UNINTERRUPTIBLE POWER SYSTEM (UPS)
G9000 SERIES
INSTALLATION AND
OPERATION MANUAL
480/480 V 80/100/160/225/300/500/750 kVA
Document: 4GBA0012 Rev. E
P/N 61480-008
January 2013
Download from Www.Somanuals.com. All Manuals Search And Download.
G9000 SERIES
INSTALLATION AND OPERATION MANUAL
480/480 V 80/100/160/225/300/500/750 kVA
Document No. 4GBA0012 Rev. E
P/N 61480-008
January 2013
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT NOTICE
The Instructions contained in this manual are not intended to cover all of the details or variations
in equipment or to provide for every possible contingency to be met in connection with
installation, operation, or maintenance. Should further information be required or should
particular problems arise which are not covered sufficiently the matter should be referred to the
local TOSHIBA sales office.
The contents of this instruction manual shall not become a part of or modify any prior or existing
equipment, commitment, or relationship. The sales contract contains the entire obligation of
TOSHIBA INTERNATIONAL CORPORATION. The warranty contained in the contract between
the parties is the sole warranty of TOSHIBA, and any statements contained herein do not create
new warranties or modify the existing warranty.
Any Electrical or mechanical modifications to this equipment without prior
written consent of TOSHIBA will void all warranties and may void UL/CUL listing.
Unauthorized modifications may also result in equipment damage, personal
injury, or loss of life.
UNINTERRUPTIBLE POWER SYSTEM
If additional information or technical assistance is required call TOSHIBA Customer Support Center toll
free at 1- 800-231-1412, or write to: Toshiba International Corporation, 13131 West Little York Road,
Houston, TX 77041-9990 Attn: UPS Product Manager.
Please complete the following information for your records. Unless otherwise specified on the warranty
card, the warranty period for the UPS or UPS part is 36 months from the shipment date (see bill of lading).
Unless otherwise specified on the warranty card, the warranty period for a UPS battery is 36 months full
replacement, and an additional 7 years pro-rated from the shipment date (see bill of lading).
Keep this manual with the UPS equipment.
Job Number:
Model Number:
Serial Number:
Application:
Shipping Date:
Date of Installation:
Inspected By:
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Purpose and Scope of Manual
This manual provides information on how to safely install, operate, and maintain your TOSHIBA power
electronics product. This manual includes a section on General Safety Instructions that describes the
warning labels and symbols that are used throughout the manual. Read the manual completely before
installing, operating, or performing maintenance on this equipment.
This manual and the accompanying drawings should be considered a permanent part of the equipment
and should be readily available for reference and review. Dimensions shown in the manual are in metric
and/or the English equivalent.
TOSHIBA reserves the right, without prior notice, to update information, make product changes, or to
discontinue any product or service identified in this publication.
TOSHIBA is a registered trademark of TOSHIBA INTERNATIONAL CORPORATION. All other product or
trade references appearing in this manual are registered trademarks of their respective owners.
TOSHIBA shall not be liable for technical or editorial omissions or mistakes in this manual. Nor
shall it be liable for incidental or consequential damages resulting from the use of information
contained in this manual.
This manual is copyrighted. No part of this manual may be photocopied or reproduced in any form without
the prior written consent of TOSHIBA INTERNATIONAL CORPORATION.
© Copyright 2013 TOSHIBA INTERNATIONAL CORPORATION.
All rights reserved.
Printed in Japan
Contacting TOSHIBA Customer Support Center
The TOSHIBA Customer Support Center can be contacted to obtain help in resolving any Uninterruptible
Power System problem that you may experience or to provide application information.
The center is open from 8 a.m. to 5 p.m. (CST), Monday through Friday. The Support Center’s toll free
number in USA is (855) 803-7087.
You may contact TOSHIBA by writing to:
TOSHIBA INTERNATIONAL CORPORATION.
INDUSTRIAL DIVISION
13131 West Little York Rd.
Houston, TX 77041-9990
Attn: UPS Product Manager
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
List of Tables........................................................................................................................................... ii
How to use this Manual...........................................................................................................................1
INTRODUCTION .............................................................................................................................2
SAFETY PRECAUTIONS .......................................................................................................3
GENERAL ...............................................................................................................................6
DEFINITIONS..........................................................................................................................7
OPERATION OVERVIEW.......................................................................................................8
SPECIFICATIONS ................................................................................................................20
OPERATOR CONTROLS AND INDICATORS..............................................................................26
LED DISPLAY .......................................................................................................................27
EPO BUTTON (Emergency Power Off button) (7)................................................................27
LIQUID CRYSTAL DISPLAY (8)...........................................................................................28
2.3.1 Menu .................................................................................................................................28
2.3.2 Input Power Failure ...........................................................................................................32
2.3.3 Fault Indication..................................................................................................................32
EXTERNAL SIGNAL TERMINAL BLOCK ............................................................................34
RemotEyeII INTRODUCTION...............................................................................................39
INSTALLATION AND OPERATION ..............................................................................................45
TRANSPORTATION AND INSTALLATION..........................................................................45
INSTALLATION PROCEDURE.............................................................................................45
PROCEDURE FOR CABLE CONNECTIONS......................................................................46
OPERATING PROCEDURES...............................................................................................70
RESPONSE TO UPS FAILURE ....................................................................................................74
PARTS REPLACEMENT...............................................................................................................75
FAULT CODES..............................................................................................................................76
DAILY INSPECTION......................................................................................................................83
Installation Planning Guides (IPG).............................................................................85
G9000 Installation and Operation Manual
i
Download from Www.Somanuals.com. All Manuals Search And Download.
List of Tables
Table 1.1
Table 1.2
Table 1.3
Table 1.4
Table 1.5.a
Table 1.5.b
Table 1.5.c
Table 1.6
Table 2.1
Table 3.1
Table 3.2
Table 3.3
Table 3.4
Table 3.5
Table 6.1
Table 7.1
UPS installation environment ................................................................................... 4
Rating of bypass input circuit breaker .................................................................... 5
Power specifications................................................................................................. 20
UPS module information .......................................................................................... 21
Detail of specifications.............................................................................................. 22
Typical efficiencies at various loads......................................................................... 24
MTBF and MTTR...................................................................................................... 24
Rating of contactors, breakers and fuses................................................................. 25
Parts list for UPS monitoring .................................................................................... 43
How to transport and install the system ................................................................... 45
List of UPS weights (lbs.) ......................................................................................... 45
Maximum permitted fault current.............................................................................. 46
Recommended cable sizes ...................................................................................... 49
Crimp type compression lug..................................................................................... 50
Fault code................................................................................................................. 77
How to perform daily inspection ............................................................................... 83
ii
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
List of Figures
Figure 1.1
Single line diagram – normal operation.................................................................... 8
Single line diagram – bypass operation ................................................................... 9
Single line diagram – battery operation.................................................................... 10
UPS parts location (80,100kVA)............................................................................... 12
UPS parts location (160,225kVA)............................................................................. 12
UPS parts location (300kVA).................................................................................... 13
UPS parts location (500kVA).................................................................................... 14
UPS parts location (750kVA).................................................................................... 15
Display PCB DPAU-81 ............................................................................................. 16
External I/F PCB IOAU-09 ...................................................................................... 16
Parallel I/F PCB IFAU-08 (80-225kVA) .................................................................. 17
Parallel I/F PCB IFAU-09 (300-750kVA) ................................................................ 17
Main PCB UPGR-M ................................................................................................ 18
Operation/display panel............................................................................................ 26
Main screen.............................................................................................................. 28
Startup/shutdown screen.......................................................................................... 29
Startup guidance ...................................................................................................... 29
Shutdown guidance.................................................................................................. 29
Input values .............................................................................................................. 29
Output values ........................................................................................................... 30
Values in battery operation....................................................................................... 30
Remote/local operation select.................................................................................. 30
Date & time adjustment............................................................................................ 30
Log menu.................................................................................................................. 31
Event log................................................................................................................... 31
Battery log ................................................................................................................ 31
Main screen (battery operation) ............................................................................... 32
Measurement screen (battery operation) ................................................................. 32
Main screen (fault indication) ................................................................................... 32
Message screen ....................................................................................................... 33
Figure 1.2
Figure 1.3
Figure 1.4.1
Figure 1.4.2
Figure 1.4.3
Figure 1.4.4
Figure 1.4.5
Figure 1.5
Figure 1.6
Figure 1.7.1
Figure 1.7.2
Figure 1.8
Figure 2.1
Figure 2.2
Figure 2.3.1
Figure 2.3.2
Figure 2.3.3
Figure 2.4.1
Figure 2.4.2
Figure 2.4.3
Figure 2.5.1
Figure 2.5.2
Figure 2.6.1
Figure 2.6.2
Figure 2.6.3
Figure 2.7.1
Figure 2.7.2
Figure 2.8
Figure 2.9
Figure 2.10.1 External signal terminal block (TN2) ....................................................................... 34
Figure 2.10.2 External signal terminal block (TN1) ....................................................................... 35
Figure 2.11
Figure 2.12
Control wiring for external contacts.......................................................................... 36
Remote "start" contact connections ......................................................................... 37
Figure 2.13.1 Configuration of the RemotEyeII (80-225kVA)......................................................... 39
Figure 2.13.2 Configuration of the RemotEyeII (300kVA).............................................................. 40
Figure 2.13.3 Configuration of the RemotEyeII (500-750kVA)....................................................... 41
Figure 2.14
Figure 2.15
Figure 2.16
Figure 2.17
Connection between display control PCB (SW1) and RemotEyeII module............. 42
PSAU-60 PCB (PS1)................................................................................................ 43
DPAU-81 PCB (SW1)............................................................................................... 43
3BBA0083P001 (Cable1)......................................................................................... 43
G9000 Installation and Operation Manual
iii
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 2.18
Figure 2.19
Figure 2.20
Figure 2.21
Figure 3.1
The connector (CN1) of PSAU-60 (PS1).................................................................. 44
The terminal block (TN) of PSAU-60 (PS1) ............................................................. 44
The connector (CN44) of PSAU-60 (PS1) ............................................................... 44
The connector (CN27) of DPAU-60 (SW1) .............................................................. 44
UPS terminal designation ....................................................................................... 50
Diagram of input/output bus bars and terminal blocks (80-225kVA)........................ 51
Diagram of input/output bus bars and terminal blocks (300kVA)............................. 52
Diagram of input/output bus bars and terminal blocks (500kVA)............................. 53
Diagram of input/output bus bars and terminal blocks (750kVA)............................. 54
Detail of the main cabinet bus bars (300kVA) ........................................................ 55
Detail of the main cabinet bus bars (500kVA) ........................................................ 56
Detail of the main cabinet bus bars (750kVA) ........................................................ 57
Bus bar connection between main cabinet and landing cabinet (300kVA) ............ 58
Bus bar connection between main cabinet and landing cabinet (500kVA) ............ 59
Bus bar connection between main cabinet and landing cabinet (750kVA) ............ 60
Power wire & control wire inter-connect between UPS and battery......................... 61
Power wire connections (parallel system configuration) .......................................... 62
Power and control wire connections for 4 units in MMS (80-225kVA)..................... 63
Figure 3.2.1
Figure 3.2.2
Figure 3.2.3
Figure 3.2.4
Figure 3.3.1
Figure 3.3.2
Figure 3.3.3
Figure 3.4.1
Figure 3.4.2
Figure 3.4.3
Figure 3.5
Figure 3.6
Figure 3.7.1
Figure 3.7.2a Power and control wire connections for 2 units in MMS (300-750kVA)................... 64
Figure 3.7.2b Detail of IFAU-09 Control Wire Connections for 2 units in MMS (300-750kVA) ...... 65
Figure 3.7.3a Power and control wire connections for 3-4 units in MMS (300-750kVA)................ 66
Figure 3.7.3b Detail of IFAU-09 Control Wire Connections for 3-4 units in MMS (300-750kVA)... 67
Figure 3.7.4a Power and control wire connections for 5-8 units in MMS (300-750kVA)................ 68
Figure 3.7.4b Detail of IFAU-09 Control Wire Connections for 5-8 units in MMS (300-750kVA)... 69
Figure 3.8
Figure 3.9
Circuit protectors location......................................................................................... 70
LCD screen (MMS operation)................................................................................... 73
iv
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
How to use this Manual
This manual is designed for ease of use, giving the user easy and quick reference to information.
This manual uses notice icons to draw attention to the user important information regarding the safe
operation and installation of the UPS. The notice icons used in this manual are explained below, and
should be taken into account and adhered to whenever they appear in the text of this manual.
Warning: A warning symbol shows potentially hazardous situation or condition
which could result in personal injury or death, if not avoided.
WARNING
Caution: A caution symbol shows potentially hazardous situation or condition
which could result in personal injury or equipment damage, if not avoided.
CAUTION
Note: A Note symbol shows the information the user or the service personnel
should observe during the UPS operation or service work.
NOTE
Prohibit: A prohibit symbol shows the act the user or the service personnel should
NEVER perform during the UPS installation, operation or service work.
PROHIBIT
Safety Recommendations: If any problems are encountered while following this manual, Toshiba
field service group assistance and correspondence is recommended.
G9000 Installation and Operation Manual
1
Download from Www.Somanuals.com. All Manuals Search And Download.
1
INTRODUCTION
The Toshiba Uninterruptible Power Supply System (UPS) is designed to provide many years of reliable
protection from power failure, brown-outs, line noise, and voltage transients. To ensure optimum
performance of the equipment, follow the manufacturer's instructions. This manual contains
descriptions required to operate the UPS. Please read this manual carefully and retain it for future
reference.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
CAUTION
This manual contains important instructions for the G9000 SERIES Uninterruptible Power Supply
Systems that should be followed during installation and maintenance of the UPS and batteries.
WARNING 1
WARNING
Lethal voltages exist within the equipment during operation. Observe all
warning and cautions in this manual. Failure to comply may result in serious
injury or death. Obtain qualified service for this equipment as instructed.
2
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING 2
CAUTION
In no event will TOSHIBA be responsible or liable for either indirect or consequential damage
or injury that may come from the misuse of this equipment.
Don’t modify the UPS entirely or partially.
Any modifications without authorization by TOSHIBA could result in
personal injuries, death or destruction of the UPS.
PROHIBIT
1.1
SAFETY PRECAUTIONS
APPLICATION
This UPS shall NOT be applied to support equipment (*) that could affect human
lives.
*
• Life support equipment (artificial dialysis, incubators, etc.)
• Toxic gas or smoke eliminators
• Equipment that must be provided under fire laws, construction
standards or other ordinances
• Equipment equivalent to the above
PROHIBIT
Special considerations are required when applying this UPS to the equipment
(**) that affect human safety and/or maintain public services.
**
• Equipment to supervise or control airways, railways, roads,
sea-lanes or other transportation.
• Equipment in nuclear power plants.
• Equipment to control communications.
• Equipment equivalent/similar to the above mentioned.
NOTE
G9000 Installation and Operation Manual
3
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING 3
NOTE
The UPS is to be installed in a controlled environment.
Improper storage and installation environment may deteriorate insulation, shorten
component life and cause malfunctions.
Keep the installation environment per standard described as follows:
TABLE 1.1 UPS Installation Environment
No.
Item
Installation
Environment standard
1
Indoors
location
2
Ambient
temperature
Minimum temperature: 32 °F(0 °C), Maximum temperature: 104 °F(40 °C) The
average temperature over any 24-hour period must be in the range 41 °F (5 °C)
to 95 °F(35 °C).
3
4
5
Relative humidity The relative humidity must be held between 5 and 95%. There must be no
condensation due to temperature changes.
Altitude
This equipment must not be applied at altitude that exceeds 2250m(7380ft)
above seal level.
Dust
Dust in the room where the UPS is installed must not exceed normal
atmospheric dust levels. In particular, that dust should not include iron particles,
oils or fats, or organic materials such as silicone.
6
Inflammable gas There should be no inflammable/explosive gas.
Hydrogen sulfide (H2S)
Sulfurous acid gas (SO2)
Chlorine gas (Cl2)
No more than 0.003 PPM
following
IEC654-4
Part 4
No more than 0.01 PPM
No more than 0.002 PPM
No more than 1 PPM
Ammonia gas (NH3)
Nitrous oxides (NOx)
Ozone (O3)
No more than 0.05 PPM
No more than 0.002 PPM
4
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING 4
NOTE
This UPS does not include a Bypass input circuit breaker (MCCB) to protect
the bypass circuit. The Bypass input circuit breaker (MCCB) is to be field
supplied and installed. Recommended Breaker (MCCB)'s Specifications are
as follows:
TABLE 1.2 Rating of Bypass Input Circuit Breaker
Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac) Breaker (A)
80
480
480
480
480
480
480
480
96
125
150
250
350
500
800
1200
100
160
225
300
500
750
120
192
271
361
601
902
AC input and AC output overcurrent protection and disconnect devices shall be field
supplied and installed. The DC circuit breaker (MCCB) shall be field supplied and installed.
The overcurrent protection device should be installed in the Battery cabinet and rated as
indicated in TABLE 1.6.
Note: The DC input overcurrent protection (Battery disconnect breaker) hereinafter will be
referred as “CB2”.
G9000 Installation and Operation Manual
5
Download from Www.Somanuals.com. All Manuals Search And Download.
1.2
GENERAL
The Toshiba G9000 UPS is designed to provide continuous and clean electrical power to a critical
load. Additionally the UPS monitors power conditions affecting the load. In the event of an input
power failure, the UPS will supply power to the critical load for the specified battery time.
If the input power is not restored promptly, back up power from the UPS battery permits the
orderly shutdown of equipment supported by the UPS. The UPS is simple to start-up, operate and
maintain.
The G9000 SERIES UPS is available in seven kVA sizes - 80, 100, 160, 225, 300, 500, 750 kVA.
