COLD WATER RUN  
For the same reason stated for Cold Water Starts, it is even more important to provide protection against condensation  
from cold inlet water on systems where the return water temperature to the boiler will always be below the acceptable  
minimum. Raypaks Cold Water Run system utilizes a variable-speed pump to inject just the right amount of water  
from the main system loop into the boiler to maintain the optimum inlet temperature. This approach allows the full  
capacity of the boiler to be utilized to meet the system load, while at the same time continuously maintaining the opti-  
mum inlet water temperature to prevent condensation.  
Boiler Start-Up Cycle  
BLENDED BOILER  
INLET TEMP  
MIN INLET  
TEMP SETTING  
SYSTEM RETURN  
START-UP  
TEMP  
TIME  
Raypaks Cold Water Run system:  
Continuously monitors and adjusts inlet water temperature to prevent condensation  
Regulates minimum inlet water temperature regardless of system temperature  
Shuts down boiler if the minimum inlet water temperature is not achieved  
Protects boiler from constant low return water temperatures with its proprietary self-tuning controller  
Utilizes variable-speed injector pump to control boiler loop temperature  
Activates alarm if shutdown occurs (option)  
A P P LICA TIO N S  
Pool Heating  
Low-temperature Industrial Process  
Very Low-temperature Return Water  
(e.g. convalescent hospital domestic  
hot water)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COLD WATER START  
BOILER  
BOILER  
PUMP  
3-WAY  
VALVE  
TO  
SYSTEM  
FROM  
SYSTEM  
SYSTEM  
PUMP  
Cold Water Start J-Box Assembly  
Typical Cold Start Plumbing  
Pictorial-Not to Scale  
COLD WATER RUN  
BOILER  
BOILER  
PUMP  
VARIABLE SPEED  
INJECTOR PUMP  
TO  
SYSTEM  
FROM  
SYSTEM  
SYSTEM  
PUMP  
Cold Water Run J-Box Assembly  
Typical Cold RunPlumbing  
Pictorial-Not to Scale  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TECHNICAL DATA  
COLD WATER START  
TYPICAL BOILER PIPING*  
* Items required for cold water operation are shown.  
Other standard system components have been omitted for clarity.  
COLD WATER RUN  
TYPICAL BOILER PIPING*  
* Items required for cold water operation are shown. Other standard system components have been omitted for clarity.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TECHNICAL DATA  
MULTIPLE UNIT COLD WATER START  
Three-Way Diverting Valve Specifications  
Total System Load  
(MBTUH)  
Valve Size  
2” NPT  
Cv  
57  
GPM  
70  
P  
3.5’  
4.2’  
5.2’  
4.8’  
3.9’  
4.2’  
500-900  
901-1,800  
2-1/2” NPT  
2-1/2” NPT  
4” Flange  
4” Flange  
4” Flange  
74  
100  
150  
220  
330  
440  
1,801-3,000  
3,001-4,000  
4,001-6,000  
6,001-8,000  
100  
152  
254  
327  
Notes:  
1. Maximum of 4 boilers per system.  
2. Many variables can impact the proper valve sizing for multiple boilers. This sizing is provided as a guide. When in doubt consult the factory.  
3. Multi-unit system ALWAYS shipped loose- Not available mounted.  
4. 4” flanges, bolts and gaskets supplied by others. Multi-units with 4” valves are to be used on hydronic heating only. The valve body is cast  
iron.  
Catalog No.: 1000.19C Effective: 06-15-08 Replaces: 01-01-07  
Raypak Inc., 2151 Eastman Ave., Oxnard, CA 93030  
(805) 278-5300 Fax (800) 872-9725  
Download from Www.Somanuals.com. All Manuals Search And Download.  

QSC Audio Speaker System SR 110B User Guide
Radica Games Games 73048 User Guide
RCA TV DVD Combo 15L500TD User Guide
Salton Blender BL22 User Guide
Samson Musical Instrument S zone User Guide
Samsung Air Conditioner UST12SBGB User Guide
Samsung Flat Panel Television LE26A457 User Guide
Sanus Systems TV Mount 6901 170053 User Guide
Sanyo Microcassette Recorder ICR B170NX User Guide
Seagate Marine Battery FR A7AY User Guide