Therma Stor Products Group Dehumidifier UA 150H User Manual

INSTALLER’S & OWNER’S MANUAL  
Ultra-Aire 150H Whole House  
Ventilating Dehumidifier  
UA-150H • Part No. 4024371 • Serial No.________________________________  
Dehumidification  
Fresh Air Ventilation  
The highly efficient Ultra-Aire 150H dehumidifier utilizes refrigeration  
to cool the incoming air stream below its dew point. This cooled and  
drier air is used to pre-cool the incoming air stream resulting in a  
significant increase in overall efficiency. After the pre-cooling stage,  
the processed air is reheated by passing through the condenser coil.  
The heat removed by the evaporator coil is returned to the air stream,  
resulting in an overall temperature increase of the air leaving the unit.  
Optional fresh outdoor air may be ducted to the unit via a six inch  
round duct. This provides fresh air to dilute pollutants and maintain  
high oxygen content in the air. The amount of fresh air ventilation can  
be regulated by a variety of dampers and controls.  
Air Filtration  
The UA-150H includes air filtration to improve indoor air quality. A  
MERV-11 media filter is standard. An optional MERV-14 deep pleated  
95% media filter is available for optimum air filtration and to reduce  
potentially harmful airborne particles. If the optional filter is chosen,  
the standard filter operates as a prefilter.  
The Ultra-Aire 150H is controlled by 24 volt remote wired controls. A  
variety of controls are available suitable to various applications.  
HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER  
© 2006 Therma-Stor LLC  
Manual P/N TS-245h 6/07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY PRECAUTIONS  
1. Safety Precautions  
Read the installation, operation and maintenance instructions  
carefully before installing and operating this device. Proper  
adherence to these instructions is essential to obtain maximum  
benefit from your UA-150H indoor air quality system.  
READ AND SAVE THESE INSTRUCTIONS  
• The device is designed to be installed INDOORS IN A SPACE THAT  
IS PROTECTED FROM RAIN AND FLOODING.  
• Install the unit with space to access the front panel for  
maintenance and service. DO NOT INSTALL UNIT WITH THE  
FRONT PANEL INACCESSIBLE.  
• Avoid directing the discharge air at people, or over the water in  
pool areas.  
• If used near a pool or spa; be certain there is NO chance the unit  
could fall into the water, splashed and that it is plugged into a GFI  
GROUND FAULT INTERRUPT OUTLET.  
• DO NOT use the device as a bench or table.  
• DO NOT place the device directly on structura lmembers.  
• A drain pan MUST be placed under the unit ifinstalled above a  
living area or above an areawhere water leakage could cause  
damage  
3
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
Place the UA-150H on supports that raise the base of the unit  
above the top of the flanges on the drain pan beneath it. Raising the  
UA-150H will help the unit drain with gravity flow. Do not place the  
UA-150H directly on structural building members without vibration  
absorbers or unwanted noise may result.  
1. Intended Application for Ultra-Aire 150H  
For the ideal installation, draw air from the central part of the home  
and return it to isolated areas of the home like the bedrooms, den,  
utility room, or family room. The ductwork of the existing heating  
system can be used to supply air to the home.  
The UA-150H may be suspended with steel hanger straps (plumbers  
tape) or a suitable alternative from structural members. Remember  
to place a drain pan under the unit if it is suspended above a finished  
area or above an area where water leakage could cause damage.  
2. Specifications  
Model:  
UA-150H Indoor Air Quality System  
Electrical:  
110-120 VAC, 12 Amps, 60 Hz,  
grounded  
The UA-150H should be located near the existing air handling  
system to minimize the required ductwork for connecting the  
UA-150H to the existing air handling system. The controls for the  
UA-150H are remote from the unit and must be located in the space  
that is to be conditioned. The controls are low voltage (24 volt) and  
should be connected to the UA-150H with low voltage thermostat  
cable.  
Capacity:  
145 pints/day @ 80°F, 60% RH  
56°F min., 100°F max.  
Operating Temp. Range:  
Air Flow:  
400 CFM without external ducting  
355 CFM @ .20 IWG external static  
290 CFM @ .40 IWG external static  
2 lb., 2 oz. R-22  
Refrigerant Charge:  
Duct connections:  
An external insulation kit is available for the UA-150H. This will  
prevent the cabinet from sweating if the unit is installed in an  
unconditioned space. This kit will also increase the efficiency of the  
unit by eliminating unwanted heat transfer between the unit and the  
unconditioned space. See the optional parts list for information on  
the kit.  
Round 10" & 6" inlets, 10" outlet  
Filter Size: Pleated cloth: 2" X 20" X 24" High Efficiency: 4" X 20"  
X 24"  
3
3
1
4
4
2
Size (w/o duct collars):  
Unit Weight:  
45 / " long x 24 / " wide x 20 / " high  
145 lb., Shipping Weight 229 lb.  
If fresh air ventilation is desired, thought should be given to the  
location for the fresh air ducting. A 6” round insulated duct will  
have to be installed on the UA-150H and run to the outside of the  
structure to bring in fresh air. Use an 8” insulated round duct for  
lengths of more than 50 feet or if more than 100 CFM is needed.  
Consult local codes for necessary distances from exhaust ports  
when installing fresh air return.  
3. Installation  
3.1 Location  
The UA-150H can be installed in a variety of locations to meet  
the owner's needs as listed below. In all cases keep the following  
cautions in mind:  
• It is designed to be installed INDOORS IN A SPACE THAT IS  
PROTECTED FROM RAIN AND FLOODING.  
3.2 Electrical Requirements  
WARNING: DO NOT ALLOW THE YELLOW LEAD FROM THE  
ULTRA-AIRE TO CONTACT THE RED LEAD OR ORANGE LEAD  
FROM THE ULTRA-AIRE OR DAMAGE TO THE TRANSFORMER  
WILL RESULT.  
• Install the unit with space to access the front panel for  
maintenance and service. Also allow easy access to the filter cover  
panel. DO NOT INSTALL UNIT WITH THE FRONT PANEL OR FILTER  
COVER PANEL INACCESSIBLE.  
• Avoid discharging the air directly at people, or over the water in  
pool areas.  
The UA-150H plugs into a common grounded outlet on a 15 or  
20 Amp circuit. It draws around 12 Amps under normal operating  
conditions. If used in a wet area (pool, spa room, or basement prone  
to flooding), a ground fault interrupter protected circuit is required.  
• If used near a pool or spa, be certain there is NO chance the unit  
could fall into the water or be splashed and that it is plugged into a  
GROUND FAULT INTERRUPTER.  
Install the remote control panel in a central area of the structure  
where it will sense the relative humidity of the structure accurately.  
Do not install the control panel where it may not accurately sense  
the relative humidity such as near HVAC supply registers, near  
exterior doors, or near a pool or spa. The installer must supply the  
wiring between the UA-150H and the control panel. Be sure to safely  
route the control wiring to prevent damage during installation. Be  
• DO NOT use the UA-150H as a bench or table.  
• DO NOT place the UA-150H directly on structural members.  
• A drain pan MUST be placed under the unit if installed above a  
living area or above an area where water leakage could cause  
damage.  
4
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
careful not to cross the wires when connecting the UA-150H and the  
remote control panel or damage to the transformer may result.  
3.4B Ducting for Dehumidification  
For the ideal installation, draw air from the central part of the home  
and return it to the isolated areas of the home like the bedrooms,  
den, utility room, or family room. The ductwork of the existing  
heating system can be used to supply air to the home. If the existing  
supply goes to isolated areas of the home, discharge the supply of  
the UA-150H into the supply of the existing heating system. If the  
existing heating system incorporates a central supply, installation of  
a separate supply duct from the UA-150H to each isolated area is  
recommended. DO NOT draw air directly from the kitchen, laundry,  
or isolated basement. You may draw air from a basement that is  
open to the home. All flexible ducting connected to the UA-150H  
should be UL listed.  
The remote controls of the UA-150H are powered by a low voltage  
circuit (24 Vac) and must NEVER contact or be connected to a high  
voltage circuit. The control wires leaving the UA-150H and the  
remote control panels are numbered and color-coded to prevent  
confusion. Some of the control wires leaving the UA-150H may  
not be used with certain control panels and should be left safely  
disconnected with wire nuts taped onto the stripped ends. Be sure to  
consult the electrical schematic in this manual or inside the access  
panel of the UA-150H before making the control connections.  
NOTE: RESET THE VENTILATION TIMER BEFORE ATTEMPTING  
TO PROGRAM AFTER INITIAL INSTALLATION. THE TIMER MAY  
NOT OPERATE CORRECTLY UNTIL IT IS RESET.  
