Rheem Air Conditioner RSNA B Series User Guide

PACKAGE AIR CONDITIONERS  
FORM NO. S11-933 REV. 2  
Supersedes Form No. S11-933 Rev. 1  
RSNA-B SUPER HIGH EFFICIENCY 13-SEER SERIES  
NOMINAL SIZES 2-5 TONS [7.0-17.6 kW]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT FEATURES & BENEFITS—RSNA-B  
These quality features are included in the Rheem  
Package Air Conditioner  
5
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT FEATURES & BENEFITS—RSNA-B SERIES  
[
] Designates Metric Conversions  
Features Below Correspond to Photos on Page 3  
1. All models feature Copeland® Scroll® compressors for maxi-  
mum efficiency and quiet operation.  
8. Refrigerant connections are conveniently located for easy  
service diagnostics.  
2. Louvered condenser compartment for protecting the coil  
against yard hazards and/or weather extremes.  
9. Condenser and evaporator coils feature enhanced fins  
for better heat transfer and rifled copper tubing for  
greater efficiency.  
3. One-piece top with a drip lip to help keep water off of the unit  
sides.  
10. Supplemental electric heat strips up to 15 kW are available  
(field or factory installed) for periods of extreme cold temper-  
atures. Single point wiring makes installation even easier.  
4. Supply and return air openings feature a one-inch tall flange  
to prevent water migration into the ductwork.  
11. All units feature an internal trap on the condensate line elimi-  
nating the need for installing an on-site external trap.  
5. Access panels have “weep holes” and channels to further  
help manage water run-off.  
12. Easily accessible control box.  
6. Side and down discharge options available on all models.  
7. Easily accessible blower section complete with slide-out  
blower.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL IDENTIFICATION—RSNA-B SERIES  
R S N A — B 036 J K 010 X X  
Factory Installed Options  
(See Next Page)  
Heating Capacity (Factory Installed)  
000 = No Resistance Heat  
005 = 05 KW Resistance Heat (018-030)  
010 = 10 KW Resistance Heat (024-048)  
015 = 15 KW Resistance Heat (036-048)  
Drive Package  
K = Direct Drive  
Electrical Designation  
J = 208-230V—1PH—60 Hz  
C= 208-230V—3PH—60 Hz  
Cooling Capacity (BTUH) [kW]  
024 = 24,000 [7.03]  
030 = 30,000 [8.79]  
036 = 36,000 [10.55]  
042 = 42,000 [12.31]  
048 = 48,000 [14.07]  
060 = 60,000 [17.59]  
Future Technical Variations  
Design Series  
B = 2nd Design  
Efficiency Designation  
N = 13 SEER Super High Efficiency  
Product Classification  
S = Package Air Conditioner  
Tradebrand  
R = Rheem  
[
] Designates Metric Conversions  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONS—RSNA-B SERIES  
Instructions for Factory Installed Option(s) Selection  
Note: Two characters following the model number will be utilized to designate a factory-installed option or com-  
bination of options. If no factory option(s) is required, nothing follows the model number.  
Step 1. After a basic rooftop model is selected, choose a two-character option code from the FACTORY  
INSTALLED OPTION SELECTION TABLE.  
FACTORY INSTALLED OPTION CODES  
Option  
Side Flow  
Code  
AA  
AK  
No Option  
x
Example: RSNA-B036JK000XX (where XX is factory installed option)  
Example: No Options  
RSNA-B036JK000  
Example: Options with Sideflow  
RSNA-B036JK000AK  
Note: Factory installed economizer is not available on these models.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL DATA—RSNA-B SERIES  
NOMINAL SIZES 2-5TONS [7.0-17.6 kW]  
Model RSNA-B Series  
Cooling Performance1  
Gross Cooling Capacity Btu [kW]  
EER/SEER2  
B024JK  
B030JK  
B036CK  
B036JK  
CONTINUED  
37,400 [10.96]  
11.7/13  
24,800 [7.27]  
11.8/13  
31,200 [9.14]  
11.1/13  
37,400 [10.96]  
11.7/13  
Nominal CFM/ARI Rated CFM [L/s]  
ARI Net Cooling Capacity Btu [kW]  
Net Sensible Capacity Btu [kW]  
Net Latent Capacity Btu [kW]  
Net System Power kW  
Compressor  
800/800 [378/378]  
24,000 [7.03]  
17,171 [5.03]  
6,829 [2]  
1000/1000 [472/472]  
30,000 [8.79]  
20,984 [6.15]  
9,016 [2.64]  
2.7  
1200/1200 [566/566]  
36,000 [10.55]  
25,736 [7.54]  
10,264 [3.01]  
3.07  
1200/1200 [566/566]  
36,000 [10.55]  
25,736 [7.54]  
10,264 [3.01]  
3.07  
2.04  
No./Type  
1/Copeland Scroll  
76  
1/Copeland Scroll  
76  
1/Copeland Scroll  
76  
1/Copeland Scroll  
76  
Outdoor Sound Rating (dB)3  
Outdoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm] OD  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Indoor Coil—Fin Type  
Tube Type  
0.375 [9.5]  
10.56 [0.98]  
1 / 18 [7]  
Louvered  
Rifled  
0.375 [9.5]  
10.56 [0.98]  
1 / 18 [7]  
Louvered  
Rifled  
0.375 [9.5]  
14.8 [1.37]  
1 / 22 [9]  
Louvered  
Rifled  
0.375 [9.5]  
14.8 [1.37]  
1 / 22 [9]  
Louvered  
Rifled  
Tube Size in. [mm]  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Refrigerant Control  
Drain Connection No./Size in. [mm]  
Outdoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
CFM [L/s]  
0.375 [9.5]  
5.54 [0.51]  
2 / 15 [6]  
TX Valves  
1/0.75 [19.05]  
Propeller  
1/22 [558.8]  
Direct/1  
0.375 [9.5]  
5.54 [0.51]  
2 / 15 [6]  
TX Valves  
1/0.75 [19.05]  
Propeller  
1/22 [558.8]  
Direct/1  
0.375 [9.5]  
5.54 [0.51]  
2 / 15 [6]  
TX Valves  
1/0.75 [19.05]  
Propeller  
1/22 [558.8]  
Direct/1  
0.375 [9.5]  
5.54 [0.51]  
2 / 15 [6]  
TX Valves  
1/0.75 [19.05]  
Propeller  
1/22 [558.8]  
Direct/1  
2500 [1180]  
1 at 1/5 HP  
1075  
2500 [1180]  
1 at 1/5 HP  
1075  
2700 [1274]  
1 at 1/5 HP  
1075  
2700 [1274]  
1 at 1/5 HP  
1075  
No. Motors/HP  
Motor RPM  
Indoor Fan—Type  
FC Centrifugal  
1/9x7 [228.6x177.8]  
Direct/2  
FC Centrifugal  
1/10x9 [254x228.6]  
Direct/3  
FC Centrifugal  
1/10x9 [254x228.6]  
Direct/3  
FC Centrifugal  
1/10x9 [254x228.6]  
Direct/3  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
No. Motors  
1
1
1
1
Motor HP  
1/4  
1/2  
1/2  
1/2  
Motor RPM  
1075  
1075  
1075  
1075  
Motor Frame Size  
48  
48  
48  
48  
Filter—Type  
Field Supplied  
No  
Field Supplied  
No  
Field Supplied  
No  
Field Supplied  
No  
Furnished  
(No.) Size Recommended in. [mm]  
Refrigerant Charge Oz. [g]  
Weights  
(1)1x20x20 [25x508x508] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]  
69.6 [1973]  
72 [2041]  
83.2 [2359]  
83.2 [2359]  
Net Weight lbs. [kg]  
Ship Weight lbs. [kg]  
See Page 10 for Notes.  
