Trane Air Conditioner TRG TRC011 EN User Manual

Air Conditioning  
Clinic  
Absorption  
Water Chillers  
One of the Equipment Series  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Preface  
Figure 1  
The Trane Company believes that it is incumbent on manufacturers to serve the  
industry by regularly disseminating information gathered through laboratory  
research, testing programs, and field experience.  
The Trane Air Conditioning Clinic series is one means of knowledge sharing. It  
is intended to acquaint a nontechnical audience with various fundamental  
aspects of heating, ventilating, and air conditioning. We have taken special care  
to make the clinic as uncommercial and straightforward as possible.  
Illustrations of Trane products only appear in cases where they help convey the  
message contained in the accompanying text.  
This particular clinic introduces the concept of absorption water chillers.  
© 2000 American Standard Inc. All rights reserved  
TRG-TRC011-EN  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Introduction ........................................................... 1  
period one  
period two  
Absorption Refrigeration Cycle ....................... 3  
Absorption System Fluids ........................................ 6  
Components of the Absorption Cycle ...................... 8  
Equilibrium Chart ................................................... 15  
Absorption Chiller Types ................................. 18  
Single-Effect Chiller ............................................... 19  
Double-Effect Chiller ............................................. 21  
Direct-Fired Chiller ................................................. 27  
Chiller/Heater ........................................................ 30  
period three Capacity Control ................................................. 34  
Crystallization ........................................................ 37  
Purge System ....................................................... 44  
period four Maintenance Considerations .......................... 46  
period five  
Application Considerations ............................. 53  
Cooling-Water Temperature Limitations ................. 54  
Combination Chiller Plants ..................................... 55  
Special Considerations for Direct-Fired Chillers ...... 57  
Equipment Rating Standards ................................. 59  
period six  
Review ................................................................... 60  
Quiz ......................................................................... 65  
Answers ................................................................ 68  
Glossary ................................................................ 69  
TRG-TRC011-EN  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iv  
TRG-TRC004-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
notes  
Figure 2  
Water chillers are used in a variety of air conditioning and process cooling  
applications. They are used to make cold water that can be transported  
throughout a facility using pumps and pipes. This cold water can be passed  
through the tubes of coils to cool the air in an air conditioning application, or it  
can provide cooling for a manufacturing or industrial process.  
Systems that employ water chillers are commonly called chilled-water  
systems.  
Figure 3  
Although water chillers come in many sizes and types, they all produce cooling  
using the same basic principles of heat transfer and change-of-phase of the  
refrigerant. This is accomplished by the chiller refrigeration cycle. They differ  
from each other based on the refrigeration cycle and the type of refrigerant fluid  
used.  
TRG-TRC011-EN  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
Water chillers using the vapor-compression refrigeration cycle vary by the type  
of compressor used. The compressor works to draw in refrigerant vapor and  
increase its pressure and temperature to create the cooling effect.  
Reciprocating, scroll, helical-rotary (or screw), or centrifugal compressors are  
generally used in water chillers that employ the vapor-compression  
refrigeration cycle.  
notes  
Absorption water chillers make use of the absorption refrigeration cycle and do  
not use a mechanical compressor. The absorption refrigeration cycle is used in  
both small and large air-conditioning equipment. This clinic, however, focuses  
on large water-chiller applications of the absorption cycle. The different types of  
absorption water chillers will be discussed in detail in Period Two.  
2
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
notes  
period one  
Figure 4  
This period describes the components of the absorption refrigeration cycle.  
Comparing the absorption refrigeration cycle with the more familiar vapor-  
compression refrigeration cycle is often an easy way to introduce it. Like the  
vapor-compression refrigeration cycle, the absorption refrigeration cycle uses  
the principles of heat transfer and change-of-phase of the refrigerant to produce  
the refrigeration effect.  
Both the vapor-compression and absorption refrigeration cycles accomplish  
cooling by absorbing heat from one fluid (chilled water) and transferring it to  
another fluid (cooling water or ambient air). Both cycles circulate refrigerant  
inside the chiller to transfer this heat from one fluid to the other. Both cycles  
also include a device to increase the pressure of the refrigerant and an  
expansion device to maintain the internal pressure difference, which is critical  
to the overall heat transfer process.  
TRG-TRC011-EN  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
notes  
reject heat  
'
&
condenser  
compressor  
expansion  
device  
energy in  
evaporator  
$
%
absorb heat  
Figure 5  
In the vapor-compression refrigeration cycle, refrigerant enters the evaporator  
in the form of a cool, low-pressure mixture of liquid and vapor ($). Heat is  
transferred from the relatively warm air or water to the refrigerant, causing the  
liquid refrigerant to boil. The resulting vapor (%) is then pumped from the  
evaporator by the compressor, which increases the pressure and temperature  
of the refrigerant vapor.  
The hot, high-pressure refrigerant vapor (&) leaving the compressor enters the  
condenser where heat is transferred to ambient air or water at a lower  
temperature. Inside the condenser, the refrigerant vapor condenses into a  
liquid. This liquid refrigerant (') then flows to the expansion device, which  
creates a pressure drop that reduces the pressure of the refrigerant to that of  
the evaporator. At this low pressure, a small portion of the refrigerant boils (or  
flashes), cooling the remaining liquid refrigerant to the desired evaporator  
temperature. The cool mixture of liquid and vapor refrigerant ($) travels to the  
evaporator to repeat the cycle.  
The vapor-compression refrigeration cycle is discussed in detail in the  
Refrigeration Cycle clinic.  
4
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
notes  
reject heat  
heat energy in  
&
'
generator  
condenser  
pump  
expansion  
device  
absorber  
evaporator  
$
%
reject heat  
absorb heat  
Figure 6  
There are two fundamental differences between the absorption refrigeration  
cycle and the vapor-compression refrigeration cycle. The first is that the  
compressor is replaced by an absorber, pump, and generator. The second is  
that, in addition to the refrigerant, the absorption refrigeration cycle uses a  
secondary fluid, called the absorbent. The condenser, expansion device, and  
evaporator sections, however, are the same.  
Refrigerant enters the evaporator in the form of a cool, low-pressure mixture of  
liquid and vapor ($). Heat is transferred from the relatively warm water to the  
refrigerant, causing the liquid refrigerant to boil. Using an analogy of the vapor-  
compression cycle, the absorber acts like the suction side of the compressor—it  
draws in the refrigerant vapor (%) to mix with the absorbent. The pump acts like  
the compression process itself—it pushes the mixture of refrigerant and  
absorbent up to the high-pressure side of the system. The generator acts like  
the discharge of the compressor—it delivers the refrigerant vapor (&) to the rest  
of the system.  
The refrigerant vapor (&) leaving the generator enters the condenser, where  
heat is transferred to water at a lower temperature, causing the refrigerant  
vapor to condense into a liquid. This liquid refrigerant (') then flows to the  
expansion device, which creates a pressure drop that reduces the pressure of  
the refrigerant to that of the evaporator. The resulting mixture of liquid and  
vapor refrigerant ($) travels to the evaporator to repeat the cycle.  
The components of the absorption refrigeration cycle will be discussed in detail  
in a moment.  
TRG-TRC011-EN  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
notes  
L
N Stable  
N Nontoxic  
N Low cost  
N Readily available  
N Environmentally friendly  
N High latent heat of  
vaporization  
Figure 7  
Absorption System Fluids  
Probably the greater of these differences between the vapor-compression and  
absorption refrigeration cycles, however, is the types of fluids used. The vapor-  
compression refrigeration cycle generally uses a halocarbon (such as  
HCFC-123, HCFC-22, HFC-134a, etc.) as the refrigerant. The particular absorption  
refrigeration cycle discussed in this clinic uses distilled water as the  
refrigerant.  
Distilled water is stable, nontoxic, low in cost, readily available,  
environmentally friendly, and has a relatively high heat of vaporization  
(1000 Btu/lb [2326 kJ/kg]). The heat of vaporization is the amount of heat  
required to fully transform (evaporate) liquid to a vapor at a given pressure.  
For the water to be used as a refrigerant, the cycle must operate in a vacuum,  
that is, at a pressure below atmospheric pressure. This will be discussed  
shortly. Finally, large quantities of water are easily absorbed by the absorbent  
and separated within the absorption cycle.  
Throughout the remainder of this clinic, when the term refrigerant is used, it  
refers to distilled water.  
6
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
notes  
L
N High affinity for water  
(refrigerant)  
N In solution, higher  
boiling point than water  
N Nontoxic  
Figure 8  
Additionally, the absorption refrigerant cycle uses a second fluid called an  
absorbent solution. The absorbent solution is confined to the absorber and  
generator sections of the cycle, and is used to carry the refrigerant from the  
low-pressure side (evaporator) to the high-pressure side (condenser) of the  
chiller. For this purpose, the absorbent should have a strong affinity (attraction)  
for the refrigerant and, when in solution with the refrigerant, a boiling point that  
is substantially higher than that of the refrigerant.  
The absorbent commonly used with water (the refrigerant) is lithium bromide.  
Lithium bromide, a nontoxic salt, has a high affinity for water. Also, when in  
solution with water, the boiling point of lithium bromide is substantially higher  
than that of water. This makes it easy to separate the refrigerant from the  
absorbent at low pressures. A certain quantity of absorbent solution, therefore,  
is pumped from the absorber to the generator in order to transport the  
refrigerant.  
Another common refrigerantabsorbent pair is ammonia as the refrigerant and  
water as the absorbent. These fluids are more common in small residential  
applications. There are other refrigerantabsorbent combinations; this clinic,  
however, will focus on water as the refrigerant and lithium bromide as the  
absorbent.  
TRG-TRC011-EN  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
notes  
dilute  
solution  
intermediate  
solution  
concentrated  
solution  
Figure 9  
These two fluids, the refrigerant and the absorbent, are mixed inside the chiller  
in various concentrations. The term dilute solution refers to a mixture that  
has a relatively high refrigerant content and low absorbent content. A  
concentrated solution has a relatively low refrigerant content and high  
absorbent content. An intermediate solution is a mixture of dilute and  
concentrated solutions.  
steam or  
hot water  
generator  
condenser  
cooling  
water  
evaporator  
chilled  
water  
heat  
exchanger  
absorber  
Figure 10  
Components of the Absorption Cycle  
The four basic components of the absorption refrigeration cycle are the  
generator and condenser on the high-pressure side, and the evaporator and  
absorber on the low-pressure side. The pressure on the high-pressure side of  
the system is approximately ten times greater than that on the low-pressure  
side.  
8
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
The operating conditions used in this section of the clinic are approximate,  
subject to variation with changing load and cooling-water temperature  
conditions.  
notes  
115°F  
[46.1°C]  
45°F  
[7.2°C]  
1.5 psia  
[10.34 kPa]  
0.15 psia  
[1.034 kPa]  
pressure  
Figure 11  
At a given pressure, the temperature at which a liquid will boil into a vapor is  
the same temperature at which the vapor will condense back into a liquid. This  
curve illustrates the pressures and corresponding temperatures at which water  
(the refrigerant) boils and condenses.  
At atmospheric pressure (14.7 psia [101.3 kPa]), water boils and evaporates at  
212°F [100°C]. When the pressure is decreased, water boils at a lower  
temperature. At the lower pressure, there is less force pushing against the  
water molecules, allowing them to separate easier.  