The inlet of the UA-150H is the 10” diameter hole in the filter  
enclosure of the unit. A 10” round collar is supplied with the unit  
to attach to round duct. The duct may be permanently attached to  
the collar. A 6” round collar is provided with the unit to attach to  
the 6” hole in the filter enclosure. The 6” collar should be capped if  
fresh make-up air is not desired. If fresh make-up air is desired see  
section 3.4C.  
A decorative picture frame is provided to cover the control panel. The  
home owner may use their choice of picture frames.  
If an extension cord is required, it must have a minimum of 12 gauge  
conductors if 25 feet long or less and 10 gauge conductors if greater  
than 25 feet long.  
The outlet of the UA-150H is located on the end of the unit. A second  
10” round collar is supplied with the unit. Cut and remove the safety  
grid, then bend the tabs on the collar inside the hole in the cabinet  
end.  
3.3 Condensate Removal  
Condensate drains by gravity via the clear hose extending from the  
unit. Route the hose to a suitable drain. Use care to keep the hose  
as flat to the floor as possible, excessive humps will prevent proper  
drainage. We do not call for a trap since there is an internal trap with  
this unit.  
A length of 6 feet or more of acoustical flex ducting on the outlet of  
the UA-150H will reduce air noise from the impeller fan. A length of  
flexible ducting on all UA-150H duct connections is recommended  
to reduce noise and vibration transmitted to rigid ductwork in the  
structure.  
If the UA-150H is located too far from a floor drain for the attached  
hose to reach, inexpensive 1/2" PVC pipe can be used to extend it. It  
is commonly available in 10' lengths from building supply, plumbing  
or hardware stores. It will slide tightly inside the end of the drain  
hose. If more than one length of pipe is required, they can be joined  
with a short piece cut from the end of the drain hose.  
Ducting the UA-150H as mentioned in sections 3.4A-3.4G requires  
consideration of the following points:  
Duct Sizing: For total duct lengths up to 25', use a minimum 10"  
diameter round or equivalent rectangular. For longer lengths, use a  
minimum 12" diameter or equivalent. Grills or diffusers on the duct  
ends must not excessively restrict airflow.  
An optional condensate pump kit may be installed if a lift is required  
to dispose of the condensate. The condensate pump kit can be  
ordered direct from the factory. See the optional parts list for  
information on the kit.  
Isolated Areas: Effective dehumidification may require that ducting  
be branched to isolated, stagnant areas. Use 8" or larger diameter  
branch ducting to each of two or three areas, use 6" or larger to  
each of four or more areas.  
3.4 Ducting  
3.4A Installing Duct Collars  
The UA-150H is equipped with 10” and 6” round inlet collars and  
a 10” round exhaust collar. The 10” and 6” round inlet collars are  
designed with tabs that fold inside the filter enclosure of the UA-  
150H. The 10” round exhaust collar is attached to the UA-150H by  
folding the tabs inside the end panel of the UA-150H.  
Connecting to existing HVAC systems: An optional 10" check damper  
is available from the factory to prevent reverse flow through the  
UA-150H. If the UA-150H is ducted to the supply of a high static air  
handler the check damper may be placed in the UA-150H supply  
duct. Contact the factory when connecting to a static pressure of  
greater than or equal to +.5” WG.  
To install the collars; Insert the tabs of the collar into the hole in the  
filter enclosure and/or end panel of the UA-150H and fold the tabs  
up to attach to UA-150H.  
5
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
3.4C Ducting for Fresh Air  
3.4D Installation in a Basement or Crawlspace  
with an Existing Forced Air HVAC System  
If the existing system has multiple returns, select one to disconnect  
from the existing forced air system and use it for the dedicated  
UA-150 return. Always select a return from a central location in the  
structure in an area that is always open to the rest of the structure.  
Do not use a return from a room that may have its’ door closed  
Fresh air can be brought into the structure by connecting a insulated  
duct from outside to the 6” UA-150H inlet and by turning on the  
fan switch or activating the humidity control (on units with the  
humidity control panel). Activate the ventilation timer on units with  
the ventilating & humidity control panel to bring in fresh air. Refer  
to section 4.5 for programming instructions for the ventilation timer.  
Advantages of this form of ventilation include:  
1. Outside air is filtered before entering the building.  
2. Outside air will be dehumidified before entering if the UA-150H  
is running in dehumidification mode.  
3. Drawing air from outside and blowing inside aids in slightly  
pressurizing the structure. This helps prevent dirty and humid  
air from entering elsewhere. It also reduces the potential for  
carcinogenic radon gas to enter and provides make-up air for  
open combustion and exhaust devices like the clothes drier,  
fireplace, and water heater.  
4. Adequate exhaust fans are recommended in the bath rooms  
and kitchen.  
In cold climates or areas where the outdoor dew point is low  
at times, ventilation can be used to dehumidify the structure.  
This is accomplished by bringing the dry, low dew point air into  
the structure during these times. This approach is often more  
economical than running the dehumidifier to remove excess  
moisture from the structure. In cold climates, it is critical to  
adequately ventilate to reduce the inside moisture content to  
avoid moisture accumulating in the wall cavities. For example; in a  
house that experiences condensation on the interior surface of the  
windows during the winter, increasing the amount of ventilation will  
often cure the problem.  
much of the time or install a separate return from the open part of  
the house.  
If the structure in which the UA-150 is to be installed has an existing  
forced air HVAC system, utilize the HVAC system to make the UA-150  
installation easier.  
Basement Installation: Install a separate 10” return for the UA-150H  
in a central area of the structure. Duct the supply of the UA-150 to  
a 10” x 10” x 10” tee/damper that is 20% open to the basement.  
Duct the other side of the tee to the air supply of the existing HVAC  
system. Connect a duct from outside to the 6” collar of the UA-150  
if you wish to provide fresh make-up air.  
An insulated 6" diameter duct is generally sufficient to provide up  
to 125 CFM of outside air. Large quantities of outside air will impact  
UA-150H performance positively or negatively, depending upon  
the inside and outside air conditions. Consult the factory by calling  
1-800-533-7533 for recommendations regarding the use of higher  
flows with your specific application.  
Crawl Space Installation: Install a separate return for the UA-150H in  
a central area of the structure. Duct the supply of the UA-150H to a  
10” x 10” x 10” tee/damper that is 20% open to the crawl space if  
desired. Duct the other side of the tee to the air supply of the existing  
HVAC system. Connect an insulated duct from outside to the 6” collar  
of the UA-150H if you wish to provide optional fresh make-up air.  
The outside air duct should be connected to the 6” round collar on  
the filter enclosure of the unit. The 6” round collar includes a manual  
damper. Adjust the manual damper to provide the desired amount of  
fresh air for ventilation. The amount of fresh air should be based on  
the size and occupancy of the residence. If you are unsure of your  
ventilation air requirements, consult the factory by calling 1-800-  
533-7533 for assistance.  
6
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
3.4E Installation in an Attic with an  
Existing Forced Air HVAC System  
ALWAYS install a catch pan with a drain or float interrupt for  
condensate under the UA-150H in an attic or condensate may drip  
down on the ceiling of the living space below.  
3.5 Quiet Installation  
The compressor is attached to the cabinet with two cable ties to  
secure it during shipment. This rigid attachment is not necessary  
once the unit is installed and may cause noise from compressor  
vibration. After installation, cut the cable ties to free the compressor  
from the cabinet.  
Locate a separate return for the UA-150H in a central area of the  
structure. Duct the supply of the UA-150H to the air supply of the  
existing HVAC system Connect an insulated duct from outside to  
the 6” collar of the UA-150H if you wish to provide fresh make-up  
air. Adjust a damper in the duct to provide the desired amount of  
fresh air.  
REMOVE THE HORIZONTAL CABINET SUPPORT TO WHICH THE  
COMPRESSOR IS ATTACHED. The ends of the support are notched  
so that the support can easily be removed. Cut the strips of metal on  
each end and remove the support section from the cabinet. This will  
prevent the compressor from transmitting vibration to the cabinet.  
Make sure none of the compressor tubes are pressed against the  
cabinet or access panel. Check that the compressor tubes are  
centered in the holes where they pass through the drain pan.  
A length of 10 feet or more of acoustical flex ducting on the outlet of  
the UA-150H will reduce air noise from the impeller fan. A length of  
flexible ducting on all UA-150H duct connections is recommended  
to reduce noise and vibration transmitted to rigid ductwork in the  
structure.  
Install an external insulation kit.  
