Thermo Products Burner GDM1 80N User Manual

GAS-FIRED FURNACE  
DOWN FLOW & DIRECT VENT (SEALED COMBUSTION)  
MODELS: GMD1-60N and GMD1-80N  
INSTALLATION AND SERVICE MANUAL  
For installation in:  
1. Manufactured Homes  
2. Modular Homes/Buildings  
3. Site Constructed—Residential (Single Story Dwellings)  
:
FOR YOUR SAFETY  
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this  
or any other appliance.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Do not touch any electrical switch; do not use any phone in your building.  
Immediately call your gas supplier from a neighbor’s phone.  
Follow the gas supplier’s instructions.  
If you cannot reach your gas supplier, call the fire department.  
: If the information in these instructions is not followed exactly, a fire or explosion may  
result causing property damage, personal injury, or loss of life.  
: Improper installation, adjustment, alteration, service, or maintenance can cause  
injury or property damage. Refer to this manual. For assistance or additional information, consult  
a qualified installer, service agency, or fuel supplier.  
: Do not use this appliance if any part has been underwater. Immediately call a  
qualified service technician to inspect the appliance and to replace any part of the electrical or  
control system that has been underwater.  
PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION, INITIAL FIRING, AND BEFORE  
PERFORMING ANY SERVICE OR MAINTENANCE. THESE INSTRUCTIONS MUST BE LEFT WITH THE USER  
AND SHOULD BE RETAINED FOR FUTURE REFERENCE BY QUALIFIED SERVICE PERSONNEL.  
THERMO PRODUCTS, LLC.  
POST OFFICE BOX 217  
NORTH JUDSON, IN 46366  
PHONE: (574) 896-2133  
MG-505  
ECN 5320-MA 130307  
MADE IN USA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
after turning off the gas supply. A final test for gas leakage must be made after  
purging the gas line.  
: DO NOT wet electronic components during the leak test. Wetting  
electronic components may damage circuitry and cause a hazardous situation.  
Dry moisture from all leads and terminals if wetting occurs. Wait at least 24  
hours for the circuit to fully dry before energizing the system.  
: The furnace and its gas valve must be disconnected from the gas  
supply during pressure testing of the gas supply system at pressures in excess  
of 1/2 PSIG or 14.0 inches W.G. The furnace can be isolated from the gas supply  
by closing its manual shut off valve at test pressures equal to or less than 1/2  
PSIG or 14.0 inches W.G.  
: Copper and brass tubing and fittings (except tin lined) shall not be  
used if the gas contains more than a trace (0.3 grains per 100 cubic ft.) of  
hydrogen sulfide gas. Check with your gas supplier.  
: If you suspect there is a problem with the furnace, the venting system  
or any other related problem, immediately contact a qualified service agency. If a  
service agency is not available, contact your fuel supplier.  
: Personal injury, or property damage, could result from major repair or  
service of this furnace by anyone other than a qualified contractor. Only the  
routine maintenance described in the user section of this manual should be  
performed by the user.  
: Do not block or obstruct air openings on the furnace or air openings  
communicating with the area in which the furnace is installed.  
: Do not allow the outside air intake to be blocked or obstructed by  
vegetation, ice, snow or any other materials.  
: Do not use this furnace if any part has been underwater. Immediately  
call a qualified service agency to inspect the furnace and to replace any part of  
the electrical or control system, which has been underwater.  
: Should overheating occur or the gas supply fail to shut off, shut off the  
manual gas supply valve to the furnace before shutting off the electrical supply.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
This page and the following page contain reproductions of the various warning  
and instruction labels placed on the Thermo Pride Gas Furnace. Please read and  
comply with the contents of these labels.  
WARNING: If you do not follow these instructions exactly, a  
fire or explosion may result causing property damage,  
personal injury or loss of life.  
A. This appliance does not have a pilot. It is equipped with a hot  
surface igniter that automatically lights the burner. Do not try to  
light the burner by hand.  
B. BEFORE OPERATING smell all around the appliance area for gas.  
Be sure to smell next to the base of unit because some gas is  
heavier than air and will settle on the floor or ground.  
WHAT TO DO IF YOU SMELL GAS  
?
?
Do not try to light any appliance.  
Do not touch any electric switch; do not use any phone in your  
building.  
?
?
Immediately call your gas supplier from a neighbor's phone.  
Follow the gas supplier's instructions.  
If you cannot reach your gas supplier, call the fire department.  
C. Use only your hand to move the gas control switch. Never use tools.  
If the switch will not move by hand, don't try to repair it, call a  
qualified service technician. Force or attempted repair may result in  
a fire or explosion.  
D. Do not use this appliance if any part has been underwater.  
Immediately call a qualified service technician to inspect the  
appliance and to replace any part of the control system and any gas  
control which has been underwater.  
1. STOP! Read the safety information above on this label.  
2. Set the thermostat to the lowest setting.  
3. Turn off all electric power to the appliance.  
4. This appliance is equipped with a hot surface igniter that  
automatically lights the burner. Do not try to light the burner by  
hand.  
5. Move the gas control switch to the "OFF" position.  
6. Wait five (5) minutes to clear out any gas. Then smell for gas,  
including near the floor or ground. If you smell gas, STOP! Follow  
"B" in the safety information above on this label. If you don't smell  
gas, go to the next step.  
7. Move the gas control switch to the "ON" position.  
8. Turn on all electric power to the appliance.  
9. Set thermostat to desired setting, and, if equipped, set the operating  
mode to "HEAT".  
10.If appliance will not operate, follow the instructions "To Turn Off  
Gas To Appliance" and call your service technician or gas supplier.  
1. Set thermostat to lowest setting, and, if equipped, set the operating  
mode to "COOL" or "OFF".  
2. If service is to be performed, turn off all electric power to the  
appliance.  
3. To turn off gas control valve, remove the burner compartment cover.  
4. Move the gas control switch to the "OFF" position.  
5. Replace the burner compartment cover.  
390540  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
TABLE OF CONTENTS  
SECTION  
BEGINNING PAGE  
I.  
SAFETY SECTION  
1
II.  
III.  
IV.  
GENERAL INSTRUCTIONS AND CLEARANCES  
FURNACE SPECIFICATIONS  
INSTALLATION  
6
8
10  
10  
10  
10  
12  
12  
13  
14  
15  
16  
18  
19  
21  
21  
23  
24  
25  
26  
27  
27  
29  
35  
35  
35  
36  
36  
37  
37  
37  
37  
38  
38  
39  
39  
40  
41  
43  
A. ROOF JACK  
B. STANDARD CHIMNEY  
C. FURNACE LOCATION  
D. BASE INSTALLATION  
1. Combustible Floor Base Model: 70-BASE  
2. Cottage Base Model: 01COT-BASE  
E. ALCOVE INSTALLATION  
F. CLOSET INSTALLATION  
G. COMBUSTION AIR  
H. GAS PIPING  
I. ELECTRICAL WIRING  
J. INITIAL START UP  
K. ADJUSTMENT OF BTU INPUT RATE  
L. BURNER ADJUSTMENT  
M. SETTING TEMPERATURE RISE  
N. FURNACE CHECKOUT PROCEDURE  
INSTALLER’S INSTRUCTIONS TO USER  
STARTING THE UNIT  
V.  
VI.  
A. SEQUENCE OF OPERATIONS  
VII. TROUBLESHOOTING  
VIII. DEALER MAINTENANCE  
A. ELECTRICAL  
B. BURNERS  
C. INDUCER BLOWER ASSEMBLY  
D. INSPECTING THE VENTING SYSTEM  
E. GASKETS/SEALING MATERIALS  
F. HEAT EXCHANGER  
G. HOUSE AIR BLOWER  
H. EXTENDED SHUTDOWN  
USERS INFORMATION SECTION  
A. WARNINGS & CAUTIONS  
B. COMPONENT LOCATIONS  
C. INSPECTION AREAS  
IX.  
