INTRODUCTION  
These quality features are included in the Rheem  
Outdoor Package Heat Pumps  
Control Box Access  
Compressor Access  
Blower Access  
Optional Electric Heater Kit  
Evaporator Coil/Filter Access  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION  
ENGINEERING FEATURES  
RJNA- Series Package Heat Pumps  
1. All models feature Copeland® Scroll® compressors offering maximum reliability, efficiency, and quiet  
operation.  
2. One-piece top over the indoor section with drip lip, drawn painted base pan, and 1" [25.4 mm] raised flanges  
for supply/return air connections provides superior water management.  
3. Convertible horizontal and vertical airflow design allows maximum field flexibility and minimizes inventory  
requirements.  
4. Standard full perimeter forkable baserail with lifting holes for easier maneuvering and installations.  
5. Factory installed one-inch [25.4 mm] throw away filter with provisions for two-inch [50.8 mm] filter.  
6. Direct or belt drive options to accommodate a wide range of design conditions as high as 1.5 inches  
[37 kPa] of external static pressure.  
7. Easily removable filter, blower, electric heat, and compressor/control access panels permits prompt service.  
8. Number and color coded wiring helps facilitate service and maintenance.  
9. Common cabinet and components allows for installation flexibility and fewer parts to inventory.  
10. Standard high pressure control on all models.  
11. Externally mounted refrigerant gauge ports for easy service diagnostics.  
12. Side and base electric power entry helps minimize roof penetrations.  
13. Quick assembly common roof curbs helps save field labor and maximize size flexibility.  
14. Factory or field installed electric heat kits available up to 24 KW.  
15. Easy to install plug-in, slip-in economizers; 100% fully modulating, single enthalpy.  
16. Quality powder paint finish offers long lasting protection against extreme weather conditions and is able to  
withstand 1000 HR salt spray test.  
[
] Designates Metric Conversions  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL IDENTIFICATION—RJNA- SERIES  
R J N A — A 036 J K 000  
Electric Heat  
000 = No Resistance Heat  
010 = 10 kW Resistance Heat  
015 = 15 kW Resistance Heat  
020 = 20 kW Resistance Heat  
Drive Package  
K = Direct Drive  
L = Belt Drive  
M = Belt Drive—High Static  
Electrical Designation  
J = 208-230 V, 1 PH, 60 Hz  
C = 208-230 V, 3 PH, 60 Hz  
D = 460 V, 3 PH, 60 Hz  
Nominal Cooling Capacity  
(BTUH) [kW]  
036 = 36,000 [10.55]  
042 = 42,000 [12.31]  
048 = 48,000 [14.07]  
060 = 60,000 [17.58]  
Future Technical Variations  
Design Series  
A = 1st Design  
Efficiency Designation  
N = 13 SEER  
Product Classification  
J = Package Heat Pump—  
Light Commercial  
Tradebrand  
R = Rheem  
[
] Designates Metric Conversions  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONS—RJNA- SERIES  
FACTORY INSTALLED OPTION CODES FOR RJNA (3-5 Ton) [10.6-17.6 kW]  
(A036, A042, A048, A060)  
Low Ambient  
Time Delay  
Freeze Stat  
Reduced Height  
Baserails  
Option Code  
Hail Guard  
Side Flow  
AA  
AD  
AF  
No Options  
x
x
x
x
AK  
AL  
BD  
BS  
BX  
CK  
x
x
x
x
x
x
x
x
x
Example: RJNA-A060CK000XXX (where XX is factory installed option)  
Example: No Options  
RJNA-A060CK000  
Example: No Options with Factory Installed Economizer  
RJNA-A060CK000AAB  
Example: Options with Hail Guard, Low Ambient, Time Delay and Freeze Stat with No Factory Installed Economizer  
RJNA-A060CK000BDA  
Example: Options same as above with Factory Installed Economizer  
RJNA-A060CK000BDB  
ECONOMIZER SELECTION FOR RJNA-  
Single Enthalpy Economizer  
With Barometric Relief  
No Economizer  
A
B
x
x
“x” indicates factory installed option.  
[
] Designates Metric Conversions  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL DATA—RJNA- SERIES  
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]  
Model RJNA- Series  
Cooling Performance1  
Gross Cooling Capacity Btu [kW]  
EER/SEER2  
A036CK  
A036CL  
A036CM  
A036DK  
CONTINUED  
37,600 [11]  
11.6/13  
37,600 [11]  
11.6/13  
37,600 [11]  
11.6/13  
37,600 [11]  
11.6/13  
Nominal CFM/ARI Rated CFM [L/s]  
ARI Net Cooling Capacity Btu [kW]  
Net Sensible Capacity Btu [kW]  
Net Latent Capacity Btu [kW]  
Net System Power kW  
Heating Performance (Heat Pumps)  
Heating Temp. Btuh [kW] Rating  
System Power KW/COP  
Low Temp. Btuh [kW] Rating  
System Power KW/COP  
HSPF (Btu/Watts-hr)  
Compressor  
1200/1200 [566/566]  
36,000 [10.5]  
26,823 [7.9]  
9177 [2.7]  
1200/1200 [566/566]  
36,000 [10.5]  
26,823 [7.9]  
9177 [2.7]  
1200/1200 [566/566]  
36,000 [10.5]  
26,823 [7.9]  
9177 [2.7]  
1200/1200 [566/566]  
36,000 [10.5]  
26,823 [7.9]  
9177 [2.7]  
3.1  
3.1  
3.1  
3.1  
35,600 [10.4]  
3.2/3.3  
35,600 [10.4]  
3.2/3.3  
35,600 [10.4]  
3.2/3.3  
35,600 [10.4]  
3.2/3.3  
21,200 [6.2]  
3/2.08  
21,200 [6.2]  
3/2.08  
21,200 [6.2]  
3/2.08  
21,200 [6.2]  
3/2.08  
7.7  
7.7  
7.7  
7.7  
No./Type  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
Outdoor Sound Rating (dB)3  
Outdoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm] OD  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
Refrigerant Control  
Indoor Coil—Fin Type  
Tube Type  
Tube Size in. [mm]  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Refrigerant Control  
Drain Connection No./Size in. [mm]  
Outdoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
CFM [L/s]  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
No. Motors/HP  
Motor RPM  
Indoor Fan—Type  
FC Centrifugal  
1/10x10 [254x254]  
Direct/3  
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
FC Centrifugal  
1/10x10 [254x254]  
Direct/3  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
No. Motors  
1
1
Motor HP  
1/2  
1/2  
3/4  
1/2  
Motor RPM  
1075  
1725  
1725  
1075  
Motor Frame Size  
48  
56  
56  
48  
Filter—Type  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Furnished  
(No.) Size Recommended in. [mm]  
Refrigerant Charge Oz. [g]  
Weights  
(2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]  
182 [5160]  
182 [5160]  
182 [5160]  
182 [5160]  
Net Weight lbs. [kg]  
Ship Weight lbs. [kg]  
See Page 14 for Notes.  
517 [235]  
532 [241]  
517 [235]  
532 [241]  
517 [235]  
532 [241]  
517 [235]  
532 [241]  
[
] Designates Metric Conversions  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL DATA—RJNA- SERIES  
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]  
Model RJNA- Series  
Cooling Performance1  
Gross Cooling Capacity Btu [kW]  
EER/SEER2  
A036DL  
A036DM  
A036JK  
A042CK  
CONTINUED  
42,500 [12.5]  
11.8/13  
37,600 [11]  
11.6/13  
37,600 [11]  
11.6/13  
37,600 [11]  
11.6/13  
Nominal CFM/ARI Rated CFM [L/s]  
ARI Net Cooling Capacity Btu [kW]  
Net Sensible Capacity Btu [kW]  
Net Latent Capacity Btu [kW]  
Net System Power kW  
Heating Performance (Heat Pumps)  
Heating Temp. Btuh [kW] Rating  
System Power KW/COP  
Low Temp. Btuh [kW] Rating  
System Power KW/COP  
HSPF (Btu/Watts-hr)  
Compressor  
1200/1200 [566/566]  
36,000 [10.5]  
26,823 [7.9]  
9177 [2.7]  
1200/1200 [566/566]  
36,000 [10.5]  
26,823 [7.9]  
9177 [2.7]  
1200/1200 [566/566]  
36,000 [10.5]  
26,823 [7.9]  
9177 [2.7]  
1400/1400 [661/661]  
40,500 [11.9]  
30,124 [8.8]  
10,376 [3]  
3.1  
3.1  
3.1  
3.4  
35,600 [10.4]  
3.2/3.3  
35,600 [10.4]  
3.2/3.3  
35,600 [10.4]  
3.2/3.3  
40,000 [11.7]  
3.6/3.28  
21,200 [6.2]  
3/2.08  
21,200 [6.2]  
3/2.08  
21,200 [6.2]  
3/2.08  
23,200 [6.8]  
3.3/2.06  
7.7  
7.7  
7.7  
7.7  
No./Type  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
Outdoor Sound Rating (dB)3  
Outdoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm] OD  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
Refrigerant Control  
Indoor Coil—Fin Type  
Tube Type  
Tube Size in. [mm]  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Refrigerant Control  
Drain Connection No./Size in. [mm]  
Outdoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
CFM [L/s]  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
No. Motors/HP  
Motor RPM  
Indoor Fan—Type  
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
FC Centrifugal  
1/10x10 [254x254]  
Direct/3  
FC Centrifugal  
1/10x10 [254x254]  
Direct/3  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
No. Motors  
1
1
Motor HP  
1/2  
3/4  
1/2  
1/2  
Motor RPM  
1725  
1725  
1075  
1075  
Motor Frame Size  
56  
56  
48  
48  
Filter—Type  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Furnished  
(No.) Size Recommended in. [mm]  
Refrigerant Charge Oz. [g]  
Weights  
(2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]  
182 [5160]  
182 [5160]  
182 [5160]  
177 [5018]  
Net Weight lbs. [kg]  
Ship Weight lbs. [kg]  
See Page 14 for Notes.  
517 [235]  
532 [241]  
517 [235]  
532 [241]  
517 [235]  
532 [241]  
521 [236]  
536 [243]  
[
] Designates Metric Conversions  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL DATA—RJNA- SERIES  
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]  
Model RJNA- Series  
Cooling Performance1  
Gross Cooling Capacity Btu [kW]  
EER/SEER2  
A042CL  
A042CM  
A042DK  
A042DL  
CONTINUED  
42,500 [12.5]  
11.8/13  
42,500 [12.5]  
11.8/13  
42,500 [12.5]  
11.8/13  
42,500 [12.5]  
11.8/13  
Nominal CFM/ARI Rated CFM [L/s]  
ARI Net Cooling Capacity Btu [kW]  
Net Sensible Capacity Btu [kW]  
Net Latent Capacity Btu [kW]  
Net System Power kW  
Heating Performance (Heat Pumps)  
Heating Temp. Btuh [kW] Rating  
System Power KW/COP  
Low Temp. Btuh [kW] Rating  
System Power KW/COP  
HSPF (Btu/Watts-hr)  
Compressor  
1400/1400 [661/661]  
40,500 [11.9]  
30,124 [8.8]  
10,376 [3]  
1400/1400 [661/661]  
40,500 [11.9]  
30,124 [8.8]  
10,376 [3]  
1400/1400 [661/661]  
40,500 [11.9]  
30,124 [8.8]  
10,376 [3]  
1400/1400 [661/661]  
40,500 [11.9]  
30,124 [8.8]  
10,376 [3]  
3.4  
3.4  
3.4  
3.4  
40,000 [11.7]  
3.6/3.28  
40,000 [11.7]  
3.6/3.28  
40,000 [11.7]  
3.6/3.28  
40,000 [11.7]  
3.6/3.28  
23,200 [6.8]  
3.3/2.06  
23,200 [6.8]  
3.3/2.06  
23,200 [6.8]  
3.3/2.06  
23,200 [6.8]  
3.3/2.06  
7.7  
7.7  
7.7  
7.7  
No./Type  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
Outdoor Sound Rating (dB)3  
Outdoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm] OD  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
Refrigerant Control  
Indoor Coil—Fin Type  
Tube Type  
Tube Size in. [mm]  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Refrigerant Control  
Drain Connection No./Size in. [mm]  
Outdoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
CFM [L/s]  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
No. Motors/HP  
Motor RPM  
Indoor Fan—Type  
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
FC Centrifugal  
1/10x10 [254x254]  
Direct/3  
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
No. Motors  
1
Motor HP  
1/2  
3/4  
1/2  
1/2  
Motor RPM  
1725  
1725  
1075  
1725  
Motor Frame Size  
56  
56  
48  
56  
Filter—Type  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Furnished  
(No.) Size Recommended in. [mm]  
Refrigerant Charge Oz. [g]  
Weights  
(2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]  
177 [5018]  
177 [5018]  
177 [5018]  
177 [5018]  
Net Weight lbs. [kg]  
Ship Weight lbs. [kg]  
See Page 14 for Notes.  
