Omron Healthcare Printer VARISPEEDF7 User Manual

Manual No.  
I66E-EN-01  
VARISPEEDꢀF7  
The Industrial Workhorse  
Model: CIMR-F7Z  
200V Class 3-phase 0.4 to 110 kW  
400V Class 3-phase 0.4 to 300 kW  
QuIckꢀSTARTꢀGuIDEꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F7Z Quick Start Guide  
Table of Contents  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warnings  
CAUTION  
Cables must not be connected or disconnected, nor signal tests carried out,  
while the power is switched on.  
The Varispeed F7 DC bus capacitor remains charged even after the power has been  
switched off. To avoid an electric shock hazard, disconnect the frequency inverter from the  
mains before carrying out maintenance. Then wait for at least 5 minutes after all LEDs  
have gone out.  
Do not perform a withstand voltage test on any part of the Varispeed. The frequency  
inverter contains semiconductors, which are not designed for such high voltages.  
Do not remove the digital operator while the mains supply is switched on. The printed cir-  
cuit board must also not be touched while the inverter is connected to the power.  
Never connect general LC/RC interference suppression filters, capacitors or overvoltage  
protection devices to the inverter input or output.  
To avoid unnecessary overcurrent faults, etc. being displayed, the signaling contacts of any  
contactor or switch fitted between inverter and motor must be integrated into the inverter  
control logic (e.g. baseblock).  
This is absolutely imperative!  
This manual must be read thoroughly before connecting and operating the inverter. All  
safety precautions and instructions for use must be followed.  
The inverter may must be operated with the appropriate line filters, following the installation  
instructions in this manual and with all covers closed and terminals covered.  
Only then will adequate protection be provided. Please do not connect or operate any  
equipment with visible damage or missing parts. The operating company is responsible  
for any injuries or equipment damage resulting from failure to heed the warnings in this  
manual.  
EN-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Safety Precautions and Instructions  
General  
Please read these safety precautions and instructions for use thoroughly before installing and oper-  
ating this inverter. Also read all of the warning signs on the inverter and ensure they are never dam-  
aged or removed.  
Live and hot inverter components may be accessible during operation. Removal of housing compo-  
nents, the digital operator or terminal covers runs the risk of serious injuries or damage in the event  
of incorrect installation or operation. The fact that frequency inverters control rotating mechanical  
machine components can give rise to other dangers.  
The instructions in this manual must be followed. Installation, operation and maintenance may only  
be carried out by qualified personnel. For the purposes of the safety precautions, qualified personnel  
are defined as individuals who are familiar with the installation, starting, operation and maintenance  
of frequency inverters and have the proper qualifications for this work. Safe operation of these units  
is only possible if they are used properly for their intended purpose.  
The DC bus capacitors can remain live for about 5 minutes after the inverter is disconnected from  
the power. It is therefore necessary to wait for this time before opening its covers. All of the main cir-  
cuit terminals may still carry dangerous voltages.  
Children and other unauthorized persons must not be allowed access to these inverters.  
Keep these Safety Precautions and Instructions for Use readily accessible and supply them to all  
persons with any form of access to the inverters.  
Intended Use  
Frequency inverters are intended for installation in electrical systems or machinery.  
Their installation in machinery and systems must conform to the following product standards of the  
Low Voltage Directive:  
EN 50178, 1997-10, Equipping of Power Systems with Electronic Devices  
EN 60204-1, 1997-12Machine Safety and Equipping with Electrical Devices  
Part 1: General Requirements (IEC 60204-1:1997)/  
Please note: Includes Corrigendum of September 1998  
EN 61010-1, A2, 1995Safety Requirements for Information Technology Equipment  
(IEC 950, 1991 + A1, 1992 + A2, 1993 + A3, 1995 + A4, 1996, modified)  
CE marking is carried out to EN 50178, using the line filters specified in this manual and following  
the appropriate installation instructions.  
Transportation and storage  
The instructions for transportation, storage and proper handling must be followed in accordance with  
the technical data.  
Installation  
Install and cool the inverters as specified in the documentation. The cooling air must flow in the  
specified direction. The inverter may therefore only be operated in the specified position (e.g.  
upright). Maintain the specified clearances. Protect the inverters against impermissible loads. Com-  
ponents must not be bent nor insulation clearances changed. To avoid damage being caused by  
static electricity, do not touch any electronic components or contacts.  
EN-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electrical Connection  
Carry out any work on live equipment in compliance with the national safety and accident prevention  
regulations. Carry out electrical installation in compliance with the relevant regulations. In particular,  
follow the installation instructions ensuring electromagnetic compatibility (EMC), e.g. shielding,  
grounding, filter arrangement and laying of cables. This also applies to equipment with the CE mark.  
It is the responsibility of the manufacturer of the system or machine to ensure conformity with EMC  
limits.  
Your supplier or Omron Yaskawa Motion Control representative must be contacted when using leak-  
age current circuit breaker in conjunction with frequency inverters.  
In certain systems it may be necessary to use additional monitoring and safety devices in compli-  
ance with the relevant safety and accident prevention regulations. The frequency inverter hardware  
must not be modified.  
Notes  
The Varispeed F7 frequency inverters are certified to CE, UL, and cUL  
EMC Compatibility  
Introduction  
This manual was compiled to help system manufacturers using OMRON YASKAWA Motion Control  
(OYMC) frequency inverters design and install electrical switch gear. It also describes the measures  
necessary to comply with the EMC Directive. The manual's installation and wiring instructions must  
therefore be followed.  
Our products are tested by authorized bodies using the standards listed below.  
Product standard: EN 61800-3:1996  
EN 61800-3; A11:2000  
Measures to Ensure Conformity of OYMC Frequency inverters to the EMC Directive  
OYMC frequency inverters do not necessarily have to be installed in a switch cabinet.  
It is not possible to give detailed instructions for all of the possible types of installation. This manual  
therefore has to be limited to general guidelines.  
All electrical equipment produces radio and line-borne interference at various frequencies. The  
cables pass this on to the environment like an aerial.  
Connecting an item of electrical equipment (e.g. drive) to a supply without a line filter can therefore  
allow HF or LF interference to get into the mains.  
The basic countermeasures are isolation of the wiring of control and power components, proper  
grounding and shielding of cables.  
A large contact area is necessary for low-impedance grounding of HF interference. The use of  
grounding straps instead of cables is therefore definitely advisable.  
Moreover, cable shields must be connected with purpose-made ground clips.  
EN-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Laying Cables  
Measures Against Line-Borne Interference:  
