Trane Fan SS PRC003 EN User Manual

Split System  
Cooling Units  
Split System Cooling Units  
TTA075A-TTA200B  
Air Handlers  
TWE050A-TWE200B  
50 Hz  
December 2000  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Introduction  
2
4
7
Features and Benefits  
Application Considerations  
Selection Procedure  
8
9
Model Number Description  
General Data  
10  
Performance Data  
13  
Cooling Performance  
Fan Performance  
13  
39  
46  
Electric Power  
Connection andWiring  
Dimension andWeights  
Mechanical Specifications  
48  
54  
75  
SS-PRC003-EN  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features  
and Benefits  
Condensing Units  
Air Handlers  
Trane 3-D® scroll compressor  
(TTA075-100A)  
Low voltage terminal board  
Expansion valve(s)  
(2)Trane Climatuffcompressors  
(TTA100-125B) with independent  
refrigerant circuits  
Convertible  
PVC drain pan  
Fan relay  
(2)Trane 3-D scroll compressors  
(TTA155-200B) with independent  
refrigerant circuits  
2) Manifolded scroll compressors with  
unloading capability (TTA100-155C)  
Compressor motor overload protection  
Control transformer  
High and low pressure cutout switches  
Internal pressure relief valve (TTA100B-  
125B)  
Liquid line filter drier, factory installed  
Holding charge of nitrogen  
Copper tube, aluminum plate fin coils  
Low ambient cooling to 35°F (1.7°C) as  
manufactured  
Efficient evaporator coil  
Baked enamel finish  
Filter access panel  
1” (25.4 mm) throwaway filters standard  
with provisions for field supplied 2”  
(50.8 mm) filters  
Adjustable belt drive motor  
Single point power entry to electric  
heaters  
Refrigerant piping and/or electrical  
connections provided from either side  
Odysseyair handler versatility is  
further increased by a complete line of  
optional accessories designed to match  
and easy to install:  
Discharge Plenum and Grille  
Return Grille  
Subbase  
Electric Heaters  
High Static Evaporator Motor  
Isolators both Rubber-in-Shear and  
SpringType  
Weather resistant baked enamel finish  
Heavy gauge steel cabinet  
Mounting/lifting rails under base  
All condensing units offer these  
optional accessories:  
Head Pressure Control — Low Ambient  
CoolingTo 0°F (-17.8°C)  
Coil Guards Kits  
Isolators both Rubber-in-Shear and  
SpringType  
Anti-Short-Cycle Kit  
Time Delay Relay  
Black Epoxy Coated Condenser Coils  
4
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features  
and Benefits  
Condensing Units Options  
In addition, Odyssey modelsTTA100B,  
TTA125B,TTA155B andTTA200B are dual  
compressor units to give true standby  
protection; if one compressor fails, the  
second will automatically start-up. Also,  
the first compressor can be serviced  
without shutting down the unit since  
refrigerant circuits are independent.  
The Odysseysplit system product line  
includes condensing units in both single  
unloading and dual compressor options.  
TTA075A andTTA100A-ton single  
compressor models feature single  
refrigeration circuitry lowering job  
installation costs by requiring only one  
set of refrigerant lines.These units are  
ideal for their low cost, new construction  
jobs, as well as renovation and  
Dual compressors are not just for  
protection; they also save energy costs.  
Most buildings are designed for the peak  
load requirements, yet the building  
usually operates at less than peak load.  
During light load conditions only one  
compressor functions to maintain the  
space comfort thus reducing the need  
for energy.  
replacement buildings.  
Equally important, Odyssey offers a  
single refrigerant circuit/capacity  
unloading option inTTA100C and  
TTA155C condensing units. These  
unloading units feature dual manifolded  
scroll compressors. They offer an  
excellent opportunity for both new  
construction and replacement jobs with  
two stages of capacity modulation and a  
single refrigeration circuit.  
Trane split systems have been specified  
in thousands of applications.You will  
find Odyssey will win even more jobs  
with its smaller, more manageable  
cabinet.  
LowAmbient Cooling Operation  
Each condensing unit can operate to  
35°F (1.7°C) as standard. An accessory  
Head Pressure Control gives you the  
capability to operate to 0°F (-17.8°C).  
SS-PRC003-EN  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features  
and Benefits  
Air Handlers Offer  
More Flexibility  
Flexibility is a key to meeting changing  
market requirements. Odyssey split  
systems offer not only various  
compressor options but also convertible  
air handlers.The air handlers can be  
installed either vertically in a mechanical  
room or horizontally above a ceiling.  
They do not require any removal of  
panels or reconfiguration of the drain  
pan to make either airflow application  
work.These air handlers have a double  
sloped condensate drain pan that allows  
for either airflow configuration and can  
easily be removed for cleaning. All the  
air handlers feature factory installed belt  
drive and ball bearing evaporator fans  
with adjustable sheaves for maximum  
airflow performance.The standard motor  
on theTWE100A air handler will deliver  
3325 cfm (5650 m3/h) at 1.0” (250 Pa) ESP.  
Additionally, oversized motors are  
available for higher static applications.  
Odyssey air handler versatility is further  
increased by a complete line of  
accessories designed to match and install  
smoothly:  
Discharge Plenum and Grille  
Return Grille  
Subbase  
Electric Heaters  
High Static Evaporator Motor  
Isolators both Rubber-in-Shear and  
SpringType  
A Full Line ofThermostats  
OdysseyA Complete  
Split System  
Odyssey delivers the flexibility to select a  
complete system that meets your  
particular job requirements. Air Handlers  
are designed, tested, and rated with  
condensing units to let you select the  
proper match between capacity and load.  
Condensing units can also be matched  
withTrane built-up air handlers.These  
matched systems can be quickly  
engineered for specific applications using  
Trane’s computerized selection  
programs.  
6
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application  
Considerations  
Application of this product should be  
within the catalogued airflow and  
performance considerations.  
LowAmbient Cooling  
As manufactured, these units can  
operate to 35°F (1.7°C) in the cooling  
mode of operation. An accessory head  
pressure control will allow operation to  
0°F (-17.8°C) outdoor ambient.When  
using these units with control systems  
such as bypass changeoverVariable Air  
Volume, consider the requirement for a  
head pressure control to allow low  
ambient cooling.  
Clearance Requirements  
The recommended clearances identified  
with unit dimensions should be  
maintained to assure adequate  
serviceability, maximum capacity and  
peak operating efficiency. Actual  
clearances that appear inadequate  
should be reviewed with your localTrane  
Representative.  
Typical HorizontalAir HandlerApplication  
Typical Split System Application  
TypicalVerticalAir HandlerApplication  
SS-PRC003-EN  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection  
Procedure  
Cooling Capacity  
Note:The formula below the table can  
be used to calculate Fan Motor Heat,  
3.5 x Bhp = MBh  
Step 1 — Calculate the buildings total  
and sensible cooling loads at design  
conditions. Use theTrane calculation  
form or any other standard accepted  
method.  
3.5 x 1.17 = 4.10 MBh  
1.375 x (kW) = kW  
1.375 x 0.8 = 1.1 kW  
Step 2 — Size the equipment usingTable  
13-1. Match the cooling loads at design  
conditions.  
NetTotal Cooling Capacity =  
77.7 MBh – 4.10 = 73.6 MBh  
16.8 - 1.2 = 15.6 kW  
Net Sensible Cooling Capacity =  
57.3 MBh – 4.10 = 53.2 MBh  
22.8 - 1.2 = 21.6 kW  
Example:The following are the building  
cooling requirements  
a
Electrical Characteristics: 380-415/50/3  
Heating Capacity  
b
Step 1 — Calculate the building heating  
Summer Design Conditions: Entering  
load.  
Evaporator Coil: 80 DB/67WB  
Step 2 — Size the system heating  
(27 DB/19WB C)  
capacity to match the calculated building  
Outdoor Ambient: 95° F (35° C)  
heating load.The following are building  
c
heating requirements:  
Total Cooling Load: 75 MBh (22 kW)  
a
d
Total Heating Load at 97.0 MBh (28.4 kW)  
Sensible Cooling Load: 53 MBh  
b
(15.5 kW)  
3000 cfm (5097 m3/h)  
e
Airflow: 3000 cfm (5097 m3/h)  
External Static Pressure: 0.77 in.  
(192.5 Pa)  
c
Electric Supplementary Heaters  
Table 45-1, the 34.88 kW heater has a  
capacity of 119,045 btu. FromTable  
47-1, the 34.88 kW indicates the heater  
model number is BAYHTRL435A.This  
heater will adequately cover the  
buildings heating requirement.  
Table 13-1 shows that aTTA075A  
matched with aTWE075A has a gross  
cooling capacity of 77.7 MBh (22.8 kW)  
and 57.3 MBh (16.8 kW) sensible capacity  
at 95 DB (35° C) ambient and 3000 cfm  
(5097 m3/h) and 80 DB/67WB (27 DB/19  
WB) air entering the evaporator.  
Air Delivery Selection  
External static pressure drop through  
the air distribution system has been  
calculated to be 0.77 inches (192.5 Pa) of  
water gauge. FromTable 44-2 static  
pressure drop through the electric  
heater is 0.23 inches (57.5 Pa) of water  
(0.77 + 0.23 = 1.00 in.) (192.5 + 57.5 = 250  
Pa). EnterTable 39-1 forTWE075AD at  
3000 cfm (5097 m3/h) and 1.00 static  
pressure (250 Pa).The standard motor at  
821 rpm will give the desired airflow.  
To find the net cooling capacities, fan  
motor heat must be subtracted.  
Determine the total unit static pressure:  
In.  
0.77 193  
0.10 25  
Pa  
External Static  
Standard Filter  
Supplementary  
Electric Heat  
0.23 57  
Total Static Pressure 1.10 275  
Note:The Evaporator Fan Performance  
Table has included the effect of a 1 in.  
(250 Pa) filter already.Therefore, the  
actualTotal Static Pressure is 1.10 - 0.10 =  
1.00 in. (275 - 25 = 250 Pa).  
With 3000 cfm (5097 m3/h) and 1.00  
inches (250 Pa), Table 39-1 shows a 1.17  
bhp (0.8 kW).  
8
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model  
Number  
Description  
CONDENSING UNIT MODEL NOMENCLATURE  
T T A 0 7 5  
A
D
0 0  
B
0
Service Digit  
TTA = Cooling Only  
Minor Design Sequence  
Nominal Gross Cooling Capacity (MBh)  
075 = 75  
100 = 100  
155 = 155  
200 = 200  
Factory Installed Options  
00 = No Options  
0S = Black Epoxy Coated Condenser Coil  
Electrical Characteristics  
D = 380-415/3/50  
Compressor  
A = Single Compressor  
B = Dual Compressor  
C = Scroll  
AIR HANDLER MODEL NOMENCLATURE  
T W E 0 5 0  
A
D
0 0  
B
0
Service Digit  
TWE = Cooling Convertible  
Minor Design Sequence  
Nominal Gross Cooling Capacity (MBh)  
050 = 50  
075 = 75  
100 = 100  
155 = 155  
200 = 200  
Factory Installed Options  
00 = No Options  
Electrical Characteristics  
D = 380-415/3/50  
Refrigerant Circuit  
A = Single  
B = Dual  
SS-PRC003-EN  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
Condensing Unit  
Table GD-1 General Data  
TTA075A  
TTA085A  
TTA100A  
TTA100B  
Cooling Performance1  
Gross Cooling Capacity, btu (kW)  
Matched Air Handler (kW)  
Condensing Unit Only2 (kW)  
ARI Net Cooling Capacity3 (kW)  
System Power kW  
Condensing Unit Power kW  
Compressor  
82,000(24.01)  
80,000(23.36)  
79,000(23.06)  
7.92  
91,000(26.64)  
91,000(26.64)  
87,000(25.47)  
8.7  
111,000(32.59)  
107,000(31.36)  
107,000(31.36)  
10.66  
102,000(30.0)  
102,000(30.0)  
100,000(29.3)  
11.3  
7.32  
7.8  
9.76  
10.3  
Number  
1
1
1
2
Type  
Trane 3-D® Scroll  
Trane 3-D® Scroll  
Trane 3-D® Scroll  
Trane Climatuff™  
2
No. Speeds  
No. Motors  
Motor HP (kW)  
1
1
1
1
1
1
6.25 (4.7)  
2875  
8.8  
6.91(5.16)  
2875  
8.8  
8.33(6.21)  
2875  
8.8  
4.15(3.1)  
2875  
9.0  
Motor RPM  
ARI Sound Rating (Bels)4  
System Data5  
No. Refrigerant Circuits  
Suction Line in. (mm) OD  
Liquid Line in. (mm) OD  
Outdoor Coil Type  
Tube Size in. (mm) OD  
Face Area, sq. ft (m2)  
Rows  
Fins Per Inch  
Outdoor FanType  
No. Used  
1
1.375(34.9)  
0.500(12.7)  
Plate Fin  
0.375(9.5)  
15.33(1.42)  
2
20(508)  
Propeller  
1
1
1
1.375(34.9)  
0.500(12.7)  
Plate Fin  
0.375(9.5)  
18.4(1.71)  
2
20(508)  
Propeller  
1
2
1.120(28.5)  
0.375(9.5)  
Plate Fin  
0.375(9.5)  
18.43(5.6)  
2
20(508)  
Propeller  
1
1.375(34.9)  
0.500(12.7)  
Plate Fin  
0.375(9.5)  
18.43(1.71)  
2
20(508)  
Propeller  
1
Diameter in. (mm)  
DriveType  
26.00(660.4)  
Direct  
28.00(711.2)  
Direct  
28.00(711.2)  
Direct  
28.00(711.2)  
Direct  
No. Speeds  
1
1
1
1
CFM6 (m3/h)  
No. Motors  
4700(7985)  
1
6500(11042)  
1
6500(11042)  
1
6500(11042)  
1
Motor HP (kW)  
Motor RPM  
0.33(.24)  
925  
13.0(5.90)  
0.75(.56)  
925  
16.0(7.26)  
0.75(.56)  
975  
16.0(7.26)  
0.75(.55)  
925  
18.8(8.5)  
R-22 Refrigerant Charge, lb7 (kg)  
Notes:  
1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (26.7°C) entering dry bulb, 67°F (19.4°C) entering wet bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this  
product. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of  
nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.  
2. Condensing Unit Only Gross Cooling Capacity rated at 45°F (7.2°C) saturated suction temperature and at 95°F (35°C) ambient.  
3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft (7.2 m) of 1.375, 0.500 OD interconnecting tubing. EER and/or SEER are rated at ARI conditions and in  
accordance with DOE test procedures. Integrated Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80°F (26.7°C) ambient, 80°F (26.7°C) entering dry bulb,  
and 67°F (19.4°C) entering wet bulb at ARI rated cfm.  
4. Sound Rating shown is tested in accordance with ARI Standard 270.  
5. System Data based on maximum linear length 80 ft (26.7 m) Maximum lift: suction 60 ft (18.3 m) liquid 60 ft (18.3 m) For greater lengths, refer to refrigerant piping applications  
manual.  
6. Outdoor Fan cfm is rated with standard air-dry coil outdoor.  
7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft (7.6 m) of interconnecting refrigerant lines.  
10  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
Condensing Unit  
Table GD-2General Data  
TTA100C  
TTA125B  
TTA155B  
TTA155C  
TTA200B  
Cooling Performance1  
Gross Cooling Capacity, btu (kW)  
Matched Air Handler  
Condensing Unit Only2  
ARI Net Cooling Capacity3  
System Power kW  
Condensing Unit Power kW  
Compressor  
108,000(31.62)  
108,000(31.62)  
106,000(31.05)  
9.61  
127,000(37.2)  
127,000(37.2)  
123,000(36.0)  
13.1  
166,000(48.60)  
163,000(47.73)  
161,000(47.14)  
16.01  
160,000(46.85)  
155,000(45.39)  
153,000(44.80)  
15.4  
216,000(63.24)  
209,000(61.18)  
209,000(61.18)  
21.40  
9.01  
12.1  
14.58  
14.6  
19.39  
Number  
Type  
No. Speeds  
No. Motors  
2
2
2
2
2
ScrollTandem  
2
Trane Climatuff™  
Trane 3-D® Scroll  
Trane 3-D® ScrollTandem  
Trane 3-D® Scroll  
1
2
1
2
1
1
1
2
Motor HP (kW)  
4.16(3.10)  
2875  
8.8  
5.20(3.9)  
2875  
8.8  
6.25(4.7)  
2875  
8.8  
6.25(4.7)  
2875  
8.8  
8.33(6.21)  
2875  
8.8  
Motor RPM  
ARI Sound Rating (Bels)4  
System Data5  
No. Refrigerant Circuits  
Suction Line in. (mm) OD  
Liquid Line in. (mm) OD  
Outdoor Coil Type  
Tube Size in. (mm) OD  
Face Area, sq. ft (m2)  
Rows  
Fins Per Inch  
Outdoor FanType  
No. Used  
1
1.375(34.9)  
0.500(12.7)  
Plate Fin  
0.375(9.5)  
18.4(1.71)  
2
20 (508)  
Propeller  
1
2
2
1.375(34.9)  
0.500(12.7)  
Plate Fin  
0.375(9.5)  
30.66(2.84)  
2
20(508)  
Propeller  
2
1
1.625(41.3)  
0.625(15.9)  
Plate Fin  
0.375(9.5)  
30.66(2.84)  
2
20 (508)  
Propeller  
2
2
1.375(34.9)  
0.500(12.7)  
Plate Fin  
0.375(9.5)  
43.9(4.08)  
2
15(381)  
Propeller  
2
1.375(34.9)  
0.500(12.7)  
Plate Fin  
0.375(9.5)  
23.97(7.3)  
2
18(457.2)  
Propeller  
1
Diameter in. (mm)  
DriveType  
28.00(711.2)  
Direct  
28.00(711.2)  
Direct  
26.00(660.4)  
Direct  
26.00(660.4)  
Direct  
28.00(711.2)  
Direct  
No. Speeds  
1
1
1
1
1
CFM6 (m3/h)  
No. Motors  
6500(11042)  
1
6760(11484)  
1
9400(15969)  
1
9400(15969)  
1
13400(22764)  
2
Motor HP (kW)  
Motor RPM  
0.75(.56)  
925  
15.5(7.03)  
0.75(.55)  
925  
25.2(11.4)  
0.33(.24)  
925  
26.0(11.8)  
0.33(.24)  
925  
27.0(12.34)  
0.75(.56)  
925  
36.0(16.33)  
R-22 Refrigerant Charge, lb7 (kg)  
Notes:  
1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (26.7°C) entering dry bulb, 67°F (19.4°C) entering wet bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this  
product. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of  
nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.  
2. Condensing Unit Only Gross Cooling Capacity rated at 45°F (7.2°C) saturated suction temperature and at 95°F (35°C) ambient.  
3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft (7.2 m) of 1.375, 0.500 OD interconnecting tubing. EER and/or SEER are rated at ARI conditions and in  
accordance with DOE test procedures. Integrated Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80°F (26.7°C) ambient, 80°F (26.7°C) entering dry bulb,  
and 67°F (19.4°C) entering wet bulb at ARI rated cfm.  
4. Sound Rating shown is tested in accordance with ARI Standard 270.  
5. System Data based on maximum linear length 80 ft (26.7 m) Maximum lift: suction 60 ft (18.3 m) liquid 60 ft (18.3 m) For greater lengths, refer to refrigerant piping applications  
manual.  
6. Outdoor Fan cfm is rated with standard air-dry coil outdoor.  
7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft (7.6 m) of interconnecting refrigerant lines.  
SS-PRC003-EN  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
Air Handler  
Table GD-3 General Data  
TWE050A  
TWE075A  
TWE100A  
TWE100B  
System Data1  
No. Refrigerant Circuits  
Suction Line in. (mm) OD  
Liquid Line in. (mm) OD  
Indoor Coil Type  
Tube Size in. (mm) OD  
Face Area sq. ft (m2)  
Rows  
1
1.120(28.4)  
0.38(9.7)  
Plate Fin  
0.375(9.5)  
5.00(.47)  
3
1
1
2
1.380(35.0)  
0.50(12.7)  
Plate Fin  
0.375(9.5)  
11.18(1.0)  
3
1.380(35.0)  
0.50(12.7)  
Plate Fin  
0.375(9.5)  
8.07(.75)  
3
1.380(35.0)  
0.50(12.7)  
Plate Fin  
0.375(9.5)  
11.18(1.0)  
3
Fins Per Inch  
12  
12  
12  
12  
Refrigerant Control  
Drain Connection No.  
Drain Connection Size in. (mm)  
Drain ConnectionType  
Indoor FanType  
No. Used  
ExpansionValve  
4
0.75(19.0)  
PVC  
FC Centrifugal  
ExpansionValve ExpansionValve  
ExpansionValve  
4
0.75(19.0)  
PVC  
FC Centrifugal  
4
0.75(19.0)  
PVC  
4
0.75(19.0)  
PVC  
FC Centrifugal  
FC Centrifugal  
1
1
1
1
Diameter in. (mm)  
Width in. (mm)  
12.0(304.8)  
12.0(304.8)  
Belt  
15.0(381)  
15.0(381)  
Belt  
15.0(381)  
15.0(381)  
Belt  
15.0(381)  
15.0(381)  
Belt  
DriveType  
No. Speeds  
1
1
1
1
CFM (m3/h)  
1670(2837)  
1
2500(4247)  
1
3325(5649)  
1
3325(5649)  
1
No. Motors  
Motor HP (kW)  
- Standard/Oversized  
Motor RPM (Standard)  
Motor Frame Size (Standard)  
Filters Type  
Furnished  
No.  
0.75/1.0(.55/.74)  
1.0/1.5(.74/1.11)  
1.5/2.0(1.11/1.49)  
1.5/2.0(1.11/1.49)  
1425  
56  
1425  
56  
1425  
56  
1425  
56  
Throwaway  
Yes  
Throwaway  
Yes  
Throwaway  
Yes  
Throwaway  
Yes  
1/1  
3
4
4
Recommended Size, in. (mm) 16x20x1/20x20x1  
16x25x1  
16x25x1  
16x25x1  
(406.4x508x25.4/  
(406.4x635x25.4) (406.4x635x25.4) (406.4x635x25.4)  
508x508x25.4)  
Notes:  
1. ARI certified with various condensing units per ARI Standard 210/240 or 340/360-93. Refer to Performance Data  
section in this catalog.  
Table GD-4 General Data  
TWE155B  
TWE200B  
System Data  
No. Refrigerant Circuits  
Suction Line in. (mm) OD  
Liquid Line in. (mm) OD  
Indoor Coil Type  
Tube Size in. (mm) OD  
Face Area sq. ft (m2)  
Rows  
2
1.38(35.0)  
0.500(12.7)  
Plate Fin  
0.375(9.5)  
16.33(1.52)  
3
2
1.38(35.0)  
0.500(12.7)  
Plate Fin  
0.375(9.5)  
21.63(2.01)  
3
Fins Per Inch  
12  
12  
Refrigerant Control  
Drain Connection No.  
Drain Connection Size in. (mm)  
Drain ConnectionType  
Indoor FanType  
ExpansionValve  
4
1.000(25.4)  
PVC  
ExpansionValve  
4
1.000(25.4)  
PVC  
FC Centrifugal  
FC Centrifugal  
No. Used  
Diameter in. (mm)  
Width in. (mm)  
2
2
15.0(381)  
15.0(381)  
Belt  
15.0(381)  
15.0(381)  
Belt  
DriveType  
No. Speeds  
1
1
CFM (m3/h)  
5000(8494)  
1
6650(11297)  
1
No. Motors  
Motor HP — Standard/Oversized  
Motor RPM (Standard)  
Motor Frame Size (Standard)  
Filters Type  
Furnished  
No.  
2.0/3.0(1.49/2.24)  
1425  
145T  
Throwaway  
3.0/5.0(2.24/3.72)  
1425  
184T  
Throwaway  
Yes  
8
Yes  
4/4  
Recommended Size, in. (mm)  
15x20x2  
(381x508x50.8)  
16x20x2/16x25x2  
(406.4x508x50.8/  
406.4x635x50.8)  
Notes:  
1. ARI certified with various condensing units per ARI Standard 210/240 or 340/360-93. Refer to Performance Data  
section in this catalog.  
