Toshiba Power Supply 100 User Manual

UNINTERRUPTIBLE POWER SYSTEM (UPS)  
G8000 SERIES  
INSTALLATION and  
OPERATION MANUAL  
480/480 V 80/100/125/150/225/300/500 kW  
Document: 61001-002  
April 2013  
© Copyright 2013 Toshiba International Corporation  
All rights reserved.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNINTERRUPTIBLE POWER SYSTEM (UPS)  
G8000 SERIES  
INSTALLATION and OPERATION MANUAL  
480/480 V 80/100/125/150/225/300/500 kW  
Document: 61001-002  
April 2013  
© Copyright 2013 Toshiba International Corporation  
All rights reserved.  
G8000 Series Installation and Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Toshiba products listed in this document are intended for usage in general electronics applications  
(computer, personal equipment, office equipment, measuring equipment, industrial robotics, domestic  
appliances, etc.). These Toshiba products are neither intended nor warranted for usage in equipment that  
requires extraordinarily high quality and/or reliability; nor are they intended to be used in equipment that, if  
a malfunction or failure occurs, may result in loss of human life or bodily injury (collectively referred to as  
“Unintended Usage”). Unintended Usage includes atomic energy control instruments, airplane or spaceship  
instruments, transportation instruments, traffic signal instruments, combustion control instruments, life  
support equipment, all types of safety devices, etc. Unintended Usage of Toshiba products listed in this  
document shall be made at the customer’s own risk.  
NOTICE  
PLEASE INFORM TOSHIBA INTERNATIONAL CORPORATION OR AUTHORIZED  
REPRESENTATIVE IN CASE OF INCONSISTENCIES, OMISSIONS, OR QUESTIONS.  
The instructions contained in this manual are not intended to cover all of the details or variations in equipment,  
nor to provide for every possible contingency concerning installation, operation, or maintenance. Should  
further information be required or if problems arise which are not covered sufficiently contact your Toshiba  
sales office.  
The contents of this instruction manual shall not become a part of or modify any prior or existing agreement,  
commitment, or relationship. The sales contract contains the entire obligation of Toshiba International  
Corporation’s UPS Division. The warranty contained in the contract between the parties is the sole warranty  
of Toshiba International Corporation’s UPS Division and any statements contained herein DO NOT create  
new warranties or modify the existing warranty.  
Any electrical or mechanical modifications to this equipment without prior written consent of Toshiba  
International Corporation will void all warranties and may void the UL/CULlisting. Unauthorized modifications  
can also result in personal injury, death, or destruction of the equipment.  
QUALIFIED PERSONNEL ONLY  
Qualified Personnel is one that has the skills and knowledge relating to the construction, installation,  
operation, and maintenance of the electrical equipment and has received safety training on the  
hazards involved (Refer to the latest edition of NFPA 70E for additional safety requirements).  
G8000 Series Installation and Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNINTERRUPTIBLE POWER SYSTEM (UPS)  
Please complete the following information and retain for your records.  
Unless otherwise specified, the warranty period for the UPS or UPS part is 12 months from the shipment  
date (see Toshiba International Corporation bill of lading).  
Unless otherwise specified, the warranty period for a UPS battery is 36 months from the shipment date (see  
Toshiba International Corporation Bill of Lading for shipping date).  
JOB NUMBER  
MODEL NUMBER  
SERIAL NUMBER  
APPLICATION  
SHIPMENT DATE  
INSTALLATION DATE  
INSPECTED BY  
G8000 Series Installation and Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Purpose  
This manual provides information on how to safely install and operate your Toshiba International Corporation  
power electronics product. This manual includes a section of general safety instructions that describes the  
warning labels and symbols that are used throughout the manual. Read the manual completely before  
installing, operating, or performing maintenance on this equipment.  
This manual and the accompanying drawings should be considered a permanent part of the equipment and  
should be readily available for reference and review. Dimensions shown in the manual are in metric and/or  
the English customary equivalent.  
Toshiba International Corporation reserves the right, without prior notice, to update information, make  
product changes, or discontinue any product or service identified in this publication.  
Toshiba is a registered trademark of the Toshiba Corporation.All other product or trade references appearing  
in this manual are registered trademarks of their respective owners.  
Toshiba International Corporation shall not be liable for direct, indirect, special, or consequential damages  
resulting from the use of the information contained within this manual.  
This manual is copyrighted. No part of this manual may be photocopied or reproduced in any form without  
the prior written consent of Toshiba International Corporation.  
© Copyright 2013 Toshiba International Corporation  
All rights reserved.  
Printed in the U.S.A.  
Toshiba’s Customer Support Center  
Contact the Toshiba Customer Support Center for assistance with application information or for any  
problems that you may experience with your Uninterruptible Power System (UPS).  
Toshiba Customer Support Center  
8 a.m. to 5 p.m. (CST) - Monday through Friday  
USA Toll Free (877) 867-8773  
Tel (713) 466-0277  
Fax (713) 896-5212  
You may also contact Toshiba by writing to:  
Toshiba International Corporation  
13131 West Little York Road  
Houston, Texas 77041-9990  
Attn: UPS Product Manager  
For further information on Toshiba’s products and services, please visit our website at:  
www.toshiba.com/ind  
G8000 Series Installation and Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
1
2
Introduction..........................................................................................................................1  
General Safety Instructions................................................................................................2  
2.1 Symbols .......................................................................................................................2  
2.2 Signal Words................................................................................................................3  
2.3 Qualified Personnel......................................................................................................3  
2.4 Factory Authorized Personnel......................................................................................4  
3
4
Important Safety Instructions.............................................................................................4  
Safety Precautions..............................................................................................................5  
4.1 Disclaimer ....................................................................................................................5  
4.2 General Maintenance...................................................................................................6  
4.3 Transporting/Unpacking...............................................................................................6  
4.4 Inspection/Storage.......................................................................................................8  
5
6
Installation Precautions......................................................................................................9  
5.1 Wiring/Connection........................................................................................................13  
Warning Labels....................................................................................................................14  
6.1 Warning Label Locations..............................................................................................15  
7
8
Weight and Dimensions .....................................................................................................18  
Transporting.........................................................................................................................19  
8.1 Transporting By Crane.................................................................................................20  
8.2 Transporting By Forklift................................................................................................21  
9
Storage/Operating Environment........................................................................................23  
9.1 Operating Precautions .................................................................................................23  
9.2 Maintenance Precautions ............................................................................................25  
9.3 Disposal .......................................................................................................................26  
10 Installation..........................................................................................................................27  
10.1 Unpacking..................................................................................................................28  
10.2 UPS Clearance ..........................................................................................................28  
10.3 Anchor Bolts...............................................................................................................29  
11 UPS Wiring .........................................................................................................................30  
11.1 80/100/125 kVA Terminal Blocks and Power Cables...................................................32  
G8000 Series Installation and Operation Manual  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
11.2 150, 225, 300, and 500 kVA Buss Strip Terminals and Power Cables.......................34  
11.3 UPS Power Cable Conduit Landing Plates................................................................39  
11.4 External Breakers.......................................................................................................42  
11.5 Grounding Wire..........................................................................................................42  
11.6 Control Wires..............................................................................................................44  
11.7 Grounding Configuration............................................................................................45  
12 UPS Specifications............................................................................................................49  
12.1 Specification Table.....................................................................................................49  
12.2 Typical Efficiency vs. Load.........................................................................................52  
13 Operator Interface .............................................................................................................53  
13.1 Key-Switch and Buttons.............................................................................................54  
13.2 LCD/LED Indicators ...................................................................................................55  
13.3 LCD Indicators ...........................................................................................................56  
13.4 Normal Display...........................................................................................................57  
13.5 Fault Display ..............................................................................................................59  
13.6 LCD Scroll..................................................................................................................60  
14 Operating the UPS.............................................................................................................61  
14.1 Operation Types.........................................................................................................62  
14.2 Pre-operational Check ...............................................................................................62  
14.3 Startup Procedures....................................................................................................63  
14.4 Switch Power Supply (UPS to Bypass)......................................................................65  
14.5 Stop............................................................................................................................66  
14.6 Complete Shutdown...................................................................................................67  
14.7 Changing Between Float Charge and Equalize Charge ............................................68  
14.8 Changing to Float Charge from Protection Charge (If applicable).............................69  
14.9 Emergency Power Off (EPO).....................................................................................70  
15 Troubleshooting ................................................................................................................70  
15.1 Types of Errors...........................................................................................................70  
15.2 Faults and Warnings Data Screen .............................................................................71  
15.3 LCD Fault & Warning Displays...................................................................................72  
15.4 Fault Messages..........................................................................................................73  
15.5 LCD Scroll (w/ faults or warnings)..............................................................................75  
15.6 Restoring UPS Operation ..........................................................................................76  
G8000 Series Installation and Operation Manual  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16 Periodic Maintenance/Parts Replacement......................................................................77  
16.1 Scheduled Maintenance ............................................................................................77  
16.2 Parts Replacement ....................................................................................................77  
Appendix A - Installation Planning Guides .............................................................................79  
80kVA IPG.............................................................................................................................79  
100kVA IPG...........................................................................................................................82  
125kVA IPG...........................................................................................................................85  
150kVA IPG...........................................................................................................................88  
225kVA IPG...........................................................................................................................91  
300kVA IPG...........................................................................................................................94  
500kVA IPG...........................................................................................................................97  
Appendix B - Outline Drawings................................................................................................101  
Appendix C - 500kVA Input- and Output- Cabinet Joining Instructions...............................105  
G8000 Series Installation and Operation Manual  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G8000 Series Installation and Operation Manual  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1 Introduction  
This manual provides information on how to safely operate your G8000 Series Uninterruptible Power  
System (UPS). This manual includes a section of general safety instructions that describes the warning  
labels and symbols that are used throughout the manual. Read the manual completely before installing,  
operating, or performing maintenance on this equipment.  
Qualified personnel should read this manual carefully before transporting, installing and wiring the UPS. In  
addition have a thorough understanding of the information provided in the chapters titled:  
• General Safety Instructions  
• Important Safety Instructions  
• Safety Precautions  
• Installation Precautions  
Please read the G8000 Series Operation Manual for important instructions on operating the UPS. This  
manual and the accompanying drawings should be considered a permanent part of the equipment and  
should be readily available for reference and review. Dimensions shown in the manual are in metric and/or  
the English customary equivalent.  
Keep the Installation Manual and the Operation Manual near the UPS for necessary reference.  
SAVE THESE INSTRUCTIONS  
G8000 Series Installation and Operation Manual  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 General Safety Instructions  
DO NOT attempt to transport, install, operate, maintain or dispose of this equipment until you have read and  
understood all of the product safety information provided in this manual.  
2.1 Symbols  
The symbols listed below are used throughout this manual. When symbols are used in this manual they will  
include important safety information that must be carefully followed.  
Safety Alert Symbol indicates that a potential  
personal injury hazard exists.  
Prohibited Symbol indicates DO NOT take action.  
Mandatory Symbol indicates that the following  
instruction is required.  
Ground Symbol indicates the location of the  
equipment grounding conductor.  
Electrical - Voltage & Shock Hazard Symbol  
indicates parts inside may cause electric shock.  
Explosion Hazard Symbol indicates parts may  
explode.  
G8000 Series Installation and Operation Manual  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.2 Signal Words  
The signal words listed below are used throughout this manual. When the words DANGER, WARNING,  
CAUTION and ATTENTION are used in this manual they will include important safety information that  
must be carefully followed.  
The word DANGER in capital letters preceded by  
the safety alert symbol indicates that an imminently  
DANGER  
hazardous situation exists, and if not avoided  
will result in loss of life or serious injury to  
personnel.  
The word WARNING in capital letters preceded by  
the safety alert symbol indicates that a potentially  
WARNING  
hazardous situation exists, and if not avoided  
may result in loss of life or serious injury to  
personnel.  
The word CAUTION in capital letters preceded by  
the safety alert symbol indicates that a potentially  
hazardous situation exists, and if not avoided may  
result in minor or moderate injury.  
CAUTION  
ThewordNOTICEincapitalletterswithoutthesafety  
alert symbol indicates a potentially hazardous  
situation exists, and if not avoided may result in  
NOTICE  
equipment and property damage.  
2.3 Qualified Personnel  
Installation, operation, and maintenance shall be performed by Qualified Personnel Only. A Qualified  
Person is one that has the skills and knowledge relating to the construction, installation, operation, and  
maintenance of the electrical equipment and has received safety training on the hazards involved (Refer  
to the latest edition of NFPA 70E for additional safety requirements).  
Qualified Personnel shall:  
Have read the entire operation manual.  
Be familiar with the construction and function of the UPS, the equipment being driven, and the  
hazards involved.  
Be trained and authorized to safely energize, de-energize, ground, lockout/tagout circuits and  
equipment, and clear faults in accordance with established safety practices.  
Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves,  
hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety  
practices.  
G8000 Series Installation and Operation Manual  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Be trained in rendering first aid.  
For further information on workplace safety visit www.osha.gov.  
2.4 Factory Authorized Personnel  
Factory authorized personnel have been factory trained and certified to install, service, and repair the  
UPS. Contact the Toshiba Customer Support Center for assistance in locating the factory authorized  
personnel nearest you.  
3 Important Safety Instructions  
The following contains important instructions that should be followed during the installation, operation, and  
maintenance of the G8000 Series UPS.  
Please refer to the battery manufacturer’s instructions for details on operating, maintaining and/or replacing  
the batteries for each system. Keep unauthorized personnel from batteries. Only a certified service  
representative with battery experience should perform service on batteries.  
CAUTION  
Misuse of this equipment could result in personal injury and/or equipment damage.  
In no event will Toshiba Corporation be responsible or liable for either indirect or  
consequential damage or injury that may come from the use of this equipment.  
The UPS system input and output is NOT equipped with an over-current protection device, or an  
output disconnection at the AC output. The user should provide circuit breakers between the UPS AC  
input (or Bypass input) and the power sources and between the UPS output and the critical load input. The  
minimum device ratings are listed in Table 3.1.  
TABLE 3.1 UPS MINIMUM DEVICE RATINGS  
CapaCity  
Rated Output  
input BReakeR Rating  
Output BReakeR Rating  
80 kVA  
480 V/277 V  
480 V/277 V  
480 V/277 V  
480 V/277 V  
480 V/277 V  
480 V/277 V  
480 V/277 V  
480 V – 150 A  
480 V – 200 A  
480 V – 200 A  
480 V – 300 A  
480 V – 400 A  
480 V – 600 A  
480 V – 800 A  
480 V – 125 A  
480 V – 150 A  
480 V – 200 A  
480 V – 250 A  
480 V – 350 A  
480 V – 500 A  
480 V – 800 A  
100 kVA  
125 kVA  
150 kVA  
225 kVA  
300 kVA  
500 kVA  
80/100/150/225/300 kVA Temperature restrictions: The maximum operating ambient temperature is 86 °F  
(30 °C) at 1.0 PF, and 104 °F (40 °C) at 0.8 PF. If the UPS is exposed to the same ambient temperature as  
the battery system, the maximum operating ambient temperature is 86 °F (30 °C) at 1.0 PF, 90 °F (32 °C)  
at 0.8 PF. Table 3.2 lists the nominal battery voltage.  
G8000 Series Installation and Operation Manual  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 3.2 UPS NOMINAL BATTERY VOLTAGE  
CapaCity  
nOminal VOltage  
360 Vdc  
FlOat VOltage  
80 kVA  
100 kVA  
125 kVA  
150 kVA  
225 kVA  
300 kVA  
500 kVA  
405 V  
405 V  
405 V  
405 V  
405 V  
405 V  
540 V  
360 Vdc  
360 Vdc  
360 Vdc  
360 Vdc  
360 Vdc  
480 Vdc  
4 Safety Precautions  
The Toshiba products listed in this document are intended for usage in general electronics applications  
(computer, personal equipment, office equipment, measuring equipment, industrial robotics, domestic  
appliances, etc.). These Toshiba products are neither intended nor warranted for use in equipment that, if  
a malfunction or failure occurs, may result in loss of human life or bodily injury (collectively referred to as  
“Unintended Usage”). Unintended Usage includes atomic energy control instruments, airplane or spaceship  
instruments, transportation instruments, traffic signal instruments, combustion control instruments, medical  
operating room or life support equipment, all types of safety devices, etc. Unintended Usage of Toshiba  
products listed in this document shall be made at the customer’s own risk.  
The application of the UPS without special consideration for equipment that supports human safety and/or  
maintain public services may cause serious accidents.  
4.1 Disclaimer  
IN NO EVENT WILL TOSHIBA CORPORATION BE RESPONSIBLE OR LIABLE FOR EITHER INDIRECT  
OR CONSEQUENTIAL DAMAGE OR INJURY THAT MAY COME FROM THE MISUSE OF THIS  
EQUIPMENT. ANY MODIFICATIONS WITHOUT AUTHORIZATION BY TOSHIBA COULD RESULT IN  
PERSONAL INJURIES, DEATH OR DESTRUCTION OF THE UPS.  
TOSHIBA RESERVES THE RIGHT TO MAKE CHANGES WITHOUT FURTHER NOTICE TO ANY  
PRODUCTS HEREIN TO IMPROVE RELIABILITY, FUNCTION OR DESIGN. TOSHIBA DOES NOT  
ASSUME ANY LIABILITY ARISING OUT OF THE APPLICATION OR USE OF ANY PRODUCT OR UPS  
DESCRIBED HEREIN; NEITHER DOES IT CONVEY ANY LICENSE UNDER ITS PATENT RIGHTS, NOR  
THE RIGHTS OF OTHERS.  
G8000 Series Installation and Operation Manual  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2 General Maintenance  
WARNING  
DO NOT remove the rear/side panels, or any sheet metla not  
designed to be removed.  
Removing rear/side panels may result in electric shock, burns,  
personal injuries or UPS failure.  
Keep the area arround the UPS clean.  
Use a vacuum cleaner to clean the UPS.  
Only factory authorized personnel sould perform internal general  
maintenance on the UPS.  
Contact the authorized Toshiba Customer Support Center or  
an authorized Toshiba representative for informaton on proper  
disposal of UPS components.  
It is illegal to dispose of certain components without conforming to  
environmental regulations for indusrial/commercial waste.  
4.3 Transporting/Unpacking  
WARNING  
WhentransportingtheUPSbycrane,followtheSPECIFIEDWORKPROCEDURE.  
The suspension wire angle should be less than 60°.  
The UPS falling or overturning may cause crushing, trapping or other personal  
injuries.  
See Installation Manual: Chapter 8 - Transporting  
DO NOT tilt the UPS more than 10° from upright position.  
Tilting the UPS more than 10° may cause crushing, trapping or other  
personal injuries.  
G8000 Series Installation and Operation Manual  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
DO NOT transport, move, store, or place the UPS on its side.  
Forces due to heavy components inside may damage the UPS.  
Avoid vibration or shock exceeding 0.5G.  
Failing to observe this precaution may cause damage to the UPS.  
DO NOT allow the UPS to suffer shock or impact when  
unpacking.  
Tools used to remove packaging materials may cause damage to the  
UPS.  
DO NOT push or pull on the sides of the packaging.or the  
UPS to move it. Always use a crane, forklift, or pallet jack for  
transporting and positioning the UPS.  
Pushing/pulling on the sides of the unit to move it may result in damage  
to the UPS. See Figure 4.1 Exterior Handling label.  
Fig. 4.1 Exterior Handling label  
BY CRANE:  
- Cables should have sufficient rating  
and equal length.  
- Keep UPS leveled when lifting/lowering  
and avoid impacts.  
BY FORKLIFT:  
- Verify forklift maximum load capacity.  
Do not push or  
pull from sides  
- Ensure that the forks are long enough  
to support the UPS and are inserted  
properly.  
Do not push or  
pull from sides  
CKSIDE  
- Do not swing or tilt the UPS when  
lifting and/or transporting.  
BA  
See manual for complete details.  
FORKS (4 Ft. Minimum length)  
WARNING:  
Risk of tipping. For safe handling, lift UPS from back and sides only (as shown above)  
G8000 Series Installation and Operation Manual  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4 Inspection/Storage  
Inspection  
Upon receipt of the UPS, an inspection for shipping damage should be performed. Use caution when  
removing the unit from the pallet. Refer to labels or documentation attached to packing material.  
Unpacking  
Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping,  
keep all original crating and packing materials for return to the shipping agent.  
NOTE: The factory warranty does not apply to damage incurred during shipping!  
Ensure that the rated capacity and the model number specified on the nameplate conform to the order  
specifications.  
Storage  
During periods of non-use, the following guidelines are recommended for storage.  
Storage Preparation  
1) Power up the UPS and allow it to operate with no load for 24 hours to fully charge  
the batteries.  
2) Stop the unit.  
3) Place the Main Circuit Breaker switch in the “OFF” position.  
