Owners &
Installation
P36 Gas Log Fireplace
Models: P36-NG4
P36-LPG4
PLEASE KEEP THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING:
FOR YOUR SAFETY
Improperinstallation,adjustment,alteration,
What to do if you smell gas:
service or maintenance can cause injury or
Do not try to light any
property damage. Refer to this manual. For
appliance
assistanceoradditionalinformationconsult
Do not touch any electrical
an authorised installer, service agency or
switch: do not use any
phone in your building.
LISTINGS AND CODE APPROVALS
the gas supplier.
Immediately call your gas
FOR YOUR SAFETY
Do not store or use gasoline or other
flammablevapoursandliquidsinthevicinity
of this or any other appliance.
Installation and service must be performed
by an authorised installer, service agency or
the gas supplier.
These gas appliances have been tested in
accordancewithAS4553-2000,NZS5262
and have been certified by the Australian
Gas Association for installation and
operationasdescribedintheseInstallation
and Operating Instructions.
supplierfromaneighbour's
phone. Follow the gas
supplier's instructions.
If you cannot reach your
gas supplier, call the fire
department.
Your unit should be serviced annually
by an authorised service person.
918-538b
Download from Www.Somanuals.com. All Manuals Search And Download.
08/16/07
TABLE OF CONTENTS
OPERATING INSTRUCTIONS
DATA BADGE
Optional Fan................................................................30
Operating Instructions .................................................30
Normal Operating Sounds Of Gas Appliances............31
Shutdown Procedure...................................................31
Data Badge ...................................................................4
INSTALLATION
First Fire ......................................................................31
Lighting Procedure ......................................................31
Copy Of The Lighting Plate Instructions......................32
Important Message........................................................5
Before You Start ............................................................5
General Safety Information ...........................................5
Installation Checklist......................................................5
Clearances ....................................................................6
Locating Your Gas fireplace ..........................................6
Manufactured Mobile Home Additional Requirements ..6
Combustible Mantels.....................................................7
Mantel Leg Clearances .................................................8
Framing And Finishing...................................................8
Unit Assembly Prior to Installation.................................9
Flueing Introduction.......................................................9
Exterior Flue Termination Locations ............................10
Flueing.........................................................................11
Simpson Dura-Vent Flueing ........................................12
Simpson Dura-Vent Flueing Components List ............12
Flueing Arrangements - Horizontal Terminations.........13
Flueing Arrangements - Horizontal Terminations.........14
Flueing Arrangements - Vertical Terminations.............15
Horizontal Terminations..............................................17
Vertical Terminations ...................................................18
Gas Line Installation....................................................20
Pilot Adjustment...........................................................20
Aeration Adjustment ....................................................20
Gas Pipe Pressure Testing..........................................20
Optional Brick Panels..................................................21
Log Set Installation......................................................21
Standard Flush Door ...................................................23
Premium Flush Front Installation.................................24
Option 1: Wall Switch ..................................................27
Option 2: Remote Control............................................27
Option 3: Wall Thermostat ..........................................27
Thermostat Wire Table ................................................27
Wiring ..........................................................................28
MAINTENANCE
Maintenance Instructions ............................................32
Gold-Plated & Brass Louvres or Trim..........................33
Log Replacement ........................................................33
Thermopile / Thermocouple.........................................33
Glass Gasket...............................................................33
Door Glass ..................................................................33
Removing Valve...........................................................34
Installing Valve.............................................................34
PARTS LIST
Main Assembly ............................................................35
Burner Assembly & Log Set ........................................36
Bay Front Assembly ....................................................37
Flush Front Accessories..............................................38
Premium Flush Front Assembly ..................................39
Cast Faceplate Assembly............................................40
WARRANTY
Warranty......................................................................43
Regency® P36-4 Gas Log Fireplace
3
Download from Www.Somanuals.com. All Manuals Search And Download.
DATA BADGE
This is a copy of the label that accompanies Thelabelislocatedonthefrontinsidebaseofthe
each P36 Zero Clearance Room Sealed Gas unit, visible when the bottom louvre is open.
Fireplace.Wehaveprintedacopyofthecontents
DATA BADGE NOTE: Regency® units are
constantly being improved. Check the label on
the unit and if there is a difference, the label on
the unit is the correct one.
here for your review.
(Australia Only)
Regency® P36-4 Gas Log Fireplace
4
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
IMPORTANT MESSAGE
GENERAL SAFETY
INFORMATION
1) The appliance shall be installed in
accordance with the manufacturer's
installation instructions,local gas fitting
regulations, municipal building codes,
water supply regulations, electrical wiring
regulations, with AS5601-2004 (AGA
gas installation code) NZS 5261 (New
Zealand)
INSTALLATION
CHECKLIST
SAVE THESE INSTRUCTIONS
TheP36-NGorP36-LPGRoomSealedFireplace
must be installed in accordance with AS5601-
2004andNZS52615261andtheseinstructions.
Carefully read all the instructions in this manual
first. Consult the "authority having jurisdiction"
to determine the need for a permit prior to
starting the installation. It is the responsibility of
the installer to ensure this fireplace is installed
in compliance with manufacturer's instructions
and all applicable codes.
1) Locate appliance
a) Locate Your Gas Fireplace
b) Clearances
c) Combustible Mantels
d) Framing & Finishing
2) Assemble Top Standoffs and Top Facing
Support and Side Nailing Strips, refer to
section"UnitAssemblyPriortoInstallation".
(NOTE: must be done before installing unit
into fireplace.)
2) Installation and repair should be done
ONLY by an authorised person.
BEFORE YOU START
NOTE: NOT INTENDED AS A FIREPLACE
INSERT.
3) THISAPPLIANCEISNOTINTENDEDASA
FIREPLACEINSERT. DONOTCONNECT
TO MASONARY FLUE.
3) Installflue(Refertosection"SimpsonDura-
vent Flueing").
4) Make gas and electrical connections. Test
the pilot. Must be as per diagram. Refer to
section "Pilot Adjustment."
4) This appliance must be connected to
the specified flue and termination cap
to the outside of the building envelope.
Never flue to another room or inside a
building. Make sure that the flue is fitted
as per Flueing instructions.
INSTALLATION AND REPAIR SHOULD
BE DONE BY A AUTHORISED SERVICE
PERSON. THE APPLIANCE SHOULD BE
INSPECTED BEFORE USE AND AT LEAST
ANNUALLYBYANAUTHORISEDSERVICE
PERSON. MORE FREQUENT CLEANING
MAY BE REQUIRED DUE TO EXCESSIVE
LINT FROM CARPETING, BEDDING
MATERIAL, ETC. IT IS IMPERATIVE THAT
CONTROL COMPARTMENTS, BURNERS
AND CIRCULATING AIR PASSAGEWAYS
OF THE APPLIANCE BE KEPT CLEAN.
5) Installstandardandoptionalfeatures. Refer
to the following sections:
a. Brick Panels
5) Inspect the flueing system annually for
b. Log Set
blockage and any signs of deterioration.
c. Flush Door
d. Premium Flush Front
e. Bay Door
6) Flueing terminals shall not be recessed into
a wall or siding.
f. Hampton® Cast Faceplate
g. Hampton® Cast Grills
h. Wall Switch
7) Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
DUE TO HIGH TEMPERATURES, THE
APPLIANCE SHOULD BE LOCATED OUT
OFTRAFFICANDAWAYFROMFURNITURE
AND DRAPERIES.
i. Remote Control
j. Wall Thermostat
k. Fan
8) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fireplace.
6) Final check.
WARNING: FAILURE TO INSTALL THIS
APPLIANCECORRECTLYWILLVOIDYOUR
WARRANTY AND MAY CAUSE A SERIOUS
HOUSE FIRE.
Before leaving this unit with the customer,
the installer must ensure that the appliance is
firing correctly and operation fully explained
to customer.
9) Wearglovesandsafetyglassesforprotection
while doing required maintenance.
CHILDREN AND ADULTS SHOULD BE
ALERTED TO THE HAZARDS OF HIGH
SURFACETEMPERATURES,ESPECIALLY
THE FIREPLACE GLASS, AND SHOULD
STAY AWAY TO AVOID BURNS OR
CLOTHING IGNITION.
10) Be aware of electrical wiring locations in
walls and ceilings when cutting holes for
termination.
This includes:
1) Clockingtheappliancetoensurethecorrect
firing rate (rate noted on label 30,000 Btu/h)
after burning appliance for 15 minutes.
11) Under no circumstances should this
appliancebemodified. Partsthathavetobe
removed for servicing should be replaced
prior to operating this appliance.
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISED WHEN THEY
ARE IN THE SAME ROOM AS THE
APPLIANCE.
2) Ifrequired,adjustingtheprimaryairtoensure
that the flame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
12) Installationandanyrepairstothisappliance
should be done by an authorised service
person.Anauthorisedservicepersonshould
be called to inspect this appliance annually.
Make it a practice to have all of your gas
appliances checked annually.
CAUTION:Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
CLOTHING OR OTHER FLAMMABLE
MATERIAL SHOULD NOT BE PLACED ON
OR NEAR THE APPLIANCE. DO NOT USE
AEROSOLS IN THE VICINITY OF THIS
APPLIANCE.
13) Do not slam shut or strike the glass door.
14) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.)
be used in this appliance.
15) The appliance area must be kept clear and
free of combustible materials, (gases and
other flammable vapours and liquids).
Regency® P36-4 Gas Log Fireplace
5
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
NOTE: The minimum floor clearance must
be maintained from the top surface of the
carpeting, tile, etc.
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your stove,
ensure that the clearances outlined on this
page are met.
MANUFACTURED
MOBILE HOME
ADDITIONAL
Minimum Clearance from Top of Unit to:
Mantel* Minimum
Ceiling from top of unit.
7"
(177mm)
REQUIREMENTS
32" (1016mm)
1) Ensure that structural members are not cut
Side Wall Clearance
Bay or Flush Front
2) Provide adequate clearances for
or weakened during installation.
6"
2"
(152mm)
(51mm)
servicing.