D. FILTER LOCATION AND CLEANING  
APPENDIX A – REPLACEMENT PARTS  
APPENDIX B – WIRING DIAGRAM  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
II. GENERAL INSTRUCTIONS AND CLEARANCES  
NOTE: READ THIS SECTION BEFORE STARTING INSTALLATION  
1. This furnace is equipped with orifices for operation with natural gas. For  
conversion to propane gas, see instructions in Gas Conversion Section of this  
manual.  
2. Any reference to L.P. or Propane gas in this manual, any other labels, or  
markings on this furnace is to be construed to be propane HD-5. A commercial  
grade of liquefied petroleum gases composed of a minimum of 90 percent liquid  
propane (C8H8).  
3. The selection of a furnace heating capacity for a proposed installation should be  
based on a heat loss calculation made according to the manuals provided by the  
Air Conditioning Contractors of America (ACCA) or the American Society of  
Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE).  
4. It is recommended that a commercial available CO alarm be installed in  
conjunction with any fossil fuel burning appliance. The CO alarm shall be  
installed according to the alarm manufacturer’s installation instructions and be  
listed in accordance with the latest edition of the UL Standard for Single and  
Multiple Station Carbon Monoxide Alarms, UL 2034, or the CSA International  
Standard, Residential Carbon Monoxide Alarming Devises, CSA 6.19.  
5. The installer shall be familiar with and comply with all codes and regulations  
applicable to the installation of these heating appliances and related equipment.  
In lieu of local codes, the installation shall be in accordance with the current  
provisions of one or more of the following standards.  
a. Federal Manufactured Home Constructions & Safety Standard (HUD Total 24,  
Part 280).  
b. American National Standard (ANSI-119.2/NFPA-501C), for installations of all  
recreational vehicles.  
c. American National Standard (ANSI-Z223.1/NFPA-54), for installation of all gas-  
fired furnaces.  
d. American National Standard Electric Code (ANSI-C1/NFPA-70), for installation of  
all electrical field wiring.  
The gas-fired furnace has been investigated under the ANSI Z 21.47-CAN/CGA 22.3-  
2001 CENTRAL FURNACE test standard. This gas fired unit is listed by Intertek  
Testing Services and described as, “For installation as central furnace special type for  
single story dwelling.”  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
: The area around the furnace must be kept free and clear of  
combustible materials, especially papers and rags.  
: This furnace is not to be used as a construction heater.  
6. Definitions of "combustible" and "non-combustible" materials as presented in the  
1999 version of the National Fuel Gas Code, ANSI Z223.1-1999/NFPA 70-1999, are  
as follows:  
a. Combustible material:  
“...materials made of or surfaced with wood, compressed  
paper, plant fibers, or other materials that are capable of  
being ignited and burned. Such material shall be  
considered combustible even though flame proofed, fire-  
retardant treated, or plastered.”  
b. Non-combustible material:  
“...material that is not capable of being ignited and  
burned; such as material consisting entirely of, or a  
combination of, steel, iron, brick, tiles, concrete,  
slate, asbestos, glass, and plaster.”  
This heating appliance must be installed with clearances to combustible material  
surfaces of not less than the minimum distances given below. Also, allow ample  
clearances for servicing the furnace for easy access to the air filter, blower assembly,  
burner assembly, controls, and vent connections.  
MODELS GMD1-60N and GMD1-80N  
CLOSET  
ALCOVE  
FRONT  
BACK  
SIDES  
ROOF JACK  
VENT CONNECTOR  
TOP  
PLENUM SIDES  
TOP AND SIDES OF DUCT  
BOTTOM OF DUCT  
6”  
0”  
0”  
0”  
6”  
1”  
1”  
1”  
1”  
18”  
0”  
0”  
0”  
6”  
1”  
1”  
1”  
1”  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
III. FURNACE SPECIFICATIONS  
MODEL  
GMD1-60  
GMD1-80  
HEAT INPUT RATE (BTUH)  
HEATING CAPACITY (BTUH)  
BURNER ORIFICE-NAT. GAS (MM)  
BURNER ORIFICE-PROP. GAS (DMS)  
GAS SUPPLY PRESSURE (IN.W.G.)  
MINIMUM REQUIRED  
PROPANE  
60,000  
49,000  
#38  
80,000  
65,000  
2.45  
#52  
#53  
11  
11  
NATURAL  
5.5  
5.5  
MAXIMUM ALLOWED  
PROPANE  
14.0  
14.0  
14.0  
14.0  
NATURAL  
GAS MANIFOLD PRESSURE (IN. W.G.)  
PROPANE  
10 + 0.3  
3.5 + 0.3  
4
10 + 0.3  
3.5 + 0.3  
4
NATURAL  
VENT PIPE SIZE (INCHES)  
DESIGN TEMPERATURE RISE (°F)  
SEASONAL EFFICIENCY  
(AFUE*, %)  
70  
70  
82  
81  
*AFUE - INCLUDES STEADY STATE THERMAL EFFICIENCY AND OFF CYCLE  
LOSSES.  
ELECTRICAL RATINGS AND SETTINGS:  
ELECTRICAL SUPPLY: 115 VAC / 60HZ / 1 PHASE  
MAXIMUM TIME DELAY TYPE FUSE OR HACR BREAKER RATING: 15 AMPS  
TOTAL RATED CURRENT (AMPS): 7.15 (GMD1)  
NOMINAL HEAT ANTICIPATOR SETTING -- 0.8 mA (GMD1)  
DIMENSIONS & WEIGHTS:  
CABINET: WIDTH - 18 IN., DEPTH – 25-3/4 IN., HEIGHT - 57 IN.  
NO.70 MOBILE HOME BASE: WIDTH - 18-5/16 IN., DEPTH - 24¼ IN., HEIGHT - 4 IN.  
WARM AIR DUCT: WIDTH – 12 IN., DEPTH – 12 IN.  
COTTAGE BASE: WIDTH – 18-3/16 IN., DEPTH - 24¼ IN., HEIGHT – 14 IN.  
FILTER QUANTITY & SIZE: 1 – 18” x 24 “  
APPROXIMATE SHIPPING WEIGHT: 165 LBS.  
PRODUCT LISTED UNDER ETL FILE NUMBER –  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
BLOWER DATA  
GMD1-60  
MANUFACTURER: MORRISON PRODUCTS, INC.  
BLOWER MODEL: 10-7, DIRECT DRIVE  
NOMINAL MOTOR POWER OUTPUT (HORSEPOWER): 1/3  
TYPICAL AIRFLOW @ SPECIFIED EXTERNAL  
STATIC PRESSURES (SCFM @. IN.W.G.):  
ESP (IN W.C.)  
LOW SPEED:  
0.2  
0.5  
759  
694  
MEDIUM LOW  
SPEED:  
907  
809  
MEDIUM HIGH  
SPEED:  
1096  
1207  
934  
HIGH SPEED:  
1029  
GMD1-80  
MANUFACTURER: MORRISON PRODUCTS, INC.  
BLOWER MODEL: 10-9, DIRECT DRIVE  
NOMINAL MOTOR POWER OUTPUT (HORSEPOWER): 1/3  
TYPICAL AIRFLOW @ SPECIFIED EXTERNAL  
STATIC PRESSURES (SCFM @. IN.W.G.):  
ESP (IN W.C.)  
LOW SPEED:  
0.2  
0.5  
712  
640  
MEDIUM LOW  
SPEED:  
870  
760  
MEDIUM HIGH  
SPEED:  
1100  
1258  
886  
HIGH SPEED:  
1003  
ALL SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
IV. INSTALLATION  
A. ROOF JACK  
The roof jack assembly and accessories must be listed by a nationally recognized  
testing agency for the appropriate heating fuel.  
