Powerware Power Supply 208 120V User Manual

Powerware® Energy Management System (EMS)  
Upgrade Kit (208/120V, 380/220V, 400/230V, 415/240V)  
User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Special Symbols  
The following are examples of symbols used on the UPS or accessories to alert you to important  
information:  
RISK OF ELECTRIC SHOCK − Observe the warning associated with the risk of electric shock  
symbol.  
CAUTION: REFER TO OPERATOR’S MANUAL − Refer to your operator’s manual for additional  
information, such as important operating and maintenance instructions.  
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in  
the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.  
Three−phase alternating current  
PROTECTIVE CONDUCTOR TERMINAL  
Do not apply around or remove from hazardous live conductors.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
1
2
3
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
4
5
6
7
8
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1  
Introduction  
®
Eaton’s Powerware Energy Management System (EMS) Upgrade Kit  
(EMS−UGK) is designed to monitor energy usage of existing power  
distribution panelboards, remote power panels, or power distribution  
units. Providing outstanding performance and reliability, the EMS−UGK’s  
unique benefits include the following:  
S Monitors up to 42 (single panel) or 84 (dual panel) circuits in a  
standard three−phase panelboard. Measures and stores energy  
parameters for each of the individual monitored circuits, letting you  
manage power with greater precision.  
S Functions in a wide variety of applications supporting various data  
center loads that may require a power distribution monitoring  
solution, especially where power needs are changing and backup  
architecture must be scalable.  
S Can be mounted on a wall with the included mounting bracket and  
customer−supplied fasteners appropriate for the type of wall.  
S Choice of voltage sensing installation: connection to an unoccupied  
circuit breaker using included transition harnesses or connection to an  
occupied circuit breaker using included wire taps.  
S Includes a software tool for easy configuring of settings and options.  
S All harnesses supplied except for optional external ground.  
S No preventive maintenance required other than verifying the  
hardware and wiring are clear of debris. The EMS−UGK does not  
require an annual calibration.  
S Advanced Metering monitoring system, providing communication  
®
options such as network connectivity through the Power Xpert  
®
Gateway Card installed in the X−Slot communication bay.  
S Intended for continuous duty operation.  
S Backed by worldwide agency approvals.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INTRODUCTION  
The following options for the EMS−UGK are available:  
S Single panel (42 circuits) or dual panel (84 circuits)  
S 208/120V or 380/220V, 400/230V, 415/240V rating  
S Liquid crystal display (LCD) for local indication of energy usage  
S Conduit box for enhanced harness protection  
S Main input monitoring (three phases and one neutral rated to  
measure currents up to 400A; up to 100A for input ground)  
The following accessories for the EMS−UGK are available:  
S Subfeed breaker monitoring, rated to measure currents up to 400A  
S 100A branch circuit breaker monitoring  
S Temperature and humidity monitoring with the optional  
Environmental Monitoring Probe (EMP) that is used with the  
Power Xpert Gateway Series 1000 Card installed in the EMS−UGK  
The EMS−UGK includes an externally−mounted enclosure with an  
optional display. Current transformers (CTs) provide branch circuit  
installation of an EMS−UGK.  
Figure 1. Typical EMS−UGK Installation (Dual Panel Shown with Optional Display)  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INTRODUCTION  
Safety Warnings  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS  
This manual contains important instructions that you should follow during installation and  
operation of the EMS−UGK. Please read all instructions before operating the equipment and  
save this manual for future reference.  
DANGER  
This EMS−UGK contains LETHAL VOLTAGES. All repairs and service should be performed  
by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE  
PARTS inside the EMS−UGK.  
CAUTION  
S
To reduce the risk of fire or electric shock, install this EMS−UGK in a temperature and  
humidity controlled, indoor environment, free of conductive contaminants. Ambient  
temperature must not exceed 40°C (104°F). Do not operate near water or excessive  
humidity (95% maximum).  
S
S
Use the branch circuit breakers to disconnect hazardous voltage from the EMS−UGK. Turn  
off the breaker before disconnecting the voltage measuring circuit cables, or hazardous  
voltage may be present at the exposed end of the cable.  
Installation or use of the equipment in a manner not specified by the manufacturer may  
impair the protection provided by the equipment.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INTRODUCTION  
Consignes de sécurité  
CONSIGNES DE SÉCURITÉ IMPORTANTES  
CONSERVER CES INSTRUCTIONS  
Ce manuel contient des instructions importantes que vous êtes invité à suivre lors de toute  
procédure d’installation et de fonctionnement de EMS−UGK. Veuillez consulter entièrement  
ces instructions avant de faire fonctionner l’équipement et conserver ce manuel afin de  
pouvoir vous y reporter ultérieurement.  
DANGER!  
Cet EMS−UGK contient des TENSIONS MORTELLES. Toute opération d’entretien et de  
réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ.  
AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans la EMS−UGK.  
ATTENTION!  
S
Pour réduire les risques d’incendie et de décharge électrique, installer la EMS−UGK  
uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la  
température et l’humidité ambiantes sont contrôlées. La température ambiante ne doit  
pas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphère  
excessivement humide (95 % maximum).  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION  
Sicherheitswarnungen  
WICHTIGE SICHERHEITSANWEISUNGEN  
AUFBEWAREN  
Dieses Handbuch enthält wichtige Hinweise, welche Sie bei der Installation und Wartung  
des EMS−UGK beachten sollten. Bitte lesen Sie alle Anweisungen des Handbuches bevor sie  
mit dem Gerät arbeiten. Bewaren Sie das Handbuch zum Nachlesen auf.  
WARNUNG  
Die EMS−UGK führt lebensgefährliche Spannungen. Alle Reparatur− und Wartungsarbeiten  
sollten nur von Kundendienstfachleuten durchgeführt werden. Die EMS−UGK enthält keine  
vom Benutzer zu wartenden Komponenten.  
ACHTUNG  
S
Um die Brand- oder Elektroschockgefahr zu verringern, diese EMS−UGK nur in Gebäuden  
mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden  
Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C nicht übersteigen.  
Die EMS−UGK nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max.  
95 %) betreiben.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION  
Advertencias de Seguridad  
INSTRUCCIONES DE SEGURIDAD IMPORTANTES  
GUARDE ESTAS INSTRUCCIONES  
Este manual contiene instrucciones importantes que debe seguir durante la instalación y el  
funcionamiento de la EMS−UGK. Por favor, lea todas las instrucciones antes de poner en  
funcionamiento el equipo y guarde este manual para referencia en el futuro.  
PELIGRO  
Este EMS−UGK contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico  
deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO.  
No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro de la EMS−UGK.  
PRECAUCIÓN  
S
Para reducir el riesgo de incendio o de choque eléctrico, instale este EMS−UGK en un  
lugar cubierto, con temperatura y humedad controladas, libre de contaminantes  
conductores. La temperatura ambiente no debe exceder los 40°C. No trabaje cerca del  
agua o con humedad excesiva (95% máximo).  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2  
Installation  
This section explains:  
S Equipment inspection  
S Unpacking  
S Parts list  
S Required tools  
S Installation and wiring  
S Initial configuration  
S Advanced Metering installation  
Inspecting the Equipment  
If any equipment has been damaged during shipment, keep the shipping  
cartons and packing materials for the carrier or place of purchase and file  
a claim for shipping damage. If you discover damage after acceptance,  
file a claim for concealed damage.  
To file a claim for shipping damage or concealed damage: 1) File with  
the carrier within 15 days of receipt of the equipment; 2) Send a copy of  
the damage claim within 15 days to your service representative.  
Unpacking the Cabinet  
Use care when moving and opening the carton. Leave the components  
packaged until ready to install.  
To unpack the cabinet:  
1. Open the outer carton and remove the items packaged with the  
cabinet.  
2. Carefully lift the cabinet out of the outer carton.  
3. Discard or recycle the packaging in a responsible manner, or store it  
for future use.  
Place the cabinet in a protected area that has adequate airflow and is  
free of humidity, flammable gas, and corrosion.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Checking the Parts List  
Verify that the following items are included with the EMS−UGK.  
All models  
Electronics module (display optional)  
Mounting bracket (installed on electronics module)  
EMS Configuration Tool CD for setup and calibration  
EMS configuration cable (DB−9 to RS−232 serial)  
This user’s guide  
Power Xpert Gateway Series 1000 Card (installed on electronics module)  
Card configuration cable (RJ−45 to RS−232 serial)  
Ethernet cable  
Power Xpert Gateway Series 1000 Card registration card  
Power Xpert Gateway Series 1000 Card Quick Start Instructions  
NOTE For more detailed information, download the Power Xpert Gateway Series 1000  
Card User’s Guide from the Documentation page on the Power Xpert card once the card  
All models (for each panel ordered)  
(2) Branch circuit harnesses, each with one 28−position circular connector and  
21 two−position connector plugs  
(44) Branch current transformers (CTs), split−core, 75A, 1V output, with two−position  
connector receptacle (includes 2 spares) (optional)  
(1) Voltage harness, with one 7−position circular connector, three spade connectors  
(A, B, C), and two ferrule connectors (Neutral, Ground)  
NOTE Dual panel option only. Voltage harness V2 does NOT include a connector for  
Ground.  