370 [168]  
379 [172]  
379 [178]  
388 [176]  
392 [178]  
401 [182]  
[
392 [178]  
401 [182]  
] Designates Metric Conversions  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL DATA—RSNA-B SERIES  
NOMINAL SIZES 2-5TONS [7.0-17.6 kW]  
Model RSNA-B Series  
Cooling Performance1  
Gross Cooling Capacity Btu [kW]  
EER/SEER2  
B042CK  
B042JK  
B048CK  
B048JK  
CONTINUED  
42,500 [12.45]  
11.5/13  
42,500 [12.45]  
11.5/13  
50,500 [14.8]  
11.6/13  
50,500 [14.8]  
11.6/13  
Nominal CFM/ARI Rated CFM [L/s]  
ARI Net Cooling Capacity Btu [kW]  
Net Sensible Capacity Btu [kW]  
Net Latent Capacity Btu [kW]  
Net System Power kW  
Compressor  
1400/1350 [661/637]  
41,000 [12.01]  
28,511 [8.35]  
12,489 [3.66]  
3.57  
1400/1350 [661/637]  
41,000 [12.01]  
28,511 [8.35]  
12,489 [3.66]  
3.57  
1600/1600 [755/755]  
48,500 [14.21]  
34,516 [10.11]  
13,984 [4.1]  
4.18  
1600/1600 [755/755]  
48,500 [14.21]  
34,516 [10.11]  
13,984 [4.1]  
4.18  
No./Type  
1/Copeland Scroll  
76  
1/Copeland Scroll  
76  
1/Copeland Scroll  
78  
1/Copeland Scroll  
78  
Outdoor Sound Rating (dB)3  
Outdoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm] OD  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Indoor Coil—Fin Type  
Tube Type  
0.375 [9.5]  
16.65 [1.55]  
1 / 22 [9]  
Louvered  
Rifled  
0.375 [9.5]  
16.65 [1.55]  
1 / 22 [9]  
Louvered  
Rifled  
0.375 [9.5]  
16.23 [1.51]  
2 / 22 [9]  
Louvered  
Rifled  
0.375 [9.5]  
16.23 [1.51]  
2 / 22 [9]  
Louvered  
Rifled  
Tube Size in. [mm]  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Refrigerant Control  
Drain Connection No./Size in. [mm]  
Outdoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
CFM [L/s]  
0.375 [9.5]  
7.39 [0.69]  
2 / 15 [6]  
TX Valves  
1/0.75 [19.05]  
Propeller  
1/22 [558.8]  
Direct/1  
0.375 [9.5]  
7.39 [0.69]  
2 / 15 [6]  
TX Valves  
1/0.75 [19.05]  
Propeller  
1/22 [558.8]  
Direct/1  
0.375 [9.5]  
7.39 [0.69]  
2 / 15 [6]  
TX Valves  
1/0.75 [19.05]  
Propeller  
1/22 [558.8]  
Direct/1  
0.375 [9.5]  
7.39 [0.69]  
2 / 15 [6]  
TX Valves  
1/0.75 [19.05]  
Propeller  
1/22 [558.8]  
Direct/1  
3500 [1652]  
1 at 1/3 HP  
1075  
3500 [1652]  
1 at 1/3 HP  
1075  
3300 [1557]  
1 at 1/3 HP  
1075  
3300 [1557]  
1 at 1/3 HP  
1075  
No. Motors/HP  
Motor RPM  
Indoor Fan—Type  
FC Centrifugal  
1/10x9 [254x228.6]  
Direct/3  
FC Centrifugal  
1/10x9 [254x228.6]  
Direct/3  
FC Centrifugal  
1/10x9 [254x228.6]  
Direct/3  
FC Centrifugal  
1/10x9 [254x228.6]  
Direct/3  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
No. Motors  
1
1
1
1
Motor HP  
1/2  
1/2  
3/4  
3/4  
Motor RPM  
1075  
1075  
1075  
1075  
Motor Frame Size  
48  
48  
48  
48  
Filter—Type  
Field Supplied  
No  
Field Supplied  
No  
Field Supplied  
No  
Field Supplied  
No  
Furnished  
(No.) Size Recommended in. [mm]  
Refrigerant Charge Oz. [g]  
Weights  
(1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]  
104 [2948]  
104 [2948]  
153.6 [4355]  
153.6 [4355]  
Net Weight lbs. [kg]  
Ship Weight lbs. [kg]  
See Page 10 for Notes.  
447 [203]  
456 [207]  
447 [203]  
456 [207]  
499 [226]  
508 [230]  
[
499 [226]  
508 [230]  
] Designates Metric Conversions  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL DATA—RSNA-B SERIES  
NOMINAL SIZES 2-5TONS [7.0-17.6 kW]  
Model RSNA-B Series  
Cooling Performance1  
Gross Cooling Capacity Btu [kW]  
EER/SEER2  
B060CK  
B060JK  
60,000 [17.58]  
11.1/13  
60,000 [17.58]  
11.1/13  
Nominal CFM/ARI Rated CFM [L/s]  
ARI Net Cooling Capacity Btu [kW]  
Net Sensible Capacity Btu [kW]  
Net Latent Capacity Btu [kW]  
Net System Power kW  
Compressor  
2000/1850 [897/873]  
58,000 [16.99]  
40,561 [11.88]  
17,439 [5.11]  
5.2  
2000/1850 [897/873]  
58,000 [16.99]  
40,561 [11.88]  
17,439 [5.11]  
5.2  
No./Type  
1/Copeland Scroll  
78  
1/Copeland Scroll  
78  
Outdoor Sound Rating (dB)3  
Outdoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm] OD  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Indoor Coil—Fin Type  
Tube Type  
0.375 [9.5]  
16.23 [1.51]  
2 / 22 [9]  
Louvered  
Rifled  
0.375 [9.5]  
16.23 [1.51]  
2 / 22 [9]  
Louvered  
Rifled  
Tube Size in. [mm]  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Refrigerant Control  
Drain Connection No./Size in. [mm]  
Outdoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
CFM [L/s]  
0.375 [9.5]  
7.39 [0.69]  
2 / 15 [6]  
TX Valves  
1/0.75 [19.05]  
Propeller  
1/22 [558.8]  
Direct/1  
0.375 [9.5]  
7.39 [0.69]  
2 / 15 [6]  
TX Valves  
1/0.75 [19.05]  
Propeller  
1/22 [558.8]  
Direct/1  
3300 [1557]  
1 at 1/3 HP  
1075  
3300 [1557]  
1 at 1/3 HP  
1075  
No. Motors/HP  
Motor RPM  
Indoor Fan—Type  
FC Centrifugal  
1/10x9 [254x228.6]  
Direct/2  
FC Centrifugal  
1/10x9 [254x228.6]  
Direct/2  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
No. Motors  
1
1
Motor HP  
1
1
Motor RPM  
1075  
1075  
Motor Frame Size  
48  
48  
Filter—Type  
Field Supplied  
No  
Field Supplied  
No  
Furnished  
(No.) Size Recommended in. [mm]  
Refrigerant Charge Oz. [g]  
Weights  
(1)1x24x30 [25x610x762] (1)1x24x30 [25x610x762]  
145.6 [4128]  
145.6 [4128]  
Net Weight lbs. [kg]  
Ship Weight lbs. [kg]  
See Page 10 for Notes.  
521 [236]  
530 [240]  
521 [236]  
530 [240]  
[
] Designates Metric Conversions  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL DATA—RSNA-B SERIES  
NOTES:  
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does  
not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable  
for operation to Ϯ20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment  
certification program, which is based on ARI Standard 210/240 or 360.  
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.  
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.  
[
] Designates Metric Conversions  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEMS PERFORMANCE—RSNA-B SERIES  
GROSS SYSTEMS PERFORMANCE DATA—RSNA-B024  
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀  
wbE  
CFM [L/s]  
DR ➀  
71°F [21.7°C]  
800 [378]  
.20  
67°F [19.4°C]  
800 [378]  
.20  
63°F [17.2°C]  
800 [378]  
.20  
880 [415]  
.21  
680 [321]  
.18  
880 [415]  
.21  
680 [321]  
.18  
880 [415]  
.21  
680 [321]  
.18  
Total BTUH [kW] 28.9 [8.47]  
28.4 [8.32]  
15.4 [4.51]  
1.3  
27.6 [8.09]  
14.4 [4.22]  
1.3  
27.3 [8.00]  
19.5 [5.71]  
1.3  
26.8 [7.85]  
18.6 [5.45]  
1.3  
26.1 [7.65]  
17.3 [5.07]  
1.3  
25.0 [7.33]  
22.0 [6.45]  
1.3  
24.6 [7.21]  
21.1 [6.18]  
1.3  
23.9 [7.00]  
19.6 [5.74]  
1.3  
75  
[23.9]  
Sens BTUH [kW] 16.2 [4.75]  
Power  
1.4  
O
U
T
D
O
O
R
Total BTUH [kW] 28.9 [8.47]  
