Split System
Cooling Units
Split System Cooling Units
TTA075A-TTA200B
Air Handlers
TWE050A-TWE200B
50 Hz
December 2000
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Introduction
2
4
7
Features and Benefits
Application Considerations
Selection Procedure
8
9
Model Number Description
General Data
10
Performance Data
13
Cooling Performance
Fan Performance
13
39
46
Electric Power
Connection andWiring
Dimension andWeights
Mechanical Specifications
48
54
75
SS-PRC003-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Features
and Benefits
Condensing Units
Air Handlers
Trane 3-D® scroll compressor
(TTA075-100A)
Low voltage terminal board
Expansion valve(s)
•
•
•
•
•
•
•
•
•
•
•
(2)Trane Climatuff™ compressors
(TTA100-125B) with independent
refrigerant circuits
Convertible
PVC drain pan
Fan relay
(2)Trane 3-D scroll compressors
(TTA155-200B) with independent
refrigerant circuits
2) Manifolded scroll compressors with
unloading capability (TTA100-155C)
Compressor motor overload protection
Control transformer
High and low pressure cutout switches
Internal pressure relief valve (TTA100B-
125B)
Liquid line filter drier, factory installed
Holding charge of nitrogen
Copper tube, aluminum plate fin coils
Low ambient cooling to 35°F (1.7°C) as
manufactured
Efficient evaporator coil
Baked enamel finish
•
•
•
•
•
•
•
•
•
•
•
•
•
Filter access panel
1” (25.4 mm) throwaway filters standard
with provisions for field supplied 2”
(50.8 mm) filters
Adjustable belt drive motor
Single point power entry to electric
heaters
Refrigerant piping and/or electrical
connections provided from either side
Odyssey™ air handler versatility is
further increased by a complete line of
optional accessories designed to match
and easy to install:
Discharge Plenum and Grille
Return Grille
Subbase
Electric Heaters
High Static Evaporator Motor
Isolators both Rubber-in-Shear and
SpringType
•
•
•
Weather resistant baked enamel finish
Heavy gauge steel cabinet
Mounting/lifting rails under base
•
•
•
•
•
•
All condensing units offer these
optional accessories:
Head Pressure Control — Low Ambient
CoolingTo 0°F (-17.8°C)
Coil Guards Kits
•
•
Isolators both Rubber-in-Shear and
SpringType
•
Anti-Short-Cycle Kit
•
•
•
Time Delay Relay
Black Epoxy Coated Condenser Coils
4
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Features
and Benefits
Condensing Units Options
In addition, Odyssey modelsTTA100B,
TTA125B,TTA155B andTTA200B are dual
compressor units to give true standby
protection; if one compressor fails, the
second will automatically start-up. Also,
the first compressor can be serviced
without shutting down the unit since
refrigerant circuits are independent.
The Odyssey™ split system product line
includes condensing units in both single
unloading and dual compressor options.
TTA075A andTTA100A-ton single
compressor models feature single
refrigeration circuitry lowering job
installation costs by requiring only one
set of refrigerant lines.These units are
ideal for their low cost, new construction
jobs, as well as renovation and
Dual compressors are not just for
protection; they also save energy costs.
Most buildings are designed for the peak
load requirements, yet the building
usually operates at less than peak load.
During light load conditions only one
compressor functions to maintain the
space comfort thus reducing the need
for energy.
replacement buildings.
Equally important, Odyssey offers a
single refrigerant circuit/capacity
unloading option inTTA100C and
TTA155C condensing units. These
unloading units feature dual manifolded
scroll compressors. They offer an
excellent opportunity for both new
construction and replacement jobs with
two stages of capacity modulation and a
single refrigeration circuit.
Trane split systems have been specified
in thousands of applications.You will
find Odyssey will win even more jobs
with its smaller, more manageable
cabinet.
LowAmbient Cooling Operation
Each condensing unit can operate to
35°F (1.7°C) as standard. An accessory
Head Pressure Control gives you the
capability to operate to 0°F (-17.8°C).
SS-PRC003-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Features
and Benefits
Air Handlers Offer
More Flexibility
Flexibility is a key to meeting changing
market requirements. Odyssey split
systems offer not only various
compressor options but also convertible
air handlers.The air handlers can be
installed either vertically in a mechanical
room or horizontally above a ceiling.
They do not require any removal of
panels or reconfiguration of the drain
pan to make either airflow application
work.These air handlers have a double
sloped condensate drain pan that allows
for either airflow configuration and can
easily be removed for cleaning. All the
air handlers feature factory installed belt
drive and ball bearing evaporator fans
with adjustable sheaves for maximum
airflow performance.The standard motor
on theTWE100A air handler will deliver
3325 cfm (5650 m3/h) at 1.0” (250 Pa) ESP.
Additionally, oversized motors are
available for higher static applications.
Odyssey air handler versatility is further
increased by a complete line of
accessories designed to match and install
smoothly:
Discharge Plenum and Grille
Return Grille
•
•
•
•
•
•
Subbase
Electric Heaters
High Static Evaporator Motor
Isolators both Rubber-in-Shear and
SpringType
A Full Line ofThermostats
Odyssey™ —A Complete
Split System
•
Odyssey delivers the flexibility to select a
complete system that meets your
particular job requirements. Air Handlers
are designed, tested, and rated with
condensing units to let you select the
proper match between capacity and load.
Condensing units can also be matched
withTrane built-up air handlers.These
matched systems can be quickly
engineered for specific applications using
Trane’s computerized selection
programs.
6
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Application
Considerations
Application of this product should be
within the catalogued airflow and
performance considerations.
LowAmbient Cooling
As manufactured, these units can
operate to 35°F (1.7°C) in the cooling
mode of operation. An accessory head
pressure control will allow operation to
0°F (-17.8°C) outdoor ambient.When
using these units with control systems
such as bypass changeoverVariable Air
Volume, consider the requirement for a
head pressure control to allow low
ambient cooling.
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate
serviceability, maximum capacity and
peak operating efficiency. Actual
clearances that appear inadequate
should be reviewed with your localTrane
Representative.
Typical HorizontalAir HandlerApplication
Typical Split System Application
TypicalVerticalAir HandlerApplication
SS-PRC003-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Selection
Procedure
Cooling Capacity
Note:The formula below the table can
be used to calculate Fan Motor Heat,
3.5 x Bhp = MBh
Step 1 — Calculate the building’s total
and sensible cooling loads at design
conditions. Use theTrane calculation
form or any other standard accepted
method.
3.5 x 1.17 = 4.10 MBh
1.375 x (kW) = kW
1.375 x 0.8 = 1.1 kW
Step 2 — Size the equipment usingTable
13-1. Match the cooling loads at design
conditions.
NetTotal Cooling Capacity =
77.7 MBh – 4.10 = 73.6 MBh
16.8 - 1.2 = 15.6 kW
Net Sensible Cooling Capacity =
57.3 MBh – 4.10 = 53.2 MBh
22.8 - 1.2 = 21.6 kW
Example:The following are the building
cooling requirements
a
Electrical Characteristics: 380-415/50/3
Heating Capacity
b
Step 1 — Calculate the building heating
Summer Design Conditions: Entering
load.
Evaporator Coil: 80 DB/67WB
Step 2 — Size the system heating
(27 DB/19WB C)
capacity to match the calculated building
Outdoor Ambient: 95° F (35° C)
heating load.The following are building
c
heating requirements:
Total Cooling Load: 75 MBh (22 kW)
a
d
Total Heating Load at 97.0 MBh (28.4 kW)
Sensible Cooling Load: 53 MBh
b
(15.5 kW)
3000 cfm (5097 m3/h)
e
Airflow: 3000 cfm (5097 m3/h)
External Static Pressure: 0.77 in.
(192.5 Pa)
c
Electric Supplementary Heaters
Table 45-1, the 34.88 kW heater has a
capacity of 119,045 btu. FromTable
47-1, the 34.88 kW indicates the heater
model number is BAYHTRL435A.This
heater will adequately cover the
building’s heating requirement.
Table 13-1 shows that aTTA075A
matched with aTWE075A has a gross
cooling capacity of 77.7 MBh (22.8 kW)
and 57.3 MBh (16.8 kW) sensible capacity
at 95 DB (35° C) ambient and 3000 cfm
(5097 m3/h) and 80 DB/67WB (27 DB/19
WB) air entering the evaporator.
Air Delivery Selection
External static pressure drop through
the air distribution system has been
calculated to be 0.77 inches (192.5 Pa) of
water gauge. FromTable 44-2 static
pressure drop through the electric
heater is 0.23 inches (57.5 Pa) of water
(0.77 + 0.23 = 1.00 in.) (192.5 + 57.5 = 250
Pa). EnterTable 39-1 forTWE075AD at
3000 cfm (5097 m3/h) and 1.00 static
pressure (250 Pa).The standard motor at
821 rpm will give the desired airflow.
To find the net cooling capacities, fan
motor heat must be subtracted.
Determine the total unit static pressure:
In.
0.77 193
0.10 25
Pa
External Static
Standard Filter
Supplementary
Electric Heat
0.23 57
Total Static Pressure 1.10 275
Note:The Evaporator Fan Performance
Table has included the effect of a 1 in.
(250 Pa) filter already.Therefore, the
actualTotal Static Pressure is 1.10 - 0.10 =
1.00 in. (275 - 25 = 250 Pa).
With 3000 cfm (5097 m3/h) and 1.00
inches (250 Pa), Table 39-1 shows a 1.17
bhp (0.8 kW).
8
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Number
Description
CONDENSING UNIT MODEL NOMENCLATURE
T T A 0 7 5
A
D
0 0
B
0
Service Digit
TTA = Cooling Only
Minor Design Sequence
Nominal Gross Cooling Capacity (MBh)
075 = 75
100 = 100
155 = 155
200 = 200
Factory Installed Options
00 = No Options
0S = Black Epoxy Coated Condenser Coil
Electrical Characteristics
D = 380-415/3/50
Compressor
A = Single Compressor
B = Dual Compressor
C = Scroll
AIR HANDLER MODEL NOMENCLATURE
T W E 0 5 0
A
D
0 0
B
0
Service Digit
TWE = Cooling Convertible
Minor Design Sequence
Nominal Gross Cooling Capacity (MBh)
050 = 50
075 = 75
100 = 100
155 = 155
200 = 200
Factory Installed Options
00 = No Options
Electrical Characteristics
D = 380-415/3/50
Refrigerant Circuit
A = Single
B = Dual
SS-PRC003-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
Condensing Unit
Table GD-1 — General Data
TTA075A
TTA085A
TTA100A
TTA100B
Cooling Performance1
Gross Cooling Capacity, btu (kW)
Matched Air Handler (kW)
Condensing Unit Only2 (kW)
ARI Net Cooling Capacity3 (kW)
System Power kW
Condensing Unit Power kW
Compressor
82,000(24.01)
80,000(23.36)
79,000(23.06)
7.92
91,000(26.64)
91,000(26.64)
87,000(25.47)
8.7
111,000(32.59)
107,000(31.36)
107,000(31.36)
10.66
102,000(30.0)
102,000(30.0)
100,000(29.3)
11.3
7.32
7.8
9.76
10.3
Number
1
1
1
2
Type
Trane 3-D® Scroll
Trane 3-D® Scroll
Trane 3-D® Scroll
Trane Climatuff™
2
No. Speeds
No. Motors
Motor HP (kW)
1
1
1
1
1
1
6.25 (4.7)
2875
8.8
6.91(5.16)
2875
8.8
8.33(6.21)
2875
8.8
4.15(3.1)
2875
9.0
Motor RPM
ARI Sound Rating (Bels)4
System Data5
No. Refrigerant Circuits
Suction Line in. (mm) OD
Liquid Line in. (mm) OD
Outdoor Coil —Type
Tube Size in. (mm) OD
Face Area, sq. ft (m2)
Rows
Fins Per Inch
Outdoor FanType
No. Used
1
1.375(34.9)
0.500(12.7)
Plate Fin
0.375(9.5)
15.33(1.42)
2
20(508)
Propeller
1
1
1
1.375(34.9)
0.500(12.7)
Plate Fin
0.375(9.5)
18.4(1.71)
2
20(508)
Propeller
1
2
1.120(28.5)
0.375(9.5)
Plate Fin
0.375(9.5)
18.43(5.6)
2
20(508)
Propeller
1
1.375(34.9)
0.500(12.7)
Plate Fin
0.375(9.5)
18.43(1.71)
2
20(508)
Propeller
1
Diameter in. (mm)
DriveType
26.00(660.4)
Direct
28.00(711.2)
Direct
28.00(711.2)
Direct
28.00(711.2)
Direct
No. Speeds
1
1
1
1
CFM6 (m3/h)
No. Motors
4700(7985)
1
6500(11042)
1
6500(11042)
1
6500(11042)
1
Motor HP (kW)
Motor RPM
0.33(.24)
925
13.0(5.90)
0.75(.56)
925
16.0(7.26)
0.75(.56)
975
16.0(7.26)
0.75(.55)
925
18.8(8.5)
R-22 Refrigerant Charge, lb7 (kg)
Notes:
1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (26.7°C) entering dry bulb, 67°F (19.4°C) entering wet bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this
product. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of
nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.
2. Condensing Unit Only Gross Cooling Capacity rated at 45°F (7.2°C) saturated suction temperature and at 95°F (35°C) ambient.
3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft (7.2 m) of 1.375, 0.500 OD interconnecting tubing. EER and/or SEER are rated at ARI conditions and in
accordance with DOE test procedures. Integrated Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80°F (26.7°C) ambient, 80°F (26.7°C) entering dry bulb,
and 67°F (19.4°C) entering wet bulb at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270.
5. System Data based on maximum linear length 80 ft (26.7 m) Maximum lift: suction 60 ft (18.3 m) liquid 60 ft (18.3 m) For greater lengths, refer to refrigerant piping applications
manual.
6. Outdoor Fan cfm is rated with standard air-dry coil outdoor.
7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft (7.6 m) of interconnecting refrigerant lines.
10
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
Condensing Unit
Table GD-2— General Data
TTA100C
TTA125B
TTA155B
TTA155C
TTA200B
Cooling Performance1
Gross Cooling Capacity, btu (kW)
Matched Air Handler
Condensing Unit Only2
ARI Net Cooling Capacity3
System Power kW
Condensing Unit Power kW
Compressor
108,000(31.62)
108,000(31.62)
106,000(31.05)
9.61
127,000(37.2)
127,000(37.2)
123,000(36.0)
13.1
166,000(48.60)
163,000(47.73)
161,000(47.14)
16.01
160,000(46.85)
155,000(45.39)
153,000(44.80)
15.4
216,000(63.24)
209,000(61.18)
209,000(61.18)
21.40
9.01
12.1
14.58
14.6
19.39
Number
Type
No. Speeds
No. Motors
2
2
2
2
2
ScrollTandem
2
Trane Climatuff™
Trane 3-D® Scroll
Trane 3-D® ScrollTandem
Trane 3-D® Scroll
1
2
1
2
1
1
1
2
Motor HP (kW)
4.16(3.10)
2875
8.8
5.20(3.9)
2875
8.8
6.25(4.7)
2875
8.8
6.25(4.7)
2875
8.8
8.33(6.21)
2875
8.8
Motor RPM
ARI Sound Rating (Bels)4
System Data5
No. Refrigerant Circuits
Suction Line in. (mm) OD
Liquid Line in. (mm) OD
Outdoor Coil —Type
Tube Size in. (mm) OD
Face Area, sq. ft (m2)
Rows
Fins Per Inch
Outdoor FanType
No. Used
1
1.375(34.9)
0.500(12.7)
Plate Fin
0.375(9.5)
18.4(1.71)
2
20 (508)
Propeller
1
2
2
1.375(34.9)
0.500(12.7)
Plate Fin
0.375(9.5)
30.66(2.84)
2
20(508)
Propeller
2
1
1.625(41.3)
0.625(15.9)
Plate Fin
0.375(9.5)
30.66(2.84)
2
20 (508)
Propeller
2
2
1.375(34.9)
0.500(12.7)
Plate Fin
0.375(9.5)
43.9(4.08)
2
15(381)
Propeller
2
1.375(34.9)
0.500(12.7)
Plate Fin
0.375(9.5)
23.97(7.3)
2
18(457.2)
Propeller
1
Diameter in. (mm)
DriveType
28.00(711.2)
Direct
28.00(711.2)
Direct
26.00(660.4)
Direct
26.00(660.4)
Direct
28.00(711.2)
Direct
No. Speeds
1
1
1
1
1
CFM6 (m3/h)
No. Motors
6500(11042)
1
6760(11484)
1
9400(15969)
1
9400(15969)
1
13400(22764)
2
Motor HP (kW)
Motor RPM
0.75(.56)
925
15.5(7.03)
0.75(.55)
925
25.2(11.4)
0.33(.24)
925
26.0(11.8)
0.33(.24)
925
27.0(12.34)
0.75(.56)
925
36.0(16.33)
R-22 Refrigerant Charge, lb7 (kg)
Notes:
1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (26.7°C) entering dry bulb, 67°F (19.4°C) entering wet bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this
product. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of
nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.
2. Condensing Unit Only Gross Cooling Capacity rated at 45°F (7.2°C) saturated suction temperature and at 95°F (35°C) ambient.
3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft (7.2 m) of 1.375, 0.500 OD interconnecting tubing. EER and/or SEER are rated at ARI conditions and in
accordance with DOE test procedures. Integrated Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80°F (26.7°C) ambient, 80°F (26.7°C) entering dry bulb,
and 67°F (19.4°C) entering wet bulb at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270.
5. System Data based on maximum linear length 80 ft (26.7 m) Maximum lift: suction 60 ft (18.3 m) liquid 60 ft (18.3 m) For greater lengths, refer to refrigerant piping applications
manual.
6. Outdoor Fan cfm is rated with standard air-dry coil outdoor.
7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft (7.6 m) of interconnecting refrigerant lines.
SS-PRC003-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
Air Handler
Table GD-3 — General Data
TWE050A
TWE075A
TWE100A
TWE100B
System Data1
No. Refrigerant Circuits
Suction Line in. (mm) OD
Liquid Line in. (mm) OD
Indoor Coil —Type
Tube Size in. (mm) OD
Face Area sq. ft (m2)
Rows
1
1.120(28.4)
0.38(9.7)
Plate Fin
0.375(9.5)
5.00(.47)
3
1
1
2
1.380(35.0)
0.50(12.7)
Plate Fin
0.375(9.5)
11.18(1.0)
3
1.380(35.0)
0.50(12.7)
Plate Fin
0.375(9.5)
8.07(.75)
3
1.380(35.0)
0.50(12.7)
Plate Fin
0.375(9.5)
11.18(1.0)
3
Fins Per Inch
12
12
12
12
Refrigerant Control
Drain Connection No.
Drain Connection Size in. (mm)
Drain ConnectionType
Indoor FanType
No. Used
ExpansionValve
4
0.75(19.0)
PVC
FC Centrifugal
ExpansionValve ExpansionValve
ExpansionValve
4
0.75(19.0)
PVC
FC Centrifugal
4
0.75(19.0)
PVC
4
0.75(19.0)
PVC
FC Centrifugal
FC Centrifugal
1
1
1
1
Diameter in. (mm)
Width in. (mm)
12.0(304.8)
12.0(304.8)
Belt
15.0(381)
15.0(381)
Belt
15.0(381)
15.0(381)
Belt
15.0(381)
15.0(381)
Belt
DriveType
No. Speeds
1
1
1
1
CFM (m3/h)
1670(2837)
1
2500(4247)
1
3325(5649)
1
3325(5649)
1
No. Motors
Motor HP (kW)
- Standard/Oversized
Motor RPM (Standard)
Motor Frame Size (Standard)
Filters —Type
Furnished
No.
0.75/1.0(.55/.74)
1.0/1.5(.74/1.11)
1.5/2.0(1.11/1.49)
1.5/2.0(1.11/1.49)
1425
56
1425
56
1425
56
1425
56
Throwaway
Yes
Throwaway
Yes
Throwaway
Yes
Throwaway
Yes
1/1
3
4
4
Recommended Size, in. (mm) 16x20x1/20x20x1
16x25x1
16x25x1
16x25x1
(406.4x508x25.4/
(406.4x635x25.4) (406.4x635x25.4) (406.4x635x25.4)
508x508x25.4)
Notes:
1. ARI certified with various condensing units per ARI Standard 210/240 or 340/360-93. Refer to Performance Data
section in this catalog.
Table GD-4 — General Data
TWE155B
TWE200B
System Data
No. Refrigerant Circuits
Suction Line in. (mm) OD
Liquid Line in. (mm) OD
Indoor Coil —Type
Tube Size in. (mm) OD
Face Area sq. ft (m2)
Rows
2
1.38(35.0)
0.500(12.7)
Plate Fin
0.375(9.5)
16.33(1.52)
3
2
1.38(35.0)
0.500(12.7)
Plate Fin
0.375(9.5)
21.63(2.01)
3
Fins Per Inch
12
12
Refrigerant Control
Drain Connection No.
Drain Connection Size in. (mm)
Drain ConnectionType
Indoor FanType
ExpansionValve
4
1.000(25.4)
PVC
ExpansionValve
4
1.000(25.4)
PVC
FC Centrifugal
FC Centrifugal
No. Used
Diameter in. (mm)
Width in. (mm)
2
2
15.0(381)
15.0(381)
Belt
15.0(381)
15.0(381)
Belt
DriveType
No. Speeds
1
1
CFM (m3/h)
5000(8494)
1
6650(11297)
1
No. Motors
Motor HP — Standard/Oversized
Motor RPM (Standard)
Motor Frame Size (Standard)
Filters —Type
Furnished
No.
2.0/3.0(1.49/2.24)
1425
145T
Throwaway
3.0/5.0(2.24/3.72)
1425
184T
Throwaway
Yes
8
Yes
4/4
Recommended Size, in. (mm)
15x20x2
(381x508x50.8)
16x20x2/16x25x2
(406.4x508x50.8/
406.4x635x50.8)
Notes:
1. ARI certified with various condensing units per ARI Standard 210/240 or 340/360-93. Refer to Performance Data
section in this catalog.
