Weil McLain Burner 800057000 Brn PO Rie F5 User Manual

Installation & Operating Manual  
Single stage operation oil burners  
RETROFIT APPLICATIONS ONLY  
If this burner is being installed in a packaged unit (ie. burner comes with a boiler or furnace), follow  
the installation and set-up instructions supplied with the heating unit, as settings may differ from  
those shown in this manual.  
- The following pages contain information, descriptions and diagrams for the proper installation  
and wiring of the burner. Please read carefully before attempting final installation.  
- This manual is to remain with the final installation designation. It is the installer’s responsibility to en-  
sure that the burner installation and operation instructions mentioned in this manual are followed and  
operated within local code authority limits.  
RIELLO 40  
CODE  
MODEL  
TYPE  
C8512519  
C8512520  
C8512521  
800057000-Brn-PO Rie F5  
800058000-Brn-PO Rie F5  
800059000-Brn-PO Rie F5  
1.00GPH Vnt-C  
1.20GPH Vnt-C  
1.40GPH Vnt-C  
C6501071(0)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
TABLE OF CONTENTS  
PACKAGE CONTENTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
SERIAL NUMBER IDENTIFICATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
Mounting flange dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
INITIAL SET-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
OIL BURNER COMPONENT IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
Burner components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
ASSEMBLY OF AIR TUBE TO BURNER CHASSIS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
MOUNTING BURNER TO BOILER OR FURNACE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 5  
Method 1-Universal Mounting Flange. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Method 2-Semi-flange Collar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Method 3-Pedestal Mount. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
AMULET INSTALLATION INSTRUCTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
INTERNAL FACTORY WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
APPLICATION FIELD WIRING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
NOZZLE PLACEMENT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
INSERTION / REMOVAL OF DRAWER ASSEMBLY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
ELECTRODE SETTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
TURBULATOR SETTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
OIL LINE CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 12  
Single line (Gravity feed system) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Two line (Lift system) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
PUMP PURGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
Single line (Gravity feed system) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
Two line (Lift system) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
SETTING THE AIR ADJUSTMENT PLATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
BURNER ADJUSTMENT TABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
BURNER START-UP CYCLE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
EXPLODED SPARE PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
SPARE PARTS LIST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 - 16  
3223  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
PACKAGE CONTENTS LIST  
Your Riello 40 burner should include the following parts. Please check to make sure all parts are present before begin-  
ning the installation.  
Quantity Description  
Code  
1
1
1
1
1
Burner with combustion head mounted  
C8512519 - C8512520 - C8512521  
Mounting gasket  
Parts bag  
C6880016  
2569525  
2569526  
C6501071  
Parts bag  
Installation manual  
Separate carton - OEM burners shipped with combustion head mounted  
Parts bag 2569525  
Parts bag 2569526  
Quantity Description  
Quantity Description  
2
2
2
4
2
Semi-flange bolts (long)  
Semi-flanges  
Mounting flange bolts (short)  
Nuts  
Chrome nuts  
1
1
1
1
1
1
By-pass plug  
Female ¼” NPT adapter  
Male 3/8” NPT adapter  
2.5 mm Allen key  
Oil pump connector (supply)  
Oil pump connector (return)  
SERIAL NUMBER IDENTIFICATION  
Your Riello burner may have been manufactured in more than one location and therefore there are two possible serial  
number identification.  
(06)  
(01)  
(12345)  
The Riello 9 character serial number, example,  
06 01 12345, is identified as follows:  
06  
01  
= Last two digits of the year of manufacture;  
= Week of manufacture;  
Year of  
manufacture  
BI-week of  
manufacture  
Increment  
12345 = Increment of 1 for each burner produced – specific  
to product code – reset to zero each January 1st.  
(06)  
(A)  
(8511111)  
(00025)  
The Riello 15 character serial number, example,  
06 A 8511111 00025, is identified as follows:  
06  
= Last two digits of the year of manu-  
facture;  
= BI-week of manufacture;  
Year of  
manufacture  
BI-week of  
manufacture  
BI-week of  
manufacture  
Increment  
A
8511111 = Burner product code;  
00025 = Increment of 1 for each burner pro-  
duced – specific to product code –  
reset to zero each January 1st.  
