maximum.  
3. Look at the flame through the flame inspection window. The high fire  
flame should be blue and should be stable. The burner surface should be  
covered with orange dots.  
2. Vent any remaining air from system using manual  
vents. Air in the system will interfere with circulation  
and cause heat distribution problems and noise.  
4. Remove the flue temperature sensor from the flue pipe and insert a  
combustion test probe.  
5. Testing is suggested for either CO2 or O2 and for CO. The values should  
be in the range listed in the table below. The CO should not exceed 100  
ppm when combustion is correct.  
Check vent piping and air piping  
1. Check for gas-tight seal at every connection and seam  
of air piping and vent piping.  
Venting system must be sealed gas-tight to  
prevent flue gas spillage and carbon  
monoxide emissions which will result in  
severe personal injury or death.  
If combustion at either high or low fire is outside the range  
given below, shut down the boiler and contact your localWeil-  
McLain representative. Failure to comply could result in severe  
personal injury, death or substantial property damage.  
Check gas piping  
1. Check around the boiler for gas odor following the  
procedure of page 21 of this manual.  
If you discover evidence of any gas leak,  
shut down the boiler at once. Find the leak  
source with bubble test and repair  
immediately.Do not start boiler again until  
corrected. Failure to comply could result  
in severe personal injury, death or  
substantial property damage.  
6. Measure natural gas input:  
a. Operate boiler 10 minutes.  
b. Turn off other appliances.  
c. At natural gas meter, measure time (in seconds) required to use one cubic  
Propane boilers — verify conversion  
1. Verify propane orifice has been installed per Propane  
Conversion instructions.  
foot of gas.  
3600 x 1000  
=
Btuh  
d. Calculate gas input:  
number of seconds from step c  
e. Btuh calculated should approximate input rating on boiler rating label.  
DO NOT adjust or attempt to measure  
gas valve outlet pressure. The gas valve is  
factory-set for the correct outlet pressure.  
This setting is suitable for natural gas and  
propane, requiring no field adjustment.  
Attemptingtoalter or measurethegasvalve  
outlet pressure could result in damage to  
the valve, causing potential severe personal  
injury, death or substantial property  
damage.  
7. Press and hold the Ultra control panel “Mode” and “-” buttons  
simultaneously until the display shows“L”.  
8. The“Lin the first digit means the boiler will operate at low fire when the  
blower speed reaches minimum.  
9. Look at the flame through the flame inspection window. The low fire  
flame should be stable and evenly distributed over burner surface with a  
uniform orange color.  
10. Repeat the combustion test of steps 4 and 5 above.  
11. Press and hold the “+” and “-” buttons to return boiler to automatic  
firing.  
12. Replace flue gas temperature sensor.  
Ultra boilers are shipped ready to fire  
natural gas ONLY. Exception: The Ultra-  
80LP is factory-equipped to fire propane.  
You must install the propane orifice if the  
boiler will be connected to propane. See  
page 9. Failure to comply could result in  
severe personal injury,death or substantial  
property damage.  
You must replace the flue gas temperature sensor to prevent  
flue gas spillage into the boiler enclosure. Failure to comply  
could result in severe personal injury, death or substantial  
property damage.  
Adjust and test boiler controls  
1. Follow instructions in the Ultra Control Supplement to set and verify  
operation of the boiler controls.  
25  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
7
Ch e c k-o u t /s t a rt u p ve rific a t io n  
Boiler and heat distribution units filled with water? Set additional field-installed limit control(s) to  
system temperature requirements? Adjusted  
balancing valves and controls to provide design  
temperature to system?  
Water chemistry verified per page 23?  
Automatic air vents, if used,open one full turn?  
Air purged from system?  
For multiple zones, adjusted for correct flow in each  
zone?  
Verified thermostat heat anticipator (if available)  
set properly? Refer to Ultra Control Supplement.  
Air purged from gas piping? Piping checked for  
leaks?  
Cycled boiler with thermostat (and with DHW  
aquastat, if installed) — Raised to highest setting  
and verified boiler goes through normal startup  
cycle? Lowered to lowest setting and verified boiler  
goes off?  
Propane orifice installed for propane firing and  
propane conversion label affixed to jacket?  
Ultra boilers are shipped ready to fire  
natural gas ONLY. Exception: The Ultra-  
80LP is factory-equipped to fire propane.  