The roof jack assembly must be installed according to the vent manufacturer’s  
instructions prior to the furnace installation. (Refer to Figure 2 for flue location on  
furnace.) Adapters for pitched roofs as well as extended barrel length roof jacks are  
available from other suppliers.  
All vent seams and connections must be sealed with high temperature silicone caulk.  
B. STANDARD CHIMNEY  
When installed as a central furnace special type for single story dwelling, venting into a  
metal vent system approved by a nationally recognized testing agency for the  
appropriate heating fuel type is permitted. Lined masonry chimneys are acceptable  
when sized appropriately. The minimum chimney size should equivalent to the inside  
free area of the 4-inch diameter vent collar exiting the furnace, or 12.5 square inches.  
Maximum chimney sizes and acceptable installation practices are referenced in the  
following publication. When installing the GMD1-80N, refer to Appendix G of the latest  
edition of the installation standard NFPA 54, National Fuel Gas Code.  
C. FURNACE LOCATION  
1. For best performance, locate the furnace so that it is centralized with respect to the  
duct system.  
2. This furnace is only intended for installation with free air return through the furnace  
door louvers. CAUTION: DO NOT connect a ducted return air system directly to  
the furnace. Improper installation may create a fire hazard and damage internal  
equipment, as well as void all manufacturers’ warranties.  
3. This furnace may be installed on combustible flooring when utilizing either the No. 70  
counterflow floor base, for below the floor duct systems, or with the cottage base, for  
floor level air distribution. See Figures 1A and 1B for depictions of the No. 70 and  
the cottage bases.  
4. This furnace is listed for closet, alcove, or freestanding applications. All applications  
must comply with the requirements of this manual.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Combustible Floor Base  
Model: 70-BASE  
Figure 1A  
Cottage Base  
Model: 01COT-BASE  
Figure 1B  
Coil Cabinet  
Model: CE111S / CE211T  
Figure 1C  
CE111S  
CE211T  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
D. BASE INSTALLATION  
1. Combustible Floor Base Model: 70-BASE  
Use the base bottom panel as a template to mark floor opening locations (see  
Figure 2). Cut a square opening in the floor for the supply air connector duct. Cut the  
opening 1-inch larger than the square template opening. (duct requires 1-inch  
clearance to combustible floor). Cut a combustion air duct opening in the floor 1/8-  
inch larger than the template opening.  
Figure 2  
After cutting openings in the floor, place the bottom panel in position. Mark the  
square opening location on the distribution duct at the connection point of the  
connector duct. Remove the bottom panel. Cut an opening in the distribution duct  
slightly larger than the connector duct. (refer to Figure 2 for location of this cut.) Cut  
the connector duct to length. Install the connector duct. Bend over each tab. Insure  
an airtight seal by using high temperature sealant or tape on the joint. Reinstall the  
bottom panel over the connector duct. Insert and secure the combustion air duct. Put  
the base top assembly in place (see Figure-3).  
CAUTION: A combustion air duct must be used. If the underside of the mobile  
home is skirted or enclosed (e.g. enclosed in a crawlspace), the combustion air  
intake should exit through the skirting, or enclosure, if at all possible. All joints  
and seams of supply ducts and combustion air ducts must be closed with a  
sealing method suitable to the application conditions and temperatures (e.g. high  
temperature silicone caulk and/or aluminum tape).  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
If the combustion air passageway cannot terminate outside of the skirting or  
enclosure, a permanent opening with a minimum of 50 square inches of  
unobstructed infiltration (free area) for ventilation air must be provided for  
adequate combustion. This permanent opening must be located no less than 12  
inches from the bottom of the enclosure or skirting.  
Figure 3  
Slit the corners of connector duct down to the top of the base assembly. If metal  
projects more than 1-inch above the top of the base assembly, trim the flanges down  
to 1-inch. While the top of distribution duct is being pulled up with one hand, bend  
down each side of the connector duct tightly to the base assembly with the other  
hand. This assures a tight connection between the base assembly and the connector  
duct and that the distribution duct will be full size. Use high temperature tape and/or  
high temperature silicone caulking on all joints and seams to minimize air leakage.  
Secure the base assembly to the floor with two screws in the front flange.  
2. Cottage Base Model: O1COT-BASE  
The O1COT-BASE cottage base (Figure 1B) is required for a freestanding cottage  
base installation. The cottage base is designed to permit the installation of a 6-inch x  
14-inch register in each of the two side panels and the front panel.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
CAUTION: A permanent opening with a minimum of 50 square inches of  
unobstructed infiltration (free area) for ventilation and combustion air must be  
provided to the interior of the structure. Additional make-up air may need to be  
supplied to the interior of the structure to compensate for exhaust fans,  
appliances, or vents, which consume air from the interior of the structure.  
Refer to the assembly installation instructions included with OM1COT-BASE cottage  
base for additional information.  
3. Coil Cabinet: CE111S / CE211T  
The CE111S / CE211T coil cabinet (figure 1C) is for applications requiring air  
conditioning. The coil cabinet is designed to have the combustion air brought in  
from the bottom thru a flexible hose, supplied with the cabinet. Refer to section G  
Combustion air of this manual for further instructions on the combustion air  
termination and connections. For additional information refer instructions provided  
with the coil cabinet.  
E. ALCOVE INSTALLATION  
In this application, a minimum of 18  
inches of clearance must be provided  
to the front of the unit. Refer to  
Figure 4.  
Alcove installations must use the No.  
70 mobile home base.  
Note – access to diagnostic view port.  
Refer to section G. COMBUSTION AIR  
for additional combustion air  
requirements.  
Figure 4  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
F. CLOSET INSTALLATION  
WARNING: HAZARD OF  
ASPHYXIATION: A suction  
effect will occur when the  
furnace is operating inside the  
closet with the closet door  
closed. For proper operation,  
the furnace blower shall create  
no more than a 0.05-inch water  
column pressure differential  
between the closet and the  
adjoining space.  
Figure 5  
1. The return air opening into the closet is to have a minimum free area of 250 square  
inches, (refer to Figure 5).  
2. The return air opening may be located in the top, the center or (ideally) the bottom of  
the closet door, or sidewall.  
: Do not obstruct any return air openings, including the return grille on  
the furnace. To do so may cause the furnace to activate the high temperature  
limit and shutdown, or it may cause asphyxiation.  
3. The cross-sectional area of the return air grille leading into the closet (when located  
in the floor or ceiling) shall not be less than 250 square inches.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
4. The total free area of openings in the floor or ceiling registers serving the return air  
system must be at least 350 square inches. At least one register must be located  
where it is not likely to be covered by carpeting, boxes, furniture, or any other  
objects.  
5. Materials located in the return air system must have a flame spread classification of  
200 or less.  
6. Wiring materials located in the return air duct system must conform to Article 300-22  
of the latest edition of the National Electrical Code, NFPA 70.  
7. Gas piping shall not be located in, or extend through, the return air duct system.  
8. Refer to section G. COMBUSTION AIR for additional combustion air requirements.  
G. COMBUSTION AIR  
CAUTION: Flexible, spiral, or corrugated duct is not recommended, due to the  
relatively high-pressure drop associated with air movement through this type of  
passageway.  
The furnace requires the proper amount of combustion airflow through the combustion  
air intake to combust the fuel cleanly and efficiently. An inadequate combustion air  
supply can result in unsafe and erratic operation of the burner, sooting of the  
combustion chamber and the heat exchanger, and possibly, offensive fuel odors. Refer  
to chapter 5.3 of the National Fuel Gas Code, ANSI Z223.1 / NFPA 54-1999, or latest  
edition for application specific combustion air requirements.  
The preferred location of the outside combustion air intake terminal (e.g. an optional  
stainless steel intake hood, part no. AOPS7402) is through the side of the structure,  
skirting, or enclosure. An acceptable alternate location is under the structure in the  
skirted or crawlspace area providing a minimum of 50 square inches of free area exists  
around the perimeter for outside combustion air to be drawn through. The opening of  
the termination must be at least 7 inches below the top of the floor.  