28.4 [8.32]  
15.4 [4.51]  
1.5  
27.6 [8.09]  
14.3 [4.19]  
1.4  
27.2 [7.97]  
19.5 [5.71]  
1.5  
26.8 [7.85]  
18.6 [5.45]  
1.4  
26.0 [7.62]  
17.3 [5.07]  
1.4  
25.0 [7.33]  
22.0 [6.45]  
1.4  
24.5 [7.18]  
21.0 [6.15]  
1.4  
23.9 [7.00]  
19.6 [5.74]  
1.4  
80  
Sens BTUH [kW] 16.1 [4.72]  
[26.7]  
Power  
1.5  
Total BTUH [kW] 28.5 [8.35]  
28.0 [8.21]  
15.3 [4.48]  
1.6  
27.2 [7.97]  
14.2 [4.16]  
1.5  
26.9 [7.88]  
19.3 [5.66]  
1.6  
26.4 [7.74]  
18.5 [5.42]  
1.6  
25.7 [7.53]  
17.2 [5.04]  
1.5  
24.6 [7.21]  
21.9 [6.42]  
1.5  
24.1 [7.06]  
20.9 [6.13]  
1.5  
23.5 [6.89]  
19.5 [5.71]  
1.5  
85  
[29.4]  
Sens BTUH [kW] 16.0 [4.69]  
Power  
1.6  
D
R
Y
Total BTUH [kW] 27.8 [8.15]  
27.3 [8.00]  
15.1 [4.43]  
1.7  
26.6 [7.80]  
14.0 [4.10]  
1.7  
26.2 [7.68]  
19.1 [5.60]  
1.7  
25.7 [7.53]  
18.3 [5.36]  
1.7  
25.0 [7.33]  
17.0 [4.98]  
1.7  
23.9 [7.00]  
21.7 [6.36]  
1.6  
23.5 [6.89]  
20.7 [6.07]  
1.6  
22.8 [6.68]  
19.3 [5.66]  
1.6  
90  
[32.2]  
Sens BTUH [kW] 15.8 [4.63]  
B
U
L
Power  
1.7  
Total BTUH [kW] 27.0 [7.91]  
26.5 [7.77]  
14.8 [4.34]  
1.8  
25.8 [7.56]  
13.8 [4.04]  
1.8  
25.3 [7.41]  
18.9 [5.54]  
1.8  
24.8 [7.27]  
18.0 [5.28]  
1.8  
24.2 [7.09]  
16.8 [4.92]  
1.8  
23.0 [6.74]  
21.4 [6.27]  
1.8  
22.6 [6.62]  
20.5 [6.01]  
1.7  
22.0 [6.45]  
19.0 [5.57]  
1.7  
95  
[35]  
B
Sens BTUH [kW] 15.5 [4.54]  
Power  
1.8  
T
E
M
P
E
R
A
T
Total BTUH [kW] 26.0 [7.62]  
25.5 [7.47]  
14.5 [4.25]  
1.9  
24.8 [7.27]  
13.5 [3.96]  
1.9  
24.3 [7.12]  
18.5 [5.42]  
1.9  
23.9 [7.00]  
17.7 [5.19]  
1.9  
23.2 [6.80]  
16.4 [4.81]  
1.9  
22.1 [6.48]  
21.1 [6.18]  
1.9  
21.7 [6.36]  
20.1 [5.89]  
1.9  
21.1 [6.18]  
18.7 [5.48]  
1.8  
100  
[37.8]  
Sens BTUH [kW] 15.2 [4.45]  
Power  
1.9  
Total BTUH [kW] 25.0 [7.33]  
24.5 [7.18]  
14.1 [4.13]  
2.0  
23.9 [7.00]  
13.1 [3.84]  
2.0  
23.3 [6.83]  
18.1 [5.30]  
2.0  
22.9 [6.71]  
17.3 [5.07]  
2.0  
22.3 [6.54]  
16.1 [4.72]  
2.0  
21.1 [6.18]  
20.6 [6.04]  
2.0  
20.7 [6.07]  
19.7 [5.77]  
2.0  
20.1 [5.89]  
18.3 [5.36]  
1.9  
105  
[40.6]  
Sens BTUH [kW] 14.7 [4.31]  
Power  
2.0  
U
R
E
Total BTUH [kW] 24.1 [7.06]  
23.7 [6.95]  
13.6 [3.99]  
2.1  
23.0 [6.74]  
12.7 [3.72]  
2.1  
22.4 [6.56]  
17.6 [5.16]  
2.1  
22.0 [6.45]  
16.8 [4.92]  
2.1  
21.4 [6.27]  
15.6 [4.57]  
2.1  
20.2 [5.92]  
20.1 [5.89]  
2.1  
19.8 [5.80]  
19.2 [5.63]  
2.1  
19.3 [5.66]  
17.9 [5.25]  
2.1  
110  
[43.3]  
Sens BTUH [kW] 14.3 [4.19]  
°F  
[°C]  
Power  
2.1  
Total BTUH [kW] 23.3 [6.83]  
22.9 [6.71]  
13.1 [3.84]  
2.2  
22.3 [6.54]  
12.2 [3.58]  
2.2  
21.7 [6.36]  
17.0 [4.98]  
2.3  
21.3 [6.24]  
16.3 [4.78]  
2.2  
20.7 [6.07]  
15.1 [4.43]  
2.2  
19.4 [5.69]  
19.4 [5.69]  
2.2  
19.1 [5.60]  
18.7 [5.48]  
2.2  
18.5 [5.42]  
17.4 [5.10]  
2.2  
115  
[46.1]  
Sens BTUH [kW] 13.7 [4.02]  
Power  
2.3  
GROSS SYSTEMS PERFORMANCE DATA—RSNA-B030  
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀  
wbE  
CFM [L/s]  
DR ➀  
71°F [21.7°C]  
1000 [472]  
.23  
67°F [19.4°C]  
1000 [472]  
.23  
63°F [17.2°C]  
1000 [472]  
.23  
1100 [519]  
.24  
850 [401]  
.21  
1100 [519]  
.24  
850 [401]  
.21  
1100 [519]  
.24  
850 [401]  
.21  
Total BTUH [kW] 37.6 [11.02] 36.9 [10.81] 35.9 [10.52] 35.0 [10.26] 34.4 [10.08] 33.4 [9.79]  
33.6 [9.85]  
27.2 [7.97]  
1.9  
33.0 [9.67]  
26.0 [7.62]  
1.9  
32.1 [9.41]  
24.2 [7.09]  
1.9  
75  
[23.9]  
Sens BTUH [kW] 21.3 [6.24] 20.3 [5.95] 18.9 [5.54] 25.2 [7.39] 24.1 [7.06] 22.4 [6.56]  
Power  
1.9  
1.9  
1.9  
1.9  
1.9  
1.9  
O
U
T
D
O
O
R
Total BTUH [kW] 37.1 [10.87] 36.4 [10.67] 35.4 [10.37] 34.5 [10.11] 33.9 [9.94] 32.9 [9.64]  
33.1 [9.70]  
26.7 [7.83]  
2.0  
32.5 [9.52]  
25.5 [7.47]  
2.0  
31.6 [9.26]  
23.8 [6.98]  
2.0  
80  
Sens BTUH [kW] 20.8 [6.10] 19.9 [5.83] 18.5 [5.42] 24.7 [7.24] 23.6 [6.92] 22.0 [6.45]  
[26.7]  
Power  
2.1  
2.0  
2.0  
2.0  
2.0  
2.0  
Total BTUH [kW] 36.3 [10.64] 35.6 [10.43] 34.7 [10.17] 33.7 [9.88] 33.1 [9.70] 32.2 [9.44]  
32.3 [9.47]  
26.2 [7.68]  
2.1  
31.7 [9.29]  
25.1 [7.36]  
2.1  
30.9 [9.06]  
23.3 [6.83]  
2.1  
85  
[29.4]  
Sens BTUH [kW] 20.3 [5.95] 19.4 [5.69] 18.0 [5.28] 24.2 [7.09] 23.1 [6.77] 21.5 [6.30]  
Power  
2.2  
2.2  
2.1  
2.2  
2.1  
2.1  
D
R
Y
Total BTUH [kW] 35.3 [10.35] 34.7 [10.17] 33.8 [9.91] 32.8 [9.61] 32.2 [9.44] 31.3 [9.17]  
31.4 [9.20]  
25.7 [7.53]  
2.3  
30.8 [9.03]  
24.6 [7.21]  
2.2  
30.0 [8.79]  
22.9 [6.71]  
2.2  
90  
[32.2]  
Sens BTUH [kW] 19.8 [5.80] 18.9 [5.54] 17.6 [5.16] 23.7 [6.95] 22.6 [6.62] 21.1 [6.18]  
B
U
L
Power  
2.3  
2.3  
2.2  
2.3  
2.2  
2.2  
Total BTUH [kW] 34.3 [10.05] 33.7 [9.88] 32.8 [9.61] 31.7 [9.29] 31.2 [9.14] 30.3 [8.88]  
30.3 [8.88]  
25.2 [7.39]  
2.4  
29.8 [8.73]  
24.1 [7.06]  
2.4  
29.0 [8.50]  
22.4 [6.56]  
2.3  
95  
[35]  
B
Sens BTUH [kW] 19.3 [5.66] 18.4 [5.39] 17.1 [5.01] 23.2 [6.80] 22.1 [6.48] 20.6 [6.04]  
Power  
2.4  
2.4  
2.4  
2.4  
2.4  
2.3  
T
E
M
P
E
R
A
T
Total BTUH [kW] 33.2 [9.73] 32.6 [9.55] 31.7 [9.29] 30.6 [8.97] 30.1 [8.82] 29.3 [8.59]  
29.2 [8.56]  
24.7 [7.24]  
2.5  
28.7 [8.41]  
23.6 [6.92]  
2.5  
27.9 [8.18]  
21.9 [6.42]  
2.4  
100  
[37.8]  
Sens BTUH [kW] 18.7 [5.48] 17.9 [5.25] 16.6 [4.86] 22.7 [6.65] 21.6 [6.33] 20.1 [5.89]  
Power  
2.5  
2.5  
2.5  
2.5  
2.5  
2.4  
Total BTUH [kW] 32.1 [9.41] 31.6 [9.26] 30.7 [9.00] 29.6 [8.67] 29.0 [8.50] 28.3 [8.29]  
28.2 [8.26]  
24.2 [7.09]  
2.6  
27.7 [8.12]  
23.1 [6.77]  
2.6  
26.9 [7.88]  
21.5 [6.30]  
2.5  
105  
[40.6]  
Sens BTUH [kW] 18.2 [5.33] 17.4 [5.10] 16.2 [4.75] 22.1 [6.48] 21.2 [6.21] 19.7 [5.77]  
Power  
2.6  
2.6  
2.6  
2.6  
2.6  
2.6  
U
R
E
Total BTUH [kW] 31.2 [9.14] 30.6 [8.97] 29.8 [8.73] 28.6 [8.38] 28.1 [8.24] 27.3 [8.00]  
27.2 [7.97]  
23.7 [6.95]  
2.7  
26.7 [7.83]  
22.6 [6.62]  
2.7  
26.0 [7.62]  
21.0 [6.15]  
2.7  
110  
[43.3]  
Sens BTUH [kW] 17.7 [5.19] 16.9 [4.95] 15.7 [4.60] 21.6 [6.33] 20.7 [6.07] 19.2 [5.63]  
°F  
[°C]  
Power  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
Total BTUH [kW] 30.4 [8.91] 29.8 [8.73] 29.0 [8.50] 27.8 [8.15] 27.3 [8.00] 26.6 [7.80]  
26.4 [7.74]  
23.2 [6.80]  
2.8  
25.9 [7.59]  
22.1 [6.48]  
2.8  
25.2 [7.39]  
20.6 [6.04]  
2.8  
115  
[46.1]  
Sens BTUH [kW] 17.2 [5.04] 16.5 [4.84] 15.3 [4.48] 21.1 [6.18] 20.2 [5.92] 18.8 [5.51]  
Power  
2.9  
2.8  
2.8  
2.8  
2.8  
2.8  
DR —Depression ratio  
dbE —Entering air dry bulb  
wbE—Entering air wet bulb  
Total —Total capacity x 1000 BTUH  
Sens —Sensible capacity x 1000 BTUH  
Power—KW input  
NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible  
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].  