12
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-1 — Gross Cooling Capacities (MBh) TTA075A Condensing Unit withTWE075AAir Handler
(I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75.7
76.2
77.8
81.8
77.3
77.9
80.4
84.6
78.6
79.4
82.7
86.9
79.7
80.8
84.6
89.0
59.6 83.5 50.1 91.7 34.0
69.5 83.7 57.4 92.0 44.6
77.8 84.1 67.3 92.4 54.9
81.8 84.6 77.2 92.5 64.8
62.3 85.1 49.2 93.1 34.5
73.2 85.3 59.9 93.6 46.1
80.4 85.7 70.6 94.0 57.4
84.6 86.4 81.6 94.2 67.9
64.9 86.3 50.8 94.2 35.2
76.7 86.6 62.2 94.8 47.5
82.7 87.0 73.9 95.3 59.7
86.9 88.0 85.8 95.5 70.9
67.3 87.4 52.3 95.2 35.7
80.1 87.7 64.5 95.9 48.8
84.6 88.2 77.0 96.1 61.3
89.0 89.1 89.1 96.7 73.7
73.1
73.6
75.6
79.4
74.5
75.2
78.0
82.0
75.7
76.6
80.1
84.3
76.7
77.7
82.0
86.3
58.2 80.5 48.8 88.2 32.7 69.9 56.6 76.9 47.4 84.1 31.3 66.3 54.8 72.9 45.8 79.5 29.8
68.1 80.6 56.0 88.6 43.3 70.5 66.6 77.1 54.4 84.7 41.8 67.0 64.8 73.2 52.6 80.3 40.3
75.6 81.1 65.9 89.0 53.6 72.9 72.9 77.6 64.2 85.1 52.2 69.9 69.9 73.7 62.5 80.8 50.6
79.4 81.6 75.8 89.2 63.4 76.7 76.7 78.3 74.3 85.3 61.8 73.5 73.5 74.5 72.5 81.1 60.1
60.9 81.9 47.8 89.4 33.3 71.2 59.2 78.2 46.3 85.2 31.8 67.5 57.4 74.1 44.6 80.6 30.3
71.8 82.1 58.5 90.0 44.8 72.0 70.2 78.5 56.8 85.9 43.3 68.5 68.4 74.4 55.0 81.5 41.7
78.0 82.6 69.2 90.4 56.0 75.2 75.2 78.9 67.6 86.2 54.1 72.0 72.0 74.9 65.7 81.8 52.4
82.0 83.4 80.2 90.7 66.5 79.1 79.1 79.9 78.6 86.7 64.9 75.8 75.8 75.9 75.9 82.4 63.1
63.4 83.0 49.4 90.4 33.9 72.3 61.7 79.3 47.9 86.1 32.4 68.5 59.8 74.7 45.7 81.4 30.8
75.3 83.3 60.8 91.1 46.2 73.1 73.1 79.6 59.1 87.0 44.7 69.9 69.9 75.5 57.2 82.5 43.1
80.1 83.8 72.4 91.4 57.8 77.2 77.2 80.1 70.7 87.3 56.2 73.8 73.8 76.1 68.9 82.9 54.4
84.3 85.0 84.4 91.9 69.4 81.2 81.2 81.3 81.3 87.9 67.8 77.8 77.8 77.9 77.9 83.4 66.0
65.9 84.0 51.0 91.3 34.3 73.2 64.1 79.8 48.9 86.9 32.8 69.4 62.2 75.6 47.0 82.1 31.2
77.7 84.4 63.0 92.1 47.5 74.8 74.8 80.6 61.3 87.9 46.0 71.4 71.4 76.4 59.4 83.3 44.4
82.0 84.9 75.5 92.4 59.8 78.9 78.9 81.2 73.8 88.3 58.2 75.5 75.5 77.1 72.0 83.8 56.3
86.3 86.4 86.4 93.0 72.3 83.1 83.1 83.2 83.2 88.8 70.6 79.6 79.6 79.6 79.6 84.3 68.8
2250
2500
2750
3000
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-1 — Gross Cooling Capacities (kW) TTA075A Condensing Unit withTWE075AAir Handler
(SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Bulb
Entering Wet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
22.2
22.3
22.8
24.0
22.6
22.8
23.5
24.8
23.0
23.2
24.2
25.5
23.3
23.7
24.8
26.1
17.5 24.5 14.7 26.9 9.9
20.4 24.5 16.8 26.9 13.1
22.8 24.6 19.7 27.1 16.1
24.0 24.8 22.6 27.1 19.0
18.2 24.9 14.4 27.3 10.1
21.4 25.0 17.5 27.4 13.5
23.5 25.1 20.7 27.5 16.8
24.8 25.3 23.9 27.6 19.9
19.0 25.3 14.9 27.6 10.3
22.5 25.4 18.2 27.8 13.9
24.2 25.5 21.6 27.9 17.5
25.5 25.8 25.1 28.0 20.8
19.7 25.6 15.3 27.9 10.4
23.5 25.7 18.9 28.1 14.3
24.8 25.8 22.5 28.1 18.0
26.1 26.1 26.1 28.3 21.6
21.4
21.5
22.1
23.3
21.8
22.0
22.8
24.0
22.2
22.4
23.5
24.7
22.4
22.8
24.0
25.3
17.0 23.6 14.3 25.8 9.6 20.5 16.6 22.5 13.9 24.6 9.2 19.4 16.0 21.4 13.4 23.3 8.7
20.0 23.6 16.4 25.9 12.7 20.6 19.5 22.6 15.9 24.8 12.3 19.6 19.0 21.4 15.4 23.5 11.8
22.1 23.7 19.3 26.1 15.7 21.3 21.3 22.7 18.8 24.9 15.3 20.5 20.5 21.6 18.3 23.7 14.8
23.3 23.9 22.2 26.1 18.6 22.5 22.5 22.9 21.7 25.0 18.1 21.5 21.5 21.8 21.2 23.7 17.6
17.8 24.0 14.0 26.2 9.7 20.8 17.3 22.9 13.6 24.9 9.3 19.8 16.8 21.7 13.1 23.6 8.9
21.0 24.0 17.1 26.3 13.1 21.1 20.6 23.0 16.6 25.2 12.7 20.1 20.0 21.8 16.1 23.9 12.2
22.8 24.2 20.3 26.5 16.4 22.0 22.0 23.1 19.8 25.2 15.9 21.1 21.1 21.9 19.3 24.0 15.3
24.0 24.4 23.5 26.5 19.5 23.2 23.2 23.4 23.0 25.4 19.0 22.2 22.2 22.2 22.2 24.1 18.5
18.6 24.3 14.5 26.5 9.9 21.2 18.1 23.2 14.0 25.2 9.5 20.0 17.5 21.9 13.4 23.8 9.0
22.1 24.4 17.8 26.7 13.5 21.4 21.4 23.3 17.3 25.5 13.1 20.5 20.5 22.1 16.8 24.2 12.6
23.5 24.5 21.2 26.8 16.9 22.6 22.6 23.5 20.7 25.6 16.5 21.6 21.6 22.3 20.2 24.3 15.9
24.7 24.9 24.7 26.9 20.3 23.8 23.8 23.8 23.8 25.7 19.8 22.8 22.8 22.8 22.8 24.4 19.3
19.3 24.6 14.9 26.7 10.0 21.4 18.8 23.4 14.3 25.4 9.6 20.3 18.2 22.1 13.8 24.0 9.1
22.8 24.7 18.4 27.0 13.9 21.9 21.9 23.6 17.9 25.7 13.5 20.9 20.9 22.4 17.4 24.4 13.0
24.0 24.9 22.1 27.1 17.5 23.1 23.1 23.8 21.6 25.8 17.0 22.1 22.1 22.6 21.1 24.5 16.5
25.3 25.3 25.3 27.2 21.2 24.3 24.3 24.4 24.4 26.0 20.7 23.3 23.3 23.3 23.3 24.7 20.2
3823
4248
4673
5098
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
SS-PRC003-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-2 — Gross Cooling Capacities (MBh) TTA075A Condensing Unit withTWE100AAir Handler
(I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
Entering Wet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
79.9
80.7
83.7
88.0
81.5
82.8
86.7
91.2
82.9
84.6
89.2
93.9
84.2
86.6
91.4
96.2
65.5 87.9 54.1 95.9 35.7
77.2 88.1 62.8 96.6 48.0
83.7 88.5 74.4 97.0 60.0
88.0 89.5 86.2 97.2 71.4
69.1 89.5 53.5 97.3 36.4
82.3 89.8 66.1 98.2 49.9
86.7 90.3 79.0 98.6 63.3
91.2 91.2 91.2 98.8 75.6
72.6 90.8 55.7 98.5 37.0
84.6 91.2 69.3 99.4 51.8
89.2 91.9 83.4 99.7 65.7
93.9 93.9 93.9 100.2 79.7
75.9 91.6 57.1 99.4 37.6
86.6 92.3 72.3 100.5 53.5
91.4 93.2 87.7 100.9 68.4
96.2 96.2 96.2 101.4 83.6
76.9
77.9
81.1
85.3
78.4
79.6
83.9
88.3
79.8
81.8
86.3
90.9
80.9
83.7
88.4
93.0
64.0 84.5 52.7 92.0 34.4 73.5 62.2 80.7 51.2 87.7 32.9 69.6 60.3 76.4 49.5 82.9 31.3
75.8 84.8 61.3 92.8 46.6 74.6 74.1 81.0 59.6 88.6 45.1 70.8 70.8 76.8 57.7 84.0 43.5
81.1 85.2 72.9 93.3 58.7 78.1 78.1 81.5 71.2 89.2 57.2 74.8 74.8 77.3 69.4 84.3 54.9
85.3 86.3 84.8 93.5 69.9 82.2 82.2 82.3 82.3 89.4 68.3 78.8 78.8 78.9 78.9 84.9 66.5
67.6 86.0 52.1 93.3 35.1 74.9 65.8 82.0 50.5 88.8 33.5 70.9 63.8 77.2 48.1 83.9 31.8
79.6 86.3 64.6 94.3 48.5 76.5 76.5 82.4 62.8 90.0 47.0 73.1 73.1 78.1 60.9 85.3 45.4
83.9 86.9 77.5 94.5 61.3 80.8 80.8 83.1 75.8 90.3 59.6 77.2 77.2 78.9 73.9 85.7 57.8
88.3 88.4 88.4 95.1 74.1 85.1 85.1 85.2 85.2 90.8 72.5 81.4 81.4 81.5 81.5 86.2 70.7
71.0 86.9 53.7 94.3 35.6 76.1 69.2 82.8 51.9 89.7 34.1 72.1 67.2 78.3 49.9 84.6 32.4
81.8 87.6 67.7 95.5 50.4 78.6 78.6 83.6 65.9 91.1 48.9 75.0 75.0 79.1 63.9 86.3 47.2
86.3 88.4 81.9 95.8 64.1 83.0 83.0 84.5 80.1 91.5 62.4 79.3 79.3 80.2 78.2 86.8 60.5
90.9 90.9 90.9 96.3 78.2 87.4 87.4 87.5 87.5 92.1 76.5 83.7 83.7 83.8 83.8 87.4 74.7
74.3 87.9 55.5 95.1 36.2 77.2 72.5 83.7 53.6 90.4 34.6 73.1 70.4 79.1 51.6 85.1 32.9
83.7 88.7 70.7 96.5 52.1 80.4 80.4 84.5 68.9 92.0 50.6 76.7 76.7 80.0 66.9 87.1 49.0
88.4 89.7 86.1 96.9 66.8 84.9 84.9 85.8 84.4 92.5 65.1 81.1 81.1 81.2 81.2 87.7 63.1
93.0 93.1 93.1 97.5 82.1 89.5 89.5 89.6 89.6 93.1 80.4 85.6 85.6 85.7 85.7 88.5 78.6
2550
2875
3200
3525
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-2 — Gross Cooling Capacities (kW) TTA075A Condensing Unit withTWE100A Air Handler
(SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Bulb
EnteringWet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.4
23.6
24.5
25.8
23.9
24.2
25.4
26.7
24.3
24.8
26.1
27.5
24.6
25.4
26.8
28.2
19.2 25.7 15.8 28.1 10.5
22.6 25.8 18.4 28.3 14.0
24.5 25.9 21.8 28.4 17.6
25.8 26.2 25.2 28.4 20.9
20.2 26.2 15.7 28.5 10.7
24.1 26.3 19.4 28.7 14.6
25.4 26.4 23.1 28.9 18.5
26.7 26.7 26.7 28.9 22.1
21.2 26.6 16.3 28.8 10.8
24.8 26.7 20.3 29.1 15.2
26.1 26.9 24.4 29.2 19.2
27.5 27.5 27.5 29.3 23.3
22.2 26.8 16.7 29.1 11.0
25.4 27.0 21.2 29.4 15.7
26.8 27.3 25.7 29.5 20.0
28.2 28.2 28.2 29.7 24.5
22.5
22.8
23.8
25.0
23.0
23.3
24.6
25.9
23.4
24.0
25.3
26.6
23.7
24.5
25.9
27.2
18.7 24.7 15.4 26.9 10.1 21.5 18.2 23.6 15.0 25.7 9.6 20.4 17.7 22.4 14.5 24.3 9.2
22.2 24.8 18.0 27.2 13.6 21.8 21.7 23.7 17.5 26.0 13.2 20.7 20.7 22.5 16.9 24.6 12.7
23.8 25.0 21.3 27.3 17.2 22.9 22.9 23.9 20.9 26.1 16.7 21.9 21.9 22.6 20.3 24.7 16.1
25.0 25.3 24.8 27.4 20.5 24.1 24.1 24.1 24.1 26.2 20.0 23.1 23.1 23.1 23.1 24.9 19.5
19.8 25.2 15.3 27.3 10.3 21.9 19.3 24.0 14.8 26.0 9.8 20.8 18.7 22.6 14.1 24.6 9.3
23.3 25.3 18.9 27.6 14.2 22.4 22.4 24.1 18.4 26.3 13.8 21.4 21.4 22.9 17.8 25.0 13.3
24.6 25.5 22.7 27.7 18.0 23.7 23.7 24.3 22.2 26.4 17.5 22.6 22.6 23.1 21.6 25.1 16.9
25.9 25.9 25.9 27.8 21.7 24.9 24.9 24.9 24.9 26.6 21.2 23.8 23.8 23.9 23.9 25.3 20.7
20.8 25.4 15.7 27.6 10.4 22.3 20.3 24.2 15.2 26.3 10.0 21.1 19.7 22.9 14.6 24.8 9.5
24.0 25.7 19.8 28.0 14.8 23.0 23.0 24.5 19.3 26.7 14.3 22.0 22.0 23.2 18.7 25.3 13.8
25.3 25.9 24.0 28.1 18.8 24.3 24.3 24.7 23.5 26.8 18.3 23.2 23.2 23.5 22.9 25.4 17.7
26.6 26.6 26.6 28.2 22.9 25.6 25.6 25.6 25.6 27.0 22.4 24.5 24.5 24.5 24.5 25.6 21.9
21.8 25.7 16.3 27.9 10.6 22.6 21.2 24.5 15.7 26.5 10.1 21.4 20.6 23.2 15.1 24.9 9.6
24.5 26.0 20.7 28.2 15.3 23.5 23.5 24.8 20.2 26.9 14.8 22.4 22.4 23.4 19.6 25.5 14.3
25.9 26.3 25.2 28.4 19.6 24.9 24.9 25.1 24.7 27.1 19.0 23.7 23.7 23.8 23.8 25.7 18.5
27.2 27.3 27.3 28.5 24.0 26.2 26.2 26.2 26.2 27.3 23.5 25.1 25.1 25.1 25.1 25.9 23.0
4331
4885
5436
5990
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
14
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-3 — Gross Cooling Capacities (MBh) TTA085A Condensing Unit withTWE075AAir Handler
(I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
83.0
83.2
83.7
86.2
84.8
85.2
86.1
89.5
86.6
87.0
88.3
92.4
88.1
88.5
90.2
95.0
61.8 92.0 53.4 102.2 37.6
70.5 92.3 59.7 102.2 48.0
79.6 92.4 68.8 102.5 57.4
86.2 92.8 77.8 102.8 66.7
64.2 94.2 52.1 104.4 38.4
73.9 94.5 62.3 104.5 49.4
84.0 94.6 72.0 104.8 59.6
89.5 95.0 81.7 105.1 69.8
66.6 96.0 53.6 106.2 39.2
77.1 96.3 64.6 106.3 50.8
88.1 96.5 75.0 106.7 61.8
92.4 96.9 85.5 107.0 72.8
68.9 97.5 55.1 107.7 39.9
80.2 97.9 66.9 107.9 52.1
90.2 98.2 77.8 108.3 63.8
95.0 98.6 89.1 108.4 75.1
80.0
80.4
81.1
84.0
81.9
82.3
83.4
87.1
83.5
84.0
85.3
89.9
85.0
85.5
87.7
92.3
60.1 88.9 52.1 98.7 36.4 76.9 58.5 85.6 50.7 95.0 35.1 73.7 56.8 82.1 49.3 91.2 33.8
69.0 89.2 58.3 98.8 46.6 77.4 67.4 86.0 56.8 95.2 45.1 74.2 65.7 82.5 55.3 91.3 43.6
78.2 89.4 67.3 99.1 56.0 78.2 76.6 86.1 65.7 95.5 54.5 75.3 75.0 82.7 64.1 91.8 53.0
84.0 89.8 76.3 99.4 65.3 81.5 81.5 86.5 74.7 95.8 63.9 78.9 78.9 83.1 73.1 92.1 62.4
62.6 90.9 50.6 100.8 37.1 78.8 61.0 87.5 49.1 96.9 35.8 75.4 59.2 83.9 47.5 92.9 34.4
72.4 91.3 60.8 100.9 48.0 79.2 70.7 87.9 59.3 97.1 46.5 75.9 69.0 84.3 57.7 93.2 45.0
82.5 91.5 70.4 101.2 58.2 80.2 80.2 88.1 68.8 97.5 56.8 77.6 77.6 84.6 67.2 93.6 55.3
87.1 91.9 80.2 101.6 68.4 84.5 84.5 88.5 78.6 97.9 67.0 81.8 81.8 85.0 76.9 93.8 65.0
65.0 92.6 52.2 102.4 37.9 80.3 63.3 89.0 50.6 98.4 36.5 76.9 61.6 85.3 49.0 94.2 35.1
75.5 93.0 63.2 102.6 49.3 80.8 73.9 89.2 61.3 98.7 47.8 77.5 72.1 85.6 59.6 94.7 46.3
85.3 93.2 73.4 103.0 60.4 82.7 82.7 89.8 71.8 99.2 58.9 79.9 79.9 86.1 70.1 95.2 57.4
89.9 93.6 83.9 103.1 71.0 87.2 87.2 90.2 82.3 99.3 69.4 84.3 84.3 86.7 80.7 95.4 67.7
67.3 94.0 53.6 103.8 38.6 81.6 65.6 90.4 52.1 99.7 37.2 78.1 63.8 86.6 50.5 95.4 35.7
78.6 94.2 65.0 104.1 50.6 82.2 76.9 90.6 63.4 100.1 49.1 78.9 75.2 86.9 61.6 96.0 47.6
87.7 94.8 76.2 104.5 62.4 84.9 84.9 91.2 74.6 100.6 60.9 82.1 82.1 87.5 72.8 96.5 59.4
92.3 95.3 87.6 104.7 73.6 89.5 89.5 91.8 85.9 100.8 72.0 86.6 86.6 88.3 84.3 96.8 70.3
2250
2500
2750
3000
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-3 — Gross Cooling Capacities (kW) TTA085A Condensing Unit withTWE075AAir Handler
(SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Bulb
Entering Wet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24.3
24.3
24.5
25.3
24.8
25.0
25.2
26.2
25.3
25.5
25.8
27.1
25.8
25.9
26.4
27.8
18.1 26.9 15.6 29.9 11.0
20.6 27.0 17.5 29.9 14.0
23.3 27.1 20.1 30.0 16.8
25.3 27.2 22.8 30.1 19.5
18.8 27.6 15.2 30.6 11.3
21.6 27.7 18.2 30.6 14.5
24.6 27.7 21.1 30.7 17.5
26.2 27.8 23.9 30.8 20.4
19.5 28.1 15.7 31.1 11.5
22.6 28.2 18.9 31.1 14.9
25.8 28.3 22.0 31.2 18.1
27.1 28.4 25.0 31.3 21.3
20.2 28.6 16.1 31.5 11.7
23.5 28.7 19.6 31.6 15.2
26.4 28.7 22.8 31.7 18.7
27.8 28.9 26.1 31.7 22.0
23.4
23.5
23.7
24.6
24.0
24.1
24.4
25.5
24.5
24.6
25.0
26.3
24.9
25.0
25.7
27.0
17.6 26.0 15.3 28.9 10.7 22.5 17.1 25.1 14.9 27.8 10.3 21.6 16.6 24.0 14.4 26.7 9.9
20.2 26.1 17.1 28.9 13.6 22.7 19.7 25.2 16.6 27.9 13.2 21.7 19.2 24.2 16.2 26.7 12.8
22.9 26.2 19.7 29.0 16.4 22.9 22.4 25.2 19.2 28.0 16.0 22.0 22.0 24.2 18.8 26.9 15.5
24.6 26.3 22.3 29.1 19.1 23.9 23.9 25.3 21.9 28.1 18.7 23.1 23.1 24.3 21.4 27.0 18.3
18.3 26.6 14.8 29.5 10.9 23.1 17.9 25.6 14.4 28.4 10.5 22.1 17.3 24.6 13.9 27.2 10.1
21.2 26.7 17.8 29.5 14.1 23.2 20.7 25.7 17.4 28.4 13.6 22.2 20.2 24.7 16.9 27.3 13.2
24.1 26.8 20.6 29.6 17.0 23.5 23.5 25.8 20.2 28.6 16.6 22.7 22.7 24.8 19.7 27.4 16.2
25.5 26.9 23.5 29.7 20.0 24.7 24.7 25.9 23.0 28.7 19.6 24.0 24.0 24.9 22.5 27.5 19.0
19.0 27.1 15.3 30.0 11.1 23.5 18.5 26.1 14.8 28.8 10.7 22.5 18.0 25.0 14.4 27.6 10.3
22.1 27.2 18.5 30.0 14.4 23.7 21.6 26.1 17.9 28.9 14.0 22.7 21.1 25.1 17.5 27.7 13.6
25.0 27.3 21.5 30.2 17.7 24.2 24.2 26.3 21.0 29.0 17.2 23.4 23.4 25.2 20.5 27.9 16.8
26.3 27.4 24.6 30.2 20.8 25.5 25.5 26.4 24.1 29.1 20.3 24.7 24.7 25.4 23.6 27.9 19.8
19.7 27.5 15.7 30.4 11.3 23.9 19.2 26.5 15.2 29.2 10.9 22.9 18.7 25.4 14.8 27.9 10.5
23.0 27.6 19.0 30.5 14.8 24.1 22.5 26.5 18.6 29.3 14.4 23.1 22.0 25.4 18.0 28.1 13.9
25.7 27.8 22.3 30.6 18.3 24.9 24.9 26.7 21.8 29.5 17.8 24.0 24.0 25.6 21.3 28.3 17.4
27.0 27.9 25.6 30.7 21.5 26.2 26.2 26.9 25.2 29.5 21.1 25.4 25.4 25.8 24.7 28.3 20.6
3823
4248
4673
5098
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
15
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-4 — Gross Cooling Capacities (MBh) TTA085A Condensing Unit withTWE100AAir Handler
(I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
Entering Wet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
87.9
88.3
89.3
93.2
90.0
90.5
92.0
96.8
91.8
92.4
95.0
67.0 97.4 57.4 107.7 39.8
77.4 97.8 65.0 107.9 51.3
88.1 98.0 75.3 108.3 62.2
93.2 98.3 85.7 108.7 73.0
70.2 99.6 56.2 109.9 40.6
81.6 100.1 68.1 110.2 53.1
92.0 100.3 79.2 110.7 65.0
96.8 100.7 90.7 110.8 76.5
73.2 101.5 58.1 111.6 41.4
85.7 101.7 70.6 112.1 54.7
95.0 102.2 82.9 112.7 67.7
84.8
85.2
86.1
90.6
86.8
87.3
89.4
94.1
88.5
89.2
92.2
97.2
89.9
90.8
94.8
99.9
65.4 93.9 56.0 103.9 38.3 81.5 63.7 90.3 54.5 99.8 36.8 78.0 61.9 86.5 53.0 95.4 35.5
75.8 94.4 63.4 104.1 49.8 81.9 74.1 90.8 61.9 100.2 48.3 78.5 72.3 86.7 59.9 96.0 46.7
86.1 94.6 73.7 104.6 60.7 83.4 83.4 91.0 72.0 100.7 59.2 80.6 80.6 87.3 70.2 96.6 57.6
90.6 95.0 84.1 104.9 71.5 87.9 87.9 91.4 82.4 100.8 69.6 85.0 85.0 87.8 80.7 96.8 67.9
68.5 96.0 54.6 105.8 39.2 83.4 66.8 92.3 53.0 101.5 37.7 79.8 64.9 88.3 51.4 97.0 36.1
80.0 96.5 66.5 106.3 51.6 83.9 78.2 92.5 64.5 102.2 50.0 80.5 76.4 88.6 62.7 97.9 48.4
89.4 96.7 77.5 106.8 63.5 86.6 86.6 93.0 75.8 102.7 62.0 83.6 83.6 89.2 74.1 98.5 60.4
94.1 97.2 89.0 106.9 74.9 91.2 91.2 93.6 87.4 102.9 73.2 88.2 88.2 89.9 85.6 98.7 71.5
71.5 97.7 56.5 107.3 40.0 85.0 69.7 93.9 54.9 102.9 38.5 81.3 67.8 89.8 53.2 98.3 36.9
84.0 98.0 68.9 108.0 53.2 85.7 82.2 94.2 67.1 103.8 51.6 82.2 80.4 90.2 65.3 99.4 50.0
92.2 98.6 81.3 108.6 66.2 89.3 89.3 94.7 79.5 104.4 64.6 86.2 86.2 90.8 77.7 99.7 62.5
97.2 99.3 93.8 108.9 78.3 94.1 94.1 95.6 92.1 104.7 76.6 91.0 91.0 91.9 90.4 100.4 74.9
74.3 99.2 58.3 108.6 40.7 86.3 72.5 95.2 56.7 104.1 39.1 82.5 70.6 91.1 55.0 99.4 37.4
87.9 99.5 71.4 109.5 54.8 87.4 86.1 95.6 69.7 105.2 53.2 83.6 83.6 91.5 67.8 100.7 51.6
94.8 100.1 84.8 110.2 68.7 91.7 91.7 96.2 83.0 105.5 66.6 88.5 88.5 92.1 81.2 101.1 64.8
99.9 101.1 98.4 110.5 81.6 96.7 96.7 97.5 96.7 106.2 79.9 93.4 93.4 93.5 93.5 101.8 78.1
2500
2800
3100
3400
100.0 100.0 102.8 95.4 112.9 80.0
93.4
94.1
97.7
76.1 103.0 59.9 113.0 42.2
89.6 103.3 73.2 113.7 56.3
97.7 103.9 86.5 114.3 70.3
102.9 102.9 104.7 100.1 114.6 83.3
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-4 — Gross Cooling Capacities (kW) TTA085A Condensing Unit withTWE100A Air Handler
(SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Bulb
EnteringWet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
25.7
25.9
26.1
27.3
26.4
26.5
26.9
28.4
26.9
27.1
27.8
29.3
27.3
27.6
28.6
30.1
19.6 28.5 16.8 31.5 11.6
22.7 28.6 19.0 31.6 15.0
25.8 28.7 22.0 31.7 18.2
27.3 28.8 25.1 31.8 21.4
20.6 29.2 16.4 32.2 11.9
23.9 29.3 19.9 32.3 15.5
26.9 29.4 23.2 32.4 19.0
28.4 29.5 26.5 32.4 22.4
21.4 29.7 17.0 32.7 12.1
25.1 29.8 20.7 32.8 16.0
27.8 29.9 24.3 33.0 19.8
29.3 30.1 27.9 33.0 23.4
22.3 30.2 17.5 33.1 12.4
26.2 30.2 21.4 33.3 16.5
28.6 30.4 25.3 33.5 20.6
30.1 30.7 29.3 33.6 24.4
24.8
24.9
25.2
26.5
25.4
25.6
26.2
27.6
25.9
26.1
27.0
28.4
26.3
26.6
27.8
29.2
19.1 27.5 16.4 30.4 11.2 23.9 18.6 26.4 16.0 29.2 10.8 22.8 18.1 25.3 15.5 27.9 10.4
22.2 27.6 18.6 30.5 14.6 24.0 21.7 26.6 18.1 29.3 14.1 23.0 21.2 25.4 17.5 28.1 13.7
25.2 27.7 21.6 30.6 17.8 24.4 24.4 26.6 21.1 29.5 17.3 23.6 23.6 25.6 20.6 28.3 16.9
26.5 27.8 24.6 30.7 20.9 25.7 25.7 26.8 24.1 29.5 20.4 24.9 24.9 25.7 23.6 28.3 19.9
20.1 28.1 16.0 31.0 11.5 24.4 19.5 27.0 15.5 29.7 11.0 23.4 19.0 25.9 15.0 28.4 10.6
23.4 28.3 19.5 31.1 15.1 24.6 22.9 27.1 18.9 29.9 14.6 23.6 22.4 25.9 18.3 28.7 14.2
26.2 28.3 22.7 31.3 18.6 25.3 25.3 27.2 22.2 30.1 18.1 24.5 24.5 26.1 21.7 28.8 17.7
27.6 28.5 26.1 31.3 21.9 26.7 26.7 27.4 25.6 30.1 21.4 25.8 25.8 26.3 25.1 28.9 20.9
20.9 28.6 16.6 31.4 11.7 24.9 20.4 27.5 16.1 30.1 11.3 23.8 19.9 26.3 15.6 28.8 10.8