Just like in the vapor-compression refrigeration cycle, this change in pressure  
allows the evaporator temperature to be low enough for the refrigerant to  
absorb heat from the water being cooled. Likewise, it allows the condenser  
temperature to be high enough for the refrigerant to reject heat to water at  
normally available temperatures. Inside of the evaporator, the pressure is very  
low, 0.15 psia [1.034 kPa] in this example, so that the refrigerant boils at 45ºF  
[7.2ºC]. In the condenser, however, the pressure is much higher (1.5 psia  
[10.34 kPa]) so that the refrigerant condenses at 115ºF [46.1ºC].  
TRG-TRC011-EN  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
notes  
steam or  
hot water  
refrigerant  
vapor  
generator  
concentrated  
solution  
dilute  
solution  
Figure 12  
Starting on the high-pressure side of the cycle, the purpose of the generator is  
to deliver the refrigerant vapor to the rest of the system. It accomplishes this by  
separating the water (refrigerant) from the lithium bromide-and-water solution.  
In the generator, a high-temperature energy source, typically steam or hot  
water, flows through tubes that are immersed in a dilute solution of refrigerant  
and absorbent. The solution absorbs heat from the warmer steam or water,  
causing the refrigerant to boil (vaporize) and separate from the absorbent  
solution. As the refrigerant is boiled away, or generated,the absorbent  
solution becomes more concentrated.  
The concentrated absorbent solution returns to the absorber and the refrigerant  
vapor migrates to the cooler condenser. Physically, the generator and  
condenser are contained inside of the same shell. The pressure in the  
condenser section is less than the pressure in the generator section. This is  
because the temperature of the cooling water flowing through the tubes of the  
condenser is less than the temperature of the steam or hot water flowing  
through the tubes of the generator.  
10  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
notes  
refrigerant  
vapor  
condenser  
cooling  
water  
liquid  
refrigerant  
Figure 13  
Inside the condenser, cooling water flows through tubes and the hot  
refrigerant vapor fills the surrounding space. As heat transfers from the  
refrigerant vapor to the water, refrigerant condenses on the tube surfaces. The  
condensed liquid refrigerant collects in the bottom of the condenser before  
traveling to the expansion device.  
In absorption water chillers, the cooling water system is typically connected to a  
cooling tower.  
liquid  
evaporator  
refrigerant  
expansion  
device  
Figure 14  
From the condenser, the liquid refrigerant flows through an expansion device  
into the evaporator. The expansion device is used to maintain the pressure  
difference between the high-pressure (condenser) and low-pressure  
(evaporator) sides of the refrigeration system. In this example, the expansion  
device is a throttling pipe, which is a long section of pipe with an orifice  
restriction in it. It creates a liquid seal that separates the high-pressure and low-  
pressure sides of the cycle.  
TRG-TRC011-EN  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
As the high-pressure liquid refrigerant flows through the expansion device, it  
causes a pressure drop that reduces the refrigerant pressure to that of the  
evaporator. This pressure reduction causes a small portion of the liquid  
refrigerant to boil off, or flash,cooling the remaining refrigerant to the  
desired evaporator temperature. The cooled mixture of liquid and vapor  
refrigerant then flows into the evaporator pan.  
notes  
refrigerant  
vapor  
chilled  
water  
evaporator  
liquid  
refrigerant  
absorber  
evaporator  
spray pump  
Figure 15  
Inside the evaporator, relatively warm return water from the chilled-water  
system flows through the tubes. An evaporator pump draws the liquid  
refrigerant from the bottom of the evaporator and continuously circulates it to  
be sprayed over the tube surfaces. This maximizes heat transfer.  
As heat transfers from the water to the cooler liquid refrigerant, the refrigerant  
boils (vaporizes) and the resulting refrigerant vapor is drawn into the lower-  
pressure absorber. Physically, the evaporator and absorber are contained inside  
the same shell.  
12  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
notes  
refrigerant  
vapor  
absorber  
intermediate  
solution  
absorber  
spray pump  
dilute  
solution  
cooling  
water  
concentrated  
solution  
Figure 16  
Inside the absorber, the refrigerant vapor is absorbed by the lithium bromide  
solution. As the refrigerant vapor is absorbed, it condenses from a vapor to a  
liquid, releasing the heat it acquired in the evaporator. This heat, along with the  
heat generated during the process of being absorbed, is rejected to the cooling  
water that is circulated through the absorber tube bundle. Absorption of the  
refrigerant vapor creates a low pressure area within the absorber. This lower  
pressure, along with the absorbents affinity for water, induces a continuous  
flow of refrigerant vapor from the evaporator.  
Maximum surface area is provided by spraying the solution over the tube  
bundle. This also provides maximum heat transfer to the cooling water. The  
absorber spray pump mixes concentrated absorbent solution (returning from  
the generator) with dilute solution (from the bottom of the absorber) and  
delivers this intermediate solution to the absorber sprays.  
There are two reasons for using an intermediate solution rather than a  
concentrated solution in the absorber sprays. First, for effective tube wetting, a  
greater quantity of solution is required than is available from the generator.  
Therefore, dilute solution is mixed with the concentrated solution to increase  
the total quantity of solution being sprayed over the tube surfaces. Second, if  
concentrated solution were sprayed directly upon the absorber tube bundle, it  
would be subjected to temperatures that could cause it to crystallizea  
solidification of the bromide salt. Therefore, the concentration is reduced by  
mixing it with dilute solution.  
TRG-TRC011-EN  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
notes  
concentrated  
solution  
heat  
exchanger  
dilute  
solution  
generator pump  
Figure 17  
As the lithium bromide solution absorbs the refrigerant, it becomes diluted and  
has less ability to absorb water vapor. To complete the cycle and sustain  
operation, the absorbent solution must be reconcentrated. Consequently, the  
generator pump continuously returns the dilute solution to the generator to  
again separate the refrigerant vapor from the solution and reconcentrate the  
solution, thus repeating the cycle.  
This cool dilute solution that is pumped from the absorber to the generator, and  
the hot concentrated solution returning from the generator, pass through a  
heat exchanger. This transfer of heat preheats the dilute solution, reducing the  
heat energy required to boil the refrigerant within the generator, and also  
precools the concentrated solution, reducing the required flow rate of cooling  
water through the absorber.  
Notice that in this example cycle, the cooling water passes through the  
condenser after passing through the absorber. Some absorption chiller designs  
split the cooling water and deliver it directly to both the absorber and the  
condenser.  
14  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
notes  
15 psia  
[103.4 kPa]  
5 psia  
[34.5 kPa]  
1 psia  
[6.9 kPa]  
$
&
0.1 psia  
[0.69 kPa]  
%
50°F  
[10°C]  
100°F  
[37.8°C]  
150°F  
[65.6°C]  
200°F  
[93.3°C]  
LiBr solution  
Figure 18  
solution temperature  
Equilibrium Chart  
The performance of the absorption refrigeration cycle can be analyzed using a  
special chart called an Equilibrium Chart for Aqueous Lithium Bromide  
Solutions. This chart plots the vapor pressure (vertical axis) versus the  
temperature (horizontal axis) and concentration (diagonal lines) of the lithium  
bromide (LiBr) solution.  
The chart shows that an increase in concentration ($ to %), at a constant  
solution temperature, results in a decrease in vapor pressure. Conversely, a  
decrease in solution temperature ($ to &), at a constant concentration, results  
in a decrease in vapor pressure. Assuming that no air or other  
noncondensables are inside the chiller, the vapor pressure of the solution  
determines the temperature at which the refrigerant will vaporize. In other  
words, the combination of solution temperature and concentration determines  
the temperature at which the refrigerant will boil (vaporize).  
TRG-TRC011-EN  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
notes  
steam or  
hot water  
condenser  
cooling  
generator  
water  
'
&
evaporator  
chilled  
water  
%
heat  
exchanger  
expansion  
device  
(
)
$
absorber  
Figure 19  
A diagram of a typical absorption refrigeration cycle can be superimposed on  
this equilibrium chart to demonstrate the function of each component in the  
system.  
Realize that the equilibrium chart can only be used for those portions of the  
cycle where the lithium bromide solution is present. It cannot be used for the  
condenser or evaporator sections. The properties of the refrigerant as it passes  
through the condenser, expansion device, and evaporator can be analyzed  
using a pressureenthalpy chart for the refrigerant (water, in this case).  
16  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Absorption Refrigeration Cycle  
notes  
15 psia  
[103.4 kPa]  
5 psia  
[34.5 kPa]  
&
1 psia  
[6.9 kPa]  
1.5 psia  
[10.3 kPa]  
%
'
0.1 psia  
[0.69 kPa]  
$
(
)
50°F  
[10°C]  
100°F  
[37.8°C]  
150°F  
[65.6°C]  
200°F  
[93.3°C]  
LiBr solution  
Figure 20  
solution temperature  
Starting at the absorber, the dilute lithium bromide solution leaves the absorber  
($) at 105°F [40.6ºC] and 59% concentration. This solution passes through the  
heat exchanger, where it is preheated to 175°F [79.4°C] (%). (Notice that there is  
no change in concentration as the solution passes through the heat exchanger.)  
In the generator, the solution absorbs heat from the steam or hot water flowing  
through the tubes. Initially, this only sensibly heats the solution to &, that is, the  
temperature of the solution increases while the concentration stays the same.  
At this point, the refrigerant begins to boil (vaporize) and separate from the  
solution. This increases the concentration of the lithium bromide solution as the  
temperature continues to increase (').  
The concentrated solution ('), now at 215°F [101.7ºC] and 64.5%, passes  
through the heat exchanger where it is cooled to 135°F [57.2ºC] ((). This cooled,  
concentrated solution (() is then mixed with dilute solution from the absorber  
($), and this intermediate solution ()) (118°F [47.8ºC] and 62% concentration) is  
pumped to the absorber spray trees. In the absorber, refrigerant vapor is  
absorbed by the intermediate solution, decreasing its concentration to 59%,  
while heat is transferred to the cooling water. The resulting cooled, dilute  
solution ($) returns to the generator to repeat the cycle.  
This chart also can be used to demonstrate the operating pressures of the cycle.  
In this example, the low-pressure sections of the cycle are operating at  
approximately 0.15 psia [1.034 kPa], and the high-pressure sections are  
operating at approximately 1.5 psia [10.34 kPa].  
TRG-TRC011-EN  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
period two  
Figure 21  
Lithium bromide-and-water absorption chillers are classified by the firing  
methodthat is, how the primary generator is heated and whether it has a  
single- or a multiple-effect generator. Indirect-fired chillers are heated with  
steam or a hot liquid (such as water) that is typically supplied by an on-site  
boiler or a local utility. It can also be heated by waste energy that is recovered  
from the exhaust of a gas turbine or by some other heat recovery device. Direct-  
fired chillers are heated via the combustion of fossil fuels. An absorption chiller  
with a single generator is called a single-effect chiller. Multiple-effect chillers  
have multiple generators.  
Like vapor-compression water chillers, absorption chillers can also be classified  
by the condensing method employed, either air-cooled or water-cooled.  
Physical size limitations typically constrain air-cooled condensing to ammonia-  
and-water absorption equipment that is applied in residential and small  
commercial applications (3 to 5 tons [10 to18 kW]). Most large commercial  
(20 to 1,500 tons [70 to 5,300 kW]) water-and-lithium bromide absorption  
chillers employ water-cooled condensing with cooling towers, because of the  
higher energy efficiency at design conditions.  