521 [236]  
536 [243]  
521 [236]  
536 [243]  
521 [236]  
536 [243]  
521 [236]  
536 [243]  
[
] Designates Metric Conversions  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL DATA—RJNA- SERIES  
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]  
Model RJNA- Series  
Cooling Performance1  
Gross Cooling Capacity Btu [kW]  
EER/SEER2  
A042DM  
A042JK  
A048CK  
A048CL  
CONTINUED  
49,500 [14.5]  
11.65/13  
42,500 [12.5]  
11.8/13  
42,500 [12.5]  
11.8/13  
49,500 [14.5]  
11.65/13  
Nominal CFM/ARI Rated CFM [L/s]  
ARI Net Cooling Capacity Btu [kW]  
Net Sensible Capacity Btu [kW]  
Net Latent Capacity Btu [kW]  
Net System Power kW  
Heating Performance (Heat Pumps)  
Heating Temp. Btuh [kW] Rating  
System Power KW/COP  
Low Temp. Btuh [kW] Rating  
System Power KW/COP  
HSPF (Btu/Watts-hr)  
Compressor  
1400/1400 [661/661]  
40,500 [11.9]  
30,124 [8.8]  
10,376 [3]  
1400/1400 [661/661]  
40,500 [11.9]  
30,124 [8.8]  
10,376 [3]  
1600/1600 [755/755]  
47,000 [13.8]  
34,700 [10.2]  
12,300 [3.6]  
4
1600/1600 [755/755]  
47,000 [13.8]  
34,700 [10.2]  
12,300 [3.6]  
4
3.4  
3.4  
40,000 [11.7]  
3.6/3.28  
40,000 [11.7]  
3.6/3.28  
46,500 [13.6]  
3.9/3.5  
46,500 [13.6]  
3.9/3.5  
23,200 [6.8]  
3.3/2.06  
23,200 [6.8]  
3.3/2.06  
27,800 [8.1]  
3.7/2.22  
7.7  
27,800 [8.1]  
3.7/2.22  
7.7  
7.7  
7.7  
No./Type  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
Outdoor Sound Rating (dB)3  
Outdoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm] OD  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
Refrigerant Control  
Indoor Coil—Fin Type  
Tube Type  
Tube Size in. [mm]  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
3 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
4 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
4 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Refrigerant Control  
Drain Connection No./Size in. [mm]  
Outdoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
CFM [L/s]  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
No. Motors/HP  
Motor RPM  
Indoor Fan—Type  
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
FC Centrifugal  
1/10x10 [254x254]  
Direct/3  
FC Centrifugal  
1/10x10 [254x254]  
Direct/3  
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
No. Motors  
1
1
Motor HP  
3/4  
1/2  
1/2  
1/2  
Motor RPM  
1725  
1075  
1075  
1725  
Motor Frame Size  
56  
48  
48  
56  
Filter—Type  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Furnished  
(No.) Size Recommended in. [mm]  
Refrigerant Charge Oz. [g]  
Weights  
(2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]  
177 [5018]  
177 [5018]  
206 [5840]  
206 [5840]  
Net Weight lbs. [kg]  
Ship Weight lbs. [kg]  
See Page 14 for Notes.  
521 [236]  
536 [243]  
521 [236]  
536 [243]  
535 [243]  
550 [249]  
535 [243]  
550 [249]  
[
] Designates Metric Conversions  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL DATA—RJNA- SERIES  
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]  
Model RJNA- Series  
Cooling Performance1  
Gross Cooling Capacity Btu [kW]  
EER/SEER2  
A048CM  
A048DK  
A048DL  
A048DM  
CONTINUED  
49,500 [14.5]  
11.65/13  
49,500 [14.5]  
11.65/13  
49,500 [14.5]  
11.65/13  
49,500 [14.5]  
11.65/13  
Nominal CFM/ARI Rated CFM [L/s]  
ARI Net Cooling Capacity Btu [kW]  
Net Sensible Capacity Btu [kW]  
Net Latent Capacity Btu [kW]  
Net System Power kW  
Heating Performance (Heat Pumps)  
Heating Temp. Btuh [kW] Rating  
System Power KW/COP  
Low Temp. Btuh [kW] Rating  
System Power KW/COP  
HSPF (Btu/Watts-hr)  
Compressor  
1600/1600 [755/755]  
47,000 [13.8]  
34,700 [10.2]  
12,300 [3.6]  
4
1600/1600 [755/755]  
47,000 [13.8]  
34,700 [10.2]  
12,300 [3.6]  
4
1600/1600 [755/755]  
47,000 [13.8]  
34,700 [10.2]  
12,300 [3.6]  
4
1600/1600 [755/755]  
47,000 [13.8]  
34,700 [10.2]  
12,300 [3.6]  
4
46,500 [13.6]  
3.9/3.5  
46,500 [13.6]  
3.9/3.5  
46,500 [13.6]  
3.9/3.5  
46,500 [13.6]  
3.9/3.5  
27,800 [8.1]  
3.7/2.22  
7.7  
27,800 [8.1]  
3.7/2.22  
7.7  
27,800 [8.1]  
3.7/2.22  
7.7  
27,800 [8.1]  
3.7/2.22  
7.7  
No./Type  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
Outdoor Sound Rating (dB)3  
Outdoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm] OD  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
Refrigerant Control  
Indoor Coil—Fin Type  
Tube Type  
Tube Size in. [mm]  
0.375 [9.5]  
5.16 [0.48]  
4 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
4 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
4 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
4 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Refrigerant Control  
Drain Connection No./Size in. [mm]  
Outdoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
CFM [L/s]  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
No. Motors/HP  
Motor RPM  
Indoor Fan—Type  
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
FC Centrifugal  
1/10x10 [254x254]  
Direct/3  
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
No. Motors  
1
Motor HP  
3/4  
1/2  
1/2  
3/4  
Motor RPM  
1725  
1075  
1725  
1725  
Motor Frame Size  
56  
48  
56  
56  
Filter—Type  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Furnished  
(No.) Size Recommended in. [mm]  
Refrigerant Charge Oz. [g]  
Weights  
(2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]  
206 [5840]  
206 [5840]  
206 [5840]  
206 [5840]  
Net Weight lbs. [kg]  
Ship Weight lbs. [kg]  
See Page 14 for Notes.  
535 [243]  
550 [249]  
535 [243]  
550 [249]  
535 [243]  
550 [249]  
535 [243]  
550 [249]  
[
] Designates Metric Conversions  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL DATA—RJNA- SERIES  
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]  
Model RJNA- Series  
Cooling Performance1  
Gross Cooling Capacity Btu [kW]  
EER/SEER2  
A048JK  
A060CK  
A060CL  
A060CM  
CONTINUED  
64,000 [18.8]  
11.55/13  
49,500 [14.5]  
11.65/13  
63,500 [18.6]  
11.55/13  
64,000 [18.8]  
11.55/13  
Nominal CFM/ARI Rated CFM [L/s]  
ARI Net Cooling Capacity Btu [kW]  
Net Sensible Capacity Btu [kW]  
Net Latent Capacity Btu [kW]  
Net System Power kW  
Heating Performance (Heat Pumps)  
Heating Temp. Btuh [kW] Rating  
System Power KW/COP  
Low Temp. Btuh [kW] Rating  
System Power KW/COP  
HSPF (Btu/Watts-hr)  
Compressor  
1600/1600 [755/755]  
47,000 [13.8]  
34,700 [10.2]  
12,300 [3.6]  
4
2000/2000 [944/944]  
61,500 [18]  
43,800 [12.8]  
17,700 [5.2]  
5.3  
2000/2000 [944/944]  
61,500 [18]  
43,800 [12.8]  
17,700 [5.2]  
5.3  
2000/2000 [944/944]  
61,500 [18]  
43,800 [12.8]  
17,700 [5.2]  
5.3  
46,500 [13.6]  
3.9/3.5  
60,500 [17.7]  
5/3.5  
60,500 [17.7]  
5/3.5  
60,500 [17.7]  
5/3.5  
27,800 [8.1]  
3.7/2.22  
7.7  
36,000 [10.5]  
4.4/2.3  
36,000 [10.5]  
4.4/2.3  
36,000 [10.5]  
4.4/2.3  
7.7  
7.7  
7.7  
No./Type  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
Outdoor Sound Rating (dB)3  
Outdoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm] OD  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
Refrigerant Control  
Indoor Coil—Fin Type  
Tube Type  
Tube Size in. [mm]  
0.375 [9.5]  
5.16 [0.48]  
4 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
4 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
4 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
4 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Refrigerant Control  
Drain Connection No./Size in. [mm]  
Outdoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
CFM [L/s]  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
No. Motors/HP  
Motor RPM  
Indoor Fan—Type  
FC Centrifugal  
1/10x10 [254x254]  
Direct/3  
FC Centrifugal  
1/11x9 [279.4x228.6]  
Direct/2  
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
No. Motors  
1
1
Motor HP  
1/2  
1
3/4  
1
Motor RPM  
1075  
1100  
1725  
1725  
Motor Frame Size  
48  
48  
56  
56  
Filter—Type  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Furnished  
(No.) Size Recommended in. [mm]  
Refrigerant Charge Oz. [g]  
Weights  
(2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]  
206 [5840]  
184 [5216]  
184 [5216]  
184 [5216]  
Net Weight lbs. [kg]  
535 [243]  
550 [249]  
565 [256]  
580 [263]  
565 [256]  
580 [263]  
565 [256]  
580 [263]  
Ship Weight lbs. [kg]  
See Page 14 for Notes.  
[
] Designates Metric Conversions  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL DATA—RJNA- SERIES  
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]  
Model RJNA- Series  
Cooling Performance1  
Gross Cooling Capacity Btu [kW]  
EER/SEER2  
A060DL  
A060DM  
A060JK  
64,000 [18.8]  
11.55/13  
64,000 [18.8]  
11.55/13  
63,500 [18.6]  
11.55/13  
Nominal CFM/ARI Rated CFM [L/s]  
ARI Net Cooling Capacity Btu [kW]  
Net Sensible Capacity Btu [kW]  
Net Latent Capacity Btu [kW]  
Net System Power kW  
Heating Performance (Heat Pumps)  
Heating Temp. Btuh [kW] Rating  
System Power KW/COP  
Low Temp. Btuh [kW] Rating  
System Power KW/COP  
HSPF (Btu/Watts-hr)  
Compressor  
2000/2000 [944/944]  
61,500 [18]  
43,800 [12.8]  
17,700 [5.2]  
5.3  
2000/2000 [944/944]  
61,500 [18]  
43,800 [12.8]  
17,700 [5.2]  
5.3  
2000/2000 [944/944]  
61,500 [18]  
43,800 [12.8]  
17,700 [5.2]  
5.3  
60,500 [17.7]  
5/3.5  
60,500 [17.7]  
5/3.5  
60,500 [17.7]  
5/3.5  
36,000 [10.5]  
4.4/2.3  
36,000 [10.5]  
4.4/2.3  
36,000 [10.5]  
4.4/2.3  
7.7  
7.7  
7.7  
No./Type  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
1/Copeland Scroll  
83  
Outdoor Sound Rating (dB)3  
Outdoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm] OD  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
0.375 [9.5]  
16.56 [1.54]  
2 / 22 [9]  
TX Valves  
Louvered  
Rifled  
Refrigerant Control  
Indoor Coil—Fin Type  
Tube Type  
Tube Size in. [mm]  
0.375 [9.5]  
5.16 [0.48]  
4 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
4 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
0.375 [9.5]  
5.16 [0.48]  
4 / 13 [5]  
TX Valves  
1/1 [25.4]  
Propeller  
1/24 [609.6]  
Direct/1  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Refrigerant Control  
Drain Connection No./Size in. [mm]  
Outdoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
CFM [L/s]  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
4000 [1888]  
1 at 1/3 HP  
1075  
No. Motors/HP  
Motor RPM  
Indoor Fan—Type  
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
FC Centrifugal  
1/10x10 [254x254]  
Belt/Variable  
1
FC Centrifugal  
1/11x9 [279.4x228.6]  
Direct/2  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
No. Motors  
1
Motor HP  
3/4  
1
1
Motor RPM  
1725  
1725  
1100  
Motor Frame Size  
56  
56  
48  
Filter—Type  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Furnished  
(No.) Size Recommended in. [mm]  
Refrigerant Charge Oz. [g]  
Weights  
(2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]  
184 [5216]  
184 [5216]  
184 [5216]  
Net Weight lbs. [kg]  
Ship Weight lbs. [kg]  
See Page 14 for Notes.  
