Unified Brands Electric Steamer HY 6GCE User Manual

OPERATOR MANUAL &  
SERVICE MANUAL  
IMPORTANT INFORMATION, KEEP FOR OPERATOR  
This manual provides information for:  
HY-6G(CE) HYPERSTEAM™  
ATMOSPHERIC CONVECTION  
STEAMER  
· Self-Contained  
INTERNATIONAL  
· Gas Heated  
· Capacity: 6 Steamer Pans (305 x 508 x 64mm)  
THIS MANUAL MUST BE RETAINED FOR FUTURE REFERENCE.  
READ, UNDERSTAND AND FOLLOW THE INSTRUCTIONS AND  
WARNINGS CONTAINED IN THIS MANUAL.  
NOTIFY CARRIER OF DAMAGE AT ONCE  
It is the responsibility of the consignee to inspect the container upon receipt of  
same and to determine the possibility of any damage, including concealed dam-  
age. Unified Brands suggests that if you are suspicious of damage to make a  
notation on the delivery receipt. It will be the responsibility of the consignee to file  
a claim with the carrier. We recommend that you do so at once.  
Manufacture Service/Questions 888-994-7636.  
Information contained in this document is known to be current and accurate at the time  
of printing/creation. Unified Brands recommends referencing our product line websites,  
unifiedbrands.net, for the most updated product information and specifications.  
1055 Mendell Davis Drive  
Jackson, MS 39272  
888-994-7636, fax 888-864-7636  
groen.com  
PART NUMBER 128805, REV. C (4/06)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
1.0  
2.0  
3.0  
4.0  
5.0  
6.0  
7.0  
8.0  
9.0  
EQUIPMENT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
INSPECTION AND UNPACKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
WATER CONDITIONING/REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
INSTALLATION, START-UP AND CONVERSION INSTRUCTIONS . . . . . . . . . . . . . . . 6  
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
10.0 SERVICE PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
11.0 SCHEMATIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
12.0 SERVICE LOG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
WARRANTY PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
References  
UNDERWRITERS LABORATORIES, INC.  
333 Pfingsten Road  
NATIONAL FIRE PROTECTION ASSOCIATION  
60 Battery March Park  
Northbrook, Illinois 60062  
Quincy, Massachusetts 02269  
NFPA/70 The National Electrical Code  
KLENZADE SALES CENTER  
ECOLAB, Inc.  
370 Wabasha  
NATIONAL SANITATION FOUNDATION  
3475 Plymouth Road  
St. Paul, Minnesota 55102  
800 328-3663 or 612 293-2233  
Ann Arbor, Michigan 48106  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.0 - Equipment Description  
Your Groen HY-6G (CE) HyPerSteam Convection  
Steamer is designed to give years of service. It has  
two stainless steel cavities (cooking chambers) which  
are served by twin, independent atmospheric steam  
generators which are gas-heated. A powerful blower  
circulates the steam in each cavity to increase heating  
efficiency.  
Each cavity holds up to three steam table pans (305 x  
508 x 64 mm). A 1.5 mm stainless steel case  
encloses the cavities, the steam generators and the  
control compartment that houses electrical  
components. Door hinges are reversible (the doors  
may be set to open from the left or right). Operating  
Controls are on the front panel.  
HY-6G (CE) steamers are equipped with fully  
electronic controls and a button-activated,  
preprogrammed CLEAN cycle.  
The HY-6G (CE) has two independent  
cavities, each with its own base-mounted  
steam generator.  
The drain system includes a spray condenser, which  
helps keep steam from escaping down the  
condensate drain.  
2.0 - Inspection and Unpacking  
Your HY-6G HyPerSteam will be delivered completely  
assembled in a heavy shipping carton and attached to  
a skid. On receipt, inspect the carton carefully for  
exterior damage.  
CAUTION  
SHIPPING STRAPS ARE UNDER TENSION AND  
CAN SNAP BACK WHEN CUT.  
Carefully cut the straps around the carton and detach  
the sides of the carton from the skid. Be careful to  
avoid personal injury. Strap edges may be very  
sharp, particularly where cut. Write down the model  
number, serial number and installation date. Space  
for these entries is provided in the Service Log at the  
back of this manual. Keep the manual near the  
equipment for reference and update as needed.  
CAUTION  
THIS UNIT WEIGHS 550 LBS. (250 KG). GET  
HELP AS NEEDED AND USE MATERIAL  
HANDLING EQUIPMENT TO MOVE IT.  
When installing, use material handling equipment to  
lift the unit straight up from the skid. Check packing  
materials for any loose parts.  
The unit will be delivered in a heavy carton,  
strapped to a wooden skid.  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.0 - Water Conditioning  
It is essential to supply the steam generator with  
3.2 If your water contains scale-forming minerals, as  
most water does, use a well-maintained water  
softener. Whether an exchangeable softener  
cartridge or a regenerating system is chosen, a  
regular exchange system is essential.  
water that will not form scale. Even though the steam  
generator is engineered to minimize scale formation,  
scale development depends on the hardness of your  
water and the number of hours the equipment  
operates.  
3.3 Installing a water meter between the softener and  
the steamer will provide an accurate gauge of  
water use, and will help determine when to  
exchange cartridges or regenerate the softener.  
Using a water softener will provide longer  
generator life, higher steam capacity, and reduce  
maintenance requirements.  
In some areas of the country, water is low enough in  
minerals to avoid scale formation. But most water  
supplies are full of minerals which form scale. It is  
this scale which could lead to an early component  
failure.  
Your water utility can tell you about the minerals in  
your water. The water going to the steam generator  
should have between 10 and 30 parts per million  
(ppm) total dissolved solids (TDS) and should have a  
pH (acidity rating) of 7.0 or higher. Please follow these  
simple precautions:  
3.4 If you notice a slowdown in steam production,  
check the unit for scale build-up. Heavy scale  
reduces the unit’s ability to boil water, and can  
even cause heating elements in the steam  
generator to overheat and burn out.  
3.1 Do not rely on unproven water treatments  
which are sold as scale prevention or scale  
removers. They don’t always work. The best  
way to prevent scale is to supply the purest  
possible water (10 - 30 ppm TDS).  
MINIMIZE SCALE PROBLEMS BY USING AND  
MAINTAINING A SOFTENER, AND BY CLEANING  
THE STEAMER REGULARLY.  
The BPST Connection on the right rear side of the steamer.  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.0 - Installation, Start-Up and Conversion  
WARNING  
THE UNIT MUST BE INSTALLED BY PERSONNEL WHO ARE QUALIFIED TO WORK WITH ELECTRICITY AND  
PLUMBING. IMPROPER INSTALLATION CAN CAUSE INJURY TO PERSONNEL AND/OR DAMAGE TO THE  
EQUIPMENT. THE UNIT MUST BE INSTALLED IN ACCORDANCE WITH APPLICABLE CODES.  
CAUTION  
DO NOT INSTALL THE UNIT WITH THE RIGHT SIDE VENTS BLOCKED OR WITHIN 30 CENTIMETERS OF  
A HEAT SOURCE (SUCH AS A BRAISING PAN, DEEP FRYER, CHAR BROILER, OR KETTLE).  
TO AVOID DRAINAGE PROBLEMS, LEVEL THE UNIT FRONT TO BACK, OR PITCH IT SLIGHTLY TO THE  
REAR.  
4.1 General  
4.1.1 Model Number and Dimensions  
disconnected from the gas supply system during  
any pressure testing of that system at test pressures  
in excess of ½ PSI (3.45 kPa). It must be isolated  
from the gas supply piping system by closing its  
individual manual shutoff valve during any pressure  
testing of the gas supply piping system at test  
pressures equal to or less than ½ PSI (3.45 kPa).  
WIDTH DEPTH HEIGHT WEIGHT  
mm (in.) mm (in,) mm (in.) Kg (lbs)  
MODEL  
549  
(21.6)  
894  
(35.2)  
1464  
(57.6)  
193  
(425)  
HY-6G(CE)  
4.2 Electrical Supply Connection  
4.1.2 Siting and Clearances  
The unit is designed for connection to fixed wiring. A  
suitably rated isolating switch with contact separation  
of at least 3 mm on both poles must be fitted to the  
installation. Wiring must be executed in accordance  
with the regulations listed on page 2 of this manual.  
The HY-6G(CE) steamer is suitable for installation in  
combustible and noncombustible locations.  
Minimum clearances for installation are:  
Right Side  
Left Side  
Rear of Flue  
300 mm (12 inches)  
0 mm (0 inches)  
150 mm (6 inches)  
Cable entry is at the bottom rear right side of the  
appliance. To gain access the panel must be  
removed. Open the lower front panel by removing its  
screws. Lift the panel and swing its bottom toward  
you. Set the panel aside.  
However, for easy service at least 300 mm (12  
inches) clearance is required for the right side of  
the unit, and it may not be installed within 300 mm  
(12 inches) of a heat source, as stated in the  
Caution above.  
Provide 230 Volt, 50 Hz, Single Phase, 15 Ampere  
service. Maximum load is 2½ amps. The electrical  
schematic is located in the service compartment. A  
copy is also printed at the rear of this manual.  
The unit must be installed in a well-ventilated room  
with an adequate air supply. The steamer must be  
installed beneath a ventilation hood, since gas  
combustion products exit the appliance.  
CAUTION  
THE UNIT MUST HAVE A SEPARATE EARTHING  
WIRE FOR SAFE OPERATION.  
