Remington Indoor Fireplace QFP40 User Guide

REMINGTON QFP40  
Direct Vent Gas Fireplace  
INSTALLATION, VENTING, OPERATION AND MAINTENANCE MANUAL  
Installation and service must be performed by a qualified installer, service agency, or the gas supplier.  
WARNING!  
If the information in these instructions is not followed exactly a fire or explosion may  
result causing property damage, personal injury or death.  
FOR YOUR SAFETY  
DO NOT store or use gasoline or other flammable vapors and liquids in the vicinity of this or  
any other appliance.  
WHAT TO DO IF YOU SMELL GAS  
N Extinquish any open flame.  
N Open windows.  
N Immediately call your gas supplier from a  
neighbor’s phone.  
N Do not try to light any appliance.  
N Do not touch any electric switch.  
N Do not use any telephone in your build-  
ing.  
N Follow the gas supplier’s instructions.  
N If you cannot reach your gas supplier, call  
the fire department.  
This appliance may be installed in an aftermarket permanently located, manufactured  
(mobile) home where not prohibited by local codes.  
This appliance is only for use with the type of gas indicated on the rating plate.  
This appliance is not convertible for use with other gases, unless a certified kit is used.  
SAVE THESE INSTRUCTIONS  
1445 North HIghway  
Colville, WA 99114  
Part #250-4721 (842-3291) 06/2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
NOTES  
MODEL NAME  
Quadra Fire REMINGTON QFP40  
SERIAL NUMBER  
Located on front, lower ledge of control panel.  
DATE PURCHASED  
DEALERSHIP WHERE PURCHASED  
DEALER PHONE  
ADDITIONAL INFORMATION  
After completing your warranty card, attach your sales receipt and  
warranty stub here for future reference.  
Page 3  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
CONTENTS  
SAFETY & CLEARANCES:  
Ratings Plate................................................................................................. 6  
Standards Listing & Clearances Label.......................................................... 7  
Safety Notices............................................................................................... 9  
SPECIFICATIONS:  
Heating Specifications .................................................................................. 10  
ZC Appliance Dimensions............................................................................. 10  
Minimum Cabinet Dimensions ...................................................................... 11  
INSTALLATION PREPARATION:  
Installation Terminology ................................................................................ 12  
Preparation ................................................................................................... 13  
Overview of Installation to Operation............................................................ 13  
LP Conversion Instructions ........................................................................... 14  
INSTALLATION:  
Minimum Framing Dimensions ..................................................................... 16  
Corner Installations ....................................................................................... 17  
Raised Fireplaces ......................................................................................... 18  
Hearth Requirements.................................................................................... 20  
Mantel Requirements.................................................................................... 21  
Arched Fascia Dimensions ........................................................................... 22  
Acid Wash Alert............................................................................................. 22  
Rectangular Fascia Dimensions ................................................................... 23  
Facing Requirements.................................................................................... 24  
Facing Over 1" Thick..................................................................................... 25  
VENTING INSTRUCTIONS:  
General Venting Instructions......................................................................... 26  
Simpson Dura-Vent Parts List & Kits ............................................................ 27  
Venting Installation Options & Guidelines .................................................... 28  
Vertical Termination Rule .............................................................................. 28  
Termination Cap Requirements .................................................................... 28  
Venting Installation Examples:  
Horizontal ........................................................................................... 29  
Vertical ............................................................................................... 29  
Class A Metal Chimney ...................................................................... 30  
Masonry Chimney .............................................................................. 31  
How to use Vent Graph................................................................................. 32  
Horizontal Termination Requirements........................................................... 33  
Horizontal Installation Instructions ................................................................ 34  
Vertical Installation Instructions .................................................................... 38  
Page 4  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
CONTENTS  
COMPLETING INSTALLATION:  
Gas Line Requirements ................................................................................ 46  
Electrical Connection ................................................................................... 47  
Optional Thermostat Connection ................................................................. 47  
Optional Brick Installation............................................................................. 48  
Logset and Nugget Installation .................................................................... 50  
Glass Installation .......................................................................................... 53  
Fascia Installation ........................................................................................ 53  
Leak Test ...................................................................................................... 54  
Initial Start-up Normal Occurrences ............................................................. 54  
Lighting Instructions ..................................................................................... 55  
Shutter Adjustment....................................................................................... 56  
Damper Adjustment...................................................................................... 56  
Flame Height Adjustment ............................................................................. 56  
Adjusting Blower Speed ............................................................................... 56  
Normal Operating Sounds ........................................................................... 56  
High Altitude Operation & Adjustment.......................................................... 57  
OPERATION:  
Control Panel ................................................................................................ 58  
MAINTENANCE:  
General Maintenance ................................................................................... 59  
Yearly Servicing ............................................................................................ 60  
Glass Replacement...................................................................................... 61  
Blower Replacement .................................................................................... 62  
Electrical Schematic ..................................................................................... 63  
TROUBLESHOOTING ............................................................................................ 64  
PARTS & ACCESSORIES....................................................................................... 66  
WARRANTY ............................................................................................................ 67  
Page 5  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
RATINGS PLATE  
MODEL: REMINGTON  
SERIAL NO.  
SERIAL NO.  
MODEL: REMINGTON  
1445 N. Highway  
Colville, WA 99114  
061-S-14-5  
APPROVED FOR CANADA AND USA TO:  
ANSI Z21.88-1998/CSA2.33-M1998 Vented Gas Fireplace Heaters and applicable sections of UL307b  
Gas Burning Heating Appliances for Mobile Homes and recreational vehicles, CAN/CGA 2.17-M91  
“Gas-Fired Appliances for use at High Altitudes”.  
FAN TYPE VENTED CIRCULATOR  
Blower Electrical Rating:  
115V., 1.5 Amps, 60 Hz, 150 watts  
Thermal Efficiency* 84% NG (blower on)  
86% LP (blower on)  
* With Maximum horizontal length.  
LP  
NG  
Input Rate on “HI” (BTU/Hr)  
Input Rate on “LO” (BTU/Hr)  
Maximum Output (BTU/Hr)  
40,000  
32,000  
34,400  
#56  
40,000  
27,000  
34,400  
#47  
.
Main Burner Orifice Front (DMS)**  
Main Burner Orifice Rear (DMS)**  
Minimum Inlet Pressure (Inches W.C.)  
Maximum Inlet Pressure (Inches W.C.)  
#53  
11"  
#42  
4.5"  
14"  
10"  
7.0"  
3.5"  
Manifold Pressure on “HI” (Inches W.C.)  
**Equipped for installation in Canada for altitudes of 0 - 4500' (1370M); and in USA for alti-  
tudes of 0 - 2000' (610M). In USA for altitudes above 2000' the vent configuration, orifice, or  
combination of both may need to be changed. See Owner’s Manual for information on making  
these changes.  
1999 2000 2001 JAN FEB MAR MAY JUN JUL AUG SEP OCT NOV DEC  
Location: Serial No. portion on lip below control panel. Lower portion behind access door on  
baseplate to right of control panel.  
Page 6  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
STANDARDS/CLEARANCES LABEL  
MODEL: REMINGTON QFP40  
VENTED GAS FIREPLACE HEATER  
NOT FOR USE WITH SOLID FUEL - NOT FOR USE WITH AIR FILTERS  
The “Remington QFP40” is factory equipped for natural gas (NG) and is field convertible to pro-  
pane gas (LP), when equipped with the Conversion Kit #842-4470 available from an Aladdin Hearth  
Products dealer. This appliance uses a millivolt-type control system consisting of a gas control valve/  
regulator, a standing pilot burner assembly, a thermopile, a piezo ignitor, and the ON/OFF switch. THIS  
UNIT DOES NOT REQUIRE 110 VOLT POWER TO OPERATE. All exhaust gases must be vented  
outside the structure of the living area. Combustion air is drawn from outside the living area structure.  
Install fireplace in accordance with all local codes, if any; if none, follow The National Fuel Gas  
Codes ANSI Z223.1-1992 and NFPA 54(88); or Canadian Installation Codes CAN/CGA-B149.  
Manufactured or Mobile Home Installation This appliance is only for use with the type of gas indi-  
cated on the rating plate and may be installed in an aftermarket, permanently located, manufactured (mo-  
bile) home where not prohibited by local codes. Installations must conform with: USA: Manufactured  
Home Construction and Safety Standard, Title 24 CFR, Part 3280. CANADA: CSA Z240.4 and Gas-  
Equipped Recreational Vehicles and Mobile Housing.  
WARNINGS:  
This appliance should be inspected before use and at least annually by a qualified service person. More  
frequent cleaning may be required where excessive lint from material like carpeting and bedding is present.  
The control compartment, the burner compartment and all circulating air passageways of the appliance  
must be kept clean and clear at all times. Due to high temperatures, the appliance should be located out  
of traffic and away from furniture and draperies. This appliance must not be connected to a chimney flue  
servicing a separate solid fuel burning appliance. Children and adults should be alerted to the hazards of  
high surface temperature and should stay away to avoid flesh burns or clothing ignition. Young children  
should be carefully supervised at all times when they are in the same room as the appliance.  
CAUTION: All safety screen or guard components removed for servicing, must be replaced prior to  
operating the appliance. Clothing or other flammable material should not be placed on or near the appli-  
ance. Risk of electrical shock. Switch the household breaker off or remove fuse before servicing unit.  
Use Simpson DURA-VENT direct vent system (Model GS) to vent this appliance to the exterior (direct  
discharge only without duct connection).  
Minimum Clearances to Combustibles  
To Adjacent Wall:  
To Mantel:  
From top of glass edge............................. 30 1/2"  
From glass edge ....................................... 7 3/4"  
From side of Rectangular fascia .............. 3"  
From side of Arched fascia ...................... 3"  
Back to enclosure (from stand-offs) ............. 0"  
Top to enclosure (from stand-offs) ............... 0"  
Sides to enclosure (from stand-offs)............. 0"  
Hearth Extension:  
From top of Rectangular Facia ................ 24"  
From top of Arched Facia ........................ 22 5/8"  
To maximum 1/2" top front facing:  
From top of glass edge............................. 20 1/4"  
From Arched Facia .................................. 12 1/4"  
From Rectangular Facia .......................... 14"  
Flue Vent....................................................... 1"  
* See Owner’s Manual For Additional Mantel  
Clearances and Options  
Does not require hearth extension or  
non-combustible floor beneath appliance.  
Page 7  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
WARNING!  
Improper installation, adjustment, alteration, service or maintenance can cause injury  
or property damage. Refer to this manual for correct installation and operational pro-  
cedures. For assistance or additional information consult a qualified installer, service  
agency, or the gas supplier.  
WARNING!  
Do not operate appliance with the glass front removed, cracked or broken. Replace-  
ment of the glass should be done by a licensed or qualified service person.  
WARNING!  
Operation of this appliance when not connected to a properly installed and maintained  
venting system or tempering with the blocked vent shutoff system can result in carbon  
monoxide (CO) poisoning and possible death.  
Caution and Warning label located on chain behind access door to right of control panel.  
CAUTION: HOT WHILE IN OPERATION. DO NOT TOUCH. KEEP CHILDREN,  
CLOTHING, FURNITURE, GASOLINE AND OTHER LIQUIDS HAVING FLAM-  
MABLE VAPORS AWAY.  
CAUTION: DO NOT OPERATE THE APPLIANCE WITH GLASS REMOVED,  
CRACKED OR BROKEN. REPLACEMENT OF THE GLASS SHOULD BE DONE  
BY A LICENSED OR QUALIFIED SERVICE PERSON.  
