Parker Hannifin Switch 6K User Manual

Automation  
Ethernet Networking  
for 6K and Gem6K  
Effective: February 11, 2002  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ethernet Networking  
User Instruction Material  
Contents  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ethernet Networking  
Overview  
The 6K is equipped for Ethernet communication. It includes 10Base-T (10Mbps twisted pair);  
TCP/IP protocol. RJ-45 connector. Default IP address is 192.168.10.30. You have these  
options for networking the 6K over Ethernet:  
6K as a client. You can connect the 6K via Ethernet to multiple devices, creating a  
client/server network. The 6K is the client, and has the ability to open or close a  
connection with another device (server) and request information from that device. The  
6K supports up to 6 simultaneous server connections. Devices (servers) that may be  
connected to the 6K include:  
Setup Wizard Available  
The Motion Planner  
Wizard Editor provides a  
setup wizard, called  
“Network”, to help you  
establish 6K Client/Server  
communication (up to six  
servers).  
Allen Bradley SLC5-05 PLC (see page 12 for setup procedures)  
OPTO22 SNAP I/O, using Modbus/TCP protocol (see page 9 for setup  
procedures)  
DVT vision system cameras (see page 11 for setup procedures)  
EXAMPLE — Closed Network:  
Ethernet Switch  
(255.255.255.0)  
out  
Ethernet Switch  
(255.255.0.0)  
out  
Connection to  
company network  
6K  
Client (Server to PC)  
IP = 192.168.10.30  
Ethernet  
Card  
Ethernet  
Card  
Device 2  
Server  
IP = 192.168.10.80  
Device 1  
Server  
PC  
IP = 192.168.10.120  
Client  
IP = 192.168.10.31  
IP = 172.20.44.180  
EXAMPLE — Direct Connect to One Server:  
Crossover Cable  
provided in 6K ship kit  
(p/n 71-017635-01)  
Serial Cable  
Device  
6K  
PC  
page 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6K as a server. The 6K waits for a PC to establish a connection with it and then provides  
information on a continual or requested basis. The PC communicates with the 6K using  
the COM6SRVR Communications Server, which is also what Motion Planner uses to  
communicate with the 6K (for details, refer to the COM6SRVR Communications Server  
Programmer’s Reference). The 6K does not support simultaneous connections with  
multiple clients (PCs).  
EXAMPLE — Closed Network:  
Switch or Hub  
(255.255.255.0)  
Switch or Hub  
(255.255.0.0)  
Connection to  
company network  
Ethernet  
Card  
Ethernet  
Card  
6K  
Server  
IP = 192.168.10.30  
PC  
Client  
IP = 192.168.10.31  
IP = 172.20.44.180  
EXAMPLE — Direct Connect to PC:  
Crossover Cable  
provided in 6K ship kit  
(p/n 71-017635-01)  
Switch or Hub  
(255.255.0.0)  
Connection to  
company network  
Ethernet  
Card  
Ethernet  
Card  
6K  
Server  
IP = 172.20.34.30  
PC  
Client  
IP = 172.20.34.160  
IP = 172.20.44.180  
Combination of server and client. For example, the 6K could be the client for an  
OPTO22 (server) and an Allen-Bradley PLC (server). At the same time, a software  
program running on a PC could be using the 6K as a server.  
Ethernet Switch  
(255.255.255.0)  
out  
Ethernet Switch  
(255.255.0.0)  
out  
Connection to  
company network  
6K  
Client (Server to PC)  
IP = 192.168.10.30  
Ethernet  
Card  
Ethernet  
Card  
Device 2  
Server  
IP = 192.168.10.80  
Device 1  
Server  
PC  
IP = 192.168.10.120  
Client  
IP = 192.168.10.31  
IP = 172.20.44.180  
page 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Peer-to-peer network with other 6K or Gem6K units. The 6K may be connected to  
other 6K devices (6K Controllers or Gem6K drive/controllers) via Ethernet. Up to eight  
6K devices may be networked in this manner. This type of connection uses UDP  
broadcasting and is not a client/server relationship. (see page 8 for setup procedures)  
Setup Wizard Available  
The Motion Planner  
Wizard Editor provides a  
setup wizard, called  
“Network”, to help you  
establish 6K peer-to-peer  
communication.  
Ethernet Switch  
(255.255.255.0)  
out  
Ethernet Switch  
(255.255.0.0)  
out  
Connection to  
company network  
6K unit 1  
IP = 192.168.10.30  
Ethernet  
Card  
Ethernet  
Card  
6K unit 2  
IP = 192.168.10.40  
PC  
IP = 192.168.10.31  
IP = 172.20.44.180  
Networking Guidelines  
Use a closed network. Because of network broadcasts, it is best to put the 6K, along  
with any associated server devices, on a closed network with its own subnet. If you  
have a PC connected to the Ethernet Client/Server network and the PC is also  
connected to your company’s network, use one Ethernet card for the Ethernet  
Client/Server network and another Ethernet card for the company network (refer to the  
example below).  
Ethernet Switch  
(255.255.255.0)  
out  
Ethernet Switch  
(255.255.0.0)  
out  
6K  
Client (Server to PC)  
IP = 192.168.10.30  
Ethernet  
Card  
Ethernet  
Card  
Device 2  
Server  
IP = 192.168.10.80  
Device 1  
Server  
PC  
IP = 192.168.10.120  
Client  
IP = 192.168.10.31  
IP = 172.20.44.180  
page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
If the 6K is placed on an open network, put the 6K and any associated server devices  
on one side of an Ethernet network switch with its own subnet and install a bridge to  
filter traffic, such that broadcast traffic does not pass in either direction (see diagram  
below).  
Ethernet Switch  
(255.255.255.0)  
out  
Ethernet Switch  
(255.255.0.0)  
out  
Bridge  
6K  
Device 2  
Client  
IP = 192.168.10.30  
Server  
IP = 192.168.10.80  
IP = 172.20.44.180  
Ethernet  
Card  
Device 1  
Server  
IP = 192.168.10.120  
PC  
Use a switch (recommended) or hub if you are making more than one Ethernet  
connection with the 6K.  
The 6K client must have the same subnet address as all of the server devices it will  
connect to (PLC, OPTO22, DVT, etc.). For example, if the subnet mask (NTMASK) is  
255.255.255.0, and the subnet address is 192.168.10.*, then all devices (including the  
6K) must have an address starting with 192.168.10.*, where the * number is unique to  
the device.  
Fieldbus (DeviceNet or Profibus) versions of the 6K (part numbers 6Kn-DN or  
6Kn-PB) cannot also communicate as an Ethernet Client at the same time.  
If you have a Fieldbus unit and need to use Ethernet instead, execute the OPTENØ  
command, then the RESETcommand (this disables the Fieldbus features), and then the  
NTFEN1or NTFEN2command.  
To re-enable Fieldbus communication, execute the NTFENØcommand, then the RESET  
command (this disables Ethernet communication), and then the OPTEN1command.  
You cannot communicate to the 6K with simultaneous transmissions over both the  
“ETHERNET” and “RS-232” (PORT1) connections.  
Follow the manufacturer’s setup procedure for each Allen-Bradley PLC, DVT camera  
and OPTO22 Ethernet I/O rack.  
You should be able to ping every 6K, DVT camera, PLC and OPTO22 I/O rack from  
the PC. Use the pingcommand at the DOS prompt:  
ping 192.168.10.30  
If your PC responds with “  
”,  
Request Timed Out  
check your Ethernet wiring and IP address setting.  
Device’s IP Address  
(space)  
The following Ethernet setup commands need only be sent once to the 6K because they  
are saved in non-volatile memory and are remembered on power-up and RESET: NTID,  
NTIO, NTIP, NTMPRB, NTMPRI, NTMPWB, and NTMPWI.  
If a PC is connected to the 6K/Device Ethernet network, then the PC should include all  
devices in a static mapping table. The static mapping procedure, for the 6K’s address, is  
found on page 6.  
If the 6K is in a peer-to-peer network, enable Ethernet communication with the NTFEN1  
command (NTFEN2mode is not compatible with peer-to-peer communication).  
page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuring the 6K for Ethernet Communication  
There are three major steps in setting up Ethernet communication between a PC and controller:  
Step 1 prepares the 6K for Ethernet communication, and must be performed using RS-232  
communication.  
Step 2 sets the TCP/IP properties on your PC to allow Ethernet communication, and  
statically maps the 6K’s MAC address to the IP address of the Ethernet card in your PC.  
The static mapping eliminates the PC’s need to ARP the controller, which reduces  
communication overhead.  
Step 3 connects the PC to the 6K via the Ethernet.  
Step 1— Preparing  
the Controller over  
RS-232  
1. Connect the 6K controller to your network (refer to Networking Guidelines on page 3).  
2. Establish an RS-232 communication link between the 6K and your computer (connect to the  
6K’s “RS-232” connector according to the instructions in the 6K Installation Guide).  
3. Install Motion Planner on your computer, and launch Motion Planner. Click on the Terminal  
tab to view the terminal emulator.  
4. In the Terminal window, click on the  
button to view the Communications Settings dialog.  
Select the Port tab and select the COM port that is connected to the 6K’s “RS-232” connector  
(see Step 2 above). Click OK.  
5. In the Terminal window, enable Ethernet communication:  
a. If you are using the 6K as a server or client, type the NTFEN2command and press  
ENTER, then type the RESETcommand and press ENTER.  
b. If you are using the 6K in a peer-to-peer connection with another 6K or Gem6K, type the  
NTFEN1command and press ENTER, then type the RESETcommand and press ENTER.  
Step 2—Setting  
TCP/IP Properties  
and Static  
1. Connect the 6K controller to your network (refer to Networking Guidelines on page 3).  
2. Install your Ethernet card and configure it for TCP/IP protocol. Refer to your Ethernet card’s  
user documentation for instructions. (If you need to change the 6K’s IP address or subnet mask,  
refer to the note on the left.)  
Mapping  
3. (see illustration below) Configure your Ethernet card’s TCP/IP properties so that your  
computer can communicate with the 6K controller.  
Changing the 6K’s IP  
Address or Subnet Mask  
a. Access the Control Panels directory.  
b. Open the Network control panel.  
The factory default 6K IP  
address is 192.168.10.30;  
the default mask is  
c. In the Network control dialog, select the Configuration tab (95/98) or the Protocols tab  
(NT) and double-click the TCP/IP network item to view the TCP/IP Properties dialog.  
255.255.255.0.  
d. In the TCP/IP Properties dialog, select the IP Address tab, select “Specify an IP Address”,  
type in 192.168.10.31 in the “IP Address” field, and type in 255.255.255.0 in the “Subnet  
Mask” field.  
If the default address and  
mask are not compatible  
with your network, you  
may change them with the  
NTADDRand NTMASK  
e. Click the OK buttons in both dialogs to finish setting up your computer’s IP address.  
commands, respectively  
(see 6K Series Command  
Reference for details on  
the NTADDRand NTMASK  
commands). To ascertain  
the 6K’s Mac address, use  
the TNTMACcommand.  
The NTADDR, NTMASKand  
TNTMACcommands may  
be sent to the 6K controller  
over an RS-232 interface  
(see Steps 4-6). NOTE: If  
you change the 6K’s IP  
address or mask, the  
changes will not take affect  
until you cycle power or  
issue a RESETcommand.  
page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
If you are using  
Windows NT, select  
the “Protocols” tab.  
Make sure this number is different  
from the one in the 6K’s IP address.  
If the 6K’s default IP address is  
unchanged (192.168.10.30), then  
select a number other than 30.  
NOTE  
If you are using a computer (Ethernet card) that is  
normally connected to a network, you should write  
down the existing IP Address and Subnet Mask  
values, so that you may restore them later.  
4. Establish an RS-232 communication link between the 6K and your computer (connect to the  
6K’s “RS-232” connector according to the instructions in the 6K Installation Guide).  
5. Install Motion Planner on your computer, and launch Motion Planner. Click on the Terminal  
tab to view the terminal emulator.  
6. In the Terminal window, click on the  
button to view the Communications Settings dialog.  
Select the Port tab and select the COM port that is connected to the 6K’s “RS-232” connector  
(see Step 4 above). Click OK.  
7. In the Terminal window, enable Ethernet communication with the appropriate NTFEN  
command:  
a. If you are using the 6K as a server or client, type the NTFEN2command and press ENTER,  
then type the RESETcommand and press ENTER.  
b. If you are using the 6K in a peer-to-peer connection with another 6K or Gem6K, type the  
NTFEN1command and press ENTER, then type the RESETcommand and press ENTER.  
8. Use the following sub-procedure to statically map the 6K’s Ethernet MAC address to IP  
address of the Ethernet card in your PC. Static mapping eliminates the need for the PC to  
ARP the 6K controller, thereby reducing communication overhead.  
a. In Motion Planner’s Terminal window, type TNTand press ENTER. The response  
includes the 6K IP address, and the 6K Ethernet address value in hex (this is also  
known as the “MAC” address). Write down the IP address and the Ethernet address  
(hex value) for later use in the procedure below.  
b. Start a DOS window. The typical method to start a DOS window is to select MS-DOS  
Prompt from the Start/Programs menu (see illustration below).  
page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
c. At the DOS prompt, type the arp –scommand (see example below) and press ENTER.  
Spaces  
(press the space bar)  
arp –s 192.168.10.30 0-90-55-0-0-1 192.168.10.31  
6K’s IP Address  
6K’s Ethernet Address  
IP Address of Ethernet Card  
(from TNTreport)  
(from TNTreport)  
d. To verify the mapped addresses, type the arp –acommand and press ENTER.  
If you receive the response “No ARP Entries Found”:  
1) Switch to the Motion Planner Terminal window, type NTFEN2(or NTFEN1if using a  
peer-to-peer network) and press ENTER, then type RESETand press ENTER.  
2) Switch to the DOS window, type the pingcommand and press ENTER:  
ping 192.168.10.30  
If your PC responds with “  
Timed Out  
wiring and IP address setting.  
Request  
”, check your Ethernet  
6K’s IP Address (from TNTreport)  
(space)  
3) Repeat the arp –scommand as instructed above. Use arp –ato verify.  
4) Switch to the Motion Planner Terminal window, type NTFEN2(or NTFEN1if using a  
peer-to-peer network) and press ENTER, then type RESETand press ENTER.  
e. (OPTIONAL) Automate the arp –sstatic mapping command. This allows your PC  
to automatically perform the static mapping when it is booted; otherwise, you will  
have to manually perform static mapping every time you boot your PC.  
Windows 95/98: Add the arp –scommand to the Autoexec.bat file.  
Windows NT: Create a batch file that contains the arp –scommand. Save the file  
(name the file “6KARP.BAT”) to the root directory on the C drive. Using Windows  
Explorer, locate the 6KARP.BAT file, create a shortcut, then cut and paste the shortcut  
into the StartUp directory. Windows NT has several StartUp directories to accommodate  
various user configurations. We recommend using the Administrators or All Users  
locations. For example, you can paste the shortcut into the  
WinNt\Profiles\AllUsers\StartMenu\Programs\StartUp directory, allowing all users to  
statically map the IP and Mac addresses whenever the PC is booted.  