18  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
condenser  
generator  
evaporator  
absorber  
Figure 22  
Single-Effect Chiller  
The single-effect absorption water chiller uses a cycle similar to the one  
presented in Period One. It includes a single generator, condenser, evaporator,  
absorber, heat exchanger, and pumps.  
These chillers are typically operated on low-pressure steam (approximately  
15 psig [204.8 kPa]) or medium-temperature liquids (approximately 270°F  
[132.2°C]). Typical coefficients of performance for single-effect water chillers are  
0.6 to 0.8. The coefficient of performance (COP) is a dimensionless ratio  
used to express the efficiency of a refrigeration machine. For an absorption  
water chiller, COP is defined as the ratio of evaporator cooling capacity divided  
by the heat energy required by the generator. A higher COP designates a higher  
efficiency.  
Notice that the COP used to express the efficiency of absorption water chillers  
excludes the electrical energy needed to operate the pumps, purge, and  
controls.  
TRG-TRC011-EN  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
steam or  
condenser  
hot water  
cooling  
water  
generator  
evaporator  
chilled  
water  
heat  
exchanger  
expansion  
device  
absorber  
absorber  
spray pump  
evaporator spray pump  
Figure 23  
generator pump  
Let us review Period One briefly. In the generator, dilute solution absorbs heat  
from the steam or hot water, causing the refrigerant to boil and separate from  
the absorbent solution. As the refrigerant boils away, the absorbent solution  
becomes concentrated and returns to the absorber. The resulting hot  
refrigerant vapor migrates to the cooler condenser, where heat transfers from  
the refrigerant vapor to the cooling water, causing the refrigerant to condense.  
The resulting condensed liquid refrigerant flows through an expansion  
device, causing a pressure drop that reduces the refrigerant pressure and  
temperature to the desired evaporator conditions. The cooled mixture of liquid  
and vapor refrigerant then flows into the evaporator pan, from which the  
evaporator spray pump continuously pumps the liquid refrigerant and sprays  
it over the tubes. As heat transfers from the water to the cooler refrigerant, the  
refrigerant boils (vaporizes) and the resulting refrigerant vapor is drawn into the  
absorber.  
Inside the absorber, the refrigerant vapor is absorbed by the lithium bromide  
solution. As the refrigerant vapor is absorbed, it is also condensed, thereby  
releasing heat to the cooling water. The absorber spray pump mixes  
concentrated absorbent solution (returning from the generator) with dilute  
solution (from inside the absorber) and delivers this intermediate solution to  
the absorber sprays. To complete the cycle, the generator pump returns the  
dilute absorbent solution to the generator to be reconcentrated. This cool dilute  
solution passes through a heat exchanger to be preheated by the hot  
concentrated solution returning from the generator.  
20  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
low-temperature  
high-temperature  
generator  
generator  
condenser  
evaporator  
absorber  
Figure 24  
Double-Effect Chiller  
The double-effect absorption chiller includes the same basic components as the  
single-effect chiller; however, it also includes an additional generator, heat  
exchanger, and pump.  
The high-temperature generator can use steam or hot water (indirect-fired) as  
the energy source, or it can use the combustion of a fuel such as natural gas or  
oil (direct-fired). First we will discuss an indirect-fired, double-effect absorption  
chiller. The direct-fired chiller will be discussed later.  
Indirect-fired, double-effect absorption chillers are typically operated on  
medium-pressure steam (approximately 115 psig [894.3 kPa]) or high-  
temperature liquids (approximately 370°F [187.8°C]). Typical COPs for these  
chillers are 0.9 to 1.2.  
TRG-TRC011-EN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
condensed  
refrigerant  
refrigerant  
vapor  
high-temperature  
generator  
refrigerant  
vapor  
steam or  
hot water  
condenser  
low-temperature  
generator  
to absorber  
Figure 25  
In the high-temperature generator, very high temperature steam or hot  
water flows through tubes that are immersed in an absorbent solution that is at  
an intermediate concentration. The solution absorbs heat from the warmer  
steam or water, causing the refrigerant to boil and separate from the absorbent  
solution. As the refrigerant boils away, the absorbent solution becomes  
concentrated and returns to the absorber.  
The hot refrigerant vapor produced in the high-temperature generator migrates  
to the low-temperature generator, where it flows through tubes that are  
immersed in a dilute solution. The solution absorbs heat from the high-  
temperature refrigerant vapor, causing the refrigerant in the low-temperature  
generator to boil and separate from the absorbent solution. As that refrigerant  
boils away, the concentration of the absorbent solution increases and it returns  
to the absorber.  
The low-temperature refrigerant vapor produced in the low-temperature  
generator migrates to the cooler condenser. Additionally, the liquid refrigerant  
that condensed inside the tubes of the low-temperature generator also flows  
into the condenser.  
22  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
condenser  
low-temperature  
cooling  
generator  
water  
evaporator  
chilled  
water  
low-temperature  
heat exchanger  
expansion  
device  
absorber  
evaporator spray pump  
low-temperature  
generator pump  
absorber  
spray pump  
Figure 26  
Next, the refrigerant travels through the condenser, expansion device,  
evaporator and absorber in a manner similar to refrigerant travel in the single-  
effect absorption chiller.  
The low-temperature generator pump returns the dilute absorbent solution  
to the low-temperature generator to be reconcentrated. This cool dilute solution  
passes through the low-temperature heat exchanger to be preheated by the  
hot concentrated solution returning from the two generators.  
steam-fired  
high-temperature  
high-temperature  
generator  
generator  
pump  
condensate  
heat  
exchanger  
high-temperature  
heat exchanger  
Figure 27  
The high-temperature generator pump draws a portion of the intermediate  
solution from the low-temperature generator and delivers it to the high-  
temperature generator to be reconcentrated. Some of this cooler intermediate  
solution passes through the high-temperature heat exchanger to be  
preheated by the hot concentrated solution coming from the high-temperature  
generator. This reduces the heat energy required to boil the refrigerant inside of  
the high-temperature generator. Precooling the concentrated solution returning  
TRG-TRC011-EN  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
to the absorber reduces the flow rate of cooling water required through the  
absorber.  
notes  
The chiller shown in Figure 27 is steam-fired and includes an additional heat  
exchanger. This condensate heat exchanger transfers heat from the hot  
condensed steam, leaving the high-temperature generator, to the cooler  
intermediate solution returning to the high-temperature generator. Notice that  
this heat exchanger is in parallel with the high-temperature heat exchanger and  
only a portion of the intermediate solution passes through each one. Again, a  
double-effect absorption chiller operating with hot water would not include the  
condensate heat exchanger.  
The precooled, concentrated solution leaving the high-temperature heat  
exchanger then mixes with the rest of the intermediate solution that is returning  
from the low-temperature generator, before traveling to the low-temperature  
heat exchanger.  
low-temperature  
high-temperature  
generator  
generator  
high-temperature  
generator pump  
absorber  
Figure 28  
low-temperature generator pump  
All double-effect absorption chillers are constructed from the same basic  
components: high-temperature generator, low-temperature generator,  
condenser, evaporator, absorber, two solution heat exchangers, and several  
pumps. There are, however, three common methods in which the solution can  
be circulated through the chiller: series, parallel, and reverse-series. The  
double-effect chiller used in the previous example employs the reverse-series  
flow cycle.  
In a reverse-series flow cycle, the dilute solution leaving the absorber is  
pumped to the low-temperature generator, where it is partially concentrated.  
Part of this intermediate solution is then pumped to the high-temperature  
generator, where it is further concentrated. The remaining intermediate  
solution, leaving the low-temperature generator, is mixed with the concentrated  
solution, leaving the high-temperature generator, before returning to the  
absorber.  
The reverse-series flow cycle requires two generator pumps. This, however,  
makes it easier to control in part-load conditions.  
24  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
low-temperature  
high-temperature  
generator  
generator  
absorber  
generator pump  
Figure 29  
In the series flow cycle, the dilute solution from the absorber is pumped  
entirely to the high-temperature generator. As the refrigerant boils away and  
migrates to the low-temperature generator, the absorbent solution becomes  
concentrated. The resulting intermediate solution then flows to the low-  
temperature generator, where it is further concentrated by the refrigerant vapor  
that was created in the high-temperature generator. The concentrated solution  
then flows back to the absorber to repeat the cycle.  
The series flow cycle has been the mainstay of most double-effect absorption  
chiller designs for many years. It is simple because it requires only one  
generator pump and is fairly straightforward to control. The series cycle,  
however, requires a significantly larger heat exchanger to obtain similar COPs  
to the other cycles.  
TRG-TRC011-EN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
low-temperature  
high-temperature  
generator  
generator  
absorber  
generator pump  
Figure 30  
In the parallel flow cycle, the dilute solution from the absorber is split  
between the low-temperature and high-temperature generators. Both streams  
of dilute solution are concentrated in the generators and mix together again  
before returning to the absorber. The parallel flow cycle can be implemented  
using one generator pump (as shown in Figure 30) if a throttling device is used  
to control the flow of solution to the low-temperature generator. Separate  
generator pumps should be used for control over the full range of operating  
conditions.  
In the end, the performance of a double-effect absorption chiller has little to do  
with the flow cycle employed. Instead, the performance depends on the choice  
of operating conditions, the amount of heat transfer surface area, the  
effectiveness of the purge system, the materials of construction, the design of  
the controls, and the manufacturing techniques.  
26  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
low-temperature  
condenser  
generator  
evaporator  
absorber  
high-temperature  
generator  
Figure 31  
Direct-Fired Chiller  
The indirect-fired absorption chillers discussed previously use steam or a hot  
liquid (such as water) as the energy source. In contrast, the high-temperature  
generator of a direct-fired absorption chiller uses the heat released by the  
combustion of a fossil fuel to boil off the refrigerant vapor.  
Common fuels used to fire the burner in the high-temperature generator are  
natural gas, number 2 fuel oil, or liquid petroleum (LP). Additionally,  
combination burners are available that can be switched from one fuel to  
another. Typical COPs for direct-fired, double-effect chillers are 0.9 to 1.1 (based  
on the higher heating value, or HHV, of the fuel).  
condensed  
refrigerant  
refrigerant vapor  
high-  
temperature  
generator  
refrigerant  
vapor  
condenser  
low-temperature  
generator  
Figure 32  
The example direct-fired chiller shown here employs the reverse-series flow  
cycle. In the high-temperature generator, the intermediate solution absorbs  
heat that is generated by the combustion process. Similar to the indirect-fired,  
double-effect chiller, this transfer of heat causes the refrigerant to boil and  
TRG-TRC011-EN  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
separate from the absorbent solution. As the refrigerant boils away, the  
solution becomes concentrated and returns to the absorber.  
notes  
The hot refrigerant vapor produced in the high-temperature generator migrates  
to the low-temperature generator where it flows through the tubes that are  
immersed in a dilute solution. The solution absorbs heat from the high-  
temperature refrigerant vapor, causing the refrigerant in the low-temperature  
generator to boil and separate from the absorbent solution. As that refrigerant  
boils away, the concentration of the solution increases and it returns to the  
absorber.  
The low-temperature refrigerant vapor produced in the low-temperature  
generator migrates to the cooler condenser. Additionally, the liquid refrigerant  
that condensed inside the tubes of the low-temperature generator flows into  
the condenser.  
condenser  
low-temperature  
cooling  
water  
generator  
evaporator  
chilled  
water  
low-temperature  
expansion  
heat exchanger  
device  
absorber  
evaporator spray pump  
low-temperature  
generator pump  
absorber  
spray pump  
Figure 33  
Next, the refrigerant travels through the condenser, expansion device,  
evaporator, and absorber in a manner similar to refrigerant travel in the  
indirect-fired double-effect absorption chiller.  