[
] Designates Metric Conversions  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEMS PERFORMANCE—RSNA-B SERIES  
GROSS SYSTEMS PERFORMANCE DATA—RSNA-B036  
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀  
wbE  
CFM [L/s]  
DR ➀  
71°F [21.7°C]  
1200 [566]  
.20  
67°F [19.4°C]  
1200 [566]  
.20  
63°F [17.2°C]  
1200 [566]  
.20  
1320 [623]  
.21  
1020 [481]  
.17  
1320 [623]  
.21  
1020 [481]  
.17  
1320 [623]  
.21  
1020 [481]  
.17  
Total BTUH [kW] 44.4 [13.01] 43.6 [12.78] 42.4 [12.43] 41.3 [12.10] 40.6 [11.90] 39.5 [11.58] 39.6 [11.61] 38.9 [11.40] 37.8 [11.08]  
75  
[23.9]  
Sens BTUH [kW] 25.5 [7.47] 24.4 [7.15] 22.7 [6.65] 30.4 [8.91] 29.1 [8.53] 27.0 [7.91] 31.4 [9.20] 30.0 [8.79] 27.9 [8.18]  
Power  
2.2  
2.1  
2.1  
2.1  
2.1  
2.1  
2.1  
2.1  
2.1  
O
U
T
D
O
O
R
Total BTUH [kW] 43.6 [12.78] 42.8 [12.54] 41.7 [12.22] 40.5 [11.87] 39.8 [11.66] 38.7 [11.34] 38.7 [11.34] 38.0 [11.14] 37.0 [10.84]  
80  
Sens BTUH [kW] 25.0 [7.33] 23.9 [7.00] 22.2 [6.51] 29.9 [8.76] 28.6 [8.38] 26.6 [7.80] 30.8 [9.03] 29.5 [8.65] 27.4 [8.03]  
[26.7]  
Power  
2.3  
2.3  
2.2  
2.3  
2.3  
2.2  
2.3  
2.3  
2.2  
Total BTUH [kW] 42.8 [12.54] 42.1 [12.34] 40.9 [11.99] 39.7 [11.63] 39.0 [11.43] 38.0 [11.14] 38.0 [11.14] 37.3 [10.93] 36.3 [10.64]  
85  
[29.4]  
Sens BTUH [kW] 24.5 [7.18] 23.4 [6.86] 21.8 [6.39] 29.4 [8.62] 28.1 [8.24] 26.1 [7.65] 30.3 [8.88] 29.0 [8.50] 27.0 [7.91]  
Power  
2.4  
2.4  
2.4  
2.4  
2.4  
2.4  
2.4  
2.4  
2.4  
D
R
Y
Total BTUH [kW] 42.0 [12.31] 41.3 [12.10] 40.2 [11.78] 38.9 [11.40] 38.3 [11.22] 37.2 [10.90] 37.2 [10.90] 36.5 [10.70] 35.5 [10.40]  
90  
[32.2]  
Sens BTUH [kW] 24.0 [7.03] 22.9 [6.71] 21.3 [6.24] 28.9 [8.47] 27.6 [8.09] 25.7 [7.53] 29.9 [8.76] 28.5 [8.35] 26.5 [7.77]  
B
U
L
Power  
2.6  
2.5  
2.5  
2.6  
2.5  
2.5  
2.5  
2.5  
2.5  
Total BTUH [kW] 41.1 [12.05] 40.4 [11.84] 39.3 [11.52] 38.0 [11.14] 37.4 [10.96] 36.3 [10.64] 36.3 [10.64] 35.6 [10.43] 34.7 [10.17]  
95  
[35]  
B
Sens BTUH [kW] 23.5 [6.89] 22.4 [6.56] 20.9 [6.13] 28.4 [8.32] 27.1 [7.94] 25.2 [7.39] 29.3 [8.59] 28.0 [8.21] 26.0 [7.62]  
Power  
2.7  
2.7  
2.6  
2.7  
2.7  
2.6  
2.7  
2.7  
2.6  
T
E
M
P
E
R
A
T
Total BTUH [kW] 40.0 [11.72] 39.3 [11.52] 38.2 [11.20] 36.9 [10.81] 36.3 [10.64] 35.3 [10.35] 35.2 [10.32] 34.5 [10.11] 33.6 [9.85]  
100  
[37.8]  
Sens BTUH [kW] 22.8 [6.68] 21.8 [6.39] 20.3 [5.95] 27.7 [8.12] 26.5 [7.77] 24.6 [7.21] 28.7 [8.41] 27.4 [8.03] 25.5 [7.47]  
Power  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
Total BTUH [kW] 38.6 [11.31] 37.9 [11.11] 36.9 [10.81] 35.5 [10.40] 34.9 [10.23] 33.9 [9.94] 33.8 [9.91] 33.2 [9.73] 32.3 [9.47]  
105  
[40.6]  
Sens BTUH [kW] 22.1 [6.48] 21.1 [6.18] 19.6 [5.74] 26.9 [7.88] 25.7 [7.53] 23.9 [7.00] 27.9 [8.18] 26.6 [7.80] 24.8 [7.27]  
Power  
3.0  
3.0  
2.9  
3.0  
2.9  
2.9  
3.0  
2.9  
2.9  
U
R
E
Total BTUH [kW] 36.9 [10.81] 36.2 [10.61] 35.2 [10.32] 33.8 [9.91] 33.1 [9.70] 32.2 [9.44] 32.0 [9.38] 31.4 [9.20] 30.6 [8.97]  
110  
[43.3]  
Sens BTUH [kW] 21.1 [6.18] 20.1 [5.89] 18.7 [5.48] 26.0 [7.62] 24.8 [7.27] 23.1 [6.77] 26.9 [7.88] 25.7 [7.53] 23.9 [7.00]  
°F  
[°C]  
Power  
3.1  
3.1  
3.1  
3.1  
3.1  
3.0  
3.1  
3.1  
3.0  
Total BTUH [kW] 34.6 [10.14] 34.0 [9.96] 33.1 [9.70] 31.5 [9.23] 30.9 [9.06] 30.1 [8.82] 29.7 [8.70] 29.2 [8.56] 28.4 [8.32]  
115  
[46.1]  
Sens BTUH [kW] 19.9 [5.83] 19.0 [5.57] 17.7 [5.19] 24.8 [7.27] 23.7 [6.95] 22.0 [6.45] 25.7 [7.53] 24.6 [7.21] 22.9 [6.71]  
Power  
3.3  
3.2  
3.2  
3.2  
3.2  
3.2  
3.2  
3.2  
3.2  
GROSS SYSTEMS PERFORMANCE DATA—RSNA-B042  
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀  
wbE  
CFM [L/s]  
DR ➀  
71°F [21.7°C]  
1350 [637]  
.23  
67°F [19.4°C]  
1350 [637]  
.23  
63°F [17.2°C]  
1350 [637]  
.23  
1490 [703]  
.24  
1150 [543]  
.21  
1490 [703]  
.24  
1150 [543]  
.21  
1490 [703]  
.24  
1150 [543]  
.21  
Total BTUH [kW] 51.1 [14.98] 50.2 [14.71] 48.8 [14.30] 47.7 [13.98] 46.9 [13.75] 45.6 [13.36] 45.2 [13.25] 44.3 [12.98] 43.1 [12.63]  
75  
[23.9]  
Sens BTUH [kW] 28.1 [8.24] 26.9 [7.88] 25.0 [7.33] 33.4 [9.79] 31.9 [9.35] 29.7 [8.70] 37.9 [11.11] 36.2 [10.61] 33.6 [9.85]  
Power  
2.6  
2.6  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
O
U
T
D
O
O
R
Total BTUH [kW] 50.1 [14.68] 49.2 [14.42] 47.8 [14.01] 46.7 [13.69] 45.9 [13.45] 44.6 [13.07] 44.1 [12.92] 43.3 [12.69] 42.2 [12.37]  
80  
Sens BTUH [kW] 27.9 [8.18] 26.7 [7.83] 24.8 [7.27] 33.2 [9.73] 31.7 [9.29] 29.5 [8.65] 37.6 [11.02] 36.0 [10.55] 33.5 [9.82]  
[26.7]  
Power  
2.7  
2.7  
2.7  
2.7  
2.7  
2.6  
2.7  
2.7  
2.6  
Total BTUH [kW] 49.0 [14.36] 48.1 [14.10] 46.8 [13.72] 45.6 [13.36] 44.8 [13.13] 43.6 [12.78] 43.1 [12.63] 42.3 [12.40] 41.1 [12.05]  
85  
[29.4]  
Sens BTUH [kW] 27.5 [8.06] 26.3 [7.71] 24.5 [7.18] 32.8 [9.61] 31.3 [9.17] 29.1 [8.53] 37.2 [10.90] 35.6 [10.43] 33.1 [9.70]  
Power  
2.9  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
D
R
Y
Total BTUH [kW] 47.9 [14.04] 47.0 [13.77] 45.8 [13.42] 44.5 [13.04] 43.7 [12.81] 42.5 [12.46] 42.0 [12.31] 41.2 [12.07] 40.1 [11.75]  
90  
[32.2]  
Sens BTUH [kW] 27.0 [7.91] 25.8 [7.56] 24.0 [7.03] 32.2 [9.44] 30.8 [9.03] 28.6 [8.38] 36.7 [10.76] 35.0 [10.26] 32.6 [9.55]  
B
U
L
Power  
3.0  
3.0  
2.9  
3.0  
3.0  
2.9  
3.0  
2.9  
2.9  
Total BTUH [kW] 46.8 [13.72] 45.9 [13.45] 44.7 [13.10] 43.4 [12.72] 42.6 [12.48] 41.4 [12.13] 40.8 [11.96] 40.1 [11.75] 39.0 [11.43]  
95  
[35]  
B
Sens BTUH [kW] 26.3 [7.71] 25.1 [7.36] 23.4 [6.86] 31.5 [9.23] 30.1 [8.82] 28.0 [8.21] 36.0 [10.55] 34.4 [10.08] 32.0 [9.38]  
Power  
3.2  
3.1  
3.1  
3.1  
3.1  
3.1  
3.1  
3.1  
3.0  
T
E
M
P
E
R
A
T
Total BTUH [kW] 45.6 [13.36] 44.8 [13.13] 43.6 [12.78] 42.2 [12.37] 41.5 [12.16] 40.4 [11.84] 39.7 [11.63] 39.0 [11.43] 37.9 [11.11]  
100  
[37.8]  
Sens BTUH [kW] 25.6 [7.50] 24.4 [7.15] 22.7 [6.65] 30.8 [9.03] 29.4 [8.62] 27.4 [8.03] 35.3 [10.35] 33.7 [9.88] 31.3 [9.17]  
Power  
3.3  
3.3  
3.2  
3.3  
3.2  
3.2  
3.3  
3.2  
3.2  
Total BTUH [kW] 44.5 [13.04] 43.7 [12.81] 42.5 [12.46] 41.1 [12.05] 40.4 [11.84] 39.3 [11.52] 38.6 [11.31] 37.9 [11.11] 36.8 [10.79]  
105  
[40.6]  
Sens BTUH [kW] 24.8 [7.27] 23.7 [6.95] 22.1 [6.48] 30.1 [8.82] 28.7 [8.41] 26.7 [7.83] 34.5 [10.11] 33.0 [9.67] 30.7 [9.00]  
Power  
3.4  
3.4  
3.4  
3.4  
3.4  
3.3  
3.4  
3.4  
3.3  
U
R
E
Total BTUH [kW] 43.4 [12.72] 42.6 [12.48] 41.5 [12.16] 40.0 [11.72] 39.3 [11.52] 38.2 [11.20] 37.5 [10.99] 36.8 [10.79] 35.8 [10.49]  
110  
[43.3]  
Sens BTUH [kW] 24.2 [7.09] 23.1 [6.77] 21.5 [6.30] 29.4 [8.62] 28.1 [8.24] 26.1 [7.65] 33.9 [9.94] 32.4 [9.50] 30.1 [8.82]  
°F  
[°C]  
Power  
3.6  
3.6  
3.5  
3.6  
3.5  
3.5  
3.5  
3.5  
3.5  
Total BTUH [kW] 42.3 [12.40] 41.6 [12.19] 40.4 [11.84] 39.0 [11.43] 38.3 [11.22] 37.2 [10.90] 36.4 [10.67] 35.7 [10.46] 34.8 [10.20]  
115  
[46.1]  
Sens BTUH [kW] 23.6 [6.92] 22.5 [6.59] 21.0 [6.15] 28.8 [8.44] 27.5 [8.06] 25.6 [7.50] 33.3 [9.76] 31.8 [9.32] 29.6 [8.67]  
Power  
3.7  
3.7  
3.7  
3.7  
3.7  
3.6  
3.7  
3.7  
3.6  
DR —Depression ratio  
dbE —Entering air dry bulb  
wbE—Entering air wet bulb  
Total —Total capacity x 1000 BTUH  
Sens —Sensible capacity x 1000 BTUH  
Power—KW input  
NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible  
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].  