1. Connect the 6K Controller to your computer using a cross-over 10Base-T cable (5-foot cable  
provided in ship kit).  
Step 3—  
Connecting the 6K  
to the PC through  
Ethernet  
2. In Motion Planner’s Terminal window, click the{bmc b_comset.bmp} button to view the  
Communications Settings dialog. Select the Port tab, select “Network” and type the IP  
address (192.168.10.30) in the text field. Click OK.  
You may now communicate to the controller over the Ethernet interface. Reminder: You  
cannot communicate to the 6K with simultaneous transmissions over both the “ETHERNET”  
and “RS-232” (PORT1) connections.  
Ethernet Connection Status LEDs (located on the RJ-45 “ETHERNET” connector):  
Green LED turns on to indicate the Ethernet physical connection is OK.  
Yellow LED flashes to indicate the 6K is transmitting over the Ethernet interface.  
page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Networking with Other 6K or Gem6K Products (Peer-to-Peer)  
You can communicate information between 6Ks and Gem6Ks over Ethernet. This feature uses  
UDP broadcasting over the subnet to transfer data, so no client/server connection is needed.  
Up to 8 different 6K or Gem6K devices can share information, with each device having access  
to shared data from the 7 other devices. Each device can broadcast 8 pieces of information  
using “shared output” variables (VARSHO1through VARSHO8). The following table lists the  
information you can assign to a “shared output” variable.  
A..........Acceleration  
NMCY... Master cycle number  
OUT..... Output status  
SS..........System status  
AD........Deceleration  
SWAP......Task swap assignment  
TASK......Task number  
ANI.....Analog input voltage  
ANO.....Analog output voltage  
AS........Axis status  
PANI... Analog input position  
PC....... Commanded position  
PCC..... Captured command pos.  
PCE..... Captured encoder pos.  
PCME... Captured master enc. pos.  
PE....... Encoder position  
TIM........Timer value  
TRIG......Trigger interrupt status  
US..........User-defined status  
V............Velocity  
ASX.....Extended axis status  
D..........Distance  
DAC.....DAC output value  
DKEY...RP240 keypad value  
ER........Error status  
VARI......Integer variable  
VARB......Binary variable  
VEL........Commanded velocity  
VELA......Actual velocity  
PER..... Position error  
PMAS... Position of Master  
PME..... Master encoder pos.  
PSHF... Net position shift  
FB........Feedback device pos.  
FS........Following status  
IN........Input status  
VMAS......Velocity of the master  
VARSHI.Shared input variable  
PSLV... Follower pos. command  
SC....... Controller status  
INO.....Enable input status  
LIM.....Limit input status  
MOV.....Axis moving status  
SCAN... PLC scan time  
SEG..... Free segment buffers  
The data can be either binary, as in the AS(axis status) operand, or a 32-bit unscaled integer, as  
in PE(encoder position) operand. The data stored in the VARSHOis not scaled.  
The NTRATEcommand sets the rate at which each controller broadcasts its updated VARSHO  
data. RECOMMENDATION: Set all devices to broadcast at the same NTRATErate of 50  
milliseconds.  
Setup  
For 6K or Gem6K sending and/or receiving information via the Peer to Peer feature:  
1. Connect the 6K/Gem6K products to the network and configure each 6K/Gem6K for  
Ethernet communication according to the procedures on page 4.  
2. Set the broadcasting rate with NTRATEcommand, preferably the same for each unit.  
3. If the unit is to receive data only (not send) you are finished with the setup for that unit.  
If the unit is to send also, complete steps 4 and 5.  
4. Assign a unique unit number (1-8) with the NTIDcommand.  
5. Assign data to the eight broadcast variables with the VARSHOcommand.  
6. Repeat steps 2-5 for each unit in the peer-to-peer network.  
Example  
First 6K or Gem6K:  
NTID1  
VARSHO1 = 1A  
VARSHO2 = 1PE  
; Assign this unit a peer-to-peer unit number of 1  
; Shared variable #1 contains axis 1's acceleration  
; Shared variable #2 contains axis 1's encoder position  
; ***********************************************************************  
; * Use this space to define shared output variables VARSHO3 – VARSHO7. *  
; ***********************************************************************  
VARSHO8 = VARI1 ; Shared variable #8 contains the value of VARI1  
NTRATE50  
; Set the broadcasting rate to 50 milliseconds  
Second 6K or Gem6K:  
NTID2  
; Assign this unit an ID of 2  
VARSHO1 = 1D  
VARSHO2 = 3PE  
; Shared variable #1 contains axis 1's programmed distance  
; Shared variable #2 contains axis 3's encoder position  
; ***********************************************************************  
; * Use this space to define shared output variables VARSHO3 – VARSHO7. *  
; ***********************************************************************  
VARSHO8 = 1ANI.1 ; Shared variable #8 contains the voltage value at analog  
page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
; input 1 on I/O brick 1  
NTRATE50  
; Set the broadcasting rate to 50 milliseconds  
Third 6K or Gem6K:  
NTRATE50  
; Set the broadcasting rate to 50 milliseconds  
; This third unit will receive data only. Therefore, it does not require  
; a unit ID number or VARSHO data assignment  
Program  
Interaction  
Each Unit can read the broadcast variables of each other unit with the nVARSHIicommand.  
The “n” specifies the ID number (NTID) of the unit you want to read from, the “i” is the  
VARSHOnumber of that unit to be read. For example, if you want unit 1 to read unit 2’s  
VARSHO8data, then use 2VARSHI8.  
Using the VARSHIcommand, you can process data from the VARSHOvariable of another peer-  
to-peer unit. Use the following ways:  
Assign the VARSHOdata to a VAR(numeric), VARI(integer), or VARB(binary) variable.  
For example, the command VARI1=2VARSHI8assigns the value of VARSHO8on unit 2  
to the VARI1integer variable.  
Assign the VARSHOdata to a virtual input (IN). For example, 3IN=2VARSHI3assigns  
the binary value of VARSHO3from unit 2 to virtual input brick 3.  
Use the VARSHOdata in a conditional expression for an IF, WAIT, WHILE, or UNTIL  
statement. For example, if VARSHO5on unit 2 is assigned is assigned the status of  
onboard trigger input 3 (VARSHO5=IN.3), then you could use this command to make  
unit 1 wait until trigger input 3 on unit 2 was on: WAIT(2VARSHI5=b1).  
Example  
First 6K or Gem6K (unit 1):  
VARI1 = 2VARSHI8  
; Assign Unit 2's VARSHO8 (which is the voltage value  
; at analog input 1 on I/O brick 1) to VARI1.  
Second 6K or Gem6K (unit 2):  
VARI100 = 1VARSHI2 ; Assign Unit 1's VARSHO2 (which is the encoder position  
; of axis 1) to VARI100.  
Third 6K or Gem6K (reading data only):  
VARI90 = 1VARSHI1 ; Assign Unit 1's VARSHO1 (which is the acceleration of  
; axis 1) to VARI90.  
Networking with OPTO22 SNAP I/O  
The 6K client can communicate with the OPTO22 SNAP I/O server to read digital and analog  
inputs and outputs, and write digital and analog outputs. The 6K supports up to eight modules  
per OPTO22.  
Setup  
1. Follow the manufacturer’s setup procedure for the OPTO22 Ethernet I/O rack.  
2. Connect the 6K and OPTO22 products in a network and configure the 6K for Ethernet  
communication according to the procedures on page 4.  
3. Choose a Server Connection Number for this device. The 6K can support up to 6  
simultaneous server connections. Pick a number (1-6) that has not been used already for  
another connection. This will be used to reference the OPTO22 unit from now on.  
4. Enter the IP address of the OPTO22 and specify a 2 for connection type with the NTIP  
command. For example, if the OPTO22 is Server #3 and its IP address is 172.20.34.170,  
then the command would be 3NTIP2,172,20,34,170.  
5. Attempt a connection to the device with NTCONN. For example, if the server number is 3,  
the command would be 3NTCONN1. If the connection is successful, Network Status bit #1  
is set (see NTS, TNTS, TNTSF). If the connection is unsuccessful, Error Status bit #23 is  
set (see ER, TER, TERF).  
6. Inform the 6K of the configuration of the OPTO22. For each module position, use the  
page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
NTIOcommand to specify the type of module in that position.  
n\mNTIO<i>  
Network Server #  
Range: 1-6  
Module Type. Options are:  
1 = Digital/Discrete Inputs  
2 = Digital/Discrete Outputs  
3 = Analog Inputs  
Module # on Server “n”  
Range: 0-7  
4 = Analog Outputs  
For example, if there is a digital input module in slot 0, then the command would be  
3\0NTIO1. If there is an Analog Input module in slot 7, then the command would be  
3\7NTIO3.  
7. Set the polling rate with the NTPOLLcommand. 50 milliseconds is recommended. For  
example, to set the polling rate to 50 ms on server #3, use the 3NTPOLL50command. If  
there is an error during polling, then Error Status bit #24 will be set.  
NTADDR172,34,54,123  
OPTEN0  
RESET  
; Set the IP address of the 6K  
; Disable the option card (for Fieldbus units only)  
Example  
NTFEN2  
RESET  
; Enable network function on 6K  
DEL OPTOSU  
DEF OPTOSU  
2NTIP2,172,34,54,124 ; Identify an OPTO22 device as Server #2, which is  
; located at IP address 172.34.54.124  
2NTCONN1  
2\1NTIO2  
2\2NTIO2  
2\3NTIO1  
2\4NTIO3  
2NTPOLL50  
END  
; Attempt connection to Server #2 (OPTO22)  
; Configure OPTO22 module 1 as digital output  
; Configure OPTO22 module 2 as digital output  
; Configure OPTO22 module 3 as digital input  
; Configure OPTO22 module 4 as analog input  
; Begin polling, set polling interval to 50 ms  
Program  
Interaction  
Once the OPTO22 is configured and a connection is made, you can then set outputs and check  
inputs.  
How the 6K addresses OPTO22 I/O locations:  
The 6K addresses each I/O bit by its location on a specific module. (NOTE: I/O points are  
not addressed by an absolute 32-bit location on the OPTO22.) Digital input and output  
modules have four I/O points, or channels, and are numbered 1-4. Analog input and output  
modules have two I/O points, or channels, and are numbered 1-2.  
EXAMPLE: OPTO22 is Network Server #3  
0
1
2
3
4
5
6
7
Digital  
Input  
Module  
Digital  
Input  
Module  
Digital  
Output  
Module  
Digital  
Output  
Module  
Analog  
Output  
Module  
Analog  
Output  
Module  
Analog  
Input  
Module  
Analog  
Input  
Module  
Input  
1
Input  
2
Input  
1
Input  
2
Output  
Output  
Output  
Output  
Input  
1
Input  
2
Input  
1
Input  
2
1
Output  
2
1
Output  
2
1
Output  
2
1
Output  
2
Input  
3
Input  
3
Output  
3
Output  
3
Input  
4
Input  
4
Output  
4
Output  
4
3\0IN.3  
3\3OUT.2  
3\5ANO.1  
3\7ANI.2  
To verify the I/O configuration (as per NTIO) and to check the status of each module’s  
inputs and outputs, type n\TIO, where “n” is the server number.  
To set a digital output, type n\mOUT.i-b, where “n” is the server number, “m” is the  
module number, “i” is the point number on that module and “b” is the state (1= on,  
0= off). To set multiple digital outputs on the same module, type n\mOUTbbbb:  
O t t #1  
page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Output #1  
Output #2  
Output #3  
Output #4  
n\mOUTbbbb  
Network Server #  
Range: 1-6  
Options for “b” are:  
1 = Turn on  
0 = Turn off  
x = Don’t Change  
Module # on Server “n”  
Range: 0-7  
For example (Server #3), to turn on outputs #1 and #4 and leave outputs #2 and #3 un-  
changed on module #2, type 3\2OUT1XX1. To turn off only output #4, type 3\2OUT.4-0.  
To set an analog output voltage, type n\mANO.i-r, where “n” is the server number, “m” is  
the module number, “i” is the output number on that module and “r” is the voltage. For  
example, to set analog output #1 on module #5 of Server #3 to 6.4V, type 3\5ANO.1=6.4.  
To read a digital input or output module, use the assignment/comparison operands (n\mIN  
or n\mOUT) or the transfer commands (n\mTINor n\mTOUT). Following are examples:  
- IF(3\0IN=b1100)is an IFcondition that reads all four digital inputs on module #0.  
IF(3\0IN.2=b1)is an IFcondition that reads only digital input #2 on module #0.  
- IF(3\2OUT=b1100)is an IFcondition that reads all four outputs on module #2.  
IF(3\2OUT.3=b1)is an IFcondition that reads only digital output #3 on module #2.  
- 3\0TINtransfers the binary status of all four digital inputs on module #0.  
3\0TIN.2transfers the binary status of only digital input #2 on module #0.  
- 3\2TOUTtransfers the binary status of all four digital outputs on module #2.  
3\2TOUT.3transfers the binary status of only digital output #3 on module #2.  
To read an analog input or output module, use the assignment/comparison operands  
(n\mANIor n\mANO) or the transfer commands (n\mTANIor n\mTANO). Following are  
examples:  
- WAIT(3\7ANI.2<2.4)is an WAITcondition that reads analog input #2 on module #7.  
- IF(3\5ANO.1>=1.0)is an IFcondition that reads analog output #1 on module #5.  
- 3\6TANItransfers the voltage status of both analog inputs on module #6.  
3\6TANI.2transfers the voltage status of only analog input #2 on module #6.  
- 3\4TANOtransfers the voltage status of both analog outputs on module #4.  
3\4TANO.1transfers the voltage status of only analog output #1 on module #4.  
Networking with a DVT Vision System  
The controller can send trigger commands to the camera. The camera should send back ASCII  
strings similar to what follows: VARn = 123.456, VARm = 234.567. The ASCII strings are  
VARassignments set apart by commas. The values are then written to the controller’s VARs;  
This data can represent anything, such as an x-y coordinate.  
Setup  
1. Follow the manufacturer’s setup procedure for the DVT camera.  
2. Connect the 6K and DVT camera in a network and configure the 6K for Ethernet  
communication according to the procedures on page 4.  
3. Choose a Server Connection Number for this device. The 6K can support up to 6  
simultaneous client connections. Pick a number (1-6) that has not been used already for  
another server connection. This will be used to reference the device from now on.  
4. Enter the IP address of the camera and specify a 3 for connection type with the NTIP  
command. For example, if the DVT camera is Server #6 and its IP address is  
172.20.34.150, then the command would be 6NTIP3,172,20,34,150.  
