Patterson Kelley Boiler MACH 05 User Manual

MACH-05  
PATTERSON-KELLEY  
MACH SERIES BOILER  
GAS-FIRED BOILER  
C.S.A Design-Certified  
Complies with ANSI Z21.13/CSA 4.9  
Gas-Fired Low Pressure Steam and Hot Water  
Boilers  
ASME Code, Section IV  
Certified by Patterson-Kelley  
C.S.A Design-Certified  
Complies with ANSI Z21.13/CSA 4.9  
Gas-Fired Low Pressure Steam and Hot Water  
Boilers  
Installation Date: _______________________  
100 Burson Street, P.O. Box 458,  
East Stroudsburg, PA 18301  
Telephone: (877) 728-5351, Facsimile: (570) 476-7247  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Table of Contents  
3.6.11 Intake Duct Connection to Boiler .........12  
3.6.12 Intake Duct Terminations.....................12  
3.6.13 Vent Elbows.........................................13  
3.7 Gas Piping.......................................................13  
3.7.1 Gas Supply Piping by Installer...............14  
3.8 Boiler Water Piping..........................................14  
3.8.1 Piping Design.........................................14  
3.8.2 Boiler Inlet and Outlet Connections .......15  
3.8.3 Boiler Water Piping by Installer..............16  
3.8.4 Flushing and Filling................................16  
3.9 Burner and Ignition System.............................17  
3.9.1 Inspection...............................................17  
3.10 Pre-Start Check List ......................................18  
3.11 Safety Checks ...............................................18  
3.11.1 Test of Ignition Safety System .............18  
3.11.2 Test of Low Water Cut-out...................19  
3.11.3 Test of High-Limit Control ....................19  
3.11.4 Test of Gas Pressure Switch ...............19  
3.12 Initial Adjustments .........................................20  
3.12.1 Operating Temperature Controller.......20  
3.12.2 Gas Pressure Adjustment....................24  
3.12.3 Air Flow Adjustments ...........................25  
3.12.4 Gas Valve Setup and Adjustment........25  
4.0 OPERATION ............................................28  
4.1 General............................................................28  
4.1.1 Control Panel Front................................28  
4.1.2 Tests ......................................................28  
4.2 Normal Lighting and Shut-Down Procedures..28  
4.2.1 Lighting Procedures...............................28  
4.2.2 Normal Shut Down Procedures .............28  
4.2.3 Emergency Shut-Off ..............................29  
4.3 Typical Boiler Operating Conditions................29  
5.0 MAINTENANCE .......................................30  
5.1 Maintenance and Inspection Schedule ...........30  
5.1.1 Daily .......................................................30  
5.1.2 Weekly ...................................................30  
1.0 INTRODUCTION ........................................1  
2.0 SAFETY......................................................1  
2.1 General..............................................................1  
2.2 Training..............................................................1  
2.3 Safety Features .................................................1  
2.4 Safety Labels.....................................................2  
2.5 Safety Precautions ............................................2  
2.5.1 Electrical Hazards ....................................2  
2.5.2 Burn, Fire, and Explosion Hazards ..........2  
2.5.3 Crush Hazards .........................................3  
2.5.4 Chemical Hazards....................................3  
2.5.5 Pressure Hazards ....................................4  
2.5.6 Slip, Fall Hazards.....................................4  
3.0 INSTALLATION..........................................5  
3.1 Receiving and Storage ......................................5  
3.1.1 Initial Inspection .......................................5  
3.1.2 Storage Prior to Installation......................5  
3.2 Compliance with Codes.....................................5  
3.3 Setup .................................................................5  
3.3.1 Foundation ...............................................5  
3.3.2 Placement ................................................5  
3.3.3 Clearances...............................................6  
3.4 Electrical Connections.......................................6  
3.5 Combustion Air ..................................................7  
3.5.1 Air Inlet Requirements..............................7  
3.6 Flue Venting.......................................................8  
3.6.1 Barometric Damper..................................8  
3.6.2 Flue Connection.......................................8  
3.6.3 Required Clearances ...............................8  
3.6.4 Vent Terminations....................................9  
3.6.5 Venting for Multiple Boilers ......................9  
3.6.6 Sealed Combustion Air/Venting System 10  
3.6.7 Removing an Existing Boiler..................10  
3.6.8 Intake/Exhaust Layout ...........................10  
3.6.9 Intake Duct Materials and Sizes: ...........12  
3.6.10 Sealing the Intake Duct........................12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Table of Contents  
5.1.3 Monthly (During Operation)....................30  
5.1.4 Semi-Annually (every 6 months)............31  
5.1.5 Annually .................................................31  
5.2 Cleaning the Burner.........................................31  
5.3 After All Repairs or Maintenance.....................31  
5.4 Sequence of Operation....................................32  
5.5 Troubleshooting...............................................32  
5.5.1 Manual Reset Service Codes ................34  
5.5.2 Auto-reset Service Codes......................35  
6.0 PARTS/TECHNICAL SUPPORT..............36  
6.1 Wiring Diagrams..............................................37  
6.1.3 Wiring Series C-450...............................40  
6.1.4 Wiring Series C-750/900/1050...............41  
6.2 Boiler Parts List ...............................................42  
6.2.1 Main Assembly.......................................42  
6.2.2 Control Panel .........................................43  
6.2.3 Display Panel.........................................44  
6.2.4 C-300/450 Heat Engine .........................45  
6.2.5 C-750/900/1050 Heat Engine ................46  
6.2.6 C-300 Boiler Gas Train ..........................47  
6.2.7 C-450 Boiler Gas Train ..........................48  
6.2.8 C-750/900/1050 Boiler Gas Train..........49  
7.0 LIMITED WARRANTY .............................50  
8.0 APPENDIX ...............................................52  
6.1.1 Terminal Block Assignments – High Voltage  
Circuit (TB2)...............................................37  
6.1.1a Terminal Block Assignments – Low Voltage  
Circuit (TB1)...............................................38  
6.1.2 Wiring Series C-300...............................39  
!
WARNING  
WARNING!  
Improper use may  
result in fire or injury.  
Read instructions/safety  
manual before installing,  
operating or servicing boiler.  
Chemicals, fuels, or other potentially hazardous  
or toxic materials must not be stored in the same  
room as the boiler.  
c
1998 HCS, Inc. 800-748-0241  
Reorder No. 6020-V2WHPK  
WARNING!  
It is essential to read, understand, and follow the  
recommendations of this manual before installing,  
operating, or servicing this equipment. Failure to  
do so could result in fire or explosion and serious  
injury, death, and/or property damage.  
WARNING!  
Installation and service must be performed by a  
qualified installer or service agency who has been  
trained on the Patterson-Kelley MACH Boiler.  
What to do if you smell gas:  
The same features which permit this boiler to achieve  
high-efficiency performance make it unlike most other  
boilers of this general size, so it is important to  
understand how this boiler operates.  
Do not try to light any appliance.  
Do not touch any electrical switch.  
Do not use any phone in your building.  
Immediately call your gas supplier from a  
neighbor's phone. Follow the gas supplier's  
instructions.  
WARNING  
If you cannot reach your gas supplier call the fire  
department.  
Do not store or use gasoline or other flammable  
vapors or liquids in the vicinity of this or any other  
appliance.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Safety  
Operated and serviced in accordance with a  
1.0 INTRODUCTION  
comprehensive safety program determined and  
established by the customer. Do not attempt to  
operate or service until such a program has been  
established.  
The P-K MACH® Series Gas-Fired Boilers are fully  
modulating using a variable speed combustion blower,  
sophisticated microprocessor controls, modulating gas  
safety shut off / control valves and a unique aluminum  
alloy heat exchanger capable of operating in a fully  
condensing mode to provide maximum efficiency in a  
minimum amount of space. The high-quality materials  
and thoroughly tested design of the boiler should  
provide years of trouble-free service if the instructions  
in this manual are followed carefully.  
Operated and serviced by qualified, properly  
trained personnel in accordance with all applicable  
codes, laws, and regulations.  
Note: Each safety device must be maintained and  
checked per the recommended schedule; refer to  
Section 5.1 of this manual.  
This manual covers installation of P-K MACH Series  
Boilers. The model numbers may be followed by a  
prefix or suffix letter in some cases to indicate special  
features or different options.  
2.2 TRAINING  
While details may differ slightly, basic operation is the  
same for all models. Boilers may be built to operate  
with natural gas or liquefied petroleum gas (propane).  
Check the rating plate for correct fuel usage and gas  
pressures.  
!
WARNING  
Improper use may  
result in fire or injury.  
Read instructions/safety  
manual before installing,  
operating or servicing boiler.  
c
1998 HCS, Inc. 800-748-0241  
Reorder No. 6020-V2WHPK  
It is essential to read, understand, and follow the  
recommendations of this manual before installing,  
operating, or servicing this equipment. Failure to do  
so could result in property damage, serious injury, or  
death.  
The boiler is only a part of the complete heating  
system. This boiler may be fully operational and yet  
because of poor circulation, control, or other operating  
characteristics, not deliver heat to the desired location.  
Additional equipment such as temperature sensors,  
pumps, flow switches, balancing valves, and check  
valves will be required for satisfactory operation of  
any system. Patterson-Kelley cannot be responsible  
for the design or operation of such systems and a  
qualified engineer or contractor must be consulted.  
Proper training is the best protection against accidents.  
Operating and service personnel must be thoroughly  
familiar with the basic construction of the P-K MACH  
Series boiler, the use and locations of the controls, the  
operation of the boiler, adjustment of its various  
mechanisms, and all applicable safety precautions. If  
any of the provisions of this manual are not fully and  
completely understood, contact the Patterson-Kelley  
Sales Department toll-free at (877) 728-5351 for  
assistance.  
2.0 SAFETY  
2.1 GENERAL  
The MACH Series gas-fired boiler must be:  
2.3 SAFETY FEATURES  
Installed, operated, and serviced in accordance  
with instructions contained in this manual.  
It is the responsibility of the customer to maintain the  
safety features, such as: guards, safety labels, safety  
controls, interlocks, lockout devices, etc., in place and  
operable.  
Installed by qualified personnel in accordance with  
designs prepared by qualified facility engineers  
including: structural, mechanical, electrical, and  
other applicable disciplines.  
Page 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Safety  
2.4 SAFETY LABELS  
2.5.2 Burn, Fire, and Explosion Hazards  
NOTE  
When opening leak test valves,  
always follow instructions in  
operation and safety manual.  
c
1998 HCS, Inc. 800-748-0241  
1998 HCS, Inc. 800-748-0241  
1998 HCS, Inc. 800-748-0241  
Reorder No. 8032-01NHPK  
General Warning  
Hot Surface  
!
WARNING  
Improper use may  
result in fire or injury.  
Read instructions/safety  
manual before installing,  
operating or servicing boiler.  
!
WARNING  
Improper use may  
result in fire or injury.  
Read instructions/safety  
manual before installing,  
operating or servicing boiler.  
c
Reorder No. 6020-V2WHPK  
c
1998 HCS, Inc. 800-748-0241  
Reorder No. 6020-V2WHPK  
!
WARNING  
Electrical hazard.  
Follow lockout/tagout  
procedure when  
NOTE  
Make sure this union is  
tight before closing cabinet  
cover after servicing boiler.  
servicing this boiler.  
C
Reorder No. 5025-V1WHPK  
c
1998 HCS, Inc. 800-748-0241  
Reorder No. 8032-02NHAK  
NOTE  
The safety labels shown above are affixed to your  
boiler. Although the labels are of high quality, they  
may become dislodged or unreadable over time.  
Contact Patterson-Kelley toll-free at (877) 728-5351  
for replacement labels.  
When opening leak test valves,  
always follow instructions in  
operation and safety manual.  
c
1998 HCS, Inc. 800-748-0241  
Reorder No. 8032-01NHPK  
Burn, fire, and explosion hazards! Installation  
must be in strict conformance to all applicable  
codes and standards including NFPA 54, ANSI  
Z223.1 and CAN/CGA B.149. Install all required  
vent lines for gas devices. Refer to Section 3.7.1.  
2.5 SAFETY PRECAUTIONS  
Provide a suitable location for the boiler, away from  
normal personnel traffic, with adequate working space,  
adequate clearances, proper ventilation and lighting,  
with a structure sufficiently strong and rigid to support  
the weight of the boiler, all piping, and accessories.  
Hazard from incorrect fuels! Possible fire,  
explosion, overheating, and damage. Do not use  
any fuels except the design fuels for the unit.  
Overfire hazards! High pressure in gas or propane  
supply could result in overfiring of other devices  
supplied from the same source.  
Fire and explosion hazards! Close the main gas  
shutoff before servicing boiler.  
