State Industries Water Heater 185244 004 User Manual

Instruction Manual  
RESIDENTIAL GAS WATER HEATERS  
POWER VENTED GAS MODELS WITH HOT SURFACE IGNITION  
NOT FOR USE IN MANUFACTURED (MOBILE) HOMES  
500 Tennessee Waltz Parkway  
Ashland City, TN 37015  
GAMA certification applies  
to all residential gas water  
heaters with capacities of 20  
to 100 gallons with input rating  
of 75,000 BTU/Hr. or less.  
For Your Safety •  
AN ODORANT IS ADDED TO THE GAS USED  
BY THIS WATER HEATER.  
ALL TECHNICAL AND WARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS  
PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER.  
KEEP THIS MANUAL IN THE POCKET ON HEATER FOR FUTURE REFERENCE  
WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED.  
PRINTED 1208  
315466-000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL SAFETY  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
SAFE INSTALLATION, USE AND SERVICE............................2  
GENERAL SAFETY..................................................................3  
TABLE OF CONTENTS............................................................4  
INTRODUCTION......................................................................4  
Preparing for the New Installation.....................................4  
INSTALLATION REQUIREMENTS FOR THE  
TEMPERATURE REGULATION ............................................22  
FOR YOUR INFORMATION...................................................23  
Start Up Conditions.........................................................23  
Condensate.....................................................................23  
Smoke/Odor....................................................................23  
Thermal Expansion.........................................................23  
Strange Sounds..............................................................23  
Operational Conditions ...................................................23  
Smelly Water...................................................................23  
“Air” in Hot Water Faucets ..............................................23  
High Temperature Shut Off System ................................23  
PERIODIC MAINTENANCE...................................................24  
Venting System Inspection..............................................24  
Burner Inspection............................................................24  
Burner Cleaning..............................................................24  
Housekeeping........................................................... 24-25  
Anode Rod Inspection.....................................................25  
Temperature-Pressure Relief Valve Operation ...............25  
Draining...........................................................................25  
Drain Valve Washer Replacement............................ 25-26  
Service............................................................................26  
LEAKAGE CHECKPOINTS....................................................26  
REPAIR PARTS......................................................................27  
TROUBLESHOOTING ..................................................... 28-30  
WARRANTY...........................................................................31  
COMMONWEALTH OF MASSACHUSETTS...........................5  
TYPICAL INSTALLATION..................................................... 6-7  
LOCATING THE NEW WATER HEATER.................................8  
Facts to Consider About Location................................. 8-9  
Insulation Blankets............................................................9  
Combustion Air and Ventilation for Appliances  
Located in Unconned Spaces.........................................9  
Combustion Air and Ventilation for Appliances  
Located in Conned Spaces....................................... 9-10  
INSTALLING THE WATER HEATER......................................11  
Water Piping ..............................................................11-12  
Temperature-Pressure Relief Valve ................................12  
Gas Piping ......................................................................13  
Sediment Traps...............................................................14  
Blower Assembly Installation ..........................................14  
Vent Pipe Connection to Blower Assembly.....................15  
Venting and Installation............................................. 15-16  
LIGHTING & OPERATING LABEL.........................................21  
INTRODUCTION  
Thank You for purchasing this water heater. Properly installed and  
maintained, it should give you years of trouble free service.  
2. The installation must conform with these instructions and the local  
code authority having jurisdiction. In the absence of local codes,  
installations shall comply with the National Fuel Gas Code ANSI  
Z223.1/NFPA 54 and the National Electrical Code, NFPA 70.  
These publications are available from The National Fire Protection  
Association, 1 Batterymarch Park, Quincy, MA 02269.  
Abbreviations Found In This Instruction Manual:  
• CSA - Canadian Standards Association  
• ANSI - American National Standards Institute  
• NFPA - National Fire Protection Association  
• ASME - American Society of Mechanical Engineers  
• GAMA - Gas Appliance Manufacturer’s Association  
• UL - Underwriters Laboratories Inc.  
3. The water heater when installed must be grounded in accordance  
with the local codes, or in the absence of local codes: In the United  
States, the National Electrical Code. ANSI/NFPA 70.  
4. If after reading this manual you have any questions or do not  
understand any portion of the instructions, call the local gas utility  
or the manufacturer whose name appears on the rating plate.  
This gas-fired water heater is design certified by Underwriters  
Laboratories Inc. underAmerican National Standard/CSAStandard for  
Gas Water Heaters ANSI Z21.10.1 • CSA 4.1 (current edition).  
5. Carefully plan the place where you are going to put the water heater.  
Correct combustion, vent action, and vent pipe installation are  
very important in preventing death from possible carbon monoxide  
poisoning and res, see Figures 1 and 2.  
PREPARING FOR THE INSTALLATION  
Examine the location to ensure the water heater complies with the  
“Locating the New Water Heater” section in this manual.  
1. Read the “General Safety” section, page 3 of this manual rst and  
then the entire manual carefully. If you don’t follow the safety rules,  
the water heater will not operate properly. It could cause DEATH,  
SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE.  
6. For California installation this water heater must be braced,  
anchored, or strapped to avoid falling or moving during an  
earthquake. See instructions for correct installation procedures.  
Instructions may be obtained from California Ofce of the State  
Architect, 400 P Street, Sacramento, CA 95814.  
This manual contains instructions for the installation, operation,  
and maintenance of the gas-red water heater. It also contains  
warnings throughout the manual that you must read and be aware  
of. All warnings and all instructions are essential to the proper  
operation of the water heater and your safety. Since we cannot put  
everything on the rst few pages, READ THE ENTIRE MANUAL  
BEFOREATTEMPTING TO INSTALL OR OPERATE THE WATER  
HEATER.  
7. Massachusetts Code requires this water heater to be installed in  
accordance with Massachusetts 248-CMR 2.00: State Plumbing  
Code and 248-CMR 5.00. For more information see next page.  
8. Complies with SCAQMD rule #1121 and districts having equivalent  
NOx requirements.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS  
For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed  
in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by  
the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above nished grade in the  
area of the venting, including but not limited to decks and porches, the following requirements shall be satised:  
INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas  
fueled equipment, the installing plumber or gastter shall observe that a hard wired carbon monoxide detector with an alarm  
and battery back-up is installed on the oor level where the gas equipment is to be installed. In addition, the installing plumber  
or gastter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each  
additional level of the dwelling, building or structure served by the sidewall horizontal vented gas fueled equipment. It shall  
be the responsibility of the property owner to secure the services of qualied licensed professionals for the installation of hard  
wired carbon monoxide detectors.  
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired  
carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent oor level.  
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall  
have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a bat-  
tery operated carbon monoxide detector with an alarm shall be installed.  
APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above  
provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certied.  
SIGNAGE Ametal or plastic identication plate shall be permanently mounted to the exterior of the building at a minimum height  
of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appli-  
ance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW.  
KEEP CLEAR OF ALL OBSTRUCTIONS.”  
INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the  
installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance  
with the provisions of 248 CMR 5.08(2)(a) 1 through 4.  
EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:  
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54  
as adopted by the Board; and  
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the  
dwelling, building, or structure used in whole or in part for residential purposes.  
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED When the manufacturer of Product  
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with  
the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall  
include:  
1. Detailed instructions for the installation of the venting system design or the venting system components; and  
2. A complete parts list for the venting system design or venting system.  
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED When the manufacturer of  
a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the ue gases,  
but identies “special venting systems,” the following requirements shall be satised by the manufacturer:  
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation  
instructions; and  
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a  
parts list and detailed installation instructions.  
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting  
instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or  
equipment at the completion of the installation.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL INSTALLATION  
GET TO KNOW YOUR WATER HEATER - GAS MODELS  
A
B
C
D
E
F
G
H
J
Vent Pipe–Exhaust  
Vent Terminal  
N
O
P
Flue  
Z
Air Intake Screen - Base Pan  
Flue Bafe Assembly**  
Insulation  
Control Harness  
Rating Plate  
AA Inner Door  
B B Outer Door  
Vent Adapter-Rubber Boot  
Blower Assembly  
Cold Water Inlet  
Inlet Water Shut-off Valve  
Union  
Q
R
S
T
U
V
CC HSI Burner Assembly  
D D Air Intake Screen -  
Blower Assembly  
E E FV Sensor/Bracket Assembly  
(40K & 50K Models Only)  
F F FV Sensor/Bracket Assembly  
(55K & 62.5K Models Only)  
Gas Supply  
Manual Gas Shut-off Valve  
Ground Joint Union  
Drip Leg (Sediment Trap)  
Drain Valve  
Gas Control Valve  
Drain Pan  
Inlet Dip Tube  
Anode**  
Hot Water Outlet  
K
L
M
W
X
Outlet Receptacle (115 VAC)  
Temperature-Pressure Relief Valve  
Y
* ALL PIPING MATERIALS TO BE SUPPLIED BY CUSTOMERS.  
** LOCATED UNDER THE BLOWER ASSEMBLY.  
NATURAL HOT SURFACE IGNITER & MAIN BURNER  
HOT  
SURFACE  
IGNITOR  
SENS
PROPANE HOT SURFACE IGNITER & MAIN BURNER  
HOT  
SURFACE  
IGNITOR  
SENSOR  
GAS CONTROL VALVE-THERMOSTAT  
TEMPERATURE INDICATORS  
*CAUTION: 115 VAC IN CONTROL HARNESS  
AND INSIDE OUTER DOOR  
TEMPERATURE ADJUSTMENT BUTTONS  
GAS MODELS  
WITH HOT SURFACE IGNITION  
& 2", 3" OR 4" PVC VENT CAPABILITY  
FIGURE 1.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL INSTALLATION  
MIXING VALVE USAGE  
FIGURE 2.  
This appliance has been design certied as complying with American  
National Standard/CSA Standard for water heaters and is considered  
suitable for:  
Water heaters are intended to produce hot water. Water heated to a  
temperature which will satisfy space heating, clothes washing, dish  
washing, and other sanitizing needs can scald and permanently injure  
you upon contact. Some people are more likely to be permanently  
injured by hot water than others. These include the elderly, children,  
the inrm, or physically/mentally handicapped. If anyone using hot  
water in your home ts into one of these groups or if there is a local  
code or state law requiring a certain temperature water at the hot water  
tap, then you must take special precautions. In addition to using the  
lowest possible temperature setting that satises your hot water needs,  
a means such as a *Mixing Valve, should be used at the hot water taps  
used by these people or at the water heater. Mixing valves are available  
at plumbing supply or hardware stores. Consult a Qualied Installer or  
Service Agency. Follow mixing valve manufacturer’s instructions for  
installation of the valves. Before changing the factory setting on the  
thermostat, read the “Temperature Regulation” section in this manual,  
see Figure 19.  
