Trane Blower BCHC User Manual

Installation, Operation, and  
Maintenance  
Blower Coil Air Handler  
Air Terminal Devices - 400 to 3000 cfm  
Models BCHC and BCVC  
AO” and later design sequence  
BCXC-SVX01B-EN  
April 2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warnings, Cautions and Notices  
ƽ WARNING  
Hazard of Explosion and Deadly Gases!  
Never solder, braze or weld on refrigerant lines or any unit components that are above  
atmospheric pressure or where refrigerant may be present. Always remove refrigerant by  
following the guidelines established by the EPA Federal Clean Air Act or other state or local  
codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to  
atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under  
pressure may become combustible in the presence of an ignition source leading to an explosion.  
Excessive heat from soldering, brazing or welding with refrigerant vapors present can form  
highly toxic gases and extremely corrosive acids. Failure to follow all proper safe refrigerant  
handling practices could result in death or serious injury.  
BCXC-SVX01B-EN  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
About This Manual  
Use this manual for commercial blower coil models BCHC and BCVC. This is the second version  
of this manual; this manual supercedes BCXB-SVX01A-EN. It provides specific installation,  
operation, and maintenance instructions for AO” and later design sequences.  
For previous design sequence information, contact your local Trane representative.  
Trademarks  
Trane, theTranelogo, Frostat, IntegratedComfort,Rover, Tracer, andTracerSummitaretrademarks  
of Trane in the United States and other countries. All trademarks referenced in this document are  
the trademarks of their respective owners.  
4
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
BCXC-SVX01B-EN  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
6
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model Number Description  
Following isacompletedescriptionof  
the blower coil model number. Each  
digit in the model number has a  
corresponding code that identifies  
specific unit options.  
Digit 14 — Unit Coil #1*  
Digit 16 — Motor Horsepower  
Note: Allcoilsarehydronicunlessstated  
0
1
2
3
=
=
=
=
none  
4
5
6
7
=
=
=
=
1 hp  
otherwise.  
1/3 hp  
1/2 hp  
3/4 hp  
1-1/2 hp  
2 hp  
0
A
L
=
=
=
none  
1-row preheat  
2-row hydronic high-capacity  
preheat  
4-row hydronic  
6-row hydronic  
4-row hydronic, autochangeover  
6-row hydronic, autochangeover  
4-row hydronic high-capacity  
6-row hydronic high-capacity  
4-row hydronic high-capacity,  
autochangeover  
3 hp  
Digits 1, 2, 3, 4 — Unit Model  
BCHC= horizontal blower coil  
BCVC= vertical blower coil  
Digit 17 — Motor Drives  
F
G
J
K
M
N
R
=
=
=
=
=
=
=
0
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
none  
A
B
C
D
E
F
390–552 rpm / 60 Hz  
478–678 rpm / 60 Hz  
540–765 rpm / 60 Hz  
619–878 rpm / 60 Hz  
727–1029 rpm / 60 Hz  
879–1245 rpm / 60 Hz  
1000–1417 rpm / 60 Hz  
1200–1700 rpm / 60 Hz  
1313–1859 rpm / 60 Hz  
1615–2288 rpm / 60 Hz  
678–877 rpm / 60 Hz  
765–990 rpm / 60 Hz  
878–1136 rpm / 60 Hz  
1029–1332 rpm / 60 Hz  
1245–1611 rpm / 60 Hz  
1174–1519 rpm / 50 Hz  
Digits 5, 6, 7 — Unit Size  
012  
018  
024  
036  
054  
072  
090  
Digit 8 — Unit Voltage  
T
1
2
3
4
5
6
=
=
=
=
=
=
=
6-row hydronic high-capacity,  
autochangeover  
3-row DX, 3/16” distributor  
(0.032)  
4-row DX, 3/16” distributor  
(0.032)  
6-row DX, 3/16” distributor  
(0.032)  
3-row DX, 3/16” distributor  
(0.049)  
4-row DX, 3/16” distributor  
(0.049)  
6-row DX, 3/16” distributor  
(0.049)  
G
H
J
K
L
M
N
P
R
T
A
B
C
D
E
=
=
=
=
=
=
=
115/60/1  
208/60/1  
230/60/1  
277/60/1  
208/60/3  
230/60/3  
460/60/3  
H
J
=
=
=
=
=
=
=
575/60/3  
220/50/1  
240/50/1  
380/50/3  
415/50/3  
190/50/3  
K
L
M
N
P
F
G
two-speed,  
115/60/1  
Digit 18 — Electric Heat Stages  
0
=
no motor, ctrls, elec ht.  
0
1
2
=
=
=
none  
1-stage  
2-stage  
Digit 9 —Insulation Type  
Digit 15 — Unit Coil #2*  
1
2
=
=
1” matte-faced  
1” foil-faced  
Digits 19, 20, 21 — Electric Heat  
Note: Allcoilsarehydronicunlessstated  
otherwise.  
Digits 10, 11 — Design Sequence  
A0  
000 = none  
100 = 10.0 kW  
0
A
L
=
=
=
none  
010 = 1.0 kW  
015 = 1.5 kW  
020 = 2.0 kW  
025 = 2.5 kW  
030 = 3.0 kW  
035 = 3.5 kW  
040 = 4.0 kW  
045 = 4.5 kW  
050 = 5.0 kW  
055 = 5.5 kW  
060 = 6.0 kW  
065 = 6.5 kW  
070 = 7.0 kW  
075 = 7.5 kW  
080 = 8.0 kW  
090 = 9.0 kW  
110  
120  
11.0 kW  
12.0 kW  
=
=
1-row reheat  
2-row hydronic high-capacity  
reheat  
4-row hydronic  
6-row hydronic  
2-row hydronic, autochangeover  
4-row hydronic, autochangeover  
6-row hydronic, autochangeover  
4-row hydronic high-capacity  
6-row hydronic high-capacity  
2-row hydronic high-capacity,  
autochangeover  
Digit 12 — Motor, Drive, and  
Control Box Location  
130 = 13.0 kW  
140 = 14.0 kW  
150 = 15.0 kW  
160 = 16.0 kW  
170 = 17.0 kW  
180 = 18.0 kW  
190 = 19.0 kW  
200 = 20.0 kW  
210 = 21.0 kW  
220 = 22.0 kW  
240 = 24.0 kW  
260 = 26.0 kW  
280 = 28.0 kW  
300 = 30.0 kW  
F
=
=
=
=
=
=
=
=
A
=
same side as coil connections,  
horizontal or counterswirl only  
opposite side from coil  
connections, horizontal or  
counterswirl only  
G
H
J
B
=
K
M
N
P
C
D
=
=
same side as coil connections,  
pre-swirl only  
opposite side from coil  
connections, pre-swirl only  
right-hand access  
R
T
1
2
3
4
5
6
=
=
=
=
=
=
=
=
4-row hydronic high-capacity,  
autochangeover  
6-row hydronic high-capacity,  
autochangeover  
3-row DX, 3/16” distributor  
(0.032)  
4-row DX, 3/16” distributor  
(0.032)  
6-row DX, 3/16” distributor  
(0.032)  
3-row DX, 3/16” distributor  
(0.049)  
4-row DX, 3/16” distributor  
(0.049)  
6-row DX, 3/16” distributor  
(0.049)  
R
L
=
=
left-hand access  
Digit 13 — Drain Pan Type, Coil  
& Drain Connection Side  
0
1
=
=
none  
Digit 22 — Electric Heat Controls  
polymer drain pan & right-hand  
connections  
0
A
B
=
=
=
none  
2
3
4
=
=
=
polymer drain pan & left-hand  
connections  
stainless steel drain pan & right-  
hand connections  
stainless steel drain pan & left-  
hand connections  
24 volt magnetic contactors  
24 volt mercury contactors  
Digit 23 — Electric Heat Options  
0
A
B
=
=
=
none  
electric heat with heater fuse  
electric heat interlocking non-  
fused disconnect  
A & B  
C
=
BCXC-SVX01B-EN  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Model Number Description  
Digit 29 — Unit Coil #1 Piping  
Package  
Digit 34 — Mixing Box Damper  
Actuator  
Digit 24 — Filters  
0
A
B
=
=
=
none  
1” throwaway  
2” pleated throwaway  
0
1
2
=
=
=
none  
Note: The back damper is the control  
damper when actuators are  
ordered. The back damper is n.c.  
(normallyclosed)orn.o.(normally  
open) as selected.  
basic piping package  
deluxe piping package  
Digit 25 — Accessory Section  
Digit 30 — Unit Coil #2 Control  
Valve  
0
=
=
=
=
=
=
=
=
=
=
=
none  
A
B
C
D
E
F
G
H
J
mixing box only  
angle filter box  
angle filter/mixing box  
top access filter box  
bottom access filter  
A & D  
A & E  
steam coil  
A & H  
B & H  
0
1
2
3
4
5
6
7
=
=
=
=
=
=
=
=
none  
0
=
=
=
=
=
=
=
=
=
=
none  
2-position, n.o., ship loose  
modulating, n.c.  
A
B
C
D
E
F
2-way, 2-position, n.c.  
2-way, 2-position, n.o.  
3-way, 2-position, n.c.  
3-way, 2-position, n.o.  
2-way modulating  
modulating, n.o.  
modulating, ship loose  
field-supplied 2-position, n.o.  
field-supplied 2-position, n.c.  
field-supplied modulating  
L
=
=
=
=
=
C & H  
D & H  
E & H  
A, D, & H  
A, E, & H  
M
N
P
3-way modulating  
G
H
J
field-supplied valve, 2-pos., n.c.  
field-supplied valve, 2-pos., n.o.  
field-supplied modulating valve  
Digit 35 — Factory Mounted  
Control Options  
K
R
Digit 31 — Unit Coil #2 Control  
Valve Cv  
0
=
=
=
=
=
=
none  
fan status  
condensate overflow  
low limit  
A & C  
A & D  
Digit 26 — Control Type  
A
C
D
F
0
1
2
3
4
=
=
=
=
=
no controls (4 x 4 junction box)  
control interface  
Tracer™ ZN010  
0
=
=
=
=
=
=
none  
A
B
C
D
E
3.3 Cv, 1/2” valve & pipe  
3.3 Cv, 1/2” valve & 3/4” pipe  
3.8 Cv, 1/2” valve & 3/4” pipe  
6.6 Cv, 1” valve & pipe  
7.4 Cv, 1” modulating valve &  
pipe  
K
N
=
=
C & D  
A, C, & D  
Tracer ZN510  
G
Tracer ZN520  
Digit 27 — Unit Coil #1 Control  
Valve  
Digit 36 — Control Options 2  
0
A
B
C
=
=
=
=
none  
F
=
8.3 Cv, 1-1/4” modulating valve &  
pipe  
0
=
=
=
=
=
=
=
=
=
=
none  
outside air sensor, field-mounted  
discharge air sensor  
A & B  
A
B
C
D
E
F
2-way, 2-position, n.c.  
2-way, 2-position, n.o.  
3-way, 2-position, n.c.  
3-way, 2-position, n.o.  
2-way modulating  
G
H
J
=
=
=
3.5 Cv, 1/2” valve & pipe  
4.4 Cv, 1/2” valve & pipe  
7.0 Cv, 3-way valve  
OR 6.0 Cv, 2-way valve, 1” valve  
& pipe  
Digit 37 — Control Options 3  
0
A
=
=
none  
3-way modulating  
dehumidification with  
communicated value  
dehumidification with local  
humidity sensor  
K
L
M
=
=
=
8.0 Cv, 1” valve & pipe  
7.4 Cv, 1” 2-position valve & pipe  
8.3 Cv, 1-1/4” 2-position valve &  
pipe  
G
H
J
field-supplied valve, 2-pos., n.c.  
field-supplied valve, 2-pos., n.o.  
field-supplied modulating valve  
B
=
Digit 28 — Unit Coil #1 Control  
Valve Cv  
Digit 38 — Zone Sensors  
0
1
Q
R
T
=
=
=
=
1.3 Cv, 1/2” valve, 3/4” pipe  
1.8 Cv, 1/2” valve, 3/4” pipe  
2.3 Cv, 1/2” valve, 3/4” pipe  
2.7 Cv, 1/2” valve, 3/4” pipe  
=
=
none  
0
=
=
=
=
=
=
none  
off/auto, setpoint knob, on/cancel,  
COMM  
U
A
B
C
D
E
3.3 Cv, 1/2” valve & pipe  
3.3 Cv, 1/2” valve & 3/4” pipe  
3.8 Cv, 1/2” valve & 3/4” pipe  
6.6 Cv, 1” valve & pipe  
7.4 Cv, 1” modulating valve &  
pipe  
2
3
4
=
=
=
off/auto/high/low, setpoint knob,  
on/cancel, COMM  
wall mtd. zone sensor (set point,  
occ, COMM)  
wall mtd. zone sensor (occ,  
COMM)  
wall mtd. zone temp sensor  
digital zone sensor (O, A, H, L; SP;  
OCC; COMM)  
digital zone sensor (CPS; OCC;  
COMM)  
wireless zone sensor (setpoint  
only)  
Digit 32 — Unit Coil #2 Piping  
Package  
0
1
2
=
=
=
none  
basic piping package  
deluxe piping package  
F
=
8.3 Cv, 1-1/4” modulating valve &  
pipe  
5
A
=
=
Digit 33 — Remote Heat Options  
G
H
J
=
=
=
3.5 Cv, 1/2” valve & pipe  
4.4 Cv, 1/2” valve & pipe  
7.0 Cv, 3-way valve  
OR 6.0 Cv, 2-way valve, 1” valve  
& pipe  
0
1
2
=
=
=
none  
staged electric heat  
2-position hot water, n.c.  
B
C
=
=
K
L
M
=
=
=
8.0 Cv, 1” valve & pipe  
7.4 Cv, 1” 2-position valve & pipe  
8.3 Cv, 1-1/4” 2-position valve &  
pipe  
Digit 39 — Extra Belt  
0
1
=
=
none  
ship loose extra belt  
Q
R
T
=
=
=
=
1.3 Cv, 1/2” valve, 3/4” pipe  
1.8 Cv, 1/2” valve, 3/4” pipe  
2.3 Cv, 1/2” valve, 3/4” pipe  
2.7 Cv, 1/2” valve, 3/4” pipe  
Digit 40 — Extra Filter  
0
1
=
=
none  
U
ship loose extra 1” throwaway  
filter  
2
=
ship loose extra 2” pleated  
throwaway  
8
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
Blower Coil General Information  
Blower coil units are draw-thru air handlers for cooling load conditions of 400–3000 cfm. Units are  
available in either horizontal (model BCHC) or vertical (model BCVC) configurations. Horizontal  
units are typically ceiling suspended via threaded rods. Knockouts are provided in all four corners  
to pass the rods through the unit. Horizontal units can also be floor mounted. Vertical units are  
typically floor mounted. They have a side inlet for easy duct connection, and do not require a field  
fabricated inlet plenum. Vertical units ship in two pieces and can be set up in either a pre-swirl or  
counter-swirl configuration.  
Basic unit components consist of a water coil, condensate drain pan, filter, duct collars, one fan  
wheel, and motor with drive. See Figure 1. Drive components consist of sheaves, belt, and motor.  
The coil, drain pan, and motor/drive assembly can easily be field-converted from right hand to left  
hand configurations or vice versa.  
Figure 1. Blower coil air handler unit components (model BCHC, horizontal unit)  
Main coil with copper  
tubes and enhanced  
aluminum fins in 2-, 4-,  
or 6-row hydronic or 3-,  
4-, or 6-row DX  
Internal filter frame  
accommodates 1- or  
2-inch filters  
Unit sizes 12, 18, 24, 36,  
54, 72, and 90 MBh  
Galvanized steel  
Knockouts in all four  
cabinet in 14-, 18-, 22-,  
and 28-inch heights  
corners for hanger rods  
Angle filter option and/or  
mixing box accommodates  
2-inch filters  
Forward curved fan  
Internal 1- or  
2-row auxiliary  
coil in preheat  
1/3 to 3 hp motor  
with drive  
selections from  
390 to 1611 rpm  
Control options  
Main and auxiliary  
drain connections on  
same side of unit  
include control  
interface, Tracer™  
ZN010, ZN510, or  
ZN520  
or reheat position  
Two, four, or six-row main coils are available for either hydronic cooling or heating. Three, four, or  
six-row direct expansion (DX) coils are also available for cooling. An optional one, two, four, or six-  
row heating coil is available factory-installed in either the preheat or reheat position. Also, a one-  
row preheat steam is available.  
All units have an internal flat filter frame for one or two-inch filters. An optional angle filter box (two  
inch only), mixing box, bottom/top filter access box, or combination angle filter mixing box is  
available.  
In addition, all units are available with either a basic or deluxe piping package option that includes  
a variety of control valve sizes in two or three-way configurations. The basic package consists of  
BCXC-SVX01B-EN  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
General Information  
a control valve and stop (ball) valves. The deluxe package consists of a control valve, a stop (ball)  
valve, a circuit setter, and strainer.  
Belt-drive motors range from 1/3 to 3 horsepower in a wide range of voltages. All motors have  
internal thermal and current overloads, permanently sealed ball bearings, and a resilient cradle  
mount to reduce noise and vibration transmission.  
Variable pitch sheave drive kit options help make it possible to more accurately select design static  
pressure. For additional flexibility, 115 volt single phase, two speed motors are optional.  
Note: Sheaves are factory set in the middle of the range. Field adjustment of sheaves, motor, and  
belt are required to arrive at desired rpm. Referto the original sales order and Table 35, p. 68  
for drive information.  
Units may have no controls (4 x 4 junction box) or any of four different control types:  
1. control interface  
2. Tracer™ ZN010  
3. Tracer ZN510  
4. Tracer ZN520  
All control options are factory-installed and tested.  
10  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pre-Installation  
Receiving and Handling  
Blower coil units are packaged for easy handling and storage on the job site. Upon delivery, inspect  
all components for possible shipping damage. See the “Receiving Checklist” section (below) for  
detailed instructions. Trane recommends leaving units and accessories in their shipping packages/  
skids for protection and handling ease until installation.  
Shipping Package  
Blower coil air handlers ship assembled on skids with protective coverings over the coil and  
discharge openings.  
Ship-Separate Accessories  
Field-installed sensors ship separately inside the units main control panel. Piping packages,  
mixing boxes, ship separately packaged on the same skid as the unit.  
Receiving Checklist  
Complete the following checklist immediately after receiving unit shipment to detect possible  
shipping damage.  
Inspectindividualcartonsbeforeaccepting. Checkforrattles, bentcartoncorners, orothervisible  
indications of shipping damage.  
If a unit appears damaged, inspect it immediately before accepting the shipment. Manually  
rotate the fan wheel to ensure it turns freely. Make specific notations concerning the damage on  
the freight bill. Do not refuse delivery.  
Inspect the unit for concealed damage before it is stored and as soon as possible after delivery.  
Report concealed damage to the freight line within the allotted time after delivery. Check with the  
carrier for their allotted time to submit a claim.  
Do not move damaged material from the receiving location. It is the receivers responsibility to  
provide reasonable evidence that concealed damage did not occur after delivery.  
Do not continue unpacking the shipment if it appears damaged. Retain all internal packing,  
cartons, and crate. Take photos of damaged material if possible.  
Notify the carriers terminal of the damage immediately by phone and mail. Request an  
immediate joint inspection of the damage by the carrier and consignee.  
Notify your Trane representative of the damage and arrange for repair. Have the carrier inspect  
the damage before making any repairs to the unit.  
Compare the electrical data on the unit nameplate with the ordering and shipping information  
to verify the correct unit is received.  
Jobsite Storage Recommendations  
This unit is intended for indoor use only. To protect the unit from damage due to the elements and  
prevent it from possibly becoming a contaminant source for IAQ problems, store the unit indoors.  
If indoor storage is not possible, the Trane Company makes the following provisions for outdoor  
storage:  
1. Place the unit(s) on a dry surface or raised off the ground to assure adequate air circulation  
beneath unit and to assure that no portion of the unit contacts standing water at any time.  
2. Cover the entire unit with a canvas tarp only. Do not use clear, black, or plastic tarps as they  
may cause excessive moisture condensation and equipment damage.  
Note: Wet interior unit insulation can become an amplification site for microbial growth (mold),  
which may cause odors and health-related indoor air quality problems. If there is visible  
evidence of microbial growth (mold) on the interior insulation, remove and replace the  
insulation prior to operating the system.  
BCXC-SVX01B-EN  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Pre-Installation  
Installation Preparation  
Before installing the unit, perform the following procedures to ensure proper unit operation.  
1. Verify the floor or foundation is level. Shim or repair as necessary. To ensure proper unit  
operation, install the unit level (zero tolerance) in both horizontal axes. Failure to level the unit  
properly can result in condensate management problems, such as standing water inside the  
unit. Standing water and wet surfaces inside units can result in microbial growth (mold) in the  
drain pan that may cause unpleasant odors and serious health-related indoor air quality  
problem.  
2. Allow adequate service and code clearances as recommended in the “Service Access” section  
(below). Position the unit and skid assembly in its final location. Test lift the unit to determine  
exact unit balance and stability before hoisting it to the installation location.  
Service Access  
See Table 1, below, and Figure 2, p. 13 for recommended service and code clearances.  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects before servicing. Follow proper  
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to  
disconnect power before servicing could result in death or serious injury.  
Table 1. Service requirements, in. (cm)  
Unit size  
Dimension A  
20 (50.8)  
12  
18  
24  
36  
54  
72  
90  
25 (63.5)  
25 (63.5)  
37 (94.0)  
37 (94.0)  
45 (114.3)  
45 (114.3)  
12  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Pre-Installation  
Figure 2. Top view of blower coil unit showing recommended service and code clearances  
3
3
Rigging and Handling  
Before preparing the unit for lifting, estimate the approximate center of gravity for lifting safety.  
Because of placement of internal components, the unit weight may be unevenly distributed, with  
more weight in the coil area. Approximate unit weights are given in “Dimensions and Weights,”  
p. 15. Also, you may reference the unit weight on the unit nameplate.  
Before hoisting the unit into position, use a proper rigging method such as straps, slings, or  
spreader bars for protection and safety. Always test-lift the unit to determine the exact unit balance  
and stability before hoisting it to the installation location.  
ƽ WARNING  
Improper Unit Lift!  
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid  
dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could  
result in death or serious injury or possible equipment or property-only damage.  
Unit Handling Procedure  
1. Position rigging sling under wood skid using spreader bars to avoid unit damage.  
2. Use a forklift with caution to prevent unit damage. The fork length must be at least 68 inches  
long to safely fork the unit from front or back.  
3. The unit center of gravity will fall within the center of gravity block at various locations  
depending on unit options.  
4. See unit nameplate for unit weight.  
Unit Location Recommendations  
When selecting and preparing the unit installation location, consider the following  
recommendations.  
BCXC-SVX01B-EN  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Pre-Installation  
1. Consider the unit weight. Reference the unit weight on the unit nameplate or in “Dimensions  
2. Allow sufficient space for the recommended clearances, access panel removal, and  
maintenance access. Refer to Figure 2, p. 13.  
3. The installer must provide threaded suspension rods for ceiling mounted units. All units must  
be installed level.  
4. Coil piping and condensate drain requirements must be considered.  
Allow room for proper ductwork and electrical connections. Support all piping and ductwork  
independently of unit to prevent excess noise and vibration.  
Skid Removal  
The unit ships on skids that provide forklift locations from the front or rear. The skid allows easy  
maneuverability of the unit during storage and transportation. Remove the skids before placing the  
unit in its permanent location.  
Remove the skids using a forklift or jack. Lift one end of the unit off of the skids. Vibration isolators  
for external isolation are field supplied.  
Pre-Installation Checklist  
Complete the following checklist before beginning unit installation.  
Verify the unit size and tagging with the unit nameplate.  
Make certain the floor or foundation is level, solid, and sufficient to support the unit and  
accessory weights. Refer to “Dimensions and Weights,” p. 15. Level or repair the floor before  
positioning the unit if necessary.  
Allow minimum recommended clearances for routine maintenance and service. Refer to unit  
submittals for dimensions.  
Allow one and one half fan diameters above the unit for the discharge ductwork.  