2) Ensurepropergroundingusingthe#8ground
Horizontal Flue Clearances
3) The appliance must be installed on a flat,
solid, continuous surface (e.g. wood, metal,
concrete).Thismaybethefloor,orraisedup
on a platform to enhance its visual impact.
If the appliance is going to be installed
on carpeting, combustible linoleum tile or
other combustible material other than wood
flooring, the appliance must be installed on
a metal or wood panel extending the full
width and depth of the appliance.
lug provided. See section "Wiring."
Top
Side
Bottom
1-1/2" (38mm)
1-1/2" (38mm)
CLEARANCES
The clearances listed below are Minimum
distances unless otherwise stated:
Vertical Flue Clearances
1-1/4" (32mm)
Alcove Clearances**:
Max. Depth
Min. Width
Min. Height
36" (914mm)
48" 1219mm)
72" 1829mm)
A major cause of chimney related fires is
failure to maintain required clearances (air
space) to combustible materials. It is of the
greatest importance that this fireplace and
flue system be installed only in accordance
with these instructions.
4) The P36 Co Axial Flue Gas Fireplace can
beinstalledinarecessedpositionorframed
out into the room as in A, B, C, D. See
Diagram 1.
* see mantle clearance instructions
(Refer to section "Combustible Mantels" &
"Mantel Leg Clearances."
Clearance to Combustibles from:
WARNING
Back
Side
0"
0"
0"
(0mm)
(0mm)
(0mm)
Fire hazard is an
extreme risk
Floor
if these clearances
are not adhered to.
Diagram 1
A) Flat on Wall
B) Flat on Wall Corner
C) Recessed into Wall/Alcove
D) Corner
5) This appliance is Listed for bedroom
installationswhenusedwithaListedMillivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
Clearances for Bay or Flush Front
6) The P36 Co Axial Flue Gas Fireplace is
approved for alcove installations, which
meet the clearances listed on this page.
7) Werecommendthatyouplanyourinstallation
on paper using exact measurements for
clearances and floor protection before
actually installing this appliance. Have an
authorized inspector, dealer, or installer
review your plans before installation.
Note: For flue terminations see section
"Exterior Flue Termination
Locations."
Regency® P36-4 Gas Log Fireplace
6
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Regency® P36-4 Gas Log Fireplace
7
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
2) Frame in the enclosure for the unit with
MANTEL LEG
CLEARANCES
framing material.
Combustible mantel leg clearances as per
diagram below:
152mm SideWall
P36
Fireplace
Maximum
38mm
projection
51mm
at 51mm
minimum
clearance.
127mm
Allowablemantelleg
projection.
Standard Framing Dimensions
A
B
C
D
FRAMING AND
FINISHING
Note: 40-1/2" (1029mm) is the minimum
height for both flex termination or
Simpson Dura-Vent flueing.
36-1/4" 36-1/4" 12-3/4" 46"*
921mm 921mm 324mm 1126mm*
1) Determine the total thickness of facing
material (e.g. drywall plus ceramic tiles) to
allow the finished surface to be flush with
the front of the unit. Total facing thickness
canvaryfrom1/2"(13mm)to1-1/4"(32mm)
thick.
Framing Dimensions with
Premium Flush Front Option
Note: The unit does not have to be
completely enclosed in a chase. The
clearance on top of the unit is 0" to
thestandoffssocombustiblebuilding
materials can be laid directly on top
of the standoffs. You must maintain
1-1/2" (38mm) clearance from the
flue to combustible materials for flex
(1-1/4" for Simpson Dura-Vent ).
A
B
C
D
37-1/4" 37-1/4" 17-3/8" 46-1/2"*
944mm 946mm 432mm 1182mm*
* 'D' is Minimum height to combustible mate-
rials including the Minimum 2" (51mm) Top
clearance to the Horizontal Flue, see flue
clearances in section "Clearances."
5) Use steel studs for framing where the
1-1/2" (38mm) clearance from the flue to
combustiblematerialcannotbemaintained,
e.g. front top header.
Premium Flush Front Framing
Do not use combustible material as lining (eg.
timber) around the fireplace as shown in the
shaded area in the diagram below.
Install Side Nailing Strips, Top Facing
Support, and Top Standoffs before
unit is slipped into position. See "Unit
Assembly Prior to Installation" section
for assembly details.
3) For exterior walls, insulate the enclosure to
the same degree as the rest of the house,
apply vapour barrier and drywall, as per
local installation codes. (Do not insulate
the fireplace itself.)
NOTE:
When using the Premium Flush Front
option, a finishing trim (962mm cover)
needs to be installed to cover the
spacers.
4) The top of the unit must not be closer than
32" (813mm) to the ceiling.
Maintain a physical gap between lining
and spacers 2-5mm. (5mm clearance to
framing each side).
Regency® P36-4 Gas Log Fireplace
8
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
1) Mount Top Facing Support using the 3
supplied screws into the three pre-punched
screw holes on the top front of the unit. Use
hole positionsA, B, or C depending on your
facing depth.
Premium Flush Front
Spacer Installation
UNIT ASSEMBLY
PRIOR TO
Beforetheunitisslidintoposition,installthe
provided spacers to the side of the fireplace
as follows;
INSTALLATION
TheTop Facing Support, the Side Nailing Strips
and the 2 Top Standoffs must be correctly
positioned and attached to the top before unit
is slipped into position.
1) Align the screw locations on spacer with
screw locations on the side of the firebox
and secure in place using 3 screws.
Top Standoff Assembly
2) Repeat for other side.
The top standoffs are shipped in a flat position
and must be folded into shape and attached.
NOTE: The side nailing strips are to be in-
stalled to the spacer after the spacer
is attached to the unit.
1) Remove the standoffs from the fireplace
top.
2) Takeeachstandoffandbendintothecorrect
shape. Bend up at the bend lines until the
screw holes in the standoff and the pre-
punched screw holes on the fireplace top
line up.
3) Attachthestandoffsecurelytothetopwith2
screws per standoff (on opposite corners).
Spacer
"C" Screw Position:
For a facing material depth of 1-1/4"
(32mm), the top facing support must be
reversed.
Left Side Shown
Top Facing Support and
Side Nailing Strips
FLUEING
INTRODUCTION
Determine the total thickness of facing material
(e.g. drywall plus ceramic tiles) to allow the
finished surface to be flush with the front of the
unit. Total facing thickness can vary from 1/2"
(13mm) to 1-1/4" (32mm) thick.
The P36 uses the "balanced flue" technology
Co Axial system. The inner liner flues products
of combustion to the outside while the outer
liner draws outside combustion air into the
combustion chamber thereby eliminating the
needtouseheatedroomairforcombustionand
losing warm room air up the chimney.
2) Use the same screw hole position for the
Side Nailing Strips as was used for the Top
Facing Support. Attach each side nailing
strip using 3 screws.
TheTopFacingSupport&SideNailingStripscan
be mounted in 3 different positions depending
on the thickness of the facing material.
Note: These flue pipes must not be
connected to any other appliance.
Screw
Position
Facing Material
Depth
The gas appliance and flue system must be
flued directly to the outside of the building,
and never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Each Co Axial Flue gas appliance must use
it's own separate flue system. Common flue
systems are prohibited.
A
1/2"
/ 13mm
/ 22mm
/ 32mm
B
7/8"
C*
1-1/4"
* For "C" screw position the top facing support
is reversed.
Regency® P36-4 Gas Log Fireplace
9
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
EXTERIOR FLUE TERMINATION LOCATIONS
Minimum clearances required for balanced flue terminals or
the flue terminals of outdoor appliances
according to AS5601-2004 (AGA gas installation code) or NZS 5261 (New Zealand)
Minimum
Clearance (mm)
a
Below eaves, balconies or other projections:
- Appliances up to 50 MJ/h input
300
500
300
500
1000
500
150
- Appliances over 50 MJ/h input
b
c
d
e
f
From the ground or above a balcony
From a return wall or external corner
From a gas meter (M)
From an electricity meter or fuse box (P)
From a drain or soil pipe
g
Horizontal from any building structure (unless appliance is approved
for closer installation) or obstruction facing a terminal
From any other flue terminal, cowl or combustion air intake
Horizontally from an openable window, door, or non-mechanical air inlet, or
any other opening into a building, with the exception of sub-floor ventilation
(see also Note (I)):
500
500
h
j
- Appliances up to 150 MJ/h input
- Appliances over 150 MJ/h input
500
1500
k
Vertically below an openable window, door, or non-mechanical air inlet,
or any other opening into a building, with the exception of sub-floor ventilation
(see also Note (I)): see table below
Clearance 'k' in mm
Space Heaters
Up to 50 MJ/h
input
All Other Appliances
Up to 50 MJ/h input Over 50 MJ/h input Over 150 MJ/h input
to 150 MJ/h input
150
500
1000
1500
NOTES:
(I) For mechanical air inlets, including spa blowers, the clearance 'j' and 'k' shall be 1500 mm in all cases.
(II) All distances shall be measured vertically or horizontally along the wall to a point in line with the nearest par to of the terminal.
(III) Prohibited area below electricity meter or fuse box extends to ground level.
(IV)A flue terminal of this type shall not be located under a roofed area unless the roofed area is fully open on at least two sides and a free flow
of air at the appliance is achieved.
Regency® P36-4 Gas Log Fireplace
10
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
FLUEING
Regency® Direct Vent System (Flex)
Horizontal Terminations Only
These flueing systems, in combination with the P36 Room Sealed Gas Fireplace, have been tested and listed as a Direct Vent type flue system
by the Australian Gas Association. The location of the termination cap must conform to the requirements in the Flue Terminal Locations diagram in
section "Exterior Flue Termination Locations."
Regency® Direct Vent (Flex) System Termination Kit (Part # 946-515) includes all the parts needed to install the P36 with a maximum run
of 1200mm.
1) 175mm dia. flexible liner (1200mm length)
2) 100mm dia. flexible liner (1200mm length)
3) spring spacers (4)
4) thimble (2)
Wall Thimble
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point, Stainless
Steel (4)
AstroCap
Termination Cap
(Part# 946-578/P)
(patented)
4" (102mm)
dia. flue pipe
If longer runs are needed, the Regency® Direct
Vent system (Flex) # 946-516 includes all the
parts needed to install the P36 with a maximum
3.0m run.