(10) Wire taps:  
2
− (5) 4.0 mm (12 AWG), yellow  
2
− (5) 0.75–2.5 mm (18–14 AWG), blue  
(3) Wire tap transition harnesses, each with a quick disconnect receptacle and a ferrule  
connector  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Main input monitoring option only (one set for each panel if ordered)  
(1) Main input harness, with one 28−position circular connector and five 2−position  
connector plugs (A, B, C, Ground, Neutral)  
(4) Main CTs, split−core, 400A, 1V output, with 2−position connector receptacle  
(1) Input ground CT, split−core, 100A, 1V output, with 2−position connector receptacle  
Conduit box option only (if ordered)  
Conduit box, left side  
Conduit box, right side, with installed DB−9 extender cable  
Subfeed Accessory Kit only (if ordered)  
(3) Subfeed transition harnesses, each with 2 two−position connector plugs  
(3) Branch CTs, split−core, 400A, 1V output, with two−position connector receptacle  
100A Split−Core CTs Accessory Kit only (if ordered)  
(10) Branch CTs, split−core, 100A, 1V output, with two−position connector receptacle  
75A Split−Core CTs Accessory Kit only (if ordered)  
(5) Branch CTs, split−core, 75A, 1V output, with two−position connector receptacle  
NOTE Accessory kits may be shipped in separate cartons.  
Tools Required  
To assemble the components, the following tools may be needed:  
®
S Phillips #2 screwdriver  
S Pliers or other appropriate tool for installing wire taps  
S Drill or other appropriate tool for installing customer−supplied wall  
anchors  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Installing the Hardware  
an appropriate site for the EMS−UGK.  
To install the EMS−UGK on a wall:  
1. Verify that the wall on which the EMS−UGK is to be mounted meets  
Table 1. Wall Specifications (Customer−Supplied Components)  
Component  
Specification  
Wall surface and  
wall anchors  
Sufficient to support the weight of the EMS−UGK and installed  
cables (see Table 12 on page 57 for weight specifications)  
Clearance around  
electronics module  
Above: 102 mm (4") [152 mm (6") recommended]  
Below: 102 mm (4")  
Sides: 152 mm (6")  
2. Loosen the four front screws, and remove the four rear screws.  
Remove the mounting bracket from the electronics module. Retain  
M4 10 screws  
(8 places)  
Figure 2. Mounting Bracket and Electronics Module (with Optional Display)  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
3. Attach the mounting bracket to the wall with appropriate wall  
Verify that at least two wall anchors attach to studs within the wall.  
376.5 mm  
(14.82")  
152.4 mm  
(6.00")  
152.4 mm  
(6.00")  
16.8 mm  
(0.66")  
12.7 mm  
(0.50") TYP  
5.3 mm  
(0.21") TYP  
226.0 mm 283.5 mm  
(8.90")  
(11.16")  
Figure 3. Mounting Template  
4. Slide the loosened front screws on the electronics module into the  
slots on the mounting bracket.  
5. Verify all screw holes are aligned. Reinstall the four screws  
7. Remove the front plate from each conduit box. Retain the plates  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
8. If installing a right conduit box, connect the DB−9 extender cable  
(installed on the extended serial port on the inside of the right  
conduit box) to the serial port (Service) on the electronics module.  
9. Slide the conduit box into place on one side of the electronics  
module. Loosen the mounting bracket screws further if needed.  
If installing conduit on both panels, repeat for the other conduit box.  
Tighten the mounting bracket screws to secure the conduit box(es).  
Serial Port  
(Service)  
Extended  
Serial Port  
Front  
Plate  
2" Bushing  
Front  
Plate  
Left Conduit  
Box  
Card Cover Plate  
1.5" Bushing  
Mounting  
Slots  
(4 places)  
1" Bushing  
Mounting Bracket  
Screws (8 places)  
Right Conduit Box  
Ground Bonding Screw  
Figure 4. Conduit Box Option  
10. Optional but recommended. Attach the conduit box(es) to the wall  
with appropriate wall anchors (not supplied). Use one or more of  
the four available mounting slots in each conduit box.  
11. Verify that all hardware is mounted and aligned properly, then  
tighten all screws. Verify the hardware is attached safely and  
securely to the wall.  
12. Continue to the following section, ꢀElectrical Connections."  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Electrical Connections  
WARNING  
S
S
Only qualified service personnel (such as a licensed electrician) shall perform the  
electrical installation. Risk of electrical shock.  
Always follow all personal protective equipment (PPE) and other safety rules when  
working around electricity.  
CAUTION  
S
S
Use the branch circuit breakers to disconnect hazardous voltage from the EMS−UGK. Turn  
off the breaker before disconnecting the voltage measuring circuit cables, or hazardous  
voltage may be present at the exposed end of the cable.  
To prevent mechanical damage, coil and secure any excess cable away from the floor.  
The EMS−UGK is designed for quick and easy installation. Labels on the  
harnesses describe where to connect the CTs and wire taps. Keyed  
circular connectors provide a quick and secure installation to the  
electronics module.  
To connect the wiring for the EMS−UGK:  
CAUTION  
Before wiring the EMS−UGK, disconnect the load and shut down the host equipment. Refer  
to the user’s guide for the host equipment for shutdown instructions.  
1. Verify that no circuits on which the EMS−UGK will be installed are  
energized. Be absolutely sure there is no power.  
2. Optional. Connect the ground cable (not supplied) from the host  
equipment to the M5 ground bonding screw on the bottom of the  
bonding screw.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
3. Plan the wiring route from the electronics module to the monitored  
following guidelines.  
S Mount the electronics module within 3.05m (10 ft) of a  
disconnect device.  
S If installing conduit (not supplied), plan for adequate conduit  
®
®
routing. Follow National Electrical Code (NEC ) and local  
guidelines for conduit length and bending radius. Installed width  
of the EMS−UGK with both conduit boxes is 633 mm (24.9").  
Remove conduit box hole plugs as needed for conduit.  
S Follow NEC and local guidelines for filling wiring space and  
maintaining the thermal performance of the equipment.  
S Plan the location and installation of the CTs and wire taps to  
allow for adequate bending radius of wiring. If necessary,  
support the CTs to avoid undue strain on wiring.  
Table 2. Current Transformer Sizing  
CT Dimensions  
(W H D)  
Maximum Wire Insulation  
Outside Diameter  
Type of CT  
Rating  
Lead Length  
Branch CT  
75A  
25.4 38.1 25.4 mm  
0.91m (36.0")  
10.16 mm (0.40")  
16.00 mm (0.63")  
22.86 mm (0.90")  
15.24 mm (0.60")  
22.86 mm (0.90")  
(1.0" 1.5" 1.0")  
Branch CT  
(separate accessory)  
100A  
400A  
100A  
400A  
41.0 51.0 30.0 mm  
1.00m (39.4")  
0.91m (36.0")  
0.91m (36.0")  
0.91m (36.0")  
(1.6" 2.0" 1.2")  
Main CT (phases A,  
B, C, and Neutral)  
96.0 100.0 46.0 mm  
(3.8" 3.9" 1.8")  
Input Ground CT  
66.0 70.0 33.0 mm  
(2.6" 2.8" 1.3")  
Subfeed CT  
(separate accessory)  
96.0 100.0 46.0 mm  
(3.8" 3.9" 1.8")  
Table 3. Wire Tap Sizing  
Housing Color  
Wire Size  
2
Blue  
0.75–2.5 mm (18–14 AWG)  
2
Yellow  
4.0 mm (12 AWG)  
NOTE Use wire taps ONLY on thermoplastic insulation (PVC).  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Table 4. Harness Sizing  
Harness  
Bundled Length  
Connection  
Lead Length  
Voltage  
3.05m (10 ft)  
Phases (A, B, C)  
0.91m (3 ft)  
1.83m (6 ft)  
Ground (V1 only), Neutral  
Phases (A, B, C), Neutral, Ground  
Circuit Breakers 1/1 – 14/28*  
Circuit Breakers 15/8 – 28/35*  
Circuit Breakers 29/15 – 42/42*  
Three−Phase Circuit Breaker  
Subfeed Breaker  
Main Input  
2.74m (9 ft)  
2.74m (9 ft)  
304.8 mm (12")  
304.8 mm (12")  
203.2 mm (8")  
101.6 mm (4")  
101.6 mm (4")  
50.8 mm (2")  
Branch Circuit  
Wire Tap Transition  
Subfeed Transition  
N/A  
N/A  
Electronics Module  
NOTE Voltage harness  
shown installed with wire  
taps on an occupied  
CT1  
CT2  
Main CTs  
(A, B, C)  
CTM  
V2  
branch circuit breaker  
(20A maximum).  
External Ground  
(optional)  
Branch CTs  
Panel Connections:  
Branch CTs (CT1)  
Branch CTs (CT2)  
Main CTs (CTM)  
Voltage (V1)  
Wire Taps  
Neutral  
Panel Connections  
and  
Communication Features  
Input Ground CT  
Voltage Harness  
Branch Circuit Harnesses  
Main Harness  
Figure 5. Wiring Overview (Example Installation)  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
4. Connect the circular connector of each harness to the electronics  
module. Verify the harness label matches the connector label on  
detailed view of both panels.  