The 70-base/coil cabinet is shipped with a combustion air duct that must be installed in  
the bottom of the base enclosure, before the furnace is installed. This 2-inch by 7-inch  
duct is shipped in two pieces. High temperature silicone sealant should be applied to  
both vertical seams, before it is snapped together with all four flanges on the same end.  
High temperature silicone must be applied to the flanges. The combustion air duct can  
then be inserted through the opening in the floor base model no.70. When the  
combustion air duct has been inserted completely, secure the duct to the combustion  
adapter with self-tapping sheet metal screws, refer to Figure 6. Make certain that the  
flanges, duct, and adapter are completely sealed to the burner enclosure base with high  
temperature silicone caulk. A 3-inch round to 7-inch x 2-1/4 inch rectangular adapter  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
plate is supplied with the furnace for adapting the 3-inch round flex combustion air duct  
to the 2-inch x 7-inch combustion air duct.  
Recommended materials for the combustion air duct are smooth, round, galvanized  
steel duct or schedule 20 PVC pipe. The maximum intake duct length allowed is  
equivalent to 40-feet of straight duct. Reduce this length by 6-feet for the intake hood  
and each 90-degree elbow used, and by 3-feet for each 45-degree elbow used the  
combustion air duct.  
Optional combustion air - a 4” round duct may be used by connecting a 3 x 4 reducer  
to the 3” flex duct supplied with the furnace.  
Figure 6  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
H. GAS PIPING  
: Because of the potential of the odorant to fade, a gas leak may not be  
detected by smell. If this furnace is installed below grade, contact your gas  
supplier for a gas detector.  
: With the gas piping pressurized, all gas piping connections must be  
leak tested using a strong soap and water solution. Any leaks must be repaired  
immediately after turning off the gas supply. A final test for gas leakage must be  
made after purging the gas line.  
: DO NOT wet electronic components during the leak test. Wetting  
electronic components may damage circuitry and cause a hazardous situation.  
Dry moisture from all leads and terminals if wetting occurs. Wait at least 24  
hours for the circuit to fully dry before energizing the system.  
: The furnace and its gas valve must be disconnected from the gas  
supply during pressure testing of the gas supply system at pressures in excess  
of 1/2 PSIG (13.9 inches W.G.). The furnace can be isolated from the gas supply  
by closing the manual gas shutoff valve serving the appliance at test pressures  
equal to, or less than, 1/2 PSIG or (13.9 inches W.G.).  
: Copper and brass tubing and fittings (except tin lined) shall not be  
used if the gas contains more than a trace (0.3 grains per 100 cubic ft.) of  
hydrogen sulfide gas. Check with your gas supplier.  
Sizing and installation of fuel lines must be in accordance with federal, state, and local  
regulations.  
A qualified installer or service person must install all gas piping and perform all required  
testing.  
Piping from the natural gas meter to the furnace shall be in accordance with  
requirements of the local gas utility. Piping from the propane tank to the furnace must  
follow the recommendations of the gas supplier. In the absence of local codes  
governing gas piping selection and installation, follow the National Fuel Gas Code,  
ANSI Z223.1 / NFPA 54-1999, or latest edition.  
A readily accessible, manual gas shutoff valve (design-certified for the applicable gas)  
with a non-displaceable rotor member shall be installed within six (6) feet of the  
furnace.  
A pipe union, or flanged connection, shall be provided directly up stream of the burner  
to allow burner removal. Unions must be of a ground joint type or flange-jointed type  
using a gasket resistant to the corrosive effects of LP gases. Pipe dope or sealant  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
design-certified to be resistant to the action of the LP gases should be used on all  
threaded joints.  
The burner is setup to be piped to the gas supply through the left-hand side of the  
furnace. For service purposes, it is recommended the gas union be located inside the  
furnace.  
A drip leg must be used on both propane and natural gas installations immediately  
upstream of the furnace in order to trap oil, condensate, and other impurities which  
might otherwise lodge in the gas valve, or plug the main burner orifice. A drip leg shall  
be provided at the outlet of the gas meter when there is excessive condensation  
between the gas meter and the furnace.  
Failure to install drip leg(s) may void the manufacturer’s limited warranty on the furnace.  
For natural gas, the maximum supply pressure is 14.0 in. W.G. and the minimum  
supply pressure, for purposes of input adjustment, is 5.5 in. W.G.  
For propane gas, the maximum supply pressure is 14.0 in. W.G. and the minimum  
supply pressure, for purposes of input adjustment, is 11.0 in. W.G.  
I. ELECTRICAL WIRING  
: When testing electrical equipment, always follow standard electrical  
procedures and precautions.  
All electrical wiring must be installed in strict accordance with local ordinances and  
codes. In the absence of local ordinances and codes, all electrical wiring must conform  
to the requirements of the National Electric Code, ANSI/NFPA 70-1999, or latest  
edition.  
1. Electrical Branch Supply Circuit  
Route all electrical wiring to the left side of the furnace. The power supply circuit to  
the furnace must be installed and grounded in accordance with the provisions of the  
National Electrical Code, ANSI/NFPA-70-1999, or latest edition, and all local codes  
having jurisdiction.  
2. Connection Of Power Supply Wires  
a. Remove the cover from junction box.  
b. Insert 115 VAC wires through the strain relief bushing (or conduit connection as  
applicable) on the left side of the furnace junction box.  
c. Connect the “hot” wire to the black wire.  
d. Connect the “neutral” wire to the white wire.  
e. Connect the “ground” wire to the green wire.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
f. Reinstall and secure the junction box cover with the original mounting screws.  
3. Connection Of Room Thermostat Wires  
NOTE: Class 1 thermostat wire must be used inside the furnace burner  
compartment.  
a. Insert 24 VAC wires through the plastic grommet on the left side of the furnace  
casing.  
b. Connect the thermostat wires to the W/R 50A65-143 control (refer to the wiring  
diagram).  
c. Connect the thermostat wires to the room thermostat.  
IMPORTANT: The room thermostat should be installed 4 to 5 feet above the floor  
on an interior wall which is relatively free from direct sources of heat (sunlight or  
supply airflow) or exposure to cold (drafts from open windows and doors). The  
nominal anticipator setting is 0.8 amperes, for the GMD (refer to the thermostat  
literature for additional information).  
Five-conductor thermostat wire is recommended for 24 VAC, low-voltage, control  
circuit wiring. How ever only 2 wires are required for the furnace (a heating  
application only).  
Maximum Recommended  
Electrical Wire Diameter  
Thermostat Wire Length  
(AWG)  
(Feet)  
24  
22  
20  
18  
55  
90  
140  
225  
Once the furnace is installed, check the thermostat anticipator for proper nominal  
setting.  
1. Connect a multimeter, capable of reading milliamps (mA), in series  
with the low voltage wires to the thermostat.  
1. Increase the thermostat setting, or create a “call for heat”.  
2. Read the value of the thermostat current, in milliamps.  
3. Adjust the heat anticipator of the thermostat to the value read by the  
multimeter.  
If the heat anticipator is set too high, the furnace may delay activation of a heating  
cycle for too long. If the heat anticipator is set too low, the furnace may cycle too  
frequently. Either condition may not provide optimal comfort to the homeowner.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
J. INITIAL START UP:  
This furnace does not have a pilot. It is equipped with a hot surface igniter, which  
automatically lights the burner. Do not attempt to light the burner by hand. Check the  
following items before the initial start-up.  
1. Check all wiring for proper hook up. Tighten any loose connections.  
2. Using a soap solution, leak test gas piping connections.  
3. Check all tubing connections to the pressure switch, inducer, burner box, and gas  
valve and make sure they are connected firmly at all their connection points.  
4. Check flue pipe, combustion air inlet, and all joints for tightness and to make sure  
there is no blockage.  
