Quantum Boiler GAS FIRED BOILERS User Guide

GAS-FIRED, DIRECT VENT, CONDENSING, HOT WATER  
BOILERS  
INSTALLATION INSTRUCTIONS  
These instructions must be affixed on or adjacent to the boiler  
WARNING  
Improper installation, adjustment, alteration, service, or maintenance can cause injury or  
property damageꢀ Refer to this manualꢀ For assistance or additional information consult a  
qualified installer, service agency, or gas supplierꢀ  
DUNKIRK BOILERS  
DUNKIRK, NEW YORK 14048 - 716 366-5500  
Member: The Hydronics Institute  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS INTRODUCTION ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 3  
BOILER RATINGS AND CAPACITIES ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 4  
RULES FOR SAFE INSTALLATION AND OPERATIONꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 7  
BEFORE INSTALLING THE BOILER ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 7  
Aꢀ codes ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 7  
Bꢀ boiler sizing ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 8  
Cꢀ considerations for boiler location ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 8  
Dꢀ locating the boiler ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 8  
Eꢀ combustion air and vent pipe requirements ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 9  
Fꢀ condensate drain requirementsꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 10  
Gꢀ foundation requirementsꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 11  
Hꢀ removing existing boiler from common venting system ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 11  
PLACING THE BOILER ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 11  
NEAR BOILER PIPING ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 12  
Aꢀ supply and return linesꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 12  
Bꢀ pressure relief valveꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 16  
Cꢀ expansion tank and make-up waterꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 16  
Dꢀ condensate drain piping ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 19  
Eꢀ filling condensate trap ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 19  
Fꢀ chilled water piping ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 20  
COMBUSTION AIR AND VENT PIPE ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 21  
Aꢀ connections and terminations ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 21  
Bꢀ installation ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 22  
GAS SUPPLY PIPING ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 25  
Aꢀ check gas supply ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 25  
Bꢀ connecting the gas piping ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 25  
Cꢀ checking the gas piping ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 26  
ELECTRICAL WIRING ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 27  
Aꢀ electric power supply ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 27  
Bꢀ install your thermostatꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 28  
Cꢀ field wiring connections ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 29  
Dꢀ schematic wiring diagram ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 30  
Eꢀ ladder wiring diagramꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 31  
CONTROLS AND ACCESSORIES ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 32  
Aꢀ UT 1013-10 integrated boiler control ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 32  
Bꢀ gas control valve ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 32  
Cꢀ hot surface igniter ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 32  
Dꢀ L4006A high limit aquastat control ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 32  
Eꢀ draft inducer temperature safety switch ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 32  
Fꢀ casting temperature safety switchꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 33  
Gꢀ differential pressure air proving switch ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 33  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hꢀ draft inducerꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 33  
Iꢀ circulator pumpꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ33  
Jꢀ drain valveꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 33  
Kꢀ relief valveꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 34  
Lꢀ flame rollout safety shutoffꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 34  
Mꢀ external condensate pumpꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 34  
START-UPꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 34  
Aꢀ water treatment and freeze protectionꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 34  
Bꢀ filling boiler with water and purging air with diaphragm type expansion tanksꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 35  
Cꢀ filling boiler with water and purging air with conventional closed type expansion tanksꢀꢀꢀꢀ 35  
Dꢀ boiler in placingꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ36  
Iꢀ for your safety read before operating  
IIꢀ operating instructions  
IIIꢀ to turn off gas to appliance  
CHECK-OUT PROCEDURES AND ADJUSTMENTSꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 37  
Aꢀ verify proper sequence of operationꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 37  
Bꢀ inspect venting and air intake systemꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 38  
Cꢀ inspect condensate drainꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ38  
Dꢀ inspect system pipingꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ38  
Eꢀ test ignition system safety shutoffꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 38  
Fꢀ test high limit control and adjustꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ38  
Gꢀ test other safety controlsꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ39  
Hꢀ set thermostat heatꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 39  
1ꢀ measure the gas input rateꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ39  
Jꢀ set thermostat to desired room temperatureꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ41  
Kꢀ review all instructionsꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 41  
Lꢀ installation and check-out certificateꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 41  
MAINTENANCE AND CLEANINGꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 43  
Aꢀ beginning of each seasonꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 43  
Bꢀ daily during heating seasonꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 43  
Cꢀ monthly during heatingꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 44  
Dꢀ periodically during heatingꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 44  
Eꢀ end of each heating season -annual shut down procedureꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 44  
Fꢀ annual examination and cleaning of boiler componentsꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 44  
SERVICE HINTSꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 47  
A flow chart/detailed sequence of operationꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 47  
Bꢀ trouble shootingꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 50  
Cꢀ differential air pressure switch checkꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 58  
REPAIR PARTSꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ59  
Aꢀ jacket and baseꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ59  
Bꢀ condensate drain trap assembly ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 61  
Cꢀ block and piping assemblyꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ62  
Dꢀ mixer and air pressure switch assemblyꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 64  
Eꢀ flue adapter and exhauster assemblyꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ 66  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION  
This appliance is a gas-fired direct vent hot water boiler with cast aluminum boiler sectionsꢀ A  
revolutionary cast aluminum heat exchanger means better heat transfer and thermal storage than  
similarly sized cast iron boilers, which results in higher efficiencyꢀ The heating system water absorbs large  
amounts of heat from the cast aluminum heat exchanger, cooling the flue gases and causing  
condensationꢀ Sealed combustion, premix gas burner, and low flame temperature means drastically  
reduced CO and NOx emissions, which contribute to a cleaner and healthier environmentꢀ  
This appliance, unlike normal residential atmospheric and induced draft units, takes its combustion air  
directly from the outdoors (sealed combustion) and does not compete with building occupants for fresh  
airꢀ Sealed combustion (also known as “direct vent”) is the safest and best way to obtain plenty of clean  
combustion airꢀ The induced draft fan draws in the outside combustion air, then takes the cooler flue  
gases from the boiler unit and provides a positive removal of the flue gases from the building through  
inexpensive and readily available PVC and CPVC pipesꢀ  
FIGURE 1  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
BOILER RATINGS AND CAPACITIES  
7$%/(ꢀꢁꢀꢀꢀ6($ꢀ/(9(/ꢀ5$7,1*6ꢀꢂꢀ1$785$/ꢀ$1'ꢀ3523$1(ꢀ*$6(6  
ꢄꢄꢀ+HDWLQJ  
&DSDFLW\  
ꢁꢂ0%+ꢃ  
ꢈꢆ  
1HWꢀ, % 5  
5DWLQJ  
ꢁꢂ0%+ꢃ  
ꢉꢊ  
6KLSSLQJꢀ  
:HLJKWꢀ  
ꢂOEVꢅꢃ  
)OXH  
'LDꢅ  
0RGHO  
,QSXWꢀꢁꢂ0%+ꢃ  
ꢆꢇ  
ꢌꢆ  
ꢏꢇꢇ  
ꢆꢇ  
ꢌꢆ  
ꢏꢇꢇ  
ꢋꢋꢇ  
ꢋꢋꢇ  
ꢋꢋꢇ  
ꢋ´ꢀ&39&ꢀ,ꢀ39&  
ꢋ´ꢀ&39&ꢀ,ꢀ39&  
ꢋ´ꢀ&39&ꢀ,ꢀ39&  
ꢍꢎ  
ꢊꢇ  
ꢆꢊ  
ꢌꢎ  
ꢁꢀꢏꢀ0%+ꢀ ꢀꢏꢐꢇꢇꢇꢀ%WXKꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ%WXKꢀ ꢀ%ULWLVKꢀ7KHUPDOꢀ8QLWVꢀ3HUꢀ+RXU  
These low pressure gas-fired hot water boilers are design certified by CSA International for use  
with natural and propane gasesꢀ The boilers are constructed and hydrostatically tested for a  
maximum working pressure of 50 psig (pounds per square inch gage) in accordance with  
AꢀSꢀMꢀEꢀ (American Society of Mechanical Engineers) Boiler and Pressure Vessel Code Section  
IV Standards for heating boilersꢀ  
++ AFUE (Annual Fuel Utilization Efficiency) and Heating Capacity is based on the DꢀOꢀEꢀ  
(Department of Energy) test procedureꢀ  
The Boilers are certified in accordance with ANSI (American National Standards Institute)  
Z21ꢀ13 standards as gas-fired, direct vent, condensing, hot water boilersꢀ  
The Heating Capacity indicates the amount of heat available after subtracting the losses up the  
stackꢀ Most of this heat is available to heat waterꢀ A small portion is heat from the jacket and  
surfaces of the boiler, and it is assumed that this heat stays in the structureꢀ The Net I=B=R  
Rating represents the portion of the remaining heat that can be applied to heat the radiation or  
terminal units (iꢀeꢀ finned tube baseboard, cast iron radiators, radiant floor, etcꢀ)ꢀ The difference  
between the Heating Capacity and the Net I=B=R Rating, called the piping and pickup  
allowance, establishes a reserve for heating the volume of water in the system and offsetting  
heat losses from the pipingꢀ The Net I=B R Ratings shown are based on a piping and pickup  
factor of 1ꢀ15 in accordance with the I=B=R Standard as published by the Hydronics Instituteꢀ  
The Net I=B=R Rating of the boiler selected should be greater than or equal to the calculated  
peak heating load (heat loss) for the building or area(s) served by the boiler and associated hot  
water heating systemsꢀ The manufacturer should be consulted before selecting a boiler for  
installations having unusual piping and pickup requirementsꢀ  
BOILERS FOR USE AT HIGH ALTITUDE  
The boilers are factory equipped for operation at altitudes ranging from 0-2,000 feet above sea  
levelꢀ For use of these boilers at altitudes above 2,000 feet above sea level, the gas input  
ratings (MBH) must be reducedꢀ  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
UꢀSꢀAꢀ ONLY: For altitudes above 2,000 feet above sea level, input ratings should be reduced  
as shown in tables IA, C, & E for natural gas boilers or in tables 1B, D & F for propane fired  
boilersꢀ Reduced input ratings are achieved by the natural deration of the gas at higher  
elevations and fine tuned by adjusting the manifold pressureꢀ  
CANADA ONLY: For altitudes in the range of 2,000-4,500 feet above sea level, boilers may be  
field equipped for use at high altitude by using a certified high altitude conversion kitꢀ The change  
in main burner orifice size results in a 10% reduction of the boiler gas input rating (MBH)ꢀ  
The conversion shall be carried out by a manufacturer’s authorized representative, in  
accordance with the requirements of the manufacturer, provincial or territorial authorities having  
jurisdiction, and in accordance with the requirements of the CSA-B 149ꢀ1 and CSA-B 149ꢀ2  
Installation Codesꢀ The certified field conversion kit includes a conversion data plate, indicating  
that the boiler has been converted for high altitude useꢀ The correct conversion information must  
be entered on the conversion data plateꢀ  
7$%/(ꢀꢁ$ꢀꢀ02'(/ꢂꢃꢄꢀ1$785$/ꢀ*$6ꢀ+,*+ꢀ$/7,78'(ꢀ5$7,1*6ꢀ  
(/(9$7,21 ꢀ)((7ꢁ  
ꢂꢃꢄꢅꢂꢂꢂ ꢆꢅꢂꢂꢂ ꢇꢅꢂꢂꢂ ꢈꢅꢂꢂꢂ ꢉꢅꢂꢂꢂ ꢊꢅꢂꢂꢂ ꢊꢅꢈꢂꢂ ꢋꢅꢈꢂꢂ  
120,1$/ ,1387 ꢀ0%+ꢁ  
+($7 &$3&,7< ꢀ0%+ꢁ  
1(7 , % 5 5$7,1* ꢀ0%+ꢁ  
*$6 25,),&( '5,// 6,=(  
ꢈꢂꢌꢂ  
ꢇꢈꢌꢂ  
ꢆꢎꢌꢂ  
ꢇꢋꢌꢂ  
ꢇꢆꢌꢄ  
ꢆꢊꢌꢇ  
ꢇꢊꢌꢋ  
ꢇꢆꢌꢂ  
ꢆꢊꢌꢆ  
ꢇꢊꢌꢈ  
ꢇꢄꢌꢋ  
ꢆꢊꢌꢍ  
ꢇꢉꢌꢂ  
ꢇꢍꢌꢇ  
ꢆꢈꢌꢎ  
ꢇꢇꢌꢂ  
ꢆꢎꢌꢉ  
ꢆꢇꢌꢆ  
ꢇꢆꢌꢈ  
ꢆꢎꢌꢄ  
ꢆꢇꢌꢂ  
ꢇꢄꢌꢂ  
ꢆꢊꢌꢋ  
ꢆꢄꢌꢋ  
ꢌꢂꢉꢍꢈ ꢌꢂꢉꢍꢈ ꢌꢂꢉꢍꢈ ꢌꢂꢉꢍꢈ ꢌꢂꢉꢍꢈ ꢌꢂꢉꢍꢈ ꢌꢂꢉꢍꢈ ꢌꢂꢉꢍꢈ  
0$1,)2/' 35(6685(  
ꢀ,1&+(6 :$7(5 &2/801ꢁ  
ꢄꢌꢈ  
ꢄꢌꢊ  
ꢆꢌꢂ  
ꢆꢌꢄ  
ꢆꢌꢍ  
ꢆꢌꢂ  
ꢄꢌꢋ  
ꢄꢌꢊ  
35(6685( 6:,7&+ 6(732,17  
ꢀ,1&+(6 :$7(5 &2/801ꢁ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
7$%/(ꢀꢁ%ꢀꢀ02'(/ꢂꢃꢄꢀ3523$1(ꢀ*$6ꢀ+,*+ꢀ$/7,78'(ꢀ5$7,1*6ꢀ  
(/(9$7,21 ꢀ)((7ꢁ  
ꢂꢃꢄꢅꢂꢂꢂ ꢆꢅꢂꢂꢂ ꢇꢅꢂꢂꢂ ꢈꢅꢂꢂꢂ ꢉꢅꢂꢂꢂ ꢊꢅꢂꢂꢂ ꢊꢅꢈꢂꢂ ꢋꢅꢈꢂꢂ  
120,1$/ ,1387 ꢀ0%+ꢁ  
+($7 &$3&,7< ꢀ0%+ꢁ  
1(7 , % 5 5$7,1* ꢀ0%+ꢁ  
*$6 25,),&( '5,// 6,=(  
ꢈꢂꢌꢂ  
ꢇꢈꢌꢂ  
ꢆꢎꢌꢂ  
ꢇꢎꢌꢂ  
ꢇꢇꢌꢍ  
ꢆꢋꢌꢄ  
ꢇꢎꢌꢂ  
ꢇꢇꢌꢍ  
ꢆꢋꢌꢄ  
ꢇꢎꢌꢂ  
ꢇꢇꢌꢍ  
ꢆꢋꢌꢄ  
ꢇꢋꢌꢂ  
ꢇꢆꢌꢄ  
ꢆꢊꢌꢇ  
ꢇꢉꢌꢈ  
ꢇꢍꢌꢎꢇꢍꢌꢇ ꢆꢎ  
ꢆꢉꢌꢆ ꢆꢈꢌꢎ  
ꢇꢉꢌꢂ  
ꢇꢇꢌꢂ  
ꢆꢇꢌꢆ  
ꢌꢂꢇꢎꢄ ꢌꢂꢇꢎꢄ ꢌꢂꢇꢎꢄ ꢌꢂꢇꢎꢄ ꢌꢂꢇꢎꢄ ꢌꢂꢇꢎꢄ ꢌꢂꢇꢎꢄ ꢌꢂꢇꢎꢄ  
0$1,)2/' 35(6685(  
ꢀ,1&+(6 :$7(5 &2/801ꢁ  
ꢄꢌꢈ  
ꢄꢌꢋ  
ꢆꢌꢍ  
ꢆꢌꢇ  
ꢆꢌꢇ  
ꢆꢌꢈ  
ꢆꢌꢈ  
ꢆꢌꢈ  
35(6685( 6:,7&+ 6(732,17  
ꢀ,1&+(6 :$7(5 &2/801ꢁ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
ꢍꢌꢈꢈ  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
7$%/(ꢀꢁ&ꢀꢀ02'(/ꢂꢅꢃꢀ1$785$/ꢀ*$6ꢀ+,*+ꢀ$/7,78'(ꢀ5$7,1*6ꢀ  
(/(9$7,21 ꢀ)((7ꢁ  
ꢂꢃꢄꢅꢂꢂꢂ ꢆꢅꢂꢂꢂ ꢇꢅꢂꢂꢂ ꢈꢅꢂꢂꢂ ꢉꢅꢂꢂꢂ ꢊꢅꢂꢂꢂ ꢊꢅꢈꢂꢂ ꢋꢅꢈꢂꢂ  
120,1$/ ,1387 ꢀ0%+ꢁ  
+($7 &$3&,7< ꢀ0%+ꢁ  
ꢊꢈꢌꢂ  
ꢊꢂꢌꢂ  
ꢉꢎꢌꢂ  
ꢉꢋꢌꢂ  
ꢉꢆꢌꢈ  
ꢈꢋꢌꢂ  
ꢈꢉꢌꢈ  
ꢈꢂꢌꢎꢇꢉꢌꢋ  
ꢇꢇꢌꢍ ꢇꢂꢌꢉ  
ꢌꢂꢊꢉꢂ ꢌꢂꢊꢉꢂ ꢌꢂꢊꢉꢂ ꢌꢂꢊꢉꢂ ꢌꢂꢊꢉꢂ ꢌꢂꢊꢉꢂ ꢌꢂꢊꢉꢂ ꢌꢂꢊꢉꢂ  
ꢈꢄꢌꢂ  
ꢉꢋꢌꢂ  
ꢉꢆꢌꢂ  
ꢉꢄꢌꢍ  
ꢉꢍꢌꢄ  
ꢈꢊꢌꢄ  
ꢈꢄꢌꢄ  
1(7 ,  
%  
5 5$7,1* ꢀ0%+ꢁ  
ꢈꢋꢌꢎꢈꢇꢌꢉ  
ꢈꢆꢌꢋ  
ꢈꢆꢌꢂ ꢌꢉꢇꢎ ꢇꢈꢌꢄ  
*$6 25,),&( '5,// 6,=(  
0$1,)2/' 35(6685(  
ꢀ,1&+(6 :$7(5 &2/801ꢁ  
ꢄꢌꢈ  
ꢄꢌꢊ  
ꢄꢌꢋ  
ꢆꢌꢂ  
ꢄꢌꢋ  
ꢄꢌꢉ  
ꢄꢌꢆ  
ꢄꢌꢍ  
35(6685( 6:,7&+ 6(732,17  
ꢀ,1&+(6 :$7(5 &2/801ꢁ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
7$%/(ꢀꢁ'ꢀꢀ02'(/ꢂꢅꢃꢀ3523$1(ꢀ*$6ꢀ+,*+ꢀ$/7,78'(ꢀ5$7,1*6ꢀ  
(/(9$7,21 ꢀ)((7ꢁ  
ꢂꢃꢄꢅꢂꢂꢂ ꢆꢅꢂꢂꢂ ꢇꢅꢂꢂꢂ ꢈꢅꢂꢂꢂ ꢉꢅꢂꢂꢂ ꢊꢅꢂꢂꢂ ꢊꢅꢈꢂꢂ ꢋꢅꢈꢂꢂ  
120,1$/ ,1387 ꢀ0%+ꢁ  
+($7 &$3&,7< ꢀ0%+ꢁ  
ꢊꢈꢌꢂ  
ꢉꢋꢌꢂ  
ꢊꢂꢌꢂ  
ꢉꢆꢌꢂ  
ꢉꢎꢌꢂ  
ꢉꢄꢌꢍ  
ꢉꢊꢌꢂ  
ꢉꢂꢌꢆ  
ꢉꢉꢌꢂ  
ꢈꢎꢌꢇ  
ꢉꢇꢌꢈ  
ꢈꢋꢌꢍ  
ꢉꢇꢌꢂ  
ꢈꢊꢌꢉ  
ꢉꢄꢌꢂ  
ꢈꢈꢌꢋ  
1(7 ,  
%  
5 5$7,1* ꢀ0%+ꢁ  
ꢈꢋꢌꢎꢈꢇꢌꢉ  
ꢈꢆꢌꢋ  
ꢈꢄꢌꢆ  
ꢈꢍꢌꢈ  
ꢈꢂꢌꢇ ꢇꢋꢎ  
*$6 25,),&( '5,// 6,=(  
ꢌꢂꢉꢂꢈ ꢌꢂꢉꢂꢈ ꢌꢂꢉꢂꢈ ꢌꢂꢉꢂꢈ ꢌꢂꢉꢂꢈ ꢌꢂꢉꢂꢈ ꢌꢂꢉꢂꢈ ꢌꢂꢉꢂꢈ  
0$1,)2/' 35(6685(  
ꢀ,1&+(6 :$7(5 &2/801ꢁ  
ꢄꢌꢈ  
ꢄꢌꢇ  
ꢄꢌꢆ  
ꢄꢌꢄ  
ꢄꢌꢄ  
ꢄꢌꢄ  
ꢄꢌꢆ  
ꢄꢌꢆ  
35(6685( 6:,7&+ 6(732,17  
ꢀ,1&+(6 :$7(5 &2/801ꢁ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
ꢍꢌꢆꢈ  