565 [256]  
580 [263]  
565 [256]  
580 [263]  
565 [256]  
580 [263]  
[
] Designates Metric Conversions  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL DATA—RJNA- SERIES  
NOTES:  
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not  
include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for  
operation to Ϯ20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment  
certification program, which is based on ARI Standard 210/240 or 360.  
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.  
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.  
[
] Designates Metric Conversions  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEMS PERFORMANCE—RJNA- SERIES  
COOLING PERFORMANCE DATA—RJNA-A036  
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀  
wbE  
CFM [L/s]  
DR ➀  
71°F [21.7°C]  
1200 [566]  
.13  
67°F [19.4°C]  
1200 [566]  
.13  
63°F [17.2°C]  
1200 [566]  
.13  
1440 [680]  
.16  
960 [453]  
.08  
1440 [680]  
.16  
960 [453]  
.08  
1440 [680]  
.16  
960 [453]  
.08  
Total BTUH [kW] 46.4 [13.60] 44.8 [13.13] 43.1 [12.63] 43.4 [12.72] 41.9 [12.28] 40.4 [11.84] 41.1 [12.05] 39.7 [11.63] 38.2 [11.20]  
75  
[23.9]  
Sens BTUH [kW] 27.9 [8.18] 25.5 [7.47] 23.1 [6.77] 33.5 [9.82] 30.6 [8.97] 27.7 [8.12] 34.8 [10.20] 31.8 [9.32] 28.8 [8.44]  
Power  
2.2  
2.2  
2.2  
2.2  
2.2  
2.1  
2.2  
2.2  
2.1  
O
U
T
D
O
O
R
Total BTUH [kW] 45.5 [13.33] 43.9 [12.87] 42.3 [12.40] 42.6 [12.48] 41.1 [12.05] 39.6 [11.61] 40.2 [11.78] 38.8 [11.37] 37.4 [10.96]  
80  
Sens BTUH [kW] 27.3 [8.00] 25.0 [7.33] 22.6 [6.62] 32.9 [9.64] 30.0 [8.79] 27.2 [7.97] 34.2 [10.02] 31.3 [9.17] 28.3 [8.29]  
[26.7]  
Power  
2.3  
2.3  
2.3  
2.3  
2.3  
2.3  
2.3  
2.3  
2.3  
Total BTUH [kW] 44.5 [13.04] 42.9 [12.57] 41.3 [12.10] 41.5 [12.16] 40.0 [11.72] 38.6 [11.31] 39.2 [11.49] 37.8 [11.08] 36.4 [10.67]  
85  
[29.4]  
Sens BTUH [kW] 26.7 [7.83] 24.4 [7.15] 22.1 [6.48] 32.3 [9.47] 29.5 [8.65] 26.8 [7.85] 33.6 [9.85] 30.7 [9.00] 27.9 [8.18]  
Power  
2.5  
2.4  
2.4  
2.4  
2.4  
2.4  
2.4  
2.4  
2.4  
D
R
Y
Total BTUH [kW] 43.3 [12.69] 41.7 [12.22] 40.2 [11.78] 40.3 [11.81] 38.9 [11.40] 37.5 [10.99] 38.0 [11.14] 36.6 [10.73] 35.3 [10.35]  
90  
[32.2]  
Sens BTUH [kW] 26.1 [7.65] 23.9 [7.00] 21.7 [6.36] 31.7 [9.29] 29.0 [8.50] 26.3 [7.71] 33.0 [9.67] 30.2 [8.85] 27.4 [8.03]  
B
U
L
Power  
2.6  
2.5  
2.5  
2.6  
2.5  
2.5  
2.6  
2.5  
2.5  
Total BTUH [kW] 42.0 [12.31] 40.5 [11.87] 39.0 [11.43] 39.0 [11.43] 37.6 [11.02] 36.3 [10.64] 36.7 [10.76] 35.4 [10.37] 34.1 [9.99]  
95  
[35]  
B
Sens BTUH [kW] 25.6 [7.50] 23.4 [6.86] 21.2 [6.21] 31.1 [9.11] 28.5 [8.35] 25.8 [7.56] 32.4 [9.50] 29.7 [8.70] 26.9 [7.88]  
Power  
2.7  
2.6  
2.6  
2.7  
2.6  
2.6  
2.7  
2.6  
2.6  
T
E
M
P
E
R
A
T
Total BTUH [kW] 40.7 [11.93] 39.3 [11.52] 37.8 [11.08] 37.7 [11.05] 36.4 [10.67] 35.1 [10.29] 35.4 [10.37] 34.2 [10.02] 32.9 [9.64]  
100  
[37.8]  
Sens BTUH [kW] 25.0 [7.33] 22.8 [6.68] 20.7 [6.07] 30.5 [8.94] 27.9 [8.18] 25.3 [7.41] 31.9 [9.35] 29.1 [8.53] 26.4 [7.74]  
Power  
2.8  
2.8  
2.7  
2.8  
2.7  
2.7  
2.8  
2.7  
2.7  
Total BTUH [kW] 39.5 [11.58] 38.1 [11.17] 36.7 [10.76] 36.5 [10.70] 35.2 [10.32] 33.9 [9.94] 34.2 [10.02] 33.0 [9.67]  
31.8 [9.32]  
25.9 [7.59]  
2.8  
105  
[40.6]  
Sens BTUH [kW] 24.4 [7.15] 22.3 [6.54] 20.2 [5.92] 30.0 [8.79] 27.4 [8.03] 24.8 [7.27] 31.3 [9.17] 28.6 [8.38]  
Power  
2.9  
2.9  
2.8  
2.9  
2.9  
2.8  
2.9  
2.9  
U
R
E
Total BTUH [kW] 38.4 [11.25] 37.0 [10.84] 35.7 [10.46] 35.4 [10.37] 34.2 [10.02] 32.9 [9.64]  
33.1 [9.70]  
30.7 [9.00]  
3.0  
31.9 [9.35]  
28.0 [8.21]  
3.0  
30.8 [9.03]  
25.4 [7.44]  
2.9  
110  
[43.3]  
Sens BTUH [kW] 23.8 [6.98] 21.8 [6.39] 19.7 [5.77] 29.3 [8.59] 26.8 [7.85] 24.3 [7.12]  
°F  
[°C]  
Power  
3.0  
3.0  
2.9  
3.0  
3.0  
2.9  
Total BTUH [kW] 37.5 [10.99] 36.1 [10.58] 34.8 [10.20] 34.5 [10.11] 33.3 [9.76]  
32.1 [9.41]  
23.8 [6.98]  
3.0  
32.2 [9.44]  
30.0 [8.79]  
3.1  
31.0 [9.09]  
27.5 [8.06]  
3.1  
29.9 [8.76]  
24.9 [7.30]  
3.0  
115  
[46.1]  
Sens BTUH [kW] 23.2 [6.80] 21.2 [6.21] 19.2 [5.63] 28.7 [8.41] 26.3 [7.71]  
Power  
3.1  
3.1  
3.0  
3.1  
3.1  
DR —Depression ratio  
dbE —Entering air dry bulb  
wbE—Entering air wet bulb  
Total —Total capacity x 1000 BTUH  
Sens —Sensible capacity x 1000 BTUH  
Power—KW input  
NOTES:  
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible  
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].  
HEATING PERFORMANCE DATA—RJNA-A036  
IDB  
60°F [15.5°C]  
1200 [566]  
70°F [21.1°C]  
1200 [566]  
80°F [26.7°C]  
1200 [566]  
CFM [L/s]  
1440 [680]  
960 [453]  
1440 [680]  
960 [453]  
1440 [680]  
960 [453]  
0
Total BTUH [kW] 8.9 [2.61]  
8.7 [2.55]  
2.1  
8.6 [2.52]  
2.2  
7.0 [2.05]  
2.3  
6.9 [2.02]  
2.4  
6.8 [1.99]  
2.4  
5.3 [1.55]  
2.6  
5.2 [1.52]  
2.6  
5.1 [1.49]  
2.7  
O
U
T
D
O
O
R
[-17.8] Power 2.1  
5
Total BTUH [kW] 12.2 [3.58] 12.0 [3.52] 11.9 [3.49] 10.4 [3.05] 10.2 [2.99] 10.1 [2.96]  
8.6 [2.52]  
2.6  
8.5 [2.49]  
2.7  
8.4 [2.46]  
2.7  
[26.7] Power 2.1 2.2 2.2 2.4 2.4 2.5  
10 Total BTUH [kW] 15.5 [4.54] 15.3 [4.48] 15.1 [4.43] 13.6 [3.99] 13.5 [3.96] 13.3 [3.90] 11.9 [3.49]  
[-12.2] Power 2.2 2.2 2.3 2.4 2.5 2.5 2.6  
15 Total BTUH [kW] 18.7 [5.48] 18.5 [5.42] 18.2 [5.33] 16.9 [4.95] 16.6 [4.86] 16.4 [4.81] 15.1 [4.43]  
[32.2] Power 2.2 2.3 2.3 2.4 2.5 2.6 2.7  
20 Total BTUH [kW] 21.8 [6.39] 21.5 [6.30] 21.2 [6.21] 20.0 [5.86] 19.7 [5.77] 19.4 [5.69] 18.3 [5.36]  
[-6.6] Power 2.2 2.3 2.4 2.5 2.5 2.6 2.7  
25 Total BTUH [kW] 24.8 [7.27] 24.5 [7.18] 24.1 [7.06] 23.0 [6.74] 22.7 [6.65] 22.3 [6.54] 21.3 [6.24]  
[37.8] Power 2.3 2.3 2.4 2.5 2.6 2.6 2.8  
30 Total BTUH [kW] 27.7 [8.12] 27.3 [8.00] 26.9 [7.88] 25.9 [7.59] 25.5 [7.47] 25.1 [7.36] 24.1 [7.06]  
[-1.1] Power 2.3 2.4 2.4 2.5 2.6 2.7 2.8  
35 Total BTUH [kW] 30.5 [8.94] 30.0 [8.79] 29.6 [8.67] 28.6 [8.38] 28.2 [8.26] 27.8 [8.15] 26.9 [7.88]  
[43.3] Power 2.4 2.4 2.5 2.6 2.6 2.7 2.8  
40 Total BTUH [kW] 33.0 [9.67] 32.6 [9.55] 32.1 [9.41] 31.2 [9.14] 30.7 [9.00] 30.3 [8.88] 29.5 [8.65]  
[4.4] Power 2.4 2.5 2.5 2.6 2.7 2.7 2.9  
45 Total BTUH [kW] 35.4 [10.37] 34.9 [10.23] 34.4 [10.08] 33.6 [9.85] 33.1 [9.70] 32.6 [9.55] 31.9 [9.35]  
[46.1] Power 2.4 2.5 2.6 2.7 2.7 2.8 2.9  
50 Total BTUH [kW] 37.6 [11.02] 37.1 [10.87] 36.6 [10.73] 35.8 [10.49] 35.3 [10.35] 34.8 [10.20] 34.1 [9.99]  
[10] Power 2.5 2.5 2.6 2.7 2.8 2.8 2.9  
11.8 [3.46]  
2.7  
11.6 [3.40]  
2.8  
D
R
Y
14.9 [4.37]  
2.8  
14.7 [4.31]  
2.8  
18.0 [5.28]  
2.8  
17.7 [5.19]  
2.9  
B
U
L
21.0 [6.15]  
2.8  
20.7 [6.07]  
2.9  
B
T
E
M
P
E
R
A
T
23.8 [6.98]  
2.9  
23.5 [6.89]  
2.9  
26.5 [7.77]  
2.9  
26.1 [7.65]  
3.0  
29.0 [8.50]  
2.9  
28.6 [8.38]  
3.0  
U
R
E
31.4 [9.20]  
3.0  
33.6 [9.85]  
3.0  
31.0 [9.09]  
3.1  
33.1 [9.70]  
3.1  
°F  
[°C]  
IDB—Indoor air dry bulb  
[
] Designates Metric Conversions  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEMS PERFORMANCE—RJNA- SERIES  