5. Make sure air filter is in place.  
6. Make sure the outside vent and air intakes are installed according to instructions  
and are free from blockage.  
OPERATING INSTRUCTIONS:  
: Turn off power to furnace before it is placed into service. The gas  
piping system must have been leak tested by a qualified heating contractor. (See  
Section IV, H, of these instructions on the installation of gas piping).  
: It may be necessary to purge the air out of the gas line for initial start-  
up of the furnace after installation. A qualified heating contractor should do this.  
If excessive gas escapes when purging the gas supply at the union, allow the  
area to ventilate for at least 15 minutes before attempting to start the furnace.  
Propane gas is especially dangerous because the specific gravity of propane gas  
allows it to accumulate at floor level at a dangerous concentration.  
: Heat exchanger oil will burn off on initial firing creating an unpleasant  
odor. To prevent this odor from occurring more than once, it is suggested that:  
1. A window(s) be opened.  
2. The thermostat be set at highest setting.  
3. The furnace remains running at conditions 1&2 for 30 minutes or until odor  
has dissipated.  
K. ADJUSTMENT OF HEAT INPUT RATE:  
The orifices for this furnace were sized: 1) for natural gas having a heating value of  
1025 BTU per cubic foot and a specific gravity of .65, or 2) for liquefied propane gas  
with a heating value of 2500 BTU per cubic foot and a specific gravity of 1.55. The  
rating label inside the furnace vestibule will specify which gas your furnace is orificed  
for. If the furnace is installed at an altitude that is more than 2,000 feet above sea level,  
it is mandatory the input to the burner be reduced 4.0% for every 1,000 feet that it is  
above sea level. If the furnace is installed at an elevation of 5,000 feet, its input must  
be reduced 20.0%. Example: a furnace rated at 80,000  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
BTU at sea level must be reduced to a firing rate of 64,000 (80,000 x .80 = 64,000) at  
an elevation of 5,000 feet. If the furnace is installed at an elevation of 2,000 feet or  
less, no reduction in input is required. Your gas supplier may supply you with the  
correct orifice sizing information.  
To check the heat input rate of your natural gas furnace, allow the unit to operate for 10  
to 15 minutes and proceed as follows:  
a. Call your gas supplier and ask for the BTU content (heating value) of one cubic foot  
of the gas, supplied to the installation area. An alternate approach is to assume a value  
of 1025 BTU/Cu Ft, which is the national average.  
b. With all other gas appliances turned off and using a stopwatch, clock the time  
required for the (small) dial on the gas meter to make one full revolution. The meter  
dial will state the cubic feet of flow for one revolution usually one, two or five.  
FORMULA: BTU/Cu Ft x Number of Cu Ft x 3600 Seconds = Input BTU/hr  
Seconds for one revolution  
EXAMPLE: 1025 BTU/Cu Ft x 2 Cu Ft x 3600 = 78,678 BTU Input  
93.80 Seconds  
Check the model number of the furnace, the input rate, the type of gas, and the  
manifold pressure on the rating label located in the burner vestibule. If using the above  
example, the furnace is a GMD1-80N model and the input rate is 78,678 BTU/hr. The  
input rate would be acceptable because it was within + 2% of the listed input of 80,000.  
c. Make sure that the gas supply pressure to the furnace is within the allowable range of  
5.5" to 14" WC pressure on natural gas and 11.0" to 14.0" WC on propane gas. The  
pressure to the furnace must be checked while the furnace burner and any other gas  
appliances on the same supply system are operating, using the 1/8 in. NPT manifold  
pressure tap shown in figure 8.  
GAS PRESSURE CHART FOR ALL GMD1-60 and GMD1-80 MODEL  
FURNACES  
SUPPLY PRESSURE MANIFOLD PRESSURE  
MAX 14” WC  
MIN 5.5” WC  
NAT  
3.5 + .3” WC  
MAX 14” WC  
MIN 11” WC  
PROPANE  
10.0” + .3” WC  
TABLE 2  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
This gas furnace is equipped with a fixed orifice sized for the manifold pressure shown  
on the rating label. The input can only be increased, or decreased, by adjusting the  
manifold pressure. Remove the 1/8" threaded pipe plug located on the gas manifold.  
Use a U tube manometer or recently calibrated pressure gage to measure the pressure.  
To adjust the pressure, remove the screw cap from the regulator on the gas valve and  
using the adjustment screw. Decrease the pressure by turning the screw  
counterclockwise or increase it by turning the screw clockwise.  
CAUTION: ADJUSTMENTS TO THE LISTED PRESSURE MUST NOT EXCEED  
0.3" WC A 0.3" WC adjustment will increase or decrease the input approximately 4.0%.  
Replace screw (cap) when adjustment is complete.  
The correct input can be assumed if the furnace manifold pressure is the same as that  
shown on the rating label if a gas meter is not available for natural gas or the unit is  
installed on an unmetered propane gas supply.  
Shut off the gas supply to the furnace. Remove the pressure gage and re-install the  
pipe plug using a thread compound resistant to the action of LP gases.  
If the rated input cannot be obtained with the present orifice at the correct pressure,  
your local gas supplier may assist in sizing the proper orifice. Thermo Products  
Engineering Department will gladly assist in sizing the orifice if you provide them with  
the heating value in BTU per cubic foot and the specific gravity of the fuel gas.  
L. BURNER ADJUSTMENT  
: The GMD1-60 and GMD1-80 furnace models utilize an in-shot burner  
design that does not require an air shutter adjustment (air shutters are not used)  
for proper flame characteristics. Burner box access cover must always be  
secured with all screws in place and tightened before operating furnace.  
This unit is designed to not require any burner adjustment. The flames should be  
checked by looking through the sight glass located on the burner box. Burner flames  
should be clear, blue, and almost transparent in color. (See Figure 8). NOTE: It is not  
unusual to have mostly blue flames with yellow or orange tips visible in the tube for  
propane gas.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Figure 8  
M. SETTING TEMPERATURE RISE  
The GMD1-60N and GMD1-80N is designed and wired at the factory for a heating  
blower speed that should result in an approximate temperature rise of 70°F.  
The blower motor is wired on low speed for heating mode of the GMD1-60N.  
The blower motor is wired on medium low speed for heating mode of the GMD1-80N.  
The temperature rise through the furnace may vary depending on the duct system,  
elevation, heating value, etc. for each installation.  
After 10 to 15 minutes of continuous operation, the temperature rise through the  
furnace must fall within a range of 55°F to 85°F. If the outlet or supply duct  
temperature is too high, check to make sure the return air filter is clean, the return air  
registers are free from obstruction, the outlet registers are properly adjusted and clear,  
and the supply and return air ducts are open.  
The circulating air blower is not moving enough air if the supply air temperature is still  
too high. Before proceeding further, turn off the power supply to the furnace and  
remove the blower door. The speed of the blower must be increased by changing the  
speed tap from the motor (see wiring diagram). This is accomplished by locating the  
control panel attached to the blower housing and switching the blower lead, which  
should be connected to the “Heat” terminal on the White-Rodgers 50A65-143 control,  
with one of the higher speed blower leads attached to a terminal marked “Park”. Be  
sure to attach any unused blower leads to a terminal marked “Park”. Replace the  
blower door and turn on the power supply.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
N. FURNACE CHECKOUT PROCEDURE  
Before any system of gas piping is finally put into service, it shall be carefully tested to  
assure that it is gas tight as indicated in section IV. H. Gas Piping of this manual.  
NOTICE: All controls on the unit should be checked for proper functioning prior to the  
qualified service personnel leaving the job site. Specifically the following should be  
checked:  
With furnace in normal heating operation, check to make certain blower will start and  
stop automatically under control of integrated fan control.  
1. Check safety limit control as follows:  
a. Shut off incoming power.  
b. Block return air opening or disconnect blower motor leads.  
c. Restore power to furnace.  
d. Set thermostat above room temperature calling for heat.  
e. When high air temperatures are reached in furnace at limit control setting with  
blower out of operation, burner should shut off.  
f. Shut off electrical power.  