24.6 28.7 20.2 31.6 15.6 25.1 24.1 27.6 19.7 30.4 15.1 24.1 23.6 26.4 19.1 29.1 14.7
27.0 28.9 23.8 31.8 19.4 26.1 26.1 27.7 23.3 30.6 18.9 25.2 25.2 26.6 22.8 29.2 18.3
28.4 29.1 27.5 31.9 22.9 27.6 27.6 28.0 27.0 30.7 22.4 26.6 26.6 26.9 26.5 29.4 21.9
21.8 29.0 17.1 31.8 11.9 25.3 21.2 27.9 16.6 30.5 11.4 24.2 20.7 26.7 16.1 29.1 11.0
25.7 29.1 20.9 32.1 16.0 25.6 25.2 28.0 20.4 30.8 15.6 24.5 24.5 26.8 19.9 29.5 15.1
27.8 29.3 24.8 32.3 20.1 26.9 26.9 28.2 24.3 30.9 19.5 25.9 25.9 27.0 23.8 29.6 19.0
29.2 29.6 28.8 32.3 23.9 28.3 28.3 28.5 28.3 31.1 23.4 27.4 27.4 27.4 27.4 29.8 22.9
4248
4756
5267
5778
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
16
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-5 — Gross Cooling Capacities (MBh) TTA100A Condensing Unit withTWE100A Air Handler
(I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
102.0 77.6 112.8 67.2 124.5 46.0
102.4 89.6 113.2 75.1 124.6 59.2
98.2
98.7
75.7 108.7 65.5 119.9 44.4 94.3 73.6 104.4 63.8 115.1 42.7 90.2 71.5 99.9 62.0 110.1 41.0
87.6 109.2 73.2 120.1 57.4 94.8 85.5 104.9 71.4 115.4 55.6 90.8 83.4 100.5 69.4 110.5 53.7
3025
3350
3675
4000
103.6 101.9 113.4 87.0 125.0 71.7 100.2 100.1 109.3 85.1 120.5 69.9 96.5 96.5 105.1 83.1 115.9 68.1 93.1 93.1 100.7 81.0 111.1 66.3
107.8 107.8 113.8 98.9 125.4 84.1 104.7 104.7 109.8 97.0 120.9 82.4 101.5 101.5 105.6 95.0 116.3 80.6 98.1 98.1 101.3 93.0 111.3 78.2
104.1 80.8 115.1 64.6 126.7 46.8 100.3 78.8 110.8 62.8 121.9 45.2 96.2 76.7 106.3 60.9 116.9 43.5 92.0 74.5 101.7 58.9 111.7 41.7
104.6 93.8 115.5 78.2 126.9 60.9 100.8 91.8 111.3 76.3 122.2 59.1 96.9 89.7 106.5 74.0 117.4 57.3 92.8 87.6 102.0 71.9 112.4 55.4
106.1 106.1 115.7 90.9 127.3 74.5 102.9 102.9 111.5 89.0 122.7 72.7 99.6 99.6 107.1 86.9 117.9 70.9 96.1 96.1 102.6 84.8 113.0 69.0
111.5 111.5 116.2 103.9 127.7 88.0 108.3 108.3 112.1 102.0 122.8 85.8 104.9 104.9 107.8 100.0 118.1 83.8 101.3 101.3 103.4 98.0 113.2 81.8
106.0 83.8 116.9 66.6 128.5 47.7 102.0 81.8 112.5 64.7 123.5 46.0 97.8 79.7 107.9 62.8 118.4 44.3 93.5 77.5 103.2 60.8 113.0 42.4
106.6 97.8 117.4 81.1 128.8 62.6 102.7 95.8 112.7 78.8 124.0 60.8 98.7 93.8 108.2 76.7 119.0 58.9 94.5 91.6 103.6 74.6 113.9 57.0
109.1 109.1 117.6 94.7 129.3 77.2 105.8 105.8 113.3 92.7 124.5 75.4 102.4 102.4 108.8 90.6 119.6 73.5 98.7 98.7 104.2 88.5 114.5 71.6
114.7 114.7 118.3 108.7 129.4 91.1 111.3 111.3 114.1 106.8 124.7 89.2 107.8 107.8 109.8 104.8 119.9 87.2 104.0 104.0 105.4 102.7 114.8 85.2
107.6 86.7 118.5 68.4 130.0 48.6 103.5 84.6 114.0 66.5 124.9 46.7 99.3 82.5 109.3 64.5 119.6 44.8 94.8 80.2 104.5 62.6 114.2 42.9
108.4 101.7 118.7 83.4 130.4 64.1 104.5 99.7 114.3 81.4 125.5 62.3 100.4 97.6 109.7 79.3 120.4 60.5 96.2 95.5 104.9 77.1 115.2 58.6
111.8 111.8 119.3 98.2 130.9 79.7 108.4 108.4 114.9 96.2 126.1 77.9 104.8 104.8 110.3 94.1 121.1 76.1 101.1 101.1 105.6 92.0 115.5 73.6
117.6 117.6 120.2 113.3 131.2 94.5 114.1 114.1 116.0 111.4 126.4 92.5 110.4 110.4 111.6 109.4 121.4 90.5 106.5 106.5 106.6 106.6 116.3 88.4
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-5 — Gross Cooling Capacities (kW) TTA100A Condensing Unit withTWE100AAir Handler
(SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Bulb
Entering Wet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
29.9
30.0
30.3
31.6
30.5
30.6
31.1
32.6
31.0
31.2
31.9
33.6
31.5
31.7
32.7
34.4
22.7 33.0 19.7 36.4 13.5
26.2 33.2 22.0 36.5 17.3
29.8 33.2 25.5 36.6 21.0
31.6 33.3 29.0 36.7 24.6
23.7 33.7 18.9 37.1 13.7
27.5 33.8 22.9 37.2 17.8
31.1 33.9 26.6 37.3 21.8
32.6 34.0 30.4 37.4 25.8
24.5 34.2 19.5 37.6 14.0
28.6 34.4 23.7 37.7 18.3
31.9 34.4 27.7 37.9 22.6
33.6 34.6 31.8 37.9 26.7
25.4 34.7 20.0 38.1 14.2
29.8 34.8 24.4 38.2 18.8
32.7 34.9 28.8 38.3 23.3
34.4 35.2 33.2 38.4 27.7
28.8
28.9
29.3
30.7
29.4
29.5
30.1
31.7
29.9
30.1
31.0
32.6
30.3
30.6
31.7
33.4
22.2 31.8 19.2 35.1 13.0 27.6 21.6 30.6 18.7 33.7 12.5 26.4 20.9 29.2 18.1 32.2 12.0
25.6 32.0 21.4 35.2 16.8 27.8 25.0 30.7 20.9 33.8 16.3 26.6 24.4 29.4 20.3 32.4 15.7
29.3 32.0 24.9 35.3 20.5 28.2 28.2 30.8 24.3 33.9 19.9 27.3 27.3 29.5 23.7 32.5 19.4
30.7 32.1 28.4 35.4 24.1 29.7 29.7 30.9 27.8 34.1 23.6 28.7 28.7 29.7 27.2 32.6 22.9
23.1 32.4 18.4 35.7 13.2 28.2 22.5 31.1 17.8 34.2 12.7 26.9 21.8 29.8 17.3 32.7 12.2
26.9 32.6 22.3 35.8 17.3 28.4 26.3 31.2 21.7 34.4 16.8 27.2 25.7 29.9 21.1 32.9 16.2
30.1 32.7 26.0 35.9 21.3 29.2 29.2 31.4 25.5 34.5 20.8 28.1 28.1 30.0 24.8 33.1 20.2
31.7 32.8 29.9 36.0 25.1 30.7 30.7 31.6 29.3 34.6 24.5 29.7 29.7 30.3 28.7 33.1 23.9
24.0 32.9 18.9 36.2 13.5 28.6 23.3 31.6 18.4 34.7 13.0 27.4 22.7 30.2 17.8 33.1 12.4
28.1 33.0 23.1 36.3 17.8 28.9 27.5 31.7 22.5 34.9 17.3 27.7 26.8 30.3 21.8 33.4 16.7
31.0 33.2 27.1 36.5 22.1 30.0 30.0 31.9 26.5 35.0 21.5 28.9 28.9 30.5 25.9 33.5 21.0
32.6 33.4 31.3 36.5 26.1 31.6 31.6 32.1 30.7 35.1 25.5 30.5 30.5 30.9 30.1 33.6 24.9
24.8 33.4 19.5 36.6 13.7 29.1 24.2 32.0 18.9 35.0 13.1 27.8 23.5 30.6 18.3 33.4 12.5
29.2 33.5 23.8 36.8 18.3 29.4 28.6 32.1 23.2 35.3 17.7 28.2 28.0 30.7 22.6 33.7 17.1
31.7 33.6 28.2 36.9 22.8 30.7 30.7 32.3 27.6 35.4 22.3 29.6 29.6 30.9 26.9 33.8 21.5
33.4 34.0 32.6 37.0 27.1 32.3 32.3 32.7 32.0 35.5 26.5 31.2 31.2 31.2 31.2 34.0 25.9
5141
5692
6242
6797
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
SS-PRC003-EN
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-6 — Gross Cooling Capacities (MBh) TTA100B Condensing Unit withTWE100BAir Handler
(I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
Entering Wet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
94.9
95.1
97.0
74.4 105.3 63.8 116.4 42.9
86.5 105.5 71.4 116.4 55.6
97.0 105.6 83.4 116.6 67.8
90.0
90.4
93.0
97.9
91.7
92.4
96.0
72.0 100.1 61.7 110.7 40.9 84.9 69.5 94.6 59.5 104.8 38.8 79.6 67.0 88.9 57.3 98.6 36.6
84.2 100.3 69.0 110.7 53.4 85.5 81.9 94.8 66.6 104.8 51.1 80.5 79.5 89.0 64.2 98.6 48.7
93.0 100.3 81.1 110.9 65.6 88.8 88.8 94.8 78.7 104.9 63.3 84.5 84.5 89.1 76.2 98.7 60.9
97.9 100.8 93.1 111.1 77.7 93.6 93.6 95.5 90.8 105.1 75.4 89.1 89.1 90.1 88.5 98.8 73.0
75.2 101.9 58.7 112.5 41.7 86.5 72.7 96.3 56.3 106.4 39.4 81.0 70.2 90.4 53.8 100.1 37.1
88.6 102.1 72.1 112.6 55.0 87.5 86.3 96.4 69.6 106.5 52.7 82.2 82.2 90.5 67.1 100.1 50.3
96.0 102.2 85.0 112.8 68.3 91.7 91.7 96.5 82.6 106.6 65.9 87.1 87.1 90.6 80.1 100.2 63.5
3000
3325
3675
4000
102.0 102.0 105.9 95.4 116.8 80.0
96.7
97.3
77.6 107.3 61.1 118.3 43.7
90.9 107.5 74.4 118.4 57.3
100.1 100.1 107.6 87.4 118.6 70.6
105.4 105.4 108.2 100.4 118.8 83.8 101.1 101.1 103.0 98.2 112.9 81.4 96.6 96.6 97.6 95.9 106.7 78.9 91.9 91.9 91.9 91.91 100.3 76.4
98.5
99.3
81.0 109.0 70.3 120.0 44.8
95.4 109.3 77.5 120.2 59.0
93.3
94.4
98.8
78.5 103.5 68.1 114.0 42.5 87.9 76.0 97.7 65.8 107.8 40.2 82.4 73.5 91.7 63.1 101.3 38.4
93.1 103.7 75.1 114.2 56.7 89.1 89.1 97.8 72.6 107.9 54.4 84.5 84.5 91.8 70.0 101.4 52.0
98.8 103.9 89.0 114.4 71.1 94.3 94.3 98.1 86.6 108.1 68.7 89.5 89.5 92.2 84.2 101.6 66.3
103.1 103.1 109.5 91.4 120.4 73.4
108.5 108.5 110.4 105.6 120.6 87.3 104.1 104.1 105.1 103.4 114.5 85.0 99.4 99.4 99.3 99.3 108.2 82.6 94.5 94.5 94.4 94.4 101.7 80.1
99.9
101.1
83.9 110.5 64.9 121.4 45.2
99.4 110.6 80.1 121.6 60.5
94.6
95.7
81.4 104.8 62.5 115.3 42.9 89.1 78.9 98.9 60.0 109.0 40.5 83.5 76.4 92.8 57.5 102.4 38.2
95.7 104.9 77.7 115.5 58.2 91.2 91.2 99.0 75.2 109.1 55.9 86.4 86.4 92.8 72.7 102.5 53.5
105.6 105.6 110.9 95.0 121.9 75.9 101.2 101.2 105.3 92.6 115.7 73.5 96.5 96.5 99.4 90.2 109.3 71.1 91.5 91.5 93.4 87.8 102.6 68.7
111.2 111.2 112.3 110.3 122.1 90.6 106.6 106.6 106.5 106.5 115.9 88.2 101.7 101.7 101.6 101.6 109.4 85.8 96.6 96.6 96.6 96.6 102.7 83.4
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-6 — Gross Cooling Capacities (kW) TTA100B Condensing Unit withTWE100BAir Handler
(SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Bulb
EnteringWet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
27.8
27.9
28.4
29.9
28.4
28.5
29.4
30.9
28.9
29.1
30.2
31.8
29.3
29.6
31.0
32.6
21.8 30.9 18.7 34.1 12.6
25.4 30.9 20.9 34.1 16.3
28.4 31.0 24.5 34.2 19.9
29.9 31.1 28.0 34.2 23.4
22.8 31.5 17.9 34.7 12.8
26.6 31.5 21.8 34.7 16.8
29.4 31.5 25.6 34.8 20.7
30.9 31.7 29.4 34.8 24.5
23.7 32.0 20.6 35.2 13.1
28.0 32.0 22.7 35.2 17.3
30.2 32.1 26.8 35.3 21.5
31.8 32.4 31.0 35.3 25.6
24.6 32.4 19.0 35.6 13.2
29.1 32.4 23.5 35.6 17.7
31.0 32.5 27.8 35.7 22.2
32.6 32.9 32.3 35.8 26.5
26.4
26.5
27.3
28.7
26.9
27.1
28.1
29.6
27.4
27.7
29.0
30.5
27.7
28.1
29.7
31.2
21.1 29.3 18.1 32.4 12.0 24.9 20.4 27.7 17.4 30.7 11.4 23.3 19.6 26.1 16.8 28.9 10.7
24.7 29.4 20.2 32.5 15.6 25.1 24.0 27.8 19.5 30.7 15.0 23.6 23.3 26.1 18.8 28.9 14.3
27.3 29.4 23.8 32.5 19.2 26.0 26.0 27.8 23.1 30.8 18.5 24.8 24.8 26.1 22.3 28.9 17.8
28.7 29.5 27.3 32.6 22.8 27.4 27.4 28.0 26.6 30.8 22.1 26.1 26.1 26.4 25.9 29.0 21.4
22.0 29.9 17.2 33.0 12.2 25.4 21.3 28.2 16.5 31.2 11.6 23.7 20.6 26.5 15.8 29.3 10.9
26.0 29.9 21.1 33.0 16.1 25.6 25.3 28.3 20.4 31.2 15.5 24.1 24.1 26.5 19.7 29.3 14.8
28.1 30.0 24.9 33.0 20.0 26.9 26.9 28.3 24.2 31.2 19.3 25.5 25.5 26.6 23.5 29.4 18.6
29.6 30.2 28.8 33.1 23.9 28.3 28.3 28.6 28.1 31.3 23.1 26.9 26.9 26.9 26.9 29.4 22.4
23.0 30.3 20.0 33.4 12.5 25.8 22.3 28.6 19.3 31.6 11.8 24.1 21.5 26.9 18.5 29.7 11.3
27.3 30.4 22.0 33.5 16.6 26.1 26.1 28.7 21.3 31.6 15.9 24.8 24.8 26.9 20.5 29.7 15.2
29.0 30.4 26.1 33.5 20.8 27.6 27.6 28.8 25.4 31.7 20.1 26.2 26.2 27.0 24.7 29.8 19.4
30.5 30.8 30.3 33.6 24.9 29.1 29.1 29.1 29.1 31.7 24.2 27.7 27.7 27.7 27.7 29.8 23.5
23.9 30.7 18.3 33.8 12.6 26.1 23.1 29.0 17.6 31.9 11.9 24.5 22.4 27.2 16.9 30.0 11.2
28.1 30.8 22.8 33.8 17.1 26.7 26.7 29.0 22.0 32.0 16.4 25.3 25.3 27.2 21.3 30.0 15.7
29.7 30.9 27.1 33.9 21.6 28.3 28.3 29.1 26.4 32.0 20.9 26.8 26.8 27.4 25.7 30.1 20.1
31.2 31.2 31.2 34.0 25.9 29.8 29.8 29.8 29.8 32.1 25.2 28.3 28.3 28.3 28.3 30.1 24.4
5098
5648
6246
6797
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
18
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-7 — Gross Cooling Capacities (MBh) - Both Compressors -TTA100C Condensing Unit withTWE100AAir Handler (I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
99.7
78.1 110.4 66.8 121.8 45.0
95.7
96.3
98.8
76.1 106.1 65.1 117.1 43.3 91.5 74.0 101.4 63.3 112.1 41.6 87.0 71.7 96.5 61.4 106.8 39.8
88.9 106.4 73.5 117.2 56.8 92.2 86.8 101.8 71.5 112.3 54.9 87.9 84.7 97.0 69.4 107.0 52.9
98.8 106.6 86.1 117.5 70.0 95.3 95.3 102.0 84.1 112.6 68.1 91.6 91.6 97.2 81.9 107.4 66.1
100.2 90.9 110.7 75.3 121.9 58.6
102.1 102.1 110.9 88.1 122.2 71.8
3000
3325
3650
4000
107.3 107.3 111.4 100.9 122.4 85.0 104.0 104.0 107.2 99.0 117.7 83.2 100.4 100.4 102.8 97.0 112.7 81.0 96.6 96.6 98.2 94.9 107.5 79.0
101.7 81.6 112.5 64.3 123.9 45.8
102.4 95.6 112.8 78.7 124.0 60.4
97.6
98.4
79.5 108.1 62.4 119.0 44.1 93.2 77.3 103.3 60.4 113.8 42.3 88.6 75.1 98.2 58.3 108.4 40.3
93.6 108.4 76.8 119.1 58.6 94.2 91.5 103.4 74.4 114.0 56.7 89.9 89.3 98.5 72.3 108.6 54.7
105.4 105.4 113.0 92.4 124.3 74.8 102.0 102.0 108.6 90.4 119.4 73.0 98.4 98.4 103.9 88.3 114.3 71.1 94.5 94.5 98.9 86.1 109.0 69.1
110.9 110.9 113.7 106.4 124.5 89.1 107.4 107.4 109.5 104.5 119.5 86.9 103.7 103.7 105.0 102.5 114.5 84.9 99.7 99.7 99.8 99.8 109.2 82.9
103.6 85.1 114.2 73.6 125.6 46.8
99.3
83.0 109.6 71.2 120.6 45.0 94.8 80.8 104.8 69.3 115.3 43.1 90.0 78.5 99.6 67.3 109.7 41.6
104.5 100.4 114.5 81.8 125.8 62.3 100.5 98.4 109.9 79.8 120.8 60.4 95.7 95.7 105.1 77.6 115.6 58.5 91.8 91.8 100.0 75.4 110.1 56.5
108.6 108.6 114.8 96.8 126.1 77.9 105.0 105.0 110.3 94.8 121.1 76.0 101.2 101.2 105.6 92.7 115.9 74.1 97.2 97.2 100.6 90.5 110.4 72.1
114.2 114.2 116.0 112.2 126.3 93.0 110.5 110.5 111.7 110.2 121.3 91.0 106.7 106.7 106.8 106.8 116.1 89.0 102.6 102.6 102.7 102.7 110.7 86.9
105.0 88.3 115.7 68.4 127.1 47.3 100.6 86.2 111.1 66.5 121.9 45.4 96.0 83.9 106.1 64.5 116.5 43.4 91.3 81.6 100.8 62.4 110.8 41.5
106.3 104.8 115.9 84.6 127.3 64.0 101.8 101.8 111.3 82.6 122.1 62.1 97.9 97.9 106.4 80.5 116.8 60.2 93.8 93.8 101.2 78.2 111.2 58.2
111.2 111.2 116.3 100.7 127.6 80.6 107.5 107.5 111.8 98.7 122.5 78.8 103.6 103.6 107.0 96.6 117.2 76.8 99.4 99.4 101.9 94.4 111.4 74.4
116.9 116.9 117.9 117.3 127.8 96.6 113.2 113.2 113.3 113.3 122.7 94.7 109.2 109.2 109.2 109.2 117.4 92.6 104.9 104.9 105.0 105.0 111.9 90.5
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-7 — Gross Cooling Capacities (kW) - Both Compressors -TTA100C Condensing Unit withTWE100A Air Handler
(SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
19.4
Enter.
Dry
Bulb
Entering Wet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
22.8
Airflow
(°C)
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
29.2
29.3
29.9
31.4
29.8
30.0
30.9
32.5
30.3
30.6
31.8
33.4
30.7
31.1
32.6
34.2
22.9 32.3 19.6 35.7 13.2
26.6 32.4 22.1 35.7 17.1
29.9 32.5 25.8 35.8 21.0
31.4 32.6 29.6 35.8 24.9
23.9 32.9 18.8 36.3 13.4
28.0 33.0 23.0 36.3 17.7
30.9 33.1 27.0 36.4 21.9
32.5 33.3 31.2 36.5 26.1
24.9 33.4 21.6 36.8 13.7
29.4 33.5 23.9 36.8 18.2
31.8 33.6 28.3 36.9 22.8
33.4 34.0 32.8 37.0 27.2
25.8 33.9 20.0 37.2 13.8
30.7 33.9 24.8 37.3 18.7
32.6 34.1 29.5 37.4 23.6
34.2 34.5 34.3 37.4 28.3
28.0
28.2
28.9
30.5
28.6
28.8
29.9
31.4
29.1
29.4
30.7
32.4
29.5
29.8
31.5
33.1
22.3 31.1 19.1 34.3 12.7 26.8 21.7 29.7 18.5 32.8 12.2 25.5 21.0 28.3 18.0 31.3 11.6
26.0 31.2 21.5 34.3 16.6 27.0 25.4 29.8 20.9 32.9 16.1 25.7 24.8 28.4 20.3 31.3 15.5
28.9 31.2 25.2 34.4 20.5 27.9 27.9 29.9 24.6 33.0 19.9 26.8 26.8 28.5 24.0 31.4 19.4
30.5 31.4 29.0 34.5 24.4 29.4 29.4 30.1 28.4 33.0 23.7 28.3 28.3 28.8 27.8 31.5 23.1
23.3 31.6 18.3 34.8 12.9 27.3 22.6 30.2 17.7 33.3 12.4 25.9 22.0 28.8 17.1 31.7 11.8
27.4 31.7 22.5 34.9 17.2 27.6 26.8 30.3 21.8 33.4 16.6 26.3 26.2 28.8 21.2 31.8 16.0
29.9 31.8 26.5 35.0 21.4 28.8 28.8 30.4 25.9 33.5 20.8 27.7 27.7 29.0 25.2 31.9 20.2
31.4 32.1 30.6 35.0 25.5 30.4 30.4 30.8 30.0 33.5 24.9 29.2 29.2 29.2 29.2 32.0 24.3
24.3 32.1 20.8 35.3 13.2 27.8 23.7 30.7 20.3 33.7 12.6 26.4 23.0 29.2 19.7 32.1 12.2
28.8 32.2 23.4 35.4 17.7 28.0 28.0 30.8 22.7 33.8 17.1 26.9 26.9 29.3 22.1 32.2 16.6
30.7 32.3 27.7 35.5 22.3 29.6 29.6 30.9 27.1 33.9 21.7 28.4 28.4 29.4 26.5 32.3 21.1
32.4 32.7 32.3 35.5 26.7 31.2 31.2 31.3 31.3 34.0 26.1 30.0 30.0 30.1 30.1 32.4 25.4
25.2 32.5 19.5 35.7 13.3 28.1 24.6 31.1 18.9 34.1 12.7 26.7 23.9 29.5 18.3 32.4 12.1
29.8 32.6 24.2 35.8 18.2 28.7 28.7 31.1 23.6 34.2 17.6 27.5 27.5 29.6 22.9 32.6 17.0
31.5 32.7 28.9 35.9 23.1 30.3 30.3 31.3 28.3 34.3 22.5 29.1 29.1 29.8 27.6 32.6 21.8
33.1 33.2 33.2 35.9 27.7 32.0 32.0 32.0 32.0 34.4 27.1 30.7 30.7 30.7 30.7 32.8 26.5
5098
5648
6203
6797
Dry coil conditions. Total Gross Cooling Capacity (kW) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
SS-PRC003-EN
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-8 — Gross Cooling Capacities (MBh) - Single Compressor -TTA100C Condensing Unit withTWE100AAir Handler (I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
Entering Wet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
62.7
65.8
69.8
73.7
63.7
67.4
71.5
75.6
64.8
68.9
73.0
77.2
65.8
70.1
74.3
78.6
60.3 68.8 49.8 75.3 29.4
65.8 69.1 57.4 75.9 41.9
69.8 69.8 69.8 76.2 54.4
73.7 73.8 73.8 76.5 67.3
63.5 69.6 46.4 76.1 29.2
67.4 69.9 60.3 76.6 43.2
71.5 71.5 71.5 77.0 57.0
75.6 75.6 75.6 77.5 71.1
64.8 70.3 55.6 76.7 31.0
68.9 70.7 63.3 77.3 44.7
73.0 73.1 73.1 77.7 59.8
77.2 77.3 77.3 78.4 75.1
65.8 70.8 49.8 77.2 30.2
70.1 71.4 66.0 77.9 46.1
74.3 74.4 74.4 78.3 62.2
78.6 78.7 78.7 79.2 78.7
60.1
63.5
67.3
71.2
61.0
65.0
69.0
73.0
62.3
66.3
70.4
74.5
63.3
67.5
71.6
75.8
59.0 65.9 48.6 72.1 28.4 57.3 57.3 62.8 47.4 68.7 27.3 54.8 54.8 59.7 46.1 65.2 26.2
63.5 66.2 56.2 72.6 40.5 61.0 61.0 63.2 54.9 69.4 39.3 58.5 58.5 60.2 53.6 66.0 37.9
67.3 67.4 67.4 73.1 53.2 64.8 64.8 64.9 64.9 69.8 52.0 62.1 62.1 62.2 62.2 66.5 50.7
71.2 71.3 71.3 73.4 66.1 68.6 68.6 68.7 68.7 70.3 64.9 65.9 65.9 65.9 65.9 67.0 63.7
61.0 66.6 45.1 72.8 28.1 58.6 58.6 63.5 43.8 69.3 26.9 56.0 56.0 60.3 42.5 65.7 25.8
65.0 67.0 59.1 73.4 42.0 62.4 62.4 64.0 57.8 70.1 40.7 59.8 59.8 60.9 56.5 66.6 39.4
69.0 69.0 69.0 73.8 55.8 66.3 66.3 66.4 66.4 70.5 54.6 63.5 63.5 63.6 63.6 67.1 53.4
73.0 73.0 73.0 74.4 69.9 70.3 70.3 70.3 70.3 71.2 68.7 67.4 67.4 67.5 67.5 67.9 67.5
62.3 67.3 54.3 73.3 30.0 59.8 59.8 64.1 45.6 69.8 28.9 57.1 57.1 60.9 44.2 66.1 27.8
66.3 67.8 62.1 74.1 43.5 63.7 63.7 64.7 60.8 70.7 42.2 61.0 61.0 61.6 59.5 67.2 40.8
70.4 70.5 70.5 74.5 58.6 67.7 67.7 67.8 67.8 71.1 57.3 64.8 64.8 64.9 64.9 67.7 56.1
74.5 74.6 74.6 75.3 73.9 71.7 71.7 71.8 71.8 71.8 71.8 68.8 68.8 68.8 68.8 68.9 68.9
63.3 67.8 48.5 73.7 29.1 60.7 60.7 64.6 47.2 70.1 27.9 58.0 58.0 61.3 45.7 66.4 26.7
67.5 68.4 64.8 74.7 45.9 64.7 64.7 65.3 63.5 71.2 43.5 61.9 61.9 62.2 62.2 67.6 42.1
71.6 71.7 71.7 75.0 61.0 68.8 68.8 68.9 68.9 71.6 59.8 65.9 65.9 66.0 66.0 68.2 58.5
75.8 75.9 75.9 75.9 75.9 72.9 72.9 73.0 73.0 73.1 73.1 69.9 69.9 70.0 70.0 70.0 70.0
3000
3325
3650
4000
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-8 — Gross Cooling Capacities (kW) - Single Compressor -TTA100C Condensing Unit withTWE100AAir Handler
(SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
19.4
Enter.