The low-temperature generator pump returns the dilute absorbent solution  
to the low-temperature generator to be reconcentrated. This cool dilute solution  
passes through the low-temperature heat exchanger to be preheated by the  
hot concentrated solution returning from the two generators.  
28  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
high-temperature  
generator  
high-temperature  
generator  
pump  
high-temperature  
heat exchanger  
Figure 34  
The high-temperature generator pump draws a portion of the intermediate  
solution from the low-temperature generator and delivers it to the high-  
temperature generator to be reconcentrated.  
This cooler intermediate solution passes through the high-temperature heat  
exchanger to be preheated by the hot concentrated solution returning from the  
high-temperature generator. This reduces the heat energy required to boil the  
refrigerant inside the high-temperature generator. Precooling the concentrated  
solution returning to the absorber reduces the flow rate of cooling water  
required through the absorber.  
The precooled, concentrated solution leaving the high-temperature heat  
exchanger then mixes with the rest of the intermediate solution that is returning  
from the low-temperature generator, before traveling to the low-temperature  
heat exchanger.  
TRG-TRC011-EN  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
refrigerant  
hot  
vapor  
water  
auxiliary  
heating bundle  
high-temperature  
generator  
Figure 35  
Chiller/Heater  
One of the benefits of a direct-fired absorption chiller is that it can be used to  
provide both cooling and heating. These chillers, therefore, can be installed in  
systems to supplement, or even replace, primary heating or domestic hot water  
equipment. This can free up equipment-room space that was required for this  
heating equipment.  
In the direct-fired absorption chiller shown here, an auxiliary heating bundle  
can be added, allowing the chiller to make hot water as well as chilled water.  
The auxiliary heating bundle draws in a portion of the refrigerant vapor leaving  
the high-temperature generator. Water flowing through the tubes absorbs heat  
from this hot refrigerant vapor, causing the refrigerant to condense on the tube  
surfaces. This transfer of heat warms the water to a temperature where it can be  
used for comfort heating, domestic hot water needs, or process heating loads.  
The key advantage of this design is that it can be configured to operate in  
cooling only, heating only, or simultaneous cooling/heating modes. For  
simultaneous operation, however, two separate sets of pipes are needed to  
deliver chilled and hot water to the system.  
30  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
L
L
L
L
Figure 36  
Each of these operating modes serves a different load requirement.  
n In cooling only mode, the absorption chiller operates exactly like the  
standard chiller offering. Its function is to make cold water.  
n In heating only mode, the only function of the chiller is to make hot water.  
n In simultaneous cooling/heating cooling priority mode, the primary  
function of the chiller is to make cold water. The heating function is  
secondary and will be performed only if there is excess capacity (burner  
fire).  
n In simultaneous heating/cooling heating priority mode, the primary  
function of the chiller is to make hot water. The cooling function is  
secondary and will be performed only if there is excess capacity (burner  
fire).  
When providing cooling, this type of direct-fired absorption chiller can only  
supply a limited amount of heat, dependent on the current cooling load. If the  
heating and cooling loads for a particular application are substantial and  
simultaneous, it may be best to use this chiller to supplement, instead of  
replace, the main heating equipment.  
TRG-TRC011-EN  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
changeover  
valve  
refrigerant  
vapor  
hot  
water  
evaporator  
high-temperature  
absorber  
generator  
Figure 37  
An alternate method is to use the evaporator as a condenser in the heating  
mode. In this example chiller, by switching the cooling/heating changeover  
valve the chiller switches to heating mode, and hot water can be delivered using  
the same piping system that was used to supply chilled water in the cooling  
mode. The cooling tower and refrigerant pumps can typically be shut off.  
In the direct-fired high-temperature generator, heat that is generated by the  
combustion process causes the refrigerant to boil and separate from the  
absorbent solution. As the refrigerant boils away, the absorbent solution  
becomes concentrated and returns to the absorber.  
The refrigerant vapor produced by the high-temperature generator flows into  
the evaporator. Heat is transferred from the hot refrigerant vapor to the water  
flowing inside the evaporator tubes, causing the refrigerant to condense on the  
tube bundle and fall into the evaporator pan. This condensed liquid refrigerant  
then overflows into the absorber section where it is absorbed by the lithium  
bromide solution.  
The resulting dilute absorbent solution is preheated as it is pumped through the  
low- and high-temperature heat exchangers, eventually returning to the high-  
temperature generator to repeat the cycle.  
The advantage of this design is that no additional bundle is required for heating  
mode. This chiller, however, can only operate in cooling mode or heating  
modeno simultaneous operation is possible.  
32  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Absorption Chiller Types  
notes  
L
L
N Problems with solution stability  
N Increased risk of corrosion problems  
N More expensive pressure vessel design requirements  
N Greater first cost due to added components  
N Larger physical size  
Figure 38  
While they are presently not available, higher-effect absorption chillers are  
being studied for commercial use due their potential for higher COPs. Typical  
COPs for these triple-effect cycles are 1.4 to 1.5. Implementation of these cycles  
into commercial water chillers, however, includes difficulties such as the  
following.  
n Higher solution temperatures create problems with stability of the  
absorbent solution and performance additives, as well as additional  
material corrosion problems.  
n In some cases, higher operating pressures which require high-cost pressure  
vessel designs.  
n Greater first cost due to the need for additional pumps and heat exchangers.  
n Larger physical size.  
As mentioned earlier, other cycles and fluid combinations are also being  
studied for commercial use. The focus of this clinic, however, is limited to water  
chillers that use a lithium bromide-and-water solution.  
TRG-TRC011-EN  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Capacity Control  
notes  
period three  
Figure 39  
The primary objective of the chiller capacity control system is to reliably  
maintain the temperature of the chilled water leaving the evaporator. The  
control system monitors the temperature of the leaving chilled water, compares  
it to the setpoint, and adjusts the amount of solution supplied to the generator  
and the heat input to the generator.  
15 psia  
[103.4 kPa]  
5 psia  
[34.5 kPa]  
1 psia  
[6.9 kPa]  
$
&
0.1 psia  
[0.69 kPa]  
%
50°F  
[10°C]  
100°F  
[37.8°C]  
150°F  
[65.6°C]  
200°F  
[93.3°C]  
LiBr solution  
Figure 40  
solution temperature  
In Period One, the Equilibrium Chart for Aqueous Lithium Bromide Solutions  
was introduced to explain how the combination of solution temperature and  
concentration determines the pressure, and temperature, at which the  
refrigerant will boil (vaporize) in the evaporator. Recall that an increase in  
solution concentration ($ to %), at a constant temperature, results in a decrease  
in vapor pressure. Conversely, a decrease in solution temperature ($ to &), at a  
constant concentration, results in a decrease in vapor pressure. Assuming that  
no air or other noncondensables are inside the chiller, the vapor pressure of the  
solution determines the temperature at which the refrigerant will vaporize. In  
34  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Capacity Control  
other words, the combination of solution temperature and concentration  
determines the temperature at which the refrigerant will boil (vaporize).  
notes  
Varying the temperature at which the refrigerant boils in the evaporator  
changes the capacity of the absorption water chiller. So, in order to control the  
capacity of the chiller to meet the ever-changing system loads, either the  
solution temperature or the solution concentration must be varied. Many chiller  
control strategies vary both simultaneously.  
15 psia  
[103.4 kPa]  
5 psia  
[34.5 kPa]  
&
1 psia  
[6.9 kPa]  
'
%
0.1 psia  
[0.69 kPa]  
(
$
$
)
50°F  
[10°C]  
100°F  
[37.8°C]  
150°F  
[65.6°C]  
200°F  
[93.3°C]  
LiBr solution  
Figure 41  
solution temperature  
A common method used to vary the temperature of the solution is to vary the  
amount of absorbent solution delivered to the generator. At part load, in  
response to a changing leaving-chilled-water temperature, less dilute solution is  
pumped to the generator, reducing the heat energy required to boil off the  
refrigerant vapor. Reduced heat input results in less refrigerant boiled off  
(vaporized) in the generator and a less-concentrated solution returning to the  
absorber (', 56% shown here at part load versus 64.5% at full load shown in  
Figure 20). This less-concentrated solution has a lower affinity for water vapor  
and, therefore, the pressure inside the absorberevaporator sections increases  
(pressures at $ and )). This increased pressure causes the refrigerant inside the  
evaporator to boil at a higher temperature, reducing the temperature difference  
between the chilled water and the refrigerant, thus reducing the chillers  
capacity.  
Because less refrigerant is boiled off in the generator, the refrigerant flow rate  
through the cycle is decreased. Consequently, the heat rejected within the  
absorber is less. Less heat rejected by the cooling tower typically results in  
lower-temperature water returning from the tower, which tends to increase the  
capacity of the chiller and further reduces heat input to the generator.  
Varying the solution flow to the generator can be accomplished in several ways.  
Historically, it has been common to use either a throttling valve or a bypass  
valve. A throttling valve creates an additional flow restriction in the pipe from  
the absorber to the generator, allowing the solution pump to ride up its pump  
curve, reducing the flow rate. A bypass valve diverts a portion of the solution  
back into the absorber, thus reducing the flow to the generator.  
TRG-TRC011-EN  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Capacity Control  
notes  
adjustable-  
frequency  
drive  
absorber  
spray pump  
Figure 42  
generator pump  
In more modern absorption chiller designs, adjustable-frequency drives  
(AFD), also known as variable-speed drives, are used to vary the speed of the  
generator pump motor, thus reducing the flow of solution to the generator.  
AFDs have the added benefit of saving pump energy at part-load conditions.  
energy valve  
generator  
Figure 43  
In order to vary the solution concentration, absorption chillers vary the heat  
input to the generator. This figure shows a modulating energy valve on a  
single-effect, steam absorption chiller. At part load, in response to a changing  
leaving-chilled-water temperature, the energy valve begins to close, reducing  
the amount of heat input to the generator. Similarly, on a direct-fired absorption  
chiller, the amount of heat input to the generator is varied by modulating the  
capacity of the burner.  
While the solution flow to the generator is varied to maintain the desired  
chilled-water temperature, the heat input to the generator is varied to control  
the solution concentration. This assures optimal efficiency and keeps the chiller  
36  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Capacity Control  
out of the condition called crystallizationa solidification of the bromide salt.  
Crystallization will be discussed next.  
notes  
In the past, absorption water chillers would vary the heat input to the generator  
as the primary means of maintaining the desired leaving-chilled-water  
temperature. Because the absorption refrigeration cycle has the capability to  
store energy, using the energy valve as the sole method of control would cause  
the chiller to react very slowly to a change in capacity. By varying the flow rate  
of solution to the generator and absorber sprays, especially with the use of  
adjustable-frequency drives, recent chiller designs are now able to react very  
quickly to ever-changing load and cooling-water conditions.  
15 psia  
[103.4 kPa]  
5 psia  
[34.5 kPa]  
1 psia  
[6.9 kPa]  
0.1 psia  
[0.69 kPa]  
crystallization  
line  
123°F  
[50.6°C]  
50°F  
[10°C]  
100°F  
[37.8°C]  
150°F  
[65.6°C]  
200°F  
[93.3°C]  
LiBr solution  
Figure 44  
solution temperature  
Crystallization  
Lithium bromide is chemically classified as a salt. In its solid state, it has a  
crystalline structure and, like most salts, is soluble in water. With any salt  
solution, there is a saturationtemperature for a given concentration, below  
which the salt begins to leave the solution as a solid. This is called  
crystallization.  
