P121 / P121LC / P121RC / P131
Zero Clearance Direct Vent Gas Fireplace
Owners &
Installation Manual
STYLE
SeeThru
LeftCorner
MODEL
P121-NG1NaturalGas
P121LC-NG1NaturalGas P121LC-LP1Propane
P121-LP1Propane
RightCorner P121RC-NG1NaturalGas P121RC-LP1Propane
Pier P131-NG1NaturalGas P131-LP1Propane
WARNING:
FORYOURSAFETY
What to do if you smell gas:
Do not try to light any appliance
Do not touch any electrical switch: do not use any
phone in your building.
Immediately call your gas supplier from a neighbour's
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
If the information in these instructions are not followed
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapours and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
918-107a
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
08/08/03
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
Safety Label
SafetyLabel ............................................................... 4
Installation
Operating Instructions
OperatingInstructions ...............................................29
LightingProcedure ....................................................29
ShutdownProcedure .................................................29
First Fire ...................................................................29
AerationAdjustment..................................................29
NormalOperatingSoundsof
ManufacturedMobileHomeRequirements ................. 2
ImportantMessage .................................................... 5
Before You Start ........................................................ 5
GeneralSafetyInformation ......................................... 5
Installation Checklist .................................................. 5
Specifications ............................................................ 6
LocatingYourFireplace ............................................. 8
Clearances ................................................................. 9
CombustibleMantelClearances ................................. 9
FramingandFinishing ...............................................10
FacingandFinishingRequirements ..........................11
Unit Assembly Prior to Installation
TopStandoffAssembly .......................................11
VentingIntroduction ..................................................11
ExteriorVentTerminationLocations..........................12
Venting: Direct Vent System (Flex) ...........................13
Venting: Simpson Dura Vent Direct Vent GS ............14
Venting: Simpson Dura Vent Components List..........14
VentingArrangements
Gas Appliances ..................................................29
Lighting Plate Instructions .........................................30
Maintenance
MaintenanceInstructions ..........................................30
GeneralVentMaintenance ........................................31
LogReplacement ......................................................31
Thermopile/Thermocouple .........................................31
Glass Gasket............................................................31
DoorGlass................................................................31
Gold-PlatedAccessories...........................................31
RemovingValve .........................................................31
InstallingValve ..........................................................32
FanReplacement ......................................................33
PartsList
HorizontalTerminations ......................................15
VerticalTerminations ..........................................17
Venting-Dura-VentHorizontalInstallations ..............19
Venting-Dura-VentVerticalTermination...................20
Venting - Installation Procedures for Direct Vent
Replacement/SparePartsList...................................34
Warranty
System (Flex) .....................................................21
ConveriontoPropane ................................................22
System Data .............................................................23
HighElevation ...........................................................23
Gas Line Installation..................................................23
Pilot Adjustment .......................................................23
Gas Pipe Pressure Test ............................................23
Warranty ...................................................................39
SITValveDescription ................................................23
Log Set Installation ...................................................24
GlassDoorRemoval..................................................26
FinishingTrim ...........................................................26
LouversandGrills......................................................26
RemoteControl(optional) ..........................................27
Remote Wall Switch (optional) ..................................27
WallThermostat(optional) ........................................27
WiringDiagram .........................................................28
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
3
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY LABEL
This is a copy of the label that accompanies
eachP121-1/P121LC-1/P121RC-1/P131-1Zero
Clearance Direct Vent Gas Fireplace. We have
printed a copy of the contents here for your
review. The safety label is located on the front
inside base of the unit, visible when the bottom
louver is open.
NOTE: Regency units are constantly being
improved. Check the label on the unit and if
there is a difference, the label on the unit is the
correct one.
For the State of Massachusetts, installation
and repair must be done by a plumber or
gasfitter licensed in the Commonwealth of
Massachusetts.
For the State of Massachusetts, flexible
connectors shall not exceed 36 inches in
length.
For the State of Massachusetts, the appli-
ances individual manual shut-off must be a
t-handle type valve.
4
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
free of combustible materials, (gases and
other flammable vapours and liquids).
IMPORTANT:
SAVE THESE
INSTRUCTIONS
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISEDWHENTHEY
AREINTHESAMEROOMASTHEAP-
PLIANCE.
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
The Panorama P121/P121LC/P121RC/P131-
NG1orP121/P121LC/P121RC/P131-LP1Direct
Vent Fireplace must be installed in accordance
with these instructions. Carefully read all the
instructions in this manual first. Consult the
"authority having jurisdiction" to determine the
needforapermitpriortostartingtheinstallation.
It is the responsibility of the installer to ensure
this fireplace is installed in compliance with
manufacturer's instructions and all applicable
codes.
GENERAL SAFETY
INFORMATION
INSTALLATION
CHECKLIST
1) The appliance installation must conform
with local codes or, in the absence of
local codes, with the current Canadian or
NationalGasCodes,CAN1-B149orANSI
Z223.1 Installation Codes.
Note: These units are
non-load bearing.
2) See general construction and assembly
instructions. Theapplianceandventshould
be enclosed.
1) Locate appliance
a) Room location, page 8.
b) Clearances to Combustibles,
page 9.
c) Mantle Clearances, page 9.
d) Framing & Finishing Requirements,
page 10.
BEFORE YOU START
3) This appliance must be connected to the
specified vent and termination cap to the
outside of the building envelope. Never
vent to another room or inside a building.
Make sure that the vent is fitted as per
Venting instructions.
Safe installation and operation of this appliance
requires common sense, however, we are
required by the Canadian Safety Standards
and ANSI Standards to make you aware of the
following:
e) Venting Requirements, pages 11-19.
2) Assemble Top Standoffs, page (NOTE:
page11mustbedonebeforeinstallingunit
into fireplace.)
INSTALLATIONANDREPAIRSHOULD
BE DONE BY A QUALIFIED SERVICE
PERSON.THEAPPLIANCESHOULDBE
INSPECTED BEFORE USE AND AT
LEASTANNUALLYBYAPROFESSION-
ALSERVICEPERSON.MOREFREQUENT
CLEANINGMAYBEREQUIREDDUETO
EXCESSIVELINTFROMCARPETING,
BEDDINGMATERIAL,ETC.ITISIMPER-
ATIVE THAT CONTROL COMPART-
MENTS,BURNERSANDCIRCULATING
AIR PASSAGEWAYS OF THE APPLI-
ANCEBEKEPTCLEAN.
4) Inspect the venting system annually for
blockage and any signs of deterioration.
3) Install vent, pages 19-21.
5) Ventingterminalsshallnotberecessedinto
a wall or siding.
4) Makegasconnections. Testthepilot. Must
be as per diagram. Page 22.
6) Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
5) Install log set where indicated on
page 24-25.
7) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fireplace.
6) Glass Door Removal (page 26), Louvers
or Grills (page 26), and Finishing Trim
(page 26).
8) Wear gloves and safety glasses for pro-
tection while doing required maintenance.
7) Install optional Wall Switch, Remote Con-
trol, or Wall Thermostat, page 27.
DUE TO HIGH TEMPERATURES, THE
APPLIANCESHOULDBELOCATEDOUT
OFTRAFFICANDAWAYFROMFURNI-
TUREANDDRAPERIES.
9) Be aware of electrical wiring locations in
walls and ceilings when cutting holes for
termination.
8) Final check.
Before leaving this unit with the customer, the
installermustensurethattheapplianceisfiring
correctly and operation fully explained to cus-
tomer.
WARNING:FAILURETOINSTALLTHIS
APPLIANCECORRECTLYWILLVOID
YOURWARRANTYANDMAYCAUSEA
SERIOUSHOUSEFIRE.
10) Under no circumstances should this appli-
ance be modified. Parts that have to be
removed for servicing should be replaced
prior to operating this appliance.
This includes:
11) Installationandanyrepairstothisappliance
should be done by a qualified service per-
son. A professional service person should
be called to inspect this appliance annually.
Make it a practice to have all of your gas
appliances checked annually.
CLOTHINGOROTHERFLAMMABLEMA-
TERIALSHOULDNOTBEPLACEDON
ORNEARTHEAPPLIANCE.
1) Clocking the appliance to ensure the cor-
rect firing rate (rate noted on label 40,000
Btu/hNG, and39,000Btu/hLP)afterburn-
ing appliance for 15 minutes.
CHILDRENANDADULTSSHOULDBE
ALERTEDTOTHEHAZARDSOFHIGH
SURFACETEMPERATURES,ESPECIAL-
LY THE FIREPLACE GLASS, AND
SHOULDSTAYAWAYTOAVOIDBURNS
ORCLOTHINGIGNITION.
2) If required, adjusting the primary air to
ensure that the flame does not carbon.
First allow the unit to burn for 15-20 min.
to stabilize.
12) Do not slam shut or strike the glass door.
13) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.)
be used in this appliance.
CAUTION: Any alteration to the product
that causes sooting or carboning that
results in damage is not the responsi-
bility of the manufacturer.
14) The appliance area must be kept clear and
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
5
INSTALLATION
SPECIFICATIONS
P121-1 See Thru
Note: These units are
non-load bearing.
P131-1 Pier
6
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
P121LC-1 Left Corner Unit
Note: These units are
non-load bearing.
P121RC-1RightCornerUnit
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
7
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
LOCATING YOUR
GAS FIREPLACE
A) P121-1 See Thru
1) When selecting a location for your stove,
ensure that the clearances are met as
outlined on page 9.
2) Provide adequate clearances for servic-
ing.
3) The appliance must be installed on a flat,
solid, continuous surface (e.g. wood, met-
al, concrete). This may be the floor, or
raised up on a platform to enhance its
visualimpact. Iftheapplianceisgoingtobe
installed on carpeting, combustible linole-
um tile or other combustible material other
than wood flooring, the appliance must be
installed on a metal or wood panel extend-
ing the full width and depth of the appli-
ance.