FOR USE WITH NATURAL GAS AND PROPANE (LP).  
A CONVERSION KIT, AS SUPPLIED BY THE MANUFACTURER, SHALL BE  
USED TO CONVERT THIS ROOM HEATER TO THE ALTERNATE FUEL.  
WARNING: IMPROPER INSTALLATION ADJUSTMENT, ALTERATION, SERVICE  
OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER  
TO THE OWNER’S INFORMATION MANUAL PROVIDED WITH THIS APPLI-  
ANCE. FORASSISTANCE OR ADDITIONAL INFORMATION CONSULT AQUALI-  
FIED INSTALLER, SERVICE AGENCY OR THE GAS COMPANY.  
Due to high temperatures, the appliance should be located out of traffic and away  
from furniture and draperies. Children and adults should be alerted to the haz-  
ards of high surface temperature and should stay away to avoid burns or cloth-  
ing ignition. Young children should be carefully supervised when they are in the  
same room as the appliance. Clothing or other flammabale material should not  
be placed on or near the appliance. The appliance area must be kept clear and  
free from combustible materials, gasoline and other flammable vapors and liq-  
uids.  
Page 8  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
SAFETY NOTICES  
IF YOU SMELL GAS!  
Do not light any appliance  
Extinguish any open flame  
Do not touch any electrical switch or plug or unplug anything  
Open windows and vacate building  
Call gas supplier from neighbor’s house, if not reached, call fire depart-  
ment  
Installation must be done by a qualified installer  
Strict adherence to the instructions in this manual must be followed. Improper installation will void the  
warranty and safety listing.  
This appliance is manufactured to operate on natural gas (NG). It is field convertible to propane (LP)  
with the manufacturers’ conversion kit. Burning incorrect fuel voids the warranty and safety listing and  
may cause an extreme safety hazard.  
Contact local building officials to obtain a permit and information on installation restrictions or require-  
ments in your locale. It is also important to notify your homeowner’s insurance company of the installa-  
tion of this appliance as well.  
Control compartments, screens, and circulating air passageways of the appliance must be kept clean  
and free of obstructions.  
Do not store or use gasoline or other flammable liquids in the vicinity of the appliance.  
Keep all furniture or other combustible items at least 36" away from the front of the heater.  
If the flame becomes sooty, dark orange in color, or extremely tall, DO NOT operate the appliance.  
Contact your dealer and arrange for servicing immediately.  
DO NOT operate the appliance if it is not operating properly in any manner. Contact your dealer for  
assistance.  
DO NOT operate the appliance if any portion was submerged in water or if any corrosion occurs.  
Do not place clothing or other flammable items on or near the appliance at any time. Due to thermo-  
static control, the possibility exists for the appliance to turn on, igniting any items on or near it.  
Open viewing glass for servicing only.  
Replace any safety screen or guards removed for servicing prior to operating the appliance.  
Operate the appliance in accordance with the instructions contained in this manual.  
If the main burners do not start correctly, turn the gas off at the gas control valve and contact your dealer  
for service.  
This unit is not for use with solid fuel. DO NOT place anything inside the firebox (other than the included  
fiber logs, embers and nuggets, or the optional brick set).  
If the fiber logs become damaged refer to Parts and Accessories page of this manual for replacement.  
Face surfaces can become extremely hot during operation. Instruct your family and guests of this  
danger and supervise young children when they are in the same room as the heater.  
Instruct everyone in the house how to shut the gas off to the appliance and also at the main gas shut-off  
valve. The gas main shut-off valve is usually next to the gas meter or propane tank and requires a  
wrench to shut off.  
Use the built-in piezo igniter to light the appliance. Do not use matches or any other external device.  
DO NOT remove, replace, modify or substitute any part of the appliance unless instructions are given in  
this manual. All other work must be done by a trained technician.  
Allow the appliance to cool before carrying out any maintenance or cleaning.  
The pilot flame must contact the thermopile and thermocouple. If it does not, turn the gas control valve  
to “OFF” and call your Dealer.  
DO NOT throw this manual away. Important operating and maintenance instructions are included.  
Page 9  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
HEATING SPECIFICATIONS  
Natural Gas  
Propane  
BTU Input  
BTU Output on “HI” (with Fan - without Fan)  
Efficiency** (with Fan)  
27,000 - 40,000  
34,400  
84%  
32,000 - 40,000  
34,400  
86%  
**Efficiency rating is the thermal efficiency rating of the product determined under con-  
tinuous operation, and independent of an installed system at maximum horizontal vent-  
ing (30').  
7"  
ZC APPLIANCE DIMENSIONS  
4"  
32 1/32"  
4 1/8"  
1/2" Stand-offs  
(3 per side)  
41"  
45  
29 1/16"  
37 1/8"  
Electrical  
Connection  
Nail Down Plate  
42"  
1"  
Gas Inlet - 1 1/4" above  
base of unit, accessible  
from either side.  
Page 10  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
MINIMUM CABINET DIMENSIONS  
The following minimum cabinet dimensions are the minimal allowances for clearance to  
combustibles, as referenced on page 7 of this manual. See page 21 for additional  
mantel information.  
Maximum mantel depth is  
12"  
Height 56 1/2"  
Minimum  
1/2" trim.  
Width 54 9/16"  
Depth 20 1/2"  
Page 11  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
INSTALLATION TERMINOLOGY  
Simpson-DuraVent  
Venting  
Framing  
Horizontal  
Termination Cap  
Mantel  
Combustible Wall  
(See Clearances, Page 7)  
DuraRock,  
Tile, etc.  
Fascia  
ZC  
Appliance  
Stand-  
offs  
Glass  
Access Door  
Electrical  
line  
Gas line  
Page 12  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
PREPARATION  
Failure to follow all of the required installation procedures may result in  
property damage, bodily injury or even death.  
This appliance must be installed in accordance with all local codes, if any;  
if not, follow ANSI Z223.1-1992 and NFPA 54(88).  
Manufactured Home or Mobile Home installation may occur only after the  
home is site located and must conform to: USA, Manufactured Home Con-  
struction and Safety Standard, Title 24 CFR, Part 3280; Canada, CSA Z240.4  
and Gas-Equipped Recreational Vehicles and Mobile Housing standards.  
The Reminington is manufactured to operate on Natural Gas (NG), it is con-  
vertible to Liquid Propane Gas (LP) when the manufacturer’s conversion  
kit, part #842-4470 is used.  
All exhaust gases must be vented outside the structure of the living-area.  
Combustion air is drawn from outside the living-area structure.  
Notify your insurance company prior to connecting gas to this fireplace.  
Installation requirements diagrammed and explained in this manual are  
grouped into segments for ease of procedure. While these requirements  
must be met fully, the order of installation may be subject to the procedure  
best suited for your specific placement of the fireplace.  
AN OVERVIEW: INSTALLATION TO OPERATION  
1.  
2.  
3.  
4.  
5.  
6.  
Remove door by releasing four spring clips (2 upper and 2 lower). See Pg. 53.  
Remove logset, lava rock, embers and packaging materials from firebox.  
Familiarize yourself with this manual.  
Finalize your installation decisions and requirements.  
Convert to LP gas if applicable to your installation. (Kit not included.) See Pgs. 14-15.  
Set unit in place and install venting per your installation requirements. Secure unit to  
floor using naildown plates.  
7.  
Connect the gas line. See Pg. 46.  
Complete electrical connections. See Pg. 47.  
8.  
9.  
Run thermostat lines to TH & TPTH connectors on valve, if applicable. See Pg. 47.  
Leak test gas line to manual shutoff valve. See Pg. 54.  
10.  
11.  
12.  
13.  
14.  
15.  
16.  
17.  
18.  
Install brick (optional accessory), lava rock, embers and logset. See Pg. 48.  
Turn on manual shutoff valve; leak test. See Pg. 46.  
Light pilot with door off and smell for gas (see Lighting Instructions). See Pg. 55.  
Re-attach door with latches. See Pg. 53.  
Adjust gas control knob to “ON” (again, follow Lighting Instructions).  
Check flames. See Pg. 55.  
Adjust damper position, if applicable. See Pg. 56.  
Attach fascia. NOTE: If using Gold or Brushed Nickel Fascia - Clean thoroughly with  
glass cleaner and non-abrasive towel prior to lighting unit. See Pg. 53.  
Set Thermostat or turn control panel switch to the “On” position. See Pg. 58.  
19.  
Page 13  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
LP CONVERSION INSTRUCTIONS  
Part # 842-4470 is required for this procedure.  
NOTE: If converting this unit to propane, do so at this point of installation.  
WARNING !  
The installation of this conversion kit must only be undertaken by a quali-  
fied and certified gas appliance installer.  
CAUTION: DISCONNECT ANY ELECTRICAL CORDS AND TURN OFF  
GAS SUPPLY TO UNIT BEFORE PROCEEDING.  
Valve Regulator Tower  
1. Turn control knob to the OFF position and shut off the gas supply to the valve.  
2. Using a Torx TH20, or slotted screwdriver, remove the three pressure regulator  
mounting screws (A), pressure regulator tower (B), and diaphragm (C). (You may  
wish to retain these items for converting back to original gas if necessary.)  
3. Insure that the rubber gasket (D) is properly positioned and install the new HI/LO  
pressure regulator assembly to the valve using the new screws (E) supplied with  
the kit. Tighten screws securely. (Reference torque = 25 in/lb)  
4. Install the enclosed identification label (F) to the valve body where it can be seen.  
A
B
E
C
D
F
Page 14  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
CONVERSION INSTRUCTIONS, (CONT.)  
Burner Orifice Replacement  
5. If logset is installed, remove logs and embers at this time.  
6. Use a Phillips screwdriver to remove pilot lighting channel and front log rack.  
7. Remove the two Phillips head screws that secure the front and rear burner pans in place.  
8. Remove the burner pans by sliding to the right and lifting out. (Shutters may need to be  
adjusted ‘closed’ to make this easier).  
9. Slide shutters out of the way. Using a 3/8" wrench or socket, remove the orifice inserts and  
replace with proper orifices for the specified gas. See below.  
10. Reinstall burner pans and adjust shutters to ‘open’ position.  
NOTE: THe right phillips screw holding front and rear burners in place should be left  
slightly loose to allow for expansion.  
CAUTION: The correct orifice placement is critical for proper appliance performance .  
Natural Gas  
#47  
Propane  
#56  
Main Burner Orifice Front (DMS)  
Main Burner Orifice Rear (DMS)  
#42  
#53  
Note: Logs and burners will be reinstalled following pilot orifice replacement.  
Pilot Orifice Replacement:  
13. Lift pilot hood and remove. See Fig. A  
14. Remove existing pilot orifice with a 5/32” allen wrench. See Fig. B  
15. Replace pilot orifice with the correct orifice for your gas type as follows:  
LP = .016  
NG = .025  
FIG. B  
FIG. A  
11.  
12.  
13.  
Replace pilot hood: Ensure that the notches are aligned and snap hood into place.  
Reinstall Log Rack, pilot lighting channel, burners, lava rock and logs.  
Install LP conversion label inside the apliance beneath the firebox, to the left of the control  
panel.  
Page 15  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
MINIMUM FRAMING DIMENSIONS  
The 1/2" stand-offs on the back and sides and 4" stand-offs on the top of the  
fireplace separate the fireplace from the framing members (see page 12,  
Installation Terminology). These stand-offs may contact the framing mem-  
bers but no material may be placed between the stand-offs and the framing.  