4. Controls  
The UA-150H can be equipped with various accessories to enhance  
its operation. A remote control panel must be used with the UA-  
150H. There are three remote control from which to choose. The  
humidity/fan control panel is used to control humidity and the  
impeller fan. Fresh air is introduced when the impeller fan operates.  
3.4F Installation in a Structure with  
Two Forced Air HVAC Systems  
Attach the UA-150H return to an independent return from the upper  
level. Attach the UA-150H supply to the supply of the basement  
HVAC system. This will promote circulation of air through the whole  
structure from the upper level to the lower level through the UA-  
150H. If the UA-150H is not connected to both HVAC systems, it  
will not control the humidity and ventilation of the entire structure.  
Connect an insulated duct from outside to the 6” collar of the UA-  
150H if you wish to provide fresh make-up air.  
Figure 1:  
Figure 2: Ventilation Timer  
and Humidity Control Panel  
Part No. 4024125  
Humidity/Fan Control Panel  
Part No. 4024155  
3.4G Installation in a Structure with No Existing Forced  
Air HVAC System  
When installing the UA-150H in a structure that does not have a  
forced air HVAC system, a single return for the UA-150H should be  
installed in central open area of the structure. DO NOT locate the  
return in a bathroom or a kitchen. The supply of the UA-150H should  
be located in the remote areas of the structure (such as bedrooms,  
den, etc..). By ducting this way, the air inside the structure will  
circulate through the UA-150H to be filtered and dehumidified. 4"  
diameter duct is recommended for branches to the bedrooms, 6"  
diameter duct is recommended for branches to larger areas. Refer to  
section 3.4B for branch duct sizing. Connect an insulated duct from  
outside to the 6” collar of the UA-150H if you wish to provide fresh  
make-up air.  
The impeller fan operates when dehumidifying or the fan switch  
is on. The ventilation timer and humidity control panel are used to  
control humidity, the impeller fan, and preset ventilation schedules.  
The quantity of fresh air should be 10 ft3/min of fresh air per person  
plus 1 ft3/min per 100 ft2 of floor space.  
4.1 Humidity/Fan Control Panel  
See Figure 1: The humidity/fan control panel automatically controls  
the humidity of the living space. The humidity/fan control panel  
contains an adjustable humidity control and a fan switch. This panel  
should be mounted in a central area of the structure where it can  
accurately sense the humidity of the air in the living space. The  
7
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
panel has a cover that must remain open to the air within the living  
space for accurate humidity sensing. Position the fan switch on  
when the home is occupied. The impeller fan blends fresh air with  
the inside air. It also filters and circulates the blended air throughout  
the home.  
4.4 Fan/Filter Switch  
Turning ON the fan/filter switch will cause the  
the UA-150H impeller fan to run continuously,  
whether the UA-150H is dehumidifying or not.  
This function is desirable if the unit is used  
for air circulation and filtration to achieve  
maximum indoor air quality. When the switch  
is ON; air will be constantly filtered through the  
UA-150H and circulated throughout the house.  
The humidity/fan control panel can be used in conjunction with the  
optional fresh air damper. When used with the optional fresh air  
damper, the fan/filter switch will act as a fresh air ventilation control.  
When the switch is ON (in this configuration), the impeller fan will  
run, the fresh air damper will open, and fresh air will be filtered  
and brought into the structure. When the switch is OFF, the fresh air  
damper will close and the impeller fan will operate only when the  
humidity control calls for dehumidification. Contact the factory for  
instructions on this type of installation.  
Figure 4  
Fan/Filter Switch  
When the switch is OFF the impeller fan will operate only when the  
humidity control calls for dehumidification or when the ventilation  
timer calls for ventilation.  
4.5 Ventilation Timer  
The ventilation timer controls the impeller fan and the motorized  
fresh air damper. When the ventilation timer is activated, the UA-  
150H will circulate the indoor air, and bring in fresh air from outside.  
The ventilation timer should be set for the required ventilation of the  
residence. The home should be ventilated with fresh air as suggested  
by applicable codes and standards. Minimally, ventilate when  
occupied by plus two people.  
4.2 Ventilation Timer and Humidity Control Panel  
See Figure 2: The ventilation timer and humidity control panel  
automatically controls both the ventilation and the humidity of  
the living space. The ventilation timer and humidity control panel  
contains an adjustable humidity control, a fan switch, and a  
ventilation timer. This panel will control the humidity and allow  
programmed ventilation of the living space. This panel works in  
conjunction with the optional fresh air damper to provide ventilation.  
The minimum fresh air ventilation schedule recommended is “on”  
when occupied two or more people.  
In cold climates or areas where the outdoor dew point is low at  
times, ventilation can be used to dehumidify the structure. This is  
accomplished by bringing the dry, low dew point air into the structure  
during these times. This approach is often more economical than  
running the dehumidifier to remove excess moisture from the  
structure. For example; in a house that experiences condensation  
on the interior surface of the windows during the winter, increasing  
the amount of ventilation will often cure the problem. To avoid  
condensation on windows and in walls, increase the ventilation  
rate and duration immediately. Call the factory for assistance if  
condensation is not eliminated.  
This panel should be mounted in a central area of the structure  
where it can accurately sense the humidity of the air in the living  
space. The panel has a cover that must remain open to the air within  
the living space for accurate humidity sensing.  
4.3 Humidity Control Adjustment  
Set the humidity control to the desired humidity  
level for the home. Turning the knob clockwise  
results in a drier setting. See the back of  
the control panel cover for set points. The  
dehumidifier will run continuously until the  
The ventilation timer is an electronic timer that displays the current  
time. This timer has a battery backup, so it will not require resetting  
after a power outage. Following a prolonged power outage the  
display of the timer will flash on and off indicating a power outage  
has occurred. The one-minute time increments of the ventilation  
timer allow you to program the ventilation of your home to fit your  
schedule.  
relative humidity (RH) is reduced to the humidity  
control dial setting. Setting the humidity control  
to lower RH levels will NOT increase the unit's  
dehumidification rate; the unit will simply run  
Figure 3:  
Humidity Control  
Adjustment Knob  
longer to reduce the area's RH to the setting. The UA-150H unit  
(and refrigerant-based dehumidifiers in general) will reduce a warm  
space's RH to a lower level than that of a cool space. It is therefore  
pointless to set the humidity control to excessively low levels in cool  
rooms; doing so will result in long periods of ineffective dehumidifier  
run time. Settings below 45% are not recommended.  
The ventilation timer has six programs with each program having  
one “on” and one “off” event. A program allows the user to turn the  
ventilation on at a certain day and time, then it allows them to turn  
the ventilation off at a certain day and time. Each of these programs  
can be repeated daily or weekly or during a specified block of days.  
All six of the programs operate independently of each other.  
Quality humidity meters are available from the factory and are  
recommended to accurately monitor humidity levels.  
8
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
If the timer fails to operate or operates erratically, check that the  
control panel receives 24Vac from the UA-150H. If 24Vac is present  
at the control panel, reset the timer by pressing the reset button at  
the bottom center of the timer face. The reset button is the small  
recessed button with an R beneath it located below the 1…7 and h  
buttons. Press the reset button in until the display clears. Release the  
reset button. The display will reappear as 00:00. Resetting the timer  
will clear the time and all program settings. After resetting the timer  
follow the instructions below to set the correct time and ventilation  
programs.  
Automatic or Manual Mode: The slide switch in the upper left of  
the timer is used to choose between automatic and manual operation  
of the timer relay. When the slide switch in the upper left of the timer  
is set to AUTO mode, the UA-150H will ventilate when the scheduled  
programs call for ventilation. When the slide switch in the upper left  
of the timer is set to manual (set to hand symbol on the right), the  
operation of the timer is controlled by the I/O button only. Pressing  
the I/O button will switch the ventilation timer between ON (detent)  
and OFF (detent). As you press the I/O button, “ON” or “OFF” will  
be displayed to the right of the time. The “ON” or “OFF” to the right  
of the time will indicate if the ventilation timer is on or off. The I/O  
button will manually override scheduled programs if the timer is in  
AUTO mode.  
Setting The Time: The following instructions explain how to set the  
ventilation timer. First, set the correct time on the timer by sliding the  
switch in the upper right hand corner of the timer to the clock symbol  
• and pressing the 1…7 (DAY), h (HOUR), and m (MINUTE) buttons.  
Remember that this timer operates on a 24-hour (military time) clock.  