NOTE To connect a harness to the electronics module, align the polarizing keys and  
keyways and insert the plug into the receptacle. Rotate the attached coupling ring clockwise  
until it snaps into position.  
Branch Circuit Harness CT1  
CT1  
CT1  
Branch Circuit Harness CT2  
Main Input Harness CTM  
Voltage Harness V1  
CT2  
CTM  
V1  
CT2  
CTM  
V2  
Figure 6. Harness Connections at the Electronics Module  
Table 5. EMS−UGK Harness Connections  
Connection Description  
CT1  
Branch circuit harness from Panel 1 / Input 1 to Panel 1 breaker poles 1–21.  
Dual panel option only. Branch circuit harness from Panel 2 / Input 2 to Panel 2 breaker poles 1–21.  
CT2  
Branch circuit harness from Panel 1 / Input 1 to Panel 1 breaker poles 22–42.  
Dual panel option only. Branch circuit harness from Panel 2 / Input 2 to Panel 2 breaker poles 22–42.  
CTM  
Main input monitoring option only. Main input harness from Panel 1 / Input 1 to Panel 1 main  
connections.  
Dual panel option only. Main input harness from Panel 2 / Input 2 to Panel 2 main connections.  
V1  
V2  
Voltage harness from Panel 1 / Input 1 to Panel 1 reference voltage connection.  
Dual panel option only. Voltage harness from Panel 2 / Input 2 to Panel 2 reference voltage  
connection.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Figure 7. Panel Detail (EMS−UGK−LV Model with Dual Panel Option Shown)  
NOTE Single Panel option only. Connections for CT1, CT2, CTM, and V2 on  
Input 2 / Panel 2 are covered with hole plugs.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
5. Main input monitoring option only. Connect the main input harness to  
NOTE If you prefer not to install the Neutral CT, the EMS−UGK software can perform an  
approximate calculation of the Neutral CT values.  
Install the four 400A main CTs to the breaker panel wiring for A, B,  
and C phases, and Neutral. Install the 100A input ground CT to the  
breaker panel ground wiring.  
NOTE To install a CT, remove the cap, open the body of the CT to insert the wire through  
the slit, and reinstall the cap. Install all CTs with the ꢀH1" lettering facing the same direction.  
Connect each labeled lead on the main input harness (A, B, C,  
Neutral, and Ground) to the appropriate installed CT. Coil and secure  
any excess cable away from other conductors.  
NOTE Verify all installed main input monitoring wiring is correct and follows NEC and local  
guidelines. Verify all CTs are installed with their ꢀH1" lettering facing the same direction.  
NOTE The input ground CT will provide valid readings only in an isolated ground system.  
A
400A  
B
C
Main CT  
Main Input  
Harness  
C
ꢀH1"  
Lettering  
Neutral  
Cap  
400A  
100A  
Ground  
Input Ground CT  
Figure 8. Main Input Harness Connections  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
6. 75A or 100A Split−Core Branch CT option only. Connect the two branch  
NOTE Each connector on the branch circuit harness is labeled with two numbers, such as  
ꢀ1/1" or ꢀ5/3." The first number indicates the circuit breaker number according to NEMA  
breaker numbering; the second number is Standard breaker numbering. See ꢀBreaker  
For each circuit breaker to be monitored, find its labeled connector  
on the branch circuit harness, connect a 75A or 100A branch CT to  
the connector, then install the CT around the output wire connected  
to the matching breaker.  
For example, for circuit breaker 05 in a NEMA panel, connect a CT  
to harness connector 5/3, then install the CT on the output wire for  
circuit breaker 05.  
Coil and secure any excess cable away from other conductors.  
Branch  
Circuit  
Harness  
Branch CT  
Breaker 05  
5/3  
Figure 9. Branch Circuit Harness Connections  
8. Verify all installed branch circuit monitoring wiring is correct and  
follows NEC and local guidelines.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
9. Subfeed Accessory only. Locate the Subfeed Accessory Kit (three  
subfeed transition harnesses and three 400A CTs). Connect a  
Install each CT around the appropriate subfeed breaker wire.  
NOTE To install a CT, remove the cap, open the body of the CT to insert the wire through  
the slit, and reinstall the cap. Install all CTs with the ꢀH1" lettering facing the same direction.  
Attach each subfeed transition harness to the appropriate  
Coil and secure any excess cable away from other conductors.  
NOTE Verify all installed subfeed monitoring wiring is correct and follows NEC and local  
guidelines. Verify all CTs are installed with their ꢀH1" lettering facing the same direction.  
Cap  
Subfeed Transition Harness  
400A CT  
ꢀH1"  
Lettering  
Branch  
Circuit  
Harness  
Figure 10. Subfeed Monitoring Connections  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
CAUTION  
S
S
Panel 1 voltage sensing includes a ground wire, but Panel 2 voltage sensing does not. If  
installing dual panels, connect the voltage harness V1 for Panel 1 first. When  
disconnecting dual panels, disconnect the voltage harness V2 for Panel 2 first.  
Use the branch circuit breakers to disconnect hazardous voltage from the EMS−UGK. Turn  
off the breaker before disconnecting the voltage measuring circuit cables, or hazardous  
voltage may be present at the exposed end of the cable.  
10. On the voltage harness V1 for Panel 1, locate the green and yellow  
Ground wire. Attach the Ground ferrule to a ground point within the  
CAUTION  
Before connecting the voltage harness to a branch circuit breaker, shut down the branch  
circuit breaker. Risk of electric shock.  
12. Choose an option for connecting the phases for voltage sensing:  
NOTE Maximum branch circuit breaker size where the voltage sensing is located is 20A.  
S Use the supplied wire tap transition harnesses to connect the  
voltage harness to an unoccupied three−phase branch circuit  
S Use the supplied wire taps to connect the voltage harness to an  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
13. Unoccupied three−phase branch circuit breaker connection only. Verify  
that the branch circuit breaker is turned off. Be absolutely certain  
there is no power.  
Attach a wire tap transition harness (supplied) to each of the phase  
A, B, and C connectors on the voltage harness.  
Connect the wire tap transition harnesses to the appropriate phase  
connections of the unoccupied three−phase branch circuit breaker.  
Coil and secure any excess cable away from other conductors.  
Wire Tap  
Transition Harness  
Unoccupied  
Breaker  
A, B, C  
Phases  
Neutral  
Voltage  
Harness  
Ground  
Breakers  
Figure 11. Voltage Harness Connections to Unoccupied Breaker (V1 Harness Shown)  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
NOTE Use wire taps ONLY on thermoplastic insulation (PVC).  
14. Occupied three−phase branch circuit breaker connection only. Verify that  
the branch circuit breaker is turned off. Be absolutely certain there  
is no power.  
Use pliers to carefully install the appropriate size wire taps  
(supplied) to phase A, B, and C wiring on the occupied circuit  
Verify the wire taps are completely closed around the wires.  
Connect the phase A, B, and C connectors on the voltage harness  
to the appropriate installed wire taps. Coil and secure any excess  
cable away from other conductors.  
Wiring to Occupied Breaker  
A, B, C  
Phases  
Neutral  
Voltage  
Harness  
Ground  
Wire Tap  
Figure 12. Voltage Harness Connections to Occupied Breaker (V1 Harness Shown)  
harness V2 and Panel 2 for Neutral, A, B, and C phase connections.  
Panel 2 does not have a Ground connection.  
16. Verify all installed voltage monitoring wiring is correct and follows  
NEC and local guidelines.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
17. If installing communication functions, install the wiring for the Alarm  
Relay and Building Alarms connections. For more information, see  
18. Start up the host equipment. Refer to the user’s guide for the host  
equipment for startup instructions.  
19. Activate the reset switch on the bottom of the electronics module:  
hold the switch for 10 seconds or until the display (if installed) turns  
off, then release the switch.  
20. Verify that the Power LED on the Power Xpert Gateway Series  
Display option only. Verify that the display on the front of the  
electronics module also activates. Press any button to display the  
mimic screen.  
Power LED  
Figure 13. Power LED on the Power Xpert Gateway Series 1000 Card  
21. Conduit Box option only. Reinstall the top plate on the left conduit  
box.  
continue to the following step.  
23. Conduit Box option only. If a right conduit box is installed, reinstall the  
top plate on the right conduit box.  
24. Continue to the following section, ꢀInitial Configuration."  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Initial Configuration  
This section describes how to use the supplied software configuration  
tool to perform initial configuration and calibration. You can use either  
the tool or the optional display (if installed) to configure the panels and  
breakers.  
After initial configuration, interface with the EMS−UGK using a Web page  
interface, the Advanced Metering monitoring system, or (if the optional  
display is installed) directly through the display.  
Installing the Software Configuration Tool  
NOTE For best results, install the software configuration tool on a computer running the  
®
Microsoft Windows XP or Windows 2000 operating system.  
®
To install the software configuration tool:  
1. Connect a computer to the service port on the electronics module  
using the supplied DB−9 to RS−232 serial cable.  
2. Set the computer’s COM port settings to COM1, 19200 baud.  
3. Verify that the computer’s settings for the date and time are  
correct. The configuration tool uses the computer’s settings to  
automatically set the date and time for the EMS−UGK. You can  
disable this feature later if needed.  
4. Insert the EMS Configuration Tool CD into the computer’s CD drive.  
The installation program begins automatically within 10 seconds.  