Dry
Bulb
EnteringWet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
22.8
Airflow
(°C)
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
18.4
19.3
20.4
21.6
18.7
19.7
20.9
22.1
19.0
20.2
21.4
22.6
19.3
20.5
21.8
23.0
17.6 20.1 14.6 22.1 8.6
19.3 20.2 16.8 22.2 12.3
20.4 20.4 20.4 22.3 15.9
21.6 21.6 21.6 22.4 19.7
18.6 20.4 13.6 22.3 8.5
19.7 20.5 17.7 22.4 12.6
20.9 20.9 20.9 22.6 16.7
22.1 22.1 22.1 22.7 20.8
19.0 20.6 16.3 22.4 9.1
20.2 20.7 18.5 22.6 13.1
21.4 21.4 21.4 22.8 17.5
22.6 22.6 22.6 23.0 22.0
19.3 20.7 14.6 22.6 8.8
20.5 20.9 19.3 22.8 13.5
21.8 21.8 21.8 22.9 18.2
23.0 23.0 23.0 23.2 23.0
17.6
18.6
19.7
20.9
17.9
19.0
20.2
21.4
18.2
19.4
20.6
21.8
18.5
19.8
21.0
22.2
17.3 19.3 14.2 21.1 8.3 16.8 16.8 18.4 13.9 20.1 8.0 16.0 16.0 17.5 13.5 19.1 7.7
18.6 19.4 16.4 21.3 11.9 17.9 17.9 18.5 16.1 20.3 11.5 17.1 17.1 17.6 15.7 19.3 11.1
19.7 19.7 19.7 21.4 15.6 19.0 19.0 19.0 19.0 20.4 15.2 18.2 18.2 18.2 18.2 19.5 14.9
20.9 20.9 20.9 21.5 19.4 20.1 20.1 20.1 20.1 20.6 19.0 19.3 19.3 19.3 19.3 19.6 18.7
17.9 19.5 13.2 21.3 8.2 17.2 17.2 18.6 12.8 20.3 7.9 16.4 16.4 17.7 12.4 19.2 7.5
19.0 19.6 17.3 21.5 12.3 18.3 18.3 18.7 16.9 20.5 11.9 17.5 17.5 17.8 16.5 19.5 11.5
20.2 20.2 20.2 21.6 16.4 19.4 19.4 19.4 19.4 20.7 16.0 18.6 18.6 18.6 18.6 19.7 15.6
21.4 21.4 21.4 21.8 20.5 20.6 20.6 20.6 20.6 20.8 20.1 19.7 19.7 19.8 19.8 19.9 19.8
18.2 19.7 15.9 21.5 8.8 17.5 17.5 18.8 13.4 20.4 8.5 16.7 16.7 17.8 12.9 19.3 8.1
19.4 19.8 18.2 21.7 12.7 18.6 18.6 18.9 17.8 20.7 12.4 17.8 17.8 18.0 17.4 19.7 12.0
20.6 20.6 20.6 21.8 17.1 19.8 19.8 19.8 19.8 20.8 16.8 19.0 19.0 19.0 19.0 19.8 16.4
21.8 21.8 21.8 22.0 21.6 21.0 21.0 21.0 21.0 21.0 21.0 20.1 20.1 20.2 20.2 20.2 20.2
18.5 19.9 14.2 21.6 8.5 17.8 17.8 18.9 13.8 20.5 8.2 17.0 17.0 18.0 13.4 19.4 7.8
19.8 20.0 19.0 21.9 13.4 19.0 19.0 19.1 18.6 20.8 12.7 18.1 18.1 18.2 18.2 19.8 12.3
21.0 21.0 21.0 22.0 17.9 20.2 20.2 20.2 20.2 21.0 17.5 19.3 19.3 19.3 19.3 20.0 17.1
22.2 22.2 22.2 22.2 22.2 21.4 21.4 21.4 21.4 21.4 21.4 20.5 20.5 20.5 20.5 20.5 20.5
5098
5648
6203
6797
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
20
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-9 — Gross Cooling Capacities (MBh) TTA125B Condensing Unit withTWE100B Air Handler
(I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
108.2 79.4 117.8 61.3 124.3 42.2 100.3 76.1 109.3 58.1 115.4 39.2 92.3 72.8 100.8 54.9 106.5 36.1 84.4 69.5 92.3 51.7 97.6 33.0
108.2 93.1 117.8 75.0 124.3 55.9 100.3 89.8 109.3 71.8 115.4 52.8 92.3 86.5 100.8 68.5 106.5 49.7 84.4 82.7 92.3 65.3 97.6 46.7
108.2 105.3 117.8 88.6 124.3 69.5 100.3 99.4 109.3 85.4 115.4 66.5 93.1 93.1 100.8 82.2 106.5 63.5 86.9 86.9 92.3 79.0 97.6 60.3
110.2 110.2 117.8 102.2 124.3 83.2 103.9 103.9 109.3 99.0 115.4 80.2 97.4 97.4 100.8 96.0 106.5 77.0 90.8 90.8 92.7 92.7 97.6 74.0
110.0 83.1 119.6 64.1 126.3 44.1 101.8 79.6 111.0 60.7 117.2 41.0 93.8 76.1 102.4 57.4 108.2 37.7 85.8 72.6 93.7 54.1 99.2 34.5
110.0 97.4 119.6 78.4 126.3 58.5 101.8 93.9 111.0 75.1 117.2 55.2 93.8 90.4 102.4 71.7 108.2 52.0 86.5 86.5 93.7 68.3 99.2 48.9
110.1 110.1 119.6 92.7 126.3 72.7 104.0 104.0 111.0 89.3 117.2 69.6 97.4 97.4 102.4 85.9 108.2 66.4 90.9 90.9 93.7 82.7 99.2 63.1
115.3 115.3 119.6 106.9 126.3 87.0 108.7 108.7 111.0 103.6 117.2 83.9 101.9 101.9 102.4 100.4 108.2 80.6 95.0 95.0 96.9 96.9 99.2 77.4
111.8 87.0 121.7 67.1 128.4 46.2 103.6 83.3 112.9 63.6 119.2 43.0 95.4 79.7 104.1 60.2 110.1 39.5 87.2 76.1 95.3 56.6 100.8 36.1
111.8 102.0 121.7 82.1 128.4 61.3 103.6 98.3 112.9 78.6 119.2 57.9 95.4 94.7 104.1 75.1 110.1 54.5 90.6 90.6 95.3 71.6 100.8 51.2
115.4 115.4 121.7 97.1 128.4 76.2 108.9 108.9 112.9 93.5 119.2 72.9 102.0 102.0 104.1 90.0 110.1 69.5 95.2 95.2 95.3 86.6 100.8 66.1
120.8 120.8 121.7 112.0 128.4 91.1 111.6 111.6 112.9 108.5 119.2 87.8 103.2 103.2 105.1 105.1 110.1 84.4 99.0 99.0 99.2 99.2 100.8 81.0
113.5 90.7 123.5 69.9 130.4 48.2 105.2 86.8 114.6 66.3 121.0 44.8 96.9 83.1 105.7 62.7 111.8 41.2 88.6 79.3 96.8 59.0 102.4 37.7
113.5 106.2 123.5 85.6 130.4 63.8 105.2 102.5 114.6 81.9 121.0 60.3 98.7 98.7 105.7 78.2 111.8 56.8 94.4 94.4 96.8 74.6 102.4 53.4
120.2 120.2 123.5 101.2 130.4 79.4 113.5 113.5 114.6 97.5 121.0 75.9 104.8 104.8 105.7 93.8 111.8 72.4 96.1 96.1 96.8 90.2 102.4 68.9
123.1 123.1 123.5 116.7 130.4 94.9 113.5 113.5 114.6 113.0 121.0 91.5 107.6 107.6 109.5 109.5 111.8 87.9 99.8 99.8 101.5 101.5 102.4 84.4
3000
3325
3675
4000
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-9 — Gross Cooling Capacities (kW) TTA125B Condensing Unit withTWE100BAir Handler
(SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Bulb
Entering Wet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
31.7
31.7
31.7
32.3
32.2
32.2
32.3
33.8
32.8
32.8
33.8
35.4
33.3
33.3
35.2
36.1
23.3 34.5 18.0 36.4 12.4
27.3 34.5 22.0 36.4 16.4
30.9 34.5 26.0 36.4 20.4
32.3 34.5 29.9 36.4 24.4
24.3 35.0 18.8 37.0 12.9
28.5 35.0 23.0 37.0 17.1
32.3 35.0 27.2 37.0 21.3
33.8 35.0 31.3 37.0 25.5
25.5 35.7 19.7 37.6 13.5
29.9 35.7 24.1 37.6 18.0
33.8 35.7 28.5 37.6 22.3
35.4 35.7 32.8 37.6 26.7
26.6 36.2 20.5 38.2 14.1
31.1 36.2 25.1 38.2 18.7
35.2 36.2 29.7 38.2 23.3
36.1 36.2 34.2 38.2 27.8
29.4
29.4
29.4
30.4
29.8
29.8
30.5
31.8
30.4
30.4
31.9
32.7
30.8
30.8
33.3
33.3
22.3 32.0 17.0 33.8 11.5 27.0 21.3 29.5 16.1 31.2 10.6 24.7 20.4 27.0 15.1 28.6 9.7
26.3 32.0 21.0 33.8 15.5 27.0 25.3 29.5 20.1 31.2 14.6 24.7 24.2 27.0 19.1 28.6 13.7
29.1 32.0 25.0 33.8 19.5 27.3 27.3 29.5 24.1 31.2 18.6 25.5 25.5 27.0 23.1 28.6 17.7
30.4 32.0 29.0 33.8 23.5 28.5 28.5 29.5 28.1 31.2 22.6 26.6 26.6 27.2 27.2 28.6 21.7
23.3 32.5 17.8 34.3 12.0 27.5 22.3 30.0 16.8 31.7 11.0 25.1 21.3 27.5 15.9 29.1 10.1
27.5 32.5 22.0 34.3 16.2 27.5 26.5 30.0 21.0 31.7 15.2 25.3 25.3 27.5 20.0 29.1 14.3
30.5 32.5 26.2 34.3 20.4 28.5 28.5 30.0 25.2 31.7 19.5 26.6 26.6 27.5 24.2 29.1 18.5
31.8 32.5 30.4 34.3 24.6 29.9 29.9 30.0 29.4 31.7 23.6 27.8 27.8 28.4 28.4 29.1 22.7
24.4 33.1 18.6 34.9 12.6 28.0 23.4 30.5 17.6 32.3 11.6 25.5 22.3 27.9 16.6 29.5 10.6
28.8 33.1 23.0 34.9 17.0 28.0 27.7 30.5 22.0 32.3 16.0 26.5 26.5 27.9 21.0 29.5 15.0
31.9 33.1 27.4 34.9 21.4 29.9 29.9 30.5 26.4 32.3 20.4 27.9 27.9 27.9 25.4 29.5 19.4
32.7 33.1 31.8 34.9 25.7 30.2 30.2 30.8 30.81 32.3 24.7 29.0 29.0 29.1 29.1 29.5 23.7
25.4 33.6 19.4 35.5 13.1 28.4 24.3 31.0 18.4 32.8 12.1 26.0 23.2 28.4 17.3 30.0 11.0
30.0 33.6 24.0 35.5 17.7 28.9 28.9 31.0 22.9 32.8 16.6 27.7 27.7 28.4 21.9 30.0 15.6
33.3 33.6 28.6 35.5 22.2 30.7 30.7 31.0 27.5 32.8 21.2 28.2 28.2 28.4 26.4 30.0 20.2
33.3 33.6 33.1 35.5 26.8 31.5 31.5 32.1 32.1 32.8 25.8 29.2 29.2 29.7 29.7 30.0 24.7
5098
5648
6246
6797
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
SS-PRC003-EN
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-10 — Gross Cooling Capacities (MBh) TTA125B Condensing Unit withTWE155BAir Handler
(I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
Entering Wet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
120.8 96.6 132.7 73.8 141.1 49.7 113.8 93.7 124.9 70.8 132.7 46.7 106.3 90.5 116.6 67.6 123.9 43.6 98.8 87.4 108.3 64.6 115.0 40.6
120.8 114.3 132.7 91.4 141.1 67.4 113.8 111.4 124.9 88.5 132.7 64.5 108.3 108.3 116.6 85.4 123.9 61.3 104.9 104.9 108.3 82.2 115.0 58.3
126.8 126.8 132.7 109.2 141.1 85.1 119.6 119.6 124.9 106.2 132.7 82.1 112.4 112.4 116.6 103.0 123.9 79.1 105.0 105.0 108.3 100.0 115.0 76.0
127.4 127.4 132.7 126.9 141.1 102.8 123.1 123.1 124.9 123.9 132.7 100.0 118.9 118.9 119.7 119.7 123.9 96.7 110.0 110.0 111.2 111.2 115.0 93.6
122.7 101.2 134.9 77.3 143.4 52.0 115.6 98.1 127.0 74.1 134.9 49.0 108.0 94.8 118.5 70.8 125.9 45.7 100.4 91.5 110.1 67.6 116.9 42.5
122.7 119.7 134.9 95.7 143.4 70.6 116.6 116.6 127.0 92.7 134.9 67.5 113.4 113.4 118.5 89.4 125.9 64.2 109.9 109.9 110.1 86.1 116.9 61.1
132.8 132.8 134.9 114.3 143.4 89.1 125.3 125.3 127.0 111.2 134.9 86.0 117.7 117.7 118.5 107.9 125.9 82.9 110.0 110.0 110.1 104.7 116.9 79.5
133.4 133.4 134.9 132.8 143.4 107.7 128.9 128.9 129.8 129.8 134.9 104.7 124.5 124.5 125.3 125.3 125.9 101.3 115.2 115.2 116.4 116.4 116.9 98.0
124.7 105.7 137.1 80.8 145.6 54.3 117.5 102.5 129.0 77.4 137.1 51.2 109.7 99.1 120.4 74.0 127.9 47.7 102.0 95.7 111.8 70.7 118.7 44.4
125.1 125.1 137.1 100.1 145.6 73.8 121.9 121.9 129.0 96.8 137.1 70.5 118.5 118.5 120.4 93.4 127.9 67.1 111.1 111.1 111.8 90.0 118.7 63.8
136.9 136.9 137.1 119.5 145.6 93.1 128.7 128.7 129.0 116.2 137.1 89.9 119.9 119.9 120.4 112.7 127.9 86.6 111.5 111.5 111.8 109.4 118.7 83.1
137.9 137.9 138.8 138.8 145.6 112.5 134.7 134.7 135.6 135.6 137.1 109.5 127.4 127.4 127.8 127.8 127.9 105.8 117.0 117.0 117.7 117.7 118.7 102.5
126.7 110.3 139.2 84.2 147.9 56.7 119.3 106.9 131.0 80.8 139.2 53.4 111.4 103.3 122.3 77.2 129.9 49.8 103.6 99.8 113.6 73.7 120.6 46.3
130.5 130.5 139.2 104.4 147.9 76.9 127.1 127.1 131.0 101.0 139.2 73.6 121.9 121.9 122.3 97.4 129.9 70.0 112.7 112.7 113.6 93.8 120.6 66.6
138.6 138.6 139.2 124.6 147.9 97.1 130.3 130.3 131.0 121.2 139.2 93.7 122.2 122.2 122.3 117.6 129.9 90.3 113.9 113.9 114.1 114.1 120.6 86.7
144.1 144.1 144.8 144.8 147.9 117.4 138.6 138.6 138.7 138.7 139.2 114.2 128.8 128.8 129.4 129.4 129.9 110.4 119.6 119.6 120.2 120.2 120.6 106.9
3750
4200
4600
5000
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-10 — Gross Cooling Capacities (kW) TTA125B Condensing Unit withTWE155BAir Handler
(SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Bulb
EnteringWet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
35.4
35.4
37.2
37.3
36.0
36.0
38.9
39.1
36.5
36.7
40.1
40.4
37.1
38.2
40.6
42.2
28.3 38.9 21.6 41.3 14.6
33.5 38.9 26.8 41.3 19.7
37.2 38.9 32.0 41.3 24.9
37.3 38.9 37.2 41.3 30.1
29.7 39.5 22.6 42.0 15.2
35.1 39.5 28.0 42.0 20.7
38.9 39.5 33.5 42.0 26.1
39.1 39.5 38.9 42.0 31.6
31.0 40.2 23.7 42.7 15.9
36.7 40.2 29.3 42.7 21.6
40.1 40.2 35.0 42.7 27.3
40.4 40.7 40.7 42.7 33.0
32.3 40.8 24.7 43.3 16.6
38.2 40.8 30.6 43.3 22.5
40.6 40.8 36.5 43.3 28.5
42.2 42.4 42.4 43.3 34.4
33.3
33.3
35.0
36.1
33.9
34.2
36.7
37.8
34.4
35.7
37.7
39.5
35.0
37.2
38.2
40.6
27.5 36.6 20.7 38.9 13.7 31.1 26.5 34.2 19.8 36.3 12.8 28.9 25.6 31.7 18.9 33.7 11.9
32.6 36.6 25.9 38.9 18.9 31.7 31.7 34.2 25.0 36.3 18.0 30.7 30.7 31.7 24.1 33.7 17.1
35.0 36.6 31.1 38.9 24.1 32.9 32.9 34.2 30.2 36.3 23.2 30.8 30.8 31.7 29.3 33.7 22.3
36.1 36.6 36.3 38.9 29.3 34.8 34.8 35.1 35.1 36.3 28.3 32.2 32.2 32.6 32.6 33.7 27.4
28.7 37.2 21.7 39.5 14.4 31.6 27.8 34.7 20.7 36.9 13.4 29.4 26.8 32.3 19.8 34.3 12.5
34.2 37.2 27.2 39.5 19.8 33.2 33.2 34.7 26.2 36.9 18.8 32.2 32.2 32.3 25.2 34.3 17.9
36.7 37.2 32.6 39.5 25.2 34.5 34.5 34.7 31.6 36.9 24.3 32.2 32.2 32.3 30.7 34.3 23.3
37.8 38.0 38.0 39.5 30.7 36.5 36.5 36.7 36.7 36.9 29.7 33.8 33.8 34.1 34.1 34.3 28.7
30.0 37.8 22.7 40.2 15.0 32.1 29.0 35.3 21.7 37.5 14.0 29.9 28.0 32.8 20.7 34.8 13.0
35.7 37.8 28.4 40.2 20.7 34.7 34.7 35.3 27.4 37.5 19.7 32.6 32.6 32.8 26.4 34.8 18.7
37.7 37.8 34.0 40.2 26.3 35.1 35.1 35.3 33.0 37.5 25.4 32.7 32.7 32.8 32.1 34.8 24.3
39.5 39.7 39.7 40.2 32.1 37.3 37.3 37.4 37.4 37.5 31.0 34.3 34.3 34.5 34.5 34.8 30.0
31.3 38.4 23.7 40.8 15.6 32.6 30.3 35.8 22.6 38.1 14.6 30.4 29.2 33.3 21.6 35.3 13.6
37.2 38.4 29.6 40.8 21.6 35.7 35.7 35.8 28.5 38.1 20.5 33.0 33.0 33.3 27.5 35.3 19.5
38.2 38.4 35.5 40.8 27.5 35.8 35.8 35.8 34.5 38.1 26.5 33.4 33.4 33.4 33.4 35.3 25.4
40.6 40.6 40.6 40.8 33.5 37.7 37.7 37.9 37.9 38.1 32.3 35.0 35.0 35.2 35.21 35.3 31.3
6372
7135
7816
8496
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
22
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-11 — Gross Cooling Capacities (MBh) TTA155B Condensing Unit withTWE155BAir Handler
(I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
153.6 120.6 169.3 101.0 185.5 68.8 148.1 117.8 163.0 98.5 178.1 66.3 141.7 114.5 155.8 95.6 169.8 63.4 134.4 110.7 147.7 92.3 160.6 60.3
154.5 140.6 169.7 116.3 186.6 90.6 149.2 137.8 163.5 113.4 179.4 87.8 142.9 134.6 156.4 110.1 171.4 84.9 135.9 131.0 148.4 106.4 162.6 81.6
157.8 157.8 170.7 136.1 187.6 111.5 153.2 153.2 164.5 133.3 180.4 108.8 147.8 147.8 157.4 130.0 172.5 105.8 141.6 141.6 149.4 126.3 163.2 101.6
165.9 165.9 171.6 156.3 188.0 131.2 161.1 161.1 165.6 153.4 180.8 128.2 155.4 155.4 158.7 150.2 173.0 125.0 149.1 149.1 151.1 146.7 164.5 121.4
156.7 126.1 172.4 99.7 188.2 69.9 151.0 123.2 165.9 97.0 180.6 67.3 144.4 119.8 158.4 93.9 172.1 64.4 136.8 116.0 149.3 89.6 162.7 61.2
158.0 148.1 172.9 121.2 189.8 93.6 152.4 145.2 166.5 118.3 182.3 90.8 146.0 141.9 159.1 114.9 174.1 87.8 138.9 138.2 151.0 111.1 165.0 84.6
163.0 163.0 173.9 143.0 190.9 116.5 158.2 158.2 167.5 140.0 182.7 112.8 152.4 152.4 160.1 136.6 174.6 109.5 145.9 145.9 152.0 132.9 165.8 105.8
171.5 171.5 175.3 165.1 191.5 137.6 166.4 166.4 169.1 162.2 184.0 134.5 160.4 160.4 162.1 159.0 175.9 131.2 153.7 153.7 153.9 153.9 167.1 127.6
159.4 131.3 174.9 103.1 190.6 71.2 153.5 128.3 168.2 100.3 182.7 68.5 146.6 124.8 159.8 96.2 173.9 65.5 138.9 120.9 151.3 92.3 164.3 62.3
161.0 155.3 175.7 125.9 192.5 96.5 155.4 152.3 169.0 122.9 184.6 93.7 148.2 148.2 161.5 119.4 176.2 90.6 141.7 141.7 153.1 115.6 167.0 87.4
167.6 167.6 176.6 149.5 193.0 120.1 162.5 162.5 170.0 146.5 185.3 117.0 156.5 156.5 162.5 143.1 177.0 113.6 149.7 149.7 154.3 139.3 168.0 109.9
176.3 176.3 178.6 173.6 194.4 143.6 170.9 170.9 172.3 170.7 186.7 140.5 164.7 164.7 164.9 164.9 178.3 137.1 157.8 157.8 157.9 157.9 169.3 133.5
161.6 136.3 177.1 106.2 192.5 72.4 155.5 133.2 169.5 102.4 184.4 69.6 148.5 129.7 161.7 98.8 175.4 66.5 140.6 125.7 153.6 96.9 165.6 63.1
163.8 162.2 178.0 130.4 194.7 99.2 157.6 157.6 171.2 127.4 186.6 96.4 151.6 151.6 163.4 123.8 178.0 93.3 144.8 144.8 154.9 119.9 168.6 90.1
171.7 171.7 179.1 155.8 195.5 124.2 166.3 166.3 172.3 152.7 187.6 121.0 160.0 160.0 164.7 149.3 179.0 117.5 153.0 153.0 156.3 145.5 169.9 113.8
180.7 180.7 180.9 180.9 196.8 149.5 175.0 175.0 175.1 175.1 189.0 146.3 168.5 168.5 168.7 168.7 180.3 142.8 161.3 161.3 161.5 161.5 171.2 139.2
4500
5000
5500
6000
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-11 — Gross Cooling Capacities (kW) TTA155B Condensing Unit withTWE155B Air Handler
(SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Bulb
Entering Wet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
45.0
45.2
46.2
48.6
45.9
46.3
47.7
50.2
46.7
47.1
49.1
51.6
47.3
48.0
50.3
52.9
35.3 49.6 29.6 54.3 20.1
41.2 49.7 34.0 54.6 26.5
46.2 50.0 39.9 54.9 32.7
48.6 50.2 45.8 55.0 38.4
36.9 50.5 29.2 55.1 20.5
43.4 50.6 35.5 55.6 27.4
47.7 50.9 41.9 55.9 34.1
50.2 51.3 48.3 56.1 40.3
38.4 51.2 30.2 55.8 20.8
45.5 51.4 36.9 56.3 28.3
49.1 51.7 43.8 56.5 35.2
51.6 52.3 50.8 56.9 42.1
39.9 51.9 31.1 56.4 21.2
47.5 52.1 38.2 57.0 29.1
50.3 52.4 45.6 57.2 36.4
52.9 53.0 53.0 57.6 43.8
43.4
43.7
44.9
47.2
44.2
44.6
46.3
48.7
44.9
45.5
47.6
50.0
45.5
46.1
48.7
51.2
34.5 47.7 28.8 52.1 19.4 41.5 33.5 45.6 28.0 49.7 18.6 39.4 32.4 43.2 27.0 47.0 17.7
40.4 47.9 33.2 52.5 25.7 41.8 39.4 45.8 32.2 50.2 24.8 39.8 38.3 43.5 31.1 47.6 23.9
44.9 48.2 39.0 52.8 31.9 43.3 43.3 46.1 38.1 50.5 31.0 41.5 41.5 43.8 37.0 47.8 29.7
47.2 48.5 44.9 52.9 37.5 45.5 45.5 46.5 44.0 50.7 36.6 43.7 43.7 44.2 42.9 48.2 35.6
36.1 48.6 28.4 52.9 19.7 42.3 35.1 46.4 27.5 50.4 18.9 40.1 34.0 43.7 26.2 47.6 17.9
42.5 48.8 34.6 53.4 26.6 42.8 41.6 46.6 33.6 51.0 25.7 40.7 40.5 44.2 32.5 48.3 24.8
46.3 49.0 41.0 53.5 33.0 44.6 44.6 46.9 40.0 51.1 32.1 42.7 42.7 44.5 38.9 48.6 31.0
48.7 49.5 47.5 53.9 39.4 47.0 47.0 47.5 46.5 51.5 38.4 45.0 45.0 45.1 45.1 48.9 37.4
37.6 49.3 29.4 53.5 20.1 42.9 36.5 46.8 28.2 50.9 19.2 40.7 35.4 44.3 27.0 48.1 18.3
44.6 49.5 36.0 54.1 27.4 43.4 43.4 47.3 35.0 51.6 26.5 41.5 41.5 44.8 33.9 48.9 25.6
47.6 49.8 42.9 54.3 34.3 45.8 45.8 47.6 41.9 51.8 33.3 43.8 43.8 45.2 40.8 49.2 32.2
50.0 50.4 50.0 54.7 41.1 48.2 48.2 48.3 48.3 52.2 40.1 46.2 46.2 46.2 46.2 49.6 39.1
39.0 49.6 30.0 54.0 20.4 43.5 38.0 47.3 28.9 51.4 19.5 41.2 36.8 45.0 28.4 48.5 18.5
46.1 50.1 37.3 54.6 28.2 44.4 44.4 47.9 36.3 52.1 27.3 42.4 42.4 45.3 35.1 49.4 26.4
48.7 50.4 44.7 54.9 35.4 46.9 46.9 48.2 43.7 52.4 34.4 44.8 44.8 45.8 42.6 49.7 33.3
51.2 51.3 51.3 55.3 42.8 49.3 49.3 49.4 49.4 52.8 41.8 47.2 47.2 47.3 47.3 50.1 40.7
7646
8496
9346
10195
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
SS-PRC003-EN
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-12— Gross Cooling Capacities (MBh) TTA155B Condensing Unit withTWE200BAir Handler
(I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
Entering Wet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
158.1 125.3 174.1 103.2 189.9 70.5 152.4 122.3 167.6 100.6 182.4 67.9 145.7 118.9 160.0 97.5 173.8 64.9 138.1 115.0 151.6 94.1 164.3 61.7
159.2 146.5 174.5 120.6 191.6 93.5 153.6 143.6 168.1 117.6 184.2 90.7 147.0 140.2 160.7 114.1 175.9 87.7 139.7 136.5 152.4 110.3 166.9 84.4
163.2 163.2 175.5 141.6 192.7 115.6 158.3 158.3 169.0 138.6 185.2 112.8 152.6 152.6 161.6 135.2 176.4 108.9 146.2 146.2 153.4 131.4 167.5 105.2
171.5 171.5 176.6 162.9 193.1 136.3 166.4 166.4 170.3 160.0 185.7 133.2 160.5 160.5 163.2 156.7 177.6 129.9 153.9 153.9 155.3 153.1 168.8 126.2
161.4 131.2 177.3 103.3 192.7 71.7 155.4 128.2 170.5 100.5 184.9 69.0 148.4 124.6 162.7 97.3 176.0 66.0 140.5 120.7 153.1 92.5 166.2 62.7
162.8 154.7 177.8 125.9 194.8 96.8 157.0 151.7 171.1 122.9 187.1 94.0 150.3 148.2 163.5 119.3 178.6 90.9 142.7 142.7 155.0 115.4 169.3 87.6
168.7 168.7 178.8 149.0 196.1 121.1 163.6 163.6 172.1 146.0 187.6 117.0 157.5 157.5 164.5 142.5 179.2 113.5 150.7 150.7 156.1 138.7 170.2 109.8
177.4 177.4 180.4 172.6 196.7 143.2 172.0 172.0 174.0 169.6 188.8 140.0 165.8 165.8 166.8 166.3 180.5 136.6 158.8 158.8 159.0 159.0 171.5 133.0
164.1 136.9 179.9 107.0 195.0 72.9 157.9 133.8 172.0 103.1 186.9 70.2 150.7 130.2 164.0 99.4 177.8 67.1 142.7 126.1 155.2 95.3 167.7 63.8
166.0 162.5 180.6 131.1 197.5 99.9 160.1 159.5 173.7 127.9 189.5 97.1 153.2 153.2 165.8 124.3 180.7 94.0 146.4 146.4 157.1 120.4 171.2 90.7
173.5 173.5 181.6 156.2 198.2 124.8 168.1 168.1 174.8 153.1 190.2 121.5 161.7 161.7 167.0 149.6 181.7 118.0 154.7 154.7 158.5 145.8 172.4 114.2
182.5 182.5 184.0 182.0 199.6 149.9 176.8 176.8 177.0 177.0 191.5 146.6 170.3 170.3 170.4 170.4 182.9 143.2 163.0 163.0 163.2 163.2 173.7 139.5
166.3 142.4 181.3 109.2 196.8 74.1 160.0 139.2 174.1 106.0 188.5 71.3 152.7 135.5 165.9 102.2 179.1 68.2 144.5 131.4 156.9 98.0 168.8 64.8
168.5 168.5 183.0 136.0 199.7 103.0 163.1 163.1 175.9 132.8 191.4 100.0 156.7 156.7 167.8 129.1 182.5 97.0 149.6 149.6 159.0 125.1 172.8 93.6
177.7 177.7 184.2 163.2 200.7 129.2 172.0 172.0 177.2 160.1 192.4 125.9 165.4 165.4 169.3 156.5 183.7 122.3 158.1 158.1 160.7 152.6 174.3 118.4
187.1 187.1 187.3 187.3 202.1 156.4 181.0 181.0 181.2 181.2 193.9 153.1 174.2 174.2 174.4 174.4 185.0 149.5 166.8 166.8 167.0 167.0 175.6 145.8
4500
5000
5500
6000
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-12 — Gross Cooling Capacities (kW) TTA155B Condensing Unit withTWE200B Air Handler
(SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Bulb
EnteringWet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
46.3
46.6
47.8
50.2
47.2
47.7
49.4
51.9
48.0
48.6
50.8
53.4
48.7
49.3
52.0
54.8
36.7 51.0 30.2 55.6 20.7
42.9 51.1 35.3 56.1 27.4
47.8 51.4 41.5 56.4 33.9
50.2 51.7 47.7 56.5 39.9
38.4 51.9 30.3 56.4 21.0
45.3 52.1 36.9 57.0 28.3
49.4 52.4 43.6 57.4 35.4
51.9 52.8 50.5 57.6 41.9
40.1 52.7 31.3 57.1 21.3
47.6 52.9 38.4 57.8 29.3
50.8 53.2 45.7 58.0 36.5
53.4 53.9 53.3 58.4 43.9
41.7 53.1 32.0 57.6 21.7
49.3 53.6 39.8 58.5 30.1
52.0 53.9 47.8 58.8 37.8
54.8 54.8 54.8 59.2 45.8
44.6
45.0
46.4
48.7
45.5
46.0
47.9
50.4
46.2
46.9
49.2
51.8
46.8
47.7
50.4
53.0
35.8 49.1 29.4 53.4 19.9 42.7 34.8 46.9 28.5 50.9 19.0 40.4 33.7 44.4 27.6 48.1 18.1
42.0 49.2 34.4 53.9 26.6 43.1 41.1 47.0 33.4 51.5 25.7 40.9 40.0 44.6 32.3 48.9 24.7
46.4 49.5 40.6 54.2 33.0 44.7 44.7 47.3 39.6 51.6 31.9 42.8 42.8 44.9 38.5 49.0 30.8
48.7 49.9 46.8 54.4 39.0 47.0 47.0 47.8 45.9 52.0 38.0 45.1 45.1 45.5 44.8 49.4 37.0
37.5 49.9 29.4 54.1 20.2 43.4 36.5 47.6 28.5 51.5 19.3 41.1 35.3 44.8 27.1 48.7 18.4
44.4 50.1 36.0 54.8 27.5 44.0 43.4 47.9 34.9 52.3 26.6 41.8 41.8 45.4 33.8 49.6 25.7
47.9 50.4 42.7 54.9 34.2 46.1 46.1 48.2 41.7 52.5 33.2 44.1 44.1 45.7 40.6 49.8 32.1
50.4 50.9 49.7 55.3 41.0 48.5 48.5 48.8 48.7 52.9 40.0 46.5 46.5 46.6 46.6 50.2 38.9
39.2 50.4 30.2 54.7 20.5 44.1 38.1 48.0 29.1 52.0 19.6 41.8 36.9 45.4 27.9 49.1 18.7
46.7 50.9 37.5 55.5 28.4 44.9 44.9 48.6 36.4 52.9 27.5 42.9 42.9 46.0 35.2 50.1 26.5
49.2 51.2 44.8 55.7 35.6 47.4 47.4 48.9 43.8 53.2 34.6 45.3 45.3 46.4 42.7 50.5 33.4
51.8 51.8 51.8 56.1 42.9 49.9 49.9 49.9 49.9 53.6 41.9 47.7 47.7 47.8 47.8 50.9 40.8
40.8 51.0 31.0 55.2 20.9 44.7 39.7 48.6 29.9 52.4 20.0 42.3 38.5 45.9 28.7 49.4 19.0
47.7 51.5 38.9 56.1 29.3 45.9 45.9 49.1 37.8 53.4 28.4 43.8 43.8 46.5 36.6 50.6 27.4
50.4 51.9 46.9 56.3 36.9 48.4 48.4 49.6 45.8 53.8 35.8 46.3 46.3 47.0 44.7 51.0 34.7
53.0 53.1 53.1 56.8 44.8 51.0 51.0 51.1 51.1 54.2 43.8 48.8 48.8 48.9 48.9 51.4 42.7