You must install the propane orifice or  
conversion kit (Ultra-80NG) if the boiler  
will be connected to propane. See page 9.  
Failure to comply could result in severe  
personal injury, death or substantial  
property damage.  
Measured natural gas input? (per page 25)  
Checked incoming gas pressure by connecting  
manometer to gas valve ahead of boiler? (Gas  
pressure must be at least 5 inches w.c. for natural  
gas, and 4 inches w.c. for propane, with boiler  
operating at high fire, and no more than 13 inches  
w.c. with boiler operating or boiler off.)  
Thermostat circuit wiring checked to ensure there  
are no stray voltages per page 24, “Check  
Thermostat Wires?”  
Observed several operating cycles for proper  
operation.  
Followed Operating Instructions in Ultra Control  
Set room thermostat to desired room temperature  
(and DHW aquastat, if installed, to desired DHW  
storage temperature)?  
Supplement?  
Burner flame and combustion verified per page 25?  
Reviewed all instructions shipped with this boiler  
with owner or maintenance person?  
Verified control operation for space heating and  
DHW (if used) per Ultra Control Supplement?  
Fill in Installation certificate on page 27.  
Tested additional field-installed controls — If boiler  
has a low water cutoff, additional high limit or other  
controls, tested for operation as outlined by  
manufacturer? (Boiler should be operating and  
should go off when controls are tested. Verify  
controls cause soft lockout or hard lockout as  
desired.)  
Return instructions to envelope and give to owner  
or place inside boiler housing.  
26  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
7
Ch e c k-o u t /s t a rt u p ve rific a t io n  
In s t a lla t io n c e rt ific a t e  
Boiler model  
CP number  
Date installed  
__________________  
___________  
Comments:  
_______________________________________  
_______________________________________  
_______________________________________  
_______________________________________  
_______________________________________  
_______________________________________  
_______________  
Measured Btuh input ____________ Fuel: Natural Gas Propane  
Installation instructions have been followed.  
Check out sequence has been performed.  
Above information is certified to be correct.  
Information received and left with owner/maintenance person  
Installer  
________________________________(company) _____________________(phone)  
________________________________(address)  
________________________________(address)  
__________________________________  
(installers signature)  
27  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
8
An n u a l s t a rt u p a n d g e n e ra l m a in t e n a n c e  
Table 5 Service and maintenance schedules  
Follow the Service and maintenance procedures given throughout this manual and in component  
literature shipped with the boiler. Failure to perform the service and maintenance could result in  
damage to the boiler or system. Failure to follow the directions in this manual and component literature  
could result in severe personal injury, death or substantial property damage.  
28  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
8a  
An n u a l s t a rt u p  
The boiler should be inspected and started annually, at the beginning of the heating season, only by a  
qualified service technician.In addition, the maintenance and care of the boiler designated in Table 5  
and explained on the following pages must be performed to assure maximum boiler efficiency and  
reliability. Failure to service and maintain the boiler and system could result in equipment failure.  
Electrical shock hazard — Turn off power to the boiler before any service operation on the boiler except  
as noted otherwise in this instruction manual. Failure to turn off electrical power could result in  
electrical shock, causing severe personal injury or death.  
Ha n d lin g c e ra m ic fib e r m a t e ria ls  
REMOVAL OF COMBUS TION CHAMBER LINING  
The combustion chamber lining in this product contains ceramic fiber material. Ceramic fibers can be  
converted to cristobalite in very high temperature applications. The International Agency for Research  
on Cancer (IARC) has concluded, "Crystalline silica inhaled in the form of quartz or cristobalite from  
occupational sources is carcinogenic to humans (Group 1).":  
Avoid breathing dust and contact with skin and eyes.  
Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for  
cristobalite at the time this document was written. Other types of respirators may be needed depending on  
the job site conditions. Current NIOSH recommendations can be found on the NIOSH web site at http://  
are also listed on this web site.  
Wear long-sleeved,loose fitting clothing,gloves,and eye protection.  
Apply enough water to the combustion chamber lining or base insulation to prevent airborne dust.  
Remove combustion chamber lining or base insulation from the boiler and place it in a plastic bag for disposal.  
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.  
NIOS H s t a t e d Firs t Aid .  
Eye: Irrigate immediately  
Breathing: Fresh air.  
Address reported problems  
Inspect boiler interior  
1. Inspect any problems reported by owner and correct 1. Remove jacket front door and inspect interior of  
before proceeding.  
boiler.  