7$%/(ꢀꢁ(ꢀꢀ02'(/ꢂꢁꢄꢄꢀ1$785$/ꢀ*$6ꢀ+,*+ꢀ$/7,78'(ꢀ5$7,1*6ꢀ  
(/(9$7,21 ꢀ)((7ꢁ  
ꢂꢃꢄꢅꢂꢂꢂ ꢆꢅꢂꢂꢂ ꢇꢅꢂꢂꢂ ꢈꢅꢂꢂꢂ ꢉꢅꢂꢂꢂ ꢊꢅꢂꢂꢂ ꢊꢅꢈꢂꢂ ꢋꢅꢈꢂꢂ  
120,1$/ ,1387 ꢀ0%+ꢁ  
+($7 &$3&,7< ꢀ0%+ꢁ  
ꢍꢂꢂꢌꢂ  
ꢎꢂꢌꢂ  
ꢎꢊꢌꢂ  
ꢋꢊꢌꢆ  
ꢎꢉꢌꢂ  
ꢋꢉꢌꢇ  
ꢊꢈꢌꢊ  
ꢎꢈꢌꢂ  
ꢎꢂꢌꢂ  
ꢋꢍꢌꢂ  
ꢋꢇꢌꢂ  
ꢊꢈꢌꢉ  
ꢋꢄꢌꢂ  
ꢊꢆꢌꢋ  
ꢊꢉꢌꢂ  
ꢉꢋꢌꢇ  
ꢋꢈꢌꢈ  
1(7 ,  
%  
5 5$7,1* ꢀ0%+ꢁ  
ꢊꢋꢌꢂ  
ꢊꢇꢌꢎꢊꢇꢌꢍ  
ꢊꢂꢌꢄ  
ꢉꢈꢌꢈ  
ꢉꢇꢌꢂ ꢈꢎ  
*$6 25,),&( '5,// 6,=(  
ꢌꢂꢋꢉꢂ ꢌꢂꢋꢉꢂ ꢌꢂꢋꢉꢂ ꢌꢂꢋꢉꢂ ꢌꢂꢋꢉꢂ ꢌꢂꢋꢉꢂ ꢌꢂꢋꢉꢂ ꢌꢂꢋꢉꢂ  
0$1,)2/' 35(6685(  
ꢀ,1&+(6 :$7(5 &2/801ꢁ  
ꢄꢌꢈ  
ꢄꢌꢎꢆꢌꢆ  
ꢍꢌꢍꢊ  
ꢆꢌꢊ  
ꢍꢌꢍꢊ  
ꢆꢌꢇ  
ꢍꢌꢍꢊ  
ꢆꢌꢄ  
ꢍꢌꢍꢊ  
ꢄꢌꢎꢄꢌꢉ  
ꢍꢌꢍꢊ ꢍꢌꢍꢊ  
35(6685( 6:,7&+ 6(732,17  
ꢀ,1&+(6 :$7(5 &2/801ꢁ  
ꢍꢌꢍꢊ  
ꢍꢌꢍꢊ  
7$%/(ꢀꢁ)ꢀꢀ02'(/ꢂꢁꢄꢄꢀ3523$1(ꢀ*$6ꢀ+,*+ꢀ$/7,78'(ꢀ5$7,1*6ꢀ  
(/(9$7,21 ꢀ)((7ꢁ  
ꢂꢃꢄꢅꢂꢂꢂ ꢆꢅꢂꢂꢂ ꢇꢅꢂꢂꢂ ꢈꢅꢂꢂꢂ ꢉꢅꢂꢂꢂ ꢊꢅꢂꢂꢂ ꢊꢅꢈꢂꢂ ꢋꢅꢈꢂꢂ  
120,1$/ ,1387 ꢀ0%+ꢁ  
+($7 &$3&,7< ꢀ0%+ꢁ  
1(7 , % 5 5$7,1* ꢀ0%+ꢁ  
*$6 25,),&( '5,// 6,=(  
ꢍꢂꢂꢌꢂ  
ꢎꢂꢌꢂ  
ꢊꢋꢌꢂ  
ꢎꢈꢌꢂ  
ꢋꢈꢌꢈ  
ꢊꢇꢌꢍ  
ꢎꢇꢌꢂ  
ꢋꢇꢌꢉ  
ꢊꢆꢌꢆ  
ꢎꢄꢌꢂ  
ꢋꢄꢌꢋ  
ꢊꢍꢌꢋ  
ꢎꢄꢌꢂ  
ꢋꢄꢌꢋ  
ꢊꢍꢌꢋ  
ꢎꢍꢌꢈ  
ꢋꢄꢌꢇ  
ꢊꢍꢌꢇ  
ꢎꢍꢌꢈ  
ꢋꢄꢌꢇ  
ꢊꢍꢌꢇ  
ꢎꢍꢌꢂ  
ꢋꢍꢌꢎ  
ꢊꢍꢌꢂ  
ꢌꢂꢉꢊꢂ ꢌꢂꢉꢊꢂ ꢌꢂꢉꢊꢂ ꢌꢂꢉꢊꢂ ꢌꢂꢉꢊꢂ ꢌꢂꢉꢊꢂ ꢌꢂꢉꢊꢂ ꢌꢂꢉꢊꢂ  
0$1,)2/' 35(6685(  
ꢀ,1&+(6 :$7(5 &2/801ꢁ  
ꢄꢌꢈ  
ꢄꢌꢊ  
ꢄꢌꢎꢆꢌꢍ  
ꢍꢌꢍꢊ  
ꢆꢌꢄ  
ꢍꢌꢍꢊ  
ꢆꢌꢆ  
ꢍꢌꢍꢊ  
ꢆꢌꢇ  
ꢍꢌꢍꢊ  
ꢆꢌꢈ  
ꢍꢌꢍꢊ  
35(6685( 6:,7&+ 6(732,17  
ꢀ,1&+(6 :$7(5 &2/801ꢁ  
ꢍꢌꢍꢊ  
ꢍꢌꢍꢊ  
ꢍꢌꢍꢊ  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
RULES FOR SAFE INSTALLATION AND OPERATION  
lꢀ Read the entire installation manual before beginning the installationꢀ Failure to follow these  
rules for safe installation and operation and these instructions could cause a malfunction of  
the boiler and result in death, serious bodily injury, and/or property damageꢀ  
2ꢀ Check all applicable state and local building codes and utility company requirements  
before installationꢀ The installation must conform with these requirements in their  
entiretyꢀ In the absence of these codes, use NFPA Installation Codes and good  
industry practiceꢀ  
3ꢀ Before servicing the boiler - allow the boiler to coolꢀ Always shut off any electricity and  
gas supply connected to the boiler prior to servicingꢀ  
4ꢀ Inspect gas line for leaksꢀ  
5ꢀ Be certain gas input rate is correctꢀ Over firing may result in early failure of the boiler  
sectionsꢀ This may cause dangerous operationꢀ Under firing may result in too much air  
for the pre-mix burner causing poor or loss of combustionꢀ  
6ꢀ Never vent the products of combustion from this boiler to an enclosed spaceꢀ Always  
vent to the outdoorsꢀ Never vent to another room or to inside a buildingꢀ  
7ꢀ Be sure there is adequate outdoor air supply to boilerꢀfor complete combustionꢀ  
8ꢀ Follow a regular service and maintenance schedule for efficient and safe operationꢀ 9ꢀ  
Keep boiler area clean of debris and free of combustible and flammable materialsꢀ  
10ꢀ Proper through the wall or through the roof combustion venting shall be in accordance with the  
materials and methods described in this manualꢀ Installation must comply with local codesꢀ  
11ꢀ This boiler and related hot water heating systems are not do it yourself itemsꢀ They  
must be installed and serviced by qualified professionalsꢀ  
WARNING  
This boiler has been equipped for residential installationsꢀ If used for commercial applications, any  
additional code requirements must be adhered to for installationꢀ This may require additional  
controls including but not limited to a low water cut off, a manual reset high temperature limit, and  
wiring and/or piping modificationsꢀ The manufacturer is not responsible for any field installation  
changes made to a boiler installation which are not described or acknowledged in this manualꢀ  
BEFORE INSTALLING THE BOILER  
Complete all of the following prior to installing the boilerꢀ  
Aꢀ CODES  
This boiler product is a gas-fired, direct vent, condensing boiler and must be installed in  
accordance with all applicable federal, state and local building codes including, but not  
limited to the following:  
United States -Installation shall conform with National Fuel Gas Code (NFPA-54/ANSI  
Z223ꢀ1-latest edition)  
Canada -  
Installation shall be in accordance with CSA B 149ꢀ1 and ꢀ2ꢀ installation  
codesꢀ  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Where required by the authority having jurisdiction, the installation must conform to the  
American Society of Mechanical Engineers Safety Code for Controls and Safety Devices  
for Automatically Fired Boilers, NoꢀCSD-1ꢀ  
The installation must conform to the requirements of the authority having jurisdiction or, in the  
absence of such requirements, to the National Fuel Gas Code, ANSI Z223ꢀ1 - latest revisionꢀ  
Installers - Follow local regulations with respect to installation of CO (Carbon  
Monoxide) Detectorsꢀ Follow maintenance recommendations in this manualꢀ  
Techniciens -Veuillez vous conformer à la réglementation en vigueur concernant 1'  
installations des détecteurs d'oxyde de carboneꢀ Suivre les consignes  
d'entretien figurant dans le manuel d'instruction ci-jointꢀ  
Bꢀ BOILER SIZING  
Check to be sure you have selected the boiler with the proper capacity before starting  
the installationꢀ The I=B R Rating of the boiler selected should be greater than or equal  
to the calculated peak heating load (heat loss) for the building or area(s) served by the  
boiler and associated hot water heating systemsꢀ See the table "BOILER RATINGS  
AND CAPACITIES"ꢀ  
Heat loss calculations should be based on approved industry methodsꢀ  
Cꢀ CONSIDERATIONS FOR BOILER LOCATION  
Before selecting a location for the boiler, the following should be consideredꢀ Each boiler  
consideredꢀ  
Supplied with the correct type of gas (natural gas or propane)ꢀ  
Connected to a suitable combustion air intake piping system to supply the correct  
amounts of fresh (outdoor) air for combustionꢀ (maximum length 80' for the Model-100  
boiler, and maximum length 100' for the Model-75 and Model-50 boilers)ꢀ  
Connected to a suitable venting system to remove the hazardous products of gas  
combustion (maximum length 80' for the Model-100 boiler, and maximum length 100' for  
the Model-75 and Model-50 boilers)ꢀ  
Connected to a suitable hot water heating system  
Supplied with a suitable electrical supply for all boiler motors and controlsꢀ  
Connected to a properly located thermostat or operating controlꢀ (not included with  
boiler)  
Placed on level surface (must NOT be installed on carpeting)  
Condensate drain line must be pitched down to floor drain or external condensate  
pump with reservoir at ¼" per foot (wood frame or blocks may be used to raise boiler)ꢀ  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dꢀ LOCATING THE BOILER  
7$%/(ꢁꢂ  
81,7  
%2,/(5ꢁ&/($5$1&(6  
&20%867,%/(  
$&&(66,%,/,7<ꢀ  
6(59,&,1*  
&216758&7,21  
&/($1,1*  
723  
/()7ꢃ6,'(  
5,*+7ꢃ6,'(  
ꢀꢁ  
ꢀꢁ  
ꢂꢁ  
ꢀꢁ  
ꢅꢁ  
ꢀꢁ  
ꢅꢁ  
ꢂꢁ  
ꢀꢁ  
ꢂꢁ  
ꢀꢁ  
%$6(  
)5217  
%$&ꢈ  
ꢆꢇꢁ  
ꢆꢇꢁ  
,17$ꢈ(ꢉ9(17ꢃ3,3,1*  
1($5ꢃ%2,/(5ꢃ+27ꢃ:$7(5  
:$7(5ꢃ3,3,1*  
ꢀꢁ  
1ꢀ Select a location which is level, central to the piping systems served and as close to the  
vent and air intake terminals as possibleꢀ  
2ꢀ Accessibility clearances, if more stringent (iꢀeꢀ larger clearances) than required fire protection  
clearances, must be used for the boiler installationꢀ Accessibility clearances may be achieved  
with the use of removable walls or partitionsꢀ  
3ꢀ The boiler is approved for installation in closets and on combustible floorsꢀ This boiler  
shall NOT be installed on carpetingꢀ  
4ꢀ The clearances shown in Table 2 indicate required clearances per IAS listingꢀ A minimum  
1" clearance must be maintained between combustible construction and each of the left,  
top and back surfaces of the boilerꢀ A minimum 8" clearance is required on the right side,  
to allow room for the inlet air pipeꢀ An 18" clearance must be maintained at a side where  
passage is required to access another side for cleaning or servicing, inspection or  
replacement of any parts that normally may require such attentionꢀ Allow at least 24" at  
the front and left side and 8" at the top for servicingꢀ No clearances are required to  
venting or combustion air intake pipingꢀ  
5ꢀ Equipment shall be installed in a location which facilitates the operation of venting and  
combustion air intake piping systems as described in this manualꢀ  
6ꢀ Advise owner of boiler to keep venting and combustion air intake passages free of obstructionsꢀ  
both the venting and combustion air intake piping systems connected to the outdoors must  
permit flow through the piping systems without restrictions for the boiler to operateꢀ  
7ꢀ The boiler shall be installed such that the automatic gas ignition system components are  
protected from water (dripping, spraying, rain, etcꢀ) during operation and service  
(circulator replacement, control replacement, etcꢀ)ꢀ  
Eꢀ COMBUSTION AIR AND VENT PIPE REQUIREMENTS  
This boiler requires a dedicated direct vent systemꢀ In a direct vent system, all air for  
combustionis taken directly from outside atmosphere, and all flue products are discharged to  
outside atmosphereꢀ  
Combustion air and vent pipe connections must terminate together in the same atmospheric  
pressure zone, either through the roof or sidewall (roof termination preferred)ꢀ See Figꢀ9 & 10  
for required clearancesꢀ  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
KEEP BOILER AREA CLEAN OF DEBRIS AND FREE OF FLAMABLE AND COMBUSTIBLE  
MATERIALS, VAPORS AND LIQUIDS  
WARNING  
When vent pipe is exposed to temperatures below freezing, such as when it passes through an  
unheated space or when a chimney is used as a raceway, vent pipe must be insulated with 1/2”  
Armaflex or equivalentꢀ In extreme cold climate areas, use 3/4" Armaflex or equivalentꢀ  
Combustion air must be clean outdoor airꢀ Combustion air must not be taken from inside struc-  
ture because that air frequently is contaminated by halogens, which include fluorides, chlorides,  
phosphates, bromides and iodidesꢀ These elements are found in aerosols, detergents, bleaches,  
cleaning solvents, salts, air fresheners, paints, adhesives and other household productsꢀ  
Locate combustion air inlet as far away as possible from swimming pool and swimming pool  
pump houseꢀ  
All combustion air and vent pipes must be airtight and watertightꢀ Combustion air and vent  
piping must also terminate exactly as shown in Figꢀ9 or 10ꢀ  
Vent connections serving appliances vented by natural draft shall not be connected into any  
portion of mechanical draft systems operating under positive pressureꢀ  
Solvent cements are combustibleꢀ Keep away from heat, sparks, and open flameꢀ Use only in  
well ventilated areasꢀ Avoid breathing in vapor or allowing contact with skin or eyesꢀ  
FAILURE TO FOLLOW THE AFOREMENTIONED WARNINGS COULD RESULT IN FIRE,  
PROPERTY DAMAGE, PERSONAL INJURY, OR DEATHꢀ  
Fꢀ CONDENSATE DRAIN REQUIREMENTS  
Condensate drain line to be pitched down to floor drain at a minimum of 1/4" per footꢀ An external  
condensate pump (not furnished) may be used if floor drain is not availableꢀ The condensate  
pump must be designed for flue gas condensate application  
NOTE:1ꢀ Condensate trap is built into the boiler, an external trap is not required and should not  
be usedꢀ  
2ꢀ Wood frame or blocks may be used to raise the boiler to maintain drain pitch or to be  
above external condensate pump reservoirꢀ  
3ꢀ There is a 115 volt AC receptacle provided on the service switch junction box which  
is located at the boiler right side, to provide power for an external condensate  
pump (if needed)ꢀ  
Gꢀ FOUNDATION REQUIREMENTS  
Boiler must be placed on level surfaceꢀ Boiler is NOT to be installed on carpetingꢀ  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE:  
1ꢀ If boiler is not level condensate drain lines will not function properlyꢀ Adjustable  
feet are located on the boiler to make up for minor surface irregularities or tiltꢀ  
2ꢀ Wood frame or blocks may be used to raise boiler to maintain drain pitch or to be  
above external condensate pump reservoirꢀ  
Hꢀ REMOVAL OF EXISTING BOILER FROM COMMON VENT SYSTEM  
When an existing boiler is removed from a common venting system, the common venting  
system is likely to be too large for proper venting of the appliances remaining connected to itꢀ  
At the time of removal of an existing boiler, the following steps shall be followed with each  
appliance remaining connected to the common venting system placed in operation, while the  
other appliances remaining connected to the common venting system are not in operationꢀ  
1ꢀ Seal any unused openings in the common venting systemꢀ  
2ꢀ Visually inspect the venting system for proper size and horizontal pitch and determine  
there is no blockageꢀ or restrictions, leakage, corrosion and other deficiencies which could  
cause an unsafe conditionꢀ  
3ꢀ Insofar as is practical, close allꢀ building doors and windows and all doors between the  
space in which the appliances remaining connected to the common venting system are  
located and other spaces of the buildingꢀ Turn on clothes dryer and any appliance not  
connected to the common venting systemꢀ Turn on any exhaust fans, such as range  
hoods and bathroom exhaust, so they will operate at maximum speedꢀ Do not operate a  
summer exhaust fanꢀ Close fire dampersꢀ  
4ꢀ Place in operation the appliance being inspectedꢀ Follow the lighting instructionsꢀ Adjust  
thermostat so appliances will operate continuouslyꢀ  
5ꢀ Test for spillage at the draft hood relief opening after 5 minutes of main burner operationꢀ  
Use the flame of a match or candle, or the smoke from a cigarette, cigar or pipeꢀ  
6ꢀ After it has been determined that each appliance remaining connected to the common venting  
system properly vents when tested as outlined above, return doors, windows, exhaust fans  
and any other gas-burning appliance to their previous condition of useꢀ  
7ꢀ Any improper operation of the common venting system should be corrected so the  
installation conforms with the National Fuel Code, NFPA-54/ANSI -Z223ꢀ1-latest revision,  
or section 5 of CSA-B 149 for Canadian standardsꢀ When resizing any portion of the  
common venting system, the common venting system should be resized to approach the  
minimum size as determined using the appropriate tables in part 11 in the National Fuel  
Gas Code, NFPA-54/ANSI- Z223ꢀ1-latest revision, or section 5 of CSA-B 149 for  
Canadian standardsꢀ  
PLACING THE BOILER  
The boiler should be placed to provide the most direct connections to the combustion air, vent  
and system piping as possibleꢀ  
Place crated boiler as close to selected location as possible and uncrate boilerꢀ The uncrated  
boiler may be moved into position with an appliance dolly or 2-wheel hand truckꢀ The dolly or hand  
truck should be inserted under the left hand side of the boilerꢀ It is possible to slide the boiler for a  
short distance on a smooth floor or surfaceꢀ  
NOTE: Refer to manual section “LOCATING THE BOILER” for required clearances for servic  
ing and maintenanceꢀ  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEAR BOILER PIPING  
CAUTION  
Copper supply and return pipingꢀ must NOT be installed directly into aluminum boiler section  
casings due to galvanic corrosion between dissimilar metalsꢀ Iron or steel bushings or pipe  
nipples should be used between copper system piping and boiler to make final connection to  
boilerꢀ Also, the use of dielectric unions is acceptableꢀ The packaged boiler is furnished with iron  
piping in the front boiler section for the supply and return connectionsꢀ  
When the installation of the boiler is for a new heating system, first install all of the radiation  
units (panels, radiators, baseboard, or tubing) and the supply and return mainsꢀ After all heating  