Specifications for each kVA model appear in Section 1.5. The principles of operation described
herein are applicable to all models.
This manual provides an overview of the G9000 SERIES components and their functions. The
appearance and purpose of operator controls and indicators is described with procedures for
operation, start-up, shutdown and basic maintenance included.
6
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
1.3
DEFINITIONS
UNINTERRUPTIBLE POWER SUPPLY SYSTEM (UPS) – All components within the UPS
Module Cabinet and associated batteries that function as a system to provide continuous,
conditioned AC power to a load. This is sometimes referred to as the "System".
UPS MODULE CABINET – The metal enclosure which contains the Converter / Charger, Inverter,
Static Transfer Switch, Internal Bypass line, operator controls, and internal control systems
required to provide specified AC power to a load.
UPS MODULE – The Converter / Charger and Inverter assemblies which, under the direction of
the internal control system and operator controls, provide specified AC power to a load.
INVERTER – The UPS components which contain the equipment and controls necessary to
convert DC power from the Converter / Charger, or the battery, to AC power required by the
critical load.
CONVERTER / CHARGER – The UPS components which contain the equipment and controls
necessary to convert input AC power to regulated DC power required for battery charging and for
supplying power to the Inverter.
STATIC TRANSFER SWITCH – The device which connects the critical load to the bypass line
when the Inverter cannot supply continuous power.
BYPASS LINE – The line which conducts electricity directly from the input power source to the critical
load during Maintenance or whenever the UPS is not completely operational.
AC INPUT POWER – Power provided by the electrical utility company, or auxiliary generator,
which is connected to the UPS for supplying the critical load.
BATTERY – The rechargeable battery strings which supply DC power to the inverter to maintain
continuous AC power to the load during AC input power failure conditions.
G9000 Installation and Operation Manual
7
Download from Www.Somanuals.com. All Manuals Search And Download.
1.4
OPERATION OVERVIEW
The UPS provides two power paths between the utility source and the critical load.
Figure 1.1 shows the path for normal operation, with the load powered by the inverter.
Figure 1.2 shows the path for bypass operation, with the load supplied through the static bypass
line.
A) Normal operation: Load power supplied by each system UPS inverter.
FIGURE 1.1 Single Line Diagram – Normal Operation: Load powered by UPS inverter
CB
52S
Bypass
Input
User supplied
MCCB
CB3
Static Transfer
Switch
INVERTER
CONVERTER
CB
CB
AC
Output
Input
User supplied
MCCB
CB1
52C
CHARGER
CB2
Power Flow
Not in Use
Battery
Cabinet
External
Battery
UPS Module
During normal operation, the path through the UPS inverter is used to power the load.
In Figure 1.1 input AC power is converted to DC by the Converter. DC power is utilized to charge
the UPS battery and to provide power to the Inverter. The Inverter converts the DC power to clean AC
power to supply the critical load.
The conversion - inversion process eliminates any voltage transients or fluctuations existing in the
input power before it reaches the critical load.
The power drawn by the critical load is equally shared between all UPS systems when multiple
UPSs are in Parallel Operation. (Refer to Figure 3.6 that shows a sample of Parallel Operation System
Configuration.)
8
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
In the event of a UPS module failure during Parallel Operation, the critical load power will be
continually supplied and shared by all other UPS.
The Bypass Input breaker and cables are to be supplied and installed by the user or
the constructor. (See WARNING 4 on page 5)
NOTE
B) Bypass Operation: Load Power supplied through UPS internal static bypass line.
FIGURE 1.2 Single Line Diagram – Bypass Operation: Load fed through static bypass line.
CB
52S
Bypass
Input
User supplied
MCCB
CB3
Static Transfer
Switch
INVERTER
CONVERTER
CB
CB
AC
Output
Input
User supplied
MCCB
CB1
52C
CHARGER
CB2
Power Flow
Not in Use
Battery
Cabinet
External
Battery
UPS Module
Figure 1.2 shows the Internal Bypass line is a Hard-wired line through 52S which supplies the
critical load with unconditioned bypass input power. Upon switching to the Internal Bypass line, the
Static Transfer Switch line through CB3 (herein after STS contactor CB3) supplies the power
immediately, and then the Internal Bypass line through 52S supplies the power. In the event of a
switching to the Bypass line, the power to the critical load will be uninterrupted. The purpose of this
Internal Bypass line is to route power to the critical load while the UPS module is de-energized
(converter and inverter), and during Start-up before the system is fully operational.
Each UPS internal static bypass line will equally share the power supplied to the critical load
whenever the system is in the Parallel Operation.
G9000 Installation and Operation Manual
9
Download from Www.Somanuals.com. All Manuals Search And Download.
In the event of a load overcurrent, the UPS transfers to bypass without interruption to the critical
load. In the case of the Parallel Operation, all UPS will transfer to bypass without interruption to the
critical load.
The internal control system determines the operation of the two paths, with the load powered from
the inverter being the normal operation.
C) Battery operation: Load Power supplied by UPS battery.
FIGURE 1.3 Single Line Diagram – Battery Operation
CB
52S
Bypass
Input
User supplied
MCCB
CB3
Static Transfer
Switch
INVERTER
CONVERTER
CB
CB
AC
Output
Input
User supplied
MCCB
CB1
52C
CHARGER
CB2
Power Flow
Not in Use
External
Battery
Battery
Cabinet
UPS Module
Figure 1.3 shows that in the event of AC input source failure or interruption, the UPS
Converter(s)* will de-energize and the UPS battery(s)* will immediately discharge and supply DC
power to the Inverter to maintain continuous AC power to the load. This operation will continue until:
a) The battery capacity expires and the inverter turns off, or
b) Input power is restored. (When input power is restored the converter will simultaneously
power the inverter and critical load, and recharge the batteries.)
A fully charged battery will provide power for the specified time at the rated load, or longer, at a
reduced load.
* (s) : In the case of the Parallel Operation
10
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
When power is restored after a low battery shutdown, the UPS converter(s) automatically restarts
operation, the charger(s) recharges the batteries and the Inverter(s) is automatically restarted without
operator intervention. Load is automatically assumed by the inverter without operator intervention.
*
(s) : In the case of the Parallel Operation
The power drawn by the load is equally shared between all UPS regardless of the presence or
absence of the UPS that is (are) in battery operation or not whenever the system is in the Parallel
Operation.
G9000 Installation and Operation Manual
11
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 1.4.1 UPS Parts Location (80,100kVA)
UPS module Front View
8. Parallel I/F PCB
IFAU-08
CPMS
CPMC
EMB
88F
Inverter, Converter,
Charger Unit
5. Relay PCB
RYAU-09
1. LCD touch panel
monitor display
2. Display PCB
DPAU-81
4. Main PCB
UPGR-M
6. External
Communication
Connector
7. Parallel control PCB
TLCR-C
3. External I/F PCB
IOAU-09
Ground Fault Sensor
FDAU-04
CB3
10. Grounding Bar
(E)
52C
52S
CB1
* Item 9 (AC input, AC output, DC input terminal) is not shown in Figure 1.4.1. (Refer to Figure 3.2.1)
FIGURE 1.4.2 UPS Parts Location (160, 225kVA)
UPS module Front View
8. Parallel I/F PCB
IFAU-08
CPMS
CPMC
EMB
88F
Inverter, Converter,
Charger Unit
5. Relay PCB
RYAU-09
1. LCD touch panel
monitor display
2. Display PCB
DPAU-81
4. Main PCB
UPGR-M
6. External
Communication
Connector
7. Parallel control PCB
TLCR-C
3. External I/F PCB
IOAU-09
Ground Fault Sensor
FDAU-04
CB3
10. Grounding Bar (E)
52C
52S
CB1
* Item 9 (AC input, AC output, DC input terminal) is not shown in Figure 1.4.2. (Refer to Figure 3.2.1)
12
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 1.4.3 UPS Parts Location (300kVA)
a) UPS cabinet – Front View
b) Door Backside (Main Cabinet)
1. LCD Touch Panel
Monitor Display
1. LCD Touch
Panel Monitor
Display
5. Power Supply PCB
PSAU-73
Door
Door
2. Display
PCB
DPAU-81
Power
Supply
PCB
Ground Fault
Sensor
PSAU-60
FDAU-04
6. External
Communication
Connector
4. Main PCB
UPGR-M
Landing
Cabinet
Main
Cabinet
c) UPS cabinet – Front Inside View
52S
CB3
CPMC
CPMS
EMB
3. External I/F PCB (IOAU-09)
CB1
52C
9. AC Input
A, B, C
9. Bypass Input
A40, B40, C40
AC Capacitors
9. DC Input
BP, BN
Converter Unit
Chopper Unit
Inverter Unit
9. AC Output
A50, B50, C50
* Item 10 (Grounding bar) is not shown in FIGURE 1.4.3. (Refer to FIGURE 3.2.2).
G9000 Installation and Operation Manual
13
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 1.4.4 UPS Parts Location (500kVA)
a) UPS cabinet – Front View b) Backside of Left Door
1. LCD Touch
Panel Monitor
Display
1. LCD Touch Panel
Monitor Display
Left
Door
Right
Door
Door
2. Display PCB
DPAU-81
Power
Supply
PCB
4. Main PCB
UPGR-M
PSAU-60
6. External
Communication
Connector
Landing
Cabinet
Main
Cabinet
c) UPS cabinet – Front Inside View
52S
CB3
CPMC
3. External I/F PCB (IOAU-09)
CB1
CPMS
EMB
52C
9. AC Input
A, B, C
9. Bypass Input
A40, B40, C40
AC Capacitors
AC Capacitors
9. DC Input
BP, BN
9. AC Output
A50, B50, C50
Converter Unit
Chopper Unit
Inverter
Unit
* Item 10 (Grounding bar) is not shown in FIGURE 1.4.4. (Refer to FIGURE 3.2.3).
14
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 1.4.5 UPS Parts Location (750kVA)
a) UPS cabinet – Front View b) Backside of Left Door
6. External
Communication
Connector
1. LCD Touch
Panel Monitor
Display
Left
Door
Right
Door
1. LCD Touch Panel
Monitor Display
Door
2. Display PCB
DPAU-81
4. Main PCB
UPGR-M
Landing
Cabinet
Main
Cabinet
c) UPS cabinet – Front Inside View
5. Power Supply PCB (PSAU-73)
52S
CPMC
CPMS
EMB
CB3
3. External I/F PCB (IOAU-09)
CB1
52C
9. AC Input
A, B, C
9. Bypass Input
A40, B40, C40
AC Capacitors
AC Capacitors
9. DC Input
BP, BN
9. AC Output
A50, B50, C50
Converter Unit
Chopper Unit
Inverter
Unit
* Item 10 (Grounding bar) is not shown in FIGURE 1.4.5. (Refer to FIGURE 3.2.4).
G9000 Installation and Operation Manual
15
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 1.5 Display PCB DPAU-81
CNV.SW
switch
13. SW6
MAINTENANCE
button
11. SW1
RESET switch
START
button
STOP
button
12. SW5
TEST switch
FIGURE 1.6 External I/F PCB IOAU-09
17. External contact signal terminal block
TN1
TN2
16
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 1.7.1 Parallel I/F PCB IFAU-08 (80-225kVA)
IFAU-08
TLIN TLOUT
CN96 CN95
CBIN
CAIN CAOUT
CBOUT
CN94
FIGURE 1.7.2 Parallel I/F PCB IFAU-09 (300-750kVA)
CN99
TLBIN
CN98
TLAIN
CN97
TLOUT
TLBOUT
CN96
TLIN
CIN
COUT
CN944 CN943 CN942 CN941
CN954 CN953
CB2IN
CN952 CN951
CA1IN
TLAOUT
CB1IN
CA2IN
CB2OUT
CB1OUT
CA2OUT
CA1OUT
G9000 Installation and Operation Manual
17
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 1.8 MAIN PCB UPGR-M
15. SW3
52L S/W switch
14. SW2
BOOT switch
11. SW1
RESET switch
Description of Figures 1.4.1-5 to 1.8:
1. LCD Touch Panel Monitor Display
The Liquid Crystal Display (LCD) Touch Panel Monitor Display indicates power flow, measured
values and fault and error messages via user selectable display screens.
Refer to FIGURE 2.1 for details.
2. Display PCB DPAU-81 (Figure 1.5):
Switches on DPAU-81 board : FOR SERVICE PERSONNEL ONLY
- (11) SW1 (RESET switch)
- (12) SW5 (TEST switch)
- (13) SW6 (MAINTENANCE switch)
3. External I/F PCB IOAU-09 (Figure 1.6):
Signal I/F on IOAU-09 board
- (17) External contact signal terminal block
Refer to FIGURE 2.10.1-2 for details.
18
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Main PCB UPGR-M (Figure 1.8):
Switches on UPGR-M board : FOR SERVICE PERSONNEL ONLY
- (11) SW1 (RESET switch)
- (14) SW2 (BOOT switch)
- (15) SW3 (52L S/W switch)
5. a) Relay PCB RYAU-09 (80-225kVA)
b) Power Supply PCB PSAU-73 (300-750kVA)
6. External Communication Connector
RS232C connector on DPAU-81 board : FOR SERVICE PERSONNEL ONLY
Refer to FIGURE 2.18 for details.
7. Parallel control PCB (not shown)
a) TLCR-C (80-225kVA)
b) TLCR-E (300-750kVA)
For use in Parallel Operation system application : Option
8. Parallel I/F PCB IFAU-08
a) IFAU-08 (80-225kVA)
b) IFAU-09 (300-750kVA)
For use in Parallel Operation system application : Option (Figure 1.7.1 and 1.7.2):
Refer to Figures 3.7.1 to 3.7.4 for details.
9. AC input, AC output, DC input terminal
Refer to Figures 3.2.1 to 3.2.4, 3.3.1 to 3.3.3, 3.4.1 to 3.4.3 for details
10. Grounding Bar (E)
11. "RESET" switch (FOR SERVICE PERSONNEL ONLY)
This switch resets errors resulting from alarm conditions.
12. "TEST" switch (FOR SERVICE PERSONNEL ONLY)
This switch changes system operation to the test-mode.
13. "MAINTENANCE" switch (FOR SERVICE PERSONNEL ONLY)
This switch sets the UPS menu parameters.
14. "BOOT" switch (FOR SERVICE PERSONNEL ONLY)
This switch enables firmware to be loaded on the control board.
15. "52L S/W" switch (FOR SERVICE PERSONNEL ONLY)
This switch prohibits turning on the AC output contactor “52C” during test/maintenance in Parallel
Operation system application.
16. External contact signal terminal block
Terminal block to connect contact signal input/output lines to and from external dry contacts.
Refer to Figure 2.10.1 and 2.10.2 for details.
G9000 Installation and Operation Manual
19
Download from Www.Somanuals.com. All Manuals Search And Download.
1.5
SPECIFICATIONS
The UPS nameplate displays the rated kVA as well as nominal voltages and currents. The
nameplate is located on the inside of the UPS front door.
TABLE 1.3 Power Specifications
Rated output
Power
Input voltage
Bypass input voltage
3 phase / 3 wire
Output voltage
3 phase / 3 wire
3 phase / 3 wire
80kVA / 72kW
100kVA / 90 kW
160kVA / 144kW
225kVA / 202.5kW
300kVA / 300kW
500kVA / 500kW
750kVA / 750kW
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
20
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 1.4 UPS Module Information
a) Overall Dimension
Width
[in.]
(mm)
Depth
[in.]
(mm)
Height
[in.]
(mm)
Net Weight
[lbs.]
(kg)
Typical
Heating
[kBTU/h]
UPS
[kVA]
Cable
Knockout
27.6
(700)
27.6
32.8
(832)
32.8
80.6
(2,047)
80.6
855
(388)
855
(388)
1,160
(526)
1,230
(558)
2,260
(1,025)
3,360
80
10.8
13.5
17.8
25.1
31.7
52.8
79.2
BOTTOM
BOTTOM
100
160
225
300
500
750
(700)
(832)
(2,047)
35.4
(900)
35.4
32.8
(832)
32.8
80.6
(2,047)
80.6
BOTTOM
BOTTOM
(900)
(832)
(2,047)
51.2
(1300)
70.9
(1800)
90.6
32.7
(830.6)
32.7
(830.6)
32.7
80.7
(2,050)
80.7
(2,050)
80.7
BOTTOM/TOP/LEFT
BOTTOM/TOP/LEFT
BOTTOM/TOP/LEFT
(1,525)
4,250
(1,928)
(2300)
(830.6)
(2,050)
b) Packing Dimension
Width
[in.]
(mm)
37.0
(940)
Depth
Height
Gross Weight
UPS
[kVA]
[in.]
(mm)
44.1
[in.]
(mm)
87.4
[lbs.]