3223  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
TECHNICAL DATA  
SPECIFICATIONS  
Fuel  
B
No heavier than # 2 fuel oil  
F3 Firing rate - Effective Output 0.50 to 0.95 US GPH - 70,000 to 133,000 BTU/h  
F5 Firing rate - Effective Output 0.75 to 1.65 US GPH - 105,000 to 231,000 BTU/h  
Voltage (single phase)  
120V 60Hz (+ 10% - 15%)  
F3 Absorbed electrical power 155 Watts  
F5 Absorbed electrical power 175 Watts  
Motor (rated)  
3250 rpm Run Current 2.2 AMP  
Capacitor  
12.5 Microfarads  
130 to 200 psig  
RIELLO 530 SE/C  
8kV 16mA  
Pump pressure  
Primary control  
Ignition transformer  
E
E1  
F
BURNER DIMENSIONS  
Model  
A
B
C
D
E
F
Inches 8 15/32 9 59/64 6 15/32  
mm 215 252 164  
Inches 9 11/64 10 11/16 7 3/32  
mm 233 272 180  
3 1/2  
89  
3 1/2  
89  
6
152  
6
8 29/32  
226  
9 13/32  
239  
F3  
F5  
152  
D7352  
E1: 10-inch long (254mm) tubes are also available.  
BURNER COMPONENTS IDENTIFICATION  
1
7
2
3
4
1
5 / ”-140mm  
2
6
5
1
7 / ” - 190 mm  
2
15  
8
/
” - 215 mm  
32  
D7351  
9
BURNER COMPONENTS  
8
1
2
3
4
5
6
7
8
9
Lockout indicator lamp and reset button  
Primary control  
Primary control sub-base  
Pump pressure regulator  
Motor  
Air adjustment and shutter  
Electronic air shutter assembly  
Combustion head  
10  
11  
12  
Semi flange 2 pieces  
10 Mounting flange with gasket  
11 Supply fuel line port  
12 Pump valve (coil)  
13 Vacuum gauge port  
14 Pressure gauge and bleeder port  
15 Return fuel line port  
13  
14  
15  
D7304  
3223  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
INITIAL SET-UP  
A) Remove burner and air tube from cartons. Check parts list (inside cover) to ensure all parts are present.  
B) Remove burner cover by loosing the three screws securing it. Remove control box and air tube cover.  
C) Remove drawer assembly from air tube, insert nozzle and set Turbulator adjustment for specific input required, then  
set aside.  
D) Mount air tube to burner chassis.  
ASSEMBLY OF AIR TUBE TO  
BURNER CHASSIS  
The air tube and drawer assembly are  
shipped in a carton separate from the burner  
chassis. Choose the proper air tube length to  
obtain the tube insertion for the specific in-  
stallation.  
A) Remove the AIR TUBE and BURNER  
CHASSIS from their respective cartons.  
B) Remove the DRAWER ASSEMBLY (1)  
S7462  
from inside the AIR TUBE by loosening  
the screw (2). Carefully pull the DRAWER ASSEMBLY out of the AIR TUBE, install the required nozzle (see page 8)  
and set aside.  
C) Remove the two BOLTS (3) from FRONT PLATE (4) of the BURNER CHASSIS. Align the two holes on the AIR  
TUBE HOLDING PATE (5) with the two holes on the BURNER CHASSIS FRONT PLATE with the BOLTS (3) re-  
moved. Replace the BOLTS and fingers tighten only. Re-install DRAWER ASSEMBLY into AIR TUBE. Tighten  
SCREW (2) securely.  
D) Tighten the two bolts (3) securely.  
MOUNTING THE BURNER TO THE BOILER OR FURNACE  
There are three possible methods to mount the burner, depending on the individual application. These are:  
1) Universal flange bolted to Boiler/Furnace unit.  
2) Semi-flange collar bolted to Boiler/Furnace unit.  