system piping and components have been installed, make final connection of the system piping  
to the boilerꢀ A hot water boiler installed above radiation level must be equipped with a low water  
cut off deviceꢀ A periodic inspection is necessary us is flushing of float type devices, per low  
water cut off manufacturers specific instructionsꢀ  
A$ SUPPLY AND RETURN LINES  
The packaged boiler unit is set up to receive 1 1/4" NPT supply and return piping from top  
accessꢀ The boiler unit can also be piped from the left side by turning the supply elbow, and  
from the rear of the unit by removing plugs in the rear boiler sectionꢀ  
NOTE: The circulator pump and isolation valves are furnished within a carton inside the boiler  
cabinet and can be installed at the installer preferred locationꢀ  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 2 SINGLE ZONE BOILER PIPING  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 3 MULTI ZONE BOILER PIPING WITH ZONE VALVES  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: When zoning with circulators, the furnished circulator pump should be used as one of the  
zone pumpsꢀ Each stripped end of the electrical wires for the circulator pump inside the junction  
box should be taped or wire nutted to prevent short circuitsꢀ Unplug the circulator pump wiring at  
the integrated boiler controlꢀ  
FIGURE 4 MULTI ZONE BOILER PIPING WITH CIRCULATORS  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 5 SINGLE ZONE BOILER PIPING  
Bꢀ PRESSURE RELIEF VALVE  
The boiler is furnished with a factory installed relief valve in the top of the boilerꢀ Provide ¾”  
piping from the supplied relief valve to a local floor drain, but leave an air gap between piping  
and drainꢀ No shutoff of any description shall be placed between safety relief valve and the  
boiler, or on the discharge pipes between such safety valve and the atmosphereꢀ Installation  
of the safety relief valve shall conform to ANSI/ASME Boiler and Pressure Vessel Code,  
Section IVꢀ The manufacturer is not responsible for any water damageꢀ  
Cꢀ EXPANSION TANK AND MAKE-UP WATER  
Determine required system fill pressure, system design temperature, and system water  
contentꢀ Boiler contains 2ꢀ6 gallons (UꢀSꢀ)ꢀ Size expansion tank accordinglyꢀ Consult  
expansion tank manufacturer for proper sizing informationꢀ Connect properly sized  
expansion tank (not furnished) as shown in Figꢀ 6 for diaphragm type expansion tank and  
Figꢀ 7 for conventional closed type expansion tanksꢀ For diaphragm type expansion tanks,  
adjust the tank air pressure to match the system fill pressureꢀ Install air vent (furnished) as  
shown for diaphragm type expansion tank system onlyꢀ Install make-up water connections  
as shown per local codesꢀ If a pressure reducing valve is used, adjust to match the system  
fill pressureꢀ In connecting the cold make-up water supply to the boiler, make sure that clean  
water supply is availableꢀ When the water supply is from a well or pump, sand strainer  
should be installed at the pumpꢀ  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 6 DIAPHRAGM TYPE EXPANSION TANK PIPING  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 7 CONVENTIONAL (closed type) EXPANSION TANK PIPING  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 8 CONDENSATE - DRAIN PIPING  
Dꢀ CONDENSATE DRAIN PIPING  
The condensate trap is built into the boiler, an external trap is not required and should NOT be usedꢀ  
Provide ½” PVC condensate drain and fittingsꢀ Condensate drain to be pitched down to floor drain at  
a minimum of ¼” per footꢀ  
Install furnished ½” PVC tee to overflow fitting as shown in Figꢀ 8ꢀ  
The ½” diameter schedule 40 PVC or CPVC condensate drain and pipe fittings must conform to ANSI  
standards and ASTM D 1785 or D2846ꢀ Schedule 40 PVC or CPVC cement and primer must conform  
to ASTM D2564 or F493ꢀ In Canada, use CSA or ULC certified schedule 40 PVC or CPVC drain pipe  
cementꢀ  
A condensate pump with a reservoir (not furnished) may be used to remove condensate to a drain line  
(sanitary line) above boiler if a floor drain is not available or its in accessibleꢀ  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Eꢀ FILLING CONDENSATE TRAP WITH WATER ON THE INITIAL START UP THE CONDEN  
SATE TRAP MUST BE MANUALLY FILLED WITH WATER  
The following are the steps required to initially fill the condensate trap for start up, these steps  
are only required at the initial start up or if maintenance requires draining of the condensate trap:  
1ꢀ Disconnect the vent condensate drain line from the bottom of the vent tee on the boilerꢀ  
2ꢀ Pour about 1 cup of cold tap water into the vent drain line with a proper funnelꢀ  
3ꢀ Excess water should go through the overflow and out through the condensate drain lineꢀ  
Verify proper operation of the drain line (or external condensate pump if used)ꢀ  
4ꢀ Reinstall the vent drain lineꢀ  
Fꢀ CHILLED WATER PIPING  
The boiler, when used in connection with a refrigeration system, must be installed so the  
chiller medium is piped in parallel with the boiler with appropriate valves to prevent the chilled  
medium from entering the boilerꢀ  
The boiler piping system of a hot water boiler connected to heating coils is located in air  
handling units where they may be exposed to refrigerated air circulation must be equipped  
with flow control valves or other automatic means to prevent gravity circulation of the boiler  
water during cooling cycleꢀ  
COMBUSTION AIR AND VENT PIPE  
Aꢀ CONNECTIONS AND TERMINATION  
For boilers connected to gas vents or chimneys, vent installations shall be in accordance with  
part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI 2223ꢀ1-latest revision,  
CAN/CGA-B 149ꢀ1 and B 149ꢀ2, and applicable provisions of the local building codesꢀ  
Provisions for combustion and ventilation air must be in accordance with section 5ꢀ3, Air For  
Combustion and Ventilation, of the National Fuel Gas Code,ANSI 2223ꢀ1-latest revision,  
CAN/CGA-B 149ꢀ1 and B 149ꢀ2, or applicable provisions of the local building codeꢀ  
These boilers require a dedicated direct vent systemꢀ All air for combustion is taken directly  
from outdoors through the combustion air intake pipeꢀ All flue products are discharged to the  
outdoors through the vent pipeꢀ  
1ꢀ See Figꢀ9 & 10 for combustion air and vent pipe roof and sidewall terminationꢀ (Roof termi  
nation is preferred) Combustion air and vent pipes must terminate together in same atmo  
spheric pressure zone as shownꢀ Construction through which vent and air intake pipes  
may be installed is a maximum 24 inches, minimum 1/4" thicknessꢀ  
2ꢀ Combustion air and vent pipe fittings must conform to American National Standards Insti  
tute (ANSI) standards and American Society for Testing and Materials (ASTM) standards  
D1784 (schedule-40 CPVC), D1785 (schedule-40 PVC), D2665 (PVC-DWV), D2241  
(SDR-21 and SDR-26 PVC), D2661 (ABS-DWV), or F628 (schedule-40 ABS)ꢀ Pipe cement  
and primer must conform to ASTM standards D2564 (PVC) or D2235 (ABS)ꢀ  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
In Canada construct all combustion air and vent pipes for this unit of CSA or ULC certified  
schedule-40 CPVC, schedule-40 PVC, PVC-DWV or ABS-DWV pipe and pipe cementꢀ  
SDR pipe is NOT approved in Canadaꢀ  
3ꢀ Combustion air and vent piping connections on boiler are sized for 2" pipeꢀ Any pipe size  
change (to 3") must be made outside of the boiler casing in a vertical run of pipe to allow  
for proper drainage of vent condensateꢀ Due to potential for flue gas temperatures over  
155°F, the first five (5) feet of vent pipe must be CPVC, the remaining vent pipe can be  
PVCꢀ If any elbows are employed within the first 5 feet of vent, they must be CPVC tooꢀ  
Two (2) - 30" pieces of 2" CPVC pipe are furnished with the boilerꢀ  
NOTE: The transition from 2" pipe to 3" pipe must be made in a vertical runꢀ  
4ꢀ Combustion air and vent piping lengths,  
%2,/(5ꢀꢀꢀꢀꢀ  
6,=(  
ꢁꢂꢀ3,3(  
0,1,080  
9(17,1*  
ꢁꢂꢀ3,3(  
0$;,080  
9(17,1*  
ꢃꢂꢀ3,3(  
0,1,080  
9(17,1*  
ꢃꢂꢀ3,3(  
0$;,080  
9(17,1*  
ꢁꢀ)((7ꢀ,1  
/(1*7+  
ꢄꢊꢀ)((7ꢀ,1  
/(1*7+  
$1'ꢀ83ꢀ72  
ꢇꢈꢉꢅž  
ꢄꢊꢀ)((7ꢀ,1  
/(1*7+  
ꢋꢅꢀ)((7ꢀ,1  
/(1*7+  
$1'ꢀ83ꢀ72  
ꢇꢈꢉꢅž  
ꢄꢅꢅ  
ꢇꢈꢉꢅž  
ꢇꢈꢉꢅž  
(/%2:6  
(/%2:6  
(/%2:6  
(/%2:6  
ꢁꢀ)((7ꢀ,1  
/(1*7+  
ꢁꢅꢀ)((7ꢀ,1  
/(1*7+  
$1'ꢀ83ꢀ72  
ꢇꢈꢉꢅž  
ꢁꢅꢀ)((7ꢀ,1  
/(1*7+  
ꢄꢅꢅꢀ)((7ꢀ,1  
/(1*7+  
$1'ꢀ83ꢀ72  
ꢇꢈꢉꢅž  
ꢌꢊ  
$
ꢊꢅ  
ꢇꢈꢉꢅž  
ꢇꢈꢉꢅž  
(/%2:6  
(/%2:6  
(/%2:6  
(/%2:6  
The first 5 feet of “TOTAL EQUIVALENT LENGTH” of vent piping run must be CPVC:  
The length of pipe is counted from the boiler jacket (air intake pipe) or from vent tee (vent  
pipe)ꢀFor additional elbows, reduce the maximum vent length as shown:  
2" 90 degree elbow -1 ½ feet per additional elbowꢀ  
3" 90 degree elbow - 3 feet per additional elbowꢀ  
Example: To add 2 additional 90 degree elbows to a 3" pipe for a 75 boilerꢀ  
Each elbow is 3 additional feet per 90 degree elbow for a total of 6 feetꢀ (1 elbow @ 3  
feet + 1 elbow @ 3 feet = 6 additional feet of pipe) The total additional pipe is then  
subtracted from the maximum allowable pipe length to give the new maximum length  
of 94 feet with 6, 90 degree elbowsꢀ (“TOTAL EQUIVALENT LENGTH”: Original 100  
feet maxꢀ - 6 feet for 2 additional elbows = new 94 feet maximum length)ꢀ  
5ꢀ Combustion air and vent piping to be pitched back to boiler at minimum ¼” per foot from  
intake and vent terminals so that all moisture in combustion air and vent piping drains to  
boilerꢀ Pipes must be pitched continuously with no sags or low spots where moisture can  
accumulate and block the flow of air or flue gasꢀ Combustion air and vent pipes must be  
airtight and watertightꢀ  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6ꢀ Consideration for the following should be used when determining an appropriate location  
for termination of combustion air and vent pipingꢀ  
• Comply with all clearances required as stated in paragraph 7ꢀ  
• Termination should be positioned where vent vapors will not damage plants/shrubs or air  
conditioning equipmentꢀ  
• Termination should be positioned so that it will not be effected by wind eddy, air born  
leaves, snow, or recirculated flue gasesꢀ  
• Termination should be positioned where it will not be subjected to potential damage by  
foreign objects, such as stones, balls, etcꢀꢀ  
• Termination should be positioned where vent vapors are not objectionableꢀ  
• Put vent on a wall away from the prevailing winter windꢀ Locate or guard the vent to  
prevent accidental contact with people or petsꢀ  
• Terminate the vent above normal snowlineꢀ Avoid locations where snow may drift and  
block the ventꢀ Ice or snow may cause the boiler to shut down if the vent becomes  
obstructedꢀ  
• Under certain conditions, flue gas will condense, forming moisture, and may be corrosiveꢀ  
In such cases, steps should be taken to prevent building materials at the vent from being  
damaged by exhaust of flue gasꢀ  
7ꢀ The venting system shall terminate at least 3 feet above any forced air inlet (except the  
boiler’s combustion air inlet) within 10 feetꢀ The venting system shall terminate at least 12  
inches from any air opening into any buildingꢀ The bottom of the vent shall be located at  
least 12 inches above gradeꢀ Termination of the vent shall be not less than 7 feet above an  
adjacent public walkwayꢀ The vent terminal shall not be installed closer than 3 feet from the  
inside corner of an L shaped structureꢀ Termination of the vent should be kept at least 3  
feet away from vegetationꢀ The venting system shall terminate at least 4 feet horizontally  
from, and in no case above or below, unless a 4 foot horizontal distance is maintained, from  
electric meters, gas meters, regulators, and relief equipmentꢀ  
FIGURE 9 ROOF VENT/INTAKE TERMINATIONS  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 10 SIDEWALL VENT/INTAKE TERMINATIONS  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 11 COMBUSTION AIR AND VENT PIPING  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Bꢀ INSTALLATION  
1ꢀ Attach combustion air intake piping to supplied Fernco 2" coupling on mixerꢀ Attach  
vent piping to furnished 2" CPVC vent tee on draft inducer outletꢀ  
NOTE: All pipe joints are to be water tightꢀ  
2ꢀ Working from the boiler to the outside, cut pipe to required length(s)ꢀ  
3ꢀ Deburr inside and outside of pipeꢀ  
4ꢀ Chamfer outside edge of pipe for better distribution of primer and cementꢀ  
5ꢀ Clean and dry all surfaces to be joinedꢀ  
6ꢀ Check dry fit of pipe and mark insertion depth on pipeꢀ  
NOTE: It is recommended that all pipes be cut, prepared, and pre-assembled before  
permanently cementing any jointꢀ  
7ꢀ After pipes have been cut and pre-assembled, apply cement primer to pipe fitting  
socket and end of pipe to insertion markꢀ Quickly apply approved cement to end of pipe  
and fitting socket (over primer)ꢀ Apply cement in light, uniform coat on the inside of  
socket to prevent buildup of excess cementꢀ Apply second coatꢀ  
8ꢀ While cement is still wet, insert pipe into socket with a’/a turn twistꢀ Be sure pipe is fully  
inserted into fitting socketꢀ  
9ꢀ Wipe excess cement from jointꢀ A continuous bead of cement will be visible around  
perimeter of a properly made jointꢀ  
10ꢀ Handle pipe joint carefully until cement setsꢀ  
11ꢀ Support combustion air and vent piping a minimum of every 5 feet using pre-formed  
metal hanging strapsꢀ Do not rigidly support pipesꢀ Allow movement due to expansion  
and contractionꢀ  
12ꢀ Slope combustion air and vent pipes toward boiler a minimum of 1/4" per linear foot with  
no sags between hangersꢀ  
13ꢀ Use appropriate methods to seal openings where vent and combustion air pipes pass  
through roof or side wallꢀ  
GAS SUPPLY PIPING  
Aꢀ CHECK GAS SUPPLY  
The gas pipe to your boiler must be the correct size for the length of run and for the total  
BTU per hour input of all gas utilization equipment connected to itꢀ See Table 3 for the  
proper sizeꢀ Be sure your gas line complies with local codes and gas company  
requirementsꢀ  
The boiler and its individual shutoff valve must be disconnected from the gas supply piping  
system during any pressure testing of that system at test pressures in excess of ‘/z psig (3ꢀ5kpa)ꢀ  
The boiler must be isolated from the gas supply piping system by closing its individual  
manual shutoff valve during any pressure testing of the gas supply piping system at test  
pressures equal to or less than ‘/z psig (3ꢀ50ka)ꢀ  
1$785$/ꢀ*$6  
ꢁꢂ´ꢀZꢃFꢃ  
3523$1(ꢀ*$6  
ꢁꢄ´ꢀZꢃFꢃ  
0$;,080ꢀ*$6ꢀ6833/<ꢀꢀ35(6685(  
0,1,080ꢀ*$6ꢀ6833/<ꢀ35(6685(  
ꢅ´ꢀZꢃFꢃ  
ꢁꢂ´ꢀZꢃFꢃ  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Bꢀ CONNECTING THE GAS PIPING  
Refer to Figꢀ12 for the general layout at the boilerꢀ It shows the basic fittings you will needꢀ  
The gas line enters the boiler from the right side jacket panelꢀ The boiler may receive the gas  
supply pipe through the left side, or rear jacket panel by relocating the gas valve connector  
and pipe assemblyꢀ The boiler is equipped with a ‘/z” NPT connection on the gas valve for  
supply pipingꢀ The following rules apply:  
1ꢀ Use only those piping materials and joining methods listed as acceptable by the authority  
having jurisdiction, or in the absence of such requirements, by the National Fuel Gas  
Code, ANSI Z223ꢀ1- latest revisionꢀ In Canada, follow the CSA- B 149ꢀ1 and ꢀ2  
Installation Codes for Gas Burning Appliances and Equipmentꢀ  
2ꢀ Use pipe joint compound suitable for liquefied petroleum gas on male threads onlyꢀ  
3ꢀ Use ground joint unionsꢀ  
4ꢀ Install a sediment trap upstream of gas controlsꢀ  