14  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Dimensions and Weights  
Horizontal Blower Coil  
*NOTE: ON UNITS WITHOUT A  
BOTTOM FILTER ACCESS SECTION  
top view  
M
M
M
PP  
Q
1.5  
J
J
front view  
Table 2. Horizontal blower coil dimensions (in.) and weights (lb)  
Basic  
unit  
weight  
Unit  
size  
G
G
J
J
H
W
L
A
B
C
D
E
F
(RH) (LH) (RH) (LH)  
K
M
P
Q
12 14.00 24.00 39.75 12.09 18.00 10.56 7.09 0.55 3.00 11.42 13.42 9.42 11.42 4.20  
8.46  
9.00  
5.75  
5.75  
5.75  
70.40  
76.10  
98.90  
18 14.00 28.00 39.75 12.09 22.00 10.56 7.09 0.55 3.00 11.42 13.42 9.42 11.42 4.20 10.46 9.00  
24 18.00 28.00 44.00 16.09 22.00 13.56 12.56 1.30 3.00 11.42 13.42 9.42 11.42 6.20 7.72 9.00  
36 18.00 40.00 44.00 16.09 34.00 13.56 12.56 1.30 3.00 11.42 13.42 9.42 11.42 6.20 13.72 9.00  
5.75 116.10  
54 22.00 40.00 49.00 20.09 34.00 13.56 12.56 0.72 3.00 11.42 13.42 9.42 11.42 7.43 13.72 11.00 7.27 138.90  
72 22.00 48.00 49.00 20.09 40.00 13.56 12.56 0.72 4.00 11.42 13.42 9.42 11.42 7.43 17.72 11.00 7.27 152.20  
90 28.00 48.00 52.00 26.09 40.00 13.56 12.56 1.66 4.00 12.79 14.79 10.79 12.79 8.24 17.72 11.25 11.64 174.80  
BCXC-SVX01B-EN  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Dimensions and Weights  
Vertical Blower Coil  
*NOTE; ON UNITSWITHOUT A  
TOP FILTER ACCESS SECTION  
vertical counter swirl  
top view  
configuration  
vertical preswirl  
configuration  
M
M
6.00  
P
Q
J
front view  
Table 3. Vertical blower coil dimensions (in.) and weights (lb)  
Basic  
unit  
weight  
Unit  
size  
G
G
J
J
H
W
L
A
B
C
D
E
F
(RH) (LH) (RH) (LH)  
K
M
N
P
Q
R
24 63.50 28.00 44.00 16.09 22.00 13.56 12.56 1.30 3.00 11.42 13.42 9.42 11.42 6.20 5.50 18.00 9.00 5.50 28.00 150.30  
36 63.50 40.00 44.00 16.09 34.00 13.56 12.56 1.30 3.00 11.42 13.42 9.42 11.42 6.20 5.50 18.00 9.00 5.50 28.00 180.40  
54 72.50 40.00 47.00 20.09 34.00 13.56 12.56 0.72 3.00 11.42 13.42 9.42 11.42 4.21 10.43 22.00 11.00 7.27 30.00 206.40  
72 72.50 48.00 47.00 20.09 40.00 13.56 12.56 0.72 4.00 11.42 13.42 9.42 11.42 4.18 10.43 22.00 11.00 7.27 30.00 228.20  
90 81.50 48.00 50.00 26.09 40.00 13.56 12.56 1.66 4.00 12.79 14.79 10.79 12.79 4.81 15.61 28.00 11.25 11.64 30.00 258.40  
16  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Dimensions and Weights  
Angle Filter and Mixing Box  
combination angle filter  
& mixing box  
mixing box  
angle filter box  
Table 4. Angle filter and mixing box dimensions (in.) and weights (lb)  
Unit size  
H
L
W
A
B
Weight  
36.0  
12  
16  
24  
36  
54  
72  
90  
14.12  
14.12  
18.12  
18.12  
22.12  
22.00  
27.90  
22.00  
22.00  
19.50  
24.50  
23.50  
23.50  
27.56  
24.11  
28.11  
28.11  
40.11  
40.11  
48.00  
48.00  
7.06  
7.06  
7.06  
7.06  
12.81  
12.81  
12.85  
15.56  
19.56  
19.56  
31.56  
31.56  
32.56  
31.56  
41.0  
43.0  
56.0  
72.0  
72.5  
84.1  
BCXC-SVX01B-EN  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Dimensions and Weights  
Bottom or Top Access Filter Box  
7.17  
.97  
FILTER  
AIR FLOW  
FILTER  
AIR FLOW  
top view  
FILTER ACCESS PANEL  
NOTES;  
right side view  
1. DIMENSIONS ARE IN INCHES.  
2. ROTATE 180° FOR TOP ACCESS.  
3. SECTIONS SHIPS ATTACHED TO THE UNIT.  
Table 5. Bottom or top access filter box dimensions (in.) and weights (lb)  
Unit size  
H
W
A
B
C
D
Weight  
15  
12  
18  
24  
36  
54  
72  
90  
14.00  
14.00  
18.00  
18.00  
22.00  
22.00  
28.00  
24.00  
28.00  
28.00  
40.00  
40.00  
48.00  
48.00  
9.98  
2.01  
2.01  
1.89  
1.89  
1.89  
1.89  
1.89  
18.23  
21.98  
23.23  
33.73  
33.73  
42.73  
41.23  
2.88  
3.01  
2.38  
3.13  
3.13  
2.63  
3.38  
9.98  
17  
14.23  
14.23  
18.23  
18.23  
23.23  
18  
25  
28  
32  
37  
18  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Dimensions and Weights  
Electric Heat  
& 90  
top view  
D
front view  
right side view  
& 90  
& 90 ARE HINGED  
ELECTRIC HEAT MAY NEED FIELD-SUPPLIED  
EXTERNALLY-WRAPPED INSULATION IF THE UNIT  
IS INSTALLED IN AN UNCONDITIONED SPACE OR  
IF SWEATING IS AN ISSUE.  
Table 6. Electric heat dimensions (in.) and weights (lb)  
Unit size  
H
W
A
B
C
D
E
Weight  
10.0  
12  
18  
24  
36  
54  
72  
90  
14.06  
14.06  
18.06  
18.06  
18.06  
18.06  
18.06  
17.88  
19.88  
21.25  
27.25  
27.25  
27.25  
27.25  
8.13  
6.79  
10.50  
10.50  
13.50  
13.50  
13.50  
13.50  
13.50  
7.75  
0.03  
0.03  
0.80  
0.80  
0.22  
0.22  
1.16  
10.13  
7.63  
8.79  
7.75  
10.8  
6.29  
12.63  
12.63  
12.63  
12.63  
12.63  
11.3  
13.63  
13.63  
13.63  
13.63  
12.29  
11.67  
11.67  
11.67  
12.8  
16.0  
17.4  
19.2  
BCXC-SVX01B-EN  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Dimensions and Weights  
Steam Coil  
ACCESS PANEL  
C
B
C
0.97  
NOTES:  
1. FILTER ACCESS & ACCESS PANEL LOCATED  
ON BOTH SIDES.  
2. WEIGHT INCLUDES CABINET WITH AVERAGE FILTER,  
BUT DOES NOT INCLUDE CIOL WEIGHT.  
SEE GENERAL DATA SECTION FOR COIL WEIGHTS.  
AIRFLOW  
H
A
0.97  
W
21.00  
FILTER ACCESS  
Table 7. Steam coil box dimensions (in.) and weights (lb)  
Coil Connections, NPT  
Unit size  
H
W
A
B
C
Weight  
34  
Supply  
Return  
12  
18  
24  
36  
54  
72  
90  
14.00  
14.00  
18.00  
18.00  
22.00  
22.00  
28.00  
24.00  
28.00  
28.00  
40.00  
40.00  
48.00  
48.00  
12.06  
12.06  
16.06  
16.06  
20.06  
20.06  
26.06  
18.04  
22.04  
22.04  
34.04  
34.04  
42.04  
40.04  
2.98  
2.98  
2.98  
2.98  
2.98  
2.98  
3.98  
1
1
3/4  
3/4  
1
37  
40  
1-1/2  
1-1/2  
2
48  
1
50  
1
56  
2
1
63  
2.5  
1-1/4  
20  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Dimensions and Weights  
Coil Connections  
Table 8. Hydronic coil connection sizes, OD (in.)  
Standard capacity  
High capacity  
Unit size  
1-row  
5/8  
4-row  
6-row  
2-row  
5/8  
4-row  
7/8  
6-row  
7/8  
12  
18  
24  
36  
54  
72  
90  
-
-
5/8  
-
-
5/8  
7/8  
7/8  
5/8  
-
-
7/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
7/8  
-
-
7/8  
1-1/8  
1-1/8  
1-1/8  
1-3/8  
1-3/8  
1-5/8  
1-3/8  
1-3/8  
1-5/8  
1-1/8  
1-1/8  
1-1/8  
Table 9. DX coil connection sizes, OD (in.)  
3- & 4-row  
6-row  
Unit size  
Suction  
5/8  
Liquid  
5/8  
Suction  
5/8  
Liquid  
5/8  
12  
18  
24  
36  
54  
72  
90  
5/8  
5/8  
5/8  
5/8  
5/8  
5/8  
7/8  
5/8  
7/8  
5/8  
7/8  
5/8  
1-1/8  
1-1/8  
1-3/8  
7/8  
1-1/8  
1-1/8  
1-1/8  
7/8  
7/8  
7/8  
7/8  
7/8  
Table 10. Steam coil connection sizes, female connection, NPT (in.)  
Unit size  
Supply  
Return  
12  
18  
24  
36  
54  
72  
90  
1
1
3/4  
3/4  
1
1-1/2  
1-1/2  
2
1
1
2
1
2-1/2  
1-1/4  
BCXC-SVX01B-EN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Dimensions and Weights  
Piping Packages  
Basic Piping  
Two-way, 1/2” and 1” valve basic piping package  
B
A
B
A
Two-way, 1-1/4” valve basic piping package  
A
B
AB  
E
B
A
Three-way, 1/2” and 1” valve basic piping package  
F
A
B
AB  
A
E
B
22  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Dimensions and Weights  
Deluxe Piping  
Two-way, 1/2” and 1” valve deluxe piping package  
D
B
A
C
Two-way 1-1/4” valve deluxe piping package  
D
A
B
AB  
E
C
BCXC-SVX01B-EN  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions and Weights  
Three-way, 1/2” and 1” valve deluxe piping package  
F
A
B
AB  
E
C
D
Table 11. Piping package dimensions (in.)  
Piping  
Nominal  
package  
tube size Actual size  
A
B
C
D
E
F
2-way  
1/2  
1
5/8  
1-1/8  
5/8  
12.025  
13.295  
12.088  
15.623  
13.370  
16.885  
2.650  
4.260  
2.097  
1.750  
3.690  
3.738  
12.625  
13.220  
12.688  
15.313  
13.210  
16.410  
5.650  
9.288  
4.497  
6.290  
9.060  
10.023  
N/A  
N/A  
3.020  
6.351  
6.701  
9.813  
3.052  
N/A  
3-way  
1/2  
3/4  
1
6.351  
6.701  
9.813  
10.520  
7/8  
1-1/8  
1-3/8  
1-1/4  
24  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Controls  
Installing Wall Mounted Controls  
Wall mounted zone sensors ship taped to the control box. Refer to Figure 3 for zone sensor  
dimensions.  
Position the controller on an inside wall three to five feet above the floor and at least 18 inches from  
the nearest outside wall. Installing the controller at a lower height may give the advantage of  
monitoring the temperature closer to the zone, but it also exposes the controller to airflow  
obstructions. Ensure that air flows freely over the controller.  
Before beginning installation, follow the wiring instructions below. Also, refer to the unit wiring  
schematic for specific wiring details and point connections.  
Wiring Instructions  
Avoid mounting the controller in an area subject to the following conditions:  
Dead spots, such as behind doors or in corners that do not allow free air circulation.  
Air drafts from stairwells, outside doors, or unsectioned hollow walls.  
Radiant heat from the sun, fireplaces, appliances, etc.  
Airflow from adjacent zones or other units.  
Unheated or uncooled spaces behind the controller, such as outside walls or unoccupied  
spaces.  
Concealed pipes, air ducts, or chimneys in partition spaces behind the controller.  
Zone Sensor Installation  
Follow the procedure below to install the zone sensor module (see Figure 3).  
Figure 3. Wall-mounted zone sensor dimensions  
1. Note the position of the setpoint adjustment knob and gently pry the adjustment knob from the  
cover using the blade of a small screwdriver.  
2. Insert the screwdriver blade behind the cover at the top of the module and carefully pry the  
cover away from the base.  
3. To install the zone sensor module without a junction box (directly to the wall):  
a. Using the module base as a template, mark the rectangular cutout for the control wiring and  
module installation holes. Ensure the base is level.  
b. Set the base aside and make the cutout. Then, drill two 3/16” diameter holes approximately  
one-inch deep. Insert and fully seat the plastic anchors.  
c. Pull the control wires through the cutout and attach the module to the wall using the screws  
provided.  
4. To install the zone sensor module to a standard junction box:  
a. Level and install a 2” x 4” junction box (installer supplied) vertically on the wall.  
BCXC-SVX01B-EN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation Controls  
b. Pull the control wires through the cutout. Attach the module to the wall using the screws  
provided.  
5. Stripthe insulationonthe interconnection wiresback0.25inchandconnecttoTB1. Screwdown  
the terminal blocks.  
6. Replace the zone sensor cover and adjustment knob.  
If installing a Tracer™ ZN510 or ZN520 zone sensor, see Tracer Summit Communication Wiring,”  
p. 27 for more information.  
Communication Wiring  
Units with Tracer ZN510 or ZN520 only  
Note: Communication link wiring is a shielded, twisted pair of wire and must comply with  
applicable electrical codes.  
Follow these general guidelines when installing communication wiring on units with either a  
Tracer™ ZN510 or ZN520 controller:  
Maintain a maximum 5000 ft. aggregate run  
Install all communication wiring in accordance with the NEC and all local codes.  
Solder the conductors and insulate (tape) the joint sufficiently when splicing communication  
wire. Do not use wire nuts to make the splice.  
Do not pass communication wiring between buildings because the unit will assume different  
ground potentials.  
Do not run power in the same conduit or wire bundle with communication link wiring.  
Service Communication Wiring  
Establish service communication using Rover™ service software connected to the Tracer™ ZN  
controller using a twisted wire pair to one of the following connection points:  
Remote zone sensor module  
Connections on the board  
This allows the technician to view and edit the Tracer™ controller configuration and troubleshoot  
the unit.  
Note: Unit control options and field wiring practices may limit the controllers communication  
ability.  
Route interconnecting wiring from the Tracer™ controller to provide service communication at the  
wall-mounted zone sensor module. Install wiring by referencing the unit wiring diagram and  
Table 12, p. 29 for appropriate wire sizes. After wiring is complete, connect the communication  
cable (provided with the Rover™ service tool) to the telephone style RJ11 connection on the zone  
sensor module. Attach the other end of the cable to a computer running Trane Rover software to  
communicate.  
Zone Sensors Without Interconnecting Wiring  
Establish servicecommunication tothe TracerZNcontrollerbywiring directlytotheboard inside  
the control box. Refer to the unit-wiring diagram for appropriate communication terminals on the  
board.  
Once wiring is complete, Use Trane Roversoftwareto communicate to the Tracer™ ZN controller.  
Tracer Communications  
Tracer™ ZN controllers have Comm5 communication ports. Typically, a communication link is  
applied between unit controllers and a building automation system. Communication also is  
possible via Rover™, Tranes service tool.  
26  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation Controls  
Peer-to-peer communication across controllers is possible even when a building automation  
system is not present.You do not need to observe polarity for Comm5 communication links.  
The controller provides six 0.25-inch quick-connect terminals for the Comm5 communication link  
connections, as follows:  
Two terminals for communication to the board  
Two terminals for communication from the board to the next unit (daisy chain)  
Two terminals for a connection from the zone sensor back to the controller  
Each controller has its own unique address or I.D. number on a Neuron chip. Setting dip switches  
are not required on the Tracer™ controller.  
Tracer Summit Communication Wiring  
For Tracer™ ZN-controlled units that will interface with the Trane Tracer Summit® building  
management system, terminate the communication wiring in the control box at the designated  
terminals on the board. Reference the unit wiring diagram or submittals.  
Ground shields at each Tracer™ ZN controller, taping the opposite end of each shield to prevent  
any connection between the shield and anther ground. Refer to Trane publication CNT-SVX04A-EN,  
Tracer ZN.520 Unit Controller - Installation, Operation and Programming Guide, for the  
communication wiring diagram.  
Communication wire must conform to the following specification:  
Shielded twisted pair 18 AWG  
Capacitance 23 (21-25) picofarads (pF) per foot  
Listing/Rating – 300V 150C NEC 725-2 (b) Class 2 Type CL2P  
Trane Part No. 400-20-28 or equivalent, available through Trane BAS Buying Group Accessories  
catalog.  
BCXC-SVX01B-EN  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation Electrical  
Unit Wiring Diagrams  
Specific unit wiring diagrams are provided on the inside of the control panel door. Typical unit  
wiring diagrams are in “Wiring Diagrams,” p. 81. Use these diagrams for connections or trouble  
analysis.  
ƽ WARNING  
Grounding Required!  
Follow proper local and state electrical codes for requirements on grounding. Failure to follow  
code could result in death or serious injury.  
Supply Power Wiring  
Wiring must conform to NEC and all applicable code requirements.  
It is the installers responsibility to provide adequately-sized power wires and proper unit  
grounding.  
Bring supply wiring through provided equipment knockouts located at the power connection point  
on the unit. Equipment submittals should be referred to for the exact electrical access connection  
point. Connect the power wires to the power connection point provided.  
Connection to the installer-provided ground path must be made to the green wire or green  
grounding screw provided on each unit.  
Locate unit wiring diagrams on the inside of the control box cover. Refer to the unit-specific wiring  
diagrams for wiring, connection point, and fuse installation information. Refer to the unit  
nameplate for unit-specific electrical information, such as voltage, minimum circuit ampacity  
(MCA), and maximum fuse size (MFS).  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects before servicing. Follow proper  
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to  
disconnect power before servicing could result in death or serious injury.  
NOTICE  
Use copper conductors only!  
Unit terminals are not designed to accept other conductor types. Failure to use copper  
conductors could cause equipment damage.  
NOTICE  
Correct phase critical!  
Correct phase sequence is critical. If phase sequence of the incoming line voltage is not correct,  
it could cause motor damage.  
Electrical Connections  
Units have one of three different connection points, depending on the unit type and options.  
1. If the unit has no controls: power and ground are tucked inside of the handy box.  
2. If the unit has a control interface or Tracer™ ZN controller: power and ground are inside the  
control box. If the unit has a control interface or a Tracer controller, the power wires and ground  
wire are inside the control box connected to a non fused disconnect switch.  
28  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation Electrical  
3. If the unit has a electric heat: power and ground connections are inside the electric heat control  
box, connected to a non-fused disconnect switch or terminal block.  
Electrical Grounding Restrictions  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects before servicing. Follow proper  
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to  
disconnect power before servicing could result in death or serious injury.  
All sensor and input circuits are normally at or near ground (common) potential. When wiring  
sensors and other input devices to the Tracer™ ZN controller, avoid creating ground loops with  
grounded conductors external to the unit control circuit. Ground loops can affect the measurement  
accuracy of the controller.  
Note: Unit transformer IT1 provides power to the blower coil unit only and is not intended for field  
connections. Field connections to the transformer IT1 may cause immediate or premature  
unit component failure.  
All input/output circuits (except isolated relay contacts and optically-isolated inputs) assume a  
grounded source, either a ground wire at the supply transformer to control panel chassis, or an  
installer supplied ground.  
Note: Do not connect any sensor or input circuit to an external ground connection.  
The installer must provide interconnection wiring to connect wall mounted devices such as a zone  
sensor module. Refer to the unit wiring schematic for specific wiring details and point-to-point  
wiring connections. Dashed lines indicate field wiring on the unit wiring schematics. All  
interconnection wiring must conform to NEC Class 2 wiring requirements and any state and local  
requirements. Refer to Table 12 for the wire size range and maximum wiring distance for each  
device.  
Table 12. Zone sensor maximum wiring distances, ft (m)  
Wire size range  
Max. wiring distance  
16–22 AWG  
200 (60.96)  
Note: Do not bundle or run interconnection wiring in parallel with or in the same conduit with any  
high voltage wires (110V or greater). Exposure of interconnection wiring to high voltage  
wiring, inductive loads, or RF transmitters may cause radio frequency interference (RFI). In  
addition, improperseparationmaycauseelectricalnoiseproblems. Therefore, useshielded  
wire (Beldon 83559/83562 or equivalent) in applications that require a high degree of noise  
immunity. Connect the shield to the chassis ground and tape at the other end.  
Minimum Circuit Ampacity (MCA) and Maximum Fuse Size (MFS) Calculations  
for Units with Electric Heat  
Use these formulas to calculate the MCA and MFS.  
Heater amps = (heater kW x 1000)/heater voltage  
Note: Use 120V heater voltage for 115V units. Use 240V heater voltage for 230V units. Use 480V  
heater voltage for 460V units. Use 600V heater voltage for 575V units.  
MCA = 1.25 x (heater amps + all motor FLAs)  
MFS or HACR type circuit breaker = (2.25 x largest motor FLA) + second motor FLA + heater amps  
(if applicable)  
HACR (Heating, Air-Conditioning and Refrigeration) type circuit breakers are required in the branch  
circuit wiring for all units with electric heat.  
BCXC-SVX01B-EN  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation Electrical  
See Table 13 for electric heat kW and Table 14, p. 31 for motor FLAs.  
Select a standard fuse size or HACR type circuit breaker equal to the MCA.  
Use the next larger standard size if the MCA does not equal a standard size.  
Standard fuse sizes are: 15, 20, 25, 30, 35, 40, 45, 50, 60 amps  
Useful Formulas  
kW = (cfm x ΔT)/3145  
ΔT = (kW x 1000)/voltage  
Single phase amps = (kW x 1000)/voltage  
Three phase amps = (kW x 1000)/(voltage x 1.73)  
Electric heat MBh = (Heater kW) (3.413)  
Table 13. Available electric heat, min–max (kW)  
Unit size  
54  
Voltage  
115/60/1  
208/60/1  
230/60/1  
277/60/1  
208/60/3  
230/60/3  
460/60/3  
575/60/3  
220/50/1  
240/50/1  
380/50/3  
415/50/3  
190/50/3  
Notes:  
12  
18  
24  
36  
72  
90  
1–3  
1–4  
1–4  
1–4  
1–4  
1–4  
1.5–4  
2–4  
1–4  
1–4  
1–4  
1.5–4  
N/A  
1–3  
1–6  
1–6  
1–6  
1–6  
1–6  
1.5–5  
2–4  
1–6  
1–6  
1–5  
1.5–5  
N/A  
1–3  
1–8  
1–8  
1–8  
1–8  
1–8  
1–8  
1–8  
1–8  
1–8  
1–8  
1–8  
N/A  
1–3  
1–3  
1–3  
1–3  
1–8  
1–8  
1–8  
1–8  
1–8  
1–8  
1–8  
1–8  
1–11  
1–11  
1–11  
1–11  
1–11  
1–8  
1–11  
1–12  
1–12  
1–16  
1–16  
1–8  
1–11  
1–12  
1–12  
1–21  
1–21  
1–8  
1–11  
1–12  
1–12  
1–30  
1–30  
1–8  
1–8  
1–8  
1–8  
1–8  
1–11  
1–11  
N/A  
1–16  
1–16  
N/A  
1–20  
1–21  
N/A  
1–28  
1–30  
N/A  
1. Heaters are available in the following Kw increments: 1.0, 1.5, 2.0, 2.5, 3.0, 3.5, 4.0, 4.5, 5.0, 5.5,  
6.0, 6.5, 7.0, 7.5, 8.0, 9.0, 10.0, 11.0, 12.0, 13.0, 14.0, 15.0, 16.0, 17.0, 18.0,19.0, 20.0, 21.0,  
22.0, 24.0, 26.0, 28.0, 30.0.  