Storage Conditions  
• For best results, store the UPS in the original shipping container and place on a wood  
or metal pallet  
• Storage temperature range: -4 to 104 °F (-20 to 40 °C)  
• The optimum storage temperature is 70 °F (21 °C). A higher ambient temperature will  
require recharging more frequently during storage  
Avoid the following storage locations:  
• Locations that are subject to extreme temperature changes or high humidity  
• Locations that are subject to high levels of dust or metal particles  
• Locations that are subject to excessive vibration  
• Inclined floor surfaces  
G8000 Series Installation and Operation Manual  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
5 Installation Precautions  
CAUTION  
Install the UPS in a controlled environment.  
Improper storage and installation environment may deteriorate  
insulation, shorten component life and cause malfunctions.  
See Table 5.1 - UPS Installation Environment Standards  
DO NOT tilt the UPS more than 10° from upright position.  
Tilting the UPS more than 10° may cause crushing, trapping or other  
personal injuries and cause physical damage to internal components.  
WARNING  
Keep the SPECIFIED CLEARANCE around the UPS.  
Inadequate space around the UPS makes it difficult to perform  
maintenance/inspections, will lead to insufficient ventilation, and/or  
cause malfunctions.  
Install anchor bolts to secure the UPS to the installation floor.  
The UPS may fall during an earthquake if the anchor bolts are not  
installed and secured.  
Only factory authorized personnel should relocate, modify, or  
replace parts in the UPS after initial installation.  
Electrical shock, injury or UPS failure may occur if non-authorized  
technicians attempt to modify or relocate the UPS.  
Please contact Toshiba Customer Support Center if you plan to move  
or make modifications to the UPS  
G8000 Series Installation and Operation Manual  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
DO NOT block air vents.  
Blocking the vents will increase the internal temperatures and may  
result in UPS failure or fire.  
DO NOT install the UPS where water may fall on it.  
Water may cause electrical shock, personal injury or UPS failure.  
DO NOT use floor wax that contains silicon in the UPS storage  
area and/or nearby rooms.  
Floor wax that contains silicon may cause static electricity.  
WARNING  
The UPS should be installed per local and/or national electric codes  
by qualified personnel.  
Faults or improper operation may occur if the UPS is not installed  
properly.  
When an external maintenance bypass is installed for the UPS,  
before switching to external bypass, ensure that the UPS unit is  
switched to AC Bypass mode and the UPS control panel display  
verifies the unit is Bypass mode.  
Switching to the external bypass while the unit is in UPS mode may  
damage the UPS.  
G8000 Series Installation and Operation Manual  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 5.1 - UPS INSTALLATION ENVIRONMENT STANDARDS  
Item  
Environment standard  
Installation Location Indoors  
Minimum operating temperature: 32 °F (0 °C).  
Maximum operating temperature: 86 °F (30 °C) at 1.0 PF (UPS with/without  
battery system).  
Ambient  
Temperature  
Maximum operating temperature: 90 °F (32 °C) at 0.8 PF (UPS with battery  
system).  
Maximum operating temperature: 104 °F (40 °C) at 0.8 PF (UPS only).  
Average 24-hour operating temperature: 86 °F (30 °C) at 1.0 PF and 41 – 95 °F  
(5 35 °C) at 0.8 PF.  
The relative humidity must be between 30 and 90% noncondensing due to  
temperature changes.  
Relative Humidity  
Altitude  
These specifications are for altitudes up to 3240 ft. (1000 m) above sea level.  
Consult with the factory to determine the derating factor for installations above  
3240 ft. (1000 m).  
Installation environment must not have vibration frequencies 10 Hz 20 Hz.  
The acceleration due to vibrations less than 10 Hz must not exceed 0.5 G.  
The acceleration due to vibrations 20 Hz 50 Hz must not exceed 0.5 G.  
The total amplitude due to vibrations 50 Hz 100 Hz must not exceed 0.1 mm.  
Vibration and  
Mechanical Shock  
Dust must not exceed normal atmospheric levels and must not include conductive  
particles, silicone or oils.  
Dust  
No flammable and/or explosive gas.  
Hydrogen sulfide (H2S)  
Sulfurous acid gas (SO2)  
Chlorine gas (Cl2)  
Less than or equal to 0.0001 PPM  
Less than or equal to 0.05 PPM  
Less than or equal to 0.002 PPM  
Less than or equal to 0.1 PPM  
Less than or equal to 0.02 PPM  
Flammable Gas  
Ammonia gas (NH3)  
Nitrous acid gas (NO2)  
Nitrous oxides (NOx)  
Ozone (O3)  
Less than or equal to 0.02 PPM  
Less than or equal to 0.002 PPM  
Hydrochloric acid mist (HCl)  
Less than or equal to 0.1 mg/m3  
Installation Precautions  
1) Install the unit in a stable, level and upright position that is free of excessive  
vibration.  
2) Install the unit where the ambient temperature is within the specified range.  
3) DO NOT install the UPS in areas that are subject to high humidity.  
4) DO NOT install the UPS in areas that allow exposure to direct sunlight.  
5) DO NOT install the UPS in areas that allow exposure to high levels of airborne dust,  
metal particles, or flammable gases.  
6) DO NOT install the UPS in areas near sources of electrical noise. Ensuring a proper  
earth ground will reduce the effects of electrical noise and will reduce the potential for  
electrical shock.  
G8000 Series Installation and Operation Manual  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7) The UPS generates and can radiate radio-frequency energy during operation. Although  
RFI noise filters are installed inside of the unit, there is no guarantee that the UPS will  
not influence some sensitive devices that are operating near by. If such interference  
is experienced, the UPS should be installed further away from the affected equipment  
and/or powered from a different source than that of the installed equipment.  
8) The user should provide over-current protection for hardwired UPS systems between  
the UPS output and the load input.  
9) After ensuring that all power sources are turned “OFF” and isolated in accordance with  
established lockout/tagout procedures, connect the power source wiring of the correct  
voltage to the input terminals of the UPS.  
NOTE: Ensure the input phasing is connected in clockwise rotation (CW). UPS internal  
circuitry is designed to disable further UPS operation if the input phasing is  
installed in counter-clockwise rotation (CCW).  
10) Connect the output terminals of the UPS to the load (refer to NEC Article 300 - Wiring  
Methods and Article 310 - Conductors For General Wiring). Size the branch circuit  
conductors in accordance with NEC Table 310.16 as published 9/2007.  
WARNING  
METAL CONDUIT IS NOT AN ACCEPTABLE GROUND.  
Conductor Routing and Grounding  
1) Use separate metal conduits for routing the input power, output power, and control  
circuits.  
2) Follow the wire size and tightening torque specifications.  
3) Always ground the unit to reduce the potential for electrical shock and to help reduce  
electrical noise.  
4) A separate ground cable should be run inside the conduit with the input power, output  
power, and control circuits.  
G8000 Series Installation and Operation Manual  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.1 Wiring/Connection  
WARNING  
Perform wiring and connections with correct polarity.  
Be careful when connecting the UPS to the battery system. A wrong  
connection may cause damage to the UPS, battery, or charger.  
Connect ONLY one (1) ground wire to the earth ground terminal.  
A missing ground wire may cause an electrical shock hazard.  
Connecting to more than one ground may cause a ground loop.  
See Chapter 8 - UPS Wiring  
DO NOT force, bend, or pull wires.  
DO NOT damage wire insulation.  
DO NOT place heavy objects on top of UPS.  
Observe the above precautions when making wire connections or  
handling the wires. Failing to observe these precautions may damage  
the insulation of the wires or may cause a fire or an electric shock  
hazard.  
NOTICE  
Follow the torque criteria for tightening screws.  
Loose connections may cause fire due to heating.  
See Chapter 11 - UPS Wiring  
G8000 Series Installation and Operation Manual  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 Warning Labels  
Below are representative warning labels and their location on the UPS. Exterior Handling labels shown in  
section 4.3, Transporting/Unpacking, are in the manual packet, and attached to the UPS shipping cover-  
ing and shipping pallet.  
NOTICE  
Make sure all the warning labels are installed in the appropriate locations.  
If a label is missing or illegible, contact Toshiba Customer Support Center or an  
authorized representative.  
(A) 48082  
(B) 40308  
DANGER  
DANGER  
AC VOLTAGE  
HAZARDOUS VOLTAGES  
Hazardous voltages are used in the operation  
of this equipment and could cause severe personal  
injury or loss of life.  
The following precautions should be observed to  
reduce the risk of injury or death.  
This UPS receives power from more  
than one source. Disconnect all AC  
sources before performing any service  
or testing inside this unit  
Only qualified technicians familiar with this equipment and the  
information supplied with it should be permitted to install and  
operate this equipment.  
Installation of electrical equipment must be done i n  
accordance with National Electrical Code and any other state  
or local codes. Proper grounding and conductor siz ing must  
be installed for safe operation.  
48082  
During operation, keep all covers in place and cabi net  
doors shut.  
When performing visual inspections and maintenance, if  
possible, be sure the UPS is turned off and the inc oming  
AC feed is turned off and locked out.  
The UPS and Battery Cabinet will have hazardous  
voltages present even after the AC feed is turned off.  
56875 FOR 80, 100, 150, 225 KVA  
(C)
If it is necessary to make measurements with the power  
on, do not touch any electrical connection points. Remove  
all jewelry from wrists and fingers. Make sure test equipment  
is in good, safe operating condition.  
USE COPPER CONDUCTORS ONLY!  
REFER TO INSTRUCTION MANUAL FOR WIRE SIZE AND TIGHTENING TORQUE  
1
2
3
4
5
6
7
8
9
10  
W
11  
N
12  
13  
While servicing, stand on some type of insulation, and be  
sure not to be grounded.  
U
V
W
U
V
W
N
U
V
-
+
480V  
480V  
AC OUTPUT  
400V  
480V  
BYPASS INPUT  
Follow the safety instructions given in the equipment manual  
carefully and observe all danger, warning and cauti on notices.  
AC INPUT  
BATTERY  
40308  
(C) 58708 FOR 300KVA  
USE COPPER CONDUCTORS ONLY !  
REFER TO INSTRUCTION MANUAL FOR WIRE SIZE AND TIGHTENING TORQUE  
(D) 40830  
WARNING  
CRITICAL FUSE SIZING  
1
2
3
6
7
8
9
10  
U
11  
V
12  
W
4
5
Incorrect fuse replacement size  
may result in fire or inadequate  
equipment protection.  
U
V
W
U
V
W
N
-
+
480V  
400V  
480V  
AC OUTPUT  
480V  
BYPASS INPUT  
AC INPUT  
BATTERY  
Replace only with same type  
and rating of fuse.  
PN 40830  
G8000 Series Installation and Operation Manual  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(E) 39561  
(F) 58705 SERIAL LABEL  
UNINTERRUPTIBLE POWER SUPPLY  
(G) 57055  
GND  
DANGER  
RISK OF ELECTRIC SHOCK  
Capacitors stay charged after power  
has been shut off.  
Accidental contact with live parts can  
cause personal injury and death.  
Turn off and lock out all power sources.  
Wait at least five (5) minutes for power  
to dissipate then check voltage before  
servicing.  
39561  
58705  
LISTED  
27E5  
MFD. IN U.S .A. FR OM FOREIGN AND DOMES TIC C OMP ON ENTS  
HOUSTON,TEXAS  
®
®
(I) 40831  
(J) 57053  
CAUTION  
CAUTION  
8A  
(control power source switch)  
Heat sink not grounded.  
Risk of electrical shock.  
Do not turn off while operating.  
Disconnect UPS and electrically  
test heat sink before touching.  
PN 40831  
6.1 Warning Label Locations  
FIGURE 6.2 – 80/100/125 KVA UPS WARNING LABELS  
G8000 Series Installation and Operation Manual  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 6.3 – 150/225 KVA UPS WARNING LABELS  
FIGURE 6.4 - 300 KVA UPS WARNING LABELS  
G8000 Series Installation and Operation Manual  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FINAL LAYOUT NOT AVAILABLE AT THIS TIME:  
CONTACT THE FACTORY FOR ADDITIONAL  
INFORMATION  
FIGURE 6.3 – 500 KVA UPS WARNING LABELS  
G8000 Series Installation and Operation Manual  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7 Weight and Dimensions  
Table 7.1 lists the unit and shipping weights for G8000 UPS models. See Appendix B for detailed outline  
and dimensioins of all models.  
TABLE 7.1 G8000 UPS UNIT AND SHIPPING WEIGHTS  
Model  
Unit  
Shipping  
80 kVA  
1390 lb. (630 kg)  
1440 lb. (652 kg)  
100 kVA  
125 kVA  
1740 lb. (789 kg)  
1740 lb. (789 kg)  
1790 lb. (812 kg)  
1790 lb. (812 kg)  
150 kVA  
2467 lb. (1119 kg)  
2980 lb. (1352 kg)  
4575 lb. (2075 kg)  
1570 lb. (712 kg)1  
4950 lb. (2245 kg)1  
2556 lb. (1159 kg)  
3069 lb. (1392 kg)  
4725 lb. (2143 kg)  
~1620 lb. (735 kg)1  
~5100 lb. (2313 kg)1  
225 kVA  
300 kVA  
500 kVA (Input Cabinet)  
500 kVA (Output Cabinet)  
1 - Weights are approximate.  
G8000 Series Installation and Operation Manual  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8 Transporting  
WARNING  
WhentransportingtheUPSbycrane,followtheSPECIFIEDWORKPROCEDURE.  
The suspension wire angle should be less than 60°.  
The UPS falling or overturning may cause crushing, trapping or other personal  
injuries.  
DO NOT tilt the UPS more than 10° from upright position.  
Tilting the UPS more than 10° may cause crushing, trapping or other  
personal injuries.  
CAUTION  
DO NOT transport, move, store, or place the UPS on its side.  
Excessive force applied from heavy components inside may damage  
the UPS.  
Avoid vibration or shock exceeding 0.5G.  
Failing to observe this precaution may cause damage to the UPS.  
DO NOT allow the UPS to suffer shock or impact when  
unpacking.  
Tools used to remove packaging materials may cause damage to the  
UPS.  
DO NOT install the UPS where water may fall on it.  
Water may cause electrical shock, personal injury or UPS failure.  
DO NOT push or pull on the sides of the packaging.or the  
UPS to move it. Always use a crane, forklift, or pallet jack for  
transporting and positioning the UPS.  
Pushing/pulling on the sides of the unit to move it may result in damage  
to the UPS. (See Figure 4.1 Exterior Handling label.)  
The UPS may be packed in a crate for extra protection during transportation. Avoid impact or vibration  
against the UPS during transportation. DO NOT expose the UPS directly to water.  
G8000 Series Installation and Operation Manual  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8.1 Transporting By Crane  
Cables should have sufficient ratings and be of the same length. Make sure the suspension cables are  
hooked at eyebolts. See Figure 8.1. Keep the angle less than 60° between cables.  
Refer to Chapter 7 - Weight and Dimension for UPS cabinet weight.  
Keep UPS leveled when lifting. DO NOT swing or tilt the UPS. Minimize the impact when lowering the UPS  
to the floor. Figure 8.2 and 8.3 indicate unacceptable lifting.  
Figure 8.4 and 8.5 show examples of acceptable and unacceptable operations.  
Less than 60°  
FIGURE 8.1 - CABLES AND EYEBOLTS TO LIFT THE UPS  
More than 60°  
Uneven Cables  
FIGURE 8.2 - ANGLE MORE THAN 60°  
FIGURE 8.3 - UNEVEN CABLES  
FIGURE 8.4 - ACCEPTABLE OPERATION  
FIGURE 8.5 - UNACCEPTABLE OPERATION  
G8000 Series Installation and Operation Manual  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8.2 Transporting By Forklift  
Refer to Chapter 7 - Weight and Dimensions.  
Verify forklift maximum load capacity and ensure that the forks are long enough to properly support the  
UPS. Insert the forks into the space shown in Figure 8.6. Spaces for the forks are provided underneath  
the UPS.  
DO NOT swing or tilt UPS when lifting and/or transporting. Minimize the impact when lowering the UPS to  
the floor.  
80 - 225 kVA  
Base  
Secure the forks against the base then lift  
Insert the forks here  
300 kVA  
Base  
Secure the forks against the base then lift  
Insert the forks here  
FIGURE 8.6 -TRANSPORTING 80-300 KVA UPS BY FORKLIFT  
G8000 Series Installation and Operation Manual  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
500 kVA  
(Ships in two parts, Input  
and Output Cabinets)  
Output Cabinet  
Input Cabinet  
Insert the forks here.  
Insert the forks here.  
Secure forks against  
the base and then lift.  
Secure forks against  
the base and then lift.  
FIGURE 8.7 -TRANSPORTING 500 KVA UPS BY FORKLIFT  
(See Appendix C for cabinet mating insturctions)  
G8000 Series Installation and Operation Manual  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9 Storage/Operating Environment  
Observe the following when storing the UPS.  
Store UPS indoors.  
Maximum storage time for the UPS between powered operation cycles is three years. If the UPS  
has been stored for a period exceeding 36 months, contact your factory authorized represnetative  
of guidance in starting the unit.  
Temperature fluctuations should be minimized.  
The optimal storage temperature range is 68 – 77 °F (20 – 25° C).  
A maximum temperature range of 32 – 104 °F (0 – 40 °C) should be observed.  
The optimal relative humidity at the storage location should be between 50 – 60%.  
Humidity must not exceed 90%.  
Avoid locations where UPS may be exposed to corrosive gas.  
Avoid locations with dirt and/or dust.  
TABLE 9.1 - UPS STORAGE/OPERATING ENVIRONMENT STANDARDS  
Item  
Environment standard  
Storage Location  
Indoors  
Minimum storage temperature: 32 °F (0 °C)  
Maximum storage temperature: 104 °F (40 °C)  
Ambient Temperature  
The relative humidity must be between 30 and 90% and without condensation  
due to temperature changes.  
Relative Humidity  
Altitude  
This equipment is rated for installations up to 3240 ft. (1000m) above  
sea level. Consult with the factory to determine the derating factor for  
installations above 3240 ft. (1000m).  
Dust must not exceed normal atmospheric levels and must not include  
conductive particles, silicone or oils.  
Dust  
No flammable and/or explosive gas.  
Hydrogen sulfide (H2S)  
Sulfurous acid gas (SO2)  
Chlorine gas (Cl2)  
Less than or equal to 0.0001 PPM  
Less than or equal to 0.05 PPM  
Less than or equal to 0.002 PPM  
Less than or equal to 0.1 PPM  
Less than or equal to 0.02 PPM  
Flammable Gas  
Ammonia gas (NH3)  
Nitrous acid gas (NO2)  
Nitrous oxides (NOx)  
Ozone (O3)  
Less than or equal to 0.02 PPM  
Less than or equal to 0.002 PPM  
Hydrochloric acid mist (HCl)  
Less than or equal to 0.1 mg/m3  
9.1 Operating Precautions  
Initial startup/comisioning of the UPS should be performed by factory authorized personnel.  
1) The UPS should not be powered up until the entire operation manual has been read.  
2) The voltage of the input power source must be within the rated input voltage range. The  
G8000 Series Installation and Operation Manual  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
input frequency range must be within the rated input frequency range.  
3) The UPS should not be used with a load that has a rated input that is greater than the  
rated output of the UPS.  
4) If using the UPS to provide power to motors that require high starting current or with  
motors that require a long starting time, call Toshiba support for guidance in over sizing  
the UPS for lock rotor current.  
5) DO NOT insert metal objects or combustible materials in the ventilation slots of the UPS.  
6) DO NOT place, hang, or paste any objects on the exterior surfaces of the UPS.  
7) The capacitors in the UPS maintain a residual charge for a while after turning the UPS  
off. The required discharge time for each UPS typeform is provided via a cabinet label  
and a CHARGE LED. Wait for at least the minimum time indicated on the label and  
ensure that the CHARGE LED has gone out before opening the door of the UPS once  
the UPS power has been turned off.  
8) DO NOT attempt to disassemble, modify, or repair the UPS. Call your Toshiba sales  
representative for repair information.  
9) Turn the power on only after installing ALL of the covers.  
10) DO NOT remove any covers of the UPS when power is on.  
11) If the UPS should emit smoke or an unusual odor or sound, turn the power off immediately.  
12) Warning signs should be placed on or near the load as a notification that the load is  
being powered by the UPS.  
13) Additional warnings and notifications shall be posted at the equipment installation  
location as deemed required by Qualified Personnel.  
WARNING  
While operating in the inverter mode, placing the input breaker  
in the “OFF” position will switch the UPS to the battery backup  
mode.  
The output of the UPS will continue uninterrupted to the load. The unit  
must be in the bypass mode at the time that the breaker is placed in  
the “OFF” position for the UPS to shutdown power to the load.  
CAUTION  
After an Emergency Power Off (EPO), DO NOT reset the breaker  
until the UPS internal circuits have been fully discharged.  
The UPS could be damaged if the unit is not fully discharged before  
the breaker is reset.  
