Omega Home Theater Server CN154 User Manual

Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(5) Near high voltage power lines or where inductive  
interference can affect the operation of the product.  
(6) Dew drops or direct exposure to sun light.  
(7) Where the elevation is in excess of 2,000 m.  
Dimension of current transformer (CT) for heater break  
alarm  
• For 0-30A (CTL-6-S)...................................For 0-50A (CTL-12-S36-8)  
φ 2.36  
30  
2.36  
2.8  
15  
Note: The environmental conditions belong to the installation  
φ 5.8  
category II of IEC 664 and the degree of pollution is 2.  
21  
2-2. Mounting  
φ 12  
2- φ 3.5  
(1) Machine the mounting hole by referring to panel cutout in  
section 2-4.  
(2) Applicable thickness of the mounting panel is from 1.0 to 3.5  
mm.  
30  
40  
2-M3 depth 4  
30  
40  
(3) As this product provides mounting fixture, insert the product  
from the front panel for installation.  
(unit : mm)  
2-5. Wiring  
2-3. How to remove the instrument out of the case  
WARNING  
CAUTION  
• Always disconnect this product from any power source  
during wiring operation to prevent electrical shock.  
• Be certain that the protective conductor terminal ( ) is  
properly grounded. Otherwise, a serious electric shock may  
result.  
When the instrument is removed/replaced in the case, make sure  
the power is off. If it is done while the power is on, it may lead  
to problems with the product and/or other problems.  
There is no need to remove your  
CN150 series controllers out  
of the case. Nevertheless, should the  
• Avoid touching the wired terminal and charged devices while  
supplying power.  
PV  
need arise, for example, for  
replacement, follow the steps  
described below:  
˚C  
SV  
(1) Wiring operation should be done according to the instruction  
for the terminal arrangement in section 2-6. Exercise care  
that no wrong connection is made.  
(2) Crimp terminal should accommodate the M3.5 screw and  
should have a width of less than 7mm.  
(3) For thermocouple input, select the compensation wire  
suitable to the thermocouple type.  
(4) For R. T. D. input, leads should be less than 5in resistance  
and three leads should have the same resistance.  
(5) Input signal line should be conducted safely apart from the  
high voltage power line.  
OUT AT  
AH AH/HB MAN STBY COM  
Insert a minus screwdriver of 6mm ~  
9mm into the opening (where  
packing is exposed) of the front case  
and rotate the screwdriver while  
pushing up the lock lever behind the  
packing. Once the instrument comes  
out by a few millimeters, you can  
remove it by hand.  
ENT  
MAN  
(6) Shield wiring (single point grounding) is effective for static  
induction noise.  
2-4. External dimensions and panel cutout  
CN154/CN155 External dimensions  
CN154/CN155 Panel cutout  
(7) Short interval twisted pair wire for input signal is effective  
for electromagnetic induction noise.  
(8) For power line, use wire or cable which is 1mm or more in  
110  
130 min.  
10  
100  
2
sectional area and of which the performance is equal to or  
higher than that of 600V vinyl insulated wire.  
92+0.8  
0
(9) Earth grounding should be performed with earth resistance  
2
less than 100and with wire thicker than 2mm .  
96  
91.6  
2-6. Terminal arrangement  
SR73A  
422A 485  
L
1
2
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
SG  
SG  
+
CN158/CN159 External dimensions  
CN158/CN159 Panel cutout  
Power  
SB  
CT  
110  
N
SD+  
SD–  
RD+  
RD–  
10  
100  
45+0.6  
0
3
(48 x N-3) +1.0  
0
4
COM+  
CONTROL  
OUTPUT  
5
NO  
NC  
height 91.6  
92+0.8  
0
height 96  
×
6
×
width 44.6  
width 48  
7
+A  
TC•mV  
V•mA  
–B  
8
COM  
AH  
When N pieces are  
installed laterally.  
N= number  
ALARM  
OUTPUT  
9
B
10  
AL/HB  
(unit : mm)  
- 3 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CN158/CN159  
3-2. Instruction for front panel  
422A 485  
: Measured value (PV) display (green)  
(1) Displays current measured value on the mode 0 basic  
screen.  
L
1
2
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
SG  
SG  
+
Power  
21  
22  
N
SD+  
SD–  
RD+  
RD–  
SB  
3
(2) Displays parameter type on each parameter screen.  
4
COM+  
: Set value (SV) display (orange)  
CONTROL  
OUTPUT  
5
NO  
NC  
(1) Displays set value on the mode 0 basic screen.  
(2) Displays selected item and set value on each parameter  
screen.  
6
7
+A  
TC•mV  
V•mA  
–B  
8
COM  
AH  
: Monitor LED  
CT  
ALARM  
OUTPUT  
9
(1) OUT (output) monitor LED (green)  
• For contact or SSR drive voltage output, a light turns  
on for output ON and turns off for output OFF.  
• For current or voltage output, the light intensity  
changes proportionally to the output altitude.  
(2) AT (auto tuning) monitor LED (green)  
23  
24  
B
10  
AL/HR  
2-7. Terminal arrangement table  
Terminal number  
CN150 Series  
• On selection by  
, ON turns on AT waiting  
Name of terminal and description  
ENT  
(
key), flashes on AT execution.  
(3) AH alarm output monitor LED (red)  
• Turns on for higher limit alarm output ON.  
(4) AL/HB alarm output monitor LED (red)  
• Turns on for lower alarm output ON or heater break  
alarm ON.  
(5) MAN (manual control output) monitor LED (green)  
• Flashes when control output is in manual operation.  
(6) STBY (control output stop) monitor LED (green)  
• Turns on when the control output stop mode is  
selected.  
Power terminal  
100-260V AC±10% 50/60Hz 12VA  
11-12  
13  
Protective conductor terminal (  
)
Input terminal  
R. T. D. A, Thermocouple, Voltage, Current +  
R. T. D. B, Thermocouple, Voltage, Current –  
R. T. D. B  
7
8
10  
Output terminal  
Contact: COM, SSR Drive voltage, Voltage,  
Current +  
Contact: NO, SSR Drive voltage, Voltage,  
Current –  
14  
15  
16  
(7) COM (communication) monitor LED (green)  
• Turns on when the remote communication mode is  
selected.  
Contact: NC  
Communication terminal  
: Key switches  
For RS-422A  
SG  
For RS-485  
(1)  
(parameter) key  
1
2
3
4
5
SG  
+
• Press on set screen to move to next set screen.  
• Keep pressing three (3) seconds for function of move  
key between basic screen of the mode 0 screen group  
and direct call screen of mode 1 screen group.  
(down) key  
• Press on the set screen to flash the point of the least  
digit and to reduce data or back increment data.  
(up) key  
SD+  
SD–  
RD+  
RD–  
(2)  
(3)  
(4)  
Alarm output (option) terminal  
COM Contact rating 240V AC 1.5A  
(resistive load)  
18  
AH  
Higher limit alarm  
19  
20  
AL/HB Lower limit alarm or heater break alarm  
• Press on the set screen to flash the point of the least  
digit and to increase data of increment data.  
Set value bias (option) input terminal  
21-22  
23-24  
ENT  
(entry/registration) key  
Heater break alarm (option) CT input terminal  
• Press on the set screen of the mode 0 screen group  
and mode 1 screen group to fix the data changed by  
the  
Note: For Thermocouple, Voltage, and Current input,  
measurement error results by connection between B and  
B terminal.  
,
keys and to extinguish flash of the point.  
• The function selecting screen, of the mode 2 screen  
group, registers data of the point flashing digit and  
simultaneously shifts a data changeable digit (the  
point flashing digit).  
• The input scaling screen, of the mode 2 screen group,  
registers data and shifts a parameter capable of being  
set (in the row in which the rightmost point is  
flashing).  
• Press the key for five seconds and it functions to  
change the basic screen of the mode 0 screen group to  
the function selecting screen of the mode 2 screen  
group and vice versa.  
3. Instruction for front panel  
3-1. Drawing and the name of the parts  
This is an example of the front panel of CN154/CN155.  
Name of parts  
: Measured value  
(PV) display  
: Set value (SV)  
display  
: Monitor LED  
: Key switches  
PV  
1
˚C  
SV  
MAN  
(5)  
(manual) key  
2
• Pressing this key on the control output screen changes  
automatic control output to manual control output and  
vice versa. During manual control output, the MAN  
monitor LED flashes.  
OUT  
AT  
AH AH/HB  
MAN STBY  
COM  
3
4
ENT  
MAN  
MAN  
• The  
key does not function in the control output  
stop mode.  
- 4 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(3) Screen change within mode 0 screen group  
• By pressing the key, the screen changes.  
(4) Screen change within mode 1 screen group  
4. Screen instruction  
4-1. Power on and initial screen display  
• Two methods are used for screen change within mode 1  
After turning on power, the display shows each power on initial  
screen for approx. 1.5 seconds, then moves into the basic screen  
of the mode 0 screen group.  
screen group. One is to press the  
key as shown on  
above mode 0 screen group. The other is to mode the  
screen directly by indicating screen No. on the top direct  
call screen.  