2.5.1 Electrical Hazards  
Fire and explosion hazards! Do not store or use  
gasoline or other flammable vapors or liquids in  
the vicinity of this or any other gas fired appliance.  
!
WARNING  
Electrical hazard.  
Follow lockout/tagout  
procedure when  
servicing this boiler.  
Burn hazard! Possible hot surfaces. Do not touch  
gas vent during firing operation. Use only factory  
recommended vent components.  
C 1998 HCS, Inc. 800-748-0241  
Reorder No. 5025-V1WHPK  
Shock hazard! Properly lockout/tagout the  
electrical service and all other energy sources  
before working on or near the boiler.  
Burn hazard! Pipes, vents, and boiler components  
could be hot. Do not touch piping or stack  
surfaces during operation or immediately after  
shutdown of the boiler.  
Shock hazard! Do not spray water directly on any  
electrical components.  
Page 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Safety  
2.5.3 Crush Hazards  
Burn hazard! Hot fluids. Use caution when  
servicing or draining boiler.  
Fire and explosion hazards! Use caution when  
servicing burner. Propane (LPG) is heavier than  
air and may linger in the combustion chamber,  
vent lines, or elsewhere.  
General Warning  
Gas leak hazard! Make sure the burner is installed  
correctly and burner hood is securely fastened  
following any maintenance performed on them.  
These connections cannot be tested after the  
burner is assembled.  
Lifting hazards! Use properly rated lifting  
equipment to lift and position the boiler. The load  
is unbalanced. Test balance before lifting 3 ft.  
above the floor. Do not allow personnel beneath  
the lifted load. Refer to approximate weights in  
the table below:  
Gas leak hazard! All threaded gas connections  
must be made using a pipe compound that is  
resistant to liquefied petroleum. Do not use  
Teflontape on threaded gas piping.  
Boiler Size  
300,000 Btu  
450,000 Btu  
750,000 Btu  
900,000 Btu  
1,050,000 Btu  
Weight in Pounds  
354  
440  
650  
700  
750  
Gas leak hazard! Check entire gas train for leaks  
after installation. If there is a smell of gas, shut  
down the boiler and obtain immediate assistance  
from trained service personnel and/or your local  
fire department.  
Overfire hazard! Possible fire and explosion from  
excess gas pressure. Make sure that gas inlet  
pressure does not exceed 14 inches W.C. to the  
regulator.  
Bump hazard from overhead ductwork and piping.  
Install components with adequate vertical  
clearance.  
Overfire hazard! Possible fire and explosion.  
Possible malfunction of regulators and/or gas  
safety shut off / control valves. Maintain all gas  
train components in good condition. Do not alter  
wiring connections. Annual inspection by factory-  
trained personnel for proper set-up and operation  
is recommended.  
2.5.4 Chemical Hazards  
Overfire and underfire hazards! Possible fire,  
explosion, overheating, and component failure.  
Do not attempt to adjust firing rate of the boiler.  
The firing rate must be adjusted only by factory  
trained personnel.  
General Warning  
Chemical hazards from cleaning products. Use  
caution when cleaning the system. The use of  
professional assistance is recommended. Use safe  
procedures for the disposal of all cleaning  
solutions.  
Combustion Condensate – a pH of approximately  
4 to 5 can be expected. Use PVC or CPVC piping.  
Collection and disposal must be in accordance  
with all applicable regulations.  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Safety  
2.5.5 Pressure Hazards  
2.5.6 Slip, Fall Hazards  
!
!
WARNING  
WARNING  
Improper use may  
Improper use may  
result in fire or injury.  
result in fire or injury.  
Read instructions/safety  
manual before installing,  
operating or servicing boiler.  
Read instructions/safety  
manual before installing,  
operating or servicing boiler.  
c
c
1998 HCS, Inc. 800-748-0241  
1998 HCS, Inc. 800-748-0241  
Pressure hazard! Hot fluids. Install isolation  
valves on boiler water inlet and outlet. Make sure  
isolation valves are closed before servicing boiler.  
Tripping hazard! Do not install piping on floor  
surfaces. Maintain clear path around boiler.  
Slip and fall hazard! Use drip pan to catch water  
while draining the boiler. Maintain dry floor  
surfaces.  
Pressure hazard! Hot fluids. Annually test safety  
relief valve for proper operation. Do not operate  
boiler with faulty relief valve.  
Slip and fall hazard! Do not locate intake or  
exhaust terminations directly above a walkway;  
dripping of condensation can cause icing of the  
walking surface.  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
Code, Section IV for 50 psig maximum operating  
pressure and/or 200º F maximum temperature.  
3.0 INSTALLATION  
Other codes or approvals which apply will be labeled  
on the boiler.  
3.1 RECEIVING AND STORAGE  
Installation of the boiler must conform to all the  
requirements of all national, state and local codes  
established by the authorities having jurisdiction or,  
in the absence of such requirements, in the U.S. to the  
National Fuel Gas Code, ANSI Z223.1/NFPA 54,  
latest edition. In Canada, the equipment shall be  
installed in accordance with the current Installation  
Code for Gas Burning Appliances and Equipment,  
CAN/CGA-B.149, and applicable Provincial  
3.1.1 Initial Inspection  
Upon receiving the boiler, inspect it for signs of  
shipping damage. Since some damage may be hidden,  
we recommend unpacking the boiler and removing the  
top cover and inspecting the boiler.  
Verify that the total number of pieces shown on the  
packing slip agrees with those actually received.  
Regulations for the class, which should be carefully  
followed in all cases. Authorities having jurisdiction  
should be consulted before installations are made.  
Important: note any damage, suspected potential  
damage, or shortage of materials on the freight bill  
and immediately notify the carrier. File all claims  
for shortage or damage with the carrier. Claims  
for hidden damages must be filed with your carrier  
within 7 days. The boiler carton is equipped with a  
“Tip (N) Tell”. If "Tip (N) Tell” arrow point is  
blue, that indicates that the package has been on its  
side or tipped over in transit.  
Where required by local codes, the installation must  
conform to American Society of Mechanical  
Engineers Safety Code for Controls and Safety  
Devices for Automatically Fired Boilers (ASME  
CSD-1).  
In the Commonwealth of Massachusetts (a) this unit  
must be installed by a licensed pipe fitter / plumber,  
(b) field installed gas cocks must be “T” handle type,  
and (c) piping of condensate shall conform with the  
State Plumbing Code.  
3.1.2 Storage Prior to Installation  
If the boiler is not installed immediately, it must be  
stored in a location adequately protected from the  
weather, preferably indoors. If this is not possible,  
then it should remain in the shipping container and be  
covered by a tarpaulin or other waterproof covering.  
3.3 SETUP  
Note: controls and other equipment that are  
damaged or fail due to weather exposure are not  
covered by warranty.  
3.3.1 Foundation  
Provide a firm, level foundation, preferably of  
concrete.  
Note: The boiler may be installed on a combustible  
floor; however, the boiler must never be installed on  
carpeting.  
3.2 COMPLIANCE WITH CODES  
The P-K MACH Series Boiler with standard  
components and with many options complies with  
American National Standard/CSA Standard ANSI  
Z21.13/CSA 4.9, latest edition, Gas-Fired Low  
Pressure Steam and Hot Water Boilers.  
3.3.2 Placement  
The boiler must be level to function properly. To  
assist in leveling the boiler, the four (4) adjustable leg  
bolts (1/2"- 13 NC) must be installed. The adjustable  
legs are also necessary to provide adequate floor  
The heat exchanger is constructed and stamped in  
accordance with ASME Boiler and Pressure Vessel  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
clearance and prevent distortion of the cabinet,  
(twisting, etc.) in addition to leveling.  
D
D
Adjustable  
Leg Bolts  
Minimum Clearances from Adjacent Walls, Ceiling, and  
Obstructions  
Type of Surface  
Dimensions (inches)  
Adjustable Legs for Leveling and Floor Clearance  
A
B
24  
*
C†  
24  
24  
D
24  
Combustible Surfaces  
36  
36  
3.3.3 Clearances  
Non-combustible Surfaces  
24**  
If the boiler is to be installed near combustible  
surfaces, the minimum clearances shown in the table  
below must be maintained.  
† "C" Do not put pipes, ducts, etc. in this area above  
the boiler.  
Failure to provide for the service access clearances,  
even with non-combustible surfaces, may cause future  
problems servicing the boiler.  
CAUTION!  
Bumping hazard from overhead ducts! Install all  
components with adequate vertical clearances.  
The boiler must be installed in a space large in  
comparison to the boiler as described in Section 6.3 of  
the National Fuel Gas Code, ANSI Z223.1, latest  
edition.  
* Clearance depends upon vent configuration.  
** Service access need be only on one side of a  
boiler or row of boilers. Boilers may be installed  
immediately adjacent to each other. However, P-K  
recommends this clearance between each boiler  
when there is insufficient access at the rear to allow  
for service and adjustment.  
No pipes,  
ducts, etc. in  
this area.  
C
A
B
3.4 ELECTRICAL CONNECTIONS  
The boiler is wired for 120 volts, single phase, 60  
hertz. The total operating amperage is indicated on  
the rating nameplate. All MACH units require less  
than 8 amps. Before starting the boiler, check to  
ensure that the proper electrical service is connected  
to the boiler.  
Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
An external electrical disconnect (not supplied with  
the boiler) with adequate overload protection is  
required. The boiler must be grounded in accordance  
with local codes or in the absence of such  
requirements, in the U.S. with National Electrical  
Codes, ANSI/NFPA No. 70 latest edition and in  
Canada to the current Canadian Electrical Code, Part I,  
CSA C22.1.  
when burned, form acids which quickly attack the  
boiler and the boiler stack. The result is improper  
combustion and premature boiler failure.  
Provisions for combustion and ventilation air must be  
in accordance with Section 5.3, Air for Combustion  
and Ventilation, of the National Fuel Gas Code,  
ANSI Z223.1, latest edition, or applicable provisions  
of the local building codes. In Canada, combustion  
air openings shall comply with CSA B.149  
Installation Code. The formula is 1 sq. in. per 1,000  
Btu/hr of gas input not less than 100 sq. in. The  
location shall be neither more than 18", nor less than  
6" above the floor level.  
Note: A dedicated earth ground (green wire) is  
required to avoid nuisance shutdowns. Do not ground  
through the conduit. It is also important that proper  
polarity be maintained.  
Note: Refer to Terminal Block Assignments (Section  
6.1.1).  
The boiler room shall be provided with two openings  
to ensure adequate combustion air and proper  
ventilation. One opening should be 6 to 12 inches  
above the floor and the other 6 to 12 inches below the  
ceiling, preferably on opposite walls. The size of  
each opening is determined by whether air is taken  
from inside or outside the building. In Canada,  
ventilation air openings shall be at least 10% of the  
cross sectional area required for combustion air, but  
not less than 10 square inches. It is to be located at  
the highest practical point communicating with  
outdoors.  
Low Voltage  
Control Junction  
120 Volt  
Electrical Control  
Box  
Junction Box  
WARNING!  
Under no circumstances shall the boiler room  
ever be under a negative pressure. Particular  
care should be taken when exhaust fans,  
compressors, air-handling units or other  
equipment may rob air from the boiler.  
Electrical Connections at Rear of Boiler  
3.5 COMBUSTION AIR  
3.5.1 Air Inlet Requirements  
Combustion air must be free from dust, lint, etc. The  
presence of such materials in the air supplied to the  
burner could cause nuisance "Low Air" shutdowns or  
premature burner failure. The boiler should not be  
operated during construction while the possibility of  
drywall dust, demolition dust, etc. exists.  
If air is taken directly from outside the building, each  
opening (minimum of two) should have a net free  
area of 1 square inch for each 4,000 Btu per hour of  
total boiler input. For instance, 112.5 square inches  
are required for 450,000 Btu per hour input.  
The combustion air supply must be completely free of  
chemical fumes which may be corrosive when burned  
in the boiler. Common chemicals which must be  
avoided are fluorocarbons and other halogenated  
compounds, most commonly present as refrigerants or  
solvents, such as freon, trichlorethylene,  
When air is taken from the outdoors through a  
vertical duct, 1 square inch per 4,000 Btu per hour is  
required. If a horizontal duct is used, 1 square inch  
per 2,000 Btu per hour is required, i.e., 225 square  
inches for 450,000 Btu per hour input.  
perchlorethylene, chlorine, etc. These chemicals,  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
If air is taken from another interior space, each  
opening should have a net free area of 1 square inch  
for each 1,000 Btu per hour of boiler input (450 square  
inches for a 450,000 Btu per hour.)  