3) Universal flange mounted to optional Pedestal mount, where flange mounting direct to appliance is not possible.  
Pedestal kit must be ordered separately.  
METHOD 1 – UNIVERSAL MOUNTING FLANGE  
A
DRY BASE  
BOILER  
B
D6013  
A
COMBUSTION  
CHAMBER  
B
S7461  
D6014  
3223  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
A) Insert the two BOLTS (1) into the UNIVERSAL MOUNTING FLANGE (10) from the flat side, ensuring the bolt heads  
are flush with the flat surface. Secure in place using two special CHROME NUTS (2) provided.  
B) Position the MOUNTING GASKET (3) between the flat surface of the UNIVERSAL MOUNTING FLANGE (10) and  
the appliance. Line up the holes in the UNIVERSAL MOUNTING FLANGE with the STUDS (4) on the appliance  
mounting plate and securely bolt the UNIVERSAL MOUNTING FLANGE to the plate.  
C) Secure the two semi-flanges of the ADJUSTABLE COLLAR (9) to the AIR TUBE using the two long BOLTS (6). Be  
sure that the ADJUSTABLE COLLAR (9) is properly positioned so the outside edge of the END CONE will be at least  
¼ inch (6.5mm) back from the inside wall of the refractory of the combustion chamber (see dimension B above). The  
measured length (A) is to include MOUNTING GASKET and FLANGE, if used.  
D) The burner may now be attached to the heating unit by insetting the AIR TUBE through the BURNER ACCESS  
HOLE (8) and into the appliance, making sure the BOLTS (1) line up with the two HOLES (5) in the ADJUSTABLE  
COLLAR (9). Secure the burner in place using two NUTS (7).  
A visual verification of the air tube insertion into the combustion chamber of the heating unit is suggested. Dimension B  
should be at least ¼” (see drawing).  
NOTE:  
A suggested method for creating mounting bolt holes in the mounting gasket: Hold the gasket against the appliance  
mounting bolts using the mounting flange for proper positioning. Lightly tap the flange with a hammer to form the holes.  
METHOD 2 – SEMI-FLANGE COLLAR  
A) Follow item C from METHOD 1.  
B) Align the air tube and attached adjustable collar so air tube is centered in the burner access hole of the boiler/fur-  
nace unit. Mark the center of the two holes in the ADJUSTABLE COLLAR on to the front plate of the heating unit.  
Then drill ¼ inch (6.5mm) holes through the front plate of the unit, using marks as a guide.  
C) Install two short BOLTS (1) through the front plate of the heating unit from the inside, and secure on the outside us-  
ing the two special CHROME NUTS (2).  
D) Follow item D from METHOD 1.  
METHOD 3 – PEDESTAL MOUNT  
Secure the MOUNTING FLANGE to MOUNTING PEDESTAL using the hardware provided with the pedestal. Secure  
burner to MOUNTING FLANGE as in METHOD 1, item A, C and D.  
NOTE:  
It is suggested that the pedestal be anchored in position on the floor by installing brackets over the pedestal tube and  
securing brackets to the floor.  
WARNING:  
WHEN THE COMBUSTION CHAMBER IS LINED WITH A REFRACTORY MATERIAL, IT IS IMPERATIVE THAT  
THE END CONE NOT PROTRUDE INTO THE CHAMBER AREA, AS EXCESSIVE HEAT AT BURNER SHUT  
DOWN WILL DAMAGE THE END CONE.  
3223  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
AMULET INSTALLATION INSTRUCTIONS  
(Required on some models)  
Amulet shown in the  
flush mounted position  
The amulets provided have been selected by Riello to protect the  
combustion tube from hot exhaust gases and flame. This protec-  
tion may be needed in applications where the combustion tube  
opening in the combustion chamber refractory is larger than the  
tube outside diameter.  
The amulet has been sized to fit Riello Model 40 sizes F3 and F5  
plus the Riello Model R35.  
When installing this amulet, handle it carefully.  
Do not exert undue pressure when pushing the amulet over the  
combustion tube.  