2. Remove the venturi air inlet silencer and clean if  
necessary.Replace silencer.  
3. Vacuum any sediment from the inside of the boiler  
and components. Remove any obstructions.  
Inspect boiler area  
1. Verify that boiler area is free of any combustible  
materials, gasoline and other flammable vapors and  
liquids.  
2. Verify that air intake area is free of any of the  
contaminants listed on page 8 of this manual. If any  
of these are present in the boiler intake air vicinity,  
they must be removed. If they cannot be removed,  
reinstall the air and vent lines per this manual and the  
Ultra Boiler Vent Supplement.  
Do not use solvents to clean any of the  
boiler components. The components could  
be damaged, resulting in unreliable or  
unsafe operation.  
29  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
8a  
An n u a l s t a rt u p  
(continued)  
Clean condensate trap  
Check water system  
1. Loosen condensate trap line hose clamps and remove  
trap line.  
2. Empty water from trap line and inspect. Flush out if  
needed with fresh water.  
3. Check condensate elbow and tee and condensate line  
to drain. Flush if necessary to clean.  
1. Verify all system components are correctly installed and operational.  
2. Check the cold fill pressure for the system. Verify it is correct (usually  
around 12 psig).  
3. Watch the system pressure as the boiler heats up (during testing) to  
ensure pressure doesnt rise too high. Excessive pressure rise indicates  
expansion tank sizing or performance problem.  
4. Replace condensate trap line and tighten hose clamps.  
5. Fill trap with fresh water by pouring into upturned  
end of PVC condensate tee.  
4. Inspect automatic air vents and air separators. Remove air vent caps and  
briefly press push valve to flush vent. Replace caps. Make sure vents do  
not leak. Replace any leaking vents.  
Check all piping for leaks  
Check expansion tank  
Eliminate all system or boiler leaks. 1. Expansion tanks provide space for water to move in and out as the  
Continual fresh make-up water will reduce  
boiler life. Mineralscan build up in sections,  
reducing heat transfer, overheating heat  
exchanger, and causing heat exchanger  
failure. Leaking water may also cause severe  
property damage.  
heating system water expands due to temperature increase or contracts  
as the water cools. Tanks may be open, closed or diaphragm or bladder  
type. See section 3 of this manual for suggested best location of expansion  
tanks and air eliminators.  
Open-type — located above highest radiator or baseboard unit, usually  
in the attic or closet. Has a gauge glass and overflow pipe to a drain.  
Closed-type — welded gas tight and located above boiler.Tank is partially  
filled with water, leaving an air cushion for expansion.  
1. Inspect all water and gas piping and verify to be leak  
free.  
2. Look for signs of leaking lines and correct any  
problems found.  
Make sure this type of tank is fitted with a tank fitting, such as the B & G  
Tank-Trol or Taco Taco-Trol. This fitting reduces gravity circulation of air-  
saturated tank water back to the system and prevents the air from bubbling  
up through the water as it returns from the system.  
3. Check gas line using procedure on page 21.  
Do not use automatic air vents in systems with closed-type tanks. The air will  
escape from the system instead of returning to the tank. Eventually, the tank  
will waterlog and no longer control pressurization. The boiler relief valve will  
weep frequently.  
Check air openings  
1. Verify that combustion and ventilation air openings  
to the boiler room and/or building are open and  
unobstructed. Check operation and wiring of  
automatic combustion air dampers, if used.  
Diaphragm- or bladder-type — welded gas tight with a rubber  
membrane to separate the tank pressurizing air and the water. May be  
located at any point in the system,but most often found near the boiler.  
2. Verify that boiler vent discharge and air intake are  
clean and free of obstructions.  
Systems with this type of expansion tank require at least one automatic air  
vent, preferably located on top of an air eliminator, as shown in examples in  
manual section 3.  
2. If relief valve has tended to weep frequently, the expansion tank may be  
waterlogged or undersized.  
Flue vent system and air piping  
1. Visually inspect entire flue gas venting system (and  
air piping, if installed) for blockage, deterioration or  
leakage. Repair any joints that show signs of leakage  
in accordance with vent manufacturers instructions.  
When air is ducted to boiler,verify that air inlet hose  
is connected and properly sealed.  