Water (Potable) Heating and Space Heating: All models are  
considered suitable for water (potable) heating and space heating.  
HOTTER WATER CAN SCALD:  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOCATING THE NEW WATER HEATER  
FACTS TO CONSIDER ABOUT THE LOCATION  
Carefully choose an indoor location for the new water heater, because  
the placement is a very important consideration for the safety of  
the occupants in the building and for the most economical use of  
the appliance. This water heater is not for use in manufactured  
(mobile) homes or outdoor installation.  
FIGURE 3.  
Whether replacing an old water heater or putting the water heater in  
a new location, the following critical points must be observed:  
1. Select a location indoors as close as practical to the vent terminal  
or location to which the water heater vent piping is going to be  
connected, and as centralized with the water piping system as  
possible.  
Also, the water heater must be located and/or protected so it is not  
subject to physical damage by a moving vehicle.  
2. Selected location must provide adequate clearances for servicing  
and proper operation of the water heater.  
Installation of the water heater must be accomplished in such a manner  
that if the tank or any connections should leak, the ow will not cause  
damage to the structure. For this reason, it is not advisable to install  
the water heater in an attic or upper oor. When such locations cannot  
be avoided, a suitable drain pan should be installed under the water  
heater. Drain pans are available at your local hardware store. Such  
a drain pan must have a minimum length and width of at least 2" (5.1  
cm) greater that the water heater dimensions and must be piped to an  
adequate drain. The pan must not restrict combustion air ow.  
Water heater life depends upon water quality, water pressure and the  
environment in which the water heater is installed. Water heaters are  
sometimes installed in locations where leakage may result in property  
damage, even with the use of a drain pan piped to a drain. However,  
unanticipated damage can be reduced or prevented by a leak detector  
or water shut-off device used in conjunction with a piped drain pan.  
These devices are available from some plumbing supply wholesalers  
and retailers, and detect and react to leakage in various ways:  
• Sensors mounted in the drain pan that trigger an alarm or turn off  
the incoming water to the water heater when leakage is detected.  
• Sensors mounted in the drain pan that turn off the water supply to  
the entire home when water is detected in the drain pan.  
This water heater must not be installed directly on carpeting. Carpeting  
must be protected by metal or wood panel beneath the appliance  
extending beyond the full width and depth of the appliance by at least  
3" (7.6 cm) in any direction, or if the appliance is installed in an alcove  
or closet, the entire oor must be covered by the panel. Failure to  
heed this warning may result in a re hazard.  
• Water supply shut-off devices that activate based on the water  
pressure differential between the cold water and hot water pipes  
connected to the water heater.  
• Devices that will turn off the gas supply to a gas water heater while  
at the same time shutting off its water supply.  
INSTALLATIONS IN AREAS WHERE FLAMMABLE LIQUIDS  
(VAPORS)ARE LIKELY TO BE PRESENT OR STORED (GARAGES,  
STORAGEAND UTILITYAREAS, ETC.): Flammable liquids (such as  
gasoline, solvents, propane (LP or butane, etc.) and other substances  
(such as adhesives, etc.) emit ammable vapors which can be ignited  
by a gas water heater’s hot surface igniter or main burner. The  
resulting ashback and re can cause death or serious burns to anyone  
in the area. This water is equipped with a FV sensor for detecting the  
presence of ammable vapors, see Figure 3. When the sensor detects  
those vapors, the unit will shut down and not operate. Should this  
happen, please refer to the troubleshooting guide on pages 28-30.  
Even though this water heater is a ammable vapors ignition resistant  
water heater and is designed to reduce the chances of ammable  
vapors being ignited, gasoline and other ammable substances should  
never be stored or used in the same vicinity or area containing a gas  
water heater or other open ame or spark producing appliance.  
Minimum clearances between the water heater and combustible  
construction are 0 inch at the sides and rear, 5" (12.7 cm) from the front  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
and 12" (30.5 cm) from the top. (Standard clearance.) If clearances  
stated on the heater differ from standard clearances, install water  
heater according to clearances stated on the heater.  
chlorine based chemicals, refrigerants, etc.) in addition to being highly  
ammable in many cases, will also react to form corrosive hydrochloric  
acid when exposed to the combustion products of the water heater.  
The results can be hazardous, and also cause product failure.  
Adequate clearance for servicing this appliance should be considered  
before installation, such as changing the anodes, etc.  
INSULATION BLANKETS  
Insulation blankets are available to the general public for external use  
on gas water heaters but are not necessary with these products. The  
purpose of an insulation blanket is to reduce the standby heat loss  
encountered with storage tank heaters. Your water heater meets or  
exceeds the National Appliance Energy Conversation Act standards  
with respect to insulation and standby loss requirements, making an  
insulation blanket unnecessary.  
A minimum clearance of 5" (12.7 cm) must be allowed for access  
to replaceable parts such as the thermostats, drain valve and relief  
valve.  
When installing the heater, consideration must be given to proper  
location. Location selected should be as close to the wall as practicable  
and as centralized with the water piping system as possible.  
Should you choose to apply an insulation blanket to this heater, you  
should follow these instructions (For identication of components  
mentioned below, see Figure 1). Failure to follow these instructions  
can restrict the air ow required for proper combustion, potentially  
resulting in re, asphyxiation, serious personal injury or death.  
FIGURE 4.  
Agas water heater cannot operate properly without the correct amount  
of air for combustion. Do not install in a conned area such as a closet,  
unless you provide air as shown in the “Locating The New Water  
Heater” section. Never obstruct the ow of ventilation air. If you have  
any doubts or questions at all, call your gas supplier. Failure to provide  
the proper amount of combustion air can result in a re or explosion  
and cause death, serious bodily injury, or property damage.  
• Do not apply insulation to the top of the water heater, as this will  
interfere with safe operation of the draft hood.  
• Do not cover the outer door, thermostat or temperature & pressure  
relief valve.  
• Do not allow insulation to come within 2" (5.1 cm) of the oor to  
prevent blockage of combustion air ow to the burner.  
• Do not cover the instruction manual. Keep it on the side of the  
water heater or nearby for future reference.  
• Do obtain new warning and instruction labels from the manufacturer  
for placement on the blanket directly over the existing labels.  
• Do inspect the insulation blanket frequently to make certain it  
does not sag, thereby obstructing combustion air ow.  
COMBUSTION AIR AND VENTILATION FOR  
APPLIANCES LOCATED IN UNCONFINED SPACES  
UNCONFINED SPACE is space whose volume is not less than  
50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the  
aggregate input rating of all appliances installed in that space. Rooms  
communicating directly with the space in which the appliances are  
installed, through openings not furnished with doors, are considered  
a part of the unconned space.  
In unconned spaces in buildings, inltration may be adequate to  
provide air for combustion, ventilation and dilution of ue gases.  
However, in buildings of tight construction (for example, weather  
stripping, heavily insulated, caulked, vapor barrier, etc.), additional air  
may need to be provided using the methods described in “Combustion  
Air and Ventilation for Appliances Located in Conned Spaces.”  
FIGURE 5.  
COMBUSTION AIR AND VENTILATION FOR  
APPLIANCES LOCATED IN CONFINED SPACES  
If this water heater will be used in beauty shops, barber shops, cleaning  
establishments, or self-service laundries with dry cleaning equipment, it  
is imperative that the water heater or water heaters be installed so that  
combustion and ventilation air be taken from outside these areas.  
CONFINED SPACE is a space whose volume is less than 50 cubic  
feet per 1,000 Btu per hour (4.8 cm per kW) of the aggregate input  
rating of all appliances installed in that space.  
Propellants of aerosol sprays and volatile compounds, (cleaners,  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chemical vapor corrosion of the ue, blower assembly and vent  
system may occur if air for combustion contains certain chemical  
vapors. Spray can propellants, cleaning solvents, refrigerator and  
air conditioner refrigerants, swimming pool chemicals, calcium and  
sodium chloride, waxes, bleach and process chemicals are typical  
compounds which are potentially corrosive.  
A. ALL AIR FROM INSIDE BUILDINGS: (See Figure 5 and 6)  
The conned space shall be provided with two permanent openings  
communicating directly with an additional room(s) of sufcient volume  
so that the combined volume of all spaces meets the criteria for an  
unconned space. The total input of all gas utilization equipment  
installed in the combined space shall be considered in making this  
determination. Each opening shall have a minimum free area of one  
square inch per 1,000 Btu per hour (22 cm2/kW) of the total input rating of  
all gas utilization equipment in the conned space, but not less than 100  
square inches (645 cm2). One opening shall commence within 12 inches  
(31 cm) of the top and one commencing within 12 inches (31 cm) of  
the bottom of the enclosures.  
FIGURE 8.  
4. When ducts are used, they shall be of the same cross-sectional  
area as the free area of the openings to which they connect. The  
minimum short side dimension of rectangular air ducts shall not  
be less than 3 inches (7.6 cm), see Figure 9.  
FIGURE 9.  
FIGURE 6.  
5. Alternatively a single permanent opening may be used when  
communicating directly with the outdoors, or with spaces that freely  
communicate with the outdoors. The opening shall have a minimum  
free area of 1 square inch per 3,000 BTU per hour (8.3 cm2/kW)  
of total input rating of all equipment in enclosure. See Figure 9A.  
B. ALL AIR FROM OUTDOORS: (See Figures 7, 8 and 9)  
The conned space shall be provided with two permanent openings,  
one commencing within 12 inches (31 cm) of the top and one  
commencing within 12 inches (31 cm) from the bottom of the  
enclosure. The openings shall communicate directly, or by ducts,  
with the outdoors or spaces (crawl or attic) that freely communicate  
with the outdoors.  
1. When directly communicating with the outdoors, each opening shall  
have a minimum free area of 1 square inch per 4,000 Btu per hour  
(5.5 cm2/kW) of total input rating of all equipment in the enclosure,  
see Figure 7.  
FIGURE 9A.  