Example: Direct calling the screen No.8 PV bias value set  
screen  
Turning  
on power  
,
Series type (  
Input type (  
)
: Thermocouple,  
: Voltage (mV),  
: R. T. D.,  
: Voltage (V),  
1-0 direct call screen  
1-0 direct call screen  
1-8 PV bias value set screen  
ENT  
key  
: Current (mA))  
key  
Displays output screen  
Control output type : Contact  
: Current  
several times  
: SSR drive voltage  
: Voltage  
point flashes  
(5) Selecting and setting digit to change of function selecting  
screen of mode 2 screen group  
Lower limit of the selected measuring range  
Higher limit of the selected measuring range  
• When the function selecting screen is displayed, the point  
of selectable digit flashes.  
Mode 0 screen group basic screen  
Measured value (PV)  
Set value (SV)  
• By pressing  
point is flashing) moves.  
key, the selectable digit (digit whose  
ENT  
• In case of changing the set value, flash the point to be  
ENT  
changed with  
key, select data with the keys and  
4-2. Alarm type code table  
press key again to register the set value and move  
selectable digit.  
Example: changing the control output characteristics from  
(heating) to (cooling)  
With/Without AL/HB  
With/Without  
AH  
Alarm code  
inhibit action assignment inhibit action  
assignment  
Not assigned  
– – – – –  
Not assigned  
– – – – –  
0 (  
1 (  
2 (  
3 (  
4 (  
5 (  
6 (  
7 (  
8 (  
)
)
)
)
)
)
)
)
)
Without  
inhibit action  
Without  
inhibit action  
Higher limit  
deviation value  
Higher limit  
absolute value  
Lower limit  
deviation value  
ENT  
ENT  
key  
key  
key  
Lower limit  
absolute value  
Without  
inhibit action  
Without  
inhibit action  
Higher limit  
deviation value  
Higher limit  
absolute value  
Lower limit  
deviation value  
With  
inhibit action  
With  
inhibit action  
Lower limit  
absolute value  
With  
inhibit action  
With  
inhibit action  
* “.” on the screen shows the selectable digit (digit whose  
point is flashing).  
Higher limit  
deviation value  
Higher limit  
absolute value  
Without  
Heater break  
Heater break  
Heater break  
Heater break  
– – – – –  
– – – – –  
– – – – –  
– – – – –  
inhibit action  
Without  
inhibit action  
ENT  
Note: In case of changing data and pressing  
key longer  
than 5 seconds, the screen moves to mode 0 basic screen  
without a data registration. It requires a data verification  
Higher limit  
deviation value  
Higher limit  
absolute value  
With  
inhibit action  
With  
inhibit action  
ENT  
with  
key and screen change.  
(6) Shifting setting items on input scaling screen of mode 2  
screen group and setting method  
Note: In the above table, the alarm codes 5 through 8 are  
selectable when the apparatus has the optional function  
of heater break alarm.  
• Pressing the  
key on the function selecting screen calls  
the input scaling screen onto the display. The decimal  
point in the rightmost position on the top row flashes.  
4-3. Screen change  
Press the  
and press the  
or  
ENT  
key to change the lower limit value  
key to register the data.  
(1) Screen change from mode 0 group to mode 1 group  
• Upon registering the lower limit value data, the decimal  
point in the rightmost digit in the bottom row begins to  
flash. Change the higher limit value by pressing the  
ENT  
• Pressing the  
of the mode 0 screen group changes it to the direct call  
screen of the mode 1 screen group and vice versa.  
key for three seconds on the basic screen  
or  
key and register it by means of the  
key.  
0-0 Basic Screen  
1-0 direct call screen  
• Upon registering the higher limit value data, the decimal  
points in the rightmost digits of the bottom and top rows  
flash. Change the positions of the decimal points by  
key  
3 seconds  
pressing the  
or  
key and register it by means of the  
ENT  
key.  
(2) Screen change from mode 0 group to mode 2 screen group  
• Pressing the key for five seconds on the basic screen  
ENT  
• Each time the  
key is pressed, the flashing decimal  
ENT  
point in the rightmost digit moves from the top row→  
bottom rowtop and bottom rowstop row.  
of the mode 0 screen group changes it to the function  
selecting screen of the mode 2 screen group and vice versa.  
• In case the lower limit value and the higher limit value are  
set to produce a difference which is less than 100 counts or  
more than 5000 counts, the higher limit value is forced to  
change to +100 or +5000 counts. The higher limit cannot  
be set to be less than a lower limit value +100 counts or  
more than a lower limit value +5000 counts.  
0-0 Basic Screen  
2-0 Function selecting screen  
ENT  
key  
5 seconds  
- 5 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4-4. Instruction for screen change and each screen  
ENT  
Note: In the following, the  
indicates that the key above  
the mark should be pressed.  
mark  
key  
5 seconds  
MODE 1 Screen Group  
1-0  
Mode 0 Screen Group  
0-0  
key  
3 seconds  
Direct call screen (screen No.0)  
Initial value: 0  
Setting range: 0~19  
Set the screen No. to move the screen of the mode 1 screen group.  
Refer to Item 4-3 (4) for detail.  
The screen with no display condition is skipped.  
Basic screen  
SV initial value: lower limit of measuring range  
Setting range: within measuring range  
1-1  
1-2  
Upper row displays measured value (PV) and lower row displays and  
changes the set value (SV). Refer to Item 5-1 for detail.  
Set value bias set screen (screen No.1)  
Initial value: 0  
Setting range: -1999~2000 unit  
Displays in the case with set value bias option. The set value is effective  
during shorted SB terminal, and is added to the set value. While it is  
valid, the leftmost point on the bottom row stays lit on each displayed  
screen, excluding the input scaling setting screen.  
0-1  
0-2  
Control output screen  
Initial value for manual operation:  
The value immediately before switched to manual  
Setting range for manual operation: 0~100%  
The measured value (PV) is displayed on the top and the control output  
value on the bottom. Pressing the MAN key on this screen switches  
auto to manual and vice versa. Refer to Item 4-6 (1) for detail.  
Proportional band set screen (screen No.2)  
Initial value: 3.0%  
Setting range: OFF, 0.1~999.9%  
Refer to Item 6-2 (1) for proportional band.  
Select “OFF” to perform ON/OFF action.  
P OFF  
Control execution/stop selecting screen  
Initial value: EXEC  
Setting range: EXEC, STBY  
STBY, MAN,  
For ON/OFF  
P=OFF  
Execution (  
) or stop (  
) of control is selected.  
1-3  
Refer to Item 4-6 (2) for detail.  
Action hysteresis set screen (screen No.3)  
Initial value: 3 or 0.3  
Setting range: 1~999 unit  
Set ON/OFF hysteresis on ON/OFF action.  
This screen appears only when P=OFF.  
0-3  
AT (auto tuning) action control screen  
Initial value: OFF  
Setting range: OFF, ON  
For “ON” selection, AT is executed and for “OFF” selection, AT is  
cancelled.  
Refer to Item 5-2 for detail. This screen appears only during ON/OFF  
operation; it does not appear when control is suspended or during  
manual output.  
1-4  
1-5  
Integral time set screen (screen No.4)  
Initial value: 120 seconds  
Setting range: OFF, 1~6000 seconds  
Refer to Item 6-2 (2) for integral time.  
Not shown on ON/OFF action. Selection of OFF starts P or PD action.  
No option  
0-4  
Higher limit alarm set screen  
Initial value: Absolute value alarm:  
Derivative time set screen (screen No.5)  
Initial value: 30 seconds  
Setting range: OFF, 1~3600 seconds  
Refer to Item 6-2 (3) for derivative time.  
Not shown on ON/OFF action.  
higher limit for the measuring range  
Deviation alarm: 2000 unit  
Setting range: Absolute value alarm: within measuring range  
Deviation alarm: 0~2000 unit  
Displays except the case with alarm option and the alarm type of the  
function selecting screen of mode 2 screen group is not specified.  
Refer to Item 5-3 (1) for detail.  
I OFF  
Selection of OFF starts P or PI action.  
I=OFF  
1-6  
Manual reset value setting screen (screen No.6)  
No.6 Initial value: 0.0%  
Setting range: -50.0~-50.0%  
0-5  
Lower limit alarm set screen  
Offset is adjusted when I=OFF (P or PD action) is selected.  
For details of manual resetting, refer to Item 4-6 (3).  
This screen appears only when 1=OFF has been selected.  
Initial value: Absolute value alarm:  
lower limit for the measuring range  
Deviation alarm: -1999 unit  
Setting range: Absolute value alarm: within measuring range  
Deviation alarm: -1999~0 unit  
Displays in case with alarm option and the alarm type of the function  
selecting screen of mode 2 screen group is higher limit and lower limit.  