6-7/8"
(173mm)
dia. Flue pipe
spring spacer
1) 175mm dia. flexible liner (3.0m length)
2) 100mm dia. flexible liner (3.0m length)
3) spring spacers (7)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point, Stainless
Steel (4)
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency® may be used for Flex installations.
3) If you are installing the P36 into a Regency® Mantel Kit, use the minimum horizontal vent height (centre-line of 1029mm). Remember
to include the mantel base in your calculations and to maintain the 32mm clearance (38mm with Flex) to the underside of the mantel
top.
Regency® P36-4 Gas Log Fireplace
11
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
SIMPSON DURA-VENT FLUEING
Horizontal or Vertical Terminations
The Simpson Dura-Vent Co Axial Flue System offers a complete line of component parts for installation of both horizontal and vertical installations.
Many items are offered in decorative black, as well as galvanized finish. We recommend using the galvanized finish for installation with the P36.
The minimum components required for a basic
horizontal termination are:
If a Vinyl Siding Standoff is required (it must
be used with vinyl siding), measure to outside
surface of wall without siding and add 2
inches.
Wall thickness is measured from the back
standoffs to the inside mounting surface of
terminationcap.Forsidingotherthanvinylfurring
strips may be used, instead of the vinyl siding
standoff, to create a level surface to mount the
flueterminal.TheTerminalmustnotberecessed
intosiding.Measurethewallthicknessincluding
furring strips.
1
1
1
1
1
Horizontal Termination Cap
90o Elbow
Flue Adaptor
Wall Thimble
Length of pipe to suit wall thickness
(see chart)
Flat Wall Installation
Wall Thickness
(inches)
Vent Length Required
(inches)
4" - 5-1/2"
7" - 8-1/2"
10" - 1-1/2"
9" - 14-1/2"
15" - 23-1/2"
6"
9"
12"
11" - 14-5/8" Adj. Pipe
17" - 24" Adj.
Corner Installation
Wall Thickness
(inches)
Vent Length Required
(inches)
3-1/4" - 6-3/4"
7-3/4" - 16-1/4"
7-1/4" - 8-3/4"
11" - 14-5/8" Adj. Pipe
17" - 24" Adj. Pipe
6" + 12"
9" + 9"
4-1/4" - 5-3/4"
6" + 9"
Simpson Dura-Vent
Co-Axial Flue GS
SIMPSON DURA-VENT FLUEING COMPONENTS LIST
All Simpson Dura-Vent components are available directly from Regency®.
Part # Description
Part # Description
Part # Description
Horiz. Termination Kit includes: 90o
902B 48" Pipe Length - Black
911B 11"-14 5/8" Adjustable Pipe Length
- Black
940
941
Wall Thimble - Support/Box
Cathedral/Ceiling - Support/Box
971
black elbow, wall thimble cover, horiz. square
termination cap, 24" black pipe, and 11" -14"
5/8" adjustable black pipe.
3951 Brass Trim for Wall Thimble/Ceiling
Sup.
917B 17"- 24" Adjustable Length - Black
45O Elbow - Galv.
963
943
Firestop Spacer
970
Basic Horiz. Termination. Kit includes:
90o blackelbow,wallthimblecover,horiz.
square termination cap.
Vert. Termination Kit includes 0/12 -
6/12 pitch adjustable flashing, storm
collar, low profile term. cap.
945
945B 45O Elbow - Black
Flashing 0/12-6/12
945G 45O Elbow - Swivel - Galv.
945BG 45O Elbow - Swivel - Black
943S Flashing 7/12-12/12
953
950
988
942
Storm Collar
978
90O Elbow - Galv.
Vinyl Siding Standoff
Wall Strap
990
990B 90O Elbow - Black
990G 90O Elbow - Swivel - Galv.
990BG 90O Elbow - Swivel - Black
Wall Thimble
908B 6" Pipe Length - Black
907B 9" Pipe Length - Black
906
Parts not supplied by Dura-Vent
12" Pipe Length - Galv.
991
980
984
985
High Wind Termination Cap (Vertical)
Vertical Termination Cap
946-506/P
510-994
640-530/P
946-205
Flue Guard (Optional)
Dura-Vent Flue Adaptor
Riser Flue Terminal
VinylSidingShieldforRiserFlue
Terminal
906B 12" Pipe Length - Black
904 24" Pipe Length - Galv.
904B 24" Pipe Length - Black
903 36" Pipe Length - Galv.
Horizontal Square Termination Cap
Horiz. Square High Wind
Termination Cap
Snorkel - 14" Rise Termination Cap
Snorkel - 36" Rise Termination Cap
903B 36" Pipe Length - Black
982
981
902
48" Pipe Length - Galv.
Regency® P36-4 Gas Log Fireplace
12
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
FLUEING ARRANGEMENTS - HORIZONTAL TERMINATIONS
SIMPSON DURA-VENT DIRECT VENT GS SYSTEM and
REGENCY® DIRECT VENT SYSTEM (FLEX)
(LPG & NG)
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o elbow (two 45o elbows equal
one 90o elbow).
Note: Must use optional flue adapter (Part # 510-994) when using Simpson Dura-Vent pipe.
Simpson Dura-Vent
4" (102mm) inner diameter
6-5/8" (168mm) outer diameter
Regency® Flex Vent
4" (102mm) inner diameter
6-7/8" (175mm) outer diameter
Aflueguardshouldbeusedwhenever
the termination is lower than the
specified minimum or as per local
codes.
Note: Regency® Co Axial Flue System
(Flex) is only approved for
horizontal terminations.
•
•
•
Maintain clearances to combustibles as listed in section "Clearances."
Horizontal flue must be supported every 3 feet (0.9 meters).
Firestops are required at each floor level and whenever passing through a wall.
Regency® P36-4 Gas Log Fireplace
13
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
FLUEING ARRANGEMENTS - HORIZONTAL TERMINATIONS
SIMPSON DURA-VENT DIRECT FLUE GS SYSTEM and
REGENCY® CO AXIAL FLUE SYSTEM (FLEX)
(LPG & NG)
The diagram below shows examples of horizontal termination arrangements using two 90o elbows (two 45o elbows equal one 90o elbow).
Note:
1) A maximum of two 90o elbows are permitted.
2) A minimum of 6 ft. (1.8m) vertical from base of unit is required if two 90o elbows are used.
3) Minimum distance between elbows is 2 ft. (0.6m).
4) Determine the permitted range of horizontal termination arrangements by using chart in section "Simpson Dura-vent
Flueing." and deducting 3 ft. (0.9m) from the maximum horizontal distance for the second 90o elbow.
Iflength"B"isincreased,length"A"mustbe
decreased by a corresponding amount.
Simpson Dura-Vent
4" inner diameter
6-5/8" outer diameter
A flue guard should be used whenever the
termination is lower than the specified minimum
or as per local codes.
•
•
•
Maintain clearances to combustibles as listed in section "Clearances."
Horizontal flue must be supported every 3 feet (0.9 meters).
Firestops are required at each floor level and whenever passing through a wall.
Regency® P36-4 Gas Log Fireplace
14
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
FLUEING ARRANGEMENTS - VERTICAL TERMINATIONS
SIMPSON DURA-VENT CO AXIAL FLUE GS SYSTEM (LPG & NG)
The P36 is approved for a 23 ft. (7.0m) vertical, with a maximum 12 ft. (3.7m) horizontal offset
using two 90o elbows (two 45o elbows equal one 90o elbow) with Simpson Dura-Vent Co Axial
Flue GS flue systems for LPG and NG, as per diagram 1.
The P36 is approved for a 37 ft. (11.3m) straight vertical, including a 20" (0.5m) horizontal offset
using two 90o elbow (two 45o elbows equal one 90o elbow) with Simpson Dura-Vent Co Axial
Flue GS flue systems for LPG and NG, as per the diagram 2.
•
•
Flue must be supported at offsets
Maintain clearances to combustibles as listed in section "Clearances."
Note: Must use optional flue adapter when using Simpson Dura-Vent pipe
(Part # 510-994).
Note: Regency® Co Axial Flue System (Flex) is only approved for horizontal
terminations.
Diagram 2
Diagram 1
Regency® P36-4 Gas Log Fireplace
15
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
The P36 is approved for a 37 ft. (11.3m) straight vertical, with Simpson
Dura-Vent Co Axial Flue GS flue systems for LPG and NG, as per the
diagram 3.
The shaded area in the diagram 3 shows all allowable combinations of
straight vertical and offset to vertical terminations with Simpson Dura-
Vent Co Axial Flue GS flue systems for LPG and NG. Maximum two
45o elbows allowed.
•
•
Flue must be supported at offsets
Firestops are required at each floor level and whenever passing
through a wall.
•
Maintain clearances to combustibles as listed in section
"Clearances."
Diagram 3
Regency® P36-4 Gas Log Fireplace
16
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
b) Horizontalrunsoffluemustbesupported
everythreefeet.Wallstrapsareavailable
for this purpose.
HORIZONTAL
TERMINATIONS
5) Markthewallfora10"x10" squarehole.The
center of the square hole should line up with
thecenterlineofthehorizontalpipe.Cutand
frame the 10 inch square hole in the exterior
wall where the flue will be terminated. If the
wall being penetrated is constructed of non-
combustible material, i.e. masonry block or
concrete,a7"(178mm)dia.(7-1/2"(191mm)
dia. for flex) hole is acceptable.
Install the flue system according to the
manufacturer's instructions included with
the components.
1) Set the unit in its desired location. Check
to determine if wall studs or roof rafters
are in the way when the flueing system is
attached. If this is the case, you may want
to adjust the location of the unit. Rough in
the gas preferably on the right side of the
unit and the electrical (junction block is on
the left side) on the left.
Diagram 3
Note: With
Dura-Vent,
theminimum
height is
achieved by
installing a
90o elbow
directlytothe
flue adaptor.