If the installation program does not begin automatically, run the  
CD_Menu.exe program on the CD.  
5. Follow the installation program instructions to install the tool.  
6. Continue to the following section, ꢀInitial System Configuration."  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Initial System Configuration  
To configure required and optional system settings:  
1. Verify the EMS−UGK is physically connected to all installed CTs.  
2. Verify that main voltages are connected and the EMS−UGK is  
powered on.  
3. Click Start > Programs > EATON > EMS Configuration Tool to open the  
configuration tool. The System Status page displays, as shown in  
Figure 14. System Status Page (Not Connected)  
4. Click Connect to establish communication with the EMS−UGK.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
5. Verify that meter and status information from the EMS−UGK  
NOTE Because the system is not yet configured, active alarms may appear in the Active  
Alarms window upon connection and may be ignored.  
If your system is dual input but only one input displays on the  
System Status page, click the Feature Settings tab and select the  
Enable Dual Input Mode check box. Return to the System Status page  
Active  
Alarms  
Window  
Figure 15. System Status Page (Connected)  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
6. Click the EMS System Settings tab to display the Configure Primary  
EMS Settings page.  
7. Configure the following required settings:  
EMS System Setting Description  
Nominal Voltage  
Settings  
Verify the nominal input voltage and frequency settings are  
correct for your installation. Adjust as needed.  
NOTE Specify nominal voltage as Line to Neutral voltage (not  
Line to Line voltage).  
Input / Output CT  
Settings  
Main input monitoring option only. Select the type and rating  
for the input and neutral CTs installed (400A) and for the input  
ground CT installed (100A).  
NOTE Configure a CT only if it is installed.  
NOTE If the neutral CT is not installed, the software calculates  
its approximate values.  
System Name and  
Rating  
(1) Specify a Name for the system:  
To change the default name, double−click in the Name field and  
type the new name. Press Enter, then click Yes to confirm.  
(2) Set the Rating in VA for the installation:  
This setting matches the summation of the ratings on your  
panels and is the overload level. To calculate the Rating, multiply  
the main breaker rating for each panel by the nominal L−N  
voltage. For example, for two 225A panels and a 120V nominal  
input voltage, the rating is 225 2 120, or 54,000 VA.  
NOTE If your breakers are configured, you can select Auto  
Calc to have the software automatically calculate the VA rating.  
LCD Mimic Screen  
Display  
(1) Select the option that best describes the installation:  
S For an EMS−UGK, select EMS−UGK.  
S For one panel, select 1 In / 1 Out.  
S For two panels, select 2 In / 2 Out.  
S For Harmonic Distortion transformers, select 1 In / 2 Out.  
S For dual input PDUs with Kirk® key interlocks, select  
2 In / 1 Out.  
(2) To display a transformer on the mimic screen, select the  
check box for Input Transformer Installed.  
NOTE The transformer symbol is not available for all mimic  
screen options.  
NOTE To revert any changes made on the current page (except System Name) back to  
default settings before saving, click Reload Sys Config.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
8. Optional. To prevent the software configuration tool from  
synchronizing with the PC date and time, select Don’t auto update.  
9. Click Save Sys Config to save the settings to the EMS−UGK.  
Depending on communication speed, updates take effect within  
15–20 seconds.  
10. Optional. Voltage and current calibration is performed at the factory.  
The EMS−UGK does not require calibration. If you choose to  
recalibrate, the original calibrated values will be lost.  
To recalibrate the settings, click the Calibration tab to display the  
EMS System Calibration page.  
NOTE For optimal results, verify that the circuits are loaded to nominal load levels prior to  
starting calibration. Have qualified service personnel (such as a licensed electrician) obtain  
the physical measurements using a multimeter and RMS current probe. For calibration,  
measure the L−N voltage (not L−L voltage).  
Enter the voltage and current measurements from the installed  
panel(s) on the EMS System Calibration page. Blank fields will not  
be calibrated.  
NOTE To revert any changes made on the current page back to default settings before  
saving, click Reload Cal Data.  
Click Save Cal Data to update the voltage calibration data and save  
the settings to the EMS−UGK. Depending on communication speed,  
updates take effect within 15–20 seconds.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
11. Click the Feature Settings tab to display the EMS Feature Settings  
page.  
12. Configure the following Miscellaneous Features:  
Feature Setting  
Description  
Audible Horn Disabled  
Select to disable the audible horn. If enabled, the horn  
sounds for each new alarm and can be turned off by  
pressing any key on the display.  
Meter Simulation Mode  
Enabled  
Select to enable demonstration mode for use with a  
simulator.  
LCD Displays Input 1 V as L to L Select to display Line to Line voltages on the display.  
LCD Displays Input 2 V as L to L If unselected, voltages display as Line to Neutral  
voltages.  
Enable THD Alarms  
Select to enable Total Harmonic Distortion metering  
alarms detected by monitor.  
Enable Dual Input Mode  
Select for dual input models.  
NOTE Deselecting this option removes all selections  
and displays for the second input.  
13. Configure the following Building Alarm Settings:  
Feature Setting  
Description  
Set Custom Alarm Name  
Contact Type  
Type a name for Building Alarms 1 through 4.  
Select if the Building Alarm is connected as  
normally−closed.  
Action When Active  
Select the action to occur when the Building Alarm  
becomes active.  
NOTE To revert any changes made on the current page back to default settings before  
saving, click Reload Config.  
14. Click Save Config to save the settings to the EMS−UGK. Depending  
on communication speed, updates take effect within 15–20  
seconds.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
15. To configure panels and breakers using the software configuration  
tool, continue to the following section, ꢀInitial Panel and Breaker  
Configuration (Using the Software Configuration Tool)."  
To configure panels and breakers using the optional display,  
16. Click Disconnect to disconnect from the EMS−UGK. Verify that ꢀNot  
Connected" displays at the bottom of the page.  
17. Close the software configuration tool and remove the configuration  
cable.  
18. Activate the reset switch on the bottom of the electronics module:  
hold the switch for 10 seconds or until the display (if installed) turns  
off, then release the switch.  
19. Continue to ꢀInitial Panel and Breaker Configuration (Using the  
Initial Panel and Breaker Configuration (Using the  
Software Configuration Tool)  
To configure the panels and breakers:  
1. Click the Panel Config tab to display the EMS Panel Settings page.  
2. Verify that the Number of BCM Panels Installed is correct for your  
installation.  
If you change the value, click Save Panel Config to save the setting to  
the EMS−UGK. Depending on communication speed, updates take  
effect within 15–20 seconds.  
3. Select the panel number to configure (Panel Selected).  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
4. Configure the following settings for the selected panel:  
Panel Setting  
Description  
Panel Rating  
Specify the panel breaker rating (in amps).  
NOTE Setting the panel breaker rating to 0 silences all  
main panel breaker alarms and zeroes the panel percent  
current levels.  
Panel Warn (%)  
Panel Alarm (%)  
Num Brkr Positions  
Panel Name  
Specify the warning threshold level (in percent load).  
Specify the alarm threshold level (in percent load).  
Specify the number of breakers in the panel.  
Specify a panel name (up to 19 characters).  
Panel Serial Number  
Panel Layout  
Specify the panel’s serial number (up to 19 characters).  
Specify the panel numbering style.  
NOTE Changing panel layout erases all branch circuit  
breaker configurations.  
NOTE To revert any changes made on the current page back to default settings before  
saving, click Reload Panel Config.  
5. Click Save Panel Config to save the settings to the EMS−UGK.  
Depending on communication speed, updates take effect within  
15–20 seconds.  
7. Click the Breaker Config tab to display the Breaker Settings page.  
The tool automatically updates the default breaker schedule with  
the latest information from the EMS−UGK. Depending on  
communication speed, updates take effect within 15–20 seconds.  
8. Select the Panel Number of the panel containing the breakers to  
configure. The tool automatically updates the selected breaker  
schedule with the latest information from the EMS−UGK.  
Depending on communication speed, updates take effect within  
15–20 seconds.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
9. The selected breaker is highlighted in bold in the schedule. The  
breaker’s configuration details display in the right half of the page.  
Click the breaker to configure. The breaker number highlights and  
its details display at right.  
10. Configure the following settings for the selected breaker:  
Breaker Setting  
Num Phases  
Breaker Rating  
Warning Level  
Alarm Level  
Description  
Specify the number of phases (1–3).  
Specify the branch breaker rating (in amps).  
Specify the warning threshold level (in percent load).  
Specify the alarm threshold level (in percent load).  
CT Ratio  
Specify the current transformer ratio (75A).  
NOTE The selected ratio converts to the value 71.9.  
NOTE To revert any changes made on the current page back to default settings before  
saving, click Reload Breaker Config.  
panel.  
12. Click Save Breaker Config to save the settings to the EMS−UGK.  
remaining panels.  
14. Click Disconnect to disconnect from the EMS−UGK. Verify that ꢀNot  
Connected" displays at the bottom of the page.  
15. Close the software configuration tool and remove the configuration  
cable.  
16. Activate the reset switch on the bottom of the electronics module:  
hold the switch for 10 seconds or until the display (if installed) turns  
off, then release the switch.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Initial Panel and Breaker Configuration (Using the Display)  
NOTE Use this section only if the optional display is installed.  