5. Attempt a connection to the device with NTCONN. For example, if the server number is 6,  
the command would be 6NTCONN1. If the connection is successful, Network Status bit  
#1 is set (see NTS, TNTS, TNTSF). If the connection is unsuccessful, Error Status bit #23  
is set (see ER, TER, TERF).  
page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
6NTIP3,172,34,54,150  
6NTCONN1  
; Identify a DVT camera as Server #6, located at  
; IP address 172.34.54.150.  
; Attempt the connection to Server #6  
Example  
Program  
Interaction  
Once a connection has been established, you can write trigger commands to the camera using  
the NTWRITcommand.  
DEL DVT  
DEF DVT  
Example  
6NTCONN1  
; Attempt connection to DVT camera  
6NTWRIT"DVT commands"  
END  
; Write the text "DVT commands" to camera  
Networking with an Allen-Bradley SLC 5/05 PLC  
The Allen-Bradley SLC 5/05 exchanges integer and binary data with the 6K. The data  
exchange is accomplished by mapping integer variables (VARI) and binary variables (VARB) in  
the 6K with data elements in the PLC’s integer and binary data files. The 6K limits the amount  
of variable mapping to 100 binary variables (50 write, 50 read) and 100 integer variables  
(50 write, 50 read).  
Setup  
1. Follow the manufacturer’s setup procedure for each Allen-Bradley PLC, DVT camera  
and OPTO22 Ethernet I/O rack.  
2. Connect the 6K and Allen-Bradley PLC in a network and configure the 6K for Ethernet  
communication according to the procedures on page 4.  
3. Choose a connection number for this device. The 6K can support up to 6 simultaneous  
client connections. Pick a number (1-6) that has not been used already for another client  
connection. The number is used to reference the device from now on.  
4. Enter the IP address of the PLC and specify a 1 for connection type with the NTIP  
command. For example, if the PLC is Server #5 and its IP address is 172.20.34.124, then  
the command would be 3NTIP1,172,20,34,124.  
5. Attempt a connection to the device with NTCONN. For example, if the server number is 5,  
the command would be 5NTCONN1. If the connection is successful, Network Status bit  
#1 is set (see NTS, TNTS, TNTSF). If the connection is unsuccessful, Error Status bit #23  
is set (see ER, TER, TERF).  
6. Map the required integer and binary variables between the 6K and the data files in the  
Allen-Bradley PLC. There are four mappings possible (a programming example is  
provided below).  
Use the NTMPRBcommand to read up to 50 binary elements from a PLC’s binary  
file and write them to VARBvariables in the 6K.  
nNTMPRBi,i,i,i  
EXAMPLE:  
Network Server #  
Range: 1-6  
IF:  
Allen-Bradley PLC is server #5  
The PLC’s binary data file 3 has 30  
elements. Use data elements 15-29  
(15 elements total) for binary data  
that is to be shared with the 6K.  
Use the 6K’s binary variables 35-49  
(15 variables total) to store the data  
from the PLC.  
# of Allen-Bradley data file  
# of first element in AB data file  
(beginning of range)  
# of elements in range  
# of first binary variable (VARB) in 6K  
The required mapping command is:  
5NTMPRB3,15,15,35  
(beginning of range, max value is 125)  
Use the NTMPRIcommand to read up to 50 integer elements from a PLC’s Integer  
file and write them to VARIvariables in the 6K.  
page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
nNTMPRIi,i,i,i  
EXAMPLE:  
Network Server #  
Range: 1-6  
IF:  
Allen-Bradley PLC is server #5  
The PLC’s integer data file 9 has 30  
elements. Use data elements 15-29  
(15 elements total) for integer data  
that is to be shared with the 6K.  
Use the 6K’s integer variables 35-49  
(15 variables total) to store the data  
from the PLC.  
# of Allen-Bradley data file  
# of first element in AB data file  
(beginning of range)  
# of elements in range  
# of first integer variable (VARI) in 6K  
The required mapping command is:  
5NTMPRI9,15,15,35  
(beginning of range, max value is 225)  
Use the NTMPWBcommand to write up to 50 binary values from VARBvariables in  
the 6K to binary elements in a PLC’s binary file.  
nNTMPWBi,i,i,i  
EXAMPLE:  
Network Server #  
Range: 1-6  
IF:  
Allen-Bradley PLC is server #5  
In the PLC’s binary data file 3, use  
data elements 0-14 (15 elements  
total) for binary data that is to be  
transmitted from the 6K.  
Use the 6K’s binary variables 20-34  
(15 variables total) to store the data  
to be transmitted to the PLC.  
# of Allen-Bradley data file  
# of first element in AB data file  
(beginning of range)  
# of elements in range  
# of first binary variable (VARB) in 6K  
The required mapping command is:  
5NTMPWB3,0,15,20  
(beginning of range, max value is 125)  
Use the NTMPWIcommand to write up to 50 integer values from VARIvariables in  
the 6K to a integer elements in a PLC’s integer file.  
nNTMPWIi,i,i,i  
EXAMPLE:  
Network Server #  
Range: 1-6  
IF:  
Allen-Bradley PLC is server #5  
The PLC’s integer data file 9 has 30  
elements. Use data elements 0-14  
(15 elements total) for integer data  
to be transmitted from the 6K.  
Use the 6K’s integer variables 20-34  
(15 variables total) to store the data  
to be transmitted to the PLC.  
# of Allen-Bradley data file  
# of first element in AB data file  
(beginning of range)  
# of elements in range  
# of first integer variable (VARI) in 6K  
The required mapping command is:  
5NTMPWI9,0,15,20  
(beginning of range, max value is 225)  
7. Set the polling rate with the NTPOLLcommand. 50 milliseconds is recommended. For  
example, to set the polling rate to 50 ms on Server #5, use the 5NTPOLL50command. If  
there is an error during polling, Error Status bit #24 will be set (see ER, TERor TERF).  
NTADDR172,34,54,123 ; Set the IP address of the 6K  
Example  
OPTEN0  
RESET  
; Disable the option card (for Fieldbus units only)  
NTFEN2  
RESET  
; Enable network function on 6K  
5NTIP1,172,34,54,124 ; Identify network server #5 as an Allen Bradley PLC  
; at IP address 172.34.54.124  
5NTCONN1  
; Connect to network server #5  
5NTMPRB11,7,1,106  
; File 11, element 7 in the AB PLC is mapped to the 6K's  
; binary variable VARB106  
5NTMPRI20,5,2,128  
5NTMPWB11,3,4,100  
5NTMPWI20,3,2,120  
5NTPOLL50  
; File 20, elements 5-6 in the AB PLC are mapped to  
; the 6K's integer variables VARI128-VARI129, respectively  
; File 11, elements 3-6, in the AB PLC are mapped to  
; the 6K's binary variables VARB100-VARB103  
; File 20, elements 3-4, in the AB PLC are mapped to  
; the 6K's integer variables VARI120-VARB121  
; Start polling network server #5, set interval to 50 ms.  
; *********************************************************************  
; The 6K's VARB106 will read from the PLC's File 11, element 7.  
; The 6K's VARI128-VARI129 will read from the PLC's File 20, elements 5-6.  
; The PLC's File 11, elements 3-6 will read from the 6K's VARB100-VARB103.  
; The PLC's File 20, elements 3-4 will read from the 6K's VARI120-VARB121.  
; *********************************************************************  
page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Program  
Interaction  
After the connection is established, mapping has been set up, and polling enabled, the 6K starts  
exchanging data automatically with the PLC. Here is how to:  
Write a binary variable to the PLC: Write a value to one of the VARBvariables in the  
NTMPWBmapping. The new data is written to the binary file during the next poll.  
Write an integer variable to the PLC: Write a value to one of the VARIvariables in the  
NTMPWImapping. The new data is written to the integer file during the next poll.  
Read a binary variable from the PLC: The VARBvariables in the NTMPRBmapping  
correspond to the values in the binary file in the PLC.  
Read an integer variable from the PLC: The VARIvariables in the NTMPRImapping  
correspond to the values in the integer file in the PLC.  
VARB100 = HAB79 ; Element 3 in file 10 of the AB PLC will be equal to VARB100  
Example  
if(VARB106 = B1111111111111111)  
; VARB106 will be equal to variable 7 in  
; file 10 of the AB PLC  
if(VARI129 = 17) ; Element 6 in file 20 of the AB PLC will be equal to VARI129  
VARI121 = 17 ; Element 4 in file 20 of the AB PLC will be equal to VARI121  
page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Error Conditions  
Error Messages  
The 6K will transmit error message to alert you of certain error conditions. Following are the  
error messages related to Ethernet networking.  
Error Response  
Possible Cause  
CONNECTION COULD NOT BE CLOSED OR  
ALREADY CLOSED  
Tried to close the network server connection (nNTCONNØ)  
when the connection was already closed.  
CONNECTION COULD NOT BE OPENED  
Tried NTCONN1and failed. Problem could be invalid IP  
address or it refused a connection.  
CONNECTION ERROR, CONNECTION IS  
NOW BEING CLOSED  
Connection error or timeout with server. When polling and  
get timeout or message aborted. This condition also sets  
Error Status bit #23 (see ER, TER, TERF).  
CONNECTION IS NOT OPEN  
Tried a NTWRITwhen connection is not open; or tried a  
\TANIor \TANOor \TINor \TOUTor \TIOwhen  
connection is not open.  
CONNECTION IS OPEN - MUST CLOSE  
FIRST  
Tried to open a network server connection (nNTCONN1)  
when the connection was already open.  
ERROR, INVALID FILE TYPE, NUMBER  
OR SIZE. SETTING NTMP COMMANDS  
TO 0 ELEMENTS. CHECK MAPPING.  
Tried to read the wrong Allen-Bradley PLC file type, there  
are not enough elements in the file, or the file doesn’t exist.  
The 6K automatically stop polling all mapped binary and  
integer variables (equivalent to executing the  
NTMPRBi,i,0,i, NTMPWBi,i,0,i, NTMPRIi,i,0,i,  
and NTMPWIi,i,0,i, commands).  
ERROR, INVALID STRING  
The DVT camera sent an invalid string response.  
ETHERNET CAN NOT BE USED WITH  
OPTION CARD - SEE OPTEN  
Tried to enable Ethernet communication (NTFEN) on a  
Fieldbus version of the 6K (part number is 6Kn-PB for  
PROFIBUS units, 6Kn-DN for DeviceNet units). You must  
disable the internal option card with OPTENØbefore  
enabling Ethernet communication. The 6K cannot  
communicate over a Fieldbus connection and Ethernet  
connection simultaneously.  
ETHERNET COMMUNICATION MUST BE  
ENABLED BEFORE MAKING  
Tried to connect to an Ethernet server (nNTCONN1) before  
you enabled Ethernet communication in the 6K with the  
NTFENcommand.  
CONNECTION - SEE NTFEN  
INVALID CONNECTION NUMBER  
Tried to make an NTSassignment or comparison using an  
invalid server number (e.g., VARB1 = 7NTS).  
INVALID I/O POINT  
Tried to read or write an OPTO22 I/O point that is not  
configured according to the NTIOcommand.  
INVALID POINT TYPE OR NUMBER,  
SEE NTIO  
Tried to set or read an I/O point (with an \IN, \OUT, \ANI,  
\ANO, \TANI, \TANO, \TIN, or \TOUTcommand), but that  
I/O point was configured with the NTIOcommand to be  
different I/O type.  
INVALID SERVER TYPE  
Tried an OPTO22-related command (\TANI, \TANO, \TIN,  
\TOUT, \TIO, \IN, \OUT, \ANI, \ANO, etc.) for a non-  
OPTO22 connection.  
NETWORK INPUTS AND OUTPUTS CANNOT  
BE ASSIGNED TO A VARSHO  
Tried to assign the status of OPTO22 I/O to a VARSHO  
variable.  
NETWORK IP ADDRESS CANNOT BE  
CHANGED WHILE CONNECTION IS  
OPEN, SEE NTCONN  
Tried to execute an NTIPcommand while the connection is  
open.  
NO NETWORK IP ADDRESS SPECIFIED  
FOR CONNECTION, SEE NTIP  
Tried to connect (nNTCONN1) to a server # that has not yet  
been established with the NTIPcommand, or tried to  
connect to a server in an incompatible subnet.  
NTFEN MUST BE 1 TO USE THIS  
COMMAND  
(Peer-to-peer connection only) Tried to execute an NTRATE  
command while NTFENis set to a value other than NTFEN1.  
NTRATE MUST BE 0 TO CHANGE NTFEN  
(Peer-to-peer connection only) Tried to execute an NTFEN  
command while NTRATEis set to a non-zero value.  
page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Error Response  
Possible Cause  
NTSELP ALREADY ENABLED ON THIS  
TASK  
NTSELP, which enables program selection via OPTO22  
inputs, has already been enabled (if multitasking, it has  
been enabled for this specific Task).  
OPTION CARD CAN NOT BE USED WITH  
ETHERNET - SEE NTFEN  
Tried to enable the internal Fieldbus Option card for  
PROFIBUS or DeviceNet communication (6Kn-PB and 6Kn-  
DN products only) with the OPTEN1command. You must  
disable Ethernet communications with the NTFENØ  
command before enabling the Option card. The 6K cannot  
communicate over a Fieldbus connection and Ethernet  
connection simultaneously.  
VARB USED BY OPTION CARD  
Tried to map a binary variable to read from or write to an  
Allen-Bradley data file, but the variable is already used for  
Fieldbus (PROFIBUS or DeviceNet) data transfer functions.  
VARIABLE MAPPING CONFLICT, SEE  
NTMPRB, NTMPRI, NTMPWI, NTMPWB  
MAPPINGS  
Tried to map the same 6K VARBor VARIvariables for read  
and write functions. Or tried to map the same 6K VARBor  
VARIvariables to another PLC.  
Error Handling  
The 6K has a Error Status register for logging certain error conditions. If you enable checking  
for an error condition (see ERRORcommand), the 6K will branch to the designated error  
program (see ERRORPcommand) when it detects the error condition. The Ethernet networking  
related Error Status register bits are noted below.  
ERROR  
Bit #  
Cause of the Error  
Branch Type How to Remedy the Error  
to ERRORP  
23  
Ethernet Client  
Connection Error.  
(Can’t connect.)  
Gosub  
Clear the error bit (ERROR.23-0), re-establish  
the Ethernet connection (nNTCONN1), and  
then issue ERROR.23-1.  
24  
Ethernet Client Polling Error. Gosub  
(After connect and polling  
device for data, polling  
timeout occurred. Cause  
could be disconnect, client  
lost power, etc.)  