4.6 Low Pressure Control  
If the low side refrigerant pressure drops to 15 PSIG, the low-  
pressure control opens and shuts off the compressor and impeller  
fan. It is an automatically reset control that will close when the  
pressure rises to 35 PSIG. Its primary function is to prevent damage  
to the compressor if a leak develops in the refrigeration system. It  
may also open if the unit is A) installed in a cool area (below 50 F)  
or B) installed where it is below 40 F and then started. Under these  
conditions, the unit will restart within several minutes. Until the unit  
warms up, it may repeat the cycle several times.  
Ventilation Schedule: Slide the switch in the upper right hand  
corner to the program symbol P. ON” will appear to the right of the  
time and the number “1” will appear in the lower right hand corner  
of the display. The “1” and “ON” signify the turn on time for the first  
program. Press the 1…7 button to choose the days of the week for  
this program. You can choose Mon.-Sun, Mon.-Fri., Sat-Sun, or any  
single day of the week. The days chosen are shown along the top  
of the display on the ventilation timer. Next press the h button to  
set the hour for the start of the ventilation period. Remember that  
this timer operates on a 24-hour clock. Then press the m button to  
set the minutes past the hour to start the ventilation. Now, with the  
ventilation start time set; press the I/O button. The word “OFF” should  
appear to the right of the time and the number “1” should remain in  
the lower right hand corner of the display. The “1” and “OFF” signify  
the turn off time for the first program. Set the turn off time using the  
1…7, h, and m buttons in the same way as described above and  
continue on to the second through sixth programs. When setting the  
ventilation programs, you can return to the current time display by  
sliding the switch in the upper right corner of the timer to RUN. The  
slide switch in the upper right must be set to RUN for the timer to  
operate with the scheduled programs.  
9
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ATTENTION INSTALLER  
WIRE THE UNIT AND CONTROL PACKAGE AS SHOWN IN THE DIAGRAM BELOW  
WARNING: DO NOT allow the yellow lead from the unit to contact the red lead or the white  
lead from the unit or damage to the transformers will result. Do not direct connect the white  
lead on the unit to the violet lead on the ventilation control or damage to the transformer will  
result.  
10  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
6. Align the back panel against these screws, pushing it forward,  
allowing it to slide downward to lock into position.  
7. Make the electrical connections to the terminals on theback  
panel as shown in the wiring diagram.  
5. (DEH 2000) DIGITAL CONTROL  
Installation Instructions  
8. Seal the hole around the wires to prevent air movement.  
9. Reconnect the quick connector onto the back panel.  
10. Reassemble the front to the back panel. Connect at the top  
first, then at the bottom.  
Figure 5:  
5.2B Wiring  
WARNING  
Warning: Do not allow the yellow lead from the Ultra-Aire  
to contact the red lead or orange lead from the Ultra-Aire or  
damage to the transformer will result.  
The installer must supply the wiring between the Ultra-Aire and  
the control panel. Be sure to safely route the control wires to  
prevent damage during installation. Be careful not to cross wires  
when connecting the Ultra-Aire and the remote control panel or  
damage to the transformer may result.  
5.1 Specifications  
Model: 4024539  
Electrical: 24 VAC  
Humidity Range: 20 – 90%  
RH Humidity Accuracy: +/- 4%  
Output: 3 Amps 24 VAC  
IMPORTANT  
The remote controls of the  
Ultra-Aire are powered by a  
low voltage circuit (24 VAC)  
and must NEVER contact or be  
connected to a high voltage  
circuit.  
5.2 Installation  
This control panel must be installed in the conditioned space and  
in accordance with all applicable codes and standards. Follow  
the instructions below when installing and setting this control.  
5.2A Install Instructions  
Some of the control wires may  
not be used with certain control  
panels and should be left safely  
disconnected with wire nuts  
taped onto the stripped ends. Be  
sure to consult the electrical  
schematic in this manual  
before making the control  
connections.  
1. Separate the front panel from the back panel by depressing  
the tongue located in the bottom of the control.  
Figure 6:  
2. Gently disconnect the quick connector on the back panel  
3. Remove the battery from the back panel by sliding it to the left  
and out from it’s retaining clip. To mount in the black battery  
holder on the front panel, insert it from the top, gently pressing  
downward until it snaps into place and is held under the top  
clip of the holder. The + engraved on the battery should be  
visible.  
Figure 7:  
4. Line the back panel up against the wall or flat surface onto  
which it is to be mounted and drill in the appropriate mounting  
holes  
5. Insert the screws so they extend approximately 1/8" from the  
wall or flat surface.  
11  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER AND HOMEOWNER  
• The word “CLOCK” appears at the top of the display during the  
clock display, along with the day and time.  
• The word “HUMIDITY” appears during the humidity display, with  
the current Set point on the left, and the ambient RH on the right.  
• The word “TEMP” appears as the unit displays the current  
temperature.  
• The fan status display is indicated by a capitol “F”. “OF” indicates  
fan off status, “on” indicates fan on status.  
• The damper display is indicated by a “d” with the same on/off  
status indicators as the temperature.  
• The ventilation program is displayed along the bottom of the  
display during the clock, humidity, and temperature displays only  
when the damper operation is set to the programmed setting “Pr”.  
WARNING  
5.3B Setting  
During the set-up process, if you make a mistake, you can always go  
back to adjust the settings. If you leave the control alone and don’t  
touch any buttons for 10 seconds, the control will remember any  
changes made and return to “home state.”  
Warning: Connecting the white wire to the control terminal  
without use of a motorized damper could create a short  
resulting in damage to the transformer.  
The white wire controls the motorized damper that can be installed  
into a fresh air duct. This provides the ability to control when fresh  
air is introduced into the building by using the ventilation timer  
function labeled “damper” on the control. If the motorized damper is  
not used, DO NOT CONNECT THE WHITE WIRE TO THE CONTROL  
OR DAMAGE TO THE TRANSFORMER MAY RESULT. Simply leave  
the white wire terminal (Y1) unused if the damper is not used.  
5.3C On/Off Setting  
Press the “ON/OFF” button to turn the system on or off. When the  
system is on, the green indicator will be lit. In the off mode, the  
controller continues the regular display sequence and indicates  
current time, temperature, and relative humidity. It also displays the  
status of the fan and damper as if the control were on, but the fan  
and damper will not operate unless the control is on and the green  
indicator is lit. Setup can be done with the control either on or off.  
5.2C Location  
Install the remote control panel in a central area of the structure  
where it will sense the relative humidity of the structure accurately.  
Do not install the control panel where it may not accurately sense  
the relative humidity such as near HVAC supply registers, near  
exterior doors and windows, or near a pool or spa.  
5.3D Setting Clock Time  
1. Push “CLOCK” button. The hour display will flash, use the “SET” +  
or – button to adjust hour. Notice the a.m./p.m. display.  
Figure 6: Setting clock time.  
2. Push “CLOCK” button again. The minute display will flash. Use the  
“+,–” buttons to adjust to the proper time.  
3. Push “CLOCK” button again. The day display will flash. Use the  
“+,–” buttons to select the proper day.  
4. Push “CLOCK” button again. The AM/PM display will flash. Verify  
AM/PM setting is correct.  
5. Push “CLOCK” button again, or wait a few seconds for the display  
to stop flashing. The time is now set.  
5.3 Operation  
5.3A Display  
When there is power to the control, the control display sequence will  
alternately show the clock, humidity, temperature, fan status, and  
fresh air damper status. The display sequence repeats continually,  
and is referred to as “home state”.  
12  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY AND HOMEOWNER  
“on” mode, the fan will run continuously. This does not effect the  
5.3E Setting Relative Humidity Set point  
dehumidification functions of the system. The system may or may  
not be ventilating or dehumidifying while the fan is running. Common  
reasons for operating the fan continuously are continuous filtration  
and air recirculation. With the fan in the “off” or “program” mode,  
the fan will operate only when needed by other functions of the  
system. The fan will remain off unless the system is dehumidifying  
and/or ventilating. The fan always runs during dehumidification, it  
also always runs during ventilation. To completely turn the system  
off, use the “ON/OFF” button as described earlier.  
The relative humidity Set point operates the dehumidifier function of  
the Ultra-Aire. It has no effect on any other function of the unit. The  
control senses the ambient relative humidity of the space in which  
it is located. The ambient condition is displayed on the right in the  
relative humidity display sequence, under the word “HUMIDITY”. The  
current Set point is displayed on the left, under the word “SET”.  
5.3H Damper Operation and Setting (Ventilation)  
The damper setting controls the ventilation function of the system.  
It has no control over the dehumidification function. In order to  
provide ventilation, the damper must be open (“on”) and the fan  
must be running. The controller takes care of these two functions  
automatically, so whenever the damper is open (“on”), the fan is  
running.  