G8000 Series Installation and Operation Manual  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9.2 Maintenance Precautions  
All internal maintenance sould be performed by factory authorized personnel.  
1) Turn off, lockout, and tagout ALL power sources before connecting the power wiring to  
the equipment or when performing maintenance.  
2) Hardwire type UPS units are not equipped with an over-current protection device, nor do  
they have an output disconnect for the AC output. A user-installed circuit breaker should  
be provided between the UPS output and the load input.  
3) The maximum ambient operating temperature is 86 °F (30 °C) at 1.0 PF, and 104 °F (40  
°C) at 0.8 PF.  
4) Only factory authorized personnel should service the UPS. Contact Toshiba for the the  
nearest authorized service center.  
5) Battery servicing should be performed by factory authorized personnel only. Contact  
your nearest factory authorized service center for battery replacement.  
Qualified Personnel ONLY!  
Qualified Personnel have the skills and knowledge relating to the construction, installation, operation, and  
maintenance of the electrical equipment and has received safety training on the hazards involved (Refer to  
the latest edition of NFPA 70E for additional safety requirements).  
Qualified Personnel shall:  
1) Have read the entire operation manual.  
2) Be trained and authorized to safely energize, de-energize, ground, lockout and tag  
circuits and equipment, and clear faults in accordance with established safety practices.  
3) Be trained in the proper use and care of protective equipment such as safety shoes,  
rubber gloves, hard hats, safety glasses, face shields, flash clothing, etc., in accordance  
with established safety practices.  
4) Be trained in rendering first aid.  
5) Be knowledgeable of batteries and the required handling and maintenance  
precautions.  
For further information on workplace safety visit www.osha.gov.  
WARNING  
Misuse of equipment could result in injury and equipment damage.  
In no event will Toshiba Corporation be responsible or liable for either  
indirect or consequential damage or injury that may result from the  
misuse of this equipment.  
G8000 Series Installation and Operation Manual  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
DO NOT dispose of the batteries in a fire.  
The batteries may explode.  
DO NOT open or mutilate the batteries.  
Released electrolyte is harmful to the eyes and skin and could also  
be toxic.  
DANGER  
A battery can present a risk of electrical shock and high short  
circuit current.  
9.3 Disposal  
Please contact your local or state environmental agency for details on disposal of electrical components  
and packaging in your particular area.  
It is illegal to dump lead-acid batteries in landfills or dispose of them improperly.  
Please help protect the Earth by contacting the environmental protection agencies in your area, the  
battery manufacturer, or call Toshiba toll-free at (877) 867-8773 for more information about recycling  
batteries.  
G8000 Series Installation and Operation Manual  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10 Installation  
WARNING  
Keep the SPECIFIED CLEARANCE around the UPS.  
Inadequate space around the UPS makes it difficult to perform  
maintenance/inspections, lead to insufficient ventilation, and/or will  
cause malfunctions.  
See Figure 10.1 - UPS Clearance  
DO NOT tilt the UPS more than 10° from upright position.  
Tilting the UPS more than 10° may cause crushing, trapping or other  
personal injuries.  
Install anchor bolts to secure the UPS to the installation floor.  
The UPS may fall during an earthquake if the anchor bolts are not  
installed and secured.  
DO NOT transport, move, store, or place the UPS on its side.  
Forces due to heavy components inside may damage the UPS.  
DO NOT allow the UPS to suffer shock or impact when  
unpacking.  
Tools used to remove packaging materials may cause damage to the  
UPS.  
DO NOT push or pull on the sides of the packaging.or the  
UPS to move it. Always use a crane, forklift, or pallet jack for  
transporting and positioning the UPS.  
Pushing/pulling on the sides of the unit to move it may result in damage  
to the UPS. See Figure 4.1 Exterior Handling label.  
G8000 Series Installation and Operation Manual  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10.1 Unpacking  
Unpack the UPS indoors on a paved floor. The UPS should be as close as possible to its final storage  
location. Overhead traveling cranes should be used to unpack any G8000 Series UPS. If an overhead  
traveling crane is not available, allow enough space for forklift operations to unpack the UPS crate. Then  
remove the crate.  
Points to observe  
Retain all small articles during unpacking and installation.  
Make sure that exterior paint is not scratched and that the UPS cabinet is not damaged.  
DO NOT damage the UPS when using tools to remove packaging materials.  
If provided, DO NOT remove the plastic sheet cover, until installation.  
Do not remove the fan covers until UPS start up. The fan covers should be removed by factory  
authorized personnel. Packing materials should be disposed by the appropriate means.  
Immediately report any abnormalities to Toshiba Customer Support Center or an authorized  
representative.  
10.2 UPS Clearance  
Maintain the indicated clearance during installation. See Figure 10.1. Ensure that the front and top air vents  
are NOT blocked.  
Top 16 in. (400 mm)  
Front  
44 in.  
(1100 mm)  
Back 0 in. (0 mm)  
Side 0 in. (0 mm)  
FIGURE 10.1 - UPS CLEARANCE  
G8000 Series Installation and Operation Manual  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10.3 Anchor Bolts  
Install the anchor bolts to secure the UPS on the floor. See Figure 10.2 for anchor bolt installation detail.  
Use 12mm (1/2”) diameter anchor bolts. There are 16mm (5/8”) diameter holes provided in the UPS base.  
See Figure 10.3 for the hole locations and dimensions for the specified UPS models.  
150/225 kVA  
(See Appendix B)  
Back  
21.7 in.  
(551 mm)  
4 x 0.5 in. - Dia. (12 mm)  
Front  
4 x 5/16 in. (16 mm)  
4 screw holes  
diameter screw holes  
(Side View)  
46.1 in. (1171 mm)  
300 kVA  
(See Appendix B)  
Anchor Bolt  
Back  
25.6 in.  
(650 mm)  
8 x 0.5 in. - Dia. (12 mm)  
FIGURE 10.2  
ANCHOR BOLT INSTALLATION DETAIL  
Front  
22.5 in.  
22.5 in.  
22.5 in.  
(571 mm)  
(571 mm)  
(571 mm)  
80/100/125 kVA  
(See Appendix B)  
500 kVA  
(See Appendix B)  
3.0 in. (76 mm)  
Back  
Back  
21.7 in.  
(551 mm)  
4 x 0.5 in. - Dia. (12 mm)  
Front  
30.0 in.  
(762 mm)  
Input Section  
Output Section  
Front  
29.7 in. (755 mm)  
33.9 in.  
20.0 in.  
22.4 in.  
20.0 in.  
(862 mm)  
(508 mm)  
(568 mm)  
(508 mm)  
12 x 0.5 in. - Dia. (12 mm)  
FIGURE 10.3  
HOLE LOCATIONS/DIMENSIONS  
ON BOTTOM OF UPS  
G8000 Series Installation and Operation Manual  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11 UPS Wiring  
Note: Always consult your local and NEC electrical codes for wiring, cabling, and circuit protection device  
requirements.  
Figure 11.1 illustrates the external wiring of the single-input G8000 UPS. See corresponding section to each  
wiring term.  
• Power cable connection at terminal blocks/buses and external breaker provision for the AC  
input/output, Bypass Input and DC input.  
• Earth ground wire at grounding terminal.  
• Control wire terminal TB1 (battery cabinet and bypass breaker)  
< UPS >  
Contactor + Thyristor  
Bypass  
Contactor  
Input  
AC Input  
Contactor  
3φ3W  
Output  
3φ4W  
Input  
Breaker  
Output  
Breaker  
Inverter  
Inverter  
Contactor  
Rectifier  
Chopper  
Charger  
TB1  
DC input  
Battery  
Breaker  
Ground  
Wire  
< Battery Cabinet >  
FIGURE 11.1 - SINGLE INPUT EXTERNAL WIRING DIAGRAM  
An external maintenance bypass may be installed in parallel with the UPS to allow servicing of the G8000  
while maintaining power to the UPS load. Contact the Toshiba Customer Service for further information.  
G8000 Series Installation and Operation Manual  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 11.2 illustrates the external wiring of the dual-input G8000 UPS. See corresponding section to each  
wiring term.  
• Power cable connection at terminal blocks/buses and external breaker provision for the AC  
input/output, Bypass Input and DC input.  
• Earth ground wire at grounding terminal.  
• Control wire terminal TB1 (battery cabinet and bypass breaker)  
< UPS >  
Bypass  
3φ4W  
Contactor + Thyristor  
Bypass  
Breaker  
Bypass  
Contactor  
Input  
AC Input  
Contactor  
3φ3W  
Output  
3φ4W  
Input  
Breaker  
Output  
Breaker  
Inverter  
Inverter  
Contactor  
Rectifier  
Chopper  
Charger  
TB1  
DC input  
Battery  
Breaker  
Ground  
Wire  
< Battery Cabinet >  
FIGURE 11.2 - DUAL INPUT EXTERNAL WIRING DIAGRAM  
An external maintenance bypass may be installed in parallel with the UPS to allow servicing of the G8000  
while maintaining power to the UPS load. Contact the Toshiba Customer Service for further information.  
G8000 Series Installation and Operation Manual  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11.1 80/100/125 kVA Terminal Blocks and Power Cables  
Note: Always consult your site specific, local, state, and NEC electrical codes for wiring, cabling, and circuit  
protection device requirements.  
The terminal blocks for the 80/100/125 kVA UPS are shown in Figure 11.3.  
Recommended external cable sizes for both 75 °C and 90 °C copper wire for a single battery string are  
listed in Table 11.1–11.2. For two or more battery strings consult with Toshiba Technical Support. Ensure  
that your installation adheres to local and NEC electrical codes.  
Use only copper wires for external cables.  
1
2
3
4
5
6
7
8
9 10 11  
12 13  
Note: Contact the  
factory if using  
more than one  
battery string.  
+
U
V
W
U
V
W
N
U
V
W
N
BATTERY  
AC INPUT  
BYPASS INPUT  
AC OUTPUT  
Cable Capacity of Terminal Blocks 1-11: 2 x #6 AWG to 2/0  
Cable Capacity of Terminal Blocks 12-13: 2 x #6 AWG to 350 kcmil  
FIGURE 11.3 - TERMINAL BLOCKS FOR 80/100/125 KVA UPS  
TABLE 11.1 RECOMMENDED CABLE SIZE & TIGHTENING TORQUE FOR 80 KVA UPS  
Block Number  
Cable Size (Min-Max)2  
75 °C Copper Wire  
Tightening Torque  
90 °C Copper Wire  
#1 – (2) 2/0 AWG  
#1 – (2) 2/0 AWG  
#1 – (2) 2/0 AWG  
#1 – (2) 2/0 AWG  
#1 – (2) 2/0 AWG  
#1 – (2) 2/0 AWG  
(2) #1 – (2 ) 2/0 AWG  
#1 – (2) 2/0 AWG  
#1 – (2) 2/0 AWG  
#1 – (2) 2/0 AWG  
(2) #1 – (2 ) 2/0 AWG  
(2) 2/0 - (2) 3/0 AWG  
(2) 2/0 - (2) 3/0 AWG  
1
2
1/0 – (2) 2/0 AWG  
1/0 – (2) 2/0 AWG  
1/0 – (2) 2/0 AWG  
1/0 – (2) 2/0 AWG  
1/0 – (2) 2/0 AWG  
1/0 – (2) 2/0 AWG  
(2) 1/0 – (2 ) 2/0 AWG  
1/0 – (2) 2/0 AWG  
1/0 – (2) 2/0 AWG  
1/0 – (2) 2/0 AWG  
(2) 1/0 – (2 )2/0 AWG  
(2) 1/0 - (2) 3/0 AWG  
(2) 1/0 - (2) 3/0 AWG  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
325 in.-lb. (36.7 N•m)  
325 in.-lb. (36.7 N•m)  
3
4
5
6
73  
8
9
10  
113  
121,2  
131,2  
1 One battery string. (Consult factory if using more than one battery string.)  
2 Maximum cable size for terminal lugs 1-11: (2) x #6 to #2 AWG; Battery Terminals 12-13: (2) x#6 AWG to 350 kcmil.  
3 Cable sized for neutral current=1.7Xphase current. Size cable appropriate to actual load type: balanced, unbalanced, non-linear.  
G8000 Series Installation and Operation Manual  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 11.2 RECOMMENDED CABLE SIZE & TIGHTENING TORQUE FOR 100 KVA UPS  
Block Number  
Cable Size (Min-Max) 2  
75 °C Copper Wire  
Tightening Torque  
90 °C Copper Wire  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
(2) 2/0 AWG  
1
2
(2) #3 – (2) 2/0 AWG  
(2) #3 – (2) 2/0 AWG  
(2) #3 – (2) 2/0 AWG  
(2) #1 – (2) 2/0 AWG  
(2) #1 – (2) 2/0 AWG  
(2) #1 – (2) 2/0 AWG  
(2) 2/0 AWG  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
325 in.-lb. (36.7 N•m)  
325 in.-lb. (36.7 N•m)  
3
4
5
6
7 3  
8
(2) #1 – (2) 2/0 AWG  
(2) #1 – (2) 2/0 AWG  
(2) #1 – (2) 2/0 AWG  
(2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
(2) 2/0 AWG  
9
10  
11 3  
121,2  
131,2  
(2) 3/0 - (2) 4/0 AWG  
(2) 2/0 - (2) 3/0 AWG  
(2) 3/0 - (2) 4/0 AWG  
(2) 2/0 - (2) 3/0 AWG  
1 One battery string. (Consult factory if using more than one battery string.)  
2 Maximum cable size for terminal lugs 1-11: 2 x 6 to 2/0 AWG; Battery Terminals 12-13: 2 x 6 AWG to 350 kcmil.  
3 Cable sized for neutral current=1.7Xphase current. Size cable appropriate to actual load type: balanced, unbalanced, non-linear.  
TABLE 11.2 RECOMMENDED CABLE SIZE & TIGHTENING TORQUE FOR 125 KVA UPS  
Block Number  
Cable Size (Min-Max) 2  
75 °C Copper Wire  
Tightening Torque  
90 °C Copper Wire  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
(2) 2/0 AWG  
1
2
(2) #3 – (2) 2/0 AWG  
(2) #3 – (2) 2/0 AWG  
(2) #3 – (2) 2/0 AWG  
(2) #3 – (2) 2/0 AWG  
(2) #3 – (2) 2/0 AWG  
(2) #3 – (2) 2/0 AWG  
(2) 2/0 AWG  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
50 in.-lb. (5.6 N•m)  
325 in.-lb. (36.7 N•m)  
325 in.-lb. (36.7 N•m)  
3
4
5
6
7 3  
8
(2) #3 – (2) 2/0 AWG  
(2) #3 – (2) 2/0 AWG  
(2) #3 – (2) 2/0 AWG  
(2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
2/0 – (2) 2/0 AWG  
(2) 2/0 AWG  
9
10  
11 3  
121,2  
131,2  
(2) 3/0 - (2) 4/0 AWG  
(2) 2/0 - (2) 3/0 AWG  
(2) 3/0 - (2) 4/0 AWG  
(2) 2/0 - (2) 3/0 AWG  
1 One battery string. (Consult factory if using more than one battery string.)  
2 Maximum cable size for terminal lugs 1-11: 2 x 6 to 2/0 AWG; Battery Terminals 12-13: 2 x 6 AWG to 350 kcmil.  
3 Cable sized for neutral current=1.7Xphase current. Size cable appropriate to actual load type: balanced, unbalanced, non-linear.  
G8000 Series Installation and Operation Manual  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11.2 150, 225, 300, and 500 kVA Buss Strip Terminals and Power Cables  
Note: Always consult your site specific, local, state, and NEC electrical codes for wiring, cabling, and circuit  
protection device requirements.  
The 150, 225, 300 and 500 kVA UPS units have buss strip power terminals.  
1.75 in.  
(45 mm)  
Figure 11.4 is a typical buss strip for a 150/225 kVA UPS.  
Figure 11.5 shows the arrangement of the terminal buss  
3 in.  
strips for the 150 and 225 kVA UPS units. The terminal  
buss strips are located inside, at the bottom of the UPS.  
The dashed line on terminals 1–13 indicates the side view  
of the bolt holes. Use 1/2 inch bolts to attach the lugs.  
(77 mm)  
0.5 in. Dia.  
(1.27 mm)  
1.97 in.  
(50 mm)  
1.77 in.  
(45 mm)  
Figure 11.6 shows the arrangement of the terminal buss  
strips for the 300 kVA UPS. The buss strips are located  
inside at the top of the unit.  
5.3 in. (135 mm)  
FIGURE 11.4 - TERMINAL BUS DETAIL  
Flywheel Input (+)  
4
1
2
3
5
6
7
8
9
10  
11  
12  
13  
+
(Optional Flywheel  
Input fuse. Flywheel (-)  
connects to Battery (-))  
U
U
V
W
V
W
N
U
V
W
N
AC INPUT  
BYPASS INPUT  
AC OUTPUT  
BATTERY  
Note: Contact the factory if using more than one battery string,  
flywheel, or combination battery and flywheel.  
FIGURE 11.5 - TERMINAL BUSS ARRANGEMENT FOR 150 AND 225 KVA UPS  
(Optional Flywheel Input fuse.  
Flywheel (-) connects to Battery (-))  
Flywheel Input (+)  
Note: Contact the factory if using more than one battery string,  
flywheel, or combination battery and flywheel.  
10  
12  
1
2
3
6
7
8
11  
4
5
+
9
U
V
W
U
V
W
N
U
V
W
AC INPUT  
3-phase 3-wire  
BATTERY  
BYPASS INPUT  
3-phase 4-wire  
AC OUTPUT  
3-phase 4-wire  
FIGURE 11.6 - TERMINAL BUSS ARRANGEMENT FOR 300 KVA UPS  
G8000 Series Installation and Operation Manual  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 11.7 shows the terminal mounting hole arrangement for the terminal buss strips for the 500 kVA  
UPS units.  
Figure 11.8 shows the arrangement of the terminal buss strips for the 500 kVA UPS. The buss strips are  
located inside at the top of the unit. The dashed line on terminals 1–13 indicates the side view of the bolt  
holes. Use 1/2 inch bolts to attach the lugs.  
3-Phase AC Power Lugs  
3-Phase Neutral and  
Battery (DC) Power Lugs  
6 x 0.5625 in. Dia.  
(14.3 mm)  
6 x 0.5625 in. Dia.  
(14.3 mm)  
0.875 in.  
(22 mm)  
0.875 in.  
(22 mm)  
1.75 in.  
1.75 in.  
(44.5 mm)  
(44.5 mm)  
0.875 in.  
(22 mm)  
0.875 in.  
(22 mm)  
0.75 in.  
(19 mm)  
0.75 in.  
(19 mm)  
1.75 in.  
(44.5 mm)  
1.75 in.  
(44.5 mm)  
1.75 in.  
(44.5 mm)  
4 in. (102 mm)  
5.5 in. (140 mm)  
FIGURE 11.7 - TERMINAL BUSS DETAILS FOR 500KVA UPS  
G8000 500KVA - INPUT SECTION  
G8000 500KVA - OUTPUT SECTION  
8
1
2
3
4
5
6
9
10  
11  
12  
13  
14  
+
7
GND  
U
V
W
U
V
W
U
V
W
AC INPUT  
N
N
BYPASS INPUT  
AC OUTPUT  
BATTERY  
FIGURE 11.8 - TERMINAL BUSS ARRANGEMENT FOR 500 KVA UPS  
For UPS’ equipped with buss strip terminals for the A/C INPUT, BYPASS INPUT, A/C OUTPUT and  
BATTERY connections, Toshiba recommends using the compression lugs listed in Table 11.3, or their  
equivalent, for cable terminations to be mounted on the bus strips.  
G8000 Series Installation and Operation Manual  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
See Table 11.5 – Table 11.6 for recommended cable sizes for the 150, 225, 300 and 500 kVA UPS.  
TABLE 11.3 RECOMMENDED CRIMP TYPE COMPRESSION LUGS FOR BUS STRIP TERMINALS  
Wire Size  
Wire  
Strand  
Class  
Recommendation  
Crimp tool Required  
Burndy type Y35 or Y46  
Vendor  
Cat. No.  
Color Key  
Die Index  
1/0  
B
I
B
Burndy  
Ilsco  
Burndy  
YA25  
CRA-1/OL  
YA25-LB  
Pink  
Pink  
Black  
12 / 348  
12 / 348  
13  
2/0  
B
I
B
Burndy  
Ilsco  
Burndy  
YA26  
CRA-2/OL  
YA27-LB  
Black  
Black  
Orange  
13  
13  
14 / 101  
3/0  
B
I
B
Burndy  
Ilsco  
Burndy  
YA-27  
CRB-3/OL  
YA28-LB  
Orange  
Orange  
Purple  
14 / 101  
14 / 101  
15  
4/0  
B
I
B
Burndy  
Ilsco  
Burndy  
YA28  
CRB-4/OL  
YA29-LB  
Purple  
Purple  
Yellow  
15  
15  
16  
300 MCM  
B
I
B
Burndy  
Ilsco  
Burndy  
YA30  
CRA-30OL  
YA32-LB  
White  
White  
Red  
17 / 298  
17 / 298  
18 / 324  
350 MCM  
600 MCM  
B
I
Burndy  
Ilsco  
YA31L  
CRA-350  
Red  
Red  
18  
18  
B
I
Burndy  
Ilsco  
YA36L  
CRA-600  
Green  
Green  
22  
22  
TABLE 11.4 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 150 KVA UNIT  
(USE 75 °C Copper Wire)  
Recommended external cable sizes for both 75 °C and 90 °C copper wire for minimum battery configurations  
are listed in Table 11.4–11.7. For extended runtime battery strings configurations consult with Toshiba  
Technical Support. Ensure that your installation adheres to local and NEC electrical codes.  