6. Louvers and Grilles: In calculating free area, consideration shall be  
given to the blocking effect of louvers, grilles or screens protecting  
openings. Screens used shall not be smaller than 1/4 inch  
(6.4 mm) mesh. If the free area through a design of louver or  
grille is known, it should be used in calculating the size opening  
required to provide the free area specied. If the design and free  
area is not known, it may be assumed that wood louvers will be  
20-25 percent free area and metal louvers and grilles will have  
60-75 percent free area. Louvers and grilles shall be xed in the  
open position or interlocked with the equipment so that they are  
opened automatically during equipment operation.  
FIGURE 7.  
2. When communicating with the outdoors through vertical ducts, each  
opening shall have a minimum free area of 1 square inch per 4,000  
Btu per hour (5.5 cm2/kW) of total input rating of all equipment in  
the enclosure, see Figure 8.  
7. Special Conditions Created by Mechanical Exhausting or  
Fireplaces: operation of exhaust fans, ventilation systems, clothes  
dryers or fireplaces may create conditions requiring special  
attention to avoid unsatisfactory operation of installed gas utilization  
equipment.  
3. When communicating with the outdoors through horizontal ducts,  
each opening shall have a minimum free area of 1 square inch  
per 2,000 Btu per hour (11 cm2/kW)) of total input rating of all  
equipment in the enclosure, see Figure 9.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLING THE NEW WATER HEATER  
THERMAL EXPANSION  
As water is heated, it expands (thermal expansion). In a closed system  
WATER PIPING  
the volume of water will grow. As the volume of water grows there will be  
a corresponding increase in water pressure due to thermal expansion.  
Thermal expansion can cause premature tank failure (leakage). This type  
of failure is not covered under the limited warranty. Thermal expansion  
can also cause intermittent temperature-pressure relief valve operation:  
water discharged from the valve due to excessive pressure build up. The  
temperature-pressure relief valve is not intended for the constant relief  
of thermal expansion. This condition is not covered under the limited  
warranty.  
A properly sized thermal expansion tank should be installed on all  
closed systems to control the harmful effects of thermal expansion.  
Contact a local plumbing service agency to have a thermal expansion  
tank installed.  
NOTE: To protect against untimely corrosion of hot and cold  
water ttings, it is strongly recommended that di-electric unions  
or couplings be installed on this water heater when connected to  
copper pipe.  
HOTTER WATER CAN SCALD:  
Water heaters are intended to produce hot water. Water heated to  
a temperature which will satisfy space heating, clothes washing,  
dish washing, cleaning and other sanitizing needs can scald and  
permanently injure you upon contact. Some people are more likely  
to be permanently injured by hot water than others. These include  
the elderly, children, the inrm, or physically/mentally handicapped.  
If anyone using hot water in your home ts into one of these groups  
or if there is a local code or state law requiring a certain temperature  
water at the hot water tap, then you must take special precautions. In  
addition to using the lowest possible temperature setting that satises  
your hot water needs, a means such as a *mixing valve, should be  
used at the hot water taps used by these people or at the water heater,  
see Figure 2. Valves for reducing point of use temperature by mixing  
cold and hot water are also available:  
All gas piping must comply with local codes and ordinances or with the  
National Fuel Gas Code (ANSI Z223.1/ NFPA-54) whichever applies.  
Copper and brass tubing and ttings (except tin lined copper tubing) shall  
not be used.  
Consult a Qualied Installer or Service Agency. Follow manufacturer’s  
instructions for installation of the valves. Before changing the factory  
setting on the thermostat, read the “Temperature Regulation” section in  
this manual.  
This water heater shall not be connected to any heating systems or  
component(s) used with a non-potable water heating appliance.  
All piping components connected to this unit for space heating  
applications shall be suitable for use with potable water.  
Toxic chemicals, such as those used for boiler treatment shall not be  
introduced into this system.  
When the system requires water for space heating at temperatures  
higher than required for domestic water purposes, a tempering valve  
must be installed. Please refer to Figure 2 for suggested piping  
arrangement.  
CLOSED WATER SYSTEMS  
Water supply systems may, because of code requirements or such  
conditions as high line pressure, among others, have installed devices  
such as pressure reducing valves, check valves, and back flow  
preventers. Devices such as these cause the water system to be a  
closed system.  
FIGURE 10.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 10 shows the typical attachment of the water piping to the The valve must be marked with a maximum set pressure not to  
water heater. The water heater is equipped with 3/4 inch NPT water  
connections.  
exceed the marked hydrostatic working pressure of the water heater  
(150 psi = 1,035 kPa) and a discharge capacity not less than the water  
heater input rate as shown on the model rating plate.  
NOTE: If using copper tubing, solder tubing to an adapter before  
attaching the adapter to the cold water inlet connection. Do not  
solder the cold water supply line directly to the cold water inlet.  
It will harm the dip tube and damage the tank.  
For safe operation of the water heater, the relief valve must not be  
removed from its designated opening nor plugged.  
The temperature-pressure relief valve must be installed directly into  
the tting of the water heater designed for the relief valve. Position the  
valve downward and provide tubing so that any discharge will exit only  
within 6 inches (15.2 cm) above, or at any distance below the structural  
oor. Be certain that no contact is made with any live electrical part.  
The discharge opening must not be blocked or reduced in size under  
any circumstances. Excessive length, over 30 feet (9.14 m), or use of  
more than four elbows can cause restriction and reduce the discharge  
capacity of the valve, see Figures 10 or 14.  
T & P Valve and Pipe Insulation (if supplied)  
Remove insulation for T & P valve and pipe connections from carton.  
No valve or other obstruction is to be placed between the relief valve  
and the tank. Do not connect tubing directly to discharge drain unless  
a 6" (15.2 cm) air gap is provided. To prevent bodily injury, hazard to  
life, or property damage, the relief valve must be allowed to discharge  
water in quantities should circumstances demand. If the discharge pipe  
is not connected to a drain or other suitable means, the water ow may  
cause property damage.  
FIGURE 11.  
Fit pipe insulation over the incoming cold water line and the hot water  
line. Make sure that the insulation is against the top cover of the  
heater.  
Fit T & P valve insulation over valve. Make sure that the insulation does  
not interfere with the lever of the T & P valve.  
Secure all insulation using tape.  
The Discharge Pipe:  
• Shall not be smaller in size than the outlet pipe size of the valve, or  
have any reducing couplings or other restrictions.  
• Shall not be plugged or blocked.  
TEMPERATURE-PRESSURE RELIEF VALVE  
• Shall be of material listed for hot water distribution.  
• Shall be installed so as to allow complete drainage of both the  
temperature-pressure relief valve, and the discharge pipe.  
• Shall terminate at an adequate drain.  
• Shall not have any valve between the relief valve and tank.  
This heater is provided with a properly certified combination  
temperature - pressure relief valve by the manufacturer.  
The valve is certied by a nationally recognized testing laboratory  
that maintains periodic inspection of production of listed equipment of  
materials as meeting the requirements for Relief Valves for Hot Water  
Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements  
of ASME.  
The temperature-pressure relief valve must be manually operated at least  
once a year. Caution should be taken to ensure that (1) no one is in front  
of or around the outlet of the temperature-pressure relief valve discharge  
line, and (2) the water manually discharged will not cause any bodily injury  
or property damage because the water may be extremely hot.  
If after manually operating the valve, it fails to completely reset and  
continues to release water, immediately close the cold water inlet  
to the water heater, follow the draining instructions, and replace the  
temperature-pressure relief valve with a new one.  
If replaced, the valve must meet the requirements of local codes, but not  
less than a combination temperature and pressure relief valve certied  
as indicated in the above paragraph.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When installed at elevations above 7,700 feet (2,347 meters), input  
rating should be reduced at the rate of 4 percent for each 1,000 feet  
(305 meters) above sea level which requires replacement of the  
burner orice in accordance with National Fuel Gas CodeANSI Z223.1/  
NFPA 54. Contact your local gas supplier for further information.  
GAS PIPING  
Failure to replace the standard orice with a high altitude orice when  
installed could result in improper and inefcient operation of the  
appliance, producing carbon monoxide gas in excess of safe limits,  
which could result in serious injury or death. Contact your gas supplier  
for any specic changes which may be required in your area.  
Make sure the gas supplied is the same type listed on the model  
rating plate. The inlet gas pressure must not exceed 14 inch water  
column (3.5 kPa) for natural and propane gas (L.P.). The minimum  
inlet gas pressure shown on the rating plate is that which will permit  
ring at rated input.  
All gas piping must comply with local codes and ordinances or with the  
National Fuel Gas Code (ANSI Z223.1/ NFPA-54) whichever applies.  
Copper and brass tubing and ttings (except tin lined copper tubing)  
shall not be used.  
Use pipe joint compound or teon tape marked as being resistant to  
the action of petroleum [Propane (L.P.)] gases.  
The appliance and its gas connection must be leak tested before  
placing the appliance in operation.  
If the gas control valve is subjected to pressures exceeding 1/2 psi  
(14 inches water column) (3.5 kPa), the damage to the gas control  
valve could result in a re or explosion from leaking gas.  
The appliance and its individual Shut-off valve shall be disconnected  
from the gas supply piping system during any pressure testing of that  
system at test pressures in excess of 1/2 pound per square inch (14  
inches water column) (3.5 kPa). It shall be isolated from the gas supply  
piping system by closing its individual manual Shut-off valve during  
any pressure testing of the gas supply piping system at test pressures  
equal to or less than 1/2 pound per square inch (3.5 kPa).  
If the main gas line Shut-off serving all gas appliances is used, also  
turn “off” the gas at each appliance. Leave all gas appliances shut  
“off” until the water heater installation is complete.  
A gas line of sufcient size must be run to the water heater. Consult  
the current edition of National Fuel Gas Code ANSI Z223.1/NFPA 54  
and your gas supplier concerning pipe size.  
Connecting the gas piping to the gas control valve of the water heater  
can be accomplished by either of the two methods shown in Figures  
12 and 13.  
There must be:  
• A readily accessible manual shut off valve in the gas supply line  
serving the water heater, and  
• A drip leg (sediment trap) ahead of the gas control valve to help  
prevent dirt and foreign materials from entering the gas control  
valve.  
• A exible gas connector or a ground joint union between the shut  
off valve and control valve to permit servicing of the unit.  
Be sure to check all the gas piping for leaks before lighting the water  
heater. Use a soapy water solution, not a match or open ame. Rinse  
off soapy solution and wipe dry.  
FIGURE 12. GAS PIPING WITH  
FLEXIBLE CONNECTOR.  