5ꢀ Use two pipe wrenches when making the connection to the gas valve to keep it from  
turningꢀ  
6ꢀ Install a manual shutoff valve in the vertical pipe about 5 feet above floorꢀ  
7ꢀ Tighten all joints securelyꢀ  
8ꢀ Propane gas connections should only be made by a licensed propane installerꢀ  
9ꢀ Two stage regulation should be used by the propane installerꢀ  
10ꢀ Propane gas piping should be checked out by the propane installerꢀ  
Cꢀ CHECKING THE GAS PIPING  
After all connection have been made, check immediately for leaksꢀ Open the manual shutoff  
valveꢀ Test for leaks by applying soap suds (or a liquid detergent) to each jointꢀ Bubbles forming  
indicate leakꢀ CORRECT EVEN THE SMALLEST LEAK AT ONCEꢀ  
WARNING  
NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKSꢀ  
TABLE 3 GAS PIPE SIZES  
1$785$/ꢆ*$6  
/HQJWKꢆRIꢆꢆꢆꢆꢆꢆꢆꢆꢆ  
3LSHꢆ&DSDFLW\ꢆꢋꢆ%78ꢆ3HUꢆ+RXUꢆ,QSXWꢆ,QFOXGHVꢆ)LWWLQJV  
3LSHꢆꢋꢆ)Wꢌ  
ꢀꢁꢂꢃ  
ꢄꢁꢅꢃ  
ꢄꢀꢃꢂꢃꢃꢃ  
ꢄꢅꢃꢂꢃꢃꢃ  
ꢀꢃ  
ꢀꢆꢀꢁꢅꢃ  
ꢂꢇ  
ꢅꢇ  
ꢈꢇ  
ꢀꢁꢂꢃꢃꢃ  
ꢇꢅꢂꢃꢃꢃ  
ꢆꢃꢂꢃꢃꢃ  
ꢅꢆꢃꢂꢃꢃꢃ  
ꢁꢈꢆꢂꢃꢃꢃ  
ꢄꢀꢆꢂꢃꢃꢃ  
ꢇꢁꢆꢂꢃꢃꢃ  
ꢈꢈꢆꢂꢃꢃꢃ  
ꢅꢇꢆꢂꢃꢃꢃ  
ꢄꢃꢆꢂꢃꢃꢃ  
3523$1(ꢆ*$6  
3LSHꢆ&DSDFLW\ꢆꢋꢆ%78ꢆ3HUꢆ+RXUꢆ,QSXWꢆ,QFOXGHVꢆ)LWWLQJV  
&RSSHUꢆ7XELQJꢍ ,URQꢆ3LSH  
ꢉꢁꢊꢃ  
/HQJWKꢆRIꢆꢆꢆꢆꢆꢆꢆꢆꢆ  
3LSHꢆꢋꢆ)Wꢌ  
ꢄꢁꢅꢃ  
ꢀꢁꢂꢃ  
ꢄꢁꢅꢃ  
ꢂꢇ  
ꢅꢇ  
ꢈꢇ  
ꢄꢅꢄꢂꢃꢃꢃ  
ꢀꢃꢂꢃꢃꢃ  
ꢊꢁꢂꢃꢃꢃ  
ꢁꢄꢇꢂꢃꢃꢃ  
ꢄꢈꢆꢂꢃꢃꢃ  
ꢄꢁꢄꢂꢃꢃꢃ  
ꢄꢉꢀꢂꢃꢃꢃ  
ꢄꢁꢀꢂꢃꢃꢃ  
ꢄꢃꢅꢂꢃꢃꢃ  
ꢅꢀꢅꢂꢃꢃꢃ  
ꢁꢇꢊꢂꢃꢃꢃ  
ꢁꢄꢊꢂꢃꢃꢃ  
ꢋꢌ2XWVLGHꢌGLDPHWHU  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The length of pipe or tubing should be measured from the gas meter or propane second stage regulatorꢀ  
FIGURE 12 GAS PIPING  
ELECTRICAL WIRING  
WARNING  
TURN OFF ELECTRICAL POWER AT FUSE BOX BEFORE MAKING ANY LINE  
VOLTAGE CONNECTIONSꢀ FOLLOW LOCAL ELECTRICAL CODESꢀ  
All electrical work must conform to local codes as well as the National Electrical Code, ANSI/  
NFPA70, latest revisionꢀ In Canada, electrical wiring shall comply with the Canadian Electrical  
Codes, CSAC22ꢀ1 and ꢀ2  
Aꢀ ELECTRIC POWER SUPPLY  
Prior to making any line voltage connections, service switch at boiler should be in the off  
position and the power turned off at the fuse box  
Run a separate 120 volt circuit from a sperate over current protection device in the  
electrical service entrance panelꢀ This should be a 15 ampere circuitꢀ A service switch has  
been pre-wired and located on the exterior boiler jacketꢀ See Figꢀ 13 for diagram showing  
location of service switch junction box and power supply connection pointsꢀ Connect black  
(hot) lead from the power supply  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
to either of the unused brass screws on the service switchꢀ Connect the white (neutral) lead from  
the power supply to the white screw on the service switchꢀ Connect the green (ground) lead  
from the power supply to the ground (green) screw on the service switchꢀ The receptacle on the  
service switch is always powered regardless of whether the switch is on or off, and could be  
used as a power supply for an external condensate pump if one is usedꢀ  
The boiler, when installed, must be electrically grounded in accordance with the requirements of  
the authority having jurisdiction or, in the absence of such requirements, with the National Elec-  
trical Code, ANSI/NFPA-70, latest revisionꢀ In Canada, electrical wiring shall comply with the  
Canadian Electrical Codes, CSA-C22ꢀ1 and ꢀ2ꢀ  
Run a 14 gauge or heavier copper wire from the boiler to a grounded connection in the service  
panel or a properly driven and electrically grounded ground rodꢀ  
Bꢀ INSTALL YOUR THERMOSTAT  
The thermostat location has an important effect on the operation of your boiler systemꢀ BE  
SURE TO FOLLOW THE INSTRUCTIONS INCLUDED WITH YOUR THERMOSTATꢀ  
Locate the thermostat about five feet above the floor on an inside wallꢀ It may be mounted di-  
rectly on the wall or on a vertical mounted outlet boxꢀ It should be sensing average room tem-  
peratureꢀ Avoid the Following:  
DEAD SPOTS:  
COLD SPOTS:  
HOT SPOTS:  
Behind doors  
Concealed pipes or ducts Concealed pipes  
Lamps  
Comers and alcoves Stairwells - drafts  
Unheated rooms on  
Fireplace  
TV sets  
Radios  
Direct sunlight  
Kitchens  
other side of wall  
Set heat anticipator at 0ꢀ7 ampsꢀ Connect 24 volt thermostat leads to the two(2) yellow wires  
located in service switch junction box, located on outer jacket of boilerꢀ See Figꢀ13 for service  
switch junction box and thermostat field wiring connectionsꢀ  
Cꢀ Connect Circulator Pump Wiring  
See Figꢀ13 for service switch junction box and circulator pump field wiring connectionsꢀ A 5 feet  
wiring harness with flexible metal conduit is supplied to connect the circulator pump to the ser-  
vice switch junction boxꢀ If the two 120 volt circulator wire terminals inside the junction box are  
not used, please leave the two wire nuts to prevent the short circuitꢀ  
CAUTION  
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLSꢀ WIRING  
ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATIONꢀ VERIFY PROPER  
OPERATION AFTER SERVICINGꢀ  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cꢀ  
FIGURE 13 FIELD WIRING CONNECTIONS  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If any of the original wire as supplied with this appliance must be replaced, it must be replaced  
with type 150°C Thermoplastic wire or its equivalent  
Dꢀ  
FIGURE 14 SCHEMATIC WIRING DIAGRAM  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Eꢀ  
FIGURE 15 LADDER WIRING DIAGRAM  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTROLS AND ACCESSORIES  
This section provides a brief description of the key controls and accessories found in this boilerꢀ  
See the Troubleshooting section of the Service Hints chapter of this installation manual for detailed  
sequences of operation and troubleshooting proceduresꢀ See the Repair Parts chapter of this manual for  
locations of all control components and accessories describedꢀ  
Aꢀ INTEGRATED BOILER CONTROL (IBC)  
The Integrated Boiler Control (IBC) is a microprocessor based controller for a high efficiency gas  
boiler that monitors all safety controls and which controls the operation of the combustion air blower,  
circulator pump, burner, and a combination hot surface igniter/flame sensorꢀ This controller is not  
intended for use with a vent damperꢀ This controller is mounted on the control panel inside of the  
boiler and contains four (5) diagnostic indicator lightsꢀ  
Bꢀ GAS CONTROL VALVE  
The electrically controlled 24 Volt Honeywell Model VR8205 Combination Gas Control Valve is  
designed to meet the requirements for use with hot surface ignition systems found in this boilerꢀ  
The valve is piped to the gas/air mixerꢀ  
Cꢀ HOT SURFACE IGNITER  
The 120 volt Hot Surface Igniter heats up to 1800 °F to initiate combustion of the gas in the burnerꢀ  
The igniter is mounted next to the burner through the gas/air mixerꢀ The igniter also serves as a  
means for proving the main burner flame by flame rectificationꢀ In the event of a lack of flame signal  
on three (3) consecutive trials for ignition, the IBC will lockoutꢀ The “VALVE” and “FLAME” diagnostic  
indicator lamps (lamp “D” and “E” on the IBC, See Figꢀ 16) will blink indicating the failure mode as a  
lack of flame signalꢀ The IBC is manually reset from lockout by either removing and reestablishing the  
thermostat’s call for heat, or by turning the service switch off, then back onꢀ  
Dꢀ HIGH LIMIT AQUASTAT CONTROL  
The High Limit Aquastat Control determines the maximum boiler water temperature and also  
provides a means for protecting the boiler and heating system from unsafe operating conditions  
which could damage the boilerꢀ The aquastat is mounted in the ½" NPT control well and ¾”x½”  
bushing on the top of the front boiler section at the hot water outletꢀ The aquastat is tied in with the  
IBC and is factory set at 180 °F water temperatureꢀ The high limit setpoint is field adjustable and may  
be set anywhere between 100 °F and 200 °Fꢀ The field setpoint adjustment for each installation  
depends on heating system requirementsꢀ The aquastat automatically resets when the boiler water  
temperature decreases (5-30 °F adjustable differential)ꢀ The differential can be adjusted with the  
(white) Differential Adjustment Wheel on the aquastat and gives the flexibility for boiler operationꢀ The  
larger the differential, the longer the run cycle of the boilerꢀ  
NOTE: The maximum setpoint of the Aquastat must not exceed 200 °Fꢀ  
Eꢀ DRAFT INDUCER TEMPERATURE SAFETY SWITCH  
The Draft Inducer Temperature Safety Switch is a disc thermostat (180 °F setpoint) located on the  
induced draft fan outlet portꢀ The switch protects the inducer and vent pipe from a potential high  
temperature condition for the discharging flue gasesꢀ This condition would typically be a result of  
higher aquastat setting or over firingꢀ The temperature safety switch automatically resets when the  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
higher aquastat setting or over firingꢀ The temperature safety switch automatically resets  
when the vent temperature decreasesꢀ (15 °F switch differential)ꢀ  
Fꢀ CASTING TEMPERATURE SAFETY SWITCH  
In the event of lack of or loss of water in the boiler, the Casting Temperature Safety Switch  
(300 °F setpoint) installed on the top of the aluminum boiler section shuts off the boiler by  
shutting off power to the Integrated Boiler Control (IBC) and causes the Power Indicator Light  
to go outꢀ This fault requires manual reset of the casting temperature safety switch to restart  
the boilerꢀ Verify that the boiler is properly filled with water before resetting this switchꢀ  
WARNING-Never run cold water into a hot empty boilerꢀ  
Gꢀ DIFFERENTIAL PRESSURE AIR PROVING SWITCH  
The diaphragm type differential pressure switch is connected by vinyl tubing to the pressure  
signal hose adaptersꢀ The pressure switch monitors air flow by sensing the diffential  
pressure measured in inches of water(“ wꢀcꢀ)ꢀ The factory settings on these switches are  
1ꢀ00 “wꢀcꢀ for Model-100, 1ꢀ35 “wꢀcꢀ for Model-75 and 1ꢀ55 “wꢀcꢀ for Model-50ꢀ The contacts  
are normally open, and close when the draft inducer is running and causing the diffential  
pressure at the switch to exceed the settingꢀ The closed switch proves there is adequate air  
flow for combustionꢀ The pressure switch shuts off the main burner if the differential pressure  
is inadequate due to a blocked vent pipe or a blocked air intake or blocked boiler sections or  
blocked draft inducerꢀ After five (5) minutes of lack of the adequate differential pressure, the  
IBC will lockoutꢀ The “PURGE” indicator light will blink, indicating a failure to prove adequate  
combustion air flow or flue gas flowꢀ The IBC is manually reset from lockout as described in  
the Sequence of Operation section of this chapterꢀ  
Hꢀ DRAFT INDUCER  
The draft inducer (blower) provides a means for pulling combustion air into and through the  
mixer, the burner, the flue ways of the cast aluminum boiler sections and the flue adapter  
before being discharged through the vent piping to the outdoorsꢀ See applicable sections for  
proper sizing and installation of combustion air and vent piping in this manualꢀ  
Iꢀ CIRCULATOR PUMP  
Every forced hot water system requires at least one circulating pumpꢀ The circulating pump  
imparts the necessary energy to move the water through the closed loop supply and return  
piping systems, terminal heating equipment (iꢀeꢀ finned tube radiators, etcꢀ) and back  
through the boiler for reheatingꢀ To provide the required hot water flow rates, the circulator  
pump must be properly sized to overcome frictional losses (usually measured in feet of  
water, also referred to as “pump head loss”) of the supply and return piping systems and  
boilerꢀ The circulator pump is furnished in a carton within the boiler cabinet for a single zone  
or zone valve controlled heating system and should be correctly located on the downstream  
(iꢀeꢀ, pumping away) side of the expansion tankꢀ For a pump controlled system (where there  
is a circulator for each zone) the circulator provided with the boiler can work for one zoneꢀ  
For more details on piping and circulators, see Near Boiler Piping section of this manualꢀ  
Jꢀ DRAIN VALVE  
The manual drain valve provides a means of draining the water in the heating system, including  
the boiler and hot water supply and return piping systems installed above the drain valveꢀ This  
drain valve is installed in the 3/4" tapping at the bottom of the front boiler sectionꢀ Any piping  
installedbelow the elevation of this drain valve will require additional drain valves to be installed  
at low points in the piping systems in order to drain the entire systemꢀ  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Kꢀ AꢀSꢀMꢀEꢀ RATED PRESSURE RELIEF VALVE  
Each boiler must have a properly sized and installed American Society of Mechanical Engi-  
neers rated pressure relief valveꢀ Water expands as it is heated by the burner/boiler sectionsꢀ  
If there is no place for the water to expand its volume, (iꢀeꢀ a properly sized and properly  
functioning expansion tank) pressure on the inside of the boiler and heating system will  
increaseꢀ The furnished relief valve will automatically open at 30 psig pressure to relieve the  
strain on the boiler and heating system from the increasing pressureꢀ The pressure relief  
valve discharge must be piped with piping same size as the valve discharge opening to an  
open drain, tub or sink, or other suitable drainage point not subject to freezing, in accordance  
with AꢀSꢀMꢀEꢀ specificationsꢀ Failure to provide the pressure relief valve with piping as herein  
described may cause water damage and/or serious bodily injuryꢀ The boiler manufacturer is  
not responsible for any water damage or personal injuryꢀ  
Lꢀ FLAME ROLLOUT SAFETY SHUTOFF  
As required, this boiler is equipped with a manual reset flame rollout safety shutoff means,  
which shuts off main burner gas in the event that the flow of combustion products through  
the flueways is reducedꢀ In the event of blocked flueways, enough air will not be available to  
support combustion, and the S9301 Integrated Boiler Control (IBC) will lockout due to loss of  
adequate air flow (after 3 trials for ignition)ꢀ The “PURGE” diagnostic indicator lamp (lamp “B”  
on the IBC, see Figꢀ16) will blink indicating the failure mode as a lack of adequate air flowꢀ  
The IBC is manually reset from lockout by either removing and reestablishing the  
thermostat’s call for heat, or by turning the service switch off, then back onꢀ If the boiler  
cannot be restored to normal operating condition by resetting the control, contact a qualified  
service agency to check heat exchanger flueways for blockageꢀ  
Mꢀ (OPTIONAL) EXTERNAL CONDENSATE PUMP  
For installations where there is no floor drain or other appropriate drainage receptacle avail-  
able to receive condensate from the boiler, an external float activated condensate pump with  
integral sump is requiredꢀ This unit can be installed to pump the condensate to a remote tie  
in point to a sanitary sewer systemꢀ For this application, the boiler must be installed so that  
proper pitch of piping to the external condensate reservoir (sump) can be accomplishedꢀ Use  
wood frame or blocks to raise boiler as required for proper installationꢀ  
START - UP  
Aꢀ WATER TREATMENT AND FREEZE PROTECTION  
1ꢀ When filling the boiler and heating system, water treatment is generally not required or  
desiredꢀ For localities where the water is unusually hard (above 7 grains hardness) or for  
low pH water conditions (below 7ꢀ0), consult a local water treatment specialistꢀ  
aꢀ This boiler is designed for use in a closed hydronic heating system ONLY!  