Any item which might obstruct or restrict the flow of  
air for combustion and ventilation must be removed.  
Do not obstruct the flue cover or any front, side, rear,  
or top vents after installation.  
4.3 Gas Supply Connection  
Incoming service must be of sufficient size to supply  
full rate without excessive pressure drop. A gas  
meter is connected to the service pipe by the Gas  
Supplier. Any existing meter should be checked out  
by the Gas Supplier to ensure that it has adequate  
capacity to provide the required rate of gas to the  
steamer, in addition to any other equipment.  
The area directly around the appliance must be  
cleared of all combustible material. The installation  
must conform with local codes or, in the absence of  
local codes, with the National Fuel Gas Code, ANSI  
Z223.1, latest edition, including the following:  
The unit and its individual shutoff valve must be  
6
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.2 Injector Diameters  
GAS INPUT RATE BTU/HR AND KW  
Natural Gas  
Propane Gas  
Injector No. of  
Dia. (mm) Injectors Dia. (mm) Injectors  
Natural Gas  
9.25 mBar  
(3.7 in. W.C)  
Propane Gas  
26.25 mBar  
(10.5 in. W.C.)  
HY-6G(CE)  
Injector  
No. of  
Main  
Burner  
Individual  
Steamer Cavity  
40950 BTU/hr  
12 KW  
40950 BTU/hr  
12 KW  
1.49  
0.99  
0.60  
4 x 2  
1 x 2  
1
0.94  
0.57  
0.25  
4 x 2  
1 x 2  
1
Standby  
Burner  
Total  
Both Cavities  
81900 BTU/hr  
24 KW  
81900 BTU/hr  
24 KW  
Pilot  
Burner  
Installation pipe work must be fitted in accordance with  
IGE/UP/2.  
4.3.3 Burner Air Adjustment  
The appliance governor is suitable for both natural and  
propane gas without conversion. The governor is  
incorporated in the gas control valve, which is inside the  
control cabinet.  
The unit is equipped with fixed aeration type burners  
which have no provision for air inlet adjustment.  
Connection to the gas supply can be completed with ½”  
B.S.P.T. pipe. Although the immediate connection to the  
appliance is ½” B.S.P.T., gas supply piping must be large  
enough to provide 90,000 BTU/hour. Minimum supply  
pressure must be 20 mBar for natural gas, or 37 mBar  
for propane gas.  
An isolating cock must be located close to the appliance  
to allow shut down in an emergency, or for servicing.  
The installation must be tested for gas soundness and  
purged as specified in IGE/UP/1.  
4.3.1 Gas Pressure Adjustment  
Gas pressure has been set at the factory but should be  
checked by connecting a manometer to the pressure tap  
on the burner manifold. The adjusted gas pressures is  
shown in the table below.  
Gas input is through a ½ inch B.S.P.T connection  
at the left rear of the unit.  
G20 Natural Gas  
G31 Propane Gas  
4.3.4 Equipotential Terminal  
mBar  
Inch W.C.  
3.7  
mBar  
Inch W.C.  
10.5  
In accordance with national regulations, each unit is  
fitted with an equipotential terminal.  
9.25  
26.25  
If necessary, the gas pressure may be readjusted as  
described in the Service Manual.  
4.4 Water Supply Connection  
The HY-6G CE model is fitted for a 3/4 inch B.S.P.T.  
cold water connection. The water supply must be  
provided at a rate of not less than 2.7 liters (0.70  
gallons) per minute. Pressure must be 2.0 to 4.0 Bar  
(30 to 60 PSI) maximum.  
NOTE: With reference to gas rate, pressure adjustments  
and conversions, this appliance is CE-approved for use  
with C20 natural gas and G31 propane gas in Ireland  
and the United Kingdom.  
Use of the appliance with non-approved gases in a listed  
country, or use in other countries, will void CE  
certification.  
Water quality minimums require totally dissolved  
solids (T.D.S.) of 30 parts per million maximum, and  
a water pH of 7.0 or greater. If the available water  
supply fails to meet these requirements, water  
treatment equipment must be provided to ensure  
steamer reliability and operating life.  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Install a WRAS approved double-check valve or an  
equally effective backflow preventive device in the  
incoming cold water line at the point of connnection(s)  
to the steamer and in compliance with all local plumbing  
codes. This installation must be per WRAS-IRN R160  
Schedule 2-15(1). For units with the dual water  
connection option, a double-check valve shall be  
installed on each water line.  
4.6 Initial Start-Up  
After the HY-6G(CE) Steamer has been installed,  
test it to ensure that the unit is operating correctly.  
4.6.1 Remove all literature and packing materials  
from the interior and exterior of the unit.  
4.6.2 Make sure the water supply line is open.  
Do not allow the connection to have any leak, regardless  
of how small.  
4.5 Drain Connection  
4.6.3 Make sure that the gas supply line is open  
and that the manual knob on the main gas  
valve is turned to the “on” position. This  
valve is located behind the front access  
panel on the right side of the unit.  
The HY-6G (CE)Steamer must be leveled front to back.  
A 38mm (1½ inch) ID hose may be attached to the drain  
pipe (supplied) by means of a hose. DO NOT  
4.6.4 Turn on electrical service to the unit. The  
HY-6G(CE) will not operate without electrical  
power. Do not attempt to operate the unit  
during a power failure.  
CONNECT THE HOSE DIRECTLY TO A BUILDING  
DRAIN. There must be a free air gap between the end  
of the hose and the building drain. The free air gap  
should be as close as possible to the unit drain. There  
must also be no other elbows or other restrictions  
between the unit drain and the free air gap.  
4.6.5 The steamer will not operate until the pilot  
burner has been ignited. To light the pilot  
burner, activate the pilot switch located at  
the lower front, next to the main gas valve.  
When the pilot ignition sequence has been  
successful, a green light on the pilot switch  
will glow.  
CAUTION  
DO NOT USE PLASTIC PIPE. THE DRAIN MUST  
WITHSTAND HOT WATER.  
Install the drain line with a constant downward pitch.  
IMPORTANT: Do not allow any water traps in the  
line. A trap can cause pressure to build up inside the  
cavity during steaming, which will make the door  
gasket leak.  
4.6.6 The “trial for ignition” period is roughly 90  
seconds. If the pilot burner does not light  
within about 90 seconds after the switch is  
activated, the ignition system automatically  
stops gas flow to the pilot burner and stops  
the ignition trial. If this happens, turn off the  
pilot switch and repeat the trial for ignition.  
During the initial start-up, the pilot may  
require several trials for ignition until all the  
air is bled from the gas piping. Subsequent  
start-ups should require only about 5  
seconds to achieve pilot ignition. Reinstall  
panel(s). NOTE: See Automatic Operation of  
Pilot at the end of this section.  
4.6.7. Once the pilot burner flame has been  
established (the green light on the electrical  
panel is on), press the ON/OFF touch pad  
for the desired steamer cavity. The steam  
generator will fill with water.  
NOTE: The door MUST be closed for the  
main (high) burner to work.  
4.6.8 When the steam generator has filled with  
water, the main and low burners will ignite  
automatically. Within 6-8 minutes the  
READY light will come on, indicating that the  
water has reached its standby temperature.  
When the READY light is displayed, you may  
take any one of the following steps:  
Leave an air gap between the hose and the building  
drain, and don’t allow water traps in the hose.  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a. Set the timer to the desired time for timed  
steaming.  
Then the unit will come back on and resume  
operation in the mode and with the (running) timer  
value existing just prior to shutdown. The pilot  
switch may be turned off during “off hours” to  
conserve energy.  
b. Turn the timer knob to the manual ON  
position for continuous steam.  
c. Let the unit stay at standby temperature.  
After the unit has been running, if the pilot burner  
ever fails to re-ignite automatically within 90  
seconds, wait 5 minutes before you attempt to  
reactivate it. In the unlikely event that ignition  
problems persist, contact your authorized Groen  
Service Agency.  
NOTE: For operation at high altitudes (2000 feet and  
above) please consult the Groen Food Service  
Engineering Department.  
WARNING  
WHEN YOU OPEN THE DOOR, STAY AWAY FROM  
STEAM COMING OUT OF THE UNIT. THE STEAM  
CAN CAUSE BURNS.  
4.7 Gas Type Conversion (See Paragraph 4.3.1 for  
important information for gas conversion. Verify  
the type of gas to be used).  
4.6.9 To shut down the unit, press the ON/OFF touch  
pad into the off position. The steam generator  
will then drain. You may also switch off the pilot  
switch to conserve energy.  
To change the type of gas used (e.g. G20 to/from  
G31) change the following:  
4.6.10 If the HY-6G(CE) Steamer behaves as  
described, the unit is functioning correctly and  
ready for use.  
Burner injector  
Pressure setting on Main Gas Valve  
Data plate  
Gas pressure Regulator Springs  
4.6.11 Automatic Operation of Pilot  
The governor spring does not need to be changed;  
only the pressure setting. ALL CONVERSIONS  
MUST BE FOR APPROVED GAS IN THE  
COUNTRIES LISTED IN PARAGRAPH 4.3.1  
Once the pilot burner is lit, it essentially functions as a  
standing pilot. In this state, if the pilot is accidentally  
extinguished (by a very strong gust of wind for example),  
it will re-ignite automatically. The unit will completely shut  
down for a few seconds while the pilot is re-ignited.  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.0 - Operation  
WARNING  
ANY POTENTIAL USER OF THE EQUIPMENT SHOULD BE TRAINED IN SAFE AND CORRECT OPERATING  
PROCEDURES.  