COOLING PERFORMANCE DATA—RJNA-A042  
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀  
wbE  
CFM [L/s]  
DR ➀  
71°F [21.7°C]  
1400 [661]  
.15  
67°F [19.4°C]  
1400 [661]  
.15  
63°F [17.2°C]  
1400 [661]  
.15  
1680 [793]  
.18  
1120 [529]  
.11  
1680 [793]  
.18  
1120 [529]  
.11  
1680 [793]  
.18  
1120 [529]  
.11  
Total BTUH [kW] 50.3 [14.74] 48.5 [14.21] 46.8 [13.72] 47.6 [13.95] 46.0 [13.48] 44.3 [12.98] 45.0 [13.19] 43.4 [12.72] 41.9 [12.28]  
75  
[23.9]  
Sens BTUH [kW] 30.8 [9.03] 28.2 [8.26] 25.6 [7.50] 37.2 [10.90] 34.0 [9.96] 30.8 [9.03] 38.6 [11.31] 35.3 [10.35] 32.0 [9.38]  
Power  
2.3  
2.3  
2.2  
2.3  
2.3  
2.2  
2.3  
2.3  
2.2  
O
U
T
D
O
O
R
Total BTUH [kW] 50.3 [14.74] 48.5 [14.21] 46.8 [13.72] 47.7 [13.98] 46.0 [13.48] 44.3 [12.98] 45.1 [13.22] 43.5 [12.75] 41.9 [12.28]  
80  
Sens BTUH [kW] 30.8 [9.03] 28.1 [8.24] 25.5 [7.47] 37.1 [10.87] 33.9 [9.94] 30.8 [9.03] 38.5 [11.28] 35.2 [10.32] 31.9 [9.35]  
[26.7]  
Power  
2.4  
2.4  
2.4  
2.4  
2.4  
2.4  
2.4  
2.4  
2.4  
Total BTUH [kW] 49.6 [14.54] 47.8 [14.01] 46.1 [13.51] 46.9 [13.75] 45.3 [13.28] 43.6 [12.78] 44.3 [12.98] 42.8 [12.54] 41.2 [12.07]  
85  
[29.4]  
Sens BTUH [kW] 30.3 [8.88] 27.7 [8.12] 25.1 [7.36] 36.6 [10.73] 33.5 [9.82] 30.4 [8.91] 38.1 [11.17] 34.8 [10.20] 31.6 [9.26]  
Power  
2.6  
2.5  
2.5  
2.6  
2.5  
2.5  
2.6  
2.5  
2.5  
D
R
Y
Total BTUH [kW] 48.3 [14.16] 46.6 [13.66] 44.9 [13.16] 45.6 [13.36] 44.0 [12.90] 42.4 [12.43] 43.0 [12.60] 41.5 [12.16] 40.0 [11.72]  
90  
[32.2]  
Sens BTUH [kW] 29.6 [8.67] 27.1 [7.94] 24.5 [7.18] 35.9 [10.52] 32.9 [9.64] 29.8 [8.73] 37.4 [10.96] 34.2 [10.02] 31.0 [9.09]  
B
U
L
Power  
2.7  
2.7  
2.6  
2.7  
2.7  
2.6  
2.7  
2.7  
2.6  
Total BTUH [kW] 46.7 [13.69] 45.0 [13.19] 43.4 [12.72] 44.0 [12.90] 42.5 [12.46] 40.9 [11.99] 41.4 [12.13] 40.0 [11.72] 38.5 [11.28]  
95  
[35]  
B
Sens BTUH [kW] 28.8 [8.44] 26.3 [7.71] 23.9 [7.00] 35.1 [10.29] 32.1 [9.41] 29.1 [8.53] 36.5 [10.70] 33.4 [9.79] 30.3 [8.88]  
Power  
2.9  
2.8  
2.8  
2.9  
2.8  
2.8  
2.9  
2.8  
2.8  
T
E
M
P
E
R
A
T
Total BTUH [kW] 45.0 [13.19] 43.4 [12.72] 41.8 [12.25] 42.4 [12.43] 40.9 [11.99] 39.4 [11.55] 39.8 [11.66] 38.4 [11.25] 37.0 [10.84]  
100  
[37.8]  
Sens BTUH [kW] 27.9 [8.18] 25.5 [7.47] 23.1 [6.77] 34.3 [10.05] 31.3 [9.17] 28.4 [8.32] 35.7 [10.46] 32.6 [9.55] 29.6 [8.67]  
Power  
3.0  
3.0  
2.9  
3.0  
3.0  
2.9  
3.0  
3.0  
2.9  
Total BTUH [kW] 43.5 [12.75] 42.0 [12.31] 40.4 [11.84] 40.8 [11.96] 39.4 [11.55] 38.0 [11.14] 38.2 [11.20] 36.9 [10.81] 35.6 [10.43]  
105  
[40.6]  
Sens BTUH [kW] 27.2 [7.97] 24.9 [7.30] 22.5 [6.59] 33.5 [9.82] 30.7 [9.00] 27.8 [8.15] 34.9 [10.23] 32.0 [9.38] 29.0 [8.50]  
Power  
3.1  
3.1  
3.0  
3.1  
3.1  
3.0  
3.1  
3.1  
3.0  
U
R
E
Total BTUH [kW] 42.4 [12.43] 40.9 [11.99] 39.4 [11.55] 39.7 [11.63] 38.3 [11.22] 36.9 [10.81] 37.1 [10.87] 35.8 [10.49] 34.5 [10.11]  
110  
[43.3]  
Sens BTUH [kW] 26.7 [7.83] 24.4 [7.15] 22.1 [6.48] 33.0 [9.67] 30.2 [8.85] 27.4 [8.03] 34.4 [10.08] 31.5 [9.23] 28.6 [8.38]  
°F  
[°C]  
Power  
3.3  
3.2  
3.2  
3.3  
3.2  
3.2  
3.3  
3.2  
3.2  
Total BTUH [kW] 41.9 [12.28] 40.4 [11.84] 39.0 [11.43] 39.3 [11.52] 37.9 [11.11] 36.5 [10.70] 36.7 [10.76] 35.4 [10.37] 34.1 [9.99]  
115  
[46.1]  
Sens BTUH [kW] 26.5 [7.77] 24.3 [7.12] 22.0 [6.45] 32.9 [9.64] 30.1 [8.82] 27.3 [8.00] 34.3 [10.05] 31.4 [9.20] 28.4 [8.32]  
Power  
3.4  
3.4  
3.3  
3.4  
3.4  
3.3  
3.4  
3.4  
3.3  
DR —Depression ratio  
dbE —Entering air dry bulb  
wbE—Entering air wet bulb  
Total —Total capacity x 1000 BTUH  
Sens —Sensible capacity x 1000 BTUH  
Power—KW input  
NOTES:  
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible  
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].  
HEATING PERFORMANCE DATA—RJNA-A042  
IDB  
60°F [15.5°C]  
1400 [661]  
70°F [21.1°C]  
1400 [661]  
80°F [26.7°C]  
1400 [661]  
CFM [L/s]  
1680 [793]  
1120 [529]  
1680 [793]  
1120 [529]  
1680 [793]  
1120 [529]  
0
Total BTUH [kW] 9.5 [2.78]  
9.4 [2.75]  
2.1  
9.3 [2.73]  
2.1  
8.7 [2.55]  
2.3  
8.6 [2.52]  
2.4  
8.5 [2.49]  
2.5  
7.1 [2.08]  
2.6  
7.0 [2.05]  
2.7  
6.9 [2.02]  
2.7  
O
U
T
D
O
O
R
[-17.8] Power 2.0  
5
Total BTUH [kW] 13.9 [4.07] 13.7 [4.02] 13.5 [3.96] 13.1 [3.84] 12.9 [3.78] 12.7 [3.72] 11.5 [3.37] 11.4 [3.34] 11.2 [3.28]  
[26.7] Power 2.1 2.1 2.2 2.4 2.5 2.5 2.7 2.7 2.8  
10 Total BTUH [kW] 17.1 [5.01] 16.9 [4.95] 16.7 [4.89] 16.3 [4.78] 16.1 [4.72] 15.9 [4.66] 14.8 [4.34] 14.6 [4.28] 14.3 [4.19]  
[-12.2] Power 2.2 2.2 2.3 2.5 2.5 2.6 2.7 2.8 2.9  
15 Total BTUH [kW] 19.5 [5.71] 19.3 [5.66] 19.0 [5.57] 18.7 [5.48] 18.4 [5.39] 18.2 [5.33] 17.2 [5.04] 16.9 [4.95] 16.7 [4.89]  
[32.2] Power 2.2 2.3 2.3 2.5 2.6 2.7 2.8 2.9 2.9  
20 Total BTUH [kW] 21.5 [6.30] 21.2 [6.21] 20.9 [6.13] 20.6 [6.04] 20.4 [5.98] 20.1 [5.89] 19.1 [5.60] 18.8 [5.51] 18.6 [5.45]  
[-6.6] Power 2.3 2.3 2.4 2.6 2.7 2.7 2.9 2.9 3.0  
25 Total BTUH [kW] 23.3 [6.83] 23.0 [6.74] 22.7 [6.65] 22.5 [6.59] 22.2 [6.51] 21.8 [6.39] 20.9 [6.13] 20.6 [6.04] 20.3 [5.95]  
[37.8] Power 2.3 2.4 2.5 2.7 2.7 2.8 2.9 3.0 3.1  
30 Total BTUH [kW] 25.4 [7.44] 25.1 [7.36] 24.7 [7.24] 24.6 [7.21] 24.2 [7.09] 23.9 [7.00] 23.0 [6.74] 22.7 [6.65] 22.4 [6.56]  
[-1.1] Power 2.4 2.5 2.5 2.7 2.8 2.9 3.0 3.1 3.2  
35 Total BTUH [kW] 28.1 [8.24] 27.8 [8.15] 27.4 [8.03] 27.3 [8.00] 26.9 [7.88] 26.5 [7.77] 25.8 [7.56] 25.4 [7.44] 25.0 [7.33]  
[43.3] Power 2.5 2.5 2.6 2.8 2.9 2.9 3.1 3.1 3.2  
40 Total BTUH [kW] 31.9 [9.35] 31.4 [9.20] 31.0 [9.09] 31.0 [9.09] 30.6 [8.97] 30.2 [8.85] 29.5 [8.65] 29.1 [8.53] 28.7 [8.41]  
[4.4] Power 2.5 2.6 2.7 2.9 2.9 3.0 3.1 3.2 3.3  
45 Total BTUH [kW] 36.9 [10.81] 36.4 [10.67] 35.9 [10.52] 36.1 [10.58] 35.6 [10.43] 35.1 [10.29] 34.6 [10.14] 34.1 [9.99] 33.6 [9.85]  
[46.1] Power 2.6 2.7 2.7 2.9 3.0 3.1 3.2 3.3 3.4  
50 Total BTUH [kW] 43.7 [12.81] 43.1 [12.63] 42.5 [12.46] 42.9 [12.57] 42.3 [12.40] 41.7 [12.22] 41.3 [12.10] 40.8 [11.96] 40.2 [11.78]  
[10] Power 2.7 2.7 2.8 3.0 3.1 3.1 3.3 3.3 3.4  
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F  
[°C]  
IDB—Indoor air dry bulb  
[
] Designates Metric Conversions  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEMS PERFORMANCE—RJNA- SERIES  
COOLING PERFORMANCE DATA—RJNA-A048  
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀  
wbE  
CFM [L/s]  
DR ➀  
71°F [21.7°C]  
1600 [755]  
.15  
67°F [19.4°C]  
1600 [755]  
.15  
63°F [17.2°C]  
1600 [755]  
.15  
1920 [906]  
.18  
1280 [604]  
.11  
1920 [906]  
.18  
1280 [604]  
.11  
1920 [906]  
.18  
1280 [604]  
.11  
Total BTUH [kW] 59.9 [17.55] 57.8 [16.94] 55.7 [16.32] 56.2 [16.47] 54.3 [15.91] 52.3 [15.33] 53.5 [15.68] 51.7 [15.15] 49.8 [14.59]  
75  
[23.9]  
Sens BTUH [kW] 35.6 [10.43] 32.6 [9.55] 29.5 [8.65] 43.0 [12.60] 39.3 [11.52] 35.6 [10.43] 46.0 [13.48] 42.0 [12.31] 38.1 [11.17]  
Power  
2.7  
2.6  
2.6  