Clear the error bit (ERROR.24-0), re-establish  
the Ethernet connection (nNTCONN1), and  
then issue ERROR.24-1.  
page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Command Descriptions  
NTCONN  
Network Connect  
Network  
<!><n>NTCONN<b>  
Type:  
Product  
Rev  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
b = Enable bit  
n = 1-6  
Range:  
Default:  
b = 0 (disconnect) or 1 (connect)  
n = 1  
b = 0  
1NTCONN: *1NTCONN0  
Response:  
See Also:  
ER, NTIP, [ NTS ], TER, TERF, TNTS, TNTSF  
The NTCONNcommand attempts the connection to the server (the server # is assigned with the NTIPcommand). If the  
connection is successful, it will be reported to the user with the message “CONNECTION SUCCESSFUL” and Network Server  
status bit #1 will be set (see NTS, TNTS, and TNTSF). If the connection is unsuccessful (e.g., attempting to connect to an  
unspecified server #, or attempting to connect to a server in an incompatible subnet), then Error Status bit #23 is set to 1  
(see ER, TER, and TERF) and the 6K transmits the error message “NO NETWORK IP ADDRESS SPECIFIED FOR  
CONNECTION, SEE NTIP”.  
Potential Error Conditions:  
If you attempt to connect to an Ethernet server before you enable Ethernet communication in the 6K with the  
NTFENcommand, the 6K will not allow the connection and will transmit the error message “ETHERNET  
COMMUNICATION MUST BE ENABLED BEFORE MAKING CONNECTION - SEE NTFEN”.  
If you attempt to execute an NTIPcommand attempt while the connection is open, the 6K will transmit the error  
message “NETWORK IP ADDRESS CANNOT BE CHANGED WHILE CONNECTION IS OPEN, SEE NTCONN”.  
If there is a connection error, a polling timeout, error message from the server (etc.), the 6K will transmit the error  
message “CONNECTION ERROR, CONNECTION IS NOW BEING CLOSED” and will also set Error Status bit #23 (see  
ER, TER, and TERF).  
Example:  
2NTIP1,172,54,125,34 ; Identify network server #2 as an Allen-Bradley PLC located at  
; IP address 172.54.125.34  
2NTCONN1  
2NTCONN0  
; Attempt connection to network server #2  
; Close the connection to network server #2  
page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
NTID  
Type:  
Network Sharing Unit ID for Peer-to-Peer Communication  
Network  
Product  
Rev  
<!>NTID<i>  
Syntax:  
Units:  
6K  
5.3  
n/a  
i = 0-8  
Range:  
Default:  
Response:  
See Also:  
i = 0 (receive variable data only, do not send variable data)  
NTID  
*NTID2  
NTRATE, VARSHI, VARSHO  
The NTIDcommand establishes the Network Unit ID for a 6K unit involved in a peer-to-peer Ethernet connection with  
other 6K or Gem6K products. Up to eight 6K or Gem6K products may be connected in the peer-to-peer network.  
Saved in Non-Volatile Memory  
This command is saved in the controller’s non-volatile memory, and is remembered on power-up  
and RESET.  
Implementation process for peer-to-peer communication (further details are provided in the Programmer’s Guide):  
1. Connect the 6K/Gem6K products to the network and configure each 6K/Gem6K for Ethernet communication  
according to the Ethernet Networking configuration procedures in the Programmer’s Guide.  
2. Set the broadcasting rate with NTRATEcommand, preferably the same rate (50 milliseconds is recommended) for  
each unit.  
3. If the unit is to receive data only (not send) you are finished with the setup for that unit. If the unit is to also send,  
complete steps 4 and 5.  
4. Assign a unique unit number (1-8) with the NTIDcommand.  
5. Assign data to the broadcast variables (up to eight) with the VARSHOcommand.  
6. Repeat steps 2-5 for each unit in the peer-to-peer network.  
Example:  
; *************************************************************************************  
; CONNECT TO 6K UNIT #1 AND SEND THE FOLLOWING SETUP COMMANDS  
NTID1  
; Assign this unit a peer-to-peer unit #1  
VARSHO1 = 1A  
VARSHO2 = 1PE  
; Shared variable #1 contains axis 1's acceleration  
; Shared variable #2 contains axis 1's encoder position  
; ```````````````````````````````````````````````````````````````````````  
; ` Use this space to define shared output variables VARSHO3 – VARSHO7. `  
; ```````````````````````````````````````````````````````````````````````  
VARSHO8 = VARI1  
NTRATE50  
; Shared variable #8 contains the value of VARI1  
; Unit #1 will broadcast at 50-millisecond intervals  
; *************************************************************************************  
; *************************************************************************************  
; CONNECT TO 6K UNIT #2 AND SEND THE FOLLOWING SETUP COMMANDS  
NTID2  
; Assign this unit a peer-to-peer unit #2  
VARSHO1 = 1D  
VARSHO2 = 3PE  
; Shared variable #1 contains axis 1's programmed distance  
; Shared variable #2 contains axis 3's encoder position  
; ```````````````````````````````````````````````````````````````````````  
; ` Use this space to define shared output variables VARSHO3 – VARSHO7. `  
; ```````````````````````````````````````````````````````````````````````  
VARSHO8 = 1ANI.1  
; Shared variable #8 contains the voltage value at analog  
; input #1 on I/O brick #1  
NTRATE50  
; Unit #2 will broadcast at 50-millisecond intervals  
; *************************************************************************************  
; *************************************************************************************  
; CONNECT TO 6K UNIT #3 AND SEND THE FOLLOWING SETUP COMMANDS  
NTRATE50  
; Unit #3 will broadcast at 50-millisecond intervals  
; This third unit will receive data only. Therefore, it does  
; not require a unit ID number or VARSHO data assignment.  
; *************************************************************************************  
page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
NTIO  
Type:  
Network I/O (OPTO22) Configuration  
Network  
Product  
Rev  
<!><n>\<m>NTIO<i>  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
m = OPTO22 I/O module #  
i = I/O module type identifier  
n = 1-6  
Range:  
m = 0-7  
i = 1 (digital inputs), 2 (digital outputs), 3 (analog inputs),  
or 4 (analog outputs)  
0\0NTIO0  
Default:  
2\3NTIO: *2\3NTIO2  
Response:  
See Also:  
\ANI,[\ANI],\ANO,[\ANO],\IN,NTCONN,NTIP,\OUT,[\OUT],\TIO  
n\mNTIO<i>  
Network Server #  
Range: 1-6  
Module Type. Options are:  
1 = Digital/Discrete Inputs  
2 = Digital/Discrete Outputs  
3 = Analog Inputs  
4 = Analog Outputs  
Module # on Server “n”  
Range: 0-7  
Use the NTIOcommand to identify to the 6K controller the type(s) of I/O modules that are used by a specific OPTO22  
server. The 6K, in turn, can use these I/O with the network I/O handling commands (\IN, \OUT, \ANI, and \ANO).  
Saved in Non-Volatile Memory  
This command is saved in the controller’s non-volatile memory, and is remembered on power-up  
and RESET.  
Implementation process for client/server connection to an OPTO22 unit (further details are provided in the Programmer’s  
Guide):  
1. Follow the manufacturer’s setup procedure for the OPTO22 Ethernet I/O rack.  
2. Connect the 6K and OPTO22 products in a network and configure the 6K for Ethernet communication according  
to the Ethernet Networking configuration procedures in the Programmer’s Guide  
3. Choose a Server Connection Number for this device. The 6K can support up to 6 simultaneous server connections.  
Pick a number (1-6) that has not been used already for another connection. This will be used to reference the  
OPTO22 unit from now on.  
4. Enter the IP address of the OPTO22 and specify a 2 for connection type with the NTIPcommand. For example, if  
the OPTO22 is Server #3 and its IP address is 172.20.34.170, then the command would be  
3NTIP2,172,20,34,170.  
5. Attempt a connection to the device with NTCONN. For example, if the server number is 3, the command would be  
3NTCONN1. If the connection is successful, Network Status bit #1 is set (see NTS, TNTS, TNTSF). If the connection  
is unsuccessful, Error Status bit #23 is set (see ER, TER, TERF).  
6. Inform the 6K of the configuration of the OPTO22. For each module position, use the NTIOcommand to specify  
the type of module in that position. For example, if there is a digital input module in slot 0, then the command  
would be 3\0NTIO1. If there is an Analog Input module in slot 7, then the command would be 3\7NTIO3.  
7. Set the polling rate with the NTPOLLcommand. 50 milliseconds is recommended. For example, to set the polling  
rate to 50 ms on server #3, use the 3NTPOLL50command. If there is an error during polling, then Error Status  
bit #24 will be set.  
Example:  
2NTIP2,172,54,125,34  
; Identify network server #2 as an OPTO22 device at IP address  
; 172.54.125.34  
2NTCONN1  
2\0NTIO1  
2\1NTIO2  
2\2NTIO3  
2NTPOLL50  
; Attempt connection to network server #2  
; Server #2 (OPTO22), module 0 is a digital input module  
; Server #2 (OPTO22), module 1 is a digital output module  
; Server #2 (OPTO22), module 2 is an analog input module  
; Start polling the OPTO22 (start reading and writing I/O),  
; set the polling interval to 50 milliseconds.  
; After this point, you can read and write to the inputs with  
page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
; the OPTO22 I/O handling commands: \ANI, [\ANI], \ANO, [\ANO],  
; \IN, \OUT, [\OUT], \TANI, \TANO, \TIN, \TIO, \TOUT  
page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NTIP  
Type:  
Network IP Address  
Network  
Product  
Rev  
<!><n>NTIP<i>,<i>,<i>,<i>,<i>  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
1st i = Server type  
2nd i = IP address octet1  
3rd i = IP address octet2  
4th i = IP address octet3  
5th i = IP address octet4  
n = 1-6  
Range:  
1st i = 1-3 (1 = Allen-Bradley PLC, 2 = OPTO22, 3 = DVT camera)  
2nd i through 5th i = 0-255.  
n = 0  
Default:  
Response:  
1st i = 1  
2nd i through 5th i = 0  
NTIP:  
*1NTIP1,172,54,125,34  
*2NTIP1,172,54,125,67  
*3NTIP ...  
(shows config. of all servers)  
1NTIP:  
*1NTIP1,172,54,125,34  
ER, NTADDR, NTCONN, NTMASK, [ NTS ], TNTS, TNTSF  
See Also:  
<n>NTIP<i>,<i>,<i>,<i>,<i>  
Network Server #  
Range: 1-6  
IP Address of Server.  
Range for each octet = 0-255.  
For example, to enter an address of  
Server Type.  
1 = Allen-Bradley PLC  
2 = OPTO22 (MODBUS/TCP)  
3 = DVT Vision Camera  
172.20.34.246, type in 172,20,34,246  
(be sure to use commas instead of  
periods between the octets).  
The NTIPcommand describes the type of connection the 6K controller will make with a server, and it specifies the IP  
address of the server.  
Saved in Non-Volatile Memory  
This command is saved in the controller’s non-volatile memory, and is remembered on power-up  
and RESET.  
Potential Error Conditions:  
A valid IP address for the designated server must be specified or the 6K connection will timeout and Error Status  
bit #23 (see ER, TER, and TERF) will be set to 1, and the NTS/TNTS/TNTSFreports will indicate which connection  
was in error.  
The subnet address must be the same for the 6K and any server it connects to, or a connection error (ER.23) will  
occur. For example, if the subnet mask is 255.255.255.0 (class C) and the 6K’s address is 172.20.34.246, then  
every server it connects to must have an address of 172.20.34.x.  
Example:  
2NTIP1,172,54,125,34  
; Identify network server #2 as an Allen-Bradley PLC  
; (Server Type #1) at IP address 172.54.125.34  
page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
NTMPRB  
Network Map Binary Variables for Reading from PLC  
Network  
Type:  
Product  
Rev  
<!><n>NTMPRB<i>,<i>,<i>,<i>  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
1st i = Allen Bradley data file #  
2nd i = # of the 1st element in data file (beginning of range)  
3rd i = # of the elements to include in range  
4th i = # of the 1st binary (VARB) variable in the 6K to map to  
n = 1-6  
Range:  
1st i = 0-n (n depends on size of file)  
2nd i = 0-n (n depends on size of file)  
3rd i = 0 or 1-50 (0 disables polling for this mapping only)  
4th i = 1-125  
1NTMPRB0,0,0,0 (no mapping)  
1NTMPRB: *1NTMPRB1,5,15,23  
Default:  
Response:  
See Also:  
NTCONN, NTIP, NTMPWB, NTMPWI, NTMPRI, NTPOLL, [ NTS ], TNTS,  
TNTSF, VARB  
<n>NTMPRB<i>,<i>,<i>,<i>  
EXAMPLE:  
Network Server #  
Range: 1-6  
IF:  
Allen-Bradley PLC is server #2  
The PLC’s binary data file 3 has 30  
elements. Use data elements 15-29  
(15 elements total) for binary data  
that is to be shared with the 6K.  
# of Allen-Bradley data file  
# of first element in AB data file  
(beginning of range)  
Use the 6K’s binary variables 35-49  
(15 variables total) to store the data  
from the PLC.  
The required mapping command is:  
2NTMPRB3,15,15,35  
# of elements in range  
# of first binary variable (VARB) in 6K  
(beginning of range, max value is 125)  
The NTMPRBcommand maps a range of binary data elements from the AB PLC to a range of binary (VARB) variables in the  
6K. There are 125 VARBvariables available in the 6K for storing binary data. To perform a binary read from the PLC:  
1. Assign the AB PLC a server number, according to its IP address (NTIPcommand).  
2. Connect to the AB PLC, according to its server number (NTCONNcommand).  
3. Map a range of binary elements in the AB PLC to a range of binary (VARB) variables in the 6K (NTMPRB  
command).  
4. Start polling the AB device at a specific polling interval (NTPOLLcommand). This updates the 6K binary (VARB)  
variables with the binary element data from the AB PLC. You can then use the PLC binary data (via the VARB  
variables) in conditional expressions, command value substitutions and variable assignments.  
Saved in Non-Volatile Memory  
This command is saved in the controller’s non-volatile memory, and is remembered on power-up  
and RESET.  
Potential Error Conditions:  
You are not allowed to map the same 6K VARBvariables for read and write functions. Nor are you allowed to map  
the same 6K VARBvariables to another PLC. If you attempt either of these conditions, the 6K will not accept the  
NTMPRBcommand and will transmit the error message “VARIABLE MAPPING CONFLICT…”.  
If you attempt to read from an AB data file of the wrong type, or read from a non-existent data element, the 6K will  
not accept the NTMPRBcommand, it will transmit the error message “ERROR, INVALID FILE TYPE, NUMBER  
OR SIZE…” and it will automatically stop polling all mapped binary and integer variables (equivalent to executing  
the NTMPRBi,i,0,i, NTMPWBi,i,0,i, NTMPRIi,i,0,i, and NTMPWIi,i,0,i, commands).  
Control over Polling: If you want to stop the 6K from reading binary data from the PLC, but continue to exchange  
NTMPRI, NTMPWIand NTMPWBdata, use the NTMPRBi,i,0,icommand. If you need to stop polling all mapped variables,  
use the nNTPOLL0command.  