5.1 Controls  
Gas Lockout Indicator and Reset Control  
Operator controls are on the front right of the unit.  
The control panel has the following touch pads and  
indicator lights. (Your controls may have either words or  
the symbols shown below):  
Should the pilot fail to ignite during start-up, a yellow  
indicator on the control panel (see page 11) will light  
and the supply of gas to the unit will be halted.  
When this occurs, the ignition process may not be  
started again for five minutes. After that time, press the  
Lockout Reset Switch located behind the front panel  
and attempt to start the unit again. If the lockout  
continues to occur after three attempts, contact your  
Groen Service Agency for assistance.  
The ON/OFF touch pad gets the  
HyPerSteam ready for use, or shuts it off.  
The READY indicator light shows that the  
steam generator is at standby  
temperature and the cavity is hot enough  
to begin steaming.  
5.2 Operating Procedure  
5.2.1 Press the ON/OFF touch pad for the steamer.  
The steam generator will fill, and heat until the  
READY light comes on. (About 10 minutes.)  
The CLEANING indicator lights when the  
unit is operating in the cleaning mode.  
5.2.2 Load food into pans in uniform layers. Pans  
should be filled to about the same levels, and  
be even on top. The maximum allowable weight  
of food is 9.8 kilograms (21.6 lbs.) per pan.  
The SERVICE indicator light shows when  
the water level probes have stopped  
working, and need to be cleaned  
(normally an indication of lime deposits).  
5.2.3 Open the door and slide the pans onto the  
supports. If you will only be steaming one pan,  
put it in the middle position.  
When one probe is not working, the  
SERVICE light flashes briefly every few  
seconds. When both probes fail, the light  
will flash continuously and the beeper will  
sound.  
5.2.4 Close the door. With the READY indicator lit,  
take one of the following steps:  
The HI TEMP indicator light comes on  
when the steam generator is too hot.  
If you want to steam the food for a certain  
length of time, set the timer for that period. The  
timer will automatically run the steamer for the  
set time and then turn it off. A red light will  
come on and a beeper will sound. Steam  
production stops.  
The unit will automatically shut off, and  
cannot be turned on again until it has  
been serviced.  
The TIMING indicator light stays on when  
the timer is running.  
To steam continuously, turn the timer to the  
manual ON position. A green light will come  
on. The unit will continue steaming until you  
stop it by turning the timer to OFF. When  
steaming continuously YOU MUST CONTROL  
STEAMING TIME.  
The CLEAN touch pad is used to start the  
automatic 50 minute cleaning cycle.  
The timer is used in three ways:  
WARNING  
1
In the OFF position the steam generator stays at a  
low boil or “holding” temperature.  
WHEN YOU OPEN THE DOOR, STAY AWAY FROM  
THE STEAM COMING OUT OF THE UNIT. THE  
STEAM CAN CAUSE BURNS.  
2
When a cook time is set, the unit steams until the  
timer reaches OFF. The steaming stops, a red light  
comes on and a beeper sounds.  
5.2.5 Open the door. Remove the pans from the  
steamer, using hot pads or oven mitts to protect  
your hands from the hot pans.  
3
With the timer turned to the ON position, the unit  
steams continuously. The green light stays lit. The  
steamer will not time down.  
5.2.6 To shut down the unit, press the ON/OFF touch  
pad OFF. The steam generator will drain.  
10  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Upper Portion of HY-6G(CE) Control Panel  
OM/SM-HY-6G(CE)  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.0 - Cleaning  
To keep your HY-6E Steamer in proper working condition/order, use the following procedure to clean the unit.  
This regular cleaning will reduce the effort required to clean the steam generators and cavities.  
6.1 Suggested Tools  
WARNING  
1. Mild detergent  
2. Stainless steel exterior cleaner such as Zepper®  
3. Steam generator de-liming agent, such as  
DISCONNECT THE POWER SUPPLY  
BEFORE CLEANING THE OUTSIDE OF  
THE STEAMER.  
Groen Delimer Descaler, Lime-Away® or an  
equivalent. A liquid de-liming agent will be  
easier to use than crystals or powders. See the  
warning about chlorides, below  
4. De-greaser, such as EncompasS®, Malone 34®,  
Puritan Puribrute®, or Con-Lie®  
5. Cloth or sponge  
6. Plastic wool or a brush with soft bristles  
7. Spray bottle  
8. Measuring cup  
KEEP WATER AND CLEANING  
SOLUTIONS OUT OF CONTROLS AND  
ELECTRICAL COMPONENTS. NEVER  
HOSE OR STEAM CLEAN ANY PART OF  
THE UNIT.  
DON’T MIX DE-LIMING AGENTS (ACID)  
WITH DE-GREASERS (ALKALI)  
ANYWHERE IN THE UNIT  
9. Nylon pad  
10. Towels  
11. Plastic disposable gloves  
12. Funnel  
AVOID CONTACT WITH ANY  
CLEANERS, DE-LIMING AGENT OR DE-  
GREASER AS RECOMMENDED BY THE  
SUPPLIER. MANY ARE HARMFUL.  
READ THE WARNINGS AND FOLLOW  
THE DIRECTIONS!  
6.2 Procedure  
6.2.1 Outside of Steamer  
EVENWHEN THEUNIT HAS BEENSHUT  
OFF, DON’T PUT HANDS OR TOOLS  
INTO THE COOKING CHAMBER UNTIL  
THE FAN HAS STOPPED TURNING.  
1. Prepare a warm solution of the mild  
detergent as instructed by the supplier. Wet  
a cloth with this solution and wring it out. Use  
the moist cloth to clean the outside of the unit.  
Do not allow freely running liquid to touch the  
controls, the control panel, any electrical part, or  
any open louver.  
DON’T OPERATE THE UNIT UNLESS  
THE TWO REMOVABLE INTERIOR  
PARTITIONS HAVE BEEN PUT BACK IN  
THEIR PROPER LOCATIONS.  
DON’T USE ANY CLEANING OR DE-  
LIMING AGENT THAT CONTAINS ANY  
SULFAMIC AGENT OR ANY CHLORIDE,  
INCLUDING HYDROCHLORIC ACID  
(HCl). TO CHECK FOR CHLORIDE  
CONTENT SEEANY MATERIAL SAFETY  
DATA SHEETS PROVIDED BY THE  
CLEANING AGENT MANUFACTURER.  
2. To remove material which may be stuck to  
the unit, use plastic wool, a fiber brush, or a  
plastic or rubber scraper with a detergent  
solution.  
3. Stainless steel surfaces may be polished  
with a recognized stainless steel cleaner such as  
Zepper®.  
IMPORTANT  
DO NOT USE ANY METAL MATERIAL (SUCH AS METAL SPONGES) OR METAL IMPLEMENT (SUCH AS A  
SPOON, SCRAPER OR WIRE BRUSH) THAT MIGHT SCRATCH THE SURFACE. SCRATCHES MAKE THE  
SURFACE HARD TO CLEAN AND PROVIDE PLACES FOR BACTERIA TO GROW. DO NOT USE STEEL  
WOOL, WHICH MAYLEAVEPARTICLESIMBEDDEDINTHESURFACEWHICHCOULDEVENTUALLYCAUSE  
CORROSION AND PITTING.  
1ꢀ  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Replace fan baffle partition and close door.  
6.2.2 Steam Generator and Cooking Chamber  
8. The cleaning cycle consists of a boiling clean  
stage, a soak stage, and a rinse stage. The full  
cycle takes about 50 minutes to complete.  
The steamer cavity and steam generator may be  
cleaned separately. When cleaning is scheduled, or  
if the SERVICE light is on, follow these simple de-  
liming instructions. REMEMBER: DON’T ALLOW  
DE-LIMING AGENTS TO MIX WITH DE-  
GREASERS.  
9. WEAR PROTECTIVE GLOVES AND EYE  
PROTECTION FOR THIS  
STEP. When the steamer  
beeper sounds, turn off the  
1. Set the timer to OFF position.  
steamer and open the door.  
After the fan has stopped,  
remove the fan baffle partition  
and rinse it well in a sink.  
2. Turn off the steamer for five  
minutes.  
Wipe out the cavity  
completely. If necessary, use a damp nylon pad.  
3. Open the door and allow the  
cavity to cool.  
10. Reinstall the fan baffle.  
4. After the cavity has cooled five minutes, make  
sure that the fan has stopped and remove the  
fan baffle partition by lifting it up and toward the  
center of the cavity.  
11. If the steamer will no longer be used, leave it off.  
Otherwise, wait 10 minutes and turn it back on.  
When the READY light comes on, the steamer is  
ready for operation.  
5. Wipe out the cavity. Make sure the drain holes  
at the back of the cavity are clear of debris.  
6.2.3 If the SERVICE light stays on:  
6. Hold down the CLEAN button while turning the  
steamer on. Continue holding it  
1. Check that the water supply is on and that the  
supply hose is not kinked. With the problem  
corrected, turn the steamer off or 10 seconds  
and then re-start.  
until the CLEANING indicator light  
comes on. Then release the  
button. After five minutes, the  
beeper will begin to beep rapidly.  
This is the signal to add 500 ml per  
cavity of Groen De-limer De-  
2. Repeat steam generator cleaning.  
Scaler (P/N 114800), Lime-A-Way® or  
equivalent as shown at right. Do not use any de-  
limer that contains chlorine.  
The process for de-liming your HY-6G (CE) Steamer is simple,  
tool-less and quick.  