Configure the panel and breaker data. You can use the following  
abbreviated instructions or follow the more detailed steps in ꢀControl  
1. From the setup screen, enter the Level 1 access password (default  
password is L1).  
2. Select Meters then Panel, highlight the panel to configure, then  
select Config.  
3. Set the Reset value to Yes and select OK to clear any breaker  
configuration settings for the panel.  
4. Configure the following settings to match the physical panel:  
Phases (always three−phase)  
Breakers (the number of breakers in the panel)  
Rating (the rating in Amps of the main panel breaker)  
Panel Layout (panel numbering style)  
5. Highlight the panel number and select Schedule.  
6. Highlight the breaker to configure and select Config.  
7. Configure the following settings to match the physical breaker:  
Phases (number of phases for the breaker)  
Rating (breaker rating in Amps)  
Warning (alarm warning level in %)  
Overload (alarm overload level in %)  
CT (the CT ratio – specify 71.9)  
8. Configure each installed breaker in the panel.  
9. If a second panel is installed, repeat the panel and breaker  
configuration for the second panel.  
10. Activate the reset switch on the bottom of the electronics module:  
hold the switch for 10 seconds or until the display (if installed) turns  
off, then release the switch.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
11. From the setup screen, clear the History Log and Load Profile. For  
12. Continue to the following section, ꢀAdvanced Metering  
Installation."  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
Advanced Metering Installation  
factory−installed in the X−Slot communication bay on the side of the  
EMS−UGK electronics module.  
To connect the cables and configure the card:  
1. Locate the Power Xpert Gateway Series 1000 Card Quick Start  
Instructions included with the EMS−UGK.  
2. Perform all the steps in the quick start instructions, ignoring the  
initial few steps that describe how to install the card in a PDU.  
The quick start instructions direct you to:  
S Connect the Ethernet cable  
S Connect the configuration (serial) cable  
S Configure IP Address assignments  
3. For more detailed information about installing the card or using  
Advanced Metering, download the Power Xpert Gateway Series  
1000 Card user’s guide from the Documentation page on the Power  
Xpert card once the card is accessible on your network or from  
Configuration  
(Serial) Port  
Ethernet  
Port 1  
Ethernet  
Port 2  
Figure 16. Power Xpert Gateway Series 1000 Card  
4. Conduit Box option only. If a right conduit box is installed, reinstall the  
top plate on the right conduit box.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 3  
Operation  
This chapter describes how to use the Energy Management System  
(EMS) Upgrade Kit (EMS−UGK) interface.  
Reset Function  
The EMS−UGK is intended for continuous duty operation. Cycle power  
for the EMS−UGK using the reset switch at the base of the electronics  
module: hold the switch for 10 seconds or until the display (if installed)  
turns off, then release the switch. The switch is intended for use as a  
programming reset function.  
NOTE The reset switch controls power to the transformer inside the electronics module.  
The reset switch does not remove three−phase sensing voltage from the Universal Control  
Board (UCB).  
Breaker Numbering  
NEMA numbering is left to right in a two−column panel. Odd−numbered  
breakers are on the left and even−numbered breakers are on the right.  
Standard numbering is top to bottom down the left side of the panel,  
then top to bottom down the right side of the panel.  
01  
03  
05  
02  
04  
06  
01  
02  
03  
04  
22  
23  
24  
25  
NEMA  
Panel  
Standard  
Panel  
Figure 17. Breaker Numbering  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Control Panel Functions  
NOTE Use this section only if the optional display is installed.  
The EMS−UGK has a graphical LCD with backlight, four status LEDs, and  
information about system events, measurements, and settings.  
Power On (green)  
Overload (yellow)  
No function (always off)  
PRESS ANY KEY TO CONTINUE  
Alarm (red)  
Control Buttons for the LCD Menu Options  
Figure 18. EMS−UGK Display  
The following table shows the indicator status and description.  
Indicator  
Status  
Description  
ON  
Green  
On  
The product on which the EMS−UGK is installed is  
operating normally.  
Off  
On  
The product on which the EMS−UGK is installed is turned  
off and will not turn on automatically.  
O/L  
Yellow  
One or more phases is in overload, or there is an alarm or  
warning for neutral overload, ground overload, main panel  
breaker overload, or panel breaker overload.  
OFF  
Off  
Not applicable for the EMS−UGK.  
AL  
Red  
Flashing  
There is a new or cleared EMS−UGK alarm condition. See  
ꢀTroubleshooting" on page 61 for additional information.  
To silence the horn, press any button.  
On  
An acknowledged alarm condition exists.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Display Functions  
The LCD displays the Eaton Powerware logo. Press any button to  
screen shows a real−time graphical representation of the operating  
status of the system. At the top of the screen, an information line cycles  
through displays of information such as the date and time and any active  
alarms or events.  
To select a menu option, press the button below the option name.  
When available:  
S Use the and buttons to scroll through a listing of information.  
S Use the and  
view or change.  
buttons to select another item on the screen to  
S Use the + or button to increase or decrease a selected value.  
S Press the  
button to return to the previous menu.  
NOTE After making configuration changes, you can save your changes immediately by  
pressing the Reset button on the Power Xpert Gateway Card installed in the X−Slot  
communication bay. The card resets automatically after five minutes.  
The backlit LCD automatically dims after a long period of inactivity. Press  
any button to restore the screen.  
Input 1 / Panel 1  
Unit Name  
Input 2 / Panel 2  
EATON  
EMS−UGK  
EMS  
000.0  
000.0  
000.0  
000.0  
000.0  
000.0  
PROFILE  
EVENTS METER  
SETUP  
EVENT ME-  
TER  
SET-  
UP  
S
Figure 19. EMS−UGK Mimic Screen and Main Menu  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Menu Map  
The following tables show the basic menu structure.  
Table 6. Menu Map for Display Functions  
Main Menu  
Submenu  
Active Events  
History  
Display Information or Menu Function  
Events  
Displays list of active system events. As events clear, they are removed from the list.  
Displays historical log of system events. The log stores the most recent 127 events  
and alarms.  
Meter*  
Input 2  
Displays Input 2 / Panel 2 performance meters for the system or critical load:  
RMS / % / THD / Crest / KWH  
detail).**  
Input 1  
Displays Input 1 / Panel 1 performance meters for the system or critical load:  
RMS / % / THD / Crest / KWH  
detail).**  
Profile*  
Setup*  
Displays load profile for the most recent 24 months. Profile includes highest and  
lowest input and output currents, frequencies, power levels, power factors,  
AC undervoltage, THD, and exact time each reading occurred. Current month’s profile  
reflects real−time values.  
* Information displayed depends on product configuration.  
** Configuration options are password−protected.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Table 7. Panel Meters  
Screen  
Label  
Meters Displayed  
Panel  
(first screen)  
ALM  
Alarm status (W for warnings, A for critical alarms)  
Ratio (in percent) of present load compared to maximum  
Average voltage  
%LOAD  
Vavg  
Imax  
Phase with highest current  
Panel  
(second screen)  
V1, V2, V3  
I1, I2, I3  
Voltage per phase  
Current per phase  
Panel  
(third screen)  
I1%, I2%, I3%  
Ratio (in percent) of present current compared to maximum  
Total kW of panel breakers  
KW  
KVA  
PF  
Total kVA of panel breakers  
Power factor  
Panel  
(fourth screen)  
#BRKS  
KWH/m  
KWH/y  
KWHt  
Number of breakers  
Kilowatt hours per month  
Kilowatt hours per year  
Total kilowatt hours  
Panel*  
(fifth screen)  
MAX V  
MAX I  
Maximum voltage logged  
Maximum current logged  
* To reset the panel statistics (fifth screen) to zero, select RESET.  
Table 8. Breaker Meters  
Screen  
Label  
Meters Displayed  
Panel X Breaker Meters  
(first screen)  
ALM  
Alarm status  
CURR%  
PHASE  
Irms  
Ratio (in percent) of present current compared to breaker rating  
Phase assignment  
Current (RMS value)  
Breaker rating  
RTNG  
Panel X Breaker Meters  
(second screen)  
W
Average W  
VA  
Average VA  
PF  
Average power factor  
WARN  
OVER  
Threshold load (in percent) at which a warning alarm is logged  
Threshold load (in percent) at which an overage alarm is logged  
Panel X Breaker Meters  
(third screen)  
KWH/m  
KWH/y  
KWHt  
Kilowatt hours per month  
Kilowatt hours per year  
Total kilowatt hours  
Panel X Breaker Meters  
(fourth screen)  
Imax  
Maximum current logged  
Maximum W logged  
Wmax  
VAmax  
PFmin  
Maximum VA logged  
Minimum power factor logged  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Setup Options  
Access to setup options is restricted to three System Setup Levels: 0, 1,  
or 2. The higher the level, the more setup options are available. Options  
on System Setup Level 0 do not require password access.  
Table 9. Setup Options  
Minimum  
Description  
Level*  
Available Settings  
Default Setting  
0
Enter Password  
Use the arrow keys to enter the password for the level you Level 1: L1  
want to access, then select DONE to display the options for Level 2: Contact your  
the setup level  
service representative  
0
Versions  
Read only  
Current firmware  
versions installed  
0
1
Contrast Adjust  
Log Out  
Adjust screen contrast with left/right arrow buttons  
10%  
Exit the Level 1 or Level 2 setup options and display the  
Level 0 setup options  
None  
1
1
Change Access  
Level Password  
Change the password for the current setup level  
Use the arrow keys to enter the new password (A–Z, 0–9, –,  
blank,), then select DONE to save the new password.  