(kg)
1,014
(460)
80
(1,120)
(2,220)
37.0
(940)
42.5
44.1
(1,120)
40.2
87.4
(2,220)
87.75
(2,229)
87.75
(2,229)
87.4
1,014
(460)
1,312
(595)
1,433
(650)
2470
100
160
225
300
500
(1,080)
(1,020)
42.5
(1,080)
58.3
40.2
(1,020)
40.2
(1480)
(1020)
(2220)
(1120)
78.3
(1990)
89.0
40.2
(1020)
40.6
87.4
(2220)
87.4
3700
(1678)
4,372
(1983)
750
(Main Cabinet)
(2,260)
(1,030)
(2,220)
750
37.0
44.1
87.4
412
(Landing Cabinet)
(940)
(1,120)
(2,220)
(187)
G9000 Installation and Operation Manual
21
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 1.5.a Detail of Specifications
Rated Output kVA
Rated Output kW
80
72
100
90
160
144
225
300
300
500
500
750
750
202.5
AC INPUT
Configuration
Voltage
Frequency
3 phase, 3 wire
480 V (+15% to -20%)
60 Hz (+/-10%)
Power Factor
>.99 Lagging at 25% – 115% Load
Input kVA
76 kVA
(86 kVA chg)
95 kVA
(107 kVA chg)
151 kVA
(170 kVA chg)
212 kVA
(238 kVA chg)
312 kVA
(336 kVA chg)
521 kVA
(560 kVA chg)
781 kVA
(840 kVA chg)
(Max Input kVA)
Walk-in Function
Start-up Delay
Input Current
1 –30 Seconds (in 1 second increments)
1 –3600 seconds (selectable in 1 second increments)
91 A
114 A
181 A
255 A
376 A
626 A
939 A
(Max Input Current)
Input Current Limiter
Reflected Current THDi
No-Load Static Loss
(103 A)
(129 A)
(204 A)
(286 A)
(404 A)
(673 A)
(1010 A)
~111% Full Load Input Current
3% max. at 60% – 100% load (no input filter required); 6% max. at 25% – 59% load.
1187 W
~108% Full Load Input Current
1187 W
1470 W
1646 W
2653 W
3905 W
5808 W
STATIC BYPASS INPUT
Configuration
Voltage
3 phase, 3 wire
480 V ±10%
60 Hz ±5%
Frequency
Bypass Overload
1000% for 1 cycle
500% for 1 cycle
BATTERY
Type
Ride Through
Lead Acid
Application Specific
480 Vdc
Nominal Voltage
Minimum Voltage
Float Voltage
DC Ripple Current
(w/o batteries)
DC Ripple Current (% of
Full Load DC Current)
Max DC Charging Current
Max. Discharge Current
400 Vdc
Up to 545 Vdc
18 Adc
9 Adc
4.7%
9 Adc
3.8%
11 Adc
2.9%
19 Adc
2.7%
32 Adc
2.7%
48 Adc
2.7%
3.4%
20 A
188 A
25 A
235 A
40 A
372 A
56 A
524 A
75 A
125 A
187 A
776 A
1292 A
1935 A
22
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Rated Output kVA
Batt. Capacity Required
at Full Load Output
Number of Cells
80
75 kWB
100
94 kWB
160
149 kWB
225
210 kWB
300
311 kWB
500
518 kWB
750
776 kWB
240
AC OUTPUT
Configuration
Voltage
3 phase, 3 wire
480 V
Voltage Regulation
Voltage Adj. Range
Voltage Unbalance
±1% (0 – 100% balanced load); ±2% (0 – 100% unbalanced load)
± 5.0% (in 0.5 V increments)
2% maximum at 100% unbalanced load
< 2% THD at 100% linear load; < 5% THD at 100% nonlinear load
2.3
THD (VOUT
)
Crest Factor
Transient Response
±2% maximum at 100% load step; ±1% maximum at loss/return of AC power;
±5% maximum at load transfer to/from static bypass
Less than 20ms
Transient Recovery Time
Frequency
60 Hz
Frequency Synch. Range
Frequency Slew Rate
Frequency Regulation
Phase Displacement
Output Current
±1% to ± 5% (selectable in 1% increments)
1 Hz/s to 5 Hz/s (selectable in 1 Hz/s increments)
±0.01% in free running mode
±1° @ 100% Balanced Load, ±3° @ 100% Unbalanced Load
96 A
120 A
192 A
271 A
361 A
601 A
Unity
902 A
Power Factor
0.9 (0.9 Lagging to 0.95 Leading within output kW rating)
125% for 2 minutes; 150% for 60 seconds
65,000 A (with optional fuses)
Overload Capacity
Withstand Rating
ENVIRONMENTAL
Cooling
125% for 10 minutes; 150% for 60 seconds
100,000 A (with optional fuses)
Forced Air
Operating Temperature
Relative Humidity
Altitude
32 °F to 104 °F (0 °C to 40 °C). Recommended : 68゚F to 86゚F ( 20 °C to 30 °C)
5% – 95% Non Condensing
0 to 7380 feet No Derating at 40゚C
Location
Paint Color
Indoor (free from corrosive gases and dust)
Munsell N1.5 (Black)
Clearance Required
Top: 20 in. (508 mm)
Front: 40 in. (1016 mm)
Top: 23.6 in. (600 mm)
Front: 42.3 in. (1075 mm)
Rear: 0 in. (0 mm)
Rear: 0 in. (0 mm)
Sides: 0 in. (0 mm) if sidecars used, 1 in. (25 mm) if no sidecars used.
Sides: 0 in. (0 mm) if sidecars used, 1 in. (25 mm) if
G9000 Installation and Operation Manual
23
Download from Www.Somanuals.com. All Manuals Search And Download.
no sidecars used.
500
Rated Output kVA
80
100
160
225
300
750
Enclosure
NEMA 1
Audible Noise
Listings/Standards
70 dB @ 1 m
UL 1778; cUL; FCC Class A-Article 47 – Part 15 B;
ISO 9001; ISO14001; ANSI C62.41 (IEEE 587 Cat. B)
3 Years Parts and Labor
Included
72 dB @ 1 m
UL 1778; cUL; IEC 62040-2 Cat. C3;
ISO 9001; ISO14001; ANSI C62.41 (IEEE 587 Cat. B)
73 dB @ 1 m
Warranty
Emergency Power Off
MONITORING
Dry Contacts Included
RS232 Port
Yes, for Input and Output Signals
Included
Intelligent Monitoring
(Optional)
SNMP; MODBus RTU; MODBus TCP; BACNET; METASYS
Display
LCD Touch Panel for Local Monitoring, Operation, and Control
TABLE 1.5.b Typical UPS Efficiencies at Various Loads
% Full Load
UNIT
20%
40%
60%
80%
100%
95.8%
95.8%
96.5%
96.5%
97.0%
97.0%
97.0%
80 kVA
100 kVA
160 kVA
225 kVA
300 kVA
500 kVA
750 kVA
92.5%
92.5%
94.7%
94.9%
94.4%
94.8%
95.5%
94.3%
94.3%
95.7%
96.2%
96.3%
96.7%
96.6%
95.0%
95.0%
96.2%
96.5%
96.9%
97.0%
97.0%
95.2%
95.2%
96.5%
96.5%
97.0%
97.0%
97.0%
TABLE 1.5.c MTBF and MTTR
Parameter
Phase I – 80-225kVA
Phase II – 300-750kVA
MTBF (Mean Time Between Failures): System (With Bypass)
Inverter (Without Bypass)
MTTR (Mean Time to Repair) – Excluding Travel and Shipping Time)
3,081,946 hr.
140,406 hr.
4 hr.
2,633,910 hr.
101,687 hr.
1.5 hr.
24
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 1.6 Rating of Contactors, Breakers and Fuses
OUTPUT CAPACITY OF EQUIPMENT
80kVA
72kW
100kVA
90kW
160kVA
144kW
225kVA
300kVA
300kW
500kVA
500kW
750kVA
750kW
NUMBER
APPLICATION
202.5kW
CB1
CB3
52C
AC input contactor
STS contactor
135A
80A
135A
80A
200A
135A
200A
200A
20A
285A
150A
285A
285A
20A
452A
260A
452A
452A
20A
680A
260A
680A
680A
20A
1005A
350A
1005A
1005A
20A
Inverter output contactor
Bypass contactor
135A
135A
20A
135A
135A
20A
52S
88RC
Control circuit contactor
Battery disconnect breaker
(Recommended)
CB2
225A
125A
125A
125A
300A
150A
150A
150A
400A
250A
250A
250A
600A
350A
350A
350A
800A
500A
500A
500A
1400A
800A
800A
800A
2000A
1200A
1200A
1200A
AC input breaker
(Recommended)
AC bypass breaker
(Recommended)
AC output breaker
(Recommended)
User supply (OPTION)
User supply (OPTION)
User supply (OPTION)
FCU, FCV, FCW
FCR, FCS, FCT
DC fuse
DC fuse
315A / 690V 315A / 690V 200A / 690V 200A / 690V 450A / 690V 630A / 690V 800A / 690V
200A / 690V 200A / 690V 350A / 690V 350A / 690V 450A / 690V 630A / 690V 800A / 690V
FPU, FPV FNU, FNV
FPR, FPS, FPT, FPW,
FNR, FNS, FNT, FNW
DC fuse
-
-
-
-
450A / 690V 630A / 690V 800A / 690V
30A / 600V 30A / 600V 30A / 600V
FUA, FUB, FUC
Control power fuse
Bypass input fuse
30A / 600V
30A / 600V
30A / 600V
30A / 600V
(OPTION)
FSU, FSV, FSW
250A / 690V 250A / 690V 200A / 690V 250A / 690V 250A / 690V 315A / 690V 315A / 690V
FZS1, 2, 3
FBS1, 2, 3
Bypass input ZNR fuse
Control power fuse
5A / 500V
30A / 600V
5A / 500V
3A / 600V
5A / 500V
30A / 600V
5A / 500V
3A / 600V
5A / 500V
30A / 600V
5A / 500V
3A / 600V
5A / 500V
30A / 600V
5A / 500V
3A / 600V
-
-
-
30A / 600V 30A / 600V
30A / 600V
-
FZR1, 2, 3
AC input ZNR fuse
-
-
FEA, FEB, FEC
Parallel control circuit fuse
3A / 600V
3A / 600V
3A / 600V
G9000 Installation and Operation Manual
25
Download from Www.Somanuals.com. All Manuals Search And Download.
2.1
LED DISPLAY
1) Load on inverter [ LOAD ON INVERTER ](green)
Illuminates when power is supplied from inverter to the critical load.
(Indicates the state of inverter transfer switch "52C".)
2) Battery operation [ BATTERY OP. ](orange)
Illuminates when power is supplied from batteries following a power failure.
3) Load on bypass [ LOAD ON BYPASS ](orange)
Illuminates when power is supplied to load devices by static bypass.
(Indicates the state of bypass transfer switch "52S".)
4) Overload [ OVERLOAD ](orange)
Illuminates in overload condition.
5) LCD fault [ LCD FAULT ](red)
Illuminates when LCD is not responding.
6) UPS fault [ UPS FAULT ](red) [Annunciator: intermittent or constant tones]
Illuminates when an error occurs in the system. In this case, the details of the error are
indicated on the display panel.
2.2
EPO BUTTON (Emergency Power Off button) (7)
When activated, the Emergency Power Off (EPO) function shuts down the UPS module. The
critical load will lose power and also shutdown. The EPO function can be performed either locally or
remotely.
G9000 Installation and Operation Manual
27
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3
LIQUID CRYSTAL DISPLAY (8)
The Liquid Crystal Display (LCD) touch panel indicates power flow, measured values, operational
guidance, data records and error messages. The LCD panel has a back-light which facilitates viewing
in different ambient lighting conditions. The LCD will automatically clear and turn off, if the screen is not
activated within 3 minute period. The LCD is turned back on when it is touched again. The LCD
ERROR indicator is cleared after 24 hours and can be reproduced by pressing any key on the panel.
2.3.1 Menu
A) MAIN MENU (FIGURE 2.2)
The LCD panel indicates power flow and measured values, while also operating the start/stop
function. The LCD panel also allows the user to verify the status and operation of the UPS Module.
FIGURE 2.2
Main screen
The following will be displayed when the START/STOP key on the MAIN MENU is pressed (Jump
into OPERATION MENU) :
1) Startup/Shutdown Guidance (FIGURES 2.3.1 to 2.3.3)
The display indicates the Startup and Shutdown guidance for the UPS system. If this operation is
PIN protected, the user is required to enter the security PIN before the screen can be accessed.
When in remote mode, the message “REMOTE operating model” will appear on this Screen. The
user cannot operate the start and stop functions without changing the setup from remote mode to local
mode.
When bypass voltage is abnormal, the message “Bypass voltage abnormal” will appear.
-Start: When the bypass voltage is abnormal, the LCD asks the operator if an interrupted
transfer is acceptable (Load may be lost).
-Stop: When the bypass voltage is abnormal, the user cannot transfer from inverter to bypass
line.
28
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 2.3.1 Startup/Shutdown Guidance
FIGURE 2.3.2 Startup guidance
FIGURE 2.3.3 Shutdown guidance
Follow Startup/Shutdown guidance accordingly.
B) MEASUREMENT MENU (FIGURES 2.4.1 to 2.4.3)
This screen shows details of measured values. Input and Output values are displayed. During
Battery operation, Remaining battery power and Run time are also displayed.
FIGURE 2.4.1 Input values
G9000 Installation and Operation Manual
29
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 2.4.2 Output values
FIGURE 2.4.3 Values in Battery operation
C) OPERATION MENU (FIGURES 2.5.1 to 2.5.2)
This screen prompts the user to select: (a) whether the start & stop operation will be performed by
local or remote operation; (b) date & time adjustment; (c) battery equalizing charge. The battery
equalizing charge operation key will appear when battery equalizing charge is set up (Setup is based
on battery type).
FIGURE 2.5.1 Remote/Local operation select
FIGURE 2.5.2 Date & Time adjustment
30
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
D) LOG MENU (FIGURES 2.6.1 to 2.6.3)
This LOG MENU displays two Touch icons in EVENT LOG and BATTERY LOG.
Pressing the EVENT LOG icon, up to 50 condition/operation records will be displayed. Press ▲
or ▼ button for page turning.
Pressing the BATTERY LOG icon, Number of battery operations and Summed battery operation
time are displayed.
FIGURE 2.6.1 Log menu
FIGURE 2.6.2 Event log
FIGURE 2.6.3 Battery log
G9000 Installation and Operation Manual
31
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3.2 Input Power Failure
During an Input Power Failure, the UPS inverter will be powered by the UPS batteries. The
following will be displayed on the main and measurement screen (Indication of battery operation and
remaining battery time).
FIGURE 2.7.1 Main screen
FIGURE 2.7.2 Measurement screen
(Battery operation)
(Battery operation)
The LCD will display a battery low voltage message when the battery capacity is near depletion.
The End of Battery Discharge announcement is displayed when the battery end voltage is reached. At
this time, the inverter will perform an electronic shutdown to prevent battery loss of life typical from
extreme deep discharge conditions. When the input power is restored, the inverter will automatically
restart to power the load, and the batteries will be simultaneously recharged. The End of Battery
announcement is shown at the bottom of the screen.
2.3.3 Fault Indication
“MESSAGE” and “SILENCE ALARM” icons will appear on the main menu when UPS failure
condition has occurred.
FIGURE 2.8 Main screen (Fault indication)
The following will be displayed when the MESSAGE icon on the main menu is pressed.
32
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
1) MESSAGE
The display shows a fault code, the description of the fault and a guidance of what action is to be
taken by the user. A maximum of 10 faults are displayed at one time. If an input power failure occurs
during a fault condition, the fault indication and input power failure announcement are alternatively
displayed at 5 second intervals.
FIGURE 2.9 Message screen
2) SILENCE ALARM
This icon will appear when a failure occurs. The audible alarm (announcing the failure) can be
silenced by pressing this icon.
G9000 Installation and Operation Manual
33
Download from Www.Somanuals.com. All Manuals Search And Download.
2.4
EXTERNAL SIGNAL TERMINAL BLOCK
The UPS is equipped with a series of input/output terminals for external annunciation of alarms
and for remote access of certain UPS functions. The layout of terminals is shown in Figure 2.10.1 and
2.10.2 with a functional description of the input/output port presented. OUT1 to OUT8 are user
programmable, but factory default settings are shown in Figure 2.10.1.
Adding same external I/F PCB “IOAU-09”, doubling signal outputs is applicable for OUT1 to OUT8.
FIGURE 2.10.1 External Signal Terminal Block (NEC Class2)
TN2
1
SUMMARY ALARM (Triggers on
fault alarm only)
2
4
3
5
OUT1: LOAD ON BYPASS
OUT2: LOAD ON INVERTER
6
7
OUT3:BATTERY OPERATION
8
9
OUT4: CONVERTER OPERATION
10
12
14
16
18
20
11
13
15
17
19
OUT5: BATTERY LOW VOLTAGE
OUT6: OVERLOAD
OUT7: SPARE
OUT8: TOTAL ALARM (Triggers
on any alarm including faults.)
52C CLOSE
*1
*1 Relay contactor (52C close): Normally Closed
UPS
34
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 2.10.2 External Signal Terminal Block (NEC Class2)
TN1
(+)
1
3
5
7
9
2
4
CB2 UVR
(-)
Battery Breaker Panel
CB2 AX
Load Circuit Breaker
52L AX
6
IN1: REMOTE INVERTER START
IN2: REMOTE INVERTER STOP
IN3: BATTERY TEMP. HIGH
8
(User supplied dry
contact)
10
12
14
16
18
20
11
13
15
17
19
IN4: POWER DEMAND
REMOTE EPO
UPS
G9000 Installation and Operation Manual
35
Download from Www.Somanuals.com. All Manuals Search And Download.
A) Output Contacts (for external alarm annunciation)
Output contacts consist of form “A”(NO) dry type contacts. Rated capacity of all output contacts is NEC
Class2 (30Vdc/1Adc). All dry contacts should be operated at their rated values or lower. Figure 2.11
illustrates a typical installation. The external relay can also be a lamp, LED, computer, etc.
FIGURE 2.11 Control Wiring for External Contacts
UPS Cabinet
External to UPS
Cabinet
Terminal
Terminal
Relay
Coil
Relay
Contact
NEC Class 2
Power Source
Details of output alarm contacts : TN2
Terminals 1 to 2 "Summary Alarm" contact
User supplied
Activated only when a major fault has occurred with the system.
Terminals 3 to 4 "Load on Bypass" contact (OUT1)
Activated when the power is supplied from the static bypass input.
Terminals 5 to 6 "Load on Inverter" contact (OUT2)
Activated when the power is supplied by the inverter.