8) Slide the appliance and flue assembly
towards the wall carefully inserting the
flue pipe into the flue cap assembly. It is
important that the flue pipe extends into
the flue cap sufficient distance so as to
result in a minimum pipe overlap of 1-1/4
inches. Securetheconnectionbetweenthe
flue pipe and the flue cap by attaching the
two sheet metal strips extending from the
flue cap assembly into the outer wall of the
flue pipe. Use the two sheet metal screws
provided to connect the strips to the pipe
section. See Diagram 4.
2) CoAxial Flue pipe and fittings are designed
with special twist-lock connections to
connect the flueing system to the appliance
flue outlet. A twist-lock appliance adaptor
is an available option that must be used in
conjunctionwiththeSimpsonDura-VentCo
Axial Flue GS system.
3) Put a bead of silicone inside the outer
section of the adapter and a bead of Stove
Mate on the inner collar. Slip the adapter
over the existing inner and outer flue collar
and fasten to the outer collar only with the
3 supplied screws (drilling pilot holes will
make this easier). Level the fireplace and
fasten it to the framing using nails or screws
through the nailing strips.
Diagram 2
Note:
9) Install wall thimble in the center of the
10" square and attach with wood screws
(Diagram 5).
a) The horizontal run of flue must be level,
or have a 1/4 inch rise for every 1 foot
of run towards the termination. Never
allow the flue to run downward. This
couldcausehightemperaturesandmay
present the possibility of a fire.
4) Assemble the desired combination of pipe
and elbows to the appliance adaptor and
twist-lock for a solid connection.
Note:
b) The location of the horizontal flue
terminationonanexteriorwallmustmeet
all local and national building codes,
and must not be blocked or obstructed.
For External Flue Terminal Locations,
see diagram in section "Exterior Flue
Termination Locations."
a) Twist-lockprocedure:Fourindentations,
locatedon thefemaleendsofpipesand
fittings, are designed to slide straight
onto the male ends of adjacent pipes
and fittings, by orienting the four pipe
indentations so they match and slide
in to the four entry slots on the male
ends,Diagram1.Pushthepipesections
completely together, then twist-lock
one section clockwise approximately
one-quarter turn, until the two sections
arefullylocked.Thefemalelockinglugs
will not be visible from the outside, on
the Black Pipe or fittings. They may be
located by examining the inside of the
female ends.
6) The arrow on the flue cap should
be pointing up. Insure that the 1-1/2"
clearances to combustible materials are
maintained. Install the termination cap,
diagram 5.
Diagram 4
The four wood screws provided should
be replaced with appropriate fasteners for
stucco, brick, concrete, or other types of
sidings.
Note: If installing termination on a siding
covered wall, a vinyl siding standoff
or furring strips must be used to
ensure that the termination is not
recessed into the siding.
Diagram 1
7) Before connecting the horizontal run of
flue pipe to the flue termination, slide the
Wall Thimble (Part # 620-926) over the flue
pipe.
Diagram 5
Note: Applysealant"Mill-Pac"toinnerpipe
andhightemperaturesiliconesealant
to outer pipe on every
twist-lock joint.
Regency® P36-4 Gas Log Fireplace
17
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
VERTICAL
Roof Pitch
Minimum Flue Height
Feet
2
2
Meters
0.61
0.61
0.61
0.76
0.99
1.22
1.52
1.83
2.13
2.29
2.44
TERMINATIONS
flat to 7/12
1) Maintain the 1-1/4"
clearances (air spaces)
to combustibles when
passing through ceilings,
walls, roofs, enclosures,
attic rafter, or other nearby
combustible surfaces.
Do not pack air spaces
with insulation. Check
section "Simpson Dura-
vent Flueing" for the
maximum vertical rise of
the flueing system and the
maximum horizontal offset
limitations.
over 7/12 to 8/12
over 8/12 to 9/12
over 9/12 to 10/12
over 10/12 to 11/12
over 11/12 to 12/12
over 12/12 to 14/12
over 14/12 to 16/12
over 16/12 to 18/12
over 18/12 to 20/12
over 20/12 to 21/12
2
2.5
3.25
4
5
6
7
7.5
8
Diagram 3
4) Assemble the desired lengths of pipe and
elbows. Ensure that all pipes and elbow
connections are in the fully twist-locked
position and sealed.
Galvanizedpipeisdesirableabovetheroofline
duetoitshighercorrosionresistance.Continue
to add pipe sections through the flashing until
the height of the flue cap meets the minimum
heightrequirementsspecifiedinDiagram5or
local codes. Note that for steep roof pitches,
the vertical height must be increased. A poor
draft, or down drafting can result from high
wind conditions near big trees or adjoining
roof lines, in these cases, increasing the flue
height may solve the problem.
5) Cut a hole in the roof centered on the small
drilled hole placed in the roof in Step 2. The
hole should be of sufficient size to meet
the minimum requirements for clearance
to combustibles of 1-1/2". Slip the flashing
undertheshingles(shinglesshouldoverlap
half the flashing) as per Diagram 4.
Diagram 1
2) Setthegasapplianceinitsdesiredlocation.
Dropaplumbbobdownfromtheceilingtothe
position of the appliance flue exit, and mark
the location where the flue will penetrate
the ceiling. Drill
a small hole at
his point. Next,
drop a plumb
bob from the
7) Ensure flue is vertical and secure the base
of the flashing to the roof with roofing rails,
slide storm collar over the pipe section and
seal with a mastic.
roof to the hole
previouslydrilled
in the ceiling,
and mark the
spot where
8) Install the vertical termination cap by twist-
the flue will
locking it.
penetrate the
roof. Determine
Note: Anyclosetsorstoragespaces,which
the flue passes through must be
enclosed.
if ceiling joists,
roof rafters or
other framing
will obstruct the
Diagram 4: The upper half of the flashing is
installed under the roofing material and not
nailed down until the chimney is installed.
This allows for small adjustments.
Diagram 2
flueing system. You
may wish to relocate the appliance or to
offset,asshowninDiagram2toavoidcutting
load bearing members.
Offset Chart
6) Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic
to avoid obstructions, it is important
to support the flue pipe every 3 feet,
to avoid excessive stress on the
elbows, and possible separation.
Wall straps are available for this
purpose (Diagram 2).
Note: Apply sealant "Mill-Pac" to inner
pipe and high temperature silicone
sealant to outer pipe on every twist-
lock joint.
3) A Firestop spacer must be installed in the
floor or ceiling of every level. To install the
Firestop spacer in a flat ceiling or wall,
cut a 10 inch square hole. Frame the hole
as shown in Diagram 3 and install the
firestop.
Diagram 5
Regency® P36-4 Gas Log Fireplace
18
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Conversion Kit #513-968 from NG to LPG
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !!
8) Remove burner orifice with a 1/2" wrench.
WARNING!
Do not over tighten the screw.
Recommended to
Conversion Kit Contains:
Use another wrench to hold on to the elbow
behind the orifice. Discard orifice.
Qty.
Part #
Description
1
910-037
LPG Injector
(Pilot Orifice)
grip the wrench by the short side.
1
1
904-390
918-590
Burner Orifice #52
Decal "Converted
to LPG"
16) Verify that if the conversion is from NG to
LPG, the screw must be re-assembled with
the red o-ring visible (Fig. 5).
1
1
1
908-528
904-529
918-546
Red "LPG" label
5/32" Allen Key
Instruction Sheet
LPG Configuration
Red o-ring visible
1) Shut off the gas supply.
Burner Orifice
2) Remove the louvers (and bay door if it is
installed).
9) Reinstall new burner orifice LPG stamped
#52 and tighten.
3) Open the flush door and remove the door.
4) Remove the logs and embers (if used).
5) Remove the 2 screws holding the Burner
10) Turn control knob to the “OFF” position.
Fig.5
11) Remove the black
protection cap by hand
from the hi-low knob
(Fig.1).
Assembly to the firebox base. Push the
Burner Assembly to the left and lift out.
17) Re-assemble the
black protection cap
(Fig. 6).
18) Reverse step 2).
Fig. 1
Fig. 6
12) Inserta5/32”or4mmAllen
wrenchintothehexagonal
key-way of the screw
(Fig. 2), rotate it counter-
clockwiseuntilitisfreeand
extract it.
Remove the 2 screws, push Burner Assembly
to the left and lift out.
WARNING!
Also check that the pilot and main
burner injectors are appropriate for
the gas type.
6) Pull off the pilot cap to expose the pilot
orifice.
Fig.2
13) Check that the screw is
clean and if necessary
remove dirt.
19) Attach clear label "This unit has been
converted to LPG" near or on the serial
# decal.
14) Flip the screw (Fig. 3).
20) Replace yellow "NG" label with red "LPG"
label.
21) Check for gas leaks.
7) Unscrew the pilot orifice with the allen key;
then replace with the LPG pilot orifice and
the pilot cap, provided in the kit.
22) Check inlet and outlet pressures.
23) Check operation of flame control.
Fig.3
15) Using the Allen wrench as
shown in Fig.4, rotate the
screwclockwiseuntilsnug,
do not overtighten.
24) Check for proper flame appearance and
glow on logs.
Fig.4
Regency® P36-4 Gas Log Fireplace
19
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
GAS LINE
PILOT ADJUSTMENT
P36-NG System Data
INSTALLATION
Periodically check the pilot flames. Correct
flame pattern has three strong blue flames:
1 flowing around the thermopile, 1 around
the thermocouple and 1 flowing across the
burner (it does not have to be touching the
burner).
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes: #37( 2.65mm)
The gas line can be brought through either the
right or the left side of the appliance. The gas
valve is situated on the right hand side of the
unit and the gas inlet is on the right hand side
of the valve.
Max. Input Rating 33 mj
Min. Input Rating 20 mj
Supply Pressure
min.1.25 kPa
Note: Ifyouhaveanincorrectflamepattern,
contact your Regency® dealer for
further instructions.
Note: If the gas line is being installed from
the left side, be sure to leave room to
accommodate servicing of the fan.
Manifold Pressure
(High)
0.9 kPa
Electrical: 240 V A.C. System.
Circulation Fan: variable speed 130 CFM.
Log Set: Ceramic fibre, 7 per set.
Flue System: Simpson Dura-Vent Direct
Flue System or Regency® Direct
Flue System (Flex)
The gas line connection may be made of
rigid pipe, copper pipe or an approved flex
connector. (If you are using rigid pipe, ensure
that the valve can be removed for servicing.)