None  
Set Date and Time  
Set Month, Date, Year (mm/dd/yyyy)  
00/00/0000  
00:00  
Set Hour, Minute (Time is a 24−hour clock.)  
1
1
1
Clear History  
Clear the History Log  
Clear the Load Profile  
None  
None  
Clear Load Profile  
Building Alarm  
Setup  
For Building Alarm 1 through Building Alarm 4:  
Name String [up to 19 characters (A–Z, 0–9, –, blank)]  
Settings: Contact Normally Open or Closed  
Building Alarm Type (REPO, EPO, TVSS/SPD,  
Custom)  
BUILDING ALARM [X]  
Open  
1 and 2: Custom;  
3: REPO; 4: EPO  
Log Only  
Notice Level (Log and Alarm options)  
Enabled/Disabled  
Enabled  
1
THD Alarm Level  
Set the voltage and current Total Harmonic Distortion for  
Input 1 and Input 2, and enable or disable this feature:  
THD settings  
5.0  
Disabled  
Enabled/Disabled  
2
2
2
Unit Type  
Read only: Model / CTO / Serial  
Factory−set identifiers  
EATON EMS−UGK  
None  
Unit Name  
Up to 19 characters (A–Z, 0–9, –, blank)  
Reset the Level 1 password to the default setting  
Reset All Lower  
Level Passwords  
* Minimum System Setup Level required to access the setup option.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Control Panel Configuration  
NOTE Use this section only if the optional display is installed.  
To set up branch circuit monitoring on your product, configure the panels  
and branch circuit breakers. Configuration requires System Setup  
Level 1 password access.  
Accessing Configuration  
To access the configuration options at System Setup Level 1:  
1. In the Setup menu, select ENTER PASSWORD.  
2. Use the arrow keys to enter the password (default password is L1  
for Level 1).  
3. Select DONE. The screen displays the setup options.  
To change the default password while logged into System Setup Level 1  
access:  
1. In the Setup menu, select CHANGE ACCESS LEVEL PASSWORD.  
2. Use the arrow keys to enter the new password (A–Z, 0–9, –, blank).  
3. Select DONE.  
Configuring Panels Containing Branch Circuit Breakers  
To configure panels containing branch circuit breakers:  
1. If not already obtained, access the System Setup Level 1 password  
level. See the previous section, ꢀAccessing Configuration."  
2. From the main menu, select METER then PANEL.  
3. On the PANEL screen, select the panel number (PNL) to configure,  
and then select CONFIG.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
4. On the PANEL CONFIG screen, set the panel’s meter settings:  
Default  
Range  
Meter Setting Description  
3
3
PHASES  
Number of phases  
42  
0–42  
(even numbers)  
BREAKERS  
Number of branch circuit  
breakers in the panel  
100  
0–1200  
RATING  
Panel breaker rating (in amps)  
(see Note 1)  
STANDARD  
STANDARD  
COLUMN  
PNL LAYOUT  
Panel layout  
(see Note 2)  
NOTE 1 Setting the panel breaker rating to 0 silences all main panel breaker  
alarms and zeroes the panel percent current levels.  
NOTE 2 Changing panel layout erases all branch circuit breaker configurations.  
To reset all values on the screen to defaults, set the RESET value to  
YES.  
5. Select OK.  
breakers to configure.  
7. When all panel configuration is complete, select the  
repeatedly to reach the main menu.  
button  
8. If all configuration is complete, save your changes by pressing the  
Reset button on the Power Xpert Gateway Card in the X−Slot  
communication bay. (The card automatically resets after five  
minutes.) Otherwise, continue to ꢀConfiguring Branch Circuit  
Configuring Panels Containing Subfeed Breakers  
To configure panels containing subfeed breakers (up to 12 per panel):  
1. If not already obtained, access the System Setup Level 1 password  
2. From the main menu, select METER then PANEL.  
3. On the PANEL screen, select the panel number (PNL) to configure,  
and then select CONFIG.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
4. On the PANEL CONFIG screen, set the panel’s meter settings:  
Default  
Range  
Meter Setting Description  
3
3
PHASES  
Number of phases  
42  
0–42  
(even numbers)  
BREAKERS*  
Number of subfeed breakers in  
the panel, times 3  
100  
0–1200  
RATING  
Subfeed breaker rating (in amps)  
(see Note 1)  
STANDARD STANDARD  
COLUMN  
PNL LAYOUT  
Panel layout  
(see Note 2)  
* For example, if the panel has 6 subfeed breakers, set the BREAKERS value to 18.  
NOTE 1 Setting the panel breaker rating to 0 silences all main panel breaker  
alarms and zeroes the panel percent current levels.  
NOTE 2 Changing panel layout erases all branch circuit breaker configurations.  
To reset all values on the screen to defaults, set the RESET value to  
YES.  
5. Select OK, the panel number (PNL), then SCHEDULE.  
On the PANEL SCHEDULE screen, each subfeed breaker displays  
as a group of three phases.  
6. Select the  
button to return to the PANEL screen.  
configure.  
8. When all panel configuration is complete, select the  
repeatedly to reach the main menu.  
button  
9. If all configuration is complete, save your changes by pressing the  
Reset button on the Power Xpert Gateway Card in the X−Slot  
communication bay. (The card automatically resets after five  
minutes.) Otherwise, continue to the following section,  
ꢀConfiguring Branch Circuit Breakers."  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Configuring Branch Circuit Breakers  
Follow the appropriate steps to configure, remove, or change the branch  
circuit breakers.  
To configure the branch circuit breakers (up to 42 per panel):  
1. If not already obtained, access the System Setup Level 1 password  
2. From the main menu, select METER then PANEL.  
3. On the PANEL screen, select the panel number (PNL) to configure,  
and then select SCHEDULE.  
4. On the PANEL SCHEDULE screen, highlight the individual breaker  
to configure and then select BREAKER.  
Breakers with blank rating (RTNG) values are not yet configured.  
numbering.  
5. On the PANEL X BREAKER METERS screen, select CONFIG and  
then configure the individual breaker’s meter settings:  
NOTE Configure a breaker only if its CT is installed.  
Default  
Range  
1–3  
Meter Setting Description  
1
PHASES  
RATING  
Number of phases  
20  
10–100  
Branch breaker rating (in amps)  
NOTE Subfeed breaker rating range  
is 100–1200.  
80  
0–100  
0–100  
10–100  
WARNING  
OVERLOAD  
CT  
Warning threshold level (in percent  
load)*  
90  
Alarm threshold level (in percent  
load)*  
71.9  
CT ratio  
* Alarm automatically turns off when the load drops below the threshold level.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
6. When the individual circuit configuration is complete, select OK to  
return to the PANEL SCHEDULE screen to configure the next  
breaker.  
7. When all branch circuit configuration is complete, select the  
button repeatedly to reach the main menu.  
8. If all configuration is complete, save your changes by pressing the  
Reset button on the Power Xpert Gateway Card in the X−Slot  
communication bay. (The card automatically resets after five  
minutes.)  
To remove a breaker from the panel:  
1. If not already obtained, access the System Setup Level 1 password  
2. From the main menu, select METER then PANEL.  
3. Highlight the panel number (PNL), and then select SCHEDULE.  
4. Highlight the breaker to remove, and then select BREAKER and  
DELETE.  
5. Select the  
button repeatedly to reach the main menu.  
6. If all configuration is complete, save your changes by pressing the  
Reset button on the Power Xpert Gateway Card in the X−Slot  
communication bay. (The card automatically resets after five  
minutes.)  
To change a breaker’s settings:  
1. If not already obtained, access the System Setup Level 1 password  
2. Follow the steps to remove a breaker from the panel.  
3. Follow the steps to configure a breaker.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
Viewing Panel Meters  
NOTE Use this section only if the optional display is installed.  
To view the meters for the panels:  
1. From the main menu, select METER then PANEL.  
2. Use the arrow keys to scroll through the panel meters (listed in  
To reset a panel’s meter statistics, scroll to the last panel screen,  
highlight the panel number, and select RESET.  
3. When viewing is complete, select the  
the main menu.  
button repeatedly to reach  
Viewing Breaker Meters  
NOTE Use this section only if the optional display is installed.  
To view the meters for the breakers:  
1. From the main menu, select METER then PANEL.  
2. On the PANEL screen, select the panel number (PNL) to view, and  
then select SCHEDULE.  
3. The PANEL SCHEDULE screen shows each breaker’s alarm status  
and rating. Use the up and down arrow keys to scroll through the  
list of breakers.  
4. To view the meters for an individual breaker, highlight the breaker  
number, and then select BREAKER.  
The PANEL X BREAKER METERS screens show meters for the  
right arrow keys to scroll through the meters.  
5. When viewing is complete, select the  
the main menu.  
button repeatedly to reach  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 4  
Communication  
This section describes the communication features of the Energy  
Management System (EMS) Upgrade Kit (EMS−UGK):  
S Serial port (Service)  
S X−Slot card (Power Xpert Gateway Series 1000 Card)  
S Relay output contacts (Alarm Relay)  
S Programmable signal inputs (Building Alarms)  
Serial Port  
(Service)  
Building  
Alarms  
terminal details.  