Line filter and frequency inverter must be mounted on the same metal plate. Mount the two compo-  
nents as close to each other as possible, with cables kept as short as possible.  
Use a power cable with well-grounded shield. For motor cables up to 50 meters in length use  
shielded cables. Arrange all grounds so as to maximize the area of the end of the lead in contact  
with the ground terminal (e.g. metal plate).  
Shielded Cable:  
Use a cable with braided shield.  
Ground the maximum possible area of the shield. It is advisable to ground the shield by connect-  
ing the cable to the ground plate with metal clips (see following figure).  
Ground Plate  
Ground Clip  
Fig 1 Earthing the cable shield with metal clips  
The grounding surfaces must be highly conductive bare metal. Remove any coats of varnish and  
paint.  
– Ground the cable shields at both ends.  
– Ground the motor of the machine.  
EN-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Mechanical Installation  
Unpacking the Inverter  
Check the following items after unpacking the inverter.  
Item  
Method  
Has the correct Inverter model been  
delivered?  
Check the model number on the nameplate on the side of the  
Inverter.  
Inspect the entire exterior of the Inverter to see if there are any  
scratches or other damage resulting from shipping.  
Is the Inverter damaged in any way?  
Are any screws or other components  
loose?  
Use a screwdriver or other tools to check for tightness.  
If any irregularities in the above items are found, contact the agency from which the Inverter was pur-  
chased or your Omron Yaskawa Motion Control representative immediately.  
Checking the Installation Site  
Protection covers are attached to the top and bottom of the NEMA 1 / IP20 Inverters. Be sure to  
remove the top cover before operating a 200 or 400 V Class Inverter with a capacity of 18.5 kW or  
less inside a panel.  
Observe the following precautions when mounting the Inverter:  
Install the Inverter in a clean location which is free from oil mist and dust. It can be installed in a  
totally enclosed panel that is completely shielded from floating dust.  
When installing or operating the Inverter, always take special care so that metal powder, oil,  
water, or other foreign matter does enter the Inverter.  
Do not install the Inverter on combustible material, such as wood.  
Install the Inverter in a location free from radioactive materials and combustible materials.  
Install the Inverter in a location free from harmful gasses and liquids.  
Install the Inverter in a location without excessive oscillation.  
Install the Inverter in a location free from chlorides.  
Install the Inverter in a location without direct sunlight.  
EN-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation Orientation  
Install the Inverter vertically so as not to reduce the cooling effect. When installing the Inverter,  
always provide the following installation space to allow normal heat dissipation.  
A
B
Air  
A
B
200V class inverter, 0.55 to 90 kW  
400V class inverter, 0.55 to 132 kW  
200V class inverter, 110 kW  
400V class inverter, 160 to 220 kW  
400V class inverter, 300 kW  
50 mm 120 mm  
120 mm 120 mm  
300 mm 300 mm  
30mm min.  
120mm min.  
30mm min.  
50mm  
min.  
Air  
Horizontal Space  
Vertical Space  
Fig 2 Installation space  
1. The same space is required horizontally and vertically for IP00, IP20 and NEMA 1 Inverters.  
2. Always remove the top protection cover after installing an Inverter with an output of 18.5 kW or less in a  
panel.  
Always provide enough space for suspension eye bolts and the main circuit lines when installing an  
Inverter with an output of 22 kW or more in a panel.  
IMPORTANT  
Installation of Inverters and EMC filters  
PE L2  
L1  
For an EMC rules compliant installation  
consider the following points:  
L3  
Ground Bonds  
Remove any paint!  
Use a line filter.  
Use shielded motor cables.  
PE  
Mount the inverter and filter on a  
grounded cunductive plate.  
Line  
Remove any paint or dirt before mount-  
ing the parts in order to reach the low-  
est possible grounding impedance.  
Inverter  
Filter  
L2  
L1 L3  
V
Load  
GND  
U
W
GND  
Cable Lenght  
as short as possible  
Grounded  
Metal Plate  
Screened  
Motor cable  
Ground Bonds  
Remove any paint!  
M
~3  
Fig 3 EMC filter installation  
EN-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical Connection  
Wiring the Inverter  
DC reactor to improve input  
power factor (optional)  
Braking resistor unit (optional)  
Short-circuit bar  
Main Contactor  
B1  
B2  
2
T
1
Fuses  
R/L1  
U/T1  
V/T2  
W/T3  
L1  
L2  
L3  
3-phase power  
380 to 480 V  
50/60 Hz  
Line  
Filter  
S/L2  
M
T/L3  
Varispeed F7  
PE  
Forward Run / Stop  
S1  
S2  
S3  
S4  
S5  
S6  
S7  
SN  
SC  
SP  
MA  
MB  
MC  
Fault relay output  
250 VAC, 1 A max.  
30 VDC, 1 A max.  
Reverse Run / Stop  
External Fault  
Fault reset  
Multi-function  
M1  
M2  
Multi-step speed setting 1  
digital inputs  
Relay output 1  
[Factory setting]  
[Default: Running]  
Multi-step speed setting 2  
M3  
Jog frequency selection  
Relay output 2  
[Default: Zero speed]  
Multi-function digital output  
250 VAC, 1 A max.  
M4  
30 VDC, 1 A max.  
M5  
M6  
Relay output 3  
[Default:  
Frequency agree 1]  
24 V  
E(G)  
Shield  
terminal  
2CN  
Pulse train input [Default:  
Frequency reference input]  
0 to 32 kHz  
RP  
+V  
Analog input setting  
adjustment  
PG  
Option  
Card  
Analog input power supply  
15 V, 20 mA  
2 kΩ  
Analog input 1: Master  
frequency reference  
0 to 10 V (20 kΩ)  
0 to 10 V  
A1  
2 k  
Ω
Multi-function analog input 2  
[Default: Frequency bias  
4 to 20 mA (20 kΩ)]  
4 to 20 mA  
A2  
P
P
AC  
0 V  
-V  
Analog input power supply  
-15 V, 20 mA  
E(G)  
Shield  
terminal  
Input  
Option  
Card  
MP  
AC  
Pulse train output  
0 to 32 kHz (2.20 kΩ)  
[Default: Output frequency]  
Adjustment,  
20 k  
Ω
-
-
Multi-function analog output 1  
(-10 to +10 V, 2 mA / 4 to 20 mA)  
[Default: Output frequency, 0 to 10 V)  
4 to 20 mA (20 kΩ)]  
+
FM  
FM  
Terminating  
resistance  
Adjustment,  
20 k  
R+  
R-  
Ω
P
P
+
Multi-function analog output 2  
(-10 to +10 V, 2 mA / 4 to 20 mA)  
[Default: Output current, 0 to 10 V)  
4 to 20 mA (20 kΩ)]  
AM  
AC  
MEMOBUS  
communication  
RS-485/422  
AM  
S+  
S-  
IG  
Twisted-pair  
shielded wires  
Shielded  
wires  
P
Fig 4 Wiring Diagram  
EN-8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Main Circuit Terminals  
Main circuit terminal functions are summarized according to terminal symbols in Table 1. Wire the  
terminals correctly for the desired purposes.  
Table 1 Main Circuit Terminal Functions (200 V Class and 400 V Class)  
Model: CIMR-F7Z††††  
Purpose  
Terminal Symbol  
R/L1, S/L2, T/L3  
R1/L11, S1/L21, T1/L31  
U/T1, V/T2, W/T3  
200 V Class  
20P4 to 2110  
2022 to 2110  
20P4 to 2110  
400 V Class  
40P4 to 4300  
4022 to 4300  
40P4 to 4300  
Main circuit power input  
Inverter outputs  
DC bus terminals  
20P4 to 2110  
40P4 to 4300  
1,  
Braking Resistor Unit Connec-  
tion  
B1, B2  
20P4 to 2018  
40P4 to 4018  
DC reactor connection  
Braking Unit connection  
Ground  
20P4 to 2018  
2022 to 2110  
20P4 to 2110  
40P4 to 4018  
4022 to 4300  
40P4 to 4300  
1,  
3,  
2
Control Circuit Terminals  
Fig 5 shows the control terminal arrangement. The functions of the control circuit terminals are  
shown in Table 2. Use the appropriate terminals for the correct purposes.  
Fig 5 Control terminal arrangement  
Table 2 Control Circuit Terminals with default settings  
Type  
No.  
Signal Name  
Function  
Forward run when ON; stopped when  
OFF.  
Signal Level  
S1 Forward run/stop command  
Reverse run when ON; stopped when  
OFF.  
S2 Reverse run/stop command  
*1  
S3  
S4  
Fault when ON.  
Reset when ON  
External fault input  
Fault reset *1  
24 VDC, 8 mA  
Photocoupler isolation  
Multi-step speed reference 1  
*1  
Functions are  