FIGURE 13. GAS PIPING WITH ALL  
BLACK IRON PIPE TO GAS CONTROL VALVE.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SEDIMENT TRAPS  
To ll the water heater with water:  
1. Close the water heater drain valve by turning the handle to the  
right (clockwise). The drain valve is on the lower front of the water  
heater.  
2. Open the cold water supply valve to the water heater.  
NOTE: The cold water supply valve must be left open when  
the water heater is in use.  
3. To insure complete lling of the tank, allow air to exit by opening  
the nearest hot water faucet. Allow water to run until a constant  
ow is obtained. This will let air out of the water heater and the  
piping.  
4. Check all water piping and connections for leaks. Repair as  
needed.  
BLOWER ASSEMBLY INSTALLATION  
A sediment trap shall be installed as close to the inlet of the water  
heater as practical at the time of water heater installation. The sediment  
trap shall be either a tee tting with a capped nipple in the bottom  
outlet or other device recognized as an effective sediment trap. If a  
tee tting is used, it shall be installed in conformance with one of the  
methods of installation shown in Figures 12 and 13.  
SEQUENCE OF INSTALLATION  
1. This power vented water heater comes with the blower assembly  
installed.  
2
After the unit is set in place, make sure the blower assembly is still  
mounted securely and the air intake screen of the blower assembly  
is installed in the dilution air opening. Also make sure the drain  
port of the rubber boot vent adapter is capped off. Lastly, make  
sure there is no damage to the blower.  
Contaminants in the gas lines may cause improper operation of the  
gas control valve that may result in re or explosion. Before attaching  
the gas line be sure that all gas pipe is clean on the inside. To trap any  
dirt or foreign material in the gas supply line, a drip leg (sometimes  
called a sediment trap) must be incorporated in the piping. The drip leg  
must be readily accessible. Install in accordance with the “Gas Piping”  
section. Refer to the current edition of the National Fuel Gas Code,  
ANSI Z223.1/NFPA 54.  
3. Make sure there is no packing material in the discharge of the  
blower or the intake of the dilution air restrictor, see Figure 15.  
4. Make sure that the plastic tubing is still attached from the air pressure  
switch to the port on the blower housing. Make sure the plastic tubing  
is not folded anywhere between the pressure switch and the blower  
housing.  
5. Make sure the ON/OFF switch is in the OFF position and that the  
outer harness is connected from the blower control box to the  
connector on the bottom side of the gas control valve.  
6. If the outer harness is not factory installed, make sure the ON/OFF  
switch is in the OFF position and then connect the outer harness  
from the blower control box to the connector on the bottom side  
of the gas control valve.  
7. This water heater is a polarity sensitive appliance and will not operate if  
thepowersupplypolarityisreversed. Thepowersupplyoroutletproviding  
power to this water heater must be wired properly (correct polarity).  
8. Do not plug in power cord until vent system is completely installed. This  
powered vent heater operates on 110-120 Vac, therefore a grounded  
outlet must be within reach of the six (6) foot (1.8 m) exible power  
cord supplied with the unit (see Figure 1). The power cord supplied  
may be used only where local codes permit. If local codes do not  
permit the use of a exible power supply cord:  
FIGURE 14.  
FILLING THE WATER HEATER  
a.) Make sure the unit is unplugged from wall outlet. Remove screws  
and open panel on front of control box.  
b.) Cut the exible power cord, leaving enough to be able to make  
connections, the remove the strain relief tting from box.  
c.) Install suitable conduit tting in side of enclosure and then follow  
(d.) and (e.) below.  
d.) Splice eld wiring into existing wiring using code authorized method  
(wire nuts, etc.).  
e.) Be certain that neutral and live connections are not reversed when  
making these connections.  
f.) Close panel on the side of control box, make sure that access  
panel is secured shut.  
Never use this water heater unless it is completely full of water. To prevent  
damage to the tank, the tank must be lled with water. Water must ow  
from the hot water faucet before turning “ON” gas to the water heater.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENT CONNECTIONS TO BLOWER ASSEMBLY  
VENTING AND INSTALLATION  
Figure 15 shows the optimal placement of the 2" to 3" or 3" to  
4" reducer; however, the vent can be reduced at any point in the  
vent system as long as the maximum and minimum vent length  
requirements are met.  
Plan the layout of the vent system from the vent termination to the water  
heater considering all of the 90° and 45° elbows plus the number of  
feet of pipe that would be needed to install the total vent system. The  
water heater must be vented to the outdoors as described in these  
instructions. DO NOT connect this water heater to an existing vent  
or chimney. It must be vented separately from all other appliances.  
Nonmetallic vent may be used if it has “Heat Deection Temperature”  
(HDT@66 psi) or 455 kPa of at least 157°F or 69°C. Typical nonmetallic  
vent materials meeting this requirement are: PVC (Schedule 40,ASTM  
D-1785), Coex Cellular Core (Schedule 40, ASTM F-441), CPVC  
(Schedule 40, ASTM D-2846), ABS (Schedule 40, ASTM D-2661).  
The ttings, other than the supplied Vent Termination should be  
equivalent to the following: PVC (Schedule 40, DWV, ASTM D-2665),  
CPVC (Schedule 40, DWV, ASTM F-438), ABS (Schedule 40 DWV,  
ASTM D-2661).  
The cement used should be as recommended by the vent pipe  
manufacturer. See the instructions on pages 18 and 19 for the proper  
method of cutting and cementing the PVC pipe and ttings.  
FIGURE 15.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The unit may be vented horizontally through a wall or vertically through  
the roof. Pipe runs must be adequately supported along both vertical  
and horizontal runs as follows:  
condensate in the vent piping. If this occurs, then adequate means  
of draining and disposing of the condensate needs to be made by  
the installer.  
• For Schedule 40, 2" PVC,ABS, Coex Cellular Core vent pipe: Every  
3 feet (0.9 m).  
CONDENSATE  
Condensate formation does not occur in all installations of power vented  
water heaters, but should be protected against on installations where it  
can form in the venting system. Condensation in the venting system of  
power vented water heaters is dependent upon installation conditions  
including, but not limited to ambient temperature and humidity of  
installation location, ambient temperature and humidity of venting space,  
vent discharge and slope, and product usage. In certain conditions,  
installations in unconditioned space or having long horizontal or vertical  
vent runs may accumulate condensate. In these conditions, the vent  
pipe should be sloped downward away from the blower assembly  
1/4" (6.4 mm) per ve feet (1.5 m) of pipe but not more than 1 1/2" (3.8  
cm) in the total vent length. If the vent piping is vented level or sloped  
upwards away from the blower assembly, then adequate means for  
draining and disposing of the condensate needs to be made by the  
installer (if condensate is detected). If you have condensate, then a  
3/8" drain hose can be connected to the built-in drain port of the rubber  
boot on the blower assembly. For your convenience, the rubber boot  
is supplied with a removable cap on the built-in drain port. Prior to  
operating the water heater, make sure the removable cap is installed  
on the drain port (if a drain hose is not needed).  
• For Schedule 40, 3" PVC,ABS, Coex Cellular Core vent pipe: Every  
3.5 feet (1.1 m).  
• For Schedule 40, 4" PVC,ABS, Coex Cellular Core vent pipe: Every  
4 feet (1.2 m).  
• For Schedule 40, 2" CPVC vent pipe: Every 5 feet (1.5 m).  
• For Schedule 40, 3" CPVC vent pipe: Every 6 feet (1.8 m).  
• For Schedule 40, 4" CPVC vent pipe: Every 6.5 feet (2.0 m).  
It is imperative that the rst hanger (or support) be located on the  
horizontal run immediately adjacent to the rst 90-degree elbow from  
the vertical rise. Support method used should isolate the vent pipe from  
the oor joists or other structural members to prevent the transmission  
of noise and vibration. Do not support, pin, or otherwise secure the  
venting system in a way that restricts the normal thermal expansion  
and contraction of the chosen venting material.  
MAXIMUM AND MINIMUM VENT LENGTHS  
If the water heater is being installed as a replacement for an existing  
power vented heater in pre-existing venting, a through inspection of  
the existing venting system must be performed prior to any installation  
work. Verify that the correct material as detailed above has been used,  
and that the minimum or maximum vent lengths and terminal location  
as detailed in this manual have been met. Carefully inspect the entire  
venting system for any signs of cracks or fractures, particularly at  
the joints between elbows and other ttings and the straight runs of  
vent pipe. Check the system for signs of sagging or other stresses  
in the joints as a result of misalignment of any components in the  
system. If any of these conditions are found, they must be corrected  
in accordance with the venting instructions in this manual before  
completing the installation and putting the water heater into service.  
40,000 BTU Units:  
For 2" Venting, the maximum equivalent feet of pipe allowed is 40  
feet (12.2 m). This does not include the supplied vent termination for  
the water heater. For the 2" venting, one 90° elbow is approximately  
equal to 5 feet (1.5 m). One 45° elbow is approximately equal to 2.5  
feet (0.8 m). It is recommended that at least 2 feet (0.6 m) of spacing  
be used in between all 45° elbows and all 90°elbows.  
For 3" Venting, the maximum equivalent feet of pipe allowed is  
120 feet (36.6 m). This does not include the Vent Termination (supplied  
locally) for the water heater. For the 3" venting, one 90° elbow is  
approximately equal to 5 feet (1.5 m). One 45° elbow is approximately  
equal to 2.5 feet (0.8 m). It is recommended that at least 2 feet (0.6 m)  
of spacing be used in between all 45° elbows and all 90°elbows.  
Except where instructed in this manual, the mixing of 2", 3" and 4"  
vent pipe is NOT ALLOWED. If 2" pipe is to be used, then a 2" to 3"  
bell reducer is recommended. Figure 15 shows the recommended  
location for the bell reducer. If the bell reducer is located at the  
rubber boot on the blower assembly, then a short section of 3" vent  
pipe needs to be installed in the rubber boot for proper connection of  
the 2" to 3" bell reducer. That length can be of the minimum length  
required for the connection.  
For 4" Venting, the maximum equivalent feet of pipe allowed is  
160 feet (48.8 m). This does not include the Vent Termination (supplied  
locally) for the water heater. For the 4" venting, one 90° elbow is  
approximately equal to 8 feet (2.4 m). One 45° elbow is approximately  
equal to 4 feet (1.2 m). It is recommended that at least 2 feet (0.6 m)  
of spacing be used in between all 45° elbows and all 90°elbows.  
If 4" pipe is to be used, then a 3" to 4" bell reducer is recommended.  