Terminals 7 to 8 "Battery Operation" contact (OUT3)
Activated when the battery is operating following an AC power failure.
Terminals 9 to 10 "Converter Operation" contact (OUT4)
Activated when the converter is operating.
Terminals 11 to 12 "Battery Low Voltage" contact (OUT5)
Activated when the battery voltage drops below discharge end voltage level during inverter
operation (i.e. During AC fail condition).
Terminals 13 to 14 "Overload" contact (OUT6)
Activated when an overload has occurred to the system.
Terminals 15 to 16 "Spare" contact (OUT7)
Terminals 17 to 18 "Total Alarm" contact (OUT8)
Activated by major fault, minor fault and alarm events.
Terminals 19 to 20 "52C Close" contact (OUT9)
Activated when the inverter output contactor 52C has closed. Form “B”(NC).
36
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
The UPS is equipped with a selectable output contact feature.
The above alarms are the default settings.
Contact Toshiba International Corporation for setup information.
NOTE
B) Input Contacts (for remote access of UPS)
External contacts are provided by the user of the UPS system. Terminal voltage at the UPS is
24VDC. Provide external dry contact accordingly.
Do not apply voltages to remote access input terminals.
Damage to UPS may result.
PROHIBIT
Refer to Figure 2.12 for a typical wiring configuration. Although this figure applies to the remote
start/stop terminals, the same wiring arrangement is used for emergency stop; power demand; and
battery temperature high.
FIGURE 2.12
Remote "Start" Contact Connections
External to UPS
Cabinet
UPS Cabinet
Relay
Coil
Start
Start
Switch
Common
0.5S- 4S
ON
OFF
24 VDC
Relay Coil current : 8.3mA
Use Momentary Switches Only
User supplied
G9000 Installation and Operation Manual
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Details of input contacts for remote access : TN1
Terminals 7 to 8 Remote "Inverter Start" input terminal (IN1)
Used to start inverter from a remote location. UPS must be programmed for remote
operation. Refer to Operations Menu for procedure.
Terminals 9 to 10
Remote "Inverter Stop" input terminal (IN2)
Used to stop inverter from a remote location. UPS must be programmed for remote
operation. Refer to Operations Menu for procedure.
Terminals 11 to 12 "Battery Temp. High" contact input (IN3)
Input fed by a thermocouple that monitors battery temperature. The converter float
voltage level is reduced for battery over-temperature conditions. External
thermocouple is user supplied
Terminals 13 to 14 "Power Demand” Command contact input (IN4)
This contact is used to control the input power. Power demand is turned ON when
the contact is closed, and power demand is turned OFF when the contact is open.
(The Power demand function is custom designed by the factory to match the users
specific system specifications. Contact the factory for additional information.)
Terminals 15 to 16 "Remote EPO" contact input
Used to perform a remote UPS Emergency Power Off (EPO).
The load will be dropped.
The UPS is equipped with a selectable input contact item.
The above items are the default settings.
Contact Toshiba International Corporation for setup information.
NOTE
In all cases, a switch having a protective cover is recommended in order to reduce
the possibility of accidental operation.
CAUTION
38
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
2.5
RemotEyeII INTRODUCTION
The “RemotEyeII”* is available as a UPS system monitoring tool. The RemotEyeII supplies a
network function to monitor UPS units via Simple Network Management Protocol (SNMP) and
Hypertext Transfer Protocol (HTTP) methods.
The RemotEyeII module is installed at the rear of the front door in G9000 UPS units. The
configuration of the RemotEyeII is shown in FIGURE 2.13.1 (80-225kVA), FIGURE 2.13.2 (300kVA)
and FIGURE 2.13.3 (500-750kVA).
FIGURE 2.13.1
Configuration of the RemotEyeII (Overview: 80-225kVA)
PSAU-60
(PS1)
Cable2
Cable3
(provided)
Cable1
(provided)
DPAU-81
(SW1)
RemotEyeII
* Consult Toshiba International Corporation for details on“RemotEyeII” monitoring software
and its capabilities.
G9000 Installation and Operation Manual
39
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 2.13.2
Configuration of the RemotEyeII (300kVA)
Back of the front door (Main cabinet)
RemotEyeII
DPAU-81
(SW1)
Cable2
Cable3
(provided)
PSAU-60
(PS1)
Cable1 (provided)
* Consult Toshiba International Corporation for details on“RemotEyeII” monitoring software
and its capabilities.
40
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 2.13.3
Configuration of the RemotEyeII (Overview: 500-750kVA)
Back of the front left door (Main cabinet)
RemotEyeII
Cable2, Cable3
(provided)
PSAU-60
(PS1)
Cable1
(provided)
DPAU-81
(SW1)
* Consult Toshiba International Corporation for details on“RemotEyeII” monitoring software
and its capabilities.
G9000 Installation and Operation Manual
41
Download from Www.Somanuals.com. All Manuals Search And Download.
The Power Supply PCB (PSAU-60, designated as PS1) and the Cable1 (designated as
3BBA0083P001) are equipped with G9000 UPS units.
The Cable2 (D-sub 9pin) and the Cable3 (12V power cable) are included in the RemotEyeII
package.
The Power Supply PCB (PS1) provides connectivity between the Display Control PCB (DPAU-81,
designated as SW1) and the RemotEyeII module in G9000 UPS units.
The RemotEye II communicates with the UPS via a Cable2. The connection is described in
FIGURE 2.14 below.
The UPS has to be de-energized when the RemotEyeII module is installed for
safety reason.
CAUTION
FIGURE 2.14
Connection between Display Control PCB (SW1) and RemotEyeII module
DPAU-81
SW1
Cable1
3BBA0083P001
PSAU-60
PS1
(male)
Cable3
Cable2
12V Power Cable
D-sub 9-pin Cable
(receptacle)
(RJ45)
RemotEyeII
(RJ45)
(RJ45)
42
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
The parts (included RemotEyeII) for UPS monitoring are listed below.
TABLE 2-1 Parts list for UPS monitoring
Parts No.
Part name
PSAU-60* :Power supply PCB (PS1)
3BBA0083P001 :Cable1
Qt’y
1
1
2
3
4
5
1
RemotEyeII module
1
D-sub 9-pin to RJ45 Cable:Cable2
1
12V Power Cable:Cable3
1
* – PCB revision suffix may be applied.
FIGURE 2.15 PSAU-60 PCB (PS1)
D-sub connector CN1
to be connected with
RemotEyeII.
Connector CN44
to be connected with
CN27 of DPAU-81(SW1).
Terminal block TN
to feed 12VDC power
to RemotEyeII.
(12V across P to N)
Connected with
3BBA0083P001(Cable1)
Shown in FIGURE 2.17.
Optional interface CN2
to give 12VDC power
(12V Pin#1 to #2)
(Note 12VDC exposed)
FIGURE 2.16 DPAU-81 (SW1)
Connector CN27
to be connected with
CN44 of PSAU-60(PS1).
FIGURE 2.17 3BBA0083P001 (Cable1)
D3200 5pin
(housing)
G9000 Installation and Operation Manual
43
Download from Www.Somanuals.com. All Manuals Search And Download.
2.6 CONNECTOR DEFINITION
FIGURE 2.18 The connector (CN1) of PSAU-60 (PS1)
DB9
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Pin 7
Pin 8
Pin 9
Description
Not used
-
RXD
TXD
-
Receive data
Transmit data
Not used
Signal ground
Not used
Not used
Not used
Not used
5
9
4
8
3
7
GND
2
6
-
-
-
-
1
D-SUB 9Pin (male)
FIGURE 2.19 The terminal block (TN) of PSAU-60 (PS1)
1
TB2
Pin 1
Pin 2
Description
+12VS +12VDC
GND(S) +12VDC ground
P
N
2
Terminal Block 2Pin
FIGURE 2.20 The connector (CN44) of PSAU-60 (PS1)
D5
Description
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
RXD
TXD
GND
Receive data
Transmit data
Signal ground
1
2
3
4
5
+24VS +24VDC
GND(S) +24VDC ground
D3200 5Pin (contact)
FIGURE 2.21 The connector (CN27) of DPAU-60 (SW1)
D5
Description
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
RXD
TXD
GND
Receive data
Transmit data
Signal ground
1
2
3
4
5
+24VS +24VDC
GND(S) +24VDC ground
D3200 5Pin (contact)
44
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
3
INSTALLATION AND OPERATION
3.1
TRANSPORTATION AND INSTALLATION
TABLE 3.1 How to transport and install the system
Transportation
Transport unit with forklift.
Installation
Using the pre-drilled four holes in the UPS
channel base, anchor the unit using
appropriate hardware. (Not provided)
If carry by overhead crane, use four M12
eyebolts. (Not provided)
Do not transport UPS cabinet laid horizontally.
PROHIBIT
Cabinets must be maintained upright within ± 15° of the vertical
during handling.
NOTE
3.2
INSTALLATION PROCEDURE
A) Note the load tolerance of the floor
Refer to Table 3.2 for list of UPS weights.
TABLE 3.2 List of UPS weights
UPS Capacity (kVA)
80
100
160
225
300
500
750
Weight (lbs)
855
855
1160
1230
2260
3360
4250
B) Minimum clearance required for ventilation
Right side
1 in. (25 mm) (not required when sidecars are used)
1 in. (25 mm) (not required when sidecars are used)
0.0 inch (0 mm)
Left side
Back side
Top side (80-225kVA)
Top side (300-750kVA)
20 inches (500 mm) (for air flow)
23.6 inches (600 mm) (for air flow)
C) Space requirement for routine maintenance
Allow for the following space at the time of installation.
Front (80-225kVA)
Front (300-750kVA)
Sides
40 inches (1000 mm)
42.3 inches (1075 mm)
0.0 inch (0 mm)
Back side
0.0 inch (0 mm)
Top side
20 inches (50 mm)
G9000 Installation and Operation Manual
45
Download from Www.Somanuals.com. All Manuals Search And Download.
D) External Battery Supply
Please refer to the following when installing and maintaining batteries:
1. The customer shall refer to the battery manufacturer's installation manual for
battery installation and maintenance instructions.
2. The maximum permitted fault current from the remote battery supply, and the
DC voltage rating of the battery supply over-current protective device are
NOTE
shown in Table 3.3.
TABLE 3.3 Maximum Permitted Fault Current
UPS Capacity
DC Voltage
Rating (V)
Maximum Fault
(kVA)
80
Current Permitted (A)
25,000
480
480
480
480
480
480
480
100
160
225
300
500
750
25,000
25,000
25,000
25,000
25,000
25,000
3.3
PROCEDURE FOR CABLE CONNECTIONS
1. Confirm the capacity of the UPS being installed. Identify the input/output power
terminal blocks accordingly as shown in the Figures 3.1 through 3.5.
2. Connect the internal control wire and power wire.
(1) Control wire Inter-connect
1. CB2 UVR to terminal TN1-1, 2 of external I/F PCB IOAU-09.
2. CB2 ON Auxiliary to terminal TN1-3, 4 of external I/F PCB IOAU-09.
(2) Power wire (AC input, Bypass input, AC output) Inter-connect
a.) From user’s distribution panel
1. X1 (A-phase) to A bus bar in UPS
2. X2 (B-phase) to B bus bar in UPS
3. X3 (C-phase) to C bus bar in UPS
b.) DC Input to UPS
1.
2.
Positive cable to BP bus bar in UPS
Negative cable to BN bus bar in UPS
46
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
After the completion of the input power cables connection:
With a phase rotation meter, check that the phase rotation of the AC Input power
terminals A, B and C as well as the Bypass Input power terminals A40, B40 and C40
are correct. The proper phase rotation is clockwise A(R) → B(S) → C(T).
NOTE
3. Connect the grounding conductor from the input service
entrance to the UPS Ground Bar (E).
REQUIRED
4. Two (2) sources feeding the UPS:
(1) Connect the AC input power cables from the input service entrance to the AC input power
terminals, identified as A, B, C in Figures 3.1 and 3.2.1 – 4. Input cables must be sized
for an ampere rating larger than the maximum input drawn by the converter. (Refer to
equipment nameplate for current ratings.) Confirm that an external bypass input circuit
breaker (MCCB) is installed (refer to WARNING 4, page 5). Connect the bypass input
power cables from the input service entrance to the bypass input power terminals,
identified as A40, B40 and C40 in Figures 3.1 and 3.2.1 – 4. Bypass input cables must be
sized for an ampere rating larger than the maximum output current capacity of the UPS.
Refer to Table 3.4 for recommended cable sizes.
(2) Connect the external signal terminal block as desired. Refer to Section 2.4 and Figure
2.10 for functional description. 14 AWG (2mm2), or less, shielded conductor is
recommended.
5. One (1) source feeding the UPS:
(1) Confirm that an external input circuit breaker sized to protect both the AC input and the
bypass line is installed. (Refer to equipment nameplate for current ratings.) Connect the
bypass input power cables from the input service entrance to the bypass input power
terminals, identified as A40, B40 and C40 in Figures 3.1 and 3.2.1 – 4. Input cables must
be sized for an ampere rating larger than the maximum current capacity of the UPS.
Refer to Table 3.4 for recommended cable sizes.
(2) Using adequately sized conductors and referring to the appropriate figure identified in
Figures 3.1 and 3.2.1 – 4, connect jumper bypass terminals A40, B40, C40 to AC input
power terminals A, B, C as identified in Figures 3.1 and 3.2.1 – 4.
G9000 Installation and Operation Manual
47
Download from Www.Somanuals.com. All Manuals Search And Download.
(3) Connect the external signal terminal block as desired. Refer to Section 2.4 and Figure
2.10 for functional description. 14 AWG (2mm2), or less, shielded conductor is
recommended.
1. Confirm that all UPS internal contactors (breakers) "CB1", "CB2", and "CB3"
are open before energizing UPS.
2. UPS power terminals are supplied with stud type fittings.
It is recommended that compression lugs be used to fasten all input/output power
NOTE
cables.
6.
Procedure for Cable Connections for Parallel Operation System
(1) Confirm the number of units to be connected in parallel. Identify the input/output power
terminal blocks and control wire connections for parallel operation systems as shown in
the appropriate Figures 3.6 and 3.7.1 – 4.
(2) Connect the external control wire and power wire.
Use Ethernet STP (Shielded Twisted Pair) Cable for all communication cabling.
Use of UTP (Unshielded Twisted Pair) Cable may cause a malfunction.
NOTE
a.) Control wire connection
Parallel configuration wiring (Refer to Figure 3.6 and 3.7.1 – 4)
-
52L control signal from Toshiba Tie Cabinet (TTC) to UPS-n IOAU-09 (TN1–
5 , 6).
a.1) 80-225kVA
-
-
Parallel control signal for CN94 as shown in Fig. 3.7.1.
Parallel control signal for CN96 and CN95 as shown in Fig. 3.7.1.
a.2) 300-750kVA
-
Parallel control signal for CN941, CN942, CN943, CN944, CN951, CN952,
CN953, CN954 as shown in Fig. 3.7.2 – 4.
-
Parallel control signal for CN96, CN97, CN98 and CN99 as shown in
Fig. 3.7.2 – 4.
b.) Power wire connection
From UPS AC Output Terminals to Toshiba Tie Cabinet (TTC) (Refer to Figure 3.6
and 3.7.1 – 4)
48
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 3.4 Recommended Cable Sizes
Input Side
Cable
Size
Output Side
Cable
Size
Bypass Side
Cable
Size
DC Input Side
Cable
Size
kVA
Input
Output
Torque
ft. lbs
Torque
ft. lbs
Torque
ft. lbs
Torque
ft. lbs
Capacity Voltage Voltage
1 AWG –
1/0 AWG
2/0 AWG –
3/0 AWG
250 MCM –
17-22
ft. lbs
17-22
ft. lbs
17-22
ft. lbs
17-22
ft. lbs
29-39
ft. lbs
29-39
ft. lbs
29-39
ft. lbs
1 AWG –
1/0 AWG
2/0 AWG –
3/0 AWG
250 MCM –
17-22
ft. lbs
17-22
ft. lbs
17-22
ft. lbs
17-22
ft. lbs
29-39
ft. lbs
29-39
ft. lbs
29-39
ft. lbs
1 AWG –
1/0 AWG
2/0 AWG –
3/0 AWG
250 MCM –
17-22
ft. lbs
17-22
ft. lbs
17-22
ft. lbs
17-22
ft. lbs
29-39
ft. lbs
29-39
ft. lbs
29-39
ft. lbs
3/0 AWG –
4/0 AWG
17-22
ft. lbs
17-22
ft. lbs
17-22
ft. lbs
17-22
ft. lbs
29-39
ft. lbs
29-39
ft. lbs
29-39
ft. lbs
80kVA
480V
480V
480V
480V
480V
480V
480V
480V
(2) x 1 AWG –
(2) x 2/0 AWG
(2) x 3/0 AWG –
(2) x 250 MCM
(2) x 350 MCM –
(2) x 400 MCM
(3) x 300 MCM –
(3) x 350 MCM
(4) x 500 MCM –
(5) x 300 MCM
(6) x 400 MCM –
(6) x 500 MCM
100kVA 480V
160kVA 480V
225kVA 480V
300kVA 480V
500kVA 480V
750kVA 480V
300 MCM
500 MCM –
300 MCM
500 MCM –
300 MCM
500 MCM –
(2) x 250 MCM
(2) x 250 MCM –
(2) x 300 MCM
(3) x 300 MCM –
(3) x 350 MCM
(4) x 350 MCM –
(5) x 250 MCM
(2) x 250 MCM
(2) x 250 MCM –
(2) x 300 MCM
(3) x 300 MCM –
(3) x 350 MCM
(4) x 350 MCM –
(5) x 250 MCM
(2) x 250 MCM
(2) x 250 MCM –
(2) x 300 MCM
(3) x 300 MCM –
(3) x 350 MCM
(4) x 350 MCM –
(5) x 250 MCM
*1 – The cables must be selected to be equal to the sizes listed in the table.
