| M165912I.3   ITEM NUMBER: 165912   SERIAL NUMBER: _____________   Owner’s Manual   Instructions for Installation/Set-up, Operation, Servicing, & Storage   Portable, Outdoor Use-Only, Gasoline Generator   2,400 Watt Continuous (2,700 Watt Surge) Capacity   Can be used to power individual appliances plugged directly into the generator’s outlets, or as a back-up   connection to a building’s power supply (via a professionally installed UL-approved transfer switch.   WARNING   READ and UNDERSTAND this manual completely before using the generator! Failure to properly set up,   operate, and maintain this generator could result in serious injury or death from carbon monoxide poisoning,   electric shock, fire/explosion, or burns. In particular, be aware of the following hazards:   CO Poisoning   Generators give off carbon monoxide, a poisonous gas that can kill you. You CANNOT smell it, see it, or taste it.    ONLY run generator OUTDOORS and at least 20 feet from the home, away from windows, vents and air intakes, to allow   proper ventilation. If you start to feel sick, dizzy, or weak while using the generator, shut off the engine and get to fresh air   RIGHT AWAY. NEVER run generator inside any enclosed or semi-enclosed spaces, including homes, basements,   garages, sheds, boxes, RVs, boats or pick-up truck beds. These spaces can trap poisonous gases, EVEN if you run a fan or   open windows.    Install carbon monoxide alarms inside nearby structures/buildings (battery-operated, or plug-in with battery backup).   Electric shock / Electrocution    High voltage electricity from generator can kill. DO NOT operate in wet locations. Be sure generator is properly grounded.   Use only UL-listed, outdoor-rated grounded extension cords of proper size.    NEVER plug the generator directly into a wall outlet. ANY connection to a building’s electrical system MUST ISOLATE   THE GENERATOR FROM UTILITY POWER via a UL-approved transfer switch installed by a licensed electrician.   Otherwise, back feed from the generator into the power grid could kill utility workers.   Fire / Explosion    DO NOT overload generator (per rated capacity), and OPERATE ONLY in an area with adequate cooling ventilation so   engine does not overheat. Exhaust can be extremely hot. Keep muffler at least 7’ from all combustible objects.    All fuels are flammable. Never fuel a running or hot engine. Never pump fuel directly into generator at gas station – use   approved container to transfer fuel. Ensure there are no fuel leaks, and keep sources of sparks and flames away.    ALWAYS keep a fire extinguisher rated “ABC” nearby.   STOP!   CHOOSE THE RIGHT GENERATOR FOR YOUR NEEDS. See the “Power load Planning & Management” section of   this manual to determine your power load requirements and then compare to the generator’s rated capacity.   INSPECT COMPONENTS: Closely inspect to make sure no components are missing or damaged. See the “Unpacking &   Delivery Inspection” section for instructions on whom to contact to report missing or damaged parts.   ARRANGE FOR PROFESSIONAL INSTALLATION of a transfer switch if you will be connecting the generator to   your building’s electrical system. See the “Installation/Initial Set-Up” section for more information about this   requirement.   Any Questions, Comments, Problems, or Parts Orders   Call NorthStar Product Support 1-800-270-0810   Download from Www.Somanuals.com. All Manuals Search And Download.   Table of Contents   Hazard Signal Word Definitions .................................................................................................2   About Your Generator .................................................................................................................4   Specifications .................................................................................................................................6   Safety Label Locations..................................................................................................................7   Machine Component Identification.............................................................................................8   Power Load Planning & Management........................................................................................10   Installation / Initial Set-Up:   1. Unpacking & Delivery Inspection..........................................................................................12   2. Planning the Power Load........................................................................................................12   3. Set-up as a PORTABLE or BUILDING BACK-UP Power Source ......................................13   4. Selecting a Suitable Site .........................................................................................................16   5. Grounding the Generator........................................................................................................18   Operation:   1. General Safety Rules for