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the AS5601-2004 or NZS 5261
installation code.
P36-LPG System Data
For 0 to 2000 feet altitude
Incorrect flame pattern will have small,
probably yellow flames, not coming into
proper contact with the rear burner or
thermopile or thermocouple.
When using copper or flex connectors use only
approved fittings. Always provide a union so
that gas lines can be easily disconnected for
servicing. Flare nuts for copper lines and flex
connectors are usually considered to meet this
requirement.
Burner Inlet Orifice Sizes: #52 (1.6 mm)
Max. Input Rating 31 mj
Min. Input Rating 18 mj
Important:Alwayscheckforgasleakswitha
soapandwatersolutionorgasleakdetector.
Do not use open flame for leak testing.
For 0 to 4500 feet Altitude:
Supply Pressure
min 2.75 kPa
Manifold Pressure
(High)
AERATION
2.7 kPa
ADJUSTMENT
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect piping from valve at
pressures over 3.45 kPa.
Electrical: 240 V A.C. System.
Circulation Fan: variable speed 130 CFM.
Log Set: Ceramic fibre, 7 per set.
Flue System: Simpson Dura-Vent Co Axial
Flue System
The air shutter can be adjusted by moving the
adjusting wire up or down. The wire is accessed
throughthebottomlouvreopening.Opentheair
shutter for a blue flame or close for a yellower
flame. The burner aeration is factory set but
may need adjusting due to either the local gas
supply or altitude. This adjustment is performed
by the gas fitter.
Minimum Air Shutter Opening:
The manifold pressure is controlled by a
regulator built into the gas control, and should
be checked at the pressure test point.
8 mm
NG
Full Open LPG
CAUTION:Carbonwillbeproducedifairshutter
Note: To properly check gas pressure, both
inlet and manifold pressures should
becheckedusingthevalvepressure
ports on the valve.
is closed too much.
Note: Any damage due to carboning
resulting from improperly setting
the aeration controls is NOT covered
under warranty.
1) Make sure the valve is in the "OFF"
position.
2) Loosen the "IN" and/or "OUT" pressure
tap(s), turning counterclockwise with a
1/8" wide flat screwdriver.
Closed - Tall yellow
Open - Short Blue
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
Regency® P36-4 Gas Log Fireplace
20
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
4) Light the pilot and turn the valve to "ON"
OPTIONAL
LOG SET
position.
BRICK PANELS
INSTALLATION
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits specified on the safety
label.
1) Undo the bottom 2 door latches and open
Read the instructions below carefully and
refer to the diagrams. If logs are broken
do not use the unit until they are replaced.
Broken logs can interfere with the pilot
operation.
and remove glass door. Remove logs.
Note: The logs must not be in the unit.
6) When finished reading manometer, turn
off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8" flat
screwdriver.Note:Screwshouldbesnug,
but do not over tighten.
2) Insert the back brick panel first by carefully
slipping it between the back wall of the
firebox and the rear log bracket.
The gas log kit (Part # 512-930) contains the
following pieces:
a) 02-49 Rear Log
b) 02-55 Middle Left Log
c) 02-50 Front Left Log
d) 02-53 Center Left Log
e) 02-51 Front Bottom Log
f) 02-54 Center Right Log
g) 02-52 Middle Right Log
S.I.T. VALVE DESCRIPTION
1) Gas on/off knob
2) Manual high/low adjustment
3) Pilot Adjustment
3) Put the side panels in next. Slide them in
from the front and push them flat up against
the wall. Be very careful not to scratch them
on the firebox hardware.
h)
i)
Embers
902-156
902-179
4) Thermocouple Connection - option
5) Outlet Pressure Tap
6) Inlet Pressure Tap
Vermiculite
7) Pilot Outlet
8) Main Gas Outlet
9) Alternative TC Connection Point
4) Install the 2 brick retaining clips, one on
each side.
The "02" refer numbers (i.e. 02-49) are
molded into the rear of each log.
NOTE: If you will be installing the optional
Brick Panels, install the Brick Panels
prior to installing the logs.
1) Carefully remove the logs from the box and
unwrap them. The logs are fragile, handle
with care - do not force into position.
2) Sprinkle the vermiculite around the firebox
base.
Vermiculite
Vermiculite
Vermiculite
3) Place the Log 02-49 on the rear log support
pins with the flat side to the back.
Regency® P36-4 Gas Log Fireplace
21
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
8) Position Log 02-54 across the cutouts in
Logs 02-51 and 02-53. The notch in the
bottom right end fitting against the 5th grate
tab.
02-49
02-49
02-53
02-51
02-54
6) Place the bottom left front edge of Log
02-55againsttherearbracketontheburner
tray and rest the log on the cutout on
Log 02-53.
02-51
02-49
5th Grate Tab
02-55
4) Place Log 02-51 on the front right side of
the burner. Push the back of the log against
the 2 brackets with the notch on the bottom
right side of the log fitting into the right side
of the grate.
02-49
02-55
02-51
02-53
02-50
02-51
02-54
02-51
Rear Bracket
9) Place Log 02-52 between Logs 02-51 and
02-49 and on the indentation on Log 02-54.
The bottom right end sits behind the rear
grate tab.
7) Sit Log 02-50 on the front left side of the
burner. Push the back of the log against the
2frontbracketswiththenotchonthebottom
of the log fitting into the first grate tab.
02-55
Bracket
Bracket
Notch
02-49
02-52
02-50
02-49
02-53
02-51
02-51
02-54
Front Brackets
Log indentation
5) Position Log 02-53 across the cutouts in
Logs 02-49 and 02-51 with the notch on the
left side of the log fitting into the 2nd grate
tab.
02-55
02-53
02-52
02-50
02-53
Rear
Grate
02-49
02-51
02-54
Tab
Photo shows rear grate tab.
Log 02-51 was removed to show
the positioning of Log 02-52.
Notch
2nd Grate Tab
Cutouts
Regency® P36-4 Gas Log Fireplace
22
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
10) Place the embers on the front of the burner
tray in the places shown on the photo.
02-49
02-55
02-52
02-50
02-51
Place embers in these 3 locations
on the burner tray.
02-54
11) Test fire to ensure proper light off (make sure flame flows smoothly from one end of burner
to the other). If there is any flame hesitation, check that area for any blockage of the burner
ports.
Embers
STANDARD FLUSH DOOR
Use the hook to pull the spring out until you
The standard flush door comes with a black
frame. To install the frame, simply hook the top
door flange onto the top of the unit and swing
the door towards the unit, diagram 1.
Flush Louvres
can put the hook into the slot on the bottom
door bracket. Repeat for 2nd spring. See
diagram 3.
1) Install the top louvre by sliding the two
bracket clips into the brackets located
underneath the top of the firebox.
2) The bottom louvre has a hinge that is
attached (2 screws per hinge) to the lip on
bottom of the unit.
Diagram 3
Diagram 1
To remove the flush door, reverse the above
steps.
Optional
Flush Trim
Attach the round
magnets to the
back of the top trim
piece and to the
bottom trim piece,
then attach trim to
the top and bottom
of Flush door.
Be careful that the glass gasket does not roll up;
there must be a gap between the gasket and
the door lip to ensure that the door sits securely
on the unit. Diagram 2.
Note: Top and bottom louvres are
different.
Diagram 2
Regency® P36-4 Gas Log Fireplace
23
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
PREMIUM FLUSH FRONT INSTALLATION
1) Unplug the power source.
6) Remove the manual control switch bracket by undoing the 2
screws.
2) Remove the top louver (if fitted) by carefully pulling it out.
3) Install the premium flush front top louver in place by sliding the louver
tabs into the louver brackets on the inside top of the firebox.
Louver Tab
7) Remove the burner ON/OFF switch from the bracket using a pair
of pliers and remove the 2 screws that secure the 2 wires on the
valve.
Burner ON/OFF
Switch
Premium Flush Front Top Louver in place.
Valve
4) Open the bottom louver.
5) Remove the bottom louver (if fitted) by undoing the 2 screws which
8) Install the new ON/OFF switch to the manual control switch
secure the louver to the hinges on the left and right side.
bracket.
Regency® P36-4 Gas Log Fireplace
24
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
12) Place the wire grommet back into the thermodisc cover with the 2
9) Connect the female connecter on the white wire to the TH terminal
female ends of the wires inside the cover as shown.
of the valve.
10) Remove the thermodisc cover from the thermodisc plate by undoing
the 2 screws and then remove the wire grommet.
13) Connect the female ends of the red and white wires to the thermo-
disc.
Thermodisc Plate
Thermodisc Cover
Grommet
14) Reattach the thermodisc plate to the thermodisc cover using the 2
screws removed in step 10.
11) Take the white wire from the kit and the red wire from the burner
ON/OFF switch and place the grommet thru the wires.
Regency® P36-4 Gas Log Fireplace
25
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
15) Connect the thermodisc wire harness to the new valve/module wire
22) Install the wire cover by fitting the 3 clips onto the flange at the front
harness. Refer to the wiring diagram on next page for details.
of the firebox. See note below for P36 units.
16) Mountthethermodiscbrackettotheadjustablebracketusing2screws.
Important: Thermodisc location is crucial, check the data badge to
identify unit and secure to screw location accordingly.
Wire Cover
17) Remove the left side bottom hinge bracket by undoing the 2
screws.
Firebox Flange
18) Install the supplied hinge to the hinge bracket using 2 screws.
19) Slide the adjustable bracket to the bottom left corner and secure in
place using the 2 screw holes on the firebox flange.
One clip shown in place
on firebox flange.
NOTE - P36 UNITS ONLY:
For the wire cover to fit in place on the P36 the top half of the wire
cover will need to be broken off by bending back and forth.
Bend Here
20) Secure loose wires using wire clips to the base of the firebox as far
back as possible.
21) Place the manual control bracket back into it's original location and
secure using 2 screws.
23) Align the bottom louver mounting tab with hinges on the left and right
side and secure using 2 screws on each side.
24) Plug in power source.
25) Close the bottom louver.