Refer to Item 5-3 (2) for detail.  
1-7  
1-8  
Set value function set screen (screen No.7)  
Initial value: 0.40  
Setting range: OFF, 0.01~1.00  
Used for suppressing overshooting and undershooting in expert PID.  
For SF=1.00, minimize overshooting, for SF=OFF, expert PID is unable  
to be normal PID action. This screen does not appear when P=OFF or  
I=OFF.  
0-6  
Heater break alarm value set screen  
Initial value: OFF  
Setting range: OFF, 0, 1~50.0A or OFF, 1~500A  
Displays in the case with heater break alarm option and alarm type of the  
mode 2 screen is higher limit+heater break.  
Refer to Item 5-3 (3) for detail.  
PV bias value set screen (screen No.8)  
Initial value: 0 or 0.0  
Setting range: -200~200 unit  
Used for sensor input error compensation.  
Controlling is performed with corrected value for bias setting.  
Upper row displays load current detected by CT.  
(If the output is OFF, it shows  
)
1-9  
PV filter time set screen (screen No.9)  
Initial value: 0 second  
Setting range: 0~100 seconds  
Used for the case of large input change and noise overlapping to reduce  
the effect.  
NOTE: The heater break alarm can be added if the instrument has alarm option and the  
control output is the contact type or the SSR drive voltage type.  
Heater break alarm  
• Set the alarm level at approx. 85% of the normal load current. In case of large current  
variation, set larger value.  
If multiple heaters are connected in parallel, set a larger value to output alarm for single heater  
break.  
1-10  
Key lock mode set screen (screen No.10)  
Initial value: OFF  
Setting range: OFF, 1, 2, 3  
No data change is effective on the display screen locked.  
Nevertheless, the direct call screen and the keylock mode setting screen  
are not locked by setting any lock No.  
• If “  
” is selected, no alarm output is obtained. Selecting “  
” during alarm output,  
the alarm output is canceled.  
• For case when heater break function is not applicable to direct current load, phase controlling  
current and three phase heater.  
• Connecting current transformer (CT)  
One of the load line wires passes through the hole of the custom CT.  
Wire from the secondary side terminal of CT to the CT input terminal of the instrument.  
Lock Nos. and Ranges to be locked are as follows:  
Lock No.  
OFF  
1
Range of Screens to Be Locked  
Release of lock  
To CT input terminal of  
controller (no polarity)  
NOTE: Two types of the heater break  
CT of 30A and 50A are available, the  
type selected upon ordering is shipped  
with the product as an accessory. Note  
the maximum current to be set is 50.0A  
Other screens than basic, control output,  
AT action control and communication mode screens  
for both types. CT is not provided when  
0~500A is designated.  
Heater (load) wire  
All except basic screen  
All screens  
2
3
- 6 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mode 2 Screen Group (Function selecting screen)  
2-0  
2
3
4
1
=
=
6
8
5
7
1-11  
Proportional cycle setting screen (screen No.11)  
Initial value: Contact output 30 seconds  
SSR drive voltage 3 seconds  
ENT  
Use  
key to move select digit and data  
registration, the selectable digit is indicated by  
flashing point.  
V and I  
output  
Setting range: 1~120 seconds  
Time of proportional setting cycle is set.  
The screen does not display voltage or current output.  
Refer to Item 4-6 (4).  
NOTE: If it is on auto tuning execution or key lock is set on lock No.1,  
2 or 3, no selection can be performed even if the digit point is  
flashing.  
1-12  
Lower limit output limiter setting screen (screen No.12)  
Initial value: 0%  
Setting range: 0~99%  
5
7
6
3
Digits and are not shown in case of no option. Digits of  
,
8
and are not displayed.  
A lower limit value of control output is set.  
Refer to Item 4-6 (5) for output limiter.  
2
1
4
:
Measuring range code select digit  
Initial value: Multi 05, Voltage (V) 81, Current 95 fixed.  
Selecting two digits from “4-5. Measuring range code table”.  
1-13  
Higher limit output limiter setting screen (screen No.13)  
Initial value: 100%  
Setting range: 1~100%  
:
Control output characteristic select digit  
Initial value:  
: RA (heating characteristics)  
: DA (cooling characteristics)  
Refer to Item 6-3.  
A higher limit value of control output is set.  
1-14  
5
7
:
:
Alarm type select digit  
Initial value:  
Select from “4-2. Alarm type code table”.  
Soft start time setting screen (screen No.14)  
Initial value: OFF  
Setting range: OFF, 1~100%  
Time for soft start, during which output is changed gradually, is set.  
Refer to Item 4-6 (6).  
No  
communi-  
cation  
Heater break alarm action mode select digit  
Initial value:  
Select from  
: Lock mode and  
Refer to Item 5-3 (3).  
1-15  
: REAL mode.  
Communication mode selecting screen (screen No.15)  
Initial value: Locl (local)  
Setting range: Locl, Remt  
2-1  
Communication is allowed in the mode displayed on the bottom.  
Input scaling screen  
Initial value:  
Lower limit value (top row)  
1-16  
0.0  
Communication address setting screen (screen No.16)  
Initial value: 0  
Setting range: 0~99  
Higher limit value (bottom row) 100.0  
Position of decimal point  
Setting range:  
0.0  
In case a plurality of apparatus are connected for communication, the  
machine No. is set in a range from 0 to 99.  
Lower limit value -1999~9899 units  
Higher limit value -1899~9999 units  
Span = Higher limit value - Lower limit value  
= 100~5000 counts  
Position of decimal point:  
No decimal point, 0.0, 0.00 and 0.000  
1-17  
1-18  
Communication data format selection screen (screen No.17)  
Initial: 7b_E  
Setting range: 7b_E, 8b_n  
Select data format of communication from 7b_E (data bit length : 7bits,  
parity: even, stop bit : 1)or 8b_n (data bit length: 8bits, parity: none,  
stop bit : 1)  
Scaling is done for linear input (mV, V or mA).  
The screen is only for monitoring and no setting is possible in the case  
of sensor input.  
Refer to Item 4-3 (6) for details.  
Communication rate selecting screen (screen No.18)  
Initial value: 1200 bps  
4-5. Measuring range code table  
Measuring  
Selectable range: 1200, 2400, 4800 and 9600 bps  
A rate for data transmission to the host is selected.  
Measuring  
Range  
RS-422A  
1-19  
Input type  
Code  
Code  
Range  
01  
02  
03  
04  
05  
06  
07  
08  
09  
10  
11  
31  
32  
33  
34  
35  
36  
37  
38  
71  
72  
73  
81  
82  
83  
~
~
0
0
*1B  
1800°C 12  
1700°C 13  
1700°C 14  
400°C  
15  
1200°C 16  
700°C  
600°C  
200.0°C  
1300°C  
200.0°C  
600°C  
600°C 39  
100.0°C 40  
50.0°C 41  
200.0°C 42  
600°C 43  
3300°F  
3100°F  
3100°F  
750°F  
2200°F  
1300°F  
1100°F  
400°F  
Delay setting screen Screen No.19  
Initial value: 80  
Setting range: 0~255  
Delay time for starting communication from receiving communication  
command is set.  
Delay time = 0.1 × set value msec.  
The screen is displayed for RS-485.  
R
S
K
K
E
J
0 ~  
0 ~  
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
0
-100  
0
-150  
0
0
0
-300  
0
-300  
0
0
0
17  
18  
19  
20  
21  
22  
0
-199.9  
0
-199.9  
0
T
N
U
L
2300°F  
400°F  
*2  
*2  
Note: For details of communication, refer to the instructions on  
1100°F  
-1100°F  
200.0°F  
120.0°F  
400°F  
communication in Item 8.  
-200 ~  
-300 ~  
~
~
~
~
~
~
-100.0  
-50.0  
0.0  
-200  
-100.0  
-50.0  
0.0  
-150.0  
-50.0  
0
Pt 100  
~
~
~
~
-300  
-150.0  
-50.0  
0
-1100°F  
200.0°F  
120.0°F  
400°F  
100.0°C 44  
50.0°C 45  
200.0°C  
JPt 100  
~
~
~
~
46  
~
~
~
~
~
~
0
10  
0
10  
50  
100  
1
Initial value: 0.0~100.0  
Conditions of scaling  
Scaling setting range:  
-1999~9999,  
Span: 100~5000 counts  
Position of decimal point:  
No decimal point, the  
first, second and third  
decimal places  
Thermocouple  
B, R, S, K, E, J, T, N: JIS/ANSI/IEC  
R. T. D.  
Pt100 : Present JIS/IEC  
JPt100 : Former JIS  
*1 Thermocouple B: Accuracy not  
guaranteed for temperatures  
below 400 °C (750 °F).  
NOTE:  
Screen flame on Item 4-4 is as follows:  
Screens always shown  
during key operation.  
0
Voltage  
V
0
5
0
10  
Screens shown during case with  
option or selected option.  