[
] Designates Metric Conversions  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEMS PERFORMANCE—RSNA-B SERIES  
GROSS SYSTEMS PERFORMANCE DATA—RSNA-B048  
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀  
wbE  
CFM [L/s]  
DR ➀  
71°F [21.7°C]  
1600 [755]  
.19  
67°F [19.4°C]  
1600 [755]  
.19  
63°F [17.2°C]  
1600 [755]  
.19  
1760 [831]  
.20  
1360 [642]  
.17  
1760 [831]  
.20  
1360 [642]  
.17  
1760 [831]  
.20  
1360 [642]  
.17  
Total BTUH [kW] 60.8 [17.82] 59.7 [17.50] 58.1 [17.03] 56.4 [16.53] 55.4 [16.24] 53.9 [15.80] 53.1 [15.56] 52.2 [15.30] 50.8 [14.89]  
75  
[23.9]  
Sens BTUH [kW] 36.3 [10.64] 34.7 [10.17] 32.3 [9.47] 41.5 [12.16] 39.7 [11.63] 36.9 [10.81] 48.2 [14.13] 46.0 [13.48] 42.8 [12.54]  
Power  
2.9  
2.9  
2.9  
2.9  
2.9  
2.9  
2.9  
2.8  
2.8  
O
U
T
D
O
O
R
Total BTUH [kW] 59.9 [17.55] 58.8 [17.23] 57.2 [16.76] 55.5 [16.27] 54.5 [15.97] 53.0 [15.53] 52.3 [15.33] 51.3 [15.03] 49.9 [14.62]  
80  
Sens BTUH [kW] 35.2 [10.32] 33.7 [9.88] 31.3 [9.17] 40.4 [11.84] 38.6 [11.31] 35.9 [10.52] 47.1 [13.80] 45.0 [13.19] 41.8 [12.25]  
[26.7]  
Power  
3.1  
3.1  
3.0  
3.1  
3.1  
3.0  
3.0  
3.0  
3.0  
Total BTUH [kW] 58.8 [17.23] 57.7 [16.91] 56.1 [16.44] 54.4 [15.94] 53.4 [15.65] 51.9 [15.21] 51.1 [14.98] 50.2 [14.71] 48.8 [14.30]  
85  
[29.4]  
Sens BTUH [kW] 34.3 [10.05] 32.8 [9.61] 30.5 [8.94] 39.5 [11.58] 37.7 [11.05] 35.1 [10.29] 46.1 [13.51] 44.1 [12.92] 41.0 [12.02]  
Power  
3.3  
3.2  
3.2  
3.3  
3.2  
3.2  
3.2  
3.2  
3.1  
D
R
Y
Total BTUH [kW] 57.4 [16.82] 56.4 [16.53] 54.8 [16.06] 53.0 [15.53] 52.0 [15.24] 50.6 [14.83] 49.7 [14.57] 48.8 [14.30] 47.5 [13.92]  
90  
[32.2]  
Sens BTUH [kW] 33.5 [9.82] 32.0 [9.38] 29.8 [8.73] 38.7 [11.34] 37.0 [10.84] 34.4 [10.08] 45.3 [13.28] 43.4 [12.72] 40.3 [11.81]  
B
U
L
Power  
3.4  
3.4  
3.4  
3.4  
3.4  
3.4  
3.4  
3.3  
3.3  
Total BTUH [kW] 55.9 [16.38] 54.9 [16.09] 53.4 [15.65] 51.5 [15.09] 50.6 [14.83] 49.2 [14.42] 48.2 [14.13] 47.4 [13.89] 46.1 [13.51]  
95  
[35]  
B
Sens BTUH [kW] 33.1 [9.70] 31.6 [9.26] 29.4 [8.62] 38.3 [11.22] 36.6 [10.73] 34.0 [9.96] 45.0 [13.19] 42.9 [12.57] 39.9 [11.69]  
Power  
3.6  
3.6  
3.5  
3.6  
3.6  
3.5  
3.5  
3.5  
3.5  
T
E
M
P
E
R
A
T
Total BTUH [kW] 54.3 [15.91] 53.3 [15.62] 51.9 [15.21] 49.9 [14.62] 49.0 [14.36] 47.7 [13.98] 46.7 [13.69] 45.8 [13.42] 44.6 [13.07]  
100  
[37.8]  
Sens BTUH [kW] 33.0 [9.67] 31.5 [9.23] 29.3 [8.59] 38.2 [11.20] 36.5 [10.70] 34.0 [9.96] 45.0 [13.19] 42.9 [12.57] 39.9 [11.69]  
Power  
3.8  
3.7  
3.7  
3.8  
3.7  
3.7  
3.7  
3.7  
3.6  
Total BTUH [kW] 52.8 [15.47] 51.8 [15.18] 50.4 [14.77] 48.4 [14.18] 47.5 [13.92] 46.2 [13.54] 45.1 [13.22] 44.3 [12.98] 43.1 [12.63]  
105  
[40.6]  
Sens BTUH [kW] 33.4 [9.79] 31.9 [9.35] 29.7 [8.70] 38.6 [11.31] 36.9 [10.81] 34.3 [10.05] 45.1 [13.22] 43.2 [12.66] 40.2 [11.78]  
Power  
3.9  
3.9  
3.9  
3.9  
3.9  
3.9  
3.9  
3.9  
3.8  
U
R
E
Total BTUH [kW] 51.3 [15.03] 50.4 [14.77] 49.0 [14.36] 46.9 [13.75] 46.1 [13.51] 44.8 [13.13] 43.6 [12.78] 42.9 [12.57] 41.7 [12.22]  
110  
[43.3]  
Sens BTUH [kW] 34.4 [10.08] 32.9 [9.64] 30.6 [8.97] 39.6 [11.61] 37.8 [11.08] 35.2 [10.32] 43.6 [12.78] 42.9 [12.57] 41.1 [12.05]  
°F  
[°C]  
Power  
4.1  
4.1  
4.0  
4.1  
4.1  
4.0  
4.1  
4.0  
4.0  
Total BTUH [kW] 50.0 [14.65] 49.1 [14.39] 47.8 [14.01] 45.6 [13.36] 44.8 [13.13] 43.6 [12.78] 42.3 [12.40] 41.6 [12.19] 40.4 [11.84]  
115  
[46.1]  
Sens BTUH [kW] 36.0 [10.55] 34.4 [10.08] 32.0 [9.38] 41.2 [12.07] 39.4 [11.55] 36.6 [10.73] 42.3 [12.40] 41.6 [12.19] 40.4 [11.84]  
Power  
4.3  
4.2  
4.2  
4.3  
4.3  
4.2  
4.2  
4.2  
4.1  
GROSS SYSTEMS PERFORMANCE DATA—RSNA-B060  
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀  
wbE  
CFM [L/s]  
DR ➀  
71°F [21.7°C]  
1850 [873]  
.20  
67°F [19.4°C]  
1850 [873]  
.20  
63°F [17.2°C]  
1850 [873]  
.20  
2040 [963]  
.21  
1570 [741]  
.18  
2040 [963]  
.21  
1570 [741]  
.18  
2040 [963]  
.21  
1570 [741]  
.18  
Total BTUH [kW] 69.9 [20.49] 68.7 [20.13] 66.8 [19.58] 66.3 [19.43] 65.1 [19.08] 63.3 [18.55] 63.8 [18.70] 62.6 [18.35] 60.9 [17.85]  
75  
[23.9]  
Sens BTUH [kW] 41.5 [12.16] 39.7 [11.63] 36.9 [10.81] 48.8 [14.30] 46.7 [13.69] 43.4 [12.72] 53.0 [15.53] 50.6 [14.83] 47.1 [13.80]  
Power  
3.9  
3.8  
3.8  
3.8  
3.7  
3.7  
3.7  
3.7  
3.7  
O
U
T
D
O
O
R
Total BTUH [kW] 69.6 [20.40] 68.4 [20.05] 66.5 [19.49] 65.9 [19.31] 64.8 [18.99] 63.0 [18.46] 63.4 [18.58] 62.3 [18.26] 60.6 [17.76]  
80  
Sens BTUH [kW] 40.4 [11.84] 38.6 [11.31] 35.9 [10.52] 47.8 [14.01] 45.6 [13.36] 42.4 [12.43] 51.9 [15.21] 49.6 [14.54] 46.1 [13.51]  
[26.7]  
Power  
4.1  
4.0  
4.0  
4.0  
4.0  
3.9  
3.9  
3.9  
3.9  
Total BTUH [kW] 68.5 [20.08] 67.3 [19.72] 65.4 [19.17] 64.8 [18.99] 63.7 [18.67] 61.9 [18.14] 62.3 [18.26] 61.2 [17.94] 59.5 [17.44]  
85  
[29.4]  