Operation .......................................................................................19   2. Preparing for Operation..........................................................................................................22   3. Starting the Engine .................................................................................................................25   4. Checking Generator Output....................................................................................................26   5. Connecting Loads...................................................................................................................27   6. Stopping the Engine ...............................................................................................................27   7. Storage & Exercise.................................................................................................................28   Maintenance & Repair..................................................................................................................30   Troubleshooting.............................................................................................................................32   Summary of Important Safety Information for Operation.......................................................33   Generator Exploded View ............................................................................................................37   Wiring Diagram.............................................................................................................................39   Limited Warranty .........................................................................................................................41   3 Download from Www.Somanuals.com. All Manuals Search And Download.   About Your Generator   Thank you for purchasing your NorthStar portable generator!   About Your Generator   This engine-driven, portable generator is designed to provide up to 2700 Watts of   electrical power (2400 watts continuous, 2700 watts surge).   It can supply power:   1. As a portable power source. You can plug appliances directly into the generator’s   electrical outlets.   2. As a back-up, standby power source for a building. A licensed electrician can connect   the generator to your building’s electrical system via the installation of an UL-approved   transfer switch. (See the “Installation & Initial Set-up” section of this manual to learn   more about specific requirements and precautions relating to wiring the generator to your   building’s electrical system.)   You must select a generator adequately sized for your power needs. You need to   determine the power needs of all the appliances/tools you wish to power at the same time and   choose a generator rated to provide at least that power level. See the “Power Load Planning &   Management” section of this manual to determine your specific power load requirements and   then compare them to this generator’s rated capacity. You must not overload the generator.   Overloading will cause damage to the generator and attached electrical devices, and may also   result in fire.   Be sure to read about site selection and grounding requirements for running this   generator. More detailed information can be found in the “Installation & Initial Set-up, Steps   5 & 6 of this manual.   This generator is too heavy for one person to lift without mechanical assistance. An   optional wheel kit is available from NorthStar and is recommended if you will be moving the   generator unassisted. Other optional accessories available from NorthStar include a vinyl   cover for storage, UL-approved transfer switches, and extension cords.   Contact NorthStar Product Support at 1-800-270-0810 with questions about optional   accessories or to order.   Read this Manual   WARNING   Improper use or maintenance of this generator can result in serious injury or death from   carbon monoxide poisoning, electric shock/electrocution, fire/explosion, or burns.   Read this manual completely before using the generator and follow all instructions and   safety rules.   You must follow all instructions and safety precautions presented throughout this manual. A   summary of important safety information can be found at the end of the manual. Keep this   manual for reference and review.   4 Download from Www.Somanuals.com. All Manuals Search And Download.   About Your Generator (cont’d)   Proper preparation, operation, and maintenance will result in operator safety, as well as best   performance and long life of the generator. For detailed engine operation and maintenance   information, always refer to the engine Owner’s Manual furnished with the generator.   NorthStar is constantly improving its products. The specifications outlined herein are subject   to change without prior notice or obligation. The purchaser and/or user shall assume liability   for any modification and/or alterations of this equipment from original design and   manufacture.   