12  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-1 Gross Cooling Capacities (MBh) TTA075A Condensing Unit withTWE075AAir Handler  
(I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
75.7  
76.2  
77.8  
81.8  
77.3  
77.9  
80.4  
84.6  
78.6  
79.4  
82.7  
86.9  
79.7  
80.8  
84.6  
89.0  
59.6 83.5 50.1 91.7 34.0  
69.5 83.7 57.4 92.0 44.6  
77.8 84.1 67.3 92.4 54.9  
81.8 84.6 77.2 92.5 64.8  
62.3 85.1 49.2 93.1 34.5  
73.2 85.3 59.9 93.6 46.1  
80.4 85.7 70.6 94.0 57.4  
84.6 86.4 81.6 94.2 67.9  
64.9 86.3 50.8 94.2 35.2  
76.7 86.6 62.2 94.8 47.5  
82.7 87.0 73.9 95.3 59.7  
86.9 88.0 85.8 95.5 70.9  
67.3 87.4 52.3 95.2 35.7  
80.1 87.7 64.5 95.9 48.8  
84.6 88.2 77.0 96.1 61.3  
89.0 89.1 89.1 96.7 73.7  
73.1  
73.6  
75.6  
79.4  
74.5  
75.2  
78.0  
82.0  
75.7  
76.6  
80.1  
84.3  
76.7  
77.7  
82.0  
86.3  
58.2 80.5 48.8 88.2 32.7 69.9 56.6 76.9 47.4 84.1 31.3 66.3 54.8 72.9 45.8 79.5 29.8  
68.1 80.6 56.0 88.6 43.3 70.5 66.6 77.1 54.4 84.7 41.8 67.0 64.8 73.2 52.6 80.3 40.3  
75.6 81.1 65.9 89.0 53.6 72.9 72.9 77.6 64.2 85.1 52.2 69.9 69.9 73.7 62.5 80.8 50.6  
79.4 81.6 75.8 89.2 63.4 76.7 76.7 78.3 74.3 85.3 61.8 73.5 73.5 74.5 72.5 81.1 60.1  
60.9 81.9 47.8 89.4 33.3 71.2 59.2 78.2 46.3 85.2 31.8 67.5 57.4 74.1 44.6 80.6 30.3  
71.8 82.1 58.5 90.0 44.8 72.0 70.2 78.5 56.8 85.9 43.3 68.5 68.4 74.4 55.0 81.5 41.7  
78.0 82.6 69.2 90.4 56.0 75.2 75.2 78.9 67.6 86.2 54.1 72.0 72.0 74.9 65.7 81.8 52.4  
82.0 83.4 80.2 90.7 66.5 79.1 79.1 79.9 78.6 86.7 64.9 75.8 75.8 75.9 75.9 82.4 63.1  
63.4 83.0 49.4 90.4 33.9 72.3 61.7 79.3 47.9 86.1 32.4 68.5 59.8 74.7 45.7 81.4 30.8  
75.3 83.3 60.8 91.1 46.2 73.1 73.1 79.6 59.1 87.0 44.7 69.9 69.9 75.5 57.2 82.5 43.1  
80.1 83.8 72.4 91.4 57.8 77.2 77.2 80.1 70.7 87.3 56.2 73.8 73.8 76.1 68.9 82.9 54.4  
84.3 85.0 84.4 91.9 69.4 81.2 81.2 81.3 81.3 87.9 67.8 77.8 77.8 77.9 77.9 83.4 66.0  
65.9 84.0 51.0 91.3 34.3 73.2 64.1 79.8 48.9 86.9 32.8 69.4 62.2 75.6 47.0 82.1 31.2  
77.7 84.4 63.0 92.1 47.5 74.8 74.8 80.6 61.3 87.9 46.0 71.4 71.4 76.4 59.4 83.3 44.4  
82.0 84.9 75.5 92.4 59.8 78.9 78.9 81.2 73.8 88.3 58.2 75.5 75.5 77.1 72.0 83.8 56.3  
86.3 86.4 86.4 93.0 72.3 83.1 83.1 83.2 83.2 88.8 70.6 79.6 79.6 79.6 79.6 84.3 68.8  
2250  
2500  
2750  
3000  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-1 Gross Cooling Capacities (kW) TTA075A Condensing Unit withTWE075AAir Handler  
(SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
Airflow  
(°C)  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
22.2  
22.3  
22.8  
24.0  
22.6  
22.8  
23.5  
24.8  
23.0  
23.2  
24.2  
25.5  
23.3  
23.7  
24.8  
26.1  
17.5 24.5 14.7 26.9 9.9  
20.4 24.5 16.8 26.9 13.1  
22.8 24.6 19.7 27.1 16.1  
24.0 24.8 22.6 27.1 19.0  
18.2 24.9 14.4 27.3 10.1  
21.4 25.0 17.5 27.4 13.5  
23.5 25.1 20.7 27.5 16.8  
24.8 25.3 23.9 27.6 19.9  
19.0 25.3 14.9 27.6 10.3  
22.5 25.4 18.2 27.8 13.9  
24.2 25.5 21.6 27.9 17.5  
25.5 25.8 25.1 28.0 20.8  
19.7 25.6 15.3 27.9 10.4  
23.5 25.7 18.9 28.1 14.3  
24.8 25.8 22.5 28.1 18.0  
26.1 26.1 26.1 28.3 21.6  
21.4  
21.5  
22.1  
23.3  
21.8  
22.0  
22.8  
24.0  
22.2  
22.4  
23.5  
24.7  
22.4  
22.8  
24.0  
25.3  
17.0 23.6 14.3 25.8 9.6 20.5 16.6 22.5 13.9 24.6 9.2 19.4 16.0 21.4 13.4 23.3 8.7  
20.0 23.6 16.4 25.9 12.7 20.6 19.5 22.6 15.9 24.8 12.3 19.6 19.0 21.4 15.4 23.5 11.8  
22.1 23.7 19.3 26.1 15.7 21.3 21.3 22.7 18.8 24.9 15.3 20.5 20.5 21.6 18.3 23.7 14.8  
23.3 23.9 22.2 26.1 18.6 22.5 22.5 22.9 21.7 25.0 18.1 21.5 21.5 21.8 21.2 23.7 17.6  
17.8 24.0 14.0 26.2 9.7 20.8 17.3 22.9 13.6 24.9 9.3 19.8 16.8 21.7 13.1 23.6 8.9  
21.0 24.0 17.1 26.3 13.1 21.1 20.6 23.0 16.6 25.2 12.7 20.1 20.0 21.8 16.1 23.9 12.2  
22.8 24.2 20.3 26.5 16.4 22.0 22.0 23.1 19.8 25.2 15.9 21.1 21.1 21.9 19.3 24.0 15.3  
24.0 24.4 23.5 26.5 19.5 23.2 23.2 23.4 23.0 25.4 19.0 22.2 22.2 22.2 22.2 24.1 18.5  
18.6 24.3 14.5 26.5 9.9 21.2 18.1 23.2 14.0 25.2 9.5 20.0 17.5 21.9 13.4 23.8 9.0  
22.1 24.4 17.8 26.7 13.5 21.4 21.4 23.3 17.3 25.5 13.1 20.5 20.5 22.1 16.8 24.2 12.6  
23.5 24.5 21.2 26.8 16.9 22.6 22.6 23.5 20.7 25.6 16.5 21.6 21.6 22.3 20.2 24.3 15.9  
24.7 24.9 24.7 26.9 20.3 23.8 23.8 23.8 23.8 25.7 19.8 22.8 22.8 22.8 22.8 24.4 19.3  
19.3 24.6 14.9 26.7 10.0 21.4 18.8 23.4 14.3 25.4 9.6 20.3 18.2 22.1 13.8 24.0 9.1  
22.8 24.7 18.4 27.0 13.9 21.9 21.9 23.6 17.9 25.7 13.5 20.9 20.9 22.4 17.4 24.4 13.0  
24.0 24.9 22.1 27.1 17.5 23.1 23.1 23.8 21.6 25.8 17.0 22.1 22.1 22.6 21.1 24.5 16.5  
25.3 25.3 25.3 27.2 21.2 24.3 24.3 24.4 24.4 26.0 20.7 23.3 23.3 23.3 23.3 24.7 20.2  
3823  
4248  
4673  
5098  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
SS-PRC003-EN  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-2 Gross Cooling Capacities (MBh) TTA075A Condensing Unit withTWE100AAir Handler  
(I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
79.9  
80.7  
83.7  
88.0  
81.5  
82.8  
86.7  
91.2  
82.9  
84.6  
89.2  
93.9  
84.2  
86.6  
91.4  
96.2  
65.5 87.9 54.1 95.9 35.7  
77.2 88.1 62.8 96.6 48.0  
83.7 88.5 74.4 97.0 60.0  
88.0 89.5 86.2 97.2 71.4  
69.1 89.5 53.5 97.3 36.4  
82.3 89.8 66.1 98.2 49.9  
86.7 90.3 79.0 98.6 63.3  
91.2 91.2 91.2 98.8 75.6  
72.6 90.8 55.7 98.5 37.0  
84.6 91.2 69.3 99.4 51.8  
89.2 91.9 83.4 99.7 65.7  
93.9 93.9 93.9 100.2 79.7  
75.9 91.6 57.1 99.4 37.6  
86.6 92.3 72.3 100.5 53.5  
91.4 93.2 87.7 100.9 68.4  
96.2 96.2 96.2 101.4 83.6  
76.9  
77.9  
81.1  
85.3  
78.4  
79.6  
83.9  
88.3  
79.8  
81.8  
86.3  
90.9  
80.9  
83.7  
88.4  
93.0  
64.0 84.5 52.7 92.0 34.4 73.5 62.2 80.7 51.2 87.7 32.9 69.6 60.3 76.4 49.5 82.9 31.3  
75.8 84.8 61.3 92.8 46.6 74.6 74.1 81.0 59.6 88.6 45.1 70.8 70.8 76.8 57.7 84.0 43.5  
81.1 85.2 72.9 93.3 58.7 78.1 78.1 81.5 71.2 89.2 57.2 74.8 74.8 77.3 69.4 84.3 54.9  
85.3 86.3 84.8 93.5 69.9 82.2 82.2 82.3 82.3 89.4 68.3 78.8 78.8 78.9 78.9 84.9 66.5  
67.6 86.0 52.1 93.3 35.1 74.9 65.8 82.0 50.5 88.8 33.5 70.9 63.8 77.2 48.1 83.9 31.8  
79.6 86.3 64.6 94.3 48.5 76.5 76.5 82.4 62.8 90.0 47.0 73.1 73.1 78.1 60.9 85.3 45.4  
83.9 86.9 77.5 94.5 61.3 80.8 80.8 83.1 75.8 90.3 59.6 77.2 77.2 78.9 73.9 85.7 57.8  
88.3 88.4 88.4 95.1 74.1 85.1 85.1 85.2 85.2 90.8 72.5 81.4 81.4 81.5 81.5 86.2 70.7  
71.0 86.9 53.7 94.3 35.6 76.1 69.2 82.8 51.9 89.7 34.1 72.1 67.2 78.3 49.9 84.6 32.4  
81.8 87.6 67.7 95.5 50.4 78.6 78.6 83.6 65.9 91.1 48.9 75.0 75.0 79.1 63.9 86.3 47.2  
86.3 88.4 81.9 95.8 64.1 83.0 83.0 84.5 80.1 91.5 62.4 79.3 79.3 80.2 78.2 86.8 60.5  
90.9 90.9 90.9 96.3 78.2 87.4 87.4 87.5 87.5 92.1 76.5 83.7 83.7 83.8 83.8 87.4 74.7  
74.3 87.9 55.5 95.1 36.2 77.2 72.5 83.7 53.6 90.4 34.6 73.1 70.4 79.1 51.6 85.1 32.9  
83.7 88.7 70.7 96.5 52.1 80.4 80.4 84.5 68.9 92.0 50.6 76.7 76.7 80.0 66.9 87.1 49.0  
88.4 89.7 86.1 96.9 66.8 84.9 84.9 85.8 84.4 92.5 65.1 81.1 81.1 81.2 81.2 87.7 63.1  
93.0 93.1 93.1 97.5 82.1 89.5 89.5 89.6 89.6 93.1 80.4 85.6 85.6 85.7 85.7 88.5 78.6  
2550  
2875  
3200  
3525  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-2 Gross Cooling Capacities (kW) TTA075A Condensing Unit withTWE100A Air Handler  
(SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
Airflow  
(°C)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
23.4  
23.6  
24.5  
25.8  
23.9  
24.2  
25.4  
26.7  
24.3  
24.8  
26.1  
27.5  
24.6  
25.4  
26.8  
28.2  
19.2 25.7 15.8 28.1 10.5  
22.6 25.8 18.4 28.3 14.0  
24.5 25.9 21.8 28.4 17.6  
25.8 26.2 25.2 28.4 20.9  
20.2 26.2 15.7 28.5 10.7  
24.1 26.3 19.4 28.7 14.6  
25.4 26.4 23.1 28.9 18.5  
26.7 26.7 26.7 28.9 22.1  
21.2 26.6 16.3 28.8 10.8  
24.8 26.7 20.3 29.1 15.2  
26.1 26.9 24.4 29.2 19.2  
27.5 27.5 27.5 29.3 23.3  
22.2 26.8 16.7 29.1 11.0  
25.4 27.0 21.2 29.4 15.7  
26.8 27.3 25.7 29.5 20.0  
28.2 28.2 28.2 29.7 24.5  
22.5  
22.8  
23.8  
25.0  
23.0  
23.3  
24.6  
25.9  
23.4  
24.0  
25.3  
26.6  
23.7  
24.5  
25.9  
27.2  
18.7 24.7 15.4 26.9 10.1 21.5 18.2 23.6 15.0 25.7 9.6 20.4 17.7 22.4 14.5 24.3 9.2  
22.2 24.8 18.0 27.2 13.6 21.8 21.7 23.7 17.5 26.0 13.2 20.7 20.7 22.5 16.9 24.6 12.7  
23.8 25.0 21.3 27.3 17.2 22.9 22.9 23.9 20.9 26.1 16.7 21.9 21.9 22.6 20.3 24.7 16.1  
25.0 25.3 24.8 27.4 20.5 24.1 24.1 24.1 24.1 26.2 20.0 23.1 23.1 23.1 23.1 24.9 19.5  
19.8 25.2 15.3 27.3 10.3 21.9 19.3 24.0 14.8 26.0 9.8 20.8 18.7 22.6 14.1 24.6 9.3  
23.3 25.3 18.9 27.6 14.2 22.4 22.4 24.1 18.4 26.3 13.8 21.4 21.4 22.9 17.8 25.0 13.3  
24.6 25.5 22.7 27.7 18.0 23.7 23.7 24.3 22.2 26.4 17.5 22.6 22.6 23.1 21.6 25.1 16.9  
25.9 25.9 25.9 27.8 21.7 24.9 24.9 24.9 24.9 26.6 21.2 23.8 23.8 23.9 23.9 25.3 20.7  
20.8 25.4 15.7 27.6 10.4 22.3 20.3 24.2 15.2 26.3 10.0 21.1 19.7 22.9 14.6 24.8 9.5  
24.0 25.7 19.8 28.0 14.8 23.0 23.0 24.5 19.3 26.7 14.3 22.0 22.0 23.2 18.7 25.3 13.8  
25.3 25.9 24.0 28.1 18.8 24.3 24.3 24.7 23.5 26.8 18.3 23.2 23.2 23.5 22.9 25.4 17.7  
26.6 26.6 26.6 28.2 22.9 25.6 25.6 25.6 25.6 27.0 22.4 24.5 24.5 24.5 24.5 25.6 21.9  
21.8 25.7 16.3 27.9 10.6 22.6 21.2 24.5 15.7 26.5 10.1 21.4 20.6 23.2 15.1 24.9 9.6  
24.5 26.0 20.7 28.2 15.3 23.5 23.5 24.8 20.2 26.9 14.8 22.4 22.4 23.4 19.6 25.5 14.3  
25.9 26.3 25.2 28.4 19.6 24.9 24.9 25.1 24.7 27.1 19.0 23.7 23.7 23.8 23.8 25.7 18.5  
27.2 27.3 27.3 28.5 24.0 26.2 26.2 26.2 26.2 27.3 23.5 25.1 25.1 25.1 25.1 25.9 23.0  
4331  
4885  
5436  
5990  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
14  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-3 Gross Cooling Capacities (MBh) TTA085A Condensing Unit withTWE075AAir Handler  
(I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
83.0  
83.2  
83.7  
86.2  
84.8  
85.2  
86.1  
89.5  
86.6  
87.0  
88.3  
92.4  
88.1  
88.5  
90.2  
95.0  
61.8 92.0 53.4 102.2 37.6  
70.5 92.3 59.7 102.2 48.0  
79.6 92.4 68.8 102.5 57.4  
86.2 92.8 77.8 102.8 66.7  
64.2 94.2 52.1 104.4 38.4  
73.9 94.5 62.3 104.5 49.4  
84.0 94.6 72.0 104.8 59.6  
89.5 95.0 81.7 105.1 69.8  
66.6 96.0 53.6 106.2 39.2  
77.1 96.3 64.6 106.3 50.8  
88.1 96.5 75.0 106.7 61.8  
92.4 96.9 85.5 107.0 72.8  
68.9 97.5 55.1 107.7 39.9  
80.2 97.9 66.9 107.9 52.1  
90.2 98.2 77.8 108.3 63.8  
95.0 98.6 89.1 108.4 75.1  
80.0  
80.4  
81.1  
84.0  
81.9  
82.3  
83.4  
87.1  
83.5  
84.0  
85.3  
89.9  
85.0  
85.5  
87.7  
92.3  
60.1 88.9 52.1 98.7 36.4 76.9 58.5 85.6 50.7 95.0 35.1 73.7 56.8 82.1 49.3 91.2 33.8  
69.0 89.2 58.3 98.8 46.6 77.4 67.4 86.0 56.8 95.2 45.1 74.2 65.7 82.5 55.3 91.3 43.6  
78.2 89.4 67.3 99.1 56.0 78.2 76.6 86.1 65.7 95.5 54.5 75.3 75.0 82.7 64.1 91.8 53.0  
84.0 89.8 76.3 99.4 65.3 81.5 81.5 86.5 74.7 95.8 63.9 78.9 78.9 83.1 73.1 92.1 62.4  
62.6 90.9 50.6 100.8 37.1 78.8 61.0 87.5 49.1 96.9 35.8 75.4 59.2 83.9 47.5 92.9 34.4  
72.4 91.3 60.8 100.9 48.0 79.2 70.7 87.9 59.3 97.1 46.5 75.9 69.0 84.3 57.7 93.2 45.0  
82.5 91.5 70.4 101.2 58.2 80.2 80.2 88.1 68.8 97.5 56.8 77.6 77.6 84.6 67.2 93.6 55.3  
87.1 91.9 80.2 101.6 68.4 84.5 84.5 88.5 78.6 97.9 67.0 81.8 81.8 85.0 76.9 93.8 65.0  
65.0 92.6 52.2 102.4 37.9 80.3 63.3 89.0 50.6 98.4 36.5 76.9 61.6 85.3 49.0 94.2 35.1  
75.5 93.0 63.2 102.6 49.3 80.8 73.9 89.2 61.3 98.7 47.8 77.5 72.1 85.6 59.6 94.7 46.3  
85.3 93.2 73.4 103.0 60.4 82.7 82.7 89.8 71.8 99.2 58.9 79.9 79.9 86.1 70.1 95.2 57.4  
89.9 93.6 83.9 103.1 71.0 87.2 87.2 90.2 82.3 99.3 69.4 84.3 84.3 86.7 80.7 95.4 67.7  
67.3 94.0 53.6 103.8 38.6 81.6 65.6 90.4 52.1 99.7 37.2 78.1 63.8 86.6 50.5 95.4 35.7  
78.6 94.2 65.0 104.1 50.6 82.2 76.9 90.6 63.4 100.1 49.1 78.9 75.2 86.9 61.6 96.0 47.6  
87.7 94.8 76.2 104.5 62.4 84.9 84.9 91.2 74.6 100.6 60.9 82.1 82.1 87.5 72.8 96.5 59.4  
92.3 95.3 87.6 104.7 73.6 89.5 89.5 91.8 85.9 100.8 72.0 86.6 86.6 88.3 84.3 96.8 70.3  
2250  
2500  
2750  
3000  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-3 Gross Cooling Capacities (kW) TTA085A Condensing Unit withTWE075AAir Handler  
(SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
Airflow  
(°C)  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
24.3  
24.3  
24.5  
25.3  
24.8  
25.0  
25.2  
26.2  
25.3  
25.5  
25.8  
27.1  
25.8  
25.9  
26.4  
27.8  
18.1 26.9 15.6 29.9 11.0  
20.6 27.0 17.5 29.9 14.0  
23.3 27.1 20.1 30.0 16.8  
25.3 27.2 22.8 30.1 19.5  
18.8 27.6 15.2 30.6 11.3  
21.6 27.7 18.2 30.6 14.5  
24.6 27.7 21.1 30.7 17.5  
26.2 27.8 23.9 30.8 20.4  
19.5 28.1 15.7 31.1 11.5  
22.6 28.2 18.9 31.1 14.9  
25.8 28.3 22.0 31.2 18.1  
27.1 28.4 25.0 31.3 21.3  
20.2 28.6 16.1 31.5 11.7  
23.5 28.7 19.6 31.6 15.2  
26.4 28.7 22.8 31.7 18.7  
27.8 28.9 26.1 31.7 22.0  
23.4  
23.5  
23.7  
24.6  
24.0  
24.1  
24.4  
25.5  
24.5  
24.6  
25.0  
26.3  
24.9  
25.0  
25.7  
27.0  
17.6 26.0 15.3 28.9 10.7 22.5 17.1 25.1 14.9 27.8 10.3 21.6 16.6 24.0 14.4 26.7 9.9  
20.2 26.1 17.1 28.9 13.6 22.7 19.7 25.2 16.6 27.9 13.2 21.7 19.2 24.2 16.2 26.7 12.8  
22.9 26.2 19.7 29.0 16.4 22.9 22.4 25.2 19.2 28.0 16.0 22.0 22.0 24.2 18.8 26.9 15.5  
24.6 26.3 22.3 29.1 19.1 23.9 23.9 25.3 21.9 28.1 18.7 23.1 23.1 24.3 21.4 27.0 18.3  
18.3 26.6 14.8 29.5 10.9 23.1 17.9 25.6 14.4 28.4 10.5 22.1 17.3 24.6 13.9 27.2 10.1  
21.2 26.7 17.8 29.5 14.1 23.2 20.7 25.7 17.4 28.4 13.6 22.2 20.2 24.7 16.9 27.3 13.2  
24.1 26.8 20.6 29.6 17.0 23.5 23.5 25.8 20.2 28.6 16.6 22.7 22.7 24.8 19.7 27.4 16.2  
25.5 26.9 23.5 29.7 20.0 24.7 24.7 25.9 23.0 28.7 19.6 24.0 24.0 24.9 22.5 27.5 19.0  
19.0 27.1 15.3 30.0 11.1 23.5 18.5 26.1 14.8 28.8 10.7 22.5 18.0 25.0 14.4 27.6 10.3  
22.1 27.2 18.5 30.0 14.4 23.7 21.6 26.1 17.9 28.9 14.0 22.7 21.1 25.1 17.5 27.7 13.6  
25.0 27.3 21.5 30.2 17.7 24.2 24.2 26.3 21.0 29.0 17.2 23.4 23.4 25.2 20.5 27.9 16.8  
26.3 27.4 24.6 30.2 20.8 25.5 25.5 26.4 24.1 29.1 20.3 24.7 24.7 25.4 23.6 27.9 19.8  
19.7 27.5 15.7 30.4 11.3 23.9 19.2 26.5 15.2 29.2 10.9 22.9 18.7 25.4 14.8 27.9 10.5  
23.0 27.6 19.0 30.5 14.8 24.1 22.5 26.5 18.6 29.3 14.4 23.1 22.0 25.4 18.0 28.1 13.9  
25.7 27.8 22.3 30.6 18.3 24.9 24.9 26.7 21.8 29.5 17.8 24.0 24.0 25.6 21.3 28.3 17.4  
27.0 27.9 25.6 30.7 21.5 26.2 26.2 26.9 25.2 29.5 21.1 25.4 25.4 25.8 24.7 28.3 20.6  
3823  
4248  
4673  
5098  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
15  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-4 Gross Cooling Capacities (MBh) TTA085A Condensing Unit withTWE100AAir Handler  
(I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
87.9  
88.3  
89.3  
93.2  
90.0  
90.5  
92.0  
96.8  
91.8  
92.4  
95.0  
67.0 97.4 57.4 107.7 39.8  
77.4 97.8 65.0 107.9 51.3  
88.1 98.0 75.3 108.3 62.2  
93.2 98.3 85.7 108.7 73.0  
70.2 99.6 56.2 109.9 40.6  
81.6 100.1 68.1 110.2 53.1  
92.0 100.3 79.2 110.7 65.0  
96.8 100.7 90.7 110.8 76.5  
73.2 101.5 58.1 111.6 41.4  
85.7 101.7 70.6 112.1 54.7  
95.0 102.2 82.9 112.7 67.7  
84.8  
85.2  
86.1  
90.6  
86.8  
87.3  
89.4  
94.1  
88.5  
89.2  
92.2  
97.2  
89.9  
90.8  
94.8  
99.9  
65.4 93.9 56.0 103.9 38.3 81.5 63.7 90.3 54.5 99.8 36.8 78.0 61.9 86.5 53.0 95.4 35.5  
75.8 94.4 63.4 104.1 49.8 81.9 74.1 90.8 61.9 100.2 48.3 78.5 72.3 86.7 59.9 96.0 46.7  
86.1 94.6 73.7 104.6 60.7 83.4 83.4 91.0 72.0 100.7 59.2 80.6 80.6 87.3 70.2 96.6 57.6  
90.6 95.0 84.1 104.9 71.5 87.9 87.9 91.4 82.4 100.8 69.6 85.0 85.0 87.8 80.7 96.8 67.9  
68.5 96.0 54.6 105.8 39.2 83.4 66.8 92.3 53.0 101.5 37.7 79.8 64.9 88.3 51.4 97.0 36.1  
80.0 96.5 66.5 106.3 51.6 83.9 78.2 92.5 64.5 102.2 50.0 80.5 76.4 88.6 62.7 97.9 48.4  
89.4 96.7 77.5 106.8 63.5 86.6 86.6 93.0 75.8 102.7 62.0 83.6 83.6 89.2 74.1 98.5 60.4  
94.1 97.2 89.0 106.9 74.9 91.2 91.2 93.6 87.4 102.9 73.2 88.2 88.2 89.9 85.6 98.7 71.5  
71.5 97.7 56.5 107.3 40.0 85.0 69.7 93.9 54.9 102.9 38.5 81.3 67.8 89.8 53.2 98.3 36.9  
84.0 98.0 68.9 108.0 53.2 85.7 82.2 94.2 67.1 103.8 51.6 82.2 80.4 90.2 65.3 99.4 50.0  
92.2 98.6 81.3 108.6 66.2 89.3 89.3 94.7 79.5 104.4 64.6 86.2 86.2 90.8 77.7 99.7 62.5  
97.2 99.3 93.8 108.9 78.3 94.1 94.1 95.6 92.1 104.7 76.6 91.0 91.0 91.9 90.4 100.4 74.9  
74.3 99.2 58.3 108.6 40.7 86.3 72.5 95.2 56.7 104.1 39.1 82.5 70.6 91.1 55.0 99.4 37.4  
87.9 99.5 71.4 109.5 54.8 87.4 86.1 95.6 69.7 105.2 53.2 83.6 83.6 91.5 67.8 100.7 51.6  
94.8 100.1 84.8 110.2 68.7 91.7 91.7 96.2 83.0 105.5 66.6 88.5 88.5 92.1 81.2 101.1 64.8  
99.9 101.1 98.4 110.5 81.6 96.7 96.7 97.5 96.7 106.2 79.9 93.4 93.4 93.5 93.5 101.8 78.1  
2500  
2800  
3100  
3400  
100.0 100.0 102.8 95.4 112.9 80.0  
93.4  
94.1  
97.7  
76.1 103.0 59.9 113.0 42.2  
89.6 103.3 73.2 113.7 56.3  
97.7 103.9 86.5 114.3 70.3  
102.9 102.9 104.7 100.1 114.6 83.3  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-4 Gross Cooling Capacities (kW) TTA085A Condensing Unit withTWE100A Air Handler  
(SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
Airflow  
(°C)  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
25.7  
25.9  
26.1  
27.3  
26.4  
26.5  
26.9  
28.4  
26.9  
27.1  
27.8  
29.3  
27.3  
27.6  
28.6  
30.1  
19.6 28.5 16.8 31.5 11.6  
22.7 28.6 19.0 31.6 15.0  
25.8 28.7 22.0 31.7 18.2  
27.3 28.8 25.1 31.8 21.4  
20.6 29.2 16.4 32.2 11.9  
23.9 29.3 19.9 32.3 15.5  
26.9 29.4 23.2 32.4 19.0  
28.4 29.5 26.5 32.4 22.4  
21.4 29.7 17.0 32.7 12.1  
25.1 29.8 20.7 32.8 16.0  
27.8 29.9 24.3 33.0 19.8  
29.3 30.1 27.9 33.0 23.4  
22.3 30.2 17.5 33.1 12.4  
26.2 30.2 21.4 33.3 16.5  
28.6 30.4 25.3 33.5 20.6  
30.1 30.7 29.3 33.6 24.4  
24.8  
24.9  
25.2  
26.5  
25.4  
25.6  
26.2  
27.6  
25.9  
26.1  
27.0  
28.4  
26.3  
26.6  
27.8  
29.2  
19.1 27.5 16.4 30.4 11.2 23.9 18.6 26.4 16.0 29.2 10.8 22.8 18.1 25.3 15.5 27.9 10.4  
22.2 27.6 18.6 30.5 14.6 24.0 21.7 26.6 18.1 29.3 14.1 23.0 21.2 25.4 17.5 28.1 13.7  
25.2 27.7 21.6 30.6 17.8 24.4 24.4 26.6 21.1 29.5 17.3 23.6 23.6 25.6 20.6 28.3 16.9  
26.5 27.8 24.6 30.7 20.9 25.7 25.7 26.8 24.1 29.5 20.4 24.9 24.9 25.7 23.6 28.3 19.9  
20.1 28.1 16.0 31.0 11.5 24.4 19.5 27.0 15.5 29.7 11.0 23.4 19.0 25.9 15.0 28.4 10.6  
23.4 28.3 19.5 31.1 15.1 24.6 22.9 27.1 18.9 29.9 14.6 23.6 22.4 25.9 18.3 28.7 14.2  
26.2 28.3 22.7 31.3 18.6 25.3 25.3 27.2 22.2 30.1 18.1 24.5 24.5 26.1 21.7 28.8 17.7  
27.6 28.5 26.1 31.3 21.9 26.7 26.7 27.4 25.6 30.1 21.4 25.8 25.8 26.3 25.1 28.9 20.9  
20.9 28.6 16.6 31.4 11.7 24.9 20.4 27.5 16.1 30.1 11.3 23.8 19.9 26.3 15.6 28.8 10.8  
24.6 28.7 20.2 31.6 15.6 25.1 24.1 27.6 19.7 30.4 15.1 24.1 23.6 26.4 19.1 29.1 14.7  
27.0 28.9 23.8 31.8 19.4 26.1 26.1 27.7 23.3 30.6 18.9 25.2 25.2 26.6 22.8 29.2 18.3  
28.4 29.1 27.5 31.9 22.9 27.6 27.6 28.0 27.0 30.7 22.4 26.6 26.6 26.9 26.5 29.4 21.9  
21.8 29.0 17.1 31.8 11.9 25.3 21.2 27.9 16.6 30.5 11.4 24.2 20.7 26.7 16.1 29.1 11.0  
25.7 29.1 20.9 32.1 16.0 25.6 25.2 28.0 20.4 30.8 15.6 24.5 24.5 26.8 19.9 29.5 15.1  
27.8 29.3 24.8 32.3 20.1 26.9 26.9 28.2 24.3 30.9 19.5 25.9 25.9 27.0 23.8 29.6 19.0  
29.2 29.6 28.8 32.3 23.9 28.3 28.3 28.5 28.3 31.1 23.4 27.4 27.4 27.4 27.4 29.8 22.9  
4248  
4756  
5267  
5778  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
16  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-5 Gross Cooling Capacities (MBh) TTA100A Condensing Unit withTWE100A Air Handler  
(I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
102.0 77.6 112.8 67.2 124.5 46.0  
102.4 89.6 113.2 75.1 124.6 59.2  
98.2  
98.7  
75.7 108.7 65.5 119.9 44.4 94.3 73.6 104.4 63.8 115.1 42.7 90.2 71.5 99.9 62.0 110.1 41.0  
87.6 109.2 73.2 120.1 57.4 94.8 85.5 104.9 71.4 115.4 55.6 90.8 83.4 100.5 69.4 110.5 53.7  
3025  
3350  
3675  
4000  
103.6 101.9 113.4 87.0 125.0 71.7 100.2 100.1 109.3 85.1 120.5 69.9 96.5 96.5 105.1 83.1 115.9 68.1 93.1 93.1 100.7 81.0 111.1 66.3  
107.8 107.8 113.8 98.9 125.4 84.1 104.7 104.7 109.8 97.0 120.9 82.4 101.5 101.5 105.6 95.0 116.3 80.6 98.1 98.1 101.3 93.0 111.3 78.2  
104.1 80.8 115.1 64.6 126.7 46.8 100.3 78.8 110.8 62.8 121.9 45.2 96.2 76.7 106.3 60.9 116.9 43.5 92.0 74.5 101.7 58.9 111.7 41.7  
104.6 93.8 115.5 78.2 126.9 60.9 100.8 91.8 111.3 76.3 122.2 59.1 96.9 89.7 106.5 74.0 117.4 57.3 92.8 87.6 102.0 71.9 112.4 55.4  
106.1 106.1 115.7 90.9 127.3 74.5 102.9 102.9 111.5 89.0 122.7 72.7 99.6 99.6 107.1 86.9 117.9 70.9 96.1 96.1 102.6 84.8 113.0 69.0  
111.5 111.5 116.2 103.9 127.7 88.0 108.3 108.3 112.1 102.0 122.8 85.8 104.9 104.9 107.8 100.0 118.1 83.8 101.3 101.3 103.4 98.0 113.2 81.8  
106.0 83.8 116.9 66.6 128.5 47.7 102.0 81.8 112.5 64.7 123.5 46.0 97.8 79.7 107.9 62.8 118.4 44.3 93.5 77.5 103.2 60.8 113.0 42.4  
106.6 97.8 117.4 81.1 128.8 62.6 102.7 95.8 112.7 78.8 124.0 60.8 98.7 93.8 108.2 76.7 119.0 58.9 94.5 91.6 103.6 74.6 113.9 57.0  
109.1 109.1 117.6 94.7 129.3 77.2 105.8 105.8 113.3 92.7 124.5 75.4 102.4 102.4 108.8 90.6 119.6 73.5 98.7 98.7 104.2 88.5 114.5 71.6  
114.7 114.7 118.3 108.7 129.4 91.1 111.3 111.3 114.1 106.8 124.7 89.2 107.8 107.8 109.8 104.8 119.9 87.2 104.0 104.0 105.4 102.7 114.8 85.2  
107.6 86.7 118.5 68.4 130.0 48.6 103.5 84.6 114.0 66.5 124.9 46.7 99.3 82.5 109.3 64.5 119.6 44.8 94.8 80.2 104.5 62.6 114.2 42.9  