3.6.2 Flue Connection  
The connection from the boiler to the vent should be  
as direct as possible and the upward slope of any  
horizontal breaching should be at least 1/4 inch per  
linear foot. The 300 and 450 vent connection  
incorporates a 4° slope toward the boiler to facilitate  
pitching of the vent for condensate collection. This  
boiler should not be connected into any portion of  
another mechanical draft system operating under  
positive pressure without consulting your local  
venting representative. Provisions must be made for  
supports to prevent contact of the vent with  
combustible surfaces.  
3.6 FLUE VENTING  
This boiler requires a special vent system. This boiler  
is not certified for use with Type "B" vent.  
This boiler is Category IV (condensing – positive  
pressure) as it is defined in ANSI Z21.13/CSA 4.9,  
latest edition. The vent material must be listed  
Category IV vent pipe (316L or AL29-4C Stainless  
Steel) and comply with UL 1738 or UL103. In  
Canada it must comply with ULC-636. The exhaust  
vent can be run horizontally or vertically.  
Note: If the vent is erected directly behind the boiler,  
make sure that the weight of the vent is not  
supported by the boiler vent collar. The collar is  
not designed to support the weight of the vent.  
Structural support and spacing from combustible  
surfaces must be in accordance with the vent  
manufacturer's requirements.  
Vent installations shall be in accordance with Part 10,  
Venting of Equipment, of the National Fuel Gas Code,  
ANSI Z223.1 or CSA B.149 code, or applicable  
provisions of the local building codes.  
Sidewall  
The venting system and the horizontal portions of the  
venting system shall be supported to prevent sagging.  
Pitch toward  
boiler 1/4" per  
foot minimum.  
The vent must be sized according to the vent  
manufacturer’s recommendations. Consult your vent  
supplier for correct sizing and structural support  
requirements. Design calculations should be based on  
a maximum of 0.22" W.C. total frictional resistance in  
the stack (measured at the boiler flue gas discharge),  
with a stack temperature of 210° F (gross) and a CO2  
level of 9% (natural gas) or 10.4% (propane). These  
values are to be used for vent sizing calculations.  
4 degree slope  
toward boiler,  
approx. ¾” per  
foot.  
The installation of a bird screen on the vent  
termination is recommended. Consult your local vent  
manufacturer for proper sizing.  
Flue Connection at Boiler  
3.6.3 Required Clearances  
3.6.1 Barometric Damper  
Provide clearances between combustion air intake,  
exhaust vent, roof and wall surfaces, doors and  
window, and snow line as shown in the following  
diagrams. The exhaust vent termination must be 14  
feet above grade when located adjacent to a public  
walkway. It must also have a minimum 6 foot  
horizontal and 6 foot vertical clearance (above or  
below) any electric meters, gas meters, regulators, or  
relief equipment.  
WARNING!  
Do not use a barometric damper with this  
boiler. (This is a positive pressure system;  
combustion gas may leak into the room.)  
Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
3.6.4 Vent Terminations  
WARNING!  
Do not locate intake or exhaust terminations  
directly above a walkway; dripping of conden-  
sation can cause icing of the walking surface.  
No rain cap  
required,  
or Tee.  
Mechanical draft vent  
terminal  
Direct vent terminal  
Outside Plate  
clearance minimum 12 in.  
Cover Plate  
Fastener  
Less  
than  
10 ft.  
Centering  
Support Plate  
Sealant  
4 ft.  
min.  
4 ft.  
min.  
Recommended  
Termination  
3 ft min.  
12 in.  
min  
Sealant  
(see text below)  
12 in.  
min.  
12" min.  
12 in.  
min.  
Mechanical draft  
vent terminal  
Grade  
Vent Termination Details  
Forced  
air inlet  
The vent should extend at least three (3) feet above  
the roof, or at least two (2) feet above the highest part  
of any structure within ten (10) feet of the vent.  
Reference: ANSI Z223.1 - 2002  
Sidewall Installations  
To prevent the possible re-circulation of flue gases,  
your vent designer must take into consideration such  
things as prevailing winds, eddy zones, building  
configurations, etc. P-K can not be responsible for  
the effects such adverse conditions may have on the  
operation of the boilers. Dimensions listed above or  
those illustrated are minimum, and may or may not be  
sufficient for conditions at a specific job site.  
Flue Gas  
Outlet  
10' min.  
Combustion  
Air Inlet  
4' min.  
A tee must be of approved design and adequate  
capacity.  
4' min above  
snow line  
3.6.5 Venting for Multiple Boilers  
The venting instructions in this manual apply to a  
single boiler.  
Venting systems for multiple boilers must be  
designed by qualified professionals and verified by  
the stack manufacturer. The venting system must  
prevent backflow of exhaust gas through idle  
boilers which are not operating.  
Rooftop Installations  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
3.6.6 Sealed Combustion Air/Venting System  
3. Insofar as is practical, close all building doors  
and windows and all doors between the space in  
which the appliances remaining connected to the  
common venting system are located and other  
spaces of the building. Turn on clothes dryers  
and any appliances not connected to the common  
venting system. Turn on any exhaust fans, such  
as range hoods and bathroom exhausts, so they  
will operate at maximum speed. Do not operate a  
summer exhaust fan. Close fireplace dampers.  
The MACH Series Boilers are also certified for  
operation with a sealed combustion air and pressurized  
venting system. Such a system employs a sealed  
combustion air intake duct leading from outdoors and  
a sealed exhaust vent terminating outdoors. Air flow  
through the system is maintained by the fan inside the  
boiler assembly.  
Vent Installation Details  
4. Place the appliance being inspected in operation.  
Follow the lighting instructions. Adjust the  
thermostat so that the appliance will operate  
continuously.  
Installation must conform to the vent manufacturer's  
instructions in all respects including joining,  
clearances, fastening, fire-stopping, and other matters.  
5. Test for spillage at the draft hood relief opening  
after 5 minutes of main burner operation. Use the  
flame of a match or candle or smoke from a  
cigarette, cigar or pipe.  
Vent ductwork may be run horizontally or vertically if  
so certified.  
3.6.7 Removing an Existing Boiler  
(from a common venting system)  
6. After it has been determined that each appliance  
remaining connected to the common venting  
system properly vents when tested as outlined  
above, return doors, windows, exhaust fans,  
fireplace dampers and any other gas-burning  
appliance to their previous conditions of use.  
When an existing boiler is removed from a common  
venting system, the common venting system is likely  
to be too large for proper venting of the appliances  
remaining connected to it.  
Any improper operation of the common venting  
system should be corrected so the installation  
conforms with the National Fuel Gas Code, ANSI  
Z223.1 and CSA B149 Installation Code. When  
resizing any portion of the common venting system,  
the common vent system should be resized to  
approach the minimum size as determined using the  
appropriate tables.  
At the time of removal of an existing boiler, while the  
other appliances remaining connected to the common  
venting system are not in operation, the following  
steps should be followed with each appliance  
remaining connected to the common venting system  
placed in operation:  
1. Seal any unused openings in the common venting  
system.  
2. Visually inspect the venting system for proper size  
and horizontal pitch and determine that there is no  
blockage or restriction, leakage, corrosion or other  
deficiency which could cause an unsafe condition.  
3.6.8 Intake/Exhaust Layout  
Four basic configurations for the intake/exhaust may  
be used. Refer to Section 3.6.3 for required  
clearances for all terminations shown in the four  
following figures.  
Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
Exhaust Vent  
(Type of flue termination  
optional when roof venting.)  
Exhaust Vent (type of  
flue termination  
optional when roof  
venting.)  
Air Inlet (tee  
mounted  
horizontally.)  
Roof  
Air Inlet  
(Type of flue  
termination  
optional.)  
Roof  
Sidewall  
Sidewall Inlet, Roof Vent  
Roof Inlet and Vent  
Air Inlet  
(Type of flue  
termination optional.)  
Exhaust Vent  
(Sidewall venting requires  
vertical tee termination.)  
Exhaust Vent  
(Sidewall venting requires  
vertical tee termination.)  
Air Inlet  
(Tee mounted horizontal.)  
Sidewall  
Sidewall  
Roof Inlet, Sidewall Vent  
Sidewall Inlet and Vent  
Basic Air Inlet/Vent Configurations  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
Exhaust Vent  
(Sidewall  
3.6.12 Intake Duct Terminations  
Venting  
Requires Up  
Elbow Mounted)  
Roof  
Round  
Air inlet  
(Down Elbow  
Mounted)  
90° Elbow  
Sidewall  
C750/900/1050 Sidewall Inlet and Vent  
3.6.9 Intake Duct Materials and Sizes:  
Material: PVC, CPVC (Schedule 40), single wall  
galvanized steel, or other suitable materials.  
Sidewall  
Air Inlet  
(tee mounted  
horizontally)  
The intake duct must be sized for a maximum pressure  
drop of 0.22 inches W.C., for the SCFM as specified  
below.  
Boiler Size  
1050  
900  
Required SCFM  
Round  
245  
210  
175  
105  
70  
750  
450  
300  
The installation of a bird screen on the intake  
termination is recommended.  
3.6.10 Sealing the Intake Duct  
No rain cap -  
Unrestricted  
Proper sealing of the intake ductwork is necessary to  
prevent infiltration of air from conditioned space.  
Joints in PVC or CPVC must be cemented. For  
galvanized duct, wrap each joint and seam with  
adhesive aluminum tape.  
3.6.11 Intake Duct Connection to Boiler  
The roof intake termination must be an  
unrestrictive type, as shown above.  
Connect the air supply duct to the collar on the back of  
the boiler. Fasten the duct to the collar with sheet  
metal screws at 90º angles. Seal the joint.  
Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
WARNING!  
Outside Plate  
All threaded connections must be made using a  
pipe compound that is resistant to the action of  
liquefied petroleum gases. Do not use Teflon  
tape on gas line threads.  
Cover Plate  
Fastener  
Centering  
Support Plate  
Field Provided  
Inlet Screens  
Sealant  
Remote Gas Shutoff  
(not supplied)  
Recommended  
Termination  
Sealant  
Natural Gas  
Supply  
By Installer  
12" min.  
Union  
Intake Termination Details  
Drip Leg  
3.6.13 Vent Elbows  
The turn from horizontal to vertical should be made  
with two 45º ells or with one long radius 90º ell for  
best operation. Do not use "short radius" ells.  
Shutoff  
(on boiler)  
Meter  
(not supplied)  
Gas Piping  
In the Commonwealth of Massachusetts, the gas cock  
must be a “T-handle type.”  
3.7 GAS PIPING  
Before making the gas hook-up, make sure the boiler  
is being supplied with the type of fuel shown on the  
boiler nameplate.  
Note: Install a sediment trap (drip leg) and a union  
connection ahead of the primary manual shutoff valve  
on the boiler. Gas piping should be installed in  
accordance with National Fuel Gas Code, ANSI  
Z223.1, latest edition, and any other local codes  
which may apply; in Canada see CAN/CGA-B.149.  
The boiler shall be installed such that the gas ignition  
system components are protected from water  
(dripping, spraying, rain, etc.) during appliance  
operation and service (circulator replacement, control  
replacement, etc.)  
Note: See Pipe Capacity for Natural Gas chart on the  
following page for required pipe size, based on  
overall length of pipe from meter plus equivalent  
length of all fittings. Approximate sizing may be  
based on 1 cubic foot of natural gas per 1,000 Btu per  
hour input, i.e., 500,000 Btu per hour requires about  
500 cubic feet per hour. (See "Typical Boiler  
Operating Conditions," Section 4.3, for more  
information.)  
The boiler is factory fire-tested and adjusted for proper  
combustion with natural gas supply pressure of 7”  
W.C. Typical gas pressure supply for natural gas is  
7" W.C. (11" W.C. for propane). The gas train  
components are certified to handle a maximum inlet  
pressure of 14" W.C. (1/2 psig.). If the available gas  
pressure exceeds 14" W.C., a suitable additional  
intermediate gas pressure regulator of the "lock up"  
type must be provided to reduce the pressure to less  
than 14" W.C.  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
Pipe Capacity for Natural Gas  
Nominal  
Iron Pipe  
Size  
Equivalent Pipe Length  
Maximum Capacity in Cubic Feet of Natural Gas per Hour  
Internal  
Diameter  
(Inches)  
Pressure Drop of 0.5 inch Water Column/Equivalent Length of Pipe  
(in feet)  
90º Ell  
(Feet)  
1.55  
2.06  
2.62  
3.45  
4.02  
5.17  
6.16  
7.67  
10.1  
Tee  
(Feet)  
3.1  
(Inches)  
20  
120  
40  
82  
60  
66  
80  
57  
100  
50  
150  
40  
200  
35  
1/2  
3/4  
1
0.622  
0.824  
1.049  
1.380  
1.610  
2.067  
2.469  
3.068  
4.026  
4.12  
5.24  
6.9  
250  
170  
138  
118  
103  
84  
72  
465  
320  
260  
220  
195  
160  
325  
500  
950  
1500  
2650  
5500  
135  
280  
430  
800  
1280  
2280  
4600  
1- 1/4  
1- 1/2  
2
950  
660  
530  
460  
400  
8.04  
10.3  
12.3  
15.3  
20.2  
1460  
2750  
4350  
7700  
15800  
990  
810  
690  
620  
1900  
3000  
5300  
10900  
1520  
2400  
4300  
8800  
1300  
2050  
3700  
7500  
1150  
1850  
3250  
6700  
2- 1/2  
3
4
3.7.1 Gas Supply Piping by Installer  
3.8 BOILER WATER PIPING  
The boiler and all gas piping connections should be  
pressure-tested and must be checked for leaks before  
being placed into service. Test with compressed air or  
inert gas if possible.  