Before using, the user shall determine the suitability of this product for its intended use and   assumes liability therein.   Contact NorthStar Product Support at 1-800-270-0810 for any questions about the   appropriate use of this generator.   Warranty Registration   Please fill out and submit the warranty registration card so that we have your contact   information for any future product literature or replacement parts you may need.   ATTENTION:   All Rental Companies and Private Owners who loan this   equipment to others!   All persons to whom you rent/loan this generator must have access to and read this manual.   Keep this owner’s manual with the generator at all times and advise all persons who will   operate the machine to read it. You must also provide personal instruction on how to safely   operate the generator and remain available to answer any questions a renter/borrower might   have.   5 Download from Www.Somanuals.com. All Manuals Search And Download.   Specifications   SPECIFICATIONS   Item Number   Maximum Output   Continuous Output   Generator Type   Voltage   #165912   2700 Watts (W)   2400 Watts (W)   Brushless   120 Volt (V)   Phase   Single phase   Frequency   Power Factor   Engine   Engine Speed   Fuel Type   Fuel Capacity   Oil Capacity   Starting Method   120 V Receptacles   56.5 - 63.3 Hertz (Hz)   1.0 p.f.   5 Hp Honda GC160 AVXA   3390 - 3798 RPM   Unleaded gasoline   2.12 quarts (2.0 L)   0.55 US quarts (0.52 L)   Recoil   2, 20 Amp (A) duplex   (NEMA 5-20R)   Circuit Breaker   Dimensions   Length   20 Amp (A) thermal, push to reset style   23.00” (58.4 cm)   15.75” (40.0 cm)   15.75” (40.0 cm)   80 lb (36 kg)   Width   Height   Dry Weight   Gross Weight   88 lb (40 kg)   6 Download from Www.Somanuals.com. All Manuals Search And Download.   Safety Label Locations   Fig02663   WARNING   BURN HAZARD   Do not touch   hot muffler.   ©2005 NT+E 1-800-270-0810   PN 39260   Always make sure safety labels are in place and in good condition. If a safety label   is missing or not legible, order new labels or unsafe operation could result.   To order replacement safety labels, call NorthStar Product Support at 1-800-270-0810.   On-Product Warning Labels   Part numbers   Description   Burn Warning   Warning   39260   779428   7 Download from Www.Somanuals.com. All Manuals Search And Download.   Machine Component Identification – 165912I.3   Figure 1 (Ref. 1-7)   Ref. Description   Ref. Description   1 2 3 4 5 6 Circuit Breaker   7 8 9 10   11   Choke Lever   Ignition Switch Lever   Recoil   Gas Tank   Air Cleaner   120V 20A Duplex Receptacle   Generator Head   Oil Drain Plug   Vibration Isolation Mount   Muffler   Figure 2 (Ref. 7-11)   8 Download from Www.Somanuals.com. All Manuals Search And Download.   Machine Component Identification – 165912I.3 (cont’d)   REFERENCE GUIDE   Reference 1 – Circuit Breaker   This portable single phase generator has 1, 20   amp (A) push to reset circuit breaker to protect   against electrical overloads.   Reference 2 – (2) 120V 20A   Duplex Receptacles   The generator has a control panel with two 120V   duplex (two receptacles in a common housing)   receptacles. The duplex is a 120 volt (V) 20 amp   (A) straight blade receptacle, National Electrical   Manufacturer’s Association (NEMA) number 5-   20R.   This receptacle accepts NEMA plug   numbers 5-15P and 5-20P. Each receptacle on   the duplex is capable of drawing 20A.   Reference 3 – Generator Head The electricity producing part of the generator.   Reference 4 – Oil Drain Plug   Refer to your Honda engine manual for oil   change recommendations.   Reference 5 – Vibration   Isolation Mount   The engine and generator mounted on rubber   cylinders that absorb most of the engine   vibration. This feature eliminates the tendency   of the machine to “walk” which is common in   engine powered equipment.   Reference 6 – Muffler   Honda’s standard muffler with an installed spark   arrestor.   Reference 7 – Choke Lever   Used during cold starts. Refer to the Honda   engine manual for usage.   Reference 8 – Ignition Switch   Lever   The red engine stop lever is located on the   engine. Always locate this lever and be familiar   with its location before operating the generator.   Grasp firmly when pull starting the engine.   Always allow room for gasoline expansion by   not filling the gas tank completely full.   Refer to your Honda engine manual for air   cleaner care.   Reference 9 – Recoil   Reference 10 – Gas Tank   Reference 11 – Air Cleaner   9 Download from Www.Somanuals.com. All Manuals Search And Download.   Power Load Planning & Management   WARNING   NEVER exceed the rated wattage capacity of your generator.   OVERLOADING may cause SERIOUS DAMAGE to the generator and   attached electrical devices, and may result in fire.   Your generator MUST BE SIZED PROPERLY to provide both the running and starting (surge)   wattage of the devices you will be powering. Before using your generator, determine the running   and starting wattage requirements of all the electrical devices you will be powering simultaneously.   