Head receeded  
1/4 inch max.  
D7285  
Excessive force can result in a broken amulet!  
If the amulet will not fit easily onto the tube, remove a small amount  
of the inner diameter with a sharp knife to provide the necessary clearance.  
The diagram below shows the proper position of the amulet after installation.  
NO AMULET  
AMULET  
FLUE GASES  
FLUE GASES  
Tapered combustion  
chamber causes increase  
in pressure inside  
Tapered combustion  
chamber causes increase  
in pressure inside  
LOW PRESSURE  
LOW PRESSURE  
HEAT  
HIGH PRESSURE  
HEAT  
AIR TUBE  
AIR TUBE  
HIGH PRESSURE  
HEAT  
HEAT  
Increase in pressure  
down air tube due  
to increase in  
combustion chamber  
pressure  
Increase in pressure down  
air tube due to increase  
in combustion chamber  
pressure  
Amulet helps prevent  
not gases from  
travelling down  
air tube  
Increase in pressure down  
air tube due to increase  
in combustion chamber  
pressure  
S7941  
3223  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
INTERNAL FACTORY WIRING  
RIELLO 40 F3 - F5 SERIES OIL BURNERS EQUIPPED  
WITH AN ELECTRONIC AIR SHUTTER  
INTERNAL FACTORY WIRING  
PUMP VALVE  
(COIL)  
MOTOR  
D7328  
CAPACITOR  
Key to lay-out:  
A - Brown  
B - White  
C - Blue  
6
- 120V source activates shutter open  
- motor lead 120V source  
11  
- 120V control lock out alarm terminal  
D - Black  
AUX - costant 120V auxiliary terminal - electronic air shutter  
ATTENTION !!  
³
Do not swap neutral and phase over, follow the diagram shown carefully and carry out a good earth  
connection.  
³
³
Minimum wire size AWG 18.  
All wiring must be done in accordance with existing codes, both national and local.  
3223  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
APPLICATION FIELD WIRING  
WIRING DIAGRAM SHOWN BELOW FOR STANDARD RIELLO 530 SE/C PRIMARY CONTROL BOX.  
INSTALLATION NOTE: ELECTRONIC AIR SHUTTER REQUIRES A CONSTANT 120V POWER SUPPLY TO  
THE AUX TERMINAL, FAILURE TO PROVIDE THIS WILL RESULT IN NO BURNER OPERATION OR AIR SHUT-  
TER WILL NOT CLOSE.  
AIR SHUTTER  
MOTOR  
AIR SHUTTER  
MOTOR  
PLEASE NOTE: OPERATING LIMIT AND SAFETY LIMIT ARE TWO SEPARATE LIMITS.  
Key to lay-out:  
1
2
3
4
5
6
- Main disconnect fuse  
- Manual service switch  
- Safety limit device  
- Operating limit device  
- Earth ground connection burner chassis  
- Burner control remote lock out alarm device - wired & supplied by others  
AUX - Auxiliary bub base add-on connector (air shutter)  
T - T - 24V thermostat connections - low voltage operated system  
MIN. WIRE SIZE:  
INSULATED 18 AWG SOLID OR 16 STRD.  
PROPER EARTH GROUNDING MEANS REQUIRED  
RATED 105° C  
ALL WIRING SHOWN PROVIDED BY OTHER.  
WARNING: DO NOT activate burner until proper oil line connections have been made, or failure of the pump  
shaft seal may occur.  
WARNING: DO NOT activate burner until all safety and operating controls have been wired in series with the  
burner, as required by local code authorities and/or as specified by the appliance manufacturer.  
3223  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
NOZZLE PLACEMENT  
A) Determine the proper firing rate for the boiler or furnace units,  
considering the specific application, and then use the Burner  
Setup charts on page 12 to select the proper nozzle and pump  
pressure to obtain the required input from the burner.  
B) Remove the NOZZLE ADAPTER (2) from the DRAWER AS-  
SEMBLY by loosening the SCREW (1).  
C) Insert the proper NOZZLE into the NOZZLE ADAPTER and  
tighten securely (Do not over tighten).  