4) The Direct Vent Gas Fireplace can be
installed as follows:
Model # Position
P121-1: See Thru
P131-1:Pier
B) P131-1 Pier
A)
B)
C)
D)
P121LC-1: Left Corner
P121RC-1: Right Corner
5) ThisapplianceisListedforbedroom instal-
lations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6) The P121-1/P121LC-1/P121RC-1/P131-1
Direct Vent Gas Fireplace is approved for
alcove installations, which meet the clear-
ances listed on this page.
7) We recommend that you plan your instal-
lation on paper using exact measurements
for clearances and floor protection before
actually installing this appliance. Have a
qualified inspector, dealer, or installer re-
view your plans before installation.
C) P121LC-1 Left Corner
Note: For Exterior Vent Termination
Locations see page 12.
.
D) P121RC-1 Right Corner
8
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated (refer to diagrams on page 8):
Clearance to Combustibles from:
Back
Side
Floor
0"
0"
0"
(0mm)
(0mm)
(0mm)
WARNING:
Fire hazard is an extreme risk
if these clearances (air space)
to combustible materials are
not adhered to. It is of greatest
importance that this fireplace
and vent system be installed
only in accordance with these
instructions.
CAUTION REQUIREMENTS: The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoffs may NOT be recessed into combus-
tible construction.
Determine the total thickness of the finished floor (eg. tile, carpet, slate) to allow
the finished surface to be flush with the base of the unit.
Ceiling Height from Floor 72" (1828mm)
Mantel Height from Base of Unit:
39" min. (991mm)
Horizontal Vent Clearances:
Top
Side
Bottom
2-1/2"(64mm)
1-1/2"(38mm)
1-1/2"(38mm)
Vertical Vent Clearances 1-1/4" (32mm)
COMBUSTIBLE MANTELS
Mantel Clearances
Because of the extreme heat this fireplace emits, the mantel clearanc-
es are critical. Combustible mantel clearances from top of unit are shown in
Diagram to the right.
Note: A non-combustible mantel may be installed at a lower height if
the framing is made of metal studs covered with a non-
combustible board.
This drawing is to scale at 1:6 (one inch = 6 inches)
Mantel can be installed anywhere in shaded area or higher using this scale.
Caution: Ensure the paint that is used on the mantel and the facing is
"heat resistant" or the paint may discolour.
* If the 3" metal extension trim is removed it must be replaced with a 3" non-
combustible material.
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
9
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
FRAMING AND FINISHING
1) For ease of installation, frame your fireplace after it is positioned and
the vent system is installed. Remember to install the top standoffs.
See page 11 for assembly. Use 2x4's and frame to local building
codes.
FramingDimensions
P121-1 (See Thru)
P131-1 (Pier)
P121LC-1 / P121RC-1
(Corner Unit)
A
25"(635mm)
minus two times
the finishing
25"(635mm)
minus two times
the finishing
26-13/16"
minus one time
the finishing
CAUTION: Verify your fireplace dimensions, framing methods
and finished wall facing details before framing. Determine the
total thickness of facing material - drywall plus ceramic tiles,
slate, etc. Allow the finish surface to be flush with the front or
side of the unit. Total facing thickness can vary from 1/2"
(13mm) to 1-1/4" (32mm) thick.
material thickness* material thickness* material thickness*
B
C
42-1/2"(1080mm) 42-1/2"(1080mm) 42-1/2"(1080mm)
46-3/4"(1187mm) 45" (1143mm)
minus one time
45"(1143mm)
minus one time
the finishing
2) When locating your appliance on an exterior wall or in a chase, apply
a vapour barrier and drywall, as per local building codes. DO NOT
INSULATETHEFIREPLACEITSELF.
the finishing
material thickness* material thickness*
CAUTION: The unit does not have to be completely enclosed in
a chase. The clearance on top of the unit is 0" to the standoffs
so combustible building materials can be laid directly on top of
the standoffs. You must maintain clearance from the vent to
combustible materials for both rigid and flex, see Vent Clear-
ances, page 9.
* Finish material thickness includes: drywall, ceramic tile, slate, etc.
P121LC-1 - Corner Unit
P121-1 - See Thru
P131-1 - Pier
P121RC-1 - Corner Unit
C
A
B
Note: These units are
non-load bearing.
10
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
FACING & FINISHING REQUIREMENTS
This fireplace is supplied with a 3" metal extension trim above the fireplace. The extension trim may be replaced if the framing is faced with a non-
combustible material placed flush with the front and side face of the unit and extending from the top of the unit. (ie. tile, slate, etc.)
VENTING
INTRODUCTION
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The P121-1/P121LC-1/P121RC-1/P131-1 uses
the "balanced flue" technology Co Axial
system. The inner liner vents products of com-
bustion to the outside while the outer liner
draws outside combustion air into the combus-
tionchambertherebyeliminatingtheneedtouse
heated room air for combustion and losing
warm room air up the chimney.
The 4 Top Standoffs must be correctly positioned and attached to the top before unit is slipped
into position.
TopStandoffAssembly
The top standoffs are shipped in a flat position and must be folded into shape and attached.
1) Remove the standoffs from the fireplace
top.
Note: These flue pipes must not be con-
nected to any other appliance.
2) Take each standoff and bend into the
correct shape. Bend up at the bend lines
until the screw holes in the standoff and the
pre-punched screw holes on the fireplace
top line up.
The gas appliance and vent system must be
venteddirectlytotheoutsideofthebuilding, and
never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Each direct vent gas appliance must use it's
own separate vent system. Common vent sys-
tems are prohibited.
3) Attach the standoff securely to the top with
4 screws per standoff (on opposite cor-
ners).
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
11
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
EXTERIOR VENT TERMINATION LOCATIONS
12
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
VENTING ARRANGEMENT - HORIZONTAL TERMINATIONS
Regency Direct Vent System (Flex) Horizontal Terminations Only
These venting systems, in combination with the P121-1/P121LC-1/P121RC-1/P131-1 Direct Vent Gas Fireplace, have been tested and listed as
a direct vent heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations
diagram on page 12.
Regency Direct Vent (Flex) System Termination Kit (Part# 946-513) includes all the parts needed to install the P121-1/P121LC-1/
P121RC-1/P131-1 with a maximum run of 2 feet.
1) 6-7/8" dia. flexible liner (2 ft. length)
2) 4" dia. flexible liner (2 ft. length)
3) spring spacers (3)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" drill point, stainless steel (4)
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency may be used for Flex installations.
3) Regency Direct Vent System (Flex) is only approved for horizontal terminations.
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
13
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
SIMPSON DURA-VENT VENTING
Horizontal or Vertical Terminations
The Simpson Dura-Vent Direct Vent System offers a complete line of component parts for installation of both horizontal and vertical installations.
Many items are offered in decorative black, as well as galvanized finish. We recommend using the galvanized finish for installation with the P121-
1/P121LC-1/P121RC-1/P131-1.
The minimum components required for a
basic horizontal termination are:
vinyl siding standoff, to
create a level surface to
mount the vent terminal.
The Terminal must not be
recessedintosiding.Meas-
ure the wall thickness in-
cluding furring strips.
1
1
1
1
1
1
Simpson Duravent Adaptor
Horizontal Termination Cap
45o Elbow
Flue Adaptor
WallThimble
Length of pipe to suit wall thickness
(see chart)
If a Vinyl Siding Standoff is
required (it must be used
with vinyl siding), measure
to outside surface of wall
without siding and add 2
inches.
Wall thickness is measured from the back
standoffs to the inside mounting surface of
termination cap. For siding other than vinyl
furring strips may be used, instead of the
Flat Wall Installation
Wall Thickness
(inches)
Vent Length
Required (inches)
4" - 5-1/2"
7" - 8-1/2"
10" - 11-1/2"
9" - 14-1/2"
15" - 23-1/2"
6"
9"
12"
11" - 14-5/8" Adj. Pipe
17" - 24" Adj. Pipe
Simpson
Dura-Vent
Direct Vent GS
The Regency AstroCapTM is certified for installations using FPI
venting systems as well as Simpson Dura-Vent® and Direct
Vent GS.
RegencyTM, and Regency AstroCapTM are the proprietary trade-
marks of FPI Fireplace Products International Ltd.
Dura-Vent® and Direct Vent GS are registered and/or propri-
etary trademarks of Simpson Dura-Vent Co. Inc.
SIMPSON DURA-VENT VENTING COMPONENTS LIST
All Simpson Dura-Vent components are available directly from Regency.
Part # Description
Part # Description
902 48" Pipe Length - Galv.
902B 48" Pipe Length - Black
911B 11"-14 5/8" Adjustable Pipe Length -
Black
Part # Description
982 Snorkel - 14" Rise Termination Cap
981 Snorkel - 36" Rise Termination Cap
940 Wall Thimble - Support/Box
941 Cathedral/Ceiling - Support/Box
3951 Brass Trim for Wall Thimble/Ceiling Sup.
963 Firestop Spacer
943 Flashing 0/12-6/12
943S Flashing 7/12-12/12
953 StormCollar
950 Vinyl Siding Standoff
988 Wall Strap
971
Horiz.TerminationKit includes:
90o black elbow, wall thimble cover, horiz.
square termination cap, 24" black pipe, and 11"
-14" 5/8" adjustable black pipe
970
Basic Horiz. Termination. Kit includes:
90o black elbow, wall thimble cover,
horiz. square termination cap
917B 17"- 24" Adjustable Length - Black
945
45O Elbow - Galv.
945B 45O Elbow - Black
978
Vert. Termination Kit includes 0/12 -
6/12 pitch adjustable flashing, storm
collar, low profile term. cap
945G 45O Elbow - Swivel - Galv.