Example:  
2NTIP1,172,54,125,34  
; Identify network server #2 as an Allen-Bradley PLC at  
page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
; IP address 172.54.125.34  
2NTCONN1  
2NTMPRB3,15,15,35  
; Attempt connection to network server #2  
; File 3, elements 15-29, in the AB PLC are mapped to  
; the 6K's binary variables VARB35-VARB49  
; Start polling network server #2, set interval to 50 ms  
; Wait until the value of VARB40 (mapped to file 3,  
; element 20, in the PLC) is 1111111100000000  
2NTPOLL50  
WAIT(VARB40=b1111111100000000)  
NTMPWB  
Network Map Binary Variables for Writing to PLC  
Network  
Type:  
Product  
Rev  
<!><n>NTMPWB<i>,<i>,<i>,<i>  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
1st i = Allen Bradley data file #  
2nd i = # of the 1st element in data file (beginning of range)  
3rd i = # of the elements to include in range  
4th i = # of the 1st binary (VARB) variable in the 6K to map to  
n = 1-6  
Range:  
1st i = 0-n (n depends on size of file)  
2nd i = 0-n (n depends on size of file)  
3rd i = 0 or 1-50 (0 disables polling for this mapping only)  
4th i = 1-125  
1NTMPWB0,0,0,0 (no mapping)  
1NTMPWB: *1NTMPWB1,5,15,23  
Default:  
Response:  
See Also:  
NTCONN, NTIP, NTMPRB, NTMPWI, NTMPRI, NTPOLL, [ NTS ], TNTS,  
TNTSF, VARB  
<n>NTMPWB<i>,<i>,<i>,<i>  
EXAMPLE:  
Network Server #  
Range: 1-6  
IF:  
Allen-Bradley PLC is server #2  
In the PLC’s binary data file 3, use  
data elements 0-14 (15 elements  
total) for binary data that is to be  
transmitted from the 6K.  
# of Allen-Bradley data file  
# of first element in AB data file  
(beginning of range)  
Use the 6K’s binary variables 20-34  
(15 variables total) to store the data  
to be transmitted to the PLC.  
The required mapping command is:  
2NTMPWB3,0,15,20  
# of elements in range  
# of first binary variable (VARB) in 6K  
(beginning of range, max value is 125)  
The NTMPWBcommand maps a range of binary data elements from the AB PLC to a range of binary (VARB) variables in the  
6K. There are 125 VARBvariables available in the 6K for exchanging binary data. To perform a binary write to the PLC:  
1. Assign the AB PLC a server number, according to its IP address (NTIPcommand).  
2. Connect to the AB PLC, according to its server number (NTCONNcommand).  
3. Map a range of binary elements in the AB PLC to a range of binary (VARB) variables in the 6K (NTMPWB  
command).  
4. Start polling the AB device at a specific polling interval (NTPOLLcommand). This updates binary data elements in  
the AB PLC with the data from the mapped VARBvariables in the 6K.  
Saved in Non-Volatile Memory  
This command is saved in the controller’s non-volatile memory, and is remembered on power-up  
and RESET.  
Potential Error Conditions:  
You are not allowed to map the same 6K VARBvariables for read and write functions. Nor are you allowed to map  
the same 6K VARBvariables to another PLC. If you attempt either of these conditions, the 6K will not accept the  
NTMPWBcommand and will transmit the error message “VARIABLE MAPPING CONFLICT…”.  
If you attempt to write to an AB data file of the wrong type, or to a non-existent data element, the 6K will not  
accept the NTMPWBcommand, it will transmit the error message “ERROR, INVALID FILE TYPE, NUMBER OR  
SIZE…” and it will automatically stop polling all mapped binary and integer variables (equivalent to executing the  
NTMPRBi,i,0,i, NTMPWBi,i,0,i, NTMPRIi,i,0,i, and NTMPWIi,i,0,i, commands).  
page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Control over Polling: If you want to stop the 6K from writing binary data to the PLC, but continue to exchange NTMPRI,  
NTMPWIand NTMPRBdata, use the NTMPWBi,i,0,icommand. If you need to stop polling all mapped variables, use the  
nNTPOLL0command.  
Example:  
2NTIP1,172,54,125,34  
; Identify network server #2 as an Allen-Bradley PLC at  
; IP address 172.54.125.34  
2NTCONN1  
; Attempt connection to network server #2  
2NTMPWB3,0,15,20  
; File 3, elements 0-14, in the AB PLC are mapped to  
; the 6K's binary variables VARB20-VARB34  
2NTPOLL50  
VARB25 = b1111000011110000  
; Start polling network server #2, set interval to 50 ms  
; The value of AB file 3, element 5, will be set to  
; 111000111000, because it is mapped to VARB25  
NTMPRI  
Network Map Integer Variables for Reading from PLC  
Network  
Type:  
Product  
Rev  
<!><n>NTMPRI<i>,<i>,<i>,<i>  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
1st i = Allen Bradley data file #  
2nd i = # of the 1st element in data file (beginning of range)  
3rd i = # of the elements to include in range  
4th i = # of the 1st integer (VARI) variable in the 6K to map to  
n = 1-6  
Range:  
1st i = 0-n (n depends on size of file)  
2nd i = 0-n (n depends on size of file)  
3rd i = 0 or 1-50 (0 disables polling for this mapping only)  
4th i = 1-225  
1NTMPRI0,0,0,0 (no mapping)  
1NTMPRI: *1NTMPRI1,5,15,23  
Default:  
Response:  
See Also:  
NTCONN, NTIP, NTMPRB, NTMPWB, NTMPWI, NTPOLL, [ NTS ], NTSELP,  
TNTS, TNTSF, VARI  
<n>NTMPRI<i>,<i>,<i>,<i>  
EXAMPLE:  
Network Server #  
Range: 1-6  
IF:  
Allen-Bradley PLC is server #2  
The PLC’s integer data file 9 has 30  
elements. Use data elements 15-29  
(15 elements total) for integer data  
that is to be shared with the 6K.  
# of Allen-Bradley data file  
# of first element in AB data file  
(beginning of range)  
Use the 6K’s integer variables 35-49  
(15 variables total) to store the data  
from the PLC.  
The required mapping command is:  
2NTMPRI9,15,15,35  
# of elements in range  
# of first integer variable (VARI) in 6K  
(beginning of range, max value is 225)  
The NTMPRIcommand maps a range of integer data elements from the AB PLC to a range of integer (VARI) variables in  
the 6K. There are 225 VARIvariables available in the 6K for storing integer data. To perform an integer data read from the  
PLC:  
1. Assign the AB PLC a server number, according to its IP address (NTIPcommand).  
2. Connect to the AB PLC, according to its server number (NTCONNcommand).  
3. Map a range of integer elements in the AB PLC to a range of integer (VARI) variables in the 6K (NTMPRI  
command).  
4. Start polling the AB device at a specific polling interval (NTPOLLcommand). This updates the 6K integer (VARI)  
variables with the integer element data from the AB PLC. You can then use the PLC integer data (via the VARI  
variables) in conditional expressions, command value substitutions and variable assignments.  
Saved in Non-Volatile Memory  
This command is saved in the controller’s non-volatile memory, and is remembered on power-up  
and RESET.  
page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Potential Error Conditions:  
You are not allowed to map the same 6K VARIvariables for read and write functions. Nor are you allowed to map  
the same 6K VARIvariables to another PLC. If you attempt either of these conditions, the 6K will not accept the  
NTMPRIcommand and will transmit the error message “VARIABLE MAPPING CONFLICT…”.  
If you attempt to read from an AB data file of the wrong type, or read from a non-existent data element, the 6K will  
not accept the NTMPRIcommand, it will transmit the error message “ERROR, INVALID FILE TYPE, NUMBER  
OR SIZE…” and it will automatically stop polling all mapped binary and integer variables (equivalent to executing  
the NTMPRBi,i,0,i, NTMPWBi,i,0,i, NTMPRIi,i,0,i, and NTMPWIi,i,0,i, commands).  
Control over Polling: If you want to stop the 6K from reading integer data from the PLC, but continue to exchange  
NTMPWI, NTMPRBand NTMPWBdata, use the NTMPRIi,i,0,icommand. If you need to stop polling all mapped variables,  
use the nNTPOLL0command.  
Example:  
2NTIP1,172,54,125,34  
; Identify network server #2 as an Allen-Bradley PLC at  
; IP address 172.54.125.34  
2NTCONN1  
2NTMPRI9,15,15,35  
; Attempt connection to network server #2  
; File 9, elements 15-29, in the AB PLC are mapped to  
; the 6K's integer variables VARI35-VARI49  
; Start polling network server #2, set interval to 50 ms  
; Wait until the value of VARI40 (mapped to file 9,  
; element 20, in the PLC) is 22  
2NTPOLL50  
WAIT(VARI40=22)  
NTMPWI  
Network Map Integer Variables for Writing to PLC  
Network  
Type:  
Product  
Rev  
<!><n>NTMPWI<i>,<i>,<i>,<i>  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
1st i = Allen Bradley data file #  
2nd i = # of the 1st element in data file (beginning of range)  
3rd i = # of the elements to include in range  
4th i = # of the 1st integer (VARI) variable in the 6K to map to  
n = 1-6  
Range:  
1st i = 0-n (n depends on size of file)  
2nd i = 0-n (n depends on size of file)  
3rd i = 0 or 1-50 (0 disables polling for this mapping only)  
4th i = 1-225  
1NTMPWI0,0,0,0 (no mapping)  
1NTMPWI: *1NTMPWI1,5,15,23  
Default:  
Response:  
See Also:  
NTCONN, NTIP, NTMPRB, NTMPRI, NTMPWB, NTPOLL, [ NTS ], TNTS,  
TNTSF, VARI  
<n>NTMPWI<i>,<i>,<i>,<i>  
EXAMPLE:  
Network Server #  
Range: 1-6  
IF:  
Allen-Bradley PLC is server #2  
The PLC’s integer data file 9 has 30  
elements. Use data elements 0-14  
(15 elements total) for integer data  
to be transmitted from the 6K.  
# of Allen-Bradley data file  
# of first element in AB data file  
(beginning of range)  
Use the 6K’s integer variables 20-34  
(15 variables total) to store the data  
to be transmitted to the PLC.  
The required mapping command is:  
2NTMPWI9,0,15,20  
# of elements in range  
# of first integer variable (VARI) in 6K  
(beginning of range, max value is 225)  
The NTMPWIcommand maps a range of integer data elements from the AB PLC to a range of integer (VARI) variables in  
the 6K. There are 225 VARIvariables available in the 6K for exchanging integer data. To perform a integer write to the  
PLC:  
1. Assign the AB PLC a server number, according to its IP address (NTIPcommand).  
2. Connect to the AB PLC, according to its server number (NTCONNcommand).  
page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Map a range of integer elements in the AB PLC to a range of integer (VARI) variables in the 6K (NTMPWI  
command).  
4. Start polling the AB device at a specific polling interval (NTPOLLcommand). This updates integer data elements  
in the AB PLC with the data from the mapped VARIvariables in the 6K.  
NOTE: The VARIvariables in the 6K are 32 bit values, but the integers in the AB PLC are 16 bit values.  
Therefore, the range for the VARIvariables must be kept in the range –32767 to +32767.  
Saved in Non-Volatile Memory  
This command is saved in the controller’s non-volatile memory, and is remembered on power-up  
and RESET.  
Potential Error Conditions:  
You are not allowed to map the same 6K VARIvariables for read and write functions. Nor are you allowed to map  
the same 6K VARIvariables to another PLC. If you attempt either of these conditions, the 6K will not accept the  
NTMPWIcommand and will transmit the error message “VARIABLE MAPPING CONFLICT…”.  
If you attempt to write to an AB data file of the wrong type, or to a non-existent data element, the 6K will not  
accept the NTMPWIcommand, it will transmit the error message “ERROR, INVALID FILE TYPE, NUMBER OR  
SIZE…” and it will automatically stop polling all mapped binary and integer variables (equivalent to executing the  
NTMPRBi,i,0,i, NTMPWBi,i,0,i, NTMPRIi,i,0,i, and NTMPWIi,i,0,i, commands).  
Control over Polling: If you want to stop the 6K from writing integer data to the PLC, but continue to exchange NTMPRI,  
NTMPRBand NTMPWBdata, use the NTMPWIi,i,0,icommand. If you need to stop polling all mapped variables, use the  
nNTPOLL0command.  
Example:  
2NTIP1,172,54,125,34  
; Identify network server #2 as an Allen-Bradley PLC at  
; IP address 172.54.125.34  
2NTCONN1  
2NTMPWI9,0,15,20  
; Attempt connection to network server #2  
; File 9, elements 0-14, in the AB PLC are mapped to  
; the 6K's integer variables VARI20-VARI34  
; Start polling network server #2, set interval to 50 ms  
; The value of AB file 9, element 5, will be set to 42,  
; because it is mapped to VARI25  
2NTPOLL50  
VARI = 42  
NTPOLL  
Network Polling Rate  
Network  
Type:  
Product  
Rev  
<!><n>NTPOLL<i>  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
i = polling rate (milliseconds)  
n = 1-6  
Range:  
i = 0 (disable polling) or 1-9999 (50 is recommended)  
0 (disabled)  
Default:  
1NTPOLL: *1NTPOLL50  
Response:  
See Also:  
NTIP, NTCONN, NTMPRB, NTMPRI, NTMPWB, NTMPWI  
The NTPOLLcommand establishes the rate at which the 6K polls the Ethernet server devices for information:  
Allen-Bradley PLC Devices: NTPOLLsets the rate at which the 6K reads and writes the VARIand VARBvariables  
that are mapped to the Allen-Bradley PLC. Variables are mapped with the NTMPRB, NTMPRI, NTMPWBand NTMPWI  
commands.  
OPTO22: NTPOLLsets the rate for polling or changing the states of the input and output modules on the OPTO22.  
OPTO22 outputs are controlled with the \OUTand \ANOcommands, and the inputs are monitored with the \IN,  
\ANI, \TANI, \TANO, \TIN, \TIO, \TOUTcommands.  
The polling rate affects the 6K overall command execution speed (slowing the polling rate will speed up the 6K’s  
command processing).  
page 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
The NTPOLLcommand is not saved in the 6K’s non-volatile memory. If you wish the 6K to re-establish the NTPOLLpolling  
rate when you cycle power or issue a RESETcommand, put the NTPOLLcommand in the startup program assigned with the  
STARTPcommand.  