Closed-type tank — tank is most likely waterlogged. Install a tank fitting  
if not already installed. Then check fill level per fitting manufacturers  
instructions. If fill level is correct, check tank size against manufacturers  
instructions. Replace with a larger tank if necessary.  
Diaphragm- or bladder-type — first,check tank size to be sure it is large  
enough for the system. If size is too small, add additional tank(s) as  
necessary to provide sufficient expansion. If tank size is large enough,  
remove tank from system and check charge pressure (usually 12 psig for  
residential applications). If tank wont hold pressure, membrane has  
been damaged. Replace tank.  
Failure to inspect for the above conditions  
and have them repaired can result in severe  
personal injury or death.  
30  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
8a  
An n u a l s t a rt u p  
(continued)  
Check boiler relief valve  
Inspect ignition electrode  
1. Inspect the relief valve and lift the lever to verify flow as in the following  
warnings, excerpted from a relief valve manufacturers warning label.  
Before operating any relief valve, ensure that it is piped with its discharge  
in a safe area to avoid severe scald potential. Read manual section 3,  
page 12,before proceeding further.  
1. Remove the ignition electrode from the boiler heat  
exchanger access cover.  
2. Removeanywhiteoxidesaccumulated on theignition  
electrode using sandpaper. If the ignition electrode  
cannot be cleaned satisfactorily, replace ignitor with  
a new one.  
Safety relief valves should be reinspected AT LEAST ONCE  
EVERY THREEYEARS,by a licensed plumbing contractor or  
authorized inspection agency, to ensure that the product has  
not been affected by corrosive water conditions and to ensure  
that the valve and discharge line have not been altered or  
tampered with illegally.Certain naturally occurring conditions  
may corrode the valve or its components over time, rendering  
the valve inoperative. Such conditions are not detectable unless  
the valve and its components are physically removed and  
inspected. This inspection must only be conducted by a  
plumbing contractor or authorized inspection agency — not  
bytheowner.Failuretoreinspect theboilerrelief valveasdirected  
could result in unsafe pressure buildup, which can result in  
severe personal injury, death or substantial property damage.  
3. Replace ignition electrode, making sure gasket is in  
good condition and correctly positioned.  
4. Make sure the electrodes are parallel to each other.  
Check ignition ground wiring  
1. Inspect boiler ground wirefrom heat exchanger access  
cover to ground terminal strip.  
2. Verify all wiring is in good condition and securely  
attached.  
3. Check ground continuity of wiring using continuity  
meter.  
4. Replace ground wires if ground continuity is not  
satisfactory.  
Following installation, the valve lever must be operated AT  
LEAST ONCE A YEAR to ensure that waterways are clear.  
Certain naturally occurring mineral deposits may adhere to  
the valve, rendering it inoperative. When manually operating  
the lever,water will discharge and precautions must be taken to  
avoid contact with hot water and to avoid water damage. Before  
operating lever,check tosee that a discharge line is connected to  
this valve directing the flow of hot water from the valve to a  
proper place of disposal. Otherwise severe personal injury may  
result. If no water flows, valve is inoperative. Shut down boiler  
until a new relief valve has been installed.  
Check all boiler wiring  
1. Inspect all boiler wiring, making sure wires are in  
good condition and securely attached.  
Check control settings  
1. Set the control module display to Parameter mode  
and check all settings.Adjust settings if necessary.See  
Ultra Control Supplement for details.  
2. After following the above warning directions, if the relief valve weeps or  
will not seat properly, replace the relief valve. Ensure that the reason for  
relief valve weeping is the valve and not over-pressurization of the system  
due to expansion tank waterlogging or undersizing.  
2. Check settings of external limit controls (if any) and  
adjust if necessary.  
31  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
8a  
An n u a l s t a rt u p  
(continued)  
Perform startup and checks  
Check flame signal  
1. Flame signal (DC volts from low voltage terminal strip terminal 9 to ground)  
should be at least 4 VDC.  
2. A lower flame signal may indicate a fouled ignitor or damaged ignitor insulation.  
If cleaning the ignitor does not improve, ground wiring is in good condition,  
and ground continuity is satisfactory, replace the ignitor.  
3. See Troubleshooting in the Ultra Control Supplement for other procedures to  
deal with low flame signal.  
1. Start boiler and perform checks and tests specified  
on pages 23 through 26 (and Control Supplement).  
2. Verify cold fill pressure is correct and that operating  
pressure does not go too high.  