2. Magnetic contactors are standard. Mercury contactors are available on horizontal units only.  
3. Units with electric heat are available with or without door interlocking disconnect switch.  
4. Units with electric heat are available with or without line fuses.  
5. Units with electric heat must not be run below the minimum cfm listed in the general data section.  
6. Electric heat is balanced staging: 1 stage = 100%, 2 stages = 50%/50%  
7. Electric heat is not available on 190/50/3 units.  
8. For two-speed units not being controlled by the Tracer™ family of controls, a 0.2-second delay for  
speed switching needs to be incorporated into the control sequence.  
30  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation Electrical  
Table 14. Motor electrical data  
Voltage  
Voltage range  
rpm  
Rated hp  
1/3  
lb  
18  
21  
29  
29  
FLA  
5.8  
LRA  
22.8  
30.4  
58.4  
58.4  
115/60/1  
104–126  
1750  
1/2  
7.2  
3/4  
12.0  
12.8  
1.0  
Two-speed  
115/60/1  
104–126  
187–253  
1750/1160  
1750  
3/4  
1.0  
1/3  
1/2  
3/4  
1.0  
1/3  
1/2  
3/4  
1.0  
1/2  
3/4  
1.0  
1.5  
2.0  
3.0  
1/2  
3/4  
1.0  
1.5  
2.0  
3.0  
1/2  
3/4  
1.0  
1.5  
2.0  
3.0  
3/4  
1.0  
1.5  
2.0  
3.0  
40  
41  
8.9/6.1  
11.5/8.1  
3.1  
3.6  
6.0  
6.4  
2.5  
3.6  
4.3  
5.6  
2.3  
2.9  
3.5  
4.8  
6.2  
8.6  
2.4  
3.0  
3.6  
4.8  
6.2  
8.6  
1.2  
1.5  
1.8  
2.4  
3.1  
4.3  
1.1  
1.4  
1.9  
2.5  
3.3  
42.0  
58.2  
11.4  
15.2  
29.2  
29.2  
12.1  
19.3  
25.3  
32.6  
11.4  
15.9  
20.2  
30.0  
38.5  
55.1  
12.8  
18.6  
23.0  
33.4  
43.6  
62.0  
6.4  
208–230/60/1  
18  
21  
29  
29  
277/60/1  
249–305  
187–229  
1750  
1750  
15.5  
21.5  
25  
29  
208/60/3  
22  
26  
28  
29  
34  
49  
230/60/3  
460/60/3  
575/60/3  
207–253  
414–506  
518–632  
1750  
1750  
1750  
22  
26  
28  
29  
34  
49  
22  
26  
9.3  
28  
11.5  
16.7  
21.8  
31.0  
7.5  
29  
34  
49  
20.5  
22.5  
31  
9.0  
13.3  
17.9  
23.7  
36  
49  
Note: For two-speed units not being controlled by the Tracer™ family of controls, a 0.2-second delay for speed switching needs  
to be incorporated into the control sequence.  
BCXC-SVX01B-EN  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation Electrical  
Table 14. Motor electrical data (continued)  
Voltage  
Voltage range  
rpm  
Rated hp  
1/3  
1/2  
3/4  
1.0  
lb  
20.5  
25  
29  
38  
20.5  
25  
29  
38  
22  
26  
28  
29  
34  
49  
22  
26  
28  
29  
34  
49  
FLA  
3.0  
3.6  
5.2  
9.3  
3.3  
4.0  
5.5  
10.6  
1.1  
1.4  
1.7  
2.1  
2.8  
3.6  
1.2  
1.5  
1.9  
2.5  
3.1  
3.6  
LRA  
15.6  
20.5  
25.6  
52.2  
17.1  
22.7  
39.1  
57.8  
5.6  
220/50/1  
198–242  
1450  
240/50/1  
216–264  
1450  
1450  
1/3  
1/2  
3/4  
1.0  
190/50/3  
380/50/3  
171–209  
342–418  
1/3  
1/2  
3/4  
1.0  
7.8  
9.8  
14.6  
18.7  
27.2  
6.8  
1.5  
2.0  
415/50/3  
374–456  
1450  
1/3  
1/2  
3/4  
1.0  
9.4  
11.0  
17.4  
22.6  
32.3  
1.5  
2.0  
Note: For two-speed units not being controlled by the Tracer™ family of controls, a 0.2-second delay for speed switching needs  
to be incorporated into the control sequence.  
32  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Mechanical  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects before servicing. Follow proper  
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to  
disconnect power before servicing could result in death or serious injury.  
Installing the Unit  
Follow the procedures below to install the blower coil unit.  
Horizontal Units, Model BCHC  
Install horizontal units suspended from the ceiling with 3/8” threaded rods that are field provided.  
There are two knockouts in each corner of the unit for installation of the threaded rods. Ensure the  
ceiling opening is large enough for unit installation and maintenance requirements.  
BCHC Installation Procedure  
Materials needed:  
threaded rods, 3/8” (4)  
nuts (8)  
flat washers or steel plates (8)  
vibration isolator hangers or turnbuckles (4)  
1. Determine the unit mounting hole dimensions. Prepare the hanger rod isolator assemblies,  
whicharefieldprovided, andinstallthemintheceiling. Tranerecommendsusingthreadedrods  
to level the unit. Consult the unit nameplate or “Dimensions and Weights,” p. 15 in this manual  
for the unit weight. See Figure 4 for proper horizontal unit installation.  
Figure 4. How to hang the horizontal unit from the ceiling  
2. Remove motor access panels and filter access panels.  
3. Punch out the eight knockouts in the top and bottom panels.  
BCXC-SVX01B-EN  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation Mechanical  
4. Guide the threaded rod through the unit from the top, careful not to damage insulation or  
wiring. See Figure 5. Insert the threaded rod at an angle to help prevent internal unit damage.  
Figure 5. When inserting the threaded rod though the unit knockouts, angle it through the top,  
careful not to damage unit coil or insulation.  
5. Put a nut and large flat washer or steel plate on the bottom of the threaded rod. See Figure 6.  
Figure 6. Correct placement of washer or steel plate and nut between threaded rod and unit.  
This helps prevent air leakage.  
6. Put a nut and flat washer or steel plate on the top to prevent air leakage.  
7. Thread the top of the rod into the isolator or turnbuckle.  
8. Hoist the unit to the suspension rods and attach with washers and lock–nuts (see Figure 4, p. 33  
for details).  
9. Level the unit for proper coil drainage and condensate removal from the drain pan. Refer to  
10. Connect the ductwork to the unit. Refer to “Duct Connections,” p. 37.  
Vertical Units, Model BCVC  
Install vertical units on the floor. Units are provided with legs that are field-installed to help  
accommodate a U-trap on the drain connection, if necessary. A field-fabricated inlet plenum is not  
34  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation Mechanical  
required. The unit is shipped in two pieces, and can be arranged in either a pre-swirl or counter-  
swirl inlet configuration (see Figure 7).  
Figure 7. Typical vertical unit installation  
Heating Coil Option  
Note: The hydronic heating coil option is factory installed in either the reheat or preheat position.  
Coils can be rotated for either right or left-hand connections.  
If you need to rotate the hydronic heating coil option to change the coil connection side, follow the  
procedure below.  
1. Remove both coil access panels.  
2. Remove the coil and rotate to change connection position.  
3. Exchange coil patch plates.  
4. Knock out drain pipe connections on new coil hand access panel.  
5. Plug old drain connections.  
Mixing Box Option  
Materials provided:  
mounting legs  
BCXC-SVX01B-EN  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation Mechanical  
interconnecting linkage, LH or RH attachment  
Materials needed:  
grooved and extendible drive rods, 1/2-inch O.D. grooved  
screws  
The mixing box option ships separately for field installation. It has two low-leak, opposed blade  
dampers and all necessary interconnecting linkage components for left or right hand attachment  
onto 1/2-inch O.D. grooved, extendible drive rods. Also, mounting legs are provided for floor  
mounting on a vertical unit. Knockouts are provided to suspend the mixing box from the ceiling  
horizontally.  
Mixing Box Installation Procedure  
1. Support the mixing box independent of the unit in the horizontal position.  
2. Install the mixing box as a sleeve around the duct collar of the filter frame. To attach the mixing  
box to the filter frame, insert screws through the matching the holes on all sides of the mixing  
box and filter frame.  
3. Install the linkage, following the procedure below.  
Linkage Installation Procedure  
1. Attach the linkage on either the right or left side of the mixing box following the procedure  
below.  
2. Open the damper blades fully. Locate drive rods on the LH or RH side for linkage attachment.  
Loosen drive rod set screw, without removing.  
3. Remove knockouts on side access panel adjacent to the drive rods.  
4. Pierce a hole through the insulation at the knockouts to allow the drive rod to extend freely  
through side of mixing box. Cut away insulation sufficiently to allow drive rod to turn smoothly.  
5. Extend drive rod end at desired position beyond side of unit. Tighten drive rod set screws.  
6. Attach linkage and tighten all set screws. Note that neither hand levers are provided. However,  
mixing box actuators are a factory-provided option that ship inside the mixing box when  
ordered.  
7. Position linkage so both sets of dampers operate freely and so that when one damper is fully  
open, the other is fully closed.  
Condensate Drain Connections  
Note: It is the installers responsibility to provide adequate condensate piping to prevent potential  
water damage to the equipment and/or building.  
Size the main drain lines and trap them the same size as the drain connection, which is 3/4”  
schedule 40 PVC, 1.050” O.D. on blower coils.  
If drain pan removal is required, make the main and auxiliary drain connections with compression  
fittings. Follow the procedure below to remove the drain pan.  
1. Remove the opposite side coil access panel.  
2. Remove the drain pan clips.  
3. Disconnect drain lines.  
4. Remove the sheet metal screw.  
5. Pull out drain pan through the opposite side.  
Note: Prime drain traps to prevent the drain pan overflow.  
36  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation Mechanical  
Plug or trap the auxiliary connection to prevent air from being drawn in and causing carryover (see  
Figure 8. Recommended drain trap installation for draw-through units  
H = 1” of length for each 1” of negative pressure + 1”additional  
J = 1/2 of H  
L = H + J + pipe diameter + insulation  
All drain lines downstream of the trap must flow continuously downhill. If segments of the line are  
routed uphill, this can cause the drain line to become pressurized. A pressurized drain line may  
cause the trap to back up into the drain pan, causing overflow.  
Duct Connections  
Install all air ducts according to the National Fire Protection Association standards for the  
“Installation of Air Conditioning and Ventilation Systems other than Residence Type (NFPA 90A)  
and Residence Type Warm Air Heating and Air Conditioning Systems (NFPA 90B).  
Make duct connections to the unit with a flexible material such as heavy canvas to help minimize  
noise and vibration. If a fire hazard exists, Trane recommends using Flexweave 1000, type FW30  
or equivalent canvas. Use three inches for the return duct and three inches for the discharge duct.  
Keep the material loose to absorb fan vibration.  
Run the ductwork straight from the opening for a minimum of 1-1/2 fan diameters. Extend  
remaining ductwork as far as possible without changing size or direction. Do not make abrupt turns  
or transitions near the unit due to increased noise and excessive static losses. Avoid sharp turns  
and use elbows with splitters or turning vanes to minimize static losses.  
Poorly constructed turning vanes may cause airflow generated noise. Align the fan outlet properly  
with the ductwork to decrease duct noise levels and increase fan performance. Check total external  
static pressures against fan characteristics to be sure the required airflow is available throughout  
the ductwork.  
To achieve maximum acoustical performance, minimize the duct static pressure setpoint.  
BCXC-SVX01B-EN  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation Piping  
Water Coil Connections  
Water coils have sweat connections. Reference coil connection dimensions in “Dimensions and  
Weights,” p. 15. Properinstallationandpipingisnecessarytoensuresatisfactorycoiloperationand  
prevent operational damage. Water inlet and outlet connections extend through the coil section  
side panel (see Figure 9). Follow standard piping practices when piping to the coil.  
Figure 9. Horizontal unit coil connect location  
NOTICE  
Potential coil-freeze condition!  
Make provisions to drain the coil when not in use to prevent coil freeze-up. Failure to follow this  
procedure could result in equipment/property damage.  
Piping Packages  
Piping packages ship separate for field installation and have sweat type connections.  
Interconnecting piping is field provided.  
When brazing piping, follow these guidelines to prevent piping component damage.  
1. Avoid exposing piping components to high heat when making sweat connections.  
2. Protect the closest valve to the connection with a wet rag.  
3. Ensure the circuit balancing valve option is in the unseated position.  
Refrigerant Coil Piping  
The DX cooling coil in a BCHC/BCVC unit is equipped with a single distributor (single-circuited).  
Exception: size 72 and 90 six-row DX cooling coils are horizontally split and have two distributors  
(double-circuited) which may be manifolded to a single refrigeration circuit in a condensing unit.  
Some condensing units have two, independent refrigeration circuits. Do not manifold two,  
independent refrigeration circuits into a single-circuited DX (evaporator) coil.  
Note: Refer to “Warnings, Cautions and Notices” for information on handling refrigerants.  
Units that are UL listed shall not have refrigerant temperatures and pressures exceeding that listed  
on the unit nameplate.  
Follow accepted refrigeration piping practices and safety precautions for typical refrigerant coil  
piping and components. Specific recommendations are provided with the compressor unit,  
including instructions for pressure-testing, evacuation, and system charging. Leak test the entire  
refrigerant system after all piping is complete. Charge the unit according to approximate weight  
requirements, operating pressures, and superheat/subcooling measurements. Adjust the thermal  
expansion valve setting, if necessary, for proper superheat.  
Liquid Line  
Line Sizing. Properly sizing the liquid line is critical to a successful application. If provided, use  
the liquid line size recommended by the manufacturer of the compressor unit. The selected tube  
38  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Installation Piping  
diameter must be as small as possible, while still providing at least 5°F [2.7°C] of subcooling at the  
expansion valve throughout the operating envelope.  
Routing. Install the liquid line with a slight slope in the direction of flow so that it can be routed  
with the suction line. Minimize tube bends and reducers because these items tend to increase  
pressure drop and reduce subcooling at the expansion valve.  
Insulation. The liquid line is generally warmer than the surrounding air, so it does not require  
insulation.  
Components. Liquid-line refrigerant components necessary for a successful job include an  
expansion valve, moisture indicating sight glass, filter drier, manual ball shutoff valves, access  
port, and possibly a solenoid valve. Position these components as close to the evaporator as  
possible.  
Thermal expansion valve (TEV)  
Select the TEV based on the actual evaporator capacity, considering the full range of loadings.  
Verify that the valve will successfully operate at the lightest load condition, considering if hot  
gas bypass is to be used. For improved modulation, choose a TEV with balanced port  
construction and an external equalizer connection. The valve must be designed to operate  
against a back pressure of 20 psi higher than actual evaporator pressure. Install the TEV directly  
on the coil liquid connection (distributor provided).  
The remote expansion-valve bulb should be firmly attached to a straight, well-drained,  
horizontal section of the suction line. The external equalizer line should be inserted  
downstream of the remote bulb.  
Moisture-indicating sight glass  
Install a moisture-indicating sight glass in the liquid line between the expansion valve and filter  
drier. The sight glass should be sized to match the size of the liquid line.  
Filter drier  
Install a properly sized liquid line filter-drier upstream from the expansion valve and as close  
to the evaporator coil as possible. Select the filter-drier for a maximum pressure drop of 2 psi  
at the design condition.  
Manual, ball-type shutoff valves on either side of the filter drier allows replacement of the core  
without evacuating the entire refrigerant charge.  
Access port  
The access port allows the unit to be charged with liquid refrigerant and is used to determine  
subcooling. This port is usually a Schraeder valve with a core.  
Solenoid valve  
If required by the compressor unit, install the solenoid valve between the filter drier and sight  
glass.  
NOTICE  
Valve Damage!  
Disassemble the thermal expansion valve before completing the brazing connections. If  
necessary, wrap the valve in a cool wet cloth while brazing. Failure to protect the valve from  
high temperatures could damage internal components.  
Suction Line  
Line sizing. Properly sizing the suction line is critical for ensuring that the oil returns to the  
compressor throughout the system operating envelope. If provided, use the suction line size(s)  
recommended by the manufacturer of the compressor unit. The selected tube diameter(s) must  
maintain adequate refrigerant velocities at all operating conditions.  
BCXC-SVX01B-EN  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Piping  
Routing. To prevent residual or condensed refrigerant from “free-flowing” toward the  
compressor, install the suction line so it slopes slightly—1 inch per 10 feet of run [1 cm per 3 m]—  
toward the evaporator. Avoid putting refrigerant lines underground. Refrigerant condensation,  
installation debris inside the line, service access, and abrasion/corrosion can quickly impair system  
reliability.  
Insulation. After operating the system and testing all fittings and joints to verify the system is  
leak-free, insulate the suction lines to prevent heat gain and unwanted condensation.  
Components. Installing the suction line requires field installation of these components: an  
access port and possibly a suction filter. Position them as close to the compressor as possible.  
Access port  
The access port is used to determine suction pressure and adjust the TEV. It should be located  
near the external equalizer line connection. This port is usually a Schraeder valve with a core.  
Suction filter  
If required by the compressor unit, a replaceable-core suction filter is installed as close to the  
compressor unit as possible. Adding manual, ball-type shutoff valves upstream and  
downstream of the filter simplifies replacement of the filter core.  
Field-Installing Evaporator Piping  
See Figure 10 and refer to the instructions below to field-install evaporator piping.  
1. Pitch the liquid line slightly—1 in./10 ft [1 cm/3 m]—so that the refrigerant drains toward the  
evaporator.  
2. Provide one expansion valve per distributor.  
3. Slightly pitch the outlet line from the suction header toward the suction riser — that is, 1 in./10  
ft [1 cm/3 m] in the direction of flow. Use the tube diameter that matches the suction-header  
connection.  
4. For the vertical riser, use the tube diameter recommended by the condensing unit  
manufacturer. Assure the top of the riser is higher than the evaporator coil.  
5. Arrange the suction line so the refrigerant vapor leaving the coil flows downward, below the  
suction-header outlet, before turning upward.  
6. Pitch the suction line slightly—1 in./10 ft [1 cm/3 m]—so the refrigerant drains toward the  
evaporator.  
7. Insulate the suction line.  
Figure 10. Field-installed evaporation piping example  
Evaporator Coil with  
Standard Circuiting  
suction line  
liquid  
line  
sight  
glass  
thermal  
expansion  
solenoid filter drier  
valve  
valve (TXV)  
distributor  
40  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation Piping  
Steam Piping  
Proper installation, piping and trapping is necessary to insure satisfactory heating coil operation  
and prevent operational damage under service conditions. These installation recommendations  
and piping diagram (see Figure 11, p. 42) must be followed to assure satisfactory, trouble-free  
operation.  
General  
1. Support all piping independently of coils.  
2. Provide swing joints or flexible fittings in all piping connections adjacent to heating coils to  
absorb expansion and contraction strains.  
3. Install coils so air passes through fins in proper direction (stenciled on top of coil channel).  
Steam Coils  
NOTICE  
Coil Condensate!  
Condensate must flow freely from the coil at all times to prevent coil damage from water  
hammer, unequal thermal stresses, freeze-up and/or corrosion. In all steam coil installations, the  
condensate return connections must be at the low point of the coil. Failure to follow these  
instructions could result in equipment damage.  
1. Install 1/2-inch 15-degree swing check vacuum breaker in unused condensate return tapping as  
close as possible to coil. Vent vacuum breaker line to atmosphere or connect into return main  
at discharge side of steam trap. Vacuum relief is particularly important when coil is controlled  
by modulating steam supply or two-position (on-off) automatic steam supply valve.  
2. Proper steam trap selection and installation is necessary for satisfactory coil performance and  
service life.  
a. Select trap based on maximum possible condensate rate and recommended load factors.  
b. Locate steam trap discharge at least 12 inches below condensate return tapping. This  
provides sufficient hydrostatic head pressure to overcome trap losses and assure complete  
condensate removal.  
c. Float and thermostatic traps are preferred because of gravity drain and continuous  
discharge operation.  
d. Use float and thermostatic traps with atmospheric pressure gravity condensate return with  
automatic controls or where possibility of low pressure supply steam exists.  
e. Bucket traps should only be used when supply steam is unmodulated and 25 psig or higher.  
f. Wheninstalledwithseriesairflow, sizetrapsforeachcoilusingcapacityoffirstcoilinairflow  
direction.  
g. Always trap each coil separately to prevent condensate holdup in one or more coils.  
h. Always install strainers as close as possible to inlet side of trap.  
3. Use V-port modulating valves to obtain gradual modulating action or slow opening 2-position  
valves to prevent steam hammer.  
Note: Contact the factory for recommendations regarding steam coil valve selections  
compatible with Tracer™ ZN controllers.  
4. Use normally-open non-modulating control valves if coils are exposed to freezing air.  
Note: Contact the factory for recommendations regarding steam coil valve selections  
compatible with Tracer™ ZN controllers.  
5. Control each coil bank separately when installing coils for series airflow with automatic steam  
control valves.  
BCXC-SVX01B-EN  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation Piping  
6. Do not modulate steam or use on-off supply control on systems with overhead or pressurized  
returns unless condensate is drained by gravity to receiver (vented to atmosphere) and  
returned to main by condensate pump.  
7. At startup with dampers, slowly turn steam on full for at least 10 minutes before opening fresh  
air intake.  
8. Pitch all supply and return steam piping down a minimum of one inch per 10 feet in direction  
of flow.  
9. Do not drain steam mains or take-offs through coils. Drain mains ahead of coils through steam  
trap to return line.  
10. Do not bush or reduce coil return tapping size. Run return pipe full size of steam trap connection  
except for short nipple screwed directly into coil condensate connection.  
11. Overhead returns require 1 psig pressure at steam trap discharge for each 2-foot elevation to  
assure continuous condensate removal.  
Figure 11. Type NS steam coils, horizontal tubes for horizontal airflow  
Code of System Components  
FT = Float and thermostatic steam trap  
BT = Bucket steam trap  
GV = Gate valve  
OV = Automatic two-position (on-off) control  
valve  
TV = Automatic three-way control valve  
VB = Vacuum breaker, 15-degree swing check  
valve  
CV = Check valve  
ST = Strainer  
AV = Automatic or manual air vent  
42  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Controls Interface  
Control Options  
Blower coil air handlers are available without controls or with one of four different control options:  
Control interface  
Tracer™ ZN010  
Tracer ZN510  
Tracer ZN520  
Units without controls have a junction box mounted on the drive side for motor power wire  
terminations. The controller is easily accessible in the control box for service. Control option  
descriptions follow below.  
Control Interface  
The control interface is for use with a field–supplied low voltage thermostat. It includes a control  
box with a transformer, motor contactor, and disconnect switch. All hot leads to the motor are  
disconnected at the contactor and disconnect switch to eliminate the risk of shock during service.  
The end devices are mounted with the wires pulled and terminated inside the two-sided terminal  
strip. All customer connections other than power are on the outside of the two-sided terminal strip.  
Tracer Controllers  
The Tracer™ family of controllers—ZN010, ZN510, and ZN520—offer the combined advantages of  
simple and dependable operation with the latest Trane-designed controller. Standard control  
features include options normally available on more elaborate control systems. All control options  
are available factory-configured or can be field-configured using Rover™ service software. For  
more detailed information, refer to Trane publication CNT-IOP-1, Installation, Operation, and  
Programming Guide (for ZN010 or ZN510), or CNT-SVX04A-EN, Installation, Operation, and  
Programming Guide (for ZN520).  
Tracer ZN010  
Tracer™ ZN010 is a stand-alone microprocessor controller.  
Tracer ZN510 and ZN520  
The Tracer™ ZN510 controller can be used as either a standalone or as part of a Trane Integrated  
Comfort™ System (ICS).  
Figure 12. ZN510 control board  
Figure 13. ZN520 control board  
In the stand-alone configuration, ZN510 or 520 receives operation commands from the zone sensor  
and/or the auto changeover sensor (on auto changeover units). ZN520 also receives commands  
from the discharge air sensor. The entering water temperature is read from the auto changeover  
sensor and determines if the unit is capable of cooling or heating. The zone sensor module is  
capable of transmitting the following information to the controller:  
Timed override on/cancel request  
BCXC-SVX01B-EN  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Controls Interface  
Zone setpoint  
Current zone temperature  
Fan mode selection (off-auto-high-low)  
For optimal system performance, blower coil units can operate as part of an Integrated Comfort™  
System (ICS) building automation system controlled by Tracer Summit®. The controller is linked  
directly to the Summit control panel via a twisted pair communication wire, requiring no additional  
interface device (i.e., a command unit). The Trane ICS system can monitor or override ZN520  
control points. This includes such points as temperature and output positions.  