bꢀ Excessive feeding of fresh make-up water to the boiler may lead to premature failure  
of the boiler sectionsꢀ  
2ꢀ Use clean fresh tap water for initial fill and make-up of boilerꢀ  
aꢀ A sand filter must be used if fill and make-up water from a well is to be usedꢀ  
bꢀ Consideration should be given to cleaning the heating system, particularly in  
retrofit situations, where a new boiler is being installed in an older piping systemꢀ  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
cꢀ In older system, obviously discolored, murky, or dirty water, or a pH reading below 7, are  
indications that the system should be cleanedꢀ  
dꢀ A pH reading between 7 and 8 is preferredꢀ  
3ꢀ Antifreeze if needed, must be of a type specifically designed for use in closed hydronic heating  
systems and with aluminumꢀ  
aꢀ Choice and use of antifreeze must be in accordance with local plumbing codesꢀ  
b Only INTERCOOL NFP-50 is approved for useꢀ  
Ÿ Use of any antifreeze other than INTERCOOL NFP-50 will void warrantyꢀ  
Ÿ Antifreeze must be maintained per manufacturers specifications, failure to do so will  
result in the warranty being voidedꢀ  
cꢀ Do not use automotive antifreeze as the type of corrosion inhibitors used will coat the boiler’s  
heat transfer surfaces and greatly reduce capacity and efficiencyꢀ  
dꢀ Consult antifreeze manufacturer’s literature for compatibility of antifreeze with  
aluminum boilerꢀ For approved manufactured antifreeze (INTERCOOL NFP-50 Coolant)  
please contact Interstate Chemical Coꢀ New York Customer Service at 1-800-422-2436ꢀ  
Some brands have corrosion inhibitors that break down more rapidly or become ineffective at  
higher operating temperatures when used with aluminumꢀ Follow the antifreeze manufacturers  
instructions on determining the proper ratio of antifreeze to water for the expected low  
temperature conditions, and for maintaining the quality of the antifreeze solutions from year to  
yearꢀ  
eꢀ Use of antifreeze in any boiler will reduce capacity by as much as 10 to 20%, due to differing  
heat transfer and pumping characteristicsꢀ This must be taken into consideration when sizing  
the heating system, pump(s), and expansion tankꢀ Consult antifreeze manufacturer’s literature  
for specific information on reduced capacityꢀ  
fꢀ Water content of the boiler is 2ꢀ6 gallonsꢀ (10 liters)  
Bꢀ FILLING BOILER WITH WATER AND PURGING ARE FOR SYSTEMS WITH DIAPHRAGM  
TYPE EXPANSION TANKSꢀ  
Refer to appropriate “Near Boiler Piping” diagramsꢀ  
1ꢀ Close all zone service valves on the supply and return pipingꢀ Open the feed valve and fill boiler  
with waterꢀ Make sure air vent is openꢀ Hold relief valve open until water runs air free for five  
seconds to rapidly bleed air from boiler, then let the relief valve snap shutꢀ  
2ꢀ Open the zone service valve on the supply pipe for the first zoneꢀ Open the purge valve on the  
first zoneꢀ Feed water will fill the zone, pushing air out the purge valveꢀ Close the purge valve  
when the water runs air freeꢀ Close the zone service valveꢀ  
3ꢀ Repeat step 2 for all remaining zonesꢀ  
4ꢀ Open all service valvesꢀ Any air remaining trapped in the return lines between the service valves  
and the boiler will be pushed towards the air vent when the boiler is placed in operationꢀ  
5ꢀ Inspect piping systemꢀ Repair any leaks immediatelyꢀ  
Cꢀ FILLING BOILER WITH WATER AND PURGING AIR FOR SYSTEMS WITH  
CONVENTIONAL CLOSED TYPE EXPANSION TANKS  
Refer to appropriate “Near Boiler Piping” diagramsꢀ  
1ꢀ Close all zone service valves on the supply and return piping and close the expansion tank service  
valveꢀ Drain expansion tankꢀ Open the feed valve and fill boiler with waterꢀ Hold relief valve open  
until water runs air free for five seconds to rapidly bleed air from boiler, then let the relief valve  
snap shutꢀ  
2ꢀ Open the zone service valve on the supply pipe for the first zoneꢀ Open the purge valve on the  
first zoneꢀ Feed water will fill the zone, pushing air out the purge valveꢀ Close the purge valve  
when the water runs air freeꢀ Close the zone service valveꢀ  
3ꢀ Repeat step 2 for all remaining zonesꢀ  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4ꢀ Open the expansion tank service valve and the tank ventꢀ Fill the tank to the proper level  
and close the tank ventꢀ Remove the handle from the expansion tank service valve so  
the homeowner doesn’t accidentally close itꢀ  
5ꢀ Open all service valvesꢀ Any air remaining trapped in the return lines between the  
service valves and the boiler will be pushed towards the expansion tank when the boiler  
is placed in operationꢀ  
6ꢀ Inspect piping systemꢀ Repair any leaks immediatelyꢀ  
NOTE: DO NOT use stop leak compoundsꢀ Leaks in threaded connections in the  
aluminumboiler sections must be repaired immediatelyꢀ Aluminum threads will not  
seal themselvesꢀ  
Dꢀ PLACING BOILER IN OPERATION  
FOR YOUR SAFETY READ BEFORE OPERATING  
WARNING: If you do not follow these instructions exactly, a fire or explosion  
may result causing property damage, personal injury or loss of life  
Aꢀ  
Bꢀ  
This appliance is equipped with an ignition device which  
automatically lights the pilotꢀ Do not try to light the pilot  
by handꢀ  
· If you cannot reach your gas supplier, call the fire  
departmentꢀ  
Cꢀ  
Dꢀ  
Use only your hand to move the system control switchꢀ  
Never use toolsꢀ If the switch will not move by hand,  
don't try to repair it, call a qualified service technicianꢀ  
Force or attempted repair may result in a fire or  
explosionꢀ  
BEFORE OPERATING smell all around the appliance  
area for gasꢀ Be sure to smell next to the floor because  
some gas is heavier than air and will settle on the floorꢀ  
WHAT TO DO IF YOU SMELL GAS  
· Do not try to light any applianceꢀ  
Do not use this appliance if any part has been under  
waterꢀ Immediately call a qualified service technician  
to inspect the appliance and to replace any part of the  
control system and any gas control which has been  
· Do not touch any electrical switch; do not use any phone  
in your buildingꢀ  
· Immediately call your gas supplier from a neighbor's  
phoneꢀ Follow the gas supplier's instructionsꢀ  
under waterꢀ  
OPERATING INSTRUCTIONS  
5ꢀ Remove the front jacket panelꢀꢀ  
1ꢀ STOP! Read the safety information above on this labelꢀ  
2ꢀ Set thermostat to lowest settingꢀ  
6ꢀ Turn the gas control knob clockwise  
to “OFF”ꢀ  
7ꢀ Wait five (5) minutes to clear out any gasꢀ Then smell for  
gas, including near the floorꢀ If you smell gas, STOP!  
Follow “B” in the safety information above on this labelꢀ If  
you don’t smell gas go on to next stepꢀ  
3ꢀ Turn off all electric power to the applianceꢀ  
4ꢀ This appliance is equipped with an ignition device which  
automatically lights the burnerꢀ DO NOT try to light the  
burner by handꢀ  
8ꢀ Turn the gas control knob counter clockwise  
“ON”ꢀ  
to  
9ꢀ Replace front jacket panelꢀ  
10ꢀ Turn on all electrical power to the applianceꢀ  
11ꢀ Set the thermostat to desired settingꢀ  
12ꢀ Iftheappliancewillnotoperate, followtheinstructionsTo  
TurnOffGasToApplianceandcallyourservicetechnician  
or gas supplierꢀ  
TO TURN OFF GAS TO APPLIANCE  
1ꢀ Set the thermostat to lowest settingꢀ  
2ꢀ Turn off all electric power to the appliance if service is to  
be preformedꢀ  
4ꢀ Turn gas control knob clockwise  
5ꢀ Replace the front jacket panelꢀ  
to “OFF”ꢀ  
3ꢀ Remove the front jacket panelꢀ  
Safe lighting and other performance criteria were met with the gas manifold and control assembly  
provided on the boiler when the boiler underwent tests specified in ANSI Z21ꢀ13-latest revisionꢀ  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHECK OUT PROCEDURE AND ADJUSTMENT  
FIGURE 16 INDICATOR LAMPS  
Aꢀ VERIFY PROPER SEQUENCE OF OPERATION  
The sequence can be followed via the diagnostic indicator lamps on the Honeywell S9301A  
integrated boiler control in Figꢀ 16ꢀ This is the normal sequence of operationꢀ A more detailed  
sequence of operation containing potential faults can be found in the service hints sectionꢀ  
',$*1267,&  
,1',&$725  
/$036  
6(48(1&(ꢀ2)ꢀ23(5$7,21  
3RZHUꢀ21ꢁꢀERLOHUꢀVWDQGLQJꢀE\ꢂꢀꢀ/DPSꢀ$ꢀLVꢀLOOXPLQDWHGꢀLQGLFDWLQJꢀꢃꢀYROWꢀSRZHUꢀLV  
EHLQJꢀVXSSOLHGꢀWRꢀWKHꢀLQWHJUDWHGꢀFRQWUROꢂ  
7KHUPRVWDWꢀFDOOVꢀIRUꢀKHDWꢁꢀHQHUJL]LQJꢀV\VWHPꢀFLUFXODWRU  
,QWHJUDWHGꢀERLOHUꢀFRQWUROꢀJRHVꢀWKURXJKꢀVHOIꢀFKHFNꢀRIꢀLQWHUQDOꢀFLUFXLWU\ꢀꢄꢅꢆꢃꢀVHFRQGVꢇ  
DQGꢀHQHUJL]HVꢀGUDIWꢀLQGXFHU  
'UDIWꢀLQGXFHUꢀFRPHVꢀXSꢀWRꢀVSHHGꢀDQGꢀHVWDEOLVKHVꢀFRPEXVWLRQꢀDLUIORZꢁꢀFDXVLQJꢀWKH  
QRUPDOO\ꢀRSHQꢀGLIIHUHQWLDOꢀSUHVVXUHꢀDLUꢀSURYLQJꢀVZLWFKꢀFRQWDFWVꢀWRꢀFORVHꢂꢀꢀ/DPSꢀ%ꢀLV  
LOOXPLQDWHGꢀLQGLFDWLQJꢀWKDWꢀFRPEXVWLRQꢀDLUIORZꢀLVꢀSURYHGꢀDQGꢀWKHꢀꢅꢈꢀVHFRQGꢀSUHꢀSXUJH  
F\FOHꢀLVꢀXQGHUꢀZD\ꢂ  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
$IWHUꢀSUHꢀSXUJHꢁꢀ/DPSꢀ%ꢀJRHVꢀRXWꢀDQGꢀ/DPSꢀ&ꢀLOOXPLQDWHVꢁꢀLQGLFDWLQJꢀWKHꢀKRWꢀVXUIDFHꢀ  
LJQLWHUꢀLVꢀSRZHUHGꢀIRUꢀWKHꢀꢂꢃꢀVHFRQGꢀLJQLWHUꢀZDUPꢄXSꢀSHULRGꢅꢀ7KHꢀEULJKWꢀ\HOORZꢀRUDQJHꢀ  
JORZꢀRIꢀWKHꢀKRWꢀVXUIDFHꢀLJQLWHUꢀFDQꢀEHꢀREVHUYHGꢀWKURXJKꢀWKHꢀREVHUYDWLRQꢀSRUWꢀLQꢀWKHꢀ  
IURQWꢀERLOHUꢀVHFWLRQꢀMXVWꢀDERYHꢀWKHꢀLJQLWHUꢅ  
$ꢅꢀè  
%ꢅꢀè  
&ꢅꢀî  
'ꢅꢀè  
(ꢅꢀè  
$ꢅꢀî  
%ꢅꢀè  
&ꢅꢀî  
'ꢅꢀî  
(ꢅꢀë  
$IWHUꢀLJQLWHUꢀZDUPꢄXSꢁꢀWKHꢀJDVꢀYDOYHꢀLVꢀHQHUJL]HGꢁꢀDQGꢀRSHQVꢀRQꢀWKHꢀQRUPDOꢀILULQJꢀUDWHꢀ  
UHJXODWRUꢀꢆꢂꢅꢇ'ꢀZꢅFꢅꢈꢀIRUꢀDꢀꢉꢀVHFRQGꢀWULDOꢀIRUꢀLJQLWLRQꢅꢀ/DPSꢀ'ꢀLOOXPLQDWHVꢅꢀ7KHꢀEOXHꢀRUDQJHꢀ  
JORZꢀRIꢀWKHꢀEXUQHUꢀFDQꢀEHꢀVHHQꢀWKURXJKꢀWKHꢀREVHUYDWLRQꢀSRUWꢅ  
7ZRꢀVHFRQGVꢀODWHUꢁꢀ/DPSꢀ&ꢀJRHVꢀRXWꢀDVꢀSRZHUꢀLVꢀWXUQHGꢀRIIꢀWRꢀWKHꢀKRWꢀVXUIDFHꢀLJQLWHUꢅꢀ  
'XULQJꢀWKHꢀODVWꢀWZRꢀVHFRQGVꢀRIꢀWKHꢀꢉꢀVHFRQGVꢀWULDOꢀIRUꢀLJQLWLRQꢁꢀPDLQꢀEXUQHUꢀIODPHVꢀLVꢀ  
SURYHQꢀE\ꢀIODPHꢀUHFWLILFDWLRQꢀWKURXJKꢀWKHꢀKRWꢀ'XULQJꢀVXUIDFHꢀLJQLWHUꢁꢀSURYLGLQJꢀIODPHꢀ  
UHFWLILFDWLRQꢀWRꢀWKHꢀLQWHJUDWHGꢀERLOHUꢀFRQWUROꢀDQGꢀIXOO\ꢀLOOXPLQDWLQJꢀ/DPSꢀ(ꢅꢅꢀ7KHꢀJDVꢀYDOYHꢀ  
UHPDLQVꢀHQHUJL]HGꢁꢀDQGꢀWKHꢀERLOHUꢀUXQVꢅ  
$ꢅꢀî  
%ꢅꢀè  
&ꢅꢀè  
'ꢅꢀî  
(ꢅꢀî  
$ꢅꢀî  
%ꢅꢀî  
&ꢅꢀè  
'ꢅꢀè  
(ꢅꢀè  
7KHUPRVWDWꢀHQGVꢀFDOOꢀIRUꢀKHDWꢁꢀGHꢄHQHUJL]LQJꢀJDVꢀYDOYHꢀDQGꢀV\VWHPꢀFLUFXODWRUꢅꢀ%XUQHUꢀ  
VWRSVꢀILULQJꢁꢀDQGꢀ/DPSꢀ'ꢀJRHVꢀRXWꢅꢀ'UDIWꢀLQGXFHUVꢀUHPDLQVꢀSRZHUHGꢅꢀ/DPSꢀ%ꢀLOOXPLQDWHVꢁꢀ  
LQGLFDWLQJꢀGUDIWꢀLQGXFHUꢀLVꢀUXQQLQJꢀIRUꢀꢊꢃꢀVHFRQGꢀSRVWSXUJHꢅ  
$ꢅꢀî  
%ꢅꢀè  
&ꢅꢀè  
'ꢅꢀè  
(ꢅꢀè  
$IWHUꢀꢊꢃꢀVHFRQGVꢁꢀGUDIWꢀLQGXFHUꢀLVꢀGHꢄHQHUJL]HGꢅꢀ/DPSꢀ%ꢀJRHVꢀRXWꢅꢀ%RLOHUꢀVWDQGVꢀE\ꢀIRUꢀ  
QH[WꢀFDOOꢀIRUꢀKHDWꢅ  
NOTE: First couple of cold starts may be rough due to gas line not being completely purged  
of air, causing low firing rate and high excess air levelsꢀꢀ  
Bꢀ INSPECT VENTING AND AIR INTAKE SYSTEM  
Operate the boiler and verify that all vent/air intake connections are gastight and watertightꢀ  
Repair any leaks immediatelyꢀ  
Cꢀ INSPECT CONDENSATE DRAIN  
Verify that all connections are watertight, and that condensate flows freelyꢀ Repair any leaks  
immediatelyꢀ  
Dꢀ INSPECT SYSTEM PIPING  
Verify that all connections are watertightꢀ Repair any leaks immediatelyꢀ  
Eꢀ TEST IGNITION SYSTEM SAFETY SHUTOFF DEVICE  
1ꢀ Turn off manual gas valve  
2ꢀ Set thermostat to call for heat  
3ꢀ Boiler begins normal sequence of operation  
4ꢀ After approximately 40 seconds (pre purge and igniter warm-up period), lamp D illumi  
nates, indicating gas valve is powered  
5ꢀ After 6 seconds, gas valve closes, lamp D goes out as integrated boiler control senses  
that flame is not present  
6ꢀ To restart system, follow operating instructions under “START-UP PLACE IN OPERATION”  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fꢀ TEST HIGH LIMIT CONTROL AND ADJUST  
While burner is operating, move indicator on high limit control below actual boiler water  
temperatureꢀ Burner should go off while circulator continues to operateꢀ Raise limit setting  
above boiler water temperature and burner should reignite after pre purge and igniter warm-  
up periodꢀ Set the high limit control to the design temperature requirements of the systemꢀ  
Maximum high limit setting is 200°Fꢀ Minimum high limit setting is 100°Fꢀ  
Gꢀ TEST OTHER SAFETY CONTROLS  
If the boiler is equipped with a low water cut off, a manual reset high limit, or additional safety  
controls, test for operation as outlined by the control manufacturerꢀ Burner should be operat-  
ing and should go off when controls are testedꢀ When safety controls are restored, burner  
should reigniteꢀ  
Hꢀ SET THERMOSTAT HEAT ANTICIPATOR (IF USED) AND VERIFY THERMOSTAT OPERATION  
For a single thermostat connected to the yellow thermostat lead wires in the furnished field  
wiring junction box, the heat anticipator should be set at 0ꢀ7 ampsꢀ For other wiring configura-  
tions, refer to the instructions provided by the thermostat manufacturer regarding adjustment  
of heat anticipatorꢀ Cycle boiler with thermostatꢀ Raise the thermostat to the highest setting  
and verify boiler goes through normal start up cycleꢀ Lower thermostat to lowest setting and  
verify boiler goes offꢀ  
Iꢀ MEASURE THE NATURAL GAS INPUT RATE  
Correct input rate is essential for proper and efficient operation of the burner and boilerꢀ  
1ꢀ Determine elevation at installation siteꢀ  
2ꢀ See page 4 and 5 of this manual to determine the correct input rate for the local elevationꢀ  
3ꢀ Obtain the yearly average heating value of the local gas supply from the gas utilityꢀ At sea  
level elevation, it should be approximately 1000 Btu’s per standard cubic footꢀ  
4ꢀ Operate boiler for 5 minutesꢀ  
5ꢀ Turn off all other gas appliances, extinguishing standing pilots where applicableꢀ  
6ꢀ At gas meter, measure time in seconds required to use one cubic foot of gasꢀ  
7ꢀ Calculate input rate according to the following formula:  
3600xheating value from step 3  
Btuh input rate = time from step 6  
8ꢀ Measured input rate should be within +/-2% of the input rating from step 2ꢀ If within 2%, go  
to step 9ꢀ If not, adjustment is required, proceed as follows:  
aꢀ Turn boiler off  
bꢀ Set up U-tube manometer or differential pressure gauge for measuring manifold pres  
sure, see FIGꢀ 17ꢀ  
cꢀ Manometer or gauge must be able to read at least 0ꢀ0 to 3ꢀ0 inches water column of  
pressure, and resolve to at least 0ꢀ1 inches water columnꢀ  
dꢀ Turn boiler onꢀ  
eꢀ Manifold pressure has been nominally set at 2ꢀ5 inches wꢀcꢀ Manifold pressure and input  
rate must always be measured with pressure regulator cover screw installedꢀ Cover screw  
must be removed for adjustmentꢀ Manifold pressure reading will change (increase) when  
cover screw is removedꢀ  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THE FOLLOWING STEPS AND DIAGRAM INDICATE THE LOCATION OF THE CONNECTION  
POINTS REQUIRED TO MEASURE THE MANIFOLD PRESSUREꢀ  
THE MANIFOLD PRESSURE MAY BE MEASURED USING A U-TUBE MANOMTERE OR A  
DIFFERENTILA PRESSURE GAUGEꢀ THE DIAGRAM SHOWS THE CONNECTION OF BOTH  
MEASURING DEVICES BUT ONLY ONE DEVICE IS REQUIRED TO MEASURE THE MANIFOLD  
PRESSUREꢀ  
© REMOVE THE PLUGꢀ INSTALL APPROPRIATE BARBED FITTING AND CONECT THE PRESSURE  
SIDE LINE FROM THE U-TUBE MANOMETER OR THE DIFFERENTIAL PRESSURE GAUGEꢀ  
REFER TO “CHECK OUT PROCEDURE AND ADJUSTMENTS” IN THIS MANUAL WHEN READING  
MANIFOLD PRESSUREꢀ  
WHEN MEASUREMENT IS COMPLETE, DISCONNECT U-TUBE MANOMETER OR DIFFERENTIAL  