3. Complete the check-out procedure on page 26.  
Check flue gas temperature  
Check burner flame  
1. Place the control display in Information mode while the boiler is operating at  
high fire. See Ultra Control Supplement for details.  
2. The flue gas temperature (electronic display first digit shows “5”) must not be  
more than 60°F higher than the return water temperature (display first digit  
shows“2”).  
The boiler contains ceramic fiber materials.  
Use care when handling these materials per  
instructions on page 29 of this manual.  
Failure to comply could result in severe  
personal injury.  
3. If the flue temperature is higher than this, shut down the boiler, allow to cool,  
and follow the procedure on pages 33 through 34 to clean the heat exchanger.  
1. Inspect flame through observation window using the  
procedure on page 25.  
2. If flame is unsatisfactory at either high fire or low fire,  
turn off boiler and allow boiler to cool down. Then remove  
burner and clean it thoroughly using a vacuum cleaner or  
compressed air.Do not use compressed air to clean burner  
if performed inside a building.  
3. To access burner, remove the heat exchanger cover plate  
following the procedure on page 33.  
4. When replacing burner,ensure gasket is in good condition  
and correctly positioned. After tightening the three retainer  
screws, bend up the retainer tabs as shown in Figure 16 to  
prevent screw rotation.  
Review with owner  
1. Review the Users Information Manual with the owner.  
2. Emphasize the need to perform the maintenance schedule specified in the  
Users Information Manual (and in this manual as well).  
3. Remind the owner of the need to call a licensed contractor should the  
boiler or system exhibit any unusual behavior.  
4. Remind the owner to follow the proper shutdown procedure and to  
schedule an annual startup at the beginning of the next heating season.  
5. After servicing, replace boiler components. Retest boiler.  
Figure 16 Burner assembly  
32  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
8b  
Ma in t e n a n c e — g e n e ra l  
Replace boiler jacket front door after startup or servicing  
Replace boiler jacket front door after start or servicing. The boiler front door must be securely fastened  
to the boiler to prevent boiler from drawing air from inside the boiler room. This is particularly  
important if the boiler is located in the same room as other appliances. Failure to keep the door securely  
fastened could result in severe personal injury or death.  
General maintenance  
2. Remove the air silencer by separating it from the air  
adapter on the blower inlet.  
3. Disconnect the gas valve plug, blower power supply  
plug and blower control connector.  
4. Release the exchanger cover plate by removing the  
nuts securing it to the exchanger.  
5. Pull the entire blower/venturi/gas valve/cover plate  
assembly out of the boiler. (See pages 39 or 41 for  
component identification and locations.)  
1. Oil motor in system requiring regular oiling.  
2. See Oil bearing circulators for motor oiling  
procedures.  
Oiled bearing circulators  
1. The circulator shipped with the Ultra boiler is water-  
lubricated. No oiling is required.  
6. Use a vacuum cleaner to remove any accumulation  
on the heating surfaces. Do not use any solvent.  
7. If the vacuum cleaner is unable to clean completely,  
wash the heating surfaces with clean, warm water.If  
necessary, use a piece of 20-gauge or lighter sheet  
metal ¾" wide by about 18 inches long to loosen  
deposits.  
8. Inspect the heat exchanger cover plate insulation.  
Replace if insulation is damaged. Read the ceramic  
fiber WARNING on page 29 before handling or  
disposing of ceramic fiber materials.  
9. Re-install the blower/venturi/gas valve/cover plate  
assembly and secure the cover plate with nuts.  
2. Check other circulators in the system. Oil any  
circulators requiring oil, following circulator  
manufacturers instructions.Over-oiling will damage  
the circulator.  
Cleaning boiler heat exchanger  
The boiler contains ceramic fiber materials.  
Use care when handling these materials per  
instructions on page 29 of this manual.  
Failure to comply could result in severe  
personal injury.  
10. Connect gas valve electrical plug and blower power  
and control connectors.  
1. Shut down boiler:  
a. Follow“To Turn Off Gas to Applianceinstructions on  
boiler and Lighting instructions.  
b. Do not drain boiler unless it will be exposed to freezing  
temperatures. If using freeze prevention fluid in system,  
do not drain.  
Inspect the O-ring that should still be in  
the gas valve inlet adapter block. The O-  
ring must be in good condition and must  
be installed when gas valve is reconnected.  