Rover Service Software  
This windows-based software package option allows field service personnel to easily monitor,  
save, download, and configure Tracer™ controllers through a communication link from a portable  
computer. When connected to the communication link, Rover™ can view any Tracer controller that  
is on the same communication link.  
Table 15. Tracer controller input/output summary  
Tracer™ controller  
ZN010  
ZN510  
ZN520  
Binary outputs  
2-speed fan  
2-position hydronic valve  
2-position mixing box damper  
1-stage electric heat  
Modulating mixed air damper  
Modulating hydronic valve  
2-stage electric heat  
Reheat (hydronic)  
Generic  
Binary inputs  
Condensate overflow detection  
Low temperature detection  
Occupancy  
Generic input  
Analog inputs  
Zone temperature  
Setpoint  
Fan mode: auto, high, low  
Entering water  
Discharge air  
Outside air  
Generic  
Notes:  
1. The generic input and output are for use with a Tracer Summit® systems only.  
2. Contact the factory for recommendations regarding steam coil valve selections compatible with Tracer™ ZN controllers.  
44  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Controls Interface  
Table 16. Tracer controller function summary  
Tracer™ Controller  
ZN010  
ZN510  
ZN520  
Control functions  
Entering water temp. sampling (purge)  
Timed override  
Auto changeover  
Fan cycling  
Warm-up  
Pre-cool  
Data sharing (master/slave)  
Random start  
Dehumidification  
Staged capacity (2-stage electric supplementary)  
DX cooling  
Other Functions  
Manual test  
Filter maintenance timer  
Setpoint limits  
Table 17. End Device Option Availability  
Tracer™  
Control  
Device  
ZN010  
Tracer ZN510 Tracer ZN520  
interface  
Condensate float switch  
Low limit  
Filter status  
Filter run-time diagnostic  
Fan status  
Positive proof fan status switch  
2-position control valves  
Modulating control valves  
2-position mixing box actuator  
Modulating mixing box actuator  
1-stage electric heat  
2-stage electric heat  
Frostat™ protection (DX coils)  
Notes:  
1. The Tracer ZN010, Tracer ZN510, and Tracer ZN520 are factory-provided controls that control the end devices listed in  
the table.  
2. The control interface option is the wiring tied back to a terminal strip to be controlled by a field-supplied controller.  
3. Units with a DX coil are provided with a DX cool relay if unit has the control interface or Tracer controls.  
4. Contact the factory for recommendations regarding steam coil valve selections compatible with Tracer™ ZN controllers.  
BCXC-SVX01B-EN  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pre-Start  
Pre-Start Checklist  
Complete this checklist after installing the unit to verify all recommended installation procedures  
are complete before unit startup. This does not replace the detailed instructions in the appropriate  
sections of this manual. Disconnect electrical power before performing this checklist. Always read  
the entire section carefully to become familiar with the procedures.  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects before servicing. Follow proper  
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to  
disconnect power before servicing could result in death or serious injury.  
Receiving  
Inspect unit and components for shipping damage. File damage claims immediately with the  
delivering carrier.  
Check unit for missing material. Look for ship-with drives, isolators, filters, and sensors that are  
packaged separately and placed inside the main control panel, fan section, or compressor section  
Check nameplate unit data so that it matches the sales order requirements.  
Unit Location  
Remove crating from the unit. Do not remove the shipping skid until the unit is set in its final  
position.  
Ensure the unit location is adequate for unit dimensions, ductwork, piping, and electrical  
connections.  
Ensure access and maintenance clearances around the unit are adequate. Allow space at the end  
of the unit for shaft removal and servicing (see “Service Access,” p. 12).  
Unit Mounting  
Place unit in its final location.  
Remove shipping skid bolts and skid.  
If using isolators, properly mount unit according to the isolator placement sheet.  
46  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Pre-Start  
Component Overview  
Verify the fan and motor shafts are parallel.  
Verify the fan and motor sheaves are aligned.  
Check the belt tension for proper adjustment. Adjust the belt tension if it is floppy or squeals  
continually.  
Ensure the fan rotates freely in the correct direction.  
Tighten locking screws, bearing set screws and sheaves.  
Ensure bearing locking collars do not wobble when rotated and correct torque settings. Refer to  
Table 31, p. 64 for recommended torques.  
Verify that a clean air filter is in place.  
Ductwork  
If using return ductwork to the unit, secure it with three inches of flexible duct connector.  
Extend discharge duct upward without change in size or direction for at least one and one half  
fan diameters.  
Use a 3” flexible duct connection on discharge ductwork.  
Ensure trunk ductwork is complete and secure to prevent leaks.  
Verify that all ductwork conforms to NFPA 90A or 90B and all applicable local codes  
Unit Piping  
Verify the condensate drain piping is complete for the unit drain pan. Install and tighten the  
condensate “P” trap drain plug.  
Make return and supply water connections to the unit and/or piping package.  
Ensure the drain pan and condensate line are not obstructed. Remove any foreign matter that  
may have fallen into the drain pan during installation.  
Verify that piping does not leak. Make sure drain lines are open while performing the leak test.  
Treat water to prevent algae, slime, and corrosion.  
Connect refrigerant piping lines.  
Connect steam supply lines and condensate return lines to coil in accordance with steam piping  
recommendations.  
Electrical  
Check all electrical connections for tightness.  
Verify motor voltage and amps on all phases with the unit nameplate ratings to ensure unit  
operates correctly.  
Unit Panels  
Ensure all unit access panels arein place and that all screws, nuts, and bolts are tightened to their  
proper torques.  
Note: During the unit break-in period, bearing temperature may be 150–160°F. during normal  
operation bearing temperature should range be 90–100°F.  
BCXC-SVX01B-EN  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up  
Sequence of Operation  
Tracer ZN Controller Sequence of Operation  
Controller Start-Up  
Refer to Trane publication CNT-SVX04A-EN, Installation, Operation, and Programming Guide, to  
operate the Tracer™ ZN controller with Trane Integrated Comfort™ System (ICS). The factory pre-  
programs the Tracer ZN controller with default values to control the temperature and unit airflow.  
UseTracer Summit®buildingautomationsystemorRover™ software tochangethedefault values.  
Follow the procedure below to operate the Tracer™ ZN controller in a stand-alone operation:  
1. Turn power on at the disconnect switch option.  
2. Position the fan mode switch to either high, low, or the auto position.  
3. Rotate the setpoint dial on the zone sensor module to 55°F for cooling or 85°F for heating.  
The appropriate control valve will actuate assuming the following conditions:  
1. Room temperature should be greater than 55°F and less than 85°F.  
2. For a two-pipe unit with an automatic changeover sensor, the water temperature input is  
appropriateforthedemandplaced ontheunit. For example, coolingoperationisrequestedand  
cold water (5° lower than room temperature) flows into the unit.  
3. Select the correct temperature setpoint.  
Note: Select and enable zone sensor temperature settings to prevent freeze damage to unit.  
Power-Up Sequence  
When 24 VAC power is initially applied to the Tracer™ ZN controller, the following sequence occurs:  
all outputs are controlled off  
Tracer reads all input values to determine initial values,  
the random start time (0–25 seconds) expires, and  
normal operation begins.  
Tracer ZN Modes of Operation  
Tracer™ ZN controllers operate the fan in one of the modes listed below as noted:  
occupied  
unoccupied  
occupied standby (Tracer ZN510 or ZN520 only)  
occupied bypass  
Tracer Summit® with supply fan control (Tracer ZN510 or ZN520 only)  
Note: The Tracer™ ZN520 controller operates the supply fan continuously when the controller is  
in the occupied and occupied standby modes, for either heating or cooling. The controller  
only cycles the fan off with heating and cooling capacity in the unoccupied mode.  
Whenthecommunicated occupancyrequestis unoccupied, theoccupancybinaryinput(if present)  
does not affect the controllers occupancy. When the communicated occupancy request is  
occupied, the controller uses the local occupancy binary input to switch between the occupied and  
occupied standby modes.  
Occupancy Sources  
There are four ways to control the Tracer™ ZN controllers occupancy, as noted below:  
1. By pressing the zone sensors timed override on” button  
2. Occupancy binary input, either normally open or normally closed, see Table 18 for occupancy  
sensor states  
48  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Start-Up  
3. Default operation of the controller (occupied mode)  
4. Communicated request, usually provided by the building automation system (BAS) or peer  
device (available on Tracer™ ZN510 and ZN520 only)  
Table 18. Occupancy sensor state  
Sensor type  
Normally open  
Normally open  
Normally closed  
Normally closed  
Sensor position  
Open  
Unit occupancy mode  
Occupied  
Closed  
Unoccupied  
Open  
Unoccupied  
Closed  
Occupied  
A communicatedrequestwillcontrolthe controllersoccupancy. Typically, thisrequestcomesfrom  
the BAS time-of-day scheduling to the controller. However, if a communication request from a BAS  
or peer controller is lost, the controller reverts to the default operating mode (occupied) after 15  
minutes (configurable, specified by the “receive heartbeat time”), if no local hardwired occupancy  
signal exists.  
If the unit is communicating with Tracer Summit® and the supply fan control programming point  
is configured for Tracer™ (the factory configures as local), then Tracer Summit will control the fan  
regardless of the fan mode switch position.  
For complete information about Tracer Summit® application setup using the Tracer™ ZN  
controller, see the Tracer Summit product literature. For more information on the setup of another  
BAS, refer to the product-specific literature from that manufacturer.  
Occupied Mode  
When the controller is in the occupied mode, the unit attempts to maintain the space temperature  
at the active occupied heating or cooling setpoint, based on the:  
measured space temperature,  
the discharge air temperature (Tracer™ ZN520 only),  
the active setpoint, and  
the proportional/integral control algorithm.  
The modulating control algorithm used when occupied or in occupied standby is described in the  
following sections. Additional information related to the handling of the controller setpoints can  
be found in the previous setpoint operation section.  
Note: Heating and cooling setpoint high and low limits are always applied to the occupied and  
occupied standby setpoints.  
Unoccupied Mode  
When the controller is in the unoccupied mode, the controller attempts to maintain space  
temperature at the stored unoccupied heating or cooling setpoint based on the:  
measured space temperature,  
active setpoint, and  
control algorithm, regardless of the presence of a hardwired or communicated setpoint.  
Similar to other controller configuration properties, the locally stored unoccupied setpoints can be  
modified using Rover™ service tool.  
During cooling mode, when the space temperature is above the cool setpoint, the primary cooling  
capacity operates at 100%. If more capacity is needed, the supplementary cooling capacity turns  
on (or opens to 100%).  
During heating mode, when the space temperature is below the heat setpoint, the primary heating  
capacity turns on. All capacity turns off when the space temperature is between the unoccupied  
cooling and heating setpoints. Note that primary heating or cooling capacity is defined by the unit  
type and whether heating or cooling is enabled or disabled. For example, if the economizer is  
BCXC-SVX01B-EN  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Start-Up  
enabled (Tracer™ ZN520 only) and possible, it is the primary cooling capacity. If hydronic heating  
is possible, it will be the primary heating capacity.  
Occupied Standby Mode (Tracer ZN510 or ZN520 only)  
The controller can be placed into the occupied standby mode when a communicated occupancy  
request is combined with the local (hardwired) occupancy binary input signal.  
During occupied standby mode, the Tracer™ ZN520 controllers economizer damper position goes  
to the economizer standby minimum position.  
Note: The economizer standby minimum position can be changed using Rover™ service tool.  
In the occupied standby mode, the controller uses the occupied standby cooling and heating  
setpoints. Because the occupied standby setpoints typically cover a wider range than the occupied  
setpoints, the controller reduces heating/cooling demand for the space. Also, units with Tracer™  
ZN520 and the fresh air economizer damper use the economizer standby minimum position to  
reduce heating and cooling demand.  
When no occupancy request is communicated, the occupancy binary input switches the  
controllers operating mode between occupied and unoccupied. When no communicated  
occupancy request exists, the unit cannot switch to occupied standby mode.  
Occupied Bypass Mode, Tracer ZN510 or ZN520 Only  
The controller can be placed in occupied bypass mode by either communicating an occupancy  
bypass request to the controller or by using the timed override “on” button on the zone sensor.  
When the controller is in unoccupied mode, pressing the “on” button will place the controller into  
occupied bypass mode for the duration of the bypass time (typically 120 minutes).  
Tracer Summit With Supply Fan Control, Tracer ZN510 or ZN520 Only  
All Tracer™ ZN lockouts (latching diagnostics) are manually reset whenever the fan mode switch  
issettotheoffpositionorwhenpowerisrestoredtotheunit. Thelastdiagnostictooccurisretained  
until the unit power is disconnected. Refer to Trane publication CNT-SVX04A-EN, Installation,  
Operation, and Programming Guide, for specific Tracer ZN520 operating procedures.  
Cooling Operation  
During cooling mode, the Tracer™ ZN controller attempts to maintain the space temperature at the  
active cooling setpoint. Based on the controllers occupancy mode, the active cooling setpoint is  
either the:  
occupied cooling setpoint,  
occupied standby cooling setpoint (Tracer ZN510 or ZN520 only), or  
unoccupied cooling setpoint.  
The controller uses the measured space temperature, the active cooling setpoint, and discharge air  
temperature (Tracer™ ZN520 only) along with the control algorithm to determine the requested  
cooling capacity of the unit (0–100%). The outputs are controlled based on the unit configuration  
and the required cooling capacity. To maintain space temperature control, the cooling outputs  
(modulating or 2-position hydronic valve, or economizer damper) are controlled based on the  
cooling capacity output.  
Note: Economizer dampers and modulating valves are only available on units with the Tracer™  
ZN520 controller. Two-position dampers are only available on units with Tracer ZN010 and  
ZN510.  
Cooling output is controlled based on the cooling capacity. At 0% capacity, all cooling capacities  
are off and the damper is at minimum position. Between 0 and 100% capacity, the cooling outputs  
are controlled according to modulating valve logic (Tracer™ ZN520 only) or cycled with 2-position  
valves. As the load increases, modulating outputs open further and binary outputs are energized  
longer. At 100% capacity, the cooling valve or damper is fully open (modulating valves) or on  
continuously (2-position valves).  
50  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Start-Up  
Note: Unit diagnostics can affect fan operation, causing occupied and occupied standby fan  
operationtobedefinedasabnormal. RefertoTroubleshooting,p. 72formoreinformation  
about abnormal fan operation.  
Economizer Cooling (Tracer ZN520 Only)  
The economizer provides cooling whenever the outdoor temperature is below the economizer  
enable setpoint and there is a need for cooling. The economizer operates to meet the space  
demand, with other forms of cooling enabling when the economizer cannot meet the demand  
alone. See economizer air damper operation for additional information.  
DX Cooling (Tracer ZN520 only)  
The controller does not use both the DX compressor and the economizer at the same time. This  
prevents problems where the entering air temperature is too low for the evaporator coil to operate  
as designed, which leads to compressor short cycling due to low discharge air temperatures.  
Discharge Air Tempering (Tracer ZN520 Only)  
Cascade cooling control initiates a discharge air tempering function if:  
the discharge air temperature falls below the discharge air temperature control low limit,  
all cooling capacity is at minimum, and  
the discharge control loop determines a need to raise the discharge air temperature.  
The controller then provides heating capacity to raise the discharge air temperature to its low limit.  
The discharge air tempering function enables when cold, fresh air is brought in through the fresh  
air damper and causes the discharge air to fall below the discharge air temperature control low  
limit. The controller exits the discharge air tempering function when heat capacity has been at 0%  
for five minutes.  
Heating Operation  
During heating mode, the Tracer™ ZN controller attempts to maintain the space temperature at the  
active heating setpoint. Based on the controllers occupancy mode, the active heating setpoint can  
be:  
occupied heating,  
occupied standby heating (Tracer ZN510 or ZN520 only), or  
unoccupied heating.  
Note: Unit diagnostics can affect the controller operation, causing unit operation to be defined as  
abnormal. Refer to Troubleshooting,” p. 72 for more information about abnormal unit  
operation.  
Heating output is controlled based on the heating capacity. At 0% capacity, the heating output is  
off continuously. Between 0 and 100% capacity, the heating output is controlled according to  
modulating valve logic (ZN520 only) or cycled with 2-position valves. As the load increases,  
modulating outputs open further and binary outputs are energized longer. At 100% capacity, the  
modulating valve is fully open (Tracer™ ZN520 only) or on continuously with 2-position valves.  
Economizer Damper (Tracer ZN520 Only)  
The economizer damper option is never used for as a source for heating, but only for ventilation.  
Therefore, the damper is at the occupied minimum position in the occupied mode. The damper  
control is primarily associated with occupied fan operation.  
Dehumidification (Tracer ZN520 only)  
During dehumidification, the Tracer™ ZN520 controller adjusts the heating setpoint up to the  
cooling setpoint. This reduces the relative humidity in the space with a minimum of energy usage.  
The controller uses the measured space temperature, the active heating setpoint, and discharge  
airtemperature(TracerZN520 only)alongwiththecontrolalgorithm, todeterminetherequested  
BCXC-SVX01B-EN  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up  
heating capacity of the unit (0–100%). The outputs are controlled based on the unit configuration  
and the required heating capacity.  
Fan Mode Operation  
WARNING  
Rotating Components!  
Disconnect all electric power, including remote disconnects before servicing. Follow proper  
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to  
disconnect power before servicing could result in death or serious injury.  
For multiple fan speed applications, the Tracer™ ZN controller offers additional fan configuration  
flexibility. See Table 19 for fan operation sequences. Separate default fan speeds for heating and  
cooling modes can be configured using Rover™ service software.  
Table 19. Tracer ZN520 fan configuration  
Auto fan operation  
Fan speed default  
Heating  
Cooling  
Continuous  
Off  
Low  
High  
Off  
Continuous  
Low  
High  
The fan runs continuously at selected speeds, high or low. When the fan mode switch is in the auto  
position or a hardwired fan mode input does not exist, the fan operates at the default configured  
speed. See Table 20 for Tracer™ ZN520 default fan configuration for heating and cooling modes.  
During unoccupied mode, the fan cycles between high speed and off with heating and cooling fan  
modes. If the requested speed is off, the fan always remains off.  
Table 20. Fan sequence of operation  
Fan speed  
Tracer™ ZN controller  
Sequence of operation  
Off  
ZN010, ZN510, ZN520  
• fan is off  
• control valves and damper option are closed  
• low air temperature detection open is still active  
• fan operates continuously at selected speed  
• 2-position control valve option cycle as needed  
• 2-position control valve option opens to an adjustable mechanical stop-position  
• fan operates continuously at selected speed  
• modulating control valve option cycles as needed  
• fan, 2-position damper cycle, and control valve cycle as needed  
• in cooling mode, fan cycles from off to high  
• in heating mode, fan cycles from off to low  
Low or high (continuous fan) ZN010, ZN510  
Low or high (continuous fan) ZN520  
Auto (cycling)  
ZN010, ZN510  
• when heating/cooling is not required, the fan is off and the 2-position damper  
option closes  
Auto  
ZN520  
• fan cycles between high and medium, and never turns off unless the controller is  
in unoccupied mode  
• modulating or 2-position control open to maintain setpoint  
During dehumidification, when the fan is in auto, the fan speed can switch depending on the error.  
The fan speed increases as the space temperature rises above the active cooling setpoint.  
52  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Start-Up  
Additional flexibility built into the controller allows you to enable or disable the local fan switch  
input. The fan mode request can be hardwired to any of the Tracer™ ZN controllers or  
communicated to the Tracer ZN510 or ZN520 controller. When both inputs are present, the  
communicated request has priority over the hardwired input. See Table 19, p. 52.  
Fan Speed Switch  
Off. Fan is turned off, two-position damper option spring-returns closed.  
High or Low. Fan runs continuously at the selected speed. The two-position damper option  
opens to an adjustable mechanical stop-position.  
Tracer ZN010 and ZN510  
Off. Fan is off; control valves and fresh air damper option close. Low air temperature detection  
option is still active.  
Auto (Fan Cycling). Fan and fresh air damper cycle with control valve option to maintain  
setpoint temperature. If the unit has a 2-speed fan, in cooling mode the fan cycles from off to high  
and in heating mode it cycles from off to low (factory default that can be field-adjusted using  
Rover™ service software). When no heating or cooling is required, the fan is off and the fresh air  
damper option closes. Units with 2-speed fans can also be field-configured using Rover to run at  
a defined speed when the fan speed switch is in the auto position.  
Low or High (Continuous Fan). Fan operates continuously while control valve option cycles to  
maintain setpoint temperature. Fresh air damper option is open.  
Tracer ZN520  
Off. Fan is off; control valve options and fresh air damper options close. The low air temperature  
detection option is still active.  
Auto. Fan speed control in the auto setting allows the modulating (three-wire floating point)  
control valve option and single or two-speed fan to work cooperatively to meet precise capacity  
requirements, while minimizing fan speed (motor/energy/acoustics) and valve position (pump  
energy/chilledwater reset). As the capacity requirement increases at low fan speed, the water valve  
opens. When the low fan speed capacity switch point is reached, the fan switches to high speed and  
the water valve repositions to maintain an equivalent capacity. The reverse sequence takes place  
with a decrease in required capacity.  
Units with 2-speed fans on low or high. The fan will run continuously at the selected speed  
and the valve option will cycle to meet setpoint.  
Continuous Fan Operation  
During occupied and occupied standby modes, the fan normally is on. For multiple speed fan  
applications, the fan normally operates at the selected or default speed (off, high, or low). When  
fan mode is auto, the fan operates at the default fan speed.  
During unoccupied mode, the fan is off. While unoccupied, the controller will heat or cool to  
maintain the unoccupied heating and cooling setpoints. In unoccupied mode, the fan runs on high  
speed only, with heating or cooling. See Table 24, p. 55.  
The unit fan is always off during occupied, occupied standby, and unoccupied modes when the unit  
is off due to a diagnostic or when the unit is in the off mode due to the local zone sensor module,  
a communicated request, or the default fan speed (off).  
If both a zone sensor module and communicated request exist, the communicated request has  
priority. See Table 23, p. 55.  
BCXC-SVX01B-EN  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up  
Fan Cycling Operation  
Tracer™ ZN520 does not support fan cycling in occupied mode. The fan cycles between high speed  
and off in the unoccupied mode only. The controllers cascade control algorithm requires  
continuous fan operation in the occupied mode.  
Fan Off Delay  
When a heating output is controlled off, the Tracer™ ZN controller automatically holds the fan on  
for an additional 30 seconds. This 30-second delay allows the fan to blow off any residual heat from  
the heating source, such as a steam coil. When the unit is heating, the fan off delay is normally  
applied to control the fan; otherwise, the fan off delay does not apply.  
Fan Start on High Speed  
On a transition from off to any other fan speed, the Tracer™ ZN controller automatically starts the  
fan on high speed and runs the fan at high speed for 0.5 seconds. This provides ample torque  
required to start all fan motors from the off position.  
Fan Operation During Occupied Heating Modes  
The ZN520 fan output(s) normally run continuously during the occupied and occupied standby  
modes, but cycle between high and off speeds with heating/cooling during the unoccupied mode.  
When in the occupied mode or occupied standby mode and the fan speed is set at the high or low  
position, thefanrunscontinuouslyattheselectedspeed. RefertoTroubleshooting,p. 72formore  
information on abnormal fan operation.  
Table 21. Fan mode operation, Tracer ZN010 and ZN510  
Heating mode  
Unoccupied  
Cooling mode  
Unoccupied  
Fan mode  
Off  
Occupied  
Off  
Occupied  
Off  
Off  
Off  
(a)  
Low  
Low  
Off/high  
Off/high  
Off/high  
Off/high  
Low  
Off/high  
Off/high  
Off/high  
Off/high  
High  
High  
High  
Auto continuous  
Cycling off  
Notes:  
Heat default  
Off/heat default  
Cool default  
Off/cool default  
1. During the transition from off to any fan speed but high, Tracer™ ZN010 and ZN510 automatically start the fan on high  
speed and run for one-half of a second before transitioning to the selected speed (if it is other than high). This provides  
enough torque to start all fan motors from the off position.  