945BG 45O Elbow - Swivel - Black
990
90O Elbow - Galv.
908B 6" Pipe Length - Black
907B 9" Pipe Length - Black
990B 90O Elbow - Black
990G 90O Elbow - Swivel - Galv.
942 WallThimble
Parts not supplied by Dura-Vent
906
906B 12" Pipe Length - Black
904 24" Pipe Length - Galv.
904B 24" Pipe Length - Black
903 36" Pipe Length - Galv.
12" Pipe Length - Galv.
990BG 90O Elbow - Swivel - Black
946-506/P
510-994
640-530/P
946-205
Vent Guard (Optional)
Dura-Vent Flue Adaptor
Riser Vent Terminal
Vinyl Siding Shield for Riser
Vent Terminal
991
980
984
985
High Wind Termination Cap (Vertical)
Vertical Termination Cap
Horizontal Square Termination Cap
Horiz. Square High Wind Termination
Cap
903B 36" Pipe Length - Black
946-206
AstroCap Standoff
14
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS
SIMPSON DURA-VENT DIRECT VENT GS SYSTEM (Propane & Natural Gas)
The diagram below shows examples of horizontal termination arrangements using one, two, or three 90o elbows (two 45o elbows equal one 90o
elbow).
Note:
1) A maximum of three 90o elbows are permitted.
Simpson Dura-Vent
4" inner diameter
2) Minimum distance between elbows is 1 ft. (305mm).
6-5/8" outer diameter
•
•
•
•
•
Maintain clearances to combustibles as listed on page 9.
Horizontal vent must be supported every 3 feet.
Firestops are required at each floor level and whenever passing through a wall.
Must use optional flue adapter (Part# 510-994) when using Simpson Dura-Vent pipe.
A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
Horizontal Venting with One (1) 90o Elbow
Straight Out Horizontal Venting
Option
A)
V
H
1' (305mm) Minimum
2' (610mm) Minimum
3' (914mm) Minimum
4' (1.22m) Minimum
5' (1.5m) Minimum
6' (1.86m) Minimum
3' (914mm) Maximum
6' (1.86m) Maximum
9' (2.7m) Maximum
12' (3.6m) Maximum
15' (4.5m) Maximum
17' (5.1m) Maximum
B)
C)
D)
E)
F)
With the above options, maximum total pipe length if 37 feet with
minimumof6feettotalverticalandmaximum17feettotalhorizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 1
Diagram 2
Please note the minimum centerline
for basic install shown above.
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
15
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Horizontal Venting with Two (2) 90o Elbows
Horizontal Venting with Three (3) 90o Elbows
Option
A)
V
H
H + H1 + H2
Option
A)
V
H + H1
2' (610mm) Min. 1' (305mm) Max. 3'(914mm)Max.
3' (914mm) Min. 3' (914mm) Max. 6' (1.86m) Max.
4' (1.22mm) Min. 5' (1.5m) Max.
1' (305mm) Minimum
2' (610mm) Minimum
3' (914mm) Minimum
4' (1.22m) Minimum
5' (1.5m) Minimum
6' (1.86m) Minimum
2' (610mm) Maximum
5' (1.5m) Maximum
8' (2.4m) Maximum
11' (3.35m) Maximum
14' (4.27m) Maximum
15' (4.5m) Maximum
B)
C)
D)
B)
C)
D)
E)
9' (2.7m) Max.
5' (1.5m) Min. 7' (2.13m) Max. 12' (3.6m) Max.
With the above options, maximum total pipe length if 37 feet with
minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
F)
With the above options, maximum total pipe length if 37 feet with
minimum of 6 feet total vertical and maximum 15 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 5
Horizontal Venting with Three (3) 90o Elbows
Diagram 3
Option
A)
V + V1
H + H1
2' (610mm) Minimum
3' (914mm) Minimum
4' (1.22m) Minimum
5' (1.5m) Minimum
3' (914mm) Maximum
6' (1.86m) Maximum
9' (2.7m) Maximum
12' (3.6m) Maximum
B)
C)
D)
Horizontal Venting with Two (2) 90o Elbows
Option
A)
V
H
H + H1
With the above options, maximum total pipe length if 37 feet with
minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
1' (305mm) Min. 1' (305mm) Max. 3'(914mm)Max.
2' (610mm) Min. 3' (0.91m) Max. 6' (1.86m) Max.
B)
C)
D)
3' (914mm) Min. 5' (1.5m) Max.
5' (1.5m) Min. 8' (2.4m) Max.
9' (2.7m) Max.
12' (3.6m) Max.
With the above options, maximum total pipe length if 37 feet with
minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 4
Diagram 6
16
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
VENTING ARRANGEMENTS - VERTICAL TERMINATIONS
SIMPSON DURA-VENT DIRECT VENT GS SYSTEM (Propane & Natural Gas)
•
•
•
•
Vent must be supported at offsets
Maintain clearances to combustibles as listed on page 9.
Firestops are required at each floor level and whenever passing through a wall.
Must use optional flue adapter when using Simpson Dura-Vent pipe (Part# 510-994).
The P121-1/P121LC-1/P121RC-1/P131-1 is approved for a maximum 35 ft. (10.7m) straight vertical, with Simpson Dura-Vent Direct Vent GS
vent systems for Propane and Natural Gas, as per diagram 7 below.
Straight Up Vertical Venting
Vertical Venting with One (1) 90o Elbow
Option
A)
V
H
1' (305mm) Minimum
2' (610mm) Minimum
3' (914mm) Minimum
4' (1.22m) Minimum
2' (610mm) Maximum
4' (1.22m) Maximum
6' (1.86m) Maximum
8' (2.4m) Maximum
B)
C)
D)
With the above options, maximum total pipe length if 37 feet with
minimum of 4 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 7
Diagram 8
IMPORTANT
When installing this unit vertically, the 45o elbow when installed in
conjunction with the Simpson Dura-Vent Adaptor will pertrude past the
unit 1-1/2" (38mm) when measured from the rear standoffs.
Note:A1-1/4"(32mm)clearancefromtheelbowmustalsobemaintained.
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
17
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Vertical Venting with Two (2) 90o Elbows
Vertical Venting with Two (2) 90o Elbows
Option
A)
V
H + H1
Option
A)
V
H
1' (305mm) Minimum
2' (610mm) Minimum
3' (914mm) Minimum
4' (1.22m) Minimum
2' (610mm) Maximum
4' (1.22m) Maximum
6' (1.86m) Maximum
8' (2.4m) Maximum
1' (305mm) Minimum
2' (610mm) Minimum
3' (914mm) Minimum
4' (1.22m) Minimum
5' (1.5m) Minimum
6' (1.86m) Minimum
4' (1.22m) Maximum
6' (1.86m) Maximum
9' (2.7m) Maximum
12' (3.6m) Maximum
15' (4.5m) Maximum
17' (5.1m) Maximum
B)
C)
D)
B)
C)
D)
E)
With the above options, maximum total pipe length if 37 feet with
minimum of 4 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
F)
With the above options, maximum total pipe length if 37 feet with
minimum of 6 feet total vertical and maximum 17 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 9
Diagram 10
Vertical Venting with Three (3) 90o Elbows
Option
A)
V + V1
H
H + H1
2' (610mm) Min. 1' (305mm) Max. 2' (610mm) Max.
3' (914mm) Min. 4' (1.22m) Max. 5' (1.5m) Max.
4' (1.22mm) Min. 6' (1.86m) Max. 8' (2.4m) Max.
B)
C)
D)
5' (1.5m) Min.
8' (2.4m) Max.
12' (3.6m) Max.
With the above options, maximum total pipe length if 37 feet with
minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 11
18
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Vertical Venting with Three (3) 90o Elbows
Option
A)
V + V1
H + H1
2' (610mm) Minimum
3' (914mm) Minimum
4' (1.22m) Minimum
5' (1.5m) Minimum
3' (914mm) Maximum
6' (1.86m) Maximum
9' (2.7m) Maximum
12' (3.6m) Maximum
B)
C)
D)
With the above options, maximum total pipe length if 37 feet with
minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 12
gram 1. Push the pipe sections com-
HORIZONTAL
INSTALLATIONS
pletely together, then twist-lock one
section clockwise approximately one-
quarter turn, until the two sections are
fullylocked. Thefemalelockinglugswill
not be visible from the outside, on the
Black Pipe or fittings. They may be
located by examining the inside of the
female ends.
Install the vent system according to the
manufacturer's instructions included
with the components.
1) Set the unit in its desired location. Check to
determine if wall studs or roof rafters are in
the way when the venting system is at-
tached. If this is the case, you may want to
adjust the location of the unit. Rough in the
gas.
Diagram 2
2) Direct Vent pipe and fittings are designed
with special twist-lock connections to con-
necttheventingsystemtotheapplianceflue
outlet. A twist-lock appliance adaptor is an
available option that must be used in con-
junction with the Simpson Dura-Vent Direct
Vent GS system.
Note:
a) Thehorizontalrunofventmustbelevel,
or have a 1/4 inch rise for every 1 foot
of run towards the termination. Never
allow the vent to run downward. This
could cause high temperatures and
may present the possibility of a fire.
Diagram 1
Note: Apply sealant "Mill-Pac" to inner
pipe and high temperature sili-
cone sealant to outer pipe on eve-
ry twist-lock joint.
3) Putabeadofsiliconeinsidetheoutersection
of the adapter and a bead of Mill Pac on the
inner collar. Slip the adapter over the exist-
ing inner and outer flue collar and fasten to
the outer collar only with the 3 supplied
screws (drilling pilot holes will make this
easier). Level the fireplace and fasten it to
the framing using nails or screws through
the nailing strips.
b) The location of the horizontal vent ter-
mination on an exterior wall must meet
alllocalandnationalbuildingcodes,and
must not be blocked or obstructed. For
External Vent Terminal Locations, see
diagram on page 12.
b) Horizontal runs of vent must be sup-
ported every three feet. Wall straps are
available for this purpose.