NOTE:
The fan must run at minimum speed to prevent the unit from overheating
which will cause automatic shutdown via the thermodisc safety switch.
Regency® P36-4 Gas Log Fireplace
26
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Option 1:
Option 2:
Option 3:
WALL SWITCH
REMOTE CONTROL
WALL THERMOSTAT
1) Run supplied 15' of wire through the right UsetheRegency® RemoteControlKit approved A wall thermostat may be installed if desired,
or left side gas inlet opening. Be careful not for this unit. Use of other systems may void
to damage wire. your warranty.
connect the wires as per the wiring diagram.
Use chart below to determine the maximum
wire length.
Note: We recommend a maximum of 15' The remote control kit comes with a hand held
of wire but if you wish to go with a transmitter, a receiver and a wall mounting
longer run, use the Thermostat Wire plate.
Note: Preferable if the thermostat is
installed on an interior wall.
Table.
1) Choose a convenient location on the wall
2) Connect wire to supplied wall switch and
to install the receiver and the receptacle
box (protection from extreme heat is very
important). Run wires from the fireplace to
that location. Use Thermostat Wire Table.
Regency® offers a programmable thermostat
but any CSA, UCL or UL approved millivolt
thermostat, 250-750 millivolt rated non-
anticipator type thermostat may be used.
install into the receptacle box.
CAUTION
Do not connect millivolt
2) Connect the two wires to the gas valve. See
CAUTION
wall switch wires for gas
appliance to a 240V power supply.
diagram below.
Do not connect millivolt
wall thermostat wires for
gas appliance to a
CAUTION
Do not connect millivolt
remote control wires for
gas appliance to a
240V power supply.
240V power supply.
Thermostat Wire Table
3) Install a 9V alkaline battery in both the
receiver and the transmitter. Install the
receiver and its cover in the wall. Switch the
hand held remote transmitter to "remote"
mode. The remote control is now ready for
operation.
Recommended Maximum Lead Length
(Two-Wire) When Using Wall
Thermostat (CP-2 System)
Wire Size
Max. Length
14 GA.
16 GA.
18 GA.
20 GA.
22 GA.
15.24 m
9.75 m
6.10 m
3.66 m
2.71 m
Regency® P36-4 Gas Log Fireplace
27
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
WIRING
This heater does not require a 240VA.C. supply
forthegascontroltooperate.A240VA.C.power
supply is needed for the fan/blower operation.
Caution: Ensure that the wires do
not touch any hot surfaces and are
away from sharp edges.
CAUTION: Label all wires prior
to disconnection when servicing
controls. Wiring errors can
cause improper and dangerous
operation.
STANDARD WIRING
WARNING: Electrical Grounding Instructions
This appliance is equipped with a three pronged (grounding) plug for your
protectionagainstshockhazardandshouldbepluggeddirectlyintoaproperly
grounded three-prong receptacle. Do not cut or remove the grounding prong
from this plug.
Regency® P36-4 Gas Log Fireplace
28
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
WIRING WITH PREMIUM FLUSH FRONT OPTION
Regency® P36-4 Gas Log Fireplace
29
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING INSTRUCTIONS
7) Slide the thermodisc into the bracket clip
OPERATING
INSTRUCTIONS
OPTIONAL
FAN
on the underside of the firebox.
8) Connect black wire from fan to the
thermodisc.
240 Volt AC power is needed for the fan switch
andblower.Thefancanbehardwiredifdesired.
Aterminalblockisprovidedonthelefthandside
of the unit. A three wire power cord can also be
used and plugged into a suitable receptacle.
1) Read and understand these instructions
before operating this appliance.
2) Check to see that all wiring is correct and
enclosed to prevent possible shock.
Unit must be grounded at all times. Do
not cut the ground terminal off under any
circumstances.
3) Check to ensure there are no gas leaks.
4) Make sure the glass in the door frame is
properly positioned. Never operate the
appliance with the glass removed.
1) Shut the power off.
9) Connect fan ground cable to ground lug.
2) Open the bottom louvre door.
3) Remove the terminal block cover.
5) Verify that the flueing and cap are
Refer to wiring diagram.
unobstructed.
10) Attach the ground wire to the stove (ground
6) Ensure that the brick panels are installed.
lug provided).
4) Slide the fan in towards the rear of the unit
and slip it over the two mounting studs.
Ensure that the fan blades do not rub
against the valve tubing.
7) Verify log placement. If the pilot cannot be
seen when lighting the unit, the logs have
been incorrectly positioned.
11) Attachblackwirefromthermodisctoterminal
block.
12) Hard wire into terminal block and to fan
8) The unit should never be turned off, and on
again without a minimum of a 60 second
wait.
speed controller. Wires not supplied.
Note: A 240 Volt AC power cord can be
installed at rough-in stage so that
the power is available. A three wire
power cord can be used.
13) Attach the terminal block cover. If the left
springwasunhookedinstep4),hookitback
into the bracket.
To Remove the Fan
1) Shut the power off.
2) Reverse the above instructions.
Note: The bearings are lubricated for life.
Do not lubricate them. Make sure
you vacuum the fan area on a regular
basis.
Optional: If you require extra space to slide
the fan to the back, the left spring can be
unhooked from the bracket.
IMPORTANT:
5) Wire the fan to the terminal block as shown
These fans collect a lot of dust from within
your home. Ensure you maintain these fan
motors on a regular basis by vacuuming
out the fan blades and housing using a soft
brush nozzle.
in the wiring diagram below.
6) Connect white wire from fan to neutral of
terminal block.
Regency® P36-4 Gas Log Fireplace
30
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING INSTRUCTIONS
NORMAL OPERATING
SOUNDS OF GAS
APPLIANCES
It is possible that you will hear some sounds
fromyourgasappliance.Thisisperfectlynormal
due to the fact that there are various gauges
and types of steel used within your appliance.
Listedbelowaresomeexamples.Allarenormal
operatingsoundsandshouldnotbeconsidered
as defects in your appliance.
LIGHTING
FIRST FIRE
PROCEDURE
The first fire in your stove is part of the paint
curing process. To ensure that the paint is
properlycured, itisrecommendedthatyouburn
your fireplace for at least four (4) hours the first
time you use it with the fan on.
1) Push in gas control knob slightly and turn to
“PILOT” position.
2) Push in control knob all the way and hold in
until the pilot lights up. Continue to hold the
control knob in for about 20 seconds after the
pilot is lit. Release knob.
Whenfirstoperated,theunitwillreleaseanodour
caused by the curing of the paint, the burning
off of any oils remaining from manufacturing.
Smoke detectors in the house may go off at
this time. Open a few windows to ventilate the
room for a couple of hours.
3) Push in gas control knob slightly and
turn to "ON" position.
Blower:
Regency® gasappliancesusehightechblowers
to push heated air farther into the room. It is not
unusual for the fan to make a "whirring" sound
when ON. This sound will increase or decrease
in volume depending on the speed setting of
your fan speed control.
4) Turn ON the flame switch.
The glass panel may require cleaning after the
unit has cooled down.
DO NOT ATTEMPT TO CLEAN THE
GLASS WHILE IT IS HOT.
Gas Inlet
Burner Tray:
Note: When the glass is cold and the
appliance is lit, it may cause
condensation and fog the glass.
This condensation is normal and
will disappear in a few minutes as
the glass heats up.
The burner tray is positioned directly under the
burnertube(s)andlogsandismadeofadifferent
gauge material from the rest of the firebox and
body.Therefore,thevaryingthicknessesofsteel
will expand and contract at slightly different
rates which can cause "ticking" and "cracking"
sounds. You should also be aware that as there
are temperature changes within the unit these
sounds will likely re-occur. Again, this is normal
for steel fireboxes.
SHUTDOWN
PROCEDURE
DO NOT BURN THE APPLIANCE
WITHOUT THE GLASS FRONT IN
PLACE.
1) Turn OFF the flame switch.
Blower Thermodisc:
When this thermally activated switch turns ON
it will create a small "clicking" sound. This is the
switch contacts closing and is normal.
2) Push in gas control knob slightly and turn to
"OFF" position.
During the first few fires, a white film
may develop on the glass front as part
of the curing process. The glass should
be cleaned or the film will bake on and
become very difficult to remove. Use a
non-abrasive cleaner and NEVER clean
the glass while it is hot.
Pilot Flame:
While the pilot flame is on it can make a very
slight "whisper" sound.
Gas Control Valve:
As the gas control valve turns ON and OFF, a
dullclickingsoundmaybeaudible,thisisnormal
operation of a gas regulator or valve.
Unit Body/Firebox:
Different types and thicknesses of steel will
expand and contract at different rates resulting
in some "cracking" and "ticking" sounds will be
heard throughout the cycling process.
Regency® P36-4 Gas Log Fireplace
31
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING INSTRUCTIONS
COPY OF THE LIGHTING PLATE INSTRUCTIONS
MAINTENANCE
INSTRUCTIONS
1) Alwaysturnoffthegasvalvebeforecleaning.
For relighting, refer to lighting instructions.
Keep the burner and control compartment
clean by brushing and vacuuming at least
once a year. When cleaning the logs, use a
soft clean paint brush as the logs are fragile
and easily damaged.
FORYOURSAFETYREADBEFORELIGHTING
This appliance must be installed in accordance with local codes, if any; if not, follow the
current CAN1-B149/ANSI Z 223.1 (Australia: AS5601-2004, New Zealand: NZS 5261)
WARNING: If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal injury or loss
oflife.Improperinstallation,adjustment,alteration,serviceormaintenance
can cause injury or property damage. Refer to the owner’s information
manual provided with this appliance. For assistance or additional
information consult a qualified installer, service agency or gas supplier.
2) Clean appliance and door with a damp
cloth (never when unit is hot). Never use
an abrasive cleaner. The glass should be
cleaned with a gas fireplace glass cleaner.
The glass should be cleaned when it
starts looking cloudy.
A)This appliance has a pilot which C)Use only your hand to push in or turn
must be lighted by hand. When
lighting the pilot, follow these
instructions exactly.
the gas control knob. Never use tools.
If the knob will not push in or turn by
hand, don’t try to repair it, call a
qualified service technician. Force or
attempted repair may result in a fire
or explosion.