3.8.1 Piping Design  
Water Flow in System  
The boiler must be disconnected at the boiler manual  
shut-off valve (located at the end of the supplied gas  
train) from the gas supply piping system during any  
pressure testing of the system at pressures in excess of  
1/2 psig (14" W.C.).  
For proper water flow requirements see below.  
Incorrect flow may result in eventual damage or  
premature failure of the equipment.  
Model  
Max Flow  
GPM  
Min Flow  
GPM  
DP ft. at  
max flow  
During any pressure testing of the gas supply piping  
system at pressures equal to or less than 1/2 psig (14"  
W.C.), the boiler should be isolated from the gas  
supply piping system by closing the manual shut-off.  
1050  
900  
750  
450  
300  
105  
90  
52  
45  
37  
22  
15  
12  
12  
Some leak test solutions, including soap and water,  
may cause corrosion. These solutions should be  
rinsed-off with water after testing.  
75  
12  
45  
8.5  
8.5  
30  
Contact factory for minimum flow at other than  
maximum firing rate.  
Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
3.8.2 Boiler Inlet and Outlet Connections  
C750  
C900  
C1050  
C450  
C300  
Condensate  
Trap (Piped to  
drain)*  
Proper flow rates may be achieved through a  
combination of primary and secondary flow loops.  
Multiple zones and pumps may result in different flow  
rates at different times. Consideration must be given  
to all possible conditions and their consequences.  
Piping With Refrigeration Machines  
Boiler Inlet and Outlet Connections  
When installed in a two-pipe system that provides both  
chilled and hot water, the control system should be  
configured so as to limit the time rate of change of  
temperature at the boiler. Consult your authorized  
Patterson-Kelley boiler representative for application  
guidance.  
Make water connections as the application warrants,  
or at a minimum as shown, but always in compliance  
with the local requirements.  
Note: The boiler is furnished with 2” grooved  
connections for Victaulic Style 75 Couplings.  
These coupling must be used with the EPDM  
Victaulic seals. Isolating valves must be installed  
in both water connections for ease of service.  
Piping With Air Handling Units  
The boiler piping system of a hot water heating boiler  
connected to heating coils located in air handling units,  
where they may be exposed to refrigerated air  
circulation, must be equipped with flow control valves  
or other automatic means to prevent gravity circulation  
of the boiler water during the cooling cycle.  
The bottom connection to the boiler is the INLET and  
must be used for the return from the system.  
The top connection to the boiler is the OUTLET and  
must be connected as the supply to the system.  
* Note: Condensate Trap must be piped to drain in  
accordance with all state and local codes.  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
Drain Valve and Piping  
3.8.3 Boiler Water Piping by Installer  
A drain valve is installed in the inlet (system return)  
header connection to the boiler. Prior to draining the  
boiler for maintenance or testing, electrical power and  
gas supply must be turned off to the boiler. The  
boiler must then be isolated from the system at the  
supply and return connections prior to draining water  
from the boiler.  
Strainer  
To avoid possible contamination of the boiler with  
dirt, rust or sediment from the system, a strainer near  
the boiler inlet is strongly recommended. Even new  
systems may contain sufficient foreign material to  
eventually reduce the performance of the heat  
exchanger. Adequate circulation of good clean water  
is essential to maximum efficiency and long life of the  
boiler.  
Note: This drain valve is installed for draining of the  
boiler water only, not the entire system. Draining of  
the system through the boiler will result in depositing  
sediment from the system in the boiler which will  
result in poor heat transfer characteristics of the boiler  
and early boiler failure.  
Relief Valve and Piping  
Each boiler is supplied with a pressure-relief valve  
sized in accordance with ASME requirements. The  
relief valve should be piped to a suitable floor drain.  
Reducing couplings or other restrictions are not  
permitted in the discharge line.  
Condensate Drain  
The condensate can be slightly acidic (pH between  
3.0 and 5.0). This may be corrosive to some building  
drain systems. A condensate neutralization system  
may be required.  
Disposal of condensate must comply with all state  
and local codes.  
Low Water Cut-off  
The boiler is furnished with a probe-type low water  
cut-off; no field piping is required. If the water level  
in the boiler drops below the probe, the boiler will shut  
down and a flashing E 12 service code will be  
displayed on the control panel. The low water cutoff  
circuit will automatically reset when the low water  
condition clears; however the boiler controls will  
retain the lockout condition until the reset button on  
the display is depressed.  
3.8.4 Flushing and Filling  
Water Quality  
The MACH Series boiler heat exchanger is made of  
an aluminum alloy. The heat exchanger requires  
special water conditions to retain efficiency and  
function properly.  
IMPORTANT!  
IMPORTANT!  
The low water cutout probe only prevents boiler  
operation when the water level in the boiler is  
insufficient. It does not detect low water  
conditions in other parts of the system.  
Installation of high point vents or additional low  
water safety devices to protect the system should  
be considered.  
Chemicals added to the system must be  
approved by the chemical manufacturer for use  
in aluminum boilers.  
IMPORTANT!  
Under no circumstances should petroleum  
based cleaning or sealing compounds be used in  
the boiler system.  
Installation of external limit controls may be required  
by certain codes or in certain installations. Review  
applicable local codes for details.  
The boiler is designed to operate in a closed-loop  
system. As such, the system should be tight and not  
require make-up water. A high percentage of  
Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
untreated make-up water will cause premature failure  
due to buildup of scale; such failure is not covered by  
warranty.  
IMPORTANT!  
If the piping system attached to this unit will be  
chemically cleaned, the boiler must be  
Scale can also reduce efficiency. For example, a scale  
thickness of 1/16" will result in a 12.5% loss of  
efficiency.  
disconnected from the system and a bypass  
installed so that the chemical cleaning solution  
does not circulate through the boiler. Following  
chemical cleaning, the system should be  
thoroughly rinsed to remove cleaning agents  
prior to reconnecting the boiler to the system.  
Water pH  
The pH of the hydronic system fluid must be between  
6.0 and 8.5. A periodic check of the system pH should  
be conducted to ensure these pH levels are maintained.  
Filling  
To be sure that the boiler is not air-bound, open the  
pressure-relief valve located at the rear of the boiler.  
Leave the relief valve open until a steady flow of  
water is observed. Close the valve and finish filling  
the system.  
IMPORTANT!  
Glycol and other additives must be approved by  
the chemical manufacturer for use in aluminum  
boilers and must meet the required pH levels  
listed above to prevent damaging the boiler.  
The water quality should be within the guidelines  
established by the American Boiler Manufacturers  
Association, as follows:  
3.9 BURNER AND IGNITION SYSTEM  
Total solids:.................................. 2,500 ppm  
Total hardness:................................ 150 ppm  
3.9.1 Inspection  
Inspect the unit to be sure nothing was damaged or  
knocked loose during shipment. Since some damage  
may be hidden, remove the top cover and inspect the  
boiler.  
The amount of oils, fats, grease, and other organic  
matter should be limited to 10 ppm.  
Consult your water conditioning or chemical treatment  
supplier for analysis and recommendations.  
Inspect the gas train, blower, ignition electrode and  
boiler in general to be sure there was no damage  
during shipment or installation.  
Flushing the System  
Before filling the boiler, flush the system to remove  
any debris from construction or maintenance. Clean  
and flush old piping thoroughly before installing the  
boiler.  
IMPORTANT!  
Under no circumstances should the hydronic  
system be flushed while the boiler is attached to  
the system since the debris or corrosion products  
could accumulate in the boiler and plug the boiler  
heat exchanger.  
Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
3.10 PRE-START CHECK LIST  
WARNING!  
Before attempting to start the boiler, make sure the  
following items have been completed.  
After checking controls by manual adjustment,  
make sure they are always reset to their proper  
settings.  
1. Section 3.9.1 Inspection.  
2. Flue gas from the boiler is properly vented; (refer  
to Section 3.6)  
3.11.1 Test of Ignition Safety System  
3. Gas connection has been made, pressure tested for  
leakage, and the line purged of air. Make sure all  
required vents have been installed.  
MACH (C300 & C450)  
Test the ignition system safety shutdown as follows:  
4. Water connections are complete, and the boiler  
and system have been filled and purged of air.  
1. Loosen the retaining screw and remove the 5 pin  
connector from one of the two gas safety shut-  
off/control valves.  
5. The boiler is connected to a 120 volt power source  
with a disconnect having adequate overload  
protection.  
2. Cycle the boiler on by generating a heat request.  
(The method for this will depend on your boiler  
configuration. See Section 3.12.1.2)  
6. Combustion air openings are not obstructed in any  
way and have adequate capacity.  
7. The boiler is placed the proper distance from any  
combustible walls, in accordance with Section  
3.3.3.  
3. The boiler should run through the normal startup  
sequence, checking all of the limits and switches  
as in a normal start up. (See Sequence of  
Operation, Section 5.4)  
8. Relief valves have been piped to floor drains.  
9. Condensate piping is properly connected.  
4. When the boiler reaches the ignition period, a 2  
will display as the first digit in the display, the  
spark terminal will energize, and one of the gas  
safety shut off / control valves will open. One  
open gas valve should not provide sufficient fuel  
to light the burner.  
10. Verify system fluid pH level is within  
specification.  
5. After 3 seconds the combustion control should  
lock out, and the display will flash E-02  
indicating a flame failure.  
3.11 SAFETY CHECKS  
The following checks of safety systems must be made  
before putting the boiler into normal operation.  
After completing this test, turn off the boiler and  
reconnect the 5 pin connector to the gas safety shut  
off / control valves retightening the retaining screw.  
Before firing the boiler refer to Sections 4.1 and 4.2  
for information on the use of the controls, lighting, and  
shut-down procedures.  
MACH (C750, C900 & C1050)  
WARNING!  
Test the ignition system safety shutdown as follows:  
Never attempt to operate a boiler that has failed  
to pass all the safety checks described below.  
1. Cycle the boiler on by generating a heat request.  
(The method for this will depend on your boiler  
configuration. See Section 3.12.1.2)  
2. Place the boiler in operation at the high fire  
setting. See section 3.12.4 Gas Valve Setup and  
Adjustment , Test Mode High  
Page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
3. Smoothly close the downstream manual isolation  
valve to reduce the gas flow and cause flame  
failure.  
burner. When the gas pressure switch opens, a  
manual reset lockout displaying E 12 on the display  
panel will occur. Upon re-opening the main gas  
cock, the E 12 indicator will remain on until the  
display panel is manually reset.  
4
The display will flash E-02 indicating a flame  
failure. The E-02 lockout will remain until reset  
on the display.  
High Gas Pressure Switch  
After completing this test, turn off the boiler and open  
the downstream manual isolation valve.  
C450 units equipped with a high pressure switch  
must be checked by closing the downstream gas cock  
while the burner is operating. The switch should shut  
down the main burner. When the gas pressure switch  
opens, a manual reset lockout displaying E 12 on the  
display panel will occur. Upon re-opening the gas  
cock, the E 12 indicator will remain on until the  
display panel is manually reset.  
3.11.2 Test of Low Water Cut-out  
The boiler is furnished with a probe-type low water  
cut-out in the outlet nozzle. Test as follows:  
Operation of the switch can be checked by first turning  
the boiler off, and then turning the system pump off.  
Isolate the boiler from the system pressure. After  
isolating the system, drain the water level below the  
low water cut-out probe. Turn the boiler back on. It  
should not operate, and a manual reset lockout  
displaying E 12 on the display panel will occur. The  
LED indicator for Low Water cut-out will no longer be  
illuminated.  
C750,C900 and C1050 units equipped with a high  
pressure switch must be checked by closing the  
downstream gas cock with the boiler off. When the  
boiler is starte , it should enter its normal starting  
cycle and fail on high gas pressure when the gas  
safety valves open. The high gas pressure switch  
actuation is evident when a manual reset lockout  
displaying E 12 on the display panel occurs. Upon  
re-opening the gas cock, the E 12 indicator will  
remain on until the display panel is manually reset.  
Return the system to normal operation and restart the  
boiler. Refer to Section 4.2.1.  