5) Mark the wall for a 10" x 10" square hole.
Thecenterofthesquareholeshouldlineup
with the centerline of the horizontal pipe.
Cutandframethe10inchsquareholeinthe
exterior wall where the vent will be termi-
nated. If the wall being penetrated is con-
structed of non-combustible material, i.e.
masonry block or concrete, a 7"(178mm)
dia. (7-1/2"(191mm) dia. for flex) hole is
acceptable.
6) The arrow on the vent cap should be
pointing up. Insure that the 1-1/2" clear-
ances to combustible materials are main-
tained (Diagram 3 on page 16). Install the
termination cap.
4) Assemble the desired combination of pipe
and elbows to the appliance adaptor and
twist-lock for a solid connection.
Note:
The four wood screws provided should be
replaced with appropriate fasteners for
stucco, brick, concrete, or other types of
sidings.
a) Twist-lockprocedure:Fourindentations,
located on the female ends of pipes and
fittings, are designed to slide straight
ontothemaleendsofadjacentpipesand
fittings, by orienting the four pipe inden-
tations so they match and slide in to the
four entry slots on the male ends, Dia-
Note: With Dura-Vent, the minimum height
is achieved by installing a 45o elbow di-
rectly to the flue adaptor.
Note: If installing termination on a siding
covered wall, a vinyl siding stand-
off or furring strips must be used
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
19
INSTALLATION
4) Assemble the desired lengths of pipe and
elbows. Ensure that all pipes and elbow
connections are in the fully twist-locked
position and sealed.
VERTICAL
TERMINATION
1) Maintain the 1-1/4" clearances (air
spaces) to combustibles when
passing through ceilings, walls,
roofs, enclosures, attic rafter, or
other nearby combustible surfac-
es. Do not pack air spaces with
insulation. Check pages 17-19 for
the maximum vertical rise of the
venting system and the maximum
horizontal offset limitations.
5) Cut a hole in the roof centered on the small
drilled hole placed in the roof in Step 2. The
hole should be of sufficient size to meet the
minimumrequirementsforclearancetocom-
bustibles of 1-1/4". Slip the flashing under
the shingles (shingles should overlap half
the flashing) as per Diagram 4.
Diagram 3
2) Setthegasapplianceinits
desired location. Drop a
plumb bob down from the
ceiling to the position of
theapplianceflueexit,and
to ensure that the termination is
not recessed into the siding.
7) Before connecting the horizontal run of
vent pipe to the vent termination, slide the
WallThimble(Part#942)overtheventpipe.
Diagram 1
mark the location where
the vent will penetrate the
ceiling. Drill a small hole at his point. Next,
drop a plumb bob from the roof to the hole
previouslydrilledintheceiling,andmarkthe
spot where the vent will penetrate the roof.
Determine if ceiling joists, roof rafters or
other framing will obstruct
the venting system. You may
wish to relocate
theapplianceor
to offset, as
shown in Dia-
gram 2 to avoid
cutting load
bearing mem-
Diagram 4: The upper half of the flashing is
installed under the roofing material and not
nailed down until the chimney is installed.
This allows for small adjustments.
8) Slide the appliance and vent assembly to-
wards the wall carefully inserting the vent
pipe into the vent cap assembly. It is impor-
tant that the vent pipe extends into the vent
cap sufficient distance so as to result in a
minimum pipe overlap of 1-1/4 inches. Se-
cure the connection between the vent pipe
and the vent cap by attaching the two sheet
metal strips extending from the vent cap
assembly into the outer wall of the vent
pipe. Use the two sheet metal screws
provided to connect the strips to the pipe
section. See Diagram 4.
6) Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic
to avoid obstructions, it is impor-
tant to support the vent pipe every
3 feet, to avoid excessive stress
on the elbows, and possible sep-
aration. Wall straps are available
for this purpose (Diagram 2).
bers.
9) Install wall thimble in the center of the 10"
square and attach with wood screws (Di-
agram 5).
Galvanized pipe is desirable above the roof-
line due to its higher corrosion resistance.
Continue to add pipe sections through the
flashing until the height of the vent cap meets
theminimumheightrequirementsspecifiedin
Diagram 5 or local codes. Note that for steep
Diagram 2
Note: Apply sealant "Mill-Pac" to inner
pipe and high temperature sili-
cone sealant to outer pipe on eve-
ry twist-lock joint.
Diagram 5
3) A Firestop spacer must be installed in the
floor or ceiling of every level. To install the
Firestop spacer in a flat ceiling or wall, cut
a 10 inch square hole. Frame the hole as
shown in Diagram 3 and install the firestop.
Roof Pitch
Minimum Vent Height
Feet
2
Meters
0.61
0.61
0.61
0.76
0.99
1.22
1.52
1.83
2.13
2.29
2.44
flat to 7/12
over 7/12 to 8/12
over 8/12 to 9/12
over 9/12 to 10/12
over 10/12 to 11/12
over 11/12 to 12/12
over 12/12 to 14/12
over 14/12 to 16/12
over 16/12 to 18/12
over 18/12 to 20/12
over 20/12 to 21/12
2
Diagram 4
2
2.5
3.25
4
5
6
7
7.5
8
Diagram 5
Diagram 3
20
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
roof pitches, the vertical height must be
increased. A poor draft, or down drafting
can result from high wind conditions near big
trees or adjoining roof lines, in these cases,
increasing the vent height may solve the
problem.
inside each other and can be adjusted for
2 x 4 or 2 x 6 walls. The liners must slip
over the collars a minimum of 1-3/8".
Note: To make the
installation more
aesthetically pleas-
ing, we recom-
mend framing out a
square to mount
the terminal to.
5) Slip the assembled liner and termination
assembly through the thimble making sure
the termination cap faces up (there are
markings on the cap that show which way
is up). This will position the termination cap
with proper down slope for draining water.
Fasten the cap to the outer wall with the 4
supplied screws.
7) Ensure vent is vertical and secure the base
of the flashing to the roof with roofing rails,
slide storm collar over the pipe section and
seal with a mastic.
8) Install the vertical termination cap by twist-
be used to ensure that the termi-
nation is not recessed into the
siding.
locking it.
6) Pull the centre 4"(100mm) liner and outer
6-7/8"(175mm) liner out enough to slip over
the flue collars of the fireplace. (You may
wish to cut the liner shorter to make it more
workable.) Do not bend liner more than 45o.
Note: Any closets or storage spaces,
which the vent passes through
must be enclosed.
2) Level the fireplace and fasten it to the
framing using nails or screws through the
nailing strips.
7) Apply Mill Pac over the fireplace inner collar
and slip the 4"(100mm) liner down over it
and attach with 3 supplied screws.
OffsetChart
3) Assemble the vent assembly by applying
Mill Pac to the 4"(100mm) inner collar of the
terminationand slippingthe4"(100mm)liner
over it at least 1-3/8" (35mm). Fasten with
the 3 screws (drilling pilot holes will make
this easier). Apply Mill Pac or high temper-
aturesiliconetothe6-7/8"(175mm)flexpipe
and slip it over the 6-7/8" outer collar of the
vent terminal at least 1-3/8"(35mm) and
fasten with the 3 screws.
8) Do the same with the 6-7/8"(175mm) liner.
9) Apply a bead of silicone between the thim-
ble and termination and around the outer
edge of the terminal at the wall in order to
keep the water out.
IMPORTANT: Do not locate termination
hood where excessive snow or ice build-
up may occur. Be sure to check vent
terminationareaaftersnowfalls, andclear
to prevent accidental blockage of venting
system. When using snow blowers, make
sure snow is not directed towards vent
termination area.
NOTE: Horizontal sections must be sup-
ported at intervals not exceeding 3
feet (0.9 meter). (Flame picture and
performance will be affected by
sags in the liner).
4) Separatethe2halvesofthewallthimbleand
securely fasten the one with the tabs to the
outside wall making sure that the tabs are
on top and bottom. Fasten the other thimble
halftotheinsidewall.Thethimblehalvesslip
INSTALLATION
PROCEDURES
for Regency AstroCapTM Direct
Vent System (Flex)
1) Locate the unit in the framing, rough in the
gas. Locate the centerline of the termina-
tion and mark wall accordingly. Cut a
10"(254mm) hole in the wall (inside dimen-
sion).
Note: A 1-1/2"(38mm) clearance around
the liner must be maintained ex-
cept that only a 1" (25mm) clear-
ance is needed at the termination
end. We recommend framing a
10"(254mm) x 10"(254mm) (inside
dimensions) hole to give struc-
tural rigidity for mounting the ter-
mination.
Note: If installing termination on a siding
covered wall, furring strips must
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
21
INSTALLATION
CONVERSION KIT FROM NATURAL GAS TO PROPANE MODEL #730-969
FOR P121-1/P121LC-1/P121RC-1/P131-1 USING SIT 820 NOVA GAS VALVE
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER
IF IN DOUBT DO NOT DO THIS CONVERSION !!
Conversion Kit Contains:
5) Pull off the pilot
cap to expose the
pilot orifice.
Qty. Part # Description
1
910-018 SIT Conversion Kit-50%
Turndown LP
1
1
1
1
1
910-037 LP Injector (Pilot Orifice)
*
Burner Orifice #50
908-255 Decal "Converted to Propane"
908-529 5/32" Allen Key
918-032 Instruction Sheet
6) Unscrew the pilot orifice with the allen key
and replace with the LP pilot orifice in the kit
and replace pilot cap.
1) Removethelouversandtrimkit.Removethe
front door.
2) Remove the logs, embers.