selected by set-  
ting H1-01 to  
H1-05.  
Auxiliary frequency ref-  
erence when ON.  
S5  
(Master/auxiliary switch)  
Multi-step speed 2  
when ON.  
Multi-step speed reference 2  
*1  
S6  
S7  
Jog frequency when  
ON.  
Jog frequency reference *1  
SC Digital input common  
SN Digital Input Neutral  
24 VDC, 250 mA max.  
SP Digital Input Power Supply  
+V 15 V power output  
+24VDC power supply for digital inputs  
*2  
15 V power supply for analog references 15 V (Max. curr.: 20mA)  
-10 to +10 V (20 kΩ)  
0 to +10 V (20 kΩ)  
A1 Frequency reference  
0 to +10 V/100%  
Auxiliary analog fre-  
quency reference;  
4 to 20 mA (250Ω)  
Function is  
selected by set- 0 V to +10 V (20 kΩ)  
ting H3-09.  
4 to 20 mA (250 Ω)  
Auxiliary Frequency Refer-  
ence  
A2  
0 to 20 mA (250 Ω)  
-V  
-15 V power output  
-15 V power supply for analog references  
AC Analog reference common  
Shield wire, optional ground  
E(G)  
line connection point  
EN-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Type  
No.  
M1  
Signal Name  
Function  
Signal Level  
During run (NO)  
Closed during Run  
M2  
M3  
Closed when output  
Function  
Zero speed (NO)  
frequency at zero level selected by H2-  
Relay contacts  
Contact capacity:  
1 A max. at 250 VAC  
M4  
(b2-01) or below  
01 to H2-03  
M5  
M6  
MA  
Speed agreement detection Within 2 Hz of set fre-  
(NO) quency when ON  
*3  
1 A max. at 30 VDC  
Closed across MA and MC during faults  
Open across MB and MC during faults  
MB Fault output signal  
MC  
Analog output fre-  
quency signal;  
0 to 10 V; 10V=FMAX H4-01  
Function  
selected by  
0 to +10 V max. 5%  
2 mA max.  
FM Output frequency  
AC Analog common  
-10 to +10 V max. 5%  
2 mA max  
Analog output power  
signal;  
0 to 10V; 10V=max.  
appl. motor capacity  
Function  
selected by  
H4-04  
AM Inverter output power  
4 to 20 mA  
0 to 32 kHz (3kΩ)  
High level voltage 3.5 to  
13.2 V  
*4  
RP Pulse Input  
H6-01 (Frequency reference input)  
H6-06 (Output frequency)  
0 to 32 kHz  
+15 V output (2.2kΩ)  
MP Pulse Output  
R+  
R-  
S+  
S-  
MEMOBUS communications  
input  
Differential input,  
PHC isolation  
For 2-wire RS-485, short R+ and S+  
as well as R- and S-.  
MEMOBUS communications  
output  
Differential input,  
PHC isolation  
IG  
Signal common  
*1. The default settings are given for terminals S3 to S7. For a 3-wire sequence, the default settings are a 3-wire sequence for S5, multi-  
step speed setting  
1 for S6 and multi-step speed setting 2 for S7.  
*2. Do not use this power supply for supplying any external equipment.  
*3. When driving a reactive load, such as a relay coil with DC power supply, always insert a flywheel diode as shown in Fig 6  
*4. Pulse input specifications are given in the following table:  
Low level voltage  
High level voltage  
H duty  
0.0 to 0.8 V  
3.5 to 13.2 V  
30% to 70%  
0 to 32 kHz  
Pulse frequency  
Flywheel diode  
The rating of the flywheel diode must  
be at least as high as the circuit volt-  
age.  
Coil  
External power:  
30 VDC max.  
1 A max.  
Fig 6 Flywheel Diode Connection  
1. In Fig 4 the wiring of the digital inputs S1 to S7 is shown for the connection of contacts or NPN transis-  
tors (0V common and sinking mode). This is the default setting.  
For the connection of PNP transistors or for using a 24V external power supply, refer to Table 3.  
2. A DC reactor is an option only for Inverters of 18.5 kW or less. Remove the short circuit bar when con-  
necting a DC reactor.  
IMPORTANT  
EN-10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Sinking/Sourcing Mode (NPN/PNP Selection)  
The input terminal logic can be switched over between sinking mode (0-V common, NPN) and  
sourcing mode (+24V common, PNP) by using the jumper CN5. An external power supply is also  
supported, providing more freedom in signal input methods.  
Table 3 Sinking / Sourcing Mode and Input Signals  
Internal Power Source - Sinking Mode (NPN)  
External Power Source - Sinking Mode (NPN)  
External +24 V  
Internal Power Source - Sourcing Mode (PNP)  
External Power Source - Sourcing Mode (PNP)  
External +24 V  
EN-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Wiring Main Circuit Inputs  
Installing Fuses  
To protect the inverter, it is recommended to use semiconductor fuses like they are shown in the  
table below.  
Table 4 Input Fuse Selection  
RatedInverter  
Fuse Selection  
Current (A)  
Selection Example (Ferraz)  
Inverter Type  
Output  
Current (A)  
3.2  
I2t (A2s)  
I2t (A2s)  
Voltage (V)  
Model  
Rating  
20P4  
20P7  
21P5  
22P2  
23P7  
25P5  
27P5  
2011  
2015  
2018  
2022  
2030  
2037  
2045  
2055  
2075  
2090  
2110  
240  
240  
240  
240  
240  
240  
240  
240  
240  
240  
240  
240  
240  
240  
240  
240  
240  
240  
10  
10  
15  
20  
30  
40  
60  
80  
100  
130  
150  
180  
240  
300  
350  
450  
550  
600  
12~25  
12~25  
23~55  
34~98  
82~220  
A60Q12-2  
A60Q12-2  
A60Q15-2  
A60Q20-2  
A60Q30-2  
A50P50-4  
A50P80-4  
A50P80-4  
A50P125-4  
A50P150-4  
A50P150-4  
A50P200-4  
A50P250-4  
A50P300-4  
A50P350-4  
A50P450-4  
600V / 12A  
600V / 12A  
600V / 15A  
600V / 20A  
600V / 30A  
500V / 50A  
500V / 80A  
500V / 80A  
500V / 125A  
500V / 150A  
500V / 150A  
500V / 200A  
500V/ 250A  
500V / 300A  
500V / 350A  
500V / 450A  
500V / 600A  
500V / 600A  
17  
17  
26  
41  
132  
250  
640  
640  
4.1  
7.0  
9.6  
15  
23  
31  
45  
58  
220~610  
290~1300  
450~5000  
1200~7200  
1800~7200  
870~16200  
1500~23000  
2100~19000  
2700~55000  
4000~55000  
7100~64000  
1600  
2200  
2200  
4000  
6200  
9000  
12000  
20000  
36000  
36000  
71  
85  
115  
145  
180  
215  
283  
346  
415  
11000~64000 A50P600-4  
13000~83000 A50P600-4  
40P4  
40P7  
41P5  
42P2  
43P7  
44P0  
45P5  
47P5  
4011  
4015  
4018  
4022  
4030  
4037  
4045  
4055  
4075  
4090  
4110  
4132  
1.8  
2.1  
3.7  
5.3  
7.6  
8.7  
12.5  
17  
24  
31  
39  
45  
60  
75  
91  
112  
150  
180  
216  
260  
480  
480  
480  
480  
480  
480  
480  
480  
480  
480  
480  
480  
480  
480  
480  
480  
480  
480  
480  
480  
5
5
10  
10  
15  
20  
25  
30  
50  
60  
70  
80  
100  
125  
150  
150  
250  
300  
350  
400  
6~55  
6~55  
10~55  
18~55  
34~72  
A60Q10-2  
A60Q10-2  
A60Q12-2  
A60Q15-2  
A60Q20-2  
A60Q30-2  
A60Q30-2  
A60Q30-2  
A70P50-4  
A70P70-4  
A70P80-4  
A70P80-4  
A70P100-4  
A70P125-4  
A70P150-4  
A70P200-4  
A70P250-4  
A70P300-4  
A70P350-4  
A70P400-4  
600V / 10A  
600V / 10A  
600V / 12A  
600V / 15A  
600V / 20A  
600V / 30A  
600V / 30A  
600V / 30A  
700V / 50A  
700V / 70A  
700V / 80A  
700V / 80A  
700V / 100A  
700V / 125A  
700V / 150A  
700V / 200A  
700V / 250A  
700V / 300A  
700V / 350A  
700V / 400A  
10  
10  
17  
26  
41  
132  
132  
132  
300  
50~570  
100~570  
100~640  
150~1300  
400~1800  
700~4100  
240~5800  
500~5800  
750~5800  
920~13000  
1500~13000  
3000~55000  
3800~55000  
5400~23000  
7900~64000  
590  
770  
770  
1200  
1900  
2700  
4800  
7500  
11000  
15000  
19000  
14000~25000  
0
20000~25000  
0
34000~40000  
0
52000~92000  
0
4160  
4185  
4220  
4300  
304  
370  
506  
675  
480  
480  
480  
480  
450  
600  
700  
900  
A70P450-4  
A70P600-4  
A70P700-4  
A70P900-4  
700V / 450A  
700V / 600A  
700V / 700A  
700V / 900A  
24000  
43000  
59000  
97000  
Consider the following precautions for the main circuit power supply input.  
If a moulded case circuit breaker is used for the power supply connection (R/L1, S/L2, and T/L3),  
ensure that the circuit breaker is suitable for the Inverter.  
EN-12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
If an earth leakage breaker is used, it should be able to detect all kinds of current in order to  
ensure a safe earth leakage current detection  
A magnetic contactor or other switching device can be used at the inverter input. The inverter  
should not be powered up more than once per hour.  