G8000 Series Installation and Operation Manual  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 11.4 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 150 KVA UNIT  
(USE 75 °C Copper Wire)  
Block Number  
Cable Size (Min-Max)  
75 °C Copper Wire  
Tightening Torque2  
90 °C Copper Wire  
250 kcmil – (2) #1 AWG  
250 kcmil – (2) #1 AWG  
250 kcmil – (2) #1 AWG  
250 kcmil – (2) #1 AWG  
250 kcmil – (2) #1 AWG  
250 kcmil – (2) #1 AWG  
1
2
300 kcmil – (2) #1 AWG  
300 kcmil – (2) #1 AWG  
300 kcmil – (2) #1 AWG  
300 kcmil – (2) #1 AWG  
300 kcmil – (2) #1 AWG  
300 kcmil – (2) #1 AWG  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
300 in.-lb. (33.9 N•m)  
3
4
5
6
74  
(2) 300 kcmil – (6) #1 AWG (2) 250 kcmil – (6) #1 AWG  
8
300 kcmil – (2) #1 AWG  
300 kcmil – (2) #1 AWG  
300 kcmil – (2) #1 AWG  
250 kcmil – (2) #1 AWG  
250 kcmil – (2) #1 AWG  
250 kcmil – (2) #1 AWG  
9
10  
114  
121  
131  
(2) 300 kcmil – (6) #1 AWG (2) 250 kcmil – (6) #1 AWG  
(2) 300 kcmil– (2) 350 kcmil (2) 250 kcmil – (2) 350 kcmil  
(2) 300 kcmil– (2) 350 kcmil (2) 250 kcmil – (2) 350 kcmil  
Flywheel Input  
(+)3  
(2) AWG 2/0  
(2) AWG 2/0  
1 One battery string. (Consult factory if using more than one battery string.)  
2 Fastener torque specified for: 1/2 in. diameter grade 5 steel bolt.  
3 Per flywheel unit  
4 Cable sized for neutral current=1.7Xphase current. Size cable appropriate to actual load type: balanced, unbalanced, non-linear.  
TABLE 11.5 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 225 KVA UNIT  
(USE 75 °C Copper Wire)  
Block Number  
Cable Size (Min-Max)  
75 °C Copper Wire  
Tightening Torque2  
90 °C Copper Wire  
(2) 2/0– (2) 3/0 AWG  
(2) 2/0– (2) 3/0 AWG  
(2) 2/0– (2) 3/0 AWG  
(2) 3/0– (2) 4/0 AWG  
(2) 3/0– (2) 4/0 AWG  
(2) 3/0– (2) 4/0 AWG  
(4) 3/0 – (4) 4/0 AWG  
(2) 3/0– (2) 4/0 AWG  
(2) 3/0– (2) 4/0 AWG  
(2) 3/0– (2) 4/0 AWG  
(4) 3/0 – (4) 4/0 AWG  
(3) 250 kcmil – (4) 3/0  
(3) 250 kcmil – (4) 3/0  
(2) AWG 2/0  
1
(2) 3/0– (2) 4/0 AWG  
(2) 3/0– (2) 4/0 AWG  
(2) 3/0– (2) 4/0 AWG  
(2) 4/0– (2) 250 kcmil  
(2) 4/0– (2) 250 kcmil  
(2) 4/0– (2) 250 kcmil  
(4) 4/0– (4) 250 kcmil  
(2) 4/0– (2) 250 kcmil  
(2) 4/0– (2) 250 kcmil  
(2) 4/0– (2) 250 kcmil  
(4) 4/0– (4) 250 kcmil  
(4) 4/0 – (4) 250 kcmil  
(4) 4/0 – (4) 250 kcmil  
(2) AWG 2/0  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
300 in.-lb. (33.9 N•m)  
2
3
4
5
6
74  
8
9
10  
114  
121  
131  
Flywheel Input (+)3  
1 One battery string. (Consult factory if using more than one battery string.)  
2 Fastener torque specified for: 1/2 in. diameter grade 5 steel bolt.  
3 Per flywheel unit  
G8000 Series Installation and Operation Manual  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4 Cable sized for neutral current=1.7Xphase current. Size cable appropriate to actual load type: balanced, unbalanced, non-linear.  
TABLE 11.6 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 300 KVA UPS  
Bus Number  
Cable Size (Min-Max)  
Tightening  
Torque2  
75 °C Copper Wire  
90 °C Copper Wire  
(2) 4/0 – (3) 1/0  
(2) 4/0 – (3) 1/0  
(2) 4/0 – (3) 1/0  
1
(2) 250 kcmil – (3) 2/0  
(2) 250 kcmil – (3) 2/0  
(2) 250 kcmil – (3) 2/0  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
2
3
41  
(4) 300 kcmil – (4) 350 kcmil (4) 300 kcmil – (4) 350 kcmil 540 in.-lb. (61 N•m)  
51  
(4) 300 kcmil – (4) 350 kcmil (4) 300 kcmil – (4) 350 kcmil 540 in.-lb. (61 N•m)  
6
(2) 300 kcmil – (3) 2/0  
(2) 300 kcmil – (3) 2/0  
(2) 300 kcmil – (3) 2/0  
(2) 300 kcmil – (3) 2/0  
(2) 300 kcmil – (3) 2/0  
(2) 250 kcmil – (3) 1/0  
(2) 250 kcmil – (3) 1/0  
(2) 250 kcmil – (3) 1/0  
(2) 250 kcmil – (3) 1/0  
(2) 250 kcmil – (3) 1/0  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
7
8
94  
10  
11  
12  
(4) 300 kcmil – (4) 350 kcmil (4) 250 kcmil – (4) 300 kcmil 540 in.-lb. (61 N•m)  
(4) 300 kcmil – (4) 350 kcmil (4) 250 kcmil – (4) 300 kcmil 540 in.-lb. (61 N•m)  
Flywheel Input (+)3  
(2) AWG 2/0  
(2) AWG 2/0  
300 in.-lb. (33.9 N•m)  
1 One battery string. (Consult factory if using more than one battery string.)  
2 Fastener torque specified for: 1/2 in. diameter grade 5 steel bolt.  
3 Per flywheel unit  
4 Cable sized for neutral current=1.7Xphase current. Size cable appropriate to actual load type: balanced, unbalanced, non-linear.  
TABLE 11.7 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 500 KVA UPS  
Bus Number  
Cable Size (Min-Max)  
75 °C Copper Wire 90 °C Copper Wire  
Tightening  
Torque1  
1
2
(3) 250 kcmil – (3) 400 kcmil (3) 4/0 kcmil – (3) 250 kcmil  
(3) 250 kcmil – (3) 400 kcmil (3) 4/0 kcmil – (3) 250 kcmil  
(3) 250 kcmil – (3) 400 kcmil (3) 4/0 kcmil – (3) 250 kcmil  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
540 in.-lb. (61 N•m)  
3
4
(3) 400 kcmil – (3) 500 kcmil (4) 400 kcmil – (4) 500 kcmil 540 in.-lb. (61 N•m)  
(3) 400 kcmil – (3) 500 kcmil (4) 400 kcmil – (4) 500 kcmil 540 in.-lb. (61 N•m)  
(3) 400 kcmil – (3) 500 kcmil (3) 400 kcmil – (3) 500 kcmil 540 in.-lb. (61 N•m)  
(6) 400 kcmil – (6) 500 kcmil (3) 400 kcmil – (3) 500 kcmil 540 in.-lb. (61 N•m)  
5
6
72  
83  
9
1/0  
1/0  
540 in.-lb. (61 N•m)  
(3) 400 kcmil – (3) 500 kcmil (3) 400 kcmil – (3) 500 kcmil 540 in.-lb. (61 N•m)  
(3) 400 kcmil – (3) 500 kcmil (3) 400 kcmil – (3) 500 kcmil 540 in.-lb. (61 N•m)  
(3) 400 kcmil – (3) 500 kcmil (3) 400 kcmil – (3) 500 kcmil 540 in.-lb. (61 N•m)  
(6) 400 kcmil – (6) 500 kcmil (3) 400 kcmil – (3) 500 kcmil 540 in.-lb. (61 N•m)  
(3) 400 kcmil – (3) 500 kcmil (3) 400 kcmil – (3) 500 kcmil 540 in.-lb. (61 N•m)  
(3) 400 kcmil – (3) 500 kcmil (3) 400 kcmil – (3) 500 kcmil 540 in.-lb. (61 N•m)  
10  
11  
122  
13  
14  
1 Fastener torque specified for: 1/2 in. diameter grade 5 steel bolt.  
2 Cable sized for neutral current=1.7Xphase current. Size cable appropriate to actual load type: balanced, unbalanced, non-linear.  
3 Ground cables  
G8000 Series Installation and Operation Manual  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11.3 UPS Power Cable Conduit Landing Plates  
Cable conduit landing plates are provided at the bottom of the 80 kVA and100 kVA UPS, at the top and  
bottom of the 150/225 kVA UPS (Older models of the G8000 150/225 kVA UPS do not come equipped with  
an upper conduit landing plate.), and at the top only of the 300/500kVA. The recommended conduit landing  
arrangements are illustrated in Figure 11.9 thru 11.13.  
The five (5) holes must be punched during installation. The dashed rectangle indicates the UPS opening  
behind the conduit landing plates.  
3.37 in.  
21.85 in.  
AC  
INPUT  
AC OUT-  
PUT  
BYPASS  
BATTERY  
Recommended  
Conduit Placement  
Order in Top Conduit  
Landing Plate  
0.78 in.  
CONTROL  
WIRES  
23.74 in.  
BASE PLATES - DIMENSIONS  
UPS BASE  
BOTTOM ENTRY DIMENSIONS  
5.9 in.  
FRONT OF UPS  
23.73 in.  
5.9 in.  
FIGURE 11.9 - BOTTOM CONDUIT LANDING PLATES FOR 80/100/125 KVA  
G8000 Series Installation and Operation Manual  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.35 in.  
21.85 in.  
17.72 in.  
AC  
INPUT  
AC OUT-  
PUT  
BYPASS  
BATTERY  
CONTROL  
WIRES  
Recommended  
Conduit Placement  
Order in Top Conduit  
Landing Plate  
42.126 in.  
BASE PLATES - DIMENSIONS  
UPS BASE  
BOTTOM ENTRY DIMENSIONS  
5.9 in.  
FRONT OF UPS  
21.5 in.  
4.36 in.  
FIGURE 11.10 - BOTTOM CONDUIT LANDING PLATES 100 KVA (T80S3K10KK6XSNH); 150/225 KVA  
4.74 in.  
CONTROL  
WIRES  
Recommended  
Conduit Placement  
Order in Top Conduit  
Landing Plate  
BATTERY  
TOP ENTRY DIMENSIONS  
AC OUT-  
PUT  
BYPASS  
0.7 in.  
4.36 in.  
FRONT OF UPS  
AC  
INPUT  
0.7 in.  
FIGURE 11.11 - TOP ACCESS CONDUIT LANDING PLATE (150 AND 225 KVA ONLY)  
G8000 Series Installation and Operation Manual  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 11.12 shows the four (4) cable landing plates provided at the top of the 300 kVA UPS. Seven (7)  
holes must be punched during installation. The dashed rectangle indicates the UPS opening behind the  
conduit landing plates.  
3.93 in.  
3.15 in.  
21.26 in.  
37.4 in.  
GROUND  
WIRE  
CONTROL  
WIRES  
AC  
INPUT  
AC OUT-  
PUT  
BATTERY  
BATTERY  
BYPASS  
0.76 in.  
Recommended  
56.70 in.  
CONDUIT LANDING PLATES - DIMENSIONS  
FIGURE 11.12 - TOP ACCESS CONDUIT LANDING PLATES (300 KVA)  
Conduit Placement  
Order in Top Conduit  
Landing Plates  
Figure 11.13 shows the three (3) conduit landing plates provided at the top of the 500 kVA UPS. The  
dashed rectangle indicates the UPS opening behind the conduit landing plates.  
Ensure that your installation adheres to local and NEC electrical codes.  
CABLE ENTRY PLATE  
(AC INPUT, BYPASS INPUT)  
28.0” X 6.3” (711 MM X 161 MM)  
CABLE ENTRY PLATE  
AC OUTPUT, DC INPUT  
28.0” X 6.3” (711 MM X 161 MM)  
CABLE ENTRY PLATE  
(CONTROL)  
28.0” X 6.3” (711 MM X 161 MM)  
FIGURE 11.13 - TOP CONDUIT LANDING PLATES FOR THE 500 KVA UPS  
G8000 Series Installation and Operation Manual  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11.4 External Breakers  
The G8000 UPS units are not equipped with circuit breakers. Qualified personnel should provide the  
external breakers for the AC input/output, bypass input and DC input.  
See Figure 11.1 – External Wiring Diagram, for the circuit position of the breakers.  
Table 11.7 shows the G8000 UPS minimum external breaker rating for each capacity. The Bypass, AC  
Input, and AC Output require 3-pole breakers.  
TABLE 11.7 UPS MINIMUM DEVICE RATINGS  
CapaCity  
Rated  
Output  
input BReakeR  
Rating  
Output BReakeR  
Rating  
dC input  
BReakeR Rating  
80 kVA  
480 V/277 V  
480 V/277 V  
480 V/277 V  
480 V/277 V  
480 V/277 V  
480 V/277 V  
480 V/277 V  
480 V – 150 A  
480 V – 200 A  
480 V – 200 A  
480 V – 300 A  
480 V – 400 A  
480 V – 600 A  
480 V – 800 A  
480 V – 125 A  
480 V – 150 A  
480 V – 200 A  
480 V – 250 A  
480 V – 350 A  
480 V – 500 A  
480 V – 800 A  
500 VDC – 300A  
500 VDC – 350A  
500 VDC – 400A  
500 VDC – 600A  
500 VDC – 900A  
500 VDC – 1200A  
600 VDC – 1200A  
100 kVA  
125 kVA  
150 kVA  
225 kVA  
300 kVA  
500 kVA  
11.5 Grounding Wire  
WARNING  
Be sure to ground the UPS as specified.  
Using the UPS without a proper ground will deteriorate the insulation,  
cause leakage of currents and electric shock.The resistance to ground  
should be less than or equal to 10 ohms.  
The 80/100/150/225kVA earth grounding bus’ are located inside, at the bottom-front of the unit.  
The 300 kVA earth grounding bus is located inside, at the top-left of the unit.  
The 500 kVA earth grounding bus is located inside, at the bottom front of the units.  
Use a AWG 2 (or 38 mm2) or larger cable for the grounding wire. Run the grounding wire through the  
opening at the bottom, or through a hole in the top conduit landing plate (if available). See Figure 11.12.  
Connect either the top or bottom earth ground bus, but not both, to the grounding wire.  
The ground wire must have a crimp terminal with a 1/2 in. (12 mm) diameter bolt hole. The ground bus has  
33/64 in. (13 mm) bolt hole. The connect the crimp terminal and ground bus together using a 7/16 in. (10  
mm) diameter bolt.  
G8000 Series Installation and Operation Manual  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G8000 - 80/100 kVA  
G8000 - 300 kVA  
Facility earth ground.  
Ground wire routing through  
top conduit landing plate.  
Through conduit landing  
plate on top (recom-  
mended)  
10 mm or  
7/16 in. Bolt  
Ground bus  
10 mm or  
7/16 in. Bolt  
12 mm or 1/2 in.  
Terminal  
Note: Use either the top or  
the bottom grounding point,  
but not both. Doing so may  
degrade the performance of  
the unit.  
Ground bus  
AWG 2  
(38 mm2)  
ground  
wire  
Feed-through opening  
To facility  
earth ground  
Alternate ground  
wire location  
G8000 - 150/225 kVA  
Facility earth ground.  
Alternate ground wire routing  
through top conduit landing  
plate.  
Note: Use either the top  
or the bottom access for  
the ground wire to connect  
to the ground buss, but  
use only one ground wire.  
Ground bus  
10 mm or  
7/16 in. Bolt  
12 mm or 1/2 in.  
Terminal  
AWG 2 (38 mm2)  
ground wire  
Feed-through opening  
To facility  
earth ground  
G8000 - 500 kVA  
Ground  
bus  
10 mm or  
7/16 in. Bolt  
12 mm or 1/2 in.  
Terminal  
AWG 1/0 (50 mm2)  
ground wire  
FIGURE 11.14 - EARTH GROUND WIRE CONNECTIONS  
G8000 Series Installation and Operation Manual  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11.6 Control Wires  
The control wires terminal layouts at TB1 (terminal bus 1) are shown below in Table 11.8.  
TABLE 11.8 EXTERNAL CONNECTIONS  
No.  
1
I/O  
Output  
Output  
Output  
Output  
Output  
Input  
Signal Name  
Operation  
Low Battery  
Closed at Low Battery  
2
Backup Operation  
Fault  
Closed during Backup Operation  
Closed if Faults present  
3
4
Inverter Supply  
Warning  
Closed during Normal Operation  
Closed if Warnings present  
5
6
P24  
}
}
7
Input  
Remote Run  
P24  
Close to run UPS  
8
Input  
9
Input  
Remote Stop  
Bypass Supply  
Output Signal Ground  
P24  
Close to stop UPS  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
Output  
Output  
Input  
Close during Bypass Operation  
(Ground for pin #1 – 5 & #10)  
Battery’s  
}
}
}
}
Input  
Battery Overheat  
Overheat B-contact  
Output  
Output  
Output  
Output  
Output  
Output  
Bypass Breaker  
52C Trip Signal  
72B Trip Signal  
72B Aux. Contact  
Shunt Trip Signal by EPO  
Battery Breaker shunt trip  
by EPO or Battery shutdown  
Battery breaker’s  
Auxiliary A-contact  
Output  
Output  
External EPO  
External EPO  
Ext EPO (Customer) N.O. Contacts  
Ext EPO (Customer) N.O. Contacts  
}
Note: All control wiring should be #18 AWG (0.823 mm2) or larger.  
G8000 Series Installation and Operation Manual  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The UPS battery cabinet and bypass breaker should be wired as shown below in Figure 11.15.  
Power Source  
Jumper wire if battery  
OH is not applied  
TC  
Bypass Breaker  
To Bypass  
Input  
10  
11  
12  
13  
Power Source  
for trip coil  
14  
15  
16  
17  
18  
19  
20  
21  
22  
Overheat  
B-Contact  
To DC  
Input  
Auxillary A-  
contact  
TB1  
UPS Cabinet  
Battery Cabinet  
Ext. EPO (Customer) N.O. Contacts  
FIGURE 11.15 - CONNECTION BETWEEN UPS, BATTERY CABINET & BYPASS BREAKER  
11.7 Grounding Configuration  
This section describes the grounding configuration to be used with various AC service entrance configurations.  
Inadequate grounding will cause problems at start-up. Connections for the ground line and the neutral line  
must be made appropriately according to the system configuration.  
11.7.1 Recommended configuration (for 4 wire input with Input Neutral  
grounded)  
Figure 11.16 shows recommended grounding configuration when the input neutral is grounded.  
The neutral line at the input source is usually grounded. The neutral terminal in the UPS cabinet should be  
disconnected from the ground bus. The neutral connection for the UPS bypass input should be grounded.  
G8000 Series Installation and Operation Manual  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Input Source  
< UPS Cabinet >  
3φ  
3φ  
N
N
3φ  
3φ  
N
3φ  
3φ  
To the  
Load  
N
G
G
G
G
Remove  
Jumper Cable  
FIGURE 11.16 - GROUNDING CONFIGURATION WITH INPUT NEUTRAL GROUNDED  
A 2 AWG (or 38 mm2) jumper cable is provided between the neutral terminal and ground bus in the UPS  
cabinet. The qualified personnel should remove the jumper cable in this configuration. The jumper cable  
location is illustrated below.  