3) Remove the grate by lifting straight up.
Remove the side brick panels (if installed).
The brick panel is very fragile - handle
with care.
7) Remove burner orifice with a 1/2" wrench
and discard. Use another wrench to hold
on to the elbow behind the orifice.
4) Remove the burner assembly by removing
the 4 Phillips head screws and then slide
the burner assembly away from the orifice
and lift out.
Burner Orifice
8) ReinstallnewburnerorificeLPstamped#50
and tighten.
9) Remove and discard the 3 pressure regu-
lator mounting screws (A), pressure regu-
lator tower (B) and diaphragm (C).
10) Insure that the rubber gasket (D) is properly
positioned and install the new HI/LO pres-
sure regulator assembly to the valve using
the new screws (E) supplied with the kit.
Tighten screws securely.
Diagram 1: Remove the left and right
screws and then slide the burner assembly
away from the orifice and lift out.
11) Reverse steps 4) to 1).
14) Check for gas leaks.
12) Attach clear label "This unit has been con-
verted to Propane" near or on the serial #
decal. Attach white label "This valve has
been converted from NG to LPG using SIT
conversion Kit Code 0.907.202" onto the
valve.
15) Check inlet and outlet pressures.
16) Check operation of flame control.
17) Check for proper flame appearance and
glow on logs.
13) Replace yellow "Natural Gas" label with red
"Propane" label
22
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
For USA installations follow local codes and/or The manifold pressure is controlled by a regu-
the current National Fuel Gas Code, ANSI lator built into the gas control, and should be
P121/P121LC/P121RC/P131-NG1
System Data
Z223.1.
checked at the pressure test point.
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes: #31
When using copper or flex connectors use only Note: To properly check gas pressure,
approved fittings. Always provide a union so
that gas lines can be easily disconnected for
servicing. Flare nuts for copper lines and flex
connectors are usually considered to meet this
requirement.
both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.
Max. Input Rating 40,000 Btu/h
Min. Input Rating 20,500 Btu/h
1) Makesurethevalveisinthe"OFF"position.
Supply Pressure min.5.0" w.c.
Important: Always check for gas leaks 2) Loosen the "IN" and/or "OUT" pressure
Manifold Pressure
with a soap and water solution or gas
leak detector. Do not use open flame for
leak testing.
tap(s), turning counterclockwise with a
1/8" wide flat screwdriver.
(High)
3.8"+/- 0.2"w.c.
Log Set: Ceramic fibre, 8 per set.
3) Attach manometer to "IN" and/or "OUT"
Vent System: Regency AstrocapTM, Re-
gency Direct Vent System (Flex) and Simp-
son Dura-Vent Direct Vent System
pressure tap(s) using a 5/16" ID hose.
PILOT ADJUSTMENT
4) Light the pilot and turn the valve to "ON"
position.
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits specified on the safety
label.
P121/P121LC/P121RC/P131-LP1
System Data
Conversion Kit# 730-969
6) When finished reading manometer, turn off
the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8"
flat screwdriver. Note: Screw should be
snug, but do not over tighten.
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes: #50
Max. Input Rating 39,000 Btu/h
Min. Input Rating 20,600 Btu/h
Periodically check the pilot flames. Cor-
rect flame pattern has three strong blue
flames: 1 flowing around the thermopile,
1 around the thermocouple and 1 flowing
across the burner (it does not have to be
touching the burner).
Supply Pressure min.12.0" w.c.
S.I.T. VALVE DESCRIPTION
Manifold Pressure
1) Gas cock knob
2) Manual high/low adjustment
3) Pilot Adjustment
4) Thermocouple Connection - option
5) Outlet Pressure Tap
6) Inlet Pressure Tap
7) PilotOutlet
8) Main Gas Outlet
9) Alternative TC Connection
Point
(High)
11"+/- 0.2" w.c.
Log Set: Ceramic fibre, 8 per set.
Note: If you have an incorrect flame pat-
tern, contact your Regency dealer
for further instructions.
Vent System: Regency AstrocapTM, Re-
gency Direct Vent System (Flex) and Simp-
son Dura-Vent Direct Vent System
Incorrect flame pattern will have small,
probably yellow flames, not coming into
proper contact with the rear burner or
thermopile or thermocouple.
HIGH ELEVATION
This unit is approved in Canada for altitude 0 to
4500 ft. (CAN1 2.17-M91).
GAS LINE
INSTALLATION
The gas line can be brought through either the
right,theleftside orthebottomoftheappliance.
The gas valve is situated on the bottom of the
unit.
GAS PIPE PRESSURE
TESTING
The gas line connection may be made of rigid
pipe, copper pipe or an approved flex connec-
tor. (If you are using rigid pipe, ensure that the
valve can be removed for servicing.) Since
somemunicipalitieshaveadditionallocalcodes
it is always best to consult with your local
authorities and the CAN/CGA B149 installation
code.
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig. (3.45
kPa). Disconnect piping from valve at pres-
sures over 1/2 psig.
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
23
INSTALLATION
1) Carefully remove the logs from the box and unwrap them. The logs
LOG INSTALLATION
are fragile, handle with care - do not force into position.
Read the instructions below carefully and refer to the diagrams.
If logs are broken do not use the unit until they are replaced.
Broken logs can interfere with the pilot operation.
2) Place Log 02-79 on the front right side of the burner. Ensure that the
notches on the far right side of the log fit into the grate posts. Push
back side of the left end of the log up against the tab on the burner.
The gas log kit (Part # 360-930) contains the following pieces:
a) 02-79 Front Right Log
b) 02-80 Front Left Log
c) 02-81 Middle Right Log
d) 02-82 Middle Left Log
902-326
902-327
902-328
902-329
902-154
e)
Embers
02-79
Please note that there are 2 of each log. This
log set is mirrored front and back.
02-79
02-80
Push back side of the left end of the log up
against the tab on the burner.
Repeat step 2 on the opposite side of the burner.
02-79
02-79
02-82
02-81
The "02" reference numbers (i.e. 02-79) are
molded into the rear of each log.
The image below shows all of the logs in place.
3) Place Log 02-80 on the front left side of the burner. Position
the right end of the log in between the two tabs and the left
end of the log into the grate post.
02-81
02-79
02-82
02-80
02-80
Tab on Burner
Grate Post
02-80
02-82
02-79
02-81
24
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Repeat step 3 on the opposite side of the burner.
Repeat step 5 on the opposite side of the burner.
02-82
02-80
02-80
02-82
4) Embers should be placed in front of Log 02-79 and Log 02-80 and also
down the middle between the logs as shown in the image below.
6) Place Log 02-81 on the middle right side of the burner. Ensure that
the log fits over the 2nd grate post from the right.
02-81
Caution: Do NOT cover burner ports.
Grate Post
5) Place Log 02-82 on the middle left side of the burner. Rest the bottom
of the Log onto the second grate post from the left. Ensure that the log
fits into a pin that is on Log 02-79.
Repeat step 6 on the opposite side of the burner.
02-81
02-81
02-82
02-79
Place Log 02-82 onto pin.
Grate Post
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
25
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
GLASS DOOR
REMOVAL
FINISHING TRIM
LOUVERS & GRILLS
1) SlidetheSideFinishingTrimupintotheslot
in the top flange of the fireplace. Push tight
against the magnet at the base of the unit.
1) Attach the screws provided to the top left
and right corners.
1) Remove the 8 screws that secure the
glass door.
NOTE: Do not tighten the screw entirely,
ensure that some room is left to be able
to hang the grill or louver over the screw.
Slide Trim into
slot.
2) Hang the Top Louver or Grill onto the 2
screws in the top fireplace opening.
2) Pull the door slightly out on an angle and
then lift up and pull completely out.
Push trim tight
against magnet.
3) Attach the Bottom Louver or Grill to the
hingesonthebottomflangeofthefireplace.
2) Slide the Corner Finishing Trim up into the
slot in the top flange of the fireplace. Push
tight against the magnet at the base of the
unit.
P121-1 & P131-1 Corner Models
Slide Trim into
slot.
4) Attach the screws provided to the top and
bottom, left and right corners similar to step
1.
5) Hang the top and bottom louver or grill onto
the screws in the top and bottom, left and
right sides of the fireplace opening.
3) P131 & P121LC/P121RC Corner Model:
Remove the 6 screws that secure the
glass door and repeat step 2.
Push trim tight
against magnet.
The Top and Bottom Side Louver or Grill is
installed the same way.
26
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Option 1:
Option 3:
Option 2:
REMOTE CONTROL
WALL THERMOSTAT
WALL SWITCH
Can be used with Option 2 or 3
but not both.
Can be used with Option 1 or 3
but not both.
Can be used with Option 1 or 2
but not both.
Use the Regency Remote Control Kit approved
for this unit. Use of other systems may void your
warranty.
1) Run the supplied 15' of wire through the
back gas inlet opening. Be careful not to
damage wire.
A wall thermostat may be installed if desired,
connect the wires as per the wiring diagram.
Use the table below to determine the maximum
wire length.
The remote control kit comes with a hand held
transmitter, a receiver and a wall mounting
plate.
Note: We recommend a maximum of 15'
of wire but if you wish to go with a
longer run, use the Thermostat
Wire Table.
Note: Preferable if the thermostat is in-
stalled on an interior wall.
1) Choose a convenient location on the wall to
install the receiver and the receptacle box
(protection from extreme heat is very im-
portant). Run wires from the fireplace to
that location. Use the Thermostat Wire Ta-
ble.
Regencyoffersanoptionalprogrammablether-
mostat but any 250-750 millivolt rated non-
anticipator type thermostat that is CSA, ULC or
UL approved may be used.
2) Connect the wire to the supplied wall switch
and install into the receptacle box.
CAUTION
Do not connect millivolt
wall switch wire to a 120V wire.