Sens BTUH [kW] 39.4 [11.55] 37.6 [11.02] 35.0 [10.26] 46.7 [13.69] 44.6 [13.07] 41.5 [12.16] 50.9 [14.92] 48.6 [14.24] 45.2 [13.25]  
Power  
4.3  
4.3  
4.2  
4.2  
4.2  
4.1  
4.2  
4.1  
4.1  
D
R
Y
Total BTUH [kW] 66.8 [19.58] 65.6 [19.23] 63.9 [18.73] 63.2 [18.52] 62.0 [18.17] 60.4 [17.70] 60.7 [17.79] 59.6 [17.47] 58.0 [17.00]  
90  
[32.2]  
Sens BTUH [kW] 38.3 [11.22] 36.6 [10.73] 34.0 [9.96] 45.7 [13.39] 43.6 [12.78] 40.6 [11.90] 49.8 [14.59] 47.6 [13.95] 44.3 [12.98]  
B
U
L
Power  
4.5  
4.5  
4.4  
4.4  
4.4  
4.3  
4.4  
4.3  
4.3  
Total BTUH [kW] 64.8 [18.99] 63.7 [18.67] 61.9 [18.14] 61.2 [17.94] 60.1 [17.61] 58.4 [17.12] 58.7 [17.20] 57.6 [16.88] 56.0 [16.41]  
95  
[35]  
B
Sens BTUH [kW] 37.3 [10.93] 35.6 [10.43] 33.1 [9.70] 44.6 [13.07] 42.6 [12.48] 39.7 [11.63] 48.8 [14.30] 46.6 [13.66] 43.4 [12.72]  
Power  
4.7  
4.7  
4.6  
4.6  
4.6  
4.5  
4.6  
4.5  
4.5  
T
E
M
P
E
R
A
T
Total BTUH [kW] 62.7 [18.38] 61.6 [18.05] 59.9 [17.55] 59.0 [17.29] 58.0 [17.00] 56.4 [16.53] 56.5 [16.56] 55.5 [16.27] 54.0 [15.83]  
100  
[37.8]  
Sens BTUH [kW] 36.3 [10.64] 34.7 [10.17] 32.3 [9.47] 43.6 [12.78] 41.7 [12.22] 38.8 [11.37] 47.8 [14.01] 45.7 [13.39] 42.5 [12.46]  
Power  
4.9  
4.9  
4.8  
4.8  
4.8  
4.7  
4.8  
4.8  
4.7  
Total BTUH [kW] 60.6 [17.76] 59.6 [17.47] 57.9 [16.97] 57.0 [16.71] 55.9 [16.38] 54.4 [15.94] 54.5 [15.97] 53.5 [15.68] 52.0 [15.24]  
105  
[40.6]  
Sens BTUH [kW] 35.3 [10.35] 33.8 [9.91] 31.4 [9.20] 42.7 [12.51] 40.8 [11.96] 37.9 [11.11] 46.9 [13.75] 44.8 [13.13] 41.6 [12.19]  
Power  
5.1  
5.1  
5.0  
5.1  
5.0  
4.9  
5.0  
5.0  
4.9  
U
R
E
Total BTUH [kW] 58.8 [17.23] 57.8 [16.94] 56.2 [16.47] 55.2 [16.18] 54.2 [15.88] 52.7 [15.44] 52.7 [15.44] 51.7 [15.15] 50.3 [14.74]  
110  
[43.3]  
Sens BTUH [kW] 34.4 [10.08] 32.9 [9.64] 30.6 [8.97] 41.8 [12.25] 39.9 [11.69] 37.1 [10.87] 45.9 [13.45] 43.9 [12.87] 40.8 [11.96]  
°F  
[°C]  
Power  
5.3  
5.3  
5.2  
5.3  
5.2  
5.2  
5.2  
5.2  
5.1  
Total BTUH [kW] 57.5 [16.85] 56.5 [16.56] 55.0 [16.12] 53.9 [15.80] 52.9 [15.50] 51.4 [15.06] 51.3 [15.03] 50.4 [14.77] 49.0 [14.36]  
115  
[46.1]  
Sens BTUH [kW] 33.5 [9.82] 32.0 [9.38] 29.8 [8.73] 40.9 [11.99] 39.1 [11.46] 36.3 [10.64] 45.0 [13.19] 43.0 [12.60] 40.0 [11.72]  
Power  
5.6  
5.5  
5.4  
5.5  
5.4  
5.4  
5.4  
5.4  
5.3  
DR —Depression ratio  
dbE —Entering air dry bulb  
wbE—Entering air wet bulb  
Total —Total capacity x 1000 BTUH  
Sens —Sensible capacity x 1000 BTUH  
Power—KW input  
NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible  
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].  
[
] Designates Metric Conversions  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AIRFLOW PERFORMANCE—RSNA-B SERIES  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AIRFLOW PERFORMANCE—RSNA-B SERIES  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL DATA—RSNA-B SERIES  
ELECTRICAL DATA – RSNA-B SERIES  
-B024JK  
-B030JK  
-B036CK  
-B036JK  
-B042CK  
-B042JK  
-B048CK  
-B048JK  
-B060CK  
-B060JK  
Unit Operating  
Voltage Range  
187-253  
187-253  
187-253  
187-253  
187-253  
187-253  
187-253  
187-253  
187-253  
187-253  
Minimum Circuit Ampacity  
16/16  
20/20  
25/25  
22/22  
25/25  
35/35  
16/16  
20/20  
25/25  
22/22  
30/30  
35/35  
18/18  
20/20  
25/25  
26/26  
30/30  
40/40  
22/22  
25/25  
30/30  
32/32  
40/40  
50/50  
33/33  
40/40  
50/50  
43/43  
50/50  
60/60  
Minimum Overcurrent  
Protection Device Size  
Maximum Overcurrent  
Protection Device Size  
No.  
1
208/230  
1
1
208/230  
1
1
208/230  
3
1
208/230  
1
1
208/230  
3
1
208/230  
1
1
208/230  
3
1
208/230  
1
1
208/230  
3
1
Volts  
208/230  
Phase  
1
HP  
2 1/6  
3450  
2 2/3  
3450  
3 1/3  
3450  
9.6/9.6  
88/88  
1
3 1/3  
3450  
3 1/2  
3450  
3 1/2  
3450  
4
4
5
5
RPM  
3450  
3450  
3450  
3450  
Amps (RLA)  
10.4/10.4 14.1/14.1  
14.4/14.4 10.3/10.3 16.5/16.5 12.2/12.2 20.2/20.2 17.3/17.3  
25/25  
Amps (LRA)  
54/54  
68/68  
77/77  
77/77  
95/95  
80.8/80.8  
137/137  
123/123  
148/148  
No.  
1
208/230  
1
1
208/230  
1
1
208/230  
1
1
1
1
1
1
1
Volts  
208/230  
1
208/230  
208/230  
208/230  
208/230  
208/230  
208/230  
Phase  
1
1/3  
2
1
1/3  
2
1
1/3  
2
1
1/3  
2
1
1
HP  
1/5  
1/5  
1/5  
1/5  
1/3  
1/3  
Amps (FLA)  
1.3  
1.3  
1.3  
1.3  
2
2
Amps (LRA)  
2.3  
2.3  
2.3  
2.3  
3.9  
1
3.9  
1
3.9  
1
3.9  
1
3.9  
3.9  
No.  
1
1
1
1
1
1
Volts  
208/230  
1
208/230  
1
208/230  
1
208/230  
1
208/230  
1
208/230  
1
208/230  
1
208/230  
1
208/230  
208/230  
Phase  
HP  
1
1
1
1
1/4  
1/2  
1/2  
1/2  
1/2  
2.4  
5.1  
1/2  
2.4  
5.1  
3/4  
4.4  
9.5  
3/4  
4.4  
9.5  
Amps (FLA)  
Amps (LRA)  
1.3  
2.3  
2.4  
5.1  
2.4  
5.1  
2.4  
5.1  
9.1  
0
9.1  
0
1. Horsepower Per Compressor.  
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.  