3.11.3 Test of High-Limit Control  
Fire the boiler and test the high limit control as  
follows:  
With the main burner operating, turn down the  
temperature setting on the "high-limit" thermostat until  
the main burner shuts off. A manual reset lockout  
displaying E 12 on the display panel will occur. The  
high-limit switch must be manually reset prior to  
resetting the boiler at the display panel. Readjust the  
high-limit thermostat to the desired setpoint.  
3.11.4 Test of Gas Pressure Switch  
Low Gas Pressure Switch  
The boiler is furnished with a low gas pressure switch.  
The operation of this switch must be checked by  
slowly closing the main gas cock while the burner is  
operating. The switch should shut down the main  
Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
3.12 INITIAL ADJUSTMENTS  
Mode  
Description  
Display  
Example  
0 180  
Standby  
(Stby)  
Normal display  
mode  
1st digit  
without a dot  
3.12.1 Operating Temperature Controller  
Parameter  
(PArA)  
Parameter  
settings  
1st digit with  
a dot  
1.125  
Information  
(InFo)  
display boiler  
sensors  
1st digit with a  
blinking dot*  
1.180*  
Standby Mode:  
The display defaults to this mode at startup or reset of  
the control. If no key is pressed for 20 minutes the  
display will return to this mode. The function of the  
keys may be two-fold as shown below.  
Key(S)  
Mode  
Duration  
momentary  
momentary  
Function  
Change to next mode  
Reset the control  
The MACH boiler is equipped with a combination  
combustion and temperature control. This control  
monitors combustion and lighting of the boiler, as well  
as maintaining temperature of the supply water. The  
temperature control portion modulates the boiler to  
maintain the desired outlet temperature based on the  
selected operating configuration.  
Reset  
Show the comfort heat  
setpoint, or max setpoint  
(outdoor reset only)  
Plus  
Plus  
momentary  
long*  
Turn the comfort heat system  
on or off  
Show the domestic hot water  
setpoint  
Minus  
Minus  
momentary  
long*  
CAUTION!  
Turn the domestic hot water  
system on or off  
The user should become thoroughly familiar with  
the operation of the boiler and controls before  
attempting to make any adjustments.  
*Note: Long duration is greater than 2 seconds.  
When in the Standby Mode the control indicates  
boiler status with the first digit of the display. The  
remaining digits indicate the boiler's actual  
temperature or lockout code. The following table  
indicates the meaning of the display digits when in  
the standby level.  
3.12.1.1 Operation of the Control  
The boiler is operated through the control/display  
panel. The display has 3 modes of standard operating  
menus. The modes are:  
Standby mode will display (Stby)  
Parameter mode will display (PArA)  
Information mode will display (InFo)  
First Digit  
Boiler Status  
Burner off - No call for heat  
Pre purge or post purge  
0
1
2
3
4
5
At each level the keys and the display have different  
functions. To ascertain which mode you are in, the  
displayed information will be shown as indicated  
under “display”.  
Ignition  
Burner on in Comfort Heat mode  
Burner on in Domestic Hot Water mode  
Checking the airflow switch  
Burner off - An internal setpoint has been  
reached. System is still calling for heat.  
6
7
Burner off - Comfort Heat pump running on  
Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
Information Mode:  
First Digit  
Boiler Status  
delay. No system call for heat.  
The information mode is used to display the values of  
the various sensors such as inlet water temp, outlet  
water temp etc. The information mode is accessed by  
pressing the MODE key several times until InFo is  
displayed. The desired sensor is selected with the  
STEP key. The following table indicates the  
displayed value:  
Burner off - Domestic Hot Water pump  
running on delay. No system call for heat.  
8
Burner off – auto reset lockout. A code is  
displayed indicating the reason for the  
lockout. (See Troubleshooting Section  
5.5.)  
9 and b  
flashing  
A
H
L
Adjusting the 3 way valve if used  
Burner on in manual high fire  
Burner on in manual low fire  
Step  
Value  
Outlet water temp  
1
2
3
4
5
6
7
8
Parameter Mode:  
Inlet water temp  
The parameter mode is used to change the settings of  
the boiler. The parameter mode is accessed by  
pressing the MODE key several times until the display  
shows PArA.  
Domestic Hot Water temp *  
Outdoor air temp *  
Flue gas temp  
Boiler outlet setpoint  
The parameters are selected with the STEP key, and  
changed with the plus “+” and minus “-“ keys. Once  
the desired value is reached, pressing the STORE key  
accepts the new setting.  
Rate of change outlet temp °F/second  
Rate of change inlet temp °F/second  
Rate of change Domestic Hot Water  
°F/second  
9
Parameters 1 through 4 are accessible directly at the  
parameter level.  
Second Comfort Heat system  
temperature  
A
Parameters higher than 4 are only accessible by  
authorized service personnel trained on the P-K  
MACH Series Boiler.  
* If the sensors for these functions are not installed,  
the display will indicate -22.  
Upper  
Parameter  
Description  
Lower Limit  
68°  
Limit  
3.12.1.2 Operating Configurations  
DHW setpoint  
if used  
The boiler has several different operating  
configurations. These are:  
1
2
158°  
DHW system  
ON/OFF  
0=OFF  
1=ON  
Internal Setpoint  
Domestic Priority  
Outdoor Air Reset  
Analog Input Setpoint  
Analog Input Direct Drive  
2=OFF +pump  
continuous  
3=ON + pump  
continuous  
3
Comfort heat  
system  
ON/OFF  
0=OFF  
1=ON  
CAUTION!  
2=OFF +pump  
continuous  
Do not modify any parameters other than those  
specifically mentioned.  
3=ON + pump  
continuous  
Setpoint or  
max boiler  
temp outdoor  
air mode  
4
68°  
182°  
Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
Internal Setpoint:  
Item  
DHW Setpoint  
Parameter  
Value  
140  
30  
1
1
The internal setpoint is set with parameter 4. The  
boiler temperature control modulates the boiler to  
maintain this internal setpoint. The upper and lower  
temperature differentials are used to instruct the boiler  
at what temperature to turn on and at what temperature  
to turn off.  
DHW Setpoint Addition  
DHW Status  
33  
2
DHW High Temp. Differential  
DHW Low Temp. Differential  
DHW Options  
25  
24  
35  
6
6
13  
Item  
Parameter  
Value  
Allowable  
Range  
In the above example, the boiler temperature will be  
set to the DHW Setpoint + the DHW Setpoint  
Addition (140ºF + 30ºF = 170ºF) when the DHW  
temperature controller indicates a call for heat from  
the DHW system. When the DHW system calls for  
heat, the Central heat pump output (Terminal 10  
TB2) de-energizes and the DHW pump output  
(Terminal 11 TB2) energizes providing 120 VAC  
power is provided to energize a relay coil for the  
DHW pump. The DHW status should be set to 1  
(DHW system ON).  
Setpoint  
4
22  
23  
5
160  
10  
9
68-185  
0-36  
Low Temp. Differential  
High Temp. Differential  
Low Temp. Setpoint  
0-36  
68  
59-140  
The boiler will modulate to try to maintain 160° F. If  
the temperature increases above 169° F which is the  
setpoint 160° F + High Temp Differential 9°F the  
boiler will shut off. Once it shuts off it will not restart  
until the temperature drops below 150° F which is the  
setpoint – Low Temp Differential. The Low Temp Set  
Point will not permit the operator to adjust the setpoint  
below 68° F. (See graph below.)  
Internal Setpoint  
175  
Boiler Turns Off  
170  
165  
160  
155  
150  
145  
Boiler Temperature  
Boiler Set Point  
Boiler Turns On  
0
10  
20  
Time  
30  
40  
Domestic Priority:  
If an indirect domestic hot water (DHW) tank is  
connected, the DHW function of the boiler will  
activate when the DHW temperature controller  
(supplied by others) closes (Terminal 5 to 8 TB 1,  
refer to Section 6.1.1), indicating a call for heat from  
the DHW system. The parameters should be set as  
follows:  
Page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
The control automatically detects the presence of the  
outdoor air sensor. If an outdoor air sensor is present,  
the boiler automatically defaults to outdoor air reset  
for setting boiler temp. The parameters should be set  
according to the following table:  
Item  
Parameter  
Value  
°F  
Allowable  
Range °F  
Maximum Setpoint  
Minimum Setpoint  
4
5
6
180  
80  
68-185  
60-140  
4-50  
Outdoor Air  
20  
Minimum Temp.  
Outdoor Air  
Maximum Temp.  
7
70  
90  
59-77  
Boiler Shutoff Temp.  
10  
32-140  
(32=off)  
Outdoor Air Offset  
Boiler Configuration  
12  
34  
0
0-144  
01  
The set point of the boiler is controlled by an outdoor  
temperature sensor. As the outdoor temperature falls  
the setpoint of the boiler is increased. The boiler  
modulates to maintain this setpoint.  
The setpoint is adjusted according to the above  
parameters. The boiler setpoint will be the maximum  
value (180° F) when the outdoor air is at or below a  
minimum temperature value (20° F). The boiler  
setpoint will be at the minimum value (80° F), when  
outdoor air is at or above a maximum temperature  
value (70° F). The setpoint for “in between“ values  
of outdoor air temperature, is linearly proportional to  
the above settings. Using the values in the table  
above, the boiler setpoint will be 80° F when the  
outdoor air temperature is 70° F. As the outdoor air  
temperature drops, the boiler setpoint will be  
CAUTION!  
Terminal 10 and 11 on TB2 are for pilot duty only.  
they should not be connected directly to the  
pump.  
Outdoor Air Reset (optional):  
OUTDOOR AIR vs BOILER SETPOINT  
increased until the outdoor air temperature is 20° F.  
At this point the boiler will reach its maximum  
setpoint of 180° F. If the outdoor air temp drops  
further, the boiler setpoint remains at 180° F.  
190  
180  
170  
160  
150  
140  
130  
120  
110  
100  
90  
The boiler shutoff temperature can be used to turn the  
boiler off at a given setpoint. For example if you  
wanted to shut the boiler off when the outdoor air  
temperature was above 65° F you would set the boiler  
shutoff temp to 90° F since this is the setpoint that is  
called for at 65° F outside air temp.  
80  
70  
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
OUTDOOR AIR TEMP °F  
Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
Analog Input to Adjust Setpoint:  
Analog Input to Control Firing Rate:  
Analog Input Setpoint  
Analog Input Firing Rate  
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
0
200  
150  
100  
50  
Boiler Setpoint  
Non adjustable Curve  
0
0
1
2
3
4
5
6
7
8
9
10  
0
1
2
3
4
5
6
7
8
9
10  
Voltage  
Voltage  
The control must be configured for analog input  
direct drive by setting parameter 34 to 02.  
The control must be configured for a remote analog  
input setpoint according to the following table:  
The firing rate of the boiler is controlled by an  
external 0 to 10 VDC signal. At a voltage greater  
Item  
Parameter  
Value  
°F  
Allowable  
Range °F  
than 0.5 VDC the boiler turns on and runs at low fire  
until 1.8 VDC is reached. The firing rate increases  
linearly with voltage until high fire is reached at 10  
VDC. The boiler setpoint Parameter 4 remains active  
to shut down the boiler when the temperature in the  
boiler exceeds this value plus the high temp  
differential. These voltage levels, as explained  
above, are all “non-adjustable”.  
Maximum Setpoint  
Minimum Setpoint  
Boiler Configuration  
4
5
180  
80  
68-185  
60-140  
34  
03  
The setpoint of the boiler is controlled by an external  
0-10 VDC signal. A signal of at least 0.5 VDC is  
required to start the boiler. At 0 VDC the setpoint is  
32° F; at 10 VDC the setpoint is 212° F. This setpoint  
is low and high limited by maximum and minimum  
setpoint parameters. The controlled setpoint voltage  
range narrows when these limits are used. If the above  
tables values are used the boiler setpoint will be 80° F  
when the voltage is anything less than approximately 3  
VDC. It will then increase linearly with voltage until  
approximately 8.5 VDC when it will be 180° F. The  
setpoint will remain at 180° F even if voltage is  
increased further.  
3.12.2 Gas Pressure Adjustment  
Note: Adjustments shall only be performed by  
service representative specifically trained and  
certified to perform maintenance on the  
Patterson-Kelley MACH Series boiler.  
See rating plate for the minimum and maximum gas  
pressure of the boiler. Each boiler is furnished with a  
manual shut-off valve which has an integrated test  
port.  
Page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
Boiler Test Mode:  
This port is located on the upstream side of the valve  
body for measuring supply pressure. (See figure  
below.)  