Failure to comply will cause a gas leak,  
resulting in severe personal injury or death.  
2. Allow time for boiler to cool to room temperature if it has  
been firing.  
3. Remove jacket front door by removing two knurled head  
screws at lower front. Lift door away from boiler to remove.  
4. Follow procedure below to access the heat exchanger  
interior.  
11. Secure gas valve inlet adapter to gas valve with (4)  
Phillips-head screws.  
12. Re-install the air silencer by pressing onto the air  
inlet adapter.  
Access exchanger:Ultra-80and Ultra-105Only  
13. Install access cover gasket, chamber insulation  
assembly and cover.Secure cover with nuts.  
14. See continued instructions on next page.  
1. Remove (4) Phillips-head screws securing gas valve  
inlet adapter to gas valve. This will disconnect the gas  
valve from the gas line.  
33  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
8b  
Ma in t e n a n c e a n d a n n u a l s t a rt u p  
(continued)  
Cleaning boiler heat exchanger  
(continued from previous page)  
11. Place cover plate gasket in groove of heat exchanger  
cover plate. Replace cover plate.  
12. Re-install hex head nuts (10mm box end wrench) on  
cover plate mounting studs and tighten in a staggering  
pattern until cover plate is uniformly tightened.  
13. Re-install blower insuring new gasket, provided in  
this kit, is in proper alignment between blower and  
heat exchanger front cover.  
14. Re-install air silencer by sliding on gas valve venturi  
and securing clamp to gas line.  
15. Connect the two blower electrical molex plugs.  
Accessexchanger: Ultra-155,-230,-310 Only  
1. Remove gas valve electrical plug from gas valve. Also  
remove two electrical molex plugs from blower  
assembly.  
2. Disconnect gas line union with pipe wrench or  
Channel Lock Pliers.  
3. Remove air silencer by lifting plastic clamp off gas  
line and then gently sliding air silencer down and off  
valve.  
4. Remove two 5/32” Allen head screws securing blower  
assembly to heat exchanger front cover.  
16. Re-connect gas valve union and gas valve electrical  
plug.  
Exchanger cleaning continued (ALL models)  
5. Remove blower and gas valve assembly.  
1. Close isolation valves on piping to isolate boiler from  
system. Attach a hose to boiler drain valve and flush  
boiler thoroughly with clean water by using purging  
valves to allow water to flow through water make-  
up line to boiler.  
2. When boiler has been flushed, restore boiler to  
operation.  
3. Perform startup and checkout procedures of pages 23  
and 26.  
4. Turn on gas supply and check for gas leaks.  
6. Remove hex head nuts (10mm box end wrench) from  
burner cover plate and remove burner cover plate  
from heat exchanger.  
7. Remove three M4 hex head screws (7mm box end  
wrench) and burner clips securing burner to cover  
plate. Remove cover plate.  
8. Use a vacuum cleaner to remove any accumulation  
on the heating surfaces. Do not use any solvent.  
9. If the vacuum cleaner is unable to clean completely,  
wash the heating surfaces with clean, warm water.If  
necessary, use a piece of 20-gauge or lighter sheet  
metal ¾" wide by about 18 inches long to loosen  
deposits.  
Failure to properly check for gas leaks can  
cause severe personal injury, death, or  
substantial property damage.  
10. Inspect the heat exchanger cover plate insulation and  
gasket. Replace if damaged. Read the ceramic fiber  
WARNING on page 29 before handling or disposing  
of ceramic fiber materials.  
5. Turn on boiler electrical supply and test boiler for  
proper operation as stated in the Ultra Boiler Manual.  
6. Replace boiler jacket front door when servicing is  
completed. SeeWarning at top of page 33.  
34  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
9
Re p la c e m e n t p a rt s  
Replacement parts must be purchased through a local  
Weil-McLain part numbersarefound inWeil-McLain  
Boilers and Controls Repair Parts Lists.  
Weil-McLain distributor. When ordering, specify  
boiler model and size and include description and  
part number of replacement part. Results from using  
modified or other manufactured parts will not be  
covered by warranty and may damage boiler or  
impair operation.  
The boiler contains ceramic fiber materials. Use care  
when handling these materials per instructions on  
page 29 of this manual. Failure to comply could result  
in severe personal injury.  