The saturation temperature for various solution concentrations is represented  
by the crystallization line on the equilibrium chart. For example, consider a  
lithium bromide solution of 65% concentration. Above 123°F [50.6°C], all salt  
remains dissolved in the solution. If, however, the solution concentration  
remains the same and the temperature falls below 123°F [50.6°C], the solution  
becomes saturatedmeaning that the solution contains more salt than it can  
hold at that temperatureand the salt begins to leave the solution in a solid  
crystalline form.  
TRG-TRC011-EN  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Capacity Control  
notes  
15 psia  
[103.4 kPa]  
5 psia  
[34.5 kPa]  
&
1 psia  
[6.9 kPa]  
%
'
0.1 psia  
[0.69 kPa]  
crystallization  
line  
$
(
)
50°F  
[10°C]  
100°F  
[37.8°C]  
150°F  
[65.6°C]  
200°F  
[93.3°C]  
LiBr solution  
Figure 45  
solution temperature  
By plotting the single-effect absorption refrigeration cycle on the equilibrium  
chart, it is apparent that crystallization is most likely to occur in the heat  
exchanger. At this particular condition, the 65% concentrated solution (') is  
cooled to 135°F [57.2°C] (() as it passes through the heat exchanger. As noted  
previously, the saturation temperature of 65% solution is 123°F [50.6°C] so  
there is no danger of crystallization.  
Consider, however, if the solution was instead 66% concentrated and cooled to  
the same 135°F [57.2°C] temperature. The saturation temperature for 66%  
concentrated solution is approximately 143°F [61.7°C]. The result would be a  
deposit of salt crystals inside the heat exchanger. Prolonged operation at this  
condition could result in a buildup of salt that would eventually block the  
passages through the heat exchanger, interrupting the operation of the chiller.  
Once a chiller is crystallized, operation can only be resumed after the solution  
temperature is raised above its saturation temperature, above 143°F [61.7°C] in  
this example. At this higher temperature, the salt crystals would return to the  
solution, allowing the chiller to operate again.  
With the advent of microelectronic controls, modern absorption water chillers  
are designed to monitor and control solution concentrations and temperatures,  
allowing the chiller to operate over a broad range of conditions without danger  
of crystallization. In addition, safety controls are available to avoid  
crystallization and even to de-crystallize the chiller if necessary. Therefore,  
crystallization is not the serious problem that it once was with absorption  
chillers.  
38  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Capacity Control  
notes  
L
L
L
Figure 46  
As discussed, the point at which crystallization occurs is determined by the  
temperature and concentration of the concentrated solution inside the heat  
exchanger.  
There are generally three possible causes of crystallization in an absorption  
water chiller:  
n Air and other noncondensables leaking into the chiller  
n Cooling water that is too cold or that fluctuates in temperature too rapidly  
n An electric power failure  
These will be discussed in the following figures.  
L
L
L
L
L
Figure 47  
Probably the most frequent cause of crystallization is that air and other  
noncondensables leak into the chiller. Because the operating pressures inside  
the absorption chiller are less than the atmospheric pressure, air wants to force  
TRG-TRC011-EN  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Capacity Control  
its way into the chiller through any available path. As explained earlier, the  
pressure and temperature inside the evaporator are determined by the  
concentration and temperature of the solution in the absorber. If air leaks into  
the chiller, however, the evaporator pressure increases because a portion of the  
volume inside the evaporatorabsorber sections is taken up by air, which is not  
absorbed by the lithium bromide solution. This increase in the evaporator  
pressure results in higher evaporator temperatures and decreased capacities.  
notes  
Sensing the increasing temperature of the chilled water leaving the evaporator,  
the chiller control system attempts to overcome the condition by increasing the  
amount of solution delivered to the generator and by increasing the amount of  
heat input to the generator. This causes more refrigerant to be boiled off in the  
generator and results in a more concentrated solution being delivered to the  
heat exchanger. Under higher load conditions, it is possible to increase this  
solution concentration to the point where crystallization occurs in the heat  
exchanger.  
In most modern absorption chillers, high-quality construction, smart  
microelectronic controls, and automatic purge systems are extremely effective  
in removing air from inside the chiller, maintaining chiller capacity, and  
avoiding crystallization. Any leaks, however, should be addressed immediately.  
L
N Decreases temperature of dilute solution  
traveling to generator  
N Results in lower  
temperature of  
concentrated solution  
returning to absorber  
N Causes concentrated  
solution inside heat  
exchanger to crystallize  
Figure 48  
Cooling water that is too cold, combined with a high load on the chiller, is  
another possible cause of crystallization. Colder cooling water causes the  
temperature of the dilute solution travelling from the absorber to the generator  
to drop. This cool dilute solution entering the heat exchanger absorbs a greater  
amount of heat from the concentrated solution and, therefore, results in a lower  
temperature of concentrated solution leaving the heat exchanger. If the  
temperature drops low enough, crystallization of the concentrated solution can  
occur.  
In the past, absorption chillers were designed to operate with constant-  
temperature cooling water. With these chillers, a sudden drop in the  
temperature of the cooling water could result in crystallization. The  
microelectronic controls for many modern absorption chillers are designed to  
40  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Capacity Control  
operate over a wide cooling-water temperature range, allowing the cooling-  
water temperature to vary with the load and ambient conditions without the risk  
of crystallization. For optimum control of leaving-chilled-water temperature,  
however, it is still generally recommended to design the system to minimize the  
rate at which the cooling-water temperature varies.  
notes  
L
L
L
Figure 49  
During normal shutdown, an absorption chiller goes through a dilution cycle to  
reduce the concentration of the solution throughout the chiller. At this reduced  
concentration, the chiller may cool off due to lower temperatures of the space  
surrounding the chiller, but it will not be in danger of crystallizing.  
In the event of a power failure, the chiller is not able to go through the normal  
dilution cycle. As the chiller cools down, those sections of the chiller that  
contain highly concentrated solution may crystallize. This is most likely to  
happen if the chiller is operating at or near full load prior to the power failure.  
Additionally, the probability of crystallization becomes greater the longer the  
chiller is without power and the cooler the temperature is in the equipment  
room.  
Today, chiller manufacturers use a variety of methods to ensure that the  
solution is diluted in case of an electric power failure. One method uses a  
combination of normally-open valves that allow refrigerant to flow, by gravity,  
and mix with the concentrated solution.  
In summary, the high-quality construction, smart microelectronic controls, and  
automatic purge systems of most modern absorption chillers have improved  
the monitoring and control of the cycle, to the point where crystallization is not  
the serious problem that it once was with absorption chillers.  
TRG-TRC011-EN  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Capacity Control  
notes  
generator  
evaporator  
heat exchanger  
bypass  
heat  
exchanger  
absorber  
Figure 50  
As a second line of defense, most absorption water chillers include devices that  
allow the chiller to recover in the event that crystallization does occur. Some of  
these devices simply sense impending crystallization, put the chiller through a  
dilution cycle, and shut the chiller down. Other devices keep the chiller  
operating while regaining control of the solution temperature and  
concentration.  
The device shown in the figure above is a heat exchanger bypass that allows  
the chiller to de-crystallize and continue to operate. If crystallization does occur,  
the heat exchanger begins to be blocked, and the flow of concentrated solution  
from the generator to the absorber is reduced. Dilute solution, however,  
continues to flow from the absorber to the generator, resulting in concentrated  
solution backing up inside the generator.  
This backed-up solution will eventually rise enough that the concentrated  
solution spills over into the bypass pipe and returns directly to the absorber,  
bypassing the heat exchanger. As a result, the temperature of the solution in the  
absorber is increased, approaching the temperature in the generator. As this  
warmer solution flows from the absorber, through the heat exchanger, to the  
generator, it raises the temperature of the heat exchanger and de-crystallization  
occurs.  
42  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Capacity Control  
notes  
evaporator pan  
refrigerant  
storage tank  
Figure 51  
Special consideration must be given to controlling the chiller at very low load  
conditions combined with low cooling water temperatures. Under these  
conditions, the chiller reaches equilibrium with a very low solution  
concentration in the absorber. There is a possibility that the chiller might not  
have enough refrigerant to dilute the solution this much. As a result, the lithium  
bromide solution absorbs all of the refrigerant in an attempt to achieve this very  
dilute concentration, causing the evaporator to run dry.  
The loss of refrigerant from the evaporator automatically stops the chiller.  
Additionally, if refrigerant is used to cool and lubricate the pump motors, a  
safety switch may shut the chiller off to protect the motor and pump.  
One solution to this problem is to charge the chiller with additional refrigerant.  
During operation, this extra refrigerant is simply stored in the evaporator pan or  
a supplemental storage tank where it has no adverse effect on chiller operation.  
When low-load and cold-cooling-water conditions are encountered, this  
additional amount of refrigerant is available to effectively dilute the solution in  
the absorber. This allows the chiller to operate throughout its capacity range  
without the need for additional control devices.  
An alternative solution is the use of controls to avoid this potential problem  
area. A float arrangement can be used to sense a low level of refrigerant in the  
evaporator, and in response, open a valve to divert solution from the absorber  
sprays directly back into the absorber sump. This reduces chiller capacity by  
slowing the rate of absorption and, therefore, the rate at which refrigerant is  
vaporized inside the evaporator.  
TRG-TRC011-EN  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Capacity Control  
notes  
purge  
condenser  
vacuum  
pump  
Figure 52  
Purge System  
As presented earlier, the accumulation of air and other noncondensable gases  
undermines the efficiency and reliability of the absorption chiller. Since  
absorption chillers operate below atmospheric pressure, regular operation of a  
purge system is required to remove, or purge,the air and other  
noncondensables that may leak into the chiller. This is necessary to maintain  
the pressures and temperatures within the chiller for maximum efficiency. The  
purge system is also used for early detection of leaks.  
44  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Capacity Control  
notes  
isolation valve  
vacuum  
pump  
purge evaporator  
coil  
purge  
tank  
refrigerant vapor from  
chiller condenser  
liquid refrigerant  
returning to  
chiller condenser  
Figure 53  
This example purge system consists of a purge tank, a small refrigeration  
system, a pump-out system, and controls. The purges refrigeration system  
includes: a small compressor, an air-cooled condensing coil, an expansion  
valve, and an evaporator coil located inside of the purge tank.  
When the chiller is operating, air migrates to the absorber, the area of the chiller  
operating at the lowest pressure. In this example purge system, an eductor  
system moves the air from the absorber to the condenser. Because the purge  
evaporator operates at a lower temperature and pressure than the chiller  
condenser, a mixture of refrigerant vapor and air is drawn from the chiller  
condenser into the purge tank. Inside the purge tank, the refrigerant condenses  
on the cold tubes of the evaporator coil, collects in the bottom of the purge  
tank, and returns to the chiller condenser as a liquid.  
The air does not condense, but instead accumulates in the top portion of the  
purge tank. Eventually, enough air accumulates to cover a large portion of the  
purge evaporator coil. The air insulates this coil, impeding heat transfer and  
reducing the temperature of the refrigerant inside the purge evaporator coil.  
When the purge refrigerant temperature drops below the setpoint, a controller  
signals the need for a pump-out sequence. The controller opens the isolation  
valves, allowing the air to be pumped out of the purge by a vacuum pump.  