D) Replace adapter, with nozzle installed, into drawer assembly  
and secure with screw (1).  
S7459  
INSTALLATION/REMOVAL  
OF DRAWER ASSEMBLY  
Removal:  
A) Loosen off oil delivery tube nut  
from pump.  
B) Loosen SCREW (3), and then un-  
plug CONTROL BOX (1) by care-  
fully pulling it back and then up.  
C) Remove the AIR TUBE COVER  
PLATE (5) by loosening the re-  
taining SCREW (4) (Two  
SCREWS – Model F5).  
D) Loosen SCREW (2), and then  
slide the complete drawer assem-  
bly out of the combustion head as  
shown.  
E) To insert drawer assembly, re-  
verse the procedure in items A to  
D above.  
S7460  
5/32” or 4 mm  
ELECTRODE SETTING  
IMPORTANT:  
These dimensions must be observed and verified.  
D6003  
5/32” to 13/64” or 4 to 5 mm  
TURBULATOR SETTING  
3
2
1
A) Loosen NUT (1), and then turn SCREW (2) until the INDEX MARKER  
(3) is aligned with the correct index number as per the Burner Setup  
charts, or OEM specifications given with the appliance.  
B) Retighten the RETAINING NUT (1).  
NOTE: OEM specifications take priority over retrofit specifications  
shown in this manual.  
MODEL F3: Zero and three are scale indicators only. From left to  
right the first line is 3 and the last line 0.  
D5997  
MODEL F5: Same as above, except scale indicators are 0 and 4.  
3223  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
OIL LINE CONNECTIONS  
This burner is shipped with the oil pump set to operate on a single line system.  
To operate on a two-line system the by-pass plug must be installed.  
WARNING: Do not operate a single line system with the by-pass plug installed. Operating a single line system with  
the by-pass plug installed will result in damage to the pump shaft seal.  
NOTE: Pump pressure must be set at time of burner start-up. A pressure gauge is attached to the PRESSURE PORT  
(8) for pressure readings. Two PIPE CONNECTORS (6) are supplied with the burner for connection to either a single or  
two-line system. Also supplied are two ADAPTORS (3), two female ¼” NPT, to adapt oil lines to burner pipe connectors.  
All pump port threads are British Parallel Thread design. Direct connection of NPT threads to the pump will damage  
the pump body.  
Riello manometers and vacuum gauges do not require any adapters, and can be safely connected to the pump ports.  
An NPT (metric) adapter must be used when connecting other gauge models.  
1
8
2
3
5
6
7
4
4
SINGLE LINE (GRAVITY FEED SYSTEM)  
A) The burner is shipped configured for use in single line applications. No changes to the oil pump are required for use  
in single line applications.  
NOTE: If the pump cover (1) is removed for any reason, be sure the O-ring (2), is properly seated in the pump cover  
(1) before re-attaching the pump cover to the pump housing.  
B) Connect the pipe connector to the SUPPLY PORT(5) of the pump. Attach the NPT adapter to the pipe connector.  
Attach the required piping to this pipe adapter. Be sure that the plug in the RETURN PORT (7) is tightened securely.  
SINGLE LINE SYSTEM-PIPE LENGTHS  
H
3/8” OD  
1/2” OD  
FT  
1.5  
3.0  
5.0  
6.5  
M
FT  
M
FT  
M
20  
0.5  
1.0  
1.5  
2.0  
33  
65  
10  
20  
40  
60  
65  
ATTENTION:  
do not exceed  
pipe lengths  
130  
260  
325  
40  
130  
195  
80  
indicated in chart!  
100  
D6009  
3223  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
TWO LINE (LIFT SYSTEM)  
A) If a two-line system is required, install the By-pass plug provided. The by-pass plug is installed in the return port  
of the pump. A 2.5-mm hexagonal key provided with the by-pass plug is to be used to install the plug.  
DO NOT use an inch size hexagonal key; damage to the by-pass plug may result.  