108.4 101.7 118.7 83.4 130.4 64.1 104.5 99.7 114.3 81.4 125.5 62.3 100.4 97.6 109.7 79.3 120.4 60.5 96.2 95.5 104.9 77.1 115.2 58.6  
111.8 111.8 119.3 98.2 130.9 79.7 108.4 108.4 114.9 96.2 126.1 77.9 104.8 104.8 110.3 94.1 121.1 76.1 101.1 101.1 105.6 92.0 115.5 73.6  
117.6 117.6 120.2 113.3 131.2 94.5 114.1 114.1 116.0 111.4 126.4 92.5 110.4 110.4 111.6 109.4 121.4 90.5 106.5 106.5 106.6 106.6 116.3 88.4  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-5 Gross Cooling Capacities (kW) TTA100A Condensing Unit withTWE100AAir Handler  
(SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
Airflow  
(°C)  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
29.9  
30.0  
30.3  
31.6  
30.5  
30.6  
31.1  
32.6  
31.0  
31.2  
31.9  
33.6  
31.5  
31.7  
32.7  
34.4  
22.7 33.0 19.7 36.4 13.5  
26.2 33.2 22.0 36.5 17.3  
29.8 33.2 25.5 36.6 21.0  
31.6 33.3 29.0 36.7 24.6  
23.7 33.7 18.9 37.1 13.7  
27.5 33.8 22.9 37.2 17.8  
31.1 33.9 26.6 37.3 21.8  
32.6 34.0 30.4 37.4 25.8  
24.5 34.2 19.5 37.6 14.0  
28.6 34.4 23.7 37.7 18.3  
31.9 34.4 27.7 37.9 22.6  
33.6 34.6 31.8 37.9 26.7  
25.4 34.7 20.0 38.1 14.2  
29.8 34.8 24.4 38.2 18.8  
32.7 34.9 28.8 38.3 23.3  
34.4 35.2 33.2 38.4 27.7  
28.8  
28.9  
29.3  
30.7  
29.4  
29.5  
30.1  
31.7  
29.9  
30.1  
31.0  
32.6  
30.3  
30.6  
31.7  
33.4  
22.2 31.8 19.2 35.1 13.0 27.6 21.6 30.6 18.7 33.7 12.5 26.4 20.9 29.2 18.1 32.2 12.0  
25.6 32.0 21.4 35.2 16.8 27.8 25.0 30.7 20.9 33.8 16.3 26.6 24.4 29.4 20.3 32.4 15.7  
29.3 32.0 24.9 35.3 20.5 28.2 28.2 30.8 24.3 33.9 19.9 27.3 27.3 29.5 23.7 32.5 19.4  
30.7 32.1 28.4 35.4 24.1 29.7 29.7 30.9 27.8 34.1 23.6 28.7 28.7 29.7 27.2 32.6 22.9  
23.1 32.4 18.4 35.7 13.2 28.2 22.5 31.1 17.8 34.2 12.7 26.9 21.8 29.8 17.3 32.7 12.2  
26.9 32.6 22.3 35.8 17.3 28.4 26.3 31.2 21.7 34.4 16.8 27.2 25.7 29.9 21.1 32.9 16.2  
30.1 32.7 26.0 35.9 21.3 29.2 29.2 31.4 25.5 34.5 20.8 28.1 28.1 30.0 24.8 33.1 20.2  
31.7 32.8 29.9 36.0 25.1 30.7 30.7 31.6 29.3 34.6 24.5 29.7 29.7 30.3 28.7 33.1 23.9  
24.0 32.9 18.9 36.2 13.5 28.6 23.3 31.6 18.4 34.7 13.0 27.4 22.7 30.2 17.8 33.1 12.4  
28.1 33.0 23.1 36.3 17.8 28.9 27.5 31.7 22.5 34.9 17.3 27.7 26.8 30.3 21.8 33.4 16.7  
31.0 33.2 27.1 36.5 22.1 30.0 30.0 31.9 26.5 35.0 21.5 28.9 28.9 30.5 25.9 33.5 21.0  
32.6 33.4 31.3 36.5 26.1 31.6 31.6 32.1 30.7 35.1 25.5 30.5 30.5 30.9 30.1 33.6 24.9  
24.8 33.4 19.5 36.6 13.7 29.1 24.2 32.0 18.9 35.0 13.1 27.8 23.5 30.6 18.3 33.4 12.5  
29.2 33.5 23.8 36.8 18.3 29.4 28.6 32.1 23.2 35.3 17.7 28.2 28.0 30.7 22.6 33.7 17.1  
31.7 33.6 28.2 36.9 22.8 30.7 30.7 32.3 27.6 35.4 22.3 29.6 29.6 30.9 26.9 33.8 21.5  
33.4 34.0 32.6 37.0 27.1 32.3 32.3 32.7 32.0 35.5 26.5 31.2 31.2 31.2 31.2 34.0 25.9  
5141  
5692  
6242  
6797  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
SS-PRC003-EN  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-6 Gross Cooling Capacities (MBh) TTA100B Condensing Unit withTWE100BAir Handler  
(I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
94.9  
95.1  
97.0  
74.4 105.3 63.8 116.4 42.9  
86.5 105.5 71.4 116.4 55.6  
97.0 105.6 83.4 116.6 67.8  
90.0  
90.4  
93.0  
97.9  
91.7  
92.4  
96.0  
72.0 100.1 61.7 110.7 40.9 84.9 69.5 94.6 59.5 104.8 38.8 79.6 67.0 88.9 57.3 98.6 36.6  
84.2 100.3 69.0 110.7 53.4 85.5 81.9 94.8 66.6 104.8 51.1 80.5 79.5 89.0 64.2 98.6 48.7  
93.0 100.3 81.1 110.9 65.6 88.8 88.8 94.8 78.7 104.9 63.3 84.5 84.5 89.1 76.2 98.7 60.9  
97.9 100.8 93.1 111.1 77.7 93.6 93.6 95.5 90.8 105.1 75.4 89.1 89.1 90.1 88.5 98.8 73.0  
75.2 101.9 58.7 112.5 41.7 86.5 72.7 96.3 56.3 106.4 39.4 81.0 70.2 90.4 53.8 100.1 37.1  
88.6 102.1 72.1 112.6 55.0 87.5 86.3 96.4 69.6 106.5 52.7 82.2 82.2 90.5 67.1 100.1 50.3  
96.0 102.2 85.0 112.8 68.3 91.7 91.7 96.5 82.6 106.6 65.9 87.1 87.1 90.6 80.1 100.2 63.5  
3000  
3325  
3675  
4000  
102.0 102.0 105.9 95.4 116.8 80.0  
96.7  
97.3  
77.6 107.3 61.1 118.3 43.7  
90.9 107.5 74.4 118.4 57.3  
100.1 100.1 107.6 87.4 118.6 70.6  
105.4 105.4 108.2 100.4 118.8 83.8 101.1 101.1 103.0 98.2 112.9 81.4 96.6 96.6 97.6 95.9 106.7 78.9 91.9 91.9 91.9 91.91 100.3 76.4  
98.5  
99.3  
81.0 109.0 70.3 120.0 44.8  
95.4 109.3 77.5 120.2 59.0  
93.3  
94.4  
98.8  
78.5 103.5 68.1 114.0 42.5 87.9 76.0 97.7 65.8 107.8 40.2 82.4 73.5 91.7 63.1 101.3 38.4  
93.1 103.7 75.1 114.2 56.7 89.1 89.1 97.8 72.6 107.9 54.4 84.5 84.5 91.8 70.0 101.4 52.0  
98.8 103.9 89.0 114.4 71.1 94.3 94.3 98.1 86.6 108.1 68.7 89.5 89.5 92.2 84.2 101.6 66.3  
103.1 103.1 109.5 91.4 120.4 73.4  
108.5 108.5 110.4 105.6 120.6 87.3 104.1 104.1 105.1 103.4 114.5 85.0 99.4 99.4 99.3 99.3 108.2 82.6 94.5 94.5 94.4 94.4 101.7 80.1  
99.9  
101.1  
83.9 110.5 64.9 121.4 45.2  
99.4 110.6 80.1 121.6 60.5  
94.6  
95.7  
81.4 104.8 62.5 115.3 42.9 89.1 78.9 98.9 60.0 109.0 40.5 83.5 76.4 92.8 57.5 102.4 38.2  
95.7 104.9 77.7 115.5 58.2 91.2 91.2 99.0 75.2 109.1 55.9 86.4 86.4 92.8 72.7 102.5 53.5  
105.6 105.6 110.9 95.0 121.9 75.9 101.2 101.2 105.3 92.6 115.7 73.5 96.5 96.5 99.4 90.2 109.3 71.1 91.5 91.5 93.4 87.8 102.6 68.7  
111.2 111.2 112.3 110.3 122.1 90.6 106.6 106.6 106.5 106.5 115.9 88.2 101.7 101.7 101.6 101.6 109.4 85.8 96.6 96.6 96.6 96.6 102.7 83.4  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-6 Gross Cooling Capacities (kW) TTA100B Condensing Unit withTWE100BAir Handler  
(SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
Airflow  
(°C)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
27.8  
27.9  
28.4  
29.9  
28.4  
28.5  
29.4  
30.9  
28.9  
29.1  
30.2  
31.8  
29.3  
29.6  
31.0  
32.6  
21.8 30.9 18.7 34.1 12.6  
25.4 30.9 20.9 34.1 16.3  
28.4 31.0 24.5 34.2 19.9  
29.9 31.1 28.0 34.2 23.4  
22.8 31.5 17.9 34.7 12.8  
26.6 31.5 21.8 34.7 16.8  
29.4 31.5 25.6 34.8 20.7  
30.9 31.7 29.4 34.8 24.5  
23.7 32.0 20.6 35.2 13.1  
28.0 32.0 22.7 35.2 17.3  
30.2 32.1 26.8 35.3 21.5  
31.8 32.4 31.0 35.3 25.6  
24.6 32.4 19.0 35.6 13.2  
29.1 32.4 23.5 35.6 17.7  
31.0 32.5 27.8 35.7 22.2  
32.6 32.9 32.3 35.8 26.5  
26.4  
26.5  
27.3  
28.7  
26.9  
27.1  
28.1  
29.6  
27.4  
27.7  
29.0  
30.5  
27.7  
28.1  
29.7  
31.2  
21.1 29.3 18.1 32.4 12.0 24.9 20.4 27.7 17.4 30.7 11.4 23.3 19.6 26.1 16.8 28.9 10.7  
24.7 29.4 20.2 32.5 15.6 25.1 24.0 27.8 19.5 30.7 15.0 23.6 23.3 26.1 18.8 28.9 14.3  
27.3 29.4 23.8 32.5 19.2 26.0 26.0 27.8 23.1 30.8 18.5 24.8 24.8 26.1 22.3 28.9 17.8  
28.7 29.5 27.3 32.6 22.8 27.4 27.4 28.0 26.6 30.8 22.1 26.1 26.1 26.4 25.9 29.0 21.4  
22.0 29.9 17.2 33.0 12.2 25.4 21.3 28.2 16.5 31.2 11.6 23.7 20.6 26.5 15.8 29.3 10.9  
26.0 29.9 21.1 33.0 16.1 25.6 25.3 28.3 20.4 31.2 15.5 24.1 24.1 26.5 19.7 29.3 14.8  
28.1 30.0 24.9 33.0 20.0 26.9 26.9 28.3 24.2 31.2 19.3 25.5 25.5 26.6 23.5 29.4 18.6  
29.6 30.2 28.8 33.1 23.9 28.3 28.3 28.6 28.1 31.3 23.1 26.9 26.9 26.9 26.9 29.4 22.4  
23.0 30.3 20.0 33.4 12.5 25.8 22.3 28.6 19.3 31.6 11.8 24.1 21.5 26.9 18.5 29.7 11.3  
27.3 30.4 22.0 33.5 16.6 26.1 26.1 28.7 21.3 31.6 15.9 24.8 24.8 26.9 20.5 29.7 15.2  
29.0 30.4 26.1 33.5 20.8 27.6 27.6 28.8 25.4 31.7 20.1 26.2 26.2 27.0 24.7 29.8 19.4  
30.5 30.8 30.3 33.6 24.9 29.1 29.1 29.1 29.1 31.7 24.2 27.7 27.7 27.7 27.7 29.8 23.5  
23.9 30.7 18.3 33.8 12.6 26.1 23.1 29.0 17.6 31.9 11.9 24.5 22.4 27.2 16.9 30.0 11.2  
28.1 30.8 22.8 33.8 17.1 26.7 26.7 29.0 22.0 32.0 16.4 25.3 25.3 27.2 21.3 30.0 15.7  
29.7 30.9 27.1 33.9 21.6 28.3 28.3 29.1 26.4 32.0 20.9 26.8 26.8 27.4 25.7 30.1 20.1  
31.2 31.2 31.2 34.0 25.9 29.8 29.8 29.8 29.8 32.1 25.2 28.3 28.3 28.3 28.3 30.1 24.4  
5098  
5648  
6246  
6797  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
18  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-7 Gross Cooling Capacities (MBh) - Both Compressors -TTA100C Condensing Unit withTWE100AAir Handler (I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
99.7  
78.1 110.4 66.8 121.8 45.0  
95.7  
96.3  
98.8  
76.1 106.1 65.1 117.1 43.3 91.5 74.0 101.4 63.3 112.1 41.6 87.0 71.7 96.5 61.4 106.8 39.8  
88.9 106.4 73.5 117.2 56.8 92.2 86.8 101.8 71.5 112.3 54.9 87.9 84.7 97.0 69.4 107.0 52.9  
98.8 106.6 86.1 117.5 70.0 95.3 95.3 102.0 84.1 112.6 68.1 91.6 91.6 97.2 81.9 107.4 66.1  
100.2 90.9 110.7 75.3 121.9 58.6  
102.1 102.1 110.9 88.1 122.2 71.8  
3000  
3325  
3650  
4000  
107.3 107.3 111.4 100.9 122.4 85.0 104.0 104.0 107.2 99.0 117.7 83.2 100.4 100.4 102.8 97.0 112.7 81.0 96.6 96.6 98.2 94.9 107.5 79.0  
101.7 81.6 112.5 64.3 123.9 45.8  
102.4 95.6 112.8 78.7 124.0 60.4  
97.6  
98.4  
79.5 108.1 62.4 119.0 44.1 93.2 77.3 103.3 60.4 113.8 42.3 88.6 75.1 98.2 58.3 108.4 40.3  
93.6 108.4 76.8 119.1 58.6 94.2 91.5 103.4 74.4 114.0 56.7 89.9 89.3 98.5 72.3 108.6 54.7  
105.4 105.4 113.0 92.4 124.3 74.8 102.0 102.0 108.6 90.4 119.4 73.0 98.4 98.4 103.9 88.3 114.3 71.1 94.5 94.5 98.9 86.1 109.0 69.1  
110.9 110.9 113.7 106.4 124.5 89.1 107.4 107.4 109.5 104.5 119.5 86.9 103.7 103.7 105.0 102.5 114.5 84.9 99.7 99.7 99.8 99.8 109.2 82.9  
103.6 85.1 114.2 73.6 125.6 46.8  
99.3  
83.0 109.6 71.2 120.6 45.0 94.8 80.8 104.8 69.3 115.3 43.1 90.0 78.5 99.6 67.3 109.7 41.6  
104.5 100.4 114.5 81.8 125.8 62.3 100.5 98.4 109.9 79.8 120.8 60.4 95.7 95.7 105.1 77.6 115.6 58.5 91.8 91.8 100.0 75.4 110.1 56.5  
108.6 108.6 114.8 96.8 126.1 77.9 105.0 105.0 110.3 94.8 121.1 76.0 101.2 101.2 105.6 92.7 115.9 74.1 97.2 97.2 100.6 90.5 110.4 72.1  
114.2 114.2 116.0 112.2 126.3 93.0 110.5 110.5 111.7 110.2 121.3 91.0 106.7 106.7 106.8 106.8 116.1 89.0 102.6 102.6 102.7 102.7 110.7 86.9  
105.0 88.3 115.7 68.4 127.1 47.3 100.6 86.2 111.1 66.5 121.9 45.4 96.0 83.9 106.1 64.5 116.5 43.4 91.3 81.6 100.8 62.4 110.8 41.5  
106.3 104.8 115.9 84.6 127.3 64.0 101.8 101.8 111.3 82.6 122.1 62.1 97.9 97.9 106.4 80.5 116.8 60.2 93.8 93.8 101.2 78.2 111.2 58.2  
111.2 111.2 116.3 100.7 127.6 80.6 107.5 107.5 111.8 98.7 122.5 78.8 103.6 103.6 107.0 96.6 117.2 76.8 99.4 99.4 101.9 94.4 111.4 74.4  
116.9 116.9 117.9 117.3 127.8 96.6 113.2 113.2 113.3 113.3 122.7 94.7 109.2 109.2 109.2 109.2 117.4 92.6 104.9 104.9 105.0 105.0 111.9 90.5  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-7 Gross Cooling Capacities (kW) - Both Compressors -TTA100C Condensing Unit withTWE100A Air Handler  
(SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
19.4  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
22.8  
Airflow  
(°C)  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
29.2  
29.3  
29.9  
31.4  
29.8  
30.0  
30.9  
32.5  
30.3  
30.6  
31.8  
33.4  
30.7  
31.1  
32.6  
34.2  
22.9 32.3 19.6 35.7 13.2  
26.6 32.4 22.1 35.7 17.1  
29.9 32.5 25.8 35.8 21.0  
31.4 32.6 29.6 35.8 24.9  
23.9 32.9 18.8 36.3 13.4  
28.0 33.0 23.0 36.3 17.7  
30.9 33.1 27.0 36.4 21.9  
32.5 33.3 31.2 36.5 26.1  
24.9 33.4 21.6 36.8 13.7  
29.4 33.5 23.9 36.8 18.2  
31.8 33.6 28.3 36.9 22.8  
33.4 34.0 32.8 37.0 27.2  
25.8 33.9 20.0 37.2 13.8  
30.7 33.9 24.8 37.3 18.7  
32.6 34.1 29.5 37.4 23.6  
34.2 34.5 34.3 37.4 28.3  
28.0  
28.2  
28.9  
30.5  
28.6  
28.8  
29.9  
31.4  
29.1  
29.4  
30.7  
32.4  
29.5  
29.8  
31.5  
33.1  
22.3 31.1 19.1 34.3 12.7 26.8 21.7 29.7 18.5 32.8 12.2 25.5 21.0 28.3 18.0 31.3 11.6  
26.0 31.2 21.5 34.3 16.6 27.0 25.4 29.8 20.9 32.9 16.1 25.7 24.8 28.4 20.3 31.3 15.5  
28.9 31.2 25.2 34.4 20.5 27.9 27.9 29.9 24.6 33.0 19.9 26.8 26.8 28.5 24.0 31.4 19.4  
30.5 31.4 29.0 34.5 24.4 29.4 29.4 30.1 28.4 33.0 23.7 28.3 28.3 28.8 27.8 31.5 23.1  
23.3 31.6 18.3 34.8 12.9 27.3 22.6 30.2 17.7 33.3 12.4 25.9 22.0 28.8 17.1 31.7 11.8  
27.4 31.7 22.5 34.9 17.2 27.6 26.8 30.3 21.8 33.4 16.6 26.3 26.2 28.8 21.2 31.8 16.0  
29.9 31.8 26.5 35.0 21.4 28.8 28.8 30.4 25.9 33.5 20.8 27.7 27.7 29.0 25.2 31.9 20.2  
31.4 32.1 30.6 35.0 25.5 30.4 30.4 30.8 30.0 33.5 24.9 29.2 29.2 29.2 29.2 32.0 24.3  
24.3 32.1 20.8 35.3 13.2 27.8 23.7 30.7 20.3 33.7 12.6 26.4 23.0 29.2 19.7 32.1 12.2  
28.8 32.2 23.4 35.4 17.7 28.0 28.0 30.8 22.7 33.8 17.1 26.9 26.9 29.3 22.1 32.2 16.6  
30.7 32.3 27.7 35.5 22.3 29.6 29.6 30.9 27.1 33.9 21.7 28.4 28.4 29.4 26.5 32.3 21.1  
32.4 32.7 32.3 35.5 26.7 31.2 31.2 31.3 31.3 34.0 26.1 30.0 30.0 30.1 30.1 32.4 25.4  
25.2 32.5 19.5 35.7 13.3 28.1 24.6 31.1 18.9 34.1 12.7 26.7 23.9 29.5 18.3 32.4 12.1  
29.8 32.6 24.2 35.8 18.2 28.7 28.7 31.1 23.6 34.2 17.6 27.5 27.5 29.6 22.9 32.6 17.0  
31.5 32.7 28.9 35.9 23.1 30.3 30.3 31.3 28.3 34.3 22.5 29.1 29.1 29.8 27.6 32.6 21.8  
33.1 33.2 33.2 35.9 27.7 32.0 32.0 32.0 32.0 34.4 27.1 30.7 30.7 30.7 30.7 32.8 26.5  
5098  
5648  
6203  
6797  
Dry coil conditions. Total Gross Cooling Capacity (kW) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
SS-PRC003-EN  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-8 Gross Cooling Capacities (MBh) - Single Compressor -TTA100C Condensing Unit withTWE100AAir Handler (I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
62.7  
65.8  
69.8  
73.7  
63.7  
67.4  
71.5  
75.6  
64.8  
68.9  
73.0  
77.2  
65.8  
70.1  
74.3  
78.6  
60.3 68.8 49.8 75.3 29.4  
65.8 69.1 57.4 75.9 41.9  
69.8 69.8 69.8 76.2 54.4  
73.7 73.8 73.8 76.5 67.3  
63.5 69.6 46.4 76.1 29.2  
67.4 69.9 60.3 76.6 43.2  
71.5 71.5 71.5 77.0 57.0  
75.6 75.6 75.6 77.5 71.1  
64.8 70.3 55.6 76.7 31.0  
68.9 70.7 63.3 77.3 44.7  
73.0 73.1 73.1 77.7 59.8  
77.2 77.3 77.3 78.4 75.1  
65.8 70.8 49.8 77.2 30.2  
70.1 71.4 66.0 77.9 46.1  
74.3 74.4 74.4 78.3 62.2  
78.6 78.7 78.7 79.2 78.7  
60.1  
63.5  
67.3  
71.2  
61.0  
65.0  
69.0  
73.0  
62.3  
66.3  
70.4  
74.5  
63.3  
67.5  
71.6  
75.8  
59.0 65.9 48.6 72.1 28.4 57.3 57.3 62.8 47.4 68.7 27.3 54.8 54.8 59.7 46.1 65.2 26.2  
63.5 66.2 56.2 72.6 40.5 61.0 61.0 63.2 54.9 69.4 39.3 58.5 58.5 60.2 53.6 66.0 37.9  
67.3 67.4 67.4 73.1 53.2 64.8 64.8 64.9 64.9 69.8 52.0 62.1 62.1 62.2 62.2 66.5 50.7  
71.2 71.3 71.3 73.4 66.1 68.6 68.6 68.7 68.7 70.3 64.9 65.9 65.9 65.9 65.9 67.0 63.7  
61.0 66.6 45.1 72.8 28.1 58.6 58.6 63.5 43.8 69.3 26.9 56.0 56.0 60.3 42.5 65.7 25.8  
65.0 67.0 59.1 73.4 42.0 62.4 62.4 64.0 57.8 70.1 40.7 59.8 59.8 60.9 56.5 66.6 39.4  
69.0 69.0 69.0 73.8 55.8 66.3 66.3 66.4 66.4 70.5 54.6 63.5 63.5 63.6 63.6 67.1 53.4  
73.0 73.0 73.0 74.4 69.9 70.3 70.3 70.3 70.3 71.2 68.7 67.4 67.4 67.5 67.5 67.9 67.5  
62.3 67.3 54.3 73.3 30.0 59.8 59.8 64.1 45.6 69.8 28.9 57.1 57.1 60.9 44.2 66.1 27.8  
66.3 67.8 62.1 74.1 43.5 63.7 63.7 64.7 60.8 70.7 42.2 61.0 61.0 61.6 59.5 67.2 40.8  
70.4 70.5 70.5 74.5 58.6 67.7 67.7 67.8 67.8 71.1 57.3 64.8 64.8 64.9 64.9 67.7 56.1  
74.5 74.6 74.6 75.3 73.9 71.7 71.7 71.8 71.8 71.8 71.8 68.8 68.8 68.8 68.8 68.9 68.9  
63.3 67.8 48.5 73.7 29.1 60.7 60.7 64.6 47.2 70.1 27.9 58.0 58.0 61.3 45.7 66.4 26.7  
67.5 68.4 64.8 74.7 45.9 64.7 64.7 65.3 63.5 71.2 43.5 61.9 61.9 62.2 62.2 67.6 42.1  
71.6 71.7 71.7 75.0 61.0 68.8 68.8 68.9 68.9 71.6 59.8 65.9 65.9 66.0 66.0 68.2 58.5  
75.8 75.9 75.9 75.9 75.9 72.9 72.9 73.0 73.0 73.1 73.1 69.9 69.9 70.0 70.0 70.0 70.0  
3000  
3325  
3650  
4000  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-8 Gross Cooling Capacities (kW) - Single Compressor -TTA100C Condensing Unit withTWE100AAir Handler  
(SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
19.4  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
22.8  
Airflow  
(°C)  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
18.4  
19.3  
20.4  
21.6  
18.7  
19.7  
20.9  
22.1  
19.0  
20.2  
21.4  
22.6  
19.3  
20.5  
21.8  
23.0  
17.6 20.1 14.6 22.1 8.6  
19.3 20.2 16.8 22.2 12.3  
20.4 20.4 20.4 22.3 15.9  
21.6 21.6 21.6 22.4 19.7  
18.6 20.4 13.6 22.3 8.5  
19.7 20.5 17.7 22.4 12.6  
20.9 20.9 20.9 22.6 16.7  
22.1 22.1 22.1 22.7 20.8  
19.0 20.6 16.3 22.4 9.1  
20.2 20.7 18.5 22.6 13.1  
21.4 21.4 21.4 22.8 17.5  
22.6 22.6 22.6 23.0 22.0  
19.3 20.7 14.6 22.6 8.8  
20.5 20.9 19.3 22.8 13.5  
21.8 21.8 21.8 22.9 18.2  
23.0 23.0 23.0 23.2 23.0  
17.6  
18.6  
19.7  
20.9  
17.9  
19.0  
20.2  
21.4  
18.2  
19.4  
20.6  
21.8  
18.5  
19.8  
21.0  
22.2  
17.3 19.3 14.2 21.1 8.3 16.8 16.8 18.4 13.9 20.1 8.0 16.0 16.0 17.5 13.5 19.1 7.7  
18.6 19.4 16.4 21.3 11.9 17.9 17.9 18.5 16.1 20.3 11.5 17.1 17.1 17.6 15.7 19.3 11.1  
19.7 19.7 19.7 21.4 15.6 19.0 19.0 19.0 19.0 20.4 15.2 18.2 18.2 18.2 18.2 19.5 14.9  
20.9 20.9 20.9 21.5 19.4 20.1 20.1 20.1 20.1 20.6 19.0 19.3 19.3 19.3 19.3 19.6 18.7  
17.9 19.5 13.2 21.3 8.2 17.2 17.2 18.6 12.8 20.3 7.9 16.4 16.4 17.7 12.4 19.2 7.5  
19.0 19.6 17.3 21.5 12.3 18.3 18.3 18.7 16.9 20.5 11.9 17.5 17.5 17.8 16.5 19.5 11.5  
20.2 20.2 20.2 21.6 16.4 19.4 19.4 19.4 19.4 20.7 16.0 18.6 18.6 18.6 18.6 19.7 15.6  
21.4 21.4 21.4 21.8 20.5 20.6 20.6 20.6 20.6 20.8 20.1 19.7 19.7 19.8 19.8 19.9 19.8  
18.2 19.7 15.9 21.5 8.8 17.5 17.5 18.8 13.4 20.4 8.5 16.7 16.7 17.8 12.9 19.3 8.1  
19.4 19.8 18.2 21.7 12.7 18.6 18.6 18.9 17.8 20.7 12.4 17.8 17.8 18.0 17.4 19.7 12.0  
20.6 20.6 20.6 21.8 17.1 19.8 19.8 19.8 19.8 20.8 16.8 19.0 19.0 19.0 19.0 19.8 16.4  
21.8 21.8 21.8 22.0 21.6 21.0 21.0 21.0 21.0 21.0 21.0 20.1 20.1 20.2 20.2 20.2 20.2  
18.5 19.9 14.2 21.6 8.5 17.8 17.8 18.9 13.8 20.5 8.2 17.0 17.0 18.0 13.4 19.4 7.8  
19.8 20.0 19.0 21.9 13.4 19.0 19.0 19.1 18.6 20.8 12.7 18.1 18.1 18.2 18.2 19.8 12.3  
21.0 21.0 21.0 22.0 17.9 20.2 20.2 20.2 20.2 21.0 17.5 19.3 19.3 19.3 19.3 20.0 17.1  
22.2 22.2 22.2 22.2 22.2 21.4 21.4 21.4 21.4 21.4 21.4 20.5 20.5 20.5 20.5 20.5 20.5  
5098  
5648  
6203  
6797  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
20  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-9 Gross Cooling Capacities (MBh) TTA125B Condensing Unit withTWE100B Air Handler  
(I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
108.2 79.4 117.8 61.3 124.3 42.2 100.3 76.1 109.3 58.1 115.4 39.2 92.3 72.8 100.8 54.9 106.5 36.1 84.4 69.5 92.3 51.7 97.6 33.0  
108.2 93.1 117.8 75.0 124.3 55.9 100.3 89.8 109.3 71.8 115.4 52.8 92.3 86.5 100.8 68.5 106.5 49.7 84.4 82.7 92.3 65.3 97.6 46.7  
108.2 105.3 117.8 88.6 124.3 69.5 100.3 99.4 109.3 85.4 115.4 66.5 93.1 93.1 100.8 82.2 106.5 63.5 86.9 86.9 92.3 79.0 97.6 60.3  
110.2 110.2 117.8 102.2 124.3 83.2 103.9 103.9 109.3 99.0 115.4 80.2 97.4 97.4 100.8 96.0 106.5 77.0 90.8 90.8 92.7 92.7 97.6 74.0  
110.0 83.1 119.6 64.1 126.3 44.1 101.8 79.6 111.0 60.7 117.2 41.0 93.8 76.1 102.4 57.4 108.2 37.7 85.8 72.6 93.7 54.1 99.2 34.5  
110.0 97.4 119.6 78.4 126.3 58.5 101.8 93.9 111.0 75.1 117.2 55.2 93.8 90.4 102.4 71.7 108.2 52.0 86.5 86.5 93.7 68.3 99.2 48.9  
110.1 110.1 119.6 92.7 126.3 72.7 104.0 104.0 111.0 89.3 117.2 69.6 97.4 97.4 102.4 85.9 108.2 66.4 90.9 90.9 93.7 82.7 99.2 63.1  
115.3 115.3 119.6 106.9 126.3 87.0 108.7 108.7 111.0 103.6 117.2 83.9 101.9 101.9 102.4 100.4 108.2 80.6 95.0 95.0 96.9 96.9 99.2 77.4  
111.8 87.0 121.7 67.1 128.4 46.2 103.6 83.3 112.9 63.6 119.2 43.0 95.4 79.7 104.1 60.2 110.1 39.5 87.2 76.1 95.3 56.6 100.8 36.1  
111.8 102.0 121.7 82.1 128.4 61.3 103.6 98.3 112.9 78.6 119.2 57.9 95.4 94.7 104.1 75.1 110.1 54.5 90.6 90.6 95.3 71.6 100.8 51.2  
115.4 115.4 121.7 97.1 128.4 76.2 108.9 108.9 112.9 93.5 119.2 72.9 102.0 102.0 104.1 90.0 110.1 69.5 95.2 95.2 95.3 86.6 100.8 66.1  
120.8 120.8 121.7 112.0 128.4 91.1 111.6 111.6 112.9 108.5 119.2 87.8 103.2 103.2 105.1 105.1 110.1 84.4 99.0 99.0 99.2 99.2 100.8 81.0  
113.5 90.7 123.5 69.9 130.4 48.2 105.2 86.8 114.6 66.3 121.0 44.8 96.9 83.1 105.7 62.7 111.8 41.2 88.6 79.3 96.8 59.0 102.4 37.7  
113.5 106.2 123.5 85.6 130.4 63.8 105.2 102.5 114.6 81.9 121.0 60.3 98.7 98.7 105.7 78.2 111.8 56.8 94.4 94.4 96.8 74.6 102.4 53.4  
120.2 120.2 123.5 101.2 130.4 79.4 113.5 113.5 114.6 97.5 121.0 75.9 104.8 104.8 105.7 93.8 111.8 72.4 96.1 96.1 96.8 90.2 102.4 68.9  
123.1 123.1 123.5 116.7 130.4 94.9 113.5 113.5 114.6 113.0 121.0 91.5 107.6 107.6 109.5 109.5 111.8 87.9 99.8 99.8 101.5 101.5 102.4 84.4  
3000  
3325  
3675  
4000  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-9 Gross Cooling Capacities (kW) TTA125B Condensing Unit withTWE100BAir Handler  
(SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
Airflow  
(°C)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
31.7  
31.7  
31.7  
32.3  
32.2  
32.2  
32.3  
33.8  
32.8  
32.8  
33.8  
35.4  
33.3  
33.3  
35.2  
36.1  
23.3 34.5 18.0 36.4 12.4  
27.3 34.5 22.0 36.4 16.4  
30.9 34.5 26.0 36.4 20.4  
32.3 34.5 29.9 36.4 24.4  
24.3 35.0 18.8 37.0 12.9  
28.5 35.0 23.0 37.0 17.1  
32.3 35.0 27.2 37.0 21.3  
33.8 35.0 31.3 37.0 25.5  
25.5 35.7 19.7 37.6 13.5  
29.9 35.7 24.1 37.6 18.0  
33.8 35.7 28.5 37.6 22.3  
35.4 35.7 32.8 37.6 26.7  
26.6 36.2 20.5 38.2 14.1  
31.1 36.2 25.1 38.2 18.7  
35.2 36.2 29.7 38.2 23.3  
36.1 36.2 34.2 38.2 27.8  
29.4  
29.4  
29.4  
30.4  
29.8  
29.8  
30.5  
31.8  
30.4  
30.4  
31.9  
32.7  
30.8  
30.8  
33.3  
33.3  
22.3 32.0 17.0 33.8 11.5 27.0 21.3 29.5 16.1 31.2 10.6 24.7 20.4 27.0 15.1 28.6 9.7  