Current  
mA  
~
4
20  
95  
*2 Thermocouple U, L: DIN43710  
In case measuring range is modified, set values, alarm action point and other  
related values are all intialized.  
NOTE: In case types of Alarms are changed, values are initialized.  
Screens shown or skipped depending on the type of  
output or the setting status of control action mode.  
- 7 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4-6. Supplementary explanation of screens  
(6) 1-14 Soft Start Time Setting Screen  
• Soft start is the function selected to raise control output  
gradually in the beginning of control. It is effective in  
preventing excessive current from flowing into a heater or  
similar apparatus.  
(1) 0-1 Control Output Screen  
• During manual control an output value is set on this  
screen. In automatic control, it is only for monitoring.  
• For switching automatic control to manual, press the  
key on the control output screen.  
• The MAN monitor LED flashes during manual control and  
goes out when control is changed to auto.  
• This screen is only for monitoring in the stop mode, when  
AT is ON, or keylock is set at 2 or 3.  
• Manual control output is released if the stop mode is  
selected or the type of input or the measuring range is  
changed during manual control.  
• For changing the manual output value, the  
keys are used. It is not necessary to press the  
• During manual control, the setting range of control output  
is between 0 and 100%. In case an output limiter has been  
set, that value serves as the higher/lower limit of the  
setting range.  
• In ON/OFF action (P=0), manual control output should be  
at 0% or 100% (For V and I output, lower limit output  
limiter or higher limit output limiter).  
MAN  
• Soft start functions in the following cases:  
Upon applying power in the auto mode  
When control stop (STBY) is changed to control  
execution (EXEC)  
When scale-over is restored to the normal state (in auto  
mode)  
The above are on condition that soft start time and  
proportional band are not set at OFF.  
• In the following cases, the soft start function is released.  
Soft start time has elapsed without problem.  
Auto is changed to stop or manual mode during the  
execution of soft start.  
Soft start time or proportional band is changed to OFF  
during the execution of soft start.  
The measurement range code is changed during the  
execution of soft start.  
Control output characteristic is changed during the  
execution of soft start.  
Scale-over of a measured value occurs during the  
execution of soft start.  
and  
ENT  
key.  
• When auto is changed to manual, the action becomes  
balanceless and bumpless. If the measured value (PV) is  
out of the proportional band, it does not attain balanceless  
and bumpless action.  
• If power is turned off during manual control output and is  
turned on again, the condition is stored in the memory.  
Control output falls to a level below the output value of  
soft start during the execution of soft start.  
• Auto tuning is unable to be carried out during the  
execution of soft start.  
Note: Moving to another screen while maintaining the manual  
mode is possible. In this case, it should be noted that  
control output is made manually. The apparatus is in the  
manual mode when the MAN monitor LED is flashing.  
5. Operation  
5-1. Setting of set value (SV)  
(1) Press the  
or  
key to set set value. Keep pressing it to  
(2) 0-2 Control Execution/Stop Screen  
flash the point of the least digit of set value and increase (or  
decrease) value.  
(2) After confirming the value to coincide the set value, press  
• Use the  
and  
keys to select control execution  
(EXEC) or stop (STBY). Then register it by means of the  
ENT  
key.  
to register the data.  
ENT  
• Upon selecting stop, the STBY monitor LED turns on and  
the control output display turns to 0%.  
• Upon selecting execution, the mode changes to automatic  
control; it is not possible to go directly from the stop to the  
manual mode. When control is being executed, the STBY  
monitor LED remains unlit.  
(3) After registration of the data, the point of the least digit goes  
off.  
Example: Setting set value to 500 °C.  
0-0 basic screen  
ENT  
key  
key  
key  
• Even at stop, the alarm works.  
• When AT is ON or 1, 2 or 3 of keylock has been selected,  
no change is allowed.  
one by one  
continuing  
point goes off to  
indicate registration  
point flashing  
point flashing  
5-2. AT (Auto tuning)  
(3) 1-6 Manual Reset Value Setting Screen  
• In the PID operation, an offset is corrected automatically  
by I, i.e., integral calculation. When I is set at OFF, this  
correction is not made and output is manually increased or  
decreased for correction. This is called manual reset (MR).  
(4) 1-11 Proportional Cycle Setting Screen  
• In the case of contact output or SSR drive voltage output,  
time in which output is ON + time in which it is OFF in  
the proportional band, that is, proportional cycle time is  
set.  
(1) Execution of AT action  
• By pressing the  
or  
key on AT action control  
and the  
screen, display on lower row turns into  
point of the least digit starts flashing, then the LED for AT  
monitoring turns on to indicate AT standby. Press  
key to start AT action with point going off and LED for  
AT monitoring flashing.  
ENT  
• LED for AT  
monitoring  
turns on  
• LED for AT  
monitoring starts  
0-1  
0-0 basic screen  
flashing  
AT action control screen  
AT  
ENT  
key  
key  
(5) 1-12, 1-13 Lower Limit and Higher Limit Output Limiters  
Setting Screens  
key  
action  
Starting  
point goes off to  
• The output limiters function effectively to maintain the  
lowest temperature, to suppress control overshoot by  
limiting control output to minimum and maximum values  
set.  
• In the output limiters, priority is given to the lower limit  
value. Therefore, when the lower limit is set at a value  
higher than the higher limit value, the higher limit value is  
forced to be the lower limit value + 1%. Therefore, the  
higher limit value cannot be set to be less than the lower  
limit value + 1%.  
point flashing  
indicate registration  
• When AT is carried out, ON/OFF action of output is  
repeated several times, with the set value as the border  
line, to make PID values stored in the memory and  
terminates. At the same time, control is started by using  
stored PID constants.  
The AT monitor LED goes out and the display on the AT  
action control screen changes to  
- 8 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(2) Abort of AT  
To abort the AT action, by showing the AT action control  
Example 2:  
In case of setting the alarm action point at 600 °C for higher  
limit absolute value alarm.  
screen, press the  
or  
key to select  
and press  
ENT  
key to abort AT and LED for AT monitoring also goes  
The set point is action point.  
off.  
0-2 Higher limit deviation value alarm set screen  
ENT  
key  
key  
key  
Note: When the AT action is aborted, each value for PID is not  
changed.  
continuing  
one by one  
point goes off to  
indicate registration  
point flashing  
point flashing  
(3) AT unable for following conditions.  
• When the control stop mode is on (The AT screen is not  
displayed.)  
(2) Lower limit alarm setting  
• The lower limit alarm set screen is shown in case where  
alarm option is added and the lower limit alarm of the  
alarm type select digit on the function selecting screen of  
the mode 2 group screen group is selected.  
• During manual output control (The AT screen is not  
displayed.)  
• The proportional band is  
setting (ON/OFF action).  
(The AT screen is not displayed.)  
• Lock No.2 or 3 is selected on the key lock set screen.  
• PV (measured) value is over the scale.  
• Lower limit deviation value alarm is output for measured  
value to be less than set value + (alarm set value).  
• For lower limit deviation value alarm, if set value + (alarm  
set value) is less than the lower limit of the measuring  
range, the action point is lower limit of the measuring  
range.  
During the execution of soft start  
(4) AT is automatically canceled in the following condition  
during AT execution.  
• Duration equal to or longer than 2 hours passed in the  
output level of 0% or 100%.  
• Lower limit absolute value alarm outputs alarm signal for  
the measured value is less than the alarm set value.  
• Power shutdown.  
• With the  
or  
key, value at which the alarm signal  
ENT  
• PV (measured) value is over the scale during AT  
execution.  
should be output is selected and registered with  
(3) Heater break alarm setting  
key.  
(5) The items enable to be set are as follows:  
• Level setting of the higher limit alarm.  
• Level setting of the lower limit alarm or heater break  
alarm.  
• The heater break alarm value setting screen is displayed  
when the apparatus is equipped with the optional heater  
break alarm function and heater break alarm is selected in  
the alarm type selection digit of the function selecting  
screen of the mode 2 screen group. The top row shows for  
monitoring purposes the value of the presently flowing  
current detected by CT and the bottom row shows the set  
value of the alarm current.  
• When OFF is set as the heater break alarm value, the  
heater break alarm does not function.  
• By setting OFF during heater break alarm signal output,  
heater break alarm output is terminated.  
• For set value other than OFF, heater break alarm signal is  
output if the current that flows in case where control  
output (contact or SSR drive voltage) is ON, is less than  
set value.  
• If LOCK mode is selected at heater break alarm action  
mode select digit on the function selecting screen of the  
mode 2 screen group and the break alarm signal is output,  
alarm signal is only terminated by changing the break  
alarm value into OFF or shutting down power.  
If REAL mode is selected and heater current is less than  
current value being set, break alarm signal is generated. If  
heater current exceeds the current threshold (0.1A), output  
of break alarm is terminated.  
• Screen number setting and key lock setting on the direct  
call screen of mode 1 screen group.  