80-225 kVA  
500 kVA  
Neutral  
Terminals  
Ground  
Bus  
Ground  
Bus  
Neutral  
Terminal  
Ground  
Bus  
Remove  
Jumper  
Cable  
300 kVA  
Remove  
Jumper  
Cable  
Neutral  
Terminal  
Ground  
Bus  
Remove  
Jumper  
Cable  
FIGURE 11.17 - JUMPER CABLE BETWEEN THE NEUTRAL TERMINAL & GROUND BUS  
G8000 Series Installation and Operation Manual  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11.7.2 Grounding Configuration (without input neutral)  
When the input source is wye-connected, the neutral line out to the bypass input should be left open. The  
UPS is grounded by connecting the neutral terminal to the ground bus with the internal jumper cable. See  
Figure 11.18.  
The jumper cable should stay in place. See Figure 11.17 for the jumper cable location.  
If a ground fault interrupter is installed, the UPS is likely to trip the interrupter during transferring to/from  
the bypass circuit. It is recommended that the ground fault interrupter be set to a minimum delay of 0.5  
seconds.  
Input Source  
< UPS Cabinet >  
3φ  
3φ  
N
N
3φ  
3φ  
N
3φ  
3φ  
To the  
Load  
N
G
G
G
G
Jumper Cable  
Remains in Place  
FIGURE 11.18 - GROUNDING CONFIGURATION WITHOUT INPUT NEUTRAL  
11.7.3 Recommended Configuration (for delta-input)  
If the input source is a delta-connection (3-phase 3-wire) without ground, the neutral terminal in the UPS  
cabinet must be connected to the ground bus with the internal jumper cable as shown in Figure 11.19.  
The jumper cable should stay in place. See Figure 11.17 for the jumper cable location.  
Input Source  
< UPS Cabinet >  
3φ  
3φ  
N
3φ  
3φ  
N
3φ  
3φ  
To the  
Load  
N
G
G
G
G
Jumper Cable  
Remains in Place  
FIGURE 11.19 - GROUNDING CONFIGURATION FOR NON-GROUNDED DELTA-INPUT  
G8000 Series Installation and Operation Manual  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11.7.4 Grounding Configuration (with corner-grounded delta-input)  
If one phase of delta-input source is grounded (B-phase for example), the ground bus in the UPS cabinet  
should NOT be connected to the neutral terminal of UPS output.  
The jumper cable should be removed see Figure 11.17 for the jumper cable location.  
During normal operation the UPS output is floating relative to the ground. An isolation transformer is  
recommended at output distribution as shown in Figure 11.20.  
Input Source  
< UPS Cabinet >  
Output Distribution  
3φ  
3φ  
N
3φ  
3φ  
Bφ  
N
3φ  
3φ  
3φ  
To the  
Load  
N
G
G
G
G
Remove  
Jumper Cable  
FIGURE 11.20 - GROUNDING CONFIGURATION WITH CORNER-GROUNDED DELTA-INPUT.  
G8000 Series Installation and Operation Manual  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12 UPS Specifications  
12.1 Specification Table  
G8000 Specifications  
T80S3K08  
KK6XSxx  
T80S3K10 T80S3K12 T80S3K15 T80S3K22 T80S3K30  
T80S3K50  
KK6XSxx  
Model Number  
KK6XSxx  
KK6XSxx  
KK6Xxx  
KK6XSxx KK6XSxx  
Rated Output  
80 kVA /  
80 kW  
100 kVA /  
100 kW  
125 kVA /  
100 kW  
150 kVA /  
150 kW  
225 kVA /  
225 kW  
300 kVA /  
300 kW  
500 kVA /  
450 kW  
Input  
Capacity  
Voltage  
480 VAC (+10% to -15%)  
60 Hz (+/-5%)  
Frequency  
Configuration  
3 Phase; 3 Wire + GND  
Input kVA  
Normal (Charging)  
89 kVA  
(100 kVA)  
111 kVA  
(122 kVA)  
112 kVA  
(123 kVA)  
163 kVA  
(174 kVA)  
247 kVA  
(258 kVA)  
329 kVA  
(340 kVA)  
484 kVA  
(505 kVA)  
Power Factor  
> 0.99 PF Lagging  
EEPROM Upgrade  
Walk-in Function  
Maximum Input  
Current  
107 A  
(120 A)  
134 A  
(147 A)  
135 A  
(148 A)  
196 A  
(209 A)  
297 A  
(311 A)  
396 A  
(409 A)  
582 A  
(608 A)  
Normal (Charging)  
Reflected THD  
< 5% @ 100% Load  
< 6% @ 25% Load  
Configuration  
Voltage  
3-Phase; 4-Wire + Gnd  
480/277V (±10%)  
Bypass  
Battery  
Frequency  
60 Hz (+/-5%)  
Bypass Overload  
Capacity  
1000% for 1 Cycle, 500% for 2 Cycle  
Number of Cells  
Type  
180  
240  
Lead Acid (Contact factory for alternative options)  
DC Nominal  
DC Minimum  
Float Charge  
360V  
480V  
408V  
540V  
288V  
405V  
Ripple Current  
AC Ripple on DC Bus: < 0.2% of DC Voltage  
(without batteries)  
Back-up Time  
Application Specific  
Max DC Charging  
Current  
30 A  
30 A  
30 A  
30 A  
30 A  
30 A  
45 A  
Max Discharge  
292 A  
359 A  
365 A  
533 A  
805 A  
1073 A  
1193 A  
Battery Capacity  
Required for Full  
Load Output  
88 kWB  
108 kWB  
110 kWB  
160 kWB  
242 kWB  
323 kWB  
478 kWB  
G8000 Series Installation and Operation Manual  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G8000 Specifications  
T80S3K08  
KK6XSxx  
T80S3K10 T80S3K12 T80S3K15 T80S3K22 T80S3K30  
T80S3K50  
KK6XSxx  
Model Number  
KK6XSxx  
KK6XSxx  
KK6Xxx  
KK6XSxx KK6XSxx  
Voltage  
480Y/277V  
Output  
Configuration  
3-Phase; 4-Wire + Gnd  
Voltage  
Regulation  
±1% for 0-100%Balanced and Unbalanced Loads  
±2% for  
0-100%  
Balanced  
and Unbal-  
anced Loads  
Voltage Adjust-  
ment Range  
±5% (in increments of 1V)  
Voltage  
±3% for 100% Linear Loads ±5% for 100% Non-Linear Loads  
Unbalance  
Crest Factor  
2
Transient Voltage  
Response  
±2% Max with a 100% Step Loads (without utilizing batteries)  
±1.5% Max with Loss/Return AC input  
±2% Max when load transfers To/From Bypass  
Transient  
<50 ms  
Recovery Time  
Frequency  
60 Hz  
Frequency Syn-  
chronous Range  
±0.5 Hz, ±1 Hz, + 1.5Hz (Selectable)  
Frequency Slew  
Rate  
1 Hz/Sec  
Frequency Regu-  
lation  
± 0.01% in free running mode  
Current  
96 A  
120 A  
150 A  
180 A  
271 A  
361 A  
601 A  
Power Factor 1.0 PF Lag: 32 - 86 °F (0  
- 30 °C)  
0.8 PF Lag:  
32 - 104 °F  
(0 - 40 °C)  
1.0 PF Lag: 32 - 86 °F (0 - 30 °C)  
0.8 PF Lag: 86 - 104 °F (30 - 40 °C)  
0.9 PF  
Lag  
32 - 104 °F  
(0 - 40 °C)  
0.8 PF Lag: 86 - 104 °F  
(30 - 40 °C)  
Overload  
Capacity  
125% for 10 Minutes,  
150% for 60 Seconds  
110% for  
5 Minutes,  
120% for  
125% for 10 Minutes, 150% for 60 Seconds  
60 Seconds  
Voltage THD  
<3% Max with 100% Linear Load / 5% Max with 100% Non-Linear Load  
65 kA (with optional fuse)  
Withstanding  
Rating  
MTBF  
Module only - 200,000 Hrs. / 3,000,000 Hrs. in Bypass  
Reliabil-  
ity  
Cooling  
Paint Color  
Weight  
Forced Air  
Environ-  
ment  
Sherwin Williams HHT2-7055, 079 Beige Texture  
1740 lb.  
(789 kg)  
1740 lb.  
(789 kg)  
2467 lb.  
(1119kg)  
2980 lb.  
(1352 kg)  
4575 lb.  
(2075 kg)  
6520 lb.  
(2957 kg)  
Weight (Shipping)  
1790 lb.  
(812 kg)  
1790 lb.  
(812 kg)  
2556 lb.  
(1159 kg)  
3069 lb.  
(1392 kg)  
4725 lb.  
(2143 kg)  
-TBD-  
Floor Loading 210 Lbs/ft²  
(1023 kg/m2)  
210 Lbs/ft²  
(1023 kg/m2)  
203 Lbs/  
ft² (990 kg/  
m2)  
245 Lbs/ft² 240 Lbs/ft²  
247 Lbs/ft²  
(1196 kg/  
m2)  
(1173 kg/ (1204 kg/m²)  
m²)  
G8000 Series Installation and Operation Manual  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G8000 Specifications  
T80S3K08  
KK6XSxx  
T80S3K10 T80S3K12 T80S3K15 T80S3K22 T80S3K30  
T80S3K50  
KK6XSxx  
Model Number  
KK6XSxx  
KK6XSxx  
KK6Xxx  
KK6XSxx KK6XSxx  
Dimension - Width  
36.8 in. (935 mm)  
55.1 in. (1400 mm)  
76.8 in.  
1951 mm)  
101.8 in.  
(2586 mm)  
Environ-  
ment  
(cont.)  
Depth  
Height  
32.5 in. (826 mm)  
31.8 in. (808 mm)  
35.7 in.  
(907 mm)  
37.4 in.  
(945 mm)  
79.2 in. (2012 mm)  
79.4 in.  
79.7 in.  
(2017 mm)  
(2024 mm)  
Cable Access  
Bottom Access  
Top or Bottom Access  
Top Access  
Minimum  
Clearance  
Top: 15.75” (400 mm)  
Front: 43 7/16” (1100 mm)  
37 in.  
(940 mm)  
Back/Left/Right Sides: Zero  
Enclosure  
NEMA 1  
Heat Loss to be  
Removed @ Full  
Load  
28,321  
BTUs/hr  
33,746  
BTUs/hr  
37,281  
BTUs/hr  
38,524  
BTUs/hr  
67,667  
BTUs/hr  
89,011  
BTUs/hr  
110,262  
BTUs/hr  
Audible Noise  
65 dBA @ 1m Typical  
68 dBA @ 1m Typical  
72 dBA @  
1m Typical  
78 dBA @  
1m Typical  
Operating Tem-  
perature  
32˚F to 86˚F (0˚C to 30˚C) for 1.0PF 32˚F to 104˚F (0˚C to 40˚C) for 0.8 PF  
Operating Humid-  
ity  
30% to 90% Non-Condensing  
Operating Altitude  
3200 ft. (1000 m)  
Listings/Standards UL 1778; UL 17025, cUL 22.2, No. 107.1; ANSI C62.41 (IEEE 587 Cat B) NFPA 70; OSHA; ISO  
9001; IEC298 IP20  
Warranty  
3 Years Parts and Labor  
Monitor-  
ing  
Dry Contacts  
Included  
Yes, for input and output signals  
RS232 Port  
Included  
Intelligent Monitor-  
ing (Optional)  
SNMP; Modbus RTU; Modbus TCP; BACNET, METASYS  
Display  
LCD Touch Panel for Local Monitoring, Operation and control  
Included  
Emergency Power  
Off  
EPO  
Input Conv.  
Battery Cct  
Out. Inv.  
6-diode Bridge Rectifier  
IGBT Chopper  
Config-  
uration  
IGBT Converter with PWM  
G8000 Series Installation and Operation Manual  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12.2 Typical Efficiency vs. Load  
UPS  
Efficiency at Percent Full Load*  
25%  
50%  
75%  
100%  
90.6%  
91.0%  
90.2%  
93.3%  
91.9%  
92.8%  
93.3%  
80 kVA  
100 kVA  
125 kVA  
150 kVA  
225 kVA  
300 kVA  
500 kVA  
83.9%  
86.4%  
88.5%  
86.9%  
87.9%  
88.8%  
91.6%  
85.3%  
90.1%  
90.9%  
91.7%  
91.9%  
91.6%  
91.1%  
90.0%  
91.2%  
90.9%  
92.3%  
92.3%  
92.2%  
90.2%  
* Actual efficiency may differ due to manufacturing variations and input power quality.  
G8000 Series Installation and Operation Manual  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13 Operator Interface  
Table 13.1 shows the functions of the operating buttons on the graphic display panel.  
NOTICE  
Press an operating button for at least 0.5 seconds to change UPS modes. Press  
the reset button for at least 5 seconds to reset the UPS.  
The UPS may not respond if the button press is too short.  
TABLE 13.1 BUTTON AND INDICATOR FUNCTIONS (See fig. 13.1 and 13.2)  
#
1
2
3
4
5
6
7
8
9
Name  
Function  
OPERATION LOCK  
Enables/disables the buttons RUN, STOP, UPS, BYPASS, FLOAT/EQUAL, and RESET.  
Stops the UPS. Transfers to bypass power if available.  
Starts the UPS. Transfers the unit from bypass to UPS power.  
Changes recharge mode between float charge and equalize charge.  
Scrolls the LCD screens up.  
STOP BUTTON  
RUN BUTTON  
FLOAT/EQUAL BUTTON  
SCROLL UP BUTTON  
SCROLL DOWN BUTTON  
RESET BUTTON  
UPS BUTTON  
Scrolls the LCD screens down.  
Reset UPS faults and warnings shown on the LCD. (See Section 13.5)  
Transfers from bypass operation to normal operation.  
Transfers from normal operation to bypass operation.  
“ON” during Bypass Supply.  
BYPASS BUTTON  
10 EPO BUTTON  
11 LCD DISPLAY  
Displays the operational, status, and warning/fault messages.  
“FLASHES” during START or STOP sequence “ON” when operating in inverter mode.  
“ON” after DC bus capacitors are fully charged through the converter.  
“ON” with nominal AC input. “FLASHES” with AC input under-voltage (85%).  
“ON” during float charge.  
12 UPS SUPPLY LED  
13 CONVERTER LED  
14 AC INPUT LED  
15 FLOAT CHARGE LED  
16 EQUALIZE CHARGE LED  
17 BATTERY LED  
18 DISCHARGE LED  
19 BYPASS INPUT LED  
20 WARNING LED  
21 FAULT LED  
“ON” during equalize charge or protection charge while battery OH contact open.  
“ON” when battery is connected. (aux-contact on)  
“ON” during battery discharge.  
“ON” with nominal bypass input. “FLASHES” when bypass is under-voltage (85%).  
Normally “OFF”. “ON” when warning displayed on LCD. “FLASHES” when AC input is abnormal.  
Normally “OFF”. “ON” when faults occur.  
22 INVERTER LED  
23 UPS LED  
Lamp “FLASHES” during START or STOP sequence. “ON” when inverter is operating.  
“ON” when the inverter output is connected to the UPS output.  
“ON” with AC output connected to the bypass/inverter sources.  
“ON” when the bypass power supplies the load  
24 AC OUTPUT LED  
25 BYPASS LED  
G8000 Series Installation and Operation Manual  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13.1 Key-Switch and Buttons  
The key-switch and operating buttons on the graphic display panel are shown in Figure 13.1. See the  
sections titled “Key-switch” and “Operating buttons” for each function.  
5
6
1
2
3
4
7
9
8
10  
EPO  
FIGURE 13.1 – GRAPHIC DISPLAY PANEL KEY-SWITCH/OPERATING BUTTONS  
G8000 Series Installation and Operation Manual  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13.2 LCD/LED Indicators  
11  
12  
20  
21  
13  
14  
22  
23  
15  
16  
24  
25  
17  
19  
18  
FIGURE 13.2 – GRAPHIC DISPLAY PANEL LCD/LED INDICATORS  
G8000 Series Installation and Operation Manual  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13.3 LCD Indicators  
The operator can scroll through the following LCD display screens using the scroll buttons.  
TABLE 13.2 - LCD DISPLAY SCREENS  
Name  
Description  
Normal Display  
Displays operational status, operational guidance, and measured  
data.  
Fault Display  
Displays detailed data when a fault occurs.  
Warning Display Displays detailed data when a warning occurs.  
NORMAL DISPLAY  
SCROLL UP  
FAULT DISPLAY  
SCROLL DOWN  
WARNIG DISPLAY  
FIGURE 13.3 - CHANGING SCREENS WITH SCROLL BUTTONS  
G8000 Series Installation and Operation Manual  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13.4 Normal Display  
The Normal Display screen indicates the UPS operational status and provides various screens: an operation  
guidance screens, mode screens and measured data screens. Table 13.3 shows these screens page by  
page and illustrates the UPS Normal Display operational status screens.  
TABLE 13.3 - NORMAL DISPLAY SCREEN EXAMPLES  
OPERATIONAL STATUS SCREENS  
Shows the UPS status at the top and guidance  
message or measured data underneath.  
BYPASS  
Shows a guidance message at start up.  
PRESS ‘RUN’ SWITCH  
Shows the output voltage and current after start up.  
UPS SUPPLY  
AC-VO 480[V]  
AC- I O 50[%]  
Shows the UPS Operation mode.  
OPERATION MODE  
NORMAL OPERATION MODE  
SYNC.  
MEASUREMENT SCREENS  
Output Voltage: Shows the output line-to-line  
output voltage.  
O/P VOLTAGE  
VOLT. 480[V]  
FREQ. 60.0[Hz]  
Output Current: Shows the RMS output current  
(%) for each phase..  
O/P CURRENT (R.M.S.)  
U
V
50[%]  
50[%]  
W 50[%]  
G8000 Series Installation and Operation Manual  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 13.3 - CONTINUED  
MEASUREMENT SCREENS  
Shows the peak output current peak (%) for each phase.  
Peak value of output current  
O/P CURRENT (PEAK)  
U
V
50[%]  
50[%]  
x 100 [%]  
RMS value for rated current x 1.41  
W 50[%]  
Shows the AC Input Voltage (line-to-line) and frequency.  
AC INPUT  
AC I/P-V 480[V]  
FREQ. 60.0[Hz]  
Shows the Bypass Input Voltage (line-to-line voltage) and  
frequency.  
BYPASS INPUT  
BYP I/P-V 480[V]  
FREQ. 60.0[Hz]  
Shows the internal DC bus voltage, battery voltage and  
battery current.  
DC INPUT  
DC-V 632[V]  
BATT-V 400[V]  
BATT- I 0[A]  
The battery current value displayed is negative during  
recharge and positive during discharge.  
Shows the cumulative UPS operation time, the  
cumulative battery backup time and the number of battery  
backup operations.  
MODE COUNT  
UPS  
35[H]  
BATTERY 56[MIN]  
32[TIM]  
The current time is displayed if there are no faults  
recorded, or after the reset button is pressed.  
CLOCK  
Date is displayed in the mm-ddyyy format. The unit does  
not calculate daylight savings time.  
TIME 03-24-06 13:58  
Time is displayed in the 24-hour format (e.g. 1:58 P.M. =  
1358 Hrs.)  
G8000 Series Installation and Operation Manual  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13.5 Fault Display  
The Fault Display screen displays the fault records until they are reset. The Warning Display screen displays  
the warning records until they are reset. The fault records will remain in the memory until the reset button  
is pressed for at least 5 seconds, even after the actual cause of the fault has been resolved. Note that the  
fault records are not deleted when the UPS is turned off.  
If the UPS is RESET while the system is in normal or bypass mode, the fault history is cleared and operation  
continues.  
If the UPS is RESET while the system is on backup mode, the system will power down, re-initialize, and  
restart.  
TABLE 13.4 FAULT & WARNING DISPLAY SCREEN EXAMPLES  
A fault record is shown with time stamp.  
FAULTS & WARNINGS  
An arrow indicates that another record can be  
displayed by pressing the up/down buttons.  
1 FUSE BLOWN  
09-09-06 08:05:30  
↓ANOTHER ITEM  
A warning record is shown with time stamp.  
FAULTS & WARNINGS  
An arrow indicates that another record can be  
displayed by pressing the up/down buttons.  
1 UPS OVERLOAD  
09-09-06 08:05:30  
↓ANOTHER ITEM  
This screen is displayed if there are no  
warnings recorded, or after the reset button is  
FAULTS & WARNINGS  
pressed.  
NO ALARM  
NO WARNING  
G8000 Series Installation and Operation Manual  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13.6 LCD Scroll  
Scroll through the LCD display screens (see Figure 13.5), in sequence, using the “SCROLL UP” and  
“SCROLL DOWN” buttons on the graphic display panel.  
SCROLL UP - Moves back to the previous screen  
SCROLL DOWN - Moves forward to the next screen  
TABLE 13.5 DISPLAY SCREEN SCROLL SEQUENCE  
UPS SUPPLY  
FAULTS & WARNINGS  
AC-VO 480[V]  
NO FAULT  
AC- I O 50[%]  
NO WARNING  
OPERATION MODE  
CLOCK  
Abbreveations  
AC  
Alternating  
Current  
NORMAL OPERATION  
MODE SYNC.  