26.3 32.0 21.0 33.8 15.5 27.0 25.3 29.5 20.1 31.2 14.6 24.7 24.2 27.0 19.1 28.6 13.7  
29.1 32.0 25.0 33.8 19.5 27.3 27.3 29.5 24.1 31.2 18.6 25.5 25.5 27.0 23.1 28.6 17.7  
30.4 32.0 29.0 33.8 23.5 28.5 28.5 29.5 28.1 31.2 22.6 26.6 26.6 27.2 27.2 28.6 21.7  
23.3 32.5 17.8 34.3 12.0 27.5 22.3 30.0 16.8 31.7 11.0 25.1 21.3 27.5 15.9 29.1 10.1  
27.5 32.5 22.0 34.3 16.2 27.5 26.5 30.0 21.0 31.7 15.2 25.3 25.3 27.5 20.0 29.1 14.3  
30.5 32.5 26.2 34.3 20.4 28.5 28.5 30.0 25.2 31.7 19.5 26.6 26.6 27.5 24.2 29.1 18.5  
31.8 32.5 30.4 34.3 24.6 29.9 29.9 30.0 29.4 31.7 23.6 27.8 27.8 28.4 28.4 29.1 22.7  
24.4 33.1 18.6 34.9 12.6 28.0 23.4 30.5 17.6 32.3 11.6 25.5 22.3 27.9 16.6 29.5 10.6  
28.8 33.1 23.0 34.9 17.0 28.0 27.7 30.5 22.0 32.3 16.0 26.5 26.5 27.9 21.0 29.5 15.0  
31.9 33.1 27.4 34.9 21.4 29.9 29.9 30.5 26.4 32.3 20.4 27.9 27.9 27.9 25.4 29.5 19.4  
32.7 33.1 31.8 34.9 25.7 30.2 30.2 30.8 30.81 32.3 24.7 29.0 29.0 29.1 29.1 29.5 23.7  
25.4 33.6 19.4 35.5 13.1 28.4 24.3 31.0 18.4 32.8 12.1 26.0 23.2 28.4 17.3 30.0 11.0  
30.0 33.6 24.0 35.5 17.7 28.9 28.9 31.0 22.9 32.8 16.6 27.7 27.7 28.4 21.9 30.0 15.6  
33.3 33.6 28.6 35.5 22.2 30.7 30.7 31.0 27.5 32.8 21.2 28.2 28.2 28.4 26.4 30.0 20.2  
33.3 33.6 33.1 35.5 26.8 31.5 31.5 32.1 32.1 32.8 25.8 29.2 29.2 29.7 29.7 30.0 24.7  
5098  
5648  
6246  
6797  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
SS-PRC003-EN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-10 Gross Cooling Capacities (MBh) TTA125B Condensing Unit withTWE155BAir Handler  
(I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
120.8 96.6 132.7 73.8 141.1 49.7 113.8 93.7 124.9 70.8 132.7 46.7 106.3 90.5 116.6 67.6 123.9 43.6 98.8 87.4 108.3 64.6 115.0 40.6  
120.8 114.3 132.7 91.4 141.1 67.4 113.8 111.4 124.9 88.5 132.7 64.5 108.3 108.3 116.6 85.4 123.9 61.3 104.9 104.9 108.3 82.2 115.0 58.3  
126.8 126.8 132.7 109.2 141.1 85.1 119.6 119.6 124.9 106.2 132.7 82.1 112.4 112.4 116.6 103.0 123.9 79.1 105.0 105.0 108.3 100.0 115.0 76.0  
127.4 127.4 132.7 126.9 141.1 102.8 123.1 123.1 124.9 123.9 132.7 100.0 118.9 118.9 119.7 119.7 123.9 96.7 110.0 110.0 111.2 111.2 115.0 93.6  
122.7 101.2 134.9 77.3 143.4 52.0 115.6 98.1 127.0 74.1 134.9 49.0 108.0 94.8 118.5 70.8 125.9 45.7 100.4 91.5 110.1 67.6 116.9 42.5  
122.7 119.7 134.9 95.7 143.4 70.6 116.6 116.6 127.0 92.7 134.9 67.5 113.4 113.4 118.5 89.4 125.9 64.2 109.9 109.9 110.1 86.1 116.9 61.1  
132.8 132.8 134.9 114.3 143.4 89.1 125.3 125.3 127.0 111.2 134.9 86.0 117.7 117.7 118.5 107.9 125.9 82.9 110.0 110.0 110.1 104.7 116.9 79.5  
133.4 133.4 134.9 132.8 143.4 107.7 128.9 128.9 129.8 129.8 134.9 104.7 124.5 124.5 125.3 125.3 125.9 101.3 115.2 115.2 116.4 116.4 116.9 98.0  
124.7 105.7 137.1 80.8 145.6 54.3 117.5 102.5 129.0 77.4 137.1 51.2 109.7 99.1 120.4 74.0 127.9 47.7 102.0 95.7 111.8 70.7 118.7 44.4  
125.1 125.1 137.1 100.1 145.6 73.8 121.9 121.9 129.0 96.8 137.1 70.5 118.5 118.5 120.4 93.4 127.9 67.1 111.1 111.1 111.8 90.0 118.7 63.8  
136.9 136.9 137.1 119.5 145.6 93.1 128.7 128.7 129.0 116.2 137.1 89.9 119.9 119.9 120.4 112.7 127.9 86.6 111.5 111.5 111.8 109.4 118.7 83.1  
137.9 137.9 138.8 138.8 145.6 112.5 134.7 134.7 135.6 135.6 137.1 109.5 127.4 127.4 127.8 127.8 127.9 105.8 117.0 117.0 117.7 117.7 118.7 102.5  
126.7 110.3 139.2 84.2 147.9 56.7 119.3 106.9 131.0 80.8 139.2 53.4 111.4 103.3 122.3 77.2 129.9 49.8 103.6 99.8 113.6 73.7 120.6 46.3  
130.5 130.5 139.2 104.4 147.9 76.9 127.1 127.1 131.0 101.0 139.2 73.6 121.9 121.9 122.3 97.4 129.9 70.0 112.7 112.7 113.6 93.8 120.6 66.6  
138.6 138.6 139.2 124.6 147.9 97.1 130.3 130.3 131.0 121.2 139.2 93.7 122.2 122.2 122.3 117.6 129.9 90.3 113.9 113.9 114.1 114.1 120.6 86.7  
144.1 144.1 144.8 144.8 147.9 117.4 138.6 138.6 138.7 138.7 139.2 114.2 128.8 128.8 129.4 129.4 129.9 110.4 119.6 119.6 120.2 120.2 120.6 106.9  
3750  
4200  
4600  
5000  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-10 Gross Cooling Capacities (kW) TTA125B Condensing Unit withTWE155BAir Handler  
(SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
Airflow  
(°C)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
35.4  
35.4  
37.2  
37.3  
36.0  
36.0  
38.9  
39.1  
36.5  
36.7  
40.1  
40.4  
37.1  
38.2  
40.6  
42.2  
28.3 38.9 21.6 41.3 14.6  
33.5 38.9 26.8 41.3 19.7  
37.2 38.9 32.0 41.3 24.9  
37.3 38.9 37.2 41.3 30.1  
29.7 39.5 22.6 42.0 15.2  
35.1 39.5 28.0 42.0 20.7  
38.9 39.5 33.5 42.0 26.1  
39.1 39.5 38.9 42.0 31.6  
31.0 40.2 23.7 42.7 15.9  
36.7 40.2 29.3 42.7 21.6  
40.1 40.2 35.0 42.7 27.3  
40.4 40.7 40.7 42.7 33.0  
32.3 40.8 24.7 43.3 16.6  
38.2 40.8 30.6 43.3 22.5  
40.6 40.8 36.5 43.3 28.5  
42.2 42.4 42.4 43.3 34.4  
33.3  
33.3  
35.0  
36.1  
33.9  
34.2  
36.7  
37.8  
34.4  
35.7  
37.7  
39.5  
35.0  
37.2  
38.2  
40.6  
27.5 36.6 20.7 38.9 13.7 31.1 26.5 34.2 19.8 36.3 12.8 28.9 25.6 31.7 18.9 33.7 11.9  
32.6 36.6 25.9 38.9 18.9 31.7 31.7 34.2 25.0 36.3 18.0 30.7 30.7 31.7 24.1 33.7 17.1  
35.0 36.6 31.1 38.9 24.1 32.9 32.9 34.2 30.2 36.3 23.2 30.8 30.8 31.7 29.3 33.7 22.3  
36.1 36.6 36.3 38.9 29.3 34.8 34.8 35.1 35.1 36.3 28.3 32.2 32.2 32.6 32.6 33.7 27.4  
28.7 37.2 21.7 39.5 14.4 31.6 27.8 34.7 20.7 36.9 13.4 29.4 26.8 32.3 19.8 34.3 12.5  
34.2 37.2 27.2 39.5 19.8 33.2 33.2 34.7 26.2 36.9 18.8 32.2 32.2 32.3 25.2 34.3 17.9  
36.7 37.2 32.6 39.5 25.2 34.5 34.5 34.7 31.6 36.9 24.3 32.2 32.2 32.3 30.7 34.3 23.3  
37.8 38.0 38.0 39.5 30.7 36.5 36.5 36.7 36.7 36.9 29.7 33.8 33.8 34.1 34.1 34.3 28.7  
30.0 37.8 22.7 40.2 15.0 32.1 29.0 35.3 21.7 37.5 14.0 29.9 28.0 32.8 20.7 34.8 13.0  
35.7 37.8 28.4 40.2 20.7 34.7 34.7 35.3 27.4 37.5 19.7 32.6 32.6 32.8 26.4 34.8 18.7  
37.7 37.8 34.0 40.2 26.3 35.1 35.1 35.3 33.0 37.5 25.4 32.7 32.7 32.8 32.1 34.8 24.3  
39.5 39.7 39.7 40.2 32.1 37.3 37.3 37.4 37.4 37.5 31.0 34.3 34.3 34.5 34.5 34.8 30.0  
31.3 38.4 23.7 40.8 15.6 32.6 30.3 35.8 22.6 38.1 14.6 30.4 29.2 33.3 21.6 35.3 13.6  
37.2 38.4 29.6 40.8 21.6 35.7 35.7 35.8 28.5 38.1 20.5 33.0 33.0 33.3 27.5 35.3 19.5  
38.2 38.4 35.5 40.8 27.5 35.8 35.8 35.8 34.5 38.1 26.5 33.4 33.4 33.4 33.4 35.3 25.4  
40.6 40.6 40.6 40.8 33.5 37.7 37.7 37.9 37.9 38.1 32.3 35.0 35.0 35.2 35.21 35.3 31.3  
6372  
7135  
7816  
8496  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
22  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-11 Gross Cooling Capacities (MBh) TTA155B Condensing Unit withTWE155BAir Handler  
(I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
153.6 120.6 169.3 101.0 185.5 68.8 148.1 117.8 163.0 98.5 178.1 66.3 141.7 114.5 155.8 95.6 169.8 63.4 134.4 110.7 147.7 92.3 160.6 60.3  
154.5 140.6 169.7 116.3 186.6 90.6 149.2 137.8 163.5 113.4 179.4 87.8 142.9 134.6 156.4 110.1 171.4 84.9 135.9 131.0 148.4 106.4 162.6 81.6  
157.8 157.8 170.7 136.1 187.6 111.5 153.2 153.2 164.5 133.3 180.4 108.8 147.8 147.8 157.4 130.0 172.5 105.8 141.6 141.6 149.4 126.3 163.2 101.6  
165.9 165.9 171.6 156.3 188.0 131.2 161.1 161.1 165.6 153.4 180.8 128.2 155.4 155.4 158.7 150.2 173.0 125.0 149.1 149.1 151.1 146.7 164.5 121.4  
156.7 126.1 172.4 99.7 188.2 69.9 151.0 123.2 165.9 97.0 180.6 67.3 144.4 119.8 158.4 93.9 172.1 64.4 136.8 116.0 149.3 89.6 162.7 61.2  
158.0 148.1 172.9 121.2 189.8 93.6 152.4 145.2 166.5 118.3 182.3 90.8 146.0 141.9 159.1 114.9 174.1 87.8 138.9 138.2 151.0 111.1 165.0 84.6  
163.0 163.0 173.9 143.0 190.9 116.5 158.2 158.2 167.5 140.0 182.7 112.8 152.4 152.4 160.1 136.6 174.6 109.5 145.9 145.9 152.0 132.9 165.8 105.8  
171.5 171.5 175.3 165.1 191.5 137.6 166.4 166.4 169.1 162.2 184.0 134.5 160.4 160.4 162.1 159.0 175.9 131.2 153.7 153.7 153.9 153.9 167.1 127.6  
159.4 131.3 174.9 103.1 190.6 71.2 153.5 128.3 168.2 100.3 182.7 68.5 146.6 124.8 159.8 96.2 173.9 65.5 138.9 120.9 151.3 92.3 164.3 62.3  
161.0 155.3 175.7 125.9 192.5 96.5 155.4 152.3 169.0 122.9 184.6 93.7 148.2 148.2 161.5 119.4 176.2 90.6 141.7 141.7 153.1 115.6 167.0 87.4  
167.6 167.6 176.6 149.5 193.0 120.1 162.5 162.5 170.0 146.5 185.3 117.0 156.5 156.5 162.5 143.1 177.0 113.6 149.7 149.7 154.3 139.3 168.0 109.9  
176.3 176.3 178.6 173.6 194.4 143.6 170.9 170.9 172.3 170.7 186.7 140.5 164.7 164.7 164.9 164.9 178.3 137.1 157.8 157.8 157.9 157.9 169.3 133.5  
161.6 136.3 177.1 106.2 192.5 72.4 155.5 133.2 169.5 102.4 184.4 69.6 148.5 129.7 161.7 98.8 175.4 66.5 140.6 125.7 153.6 96.9 165.6 63.1  
163.8 162.2 178.0 130.4 194.7 99.2 157.6 157.6 171.2 127.4 186.6 96.4 151.6 151.6 163.4 123.8 178.0 93.3 144.8 144.8 154.9 119.9 168.6 90.1  
171.7 171.7 179.1 155.8 195.5 124.2 166.3 166.3 172.3 152.7 187.6 121.0 160.0 160.0 164.7 149.3 179.0 117.5 153.0 153.0 156.3 145.5 169.9 113.8  
180.7 180.7 180.9 180.9 196.8 149.5 175.0 175.0 175.1 175.1 189.0 146.3 168.5 168.5 168.7 168.7 180.3 142.8 161.3 161.3 161.5 161.5 171.2 139.2  
4500  
5000  
5500  
6000  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-11 Gross Cooling Capacities (kW) TTA155B Condensing Unit withTWE155B Air Handler  
(SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
Airflow  
(°C)  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
45.0  
45.2  
46.2  
48.6  
45.9  
46.3  
47.7  
50.2  
46.7  
47.1  
49.1  
51.6  
47.3  
48.0  
50.3  
52.9  
35.3 49.6 29.6 54.3 20.1  
41.2 49.7 34.0 54.6 26.5  
46.2 50.0 39.9 54.9 32.7  
48.6 50.2 45.8 55.0 38.4  
36.9 50.5 29.2 55.1 20.5  
43.4 50.6 35.5 55.6 27.4  
47.7 50.9 41.9 55.9 34.1  
50.2 51.3 48.3 56.1 40.3  
38.4 51.2 30.2 55.8 20.8  
45.5 51.4 36.9 56.3 28.3  
49.1 51.7 43.8 56.5 35.2  
51.6 52.3 50.8 56.9 42.1  
39.9 51.9 31.1 56.4 21.2  
47.5 52.1 38.2 57.0 29.1  
50.3 52.4 45.6 57.2 36.4  
52.9 53.0 53.0 57.6 43.8  
43.4  
43.7  
44.9  
47.2  
44.2  
44.6  
46.3  
48.7  
44.9  
45.5  
47.6  
50.0  
45.5  
46.1  
48.7  
51.2  
34.5 47.7 28.8 52.1 19.4 41.5 33.5 45.6 28.0 49.7 18.6 39.4 32.4 43.2 27.0 47.0 17.7  
40.4 47.9 33.2 52.5 25.7 41.8 39.4 45.8 32.2 50.2 24.8 39.8 38.3 43.5 31.1 47.6 23.9  
44.9 48.2 39.0 52.8 31.9 43.3 43.3 46.1 38.1 50.5 31.0 41.5 41.5 43.8 37.0 47.8 29.7  
47.2 48.5 44.9 52.9 37.5 45.5 45.5 46.5 44.0 50.7 36.6 43.7 43.7 44.2 42.9 48.2 35.6  
36.1 48.6 28.4 52.9 19.7 42.3 35.1 46.4 27.5 50.4 18.9 40.1 34.0 43.7 26.2 47.6 17.9  
42.5 48.8 34.6 53.4 26.6 42.8 41.6 46.6 33.6 51.0 25.7 40.7 40.5 44.2 32.5 48.3 24.8  
46.3 49.0 41.0 53.5 33.0 44.6 44.6 46.9 40.0 51.1 32.1 42.7 42.7 44.5 38.9 48.6 31.0  
48.7 49.5 47.5 53.9 39.4 47.0 47.0 47.5 46.5 51.5 38.4 45.0 45.0 45.1 45.1 48.9 37.4  
37.6 49.3 29.4 53.5 20.1 42.9 36.5 46.8 28.2 50.9 19.2 40.7 35.4 44.3 27.0 48.1 18.3  
44.6 49.5 36.0 54.1 27.4 43.4 43.4 47.3 35.0 51.6 26.5 41.5 41.5 44.8 33.9 48.9 25.6  
47.6 49.8 42.9 54.3 34.3 45.8 45.8 47.6 41.9 51.8 33.3 43.8 43.8 45.2 40.8 49.2 32.2  
50.0 50.4 50.0 54.7 41.1 48.2 48.2 48.3 48.3 52.2 40.1 46.2 46.2 46.2 46.2 49.6 39.1  
39.0 49.6 30.0 54.0 20.4 43.5 38.0 47.3 28.9 51.4 19.5 41.2 36.8 45.0 28.4 48.5 18.5  
46.1 50.1 37.3 54.6 28.2 44.4 44.4 47.9 36.3 52.1 27.3 42.4 42.4 45.3 35.1 49.4 26.4  
48.7 50.4 44.7 54.9 35.4 46.9 46.9 48.2 43.7 52.4 34.4 44.8 44.8 45.8 42.6 49.7 33.3  
51.2 51.3 51.3 55.3 42.8 49.3 49.3 49.4 49.4 52.8 41.8 47.2 47.2 47.3 47.3 50.1 40.7  
7646  
8496  
9346  
10195  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
SS-PRC003-EN  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-12Gross Cooling Capacities (MBh) TTA155B Condensing Unit withTWE200BAir Handler  
(I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
158.1 125.3 174.1 103.2 189.9 70.5 152.4 122.3 167.6 100.6 182.4 67.9 145.7 118.9 160.0 97.5 173.8 64.9 138.1 115.0 151.6 94.1 164.3 61.7  
159.2 146.5 174.5 120.6 191.6 93.5 153.6 143.6 168.1 117.6 184.2 90.7 147.0 140.2 160.7 114.1 175.9 87.7 139.7 136.5 152.4 110.3 166.9 84.4  
163.2 163.2 175.5 141.6 192.7 115.6 158.3 158.3 169.0 138.6 185.2 112.8 152.6 152.6 161.6 135.2 176.4 108.9 146.2 146.2 153.4 131.4 167.5 105.2  
171.5 171.5 176.6 162.9 193.1 136.3 166.4 166.4 170.3 160.0 185.7 133.2 160.5 160.5 163.2 156.7 177.6 129.9 153.9 153.9 155.3 153.1 168.8 126.2  
161.4 131.2 177.3 103.3 192.7 71.7 155.4 128.2 170.5 100.5 184.9 69.0 148.4 124.6 162.7 97.3 176.0 66.0 140.5 120.7 153.1 92.5 166.2 62.7  
162.8 154.7 177.8 125.9 194.8 96.8 157.0 151.7 171.1 122.9 187.1 94.0 150.3 148.2 163.5 119.3 178.6 90.9 142.7 142.7 155.0 115.4 169.3 87.6  
168.7 168.7 178.8 149.0 196.1 121.1 163.6 163.6 172.1 146.0 187.6 117.0 157.5 157.5 164.5 142.5 179.2 113.5 150.7 150.7 156.1 138.7 170.2 109.8  
177.4 177.4 180.4 172.6 196.7 143.2 172.0 172.0 174.0 169.6 188.8 140.0 165.8 165.8 166.8 166.3 180.5 136.6 158.8 158.8 159.0 159.0 171.5 133.0  
164.1 136.9 179.9 107.0 195.0 72.9 157.9 133.8 172.0 103.1 186.9 70.2 150.7 130.2 164.0 99.4 177.8 67.1 142.7 126.1 155.2 95.3 167.7 63.8  
166.0 162.5 180.6 131.1 197.5 99.9 160.1 159.5 173.7 127.9 189.5 97.1 153.2 153.2 165.8 124.3 180.7 94.0 146.4 146.4 157.1 120.4 171.2 90.7  
173.5 173.5 181.6 156.2 198.2 124.8 168.1 168.1 174.8 153.1 190.2 121.5 161.7 161.7 167.0 149.6 181.7 118.0 154.7 154.7 158.5 145.8 172.4 114.2  
182.5 182.5 184.0 182.0 199.6 149.9 176.8 176.8 177.0 177.0 191.5 146.6 170.3 170.3 170.4 170.4 182.9 143.2 163.0 163.0 163.2 163.2 173.7 139.5  
166.3 142.4 181.3 109.2 196.8 74.1 160.0 139.2 174.1 106.0 188.5 71.3 152.7 135.5 165.9 102.2 179.1 68.2 144.5 131.4 156.9 98.0 168.8 64.8  
168.5 168.5 183.0 136.0 199.7 103.0 163.1 163.1 175.9 132.8 191.4 100.0 156.7 156.7 167.8 129.1 182.5 97.0 149.6 149.6 159.0 125.1 172.8 93.6  
177.7 177.7 184.2 163.2 200.7 129.2 172.0 172.0 177.2 160.1 192.4 125.9 165.4 165.4 169.3 156.5 183.7 122.3 158.1 158.1 160.7 152.6 174.3 118.4  
187.1 187.1 187.3 187.3 202.1 156.4 181.0 181.0 181.2 181.2 193.9 153.1 174.2 174.2 174.4 174.4 185.0 149.5 166.8 166.8 167.0 167.0 175.6 145.8  
4500  
5000  
5500  
6000  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-12 Gross Cooling Capacities (kW) TTA155B Condensing Unit withTWE200B Air Handler  
(SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
Airflow  
(°C)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
23.9  
26.7  
29.4  
32.2  
46.3  
46.6  
47.8  
50.2  
47.2  
47.7  
49.4  
51.9  
48.0  
48.6  
50.8  
53.4  
48.7  
49.3  
52.0  
54.8  
36.7 51.0 30.2 55.6 20.7  
42.9 51.1 35.3 56.1 27.4  
47.8 51.4 41.5 56.4 33.9  
50.2 51.7 47.7 56.5 39.9  
38.4 51.9 30.3 56.4 21.0  
45.3 52.1 36.9 57.0 28.3  
49.4 52.4 43.6 57.4 35.4  
51.9 52.8 50.5 57.6 41.9  
40.1 52.7 31.3 57.1 21.3  
47.6 52.9 38.4 57.8 29.3  
50.8 53.2 45.7 58.0 36.5  
53.4 53.9 53.3 58.4 43.9  
41.7 53.1 32.0 57.6 21.7  
49.3 53.6 39.8 58.5 30.1  
52.0 53.9 47.8 58.8 37.8  
54.8 54.8 54.8 59.2 45.8  
44.6  
45.0  
46.4  
48.7  
45.5  
46.0  
47.9  
50.4  
46.2  
46.9  
49.2  
51.8  
46.8  
47.7  
50.4  
53.0  
35.8 49.1 29.4 53.4 19.9 42.7 34.8 46.9 28.5 50.9 19.0 40.4 33.7 44.4 27.6 48.1 18.1  
42.0 49.2 34.4 53.9 26.6 43.1 41.1 47.0 33.4 51.5 25.7 40.9 40.0 44.6 32.3 48.9 24.7  
46.4 49.5 40.6 54.2 33.0 44.7 44.7 47.3 39.6 51.6 31.9 42.8 42.8 44.9 38.5 49.0 30.8  
48.7 49.9 46.8 54.4 39.0 47.0 47.0 47.8 45.9 52.0 38.0 45.1 45.1 45.5 44.8 49.4 37.0  
37.5 49.9 29.4 54.1 20.2 43.4 36.5 47.6 28.5 51.5 19.3 41.1 35.3 44.8 27.1 48.7 18.4  
44.4 50.1 36.0 54.8 27.5 44.0 43.4 47.9 34.9 52.3 26.6 41.8 41.8 45.4 33.8 49.6 25.7  
47.9 50.4 42.7 54.9 34.2 46.1 46.1 48.2 41.7 52.5 33.2 44.1 44.1 45.7 40.6 49.8 32.1  
50.4 50.9 49.7 55.3 41.0 48.5 48.5 48.8 48.7 52.9 40.0 46.5 46.5 46.6 46.6 50.2 38.9  
39.2 50.4 30.2 54.7 20.5 44.1 38.1 48.0 29.1 52.0 19.6 41.8 36.9 45.4 27.9 49.1 18.7  
46.7 50.9 37.5 55.5 28.4 44.9 44.9 48.6 36.4 52.9 27.5 42.9 42.9 46.0 35.2 50.1 26.5  
49.2 51.2 44.8 55.7 35.6 47.4 47.4 48.9 43.8 53.2 34.6 45.3 45.3 46.4 42.7 50.5 33.4  
51.8 51.8 51.8 56.1 42.9 49.9 49.9 49.9 49.9 53.6 41.9 47.7 47.7 47.8 47.8 50.9 40.8  
40.8 51.0 31.0 55.2 20.9 44.7 39.7 48.6 29.9 52.4 20.0 42.3 38.5 45.9 28.7 49.4 19.0  
47.7 51.5 38.9 56.1 29.3 45.9 45.9 49.1 37.8 53.4 28.4 43.8 43.8 46.5 36.6 50.6 27.4  
50.4 51.9 46.9 56.3 36.9 48.4 48.4 49.6 45.8 53.8 35.8 46.3 46.3 47.0 44.7 51.0 34.7  
53.0 53.1 53.1 56.8 44.8 51.0 51.0 51.1 51.1 54.2 43.8 48.8 48.8 48.9 48.9 51.4 42.7  
7646  
8496  
9346  
10195  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
24  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-13 Gross Cooling Capacities (MBh) - Both Compressors -TTA155C Condensing UnitWithTWE155B Air Handler (I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
147.1 118.2 163.0 98.8 180.4 66.6 141.7 115.6 156.9 96.3 173.3 64.1 135.4 112.5 149.9 93.6 165.4 61.4 128.3 109.1 142.1 90.5 156.9 58.5  
147.9 138.6 163.3 113.9 180.5 87.8 142.7 136.0 157.2 111.3 173.4 85.1 136.7 133.1 150.1 108.1 165.5 82.2 130.0 129.8 142.3 104.8 157.1 79.1  
152.6 152.6 163.5 134.0 180.8 108.6 148.0 148.0 157.4 131.3 173.6 106.0 142.7 142.7 150.5 128.3 165.8 103.0 136.7 136.7 142.8 125.0 157.3 99.9  
160.5 160.5 164.5 154.5 180.9 129.2 155.8 155.8 158.6 151.9 173.8 126.4 150.3 150.3 152.0 149.0 166.0 123.3 144.1 144.1 144.3 144.3 157.6 120.1  
150.0 123.9 165.9 96.6 183.5 68.0 144.4 121.2 159.6 94.0 176.1 65.3 137.8 118.1 152.4 91.0 167.8 62.4 130.5 114.6 144.3 87.8 159.1 59.2  
151.2 146.4 166.1 119.0 183.6 90.8 145.9 143.8 159.8 116.3 176.2 88.1 139.4 139.4 152.6 113.2 168.0 85.1 133.2 133.2 144.6 109.8 159.3 82.0  
157.6 157.6 166.5 141.1 183.8 113.6 152.8 152.8 160.2 138.4 176.5 110.9 147.2 147.2 153.1 135.3 168.3 107.9 140.9 140.9 145.2 132.0 159.7 104.8  
165.9 165.9 168.1 163.7 184.0 135.8 160.9 160.9 162.1 161.1 176.7 133.0 155.1 155.1 155.2 155.2 168.6 129.9 148.6 148.6 148.7 148.7 159.9 126.6  
152.4 129.4 168.4 100.0 185.9 69.1 146.6 126.6 161.8 97.3 178.3 66.3 139.9 123.4 154.4 94.3 169.9 63.3 132.5 120.0 146.2 91.0 161.0 60.2  
154.3 153.9 168.6 124.0 186.1 93.7 148.6 148.6 162.0 121.2 178.5 91.0 143.0 143.0 154.7 118.1 170.0 87.9 136.6 136.6 146.5 114.7 161.2 84.8  
162.0 162.0 169.1 147.9 186.4 118.3 156.9 156.9 162.6 145.1 178.8 115.6 151.1 151.1 155.4 142.1 170.2 112.3 144.5 144.5 147.4 138.7 161.4 109.0  
170.7 170.7 170.9 170.9 186.6 142.1 165.3 165.3 165.4 165.4 179.1 139.3 159.2 159.2 159.4 159.4 170.7 136.1 152.5 152.5 152.7 152.7 161.9 132.8  
154.4 134.6 170.5 103.1 188.0 70.0 148.5 131.8 163.7 100.4 180.3 67.2 141.7 128.6 156.1 97.4 171.6 64.2 134.2 125.1 147.7 94.1 162.5 61.0  
157.1 157.1 170.8 128.8 188.2 96.4 152.1 152.1 164.0 126.0 180.4 93.7 146.2 146.2 156.4 122.8 171.8 90.6 139.6 139.6 148.1 119.3 162.8 87.5  
165.9 165.9 171.5 154.6 188.6 122.9 160.6 160.6 164.8 151.7 180.6 119.8 154.5 154.5 157.5 148.6 172.1 116.6 147.7 147.7 149.5 145.3 163.1 113.2  
174.9 174.9 175.1 175.1 188.9 148.3 169.2 169.2 169.4 169.4 181.1 145.4 162.8 162.8 163.0 163.0 172.6 142.2 155.9 155.9 156.1 156.1 163.5 138.9  
4500  
5000  
5500  
6000  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-13 Gross Cooling Capacities (kW) - Both Compressors -TTA155C Condensing UnitWithTWE155B Air Handler (SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
Airflow  
(°C)  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
43.1  
43.3  
44.7  
47.0  
43.9  
44.3  
46.2  
48.6  
44.6  
45.2  
47.4  
50.0  
45.2  
46.0  
48.6  
51.2  
34.6 47.7 28.9 52.8 19.5  
40.6 47.8 33.4 52.8 25.7  
44.7 47.9 39.2 52.9 31.8  
47.0 48.2 45.2 53.0 37.8  
36.3 48.6 28.3 53.7 19.9  
42.9 48.6 34.9 53.7 26.6  
46.2 48.8 41.3 53.8 33.3  
48.6 49.2 47.9 53.9 39.8  
37.9 49.3 29.3 54.4 20.2  
45.1 49.4 36.3 54.5 27.4  
47.4 49.5 43.3 54.6 34.6  
50.0 50.0 50.0 54.6 41.6  
39.4 49.9 30.2 55.1 20.5  
46.0 50.0 37.7 55.1 28.2  
48.6 50.2 45.3 55.2 36.0  
51.2 51.3 51.3 55.3 43.4  
41.5  
41.8  
43.3  
45.6  
42.3  
42.7  
44.7  
47.1  
42.9  
43.5  
46.0  
48.4  
43.5  
44.5  
47.0  
49.6  
33.8 45.9 28.2 50.7 18.8 39.7 32.9 43.9 27.4 48.4 18.0 37.6 31.9 41.6 26.5 45.9 17.1  
39.8 46.0 32.6 50.8 24.9 40.0 39.0 43.9 31.7 48.5 24.1 38.1 38.0 41.7 30.7 46.0 23.2  
43.3 46.1 38.5 50.8 31.0 41.8 41.8 44.1 37.6 48.5 30.2 40.0 40.0 41.8 36.6 46.1 29.3  
45.6 46.4 44.5 50.9 37.0 44.0 44.0 44.5 43.6 48.6 36.1 42.2 42.2 42.3 42.3 46.1 35.2  
35.5 46.7 27.5 51.6 19.1 40.4 34.6 44.6 26.7 49.1 18.3 38.2 33.6 42.3 25.7 46.6 17.3  
42.1 46.8 34.1 51.6 25.8 40.8 40.8 44.7 33.2 49.2 24.9 39.0 39.0 42.3 32.2 46.7 24.0  
44.7 46.9 40.5 51.7 32.5 43.1 43.1 44.8 39.6 49.3 31.6 41.3 41.3 42.5 38.6 46.7 30.7  
47.1 47.5 47.2 51.7 38.9 45.4 45.4 45.4 45.4 49.4 38.0 43.5 43.5 43.6 43.6 46.8 37.1  
37.1 47.4 28.5 52.2 19.4 41.0 36.1 45.2 27.6 49.7 18.5 38.8 35.1 42.8 26.6 47.1 17.6  
43.5 47.4 35.5 52.3 26.6 41.9 41.9 45.3 34.6 49.8 25.7 40.0 40.0 42.9 33.6 47.2 24.8  
46.0 47.6 42.5 52.4 33.8 44.2 44.2 45.5 41.6 49.8 32.9 42.3 42.3 43.2 40.6 47.3 31.9  
48.4 48.4 48.4 52.4 40.8 46.6 46.6 46.7 46.7 50.0 39.9 44.6 44.6 44.7 44.7 47.4 38.9  
38.6 47.9 29.4 52.8 19.7 41.5 37.7 45.7 28.5 50.2 18.8 39.3 36.6 43.3 27.5 47.6 17.9  