When operating on a two-line system, supply and return lines should be the same diameter and both should  
extend to the same depth inside the fuel tank. Be sure there are no air leaks or blockages in the piping sys-  
tem. Any obstructions in the return line will cause failure of the pump shaft seal.  
2 LINE (LIFT) SYSTEM-PIPE LENGTHS  
H
3/8” OD  
1/2” OD  
FT  
0.0  
1.5  
3.0  
5.0  
6.5  
9.5  
11  
M
FT  
M
35  
30  
25  
20  
15  
8
FT  
M
100  
100  
100  
90  
70  
30  
20  
0.0  
0.5  
1.0  
1.5  
2.0  
3.0  
3.5  
115  
100  
80  
65  
50  
330  
330  
330  
295  
230  
100  
65  
ATTENTION:  
do not exceed  
pipe lengths  
indicated in chart!  
25  
20  
D6008  
6
To install the by-pass plug:  
1) Remove the return plug (7).  
2) Install the by-pass plug (4) using the 2.5 mm hexagonal key.  
B) Attach the two PIPE CONNECTORS (6) to the pump SUPPLY and pump RETURN PORTS (5 and 7). Attach the  
required piping to these two pipe connectors using the NPT/ METRIC ADAPTERS that are supplied with the burner.  
WARNING:  
- Pipe dope or Teflon tapes are NOT to be used on any direct oil connection to the fuel pump.  
- The height ‘P’ in Pipe Length Charts should not exceed 13 feet (4 m).  
- The vacuum should not exceed 11.44 inches of mercury.  
IMPORTANT:  
An external, appropriately listed and certified oil filter must be placed in the fuel line between the fuel tank  
and the burner pump.  
PUMP PURGE  
NOTE: To protect the pump gears, it is advisable to lubricate the pump prior  
to purging a lift system. Apply oil through the VACUUM PORT (C).  
B
C
A) SINGLE LINE (GRAVITY FEED SYSTEM)  
I. Loosen the bleeder valve (A) until oil flows out. Tighten the bleeder valve  
securely and startburner.  
II. When bleeding the pump by pressure:  
1) Loosen the bleeder valve (A).  
2) Disconnect nozzle oil supply line at the pump nozzleport (B).  
3) Attach a flexible plastic tube to the pump nozzle, port directing the oil  
flow into a bucket.  
4) Loosen the screw(s) securing the air tube cover, allowing it to be re-  
moved freely.  
5) Holding the air tube cover in its proper location start the burner.  
6) When the solenoid valve is engaged approximately 10 seconds after  
starting, remove the air tube cover and shine a light source on the  
photocell, allowing it to see false light.  
A
D7284  
3223  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
7) Run the burner until the fuel pump has been purged of air, then tighten the bleeder valve and immediately  
shut down the burner.  
8) Reinstall the air tube cover and nozzle line.  
9) The burner can now be started normally.  
WARNING: Omitting steps 2 and 3 will result in a collection of unburned oil in the combustion chamber creating a haz-  
ardous situation upon burner startup.  
B) TWO LINE (LIFT SYSTEM)  
Turn off the main power source to the burner and remove the air tube cover.  
Shines a light source on the photocell (now visible where the air tube cover was removed), return power to the burner  
and activate the burner. With the light source in place, the burner will operate in prepurge only. When the pump is suffi-  
ciently purged, the hydraulic air shutter will open.  
Once the burner is purged, turn off the power source and replace the air tube cover.  
Return power to the burner. The burner is now ready to operate.  
ATTENTION:  
It is important that the fuel line be completely sealed and free from air leaks or any internal blockages.  
WARNING! WHEN THE BYPASS PLUG IS INSTALLED, A TWO-PIPE SYSTEM MUST BE USED OR FAILURE OF  
THE PUMP SHAFT WILL OCCUR.  
SETTING THE AIR ADJUSTMENT PLATE  
1
The electronic air shutter assembly (1) is operated on a  
120V 60Hz. motor, and the burner motor will not operate un-  
til the air shutter is in its fully open position.  
Set the air plate (4) setting according to OEM setup informa-  
2
3
5
4
tion or by following the Retrofit settings listed in this manual.  