TIME 03-24-06 13:58  
DC  
IO  
Direct Current  
Current  
Output  
MODE COUNT  
I/P  
Input  
(The LCD displays a  
diagram of the electrical  
power flow.)  
UPS  
35[H]  
O/P  
VO  
Output  
BATTERY 56[MIN]  
32[TIM]  
Voltage  
Output  
O/P VOLTAGE  
DC INPUT  
DC-V 632[V]  
BATT-V 400[V]  
BATT- I 0[A]  
VOLT. 480[V]  
FREQ. 60.0[HZ]  
O/P CURRENT (R.M.S.)  
BATTERY  
U
V
W
50[%]  
50[%]  
50[%]  
BACK-UP RATING 10[MIN]  
DISCHARGING 15[MIN]  
O/P CURRENT (PEAK)  
AC INPUT  
U
V
W
50[%]  
50[%]  
50[%]  
AC I/P-V 480[V]  
FREQ. 60.0[HZ]  
G8000 Series Installation and Operation Manual  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14 Operating the UPS  
This section describes the basic procedures to operate the UPS. Figure 14.1 shows the location and  
functions of the operating switches to operate the UPS.  
WARNING  
If the UPS produces smoke or smells strange, immediately turn  
off all AC and DC input circuit breakers.  
Continued operation may result in fire. Contact Toshiba or Authorized  
representatives.  
DO NOT turn off the control power supply switch (8A) during UPS  
operation.  
This may result in UPS faults.  
EPO Switch  
(Emergency Power Off Switch)  
See Section 14.9  
Control Power Supply Switch  
FIGURE 14.1 - EPO AND CONTROL POWER SUPPLY OPERATING SWITCHES  
G8000 Series Installation and Operation Manual  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14.1 Operation Types  
The operation types are summarized below.  
TABLE 14.1 OPERATION TYPES  
Operation  
Description  
Complete Shutdown  
Turn off the control power supply. Shut down the UPS  
completely.  
Float / Equalize Charge Changing the battery recharge mode between float charge and  
equalize charge.  
Protection Charge  
Automatic recharge mode transition from protection charge to  
float charge.  
Startup  
Starting up and operating the UPS.  
Stop  
Stop the inverter and chopper/charger.  
Switch Power Supply  
Switching power supply source between UPS and Bypass.  
14.2 Pre-operational Check  
CAUTION  
Perform the pre-operational check before operating the UPS.  
Before operating the UPS:  
1. Make sure all covers/panels are in place and secured.  
2. Make sure the temperature in the UPS/Battery room is within specified limits.  
3. Before starting the UPS, check the power source to make sure AC input power is on.  
4. Make sure battery breaker’s auxiliary A-contact is connected to the terminal block TB1.  
G8000 Series Installation and Operation Manual  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14.3 Startup Procedures  
The procedure to start the UPS is shown in Steps 1-5.  
LED Key  
- LED Off  
- LED On  
- LED Flash  
STEP 1  
SYSTEM INITIALIZE  
Turn on the control power supply switch.  
(Figure 14.1) and ensure the operation lock is  
set to OPERATION. (Figure 13.1 - 1)  
UPS  
INVERTER  
CONVERTER  
AC INPUT  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
STEP 2  
BYPASS  
Wait for a few seconds.  
PRESS ‘RUN’ SWITCH  
UPS  
INVERTER  
CONVERTER  
AC INPUT  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
STEP 3  
BYPASS  
Press the “RUN” button for at least 0.5  
seconds.  
UPS STARTING  
WAIT FOR A WHILE  
CONVERTER LED is “ON” and INVERTER  
LED flashes.  
UPS  
AC  
INVERTER  
CONVERTER  
AC INPUT  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
G8000 Series Installation and Operation Manual  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 4-5 continues the procedure to start the UPS.  
LED Key  
- LED Off  
- LED On  
- LED Flash  
BYPASS  
STEP 4  
Turn on the DC Input Breaker (72B) on the  
external battery cabinet.  
MOVE 72B TO ‘ON’ POSITION  
BATTERIES LED is “ON”.  
UPS  
INVERTER  
CONVERTER  
AC INPUT  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
UPS SUPPLY  
STEP 5  
AC - Vo 480 V  
AC - Io 50%  
*Press the “UPS” button for at least 0.5  
seconds. This completes UPS startup  
procedure  
UPS  
BYPASS LED is “OFF”.  
UPS LED is “ON”.  
INVERTER  
CONVERTER  
AC INPUT  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
NOTE  
*If the AC switch does not function, contact  
Toshiba or authorized representatives.  
If the bypass power source is out of  
specification, this operation will be inhibited.  
In order to switch manually, press the “UPS”  
button for 5 seconds or more.  
G8000 Series Installation and Operation Manual  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14.4 Switch Power Supply (UPS to Bypass)  
The procedure to transfer between the UPS supply and the bypass supply is shown in Steps 1-3  
LED Key  
- LED Off  
- LED On  
- LED Flash  
STEP 1  
UPS SUPPLY  
Check AC INPUT LED and BYPASS LED are  
on to make sure power is being delivered to  
the UPS.  
AC - Vo 480 v  
AC - Io 50%  
UPS  
INVERTER  
CONVERTER  
AC INPUT  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
STEP 2  
BYPASS  
Press the “BYPASS” button for at least 0.5  
seconds.  
UPS LED is “OFF”.  
BYPASS LED is “ON”.  
UPS  
INVERTER  
CONVERTER  
AC INPUT  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
STEP 3  
BYPASS  
Please wait until procedure is completed.  
AC - Vo 480 V  
AC - Io 50%  
PRESS ‘UPS’ SWITCH  
UPS  
INVERTER  
CONVERTER  
AC INPUT  
NOTE  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
To change from Bypass to UPS supply, follow  
SWITCH  
BATTERIES  
AC OUTPUT  
the Startup Procedures - STEP 5.  
If the AC switch does not function, contact  
Toshiba or authorized representatives.  
BYPASS  
BYPASS INPUT  
G8000 Series Installation and Operation Manual  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14.5 Stop  
The procedure to stop the UPS is shown in Steps 1-3.  
LED Key  
- LED Off  
- LED On  
- LED Flash  
BYPASS  
STEP 1  
AC - Vo 480 V  
AC - Io 50%  
PRESS ‘UPS’ SWITCH  
Transfer to Bypass supply as described in  
Switch Power Supply.  
UPS LED is “OFF”.  
UPS  
BYPASS LED is “ON”.  
INVERTER  
CONVERTER  
AC INPUT  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
BYPASS  
STEP 2  
Turn off the DC Input Breaker (72B) on  
the external battery cabinet, and, press  
the G8000 “STOP” button for at least 0.5  
seconds.  
MOVE #72B TO ‘OFF’ POSITION  
UPS  
BATTERIES LED is “OFF”.  
INVERTER  
CONVERTER  
AC INPUT  
INVERTER LED flashes then “OFF”.  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
FLOAT CHARGE LED and CONVERTER  
LED are “OFF”.  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
STEP 3  
BYPASS  
Wait until procedure is completed.  
PRESS ‘RUN’ SWITCH  
UPS  
INVERTER  
CONVERTER  
AC INPUT  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
G8000 Series Installation and Operation Manual  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14.6 Complete Shutdown  
The procedure to turn off the control power and shut down the UPS completely is shown in Steps 1-6.  
STEP 1  
BYPASS  
Transfer to Bypass supply as described in  
Switch Power Supply.  
DC-V 0 [V]  
BATT-V 0 [V]  
UPS LED is “OFF”.  
BATT-I 0 [A]  
BYPASS LED is “ON”.  
STEP 2  
Turn off the DC input breaker, and, press the  
“STOP” button for at least 0.5 sec.  
BATTERIES LED is “OFF”.  
INVERTER LED flashes then “OFF”.  
FLOAT CHARGE LED and CONVERTER LED  
are “OFF”.  
STEP 3  
Please wait until procedure is completed.  
STEP 4  
Scroll the LCD screen to see the DC INPUT  
and make sure DC bus voltage is 0V.  
STEP 5  
NOTICE  
*Turn off the control power supply switch (8A).  
Nothing is displayed on the LCD.  
*STEP 5 - This operation is different from  
the instructions displayed on the screen.  
All LED’s are “OFF”.  
Be sure to perform the procedure as  
specified in this manual.  
STEP 6  
Turn off all breakers at AC Input, Bypass Input,  
and AC Output.  
Shutdown is completed and UPS is isolated.  
G8000 Series Installation and Operation Manual  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14.7 Changing Between Float Charge and Equalize Charge  
The procedure to change the recharge mode between float charge and equalize charge is shown in Steps  
1-3.  
See the Note below for an explanation of Float and Equalize charge modes.  
LED Key  
- LED Off  
- LED On  
- LED Flash  
STEP 1  
UPS SUPPLY  
Make sure that the FLOAT CHARGE LED is  
“ON”.  
AC - Vo 480 V  
AC - Io 50%  
UPS  
INVERTER  
CONVERTER  
AC INPUT  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
UPS SUPPLY  
STEP 2  
Press FLOAT/EQUAL button for at least 0.5  
sec.  
AC - Vo 480 V  
AC - Io 50%  
Change completed.  
UPS  
EQUAL CHARGE LED is “ON”.  
FLOAT CHARGE LED is “OFF”  
INVERTER  
CONVERTER  
AC INPUT  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
STEP 3  
Please wait until procedure is completed.  
BYPASS  
BYPASS INPUT  
NOTE  
In equalize charge mode, the battery is  
charged for a programmed period at a  
specified voltage (depending on the battery  
spec), rather than the float charge, in order  
to prevent voltage deviations among battery  
cells. This should be done once every six  
months if possible.  
The G8000 UPS will automatically perform  
the equalize recharge after battery backup  
operation.  
G8000 Series Installation and Operation Manual  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14.8 Changing to Float Charge from Protection Charge (If applicable)  
The manual procedure to change from protection charge to float charge is shown in Step 1-3.This operation  
applies to batteries after they have experienced over temperature condition.  
See the Note below for an explanation of float charge and protection charge.  
LED Key  
- LED Off  
- LED On  
- LED Flash  
STEP 1  
UPS SUPPLY  
Make sure that the EQUAL CHARGE LED is  
“ON”.  
AC - Vo 480 V  
AC - Io 50%  
UPS  
INVERTER  
CONVERTER  
AC INPUT  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
STEP 2  
Make sure that the “BATT FAULT1” warning  
goes away.  
UPS SUPPLY  
AC - Vo 480 V  
AC - Io 50%  
STEP 3  
Press “FLOAT/EQUAL” button for at least 0.5  
seconds.  
UPS  
INVERTER  
CONVERTER  
AC INPUT  
Procedure completed.  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
NOTE  
BYPASS  
BYPASS INPUT  
The battery is normally being charged at float  
charge mode. To prevent thermal runaway of  
the battery, this mode will automatically be  
changed to protection charge when a “BATT  
FAULT1” (Battery over temperature) warning  
occurs.  
In protection charge mode, the battery is  
automatically charged at a voltage about 5%  
lower than float charge.  
If the “BATT FAULT1” warning message goes  
away and a programmed duration is elapsed  
(about 24 hours), this mode will automatically  
be changed back to float charge. Thus, it is not  
usually required to change the recharge mode  
manually back to the float charge.  
G8000 Series Installation and Operation Manual  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14.9 Emergency Power Off (EPO)  
Press the EPO switch for immediate shutdown of all power through the UPS. The signal from the EPO  
is processed as a “hard fault” by the UPS and results in gate-blocks on the transistors and opens all the  
internal contactors.  
To Reset the UPS after triggering the EPO, do the following:  
1. Shut Down the UPS as described in section 14.6.  
2. Restart the UPS as described in section 14.3.  
15 Troubleshooting  
When an error occurs in the UPS, error data is displayed on the LCD screen. This section will describe the  
types of errors, the error messages displayed on the LCD screen and the procedures to correct the errors.  
15.1 Types of Errors  
The following types of errors may occur in the UPS:  
TABLE 15.1 OPERATION TYPES  
Name  
Description  
Fault (Trip)  
The UPS has been tripped and has stopped operating.  
The UPS is in Bypass mode.  
Fault  
Warning-1 (Input Power Failure) Power is supplied from the battery. When the warning is  
corrected, power will automatically be supplied from the  
AC input.  
Warning-2 (Stop and Restart)  
Warning (Operation Control)  
(Guidance)  
The UPS transfers to Bypass supply and the UPS stops  
operating. When the warning is corrected, the UPS will  
automatically be restarted and revert to UPS supply.  
Warning  
An error or a phenomena related to an error occurred.  
Since this problem does not directly affect operation, the  
system switches to synchronized mode.  
An error or indication of an error has occurred, but  
operation was not affected.  
G8000 Series Installation and Operation Manual  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15.2 Faults and Warnings Data Screen  
This screen appears when a trip error is detected. Up to 10 screens of fault data can be displayed. Figure  
15.1 and Table 15.2 show a sample screen and describe the data shown in the screen.  
FAULTS & WARNINGS  
1
2
1 UPS OVERLOAD  
09-09-06 08:05:30  
↓ANOTHER ITEM  
3
4
FIGURE 15.1 - SAMPLE FAULT DATA SCREEN  
TABLE 15.2 - FAULT AND WARNING DATA SCREEN DESCRIPTIONS  
#
1
2
3
Name  
Number  
Message  
Time  
Description  
The number of the message in the order that it was detected (1 - 10).  
(Up to 10 screens of fault data can be displayed.)  
Shows the type of the fault or warning message.  
The date (mm-dd-yy) and time (in 24-hour format) the fault was  
detected.  
Indicates whether there is a fault screen before or after this screen.  
Indicates there is a fault screen before this screen.  
4
Scroll Indicator  
↓ Indicates there is a fault screen after this screen.  
↓ Indicates there are fault screens before and after this screen.  
G8000 Series Installation and Operation Manual  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15.3 LCD Fault & Warning Displays  
When a fault occurs, a screen is shown as in Figure 15.2. When a warning occurs, a screen is shown as in  
Figure 15.3. Select the desired fault or warning data to be displayed using the scroll buttons.  
BYPASS  
FAULT STOP  
FAULTS & WARNINGS  
1 FUSE BLOWN  
09-09-06 08:05:30  
FIGURE 15.2 - FAULT DISPLAY  
UPS SUPPLY  
AC-VO 480[V]  
AC- I O 50[%]  
FAULTS & WARNINGS  
1 UPS OVERLOAD  
09-09-06 08:05:30  
FIGURE 15.3 - WARNING DISPLAY  
G8000 Series Installation and Operation Manual  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15.4 Fault Messages  
Figure 15.4 show the locations for fault detection. Tables 15.3 through 15.7 gives details for the fault and  
warning messages referred to in section “Fault Data Screen.” The “item” code associated with each fault  
or warning message may be used to determine the physical location of the fault or warning by referring to  
Figure 15.4. The UPS unit may be shipped with different protective configurations from the standard shown  
in Figure 15.4, if specified by the customer. See the protective configuration indicated on the single line  
diagram for each UPS.  
47S  
95S  
27S  
59S  
59I  
271  
49  
51I  
45  
Inverter  
52R  
83MC1  
83MC  
Battery  
Chopper  
30U  
26  
76C  
5E  
76  
80PS  
30ST  
48  
71F  
80B1 80B2  
26B  
95C  
59C  
47C  
27C  
83BF  
FIGURE 15.4 - PROTECTIVE DETECTOR LOCATIONS  
TABLE 15.3 - FAULT (TRIP)  
ITEM LCD MESSAGE INDICATION  
DESCRIPTION  
26  
OVER HEAT  
(NO INDICATION)  
STARTUP ERR  
EMG.STOP  
HIGH TEMP IN THE CABINET.  
30ST  
48  
AN ERROR OCCURRED IN THE MAIN CONTROL MICROPROCESSOR (CPU).  
STARTUP WAS NOT COMPLETED WITHIN THE NORMAL TIME FRAME.  
AN EMERGENCY STOP WAS ACTIVATED VIA THE EXTERNAL CONTACT.  
RECTIFIER, DC, OR INVERTER MAIN CIRCUIT FUSE BLOWN.  
DC OVER-CURRENT - EXCESSIVE CURRENT IN DC CIRCUIT.  
BATTERY VOLTAGE IS BELOW CUTOFF VOLTAGE.  
5E  
71F  
76  
FUSE BLOWN  
DC OC  
80B2  
80PS  
BATT. UV  
CONT. PS. ERR  
THE CONTROL POWER SUPPLY VOLTAGE FAILED.  
TABLE 15.4 - WARNING – 1 (CONVERTER STOP/INPUT POWER ERROR)  
ITEM LCD MESSAGE INDICATION  
DESCRIPTION  
AC INPUT UNDERVOLTAGE - AC INPUT VOLTAGE IS TOO LOW.  
AC INPUT PHASE ROTATION ERROR.  
27S  
47S  
59S  
95S  
AC I/P UV  
AC PHASE ERR  
AC I/P OV  
AC INPUT OVERVOLTAGE - AC INPUT VOLTAGE IS TOO HIGH.  
AC INPUT FREQUENCY ERROR.  
I/P FREQ. ERR  
G8000 Series Installation and Operation Manual  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 15.5 - WARNING - 2 (STOP AND RESTART)  
Item LCD Message Indication  
Description  
AC O/P UV  
UNIT FAULT  
DC OV  
AC output voltage is low.  
IGBT Stack Failure.  
27I  
30U  
45  
Over-voltage in DC circuit.  
Output overload  
49  
AC O/P OL  
INV. OC  
Inverter over-current.  
51I  
59I  
76C  
AC O/P OV  
BATT. OC  
AC output voltage is high.  
Over-current in Battery section.  
TABLE 15.6 - WARNING (OPERATION CONTROL)  
Item LCD Message Indication  
Description  
Bypass input voltage is low.  
27C  
47C  
59C  
95C  
BYPASS UV  
BYPASS ERR.  
BYPASS OV  
BYPASS ASY.  
Bypass input phase rotation error.  
Bypass input voltage is high.  
Bypass input frequency error.  
TABLE 15.7 - WARNING (GUIDANCE)  
Item LCD Message Indication  
26B BATT. OVER HEAT  
80B1 BATT. UV (ALM)  
Description  
Battery temperature is too high.  
Battery voltage is near cutoff voltage.  
G8000 Series Installation and Operation Manual  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15.5 LCD Scroll (w/ faults or warnings)  
This section describes how to scroll through the LCD screens when a fault has occurred (when Fault Data  
screens exist).  
Figure 15.5 shows the locations of the buttons to scroll the LCD screens. See Table 15.8 for details of the  
scroll buttons and how they are used for screen scrolling.  
5
6
7
FIGURE 15.5 - POSITION OF SCROLL AND RESET BUTTONS  
TABLE 15.8 - BUTTON FUNCTIONS  
# Name  
Function  
5
SCROLL UP  
Scrolls to the previous screen.  
6
SCROLL DOWN  
RESET  
Scrolls to the following screen.  
Resets the UPS faults and warnings shown on the LCD and deletes fault history data stored in  
memory.  
7
G8000 Series Installation and Operation Manual  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15.6 Restoring UPS Operation  
WARNING  
Contact Toshiba in the event of malfunction or fault.  
This UPS should be repaired only by factory authorized personnel.  
Servicing by untrained personnel may extend the fault or result in  
electric shock or personal injury.  
Do NOT attempt to modify or relocate the UPS.  
Electric shock, personal injury or fault may result if unauthorized  
personnel attempt to modify or relocate the UPS. Be sure to contact  
toshiba customer service if you need to modify or relocate the UPS.  
Do not open the front and/or rear panels.  
The parts inside carry energy-high current. Touching them may result  
in electric shock, burns or fault.  
The procedure to restore UPS operation is shown in Steps 1-2. The example shows the UPS restored  
after a trip fault occurred on inverter over current with the message “INV. OC.”  
STEP 1  
LED Key  
- LED Off  
- LED On  
Check the LCD screen.  
Also check other fault data screens with  
scroll buttons graphic panel.  
BYPASS  
1 INV. OC  
07-15-07 08:05:30  
STEP 2  
Contact Toshiba Customer Support and  
follow the directions given by the service  
personnel.  
ANOTHER ITEM  
UPS  
INVERTER  
CONVERTER  
AC INPUT  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
G8000 Series Installation and Operation Manual  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16 Periodic Maintenance/Parts Replacement  
The G8000 is designed to provide long-term trouble-free power conditioning and backup. Optimum  
performance can be best maintained by regular, periodic, preventive maintenance.  
16.1 Scheduled Maintenance  
The G8000 UPS should have scheduled maintenance performed on it annually by a factory-authorized  
service provider. The preventive maintenance should include at minimum:  
Clean UPS exterior  
Clean UPS interior  
Verify power supply voltages  
Check for loose/overheated connections  
Scan error log and correct potential UPS-related issues  
16.2 Parts Replacement  
The following list shows the recommended intervals for periodic replacement of certain UPS parts.  