The input phases (R/S/T) can be connected in any sequence.  
If the Inverter is connected to a large-capacity power transformer (600 kW or more) or a phase  
advancing capacitor is switched nearby, an excessive peak current could flow through the input  
power circuit, causing an inverter damage. As a countermeasure install an optional AC Reactor  
at the inverter input or a DC reactor at the DC reactor connection terminals.  
Use a surge absorber or diode for inductive loads near the Inverter. Inductive loads include mag-  
netic contactors, electromagnetic relays, solenoid valves, solenoids, and magnetic brakes.  
Wiring the Output Side of the Main Circuit  
The following precautions should be considered for the output circuit wiring.  
Never connect any power source to the inverter output terminals. Otherwise the inverter can be  
damaged.  
Never short or ground the output terminals. Otherwise the inverter can be damaged.  
Do not use phase correction capacitors. Otherwise the inverter and capacitors can be damaged.  
Check the control sequence to make sure, that the magnetic contactor (MC) between the Inverter  
and motor is not turned ON or OFF during inverter operation. If the MC is turned ON during the  
Inverter is operation, a large inrush current will be created and the inverter’s overcurrent protec-  
tion may operate.  
Ground Connection  
The following precautions should be considered for the ground connection.  
Do not share the ground wire with other devices, such as welding machines or power tools.  
Always use a ground wire, that complies with technical standards on electrical equipment and  
minimize the length of the ground wire.  
Leakage current is caused by the Inverter. Therefore, if the distance between the ground elec-  
trode and the ground terminal is too long, potential on the ground terminal of the Inverter will  
become unstable.  
When more than one Inverter is used, do not to loop the ground wire.  
OK  
NO  
Fig 7 Ground Wiring  
Control Circuit Wiring Precautions  
Consider the following precautions for wiring the control circuits.  
Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1,  
V/T2, W/T3, B1, B2,  
,
1, 2, and 3, PO, NO) and other high-power lines.  
Separate wiring for control circuit terminals MA, MB, MC, M1 to M6 (relay outputs) from wiring to  
other control circuit terminals.  
If an optional external power supply is used, it should be a UL Listed Class 2 power supply.  
Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults.  
Ground the cable shields with the maximum contact area of the shield and ground.  
Cable shields have to be grounded on both cable ends.  
EN-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Keypad Operation  
Digital Operator Display (optional)  
The key names and functions of the Digital Operator are described below  
Drive Mode Indicators  
FWD: Lights up when a forward run command is  
input.  
REV:  
SEQ:  
REF:  
Lights up when a reverse run command is  
input.  
Lights up when any other run command  
source than the Digital Operator is selected.  
Lights up when any other frequency reference  
source than the Digital Operator is selected.  
ALARM: Lights up when an error or alarm has  
occurred.  
Data Display  
Displays monitor data, parameter numbers, and set-  
tings.  
Mode Display (displayed at the upper left of the data display  
DRIVE: Lights up in Drive Mode.  
QUICK: Lights up in Quick Programming Mode.  
ADV:  
Lights up in Advanced Programming Mode.  
VERIFY:Lights up in Verify Mode.  
A. TUNE:Lights up in Autotuning Mode.  
Keys  
Execute operations such as setting user parameters,  
monitoring, jogging, and autotuning.  
Digital Operator Keys  
Key  
Name  
Function  
Switches between operation via the Digital Operator (LOCAL) and  
LOCAL/REMOTE Key the settings in b1-01 and b1-02 (REMOTE).  
This key can be enabled or disabled by setting parameter o2-01.  
MENU Key  
Selects the modes.  
ESC Key  
Returns to the status before the DATA/ENTER Key was pressed.  
Enables jog operation when the Inverter is being operated from the  
Digital Operator.  
JOG Key  
Selects the rotation direction of the motor when the Inverter is being  
operated from the Digital Operator.  
FWD/REV Key  
Shift/RESET Key  
Sets the active digit when programming user parameters.  
Also acts as the Reset key when a fault has occurred.  
Selects user parameter numbers and increments parameter set-  
Increment Key  
Decrement Key  
tings.  
Used to move to the next item or data.  
Selects user parameter numbers and decrements parameter set-  
tings.  
Used to move to the previous item or data.  
DATA/ENTER Key  
RUN Key  
Enters menus and parameters and validates parameter settings.  
Starts operation when the Inverter is being controlled by the Digital  
Operator (LOCAL Mode).  
Stops Inverter operation (LOCAL and REMOTE Mode).  
This key can be enabled or disabled when operating from a source  
different tan the operator by setting parameter o2-02.  
STOP Key  
EN-14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Power Up and Basic Parameter Setup  
Start Up Procedure  
START  
Installation  
Wiring  
Set power supply  
voltage jumper *1  
Turn ON power  
Confirm status  
Basic settings  
(Quick programming mode)  
Select control  
method.  
NO  
Vector Control (A1-02 = 2 or 3) *5  
V/f control  
YES  
YES  
V/f Control with PG (A1-02 = 1  
PG?  
NO  
V/f control  
Set E1-03, E2-04 and F1-01.  
*2  
Set E1-03.  
V/f default: 200V/50Hz (400V/50Hz)  
V/f default: 200V/50Hz (400V/50Hz)  
Settings according  
to control mode  
Motor  
operation possible  
during autotuning?  
*3  
NO  
YES  
*6  
Non-rotating autotuning  
*4  
*6  
Rotating  
Non-rotating  
for line-to-line resistance  
autotuning  
autotuning  
Application settings  
(Advanced programming mode)  
1.Set for 400 V Class Inverter for 75 kW or more.  
2.If there is a reduction gear between the motor and PG, set the  
reduction ratio in F1-12 and F1-13 in advanced programming  
mode.  
No-load  
operation  
3.Use rotational autotuning to increase autotuning accuracy  
whenever it is okay for the motor to be operated.  
4.If the motor cable changes to 50 m or longer for the actual  
installation, perform non-rotating autotuning for the line-to-line  
resistance only on site.  
Loaded  
operation  
Optimum adjustments  
and parameter settings  
5.The default control mode is Open Loop Vector control  
(A1-02=2).  
Check/record  
6.If the maximum output frequency and the base frequency are  
different, set the maximum output frequency (E1-04) after  
autotuning.  
parameter settings  
END  
Fig 8 Trial Operation Flowchart  
EN-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Before Power Up  
The following points should be checked carefully before the power is switched on.  
Check if the power supply meets the inverter specification.  
Check if the power supply cables are tightly connected to the right terminals (L1, L2, L3).  
Check if the motor cables are tightly connected to the right terminals on the inverter side (U, V,  
W) as well as on the motor side.  
Check if the braking unit / braking resistor is connected correctly.  
Check if the Inverter control circuit terminal and the control device are wired correctly.  
Set all Inverter control circuit terminals to OFF.  
When a PG card is used, check if it is wired correctly.  
Display after Power Up  
After normal power up without any problems the operator display shows the following messages  
Rdy  
-DRIVE-  
Frequency Ref  
Display for normal  
operation  
The frequency reference monitor is dis-  
played in the data display section.  
U1- 01=50.00Hz  
U1-02=50.00Hz  
U1-03=10.05A  
When a fault has occurred or an alarm is active a fault or alarm message will appear. In this case,  
-DRIVE-  
A fault or alarm message is shown on the  
display.  
The example shows a low voltage alarm.  
UV  
Display for fault operation  
DC Bus Undervolt  