2. When the heating output is controlled off, ZN010 and ZN510 automatically control the fan on for an additional 30  
seconds. This delay allows the fan to dissipate any residual heat from the heating source, such as electric heat.  
(a) Whenever two states are listed for the fan, the first state (off) applies when there is not a call for heating or cooling. The  
second state (varies) applies where there is a call for heating or cooling. The heat default is factory-configured for low fan  
speed, and the cool default is high.  
Table 22. Valid operating range and factor default setpoints, Tracer ZN010 and ZN510  
Setpoint/parameter  
Unoccupied cooling setpoint  
Occupied cooling setpoint  
Occupied heating setpoint  
Unoccupied heating setpoint  
Cooling setpoint high limit  
Cooling setpoint low limit  
Heating setpoint high limit  
Heating setpoint low limit  
Power up control wait  
Default setting  
85°F  
Valid operating range  
40°F–115°F  
74°F  
40°F–115°F  
71°F  
40°F–115°F  
60°F  
40°F–115°F  
110°F  
40°F  
40°F–115°F  
40°F–115°F  
105°F  
40°F  
40°F–115°F  
40°F–115°F  
0 sec  
0 sec–240 sec  
54  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Start-Up  
Table 23. Local fan switch enabled  
Communicated  
Fan switch (local)  
Fan operation fan speed input  
Off  
Ignored  
Ignored  
Ignored  
Off  
Off  
Low  
High  
Auto  
Low  
High  
Off  
Low  
Low  
High  
High  
Auto  
Auto (configured default, determined by heat/cool mode)  
Table 24. Fan operation in heating and cooling modes  
Heating  
Cooling  
Unoccupied  
Fan mode  
Occupied  
Off  
Unoccupied  
Off  
Occupied  
Off  
Off  
Off  
Low  
Low  
Off/high  
Off/high  
Low  
Off/high  
Off/high  
High  
High  
High  
Auto (continuous)  
Default fan speed Off/high  
Default fan speed Off/high  
Two- and Four-Pipe Changeover Operation  
Tracer™ ZN controllers offer accurate and reliable unit changeover using 2-way valves and the  
controllers entering water temperature sampling function. Only units using the main hydronic coil  
for both heating and cooling (2-pipe and 4-pipe changeover units) use the entering water  
temperature sampling function.  
Two-pipe and 4-pipe changeover applications require an entering water temperature sensor to  
allow the main coil to be used for heating and cooling. This sensor is factory-provided and should  
be field-installed on the entering water pipe.  
The entering water temperature sampling function periodically opens the two-way valve to allow  
temporary water flow, producing reliable entering water temperature measurement. To ensure  
accurate unit changeover without sacrificing the benefits of 2-way, 2-position valves, Tracer™ ZN  
controllers periodically test the entering water temperature on all hydronic main coil changeover  
units. Hydronic heating/cooling changeover operation requires central plant operation, and the  
unitcontrollermustuseanenteringwatertemperaturesensortoverifydeliveryofthecorrectwater  
temperature from the central plant.  
Entering Water Temperature Sampling Function  
The entering water temperature (EWT) must be five degrees above the space temperature for  
hydronic heating and five degrees below the space temperature for hydronic cooling. When water  
BCXC-SVX01B-EN  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Start-Up  
flows normally and frequently through the coil, the controller does not invoke the sampling  
function because the EWT is satisfactory.  
Table 25. Unit mode as related to water temperature  
Unit type  
EWT sensor required?  
Coil water temperature  
2-pipe changeover  
Yes  
• Can cool if: space temp - EWT 5°F  
• Can heat if: EWT - space temp 5°F  
• Can cool if: space temp - EWT 5°F  
• Can heat if: EWT - space temp 5°F  
Hot water assumed  
4-pipe changeover  
Yes  
2-pipe heating only  
2-pipe cooling only  
4-pipe heat/cool  
No  
No  
No  
Cold water assumed  
• Cold water assumed in main coil  
• Hot water assumed in auxiliary coil  
However, when the controller detects an incorrect water temperature based on heating or cooling  
mode, it invokes the entering water temperature sampling function. For example, when the  
measured EWT is too coolto heatortoo warm to cool. Forcooling theEWTneedsto be five degrees  
below the measured space temperature. For heating, the EWT should be five degrees above the  
measured space temperature.  
After the controller invokes the function, the unit opens the main hydronic valve for no more than  
three minutes before considering the measured EWT. The controller allows an initial stabilization  
period, equal to 30 seconds plus 1/2 the valve stroke time, to flush the coil. Once the temperature  
stabilization period expires, the controller compares the EWT against the effective space  
temperature (either hardwired or communicated) to determine whether the EWT is correct for the  
desired heating or cooling mode. If the EWT is not usable for the desired mode, the controller  
continues to compare the EWT against the effective space temperature for a maximum of three  
minutes.  
The controller automatically disables the entering water temperature sampling and closes the  
main hydronic valve when the measured EWT exceeds the high EWT limit (110°F). When the EWT  
is warmer than 110°F, the controller assumes the EWT is hot because it is unlikely the coil would  
drift to a high temperature unless the actual loop temperature was very high.  
If the EWT is unusable—too cool to heat or too warm to cool—the controller closes the hydronic  
valve and waits 60 minutes before initializing another sampling. If the controller determines the  
EWT is valid for heating or cooling, it resumes normal heating/cooling control and effectively  
disables entering water temperature sampling until it is required.  
Electric Heat Operation  
Tracer™ ZN controllers support 1-stage electric heat. Also, Tracer ZN520 supports 2-stage electric  
heat. Tracer ZN520 cycles the electric heat to control the discharge air temperature. The rate of  
cycling is dependent upon the load in the space and the temperature of the incoming fresh air from  
the economizer (if any). Two-pipe changeover units with electric heat use the electric heat only  
when hot water is not available.  
Economizer Damper (Tracer ZN520 Only)  
With a valid outdoor air temperature (either hardwired or communicated), Tracer™ ZN520 usesthe  
modulating economizer damper as the highest priority cooling source. Economizer operation is  
only possible using a modulating damper during the occupied, occupied standby, unoccupied, and  
occupied bypass modes.  
The controller initiates the economizer function if the fresh air temperature is cold enough for use  
as free cooling capacity. If the fresh air temperature is less than the economizer enable setpoint  
(absolute dry bulb), the controller modulates the fresh air damper (between the active minimum  
damper position and 100%) to control the amount of fresh air cooling capacity. When the fresh air  
56  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Start-Up  
temperature rises 5°F above the economizer enable point, the controller disables economizing and  
moves the fresh air damper back to its predetermined minimum position based on the current  
occupancy mode or communicated minimum damper position.  
Table 26. Relationship between outdoor temperature sensors and economizer damper position (Tracer ZN520 only)  
Modulatingfreshairdamper  
Outdoor air temperature  
occupied or occupied bypass Occupied standby  
Unoccupied  
None or invalid  
Open to occupied minimum  
position  
Open to occupied standby minimum Closed  
position  
Failed  
Open to occupied minimum  
position  
Open to occupied standby  
Closed  
Present and economizer  
feasible  
Economizing: minimum position Economizing: between occupied  
Open and economizing only when  
to 100%  
standby minimum position to 100% unit operating, closed otherwise  
Present and economizer not  
feasible  
Open to occupied minimum  
position  
Open to occupied standby minimum Closed  
position  
Tracer Dehumidification (Tracer ZN520 Only)  
Dehumidification is possible when mechanical cooling is available, the heating capacity is located  
in the reheat position, and the space relative humidity setpoint is valid.The controller starts  
dehumidifying the space when the space humidity exceeds the humidity setpoint. The controller  
continues to dehumidify until the sensed humidity falls below the setpoint minus the relative  
humidity offset. The controller uses the cooling and reheat capacities simultaneously to  
dehumidify the space. While dehumidifying, the discharge air temperature is controlled to  
maintain the space temperature at the current setpoint.  
A typical scenario involves high humidity and high temperature load of the space. The controller  
setsthecoolingcapacityto100%andusesthereheatcapacity towarmthedischargeairtomaintain  
space temperature control. Dehumidification may be disabled via Tracer™ or configuration.  
Note: If the unit is in the unoccupied mode, the dehumidification routine will not operate.  
Data Sharing (Tracer ZN510 or ZN520 Only)  
Because this controller utilizes LonWorks® technology, the controller can send or receive data  
(setpoint, heat/cool mode, fan request, space temperature, etc.) to and from other controllers on  
the communication link, with or without the existence of a building automation system. This  
applies toapplications where multipleunit controllers shareasinglespacetemperaturesensor(for  
rooms with multiple units but only one zone sensor) for both standalone (with communication  
wiring between units) and building automation system applications. For this application you will  
need to use the Rover™ service tool. For more information on setup, refer to the Trane publication  
EMTX-IOP-2.  
Binary Inputs  
Tracer™ ZN controllers have the following binary inputs, factory-configured for the following  
functions:  
Binary input 1: low temperature detection (freezestat)  
Binary input 2: condensate overflow  
Binary input 3: occupancy/ generic  
Binary input 4: fan status (Tracer ZN520 only)  
Note: The generic binary input can be used with a Tracer Summit® building automation system  
only.  
BIP1: Low Temperature Detection Option  
The factory hard wires the low temperature detection sensor to binary input #1 (BIP1) on the  
Tracer™ ZN controller. The sensor defaults normally closed (N.C.), and will trip off the unit on a low  
BCXC-SVX01B-EN  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Start-Up  
temperature diagnostic when detecting low temperature. In addition, Tracer ZN controls unit  
devices as listed below:  
Fan: Off  
Valves: Open  
Electric heat: Off  
Damper: Closed  
Note: See the “Diagnostics” section for more information.  
BIP2: Condensate Overflow Detection Option  
The factory hard wires the condensate overflow sensor to binary input #2 (BIP2) on the Tracer™  
ZN controller. The sensor defaults normally closed (N.C.), and will trip off the unit on a condensate  
overflowdiagnosticifcondensate reachesthetrippoint. Inaddition, TracerZNcontrolsunitdevices  
as listed below:  
Fan: Off  
Valves: Closed  
Electric heat: Off  
BIP3: Occupancy Sensor  
Binary input #3 (BIP3) on Tracer™ ZN is available for field- wiring an occupancy sensor, such as a  
binary switch or a timeclock, to detect occupancy. The sensor can be either normally open or  
normally closed. Reference Table 27, p. 58.  
BIP4: Fan Status (ZN520 Only)  
Binary input #4 (BIP4) on Tracer™ ZN is available for sensor, such as a binary switch or a timeclock,  
to detect occupancy. The sensor defaults normally open but can be configured as either normally  
open or closed.  
Table 27. Binary input configurations  
Controller operation  
Binary input  
BI 1  
Description  
Configuration  
Contact closed  
Normal  
Contact open  
(a)  
(b)  
Low temperature detection  
NC  
NC  
NO  
NO  
NO  
Diagnostic  
BI 2  
Condensate overflow  
Normal  
Diagnostic  
BI 3  
Occupancy  
Unoccupied  
Occupied  
(c)  
BI 3  
Generic binary input  
Normal  
Normal  
BI 4  
Fan status  
Normal  
Diagnostic  
Notes:  
1. The occupancy binary input is for standalone unit controllers as an occupied/unoccupied input. However, when the  
controller receives a communicated occupied/unoccupied request, the communicated request has priority over the  
hardwired input.  
2. If the fan mode input is in the off position or the controller is in the unoccupied mode with the fan off, the fan status input  
will be open. A diagnostic will not be generated when the controller commands the fan off. A diagnostic will only be  
generated if the fan status input does not close after one minute from energizing a fan output or any time the input is  
open for one minute. The controller waits up to one minute after energizing a fan output to allow the differential pressure  
to build up across the fan.  
(a) During low temperature, condensate overflow, and fan status diagnostics, the Tracer™ ZN520 control disables all normal  
unit operation of the fan, valves, and damper.  
(b)The table below shows the controller’s response to low temperature detection, condensate overflow, and fan status diag-  
nostics.  
(c) The generic binary input does not affect unit operation. A building automation system reads this input as a generic binary  
input.  
Description  
BIP  
BI 1  
BI 2  
BI 4  
Fan  
Off  
Valve  
Open  
Electric heat  
Damper  
Closed  
Low temperature detection  
Condensate overflow  
Fan status  
Off  
Off  
Off  
Off  
Closed  
Closed  
Closed  
Off  
Closed  
58  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Start-Up  
Analog Inputs  
See Table 28 for a complete description of analog inputs.  
Table 28. Analog inputs  
Analog input  
Zone  
Terminal  
TB3-1  
Function  
Range  
ZN010  
ZN510  
ZN520  
Space temperature input  
Analog ground  
5° to 122°F (-15° to 50°C)  
N/A  
Ground  
Set  
TB3-2  
TB3-3  
Setpoint input  
40° to 115°F (4.4° to 46.1°C)  
4821 to 4919 W (Off)  
2297 to 2342 W (Auto)  
10593 to 10807 W (Low)  
15137 to 16463 W (High)  
N/A  
Fan  
TB3-4  
Fan switch input  
Ground  
TB3-6  
J3-1  
J3-2  
J3-3  
J3-4  
J3-6  
Analog ground  
Analog Input 1  
Entering water temperature  
Analog ground  
-40° to 212°F (-40° to 100°C)  
N/A  
Analog Input 2  
Analog Input 3  
Analog Input 4  
Discharge air temperature  
Analog ground  
-40° to 212°F (-40° to 100°C)  
N/A  
Fresh air temp/generic temp  
Analog ground  
-40° to 212°F (-40° to 100°C)  
N/A  
J3-7  
Universal Input  
Generic 4-20 ma  
Humidity  
0 – 100%  
0 – 100%  
0 – 2000ppm  
CO2  
Ground  
Ground  
Notes:  
J3-8  
J3-9  
Analog ground  
N/A  
N/A  
Analog ground  
1. The zone sensor, entering water temperature sensor, discharge air sensor, and the outside air temperature sensor are 10KW thermistors.  
2. Zone sensor: Wall mounted sensors include a thermistor soldered to the sensor’s circuit board.  
3. Changeover units include an entering water temperature sensor.  
Binary Outputs  
Binary outputs are configured to support the following:  
Two fan stages (when one or two fan stages are present, J1-2 can be configured as exhaust fan)  
One hydronic cooling stage  
One hydronic heating stage (dehumidification requires this to be in the reheat position)  
One DX cooling stage  
One or two-stage electric heat (dehumidification requires this to be in the reheat position)  
Face and bypass damper  
Modulating fresh air damper (Tracer™ ZN520 only)  
One-stage baseboard heat  
BCXC-SVX01B-EN  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Start-Up  
Table 29. Binary output configuration  
Binary output  
pin connection Configuration  
ZN010  
ZN510  
ZN520  
J1-1  
J1-2  
J1-3  
J1-4  
Fan high  
N/A  
Fan low  
(Key)  
Fan low  
(a)  
J1-5  
J1-6  
Main valve – open, or 2 pos. valve  
Aux. valve/elec. ht.  
Aux. valve – close  
J1-7  
2-pos. damper  
J1-9  
Heat valve – open, or 2 pos. valve, or first stage elec. ht.  
J1-10  
J1-11  
J1-12  
TB4-1  
TB4-2  
Notes:  
Heat valve – close or sec. stage elec. ht.  
Fresh air damper – open  
Fresh air damper – close  
Generic / baseboard heat output  
24 VAC  
1. If no valves are ordered with the unit, the factory default for Tracer™ ZN010 and ZN510 controllers are: main valve  
configured as normally closed and aux. valve configured as normally open.  
2. If the fresh air damper option is not ordered on the unit, 2-pos. damper is configured as none.  
3. Pin J1-2 can be configured for an exhaust fan with the use of Rover™ software. Factory default is none.  
(a) Two-pipe hydronic heat/cool changeover units use terminals J1-5 and J1-6 to control the primary valve for both heating and  
cooling. Units configured and applied as 2-pipe hydronic heat/cool changeover with electric heat, use terminals J1-5 and  
J1-6 to control the primary valve (for both cooling and heating), and terminals J1-9 and J1-10 for the electric heat stage.  
For those 2-pipe changeover units, electric heat will not energize while the hydronic supply is hot (5 or more degrees  
above the space temperature). In a 4-pipe application, pin J1-5 is for cooling and pin J1-6 for heating.  
Zone Sensor  
The Tracer™ ZN controller accepts the following zone sensor module inputs:  
Space temperature measurement (10kW thermistor)  
Local setpoint (either internal or external on the zone sensor module)  
Fan mode switch  
Timed override, using “on” and “cancel” buttons (Tracer ZN510 and ZN520 only)  
Communication jack (Tracer ZN510 and ZN520 only)  
Table 30. Zone sensor wiring connections  
TB1  
Description  
Space temperature  
Common  
1
2
3
4
5
6
Setpoint  
Fan mode  
Communications  
Communications  
Space Temperature Measurement  
Zone sensors use a 10kW thermistor to measure the space temperature. Wall-mounted zone  
sensors include a space temperature thermistor. Unit-mounted zone sensors have a return air  
sensor mounted in the units return airstream. If both a hardwired and communicated space  
60  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Start-Up  
temperature value exists, the controller ignores the hardwired space temperature input and uses  
the communicated value.  
Local Setpoint  
The zone sensor may be equipped with a thumbwheel for setpoint adjustment.  
Fan Mode Switch  
The zone sensor may be equipped with a fan mode switch. The fan mode switch offers selections  
of off, low, high, or auto.  
External Setpoint Adjustment  
Zone sensors with an external setpoint adjustment (1kW) provide the Tracer™ ZN controller with  
a local setpoint (50 to 85°F or 10 to 29.4°C). The external setpoint is exposed on the zone sensors  
front cover.  
When the hardwired setpoint adjustment is used to determine the setpoints, all unit setpoints are  
calculated based on the hardwired setpoint value, the configured setpoints, and the active mode  
of the controller. The hardwired setpoint is used with the controllers occupancy mode (occupied,  
occupied standby, or unoccupied), the heating or coolingmode, the temperature deadband values,  
and the heating and cooling setpoints (high and low limits) to determine the controllers active  
setpoint.  
When a building automation system or other controller communicates a setpoint to the controller,  
the controller ignores the hardwired setpoint input and uses the communicated value. The  
exception is the unoccupied mode, when the controller always uses the stored default unoccupied  
setpoints. After the controller completes all setpoint calculations, based on the requested setpoint,  
the occupancy mode, the heating and cooling mode, and other factors, the calculated setpoint is  
validated against the following setpoint limits:  
Heating setpoint high limit  
Heating setpoint low limit  
Cooling setpoint high limit  
Cooling setpoint low limit  
Note: Only units with ZN510 or ZN520 can receive a communicated setpoint from Tracer™ or  
other building automation system. However, Rover™ service software can communicate  
with all Tracer ZN controllers.  
These setpoint limits only apply to the occupied and occupied standby heating and cooling  
setpoints. These setpoint limits do not apply to the unoccupied heating and cooling setpoints  
stored in the controllers configuration.  
When the controller is in unoccupied mode, it always uses the stored unoccupied heating and  
cooling setpoints.The unit can also be configured to enable or disable the local (hardwired)  
setpoint. This parameter provides additional flexibility to allow you to apply communicated,  
hardwired, or default setpoints without making physical changes to the unit.  
Similar to hardwired setpoints, the effective setpoint value for a communicated setpoint is  
determined based on the stored default setpoints (which determines the occupied and occupied  
standby temperature deadbands) and the controllers occupancy mode.  
Fan Switch  
The zone sensor fan switch provides the controller with an occupied (and occupied standby) fan  
request signal (Off, Low, High, Auto). If the fan control request is communicated to the controller,  
the controller ignores the hardwired fan switch input and uses the communicated value. The zone  
sensor fanswitch inputcanbe enabledordisabledthrough configurationusingtheRoverservice  
tool. If the zone sensor switch is disabled, the controller resorts to its stored configuration default  
fan speeds for heating and cooling, unless the controller receives a communicated fan input.  
BCXC-SVX01B-EN  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up  
When the fan switch is in the off position, the controller does not control any unit capacity. The unit  
remainspoweredandalloutputsdrivetotheclosedposition. Uponalossofsignalonthefanspeed  
input, the controller reports a diagnostic and reverts to using the default fan speed.  
On/Cancel Buttons  
Momentarily pressing the on button during unoccupied mode places the controller in occupied  
bypass mode for 120 minutes. You can adjust the number of minutes in the unit controller  
configuration using Rover™ service tool. The controller remains in occupied bypass mode until the  
override time expires or until you press the Cancel button.  
Communication Jack  
Use the RJ-11 communication as the connection point from Rover™ service tool to the  
communication link—when the communication jack is wired to the communication link at the  
controller. By accessing the communication jack via Rover, you gain access to any controller on the  
link.  
Figure 14. Resistance temperature curve for the zone sensor, entering water temperature sensor,  
and discharge air sensor  
62  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Maintenance Procedures  
Perform the following maintenance procedures to ensure proper unit operation.  
Air Filters  
Always install filters with directional arrows pointing toward the fan.  
Fan Bearings  
Fan bearings are permanently sealed and lubricated and do not require additional lubrication.  
Fan Motors  
Inspect fan motors periodically for excessive vibration or temperature. Operating conditions will  
vary the frequency of inspection and lubrication. Motor lubrication instructions are on the motor  
tag or nameplate. If for some reason these instructions are not available, contact the motor  
manufacturer. Some motor manufacturers may not provide oil tubes on motors with permanently  
sealed bearings.  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects before servicing. Follow proper  
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to  
disconnect power before servicing could result in death or serious injury.  
Before lubricating the motor:  
1. Turn the motor off and disconnect power to the unit to ensure the motor doesn’t accidentally  
start.  
2. Use a No. 10 SAE, non-detergent automotive type oil. Do not over-oil.  
Sheave Alignment  
To prevent interference of the fan frame with the belt, make sure that the belt edge closes to the  
motor has the proper clearance from the fan frame as shown in Figure 15, p. 64.  
Align the fan and motor sheaves by using a straight–edge or taut string, as shown in Figure 16,  
p. 64. The straight-edge must be long enough to span the distance between the sheave outside  
edges.  
When the sheaves are aligned, the straight–edge will touch both sheaves at points A through D,  
as shown in Figure 16. For uneven width sheaves, place a string in the center groove of both  
BCXC-SVX01B-EN  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Maintenance  
sheaves and pull tight. Adjust sheaves and tighten the sheave set screws to the correct torques  
recommended in Table 31.  
Figure 15. Clearance recommendation to  
prevent fan frame and belt interface  
Figure 16. Correct sheave alignment  
Table 31. Recommended torques for tightening sheaves and bearing thrust collar  
Torque (in.-lb)  
Ft-lb  
12  
N-m  
16.3  
7.5  
Sheave setscrew  
Bearing thrust collar  
Fan wheel screw  
144  
66  
5.5  
12  
144  
16.3  
Fan Assembly Set Screws  
Check and adjust fan wheel, bearing, and sheave set screws whenever a component is removed  
or an adjustment is made. Refer to Table 31 for recommendations.  
Fan Belt Tension  
Proper belt tension is necessary to endure maximum bearing and drive component life and is  
based on fan brake horsepower requirements. Replace belt when frayed or worn.  
Fan belt tension should only be tight enough so the belt does not slip and maintains adequate  
airflow.  
Note: Check fan belt tension at least twice during the first days of new belt operation since there  
is a rapid decrease in tension until belts are run-in.  
Be careful not to over-tension fan belt. Excessive tension will reduce fan and motor bearing life,  
accelerate belt wear and possibly cause shaft failure. Clean the sheaves and belt with a dry cloth.  
Keep oil and grease away from the belt because they may cause belt deterioration and slippage.  
Trane does not recommend belt dressing.  
64  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Maintenance  
NOTICE  
Belt tension!  
Do not over-tension belts. Excessive belt tension will reduce fan and motor bearing life,  
accelerate belt wear, and could result in shaft failure.  