(6) Relationship between AT and set value bias is as follows;  
• When SB terminal is shorted before AT execution, AT  
executes in the condition with SV+set value bias.  
• When SB terminal is opened during AT execution  
mentioned in the above, AT executes with SV+set value  
bias condition, then controlled with SV condition after  
completing AT execution.  
• When SB terminal is opened, AT executes with SV  
condition.  
• When SB terminal is shorted during AT execution  
mentioned in the above, AT executes with SV condition,  
then controlled with SV+set value bias condition after  
completing AT execution.  
5-3. Setting of alarm  
(1) Higher limit alarm setting  
• The higher limit alarm set screen is shown in case where  
alarm option is added and the higher limit alarm of the  
alarm type select digit on the function selecting screen of  
the mode 2 screen group is selected.  
• Higher limit deviation value alarm is output for measured  
value to be greater than set value + alarm set value.  
• For higher limit deviation value alarm, if set value + alarm  
set value exceeds the higher limit of the measuring range,  
the action point is the higher limit of the measuring range.  
• Higher limit absolute value alarm outputs alarm signal for  
the measured value exceeds the alarm set value.  
• Set the heater break alarm current value by means of the of  
ENT  
the  
or  
key and register it by using the  
key.  
6. Supplement  
6-1. Auto return function  
In case there is no key operation for three minutes on each of the  
screens except the control output screen and the heater break  
alarm value setting screen, the basic screen of the mode 0 screen  
group is displayed (auto return).  
• With the  
or  
key, value at which the alarm signal  
ENT  
should be output is selected and registered with  
Example 1:  
key.  
In case of setting the alarm action point at 600 °C for higher  
limit deviation value alarm. Set value is 500 °C.  
As 500 °C + X °C + = 600 °C, X=600-500 = 100 °C should  
be set.  
6-2. PID (Screen No.2, 4 and 5 of mode 1 screen group)  
PID values are automatically set by performing auto tuning,  
modification may be required for object to be controlled.  
If auto tuning is not performed, PID value should be set.  
0-2 Higher limit deviation value alarm set screen  
ENT  
key  
key  
key  
continuing  
one by one  
point goes off to  
indicate registration  
point flashing  
point flashing  
- 9 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(1) P (proportional action)  
7. Instructions on Communication  
Control output rate (%) is set for measuring range.  
Control output value changes in proportion with measured  
value (PV) and set value (SV).  
For wide proportional band, change of control output is small  
relative to deviation. The narrower the proportional band is,  
the larger the output variation is and the more intense  
proportional action is. Too narrow proportional band causes  
ON-OFF like action with oscillation.  
7-1. General  
Section 7 deals with communication interface, which is an  
optional function, and communication procedure.  
For the CN150 series, two types of communication  
interface, RS-422A and RS-485 are available. Each enables a  
personal computer or the like to set and read various data by the  
use of signals which conform with EIA standards.  
(2) I (integral time)  
A function that compensates the offset created by  
proportional action. Effect of compensation is weaker for  
longer integral time and is intensified by shortening time.  
Too short integral time causes integrating hunting and may  
result in wavy operation.  
RS-422A and RS-485 are communication standards established  
by the Electric Industries Association (EIA), which are meant for  
electrical or mechanical matters, the so-called hardware, but not  
for the software portion of the data transmission procedure.  
Accordingly, communication even with an apparatus having the  
same interface cannot be made unconditionally. It requires a  
thorough understanding of specifications and procedures.  
(3) D (derivative time)  
Improves stability of control by reducing overshooting of  
integration from expected change of the control output.  
Effect of compensation is weaker for shorter derivative time  
and is intensified for longer time. Too long derivative time  
may result in oscillating operation.  
The use of RS-422A or RS-485 allows a plurality of apparatuses  
to be connected in a parallel configuration. It is also possible to  
use a line converter for conversion of RS-232C to/from RS-422A  
and RS-232C to/from RS-485.  
6-3. Control output characteristics ( digit of function  
selecting screen of mode 2 screen group)  
7-2. How to connect CN150 Series with host computer  
7-2-1. Control signals  
Control output characteristics determines the control output  
direction according to the measured value (PV) relative to the set  
value (SV).  
Since the apparatus is provided with input/output transmitting and  
receiving data lines and an earthing line for signals but not with  
any other signal line, control signals should be processed by the  
host side.  
(1)  
(RA characteristics)  
Control output increases for lower measured value relative to  
set value, it is used for heating on temperature control.  
The method of processing differs from system to system and  
connection details should meet requirements of the host  
computer. Examples of connection are shown in the following.  
(2)  
(DA characteristics)  
Control output decreases for lower measured value relative to  
set value, it is used for cooling on temperature control.  
7-2-2. Connection of RS-422A  
6-4. Error message  
(1) The logical levels of input and output of this apparatus are  
basically as follows:  
(1) Defect of measuring input  
In case of thermocouple break, R.T.D. A break  
and PV being approx. 10% greater than higher  
limit of measuring range.  
Mark state  
**– <**+ (Example: SD- < SD+)  
(including the state in which communication is not carried  
out)  
Space state  
**– >**+ (Example: SD- > SD+)  
In case of PV being approx. 10% less than the  
lower limit of measuring range with inverted  
polarity of input wiring.  
However, since the impedance of SD+ and SD- of this  
apparatus is high until just before transmission, the above  
levels are output just before commencing transmission.  
(2) Example of Connection of RS-422A  
Cold junction (CJ) defect to higher side for  
thermocouple input.  
Host computer  
Cold junction (CJ) defect to lower side for  
thermocouple input.  
SR73A and 74A Controllers 1  
FG (Earthing for protection)  
terminal No.  
Shielding wire  
2
SD+  
SD -  
RD+  
RD -  
SG  
SD+  
SD -  
RD+  
RD-  
SG  
Transmitted data  
3
4
5
1
Break of B or B and multiple break of A, B, B  
upon R.T.D. input  
Received data  
Earthing for signal  
(2) Defect of Heater Break Alarm CT Input  
The CT input value exceeds 55A (550A for 0~5V  
DC input).  
SR73A and 74A Controllers 2  
terminal No.  
+ 2  
SD  
SD  
RD  
RD  
SG  
The CT input value falls to -5A (-50A for 0~5V  
DC input) or lower.  
Transmitted data  
- 3  
+ 4  
- 5  
1
Received data  
Earthing for signal  
Terminal resistance (510)  
Note: Message of heater break alarm is only displayed on  
heater break alarm set screen.  
Note: Some line converters between RS-232C and RS-422A  
may have the following indication for terminal  
(connector) output. If that is the case, logical levels  
should be checked before connection.  
is shown when output is OFF. It is not  
defective.  
Note: Contact to us or our representative in case of any defect  
regarding this product.  
- 10 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example: Mark state  
Space state  
T × D+ > T × D-  
T × D+ < T × D-  
7-3-1. Communication mode selecting screen (  
(1) Local Mode (  
)
)
Line converter  
SR73A and 74A Controllers  
terminal No.  
The COM lamp on the front panel goes out to allow the  
setting to be changed by the use of the front keys. In  
communication, only the change from local to remote and the  
read commands are valid.  
FG (Earthing for protection)  
Shielding wire  
2
3
4
5
1
T x D+  
T x D-  
R x D+  
R x D-  
SG  
SD+  
SD-  
RD+  
RD-  
SG  
(2) Remote Mode (  
)
The COM lamp on the front panel turns on and the  
commands for read and write through communication  
become valid.  
Front key operation works only to change from remote to  
local.  
7-2-3. Connection of RS-485  
(1) The logical levels of input and output of this apparatus are  
basically as follows:  
Mark state  
-Terminal < +Terminal  
(including the state in which communication is not carried  
out)  
7-3-2. Communication address (  
) setting screen  
Space state  
-Terminal > +Terminal  
RS-422A and RS-485 allow connection of a plurality of  
apparatuses but in fact, communication is carried out between two  
apparatuses. Therefore, the address of each apparatus is  
designated by a number between 00 and 99 so as to enable the  
designated apparatus to respond.  
However, since the impedance of +terminal and -terminal of  
this apparatus is high until just before transmission, the above  
levels are output just before commencing transmission.  
(2) Example of Connection of RS-485  
Host computer  
FG (Earthing for protection)  
CN150 Controllers 1  
Shielding wire  
7-3-3. Communication data format (  
) selecting screen  
terminal No.  
(+)  
(-)  
SG  
(+)  
(-)  
SG  
2
3
1
Select data format of communication from 7b_E (data bit length  
: 7 bits, parity : even, stop bit : 1) or 8b_n (data bit length : 8bits,  
parity : none, stop bit : 1)  
CN150 Controllers 2  
terminal No.  
7-3-4. Communication rate (  
) selecting screen  
2
3
1
(+)  
(-)  
SG  
A rate of transmission from the controller to the host is selected  
from among 1200, 2400, 4800 and 9600 bps.  