44.5 48.0 36.9 52.8 27.4 42.8 42.8 45.8 36.0 50.3 26.5 40.9 40.9 43.4 34.9 47.7 25.6  
47.0 48.3 44.4 52.9 35.1 45.2 45.2 46.1 43.5 50.4 34.1 43.2 43.2 43.8 42.5 47.7 33.2  
49.6 49.6 49.6 53.0 42.6 47.7 47.7 47.7 47.7 50.5 41.6 45.6 45.6 45.7 45.7 47.9 40.7  
7646  
8496  
9346  
10195  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
SS-PRC003-EN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-14 Gross Cooling Capacities (MBh) - Single Compressor -TTA155C Condensing Unit withTWE155B Air Handler (I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
90.4  
96.3  
90.4 99.1 67.0 109.4 42.8  
96.3 99.6 87.3 109.8 62.7  
87.8  
93.4  
99.2  
87.8 95.6 65.6 105.2 41.5 84.6 84.6 91.5 64.0 100.7 40.0 80.9 80.9 87.0 62.2 95.7 38.3  
93.4 96.1 85.9 105.5 61.1 90.1 90.1 92.1 84.3 101.1 59.5 86.2 86.2 87.6 82.5 96.1 57.7  
99.2 99.3 99.3 106.0 81.3 95.7 95.7 95.8 95.8 101.5 79.7 91.7 91.7 91.8 91.8 96.5 77.9  
4500  
5000  
5500  
6000  
102.2 102.2 102.3 102.3 109.9 82.7  
108.3 108.3 108.4 108.4 110.7 103.2 105.1 105.1 105.2 105.2 106.9 101.8 101.4 101.4 101.5 101.5 102.6 100.3 97.3 97.3 97.4 97.4 97.5 97.5  
92.5  
98.6  
92.5 100.2 70.1 110.4 42.7  
98.6 100.8 92.2 110.6 65.1  
89.7  
95.6  
89.7 96.6 68.6 106.2 41.3 86.4 86.4 92.4 67.0 101.5 39.8 82.6 82.6 87.8 65.1 96.5 38.1  
95.6 97.3 90.8 106.6 63.6 92.1 92.1 93.3 89.2 102.0 62.0 88.1 88.1 88.8 87.4 97.0 60.3  
104.7 104.7 104.8 104.8 111.1 87.2 101.6 101.6 101.7 101.7 107.0 85.7 97.9 97.9 98.0 98.0 102.5 84.1 93.8 93.8 93.9 93.9 97.5 82.4  
111.0 111.0 111.1 111.1 112.2 109.7 107.6 107.6 107.7 107.7 108.4 108.3 103.8 103.8 103.9 103.9 104.0 104.0 99.6 99.6 99.7 99.7 99.8 99.8  
94.4  
94.4 101.1 72.9 111.3 43.5  
91.5  
97.5  
91.5 97.5 71.5 107.0 42.1 88.0 88.0 93.2 69.8 102.3 40.6 84.1 84.1 88.5 68.0 97.1 38.9  
97.5 98.4 95.6 107.4 66.1 93.8 93.8 94.4 94.0 102.8 64.5 89.7 89.7 89.8 89.8 97.8 62.7  
100.6 100.6 102.0 97.0 111.5 67.6  
106.9 106.9 107.0 107.0 112.0 91.5 103.6 103.6 103.7 103.7 107.9 90.1 99.8 99.8 99.9 99.9 103.3 88.5 95.6 95.6 95.6 95.6 98.3 86.7  
113.2 113.2 113.4 113.4 113.4 113.4 109.8 109.8 109.9 109.9 110.0 110.0 105.9 105.9 106.0 106.0 106.0 106.0 101.5 101.5 101.6 101.6 101.7 101.7  
96.0  
96.0 101.9 75.7 112.0 44.3  
92.9  
99.1  
92.9 98.2 74.3 107.6 42.9 89.4 89.4 93.9 72.6 102.9 41.3 85.4 85.4 89.1 70.7 97.6 39.7  
99.1 99.1 99.1 108.2 68.5 95.3 95.3 95.4 95.4 103.5 66.8 91.1 91.1 91.2 91.2 98.4 65.1  
102.3 102.3 103.0 101.7 112.4 70.7  
108.7 108.7 108.8 108.8 112.8 95.7 105.3 105.3 105.4 105.4 108.7 94.3 101.4 101.4 101.5 101.5 104.1 92.6 97.1 97.1 97.2 97.2 99.1 90.9  
115.1 115.1 115.2 115.2 115.3 115.3 111.7 111.7 111.8 111.8 111.9 111.9 107.6 107.6 107.7 107.7 107.8 107.8 103.2 103.2 103.3 103.3 103.4 103.4  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-14 Gross Cooling Capacities (kW) - Single Compressor - TTA155C Condensing Unit withTWE155B Air Handler (SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
Airflow  
(°C)  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
26.5  
28.2  
29.9  
31.7  
27.1  
28.9  
30.7  
32.5  
27.6  
29.4  
31.3  
33.2  
28.1  
30.0  
31.8  
33.7  
26.5 29.0 19.6 32.0 12.5  
28.2 29.2 25.6 32.1 18.4  
29.9 30.0 30.0 32.2 24.2  
31.7 31.7 31.7 32.4 30.2  
27.1 29.3 20.5 32.3 12.5  
28.9 29.5 27.0 32.4 19.1  
30.7 30.7 30.7 32.5 25.5  
32.5 32.5 32.5 32.9 32.1  
27.6 29.6 21.4 32.6 12.7  
29.4 29.9 28.4 32.7 19.8  
31.3 31.3 31.3 32.8 26.8  
33.2 33.2 33.2 33.2 33.2  
28.1 29.8 22.2 32.8 13.0  
30.0 30.2 29.8 32.9 20.7  
31.8 31.9 31.9 33.0 28.0  
33.7 33.7 33.7 33.8 33.8  
25.7  
27.4  
29.1  
30.8  
26.3  
28.0  
29.7  
31.5  
26.8  
28.5  
30.3  
32.1  
27.2  
29.0  
30.8  
32.7  
25.7 28.0 19.2 30.8 12.1 24.8 24.8 26.8 18.7 29.5 11.7 23.7 23.7 25.5 18.2 28.0 11.2  
27.4 28.1 25.2 30.9 17.9 26.4 26.4 27.0 24.7 29.6 17.4 25.2 25.2 25.7 24.2 28.2 16.9  
29.1 29.1 29.1 31.0 23.8 28.0 28.0 28.0 28.0 29.7 23.3 26.9 26.9 26.9 26.9 28.3 22.8  
30.8 30.8 30.8 31.3 29.8 29.7 29.7 29.7 29.7 30.0 29.4 28.5 28.5 28.5 28.5 28.6 28.6  
26.3 28.3 20.1 31.1 12.1 25.3 25.3 27.1 19.6 29.7 11.6 24.2 24.2 25.7 19.1 28.2 11.2  
28.0 28.5 26.6 31.2 18.6 27.0 27.0 27.3 26.1 29.9 18.2 25.8 25.8 26.0 25.6 28.4 17.6  
29.7 29.8 29.8 31.3 25.1 28.7 28.7 28.7 28.7 30.0 24.6 27.5 27.5 27.5 27.5 28.5 24.1  
31.5 31.5 31.5 31.7 31.7 30.4 30.4 30.4 30.4 30.5 30.5 29.2 29.2 29.2 29.2 29.2 29.2  
26.8 28.5 20.9 31.3 12.3 25.8 25.8 27.3 20.4 29.9 11.9 24.6 24.6 25.9 19.9 28.4 11.4  
28.5 28.8 28.0 31.5 19.4 27.5 27.5 27.6 27.5 30.1 18.9 26.3 26.3 26.3 26.3 28.6 18.4  
30.3 30.4 30.4 31.6 26.4 29.2 29.2 29.2 29.2 30.3 25.9 28.0 28.0 28.0 28.0 28.8 25.4  
32.1 32.2 32.2 32.2 32.2 31.0 31.0 31.0 31.0 31.0 31.0 29.7 29.7 29.8 29.8 29.8 29.8  
27.2 28.7 21.7 31.5 12.5 26.2 26.2 27.5 21.3 30.1 12.1 25.0 25.0 26.1 20.7 28.6 11.6  
29.0 29.0 29.0 31.7 20.1 27.9 27.9 27.9 27.9 30.3 19.6 26.7 26.7 26.7 26.7 28.8 19.0  
30.8 30.9 30.9 31.8 27.6 29.7 29.7 29.7 29.7 30.5 27.1 28.4 28.4 28.5 28.5 29.0 26.6  
32.7 32.7 32.7 32.8 32.8 31.5 31.5 31.5 31.5 31.6 31.6 30.2 30.2 30.2 30.2 30.3 30.3  
7646  
8496  
9346  
10195  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
26  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
System  
Table PD-15 Gross Cooling Capacities (MBh) TTA200B Condensing Unit withTWE200B Air Handler  
(I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (°F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(°F)  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
201.0 158.5 221.1 132.8 242.4 89.9 193.1 154.4 212.5 129.3 232.6 86.5 184.9 150.2 203.5 125.7 222.1 83.0 176.4 145.8 194.2 122.0 211.7 79.5  
202.2 184.9 221.6 152.5 243.5 118.4 194.5 180.9 213.1 148.6 234.1 114.8 186.6 176.8 204.3 144.5 224.2 111.1 178.4 172.6 195.1 140.3 214.1 107.4  
206.7 206.7 222.8 178.8 244.6 146.0 200.1 200.1 214.3 174.8 235.3 142.4 193.3 193.3 205.5 170.7 225.5 138.8 186.1 186.1 196.4 166.6 215.5 135.1  
217.1 217.1 224.1 205.3 245.0 172.1 210.4 210.4 215.9 201.5 235.7 168.2 203.4 203.4 207.3 197.5 226.1 164.2 196.1 196.1 198.7 193.5 216.2 160.2  
204.9 165.7 225.2 130.5 246.0 91.4 196.8 161.6 216.3 126.8 235.8 87.9 188.4 157.3 207.0 123.0 225.4 84.3 179.6 152.9 197.4 119.1 214.5 80.7  
206.6 194.8 225.8 159.1 247.6 122.3 198.8 190.8 217.0 155.1 237.8 118.8 190.7 186.6 207.9 150.9 227.7 115.1 182.5 182.4 198.5 146.6 217.2 111.3  
213.4 213.4 227.0 187.8 248.8 152.5 206.6 206.6 218.2 183.8 239.1 148.9 199.4 199.4 209.1 179.7 228.3 143.9 191.9 191.9 199.8 175.5 218.1 139.7  
224.4 224.4 228.9 217.1 249.3 180.5 217.3 217.3 220.5 213.2 239.7 176.6 210.0 210.0 211.9 209.2 229.8 172.5 202.3 202.3 202.5 202.5 219.6 168.4  
208.3 172.6 228.5 134.9 248.9 93.0 200.0 168.4 219.3 131.2 238.5 89.5 191.3 164.0 209.8 127.3 227.8 85.8 182.3 159.5 199.1 121.9 216.7 82.0  
210.6 204.3 229.3 165.4 250.9 126.1 202.7 200.3 220.3 161.3 240.9 122.5 193.9 193.9 210.9 157.0 230.5 118.8 186.3 186.3 201.3 152.7 219.8 115.0  
219.4 219.4 230.5 196.5 251.4 157.5 212.2 212.2 221.6 192.5 241.6 153.5 204.7 204.7 212.3 188.3 231.4 149.4 197.0 197.0 202.9 184.0 220.9 145.1  
230.7 230.7 233.3 228.5 252.9 188.5 223.3 223.3 224.9 224.6 243.1 184.5 215.7 215.7 215.9 215.9 232.9 180.4 207.7 207.7 207.9 207.9 222.4 176.2  
211.2 179.2 231.3 139.1 251.4 94.4 202.6 174.9 221.0 134.2 240.8 90.7 193.8 170.5 211.3 129.8 229.8 86.9 184.7 166.0 201.4 125.3 218.4 83.1  
214.3 213.5 232.3 171.4 253.7 129.7 205.8 205.8 223.1 167.2 243.4 126.1 198.3 198.3 213.5 162.9 232.8 122.4 190.4 190.4 203.7 158.5 221.9 118.6  
224.6 224.6 233.7 204.9 254.5 162.9 217.2 217.2 224.6 200.8 244.4 158.8 209.4 209.4 215.2 196.6 234.0 154.6 201.4 201.4 205.6 192.3 223.3 150.3  
236.3 236.3 236.5 236.5 256.0 196.3 228.6 228.6 228.8 228.8 245.9 192.2 220.7 220.7 220.9 220.9 235.5 188.1 212.4 212.4 212.6 212.6 224.8 183.8  
6000  
6675  
7350  
8025  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
Table PD-15 Gross Cooling Capacities (MBh) TTA200B Condensing Unit withTWE200B Air Handler  
(SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°C)  
22.8 16.1  
m3/h  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
Airflow  
(°C)  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
24  
27  
29  
32  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
58.8  
59.2  
60.5  
63.6  
60.0  
60.5  
62.5  
65.7  
61.0  
61.7  
64.2  
67.5  
61.8  
62.7  
65.8  
69.2  
46.4 64.7 38.9 71.0 26.3  
54.1 64.9 44.7 71.3 34.7  
60.5 65.2 52.3 71.6 42.7  
63.6 65.6 60.1 71.7 50.4  
48.5 65.9 38.2 72.0 26.8  
57.0 66.1 46.6 72.5 35.8  
62.5 66.5 55.0 72.8 44.6  
65.7 67.0 63.6 73.0 52.8  
50.5 66.9 39.5 72.9 27.2  
59.8 67.1 48.4 73.5 36.9  
64.2 67.5 57.5 73.6 46.1  
67.5 68.3 66.9 74.1 55.2  
52.5 67.7 40.7 73.6 27.6  
62.5 68.0 50.2 74.3 38.0  
65.8 68.4 60.0 74.5 47.7  
69.2 69.2 69.2 74.9 57.5  
56.5  
57.0  
58.6  
61.6  
57.6  
58.2  
60.5  
63.6  
58.5  
59.3  
62.1  
65.4  
59.3  
60.3  
63.6  
66.9  
45.2 62.2 37.9 68.1 25.3 54.1 44.0 59.6 36.8 65.0 24.3 51.6 42.7 56.9 35.7 62.0 23.3  
53.0 62.4 43.5 68.5 33.6 54.6 51.8 59.8 42.3 65.7 32.5 52.2 50.5 57.1 41.1 62.7 31.5  
58.6 62.7 51.2 68.9 41.7 56.6 56.6 60.2 50.0 66.0 40.6 54.5 54.5 57.5 48.8 63.1 39.6  
61.6 63.2 59.0 69.0 49.3 59.6 59.6 60.7 57.8 66.2 48.1 57.4 57.4 58.2 56.7 63.3 46.9  
47.3 63.3 37.1 69.0 25.7 55.2 46.1 60.6 36.0 66.0 24.7 52.6 44.8 57.8 34.9 62.8 23.6  
55.9 63.5 45.4 69.6 34.8 55.8 54.6 60.9 44.2 66.7 33.7 53.4 53.4 58.1 42.9 63.6 32.6  
60.5 63.9 53.8 70.0 43.6 58.4 58.4 61.2 52.6 66.8 42.1 56.2 56.2 58.5 51.4 63.9 40.9  
63.6 64.6 62.4 70.2 51.7 61.5 61.5 62.0 61.3 67.3 50.5 59.2 59.2 59.3 59.3 64.3 49.3  
49.3 64.2 38.4 69.8 26.2 56.0 48.0 61.4 37.3 66.7 25.1 53.4 46.7 58.3 35.7 63.4 24.0  
58.6 64.5 47.2 70.5 35.9 56.8 56.8 61.8 46.0 67.5 34.8 54.5 54.5 58.9 44.7 64.4 33.7  
62.1 64.9 56.4 70.7 44.9 59.9 59.9 62.2 55.1 67.8 43.7 57.7 57.7 59.4 53.9 64.7 42.5  
65.4 65.8 65.8 71.2 54.0 63.1 63.1 63.2 63.2 68.2 52.8 60.8 60.8 60.9 60.9 65.1 51.6  
51.2 64.7 39.3 70.5 26.6 56.7 49.9 61.9 38.0 67.3 25.5 54.1 48.6 59.0 36.7 63.9 24.3  
60.3 65.3 49.0 71.3 36.9 58.1 58.1 62.5 47.7 68.2 35.8 55.8 55.8 59.6 46.4 65.0 34.7  
63.6 65.8 58.8 71.6 46.5 61.3 61.3 63.0 57.6 68.5 45.3 59.0 59.0 60.2 56.3 65.4 44.0  
66.9 67.0 67.0 72.0 56.3 64.6 64.6 64.7 64.7 69.0 55.1 62.2 62.2 62.2 62.2 65.8 53.8  
10195  
11340  
12488  
13633  
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
All capacities shown are gross and have not considered indoor fan heat.  
To obtain net cooling capacities subtract indoor fan heat.  
TGC = Total Gross Cooling Capacity  
SHC = Sensible Heat Capacity  
SS-PRC003-EN  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Condensing Unit  
Table PD-16 Cooling Performance (MBh) TTA075A Condensing Unit Only  
(I-P)  
ODTemp  
°F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
175  
69.1  
5.01  
181  
76.2  
5.13  
188  
83.6  
5.27  
195  
91.2  
5.40  
202  
99.0  
5.55  
210  
106.9  
5.70  
65  
75  
Head press psig  
Cap. Btu/1000  
OD Unit KW  
202  
66.9  
5.54  
209  
73.7  
5.68  
216  
80.7  
5.82  
223  
87.9  
5.97  
231  
95.3  
6.12  
239  
102.8  
6.28  
Head press psig  
Cap. Btu/1000  
OD Unit KW  
232  
64.1  
6.16  
239  
70.6  
6.31  
247  
77.3  
6.46  
254  
84.1  
6.61  
262  
91.1  
6.77  
270  
98.2  
6.94  
85  
Head press psig  
Cap. Btuh/1000  
OD Unit KW  
264  
60.8  
6.86  
272  
66.9  
7.02  
280  
73.2  
7.17  
288  
79.7  
7.33  
296  
86.3  
7.49  
304  
93.1  
7.66  
95  
Head press psig  
Cap. Btuh/1000  
OD Unit KW  
299  
57.0  
7.65  
307  
62.7  
7.80  
315  
68.7  
7.95  
323  
74.8  
8.11  
332  
81.1  
8.27  
341  
87.6  
8.45  
105  
115  
Head press psig  
Cap. Btuh/1000  
OD Unit KW  
335  
52.8  
8.51  
344  
58.2  
8.65  
352  
63.7  
8.80  
361  
69.5  
8.95  
370  
75.5  
9.12  
380  
81.8  
9.29  
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.  
Table PD-16 Cooling Performance (kW) TTA075A Condensing Unit Only  
(SI)  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1208  
20.2  
5.01  
1251  
22.3  
5.13  
1297  
24.5  
5.27  
1345  
26.7  
5.40  
1395  
29.0  
5.55  
1446  
31.3  
5.70  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1396  
19.6  
5.54  
1442  
21.6  
5.68  
1491  
23.6  
5.82  
1541  
25.7  
5.97  
1593  
27.9  
6.12  
1647  
30.1  
6.28  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1600  
18.8  
6.16  
1650  
20.7  
6.31  
1701  
22.6  
6.46  
1754  
24.6  
6.61  
1808  
26.7  
6.77  
1865  
28.7  
6.94  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1822  
17.8  
6.86  
1874  
19.6  
7.02  
1927  
21.4  
7.17  
1983  
23.3  
7.33  
2040  
25.3  
7.49  
2099  
27.3  
7.66  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
2059  
16.7  
7.65  
2114  
18.4  
7.80  
2170  
20.1  
7.95  
2227  
21.9  
8.11  
2287  
23.7  
8.27  
2350  
25.7  
8.45  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
2313  
15.5  
8.51  
2369  
17.0  
8.65  
2428  
18.7  
8.80  
2488  
20.4  
8.95  
2551  
22.1  
9.12  
2617  
24.0  
9.29  
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.  
28  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Condensing Unit  
Table PD-17 Cooling Performance (MBh) TTA085A Condensing Unit Only  
(I-P)  
ODTemp  
°F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
160  
79.8  
5.64  
164  
88.0  
5.73  
169  
96.6  
5.83  
173  
105.7  
5.93  
178  
115.1  
6.04  
184  
124.9  
6.15  
65  
75  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
185  
76.4  
6.14  
189  
84.1  
6.23  
194  
92.3  
6.33  
199  
100.8  
6.44  
204  
109.8  
6.56  
209  
119.2  
6.68  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
212  
72.6  
6.73  
217  
80.0  
6.83  
222  
87.7  
6.94  
227  
96.0  
7.06  
232  
104.6  
7.18  
238  
113.6  
7.31  
85  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
242  
68.6  
7.43  
247  
75.7  
7.55  
252  
83.1  
7.67  
258  
91.0  
7.79  
264  
99.3  
7.92  
270  
107.9  
8.05  
95  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
275  
64.4  
8.24  
280  
71.2  
8.36  
286  
78.4  
8.49  
292  
86.0  
8.62  
298  
94.0  
8.76  
304  
102.3  
8.89  
105  
115  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
311  
60.0  
9.15  
317  
66.6  
9.28  
323  
73.6  
9.42  
329  
80.9  
9.56  
335  
88.6  
9.70  
342  
96.5  
9.83  
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.  
Table PD-17 Cooling Performance (kW) TTA085A Condensing Unit Only  
(SI)  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1102  
23.4  
5.64  
1132  
25.8  
5.73  
1163  
28.3  
5.83  
1196  
30.9  
5.93  
1230  
33.7  
6.04  
1266  
36.6  
6.15  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1273  
22.4  
6.14  
1304  
24.6  
6.23  
1337  
27.0  
6.33  
1371  
29.5  
6.44  
1407  
32.2  
6.56  
1444  
34.9  
6.68  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1462  
21.3  
6.73  
1494  
23.4  
6.83  
1529  
25.7  
6.94  
1565  
28.1  
7.06  
1603  
30.6  
7.18  
1642  
33.3  
7.31  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1669  
20.1  
7.43  
1704  
22.2  
7.55  
1741  
24.3  
7.67  
1779  
26.6  
7.79  
1819  
29.1  
7.92  
1860  
31.6  
8.05  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1896  
18.9  
8.24  
1934  
20.9  
8.36  
1973  
23.0  
8.49  
2013  
25.2  
8.62  
2055  
27.5  
8.76  
2099  
29.9  
8.89  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
2142  
17.6  
9.15  
2184  
19.5  
9.28  
2225  
21.6  
9.42  
2269  
23.7  
9.56  
2313  
25.9  
9.70  
2358  
28.3  
9.83  
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.  
SS-PRC003-EN  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Condensing Unit  
Table PD-18 Cooling Performance (MBh) TTA100A Condensing Unit Only  
(I-P)  
ODTemp  
°F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
174  
95.7  
6.69  
180  
105.0  
6.84  
186  
114.7  
7.01  
193  
124.8  
7.19  
199  
135.3  
7.37  
207  
146.1  
7.58  
65  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
200  
91.2  
7.38  
206  
99.9  
7.54  
212  
109.1  
7.72  
219  
118.7  
7.91  
226  
128.8  
8.12  
234  
139.2  
8.34  
75  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
228  
86.4  
8.19  
234  
94.7  
8.37  
241  
103.5  
8.57  
248  
112.7  
8.77  
256  
122.3  
8.99  
264  
132.2  
9.22  
85  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
259  
81.3  
9.13  
265  
89.3  
9.33  
273  
97.8  
9.54  
280  
106.6  
9.76  
288  
115.8  
9.99  
297  
125.2  
10.23  
95  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
292  
76.1  
10.19  
299  
83.8  
10.41  
307  
91.9  
10.64  
315  
100.4  
10.88  
324  
109.2  
11.12  
332  
118.3  
11.36  
105  
115  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
328  
70.7  
11.37  
336  
78.2  
11.61  
344  
86.0  
11.86  
353  
94.2  
12.11  
362  
102.6  
12.36  
371  
111.3  
12.60  
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.  
Table PD-18 Cooling Performance (kW) TTA100A Condensing Unit Only  
(SI)  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1200  
28.0  
6.69  
1240  
30.7  
6.84  
1283  
33.6  
7.01  
1327  
36.5  
7.19  
1375  
39.6  
7.37  
1425  
42.8  
7.58  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1377  
26.7  
7.38  
1418  
29.3  
7.54  
1462  
32.0  
7.72  
1509  
34.8  
7.91  
1559  
37.7  
8.12  
1612  
40.7  
8.34  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1571  
25.3  
8.19  
1615  
27.7  
8.37  
1662  
30.3  
8.57  
1711  
33.0  
8.77  
1763  
35.8  
8.99  
1819  
38.7  
9.22  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1783  
23.8  
9.13  
1830  
26.2  
9.33  
1880  
28.6  
9.54  
1932  
31.2  
9.76  
1987  
33.9  
9.99  
2045  
36.7  
10.23  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
2014  
22.3  
10.19  
2064  
24.5  
10.41  
2117  
26.9  
10.64  
2173  
29.4  
10.88  
2231  
32.0  
11.12  
2292  
34.6  
11.36  
Head pressure (kPA)  
Capacity (kW)  
2263  
20.7  
2318  
22.9  
2375  
25.2  
2434  
27.6  
2495  
30.1  
2559  
32.6  
OD Unit Power (kW)  
11.37  
11.61  
11.86  
12.11  
12.36  
12.60  
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.  
30  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Condensing Unit  
Table PD-19 Cooling Performance (MBh) TTA100B Condensing Unit Only  
(I-P)  
ODTemp  
°F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
172  
93.8  
7.46  
178  
103.2  
7.69  
184  
113.0  
7.90  
191  
123.2  
8.11  
198  
133.8  
8.32  
205  
144.7  
8.52  
65  
75  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
197  
88.4  
8.00  
203  
97.4  
8.27  
210  
106.7  
8.54  
217  
116.4  
8.79  
224  
126.5  
9.05  
232  
136.9  
9.31  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
224  
82.8  
8.50  
231  
91.3  
8.82  
238  
100.2  
9.13  
246  
109.4  
9.44  
253  
118.9  
9.75  
261  
128.8  
10.07  
85  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
254  
77.0  
8.94  
261  
85.0  
9.31  
268  
93.4  
9.68  
276  
102.1  
10.05  
284  
111.1  
10.43  
293  
120.4  
10.81  
95  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
285  
71.0  
9.32  
293  
78.5  
9.76  
301  
86.4  
10.19  
309  
94.6  
10.63  
317  
103.1  
11.07  
326  
111.8  
11.52  
105  
115  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
319  
64.9  
9.66  
327  
72.0  
10.16  
335  
79.3  
10.66  
344  
87.0  
11.17  
353  
94.9  
11.68  
362  
103.1  
12.21  
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.  
Table PD-19 Cooling Performance (kW) TTA100B Condensing Unit Only  
(SI)  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1186  
27.5  
7.46  
1227  
30.2  
7.69  
1270  
33.1  
7.90  
1315  
36.1  
8.11  
1362  
39.2  
8.32  
1412  
42.4  
8.52  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1359  
25.9  
8.00  
1403  
28.5  
8.27  
1449  
31.3  
8.54  
1497  
34.1  
8.79  
1547  
37.0  
9.05  
1600  
40.1  
9.31  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1546  
24.2  
8.50  
1593  
26.7  
8.82  
1642  
29.3  
9.13  
1693  
32.0  
9.44  
1746  
34.8  
9.75  
1802  
37.7  
10.07  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1749  
22.5  
8.94  
1799  
24.9  
9.31  
1850  
27.3  
9.68  
1904  
29.9  
10.05  
1960  
32.5  
10.43  
2019  
35.2  
10.81  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1967  
20.8  
9.32  
2019  
23.0  
9.76  
2073  
25.3  
10.19  
2130  
27.7  
10.63  
2188  
30.2  
11.07  
2249  
32.7  
11.52  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
2200  
19.0  
9.66  
2255  
21.1  
10.16  
2312  
23.2  
10.66  
2371  
25.5  
11.17  
2431  
27.8  
11.68  
2494  
30.2  
12.21  
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.  