Copper Wire Size—AWG (1% Voltage Drop)  
300  
250  
200  
150  
4
4
6
8
3
4
4
6
8
2
3
4
6
8
2
3
4
4
6
1
2
3
4
6
8
1/0 1/0 2/0 2/0 3/0 3/0 3/0 4/0 4/0 4/0  
4/0  
4/0  
3/0  
1/0  
1
250 250 250 250 300 300 300  
1
2
4
6
8
1
2
3
4
6
1/0 1/0 2/0 2/0 2/0 3/0 3/0 3/0  
4/0  
3/0  
2/0  
1
4/0  
3/0  
2/0  
1
4/0  
3/0  
2/0  
1
4/0  
3/0  
2/0  
1/0  
2
250 250 250  
1
3
4
6
1
2
4
6
1/0 1/0 1/0 2/0 2/0 2/0  
4/0  
2/0  
1/0  
1
4/0  
3/0  
1/0  
1
4/0  
3/0  
1/0  
1
2
3
4
1
3
4
1
2
4
1/0 1/0 1/0  
100 10  
2
3
2
3
1
3
50 14 12 10 10  
2
2
2
2
15 20 25 30 35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
95  
100 105 110 115 120 125  
CIRCUIT AMPACITY  
Notes: 1. Wire size based on 60°C. type copper conductors below 100 ampacity.  
2. Wire size based on 75°C. type copper conductors for 100 ampacity and above.  
[
] Designates Metric Conversions  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRIC HEATER KITS—RSNA-B SERIES  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT DIMENSIONS—RSNA-B SERIES  
UNIT DIMENSIONS  
PACKAGE  
AIR CONDITIONERS  
OUTDOOR FAN GRILLE  
AND COMPRESSOR ACCESS  
CONTROL  
FILTER ACCESS  
ACCESS PANEL  
PANEL (FOR  
UNIT MOUNTED  
FILTER ACCESSORY)  
30% 2%  
LIQUID PRESSURE  
SERVICE PORT  
OUTDOOR COIL  
PROTECTIVE GRILLE  
TOP COVER  
21% 2%  
SUCTION PRESSURE  
SERVICE PORT  
THREADED PVC CONDENSATE  
DRAIN CONNECTION N.P.T.  
THERMOSTAT WIRING  
ENTRANCE  
29% 2%  
IMPORTANT: UNIT MUST BE LEVEL TO  
PREVENT WATER MIGRATION  
ELECTRICAL POWER  
ENTRANCE  
CORNER WEIGHTS  
% OF TOTAL  
UNIT WEIGHT  
20% 2%  
SIDE RETURN  
DUCT OPENING  
BLOWER/  
EVAPORATOR  
ACCESS PANEL  
SIDE SUPPLY  
DUCT OPENING  
TOP VIEW  
BOTTOM VIEW  
451/16"  
4719/32"  
[1209 mm]  
[1145 mm]  
13/16"  
[30 mm]  
TYP.  
INSIDE  
11/2"  
[38 mm]  
TYP.  
BOTTOM  
RETURN  
DUCT  
OPENING  
5013/16"  
[1290 mm]  
497/16"  
[1256 mm]  
INSIDE  
BOTTOM  
SUPPLY  
DUCT  
141/4"  
[362 mm]  
TYP.  
OPENING  
199/16"  
[497 mm]  
153/8"  
[391 mm]  
313/16"  
[97 mm]  
45/16"  
[95 mm]  
33/16"  
[97 mm]  
OUTDOOR FAN  
GRILLE &  
COMPRESSOR ACCESS  
[
] Designates Metric Conversions  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT DIMENSIONS—RSNA-B SERIES  
SIDE VIEW  
SIDE VIEW  
OUTDOOR  
COIL PROTECTIVE  
GRILLE  
FILTER ACCESS PANEL (FOR UNIT  
MOUNTED FILTER ACCESSORY  
THERMOSTAT  
WIRE ENTRANCE  
11/8"  
[28.6 mm]  
255/16"  
[643 mm]  
103/16"  
[259 mm]  
51/16"  
[129 mm]  
ELECTRICAL  
POWER ENTRANCE  
527/16"  
[1332 mm]  
BLOWER/  
EVAPORATOR  
ACCESS PANEL  
43/4"  
[121 mm]  
FRONT VIEW  
REAR VIEW  
CONTROL  
ACCESS PANEL  
47/8"  
[124 mm]  
SIDE SUPPLY  
DUCT OPENING  
133/4"  
[349 mm]  
LIQUID  
PRESSURE  
SERVICE PORT  
75/16"  
[186 mm]  
57/16" [138 mm]  
81/2"  
[216 mm]  
TYP.  
143/16"  
[360 mm]  
TYP.  
2211/16"  
[576 mm]  
47/16"  
[113 mm]  
471/2"  
[1207 mm]  
15"  
[381 mm]  
191/8"  
[486 mm]  
SIDE RETURN  
DUCT OPENING  
SHOWN WITH DUCT COVERS REMOVED.  
THREADED PVC  
CONDENSATED DRAIN  
CONNECTION (3/4 N.P.T.)  
SUCTION PRESSURE  
SERVICE PORT  
IMPORTANT:  
IMPORTANT:  
Unit must be level to  
prevent water migration.  
INSTALLATION MUST NOT  
INTERFERE WITH DRAINAGE  
OPENINGS IN BOTTOM OF UNIT  
UNDER OUTDOOR COIL.  
Model #  
Height “A”  
B024, B030,  
B036  
3515/16  
B042, B048,  
B060  
41  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL INSTALLATIONS  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
ACCESSORY EQUIPMENT  
Accessory  
Model  
Application  
Accessory  
Model No.  
Description  
RXSG-AAA08 (8" [203 mm] Height)  
RXSG-AAA14 (14" [356 mm] Height)  
RXSG-AAA24 (24" [610 mm] Height)  
Roofcurbs  
RSNA-B  
Supply & Return Diffusers  
RSNA-B  
RSNA-B  
RXRN-BD15  
RXRE-CAA30 (3 Position)  
RXRD-CAM10 (Fully Modulating)  
Economizers (Downflow ONLY)  
RXRF-FAB1 (Motorized-35%)  
RXRF-FAA1 (Fixed-35%)  
Fresh Air Damper  
RSNA-B  
RSNA-B  
RXMC-CA02 (16" [406 mm] Ducts)  
RXMC-CA03 (18" [457 mm] Ducts)  
Rectangular to Round Transition (Downflow)  
Filter Kit  
RSNA-B  
RSNA-B  
RSNA-B  
RSNA-B  
RSNA-B  
RXRY-B01  
RXRZ-A18  
RXAB-A02  
RXAC-A02  
RXMC-BA01  
Low Ambient Control  
High Pressure Control  
Low Pressure Control  
Sideflow Rectangular to Round Transition  
RXGJ-EP84W (White-Rodgers Gas Valve)  
RXGJ-EP85H (Honeywell Gas Valve)  
LP Conversion Kits  
RSNA-B  
RSNA-B  
Canadian High Altitude Kit (for Natural Gas only*)  
RXRX-AH01  
*If a particular unit is to be converted to operate on LP (propane) for elevations above 2000 ft. [609.6 m] in Canada, the existing Natural Gas to LP Conversion Kits for the  
subject models already contain the necessary orifices and instructions to de-rate the input for 2000-4500 ft. [609.6-1371.6 m] Canadian applications.  
[
] Designates Metric Conversions  
COMMON SUPPLY/RETURN  
CONCENTRIC AIR DIFFUSER  
SUPPLY/RETURN DIFFUSER  
NOTE: The location of the combination supply and return diffuser should  
not exceed 10 feet [3.05 m] above the floor level for units @ 1000 CFM  
[472 L/s] or less and 12 [3.66 m] to 14 feet [4.27 m] above the floor level  
for units with CFM greater than 1000 [472 L/s]. If the diffuser is installed  
with a greater distance than recommended above, the supply air may  
become stratified above the required comfort area causing uncomforta-  
ble conditions.  
AIRFLOW/PRESSURE DROP  
INFORMATION (INCHES W.C. [kPa])  
Designed to convert a side by side or an over and under arrange-  
ment into a concentric distribution of air. The diffuser is flush  
mounted, completely insulated, assembled, and internally baffled  
to provide four way supply air distribution with a center return. To  
make the assembly complete and ready to fit into a 2' [0.61 m] x  
4' [1.22 m] suspended ceiling grid, the diffuser includes  
adjustable supply louvers, hanging rings, anti-sweat gasket, and  
round flanges for use with flexible ducts.  
Approximate CFM [L/s]-Supply Air  
Accessory  
1300 [614] 1575 [743] 1800 [850] 2200 [1038]  
Plenum & Supply/Return Duct .07 [.017] .10 [.024] .12 [.030] .17 [.042]  
Diffuser  
Economizer  
.09 [.022] .13 [.032] .16 [.040] .24 [.060]  
.06 [.015] .09 [.022] .11 [.027] .17 [.042]  
SUPPLY AIR/PERFORMANCE  
Diffuser Airflow CFM [L/s]  
800 [378]-1200 [566]  
1600 [755]-2000 [944]  
Range of Throw Ft. [m]  
14 [4.27]-16 [4.88]  
18 [5.49]-28 [8.53]  
Model No.  
RXRN-  
Diameter  
Inches [mm]  
Shipping Wt.  
Lbs. [kg]  
Dimension A  
Inches [mm]  
BD15  
16 [406]  
90 [40.82]  
201/2 [521]  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
DUCT ADAPTERS  
RECTANGULARTO ROUND  
TRANSITIONS (DOWNFLOW)  
RXMC-CA02  
RXMC-CA03  
[
] Designates Metric Conversions  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
FRESH AIR DAMPER FOR USE ON  
RSNA-B SERIES  
RXRF-FAA1 (Fixed - 0-35%)  
The 0-35% manual outside Air Damper is designed to replace the  
unit return air duct cover. No drilling or damper assembly is  
required. The amount of outside air (0-35%) is controlled by sim-  
ply adjusting the side damper.  