The test mode should be used when checking and  
setting the gas safety shut off / control valves on the  
MACH Series boilers. In this mode an automatic  
heat request is simulated as follows:  
Test Mode High:  
Simultaneously pressing the “Mode” button and the  
“+” button for 3 seconds activates the “Test Mode  
High” function to drive the boiler output to  
maximum. The display will blink and indicate “H” in  
the first digit of the display to indicate the boiler is  
being driven to the maximum output rating. This test  
mode will automatically terminate after 15 minutes or  
can be terminated from the control/display panel by  
simultaneously pressing the “+” and “-“ buttons for  
three seconds.  
Gas Pressure Test Port  
Test Mode Low:  
Test Port  
Simultaneously pressing the “Mode” button and the  
“-” button for 3 seconds activates the “Test Mode  
Low” function to drive the boiler output to minimum.  
The display will blink and indicate “L” in the first  
digit of the display to indicate the boiler is being  
driven to the minimum output rating. This test mode  
will automatically terminate after 15 minutes or can  
be terminated from the control/display panel by  
simultaneously pressing the “+” and “-“ buttons for  
three seconds.  
The supply pressure during main burner operation  
must be greater than the minimum indicated on the  
rating plate (3.5". W.C. for natural gas, 7" W.C. for  
propane).  
3.12.3 Air Flow Adjustments  
The air flow is pre-set at the factory prior to shipment.  
In unusual situations the air/gas ratio may have to be  
adjusted to obtain proper combustion readings for  
specific local conditions.  
MACH C300 & C450  
Required Tools:  
2 mm hex wrench  
Slotted screwdriver  
Combustion analyzer  
Combustion measurement instrumentation must be  
used to adjust the boiler for local conditions (See  
instructions below). Adjust the carbon dioxide (CO2)  
or oxygen (O2) reading to achieve conditions as listed  
in the following Table 3-1.  
The MACH C300 and C450 boilers are equipped  
with two combined gas/air control and gas safety shut  
off control valves. The valves function in parallel  
with the variable speed combustion blower to supply  
the correct gas air ratio for optimum performance and  
efficiency. The combustion blower speed is  
controlled automatically and determines the amount  
of negative pressure felt at the gas safety shut off /  
control valves. The gas valve servo regulators adjust  
gas flow for each valve to maintain zero pressure at  
the outlet nozzle of the associated valves.  
3.12.4 Gas Valve Setup and Adjustment  
Note: Verify gas pressure at inlet to boiler is in  
accordance with Table 3-1 below. Gas flow is  
dependent primarily on fan speed not upstream gas  
pressure. When set up for natural gas operation, the  
boiler is capable of operating with gas supply pressure  
as low as 3.5” W C.  
Page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
Table 3-1 Combustion Reading For Setting Gas Safety Shut Off / Control Valves  
Nominal  
Gas Pressure  
7" W.C  
High Fire Setting  
Low Fire Setting  
Fuel  
% O2  
% CO2  
% O2  
% CO2  
5.0 + 0.2  
5.0 + 0.2  
9.0 + 0.2  
5.2 + 0.2  
5.2 + 0.2  
8.8 + 0.2  
Natural Gas  
11" W.C  
10.4 + 0.3  
10.3 + 0.3  
Propane  
Adjustment:  
Clockwise rotation decreases gas flow.  
Counterclockwise rotation increases gas flow.  
There must be sufficient load to operate the boiler at  
high fire to perform the following adjustments. Start  
the boiler and observe proper operating parameters for  
the system.  
Low Fire Setting  
Set boiler to the “Test Mode Low”, as described  
above, to achieve minimum firing rate of the boiler.  
Check combustion readings using a combustion  
analyzer. If combustion readings are not in  
accordance with Table 3-1 adjust as follows:  
Note: The MACH C300 and C450 boilers are each  
equipped with two gas safety shut off / control valves  
that operate in parallel. When making any adjustment  
to the valves, the adjustment must be performed on  
each of the valves equally.  
Using a 2 mm hex wrench, adjust the pressure  
regulator offset adjustment (see the figure below, item  
“R”) to achieve the CO2 /O2 level prescribed in Table  
3-1. Note that equal adjustments must be made to  
each of the valves. Adjustments to the offset pressure  
regulators should not exceed ¼ turn at a time before  
allowing the readings to respond and stabilize. Please  
note, the rotation of the Low Fire adjustment is  
opposite of the High Fire as follows: Clockwise  
rotation increases gas flow, counterclockwise rotation  
Example: If an increase in the gas flow is required to  
lower the O2 level, turn each of the maximum flow  
restrictors equivalent amounts (i.e. ¼ or ½ turn each)  
and allow the analyzer readings to respond and  
stabilize before proceeding with additional adjustment.  
Adequate response time must be allowed for  
combustion readings to stabilize. This response time  
will be longer for low firing rates than for high firing  
rates.  
decreases gas flow.  
"R"  
High Fire Setting  
Set boiler to the “Test Mode High”, as described  
above, to achieve maximum firing rate of the boiler.  
Check combustion readings using a combustion  
analyzer. If combustion readings are not in  
accordance with Table 3-1 adjust as follows:  
Using a slotted screw driver or 2 mm hex wrench, set  
the maximum restrictor (high fire screw – see the  
figure below, item “D”) on each of the gas safety shut  
off / control valves by turning clockwise or  
counterclockwise to achieve the desired CO2 or O2  
level; see Table 3-1 for correct settings. (There will be  
a slight time delay between the adjustment and the  
response of the CO2/O2 measuring instrument).  
"D"  
C300/450 Adjusting Low and High Fire  
Page 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Installation  
Low Fire Setting  
MACH C750, C900 & C450  
Required Tools:  
Set boiler to the “Test Mode Low”, as described  
above, to achieve minimum firing rate of the boiler.  
Check combustion readings using a combustion  
analyzer. If combustion readings are not in  
accordance with Table 3-1, adjust as follows:  
TORX® T40 or 5 mm hex wrench  
3 mm or 7/64 in hex wrench  
Combustion analyzer  
The MACH C750,C900 and C1050 boilers are  
equipped with a Honeywell combined gas/air control  
and gas safety shut off control valves. The valve  
functions in parallel with the variable speed  
combustion blower to supply the correct gas air ratio  
for optimum performance and efficiency. The  
combustion blower speed is controlled automatically  
and determines the amount of negative pressure felt at  
the gas safety shut off / control valves. The gas/air  
regulator adjusts gas flow to maintain the proper  
pressure at the outlet nozzle of the associated valve.  
Remove the cap on the gas regulator using a slotted  
screwdriver (See Fig. XX). This will expose the offset  
adjustment screw.  
Using a TORX® T40 or a 5 mm hex wrench, carefully  
adjust the low fire gas setting to achieve the CO2 /O2  
level prescribed in Table 3-1.  
Note: The rotation of the Low Fire adjustment is  
opposite of the High Fire as follows: Clockwise  
rotation increases gas flow, counterclockwise rotation  
decreases gas flow.  
Adjustments to the offset pressure regulators should  
not exceed ¼ turn at a time before allowing the  
readings to respond and stabilize.  
Adjustment:  
After proper low fire offset adjustment is made,  
reinstall the slotted cap on the regulator.  
There must be sufficient load to operate the boiler at  
high fire to perform the following adjustments. Start  
the boiler and observe proper operating parameters for  
the system.  
Following all gas valve adjustments, check for proper  
light-off and verify correct fuel/air mix and  
combustion quality throughout the entire firing range  
(from lowest to highest fan speed).  
High Fire Setting  
High fire adjustment  
Set boiler to the “Test Mode High”, as described  
above, to achieve maximum firing rate of the boiler.  
Check combustion readings using a combustion  
analyzer. If combustion readings are not in  
accordance with Table 3-1, adjust as follows:  
Remove the flat, round, blue plastic cap from the  
cover. Using a 3mm (7/64”) hex wrench, turn the  
adjustment screw counterclockwise to increase or  
clockwise to decrease gas flow and achieve the desired  
CO2 or O2 level; see Table 3-1 for correct settings.  
(There will be a slight time delay between the  
adjustment and the response of the CO2/O2 measuring  
instrument. Adjust the settings in small increments and  
allow the combustion readings to stabilize before  
readjusting. When desired adjustments are complete,  
reinstall the blue plastic cap on the cover.  
Low fire adjustment  
C750/900/10500 Adjusting Low and High  
Page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Operation  
4.0 OPERATION  
4.2.1 Lighting Procedures  
4.1 GENERAL  
1. Close main gas valve.  
2. Turn On-Off switch to "OFF" position.  
3. Wait 5 minutes.  
4.1.1 Control Panel Front  
4. Open main gas valve.  
5. Turn On-Off switch to "ON" position.  
6. Push reset button on display panel if required.  
7. Push reset on low gas pressure switch and high gas  
pressure switch.  
The controller will now complete the automatic firing  
sequence.  
4.2.2 Normal Shut Down Procedures  
1. Close all manual gas valves.  
2. Turn off electric power.  
Control Panel  
Become familiar with the basic operation of the boiler.  
The front of the control panel shows Operating  
Instructions.  
4.1.2 Tests  
Safe lighting and other performance criteria were met  
with the gas manifold and control assembly provided  
on this boiler when the boiler underwent tests  
specified in ANSI Z21.13/CSA 4.9, latest edition.  
(See "Factory Firetest" label.)  
4.2 NORMAL LIGHTING AND SHUT-DOWN  
PROCEDURES  
If a fault is indicated please refer to  
Troubleshooting, Section 5.5, to determine the  
cause of the fault prior to start up.  
WARNING!  
Do not use this boiler if any part has been under  
water. Immediately call a qualified service  
technician to inspect the boiler and to replace any  
part of the control system and any gas control  
which has been under water.  
Page 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Operation  
4.2.3 Emergency Shut-Off  
The main gas cock should be closed immediately if an  
emergency situation occurs.  
Main Gas Cock  
WARNING!  
If overheating occurs or the gas supply  
fails to shut off, do not turn off or  
disconnect the electrical supply to the  
pump. Instead, shut off the gas supply at a  
location external to the boiler.  
Emergency Shut-Off  
4.3 TYPICAL BOILER OPERATING CONDITIONS  
Model  
Input  
Natural Gas  
LP Gas  
Total  
Number  
Rating  
*(1030 Btu/cu. ft.)  
**(2500 Btu/cu. ft.)  
Amperage  
(Btu/hr)  
Gas  
Rate  
(CFH)  
Output  
Capacity  
(Btu/hr)  
Gas  
Rate  
(CFH)  
Output  
Capacity  
(Btu/hr)  
300  
300,000  
291*  
275,000  
120**  
275,000  
8 amps or less  
450  
750  
450,000  
750,000  
900,000  
1,050,000  
437*  
728*  
873*  
414,000  
712,500  
846,000  
987,000  
180**  
300*  
360**  
420**  
414,000  
712,500  
846,000  
987,000  
8 amps or less  
8 amps or less  
8 amps or less  
8 amps or less  
900  
1050  
1019*  
Note: The heat exchanger is constructed and stamped for 50 psig maximum operating pressure and/or 200º F  
maximum temperature.  
Page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Maintenance  
5.0 MAINTENANCE  
WARNING!  
Check daily to be sure that the boiler area is free  
and clear of any combustible materials, including  
flammable vapors and liquids.  
5.1 MAINTENANCE AND INSPECTION SCHEDULE  
WARNING!  
5.1.2 Weekly  
Label all wires prior to disconnection when  
servicing controls. Wiring errors can cause  
improper and dangerous operation.  
Observe the conditions of the main flame. A normal  
high fire flame is blue. If the high fire flame is yellow  
then corrective action must be taken. In normal low  
fire the burner will glow a yellowish-orange.  
WARNING!  
Correct air adjustment is essential to the efficient  
operation of this boiler. If an adjustment in the  
combustion is necessary, the flue gas composition  
should be checked with a carbon dioxide (CO2) or  
oxygen (O2) analyzer to set conditions. Refer to Table  
3-1, Section 3.12.4 for proper combustion readings.  
Use care when reassembling main gas line to  
assure all connections are tight.  
WARNING!  
Use care when servicing boiler in order to prevent  
the accumulation of gas in or around the  
combustion chamber.  
5.1.3 Monthly (During Operation)  
1. Test flame detection by voltage reading at the  
terminal strip (Terminal 9 on TB-1 and ground  
screw). The voltage reading should be between (5  
and 10 VDC).  
WARNING!  
General lockout/ tagout procedure must be  
employed when servicing this unit.  
2. Test high-limit Control. Refer to Section 3.11.3.  
3. Test operating temperature controls by reducing or  
increasing temperature setting as necessary to  
check burner operation.  
WARNING!  
Determine the cause of the lockout before  
resetting the boiler. If able to determine cause of  
lockout, then appropriate corrective action should  
be taken. If not able to determine cause of the  
problem, call a qualified service technician.  