7646
8496
9346
10195
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
24
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-13 — Gross Cooling Capacities (MBh) - Both Compressors -TTA155C Condensing UnitWithTWE155B Air Handler (I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
147.1 118.2 163.0 98.8 180.4 66.6 141.7 115.6 156.9 96.3 173.3 64.1 135.4 112.5 149.9 93.6 165.4 61.4 128.3 109.1 142.1 90.5 156.9 58.5
147.9 138.6 163.3 113.9 180.5 87.8 142.7 136.0 157.2 111.3 173.4 85.1 136.7 133.1 150.1 108.1 165.5 82.2 130.0 129.8 142.3 104.8 157.1 79.1
152.6 152.6 163.5 134.0 180.8 108.6 148.0 148.0 157.4 131.3 173.6 106.0 142.7 142.7 150.5 128.3 165.8 103.0 136.7 136.7 142.8 125.0 157.3 99.9
160.5 160.5 164.5 154.5 180.9 129.2 155.8 155.8 158.6 151.9 173.8 126.4 150.3 150.3 152.0 149.0 166.0 123.3 144.1 144.1 144.3 144.3 157.6 120.1
150.0 123.9 165.9 96.6 183.5 68.0 144.4 121.2 159.6 94.0 176.1 65.3 137.8 118.1 152.4 91.0 167.8 62.4 130.5 114.6 144.3 87.8 159.1 59.2
151.2 146.4 166.1 119.0 183.6 90.8 145.9 143.8 159.8 116.3 176.2 88.1 139.4 139.4 152.6 113.2 168.0 85.1 133.2 133.2 144.6 109.8 159.3 82.0
157.6 157.6 166.5 141.1 183.8 113.6 152.8 152.8 160.2 138.4 176.5 110.9 147.2 147.2 153.1 135.3 168.3 107.9 140.9 140.9 145.2 132.0 159.7 104.8
165.9 165.9 168.1 163.7 184.0 135.8 160.9 160.9 162.1 161.1 176.7 133.0 155.1 155.1 155.2 155.2 168.6 129.9 148.6 148.6 148.7 148.7 159.9 126.6
152.4 129.4 168.4 100.0 185.9 69.1 146.6 126.6 161.8 97.3 178.3 66.3 139.9 123.4 154.4 94.3 169.9 63.3 132.5 120.0 146.2 91.0 161.0 60.2
154.3 153.9 168.6 124.0 186.1 93.7 148.6 148.6 162.0 121.2 178.5 91.0 143.0 143.0 154.7 118.1 170.0 87.9 136.6 136.6 146.5 114.7 161.2 84.8
162.0 162.0 169.1 147.9 186.4 118.3 156.9 156.9 162.6 145.1 178.8 115.6 151.1 151.1 155.4 142.1 170.2 112.3 144.5 144.5 147.4 138.7 161.4 109.0
170.7 170.7 170.9 170.9 186.6 142.1 165.3 165.3 165.4 165.4 179.1 139.3 159.2 159.2 159.4 159.4 170.7 136.1 152.5 152.5 152.7 152.7 161.9 132.8
154.4 134.6 170.5 103.1 188.0 70.0 148.5 131.8 163.7 100.4 180.3 67.2 141.7 128.6 156.1 97.4 171.6 64.2 134.2 125.1 147.7 94.1 162.5 61.0
157.1 157.1 170.8 128.8 188.2 96.4 152.1 152.1 164.0 126.0 180.4 93.7 146.2 146.2 156.4 122.8 171.8 90.6 139.6 139.6 148.1 119.3 162.8 87.5
165.9 165.9 171.5 154.6 188.6 122.9 160.6 160.6 164.8 151.7 180.6 119.8 154.5 154.5 157.5 148.6 172.1 116.6 147.7 147.7 149.5 145.3 163.1 113.2
174.9 174.9 175.1 175.1 188.9 148.3 169.2 169.2 169.4 169.4 181.1 145.4 162.8 162.8 163.0 163.0 172.6 142.2 155.9 155.9 156.1 156.1 163.5 138.9
4500
5000
5500
6000
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-13 — Gross Cooling Capacities (kW) - Both Compressors -TTA155C Condensing UnitWithTWE155B Air Handler (SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Bulb
Entering Wet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
43.1
43.3
44.7
47.0
43.9
44.3
46.2
48.6
44.6
45.2
47.4
50.0
45.2
46.0
48.6
51.2
34.6 47.7 28.9 52.8 19.5
40.6 47.8 33.4 52.8 25.7
44.7 47.9 39.2 52.9 31.8
47.0 48.2 45.2 53.0 37.8
36.3 48.6 28.3 53.7 19.9
42.9 48.6 34.9 53.7 26.6
46.2 48.8 41.3 53.8 33.3
48.6 49.2 47.9 53.9 39.8
37.9 49.3 29.3 54.4 20.2
45.1 49.4 36.3 54.5 27.4
47.4 49.5 43.3 54.6 34.6
50.0 50.0 50.0 54.6 41.6
39.4 49.9 30.2 55.1 20.5
46.0 50.0 37.7 55.1 28.2
48.6 50.2 45.3 55.2 36.0
51.2 51.3 51.3 55.3 43.4
41.5
41.8
43.3
45.6
42.3
42.7
44.7
47.1
42.9
43.5
46.0
48.4
43.5
44.5
47.0
49.6
33.8 45.9 28.2 50.7 18.8 39.7 32.9 43.9 27.4 48.4 18.0 37.6 31.9 41.6 26.5 45.9 17.1
39.8 46.0 32.6 50.8 24.9 40.0 39.0 43.9 31.7 48.5 24.1 38.1 38.0 41.7 30.7 46.0 23.2
43.3 46.1 38.5 50.8 31.0 41.8 41.8 44.1 37.6 48.5 30.2 40.0 40.0 41.8 36.6 46.1 29.3
45.6 46.4 44.5 50.9 37.0 44.0 44.0 44.5 43.6 48.6 36.1 42.2 42.2 42.3 42.3 46.1 35.2
35.5 46.7 27.5 51.6 19.1 40.4 34.6 44.6 26.7 49.1 18.3 38.2 33.6 42.3 25.7 46.6 17.3
42.1 46.8 34.1 51.6 25.8 40.8 40.8 44.7 33.2 49.2 24.9 39.0 39.0 42.3 32.2 46.7 24.0
44.7 46.9 40.5 51.7 32.5 43.1 43.1 44.8 39.6 49.3 31.6 41.3 41.3 42.5 38.6 46.7 30.7
47.1 47.5 47.2 51.7 38.9 45.4 45.4 45.4 45.4 49.4 38.0 43.5 43.5 43.6 43.6 46.8 37.1
37.1 47.4 28.5 52.2 19.4 41.0 36.1 45.2 27.6 49.7 18.5 38.8 35.1 42.8 26.6 47.1 17.6
43.5 47.4 35.5 52.3 26.6 41.9 41.9 45.3 34.6 49.8 25.7 40.0 40.0 42.9 33.6 47.2 24.8
46.0 47.6 42.5 52.4 33.8 44.2 44.2 45.5 41.6 49.8 32.9 42.3 42.3 43.2 40.6 47.3 31.9
48.4 48.4 48.4 52.4 40.8 46.6 46.6 46.7 46.7 50.0 39.9 44.6 44.6 44.7 44.7 47.4 38.9
38.6 47.9 29.4 52.8 19.7 41.5 37.7 45.7 28.5 50.2 18.8 39.3 36.6 43.3 27.5 47.6 17.9
44.5 48.0 36.9 52.8 27.4 42.8 42.8 45.8 36.0 50.3 26.5 40.9 40.9 43.4 34.9 47.7 25.6
47.0 48.3 44.4 52.9 35.1 45.2 45.2 46.1 43.5 50.4 34.1 43.2 43.2 43.8 42.5 47.7 33.2
49.6 49.6 49.6 53.0 42.6 47.7 47.7 47.7 47.7 50.5 41.6 45.6 45.6 45.7 45.7 47.9 40.7
7646
8496
9346
10195
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
SS-PRC003-EN
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-14 — Gross Cooling Capacities (MBh) - Single Compressor -TTA155C Condensing Unit withTWE155B Air Handler (I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
Entering Wet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
90.4
96.3
90.4 99.1 67.0 109.4 42.8
96.3 99.6 87.3 109.8 62.7
87.8
93.4
99.2
87.8 95.6 65.6 105.2 41.5 84.6 84.6 91.5 64.0 100.7 40.0 80.9 80.9 87.0 62.2 95.7 38.3
93.4 96.1 85.9 105.5 61.1 90.1 90.1 92.1 84.3 101.1 59.5 86.2 86.2 87.6 82.5 96.1 57.7
99.2 99.3 99.3 106.0 81.3 95.7 95.7 95.8 95.8 101.5 79.7 91.7 91.7 91.8 91.8 96.5 77.9
4500
5000
5500
6000
102.2 102.2 102.3 102.3 109.9 82.7
108.3 108.3 108.4 108.4 110.7 103.2 105.1 105.1 105.2 105.2 106.9 101.8 101.4 101.4 101.5 101.5 102.6 100.3 97.3 97.3 97.4 97.4 97.5 97.5
92.5
98.6
92.5 100.2 70.1 110.4 42.7
98.6 100.8 92.2 110.6 65.1
89.7
95.6
89.7 96.6 68.6 106.2 41.3 86.4 86.4 92.4 67.0 101.5 39.8 82.6 82.6 87.8 65.1 96.5 38.1
95.6 97.3 90.8 106.6 63.6 92.1 92.1 93.3 89.2 102.0 62.0 88.1 88.1 88.8 87.4 97.0 60.3
104.7 104.7 104.8 104.8 111.1 87.2 101.6 101.6 101.7 101.7 107.0 85.7 97.9 97.9 98.0 98.0 102.5 84.1 93.8 93.8 93.9 93.9 97.5 82.4
111.0 111.0 111.1 111.1 112.2 109.7 107.6 107.6 107.7 107.7 108.4 108.3 103.8 103.8 103.9 103.9 104.0 104.0 99.6 99.6 99.7 99.7 99.8 99.8
94.4
94.4 101.1 72.9 111.3 43.5
91.5
97.5
91.5 97.5 71.5 107.0 42.1 88.0 88.0 93.2 69.8 102.3 40.6 84.1 84.1 88.5 68.0 97.1 38.9
97.5 98.4 95.6 107.4 66.1 93.8 93.8 94.4 94.0 102.8 64.5 89.7 89.7 89.8 89.8 97.8 62.7
100.6 100.6 102.0 97.0 111.5 67.6
106.9 106.9 107.0 107.0 112.0 91.5 103.6 103.6 103.7 103.7 107.9 90.1 99.8 99.8 99.9 99.9 103.3 88.5 95.6 95.6 95.6 95.6 98.3 86.7
113.2 113.2 113.4 113.4 113.4 113.4 109.8 109.8 109.9 109.9 110.0 110.0 105.9 105.9 106.0 106.0 106.0 106.0 101.5 101.5 101.6 101.6 101.7 101.7
96.0
96.0 101.9 75.7 112.0 44.3
92.9
99.1
92.9 98.2 74.3 107.6 42.9 89.4 89.4 93.9 72.6 102.9 41.3 85.4 85.4 89.1 70.7 97.6 39.7
99.1 99.1 99.1 108.2 68.5 95.3 95.3 95.4 95.4 103.5 66.8 91.1 91.1 91.2 91.2 98.4 65.1
102.3 102.3 103.0 101.7 112.4 70.7
108.7 108.7 108.8 108.8 112.8 95.7 105.3 105.3 105.4 105.4 108.7 94.3 101.4 101.4 101.5 101.5 104.1 92.6 97.1 97.1 97.2 97.2 99.1 90.9
115.1 115.1 115.2 115.2 115.3 115.3 111.7 111.7 111.8 111.8 111.9 111.9 107.6 107.6 107.7 107.7 107.8 107.8 103.2 103.2 103.3 103.3 103.4 103.4
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-14 — Gross Cooling Capacities (kW) - Single Compressor - TTA155C Condensing Unit withTWE155B Air Handler (SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Bulb
EnteringWet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
26.5
28.2
29.9
31.7
27.1
28.9
30.7
32.5
27.6
29.4
31.3
33.2
28.1
30.0
31.8
33.7
26.5 29.0 19.6 32.0 12.5
28.2 29.2 25.6 32.1 18.4
29.9 30.0 30.0 32.2 24.2
31.7 31.7 31.7 32.4 30.2
27.1 29.3 20.5 32.3 12.5
28.9 29.5 27.0 32.4 19.1
30.7 30.7 30.7 32.5 25.5
32.5 32.5 32.5 32.9 32.1
27.6 29.6 21.4 32.6 12.7
29.4 29.9 28.4 32.7 19.8
31.3 31.3 31.3 32.8 26.8
33.2 33.2 33.2 33.2 33.2
28.1 29.8 22.2 32.8 13.0
30.0 30.2 29.8 32.9 20.7
31.8 31.9 31.9 33.0 28.0
33.7 33.7 33.7 33.8 33.8
25.7
27.4
29.1
30.8
26.3
28.0
29.7
31.5
26.8
28.5
30.3
32.1
27.2
29.0
30.8
32.7
25.7 28.0 19.2 30.8 12.1 24.8 24.8 26.8 18.7 29.5 11.7 23.7 23.7 25.5 18.2 28.0 11.2
27.4 28.1 25.2 30.9 17.9 26.4 26.4 27.0 24.7 29.6 17.4 25.2 25.2 25.7 24.2 28.2 16.9
29.1 29.1 29.1 31.0 23.8 28.0 28.0 28.0 28.0 29.7 23.3 26.9 26.9 26.9 26.9 28.3 22.8
30.8 30.8 30.8 31.3 29.8 29.7 29.7 29.7 29.7 30.0 29.4 28.5 28.5 28.5 28.5 28.6 28.6
26.3 28.3 20.1 31.1 12.1 25.3 25.3 27.1 19.6 29.7 11.6 24.2 24.2 25.7 19.1 28.2 11.2
28.0 28.5 26.6 31.2 18.6 27.0 27.0 27.3 26.1 29.9 18.2 25.8 25.8 26.0 25.6 28.4 17.6
29.7 29.8 29.8 31.3 25.1 28.7 28.7 28.7 28.7 30.0 24.6 27.5 27.5 27.5 27.5 28.5 24.1
31.5 31.5 31.5 31.7 31.7 30.4 30.4 30.4 30.4 30.5 30.5 29.2 29.2 29.2 29.2 29.2 29.2
26.8 28.5 20.9 31.3 12.3 25.8 25.8 27.3 20.4 29.9 11.9 24.6 24.6 25.9 19.9 28.4 11.4
28.5 28.8 28.0 31.5 19.4 27.5 27.5 27.6 27.5 30.1 18.9 26.3 26.3 26.3 26.3 28.6 18.4
30.3 30.4 30.4 31.6 26.4 29.2 29.2 29.2 29.2 30.3 25.9 28.0 28.0 28.0 28.0 28.8 25.4
32.1 32.2 32.2 32.2 32.2 31.0 31.0 31.0 31.0 31.0 31.0 29.7 29.7 29.8 29.8 29.8 29.8
27.2 28.7 21.7 31.5 12.5 26.2 26.2 27.5 21.3 30.1 12.1 25.0 25.0 26.1 20.7 28.6 11.6
29.0 29.0 29.0 31.7 20.1 27.9 27.9 27.9 27.9 30.3 19.6 26.7 26.7 26.7 26.7 28.8 19.0
30.8 30.9 30.9 31.8 27.6 29.7 29.7 29.7 29.7 30.5 27.1 28.4 28.4 28.5 28.5 29.0 26.6
32.7 32.7 32.7 32.8 32.8 31.5 31.5 31.5 31.5 31.6 31.6 30.2 30.2 30.2 30.2 30.3 30.3
7646
8496
9346
10195
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
26
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
System
Table PD-15 — Gross Cooling Capacities (MBh) TTA200B Condensing Unit withTWE200B Air Handler
(I-P)
AmbientTemperature (°F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (°F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
201.0 158.5 221.1 132.8 242.4 89.9 193.1 154.4 212.5 129.3 232.6 86.5 184.9 150.2 203.5 125.7 222.1 83.0 176.4 145.8 194.2 122.0 211.7 79.5
202.2 184.9 221.6 152.5 243.5 118.4 194.5 180.9 213.1 148.6 234.1 114.8 186.6 176.8 204.3 144.5 224.2 111.1 178.4 172.6 195.1 140.3 214.1 107.4
206.7 206.7 222.8 178.8 244.6 146.0 200.1 200.1 214.3 174.8 235.3 142.4 193.3 193.3 205.5 170.7 225.5 138.8 186.1 186.1 196.4 166.6 215.5 135.1
217.1 217.1 224.1 205.3 245.0 172.1 210.4 210.4 215.9 201.5 235.7 168.2 203.4 203.4 207.3 197.5 226.1 164.2 196.1 196.1 198.7 193.5 216.2 160.2
204.9 165.7 225.2 130.5 246.0 91.4 196.8 161.6 216.3 126.8 235.8 87.9 188.4 157.3 207.0 123.0 225.4 84.3 179.6 152.9 197.4 119.1 214.5 80.7
206.6 194.8 225.8 159.1 247.6 122.3 198.8 190.8 217.0 155.1 237.8 118.8 190.7 186.6 207.9 150.9 227.7 115.1 182.5 182.4 198.5 146.6 217.2 111.3
213.4 213.4 227.0 187.8 248.8 152.5 206.6 206.6 218.2 183.8 239.1 148.9 199.4 199.4 209.1 179.7 228.3 143.9 191.9 191.9 199.8 175.5 218.1 139.7
224.4 224.4 228.9 217.1 249.3 180.5 217.3 217.3 220.5 213.2 239.7 176.6 210.0 210.0 211.9 209.2 229.8 172.5 202.3 202.3 202.5 202.5 219.6 168.4
208.3 172.6 228.5 134.9 248.9 93.0 200.0 168.4 219.3 131.2 238.5 89.5 191.3 164.0 209.8 127.3 227.8 85.8 182.3 159.5 199.1 121.9 216.7 82.0
210.6 204.3 229.3 165.4 250.9 126.1 202.7 200.3 220.3 161.3 240.9 122.5 193.9 193.9 210.9 157.0 230.5 118.8 186.3 186.3 201.3 152.7 219.8 115.0
219.4 219.4 230.5 196.5 251.4 157.5 212.2 212.2 221.6 192.5 241.6 153.5 204.7 204.7 212.3 188.3 231.4 149.4 197.0 197.0 202.9 184.0 220.9 145.1
230.7 230.7 233.3 228.5 252.9 188.5 223.3 223.3 224.9 224.6 243.1 184.5 215.7 215.7 215.9 215.9 232.9 180.4 207.7 207.7 207.9 207.9 222.4 176.2
211.2 179.2 231.3 139.1 251.4 94.4 202.6 174.9 221.0 134.2 240.8 90.7 193.8 170.5 211.3 129.8 229.8 86.9 184.7 166.0 201.4 125.3 218.4 83.1
214.3 213.5 232.3 171.4 253.7 129.7 205.8 205.8 223.1 167.2 243.4 126.1 198.3 198.3 213.5 162.9 232.8 122.4 190.4 190.4 203.7 158.5 221.9 118.6
224.6 224.6 233.7 204.9 254.5 162.9 217.2 217.2 224.6 200.8 244.4 158.8 209.4 209.4 215.2 196.6 234.0 154.6 201.4 201.4 205.6 192.3 223.3 150.3
236.3 236.3 236.5 236.5 256.0 196.3 228.6 228.6 228.8 228.8 245.9 192.2 220.7 220.7 220.9 220.9 235.5 188.1 212.4 212.4 212.6 212.6 224.8 183.8
6000
6675
7350
8025
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-15 — Gross Cooling Capacities (MBh) TTA200B Condensing Unit withTWE200B Air Handler
(SI)
AmbientTemperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Bulb
Entering Wet Bulb (°C)
22.8 16.1
m3/h
16.1
19.4
22.8
16.1
19.4
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
58.8
59.2
60.5
63.6
60.0
60.5
62.5
65.7
61.0
61.7
64.2
67.5
61.8
62.7
65.8
69.2
46.4 64.7 38.9 71.0 26.3
54.1 64.9 44.7 71.3 34.7
60.5 65.2 52.3 71.6 42.7
63.6 65.6 60.1 71.7 50.4
48.5 65.9 38.2 72.0 26.8
57.0 66.1 46.6 72.5 35.8
62.5 66.5 55.0 72.8 44.6
65.7 67.0 63.6 73.0 52.8
50.5 66.9 39.5 72.9 27.2
59.8 67.1 48.4 73.5 36.9
64.2 67.5 57.5 73.6 46.1
67.5 68.3 66.9 74.1 55.2
52.5 67.7 40.7 73.6 27.6
62.5 68.0 50.2 74.3 38.0
65.8 68.4 60.0 74.5 47.7
69.2 69.2 69.2 74.9 57.5
56.5
57.0
58.6
61.6
57.6
58.2
60.5
63.6
58.5
59.3
62.1
65.4
59.3
60.3
63.6
66.9
45.2 62.2 37.9 68.1 25.3 54.1 44.0 59.6 36.8 65.0 24.3 51.6 42.7 56.9 35.7 62.0 23.3
53.0 62.4 43.5 68.5 33.6 54.6 51.8 59.8 42.3 65.7 32.5 52.2 50.5 57.1 41.1 62.7 31.5
58.6 62.7 51.2 68.9 41.7 56.6 56.6 60.2 50.0 66.0 40.6 54.5 54.5 57.5 48.8 63.1 39.6
61.6 63.2 59.0 69.0 49.3 59.6 59.6 60.7 57.8 66.2 48.1 57.4 57.4 58.2 56.7 63.3 46.9
47.3 63.3 37.1 69.0 25.7 55.2 46.1 60.6 36.0 66.0 24.7 52.6 44.8 57.8 34.9 62.8 23.6
55.9 63.5 45.4 69.6 34.8 55.8 54.6 60.9 44.2 66.7 33.7 53.4 53.4 58.1 42.9 63.6 32.6
60.5 63.9 53.8 70.0 43.6 58.4 58.4 61.2 52.6 66.8 42.1 56.2 56.2 58.5 51.4 63.9 40.9
63.6 64.6 62.4 70.2 51.7 61.5 61.5 62.0 61.3 67.3 50.5 59.2 59.2 59.3 59.3 64.3 49.3
49.3 64.2 38.4 69.8 26.2 56.0 48.0 61.4 37.3 66.7 25.1 53.4 46.7 58.3 35.7 63.4 24.0
58.6 64.5 47.2 70.5 35.9 56.8 56.8 61.8 46.0 67.5 34.8 54.5 54.5 58.9 44.7 64.4 33.7
62.1 64.9 56.4 70.7 44.9 59.9 59.9 62.2 55.1 67.8 43.7 57.7 57.7 59.4 53.9 64.7 42.5
65.4 65.8 65.8 71.2 54.0 63.1 63.1 63.2 63.2 68.2 52.8 60.8 60.8 60.9 60.9 65.1 51.6
51.2 64.7 39.3 70.5 26.6 56.7 49.9 61.9 38.0 67.3 25.5 54.1 48.6 59.0 36.7 63.9 24.3
60.3 65.3 49.0 71.3 36.9 58.1 58.1 62.5 47.7 68.2 35.8 55.8 55.8 59.6 46.4 65.0 34.7
63.6 65.8 58.8 71.6 46.5 61.3 61.3 63.0 57.6 68.5 45.3 59.0 59.0 60.2 56.3 65.4 44.0
66.9 67.0 67.0 72.0 56.3 64.6 64.6 64.7 64.7 69.0 55.1 62.2 62.2 62.2 62.2 65.8 53.8
10195
11340
12488
13633
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
SS-PRC003-EN
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Condensing Unit
Table PD-16 — Cooling Performance (MBh) TTA075A Condensing Unit Only
(I-P)
ODTemp
°F
Suction ReferenceTemperature °F
30
35
40
45
50
55
Head press psig
Cap. Btu/1000
OD Unit kW
175
69.1
5.01
181
76.2
5.13
188
83.6
5.27
195
91.2
5.40
202
99.0
5.55
210
106.9
5.70
65
75
Head press psig
Cap. Btu/1000
OD Unit KW
202
66.9
5.54
209
73.7
5.68
216
80.7
5.82
223
87.9
5.97
231
95.3
6.12
239
102.8
6.28
Head press psig
Cap. Btu/1000
OD Unit KW
232
64.1
6.16
239
70.6
6.31
247
77.3
6.46
254
84.1
6.61
262
91.1
6.77
270
98.2
6.94
85
Head press psig
Cap. Btuh/1000
OD Unit KW
264
60.8
6.86
272
66.9
7.02
280
73.2
7.17
288
79.7
7.33
296
86.3
7.49
304
93.1
7.66
95
Head press psig
Cap. Btuh/1000
OD Unit KW
299
57.0
7.65
307
62.7
7.80
315
68.7
7.95
323
74.8
8.11
332
81.1
8.27
341
87.6
8.45
105
115
Head press psig
Cap. Btuh/1000
OD Unit KW
335
52.8
8.51
344
58.2
8.65
352
63.7
8.80
361
69.5
8.95
370
75.5
9.12
380
81.8
9.29
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.
Table PD-16 — Cooling Performance (kW) TTA075A Condensing Unit Only
(SI)
ODTemp
°C
Suction ReferenceTemperature °C
-1.1
1.7
4.4
7.2
10.0
12.8
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1208
20.2
5.01
1251
22.3
5.13
1297
24.5
5.27
1345
26.7
5.40
1395
29.0
5.55
1446
31.3
5.70
18.3
23.9
29.4
35.0
40.6
46.1
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1396
19.6
5.54
1442
21.6
5.68
1491
23.6
5.82
1541
25.7
5.97
1593
27.9
6.12
1647
30.1
6.28
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1600
18.8
6.16
1650
20.7
6.31
1701
22.6
6.46
1754
24.6
6.61
1808
26.7
6.77
1865
28.7
6.94
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1822
17.8
6.86
1874
19.6
7.02
1927
21.4
7.17
1983
23.3
7.33
2040
25.3
7.49
2099
27.3
7.66
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
2059
16.7
7.65
2114
18.4
7.80
2170
20.1
7.95
2227
21.9
8.11
2287
23.7
8.27
2350
25.7
8.45
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
2313
15.5
8.51
2369
17.0
8.65
2428
18.7
8.80
2488
20.4
8.95
2551
22.1
9.12
2617
24.0
9.29
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.
28
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Condensing Unit
Table PD-17 — Cooling Performance (MBh) TTA085A Condensing Unit Only
(I-P)
ODTemp
°F
Suction ReferenceTemperature °F
30
35
40
45
50
55
Head press PSIG
Cap. Btuh/1000
OD Unit KW
160
79.8
5.64
164
88.0
5.73
169
96.6
5.83
173
105.7
5.93
178
115.1
6.04
184
124.9
6.15
65
75
Head press PSIG
Cap. Btuh/1000
OD Unit KW
185
76.4
6.14
189
84.1
6.23
194
92.3
6.33
199
100.8
6.44
204
109.8
6.56
209
119.2
6.68
Head press PSIG
Cap. Btuh/1000
OD Unit KW
212
72.6
6.73
217
80.0
6.83
222
87.7
6.94
227
96.0
7.06
232
104.6
7.18
238
113.6
7.31
85
Head press PSIG
Cap. Btuh/1000
OD Unit KW
242
68.6
7.43
247
75.7
7.55
252
83.1
7.67
258
91.0
7.79
264
99.3
7.92
270
107.9
8.05
95
Head press PSIG
Cap. Btuh/1000
OD Unit KW
275
64.4
8.24
280
71.2
8.36
286
78.4
8.49
292
86.0
8.62
298
94.0
8.76
304
102.3
8.89
105
115
Head press PSIG
Cap. Btuh/1000
OD Unit KW
311
60.0
9.15
317
66.6
9.28
323
73.6
9.42
329
80.9
9.56
335
88.6
9.70
342
96.5
9.83
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.
Table PD-17 — Cooling Performance (kW) TTA085A Condensing Unit Only
(SI)
ODTemp
°C
Suction ReferenceTemperature °C
-1.1
1.7
4.4
7.2
10.0
12.8
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1102
23.4
5.64
1132
25.8
5.73
1163
28.3
5.83
1196
30.9
5.93
1230
33.7
6.04
1266
36.6
6.15
18.3
23.9
29.4
35.0
40.6
46.1
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1273
22.4
6.14
1304
24.6
6.23
1337
27.0
6.33
1371
29.5
6.44
1407
32.2
6.56
1444
34.9
6.68
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1462
21.3
6.73
1494
23.4
6.83
1529
25.7
6.94
1565
28.1
7.06
1603
30.6
7.18
1642
33.3
7.31
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1669
20.1
7.43
1704
22.2
7.55
1741
24.3
7.67
1779
26.6
7.79
1819
29.1
7.92
1860
31.6
8.05
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1896
18.9
8.24
1934
20.9
8.36
1973
23.0
8.49
2013
25.2
8.62
2055
27.5
8.76
2099
29.9
8.89
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
2142
17.6
9.15
2184
19.5
9.28
2225
21.6
9.42
2269
23.7
9.56
2313
25.9
9.70
2358
28.3
9.83
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.
SS-PRC003-EN
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Condensing Unit
Table PD-18 — Cooling Performance (MBh) TTA100A Condensing Unit Only
(I-P)
ODTemp
°F
Suction ReferenceTemperature °F
30
35
40
45
50
55
Head press PSIG
Cap. Btuh/1000
OD Unit KW
174
95.7
6.69
180
105.0
6.84
186
114.7
7.01
193
124.8
7.19
199
135.3
7.37
207
146.1
7.58
65
Head press PSIG
Cap. Btuh/1000
OD Unit KW
200
91.2
7.38
206
99.9
7.54
212
109.1
7.72
219
118.7
7.91
226
128.8
8.12
234
139.2
8.34
75
Head press PSIG
Cap. Btuh/1000
OD Unit KW
228
86.4
8.19
234
94.7
8.37
241
103.5
8.57
248
112.7
8.77
256
122.3
8.99
264
132.2
9.22
85
Head press PSIG
Cap. Btuh/1000
OD Unit KW
259
81.3
9.13
265
89.3
9.33
273
97.8
9.54
280
106.6
9.76
288
115.8
9.99
297
125.2
10.23
95
Head press PSIG
Cap. Btuh/1000
OD Unit KW
292
76.1
10.19
299
83.8
10.41
307
91.9
10.64
315
100.4
10.88
324
109.2
11.12
332
118.3
11.36
105
115
Head press PSIG
Cap. Btuh/1000
OD Unit KW
328
70.7
11.37
336
78.2
11.61
344
86.0
11.86
353
94.2
12.11
362
102.6
12.36
371
111.3
12.60
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.
Table PD-18 — Cooling Performance (kW) TTA100A Condensing Unit Only
(SI)
ODTemp
°C
Suction ReferenceTemperature °C
-1.1
1.7
4.4
7.2
10.0
12.8
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1200
28.0
6.69
1240
30.7
6.84
1283
33.6
7.01
1327
36.5
7.19
1375
39.6
7.37
1425
42.8
7.58
18.3
23.9
29.4
35.0
40.6
46.1
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1377
26.7
7.38
1418
29.3
7.54
1462
32.0
7.72
1509
34.8
7.91
1559
37.7
8.12
1612
40.7
8.34
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1571
25.3
8.19
1615
27.7
8.37
1662
30.3
8.57
1711
33.0
8.77
1763
35.8
8.99
1819
38.7
9.22
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1783
23.8
9.13
1830
26.2
9.33
1880
28.6
9.54
1932
31.2
9.76
1987
33.9
9.99
2045
36.7
10.23
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
2014
22.3
10.19
2064
24.5
10.41
2117
26.9
10.64
2173
29.4
10.88
2231
32.0
11.12
2292
34.6
11.36
Head pressure (kPA)
Capacity (kW)
2263
20.7
2318
22.9
2375
25.2
2434
27.6
2495
30.1
2559
32.6
OD Unit Power (kW)
11.37
11.61
11.86
12.11
12.36
12.60
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.