Autotuning  
Autotuning sets motor parameters automatically when using Open Loop or Closed Loop Vector con-  
trol, when the cable length is long or the installation has changed.  
Setting the Autotuning Mode  
One of the following three autotuning modes can be set.  
Rotating autotuning  
Non-rotating autotuning  
Non-rotating autotuning for line-to-line resistance only  
Rotating Autotuning (T1-01 = 0)  
Rotating autotuning is used for Open Loop and Closed Loop Vector control only. Set T1-01 to 0,  
input the data from the motor nameplate, and then press the RUN key on the Digital Operator. The  
Inverter will operate the motor for approximately 1 minute and set the required motor parameters  
automatically.  
Non-rotating Autotuning (T1-01 = 1)  
Non-rotating autotuning is used for Open Loop and Closed Loop Vector control only. Set T1-01 to 1,  
input the data from the motor nameplate, and then press the RUN key on the Digital Operator. The  
inverter will supply power to the non-rotating motor for approximately 1 minute and some of the  
EN-16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
motor parameters will be set automatically. The remaining motor parameters will be set automati-  
cally during the first time operation.  
Non-rotating Autotuning for Line-to-Line Resistance (T1-01 = 2)  
Non-rotating autotuning for line-to-line resistance can be used in any control mode. This is the only  
possible autotuning for V/f control and V/f control with PG.  
It can be used to improve the performance when the motor cable is long, the cable length has  
changed or when the motor and inverter have different capacities.  
To perform autotuning in V/f control or V/f control with PG, set T1-02 (Motor rated power) and T1-04  
(Motor rated current) and then press the RUN key on the Digital Operator. The Inverter will supply  
power to the non-rotating motor for approximately 20 seconds and the Motor line-to-line resistance  
and cable resistance will be automatically measured.  
1. Power will be supplied to the motor during autotuning but the motor will not turn. Do not touch the motor  
until autotuning has been completed.  
2. Ensure that all motor contactors are closed before the autotuning is started.  
3. To cancel autotuning press the STOP key on the Digital Operator.  
IMPORTANT  
Other Alarms and Faults During Autotuning  
For an overview of possible autotuning alarms or faults and corrective actions refer to page 24, Auto-  
EN-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
User Parameter  
Param-  
eter  
Num-  
ber  
Param-  
eter  
Num-  
Name  
Description  
Name  
Description  
ber  
Motor Slip Compensation (not available in V/f with  
PG)  
Initialize Data  
Language  
selection for  
Used to improve speed accuracy  
0:English  
2:German  
3:French  
Slip compensa-  
tion gain  
Increase if output frequency is too low  
Decrease if output frequency is too  
high.  
C3-01  
C3-02  
Digital Opera-  
tor dis-  
A1-00  
4:Italian  
5:Spanish  
6:Portuguese  
play(JVOP-  
160-OY only)  
Sets the slip compensation delay time  
Slip compensa-  
tion delay time  
(only available  
in V/f and OLV)  
Increase if output frequency is not  
stable  
Decrease setting when slip compen-  
sation responsiveness is low.  
0:Monitoring only (Monitoring drive  
mode and setting A1-01 and A1-04.)  
1:Used to select user parameters (Only  
parameters set in A2-01 to A2-32 can  
be read and set.)  
Parameter  
A1-01  
Speed Control (ASR) (only available in V/f with PG  
and CLV)  
2:Advanced  
access level  
(Parameters can be read and set in  
both, quick programming mode (Q)  
and advanced programming mode  
(A).  
ASR propor-  
tional gain 1  
Sets the proportional gain of the speed  
loop (ASR)  
C5-01  
0:V/f control  
ASR integral  
time 1  
Sets the integral time of the speed loop  
(ASR)  
C5-02  
Control method  
A1-02  
1:V/f control with PG  
2:Open loop vector control  
3:Closed loop vector control  
selection  
P,I  
ASR propor-  
tional gain 2  
P = C5-01  
I = C5-02  
C5-03  
0: No initializing  
1110:Initializes using the user  
parameters  
2220:Initializes using a two-wire  
sequence. (Initializes to the factory  
setting.)  
3330: Initializes using a three-wire  
sequence.  
P = C5-03  
I = C5-04  
ASR integral  
time 2  
C5-04  
C5-06  
Motor  
speed (Hz)  
A1-03 Initialize  
0
E1-04  
ASR delay time  
(only CLV)  
Sets the ASR filter time constant.  
ASR switching Sets the frequency for switching  
C5-07 frequency  
(only CLV)  
Sequence / Reference Source  
between ASR gain 1, 2 and ASR integral  
time 1, 2  
Sets the frequency reference input  
method.  
0:Digital Operator  
1:Control circuit terminal (analog input)  
2:Serial communication (RS422 / 485)  
3:Option Card  
Reference  
b1-01 source selec-  
tion  
ASR integral  
C5-08 limit  
Sets the limit for the integral part of the  
ASR controller.  
(only CLV)  
Carrier Frequency  
Sets the run command input method.  
0:Heavy Duty  
1:Normal Duty 1  
2:Normal Duty 2  
Heavy/Normal  
C6-01  
RUN com-  
b1-02 mand source  
selection  
0:Digital Operator  
duty selection  
1:Control circuit terminal (digital inputs)  
2:Serial communication (RS422 / 485)  
3:Option Card  
Selects the carrier frequency (factory  
setting depends on Inverter capacity)  
Selects the stopping method when the  
Run signal is removed  
0:Deceleration to stop  
1:Coast to stop  
2:DC injection to stop  
3:Coast to stop with timer (New Run  
commands are disregarded while  
coasting.)  
0: Low noise, low carrier  
1: 2.0 kHz  
Carrier fre-  
C6-02 quency selec-  
tion  
Stopping  
b1-03 method selec-  
tion  
2: 5.0 kHz  
3: 8.0 kHz  
4: 10.0 kHz  
5: 12.5 kHz  
6: 15.0 kHz  
F: Programmable pattern  
0:Reverse enabled  
Speed Settings  
1:Reverse disabled  
Prohibition of  
b1-04 reverse opera-  
tion  
Multi speed  
references 1 to  
16  
d1-01  
to  
d1-16  
2:Output Phase Rotation (both rota-  
tional directions are enabled)  
3:Output Phase Rotation with Reverse  
disabled.  
Sets the multi-step speed references.  
Jog frequency  
reference  
d1-17  
Acceleration / Deceleration Settings  
Acceleration/  
Deceleration  
times  
Sets the time to accelerate/decelerate  
from 0 Hz to the maximum output fre-  
quency.  
Torque Control (only available in CLV)  
C1-  
††  
Torque control  
selection  
0:Speed control  
1:Torque control  
d5-01  
S-Curve Settings  
Sets the delay from inputting a “speed/  
torque control change” signal (by digital  
input) until the control is acutally  
changed  
Speed/torque  
d5-06 control switch  
over timer  
S-curve char-  
acteristic time  
at acceleration  
Sets the S-curve characteristic at accel-  
eration start and end.  
C2-  
††  
V/f Pattern Settings  
Input voltage  
setting  
This setting is used as a reference value  
for protection functions.  
E1-01  
EN-18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Param-  
eter  
Num-  
ber  
Param-  
eter  
Num-  
ber  
Name  
Description  
Name  
Description  
Selects on which terminal the main  
frequency reference can be input.  
0:Use analog input 1 on terminal  
A1 for main frequency reference.  
1:Use analog input 2 on terminal A2  
for main frequency reference.  
Output Voltage (V)  
Max. output  
E1-04 frequency  
(FMAX)  
Terminal A1/  
A2 switching  
H3-13  
Max. output  
E1-05 voltage  
(VMAX)  
Terminal FM  
H4-01 monitor selec-  
tion  
Sets the number of the monitor item  
to be output (U1-††) at terminal FM/  
AM.  
Terminal AM  
H4-04 monitor selec-  
tion  
Frequency (Hz)  
Base fre-  
E1-06  
To set V/f characteristics in a straight  
line, set the same values for E1-07  
and E1-09. In this case, the setting for  
E1-08 will be disregarded.  
Always ensure that the four frequen-  
cies are set in the following order:  
E1-04 (FMAX) E1-06 (FA) > E1-07  
(FB) E1-09 (FMIN)  
quency (FA)  
Pulse Train I/O  
Selects the pulse train input function  
0:Frequency reference  