Installation requires a level surface capable of supporting the weight of the  
fireplace (240 lbs.) and vent.  
Fireplace must be placed directly on wood or non-combustible surface (not on  
linoleum or carpet).  
HOT WHILE IN OPERATION! Installation location must be out of traffic and  
away from furniture and draperies.  
NOTE: Framing dimensions shown below reflect an 1/4" overage on top  
and 1/8" overage to each side.  
56 1/2"  
45 1/2"  
Route electrical  
line to the right  
rear of fireplace.  
19 5/8"  
43"  
Route Gas Line 6 7/16" behind the framing opening (on either side of can).  
For hardpipe connection, allow 1 1/4" above the base of fireplace.  
Page 16  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
CORNER INSTALLATIONS  
The usual 45º installation uses the minimum framing dimensions shown in the illustration  
below. PLEASE NOTE: All clearances as referenced on page 7 still apply.  
13 13/16"  
12 1/16"  
19 5/8"  
45 3/16"  
43"  
10 7/16"  
Page 17  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
RAISED FIREPLACE  
The fireplace and it’s hearth, if desired, may be placed on a platform designed to support  
the fireplace weight (240lbs.) and venting.  
Hearth  
Raised Platform  
Page 18  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
RAISED FIREPLACE WITH RAISED HEARTH  
Raised Hearth  
Raised Platform  
Page 19  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
HEARTH REQUIREMENTS  
No clearances to combustible flooring are required for installation of the Remington QFP40,  
as referenced in the Clearances to Combustibles on page 7 of this manual.  
NOTE: Ensure the depth of your flooring material does not exceed the 1" height at  
bottom front flange of the ZC Appliance, illustrated below. Clearance of this area is  
necessary in order to allow freedom of movement of the control panel access door when  
installed later.  
Left Side of  
ZC  
Appliance  
Right Side of  
ZC  
Appliance  
Lower front  
edge of ZC  
Appliance  
Flooring  
(tile, wood, carpet)  
must lie beneath this edge.  
1"  
Page 20  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
MANTEL REQUIREMENTS  
COMBUSTIBLE MANTELS  
As referenced on page 7, Clearance to Combustible Materials:  
The allowable height from the top of the glass to the lower edge of a  
maximum mantel depth of 12", is 30 1/2".  
The allowable height from the top of the glass to a combustible trim  
width of 1/2” or less is 20 1/4".  
MANTEL CLEARANCES FROM TOP OF  
GLASS TO LOWER EDGE OF MANTEL  
OR TRIM.  
20 1/4"  
MANTEL CLEARANCES FROM BOTTOM OF ZC  
APPLIANCE TO LOWER EDGE OF MANTEL OR TRIM.  
56 1/2"  
46 1/4"  
Page 21  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
FASCIA DIMENSIONS  
ARCHED  
Part #841-0710 Gold  
Part #841-0750 Brushed Nickel  
Part #841-0720 Black  
40 1/2"  
R53 7/16"  
31"  
32 13/16"  
28 7/8"  
17 1/2"  
7 3/16"  
ACID WASH ALERT!  
An acid wash (muriatic acid) is commonly used to remove excess  
mortar, primarily on brick faces. Prior to installation of the fascia,  
determine if the masonry surrounding your fireplace that has been  
treated with an acid wash has been properly neutralized with an am-  
monia solution. If not, the gold or nickel fascia may develop a perma-  
nent tarnish when the acid evaporates over time. Contact your ma-  
sonry builder if uncertain if your facing has been properly neutral-  
ized.  
Page 22  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
FASCIA DIMENSIONS  
RECTANGULAR  
Part #841-0730 Black  
40 3/4"  
31"  
31 1/2"  
17 1/2"  
7 3/8"  
Page 23  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
FACING REQUIREMENTS  
Durarock or other non-combustible material must extend  
from header to floor and to framing on either side.  
HEADER  
NON-  
COMBUSTIBLE  
FACING  
3" MIN. FOR  
ARCHED or  
RECTANGULAR  
FASCIA  
NOTE: Tile may be tucked beneath the fascia on sides and top, but not on the  
bottom.  
Page 24  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
FACING OVER 1” (25mm) THICK  
Facing material greater than 1" (25mm) thick, such as brick, river rock, etc., will require  
installation around the perimeter of the face. If your unit did not ship with a template for  
this purpose, contact your dealer for an Arched Fascia Template, Part #842-3770.  
Note: Template is 1/4" oversized to allow for fit.  
Template  
Page 25  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
GENERAL VENTING INSTRUCTIONS  
PLEASE NOTE: In order to comply with applicable codes and product warranties, only Simpson  
Dura-Vent venting components may be used.  
DO NOT USE FIELD-FABRICATED VENTING COMPONENTS.  
The Quadra-Fire Remington Fireplace QFP40 is approved to be vented either horizontally, through  
the side wall, or vertically, through the roof. You may vent through a Class A or masonry chimney  
if a Simpson Dura-Vent adapter is used (for USA installations only). Only Simpson Dura-Vent  
components labeled and listed on page 27 may be used.  
This fireplace is a direct vent heater. All combustion air must come directly from the outside of the  
building. The vent pipe for this unit consists of an inner and an outer pipe. The inner pipe carries  
the stove exhaust out of the system, and the outer pipe brings fresh combustion air into the stove.  
A wall thimble is optional when the venting passes through a wall. A support box or firestop is  
required when the venting passes through a ceiling. Roof flashing and a storm collar are required  
when venting passes through the roof. Follow instructions provided with the vent for installation of  
these items.  
IMPORTANT  
Read all these instructions carefully before starting the installation. Failure to follow instructions  
may create a fire or other safety hazard, and will void the warranty. Be sure to follow these  
installation instructions for venting and clearance to combustible requirements, which may vary  
from one installation to another. Do not extend the venting system in excess of the distance  
prescribed in these manufacturer’s installation instructions. This gas appliance must not  
be connected to a chimney flue serving a separate solid-fuel burning appliance.  
INSTALLATION PRECAUTIONS  
The Quadra-Fire Remington QFP40 Fireplace is an engineered product that has been designed  
and tested. The warranty will be voided, and serious fire, health, or other safety hazards may  
result from any of the following actions: Installation of any damaged venting component, unau-  
thorized modification of the venting system, installation of any component part not approved by  
Aladdin Hearth Products, or installation other than as instructed by these instructions. Consult  
your local building codes before beginning this installation.  
WARNING: Always maintain the required clearances (air space) to nearby combustibles to avoid  
creating a fire hazard. Do not fill air space with insulation. Minimum clearance between vent pipes  
and combustible surfaces is 2" (50mm). Be sure to check the vent termination clearance require-  
ments from decks, windows, soffits, gas regulators, air supply inlets and public walkways, as  
specified on page 31 of these installation instructions and local building codes.  
The gas fireplace and vent system must be vented directly to the outside of the building,  
and never be attached to a chimney serving a separate solid fuel or gas-burning appliance. This  
direct vent gas fireplace must use its own separate vent system. Common vent systems are  
prohibited.  
SAFETY PRECAUTIONS FOR THE INSTALLER  
Wear gloves and safety glasses for protection when installing this stove. Exercise extreme cau-  
tion when using ladders or on rooftops around power lines. Be aware of electrical wiring locations  
in walls and ceilings.  
Page 26  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
SIMPSON DURA-VENT PARTS LIST  
Simpson Dura-Vent offers a complete line of component parts for installation in both horizontal  
and vertical applications. Many items are offered in decorative black, as well as a galvanized  
finish. The galvanized pipe and fittings are used for concealed locations such as attics, or  
spaces where corrosion is a factor, such as above the roofline. Decorative brass and chrome  
trim kits are available for both wall thimbles and ceiling support boxes. Snorkel terminations are  
available for applications which may require a vertical rise on the building exterior. The follow-  
ing components have been approved for use with the Quadra-Fire Remington QFP40 Fire-  
place.  
705C Flashing (masonry chimney)  
902  
902B 48” Pipe Length, Black  
903 36” Pipe Length  
903B 36” Pipe Length, Black  
904 24” Pipe Length  
904B 24” Pipe Length, Black  
906 12” Pipe Length  
48” Pipe Length  
906B 12” Pipe Length, Black  
907B 9” Pipe Length, Black  
908B 6” Pipe Length, Black  
909B Retro Connector  
911B 11” - 14 5/8” Pipe, Adjustable, Black  
940  
941  
943  
Round Support Box/Wall Thimble  
Cathedral Ceiling Support Box  
Flashing, 0/12 to 6/12 Roof Pitch  
943S Flashing, 7/12 to 12/12 Roof Pitch  
945 45° Elbow  
945B 45° Elbow, Black  
950  
953  
963  
981  
982  
985  
Vinyl Siding Standoff  
Storm Collar  
Ceiling Firestop  
Snorkel Termination (36”)  
Snorkel Termination (14”)  
High Wind Horizontal Termination Cap  
985K Top Adapter  
986K Top Adapter  
987K Top Adapter  
988  
990  
Wall Strap  
90° Elbow  
990B 90° Elbow, Black  
991  
High Wind Vertical Termination Cap  
The following high wind horizontal termination cap may be ob-  
tained from your local dealer:  
HHW2 Aladdin High Wind Horizontal Termination Cap  
Page 27  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
VENTING INSTALLATION OPTIONS & GUIDELINES  
There are four types of direct vent system installations approved for use with the REMINGTON  
QFP40. It is very important to maintain a balance between the combustion air intake and the flue  
gas exhaust venting system. The types of installation are:  
Horizontal Termination (Figure 1)  
Into a Class A Metal Chimney (Figure 3)*  
*USA installations only  
Vertical Termination (Figure 2)  
Into a Masonry Chimney (Figure 4)*  
Note: Certain limitations as to vent and vertical termination configuration apply, and  
must be strictly adhered to. Read this manual carefully.  
When planning your installation, it will be necessary to select the proper length of vent pipe for  
your particular requirements. The vent graph on page 32 will show the relationship between vertical  
and horizontal side wall venting, and will help you to determine the various vent lengths permitted.  
It is also important to note the wall thickness. Select the amount of vertical rise desired for “vertical-  
to-horizontal” type installations. To determine the length of your pipe required for vertical  
installations, measure the distance from the application flue outlet to the ceiling, the ceiling  
thickness, the vertical rise in an attic or second story, and allow for sufficient vent height above the  
roofline. For two-story applications, fire stops are required at each floor level. If an offset is  
needed in the attic, additional pipe and elbows will be required.  
When installing this appliance into an existing masonry chimney, it is important to carefully measure  
the length of flex needed to reach from the appliance outlet to the termination cap. If the flex  
length is too short, a flex coupler will be needed to attach an additional length of flex liner to make  
up the difference. If the flex length is too long, the liner could sag below the appliance outlet,  
which could result in a potential fire hazard.  
A masonry chimney or a factory-built chimney must be the required height above the roof  
and any other nearby obstructions. The chimney must be at least three feet higher than  
the highest point where it passes through the roof and at least two feet higher than the  
highest part of the roof or structure that is within ten feet of the chimney, measured  
horizontally. See 2-10-3 diagram below. These are safety requirements and are not  
meant to assure proper flue draft.  
3'  
Minimum  
2'  
Minimum  
10'  
2-10-3 VERTICAL TERMINATION RULE  
Page 28  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
TERMINATION CAP REQUIREMENTS:  
ON HORIZONTAL TERMINATIONS USE ONLY DURAVENT PART  
# 985, OR ALADDIN HEARTH PRODUCTS PART #HHW2  
VERTICAL TERMINATIONS USE ONLY DURAVENT PART #991.  