30
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Condensing Unit
Table PD-19 — Cooling Performance (MBh) TTA100B Condensing Unit Only
(I-P)
ODTemp
°F
Suction ReferenceTemperature °F
30
35
40
45
50
55
Head press PSIG
Cap. Btuh/1000
OD Unit KW
172
93.8
7.46
178
103.2
7.69
184
113.0
7.90
191
123.2
8.11
198
133.8
8.32
205
144.7
8.52
65
75
Head press PSIG
Cap. Btuh/1000
OD Unit KW
197
88.4
8.00
203
97.4
8.27
210
106.7
8.54
217
116.4
8.79
224
126.5
9.05
232
136.9
9.31
Head press PSIG
Cap. Btuh/1000
OD Unit KW
224
82.8
8.50
231
91.3
8.82
238
100.2
9.13
246
109.4
9.44
253
118.9
9.75
261
128.8
10.07
85
Head press PSIG
Cap. Btuh/1000
OD Unit KW
254
77.0
8.94
261
85.0
9.31
268
93.4
9.68
276
102.1
10.05
284
111.1
10.43
293
120.4
10.81
95
Head press PSIG
Cap. Btuh/1000
OD Unit KW
285
71.0
9.32
293
78.5
9.76
301
86.4
10.19
309
94.6
10.63
317
103.1
11.07
326
111.8
11.52
105
115
Head press PSIG
Cap. Btuh/1000
OD Unit KW
319
64.9
9.66
327
72.0
10.16
335
79.3
10.66
344
87.0
11.17
353
94.9
11.68
362
103.1
12.21
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.
Table PD-19 — Cooling Performance (kW) TTA100B Condensing Unit Only
(SI)
ODTemp
°C
Suction ReferenceTemperature °C
-1.1
1.7
4.4
7.2
10.0
12.8
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1186
27.5
7.46
1227
30.2
7.69
1270
33.1
7.90
1315
36.1
8.11
1362
39.2
8.32
1412
42.4
8.52
18.3
23.9
29.4
35.0
40.6
46.1
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1359
25.9
8.00
1403
28.5
8.27
1449
31.3
8.54
1497
34.1
8.79
1547
37.0
9.05
1600
40.1
9.31
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1546
24.2
8.50
1593
26.7
8.82
1642
29.3
9.13
1693
32.0
9.44
1746
34.8
9.75
1802
37.7
10.07
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1749
22.5
8.94
1799
24.9
9.31
1850
27.3
9.68
1904
29.9
10.05
1960
32.5
10.43
2019
35.2
10.81
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1967
20.8
9.32
2019
23.0
9.76
2073
25.3
10.19
2130
27.7
10.63
2188
30.2
11.07
2249
32.7
11.52
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
2200
19.0
9.66
2255
21.1
10.16
2312
23.2
10.66
2371
25.5
11.17
2431
27.8
11.68
2494
30.2
12.21
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.
SS-PRC003-EN
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Condensing Unit
Table PD-20 — Gross Cooling Capacities (MBh) - Both Compressors - (I-P)
TTA100C Condensing Unit Only
ODTemp
°F
Suction ReferenceTemperature °F
30
35
40
45
50
55
Head press PSIG
Cap. Btuh/1000
OD Unit KW
147.0
95.6
5.6
152.8
105.6
5.8
158.9
116.2
5.9
165.3
127.2
6.1
172.1
138.7
6.3
179.4
150.7
6.4
65
75
Head press PSIG
Cap. Btuh/1000
OD Unit KW
169.9
90.8
6.2
175.8
100.4
6.3
182.2
110.4
6.5
188.9
121.0
6.7
196.0
132.1
6.8
203.6
143.6
7.0
Head press PSIG
Cap. Btuh/1000
OD Unit KW
195.0
85.7
6.8
201.2
94.8
7.0
207.8
104.5
7.2
214.9
114.6
7.3
222.3
125.2
7.5
230.3
136.3
7.7
85
Head press PSIG
Cap. Btuh/1000
OD Unit KW
222.5
80.4
7.6
229.0
89.1
7.8
236.0
98.3
7.9
243.4
108.0
8.1
251.2
118.2
8.3
259.5
128.8
8.5
95
Head press PSIG
Cap. Btuh/1000
OD Unit KW
252.5
74.8
8.5
259.3
83.1
8.6
266.6
92.0
8.8
274.4
101.3
9.0
282.6
111.1
9.2
291.3
121.3
9.4
105
115
Head press PSIG
Cap. Btuh/1000
OD Unit KW
284.9
69.0
9.4
292.1
77.0
9.6
299.8
85.5
9.8
307.9
94.5
10.0
316.6
103.8
10.2
325.7
113.6
10.4
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.
Table PD-20 — Gross Cooling Capacities (kW) - Both Compressors - (SI)
TTA100C Condensing Unit Only
ODTemp
°C
Suction ReferenceTemperature °C
-1.1
1.7
4.4
7.2
10.0
12.8
Head pressure (kPA)
Capacity (kW)
1014
28.0
5.59
1054
30.9
5.76
1095
34.0
5.93
1140
37.2
6.09
1187
40.6
6.27
1237
44.1
6.45
18.3
23.9
29.4
35.0
40.6
46.1
OD Unit Power (kW)
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1171
26.6
6.17
1212
29.4
6.33
1256
32.3
6.50
1302
35.4
6.67
1351
38.7
6.85
1404
42.0
7.04
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1345
25.1
6.85
1388
27.8
7.00
1433
30.6
7.17
1482
33.6
7.35
1533
36.7
7.53
1588
39.9
7.74
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1534
23.5
7.62
1579
26.1
7.78
1627
28.8
7.95
1678
31.6
8.13
1732
34.6
8.32
1789
37.7
8.53
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1741
21.9
8.49
1788
24.3
8.65
1838
26.9
8.82
1892
29.7
9.01
1949
32.5
9.22
2009
35.5
9.43
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1964
20.2
9.44
2014
22.5
9.61
2067
25.0
9.79
2123
27.7
9.99
2183
30.4
10.20
2246
33.3
10.43
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.
32
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Condensing Unit
Table PD-21 — Gross Cooling Capacities (MBh) - Single Compressor - (I-P)
TTA100C Condensing Unit Only
ODTemp
°F
Suction ReferenceTemperature °F
30
35
40
45
50
55
Head press PSIG
Cap. Btuh/1000
OD Unit KW
119.4
52.0
2.9
122.4
58.0
3.0
125.5
64.3
3.1
128.8
70.8
3.1
132.2
77.6
3.2
135.8
84.7
3.2
65
75
Head press PSIG
Cap. Btuh/1000
OD Unit KW
140.4
49.6
3.2
143.6
55.3
3.2
146.8
61.3
3.3
150.3
67.6
3.3
153.9
74.1
3.4
157.6
80.9
3.4
Head press PSIG
Cap. Btuh/1000
OD Unit KW
163.7
47.1
3.4
167.0
52.4
3.5
170.5
58.1
3.5
174.1
64.1
3.6
177.9
70.4
3.6
181.9
77.0
3.7
85
Head press PSIG
Cap. Btuh/1000
OD Unit KW
189.5
44.3
3.8
192.9
49.4
3.8
196.5
54.8
3.9
200.4
60.5
3.9
204.4
66.6
4.0
208.7
72.9
4.0
95
Head press PSIG
Cap. Btuh/1000
OD Unit KW
217.7
41.4
4.2
221.3
46.2
4.2
225.2
51.4
4.2
229.2
56.8
4.3
233.5
62.6
4.3
238.0
68.7
4.4
105
115
Head press PSIG
Cap. Btuh/1000
OD Unit KW
248.5
38.3
4.6
252.4
42.9
4.6
256.4
47.8
4.7
260.7
53.0
4.7
265.3
58.5
4.8
270.0
64.3
4.8
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.
Table PD-21 — Gross Cooling Capacities (kW) - Single Compressor - (SI)
TTA100C Condensing Unit Only
ODTemp
°C
Suction ReferenceTemperature °C
-1.1
1.7
4.4
7.2
10.0
12.8
Head pressure (kPA)
Capacity (kW)
823
15.2
2.95
844
17.0
3.01
866
18.8
3.06
888
20.7
3.12
912
22.7
3.17
936
24.8
3.21
18.3
23.9
29.4
35.0
40.6
46.1
OD Unit Power (kW)
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
968
14.5
3.17
990
16.2
3.22
1012
18.0
3.27
1036
19.8
3.32
1061
21.7
3.37
1087
23.7
3.42
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1129
13.8
3.45
1151
15.3
3.49
1175
17.0
3.54
1200
18.8
3.59
1227
20.6
3.64
1254
22.5
3.69
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1306
13.0
3.78
1330
14.5
3.82
1355
16.0
3.86
1381
17.7
3.91
1409
19.5
3.96
1439
21.3
4.01
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1501
12.1
4.16
1526
13.5
4.20
1552
15.0
4.24
1580
16.6
4.29
1610
18.3
4.34
1641
20.1
4.39
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1714
11.2
4.60
1740
12.6
4.63
1768
14.0
4.67
1798
15.5
4.72
1829
17.1
4.77
1862
18.8
4.82
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.
SS-PRC003-EN
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Condensing Unit
Table PD-22 — Cooling Performance (MBh) TTA125B Condensing Unit Only
(I-P)
ODTemp
°F
Suction ReferenceTemperature °F
30
35
40
45
50
55
Head press PSIG
Cap. Btuh/1000
OD Unit KW
169
115.6
8.89
174
127.1
9.17
180
139.1
9.43
186
151.6
9.70
193
164.5
9.96
199
177.9
10.23
65
75
Head press PSIG
Cap. Btuh/1000
OD Unit KW
194
109.1
9.43
200
120.1
9.77
206
131.6
10.10
212
143.5
10.43
219
155.9
10.76
227
168.6
11.10
Head press PSIG
Cap. Btuh/1000
OD Unit KW
221
102.5
9.98
227
112.9
10.37
234
123.9
10.77
241
135.2
11.17
248
146.9
11.58
256
159.0
11.99
85
Head press PSIG
Cap. Btuh/1000
OD Unit KW
250
95.7
10.52
257
105.6
10.98
264
115.9
11.45
272
126.6
11.92
280
137.7
12.41
288
149.1
12.90
95
Head press PSIG
Cap. Btuh/1000
OD Unit KW
282
88.7
11.06
290
98.1
11.59
297
107.8
12.14
305
117.8
12.69
313
128.2
13.25
321
138.9
13.83
105
115
Head press PSIG
Cap. Btuh/1000
OD Unit KW
317
81.7
11.59
324
90.4
12.21
332
99.5
12.83
340
108.9
13.47
349
118.6
14.11
358
128.6
14.78
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.
Table PD-22 — Cooling Performance (kW) TTA125B Condensing Unit Only
(SI)
ODTemp
°C
Suction ReferenceTemperature °C
-1.1
1.7
4.4
7.2
10.0
12.8
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1163
33.9
8.89
1201
37.2
9.17
1241
40.7
9.43
1283
44.4
9.70
1327
48.2
9.96
1374
52.1
10.23
18.3
23.9
29.4
35.0
40.6
46.1
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1335
32.0
9.43
1377
35.2
9.77
1420
38.5
10.10
1465
42.0
10.43
1512
45.6
10.76
1562
49.4
11.10
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1523
30.0
9.98
1568
33.1
10.37
1614
36.3
10.77
1662
39.6
11.17
1712
43.0
11.58
1765
46.6
11.99
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1727
28.0
10.52
1774
30.9
10.98
1823
33.9
11.45
1874
37.1
11.92
1928
40.3
12.41
1983
43.7
12.90
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1947
26.0
11.06
1997
28.7
11.59
2049
31.6
12.14
2103
34.5
12.69
2159
37.5
13.25
2217
40.7
13.83
Head pressure (kPA)
Capacity (kW)
2185
23.9
2237
26.5
2291
29.1
2347
31.9
2405
34.7
2465
37.7
OD Unit Power (kW)
11.59
12.21
12.83
13.47
14.11
14.78
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.
34
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Condensing Unit
Table PD-23 — Cooling Performance (MBh) TTA155B Condensing Unit Only
(I-P)
ODTemp
°F
Suction ReferenceTemperature °F
30
35
40
45
50
55
Head press PSIG
Cap. Btuh/1000
OD Unit KW
173
140.3
9.95
179
154.9
10.20
186
170.1
10.48
194
185.9
10.78
201
202.2
11.10
209
218.8
11.43
65
Head press PSIG
Cap. Btuh/1000
OD Unit KW
200
136.0
11.00
206
150.0
11.28
214
164.4
11.58
221
179.3
11.90
229
194.6
12.23
238
210.3
12.58
75
Head press PSIG
Cap. Btuh/1000
OD Unit KW
228
130.4
12.22
236
143.6
12.52
243
157.3
12.84
251
171.4
13.17
259
185.9
13.51
268
200.7
13.87
85
Head press PSIG
Cap. Btuh/1000
OD Unit KW
259
123.6
13.60
267
136.1
13.92
275
149.0
14.24
283
162.4
14.58
292
176.1
14.92
301
190.2
15.29
95
Head press PSIG
Cap. Btuh/1000
OD Unit KW
293
115.9
15.15
301
127.6
15.46
309
139.8
15.78
317
152.3
16.11
326
165.3
16.46
336
178.8
16.84
105
115
Head press PSIG
Cap. Btuh/1000
OD Unit KW
328
107.4
16.84
336
118.3
17.13
345
129.7
17.44
354
141.5
17.77
363
153.9
18.12
373
166.8
18.50
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.
Table PD-23 — Cooling Performance (kW) TTA155B Condensing Unit Only
(SI)
ODTemp
°C
Suction ReferenceTemperature °C
-1.1
1.7
4.4
7.2
10.0
12.8
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1192
41.1
9.95
1238
45.4
10.20
1285
49.8
10.48
1336
54.4
10.78
1389
59.2
11.10
1444
64.1
11.43
18.3
23.9
29.4
35.0
40.6
46.1
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1376
39.8
11.00
1424
43.9
11.28
1474
48.1
11.58
1526
52.5
11.90
1581
57.0
12.23
1638
61.6
12.58
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1575
38.2
12.22
1625
42.1
12.52
1677
46.1
12.84
1732
50.2
13.17
1788
54.4
13.51
1848
58.8
13.87
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1789
36.2
13.60
1841
39.9
13.92
1896
43.6
14.24
1952
47.5
14.58
2012
51.6
14.92
2073
55.7
15.29
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
2018
33.9
15.15
2073
37.4
15.46
2130
40.9
15.78
2188
44.6
16.11
2250
48.4
16.46
2315
52.4
16.84
Head pressure (kPA)
Capacity (kW)
2263
31.4
2320
34.6
2379
38.0
2440
41.4
2504
45.1
2571
48.8
OD Unit Power (kW)
16.84
17.13
17.44
17.77
18.12
18.50
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.
SS-PRC003-EN
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Condensing Unit
Table PD-24 — Gross Cooling Capacities (MBh) - Both Compressors - (I-P)
TTA155C Condensing Unit Only
ODTemp
°F
Suction ReferenceTemperature °F
30
35
40
45
50
55
Head press. PSIG
Cap. Btuh/1000
OD Unit KW
164.9
132.3
9.3
170.4
146.2
9.5
176.3
160.9
9.7
182.6
176.2
10.0
189.2
192.1
10.2
196.0
208.5
10.5
65
Head press. PSIG
Cap. Btuh/1000
OD Unit KW
191.3
128.5
10.3
197.3
142.0
10.5
203.6
156.0
10.7
210.3
170.6
11.0
217.2
185.6
11.3
224.4
201.0
11.6
75
Head press. PSIG
Cap. Btuh/1000
OD Unit KW
220.1
123.5
11.4
226.5
136.4
11.7
233.2
149.7
11.9
240.2
163.5
12.2
247.4
177.7
12.5
255.0
192.3
12.8
85
Head press. PSIG
Cap. Btuh/1000
OD Unit KW
251.1
117.4
12.7
257.9
129.6
13.0
265.0
142.2
13.3
272.4
155.3
13.6
280.0
168.7
13.9
287.9
182.6
14.2
95
Head press. PSIG
Cap. Btuh/1000
OD Unit KW
284.5
110.4
14.2
291.7
121.9
14.5
299.1
133.8
14.8
306.8
146.1
15.0
314.8
158.8
15.3
323.2
172.0
15.7
105
115
Head press. PSIG
Cap. Btuh/1000
OD Unit KW
320.2
102.7
15.8
327.7
113.4
16.1
335.4
124.5
16.4
343.4
136.1
16.6
351.8
148.1
16.9
360.6
160.7
17.3
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.
Table PD-24 — Gross Cooling Capacities (kW) - Both Compressors - (SI)
TTA155C Condensing Unit Only
ODTemp
°C
Suction ReferenceTemperature °C
-1.1
1.7
4.4
7.2
10.0
12.8
Head pressure (kPA)
Capacity (kW)
1137
38.7
9.30
1175
42.8
9.50
1216
47.1
1259
51.6
9.96
1304
56.2
1352
61.0
18.3
23.9
29.4
35.0
40.6
46.1
OD Unit Power (kW)
9.72
10.22
10.49
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1319
37.6
10.27
1361
41.6
10.50
1404
45.7
10.75
1450
49.9
11.01
1497
54.3
11.29
1547
58.9
11.58
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1517
36.2
11.41
1562
39.9
11.67
1608
43.8
11.94
1656
47.9
12.22
1706
52.0
12.51
1758
56.3
12.81
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1731
34.4
12.73
1778
38.0
13.00
1827
41.6
13.28
1878
45.5
13.56
1930
49.4
13.86
1985
53.5
14.17
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1962
32.3
14.21
2011
35.7
14.48
2062
39.2
14.76
2115
42.8
15.04
2170
46.5
15.34
2228
50.4
15.66
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
2208
30.1
15.84
2259
33.2
16.10
2313
36.5
16.36
2368
39.8
16.64
2426
43.4
16.94
2487
47.1
17.26
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.
36
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Condensing Unit
Table PD-25 — Cooling Performance (MBh) - Single Compressor - (I-P)
TTA155C Condensing Unit Only
ODTemp
Suction ReferenceTemperature °F
°F
30
35
40
45
50
55
Head press. PSIG
Cap. Btuh/1000
OD Unit KW
137.1
67.8
4.8
139.8
75.1
4.8
142.6
82.9
4.8
145.7
91.3
4.9
149.0
100.1
5.0
152.4
109.4
5.0
65
Head press. PSIG
Cap. Btuh/1000
OD Unit KW
161.2
66.9
5.1
164.2
74.1
5.2
167.3
81.7
5.3
170.6
89.7
5.3
174.1
98.1
5.4
177.7
106.9
5.5
75
Head press. PSIG
Cap. Btuh/1000
OD Unit KW
187.7
65.1
5.6
191.0
72.1
5.7
194.3
79.5
5.7
197.9
87.2
5.8
201.6
95.2
5.9
205.4
103.5
6.0
85
Head press. PSIG
Cap. Btuh/1000
OD Unit KW
216.7
62.6
6.2
220.2
69.4
6.3
223.9
76.5
6.3
227.7
83.8
6.4
231.6
91.5
6.5
235.6
99.4
6.6
95
Head press. PSIG
Cap. Btuh/1000
OD Unit KW
248.3
59.5
6.9
252.0
65.9
6.9
255.9
72.7
7.0
260.0
79.7
7.1
264.1
87.1
7.1
268.5
94.7
7.2
105
115
Head press. PSIG
Cap. Btuh/1000
OD Unit KW
282.5
55.8
7.6
286.5
61.9
7.7
290.6
68.3
7.7
294.9
75.0
7.8
299.3
82.0
7.9
303.9
89.3
8.0
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.
Table PD-25 — Cooling Performance (kW) - Single Compressor - (SI)
TTA155C Condensing Unit Only
ODTemp
°C
Suction ReferenceTemperature °C
-1.1
1.7
4.4
7.2
10.0
12.8
Head pressure (kPA)
Capacity (kW)
945
19.9
4.76
964
22.0
4.80
983
24.3
4.85
1005
26.7
4.91
1027
29.3
4.97
1051
32.0
5.04
18.3
23.9
29.4
35.0
40.6
46.1
OD Unit Power (kW)
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1112
19.6
5.14
1132
21.7
5.19
1154
23.9
5.25
1176
26.3
5.32
1200
28.7
5.39
1225
31.3
5.47
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1294
19.1
5.62
1317
21.1
5.68
1340
23.3
5.75
1364
25.5
5.82
1390
27.9
5.90
1416
30.3
5.98
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1494
18.3
6.19
1518
20.3
6.26
1544
22.4
6.33
1570
24.5
6.41
1597
26.8
6.48
1625
29.1
6.57
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1712
17.4
6.85
1738
19.3
6.92
1765
21.3
6.99
1792
23.3
7.07
1821
25.5
7.15
1851
27.7
7.23
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1948
16.3
7.61
1975
18.1
7.67
2004
20.0
7.74
2033
22.0
7.81
2064
24.0
7.89
2096
26.2
7.97
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.
SS-PRC003-EN
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Condensing Unit
Table PD-26 — Cooling Capacities (MBh)TTA200B Condensing Unit Only
(I-P)
ODTemp
°F
Suction ReferenceTemperature °F
30
35
40
45
50
55
Head press PSIG
Cap. Btuh/1000
OD Unit KW
181
188.3
12.97
187
206.3
13.31
194
225.0
13.66
201
244.3
14.04
208
264.3
14.45
216
285.0
14.88
65
Head press PSIG
Cap. Btuh/1000
OD Unit KW
207
179.3
14.39
214
196.2
14.76
221
213.9
15.15
229
232.4
15.57
237
251.6
16.02
245
271.4
16.48
75
Head press PSIG
Cap. Btuh/1000
OD Unit KW
236
169.7
16.07
244
185.9
16.47
251
202.8
16.90
259
220.4
17.36
267
238.8
17.83
276
257.7
18.32
85
Head press PSIG
Cap. Btuh/1000
OD Unit KW
268
159.7
17.98
276
175.2
18.43
284
191.4
18.90
292
208.4
19.39
301
225.9
19.89
310
244.0
20.40
95
Head press PSIG
Cap. Btuh/1000
OD Unit KW
302
149.2
20.13
311
164.2
20.63
319
179.9
21.14
328
196.2
21.67
338
213.1
22.19
347
230.3
22.70
105
115
Head press PSIG
Cap. Btuh/1000
OD Unit KW
339
138.4
22.50
348
153.0
23.06
358
168.3
23.62
367
184.0
24.18
377
200.1
24.72
387
216.5
25.23
Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.
Table PD-26 — Cooling Capacities (MBh)TTA200B Condensing Unit Only
(SI)
ODTemp
°C
Suction ReferenceTemperature °C
-1.1
1.7
4.4
7.2
10.0
12.8
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1248
55.1
12.97
1292
60.4
13.31
1338
65.9
13.66
1387
71.5
14.04
1437
77.4
14.45
1491
83.4
14.88
18.3
23.9
29.4
35.0
40.6
46.1
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1430
52.5
14.39
1476
57.4
14.76
1525
62.6
15.15
1577
68.0
15.57
1631
73.7
16.02
1688
79.5
16.48
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1630
49.7
16.07
1680
54.4
16.47
1732
59.4
16.90
1787
64.5
17.36
1844
69.9
17.83
1904
75.4
18.32
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
1848
46.7
17.98
1901
51.3
18.43
1957
56.1
18.90
2015
61.0
19.39
2076
66.2
19.89
2139
71.4
20.40
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
2085
43.7
20.13
2142
48.1
20.63
2202
52.7
21.14
2264
57.5
21.67
2329
62.4
22.19
2395
67.4
22.70
Head pressure (kPA)
Capacity (kW)
2340
40.5
2402
44.8
2467
49.3
2533
53.9
2602
58.6
2671
63.4
OD Unit Power (kW)
22.50
23.06
23.62
24.18
24.72
25.23
Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.
38
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Handler
Table PD-27— Evaporator Fan Performance —TWE050A (I-P)
External Static Pressure (Inches of Water Column)
.10"
.20"
.30"
.40" .50" .60" .70" .80"
.90"
1.00"
1.10"
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1400
1500
1600
1700
1800
1900
2000
2100
—
—
—
—
—
—
—
—
646 0.37 698 0.42 751 0.47 803 0.52 856 0.56 908 0.61 941 0.65 973 0.68 1006 0.71
607 0.36 661 0.40 713 0.45 764 0.50 816 0.54 867 0.59 919 0.64 952 0.67 984 0.71
625 0.38 676 0.43 727 0.48 778 0.52 828 0.57 879 0.62 930 0.67 963 0.70 995 0.74
—
—
—
—
—
—
—
—
—
—
—
—
—
—
601 0.35 648 0.40 696 0.44 744 0.49 792 0.54 841 0.59 889 0.64 937 0.69 971 0.73 1005 0.77
625 0.36 671 0.41 716 0.46 762 0.51 807 0.56 853 0.61 898 0.66 944 0.71 979 0.76
642 0.40 687 0.45 731 0.50 776 0.55 820 0.60 865 0.66 909 0.71 951 0.75 987 0.80
659 0.44 703 0.49 745 0.54 790 0.60 833 0.65 877 0.70 920 0.75 957 0.80 994 0.84
674 0.48 722 0.54 770 0.60 817 0.65 857 0.70 897 0.75 936 0.80 973 0.85 1009 0.89
—
—
—
—
—
—
—
—
0.75 HP Standard Motor
and Standard Static Drive
1.0 HP Oversized Motor
and High Static Drive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.
Table PD-27— Evaporator Fan Performance —TWE050A (SI)
External Static Pressure (Pascal)
25
50
75
100
125
150
174
199
224
249
274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2379
2549
2718
2888
3058
3228
3398
3568
—
—
—
—
—
—
—
—
646 0.28 698 0.31 751 0.35 803 0.39 856 0.42 908 0.45 941 0.48 973 0.51 1006 0.53
607 0.27 661 0.30 713 0.34 764 0.37 816 0.40 867 0.44 919 0.48 952 0.50 984 0.53
625 0.28 676 0.32 727 0.36 778 0.39 828 0.43 879 0.46 930 0.50 963 0.52 995 0.55
—
—
—
—
—
—
—
—
—
—
—
—
—
—
601 0.26 648 0.30 696 0.33 744 0.37 792 0.40 841 0.44 889 0.48 937 0.51 971 0.54 1005 0.57
625 0.27 671 0.31 716 0.34 762 0.38 807 0.42 853 0.45 898 0.49 944 0.53 979 0.57
642 0.30 687 0.34 731 0.37 776 0.41 820 0.45 865 0.49 909 0.53 951 0.56 987 0.60
659 0.33 703 0.37 745 0.40 790 0.45 833 0.48 877 0.52 920 0.56 957 0.60 994 0.63
674 0.36 722 0.40 770 0.45 817 0.48 857 0.52 897 0.56 936 0.60 973 0.63 1009 0.66
—
—
—
—
—
—
—
—
0.56 kW Standard Motor
and Standard Static Drive
0.75 kW Oversized Motor
and High Static Drive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.
Table PD-28 — Blower Speeds —TWE050A
Motor DriveTurns Open
Drive
6
5
4
3
2
1
0
Standard
High Static
N/A
N/A
590
713
639
772
688
832
737
891
786
951
835
1009
SS-PRC003-EN
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Handler
Table PD-29— Evaporator Fan Performance TWE075A (I-P)
External Static Pressure (In. Of Water Column)
0.10
0.20
0.30
0.40 0.50 0.60 0.70 0.80
0.90
1.00
1.10
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2000
2125
2250
2375
2500
2625
2750
2875
3000
—
—
—
—
—
—
—
—
443 0.44 489 0.49 535 0.54 581 0.59 627 0.64 673 0.69 719 0.74 765 0.79 791 0.83 818 0.89
453 0.46 499 0.52 546 0.57 592 0.63 638 0.68 684 0.74 730 0.79 771 0.85 798 0.90 825 0.96
463 0.49 510 0.55 556 0.61 602 0.67 649 0.73 695 0.79 742 0.85 776 0.91 804 0.97 831 1.03
473 0.51 520 0.57 567 0.64 613 0.70 660 0.77 706 0.83 753 0.90 782 0.97 810 1.03 838 1.10
445 0.47 489 0.54 533 0.60 578 0.67 622 0.73 667 0.80 711 0.86 756 0.93 784 0.99 813 1.07 842 1.14
464 0.50 506 0.57 548 0.63 589 0.69 631 0.76 672 0.82 714 0.88 757 0.95 786 1.01 815 1.09 844 1.17
484 0.53 523 0.59 562 0.66 601 0.72 640 0.78 678 0.84 717 0.91 758 0.97 787 1.03 817 1.12 847 1.21
504 0.56 540 0.62 576 0.68 612 0.74 648 0.81 684 0.87 720 0.93 759 0.99 789 1.05 819 1.15 850 1.24
524 0.59 557 0.65 590 0.71 624 0.77 657 0.83 690 0.89 723 0.95 760 1.01 790 1.07 821 1.17 853 1.27
1.0 HP Standard Motor
and Low Static Drive
1.0 HP Standard Motor
and Drive
1.5 HP Oversized Motor
and High Static Drive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm)
throwaway filters.
2. Tabulated brake horsepower is the motor shaft output
Table PD-29 — Continued
External Static Pressure (In. Of Water Column)
required.
1.20 1.30 1.40 1.50 1.60
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
844 0.96 871 1.02 897 1.09 924 1.15 950 1.21
3. Factory setting of motor sheave is 1.5 turns open.
Adjustments are made in 0.5 turn increments.