When the purge refrigerant temperature rises again, the controller closes the  
isolation valves.  
The purge controls can be used to track and record how often pump-out occurs.  
Excessive purging activity may indicate an air leak or depletion of the corrosion  
inhibitor. The results can be decreased capacity, increased risk of internal  
corrosion, and possible crystallization. Leaks can be detected early by  
comparing pump-out activity over the last 24 hours to the 30-day average.  
TRG-TRC011-EN  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Maintenance Considerations  
notes  
period four  
Figure 54  
Today, after an absorption chiller is installed and put into operation, it functions  
without a full-time attendant. In most cases, the chiller starts and stops on a  
schedule controlled by a building automation system or a simple time clock.  
Water chillers are designed for maximum reliability with a minimum amount of  
maintenance. Like all large mechanical systems, however, certain routine  
maintenance procedures are recommended. Periodic inspection of the purge  
system, cooling tower, fluid levels, heat transfer surfaces, energy supply, and  
pumps helps to maintain the absorption water chiller in peak operating  
condition. This period discusses these general maintenance requirements of  
absorption water chillers.  
L
L
L
Crystallization margin  
Purge pump-out activity  
L
L
L
Chilled water inlet and outlet  
temperatures and pressures  
Cooling water inlet and outlet  
temperatures and pressures  
Gas supply pressure (direct-  
fired)  
Absorber inlet and outlet  
solution temperatures and  
concentrations  
L
L
L
L
Absorber spray solution  
temperature  
Generator inlet and outlet  
solution temperatures  
Evaporator refrigerant  
temperature  
Condenser refrigerant  
temperature  
Figure 55  
Chiller operation should be checked daily and recorded in an operating log.  
Standard operating logs include: solution data; evaporator, absorber, and  
46  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Maintenance Considerations  
condenser inlet and outlet temperatures; and purge operation. Logs are a  
valuable tool for determining the onset of system problems.  
notes  
This data may be obtained either manually or in conjunction with a building  
automation system. The chiller controller should be capable of providing this  
information quickly and easily. An automated control system is an efficient way  
to identify operating changes and schedule maintenance before they become a  
problem.  
L
N Pump teardown and inspection every 5 to 10 years  
N Controls: no maintenance or calibration required  
N Visually inspect overall unit  
N Inspect safety controls and electrical components  
Figure 56  
Absorption chillers typically include the following mechanical components:  
pump(s) to circulate refrigerant and absorbent solution, a purge to remove  
noncondensables from the chiller, a burner (if directly-fired), and a steam or hot  
water control valve (if indirectly-fired).  
Chiller manufacturers use different types of pumps. Some use a single pump,  
while others use individual pumps. Some use hermetic pumps that are cooled  
and lubricated by the pumped solution, and others use pumps with open  
motors that require an external shaft seal. The pumps should be disassembled  
and inspected at routine intervals. Be sure to consult the manufacturer for  
specific recommendations.  
With the advent of microprocessor-based controls, the control panel and  
auxiliary controllers require no recalibration or maintenance. Remotely-  
mounted electronic sensors send information to the chiller controller, which can  
be connected to a building automation system to communicate information  
and allow system-level optimization. These systems can notify the operator  
with an alarm or diagnostic message when a problem occurs.  
As for any mechanical equipment, a daily visual inspection of the chiller is  
recommended to look for condensation, loosened electrical or control wiring,  
or signs of corrosion. Special attention should be given to safety controls and  
electrical components.  
TRG-TRC011-EN  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Maintenance Considerations  
notes  
L
N Check level of liquid refrigerant in purge  
condensing unit  
N Check vacuum pump oil  
L
N Inspect purge condensing coil and clean as  
necessary  
N Change vacuum pump oil as needed  
Figure 57  
Most purges are fully automatic and generally require less maintenance than  
previous-generation manually operated purges. Purge-related maintenance  
procedures are simple.  
n Weekly: With the purge unit operating, check the purge tank condensing  
activity by observing the liquid refrigerant level in the sump sight glass and  
checking the vacuum pump oil.  
n Semiannually: Inspect the air-cooled condensing-unit coil and clean as  
needed. A fouled coil will reduce purge efficiency and capacity. Change the  
vacuum pump oil as needed.  
As mentioned in Period Three, the purge can be used to indicate an air leak or  
depletion of the corrosion inhibitor. Leaks can be detected early by comparing  
pump-out activity over the last 24 hours to the 30-day average. The hermetic  
integrity of the absorption chiller is critical to its operation. Any leaks should be  
addressed immediately.  
48  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Maintenance Considerations  
notes  
L
N Verify proper operation  
L
N Inspect burner firing rate,  
blower, linkage, and  
safety controls  
N Test run with alternate  
fuel, if dual-fuel burner  
Figure 58  
The burner is the heart of a direct-fired absorption chiller. Correct operation is,  
therefore, necessary for optimum chiller performance. Daily checks should be  
made in accordance with the manufacturers recommendations. Each cooling  
season, the burners firing rate, blower, linkage, and safety controls should be  
checked to ensure proper operation. If a dual-fuel burner is being used, it  
should be periodically test run with the alternate fuel to ensure reliable  
operation.  
Manufacturers of direct-fired absorption chillers provide detailed burner  
maintenance checklists, generally with maintenance requirements at 3-, 6-, and  
12-month intervals. To ensure efficiency and increase longevity of both the  
burner and the chiller, consult manufacturersmaintenance manuals and follow  
their instructions.  
With indirect-fired absorption chillers, periodic inspection of the energy valve is  
recommended to check for leaks. Again, consult manufacturersmaintenance  
manuals for specific recommendations.  
TRG-TRC011-EN  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Maintenance Considerations  
notes  
L
N Use a qualified water treatment  
specialist  
N Clean absorber and condenser  
tubes as needed  
N Clean waterside strainers  
N Test tubes every 3 years  
Figure 59  
The use of better heat-transfer materials will reduce future maintenance costs.  
The high-temperature generator, for example, contains high-temperature  
lithium bromide solution that, when exposed to air and other noncondensables,  
is more corrosive than in other sections of the chiller. Better materials in the  
high-temperature generator will improve reliability and require less  
maintenance. When selecting an absorption chiller, both installation and  
maintenance costs must be considered when comparing different designs.  
To ensure optimum heat transfer performance, the heat transfer surfaces must  
be kept free of scale and sludge. Even a thin deposit of scale can substantially  
reduce heat transfer capacity. Engage the services of a qualified water  
treatment specialist to determine the level of water treatment required to  
remove contaminants from the cooling water.  
Scale deposits are best removed by chemical means. During this process, the  
absorber and condenser are commonly isolated from the rest of the cooling-  
tower-water circuit by valves, while a pump circulates cleaning solution through  
the tubes.  
Sludge is removed mechanically. This typically involves removing the water  
boxes from the absorber and condenser, and loosening the deposits with a stiff-  
bristled brush. The loosened material is then flushed from the tubes with clear  
water. As part of this procedure, the strainers in both the chilled-water and  
cooling-water circuits should be cleaned every year.  
Every three years (more frequently in process or critical applications), a  
qualified service organization should perform nondestructive inspections of the  
tubes inside the generator(s), condenser, evaporator, absorber, and heat  
exchanger(s). The eddy-current tube test is a common method.  
50  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Maintenance Considerations  
notes  
L
N Conduct annually or  
semiannually  
N Verifies corrosion inhibitor levels  
N Verifies performance additive  
levels  
L
N Conduct annually  
Figure 60  
An absorption chiller requires a very deep vacuum to operate efficiently. The  
introduction of air and other noncondensables into the chiller will adversely  
affect the chillers performance. In a lithium bromide absorption chiller, where  
the absorbent is a salt, corrosion is a potential problem that must be avoided. It  
may not be possible to completely prevent corrosion inside the chiller, although  
it can be reduced or controlled by the addition of a chemical called a corrosion  
inhibitor.  
Corrosion inhibitors are primarily intended to protect the steel components of  
the chiller from the corrosive action of the lithium bromide-and-water mixture.  
The inhibitor is added to the lithium bromide solution to promote the formation  
of a thin protective layer of oxide quickly and uniformly over the steel  
components inside the chiller. This coating is more impervious to the reaction  
with water, resulting in longer life for the chiller. Corrosion inhibitors also  
reduce the production of noncondensable gas that is generated during the  
corrosion process. The corrosion inhibitor, however, does not directly protect  
the copper components from corrosion. Corrosion protection for the copper  
heat transfer components primarily depends on the materials selected to  
assure maximum design life.  
Additionally, most lithium bromide absorption chillers use a chemical  
performance additive to achieve and maintain design performance. This  
additive considerably enhances the rate at which refrigerant vapor is absorbed  
by the lithium bromide solution.  
TRG-TRC011-EN  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Maintenance Considerations  
If air leaks into the chiller, the corrosion inhibitor is depleted as it reacts with the  
air and produces hydrogen. To maintain chiller efficiency and ensure continued  
corrosion protection, the lithium bromide solution must be analyzed  
notes  
periodically to determine if corrosion inhibitor and performance additive levels  
are within acceptable limits. This is the most important periodic maintenance  
requirement! A laboratory test is required to determine these levels. Suggested  
intervals for testing are once per year for comfort-cooling applications and  
twice per year for chillers in continuous or critical service. Analysis of the  
refrigerant is also recommended. Consult the chiller manufacturer for specific  
corrosion inhibitor and performance additive recommendations.  
52  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Application Considerations  
notes  
period five  
Figure 61  
Several considerations must be addressed when applying absorption water  
chillers, including:  
n Cooling-water temperature limitations  
n Combination chiller plants  
n Special considerations for direct-fired chillers  
n Equipment rating standards  
While not all-inclusive, this list does represent some of the key issues.  
TRG-TRC011-EN  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Application Considerations  
notes  
cooling tower  
diverting  
valve  
bypass  
condenser  
Figure 62  
Cooling-Water Temperature Limitations  
The temperature of the cooling water significantly impacts the operation of an  
absorption chiller. As the temperature of the entering-cooling-water decreases,  
chiller capacity increases.  
Some absorption chiller designs can experience operational problems if the  
cooling-water temperature changes too rapidly or becomes too low. If the  
temperature of the cooling water changes too rapidly, there is potential for the  
absorbent solution to carry over from the generator into the condenser. This  
increases the risk of corrosion in the condenser and evaporator sections of the  
chiller, and reduces the cooling capacity of the chiller. Additionally, low cooling-  
water temperatures increase the risk of crystallization. When applying these  
chillers, a cooling tower bypass is typically recommended for stable control of  
the cooling-water temperature.  
In some new chiller and control designs, variable-speed drives are used to vary  
the flow of solution through the chiller, allowing the chiller to maintain tight  
control in situations where the cooling-water temperature may be highly  
variable. In many cases, this means that a cooling tower bypass may not be  
required, although this should be verified by the system designer. In  
applications that require tight control of the leaving-chilled-water temperature,  
however, it is still generally recommended to design the system to minimize the  
rate at which the cooling-water temperature varies.  
In all cases, the chiller manufacturer should be consulted for specific cooling-  
water temperature limitations and control requirements.  
54  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Application Considerations  
notes  
operate  
absorption  
chiller  
operate  
electric  
chiller  
operate  
electric  
chiller  
1
2
3
4
5
6
7
8
9
10 11 12  
1
2
3
4
5
6
7
8
9
10 11 12  
on-peak  
period  
Figure 63  
Combination Chiller Plants  
Absorption chillers possess two operating characteristics that can noticeably  
improve overall system efficiency and reduce system energy costs.  