*2 – Voltage drop across power cables not to exceed 2% of nominal source voltage.
*3 – Allowable ampere-capacities based on 75 °C insulated copper conductor at ambient temperature of 30 °C.
*4 – All wiring to be in accordance with all applicable national and/or local electrical codes.
G9000 Installation and Operation Manual
49
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 3.5 Crimp Type Compression Lug
WIRE
WIRE
STRAND
CLASS
B
RECOMMENDATION
CRIMP TOOL REQUIRED
SIZE
BURNDY TYPE Y35 OR Y46
(CODE)
1 AWG
VENDOR CAT. NO.
BURNDY YA1C
COLOR KEY
GREEN
GREEN
---
DIE INDEX
11 / 375
11 / 375
1019
12 / 348
12 / 348
1020
ILSCO
BURNDY
BURNDY
ILSCO
BURNDY
BURNDY
ILSCO
BURNDY
BURNDY
ILSCO
BURNDY
BURNDY
ILSCO
BURNDY
BURNDY
ILSCO
BURNDY
BURNDY
ILSCO
BURNDY
BURNDY
ILSCO
CRA-1L
YA25-LB
YA25
CRA-1/OL
YA25-LB
YA26
CRA-2/OL
YA27-LB
YA27
CRB-3/OL
YA28-LB
YA28
CRB-4/OL
YA29-LB
YA29
CRA-250L
YA30-LB
YA30
CRA-300L
YA32-LB
YA31
I
B
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
250 MCM
300 MCM
350 MCM
400 MCM
PINK
PINK
I
B
---
BLACK
BLACK
---
ORANGE
ORANGE
---
13
13
I
B
1021
14 / 101
14 / 101
1022
I
B
PURPLE
PURPLE
---
YELLOW
YELLOW
---
15
15
I
B
1023
16
16
I
B
1024
WHITE
WHITE
---
17 / 298
17 / 298
1026
18 / 324
18 / 324
1027
I
B
RED
CRA-350L
YA34-LB
YA32
CRA-400L
YA36-LB
RED
I
B
BURNDY
BURNDY
ILSCO
---
BLUE
BLUE
---
19 / 470
19 / 470
1027
I
BURNDY
500 MCM
B
BURNDY
ILSCO
BURNDY
YA34
CRA-500L
YA38-LB
BROWN
BROWN
---
20 / 299
20 / 299
1029
I
NOTE: When using crimp type lugs, the lugs should be crimped to the specifications given in the
manufacturer's instructions for both crimp tool and lug.
FIGURE 3.1 UPS Terminal Designation
Terminals
A40
B40
52S
Bypass
Input
C40
CB3
Static Transfer
Switch
Converter
/Charger
Inverter
Terminals
52C
Terminals
A50
B50
CB1
AC
Input
A
B
C
AC
Output
C50
Terminals
BP
BN
CB2
External
Battery
50
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.2.1. Diagram of input/output bus bars and terminal blocks (80-225kVA)
Location of bus bars and terminal blocks (Bottom Entry)
Detailed Power Terminals
H=80.6” (2047mm) D=32.8” (832mm)
160kVA to 225kVA : 35.4” (900mm)
80kVA to 100kVA : 27.6” (700mm)
For power terminals, use 1/2” (12mm) Diameter bolts.
UPS module
External
Block
IOAU-09
DC Input
AC Input
Bypass Input
B40
AC Output
B50
BN
BP
C
A
AC
Output
A50,B50,C50
B
A40
C40
A50
C50
AC
Input
A,B,C
Grounding
Bar (E)
Bypass
Input
A40,B40,C40
UPS module
Battery
Input
BN,BP
G9000 Installation and Operation Manual
51
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.2.2. Diagram of input/output bus bars and terminal blocks (300kVA)
Location of bus bars and terminal blocks (Bottom/Top/Left Side Entry)
Detailed Power Terminals
H=80.7” (2050mm) D=32.7” (830.6mm)
For power terminals, use 1/2” (12mm) diameter bolts.
51.2" (1300)
A
E
External
Block
IOAU-09
Grounding
Bar
B
AC Input
AC Input
A, B, C
C
A40
B40
C40
BP
Bypass Input
A40, B40, C40
Bypass
Input
DC Input
BP, BN
AC Output
A50, B50, C50
DC Input
BN
A50
B50
C50
Grounding Bar
(not shown)
AC
Output
15.8" (400)
UPS module (300kVA)
52
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.2.3. Diagram of input/output bus bars and terminal blocks (500kVA)
Location of bus bars and terminal blocks (Bottom/Top/Left Side Entry)
Detailed Power Terminals
H=80.7” (2050mm) D=32.7” (830.6mm)
70.9" (1800)
For power terminals, use 1/2” (12mm) diameter bolts.
A
E
External
Block
IOAU-09
Grounding
Bar
B
AC Input
AC Input
A, B, C
C
A40
B40
C40
BP
Bypass Input
A40, B40, C40
Bypass
Input
DC Input
BP, BN
AC Output
A50, B50, C50
DC Input
BN
A50
B50
C50
Grounding Bar
(not shown)
AC
Output
18.5" (470)
UPS module (500kVA)
G9000 Installation and Operation Manual
53
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.2.4. Diagram of input/output bus bars and terminal blocks (750kVA)
Location of bus bars and terminal blocks (Bottom/Top/Left Side Entry)
Detailed Power Terminals
H=80.7” (2050mm) D=32.7” (830.6mm)
90.6" (2300)
For power terminals, use 1/2” (12mm) diameter bolts.
A
E
External
Block
IOAU-09
Grounding
Bar
B
AC Input
AC Input
A, B, C
C
A40
B40
C40
BP
Bypass Input
A40, B40, C40
Bypass
Input
DC Input
BP, BN
AC Output
A50, B50, C50
DC Input
BN
A50
B50
C50
Grounding Bar
(not shown)
AC
Output
19.7" (500)
UPS module (750kVA)
54
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.3.1 Detail of the main cabinet bus bars (300kVA)
BUS BAR DETAIL
(TOP VIEW)
BUS BAR DETAIL
(TOP VIEW)
G9000 Installation and Operation Manual
55
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.3.2 Detail of the main cabinet bus bars (500kVA)
BUS BAR DETAIL
(TOP VIEW)
BUS BAR DETAIL
(TOP VIEW)
56
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.3.3 Detail of the main cabinet bus bars (750kVA)
BUS BAR DETAIL
(TOP VIEW)
G9000 Installation and Operation Manual
57
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.4.1 Bus bar connection between main cabinet and landing cabinet (300kVA)
BUS BAR CONNECTION
(TOP VIEW)
ALTERNATE
BUS BAR CONNECTION
(TOP VIEW)
Main
Cabinet
Landing
Cabinet
58
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.4.2 Bus bar connection between main cabinet and landing cabinet (500kVA)
BUS BAR CONNECTION
(TOP VIEW)
ALTERNATE
BUS BAR CONNECTION
(TOP VIEW)
Landing
Cabinet
Main
Cabinet
G9000 Installation and Operation Manual
59
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.4.3 Bus bar connection between main cabinet and landing cabinet (750kVA)
BUS BAR CONNECTION
(TOP VIEW)
ALTERNATE
BUS BAR CONNECTION
(TOP VIEW)
Landing
Cabinet
Main
Cabinet
60
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.5 Diagram of Power Wire & Control Wire Inter-Connect between UPS and Battery
UVR
2
DC Breaker for Battery
G9000 Installation and Operation Manual
61
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.6
Diagram of Power Wire Connections (Parallel System Configuration)
Toshiba Tie Cabinet (TTC)
UPS-1
52MB
Maintenance
Bypass Breaker
Bypass
52S
Inverter
Bypass input
AC input
Converter
/Charger
CB1
AC output
52C
52L1
UPS
Breaker
CB2 Battery
UPS-2
Bypass
Bypass input
AC input
52S
Output
Breaker
Converter
/Charger
52CS
Inverter
CB1
AC output
52C
52L2
UPS
Breaker
Battery
CB2
UPS-n
Bypass input
AC input
Bypass
52S
Inverter
UPS
Breaker
Converter
/Charger
52Ln (*1)
CB1
AC output
52C
(*1) n: Maximum=4 (80-225kVA)
Maximum=8 (300-750kVA)
CB2 Battery
62
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.7.1 Diagram of Power Wire & Control Wire Connections for 4 units in MMS Configuration
(80-225kVA)
UPS-1
IOAU-09
TN1
5
IFAU-08
CN96
TLIN
6
*1
CN95
TLOUT
CN94
CBIN
CBOUT
CAIN
AC
OUTPUT
Use Ethernet STP
(Shielded Twisted
Pair) Cable (Cat 5 or
Cat 6) with RJ45
modular connectors
for all communication
cabling.
Use of UTP
(Unshielded Twisted
CAOUT
A50
B50
C50
*2
ON
Toshiba Tie Cabinet (TTC)
UPS-2
IOAU-09
TN1
5
IFAU-08
CN96
TLIN
6
CN95
TLOUT
43
44
52L1-AX
45
46
47
48
52L2-AX
CN94
CBIN
52L3-AX
Total cable length
from UPS-1 to UPS-n
should be within
100m.
CBOUT
CAIN
49
52L4-AX
50
AC
OUTPUT
CAOUT
A50
B50
C50
*2
OFF
UPS-3
IOAU-09
TN1
5
IFAU-08
CN96
TLIN
6
CN95
TLOUT
CN94
CBIN
CBOUT
CAIN
AC
OUTPUT
A50
CAOUT
B50
C50
AC OUTPUT
UPS-1
*2
OFF
A
B
C
UPS-4
IOAU-09
TN1
5
IFAU-08
CN96
TLIN
UPS-2
6
A
B
C
CN95
TLOUT
CN94
CBIN
UPS-3
A
B
C
*1 Return from the last
UPS module to the first UPS
module (continuous loop).
*2 DIP switch position
UPS-1 and UPS-n (n=2-4): ON
Otherwise : OFF
CBOUT
CAIN
AC
OUTPUT
UPS-4
CAOUT
A50
B50
C50
A
B
C
*2
ON
G9000 Installation and Operation Manual
63
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.7.2a Diagram of Power Wire & Control Wire Connections for 2 units in MMS Configuration
(300-750kVA)
UPS-1
IOAU-09
TN1
5
IFAU-09
CN99
TLBIN
CN98
TLAIN
CN97
TLBOUT
CN96
TLAOUT
6
*1
*1
Toshiba Tie Cabinet (TTC)
Use Ethernet STP
(Shielded Twisted
Pair) Cable ( Cat 5 or
Cat 6) with RJ45
modular connectors
for all communication
cabling.
*2
ON
CN954
47
48
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
52L1-AX
49
Use of UTP
52L2-AX
50
(Unshielded Twisted
Pair) Cable may
cause malfunction.
CN944
CB2OUT
CN943
CB1OUT
CN942
CA2OUT
CN941
CA1OUT
AC
OUTPUT
A50
B50
C50
Total cable length
from UPS-1 to UPS-2
should be within
100m.
ON
*2
UPS-2
IOAU-09
TN1
5
IFAU-09
CN99
TLBIN
CN98
TLAIN
CN97
TLBOUT
CN96
TLAOUT
6
*2
ON
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
AC OUTPUT
UPS-1
*1 Return from the last
UPS module to the first UPS
module (continuous loop).
*2 DIP switch position
UPS-1 and UPS-2 : ON
A
B
C
CN944
CB2OUT
CN943
CB1OUT
CN942
CA2OUT
CN941
CA1OUT
AC
OUTPUT
UPS-2
A
B
C
A50
B50
C50
*2
ON
64
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.7.2b Detail of IFAU-09 Control Wire Connections for 2 units in MMS Configuration (300-750kVA)
No.1 UPS
No.2 UPS
IFAU-09
IFAU-09
CN99 TLBIN
CN99 TLBIN
CN98 TLAIN
CN97 TLBOUT
CN96 TLAOUT
CN954 CB2IN
CN953 CB1IN
CN952 CA2IN
CN951 CA1IN
CN944 CB2OUT
CN943 CB1OUT
CN942 CA2OUT
CN941 CA1OUT
CN98 TLAIN
CN97 TLBOUT
CN96 TLAOUT
CN954 CB2IN
CN953 CB1IN
CN952 CA2IN
CN951 CA1IN
CN944 CB2OUT
CN943 CB1OUT
CN942 CA2OUT
CN941 CA1OUT
IOAU-09
IOAU-09
~~~~~
~~~~~
G9000 Installation and Operation Manual
65
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.7.3a Diagram of Power Wire & Control Wire Connections for 3 or 4 units in MMS Configuration
(300-750kVA)
UPS-1
IOAU-09
TN1
5
IFAU-09
CN99
TLBIN
CN98
TLAIN
CN97
TLBOUT
CN96
TLAOUT
6
*1
*1
*2
ON
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
Use Ethernet STP
(Shielded Twisted
Pair) Cable( Cat 5 or
Cat 6) with RJ45
modular connectors
for all communication
cabling.
CN944
CB2OUT
CN943
CB1OUT
CN942
CA2OUT
CN941
CA1OUT
Toshiba Tie Cabinet (TTC)
AC
OUTPUT
A50
B50
C50
35
52L1-AX
36
Use of UTP
ON
*2
37
38
.
.
.
(Unshielded Twisted
Pair) Cable may
cause malfunction.
52L2-AX
UPS-2
IOAU-09
TN1
5
IFAU-09
CN99
TLBIN
CN98
TLAIN
CN97
TLBOUT
CN96
TLAOUT
49
50
52Ln-AX
*3
6
Total cable length
from UPS-1 to UPS-n
should be within
100m.
*2
OFF
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
CN944
CB2OUT
CN943
CB1OUT
CN942
CA2OUT
CN941
CA1OUT
AC
OUTPUT
AC OUTPUT
UPS-1
A50
B50
C50
A
B
C
*2
OFF
UPS-2
A
B
C
UPS-n*3
IOAU-09
TN1
5
.
.
.
IFAU-09
CN99
TLBIN
CN98
TLAIN
CN97
TLBOUT
CN96
TLAOUT
*1 Return from the last
UPS module to the first UPS
module (continuous loop).
*2 DIP switch position
UPS-1 and UPS-n: ON
Otherwise : OFF
6
UPS-n *3
A
B
C
*2
ON
*3 n = 3-4 (maximum) for this
cabling configuration
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
CN944
CB2OUT
CN943
CB1OUT
CN942
CA2OUT
CN941
CA1OUT
AC
OUTPUT
A50
B50
C50
ON
*2
66
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.7.3b Detail of IFAU-09 Control Wire Connections for 3 or 4 units in MMS Configuration
(300-750kVA)
No.1 UPS
No.2 UPS
No.N UPS
IFAU-09
IFAU-09
IFAU-09
CN99 TLBIN
CN99 TLBIN
CN99 TLBIN
CN98 TLAIN
CN97 TLBOUT
CN96 TLAOUT
CN954 CB2IN
CN953 CB1IN
CN952 CA2IN
CN951 CA1IN
CN944 CB2OUT
CN943 CB1OUT
CN942 CA2OUT
CN941 CA1OUT
CN98 TLAIN
CN97 TLBOUT
CN96 TLAOUT
CN954 CB2IN
CN953 CB1IN
CN952 CA2IN
CN951 CA1IN
CN944 CB2OUT
CN943 CB1OUT
CN942 CA2OUT
CN941 CA1OUT
CN98 TLAIN
CN97 TLBOUT
CN96 TLAOUT
CN954 CB2IN
CN953 CB1IN
CN952 CA2IN
CN951 CA1IN
CN944 CB2OUT
CN943 CB1OUT
CN942 CA2OUT
CN941 CA1OUT
IOAU-09
IOAU-09
IOAU-09
~~~~~
~~~~~
~~~~~
G9000 Installation and Operation Manual
67
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.7.4a Diagram of Power Wire & Control Wire Connections for 5 to 8 units in MMS Configuration
(300-750kVA)
UPS-1
IOAU-09
TN1
5
IFAU-09
CN99
TLBIN
CN98
TLAIN
CN97
TLBOUT
CN96
TLAOUT
6
*1
*1
ON
*2
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
CN944
CB2OUT
CN943
CB1OUT
CN942
CA2OUT
CN941
CA1OUT
Toshiba Tie Cabinet (TTC)
AC
OUTPUT
A50
B50
C50
35
52L1-AX
36
*2
ON
37
38
Use Ethernet STP
(Shielded Twisted
Pair) Cable ( Cat 5 or
Cat 6) with RJ45
modular connectors
for all communication
cabling.
52L2-AX
.
.
.
UPS-2
IOAU-09
TN1
5
IFAU-09
CN99
TLBIN
CN98
TLAIN
CN97
TLBOUT
CN96
TLAOUT
49
52Ln-AX
50
*3
6
Use of UTP
(Unshielded Twisted
Pair) Cable may
cause malfunction.
*2
OFF
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
Total cable length
from UPS-1 to UPS-n
should be within
100m.
CN944
CB2OUT
CN943
CB1OUT
CN942
CA2OUT
CN941
CA1OUT
AC
OUTPUT
AC OUTPUT
UPS-1
A50
B50
C50
A
B
C
*2
OFF
UPS-2
A
B
C
UPS-n *3
IOAU-09
TN1
5
.
.
.
IFAU-09
CN99
TLBIN
CN98
TLAIN
CN97
TLBOUT
CN96
TLAOUT
6
UPS-n
*3
A
B
C
*2
ON
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
*1 Return from the last
UPS module to the first UPS
module (continuous loop).