Figure 15 shows the recommended location for the bell reducer. If  
the bell reducer is located at the rubber boot on the blower assembly,  
then a short section of 3" vent pipe needs to be installed in the rubber  
boot for proper connection of the 3" to 4" bell reducer. That length  
can be of the minimum length required for the connection.  
50,000 BTU Units:  
For 2" Venting, the maximum equivalent feet of pipe allowed is 40  
feet (12.2 m). This does not include the supplied Vent Termination for  
the water heater. For the 2" venting, one 90° elbow is approximately  
equal to 5 feet (1.5 m). One 45° elbow is approximately equal to 2.5  
feet (0.8 m). It is recommended that at least 2 feet (0.6 m) of spacing  
be used in between all 45° elbows and all 90°elbows.  
The 40,000, 50,000, 55,000 and 62,500 BTU units are supplied with  
a 2" Schedule 40 PVC 22.5° Vent Terminal. If you decide to vent with  
3" or 4" pipe, a Schedule 40 DWV 45° Vent Terminal must be used.  
For your convenience, we have included a screen for both 3" and 4"  
Vent Terminals.  
For 3" Venting, the maximum equivalent feet of pipe allowed is  
120 feet (36.6 m). This does not include the Vent Termination (supplied  
locally) for the water heater. For the 3" venting, one 90° elbow is  
approximately equal to 5 feet (1.5 m). One 45° elbow is approximately  
equal to 2.5 feet (0.8 m). It is recommended that at least 2 feet (0.6 m)  
of spacing be used in between all 45° elbows and all 90°elbows.  
The vent piping should be connected to the blower with a rubber  
adapter and secured with hose clamps. The adapter and clamps are  
provided with the heater.  
Even the flue gas temperature leaving the blower is between  
140°F (69°C) and 175°F (79°C), some installations will have water  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For 4" Venting, the maximum equivalent feet of pipe allowed is  
160 feet (48.8 m). This does not include the Vent Termination (supplied  
locally) for the water heater. For the 4" venting, one 90° elbow is  
approximately equal to 8 feet (2.4 m). One 45° elbow is approximately  
equal to 4 feet (1.2 m). It is recommended that at least 2 feet (0.6 m)  
of spacing be used in between all 45° elbows and all 90°elbows.  
The vent system must terminate so that proper clearances are  
maintained as cited in local codes or the current edition of the  
National Fuel Gas Code, ANSI Z223.1/NFPA 54, 7.3.4e and 7.8a,b,  
as follows:  
1. The exit terminals of a mechanical vent system shall be not less  
than 7 feet (2.13 m) above grade when located adjacent to public  
walkways, see Figure 16.  
55,000 and 62,500 BTU Units:  
NOTE: The 55,000 and 62,500 BTU Units are not approved for 2"  
venting.  
2. Aventing system shall terminate at least 3 feet (0.91 m) above any  
forced air inlet located within 10 feet (3.1 m), see Figure 16.  
For 3" Venting, the maximum equivalent feet of pipe allowed is 80  
feet (24.4 m). This does not include the supplied Vent Termination for  
the water heater. For the 3" venting, one 90° elbow is approximately  
equal to 5 feet (1.5 m). One 45° elbow is approximately equal to 2.5  
feet (0.8 m). It is recommended that at least 2 feet (0.6 m) of spacing  
be used in between all 45° elbows and all 90°elbows.  
3. The venting system shall terminate at least 4 feet (1.2 m) below,  
4 feet (1.2 m) horizontally from or, 1 foot (0.31 m) above any door,  
window or gravity air inlet into any building.  
The manufacturer also recommends that the vent termination  
should not be installed closer than 18" (45.7 cm) from an inside  
corner of an L shaped structure and not be less than 1 foot (0.31  
m) above grade.  
For 4" Venting, the maximum equivalent feet of pipe allowed is  
120 feet (36.6 m). This does not include the Vent Termination (supplied  
locally) for the water heater. For the 4" venting, one 90° elbow is  
approximately equal to 8 feet (2.4 m). One 45° elbow is approximately  
equal to 4 feet (1.2 m). It is recommended that at least 2 feet (0.6 m)  
of spacing be used in between all 45° elbows and all 90°elbows.  
The vent shall terminate a minimum of 12'' (30.5 cm) above  
expected snowfall level to prevent blockage of vent termination,  
see Figure 16.  
VENTING  
4. In cold climates, it is recommended that vent termination not be  
mounted directly above or within 3 feet (0.91 m) horizontally from  
an oil tank vent or gas meter to avoid potential freeze-up from  
condensation, see Figure 16..  
Plan the vent system layout so that proper clearances are maintained  
from plumbing and wiring.  
Vent pipes serving power vented appliances are classied by building  
codes as “vent connectors”. Required clearances from combustible  
materials must be provided in accordance with information in this  
manual under LOCATION OF HEATER and VENT TERMINAL  
INSTALLATIONS, and with the National Fuel Gas Code and local  
codes.  
VENT TERMINAL INSTALLATION  
1. After the point of termination has been determined, use the cover  
plate as a template to mark the hole for the vent pipe to insert  
through the wall. BEWARE OF CONCEALED WIRING AND  
PIPING INSIDE OF WALL.  
2. If the Vent Terminal is being installed on the outside of a nished  
wall, it may be easier to mark both the inside and outside wall.  
Align the holes by drilling a hole through the center of the template  
from the inside through to the outside. The template can now be  
positioned on the outside wall using the drilled hole as a centering  
point for the template.  
3. A) MASONRY SIDE WALLS  
Chisel an opening approximately one half inch larger than the  
marked circle.  
B) WOODEN SIDE WALLS  
Drill a pilot hole approximately one quarter inch outside of the  
marked circle. This pilot hole is used as a starting point for a  
saws-all or sabre saw blade. Cut around the marked circle staying  
approximately one quarter inch outside of the line. (This will allow  
the vent pipe to easily slide through the opening. The resulting  
gap will be covered up by the vent terminal cover plates.) Repeat  
this step on inside wall if necessary.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 16.  
This unit can vent through 2", 3" or 4" nonmetallic pipe and ttings.  
VERTICAL VENT TERMINATION RESTRICTIONS  
The vent pipe installation can be started from either the blower  
discharge or the termination wall. Keep in mind the total vent system  
(pipe and elbows) when installing the vent system, see VENTING  
AND INSTALLATION, pages 15 - 17.  
1. Minimum of twelve 12" (30.5 cm) above the roof or twelve 12"  
(30.5 cm) above the anticipated snow level. Provide proper support  
FIGURE 17.  
The vent terminal should be kept as close as possible to the outside  
wall, but you need to allow at least 1.5" (3.8 cm) of pipe past the wall,  
for the wall ange and vent terminal to mount on the pipe.  
Before the vent terminal is installed, caulk (not supplied) around the  
pipe on the exterior wall and install the optional wall ange. The ange  
can be held to the outside wall by placing some of the caulking on the  
back of the ange. The wall ange is supplied for decorative purposes  
only and is not a requirement for the vent termination (if not needed  
by the installer).  
VERTICAL VENT THROUGH ROOF  
This unit is approved for venting through the roof with the type vent  
terminal that is included with the unit. A proper ashing or “BOOT”  
should be used to seal the pipe where it exits the roof.  
FIGURE 18.  
2. 4' (1.2 m) from or 1' (0.3 m) above any gable, dormer, or other  
roof structure with access to interior of building (i.e.-vent, window  
etc.).  
The total vent system should not exceed that which is specied, see  
VENTING AND INSTALLATION, pages 15 - 17.  
All of the pipe should be secured as per the instructions in the  
instructions in the VENTING AND INSTALLATION, pages 15 - 17.  
3. 3' (0.9 m) above any forced air inlet located within 10' (3.0 m).  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRIMER  
VENT PIPE PREPARATION  
It is recommended that Tetrahydrofuran (THF) be used to prepare the  
surfaces of pipe and ttings for solvent welding. Do not use water,  
rags, gasoline or any other substitutes for cleaning PVC or CPVC  
surfaces. A chemical cleaner such as MEK may be used.  
1. INITIAL PREPARATION  
A. Make sure the solvent cement you are planning to use is  
designed for the specic application you are attempting.  
CEMENT  
B. Know the physical and chemical characteristics and limitations  
of the PVC and CPVC piping materials that you are about to  
use.  
The cement should be a bodied cement of approximately 500 to  
1600 centipoise viscosity containing 10-20% (by weight) virgin PVC  
material solvated with tetrahydrofuran (THF). Small quantities of  
dimethyl formamide (DMF) may be included to act as a retarding  
agent to extend curing time. Select the proper cement; Schedule 40  
cement should be used for Schedule 40 pipe. Never use all-purpose  
cements, commercial glues and adhesives orABS cement to join PVC  
or CPVC pipe and ttings.  
C. Know the reputation of your manufacturer and their  
products.  
D. Know your own qualications or those of your contractor. The  
solvent welding technique of joining PVC and CPVC pipe is  
a specialized skill just as any other pipe tting technique.  
E. Closely supervise the installation and inspect the nished  
job before start-up.  
F. Contact the manufacturer, supplier, or competent consulting  
agency if you have any questions about the application or  
installation of PVC and CPVC pipe.  
G. Take the time and effort to do a professional job. Shortcuts  
will only cause you problems and delays in start-up. By far,  
the majority of failures in PVC and CPVC systems are the  
result of shortcuts and/or improper joining techniques.  
APPLICATORS  
Select a suitable pure bristle type paint brush. Use a proper width brush  
or roller to apply the primer and cement (see chart below). Speedy  
application of cement is important due to its fast drying characteristics.  
IMPORTANT NOTE: A dauber type applicator should only be used  
on pipe sizes 2" and below. For larger diameter pipe, a brush or roller  
must be used.  
2. SELECTION OF MATERIALS  
Cutting Device - Saw or Pipe Cutter  
Deburring Tool, Knife, File, or Beveling Machine (2" and above)  
Brush - Pure Bristle  
RECOMMENDED BRUSH* SIZE FOR PRIMER  
AND CEMENT APPLICATIONS  
Rag - Cotton (Not Synthetic)  
Nominal Pipe  
(IPS)  
Size Brush Width  
(INS.)  
Primer and Cleaner  
2
3
1-1/2  
Solvent Cement - PVC for PVC Components and CPVC for CPVC  
Components  
1-1/2 - 2-1/2  
*USE ONLY NATURAL BRISTLE  
Containers - Metal or Glass to hold Primer and Cement. Select  
the type of PVC or CPVC materials to be used on the basis of their  
application with respect to chemical resistance, pressure rating,  
temperature characteristics, etc.  