CFM
2000
2125
2250
2375
2500
2625
2750
2875
3000
852 1.03 879 1.09 906 1.16 933 1.22
859 1.10 886 1.17 914 1.23 942 1.30
866 1.17 894 1.24 922 1.30 950 1.37
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
870 1.21 899 1.29 928 1.36
874 1.25 903 1.33 932 1.42
877 1.29 907 1.38 937 1.47
880 1.33 911 1.43 942 1.52
884 1.37 915 1.48 946 1.58
1.5 HP Oversized Motor
—
—
—
—
—
—
—
—
—
—
and High Static Drive
1.0 HP Standard Motor
and Drive
Table PD-29 — Evaporator Fan Performance TWE075A (SI)
External Static Pressure (Pascal)
25
50
75
100
125 150 174
199
224
249
274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
3338
3547
3755
3964
4173
4381
4590
4798
5007
—
—
—
—
—
—
—
—
443 0.33 489 0.37 535 0.4 581 0.44 627 0.48 673 0.51 719 0.55 765 0.59 791 0.62 818 0.66
453 0.34 499 0.39 546 0.43 592 0.47 638 0.51 684 0.55 730 0.59 771 0.63 798 0.67 825 0.72
463 0.37 510 0.41 556 0.45 602 0.5 649 0.54 695 0.59 742 0.63 776 0.68 804 0.72 831 0.77
473 0.38 520 0.43 567 0.48 613 0.52 660 0.57 706 0.62 753 0.67 782 0.72 810 0.77 838 0.82
445 0.35 489 0.4 533 0.45 578 0.5 622 0.54 667 0.6 711 0.64 756 0.69 784 0.74 813 0.8 842 0.85
464 0.37 506 0.43 548 0.47 589 0.51 631 0.57 672 0.61 714 0.66 757 0.71 786 0.75 815 0.81 844 0.87
484 0.4 523 0.44 562 0.49 601 0.54 640 0.58 678 0.63 717 0.68 758 0.72 787 0.77 817 0.84 847 0.9
504 0.42 540 0.46 576 0.51 612 0.55 648 0.6 684 0.65 720 0.69 759 0.74 789 0.78 819 0.86 850 0.92
524 0.44 557 0.48 590 0.53 624 0.57 657 0.62 690 0.66 723 0.71 760 0.75 790 0.8 821 0.87 853 0.95
.75 kW Standard Motor
and Low Static Drive
.75 kW Standard Motor
and Drive
1.12 kW Oversized Motor
and High Static Drive
Notes:
Table PD-29 — Continued
1. Performance based on a wet coil and 1 inch (25.4 mm)
throwaway filters.
2. Tabulated brake horsepower is the motor shaft
External Static Pressure (Pascal)
output required.
3. Factory setting of motor sheave is 1.5 turns open.
Adjustments are made in 0.5 turn increments.
299
324 349 374
398
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW
3338
3547
3755
3964
4173
4381
4590
4798
5007
844 0.72 871 0.76 897 0.81 924 0.86 950 0.9
852 0.77 879 0.81 906 0.87 933 0.91
859 0.82 886 0.87 914 0.92 942 0.97
866 0.87 894 0.92 922 0.97 950 1.02
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Table PD-30 — Blower Speeds —TWE075A
870 0.9 899 0.96 928 1.01
874 0.93 903 0.99 932 1.06
877 0.96 907 1.03 937 1.1
880 0.99 911 1.07 942 1.13
884 1.02 915 1.1 946 1.18
—
—
—
—
—
—
—
—
—
—
Motor DriveTurns Open
Drive
6
5
4
3
2
1
0
Standard
Low Static N/A
High Static N/A
N/A
600
428
700
650
464
750
700
499
800
750
535
850
800
571
900
850
606
950
1.12 kW Oversized Motor and High Static Drive
.75 kW Standard Motor
and Drive
40
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Handler
Table PD-31 — Evaporator Fan Performance TWE100A,TWE100B (I-P)
External Static Pressure (In. Of Water Column)
0.10
0.20
0.30
0.40 0.50 0.60 0.70 0.80
0.90
1.00
1.20
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP Standard Motor and Low Static Drive
2600
460 0.32 493 0.39 527 0.47 565 0.55 603 0.63 641 0.71 679 0.79 717 0.87 744 0.94 772 1.01 826 1.16
473 0.37 506 0.45 540 0.53 576 0.61 613 0.69 649 0.77 686 0.85 723 0.93 748 1.00 775 1.07 830 1.20
487 0.43 519 0.50 552 0.58 587 0.67 623 0.75 658 0.83 693 0.91 728 0.99 751 1.06 779 1.12 833 1.25
501 0.49 532 0.56 565 0.64 599 0.72 632 0.81 666 0.89 700 0.97 734 1.05 755 1.11 783 1.18 737 1.30
520 0.58 548 0.65 581 0.73 613 0.81 644 0.89 677 0.98 710 1.06 740 1.13 759 1.19 787 1.25 841 1.37
541 0.69 568 0.76 600 0.84 631 0.93 658 1.00 691 1.08 721 1.16 746 1.21 764 1.28 793 1.34 846 1.48
562 0.82 588 0.88 618 0.97 648 1.05 671 1.11 703 1.19 732 1.27 753 1.31 772 1.38 801 1.45 853 1.59
582 0.96 608 1.03 637 1.11 666 1.20 685 1.26 711 1.31 739 1.38 763 1.44 787 1.51 815 1.58 862 1.74
602 1.11 628 1.17 656 1.26 683 1.35 698 1.40 720 1.43 747 1.50 773 1.58 801 1.64 829 1.71 872 1.89
2775
2950
3125
3300
3475
3650
3825
4000
1.5 HP Standard Motor and Drive
2.0 HP Oversized Motor
and High Static Drive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are
made in 0.5 turn increments.
Table PD-31— Continued
External Static Pressure (In. Of Water Column)
4. Low Static Drive must be field supplied.
1.40
1.60
CFM
RPM BHP RPM BHP
2.0 HP Oversized Motor
and High Static Drive
2600
2775
2960
3125
3300
3475
3650
3825
4000
881 1.30 936 1.45
884 1.36 938 1.51
886 1.41 939 1.57
889 1.47 941 1.64
892 1.54 945 1.73
897 1.63 950 1.85
902 1.73 955 1.99
912 1.89 960 2.18
922 2.04 965 2.30
Table PD-31— Evaporator Fan Performance TWE0100A,TWE100B (SI)
External Static Pressure (Pascal)
25
50
75
100
125
150
174
199
224
249
299
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 kW Standard Motor and Low Static Drive
4417
4715
5012
5309
5607
5904
6201
6499
6796
460 0.24 493 0.29 527 0.35 565 0.41 603 0.47 641 0.53 679 0.59 717 0.65 744 0.7 772 0.75 826 0.87
473 0.28 506 0.34 540 0.4 576 0.45 613 0.51 649 0.57 686 0.63 723 0.69 748 0.75 775 0.8 830 0.89
487 0.32 519 0.37 552 0.43 587 0.5 623 0.56 658 0.62 693 0.68 728 0.74 751 0.79 779 0.84 833 0.93
501 0.37 532 0.42 565 0.48 599 0.54 632 0.6 666 0.66 700 0.72 734 0.78 755 0.83 783 0.88 737 0.97
520 0.43 548 0.48 581 0.54 613 0.6 644 0.66 677 0.73 710 0.79 740 0.84 759 0.89 787 0.93 841 1.02
541 0.51 568 0.57 600 0.63 631 0.69 658 0.75 691 0.8 721 0.87 746 0.9 764 0.95 793
1
846 1.1
562 0.61 588 0.66 618 0.72 648 0.78 671 0.83 703 0.89 732 0.95 753 0.98 772 1.03 801 1.08 853 1.19
582 0.72 608 0.77 637 0.83 666 0.89 685 0.94 711 0.98 739 1.03 763 1.07 787 1.13 815 1.18 862 1.3
602 0.83 628 0.87 656 0.94 683 1.01 698 1.04 720 1.07 747 1.12 773 1.18 801 1.22 829 1.28 872 1.41
1.12 kW Standard Motor and Drive
1.49 kW Oversized Motor
and High Static Drive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm)
throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 3.0 turns open. Adjustments are
made in 0.5 turn increments.
Table PD-31— Continued
External Static Pressure (Pascal)
349
398
4. Low Static Drive must be field supplied.
m3/hr RPM kW RPM kW
1.49 kW Oversized Motor
and High Static Drive
4417
4715
5012
5309
5607
5904
6201
6499
6796
881 0.97 936 1.08
884 1.01 938 1.13
886 1.05 939 1.17
889 1.1 941 1.22
892 1.15 945 1.29
897 1.22 950 1.38
902 1.29 955 1.48
912 1.41 960 1.63
922 1.52 965 1.72
Table PD-32 — Blower Speeds —TWE100A,TWE100B
Motor SheaveTurns Open
Drive
6
5
4
3
2
1
0
Standard
N/A
587
453
606
745
629
485
641
789
671
518
677
833
713
550
713
877
755
583
748
920
796
615
784
965
Low Static N/A
High Static N/A
High Static II N/A
SS-PRC003-EN
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Handler
Table PD-33 — Evaporator Fan Performance — TWE155B (I-P)
External Static Pressure (Inches of Water Column)
.10"
.20"
.30"
.40"
.50" .60" .70" .80" .90"
1.00"
1.20"
1.40"
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3.0 HP Oversized Motor
and High Static Drive
2.0 HP Standard Motor and Drive
4000
4250
4500
4750
5000
5260
5500
5750
6000
628 1.34 653 1.38 678 1.43 692 1.48 708 1.52 723 1.57 738 1.60 749 1.61 759 1.62 795 1.66 851 1.85 907 2.03
633 1.37 658 1.41 683 1.46 697 1.51 713 1.55 728 1.60 743 1.62 751 1.63 770 1.64 806 1.71 862 1.90 918 2.11
637 1.40 662 1.44 687 1.49 701 1.53 717 1.58 732 1.63 747 1.64 754 1.65 782 1.67 817 1.76 873 1.96 929 2.19
641 1.42 666 1.50 691 1.53 705 1.61 721 1.63 736 1.65 751 1.66 765 1.67 793 1.72 828 1.81 884 2.01 940 2.27
645 1.44 670 1.52 695 1.56 710 1.65 725 1.67 739 1.68 758 1.70 777 1.74 806 1.81 839 1.91 896 2.13
650 1.46 675 1.53 700 1.59 716 1.67 728 1.70 741 1.73 765 1.75 790 1.82 819 1.92 849 2.03 907 2.28
652 1.47 678 1.55 703 1.63 721 1.71 734 1.75 747 1.78 775 1.83 804 1.92 832 2.03 861 2.15 920 2.44
653 1.48 680 1.57 706 1.68 726 1.76 743 1.81 761 1.86 789 1.94 817 2.04 846 2.16 875 2.29 935 2.61
655 1.49 681 1.59 709 1.74 731 1.80 752 1.87 774 1.94 803 2.05 831 2.17 860 2.29 889 2.44 950 2.78
—
—
—
—
—
—
—
—
—
—
Notes:
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.
Table PD-33 — Evaporator Fan Performance TWE155B (SI)
External Static Pressure (Pascal)
25
50
75
100
125
150
174
199
224
249
299
349
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 kW Oversized Motor
1.49 kW Standard Motor and Drive
and High Static Drive
6796
7221
7646
8070
8495
8937
9345
9769
10194
628
1
653 1.03 678 1.07 692 1.1 708 1.13 723 1.17 738 1.19 749 1.2 759 1.21 795 1.24 851 1.38 907 1.51
633 1.02 658 1.05 683 1.09 697 1.13 713 1.16 728 1.19 743 1.21 751 1.22 770 1.22 806 1.28 862 1.42 918 1.57
637 1.04 662 1.07 687 1.11 701 1.14 717 1.18 732 1.22 747 1.23 754 1.23 782 1.25 817 1.31 873 1.46 929 1.63
641 1.06 666 1.12 691 1.14 705 1.2 721 1.22 736 1.23 751 1.24 765 1.25 793 1.28 828 1.35 884 1.5 940 1.69
645 1.07 670 1.13 695 1.16 710 1.23 725 1.25 739 1.25 758 1.27 777 1.3 806 1.35 839 1.42 896 1.59
650 1.09 675 1.14 700 1.19 716 1.25 728 1.27 741 1.29 765 1.3 790 1.36 819 1.43 849 1.51 907 1.7
652 1.1 678 1.16 703 1.22 721 1.28 734 1.3 747 1.33 775 1.36 804 1.43 832 1.51 861 1.6 920 1.82
653 1.1 680 1.17 706 1.25 726 1.31 743 1.3 761 1.39 789 1.45 817 1.52 846 1.61 875 1.71 935 1.95
655 1.11 681 1.19 709 1.3 731 1.34 752 1.35 774 1.45 803 1.53 831 1.62 860 1.71 889 1.82 950 2.07
—
—
—
—
—
—
—
—
—
—
Notes:
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.
Table PD-34— Blower Speeds —TWE155B
Motor SheaveTurns Open
Drive
6
5
4
3
2
1
0
Standard
High Static
619
777
648
806
677
835
705
863
734
892
763
921
N/A
950
42
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Handler
Table PD-35 — Evaporator Fan Performance TWE200B (I-P)
External Static Pressure (In. Of Water Column)
0.10
0.20
0.30
0.40 0.50 0.60 0.70 0.80
0.90
1.00
1.20
140
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5200
5525
5850
6175
6500
6825
7150
7475
7800
—
—
—
—
—
—
461 0.74 503 0.91 545 1.07 587 1.03 619 1.17 685 1.40 723 1.59 750 1.74 777 1.89 851 2.19 898 2.39
479 0.88 521 1.04 563 1.21 605 1.21 640 1.35 701 1.58 739 1.77 766 1.92 793 2.07 859 2.37 906 2.60
497 1.01 539 1.18 581 1.34 623 1.39 661 1.53 717 1.76 755 1.95 782 2.10 809 2.25 868 2.55 915 2.81
473 0.99 515 1.15 557 1.31 599 1.48 641 1.57 682 1.71 732 1.94 769 2.12 796 2.27 823 2.43 877 2.73 924 3.02
492 1.12 534 1.28 576 1.45 618 1.61 660 1.75 702 1.90 748 2.12 784 2.30 811 2.45 838 2.60 886 2.91 933 3.22
510 1.25 552 1.42 594 1.59 636 1.75 678 1.91 723 2.10 763 2.30 794 2.47 820 2.62 846 2.77 894 3.09 941 3.42
528 1.38 570 1.56 612 1.73 654 1.90 697 2.07 744 2.30 779 2.49 804 2.64 830 2.78 855 2.94 903 3.26 950 3.62
550 1.61 594 1.77 640 1.92 683 2.08 721 2.29 760 2.50 790 2.67 815 2.81 840 2.96 865 3.11 914 3.47 959 3.85
572 1.83 618 1.97 668 2.10 712 2.27 746 2.52 776 2.69 802 2.84 826 2.99 851 3.13 876 3.27 926 3.67 969 4.08
3.0 HP Standard
Motor and Low
Static Drive
3.0 HP Standard
3.0 HP Standard Motor
5.0 HP Oversized Motor
Motor and Low
Static Drive System II
and Standard
and High Static
Drive System
Drive System
Notes:
1. Performance based on a wet coil and 2 inch (51mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in
0.5 turn increments.
Table PD-35 — Continued
External Static Pressure (In. Of Water Column)
1.60 1.80
RPM BHP RPM BHP
4. Low static drive components referencing this note are field supplied.
CFM
5.0 HP Oversized Motor and High Static Drive
System
5200
5525
5850
5175
8500
8825
7150
7475
7800
944 2.75 989 3.12
952 2.96 997 3.33
961 3.17 1006 3.54
970 3.38 1015 3.75
978 3.59 1023 3.96
986 3.80
994 4.01
1003 4.25
1012 4.50
—
—
—
—
—
—
—
—
Table PD-35 — Evaporator Fan Performance TWE200B (SI)
External Static Pressure (Pascal)
25
50
75
100 125 150
174
199
224
249
299
349
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
8835
9387
9939
—
—
—
—
—
—
461 0.55 503 0.68 545 0.8 587 0.77 619 0.87 685 1.04 723 1.19 750 1.3 777 1.41 851 1.63 898 1.78
479 0.66 521 0.78 563 0.9 605 0.9 640 1.01 701 1.18 739 1.32 766 1.43 793 1.54 859 1.77 906 1.94
497 0.75 539 0.88 581
1
623 1.04 661 1.14 717 1.31 755 1.45 782 1.57 809 1.68 868 1.9 915 2.1
10491
11044
11596
12148
12700
13252
473 0.74 515 0.86 557 0.98 599 1.1 641 1.17 682 1.28 732 1.45 769 1.58 796 1.69 823 1.81 877 2.04 924 2.52
492 0.84 534 0.95 576 1.08 618 1.2 660 1.3 702 1.42 748 1.58 784 1.72 811 1.83 838 1.94 886 2.17 933 2.4
510 0.93 552 1.06 594 1.19 636 1.3 678 1.42 723 1.57 763 1.72 794 1.84 820 1.95 846 2.07 894 2.3 941 2.55
528 1.03 570 1.16 612 1.29 654 1.42 697 1.54 744 1.72 779 1.86 804 1.97 830 2.07 855 2.19 903 2.43 950 2.7
550 1.2 594 1.32 640 1.43 683 1.55 721 1.71 760 1.87 790 1.99 815 2.1 840 2.21 865 2.32 914 2.59 959 2.87
572 1.36 618 1.47 668 1.57 712 1.69 746 1.88 776 2.01 802 2.12 826 2.23 851 2.33 876 2.44 926 2.74 969 3.04
2.24 kW Standard
Motor and Low
Static Drive System Static Drive System II
2.24 kW Standard
Motor and Low
2.24 kW Standard
Motor and Standard
Drive System
3.73 kW Oversized Motor
and High Static Drive System
Notes:
1. Performance based on a wet coil and 2 inch (51mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in
0.5 turn increments.
Table PD-35 — Continued
External Static Pressure (Pascal)
398
448
4. Low static drive components referencing this note are field supplied.
m3/hr RPM kW RPM kW
3.73 kW Oversized Motor
and High Static Drive System
8835
9387
9939
10491
11044
11596
12148
12700 1003 3.17
13252 1012 3.36
944 2.05 989 2.33
952 2.21 997 2.48
961 2.36 1006 2.64
970 2.52 1015 2.8
978 2.68 1023 2.95
Table PD-36— Blower Speeds —TWE200B
Motor SheaveTurns Open
Drive
6
5
4
3
2
1
0
986 2.83
994 2.99
—
—
—
—
—
—
—
—
Standard
706
457
574
N/A
732
478
595
821
758
500
617
862
784
521
638
903
811
542
659
945
837
563
680
986
863
585
702
Low Static I
Low Static II
High Static
1027
SS-PRC003-EN
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-37— Discharge PlenumAnd GrilleAssemblyThrow Distance (ft) —Air Handler
Unit
Model No.
Louver Angle Deflection Position
CFM
1400
1600
1800
2000
2200
2100
2400
2700
3000
3200
3600
4000
4400
4800
4300
4900
5400
6000
5600
6400
7200
8000
m3/h
2380
2718
3060
3398
3737
3568
4079
4586
5098
5436
6116
6797
7477
8154
7304
8327
9176
10195
9515
10872
12233
13594
Straight
38 (11.6)
42 (12.8)
46 (14.0)
48 (14.6)
51 (15.5)
49 (14.9)
52 (15.9)
55 (16.8)
58 (17.7)
56 (17.1)
62 (18.9)
66 (20.1)
71 (21.6)
76 (23.2)
42 (12.8)
47 (14.3)
52 (15.9)
57 (17.4)
50 (15.2)
56 (17.1)
62 (18.9)
66 (20.1)
20, ft (m)
24 (7.3)
31 (9.4)
40, ft (m)
22 (6.7)
26 (7.9)
55, ft (m)
18 (5.5)
20 (6.1)
22 (6.7)
24 (7.3)
TWE050
TWE075
37 (11.3)
43 (13.1)
50 (15.2)
38 (11.6)
43 (13.1)
48 (14.6)
53 (16.2)
46 (14.0)
51 (15.5)
57 (17.4)
62 (18.9)
67 (20.4)
32 (9.8)
38 (11.6)
44 (13.4)
49 (14.9)
40 (12.2)
46 (14.0)
51 (15.5)
57 (17.4)
29 (8.8)
33 (10.1)
36 (11.0)
31 (9.4)
25 (7.6)
27 (8.2)
29 (8.8)
31 (9.4)
32 (9.8)
30 (9.1)
33 (10.1)
35 (10.7)
38 (11.6)
42 (12.8)
21 (6.4)
25 (7.6)
29 (8.8)
32 (9.8)
27 (8.2)
30 (9.1)
33 (10.1)
35 (10.7)
35 (10.7)
38 (11.6)
42 (12.8)
38 (11.6)
42 (12.8)
47 (14.3)
52 (15.9)
56 (17.1)
29 (8.8)
TWE100
32 (9.8)
TWE155
TWE200
37 (11.3)
41 (12.5)
33 (10.1)
38 (11.6)
42 (12.8)
47 (14.3)
Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s).
Throw distance values at other terminal velocities may be established by multiplying throw distances in table above
by throw factor:
Terminal Velocity
50 fpm (.25 m/s)
100 fpm (.51 m/s)
150 fpm (.76 m/s)
Throw Factor
x
x
x
1.50
.75
.50
Table PD-38— Static Pressure DropThrough Accessories (Inches OfWater Column)1 —
Air Handler
Discharge
Unit
Model No.
Return Grille
Plenum and Grille2
Electric Heaters (kW)
CFM
1400
1600
2000
2100
2400
3000
2800
3200
4300
4800
6000
5600
6400
8000
m3/h
2380
2718
3398
3568
4079
5098
4756
5436
7304
8154
10195
9515
10872
13594
In. wc1 Pascal In. wc1 Pascal
5-10
.06
08
15-20
.06
.08
.13
.03
.06
.12
.04
.13
.02
.03
.06
.04
.0-6
.10
25-30
.12
.14
.19
.05
.08
.17
.14
.19
.04
.06
.12
.10
.13
.20
35-50
—
—
.09
.12
.18
.05
.08
.13
.04
.07
.07
.09
.15
.07
.11
(22.4)
(29.9)
(44.8)
(12.5)
(19.9)
(32.4)
(10.0)
(17.4)
(17.4)
(22.4)
(37.4)
(17.4)
(27.4)
(42.3)
.16
.21
.33
.19
.27
.40
.34
.43
.18
.23
.34
.32
.43
.66
(39.8)
(52.3)
(82.2)
(47.3)
TWE050A
.13
.02
.03
.06
.03
.06
.02
.03
.06
.04
.06
.10
—
.08
.12
.23
.20
.26
.05
.08
.17
.15
.19
.30
TWE075A
(67.2)
(99.6)
(84.7)
(107.1)
(44.8)
(57.3)
TWE100A
TWE100B
TWE155B
TWE200B
(84.7)
(79.7)
(107.1)
(164.3)
.17
1. Return air filter ESP included in Fan PerformanceTable data.
2. At louver opening angle of 42°F (5.5°C). For ESP at other angle openings, see accessory Installer’s Guide.
44
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-39 —Auxiliary Electric Heat Capacity —Air Handler
No.
of
Stages
1
1
1
2
Stage 1
kW
Stage 2
Total
Unit
Model No.
Total
kW
Btu
kW
Btu
Output
—
kW
Input
5.00
9.96
14.96
24.92
Btu
Input
5.00
Output
17,065
33,993
51,058
51,058
Input
—
—
Output
17,065
33,993
51,058
85,051
5.00
9.96
14.96
24.92
TWE050/075/100AD
TWE100BD
9.96
—
—
14.96
14.96
—
9.96
33,993
TWE075, 100AD
TWE100BD
34.88
10.00
19.92
29.92
49.84
2
1
1
2
2
19.92
10.00
19.92
19.92
29.92
67,987
34,130
67,987
67,987
102,117
14.96
—
51,058
—
34.88
10.00
19.92
29.92
49.84
119,045
34,130
67,987
102,117
170,104
TWE155,200B
—
—
10.00
19.92
34,130
67,987
*Heaters are rated at 400v. For other than rated voltage,
2
2
Voltage
Voltage
Rated Voltage
Capacity =
x Rated Capacity and kW =
Rated kW.
(
)
(
)
Rated Voltage
SS-PRC003-EN
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-1 — UnitWiring — Condensing Units
Minimum
Circuit
Ampacity
Maximum Fuse Size
or Maximum Circuit
Breaker
Unit
Model No.
Unit Operating
Voltage
TTA075A
TTA085A
TTA100A
TTA100B
TTA125B
TTA155B
TTA155C
TTA200B
380/415
380/415
380/415
380/415
380/415
380/415
380/415
380/415
15.5
17.8
21.5
26.3
27.4
28.3
35.1
39.3
25
25
35
35
35
35
45
50
Table ED-2 — Electrical Characteristics — Motors — Condensing Units
Compressor Motor
Amps
Condenser Fan Motor
FLA
Amps
LRA
(Ea.)
4.0
Unit
RLA
(Ea.)
11.0
11.9
14.9
10.5
11.0
11.0
14.0
14.9
LRA
(Ea.)
90.0
118.0
118.0
71.0
64.0
90.0
92.5
118.0
Model No.
TTA075A
TTA085A
TTA100A
TTA100B
TTA125B
TTA155B
TTA155C
TTA200B
No.
1
1
1
2
2
2
Phase
No.
1
1
1
1
2
2
Phase
(Ea.)
1.6
3
3
3
3
3
3
3
3
1
1
1
1
1
1
1
1
2.7
2.7
2.7
2.7
1.6
9.3
9.3
7.0
7.0
4.0
3.8
9.3
1
2
2
2
1.6
2.7
NOTE:
1. Electrical characteristics reflect nameplate values and are calculated in accordance with UL and ARI specifications.
Table ED-3 — Electrical Characteristics — Motors —Air Handler
Standard Fan Motor
Oversized Fan Motor
Unit
Amps
Amps
Model No.
TWE050
TWE075
TWE100
TWE155
TWE200
Volts
Phase
FLA
2.9
3.8
4.0
4.5
7.6
LRA
8.2
19.7
27.5
36.2
45.0
Phase
FLA
1.8
4.0
5.3
6.9
9.0
LRA
21.6
27.5
37.5
39.2
65.1
380/415
380/415
380/415
380/415
380/415
3
3
3
3
3
3
3
3
3
3
Table ED-4 — UnitWiring —Air Handler
Minimum
Unit Operating
Voltage Range
Maximum Fuse
Circuit
Ampacity
Unit
Model No.
Size or Maximum
Circuit Breaker
TWE050
TWE075
TWE100
TWE155
TWE200
380/415
380/415
380/415
380/415
380/415
4
5
5
6
10
15
15
15
15
15
46
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electric Heat
Data
Table ED-5 — UnitWiringWith Electric Heat (Single Point Connection) —Air Handlers
Heater
Model No.
Heater
kW Rating1
5.00
To Use
with Unit
Control
Stages
Minimum
Maximum
Circuit Ampacity 2
Fuse Breaker Size 2
BAYHTRL405A
BAYHTRL410A
BAYHTRL415A
BAYHTRL425A
BAYHTRL405A
BAYHTRL410A
BAYHTRL415A
BAYHTRL425A
BAYHTRL435A
BAYHTRL405A
BAYHTRL410A
BAYHTRL415A
BAYHTRL425A
BAYHTRL435A
BAYHTRM410A
BAYHTRM420A
BAYHTRM430A
BAYHTRM450A
BAYHTRM410A
BAYHTRM420A
BAYHTRM430A
BAYHTRM450A
1
1
1
2
1
1
1
2
2
1
1
1
2
2
1
1
2
2
1
1
2
2
11
17
24
37
12
18
25
38
51
12
19
25
38
52
19
32
46
72
23
36
49
76
15
20
25
40
15
20
25
40
60
15
20
25
40
60
20
35
50
80
25
40
50
80
9.96
TWE050AD
TWE075AD
14.96
24.92
5.00
9.96
14.96
24.92
34.88
5.00
9.96
14.96
29.92
34.88
10.00
19.92
29.92
49.84
10.00
19.92
29.92
49.84
TWE100AD,TWE100BD
TWE155BD
TWE200BD
1. kW ratings are at 400v for 3 phase, 400v air handlers
2
2
Voltage
Voltage
Rated Voltage
For other than rated voltage, ampacity =
x Rated Capacity and kW =
Rated kW.
(
)
(
)
Rated Voltage
2. Any power supply and circuits must be wired and protected in accordance with local codes. MCA and Maximum Fuse Size is based on 400V.
3. Field wire must be rated at least 167°F (75°C).
4. Field wire must be rated at least 194°F (90°C).
SS-PRC003-EN
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Jobsite
Connections
Wiring shown with dashed lines is to be
furnished and installed by the customer.
All customer- supplied wiring must be
copper only and must conform to local
electrical codes.
NOTE:
1.When electric heater accessory is
used, single point power entry or dual
point power entry is field optional.
Single point power entry option is
through electric heater only.
TTA050/TWE050A
FieldWiring:
A — 3 power wires. Line voltage for
3 phase, 2 wires for single phase.
B — 3 power wires. Line voltage for
3 phase, 2 wires for single phase.
C — Cooling only thermostat: 3 wires,
24 volts.
— One-stage electric heat: add
1 additional wire, 24 volts.
— Two-stage electric heat: add
2 additional wires, 24 volts.
D — 2 wires, 24 volts.
D — 5 wires, 24 volts.
(2)TTA050/TWE100B
TTA075A/TWE075A;
FieldWiring:
TTA085/TWE075A;
TTA125B/TWE155B;
A — 3 power wires. Line voltage for
3 phase, 2 wires for single phase.
B — 3 power wires. Line voltage for
3 phase, 2 wires for single phase.
C — Cooling only thermostat: 4 wires,
24 volts.
— One-stage electric heat add
1 additional wire, 24 volts.
— Two-stage electric heat: add
2 additional wires, 24 volts.