Replace boiler jacket front door after startup or servicing  
Replace boiler jacket front door after start or servicing. The boiler front door must be securely fastened to the boiler to  
prevent boiler from drawing air from inside the boiler room. This is particularly important if the boiler is located in the  
same room as other appliances. Failure to keep the door securely fastened could result in severe personal injury or death.  
Miscellaneous parts and kits  
35  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
9
Re p la c e m e n t p a rt s  
(continued)  
Jacket parts  
36  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
9
Re p la c e m e n t p a rt s  
(continued)  
Jacket parts  
37  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
9
Re p la c e m e n t p a rt s  
(continued)  
Heat exchanger and piping — Ultra-80 & -105  
38  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
9
Re p la c e m e n t p a rt s  
(continued)  
Heat exchanger and piping — Ultra-80 & -105  
39  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
9
Re p la c e m e n t p a rt s  
(continued)  
Heat exchanger and piping — Ultra-155 to -310  
40  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
9
Re p la c e m e n t p a rt s  
(continued)  
Heat exchanger and piping — Ultra-155 to -310  
41  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
9
Re p la c e m e n t p a rt s  
(continued)  
Controls  
42  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
10  
Dim e n s io n s  
Notes  
1. Boiler supply and return tappings are both 1" NPT (Ultra-  
80/105/155/230) or 1¼" NPT (Ultra-310). See pages 14  
through 18 for recommended system supply and return  
piping sizes.Wall-hung boilers:water piping and gas pipe  
can be routed through bottom of enclosure using wall-  
mounting kit.  
and 1¼" circulator flanges are shipped with boiler on Ultra-  
80/105/155/230. Both 1¼" and 1½" circulator flanges are  
shipped with boiler on Ultra-310.  
3. Relief valve is shipped loose. See page 11 for mounting  
details. Relief valve mounts on supply pipe off of supply  
tee and ¾" street elbow as shown.  
2. Boiler circulator is shipped loose. Circulator may be  
mounted on either boiler supply or return piping. Both 1"  
43  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS -FIRED WATER BOILER — Bo ile r Ma n u a l  
11  
Ra t in g s  
DOE  
5. Weil-McLain Low temperature seasonal efficiency is based  
on ASHRAE 103 test method, using boiler return water  
temperature of 90°F, with boiler outlet water temperature  
of 110°F.  
6. Combustion efficiency is based on I=B=R testing procedure  
BTS-2000, and equal to 100% minus flue loss.  
7. Thermal efficiency is based on I=B=R testing procedure  
BTS-2000.  
8. Weil-McLain Low temperature efficiency is based on the  
I=B=R testing procedures, using boiler return water  
temperature of 90°F and boiler outlet water temperature  
of 110°F.  
9. Ratings shown are for sea level applications only. For  
altitudes from sea level to 5,500 feet above sea level, the  
Ultra boiler requires no modifications and automatically  
derates itself by approximately 4% per 1000 feet above sea  
level. For elevations above 5,500 feet, contact your local  
Weil-McLain sales office for details.  
1. As an Energy Star Partner, Weil-McLain has determined  
that Ultra boilers meet the Energy Star guidelines for energy  
efficiency.  
2. Based on standard test procedures prescribed by the United  
States Department of Energy.  
3. Net I=B=R ratings are based on net installed radiation of  
sufficient quantity for the requirements of the building  
and nothing need be added for normal piping and pickup.  
Ratings are based on a piping and pickup allowance of  
1.15. An additional allowance should be made for unusual  
piping and pickup loads.  
4. Ultra boilers require special venting, consistent with  
Category IV boiler. Use only the vent materials and  
methods specified in Ultra vent supplements. Ultra boilers  
must be direct-vented. Ultra-230 can be vented with either  
3" or 4" vent pipe.Vent length limits for 3" vent are not as  
long as for 4" vent.  
Notes  
44  
Part number 550-101-233/0903  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Weider Home Gym 831150341 User Manual
Wenger Watch 543103 User Manual
Weslo Treadmill WLTL26080 User Manual
Westinghouse Flat Panel Television LTV 27w6 HD User Manual
Westinghouse Outdoor Ceiling Fan ETL ES Origami WH10 User Manual
Whirlpool Cooktop GJC3054RB00 User Manual
Whirlpool Refrigerator 4VET19DK User Manual
Yamaha Offroad Vehicle 5GW F8199 13 User Manual
Zanussi Cooktop 200228 User Manual
Zanussi Fryer 285764 User Manual