If the Set point is equal to or greater than the current ambient  
condition, the space does not need to be dried, sothe dehumidifier  
function will be off. Example: Set point: 50%RH Current condition  
45% RH = Dehumidifier off, red “DEHU”indicator not lit.  
This is true even if the fan has been set to the “off” mode. The  
ventilation indicator will be lit whenever the unit is ventilating.  
If the Set point is less than the ambient condition, thedehumidifier  
will be on, and the red “DEHU” indicator will be lit. The space is more  
humid than the Set point, so the controller operates the dehumidifier  
to dry the space.Example: Set point: 50% RH Current condition: 55%  
RH =Dehumidifier on, red “DEHU” indicator lit.  
There are three damper operation modes, “on”, “off” (denoted by  
“OF”), and program (denoted by “Pr”). With the damper in the “on”  
mode, the damper will be open and the fan of the system will be  
operating in order to introduce fresh air into the space. Use this  
mode for continuous fresh air ventilation. The fan is always on when  
the damper is open. When in “off” mode, the damper will not open  
and the system will not ventilate.  
To set the relative humidity Set point, press the “HUM”button. The  
display will show the “HUMIDITY” display, and theword “SET” will  
flash. Use the “SET” + or – buttons to adjustthe relative humidity  
Set point as desired. Therma-Stor LLC recommends relative  
humidity levels of 45% in the summer,and lower levels in the  
winter. It is not recommended thehumidity Set point be set below  
35%. In order to dry thehome in the winter in a cold climate, use  
the ventilationfunction of the system rather than the dehumidifier  
function.  
When in the “program” mode, the control will operate the damper  
and fan (ventilate) according to the programmed ventilation schedule  
(see the section referring to programming the ventilation schedule).  
To select damper operation:  
1. Press the “DAMPER” button. The letter “d” will appear on the  
display, along with the current mode setting.  
5.3F Fan Setting and Operation  
Use the “FAN” button to adjust the fan operation. There are 3 choices  
for fan operation: “on”, “off” (denoted by “OF”), or program (denoted  
by “Pr”). To set operation,  
1. Press the “FAN” button. The display will indicate the current fan  
setting.  
2. Use the “SET” + or – buttons to adjust fan operation (“on”, “OF”’  
or “Pr”). Press the “FAN” button again or leave the unit alone for  
10 seconds to return to home state.  
2. Use the “SET” + or – buttons to adjust the fan setting to the  
desired mode (“on”, “OF”, or “Pr”).  
3. Press the “DAMPER” button again or leave the control alone for  
10 seconds to select the indicated damper mode and return to  
the home state.  
5.3G Fan On Fan Off Fan Program  
The fan display reading in the normal display sequence does not  
indicate the current fan setting, it indicates the current fan status,  
and will always read either on or off. With the fan in the  
13  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY AND HOMEOWNER  
6.3I Intermittent or Programmed Ventilation  
9. Pressing the “PROG” button again to move onto “program 2/stop”  
With the damper in program mode (denoted by “Pr” when setting the  
damper operation) the system will operate the ventilation function  
according to the current ventilation program.  
and begin the process again if setting the other programs. Follow  
the same procedure for each program.  
10. To end the program process simply leave the control alone (don’t  
push any buttons) for about 10 seconds. The unit will remember  
any changes and return to “home state”.  
There are 4 programs available for ventilation Monday through  
Friday. There are also 4 programs for Saturday and 4 programs  
for Sunday. No other choice of days is available. Each program  
to be used has an “on event” called “START” which brings the  
ventilation function on, and an “off event” called “STOP” which turns  
the function off. Each START and STOP must be entered in to the  
controller.  
5.3J Programming Notes  
To run the ventilation program, the damper mode must be in the  
“program” mode (“Pr”).  
The timer can be operated manually without changing the program  
by adjusting the damper mode from “program” to either “on” or  
“off”.  
To delete a program after it has been entered, adjust the program so  
the “START” and “STOP” times are identical.  
Occupants should determine ventilation times and rates. Therma-  
Stor LLC makes no firm recommendations concerning when to  
ventilate. Common ventilation schedules include constant ventilation,  
ventilation based on occupancy times, intermittent operation, and  
seasonal ventilation.  
Remember the control must be on for the unit to be functioning  
- make sure the green power indicator “ON” is lit.  
To set or adjust the ventilation program:  
5.3K Ventilating or Dehumidifying to Control Indoor  
Relative Humidity Levels  
1. Press the “PROG” button two times. The display will indicate  
“Program 1/start” at the bottom, and the hour display will flash.  
Fresh air ventilation may have a drying effect or a wetting effect on  
the indoor space, depending on the amount of moisture present in  
the outdoor air. Relative humidity is not a good indicator of outside  
humidity levels: use dew point measurements instead. Consider  
outside humidity levels when using the ventilation function of the  
dehumidifier.  
2. Use the “SET” + or – button to adjust the hour for the Program 1  
start time. Be sure to pay attention to the am/pm setting.  
3. Press the “PROG” button again. The display will indicate “Program  
1/start” at the bottom, and now the minute display will flash.  
4. Use the “SET” + or – buttons to adjust to the desired minute  
setting.  
5.3L Stop Start  
During summer in hot, humid climates operating in ventilation mode  
will increase the moisture load in the home.  
5. Press the “PROG” button again to move on to the “Program  
1/stop” event. The display will indicate “Program 1/stop” at the  
bottom, and the hour display will flash.  
Consider reducing the amount or frequency of fresh air ventilation if  
indoor humidity continues to be high.  
6. Use the “SET” + or – button to adjust the hour for the Program 1  
stop time. Be sure to pay attention to the am/pm setting.  
5.3M Low Pressure Control  
If the low side refrigerant pressure drops to 15 PSIG, the low-  
pressure control opens and shuts off the compressor and impeller  
fan. It is an automatically reset control. It will close when the  
refrigerant pressure rises to 35 PSIG. Its primary function is to  
prevent damage to the compressor if a leak develops in the  
refrigeration system. It may also open if the unit is A) installed in a  
cool area (below 50 F) or B) installed where it is below 40 F and then  
started. Under these conditions, the unit will restart within several  
minutes. Until the unit warms up, it may cycle several times.  
7. Press the “PROG” button again. The display will indicate “Program  
1/stop” at the bottom, and now the minute display will flash.  
8. Use the “SET” + or – buttons to adjust to the desired minute  
setting.  
14  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
6. Maintenance  
6.1 Standard Air Filter  
7. Service  
7.1 Warranty  
The UA-150H is equipped with a pleated cloth air filter. This filter  
should be checked every three months. Operating the unit with  
a dirty filter will reduce dehumidifier capacity and efficiency and  
may cause the compressor to cycle off and on unnecessarily on the  
defrost control.  
A warranty certificate has been enclosed with this unit; read it  
before any repair is initiated. If a warranty repair is required, call the  
factory first at 1-800-533-7533 for warranty claim authorization and  
technical assistance.  
7.2 Technical Description  
To access the air filter, remove the filter access panel from the end  
of the UA-150H by unscrewing the two thumbscrews and sliding the  
panel to the left until it is free from underneath the side panel. The  
filter(s) should be readily visible and can be removed by pulling them  
straight out of the UA-150H.  
The UA-150H uses a refrigeration system similar to an air  
conditioner's to remove heat and moisture from incoming air, and  
add heat to the air that is discharged (See Figure 15).  
Hot, high-pressure refrigerant gas is routed from the compressor  
to the condenser coil (See Figure 3). The refrigerant is cooled  
and condensed by giving up its heat to the air that is about to be  
discharged from the unit. The refrigerant liquid then passes through  
a filter/drier and capillary tubing which causes the refrigerant  
pressure and temperature to drop. It next enters the evaporator coil  
where it absorbs heat from the incoming air and evaporates. The  
evaporator operates in a flooded condition, which means that all the  
evaporator tubes contain liquid refrigerant during normal operation.  
A flooded evaporator should maintain nearly constant pressure and  
temperature across the entire coil, from inlet to outlet.  
The pleated cloth filter can generally be vacuumed clean several  
times before needing replacement. Replacement filters can be  
ordered from the factory or purchased locally if available. DO NOT  
operate the unit without the standard filter or with a less effective  
filter than the standard filter. The heat exchange coils inside the unit  
could become clogged and require disassembly to clean.  
6.2 High Efficiency Air Filter  
An optional high efficiency pleated microglass paper filter is  
available for the UA-150H. This filter is rated as 90%-95% efficient  
by the ASHRAE Dust Spot test method 52-76. The high efficiency  
pleated microglass paper filter should be used in conjunction with  
the standard filter, and placed directly behind the standard filter.  