D — 2 wires, 24 volts to outdoor
section ‘’A’’
TTA085/TWE100A;
TTA155B/TWE155B;
TTA100A/TWE100A
TTA200B/TWE200B;
FieldWiring:
TTA155C/TWE155B
A — 3 power wires, line voltage.
B — 3 power wires, line voltage for
3 phase; 2 wires for single phase.
C — Cooling only thermostat: 3 wires,
24 volts.
FieldWiring
A — 3 power wires, line voltage
B — 3 power wires, line voltage
C — Cooling only thermostat: 4 wires,
24 volts.
— One-stage electric heat: add
1 additional wire, 24 volts.
— Two-stage electric heat: add
2 additional wires; 24 volts.
D — 4 wires, 24 volts.
— One-stage electric heat: add
1 additional wire, 24 volts.
— Two-stage electric heat: add
2 additional wires, 24 volts.
D — 5 wires, 24 volts.
— 2 wires, 24 volts to outdoor
section ‘’B’’
TTA100B/TWE100B
FieldWiring:
A — 3 power wires, line voltage.
B — 3 power wires, line voltage for
3 phase; 2 wires for single phase.
C — Cooling only thermostat: 4 wires,
24 volts.
(2)TTA075A/TWE155B;
(2)TTA100A/TWE200B
FieldWiring:
A — 3 power wires, line voltage.
B — 3 power wires, line voltage.
C — Cooling only thermostat: 4 wires,
24 volts.
— One-stage electric heat: add
1 additional wire, 24 volts.
— Two-stage electric heat: add
2 additional wires, 24 volts.
— One-stage electric heat: add
1 additional wire, 24 volts.
— Two-stage electric heat: add
2 additional wires, 24 volts.
D — 6 wires, 24 volts.
48
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
Air Handler
Air Handler
Typical wiring diagram. For specific
wiring, see individual Service Facts.
SS-PRC003-EN
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
Condensing Unit
Condensing Unit — Single Compressor
Typical wiring diagram. For specific
wiring, see individual Service Facts.
50
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
Condensing Unit
Condensing Unit — Single Compressor
SS-PRC003-EN
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
Condensing Unit
Condensing Unit — Dual Compressor
Typical wiring diagram. For specific
wiring, see individual Service Facts.
52
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
Condensing Unit
Condensing Unit — Dual Compressor
C757164P01
SS-PRC003-EN
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-1 —TTA075 Condensing Units
All dimensions are in inches and millimeters.
Note 1:
Minimum Clearance for proper operation
is 36 inches (914) from walls, shrubbery,
privacy fences, etc. Minimum clearance
between adjacent units is 72 inches (1829).
54
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-2 —TTA085A and 100A Condensing Units
All dimensions are in inches and millimeters.
Note 1:
Minimum Clearance for proper operation
is 36 inches (914) from walls, shrubbery,
privacy fences, etc. Minimum clearance
between adjacent units is 72 inches (1829).
SS-PRC003-EN
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-3 —TTA100C Condensing Units
All dimensions are in inches and millimeters.
Note 1:
Minimum Clearance for proper operation
is 36 inches (914) from walls, shrubbery,
privacy fences, etc. Minimum clearance
between adjacent units is 72 inches (1829).
56
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-4 —TTA100B andTTA125B Condensing Units
All dimensions are in inches and millimeters.
SS-PRC003-EN
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD- 5—TTA155B Condensing Unit
All dimensions are in inches and millimeters.
Note 1:
Minimum Clearance for proper operation
is 36 inches (914) from walls, shrubbery,
privacy fences, etc. Minimum clearance
between adjacent units is 72 inches (1829).
58
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-6 — TTA155C Condensing Units
All dimensions are in inches and millimeters.
Note 1:
Minimum Clearance for proper operation
is 36 inches (914) from walls, shrubbery,
privacy fences, etc. Minimum clearance
between adjacent units is 72 inches (1829).
SS-PRC003-EN
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-7 —TTA200B Condensing Unit
All dimensions are in inches and millimeters.
Note 1:
Minimum Clearance for proper operation
is 36 inches (914) from walls, shrubbery,
privacy fences, etc. Minimum clearance
between adjacent units is 72 inches (1829).
60
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-8 —TWE050AAir Handlers
All dimensions are in inches and millimeters.
Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.
SS-PRC003-EN
61
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-9 —TWE075AAir Handlers
All dimensions are in inches and millimeters.
Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.
62
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-10 —TWE100A Air Handlers
All dimensions are in inches and millimeters.
Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.
SS-PRC003-EN
63
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-11 —TWE100B Air Handlers
All dimensions are in inches and millimeters.
Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.
64
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-12 —TWE050A, 075A, 100A andTWE100BAir Handlers
All dimensions are in inches and millimeters.
Table DD-1 —Air Handler Dimensions — in. (mm)
Model No.
TWE050A
AA
AB
12 1/16
(306.4)
16
(406.4)
16
(406.4)
16
(406.4)
AC
AD
AE
2 15/16
(74.6)
6 5/8
AF
AJ
7 13/16
(198.4)
7
(177.8)
7
(177.8)
7
(177.8)
AK
12 3/8
(314.3)
16
(406.4)
16
(406.4)
16
(406.4)
AL
35 5/8
1 5/8
32 1/4
32 1/4
34 9/16
(878)
(905)
(41.3)
1 11/16
(42.9)
1 11/16
(42.9)
1 11/16
(42.9)
(819.2)
41 15/16
(1065.2)
57 15/16
(1471.6)
57 15/16
(1471.6)
(819.2)
TWE075A
TWE100A
TWE100B
45 1/8
41 3/4
36 7/8
(1146.2)
(168.3)
(1060.5)
57 13/16
(1468.4)
57 13/16
(1468.4)
(936.6)
61 1/8
6 5/8
36 7/8
(1552.6)
61 1/8
(1552.6)
(168.3)
6 5/8
(168.3)
(936.6)
36 7/8
(936.6)
SS-PRC003-EN
65
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-13 —TWE155B Air Handlers
All dimensions are in inches and millimeters.
Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.
66
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-14 —TWE200BAir Handlers
All dimensions are in inches and millimeters.
Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.
SS-PRC003-EN
67
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-15 —TWE155B and 200BAir Handlers
All dimensions are in inches and millimeters.
Table DD-2 —Air Handler Dimensions — in. (mm)
Model No.
TWE155B
TWE200B
A
B
C
D
E
F
G
H
J
77 1/4 (1962.2)
89 1/4 (2267)
1 3/16 (30.2)
1 11/16 (42.9)
48 (1219.2)
11 7/16 (290.5)
18 (457.2)
3 3/8 (85.7)
3 1/16 (77.8)
35 1/16 (890.6)
39 1/8 (993.8)
73 7/8 (1876.4)
82 7/8 (2105)
3 3/4 (95.3)
4 9/16 (115.9)
50 13/16 (1290.6) 11 1/2 (292.1)
20 1/8 (511.2)
Table DD-2 —Air Handler Dimensions — in. (mm) (Continued)
Model No.
TWE155B
TWE240B
K
L
M
N
P
Q
R
S
T
35 1/16 (890.6)
39 1/8 (993.8)
2 13/16 (71.4)
4 7/8 (123.8)
18 (457.2)
20 (508)
3 9/16 (90.5)
3 (76.2)
2 7/8 (73)
35 1/16 (890.6)
39 1/8 (993.8)
3 3/4 (95.3)
4 9/16 (115.9)
35 1/16 (890.6)
39 1/8 (993.8)
73 3/8 (1863.7)
82 7/8 (2105)
4 13/16 (122.2)
68
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure 16 — Electric Heater forTWE050, 075, 100 Air Handlers
All dimensions are in inches and millimeters.
Figure DD-17 — Electric Heater forTWE155 and 200Air Handlers
SS-PRC003-EN
69
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Table DD-3 — Discharge Plenum And
Figure DD-18 — Discharge Plenum and Grille
Grille Dimensions — in. (mm)
All dimensions are in inches and millimeters.
Model
Model No.
A
B
C
28
TWE050 BAYPLNM015
TWE075 BAYPLNM016
TWE100 BAYPLNM017
3715/16 2115/16
(963.6) (557.2) (711.2)
471/2
(1206.5) (635) (711.2)
631/2
25 28
(1612.9) (635) (711.2)
25
28
Table DD-4 — Discharge Plenum And
Grille Dimensions — in. (mm)
For Use with Electric Heat
Model
Model No.
A
B
C
29
TWE050 BAYPLNM025
TWE075 BAYPLNM026
TWE100 BAYPLNM027
TWE155 BAYPLNM028
TWE200 BAYPLNM029
3715/16 2115/16
(963.6) (557.2) (736.6)
471/2
(1206.5) (635) (736.6)
631/2
25 29
(1612.9) (635) (736.6)
791/2 2711/16
35
(2019.3) (703.3) (889)
921/2
35
(2349.5) (773.1) (889)
25
29
307/16
Table DD-5 — Subbase Dimensions
Figure DD-19 — Subbase
— in. (mm)
Model
Model No.
A
B
TWE050 BAYBASE001
TWE075 BAYBASE002
TWE100 BAYBASE003
TWE155 BAYBASE004
TWE200 BAYBASE005
38
22
(558.8)
25
(635)
25
(635)
275/8
(701.7)
307/16
(773.1)
(965.2)
471/2
(1206.5)
631/2
(1612.9)
791/2
(2019.3)
921/2
(2349.5)
70
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-20 — HotWater Coil
All dimensions are in inches and millimeters.
3.00 (76 mm) DIA.
HOLE FOR 2” (50.8 mm) NPT
SUPPLY
3.00 (76 mm) DIA.
HOLE FOR 2” (50.8 mm) NPT
RETURN
329/32
99 mm
BAYWATR017
3.00 (76 mm) DIA.
HOLE FOR 2” (50.8 mm) NPT
SUPPLY
3.00 (76 mm) DIA.
HOLE FOR 2” (50.8 mm) NPT
RETURN
BAYWATR018
BAYWATR019
BAYWATR020
BAYWATR021
Table DD-6 — HotWater Coil Dimensions — in. (mm)
Model
TWE050
Accessory No.
BAYWATR017
A
38
B
C
D
5
(127)
5
(127)
6
(152)
6
E
9
F
G
14
(356)
14
(356)
16
(406)
16
H
26
(660)
30
(762)
36
(914)
51
J
12
(305)
18
(457)
18
(457)
18
(457)
18
K
6
L
N
M
MM
109/16
(268)
77/8
223/32
(561)
255/32
(639)
255/32
(639)
2725/32
(706)
3019/32
(777)
135/8
141/32
(356)
171/8
(435)
171/8
(435)
193/4
(502)
229/16
(573)
41/32
227/32
(72)
227/32
(72)
227/32
(72)
17/8
81/32
(965)
4719/32
(1209)
6319/32
(1615)
7921/32
(2023)
9221/32
(2353)
(346)
1519/32
(396)
1519/32
(396)
147/16
(367)
163/8
(229)
1027/32
(275)
117/8
(302)
153/32
(383)
1423/32
(374)
(152)
827/32
(225)
1327/32
(352)
147/32
(361)
147/32
(361)
(102)
(204)
103/8
(264)
103/8
(264)
99/16
TWE075
TWE100
TWE155
TWE200
BAYWATR018
BAYWATR019
BAYWATR020
BAYWATR021
83/32
(206)
83/32
(206)
615/16
(176)
87/8
(200)
77/8
(200)
71/16
(152)
7
(178)
(406)
18
(457)
(1295)
64
(1626)
(48)
(243)
(179)
33/4
99/16
71/16
(416)
(457)
(225)
(95)
(243)
(179)
SS-PRC003-EN
71
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Figure DD-21 — Steam Coil
All dimensions are in inches and millimeters.
Table DD-7 — Steam Coil Dimensions — in. (mm)
Model
Accessory No.
A
38
B
C
D
5
E
9
F
G
14
H
J
K
2
L
M
26
N
12
P
6
Q
R
TWE050 BAYWATR012
TWE075 BAYWATR013
TWE100 BAYWATR014
TWE155 BAYWATR015
TWE200 BAYWATR016
221/8
133/16
141/16
103/8
113/8
11/2
27/8
93/4
(965.2) (562) (335)
475/8
(1209.7) (639.8) (503.2) (127) (276.2) (435) (355.6) (339.7) (288.9) (63.5) (50.8) (762) (457.2) (225.4) (73) (247.7)
635/8 117/8 171/8 133/8 111/8 21/2 133/8 27/8 93/4
16 36 18
(1616.1) (639.8) (503.2) (152.4) (301.6) (435) (406.4) (339.7) (282.6) (63.5) (50.8) (914.4) (457.2) (339.7) (73) (247.7)
795/8 193/4 181/2 111/8 21/2 17/8 93/4
16 51 18
(2022.5) (706.4) (633.4) (152.4) (382.6) (501.7) (406.4) (469.9) (282.6) (63.5) (50.8) (1295.4) (457.2) (360.4) (47.6) (247.7)
925/8 305/8 257/8 143/4 191/2 121/6 21/2 33/4 107/8
18 64 18
(127) (228.6) (357.2) (355.6) (263.5) (288.9) (50.8) (38.1) (660.4) (304.8) (152.4) (73) (247.7)
5
253/16
253/16
1913/16
1913/16
107/8 171/8 133/8 113/8 21/2 87/8 27/8 93/4
14 30 18
2
6
2
2713/16 2415/16
6
151/16
2
143/16
143/16
7
229/16
2
(2352.7) (777.9) (657.2) (177.8) (374.7) (573.1) (457.2) (495.3) (309) (63.5) (50.8) (1625.6) (457.2) (360 .4) (95.3) (276.2)
72
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Weights
TableW-1 — Unit and CornerWeights — lb (kg)
Unit
Shipping
Net
CornerWeights
Model No.
TTA075A
Maximum — lb (kg) Maximum — lb (kg)
1
105
(47.6)
134
(60.8)
153
(69.4)
139
(63.0)
153
(69.4)
192
(87.1)
216
2
80
3
59
4
78
(35.4)
94
(42.6)
83
(37.7)
86
(39.0)
89
(40.4)
142
(64.4)
118
366
(166.0)
444
(201.4)
514
322
(146.1)
390
(176.9)
460
(36.3)
95.5
(43.3)
145
(65.8)
125
(56.7)
156
(70.8)
192
(26.8)
66.5
(30.2)
79
(35.8)
78
(35.4)
90
(40.8)
142
(64.4)
115
(52.2)
176
(79.8)
TTA100A
TTA100B
TTA100C
TTA125B
TTA155B
TTA155C
TTA200B
(233.1)
483
(219.1)
542
(208.7)
428
(194.1)
488
(245.9)
744
(337.5)
745
(221.4)
668
(303.0)
660
(87.1)
211
(95.7)
232
(337.9)
915
(415.0)
(299.4)
830
(376.5)
(98.0)
240
(108.9)
(53.5)
182
(82.6)
(105.2)
TableW-2 —AccessoryWeights — Net lb (kg)
Unit
Model No.
TTA075A
RIS
Steel Spring
Isolators
12
Anti Short
Coil
Guard
8
(3.6)
11
(5)
20
Low
Ambient
23
(10.4)
23
(10.4)
23
Isolators
CycleTimer
Thermostats
2
(.9)
2
(.9)
2
1
(.5)
1
(.5)
1
1
(.5)
1
(.5)
1
(5.4)
12
(5.4)
12
TTA100A
TTA100B
TTA125B
(.9)
2
(.9)
2
(.9)
(5.4)
12
(5.4)
12
(5.4)
(.5)
1
(.5)
1
(.5)
(9.1)
22
(10)
34
(.5)
1
(.5)
1
(.5)
(10.4)
23
(10.4)
23
(10.4)
TTA155D
TTA155C
TTA200B
(15.4)
TTA155, 200
TTA075, 100, 125
SS-PRC003-EN
73
Download from Www.Somanuals.com. All Manuals Search And Download.
Weights
TableW-3 —Air Handlers, Coils,And CornerWeights — lb (kg)1
Unit
Model No.
TWE050
Shipping
Maximum (lb)
298
Net
Maximum (lb)
262
CornerWeights —Vertical
CornerWeights — Horizontal
#1
59
(26.8)
79
(35.9)
107
(48.5)
173
#2
59
(26.8)
79
#3
59
(26.8)
79
#4
59
(26.8)
79
(35.9)
107
(48.5)
173
A
54
(24.5)
77
(35)
102
(46.3)
174
(79)
185
(84)
B
64
C
64
(29.03)
81
D
54
(24.5)
73
(33.1)
102
(46.3)
170
(77.1)
179
(81.2)
(135)
(118.9)
346
(157)
419
(190.1)
690
(313)
820
(372)
(29)
TWE075
TWE100
TWE125
TWE200
388
(176)
473
(214.6)
754
(342)
886
(401.9)
84
(35.9)
107
(48.5)
173
(35.9)
107
(48.5)
173
(38.1)
113
(51.3)
156
(36.7)
113
(51.3)
190
(78.5)
204
(92.5)
(78.5)
204
(92.5)
(78.5)
204
(92.5)
(78.5)
204
(92.5)
(70.8)
228
(103.4)
(86.2)
221
(100.3)
Note:
1. If application requires steam or hot water heating coils, field supplied isolators must be utilized.
Vertical
TWE050, 075, 100
Vertical
TWE155, 200
Horizontal
TWE050, 075, 100
Horizontal
TWE155, 200
TableW-4 —AccessoryWeights (Net lb)
RIS
RIS
Isolator
Suspended
Mount
9
Steel Spring Steel Spring
Discharge
Plenum
And Grille1
58
Discharge
Plenum
And Grille2
93
Electric
Heat
Min. Max.
32/43
Isolator
Floor
Mount
2
Isolator
Floor
Mount
12
Isolator
Suspended
Mount
6
Unit
Return
Air Grille
3
Oversized
Motor
31
Model No.
TWE050
Subbase
14
(26.3)
73
(33.1)
92
(41.7)
124
(56.3)
145
(42.2)
123
(55.8)
156
(70.8)
230
(104.3)
264
(1.4)
5
(2.3)
7
(3.2)
10
(4.5)
12
(14.5/19.5)
27/45
(12.3/20.4)
27/45
(12.3/20.4)
79/100
(35.8/45.4)
79/100
(6.4)
19
(8.6)
23
(10.4)
27
(12.3)
31
(14.1)
48
(21.8)
50
(22.7)
80
(36.3)
88
(.9)
2
(.9)
2
(.9)
2
(.9)
2
(4)
6
(2.7)
7
(3.2)
7
(3.2)
9
(5.4)
12
(5.4)
12
(5.4)
12
(5.4)
12
(2.7)
6
(2.7)
6
(2.7)
6
(2.7)
6
TWE075
TWE100
TWE155
TWE200
(65.8)
(119.8)
(5.4)
(35.8/45.4)
(14.06)
(40)
(.9)
(4)
(5.4)
(2.7)
Note:
1. For use when no heat is supplied.
2. For use with electric heat.
74
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications Condensing Units
General
Refrigeration System – Dual Compressor
TTA100B,TTA125B,TTA155B,TTA200B
units shall have two separate and
independent refrigeration circuits. Each
refrigeration circuit shall have an integral
subcooling circuit. A refrigeration filter
drier shall be provided as standard.
Units shall have both a liquid line and
suction gas line service valve with gauge
port.
Refrigeration System — Dual
Units shall be assembled on heavy
gauge steel mounting/lifting rails and
shall be weatherproofed. Units shall
include a hermetic scroll or reciprocating
compressor(s), plate fin condenser coil,
fans and motors, controls, and holding
charge of nitrogen. Operating range
shall be between 115°F (46.1°C) and 35°F
(1.7°C) in cooling as standard from the
factory. Units shall be rated in
Manifolded Compressors
TTA 100C andTTA155C units shall have
a single refrigeration circuit with an
integral subcooling circuit. A
refrigeration filter drier shall be
provided as standard. Units shall have
both a liquid line and suction gas line
service valve with gauge port.
The units shall have two scroll
compressors manifolded together.
Motor shall be suction gas-cooled and
shall have a voltage utilization range of
plus or minus 10 percent of nameplate
voltage. Crankcase heater, discharge
line thermostat, and current-sensitive
motor overloads shall be included for
maximum protection. Scroll type
compressor shall provide inherently
low vibration and noise by having no
suction and discharge valves. External
high and low pressure cutout devices
shall be provided. Evaporator defrost
control provided in the indoor blower
coil shall prevent compressor slugging
by temporarily interrupting
accordance with ARI Standard 210/240,
340/360 or 365.
TTA100B,TTA125B, units shall have two
Trane direct-drive, hermetic
reciprocating compressors with
centrifugal oil pump and provide
positive lubrication to all moving parts.
Reciprocating compressor shall have
internal spring isolation and sound
muffling to minimize vibration
transmission and noise.
Casing
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant baked enamel finish.
Units surface shall be tested 500 hours
in salt spray test. Units shall have
removable end panels which allow
access to all major components and
controls.
TTA155B,TTA200B units shall have two
Trane direct-drive, hermetic scroll
compressors with centrifugal oil pump
and provide positive lubrication to all
moving parts. Motor shall be suction
gas-cooled and shall have a voltage
utilization range of plus or minus 10
percent of nameplate voltage. Crankcase
heater, discharge line thermostat, and
current-sensitive motor overloads shall
be included for maximum protection.
Scroll compressor shall provide
inherently low vibration and noise by
having no suction and discharge valves.
External high and low pressure cutout
devices shall be provided. Evaporator
defrost control provided in indoor
blower coil shall prevent compressor
slugging by temporarily interrupting
compressor operation when low
evaporator coil temperatures are
encountered.
Refrigeration System – Single
Compressor
TTA075A,TTA100A units shall have a
single refrigeration circuit. Each
compressor operation when low
evaporator coil temperatures are
encountered.
refrigeration circuit has an integral
subcooling circuit. A refrigeration filter
drier shall be provided as standard.The
units shall have both a liquid line and
suction gas line service valve with gauge
port.TTA075A,TTA100A units shall have
one direct-drive, hermetic scroll
compressor with centrifugal oil pump
providing positive lubrication to moving
parts. Motor shall be suction gas-cooled
and shall have a voltage utilization range
of plus or minus 10 percent of unit
nameplate voltage. Crankcase heater,
discharge line thermostat, and current-
sensitive motor overloads shall be
included for maximum protection. Scroll
type compressor shall provide
inherently low vibration and noise by
having no suction and discharge valves.
External high and low pressure cutout
devices shall be provided. Evaporator
defrost control provided in indoor
blower coil shall prevent compressor
slugging by temporarily interrupting
compressor operation when low
evaporator coil temperatures are
encountered.
Condenser Coil
Coils shall be internally finned or
smooth bore 3/8” (10 mm) copper tubes
mechanically bonded to a configured
aluminum plate fin as standard. Coil
shall be factory pressure and leak
tested to 420 psig (2,899 kPa) air
pressure. Metal grilles with PVC
coating for coil protection is optional.
Condenser Fan And Motor(s)
Direct-drive, statically and dynamically
balanced, 26 or 28-inch (660 or 711
mm) propeller fan(s) with aluminum
blades and electro- coated steel hubs
shall be used in draw-thru vertical
discharge position. Either permanently
lubricated totally enclosed or open
construction motors shall be provided
and shall have built-in current and
thermal overload protection. Motor(s)
shall have be either ball or sleeve
bearing type.
SS-PRC003-EN
75
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications Condensing Units
Controls
Hot Gas Bypass Kit —This accessory
shall be available to provide capacity
modulation.
Condensing units shall be completely
factory wired with necessary controls
and contactor pressure lugs or
terminal block for power wiring.
Control wiring shall be 24-volt control
circuit which includes fusing and
control transformer. Units shall provide
external location for mounting a fused
disconnect device.Time delay timers to
prevent compressors in dual
Time Delay Relay —This accessory
shall prevent compressors in dual
compressor unit from combine on line
simultaneously.Time shall be 24-volt,
60 cycle, with four minute timing
period.
Anti-Short-CycleTimer —This
accessory shall prevent rapid on-off
compressor cycling in light load
conditions by not allowing compressor
to operate for 5-7 minutes upon
shutdown.This accessory shall consist
of a 24-volt, solid state timing device
with either 5 or 7 minute fixed-off
timing period.
compressor units from simultaneous
start-up and anti- recycle timers are
available as optional accessories.
Low Ambient Operation
Standard units shall start and operate
to approximately 35°F (1.7°C) when
matched withTrane air handlers and
coils. Optional head pressure control
accessory permits operation to 0°F (-
17.8°C).
Condenser Coil Guard — Metal grille
with PVC coating shall be provided to
alleviate coil damage.
Accessories
Factory InstalledAccessories
Low Ambient Head Pressure Control
—This accessory shall modulate the
RPM of unit outdoor fan motor in
response to outdoor ambient
temperature and unit head pressure.
Accessory provides unit cooling
operation to outdoor temperatures of
0° F (-17.8° C).
Black Epoxy Coated Condenser Coil —
This option is designed to provide
corrosion protection of air cooled
condenser coils for seacoast
application.The black epoxy coil
protection is a factory applied
thermoset vinyl coating, bonded to
normal aluminum fin stock.The
uniform thickness of the bonded vinyl
layer exhibits excellent corrosion
protection in salt spray tests performed
in accordance with ASTM B177.
Vibration Isolation Packages —This
accessory shall reduce transmission of
noise and vibration to building
structures, equipment, and adjacent
spaces. Packages shall be available in
either neoprene-in-shear or spring-flex
types.
76
SS-PRC003-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications Air Handlers
General
Evaporator Fan
Discharge Plenums and Grilles —
Accessory discharge plenums shall be
available for vertical, free discharge
applications. Plenums shall be
constructed of heavy-gauge, zinc coated,
galvanized steel finished with baked
enamel to match the air handler unit.
Grilles shall be satin finished aluminum
and have four-way adjustable louvers.
Air handler units shall be completely
factory assembled including coil,
condensate drain pan, fan motor(s),
filters, and controls in an insulated
casing that can be applied in either
vertical or horizontal configuration. Units
shall be rated and tested in accordance
with ARI Standard 210, 240, 360.
Double inlet, double width, forward
curved, centrifugal-type fan(s) with
adjustable belt drive shall be standard.
Thermal overload protection shall be
standard on motor. Fan and motor
bearings shall be permanently
lubricated. Oversized motors shall be
available as an option for high static
application.
Casing
ReturnAir Grilles —Accessory return air
grille shall be provided for vertical front,
free return applications. Grilles shall be
installed in place of the front lower side
panel. Grille shall be satin finished
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant baked enamel finish.
Casing is completely insulated with fire-
retardant, permanent, odorless, glass
fiber material. Knockouts shall be
provided for unit electrical power and
refrigerant piping connections. Captive
screws shall be standard on all access
panels.
Controls
Magnetic evaporator fan contactor, low
voltage terminal strip, check valve(s), and
single point power entry shall be
included. All necessary controls shall be
factory-installed and wired. Evaporator
defrost control shall be included to
prevent compressor slugging by
temporarily interrupting compressor
operation when low evaporator coil
temperatures are encountered.
aluminum with non-adjustable louvers.
Mounting Subbase —This accessory
shall be available for vertical floor mount
configurations. Subbase shall be
constructed of heavy gauge, zinc coated,
galvanized steel with baked enamel
finish to match air handler unit. Subbase
is required in the vertical air flow
application for condensate drain
trapping and when isolators are
required.
Filters
Refrigeration System
One inch, throwaway filters shall be
standard onTWE050A,TWE050B,
TWE075A,TWE100A andTWE100B
model air handlers. Filters shall be
accessible from the side coil access
panel. Filter rack can be field converted
to two-inch capability.Two-inch
throwaway filters shall be standard on
TWE155B andTWE200B models.
TheTWE050A,TWE075A,TWE100A units
shall have a single refrigeration circuit
and theTWE050B,TWE100B,TWE155B,
TWE200B units shall have dual
Vibration Isolators —This accessory
shall reduce transmission of noise and
vibration to building structures,
equipment, and adjacent spaces.
Packages shall be available in either
neoprene-in shear or spring-flex types in
floor or suspended mountings.
refrigeration circuits. Each refrigeration
circuit is controlled by a factory installed
thermal expansion valve.
Evaporator Coil
Configured aluminum fin surface shall
be mechanically bonded to 3/8” (10 mm)
internally enhanced copper tubing and
factory pressure and leak tested at 375
psig (2,586 kPa). Coil is arranged for
draw-thru airflow and shall provide
condensate drain pan constructed of
PVC plastic and provide external
connections on either side of the unit.
Accessories
Electric Heaters —Approved electric
heat modules shall be available for
installation directly on fan discharge.
Electric heaters shall be available in a
wide range of capacities with one or
two-stage control, single-point electric
power connection and terminal strip
connections. Electric heater elements
shall be constructed on heavy-duty
nickel chromium elements internally
wye connected on 480 volt, three phase.
Each 480 volt heater shall have
Oversized Motors — Field installed
oversized motors shall be available for
high static pressure applications.
Control Options
Standard IndoorThermostats —Two
stage heating and cooling operation or
one stage heating and cooling
thermostats shall be available in either
manual or automatic changeover.
Programmable Electronic Night Setback
Thermostat —The option shall provide
heating setback and cooling setup with
7-day programming capability.
automatic line break high limit controls.
SS-PRC003-EN
77
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Literature Order Number
File No.
SS-PRC003-EN
PL-UN-SS-PRC003-EN-12-00
TheTrane Company
An American Standard Company
Supersedes
SS-PRC003-EN 07-00
Inland - LaCrosse
Stocking Location
For more information contact your
local office or e-mail us at
SinceTheTrane Company has a policy of continuous product and product data improvement, it reserves the right
to change design and specifications without notice.
Download from Www.Somanuals.com. All Manuals Search And Download.
|