OM/SM-HY-6G(CE)  
1ꢁ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.0 - Maintenance  
The HY-6G(CE) Steamer is designed for minimum  
2. Inspect the cooking chamber drain to be sure  
it is not blocked.  
maintenance, and no user adjustments should be  
necessary. Certain parts may need replacement after  
prolonged use. If there is a need for service, only  
Groen personnel or authorized Groen representatives  
should perform the work.  
3. Adjust the latch pin to allow for changes that  
might occur as the gasket ages:  
a. Loosen the lock nut at the base of the  
latch pin. Turn the latch pin ¼ turn  
Always supply water with a low mineral count that  
meets the standards outlined in the Water  
Conditioning section of this manual.  
clockwise, and re-tighten the lock nut.  
b. After adjustment, run the unit to test for  
further steam leakage  
The unit does not contain fuses that could be  
replaced by the operator.  
c. If there is still leakage, repeat the  
adjustment.  
If steam or condensate is seen leaking from around  
the door, take the following steps:  
d. Continue adjusting the pin clockwise until  
the door fits tightly enough to prevent  
leakage.  
1. Check the door gasket. Replace if it is cracked or  
split.  
8.0 - Troubleshooting  
This Groen Steamer is designed to operate smoothly and efficiently if properly maintained. However, the following is  
a list of checks to make in the event of a problem. Wiring diagrams are furnished inside the service panel. If an item  
on the check list is marked with (X), it means that the work should be done by a factory-authorized service  
representative.  
SYMPTOM  
WHO  
WHAT TO CHECK  
Pilot will not light  
User  
a. Are electrical connections made with a ground?  
b. Is gas supply connection made?  
c. Is pilot ignition switch on?  
d. Is gas valve turned on?  
e. Are building fuses or circuit breakers all right?  
f. Are there drafts which could blow out the pilot?  
Auth Service  
Rep Only  
g. Is spark ignition cable connected to module? (X)  
Steam generator does not fill with  
water.  
User  
a. Is the ON/OFF touch pad depressed?  
b. Is the water supply connected?  
c. Is the water turned on?  
d. Check for low water pressure (less than 210 kPa or  
30 PSI).  
e. Is the screen at the water connection clogged?  
f. Has the steam generator been delimed?  
No steam.  
User  
User  
a. Is the ON/OFF touch pad depressed?  
b. Is the water supply connected?  
c. Is the water turned on?  
d. Are steamer doors open?  
e. Is the steam generator limed up?  
Red light comes on after four  
minutes.  
a. Is the water supply connected?  
b. Is the water turned on?  
c. Has the unit been delimed? (Refer to Cleaning  
Section)  
Excessive steam escaping from rear User  
of unit  
a. Is the water spray hose kinked or obstructed?  
Auth Service  
Rep Only  
b. Is the water spray solenoid connected?(X)  
c. Is the drain properly vented? (X)  
1ꢂ  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9.0 - Parts List  
9.1 External Cabinet and Sheet Metal  
Key  
1
Description  
Lower Side Panels  
Part No.  
096848  
096720  
042505  
094150  
070123  
094147  
094148  
096788  
078914  
003823  
123100  
123128  
096855  
Key  
Description  
Part No.  
123183  
096785  
099943  
123184  
123182  
096765  
096854  
128964  
100983  
122021  
122144  
122122  
116392  
13 Upper Right Side Panel  
14 Lower Back Panel  
15 Sink Drain Fitting  
16 Upper Left Panel  
17 Top Panel  
2
Lower Front Panel  
Adjustable Table Leg  
Door  
3
4
5
Door Handle  
6
Door Gasket  
18 Flue Cover  
7
Left Pan Rack  
Blower Cover/Rack  
Door Locking Pin  
19 Flue  
8
20 Back Panel  
9
21 Timer  
9a Door Pin Lock Nut  
10 Timer Knob  
22 Equipotential Terminal Assembly  
23 Water Supply Adapter Assembly  
24 Gas Lockout Indicator Light  
25 BSPT to NPT Adapter  
11 Mylar Overlay Plate  
12 Vent Pipe  
OM/SM-HY-6G(CE)  
1ꢃ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9.0 - Parts List  
9.2 Cavity Control Section  
Key  
1
Description  
Top Cover Clip  
Timer  
Part No.  
123156  
100983  
096857  
088865  
088874  
099250  
099953  
088880  
127525  
Key  
10  
11  
12  
13  
14  
15  
16  
Description  
Part No.  
096740  
096813  
128800  
119801  
119815  
119817  
088847  
088846  
Fan Motor  
2
Motor Capacitor, 3 MFD  
Cover, Control Panel  
Steamer Control PC Board  
Transformer  
3 x Door Switch  
4
5
6
7
8
9
Ready Thermostat  
Steam Port  
Steam Port Gasket  
Steam Hose, Top  
Steam Hose, Bottom  
1-3/8” Hose Clamp  
Timer Board  
Top Cavity Drain Hose  
17x Bottom Cavity Drain Hose  
x - Part Not Shown  
16  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9.0 - Parts List  
9.3 Steamer Base Section - Front  
Key  
1
Description  
Terminal Block  
Part No.  
003887  
128766  
119813  
070178  
119814  
074842  
106234  
122180  
Key  
Description  
Part No.  
087951  
122003  
119860  
119829  
122158  
100513  
094128  
123655  
9
Gas Pilot Switch, Rocker  
2
Cover, Housing  
10 Reset Switch, Pushbutton  
11 Circuit Breaker, 10 Amp  
12 Lug, Ground  
3
Relay, 12V DC  
4
Water Level Probes  
Relay, 24V DC  
5
13 Main Gas Valve  
6
Reset Relay 24VAC  
Transformer 75 VA, 240V  
Controller, Pilot Ignition  
14 Regulator  
7
15 Steam Generator Assembly LH  
16 Steam Generator Assembly RH  
8
OM/SM-HY-6G(CE)  
1ꢄ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9.0 - Parts List  
9.4 Steamer Base - Rear  
Key  
1
Description  
Gas Valve, 24V  
Part No.  
122120  
123707  
096712  
123711  
123475  
123706  
Key  
7
Description  
1/4" Tubing, Pilot  
Part No.  
122140  
123705  
123704  
100513  
042505  
096892  
2
1/2" Tubing  
3/8" Tubing  
Heat Shield  
1/2" Tubing  
3/8" Tubing  
8
Manifold Fitting Assembly  
Manifold Fitting Assembly  
Regulator  
3
9
4
10  
11  
12  
5
Adjustable Foot  
6
Over Temperature Sensor  
1ꢅ  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9.0 - Parts List  
9.5 Steamer Plumbing  
Key  
1x  
2
Description  
Plate, Cover, Water Inlet  
Hose, PVC, Clear  
Part No.  
098693  
099915  
096771  
127393  
096772  
127522  
122144  
071234  
099911  
099912  
Key  
11  
12  
13  
14  
15  
16  
Description  
Gen Drain Hose Clamps  
Drain Box  
Part No.  
095656  
096791  
099213  
096792  
088847  
088846  
073259  
096855  
090827  
3
Hose, Condensate  
Drain Box Flap  
4x  
5
Drain Kit  
Drain Box Cover  
Water Inlet Hose  
Top Cavity Drain Hose  
Bottom Cavity Drain Hose  
6
Water Inlet Hose Clamp  
Water Inlet Adapter Assy (BSPT)  
Steam Gen Drain Valve  
Outer Gen Drain Hose  
Inner Gen Drain Hose  
7
17x Cavity Drain Hose Clamp 21/4"  
8
18  
19  
Vent Pipe  
9
Water Inlet Valve 3 Way  
10  
x - Not Shown  
OM/SM-HY-6G(CE)  
1ꢆ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9.0 - Parts List  
9.6 Steamer Motor and Controls  
Key  
1
Description  
Part No.  
096740  
101145  
096868  
094135  
096790  
100983  
Key  
7
Description  
Part No.  
123100  
096857  
118102  
088865  
099250  
Fan Motor  
Timer Knob  
Door Switch  
2x  
3
Timer Fastener Nut  
Motor Shaft Seal  
Motor Insulator  
Fan  
8
9
Steam Port Kit*  
-Ready Thermostat  
-Steam Port Gasket  
4
10  
11  
5
6
Timer 50 Hz  
*Includes Thermostat and Steam Port Gasket  
ꢀ0  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9.0 - Parts List  
9.7 Steamer Generator Individual Parts  
Key Description  
New  
Key  
8
Description  
Bottom Cavity Drain Hose  
Top Steam Hose  
New  
1
1
Steam Gen Weldment, Inner  
094128  
123655  
096896  
096770  
106392  
081670  
070178  
088847  
088846  
099953  
099915  
096772  
099912  
099911  
096771  
088880  
Steam Gen Weldment, Outer  
Right Steam Gen. Insulation  
Left Steam Gen. Insulation  
Safety Valve  
9
2x  
3x  
4
10 Sink Drain Hose  
11x Water Inlet Hose  
12 Inner Steam Generator Drain Hose  
13 Outer Steam Generator Drain Hose  
14 Condensate Hose  
5
Drain Box Spray Nozzle  
Water Level Probe  
6
7
Top Cavity Drain Hose  
15 Bottom Steam Hose  
x - Part Not Shown  
OM/SM-HY-6G(CE)  
ꢀ1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9.0 - Parts List  
9.7 Steamer Individual Parts  
Key  
1
Description  
Main Gas Valve  
Part No.  