3. MAKING THE JOINT  
A. Cutting  
Insertion Tool - Helpful for larger diameter pipe and ttings 6 inches  
(15.2 cm) and above.  
Pipe must be squarely cut to allow for the proper interfacing of the  
pipe end and the tting socket bottom. This can be accomplished  
with a miter box saw or wheel type cutter. Wheel type cutters are  
not generally recommended for larger diameters since they tend  
to are the corner of the pipe end. If this type of cutter is used, the  
are on the end must be completely removed.  
NOTE: Power saws should be specically designed to cut plastic  
pipe.  
STEP A  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Deburring  
Use a knife, plastic pipe deburring tool, or le to remove burrs  
from the end of small diameter pipe. Be sure to remove all burrs  
from around the inside as well as the outside of the pipe. A slight  
chamfer (bevel) of about 10°-15° should be added to the end to  
permit easier insertion of the pipe into the end of the tting. Failure  
to chamfer the edge of the pipe may remove cement from the tting  
socket, causing the joint to leak.  
STEP E  
F. Joint assembly  
Working quickly, insert the pipe into the tting socket bottom and  
give the pipe or tting a 1/4 turn to evenly distribute the cement.  
Do not continue to rotate the pipe after it has hit the bottom of the  
tting socket. A good joint will have sufcient cement to make a  
bead all the way around the outside of the tting hub. The tting  
will have a tendency to slide back while the cement is still wet so  
hold the joint together for about 15 seconds.  
STEP B  
C. Test dry t of the joint  
Tapered tting sockets are designed so that an interfaced t should  
occur when the pipe is inserted about 1/3 to 2/3 of the way into  
the socket. Occasionally, when pipe tting dimensions are at the  
tolerance extremes, it will be possible to fully insert dry pipe to the  
bottom of the tting socket. When this happens, a sufcient quantity  
of cement must be applied to the joint to ll the gap between the  
pipe and tting. The gap must be lled to obtain a strong, leak-free  
joint.  
D. Inspection, cleaning, priming  
Visually inspect the inside of the pipe and tting sockets and  
remove all dirt, grease or moisture with a clean dry rag. If wiping  
fails to clean the surfaces, a chemical cleaner must be used.  
Check for possible damage such as splits or cracks and replace  
if necessary.  
STEP F  
G. Cleanup and joint movement  
Depth-of-entry  
Remove all excess cement from around the pipe and tting with a  
dry cotton rag. This must be done while the cement is still soft.  
Marking the depth of entry is a way to check if the pipe has reached  
the bottom of the tting socket in Step F. Measure the tting depth  
and mark this distance on the pipe O.D. You may want to add  
several inches to the distance and make a second mark as the  
primer and cement will most likely destroy your rst one.  
The joint should not be disturbed immediately after the cementing  
procedure, and sufcient time should be allowed for proper curing of  
the joint. Exact drying time is difcult to predict because it depends  
on variables such as temperature, humidity and cement integrity.  
For more specic information, you should contact your solvent  
cement manufacturer.  
Apply primer to the surface of the pipe and tting socket with a  
natural bristle brush. This process softens and prepares the PVC  
or CPVC for the solvent cementing step. Move quickly and without  
hesitation to the cementing procedure while the surfaces are still  
wet with primer.  
E. Application of solvent cement  
• Apply the solvent cement evenly and quickly around the outside  
of the pipe at a width a little greater than the depth of the tting  
socket.  
• Apply a light coat of cement evenly around the inside of the  
tting socket. Avoid puddling.  
• Apply a second coat of cement to the pipe end.  
STEP G  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TEMPERATURE REGULATION  
Due to the nature of the typical gas water heater, the water temperature  
in certain situations may vary up to 30°F (16.7°C) higher or lower at  
the point of use such as, bathtubs, showers, sink, etc.  
control has a tamper resistant feature for changing the temperature  
setting. To change the temperature setting follow these instructions:  
1. “Wake Up” the temperature indicators by holding down both  
“COOLER” and “HOTTER” temperature adjustment buttons at  
the same time for one second, see Figure 19. One or two of the  
temperature indicators will light up. These indicators will only remain  
on for 30 seconds if no further buttons are pressed.After 30 seconds  
the control will go back to “Sleep” mode.  
It is recommended that lower water temperatures be used to avoid  
the risk of scalding. It is further recommended, in all cases, that the  
water temperature be set for the lowest temperature which satises  
your hot water needs. This will also provide the most energy efcient  
operation of the water heater.  
2. Release both of the temperature adjustment buttons.  
a. To decrease the temperature press and release the “COOLER”  
button until the desired setting is reached.  
b. To increase the temperature press and release the “HOTTER”  
button until the desired setting is reached.  
NOTE: Holding down the button will not continue to lower or raise the  
temperature setting. The button must be pressed and released for  
each temperature change desired.  
Should overheating occur or the gas supply fail to shut off, turn off the  
manual gas control valve to the appliance.  
GAS CONTROL VALVE - FRONT VIEW  
HOT WATER CAN SCALD: Water heaters are intended to produce  
hot water. Water heated to a temperature which will satisfy space  
heating, clothes washing, dish washing, and other sanitizing needs  
can scald and permanently injure you upon contact. Some people  
are more likely to be permanently injured by hot water than others.  
These include the elderly, children, the inrm, or physically/mentally  
handicapped. If anyone using hot water in your home ts into one of  
these groups or if there is a local code or state law requiring a certain  
temperature water at the hot water tap, then you must take special  
precautions. In addition to using the lowest possible temperature  
setting that satises your hot water needs, a means such as a mixing  
valve, should be used at the hot water taps used by these people or  
at the water heater. Mixing valves are available at plumbing supply  
or hardware stores, see Figure 2. Follow manufacturer’s instructions  
for installation of the valves. Before changing the factory setting on  
the thermostat see Figure 19.  
Never allow small children to use a hot water tap, or to draw their own  
bath water. Never leave a child or handicapped person unattended  
in a bathtub or shower.  
The water heater should be located in an area where the general public  
does not have access. If a suitable area is not available, a cover should  
be installed over the thermostat to prevent tampering.  
Time to Produce  
Display  
A B C  
2nd and 3rd Degree  
Burns on Adult Skin  
Temperature Setting  
The water temperature setting was factory set at the lowest  
C-Flashing = approx. 160°F (71°C)  
C = approx. 150°F (66°C)  
B = approx. 140°F (60°C)  
A = approx. 130°F (54°C)  
= approx. 120°F (49°C)  
About 1/2 seconds  
About 1-1/2 seconds  
Less than 5 seconds  
About 30 seconds  
More than 5 minutes  
- - - - - - - - - - - - -  
temperature; Pressing the “COOLER”  
temperature and pressing the “HOTTER”  
temperature.  
button decreases  
button increases the  
Setting the water heater temperature at 120°F (49°C) (Approx. “ ” mark  
on temperature setting of the gas control valve) will reduce the risks of  
scalds. Some states require settings at specic lower temperatures.  
To avoid any unintentional changes in water temperature settings, the  
Time to Produce  
WARM = approx. 80°F (27°C)  
FIGURE 19.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR YOUR INFORMATION  
START UP CONDITIONS  
STRANGE SOUNDS  
Possible noises due to expansion and contraction of some metal parts  
during periods of heat-up and cool-down do not necessarily represent  
harmful or dangerous conditions.  
CONDENSATE  
Whenever the water heater is lled with cold water, some condensate  
will form while the burner is on.Awater heater may appear to be leaking  
when in fact the water is condensate. This usually happens when:  
Condensation causes sizzling and popping within the burner area  
during heating and cooling periods and should be considered normal.  
See “Condensate” in this section.  
a. A new water heater is lled with cold water for the rst time.  
b. Burning gas produces water vapor in water heaters, particularly  
high efciency models where ue temperatures are lower.  
c. Large amounts of hot water are used in a short time and the rell  
water in the tank is very cold.  
OPERATIONAL CONDITIONS  
SMELLY WATER  
Moisture from the products of combustion condense on the cooler  
tank surfaces and form drops of water which may fall onto the burner  
or other hot surfaces to produce a “sizzling” or “frying” noise.  
In each water heater there is installed at least one anode rod (see parts  
section) for corrosion protection of the tank. Certain water conditions  
will cause a reaction between this rod and the water. The most common  
complaint associated with the anode rod is one of a “rotten egg smell”  
in the hot water. The smell is a result of four factors which must all be  
present for the odor to develop:  
Because of the suddenness and amount of water, condensate water  
may be diagnosed as a “tank leak”. After the water in the tank warms  
up (about 1-2 hours), the condition should disappear.  
a. A concentration of sulfate in the supply water.  
b. Little or no dissolved oxygen in the water.  
c. Asulfate reducing bacteria which has accumulated within the water  
heater (this harmless bacteria is nontoxic to humans).  
d. An excess of active hydrogen in the tank. This is caused by the  
corrosion protective action of the anode.  
Do not assume the water heater is leaking until there has been enough  
time for the water in the tank to warm up.  
An undersized water heater will cause more condensation. The water  
heater must be sized properly to meet the family’s demands for hot  
water including dishwashers, washing machines and shower heads.  
Smelly water may be eliminated or reduced in some water heater  
models by replacing the anode(s) with one of less active material,  
and then chlorinating the water heater tank and all water lines.  
Contact the local water heater supplier or service agency for further  
information concerning anAnode Replacement Kit and this chlorination  
treatment.  
Excessive condensate may be noticed during the winter and early  
spring months when incoming water temperatures are at their  
lowest.  
Good venting is essential for a gas red water heater to operate  
properly as well as to carry away products of combustion and water  
vapor.  
If the smelly water persists after the anode replacement and chlorination  
treatment, we can only suggest that chlorination or aeration of the  
water supply be considered to eliminate the water problem.  
SMOKE/ODOR  
It is not uncommon to experience a small amount of smoke and odor  
during the initial start-up. This is due to burning off of oil from metal  
parts, and will disappear in a short while.  
Do not remove the anode leaving the tank unprotected. By doing  
so, all warranty on the water heater tank is voided.  
THERMAL EXPANSION  
“AIR” IN HOT WATER FAUCETS  
CLOSED WATER SYSTEMS  
Water supply systems may, because of code requirements or such  
conditions as high line pressure, among others, have installed devices  
such as pressure reducing valves, check valves, and back ow preventers.  