FIG. 1 HORIZONTAL TERMINATION  
Pipe Length  
Horizontal  
Termination  
Cap Use  
ONLY  
90° Elbow  
#985 or  
#HHW2  
Wall Thimble/Firestop  
DuraVent #991  
Storm Collar  
Flashing  
Firestop  
Ceiling Support  
Pipe Lengths  
FIG. 2 VERTICAL  
TERMINATION  
Page 29  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
VENTING INSTALLATION, CONT.  
FIG. 3 INSTALLATION INTO A CLASS A METAL CHIMNEY  
(USA ONLY)  
Dura Vent #991  
ONLY High Wind  
Termination Cap  
Top Adapter  
Existing Metal  
Chimney System  
4" Flex Pipe  
Retro Connector  
Direct Vent Pipe  
Page 30  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
VENTING INSTALLATION, CONT.  
FIG. 4 INSTALLATION INTO A MASONRY CHIMNEY  
(USA ONLY)  
DuraVent #991 High  
Wind Termination Cap  
ONLY  
Top Adapter  
Flashing  
4" Flex Liner  
Retro  
Connector  
Direct Vent  
Pipe  
Page 31  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
HOW TO USE VENT GRAPH  
1. Measure the distance from the top of stove to the center of the 90° elbow. On the  
graph below, draw a horizontal line from that measurement on the vertical axis across  
until it intersects with the slanted line.  
2. From the point of this intersection, draw a vertical line to the bottom of the graph.  
3. The point at which this line meets the bottom line of the graph is the maximum length  
of the horizontal run.  
Example 1: If the vertical dimension from the top of the stove to the center of the 90°  
elbow is 7' (2.13m), the horizontal run to the outer wall flange must not  
exceed 9' 9" (2.97m).  
Example 2: If the vertical dimension from the top of the stove is 21’ (6.4m), the hori-  
zontal run to the outer wall flange must not exceed 7’ 3" (2.21m).  
Note: The maximum horizontal vent run is 15' (4.57m) when the vertical vent rise is 10'  
(3.05m).  
The minimum horizontal vent run is 12" (305mm).  
Minimum wall thickness is 4" (102mm). Maximum wall thickness is 20" (508mm).  
• Vent damper may need to be adjusted if your installation falls in the shaded area  
shown in graph.  
30'  
28'  
26'  
24'  
22'  
Ex. 2  
20'  
18'  
VERTICAL DISTANCE  
FROM APPLIANCE TOP  
TO THE 90° ELBOW  
16'  
14'  
12'  
10'  
8'  
EX. 1  
6'  
4'  
2'  
0'  
11" 2'  
(MIN)  
4'  
6'  
8'  
10'  
12'  
14' 15'  
(MAX)  
TOTAL HORIZONTAL RUN TO  
OUTSIDE OF EXTERIOR WALL  
(EXCLUDING ELBOWS)  
Page 32  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
HORIZONTAL TERMINATION REQUIREMENTS  
A. *12” (30cm) minimum: Clearance above grade, veranda, porch, deck, or balcony.  
B. *12” (30cm) minimum: Clearance to window or door that may be opened.  
C. 12” (30cm) minimum: Clearance to permanently closed window (recommended to prevent  
condensation on window.  
D. 18” (46cm) minimum: Vertical clearance to ventilated soffit located above the terminal  
within a horizontal distance of 2’ (60cm) from the centerline of the terminal.  
E. 12” (30)cm) minimum: Clearance to unventilated soffit.  
F. 6 (15cm): Clearance to outside corner.  
G. 9 (23cm): Clearance to inside corner.  
*Not to be installed above a meter/regulator (gas or electrical) assembly within 3’ (90cm)  
horizontally from the centerline of the meter/regulator.  
H. *6’ (1.8m) minimum: Clearance to service regulator vent outlet.  
I. *12” (30cm) minimum: Clearance to nonmechanical air supply inlet to building or the  
combustion air inlet to any other appliance.  
J. *6’ (1.8m) minimum: Clearance to a mechanical air supply air inlet.  
K. *+7’ (2.1m) minimum: Clearance above paved sidewalk or a paved driveway located on  
public property.  
L. *#12” (30 cm) minimum: Clearance under veranda, porch, deck, or balcony.  
M. 6” (15 cm) minimum: Clearance to adjacent building or deck.  
N. 6” (15 cm) minimum: Clearance to nearby building  
+A vent shall not terminate directly above a sidewalk or paved driveway which is located between  
two single-family dwellings and serves both dwellings.*  
#Only permitted if veranda, porch, deck, or balcony, is fully open on a minimum of two sides  
beneath the floor.*  
*As specified in CGA B149 Installation Codes  
Note: Local Codes or regulations may require different clearances.  
N
V
H
Fixed  
Openable  
V
Closed  
I
B
F
G
C
M
A
K
V
A
V
J
A
= vent terminal  
V
A
= air supply inlet  
Page 33  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
HORIZONTAL INSTALLATION  
NOTE:  
Horizontal sections require a 1/4" (6mm) rise for every 12" (305mm) of horizontal  
travel.  
Exterior Vent Diameter = 6 5/8" (177mm); Inner Vent Diameter = 4" (101mm)  
Horizontal sections require noncombustible support every 3' (914mm) , e.g. plumbing  
tape.  
Step 1. Determine the desired location of the fireplace. Check to ensure that wall studs  
or roof rafters are not in the way when the venting system is attached. If this is  
the case, you may want to adjust the location of the stove.  
Step 2. Simpson Dura-Vent pipe is designed with special twist-lock connections. To  
connect the venting system to the stove flue outlet, a twist-lock adapter is built  
into the stove at the factory. Remember to include wall thickness in minimum  
clearances when figuring the measurements for your installation needs.  
Note: Twist-lock procedure: Four indentations, located on the female ends of pipes and  
fittings, are designed to slide straight onto the male ends of adjacent pipes and fittings by  
orienting the four pipe indentations so they match and slide into the four entry slots on  
the male ends, see Fig. 5 below. Push the pipe sections completely together, then twist-  
lock one section clockwise approximately one-quarter turn, until the two sections are  
fully locked. The female locking lugs will not be visible from the outside, on the pipe or  
fittings. They may be located by examining the inside of the female ends.  
FIG. 5  
FEMALE LOCKING LUGS  
MALE LOCKING LUGS  
NOTE: Horizontal runs of vent must be supported every 3' (914mm). Wall straps are available  
for this purpose.  
Page 34  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
Step 3. With the adapter, any vertical pipe required for your installation, and the 90°  
elbow attached to the flue outlet, measure the distance from the base of the ZC  
appliance to the center of the 90° elbow, adding 1/4" rise for every 1' of horizontal  
venting, as referenced in Note 1, below. Measure this height at the correct wall  
location for your installation, maintaining minimum clearance to combustibles,  
and mark the wall for a 10" x 10" (254mm x 254mm) square hole. The center of  
the square hole should line up with the centerline of the horizontal pipe, as  
shown in Figure 6A. Cut and frame the hole in the exterior wall where the vent  
will be terminated, Figure 6B. If the wall being penetrated is constructed of  
noncombustible material, i.e. masonry block or concrete, a 7" (178mm) diameter  
hole is acceptable.  
Wall  
FIG. 6A  
Center  
of Hole  
10' x 10'  
Opening  
Center  
Line  
10"  
Center Line  
10"  
49"  
FIG. 6B  
NOTE:  
(1)  
Installation requires a minimum of 1' (305mm) horizontal run of vent with a ¼" (6mm)  
rise run towards the termination. Each 1' (305mm) of horizontal venting must include a  
1/4" rise. Never allow the vent to run downward. This could cause high temperatures  
and may present the possibility of a fire.  
(2)  
(3)  
The location of the horizontal vent termination on an exterior wall must meet all local and  
national building codes, and must not be easily blocked or obstructed, see page 33.  
For installations requiring a vertical rise on the exterior of the building, 14" (356mm) and  
36" (914mm) tall snorkel terminations are available. Follow the same installation  
procedures as used for standard horizontal terminations. If the snorkel termination must  
be installed below grade (i.e. basement application), proper drainage must be provided  
to prevent water from entering the snorkel termination. Do not backfill around snorkel  
termination.  
Page 35  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
HORIZONTAL INSTALLATION (CONT.)  
Step 4. Position the horizontal vent termination in the center of the 10" (254mm) square hole, run a  
bead of non-hardening mastic around its outside edges, so as to make a seal between it and  
the wall, attach termination cap to the exterior wall with the four wood screws provided. The  
arrow on the vent cap should be pointing up (Figure 7) . Insure that proper clearances to  
combustible materials are maintained.  
WOOD SCREW  
FIG. 7  
PART #985 OR  
HHW2  
HOT  
NOTE:  
(1)  
The four wood screws provided should be replaced with appropriate fasteners for stucco,  
brick, concrete, or other types of sidings.  
(2)  
If you are using Simpson DuraVent termination cap # 985 on a building with vinyl siding, a  
vinyl siding standoff (Simpson Dura-Vent Part #950), should be installed between the vent  
cap and the exterior wall (Figure 8). Attach the vinyl siding standoff to the horizontal vent  
termination. The vinyl siding standoff prevents excessive heat from possibly melting the vinyl  
siding material. Vent terminal shall not be recessed into a wall or siding. Remove siding  
from beneath area of standoff.  
VINYL SIDING  
APPLY SEALANT  
ALL FOUR SIDES  
FIG. 8  
SCREWS  
BOLT HORIZONTAL TOP  
TO VINYL STANDOFF  
VINYL SIDING STANDOFF w/  
SIDING BENEATH REMOVED  
Page 36  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
HORIZONTAL INSTALLATION (CONT.)  
Step 5. Slide the stove and vent assembly (see Fig. 9 below) towards the wall, carefully  
inserting the vent pipe into the vent cap assembly. It is important that the vent  
pipe extend into the vent cap sufficient distance so as to result in a minimum  
pipe overlap of 1¼" (32mm). Secure the connection between the vent pipe and  
the vent cap by attaching the two sheet metal strips extending from the vent cap  
assembly into the outer wall of the vent pipe. Use the two sheet metal screws  
provided to connect the strips to the pipe section. (Figure 9).  
Note: The attachment from the vent pipe to the vent cap must be siliconed. Venting  
terminals shall not be recessed into a wall or siding.  
FIG. 9  
FOLD STRAP HERE  
SHEET METAL SCREW  
WALL THIMBLE/CEILING  
FIRESTOP AS REQUIRED BY  
LOCAL JURISDICTION.  
STRAP  
Page 37  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
VERTICAL INSTALLATION INSTRUCTIONS  
USING GS SERIES PIPE  
Step 1. Check the installation instructions for required 1" clearances (air space) to com-  
bustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, or  
other nearby combustible surfaces. See page 40, Fig. 16. Do not pack air  
space with insulation. Check the instructions below for maximum vertical rise of  
the venting system, and any maximum horizontal offset limitations. All offsets  
must fall within the set parameters of the vent graph located on page 31.  
NOTE: Maximum vertical rise allowable is 30' (900mm) (Figure 10).  
FIG. 10  
30' MAX  
FIG. 11  
NOTE: Maximum number of 45° elbows permitted for a vertical installation is eight,  
provided their installation does not decrease maximum vertical rise (as specifiedby  
Vent graph, on page 31).  