122158  
100513  
123705  
123704  
122180  
122120  
Key  
6
Description  
Pilot Gas Switch  
Part No.  
087951  
090827  
071234  
123641  
003328  
2
Regulator - Natural Gas  
Gas Manifold(Left)  
Gas Manifold (Right)  
Igniter Module  
7
Water Inlet Valve - 3 outlet  
Steam Generator Drain Valve  
Pilot Burner - Natural Gas  
3a  
3b  
4
8
9
10x Flame Sensor  
5
Solenoid Gas Valve  
x - Not Shown  
ꢀꢀ  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10.0 - Service Procedures  
The following procedures are based upon having access to the steamer on all four sides. If the steamer is installed  
between other appliances and there is not enough room on the sides for access, the steamer must then be pulled out  
from its position to gain proper access.  
Care should be taken in moving the steamer so as not to stress or pull on the electrical and water connections.  
1. If the top/left side cover must be removed due to a  
faulty door switch, remove the right side panel (as  
above) first. Then remove the top left panel in the  
same manner.  
10.1  
Top Right Side Panel (Louvered) - Removal  
P/N 123183  
1. With a flat blade screw driver remove the two 10-32  
screws on the lower edge and one screw on the top  
edge of the panel. The panel is held to the steamer  
by two spring-like clips at the rear and bottom edge.  
10.4  
Adjustable Legs  
P/N 042505  
2. Once the screws are removed SLIDE the panel  
towards the front with a lifting motion. Do not attempt  
to PRY the panel. Once the panel is free of the rear  
and lower clips, it may be lifted off.  
1. Each leg is provided with a screw type support post.  
These may be extended or retracted by turning them  
with a wrench or ChannelLock. Make sure that all  
four legs are in tight contact with the floor for proper  
steamer support.  
ASSEMBLY TIP: When replacing the panel, press the  
rear edge inward so that both clips will be retained by the  
back flange. Make sure that the holes in the panel are in  
alignment with the tapped holes in the steamer so that  
the replacement of the two 10-32 screws will be easy and  
not damage the screws.  
2. If damaged, these posts may be replaced by tapping  
out (on opposite sides of the leg) the threaded fitting  
which is friction held in each stainless steel leg. The  
stainless leg and the threaded fitting are one  
assembly.  
NOTE: The following components and assemblies are to  
be found in the lower table portion of the steamer.  
10.2  
Steamer Table Panels  
Front P/N 096720  
Rear P/N 096785  
Left/Right Side P/N 096848  
10.5  
Steam Generator Drain Valve  
P/N 071234  
1. To remove the steamer table lower panel, simply  
raise the panel and swing out. There are no fasteners  
on this panels and it is retained only by upper and  
lower tracks.  
1. Turn off power and allow steamer to drain  
completely. Remove back cover panel and loosen  
hose clamps.  
2. To remove the front and side panels remove the  
screw(s) holding the panel, then remove the panels.  
2. Disconnect both ends of the drain hose from the  
spray box and the steam generator.  
3. The front and rear panels are unique and the two  
side panels are identical and interchangeable.  
3. Unplug and disconnect the valve electrical wires.  
Remove the nuts holding the valve to the plate.  
Remove the valve from the threaded studs. Then  
remove the silicone hose from the valve.  
10.3  
Left Side - Removal  
P/N 123184  
4. Inspect the silicone hose for any damage or lime  
buildup. Replace hose if required.  
Under normal conditions, the left side cover should never  
have to be removed as there are no operational and/or  
replacement parts to be accessed. The single exception  
is if the door has been reversed so that the handle is on  
the LEFT and the Door Interlock Switch is found to be  
defective and must be replaced. The door switches for  
BOTH door positions are installed at the time of  
manufacture, so there is no need to access the switch if  
the door is to be reversed.  
5. Attach new drain valve to valve bracket. Pull silicone  
hose through drain valve and loosely install hose  
clamps over both ends of the hose. Be sure silicone  
hose is properly aligned and does not have any  
kinks, bends and/or twists.  
OM/SM-HY-6G(CE)  
ꢀꢁ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Position the valve over the valve mounting threaded  
studs and connect both ends of the hose to the drain  
box and steam generator.  
the two screws. Make sure that the valve is NOT  
installed upside down.  
9. Re-attach the hoses to the valve. Slide the hoses all  
the way so that the end of the hose is flush against  
the face of the valve.  
7. Position the spring clamps about 3 mm (1/8") from  
the end of the hose.  
8. Install and tighten valve mounting 10-32 cap nuts.  
9. Plug valve electrical leads into the wiring harness.  
To Test:  
IMPORTANT. Make sure that the correct steam  
generator hose is connected to the corresponding valve  
outlet. Slide the hose clamps back into position around  
the end of the hose and tighten the clamps.  
Slide the hose clamps so that they are within 3 mm (1/8  
inch) from the end of the hose.  
Operate steamer and allow steam generator to fill. Check  
for leaks and observe if drain valve fully closes. Turn off  
steamer and observe that drain valve opens and the  
steam generator drains. Install back cover.  
TOP hose — to the TOP Steam Generator  
MIDDLE hose — to the BOTTOM Steam Generator  
BOTTOM hose — to the DRAIN Box  
10.6  
Water Inlet Valve - Three Way  
P/N 090827  
11. Attach the three sets of wires to the valve making  
sure that the proper wires are connected to the  
corresponding terminals.  
1. Turn off power to the steamer. Turn off the water  
supply to the steamer. Remove the water supply  
hose connection on the rear of the steamer.  
To Test:  
2. As viewed from the rear, remove the back panel and  
the right panel.  
With power ON, turn on the power switch to one cavity.  
The fill solenoid for that steam generator should energize  
allowing water to enter the steam generator. When  
READY light is ON, spray valve solenoid should energize  
and water should enter the drain box.  
3. The water inlet of the valve branches to three  
individual solenoid activated valves within a single  
housing, with the following sets of wires:  
10.7 Water Inlet Valve Coil  
Solenoid  
Wires  
Top Steam Generator Fill: Green and Blue  
Bottom Steam Generator Fill: Violet and Gray  
If a solenoid coil on the water inlet valve is defective,  
replace the entire valve in accordance with Section 10.6.  
Condensate Spray:  
Black and White  
10.8 Drain Box Spray Nozzle  
4. Slide the hose clamps down the hose until needed  
for reassembly. Loosen and remove the hoses using  
a gentle rocking motion.  
P/N 081670  
1. Raise the stainless steel vent pipe to remove it from  
the drain box. Do not loosen the hose clamp around  
the vent pipe. The hose clamp serves to prevent the  
pipe from going too far into the drain box. Secure the  
vent pipe in the raised position.  
5. From the back of the steamer, remove the two  
screws holding the valve assembly in place. Then  
lower the valve WITH THE WIRES STILL  
ATTACHED.  
2. Lift the cover of the drain box. There are no fasteners  
holding the cover on the drain box.  
6. From the back of the steamer, remove the two 8-32  
screws holding the valve assembly in place. Lower  
the valve.  
3. Tip the cover and note there is a circular hole in the  
middle and the spray nozzle (with a hex head) is in  
the center of the hole.  
7. Carefully unplug the connectors, one at a time and  
attach to the new valve.  
4. With a socket wrench, turn the spray nozzle in the  
counter-clockwise direction to remove.  
8. To install a new valve, reverse the procedures and  
first install the six wires (three sets) as listed in Item 3  
of this Section. Fasten the valve to the steamer with  
5. To install new nozzle, place pipe compound on the  
nozzle threads, insert nozzle in socket wrench and  
start the nozzle in the hole. Tighten nozzle.  
ꢀꢂ  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Replace cover on drain box and lower vent pipe into  
the drain box.  
18. Once the steam generator has been removed, the  
fittings and probes may be transferred to the new  
steam generator. Make sure that all screw fittings are  
installed using high temperature pipe compound.  
10.9 Steam Generator  
P/N 094128 and 123655  
NOTE: Refer to appropriate sections for detailed  
1. Shut off power, water and gas supply to the steamer.  
2. Turn main gas valve to the OFF position.  
instructions on fittings and heater assembly.  
19. Install new boiler in the reverse order of removal.  
3. Disconnect the water inlet hose, steam hose and  
drain hose by loosening the hose clamps and  
working the hose off the respective fitting.  
20. Attach the water inlet hose, drain hose and steam  
hose. Tighten hoses around fittings with hose clamps  
10.10  
Steam Generator Probes (High and Low  
Water) P/N 070178.  
4. Disconnect the two boiler manifold gas lines from the  
gas solenoid valves.  
1. Shut off power to the steamer.  
5. Disconnect “spark” lead from igniter module and  
disconnect the two boiler manifold gas lines from the  
manifold. Remove the gas lines from the unit.  
2. With a wrench LOOSEN, but do not remove the nuts  
holding the wire(s) on the probe terminal(s)  
6. Remove flame holders and/or jets if necessary.  
7. Disconnect pilot line from the main gas valve.  
3. The wires are connected to wire fork terminals.  
These will "snap" on and off the terminal post. "Un-  
snap" them by gently pulling on the terminal.  
8. Disconnect “spark” lead from igniter module and pilot  
burner.  
4. Using an open ended wrench, turn the probe  
counter-clockwise to remove.  
9. Remove pilot burner.  
To Install:  
10. If identification is missing from the water level probe  
electrical leads, identify and mark them at this time.  
5. Apply high temperature pipe compound to the probe  
and screw it in by hand. Using an open ended  
wrench, tighten the probe into the fitting.  