CAUTION
2) Connect the two wires to the gas valve.
Do not connect millivolt
wall thermostat wires
to a 120V wire.
See diagram below.
Thermostat Wire Table
Recommended Maximum Lead Length
(Two-Wire) When Using Wall
CAUTION
Thermostat (CP-2 System)
Do not connect millivolt remote
control wires to a 120V wire.
Wire Size
Max. Length
14 GA.
16 GA.
18 GA.
20 GA.
22 GA.
50 Ft.
32 Ft.
20 Ft.
12 Ft.
9 Ft.
3) Install 3 AAA alkaline batteries in transmitter
and 4 AA alkaline batteries in the receiver.
Install the receiver and its cover in the wall.
Switch the remote receiver to "remote"
mode. The remote control is now ready for
operation.
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
27
INSTALLATION
WIRING DIAGRAM
No electrical power supply is required for the
gas control to operate. 120 Volt AC power is
needed for the fan switch and blower. The fan
can be hard wired if desired. A terminal block
is provided on the left hand side of the unit. A
three wire power cord can also be used and
plugged into a suitable receptacle.
(Do not cut the ground terminal off under
any circumstances.)
Caution: Ensure that the wires do
not touch any hot surfaces and are
away from sharp edges.
CAUTION:
Label all wires
prior to disconnection when
servicing controls. Wiring er-
rors can cause improper and
dangerous operation.
28
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING INSTRUCTIONS
CAUTION: Carbon will be produced if air
shutter is closed too much.
6) Rotate the flame height regulator to adjust
OPERATING
the flame height higher or lower.
INSTRUCTIONS
Note: Any damage due to carboning re-
sulting from improperly setting
the aeration controls is NOT cov-
ered under warranty.
1) Read and understand these instructions
SHUTDOWN
PROCEDURE
before operating this appliance.
2) Check to see that all wiring is correct and
1) Use the wall switch, thermostat or remote
enclosed to prevent possible shock.
control to turn off the main burner.
3) Check to ensure there are no gas leaks.
2) Turn the main gas control clockwise to the
"OFF" position to turn off the pilot.
4) Make sure the glass in the door frame is
properly positioned. Never operate the ap-
pliance with the glass removed.
FIRST FIRE
5) Verify that the venting and cap are unob-
Adjustment Wire - Pull down to open or
push up to close aeration cap.
structed.
DO NOT BURN THE APPLIANCE
WITHOUT THE GLASS FRONT IN
PLACE.
6) Ensure that the brick panels are installed.
Closed - Tall yellow
Open - Short Blue
7) Verify log placement. If the pilot cannot be
seen when lighting the unit, the logs have
been incorrectly positioned.
The first fire in your stove is part of the paint
curing process. To ensure that the paint is
properly cured, it is recommended that you burn
your fireplace for at least four (4) hours the first
time before you use it with the fan on.
Note: Aeration Adjustment should only
be performed by an authorized
Regency Installer at the time of
installation or service.
8) The unit should never be turned off, and on
again without a minimum of a 60 second
wait.
When first operated, the unit will release an
odour caused by the curing of the paint, the
burning off of any oils remaining from manufac-
turing. Smoke detectors in the house may go off
at this time. Open a few windows to ventilate the
room for a couple of hours.
NORMAL OPERATING
SOUNDS OF GAS
APPLIANCES
Note: When the glass is cold and the
appliance is lit, it may cause con-
densation and fog the glass. This
condensation is normal and will
disappear in a few minutes as the
glass heats up.
It is possible that you will hear some sounds
from your gas appliance. This is perfectly nor-
mal due to the fact that there are various gauges
and types of steel used within your appliance.
Listed below are some examples. All are nor-
mal operating sounds and should not be
considered as defects in your appliance.
LIGHTING
PROCEDURE
IMPORTANT Gas cock knob cannot be
turned from "PILOT" to "OFF" unless it is
partially depressed.
During the first few fires, a white film
may develop on the glass front as part of
the curing process. The glass should be
cleaned after the unit has cooled down
or the film will bake on and become very
difficult to remove. Use a non-abrasive
cleaner and DO NOT ATTEMPT TO CLEAN
THE GLASS WHILE IT IS HOT.
Blower:
Regency gas appliances use high tech blowers
to push heated air farther into the room. It is not
unusual for the fan to make a "whirring" sound
when ON. This sound will increase or decrease
in volume depending on the speed setting of
your fan speed control.
1) Turn burner OFF using "ON/OFF" switch.
2) Turn gas control knob so indicator points to
"OFF" position and allow 5 minutes for any
gas in the combustion chamber to escape.
Burner Tray:
3) Turn gas control knob counterclockwise
so indicator points to the "PILOT" position.
Depress the gas control knob fully. De-
press the igniter button several times until
the pilot lights. After approximately one
minute, release the gas control knob. The
pilot flame should continue to burn. If the
pilot does not remain lit, repeat operation
allowing a longer period before releasing
gas control knob.
The burner tray is positioned directly under the
burner tube(s) and logs and is made of a
different gauge material from the rest of the
firebox and body. Therefore, the varying thick-
nesses of steel will expand and contract at
slightly different rates which can cause "tick-
ing" and "cracking" sounds. You should also be
aware that as there are temperature changes
within the unit these sounds will likely re-occur.
Again, this is normal for steel fireboxes.
AERATION
ADJUSTMENT
The air shutter can be adjusted by moving the
adjusting wire up or down. The wire is ac-
cessed through the bottom louver opening.
Open the air shutter for a blue flame or close for
a yellower flame. The burner aeration is factory
setbutmayneedadjustingduetoeitherthelocal
gas supply or altitude.
4) When the pilot stays lit, turn the gas knob
further counterclockwise to the "ON" po-
sition.
Blower Thermodisc:
When this thermally activated switch turns ON
it will create a small "clicking" sound. This is the
switch contacts closing and is normal.
Minimum Air Shutter Opening:
5) Use the wall switch, thermostat or remote
3/16"
3/8"
Natural Gas
Propane
control to turn on the unit.
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
29
OPERATING INSTRUCTIONS
Unit Body/Firebox:
Pilot Flame:
While the pilot flame is on it can make a very
slight "whisper" sound.
MAINTENANCE
INSTRUCTIONS
Different types and thicknesses of steel will
expand and contract at different rates resulting
in some "cracking" and "ticking" sounds will be
heard throughout the cycling process.
Gas Control Valve:
1) Always turn off the gas valve before
cleaning. For relighting, refer to lighting
instructions. Keep the burner and control
compartment clean by brushing and vacu-
uming at least once a year. When cleaning
the logs, use a soft clean paint brush as the
logs are fragile and easily damaged.
As the gas control valve turns ON and OFF, a
dullclickingsoundmaybeaudible,thisisnormal
operation of a gas regulator or valve.
Copy of the Lighting Plate Instructions
FOR YOUR SAFETY READ BEFORE LIGHTING
2) Cleanapplianceanddoorwithadampcloth
(never when unit is hot). Never use an
abrasive cleaner. The glass should be
cleaned with a gas fireplace glass cleaner.
The glass should be cleaned when it
starts looking cloudy.
This appliance must be installed in accordance with local codes, if any; if not, follow
thecurrentCAN1-B149/ANSIZ223.1(Australia:AG601,NewZealand:NZS5261)
WARNING: If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal injury or loss
oflife.Improperinstallation,adjustment,alteration,serviceormaintenance
can cause injury or property damage. Refer to the owner’s information
manual provided with this appliance. For assistance or additional
information consult a qualified installer, service agency or gas supplier.
3) The heater is finished in a heat resistant
paint and should only be refinished with
heat resistant paint. Regency uses Stove-
Bright Paint - Metallic Black #6309.
A)This appliance has a pilot which C)Use only your hand to push in or turn
must be lighted by hand. When
lighting the pilot, follow these
instructions exactly.
the gas control knob. Never use tools.
If the knob will not push in or turn by
hand, don’ttrytorepairit, callaqualified
service technician. Force or attempted
repair may result in a fire or explosion.
4) Make a periodic check of burner for proper
position and condition. Visually check the
flame of the burner periodically, making
sure the flames are steady; not lifting or
floating. Ifthereisaproblem, callaqualified
service person.
B)BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to
smell next to the floor because some D) Do not use this appliance if any part has
gas is heavier than air and will settle
on the floor.
been under water. Immediately call a
qualifiedservicetechniciantoinspectthe
appliance and to replace any part of the
controlsystemandanygascontrolwhich
has been under water.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electric switch, do
not use any phone in your building
5) The appliance and venting system must be
inspected before use, and at least annual-
ly, by a qualified field service person, to
ensure that the flow of combustion and
ventilation air is not obstructed.
This appliance needs fresh air for safe
- Immediately call your gas supplier operationandmustbeinstalledsothereare
from a neighbours phone. Follow the provisions for adequate combustion and
gassupplier’sinstructions.
- Ifyoucannotreachyourgassupplier,
call the fire department.
ventilation air.
Note: Never operate the appliance with-
out the glass properly secured in
place.
CAUTION:Hotwhileinoperation.Donottouch.SevereBurnsmayresult.Due
tohighsurfacetemperatureskeepchildren,clothingandfurniture,gasoline
and other liquids having fammable vapors away. Keep burner and control
compartment clean. See installation and operating instructions
accompanyingappliance.
6) Do not use this appliance if any part has
been under water. Immediately call a qual-
ified service technician to inspect the ap-
pliance and to replace nay part of the
control system and any gas control which
has been under water.
LIGHTING INSTRUCTIONS
STOP! Read the safety information 4) Push in control knob all the way and
above on this label.