First, absorption chillers use fossil fuels rather than electricity. Operating  
absorption chillers at times when on-peak electric energy and/or demand costs  
are high reduces total system utility costs. In such installations, the absorption  
chiller can operate during on-peak periods to avoid the high cost of electricity.  
The electric chiller can run during off-peak periods to take advantage of the  
lower cost of electricity.  
Combination gas-and-electric plants can also exploit the heating capability of  
direct-fired absorption chillers. Both electric and absorption chillers can be used  
to provide summer cooling. If the electric chiller is large enough to satisfy the  
entire winter cooling load, the direct-fired absorption chiller can be switched to  
heating operation to either satisfy the entire winter heating load or supplement  
the primary heating equipment. In such applications, selection of the direct-  
fired absorption chiller should be made to allow downsizing, or perhaps even  
elimination of, the primary heating equipment.  
TRG-TRC011-EN  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Application Considerations  
notes  
absorption  
chiller  
electric  
chiller  
58°F  
[14.4°C]  
50°F  
[10°C]  
42°F  
[5.6°C]  
Figure 64  
The second beneficial operating characteristic is that an absorption chiller  
works more efficiently and produces more cooling with increased leaving-  
chilled-water temperatures.  
Applications with two chillers can be either piped in series or in parallel.  
Though there are advantages associated with each arrangement, the series  
configuration allows a noticeable increase in the overall system efficiency of a  
combination gas-and-electric chiller plant. The series arrangement allows the  
upstream chiller to cool the water part of the way and uses the downstream  
chiller to cool the water the rest of the way to the setpoint. Placing the  
absorption chiller in the upstream position allows it to provide a warmer  
leaving-chilled-water temperature, 50ºF [10ºC] in this example. This not only  
improves the absorption chillers efficiency and capacity, but also reduces the  
cooling load and energy consumption of the electric chiller.  
The series arrangement also has the capability to preferentially load the gas-  
burning chiller, allowing the system to maximize the use of lower-cost fuel  
during periods of high electrical energy cost. Piping two chillers in series also  
means that the entire system-water flow must pass through both chillers.  
Exercise care when selecting the chillers to avoid exceeding their maximum  
flow rates. Notice that the example series arrangement shown here also takes  
advantage of a 16°F [8.9°C] temperature differential across the chillers. This  
increased temperature differential allows the water flow rate to be reduced and  
results in lower pumping costs.  
Overall, the key to successful implementation of a combination gas-and-electric  
chiller plant is an intelligent building automation system that optimizes chiller  
plant operation relative to electrical and gas utility rate structures.  
56  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Application Considerations  
notes  
cooling  
tower  
flue stack  
exhaust duct  
direct-fired  
absorption chiller  
Figure 65  
Special Considerations for Direct-Fired Chillers  
The combustion process that occurs in the burner is key to the operation of a  
direct-fired absorption chiller. It also introduces several additional  
considerations when applying this type of chiller.  
n Combustion air requirements: Combustion equipment is designed and  
operated to ensure complete combustion. Incomplete combustion uses fuel  
inefficiently, can be hazardous because of carbon monoxide production, and  
contributes to air pollution. The quantity of air to provide for a particular  
direct-fired absorption chiller installation is determined by such factors as  
expected variations in fuel and air supplies, system application, burner  
design, and control requirements.  
n Venting of exhaust: A flue exhaust-gas duct and stack must be installed to  
effectively vent the products of combustion out of the building. This duct  
and stack must be designed and installed in compliance with municipal,  
state, and federal regulations. Also, be careful not to locate the stack too  
close to the cooling tower.  
n Gas train: The main gas control train regulates the fuel flow to the burner  
manifold and provides safe operation. The gas train is selected based upon  
the pressure of the gas main and local code requirements.  
n NOx emissions: Nitrogen oxides (NOx) are the combustion emissions  
containing nitrogen and oxygen in direct-fired absorption chiller  
applications. Due to environmental concerns, some local building codes  
require low NOx emissions. Manufacturers have developed low-NOx  
burners that use various methods for reducing emissions. One cost-effective  
method of achieving low emissions in commercial installations, flue-gas  
recirculation, recycles flue gases to lessen NOx formation by reducing the  
flame temperature and the amount of oxygen available for combustion.  
TRG-TRC011-EN  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Application Considerations  
notes  
L
N Combustion air ducted from  
outside the machinery room  
N Refrigerant vapor detector to  
shut down combustion  
process in the event of a  
refrigerant leak  
Figure 66  
In general, ASHRAE Standard 15-1994, Safety Code for Mechanical  
Refrigeration,does not apply to absorption water chillers due to Section 2.3,  
which states:  
This code does not apply where water is the primary refrigerant.  
Section 8.13.6 of the Standard, however, does affect direct-fired absorption  
chillers. It states:  
No open flames that use combustion air from the machinery room  
shall be installed where any refrigerant is used … Combustion  
equipment shall not be installed in the same machinery room with  
refrigerant-containing equipment except under one of the following  
conditions:  
(a) Combustion air is ducted from outside the machinery room and  
sealed in such a manner as to prevent any refrigerant leakage from  
entering the combustion chamber, or  
(b) A refrigerant vapor detector is employed to automatically shut  
down the combustion process in the event of refrigerant leakage.  
When halocarbon refrigerants (such as HCFC-123, HCFC-22, HFC-134a, etc.) are  
present during a combustion process, they can break down into products that  
are both harmful to humans and corrosive to machinery. The intent of  
Standard 15 is to avoid both of these hazards by preventing refrigerant  
exposure to any combustion process. Thus, the use of an open-flame device,  
such as a boiler or the burner of a direct-fired absorption chiller, in a machinery  
room is strictly prohibited by this section unless one of the exceptions is  
employed.  
Exception (a) allows combustion air to be ducted to the open-flame device from  
outside the machinery room in order to prevent air (and refrigerants) present in  
the machinery room from entering the flame. Alternatively, exception (b) allows  
58  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Application Considerations  
a refrigerant vapor detector to monitor refrigerant levels in the machinery  
room. When the detector measures refrigerant levels above those allowable, a  
building automation system is used to automatically shut down the combustion  
process. Due to the lower cost, many building owners employ exception (b) in  
machinery rooms that have direct-fired absorption chillers or boilers.  
notes  
L
N Establish definitions, testing,  
and rating requirements  
L
N Single- and double-effect  
absorption chillers  
N Indirect- and direct-fired  
absorption chillers  
N Water-and-lithium bromide  
solution  
Figure 67  
Equipment Rating Standards  
The Air Conditioning & Refrigeration Institute (ARI) establishes rating standards  
for packaged HVAC equipment. The overall objective of ARI Standard 560 is to  
promote consistent rating of many types and sizes of absorption water chillers.  
It covers single-effect chillers operating on steam or a hot fluid, double-effect  
chillers operating on steam or a hot fluid, and direct-fired double-effect chillers  
operating on natural gas, oil, or liquid petroleum (LP). It pertains to chillers  
using water as the refrigerant and lithium bromide as the absorbent.  
The standard rating conditions used for ARI rating represent typical design  
temperatures and flow rates for which water-cooled systems are designed.  
They are not suggestions for good design practice for a given systemthey  
simply define a common rating point to aid comparisons. Trends toward  
improved system energy efficiency have changed some of the actual conditions  
for specific applications.  
Impurities in the chilled- and cooling-water systems eventually deposit on  
evaporator, absorber, and condenser tube surfaces, impeding heat transfer.  
Catalogued performance data includes a fouling factor that accounts for this  
effect to more closely predict actual chiller performance.  
Remember that the ARI rating is a standardized representation. Many chillers  
do not run at standard rating conditions. Performing a comprehensive energy  
analysis is still the best method of comparing the system operating cost  
difference between two chillers.  
TRG-TRC011-EN  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period six  
Review  
notes  
period six  
Figure 68  
We will now review the main concepts that were covered in this clinic on  
absorption water chillers.  
steam or  
condenser  
hot water  
generator  
evaporator  
chilled  
water  
heat  
expansion  
exchanger  
device  
absorber  
cooling  
water  
Figure 69  
Period One presented the basic single-effect, absorption refrigeration cycle. In  
the generator, dilute solution absorbs heat from the steam or hot water  
flowing through the tubes, causing the refrigerant to boil and separate from the  
absorbent solution. As the refrigerant boils away, the absorbent solution  
becomes concentrated and returns to the absorber. The resulting refrigerant  
vapor migrates to the cooler condenser, where heat transfers from the hot  
refrigerant vapor to the cooling water inside the tubes, causing the refrigerant  
to condense on the tube surfaces. The resulting condensed liquid refrigerant  
flows through an expansion device, causing a pressure drop that reduces the  
refrigerant pressure to that of the evaporator. This pressure reduction causes a  
small portion of the liquid refrigerant to boil off, cooling the remaining  
refrigerant to the desired evaporator temperature. The cooled mixture of liquid  
60  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period six  
Review  
and vapor refrigerant then flows into the evaporator pan, from which the  
evaporator spray pump continuously pumps the liquid refrigerant to be  
sprayed over the tubes. As heat transfers from the chilled water flowing  
through the tubes to the cooler refrigerant, the refrigerant boils (vaporizes) and  
the resulting refrigerant vapor is drawn into the absorber.  
notes  
Inside the absorber, the refrigerant vapor is absorbed by the lithium bromide  
solution, releasing heat to the cooling water which is circulated through the  
tubes. Absorption of the refrigerant vapor creates a low pressure area within  
the absorber, inducing a continuous flow of refrigerant from the evaporator to  
the absorber. The absorber spray pump mixes concentrated absorbent  
solution (returning from the generator) with dilute solution (from inside the  
absorber) and delivers this intermediate solution to the absorber sprays. The  
lithium bromide solution becomes diluted as it absorbs the refrigerant. To  
complete the cycle, the generator pump continuously returns the dilute  
absorbent solution to the generator to be reconcentrated. This cool dilute  
solution passes through a heat exchanger to be preheated by the hot  
concentrated solution returning from the generator.  
Figure 70  
Period Two discussed the various types of absorption water chillers, including  
the single-effect, double-effect, and direct-fired chillers.  
The double-effect absorption chiller includes the same basic components as the  
single-effect chiller, and also includes an additional generator, heat exchanger,  
and pump. The high-temperature generator can use steam or a hot liquid such  
as water as the energy source (indirect-fired) or the combustion of a fossil fuel  
such as natural gas or oil as the energy source (direct-fired).  
This period also introduced the use of the direct-fired absorption chiller/heater  
to provide both cooling and heating.  
TRG-TRC011-EN  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period six  
Review  
notes  
L
N Vary solution flow to generator  
N Vary heat input to generator  
L
N High-quality construction  
N Microelectronic controls  
N Automatic purge systems  
N De-crystallization devices  
L
Figure 71  
Period Three explained the part-load operation of the absorption chiller. It  
described the use of energy valves, burner controls, throttling and bypass  
valves, and adjustable-frequency drives as methods for controlling the capacity  
on the chiller. Valves and AFDs are used to vary the flow rate of solution to the  
generator. Modulating energy valves and burner controls are used to vary the  
heat input to the generator.  