Example:  
2NTIP1,172,54,125,34  
; Identify network server #2 as an Allen-Bradley PLC at  
; IP address 172.54.125.34  
2NTCONN1  
; Attempt connection to network server #2  
2NTMPRI20,5,2,128  
; File 20, variables 5 and 6 in the AB PLC are mapped to VARI128  
; and VARI129, respectively  
2NTPOLL50  
; Start polling network server #2, set interval to 50 milliseconds  
NTRATE  
Network Sharing Rate for Peer-to-Peer Communication  
Network  
<!>NTRATE<i>  
Type:  
Product  
Rev  
Syntax:  
Units:  
6K  
5.3  
i = milliseconds  
0 (off) to 1000  
0 (off)  
(50 milliseconds is recommend)  
Range:  
Default:  
Response:  
See Also:  
NTRATE:  
*NTRATE50  
NTFEN, NTID, SYSPER, VARSHO, VARSHI  
Use the NTRATEcommand to establish the broadcast rate for VARSHOinformation packets to other 6K units. With  
NTRATE0, broadcasting and listening to other units that are broadcasting is disabled. With a value > 0, it is enabled. A rate  
of 50 is recommended. All sharing units should have the same NTRATE. NTRATEis not accepted unless the 6K is operating  
in NTFEN1mode.  
Each 6K unit internally updates its VARSHOdata at the System Update Rate (2 milliseconds); therefore, the NTRATE  
command must be set to a value of 2 milliseconds. If you lengthen the System Update Rate (see SYSPER), increase the  
NTRATEvalue accordingly.  
The NTRATEcommand is not saved in the 6K’s non-volatile memory. If you wish the 6K to re-establish the NTRATE  
broadcasting rate when you cycle power or issue a RESETcommand, put the NTRATEcommand in the startup program  
assigned with the STARTPcommand.  
Example:  
; *************************************************************************************  
; Send these setup commands to 6K unit #1  
NTID1  
; Set unit 1's network ID to 1  
NTRATE50  
; Unit 1 will broadcast at 50-millisecond intervals  
; *************************************************************************************  
; *************************************************************************************  
; Send these setup commands to 6K unit #2  
NTID2  
; Set unit 2's network ID to 2  
NTRATE50  
; Unit 2 will broadcast at 50-millisecond intervals  
page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
[ NTS ]  
Type:  
Network Status  
Network; Assignment/Comparison  
Product  
Rev  
nTNTS<.i>  
Syntax:  
Units:  
6K  
5.3  
n = server #  
i = bit number of status register (see table below)  
n = 1-6  
Range:  
i = 1-8  
n/a  
Default:  
n/a  
Response:  
See Also:  
NTCONN, NTIP, NTPOLL, TNTSF  
Use the NTSoperand to assign the Network Status bits to a binary variable, or to make a comparison against a binary or  
hexadecimal value.  
Syntax: VARBx=nNTSwhere “n” is the network server number (e.g., VARB16=2NTS). The NTSoperand can also be used  
in an expression such as IF(2NTS=b11Ø1), or IF(2NTS=h7F). To make a comparison against a binary value,  
place the letter b (b or B) in front of the value. The binary value itself must only contain ones, zeros, or Xs (1, Ø,  
X, x). To make a comparison against a hexadecimal value, place the letter h (h or H) in front of the value. The  
hexadecimal value itself must only contain the letters A through F, or the numbers Ø through 9.  
Bit Select Operation: Use the bit select operator (.) in conjunction with the bit number to specify a specific  
Network Status bit. Examples: VARB1=2NTS.3assigns Network Status bit 3 for network server 2 to binary  
variable 1; IF(2NTS.3=b1)is a conditional statement that is true if Network Status bit 3 for network server 2 is  
set to 1 (polling is enabled).  
Bit #  
(left to right)  
Function (1 = yes, 0 = no)  
1
2
Connection Open.  
Client Connection Error. This bit is set when a connection attempt with a server times out. This will  
also set Error Status bit #23 (see ER, TER, TERF).  
3
4
Polling Enabled. This bit is set when polling is enabled with NTPOLL.  
Error during polling. This bit is set when an error during polling occurs. This will also set Error Status  
bit #24 (see ER, TER, TERF).  
5-8  
Reserved  
NTSELP  
Network Program Select Enable  
Network  
Type:  
Product  
Rev  
<!>NTSELP<b>,<i>  
Syntax:  
Units:  
6K  
5.3  
b = enable bit  
i = number of the integer variable (VARI) used for program  
select  
b = 0 (disable) or 1 (enable)  
i = 1-225  
Range:  
Default:  
b = 0 (disabled)  
i = 1  
NTSELP:  
*NTSELP0,1  
Response:  
See Also:  
COMEXS, NTCONN, NTIP, NTMPRI, NTMPWI, NTPOLL, [ NTS ], TDIR,  
TNTS, TNTSF  
The NTSELPcommand allows you to enable/disable the Network Program Select Mode, where, through the process of  
exchanging integer data, an Allen-Bradley PLC can execute a 6K/Gem6K program by its number. Use the following  
procedure as a guideline for implementing the Network Program Select mode:  
1. Setup up Ethernet Networking with the Allen-Bradley PLC. This includes assigning the server connection (NTIP)  
and connecting (NTCONN).  
2. Use the NTMPRIcommand to map at least one 6K variable to an Element in an integer data file in the PLC.  
page 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Start polling the PLC for integer data (NTPOLL). When the 6K polls the PLC, it will read the value of the mapped  
Element into the associated 6K integer variable (VARI).  
4. Use the NTSELPcommand to enable the Network Program Select mode and identify the 6K integer variable (VARI)  
to supply the program selection number. Once enabled, the 6K will poll the PLC (at the NTPOLLrate), read the  
integer data from the PLC into the mapped VARIvariable, and execute the program (by number) according to the  
value of the mapped VARIvariable. After executing and completing the selected program, the controller will  
resume polling the inputs again. To disable the Network Program Select mode, place the NTSELPØcommand in a  
program that can be selected.  
5. Program the PLC to set the Element value to select the program (by its number) in the 6K. For example, suppose  
Element #4 of File #2 is mapped to the 6K’s integer variable #9. If the value of Element #4 is 8 when it is polled, the  
6K will execute program #8.  
WHAT IS THE PROGRAM NUMBER?  
A program’s number is determined by the order in which the program was downloaded to the controller. The  
first program downloaded is program #1, the second downloaded is program #2, etc. The number of each  
program stored in the controller's memory can be obtained through the TDIRreport — refer to the number  
reported in front of each program name. When selecting programs with an integer variable (mapped to an  
Element in the PLC data file), the 6K will execute the program number that matches the value of the variable  
at the time the associated Element was polled from the PLC.  
Multi-Tasking: If you are using multi-tasking, be aware that each Task has its own Network Program Select Mode. If you  
wish to enable variable-initiated program selection in an external task (a task other than the task that is executing the  
NTSELPcommand), then you must prefix the NTSELPcommand to address the targeted task. For example 3%NTSELP1,40  
enables Network Program Select Mode in Task #3, and uses the value of VARI40to program the number of the program to  
execute.  
What conditions can disable the Network Program Select Mode?  
Executing the Kill (!K) command  
Executing the Stop (!S) command, or activating an input defined as a stop input (see INFNCor LIMFNC). This  
disables Program Select Mode only if the Task is operating in the COMEXS2mode.  
Example:  
2NTIP1,172,54,125,34  
; Network server #2 is an Allen-Bradley PLC at IP address  
; 172.54.125.34  
2NTCONN1  
; Attempt connection to network server #2  
2NTMPRI20,5,2,128  
; VARI128 and VARI129 (in the 6K) are mapped to File 20, Elements  
; 5 and 6 in the AB PLC. The values of VARI128 and VARI129 will be  
; derived from the values of File 20, elements 5 and 6 in the PLC.  
; Start polling the AB PLC, set polling interval to 50 ms  
; VARI128 is the network program select variable, which is mapped  
; with File 20, Element 5, in the AB PLC. When the 6K polls  
; Element 5, it will execute the program according to the value  
; of Element 5. The program will be executed in Task 3.  
2NTPOLL50  
3%NTSELP1,128  
NTWRIT  
Network Write ASCII String to DVT Camera  
Network  
Type:  
Product  
Rev  
<!><n>NTWRIT"<message>"  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
message = ASCII string  
n = 1-6  
Range:  
message = up to 69 characters (cannot use ", ; or :)  
n/a  
Default:  
n/a  
Response:  
See Also:  
NTIP  
Use the NTWRITcommand to write ASCII strings to the DVT camera. If you address the NTWRITcommand to a non-DVT  
connection (see NTIP), the 6K transmits the error message “INVALID SERVER TYPE”.  
Example:  
page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2NTIP3,172,54,125,34 ; Network server #2 a DVT camera at IP address 172.54.125.34  
2NTCONN1  
; Attempt connection to the DVT camera  
2NTWRIT"P134"  
; Write the string "P134" to the DVT camera  
TNTS  
Transfer Network Status  
Network  
<!><n>TNTS<.i>  
Type:  
Product  
Rev  
Syntax:  
Units:  
6K  
5.3  
n = server #  
i = bit number of status register (see table below)  
n = 1-6  
i = 1-8  
n/a  
Range:  
Default:  
TNTS:  
*TNTS:  
(displays status of all six servers)  
1TNTS 0000_0000  
Response:  
2TNTS 0000_0000  
3TNTS 0000_0000  
4TNTS 0000_0000  
5TNTS 0000_0000  
6TNTS 0000_0000  
2TNTS:  
*2NTS  
1010_0000 (status for server 2)  
2TNTS.3: *2TNTS.3  
TNTS.3: *TNTS.3  
1
(bit 3 for server 2)  
110000  
(bit 3 for all six servers)  
NTCONN, NTIP, NTPOLL, [ NTS ], TNTSF  
See Also:  
The TNTScommand returns the current status of all network server connections. To use the Network Status register  
conditions in a conditional expression or for a binary variable assignment, use the NTSassignment/comparison operand.  
FULL-TEXT STATUS REPORT AVAILABLE  
The TNTSstatus command reports a binary bit report. If you would like to see a more descriptive text-  
based report, use the TNTSFcommand description.  
Bit #  
(left to right)  
Function (1 = yes, 0 = no)  
1
2
Connection Open.  
Client Connection Error. This bit is set when a connection attempt with a server times out. This will  
also set Error Status bit #23 (see ER, TER, TERF).  
3
4
Polling Enabled. This bit is set when polling is enabled with NTPOLL.  
Error during polling. This bit is set when an error during polling occurs. This will also set Error Status  
bit #24 (see ER, TER, TERF).  
5-8  
Reserved  
TNTSF  
Transfer Network Status (full-text report)  
Product Rev  
Type  
Syntax <!>TNTSF  
Units N/A  
Network  
6K  
N.N.N  
Range N/A  
Default N/A  
Response  
*TNTSF: (see example below)  
See Also NTCONN, NTIP, NTCLS, NTPOLL, [ NTS ], TNTS  
The TNTSFcommand returns a text-based status report of network server connections. This is an alternative to the binary  
report (TNTS). Example TNTSFresponse:  
*TNTSF  
*
Connection #  
1
2
3
4
5
6
page 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
*Connection Open  
YES NO NO NO NO NO  
*Server Connection Error NO NO NO NO NO NO  
*In Polling Mode  
*Polling Timeout Error  
*
YES NO NO NO NO NO  
NO NO NO NO NO NO  
*Reserved  
*Reserved  
*Reserved  
*Reserved  
NO NO NO NO NO NO  
NO NO NO NO NO NO  
NO NO NO NO NO NO  
NO NO NO NO NO NO  
VARSHI  
Type:  
Shared Input Variable for Peer-to-Peer Data Exchange  
Variable; Network  
Product  
Rev  
<!><n>VARSHI<i>  
Syntax:  
6K  
5.3  
(see diagram below for assignment syntax)  
n = unit number in the peer-to-peer network;  
i = VARSHO number from unit “n”  
Units:  
n = 1-8;  
i = 1-8  
Range:  
n/a  
Default:  
1VARSHI1: *1VARSHI1=0.0  
IN, VAR, VARB, VARI, VARSHO  
Response:  
See Also:  
The VARSHIcommand helps you use shared data over a peer-to-peer Ethernet connection with other 6K or Gem6K  
products. VARSHIcan be used to assign the integer or binary VARSHOdata to a VAR(numeric), VARI(integer), or VARB  
(binary) variable, or to a virtual input brick (IN). You can also use VARSHIin a conditional statement, such as IF, WAIT,  
WHILE, or UNTIL.  
The diagram below shows the syntax requirements for assigning VARSHIdata to a variable:  
<assignment> = <n>VARSHI<i>  
Assignment options:  
Number of the VARSHO  
variable from unit <n>  
<variable>n  
Variable number  
Number of the source unit  
(use this unit’s VARSHO  
data)  
VAR(numeric variable)  
VARI(integer variable)  
VARB(binary variable)  
n IN (virtual input assignment)  
I/O brick number.  
Range: 1-8  
Must be an unused I/O brick  
The Implementation Process, beginning on page 8, identifies how to use the VARSHIcommand in  
context with the process of setting up the peer-to-peer Ethernet data sharing.  
Example: This example uses peer-to-peer communication with three 6K8 products.  
;**** This code is executed on Peer unit #1: **************************  
NTID1  
; This unit is the "primary unit" (unit #1)  
NTRATE100  
VARSHO1=1PE  
; Set the sharing rate to 100ms and enable this unit  
; Store axis #1 encoder position in shared output variable #1  
;*************************************************************************  
;**** This code is executed on unit #3: **************************  
NTID3  
; Set unit ID to 3  
NTRATE100  
VARSHO2=4PCEA  
; Set the sharing rate to 100ms and enable this unit  
; Store the captured encoder position of axis #4 in shared  
; output variable #2  
VARSHO1=3AS  
; Store axis #3's axis status (binary data) in shared  
; output variable #1  
;*************************************************************************  
page 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
;**** This code is executed on unit #2: **************************  
NTID2  
; Set unit ID to 2  
NTRATE100  
VAR1=1VARSHI1  
; Set the sharing rate to 100ms and enable this unit  
; Load the value of unit #1's first shared data (1PE) into VAR1  
WRITE"AXIS 1 AT POSITION" ; Report axis 1's current position (the value of VAR1)  
WRVAR1  
VAR2=8PCEA-3VARSHI2  
; Calculate offset position: Subtract synch unit #3's  
; VARSHO2 (4PCEA) from the captured encoder position  
; of axis #8 (8PCEA).  
IF(VAR2>10000)  
; If position offset by more than 10000 encoder counts  
WRITE"AXIS 20 OUT OF POSITION"  
NIF  
VARB1=3VARSHI1  
IF(VARB1=B1)  
; Get unit 3's VARSHO1 information (3AS)  
; If axis 3 on unit #3 (axis #19) is in motion  
WRITE"AXIS 19 IN MOTION"  
NIF  
;*************************************************************************  
VARSHO  
Shared Output Variable for Peer-to-Peer Data Exchange  
Variable; Network  
<!>VARSHO<i><=xx>  
Type:  
Product  
Rev  
Syntax:  
Units:  
6K  
5.3  
i = variable number  
xx = 32-bit data operand (see list below)  
i = 1-8  
n/a  
Range:  
Default:  
VARSHO1:  
*VARSHO1=PME  
Response:  
See Also:  
NTRATE, VAR, VARB, VARI, VARSHI  
The VARSHOcommand is used to set up data to be shared over a peer-to-peer Ethernet connection (i.e., connection between  
other 6K or Gem6K products).  