2.7  
2.7  
2.6  
2.7  
2.6  
2.6  
O
U
T
D
O
O
R
Total BTUH [kW] 58.7 [17.20] 56.6 [16.59] 54.5 [15.97] 55.0 [16.12] 53.1 [15.56] 51.2 [15.01] 52.3 [15.33] 50.5 [14.80] 48.7 [14.27]  
80  
Sens BTUH [kW] 35.1 [10.29] 32.1 [9.41] 29.1 [8.53] 42.5 [12.46] 38.8 [11.37] 35.2 [10.32] 45.5 [13.33] 41.6 [12.19] 37.7 [11.05]  
[26.7]  
Power  
2.9  
2.8  
2.8  
2.9  
2.8  
2.8  
2.9  
2.8  
2.8  
Total BTUH [kW] 57.4 [16.82] 55.4 [16.24] 53.4 [15.65] 53.8 [15.77] 51.9 [15.21] 50.0 [14.65] 51.1 [14.98] 49.3 [14.45] 47.5 [13.92]  
85  
[29.4]  
Sens BTUH [kW] 34.6 [10.14] 31.6 [9.26] 28.7 [8.41] 41.9 [12.28] 38.3 [11.22] 34.7 [10.17] 44.9 [13.16] 41.1 [12.05] 37.2 [10.90]  
Power  
3.0  
3.0  
3.0  
3.1  
3.0  
3.0  
3.0  
3.0  
2.9  
D
R
Y
Total BTUH [kW] 56.1 [16.44] 54.1 [15.86] 52.1 [15.27] 52.5 [15.39] 50.6 [14.83] 48.8 [14.30] 49.8 [14.59] 48.0 [14.07] 46.3 [13.57]  
90  
[32.2]  
Sens BTUH [kW] 33.9 [9.94] 31.0 [9.09] 28.1 [8.24] 41.2 [12.07] 37.7 [11.05] 34.2 [10.02] 44.2 [12.95] 40.4 [11.84] 36.7 [10.76]  
B
U
L
Power  
3.2  
3.2  
3.1  
3.2  
3.2  
3.1  
3.2  
3.2  
3.1  
Total BTUH [kW] 54.7 [16.03] 52.8 [15.47] 50.9 [14.92] 51.1 [14.98] 49.3 [14.45] 47.5 [13.92] 48.4 [14.18] 46.7 [13.69] 45.0 [13.19]  
95  
[35]  
B
Sens BTUH [kW] 33.1 [9.70] 30.3 [8.88] 27.5 [8.06] 40.4 [11.84] 37.0 [10.84] 33.5 [9.82] 43.5 [12.75] 39.7 [11.63] 36.0 [10.55]  
Power  
3.4  
3.4  
3.3  
3.4  
3.4  
3.3  
3.4  
3.3  
3.3  
T
E
M
P
E
R
A
T
Total BTUH [kW] 53.3 [15.62] 51.4 [15.06] 49.5 [14.51] 49.6 [14.54] 47.9 [14.04] 46.2 [13.54] 46.9 [13.75] 45.3 [13.28] 43.6 [12.78]  
100  
[37.8]  
Sens BTUH [kW] 32.3 [9.47] 29.6 [8.67] 26.8 [7.85] 39.6 [11.61] 36.3 [10.64] 32.9 [9.64] 42.7 [12.51] 39.0 [11.43] 35.4 [10.37]  
Power  
3.6  
3.5  
3.5  
3.6  
3.5  
3.5  
3.6  
3.5  
3.5  
Total BTUH [kW] 51.7 [15.15] 49.9 [14.62] 48.1 [14.10] 48.1 [14.10] 46.4 [13.60] 44.7 [13.10] 45.4 [13.31] 43.8 [12.84] 42.2 [12.37]  
105  
[40.6]  
Sens BTUH [kW] 31.5 [9.23] 28.8 [8.44] 26.1 [7.65] 38.8 [11.37] 35.5 [10.40] 32.2 [9.44] 41.9 [12.28] 38.3 [11.22] 34.7 [10.17]  
Power  
3.8  
3.7  
3.6  
3.8  
3.7  
3.7  
3.7  
3.7  
3.6  
U
R
E
Total BTUH [kW] 50.2 [14.71] 48.4 [14.18] 46.6 [13.66] 46.5 [13.63] 44.9 [13.16] 43.3 [12.69] 43.8 [12.84] 42.3 [12.40] 40.8 [11.96]  
110  
[43.3]  
Sens BTUH [kW] 30.7 [9.00] 28.1 [8.24] 25.5 [7.47] 38.0 [11.14] 34.8 [10.20] 31.5 [9.23] 41.0 [12.02] 37.5 [10.99] 34.0 [9.96]  
°F  
[°C]  
Power  
3.9  
3.9  
3.8  
4.0  
3.9  
3.8  
3.9  
3.9  
3.8  
Total BTUH [kW] 48.5 [14.21] 46.8 [13.72] 45.1 [13.22] 44.9 [13.16] 43.3 [12.69] 41.7 [12.22] 42.2 [12.37] 40.7 [11.93] 39.2 [11.49]  
115  
[46.1]  
Sens BTUH [kW] 29.9 [8.76] 27.4 [8.03] 24.8 [7.27] 37.2 [10.90] 34.1 [9.99] 30.9 [9.06] 40.3 [11.81] 36.8 [10.79] 33.4 [9.79]  
Power  
4.1  
4.0  
4.0  
4.1  
4.1  
4.0  
4.1  
4.0  
4.0  
DR —Depression ratio  
dbE —Entering air dry bulb  
wbE—Entering air wet bulb  
Total —Total capacity x 1000 BTUH  
Sens —Sensible capacity x 1000 BTUH  
Power—KW input  
NOTES:  
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible  
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].  
HEATING PERFORMANCE DATA—RJNA-A048  
IDB  
60°F [15.5°C]  
1200 [566]  
70°F [21.1°C]  
1200 [566]  
80°F [26.7°C]  
1200 [566]  
CFM [L/s]  
1440 [680]  
960 [453]  
1440 [680]  
960 [453]  
1440 [680]  
960 [453]  
0
Total BTUH [kW] 13.5 [3.96] 13.3 [3.90] 13.1 [3.84] 13.0 [3.81] 12.8 [3.75] 12.6 [3.69] 12.0 [3.52] 11.8 [3.46] 11.6 [3.40]  
[-17.8] Power 2.4 2.4 2.5 2.7 2.8 2.8 3.1 3.1 3.2  
Total BTUH [kW] 17.3 [5.07] 17.1 [5.01] 16.8 [4.92] 16.8 [4.92] 16.5 [4.84] 16.3 [4.78] 15.8 [4.63] 15.5 [4.54] 15.3 [4.48]  
[26.7] Power 2.4 2.5 2.6 2.8 2.8 2.9 3.1 3.2 3.3  
10 Total BTUH [kW] 21.0 [6.15] 20.7 [6.07] 20.4 [5.98] 20.5 [6.01] 20.2 [5.92] 19.9 [5.83] 19.5 [5.71] 19.2 [5.63] 18.9 [5.54]  
[-12.2] Power 2.5 2.5 2.6 2.8 2.9 2.9 3.2 3.2 3.3  
15 Total BTUH [kW] 24.6 [7.21] 24.3 [7.12] 23.9 [7.00] 24.1 [7.06] 23.7 [6.95] 23.4 [6.86] 23.1 [6.77] 22.7 [6.65] 22.4 [6.56]  
[32.2] Power 2.5 2.6 2.6 2.8 2.9 3.0 3.2 3.3 3.4  
20 Total BTUH [kW] 28.1 [8.24] 27.7 [8.12] 27.3 [8.00] 27.6 [8.09] 27.2 [7.97] 26.8 [7.85] 26.6 [7.80] 26.2 [7.68] 25.8 [7.56]  
[-6.6] Power 2.6 2.6 2.7 2.9 3.0 3.0 3.3 3.3 3.4  
25 Total BTUH [kW] 31.5 [9.23] 31.1 [9.11] 30.6 [8.97] 31.0 [9.09] 30.6 [8.97] 30.1 [8.82] 30.0 [8.79] 29.6 [8.67] 29.1 [8.53]  
[37.8] Power 2.6 2.7 2.7 2.9 3.0 3.1 3.3 3.4 3.5  
30 Total BTUH [kW] 34.8 [10.20] 34.3 [10.05] 33.9 [9.94] 34.3 [10.05] 33.8 [9.91] 33.3 [9.76] 33.3 [9.76] 32.8 [9.61] 32.4 [9.50]  
[-1.1] Power 2.7 2.7 2.8 3.0 3.1 3.1 3.3 3.4 3.5  
35 Total BTUH [kW] 38.1 [11.17] 37.5 [10.99] 37.0 [10.84] 37.5 [10.99] 37.0 [10.84] 36.5 [10.70] 36.5 [10.70] 36.0 [10.55] 35.5 [10.40]  
[43.3] Power 2.7 2.8 2.8 3.0 3.1 3.2 3.4 3.5 3.6  
40 Total BTUH [kW] 41.2 [12.07] 40.6 [11.90] 40.0 [11.72] 40.7 [11.93] 40.1 [11.75] 39.5 [11.58] 39.7 [11.63] 39.1 [11.46] 38.5 [11.28]  
[4.4] Power 2.8 2.8 2.9 3.1 3.2 3.2 3.4 3.5 3.6  
45 Total BTUH [kW] 44.2 [12.95] 43.6 [12.78] 43.0 [12.60] 43.7 [12.81] 43.1 [12.63] 42.5 [12.46] 42.7 [12.51] 42.1 [12.34] 41.5 [12.16]  
[46.1] Power 2.8 2.9 2.9 3.1 3.2 3.3 3.5 3.6 3.7  
50 Total BTUH [kW] 47.2 [13.83] 46.5 [13.63] 45.8 [13.42] 46.6 [13.66] 46.0 [13.48] 45.3 [13.28] 45.6 [13.36] 45.0 [13.19] 44.3 [12.98]  
[10] Power 2.8 2.9 3.0 3.2 3.3 3.3 3.5 3.6 3.7  
O
U
T
D
O
O
R
5
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F  
[°C]  
IDB—Indoor air dry bulb  
[
] Designates Metric Conversions  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEMS PERFORMANCE—RJNA- SERIES  
COOLING PERFORMANCE DATA—RJNA-A060  
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀  
wbE  
CFM [L/s]  
DR ➀  
71°F [21.7°C]  
2000 [944]  
.19  
67°F [19.4°C]  
2000 [944]  
.19  
63°F [17.2°C]  
2000 [944]  
.19  
2500 [1180]  
.22  
1500 [708]  
.15  
2500 [1180]  
.22  
1500 [708]  
.15  
2500 [1180]  
.22  
1500 [708]  
.15  
Total BTUH [kW] 74.9 [21.95] 71.6 [20.98] 68.4 [20.05] 71.3 [20.90] 68.2 [19.99] 65.1 [19.08] 67.6 [19.81] 64.6 [18.93] 61.7 [18.08]  
75  
[23.9]  
Sens BTUH [kW] 44.2 [12.95] 39.6 [11.61] 35.0 [10.26] 53.4 [15.65] 47.8 [14.01] 42.3 [12.40] 57.5 [16.85] 51.5 [15.09] 45.5 [13.33]  
Power  
4.0  
3.9  
3.8  
3.9  
3.9  
3.8  
3.9  
3.8  
3.8  
O
U
T
D
O
O
R
Total BTUH [kW] 74.4 [21.80] 71.2 [20.87] 67.9 [19.90] 70.8 [20.75] 67.7 [19.84] 64.6 [18.93] 67.1 [19.67] 64.2 [18.82] 61.2 [17.94]  
80  
Sens BTUH [kW] 44.3 [12.98] 39.7 [11.63] 35.0 [10.26] 53.5 [15.68] 47.9 [14.04] 42.3 [12.40] 57.6 [16.88] 51.5 [15.09] 45.5 [13.33]  
[26.7]  
Power  
4.2  
4.1  
4.1  
4.2  
4.1  
4.0  
4.1  
4.1  
4.0  
Total BTUH [kW] 73.3 [21.48] 70.2 [20.57] 67.0 [19.64] 69.7 [20.43] 66.7 [19.55] 63.6 [18.64] 66.0 [19.34] 63.1 [18.49] 60.3 [17.67]  
85  
[29.4]  
Sens BTUH [kW] 43.8 [12.84] 39.2 [11.49] 34.7 [10.17] 53.0 [15.53] 47.5 [13.92] 41.9 [12.28] 57.1 [16.73] 51.1 [14.98] 45.2 [13.25]  