NOTE: Maximum number of 90° elbows permitted for a vertical installation is four, pro-  
vided the termination falls within the shaded area shown in vent graph on page  
32. See also Figure 12 below. ADDITIONAL RESTRICTION: This installa-  
tion may not have two horizontal sections connected by 90° elbows.  
FIG. 12  
2'  
1'  
2'  
1'  
1'  
Step 2. Set the gas stove in its desired location. Drop a plumb bob down from the ceiling  
to the position of the stove flue exit, and mark the location where the vent will  
penetrate the ceiling. Drill a small hole at this point. Next, drop a plumb bob from  
the roof to the hole previously drilled in the ceiling, and mark the spot where the  
vent will penetrate the roof. Determine if ceiling joists, roof rafters, or other fram-  
ing will obstruct the venting system. You may wish to relocate the stove, or to  
offset, as shown in Figure 11, to avoid cutting loadbearing members.  
Page 38  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
VERTICAL INSTALLATION INSTRUCTIONS  
Step 3. To install the round support box/wall thimble in a flat ceiling, cut a 10" (254mm)  
square hole in the ceiling, centered on the hole drilled in Step 2. Frame the hole  
CeilingJoists  
as shown in Figure 13.  
Framing  
FIG. 13  
1 - 1/2" Long  
WoodScrews  
Step 4. Assemble the desired lengths of GS pipe and elbows necessary to reach from  
the stove up through the round support box. Ensure that all pipe and elbow  
connections are in their fully twist-locked position. Be sure to seal the outer pipe  
with appropriate sealant (high temperature silicone).  
Step 5. Cut a hole in the roof centered on the small drill hole placed in the roof in Step 2.  
The hole should be of sufficient size to meet the minimum requirements for  
clearance to combustibles, as specified. Continue to assemble lengths of pipe  
and elbows necessary to reach from the ceiling support box up through the roof  
line. Galvanized pipe and elbows may be utilized in the attic, as well as above  
the roofline. The galvanized finish is desirable above the roofline, due to its higher  
corrosion resistance.  
NOTE:  
(1)  
If an offset is necessary in the attic to avoid obstructions, it is important to sup-  
port the vent pipe every 3' (914mm) to avoid excessive stress on the elbows, and  
possible separation. Wall straps are available for this purpose (page 38, Figure  
11).  
(2)  
Whenever possible, use 45° elbows, instead of 90° elbows. The 45° elbow of-  
fers less restriction to the flow of flue gases and intake air.  
Step 6. Slip the flashing over the pipe section(s) protruding through the roof. Secure the  
base of the flashing to the roof with roofing nails. Insure the roofing material  
overlaps the top edge of the flashing as shown in Figure 14. Verify that the  
chimney is the required height above the roof. See “2-10-3 Vertical Termination  
Rule” on page 28 of this manual  
SHINGLES OVERLAP  
TOP EDGE OF  
FLASHING  
FIG. 14  
Page 39  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
VERTICAL INSTALLATION INSTRUCTIONS (CONT.)  
USING GS SERIES PIPE (CONT.)  
Step 7. Continue to assemble pipe sections until the height of the vent cap (H) (Figure  
15) meets the minimum code requirements described in code requirements as  
outlined in the current CAN/CGA-Bl49 Installation Codes (in Canada), the Na-  
tional Fuel Gas Code NFPA 54/ANSI Z223.1 (in USA), or local codes. Note that  
for steep roof pitches, the vent height must be increased. In high wind conditions,  
nearby trees adjoining rooflines, steep pitched roofs, and other similar factors  
can result in poor draft, or down drafting. In these cases increasing the vent  
height may solve this problem.  
Step 8. Twist-lock the vent cap and seal.  
NOTE:  
(1)  
For multi-story vertical installations, a ceiling firestop (SDV part #963) is required  
at the second floor, and any subsequent floors (Figure 16). The opening should  
be framed to 10" x 10" (254mm x 254mm) inside dimensions, in the same man-  
ner as shown in Figure 13.  
(2)  
Any occupied areas above the first floor, including closets and storage spaces,  
which the vertical vent passed through must be enclosed. The enclosure may be  
framed and sheetrocked with standard construction materials; however, refer to  
these installation instructions for the minimum allowable clearance between the  
outside of the vent pipe and the combustible surfaces of the enclosure. Do not fill  
any of the required air space with insulation.  
MINIMUM 1"  
CLEARANCE  
FIG. 16  
MINIMUM 1"  
FIG. 15  
CLEARANCE  
MINIMUM 1"  
CLEARANCE  
Page 40  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
VERTICAL INSTALLATION INSTRUCTIONS (CONT.)  
CATHEDRAL CEILING INSTALLATION  
Step 1. Follow installation Steps 1 and 2 under vertical termination section.  
Step 2. Using the plumb-bob, mark the centerline of the venting system on the ceiling,  
and drill a small hole through the ceiling and roof at this point. From the roof,  
locate the drill hole and mark the outline of the cathedral ceiling support box.  
Step 3. Remove shingles or other roof covering as necessary to cut the rectangular  
hole for the support box. Cut the hole 1/8" (3mm) larger than the support box  
outline.  
Step 4. Lower the support box through the hole in the roof until the bottom of the box  
protrudes at least 2" (51mm) below the ceiling (Figure 17). Align the support box  
both vertically and horizontally with a level. Temporarily tack the support box in  
place through the inside walls and into the roof sheathing.  
FIG. 17  
Step 5. Using tin snips, cut the support box from the top corners down to the roofline,  
and fold the resulting flaps over the roof sheathing (Figure 18). Before nailing it  
to the roof, run a bead of non-hardening mastic around the top edges of the  
support box to make a seal between it and the roof. Clean out any combustible  
material from inside the support box.  
FIG. 18  
Step 6. Complete the cathedral ceiling installation by following the same procedures  
outlines in steps 4 through 8 for vertical terminations.  
Page 41  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
VERTICAL INSTALLATION INSTRUCTIONS (CONT.)  
INSTALLATION INTO A CLASS A METAL CHIMNEY (USA ONLY)  
NOTE: Have the existing installation inspected by a qualified chimney sweep or profes-  
sional installer prior to converting to direct vent. The existing chimney system  
must be in serviceable condition and functionally sound and clean.  
Step 1. Remove existing chimney cap.  
Step 2. Measure the distance from the top of the chimney to the bottom of the ceiling  
support box, add 3" (76mm) to this measurement, and cut a section of 4" (102mm)  
flex pipe to that length (the flex should be extended to its nominal length).  
Step 3. Connect the end of the flex pipe section to the underside of the top adapter (SDV  
#985K, 986K or 987K), using three sheet metal screws (Figure 19).  
Step 4. Pass the flex pipe down through the center of the chimney system, and center  
the top adapter on the top of the chimney pipe. Drill four 1/8" (3.3mm) diameter  
holes through the top adapter, and into the chimney top. Ensure that you are  
drilling into the metal on the chimney. Twist lock the high wind termination cap  
(SDV #991) onto the top adapter (Figures 20 and 21).  
Step 5. Pull the flex pipe down through the ceiling support box, until it protrudes approxi-  
mately 3" (76mm). Connect the flex pipe to the retro connector (SDV #909B),  
and attach with sheet metal screws.  
Step 6. Push the flex pipe back up into the ceiling support box, center the retro connec-  
tor, and attach it to the support box with sheet metal screws.  
Step 7. The connection between the appliance and the retro connector may be com-  
pleted with sections of direct vent pipe.  
FIG. 19  
FIG. 20  
FIG. 21  
TOP  
ADAPTER  
TERMINATION  
CAP  
SHEET  
METAL  
SCREWS  
FLEX  
PIPE  
DRILL (4) 1/8”  
DIAMETER  
HOLES  
SHEET  
METAL  
SCREWS  
Page 42  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
VERTICAL INSTALLATION INSTRUCTIONS (CONT.)  
INSTALLATION INTO AN EXISTING MASONRY CHIMNEY (USA ONLY)  
Step 1. Before cutting any holes, assemble the desired sections of direct vent pipe to  
determine the center of the masonry penetration.  
FIG. 22  
Step 2. Once the center point of the penetra-  
tion has been determined, cut a 6"  
(152mm) diameter hole in the masonry.  
If the hole is too large, the retro connec-  
tor might not mount properly; if the hole  
is too small, the appliance might starve  
for intake air. If there is a frame wall in  
front of the masonry wall, cut and frame  
a 10" (254mm) square opening in the  
wall (centered around the 6" [152mm]  
masonry opening). If there is sheet rock  
only (no studs) in front of the masonry  
the 10" (254mm) opening is still needed,  
but does not need to be framed. This  
allows the retro connector to mount di-  
rectly on the masonry and provide the  
correct clearances to combustibles (see  
Figure 22).  
Step 3. Secure the flashing (SDV #705C) to the  
top of the masonry chimney using a  
bead of non-hardening sealant-adhe-  
sive. If the flashing is larger than the top  
of the chimney, cut and fold flashing as  
needed to fit chimney (Figure 23).  
Step 4. To determine the length of flex needed,  
measure from 3" (76mm) above the top  
of the flashing down to the level of the  
opening. Add the distance from the cen-  
ter of the chimney out through the wall.  
Cut a piece of 4" (102mm) flex to this  
length (extended to its nominal length).  
Be sure to leave 2"-3" (51mm-76mm) of  
flex above the existing chimney to allow  
for connection to the termination kit.  
FIG. 23  
Page 43  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
VERTICAL INSTALLATION INSTRUCTIONS (CONT.)  
Step 5. Connect the flex liner to the top adapter  
using three sheet metal screws (see Fig-  
ure 19, page 42).  
FIG. 24  
Step 6. Feed the flex liner through the flashing  
into the chimney. Carefully feed the flex  
liner down the chimney to the bottom and  
out the opening in the masonry wall,  
forming an angle to line up the flex liner  
with the vent opening on the appliance.  
WARNING: Do not let the flex liner  
sag below the level at which it will  
connect to the appliance or connec-  
tor. This could allow hot gas to be-  
come trapped and potentially become  
a fire hazard. The flex liner path  
should always be sloped up toward  
the termination cap.  
FIG. 25  
Step 7. If additional lengths of flex liner are  
needed to span the chimney height, use  
a flex coupler to connect the pieces of  
flex liner together. Connect the flex to  
the coupler by using four sheet metal  
screws for each side (Figure 24).  
Step 8. Secure the top adapter to the flashing.  
Use three sheet metal screws through  
the side of the top adapter into the flange  
on the flashing (Figure 25). Twist lock  
the high wind termination cap (SDV  
#991) on to the top adapter.  
Page 44  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
VERTICAL INSTALLATION INSTRUCTIONS (CONT.)  
Step 9. Attach the flex to the retro connector.  
Use three sheet metal screws to attach  
the flex liner to the connector (Figure  
26). Mount the retro connector to the ma-  
sonry wall using masonry bolts. Redrill  
larger holes on connector as needed.  
Be careful to ensure that the connector  
is centered in the opening and the  
mounting holes line up with the masonry  
wall.  
FIG. 26  
Step 10.  
Slide wall thimble cover (SDV  
#940) over retro connector and secure  
with masonry bolts (Figure 27). If you  
have a framed wall in front of the ma-  
sonry, use wood screws to mount wall  
thimble cover to framed wall, over retro  
connector and 10" (254mm) square  
framed opening (Figure 22). If needed,  
add a section of direct vent pipe to the  
retro connector in order to extend  
through the opening in the wall thimble  
cover.  