IMPORTANT: Remove blockage or reconnect blower motor and restore power.  
2. Make certain thermostat will automatically start and stop furnace.  
3. Block the flue pipe outlet gradually until the pressure switch functions shutting off  
the main burners.  
4. Block the inlet gradually until pressure switch functions shutting off the main burners.  
IMPORTANT: Remove flue or air inlet blockages when done.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
V. INSTALLER'S INSTRUCTIONS TO USER:  
After completing the installation, the installer shall inform and/or demonstrate to the  
homeowner:  
1. The location of all the instructions in the furnace must be kept along with  
instructions for any accessories in the plastic pouch near the furnace.  
2. The location and use of the manual gas shut off valve and furnace electrical  
disconnect switch. Instruct user to always shut off gas before shutting off electric  
power.  
3. The sequence of operation of the furnace.  
4. The correct operation and maintenance of the appliance as outlined in the Users  
Information section of this manual.  
5. That failure to maintain and operate this furnace in accordance with these  
instructions could result in hazardous conditions, bodily injury, and property  
damage and may void the limited warranty on the furnace.  
6. Review with and encourage the user to read the label reproductions and all  
warnings and instructions outlined on the front cover and in sections I, II and III of  
this manual and in the Users Information section of this manual.  
7. Recommend the user has a qualified heating contractor inspect the furnace at the  
start of each heating season. Inform the user of the frequency of inspection  
required for reach item in the User Information Section of this manual.  
8. Should the furnace not operate after installation – note diagnostic code through  
view port prior to removing door.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
VI. STARTING THE UNIT  
A. SEQUENCE OF OPERATIONS  
CONTINUOUS SAFE OPERATION CHECK IF FLAME  
AT ANY TIME THE  
GAS VALVE IS  
NOT ENERGIZED  
SIMULATION CONDITION PRESENT OR ROLL-OUT  
SWITCH OPENS, SYSTEM ENERGIZES INDUCER  
FAN FOR 15 SECONDS AND CIRCULATOR BLOWER  
AT HEATING SPEED UNTIL SITUATION CORRECTION  
START  
THERMOSTAT CALLS FOR  
HEAT, CONTACTS CLOSE  
CONTROL BOARD ENERGIZED,  
INDUCER ENERGIZED  
PRESSURE SWITCH SENSES  
ADEQUATE DIFFERENTIAL  
PRESSURE CONTACTS CLOSE  
POWER IS APPLIED TO  
THE SILICON NITRIDE  
IGNITOR. IGNITOR  
POWER INTERRUPTION  
SYSTEM SHUTS OFF,  
RESTARTS WHEN  
WARM-UP IS 20 SECONDS  
POWER IS RESTORED.  
START TRIAL  
FOR IGNITION  
AFTER IGNITOR WARM-UP,  
THE GAS VALVE IS  
ENERGIZED TO OPEN  
FLAME MUST BE  
DETECTED WITHIN  
4 SECONDS IF FLAME  
IS DETECTED, THE  
IF FLAME IS NOT  
DETECTED, THE GAS VALVE  
IS DE-ENERGIZED, THE  
IGNITOR IS TURNED OFF AND  
THE CONTROL BOARD CONTROL  
GOES INTO "RETRY" SEQUENCE  
DELAY-TO-FAN-ON  
TIME BEGINS (45 SECONDS)  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
AFTER DELAY-TO-FAN--ON  
PERIOD ENDS, CIRCULATING  
AIR FAN IS ENERGIZED AT  
HEATING SPEED. THE  
(OPTIONAL) ELECTRONIC  
AIR CLEANER AND  
THE RETRY SEQUENCE  
PROVIDES A 60 SECOND  
WAIT BEFORE IGNITION  
RETRY. RETRY IS  
ATTEMPTED WITH AN  
ADDITIONAL 10 SECONDS  
OF IGNITOR WARM-UP TIME.  
MAIN  
BURNER  
OPERATION  
HUMIDIFIER ARE ENERGIZED.  
IF IGNITION ATTEMPT IS  
UNSUCCESSFUL, ONE  
MORE RETRY WILL BE  
MADE BEFORE THE  
CONTROL BOARD GOES  
INTO SYSTEM LOCKOUT.  
WHEN THERMOSTAT IS  
SATISFIED, CONTACTS  
OPEN AND THE GAS  
VALVE IS DE-ENERGIZED.  
AFTER PROOF OF FLAME  
LOSS, INDUCER STARTS  
5 SECOND POST SURGE  
AND (OPTIONAL) HUMIDIFIER  
IS DE-ENERGIZED. THE  
DELAY-TO-FAN-OFF PERIOD  
BEGINS (180 SECONDS)  
CALL  
FOR HEAT  
SATISFIED  
IF FLAME IS DETECTED,  
THEN LOST, THE CONTROL  
BOARD WILL REPEAT THE  
INITIAL IGNITION SEQUENCE  
FOR A TOTAL OF SIX  
RECYCLES. AFTER SIX  
UNSUCCESSFUL RECYCLE  
ATTEMPTS, THE CONTROL  
WILL GO INTO SYSTEM  
LOCKOUT.  
AFTER THE DELAY-TO-  
FAN-OFF PERIOD ENDS,  
THE CIRCULATING AIR  
FAN AND (OPTIONAL)  
ELECTRONIC AIR CLEANER  
ARE DE-ENERGIZED.  
IF SYSTEM IS IN LOCKOUT, THE  
MODULE WILL RESET ITSELF  
AFTER 60 MINUTES OR MAY  
BE MANUALLY RESET BY  
END OF CYCLE  
INTERRUPTING THE POWER  
TO THE FURNACE AT THE  
DISCONNECT OR INTERRUPTING  
THE CALL FOR HEAT AT THE  
THERMOSTAT. IF THIS DOES  
NOT RESTART THE SYSTEM,  
REFER TO THE TROUBLESHOOTING  
SECTION OF THIS MANUAL.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
VII. TROUBLESHOOTING  
THIS SECTION IS ONLY TO BE PERFORMED BY TRAINED, QUALIFIED SERVICE  
PERSONNEL, AND NOT BY THE FURNACE OWNER.  
NOTICE: BEFORE TROUBLESHOOTING, FAMILIARIZE YOURSELF WITH THE  
START UP AND CHECKOUT PROCEDURE. ALL INSTALLATION AND  
SERVICES MUST BE PERFORMED BY QUALIFIED HEATING CONTRACTORS  
When testing electrical equipment, always follow standard electrical  
procedures and precautions.  
Note – check diagnostic code through view port prior to removal of door.  
1. Check for line voltage (110-120VAC) to the furnace. If there is no line voltage  
applied to the furnace, check that disconnecting switch is “on”, fuses or circuit  
breakers have not blown or tripped.  
2. Make sure thermostat is “calling for heat”.  
3. Check for adequate fuel supply and pressure. Are all the fuel shutoff valves  
open?  
4. To assist you in troubleshooting this furnace, it is equipped with an integrated  
ignition control with diagnostics. These diagnostics evaluate what malfunction  
the control system has experienced and will activate a flashing light on the  
control in different sequences to help pinpoint the failure.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
DIAGNOSTIC FEATURES  
: Power must be disconnected before servicing.  
The 50A65-143 control continuously monitors its own operation and the operation of the  
system. If a failure occurs, the LED will indicate a failure code as shown below. If the  
failure is internal to the control, the light will stay on continuously. In this case,  
the entire control should be replaced, as the control is not field-repairable.  
If the sensed failure is in the system (external to the control), the LED will flash in the  
following flash-pause sequences to indicate failure status (each flash will last  
approximately 0.25 seconds, and each pause will last approximately 2 seconds).  