4. Test the low water level cut-out. Refer to Section  
3.11.2.  
5. Test low gas pressure switch. Refer to Section  
3.11.4.  
Verify proper operation after servicing.  
6. Check the condensate drain system. Clean and  
flush as necessary.  
Installation and service must be performed by a  
qualified installer or service agency who has been  
trained on the Patterson-Kelley MACH boiler.  
5.1.1 Daily  
Observe operating temperature and general conditions.  
Make sure that the flow of combustion and ventilating  
air to the boiler is not obstructed. Determine the cause  
of any service codes or lockouts on the display panel.  
Observe any unusual noises or operating conditions  
and make the necessary corrections. Notify  
responsible individuals for required corrective action  
or repair.  
Page 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Maintenance  
5.1.4 Semi-Annually (every 6 months)  
7. Qualified service personnel should thoroughly  
inspect the heating system and correct any  
problems prior to re-starting the boiler.  
In addition to the recommended monthly service:  
1. Clean burner of any accumulated dust or lint. See  
Section 5.2 on "Cleaning the Burner."  
8. Perform combustion analysis and readjust to  
manufacturer's specifications as necessary. It is  
recommended that a copy of this report is filed for  
future reference.  
2. Inspect burner for any signs of deterioration or  
corrosion. Replace immediately if deterioration or  
corrosion is evident.  
9. Perform a leak test of the gas valves in accordance  
with the manufacturer's instructions.  
Installation and service must be performed by a  
qualified installer or service agency who has been  
trained on the Patterson-Kelley MACH boiler.  
Installation and service must be performed by a  
qualified installer or service agency who has been  
trained on the Patterson-Kelley MACH boiler.  
The blower motor is permanently lubricated and does  
not require periodic lubrication.  
5.1.5 Annually  
5.2 CLEANING THE BURNER  
In addition to the recommended monthly service:  
1. Lockout and tagout gas supply to the boiler.  
2. Lockout and tagout electrical power to the boiler.  
3. Remove the top cover of the boiler.  
1. Inspect and clean the inlet screen of any  
accumulated dust or lint.  
2. Check burner and clean off any soot or foreign  
material that may have accumulated. See Section  
5.2 on "Cleaning the Burner." Check for corrosion  
of the burner and its parts. If there is evidence of  
deterioration or corrosion, replace immediately.  
4. Disconnect the electrical connections to the blower  
and gas safety shut off / control valves.  
5. Unbolt burner hood and remove the gas train  
assembly.  
3. Inspect combustion chamber when the burner is  
removed for inspection. Note any signs of  
deterioration. Clean as necessary.  
6. Carefully remove the burner. Use low pressure air  
to remove any dust or lint from the burner. Using  
a soft clean cloth, wipe the inside surface of the  
burner. DO NOT wipe the mesh side (flame side)  
of the burner.  
4. Inspect and clean heat exchanger. Use vacuum to  
remove accumulations from the heat exchanger  
pins and surfaces. Clean the casting pins by  
flushing with clean water and air drying. Do not  
use any cleaning agents or solvents. A soft nylon  
brush may be used in accessible areas.  
5.3 AFTER ALL REPAIRS OR MAINTENANCE  
5. Drain and flush the inside of the heat exchanger as  
required (separate from system flush).  
1. Follow "Pre-Start Check List" (Section 3.10) and  
all "Safety Checks" (Section 3.11).  
6. Examine the venting system at least once a year.  
Refer to the vent manufacturer's instructions for  
requirements in addition to those listed below.  
2. Check gas pressure. (Section 3.12.2.)  
3. Perform combustion check. Adjust gas flow if  
necessary. (Section 3.12.4.).  
a. Check all joints and pipe connections for  
tightness.  
b. Check pipe for corrosion or deterioration. If  
any piping needs replacing, do so  
immediately.  
Page 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Maintenance  
10. The unit modulates between the low fire setting  
and the high fire setting to maintain the desired  
outlet water temp set point.  
5.4 SEQUENCE OF OPERATION  
1. When the On/Off (Main power) switch is turned  
on, power is provided through a circuit breaker to  
the boiler control and the combustion blower. The  
boiler control powers a 24 V transformer. The  
boiler control supplies 24 V power through a high  
limit temperature switch and a low water level  
control.  
11. When the load is below the low fire rating of the  
boiler the boiler will continue firing and the outlet  
water temperature will rise until it reaches the set  
point + temperature differential. At this point the  
burner is turned off, and the fan continues to run to  
post purge the boiler for 15 seconds.  
2. The low water level control is closed when there is  
water in the boiler up to the probe.  
12. When the water temperature is reduced by the load  
on the system, a heat request is again generated.  
The operating sequence will recycle to step 6,  
provided the limits on water level, gas pressure  
and high temperature are all met.  
3. When the temperature sensed by the high limit  
temperature control is below the set limit, the  
switch is closed. Manual reset of the switch is  
required following conditions exceeding high limit  
temperature.  
4. If either the high limit temperature control or the  
low water level control is open, the boiler control  
locks out and indicates E 12 on the display.  
5.5 TROUBLESHOOTING  
The MACH Series boiler will display service codes to  
indicate some problems with the boiler. There are two  
types of lockouts the control may experience: manual  
reset lockouts requiring an operator to press the reset  
button, and automatic reset lockouts, where the control  
will automatically attempt to restart the boiler. A  
listing of service codes is included at the end of this  
section.  
5. Depending on the settings in the boiler control, a  
heat request is generated.  
6. The controller checks that the low air pressure  
switch is open indicating no airflow. The blower  
is driven towards the prestart fan speed. When the  
air pressure switch closes the 15 second prepurge  
time is started, and the blower is driven toward the  
ignition speed.  
Should the unit fail to operate, call a qualified service  
technician to troubleshoot the problem and implement  
corrective action.  
7. After the 15 second prepurge the gas pressure  
switch circuit is checked to ensure the gas pressure  
is within design parameters.  
8. If there are no lockouts then when the blower  
speed is within 200 rpm of the ignition fan speed,  
a trial for ignition period of 3 seconds is initiated.  
The internal spark generator and the gas safety  
shut off / control valves are energized.  
The Loss of Power  
In the event of a power failure (or when the On/Off  
switch is in the Off position), the display panel is not  
illuminated and the entire system is de-energized,  
closing all automatic valves and halting all boiler  
operations. When power is restored the sequence of  
operation will resume at Step 5, provided that all the  
limits are satisfied. If any manual reset lockout was  
present when the power is lost, the display will flash E  
04 when the power is resumed. This indicates that the  
control was in lockout mode but does not indicate  
which service code was present.  
9. The internal spark generator is de-energized .3  
seconds before the end of the trial for ignition  
period. After the trial for ignition period, if a flame  
signal is detected by the flame rectification  
system, the control initiates a flame stabilization  
period of 5 seconds at the ignition rpm of the fan.  
The fan is driven to low fire for 1 minute before  
the boiler is released to modulation.  
Page 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Maintenance  
Loss of Water Level  
manually reset and the front panel reset button is  
pressed. Once the switch, and the front panel are reset,  
the sequence returns to Step 5, provided that the other  
limits are satisfied.  
The low water switch opens when there is insufficient  
water level in the boiler. E 12 is shown on the display,  
and burner operation is interrupted. When the correct  
water level is re-established, pushing the reset button  
will return the sequence to Step 5, provided that the  
other limits are satisfied.  
Low Air  
If the display panel indicates E 08 this indicates  
insufficient airflow through the burner. Check that the  
burner is clean ("Cleaning the Burner," Section 5.2)  
and that there are no obstructions to airflow in the  
intake or exhaust ducts. A low air indication does not  
necessarily mean that the low air switch is defective.  
Low Gas Pressure  
The low gas pressure switch opens when there is (or  
has been) insufficient gas pressure available for proper  
operation of the boiler; E 12 is shown on the display,  
and burner operation is interrupted. If a gas-supply  
shut-off valve is closed for any reason, a low gas  
condition will result.  
Air Switch Closed  
If the display panel indicates B 61 this indicates the air  
pressure switch did not open when the blower was shut  
off. Check that there is no air flow through the boiler  
when the fan is off. If there is no hidden source of air  
flow, replace the switch.  
When gas pressure is restored, E 12 will remain on the  
display panel, and the boiler will remain locked out  
until the front panel reset button is pressed.  
Once the control is reset, the sequence returns to Step  
5, provided that the other limits are satisfied.  
Flame Failure  
High Gas Pressure  
In the event of a flame failure during a firing period or  
a trial for ignition, the main fuel valves are de-  
energized and a manual reset lockout occurs. After the  
spark ignition is re-energized, the 3 second trial-for-  
ignition begins again. If flame failure occurs during a  
trail-for-ignition, a safety lockout occurs. The display  
will indicate E 02. If flame failure occurs and an  
service code is displayed, the combustion control must  
be manually reset.  
The high gas pressure switch opens when there is (or  
has been) excessive gas pressure for the proper  
operation of the boiler. An E 12 service code is  
displayed and the burner operation is interrupted.  
When proper gas pressure is restored, E 12 remains on  
the display with the boiler locked out until the front  
display panel reset button is pressed.  
E 00 signifies a leaky gas valve. In the event of a false  
flame signal E 00 fault code is indicated. This fault  
code could indicate a gas valve failure or leakage of  
the gas valve. If gas valve leakage is suspected, the  
unit must be isolated by turning off the main gas  
supply line until the gas valve is replaced.  
High Water Temperature  
When the boiler water has exceeded both the operating  
and high-limit temperature the high limit switch opens,  
and E 12 is shown on the display. When the water  
temperature falls below the high-limit temperature, the  
boiler will remain locked out until the switch is  
Page 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Maintenance  
5.5.1 Manual Reset Service Codes  
Code  
E 00  
E 02  
E 03  
E 04  
Lockout  
False flame.  
Description  
A flame signal is present when it shouldn’t be.  
Flame failure.  
The burner did not light on startup, or loss of flame during run.  
Check all gas valves electrical connections.  
Gas Valve error.  
General lockout.  
The power was lost after a lockout. The control loses the description of the lockout on  
power loss.  
E 05  
E 06  
E 07  
E 08  
E 11  
E 12  
E 13  
E 14  
E 15  
E 16  
E 17  
E 18  
E 19  
E 25  
E 28  
E 29  
E 31  
E 32  
E 33  
E 35  
E 36  
E 37  
E 38  
E 40  
E 44  
E 52  
E 60  
Internal control failure.  
Internal control failure.  
Internal control failure.  
Air pressure switch open.  
Internal control failure.  
External limit open.  
Call for service.  
Call for service.  
Call for service.  
The air pressure switch failed to close to indicate sufficient air flow to start the boiler.  
Call for service.  
One of the external limits has opened. (High/Low Gas Pressure, High Temp, Low water).  
Internal control failure.  
Internal control failure.  
Internal control failure.  
Internal control failure.  
Internal control failure.  
Outlet high limit temp.  
Return high limit temp.  
Outlet temp rapid change.  
No blower feedback.  
Call for service.  
Call for service.  
Call for service.  
Call for service.  
Call for service.  
The outlet water temperature has exceeded the internal high limit temperature setting.  
The return water temperature has exceeded the internal high limit temperature setting.  
The outlet water temperature is increasing too fast. Indicating low flow condition.  
The blower should be running but it is not, or the feedback signal has been interrupted.  
Blower feedback will not zero. The blower will not go to zero speed even though it should be off.  
Outlet sensor shorted.  
Return sensor shorted.  
DHW sensor shorted.  
Flue sensor shorted.  
Outlet sensor open.  
Return sensor open.  
DHW sensor open.  
Flue sensor open.  
The outlet temperature sensor is short circuited.  
The return temperature sensor is short circuited.  
The DHW temperature sensor is short circuited.  
The flue gas temperature sensor is short circuited.  
The outlet temperature sensor is indicating an open circuit.  
The return temperature sensor is indicating an open circuit.  
The DHW sensor is indicating an open circuit.  
The flue gas temperature sensor is indicating an open circuit.  
Call for service.  
Internal control failure.  
High flue temp.  
The flue temperature has exceeded the maximum allowable setting.  
Call for service.  
Internal control failure.  
Note: When an Internal Control Failure occurs, as identified by E-Codes listed above, the failure is internal to the  
MCBA and replacement of the MCBA is required. A qualified service technician must be called to replace the  
MCBA device.  
Page 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
5.5.2 Auto-reset Service Codes  
Maintenance  
Code  
b 08  
b 18  
b 19  
b 24  
Lockout  
Description  
Air pressure switch open.  
Outlet high limit temp.  
Return high limit temp.  
Switched inlet / outlet.  
The air pressure switch failed to close to indicate sufficient air flow to start the boiler.  
The outlet water temperature has exceeded the internal high limit temperature setting.  