11. Disconnect the electrical lead from the water level  
probe which is being removed, and carefully remove  
the probe. Be careful not to damage the ceramic  
material on the probe.  
6. Replace the wire(s) to the probes by snapping the  
fork terminals around the terminal post. Using a  
wrench, tighten the terminal nut.  
12. Clean the probe and the probe holder.  
NOTE: If two probes are to be replaced, either  
replace them one at a time or note the color of the  
wires attached to the probes. Do not get them mixed  
up.  
13. Inspect the probe and its ceramic for damage. If  
damaged, replace the probe.  
14. Disconnect boiler temperature probe leads from  
harness.  
10.11  
Main Gas Valve and Gas Pressure  
Adjustment P/N 122158  
15. Remove temperature probe. If male fitting was  
removed with the probe and compression nut,  
remove it from the probe.  
1. Disconnect power to the steamer.  
2. Remove the front and side panels, as described in  
Section 10.2, above.  
16. With a socket wrench, remove the four 1/4-20 bolts  
holding the steam generator to the steamer table.  
3. Turn the manual gas valve to the closed position.  
Disconnect the wire to the solenoids.  
17. The entire steam generator (with fittings attached)  
may now be removed. Remove outer bolt from the  
side and inner bolt from the rear.  
4. Note the color and position of the two connectors for  
assembly.Remove the aluminum tubing from the  
OM/SM-HY-6G(CE)  
ꢀꢃ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
main gas valve assembly using an open-ended  
wrench. Be careful not to move the aluminum tubing  
excessively, or to bend it.  
4. From the left side (or back) of the steamer, use a  
wrench to loosen and disconnect the aluminum  
tubing to the inner and outer manifolds.  
5. Using a wrench, remove the two bolts that fasten the  
main gas valve bracket.  
5. The entire assembly of both regulators and the gas  
solenoid valves for the upper and lower steam  
generators may be removed as an integrated unit.  
6. With a pipe wrench, open the pipe union on the left  
side of the main gas valve and remove the gas inlet  
pipe from the manual gas valve.  
6. Remove the gas solenoid valve(s) as required.  
To Reinstall:  
7. Remove the main gas valve and manual gas valve  
assembly.  
7. Clean pipe threads and apply compound to all joints  
being connected.  
To Assemble:  
8. Install the new gas solenoid valve.  
8. Clean pipe threads and apply compound to all joints  
being connected.  
9. Slide the assembly into the steamer and reconnect  
the pipe union. Align the gas valves with their  
respective aluminum tubing.  
9. Install the main gas valve in the reverse order of  
removal (Steps 8 through 1).  
10. Using a wrench, connect the aluminum tubing to the  
burner manifold.  
10.12  
Gas Solenoid Valve  
P/N 122120  
11. Reconnect the wires to the correct valve.  
The gas solenoid valves must be removed as an  
assembly along with the regulators, using the following  
procedures:  
10.13  
Igniter Module  
P/N 122180  
1. Turn off the gas supply and power to the steamer.  
1. Shut off power and gas to the steamer.  
2. Disconnect wires from the main gas (Section 10.11)  
and from the gas solenoid valves.  
2. Remove the cover to the electrical compartment.  
3. The igniter module is located under the relays.  
3. From the front of the steamer, loosen and  
disconnect the pipe union which connects the  
assembly to the main gas valve.  
4. Note or tag the wires for reinstallation if necessary,  
before unplugging. Carefully disconnect the push  
REAR VIEW  
ꢀ6  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
terminals from the igniter module. Be careful not to  
pull the terminal by the wire. Use needle nose pliers  
to grip onto the terminal itself.  
7. Remove the flame sensor from the flame sensor  
bracket.  
8. Remove the pilot burner.  
Installation:  
5. Remove the screws that secure the igniter manifold.  
6. Remove the igniter module.  
To Install:  
9. Connect the pilot line to the pilot burner.  
10. Connect the “spark” lead to the pilot burner. Be sure  
to route the lead around the outside of the gas lines.  
7. Position the new igniter against the back wall of the  
electrical compartment.  
11. Replace the flame sensor on the flame sensor  
bracket.  
8. When all four screws are partially threaded, tighten  
them one at a time.  
12. Apply anti-seize lubricant to mounting head screw  
threads. Install the pilot burner and flame sensor  
assembly, and tighten the screws.  
9. Plug in each of the terminals. Double check to  
ensure that they are in the correct location.  
10.14  
Pilot Switch (SW3) Removal  
P/N 087951  
NOTE: Route the “spark” lead and flame sensor wire  
away from the manifold to prevent improper  
operation.  
1. Shut off the power supply. Disconnect the four color  
coded wires from the switch assembly.  
13. Turn manual gas valve to the ON position.  
2. The switch snaps into the metal plate where it is  
retained by plastic tabs on the top and bottom. To  
remove the switch from the plate, press in on both  
tabs at the same time and slide the switch out of the  
bracket hole.  
14. Connect unit to the branch circuit and turn on the  
main gas supply.  
15. Place pilot switch SW3 in the ON position. Check for  
gas soundness.  
To replace the switch  
Pilot Flame Current Check  
3. Insert the new switch into the bracket hole until its  
tabs clear the hole and snap into position.  
4. Reattach the wires to the switch.  
10.15  
Pilot Burner Replacement/Current Check/  
Adjustment - Pilot Flame Sensor  
Replacement  
WARNING  
WHEN STEAMER POWER IS TURNED ON, THERE IS  
HIGH VOLTAGE PRESENT IN THE ELECTRICAL  
COMPONENTS COMPARTMENT. BE SURE THAT  
STEAMER IS DISCONNECTED FROM BRANCH  
CIRCUIT BEFORE PERFORMING ANY REPAIRS.  
P/N 123641)  
P/N 003328 Flame Sensor  
1. Turn off the main gas and power supply.  
2. Remove the front cover.  
1. Turn off steamer power.  
3. Remove the right side panel as described in  
Paragraph 10.2.  
2. Disconnect the ground (green) wire from the igniter  
module.  
4. Turn the manual gas valve to the OFF position. Turn  
the pilot switch to the OFF position.  
3. Connect a DC micrometer between the igniter  
ground terminal and the disconnected green wire.  
5. Disconnect the pilot line from the pilot burner.  
6. Disconnect the “spark” lead from the pilot burner.  
OM/SM-HY-6G(CE)  
ꢀꢄ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12. Fit the burner manifold to the steam generator  
manifold mounting bracket.  
WARNING  
DO NOT ATTEMPT TO LIGHT THE PILOT BURNER  
WITH A FLAME.  
13. Reinstall and tighten the aluminum tubes to the  
burner manifold.  
4. Ignite the pilot. The micrometer should read 3  
microamps minimum.  
NOTE: Ensure all gas connections are sound before  
continuing.  
If current reading is correct, replace the igniter  
module (see 10.13).  
10.17 Timer Assembly  
Timer Fastener Nut  
P/N 101145  
P/N 100983  
If current reading is below 3 microamps,  
continually check the Flame Rectification Circuit  
(large orange wire, spark electrode, pilot burner  
hood, and ground connections). If necessary,  
tighten ground connections and/or replace  
defective component(s).  
1. Remove the three hex nuts which retain the control  
panel cover. Remove the cover.  
2. Remove the knob from the timer. Under the knob is  
a hexagonal nut which holds the time mechanism to  
the steamer. Note that there is a flat on the timer  
shaft which corresponds to a frictional mounting hole  
on the knob.  
5. Check for moisture around the pilot burner, and for  
corrosion on the electrode and the pilot burner hood.  
If necessary, remove moisture with a dry, clean  
cloth. If hood and/or electrode are excessively  
corroded, replace pilot burner assembly.  
3. From the left side, unplug the five terminals/wires  
(violet, gray, black, tan and white) from the timer  
mechanism and unplug the two black timer motor  
leads.  
10.16  
Steam Generator Gas Jet Manifolds  
P/N 123704 and 123705  
4. With an open-ended wrench, remove the hex nut  
holding the timer in place. The timer may then be  
removed from inside the compartment.  
1. Shut-off power and gas to the steamer.  
2. Remove the right side panel.  
NOTE: Right below the timer shaft, the timer has a small  
plastic disk molded onto the case. There is a  
corresponding hole punched into the front panel. This  
hole may be seen from the inside of the compartment  
only when the timer is removed.  
3. Turn manual gas valve to the closed position.  
4. Remove the four aluminum tubes connected to the  
manifolds. Disconnect using an open ended wrench.  
5. Disconnect all wire connections to the pilot.  
To Install:  
6. Remove the two screws from the pilot mounting  
bracket. Remove pilot from the gas manifold.  
5. Fit the timer in place making sure that it is properly  
placed so that the disk on the timer fits into the  
punched hole in the front panel.  
7. Using a wrench, remove the two top and one bottom  
bolts which hold the manifold to the steam generator  
manifold mounting bracket.  
6. Once the timer is properly located, tighten the hex  
nut so that the timer does not slip or rotate. Do not  
over-tighten the nut.  
8. Remove the screws in the heat shield.  
7. Align the flat of the knob hole with the flat on the  
timer shaft. Press the knob firmly onto the timer  
shaft.  
9. Remove the burner manifold from the appliance.  
10. Remove the flame retention springs and injectors as  
required.  
8. Plug in the wires identified above and connect the  
two black wires from the motor leads.  