*2 DIP switch position
UPS-1 and UPS-n : ON
Otherwise : OFF
CN944
CB2OUT
CN943
CB1OUT
CN942
CA2OUT
CN941
CA1OUT
*3 n = 5-8 (maximum) for this
cabling configuration
AC
OUTPUT
A50
B50
C50
*2
ON
68
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3.7.4b Detail of IFAU-09 Control Wire Connections for 5 to 8 units in MMS Configuration
(300-750kVA)
No.1 UPS
No.2 UPS
No.N UPS
IFAU-09
IFAU-09
IFAU-09
CN99 TLBIN
CN99 TLBIN
CN99 TLBIN
CN98 TLAIN
CN97 TLBOUT
CN96 TLAOUT
CN954 CB2IN
CN953 CB1IN
CN952 CA2IN
CN951 CA1IN
CN944 CB2OUT
CN943 CB1OUT
CN942 CA2OUT
CN941 CA1OUT
CN98 TLAIN
CN97 TLBOUT
CN96 TLAOUT
CN954 CB2IN
CN953 CB1IN
CN952 CA2IN
CN951 CA1IN
CN944 CB2OUT
CN943 CB1OUT
CN942 CA2OUT
CN941 CA1OUT
CN98 TLAIN
CN97 TLBOUT
CN96 TLAOUT
CN954 CB2IN
CN953 CB1IN
CN952 CA2IN
CN951 CA1IN
CN944 CB2OUT
CN943 CB1OUT
CN942 CA2OUT
CN941 CA1OUT
IOAU-09
IOAU-09
IOAU-09
~~~~~
~~~~~
~~~~~
G9000 Installation and Operation Manual
69
Download from Www.Somanuals.com. All Manuals Search And Download.
3.4
OPERATING PROCEDURES
For Parallel Operation system, refer to section “D) MMS Start-up Procedure”.
(Parallel Operation system is herein after MMS [Multi Module System])
A) Start-up Procedure
Before the UPS startup, the internal Bypass line starts to supply the unconditioned bypass
input power to the load if the External input (or Bypass) Circuit Breaker is closed. Be
extremely careful with closing the External input (or Bypass) Circuit Breaker.
Confirm the position of the circuit protectors (CPMC, CPMS and EMB) located at the upper
part of the cabinet (FIGURE 3.8).
NOTE
1) CPMC and CPMS: ON; 2) EMB: OFF.
FIGURE 3.8 Circuit protectors location
CPMC
CPMS
EMB
a.) Verify that the External Bypass Input Circuit Breaker for each unit is closed.
(user supplied)
b.) Verify that Battery Disconnect Circuit Breaker (CB2) is opened or in tripping position.
c.) If a dual source is feeding the UPS, close the External AC Input Circuit Breaker manually (user
supplied).
d.) The LCD panel boots up automatically, and the screen will show that the Load is powered by
bypass line.
e.) On the LCD panel, select “OPERATION” tab, and then press the “STARTUP GUIDANCE” button
to continue UPS start-up. (Refer to Figure 2.3)
f.) Follow the “STARTUP GUIDANCE” accordingly until the completion of the inverter startup.
When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter start
operation can only be performed remotely. If local inverter start operation is required (at the
UPS), select "LOCAL ONLY" or “REMOTE & LOCAL” in the OPERATION MENU.
NOTE
70
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
B) Shut-down Procedure
If a total UPS shutdown is required, verify that the critical load is OFF.
a.) Press the "START/STOP" icon from the Main Menu or the Operation Menu on the LCD.
b.) On the LCD panel, press “START/STOP” icon, and then select “SHUTDOWN GUIDANCE” icon.
(Refer to Figure 2.3)
c.) Follow the “SHUTDOWN GUIDANCE” until Inverter stops. The UPS will simultaneously transfer
to Bypass operation.
d.) In general, only the Inverter will be stopped and the Converter will remain energized to charge the
batteries.
When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter
start operation can only be performed remotely. If local inverter stop operation is
required (at the UPS), select "LOCAL ONLY" or “REMOTE & LOCAL” in the
OPERATION MENU.
NOTE
e.) If stopping both the Inverter and Converter is required, open the Battery Disconnect circuit
breaker (CB2) manually in accordance with guidance.
Verify the load is OFF if the next step is to be performed.
Power to the load has been supplied through the bypass line. Power to load will be lost
after execution of the next step. The load will drop.
CAUTION
f.) If a dual source is feeding the UPS, open the External AC Input Circuit Breaker (user supplied)
manually.
g.) If turning off all power to the critical load is desired, open the External Bypass Input Circuit
Breaker (user supplied) manually.
In bypass mode, all UPS power terminals are still alive. Lethal voltages are present.
De-energize all external sources of AC and DC power. Before removing the covers, wait
5 minutes after de-energizing. Check no-voltage before handling UPS. Be careful of
the devices even when the UPS has been de-energized, since internal devices may be
WARNING
energized.
G9000 Installation and Operation Manual
71
Download from Www.Somanuals.com. All Manuals Search And Download.
C) Bypass Operation Procedure
** Transfer from Inverter to Bypass
1. Check for “SYNC” on the LCD.
2. Press the "START/STOP” icon on the LCD.
3. Follow the “SHUTDOWN GUIDANCE” and Press the "STOP" icon on the LCD.
** Transfer from bypass to inverter.
UPS
1. Press the "START/STOP" icon on the LCD.
2. Follow the “STARTUP GUIDANCE” and Press the "START" icon on the LCD..
When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter
start operation can only be performed remotely. If local inverter start or stop operation is
required (at the UPS), select "LOCAL ONLY" or “REMOTE & LOCAL” in the
OPERATION MENU.
NOTE
72
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
D) MMS Start-up Procedure
External Circuit Check (Ensure System is in Maintenance Bypass)
1. Verify that Tie cabinet Maintenance bypass breaker 52MB is closed.
2. Verify that Tie cabinet Output breaker 52CS is open.
3. Verify that Tie cabinet UPS breakers 52L1, 52L2…and 52Ln are closed.
Start-up from UPS-1 to UPS-n
1. Start-up each UPS in accordance with “A) Start-up Procedure”. Each UPS will start Inverter
Operation synchronized with the bypass input. The Maintenance Bypass Switch is synchronized
with the Static Transfer Switch.
Transfer from Maintenance Bypass to MMS Bypass Operation
1. Close Tie cabinet breaker 52CS.
2. Open Tie cabinet Breaker 52MB.
When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter
start operation can only be performed remotely. If local inverter start operation is
required (at the UPS), select "LOCAL ONLY" or “REMOTE & LOCAL” in the
OPERATION MENU.
NOTE
Transfer from UPS MMS Bypass Operation To UPS MMS Inverter Operation
1. Transfer MMS Bypass Operation to MMS Inverter Operation from Operation Menu on any UPS
LCD as shown in Fig. 3.9.
FIGURE 3.9 LCD Screen (MMS Operation)
G9000 Installation and Operation Manual
73
Download from Www.Somanuals.com. All Manuals Search And Download.
4
RESPONSE TO UPS FAILURE
UPS FAULT
Depress “SILENCE ALARM” icon on Main Menu.
Annunciator Silence
Recording of Fault
Primary Action
Refer to the list of fault codes in section 6.0 for error description.
Take necessary action according to display guidance.
When faults happen, contact the Authorized Toshiba Service
Representatives or call Toshiba International Corporation at
1-877-867-8773.
Information to Service
Note
The error code indicated on the LCD display panel when an UPS
alarms is very important.
In order to reduce repair time, please include this information,
along with the operation and load status for all correspondence to
Toshiba field service group.
NOTE
74
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
5
PARTS REPLACEMENT
Contact Toshiba International Corporation or its authorized service representatives on all issues
regarding the replacement of parts.
A) Battery
Battery lifetime may vary according to the frequency of use and the average ambient
operating temperature. The end of battery life is defined as the state of charge resulting in an
ampere-hour capacity less than, or equal to, 80% of nominal capacity.
Replace battery if its capacity is within this percentage.
B) UPS Component Parts
UPS components have a defined life expectancy (Fans, Capacitors, Filters, etc.)
Contact Toshiba International Corporation or its authorized service representatives for a complete
parts replacement schedule. Recommended replacement time interval varies with operating
environment.
Contact Toshiba International Corporation or its authorized service representatives for application
specific recommendations.
Any parts replacements (including modification) without authorized by
Toshiba could result in personal injuries, death or destruction of the
UPS.
WARNING
G9000 Installation and Operation Manual
75
Download from Www.Somanuals.com. All Manuals Search And Download.
6
FAULT CODES
This section covers fault codes, their description and required action.
At time of error :
Verify and record the occurrence of the alarm. Note details of alarm message displayed on the LCD
display panel.
Contact Toshiba International Corporation at 1-877-867-8773.
76
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Failure Code List
Table 6.1 Fault Code
Note 3
Code
Note 1
Note 2
External
relay contact
Failure
lamp
Status message
Meaning
Guidance
Buzzer
indication
CHECK INPUT
POWER
SOURCE
Alarm
AC input
abnormal
AC INPUT VOLTAGE
OUT OF RANGE
Input line voltage is out of the specified
range.
Intermittent
sound
UA801
-
-
AC INPUT
FREQUENCY OUT
OF RANGE
CHECK INPUT
POWER
SOURCE
Alarm
AC input
abnormal
Input line frequency is out of the specified
range.
Intermittent
sound
UA802
UA803
CHECK INPUT
POWER
SOURCE
Alarm
AC input
abnormal
AC INPUT PHASE
ROTATION ERROR
Input line power conductors are not wired in
a proper phase sequence.
Intermittent
sound
-
CONVERTER OPE.
PROHIBITED
Intermittent
sound
UA804
UA805
The converter interlock is active.
-
Alarm
-
-
WARNING :
DECREASE
LOAD
INVERTER
OVERLOAD
The output load current has exceeded 105%
of the rated current.
Intermittent
sound
Alarm
Overload
WARNING :
DECREASE
LOAD
INVERTER
OVERLOAD
The output load current has exceeded 110%
of the rated current.
Intermittent
sound
Alarm
Overload
UA806
UA807
UA808
UA810
UA812
-
-
-
-
-
WARNING :
DECREASE
LOAD
INVERTER
OVERLOAD
The output load current has exceeded 125%
of the rated current.
Intermittent
sound
Alarm
Overload
WARNING :
DECREASE
LOAD
INVERTER
OVERLOAD
The output load current has exceeded 150%
of the rated current.
Intermittent
sound
Alarm
Overload
WARNING :
DECREASE
LOAD
INVERTER
OVERLOAD
Short time over-current has been detected
during the inverter operation.
Intermittent
sound
Alarm
Overload
Alarm
Bypass input
abnormal
BYPASS VOLTAGE
OUT OF RANGE
Bypass line voltage is out of the specified
range.
CHECK BYPASS
INPUT
Intermittent
sound
Alarm
Bypass input
abnormal
BYPASS PHASE
ROTATION ERROR
Bypass line power conductors are not wired
in a proper phase sequence.
CHECK BYPASS
INPUT
Intermittent
sound
UA813
UA814
-
-
BYPASS
FREQUENCY OUT
OF RANGE
Alarm
Bypass input
abnormal
Bypass line frequency is out of the specified
range.
CHECK BYPASS
INPUT
Intermittent
sound
TRANSFER
PROHIBITED
Transfer to the bypass is not available due to
bypass abnormality.
Intermittent
sound
UA815
UA817
-
-
Alarm
Alarm
-
-
EMERGENCY STOP
ACTIVATED
The emergency stop was activated by the
EPO switch or an external contact.
The UPS could not transfer to the bypass
because the inverter output was not
synchronized to the bypass.
The UPS could not transfer to the bypass
because external “generator operation”
signal indicates a backup generator is in
operation.
-
TRANSFER
PROHIBITED
UA821
UA822
-
-
-
Alarm
Alarm
-
-
TRANSFER
PROHIBITED
-
G9000 Installation and Operation Manual
77
Download from Www.Somanuals.com. All Manuals Search And Download.
Note 3
Code
indication
Note 1
External
relay contact
Note 2
Failure
lamp
Status message
Meaning
Guidance
Buzzer
Intermittent
sound
UA824
UA827
UA831
UA833
CB2 OPEN
The battery circuit breaker (CB2) is open.
TURN ON CB2
Alarm
Alarm
Alarm
Alarm
-
-
-
-
52C OPEN
PROHIBITED
The interlock for the inverter output contactor
(52C) is active.
Intermittent
sound
-
-
-
EMERGENCY
BYPASS SWITCH ON on.
Emergency bypass switch has been turned
Intermittent
sound
Intermittent
sound
52L OPEN
The load circuit breaker(52L) is turned off.
BATTERY
DEPLETED/AC OUT
STOPPED
Major
End-of-
Discharge
The battery voltage has reached the
depleted level.
UA834
-
-
-
Lit on
The UPS could not transfer to the bypass
because the bypass source has an
abnormality.
Remote start or stop signal is being received
continuously for a considerable time.
TRANSFER
PROHIBITED
UA835
UA860
UA861
-
-
-
Alarm
Alarm
Alarm
-
-
-
REMOTE BUTTON
ABNORMAL
Intermittent
sound
LOCAL BUTTON
ABNORMAL
Local start or stop signal is being received
continuously for a considerable time.
Intermittent
sound
BALANCER
OVERLOAD
The UPS detected a neutral point voltage
unbalance.
Intermittent
sound
Intermittent
sound
Alarm
Overload
UA870
UA890
UF001
UF002
UF003
UF011
UF052
UF056
UF059
UF102
UF103
UF108
-
-
-
EXTERNAL ALARM
External Alarm relay turned on.
Alarm
Major
Major
Major
Major
Minor
Minor
Minor
Major
Major
Major
-
INPUT CIRCUIT
ABNORMAL
The MMS input reference error signal
exceeds specifications.
CALL SERVICE
ENGINEER
Continuous
sound
Lit on
Lit on
Lit on
Lit on
Flicker
Flicker
Flicker
Lit on
Lit on
Lit on
CONVERTER
OVERCURRENT
CALL SERVICE
ENGINEER
Continuous
sound
Detection of MMS converter overcurrent.
Pre-charging circuit is not working properly.
CONVERTER
ABNORMAL
CALL SERVICE
ENGINEER
Continuous
sound
Major discrepancy between reference signal
and actual state of contactor CB1.
CALL SERVICE
ENGINEER
Continuous
sound
CB1 ABNORMAL
CB1 ABNORMAL
Minor discrepancy between reference signal
and actual state of contactor CB1.
CALL SERVICE
ENGINEER
Intermittent
sound
CONVERTER
OVERCURRENT
CALL SERVICE
ENGINEER
Intermittent
sound
Detection of SMS converter overcurrent.
INPUT CIRCUIT
ABNORMAL
The SMS input reference error signal
exceeds specifications.
CALL SERVICE
ENGINEER
Intermittent
sound
CALL SERVICE
ENGINEER
Continuous
sound
DC OVERVOLTAGE
DC UNDERVOLTAGE
DC voltage surpasses the overvoltage level.
DC voltage dropped below the undervoltage
level.
CALL SERVICE
ENGINEER
Continuous
sound
CHOPPER
OVERCURRENT
Detection of DC overcurrent from backup
battery.
CALL SERVICE
ENGINEER
Continuous
sound
78
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Note 3
Code
indication
Note 1
External
relay contact
Note 2
Failure
lamp
Status message
Meaning
Guidance
Buzzer
CALL SERVICE
ENGINEER
Continuous
sound
UF109
UF110
UF111
UF112
UF119
DC UNBALANCED
Major unbalance of the neutral point voltage.
Major
Major
Major
Major
Major
Lit on
Lit on
Lit on
Lit on
Lit on
ZERO PHASE
OVERCURRENT
Detection of converter zero-sequence
overcurrent.
CALL SERVICE
ENGINEER
Continuous
sound
UPS CONTROL
CIRCUIT ERROR
CALL SERVICE
ENGINEER
Continuous
sound
Battery current unbalance.
DC CIRCUIT
ABNORMAL
CALL SERVICE
ENGINEER
Continuousso
und
Sudden change of the DC voltage level.
DC GROUND
FAULT
Detection of DC ground fault UF159 exceeds CALL SERVICE
Continuous
sound
10 seconds. UPS transfers to bypass.
ENGINEER
CONTROL POWER
SUPPLY
ABNORMAL
DC VOLTAGE
ABNORMAL
Power supply voltage to IGBT driver PCB is
below the specified level.
CALL SERVICE
ENGINEER
Continuous
sound
UF128
Major
Lit on
24 hours after input power restoration,
batteries does not reach float voltage level.
CALL SERVICE
ENGINEER
Intermittent
sound
UF151
UF152
UF154
Minor
Minor
Minor
Flicker
Flicker
Flicker
DC VOLTAGE
ABNORMAL
Unable to equalize the voltage of various
batteries after 24 hours.
CALL SERVICE
ENGINEER
Intermittent
sound
CALL SERVICE
ENGINEER
Intermittent
sound
CB2 ABNORMAL
During UVR, status signal from CB2 is ON.
CHG.STOPPED
(BATTERY
OVERTEMP.)
Minor
Battery
abnormal
Intermittent
sound
UF156
UF157
UF158
UF157 failure persisted for over 2 hours.
CHECK BATTERY
CHECK BATTERY
CHECK BATTERY
Flicker
Flicker
Flicker
BATTERY
OVERTEMPERATU
RE
Minor
Battery
abnormal
Detection of overtemperature at the
batteries.
Intermittent
sound
Minor
Battery
abnormal
BATTERY LIQUID
LOW
Intermittent
sound
Low level of battery electrolyte solution.
DC GROUND
FAULT
Detection of DC ground fault. Chopper
operation is stopped.