1:PID feedback value  
Pulse train  
H6-01 input function  
selection  
Base Voltage  
E1-13  
2:PID target value  
(VBASE)  
Sets the number of pulses in Hz that  
is equivalent to 100% of the input item  
selected in H6-01.  
Pulse train  
H6-02  
Motor Data Settings  
input scaling  
Motor rated  
current  
E2-01  
Pulse train  
H6-06 monitor selec-  
tion  
Selects the pulse train monitor output  
item (U1-††)  
Motor rated  
E2-02  
slip  
Pulse monitor Sets the number of pulses output in  
H6-07  
Motor no-load  
E2-03  
scaling  
Hz when the monitor item is 100%.  
current  
Stall Prevention  
Sets the motor data.  
Number of  
E2-04  
0:Disabled (Acceleration as set.  
With a heavy load, the motor may  
stall.)  
1:Enabled (Acceleration stopped  
when L3-02 level is exceeded.  
Acceleration starts again when the  
current has fallen below the stall  
prevention level).  
2:Intelligent acceleration mode (Using  
the L3-02 level as a basis, accelera-  
tion is automatically adjusted. Set  
acceleration time is disregarded.)  
motor poles  
Motor  
E2-09 mechanical  
losses  
Stall preven-  
tion selection  
L3-01 during accel  
(not available  
Motor rated  
E2-11  
output power  
in CLV)  
PG Option Setup  
Sets the number of PG pulses per  
revolution  
F1-01 PG constant  
0:Phase A leads with forward run  
command  
1:Phase B leads with forward run  
command  
0:Disabled (Deceleration as set. If  
deceleration time is too short, a  
DC bus overvoltage may result.)  
1:Enabled (Deceleration is stopped  
when the DC bus voltage exceeds  
the stall prevention level. Decelera-  
tion restarts when the voltage falls  
below the stall prevention level  
again.)  
2:Intelligent deceleration mode  
(Deceleration rate is automatically  
adjusted so that the Inverter can  
decelerate in the shortest possible  
time. The set deceleration time is  
disregarded.)  
F1-05 PG rotation  
Digital I/O Settings  
Terminal S3 to Refer to page 20, Digital Input Func-  
H1-01  
to  
H1-05  
S7 function  
selection  
tion Selections (H1-01 to H1-05) for a  
list of selections  
Stall preven-  
L3-04 tion selection  
during decel  
Terminal M1-  
M2 and M3-  
M4 function  
selection  
H2-01  
and  
H2-02  
Refer to page 20, Digital Output Func-  
tion Selections for a list of selections  
Analog I/O Settings  
Selects the signal level input at multi-  
function analog input A2.  
0:0 to +10 V (11 bit).  
3:Enabled with braking resistor  
Fault Restart  
Analog input  
H3-08 A2 signal level  
selection  
Sets the number of auto restart  
attempts.  
Automatically restarts after a fault and  
conducts a speed search from the run  
frequency.  
1:-10 to +10 V  
Number of  
L5-01 auto restart  
attempts  
2:4 to 20 mA (9-bit input).  
Ensure to switch S1-2 to “V” before  
using a voltage input.  
Analog input  
H3-09 A2 function  
selection.  
Selects the multi-function analog  
input function for terminal A2.  
Sets whether a fault relay is activated  
during fault restart.  
0:No output (Fault relay is not acti-  
vated.)  
1:Output (Fault relay is activated.)  
Auto restart  
L5-02 operation  
selection  
EN-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Param-  
eter  
Num-  
ber  
Param-  
eter  
Num-  
ber  
Name  
Description  
Name  
Description  
Fault Trace Data  
Torque Limit (only OLV and CLV)  
U2-01 Current fault  
Forward drive Sets the torque limit vlaue as a per-  
L7-01  
torque limit  
centage of the motor rated torque.  
U2-02 Last fault  
Four individual regions can be set.  
Reverse drive  
torque limit  
U2-03 Reference frequency at fault  
U2-04 Output frequency at fault  
U2-05 Output current at fault  
L7-02  
Output torque  
Positive torque  
Forward  
L7-03 regenerative  
torque limit  
No.  
o
motor  
Regen.  
U2-07 Output voltage reference at fault  
U2-08 DC bus voltage at fault  
U2-09 Output power at fault  
U2-11 Input terminal status at fault  
U2-12 Output terminal status at fault  
U2-13 Operation status at fault  
U2-14 Cumulative operation time at fault  
Fault History Data  
rotations  
Reverse  
Forward  
Regen.  
Reverse  
L7-04 regenerativ  
torque limit  
Negative torque  
Monitor Data  
U1-01 Frequency reference in Hz / rpm  
U1-02 Output frequency in Hz / rpm  
U1-03 Output current in A  
U3-01  
to  
U1-06 Output voltage in VAC  
U1-07 DC bus voltage in VDC  
U1-08 Output power in kW  
Last fault to fourth last fault  
U3-04  
U3-05  
to  
U3-08  
Cumulative operation time at fault 1 to 4  
Fifth last to tenth last fault  
U1-09 Torque reference  
Shows input ON/OFF status.  
U1-10 =  
U3-09  
to  
1: FWD command  
(S1) is ON  
U3-14  
1: REV command  
(S2) is ON  
1: Multi input 1  
(S3) is ON  
U3-15  
to  
U3-20  
Accumulated time of fifth to tenth fault  
Input terminal  
status  
U1-10  
1: Multi input 2  
(S4) is ON  
1: Multi input 3  
(S5) is ON  
1: Multi input 4  
(S6) is ON  
1: Multi input 5  
(S7) is O N  
* The following faults are not recorded in the error log:  
CPF00, 01, 02, 03, UV1, and UV2.  
Digital Input Function Selections (H1-01 to H1-05)  
3
4
5
Multi-step speed reference 1  
Multi-step speed reference 2  
Mulit-step speed reference 3  
Shows output ON/OFF status.  
U1-11 =  
Jog frequency command (higher priority than multi-  
step speed reference)  
6
1: Multi-function  
contact output 1  
(M1-M2) is ON  
1: Multi-function  
contact output 2  
(M3-M4) is ON  
1: Multi-function  
contact output 3  
(M5-M6) is ON  
Not used  
7
F
Accel/decel time selection 1  
Not used (Set when a terminal is not used)  
Fault reset (Reset when turned ON)  
PI control disable  
Output termi-  
nal status  
14  
19  
U1-11  
External fault; Input mode: NO contact/NC contact,  
Detection mode: Normal/during operation  
20 to  
2F  
(Always 0).  
1: Error output  
(MA/MB-MC) is ON  
71  
77  
Speed/torque control change (ON: Torque control)  
Speed control (ASR) gain switching (ON: C5-03)  
Inverter operating status.  
Digital Output Function Selections  
(H2-01 and H2-02  
U1-12 =  
Run  
During run 1 (ON: run command is ON or voltage is  
0
being output)  
1: Zero speed  
Inverter operation ready; READY: After initialization or  
no faults  
1: Reverse  
6
Operation sta-  
tus  
U1-12  
1: Reset signal input  
1: Speed agree  
1: Inverter ready  
1: Minor fault  
F
Not used. (Set when the terminal is not used.)  
Minor fault (Alarm) (ON: Alarm displayed)  
During reverse run (ON: During reverse run)  
10  
1A  
Motor overload (OL1, including OH3) pre-alarm (ON:  
90% or more of the detection level)  
1F  
30  
1: Major fault  
U1-13 Cumulative operation time in hrs.  
U1-21 ASR input  
During torque limit (current limit) (ON: During torque  
limit)  
Activated if the ASR is operating for torque limit. The  
ASR output becomes the torque reference, the motor  
is rotating at the speed limit.  
U1-22 ASR output  
32  
U1-34 OPE fault parameter  
U1-40 Cooling fan operating time in hrs.  
EN-20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
General Faults and Alarms  
Faults and Alarms indicate unsusal inverter / application conditions.  
An alarm does not necessarily switch off the inverter but a message is displayed on the keypad (i.e.  
a flashing alarm code) and an alarm output can be generated at the multi-function outputs (H2-01  
and H2-02) if programmed. An alarm automatically disappears if the alarm condition is not present  
anymore.  
A fault switches the inverter output off immediately, a message is displayed on the keypad and the  
fault output is switched. The fault must be reset manually after the cause and the RUN signal have  
been removed.  
The following table shows a list of faults and alarms with their corrective actions.  
Alarm Fault  
Display  
Meaning  
Corrective Actions  
Option Card Communication Alarm  
After initial communication was established, the  
connection was lost.  
Check the connections and all user-side soft-  
ware configurations.  
BUS  
Option Com Err  