Power  
4.5  
4.4  
4.3  
4.4  
4.3  
4.2  
4.4  
4.3  
4.2  
D
R
Y
Total BTUH [kW] 71.8 [21.04] 68.7 [20.13] 65.6 [19.23] 68.2 [19.99] 65.2 [19.11] 62.3 [18.26] 64.5 [18.90] 61.7 [18.08] 58.9 [17.26]  
90  
[32.2]  
Sens BTUH [kW] 43.0 [12.60] 38.5 [11.28] 34.0 [9.96] 52.2 [15.30] 46.7 [13.69] 41.3 [12.10] 56.3 [16.50] 50.4 [14.77] 44.5 [13.04]  
B
U
L
Power  
4.7  
4.6  
4.5  
4.6  
4.5  
4.4  
4.6  
4.5  
4.4  
Total BTUH [kW] 70.0 [20.51] 67.0 [19.64] 63.9 [18.73] 66.4 [19.46] 63.5 [18.61] 60.6 [17.76] 62.7 [18.38] 60.0 [17.58] 57.2 [16.76]  
95  
[35]  
B
Sens BTUH [kW] 41.9 [12.28] 37.5 [10.99] 33.2 [9.73] 51.1 [14.98] 45.8 [13.42] 40.4 [11.84] 55.2 [16.18] 49.4 [14.48] 43.7 [12.81]  
Power  
4.9  
4.8  
4.7  
4.8  
4.7  
4.6  
4.8  
4.7  
4.6  
T
E
M
P
E
R
A
T
Total BTUH [kW] 68.0 [19.93] 65.1 [19.08] 62.1 [18.20] 64.4 [18.87] 61.6 [18.05] 58.8 [17.23] 60.7 [17.79] 58.1 [17.03] 55.4 [16.24]  
100  
[37.8]  
Sens BTUH [kW] 40.7 [11.93] 36.5 [10.70] 32.2 [9.44] 49.9 [14.62] 44.7 [13.10] 39.5 [11.58] 54.0 [15.83] 48.4 [14.18] 42.7 [12.51]  
Power  
5.1  
5.0  
4.9  
5.1  
5.0  
4.9  
5.0  
4.9  
4.8  
Total BTUH [kW] 66.0 [19.34] 63.1 [18.49] 60.3 [17.67] 62.4 [18.29] 59.7 [17.50] 56.9 [16.68] 58.7 [17.20] 56.1 [16.44] 53.6 [15.71]  
105  
[40.6]  
Sens BTUH [kW] 39.6 [11.61] 35.4 [10.37] 31.3 [9.17] 48.8 [14.30] 43.7 [12.81] 38.6 [11.31] 52.8 [15.47] 47.3 [13.86] 41.8 [12.25]  
Power  
5.4  
5.3  
5.1  
5.3  
5.2  
5.1  
5.3  
5.2  
5.1  
U
R
E
Total BTUH [kW] 64.1 [18.79] 61.3 [17.97] 58.5 [17.14] 60.5 [17.73] 57.8 [16.94] 55.2 [16.18] 56.8 [16.65] 54.3 [15.91] 51.8 [15.18]  
110  
[43.3]  
Sens BTUH [kW] 38.5 [11.28] 34.5 [10.11] 30.5 [8.94] 47.7 [13.98] 42.7 [12.51] 37.8 [11.08] 51.8 [15.18] 46.4 [13.60] 41.0 [12.02]  
°F  
[°C]  
Power  
5.6  
5.5  
5.4  
5.5  
5.4  
5.3  
5.5  
5.4  
5.3  
Total BTUH [kW] 62.4 [18.29] 59.7 [17.50] 57.0 [16.71] 58.8 [17.23] 56.2 [16.47] 53.7 [15.74] 55.1 [16.15] 52.7 [15.44] 50.3 [14.74]  
115  
[46.1]  
Sens BTUH [kW] 37.8 [11.08] 33.8 [9.91] 29.9 [8.76] 47.0 [13.77] 42.1 [12.34] 37.2 [10.90] 51.1 [14.98] 45.7 [13.39] 40.4 [11.84]  
Power  
5.8  
5.7  
5.6  
5.7  
5.6  
5.5  
5.7  
5.6  
5.5  
DR —Depression ratio  
dbE —Entering air dry bulb  
wbE—Entering air wet bulb  
Total —Total capacity x 1000 BTUH  
Sens —Sensible capacity x 1000 BTUH  
Power—KW input  
NOTES:  
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible  
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].  
HEATING PERFORMANCE DATA—RJNA-A060  
IDB  
60°F [15.5°C]  
2000 [944]  
70°F [21.1°C]  
2000 [944]  
80°F [26.7°C]  
2000 [944]  
CFM [L/s]  
2500 [1180]  
1500 [708]  
2500 [1180]  
1500 [708]  
2500 [1180]  
1500 [708]  
0
Total BTUH [kW] 16.6 [4.86] 16.3 [4.78] 16.0 [4.69] 15.0 [4.40] 14.7 [4.31] 14.4 [4.22] 14.9 [4.37] 14.6 [4.28] 14.4 [4.22]  
[-17.8] Power 3.0 3.1 3.2 3.4 3.5 3.7 3.9 4.1 4.2  
Total BTUH [kW] 22.7 [6.65] 22.3 [6.54] 21.9 [6.42] 21.1 [6.18] 20.7 [6.07] 20.3 [5.95] 21.0 [6.15] 20.6 [6.04] 20.3 [5.95]  
[26.7] Power 3.1 3.2 3.3 3.5 3.6 3.7 4.0 4.2 4.3  
10 Total BTUH [kW] 28.5 [8.35] 28.0 [8.21] 27.5 [8.06] 26.9 [7.88] 26.4 [7.74] 25.9 [7.59] 26.8 [7.85] 26.3 [7.71] 25.9 [7.59]  
[-12.2] Power 3.2 3.3 3.4 3.6 3.7 3.8 4.1 4.2 4.4  
15 Total BTUH [kW] 34.0 [9.96] 33.4 [9.79] 32.8 [9.61] 32.3 [9.47] 31.8 [9.32] 31.2 [9.14] 32.3 [9.47] 31.7 [9.29] 31.1 [9.11]  
[32.2] Power 3.3 3.4 3.5 3.7 3.8 3.9 4.2 4.3 4.5  
20 Total BTUH [kW] 39.1 [11.46] 38.4 [11.25] 37.7 [11.05] 37.5 [10.99] 36.8 [10.79] 36.2 [10.61] 37.4 [10.96] 36.8 [10.79] 36.1 [10.58]  
[-6.6] Power 3.4 3.5 3.6 3.8 3.9 4.0 4.3 4.4 4.6  
25 Total BTUH [kW] 43.9 [12.87] 43.2 [12.66] 42.4 [12.43] 42.3 [12.40] 41.5 [12.16] 40.8 [11.96] 42.2 [12.37] 41.5 [12.16] 40.7 [11.93]  
[37.8] Power 3.5 3.6 3.7 3.9 4.0 4.1 4.4 4.5 4.7  
30 Total BTUH [kW] 48.4 [14.18] 47.6 [13.95] 46.7 [13.69] 46.8 [13.72] 46.0 [13.48] 45.1 [13.22] 46.7 [13.69] 45.9 [13.45] 45.1 [13.22]  
[-1.1] Power 3.5 3.7 3.8 4.0 4.1 4.2 4.5 4.6 4.8  
35 Total BTUH [kW] 52.6 [15.42] 51.7 [15.15] 50.7 [14.86] 50.9 [14.92] 50.1 [14.68] 49.2 [14.42] 50.9 [14.92] 50.0 [14.65] 49.1 [14.39]  
[43.3] Power 3.6 3.7 3.9 4.0 4.2 4.3 4.6 4.7 4.8  
40 Total BTUH [kW] 56.4 [16.53] 55.4 [16.24] 54.5 [15.97] 54.8 [16.06] 53.8 [15.77] 52.9 [15.50] 54.7 [16.03] 53.8 [15.77] 52.8 [15.47]  
[4.4] Power 3.7 3.8 4.0 4.1 4.3 4.4 4.6 4.8 4.9  
45 Total BTUH [kW] 59.9 [17.55] 58.9 [17.26] 57.8 [16.94] 58.3 [17.09] 57.3 [16.79] 56.3 [16.50] 58.2 [17.06] 57.2 [16.76] 56.2 [16.47]  
[46.1] Power 3.8 3.9 4.1 4.2 4.4 4.5 4.7 4.9 5.0  
50 Total BTUH [kW] 63.1 [18.49] 62.0 [18.17] 60.9 [17.85] 61.5 [18.02] 60.4 [17.70] 59.3 [17.38] 61.4 [17.99] 60.4 [17.70] 59.3 [17.38]  
[10] Power 3.9 4.0 4.1 4.3 4.5 4.6 4.8 5.0 5.1  
O
U
T
D
O
O
R
5
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F  
[°C]  
IDB—Indoor air dry bulb  
[
] Designates Metric Conversions  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AIRFLOW PERFORMANCE—RJNA- SERIES  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AIRFLOW PERFORMANCE—RJNA- SERIES  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AIRFLOW PERFORMANCE—RJNA- SERIES  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA—RJNA- SERIES  
ELECTRICAL DATA – RJNA SERIES  
-A036CK -A036CL -A036CM -A036DK -A036DL -A036DM -A036JK -A042CK -A042CL -A042CM -A042DK -A042DL -A042DM -A042JK  
Unit Operating  
Voltage Range  
187-253 187-253 187-253 414-506 414-506 414-506 187-253 187-253 187-253 187-253 414-506 414-506 414-506 187-253  
Minimum Circuit  
Ampacity  
Minimum Overcurrent  
Protection Device Size  
Maximum Overcurrent  
Protection Device Size  
19/19  
25/25  
18/18  
20/20  
19/19  
25/25  
9
9
9
25/25  
30/30  
20/20  
25/25  
19/19  
25/25  
20/20  
25/25  
10  
15  
15  
10  
15  
15  
10  
15  
15  
27/27  
35/35  
40/40  
15  
15  
15  
15  
15  
15  
25/25  
1
25/25  
1
25/25  
1
35/35  
1
25/25  
1
25/25  
1
25/25  
1
No.  
Volts  
1
460  
3
1
460  
3
1
460  
3
1
460  
3
1
460  
3
1
460  
3
1
208/230 208/230 208/230  
208/230 208/230 208/230 208/230  
208/230  
Phase  
3
3
3
1
3
3
3
3
3
3
1
HP  
2.5  
2.5  
2.5  
2.5  
3450  
4.8  
35  
1
2.5  
3450  
4.8  
35  
1
2.5  
3450  
4.8  
35  
1
2.5  
3
3
3
3
3450  
16.5/16.5  
95/95  
1
RPM  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
5.1  
39  
1
3450  
5.1  
39  
1
3450  
5.1  
39  
1
Amps (RLA)  
Amps (LRA)  
No.  
9.6/9.6 9.6/9.6 9.6/9.6  
15/15 10.3/10.3 10.3/10.3 10.3/10.3  
77/77  
1
77/77  
1
77/77  
1
83/83  
1
77/77  
1
77/77  
1
77/77  
1
Volts  
208/230 208/230 208/230  
460  
1
460  
1
460  
1
208/230 208/230 208/230 208/230  
460  
1
460  
1
460  
1
208/230  
1
Phase  
1
1
1
1
1
1
1
HP  
1/3  
2.2  
4.7  
1
1/3  
2.2  
4.7  
1
1/3  
2.2  
4.7  
1
1/3  
1
1/3  
1
1/3  
1
1/3  
2.2  
4.7  
1
1/3  
2.2  
4.7  
1
1/3  
2.2  
4.7  
1
1/3  
2.2  
4.7  
1
1/3  
1
1/3  
1
1/3  
1
1/3  
Amps (FLA)  
Amps (LRA)  
No.  