Terminal resistance (510)  
7-3-5. Delay (  
) setting screen  
7-2-4. Terminal resistance  
In the case of RS-485, a minimum delay time for transmission  
from receiving a communication command is set. Delay time is a  
set value (0~255) × 0.1 msec. Nevertheless, actual delay time  
includes time for processing the command added to the above  
delay time.  
As CN150 Series are not provided with terminal resistance,  
connect a 510resistance to only the last (the furthest from the  
host) station.  
Note: If terminal resistance is connected to two or more,  
correct action is not guaranteed.  
7-4. Communication protocol  
7-4-1. Communication procedure  
7-2-5. Control of 3-state output  
Communication is carried out for each block and the  
communication right alternates between the controller and the  
host from block to block.  
(1) Since RS-422A and RS-485 employ the multi-drop system,  
in order to prevent signals from colliding, transmission  
output should be controlled to maintain high impedance  
while communication is not being made or signals are being  
received.  
Host computer  
Controller (CN150 Series)  
Transmission  
(Reading)  
Transmitting command block  
(2) It should be controlled so that high impedance turns to the  
normal state of output immediately before starting  
transmission and high impedance is restored immediately  
when transmission ends. Because 3-state control is delayed  
by about 3 msec. maximum from the transmission of the end  
bit of the end character, a delay time of about 4 msec. should  
be provided in case transmission is started immediately.  
Response  
Returning response block  
(Reading)  
Transmission  
(Reading)  
Transmitting command block  
Response  
Returning response block  
(Reading)  
7-4-2. Explanation of block  
7-3. Setting of communication parameters  
(1) The data format in one block is shown below:  
There are four communication-related parameters to be set as  
shown below. They are set by means of front keys except for  
changing the communication mode from remote to local.  
Lower  
Lower  
position  
Higher  
position  
Higher  
position  
:
CR  
@
Text  
position  
1
2
3
4
6
[
[
[
[
[
] Communication mode  
] Communication address  
] Communication data format  
] Communication rate  
] Delay  
5
: Start character• • • • • @(40H) Shows the start of a  
block.  
- 11 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(2) Write Data  
: Address (Machine No.)  
• • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
Two digits  
The text format of write data  
contains a command and write data  
value.  
Command  
Write data  
Two-digit address data (00~99) set in the controller is  
divided to the higher position (tens) and the lower  
position (units) and each is shown by an ASCII code.  
: Text •••••••••••••••••••••••••••••••••••A group of a command and data,  
in the format of each command.  
Contents of  
Write Data  
Contents of  
Write Data  
Command  
Command  
Attribute  
Attribute  
PV bias value  
E1  
SV value  
*2 Numerical  
value  
Numerical  
value  
F1  
Control output value  
Stop status  
PV filter value  
Numerical  
value  
E2  
E3  
E4  
E5  
E6  
E7  
E8  
E9  
EA  
EB  
EC  
ED  
EE  
EF  
Numerical  
value  
F2  
F3  
F4  
F5  
F6  
F7  
: End character.• • • • • • • • • (3AH) Shows the end of the  
block.  
1 byte  
1 byte  
1 byte  
Proportional cycle  
time  
Numerical  
value  
: BCC check  
• • • • • • • • • • • •  
BCC check data is shown in two  
digits.  
Manual status  
AT status  
Lower limit output  
limiter value  
Numerical  
value  
Higher limit output  
limiter value  
Numerical  
value  
A value obtained by exclusive OR operation of data  
following @(data in the higher position of the address)  
through : is converted to two ASCII characters and  
shown by two digits in the higher and lower positions.  
Higher limit alarm  
(AH) value  
Numerical  
value  
Soft start time value  
Numerical  
value  
Lower limit alarm  
(AL) value  
Numerical  
value  
Communication  
mode  
1 byte  
Heater break alarm  
(HB) value  
Numerical  
value  
(Example) BCC operation of DI read command (Address: 01)  
Set value bias (SB)  
value  
Numerical  
value  
@
0
1
D
1
:
BCC  
CR  
Proportional band  
(P) value  
Numerical  
value  
(40H)  
(30H)  
(31H)  
(44H)  
(31H)  
(3AH)  
(34H)(45H)  
(0DH)  
Integral time (I) value  
Numerical  
value  
4
E
Derivative time (D)  
value  
Numerical  
value  
••BCC=(34H), (45H)  
30H + 31H + 44H + 31H + 3AH=4EH  
In the above, + =EX-OR (exclusive OR)  
Target value function  
(SF) value  
Numerical  
value  
Hysteresis (DF) value  
Numerical  
value  
: Terminator  
• • • • • • • • • • • •  
CR(0DH) Shows the termination  
of the data of the block.  
Manual reset (MR)  
value  
Numerical  
value  
(2) In this protocol, address data is inserted in the block in each  
transmission or response and so no data link needs to be  
established or aborted.  
*2 SV value is target set value.  
(3) Response Data  
(3) The apparatus which has the address matches the one in the  
command block, interprets the command, data, etc., and  
returns a response block by inserting the same address into it.  
Apparatuses which the addresses do not match the one in the  
block wait for the next block without activating.  
(4) In the case of receiving block data and the terminator CR is  
not completed in about 1 second after receiving the start  
character, it designates a time-out and automatically waits for  
the next command, that is, the start character @ is being  
waited for.  
Response data has different formats depending on whether  
read data has been received or write data has been received.  
Response data to read data received  
Command  
Data 1  
,
Data 2  
,
,
Data n  
Appropriate read data contents of commands shown in  
the table of the read data text format are sent back.  
Response data to write data received  
Command  
Write data  
The same data as the received write data is sent back.  
7-5. Text  
7-5-2. Data format  
7-5-1. Text format  
The data format is divided to 3 categories; numerical data, 1 byte  
data and special data.  
The text format is classified into read data, write data and  
response data.  
(1) Numerical Data (-2999~9999)  
(1) Read Data  
The length of numerical data in the text is fixed to six  
characters including a code and a decimal point. A code (+  
or -) is attached to the head of the numerical data. In the case  
where the numerical value including a code is less than six  
characters, 0 is inserted between the code and the figure or  
figures to make the value six characters. When a code is  
excluded, each of the 5 characters is a figure or a decimal  
point.  
The text format of read data contains only of a  
command of two characters.  
Command  
Command  
D1  
Contents of Read Data  
PV value, Execution SV value*1, Control output value,  
Stop (STBY) status, Manual (MAN) status, AH status,  
AL/HB status, AT status, SB status.  
Set value of higher limit alarm (AH), Set value of lower  
limit alarm (AL).  
D2  
Load current value, Set value of heater break alarm (HB).  
D3  
D4  
+
Numerical value  
-
Set value of set value bias (SB).  
Numerical data (30H~39H) or a decimal point (2EH)  
Code + (2BH) or – (2DH)  
Proportional band (P) value, Integral time (I), Derivative  
time (D) value, Set value of target value function (SF).  
D5  
D6  
D7  
D8  
D9  
Set value of hysteresis (DF).  
Examples of numerical data  
Set value of manual reset (MR).  
Set value of PV bias, Set value of PV filter.  
Set value of proportional cycle time.  
Set value of lower limit output limiter, Set value of  
higher limit output limiter.  
1
+
2
0
3
0
4
0
5
0
6
1
1
2
0
3
0
4
0
5
0
6
1
1
0.01  
-1  
-0.01  
DA  
+
+
+
+
0
0
1
0
0
1
2
0
.
2
.
0
3
3
0
1
4
4
0
0
1
1
0
0
2
2
.
.
3
.
0
.
1
4
4
1
DB  
DC  
Set value of soft start time.  
Communication mode, Delay time.  
1234  
12.34  
-123.4  
-12.34  
-0.001  
*1  
The execution SV value is a total of the SV value and the  
value bias.  
3
0
0
0
0 or OFF  
- 12 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(2) One-Byte Data  
Error Types  
One-byte data in the text has a fixed length of one character  
which is either 0 or 1. Seven items are covered, namely, stop  
status, manual status, AT status, AH status, AL/HB status  
and communication mode.  
Description  
Error No.  
Error Type  
BCC error  
05  
06  
08  
09  
11  
12  
Arithmetic value is not in accord with BCC.  
Command other than prescribed one was received.  
Command error  
Data format error  
Data error  
Stop (STBY), Manual (MAN), AT (ON), AH (ON),  
AL/HB (ON), SB (ON), Communication (when the  
remote mode is on).  
The format is different from prescribed one.  
Value is out of prescribed data range in the case of  
write command.  
Write command was received when write command  
was invalid.  
Write mode error  
Option error  
1
Command of unequipped option was received.  
Execution (EXEC), Auto (AUTO), AT (OFF), AH  
(OFF), AL/HB (OFF), SB (OFF), Communication  
(when the local mode is on).  
7-5-4. Non-response process  
0
When an error is found in the block upon receiving data  
(3) Special Data  
Special data is data sent in response to numerical data which  
transmitted from the host, the next correct data block is waited for  
without transmission of response data. Therefore, the host has to  
retransmit the command block in any of the following cases:  
are outside of the ordinary range. Their patterns are shown  
in the following.  