To adjust the air plate (4) to the desired set point indicator  
(2), loosen the center air shutter assembly screw (5) and  
loosen the side air plate screw (3), move air plate (4) by us-  
ing the air plate adjust arm. After adjustments are made  
please retighten screws (3) & (5).  
The final position of the air adjustment plate will vary on  
each installation. Using proper combustion test instruments  
to establish the proper setting of the air gate setting to  
achieve safe and efficient results according the appliance  
information or if not available.  
D7305  
NOTE: Variations in flue gas, smoke, CO2 and temperature readings may be experienced when burner cover is put  
in place. Therefore, the burner cover must be in place when making final combustion instrument readings, to ensure  
proper test results are obtained.  
3223  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
BURNER ADJUSTMENT TABLE  
NON-RETROFIT APPLICATIONS  
If this burner is being installed in a packaged unit (i.e. Burner comes with a boiler or furnace), follow the instal-  
lation and set-up instructions supplied with the heating appliance, as settings will differ from those shown in  
this manual.  
RIELLO BURNER SET UP SHEET  
Weil McLain Part No.  
Riello Part No.  
8000-5700  
C8512519  
8000-5800  
8000-5900  
C8512520  
F5 Factory  
preset *1  
UO4  
C8512521  
F5 Factory  
preset *1  
UO5  
Riello 40  
F5 Factory  
preset *1  
UO3  
F5  
Burner Model  
Series  
Boiler  
UO3  
0,8  
Input  
GPH  
1,0  
1,2  
1,4  
Nozzle  
Delavan  
.65 X 70°B  
.85 X 60°B  
1.00 X 70°B  
1.10 X 70°B  
Pump Pressure  
PSI  
150  
145  
145  
160  
Turbolator Setting  
Air Gate Setting  
0
2.75  
8
1
2.8  
8
3
2.9  
8
4
2.9  
8
Air tube length  
inches  
Ait tube insertion  
inches  
4 1/4"  
4 1/4"  
4 1/4"  
4 1/4"  
*1 Nozzle pre-installed at factory.  
NOTE:  
The above set up charts are a starting point only.  
The burner and appliance must be properly set up using proper combustion testing equipment.  
Note: Any approved oil burner nozzle type, angle and manufacturer maybe used, as long as input is corresponding the  
correct BTU/hr. or US gph input rating of the appliance.  
COMBUSTION CHAMBER  
Follow the instructions furnished by the boiler/furnace manufacturer. Size retrofit application according to the appropri-  
ate installation codes (e.g. CSA B139 or NFPA #31).  
BURNER START-UP CYCLE  
Normal  
Lock-out, due to light-failure  
Thermostat  
Motor  
Ignition transformer  
Valve  
Flame  
Lock-out lamp  
D5229  
~ 12s  
~ 12s  
~ 5s  
3223  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED SPARE PARTS LIST  
35  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPARE PARTS LIST  
No.  
CODE  
F5 DESCRIPTION  
No.  