Aluminum electrolytic capacitors: Replace once every 7-10 years.  
Fuses: Replace once every 7-10 years  
Cooling fan: Replace once every 7-10 years  
Batteries (If applicable): See the Backup Battery Cabinet manual for specific test, maintenance and  
replacement instructions.  
G8000 Series Installation and Operation Manual  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G8000 Series Installation and Operation Manual  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A - Installation Planning Guides  
80kVA IPG  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 80kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K08KK6XSxx)  
General Mechanical Information  
Dimensions  
(W x D x H)  
Inches  
Floor  
Approximate Full-Load  
Heat Rejection  
Btu/Hr  
Mechanical Clearance (Inches)from UPS  
for Ventilation and Maintenance Access  
Weight  
Lbs.  
Loading  
Lbs./ft. 2  
Top  
Front  
Bottom  
Sides  
Back  
36.8” x 32.5” x 79.2” 1,740  
210  
28,321  
15.75”  
43.5”  
0”  
0”  
0”  
Primary AC Input (480V 3-Phase / 3-Wire)  
Maximum Input Power Demand  
Normal Mode (Recharge Mode)  
Suggested External  
Overcurrent Protection  
Amps  
External Feeder Wire Size: Min. – Max. Per Phase  
kVA  
PF  
Amps  
AWG or kcmil at 75º C Temp. Rating  
89(100)  
>0.99  
107 (120)  
150 A  
1/0 – (2) x 2/0  
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)  
Maximum Input Power  
Demand  
Suggested External  
External Feeder Wire Size:  
Overcurrent Protection  
Min. – Max. Per Phase // Min. – Max. for Neutral  
kVA  
PF  
Amps  
Amps  
AWG or kcmil at 75º C Temp. Rating  
80  
1.0  
96  
125 AT  
1/0 – (2) x 2/0 // (2) x 1/0 – (2) x 2/0  
DC Backup Input (Battery - 360VDC Nom./Flywheel 550VDC Nom.)  
DC Capacity for Full Maximum Discharge  
Suggested External  
Overcurrent Protection*  
Amps  
External Feeder Wire Size:  
Min. – Max.  
Backup System  
Load Output  
at Full Load Output  
kWB  
Amps DC  
AWG or kcmil at 75º C Temp. Rating  
Battery  
88  
88  
292  
158  
300 A  
175 A  
(2) x 1/0 – (2) x 3/0  
2/0  
Flywheel  
* If required. Most Battery and Flywheel Cabinets are equipped with built-in breakers.  
AC Output (480/277V 3-Phase / 4-Wire)  
Suggested External  
Overcurrent Protection  
External Feeder Wire Size:  
Min. – Max. Per Phase // Min. – Max. for Neutral  
Rated Output Power  
kVA  
PF  
Amps  
Amps  
AWG or kcmil at 75º C Temp. Rating  
80  
1.0  
96  
125 A  
1/0 – (2) x 2/0 // (2) x 1/0 – (2) x 2/0  
Important Notes:  
12. Cable sizing calculations based on the following assumptions:  
1. CABLE ACCESS – Bottom only.  
-
Minimum size is smallest size based on ampacity at 30 °C.  
-
Maximum size cable is based on cable bend radius  
limitations at the UPS terminals.  
2. Maximum Current required at Primary AC Input based on full  
load output and maximum battery charging current.  
-
-
Neutral sized for 2X phase current.  
3. Output load conductors are to be installed in separate  
conduit from input conductors.  
Not more than 3 current-carrying conductors installed in  
conduit in ambient temperature of 30 °C.  
Temperature rating of copper conductors/terminals: 75 °C.  
Reference: 2005 NEC Handbook, Table 310.16.  
4. Control wires and power wires are to be installed in separate  
conduits.  
-
-
5. Recommended AC input and output overcurrent protection  
based on continuous full load current per NEC.  
NOTE: Consult latest edition of applicable  
national and local codes for possible  
variations.  
6. Wiring shall comply with all applicable national and local  
electrical codes.  
7. Grounding conductors to be sized per NEC Article 250-122.  
Neutral conductors to be sized per NEC Article 310.15.  
- Primary AC Input: 3φ, 3-wire + ground.  
13. Ratings of wires and overcurrent devices are suggested  
minimums. Consult with a registered Professional Engineer  
within your local area for proper size selections.  
- Alternate AC Input: 3φ, 4-wire + ground.  
- AC Output: 3φ, 4-wire + ground.  
- DC Input: 2-wire (Positive/Negative) + ground.  
TOSHIBA INTERNATIONAL CORPORATION  
13131 West Little York Road  
Houston, TX 77041  
Telephone: (877) 867-8773  
Fax: (713) 896-5212  
8. Nominal battery voltage based on the use of VRLA type  
batteries (2.0 volts/cell nominal).  
9. Maximum battery discharge current based on lowest  
permissible discharge voltage of 1.67 VPC.  
10. DC wires should be sized to allow not more than a 2-volt  
drop at maximum discharge current.  
Web Site: www.toshiba.com/ind  
11. Weights do not include batteries or other auxiliary equipment  
external to the UPS.  
Rev. 2.2  
G8000 Series Installation and Operation Manual  
Page 1 of 3  
G8000-IPG-80kVA  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 80kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K08KK6XSxx)  
G8000 80KVA OUTLINE DRAWING  
G8000 Series Installation and Operation Manual  
80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 80kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K08KK6XSxx)  
Anchorage pattern:  
Install anchor bolts to secure the UPS to the floor.  
Use 1/2” (12mm) diameter anchor bolts. The UPS base has four pre-drilled 5/8” (16 mm)  
holes provided. See the figure below for dimensions and locations.  
Anchorage Pattern for G8000 80kVA UPS  
Rev. 2.2  
Page 3 of 3  
G8000-IPG-80kVA  
G8000 Series Installation and Operation Manual  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
100kVA IPG  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 100kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K10KK6XSxx)  
General Mechanical Information  
Dimensions  
(W x D x H)  
Inches  
Floor  
Approximate Full-Load  
Heat Rejection  
Btu/Hr  
Mechanical Clearance (Inches)from UPS  
for Ventilation and Maintenance Access  
Weight  
Lbs.  
Loading  
Lbs./ft. 2  
Top  
Front  
Bottom  
Sides  
Back  
36.8” x 32.5” x 79.2” 1,740  
210  
33,746  
15.75”  
43.5”  
0”  
0”  
0”  
Primary AC Input (480V 3-Phase / 3-Wire)  
Maximum Input Power Demand  
Normal Mode (Recharge Mode)  
Suggested External  
Overcurrent Protection  
Amps  
External Feeder Wire Size: Min. – Max. Per Phase  
kVA  
PF  
Amps  
AWG or kcmil at 75º C Temp. Rating  
110 (122)  
>0.99  
134 (147)  
200 AT  
(2) x #3 – (2) x 2/0  
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)  
Maximum Input Power  
Demand  
Suggested External  
External Feeder Wire Size:  
Overcurrent Protection  
Min. – Max. Per Phase // Min. – Max. for Neutral  
kVA  
PF  
Amps  
Amps  
AWG or kcmil at 75º C Temp. Rating  
100  
1.0  
120  
150 AT  
(2) x #3 – (2) x 2/0 // (2) 2/0  
DC Backup Input (Battery - 360VDC Nominal)  
DC Capacity for Full Maximum Discharge  
Suggested External  
Overcurrent Protection*  
Amps  
External Feeder Wire Size:  
Min. – Max.  
Backup System  
Load Output  
at Full Load Output  
kWB  
Amps DC  
AWG or kcmil at 75º C Temp. Rating  
Battery  
108  
359  
350 A  
(2) x 3/0 – (2) x 4/0  
* If required. Most Battery Cabinets are equipped with built-in breakers.  
AC Output (480/277V 3-Phase / 4-Wire)  
Suggested External  
Overcurrent Protection  
External Feeder Wire Size:  
Min. – Max. Per Phase // Min. – Max. for Neutral  
Rated Output Power  
kVA  
PF  
Amps  
Amps  
AWG or kcmil at 75º C Temp. Rating  
100  
1.0  
120  
150 AT  
(2) x #3 – (2) x 2/0 // (2) 2/0  
Important Notes:  
12. Cable sizing calculations based on the following assumptions:  
1. CABLE ACCESS – Bottom only.  
-
Minimum size is smallest size based on ampacity at 30 °C.  
-
Maximum size cable is based on cable bend radius  
limitations at the UPS terminals.  
2. Maximum Current required at Primary AC Input based on full  
load output and maximum battery charging current.  
-
-
Neutral sized for 2X phase current.  
3. Output load conductors are to be installed in separate  
conduit from input conductors.  
Not more than 3 current-carrying conductors installed in  
conduit in ambient temperature of 30 °C.  
Temperature rating of copper conductors/terminals: 75 °C.  
Reference: 2005 NEC Handbook, Table 310.16.  
4. Control wires and power wires are to be installed in separate  
conduits.  
-
-
5. Recommended AC input and output overcurrent protection  
based on continuous full load current per NEC.  
NOTE: Consult latest edition of applicable  
national and local codes for possible  
variations.  
6. Wiring shall comply with all applicable national and local  
electrical codes.  
7. Grounding conductors to be sized per NEC Article 250-122.  
Neutral conductors to be sized per NEC Article 310.15.  
- Primary AC Input: 3φ, 3-wire + ground.  
13. Ratings of wires and overcurrent devices are suggested  
minimums. Consult with a registered Professional Engineer  
within your local area for proper size selections.  
- Alternate AC Input: 3φ, 4-wire + ground.  
- AC Output: 3φ, 4-wire + ground.  
- DC Input: 2-wire (Positive/Negative) + ground.  
TOSHIBA INTERNATIONAL CORPORATION  
13131 West Little York Road  
Houston, TX 77041  
Telephone: (877) 867-8773  
Fax: (713) 896-5212  
8. Nominal battery voltage based on the use of VRLA type  
batteries (2.0 volts/cell nominal).  
9. Maximum battery discharge current based on lowest  
permissible discharge voltage of 1.67 VPC.  
10. DC wires should be sized to allow not more than a 2-volt  
drop at maximum discharge current.  
Web Site: www.toshiba.com/ind  
11. Weights do not include batteries or other auxiliary equipment  
external to the UPS.  
Rev. 2.2  
Page 1 of 3  
G8000-IPG-100kVA  
G8000 Series Installation and Operation Manual  
82  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 100kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K10KK6XSxx)  
G8000 100KVA OUTLINE DRAWING  
Rev. 2.2  
Page 2 of 3  
G8000-IPG-100kVA  
G8000 Series Installation and Operation Manual  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 100kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K10KK6XSxx)  
Anchorage pattern:  
Install anchor bolts to secure the UPS to the floor.  
Use 1/2” (12mm) diameter anchor bolts. The UPS base has four pre-drilled 5/8” (16 mm)  
holes provided. See the figure below for dimensions and locations.  
Anchorage Pattern for G8000 100kVA UPS  
Rev. 2.2  
Page 3 of 3  
G8000-IPG-100kVA  
G8000 Series Installation and Operation Manual  
84  
Download from Www.Somanuals.com. All Manuals Search And Download.  
125kVA IPG  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 125kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K12KK6XS2xx)  
General Mechanical Information  
Dimensions  
(W x D x H)  
Inches  
Floor  
Approximate Full-Load  
Heat Rejection  
Btu/Hr  
Mechanical Clearance (Inches)from UPS  
for Ventilation and Maintenance Access  
Weight  
Lbs.  
Loading  
Lbs./ft. 2  
Top  
Front  
Bottom  
Sides  
Back  
36.8” x 32.5” x 79.2” 1,740  
210  
33,746  
15.75”  
43.5”  
0”  
0”  
0”  
Primary AC Input (480V 3-Phase / 3-Wire)  
Maximum Input Power Demand  
Normal Mode (Recharge Mode)  
Suggested External  
Overcurrent Protection  
Amps  
External Feeder Wire Size: Min. – Max. Per Phase  
kVA  
PF  
Amps  
AWG or kcmil at 75º C Temp. Rating  
112 (123)  
>0.99  
135 (148)  
200 AT  
(2) x #3 – (2) x 2/0  
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)  
Maximum Input Power  
Demand  
Suggested External  
External Feeder Wire Size:  
Overcurrent Protection  
Min. – Max. Per Phase // Min. – Max. for Neutral  
kVA  
PF  
Amps  
Amps  
AWG or kcmil at 75º C Temp. Rating  
125  
0.8  
150  
200 AT  
(2) x #1 – (2) x 2/0 // (2) 2/0  
DC Backup Input (Battery - 360VDC Nominal)  
DC Capacity for Full Maximum Discharge  
Suggested External  
Overcurrent Protection*  
Amps  
External Feeder Wire Size:  
Min. – Max.  
Backup System  
Load Output  
at Full Load Output  
kWB  
Amps DC  
AWG or kcmil at 75º C Temp. Rating  
Battery  
110  
365  
400 A  
(2) x 3/0 – (2) x 4 /0  
* If required. Most Battery Cabinets are equipped with built-in breakers.  
AC Output (480/277V 3-Phase / 4-Wire)  
Suggested External  
Overcurrent Protection  
External Feeder Wire Size:  
Min. – Max. Per Phase // Min. – Max. for Neutral  
Rated Output Power  
kVA  
PF  
Amps  
Amps  
AWG or kcmil at 75º C Temp. Rating  
125  
0.8  
150  
200 AT  
(2) x #1 – (2) x 2/0 // (2) 2/0  
Important Notes:  
12. Cable sizing calculations based on the following assumptions:  
1. CABLE ACCESS – Bottom only.  
-
Minimum size is smallest size based on ampacity at 30 °C.  
-
Maximum size cable is based on cable bend radius  
limitations at the UPS terminals.  
2. Maximum Current required at Primary AC Input based on full  
load output and maximum battery charging current.  
-
-
Neutral sized for 2X phase current.  
3. Output load conductors are to be installed in separate  
conduit from input conductors.  
Not more than 3 current-carrying conductors installed in  
conduit in ambient temperature of 30 °C.  
Temperature rating of copper conductors/terminals: 75 °C.  
Reference: 2005 NEC Handbook, Table 310.16.  
4. Control wires and power wires are to be installed in separate  
conduits.  
-
-
5. Recommended AC input and output overcurrent protection  
based on continuous full load current per NEC.  
NOTE: Consult latest edition of applicable  
national and local codes for possible  
variations.  
6. Wiring shall comply with all applicable national and local  
electrical codes.  
7. Grounding conductors to be sized per NEC Article 250-122.  
Neutral conductors to be sized per NEC Article 310.15.  
- Primary AC Input: 3φ, 3-wire + ground.  
13. Ratings of wires and overcurrent devices are suggested  
minimums. Consult with a registered Professional Engineer  
within your local area for proper size selections.  
- Alternate AC Input: 3φ, 4-wire + ground.  
- AC Output: 3φ, 4-wire + ground.  
- DC Input: 2-wire (Positive/Negative) + ground.  
TOSHIBA INTERNATIONAL CORPORATION  
13131 West Little York Road  
Houston, TX 77041  
Telephone: (877) 867-8773  
Fax: (713) 896-5212  
8. Nominal battery voltage based on the use of VRLA type  
batteries (2.0 volts/cell nominal).  
9. Maximum battery discharge current based on lowest  
permissible discharge voltage of 1.67 VPC.  
10. DC wires should be sized to allow not more than a 2-volt  
drop at maximum discharge current.  
Web Site: www.toshiba.com/ind  
11. Weights do not include batteries or other auxiliary equipment  
external to the UPS.  
Rev. 0  
G8000 Series Installation and Operation Manual  
Page 1 of 3  
G8000-IPG-125kVA 0.8PF  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 125kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K12KK6XS2xx)  
G8000 125KVA OUTLINE DRAWING  
Rev. 0  
Page 2 of 3  
G8000-IPG-125kVA 0.8PF  
G8000 Series Installation and Operation Manual  
86  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 125kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K12KK6XS2xx)  
Anchorage pattern:  
Install anchor bolts to secure the UPS to the floor.  
Use 1/2” (12mm) diameter anchor bolts. The UPS base has four pre-drilled 5/8” (16 mm)  
holes provided. See the figure below for dimensions and locations.  
Anchorage Pattern for G8000 100kVA UPS  
Rev. 0  
Page 3 of 3  
G8000-IPG-125kVA 0.8PF  
G8000 Series Installation and Operation Manual  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
150kVA IPG  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 150kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K15KK6XSxx)  
General Mechanical Information  
Dimensions  
(W x D x H)  
Inches  
Floor  
Approximate Full-Load  
Heat Rejection  
Btu/Hr  
Mechanical Clearance (Inches)from UPS  
for Ventilation and Maintenance Access  
Weight  
Lbs.  
Loading  
Lbs./ft. 2  
Top  
Front  
Bottom  
Sides  
Back  
55.1” x 31.8” x 79.2” 2,467  
203  
38,754  
15.75”  
43.5”  
0”  
0”  
0”  
Primary AC Input (480V 3-Phase / 3-Wire)  
Maximum Input Power Demand  
Normal Mode (Recharge Mode)  
Suggested External  
Overcurrent Protection  
Amps  
External Feeder Wire Size: Min. – Max. Per Phase  
kVA  
PF  
Amps  
AWG or kcmil at 75º C Temp. Rating  
167 (183)  
>0.99  
196 (209)  
300 AT  
300 kcmil - (2) x #1  
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)  
Maximum Input Power  
Demand  
Suggested External  
Overcurrent Protection  
Amps  
External Feeder Wire Size:  
Min. – Max. Per Phase // Min. – Max. for Neutral  
AWG or kcmil at 75º C Temp. Rating  
kVA  
PF  
Amps  
150  
1.0  
180  
250 AT  
300 kcmil - (2) x #1 // (2) x 300 kcmil - (4) x #1  
DC Backup Input (Battery - 360VDC Nom./Flywheel 550VDC Nom.)  
DC Capacity for Full Maximum Discharge  
Suggested External  
Overcurrent Protection*  
Amps  
External Feeder Wire Size:  
Min. – Max.  
Backup System  
Load Output  
at Full Load Output  
kWB  
Amps DC  
AWG or kcmil at 75º C Temp. Rating  
Battery  
160  
533  
600 A  
(2) x 300 kcmil – (2) x 350 kcmil  
* If required. Most Battery and Flywheel Cabinets are equipped with built-in breakers.  
AC Output (480/277V 3-Phase / 4-Wire)  
Suggested External  
Overcurrent Protection  
Amps  
External Feeder Wire Size:  
Min. – Max. Per Phase // Min. – Max. for Neutral  
Rated Output Power  
kVA  
PF  
Amps  
AWG or kcmil at 75º C Temp. Rating  
150  
1.0  
180  
225 AT  
300 kcmil - (2) x #1 // (2) x 300 kcmil - (4) x #1  
Important Notes:  
12. Cable sizing calculations based on the following assumptions:  
1. CABLE ACCESS – Top and Bottom.  
-
Minimum size is smallest size based on ampacity at 30 °C.  
-
Maximum size cable is based on cable bend radius  
limitations at the UPS terminals.  
2. Maximum Current required at Primary AC Input based on full  
load output and maximum battery charging current.  
-
-
Neutral sized for 2X phase current.  
3. Output load conductors are to be installed in separate  
conduit from input conductors.  
Not more than 3 current-carrying conductors installed in  
conduit in ambient temperature of 30 °C.  
4. Control wires and power wires are to be installed in separate  
conduits.  
-
-
Temperature rating of copper conductors/terminals: 75 °C.  
Reference: 2005 NEC Handbook, Table 310.16.  
5. Recommended AC input and output overcurrent protection  
based on continuous full load current per NEC.  
NOTE: Consult latest edition of applicable  
national and local codes for possible  
variations.  
6. Wiring shall comply with all applicable national and local  
electrical codes.  
7. Grounding conductors to be sized per NEC Article 250-122.  
Neutral conductors to be sized per NEC Article 310.15.  
- Primary AC Input: 3φ, 3-wire + ground.  
13. Ratings of wires and overcurrent devices are suggested  
minimums. Consult with a registered Professional Engineer  
within your local area for proper size selections.  
- Alternate AC Input: 3φ, 4-wire + ground.  
- AC Output: 3φ, 4-wire + ground.  
- DC Input: 2-wire (Positive/Negative) + ground.  
TOSHIBA INTERNATIONAL CORPORATION  
13131 West Little York Road  
Houston, TX 77041  
Telephone: (877) 867-8773  
Fax: (713) 896-5212  
8. Nominal battery voltage based on the use of VRLA type  
batteries (2.0 volts/cell nominal).  
9. Maximum battery discharge current based on lowest  
permissible discharge voltage of 1.67 VPC.  
10. DC wires should be sized to allow not more than a 2-volt  
drop at maximum discharge current.  
Web Site: www.toshiba.com/ind  
11. Weights do not include batteries or other auxiliary  
equipment external to the UPS.  