The start character was not @ (40H).  
The communication No. did not match.  
The end character was not CR (0DH).  
A hardware error such as a framing error, overrun or a  
parity error occurred.  
Numerical data is +10000~+10999.  
0
0
0
0
0
0
0
9
9
9
10000  
U
10999  
U
Numerical data exceeds the indicated range.  
more than  
11000  
less than  
-3000  
H
0
0
0
L
0
0
0
0
0
0
D
E
D
E
7-5-5. Restrictions by commands, etc.  
Numerical data is over the scale.  
(1) Restrictions by Read Command  
0
0
0
0
0
The (+) side  
H
0
The (-) side  
L
0
Upon receiving the D1 read command, the status of  
unequipped options (AH, AL/HB, SB) become 0 (30H).  
(2) Restrictions by Write Command  
CT temperature exceeded the higher limit value or fell  
below the lower limit value in the case of thermocouple  
input.  
ER09  
The higher  
limit side  
The lower  
limit side  
H
0
0
0
L
0
0
0
C
J
C
J
In the case of P=OFF and Y and P output, write data of  
E2 (write command of manual output value) is either of  
the following two. Otherwise, ER09 is sent back.  
Wire breaking detected in the case of R.T.D. input  
0
0
0
0
B
0
+
+
0
0
0
0
0
0
0
1
0
0
0%  
100%  
CT input value exceeded the higher limit value or fell  
below the lower limit value.  
In the case of P=OFF and V and I output, a lower limit  
output limiter value or a higher limit output limiter  
value is to be set.  
The higher  
limit side  
The lower  
limit side  
H
0
0
0
L
0
0
0
H
B
H
B
ER11  
Control output either turned on or turned off while CT  
input measurement was ongoing.  
If a write command is invalid due to the local mode, a set  
value of keylock, AT or some other conditions, and that  
command is received, ER11 should be sent back. The  
following cases also require ER11 to be sent back.  
Data is undeterminable due to a set value of alarm code,  
P=OFF, or some other reasons.  
• Data in the case where the alarm code is 0 and D2  
(AH, AL) or D3 (CT, HB) command has been  
received.  
Condition  
Received Write Command  
E2 (Manual control output value)  
E4 (Manual status)  
Stop mode (STBY)  
• Data in the case where the alarm code is 1~4 and D3  
(CT, HB) command has been received.  
• AL data in the case where the alarm code is 5~8 and  
D2 (AH, AL) command has been received.  
• I, D, SF or MR data in the case where P=OFF and D5  
(P, I, D, SF, MR) command has been received.  
E5 (AT status)  
Auto mode (AUTO)  
Manual mode (MAN)  
E2 (Manual control output value)  
E5 (AT status)  
E6 (Set value of AH)  
E7 (Set value of AL)  
E8 (Set value of HB)  
E8 (Set value of HB)  
E7 (Set value of AL)  
EE (DF: Hysteresis)  
Alarm code = 0  
Alarm code = 1~4  
Alarm code = 5~8  
P=OFF  
0
0
0
0
+
0
7-5-3. Communication error  
E5 (AT status)  
When an error is found in the block after receiving data from the  
host, an error message is sent back. The format of error messages  
and the types of errors are described in the following.  
EB (I: Integral time)  
EC (D: Derivative time)  
ED (SF: Target value function)  
EF (MR: Manual reset)  
EF (MR: Manual reset)  
ED (SF: Target value function)  
P=OFF  
Error Message Format  
I=OFF  
I=OFF  
Address No.  
Error No.  
BCC  
:
@
40H  
CR  
E
45H  
R
52H  
Space  
20H  
3AH  
Higher Lower  
position position  
Higher Lower 0DH  
position position  
- 13 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(3) Restrictions by Read/Write Commands Depending on  
Equipped Optional Functions  
(8) D8  
Received  
data  
D8  
D8  
ER12  
Transmitted  
data  
PV bias  
PV filter  
,
When a command which becomes invalid because an  
optional function is not equipped, ER12 should be sent  
back. (Read commands are included.)  
(9) D9  
Received  
data  
D9  
D9  
Proportional cycle  
time  
Condition  
Received Command  
Transmitted  
data  
D2 (AH/AL) read command  
(10) DA  
E6 (Set value of AH) write command  
E7 (Set value of AL) write command  
D3 (CT/HB) read command  
Without alarm option  
Without HB option  
Without SB option  
Received  
data  
DA  
DA  
Transmitted  
data  
Lower limit output  
limiter value  
Higher limit output  
limiter value  
E8 (Set value of HB) write command  
D4 (Set value of SB) read command  
E9 (Set value of SB) write command  
,
(11) DB  
Received  
data  
DB  
DB  
(4) Others  
Transmitted  
data  
When P (proportional band)=OFF is prepared to be set, data  
is as follows:  
Soft start time  
(12) DC  
+
0
0
0
.
0
0
0
0
.
0
OFF  
or  
Received  
data  
DC  
DC  
Transmitted  
data  
7-6. A list of transmitted/received data  
C_MD  
Delay time  
,
The text portions of data in read commands and write commands  
are listed below.  
7-6-2. Write command  
In write commands, received data and transmitted data are  
identical.  
Block Data Format  
Text Data  
Address No.  
:
BCC  
position position 0DH  
@
40H  
CR  
(1) E1  
3AH  
Higher Lower  
Higher Lower  
position position  
SV value  
E
1
(2) E2  
7-6-1. Read command  
Control output value (OUT)  
STBY : 1 (31H)  
E
2
3
(1) D1  
(3) E3  
Received  
D1  
data  
STBY  
E
EXEC : 0 (30H)  
Output  
value  
Transmitted  
data  
PV  
value  
SV  
value  
STBY MAN  
AH  
AL  
AT  
SB  
D1  
,
,
,
,
,
,
,
,
(4) E4  
0 (30H) or 1 (31H)  
MAN : 1 (31H)  
AUTO : 0 (30H)  
MAN  
AT  
E
4
(2) D2  
(5) E5  
Received  
data  
D2  
D2  
AT-ON : 1 (31H)  
AT-OFF : 0 (30H)  
E
5
6
7
Transmitted  
data  
Set value of AH  
Set value of AL  
,
(6) E6  
(3) D3  
Set value of AH  
Set value of AL  
E
Received  
data  
D3  
D3  
(7) E7  
Transmitted  
data  
CT current value  
Set value of HB  
,
E
(4) D4  
(8) E8  
Received  
data  
D4  
D4  
Set value of HB  
Set value of SB  
E
8
9
Transmitted  
data  
Set value of SB  
(9) E9  
E
(5) D5  
(10) EA  
Received  
data  
D5  
D5  
P (proportional band) value  
I (integral time) value  
E
A
B
Transmitted  
data  
SF value  
P value  
I value  
D value  
,
,
,
(11) EB  
(6) D6  
E
Received  
data  
D6  
D6  
(12) EC  
Transmitted  
data  
Hysteresis  
D (derivative time) value  
E
(13) ED  
E
C
D
(7) D7  
Received  
data  
D7  
D7  
SF (target value function) value  
Transmitted  
data  
Set value of MR  
- 14 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(14) EE  
measuring range in case of T and U  
input, though.  
JIS Pt100 / JPt100 3-wire type  
Approx. 0.25mA  
DF (hysteresis) value  
E
E
• R.T.D:  
Amperage:  
Lead wire tolerable  
resistance:  
(15) EF  
MR (manual reset) value  
E
F
5max. / wire (The 3 lead wires  
should have same resistance.)  
0~10, 10~50, 0~100mV DC or 0~1,  
1~5, 0~10V DC  
500kmin.  
4~20mA DC  
(16) F1  
• Voltage :  
PV bias value  
PV filter value  
F
1
2
Input impedance:  
• Current:  
(17) F2  
Receiving impedance: 250Ω  
• Input scaling function: Scaling possible for voltage (mV, V)  
or current (mA) input.  
F
(18) F3  
Scaling range:  
Span:  
Position of decimal  
point:  
• Sampling cycle:  
• PV bias range:  
• PV filter:  
-1999~9999 counts.  
100~5000 counts  
Proportional cycle time  
Lower limit output limiter value  
Higher limit output limiter value  
F
3
(19) F4  
None, 0.0, 0.00, 0.000  
0.5 sec.  
± 200 unit  
F
4
5
0~100 sec. (0=without filter)  
(20) F5  
F
Control  
(21) F6  
• Control mode:  
• Proportional band (P): Off, 0.1~999.9% FS (Off setting: On-  
Off action)  
• Integral time (I):  
• Derivative time (D):  
• Manual reset (MR):  
• Output limiter:  
Auto tuning PID/ ON-OFF control  
Soft start time  
F
6
7
(22) F7  
Off, 1~6000 sec. (Off setting: P-PD  
action)  
Off, 1~3600 sec. (Off setting: P-PI  
action)  
-50.0~50.0% (Valid when P OFF  
and I=OFF)  
Lower limit limiter 0~99%, Higher  
limit limiter 1~100% (Priority given to  
lower limit limiter)  
Off, 1~100 sec.  