CALL SERVICE
ENGINEER
Intermittent
sound
UF159
UF160
UF161
UF162
Minor
Minor
Minor
Minor
Flicker
Flicker
Flicker
Flicker
UPS CONTROL
CIRCUIT ERROR
CALL SERVICE
ENGINEER
Intermittent
sound
Abnormal behavior of DC current sensor.
UF151 failure is running for over 24 hours.
CHG.STOPPED(DC
VOLT. ABNORMAL)
CALL SERVICE
ENGINEER
Intermittent
sound
BATTERY
ABNORMAL
BATTERY
VOLTAGE
ABNORMAL
Failure detection based on battery
self-check.
CALL SERVICE
ENGINEER
Intermittent
sound
CALL SERVICE
ENGINEER
Intermittent
sound
UF163
UF170
Battery voltage is abnormal.
Minor
Minor
Flicker
Flicker
Detection of a large variation of the
difference between control-only and
protection-only battery voltage.
VDB SENSOR
ABNORMAL
CALL SERVICE
ENGINEER
Intermittent
sound
UPS CONTROL
CIRCUIT ERROR
Poor shared current in parallel chopper
circuit; or improper charging current.
CALL SERVICE
ENGINEER
Intermittent
sound
UF171
UF172
Minor
Minor
Flicker
Flicker
CHG. STOPPED
(DEVICE STATUS)
CALL SERVICE
ENGINEER
Intermittent
sound
Energy storage device error.
G9000 Installation and Operation Manual
79
Download from Www.Somanuals.com. All Manuals Search And Download.
Note 3
Code
indication
Note 1
External
relay contact
Note 2
Failure
lamp
Status message
Meaning
Guidance
Buzzer
INVERTER
OVERVOLTAGE
CALL SERVICE
ENGINEER
Continuous
sound
UF201
UF202
UF203
Detection of output overvoltage.
Output voltage dropped.below specs.
Detection of inverter overcurrent.
Major
Major
Major
Lit on
Lit on
Lit on
INVERTER
UNDERVOLTAGE
CALL SERVICE
ENGINEER
Continuous
sound
INVERTER
OVERCURRENT
CALL SERVICE
ENGINEER
Continuous
sound
Detection of a large variation of the reference
error signal (current reference and actual
current).
OUTPUT CIRCUIT
ABNORMAL
CALL SERVICE
ENGINEER
Continuous
sound
UF204
Major
Lit on
UPS CONTROL
CIRCUIT ERROR
Discrepancy between output voltage and
external voltage (bypass, common ac bus)
CALL SERVICE
ENGINEER
Continuous
sound
UF206
UF207
UF208
UF209
UF210
UF211
UF213
UF214
UF217
UF230
Major
Major
Major
Major
Major
Major
Major
Major
Major
Major
Lit on
Lit on
Lit on
Lit on
Lit on
Lit on
Lit on
Lit on
Lit on
Lit on
ZERO PHASE
OVERCURRENT
CALL SERVICE
ENGINEER
Continuous
sound
Inverter zero-sequence overcurrent.
Cross current is abnormal.
UPS CONTROL
CIRCUIT ERROR
CALL SERVICE
ENGINEER
Continuous
sound
CALL SERVICE
ENGINEER
Continuous
sound
52C ABNORMAL
52C ABNORMAL
52C ABNORMAL
OVERTEMP
Error to close the contactor 52C.
Error to open the contactor 52C.
CALL SERVICE
ENGINEER
Continuous
sound
No answer from contactor 52C during
inverter operation.
CALL SERVICE
ENGINEER
Continuous
sound
Heatsinks temperature exceeds thermal
settings.
CALL SERVICE
ENGINEER
Continuous
sound
COOLING FAN
ABNORMAL
CALL SERVICE
ENGINEER
Continuous
sound
Thermal relay activated protection.
INVERTER
OVERVOLTAGE
Detection of inverter output phase
overvoltage.
CALL SERVICE
ENGINEER
Continuous
sound
ZERO PHASE
OVERCURRENT
CALL SERVICE
ENGINEER
Continuous
sound
Detection of zero-sequence overcurrent.
Discrepancy between output voltage and
inverter voltage, or between output voltage
and bypass voltage.
UPS CONTROL
CIRCUIT ERROR
CALL SERVICE
ENGINEER
Intermittent
sound
UF253
Minor
Flicker
OUTPUT VOLTAGE
ABNORMAL
Output voltage is outside of the specified
range.
CALL SERVICE
ENGINEER
Intermittent
sound
UF256
UF257
UF258
UF259
Minor
Minor
Minor
Minor
Flicker
Flicker
Flicker
Flicker
Contactor 52C failed to open during load
transfer from inverter to bypass.
CALL SERVICE
ENGINEER
Intermittent
sound
52C ABNORMAL
Load transfer due to overload for over 4
times within 5 minutes.
CALL SERVICE
ENGINEER
Intermittent
sound
LOAD ABNORMAL
ANOTHER UPS
ABNORMAL
CALL SERVICE
ENGINEER
Intermittent
sound
No detection of another UPS voltage signal.
80
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Note 3
Code
indication
Note 1
External
relay contact
Note 2
Failure
lamp
Status message
Meaning
Guidance
Buzzer
UPS CONTROL
CIRCUIT ERROR
CALL SERVICE
ENGINEER
Continuous
sound
UF301
UF302
UF303
UF305
UF306
AD reference has an abnormal value.
Major
Major
Major
Major
Major
Lit on
Lit on
Lit on
Lit on
Lit on
UPS CONTROL
CIRCUIT ERROR
Detection of an external interruption during
the software execution.
CALL SERVICE
ENGINEER
Continuous
sound
UPS CONTROL
CIRCUIT ERROR
Timer does not reset in the specified period
(WDT settings)
CALL SERVICE
ENGINEER
Continuous
sound
UPS CONTROL
CIRCUIT ERROR
Detection of an abnormal clock speed in the
DSP or FPGA.
CALL SERVICE
ENGINEER
Continuous
sound
UPS CONTROL
CIRCUIT ERROR
INVERTER
VOLTAGE
ABNORMAL
CONTROL POWER
SUPPLY
ABNORMAL
Control power supply voltage is below the
specified level.
CALL SERVICE
ENGINEER
Continuous
sound
CALL SERVICE
ENGINEER
Continuous
sound
UF309
UF310
Inverter voltage is out of the specified range.
Major
Major
Lit on
Lit on
MMS backup control power supplies exhibit
abnormal condition.
CALL SERVICE
ENGINEER
Continuous
sound
UPS CONTROL
CIRCUIT ERROR
Cable disconnection in the parallel interface
board during load supply.
CALL SERVICE
ENGINEER
Continuous
sound
UF320
UF323
UF331
UF332
UF333
UF334
Major
Major
Major
Major
Major
Major
Lit on
Lit on
Lit on
Lit on
Lit on
Lit on
UPS CONTROL
CIRCUIT ERROR
Major communication error during parallel
operation.
CALL SERVICE
ENGINEER
Continuous
sound
UPS CONTROL
CIRCUIT ERROR
CALL SERVICE
ENGINEER
Continuous
sound
Gate driver abnormal for phase U (Note 4)
Gate driver abnormal for phase V (Note 4)
Gate driver abnormal for phase W (Note 4)
Gate driver abnormal for chopper (Note 4)
UPS CONTROL
CIRCUIT ERROR
CALL SERVICE
ENGINEER
Continuous
sound
UPS CONTROL
CIRCUIT ERROR
CALL SERVICE
ENGINEER
Continuous
sound
UPS CONTROL
CIRCUIT ERROR
CONTROL POWER
SUPPLY
CALL SERVICE
ENGINEER
Continuous
sound
SMS backup control power supplies exhibit
abnormal.
CALL SERVICE
ENGINEER
Intermittent
sound
UF352
Minor
Flicker
ABNORMAL
UPS CONTROL
CIRCUIT ERROR
Synchronization error signal is being
received for a considerable time.
CALL SERVICE
ENGINEER
Intermittent
sound
UF363
UF371
Minor
Minor
Flicker
Flicker
UPS CONTROL
CIRCUIT ERROR
Minor communication error during parallel
operation.
CALL SERVICE
ENGINEER
Intermittent
sound
Unable to synchronize the inverter output
and the bypass voltage when the bypass is
normal.
UPS CONTROL
CIRCUIT ERROR
CALL SERVICE
ENGINEER
Intermittent
sound
UF372
Minor
Flicker
UPS CONTROL
CIRCUIT ERROR
Cable disconnection in the parallel interface
board.
CALL SERVICE
ENGINEER
Intermittent
sound
UF374
UF375
UF376
UF377
UF378
UF379
Minor
Minor
Minor
Minor
Minor
Minor
Flicker
Flicker
Flicker
Flicker
Flicker
Flicker
UPS CONTROL
CIRCUIT ERROR
Unable to achieve synchronization for
parallel operation.
CALL SERVICE
ENGINEER
Intermittent
sound
UPS CONTROL
CIRCUIT ERROR
No control response from another UPS
although its detection is possible.
CALL SERVICE
ENGINEER
Intermittent
sound
UPS CONTROL
CIRCUIT ERROR
Overload detection signal is being received
continuously for a considerable time.
CALL SERVICE
ENGINEER
Intermittent
sound
UPS CONTROL
CIRCUIT ERROR
CALL SERVICE
ENGINEER
Intermittent
sound
No answer for sending synchronizing signal.
UPS CONTROL
CIRCUIT ERROR
Abnormal clock speed of the parallel control
board processor.
CALL SERVICE
ENGINEER
Intermittent
sound
G9000 Installation and Operation Manual
81
Download from Www.Somanuals.com. All Manuals Search And Download.
Note 3
Code
indication
Note 1
External
relay contact
Note 2
Failure
lamp
Status message
52S ABNORMAL
52S ABNORMAL
Meaning
Guidance
Buzzer
CALL SERVICE
ENGINEER
Continuous
sound
UF401
UF402
UF420
UF451
UF452
Error to close the contactor 52S.
Error to open the contactor 52S.
Major
Major
Major
Minor
Minor
Lit on
Lit on
Lit on
Flicker
Flicker
CALL SERVICE
ENGINEER
Continuous
sound
52L OPERATION
ERROR
Load circuit breaker 52L opened during
inverter operation.
Continuous
sound
CHECK 52L
Contactor 52S failed during load transfer
from inverter to bypass.
CALL SERVICE
ENGINEER
Intermittent
sound
52S ABNORMAL
CB3 ABNORMAL
CALL SERVICE
ENGINEER
Intermittent
sound
Contactor CB3 is not working properly.
(Note 1) 1) "Major" is defined as major failure. Inverter transferred to the static bypass line;
2) "Minor" is defined as a minor failure. UPS continues to operate normally, but cause of alarm
must be identified;
(Note 2) Indicates one of two possible LED illumination patterns - continuously on (lit) or intermittent
(flicker).
(Note 3) Code indication means:
UA+++------------------------ Alarm
UF+++------------------------ Failure
U%0++----------------------- Rectifier circuit failure
U%1++----------------------- DC circuit failure
U%2++----------------------- Inverter circuit failure
U%3++----------------------- Control circuit failure
U%4++----------------------- Bypass system failure
U%8++----------------------- Alarm
U%+00 - U%+49 --------- Major failure
U%+50 - U%+99 --------- Minor failure
*) “+” denotes any numeral from 0 to 9
*) “%” denotes either “A” or “F”
82
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
7
DAILY INSPECTION
Please perform the daily inspection while the UPS is running. The daily inspection items are shown in
Table 7.1.
The customers can only inspect exterior or environment of cabinet. When the customers
want to perform the detailed inspection, contact the Authorized Toshiba Service
Representatives or call Toshiba International Corporation at 1-877-867-8773.
NOTE
TABLE 7.1 How to perform daily inspection
No. Subject
Procedure
Criteria and/or Action needed
Term
Period
Method/Tool
Visual check and
smelling
1. Environmental
ambient
Dust or Gas
Daily
Ventilate room atmosphere if dusty or smelling gas.
Dewdrops
Daily
Daily
Visual check
Fix the dripping source
Condensation
Temperature
Humidity
Dehumidify upon necessity.
Thermometer
hygrometer
Temperature: 32 – 104 °F Humidity: 30 – 90%
No condensation.
To be controlled at about 77 °F by A/C.
2. Cabinet
Construction
Vibration or
Daily
Touch and hearing Check if fans have irregular sound.
Contact service representative in case of
abnormalities.
Audible noise
Overheating
When needed Touching exterior
Contact service representative in case of
abnormalities.
Air filter clog
When needed Visual check
Clean/wipe if clogged or dusty.
No characters faded, illegible, or any other
abnormalities.
3. Operation
LCD sharpness
Brightness
Daily
Daily
Visual check
Visual check
Left-bottom LED
Left-bottom LED should be green.
Contact service representative when the LED shows
red with the backlight lost.
Indication terms:
Output voltage
Output current
AC input voltage
Output frequency
Battery voltage
Battery current
DC voltage
Check indication terms/values if within the adequate
window.
Also check indication meters on surface of optional
cabinet, if installed.
4. LEDs
4 status LEDs
Daily
Daily
Visual check
Visual check
Check if LEDs turn on, off or flash according to the
operation.
2 fault LEDs
If UPS fault LED turns on, scroll the screen to see
fault codes and record the codes.
Contact service representative to tell about fault
codes and UPS symptom.
G9000 Installation and Operation Manual
83
Download from Www.Somanuals.com. All Manuals Search And Download.
84
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A Installation Planning Guides (IPG)
Installation Planning Guide for 80kVA UPS
Standard System: 480V Input, 480V Output
General Mechanical Information
Approximate Full-Load Mechanical Clearance (Inches)from UPS
Dimensions
(W x D x H)
Weigh
t
Floor
Loading
Heat Rejection
for Ventilation and Maintenance Access
Inches
Lbs.
Lbs./ft. 2
Btu/Hr
Top
Front
Bottom
Sides**
Back
27.6” x 32.8” x 80.6”* 855
136
10,771
20”
40”
0”
0”
0”
* Height includes removable fan housing – Frame height is 78.7”.
** 0” clearance for peripheral equipment, 1” clearance for walls.
Primary AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power Demand
Normal Mode (Recharge Mode)
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size: Min. – Max. Per Phase
kVA
PF
Amps
AWG or kcmil at 75º C Temp. Rating
76 (80)
>0.99
91 (97)
125 AT
#1 – 1/0
Alternate (Bypass) AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power
Demand
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size:
Min. – Max. Per Phase
AWG or kcmil at 75º C Temp. Rating
kVA
PF
Amps
80
0.9
96
125 AT
#1 – 1/0
Battery Input (480VDC Nominal)
Battery Capacity Required Maximum Discharge
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size: Min. – Max.
for Full Load Output
at Full Load Output
kWB
Amps DC
AWG or kcmil at 75º C Temp. Rating
75 @ 0.9 PF
188
200 AT
3/0 – 250 kcmil
AC Output (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase
Rated Output Power
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
80
0.9
96
125 AT
#1 – 1/0
Important Notes:
11. Cable sizing calculations based on the following assumptions:
1. Maximum input current is limited to 106% of the full-load
input current.
-
Minimum size is smallest size based on ampacity at 30 °C.
Maximum size cable is based on cable bend radius
limitations at the UPS terminals.
-
2. Output load conductors are to be installed in separate
conduit from input conductors.
-
Not more than 3 current-carrying conductors installed in
conduit in ambient temperature of 30 °C.
Temperature rating of copper conductors/terminals: 75 °C.
Reference: 2005 NEC Handbook, Table 310.16.
3. Control wires and power wires are to be installed in separate
conduits.
-
-
4. Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
NOTE: Consult latest edition of applicable
national and local codes for possible
variations.
5. Wiring shall comply with all applicable national and local
electrical codes.
6. Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
- Primary AC Input: 3φ, 3-wire + ground.
12. Ratings of wires and overcurrent devices are suggested
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.
- Alternate AC Input: 3φ, 3-wire + ground.
- AC Output: 3φ, 3-wire + ground.
- DC Input: 2-wire (Positive/Negative) + ground.
7. Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
TOSHIBA INTERNATIONAL CORPORATION
13131 West Little York Road
Houston, TX 77041
Telephone: (800) 231-1412
Fax: (713) 896-5212
8. Maximum battery discharge current based on lowest
permissible discharge voltage of 1.67 VPC.
9. DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
10. Weights do not include batteries or other auxiliary equipment
external to the UPS.
G9000 Installation and Operation Manual
85
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Planning Guide for 100kVA UPS
Standard System: 480V Input, 480V Output
General Mechanical Information
Approximate Full-Load
Heat Rejection
Mechanical Clearance (Inches)from UPS
for Ventilation and Maintenance Access
Dimensions
(W x D x H)
Floor
Loading
Lbs./ft. 2
Weight
Lbs.
Inches
Btu/Hr
Top
Front
Bottom
Sides**
Back
27.6” x 32.8” x 80.6”* 855
136
13,463
20”
40”
0”
0”
0”
* Height includes removable fan housing – Frame height is 78.7.”
** 0” clearance for peripheral equipment, 1” clearance for walls.
Primary AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power Demand
Normal Mode (Recharge Mode)
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size: Min. – Max. Per Phase
kVA
PF
Amps
AWG or kcmil at 75º C Temp. Rating
95 (101)
>0.99
114 (121)
150 AT
2/0 – 3/0
Alternate (Bypass) AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power
Demand
Suggested External
External Feeder Wire Size:
Overcurrent Protection
Min. – Max. Per Phase
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
100
0.9
120
150 AT
2/0 – 3/0
Battery Input (480VDC Nominal)
Battery Capacity Required Maximum Discharge
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size: Min. – Max.