RXRF-FAB1 (Motorized - 0-35%)  
The 0-35% motorized outside Air Damper is designed to replace  
the unit return air duct cover. No drilling or damper assembly is  
required. The control motor opens the adjustable slide damper  
when the unit blower motor is energized.  
ECONOMIZERS  
RXRE-CAA30 (3 Position) and  
RXRD-CAM10 (Fully Modulating) for  
RSNA-B Series  
RXRE-CAA30 (3 Position)  
Provided with enthalpy control, and  
mixed air sensor. Settings include  
fully open, fully closed and adjustable  
mid point.  
RXRD-CAM10 (Fully Modulating)  
Provided with enthalpy control, mixed  
air sensor and minimum position poten-  
tiometer for proportioning (modulating)  
the amount of fresh air.  
Note: See economizer installation instruc-  
tions for correct filter access door.  
[
] Designates Metric Conversions  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
FILTER KIT INSTALLATION  
RXRY-B01  
For use in either  
vertical or horizontal  
discharge.  
CFM [L/s]  
Airflow Pressure Drop, Inches W.C. [kPa]  
1" Filter  
Minimum  
Airflow  
Nominal  
Airflow  
Maximum  
Airflow  
CFM [L/s]  
500 [236]  
600 [283]  
700 [330]  
800 [378]  
900 [425]  
1000 [472]  
1100 [519]  
1200 [566]  
1300 [614]  
1400 [661]  
1500 [708]  
1600 [755]  
1700 [802]  
1800 [850]  
1900 [897]  
2000 [944]  
2" Filter  
Model No.  
.02 [.0050]  
.03 [.0075]  
.03 [.0075]  
.04 [.0010]  
.05 [.0124]  
.06 [.0149]  
.08 [.0199]  
.09 [.0224]  
.12 [.0299]  
.15 [.0373]  
.19 [.0473]  
.21 [.0523]  
.23 [.0572]  
.24 [.0598]  
.25 [.0623]  
.27 [.0672]  
.29 [.0722]  
RSNA-B  
RSNA-B  
RSNA-B  
RSNA-B  
RSNA-B  
RSNA-B  
510 [241]  
680 [321]  
850 [401]  
1020 [481]  
1190 [562]  
1275 [602]  
600 [283]  
800 [378]  
660 [311]  
880 [415]  
.02 [.0050]  
.03 [.0075]  
1000 [472]  
1200 [566]  
1400 [661]  
1500 [708]  
1100 [519]  
1320 [623]  
1540 [727]  
1650 [779]  
.04 [.0010]  
.05 [.0124]  
.07 [.0174]  
.08 [.0199]  
.10 [.0249]  
.13 [.0324]  
[
] Designates Metric Conversions  
.16 [.0398]  
.19 [.0473]  
.20 [.0498]  
.21 [.0523]  
.22 [.0548]  
.24 [.0598]  
.26 [.0647]  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
DUCT ADAPTER SIDEFLOW  
SQUARETO ROUNDTRANSITION  
RXMC-BA01  
Adapts the side rectangular supply and return openings to 14"  
[356 mm] diameter round openings. Adapters provided with same  
finish as unit and also provided with thermal insulation.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
ROOFCURB (Full Perimeter)  
RXSG-AAA08, RXSG-AAA14  
and RXSG-AAA24 for  
RSNA-B Series  
Hinged corners make for  
fast, easy set-up.  
RXSG-AAA08  
(8" [203 mm] High)  
NOT for use with  
RQKA/RQLA/RQMA  
Package Heat Pumps.  
[
] Designates Metric Conversions  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
ROOFCURB (Full Perimeter) (Cont.)  
RXSG-AAA24  
(24" [610 mm] High)  
[
] Designates Metric Conversions  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
PACKAGE AIR CONDITIONERS &  
GAS/ELECTRIC PACKAGE UNITS  
ROOFCURB INSTALLATION (Full Perimeter)  
[
] Designates Metric Conversions  
ROOFCURB ADAPTERS  
Fabricated from galvanized steel to adapt the New cabinet to the old style curb. All are furnished with a New gasket.  
OLD MODEL  
OLD CURB MODEL  
NEW MODEL TO OLD MODEL  
ROOFCURB ADAPTER  
NEW MODEL PACKAGE  
SMALL CABINET  
RXPA-CA20 (1)  
RXRA-DB20 (2)  
(11/2-2 TON) [5.28-7.03 kW]  
RSNC-, RSND-, RSNE-  
RRGE-, RRGF-, RRGG-, RSNY  
20 SERIES  
ONLY 1 CABINET SIZE—  
MEDIUM CABINET  
ALL MODELS  
RXPA-CA21 (1)  
RXRA-DB21 (2)  
RXPX-BACCA20  
RXRX-BACDB20  
RXPX-BACCA21  
RXRX-BACDB21  
RXPX-BCCCA22  
RXRX-BCCDB22  
RXPX-BCCCA23  
RXRX-BCCDB23  
(21/2-3 TON) [8.79-10.55 kW]  
RSNC-, RSND-, RSNE-  
RRGE-, RRGF-, RRGG-, RSNY  
21 SERIES  
22 SERIES  
RSNA-B  
LARGE CABINET  
(3-31/2 TON) [10.55-12.31 kW]  
RRGE-, RRGF-, RRGG-, RSNY  
RXPA-CA22 (1)  
RXRA-DB22 (2)  
EXTRA LARGE CABINET  
(31/2-5 TON) [12.31-17.58 kW]  
RSNC-, RSND-, RSNE-  
RXPA-CA23 (1)  
RXRA-DB23 (2)  
23 SERIES  
RRGE-, RRGF-, RRGG-, RSNY  
(4-5 TON) [14.07-17.58 kW]  
(1) SLOPE TYPE  
(2) FULL PERIMETER TYPE  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
LIFT KIT—MODEL NO. RXML-A01  
The lift kit is intended for temporary installation while the unit is  
being lifted into position. Kit includes 4 lift brackets.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
ELECTRIC HEATER KITS—RSNA-B  
Unit Model Application  
Electric Heater Kit Models  
RXQJ-A05J (208-240 volt, 1-ph, 5kW)  
RXQJ-A10J (208-240 volt, 1-ph, 10kW)  
RXQJ-A05J (208-240 volt, 1-ph, 5kW)  
RXQJ-A10J (208-240 volt, 1-ph, 10kW)  
RXQJ-A10J (208-240 volt, 1-ph, 10kW)  
RXQJ-A15J (208-240 volt, 1-ph, 15kW)  
RXQJ-B10J (208-240 volt, 1-ph, 10kW)  
RXQJ-B15J (208-240 volt, 1-ph, 15kW)  
RXQJ-B10J (208-240 volt, 1-ph, 10kW)  
RXQJ-B15J (208-240 volt, 1-ph, 15kW)  
RXQJ-A10C (208-240 volt, 3-ph, 10kW)  
RXQJ-A15C (208-240 volt, 3-ph, 15kW)  
RXQJ-A16C (208-240 volt, 3-ph, 15kW-Canadian)  
RXQJ-A10C (208-240 volt, 3-ph, 10kW)  
RXQJ-A15C (208-240 volt, 3-ph, 15kW)  
RXQJ-A10C (208-240 volt, 3-ph, 10kW)  
RXQJ-A15C (208-240 volt, 3-ph, 15kW)  
RSNA-B024JK  
RSNA-B030JK  
RSNA-B036JK  
RSNA-B042JK  
RSNA-B048JK  
RSNA-B036CK  
RSNA-B042CK  
RSNA-B048CK, RSNA-B060CK  
[
] Designates Metric Conversions  
WARNING  
ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED,  
TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETYTESTING AGENCY FOR USEWITHTHIS UNIT. USE OF ANY OTHER  
MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROP-  
ERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING SCHEMATICS—RSNA-B SERIES  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING SCHEMATICS—RSNA-B SERIES  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING SCHEMATICS—RSNA-B SERIES  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING SCHEMATICS—RSNA-B SERIES  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING SCHEMATICS—RSNA-B SERIES  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING SCHEMATICS—RSNA-B SERIES  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM  
YOUR RETAILER.  
GENERALTERMS OF LIMITED WARRANTY  
Rheem will furnish a replacement for any part of this product  
which fails in normal use and service within the applicable  
periods stated, in accordance with the terms of the limited  
warranty.  
For Complete Details of the Limited Warranty, Including Applicable Terms  
and Conditions, SeeYour Local Installer or Contact the Manufacturer for  
a Copy.  
Condenser Coil and Evaporator Coil leaks  
caused by factory defects ..........................Five (5) Years  
Compressor..................................................Five (5) Years  
Any Other Part  
1-Phase Models............................................Five (5) Years  
3-Phase Models..............................................One (1) Year  
RHEEM  
AIR CONDITIONING  
DIVISION  
Before proceeding with installation, refer  
to installation instructions packaged  
with each model, as well as complying  
with all Federal, State, Provincial, and  
Local codes, regulations, and practices.  
5600 Old Greenwood Road, Fort Smith, Arkansas 72908  
“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.”  
PRINTED IN U.S.A.  
11-05 DC  
FORM NO. S11-933 REV. 2  
Supersedes Form No. S11-933 Rev. 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  

PYLE Audio Speaker PLWB108X User Guide
Rockford Fosgate Car Speaker RFP 1408 1808 User Guide
Roland Musical Instrument Vs 880 User Guide
Rotel Stereo Amplifier RB 870BX User Guide
Saeco Coffee Makers Coffeemaker HD8836 User Guide
Samsung CRT Television 15K10 User Guide
Samsung DVD VCR Combo V6700 User Guide
Sanyo Battery Charger UF553450R User Guide
Saturn Automobile 2005 Relay User Guide
Schneider Electric Marine Instruments PM810 User Guide