SS-PRC003-EN  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Condensing Unit  
Table PD-20 Gross Cooling Capacities (MBh) - Both Compressors - (I-P)  
TTA100C Condensing Unit Only  
ODTemp  
°F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
147.0  
95.6  
5.6  
152.8  
105.6  
5.8  
158.9  
116.2  
5.9  
165.3  
127.2  
6.1  
172.1  
138.7  
6.3  
179.4  
150.7  
6.4  
65  
75  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
169.9  
90.8  
6.2  
175.8  
100.4  
6.3  
182.2  
110.4  
6.5  
188.9  
121.0  
6.7  
196.0  
132.1  
6.8  
203.6  
143.6  
7.0  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
195.0  
85.7  
6.8  
201.2  
94.8  
7.0  
207.8  
104.5  
7.2  
214.9  
114.6  
7.3  
222.3  
125.2  
7.5  
230.3  
136.3  
7.7  
85  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
222.5  
80.4  
7.6  
229.0  
89.1  
7.8  
236.0  
98.3  
7.9  
243.4  
108.0  
8.1  
251.2  
118.2  
8.3  
259.5  
128.8  
8.5  
95  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
252.5  
74.8  
8.5  
259.3  
83.1  
8.6  
266.6  
92.0  
8.8  
274.4  
101.3  
9.0  
282.6  
111.1  
9.2  
291.3  
121.3  
9.4  
105  
115  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
284.9  
69.0  
9.4  
292.1  
77.0  
9.6  
299.8  
85.5  
9.8  
307.9  
94.5  
10.0  
316.6  
103.8  
10.2  
325.7  
113.6  
10.4  
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.  
Table PD-20 Gross Cooling Capacities (kW) - Both Compressors - (SI)  
TTA100C Condensing Unit Only  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
1014  
28.0  
5.59  
1054  
30.9  
5.76  
1095  
34.0  
5.93  
1140  
37.2  
6.09  
1187  
40.6  
6.27  
1237  
44.1  
6.45  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1171  
26.6  
6.17  
1212  
29.4  
6.33  
1256  
32.3  
6.50  
1302  
35.4  
6.67  
1351  
38.7  
6.85  
1404  
42.0  
7.04  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1345  
25.1  
6.85  
1388  
27.8  
7.00  
1433  
30.6  
7.17  
1482  
33.6  
7.35  
1533  
36.7  
7.53  
1588  
39.9  
7.74  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1534  
23.5  
7.62  
1579  
26.1  
7.78  
1627  
28.8  
7.95  
1678  
31.6  
8.13  
1732  
34.6  
8.32  
1789  
37.7  
8.53  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1741  
21.9  
8.49  
1788  
24.3  
8.65  
1838  
26.9  
8.82  
1892  
29.7  
9.01  
1949  
32.5  
9.22  
2009  
35.5  
9.43  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1964  
20.2  
9.44  
2014  
22.5  
9.61  
2067  
25.0  
9.79  
2123  
27.7  
9.99  
2183  
30.4  
10.20  
2246  
33.3  
10.43  
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.  
32  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Condensing Unit  
Table PD-21 Gross Cooling Capacities (MBh) - Single Compressor - (I-P)  
TTA100C Condensing Unit Only  
ODTemp  
°F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
119.4  
52.0  
2.9  
122.4  
58.0  
3.0  
125.5  
64.3  
3.1  
128.8  
70.8  
3.1  
132.2  
77.6  
3.2  
135.8  
84.7  
3.2  
65  
75  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
140.4  
49.6  
3.2  
143.6  
55.3  
3.2  
146.8  
61.3  
3.3  
150.3  
67.6  
3.3  
153.9  
74.1  
3.4  
157.6  
80.9  
3.4  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
163.7  
47.1  
3.4  
167.0  
52.4  
3.5  
170.5  
58.1  
3.5  
174.1  
64.1  
3.6  
177.9  
70.4  
3.6  
181.9  
77.0  
3.7  
85  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
189.5  
44.3  
3.8  
192.9  
49.4  
3.8  
196.5  
54.8  
3.9  
200.4  
60.5  
3.9  
204.4  
66.6  
4.0  
208.7  
72.9  
4.0  
95  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
217.7  
41.4  
4.2  
221.3  
46.2  
4.2  
225.2  
51.4  
4.2  
229.2  
56.8  
4.3  
233.5  
62.6  
4.3  
238.0  
68.7  
4.4  
105  
115  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
248.5  
38.3  
4.6  
252.4  
42.9  
4.6  
256.4  
47.8  
4.7  
260.7  
53.0  
4.7  
265.3  
58.5  
4.8  
270.0  
64.3  
4.8  
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.  
Table PD-21 Gross Cooling Capacities (kW) - Single Compressor - (SI)  
TTA100C Condensing Unit Only  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
823  
15.2  
2.95  
844  
17.0  
3.01  
866  
18.8  
3.06  
888  
20.7  
3.12  
912  
22.7  
3.17  
936  
24.8  
3.21  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
968  
14.5  
3.17  
990  
16.2  
3.22  
1012  
18.0  
3.27  
1036  
19.8  
3.32  
1061  
21.7  
3.37  
1087  
23.7  
3.42  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1129  
13.8  
3.45  
1151  
15.3  
3.49  
1175  
17.0  
3.54  
1200  
18.8  
3.59  
1227  
20.6  
3.64  
1254  
22.5  
3.69  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1306  
13.0  
3.78  
1330  
14.5  
3.82  
1355  
16.0  
3.86  
1381  
17.7  
3.91  
1409  
19.5  
3.96  
1439  
21.3  
4.01  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1501  
12.1  
4.16  
1526  
13.5  
4.20  
1552  
15.0  
4.24  
1580  
16.6  
4.29  
1610  
18.3  
4.34  
1641  
20.1  
4.39  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1714  
11.2  
4.60  
1740  
12.6  
4.63  
1768  
14.0  
4.67  
1798  
15.5  
4.72  
1829  
17.1  
4.77  
1862  
18.8  
4.82  
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.  
SS-PRC003-EN  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Condensing Unit  
Table PD-22 Cooling Performance (MBh) TTA125B Condensing Unit Only  
(I-P)  
ODTemp  
°F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
169  
115.6  
8.89  
174  
127.1  
9.17  
180  
139.1  
9.43  
186  
151.6  
9.70  
193  
164.5  
9.96  
199  
177.9  
10.23  
65  
75  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
194  
109.1  
9.43  
200  
120.1  
9.77  
206  
131.6  
10.10  
212  
143.5  
10.43  
219  
155.9  
10.76  
227  
168.6  
11.10  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
221  
102.5  
9.98  
227  
112.9  
10.37  
234  
123.9  
10.77  
241  
135.2  
11.17  
248  
146.9  
11.58  
256  
159.0  
11.99  
85  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
250  
95.7  
10.52  
257  
105.6  
10.98  
264  
115.9  
11.45  
272  
126.6  
11.92  
280  
137.7  
12.41  
288  
149.1  
12.90  
95  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
282  
88.7  
11.06  
290  
98.1  
11.59  
297  
107.8  
12.14  
305  
117.8  
12.69  
313  
128.2  
13.25  
321  
138.9  
13.83  
105  
115  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
317  
81.7  
11.59  
324  
90.4  
12.21  
332  
99.5  
12.83  
340  
108.9  
13.47  
349  
118.6  
14.11  
358  
128.6  
14.78  
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.  
Table PD-22 Cooling Performance (kW) TTA125B Condensing Unit Only  
(SI)  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1163  
33.9  
8.89  
1201  
37.2  
9.17  
1241  
40.7  
9.43  
1283  
44.4  
9.70  
1327  
48.2  
9.96  
1374  
52.1  
10.23  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1335  
32.0  
9.43  
1377  
35.2  
9.77  
1420  
38.5  
10.10  
1465  
42.0  
10.43  
1512  
45.6  
10.76  
1562  
49.4  
11.10  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1523  
30.0  
9.98  
1568  
33.1  
10.37  
1614  
36.3  
10.77  
1662  
39.6  
11.17  
1712  
43.0  
11.58  
1765  
46.6  
11.99  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1727  
28.0  
10.52  
1774  
30.9  
10.98  
1823  
33.9  
11.45  
1874  
37.1  
11.92  
1928  
40.3  
12.41  
1983  
43.7  
12.90  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1947  
26.0  
11.06  
1997  
28.7  
11.59  
2049  
31.6  
12.14  
2103  
34.5  
12.69  
2159  
37.5  
13.25  
2217  
40.7  
13.83  
Head pressure (kPA)  
Capacity (kW)  
2185  
23.9  
2237  
26.5  
2291  
29.1  
2347  
31.9  
2405  
34.7  
2465  
37.7  
OD Unit Power (kW)  
11.59  
12.21  
12.83  
13.47  
14.11  
14.78  
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.  
34  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Condensing Unit  
Table PD-23 Cooling Performance (MBh) TTA155B Condensing Unit Only  
(I-P)  
ODTemp  
°F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
173  
140.3  
9.95  
179  
154.9  
10.20  
186  
170.1  
10.48  
194  
185.9  
10.78  
201  
202.2  
11.10  
209  
218.8  
11.43  
65  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
200  
136.0  
11.00  
206  
150.0  
11.28  
214  
164.4  
11.58  
221  
179.3  
11.90  
229  
194.6  
12.23  
238  
210.3  
12.58  
75  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
228  
130.4  
12.22  
236  
143.6  
12.52  
243  
157.3  
12.84  
251  
171.4  
13.17  
259  
185.9  
13.51  
268  
200.7  
13.87  
85  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
259  
123.6  
13.60  
267  
136.1  
13.92  
275  
149.0  
14.24  
283  
162.4  
14.58  
292  
176.1  
14.92  
301  
190.2  
15.29  
95  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
293  
115.9  
15.15  
301  
127.6  
15.46  
309  
139.8  
15.78  
317  
152.3  
16.11  
326  
165.3  
16.46  
336  
178.8  
16.84  
105  
115  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
328  
107.4  
16.84  
336  
118.3  
17.13  
345  
129.7  
17.44  
354  
141.5  
17.77  
363  
153.9  
18.12  
373  
166.8  
18.50  
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.  
Table PD-23 Cooling Performance (kW) TTA155B Condensing Unit Only  
(SI)  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1192  
41.1  
9.95  
1238  
45.4  
10.20  
1285  
49.8  
10.48  
1336  
54.4  
10.78  
1389  
59.2  
11.10  
1444  
64.1  
11.43  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1376  
39.8  
11.00  
1424  
43.9  
11.28  
1474  
48.1  
11.58  
1526  
52.5  
11.90  
1581  
57.0  
12.23  
1638  
61.6  
12.58  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1575  
38.2  
12.22  
1625  
42.1  
12.52  
1677  
46.1  
12.84  
1732  
50.2  
13.17  
1788  
54.4  
13.51  
1848  
58.8  
13.87  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1789  
36.2  
13.60  
1841  
39.9  
13.92  
1896  
43.6  
14.24  
1952  
47.5  
14.58  
2012  
51.6  
14.92  
2073  
55.7  
15.29  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
2018  
33.9  
15.15  
2073  
37.4  
15.46  
2130  
40.9  
15.78  
2188  
44.6  
16.11  
2250  
48.4  
16.46  
2315  
52.4  
16.84  
Head pressure (kPA)  
Capacity (kW)  
2263  
31.4  
2320  
34.6  
2379  
38.0  
2440  
41.4  
2504  
45.1  
2571  
48.8  
OD Unit Power (kW)  
16.84  
17.13  
17.44  
17.77  
18.12  
18.50  
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.  
SS-PRC003-EN  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Condensing Unit  
Table PD-24 Gross Cooling Capacities (MBh) - Both Compressors - (I-P)  
TTA155C Condensing Unit Only  
ODTemp  
°F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press. PSIG  
Cap. Btuh/1000  
OD Unit KW  
164.9  
132.3  
9.3  
170.4  
146.2  
9.5  
176.3  
160.9  
9.7  
182.6  
176.2  
10.0  
189.2  
192.1  
10.2  
196.0  
208.5  
10.5  
65  
Head press. PSIG  
Cap. Btuh/1000  
OD Unit KW  
191.3  
128.5  
10.3  
197.3  
142.0  
10.5  
203.6  
156.0  
10.7  
210.3  
170.6  
11.0  
217.2  
185.6  
11.3  
224.4  
201.0  
11.6  
75  
Head press. PSIG  
Cap. Btuh/1000  
OD Unit KW  
220.1  
123.5  
11.4  
226.5  
136.4  
11.7  
233.2  
149.7  
11.9  
240.2  
163.5  
12.2  
247.4  
177.7  
12.5  
255.0  
192.3  
12.8  
85  
Head press. PSIG  
Cap. Btuh/1000  
OD Unit KW  
251.1  
117.4  
12.7  
257.9  
129.6  
13.0  
265.0  
142.2  
13.3  
272.4  
155.3  
13.6  
280.0  
168.7  
13.9  
287.9  
182.6  
14.2  
95  
Head press. PSIG  
Cap. Btuh/1000  
OD Unit KW  
284.5  
110.4  
14.2  
291.7  
121.9  
14.5  
299.1  
133.8  
14.8  
306.8  
146.1  
15.0  
314.8  
158.8  
15.3  
323.2  
172.0  
15.7  
105  
115  
Head press. PSIG  
Cap. Btuh/1000  
OD Unit KW  
320.2  
102.7  
15.8  
327.7  
113.4  
16.1  
335.4  
124.5  
16.4  
343.4  
136.1  
16.6  
351.8  
148.1  
16.9  
360.6  
160.7  
17.3  
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.  
Table PD-24 Gross Cooling Capacities (kW) - Both Compressors - (SI)  
TTA155C Condensing Unit Only  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
1137  
38.7  
9.30  
1175  
42.8  
9.50  
1216  
47.1  
1259  
51.6  
9.96  
1304  
56.2  
1352  
61.0  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
OD Unit Power (kW)  
9.72  
10.22  
10.49  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1319  
37.6  
10.27  
1361  
41.6  
10.50  
1404  
45.7  
10.75  
1450  
49.9  
11.01  
1497  
54.3  
11.29  
1547  
58.9  
11.58  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1517  
36.2  
11.41  
1562  
39.9  
11.67  
1608  
43.8  
11.94  
1656  
47.9  
12.22  
1706  
52.0  
12.51  
1758  
56.3  
12.81  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1731  
34.4  
12.73  
1778  
38.0  
13.00  
1827  
41.6  
13.28  
1878  
45.5  
13.56  
1930  
49.4  
13.86  
1985  
53.5  
14.17  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1962  
32.3  
14.21  
2011  
35.7  
14.48  
2062  
39.2  
14.76  
2115  
42.8  
15.04  
2170  
46.5  
15.34  
2228  
50.4  
15.66  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
2208  
30.1  
15.84  
2259  
33.2  
16.10  
2313  
36.5  
16.36  
2368  
39.8  
16.64  
2426  
43.4  
16.94  
2487  
47.1  
17.26  
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.  
36  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Condensing Unit  
Table PD-25 Cooling Performance (MBh) - Single Compressor - (I-P)  
TTA155C Condensing Unit Only  
ODTemp  
Suction ReferenceTemperature °F  
°F  
30  
35  
40  
45  
50  
55  
Head press. PSIG  
Cap. Btuh/1000  
OD Unit KW  
137.1  
67.8  
4.8  
139.8  
75.1  
4.8  
142.6  
82.9  
4.8  
145.7  
91.3  
4.9  
149.0  
100.1  
5.0  
152.4  
109.4  
5.0  
65  
Head press. PSIG  
Cap. Btuh/1000  
OD Unit KW  
161.2  
66.9  
5.1  
164.2  
74.1  
5.2  
167.3  
81.7  
5.3  
170.6  
89.7  
5.3  
174.1  
98.1  
5.4  
177.7  
106.9  
5.5  
75  
Head press. PSIG  
Cap. Btuh/1000  
OD Unit KW  
187.7  
65.1  
5.6  
191.0  
72.1  
5.7  
194.3  
79.5  
5.7  
197.9  
87.2  
5.8  
201.6  
95.2  
5.9  
205.4  
103.5  
6.0  
85  
Head press. PSIG  
Cap. Btuh/1000  
OD Unit KW  
216.7  
62.6  
6.2  
220.2  
69.4  
6.3  
223.9  
76.5  
6.3  
227.7  
83.8  
6.4  
231.6  
91.5  
6.5  
235.6  
99.4  
6.6  
95  
Head press. PSIG  
Cap. Btuh/1000  
OD Unit KW  
248.3  
59.5  
6.9  
252.0  
65.9  
6.9  
255.9  
72.7  
7.0  
260.0  
79.7  
7.1  
264.1  
87.1  
7.1  
268.5  
94.7  
7.2  
105  
115  
Head press. PSIG  
Cap. Btuh/1000  
OD Unit KW  
282.5  
55.8  
7.6  
286.5  
61.9  
7.7  
290.6  
68.3  
7.7  
294.9  
75.0  
7.8  
299.3  
82.0  
7.9  
303.9  
89.3  
8.0  
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.  
Table PD-25 Cooling Performance (kW) - Single Compressor - (SI)  
TTA155C Condensing Unit Only  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
945  
19.9  
4.76  
964  
22.0  
4.80  
983  
24.3  
4.85  
1005  
26.7  
4.91  
1027  
29.3  
4.97  
1051  
32.0  
5.04  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1112  
19.6  
5.14  
1132  
21.7  
5.19  
1154  
23.9  
5.25  
1176  
26.3  
5.32  
1200  
28.7  
5.39  
1225  
31.3  
5.47  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1294  
19.1  
5.62  
1317  
21.1  
5.68  
1340  
23.3  
5.75  
1364  
25.5  
5.82  
1390  
27.9  
5.90  
1416  
30.3  
5.98  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1494  
18.3  
6.19  
1518  
20.3  
6.26  
1544  
22.4  
6.33  
1570  
24.5  
6.41  
1597  
26.8  
6.48  
1625  
29.1  
6.57  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1712  
17.4  
6.85  
1738  
19.3  
6.92  
1765  
21.3  
6.99  
1792  
23.3  
7.07  
1821  
25.5  
7.15  
1851  
27.7  
7.23  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1948  
16.3  
7.61  
1975  
18.1  
7.67  
2004  
20.0  
7.74  
2033  
22.0  
7.81  
2064  
24.0  
7.89  
2096  
26.2  
7.97  
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.  
SS-PRC003-EN  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Condensing Unit  
Table PD-26 Cooling Capacities (MBh)TTA200B Condensing Unit Only  
(I-P)  
ODTemp  
°F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
181  
188.3  
12.97  
187  
206.3  
13.31  
194  
225.0  
13.66  
201  
244.3  
14.04  
208  
264.3  
14.45  
216  
285.0  
14.88  
65  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
207  
179.3  
14.39  
214  
196.2  
14.76  
221  
213.9  
15.15  
229  
232.4  
15.57  
237  
251.6  
16.02  
245  
271.4  
16.48  
75  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
236  
169.7  
16.07  
244  
185.9  
16.47  
251  
202.8  
16.90  
259  
220.4  
17.36  
267  
238.8  
17.83  
276  
257.7  
18.32  
85  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
268  
159.7  
17.98  
276  
175.2  
18.43  
284  
191.4  
18.90  
292  
208.4  
19.39  
301  
225.9  
19.89  
310  
244.0  
20.40  
95  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
302  
149.2  
20.13  
311  
164.2  
20.63  
319  
179.9  
21.14  
328  
196.2  
21.67  
338  
213.1  
22.19  
347  
230.3  
22.70  
105  
115  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
339  
138.4  
22.50  
348  
153.0  
23.06  
358  
168.3  
23.62  
367  
184.0  
24.18  
377  
200.1  
24.72  
387  
216.5  
25.23  
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.  
Table PD-26 Cooling Capacities (MBh)TTA200B Condensing Unit Only  
(SI)  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1248  
55.1  
12.97  
1292  
60.4  
13.31  
1338  
65.9  
13.66  
1387  
71.5  
14.04  
1437  
77.4  
14.45  
1491  
83.4  
14.88  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1430  
52.5  
14.39  
1476  
57.4  
14.76  
1525  
62.6  
15.15  
1577  
68.0  
15.57  
1631  
73.7  
16.02  
1688  
79.5  
16.48  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1630  
49.7  
16.07  
1680  
54.4  
16.47  
1732  
59.4  
16.90  
1787  
64.5  
17.36  
1844  
69.9  
17.83  
1904  
75.4  
18.32  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
1848  
46.7  
17.98  
1901  
51.3  
18.43  
1957  
56.1  
18.90  
2015  
61.0  
19.39  
2076  
66.2  
19.89  
2139  
71.4  
20.40  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
2085  
43.7  
20.13  
2142  
48.1  
20.63  
2202  
52.7  
21.14  
2264  
57.5  
21.67  
2329  
62.4  
22.19  
2395  
67.4  
22.70  
Head pressure (kPA)  
Capacity (kW)  
2340  
40.5  
2402  
44.8  
2467  
49.3  
2533  
53.9  
2602  
58.6  
2671  
63.4  
OD Unit Power (kW)  
22.50  
23.06  
23.62  
24.18  
24.72  
25.23  
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.  
38  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Air Handler  
Table PD-27Evaporator Fan Performance TWE050A (I-P)  
External Static Pressure (Inches of Water Column)  
.10"  
.20"  
.30"  
.40" .50" .60" .70" .80"  
.90"  
1.00"  
1.10"  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
646 0.37 698 0.42 751 0.47 803 0.52 856 0.56 908 0.61 941 0.65 973 0.68 1006 0.71  
607 0.36 661 0.40 713 0.45 764 0.50 816 0.54 867 0.59 919 0.64 952 0.67 984 0.71  
625 0.38 676 0.43 727 0.48 778 0.52 828 0.57 879 0.62 930 0.67 963 0.70 995 0.74  
601 0.35 648 0.40 696 0.44 744 0.49 792 0.54 841 0.59 889 0.64 937 0.69 971 0.73 1005 0.77  
625 0.36 671 0.41 716 0.46 762 0.51 807 0.56 853 0.61 898 0.66 944 0.71 979 0.76  
642 0.40 687 0.45 731 0.50 776 0.55 820 0.60 865 0.66 909 0.71 951 0.75 987 0.80  
659 0.44 703 0.49 745 0.54 790 0.60 833 0.65 877 0.70 920 0.75 957 0.80 994 0.84  
674 0.48 722 0.54 770 0.60 817 0.65 857 0.70 897 0.75 936 0.80 973 0.85 1009 0.89  
0.75 HP Standard Motor  
and Standard Static Drive  
1.0 HP Oversized Motor  
and High Static Drive  
Notes:  
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.  
Table PD-27Evaporator Fan Performance TWE050A (SI)  
External Static Pressure (Pascal)  
25  
50  
75  
100  
125  
150  
174  
199  
224  
249  
274  
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW  
2379  
2549  
2718  
2888  
3058  
3228  
3398  
3568  
646 0.28 698 0.31 751 0.35 803 0.39 856 0.42 908 0.45 941 0.48 973 0.51 1006 0.53  
607 0.27 661 0.30 713 0.34 764 0.37 816 0.40 867 0.44 919 0.48 952 0.50 984 0.53  
625 0.28 676 0.32 727 0.36 778 0.39 828 0.43 879 0.46 930 0.50 963 0.52 995 0.55  
601 0.26 648 0.30 696 0.33 744 0.37 792 0.40 841 0.44 889 0.48 937 0.51 971 0.54 1005 0.57  
625 0.27 671 0.31 716 0.34 762 0.38 807 0.42 853 0.45 898 0.49 944 0.53 979 0.57  
642 0.30 687 0.34 731 0.37 776 0.41 820 0.45 865 0.49 909 0.53 951 0.56 987 0.60  
659 0.33 703 0.37 745 0.40 790 0.45 833 0.48 877 0.52 920 0.56 957 0.60 994 0.63  
674 0.36 722 0.40 770 0.45 817 0.48 857 0.52 897 0.56 936 0.60 973 0.63 1009 0.66  
0.56 kW Standard Motor  
and Standard Static Drive  
0.75 kW Oversized Motor  
and High Static Drive  
Notes:  
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.  
Table PD-28 Blower Speeds TWE050A  
Motor DriveTurns Open  
Drive  
6
5
4
3
2
1
0
Standard  
High Static  
N/A  
N/A  
590  
713  
639  
772  
688  
832  
737  
891  
786  
951  
835  
1009  
SS-PRC003-EN  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Air Handler  
Table PD-29Evaporator Fan Performance TWE075A (I-P)  
External Static Pressure (In. Of Water Column)  
0.10  
0.20  
0.30  
0.40 0.50 0.60 0.70 0.80  
0.90  
1.00  
1.10  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
2000  
2125  
2250  
2375  
2500  
2625  
2750  
2875  
3000  
443 0.44 489 0.49 535 0.54 581 0.59 627 0.64 673 0.69 719 0.74 765 0.79 791 0.83 818 0.89  
453 0.46 499 0.52 546 0.57 592 0.63 638 0.68 684 0.74 730 0.79 771 0.85 798 0.90 825 0.96  
463 0.49 510 0.55 556 0.61 602 0.67 649 0.73 695 0.79 742 0.85 776 0.91 804 0.97 831 1.03  
473 0.51 520 0.57 567 0.64 613 0.70 660 0.77 706 0.83 753 0.90 782 0.97 810 1.03 838 1.10  
445 0.47 489 0.54 533 0.60 578 0.67 622 0.73 667 0.80 711 0.86 756 0.93 784 0.99 813 1.07 842 1.14  
464 0.50 506 0.57 548 0.63 589 0.69 631 0.76 672 0.82 714 0.88 757 0.95 786 1.01 815 1.09 844 1.17  
484 0.53 523 0.59 562 0.66 601 0.72 640 0.78 678 0.84 717 0.91 758 0.97 787 1.03 817 1.12 847 1.21  
504 0.56 540 0.62 576 0.68 612 0.74 648 0.81 684 0.87 720 0.93 759 0.99 789 1.05 819 1.15 850 1.24  
524 0.59 557 0.65 590 0.71 624 0.77 657 0.83 690 0.89 723 0.95 760 1.01 790 1.07 821 1.17 853 1.27  
1.0 HP Standard Motor  
and Low Static Drive  
1.0 HP Standard Motor  
and Drive  
1.5 HP Oversized Motor  
and High Static Drive  
Notes:  
1. Performance based on a wet coil and 1 inch (25.4 mm)  
throwaway filters.  
2. Tabulated brake horsepower is the motor shaft output  
Table PD-29 Continued  
External Static Pressure (In. Of Water Column)  
required.  
1.20 1.30 1.40 1.50 1.60  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
844 0.96 871 1.02 897 1.09 924 1.15 950 1.21  
3. Factory setting of motor sheave is 1.5 turns open.  
Adjustments are made in 0.5 turn increments.  
CFM  
2000  
2125  
2250  
2375  
2500  
2625  
2750  
2875  
3000  
852 1.03 879 1.09 906 1.16 933 1.22  
859 1.10 886 1.17 914 1.23 942 1.30  
866 1.17 894 1.24 922 1.30 950 1.37  
870 1.21 899 1.29 928 1.36  
874 1.25 903 1.33 932 1.42  
877 1.29 907 1.38 937 1.47  
880 1.33 911 1.43 942 1.52  
884 1.37 915 1.48 946 1.58  
1.5 HP Oversized Motor  
and High Static Drive  
1.0 HP Standard Motor  
and Drive  
Table PD-29 Evaporator Fan Performance TWE075A (SI)  
External Static Pressure (Pascal)  
25  
50  
75  
100  
125 150 174  
199  
224  
249  
274  
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW  
3338  
3547  
3755  
3964  
4173  
4381  
4590  
4798  
5007  
443 0.33 489 0.37 535 0.4 581 0.44 627 0.48 673 0.51 719 0.55 765 0.59 791 0.62 818 0.66  
453 0.34 499 0.39 546 0.43 592 0.47 638 0.51 684 0.55 730 0.59 771 0.63 798 0.67 825 0.72  
463 0.37 510 0.41 556 0.45 602 0.5 649 0.54 695 0.59 742 0.63 776 0.68 804 0.72 831 0.77  
473 0.38 520 0.43 567 0.48 613 0.52 660 0.57 706 0.62 753 0.67 782 0.72 810 0.77 838 0.82  
445 0.35 489 0.4 533 0.45 578 0.5 622 0.54 667 0.6 711 0.64 756 0.69 784 0.74 813 0.8 842 0.85  
464 0.37 506 0.43 548 0.47 589 0.51 631 0.57 672 0.61 714 0.66 757 0.71 786 0.75 815 0.81 844 0.87  
484 0.4 523 0.44 562 0.49 601 0.54 640 0.58 678 0.63 717 0.68 758 0.72 787 0.77 817 0.84 847 0.9  
504 0.42 540 0.46 576 0.51 612 0.55 648 0.6 684 0.65 720 0.69 759 0.74 789 0.78 819 0.86 850 0.92  
524 0.44 557 0.48 590 0.53 624 0.57 657 0.62 690 0.66 723 0.71 760 0.75 790 0.8 821 0.87 853 0.95  
.75 kW Standard Motor  
and Low Static Drive  
.75 kW Standard Motor  
and Drive  
1.12 kW Oversized Motor  
and High Static Drive  
Notes:  
Table PD-29 Continued  
1. Performance based on a wet coil and 1 inch (25.4 mm)  
throwaway filters.  
2. Tabulated brake horsepower is the motor shaft  
External Static Pressure (Pascal)  
output required.  
3. Factory setting of motor sheave is 1.5 turns open.  
Adjustments are made in 0.5 turn increments.  
299  
324 349 374  
398  
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW  
3338  
3547  
3755  
3964  
4173  
4381  
4590  
4798  
5007  
844 0.72 871 0.76 897 0.81 924 0.86 950 0.9  
852 0.77 879 0.81 906 0.87 933 0.91  
859 0.82 886 0.87 914 0.92 942 0.97  
866 0.87 894 0.92 922 0.97 950 1.02  
Table PD-30 Blower Speeds TWE075A  
870 0.9 899 0.96 928 1.01  
874 0.93 903 0.99 932 1.06  
877 0.96 907 1.03 937 1.1  
880 0.99 911 1.07 942 1.13  
884 1.02 915 1.1 946 1.18  
Motor DriveTurns Open  
Drive  
6
5
4
3
2
1
0
Standard  
Low Static N/A  
High Static N/A  
N/A  
600  
428  
700  
650  
464  
750  
700  
499  
800  
750  
535  
850  
800  
571  
900  
850  
606  
950  
1.12 kW Oversized Motor and High Static Drive  
.75 kW Standard Motor  
and Drive  
40  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Air Handler  
Table PD-31 Evaporator Fan Performance TWE100A,TWE100B (I-P)  
External Static Pressure (In. Of Water Column)  
0.10  
0.20  
0.30  
0.40 0.50 0.60 0.70 0.80  
0.90  
1.00  
1.20  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
1.5 HP Standard Motor and Low Static Drive  
2600  
460 0.32 493 0.39 527 0.47 565 0.55 603 0.63 641 0.71 679 0.79 717 0.87 744 0.94 772 1.01 826 1.16  
473 0.37 506 0.45 540 0.53 576 0.61 613 0.69 649 0.77 686 0.85 723 0.93 748 1.00 775 1.07 830 1.20  
487 0.43 519 0.50 552 0.58 587 0.67 623 0.75 658 0.83 693 0.91 728 0.99 751 1.06 779 1.12 833 1.25  
501 0.49 532 0.56 565 0.64 599 0.72 632 0.81 666 0.89 700 0.97 734 1.05 755 1.11 783 1.18 737 1.30  
520 0.58 548 0.65 581 0.73 613 0.81 644 0.89 677 0.98 710 1.06 740 1.13 759 1.19 787 1.25 841 1.37  
541 0.69 568 0.76 600 0.84 631 0.93 658 1.00 691 1.08 721 1.16 746 1.21 764 1.28 793 1.34 846 1.48  
562 0.82 588 0.88 618 0.97 648 1.05 671 1.11 703 1.19 732 1.27 753 1.31 772 1.38 801 1.45 853 1.59  
582 0.96 608 1.03 637 1.11 666 1.20 685 1.26 711 1.31 739 1.38 763 1.44 787 1.51 815 1.58 862 1.74  
602 1.11 628 1.17 656 1.26 683 1.35 698 1.40 720 1.43 747 1.50 773 1.58 801 1.64 829 1.71 872 1.89  
2775  
2950  
3125  
3300  
3475  
3650  
3825  
4000  
1.5 HP Standard Motor and Drive  
2.0 HP Oversized Motor  
and High Static Drive  
Notes:  
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are  
made in 0.5 turn increments.  