Alarm  
Relay  
Power Xpert Gateway  
Series 1000 Card  
Figure 20. Communication Features (EMS−UGK−LV Model with Dual Panel Option Shown)  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
COMMUNICATION  
Installing Communication Features  
To install the communication options and control terminals:  
1. Install and connect the appropriate cable(s).  
See the following section, ꢀCommunication Options," or ꢀControl  
2. Route and tie the cable(s) out of the way.  
Communication Options  
The EMS−UGK has serial communication capabilities through the serial  
port or through the X−Slot card.  
Serial Port (Service)  
To establish communication between the EMS−UGK and a computer,  
connect your computer to the EMS−UGK serial port using a  
communication cable (not supplied).  
If the optional conduit box is installed, a DB−9 extender cable (supplied)  
provides access to the port.  
6
7
8
9
1
2
3
4
5
Figure 21. Serial Port  
Table 10. Serial Port Pin Assignment  
Pin Number Signal Name  
Direction from the  
EMS−UGK  
Function  
2
3
5
TxD  
RxD  
GND  
Transmit to external device  
Receive from external device  
Signal common (tied to chassis)  
Out  
In  
Ċ
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
COMMUNICATION  
®
Use the computer’s HyperTerminal (or equivalent) application to access  
Terminal mode through the EMS−UGK communication port.  
Table 11. Terminal Mode  
Key Combination*  
[ESC] [A]  
Display  
Active Events  
Comment  
Displays a list of active events.  
[ESC] [H]  
History Log  
Prints the History Log with a firmware version header, beginning with the  
oldest entry. Alarms that occur while the log is printing are included in  
chronological order.  
System events are continually logged through the serial port to the device  
connected to the port.  
[ESC] [P]  
[ESC] [V]  
Profile Log  
Prints the Profile Log, beginning with the oldest entries.  
All screens  
(video mode)  
Navigate the screens just as on the EMS−UGK’s display, substituting the  
keyboard keys 1, 2, 3, 4, and 5 for the five pushbuttons on the EMS−UGK  
display. The indicators display as text to the right of the main screen.  
* Hold down the [ESC] key and press the letter key.  
X−Slot Card  
The Power Xpert Gateway Series 1000 Card installed in the X−Slot  
communication bay provides remote monitoring through a Web browser  
interface, e−mail, and a network managment system using SNMP;  
®
connects to a twisted−pair Ethernet (10/100BaseT) network. Modbus  
TCP support provides direct integration of a monitored panel’s  
parameters to a Building Management System (BMS). It has a built−in  
switching hub that allows one additional network device to be  
connected to the network without the requirement of an additional  
network drop.  
NOTE LAN drops for use with the X−Slot card must be provided by the customer.  
bay.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
COMMUNICATION  
Control Terminals  
The cables should be connected to the control terminals with a mating  
connector. The relay contact terminals have functional electrical isolation  
from the system. The building alarms share a common (–) through  
100 ohms, and have functional electrical isolation from the system, but  
not from each other.  
1
2
+ Polarity  
– Polarity  
Building Alarm 1  
Building Alarm 2  
+ Polarity  
– Polarity  
TB1  
3
4
+ Polarity  
– Polarity  
Building Alarm 3  
Building Alarm 4  
EMS−UGK  
Connectors  
+ Polarity  
– Polarity  
Common  
C
TB2  
Normally Open  
Normally Closed  
NO  
NC  
Relay Output  
Figure 22. External Control Terminal Connections  
NOTE If using a semiconductor switch type, pay attention to the proper polarity. A relay or  
other contact closure is preferred.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
COMMUNICATION  
Relay Output Contacts (Alarm Relay)  
The EMS−UGK incorporates a programmable relay output with potential  
free contacts for remote alarm indications.  
The SPDT (single pole double throw) relay provides both NO and NC  
contacts. These contacts can be connected to equipment at the facility  
(such as a light or an alarm bell) to signal when an alarm is active on the  
EMS−UGK. This feature is useful if the EMS−UGK is located in a remote  
area where the EMS−UGK horn may not be heard immediately.  
WARNING  
The relay output contacts must not be connected to any utility connected circuits. Reinforced  
insulation to the utility is required. The relay output contacts have a maximum rating of 8A  
at 32 Vdc or less, derate to 1A at 60 Vdc. Do not operate above 42.4 Vpk or 60 Vdc.  
Programmable Signal Inputs (Building Alarms)  
The EMS−UGK incorporates four programmable signal inputs, each with  
a signal and a signal return. When the signal is shorted, the input is read  
as active. The pins must be shorted with maximum resistance of  
10 ohm to activate the specific input. Seventeen milliamps are required  
to drive the signal active.  
control is required.  
This feature lets you connect the EMS−UGK to your building alarms,  
such as smoke detectors or overtemperature alarms. For each building  
alarm, you can set:  
S The building alarm name  
S The contact type (NO or NC)  
S The building alarm type  
NOTE A building alarm programmed for REPO will trigger the REPO alarm and the alarm  
associated with the building alarm number.  
S The notice level  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
COMMUNICATION  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 5  
Maintenance  
Keep the area around the hardware and wiring clean and dust-free. Wipe  
with a dry cloth as needed. The Energy Management System (EMS)  
Upgrade Kit (EMS−UGK) does not require an annual calibration.  
Recycling the Used Equipment  
Contact your local recycling or hazardous waste center for information  
on proper disposal of the used equipment.  
CAUTION  
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper  
disposal, contact your local recycling/reuse or hazardous waste center.  
Updating the Firmware  
To keep the firmware updated with the latest improvements and  
benefits, visit www.powerware.com often for updates. You can download  
the latest firmware version and the instructions for installing it.  
Replacing the Power Xpert Gateway Series 1000 Card  
The card can be replaced easily without turning the EMS−UGK off or  
disconnecting the load. Follow the instructions included with the card. If  
the optional conduit box is installed:  
1. Remove the front plate on the right conduit box. Retain the plate  
and screws for later reinstallation.  
2. Remove the card cover plate at the bottom right of the right conduit  
box. Retain the plate and screws for later reinstallation.  
3. Follow the instructions included with the card to remove the old  
card, replace with the new card, and verify operation.  
4. Reinstall the card cover plate and front plate.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
MAINTENANCE  
Rewiring and Reconfiguring the Installation  
DANGER  
This EMS−UGK contains LETHAL VOLTAGES. All repairs and service should be performed  
by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE  
PARTS inside the EMS−UGK.  
WARNING  
S
S
Only qualified service personnel (such as a licensed electrician) shall perform the  
electrical installation. Risk of electrical shock.  
Always follow all personal protective equipment (PPE) and other safety rules when  
working around electricity.  
To rewire and reconfigure the EMS−UGK:  
CAUTION  
Before rewiring the EMS−UGK, disconnect the load and shut down the host equipment. Refer  
to the user’s guide for the host equipment for shutdown instructions.  
1. Depending on the rewiring involved, follow the appropriate  
harness and CT connections. Observe all warnings and cautions  
associated with the installation steps.  
2. For each updated connection, reconfigure the appropriate settings  
in the EMS−UGK using the supplied software configuration tool, a  
web page interface, the Advanced Metering monitoring system, or  
(if the optional display is installed) directly through the display. See  
3. Activate the reset switch on the bottom of the electronics module:  
hold the switch for 10 seconds or until the display (if installed) turns  
off, then release the switch.  
4. Verify the rewired and reconfigured installation operates as  
intended.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 6  
Specifications  
Table 12. Dimensions and Weight  
Component  
Weight  
Dimensions (WxHxD)  
Electronics module  
(dual panel with display)  
377 284 118 mm  
8.2 kg (18 lb)  
(14.8" 11.2"  4.6")  
Electronics module  
(dual panel without display)  
377 284 113 mm  
7.7 kg (17 lb)  
(14.8" 11.2"  4.5")  
128 287 113 mm  
Conduit box (each side)  
Mounting bracket  
1.6 kg (3.6 lb)  
1.5 kg (3.4 lb)  
(5.0" 11.3" 4.5")  
See Note 2  
Harnesses (each):  
Branch circuit  
Voltage  
0.7 kg (1.6 lb)  
0.4 kg (0.8 lb)  
0.2 kg (0.4 lb)  
Ċ
Main input  
Split−core CTs (each):  
Branch, 75A  
Branch, 100A  
0.07 kg (0.15 lb)  
0.10 kg (0.22 lb)  
0.71 kg (1.56 lb)  
0.51 kg (1.13 lb)  
Ċ
Ċ
Main, 400A  
Input ground, 100A  
Advanced Metering external cables  
0.9 kg (2 lb)  
NOTE 1 Weight varies depending on installed options.  
NOTE 2 Weights and dimensions for electronics module include mounting bracket but do not include connectors or  
reset switch. Dimensions vary depending on installed options.  
Table 13. Communication Options  
X−Slot Communication Bay  
Serial Port  
Power Xpert Gateway Series 1000 Card  
DB−9 (RS−232)  
Signal Inputs  
(4) programmable inputs (signal and signal return)  
for indicating building alarms or other use  
NOTE Signal only (at 17 mA); action power must be supplied externally.  