To Reassemble:  
9. Reattach the control panel cover.  
11. Replace the injectors and retention springs. Ensure a  
suitable gas sealant is used on the threads of the  
injectors to ensure a gas tight seal  
ꢀꢅ  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10.18  
Fan  
P/N 096790  
7. To prepare motor for mounting, slide the oil slinger  
washer onto the shaft about ½" (12 mm) down the  
shaft.  
IMPORTANT: Make sure that the fan has come to a  
complete stop before attempting any work on the fan.  
IMPORTANT: This washer has two surfaces: A  
rubber surface and a phenolic surface. Make sure  
the phenolic surface is facing the motor.  
1. To remove the fan from either the top or bottom  
cavity, open the door and remove the pan support  
wire rack in front of the fan.  
8. Install the plate seal holder onto the motor shaft.  
Carefully slide the plate seal holder down the motor  
shaft until it engages the slinger washer. Continue  
moving the plate seal holder down the motor shaft  
until the plate comes to rest on the raised bosses of  
the motor casting.  
2. With an allen wrench, loosen the set screw which  
holds the fan to the motor shaft.  
3. Hold onto the fan, and with a slight rocking motion  
pull the fan off the motor shaft.  
To Install:  
9. Using this technique, the rubber side of the oil  
Slinger washer should be in contact with the plate  
holder and there should be a space of  
4. Note that the motor shaft has a flat surface. Position  
the fan hub on the motor shaft so that the allen set  
screw is opposite the flat portion of the motor shaft.  
approximately 5/64" (2 mm) between the  
phenolic face of the washer and the motor.  
5. Slide the fan onto the motor shaft far enough so that  
the motor shaft is at the end of the fan hub.  
10. Using four hex/slotted 6-32 screws, screw the motor  
mounting plate to the motor with each screw passing  
through corresponding holes in the plate seal holder.  
6. With an allen wrench, tighten the set screw on the  
fan.  
11. The entire assembly may now be positioned on the  
four threaded studs protruding from the cavity wall.  
Fasten the assembly with nuts using a wrench. Make  
sure that the green/yellow ground strap is secured  
under one of the nuts securing the motor. The upper  
motor has a drip shield installed on the lower studs.  
NOTICE: Advise customer to periodically clean the fan  
blades of deposited food grade grease coming from the  
foods being cooked. The deposit of such grease over  
time could cause the fan to vibrate.  
10.19  
Fan Motor Assembly  
P/N 096740  
Motor Insulation  
P/N 094135  
10.20  
Motor Starting Capacitor  
P/N 096813  
Motor Shaft Seal  
P/N 096868  
Oil Slinger Washer  
P/N 096831  
1. Turn off electrical power to the steamer.  
1. Shut off electrical power to the steamer.  
2. Loosen and remove the screw holding the capacitor.  
2. From inside the cavity, remove fan using an allen  
wrench as indicated in Section 10.17.  
3. Unplug the two terminal wires from the capacitor.  
Remove the capacitor.  
3. Using a socket wrench, remove the four 1/4-20 Keps  
nuts holding the motor. Note that one of the nuts  
secures the motor ground strap to the steamer.  
To Install New Capacitor:  
NOTICE: Make sure that the correct capacitor is  
used, which is 3 mfd at 330 volt.  
To Install a New Motor:  
4. Make sure the capacitor is seated properly, then  
tighten the screw securing the capacitor to the  
mounting plate.  
4. Make sure the motor insulation board is installed on  
the four threaded studs to the cavity wall.  
5. Apply lubricant on both sides of the steamer motor  
seal and the inside hole. Refer to the Motor  
Assembly Chart.  
5. Plug terminal wires to the capacitor.  
10.21  
Steam Generator Ready Thermostat  
P/N 088865  
6. Insert the steamer motor seal in the cutout of the  
insulator board.  
This thermostat is attached to the cavity steam port.  
OM/SM-HY-6G(CE)  
ꢀꢆ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Turn off power to the steamer.  
cavity and one for the bottom cavity. If both hoses are to  
be replaced, replace them one at a time.  
2. Unplug the two wires from the thermostat.  
3. Using a wrench, remove the thermostat.  
1. Shut off power to the steamer.  
2. Remove cavity side and lower side panels of table.  
4. To install a new thermostat, use a small amount of  
heat sink compound (1 drop), applied to bottom of  
thermostat. Seat the thermostat on the steam port  
and connect.  
3. In the upper portion of the steamer, remove hose.  
Turn and pull the hose to remove it from the hose  
nipple.  
5. Plug the thermostat into the wiring harness.  
4. In the lower section of the steamer, remove the hose  
clamp from where the hose is connected to the  
steam generator. Turn and pull the hose to remove it  
from the hose nipple.  
10.22  
Steam Port  
Gasket  
P/N 096736  
P/N 099250  
1. Shut off power to the steamer.  
5. The hose may be removed. Be careful that the hose  
clamps do not fall off and get lost.  
2. Remove the 1-1/8 inch steam hose by loosening the  
clamp around the hose and sliding it away from the  
steam port. Turn and pull to loosen hose and remove  
from steam port.  
IMPORTANT: Make sure that the correct part (and  
part number) are being used. The two hoses in the  
steamer are of different lengths. (See Page 21 for  
Part Numbers.)  
3. With a wrench, remove the screws holding the  
thermostat to the steam port.  
To Install:  
4. Cut and fold up aluminum foil insulation blanket to  
expose the two nuts which hold the steam port to the  
cavity wall threaded studs.  
6. Slide the two hose clamps onto the hose and  
position the hose adjacent to the steam port and  
steam generator.  
5. With a wrench, remove the two nuts.  
6. Remove the steam port.  
To Install:  
7. Slide the hose onto the hose nipple on the steam  
port and at the other end, onto the steam generator  
nipple. Make sure the hose is on all the way so that  
the end of the hose is against the face of the nipples.  
8. Install the hose clamps 3 mm (1/8") from the end of  
the hose.  
7. Put a small bead of silicone sealant in and around  
the groove in the steam port to seal any possible  
leaks, or use gasket P/N 099250.  
10.24  
Door Removal/Installation/Alignment  
P/N 094150  
8. Install steam port on threaded studs. Secure with two  
nuts.  
1. To remove the door, turn off the steamer power and  
allow the steamer to cool. Then, remove door by  
supporting the weight of the door and remove hinge  
pin.  
9. Fold down aluminum foil insulation blanket to original  
blanket position and repair cuts with aluminum foil  
duct tape.  
2. Place the door on a flat, clean table or similar  
support, with gasket facing up. Be careful not to  
scratch door surface.  
10. Reinstall thermostat as described in 10.20 above.  
11. Reinstall steam hose to steam port and install the  
clamp.  
3. Inspect door gasket for signs of cuts or other defects  
which may impair its function. Replace if necessary.  
10.23  
Cavity Steam Hose Assemblies  
P/N 099953 (Top)  
To Install:  
P/N 088880 (Bottom)  
4. To install the door, apply NEVER-SEEZ lubricant to  
hinge pin. Align door with hinge and insert hinge pin.  
There are two hoses which connect the steam  
generators with their respective cavities. One for the top  
ꢁ0  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Loosen lock nut with a wrench. Remove door locking  
pin and lock nut.  
To Align:  
5. Place a piece of masking tape over the door pin  
(bullet) hole in the door.  
6. Coat bullet threads with NEVER-SEEZ high  
temperature compound. Install door locking pin and  
lock nut directly across steamer cavity from old door  
locking pin location. Install these items so that lock  
nut-to-end of bullet distance is approximately the  
same as measured in Step 4.  
6. Close the door until the door pin just penetrates the  
masking tape. Make sure the door pin contacts only  
the door latch spring.  
7. If door pin does not strike the center of the spring  
hole in the U-channel, loosen the hinge-to-oven bolts  
and align the door to the door pin. Tighten hinge-to-  
oven mounting bolts.  
7. Remove the two truss head screws from above and  
below the old bullet location and install them above  
and below the new bullet location.  
8. Remove screws and U-channel from the door. Take  
the magnet and block assembly from present  
location and place it at the opposite end of the door  
channel, with the magnet facing outward from the  
door.  
8. You should be able to pull a dollar bill or comparable  
piece of paper smoothly between the gasket and  
oven cavity with the door closed. To adjust the hinge  
side, loosen the door-to-hinge bolts and align the  
door gasket with the oven cavity. Tighten the door-  
to-hinge mounting bolts. To adjust the bullet side  
refer to 10.30.  
9. Remove screws which secure the handle. Remove  
door handle from cam.  
9. Operate the steamer and check for leaks.  
10. Apply NEVER-SEEZ high temperature (rated for  
250ºC) anti-seize and lubricating compound to the  
cam and Locktite 242 to screw threads.  
10.25  
Door Switch  
P/N 096857  
11. Turn handle and cam 180-degrees from their original  
positions and install them on the door with screws.  
Be sure handle and cam move smoothly.  
1. From the right side of the steamer with panel  
removed, unplug the door switch from the cable  
harness.  
12. Be sure door handle is in the DOWN position. Turn  
U-channel 180-degrees from its original position,  
hold door spring in U-channel open with a  
2. The switch (for normal door opening) is held in place  
with two small screws. With a flat blade screwdriver,  
remove these screws and the switch may be  
removed.  
screwdriver or similar tool, and install U-channel.  
Don not install the screw at this time.  
3. To install screws for the door switch reverse the  
above procedure.  
13. Check operation of the cam. Push up on the door  
handle and check if the spring opens. If the spring  
does not open, cam and spring are NOT correctly  
aligned and problem must be corrected.  