Table PD-31Continued  
External Static Pressure (In. Of Water Column)  
4. Low Static Drive must be field supplied.  
1.40  
1.60  
CFM  
RPM BHP RPM BHP  
2.0 HP Oversized Motor  
and High Static Drive  
2600  
2775  
2960  
3125  
3300  
3475  
3650  
3825  
4000  
881 1.30 936 1.45  
884 1.36 938 1.51  
886 1.41 939 1.57  
889 1.47 941 1.64  
892 1.54 945 1.73  
897 1.63 950 1.85  
902 1.73 955 1.99  
912 1.89 960 2.18  
922 2.04 965 2.30  
Table PD-31Evaporator Fan Performance TWE0100A,TWE100B (SI)  
External Static Pressure (Pascal)  
25  
50  
75  
100  
125  
150  
174  
199  
224  
249  
299  
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW  
1.12 kW Standard Motor and Low Static Drive  
4417  
4715  
5012  
5309  
5607  
5904  
6201  
6499  
6796  
460 0.24 493 0.29 527 0.35 565 0.41 603 0.47 641 0.53 679 0.59 717 0.65 744 0.7 772 0.75 826 0.87  
473 0.28 506 0.34 540 0.4 576 0.45 613 0.51 649 0.57 686 0.63 723 0.69 748 0.75 775 0.8 830 0.89  
487 0.32 519 0.37 552 0.43 587 0.5 623 0.56 658 0.62 693 0.68 728 0.74 751 0.79 779 0.84 833 0.93  
501 0.37 532 0.42 565 0.48 599 0.54 632 0.6 666 0.66 700 0.72 734 0.78 755 0.83 783 0.88 737 0.97  
520 0.43 548 0.48 581 0.54 613 0.6 644 0.66 677 0.73 710 0.79 740 0.84 759 0.89 787 0.93 841 1.02  
541 0.51 568 0.57 600 0.63 631 0.69 658 0.75 691 0.8 721 0.87 746 0.9 764 0.95 793  
1
846 1.1  
562 0.61 588 0.66 618 0.72 648 0.78 671 0.83 703 0.89 732 0.95 753 0.98 772 1.03 801 1.08 853 1.19  
582 0.72 608 0.77 637 0.83 666 0.89 685 0.94 711 0.98 739 1.03 763 1.07 787 1.13 815 1.18 862 1.3  
602 0.83 628 0.87 656 0.94 683 1.01 698 1.04 720 1.07 747 1.12 773 1.18 801 1.22 829 1.28 872 1.41  
1.12 kW Standard Motor and Drive  
1.49 kW Oversized Motor  
and High Static Drive  
Notes:  
1. Performance based on a wet coil and 1 inch (25.4 mm)  
throwaway filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 3.0 turns open. Adjustments are  
made in 0.5 turn increments.  
Table PD-31Continued  
External Static Pressure (Pascal)  
349  
398  
4. Low Static Drive must be field supplied.  
m3/hr RPM kW RPM kW  
1.49 kW Oversized Motor  
and High Static Drive  
4417  
4715  
5012  
5309  
5607  
5904  
6201  
6499  
6796  
881 0.97 936 1.08  
884 1.01 938 1.13  
886 1.05 939 1.17  
889 1.1 941 1.22  
892 1.15 945 1.29  
897 1.22 950 1.38  
902 1.29 955 1.48  
912 1.41 960 1.63  
922 1.52 965 1.72  
Table PD-32 Blower Speeds TWE100A,TWE100B  
Motor SheaveTurns Open  
Drive  
6
5
4
3
2
1
0
Standard  
N/A  
587  
453  
606  
745  
629  
485  
641  
789  
671  
518  
677  
833  
713  
550  
713  
877  
755  
583  
748  
920  
796  
615  
784  
965  
Low Static N/A  
High Static N/A  
High Static II N/A  
SS-PRC003-EN  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Air Handler  
Table PD-33 Evaporator Fan Performance TWE155B (I-P)  
External Static Pressure (Inches of Water Column)  
.10"  
.20"  
.30"  
.40"  
.50" .60" .70" .80" .90"  
1.00"  
1.20"  
1.40"  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
3.0 HP Oversized Motor  
and High Static Drive  
2.0 HP Standard Motor and Drive  
4000  
4250  
4500  
4750  
5000  
5260  
5500  
5750  
6000  
628 1.34 653 1.38 678 1.43 692 1.48 708 1.52 723 1.57 738 1.60 749 1.61 759 1.62 795 1.66 851 1.85 907 2.03  
633 1.37 658 1.41 683 1.46 697 1.51 713 1.55 728 1.60 743 1.62 751 1.63 770 1.64 806 1.71 862 1.90 918 2.11  
637 1.40 662 1.44 687 1.49 701 1.53 717 1.58 732 1.63 747 1.64 754 1.65 782 1.67 817 1.76 873 1.96 929 2.19  
641 1.42 666 1.50 691 1.53 705 1.61 721 1.63 736 1.65 751 1.66 765 1.67 793 1.72 828 1.81 884 2.01 940 2.27  
645 1.44 670 1.52 695 1.56 710 1.65 725 1.67 739 1.68 758 1.70 777 1.74 806 1.81 839 1.91 896 2.13  
650 1.46 675 1.53 700 1.59 716 1.67 728 1.70 741 1.73 765 1.75 790 1.82 819 1.92 849 2.03 907 2.28  
652 1.47 678 1.55 703 1.63 721 1.71 734 1.75 747 1.78 775 1.83 804 1.92 832 2.03 861 2.15 920 2.44  
653 1.48 680 1.57 706 1.68 726 1.76 743 1.81 761 1.86 789 1.94 817 2.04 846 2.16 875 2.29 935 2.61  
655 1.49 681 1.59 709 1.74 731 1.80 752 1.87 774 1.94 803 2.05 831 2.17 860 2.29 889 2.44 950 2.78  
Notes:  
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.  
Table PD-33 Evaporator Fan Performance TWE155B (SI)  
External Static Pressure (Pascal)  
25  
50  
75  
100  
125  
150  
174  
199  
224  
249  
299  
349  
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW  
2.24 kW Oversized Motor  
1.49 kW Standard Motor and Drive  
and High Static Drive  
6796  
7221  
7646  
8070  
8495  
8937  
9345  
9769  
10194  
628  
1
653 1.03 678 1.07 692 1.1 708 1.13 723 1.17 738 1.19 749 1.2 759 1.21 795 1.24 851 1.38 907 1.51  
633 1.02 658 1.05 683 1.09 697 1.13 713 1.16 728 1.19 743 1.21 751 1.22 770 1.22 806 1.28 862 1.42 918 1.57  
637 1.04 662 1.07 687 1.11 701 1.14 717 1.18 732 1.22 747 1.23 754 1.23 782 1.25 817 1.31 873 1.46 929 1.63  
641 1.06 666 1.12 691 1.14 705 1.2 721 1.22 736 1.23 751 1.24 765 1.25 793 1.28 828 1.35 884 1.5 940 1.69  
645 1.07 670 1.13 695 1.16 710 1.23 725 1.25 739 1.25 758 1.27 777 1.3 806 1.35 839 1.42 896 1.59  
650 1.09 675 1.14 700 1.19 716 1.25 728 1.27 741 1.29 765 1.3 790 1.36 819 1.43 849 1.51 907 1.7  
652 1.1 678 1.16 703 1.22 721 1.28 734 1.3 747 1.33 775 1.36 804 1.43 832 1.51 861 1.6 920 1.82  
653 1.1 680 1.17 706 1.25 726 1.31 743 1.3 761 1.39 789 1.45 817 1.52 846 1.61 875 1.71 935 1.95  
655 1.11 681 1.19 709 1.3 731 1.34 752 1.35 774 1.45 803 1.53 831 1.62 860 1.71 889 1.82 950 2.07  
Notes:  
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.  
Table PD-34Blower Speeds TWE155B  
Motor SheaveTurns Open  
Drive  
6
5
4
3
2
1
0
Standard  
High Static  
619  
777  
648  
806  
677  
835  
705  
863  
734  
892  
763  
921  
N/A  
950  
42  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Air Handler  
Table PD-35 Evaporator Fan Performance TWE200B (I-P)  
External Static Pressure (In. Of Water Column)  
0.10  
0.20  
0.30  
0.40 0.50 0.60 0.70 0.80  
0.90  
1.00  
1.20  
140  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
5200  
5525  
5850  
6175  
6500  
6825  
7150  
7475  
7800  
461 0.74 503 0.91 545 1.07 587 1.03 619 1.17 685 1.40 723 1.59 750 1.74 777 1.89 851 2.19 898 2.39  
479 0.88 521 1.04 563 1.21 605 1.21 640 1.35 701 1.58 739 1.77 766 1.92 793 2.07 859 2.37 906 2.60  
497 1.01 539 1.18 581 1.34 623 1.39 661 1.53 717 1.76 755 1.95 782 2.10 809 2.25 868 2.55 915 2.81  
473 0.99 515 1.15 557 1.31 599 1.48 641 1.57 682 1.71 732 1.94 769 2.12 796 2.27 823 2.43 877 2.73 924 3.02  
492 1.12 534 1.28 576 1.45 618 1.61 660 1.75 702 1.90 748 2.12 784 2.30 811 2.45 838 2.60 886 2.91 933 3.22  
510 1.25 552 1.42 594 1.59 636 1.75 678 1.91 723 2.10 763 2.30 794 2.47 820 2.62 846 2.77 894 3.09 941 3.42  
528 1.38 570 1.56 612 1.73 654 1.90 697 2.07 744 2.30 779 2.49 804 2.64 830 2.78 855 2.94 903 3.26 950 3.62  
550 1.61 594 1.77 640 1.92 683 2.08 721 2.29 760 2.50 790 2.67 815 2.81 840 2.96 865 3.11 914 3.47 959 3.85  
572 1.83 618 1.97 668 2.10 712 2.27 746 2.52 776 2.69 802 2.84 826 2.99 851 3.13 876 3.27 926 3.67 969 4.08  
3.0 HP Standard  
Motor and Low  
Static Drive  
3.0 HP Standard  
3.0 HP Standard Motor  
5.0 HP Oversized Motor  
Motor and Low  
Static Drive System II  
and Standard  
and High Static  
Drive System  
Drive System  
Notes:  
1. Performance based on a wet coil and 2 inch (51mm) throwaway filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in  
0.5 turn increments.  
Table PD-35 Continued  
External Static Pressure (In. Of Water Column)  
1.60 1.80  
RPM BHP RPM BHP  
4. Low static drive components referencing this note are field supplied.  
CFM  
5.0 HP Oversized Motor and High Static Drive  
System  
5200  
5525  
5850  
5175  
8500  
8825  
7150  
7475  
7800  
944 2.75 989 3.12  
952 2.96 997 3.33  
961 3.17 1006 3.54  
970 3.38 1015 3.75  
978 3.59 1023 3.96  
986 3.80  
994 4.01  
1003 4.25  
1012 4.50  
Table PD-35 Evaporator Fan Performance TWE200B (SI)  
External Static Pressure (Pascal)  
25  
50  
75  
100 125 150  
174  
199  
224  
249  
299  
349  
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW  
8835  
9387  
9939  
461 0.55 503 0.68 545 0.8 587 0.77 619 0.87 685 1.04 723 1.19 750 1.3 777 1.41 851 1.63 898 1.78  
479 0.66 521 0.78 563 0.9 605 0.9 640 1.01 701 1.18 739 1.32 766 1.43 793 1.54 859 1.77 906 1.94  
497 0.75 539 0.88 581  
1
623 1.04 661 1.14 717 1.31 755 1.45 782 1.57 809 1.68 868 1.9 915 2.1  
10491  
11044  
11596  
12148  
12700  
13252  
473 0.74 515 0.86 557 0.98 599 1.1 641 1.17 682 1.28 732 1.45 769 1.58 796 1.69 823 1.81 877 2.04 924 2.52  
492 0.84 534 0.95 576 1.08 618 1.2 660 1.3 702 1.42 748 1.58 784 1.72 811 1.83 838 1.94 886 2.17 933 2.4  
510 0.93 552 1.06 594 1.19 636 1.3 678 1.42 723 1.57 763 1.72 794 1.84 820 1.95 846 2.07 894 2.3 941 2.55  
528 1.03 570 1.16 612 1.29 654 1.42 697 1.54 744 1.72 779 1.86 804 1.97 830 2.07 855 2.19 903 2.43 950 2.7  
550 1.2 594 1.32 640 1.43 683 1.55 721 1.71 760 1.87 790 1.99 815 2.1 840 2.21 865 2.32 914 2.59 959 2.87  
572 1.36 618 1.47 668 1.57 712 1.69 746 1.88 776 2.01 802 2.12 826 2.23 851 2.33 876 2.44 926 2.74 969 3.04  
2.24 kW Standard  
Motor and Low  
Static Drive System Static Drive System II  
2.24 kW Standard  
Motor and Low  
2.24 kW Standard  
Motor and Standard  
Drive System  
3.73 kW Oversized Motor  
and High Static Drive System  
Notes:  
1. Performance based on a wet coil and 2 inch (51mm) throwaway filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in  
0.5 turn increments.  
Table PD-35 Continued  
External Static Pressure (Pascal)  
398  
448  
4. Low static drive components referencing this note are field supplied.  
m3/hr RPM kW RPM kW  
3.73 kW Oversized Motor  
and High Static Drive System  
8835  
9387  
9939  
10491  
11044  
11596  
12148  
12700 1003 3.17  
13252 1012 3.36  
944 2.05 989 2.33  
952 2.21 997 2.48  
961 2.36 1006 2.64  
970 2.52 1015 2.8  
978 2.68 1023 2.95  
Table PD-36Blower Speeds TWE200B  
Motor SheaveTurns Open  
Drive  
6
5
4
3
2
1
0
986 2.83  
994 2.99  
Standard  
706  
457  
574  
N/A  
732  
478  
595  
821  
758  
500  
617  
862  
784  
521  
638  
903  
811  
542  
659  
945  
837  
563  
680  
986  
863  
585  
702  
Low Static I  
Low Static II  
High Static  
1027  
SS-PRC003-EN  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-37Discharge PlenumAnd GrilleAssemblyThrow Distance (ft) Air Handler  
Unit  
Model No.  
Louver Angle Deflection Position  
CFM  
1400  
1600  
1800  
2000  
2200  
2100  
2400  
2700  
3000  
3200  
3600  
4000  
4400  
4800  
4300  
4900  
5400  
6000  
5600  
6400  
7200  
8000  
m3/h  
2380  
2718  
3060  
3398  
3737  
3568  
4079  
4586  
5098  
5436  
6116  
6797  
7477  
8154  
7304  
8327  
9176  
10195  
9515  
10872  
12233  
13594  
Straight  
38 (11.6)  
42 (12.8)  
46 (14.0)  
48 (14.6)  
51 (15.5)  
49 (14.9)  
52 (15.9)  
55 (16.8)  
58 (17.7)  
56 (17.1)  
62 (18.9)  
66 (20.1)  
71 (21.6)  
76 (23.2)  
42 (12.8)  
47 (14.3)  
52 (15.9)  
57 (17.4)  
50 (15.2)  
56 (17.1)  
62 (18.9)  
66 (20.1)  
20, ft (m)  
24 (7.3)  
31 (9.4)  
40, ft (m)  
22 (6.7)  
26 (7.9)  
55, ft (m)  
18 (5.5)  
20 (6.1)  
22 (6.7)  
24 (7.3)  
TWE050  
TWE075  
37 (11.3)  
43 (13.1)  
50 (15.2)  
38 (11.6)  
43 (13.1)  
48 (14.6)  
53 (16.2)  
46 (14.0)  
51 (15.5)  
57 (17.4)  
62 (18.9)  
67 (20.4)  
32 (9.8)  
38 (11.6)  
44 (13.4)  
49 (14.9)  
40 (12.2)  
46 (14.0)  
51 (15.5)  
57 (17.4)  
29 (8.8)  
33 (10.1)  
36 (11.0)  
31 (9.4)  
25 (7.6)  
27 (8.2)  
29 (8.8)  
31 (9.4)  
32 (9.8)  
30 (9.1)  
33 (10.1)  
35 (10.7)  
38 (11.6)  
42 (12.8)  
21 (6.4)  
25 (7.6)  
29 (8.8)  
32 (9.8)  
27 (8.2)  
30 (9.1)  
33 (10.1)  
35 (10.7)  
35 (10.7)  
38 (11.6)  
42 (12.8)  
38 (11.6)  
42 (12.8)  
47 (14.3)  
52 (15.9)  
56 (17.1)  
29 (8.8)  
TWE100  
32 (9.8)  
TWE155  
TWE200  
37 (11.3)  
41 (12.5)  
33 (10.1)  
38 (11.6)  
42 (12.8)  
47 (14.3)  
Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s).  
Throw distance values at other terminal velocities may be established by multiplying throw distances in table above  
by throw factor:  
Terminal Velocity  
50 fpm (.25 m/s)  
100 fpm (.51 m/s)  
150 fpm (.76 m/s)  
Throw Factor  
x
x
x
1.50  
.75  
.50  
Table PD-38Static Pressure DropThrough Accessories (Inches OfWater Column)1 —  
Air Handler  
Discharge  
Unit  
Model No.  
Return Grille  
Plenum and Grille2  
Electric Heaters (kW)  
CFM  
1400  
1600  
2000  
2100  
2400  
3000  
2800  
3200  
4300  
4800  
6000  
5600  
6400  
8000  
m3/h  
2380  
2718  
3398  
3568  
4079  
5098  
4756  
5436  
7304  
8154  
10195  
9515  
10872  
13594  
In. wc1 Pascal In. wc1 Pascal  
5-10  
.06  
08  
15-20  
.06  
.08  
.13  
.03  
.06  
.12  
.04  
.13  
.02  
.03  
.06  
.04  
.0-6  
.10  
25-30  
.12  
.14  
.19  
.05  
.08  
.17  
.14  
.19  
.04  
.06  
.12  
.10  
.13  
.20  
35-50  
.09  
.12  
.18  
.05  
.08  
.13  
.04  
.07  
.07  
.09  
.15  
.07  
.11  
(22.4)  
(29.9)  
(44.8)  
(12.5)  
(19.9)  
(32.4)  
(10.0)  
(17.4)  
(17.4)  
(22.4)  
(37.4)  
(17.4)  
(27.4)  
(42.3)  
.16  
.21  
.33  
.19  
.27  
.40  
.34  
.43  
.18  
.23  
.34  
.32  
.43  
.66  
(39.8)  
(52.3)  
(82.2)  
(47.3)  
TWE050A  
.13  
.02  
.03  
.06  
.03  
.06  
.02  
.03  
.06  
.04  
.06  
.10  
.08  
.12  
.23  
.20  
.26  
.05  
.08  
.17  
.15  
.19  
.30  
TWE075A  
(67.2)  
(99.6)  
(84.7)  
(107.1)  
(44.8)  
(57.3)  
TWE100A  
TWE100B  
TWE155B  
TWE200B  
(84.7)  
(79.7)  
(107.1)  
(164.3)  
.17  
1. Return air filter ESP included in Fan PerformanceTable data.  
2. At louver opening angle of 42°F (5.5°C). For ESP at other angle openings, see accessory Installers Guide.  
44  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-39 Auxiliary Electric Heat Capacity Air Handler  
No.  
of  
Stages  
1
1
1
2
Stage 1  
kW  
Stage 2  
Total  
Unit  
Model No.  
Total  
kW  
Btu  
kW  
Btu  
Output  
kW  
Input  
5.00  
9.96  
14.96  
24.92  
Btu  
Input  
5.00  
Output  
17,065  
33,993  
51,058  
51,058  
Input  
Output  
17,065  
33,993  
51,058  
85,051  
5.00  
9.96  
14.96  
24.92  
TWE050/075/100AD  
TWE100BD  
9.96  
14.96  
14.96  
9.96  
33,993  
TWE075, 100AD  
TWE100BD  
34.88  
10.00  
19.92  
29.92  
49.84  
2
1
1
2
2
19.92  
10.00  
19.92  
19.92  
29.92  
67,987  
34,130  
67,987  
67,987  
102,117  
14.96  
51,058  
34.88  
10.00  
19.92  
29.92  
49.84  
119,045  
34,130  
67,987  
102,117  
170,104  
TWE155,200B  
10.00  
19.92  
34,130  
67,987  
*Heaters are rated at 400v. For other than rated voltage,  
2
2
Voltage  
Voltage  
Rated Voltage  
Capacity =  
x Rated Capacity and kW =  
Rated kW.  
(
)
(
)
Rated Voltage  
SS-PRC003-EN  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-1 UnitWiring Condensing Units  
Minimum  
Circuit  
Ampacity  
Maximum Fuse Size  
or Maximum Circuit  
Breaker  
Unit  
Model No.  
Unit Operating  
Voltage  
TTA075A  
TTA085A  
TTA100A  
TTA100B  
TTA125B  
TTA155B  
TTA155C  
TTA200B  
380/415  
380/415  
380/415  
380/415  
380/415  
380/415  
380/415  
380/415  
15.5  
17.8  
21.5  
26.3  
27.4  
28.3  
35.1  
39.3  
25  
25  
35  
35  
35  
35  
45  
50  
Table ED-2 Electrical Characteristics Motors Condensing Units  
Compressor Motor  
Amps  
Condenser Fan Motor  
FLA  
Amps  
LRA  
(Ea.)  
4.0  
Unit  
RLA  
(Ea.)  
11.0  
11.9  
14.9  
10.5  
11.0  
11.0  
14.0  
14.9  
LRA  
(Ea.)  
90.0  
118.0  
118.0  
71.0  
64.0  
90.0  
92.5  
118.0  
Model No.  
TTA075A  
TTA085A  
TTA100A  
TTA100B  
TTA125B  
TTA155B  
TTA155C  
TTA200B  
No.  
1
1
1
2
2
2
Phase  
No.  
1
1
1
1
2
2
Phase  
(Ea.)  
1.6  
3
3
3
3
3
3
3
3
1
1
1
1
1
1
1
1
2.7  
2.7  
2.7  
2.7  
1.6  
9.3  
9.3  
7.0  
7.0  
4.0  
3.8  
9.3  
1
2
2
2
1.6  
2.7  
NOTE:  
1. Electrical characteristics reflect nameplate values and are calculated in accordance with UL and ARI specifications.  
Table ED-3 Electrical Characteristics Motors Air Handler  
Standard Fan Motor  
Oversized Fan Motor  
Unit  
Amps  
Amps  
Model No.  
TWE050  
TWE075  
TWE100  
TWE155  
TWE200  
Volts  
Phase  
FLA  
2.9  
3.8  
4.0  
4.5  
7.6  
LRA  
8.2  
19.7  
27.5  
36.2  
45.0  
Phase  
FLA  
1.8  
4.0  
5.3  
6.9  
9.0  
LRA  
21.6  
27.5  
37.5  
39.2  
65.1  
380/415  
380/415  
380/415  
380/415  
380/415  
3
3
3
3
3
3
3
3
3
3
Table ED-4 UnitWiring Air Handler  
Minimum  
Unit Operating  
Voltage Range  
Maximum Fuse  
Circuit  
Ampacity  
Unit  
Model No.  
Size or Maximum  
Circuit Breaker  
TWE050  
TWE075  
TWE100  
TWE155  
TWE200  
380/415  
380/415  
380/415  
380/415  
380/415  
4
5
5
6
10  
15  
15  
15  
15  
15  
46  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electric Heat  
Data  
Table ED-5 UnitWiringWith Electric Heat (Single Point Connection) Air Handlers  
Heater  
Model No.  
Heater  
kW Rating1  
5.00  
To Use  
with Unit  
Control  
Stages  
Minimum  
Maximum  
Circuit Ampacity 2  
Fuse Breaker Size 2  
BAYHTRL405A  
BAYHTRL410A  
BAYHTRL415A  
BAYHTRL425A  
BAYHTRL405A  
BAYHTRL410A  
BAYHTRL415A  
BAYHTRL425A  
BAYHTRL435A  
BAYHTRL405A  
BAYHTRL410A  
BAYHTRL415A  
BAYHTRL425A  
BAYHTRL435A  
BAYHTRM410A  
BAYHTRM420A  
BAYHTRM430A  
BAYHTRM450A  
BAYHTRM410A  
BAYHTRM420A  
BAYHTRM430A  
BAYHTRM450A  
1
1
1
2
1
1
1
2
2
1
1
1
2
2
1
1
2
2
1
1
2
2
11  
17  
24  
37  
12  
18  
25  
38  
51  
12  
19  
25  
38  
52  
19  
32  
46  
72  
23  
36  
49  
76  
15  
20  
25  
40  
15  
20  
25  
40  
60  
15  
20  
25  
40  
60  
20  
35  
50  
80  
25  
40  
50  
80  
9.96  
TWE050AD  
TWE075AD  
14.96  
24.92  
5.00  
9.96  
14.96  
24.92  
34.88  
5.00  
9.96  
14.96  
29.92  
34.88  
10.00  
19.92  
29.92  
49.84  
10.00  
19.92  
29.92  
49.84  
TWE100AD,TWE100BD  
TWE155BD  
TWE200BD  
1. kW ratings are at 400v for 3 phase, 400v air handlers  
2
2
Voltage  
Voltage  
Rated Voltage  
For other than rated voltage, ampacity =  
x Rated Capacity and kW =  
Rated kW.  
(
)
(
)
Rated Voltage  
2. Any power supply and circuits must be wired and protected in accordance with local codes. MCA and Maximum Fuse Size is based on 400V.  
3. Field wire must be rated at least 167°F (75°C).  
4. Field wire must be rated at least 194°F (90°C).  
SS-PRC003-EN  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Jobsite  
Connections  
Wiring shown with dashed lines is to be  
furnished and installed by the customer.  
All customer- supplied wiring must be  
copper only and must conform to local  
electrical codes.  
NOTE:  
1.When electric heater accessory is  
used, single point power entry or dual  
point power entry is field optional.  
Single point power entry option is  
through electric heater only.  
TTA050/TWE050A  
FieldWiring:  
A — 3 power wires. Line voltage for  
3 phase, 2 wires for single phase.  
B — 3 power wires. Line voltage for  
3 phase, 2 wires for single phase.  
C — Cooling only thermostat: 3 wires,  
24 volts.  
— One-stage electric heat: add  
1 additional wire, 24 volts.  
Two-stage electric heat: add  
2 additional wires, 24 volts.  
D — 2 wires, 24 volts.  
D — 5 wires, 24 volts.  
(2)TTA050/TWE100B  
TTA075A/TWE075A;  
FieldWiring:  
TTA085/TWE075A;  
TTA125B/TWE155B;  
A — 3 power wires. Line voltage for  
3 phase, 2 wires for single phase.  
B — 3 power wires. Line voltage for  
3 phase, 2 wires for single phase.  
C — Cooling only thermostat: 4 wires,  
24 volts.  
— One-stage electric heat add  
1 additional wire, 24 volts.  
Two-stage electric heat: add  
2 additional wires, 24 volts.  
D — 2 wires, 24 volts to outdoor  
section ‘A’’  
TTA085/TWE100A;  
TTA155B/TWE155B;  
TTA100A/TWE100A  
TTA200B/TWE200B;  
FieldWiring:  
TTA155C/TWE155B  
A — 3 power wires, line voltage.  
B — 3 power wires, line voltage for  
3 phase; 2 wires for single phase.  
C — Cooling only thermostat: 3 wires,  
24 volts.  
FieldWiring  
A — 3 power wires, line voltage  
B — 3 power wires, line voltage  
C — Cooling only thermostat: 4 wires,  
24 volts.  
— One-stage electric heat: add  
1 additional wire, 24 volts.  
Two-stage electric heat: add  
2 additional wires; 24 volts.  
D — 4 wires, 24 volts.  
— One-stage electric heat: add  
1 additional wire, 24 volts.  
Two-stage electric heat: add  
2 additional wires, 24 volts.  
D — 5 wires, 24 volts.  
— 2 wires, 24 volts to outdoor  
section ‘’B’’  
TTA100B/TWE100B  
FieldWiring:  
A — 3 power wires, line voltage.  
B — 3 power wires, line voltage for  
3 phase; 2 wires for single phase.  
C — Cooling only thermostat: 4 wires,  
24 volts.  
(2)TTA075A/TWE155B;  
(2)TTA100A/TWE200B  
FieldWiring:  
A — 3 power wires, line voltage.  
B — 3 power wires, line voltage.  
C — Cooling only thermostat: 4 wires,  
24 volts.  
— One-stage electric heat: add  
1 additional wire, 24 volts.  
Two-stage electric heat: add  
2 additional wires, 24 volts.  
— One-stage electric heat: add  
1 additional wire, 24 volts.  
Two-stage electric heat: add  
2 additional wires, 24 volts.  
D — 6 wires, 24 volts.  
48  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
Air Handler  
Air Handler  
Typical wiring diagram. For specific  
wiring, see individual Service Facts.  
SS-PRC003-EN  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
Condensing Unit  
Condensing Unit Single Compressor  
Typical wiring diagram. For specific  
wiring, see individual Service Facts.  
50  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
Condensing Unit  
Condensing Unit Single Compressor  
SS-PRC003-EN  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
Condensing Unit  
Condensing Unit Dual Compressor  
Typical wiring diagram. For specific  
wiring, see individual Service Facts.  
52  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
Condensing Unit  
Condensing Unit Dual Compressor  
C757164P01  
SS-PRC003-EN  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-1 TTA075 Condensing Units  
All dimensions are in inches and millimeters.  
Note 1:  
Minimum Clearance for proper operation  
is 36 inches (914) from walls, shrubbery,  
privacy fences, etc. Minimum clearance  
between adjacent units is 72 inches (1829).  
54  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-2 TTA085A and 100A Condensing Units  
All dimensions are in inches and millimeters.  
Note 1:  
Minimum Clearance for proper operation  
is 36 inches (914) from walls, shrubbery,  
privacy fences, etc. Minimum clearance  
between adjacent units is 72 inches (1829).  
SS-PRC003-EN  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-3 TTA100C Condensing Units  
All dimensions are in inches and millimeters.  
Note 1:  
Minimum Clearance for proper operation  
is 36 inches (914) from walls, shrubbery,  
privacy fences, etc. Minimum clearance  
between adjacent units is 72 inches (1829).  