The mixture of gas and liquid refrigerant enter the accumulator  
after leaving the evaporator coil. The accumulator prevents any  
liquid refrigerant from reaching the compressor. The compressor  
evacuates the cool refrigerant gas from the accumulator and  
compresses it to a high pressure and temperature to repeat the  
process.  
This filter is able to remove allergy-causing particles from the  
airstream. Check the high efficiency air filter every two years and  
replace if necessary. The high efficiency filter has a much larger  
surface area than the standard filter, thus the standard filter may  
need to be cleaned or replaced several times before the high  
efficiency filter requires replacement. Be careful not to damage the  
fabric media when handling the high efficiency pleated paper filter.  
Do not attempt to clean the high efficiency pleated paper filter. It  
should be replaced when it becomes restrictive (See Figure 7).  
6.3 Impeller Fan Oiling  
The impeller fan motor is factory lubricated for many years of normal  
operation, and no further oiling is required.  
6.4 Optional Fresh Air Return  
Check and clean the screen on the outdoor fresh air return  
seasonally. The screen may become plugged during the seasons  
when there are many particles in the outdoor air.  
Figure 15: Refrigeration System of UA-150H  
15  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
Evaporator coil frosted continuously, low dehumidifying  
capacity.  
7.3 Troubleshooting  
No dehumidification, neither impeller fan nor compressor run  
with fan switch and ventilation timer OFF.  
1. Unit unplugged or no power to outlet.  
2. Humidity control set too high or defective  
(Sec. 3.3 & 5.7A)  
1. Defrost thermostat loose or defective (Sec. 5.8).  
2. Low refrigerant charge  
3. Dirty air filter(s) or airflow restricted.  
4. Excessively restrictive ducting connected to unit.  
3. Loose connection in internal or control wiring.  
4. Defective Compressor relay.  
5. Defective control transformer.  
6. Low pressure Control open (Sec 3.7 & 5.10).  
7. Optional Condensate Pump Safety Switch open (Sec 5.11).  
Unit not providing ventilation. Ventilation timer not operating  
correctly.  
1. If timer is not functioning correctly reset timer and reprogram  
(Sec. 3.5).  
2. Check control wire connections (check  
connections at fresh air damper also).  
3. Defective fresh air damper (Sec. 5.9).  
4. Defective fan switch.  
No dehumidification, compressor does not run but impeller fan  
runs with fan switch and ventilation timer OFF and humidity  
control turned to ON.  
1. Defective compressor run capacitor (Sec. 5.6).  
2. Bad connection in compressor circuit  
(See Fig. 4).  
3. Defective compressor overload (Sec. 5.6A).  
4. Defective compressor (Sec. 5.6).  
Unit removes some water, but not as much as expected.  
1. Air temperature and/or humidity have dropped.  
2. Humidity meter and or thermometer used are out of calibration.  
3. Unit has entered defrost cycle (Sec. 5.8).  
4. Air filter dirty (Sec. 4.1 & 4.2).  
5. Defrost thermostat open (Sec. 5.8).  
5. Defective defrost thermostat (Sec 5.8).  
6. Low refrigerant charge (Sec. 5.4).  
7. Air leak such as loose cover or ducting leaks.  
8. Defective compressor (Sec. 5.6).  
9. Restrictive ducting (Sec. 2.4).  
10.Optional Condensate Pump Safety Switch open (Sec 5.11).  
Impeller fan runs with fan switch and ventilation timer OFF, but  
compressor cycles on & off.  
1. Low ambient temperature and/or humidity causing unit to  
cycle through defrost mode.  
2. Defective compressor overload (Sec. 5.6A).  
3. Defective compressor (Sec. 5.6).  
4. Defrost thermostat defective (Sec. 5.8).  
5. Dirty air filter(s) or airflow restricted.  
6. Low refrigerant charge, causing defrost control to cycle.  
7. Bad connection in compressor circuit.  
Unit Test to determine problem:  
1. Detach field control wiring connections from main unit.  
2. Connect the yellow and green pigtails from the main unit  
together; only the impeller fan should run. Disconnect the  
wires.  
3. Connect the yellow and blue pigtails from the main unit  
together; the compressor and impeller fan should run.  
4. If these tests work, the main unit is working properly. You  
should check the control panel and field control wiring for  
problems next.  
5. Remove the control panel from the mounting box and detach  
it from the field installed control wiring. Connect the blue,  
yellow, and green wires from the control panel directly to the  
corresponding colored pigtails on the main unit. Leave the  
violet, white and red wires disconnected!  
Impeller fan does not run with fan switch in either position.  
Impeller fan does not run with ventilation timer activated.  
Compressor runs briefly but cycles on & off with humidity  
control turned to ON.  
1. Loose connection in impeller fan circuit (See Fig. 4).  
2. Obstruction prevents impeller fan rotation.  
3. Defective impeller fan.  
4. Defective impeller fan relay.  
5. Defective impeller fan capacitor.  
6. Turn on the fan switch; the impeller fan should run. Turn off the  
fan switch.  
Impeller fan runs with fan switch ON. Impeller fan does not run  
with ventilation timer activated.  
7. Turn on the humidity control; the compressor and impeller fan  
should run.  
8. If these tests work, the problem is most likely in the field  
control wiring.  
1. Defective ventilation timer.  
2. Time not correct on ventilation timer.  
3. Ventilation timer set to manual & switched OFF.  
4. Defective fan switch.  
16  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
5. Compressor terminals C and R: No continuity indicates an open  
run winding. The compressor must be replaced. Normal run  
winding resistance is .5 to 2 ohms.  
6. Compressor terminal C and overload terminal 1: No continuity  
indicates a defective overload lead.  
7. Overload terminals 1 and 3: If there is no continuity, the  
overload may be tripped. Wait 10 minutes and try again. If  
there is still no continuity, it is defective and must be replaced.  
8. Compressor terminal C and compressor case: Continuity  
indicates a grounded motor. The compressor must be replaced.  
9. Disconnect the wires from the run capacitor. Set the ohmmeter  
to the Rx1 scale. The capacitor is shorted and must be  
replaced if continuity exists across its terminals. If there is no  
needle movement with the meter set on the Rx100000 scale,  
the capacitor is open and must be replaced.  
10. Reconnect the wires to the compressor and capacitor. Plug in  
and turn on the unit. If the compressor fails to start, replace  
the run capacitor.  
11. If the unit still does not start, adding a hard-start kit (relay &  
capacitor) will provide greater starting torque. If this doesn't  
work, the compressor has an internal mechanical defect and  
must be replaced.  
7.4 Refrigerant Charging  
If the refrigerant charge is lost due to service or a leak, a new charge  
must be accurately weighed in. If any of the old charge is left in the  
system, it must be recovered before weighing in the new charge.  
Refer to the unit nameplate for the correct charge weight and  
refrigerant type.  
7.5 Impeller Fan Replacement  
The motorized impeller fan is a unitary assembly consisting of the  
motor and impeller fan. If defective, the complete assembly must be  
replaced.  
1. Unplug the power cord.  
2. Remove the cabinet access panel.  
3. Remove the screw attaching the impeller fan support bracket  
to the base.  
4. Disconnect the impeller fan leads inside the electric box.  
5. Push up on the inlet ring and pull the impeller fan and impeller  
fan support bracket to the right.  
6. Align the bracket with the two notches in the front flange of the  
base (behind the foam).  
7. Slide the impeller fan assembly from the unit.  
8. Remove the defective impeller fan from the bracket and  
replace with it with the new impeller fan.  
7.6B Replacing a Burned Out Compressor  
9. Reassemble the new impeller fan by reversing the above  
procedure. Note: There are two pins on the backside of the  
cabinet that must align with the two holes in the impeller fan  
support bracket.  
The refrigerant and oil mixture in a compressor is chemically  
very stable under normal operating conditions. However, when an  
electrical short occurs in the compressor motor, the resulting high  
temperature arc causes a portion of the refrigerant oil mixture to  
break down into carbonaceous sludge, a very corrosive acid, and  
water. These contaminants must be carefully removed otherwise  
even small residues will attack replacement compressor motors and  
cause failures.  
7.6 Compressor/Capacitor Replacement  
This compressor is equipped with a two terminal external overload  
and a run capacitor, but no start capacitor or relay (See Figure 4).  
7.6A Checking Compressor Motor Circuits  
Perform the following tests if the impeller fan runs but the  
compressor does not with the fan switch and ventilation timer OFF  
and the humidity control ON.  