PRESSURE GAUGEꢀ BE SURE TO REINSTALL 1/8" PLUG, USING APPROPRIATE PIPE THREAD  
SEALANT APPROVED FOR USE WITH NATURAL AND LIQUIFIED PETROLEUM GASESꢀ  
FIGURE 17 MANIFOLD PRESSURE MEASUREMENT DETAIL  
Top view of gas control  
NOTE: Regulator cover screw must be installed  
at all times unless adjusting manifold  
pressureꢀ Firing rate and manifold  
pressure must only be measured with  
cover screw firmly installedꢀ  
FIGURE 18 GAS VALVE  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Iꢀ Remove regulator cover screw on top of gas valve, and insert an appropriate screw-  
driver into adjustment screwꢀ  
IIꢀ Turn adjustment screw clockwise to increase input rate, or counter clockwise to de-  
crease input rateꢀ  
IIIꢀ Replace cover screw, or cover hole temporarily with your finger to check new mani-  
fold pressure settingꢀ Do not set manifold pressure lower than 2ꢀ0 inches wꢀcꢀ or  
higher than 3ꢀ0 inches wꢀcꢀ when adjusting input rateꢀ  
IVꢀ Measure new input rate (cover screw must be installed)ꢀ Repeat steps Iꢀ-IV until the  
input rate is within +/-2% of the nameplate input ratingꢀ  
Vꢀ If the actual input rate can not be set to within 2% of the correct input rating by adjust-  
ing manifold pressure, a change in gas orifice size is requiredꢀ Consult the boiler  
manufacturer for information on correct orifice sizingꢀ The specific gravity (G) and the  
higher heating value (HHV) of the local natural gas must be obtained from the local  
gas utility in order to determine the proper orifice sizeꢀ  
fꢀ After adjusting input rate, turn boiler off, remove manometer or pressure gauge, reinstall  
1/8" plug on gas valveꢀ Turn boiler onꢀ  
9ꢀRestore all gas appliances that may have been shut off (while measuring boiler input  
rate) to normal operating conditionsꢀ  
Jꢀ SET THERMOSTAT TO DESIRED ROOM TEMPERATURE  
Observe several operating cycles to verify proper operationꢀ  
K REVIEW ALL INSTRUCTIONS  
Review all instructions shipped with this boiler with owner or maintenance personꢀ Instructions  
must be affixed on or adjacent to the boilerꢀ  
Lꢀ COMPLETE AND SIGN THE INSTALLATION AND CHECK-OUT CERTIFICATE ON THE  
FOLLOWING PAGEꢀ  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION AND CHECK-OUT CERTIFICATE  
Boiler Model  
Serial #  
Date Installed___________  
Measured BTU/HR input____________  
¡ Installation instructions have been followed  
¡ Checkout procedure and adjustments performed  
¡ Maintenance and Service issues reviewed with owner/ maintenance person  
¡ Installation booklet affixed on or adjacent to boiler  
Installer (Company)  
Address  
Phone  
Installer’s Name  
Signature  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE AND CLEANING  
Maintenance as outlined below can be performed by the owner unless otherwise notedꢀ  
The acidic nature of flue gasses condensing on the aluminum boiler sections will cause the  
formation of aluminum oxideꢀ This oxide formation is normal, is generally uniform throughout the  
boiler sections, and represents a negligible mass of aluminum that is consumed by oxidation  
during the life of the boilerꢀ If left unchecked, this buildup may eventually cause blockage of the  
flue gas passages in the boiler sections, reducing efficiency, and ultimately shutting down the  
boiler due to lack of combustion air flowꢀ Regular service and maintenance by a qualified service  
agency must be performed to assure safe trouble free operation and maximum efficiencyꢀ  
Aꢀ BEGINNING OF EACH HEATING SEASON  
1ꢀ Annual service call by a qualified service agency, which includes:  
aꢀ Examine flue passages between boiler sections, burner, and condensate lines, and  
clean if necessary following the annual examination and cleaning instructions in para  
graph “F” on the next pageꢀ  
bꢀ Visually inspect venting and air intake system for proper function, deterioration or  
leakageꢀ If the vent or air intake show any signs of deterioration or leakage, repair or  
replace them, immediatelyꢀ Insure proper reassembly and resealing of the vent and air  
intake systemꢀ cꢀCheck for and remove any obstruction to the flow of combustion air  
or venting of flue gasesꢀ Check the air baffle located inside 1 1/2"x2" flexible coupling  
on the mixer, clean it if necessary and make sure to put it backꢀ Refer to repair parts  
diagram of mixer and pressure switch assembly for exact locationꢀ  
dꢀ Follow instructions for “PLACING BOILER IN OPERATION”ꢀ  
eꢀ Follow instructions for” CHECK OUT PROCEDURE AND ADJUSTMENTS”ꢀ  
fꢀ Visually inspect condensate drain line for proper operation and deteriorationꢀ Check  
for plugged condensate drain lineꢀ  
gꢀ Check the silicone rubber seals between boiler sectionsꢀ Insure that there are no  
leaksꢀ Use RTV silicone rubber adhesive sealant (available in caulking gun tubes)  
rated for at least 400° F to replace or repair seals in locations where original seals  
have deterioratedꢀ  
hꢀ Check all gasketed joints for leakage, and tighten bolts or replace gaskets if necessaryꢀ  
iꢀ Remove jacket front and top panels and check for piping leaks around relief valve and  
other fittingsꢀ Repair, if foundꢀ DO NOT use stop leak compoundsꢀ  
2ꢀ Check that boiler area is free from combustible materials, gasoline, and other flammable  
vapors and liquidsꢀ  
3ꢀ Circulator pump and blower motor furnished with boiler are permanently lubricated from  
factory and require no further lubricationꢀ Additional or non-factory supplied pumps and/or  
motors should be lubricated according to the pump and/or motor manufacturer’s instructionꢀ  
Bꢀ DAILY DURING HEATING SEASON  
1ꢀ Check for and remove any obstruction to the flow of combustion air or venting of flue gasesꢀ  
2ꢀ Check that boiler area is free from combustible materials, gasoline, and other flammable  
vapors and liquidsꢀ  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cꢀ MONTHLY DURING HEATING SEASON  
1ꢀ Remove jacket front and top panels and check for piping leaks around relief valve and  
other fittingsꢀ If found, contact a qualified service agency to repairꢀ DO NOT use stop leak  
compoundsꢀ  
2ꢀ Test relief valveꢀ Refer to valve manufacturers instructions packaged with relief valveꢀ  
3ꢀ Visually inspect venting and air intake system for proper function, deterioration, or  
leakageꢀ If the vent or air intake show any signs of deterioration or leakage, contact a  
qualified service agency to repair or replace them immediately and to insure proper  
reassembly and resealing of the vent and air intake systemꢀ  
4ꢀ Visually inspect the clear vinyl condensate lines and the PVC condensate drain pipe for  
proper operation, leakage, and deteriorationꢀ If the condensate lines or drain pipe show  
any signs of blockage, leakage, or deterioration contact a qualified service agency to  
clean, repair, or replace them immediatelyꢀ  
5ꢀ Check the air baffle located inside 1 1/2"x 2" flexible coupling, clean it if necessary and  
make sure to put it backꢀ Refer to repair parts diagram, mixer and pressure switch  
assemblyꢀ  
Dꢀ PERIODICALLY DURING HEATING SEASON  
1ꢀ Where low water cut offs are used, a periodic inspection of the low water cut off is  
necessary, including flushing of float type devicesꢀ Refer to low water cut off  
manufacturer’s specific instructionsꢀ  
Eꢀ END OF EACH HEATING SEASON - ANNUAL SHUTDOWN PROCEDUR  
1ꢀ Follow instructions “TO TURN OFF GAS TO APPLIANCE”ꢀ  
2ꢀ If heating system is to remain out of service during freezing weather, and does not contain  
antifreeze, drain system completelyꢀ If boiler will be exposed to freezing temperatures,  
drain condensate linesꢀ Otherwise, do not drain system or boilerꢀ  
Fꢀ ANNUAL EXAMINATION AND CLEANING OF BOILER COMPONENTS  
The following service procedures must be performed only by a qualified service  
agencyꢀ Boiler owner should not attempt these proceduresꢀ  
1ꢀ Before Servicing, turn off electrical power to boiler at service switchꢀ Close manual gas  
valve to turn off gas supply to boilerꢀ  
2ꢀ Cleaning Flue passages between boiler sectionsꢀ  
aꢀAny buildup of sediment or aluminum oxide (white powdery or flaky substance) in the  
flue passages must be cleaned as follows:  
bꢀRemove jacket front and top panelsꢀ Disconnect condensate drain line from the barbed  
fitting on the bottom of the boilerꢀ Keep the open end of the drain line above the water  
level in the condensate trap to prevent the trap from drainingꢀ Disconnect pressure switch  
hose from barbed fitting on gas valveꢀ Disconnect 1½ x 2” flexible coupling from air inletꢀ  
Disconnect air by-pass (½” transparent vinyl tube) from the bottom of the mixerꢀ  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
cꢀ Remove air baffle from 1%z” x2" flexible coupling and clean air baffle if necessaryꢀ  
Refer to repair parts diagram, mixer and pressure switch assemblyꢀ  
dꢀ Confirm that manual gas valve is closed and disconnect gas line to gas valve at unionꢀ  
Disconnect wires to gas valveꢀ and igniterꢀ  
eꢀ Loosen but do not remove five (5) nuts attaching mixer assembly to boilerꢀ Remove  
two (2) igniter screws and very carefully remove the igniterꢀ Use care when removing  
the igniter, it is very brittle!!  
fꢀ Remove five (5) nuts and remove mixer assemblyꢀ Remove burner and mixer gasketꢀ  
gꢀ Aluminum oxide deposits are water soluble and may be rinsed away with spraying or  
running waterꢀ Before rinsing, connect a ‘/z” IꢀDꢀ hose to the barbed fitting on the  
bottom of the boiler and run the hose to a bucket or drainꢀ  
hꢀ After rinsing, remove any remaining loosened sediment using a shop vacuum with a  
snorkel attachmentꢀ  
i Inspect burner for any foreign matter in the flame ports or inside the burnerꢀ Any for-  
eign matter should be removed by blowing with compressed air or vacuumingꢀ  
jꢀ Inspect interior of mixer for any signs of sediment or aluminum oxide and clean if necessaryꢀ  
kꢀ Reinstall burner and mixer gasket and position mixer assembly over studsꢀ Install five  
(5) nuts but do not tightenꢀ Reinstall igniter and igniter gasket and fasten with two (2)  
screwsꢀ Use care when installing the igniterꢀ It is very brittle!! Tighten five (5) nuts  
holding mixer assemblyꢀ  
lꢀ Connect:  
• gas line to gas valve  
• condensate drain line to boiler  
• pressure switch hose to gas valve  
• air by-pass to mixer  
• 1 1/2" x2" flexible coupling to air inlet and make sure to put air baffle back to  
correct position  
• igniter wires  
• gas valve wires  
3ꢀ Visually inspect condensate lines leading from the boiler sections and the vent tee to the  
condensate trapꢀ Refer to repair parts diagramsꢀ Any foreign material or debris that is  
visible in the condensate lines needs to be cleaned out as follows: ꢀ  
aꢀ Raise condensate trap and drain condensate lines completelyꢀ  
bꢀ Once the condensate trap is emptied of water, disconnect condensate lines from the  
fittings on the boiler, the vent tee, and the condensate outletꢀ  
cꢀ Remove the condensate trap and run cold water through the condensate lines to  
thoroughly flush out any sediment or debris in the linesꢀ  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
dꢀ Reinstall and connect the condensate trap, using the hose clamps to secure the various  
condensate lines to their fittingsꢀ  
eꢀ Follow the instructions under “NEAR BOILER PIPING” for”filling condensate trap with  
water”  
4ꢀ Inspection of the flue connector requires the following steps (Refer to the repair parts diagramꢀ)  
aꢀ Loosen the clamp on the draft inducer end of the 2" flexible coupling that connects the  
vent tee to the draft inducerꢀ Disconnect (unplug) wiring harness from draft inducer motor  
and draft inducer temperature safety switchꢀ Remove four (4) bolts that attach draft in  
ducer to flue connectorꢀ  
bꢀ Remove draft inducer and gasket from top of flue connectorꢀ  
cꢀ Inspect interior of flue connectorꢀ Any buildup of sediment or aluminum oxide on the  
inside surface must be cleanedꢀ Position the draft inducer gasket and the draft inducer  
and fasten with four (4) screwsꢀ Be sure to connect ground wire from draft inducer motor  
to one of the four mounting screwsꢀ  
dꢀ Connect wiring harness leads to the draft inducer motor and the draft inducer tempera  
ture safety switchꢀ  
eꢀ Connect the 2" flexible coupling to the draft inducer outletꢀ  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE HINTS  
DETAILED SEQUENCE OF OPERATION  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DETAILED SEQUENCE OF OPERATION  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
END OF NORMAL SEQUENCE OF OPERATION  
DETAILED SEQUENCE OF OPERATION  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!!WARNING!!  
FIRE, EXPLOSION OR SHOCK HAZARD MAY CAUSE  
PROPERTY DAMAGE, SEVERE INJURY OR DEATHꢀ  
DO NOT ATTEMPT TO MODIFY THE PHYSICAL OR ELECTRICAL  
CHARACTERISTICS OF THIS BOILER IN ANY WAYꢀ  
IMPORTANT  
1ꢀ IN A RESET FROM LOCKOUT CONDITION, ALL ELECTRICAL METER READINGS AT THE GAS  
CONTROL VALVE (24 VAC) MUST BE TAKEN WITHIN THE TRIAL FOR IGNITION PERIODꢀ  
2ꢀ IF ANY COMPONENT DOES NOT FUNCTION PROPERLY, MAKE SURE IT IS CORRECTLY INSTALLED  
AND WIRED BEFORE REPLACING ITꢀ  
3ꢀ STATIC ELECTRICITY DISCHARGE CAN DAMAGE THE INTEGRATED BOILER CONTROL (IBC)ꢀ  
TOUCH METAL SURFACE TO DISCHARGE STATIC ELECTRICITY BEFORE TOUCHING IBCꢀ  
4ꢀ THE IBC CANNOT BE REPAIREDꢀ IF IT MALFUNCTIONS IT MUST BE REPLACEDꢀ  
5ꢀ ONLY TRAINED, EXPERIENCED SERVICE TECHNICIANS SHOULD SERVICE THE IBC SYSTEMSꢀ  
FOLLOWING TROUBLESHOOTING, CHECK OUT THE SYSTEM FOLLOWING THE SEQUENCE OF  
OPERATION SECTION OF THIS CHAPTER FOR A NORMAL LIGHT OFF SEQUENCEꢀ  
6ꢀ ALL CONTROLS ARE FACTORY TESTED IN THE ASSEMBLY PROCESS AND A DEFECTIVE  
CONTROL IS GENERALLY THE LEAST LIKELY CAUSEꢀ IF YOU SUSPECT YOU HAVE A DEFECTIVE  
CONTROL, READ THROUGH THE TROUBLESHOOTING CHART BEFORE YOU REPLACE ITꢀ  
7ꢀ IT IS EXTREMELY UNLIKELY THAT THE TWO CONSECUTIVE CONTROLS ARE DEFECTIVEꢀ IF IT  
SEEMS TO BE HAPPENING, CHANCES ARE THAT EITHER THERE IS NOTHING WRONG WITH THE  
CONTORL OR IT IS BEING DAMAGED BY SOME OTHER PROBLEM (AN ELECTRICAL SHORT  
BURNING OUT A TRANSFORMER, FOR EXAMPLE)ꢀ  
INITIAL SERVICE CHECKS  
1ꢀ BEFORE TROUBLESHOOTING:  
Aꢀ MAKE SURE THAT CIRCUIT BREAKER IS ON OR FUSE IS OK AT ELECTRICAL PANELꢀ  
Bꢀ MAKE SURE THAT SERVICE SWITCH IS ONꢀ  
Cꢀ MAKE SURE THAT GAS IS ON AT THE GAS METER, AT ALL APPROPRIATE MANUAL  
SHUTOFF VALVES AND AT THE GAS CONTROL VALVEꢀ  
Dꢀ MAKE SURE THAT THE THERMOSTAT IS CALLING FOR HEATꢀ  
Eꢀ CHECK THAT WIRE CONNECTORS AT THE INTEGRATED BOILER CONTROL AND AT THE  
ORIGINATING CONTROL ARE SECURELY PLUGGED IN OR CONNECTEDꢀ  
Fꢀ CHECK THAT HOSES ARE SECURELY CONNECTED AND ARE NOT PLUGGED IN OR  
DAMAGEDꢀ  
2ꢀ TROUBLESHOOTING TOOLS:  
Aꢀ VOLTMETER TO CHECK 120 VAC AND 24 VAC  
Bꢀ CONTINUITY TESTERꢀ  
Cꢀ INCLINED MANOMETER OR PRESSURE GAUGE WITH 0-2ꢀ0” RANGE (0ꢀ01” SCALE) FOR  
MEASURING SUCTION PRESSURES AT PRESSURE SWITCHꢀ  
Dꢀ U-TUBE MANOMETER OR DIFFERENTIAL PRESSURE GAUGE WITH 0-14” RANGE (0ꢀ1”  
SCALE) FOR MEASURING INLET AND MANIFOLD GAS PRESSURESꢀ  
3ꢀ WHAT IS SYSTEM STATUS?  