4. If the door has been reversed and the switch must  
be removed and replaced, refer to the top and left  
side panel removal in Section 10.3 and then remove  
the switch as above.  
14. Apply a light amount of Locktite 242 to screws, then  
install screws securing U-channel.  
10.26  
Door Reversing Procedures  
15. Apply Locktite 242 to the hinge-to-steamer bolts,  
then install door and hinge mounting bolts. Do NOT  
tighten mounting bolts at this time.  
1. Turn off steamer power and allow steamer to cool.  
2. To remove door, support door while removing hinge-  
to-steamer bolts.  
16. Align door to steamer. Refer to 10.24, Alignment  
procedure.  
3. Place door with hinge on a flat, clean table (or similar  
support), with the gasket facing up. Be careful not to  
scratch door surface.  
IMPORTANT. When the door is reversed, the alternate  
door switch (installed at time of manufacture) must be  
connected to the circuit.  
4. Note and record distance between lock nut and end  
of door locking pin (bullet). This information will be  
needed during bullet installation described in Step 6.  
17. From the right side access to the upper portion of the  
steamer, disconnect the two leads of the door  
switch.  
OM/SM-HY-6G(CE)  
ꢁ1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
18. The wires for the alternate door switch may be  
foundunder the cavities. Connect the two wires from  
the switch to the wiring harness.  
13. Align door to steamer, per Paragraph 10.24..  
10.28 Door Handle, Magnet and Block Assembly  
Door Handle  
Magnet & Block  
Screws  
P/N 070123  
P/N 069762  
P/N 005764  
P/N 074252  
19. Close steamer door and operate steamer for six to  
eight minutes. If steamer fan does not operate,  
check location of door magnet and try operation  
again. If fan operation problem still exists, refer to  
the Troubleshooting Section of this Manual.  
Door Cam  
U-Channel Assy P/N 094144  
Outer Door Panel P/N 094140  
Inner Door Panel P/N 094141  
Door Insulation Bd P/N 094192  
20. Allow steamer to operate for approximately 5  
minutes, and then check for leaks. If there are no  
leaks then steamer is ready for operation. If there  
are leaks around the door, recheck door alignment,  
and if necessary, door gasket installation.  
1. Turn steamer off and allow it to cool.  
2. Remove screws and U-channel from the door.  
10.27  
Door Gasket  
P/N 094147  
3. Remove screws securing handle, door handle, and  
cam.  
1. To install, turn off steamer, and allow to cool.  
4. Apply a NEVER-SEEZ high temperature compound  
to the door cam and Locktite 242 to screw threads.  
2. Remove the door hinge using one of the following  
two methods:  
5. Assemble door cam to handle with screws.  
a) Support door weight and remove hinge pin, or  
6. Be sure door handle is in the DOWN position. Hold  
U-channel door spring open with a screwdriver or  
similar tool, then install the U-channel. Do NOT  
install screws at this time  
b) Support weight of the door and remove the two  
door-to-hinge bolts.  
3. Place the door on a flat, clean, smooth table or  
7. Check operation of the cam and door spring. Push  
up on the door handle and check if spring opens. If  
the spring does not open, the cam and spring are not  
correctly aligned and the problem must be corrected.  
similar support. Be careful not to scratch the door  
4. Position door on workbench so that its front is lying  
flat, with handle hanging over edge of bench.  
8. Apply a light amount of Locktite 242 to screws, then  
install screws, securing U-channel.  
5. Remove inner door panel.  
6. Remove and discard gasket.  
10.29  
Door Spring  
P/N 078911  
7. Clean back of the inner door panel. Be sure old  
sealant is completely removed.  
1. Turn off steamer and allow it to cool.  
8. Install new door gasket around inner door panel. Be  
sure the inner door panel flange is fully inserted into  
the door gasket groove.  
2. With flat blade screwdriver, remove two screws on  
U-channel and remove U-channel from door.  
3. Carefully remove retaining ring from one end of  
spring support pin, then remove the pin by moving  
the pin to the left and to the right.  
9. Apply a high temperature silicone sealant, such as  
GE RTV 180 or equivalent, to the four door spacers.  
10. Apply Locktite 242 to the inner door panel mounting  
screws.  
4. With a wrench, remove the nut. Lift the spring  
retainer, and then remove the spring.  
11. Install inner door panel and door gasket on the door  
spacers, and tighten mounting screws.  
To Install:  
5. Apply a high temperature (rated 250ºC) anti-seize,  
lubricating compound (NEVER-SEEZ) on the bottom  
of the U-channel surface that contacts the spring.  
12. Align door with hinge and insert hinge pin OR apply  
Locktite 242 to the door-to-hinge bolts, then install  
door and mounting bolts. Do NOT tighten mounting  
bolts at this time.  
ꢁꢀ  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Install spring onto brass roller, then place square  
plate over spring.  
2. Note and record the distance between the lock nut  
and the end of the (bullet shaped) door locking pin.  
This information is important and will be needed for  
installation.  
7. Apply Locktite 242 to Keps nut and install Keps nut.  
8. Install spring support pin, then push the retaining ring  
onto the pin using a screwdriver.  
3. Loosen lock nut and remove lock nut and door pin  
(bullet) from front panel.  
9. Hold door spring open with a screwdriver or similar  
tool, hold door handle in the down position and install  
the U-channel, top end first - then lower channel into  
position. Check that spring opens when door handle  
is pushed up.  
4. To install new door locking pin, coat locking pin  
threads with NEVER-SEEZ high temperature  
compound.  
5. Install locking pin and lock nut. The lock nut to end-  
of-bullet distance should be approximately the same  
as measured above, in Step 2.  
10. Apply Locktite 242 to U-channel mounting screws,  
then install the screws.  
10.31  
Indicator Neons (Lockout)  
11. Replace the two screws in the U-channel, applying  
Locktite 242 to secure them in place.  
1. Turn off main gas supply  
2. Turn off oven power and disconnect from branch  
circuit power.  
3. Remove upper right side panel  
10.30  
Door Locking Pin  
P/N 078914  
Lock Nut  
P/N 003823  
4. Replace neons as necessary.  
1. Turn steamer off and allow it to cool.  
OM/SM-HY-6G(CE)  
ꢁꢁ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ꢁꢂ  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12.0 - Service Log  
Model No.  
Purchased From  
Serial No.  
Location  
Date Purchased  
Purchase Order No.  
Date Installed  
For Service Call  
Date  
Maintenance Performed  
Performed by  
OM/SM-HY-6G(CE)  
ꢁꢃ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Limited Warranty To Commercial Purchasers*  
(for Areas Outside of the U.S. and Canada)  
Groen Foodservice Equipment ("Groen Equipment") has been skillfully manufactured, carefully inspected and  
packaged to meet rigid standards of excellence. Groen warrants its Equipment to be free from defects in material and  
workmanship for twelve months from date of installation or eighteen months from date of shipment with the following  
conditions and subject to the following limitations.  
I.  
This parts warranty is limited to Groen Equipment sold to the original commercial purchaser/users (but not  
original equipment manufacturers), at its original place of installation, in areas outside the U.S. and Canada.  
II. Damage during shipment is to be reported to the carrier, is not covered under this warranty, and is the sole  
responsibility of the purchaser/user.  
III. Groen, or an authorized service representative, will repair or replace parts, at Groen's sole election, for any  
Groen Equipment, including but not limited to, draw-off valves, safety valves, gas and electric components,  
found to be defective during the warranty period.  
IV. This warranty does not cover boiler maintenance, calibration, or periodic adjustments as specified in  
operating instructions or manuals, and consumable parts such as scraper blades, gaskets, packing, etc., or  
labor costs incurred for removal of adjacent equipment or objects to gain access to Groen Equipment. This  
warranty does not cover defects caused by improper installation, abuse, careless operation, or improper  
maintenance of equipment. This warranty does not cover damage caused by poor water quality or improper  
boiler maintenance.  
v. THIS WARRANTY IS EXCLUSIVE AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR  
IMPLIED, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A  
PARTICULAR PURPOSE, EACH OF WHICH IS HEREBY EXPRESSLY DISCLAIMED. THE REMEDIES  
DESCRIBED ABOVE ARE EXCLUSIVE AND IN NO EVENT SHALL GROEN BE LIABLE FOR SPECIAL,  
CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR THE BREACH OR DELAY IN PERFORMANCE OF  
THIS WARRANTY.  
VI. Groen Equipment is for commercial use only. If sold as a component of another (O.E.M.) manufacturer's  
equipment or if used as a consumer product, such Equipment is sold AS IS and without any warranty.  
* (Covers All Food Service Equipment Ordered After October 1,1995)  
ꢁ6  
OM/SM-HY-6G(CE)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1055 Mendell Davis Drive • Jackson MS 39272  
888-994-7636 • 601-372-3903 • Fax 888-864-7636  
groen.com  
PART NUMBER 128805, REV. C (4/06)  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Techno Source Handheld Game System 20720 User Manual
Teledyne Respiratory Product 3190Z User Manual
Tiger Games 59939 2 User Manual
Toshiba Digital Camera IK 645A User Manual
Toshiba Scanner PA3712D 1ETC User Manual
Tote Vision Computer Monitor LCD 1513VB User Manual
U Line Refrigerator U 2115RB 00 User Manual
Verbatim MP3 Player VM 205 User Manual
Vizio Outdoor Ceiling Fan C BC511C User Manual
Vulcan Hart Fryer MF 1 User Manual