The following procedure is effective only if the system is monitored  
after replacing the compressor to insure that the clean up was  
complete.  
1. This procedure assumes that the previously listed compressor  
motor circuit tests revealed a shorted or open winding.  
2. Remove and properly dispose of the system charge. DO NOT  
vent the refrigerant or allow it to contact your eyes or skin.  
3. Remove the burned out compressor. Use rubber gloves if there  
is any possibility of contacting the oil or sludge.  
4. To facilitate subsequent steps, determine the type of burn  
out that occurred. If the discharge line shows no evidence  
of sludge and the suction line is also clean or perhaps has  
some light carbon deposits, the burn out occurred while the  
compressor was not rotating. Contaminants are therefore  
largely confined to the compressor housing. A single  
installation of liquid and suction line filter/driers will probably  
clean up the system.  
1. Unplug the unit; remove the cabinet side and the electrical  
connection cover on the compressor top.  
2. Plug in the unit and turn the humidity control to ON. Check for  
110 volts from compressor terminal R to overload terminal 3  
using an AC voltmeter. If voltage is present, go to step 3. If no  
voltage, there may be a loose connection in the compressor  
circuit. Test each component for continuity. See the appropriate  
section if a defect is suspected.  
3. Unplug the unit, and then disconnect the red and yellow wires  
from compressor terminals R & S. Using an ohmmeter check  
continuity between the points listed below.  
4. Compressor terminals C and S: No continuity indicates an open  
start winding. The compressor must be replaced. Normal start  
winding resistance is 3 to 7 ohms.  
17  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
If sludge is evident in the discharge line, it will likely be found in the  
suction line. This indicates the compressor burned out will running.  
Sludge and acid have been pumped throughout the system. Several  
changes of the liquid and suction filter/driers will probably be  
necessary to cleanse the system.  
(see back of control panel cover). ). If it still does not run, remove the  
stop screw from the panel and turn the knob farther. If it then runs,  
the humidity control is out of calibration or the RH is below 40%.  
The UA-150H is equipped with an automatic defrost mechanism.  
If the UA-150H operates in conditions that develop frost on the  
evaporator, it will sense the frost build-up and automatically defrost  
the evaporator. The UA-150H may not appear to be operating  
correctly during the defrost sequence, but once the defrost sequence  
is completed, the UA-150H will resume dehumidifying.  
5. Correct the system fault that caused the burn out. Consult the  
factory for advice.  
6. Install the replacement compressor with a new capacitor and  
an oversized liquid line filter.  
7.7B Programmable Ventilation Timer  
In a running burn out, install an oversized suction line filter/drier  
between the accumulator and compressor. Thoroughly flush the  
accumulator with refrigerant to remove all trapped sludge and to  
prevent the oil hole from becoming plugged. A standing burn out  
does not require a suction line filter/drier.  
The ventilation timer controls the impeller fan and the motorized  
fresh air damper. When the ventilation timer is activated, the UA-  
150H will circulate the indoor air, and bring in fresh air from outside.  
The ventilation timer should be set for the required ventilation of  
the residence. The home should be ventilated with fresh air as  
suggested by applicable codes and standards.  
7. Evacuate the system with a good vacuum pump and accurate  
vacuum gauge. Leave the pump on the system for at least an  
hour.  
8. Operate the system for a short period of time, monitoring the  
suction pressure to determine that the suction filter is not  
becoming plugged. Replace the suction filter/drier if pressure  
drop occurs. If a severe running burn out has occurred, several  
filter/driers may have to be replaced to remove all of the acid  
and moisture.  
If the UA-150H fails to ventilate as expected, check that the time on  
the timer is correct. For the timer to carry out the program schedule,  
the slide switch in the upper left corner on the timer must be set to  
“AUTO”. The slide switch in the upper right corner of the UA-150H  
must be set to “RUN”. Also check the programs on the timer to be  
sure that the timer is calling for ventilation at the correct times. If  
the timer fails to operate or operates erratically, reset the timer; see  
section 4.5 of this manual.  
NOTE: NEVER use the compressor to evacuate the system or any  
part of it.  
7.8 Defrost Thermostat  
The defrost thermostat is attached to the refrigerant suction tube  
between the accumulator and the compressor. It will automatically  
shut the compressor off if the low side refrigerant temperature drops  
due to excessive frost formation on the evaporator coil. The impeller  
fan will continue to run, causing air to flow through the evaporator  
coil and melt the ice. When the ice has melted, the evaporator  
temperature will rise and the thermostat will restart the compressor.  
7.6C Replacing a Compressor, Nonburn Out  
Remove the refrigerant from the system. Replace the compressor  
and liquid line filter/drier. Charge the system to 50 PSIG and check  
for leaks. Remove the charge and weigh in the refrigerant quantity  
listed on the nameplate. Operate the system to verify performance.  
7.7 Remote Controls  
7.9 Electric Ventilation Damper  
The UA-150H is controlled by devices mounted on a panel that is  
remote from the unit. You may or may not have the devices listed  
below depending on the model of the remote control panel you  
purchased. If the UA-150H fails to operate as desired, always check  
the settings of the controls to insure that they are correct. Check  
that the controls are receiving 24Vac from the UA-150H. Check the  
connections between the UA-150H, the control panel, and the field  
control wiring.  
The electric ventilation damper is controlled by the ventilation timer.  
The damper will open when the ventilation timer is activated to  
allow fresh air into the structure through the 6” diameter fresh air  
inlet duct. The electric ventilation damper will remain closed when  
the ventilation timer is not activated to prevent over-ventilating the  
structure when the unit is dehumidifying or recirculating the indoor air.  
The electric ventilation timer operates on 24 Vac from the control  
circuit. DO NOT connect high voltage to the damper motor or  
damage to the motor may result. DO NOT force the blade of the  
damper by hand or damage to the damper motor may result.  
7.7A Humidity Control  
The humidity control is an adjustable switch that closes when the  
relative humidity of the air in which it is located rises to the dial set  
point. It opens when the RH drops 4 to 6% below the set point. If the  
UA-150H does not run, try turning the humidity control clockwise  
until it reaches the stop and the knob pointer points at “Max Dry”  
The damper opens in one direction only. The damper rotates very  
slowly, allow sufficient time for the damper to cycle. The damper will  
take approximately 1 minute to cycle from closed to open or from  
open to closed.  
18  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
If the electric ventilation damper fails to operate:  
1. Check that the wiring is correct and that voltage is present at  
the damper motor.  
7.11 Condensate Pump Kit  
An optional condensate pump kit is available from the factory for use  
with the UA-150H. Condensate is automatically pumped to a remote  
location when the water level in the pump's reservoir rises to close  
the float switch.  
2. Check for any obstruction inside the damper. If the electric  
ventilation damper fails to operate after performing these  
checks, it must be replaced.  
The pump also contains a safety float switch. The white leads from  
this switch extend from beneath the pump cover. This switch should  
be installed in series with the field wire that connects the blue (#5)  
lead from the UA150H to the blue (#5) lead on the control panel.  
7.10 Low Pressure Control  
If the low side refrigerant pressure drops to 15 PSIG, the low-  
pressure control opens and shuts off the compressor and impeller  
fan. It is an automatically reset control. It will close when the  
refrigerant pressure rises to 35 PSIG. Its primary function is to  
prevent damage to the compressor if a leak develops in the  
refrigeration system. It may also open if the unit is A) installed in a  
cool area (below 50 F) or B) installed where it is below 40 F and then  
started. Under these conditions, the unit will restart within several  
minutes. Until the unit warms up, it may cycle several times.  
If the pump fails, this switch opens the compressor control circuit  
and stops water production before the reservoir overflows. The UA-  
150H will continue to ventilate or circulate air as normal, but will not  
dehumidify until this switch closes.  
Electric Schematics of the UA-150H  
19  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
Pictorial Electrical Diagrams of UA-150H  
20  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
Wiring Diagrams  
21  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE PARTS LIST: UA-150H  
ITEM  
PART NO.  
4024369  
4017777  
4023645  
QTY.  