1) Push in gas control knob slightly and
turn clockwise
hold in. Continually push and release
the black button on spark igniter until
pilot lights. Continue to hold the
control knob in for about 1/2 minute
after the pilot is lit. Release knob and
it will pop back up. Pilot should remain
lit. If it goes out, repeat steps 1) to 4).
If knob does not pop up when released,
stop and immediately call your service
technicianorgassupplier.Ifthepilotwill
notstaylitafterseveraltries,turnthegas
control knob to “OFF” and call your
service technician or gas supplier.
to “OFF”. Knob
cannotbeturnedfrom“PILOT”to“OFF”
unless knob is pushed in slightly. Do
notforce.
2) Wait five (5) minutes to clear out any
gas. IfyouthensmellgasSTOP!follow
“B” in the safety information above on
this label. If you don’t smell gas, go to
the next step.
7) In the event this appliance has been serv-
iced check that the vent-air system has
been properly resealed & reinstalled in
accordance with the manufacturer's in-
structions.
8) Verify operation after servicing.
3) Turn knob on gas control counter-
clockwise
to“PILOT”.
PILOT BURNER
VEILLEUSE
5) Turn gas control knob
OFF
General Vent Maintenance
counterclock-wise
to “ON”.
THERMOPILE
Conduct an inspection of the venting system
semi-annually.Recommendedareastoinspect
as follows:
6) Use rocker switch to op-
erate main burner.
ELEMENT
THERMO-
ELECTRIQUE
TO TURN OFF GAS APPLIANCE
1) Check the Venting System for corrosion in
areas that are exposed to the elements.
These will appear as rust spots or streaks,
and in extreme cases, holes. These com-
ponents should be replaced immediately.
2) Turn off all electric power to the
appliance if service is to be performed.
1) Push in the gas control knob slightly and
turn clockwise to “OFF”. Do not force.
You may shut off the pilot during prolonged non use periods to conserve fuel.
908-017a
DO NOT REMOVE THIS INSTRUCTION PLATE
30
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
2) Remove the Cap, and shine a flashlight
down the Vent. Remove any bird nests, or
other foreign material.
GLASS GASKET
REMOVING VALVE
If the glass gasket requires replacement use
a tadpole glass gasket (Part # 936-155).
1) Shut off the gas supply.
3) Check for evidences of excessive con-
densation, such as water droplets forming
intheinnerliner,andsubsequentlydripping
out the joints, Continuous condensation
can cause corrosion of caps, pipe, and
fittings. It may be caused by having exces-
sive lateral runs, too many elbows, and
exterior portions of the system being ex-
posed to cold weather.
2) Removethelouversandtrimkit.Removethe
front door.
3) Remove the logs, embers.
DOOR GLASS
4) Remove the grate by lifting straight up.
Your Regency fireplace is supplied with high
temperature 5mm-Tempered glass & 5mm-Ce-
ramic glass. If your glass requires cleaning, we
recommend using an approved glass cleaner
available at all authorized dealers. Do not use
abrasive materials.
4) Inspect joints, to verify that no pipe sections
or fittings have been disturbed, and conse-
quently loosened. Also check mechanical
supports such as Wall Straps, or plumbers'
tape for rigidity.
CAUTION&WARNINGS:
* Do not clean when the glass is hot.
* Theuseofsubstituteglasswillvoidallproduct
warranties.
* Care must be taken to avoid breakage of the
glass.
* Do not strike or abuse the glass.
* Do not operate this fireplace without the glass
front or with a cracked or broken glass front.
* Wear gloves when removing damaged or
broken glass.
* Replacement of the glass panels should be
done by a licensed or qualified service per
son.
LOG REPLACEMENT
5) Remove the side brick clip in the top of the
firebox and then slide the Side Brick Panel
out. The brick panels are very fragile
- handle with care.
Theunitshouldneverbeusedwithbrokenlogs.
Turn off the gas valve and allow the unit to cool
before opening door and carefully remove the
logs. (The pilot light generates enough heat to
burn someone.) If for any reason a log should
need replacement, you must use the proper
replacement log. The position of these logs
must be as shown in the diagrams under Log
Installation.
GLASSREPLACEMENT
Note: Improper positioning of logs may
create carbon build-up and will
severely alter the unit's perform-
ance which is not covered under
warranty.
In the event that you break your glass by impact,
purchase your replacement from an authorized
Regency dealer only. Replacement glass is
shipped already installed into the door frame.
Reinstall as per Glass Door Installation on page
22.
THERMOPILE/
THERMOCOUPLE
REPLACEMENTPARTS:
6) Remove the burner by removing the 4
screws.
Front Door - Tempered (Part# 360-528)
Side Door - Tempered (Part# 360-529)
Front Door - Ceramic (Part# 360-538)
Side Door - Ceramic (Part# 360-539)
1) OpentheBottomLouversorGrills.Remove
the Top Louver or Grill.
2) Remove the Trim Kit, Glass Door, Log Set,
Grate and Burner Assembly (see page 26).
3) Disconnect thermocouple by loosening nut
from the valve with a 9mm wrench. Discon-
nect thermopile by loosening 2 screws
marked TP on the valve.
GOLD-PLATED
ACCESSORIES
The 24 carat gold-plated finish requires little
maintenance, and need only be cleaned with a 7) Slide the burner assembly away from the
damp cloth. DO NOT use abrasive materials or
chemical cleaners, as they may harm the finish
and void the warranty. Clean any finger-
prints off before turning the unit on.
4) Remove 2 screws from the pilot assembly
and pull up far enough to be able to loosen
thethermocoupleorthermopilewitha7/16"
wrench. NOTE: the pilot line is very fragile,
use caution when pulling it up.
orifice and lift out.
5) Drop the thermocouple or thermopile down
through the extrusion and pull it out of the
unit.
6) Reinstall the new ones in reverse order.
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
31
MAINTENANCE
8) Remove the Side Base Brick Panels and 13) Undo the pilot tube from the valve with a
INSTALLING VALVE
finally the Long Base Brick Panels.
7/16" wrench.
14) Undo the quick drop out thermocouple nut
on the valve with a 9mm (metric) wrench.
1) Attach the valve to the valve bracket with
the 6 (m5x8 metric) screws provided.
15) Remove the Piezo igniter wire and push
button assembly.
2) Reconnect the "gas out" flare fitting with an
11/16" wrench.
16) Undo the "gas out" flare nut with a 13/16"
wrench.
3) Reconnect the "gas out" flare nut with a 13/
16" wrench.
17) Undo the "gas out" flare fitting with an
11/16" wrench.
4) Install piezo ignitor push button assembly
and reconnect wire.
Remove Left & Right Side Base
Brick Panels
18) Removethe6Phillipsheadscrewsfromthe
sides of the valve bracket and remove
valve.
5) Reconnectthequickdropoutthermocouple
nut with a 9mm wrench.
6) Reconnect the pilot tube nut with a 7/16"
Hint: If you are using black pipe, ensure
that there is a union by the valve,
otherwise removal will be almost
impossible.
wrench.
7) Scrape off the old gasket from the floor of
the firebox and from the valve tray assem-
bly.
8) Install a new gasket and reinstall the valve
tray assembly.
Note: Failure to install a new gasket may
severely affect the appliance perform-
ance.
Remove the 2 Long Base Brick Panels
9) Reinstall the 16 hold down screws.
9) Disconnect the inlet gas line.
10) Hook up the 2 TP and 2 TH wires to the
appropriate connections on the valve.
10) Disconnect the 2 TP wires and the 2 TH
wires from the valve.
11) Reinstall the Burner Assembly.
11) Remove the 16 Phillips head screws secur-
ing the valve tray.
13) Hookupthegaslineandcheckforgasleaks
with a soap and water solution or a gas leak
detector. (Do not use open flame for leak
testing.)
14) Fire up the unit temporarily
15) Check the manifold pressure.
16) Reinstallthelogs, grate andbrickpanelsas
needed.
17) Reinstall the glass doors.
18) Fire up the unit again and check for proper
flame appearance.
12) Lift the entire assembly out.
32
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
FAN REPLACEMENT
1) Shut off power.
6) Replace fan.
2) Remove top louvers.
7) Repeat for opposite side/corner.
3) Unplug power wires.
8) Reverse steps 1 - 5 for installation.
4) Remove 4 screws securing fan to mounting bracket.
9) To remove the thermodisc, located at the back center of the unit, slide
the thermodisc/cover assembly away from the bracket clip on the under
side of the firebox. Reverse for installation. Ensure that no wires will touch
hot surfaces.
5) Remove 2 connector wires.
Connector wires
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
33
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
P121-1 (SEE THRU) MAIN ASSEMBLY
Part #
Description
Part #
Description
Part #
Description
135) 360-069 Heat Shield - Side
360-926 LouverFront-Black/Brass(set)
1) 360-528 Door Assy Front - Tempered
360-538 Door Assy Front - Ceramic
(Optional)
181) *
Extension Trim - See Thru
146) 360-033 Left Side Door Trim
360-034 Right Side Door Trim
150) 360-123 Magnet Bracket - Front
151) 904-258 Magnet
204) 360-940 Dec. Grill Front - Black (set)
2) 360-529 Door Assy Side - Tempered
360-539 Door Assy Side - Ceramic
(Optional)
205) 948-216 Regency Logo Plate
206) 910-171 Fan Axial 115V
168) 360-068 Door Cover Assembly - Side
207) 910-142 Thermodisc
918-107a Manual
9) 360-046 Nailing Strip - Top - Front
10) 360-047 Nailing Strip - Top - Side
11) 430-001 Standoff - Top
171) 360-920 Louver Front - Black (set)
360-922 Louver Front - Black/Gold (set)
360-924 Louver Front - Black/Steel (set)
17) 360-086 Gasket - Relief Door
*Not available as a replacement part.