FIG. 27  
Step 11.  
The connection between the appli-  
ance and the retro connector may be  
completed with sections of direct vent  
pipe.  
WARNING: If any other appliances have been previously attached to  
this masonary flue or an open fireplace, etc., all openings into flue  
should be sealed properly. it is very important that there is only one  
appliance on a vent system and that there are no air leaks into the  
masonry chimney itself other than the vent appliance venting.  
Page 45  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
GAS LINE REQUIREMENTS  
The gas line must be installed in accordance with all local codes, if any; if not, follow  
ANSI 223.1 and the requirements listed below. Ensure that a 1 1/4" allowance from  
base of unit is made for hard pipe installation, see page 16, Minimum Framing Dimen-  
sions.  
The fireplace and gas control valve must be disconnected from the gas supply piping  
during any pressure testing of that system at test pressures in excess of 1/2 psig. For  
pressures under 1/2 psig, isolate the gas supply piping by closing the manual shutoff  
valve.  
The appliance must be isolated from the gas supply piping system by closing its equip-  
ment shutoff valve during any pressure testing of the gas supply piping system at test  
pressures equal to or less than 1/2 psi (3.5 kPa).  
Leak test all gas line joints and the gas control valve prior to and after starting the  
fireplace.  
Fuel  
This unit is manufactured for use with natural gas. To convert to LP gas, Part  
#842-4470, LP Conversion Kit, is required and available through your dealer  
Gas Line Connection  
A manual shutoff valve is installed in the unit. To access the shutoff valve, open the  
control panel access door and locate the red swing handle to the right of the  
control panel beneath the firebox.  
Gas Inlet Pressure  
All other gas appliances in the household must be turned “ON” to  
check Inlet Pressure, and;  
Inlet pressure can only be checked with fireplace burner “ON”.  
Input Pressure  
Standard  
Minimum  
4.5"W.C.  
11"W.C.  
Maximum  
7"W.C.  
Natural Gas  
Propane  
7" W.C.  
11" W.C.  
14"W.C.  
If the pressure is not sufficient, ensure: 1) the piping used is large enough, 2)  
the supply regulator is adequately adjusted, and 3) that the total gas load for  
the residence does not exceed the amount supplied.  
The supply regulator (the regulator that attaches directly to the residence inlet  
or to the propane tank) should supply gas at the suggested input pressure  
listed above. Contact the local gas supplier if the regulator is at an improper  
pressure.  
Page 46  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
ELECTRICAL CONNECTION  
Make sure the household breaker is shut off prior to working on any electrical  
lines.  
This appliance, when installed, must be electrically grounded in acordance  
with local codes or, in the absence of local codes, with the National Electrical  
Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.  
The electrical line must be at least 14 gauge and supply 120 Volts at 60 Hz (2  
Amps)  
COPPER  
WHITE  
WIRE  
BLACK  
Remove the junction box cover at the right rear corner of the fireplace near  
the base.  
Feed the electrical line through the strain relief (use insulated Romex type  
wire).  
Remove the wires from the junction box. Expose approximately 1/2” of metal  
wire from each line of the electrical line. Use wire nuts to secure the wires  
together. Connect copper ground wire to grounding screw as shown in fig-  
ure above, connect the white wire to the common wire (usually white), and  
the black wire to the hot wire (usually black).  
Push the wire connections into the junction box. Replace the cover plate.  
Tighten the strain relief onto the outer insulation of the electrical line to se-  
cure.  
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring er-  
rors can cause improper and dangerous operation. Verify proper opera-  
tion after servicing.  
OPTIONAL THERMOSTAT INSTALLATION  
A remote control or wall switch may be wired to the TH and TPTH thermostat terminals.  
See Parts and Accessories on page 66 to order through your dealer.  
Page 47  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
BRICK INSTALLATION  
Installation of the brick set should be made prior to the logset, nugget and lava  
rock installation.  
Optional Accessory Part # 841-0740  
Kits includes: 1 Rear brick, 1 Right Brick, 1 Left Brick and 2 Brick clips.  
NOTE: BRICK IS FRAGILE. HANDLE WITH CARE.  
1. Place rear brick behind log rack against rear wall of firebox as shown in Fig. 1.  
FIG. 1  
.
2. Remove mounting screws from the upper right and left sides of firebox, see Figure  
4 for location of mounting screw, and gently slide the right and left side brick panels  
into place as shown in Figures 2 and 3.  
FIG. 2  
Page 48  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
BRICK INSTALLATION, CONT.  
FIG. 3  
3. Attach brick retaining clips to right and left sides, using mounting screws removed  
in Step 2. (Fig. 4).  
Mounting  
screw & clip  
placement.  
FIG. 4  
Page 49  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
LOGSET AND NUGGET INSTALLATION  
NOTE: If you plan to install the optional brick set, do so prior to installing the logset,  
nuggets and lava rock. Continue at this point AFTER installing the optional brick  
set.  
LOG IDENTIFICATION  
Rear Log  
Right Twig  
Left Twig  
Rear Log  
Lower Front  
Left Twig  
Lower Center  
Front Twig  
Lower Right  
Front Twig  
1. Install complete bag of lavarock in indicated gray area ONLY shown in Figs. 1 & 2.  
2. Install nuggets. Avoid covering burner secondary air channels, nuggets should be distrib-  
uted evenly; one layer on front and back shelves. CAUTION! Avoid nugget buildup at  
pilot transfer channel. See Fig.  
FIG. 1 FIREBOX FLOOR  
LAVA  
ROCK  
SECONDARY  
AIR GAPS  
NUGGETS  
PILOT CHANNEL  
LAVA  
ROCK  
LAVA ROCK  
Page 50  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
LOGSET AND NUGGET INSTALLATION, CONT.  
FIG. 2 NUGGET PLACEMENT  
3. Set Rear Log in rear log bracket with pegs in  
upright position. Fig. 3.  
4. Set the notch in the Front Log over the pilot  
transfer channel and center log side-to-side  
on the grate with pegs in upright position.  
Fig. 4.  
FIG. 3 REAR LOG  
FIG. 4 REAR & FRONT LOGS  
Page 51  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
LOGSET AND NUGGET INSTALLATION, CONT.  
5. Place Left Twig onto pegs on top of Rear  
and Front Logs. Fig. 5.  
FIG. 7 LOWER FRONT LEFT TWIG  
6. Place Right Twig onto pegs on top of  
Rear and Front Logs. Fig. 6.  
7. Place Lower Left Front Twig in front of  
stops on log rack. Fig. 7.  
8. Place Lower Front Right Twig in front of  
stops on log rack. Fig. 8.  
9. Place Lower Center Front Twig at cen-  
ter of log rack. Fig. 9.  
FIG. 5 LEFT TWIG  
FIG. 8 LOWER FRONT RIGHT TWIG  
FIG. 9 LOWER FRONT CENTER TWIG  
FIG. 6 RIGHT TWIG  
Page 52  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
INSTALLING GLASS  
The glass assembly has a narrow metal edge at top of the frame, and wide metal edge at  
bottom of the frame. To install the glass assembly, lift and set the bottom T-bar extensions onto  
the bottom alignment pins located at the edge of firebox--refer to diagram below. With the  
bottom edge of glass assembly resting on the bottom alignment pins, lift up and onto the top  
alignment pins. Secure the assembly to zc appliance with the spring latches, two on top and two  
at bottom.  
Narrow Edge (TOP)  
Spring Latches.  
(2 upper & 2 lower)  
Flanges for fas-  
cia attachment,  
T-bar extension  
of Flange.  
Alignment pins.  
(2 per side)  
and T-bar exten-  
sions for setting  
glass onto align-  
ment pins.  
(2 per side)  
Wide Edge (BOTTOM)  
WARNING: Use care in handling of glass assembly, do not strike or slam as this  
could cause breakage.  
INSTALLING FASCIA  
All arched and rectangular fascia attach to four flanges located two to each side of the  
glass frame. Insert and finger start bolts tightening with the 5/32" Allen wrench supplied with  
unit.  
Insert bolts through  
these holes and into  
Flanges shown in  
picture above. (2 per  
side)  
Page 53  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
LEAK TEST  
1. Turn on gas to the fireplace.  
2. Turn on gas at the manual shutoff valve.  
3. Leak test all gas joints prior to starting the appliance.  
4. Familiarize yourself with the control panel components, see page 58.  
5. Follow Lighting Instructions on next page to light the pilot and then the main burner.  
6. Leak test all gas joints again.  
7. Check the pilot flame ensuring that it looks like the illustration below. Adjust the  
pilot flame if necessary.  
Flames  
Pilot Hood  
Thermopile  
Thermocouple  
Piezo Igniter  
INITIAL START-UP: NORMAL OCCURRENCES  
WARNING!  
You must clean all finger-  
prints and oils from any  
gold surface prior to firing  
the fireplace for the first  
time.  
Fumes from curing paint and oil burning off the steel is a normal occurrence. Open  
window to vent the area until fumes disappear.  
Condensation appearing on the glass each time you start the fireplace is also normal.  
Blue Flames will occur on the initial start-up. After fifteen minutes the flames will become  
the yellow/orange flame color.  
Remote Wall Switch: If you install a remote wall switch to operate the fireplace, leave  
the ON/OFF switch on the fireplace control panel in the “ON” position.  
Do not place any combustible items on top of or directly in front of the fireplace,  
even temporarily. The optional thermostat may start the fireplace causing a  
combustible item to ignite.  
If the fireplace turns on and off frequently while using the thermostat, you may  
want to adjust the flame height down until it produces just enough heat needed,  
or relocate the thermostat further away from the fireplace.  
Page 54  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
LIGHTING INSTRUCTIONS  
FOR YOUR SAFETY READ BEFORE LIGHTING  
WARNING: If you do not follow these instructions exactly, a fire or explosion may  
result causing property damage, personal injury or loss of life.  
A. This appliance has a pilot that must be lit manually. When lighting the pilot, follow these instructions  
exactly  
B. BEFORE LIGHTING, smell around the appliance area for gas. Be sure to smell next to the floor because  
some gas is heavier than air and will settle on the floor.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
do not touch any electric switch; do not use any phone in your building.  
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.  
If you cannot reach your gas supplier, call the fire department.  
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or  
turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result  
in a fire or explosion.  
D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician  
to inspect the appliance and to replace any part of the control system and any gas control which has been  
under water.  
LIGHTING INSTRUCTIONS  
INPUT SIDE  
TEST VALVE  
OUTPUT SIDE  
1. STOP! Read the safety information above on this label.  
TEST VALVE  
2. Set the thermostat to the lowest setting (if applicable) and turn off the  
switch at the control panel.  
3. Disconnect power from appliance.  
4. Remove facia.  
5. Open the door of the appliance with spring latches located at the top and bottom of the door.  
6. Wait five (5) minutes to clear out any gas. Smell for gas, including near the floor. If you smell gas, STOP!  
Follow “B” of the safety information above. If you don’t smell gas go to the next step.  
7. Push gas control knob in and turn to pilot position. NOTE: Knob cannot be turned from “PILOT” to “OFF”  
unless knob is pushed in slightly. Do not force.  
8. Press down on the gas control knob in pilot position and simultaneously press piezo igniter on the control  
panel. (This may take many repetitions for lighting.)  
9. The pilot should be visible through the door below the front log.  
10. After the pilot is lit, continue holding control knob down for approximately 30 seconds. Release knob and  
it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 9.  
If the knob does not pop up when released, stop and immediately call your service technician or gas  
supplier.  