Rev. 2.2  
Page 1 of 3  
G8000-IPG-150kVA  
G8000 Series Installation and Operation Manual  
88  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 150kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K15KK6XSxx)  
Rev. 2.2  
Page 2 of 3  
G8000-IPG-150kVA  
G8000 Series Installation and Operation Manual  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 150kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K15KK6XSxx)  
Anchorage pattern:  
Install anchor bolts to secure the UPS to the floor.  
Use 1/2” (12mm) diameter anchor bolts. The UPS base has four pre-drilled 5/8” (16 mm)  
holes provided. See the figure below for dimensions and locations.  
Anchorage Pattern for G8000 150kVA UPS  
Rev. 2.2  
Page 3 of 3  
G8000-IPG-150kVA  
G8000 Series Installation and Operation Manual  
90  
Download from Www.Somanuals.com. All Manuals Search And Download.  
225kVA IPG  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 225kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K22KK6XSxx)  
General Mechanical Information  
Dimensions  
(W x D x H)  
Inches  
Floor  
Approximate Full-Load  
Heat Rejection  
Btu/Hr  
Mechanical Clearance (Inches)from UPS  
for Ventilation and Maintenance Access  
Weight  
Lbs.  
Loading  
Lbs./ft. 2  
Top  
Front  
Bottom  
Sides  
Back  
55.1” x 31.8” x. 79.2” 2,980  
245  
67,667  
15.75”  
43.5”  
0”  
0”  
0”  
Primary AC Input (480V 3-Phase / 3-Wire)  
Maximum Input Power Demand  
Normal Mode (Recharge Mode)  
Suggested External  
Overcurrent Protection  
Amps  
External Feeder Wire Size: Min. – Max. Per Phase  
kVA  
PF  
Amps  
AWG or kcmil at 75º C Temp. Rating  
247 (258)  
>0.99  
297 (311)  
400 AT  
(2) x 3/0 – (2) x 4/0  
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)  
Maximum Input Power  
Demand  
Suggested External  
External Feeder Wire Size:  
Overcurrent Protection  
Min. – Max. Per Phase // Min. – Max. for Neutral  
kVA  
PF  
Amps  
Amps  
AWG or kcmil at 75º C Temp. Rating  
225  
1.0  
271  
350 AT  
(2) x 4/0 – (2) x 250 kcmil // (4) x 4/0 – (4) x 250 kcmil  
DC Backup Input (Battery - 360VDC Nom./Flywheel 550VDC Nom.)  
DC Capacity for Full Maximum Discharge  
Suggested External  
Overcurrent Protection*  
Amps  
External Feeder Wire Size:  
Min. – Max.  
Backup System  
Load Output  
at Full Load Output  
kWB  
Amps DC  
AWG or kcmil at 75º C Temp. Rating  
Battery  
242  
805  
900 A  
(4) x 4/0 – (4) x 250 kcmil  
* If required. Most Battery and Flywheel Cabinets are equipped with built-in breakers.  
AC Output (480/277V 3-Phase / 4-Wire)  
Suggested External  
Overcurrent Protection  
External Feeder Wire Size:  
Min. – Max. Per Phase // Min. – Max. for Neutral  
Rated Output Power  
kVA  
PF  
Amps  
Amps  
AWG or kcmil at 75º C Temp. Rating  
225  
1.0  
271  
350 AT  
(2) x 4/0 – (2) x 250 kcmil // (4) x 4/0 – (4) x 250 kcmil  
Important Notes:  
12. Cable sizing calculations based on the following assumptions:  
1. CABLE ACCESS – Top and Bottom.  
-
Minimum size is smallest size based on ampacity at 30 °C.  
-
Maximum size cable is based on cable bend radius  
limitations at the UPS terminals.  
2. Maximum Current required at Primary AC Input based on full  
load output and maximum battery charging current.  
-
-
Neutral sized for 2X phase current.  
3. Output load conductors are to be installed in separate  
conduit from input conductors.  
Not more than 3 current-carrying conductors installed in  
conduit in ambient temperature of 30 °C.  
Temperature rating of copper conductors/terminals: 75 °C.  
Reference: 2005 NEC Handbook, Table 310.16.  
4. Control wires and power wires are to be installed in separate  
conduits.  
-
-
5. Recommended AC input and output overcurrent protection  
based on continuous full load current per NEC.  
NOTE: Consult latest edition of applicable  
national and local codes for possible  
variations.  
6. Wiring shall comply with all applicable national and local  
electrical codes.  
7. Grounding conductors to be sized per NEC Article 250-122.  
Neutral conductors to be sized per NEC Article 310.15.  
- Primary AC Input: 3φ, 3-wire + ground.  
13. Ratings of wires and overcurrent devices are suggested  
minimums. Consult with a registered Professional Engineer  
within your local area for proper size selections.  
- Alternate AC Input: 3φ, 4-wire + ground.  
- AC Output: 3φ, 4-wire + ground.  
- DC Input: 2-wire (Positive/Negative) + ground.  
TOSHIBA INTERNATIONAL CORPORATION  
13131 West Little York Road  
Houston, TX 77041  
Telephone: (877) 867-8773  
Fax: (713) 896-5212  
8. Nominal battery voltage based on the use of VRLA type  
batteries (2.0 volts/cell nominal).  
9. Maximum battery discharge current based on lowest  
permissible discharge voltage of 1.67 VPC.  
10. DC wires should be sized to allow not more than a 2-volt  
drop at maximum discharge current.  
Web Site: www.toshiba.com/ind  
11. Weights do not include batteries or other auxiliary equipment  
external to the UPS.  
Rev. 2.3  
Page 1 of 3  
G8000-IPG-225kVA  
G8000 Series Installation and Operation Manual  
91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 225kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K22KK6XSxx)  
Rev. 2.3  
Page 2 of 3 G8000-IPG-225kVA  
G8000 Series Installation and Operation Manual  
92  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 225kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K22KK6XSxx)  
Anchorage pattern:  
Install anchor bolts to secure the UPS to the floor.  
Use 1/2” (12mm) diameter anchor bolts. The UPS base has four pre-drilled 5/8” (16 mm)  
holes provided. See the figure below for dimensions and locations.  
Anchorage Pattern for G8000 225kVA UPS  
Rev. 2.3  
Page 3 of 3  
G8000-IPG-225kVA  
G8000 Series Installation and Operation Manual  
93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
300kVA IPG  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 300kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K30KK6XSxx)  
General Mechanical Information  
Dimensions  
(W x D x H)  
Inches  
Floor  
Approximate Full-Load  
Heat Rejection  
Btu/Hr  
Mechanical Clearance (Inches)from UPS  
for Ventilation and Maintenance Access  
Weight  
Lbs.  
Loading  
Lbs./ft. 2  
Top  
Front  
Bottom  
Sides  
Back  
76.8” x 35.7” x 79.2” 4,575  
240  
89,011  
15.75”  
43.5”  
0”  
0”  
0”  
Primary AC Input (480V 3-Phase / 3-Wire)  
Maximum Input Power Demand  
Normal Mode (Recharge Mode)  
Suggested External  
Overcurrent Protection  
Amps  
External Feeder Wire Size: Min. – Max. Per Phase  
kVA  
PF  
Amps  
AWG or kcmil at 75º C Temp. Rating  
326 (329)  
>0.99  
396 (409)  
600 AT  
(2) 250 kcmil – (3) x 2/0  
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)  
Maximum Input Power  
Demand  
Suggested External  
Overcurrent Protection  
Amps  
External Feeder Wire Size:  
Min. – Max. Per Phase // Min. – Max. for Neutral  
AWG or kcmil at 75º C Temp. Rating  
kVA  
PF  
Amps  
300  
1.0  
361  
500 AT  
(2) 300 kcmil – (3) x 2/0 (2) 300 kcmil // (4) x 300 kcmil – (6) x 2/0  
DC Backup Input (Battery - 360VDC Nom.)  
DC Capacity for Full Maximum Discharge  
Suggested External  
Overcurrent Protection*  
Amps  
External Feeder Wire Size:  
Min. – Max.  
Backup System  
Load Output  
at Full Load Output  
kWB  
Amps DC  
AWG or kcmil at 75º C Temp. Rating  
Battery  
323  
1073  
1200 A  
(4) x 300 kcmil – (4) x 350 kcmil  
* If required. Most Battery Cabinets are equipped with built-in breakers.  
AC Output (480/277V 3-Phase / 4-Wire)  
Suggested External  
Overcurrent Protection  
External Feeder Wire Size:  
Min. – Max. Per Phase // Min. – Max. for Neutral  
AWG or kcmil at 75º C Temp. Rating  
Rated Output Power  
kVA  
PF  
Amps  
Amps  
300  
1.0  
361  
450 AT  
(2) 300 kcmil – (3) x 2/0 (2) 300 kcmil // (4) x 300 kcmil – (6) x 2/0  
Important Notes:  
12. Cable sizing calculations based on the following assumptions:  
1. CABLE ACCESS – Top only.  
-
Minimum size is smallest size based on ampacity at 30 °C.  
-
Maximum size cable is based on cable bend radius  
limitations at the UPS terminals.  
2. Maximum Current required at Primary AC Input based on full  
load output and maximum battery charging current.  
-
-
Neutral sized for 2X phase current.  
3. Output load conductors are to be installed in separate  
conduit from input conductors.  
Not more than 3 current-carrying conductors installed in  
conduit in ambient temperature of 30 °C.  
Temperature rating of copper conductors/terminals: 75 °C.  
Reference: 2005 NEC Handbook, Table 310.16.  
4. Control wires and power wires are to be installed in separate  
conduits.  
-
-
5. Recommended AC input and output overcurrent protection  
based on continuous full load current per NEC.  
NOTE: Consult latest edition of applicable  
national and local codes for possible  
variations.  
6. Wiring shall comply with all applicable national and local  
electrical codes.  
7. Grounding conductors to be sized per NEC Article 250-122.  
Neutral conductors to be sized per NEC Article 310.15.  
- Primary AC Input: 3φ, 3-wire + ground.  
13. Ratings of wires and overcurrent devices are suggested  
minimums. Consult with a registered Professional Engineer  
within your local area for proper size selections.  
- Alternate AC Input: 3φ, 4-wire + ground.  
- AC Output: 3φ, 4-wire + ground.  
- DC Input: 2-wire (Positive/Negative) + ground.  
TOSHIBA INTERNATIONAL CORPORATION  
13131 West Little York Road  
Houston, TX 77041  
Telephone: (877) 867-8773  
Fax: (713) 896-5212  
8. Nominal battery voltage based on the use of VRLA type  
batteries (2.0 volts/cell nominal).  
9. Maximum battery discharge current based on lowest  
permissible discharge voltage of 1.67 VPC.  
10. DC wires should be sized to allow not more than a 2-volt  
drop at maximum discharge current.  
Web Site: www.toshiba.com/ind  
11. Weights do not include batteries or other auxiliary equipment  
external to the UPS.  
Rev. 2.3  
Page 1 of 3  
G8000-IPG-300kVA  
G8000 Series Installation and Operation Manual  
94  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 300kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K30KK6XSxx)  
G8000 Series Installation and Operation Manual  
95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 300kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K30KK6XSxx)  
Anchorage pattern:  
Install anchor bolts to secure the UPS to the floor.  
Use 1/2” (12mm) diameter anchor bolts. TheUPS base has eight pre-drilled 5/8” (16 mm)  
holes provided. See the figure below for dimensions and locations.  
Anchorage Pattern for G8000 300kVA UPS  
G8000 Series Installation and Operation Manual  
96  
Download from Www.Somanuals.com. All Manuals Search And Download.  
500kVA IPG  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 500kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K50KK6XSxx)  
General Mechanical Information  
Dimensions  
(W x D x H)  
Inches  
Floor  
Approximate Full-Load  
Heat Rejection  
Btu/Hr  
Mechanical Clearance (Inches)from UPS  
for Ventilation and Maintenance Access  
Weight  
Lbs.  
Loading  
Lbs./ft. 2  
Top  
Front  
Bottom  
Sides  
Back  
101.8” x 37.4” x 79.7” 6520  
247  
101,490  
15.75”  
37”  
0”  
0”  
0”  
Primary AC Input (480V 3-Phase / 3-Wire)  
Maximum Input Power Demand  
Normal Mode (Recharge Mode)  
Suggested External  
Overcurrent Protection  
Amps  
External Feeder Wire Size: Min. – Max. Per Phase  
kVA  
PF  
Amps  
AWG or kcmil at 75º C Temp. Rating  
484 (505)  
>0.99  
582 (608)  
800 AT  
(3) x 250 kcmil – (3) x 300 kcmil  
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)  
Maximum Input Power  
Demand  
Suggested External  
Overcurrent Protection  
Amps  
External Feeder Wire Size:  
Min. – Max. Per Phase // Min. – Max. for Neutral  
AWG or kcmil at 75º C Temp. Rating  
kVA  
PF  
Amps  
500  
0.9  
601  
800 AT  
(3) x 400 kcmil – (3) x 500 kcmil // (6) x 400 kcmil – (6) x 500 kcmil  
DC Backup Input (Battery - 480VDC Nom.)  
DC Capacity for Full Maximum Discharge  
Suggested External  
Overcurrent Protection*  
Amps  
External Feeder Wire Size/pole:  
Min. – Max.  
Backup System  
Load Output  
at Full Load Output  
kWB  
Amps DC  
AWG or kcmil at 75º C Temp. Rating  
Battery  
478  
1193  
1200 A  
(3) x 400 kcmil – (3) x 500 kcmil  
* If required. Most Battery and Flywheel Cabinets are equipped with built-in breakers.  
AC Output (480/277V 3-Phase / 4-Wire)  
Suggested External  
Overcurrent Protection  
External Feeder Wire Size:  
Min. – Max. Per Phase // Min. – Max. for Neutral  
AWG or kcmil at 75º C Temp. Rating  
Rated Output Power  
kVA  
PF  
Amps  
Amps  
500  
0.9  
601  
800 AT  
(3) x 400 kcmil – (3) x 500 kcmil // (6) x 400 kcmil – (6) x 500 kcmil  
Important Notes:  
12. Cable sizing calculations based on the following assumptions:  
1. CABLE ACCESS – Top only.  
-
Minimum size is smallest size based on ampacity at 30 °C.  
-
Maximum size cable is based on cable bend radius limitations at  
the UPS terminals.  
2. Maximum Current required at Primary AC Input based on full  
load output and maximum battery charging current.  
-
-
Neutral sized for 1.7X phase current.  
3. Output load conductors are to be installed in separate  
conduit from input conductors.  
Not more than 3 current-carrying conductors installed in conduit  
in ambient temperature of 30 °C.  
Temperature rating of copper conductors/terminals: 75 °C.  
Reference: 2005 NEC Handbook, Table 310.16.  
4. Control wires and power wires are to be installed in separate  
conduits.  
-
-
5. Recommended AC input and output overcurrent protection  
based on continuous full load current per NEC.  
NOTE: Consult latest edition of applicable  
national and local codes for possible  
variations.  
6. Wiring shall comply with all applicable national and local  
electrical codes.  
7. Grounding conductors to be sized per NEC Article 250-122.  
Neutral conductors to be sized per NEC Article 310.15.  
- Primary AC Input: 3φ, 3-wire + ground.  
13. Ratings of wires and overcurrent devices are suggested  
minimums. Consult with a registered Professional Engineer within  
your local area for proper size selections.  
- Alternate AC Input: 3φ, 4-wire + ground.  
- AC Output: 3φ, 4-wire + ground.  
- DC Input: 2-wire (Positive/Negative) + ground.  
TOSHIBA INTERNATIONAL CORPORATION  
13131 West Little York Road  
Houston, TX 77041  
Telephone: (877) 867-8773  
Fax: (713) 896-5212  
8. Nominal battery voltage based on the use of VRLA type  
batteries (2.0 volts/cell nominal).  
9. Maximum battery discharge current based on lowest  
permissible discharge voltage of 1.67 VPC.  
10. DC wires should be sized to allow not more than a 2-volt  
drop at maximum discharge current.  
Web Site: www.toshiba.com/ind  
11. Weights do not include batteries or other auxiliary equipment  
external to the UPS.  
Rev. 0.0  
G8000 Series Installation and Operation Manual  
Page 1 of 3  
G8000-IPG-500kVA  
97  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 500kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K50KK6XSxx)  
G8000 300kVA UPS Cabling Connection Dimensions  
G8000 Series Installation and Operation Manual  
98  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOSHIBA G8000 Series UPS  
Installation Planning Guide for 500kVA UPS  
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K50KK6XSxx)  
Anchorage pattern:  
Install anchor bolts to secure the UPS to the floor.  
Use 1/2” (12mm) diameter anchor bolts. The UPS base has eight pre-drilled 5/8” (16 mm)  
holes provided. See the figure below for dimensions and locations.  
Anchorage Pattern for G8000 500kVA UPS  
Rev. 0.0  
Page 3 of 3  
G8000-IPG-500kVA  
G8000 Series Installation and Operation Manual  
99  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G8000 Series Installation and Operation Manual  
100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B - Outline Drawings  
G8000 Series Installation and Operation Manual  
101  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G8000 Series Installation and Operation Manual  
102  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE B.3 - G8000 300 KVA OUTLINE DRAWING  
G8000 Series Installation and Operation Manual  
103  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G8000 Series Installation and Operation Manual  
104  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix C - 500kVA Input- and Output- Cabinet Joining  
Instructions  
Joining the G8000 500kVA Sections  
1. Remove Shipping Material (Retain Connection Kit Box and Manual).  
2. On a leveled floor bring the two cabinets together. Input cabinet on the left side. See  
FIG. 1. Leave a gap of 0.25”-0.30” between the cabinets. See FIG. 2.  
FIG. 1  
FIG. 2  
3.  
4. On Input cabinet: Open the door, remove back panel (retain hardware). See FIG. 3.  
Insert 1/2-13X1.75” bolt, flat & lock washer assembly (supplied); two in the front and  
two in the back. See FIG. 4 & FIG. 5.  
G8000 Series Installation and Operation Manual  
105  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIG. 3  
FIG. 4  
5. On Output cabinet: Open the door. Insert Neutral bus between the cabinets as  
shown in FIG. 5 & FIG. 6 and connect on corresponding output and input cabinet  
neutral bus using 3/8-16X1.25” bolt, flat, belleville washer and nut (supplied).  
Insert Belleville washer between flat washer and nut.  
6. Insert AC Bus (qty. 3) between the cabinets as shown in FIG. 5 & FIG. 6 and connect  
on corresponding output and input cabinet AC bus using 1/2-13X1.25” bolt, flat, bel-  
leville washer and nut (supplied).  
Insert Belleville washer between flat washer and nut.  
7. Insert DC Bus (qty. 2) between the cabinets as shown in FIG. 5 & FIG. 6 and con-  
nect on corresponding output and input cabinet DC bus using 1/2-13X1.25” bolt, flat,  
belleville washer and nut (supplied).  
G8000 Series Installation and Operation Manual  
106  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Insert Belleville washer between flat washer and nut.  
DC BUS  
FIG. 5  
8. Connect the Control plug/connector (male) located in input cabinet to the mating  
connector (female) in the output cabinet thru conduit plate in the side panels. See  
FIG. 5 & FIG. 6.  
9. Connect the Ground cable located in input cabinet to the Ground Bus located in the  
output cabinet thru the grommet hole in the side panels.  
NOTE: SEE MANUAL PAGE 38 FOR CONNECTING POWER CABLES & ANCHOR-  
ING THE CABINETS TO THE FLOOR. AFTER CONNECTING THE CABLES.  
ENSURE NO LOOSE HARDWARE, METAL SHAVINGS, TOOLS, ETC. ARE LEFT BE-  
HIND INSIDE THE CABINET.  
CLOSE THE CABINETS FRONT AND BACK. RECOMMENDED TORQUE VALUES OF  
3/8” STEEL BOLT IS 220 IN-LBS, 1/2” STEEL BOLT IS 390 IN-LBS.  
G8000 Series Installation and Operation Manual  
107  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G8000 Series Installation and Operation Manual  
108  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INDUSTRIAL DIVISION  
13131 West Little Your road, Houston, Texas 77041  
Tel (713) 466-0277 Fax (713) 466-8773  
U.S. (877) 867-8773 Canada (800) 872-2192 Mexico 01/800/527-1204  
www.toshiba.com/ind  
Printed in the U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

TC electronic SDN BHD Air Compressor CL 1B User Manual
Toshiba Air Conditioner RAS 10SAVP E User Manual
Toshiba Label Maker BSA4TMGS12QMR User Manual
Transition Networks Cable Box DVP 5140K User Manual
Triarch Indoor Furnishings 25981 User Manual
Tyco Electronics Portable Radio P5200 User Manual
U Line Freezer 75F User Manual
Vantec Range 355UF User Manual
Wayne Dalton TV Antenna 3995 User Manual
Weber Gas Grill 1000 Series User Manual