1
2
DESCRIPTION  
Air Filter, Pleated Cloth  
1
2
3
Capillary Tube, .059" X .124" X 32.00" (not shown)  
Compressor Service Kit, Carlyle (EBA120111A)  
(Includes Compressor, Capacitor & Overload)  
Compressor Overload (EBA120111A) (not shown)  
Compressor Relay, SPST, 24 Vac, 30A  
Compressor Run Capacitor, 30 MFD  
Condenser Coil  
Defrost Thermostat,  
Defrost Thermostat Mounting Clip, (item 8) (not shown)  
Evaporator Coil  
1
4
5
6
7
8
4022595  
4022484  
4022740  
4022563  
4021470  
4021648  
4022557  
4024270  
4020924  
4024360  
4025087  
4021626  
4024368  
4023928  
4022219  
4021332  
4022487  
4024359  
40218181  
4024365  
4024361  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
Impeller Fan  
Impeller Fan Relay, SPDT, 24 Vac, 15A  
Impeller Fan Run Capacitor, 16MFD  
Filter/Drier  
Hose, Drain Pan, .56” ID x 8'  
Inlet Collar, 10” Galvanized Steel  
Inlet Collar, 6” Galvanized Steel with Damper  
Low Pressure Control  
Outlet Collar, 10” Galvanized Steel  
Transformer, 120/24 Vac, 40 VA  
Wiring Diagram (Not shown. See page 21)  
Accumulator (not shown)  
Cord/Wire Harness (not shown)  
Wire Harness, Lo V (not shown)  
The UA-150H  
22  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL PARTS LIST: UA-150H  
ITEM  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
PART NO.  
4024370  
4024375  
4022220  
4024155  
4024125  
4023660  
4023672  
4024153  
4021495  
4024150  
4024122  
4025560  
4022486  
4024377  
4024431  
QTY.  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
DESCRIPTION  
Air Filter, High Efficiency, Pleated Microglass Paper, 90%-95%  
Check Damper, 10" Diameter (not shown)  
Condensate Pump Kit, External  
Control Panel Assembly, Humidity/Fan  
Control Panel Assembly, Ventilation Timer & Humidity  
Controller, Humidity  
Duct Damper, 6” Diameter, Electrically Actuated (not shown)  
Cover for Items 28 & 29 (not shown)  
Knob, Black, .25” shaft  
Instructions, Humidity/Fan (not shown)  
Instructions, Ventilation Timer & Humidity (not shown)  
Switch, Black, SPDT, On/Off  
Timer, 7-Day, 24 Vac, Programmable  
Optional External Insulation Kit (not shown)  
Vibration Kit,150H Series (not shown)  
Accessories  
23  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VIBRATION ISOLATION KIT: UA-150H  
INSTRUCTIONS FOR ASSEMBLING THE VIBRATION ISOLATORS TO THE 150H  
1. Lift one end of the UA-150H at least 12” off the floor.  
2. Slide (2) of the nuts over each screw.  
3. Attach the screws (with nuts) to the holes located in the bottom corners of the UA-150H.  
4. Slide the grommet over the screw and nuts assembly.  
5. Repeat for the other end of the UA-150H.  
24  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXTERNAL INSULATION KIT: UA-150H  
Install the insulation kit as shown in the illustration below. After  
INSTRUCTIONS FOR APPLYING  
THE INSULATION TO THE UA-150H  
The UA-150H must be clean, dry and at room temperature to apply  
the insulation kit. The insulation has a pressure sensitive adhesive  
with release paper applied to one side. To apply the insulation,  
remove the release paper and press the sheet firmly against the  
UA-150H. Apply insulation before installing the UA-150H if possible,  
as this is the easiest time to install the insulation kit.  
installing the insulation, cut out the holes for the supply and return  
connections and cut the seam around the removable front cover so  
it can be removed easily. If more insulation is needed two or more  
insulation kits may be applied to a single UA-150H.  
The dimensions below each location represent the size of the individual insulation pieces.  
25  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ATTENTION INSTALLER  
26  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ULTRA-AIRE 150H Dehumidifier Limited Warranty  
from misuse, abuse, lack of normal care, corrosion,  
freezing, tampering, modification, unauthorized or  
improper repair or installation, accident, acts of  
nature or any other cause beyond Therma-Stor  
LLC's reasonable control.  
WARRANTOR:  
Therma-Stor LLC  
PO Box 8680  
Madison, WI 53708  
Telephone: 1-800-533-7533  
WHO IS COVERED: This warranty extends only to  
the original residential end-user of the Ultra-Aire  
150H dehumidifier, and may not be assigned or  
transferred.  
LIMITATIONS AND EXCLUSIONS: If any Ultra-Aire  
150H Dehumidifier part is repaired or replaced, the  
new part shall be warranted for only the remainder  
of the original warranty period applicable thereto  
(but all warranty periods will be extended by the  
period of time, if any, that the Ultra-Aire 150H  
Dehumidifier is out of service while awaiting  
covered warranty service).  
FIRST YEAR WARRANTY: Therma-Stor LLC  
warrants that, for one (1) year the Ultra-Aire 150H  
dehumidifier will operate free from any defects in  
materials and workmanship, or Therma-Stor LLC  
will, at its option, repair or replace the defective  
part(s), free of any charge.  
UPONTHEEXPIRATIONOFTHEWRITTENWARRANTY  
APPLICABLE TO THE ULTRA-AIRE DEHUMIDIFIER  
OR ANY PART THEREOF, ALL OTHER WARRANTIES  
IMPLIED BY LAW, INCLUDING MERCHANTABILITY  
AND FITNESS FOR A PARTICULAR PURPOSE,  
SHALL ALSO EXPIRE. ALL WARRANTIES MADE  
BY THERMA-STOR LLC ARE SET FORTH HEREIN,  
AND NO CLAIM MAY BE MADE AGAINST THERMA-  
STOR LLC BASED ON ANY ORAL WARRANTY. IN NO  
EVENT SHALL THERMA-STOR LLC, IN CONNECTION  
WITH THE SALE, INSTALLATION, USE, REPAIR OR  
REPLACEMENT OF ANY ULTRA-AIRE DEHUMIDIFIER  
OR PART THEREOF BE LIABLE UNDER ANY  
LEGAL THEORY FOR ANY SPECIAL, INDIRECT OR  
CONSEQUENTIAL DAMAGES INCLUDING WITHOUT  
LIMITATION WATER DAMAGE (THE END-USER  
SHOULDTAKEPRECAUTIONSAGAINSTSAME),LOST  
PROFITS, DELAY, OR LOSS OF USE OR DAMAGE TO  
ANY REAL OR PERSONAL PROPERTY.  
SECOND THROUGH FIFTH YEAR WARRANTY:  
Therma-Stor LLC further warrants that for a period  
of five (5) years, the condenser, evaporator, and  
compressor of the Ultra-Aire 150H dehumidifier  
will operate free of any defects in material or  
workmanship, or Therma-Stor LLC, at its option,  
will repair or replace the defective part(s), provided  
that all labor and transportation charges for the  
part(s) shall be borne by the end-user.  
END-USER RESPONSIBILITIES: Warranty service  
must be performed by a Servicer authorized by  
Therma-Stor LLC. If the end-user is unable to locate  
or obtain warranty service from an authorized  
Servicer, he should call Therma-Stor LLC at the  
above number and ask for the Therma-Stor LLC  
Service Department, which will then arrange for  
covered warranty service. Warranty service will be  
performed during normal working hours.  
Some states do not allow limitations on how long an  
implied warranty lasts, and some do not allow the  
exclusion or limitation of incidental or consequential  
damages, so one or both of these limitation may not  
apply to you.  
The End-user must present proof of purchase  
(lease) upon request, by use of the warranty card  
or other reasonable and reliable means. The end-  
user is responsible for normal care. This warranty  
only applies to residential applications and does  
not cover any defect, malfunction, etc. resulting  
LEGAL RIGHTS: This warranty gives you specific  
legal rights, and you may also have other rights  
which vary from state to state.  
27  
Ultra-Aire 150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Information in this document is subject to change without notice. No part of  
this document may be reproduced or transmitted in any form or by any means,  
electronic or mechanical, for any purpose, without the express written permission  
of Therma-Stor LLC. © 2006 Therma-Stor LLC. All rights reserved.  
PO Box 8680 • Madison, WI 53708  
Phone: 608-222-5301 • Fax: 608-222-1447  
Download from Www.Somanuals.com. All Manuals Search And Download.  

The Singing Machine CD Player SMVG 600 User Manual
Tiffen Carrying Case F 8 User Manual
Timex Watch W260 User Manual
TOA Electronics Portable Speaker F 2000B User Manual
Triarch Indoor Furnishings MR29230 User Manual
Tricity Bendix Kitchen Entertainment Center EG 205 User Manual
Universal Remote Control Universal Remote R6 User Manual
Vizio Car Satellite TV System E4011 A2 User Manual
Walker Indoor Furnishings W42C77BL User Manual
Walker Indoor Furnishings W44COSBL User Manual