3) The heater is finished in a heat resistant
paintandshouldonlyberefinishedwithheat
resistant paint. Regency® uses StoveBright
Paint - Metallic Black #6309.
B)BEFORE LIGHTING smell all around
the appliance area for gas. Be sure
to smell next to the floor because
4) Make a periodic check of burner for proper
position and condition. Visually check the
flameoftheburnerperiodically,makingsure
the flames are steady; not lifting or floating.
If there is a problem, call an authorized
service person.
some gas is heavier than air and D)Do not use this appliance if any part
will settle on the floor.
has been under water. Immediately
call a qualified service technician to
inspect the appliance and to replace
any part of the control system and any
gas control which has been under
water.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electric switch, do
not use any phone in your building
- Immediately call your gas supplier
5) The appliance and flueing system must be
inspected before use, and at least annually,
by an authorized field service person, to
ensure that the flow of combustion and
ventilation air is not obstructed.
from a neighbours phone. Follow This appliance needs fresh air for safe
the gas supplier’s instructions. operation and must be installed so there
- If you cannot reach your gas are provisions for adequate combustion
supplier, call the fire department. and ventilation air.
CAUTION:Hotwhileinoperation.Donottouch.SevereBurnsmayresult.Due
tohighsurfacetemperatureskeepchildren,clothingandfurniture,gasoline
and other liquids having fammable vapors away. Keep burner and control
compartment clean. See installation and operating instructions
accompanyingappliance.
Note: Never operate the appliance without
the glass properly secured in
place.
6) Donotusethisapplianceifanyparthasbeen
underwater.Immediatelycallanauthorized
service technician to inspect the appliance
andtoreplacenaypartofthecontrolsystem
and any gas control which has been under
water.
LIGHTINGINSTRUCTIONS
STOP! Read the safety information above on this label.
1) Push in gas control knob slightly and turn to “PILOT” position.
7) Verify operation after servicing.
2) Push in control knob all the way and hold in until the pilot lights up. Continue
to hold the control knob in for about 20 seconds after the pilot is lit. Release
knob.
General Flue Maintenance
3) Push in gas control knob slightly and
turn to "ON" position.
Conduct an inspection of the flueing system
semi-annually. Recommended areas to inspect
as follows:
Gas Inlet
4) Turn ON the flame switch.
1) Check the Flueing System for corrosion in
areas that are exposed to the elements.
These will appear as rust spots or
streaks, and in extreme cases, holes.
These components should be replaced
immediately.
TO TURN OFF GAS APPLIANCE
You may shut off the pilot during prolonged non use periods to conserve fuel.
1) Turn OFF the flame switch.
2) Push in gas control knob slightly and turn to "OFF" position.
2) Remove the Cap, and shine a flashlight
down the Flue. Remove any bird nests, or
other foreign material.
DO NOT REMOVE THIS INSTRUCTION PLATE
918-253a
Regency® P36-4 Gas Log Fireplace
32
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
3) Check for evidences of excessive
condensation,suchaswaterdropletsforming
in the inner liner, and subsequently dripping
outthejoints,Continuouscondensationcan
cause corrosion of caps, pipe, and fittings.
It may be caused by having excessive
lateral runs, too many elbows, and exterior
portions of the system being exposed to
cold weather.
Flush Glass Replacement
THERMOPILE /
Remove the flush door front (as per instructions
in section "Standard Flush Door"). Remove
the 4 glass clips from each corner. Slide in the
new replacement glass. Push the 4 glass clips
back onto the frame. The glass must have
gasketing around it.
THERMOCOUPLE
1) Open the bottom louvres.
2) Loosenthethermocoupleorthermopilewith
a 7/16" spanner.
3) Disconnect thermocouple by loosening
nut from the valve with a 9mm spanner.
Disconnect thermopile by loosening 2
screws marked TP on the valve.
4) Inspect joints, to verify that no pipe
sections or fittings have been disturbed,
and consequently loosened. Also check
mechanical supports such as Wall Straps,
or plumbers' tape for rigidity.
4) Drop the thermocouple or thermopile down
from the bracket and pull it out of the unit.
5) Reinstall the new ones in reverse order.
GOLD-PLATED &
BRASS
GLASS GASKET
If the glass gasket requires replacement use
5/8" flat glass gasket for the Bay Front (Part
# 936-243) and a tadpole glass gasket for the
Flush Front (Part # 936-155).
LOUVRES OR TRIM
The 24 carat gold plated or brass finish on the
trim requires little maintenance, and need only
be cleaned with a damp cloth. DO NOT use
abrasive materials or chemical cleaners, as
they may harm the finish and void the warranty.
Cleananyfingerprintsoff beforeturningthe
unit on. If the top louvres start to discolour,
check the door gasket seal and replace if
necessary.
DOOR GLASS
Your Regency® fireplace is supplied with high
temperature,5mmNeoceramceramicglassthat
will withstand the highest heat that your unit will
produce. If your glass requires cleaning, we
recommend using an approved glass cleaner
available at all authorized dealers. Do not use
abrasive materials. Do not clean the glass
when hot.
Bay Glass Replacement
1) Remove the door from the unit and place
on a soft surface to prevent scratching.
LOG REPLACEMENT
2) Remove the nuts holding the glass clips in
place and remove.
The unit should never be used with broken logs.
Turn off the gas valve and allow the unit to cool
before opening door and carefully remove the
logs. (The pilot light generates enough heat to
burn someone.) If for any reason a log should
need replacement, you must use the proper
replacement log. The position of these logs
must be as shown in the diagrams under Log
Installation.
3) Replace the glass. The glass must have
gasketing around it.
Intheeventthatyoubreakyourglassbyimpact,
purchase your replacement from an authorized
Regency® dealer only, and follow our step-by-
step instructions for replacement.
5) Reversetheprevioussteps,replacetheglass
clips and fasten with the nuts but do not over
tighten, as this can break the glass.
WARNING: Do not operate the
appliance with the glass panels
removed, cracked or broken.
Replacement of the glass panels
should be done by a licensed or
qualified service person.
6) Replace door on the stove and check the
seal.
Note: Improper positioning of logs may
create carbon build-up and will
severely alter the unit's performance
which is not covered under
warranty.
Caution: Wear gloves when
removing damaged or broken
glass.
Regency® P36-4 Gas Log Fireplace
33
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
10) Undo the pilot tube from the valve with a
REMOVING VALVE
INSTALLING VALVE
7/16" spanner.
1) Shut off the gas supply.
1) Attach the valve to the valve bracket with
11) Undo the quick drop out thermocouple nut
the 4 (m5x8 metric) screws provided.
on the valve with a 9mm (metric) spanner.
2) Remove the louvres (and bay door if it is
on).
2) Reconnect the "gas out" flare fitting with an
12) Remove the Piezo igniter wire and push
11/16" spanner.
button assembly.
3) Open the flush door and remove the door.
3) Reconnect the "gas out" flare nut with a
13) Undo the "gas out" flare nut with a 13/16"
4) Remove the logs.
13/16" spanner.
spanner.
5) Remove the burner/grate assembly by
removing the two Phillips head screws and
then lift the burner assembly out.
4) Install piezo ignitor push button assembly
14) Undo the "gas out" flare fitting with an 11/16"
and reconnect wire.
spanner.
5) Reconnectthequickdropoutthermocouple
15) Remove the 4 Phillips head screws from
the sides of the valve bracket and remove
valve.
nut with a 9mm spanner.
6) Reconnect the pilot tube nut with a 7/16"
spanner.
7) Scrapeofftheoldgasketfromthefloorofthe
firebox and from the valve tray assembly.
8) Install a new gasket and reinstall the valve
tray assembly.
Note: Failure to install a new gasket
may severely affect the appliance
performance.
9) Reinstall the 10 hold down screws.
10) Hook up the 2 TP and 2 TH wires to the
appropriate connections on the valve.
11) Reinstall the front log stand.
Diagram 1: Remove the left and right screws
and then lift out the burner/grate assembly.
12) Install Burner/grate assembly
6) Remove the rear log stand by removing the
13) Hook up the gas line and check for gas
leaks with a soap and water solution or a
gas leak detector. (Do not use open flame
for leak testing.)
2 screws.
screws
Rear Log Stand
Hint:
If you are using black pipe, ensure
that there is a union by the valve,
otherwise removal will be almost
impossible.
14) Fire up the unit temporarily
15) Check the manifold pressure.
16) Reinstall the logs and brick panels as
needed.
17) Close the door and replace the louvres.
18) Fire up the unit again and check for proper
screws
Valve Tray Assembly
flame appearance and glow on logs.
Diagram 2: Rear Log Stand and
Valve Tray Assembly
7) Disconnect the inlet gas line. See diagram
2.
8) Disconnect the 2 TP wires and the 2 TH
wires from the valve.
9) Removethe10Phillipsheadscrewssecuring
thevalvetrayassemblyinplace(diagram2)
andthenlifttheentireassemblyout diagram
3).