Each unit on the Ethernet peer-to-peer network has eight “shared output” variables (VARSHO1through VARSHO8) with which  
it can share with other units the values of its motion attributes, controller status, variables, etc. (see list below). The type of  
data can be either binary, as in the AS(axis status) operand, or a 32-bit unscaled integer, as in PE(encoder position)  
operand. The data stored in the VARSHOis not scaled.  
For example, unit #2 could execute VARSHO1=3PEto share the encoder position of axis #3 in shared output variable #1.  
Each unit will re-broadcast its updated VARSHOdata at a rate set with the NTRATEcommand.  
RECOMMENDATION: Set all devices to broadcast at the same NTRATErate of 50 milliseconds.  
The Implementation Process, beginning on page 8, identifies how to use the VARSHOcommand in  
context with the process of setting up the peer-to-peer Ethernet data sharing.  
Options for shared data in the VARSHOvariable:  
A.........Acceleration  
NMCY...Master cycle number  
OUT......Output status  
SS..........System status  
AD.......Deceleration  
SWAP.....Task swap assignment  
TASK.....Task number  
ANI.....Analog input voltage  
ANO.....Analog output voltage  
AS.......Axis status  
PANI...Analog input position  
PC........Commanded position  
PCC......Captured command pos.  
PCE......Captured encoder pos.  
PCME...Captured master enc. pos.  
PE........Encoder position  
TIM.......Timer value  
TRIG.....Trigger interrupt status  
US..........User-defined status  
V............Velocity  
ASX.....Extended axis status  
D.........Distance  
DAC.....DAC output value  
DKEY...RP240 keypad value  
ER.......Error status  
VARI.....Integer variable  
VARB.....Binary variable  
VEL.......Commanded velocity  
VELA.....Actual velocity  
PER......Position error  
PMAS...Position of Master  
PME......Master encoder pos.  
PSHF...Net position shift  
FB.......Feedback device pos.  
FS.......Following status  
IN.......Input status  
VMAS.....Velocity of the master  
VARSHI.Shared input variable  
PSLV...Follower pos. command  
SC........Controller status  
INO.....Enable input status  
LIM.....Limit input status  
MOV.....Axis moving status  
SCAN...PLC scan time  
SEG......Free segment buffers  
page 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Example: This example uses peer-to-peer communication with three 6K8 products.  
;**** This code is executed on Peer unit #1: **************************  
NTID1  
; This unit is the "primary unit" (unit #1)  
NTRATE100  
VARSHO1=1PE  
; Set the sharing rate to 100ms and enable this unit  
; Store axis #1 encoder position in shared output variable #1  
;*************************************************************************  
;**** This code is executed on unit #3: **************************  
NTID3  
; Set unit ID to 3  
NTRATE100  
VARSHO2=4PCEA  
; Set the sharing rate to 100ms and enable this unit  
; Store the captured encoder position of axis #4 in shared  
; output variable #2  
VARSHO1=3AS  
; Store axis #3's axis status (binary data) in shared  
; output variable #1  
;*************************************************************************  
;**** This code is executed on unit #2: **************************  
NTID2  
; Set unit ID to 2  
NTRATE100  
VAR1=1VARSHI1  
; Set the sharing rate to 100ms and enable this unit  
; Load the value of unit #1's first shared data (1PE) into VAR1  
WRITE"AXIS 1 AT POSITION" ; Report axis 1's current position (the value of VAR1)  
WRVAR1  
VAR2=8PCEA-3VARSHI2  
; Calculate offset position: Subtract synch unit #3's  
; VARSHO2 (4PCEA) from the captured encoder position  
; of axis #8 (8PCEA).  
IF(VAR2>10000)  
; If position offset by more than 10000 encoder counts  
WRITE"AXIS 20 OUT OF POSITION"  
NIF  
VARB1=3VARSHI1  
IF(VARB1=B1)  
; Get unit 3's VARSHO1 information (3AS)  
; If axis 3 on unit #3 (axis #19) is in motion  
WRITE"AXIS 19 IN MOTION"  
NIF  
;*************************************************************************  
page 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
[ \ANI ]  
Type:  
Network Analog Input Voltage Status  
Network; Assignment or Comparison  
Product  
Rev  
n\mANI.i (see example below)  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
m = module #  
i = analog input # on module “m”  
n = 1-6  
Range:  
m = 0-7  
j = 1-2  
n/a  
Default:  
n/a  
Response:  
See Also:  
NTIO, \TANI, \TIO, VAR  
Use the \ANIoperand to assign the voltage level of an OPTO22 analog input to a real variable (VAR), or to make a  
comparison against another value.  
Syntax: VARx=n\mANI.iwhere “n” is the network server number of the OPTO22 unit, “m” is the I/O module number,  
and “i” is the input/channel number on the module (e.g., VAR3=2\1ANI.1assigns the voltage at analog input 1  
on module 1 of OPTO22 server 2 to VAR3). The \ANIoperand can also be used in a condition expression such as  
IF(2\3ANI.1>=2.0)or WAIT(2\4ANI.1<=1.5).  
The controller addresses the OPTO22 I/O locations as follows:  
Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute  
32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered  
1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2.  
EXAMPLE: OPTO22 is Network Server #2  
0
1
2
3
4
5
6
7
Digital  
Input  
Module  
Digital  
Input  
Module  
Digital  
Output  
Module  
Digital  
Output  
Module  
Analog  
Output  
Module  
Analog  
Output  
Module  
Analog  
Input  
Module  
Analog  
Input  
Module  
Input  
1
Input  
2
Input  
1
Input  
2
Output  
Output  
Output  
Output  
Input  
1
Input  
2
Input  
1
Input  
2
1
Output  
2
1
Output  
2
1
Output  
2
1
Output  
2
Input  
3
Input  
3
Output  
3
Output  
3
Input  
4
Input  
4
Output  
4
Output  
4
2\0IN.3  
2\3OUT.2  
2\5ANO.1  
2\7ANI.2  
Example:  
2NTIP2,172,54,125,34 ; Identify network server #2 as an OPTO22 unit at IP address  
; 172.54.125.34  
2NTCONN1  
2\6NTIO3  
2\7NTIO3  
; Attempt a connection to network server #2 (OPTO22 unit)  
; Server #2 (OPTO22), module #6 is an analog input module  
; Server #2 (OPTO22), module #7 is an analog input module  
WAIT(2\6ANI.1<=+1.5) ; Wait until the voltage at analog input #1 of module #6 on  
; Server #2 (OPTO22) is less than or equal to +1.5VDC  
IF(2\7ANI.2>+2.4)  
; If the voltage at analog input #2 of module 7 on Server #2  
; (OPTO22) is greater than +2.4 VDC ...  
page 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
\ANO  
Type:  
Network Analog Output  
Network  
Product  
Rev  
<!>n\mANO.i=r  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
m = module #  
i = analog output # on module “m”  
r = voltage value (VDC)  
n = 1-6  
Range:  
m = 0-7  
i = 1-2  
r = -10.00 to +10.00  
n/a  
Default:  
n/a  
Response:  
See Also:  
[ \ANO ], NTIO, \TANO, \TIO  
Use the \ANOcommand to set the voltage of an OPTO22 analog output. The maximum output range can be set from –  
10.00 VDC to +10.00 VDC. The 6K controller does not recognize the voltage range set on the I/O device (i.e., an \ANO  
setting of +10 VDC is allowed for an analog output configured with a maximum limit of +5 VDC.)  
The controller addresses the OPTO22 I/O locations as follows:  
Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute  
32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered  
1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2.  
EXAMPLE: OPTO22 is Network Server #2  
0
1
2
3
4
5
6
7
Digital  
Input  
Module  
Digital  
Input  
Module  
Digital  
Output  
Module  
Digital  
Output  
Module  
Analog  
Output  
Module  
Analog  
Output  
Module  
Analog  
Input  
Module  
Analog  
Input  
Module  
Input  
1
Input  
2
Input  
1
Input  
2
Output  
Output  
Output  
Output  
Input  
1
Input  
2
Input  
1
Input  
2
1
Output  
2
1
Output  
2
1
Output  
2
1
Output  
2
Input  
3
Input  
3
Output  
3
Output  
3
Input  
4
Input  
4
Output  
4
Output  
4
2\0IN.3  
2\3OUT.2  
2\5ANO.1  
2\7ANI.2  
Example:  
2NTIP2,172,54,125,34 ; Identify network server #2 as an OPTO22 unit at IP address  
; 172.54.125.34  
2NTCONN1  
2\4NTIO4  
2\5NTIO4  
; Attempt a connection to network server #2 (OPTO22 unit)  
; Server #2 (OPTO22), module #4 is an analog output module  
; Server #2 (OPTO22), module #5 is an analog output module  
2\4ANO.1=4.8  
; On Server #3, module #4, set the voltage on analog output #1 to  
; +4.8 VDC  
page 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
[ \ANO ]  
Type:  
Network Analog Output Status  
Network; Assignment or Comparison  
Product  
Rev  
n\mANO.i (see example below)  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
m = module #  
i = analog output # on module “m”  
n = 1-6  
Range:  
m = 0-7  
j = 1-2  
n/a  
Default:  
n/a  
Response:  
See Also:  
\ANO, NTIO, \TANI, \TIO, VAR  
Use the \ANOoperand to assign the voltage level of an OPTO22 analog output to a real variable (VAR), or to make a  
comparison against another value. The voltage at the analog outputs is controlled with the \ANOcommand.  
Syntax: VARx=n\mANO.iwhere “n” is the network server number of the OPTO22 unit, “m” is the I/O module number,  
and “i” is the output/channel number on the module (e.g., VAR3=2\5ANO.1assigns the voltage at analog input 1  
on module 5 of OPTO22 server 2 to VAR3). The \ANOoperand can also be used in a condition expression such as  
IF(2\3ANO.1>=2.0)or WAIT(2\4ANO.1<=1.5).  
The controller addresses the OPTO22 I/O locations as follows:  
Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute  
32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered  
1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2.  
EXAMPLE: OPTO22 is Network Server #2  
0
1
2
3
4
5
6
7
Digital  
Input  
Module  
Digital  
Input  
Module  
Digital  
Output  
Module  
Digital  
Output  
Module  
Analog  
Output  
Module  
Analog  
Output  
Module  
Analog  
Input  
Module  
Analog  
Input  
Module  
Input  
1
Input  
2
Input  
1
Input  
2
Output  
Output  
Output  
Output  
Input  
1
Input  
2
Input  
1
Input  
2
1
Output  
2
1
Output  
2
1
Output  
2
1
Output  
2
Input  
3
Input  
3
Output  
3
Output  
3
Input  
4
Input  
4
Output  
4
Output  
4
2\0IN.3  
2\3OUT.2  
2\5ANO.1  
2\7ANI.2  
Example:  
2NTIP2,172,54,125,34 ; Identify network server #2 as an OPTO22 unit at IP address  
; 172.54.125.34  
2NTCONN1  
2\4NTIO4  
; Attempt a connection to network server #2 (OPTO22 unit)  
; Server #2 (OPTO22), module #4 is an analog output module  
2\4ANO.1=4.8  
; On Server #3, module #4, set the voltage on analog output #1 to  
; +4.8 VDC  
VAR23=2\4ANO.1  
; Assign the voltage at analog output #1 on module #4 of Server #2  
; to real variable #23 (VAR23). Based on the preceding command,  
; the value should be +4.80.  
WAIT(2\4ANO.2<=+1.5) ; Wait until the voltage at analog output #1 of module #4 on  
; Server #2 is less than or equal to +1.5VDC  
page 36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
[ \IN ]  
Network Digital Input Status  
Network; Assignment or Comparison  
n\mIN<=Bbbbb> (see example below)  
Type:  
Product  
Rev  
Syntax:  
6K  
5.3  
n\iIN.i  
(see example below)  
n = network server #  
Units:  
m = module #  
i = digital input # on module “m” (for bit-select operation)  
n = 1-6  
Range:  
m = 0-7  
j = 1-4  
n/a  
Default:  
n/a  
Response:  
See Also:  
NTIO, \TIN, \TIO, VARB  
Use the \INoperand to assign an OPTO22 digital input value to a binary variable (VARB), or to make a comparison against a  
binary or hexadecimal value.  
Syntax: VARBx=n\mINwhere “n” is the network server number of the OPTO22 unit and “m” is the I/O module number  
(e.g., VARB16=2\0IN). The \INoperand can also be used in an expression such as IF(2\3IN=b11Ø1), or  
IF(2\3IN=h7F). To make a comparison against a binary value, place the letter b (b or B) in front of the value.  
The binary value itself must only contain ones, zeros, or Xs (1, Ø, X, x). To make a comparison against a  
hexadecimal value, place the letter h (h or H) in front of the value. The hexadecimal value itself must only  
contain the letters A-F, or the numbers Ø-9.  
Bit Select Operation: To address only one input value, instead of all the inputs, use the bit select (.) operator.  
For example, VARB1=2\3IN.3assigns the binary state of input 3 on module 3 of OPTO22 server 2 to binary  
variable 1. In another example, WAIT(2\3IN.1=b1)tells the 6K to wait until input 1 on module 3 of OPTO22  
server 2 is active.  
The controller addresses the OPTO22 I/O locations as follows:  
Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute  
32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered  
1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2.  
EXAMPLE: OPTO22 is Network Server #2  
0
1
2
3
4
5
6
7
Digital  
Input  
Module  
Digital  
Input  
Module  
Digital  
Output  
Module  
Digital  
Output  
Module  
Analog  
Output  
Module  
Analog  
Output  
Module  
Analog  
Input  
Module  
Analog  
Input  
Module  
Input  
1
Input  
2
Input  
1
Input  
2
Output  
Output  
Output  
Output  
Input  
1
Input  
2
Input  
1
Input  
2
1
Output  
2
1
Output  
2
1
Output  
2
1
Output  
2
Input  
3
Input  
3
Output  
3
Output  
3
Input  
4
Input  
4
Output  
4
Output  
4
2\0IN.3  
2\3OUT.2  
2\5ANO.1  
2\7ANI.2  
Example:  
2NTIP2,172,54,125,34 ; Identify network server #2 as an OPTO22 unit at IP address  
; 172.54.125.34  
2NTCONN1  
2\0NTIO1  
2\1NTIO1  
; Attempt a connection to network server #2 (OPTO22 unit)  
; Server #2 (OPTO22), module #0 is a digital input module  
; Server #2 (OPTO22), module #1 is a digital input module  
WAIT(2\1IN.2=b1)  
IF(2\0IN=bxx1)  
; Wait until input #2 of module #1 on Server #2 (OPTO22) is active  
; If input #3 of module 0 on Server #2 (OPTO22) is active ...  
page 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
\OUT  
Type:  
Network Digital Output  
Network  
Product  
Rev  
<!>n\mOUT<b><b><b><b>  
Syntax:  
6K  
5.3  
<!>n\mOUT.i-b  
n = network server #  
Units:  
m = module #  
b = enable bit  
i = digital output # on module “m”  
n = 1-6  
Range:  
m = 0-7  
b = 1 (turn on), 0 (turn off), or X (don’t change)  
i = 1-4  
n\mOUT0000  
Default:  
n/a  
Response:  
See Also:  
[ \OUT ], NTIO, \TIO, \TOUT  
Controlling Multiple Outputs  
Controlling One Output  
Output Number  
(Range: 1-4)  
Output #1  
Output #2  
Output #3  
Output #4  
n\mOUT.i-b  
n\mOUTbbbb  
Network Server #  
(Range: 1-6)  
Options for “b” are:  
1 = Turn on  
0 = Turn off  
Network Server #  
(Range: 1-6)  
Options for “b” are:  
1 = Turn on  
x = Don’t Change  
Module # on Server “n”  
0 = Turn off  
x = Don’t Change  
(Range: 0-7)  
Module # on Server “n”  
(Range: 0-7)  
Use the \OUTcommand to control the state of each digital output on the OPTO22 unit.  