Control Fault  
A torque limit was reached continuously for 3  
seconds or longer during a deceleration stop in  
Open Loop Vector control  
CF  
Check the motor parameters  


Out of Control  
CPF00  
COM-  
ERR(OP&INV)  
Digital Operator Communication Fault 1/2  
• Communication fault between Operator and  
Inverter  
• Disconnect the Digital Operator and then  
connect it again.  
• Cycle the Inverter power supply.  
• Replace the Inverter.  
CPF01  
COM-  
• CPU External RAM Fault  
ERR(OP&INV)  
CPF02 Fault  
Baseblock circuit error  
CPF02  
BB Circuit Err  



• Perform an initialization to factory defaults.  
• Cycle the Inverter power supply.  
• Replace the Inverter.  
CPF03  
EEPROM error  
CPF03  
EEPROM Error  
CPF04  
CPF04  
INternal A/D Err  
CPU Internal A/D Converter Fault  
F1-04 = 0, 1 or 2 and A1-02 = 1 or 3  
The speed deviation has been greater than the  
setting in F1-10 for a time longer than the setting  
F1-11.  
• Reduce the load.  
• Lengthen the acceleration and deceleration  
time  
• Check the mechanical system  
• Check the settings of F1-10 and F1-11  
• Check the sequence and if the brake is  
opened when the inverter starts to increase  
the speed.  

DEV  
Speed Deviation  
F1-04 = 3 and A1-02 = 1 or 3  
The speed deviation has been greater than the  
setting in F1-10 for a time longer than the setting  
F1-11.  

Forward/Reverse Run Commands Input  
Together  
Both the forward and the reverse run commands  
are input simultaneously for 500ms or more.  
This alarm stops the motor.  
EF  
Check external sequence logic, so that only  
one input is activated at a time.  
External Fault  

• Check for an external fault condition.  
• Verify the parameters.  
• Verify communication signals  
External fault input from Communications  
Option Card  
EF0  
Opt External Flt  

External fault at terminal Sx (x stands for termi- Eliminate the cause of the external fault con-  
nals S3 to S7) dition.  
EFx  
Ext Fault Sx  



Detected after a fault when a RESET command Remove the RUN signal first and reset the  
is input while the RUN command is still active error.  
Ext Run Active  
Cannot Reset  
• Remove the motor and run the Inverter  
without the motor.  
Ground Fault  
The ground current at the Inverter output  
• Check the motor for a phase to ground  
short.  
GF  

Ground Fault  
exceeded 50% of the Inverter rated output cur- • Check the output current with a clampmeter  
rent and L8-09=1 (Enabled).  
to verify the DCCT reading.  
• Check the control sequence for wrong  
motor contactor signals.  
EN-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Alarm Fault  
Display  
Meaning  
Corrective Actions  
• Remove the motor and run the Inverter  
without the motor.  
Over Current  
• Check the motor for a phase-to-phase  
OC  
Over Current  
The Inverter’s output current exceeded the over- short.  
current detection level.  

• Verify the accel/decel times (C1-††).  
• Check the Inverter for a phase-to-phase  
short at the output.  
Heatsink Overheat  
L8-03 = 0,1 or 2 and the temperature of the  
Inverter's cooling fin exceeded the L8-02 value.  
• Check for dirt build-up on the fans or heat-  
sink.  
• Reduce the ambient temperature around  
the drive.  

OH  
Inverter's Cooling Fan Stopped  
Heatsnk Overtemp  
L8-03 = 3 or 4 and the temperature of the  
Inverter's cooling fin exceeded the L8-02 value.  
• Replace the cooling fan(s).  

Heatsink Overheat  
The temperature of the Inverter’s heatsink  
exceeded 105 °C.  
• Check for dirt build-up on the fans or heat-  
sink.  
• Reduce the ambient temperature around  
the drive.  
OH1  


Heatsink Max Temp  
Inverter’s Cooling Fan Stopped  
• Replace the cooling fan(s).  
Motor Overload  
Detected when L1-01 is set to 1,2 or 3 and the  
Inverter’s I²t value exceeded the motor overload  
curve.  
The overload curve is adjustable using parame-  
ter  
E2-01 (Motor Rated Current), L1-01 (Motor Pro-  
tection Selection) and L2-02 (Motor Protection  
Time Constant)  
• Recheck the cycle time and the size of the  
load as well as the accel/decel times (C1-  
††).  
• Check the V/f characteristics (E1-††).  
• Check the setting of Motor Rated Current  
Setting (E2-01).  
OL1  
Motor Overload  
• Recheck the cycle time and the size of the  
load as well as the accel/decel times (C1-  
††).  
• Check the V/f Characteristics (E1-††).  
• Check if the inverter rated current matches  
the motor rated current.  
Inverter Overload  
The Inverter output current exceeded the Invert-  
ers’s overload capability  
OL2  
Inv Overload  

F1-03 = 0, 1 or 2 and A1-02 = 1 or 3  
The motor speed feedback (U1-05) exceeded  
the setting in F1-08 for a time longer than the  
setting of  

• Adjust the ASR settings in the C5 parame-  
ter groupt  
• Check the reference circuit and reference  
gain.  
F1-09  
OS  
Overspeed Det.  
F1-03 = 3 and A1-02 = 1 or 3  
The motor speed feedback (U1-05) exceeded  
the setting in F1-08 for a time longer than the  
setting of  
• Check the settings in F1-08 and F1-09  

F1-09  
• Increase the deceleration time (C1-02/04)  
or connect a braking option.  
• Check the power supply and decrease the  
voltage to meet the inverter’s specifica-  
tions.  
The DC bus voltage has exceeded the overvolt-  
age detection level.  
Default detection levels are:  
200 V class: 410 VDC  

(onlyin  
OV  



stop  
condi-  
tio)  
DC Bus Overvolt  
400 V class: 820 VDC  
• Check the braking chopper / resistor.  
Input Phase Loss  
Too big DC bus voltage ripple.  
Only detected when L8-05=1 (enabled)  
• Tighten the input terminal screws  
• Check the power supply voltage  
PF  
Input Phase Loss  
PG Disconnection  
Detected when F1-02 = 0, 1 or 2 and A1-02 = 1  
or 3.  
Detected when no PG (encoder) pulses have  
been received for a time longer than the setting  
in F1-14.  
• Fix the broken/disconnected wiring.  
• Supply power to the PG properly.  
• Check the sequence and if the brake is  
opened when the inverter starts to increase  
the speed.  
PGO  
PG Open  
PG Disconnection  
Detected when F1-02 = 3 and A1-02 = 1 or 3.  
PG (encoder) pulses have not been received for  
a time longer than the setting in F1-14.  