Relay Output Contacts  
(1) relay output for indicating alarm condition present  
NO and NC relay contacts are rated at 8A at 32 Vdc or less, derate to 1A at 60 Vdc.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SPECIFICATIONS  
Table 14. Electrical Input  
Nominal Voltage  
EMS−UGK−LV: 208/120V  
EMS−UGK−HV: 380/220V, 400/230V, 415/240V  
Nominal Frequency (Range)  
Input Conductor Configuration  
50/60 Hz (45–65 Hz)  
Panel 1: 3 wire + N + Gnd  
Panel 2: 3 wire + N  
Current Rating  
0.29A  
Table 15. Environmental and Safety  
Operating Temperature  
0°C to 40°C (32°F to 104°F)  
−55°C to 85°C (−67°F to 185°F)  
Nonoperating Temperature  
Relative Humidity  
0–95% noncondensing  
Operating Altitude  
Up to 2,000 meters (6,600 ft) above sea level  
Up to 12,200 meters (40,000 ft) above sea level  
<45 dB, excluding alarms  
Nonoperating Altitude  
Acoustical Noise  
EMI Suppression  
FCC 47, part 15, for Class A devices  
Electrostatic Discharge (ESD)  
IEC 61000−4−2  
Up to 8 kVA pulse without damage and no adverse effect to critical load  
Agency Markings  
UL 61010−1, CSA C22.2 No. 61010−1, CE Mark, IEC 61010−1:2001−02  
Installation Category  
Installation Category III  
For measurements performed in the building installation on equipment such as  
panelboards, circuit breakers, wiring, and like equipment.  
Table 16. Display (Optional)  
Interface  
Backlit LCD panel with 8 lines by 40 characters (approximately 64 240 pixels),  
4 LED indicators, and 5 pushbuttons  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS  
Table 17. Metering  
Panel Monitoring Rating  
Maximum 400A  
CT1, CT2, CTM connections: 240V CAT III  
V1, V2 connections: 208V CAT III for EMS−UGK−LV, 415V CAT III for EMS−UGK−HV  
Monitors up to 84 individual branch circuit breakers (two 42−circuit panels)  
Fully calibrated at the factory  
Branch Circuits  
Calibration  
Clock  
Real Time Clock (RTC) with one−second resolution, automatic leap year adjustment,  
and one month backup time  
Sampling Frequency  
Current Accuracy  
Voltage Accuracy  
Current and voltage for each breaker sampled 2000 times per second with a  
bandwidth of 1 KHz  
Main input: 2% from 10–100% of full range  
Branch circuit: 5% from 10–100% of full range  
2%  
Blinding Thresholds  
(zeroing of low meters)  
Panel breakers: 1/16 of breaker rating  
Main current: <6A  
Neutral current (installed Neutral CT): <6A  
Neutral current (calculated Neutral): <15A  
THD alarming: Phase current <20% of maximum phase current rating  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 7  
Troubleshooting  
Typical Alarms and Conditions  
The following table describes typical alarms and conditions for the  
EMS−UGK. For further help, please contact the Help Desk.  
To silence the horn, press any button.  
To view the active alarms or alarm history, select EVENTS on the  
optional display, then ACTIVE EVENTS or HISTORY.  
If the optional display is not installed, view the data through your  
communication interface.  
Alarm or Condition  
Possible Cause  
Action  
The EMS−UGK appears  
frozen or locked up.  
Need to cycle power.  
Activate the reset switch on the bottom of the  
electronics module: hold the switch for 10 seconds  
or until the display (if installed) turns off, then  
release the switch.  
Service and Support  
If you have any questions or problems with the EMS−UGK, call your  
Local Distributor or the Help Desk at one of the following telephone  
numbers and ask for an EMS−UGK technical representative:  
United States:  
Canada:  
1−800−356−5737 or 1−919−870−3149  
1−800−461−9166 ext 260  
Call your local service representative  
All other countries:  
Please have the following information ready when you call for service:  
S Model number  
S Serial number  
S Date of failure or problem  
S Symptoms of failure or problem  
S Customer return address and contact information  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TROUBLESHOOTING  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 8  
Warranty  
Limited Factory Warranty  
Powerware Energy Management System (EMS) Upgrade Kit  
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware  
Corporation (ꢀEaton").  
LIMITED WARRANTY: This limited warranty (ꢀWarranty") applies only to the original end−user (ꢀEnd−User") of the  
Powerware EMS Upgrade Kit (ꢀProduct") and cannot be transferred. This Warranty applies even in the event that  
the Product is initially sold by Eaton for resale to an End−User.  
LIMITED WARRANTY PERIOD: The period covered by this Warranty for Product installed [and currently located] in  
the fifty (50) United States and the District of Columbia is twelve (12) months from the date of Product shipment for  
parts replacement. The period covered by this Warranty for Product installed [and currently located] outside of the  
fifty (50) United States and the District of Columbia is twelve (12) months from the date of Product shipment for  
parts replacement.  
WHAT THIS LIMITED WARRANTY COVERS: The warrantor warrants that the Powerware EMS Upgrade Kit and  
Eaton−provided accessories (individually and collectively, "Warranted Items") are free from defects in material and  
workmanship. If, in the opinion of Eaton, a Warranted Item is defective and the defect is within the terms of this  
Warranty, Eaton’s sole obligation will be to repair or replace such defective item (including by providing service,  
parts, and labor, as applicable), at the option of Eaton. Any parts that are replaced may be new or reconditioned. All  
parts replaced by Eaton shall become the property of Eaton. The End−User shall return the defective part or parts to  
a location specified by Eaton.  
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages  
caused by: (a) failure to properly store the Product before installation; (b) shipping and delivery of the Product if  
shipping is FOB Factory; (c) neglect, accident, fire, flood, lightning, vandalism, acts of God, End−User’s neglect,  
abuse, misuse, misapplication, incorrect installation; (d) repair or alteration not authorized in writing by Eaton  
personnel or performed by an authorized Eaton Customer Service Engineer or Agent; or (e) improper testing,  
operation, maintenance, adjustment, or any modification of any kind not authorized in writing by Eaton personnel or  
performed by an authorized Eaton Customer Service Engineer or Agent.  
This Warranty is not valid: (a) if the Product is moved to a new location by someone other than an authorized Eaton  
Customer Service Engineer (in the USA) or Agent (outside of the USA); or (b) if the Product’s serial numbers have  
been removed or are illegible. Any Warranted Items repaired or replaced pursuant to this Warranty will be warranted  
for the remaining portion of the original Warranty subject to all the terms thereof. Labor warranty is not provided.  
Any equipment, parts, or materials included in the Product and not manufactured by Eaton are warranted solely  
by the manufacturer of such equipment, parts, or materials and are not included as part of this Warranty.  
THIS WARRANTY IS THE END−USER’S SOLE REMEDY AND IS EXPRESSLY IN LIEU OF, AND THERE ARE NO OTHER  
EXPRESSED OR IMPLIED GUARANTEES OR WARRANTIES (INCLUDING ANY IMPLIED WARRANTY OF  
MERCHANTABILITY OR FITNESS FOR ANY PURPOSE, WHICH ARE EXPRESSLY DISCLAIMED).  
LIMITATION OF LIABILITY: In no event shall Eaton be liable for any indirect, incidental, special, or consequential  
damages of any kind or type whatsoever, or based on any claim or cause of action, however denominated. Eaton  
shall not be responsible for failure to provide service or parts due to causes beyond Eaton’s reasonable control. In  
no case will Eaton’s liability under this Warranty exceed the replacement value of the Warranted Items.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
WARRANTY  
END−USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End−User must use the Product  
in a normal way, follow the Product’s user’s guide, and protect against further damage to the Product if there is a  
covered defect.  
OTHER LIMITATIONS: Eaton’s obligations under this Warranty are expressly conditioned upon receipt by Eaton of  
all payments due to it (including interest charges, if any). During such time as Eaton has not received payment of  
any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Eaton  
shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run  
and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts.  
COSTS NOT RELATED TO WARRANTY: The End−User shall be invoiced for, and shall pay for, all services not  
expressly provided for by the terms of this Warranty. Any costs for replacement equipment, installation, materials,  
freight charges, travel expenses, or labor of Eaton representatives outside the terms of this Warranty will be borne  
by the End−User.  
OBTAINING WARRANTY SERVICE: In the USA, call the Eaton Customer Reliability Center 7x24 at 800−843−9433.  
Outside of the USA, call your local Eaton sales or service representative, or call the Eaton Customer Reliability  
Center in the USA at 919−870−3028. For comments or questions about this Limited Factory Warranty, write to the  
Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.  
EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*1642017241*  
164201724 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Philips Clock Radio AJ3150 39 User Manual
Philips Portable DVD Player PET748 User Manual
Pioneer Stereo System HTS 260 User Manual
Planar Flat Panel Television XP17WSA User Manual
Poulan Lawn Mower 157257 User Manual
Poulan Trimmer 530088894 User Manual
Premier Mounts TV Mount PSM 402F User Manual
Profoto Portable Generator Pro B2 User Manual
ProSpot Fitness Fitness Equipment HG 5 User Manual
Proxim Webcam CPN 65755B User Manual