Aꢀ CONSULT THE CHART ON THE FOLLOWING PAGEꢀ  
Bꢀ FIGURE 15 ON PAGE 29 SHOWS THE LOCATION ON THE BOILER OF THE DIAGNOSTIC  
INDICATOR LAMPSꢀ  
TROUBLE SHOOTING  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6<67(0ꢀ67$786  
UC@ꢀDI9D86UPSꢀGDBCUTꢀUS68ꢂꢀUC@ꢀPQ@S6UDIBꢀT@RV@I8@ꢁꢀꢀDAꢀUC@ꢀT`TU@HꢀGP8ꢂTꢀ  
PVUꢅꢀUC@ꢀGDBCUTꢀDI9D86U@ꢀUC@ꢀQPDIUꢀDIꢀUC@ꢀT@RV@I8@ꢀPAꢀPQ@S6UDPIꢀXC@S@ꢀ  
GP8ꢂPVUꢀP88VSTꢁꢀꢀDAꢀUCDTꢀU67G@ꢀ9P@TꢀIPUꢀS@69DG`ꢀQSPWD9@ꢀUC@ꢀS@6TPIꢀAPSꢀ  
7PDG@SꢀH6GAVI8UDPIꢀPSꢀIPIꢄPQ@S6UDPIꢅꢀS@A@SꢀUPꢀUC@ꢀAPGGPXDIBꢀQ6B@TꢀAPSꢀ  
HPS@ꢀ9@U6DG@9ꢀUSPV7G@TCPPUDIBꢀQSP8@9VS@Tꢁ  
/,*+7 67$786  
,1',&$7(6  
D78ꢀDTꢀ@I@SBDa@9ꢀUCSPVBCꢀ!#ꢀWPGUꢀUS6ITAPSH@Sꢁ  
D78ꢀDTꢀIPUꢀ@I@SBDa@9ꢁ  
PI  
32:(5  
385*(  
PAA  
7GDIꢂDIB D78ꢀS@8@DW@TꢀHPS@ꢀꢀUC6Iꢀ#ꢃꢀW68  
PI  
D78ꢀDTꢀ@I@SBDaDIBꢀUC@ꢀ9S6AUꢀDI9V8@Sꢀ6I9ꢀ6DSꢀAGPXꢀDTꢀQSPW@Iꢁ  
PAAꢀ9VSDIBꢀQVSB@ꢀ8`8G@ꢄ9S6AUꢀDI9V8@SꢀDTꢀIPUꢀQPX@S@9ꢀPSꢀ6DSꢀAGPX  
DTꢀIPUꢀQSPW@Iꢁ  
PAA  
PAAꢀ9VSDIBꢀDBIDU@Sꢀ6I9ꢀSVIꢀ8`8G@ꢄIPSH6GꢀPQ@S6UDPIꢅꢀQVSB@  
8`8G@ꢀ8PHQG@U@ꢁ  
D78ꢀDTꢀGP8ꢂ@9ꢀPVUꢁꢀꢀQSP7G@Hꢀ8PVG9ꢀDI9D86U@ꢀA6GT@ꢀQPTDUDW@ꢀQSPPA  
PAꢀ6DSꢀAGPXꢁꢀꢀ7GP8ꢂ@9ꢀW@IUꢀPSꢀDIU6ꢂ@ꢀ6DSꢀQDQ@ꢀPSꢀAGV@ꢀX6`ꢁ  
D78ꢀDTꢀ@I@SBDaDIBꢀDBIDU@S  
7GDIꢂDIB  
PI  
PAA  
PI  
,*1,7(5  
9$/9(  
)/$0(  
DBIDU@SꢀDTꢀIPUꢀ@I@SBDa@9  
D78ꢀDTꢀ@I@SBDaDIBꢀB6Tꢀ8PIUSPGꢀW6GW@ꢀUPꢀPQ@Iꢁ  
B6Tꢀ8PIUSPGꢀW6GW@ꢀDTꢀ8GPT@9ꢁ  
PAA  
D78ꢀDTꢀGP8ꢂ@9ꢀPVUꢁꢀꢀQSP7G@HꢀDTꢀAG6H@ꢀC6TꢀIPUꢀ7@@IꢀQSPW@IꢀDI  
7GDIꢂDIB  
UCS@@ꢀꢆ"ꢇꢀDBIDUDPIꢀ6UU@HQUTꢁꢀꢀH6`ꢀ7@ꢀ9V@ꢀUPꢀ7SPꢂ@IꢀDBIDU@SꢀPS  
ꢀG68ꢂꢀPAꢀPSꢀGPXꢀAG6H@ꢀTDBI6GꢅꢀPSꢀIPꢀB6Tꢁ  
PI  
AG6H@ꢀQSPW@I  
PAA  
AG6H@ꢀVIQSPW@I  
TROUBLE SHOOTING  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING CHART 1  
ELE
THE FO
DANGE
TOUC
MUST B
WHAT T
SHOULD
FAIL TO
THE EL
SHUT O
APPLIAN
DO NOT
CONTR
QUALIFI
BOILER
SYSTEM
UNDER
USE ON
KNOBꢀ N
BY HAN
ATTEM
EXPLOS
TROUBLE SHOOTING  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING CHART 2  
TROUBLE SHOOTING  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING CHART 3  
TROUBLE SHOOTING  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING CHART 4  
TROUBLE SHOOTING  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING CHART 5  
TROUBLE SHOOTING  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING CHART 6  
TROUBLE SHOOTING  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The following steps and diagram  
indicate the locations of the  
connection points required to check  
the differential air pressureꢀ  
The differential air pressure switch is  
a safety device which will prevent the  
boiler from firing if there is an air  
intake, boiler heat exchanger or vent  
blockageꢀ  
Turn off service switch, or lower  
thermostat settingꢀ  
Remove vinyl caps from Tee and 4-  
way connectorꢀ  
Install testing lines as shown to  
inclined manometer or differential  
pressure gauge with the ability to  
read 0ꢀ01” to 2ꢀ0” wꢀcꢀ  
Turn on service switch and set  
thermostat to call for heatꢀ  
Boiler Status  
Not Running  
Setpoint  
Differential Pressure (wꢀcꢀ)  
Pressure Switch Connects  
Normally Open  
0”  
1ꢀ00” for Model-100  
1ꢀ35” for Model-75  
1ꢀ55” for Model-50  
Running Without  
Blockage  
Greater Than Setpoints  
Closed  
Open  
Running With  
Blockage  
Less Than or Equal to  
Setpoints  
If manometer readings do not correspond to the chart above, check for possible causes:  
- Blockage or moisture in suction lines  
- Blockage in air intake or vent pipes  
- Undersized air intake or vent pipes  
- Loose blower wheel or motor shaft  
- Inncorect pressure switch or pressure switch setpoint  
When pressure reading is proper and the pressure switch is operating properly, remove testing  
lines and reinstall vinyl caps to Tee and 4-way connectorꢀ  
Cꢀ  
DIFFERENTIAL AIR PRESSURE SWITCH CHECK  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Aꢀ  
JACKET AND BASE ASSEMBLY  
REPAIR PARTS  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
-$&ꢀ(7ꢁ$1'ꢁ%$6(ꢁ$66(0%/<  
'(6&5,37,21  
ꢀꢁ  
ꢀ(<  
,7(0 180%(5  
48$17,7<  
ꢌ$  
ꢌ%  
ꢌ&  
ꢂꢅ  
ꢂꢂ  
ꢂꢆ  
ꢂꢇ  
ꢂꢈ  
ꢂꢄ  
ꢂꢊ  
ꢂꢃ  
ꢂꢋ  
ꢂꢌ  
ꢆꢅ  
ꢆꢂ  
ꢆꢆ  
ꢃꢄꢅꢅꢅꢂꢅꢆꢅ  
ꢃꢄꢅꢅꢅꢂꢅꢆꢂ  
ꢃꢄꢅꢅꢅꢂꢅꢆꢆ  
ꢃꢄꢅꢅꢅꢂꢅꢆꢇ  
ꢃꢄꢅꢅꢅꢂꢅꢆꢈ  
ꢃꢄꢅꢅꢅꢂꢅꢆꢄ  
ꢃꢄꢅꢅꢅꢂꢅꢆꢊ  
ꢂꢈꢊꢊꢆꢋꢅꢂ  
ꢂꢈꢊꢇꢂꢇꢂꢆ  
ꢂꢈꢊꢇꢂꢅꢂꢅ  
ꢂꢈꢊꢇꢂꢅꢈꢈ  
ꢂꢈꢊꢊꢆꢋꢅꢇ  
ꢂꢈꢊꢇꢂꢅꢌꢂ  
ꢂꢈꢊꢇꢂꢂꢆꢅ  
ꢂꢈꢊꢇꢂꢇꢂꢊ  
ꢀ)5217ꢀꢀ3$1(/ꢀ  
ꢀ5,*+7ꢀ3$1(/ꢀ  
ꢀ/()7ꢀ3$1(/ꢀ  
ꢀ%$&ꢉꢀ3$1(/ꢀ  
723ꢀ3$1(/ꢀ  
ꢀ%$6(ꢀ  
ꢀ&21752/ꢀ3$1(/  
ꢀ$7ꢂꢈꢅ%ꢂꢅꢂꢊꢀ75$16)250(5ꢀꢆꢈꢀ9$&  
ꢀ336ꢂꢅꢂꢂꢂꢍꢆꢊꢋꢅꢀ$,5ꢀ35(6685(ꢀ6:,7&+ꢀꢎꢂꢅꢅꢏ  
ꢀ336ꢂꢅꢂꢂꢂꢍꢆꢊꢋꢂꢀ$,5ꢀ35(6685(ꢀ6:,7&+ꢀꢎꢃꢄꢏ  
ꢀ336ꢂꢅꢂꢂꢂꢍꢆꢊꢋꢆꢀ$,5ꢀ35(6685(ꢀ6:,7&+ꢀꢎꢄꢅꢏ  
ꢀ87ꢀꢂꢅꢂꢇꢍꢂꢅꢀ,17(*5$7('ꢀ%2,/(5ꢀ&21752/ꢀ  
ꢀ&2ꢍꢆꢇꢊꢊꢀ*/,'(ꢀ  
ꢀ+(<&2ꢀ2&%ꢍꢂꢄꢅꢅꢀ%86+,1*ꢀ  
ꢀ5$&2ꢀꢆꢇꢆꢀꢈꢈꢆꢀ%2;  
ꢀ3(6ꢀ6:,7&+ꢀꢊꢌꢂꢍ,  
ꢀ&29(5ꢀ3/$7(ꢀꢀ5$&2ꢀꢌꢅꢆꢍꢋꢅꢆ  
ꢀꢈꢂꢌꢍꢂ$$ꢂꢀꢆò´ꢀ3/8*  
ꢀꢈꢂꢄꢍꢂ$$ꢂꢀꢂò´ꢀ3/8*  
ꢀ%3)ꢀꢇꢀò´ꢀ3/8*  
ꢂꢈꢊꢇꢂꢇꢂꢌ  
ꢂꢈꢊꢇꢂꢇꢂꢋ  
ꢂꢈꢊꢇꢂꢂꢃꢈ  
ꢂꢈꢊꢇꢂꢂꢃꢂ  
ꢂꢈꢊꢇꢂꢂꢃꢊ  
ꢂꢈꢊꢇꢂꢂꢃꢄ  
ꢃꢄꢅꢅꢅꢂꢅꢆꢃ  
ꢀꢈꢆꢂꢍꢂ$$ꢂꢀꢇ´ꢀ3/8*  
ꢀ/2:(5ꢀ)5217ꢀ3$1(/ꢀꢍꢀ%/8(  
&,ꢍꢅꢅꢂꢐꢅꢇ  
ꢂꢈꢊꢆꢊꢅꢈꢇ  
&,ꢍꢅꢅꢊꢐꢅꢂ  
ꢂꢈꢊꢆꢊꢅꢈꢇ  
ꢈꢇꢇꢅꢅꢋꢆꢊ  
ꢂꢈꢊꢇꢂꢇꢂꢄ  
ꢃꢄꢅꢅꢅꢂꢅꢅꢆ  
7$&2ꢀ&,5&8/$7,1*ꢀ3803  
7$&2ꢀ,62/$7,21ꢀ9$/9(ꢀ6(7  
*581')26ꢀ&,5&8/$7,1*ꢀ3803  
*581')26ꢀ,62/$7,21ꢀ9$/9(ꢀ6(7  
ꢀ&,5&8/$7,1*ꢀ3803ꢀ+$51(66  
ꢀ:,5,1*ꢀ+$51(66  
Á
Á
Á
Á
Á
Á
ꢀ-$&ꢉ(7ꢀ&203/(7(  
REPAIR PARTS  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Bꢀ  
CONDENSATE DRAIN TRAP ASSEMBLY  
&21'(16$7(ꢁ'5$,1ꢁ75$3ꢁ$66(0%/<  
ꢀꢁ  
ꢀ(<  
,7(0 180%(5  
'(6&5,37,21  
48$17,7<  
ꢂꢃꢄꢅꢂꢆꢅꢇ  
ꢀꢇꢈꢆꢂꢈꢀꢀò´,'[ꢂꢉꢊ´ꢀ7+ꢋꢀ9,1</ꢀ78%,1*  
$6ꢀ5(48,5('  
ꢌꢂꢃꢄꢅꢂꢂꢃꢂ  
ꢀꢇꢍꢂꢅꢃꢀꢀô´ꢀ61$3ꢀ*5,3ꢀ&/$03  
ꢂꢃꢄꢅꢂꢅꢌꢆ  
ꢂꢃꢄꢅꢂꢂꢆꢂ  
ꢂꢃꢄꢅꢂꢅꢌꢂ  
ꢂꢃꢄꢅꢂꢅꢆꢄ  
ꢂꢃꢄꢅꢂꢆꢌꢆ  
ꢂꢃꢄꢅꢂꢅꢌꢅ  
ꢀꢄꢌꢆꢄꢍꢀꢀò´,'ꢀ+26(ꢀ7((  
ꢀꢄꢌꢆꢂꢍꢀꢀò´137[ꢀò´,'ꢀ78%(ꢀ675$,*+7  
ꢀò´ꢀ39&ꢀ&283/,1*ꢎꢀ6&+ꢀꢊꢆ  
ꢀò´ꢃ´ꢀ39&ꢀ1,33/(ꢎꢀ6&+ꢀꢊꢆ  
ꢀò´,'ꢀò´,'ꢀò´13778%(ꢀ7((  
ꢀ6ꢏꢀ6ꢏꢀ&/$03ꢎꢀ6,=(ꢀꢂꢄꢀꢐꢂꢅꢉꢂꢄ´aꢂꢀò´ꢑ  
REPAIR PARTS  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPAIR PARTS  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
%2,/(5ꢁ%/2&ꢀꢁ$1'ꢁ3,3,1*ꢁ$66(0%/<  
'(6&5,37,21  
+2))0$1ꢅ9(17ꢅꢆꢇꢇ  
ôꢋꢅ[ꢀꢌꢍꢋꢅ%86+,1*  
ôꢋꢅ%/$&!ꢅ7((  
ôꢋꢅ[ꢉꢊžꢅ675((7ꢅ(/%2:  
ôꢋꢅ[ꢂòꢋꢅ1,33/(  
ôꢋꢅ$60(ꢅ5(/,()ꢅ9$/9(  
ôꢋ[ꢅꢈꢋꢅ1,33/(  
óꢋꢎꢈꢊꢅ+(;ꢅ187ꢅ:ꢌ6(55$7('ꢅ:$6+(5ꢅ+($'  
ꢍꢎꢃꢈꢅ[ꢅꢃꢌꢀꢂꢋꢅ62&ꢅ+'ꢅ&$3ꢅ6&5(:  
ꢃꢂ7ꢈꢂꢎꢁꢈꢉꢃꢊꢅ&$67,1*ꢅ7(03ꢏꢅ6$)(7<ꢅ6:,7&+  
óꢋꢎꢈꢊꢅ[ꢅꢀòꢋꢅ62&ꢅ+'ꢅ&$3ꢅ6&5(:  
óꢋꢎꢈꢊꢅ[ꢅꢀóꢋꢅ678'ꢅ7+5($'('  
7(67('ꢅ%/2&!ꢅꢐ,1&/8'(6ꢅꢍꢑꢀꢀꢑꢀꢁꢅ$1'ꢅꢈꢊꢑꢈꢈꢒ  
óꢋꢅ[ꢀóꢋꢅ&$55,$*(ꢅ%2/7  
ꢂꢈꢊꢀꢇꢅòꢋꢅ137ꢅ[ꢅòꢋꢅ,'ꢅ78%(ꢅ675$,*+7  
ꢀóꢋꢅ[ꢅꢈòꢋꢅ1,33/(ꢅ%/$&!  