Devices such as these cause the water system to be a closed system.  
HYDROGEN GAS: Hydrogen gas can be produced in a hot water  
system that has not been used for a long period of time (generally  
two weeks or more). Hydrogen gas is extremely ammable and  
explosive. To prevent the possibility of injury under these conditions, we  
recommend the hot water faucet, located farthest away, be opened for  
several minutes before any electrical appliances which are connected  
to the hot water system are used (such as a dishwasher or washing  
machine). If hydrogen gas is present, there will probably be an unusual  
sound similar to air escaping through the pipe as the hot water faucet  
is opened. There must be no smoking or open ame near the faucet  
at the time it is open.  
THERMAL EXPANSION  
As water is heated, it expands (thermal expansion). In a closed system  
the volume of water will grow. As the volume of water grows there will be  
a corresponding increase in water pressure due to thermal expansion.  
Thermal expansion can cause premature tank failure (leakage). This type  
of failure is not covered under the limited warranty. Thermal expansion  
can also cause intermittent temperature-pressure relief valve operation:  
water discharged from the valve due to excessive pressure build up. The  
temperature-pressure relief valve is not intended for the constant relief  
of thermal expansion. This condition is not covered under the limited  
warranty.  
HIGH WATER TEMPERATURE SHUT OFF SYSTEM  
This water heater is equipped with an automatic gas shut-off system.  
This system works when high water temperatures are present. Turn  
“OFF” the entire gas supply to the water heater. The high temperature  
shut-off is built into the gas control valve. It is non-resettable. If the  
high temperature shut-off activates, the gas control valve must be  
replaced. Contact your gas supplier or service agency.  
A properly sized thermal expansion tank should be installed on all  
closed systems to control the harmful effects of thermal expansion.  
Contact a local plumbing service agency to have a thermal expansion  
tank installed.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PERIODIC MAINTENANCE  
proper combustion. A visual inspection of the main burner and HSI  
igniter assembly should also be done at least once a year, see Figure  
20.  
VENTING SYSTEM INSPECTION  
Soot build-up indicates a problem that requires correction before  
further use. Turn “OFF” gas to water heater and leave off until repairs  
are made, because failure to correct the cause of the sooting can result  
in a re causing death, serious injury, or property damage.  
FIGURE 20.  
BURNER CLEANING  
In the event your burner or burner air openings require cleaning, turn  
the blower switch to the “OFF” position and allow the burner to cool.  
Call a service agency to remove and clean the burner and correct the  
problem that required the burner to be cleaned.  
At least once a year a visual inspection should be made of the venting  
system. You should look for:  
HOUSEKEEPING  
1. Obstructions which could cause improper venting. The combustion  
and ventilation air ow must not be obstructed.  
Vacuum around base of water heater for dust, dirt, and lint on a  
regular basis.  
2. Damage or deterioration which could cause improper venting or  
leakage of combustion products.  
Be sure the vent piping is properly connected to prevent escape of  
dangerous ue gasses which could cause deadly asphyxiation.  
Obstructions and deteriorated vent systems may present serious  
health risk or asphyxiation.  
Chemical vapor corrosion of the ue and vent system may occur  
if air for combustion contains certain chemical vapors. Spray can  
propellants, cleaning solvents, refrigerator and air conditioner  
refrigerants, swimming pool chemicals, calcium and sodium chloride,  
waxes, bleach and process chemicals are typical compounds which  
are potentially corrosive.  
If after inspection of the vent system you found sooting or deterioration,  
something is wrong. Call the local gas utility to correct the problem  
and clean or replace the ue and venting before resuming operation  
of the water heater.  
This water heater unit is supplied with a plastic Air Intake Screen that  
will lter and prevent lint build-up on the bottom of the ame arrestor  
of this heater. To prevent the lint build-up on the arrestor, the lint  
screen must be installed on the Base Pan with the “arrows” pointing  
upwards as shown in Figure 21. If the Air Intake Screen is missing  
from this heater, please contact your service agency or local installer  
for a replacement part.  
BURNER OPERATION AND INSPECTION  
Flood damage to a water heater may not be readily visible or  
immediately detectable. However, over a period of time a ooded water  
heater will create dangerous conditions which can cause DEATH,  
SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. Contact a  
qualied installer or service agency to replace a ooded water heater.  
Do not attempt to repair the unit! It must be replaced!  
At least once a year a visual inspection should be made of the  
main burner and the hot surface igniter assembly for proper ame  
characteristics and ignition sequences. This can be done by removing  
the Outer Door and viewing the main burner operation through the  
Viewport on the Inner Door, see Figure 1. The main burner should  
provide complete combustion of gas, ignite rapidly, give reasonably  
quiet operation, and cause no excessive ame lifting from the burner  
ports. If the proper ame characteristics are not evident (see Figure  
20), make sure that the ow of combustion and ventilation air is not  
blocked on the Air Intake Screen at the base of the water heater (see  
Figure 21), the Lint screen on the blower assembly (see Figure 1),  
and in the venting system.  
FIGURE 21.  
AT LEAST ONCE EVERY SIX MONTHS A VISUAL INSPECTION  
SHOULD BE MADE OF THEAIR INTAKE SCREENS ON THE BASE  
OF THE WATER HEATERAND THE BLOWERASSEMBLY. CLEAN  
IF LINT ACCUMULATIONS ARE NOTICED.  
You should also check for sooting. Soot is not normal and will impair  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If after manually operating the valve, it fails to completely reset and  
continues to release water, immediately close the cold water inlet  
to the water heater, follow the draining instructions, and replace the  
temperature-pressure relief valve with a new one.  
INSTALLED IN SUITABLE AREA: To insure sufcient ventilation  
and combustion air supply, proper clearances from the water heater  
must be maintained. See “Locating the New Water Heater” section.  
Combustible materials such as clothing, cleaning materials, or  
ammable liquids, etc. must not be placed against or adjacent to the  
water heater which can cause a re.  
If the temperature-pressure relief valve on the appliance weeps or  
discharges periodically, this may be due to thermal expansion. You  
may have a check valve installed in the water line or a water meter  
with a check valve. Consult your local water supplier or service  
agency for further information. Do not plug the temperature-pressure  
relief valve.  
ANODE ROD INSPECTION  
DRAINING  
The anode rod is used to protect the tank from corrosion. Most hot  
water tanks are equipped with an anode rod. The submerged rod  
sacrices itself to protect the tank. Instead of corroding the tank,  
water ions attack and eat away the anode rod. This does not affect  
the water’s taste or color. The rod must be maintained to keep the  
tank in operating condition.  
The water heater should be drained if being shut down during freezing  
temperatures. Also periodic draining and cleaning of sediment from  
the tank may be necessary.  
Anode deterioration depends on water conductivity, not necessarily  
water condition. A corroded or pitted anode rod indicates high water  
conductivity and should be checked and/or replaced more often than  
an anode rod that appears to be intact. Replacement of a depleted  
anode rod can extend the life of your water heater. Inspection should  
be conducted by a qualied technician, and at a minimum should be  
checked annually after the warranty period.  
1. Set the blower switch to the “OFF” position.  
2. CLOSE the cold water inlet valve to the water heater.  
3. OPEN a nearby hot water faucet and leave open to allow for  
draining.  
TEMPERATURE-PRESSURE  
RELIEF VALVE OPERATION  
4. Connect a hose to the drain valve and terminate to an adequate  
drain.  
5. OPEN the water heater drain valve to allow for tank draining.  
NOTE: If the water heater is going to be shut down and drained  
for an extended period, the drain valve should be left open with  
hose connected allowing water to terminate to an adequate  
drain.  
6. CLOSE the drain valve.  
7. Follow instructions in the “Filling The Water Heater” section.  
8. Follow the lighting instructions on the label or see page 14 under  
“Lighting Instructions” to restart the water heater.  
The temperature-pressure relief valve must be manually operated at  
least once a year.  
DRAIN VALVE WASHER REPLACEMENT  
(See Figure 23)  
1. Turn “OFF” gas supply to water heater.  
2. Follow “Draining” instructions.  
3. Turning counterclockwise (  
screw handle.  
), remove the hex cap below the  
FIGURE 22.  
4. Remove the washer and put the new one in place.  
When checking the temperature-pressure relief valve operation, make  
sure that (1) no one is in front of or around the outlet of the temperature-  
pressure relief valve discharge line, and (2) that the water discharge  
will not cause any property damage, as the water may be extremely  
hot, see Figure 22.  
5. Screw the handle and cap assembly back into the drain valve and  
retighten using a wrench. DO NOT OVER TIGHTEN.  
6. Follow instructions in the “Filling The Water Heater” section.  
7. Check for leaks.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Follow the lighting instructions in the “Lighting” section to restart  
the water heater.  
SERVICE  
If a condition persists or you are uncertain about the operation of the  
water heater contact a service agency.  
Use this guide to check a “Leaking” water heater. Many suspected  
“Leakers” are not leaking tanks. Often the source of the water can  
be found and corrected.  
If you are not thoroughly familiar with gas codes, your water heater,  
and safety practices, contact your gas supplier or qualied installer  
FIGURE 23.  
to check the water heater.  
LEAKAGE CHECKPOINTS  
Read this manual rst. Then before checking the water heater make  
sure the gas supply has been turned “OFF”, and never turn the gas  
“ON” before the tank is completely full of water.  
Never use this water heater unless it is completely lled with water.  
To prevent damage to the tank, the tank must be lled with water.  
Water must ow from the hot water faucet before turning “ON” gas  
to the water heater.  
A. Water at the blower assembly is water vapor which has condensed  
out of the combustion products. This is caused by a problem in  
the vent. Contact the gas utility.  
B. *Condensation may be seen on pipes in humid weather or pipe  
connections may be leaking.  
C. *The anode rod tting may be leaking (anode is located under the  
Blower Assembly).  
D. Small amounts of water from temperature-pressure relief valve  
may be due to thermal expansion or high water pressure in your  
area.  
E. *The temperature-pressure relief valve may be leaking at the tank  
tting.  
F. Water from a drain valve may be due to the valve being slightly  
opened.  
G. *The drain valve may be leaking at the tank tting.  
H. Combustion products contain water vapor which can condense on  
the cooler surfaces of the tank. Droplets form and drip onto the  
burner or run on the oor. This is common at the time of start-up  
after installation and when incoming water is cold.  
I. Water in the water heater bottom or on the oor may be from  
condensation, loose connections, or the relief valve. DO NOT  
replace the water heater until a full inspection of all possible water  
sources is made and necessary corrective steps taken.  