If the pilot will not stay lit after several tries, turn the gas control knob to “OFF” and call your service  
technician or gas supplier.  
11. Turn gas control knob to “ON”.  
12. Turn burner switch on the control panel to on. If thermostat is to be used,  
leave switch in “OFF” position and set the thermostat to desired setting.  
13. Reconnect electrical power to appliance.  
TO TURN OFF GAS TO APPLIANCE  
1. Set the thermostat to lowest setting.  
2. Turn off all electric power to the appliance if service is to be performed.  
3. Push in gas control knob slightly and turn clockwise  
Do not force.  
to “OFF” position.  
Page 55  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
SHUTTER ADJUSTMENT  
A 5/32 Allen wrench is supplied with unit to make adjustment to the two Allen bolts which  
operate the shutter adjustment for rear (top) and front (lower) main burners. These are located  
beneath the firebox, behind the control panel on your left at the base of the burner pans.  
Light stove and allow to burn for 20 minutes to allow logs to cure. While logs are curing  
you may notice a bright orange flame, this is normal. When this flame turns to yellow or disap-  
pears, the shutter adjustment can take place.  
The shutter is pre-set to the open position at factory, so adjustment may not be necessary.  
If flame height adjustment is required, turn the allen bolts counterclockwise to close shutters and  
obtain a yellow flame. For a blue flame with more glow, turn the allen bolts clockwise to open the  
shutters. Wait 5 minutes for flame to settle. If the flame is not satisfactory, repeat the procedure.  
This setting should only require attention during initial set-up.  
DAMPER ADJUSTMENT  
NOTE: Fireplace must be operating to make this adjustment. An adjustable damper is  
built in to the unit to control the flow rate of exhaust gases. This ensures proper combustion for  
your vent configuration and is also a factor in flame appearance.  
The damper control is located above the heat exchanger. Use a flashlight to locate the  
Phillips screwhead. Using a long Phillips screwdriver, loosen the screwhead. Above that screw  
is an extension rod with a standard driver slot at the end near the front of the unit.  
Use a standard screwdriver to make the adjustment while observing flame appearance,  
turn counterclockwise until optimum operation occurs. This setting should only require attention  
during initial set-up.  
.
ADJUSTING FLAME HEIGHT  
The flame of the fireplace is adjustable in order to tailor the look and heat output to your specific  
needs. It is adjusted by turning the Comfort Control dial on the control panel, see page 58.  
ADJUSTING THE BLOWER SPEED  
The blower will turn on automatically within approximately 10 minutes after start-up and the  
fireplace is up to temperature. This aids in transferring the heat into the living area. The blower  
speed can be increased or decreased using the Fan Speed knob on the control panel, see page  
54.  
NORMAL OPERATING SOUNDS  
Blower ......................... The fireplace uses a 160 cfm blower to circulate heated air into  
the living area. It produces a whirring sound which increases in  
volume as the speed is increased.  
Pilot Flame .................. The pilot flame remains on constantly and makes a “whisper” sound.  
Gas control valve ....... As the valve opens and shuts down it will click.  
Burner pan .................. The burner pan is located beneath the logs. It distributes the gas  
producing a clean, efficient and aesthetic burn. As the main burner  
gets up to temperature a creaking sound will be heard. This is the  
expansion of the metal. The sound will cease once the fireplace is  
up to temperature but may return upon cool down.  
Blower snap disc........ This part may produce a clicking sound as the blower turns on and  
off.  
Heat Exchanger .......... A normal expansion and contraction sound may be heard.  
Page 56  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
HIGH ALTITUDE OPERATION  
In Canada, this unit is approved from 0 to 4500 feet above sea level. Installation of this  
stove at altitudes above 4500 feet is subject to field test of the individual installation and approval  
by the local authority having jurisdiction.  
In the United States, input ratings of this unit are based on sea level operation, and shall  
not be changed for operation at elevations up to 2000 feet. For operation at elevations above  
2000 feet, this stove shall be reduced at the rate of 4% for each 1000 feet above sea level.  
Exception: As permitted by the authority having jurisdiction.  
To adjust stove for operation above 2000 feet the burner orifices may need to be changed.  
The orifices are located beneath the log set so it is necessary to first remove the logs. To do so  
please refer to the following detailed instructions to achieve optimum performance of your stove.  
WARNING ! The following procedure should only be undertaken by a qualified and certified gas  
appliance installer.  
CAUTION: DISCONNECT ANY ELECTRICAL CORDS AND TURN OFF GAS SUPPLY TO  
UNIT BEFORE PROCEEDING.  
1. If logset is installed, remove logs and embers at this time.  
2. With a Phillips screwdriver, remove pilot lighting channel and front log rack.  
3. Remove the two Phillips head screws that secure the front and rear burner pan in place.  
4. Remove the burner pans by sliding to the right and lifting out. (Shutters may need to be  
adjusted ‘closed’ to make this easier).  
5. Slide shutters out of the way. Using a 3/8" wrench or socket, remove the orifice inserts and  
replace with proper orifices for the specified gas. See below.  
6.  
Reinstall burner pans and adjust shutters to ‘open’ position.  
CAUTION: The correct orifice placement is critical for proper appliance performance fol-  
low BTU de-rating chart below to locate the necessary orifice size for the  
front and rear burners.  
EQUIVALENT ORIFICE SIZES AT HIGH ALTITUDES  
(Includes 4% Input Reduction For Each 1000 Feet)  
Orifice size 2000 3000 4000 5000 6000 7000 8000 9000 10000  
at Sea Level:  
Natural Gas  
Front 47  
Rear 42  
Propane  
Front 56  
Rear 53  
48  
43  
48  
43  
48  
43  
49  
44  
50  
44  
50  
45  
51  
46  
51  
47  
52  
47  
57  
54  
57  
54  
57  
54  
58  
54  
58  
54  
59  
55  
60  
55  
61  
55  
62  
56  
Page 57  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
OPERATION  
Read this entire manual prior to using the fireplace. Pay particular attention to the “Safety  
Precautions” section on pages 6-9. Failure to follow the instructions may result in prop-  
erty damage, bodily injury, or even death.  
CONTROL PANEL  
Main Burner  
Fan Speed  
Comfort Control  
Thermostat  
Connection  
Valve Control  
Ignitor  
FAN SPEED This knob controls the speed of the internal convection blower that pushes  
the heated air into the room.  
MAIN BURNER ..................................... This control is used to turn the fireplace on and  
off.  
PILOT IGNITOR ................................... The pilot ignitor is used only to start the pilot.  
When pressed, it sends an electrical charge to  
the pilot assembly. This creates a blue spark  
directly next to the pilot, igniting the pilot flame.  
VALVE CONTROL................................. This knob is used to control gas to the fireplace  
and for starting the pilot. There are three posi-  
tions, ON, OFF, & PILOT. The pointer on the  
panel indicates the position of the knob.  
COMFORT CONTROL .......................... This knob controls the flame height from low  
(“LO”) to high (“HI”).  
If using a remote control or thermostat, the On/Off Switch must be left “OFF”.  
Turning the On/Off Switch “ON” will keep the fireplace on continually.  
Page 58  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
MAINTENANCE  
GENERAL  
Installation and repair should be done by a qualified service person. The appliance  
should be inspected before use and at least annually by a professional service person.  
More frequent cleaning may be required due to excessive lint from carpeting, bedding  
material, et cetera. It is imperative that control compartments, burners and circulating  
air passageways of the appliance be kept clean.  
GLASS CLEANING  
WARNING! DO NOT CLEAN GLASS WHEN HOT! TURN UNIT OFF AND ALLOW TO  
COOL. DO NOT USE ABRASIVE CLEANERS ON GLASS SURFACE!  
Turn off pilot light.  
Remove fascia.  
Open door by releasing four spring latches, two on top and two on bottom of glass.  
Using glass cleaner, wipe with soft cloth or clean paper towel until surface is dry.  
Relight pilot.  
Close door.  
Replace Fascia.  
Check main burner’s operation.  
NOTE:  
If you observe a white film on the door glass, use a hard water deposit glass cleaner  
or contact your dealer. The use of a glass cleaner will reduce the mineral deposits.  
NOTE: Do not use abrasive materials or chemical cleaners.  
Refer to page 61 for Glass Replacement instructions.  
GOLD OR NICKEL FASCIA - CARE AND TREATMENT  
WARNING! You must clean all the fingerprints and oils from gold or nickel surface  
prior to firing the fireplace for the first time.  
Use a glass cleaner or vinegar and a very soft towel to remove the oils. If gold or nickel  
fascia is not cleaned properly prior to lighting the first fire, the oils remaining from fingerprints  
can cause permanent markings on the gold plating. After the plating is cured, the oils will not  
affect the finish and regular maintenance can be provided using glass cleaner and a very soft  
cloth as needed.  
Page 59  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
YEARLY SERVICING PROCEDURES  
WARNING! Failure to inspect and maintain the fireplace may lead to improper com-  
bustion and apotentially dangerous situation. The following procedures are rec-  
ommended to be completed by a qualified technician once per year, preferably  
prior to the burning season.  
1. Check the pilot flame. It should engulf approximately 3/8" of the top of the thermopile and  
engulf the top of the thermocouple (see illustration on page 54).  
2. Shut off gas to the fireplace by turning the valve control knob to “OFF” (see step A under  
“Starting the Pilot” on page 55). Allow the fireplace to cool for 15 minutes. Remove the  
fascia and glass.  
3. Remove the log set (NOTE: the logs are extremely fragile ceramic. If any log is cracked  
or deteriorated, replace it when reinstalling. Check the logs for sooting. A small amount of  
soot along the bottom of the logs is normal. If excessive sooting is found, the fireplace will  
require adjustment. Contact your dealer.  
4. Clean the burner pan (especially in the burner holes and slots) and inspect the following:  
a. Check for burner pan holes that are cracked, severely warped, or corroded.  
b. Make sure the burner pan assembly fits flat against the floor of the firebox.  
c. Check the firebox and area around the pilot to make sure there is no warping or damage. If  
any problem is found, discontinue use and contact your dealer for service.  
5. Reinstall the log set. Reinstall the glass (if the glass is damaged, contact your dealer for a  
replacement) Make sure the gasket along the perimeter of the glass contacts the face of  
the firebox and forms an airtight seal. If it does not, realign or replace the gasket to insure  
an airtight seal. Reinstall the fascia.  
6. Inspect the area behind the access door. Check the gas control valve and all of the gas  
lines. If any damage is found, discontinue use and contact your dealer for service.  
7. Start the pilot and turn on the main burner. The flames should be orange/yellow and not  
touch the top of the firebox. If the pilot or main burners do not burn correctly, contact your  
dealer for service. Monitor the blower operation.  
8. Remove any debris or vegetation near the vent termination, ensuring that the flow of com-  
bustion and ventilation air is not obstructed. Contact your dealer if any sooting or deteriora-  
tion is found near the vent termination.  
Page 60  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
GLASS REPLACEMENT  
Replace glass with part #842-3820 ONLY, available from your dealer.  
1.  
2.  
Turn valve to “OFF” position to prevent start-up of unit while door is removed.  
Prepare a flat area to lay the door on by covering the surface with cardboard,  
disposable tarp or paper large enough to contain the entire door.  
Wear leather gloves, long sleeves and safety glasses to protect against injury  
from any broken glass.  
3.  
4.  
5.  
6.  
Ensure that unit has completely cooled. Remove fascia, then door.  
Lay door on prepared surface with the front facing down.  
