LOW NOx TURBOPOWER® • PACKAGED WATER HEATER
NICKELSHIELD® NICKEL-PLATED STORAGE TANK
TANK SERIES 600 GALLONS VERTICAL
Min. Inlet
Flow Gas
Pressure
" W.C. d
Dimensions
(inches)
Blower
Motor
Shipping
Weight
#
Recovery gph c
MODEL
NUMBER
INPUT
Btu/h
SCAQMD Energy
Model No.
40° - 120°F 40° - 140°F
A
B
C
HP
Amps
1000 N 600A-TPL
1500 N 600A-TPL
1000
1500
800
1200
800,000
1,200,000
4.5.
4.5
8TPL
12TPL
800 MBtu/h
1200 MBtu/h 41
33
8
8
1
1/2
1
7
14
2430
2710
1-1/4
c Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.
d With standard gas train
* The information presented is for natural gas 0.6 S.G.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see form #PV 6452.
STANDARD GAS PRESSURE REQUIREMENTS:
SEE TABLE FOR MINIMUM PRESSURE BY MODEL.
MAXIMUM STATIC INLET GAS PRESSURE IS 10.5" W.C.
STANDARD ELECTRICAL REQUIREMENTS:
VOLTAGE: 120V, 1Ø, 60 HZ., 20 AMPS.
OTHER VOLTAGES REQUIRE AN EXTERNAL
STEPDOWN TRANSFORMER.
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,
CONTACT YOUR PVI REPRESENTATIVE.
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND
SPECIFICATION WITHOUT NOTICE.
VENTING REQUIREMENTS:
-.02" TO -.06" W.C. (NEGATIVE PRESSURE).
TYPE B VENTING.
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON
THE VENT CONNECTION DIAMETER EXCLUSIVELY. CHECK
NATIONAL FUEL GAS CODE UNDER "FAN ASSISTED."
Product is patented in the U.S., Canada, and Mexico.
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
PV 6529 02/25/04
Download from Www.Somanuals.com. All Manuals Search And Download.
|