1 flash, then pause  
System lockout  
Pressure switch stuck closed  
2 flashes, then pause  
3 flashes, then pause  
4 flashes, then pause  
6 flashes, then pause  
7 flashes, then pause  
8 flashes, then pause  
Pressure switch stuck open  
Open limit switch or rollout switch  
115 Volt AC power reversed  
Low flame sense signal  
Check igniter or improper grounding  
Continuous flashing  
(No pause)  
Flame has been sensed when  
no flame should be present  
(No call for heat)  
The LED will also flash once at power-up.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
TROUBLESHOOTING GUIDE  
THE SYSTEM IS STARTED BY SETTING THE THERMOSTAT TO CALL FOR  
HEAT. THE FOLLOWING SHOULD HELP ESTABLISH THE TYPE OF  
MALFUNCTION OR DEVIATION FROM THE NORMAL OPERATION.  
TO USE THIS DIAGRAM, FOLLOW THE INSTRUCTIONS IN THE BOXES.  
NOTE: CHECK DIAGNOSTIC CODE THROUGH VIEW PORT PRIOR TO REMOVING ACCESS DOOR.  
TURN THERMOSTAT TO CALL FOR HEAT  
DOES THERMOSTAT MAKE CONTACT?  
No  
Yes  
IS ROOM  
TEMPERATURE  
ABOVE  
IS ROOM TEMPERATURE  
BELOW THERMOSTAT  
SETTING?  
TURN T'STAT  
SETTING ABOVE  
ROOM TEMP.  
No  
No  
90 DEGREES F?  
Yes  
COOL THE THERMOSTAT  
Yes  
IS THE TRANSFORMER  
No  
ARE WIRES CONNECTED  
PROPERLY?  
No  
CORRECT WIRE  
CONNECTIONS  
SUPPLYING 24 VOLTS  
TO THE THERMOSTAT?  
Yes  
Yes  
REPLACE  
THERMOSTAT  
IS INTERNAL DAMAGE  
PRESENT ON THE  
TRANSFORMER?  
CHECK INPUT  
POWER, SERVICE  
SWITCH AND FUSES  
No  
Yes  
REPLACE TRANSFORMER  
IS THERE 24 VOLTS  
ACROSS "TH" & "TR"  
AT THE INTEGRATED  
CONTROL?  
CHECK FOR  
CONTINUITY  
& PROPER  
IS THE INDUCER  
BLOWER OPERATING?  
No  
No  
CONNECTIONS  
Yes  
Yes  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Yes  
Yes  
CHECK THE INTEGRATED  
CONTROL DIAGNOSTIC LED  
IS THERE LINE VOLTAGE  
ACROSS INDUCER POWER  
TERMINALS "IND" & "IND N"  
AT THE INTEGRATED CONTROL?  
LAMP. RESET BY INTERRUPTING  
POWER TO CONTROL FOR MORE  
THAN ONE SECOND. IF LED STAYS  
ON CONTINUOUSLY, REPLACE  
INTEGRATED CONTROL.  
No  
Yes  
CHECK WIRING TO INDUCER  
AND IF OK, REPLACE  
INDUCER ASSEMBLY.  
CHECK THE INTEGRATED CONTROL  
DIAGNOSTIC LED LAMP. RESET BY  
INTERRUPTING POWER TO CONTROL  
FOR MORE THAN ONE SECOND. IF  
LED STAYS ON CONTINUOUSLY  
IS THERE LINE VOLTAGE  
ACROSS HOT SURFACE  
IGNITOR TERMINALS  
"IGN" & "IGN N" AT THE  
INTEGRATED CONTROL?  
DOES THE HOT  
SURFACE  
IGNITOR ENERGIZE  
AND GLOW?  
No  
No  
REPLACE INTEGRATED CONTROL.  
Yes  
CHECK WIRING TO HOT  
SURFACE IGNITOR AND  
IF OK, REPLACE HOT  
Yes  
SURFACE IGNITOR ASSEMLBY.  
CHECK ACROSS "MV"  
AFTER HOT  
TERMINALS ON INTEGRATED  
CONTROL FOR 24 VOLTS DURING  
THE 4 SECOND FLAME PROVING  
PERIOD AFTER IGNITOR WARM-UP.  
IS THERE 24 VOLTS?  
SURFACE IGNITOR  
WARM-UP, DOES  
GAS VALVE OPEN?  
No  
No  
SAME AS ABOVE  
Yes  
Yes  
CHECK WIRING TO GAS  
VALVE AND IF OK,  
REPLACE GAS VALVE.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Yes  
AFTER GAS VALVE  
OPENS, DO THE  
BURNERS IGNITE?  
MEASURE MANIFOLD  
PRESSURE. IS  
PRESSURE ADEQUATE?  
ADJUST TO 3.5" WC FOR  
NATURAL GAS OR 10.0" WC  
FOR PROPANE GAS  
No  
No  
Yes  
CHECK IGNITOR  
VOLTAGE DURING  
20 SECOND WARM-UP,  
IT SHOULD BE AT  
No  
CORRECT LINE  
VOLTAGE PROBLEM.  
LEAST 105 VOLTS.  
Yes  
Yes  
IS IGNITOR  
POSITIONED  
CORRECTLY?  
No  
REPOSITION TO  
CORRECT LOCATION.  
DO BURNERS STAY  
LIT PAST PROOF  
OF FLAME CHECK?  
No  
CHECK FLAME  
PROVING CIRCUIT  
Yes  
DOES THE INTEGRATED  
CONTROL ENERGIZE THE  
CIRCULATING AIR  
BLOWER AFTER THE 45  
SECOND TIME DELAY?  
CHECK ACROSS THE  
CIRCULATING AIR  
BLOWER TERMINALS  
"CIR N" & "HEAT"  
No  
No  
REPLACE THE  
INTEGRATED CONTROL.  
FOR PROPER VOLTAGE.  
Yes  
CONFIRM IF EITHER  
BLOWER WHEEL IS  
RUBBING AGAINST  
HOUSING OR MOTOR  
SHAFT IS SPINNING  
FREELY AND REPAIR  
OR REPLACE AS  
DOES THE CIRCULATING  
AIR FAN COME ON  
No  
DOES BLOWER  
SPIN FREELY?  
No  
WHEN ENERGIZED?  
NECESARRY.  
Yes  
IS CAPACITOR  
WORKING PROPERLY?  
Yes  
REPLACE MOTOR  
Yes  
No  
REPLACE CAPACITOR  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Yes  
CHECK ALL  
WIRING FOR  
LOOSE  
IS LED LIGHT  
ON INTEGRATED  
CONTROL FLASHING?  
DOES SYSTEM RUN UNTIL  
THERMOSTAT IS SATISFIED?  
No  
No  
CONNECTIONS  
Yes  
Yes  
CHECK FOR SHORT IN  
WIRE TO THERMOSTAT  
AND CORRECT IF  
DOES BURNER SHUT OFF  
WHEN THERMOSTAT IS  
SATISFIED?  
No  
NECESSARY.  
IF LED FLASHES:  
1 FLASH, THEN PAUSE SYSTEM LOCKOUT  
Yes  
2 FLASHES, THEN PAUSE PRESSURE SWITCH STUCK CLOSED  
3 FLASHES, THEN PAUSE PRESSURE SWITCH STUCK OPEN  
4 FLASHES, THEN PAUSE OPEN LIMIT SWITCH OR ROLLOUT SWITCH  
6 FLASHES, THEN PAUSE 115 VOLT AC POWER REVERSED  
7 FLASHES, THEN PAUSE LOW FLAME SENSE SIGNAL  
DOES THE CIRCULATING  
AIR BLOWER TURN OFF  
AFTER THERMOSTAT IS  
SATISFIED WITHIN  
120 SECONDS?  
8 FLASHES, THEN PAUSE CHECK IGNITOR OR IMPROPER GROUNDING  
CONTINUOUS FLASHING  
(NO PAUSE)  
FLAME HAS BEEN SENSED WHEN NO FLAME  
SHOULD BE PRESENT (NO CALL FOR HEAT)  
THE LED WILL ALSO FLASH ONCE AT POWER-UP.  