The return water temperature has exceeded the internal high limit temperature setting.  
The inlet water temperature has been more than 18° F above the outlet for more than  
75 seconds.  
b 25  
b 26  
Outlet temp rapid change.  
The outlet water temperature is increasing too fast. Indicating low flow condition.  
High exhaust back pressure. The high exhaust back pressure switch is tripped indicating a blocked stack, inlet, or  
condensate system.  
b 30  
Max delta T.  
The temperature rise across the heat exchanger is greater than maximum allowed,  
indicating insufficient flow.  
b 40  
b 52  
b 61  
b 65  
Flue sensor open.  
The flue gas temperature sensor is indicating an open circuit.  
The flue temperature has exceeded the maximum allowable setting.  
The air pressure switch failed to open prior to starting the blower.  
The fan is being directed to a higher speed than it is achieving.  
High flue temp.  
Air pressure switch closed.  
Fan speed incorrect.  
WARNING  
If any “Manual Reset” limit device trips,  
DO NOT  
reset without determining and correcting the cause.  
Page 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.0 PARTS/TECHNICAL SUPPORT  
Spare parts and replacement parts can be ordered from  
Patterson-Kelley by calling toll free (877) 728-5351.  
Ask for the Heat Transfer Department. The fax  
number is (570) 476-7247. Refer to the parts list  
shown on the assembly drawing provided with this  
manual. Technical information is also available at the  
above number. When ordering replacement parts  
please have the model number and serial number of  
your boiler available.  
Page 36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.1 WIRING DIAGRAMS  
6.1.1 Terminal Block Assignments – High Voltage Circuit (TB2)  
Terminal Number  
Label  
Description  
1
2
115 VAC LINE  
Boiler Supply Power, 115 VAC, 60 HZ, 1 ph, 8 amp  
115 VAC NEUTRAL  
115 VAC NEUTRAL  
115 VAC NEUTRAL  
115 VAC NEUTRAL  
GROUND  
3
Aux. Switched Output  
Boiler Circ. Pump  
DHW Circ. Pump  
Boiler Supply Ground  
Aux .Ground  
4
5
6
7
GROUND  
8
GROUND  
9
115 VAC SW. OUTPUT  
Aux. Switched Output, Pilot duty only, 1 amp max.  
Boiler Circ. Pump, Pilot duty only, 1 amp max.  
10  
115 VAC CIRC. PMP  
CONTACTOR  
11  
115 VAC DHW PMP  
CONTACTOR  
DHW Circ. Pump, Pilot Duty only, 1 amp max.  
Dry Contacts, 24 VAC max, 1 amp max.  
12  
13  
14  
15  
16  
17  
MASTER ALARM RELAY  
MASTER ALARM RELAY  
THREE WAY VALVE RELAY  
THREE WAY VALVE RELAY  
DAMPER RELAY  
DHW Dry Contacts, 24 VAC max, 1 amp max.  
Combustion Air Damper, Dry Contacts, 24 VAC max, 1 amp  
max.  
DAMPER RELAY  
Page 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.1.1a Terminal Block Assignments – Low Voltage Circuit (TB1)  
Terminal Number  
Label  
Description  
1
2
HEAT REQUEST  
Boiler Enable, Contact Closure.  
DO NOT ENERGIZE.  
HEAT REQUEST  
3
INTERLOCK JUMPER  
INTERLOCK JUMPER  
DHW TEMP. SENSOR  
OUTDOOR TEMP SENSOR  
CIRC. PMP PWM SIGNAL  
COMMON  
External Limit (auto reset), Contact Closure.  
DO NOT ENERGIZE.  
4
5
6
Thermistor - factory option.  
7
Pulse Width Modulation.  
8
Common to be used with 5, 6, 7, and 10 when used.  
Common to be used with 5, 6, 7, and 10 when used.  
9
COMMON  
10  
O-10 V ANAL. INPUT CONTROL Remote control of firing rate or setpoint.  
11  
12  
13  
14  
15  
16  
17  
+10 VOLT  
Regulated 10V output.  
RS-485 port A.  
COM 1  
COM 2  
RS-485 port B.  
OUTSIDE TEMP W/ FILTER  
OUTSIDE TEMP W/ FILTER  
SPARE  
Thermistor - factory option.  
Thermistor - factory option.  
SPARE  
Page 38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.1.2 Wiring Series C-300  
Page 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.1.3 Wiring Series C-450  
Page 40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.1.4 Wiring Series C-750/900/1050  
Page 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.2 BOILER PARTS LIST  
6.2.1 Main Assembly  
MACH Series 300/450  
MACH Series 750/900/1050  
Mark  
Description  
Blower and Gas Train  
Mark  
Description  
1
2
3
4
5
1
2
3
4
Heat Engine  
Boiler Gas Train  
Cabinet  
Manifold, System Return, Boiler Outlet  
Manifold, System Supply, Boiler Inlet  
Cabinet  
Control Panel  
High Temperature - Aquastat  
Page 42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.2.2 Control Panel  
Mark  
Description  
AM-3 Relay Module  
1
2
3
4
5
Boiler Control MACH Series - MCBA  
Transformer  
Low Water Cutoff  
Control Mounting Plate  
Page 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.2.3 Display Panel  
3
2
Mark  
Description  
Circuit Breaker  
1
2
3
4
5
6
7
8
Air Pressure Switch  
Fastening Clip  
4
Display Panel  
8
On/Off Switch  
Pressure Temperature Gauge  
Panel Sheet Metal  
Stack Pressure Switch  
7
1
6
5
Page 44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.2.4 C-300/450 Heat Engine  
Mark  
Description  
1
2
Gasket Blower to Burner Hood  
Burner Hood  
3
Inside Burner Hood Gasket  
Outside Burner Hood Gasket  
Burner  
4
5
6
Burner Flange With Insulation  
Sight Glass  
7
8
Seal Sight Glass  
9
Sight Glass Holder  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
Exhaust Pipe Lip Ring  
Exhaust Manifold  
Inspection Cover Gasket  
Inspection Cover  
Gasket (Header Gasket)  
Boiler Outlet / Supply Manifold  
Boiler Inlet / Return Manifold  
Condensate Trap  
Manifold Mounting Plate  
Thermistor (Temperature Sensor)  
Page 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.2.5 C-750/900/1050 Heat Engine  
MARK DESCRIPTION  
1
Gasket Blower to Burner Hood  
2
Burner Hood  
3
Burner Hood Gasket  
4
Burner  
5
6
7
8
View Glass Assembly  
Heat Exchanger Sectional Castings  
Exhaust Pipe Lip Ring  
Condense Collector / Exhaust Manifold  
Inspection Cover & Gasket  
Manifold Gaskets  
Boiler Outlet / Supply Manifold  
Boiler Inlet / Return Manifold  
Condensate Trap  
9
10  
11  
12  
13  
14  
Manifold Mounting Plate  
Page 46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.2.6 C-300 Boiler Gas Train  
Mark  
1
Description  
Main Gas Shut-off Valve  
2
3
4
5
6
7
8
Low Gas Pressure Switch  
Gas Safety Shut-off/Control Valve  
Air/Gas Manifold  
Swirlplate  
Blower  
Gas Leak Test Port  
Flex Hoses w/ Gas Valve Adaptors  
Page 47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.2.7 C-450 Boiler Gas Train  
Mark  
1
Description  
Main Gas Shut-off Valve  
Low Gas Pressure Switch  
High Gas Pressure Switch  
Gas Safety Shut-off/Control Valve  
Gas Manifold Shut-off Valve  
Air/Gas Manifold  
2
3
4
5
6
7
Swirlplate  
8
Blower  
9
Gas Leak Test Port  
10  
Flex Hoses with Gas Valve Adapters  
Page 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Parts and Technical Support  
6.2.8 C-750/900/1050 Boiler Gas Train  
Mark  
Description  
1
2
Main Gas Shut-off Valve  
Low Gas Pressure Switch  
3
High Gas Pressure Switch  
Gas Safety Shut-off/Control Valve  
Gas Manifold Shut-off Valve  
Flex Hose with Gas Valve Adaptor  
Venturi  
4
5
6
7
8
Premix Combustion Blower  
Burner Hood  
9
10  
Burner  
Page 49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Limited Warranty  
C. Any damage to the Product due to abrasion,  
7.0 LIMITED WARRANTY  
erosion, corrosion, deterioration, abnormal  
temperatures or the influence of foreign matter or  
energy.  
Subject to the terms and conditions herein and except  
as provided below with respect to products or parts not  
manufactured by Patterson-Kelley Co., Seller warrants  
to the original owner at the original installation site  
that products manufactured by Seller ("Products") will  
be free from defects in materials and workmanship for  
a period of five (5) years from date of shipment (the  
"Warranty Period"). For products or parts not  
manufactured by Patterson-Kelley, the warranty  
obligations shall, in all respects, be limited to one (1)  
year.  
D. The design or operation of owner's plant or  
equipment or of any facility or system of which  
any Product may be made a part.  
E. The suitability of any Product for any particular  
application.  
F. Any failure resulting from misuse, modification  
not authorized by Seller in writing, improper  
installation or lack of or improper maintenance.  
G. Equipment furnished by the owner, either mounted  
or unmounted, or when contracted for by the  
owner to be installed or handled.  
REMEDY  
The sole remedy of this warranty is expressly limited  
to the repair or replacement of any part found to be  
defective under conditions of normal use within the  
Warranty Period. Installation is not included.  
H. Leakage or other malfunction caused by:  
1. Defective installations in general and  
specifically, any installation which is made:  
a. in violation of applicable state or local  
plumbing housing or building codes,  
WARRANTY  
b. contrary to the written instructions  
furnished with the unit  
The owner must notify the original installer of the  
Product and Seller (Attention: Patterson-Kelley Co.,  
P.O. Box 458, East Stroudsburg, PA 18301), in  
writing, within the Warranty Period, providing a  
detailed description of all claimed defects.  
Transportation to the factory or other designated  
facility for repairs of any products or items alleged  
defective shall, in all events, be the responsibility and  
at the cost of the owner.  
2. Adverse local conditions in general and,  
specifically, sediment or lime precipitation in  
the tubes and/or headers or corrosive elements  
in the atmosphere.  
3. Misuse in general and, specifically, operation  
and maintenance contrary to the written  
instructions furnished with the unit,  
disconnection, alteration or addition of  
components or apparatus, not approved by  
Seller, operation with fuels or settings other  
than those set forth on the rating plate or  
accidental or exterior damage.  
EXCLUSIONS  
Seller shall have no liability for and this warranty does  
not cover:  
I. Production of noise, odors, discoloration or rusty  
water.  
A. Incidental, special or consequential damages, such  
as loss of the use of products, facilities or  
production, inconvenience, loss of time or labor  
expense involved in repairing or replacing the  
alleged defective Product.  
J. Damage to surrounding area or property caused by  
leakage or malfunction.  
K. Costs associated with the replacement and/or  
repair of the unit including: any freight, shipping  
or delivery charges, any removal, installation or  
reinstallation charges, any material and/or permits  
required for installation, reinstallation or repair,  
B. The performance of any Product under conditions  
varying materially from those under which such  
Product is usually tested under industry standards  
at of the time of shipment.  
Page 50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Limited Warranty  
charges to return the boiler and or components.  
Seller's liability under this warranty shall not in  
any case exceed the amount paid for the Product  
found to be defective.  
SEVERABILITY  
To the extent that any provision of this warranty would  
be void or prohibited under applicable law, such  
provisions shall be limited in effect to the minimum  
extent necessary to render the remaining provisions  
hereof enforceable.  
THIRD PARTY WARRANTIES  
For goods or components not manufactured by Seller,  
the warranty obligations of Seller shall, in all respects,  
conform and be limited to one (1) year from the date  
of shipment.  
NO OTHER WARRANTIES  
Seller makes no implied warranty of merchantability  
or fitness for a particular purpose or other warranties  
with respect to any products or services except as  
expressly set forth in this limited warranty.  
Page 51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACH® Series Gas-Fired Boiler  
Appendix  
8.0 APPENDIX  
Date  
Hi/Low-Fire  
O2  
CO  
CO2  
Stack Temp  
Action  
By  
Page 52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Napoleon Grills Gas Grill PRO 500 User Manual
Network Computing Devices Radar Detector 1500 MKII User Manual
Neuton Lawn Mower MA 56 User Manual
Nokia Network Card DNT2Mi fp User Manual
Nortel Networks Switch 100 Chassis User Manual
Omnitron Systems Technology TV Converter Box FlexPoint GX T User Manual
Panasonic DVD Player DVD RV22 User Manual
Panasonic Home Security System BB HCM511A User Manual
Panasonic Radio KX TR320B User Manual
Paradyne Network Router 3700 A2 GB20 10 User Manual