Regency® P36-4 Gas Log Fireplace
34
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
MAIN ASSEMBLY
Part #
Description
1) 910-142
Thermodisc-Fan Auto ON/OFF
Thermodisc Bracket
Chain
2)
*
3) 948-045
4) 948-025
6) 510-125
7) 910-006
8) 510-126
9) 910-140
10) 910-246
Spring
Terminal Block Housing
Terminal Block
Terminal Block Cover
Fan Switch HIGH/OFF/LOW
Burner Switch ON/OFF
12) 910-169/P Fan Motor
31
30
910-520
910-714
Wire Harness
Power Cord (240 V)
14) 510-026
15) 948-253
Hinge Bracket - Left/Right
Door Handle
17)
*
Wire Holder Clip
20) 510-033
21) 510-064
22) 510-153
23) 510-011
24) 511-044
Top Nailing Strip
Side Nailing Strip
Baffle Plate
28
30
Standoff - Top
Standoff - Side/Back
Outer Flue Collar
Inner Flue Collar Assembly
Gasket for Flue Collar
Flue Mounting Plate
27)
28)
30)
31)
*
*
*
*
22
23
27
513-901
Brick Panel Set - Standard Brown
Brick Panel Set - Standard Red
Brick Panel Set - Herringbone Brown
Brick Panel Set - Herringbone Red
Brick Panel - Back
20
513-902
513-903
513-904
*
*
*
33)
34)
35)
23
Brick Panel - Left
Brick Panel - Right
24
36) 910-073
37) 910-074
Spark Generator Battery Holder
Spark Generator Switch c/w Wire
511-031
Brick Clip (each)
21
918-538
513-968
Manual
Conversion Kit - NG to LPG
17
14
6
7
4
3
8
33
15
1
24
14
2
21
37
36
10
9
34
BRICKPANELSET
DOORS&LOUVERSPLEASE
REFER SEPARATESECTION
35
Regency® P36-4 Gas Log Fireplace
35
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
BURNER ASSEMBLY & LOG SET
Part #
Description
513-560/P
513-562/P
52) *
Valve Assy - NG
Valve Assy - LPG
Valve Tray -NG
92
53) 430-055
54) 910-421
55) 910-422
57) 910-478
58) *
Gasket - Valve Access Plate
Pilot ON/OFF 3" Extension Knob
HI/LOW 3" Extension Knob
S.I.T. Valve - NG/LPG
Valve Bracket
93
94
95
98
59) *
Firebox Base
65) *
Pilot Bracket
97
66) 910-038
910-039
904-240
904-390
910-036
910-037
936-170
67) *
Pilot Assy-NG 3 way flame-S.I.T.
Pilot Assy-LPG 3 way flame-S.I.T.
Orifice #37 - NG (Burner)
Orifice #52 - LPG (Burner)
Pilot Orifice - NG
96
Pilot Orifice - LPG
Orifice Gasket
Pilot Holder
68) W840470
Pilot Assembly Gasket
79) 512-525
82) 511-030
84) *
85) 512-930
86) 910-386
87) 910-341
88) 910-096
Burner Assy - NG
Burner Grate Assy
Rear Log Support Assy
Log Set
Thermocouple
Thermopile
Pilot Hood (3-way)
92) *
93) *
94) *
95) *
96) *
97) *
98) *
Rear Log
Middle Right Log
Front Left Log
Center Left Log
Center Right Log
Front Bottom Log
Middle Left Log
*Not available as a replacement part.
Regency® P36-4 Gas Log Fireplace
36
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
BAY FRONT ASSEMBLY
Part #
Description
Part #
Description
Bay Louvres - Black
780-931
Bay Front Complete
510-988
510-990
510-992
510-993
*
103) 940-092/P Side Glass
Bay Louvres - Gold/Black
Bay Louvres - Brass/Black
Bay Louvres - Steel/Black
Bay Louvre Assy-Top
107) 936-243
Glass Gasket - Soft Fibre Black
108) 940-094/P Center Glass
111) 780-905
780-906
Brick Panel Inlay - Rustic Brown Bay
Brick Panel Inlay - Old Town Red Bay
115)
116)
*
Bay Louvre Assy-Btm
780-938
780-936
*
Bay Front Trim - Brass
Bay Front Trim - Steel
Bay Front Trim -Top/Bottom
117) 904-196
120)
Magnet (1" round)
Flush Glass Retainer Bracket
*
112)
*Not available as a replacement part.
780-934
*
*
Bay Door Trim - Gold
Bay Door Trim-Gold-Bottom
Bay Door Trim-Gold-Top
113)
114)
Regency® P36-4 Gas Log Fireplace
37
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
FLUSH FRONT ACCESSORIES
Part #
Description
132) 512-518
Flush Door Assembly
135) 940-090/P Glass (Flush)
136) 936-155
904-691
Glass Gasket (Tadpole)
U-Clip (each)
510-920
510-921
510-922
510-923
138) *
Flush Louvres - Gold/Black
Flush Louvres - Brass/Black
Flush Louvres - Black
Flush Louvres - Steel/Black
Flush Louvre Assy-Top
Flush Louvre Assy-Btm
139) *
136
138
135
510-954
146) *
Barcelona Surround - Black
Barcelona Assy
148) *
Barcelona Louvre Assy
150
152
510-932
150) *
Flush Glass Trim - Gold (2/Set)
Flush Glass Trim-Gold
904-196
Magnet (1" round)
146
510-934
510-947
152) *
Flush Glass Trim - Brass (2/Set)
Flush Glass Trim - Steel (2/Set)
Flush Glass Trim-Brass
148
904-196
Magnet (1" round)
132
139
510-986
510-909
510-910
157) *
Finishing Trim (3 piece) - Black
Finishing Trim (3 piece) - Steel
Finishing Trim (4 piece) - Steel
Finishing Trim Left
158) *
Finishing Trim Top
159) *
160) *
Finishing Trim Right
Finishing Trim Bottom
157
158
161) 513-949
Flush Door Screen Pkg.
*Not available as a replacement part.
159
160
161
Regency® P36-4 Gas Log Fireplace
38
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
PREMIUM FLUSH FRONT ASSEMBLY
Part #
Description
516-916
Premium Flush Front - Black
Wiring
513-948
910-975
Thermodisc
180)
181)
182)
183)
*
*
*
*
Top Louver
Bottom Louver
Thermodisc Mounting Bracket
Spacers
*Not available as a replacement part.
Regency® P36-4 Gas Log Fireplace
39
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
CAST FACEPLATE ASSEMBLY
Part #
Description
513-971
Cast Faceplates (Set) - Black Metallic
201) *
Cast Faceplate - Right
Cast Faceplate - Top
Cast Faceplate - Left
202) *
203) *
513-991
204) *
205) *
Cast Grills (Set) - Black Metallic (Aust. only 240 volt)
Cast Grill - Top
Cast Grill - Bottom
513-976
Cast Faceplates (Set) - Black Enamel
Cast Faceplate - Right
201) *
202) *
203) *
Cast Faceplate - Top
Cast Faceplate - Left
513-996
204) *
205) *
Cast Grills (Set) - Black Enamel (Aust. only 240 volt)
Cast Grill - Top
Cast Grill - Bottom
* Not available as a replacement part.
Regency® P36-4 Gas Log Fireplace
40
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
Regency® P36-4 Gas Log Fireplace
41
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
Regency® P36-4 Gas Log Fireplace
42
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY
Regency® Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal QualityAssurance Team carefully
inspects each unit thoroughly before it leaves our door. FPI is pleased to extend this limited lifetime warranty to the original purchaser
of a Regency® Product.
The Warranty: Lifetime
Covered under the agreement are the following components: Combustion chamber, heat exchanger, burner tubes, logs, embers, glass (thermal
breakage) and all gold plating against defective manufacture.
NOTE: Gold Plated Barcelona Front - slight imperfections in the gold plating are due to the plating process and are not considered defects.
The above will be covered for parts and labour for the first five years and parts only thereafter.
Electrical components such as blowers, switches, wiring, thermodiscs, remote control, thermopiles, thermocouples and gas valves are covered for
one year from the date of purchase.
The warranty on brass parts is for one year, no labour. The brass is not warranted against tarnishing.
Conditions:
All installations must be performed by a qualified gas fitter and installed according to all applicable local and national codes. Also, all service
work must be carried out by a qualified gas service person provided by the selling dealer. It is the responsibility of the installer to ensure that
the appliance is firing as per rating plate. Any part or parts of this unit which in our judgement show evidence of such defect will be repaired or
replaced at Regency®'s option, through an accredited distributor or agent provided that the defective part be returned to the distributor or agent
Transportation Prepaid, if requested. In areas where there is not an approved service agent or the closest approved service agent is situated
more than twenty-five (25) kilometres from the installation, Australian Heating Distributors are not obliged to arrange warranty repairs and travel
and/or additional labour charges will apply.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim. It does not cover installation and operational
related problems such as over-firing, downdrafts or spillage caused by environmental conditions, nearby trees, buildings, hilltops, mountains,
inadequate flueing or ventilation, excessive offsets, negative air pressures caused by insufficient make up air, mechanical systems such as furnaces,
fans, clothes dryers etc.
The warranty does not extend to any part or parts which show evidence of misuse or abuse, neglect, accident, lack of maintenance, or improper
installation.
Products made by other manufacturers and used in conjunction with the operation of this appliance without authorization from Regency®, may
nullify your warranty on this product.
FPI Ltd., shall in no event be liable for any special, indirect consequential damages of any nature whatsoever which are in excess of the original
purchase price of the product. Any alteration to the unit which causes sooting or carboning that results in damage to the exterior facia is not the
responsibility of FPI.
General:
It is essential that all submitted claims provide all of the necessary information including purchase date, serial #, type of unit and part or parts
requested.
SUBJECT TO CHANGE.
DISTRIBUTORS:
Western Australia
Eastern Australia
AUSTRALIAN HEATING DISTRIBUTORS
31 CLUNE STREET
FIREPLACE PRODUCTS AUSTRALIA PTY. LTD.
21-23 SOUTH LINK BLVD.
BAYSWATER, WA 6053
DANDENONG, VIC 3175
SERVICE AGENTS:
HEARTH HOUSE SERVICE
31 CLUNE STREET
BAYSWATER, WA 6053
NOTE: PLEASE RETAIN YOUR INVOICE AS PROOF OF PURCHASE FOR WARRANTY VERIFICATION
INCORRECT INSTALLATION OR GAS PRESSURE SETTINGS ARE NOT COVERED BY WARRANTY
A SERVICE OR CALLOUT FEE WILL BE CHARGED IN THESE CIRCUMSTANCES.
Regency® P36-4 Gas Log Fireplace
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Printed in Canada
© Copyright 2007, FPI Fireplace Products International Ltd. All rights reserved.
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Q See Baby Monitor QSDB8209C User Guide
Ramsey Electronics Car Satellite TV System HR20 User Guide
RCA Car Video System DRC220N User Guide
RCA Flat Panel Television RLC2609 User Guide
Remington Electric Shaver BHT 600 User Guide
RIDGID Saw TS2400LS User Guide
Roberts Radio Radio CRD 39 User Guide
Samsung Portable DVD Player DVD L300WDEU User Guide
Sanyo Headphones SHH9508 User Guide
Sanyo Projector PLV WF20 User Guide