CHECK COMPLETE SYSTEM OUT.  
Yes  
LED LIGHT STAYS ON CONTINUOUSLY,  
COMPLETE FAILURE - REPLACE INTEGRATED CONTROL.  
TROUBLESHOOTING COMPLETE.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
VIII. DEALER MAINTENANCE  
A qualified heating contractor should perform the following maintenance  
procedures at the beginning of each heating season. Correct any deficiencies at  
once.  
WARNING: Personal injury or property damage could result from repair or  
service of this furnace by anyone other than a qualified heating contractor. Only  
the homeowner/user routine maintenance described in the Users Information  
Manual may be performed by the user.  
WARNING: To avoid injury from moving parts, shut off the power to the  
furnace before removing blower compartment door.  
CAUTION: Label wires prior to disconnection when servicing controls. Wiring  
errors can cause improper and dangerous operation.  
A. ELECTRICAL:  
1. Check all wiring for loose connections and any signs of damage or unusual wear.  
2. Check for correct voltage at the furnace when operating.  
3. Check amp-draw on blower motor and inducer motor to assure they are not  
exceeding nameplate amp rating.  
4. Check for correct operation and proper settings (if manually adjustable) of all  
controls.  
Shut off gas and disconnect power before continuing.  
B. BURNERS  
If it appears that material is accumulating in the burner box, the burner box cover can  
be removed and the box and burners can be vacuumed. If necessary, the burners  
assembly can be removed by taking out the two screws/one on each bracket on top of  
burner box and removing the burner manifold assembly (See Fig. 9). Assembly must  
be pulled & tilted down in order to remove from box. If necessary, the individual tubes  
can be cleaned out using compressed air to blow out the individual tubes. Care must  
be taken not to damage the igniter.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Figure 9  
C. INDUCER BLOWER ASSEMBLY  
Inspect the pressure switch and tubing connections and inspect the blower/assembly  
for warpage, deterioration and carbon or other build-up. If necessary, clean the  
accessible portions of the housing and blower with a damp cloth. Vacuum to remove  
any lint or dust from the motor assembly.  
D. INSPECTING THE VENTING SYSTEM  
The venting system should be inspected during the annual maintenance check-up or  
during each subsequent service call.  
Check all vent pipes for restrictions due to soot, or carbon build-up, as well as foreign  
matter, or any materials, that cause the venting system to restrict the proper venting of  
combustion products. If a restriction is found, the flue vent must be cleaned or  
replaced to ensure proper venting.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Vent pipes should also be inspected for any signs of corrosion, deterioration, or leakage  
that may cause combustion by-products to infiltrate the home or indoor environment.  
If signs of corrosion, deterioration, or leakage are evident, the vent pipe must be  
replaced with a properly sized, agency-approved, vent pipe.  
E. GASKETS/SEALING MATERIALS  
Inspect all visible gaskets for signs of degradation, especially any seals which were  
removed as part of the inspection. Replace any suspect gaskets.  
F. HEAT EXCHANGER  
Inspect for corrosion, pitting, warpage, deterioration, carbon build-up, and loose gaskets  
in the flue pipe, burner box, and accessible areas of the heat exchanger.  
G. HOUSE AIR BLOWER  
Check and clean the blower wheel, housing, and compartment with a vacuum. Check  
the motor nameplate and follow the motor manufacturers instructions for lubrication, if  
required.  
IMPORTANT: Some motors are permanently lubricated and should not be oiled.  
See motor nameplate for specific instructions.  
H. EXTENDED SHUTDOWN  
If this furnace is shut down or off for an extended period of time, several steps can be  
taken to help insure a smooth and reliable start.  
ON SHUT DOWN:  
1. Close the gas supply shutoff valve(s).  
2. Turn the furnace power switch “off” and disconnect electrical power to the unit.  
ON START-UP:  
1. Have the heating system (and furnace) inspected and started by a qualified  
service person.  
2. Set the room thermostat above room temperature.  
3. Open all shutoff valves in the gas supply line.  
4. Turn “on” the main power at the disconnecting switch and at the furnace power  
switch to start the inducer.  
5. Follow the “BURNER OPERATION AND ADJUSTMENT” procedure in Section J.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
IX. USER INFORMATION SECTION  
A. WARNINGS AND CAUTIONS:  
: If you suspect there is a problem with the furnace, pertaining to the  
venting system or any other related problem, immediately contact a qualified  
service agency. If a service agency is not available, contact your fuel  
supplier.  
: Personal injury or property damage could result from major repair  
or service of this furnace by anyone other than a qualified contractor. The  
user should only perform the routine maintenance described in the user  
section of this manual.  
: The area around the furnace should be kept free and clear of  
combustible materials, especially papers and rags.  
: Do not block or obstruct air openings on the furnace casing. Do not  
block or obstruct air openings communicating within the area in which the  
furnace is installed.  
: Do not allow the outside air intake to be blocked or obstructed by  
vegetation, ice, snow, or any other materials.  
: Do not use this furnace if any part has been underwater.  
Immediately call a qualified service agency to inspect the furnace and to  
replace any part of the electrical or control system, which has been  
underwater.  
: Should overheating occur or the fuel supply fail to shut off, shut off  
the manual fuel supply valve to the furnace before shutting off the electrical  
supply.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
B. COMPONENT LOCATIONS  
The following diagram shows a typical furnace installation and typical position of  
the components referenced in these instructions.  
Figure 10  
C. INSPECTION AREAS  
IMPORTANT: For safe operation it is the responsibility of the owner and/or user  
that the burner, chimney/vent pipe, heat exchanger and controls should be  
inspected every year by a qualified heating contractor.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
1. VESTIBULE: The furnace vestibule areas or burner compartment should be  
inspected by removing front door of the furnace and looking for signs of  
excessive heat such as discoloration of components, materials damaged  
from rust or corrosion, soot or carbon build-up.  
2. EXTERIOR OF FURNACES: The furnace exterior should be inspected for  
signs of excessive heat such as discoloration of materials or damage from  
rust or corrosion.  
3. VENT CONNECTOR: The furnace vent pipe should be inspected for signs of  
rust, corrosion pitting, or holes in the pipe. Check for leakage around seams  
in pipe indicated by soot or condensate streaks.  
4. ROOF JACKS: The furnace roof jack should be inspected for signs of rust or  
corrosion, pitting or holes, signs of excessive condensation or moisture  
leaking from roof jack.  
D. FILTER LOCATION AND CLEANING  
CAUTION: To avoid injury from moving part, hot surfaces or electrical  
shock, shut off the power to the furnace and allow the furnace to cool  
before removing furnace access door to service filter.  
The air filter should be inspected each month and cleaned when dirty. Clean the  
filter by soaking it in water with a mild detergent and rinsing it with clean water.  
Allow the filter to air dry before reinstalling it in the furnace. Cleaning the air filter  
frequently may prevent airborne contaminants from going through the furnace  
and depositing in the furnace, duct system, and interior of the building.  
See Figure 10, in this section, for the location of the return air filter.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
APPENDIX A – REPLACEMENT PARTS  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
APPENDIX B – WIRING DIAGRAM  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tektronix Pill Reminder Device DC 504 User Manual
Thule Automobile Accessories Kit 2181 User Manual
Tiger Games 36293 User Manual
Toastmaster Blender RHBLRET User Manual
Topcom MP3 Player II 128 User Manual
Toro Lawn Mower 22621223 24 User Manual
Tricity Bendix Oven TBS 605 User Manual
True Fitness Treadmill PS75 User Manual
ViewSonic Car Video System VG700 User Manual
Weed Eater Lawn Mower 186843 User Manual