Leakage from other appliances, water lines, or ground seepage should  
also be checked.  
*
To check where threaded portion enters tank, insert cotton swab  
between jacket opening and tting. If cotton is wet, follow “Draining”  
instructions in the “Periodic Maintenance” section and then remove  
tting. Put pipe dope or teon tape on the threads and replace.  
Then follow “Filling the Water Heater” instructions in the “Installing  
the New Water Heater” section.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPAIR PARTS LIST  
Key No. Part Description  
1
2
Burner Assembly  
Burner Head  
3
Burner Orice  
4
Burner Tube  
5
HSI Ignition Assembly  
Inner Door  
6
7
Inner Door Gasket  
Flue Bafe  
8
9
Flue Restrictor  
Blower Assembly  
Air Intake Screen - Base Pan  
Inlet Tube  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
Gas Control Valve  
Drain Valve  
Drain Valve Washer  
Outer Door (may appear different than shown)  
Anode Rod  
Temperature-Pressure Relief Valve  
Viewport Bracket  
Viewport Glass  
Viewport Insulation  
20” Dia. Drain Pan w/Side Drain (optional)  
22” Dia. Drain Pan w/Side Drain (optional)  
24” Dia. Drain Pan w/Side Drain (optional)  
26” Dia. Drain Pan w/Side Drain (optional)  
Instruction Manual  
*23  
24  
Air Intake Screen - Blower Assembly  
FV Sensor  
BURNER ASSEMBLY  
25  
26A  
26B  
**27  
FV Sensor Bracket (40K & 50K models only)  
FV Sensor Bracket (55K & 62.5K models only)  
Nipple with Heat Trap  
**28  
Secondary Anode with Heat Trap  
* Not Shown.  
** Optional  
Now that you have purchased this water heater, should a need ever exist for repair  
parts or service, simply contact the company it was purchased from or direct from  
the manufacturer listed on the rating plate on the water heater.  
1
Be sure to provide all pertinent facts when you call or visit.  
DRAIN PAN  
OUTER DOOR  
(ALTERNATE)  
Selling prices will be furnished on request or parts will be shipped at prevailing  
prices and you will be billed accordingly.  
The model number of your Gas Water Heater will be found on the rating place  
located above the gas control valve.  
22  
WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE FOLLOWING  
INFORMATION:  
16  
MODEL NUMBER  
TYPE GAS (NATURAL OR PROPANE (L.P.)  
SERIAL NUMBER  
PART DESCRIPTION  
THIS IS A REPAIR PARTS LIST, NOT A PACKING LIST.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING GUIDELINES  
TROUBLE SHOOTING  
Please check guidelines below. For your safety, water heater service should be performed only by a qualied service technician.  
Read the GENERAL SAFETY INFORMATION section rst.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING GUIDELINES  
These guidelines should be utilized by a qualied service agent. When calling for service notify the service agent  
that this is a “Flammable Vapor Ignition Resistant” Product.  
Figure 1 and 15.  
Page 9.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED RESIDENTIAL GAS WARRANTY  
claimed defective heater or part to such distributor except in the state of  
THIS WARRANTY IS APPLICABLE TO THE ORIGINAL OWNER ONLY.  
If the glass lined tank in this water heater shall prove upon examination  
by (the warrantor) to have leaked during the warranty period in normal  
residential use, due to natural corrosion from potable water therein, the  
warrantor will furnish the ORIGINALOWNER a replacement water heater of  
equivalent size and current model, or a replacement part for any component  
part which fails in normal use, in accordance with the warranty terms and  
conditions specied below. THE WATER HEATER REPLACEMENT  
MODEL OR PART WILL BE WARRANTED FOR ONLY THE UNEXPIRED  
PORTION OF THE ORIGINAL WARRANTY. The warranty period will be  
determined by the original installation date of the water heater. PROOF-  
OF-PURCHASEAND PROOF-OF-INSTALLATIONARE NECESSARYTO  
VALIDATE THIS WARRANTY. This warranty is not transferable.  
California where such charges are the manufacturer’s responsibility.  
c. All cost necessary or incidental for handling and administrative charges,  
and for any materials and/or permits required for installation of the  
replacement heater or part.  
LIMITATION ON IMPLIED WARRANTIES  
Implied warranties, including any warranty of merchantability imposed  
on the sale of this heater under state law are limited to one year duration  
for the heater or any of its parts. Some states do not allow limitations  
on how long an implied warranty lasts, so the above limitations may not  
apply to you.  
CLAIM PROCEDURE  
Any claim under this warranty should be initiated with the dealer who sold  
the heater, or with any other dealer handling the warrantor’s products.  
WARRANTY PERIOD  
Product Line  
GS6  
TANK1  
PARTS2  
6 YEARS  
6 YEARS  
The warrantor will only honor replacement with identical or similar water  
heater or parts thereof which are manufactured or distributed by the  
warrantor.  
When the water heater has been used for other than single family  
residential application: 1. The tank warranty shall be reduced to1 year  
for 6 year models. 2. The parts warranty shall be reduced to 1 year for  
all models. Returned parts which meet any of the following conditions  
are not covered by this warranty: 1) improper installation or removal; 2)  
damaged by other than normal wear; 3) replaced for cosmetic purposes;  
or 4) returned with defaced date codes.  
Dealer replacements are made subject to in-warranty validation by  
warrantor.  
PROOF-OF-PURCHASE AND PROOF-OF-INSTALLATION DATES  
ARE REQUIRED TO SUPPORT WARRANTY FOR CLAIM FROM  
ORIGINAL OWNER. THIS FORM DOES NOT CONSTITUTE PROOF-  
OF-PURCHASE OR PROOF-OF-INSTALLATION.  
CONDITIONS AND EXCEPTIONS  
This warranty shall apply only when the water heater is installed and  
operated in accordance with: 1) all local re codes and plumbing codes,  
ordinances and regulations; 2) the printed instructions provided with it; 3)  
good industry practices; and 4) proper safety practices such as but not  
limited to a properly sized drain pan if installed in an area where leakage  
from connections of the tank would result in damage to the area adjacent  
to the heater. In addition, a new temperature and pressure relief valve,  
certied by the Canadian StandardsAssociation must have been properly  
installed and piped to the nearest drain.  
DISCLAIMERS  
NO EXPRESS WARRANTY HAS BEEN OR WILL BE MADE IN BEHALF  
OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY  
OF THE HEATER OR THE INSTALLATION, OPERATION, REPAIR OR  
REPLACEMENT OF THE HEATER OR PARTS. THE WARRANTOR  
SHALL NOT BE RESPONSIBLE FOR WATER DAMAGE, LOSS OF  
USE OF THE UNIT, INCONVENIENCE, LOSS OR DAMAGE TO  
PERSONALPROPERTY, OR OTHER CONSEQUENTIALDAMAGE. THE  
WARRANTOR SHALLNOT BE LIABLE BY VIRTUE OF THIS WARRANTY  
OR OTHERWISE FOR DAMAGE TO ANY PERSONS OR PROPERTY,  
WHETHER DIRECT OR INDIRECT, AND WHETHER ARISING IN  
CONTRACT OR IN TORT.  
This warranty shall apply only when the heater is:  
owned by the original purchaser;  
used at temperatures not exceeding the maximum calibrated  
setting of its thermostat;  
not subjected to excessive water pressure uctuations and not subject  
to an operating pressure greater than 150 P.S.I.;  
lled with potable water, free to circulate at all times and with the tank  
free of damaging water sediment or scale deposits;  
used in a non-corrosive and non-contaminated atmosphere;  
used with factory approved anode(s) installed;  
in its original installation location;  
in the United States and its territories or possessions;  
sized in accordance with proper sizing techniques for residential water  
heaters;  
bearing a rating plate which has not been altered, defaced or removed  
except as required by the warrantor;  
used in an open system or in a closed system with a properly  
sized and installed thermal expansion tank;  
red at the factory rated input using the fuel stated in the face of the  
rating plate;  
Some states do not allow the limitation or exclusion of incidental or  
consequential damages, so the above limitation or exclusion may not  
apply to you.  
This warranty gives you specic legal rights, and you may also have other  
rights which vary from state to state. Should governmental regulations or  
industry standards prohibit the Manufacturer from furnishing a comparable  
model replacement under this warranty, the Owner will be furnished with  
the closest comparable water heater meeting the current governmental  
regulations and industry standards.Asupplementary fee may be assessed  
to cover the additional cost associated with the changes made to meet  
applicable regulations and standards.  
Fill out and keep with water heater.  
operated with the inner and outer combustion chamber doors  
in place;  
maintained in accordance with the instructions printed in the  
manual included with the heater.  
IMPORTANT INFORMATION  
Model Number____________________________________________  
Serial Number_____________________________________________  
Installation Information:  
Any accident to the water heater or any part thereof (including freezing,  
re, oods, or lightning), any misuse, abuse or alteration of it, any operation  
of it in a modied form, or any attempt to repair tank leaks or parts, will  
void this warranty.  
Date Installed ____________________________________________  
Company’s Name _________________________________________  
Street or P.O. Box _________________________________________  
City, State, and Zip Code ___________________________________  
Phone Number _______________Plumber’s Name_______________  
SERVICE AND LABOR RESPONSIBILITY  
UNDER THIS LIMITED WARRANTY, THE WARRANTOR WILLPROVIDE  
ONLY A REPLACEMENT WATER HEATER OR PART THEREOF. THE  
OWNER IS RESPONSIBLE FOR ALL OTHER COSTS. Such costs may  
include but are not limited to:  
a. Labor charges for service, removal, or reinstallation of the water heater  
or part thereof.  
b. Shipping and delivery charges for forwarding the new water heater  
or replacement part from the nearest distributor and returning the  
Download from Www.Somanuals.com. All Manuals Search And Download.  
500 Tennessee Waltz Parkway  
Ashland City, TN 37015  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Shark Carpet Cleaner S3601K 11 User Manual
Shure Headphones bg41 User Manual
Sony Car Speaker SA W2500 User Manual
Sony CRT Television KDL 40W580B User Manual
Sony Digital Photo Frame D810 DPF D720 User Manual
Sony Inflatable Bouncy Toy NWZ WS613 User Manual
Sony Laptop 4 2003H User Manual
Sony Laptop VPCW212ADWI User Manual
Sunbeam Toaster BR2500 User Manual
System Sensor Smoke Alarm DH500 User Manual