56  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-4 TTA100B andTTA125B Condensing Units  
All dimensions are in inches and millimeters.  
SS-PRC003-EN  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD- 5TTA155B Condensing Unit  
All dimensions are in inches and millimeters.  
Note 1:  
Minimum Clearance for proper operation  
is 36 inches (914) from walls, shrubbery,  
privacy fences, etc. Minimum clearance  
between adjacent units is 72 inches (1829).  
58  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-6 TTA155C Condensing Units  
All dimensions are in inches and millimeters.  
Note 1:  
Minimum Clearance for proper operation  
is 36 inches (914) from walls, shrubbery,  
privacy fences, etc. Minimum clearance  
between adjacent units is 72 inches (1829).  
SS-PRC003-EN  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-7 TTA200B Condensing Unit  
All dimensions are in inches and millimeters.  
Note 1:  
Minimum Clearance for proper operation  
is 36 inches (914) from walls, shrubbery,  
privacy fences, etc. Minimum clearance  
between adjacent units is 72 inches (1829).  
60  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-8 TWE050AAir Handlers  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dimensions do not include 1/2”  
(12.7mm) access panel depth.  
2. Removable drain pan and attached drain connection may be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection must be removed to slide drain pan out  
for cleaning. Access plate must be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
removal of pan on drain connection end of unit.  
SS-PRC003-EN  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-9 TWE075AAir Handlers  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dimensions do not include 1/2”  
(12.7mm) access panel depth.  
2. Removable drain pan and attached drain connection may be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection must be removed to slide drain pan out  
for cleaning. Access plate must be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
removal of pan on drain connection end of unit.  
62  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-10 TWE100A Air Handlers  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dimensions do not include 1/2”  
(12.7mm) access panel depth.  
2. Removable drain pan and attached drain connection may be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection must be removed to slide drain pan out  
for cleaning. Access plate must be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
removal of pan on drain connection end of unit.  
SS-PRC003-EN  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-11 TWE100B Air Handlers  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dimensions do not include 1/2”  
(12.7mm) access panel depth.  
2. Removable drain pan and attached drain connection may be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection must be removed to slide drain pan out  
for cleaning. Access plate must be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
removal of pan on drain connection end of unit.  
64  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-12 TWE050A, 075A, 100A andTWE100BAir Handlers  
All dimensions are in inches and millimeters.  
Table DD-1 Air Handler Dimensions in. (mm)  
Model No.  
TWE050A  
AA  
AB  
12 1/16  
(306.4)  
16  
(406.4)  
16  
(406.4)  
16  
(406.4)  
AC  
AD  
AE  
2 15/16  
(74.6)  
6 5/8  
AF  
AJ  
7 13/16  
(198.4)  
7
(177.8)  
7
(177.8)  
7
(177.8)  
AK  
12 3/8  
(314.3)  
16  
(406.4)  
16  
(406.4)  
16  
(406.4)  
AL  
35 5/8  
1 5/8  
32 1/4  
32 1/4  
34 9/16  
(878)  
(905)  
(41.3)  
1 11/16  
(42.9)  
1 11/16  
(42.9)  
1 11/16  
(42.9)  
(819.2)  
41 15/16  
(1065.2)  
57 15/16  
(1471.6)  
57 15/16  
(1471.6)  
(819.2)  
TWE075A  
TWE100A  
TWE100B  
45 1/8  
41 3/4  
36 7/8  
(1146.2)  
(168.3)  
(1060.5)  
57 13/16  
(1468.4)  
57 13/16  
(1468.4)  
(936.6)  
61 1/8  
6 5/8  
36 7/8  
(1552.6)  
61 1/8  
(1552.6)  
(168.3)  
6 5/8  
(168.3)  
(936.6)  
36 7/8  
(936.6)  
SS-PRC003-EN  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-13 TWE155B Air Handlers  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dimensions do not include 1/2”  
(12.7mm) access panel depth.  
2. Removable drain pan and attached drain connection may be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection must be removed to slide drain pan out  
for cleaning. Access plate must be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
removal of pan on drain connection end of unit.  
66  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-14 TWE200BAir Handlers  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dimensions do not include 1/2”  
(12.7mm) access panel depth.  
2. Removable drain pan and attached drain connection may be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection must be removed to slide drain pan out  
for cleaning. Access plate must be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
removal of pan on drain connection end of unit.  
SS-PRC003-EN  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-15 TWE155B and 200BAir Handlers  
All dimensions are in inches and millimeters.  
Table DD-2 Air Handler Dimensions in. (mm)  
Model No.  
TWE155B  
TWE200B  
A
B
C
D
E
F
G
H
J
77 1/4 (1962.2)  
89 1/4 (2267)  
1 3/16 (30.2)  
1 11/16 (42.9)  
48 (1219.2)  
11 7/16 (290.5)  
18 (457.2)  
3 3/8 (85.7)  
3 1/16 (77.8)  
35 1/16 (890.6)  
39 1/8 (993.8)  
73 7/8 (1876.4)  
82 7/8 (2105)  
3 3/4 (95.3)  
4 9/16 (115.9)  
50 13/16 (1290.6) 11 1/2 (292.1)  
20 1/8 (511.2)  
Table DD-2 Air Handler Dimensions in. (mm) (Continued)  
Model No.  
TWE155B  
TWE240B  
K
L
M
N
P
Q
R
S
T
35 1/16 (890.6)  
39 1/8 (993.8)  
2 13/16 (71.4)  
4 7/8 (123.8)  
18 (457.2)  
20 (508)  
3 9/16 (90.5)  
3 (76.2)  
2 7/8 (73)  
35 1/16 (890.6)  
39 1/8 (993.8)  
3 3/4 (95.3)  
4 9/16 (115.9)  
35 1/16 (890.6)  
39 1/8 (993.8)  
73 3/8 (1863.7)  
82 7/8 (2105)  
4 13/16 (122.2)  
68  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure 16 Electric Heater forTWE050, 075, 100 Air Handlers  
All dimensions are in inches and millimeters.  
Figure DD-17 Electric Heater forTWE155 and 200Air Handlers  
SS-PRC003-EN  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Table DD-3 Discharge Plenum And  
Figure DD-18 Discharge Plenum and Grille  
Grille Dimensions in. (mm)  
All dimensions are in inches and millimeters.  
Model  
Model No.  
A
B
C
28  
TWE050 BAYPLNM015  
TWE075 BAYPLNM016  
TWE100 BAYPLNM017  
3715/16 2115/16  
(963.6) (557.2) (711.2)  
471/2  
(1206.5) (635) (711.2)  
631/2  
25 28  
(1612.9) (635) (711.2)  
25  
28  
Table DD-4 Discharge Plenum And  
Grille Dimensions in. (mm)  
For Use with Electric Heat  
Model  
Model No.  
A
B
C
29  
TWE050 BAYPLNM025  
TWE075 BAYPLNM026  
TWE100 BAYPLNM027  
TWE155 BAYPLNM028  
TWE200 BAYPLNM029  
3715/16 2115/16  
(963.6) (557.2) (736.6)  
471/2  
(1206.5) (635) (736.6)  
631/2  
25 29  
(1612.9) (635) (736.6)  
791/2 2711/16  
35  
(2019.3) (703.3) (889)  
921/2  
35  
(2349.5) (773.1) (889)  
25  
29  
307/16  
Table DD-5 Subbase Dimensions  
Figure DD-19 Subbase  
in. (mm)  
Model  
Model No.  
A
B
TWE050 BAYBASE001  
TWE075 BAYBASE002  
TWE100 BAYBASE003  
TWE155 BAYBASE004  
TWE200 BAYBASE005  
38  
22  
(558.8)  
25  
(635)  
25  
(635)  
275/8  
(701.7)  
307/16  
(773.1)  
(965.2)  
471/2  
(1206.5)  
631/2  
(1612.9)  
791/2  
(2019.3)  
921/2  
(2349.5)  
70  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-20 HotWater Coil  
All dimensions are in inches and millimeters.  
3.00 (76 mm) DIA.  
HOLE FOR 2(50.8 mm) NPT  
SUPPLY  
3.00 (76 mm) DIA.  
HOLE FOR 2(50.8 mm) NPT  
RETURN  
329/32  
99 mm  
BAYWATR017  
3.00 (76 mm) DIA.  
HOLE FOR 2(50.8 mm) NPT  
SUPPLY  
3.00 (76 mm) DIA.  
HOLE FOR 2(50.8 mm) NPT  
RETURN  
BAYWATR018  
BAYWATR019  
BAYWATR020  
BAYWATR021  
Table DD-6 HotWater Coil Dimensions in. (mm)  
Model  
TWE050  
Accessory No.  
BAYWATR017  
A
38  
B
C
D
5
(127)  
5
(127)  
6
(152)  
6
E
9
F
G
14  
(356)  
14  
(356)  
16  
(406)  
16  
H
26  
(660)  
30  
(762)  
36  
(914)  
51  
J
12  
(305)  
18  
(457)  
18  
(457)  
18  
(457)  
18  
K
6
L
N
M
MM  
109/16  
(268)  
77/8  
223/32  
(561)  
255/32  
(639)  
255/32  
(639)  
2725/32  
(706)  
3019/32  
(777)  
135/8  
141/32  
(356)  
171/8  
(435)  
171/8  
(435)  
193/4  
(502)  
229/16  
(573)  
41/32  
227/32  
(72)  
227/32  
(72)  
227/32  
(72)  
17/8  
81/32  
(965)  
4719/32  
(1209)  
6319/32  
(1615)  
7921/32  
(2023)  
9221/32  
(2353)  
(346)  
1519/32  
(396)  
1519/32  
(396)  
147/16  
(367)  
163/8  
(229)  
1027/32  
(275)  
117/8  
(302)  
153/32  
(383)  
1423/32  
(374)  
(152)  
827/32  
(225)  
1327/32  
(352)  
147/32  
(361)  
147/32  
(361)  
(102)  
(204)  
103/8  
(264)  
103/8  
(264)  
99/16  
TWE075  
TWE100  
TWE155  
TWE200  
BAYWATR018  
BAYWATR019  
BAYWATR020  
BAYWATR021  
83/32  
(206)  
83/32  
(206)  
615/16  
(176)  
87/8  
(200)  
77/8  
(200)  
71/16  
(152)  
7
(178)  
(406)  
18  
(457)  
(1295)  
64  
(1626)  
(48)  
(243)  
(179)  
33/4  
99/16  
71/16  
(416)  
(457)  
(225)  
(95)  
(243)  
(179)  
SS-PRC003-EN  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Figure DD-21 Steam Coil  
All dimensions are in inches and millimeters.  
Table DD-7 Steam Coil Dimensions in. (mm)  
Model  
Accessory No.  
A
38  
B
C
D
5
E
9
F
G
14  
H
J
K
2
L
M
26  
N
12  
P
6
Q
R
TWE050 BAYWATR012  
TWE075 BAYWATR013  
TWE100 BAYWATR014  
TWE155 BAYWATR015  
TWE200 BAYWATR016  
221/8  
133/16  
141/16  
103/8  
113/8  
11/2  
27/8  
93/4  
(965.2) (562) (335)  
475/8  
(1209.7) (639.8) (503.2) (127) (276.2) (435) (355.6) (339.7) (288.9) (63.5) (50.8) (762) (457.2) (225.4) (73) (247.7)  
635/8 117/8 171/8 133/8 111/8 21/2 133/8 27/8 93/4  
16 36 18  
(1616.1) (639.8) (503.2) (152.4) (301.6) (435) (406.4) (339.7) (282.6) (63.5) (50.8) (914.4) (457.2) (339.7) (73) (247.7)  
795/8 193/4 181/2 111/8 21/2 17/8 93/4  
16 51 18  
(2022.5) (706.4) (633.4) (152.4) (382.6) (501.7) (406.4) (469.9) (282.6) (63.5) (50.8) (1295.4) (457.2) (360.4) (47.6) (247.7)  
925/8 305/8 257/8 143/4 191/2 121/6 21/2 33/4 107/8  
18 64 18  
(127) (228.6) (357.2) (355.6) (263.5) (288.9) (50.8) (38.1) (660.4) (304.8) (152.4) (73) (247.7)  
5
253/16  
253/16  
1913/16  
1913/16  
107/8 171/8 133/8 113/8 21/2 87/8 27/8 93/4  
14 30 18  
2
6
2
2713/16 2415/16  
6
151/16  
2
143/16  
143/16  
7
229/16  
2
(2352.7) (777.9) (657.2) (177.8) (374.7) (573.1) (457.2) (495.3) (309) (63.5) (50.8) (1625.6) (457.2) (360 .4) (95.3) (276.2)  
72  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weights  
TableW-1 Unit and CornerWeights lb (kg)  
Unit  
Shipping  
Net  
CornerWeights  
Model No.  
TTA075A  
Maximum lb (kg) Maximum lb (kg)  
1
105  
(47.6)  
134  
(60.8)  
153  
(69.4)  
139  
(63.0)  
153  
(69.4)  
192  
(87.1)  
216  
2
80  
3
59  
4
78  
(35.4)  
94  
(42.6)  
83  
(37.7)  
86  
(39.0)  
89  
(40.4)  
142  
(64.4)  
118  
366  
(166.0)  
444  
(201.4)  
514  
322  
(146.1)  
390  
(176.9)  
460  
(36.3)  
95.5  
(43.3)  
145  
(65.8)  
125  
(56.7)  
156  
(70.8)  
192  
(26.8)  
66.5  
(30.2)  
79  
(35.8)  
78  
(35.4)  
90  
(40.8)  
142  
(64.4)  
115  
(52.2)  
176  
(79.8)  
TTA100A  
TTA100B  
TTA100C  
TTA125B  
TTA155B  
TTA155C  
TTA200B  
(233.1)  
483  
(219.1)  
542  
(208.7)  
428  
(194.1)  
488  
(245.9)  
744  
(337.5)  
745  
(221.4)  
668  
(303.0)  
660  
(87.1)  
211  
(95.7)  
232  
(337.9)  
915  
(415.0)  
(299.4)  
830  
(376.5)  
(98.0)  
240  
(108.9)  
(53.5)  
182  
(82.6)  
(105.2)  
TableW-2 AccessoryWeights Net lb (kg)  
Unit  
Model No.  
TTA075A  
RIS  
Steel Spring  
Isolators  
12  
Anti Short  
Coil  
Guard  
8
(3.6)  
11  
(5)  
20  
Low  
Ambient  
23  
(10.4)  
23  
(10.4)  
23  
Isolators  
CycleTimer  
Thermostats  
2
(.9)  
2
(.9)  
2
1
(.5)  
1
(.5)  
1
1
(.5)  
1
(.5)  
1
(5.4)  
12  
(5.4)  
12  
TTA100A  
TTA100B  
TTA125B  
(.9)  
2
(.9)  
2
(.9)  
(5.4)  
12  
(5.4)  
12  
(5.4)  
(.5)  
1
(.5)  
1
(.5)  
(9.1)  
22  
(10)  
34  
(.5)  
1
(.5)  
1
(.5)  
(10.4)  
23  
(10.4)  
23  
(10.4)  
TTA155D  
TTA155C  
TTA200B  
(15.4)  
TTA155, 200  
TTA075, 100, 125  
SS-PRC003-EN  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weights  
TableW-3 Air Handlers, Coils,And CornerWeights lb (kg)1  
Unit  
Model No.  
TWE050  
Shipping  
Maximum (lb)  
298  
Net  
Maximum (lb)  
262  
CornerWeights Vertical  
CornerWeights Horizontal  
#1  
59  
(26.8)  
79  
(35.9)  
107  
(48.5)  
173  
#2  
59  
(26.8)  
79  
#3  
59  
(26.8)  
79  
#4  
59  
(26.8)  
79  
(35.9)  
107  
(48.5)  
173  
A
54  
(24.5)  
77  
(35)  
102  
(46.3)  
174  
(79)  
185  
(84)  
B
64  
C
64  
(29.03)  
81  
D
54  
(24.5)  
73  
(33.1)  
102  
(46.3)  
170  
(77.1)  
179  
(81.2)  
(135)  
(118.9)  
346  
(157)  
419  
(190.1)  
690  
(313)  
820  
(372)  
(29)  
TWE075  
TWE100  
TWE125  
TWE200  
388  
(176)  
473  
(214.6)  
754  
(342)  
886  
(401.9)  
84  
(35.9)  
107  
(48.5)  
173  
(35.9)  
107  
(48.5)  
173  
(38.1)  
113  
(51.3)  
156  
(36.7)  
113  
(51.3)  
190  
(78.5)  
204  
(92.5)  
(78.5)  
204  
(92.5)  
(78.5)  
204  
(92.5)  
(78.5)  
204  
(92.5)  
(70.8)  
228  
(103.4)  
(86.2)  
221  
(100.3)  
Note:  
1. If application requires steam or hot water heating coils, field supplied isolators must be utilized.  
Vertical  
TWE050, 075, 100  
Vertical  
TWE155, 200  
Horizontal  
TWE050, 075, 100  
Horizontal  
TWE155, 200  
TableW-4 AccessoryWeights (Net lb)  
RIS  
RIS  
Isolator  
Suspended  
Mount  
9
Steel Spring Steel Spring  
Discharge  
Plenum  
And Grille1  
58  
Discharge  
Plenum  
And Grille2  
93  
Electric  
Heat  
Min. Max.  
32/43  
Isolator  
Floor  
Mount  
2
Isolator  
Floor  
Mount  
12  
Isolator  
Suspended  
Mount  
6
Unit  
Return  
Air Grille  
3
Oversized  
Motor  
31  
Model No.  
TWE050  
Subbase  
14  
(26.3)  
73  
(33.1)  
92  
(41.7)  
124  
(56.3)  
145  
(42.2)  
123  
(55.8)  
156  
(70.8)  
230  
(104.3)  
264  
(1.4)  
5
(2.3)  
7
(3.2)  
10  
(4.5)  
12  
(14.5/19.5)  
27/45  
(12.3/20.4)  
27/45  
(12.3/20.4)  
79/100  
(35.8/45.4)  
79/100  
(6.4)  
19  
(8.6)  
23  
(10.4)  
27  
(12.3)  
31  
(14.1)  
48  
(21.8)  
50  
(22.7)  
80  
(36.3)  
88  
(.9)  
2
(.9)  
2
(.9)  
2
(.9)  
2
(4)  
6
(2.7)  
7
(3.2)  
7
(3.2)  
9
(5.4)  
12  
(5.4)  
12  
(5.4)  
12  
(5.4)  
12  
(2.7)  
6
(2.7)  
6
(2.7)  
6
(2.7)  
6
TWE075  
TWE100  
TWE155  
TWE200  
(65.8)  
(119.8)  
(5.4)  
(35.8/45.4)  
(14.06)  
(40)  
(.9)  
(4)  
(5.4)  
(2.7)  
Note:  
1. For use when no heat is supplied.  
2. For use with electric heat.  
74  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications Condensing Units  
General  
Refrigeration System Dual Compressor  
TTA100B,TTA125B,TTA155B,TTA200B  
units shall have two separate and  
independent refrigeration circuits. Each  
refrigeration circuit shall have an integral  
subcooling circuit. A refrigeration filter  
drier shall be provided as standard.  
Units shall have both a liquid line and  
suction gas line service valve with gauge  
port.  
Refrigeration System Dual  
Units shall be assembled on heavy  
gauge steel mounting/lifting rails and  
shall be weatherproofed. Units shall  
include a hermetic scroll or reciprocating  
compressor(s), plate fin condenser coil,  
fans and motors, controls, and holding  
charge of nitrogen. Operating range  
shall be between 115°F (46.1°C) and 35°F  
(1.7°C) in cooling as standard from the  
factory. Units shall be rated in  
Manifolded Compressors  
TTA 100C andTTA155C units shall have  
a single refrigeration circuit with an  
integral subcooling circuit. A  
refrigeration filter drier shall be  
provided as standard. Units shall have  
both a liquid line and suction gas line  
service valve with gauge port.  
The units shall have two scroll  
compressors manifolded together.  
Motor shall be suction gas-cooled and  
shall have a voltage utilization range of  
plus or minus 10 percent of nameplate  
voltage. Crankcase heater, discharge  
line thermostat, and current-sensitive  
motor overloads shall be included for  
maximum protection. Scroll type  
compressor shall provide inherently  
low vibration and noise by having no  
suction and discharge valves. External  
high and low pressure cutout devices  
shall be provided. Evaporator defrost  
control provided in the indoor blower  
coil shall prevent compressor slugging  
by temporarily interrupting  
accordance with ARI Standard 210/240,  
340/360 or 365.  
TTA100B,TTA125B, units shall have two  
Trane direct-drive, hermetic  
reciprocating compressors with  
centrifugal oil pump and provide  
positive lubrication to all moving parts.  
Reciprocating compressor shall have  
internal spring isolation and sound  
muffling to minimize vibration  
transmission and noise.  
Casing  
Unit casing shall be constructed of zinc  
coated, heavy gauge, galvanized steel.  
Exterior surfaces shall be cleaned,  
phosphatized, and finished with a  
weather-resistant baked enamel finish.  
Units surface shall be tested 500 hours  
in salt spray test. Units shall have  
removable end panels which allow  
access to all major components and  
controls.  
TTA155B,TTA200B units shall have two  
Trane direct-drive, hermetic scroll  
compressors with centrifugal oil pump  
and provide positive lubrication to all  
moving parts. Motor shall be suction  
gas-cooled and shall have a voltage  
utilization range of plus or minus 10  
percent of nameplate voltage. Crankcase  
heater, discharge line thermostat, and  
current-sensitive motor overloads shall  
be included for maximum protection.  
Scroll compressor shall provide  
inherently low vibration and noise by  
having no suction and discharge valves.  
External high and low pressure cutout  
devices shall be provided. Evaporator  
defrost control provided in indoor  
blower coil shall prevent compressor  
slugging by temporarily interrupting  
compressor operation when low  
evaporator coil temperatures are  
encountered.  
Refrigeration System Single  
Compressor  
TTA075A,TTA100A units shall have a  
single refrigeration circuit. Each  
compressor operation when low  
evaporator coil temperatures are  
encountered.  
refrigeration circuit has an integral  
subcooling circuit. A refrigeration filter  
drier shall be provided as standard.The  
units shall have both a liquid line and  
suction gas line service valve with gauge  
port.TTA075A,TTA100A units shall have  
one direct-drive, hermetic scroll  
compressor with centrifugal oil pump  
providing positive lubrication to moving  
parts. Motor shall be suction gas-cooled  
and shall have a voltage utilization range  
of plus or minus 10 percent of unit  
nameplate voltage. Crankcase heater,  
discharge line thermostat, and current-  
sensitive motor overloads shall be  
included for maximum protection. Scroll  
type compressor shall provide  
inherently low vibration and noise by  
having no suction and discharge valves.  
External high and low pressure cutout  
devices shall be provided. Evaporator  
defrost control provided in indoor  
blower coil shall prevent compressor  
slugging by temporarily interrupting  
compressor operation when low  
evaporator coil temperatures are  
encountered.  
Condenser Coil  
Coils shall be internally finned or  
smooth bore 3/8(10 mm) copper tubes  
mechanically bonded to a configured  
aluminum plate fin as standard. Coil  
shall be factory pressure and leak  
tested to 420 psig (2,899 kPa) air  
pressure. Metal grilles with PVC  
coating for coil protection is optional.  
Condenser Fan And Motor(s)  
Direct-drive, statically and dynamically  
balanced, 26 or 28-inch (660 or 711  
mm) propeller fan(s) with aluminum  
blades and electro- coated steel hubs  
shall be used in draw-thru vertical  
discharge position. Either permanently  
lubricated totally enclosed or open  
construction motors shall be provided  
and shall have built-in current and  
thermal overload protection. Motor(s)  
shall have be either ball or sleeve  
bearing type.  
SS-PRC003-EN  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications Condensing Units  
Controls  
Hot Gas Bypass Kit This accessory  
shall be available to provide capacity  
modulation.  
Condensing units shall be completely  
factory wired with necessary controls  
and contactor pressure lugs or  
terminal block for power wiring.  
Control wiring shall be 24-volt control  
circuit which includes fusing and  
control transformer. Units shall provide  
external location for mounting a fused  
disconnect device.Time delay timers to  
prevent compressors in dual  
Time Delay Relay This accessory  
shall prevent compressors in dual  
compressor unit from combine on line  
simultaneously.Time shall be 24-volt,  
60 cycle, with four minute timing  
period.  
Anti-Short-CycleTimer This  
accessory shall prevent rapid on-off  
compressor cycling in light load  
conditions by not allowing compressor  
to operate for 5-7 minutes upon  
shutdown.This accessory shall consist  
of a 24-volt, solid state timing device  
with either 5 or 7 minute fixed-off  
timing period.  
compressor units from simultaneous  
start-up and anti- recycle timers are  
available as optional accessories.  
Low Ambient Operation  
Standard units shall start and operate  
to approximately 35°F (1.7°C) when  
matched withTrane air handlers and  
coils. Optional head pressure control  
accessory permits operation to 0°F (-  
17.8°C).  
Condenser Coil Guard Metal grille  
with PVC coating shall be provided to  
alleviate coil damage.  
Accessories  
Factory InstalledAccessories  
Low Ambient Head Pressure Control  
This accessory shall modulate the  
RPM of unit outdoor fan motor in  
response to outdoor ambient  
temperature and unit head pressure.  
Accessory provides unit cooling  
operation to outdoor temperatures of  
0° F (-17.8° C).  
Black Epoxy Coated Condenser Coil —  
This option is designed to provide  
corrosion protection of air cooled  
condenser coils for seacoast  
application.The black epoxy coil  
protection is a factory applied  
thermoset vinyl coating, bonded to  
normal aluminum fin stock.The  
uniform thickness of the bonded vinyl  
layer exhibits excellent corrosion  
protection in salt spray tests performed  
in accordance with ASTM B177.  
Vibration Isolation Packages This  
accessory shall reduce transmission of  
noise and vibration to building  
structures, equipment, and adjacent  
spaces. Packages shall be available in  
either neoprene-in-shear or spring-flex  
types.  
76  
SS-PRC003-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications Air Handlers  
General  
Evaporator Fan  
Discharge Plenums and Grilles —  
Accessory discharge plenums shall be  
available for vertical, free discharge  
applications. Plenums shall be  
constructed of heavy-gauge, zinc coated,  
galvanized steel finished with baked  
enamel to match the air handler unit.  
Grilles shall be satin finished aluminum  
and have four-way adjustable louvers.  
Air handler units shall be completely  
factory assembled including coil,  
condensate drain pan, fan motor(s),  
filters, and controls in an insulated  
casing that can be applied in either  
vertical or horizontal configuration. Units  
shall be rated and tested in accordance  
with ARI Standard 210, 240, 360.  
Double inlet, double width, forward  
curved, centrifugal-type fan(s) with  
adjustable belt drive shall be standard.  
Thermal overload protection shall be  
standard on motor. Fan and motor  
bearings shall be permanently  
lubricated. Oversized motors shall be  
available as an option for high static  
application.  
Casing  
ReturnAir Grilles Accessory return air  
grille shall be provided for vertical front,  
free return applications. Grilles shall be  
installed in place of the front lower side  
panel. Grille shall be satin finished  
Unit casing shall be constructed of zinc  
coated, heavy gauge, galvanized steel.  
Exterior surfaces shall be cleaned,  
phosphatized, and finished with a  
weather-resistant baked enamel finish.  
Casing is completely insulated with fire-  
retardant, permanent, odorless, glass  
fiber material. Knockouts shall be  
provided for unit electrical power and  
refrigerant piping connections. Captive  
screws shall be standard on all access  
panels.  
Controls  
Magnetic evaporator fan contactor, low  
voltage terminal strip, check valve(s), and  
single point power entry shall be  
included. All necessary controls shall be  
factory-installed and wired. Evaporator  
defrost control shall be included to  
prevent compressor slugging by  
temporarily interrupting compressor  
operation when low evaporator coil  
temperatures are encountered.  
aluminum with non-adjustable louvers.  
Mounting Subbase This accessory  
shall be available for vertical floor mount  
configurations. Subbase shall be  
constructed of heavy gauge, zinc coated,  
galvanized steel with baked enamel  
finish to match air handler unit. Subbase  
is required in the vertical air flow  
application for condensate drain  
trapping and when isolators are  
required.  
Filters  
Refrigeration System  
One inch, throwaway filters shall be  
standard onTWE050A,TWE050B,  
TWE075A,TWE100A andTWE100B  
model air handlers. Filters shall be  
accessible from the side coil access  
panel. Filter rack can be field converted  
to two-inch capability.Two-inch  
throwaway filters shall be standard on  
TWE155B andTWE200B models.  
TheTWE050A,TWE075A,TWE100A units  
shall have a single refrigeration circuit  
and theTWE050B,TWE100B,TWE155B,  
TWE200B units shall have dual  
Vibration Isolators This accessory  
shall reduce transmission of noise and  
vibration to building structures,  
equipment, and adjacent spaces.  
Packages shall be available in either  
neoprene-in shear or spring-flex types in  
floor or suspended mountings.  
refrigeration circuits. Each refrigeration  
circuit is controlled by a factory installed  
thermal expansion valve.  
Evaporator Coil  
Configured aluminum fin surface shall  
be mechanically bonded to 3/8(10 mm)  
internally enhanced copper tubing and  
factory pressure and leak tested at 375  
psig (2,586 kPa). Coil is arranged for  
draw-thru airflow and shall provide  
condensate drain pan constructed of  
PVC plastic and provide external  
connections on either side of the unit.  
Accessories  
Electric Heaters Approved electric  
heat modules shall be available for  
installation directly on fan discharge.  
Electric heaters shall be available in a  
wide range of capacities with one or  
two-stage control, single-point electric  
power connection and terminal strip  
connections. Electric heater elements  
shall be constructed on heavy-duty  
nickel chromium elements internally  
wye connected on 480 volt, three phase.  
Each 480 volt heater shall have  
Oversized Motors Field installed  
oversized motors shall be available for  
high static pressure applications.  
Control Options  
Standard IndoorThermostats Two  
stage heating and cooling operation or  
one stage heating and cooling  
thermostats shall be available in either  
manual or automatic changeover.  
Programmable Electronic Night Setback  
Thermostat The option shall provide  
heating setback and cooling setup with  
7-day programming capability.  
automatic line break high limit controls.  
SS-PRC003-EN  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Literature Order Number  
File No.  
SS-PRC003-EN  
PL-UN-SS-PRC003-EN-12-00  
TheTrane Company  
An American Standard Company  
Supersedes  
SS-PRC003-EN 07-00  
Inland - LaCrosse  
Stocking Location  
For more information contact your  
local office or e-mail us at  
SinceTheTrane Company has a policy of continuous product and product data improvement, it reserves the right  
to change design and specifications without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Texas Instruments Calculator TLV320AIC12KEVMB K User Manual
Texas Instruments Electric Heater TLC3578EVM User Manual
Texas Instruments Music Mixer TPA0202 User Manual
Toshiba DVD Player SD K740 User Manual
Toshiba Laptop 4010 User Manual
Tripp Lite Network Cables F005 006 User Manual
Troy Bilt Tiller 630B Tuffy User Manual
Vector Work Light VEC157 User Manual
ViewSonic Computer Monitor VA2216w User Manual
Viking Ventilation Hood DIV1200 User Manual