24) *
Relief Door Assembly
32) 902-296 Brick Panel - Base - Front
33) 902-297 Brick Panel - Base - Side
34) 902-298 Brick Panel - Side
98) 910-366 Switch Cover Plate
99) 910-363 Wall Switch
100) 910-367 Switch Receptacle Plastic Box
910-882 Wire - Valve to Burner Switch
34
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
P131-1 (PIER) MAIN ASSEMBLY
Part #
Description
Part #
Description
Part #
Description
141) 360-031 ColumnFinishingTrim
146) 360-035 FinishingTrim
1) 360-528 Door Assy Front - Tempered
360-946 Door Assy Front - Ceramic
(Optional)
181) *
Extension Trim - Pier
204) 360-940 Dec. Grill Front - Black (set)
206) 910-171 Fan Axial 115V
149) 360-122 Magnet Bracket - Corner
150) 360-123 Magnet Bracket - Front
151) 904-258 Magnet
2) 360-529 Door Assy Side - Tempered
360-948 Door Assy Side- Ceramic
(Optional)
224) 360-942 Dec. Grill Side - Black (set)
225) 948-216 Regency Logo Plate
226) 910-412 Thermodisc
171) 360-920 Louver Front - Black (set)
360-922 Louver Front - Black/Gold (set)
360-924 Louver Front - Black/Steel (set)
360-926 Louver Front - Black/Brass (set)
9) 360-046 Nailing Strip - Top - Front
10) 360-047 Nailing Strip - Top - Side
11) 430-001 Standoff - Top
918-107a Manual
*Not available as a replacement part.
17) 360-086 Gasket - Relief Door
173) 360-932 Louver Side - Black (set)
360-934 Louver Side - Black/Gold (set)
360-936 Louver Side - Black/Steel (set)
360-938 Louver Side - Black/Brass (set)
24) *
Relief Door Assembly
32) 902-296 Brick Panel - Base - Side
33) 902-297 Brick Panel - Base - Front
34) 902-298 Brick Panel - Side
98) 910-366 Switch Cover Plate
99) 910-363 Wall Switch
100) 910-367 Switch Receptacle Plastic Box
910-882 Wire - Valve to Burner Switch
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
35
PARTS LIST
P121RC-1 (RIGHT CORNER) MAIN ASSEMBLY
Part #
Description
Part #
Description
Part #
Description
173) 360-932 Louver Side - Black (set)
360-934 Louver Side - Black/Gold (set)
360-936 Louver Side - Black/Steel (set)
360-938 Louver Side - Black/Brass (set)
35) 902-300 Brick Panel - Front
1) 360-528 Door Assy Front - Tempered
360-538 Door Assy Front - Ceramic
(Optional)
98) 910-366 Switch Cover Plate
99) 910-363 Wall Switch
100) 910-367 Switch Receptacle Plastic Box
910-882 Wire - Valve to Burner Switch
2) 360-529 Door Assy Side - Tempered
360-539 Door Assy Side - Ceramic
(Optional)
181) *
Extension Trim
204) 360-940 Dec. Grill Front - Black (set)
206) 910-171 Fan Axial 115V
224) 360-942 Dec. Grill Side - Black (set)
138) 360-063 Heat Shield - Front
141) 360-031 ColumnFinishingTrim
9) 360-046 Nailing Strip - Top - Front
10) 360-047 Nailing Strip - Top - Side
11) 430-001 Standoff - Top
780-013 Standoff - Rear
17) 360-086 Gasket - Relief Door
146) 360-035 Finishing Trim - Left Side
225) 948-216 Regency Logo Plate
226) 910-142 Thermodisc
149) 360-122 Magnet Bracket - Corner
150) 360-123 Magnet Bracket - Front
151) 904-258 Magnet
24) *
Relief Door Assembly
918-107a Manual
158) 360-060 Door Cover Assembly-Front
32) 902-296 Brick Panel - Base - Side
33) 902-297 Brick Panel - Base - Front
34) 902-298 Brick Panel - Side
*Not available as a replacement part.
171) 360-920 Louver Front - Black (set)
360-922 Louver Front - Black/Gold (set)
360-924 Louver Front - Black/Steel (set)
360-926 Louver Front - Black/Brass (set)
36
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
P121LC-1 (LEFT CORNER) MAIN ASSEMBLY
Part #
Description
Part #
Description
Part #
Description
173) 360-932 Louver Side - Black (set)
360-934 Louver Side - Black/Gold (set)
360-936 Louver Side - Black/Steel (set)
360-938 Louver Side - Black/Brass (set)
98) 910-366 Switch Cover Plate
99) 910-363 Wall Switch
100) 910-367 Switch Receptacle Plastic Box
910-882 Wire - Valve to Burner Switch
1) 360-528 Door Assy Front - Tempered
360-538 Door Assy Front - Ceramic
(Optional)
2) 360-529 Door Assy Side - Tempered
360-539 Door Assy Side - Ceramic
(Optional)
204) 360-940 Dec. Grill Front - Black (set)
206) 910-171 Fan Axial 115V
224) 360-942 Dec. Grill Side - Black (set)
138) 360-069 Heat Shield - Front
141) 360-031 ColumnFinishingTrim
146) 360-035 FinishingTrim
9) 360-046 Nailing Strip - Top - Front
10) 360-047 Nailing Strip - Top - Side
11) 430-001 Standoff - Top
225) 948-216 Regency Logo Plate
226) 910-142 Thermodisc
149) 360-122 Magnet Bracket - Corner
150) 360-123 Magnet Bracket - Front
151) 904-258 Magnet
918-107a Manual
17) 360-086 Gasket - Relief Door
24) *
Relief Door Assembly
*Not available as a replacement part.
158) 360-062 Door Cover Assembly-Front
32) 902-296 Brick Panel - Base - Side
33) 902-297 Brick Panel - Base - Front
34) 902-298 Brick Panel - Side
171) 360-920 Louver Front - Black (set)
360-922 Louver Front - Black/Gold (set)
360-924 Louver Front - Black/Steel (set)
360-926 Louver Front - Black/Brass (set)
35) 902-300 Brick Panel - Front
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
37
PARTS LIST
P121/P121LC/P121RC/P131-1 BURNER ASSEMBLY & LOG SET
Part #
Description
360-930
41) 904-326
42) 904-327
43) 904-328
44) 904-329
Log Set
Front Right Log
Front Left Log
Middle Left Log
Middle Right Log
360-574/P
56) 360-378/P
Valve Assembly
Valve S.I.T. - NG
57) 360-090
58) *
Gasket - Valve Tray
Valve Tray
66) 910-038
Pilot Assembly - NG
67) *
PilotHolder
68) W840470
69) 910-190
Pilot Assembly Gasket
Piezo Ignitor and Nut
79) 360-525
82) 360-027
904-690
Burner Assembly
Grate Assembly
Orifice #31 - NG
Orifice Gasket
936-170
*Not available as a replacement part.
38
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY
Regency Fireplace Products, are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance
Teamcarefullyinspectseachunitthoroughlybeforeitleavesourdoor. RegencyIndustriesLtd.ispleasedtoextendthislimited
lifetime warranty to the original purchaser of a Regency Product.
The Warranty: Lifetime
Covered under the agreement are the following components: Combustion chamber, heat exchanger, burner tubes, logs, embers,
glass (thermal breakage) and all gold plating (against defective manufacture).
The above will be covered for parts and labour for the first five years and parts only thereafter. Electrical components such as blowers,
fan motor, switches, wiring, thermodiscs, remote control, thermopiles, thermocouples, pilot assemblies, and gas valves are
covered for one year from the date of purchase.
Conditions:
All installations must be performed by a qualified gas fitter and installed according to all applicable local and national codes. Also,
all service work must be carried out by a qualified gas service person who is recommended by the selling dealer. It is the
responsibility of the installer to ensure that the appliance is firing as per rating plate. Any part or parts of this unit which in our
judgement show evidence of such defect will be repaired or replaced at Regency's option, through an accredited distributor or agent
provided that the defective part be returned to the distributor or agent Transportation Prepaid, if requested.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim. It does not cover installation
and operational related problems such as over-firing, downdrafts or spillage caused by environmental conditions, nearby trees,
buildings, hilltops, mountains, inadequate venting or ventilation, excessive offsets, negative air pressures caused by insufficient
make up air, mechanical systems such as furnaces, fans, clothes dryers etc.
The warranty does not extend to any part or parts which show evidence of misuse or abuse, neglect, accident or lack of maintenance.
Products made by other manufacturers and used in conjunction with the operation of this appliance without authorization from
Regency, may nullify your warranty on this product.
Regency Industries Ltd., shall in no event be liable for any special, indirect consequential damages of any nature whatsoever which
are in excess of the original purchase price of the product. Any alteration to the unit which causes sooting or carboning that results
in damage to the exterior facia is not the responsibility of Regency Industries Ltd.
Note: Warranty is not transferable.
VentComponents:
The venting components are under warranty from Simpson Dura-Vent Inc.
General:
It is essential that all submitted claims provide all of the necessary information including purchase date, serial #, type of unit and
part or parts requested.
Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Regency fireplace products are designed
withreliabilityandsimplicityinmind. In
addition, our internal QualityAssurance
Team carefully inspects each unit
thoroughly before it leaves our
door.
Fireplace Products International
Ltd. is pleased to extend this Lim-
ited Lifetime Warranty to the original
purchaser of a Regency Product.
See the inside back cover for details.
Register your Regency online at
Installer:Pleasecompletethefollowinginformation
Dealer Name & Address:______________________________________________
__________________________________________________________________
Installer: ___________________________________________________________
Phone #: ___________________________________________________________
Date Installed: ______________________________________________________
Serial No.: _________________________________________________________
Regency and Panorama are trademarks of FPI Fireplace Products International Ltd.
© FPI Fireplace Products International Ltd. 2003
Printed in Canada