2.2  
2.4  
1
2.4  
1
2.4  
1
2.4  
1
2.4  
1
2.4  
1
4.7  
1
Volts  
208/230 208/230 208/230  
460  
1
460  
3
460  
3
208/230 208/230 208/230 208/230  
460  
1
460  
3
460  
3
208/230  
1
Phase  
1
3
3
1
1
3
3
HP  
1/2  
2.7  
6.5  
1/2  
2.2  
10.6  
3/4  
3.2  
16.8  
1/2  
1.5  
3.6  
1/2  
1.1  
5.3  
3/4  
1.6  
8.4  
1/2  
2.7  
6.5  
1/2  
2.7  
6.5  
1/2  
2.2  
10.6  
3/4  
3.2  
16.8  
1/2  
1.5  
3.6  
1/2  
1.1  
5.3  
3/4  
1.6  
8.4  
1/2  
Amps (FLA)  
Amps (LRA)  
2.7  
6.5  
1. Horsepower Per Compressor.  
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA—RJNA- SERIES  
ELECTRICAL DATA – RJNA SERIES  
-A048CK -A048CL -A048CM -A048DK -A048DL -A048DM -A048JK -A060CK -A060CL -A060CM -A060DL -A060DM -A060JK  
Unit Operating  
Voltage Range  
187-253 187-253 187-253 414-506 414-506 414-506 187-253 187-253 187-253 187-253 414-506 414-506 187-253  
Minimum Circuit  
Ampacity  
Minimum Overcurrent  
Protection Device Size  
Maximum Overcurrent  
Protection Device Size  
22/22  
25/25  
21/21  
25/25  
22/22  
25/25  
11  
15  
15  
11  
15  
15  
11  
15  
15  
30/30  
35/35  
32/32  
40/40  
28/28  
35/35  
28/28  
35/35  
14  
20  
20  
14  
20  
20  
46/46  
60/60  
60/60  
30/30  
1
30/30  
1
30/30  
1
45/45  
1
45/45  
1
45/45  
1
45/45  
1
No.  
Volts  
1
460  
3
1
460  
3
1
460  
3
1
460  
3
1
460  
3
1
208/230 208/230 208/230  
208/230 208/230 208/230 208/230  
208/230  
Phase  
3
3
3
1
3
5
3
5
3
5
1
HP  
3.5  
3.5  
3.5  
3.5  
3450  
6.4  
44  
1
3.5  
3450  
6.4  
44  
1
3.5  
3450  
6.4  
44  
1
3.5  
5
5
5
RPM  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
8.2  
62  
1
3450  
8.2  
62  
1
3450  
Amps (RLA)  
Amps (LRA)  
No.  
12.4/12.4 12.4/12.4 12.4/12.4  
18.3/18.3 17.3/17.3 17.3/17.3 17.3/17.3  
109/109 123/123 123/123 123/123  
28.8/28.8  
88/88  
1
88/88  
1
88/88  
1
148/148  
1
1
1
1
1
Volts  
208/230 208/230 208/230  
460  
1
460  
1
460  
1
208/230 208/230 208/230 208/230  
460  
1
460  
1
208/230  
Phase  
1
1
1
1
1
1
1
1
HP  
1/3  
2.2  
4.7  
1
1/3  
2.2  
4.7  
1
1/3  
2.2  
4.7  
1
1/3  
1
1/3  
1
1/3  
1
1/3  
2.2  
4.7  
1
1/3  
2.2  
4.7  
1
1/3  
2.2  
4.7  
1
1/3  
2.2  
4.7  
1
1/3  
1
1/3  
1
1/3  
Amps (FLA)  
Amps (LRA)  
No.  
2.2  
2.4  
1
2.4  
1
2.4  
1
2.4  
1
2.4  
1
4.7  
1
Volts  
208/230 208/230 208/230  
460  
1
460  
3
460  
3
208/230 208/230 208/230 208/230  
460  
3
460  
3
208/230  
Phase  
1
3
3
1
1
1
3
3
1
1
HP  
1/2  
2.7  
6.5  
1/2  
2.2  
10.6  
3/4  
3.2  
16.8  
1/2  
1.5  
3.6  
1/2  
1.1  
5.3  
3/4  
1.6  
8.4  
1/2  
2.7  
6.5  
3/4  
3.2  
16.8  
1
3/4  
1.6  
8.4  
1
Amps (FLA)  
Amps (LRA)  
7.6  
0
3.8  
24  
1.9  
12  
7.6  
0
1. Horsepower Per Compressor.  
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNITS WITH HEATER KITS—RJNA- SERIES  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNITS WITH HEATER KITS—RJNA- SERIES  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNITS WITH HEATER KITS—RJNA- SERIES  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNITS WITH HEATER KITS—RJNA- SERIES  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNITS WITH HEATER KITS—RJNA- SERIES  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNITS WITH HEATER KITS—RJNA- SERIES  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNITS WITH HEATER KITS—RJNA- SERIES  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT DIMENSIONS—RJNA- SERIES  
UNI
PAC
HEA
[
] Designates Metric Conversions  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT DIMENSIONS—RJNA- SERIES  
UNIT DIMENSIONS  
PACKAGE  
HEAT PUMPS  
BOTTOM VIEW  
[
] Designates Metric Conversions  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT DIMENSIONS—RJNA- SERIES  
SELECTION PROCEDURE  
1. Determine cooling and heating requirements at design  
conditions.  
3. Determine blower speed and power to meet the system  
requirements.  
At the given external static pressure of 1.1 in wg, the belt model  
must be selected. Enter the belt drive blower performance table  
at 1600 CFM [755 L/s] and 1.1 in wg ESP:  
RPM ..................1205  
Example:  
Total cooling capacity ............43,600 BTUH [12.78 kW]  
Sensible cooling capacity ......34,000 BTUH [9.96 kW]  
Condenser entering air ..........95°F [35°C]  
Evaporator entering air ..........63°F [17°C] wb/76°F [24°C] db  
Indoor air flow ........................1600 CFM [755 L/s]  
External static pressure..........1.1 in wg  
Required efficiency ................13 SEER  
Watts ..................725  
Drive ..................M  
4. Calculate indoor blower BTUH heat effect.  
BTUH = Watts x 3.413 = 2474  
2. Select unit to meet cooling requirements.  
Since total cooling is within the range of 4 ton [14.07 kW] unit and  
requires 13 SEER efficiency level, enter cooling performance  
table, at 95°F [35°C] outdoor temperature, 63°F [17°C] wb enter-  
ing indoor air, and 1600 CFM [755 L/s]:  
5. Calculate net cooling capacities.  
Net total cooling = 46,700 – 2474 = 44,226 BTUH [12.96 kW]  
Net sensible cooling = 33,716 – 2474 = 31.242 BTUH [9.16 kW]  
Total capacity..........................46,700 BTUH [13.68 kW]  
Power input ............................3.3 kW  
And also, at 76°F [24°C] db indoor entering air, and using the for-  
mula at the bottom of the page:  
Sensible capacity....................33,710 BTUH [9.87 kW]  
WEIGHTS  
CENTER OF GRAVITY (C.G.)  
Accessory  
Shipping—lbs [kg] Operating—lbs [kg]  
Capacity Tons [kW]  
3-5 [10.6-17.6]  
A in. [mm]  
381/4 [972]  
B in. [mm]  
253/4 [654]  
Economizer  
142 [64]  
30 Est. [13]  
90 [41]  
130 [59]  
25 Est. [11]  
80 [36]  
Power Exhaust  
Horizontal Economizer  
Fresh Air Damper (Manual)  
Fresh Air Damper (Motorized)  
Roof Curb 8"  
11 [5]  
9
[4]  
13 [6]  
11 [5]  
80 [36]  
88 [40]  
104 [47]  
Capacity Tons [kW] Corner Weights by Percentage  
84 [38]  
A
B
C
D
Roof Curb 14"  
Roof Curb 24"  
92 [42]  
108 [49]  
3-5 [10.6-17.6]  
23% 27% 23% 27%  
[
] Designates Metric Conversions  
*Allow 57” for economizer on duct side.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES—RJNA- SERIES  
ACCESSORY EQUIPMENT  
Accessory  
Model No.  
Model Application  
Factory Installed  
3 to 5 Ton  
[10.6 to 17.6 kW]  
Accessory  
Description  
3 to 5 Ton  
3 to 5 Ton  
[10.6 to 17.6 kW]  
[10.6 to 17.6 kW]  
RXJJ-A06 (J, C, D)  
RXJJ-A10 (J, C, D)  
RXJJ-A11 (J, C, D)  
RXJJ-A12 (J, C, D)  
RXJJ-A15 (J, C, D)  
RXJJ-A20 (J, C, D)  
RXJJ-A21 (J, C, D)  
RXJJ-A24 (J, C, D)  
See Heater Kit  
Electric Table  
Electric Heater Kits  
RJNA-  
Roofcurb 14"  
Roofcurb 24"  
RJNA-  
RJNA-  
RXKG-BAD14  
RXKG-BAD24  
No  
No  
RXRX-BBCDB21  
RXRX-BBCDB22  
RXRX-BBCDB23  
Roofcurb Adapters  
RJNA-  
No  
RJNA-  
RJNA-  
RJNA-  
RJNA-  
RJNA-  
RJNA-  
RXRD-KECM3  
RXRX-AV02  
RXRX-AR02  
RXRX-BFF04C  
RXRF-FBA1  
RXRF-FBB1  
Economizer with Single Enthalpy ➀  
Dual Enthalpy Kit  
Yes  
No  
No  
No  
No  
No  
CO2 Sensor  
Power Exhaust  
Fresh Air Damper Manual  
Fresh Air Damper Motorized  
Rectangular to Round 18"  
Duct Adapters for Concentric Diffuser  
RJNA-  
RXMC-CB03  
No  
Concentric Diffuser 18" Step  
Concentric Diffuser 18" Flush  
Rectangular to Round 16" Side  
Louver Kit (3 Sides)  
RJNA-  
RJNA-  
RXRN-FA60  
RXRN-FA70  
RXMC-BB01  
RXRX-AAD01B  
RXMD-B01  
No  
No  
RJNA-  
No  
All RJNA Models  
RJNA-  
Yes  
Yes  
Yes  
Time Delay  
Low Ambient Control to 0°F [-18°C]  
RJNA-  
RXPZ-C01  
*Voltage  
NOTES: Economizer is designed for downflow  
J = 208-230 VAC-1PH-60HZ D = 460 VAC-3PH-60HZ  
C = 208-230 VAC-3PH-60HZ  
or horizontal applications.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES—RJNA- SERIES  
Roofcurb Adapters  
OLD CURB MODEL ROOFCURB ADAPTER  
NEW MODEL  
Old Models  
MEDIUM CABINET (3 TON [11 kW])  
RXPA-CA21 (1)  
RXRA-DB21 (2)  
(-)SNC, (-)SND, (-)SNE  
(-)RGE, (-)RGF, (-)RGG  
(-)PNC, (-)PND  
21 SERIES  
22 SERIES  
RXRX-BBCDB21  
RXRX-BBCDB22  
LARGE CABINET  
(3-3.5 TON [11-12 kW])  
(-)RGE, (-)RGF, (-)RGG,  
RXPA-CA22 (1)  
RXRA-DB22 (2)  
(-)RGH (3 TON [11 kW])  
RJNA  
EXTRA LARGE CABINET  
(3.5-5 TON [12-18 kW])  
(-)SNC, (-)SND, (-)SNE  
(-)RGE, (-)RGF,  
(-)RGG (4-5 TON [14-18 kW])  
(-)PNC, (-)PND, (-)RGH  
(3.5, 4 TON [12-14 kW])  
RXPA-CA23 (1)  
RXRA-DB23 (2)  
23 SERIES  
RXRX-BBCDB23  
(1) SLOPE TYPE (2) FULL PERIMETER TYPE  
Model Number Identifier:  
Field Installed Resistance  
Heater Kits  
R X J J — A 15 C  
Electric Heater Kits are designed for field  
installation using either single-point power  
wiring or dual circuit wiring. Low voltage  
plugs are provided to allow for quick  
connection to the unit. Removing a block-  
off panel on the unit allows the heater  
elements to be inserted into the supply air  
down stream from the indoor coil and  
supply air blower.  
Electrical Designation  
J = 208-230 V, 1 PH, 60 Hz  
C = 208-230 V, 3 PH, 60 Hz  
D = 460 V, 3 PH, 60 Hz  
Nominal Heater kW  
06 = 6 kW  
15 = 15 kW  
10 = 10 kW  
11 = 11 kW *  
12 = 12 kW  
20 = 20 kW  
21 = 21 kW *  
24 = 24 kW  
* Canadian Models Only  
[
] Designates Metric Conversions  
Design Series  
A = Initial Design  
Accessory Designation  
J = Electric Heater  
Accessory Classification  
J = Package Heat Pump  
X = Accessory  
R = Trade Name  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
TYPICAL INSTALLATION  
ROOFCURBS (Full Perimeter)  
Rheem’s new roofcurb design can be utilized on  
I
3 through 5 ton [10.6-17.6 kW] models.  
I
Two available heights (14" [356 mm] and  
24" [610 mm]) for ALL models.  
I
Quick assembly corners for simple and fast assembly.  
I
Opening provided in bottom pan to match the  
“Thru the Curb” electrical connection opening  
provided on the unit base pan.  