AWG or kcmil at 75º C Temp. Rating
for Full Load Output
at Full Load Output
kWB
Amps DC
94 @ 0.9 PF
235
250 AT
250 kcmil – 300 kcmil
AC Output (480/277V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase
Rated Output Power
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
100
0.9
120
150AT
2/0 – 3/0
Important Notes:
11. Cable sizing calculations based on the following assumptions:
1. Maximum input current is limited to 106% of the full-load
input current.
-
Minimum size is smallest size based on ampacity at 30 °C.
Maximum size cable is based on cable bend radius
limitations at the UPS terminals.
-
2. Output load conductors are to be installed in separate
conduit from input conductors.
-
Not more than 3 current-carrying conductors installed in
conduit in ambient temperature of 30 °C.
Temperature rating of copper conductors/terminals: 75 °C.
Reference: 2005 NEC Handbook, Table 310.16.
3. Control wires and power wires are to be installed in
separate conduits.
-
-
4. Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
NOTE: Consult latest edition of applicable
national and local codes for possible
variations.
5. Wiring shall comply with all applicable national and local
electrical codes.
6. Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
- Primary AC Input: 3φ, 3-wire + ground.
12. Ratings of wires and overcurrent devices are suggested
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.
- Alternate AC Input: 3φ, 3-wire + ground.
- AC Output: 3φ, 3-wire + ground.
- DC Input: 2-wire (Positive/Negative) + ground.
7. Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
TOSHIBA INTERNATIONAL CORPORATION
13131 West Little York Road
Houston, TX 77041
Telephone: (800) 231-1412
Fax: (713) 896-5212
8. Maximum battery discharge current based on lowest
permissible discharge voltage of 1.67 VPC.
9. DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
10. Weights do not include batteries or other auxiliary
equipment external to the UPS.
86
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Planning Guide for 160kVA UPS
Standard System: 480V Input, 480V Output
General Mechanical Information
Approximate Full-Load
Heat Rejection
Mechanical Clearance (Inches)from UPS
for Ventilation and Maintenance Access
Dimensions
(W x D x H)
Floor
Loading
Lbs./ft. 2
Weight
Lbs.
Inches
Btu/Hr
Top
Front
Bottom
Sides**
Back
35.4” x 32.8” x 80.6”* 1160
144
17,821
20”
40”
0”
0”
0”
* Height includes removable fan housing – Frame height is 78.7”.
** 0” clearance for peripheral equipment, 1” clearance for walls.
Primary AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power Demand
Normal Mode (Recharge Mode)
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size: Min. – Max. Per Phase
kVA
PF
Amps
AWG or kcmil at 75º C Temp. Rating
151 (160)
>0.99
181 (192)
250 AT
250 kcmil – 300 kcmil
Alternate (Bypass) AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power
Demand
Suggested External
External Feeder Wire Size:
Overcurrent Protection
Min. – Max. Per Phase
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
160
0.9
192
250 AT
250 kcmil – 300 kcmil
Battery Input (480VDC Nominal)
Battery Capacity Required Maximum Discharge
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size: Min. – Max.
AWG or kcmil at 75º C Temp. Rating
500 kcmil
for Full Load Output
at Full Load Output
kWB
Amps DC
149 @ 0.9 PF
372
400 AT
AC Output (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase //
Rated Output Power
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
160
0.9
192
250 AT
250 kcmil – 300 kcmil
Important Notes:
11. Cable sizing calculations based on the following assumptions:
1. Maximum input current is limited to 106% of the full-load
input current.
-
Minimum size is smallest size based on ampacity at 30 °C.
Maximum size cable is based on cable bend radius
limitations at the UPS terminals.
-
2. Output load conductors are to be installed in separate
conduit from input conductors.
-
Not more than 3 current-carrying conductors installed in
conduit in ambient temperature of 30 °C.
Temperature rating of copper conductors/terminals: 75 °C.
Reference: 2005 NEC Handbook, Table 310.16.
3. Control wires and power wires are to be installed in
separate conduits.
-
-
4. Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
NOTE: Consult latest edition of applicable
national and local codes for possible
variations.
5. Wiring shall comply with all applicable national and local
electrical codes.
6. Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
- Primary AC Input: 3φ, 3-wire + ground.
12. Ratings of wires and overcurrent devices are suggested
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.
- Alternate AC Input: 3φ, 3-wire + ground.
- AC Output: 3φ, 3-wire + ground.
- DC Input: 2-wire (Positive/Negative) + ground.
7. Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
TOSHIBA INTERNATIONAL CORPORATION
13131 West Little York Road
Houston, TX 77041
Telephone: (800) 231-1412
Fax: (713) 896-5212
8. Maximum battery discharge current based on lowest
permissible discharge voltage of 1.67 VPC.
9. DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
10. Weights do not include batteries or other auxiliary
equipment external to the UPS.
G9000 Installation and Operation Manual
87
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Planning Guide for 225kVA UPS
Standard System: 480V Input, 480V Output
General Mechanical Information
Approximate Full-Load
Heat Rejection
Mechanical Clearance (Inches)from UPS
for Ventilation and Maintenance Access
Dimensions
(W x D x H)
Floor
Loading
Lbs./ft. 2
Weight
Lbs.
Inches
Btu/Hr
Top
Front
Bottom Sides**
Back
35.4” x 32.8” x 80.6”* 1230
152
25,060
20”
40”
0”
0”
0”
* Height includes removable fan housing – Frame height is 78.7”.
** 0” clearance for peripheral equipment, 1” clearance for walls.
Primary AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power Demand
Normal Mode (Recharge Mode)
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size: Min. – Max. Per Phase
kVA
PF
Amps
AWG or kcmil at 75º C Temp. Rating
212 (235)
>0.99
255 (283)
350 AT
500 kcmil – (2) x 250 kcmil
Alternate (Bypass) AC Input (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase
Maximum Input Power Demand
kVA
PF
Amps (Max.)
Amps
AWG or kcmil at 75º C Temp. Rating
225
0.9
271
350 AT
500 kcmil - (2) x 250 kcmil
Battery Input (480VDC Nominal)
Battery Capacity Required Maximum Discharge
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size: Min. – Max.
for Full Load Output
at Full Load Output
kWB
Amps DC
AWG or kcmil at 75º C Temp. Rating
210 @ 0.9 PF
524
600 AT
(2) x 300 kcmil – (2) x 400 kcmil
AC Output (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase
Rated Output Power
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
225
0.9
271
350 AT
500 kcmil – (2) x 250 kcmil
Important Notes:
11. Cable sizing calculations based on the following assumptions:
1. Maximum input current is limited to 106% of the full-load
input current.
-
Minimum size is smallest size based on ampacity at 30 °C.
Maximum size cable is based on cable bend radius
limitations at the UPS terminals.
-
2. Output load conductors are to be installed in separate
conduit from input conductors.
-
Not more than 3 current-carrying conductors installed in
conduit in ambient temperature of 30 °C.
Temperature rating of copper conductors/terminals: 75 °C.
Reference: 2005 NEC Handbook, Table 310.16.
3. Control wires and power wires are to be installed in
separate conduits.
-
-
4. Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
NOTE: Consult latest edition of applicable
national and local codes for possible
variations.
5. Wiring shall comply with all applicable national and local
electrical codes.
6. Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
- Primary AC Input: 3φ, 3-wire + ground.
12. Ratings of wires and overcurrent devices are suggested
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.
- Alternate AC Input: 3φ, 3-wire + ground.
- AC Output: 3φ, 3-wire + ground.
- DC Input: 2-wire (Positive/Negative) + ground.
7. Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
TOSHIBA INTERNATIONAL CORPORATION
13131 West Little York Road
Houston, TX 77041
Telephone: (800) 231-1412
Fax: (713) 896-5212
8. Maximum battery discharge current based on lowest
permissible discharge voltage of 1.67 VPC.
9. DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
10. Weights do not include batteries or other auxiliary
equipment external to the UPS.
88
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Planning Guide for 300kVA UPS
Standard System: 480V Input, 480V Output
General Mechanical Information
Approximate Full-Load
Heat Rejection
Mechanical Clearance (Inches)from UPS
for Ventilation and Maintenance Access
Dimensions
(W x D x H)
Floor
Loading
Lbs./ft. 2
Weight
Lbs.
Inches
Btu/Hr
Top
Front
Bottom
Sides**
Back
51.2” x 32.7” x 80.7”* 1230
189
31,659
20”
40”
0”
0”
0”
* Height includes removable fan housing – Frame height is 78.7”.
** 0” clearance for peripheral equipment, 1” clearance for walls.
Primary AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power Demand
Normal Mode (Recharge Mode)
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size: Min. – Max. Per Phase
kVA
PF
Amps
AWG or kcmil at 75º C Temp. Rating
312 (337)
>0.99
376 (406)
500 AT
(2) x 250 kcmil - (2) x 300 kcmil
Alternate (Bypass) AC Input (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase
Maximum Input Power Demand
kVA
PF
Amps (Max.)
Amps
AWG or kcmil at 75º C Temp. Rating
300
1.0
361
500 AT
(2) x 4/0 - (2) x 250 kcmil
Battery Input (480VDC Nominal)
Battery Capacity Required
for Full Load Output
kWB
Discharge at Full
Suggested External Overcurrent Protection
External Feeder Wire Size:
Load Output
Amps DC
Amps
AWG or kcmil at 75º C Temp. Rating
309 @ 1.0 PF
772
800 AT
(2) x 400 kcmil
* Contact factory rep for alternate configurations.
AC Output (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase
Rated Output Power
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
300
1.0
361
500 AT
(2) x 4/0 – (2) x 250 kcmil
Important Notes:
11. Cable sizing calculations based on the following assumptions:
1. Maximum input current is limited to 106% of the full-load
input current.
-
Minimum size is smallest size based on ampacity at 30 °C.
Maximum size cable is based on cable bend radius
limitations at the UPS terminals.
-
2. Output load conductors are to be installed in separate
conduit from input conductors.
-
Not more than 3 current-carrying conductors installed in
conduit in ambient temperature of 30 °C.
Temperature rating of copper conductors/terminals: 75 °C.
Reference: 2005 NEC Handbook, Table 310.16.
3. Control wires and power wires are to be installed in
separate conduits.
-
-
4. Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
NOTE: Consult latest edition of applicable
national and local codes for possible
variations.
5. Wiring shall comply with all applicable national and local
electrical codes.
6. Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
- Primary AC Input: 3φ, 3-wire + ground.
12. Ratings of wires and overcurrent devices are suggested
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.
- Alternate AC Input: 3φ, 3-wire + ground.
- AC Output: 3φ, 3-wire + ground.
- DC Input: 2-wire (Positive/Negative) + ground.
7. Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
TOSHIBA INTERNATIONAL CORPORATION
13131 West Little York Road
Houston, TX 77041
Telephone: (800) 231-1412
Fax: (713) 896-5212
8. Maximum battery discharge current based on lowest
permissible discharge voltage of 1.67 VPC.
9. DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
10. Weights do not include batteries or other auxiliary
equipment external to the UPS.
G9000 Installation and Operation Manual
89
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Planning Guide for 500kVA UPS
Standard System: 480V Input, 480V Output
General Mechanical Information
Approximate Full-Load Mechanical Clearance (Inches)from UPS
Dimensions
(W x D x H)
Floor
Loading
Lbs./ft. 2
Weight
Lbs.
Heat Rejection
for Ventilation and Maintenance Access
Inches
kBtu/Hr
Top
Front
Bottom Sides**
Back
70.9” x 32.7” x 80.7”* 3300
205
52.8
23.6”
42.3”
0”
0”
0”
* Height includes removable fan housing – Frame height is 78.7”.
** 0” clearance for peripheral equipment, 1” clearance for walls.
Primary AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power Demand
Normal Mode (Recharge Mode)
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size: Min. – Max. Per Phase
kVA
PF
Amps
AWG or kcmil at 75º C Temp. Rating
521 (562)
>0.99
626 (676)
800 AT
(3) x 300 kcmil – (3) x 350 kcmil
Alternate (Bypass) AC Input (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase
Maximum Input Power Demand
kVA
PF
Amps (Max.)
Amps
AWG or kcmil at 75º C Temp. Rating
500
1.0
601
800 AT
(3) x 300 kcmil – (3) x 350 kcmil
Battery Input (480VDC Nominal)
Battery Capacity Required Maximum Discharge
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size:
for Full Load Output
at Full Load
kWB
Amps DC
AWG or kcmil at 75º C Temp. Rating
512 @ 1.0 PF
1292
1400 AT
4 x 400 kcmil – 4 x 500 kcmil
* Contact factory rep for alternate configurations.
AC Output (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase
Rated Output Power
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
500
1.0
601
800 AT
(3) x 300 kcmil – (3) x 350 kcmil
Important Notes:
11. Cable sizing calculations based on the following assumptions:
1. Maximum input current is limited to 108% of the full-load
input current.
-
Minimum size is smallest size based on ampacity at 30 °C.
Maximum size cable is based on cable bend radius
limitations at the UPS terminals.
-
2. Output load conductors are to be installed in separate
conduit from input conductors.
-
Not more than 3 current-carrying conductors installed in
conduit in ambient temperature of 30 °C.
Temperature rating of copper conductors/terminals: 75 °C.
Reference: 2005 NEC Handbook, Table 310.16.
3. Control wires and power wires are to be installed in
separate conduits.
-
-
4. Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
NOTE: Consult latest edition of applicable
national and local codes for possible
variations.
5. Wiring shall comply with all applicable national and local
electrical codes.
6. Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
- Primary AC Input: 3φ, 3-wire + ground.
12. Ratings of wires and overcurrent devices are suggested
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.
- Alternate AC Input: 3φ, 3-wire + ground.
- AC Output: 3φ, 3-wire + ground.
- DC Input: 2-wire (Positive/Negative) + ground.
7. Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
TOSHIBA INTERNATIONAL CORPORATION
13131 West Little York Road
Houston, TX 77041
Telephone: (800) 231-1412
Fax: (713) 896-5212
8. Maximum battery discharge current based on lowest
permissible discharge voltage of 1.67 VPC.
9. DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
10. Weights do not include batteries or other auxiliary
equipment external to the UPS.
90
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Planning Guide for 750kVA UPS
Standard System: 480V Input, 480V Output
General Mechanical Information
Approximate Full-Load
Heat Rejection
Mechanical Clearance (Inches)from UPS
for Ventilation and Maintenance Access
Dimensions
(W x D x H)
Floor
Loading
Weight
Inches
Lbs.
Lbs./ft. 2
Btu/Hr
Top
Front
Bottom Sides**
Back
90.6” x 32.7” x 80.7”*
4255
207
79,147
20”
40”
0”
0”
0”
* Height includes removable fan housing – Frame height is 78.7”.
** 0” clearance for peripheral equipment, 1” clearance for walls.
Primary AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power Demand
Normal Mode (Recharge Mode)
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size: Min. – Max. Per Phase
kVA
PF
Amps
AWG or kcmil at 75º C Temp. Rating
781 (875)
>0.99
939 (1052)
1400 A
(4) x 500 kcmil
Alternate (Bypass) AC Input (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase
Maximum Input Power Demand
kVA
PF
Amps (Max.)
Amps
AWG or kcmil at 75º C Temp. Rating
750
1.0
902
1200 A
(4) x350 kcmil – (4) x 400 kcmil
Battery Input (480VDC Nominal)
Battery Capacity Required
for Full Load Output
kWB
Discharge at Full
Load
Suggested External
Overcurrent Protection
Amps
External Feeder Wire Size:
Amps DC
AWG or kcmil at 75º C Temp. Rating
776 @ 1.0 PF
1935
2000 AT
(6) x 400 kcmil – (6) x 500 kcmil
* Contact factory rep for alternate configurations.
AC Output (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase
Rated Output Power
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
750
1.0
902
1200 A
(4) x350 kcmil – (4) x 400 kcmil
Important Notes:
11. Cable sizing calculations based on the following assumptions:
1. Maximum input current is limited to 106% of the full-load
input current.
-
Minimum size is smallest size based on ampacity at 30 °C.
Maximum size cable is based on cable bend radius
limitations at the UPS terminals.
-
2. Output load conductors are to be installed in separate
conduit from input conductors.
-
Not more than 3 current-carrying conductors installed in
conduit in ambient temperature of 30 °C.
Temperature rating of copper conductors/terminals: 75 °C.
Reference: 2005 NEC Handbook, Table 310.16.
3. Control wires and power wires are to be installed in
separate conduits.
-
-
4. Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
NOTE: Consult latest edition of applicable
national and local codes for possible
variations.
5. Wiring shall comply with all applicable national and local
electrical codes.
6. Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
- Primary AC Input: 3φ, 3-wire + ground.
12. Ratings of wires and overcurrent devices are suggested
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.
- Alternate AC Input: 3φ, 3-wire + ground.
- AC Output: 3φ, 3-wire + ground.
- DC Input: 2-wire (Positive/Negative) + ground.
7. Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
TOSHIBA INTERNATIONAL CORPORATION
13131 West Little York Road
Houston, TX 77041
Telephone: (800) 231-1412
Fax: (713) 896-5212
8. Maximum battery discharge current based on lowest
permissible discharge voltage of 1.67 VPC.
9. DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
10. Weights do not include batteries or other auxiliary
equipment external to the UPS.
G9000 Installation and Operation Manual
91
Download from Www.Somanuals.com. All Manuals Search And Download.
92
G9000 Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
G9000 Installation and Operation Manual
93
Download from Www.Somanuals.com. All Manuals Search And Download.
INDUSTRIAL DIVISION
13131 West Little York Rd., Houston, TX 77041
Tel: 713/466-0277 Fax 713/466-8773
US 877/867-8773
Canada 800/872-2192
Mexico 01/800/527-1204
www.toshiba.com/ind
Printed in Japan
Download from Www.Somanuals.com. All Manuals Search And Download.
|