CODE  
F5 DESCRIPTION  
OPTIONAL  
60  
61  
C7001085  
C7001033  
TYPE L 24V SWITCHING RELAY  
AMULET - CERAFELT SLEEVE KIT  
1
2
3
4
5
6
7
8
9
C8111227  
BURNER BACK COVER  
PIPE CONNECTOR - SUPPLY  
3/8” NPT/METRIC ADAPTER - MALE  
PIPE CONNECTOR - RETURN  
1/4” NPT/ METRIC ADAPTER - FEMALE  
CRUSHABLE METAL WASHER  
BLEEDER  
O-RING - PUMP PRESSURE REGULATOR  
REGULATOR SCREW  
O-RING - PUMP COVER  
PUMP SCREEN  
3006992  
3006571  
3006993  
3005847  
3007077  
3007568  
3007028  
3007202  
3007943  
CAPILLARY PORT PLUG  
10 3007162  
11 3005719  
12 3006925  
13 3007203  
14 3007029  
15 3007156  
16 3007268  
17 3007087  
18 3001157  
19 3002278  
20 3006553  
21 3002279  
22 3007802  
23 3000443  
24 3005843  
C7010002  
VALVE STEM  
VALVE STEM PLATE  
O-RING - VALVE STEM UPPER  
O-RING - VALVE STEM LOWER  
NOZZLE OUTLET FITTING  
CRUSHABLE METAL WASHER 5/8” ID  
PRIMARY CONTROL 530SE/C  
PRIMARY CONTROL SUB BASE  
COIL U-BRACKET AND KNURLED NUT  
COIL  
C7001029  
PUMP  
PUMP DRIVE KEY  
MOTOR  
25 3007316  
26 3002280  
27 3005854  
29 3020248  
30 3005708  
31 3005844  
AIR TUBE COVER  
PHOTOCELL  
SEMI FLANGE (2 REQUIRED)  
MOUNTING GASKET  
FAN  
CAPACITOR 12.5 µF  
32 3007320  
33 3007204  
34 3020249  
ACOUSTIC LINER  
MANUAL AIR SHUTTER  
ELECTRONIC AIR SHUTTER  
35  
C7001082  
F5 REPLACEMENT AIR DAMPER KIT  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPARE PARTS LIST  
No.  
CODE  
F5 DESCRIPTION  
40  
C7001331  
F5 SBT WELDED 4.25" COMPLETE  
41 3006968  
TURBULATOR DISC  
42 3006966  
43 3006965  
ELECTRODE SUPPORT  
NOZZLE ADAPTER  
44 3008629  
45 3008634  
NOZZLE OIL TUBE  
REGULATOR ASSEMBLY  
46 3008631  
47 3005869  
ELECTRODE ASSEMBLY  
ELECTRODE PORCELAIN  
48  
C7001335  
F5 SBT WELDED 4.25" TUBE ONLY  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GB  
35 Pond Park Rd.  
Hingham, MA 02043  
Phone: 781-749-8292  
Toll Free: 800-992-7637  
Fax: 781-740-2069  
2165 Meadowpine Blvd.  
Mississauga,On L5H 3R2  
Phone: 905-542-0303  
Toll Free: 800-387-3898  
Fax: 905-542-1525  
BURNER START- UP FORM *  
Burner S/N. or Model:  
Installer name:  
Company:  
Appliance:  
Installation date:  
Fax:  
Address:  
Phone:  
Owner Name:  
Address:  
Phone:  
E-mail:  
Burner Start-up Info (OIL)  
Nozzle info:  
Air setting:  
Pump pressure:  
Turbolator setting:  
Draft breech:  
Draft overfire:  
CO2:  
CO:  
O2:  
Two lines:  
Smoke density:  
(Bacharach)  
Single line:  
Thisform wasdesigned and provided in the installation manual for reference and also forproviding tech-  
*
nical information which can be faxed or mailed to our technical hot-line coordinator when technical assis-  
tance is required. Please complete this form, fax it or mail it at the address/fax above, or send an e-mail  
with the information listed below to: [email protected]  
3223  
Download from Www.Somanuals.com. All Manuals Search And Download.  
35 Pond Park Road  
Hingham, MA 02043  
Phone 781-749-8292  
Toll Free 800-992-7637  
Fax 781-740-2069  
2165 Meadowpine Blvd  
Mississauga, ON L5N 6H6  
Phone 905-542-0303  
Toll Free 800-387-3898  
Fax 905-542-1525  
Technical Support Hotline  
1-800-4-RIELLO  
1-800-474-3556  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Wegener Communications Stereo Receiver DVR395 User Manual
Welbilt Septic System 999362 User Manual
Western Digital Computer Drive Computer Hard Drive User Manual
Westinghouse Mixer SA61950 User Manual
Wolf Appliance Company Ventilation Hood PI543418 R User Manual
Xantrex Technology Marine Battery RS3000 User Manual
Yamaha Speaker System KMS 1000 User Manual
Zanussi Washer FLE 1016 W User Manual
Zebra Technologies Printer P310C User Manual
Zenoah Edger HEZ2601F User Manual