EN-22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alarm Fault  
Display  
Meaning  
Corrective Actions  
DC Bus Fuse Open  
The fuse in the main circuit is blown.  
Warning:  
• Check the motor and the motor cables for  
short circuits or insulation failures (phase-  
to-phase).  
PUF  

DC Bus Fuse Open  
PG (encoder) pulses have not been received for • Replace the inverter after correcting the  
a time longer than the setting in F1-14.  
fault.  
Dynamic Braking Transistor  
The built-in dynamic braking transistor failed  
• Cycle power to the inverter.  
• Replace the inverter.  
RR  

DynBrk Transistr  
The DC bus voltage is below the Undervoltage • Check the input voltage.  
Detection Level  
• Check the wiring of the input terminals.  
• Check the input voltage and the wiring of  
the input terminals.  

(L2-05). The default settings are:  
200V class: 190 VDC  
400 V class: 380 VDC  
(onlyin  
UV1  


stop  
condi-  
tio)  
DC Bus Undervolt  
• Extend the settings in C1-01/03  
Main Circuit MC Operation Failure  
No MC response during Inverter operation.  
Replace the Inverter.  
Control Power Supply Undervoltage  
Undervoltage of the control circuit while the  
Inverter was running.  
• Remove all connection to the control termi-  
nals and cycle the power to the Inverter.  
• Replace the Inverter.  
UV2  
CTL PS Undervolt  
Operator Programming Errors  
An Operator Programming Error (OPE) occurs when two or more parameter related to each other  
are set inappropriately or an individual parameter setting is incorrect. The Inverter does not operate  
until the parameter setting is corrected; however, no other alarm or fault output will occur. If an OPE  
occurs, change the related parameter by checking the cause shown in the table below. When an  
OPE error is displayed, press the ENTER key to see U1-34 (OPE Detected). This monitor displays  
the parameter that is causing the OPE error.  
Display  
Meaning  
Corrective Actions  
OPE01  
kVA Selection  
Inverter kVA Setting Error  
Enter the correct kVA setting in o2-04.  
OPE02  
Limit  
Parameter setting is out of its range  
Verify the parameter settings.  
One of the following errors has been made in the multi-  
function input (H1-01 to H1-05) settings:  
• Duplicate functions were selected.  
• UP/DOWN Command(10 and 11) were not selected  
simultaneously.  
• The up/down commands (10 and 11) and Accel/  
Decel Ramp Hold (A) were selected at the same  
time.  
• More than one of the Speed Search inputs (61, 62,  
64) were set simultaneously.  
• External Baseblock NO (8) and External Baseblock  
NC (9) were selected at the same time.  
• The up/down commands (10 and 11) were selected  
while PID Control was enabled.  
OPE03  
Terminal  
Verify the parameter settings in H1-††  
• The Emergency Stop Command NO (15) and NC(17)  
are set simultaneously.  
• PID is enabled and UP and/or DOWN (10 / 11) com-  
mand are set.  
• HSB (68) and KEB (65/66) command are set simulta-  
neously.  
RUN/Reference Command Selection Error  
• Verify that the board is installed. Remove the power  
supply and re-install the option board again  
• Recheck the setting of b1-01 and b1-02  
The Reference Source Selection b1-01 and/or the RUN  
Source Selection parameter b1-02 are set to 3 (option  
board) but no option board is installed.  
OPE05  
Sequence Select  
Control Method Selection Error  
One of the control methods needing a PG feedback  
Verify the control method selection in parameter A1-02  
OPE06  
PG Opt Missing  
was selected (A1-02 = 1 or 3), but a PG option board is and/or the installation of the PG option board.  
not installed.  
EN-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Display  
Meaning  
Function Selection Error  
Corrective Actions  
A setting has been made that is applicable with the cur-  
rent control method.  
Example: A function used only with open loop vector  
control was selected for V/f control.  
OPE08  
Constant Selection  
Verify the control method and the function.  
Check parameters (E1-††). A frequency/voltage value  
may be set higher than the maximum frequency/voltage.  
OPE010  
V/f Ptrn Setting  
V/f Parameter Setting Error  
Autotuning Faults  
Autotuning faults are shown below. When the following faults are detected, the fault is displayed on  
the digital operator and the motor coasts to stop. No fault or alarm outputs will be operated.  
Display  
Meaning  
Corrective Actions  
• Check the input data.  
• Check the Inverter and motor capacity.  
• Check the motor rated current and no-load current set-  
ting.  
Er-01  
Fault  
Motor data fault  
• Check the input data.  
• Check wiring and the machine.  
• Check the load.  
Er-02  
Minor Fault  
Alarm  
Er-03  
STOP key  
STOP key input  
-
Line-to-Line Resistance Fault  
Autotuning result is outside the parameter setting  
range.  
Er-04  
Resistance  
• Check the input data.  
No-Load Current Fault  
Autotuning result is outside the parameter setting  
range.  
• Check the motor wiring.  
Er-05  
No-Load Current  
• If the motor is connected to the machine, disconnect it.  
• If the setting of T1-03 is higher than the Inverter input  
power supply voltage (E1-01), change the input data.  
Rated Slip Fault  
Autotuning result is outside the parameter setting  
range.  
Er-08  
Rated slip  
Acceleration Fault (Rotating autotuning only)  
The motor did not accelerate in the specified time  
(C1-10+10sec.)  
• Increase C1-01(Acceleration time)  
• Increase L7-01 and L7-02 (Torque limits)  
• If the motor is connected to the machine, disconnect it.  
Er-09  
Accelerate  
Motor Speed Fault (Rotating autotuning only)  
• If the motor is connected to the machine, disconnect it.  
The torque reference exceeded 100% during accel- • Increase C1-01  
Er-11  
Motor Speed  
eration. Deteceted only when A1-02 = 2 or 3 (Vector • Check the input data (particularly the number of PG  
control modes).  
pulses and the number of motor poles)  
Current Detection Fault  
• The current exceeded the motor rated current.  
• Any of U/T1, V/T2 and W/T3 has open-phase.  
Er-12  
I-det. Circuit  
Check wiring of the Inverter and the mounting.  
Leakage Inductance Fault  
Er-13  
Leakage Induc- Autotuning result is outside the parameter setting  
Check motor wiring.  
tance Fault  
range.  
Rated Current Setting Alarm  
Displayed after auto-tuning is complete  
During auto-tuning, the measured value of motor  
rated current (E2-01) was higher than the set value.  
End-1  
V/f Over Setting  
Check the motor rated current value.  
• Check the input data  
• Check the motor wiring.  
• If the motor is connected to the machine, disconnect it.  
Motor Core Saturation Alarm  
(only for rotating autotuning)  
End-2  
Saturation  
Rated Current Setting Alarm  
During autotuning the measured value of motor rated Check the motor rated current value  
current (E2-01) was greater than the set value.  
End-3  
Rated FLA Alm  
EN-24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 

Miller Electric Welder MW 4150 User Manual
Multiquip Portable Generator DCA180SSJU User Manual
Musical Fidelity Stereo Amplifier A308 CR User Manual
NEC Telephone AT 35 User Manual
NETGEAR Network Router DGND4000 100NAS User Manual
New Buck Corporation Indoor Fireplace 42ZCBB User Manual
Optiview DVR 22806 437 User Manual
Oricom Cordless Telephone ECO80 User Manual
Panasonic CD Player CF VCD711 User Manual
Panasonic Impact Driver EY6506 User Manual