1~999 units  
1~120 sec. (Factory-set value: 30 sec.  
for contact output and 3 sec. for SSR  
drive voltage output.)  
C MD: Communication mode  
C_MD  
E
Remote: 1 (31H)  
Local:  
0 (30H)  
8. Specifications  
Display  
• Digital display:  
Measured value (PV)/7-segment green  
LED 4 digits  
Set value (SV) /7-segment orange  
LED 4 digits  
7-segment LED for PV and SV  
Green LEDs for 5 points of output  
(OUT), auto tuning (AT), operating  
mode (STBY), remote (COM) and  
manual output (MAN). Red LEDs for  
2 points of alarm (AH, AL/HB).  
±(0.3% FS+1 digit) excluding cold  
junction temperature compensation  
accuracy in the case of the  
• Soft start of output:  
• ON/OFF hysteresis:  
• Proportional cycle:  
• Parameter display:  
• Action display:  
• Control output  
characteristics:  
RA / DA selectable (set to RA when  
shipped)  
• Set value function (SF) : Off (Off = 0.00) and 0.01~1.00  
• Display accuracy:  
Control Output  
• Contact output:  
• Current output :  
240V AC 2.5A / resistive load: 1.5A /  
inductive load  
4~20mA DC / load resistance: 600Ω  
max.  
thermocouple input.  
±5% FS for temperatures below 400°C  
(750 °F) of thermocouple B.  
• Display accuracy range: 23±5 °C (18~28 °C)  
• Display resolution: Depends on measuring range (0.001,  
0.01, 0.1, 1)  
• Measured display range: -10~110% (-210~680 °C for -200~  
600 °C of R.T.D. input)  
SSR drive voltage  
output :  
15±3V DC (with load resistance at  
1.5k) /load current: 20mA maximum  
0~10V DC /  
• Voltage output :  
load current: 2mA maximum  
Setting  
Manual Control  
• Setting:  
• Setting range:  
By 5 front key switches  
Same as measuring range.  
• Output setting range:  
0~100% (setting resolution: 1%) but  
within range set by higher/lower  
output limiters.  
Input  
• Auto/manual switching: Balanceless bumpless. Within  
proportional band range.  
• Type of input :  
Multiple input of Thermocouple,  
R.T.D., Voltage (mV), or Voltage (V),  
or Current 4~20mA DC by code  
selection  
B, R, S, K, E, J, T, N, {U, L (DIN  
43710)} Refer to Measuring range  
code table.  
100max.  
500kmin.  
Standard feature (up scale)  
Communication (Optional)  
• Signal level:  
EIA standards, conforming with RS-  
422A and RS-485.  
• Thermocouple:  
• Communication system: RS-422A 4-wire half duplex multi-  
drop system. RS-485 2-wire half  
External resistance:  
Input impedance:  
Burnout:  
Cold junction  
temperature  
duplex multi-drop (bus) system.  
• Synchronous system:  
• Data format:  
Start-stop synchronous system.  
Select data format of communication  
from 7b_E (data bit length: 7bits,  
parity: even, stop bit: 1) or 8b_n  
(data bit length: 8bits, parity: none,  
stop bit: 1)  
compensation accuracy: ±2°C (°F) (5~45 °C)  
±5 °C to the negative side of  
- 15 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
• Communication address:Machine numbers are set in a range  
from 0 to 99.  
• Current setting range: Off, 0.1~50.0A (Alarm action stops  
when Off is set.) or, Off, 1~500A  
(when 0~5 V DC for CT input is  
selected)  
• Communication rate:  
1200, 2400, 4800 and 9600 bps.  
• Communication delay: To be set in a range from 0 to 255  
(Setting possible only in the case of  
RS-485.)  
• Setting resolution:  
• Amperage display:  
• Display accuracy:  
0.1A or 1A  
0.0~55.0A or 0~550A  
5% FS (when sine wave is 50 Hz) or  
1% FS (in case of 0~5 V DC input)  
• Communication  
distance:  
RS-422A maximum 1200m  
(depending on conditions)  
RS-485 maximum 500m  
(depending on conditions)  
• Minimum time for  
action confirmation:  
• Alarm holding:  
On time: 500 msec.  
Selectable between Lock (holding)  
and Real (no holding)  
2 sec.  
• Transmission procedure: No procedure.  
• Communication code: Conforming with ASCII codes.  
• Sampling cycle:  
• Control signal:  
• Error detection:  
Not used.  
Vertical parity (even parity) checking.  
BCC (block check character)  
checking.  
Set value Bias (option)  
• Setting range:  
• Setting resolution:  
• Action input:  
-1999~2000 unit  
Same as display resolution  
Non-voltage contact (bias in action  
when SB terminal is closed)  
• Connectable number  
of apparatuses:  
Possible to connect 100 units  
maximum (including the host,  
depending on conditions)  
Others  
Alarm Output (Optimal)  
• Data storage:  
• Isolation:  
By non-volatile memory (EEPROM)  
Input, control output, communication  
and alarm output circuits are isolated  
from each other.  
Input, set value bias and CT input  
circuits are not isolated from each  
other.  
• Number of alarm points: 2 (AH and AL/HB, both for normal  
open and common)  
• Alarm Type:  
Selectable from the following 9  
combinations.  
(5 through 8 are selectable only when  
apparatus has heater break alarm  
function.)  
• Ambient conditions for use  
Temperature/humidity  
ranges:  
0. Not assigned  
1. Higher limit deviation value + lower limit deviation value  
without inhibit action  
2. Higher limit absolute value + lower limit absolute value  
without inhibit action  
3. Higher limit deviation value + lower limit deviation value  
with inhibit action  
4. Higher limit absolute value + lower limit absolute value with  
inhibit action  
5. Higher limit deviation value without inhibit action + heater  
break  
6. Higher limit absolute value without inhibit action + heater  
break  
7. Higher limit deviation value with inhibit action + heater  
break  
-10~50 °C and below 90%RH (on the  
condition that there is no dew  
condensation)  
2000 m above sea level or lower  
II  
2
Height:  
Installation category:  
Degree of pollution:  
• Supply voltage/  
frequency:  
• Power consumption:  
• Insulation resistance:  
100-260V AC±10% (50 / 60 Hz)  
12 VA max.  
Between input / output terminal and  
power supply terminal:  
500V DC 20 Mminimum  
Between input / output terminal and  
protective conductor terminal:  
500V DC 20 Mminimum  
1 min. at 2300V AC between input /  
output terminal and power supply  
terminal  
1 min. at 1500V AC between power  
supply terminal and protective  
conductor terminal  
8. Higher limit absolute value with inhibit action + heater break  
• Dielectric strength:  
• Alarm setting range:  
Higher limit and lower limit absolute  
value alarms: Within full scale of  
measuring range  
Higher limit: 0~2000 unit  
Lower limit: -1999~0 unit  
On-Off action  
Deviation value:  
• Alarm action:  
• Alarm action hysteresis: Fixed to 0.2% of the measuring range  
• Alarm output / rating: Contact 1a (common) / 240V AC 1.5A  
(resistive load)  
• Protective structure:  
• Material :  
Only front panel has simple dust-proof  
and drip-proof structure  
PPO resin molding (equivalent to  
UL94V-1)  
• External dimensions  
CN154, CN155:  
H96 × W96 × D110  
(panel depth: 100)mm  
H96 × W48 × D110  
(panel depth: 100)mm  
Push-in panel (one-touch mount)  
1.0~3.5 mm  
Heater Break Alarm (option)  
This function can be added if the instrument has an alarm option  
and the control output is the contact type or the SSR drive voltage  
type.  
CN158, CN159:  
• Mounting:  
• Alarm action:  
Heater amperage detected by  
externally attached CT. (except 0~5V  
DC input)  
Alarm output On upon detection of  
heater break while control output is  
On.  
• Panel thickness:  
• Panel cutout  
CN154, CN155:  
CN158, CN159:  
• Weight  
H92 × W92mm  
H92 × W45mm  
CN154, CN155:  
CN158, CN159:  
Approx. 400 g  
Approx. 300 g  
The contents of this manual are subject to change without notice.  
- 16 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Freezer F1471SF User Manual
Milwaukee Cordless Drill 2415 20 User Manual
MotoSAT Network Card G74 User Manual
National Instruments Computer Hardware PXI 8150 User Manual
NEC Microwave Oven N230S User Manual
Nilfisk ALTO Vacuum Cleaner S12cc User Manual
Panasonic Automobile Parts HR E User Manual
Panasonic Computer Drive CF VDR302U User Manual
Panasonic Network Card 2SC3130 User Manual
Parrot Car Stereo System MKI9000 User Manual