Table 32. BCHC/BCVC fan, filter, and mixing box general data  
Unit size  
12  
18  
24  
36  
54  
72  
90  
Nominal cfm  
400  
600  
800  
1200  
1800  
2400  
3000  
Air flow  
Minimum cfm  
Maximum cfm  
Fan data  
250  
500  
375  
675  
500  
750  
1125  
2400  
1500  
3000  
1875  
4000  
1000  
1600  
Fan wheel, in. (dia. x width)  
Maximum rpm  
Motor hp  
9.5 x 4.5 9.5 x 4.5  
9.5 x 9.5  
1800  
9.5 x 9.5 12.6 x 9.5 12.6 x 9.5 12.6 x 9.5  
2300  
2300  
1800  
1500  
1500  
1500  
0.33–1.0  
0.33–1.0  
0.33–1.0  
0.33–1.5  
0.33–2.0  
0.33–3.0  
0.33–3.0  
Unit flat filter  
Qty. - size, in.  
1 - 12 x 24 1 - 12 x 24 1 - 16 x 25 2 - 16 x 20 2 - 20 x 20 1 - 20 x 20 3 - 16 x 25  
1 - 20 x 25  
Area, sq. ft  
2.000  
200  
2.000  
300  
2.778  
288  
4.444  
270  
5.556  
324  
6.250  
384  
8.333  
360  
Velocity, ft/min.  
Angle filter  
Qty. - size, in.  
Area, sq. ft  
2 - 12 x 24 2 - 12 x 24 2 - 12 x 24 2 - 20 x 20 4 - 16 x 20 4 - 16 x 20 4 - 20 x 20  
4.000  
100  
4.000  
150  
4.000  
200  
5.556  
216  
8.889  
203  
8.889  
270  
11.111  
270  
Velocity, ft/min.  
Bottom / top access filter box  
Qty. - size, in.  
1 - 12 x 20 1 - 12 x 24 1 - 16 x 25 1 - 16 x 20 1 - 16 x 20 1 - 20 x 25 2 - 16 x 25  
1 - 16 x 16 1 - 20 x 20 1 - 20 x 20 1 - 14 x 25  
Area, sq. ft  
1.700  
240  
2.000  
300  
2.800  
288  
4.000  
300  
5.000  
360  
6.300  
384  
8.000  
375  
Velocity, ft/min.  
Mixing box  
Damper opening width, in.  
Damper opening height, in.  
Area, sq. ft  
15.5  
7
19.5  
7
19.5  
7
31.5  
7
31.5  
12.75  
2.789  
645  
31.5  
12.75  
2.789  
861  
31.5  
12.75  
2.789  
1076  
0.753  
531  
0.948  
633  
0.948  
844  
1.531  
784  
Velocity, ft/min.  
Note: Minimum air flow limits apply to units with hot water or electric heat only. There is no minimum airflow limit on cooling  
on units. Maximum airflow limits are to help prevent moisture carryover.  
Table 33. BCBH/BCVC valve package waterflow limits  
Tube size (in.)  
gpm  
8.6  
1/2  
3/4  
1
19.3  
34.3  
53.5  
1-1/4  
BCXC-SVX01B-EN  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Table 34. BCHC/BCVC coil general data  
Unit size  
12  
18  
24  
36  
54  
72  
90  
Nominal cfm  
400  
600  
800  
1200  
1800  
2400  
3000  
Hydronic & DX coil data  
2
Area - ft  
0.89  
8
1.11  
8
1.67  
12  
2.67  
12  
4.00  
18  
5.00  
18  
6.67  
24  
(a),(b)  
Width - in.  
(c)  
Length - in.  
16  
20  
20  
32  
32  
40  
40  
Velocity - ft/min.  
450  
540  
480  
450  
450  
480  
450  
Hydronic coil data  
• High-capacity  
2
Area - ft  
0.89  
8
1.11  
8
1.67  
12  
2.67  
12  
3.89  
17.5  
32  
4.86  
17.5  
40  
6.25  
22.5  
40  
(a),(d)  
Width - in.  
Length - in.  
16  
20  
20  
32  
Velocity - ft/min.  
450  
540  
480  
450  
463  
494  
480  
1-row coil  
(e)  
Minimum gpm  
1.0  
5.2  
4.4  
5.1  
19.4  
1.0  
5.2  
5.2  
6.0  
22.2  
1.0  
5.2  
6.6  
7.8  
33.2  
1.0  
6.1  
6.1  
7.9  
(f)  
Maximum gpm  
5.2  
32.6  
17.6  
22.4  
132.9  
32.6  
20.4  
26.0  
155.1  
42.0  
25.8  
32.9  
196.6  
Dry coil weight - lb  
Wet coil weight - lb  
9.3  
11.0  
47.1  
3
Internal volume - in  
2-row coil  
• High-capacity  
Minimum gpm  
1.0  
5.2  
5.9  
7.2  
36.0  
1.0  
5.2  
7.0  
8.4  
38.8  
2.0  
2.0  
6.1  
6.1  
7.9  
Maximum gpm  
10.4  
9.9  
10.4  
14.1  
17.6  
96.9  
32.6  
27.2  
36.1  
246.5  
32.6  
32.1  
42.5  
288.0  
42.0  
39.4  
52.6  
365.5  
Dry coil weight - lb  
Wet coil weight - lb (kg)  
12.3  
66.5  
3
Internal volume - in  
4-row coil  
• Standard capacity  
Minimum gpm  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
8.8  
8.8  
11.7  
62.6  
58.5  
77.0  
512.3  
Maximum gpm  
47.0  
37.2  
48.3  
307.4  
47.0  
44.5  
57.7  
365.5  
(g)  
Dry coil weight - lb  
Wet coil weight - lb  
Internal volume - in  
• High-capacity  
Minimum gpm  
2.0  
2.0  
10.4  
2.9  
2.9  
6.1  
6.1  
7.9  
Maximum gpm  
10.4  
10.5  
13.1  
15.7  
17.7  
22.5  
132.9  
15.7  
25.5  
32.5  
193.8  
32.6  
47.0  
62.7  
433.0  
32.6  
56.3  
74.9  
516.7  
42.0  
73.1  
97.9  
688.3  
Dry coil weight - lb  
Wet coil weight - lb  
12.4  
15.5  
3
Internal volume - in  
72.0 85.8  
66  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Table 34. BCHC/BCVC coil general data (continued)  
Unit size  
12  
18  
24  
36  
54  
72  
90  
Nominal cfm  
6-row coil  
400  
600  
800  
1200  
1800  
2400  
3000  
• Standard capacity  
Minimum gpm  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
8.8  
8.8  
11.7  
Maximum gpm  
47.0  
52.4  
68.1  
434.8  
47.0  
63.1  
82.0  
523.4  
62.6  
Dry coil weight - lb  
82.7  
Wet coil weight - lb  
108.7  
720.0  
Internal volume - in  
• High-capacity  
Minimum gpm  
2.0  
2.0  
2.9  
2.9  
6.1  
6.1  
7.9  
Maximum gpm  
10.4  
14.6  
18.2  
99.7  
10.4  
17.4  
21.8  
121.8  
15.7  
24.7  
31.5  
188.3  
15.7  
36.1  
46.1  
276.9  
32.6  
65.4  
87.8  
620.4  
32.6  
78.6  
105.6  
745.9  
42.0  
Dry coil weight - lb  
Wet coil weight - lb  
Internal volume - in  
• Steam coil data  
101.5  
137.0  
983.1  
3
2
Area - ft  
0.71  
6
0.88  
6
1.75  
12  
2.75  
12  
4.13  
18  
5.13  
18  
6.83  
24  
Width - in.  
Length - in.  
17  
26  
3
21  
21  
33  
33  
41  
41  
Velocity - ft/min.  
25  
18  
17  
17  
16  
16  
1-row coil  
3
5
5
14  
14  
9
Minimum steam press - psig 2.0  
Maximum steam press - psig 15.0  
2.0  
15.0  
18.7  
20.4  
47.7  
2.0  
15.0  
32.5  
36.0  
95.3  
2.0  
2.0  
2.0  
2.0  
15.0  
41.1  
45.8  
130.8  
15.0  
57.4  
64.5  
196.1  
15.0  
64.8  
73.2  
231.6  
15.0  
84.9  
96.1  
308.7  
Dry coil weight - lb  
Wet coil weight - lb  
Internal volume - in  
16.7  
18.2  
41.7  
3
(a) Coil width = Length in the direction of a coil header, typically vertical.  
(b)Hydronic and DX coil data” width dimensions apply only to DX coils (all unit sizes), 1-row standard ca-  
pacity hydronic coils (unit sizes 012 through 036), and 4- and 6-row standard capacity hydronic coils (54  
through 90).  
(c) Coil length = Length of coil in direction of the coil tubes, typically horizontal and perpendicular to airflow.  
(d)High-capacity hydronic coil data” width dimensions apply only to 1-row standard capacity hydronic coils  
(unit sizes 054 through 090) and 2-, 4-, and 6-row high capacity hydronic coils (all unit sizes).  
(e) The minimum waterflow at 1.5 fps tubeside velocity is to ensure the coil self-vents properly. There is no  
minimum waterflow limit for coils that do not require self venting.  
(f) Maximum gpm limits are to prevent erosion and noise problems.  
(g)DX coil height and width dimensions are same as comparable hydronic coils. Four- and six-row DX coil dry  
weight dimensions are same as comparable 4- and 6-row hydronic coils. A 3-row DX coil dry weight is 25%  
less than a comparable 4-row hydronic coil. Internal volumes are approximately 6% less than comparable  
hydronic coils.  
BCXC-SVX01B-EN  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Maintenance  
Table 35. Drive data  
Fan rpm range  
Motor speed  
Motor sheave  
Browning Trane  
Fan sheave  
Browning Trane  
Belt  
Browning  
Unit Motor  
1750  
1450 Drive  
size  
watts  
HP  
Trane  
(60 Hz) (50 Hz) letter  
12, 18 186–1119 1/3 to 1-1/2 1VL40x5/8 X10090082090 AK74x3/4 X10070173270  
A41  
A39  
A37  
A36  
A35  
A34  
A34  
A53  
A48  
A46  
A45  
A43  
A41  
A39  
A38  
A37  
A36  
A48  
A46  
A45  
A43  
A41  
A40  
A53  
A50  
A48  
A46  
A45  
A43  
A41  
A40  
A40  
A51  
A49  
A48  
A46  
A45  
A43  
A59  
A56  
A53  
A53  
A50  
A49  
A48  
A46  
A46  
A56  
A56  
A53  
A53  
A50  
A49  
X10200254160 619–878  
X10200254140 727–109  
513–727  
602–853  
D
E
F
G
H
J
K
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
T
A
B
C
D
E
F
AK64x3/4 X10070173030  
AK54x3/4 X10070172C40  
AK46x3/4 X10070172A20  
AK39x3/4 X10070172700  
AK34x3/4 X10070172640  
AK28x3/4 X10070172440  
X10200254120 879–1245 728–1031  
X10200254110 1000–1417 829–1174  
X10200254100 1200–1700 994–1409  
X10200254090 1313–1859 1088–1541  
X10200254090 1615–2288 1338–1896  
X10200254280 390–552  
X10200254230 478–678  
X10200254210 540–765  
X10200254200 619–878  
X10200254180 727–1029 602–853  
X10200254160 879–1245 728–1031  
X10200254140 1000–1417 829–1174  
X10200254130 1200–1700 994–1409  
X10200254120 1313–1859 1088–1541  
X10200254110 1615–2288 1338–1896  
X10200254230 678–877  
X10200254210 765–990  
X10200254200 878–1136 727–941  
X10200254180 1029–1332 853–1104  
X10200254160 1245–1611 1031–1335  
X10200254150 1174–1519  
X10200254280 390–552  
X10200254250 478–678  
X10200254230 540–765  
X10200254210 619–878  
X10200254200 727–1029 602–853  
X10200254180 879–1245 728–1031  
X10200254160 1000–1417 829–1174  
X10200254150 1200–1700 994–1409  
X10200254150 1313–1859 1088–1541  
X10200254260 678–877  
X10200254240 765–990  
X10200254230 878–1136 727–941  
X10200254210 1029–1332 853–1104  
X10200254200 1245–1611 1031–1335  
X10200254180 1174–1519  
X10200254340 390–552  
X10200254310 478–678  
X10200254280 540–765  
X10200254280 619–878  
X10200254250 727–1029 602–853  
X10200254240 879–1245 728–1031  
X10200254230 1000–1417 829–1174  
X10200254210 1200–1700 994–1409  
X10200254210 1313–1859 1088–1541  
24, 36 186–1119 1/3 to 1-1/2 1VL40x5/8 X10090082090 AK114x3/4 X10070173A30  
AK94x3/4 X10070173630  
323–457  
396–562  
447–634  
513–727  
AK84x3/4 X10070173450  
AK74x3/4 X10070173270  
AK64x3/4 X10070173030  
AK54x3/4 X10070172C40  
AK46x3/4 X10070172A20  
AK39x3/4 X10070172700  
AK34x3/4 X10070172640  
AK28x3/4 X10070172440  
1492–2238 2 and 3(a)  
1VM50x5/8 X10090082170 AK94x3/4 X10070173630  
1VM50x7/8 X10090082190 AK84x3/4 X10070173450  
AK74x3/4 X10070173270  
562–727  
634–820  
AK64x3/4 X10070173030  
AK54x3/4 X10070172C40  
AK46x3/4 X10070172A20  
54, 72 186–1119 1/3 to 1-1/2 1VL40x5/8 X10090082090 AK114x3/4 X10070173A30  
AK94x3/4 X10070173630  
323–457  
396–562  
447–634  
513–727  
AK84x3/4 X10070173450  
AK74x3/4 X10070173270  
AK64x3/4 X10070173030  
AK54x3/4 X10070172C40  
AK46x3/4 X10070172A20  
AK39x3/4 X10070172700  
AK34x3/4 X10070172640  
G
H
J
1492–2238 2 and 3(a) 1VM50x5/8 X10090082170 AK94x3/4 X10070173630  
562–727  
634–820  
L
1VM50x7/8 X10090082190 AK84x3/4 X10070173450  
AK74x3/4 X10070173270  
M
N
P
AK64x3/4 X10070173030  
AK54x3/4 X10070172C40  
AK46x3/4 X10070172A20  
R
T
A
B
C
D
E
F
90  
186–1119 1/3 to 1 1/2 1VL40x5/8 X10090082090 AK114x3/4 X10070173A30  
AK94x3/4 X10070173630  
323–457  
396–562  
447–634  
513–727  
AK84x3/4 X10070173450  
AK74x3/4 X10070173270  
AK64x3/4 X10070173030  
AK54x3/4 X10070172C40  
AK46x3/4 X10070172A20  
AK39x3/4 X10070172700  
AK34x3/4 X10070172640  
G
H
J
1492–2238 2 and 3(a) 1VM50 X 5/8 X10090082170 AK94x3/4 X10070173630  
X10200254310 678–877  
X10200254310 765–990  
X10200254280 878–1136 727–941  
X10200254280 1029–1332 853–1104  
X10200254250 1245–1611 1031–1335  
X10200254240 1174–1519  
562–727  
634–820  
L
1VM50 X 7/8 X10090082190 AK84x3/4 X10070173450  
AK74x3/4 X10070173270  
M
N
P
R
T
AK64x3/4 X10070173030  
AK54x3/4 X10070172C40  
AK46x3/4 X10070172A20  
(a) 2 hp 60 Hz motors have 5/8” bore sheaves. 2 hp 50 Hz motors have 7/8” bore sheaves. All 3 hp motors have 7/8” bore sheaves with the exception of  
575V, which has the 5/8” bore.  
68  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Maintenance  
Coil Maintenance  
Keep coils clean to maintain maximum performance. For operation at its highest efficiency, clean  
the coil often during periods of high demand or when dirty conditions prevail. Clean the coil a  
minimum of once per year to prevent dirt buildup in the coil fins, where it may not be visible.  
Remove large debris from the coils and straighten fins before cleaning. Remove filters before  
cleaning. Rinse coils thoroughly after cleaning. Clean the coil fins using one of these methods:  
steam with detergent  
hot water spray and detergent  
commercially available chemical coil cleaner  
NOTICE  
Potential unit damage from coil cleaners!  
Do not use acidic chemical coil cleaners. Also, do not use alkaline chemical coil cleaners with a  
pH value greater then 8.5 (after mixing) without using an aluminum corrosion inhibitor in the  
cleaning solution. Using these types of cleaners could result in equipment damage.  
Inspecting and Cleaning Coils  
Coils become externally fouled as a result of normal operation. Dirt on the coil surface reduces its  
ability to transfer heat and can cause comfort problems, increased airflow resistance and thus  
increased operating energy costs. If the coil surface dirt becomes wet, which commonly occurs  
with cooling coils, microbial growth (mold) may result, causing unpleasant odors and serious  
health-related indoor air quality problems.  
Inspect coils at least every six months or more frequently as dictated by operating experience.  
Cleaning frequently is dependent upon system operating hours, filter maintenance, and efficiency  
and dirt load. Follow is the suggested method below:  
Steam, Hot Water, and Cooling Coil Cleaning Procedure  
1. Don the appropriate personal protective equipment (PPE).  
2. Gain access to both sides of the coil section.  
3. Use a soft brush to remove loose debris from both sides of the coil.  
4. Use a steam cleaning machine, starting from the top of the coil and working downward. Clean  
the leaving air side of the coil first, then the entering air side.  
Use a block-off to prevent steam from blowing through the coil and into a dry section of the unit.  
5. Repeat Step 4 as necessary. Confirm that the drain line is open following completion of the  
cleaning process.  
6. Allow the unit to dry thoroughly before putting the system back into service.  
7. Straighten any coil fins that may be damaged with a fin rake.  
8. Replace all panels and parts and restore electrical power to the unit.  
9. Ensure that contaminated material doesnot contact other areas of the unit or building. Properly  
dispose of all contaminated materials and cleaning solutions.  
ƽ WARNING  
Hazardous chemicals!  
Coil cleaning agents can be either acidic or highly alkaline. Handle chemical carefully. Proper  
handling should include goggles or face shield, chemical resistant gloves, boots, apron or suit as  
required. For personal safety refer to the cleaning agent manufacturer’s Materials Safety Data  
Sheet and follow all recommended safe handling practices. Failure to follow all safety  
instructions could result in death or serious injury.  
BCXC-SVX01B-EN  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Maintenance  
Winterizing the Coil  
Make provisions to drain coils that are not in use, especially when subjected to freezing  
temperatures.  
To drain the coil, first blow out the coil with compressed air. Next, fill and drain the tubes with full-  
strength ethylene glycol several times. Then drain the coil as completely as possible.  
NOTICE  
Potential coil-freeze condition!  
Make provisions to drain the coil when not in use to prevent coil freeze-up. Failure to follow this  
procedure could result in equipment damage.  
Periodic Maintenance Checklists  
Monthly Checklist  
Thefollowing check list providesthe recommended maintenance schedule tokeeptheunit running  
efficiently.  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects before servicing. Follow proper  
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to  
disconnect power before servicing could result in death or serious injury.  
ƽ WARNING  
Rotating parts!  
Secure drive sheaves to ensure motor cannot freewheel. Failure to follow this procedure could  
result in death, personal injury or equipment damage.  
1. Inspect unit air filters. Clean or replace if airflow is blocked or if filters are dirty.  
2. Check the condition and tension of fan belts. Adjust tension if belts are floppy or squeal  
continually. Replace worn or fraying belts in matched sets.  
Note: Check and adjustbelttensionatleast twice daily the first days of new belt operation. Belt  
tension will rapidly decrease until the belts are run in.  
3. Re-lubricate motor bearings, if motor is fitted with oil tubes and operating conditions include  
moist or dirty air, continuous duty and/or high temperatures.  
Semi-Annual Maintenance  
1. Verify the fan motor is properly lubricated. Follow lubrication recommendations on the motor  
tag or nameplate. Contact the motor manufacturer for more information.  
2. With power disconnected, manually rotate the fan wheel to check for obstructions in the  
housing or interference with fan blades. Remove any obstructions and debris.  
3. Check the fan assembly sheave alignment. Tighten set screws to their proper torques.  
4. Check fan belt tension. Adjust if belt is slipping. Replace if belt is worn or frayed.  
5. Inspect the coils for dirt build-up. Clean fins if airflow is clogged.  
Annual Maintenance  
Check and tighten all set screws, bolts, locking collars and sheaves.  
1. Inspect, clean, and tighten all electrical connections and wiring.  
70  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Maintenance  
2. Visually inspect the entire unit casing for chips or corrosion. Remove rust or corrosion and  
repaint surfaces.  
3. Clean fan wheels and fan shaft. Remove any rust from the fan shaft with an emery cloth and  
recoat with L.P.S. 3 or equivalent.  
4. Inspect the drainpan for sludge or other foreign material. Clear the drain openings and drain  
line to ensure adequate flow.  
5. Rotate the fan wheel and check for obstructions in the fan housing. The wheel should not rub  
on the fan housing or cutoff. Adjust to center if necessary and tighten the wheel set screws per  
the torque recommendations in Table 31, p. 64.  
6. Examine flex connector for cracks or leaks.  
7. Repair or replace any damaged duct material.  
BCXC-SVX01B-EN  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Diagnostics  
Troubleshooting  
LED Activity  
Red Service LED  
The red LED normally indicates if the unit controller is operating properly or not. Refer to Table 36.  
Table 36. Red service LED activity‘  
LED activity  
Description  
Off continuously after power is applied to the controller. Normal operation  
On continuously, even when power is first applied to the Someone is pressing the Service button or the controller  
controller.  
has failed.  
LED flashes about once every second.  
Uninstall (normal controller mode). Use Rover™ service  
tool to restore normal unit operation.  
Black Service push button.  
Use the Service button to install the Tracer™ ZN520  
controller in a communication network.  
Green Status LED  
The green LED normally indicates whether the controller is powered on (24 VAC supplied). Refer  
to Table 37.  
Table 37. Green status LED activity  
Green LED activity  
On continuously  
Description  
Power on (normal operation).  
The controller is in manual output test mode.  
No diagnostics present.  
Blinks (one blink)  
The controller is in manual output test mode.  
One or more diagnostics are present.  
Blinks (two blinks)  
(a)  
LED blinks (1/4 second on, 1/4 second, off for 10 seconds)  
LED off  
Wink mode.  
Power is off.  
Controller failure.  
Test button is pressed.  
(a) The Wink feature allows you to identify a controller. By sending a request from Rover™ service tool, you can request the  
controller to wink (blink on and off as a notification that the controller received the signal). The green LED blinks (1/4  
second on, 1/4 second off for 10 seconds) during Wink mode.  
Yellow Comm LED  
The yellow comm LED blinks at the rate the controller receives communication. The yellow LED  
does not blink when the controller is transmitting communication data. Refer to Table 38.  
Table 38. Yellow comm LED activity  
LED activity  
Description  
Off continuously  
The controller is not detecting any communication.  
(Normal for standalone applications.)  
LED blinks or flickers  
LED on continuously  
The controller detects communication.  
(Normal for communicating applications, including data sharing.)  
Abnormal condition or extremely high traffic on the link.  
High traffic on the link.  
Note: If the service push button is held down for more than 15 seconds, the Tracer™ ZN controller  
will uninstall itself from the ICS communication network and shut down all unit operation.  
This mode is indicated by the red Service LED flashing once every second. See the Red  
72  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Diagnostics  
Service LED section. Use Rover™ service tool to restore the unit to normal operation. Refer  
to the Rover product literature for more information.  
Manual Output Test  
The purpose of the manual output test sequence is to verify output and end device operation. Use  
the manual output test to:  
Verify output wiring and operation without using Rover™, service tool.  
Force the water valve to open and balance the hydronic system.  
Note: The manual output test is not an automatic cycle. You must press the Test button to proceed  
through each step.  
The controller observes all diagnostics that occur during the test sequence. Although an automatic  
diagnostic reset sequence exists as part of the controllers normal operation, the automatic  
diagnostic reset feature is not active during the test sequence.  
If left in an individual test step, the controller remains in test mode for 60 minutes and then exits  
to normal operation.  