ꢀóꢋꢅ[ꢅôꢋꢅ[ꢅꢀóꢋꢅ7((  
ꢀ(<ꢁꢂ  
,7(0ꢁ180%(5  
ꢀꢁꢂꢃꢀꢀꢄꢂ  
ꢀꢁꢂꢉꢃꢊꢊꢀ  
ꢀꢁꢂꢉꢃꢊꢇꢂ  
ꢀꢁꢂꢉꢃꢊꢁꢊ  
ꢀꢁꢂꢊꢇꢊꢊꢈ  
ꢀꢁꢂꢈꢈꢊꢀꢀ  
ꢀꢁꢂꢊꢇꢈꢊꢀ  
ꢀꢁꢂꢉꢄꢍꢀꢊ  
ꢀꢁꢂꢉꢄꢍꢊꢈ  
ꢀꢁꢂꢃꢀꢊꢊꢊ  
ꢀꢁꢂꢉꢄꢍꢊꢀ  
ꢀꢁꢂꢉꢄꢍꢊꢄ  
ꢁꢀꢍꢊꢊꢉꢀꢊ  
ꢀꢁꢂꢉꢄꢊꢁꢊ  
ꢀꢁꢂꢃꢀꢀꢊꢀ  
ꢀꢁꢂꢊꢇꢊꢁꢁ  
ꢀꢄꢀꢊꢊꢊꢀ  
48$17,7<  
ꢀꢈ  
ꢀꢊ  
ꢀꢀ  
ꢀꢈ  
ꢀꢃ  
ꢀꢁ  
ꢀꢄ  
ꢀꢂ  
ꢀꢇ  
ꢀꢍ  
ꢀꢉ  
ꢈꢊ  
ꢈꢀ  
ꢈꢈ  
ꢈꢃ  
ꢈꢁ  
ꢈꢄ  
ꢈꢂ  
ꢈꢇ  
ꢈꢍ  
ꢀꢁꢂꢈꢈꢊꢊꢊ  
ꢀꢁꢂꢉꢃꢊꢄꢂ  
ꢀꢁꢂꢀꢉꢊꢊꢈ  
ꢀꢁꢂꢉꢃꢊꢄꢍ  
ꢀꢁꢂꢉꢃꢊꢊꢁ  
ꢀꢁꢂꢂꢈꢍꢊꢁ  
ꢀꢁꢂꢃꢀꢃꢈꢁ  
ꢀꢁꢂꢉꢃꢊꢊꢀ  
ꢀꢈꢂꢊꢊꢊꢂ  
ôꢋꢅ'5$,1ꢅ9$/9(  
ꢀꢋꢅ64ꢅ62&!(7ꢅ3/8*  
(03,5(ꢅ6,*+7ꢅ*/$66  
ôꢋꢅ64ꢅ+'ꢅ3/8*  
ôꢋꢅ[òꢋꢅ%86+,1*  
ꢀꢈꢃꢍꢂꢉ$ꢅ&21752/ꢅ:(//ꢅòꢋꢅ137  
/ꢁꢊꢊꢂ$ꢅꢈꢀꢄꢄ%ꢅ+,ꢅ/,0,7ꢅ$48$67$7  
ôꢋꢅ[ꢀꢌꢍꢋꢅ%86+,1*  
7(03ꢅ1ꢅ35(6685(ꢅ*$8*(  
6,*+7ꢅ*/$66ꢅ$'$37(5  
ꢀꢁꢂꢃꢀꢊꢊꢁ  
ꢀꢁꢂꢃꢀꢊꢊꢄ  
ꢀꢌꢍꢋꢅ137ꢅóꢋꢅ+26(ꢅ,'ꢅ%5$66ꢅ%$5%ꢅ),77,1*  
REPAIR PARTS  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dꢀ  
MIXER AND AIR PRESSURE SWITCH ASSEMBLY  
REPAIR PARTS  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
0,;(5ꢁ$1'ꢁ$,5ꢁ35(6685(ꢁ6:,7&+ꢁ$66(0%/<  
'(6&5,37,21  
ꢀ%851(5ꢀ*$6ꢈ(7ꢀ  
ꢀꢂꢆꢆꢀ%851(5ꢀꢉ%6,ꢊ  
ꢀꢋꢌꢀ%851(5ꢀꢉ%6,ꢊ  
ꢀꢌꢆꢀ%851(5ꢀꢉ%6,ꢊ  
ꢀ0,;(5ꢀ*$6ꢈ(7ꢀ  
ꢀó´ꢏꢇꢆꢀ+(;ꢀ187ꢀ:ꢐ6(55$7('ꢀ:$6+(5ꢀ+($'  
ꢀ0,;(5ꢀ&$67,1*ꢀ0$&+,1('  
ꢀꢇ´ꢂò´ꢀ)/(;,%/(ꢀ&283/,1*  
ꢀꢂꢆꢆꢀ$,5ꢀ%$))/(  
ꢀꢋꢌꢀ$,5ꢀ%$))/(  
ꢀꢌꢆꢀ$,5ꢀ%$))/(  
ꢀ$,5ꢀ,1/(7  
ꢀꢇ´ꢀ)(51&2ꢀ&283/,1*  
ꢀꢂꢆꢏꢅꢇ´[ꢅꢐꢍ´ꢀ0$&+,1(ꢀ6&5(:ꢀ  
ꢀ+27ꢀ685)$&(ꢀ,*1,7(5ꢀꢉ)25ꢀꢌꢆꢐꢋꢌꢊ  
ꢀ+27ꢀ685)$&(ꢀ,*1,7(5ꢀꢉ)25ꢀꢂꢆꢆꢊ  
ꢀ+27ꢀ685)$&(ꢀ,*1,7(5ꢀ*$6ꢈ(7ꢀ  
ꢀ0,;(5ꢀ%86+,1*  
ꢀ(<ꢀꢁ  
ꢇ$  
ꢇ%  
ꢇ&  
ꢋ$  
ꢋ%  
ꢋ&  
ꢂꢆ  
ꢂꢂ$  
ꢂꢂ%  
ꢂꢇ  
ꢂꢅ  
ꢂꢃ  
ꢂꢌ  
ꢂꢄ  
ꢂꢋ  
ꢂꢍ  
ꢂꢎ  
ꢇꢆ  
ꢇꢂ  
ꢇꢇ  
ꢇꢅ  
ꢇꢃ  
,7(0180%(5  
ꢂꢃꢄꢅꢂꢆꢇꢅ  
ꢂꢃꢄꢅꢂꢆꢆꢄ  
ꢂꢃꢄꢅꢂꢆꢆꢋ  
ꢂꢃꢄꢅꢂꢆꢆꢍ  
ꢂꢃꢄꢅꢂꢆꢇꢌ  
ꢂꢃꢄꢎꢌꢍꢂꢆ  
ꢂꢇꢂꢆꢂꢆꢆꢍ  
ꢂꢃꢄꢅꢂꢅꢂꢂ  
ꢃꢇꢌꢅꢂꢂꢆꢆ  
ꢃꢇꢌꢅꢂꢂꢆꢂ  
ꢃꢇꢌꢅꢂꢂꢆꢇ  
ꢃꢇꢌꢅꢂꢂꢆꢅ  
ꢂꢃꢄꢅꢂꢆꢂꢌ  
ꢂꢃꢄꢎꢌꢍꢆꢎ  
ꢃꢅꢍꢆꢆꢆꢂꢅ  
ꢃꢅꢍꢆꢆꢆꢂꢃ  
ꢂꢃꢄꢅꢂꢆꢇꢃ  
ꢂꢃꢄꢅꢂꢅꢆꢎ  
ꢂꢃꢄꢆꢋꢅꢆꢂ  
ꢂꢃꢄꢎꢅꢍꢆꢌ  
ꢂꢃꢄꢅꢂꢅꢆꢋ  
ꢂꢃꢄꢅꢂꢅꢆꢍ  
ꢂꢃꢄꢅꢂꢂꢆꢃ  
ꢂꢃꢄꢅꢂꢅꢂꢅ  
ꢂꢃꢄꢅꢂꢂꢃꢅ  
ꢂꢃꢄꢅꢂꢂꢌꢂ  
ꢂꢃꢄꢅꢂꢆꢅꢅ  
ꢂꢃꢄꢅꢂꢅꢂꢃ  
ꢂꢃꢄꢇꢎꢆꢆꢅ  
ꢂꢃꢄꢅꢂꢅꢂꢇ  
ꢂꢃꢄꢅꢂꢆꢂꢆ  
ꢂꢃꢄꢅꢂꢆꢃꢃ  
ꢂꢃꢄꢅꢂꢂꢆꢅ  
ꢂꢃꢄꢅꢂꢅꢂꢆ  
ꢂꢃꢄꢅꢂꢆꢇꢎ  
ꢂꢃꢄꢅꢂꢆꢅꢆ  
ꢂꢃꢄꢅꢂꢆꢅꢇ  
ꢂꢃꢄꢅꢂꢆꢅꢄ  
ꢂꢃꢄꢅꢂꢆꢅꢋ  
48$17,7<  
ꢀò´ꢀꢅ´ꢀ67'ꢀ%/$&ꢈꢀ1,33/(  
ꢀꢂꢐꢍ¶¶ꢀ137ꢀ%5$66ꢀ3/8*ꢀ±ꢀꢅꢐꢂꢄ¶¶ꢀ+(;ꢀ62&ꢈ(7  
ꢀ+21(<:(//ꢀ*$6ꢀ9$/9(ꢀ95ꢍꢇꢆꢌ  
ꢀꢌꢐꢂꢄꢏꢇꢃꢂꢐꢃꢀ+26(ꢀ,'ꢀ%5$66ꢀ%$5%ꢀ),77,1*  
ꢀꢄꢇꢆꢄꢃꢀꢀó´,'ꢀ78%(ꢀ7((  
ꢀó´,'ꢀ78%(ꢀꢀꢃꢏ:$<ꢀ&211(&725  
ꢀꢅꢐꢍ´ꢀ+26(ꢀ&/$03ꢀ+&ꢏꢄ67  
ꢂꢆ  
ꢀ3&ꢇꢌꢆꢏꢂꢇ9,1</ꢀ&$3  
ꢀꢌꢎꢆꢆꢄꢀó´,'[ꢅꢐꢍ´2'ꢀ9,1</ꢀ78%,1*  
ꢀꢂꢐꢃ¶¶,'ꢅꢐꢍ´2'ꢀ9,1</ꢀ78%,1*ꢀꢉ5('ꢊ  
ꢀꢂꢐꢃ´ꢀ,'ꢀ6,/,&21(ꢀ78%,1*  
$6ꢀ5(48,5('  
$6ꢀ5(48,5('  
$6ꢀ5(48,5('  
ꢇꢌ$  
ꢇꢌ%  
ꢇꢌ&  
ꢇꢄ  
ꢇꢋ$  
ꢇꢋ%  
ꢇꢋ&  
ꢇꢋ'  
ꢇꢋ(  
ꢇꢋ)  
ꢀ336ꢂꢆꢂꢂꢂꢏꢇꢄꢍꢆꢀ$,5ꢀ35(6685(ꢀ6:,7&+ꢀꢉꢂꢆꢆꢊ  
ꢀ336ꢂꢆꢂꢂꢂꢏꢇꢄꢍꢂꢀ$,5ꢀ35(6685(ꢀ6:,7&+ꢀꢉꢋꢌꢊ  
ꢀ336ꢂꢆꢂꢂꢂꢏꢇꢄꢍꢇꢀ$,5ꢀ35(6685(ꢀ6:,7&+ꢀꢉꢌꢆꢊ  
ꢀꢄꢇꢆꢃꢅꢀò¶¶ꢀ137ꢂꢐꢇ´,'ꢀ78%(ꢀ(/%2:  
ꢀ*$6ꢀ25,),&(ꢀ±ꢀ1$785$/ꢑꢀꢂꢆꢆ1ꢀꢉꢆꢒꢆꢍꢄꢆꢑꢀꢁꢃꢃꢊ  
ꢀ*$6ꢀ25,),&(ꢀ±ꢀ1$785$/ꢑꢀꢋꢌ1ꢀꢉꢆꢒꢆꢋꢄꢆꢑꢀꢁꢃꢍꢊ  
ꢀ*$6ꢀ25,),&(ꢀ±ꢀ1$785$/ꢑꢀꢌꢆ1ꢀꢉꢆꢒꢆꢄꢂꢌꢊ  
ꢀ*$6ꢀ25,),&(ꢀꢏꢀ3523$1(ꢑꢀꢂꢆꢆ3ꢀꢉꢆꢒꢆꢄꢋꢆꢑꢀꢁꢌꢂꢊ  
ꢀ*$6ꢀ25,),&(ꢀ±ꢀ3523$1(ꢑꢀꢋꢌ3ꢀꢉꢆꢒꢆꢄꢆꢌꢊ  
ꢀ*$6ꢀ25,),&(ꢀ±ꢀ3523$1(ꢑꢀꢌꢆ3ꢀꢉꢆꢒꢆꢃꢎꢇꢊ  
REPAIR PARTS  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Eꢀ  
FLUE ADAPTER AND EXHAUST ASSEMBLY  
)/8(ꢁ$'$37(5ꢁ$1'ꢁ(;+$867(5ꢁ$66(0%/<  
ꢀ(<ꢀꢁ ,7(0180%(5  
'(6&5,37,21  
(;+$867ꢀ7((ꢀ$66(0%/<ꢀꢇꢀꢂꢇ$ꢈ%ꢈ&ꢈ'ꢈ(ꢀꢉꢀ)  
ꢋꢄꢅꢂꢍꢀꢂꢎꢄ´137[ꢂꢎꢄ´,'ꢀ78%(ꢀ675$,*+7  
39&ꢀꢂꢀꢂꢎꢄ´ꢀ0$/(ꢀ6/,3ꢀ[ꢀꢂꢎꢄ´ꢀ)(0$/(ꢀ137  
39&ꢀ6&+ꢀꢊꢅꢀꢄ´[ꢂꢇꢂꢎꢄ´ꢀ5('8&(5  
ꢌꢎꢊ¶¶ꢀ$/80,180ꢀ)/$7ꢀ:$6+(5  
ꢄ´ꢀ&39&ꢀꢀ7((ꢈꢀ6&+ꢀꢃꢅ  
ꢄ´ꢀ&39&ꢀ3,3(ꢄꢇꢂꢎꢄ¶¶ꢈꢀ6&+ꢀꢊꢅ  
9(17ꢀ6:,7&+ꢀ*$6*(7  
ꢌꢋ7;ꢂꢂꢇꢄꢄꢊꢆꢂꢀ,1'8&(5ꢀ7(03ꢀ6$)(7<ꢀ6:,7&+  
ꢁꢊꢇꢄꢅ[ꢂꢎꢊ´ꢀ+:+ꢀ3/$67ꢀ)250ꢀ6&5(:  
ꢂꢂꢋꢏꢂꢋꢇꢂꢂꢀ,1'8&('ꢀ'5$)7ꢀ%/2:(5  
%/2:(5ꢀ*$6*(7  
48$17,7<  
ꢂ$  
ꢂ%  
ꢂ&  
ꢂ'  
ꢂ(  
ꢂ)  
ꢂꢃꢄꢅꢅꢆꢅꢅꢄ  
ꢂꢊꢋꢌꢂꢂꢅꢂ  
ꢂꢊꢋꢌꢂꢅꢂꢌ  
ꢂꢊꢋꢌꢂꢅꢂꢊ  
ꢂꢊꢋꢆꢏꢃꢂꢏ  
ꢂꢊꢋꢌꢂꢌꢅꢏ  
ꢂꢊꢋꢌꢂꢌꢅꢊ  
ꢂꢊꢋꢌꢂꢅꢄꢃ  
ꢂꢊꢋꢌꢂꢌꢅꢌ  
ꢂꢊꢋꢆꢏꢃꢅꢃ  
ꢂꢊꢋꢌꢂꢅꢍꢍ  
ꢂꢊꢋꢌꢂꢅꢄꢋ  
ꢂꢄꢂꢅꢂꢅꢄꢂ  
ꢂꢊꢋꢌꢂꢅꢄꢍ  
ꢂꢊꢋꢆꢏꢃꢂꢅ  
ꢂꢊꢋꢆꢌꢃꢅꢊ  
ꢂꢊꢋꢌꢂꢂꢅꢌ  
ꢂꢊꢋꢌꢂꢂꢊꢂ  
ꢂꢊꢋꢌꢂꢅꢌꢏ  
ꢂꢊꢋꢌꢂꢌꢅꢂ  
ꢂꢊꢋꢌꢂꢌꢅꢄ  
ꢂꢊꢋꢌꢂꢂꢏꢂ  
ꢂꢊꢋꢌꢂꢂꢊꢌ  
)/8(ꢀ&211(&725  
5(&29(5<ꢀ&2,/ꢀ*$6*(7  
ꢂꢎꢊ´ꢇꢄꢅꢀ+(;ꢀ187ꢀ:ꢎ6(55$7('ꢀ:$6+(5ꢀ%/2&*  
ꢂꢎꢃ,ꢀ137ꢀꢂꢎꢊ,ꢀ+26(ꢀ,'ꢀ%5$66ꢀ%$5%ꢀ),77,1*  
ꢋꢄꢅꢊꢌꢀꢂꢎꢄ¶¶ꢀ137ꢂꢎꢄ¶¶ꢀ,'ꢀ78%(ꢀ(/%2:  
ꢏꢍꢂꢌꢊꢀꢌꢎꢊ¶¶ꢀ61$3ꢀ*5,3ꢀ&/$03  
ꢏꢆꢅꢂꢆꢀò¶¶ꢀ,'ꢂꢎꢃꢀ7+*ꢀ9,1</ꢀ78%(  
+26(ꢈꢀꢌ´ꢀ/21*ꢀꢀꢄꢇꢌꢎꢃ´ꢀ,'ꢀ;ꢀꢄꢇꢌꢎꢊ´ꢀ2'  
6ꢐꢀ6ꢐꢀ&/$03ꢈꢀ6,=(ꢀꢊꢊ  
ꢂꢅ  
ꢂꢂ  
ꢂꢄ  
ꢂꢌ  
ꢂꢊ  
ꢂꢏ  
ꢂꢋ  
ꢂꢍ  
$6ꢀ5(48,5('  
3&ꢄꢏꢅꢇꢂꢄꢀ9,1</ꢀ&$3  
ꢌꢎꢃ,ꢀ+26(ꢀ&/$03ꢀ+&ꢇꢋ67  
REPAIR PARTS  
14683301  
66  
Rev, 3, August 2003  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Pyramid Technologies Power Supply PS 3KX User Guide
Raymarine GPS Receiver RS12 User Guide
RCA MP3 Player M3804 User Guide
RCA Portable CD Player RCD025 User Guide
Revolabs Wireless Office Headset 500 PBX User Guide
Samsung Cell Phone 9330 User Guide
Samsung Computer Hardware SSC 12P User Guide
Samsung Computer Monitor 181T User Guide
Samsung Portable Media Storage GT B9150 User Guide
Savin All in One Printer 9940DP User Guide