I
2" [51 mm] x 4" [102 mm] Nailer provided.  
I
Insulating panels provided.  
I
Sealing gasket (28" [711 mm]) provided  
with Roofcurb.  
I
Packaged for easy field assembly.  
Roofcurb Model  
RXKG-BAD14  
RXKG-BAD24  
Height of Curb  
14" [356 mm]  
24" [610 mm]  
[
] Designates Metric Conversions  
ROOFCURB FOR 3-5 TON  
[10.6-17.6 kW] MODELS  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
ECONOMIZERS  
RXRD-KECM3—3-5 Ton [10.6-17.6 kW] Models Single Enthalpy with Barometric Relief  
RXRX-AV02—Dual Enthalpy Kit  
3-5 Ton [10.6-17.6 kW] Models  
RXRX-AR02—3-5 Ton [10.6-17.6 kW] Models  
Optional CO2 Sensor  
I
Features Honeywell Controls  
I
Available factory installed or field accessory  
I
Gear Driven Direct Drive Actuator  
Fully Modulating (0-100%)  
Low Leakage Dampers  
Horizontal or Downflow Applications  
Slip-In Design for Easy Installations  
Plug-In Polarized 12-pin Electrical Connections  
Pre-configured—No Field Adjustments Necessary  
Standard Barometric Relief Damper Provided  
I
I
I
I
I
I
I
I
Single Enthalpy with Dual Enthalpy Upgrade Kit  
CO2 Input Sensor Available (Field Installed)  
Economizer slips in complete for Downflow or  
I
I
Horizontal Duct application  
Field Assembled Hood Ships with Economizer  
Optional Remote Minimum Position (Honeywell  
I
I
#S963B1128) is Available from ProStock  
Field Installed Power Exhaust Available  
I
3-5 TON [10.6-17.6 kW] MODELS  
[
] Designates Metric Conversions  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
INTEGRAL POWER EXHAUST FOR ECONOMIZER  
(FIELD INSTALLED ONLY)  
RXRX-BFF04C—3-5 Ton [10.6-17.6 kW] Models 208-230 V, 1 PH, 60 Hz  
I
For RXRD-KECM3 Economizer  
I
Downflow or horizontal applications  
I
Requires separate power supply with disconnect  
Adjustable switch on economizer, factory preset to  
I
energize power exhaust at 95% outside air position  
Polarized plug connects power exhaust relay  
I
to economizer  
Illustration  
ST-A0903-01  
POWER EXHAUST KIT FOR RXRD-ECCM(-), RXRD-EECM(-) ECONOMIZERS  
High Speed  
Model No.  
No. of Fans  
Volts  
Phase  
Watts (ea.)  
FLA (ea.)  
LRA (ea.)  
RPM  
CFM ➀  
RXRX-BFF04C  
1
208-230  
1
240  
2600  
1700  
1.06  
1.9  
CFM is at 0" w.c. external static pressure.  
FRESH AIR DAMPER  
3 to 5 Ton [10.6 to 17.6 kW] Models  
RXRF-FBA1 (Manual)  
RXRF-FBB1 (Motorized)  
I319.DGN  
FRESH AIR DAMPER  
[
] Designates Metric Conversions  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
DUCT ADAPTERS (3 TO 5 TON [10.6 TO 17.6 kW] MODELS)  
Rectangular to Round  
Transitions (Downflow)  
RXMC-CB03 – 18" [457 mm] Round  
Available in 18 inch round  
to fit all units. Drops  
into and secures to  
RXKG- Series Roofcurbs.  
For use with  
Concentric Diffusers.  
[
] Designates Metric Conversions  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
SIDE DISCHARGE CONCENTRIC DIFFUSER  
RXRN-FA60 (3 to 5 Ton [10.6 to 17.6 kW] Models)  
For Use With Duct Adapter (RXMC)  
DIMENSIONAL DATA  
Duct  
Size  
Model No.  
A
B
C
D
E
F
G
H
I
J
K
475/8"  
235/8"  
113/8"  
211/2"  
451/2"  
221/2"  
111/2"  
103/4"  
451/2"  
211/2"  
71/8"  
RXRN-FA60  
18RD  
[1210 mm] [600 mm] [289 mm] [546 mm] [1156 mm] [572 mm] [292 mm] [273 mm] [1156 mm] [546 mm] [181 mm]  
ENGINEERING DATA  
Static  
Pressure  
Throw  
Feet  
Neck  
Vel.  
Jet  
Vel.  
Noise  
Level  
Model No.  
CFM [L/s]  
1000 [472]  
1200 [566]  
1400 [661]  
1600 [755]  
1800 [850]  
2000 [944]  
2200 [1038]  
.14  
.17  
.20  
.24  
.30  
.36  
.40  
10-17  
11-18  
12-19  
12-20  
13-21  
14-23  
16-25  
351  
421  
491  
561  
632  
702  
772  
351  
421  
491  
561  
632  
702  
772  
20  
20  
20  
20  
20  
20  
20  
RXRN-FA60  
[
] Designates Metric Conversions  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
FLUSH MOUNT CONCENTRIC DIFFUSER  
RXRN-FA70 (3 to 5 Ton [10.6 to 17.6 kW] Models)  
For Use With Duct Adapter (RXMC)  
DIMENSIONAL DATA  
Duct  
Size  
Model No.  
A
B
C
D
E
F
G
H
475/8"  
[1210 mm]  
235/8"  
[600 mm]  
131/2"  
[343 mm]  
21"  
[533 mm]  
45"  
[1143 mm]  
221/2"  
[572 mm]  
111/4"  
[286 mm]  
101/2"  
[267 mm]  
RXRN-FA70  
18RD  
ENGINEERING DATA  
Static  
Throw  
Neck  
Jet  
Noise  
Level  
Model No.  
CFM [L/s]  
Pressure  
Feet  
Vel.  
391  
469  
547  
625  
703  
781  
859  
Vel.  
1000 [472]  
1200 [566]  
1400 [661]  
1600 [755]  
1800 [850]  
2000 [944]  
2200 [1038]  
.14  
.17  
.20  
.24  
.30  
.36  
.40  
15-20  
16-22  
17-24  
18-25  
20-28  
21-29  
22-30  
694  
833  
20  
25  
30  
30  
35  
40  
40  
972  
RXRN-FA70  
1111  
1250  
1389  
1528  
[
] Designates Metric Conversions  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MECHANICAL SPECIFICATIONS—RJNA- SERIES  
THERMOSTATS—PACKAGE HEAT PUMPS  
RECOMMENDED HEAT PUMP THERMOSTATS  
Units Without Economizer  
Cooling  
Stages  
Heating  
Stages  
Manufacturer  
Honeywell  
Model  
Sub-Base  
T7300A1005  
T8611R1166  
T874R  
Q7300C1006  
Included  
1
1
1
1
1
1
1
1
1
2
1
1
2
2
2
2
2
2
2
2
2
3
2
2
Q674F1360  
Included  
T841A1209  
T874G1881  
T8141A  
Q674F1360  
Included  
3AAT86B8A2  
3AAT83D9C1  
1F59-057  
1F92-71  
Included  
General Electric  
White-Rodgers  
Maple Chase  
Included  
Included  
Included  
962-0  
Included  
962-1  
Included  
Units With Economizer  
Included  
Honeywell  
T874W1031  
2
3
Coils  
Manual Fresh Air Damper  
SAMPLE  
The evaporator and condenser coils shall  
Damper shall consist of damper and rain-  
SPECIFICATIONS  
be fabricated of copper tubes with mechani- hood which is manually preset to admit up  
cally bonded aluminum plate fins. They  
shall be pressure tested prior to assembly  
into the unit, and electronically leak tested  
after assembly.  
to 35% of outside air for field installation.  
Unit shall be completely factory assembled  
and performance tested to provide the  
required cooling and heating functions suit-  
able for outdoor installations. Unit shall be  
UL/cUL listed and rated in accordance to  
ARI Standard 210.  
Motorized Fresh Air Damper  
Damper shall consist of motor, damper, and  
rainhood which can admit up to 35% of out-  
side air for field installation.  
Condenser Fan  
A single direct drive propeller fan shall dis-  
charge air vertically upward. The fan motor  
shall be permanently lubricated and have  
built-in overload protection.  
Electric Heat Kits  
Cabinet  
Electric heat kits shall be available in a wide  
range of capacity with branch circuit fusing  
allowing single point wiring. Kits shall be  
UL/cUL approved. Each kit shall be offered  
as a field or factory installed option.  
Unit casing, base pan and framework shall  
be manufactured of galvanized sheet metal  
primed and finished with powder paint  
capable of withstanding a 1000-hour salt  
spray test per ASTM B 117. Unit interior cab-  
inet surfaces shall be insulated with a mini-  
mum 1/2-inch thick foil faced insulation.  
Access panels shall be easily removable  
providing access to the blower, filter, heating  
compartment, and compressor/control box.  
Unit base rails shall be provided with fork  
insertion slots and rigging holes. Conden-  
sate drain pan shall be of sloped design to  
conform to ASHRAE 62. Unit shall be sup-  
plied ready for vertical airflow and be easily  
convertible to horizontal airflow at or before  
installation.  
Evaporator Blower  
A single, double inlet, centrifugal wheel  
shall rotate in permanently lubricated ball  
bearings. The wheel shall be made from  
steel with corrosion resistant finish and shall  
be statically and dynamically balanced.  
Pressure Controls  
High and low pressure controls shall be  
included for field or factory installation.  
Low Ambient Control  
Low ambient control shall be provided to  
cycle the condenser fan in response to  
condensing pressure and allow operation  
to 0 degrees F. The option shall be field or  
factory installed.  
ACCESSORIES  
ROOF CURB  
Curb shall be full perimeter type, complying  
with the standards of the National Roofing  
Contractors Association. Design shall pro-  
vide for drop-in of supply and return ducts  
prior to setting unit, and include an insulat-  
ing panel for the rest of the curb area.  
Time Delay Control  
Time delay control shall be provided to  
prevent the compressor from restarting 5  
minutes after shutdown. The control shall  
be field or factory installed.  
Compressor(s)  
Unit shall be provided with fully hermetic  
scroll compressor(s) with internally protected  
safety controls.  
Economizer  
Louver Panel Kits  
Economizer shall be completely assembled  
for field installation. Unit shall include all  
controls and dampers including the baro-  
metric relief damper.  
Field or factory installed louver kits shall  
be provided for condenser coil protection  
against hail or flying debris.  
[
] Designates Metric Conversions  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING SCHEMATICS—RJNA- SERIES  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING SCHEMATICS—RJNA- SERIES  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING SCHEMATICS—RJNA- SERIES  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING SCHEMATICS—RJNA- SERIES  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING SCHEMATICS—RJNA- SERIES  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING SCHEMATICS—RJNA- SERIES  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING SCHEMATICS—RJNA- SERIES  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM  
YOUR RETAILER.  
GENERAL TERMS OF LIMITED WARRANTY  
Rheem will furnish a replacement for any part of this product  
which fails in normal use and service within the applicable  
periods stated, in accordance with the terms of the limited  
warranty.  
Compressor...................................................Five (5) Years  
Electric Heating Elements ...............................Five (5) Years  
Any Other Part  
1-Phase Models .............................................Five (5) Years  
3-Phase Models...............................................One (1) Year  
For Complete Details of the Limited Warranty, Including Applicable Terms  
and Conditions, See Your Local Installer or Contact the Manufacturer  
for a Copy.  
RHEEM  
AIR CONDITIONING  
DIVISION  
Before proceeding with installation, refer  
to installation instructions packaged  
with each model, as well as complying  
with all Federal, State, Provincial, and  
Local codes, regulations, and practices.  
5600 Old Greenwood Road, Fort Smith, Arkansas 72908  
“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.”  
PRINTED IN U.S.A.  
8-05 DC  
FORM NO. P11-763 REV. 1  
Supersedes Form No. P11-763  
Download from Www.Somanuals.com. All Manuals Search And Download.  

QSC Audio DJ Equipment 10 SERIES User Guide
QSC Audio Stereo Amplifier IT 42 User Guide
Radio Shack Portable Radio FRS 105 User Guide
Radio Shack Telephone ET 1754 User Guide
Raritan Computer Switch UST IP User Guide
RCA Portable CD Player RP2730 User Guide
Rotel Stereo Receiver RX 975 User Guide
Samsung Microwave Oven CM929B User Guide
Samsung Microwave Oven SMH7178STE User Guide
Sanyo Air Conditioner 101 User Guide