Use a Phillips screwdriver to remove the 16 screws holding the four retaining  
strips in place and set aside.  
7.  
8.  
Carefully remove the retaining strips and set aside.  
Carefully remove broken/defective glass and dispose of pieces. Dust any par-  
ticles of glass off the door frame and dispose of the covering it was laid on. Any  
particles of broken glass could scratch the replacement piece if contact is made  
during the replacement. Scratches in the glass may cause breakage.  
Place a clean covering on your work surface.  
9.  
10.  
Position the door frame face down upon the clean surface and place the new  
glass on the frame with the thin side of gasketing down, facing the front.  
Reinstall the retainer strips using the screws removed earlier. Take care not to  
over tighten the screws.  
11.  
12.  
13.  
Replace the glass with the narrow edging of frame on the top, but do not latch  
until Lighting Instructions (page 55) have been completed.  
Replace fascia.  
4 Retaining strips  
16 screws  
Gasketing  
(Thick side up.)  
Glass  
Frame Bottom  
Frame Top  
Page 61  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
BLOWER REPLACEMENT  
Part #842-3790  
1.  
Disconnect power to unit at power supply (this may require shutting off power  
at the circuit breaker box).  
Remove fascia and door.  
2.  
3.  
4.  
5.  
Remove control panel cover.  
Disconnect white wire from white wire at junction box in unit.  
Disconnect black wire from snap disc.  
NOTE: Removing the blower requires passing the blower unit through a restricted  
area. Care must be taken to ensure that your gas line is out of the way.  
Depending on your gas line installation, it may be necessary to discon-  
nect your gas line on the valve side of shutoff within the unit and move  
the flex line aside.  
6.  
Reach in and take hold of one or both ends of the blower impeller(s) and lift  
it up off mounting studs.  
7.  
Pull blower forward, towards the back of valve.  
Slide blower all the way to your right.  
8.  
9.  
10.  
Rotate left side of blower towards the front of unit.  
Carefully maneuver blower out the front, over gas line between control panel  
and door latch.  
11.  
Reinstall new blower in reverse order.  
NOTE: When reinstalling ensure that rubber grommets on the end being inserted  
first are not dislodged from the blower.  
Page 62  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
ELECTRICAL SCHEMATIC  
Page 63  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
TROUBLESHOOTING  
Pilot won’t light  
Is a gas shut-off valve turned on?  
Is the valve control knob turned to “PILOT”  
(See Lighting Instructions, #7, Pg. 55).  
Is the valve control knob pushed in? (See Lighting Instructions, #8)  
Was the igniter pressed repeatedly? (See Lighting Instructions, #8)  
Main Burners Will Not Start  
Has the pilot light gone out? (See Lighting Instructions, Pg. 55).  
Is the gas control valve turned to “PILOT” or “OFF” ? (See Lighting Instructions).  
Is the ON/OFF switch in the “OFF” position? (Turn to “ON”)  
Is the remote control working correctly?  
(See instruction manual for the remote control).  
Is the thermostat disconnected or set too low?  
(See Thermostat Operation, Pg. 47).  
If LP, is the tank empty?  
Remote Control Does Not Turn Unit On / Off  
Has the pilot light gone out? (See Lighting Instructions, Pg. 55).  
Is the gas control valve turned to “PILOT” or “OFF? (See Lighting Instructions).  
Is the ON/OFF switch turned to “OFF”? (Turn the switch to “OFF”)  
If the switch is on, unit will remain on.  
Is the remote too far away from the fireplace? (Use remote closer to fireplace)  
Is the remote control receiver turned “OFF”?  
(See instruction manual for the remote control).  
Are the remote control batteries dead?  
(See instruction manual for the remote control).  
Thermostat Does Not Work  
Has the pilot light gone out? (SeeLighting Instructions, Pg. 55).  
Is the gas control valve turned to “PILOT” or “OFF” ? (See Lighting Instructions).  
Is the thermostat set too low? (See Thermostat Operation, Pg. 47).  
Is the On/OFF switch turned to “OFF? (Set the switch to “ON”)  
If switch is on, unit will remain on. (The switch overrides the thermostat.)  
Fireplace Will Not Distribute Heat  
Is the fireplace getting electricity? (Check the breaker switch)  
Is the fireplace up to temperature? (See Operating Procedures, Pgs. 54-58).  
Is Blower operational? (Check Fan Speed control, Pg. 58).  
Page 64  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
TROUBLESHOOTING, (CONT.)  
Pilot Goes Out Once a Month or More  
Has the gas supply been shut off? (Keep gas supply turned on)  
Flames Are Too blue  
Has the fireplace just been started? (This is normal - see Initial Start-up Pg. 54).  
Primary Air adjustment--contact dealer.  
Flames Are Too Short (Under 6”)  
Is the flame height may be turned too low? (Turn the flame height to “HI”; see  
Adjusting the Flame Height, Pg. 56).  
Primary air adjustment - Contact Dealer.  
Damper adjusted properly? - Contact Dealer.  
Thin Layer of Soot Covers the Glass  
Are the logs or embers placed incorrectly? (See Log Set Installation, Pg. 50).  
Is the air shutter adjusted properly? (Contact Dealer for Air Shutter adjustment)  
Damper adjusted properly?  
Fireplace Design:  
Many of the components within this fireplace are designed specifically for safety  
purposes. It is therefore imperative that only certified gas service technicians should  
service this fireplace.  
Main Burner Operation:  
A millivolt system controls the operation of this fireplace. The thermopile and  
thermocouple generate electricity when heated by the pilot flame. This electricity is used  
to operate the gas valve. Without enough electricity, the gas valve will not turn on. That  
is why when starting the pilot the gas control knob has to be pressed in long enough for  
the thermocouple to heat up and generate enough electricity. The thermopile provides  
power for the ON/OFF switch, remote control, or thermostat. Because the thermopile  
generates the electricity needed to turn the fireplace on and off, this fireplace can be  
operated when the power is out (although the blower will not run).  
Gas Buildup Prevention Feature:  
This appliance’s utilization of a high-technology gas valve in conjunction with a  
pilot flame ensures that no gas builds up inside the firebox.  
The thermocouple (next to the pilot) senses when the pilot flame is lit. If the pilot  
flames goes out, this thermocouple no longer generates electricity, causing the gas valve  
to automatically shut off all gas to the heater, preventing the pilot from spilling gas into  
the firebox.  
Page 65  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
PARTS & ACCESSORIES  
PARTS  
842-0240  
842-3501  
842-3910  
842-3900  
842-4480  
842-4490  
842-4520  
842-4500  
842-4510  
842-4530  
842-4550  
842-4540  
842-3790  
842-4560  
842-4570  
842-3940  
841-0370  
842-3250  
842-1660  
842-0360  
832-2970  
842-3780  
842-3820  
842-3291  
Valve (NG)  
Pilot  
Pilot Orifice NG (.025)  
Pilot Orifice LP (.016)  
Logset (7 pieces)  
Rear Log  
Front Log  
Left Twig  
Right Twig  
Lower Left Front Twig  
Lower Right Front Twig  
Lower Center Front Twig  
Blower  
Front Pan Burner  
Rear Pan Burner  
Lava Rock  
Nuggets  
Rheostat  
On/Off Switch  
Piezo Igniter  
Blower Snapdisc, 125°  
Baffle  
Glass  
Owner’s Manual  
ACCESSORIES  
841-0710  
841-0750  
841-0720  
841-0730  
841-0740  
842-4470  
812-2880  
811-0520  
844-0100  
Fascia, Arched Gold  
Fascia Arched Brushed Nickel  
Fascia, Arched Black  
Fascia, Rectangular Black  
Brick (3 pieces)  
LP Conversion Kit (SIT EZ change)  
Thermostat, manual  
Thermostat, programable  
Thermostatic Remote Control  
Page 66  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40 Direct Vent FIREPLACE  
WARRANTY  
North America’s Best  
Limited Lifetime Gas Appliance Warranty  
GAS APPLIANCE LIMITED LIFETIME WARRANTY  
Aladdin Hearth Products, warrants this gas heating appliance to the original purchaser for the lifetime of the  
appliance, to be free from defects in material and workmanship. This warranty gives you specific legal rights; you  
may have other rights which may vary from state to state.  
This limited Lifetime Warranty covers items such as but not limited to combustion chambers, heat exchange  
systems, burners, gas logs, doors, gold plating, and glass damaged by thermal breakage.  
All parts to be replaced must be returned to an authorized Aladdin Hearth Products dealer at purchaser’s expense  
for inspection and approval by Aladdin Hearth Products prior to repair or replacement. No repair or replacement  
costs will be honored without approval of Aladdin Hearth Products.  
This new Quadra-Fire product must be installed by a competent, authorized service contractor. It must be installed  
and operated at all times in accordance with the Installation, Operation and Maintenance Instructions included in  
this manual, as well as any applicable local and national codes. Any alteration, willful abuse, accident, or misuse of  
the product shall void this warranty.  
Any installation, construction, transportation, or other related costs or expenses arising from defective part(s), repair,  
replacement, etc., will not be covered by this warranty, nor will Aladdin Hearth Products assume responsibility for  
them. Further, Aladdin Hearth Products will not be responsible for any incidental, indirect, or consequential  
damages, except as provided by law.  
All electrical components such as but not limited to blowers, wiring, speed controls, thermodisc switches and gas  
valves are covered by Aladdin’s one year warranty program.  
Aladdin Hearth Products will not be responsible for any alteration to the unit which causes sooting that results in  
damage to the interior of the building in which this appliance is installed.  
This warranty is void if the insert has been operated in atmospheres contaminated by chlorine, fluorine, or other  
damaging chemicals, the stove is subjected to prolonged periods of dampness or condensation, or there is any  
damage to the stove or other components due to water or weather damage which is the result of, but not limited to,  
improper chimney or venting installation.  
This limited Lifetime Warranty does not extend to or include paint, door gasketing, glass gasketing, firebrick or other  
ceramic insulating materials. It does not cover installation or operational-related problems such as overfiring,  
downdrafts or spillage caused by environmental conditions, nearby trees, buildings, hilltops, mountains, inadequate  
venting or ventilation, excessive offsets, or negative air pressures caused by mechanical systems such as furnaces,  
fans, clothes dryers, etc.  
This limited Lifetime Warranty does not apply to venting components, hearth components or other accessories used  
in conjunction with the installation of this product not manufactured by Aladdin Hearth Products.  
This limited Lifetime Warranty is effective on all gas inserts sold after September 1, 1996, and supersedes any and  
all warranties currently in existence.  
IMPORTANT  
Completing and returning your warranty registration card will assist us in expediting any warranty claims. Please  
return the completed card within 10 days from the date of purchase to Aladdin Hearth Products, 401 North Wynne  
Street, Colville, WA 99114-2153. Proof of purchase is required to secure warranty.  
Copyright Aladdin Hearth Products, August 1998  
Page 67  
250-4721 JUNE 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMINGTON QFP40  
Direct Vent Gas Fireplace  
Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Raypak Boiler 2100 4001 User Guide
RCA Clock RCD10 User Guide
Remington Chainsaw RM1015SPS User Guide
Renesas Computer Hardware R8C 27 User Guide
Rockford Fosgate Car Speaker PCH 14X User Guide
Rose electronic Photo Scanner CTP 8S User Guide
Samson Headphones CL7 User Guide
Samsung All in One Printer CLP 600 User Guide
Schumacher Remote Starter VTV 20 User Guide
SECO LARM USA Door SK 1131 SQ User Guide