The controller addresses the OPTO22 I/O locations as follows:  
Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute  
32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered  
1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2.  
EXAMPLE: OPTO22 is Network Server #2  
0
1
2
3
4
5
6
7
Digital  
Input  
Module  
Digital  
Input  
Module  
Digital  
Output  
Module  
Digital  
Output  
Module  
Analog  
Output  
Module  
Analog  
Output  
Module  
Analog  
Input  
Module  
Analog  
Input  
Module  
Input  
1
Input  
2
Input  
1
Input  
2
Output  
Output  
Output  
Output  
Input  
1
Input  
2
Input  
1
Input  
2
1
Output  
2
1
Output  
2
1
Output  
2
1
Output  
2
Input  
3
Input  
3
Output  
3
Output  
3
Input  
4
Input  
4
Output  
4
Output  
4
2\0IN.3  
2\3OUT.2  
2\5ANO.1  
2\7ANI.2  
Example:  
2NTIP2,172,54,125,34 ; Identify network server #2 as an OPTO22 unit at IP address  
; 172.54.125.34  
2NTCONN1  
2\2NTIO2  
2\3NTIO2  
2\3OUT1001  
; Attempt a connection to network server #2 (OPTO22 unit)  
; Server #2 (OPTO22), module #2 is a digital output module  
; Server #2 (OPTO22), module #3 is a digital output module  
; On Server #2, module #3, turn on Outputs #1 and #4 and turn off  
; Outputs #2 and #3  
2\2OUT.3-1  
; On Server #2, module #2, turn on only Output #1  
page 38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
[ \OUT ]  
Network Digital Output Status  
Network; Assignment or Comparison  
n\mOUT<=Bbbbb> (see example below)  
Type:  
Product  
Rev  
Syntax:  
6K  
5.3  
n\iOUT.i  
(see example below)  
n = network server #  
Units:  
m = module #  
i = digital output # on module “m” (for bit-select operation)  
n = 1-6  
Range:  
m = 0-7  
j = 1-4  
n/a  
Default:  
n/a  
Response:  
See Also:  
NTIO, \OUT, \TOUT, \TIO, VARB  
Use the \OUToperand to assign an OPTO22 digital output value to a binary variable (VARB), or to make a comparison against  
a binary or hexadecimal value. The digital outputs are turned on and off with the \OUTcommand.  
Syntax: VARBx=n\mOUTwhere “n” is the network server number of the OPTO22 unit and “m” is the I/O module number  
(e.g., VARB16=2\0OUT). The \OUToperand can also be used in an expression such as IF(2\3OUT=b11Ø1), or  
IF(2\3OUT=h7F). To make a comparison against a binary value, place the letter b (b or B) in front of the value.  
The binary value itself must only contain ones, zeros, or Xs (1, Ø, X, x). To make a comparison against a  
hexadecimal value, place the letter h (h or H) in front of the value. The hexadecimal value itself must only  
contain the letters A-F, or the numbers Ø-9.  
Bit Select Operation: To address only one output value, instead of all the outputs, use the bit select (.) operator.  
For example, VARB1=2\3OUT.3assigns the binary state of output 3 on module 3 of OPTO22 server 2 to binary  
variable 1. In another example, IF(2\3OUT.1=b1)evaluates true if output 1 on module 3 of OPTO22 server 2  
is active.  
The controller addresses the OPTO22 I/O locations as follows:  
Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute  
32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered  
1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2.  
EXAMPLE: OPTO22 is Network Server #2  
0
1
2
3
4
5
6
7
Digital  
Input  
Module  
Digital  
Input  
Module  
Digital  
Output  
Module  
Digital  
Output  
Module  
Analog  
Output  
Module  
Analog  
Output  
Module  
Analog  
Input  
Module  
Analog  
Input  
Module  
Input  
1
Input  
2
Input  
1
Input  
2
Output  
Output  
Output  
Output  
Input  
1
Input  
2
Input  
1
Input  
2
1
Output  
2
1
Output  
2
1
Output  
2
1
Output  
2
Input  
3
Input  
3
Output  
3
Output  
3
Input  
4
Input  
4
Output  
4
Output  
4
2\0IN.3  
2\3OUT.2  
2\5ANO.1  
2\7ANI.2  
Example:  
2NTIP2,172,54,125,34 ; Identify network server #2 as an OPTO22 unit at IP address  
; 172.54.125.34  
2NTCONN1  
2\3NTIO2  
2\3OUT1001  
; Attempt a connection to network server #2 (OPTO22 unit)  
; Server #2 (OPTO22), module #3 is a digital output module  
; On Server #2, module #3, turn on Outputs #1 and #4 and turn off  
; Outputs #2 and #3  
VARB9=2\3OUT  
; Assign the binary state of all digital outputs on module #3 of  
; Server #2 to binary variable #9 (VARB9). As a result, the value  
; of VARB9 will be 1001_0000_0000_0000_0000_0000_0000_0000.  
; If input #3 of module 3 on Server #2 (OPTO22) is active ...  
IF(2\3OUT=bxx1)  
page 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
\TANI  
Type:  
Transfer Network Analog Input Status  
Network; Transfer  
Product  
Rev  
<!>n\mTANI<.i>  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
m = module #  
i = analog input # on module “m” (for bit-select operation)  
(The response represents volts DC.)  
n = 1-6  
m = 0-7  
i = 1-2  
Range:  
n/a  
Default:  
1\1TANI:  
*2.42,3.32  
Response:  
1\1TANI.2: *3.32  
[ \ANI ], NTIO, \TIO  
See Also:  
The \TANIcommand returns the voltage present at one of the network analog inputs. The network server number and  
module number must precede the \TANIcommand (e.g., 2\3ANIreports the voltage present on all analog inputs on  
module 3 of network server 2).  
If the status of a specific analog input is required, use the bit select operator (.). For example, 1\3TANI.2reports the  
voltage of analog input 2 on module 3 of network server 1.  
The controller addresses the OPTO22 I/O locations as follows:  
Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute  
32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered  
1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2.  
EXAMPLE: OPTO22 is Network Server #2  
0
1
2
3
4
5
6
7
Digital  
Input  
Module  
Digital  
Input  
Module  
Digital  
Output  
Module  
Digital  
Output  
Module  
Analog  
Output  
Module  
Analog  
Output  
Module  
Analog  
Input  
Module  
Analog  
Input  
Module  
Input  
1
Input  
2
Input  
1
Input  
2
Output  
Output  
Output  
Output  
Input  
1
Input  
2
Input  
1
Input  
2
1
Output  
2
1
Output  
2
1
Output  
2
1
Output  
2
Input  
3
Input  
3
Output  
3
Output  
3
Input  
4
Input  
4
Output  
4
Output  
4
2\0TIN.3  
2\3TOUT.2  
2\5TANO.1  
2\7TANI.2  
page 40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
\TANO  
Type:  
Transfer Network Analog Output Status  
Network; Transfer  
Product  
Rev  
<!>n\mTANO<.i>  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
m = module #  
i = analog output # on module “m” (for bit-select operation)  
(The response represents volts DC.)  
n = 1-6  
m = 0-7  
i = 1-2  
Range:  
n/a  
Default:  
1\1TANO:  
*2.42,3.32  
Response:  
1\1TANO.2: *3.32  
\ANO, [ \ANO ], NTIO, \TIO  
See Also:  
The \TANOcommand returns the voltage commanded at one of the network analog outputs (the voltage is commanded with  
the \ANOcommand). The network server number and module number must precede the \TANOcommand (e.g., 2\3ANO  
reports the voltage commanded on all analog outputs on module 3 of network server 2).  
If the status of a specific analog output is required, use the bit select operator (.). For example, 1\3TANO.2reports the  
voltage of analog output 2 on module 3 of network server 1.  
The controller addresses the OPTO22 I/O locations as follows:  
Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute  
32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered  
1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2.  
EXAMPLE: OPTO22 is Network Server #2  
0
1
2
3
4
5
6
7
Digital  
Input  
Module  
Digital  
Input  
Module  
Digital  
Output  
Module  
Digital  
Output  
Module  
Analog  
Output  
Module  
Analog  
Output  
Module  
Analog  
Input  
Module  
Analog  
Input  
Module  
Input  
1
Input  
2
Input  
1
Input  
2
Output  
Output  
Output  
Output  
Input  
1
Input  
2
Input  
1
Input  
2
1
Output  
2
1
Output  
2
1
Output  
2
1
Output  
2
Input  
3
Input  
3
Output  
3
Output  
3
Input  
4
Input  
4
Output  
4
Output  
4
2\0TIN.3  
2\3TOUT.2  
2\5TANO.1  
2\7TANI.2  
page 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
\TIN  
Type:  
Transfer Network Digital Input Status  
Network; Transfer  
Product  
Rev  
<!>n\mTIN<.i>  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
m = module #  
i = digital input # on module “m” (for bit-select operation)  
n = 1-6  
m = 0-7  
i = 1-4  
Range:  
n/a  
Default:  
1\1TIN:  
*1100  
*1  
Response:  
1\1TIN.2:  
[ \IN ], NTIO, \TIO  
See Also:  
The \TINcommand returns the current status (active/on or inactive/off) of the network digital inputs. Each module of  
digital inputs has its own unique \TINresponse. The network server number and module number must precede the \TIN  
command (e.g., 2\3TINreports the status of all digital inputs on module 3 of network server 2).  
If the status of a specific input is required, use the bit select operator (.). For example, 1\3TIN.2reports the status of input  
2 on module 3 of network server 1.  
The controller addresses the OPTO22 I/O locations as follows:  
Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute  
32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered  
1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2.  
EXAMPLE: OPTO22 is Network Server #2  
0
1
2
3
4
5
6
7
Digital  
Input  
Module  
Digital  
Input  
Module  
Digital  
Output  
Module  
Digital  
Output  
Module  
Analog  
Output  
Module  
Analog  
Output  
Module  
Analog  
Input  
Module  
Analog  
Input  
Module  
Input  
1
Input  
2
Input  
1
Input  
2
Output  
Output  
Output  
Output  
Input  
1
Input  
2
Input  
1
Input  
2
1
Output  
2
1
Output  
2
1
Output  
2
1
Output  
2
Input  
3
Input  
3
Output  
3
Output  
3
Input  
4
Input  
4
Output  
4
Output  
4
2\0TIN.3  
2\3TOUT.2  
2\5TANO.1  
2\7TANI.2  
\TIO  
Transfer Ethernet I/O status  
Network; Transfer  
<!>n\TIO  
Type:  
Product  
6K  
Rev  
Syntax:  
Units:  
5.3  
n = network server #  
n = 1-6  
Range:  
Default:  
Response:  
See Also:  
n/a  
(see example below)  
NTIO, \TANI, \TANO, \TIN, \TOUT  
The \TIOcommand displays the status of the current I/O configuration for the specified OPTO22 network server. If a  
module is not configured (with the NTIOcommand), it will not be included in the report. A digital I/O module has 4 points  
and an analog I/O module has 2.  
Example Response:  
>1\TIO  
*SERVER 1  
* Module Type  
Status  
1011  
*
0
DIGITAL INPUTS  
page 42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
*
*
*
*
1
2
4
7
DIGITAL OUTPUTS  
ANALOG OUTPUTS  
DIGITAL INPUTS  
ANALOG INPUTS  
0001  
+10.000, -4.456  
1110  
+6.753, +0.000  
\TOUT  
Type:  
Transfer Network Digital Output Status  
Network; Transfer  
Product  
Rev  
<!>n\mTOUT<.i>  
Syntax:  
Units:  
6K  
5.3  
n = network server #  
m = module #  
i = digital output # on module “m” (for bit-select operation)  
n = 1-6  
m = 0-7  
i = 1-4  
Range:  
n/a  
Default:  
1\1TOUT:  
*1100  
Response:  
1\1TOUT.2: *1  
[ \OUT ], NTIO, \TIO  
See Also:  
The \TOUTcommand returns the current status (active/on or inactive/off) of the OPTO22 digital outputs (the outputs are  
turned on and off with the \OUTcommand). Each module of digital outputs has its own unique \TOUTresponse. The  
network server number and module number must precede the \TOUTcommand (e.g., 2\3TOUTreports the status of all  
digital outputs on module 3 of network server 2).  
If the status of a specific output is required, use the bit select operator (.). For example, 1\3TOUT.2reports the status of  
output 2 on module 3 of network server 1.  
The controller addresses the OPTO22 I/O locations as follows:  
Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute  
32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered  
1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2.  
EXAMPLE: OPTO22 is Network Server #2  
0
1
2
3
4
5
6
7
Digital  
Input  
Module  
Digital  
Input  
Module  
Digital  
Output  
Module  
Digital  
Output  
Module  
Analog  
Output  
Module  
Analog  
Output  
Module  
Analog  
Input  
Module  
Analog  
Input  
Module  
Input  
1
Input  
2
Input  
1
Input  
2
Output  
Output  
Output  
Output  
Input  
1
Input  
2
Input  
1
Input  
2
1
Output  
2
1
Output  
2
1
Output  
2
1
Output  
2
Input  
3
Input  
3
Output  
3
Output  
3
Input  
4
Input  
4
Output  
4
Output  
4
2\0TIN.3  
2\3TOUT.2  
2\5TANO.1  
2\7TANI.2  
page 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 

Miele Coffeemaker CM 5200 User Manual
Miele Oven H 5981 BP User Manual
MTX Audio Portable Speaker T5515 04 User Manual
NETGEAR Network Router GS108Ev3 User Manual
New Holland Lawn Mower TG Series User Manual
Niles Audio Universal Remote RCA TT User Manual
Nokia Cell Phone 2720 User Manual
Olympus Camera Lens 261012 User Manual
Oster Kitchen Grill 166143 User Manual
Palsonic CRT Television 5125PF User Manual