Many service calls are due to unit diagnostics. The test sequence resets unit diagnostics and  
attemptstorestorenormalunitoperationpriorto testingtheoutputs. Ifthediagnosticsremainafter  
a reset, the STATUS LED indicates the diagnostic condition is still present (two blinks).  
Manual Output Test Procedure  
Follow the procedure below to test the Tracer™ ZN010, ZN510, or ZN520 controller.  
1. Press and hold the Test button for at least two seconds (not exceeding five seconds), and then  
release, to start the test mode.  
2. The test sequence will turn off all outputs and then attempt to clear all diagnostics.  
3. Press the Test button several more times (no more than once per second) to advance through  
the test sequence.  
The outputs are not subject to minimum times during the test sequence. However, the test  
sequence only permits one step per second which limits minimum output time.  
The green LED is turned off when the Test button is pressed. To begin the manual output test mode,  
press and hold the Test button (turning off the green LED) for at least two seconds. The green LED  
will begin to blink, indicating the controller is in test mode.  
BCXC-SVX01B-EN  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Diagnostics  
Table 39. Tracer ZN010 and ZN510 test sequence for 1-heat/1-cool configurations  
(a)  
Fan  
Cool output  
Heat output  
Damper  
J1-  
Steps  
J1-1, J1-3  
Off  
J1-  
Off  
Off  
Off  
Off  
On  
J1-  
Off  
Off  
Off  
Off  
Off  
On  
Off  
1. Off  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
Open  
2. Fan high  
3. Exhaust fan  
4. Fan  
High  
(b)  
Low  
High  
High  
5. Cool  
6. Heat  
Off  
Off  
(c)  
7. Two-position damper  
8. Exit  
High  
(d)  
Note: The 2-position damper energizes during this step if the controller is configured for a 2-position damper.  
(a) At the beginning of step 2, the controller attempts to clear all diagnostics.  
(b)Tracer™ ZN010 and ZN510 have a binary output default as “none” on J1-X from the factory. If the unit has a 2-speed fan,  
step 3 will energize the low fan speed. If the unit has a single speed fan, step 3 will continue to energize the high fan speed.  
This binary output can be reconfigured as an exhaust fan, with the use of Rover™ software.  
(c) After the fresh air damper step, the test sequence performs the exit step.This initiates a reset and attempts to return the  
controller to normal operation.  
(d)For all 1-heat/1-cool applications including 2-pipe changeover, the cooling and heat test stage energize. This occurs even  
though during normal 2-pipe changeover operation binary output controls the unit valve for both cooling and heating.  
Table 40. Tracer ZN520 test sequence  
Main  
Electric heat or Fresh air  
Fan  
J1-2  
valve  
aux. valve  
damper  
Generic/baseboard heat  
Step  
J1-1  
J1-3  
J1-5  
J1-6  
J1-9  
J1-10  
J1-11  
J1-12  
TB4-1  
(a)  
1. Off  
Off  
Off  
Off  
Off  
On  
Off  
aux: on  
Off  
On  
Off  
EH: off  
(b)  
2. Fan high  
High  
Off  
Off  
Off  
Off  
Low  
Off  
Off  
Off  
Off  
Off  
Off  
On  
Off  
Off  
Off  
Off  
Off  
Off  
On  
Off  
Off  
Off  
Off  
Off  
On  
On  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
(c)  
3.  
4. Fan low  
Off  
Off  
Off  
Off  
Exh  
5. Main open  
High  
High  
6. Main close, EH1 on  
7. Aux. open  
(d)  
High  
EH1 on  
8. Aux. close, damper open  
High  
Off  
Off  
Off  
Off  
Off  
On  
On  
Off  
Off  
EH1 off  
EH2 on  
9. Damper close  
High  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
On  
Off  
Off  
On  
10. Generic/baseboard heat energized High  
(e)  
11. Exit  
Exit  
(a) Upon entering manual output test mode, the controller turns off all fan and electric heat outputs and drives.  
(b)At the beginning of step 2, the controller attempts to clear all diagnostics.  
(c) The low fan speed output energizes at step 3. If the unit is configured for a 1 speed fan, the fan remains on high speed at step 3.  
(d)If the unit is configured for a 1- or 2-speed fan, and BOP2 is configured for an exhaust fan, the exhaust fan output energizes on step 7. The exhaust  
fan output is shared with medium speed.  
(e) After step 10, the test sequence performs an exit. This initiates a reset and attempts to return the controller to normal operation.  
Diagnostics  
Translating Multiple Diagnostics  
Thecontrollersenses andrecords each diagnostic independently of otherdiagnostics. It is possible  
tohavemultiplediagnosticspresentsimultaneously. Thediagnosticsarereportedintheorderthey  
occur.  
Possible diagnostics include:  
74  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Diagnostics  
Low temperature detection  
Condensate overflow  
Low air flow - fan status  
Discharge air temp limit  
Space temperature failure  
1
Entering water temp failure  
Discharge air temp failure  
Outdoor air temp failure  
Local setpoint failure  
Local fan mode failure  
CO sensor failure  
2
Generic AIP failure  
Humidity input failure  
Defrosting compressor lockout  
Maintenance required  
Invalid Unit Configuration  
Generic temperature failure  
Discharge air low limit  
Resetting Diagnostics  
There are seven ways to reset unit diagnostics:  
1. Automatically by the controller  
2. By initiating a manual output test at the controller  
3. By cycling power to the controller  
4. By using a building automation system (Tracer™ ZN510 or ZN520 only)  
5. By using the Rover™ service tool  
6. By using any other communicating device able to access the controllers diagnostic reset input  
(Tracer ZN510 or ZN520 only)  
7. By cycling the fan switch from off to any speed setting (Tracer ZN520 only)  
Automatic Reset by the Controller  
The controller includes an automatic diagnostic reset function which attempts to automatically  
restore the unit when a low temperature diagnostic occurs.  
Note: The controller implements the automatic diagnostic reset function only once every 24  
hours. For the controller to increment the 24 hour timer, you must maintain power to the  
controller. Cycling power resets all timers and counters.  
After the controller detects the first low temperature diagnostic, the unit waits 30 minutes before  
invoking the automatic diagnostic reset function. The automatic diagnostic reset function clears  
the special diagnostic and attempts to restore the controller to normal operation. The controller  
resumes normal operation until another diagnostic occurs.  
Note: The automatic diagnostic reset function does not operate during the manual output test  
sequence.  
If a special diagnostic occurs within 24 hours after an automatic diagnostic reset, the controller  
must be manually reset. Other possible methods of resetting diagnostics are described in the  
sections that follow.  
1
Non-latching diagnostics automatically reset when the input is present and valid.  
BCXC-SVX01B-EN  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Diagnostics  
Manual Output Test  
You can use the Test button on the controller either during installation to verify proper end device  
operation or during troubleshooting. When you press the Test button, the controller exercises all  
outputs in a predefined sequence. The first and last outputs of the sequence reset the controller  
diagnostics. See p. 73 for more information about the manual output test.  
Cycling Power  
When someone turns off the controllers 24 VAC power, then re-applies power, the unit cycles  
through a power up sequence. By default, the controller attempts to reset all diagnostics at power  
up. Diagnostics present at power-up and those that occur after power-up are handled according to  
the defined unit diagnostics sequences (see Table 41, p. 77 and Table 42, p. 77).  
Building Automation System (Tracer ZN510 or ZN520 Only)  
Some building automation systems can reset diagnostics in the Tracer™ ZN510 or ZN520  
controller. For more complete information, refer to the product literature for the building  
automation system.  
Rover Service Tool  
Rover™ service tool can reset diagnostics in the Tracer™ ZN520 controller. For more complete  
information, refer to the Rover Installation, Operation, and Programming manual.  
Diagnostic Reset (Tracer ZN510 or ZN520 Only)  
Any device that can communicate the network variable nviRequest (enumeration “clear_alarm”)  
can reset diagnostics in the Tracer™ ZN510 or ZN520 controller. The controller also attempts to  
reset diagnostics whenever power is cycled.  
Cycling the Fan Switch (Tracer ZN520 Only)  
If the user cycles the fan speed switch from off to any speed, the controller resets all diagnostics.  
Diagnostics may recur immediately if the problem still exists.  
The green LED normally indicates whether or not the controller is powered on (24 VAC).  
Trane’s Service Tool, Rover  
Rover™, Trane’s service tool, can reset diagnostics present in the controller. For complete  
information about Rover, refer to Trane publication EMTX-IOP-2 Rover Installation, Operation and  
Programming Guide.  
Alarm Reset  
Any device that can communicate alarm reset information can reset diagnostics present in the  
controller.  
76  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Diagnostics  
Table 41. Tracer ZN010 and ZN510 controller diagnostics  
Diagnostic  
Latching  
No  
Fan  
Valves  
No action  
Closed  
Electric heat  
No action  
Off  
Damper  
No action  
Closed  
Auxiliary temperature failure  
Condensate overflow detection  
Entering water temperature  
Fan mode failure  
Enabled  
Off  
Yes  
No  
Enabled  
Enabled  
Disabled  
Off  
Enabled  
Enabled  
Disabled  
Open  
Enabled  
Enabled  
Disabled  
Off  
Enabled  
Enabled  
Disabled  
Closed  
No  
Invalid unit configuration failure  
Low temperature detection  
Maintenance required  
Setpoint  
Yes  
Yes  
Yes  
Enabled  
Enabled  
Off  
No action  
No action  
Closed  
No action  
No action  
Off  
No action  
No action  
Closed  
No  
Zone temperature failure  
Notes:  
No  
1. Priority Level: Diagnostics are listed in order from highest to lowest priority. The controller senses and records each  
diagnostic independently of other diagnostics. It is possible to have multiple diagnostics present simultaneously. The  
diagnostics affect unit operation according to priority level.  
2. Latching: A latching diagnostic requires a manual reset of the controller; while a non-latching diagnostic automatically  
resets when the input is present and valid.  
3. Enabled: End device is allowed to run if there is a call for it to run.  
4. Disabled: End device is not allowed to run even if there is a call for it to run.  
5. No Action: The diagnostic has no affect on the end device.  
Table 42. Tracer ZN520 diagnostics  
(a)  
Diagnostic  
Fan Other outputs  
Condensate overflow  
Off  
Off  
Off  
Off  
On  
Off  
Off  
On  
Valves closed, fresh air damper closed, electric heat off, baseboard heat off  
Valves open, fresh air damper closed, electric heat off, baseboard heat off  
Valves closed, fresh air damper closed, electric heat off, baseboard heat off  
Valves closed, fresh air damper closed, electric heat off, baseboard heat off  
Low temperature detection  
Low air flow - fan failure  
Space temperature failure  
Entering water temperature failure  
Discharge air temperature low limit  
Discharge air temperature failure  
Fresh air temperature failure  
(b)  
Valves enabled , fresh air damper enabled , electric heat enabled , baseboard heat off  
Valves open, fresh air damper closed, electric heat off, baseboard heat off  
Valves closed, fresh air damper closed, electric heat off, baseboard heat off  
(c)  
Valves enabled, fresh air damper minimum position , electric heat enabled, baseboard heat  
enabled  
Relative humidity failure  
Generic 4-20ma failure  
On  
On  
On  
On  
On  
On  
Off  
On  
Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled  
Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled  
Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled  
Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled  
Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled  
Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled  
Valves disabled, fresh air damper disabled, electric heat disabled, baseboard heat disabled  
Valves enabled, fresh air damper enabled, electric heat enabled  
CO input failure  
2
Maintenance required  
Local fan mode failure  
Local setpoint failure  
Invalid unit configuration  
Normal - power up  
(a) The generic binary output (TB4-1, TB4-2) state is unaffected by all unit diagnostics.  
(b)When the entering water temperature is required but not present, the Tracer™ ZN520 controller generates a diagnostic to indicate the sensor loss  
condition. The controller automatically clears the diagnostic once a valid entering water temperature value is present (non-latching diagnostic). When  
theentering water temperature sensor fails, the controller prohibits all hydronic cooling operation, butallows the delivery of heat when heating is required.  
In the Cool mode, all cooling is locked-out, but normal fan and outdoor air damper operation is permitted.  
(c) When the outdoor air temperature sensor has failed or is not present, the Tracer ZN520 controller generates a diagnostic to indicate the sensor loss  
condition. The controller automatically clears the diagnostic once a valid outdoor air temperature value is present (non-latching diagnostic). When the  
outdoor air temperature sensor fails or is not present, the controller prohibits economizer operation.  
BCXC-SVX01B-EN  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Diagnostics  
Common Diagnostics  
Table 43. Fan outputs do not energize  
Probably cause  
Explanation  
Random start observed  
After power-up, the controller always observes a random start that varies between 0 and 30 seconds. The controller  
remains off until the random start time expires.  
Power-up control wait  
When power-up control wait is enabled (non-zero time), the controller remains off until one of two conditions occurs:  
1. The controller exits power-up control wait once it receives communicated information.  
2. The controller exits power-up control wait once the power-up control wait time expires.  
Cycling fan operation  
Unoccupied operation  
When the fan mode switch is in the auto position, the unit fan cycles off when there is no call for heating or cooling.  
The heating/cooling sources cycle on or off periodically with the unit fan to match the capacity according to pulse width  
modulation (PWM) logic.  
The fan cycles with capacity when the unit is in unoccupied mode. This occurs even if the unit is in continuous fan  
operation. While unoccupied, the fan cycles on or off with heating/cooling to provide varying amounts of heating or  
cooling to the space. to match the capacity diagnostics according to pulse-width-modulation (PWM) logic.  
Fan mode off  
When using the local fan mode switch to determine the fan operation, the off position controls the unit fan to off.  
Requested mode: off  
It is possible to communicate the operating mode (such as off, heat, and cool) to the controller. When “off” is  
communicated to the controller, the unit controls the fan to off. The unit is not capable of heating or cooling when the  
controller is in this mode.  
Diagnostic present  
A specific list of diagnostics affects fan operation. For more information, see Table 41, p. 77 and Table 42, p. 77.  
No power to the  
controller  
If the controller does not have power, the unit fan does not operate. For the Tracer™ ZN controller to operate normally,  
it must have an input voltage of 24 VAC. When the green LED is off continuously, the controller does not have sufficient  
power or has failed.  
Unit configuration  
Manual output test  
The controller must be properly configured based on the actual installed end devices and application. When the unit  
configuration does not match the actual end devices, the valves may not work correctly.  
The controller includes a manual output test sequence to verify binary output operation and the associated wiring.  
However, based on the current step in the test sequence, the unit fan may not be powered on. Refer to “Manual Output  
Unit wiring  
The wiring between the controller outputs and the fan relays and contacts must be present and correct for normal fan  
operation. Refer to the specific unit wiring diagrams on the unit.  
Table 44. Valves stay closed  
Probable cause  
Normal operation  
Requested mode: off  
Explanation  
The controller opens and closes the valves to meet the unit capacity requirements.  
It is possible to communicate the operating mode (such as off, heat, and cool) to the controller. When off is  
communicated to the controller, the unit controls the fan to off. The unit is not capable of heating or cooling when the  
controller is in this mode.  
Valve override  
The controller can communicate a valve override request.This request affects the valve operation.  
Manual output test  
The controller includes a manual output test sequence to verify analog and binary output operation and the associated  
wiring. However, based on the current step in the test sequence, the valves may not be open. Refer to the “Manual  
Diagnostic present  
Sampling logic  
A specific list of diagnostics affects valve operation. For more information, see Table 41, p. 77 and Table 42, p. 77.  
The controller includes entering water temperature sampling logic that automatically invokes during 2-pipe or 4-pipe  
changeover. It determines when the entering water temperature is either too cool or too hot for the desired heating  
Unit configuration  
The controller must be properly configured based on the actual installed end devices and application. When the unit  
configuration does not match the actual end device, the valves may not work correctly.  
No power to the  
controller  
If the controller does not have power, the unit fan does not operate. For the Tracer™ ZN010, 510 controller to operate  
normally, it must have an input voltage of 24 VAC. When the green LED is off continuously, the controller does not have  
sufficient power or has failed.  
Unit wiring  
The wiring between the controller outputs and the valve(s) must be present and correct for normal valve operation.  
Refer to the unit wiring diagrams on the unit.  
78  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Diagnostics  
Table 45. Valves stay open  
Probable cause  
Normal operation  
Valve override  
Explanation  
The controller opens and closes the valves to meet the unit capacity requirements.  
The controller can communicate a valve override request to affect the valve operation.  
Manual output test  
The controller includes a manual output test sequence that verifies analog and binary output operation and the  
associated wiring. However, based on the current step in the test sequence, the valves may be open. Refer to the  
Diagnostic present  
Sampling logic  
A specific list of diagnostics affects valve operation. For more information, see Table 41, p. 77 and Table 42, p. 77.  
The controller includes entering water temperature sampling logic that automatically invokes during 2-pipe or 4-pipe  
changeover to determine if the entering water temperature is correct for the unit operating mode. Refer to “Entering  
Unit configuration  
Unit wiring  
The controller must be properly configured based on the actual installed end devices and application. When the unit  
configuration does not match the actual end device, the valves may not work correctly.  
The wiring between the controller outputs and the valve(s) must be present and correct for normal valve operation.  
Refer to the unit wiring diagrams on the unit.  
Table 46. Electric heat not operating  
Probable cause  
Normal operation  
Requested mode: off  
Explanation  
The controller cycles electric heat on and off to meet the unit capacity requirements.  
It is possible to communicate the operating mode (such as off, heat, cool) to the controller. When off is communicated  
to the controller, the units shuts off the electric heat.  
Communicated disable  
Manual output test  
Numerous communicated requests may disable electric heat, including an auxiliary heat enable input and the heat/  
cool mode input. Depending on the state of the communicated request, the unit may disable electric heat.  
The controller includes a manual output test sequence that verifies analog and binary output operation and associated  
output wiring. However, based on the current step in the test sequence, the electric heat may not be on. Refer to the  
Diagnostic present  
Unit configuration  
A specific list of diagnostics affects electric heat operation. For more information, see Table 41, p. 77 and Table 42,  
p. 77.  
The controller must be properly configured based on the actual installed end devices and application. When the unit  
configuration does not match the actual end device, the electric heat may not work properly.  
No power to the  
controller  
If the controller does not have power, the unit fan does not operate. For the Tracer™ ZN010, 510 controller to operate  
normally, it must have an input voltage of 24 VAC. When the green LED is off continuously, the controller does not have  
sufficient power or has failed.  
Unit wiring  
The wiring between the controller outputs and the electric heat contacts must be present and correct for normal electric  
heat operation. Refer to the unit wiring diagrams on the unit.  
Table 47. Fresh air damper stays closed  
Probable cause  
Explanation  
Warm-up and cool-down The controller includes both a warmup and cooldown sequence to keep the fresh air damper closed during the transition  
from unoccupied to occupied. This is an attempt to bring the space under control as quickly as possible.  
Requested mode: off  
It is possible to communicate the operating mode (such as off, heat, cool) to the controller. When off is communicated  
to the controller, the unit closes the fresh air damper.  
Manual output test  
The controller includes a manual output test sequence that verifies analog and binary output operation and associated  
output wiring. However, based on the current step in the test sequence, the fresh air damper may not be open. Refer  
Diagnostic present  
Unit configuration  
A specific list of diagnostics effects fresh air damper operation. For more information, see Table 41, p. 77 and Table 42,  
p. 77.  
The controller must be properly configured based on the actual installed end devices and application. When the unit  
configuration does not match the actual end device, the damper may not work correctly.  
No power to the  
controller  
If the controller does not have power, the unit fan does not operate. For the Tracer™ ZN010, 510 controller to operate  
normally, it must have an input voltage of 24 VAC. When the green LED is off continuously, the controller does not have  
sufficient power or has failed.  
Unit wiring  
The wiring between the controller outputs and the fresh air damper must be present and correct for normal damper  
operation. Refer to the unit wiring diagrams on the unit.  
BCXC-SVX01B-EN  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Diagnostics  
Table 48. Fresh air damper stays open  
Probable cause  
Explanation  
Normal operation  
Thecontrolleropensandclosesthefreshairdamperbasedonthecontroller’soccupancymodeandfanstatus. Normally,  
the fresh air damper is open during occupied mode when the fan is running and closed during unoccupied mode.  
Manual output test  
The controller includes a manual output test sequence that verifies analog and binary output operation and associated  
wiring. However, based on the current step in the test sequence, the fresh air damper may be open. Refer to the “Manual  
Unit configuration  
Unit wiring  
The controller must be properly configured based on the actual installed end devices and application. When the unit  
configuration does not match the actual end device, the damper may not work correctly.  
The wiring between the controller outputs and the fresh air damper must be present and correct for normal damper  
operation. Refer to the unit wiring diagrams on the unit.  
Table 49. Valves stay closed  
Probable cause  
Explanation  
Requested mode off  
You can communicate a desired operating mode (such as off, heat, and cool) to the controller. When off is communicated  
to the controller, the unit controls the fan off. There is no heating or cooling (valves are closed).  
Power-up control wait  
Manual output test  
When power up control wait is enabled (non-zero time), the controller remains off until one of two conditions occurs:  
The controller exits power up control wait once it receives communicated information.  
The controller exits power up control wait once the power up control wait time expires.  
The controller includes a manual output test sequence you can use to verify output operation and associated output  
wiring. However, based on the current step in the test sequence, the valve(s) may not be open. Refer to the “Manual  
Fan mode off  
When a local fan mode switch (provided on the Trane zone sensor) determines the fan operation, the off position  
controls the unit off and valves to close.  
Sampling logic  
The controller includes entering water temperature sampling logic which is automatically invoked during 2-pipe and  
4-pipe changeover when the entering water temperature is either too cool or too hot for the desired heating or cooling.  
Diagnostic present  
Unit configuration  
A specific list of diagnostic affects valve operation. For more information, see Table 41, p. 77 and Table 42, p. 77.  
The controller must be properly configured based on the actual installed end devices and application. When the unit  
configuration does not match the actual end devices, the valves may not work correctly.  
Example: A 2-pipe heat/cool changeover unit will not cool if the entering water temperature is too warm for cooling  
or if the entering water sensor is not present. The unit will not heat if the entering water temperature is too cool for  
heating.  
Unit wiring  
The wiring between the controller outputs and the valve(s) must be present and correct for normal valve operation.  
Random start observed  
After power up, the controller always observes a random start from 0 to 25 seconds. The controller remains off until  
the random start time expires.  
Table 50. DX or electric outputs do not energize  
Probable cause  
Unit wiring  
Explanation  
The wiring between the controller outputs and the end devices must be present and correct for normal operation.  
Unit configuration  
The controller must be properly configured based on the actual installed end devices and application. When the unit  
configuration does not match the actual end devices, the unit may not work correctly.  
Diagnostic present  
Manual output test  
A specific list of diagnostic affects valve operation. For more information, see Table 41, p. 77 and Table 42, p. 77.  
The controller includes a manual output test sequence you can use to verify output operation and associated output  
wiring. However, based on the current step in the test sequence, the valve(s) may not be open. Refer to the “Manual  
Freeze avoidance  
Normal operation  
When the fan is off with no demand for capacity (0%) and the outdoor air temperature is below is below the freeze  
avoidance setpoint, the controller disables compressors and electric heat outputs. This includes unoccupied mode when  
there is no call for capacity or any other time the fan is off.  
The controller energizes the outputs only as needed to meet the unit capacity requirements.  
80  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
Two-Pipe BCXC with Tracer ZN510  
208 volt/3 phase  
2-position damper  
single stage electric heat  
2-position valve  
condensate overflow  
wall-mounted zone sensor  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including  
remote disconnects before servicing. Follow  
proper lockout/tagout procedures to ensure  
the power can not be inadvertently  
energized. Failure to disconnect power before  
servicing could result in death or serious  
injury.  
NOTICE  
Use copper conductors only!  
Unit terminals are not designed to accept  
other conductor types. Failure to use copper  
conductors could cause equipment damage.  
BCXC-SVX01B-EN  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Wiring Diagrams  
Four-Pipe BCXC with Tracer ZN510  
208 volt/3 phase  
2-position valves  
2-position damper  
condensate overflow  
low limit protection  
wall-mounted zone sensor  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including  
remote disconnects before servicing. Follow  
proper lockout/tagout procedures to ensure  
the power can not be inadvertently  
energized. Failure to disconnect power before  
servicing could result in death or serious  
injury.  