It also introduced the concept of crystallization, which occurs when the  
absorbent solution becomes saturated and the salt begins to leave the solution  
as a solid. Causes of crystallization include: air and other noncondensable  
gases leaking into the chiller, cooling water that is too cold or that fluctuates in  
temperature too rapidly, and an electric power failure. In most modern  
absorption chiller designs, high-quality construction, smart microelectronic  
controls, and automatic purge systems are extremely effective in avoiding  
crystallization. Additionally, most absorption water chillers include devices that  
allow the chiller to recover in the event that crystallization does occur.  
The operation of the purge system as a means of removing air and other  
noncondensables from inside the chiller was also presented.  
62  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period six  
Review  
notes  
L
N Operating log  
N Mechanical components  
N Heat transfer surfaces  
N Absorbent solution analysis (corrosion inhibitor and  
performance additive levels)  
Figure 72  
Period Four described general maintenance requirements for absorption water  
chillers, including:  
n Recommended data for a daily log  
n Recommended maintenance for mechanical components, such as the  
solution and refrigerant pumps, purge, and burner  
n Recommended maintenance for heat-transfer surfaces  
n Required analysis of the absorbent solution to ensure acceptable levels of  
the corrosion inhibitors and performance additives  
L
N Cooling-water temperature limitations  
N Combination gas-and-electric chiller plants  
N Special considerations for direct-fired chillers  
N Equipment rating standards  
Figure 73  
Period Five presented several considerations for applying absorption water  
chillers. These included cooling-water temperature limitations, the advantages  
of using combination gas-and-electric chiller plants, special considerations  
when using direct-fired chillers, and equipment rating standards.  
TRG-TRC011-EN  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period six  
Review  
notes  
Figure 74  
For more information, refer to the following references:  
n Trane product catalogs for absorption water chiller products (Trane literature  
order numbers ABS-DS-1, ABS-DS-4, ABS-DS-6, and ABS-PRC001-EN)  
n Absorption Chiller System Design Applications Engineering Manual (Trane  
literature order number SYS-AM-13)  
n Trane Air Conditioning Manual  
n Equilibrium Chart for Aqueous Lithium Bromide Solutions laminated chart,  
I-P units (Trane literature order number 1-43.198)  
n ASHRAE Handbook Fundamentals  
n ASHRAE Handbook Refrigeration  
For more information on additional educational materials available from Trane,  
contact your local Trane office (request a copy of the Educational Materials  
catalogTrane order number EM-ADV1) or visit our online bookstore at  
64  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quiz  
Questions for Period 1  
1
What are the names of the two working fluids used within the absorption  
cycle?  
%
$
'
)
&
(
Figure 75  
2
3
Identify the components of the absorption refrigeration cycle labeled in  
Figure 75.  
What are the two major components on the high-pressure side of the  
absorption refrigeration cycle? What are the two major components on the  
low-pressure side of the cycle?  
4
5
6
Does the absorption cycle operate at pressures above or below  
atmospheric pressure?  
Which of the following components do not contain absorbent solution?  
(generator, condenser, evaporator, absorber, heat exchanger)  
What is the purpose of the heat exchanger in the absorption refrigeration  
cycle?  
Questions for Period 2  
7
What additional components are included on a double-effect absorption  
chiller versus a single-effect chiller?  
8
Which type of absorption water chiller is capable of providing simultaneous  
cooling and heating?  
TRG-TRC011-EN  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quiz  
Questions for Period 3  
9
Does an increase in solution concentration, assuming a constant solution  
temperature, result in an increase or decrease in vapor pressure?  
10 What is crystallization?  
11 What are the most common causes of crystallization in an absorption chiller  
and how can these conditions be avoided?  
Questions for Period 4  
12 What is the purpose of analyzing the lithium bromide solution?  
Questions for Period 5  
13 True or False: All absorption water chillers require the use of a cooling  
tower bypass for stable control of the cooling-water temperature.  
14 List two special considerations discussed in this clinic for applying direct-  
fired absorption water chillers.  
66  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TRG-TRC011-EN  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Answers  
1
2
Refrigerant (distilled water) and absorbent (lithium bromide)  
$ generator, % condenser, & expansion device, ' evaporator, ( absorber,  
) heat exchanger  
3
4
5
6
Generator and condenser; evaporator and absorber  
Below atmospheric pressure  
Condenser and evaporator  
To preheat the dilute solution returning to the generator, which reduces the  
heat energy required to boil the refrigerant, and precool the concentrated  
solution returning to the absorber, which reduces the flow rate of cooling  
water required to absorb heat in the absorber.  
7
High-temperature generator, high-temperature heat exchanger, and  
possibly an additional pump (depending on the type of flow cycle used)  
8
9
Direct-fired absorption chiller (with an auxiliary heating bundle)  
Decrease in vapor pressure  
10 The process of lithium bromide leaving the solution as a solid when the  
absorbent solution is cooled below its saturation temperature.  
11 Air leaking into the chiller, avoided by quality construction and automatic  
purging. Cooling water that is too cold or that fluctuates in temperature too  
rapidly, avoided by using improved microelectronic controls or a cooling  
tower bypass. Electric power failure, avoided by gravity-fed dilution cycles.  
12 To determine if corrosion inhibitor and performance additive levels are  
within acceptable limits. Air leaking into the chiller can deplete the  
corrosion inhibitor.  
13 False. Many new chiller and control designs are able to maintain control of  
the cycle, even in situations where the cooling-water temperature may be  
highly variable.  
14 Quantity of combustion air required, venting of combustion exhaust, sizing  
of the main gas train, requirements for low NOx emissions, and compliance  
with ASHRAE Standard 15.  
68  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary  
absorbent A substance used to absorb refrigerant and transport it from the  
low-pressure to the high-pressure side of the absorption refrigeration cycle. In  
absorption water chillers, the absorbent is commonly lithium bromide.  
absorber A component of the absorption refrigeration system where  
refrigerant vapor is absorbed by the absorbent solution and rejects heat to  
cooling water.  
adjustable-frequency drive (AFD) A device used to control the capacity of a  
pump by varying the speed of the pump motor.  
ARI Air Conditioning & Refrigeration Institute.  
ARI Standard 560 A publication, titled Absorption Water Chilling and Water  
Heating Packages,used to promote consistent rating methods for many types  
and sizes of absorption water chillers, using water as the refrigerant and lithium  
bromide as the absorbent. It covers single-effect chillers operating on steam or  
a hot fluid; indirect-fired double-effect chillers operating on steam or a hot fluid;  
and direct-fired double-effect chillers operating on natural gas, oil, or liquid  
petroleum (LP).  
ASHRAE American Society of Heating, Refrigerating and Air-Conditioning  
Engineers.  
ASHRAE Standard 15 A publication, titled Safety Code for Mechanical  
Refrigeration,that specifies safe design, construction, installation, and  
operation of refrigerating systems.  
auxiliary heating bundle A separate heat exchanger added to a direct-fired  
absorption chiller to allow it to provide simultaneous cooling and heating.  
chilled water The cold water produced by the chiller (flowing through the  
tubes in the evaporator) and pumped to the air-handler coils throughout the  
building.  
chilled-water system Uses water as the cooling media. The refrigerant inside  
the evaporator absorbs heat from the water and this water is pumped to coils in  
order to absorb heat from the air used for space conditioning.  
coefficient of performance (COP) A dimensionless ratio used to express the  
efficiency of a refrigeration machine. For an absorption water chiller, it is  
defined as the ratio of evaporator cooling capacity divided by the heat energy  
required by the generator, excluding the electrical energy needed to operate the  
pumps, purge, and controls. A higher COP designates a higher efficiency.  
compressor A mechanical device used in the vapor-compression refrigeration  
cycle to increase the pressure and temperature of the refrigerant vapor.  
concentrated absorbent solution A mixture of refrigerant and absorbent that  
has a relatively low refrigerant content and high absorbent content.  
TRG-TRC011-EN  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary  
condenser A component of the absorption refrigeration system in which  
refrigerant vapor is converted to liquid as it rejects heat to cooling water.  
cooling water Water obtained from a source (cooling tower, river, pond) to  
which heat is rejected. This water flows through tubes in the absorber and the  
condenser.  
corrosion inhibitor Chemical added to the absorbent solution to protect the  
steel components of the chiller from the corrosive action of the water and  
lithium bromide solution.  
crystallization The process of the absorbent leaving the solution as a solid,  
when the solution is cooled below its saturation temperature.  
dilute absorbent solution A mixture of refrigerant and absorbent that has a  
relatively high refrigerant content and low absorbent content.  
direct-fired A type of absorption chiller that uses the combustion of a fossil  
fuel (such as natural gas or oil) directly to provide heat to the high-temperature  
generator.  
double-effect A type of absorption chiller that uses two generators, a high-  
temperature generator and a low-temperature generator.  
equilibrium chart A graphical representation of the properties of lithium  
bromide solutions. Vapor pressure is plotted on the vertical axis, solution  
temperature on the horizontal axis, and concentration on the diagonal lines.  
evaporator A component of the absorption refrigeration system where cool  
liquid refrigerant absorbs heat from water (from the building system), causing  
the refrigerant to boil.  
expansion device A component of the absorption refrigeration system used to  
reduce the pressure and temperature of the refrigerant to desired evaporator  
conditions.  
flash The process of liquid refrigerant being vaporized by a sudden reduction  
of pressure.  
generator A component of the absorption refrigeration system in which  
refrigerant vapor boils and is separated from the absorbent solution as it  
absorbs heat from the primary heat source.  
indirect-fired A type of absorption chiller that uses steam or a hot fluid (such  
as water) from an external source to provide heat to the generator.  
intermediate absorbent solution A mixture of refrigerant and absorbent that  
is a combination of dilute and concentrated solutions.  
performance additive Chemical added to the absorbent solution to enhance  
the rate at which refrigerant vapor is absorbed by the lithium bromide solution,  
improving the performance of the cycle.  
70  
TRG-TRC011-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary  
purge A device used to remove air and other noncondensable gases that may  
leak into the low-pressure absorption chiller.  
refrigerant A substance used to absorb and transport heat for the purpose of  
cooling. In a large absorption water chiller, the refrigerant is distilled water.  
saturation temperature The temperature, for a given concentration, at which  
the solution contains the most salt that it can hold. If the temperature drops any  
further, the salt begins to leave the solution in a solid form (crystallize).  
single-effect A type of absorption chiller that uses a single generator.  
throttling pipe A type of expansion device used in absorption water chillers. It  
is a section of pipe with an orifice inside.  
variable-speed drive See adjustable-frequency drive.  
TRG-TRC011-EN  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Literature Order Number  
File Number  
TRG-TRC011-EN  
E/AV-FND-TRG-TRC011-0400-EN  
2803-11-677  
The Trane Company  
Supersedes  
Worldwide Applied Systems Group  
3600 Pammel Creek Road  
La Crosse, WI 54601-7599  
Stocking Location  
La Crosse  
An American Standard Company  
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change  
design and specifications without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Teac Recording Equipment AD RW900 User Manual
Toastmaster Can Opener 2246 User Manual
Triarch Indoor Furnishings 25981 User Manual
Tricity Bendix Clothes Dryer TM 220 W User Manual
Tricity Bendix Clothes Dryer TM 550 User Manual
Tricity Bendix Freezer TB 44 UF User Manual
Uniden Cordless Telephone EXA3245 User Manual
Unified Brands Fryer Braising Pan User Manual
Vincent Audio Stereo Receiver SV 123 User Manual
Vulcan Hart Convection Oven E14 User Manual