NOTICE  
Use copper conductors only!  
Unit terminals are not designed to accept  
other conductor types. Failure to use copper  
conductors could cause equipment damage.  
82  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
Four-Pipe BCXC with Tracer ZN510  
115 volt/1 phase  
2-position valves  
2-position damper  
2-speed motor  
condensate overflow  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including  
remote disconnects before servicing. Follow  
proper lockout/tagout procedures to ensure  
the power can not be inadvertently  
energized. Failure to disconnect power before  
servicing could result in death or serious  
injury.  
NOTICE  
Use copper conductors only!  
Unit terminals are not designed to accept  
other conductor types. Failure to use copper  
conductors could cause equipment damage.  
BCXC-SVX01B-EN  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
Two-Pipe BCXC with Tracer ZN520  
460 volt/3 phase  
2-position valve  
economizer damper  
2-stage electric heat  
fan status switch  
condensate overflow  
wall-mounted zone sensor  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including  
remote disconnects before servicing. Follow  
proper lockout/tagout procedures to ensure  
the power can not be inadvertently  
energized. Failure to disconnect power before  
servicing could result in death or serious  
injury.  
NOTICE  
Use copper conductors only!  
Unit terminals are not designed to accept  
other conductor types. Failure to use copper  
conductors could cause equipment damage.  
84  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
Four-Pipe BCXC with Tracer ZN520  
460 volt/3 phase  
2-position valves  
condensate overflow  
fan status switch  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including  
remote disconnects before servicing. Follow  
proper lockout/tagout procedures to ensure  
the power can not be inadvertently  
energized. Failure to disconnect power before  
servicing could result in death or serious  
injury.  
NOTICE  
Use copper conductors only!  
Unit terminals are not designed to accept  
other conductor types. Failure to use copper  
conductors could cause equipment damage.  
BCXC-SVX01B-EN  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
Four-Pipe BCXC with Tracer ZN520  
460 volt/3 phase  
economizer damper  
condensate overflow  
fan status switch  
wall-mounted zone sensor  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including  
remote disconnects before servicing. Follow  
proper lockout/tagout procedures to ensure  
the power can not be inadvertently  
energized. Failure to disconnect power before  
servicing could result in death or serious  
injury.  
NOTICE  
Use copper conductors only!  
Unit terminals are not designed to accept  
other conductor types. Failure to use copper  
conductors could cause equipment damage.  
86  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
Four-Pipe BCXC with Tracer ZN520  
460 volt/3 phase  
3-wire floating point valves  
economizer damper  
condensate overflow  
fan status switch  
wall-mounted zone sensor  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including  
remote disconnects before servicing. Follow  
proper lockout/tagout procedures to ensure  
the power can not be inadvertently  
energized. Failure to disconnect power before  
servicing could result in death or serious  
injury.  
NOTICE  
Use copper conductors only!  
Unit terminals are not designed to accept  
other conductor types. Failure to use copper  
conductors could cause equipment damage.  
BCXC-SVX01B-EN  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
Four-Pipe BCXC with Control Interface  
• 208 volt/3 phase  
• 3-wire floating point valves  
• 2-position damper  
• low limit protection  
• condensate overflow  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including  
remote disconnects before servicing. Follow  
proper lockout/tagout procedures to ensure  
the power can not be inadvertently  
energized. Failure to disconnect power before  
servicing could result in death or serious  
injury.  
NOTICE  
Use copper conductors only!  
Unit terminals are not designed to accept  
other conductor types. Failure to use copper  
conductors could cause equipment damage.  
88  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
Four-Pipe BCXC with Control Interface  
115 volt/1 phase  
2-position damper  
2-speed motor  
condensate overflow  
low limit protection  
ƽ WARNING  
Hazardous Voltage!  
Disconnect all electric power, including  
remote disconnects before servicing. Follow  
proper lockout/tagout procedures to ensure  
the power can not be inadvertently  
energized. Failure to disconnect power before  
servicing could result in death or serious  
injury.  
NOTICE  
Use copper conductors only!  
Unit terminals are not designed to accept  
other conductor types. Failure to use copper  
conductors could cause equipment damage.  
BCXC-SVX01B-EN  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
BCXC with DX Coil and Tracer ZN520  
277 volt/1 phase  
economizer damper  
condensate overflow  
wall-mounted zone sensor  
NOTES:  
1
UNLESSS OTHERRWISEE NNOTEDD,, ALL SWWITCHHEES ARE SSHOWN  
AT 25°° C (777°° F), AT ATMOOSPHEERIC PPRRESSURE, AT  
LEGEND  
DEVICE PPREFIX LLOCATIIOON CODE  
277/60/1  
N
LOCATION  
AREA  
DEVICE  
DESIGNATION  
LINE  
NUMBER  
L1  
50% RELAATIVE HHUMIDIITY, WWIITH ALLL UTILIITIESTTURNED  
OFF, ANND AFTTEER A NORRMAL SSHUTDOWN HASS OCCURED.  
DESCRIPTION  
1
2
1
2
3
MAIN CONTROOL PANEL  
SUPPLY FANN AND COOIL SECCTION  
1CB1  
1K1  
TRANSFORRMER CIRRCUIT BBRREAKER  
SUPPLY FAN COONTACTOR  
DX RELAY  
16  
20  
24  
2
DASHEDD LINESS INDICCATE REECOMMEENDED FFIELD WWIRING  
BY OTHEERS. DDAASHED LLINE ENNCLOSUURES ANND/OR DDASHED  
DEVICEE OUTLIINES IINNDICATTE COMPPONENTTS PROVIDED  
BYTHE FIELD. SOLID LINES INDICATE WIRING BY  
TRANE CO.  
4
5
6
7
MIXING BOX SECTION  
EXTERNAL PIPING  
ELECTRIC HEAT CONTROL BOX  
FIELD INSTALLED DEVICE  
1K3  
3
7
S
S
6
6
7S6  
1T1  
1TB1-L11,-L2  
1U1  
CONTROOL POWERRTRANSSFFORMER  
CONTROOLTERRMINAL BLOCK  
ZN CONTRROLLER  
16  
3
4
ALL FIELD WIRINNG MUSTT BE INN ACCORRDANCCE WITHTHE  
NATIONAL ELEECTRIIC CODDEE (NEC), STATEE AND LLOCAL  
REQUIREMMENTS.  
4
18  
11  
2B1  
SUPPLY FANN MOTOR  
NUMBERS ALONGGTHE RRIGHT SSIDE OOFTHE SSCHEMATIC  
DESIGNAATETHEE LLOCATIION OF CCONTACCTS BY LLINE NUUMBER.  
5
2S2  
CONDENNSATE OVERFLOW SSWITCH  
32  
5
FIELD SUUPPLIEED CONNTROL RELAYSS, POWEERED BYYTHIS UNIT,  
MUST BE PILOT DUUTY RAATED,, 224VAC COILL, 6VAA MAX.  
6
2S5  
2S7  
2S8  
4U4  
FAN STATUUS SWITCH  
36  
23  
24  
27  
ELECTRIC HEAT  
CONTROL BOX  
1S1  
6
7
WIRINGGTO ZONNEE SENSOOR MUSTT BE 16--22 AWGG, CUTWWISTED  
PAIR SHIIELDEEDD CABLEE AND NNO MORETHANN 10000 FFT LG.  
SHIELD MMUST BEE GGROUNDDED AT UUCM ENDD(END CCHASSIIS) AND  
TAPED ATTHE OTHER END. IF INSTALLED IN CONDUIT, DO  
NOT INSTTALL WIIRRES IN CCONDUITTTHAT CCONTAIINNS WIREES 24VAC  
OR HIGH VVOLTAGEE POWERR WWIRES.  
ELECTRIC HT LOCKOOUT SWITCH  
EVAP DEFRROST FROSTAT  
7
MIXING BOOX DAMPPER ACTTUATOR  
8
WHT BLK  
COMMUNICATION WWIRE MUSTT BETRANEE PART NO.  
400-20-28, OR WWINDY CIITTY OR CONNNECT AIR  
"LEVEL 4" CABLE. MAXIMUM OF 4500 FOOT  
AGGREGATE RUN.  
CAUTION! DO NOT RUN POWER INTHE SAME  
CONDUIT OR WIRRE BUNNDDLE WITTH COMMMUNICAATION LINK.  
FOR ADDITIONAAL INFORMAATION REFERTO EMTTX-EBB-68.  
9
1K1  
1K21  
1K1  
4A(WHT)  
WHT,BRN  
2B1  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
COM  
7K5  
EXHAUST FAN CONTTROL RRELAY  
21  
M
8
9
31  
LOW  
HI  
7RT1  
7RT3  
7S6  
DISCHARGGE AIRTTEMP SSEENSOR  
OUTSIDDE AIRRTTEMP SEENSOR  
FUSED DISCONNNECT SSWWITCH  
33  
35  
3
BLK,BLK  
BLK  
5A  
GRN  
7U6  
P
ZONE SENSORR MODULE  
PLUG CONNNECTOR  
JACK CONNNECTOR  
20  
BRN  
J
1T1  
1CB1  
1TB1-L2  
11  
W(BLK)  
BLU  
YEL  
B(BLK)  
24V  
75VA  
1TB1-L2  
E
D(WHT)  
1U1  
POWER  
11  
1TB1-L1  
C,K  
10  
D
(BLK)  
TB1-1 24V  
J1  
GNDTB1-2  
6
7U6  
1K1  
7K5  
1K2  
W,X  
E
(BLK)  
17A(BLK)  
14A(YEL)  
1K1-10,12  
1
HIGH SPEED  
ZONETB3-1  
GNDTB3-2  
SETTB3-3  
FANTB3-4  
1
2
3
4
6
5
ZONE  
1TB1-L1  
10  
1P1-1  
1P1-2  
1P1-3  
5
1TB1-L1  
1TB1-L1  
1TB1-L1  
2
EXHAUST  
COM  
10  
CSP  
5
1K3  
5P4-2  
5J4-2  
5P3-2  
1P2-1  
5P3-1  
DX COOLING  
5P4-1  
1P2-2  
1J2-2  
11PP22--23  
19B  
G
K
FAN SWITCH  
COMM LOW(-)  
COMM HI(+)  
1J2-1  
2J3-1  
5J4-1  
5P3-3  
2J3-2  
2
4
10  
1P1-5  
C
1K3  
8
5P4-3  
5P3-3  
1P2-1  
1J2-1  
1P5-1  
1P2-3  
5P4-3  
5J4-3  
2S8  
2J3-3  
5P6-2  
2J6-2  
5P6-3  
2J6-3  
J
G,J  
38A  
5J4-3  
3
1K3-23  
5
9
ON/OFF  
CLG  
STAGE 1  
TB2-6  
COMM  
1J2-3  
2J3-3  
1J2-3  
1
-
1J2-2  
1P1-56  
5P7-2  
5P6-1  
COMMON  
2J6-1  
5P7-1  
STAGE 1  
5J7-1  
1P5-2  
2S7  
X
BRN  
ORG  
PUR  
15C(ORG)  
1J5-2  
TB2-5  
1J5-1  
5J7-2  
5P7-3  
5J7-3  
10  
1P1-9  
+
-
ELECTRIC HEAT  
8
1P5-3  
5P6-3  
5P7-3  
1P5-3  
LO(-)  
16C(PUR)  
1J5-3  
CONTROL BOX  
STAGE 2  
10 STAGE 2  
11 OPEN  
TB2-4  
COMM  
1J5-3  
2J6-3  
5J7-3  
TR1  
TR  
1P1-10  
TRACER  
COMM OUT  
4U4  
TR1 CCW  
1J8-1  
1P8-1  
2J9-1  
1P8-3  
4P9-3  
HI(+)  
E(WHT)  
1J8-3  
C
B
12A(PNK)  
1P1-11  
13A(BRN)  
1P1-12  
TB2-3  
CCW  
CW  
V
1P8-4  
V
X
R
2J9-3  
4P9-1  
SPLICE AND  
INSULATE SHIELDS  
+
-
OAD  
1J8-2  
4P9-4  
2J9-4  
2J9-2  
4P9-2  
C
B
B(BLK)  
TR  
CW  
12 CLOSE  
TB2-2  
1J8-4  
LO(-)  
1P8-2  
TRACER  
COMM IN  
COMM  
7
TB4-1 BOP  
TB2-1  
HI(+)  
+
GENERIC BOP  
GENERIC  
TB4-2 24V  
9
2S3  
5RT2  
5P10-1  
5P10-2  
1P11-1  
2J10-1  
1P11-2  
2J10-2  
1J11-1  
2S2  
23A(PUR)  
2J13-1  
B
2P13-1  
B
2J13-2  
J2-3  
J2-4  
J2-5  
J2-6  
J2-7  
J2-8  
1J11-2  
2J12-1  
2J12-2  
2P13-2  
GREEN PLUG  
ƽ WARNING  
Hazardous Voltage!  
BI-2  
27RT1  
SPLICE  
SPLICE  
CONDENSATE  
24A(PUR)  
J3-3  
AI-2 DAT  
2P12-1  
Disconnect all electric power, including  
J3-4  
J3-5  
J3-6  
2P12-2  
SPLICE  
OR FIELD RECONFIGURED  
AS GENERIC  
BI-3  
OCC/UNOCC  
remote disconnects before servicing. Follow  
proper lockout/tagout procedures to ensure  
the power can not be inadvertently  
7RT3  
SPLICE  
AI-3-OAT  
2S5  
25A(YEL)  
26A(YEL)  
energized. Failure to disconnect power before  
servicing could result in death or serious  
injury.  
BI-4  
P
d
FAN-STAT  
NOTICE  
Use copper conductors only!  
Unit terminals are not designed to accept  
other conductor types. Failure to use copper  
conductors could cause equipment damage.  
90  
BCXC-SVX01B-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
BCXC with DX Coil, Hydronic Heating, and Tracer ZN520  
460 volt/3 phase  
economizer damper  
condensate overflow  
wall-mounted zone sensor  
NOTES:  
1
UNLESSS OTHERRWISEE NNOTEDD,, ALL SWWITCHHEES ARE SSHOWN  
AT 25˚ C (77˚ F), AT ATMOSSPHERRIC PREESSURE, AT  
LEGEND  
DEVICE PPREFIX LLOCATIIOON CODE  
460/60/3  
L1 L2  
LOCATION  
AREA  
DEVICE  
DESIGNATION  
LINE  
DESCRIPTION  
L3  
50% RELAATIVE HHUMIDIITY, WWIITH ALLL UTILIITIES TTURNED  
OFF, ANND AFTTEER A NORRMAL SSHUTDOWN HAAS OCCCUURED.  
1
NUMBER  
1
2
3
MAIN CONTROL PANEL  
SUPPLY FAN AND COOIL SECTION  
1CB1  
1K1  
TRANSFORRMER CIRRCUIT BBRREAKER  
SUPPLY FAN COONTACTOR  
DX RELAY  
16  
20  
24  
7
2
DASHED LLINES IINDICAATE REECCOMMENNDED FFIIELD WIIRING  
BY OTHEERS. DDAASHED LLINE ENNCLOSUURES ANND/OR DDASHED  
DEVICEE OUTLIINES IINNDICATTE COMPPONENTTS PROVIDED  
BY THE FIELD. SOLID LINES INDICATE WIRING BY  
TRANE CO.  
2
4
5
6
7
MIXING BOX SECTION  
EXTERNAL PIPING  
1K3  
1S1  
MANUAL DDISCONNNECT SSWITCH  
CONTROOL POWERR TRANSSFFORMER  
CONTROOL TERRMMINAL BBLOCK  
ZN CONTRROLLER  
3
7
S
S
66  
7S6  
1T1  
16  
3
4
ALL FIELD WIRRING MUSST BE IN ACCORDANCE WITH THE  
NATIONAL ELECTRIC COODE (NEC), STATE AND LOCAL  
REQUIREEMENTS.  
FIELD INSTALLED DEVICE  
1TB1-L1,-L2  
1U1  
4
18  
11  
33  
32  
30  
2B1  
SUPPLY FAAN MOTOR  
NUMBERS ALOONG THE RRIGHT SIDE OF THE SCHEMATIC  
DESIGNATE TTHE LOCATTION OF CONTACTS BY LINE NUMBER.  
2RT1  
2S2  
DISCHARGE AIRR TEMP SENSOR  
CONDENSSATE OVVEERFLOW SSWITCH  
FREEZE-STAT  
5
5
FIELD SUPPPLIEED CONTROLL RELAYS, POWERED BY THIS UNIT,  
MUST BE PIILOT DUTYY RATED, 24VAC COIL, 6VA MAX.  
2S3  
6
GRN  
BLK BLK  
BLK  
6
7
WIRING TO ZZONE SENSOOR MUST BE 16--22 AWG, CU TWISTED  
PAIR SHIELDDED CABLEE AND NO MORE THAN 1000 FT LG.  
SHIELD MUSTT BE GROUNNDED AT UCM END(END CHASSIS) AND  
TAPED AT THE OTHER END. IF INSTALLED IN CONDUIT, DO  
NOT INSTALLL WIREES IN CCOONDUIT THAT CONTAINS WIRES 24VAC  
OR HIGHH VOLTAAGE POOWWER WIRES.  
7
2S8  
EVAP DEFROST FROSTAT  
24  
1S1  
EQUIPMENT  
GROUND  
8
1A  
2A  
3A  
COMMUNICATTION WIRREE MUST BE TRANE PART NO.  
400-20-28, OR WINDYY CITY OR CONNECT AIR  
"LEVEL 4" CABLE. MAXIMUM OF 4500 FOOT  
AGGREGATE RUN.  
9
1K1  
1K21  
1K1  
7B3  
7K5  
HEATING COIL VAALVE MMOTOR  
EXHAUST FAN CONTTROL RRELAY  
25  
21  
4A  
A,BLK/RED  
A,BLK  
A
2B1  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
CAUTION! DO NOT RUN POWER IN THE SAME  
CONDUIT OR WWIRE BUNDDLE WITH COMMUNICATION LINK.  
FOR ADDITIOONAL INFOORMATION REFER TO EMTX-EB-68.  
COM  
M
5A  
8
9
BLUE CONNECCTORS USEED FOR COOLIING CIRCUIT,  
RED CONNEECTORS USSED FOR HHEEATING CIRCUIT.  
BLUE WIRESS USED FORR COOLINGG CIRCUIT, RED  
WIRES USSED FORR HHEATINGG CIRCUIT.  
31  
LOW  
HI  
7RT3  
7S6  
7U4  
7U6  
P
OUTSIDE AIR TEMP SENSOR  
FUSED DISCONNNECT SSWWITCH  
MIXING BOOX DAMPPER ACTTUATOR  
ZONE SENSORR MODULE  
PLUG CONNNECTOR  
35  
3
6A  
GRN  
27  
20  
BLK  
BLK/RED  
J
JACK CONNNECTOR  
1T1  
1CB1  
1TB1-L2  
W(BLK)  
BLU  
YEL  
B(BLK)  
24V  
75VA  
11  
1TB1-L2  
E
D(WHT)  
1U1  
POWER  
11  
1TB1-L1  
C,K,M  
D
(BLK)  
TB1-1 24V  
J1  
GND TB1-2  
10  
6
7U6  
ZONE  
1K1  
7K5  
1K2  
W
E
(BLK)  
17A(BLK)  
14A(YEL)  
1K1-10,12  
1
HIGH SPEED  
ZONE TB3-1  
GND TB3-2  
SET TB3-3  
FAN TB3-4  
1
2
3
4
6
5
1TB1-L1 10  
1P1-1  
1P1-2  
1P1-3  
5
1TB1-L1  
1TB1-L1  
1TB1-L1  
2
EXHAUST  
COM  
CSP  
10  
5
1K3  
5P4-2  
5J4-2  
5P3-2  
2J3-2  
5P3-3  
1P2-1  
5P3-1  
DX COOLING  
5P4-1  
1P2-2  
1J2-2  
11PP22--23  
G
K
FAN SWITCH  
COMM LOW(-)  
COMM HI(+)  
1J2-1  
2J3-1  
5J4-1  
5P3-3  
2
4
10  
1P1-5  
C
1K3  
8
5P4-3  
1P2-1  
1J2-1  
1P5-1  
1J5-1  
1P2-3  
5P4-3  
5J4-3  
2S8  
2J3-3  
5P6-2  
J
G,J  
38A  
5J4-3  
3
19B  
1K3-23  
5
9
ON/OFF  
CLG  
ON/OFF  
TB2-6  
COMM  
1J2-3  
2J3-3  
1J2-3  
1
-
1J2-2  
1P1-56  
7B3 (7VA MAX)  
5P7-2  
5J7-2  
5P7-3  
5J7-3  
5P6-1  
2J6-1  
1P5-3  
1J5-3  
1P8-3  
5P7-1  
1P5-2  
C
1J5-2  
2S7  
M
L
B
15A  
M
TB2-5  
D
5J7-1  
5P6-3  
2J6-2  
5P6-3  
2J6-3  
10  
1P1-9  
+
-
HTG  
8
5P7-3  
5J7-3  
1P5-3  
LO(-)  
TB2-4  
COMM  
2J6-3  
4P9-3  
1J5-3  
1P1-10  
TRACER  
COMM OUT  
7U4  
1J8-1  
1P8-1  
2J9-1  
SPLICE  
SPLICE  
HI(+)  
E(WHT)  
1J8-3  
12A(PNK)  
1P1-11  
13A(BRN)  
1P1-12  
TR1 CCW  
11 OPEN  
TB2-3  
2J9-3  
4P9-4  
4P9-1  
2J9-2  
SPLICE  
SPLICE AND  
INSULATE SHIELDS  
+
-
OAD  
1J8-2  
1P8-4  
SPLICE  
B(BLK)  
TR  
CW  
12 CLOSE  
TB2-2  
1J8-4  
LO(-)  
2J9-4  
4P9-2  
1P8-2  
TRACER  
COMM IN  
COMM  
7
TB4-1 BOP  
GENERIC  
TB4-2 24V  
TB2-1  
HI(+)  
+
GENERIC BOP  
9
2S3  
21A(GRA)  
22A(GRA)  
J2-1  
J2-2  
J2-3  
J2-4  
J2-5  
J2-6  
BI-1  
5RT2  
5P10-1  
5P10-2  
1P11-1  
FRZ-STAT  
2J10-1  
1P11-2  
1J11-1  
2S2  
23A(PUR)  
2J13-1  
B
2P13-1  
B
2J13-2  
ƽ WARNING  
Hazardous Voltage!  
2J10-2  
1J11-2  
34A(BRN)  
2J12-1  
35A(BRN)  
2J12-2  
2P13-2  
GREEN PLUG  
BI-2  
27RT1  
CONDENSATE  
B
24A(PUR)  
J3-3  
AI-2 DAT  
2P12-1  
B
Disconnect all electric power, including  
J3-4  
J3-5  
J3-6  
2P12-2  
OR FIELD RECONFIGURED  
AS GENERIC  
remote disconnects before servicing. Follow  
proper lockout/tagout procedures to ensure  
the power can not be inadvertently  
energized. Failure to disconnect power before  
servicing could result in death or serious  
injury.  
BI-3  
OCC/UNOCC  
7RT3  
SPLICE  
SPLICE  
AI-3-OAT  
2S5  
NOTICE  
Use copper conductors only!  
Unit terminals are not designed to accept  
other conductor types. Failure to use copper  
conductors could cause equipment damage.  
BCXC-SVX01B-EN  
91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Literature Order Number  
Date  
BCXC-SVX01B-EN  
April 2008  
Supersedes  
BCXC-SVX01A-EN September 2002  
For more information, contact your local Trane  
office or e-mail us at [email protected]  
Trane has a policy of continuous product and product data improvement and reserves the right to  
change design and specifications without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tiger Games E Yo User Manual
Tiger Games Pokedex Deluxe User Manual
Toshiba CRT Television 35A44 User Manual
Toshiba Digital Camera PDR 3310 User Manual
Toshiba PDAs Smartphones e740 User Manual
TrekStor eBook Reader 7 User Manual
TRENDnet Network Router TEW 631BRP User Manual
United States Stove Furnace 24AF User Manual
Vanguard Fire Pit VI33NRA User Manual
ViewSonic Computer Monitor VA2013WM User Manual