The sum of the running and starting wattages of the devices being powered must not exceed the   continuous output rating of your generator. (The continuous output rating of your generator is listed   in the “Specifications” section of this manual.) Note that:    Devices without electric motors such as light bulbs, radios, and televisions have the same   running and starting wattage.    Devices with electric motors such as refrigerators, compressors, and hand tools typically   require a starting wattage that is 3 to 5 times greater than the running wattage.   The running and starting wattage requirements are often listed on a device’s nameplate. If wattage   is not given on the device’s nameplate, the wattage may be calculated by multiplying the nameplate   voltage by nameplate amperage, Watts = Volts X Amps.   Example conversion to watts:   120 Volts X 5 Amps = 600 Watts   If only the running voltage is given on the nameplate for a device with an electric motor, the starting   wattage can be approximated to be three to five times the running wattage.   Estimates for the running wattage requirements for common devices are listed in Table 1 below.   Guidance for starting wattages is provided in the table’s footnotes.   Table 1   Running   Watts   1700 (a,b) Jet pump   Running   Watts   800 (a)   1200   100   Device   Device   Air conditioner (12.000 BTU)   Battery charger (20 Amp)   Belt sander (3”)   Chain saw   500   1000   1200   Lawn mower   Light bulb (100 Watt)   Microwave oven   700   Circular saw (6½”)   Coffee maker   2000 (a,b) Milk cooler   1800 (a,b) Oil burner on furnace   1100 (a)   300   Compressor (1 HP)   Compressor (3/4 HP)   Compressor (1/2 HP)   Curling iron   Dishwasher   Edge trimmer   1400 (a,b) Oil-fired space heater (140,000 Btu)   1800 (a) Oil-fired space heater (85,000 Btu)   1400 (a) Oil-fired space heater (30,000 Btu)   400   225   150   4500   600 (a)   150   700   1200   500   Oven   Paint sprayer, Airless (1/3 HP)   Paint sprayer, Airless (handheld)   Radio   Electric nail gun   1200   200   10   Download from Www.Somanuals.com. All Manuals Search And Download.   Power Load Planning & Management (cont’d)   Running   Running   Watts   600 (b)   200   Device   Watts   1500   1250   Device   Refrigerator   Slow cooker   Electric range (1 element)   Electric skillet   Furnace fan (1/3 HP)   Freezer   1200 (a) Submersible pump (1-1/2 HP)   2800 (a)   2000 (a)   1500 (a)   600 (a)   2000 (a)   500   1000   250   70   3000   800 (b)   1200   1100   875   Submersible pump (1 HP)   Submersible pump (1/2 HP)   Sump pump   Hair dryer   Hand drill (1”)   Hand drill (1/2”)   Hand drill (3/8”)   Hand drill (1/4”)   Hedge trimmer   Home computer   Impact wrench   Table saw   500   Television   250   Toaster   450   150   Vacuum cleaner   VCR   500   Water Heater   Weed trimmer   500   (a) Hard-starting motors require 3-5 times the rated running watts   (b) For extremely hard to start loads such as air conditioners and air compressors, consult the   equipment dealer to determine maximum wattage   To calculate the running and starting wattage requirements for the devices you will be   powering, follow these steps:   1. Make a list of all electrical devices you will be powering at the same time with the generator.   2. List the greater of the running or starting wattage next to each device as obtained from the   devices’ nameplate or Table 1. If only the running wattage for a device with an electric   motor is known, the starting wattage can be estimated to be at least 3 times the running   wattage.   3. Add the wattages for all devices on your list. This total must be lower than the continuous   output rating of your generator.   Example:   Greater of Starting/Running   Device to be Powered   Light Bulb   Wattage   75 W   Refrigerator – 18 Cu. Ft.   Microwave   1600 W   700 W   Window AC   Sump pump (1/3 hp)   Total   1800 W   2100 W   6275W   In this example, the generator must have a continuous output of at least 6275 W in order to   power all of the devices simultaneously.   STAGGERING LOADS   You can increase the number of devices your generator can power by staggering the load on the   generator. For example, you could alternately power your refrigerator and air conditioner for   limited periods of time -- powering only one of the devices at a time and never powering both at the   same time.   11   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation / Initial Set-Up   There are a number of important steps required to set up your generator for initial use. These   steps are:   Steps for Installation / Initial Set-Up   1. Unpacking & delivery inspection.   2. Planning the power load to stay within the generator’s rated   capacity.   3. Setting up generator for the type of power generation you need:   a. portable power source, or   b. connected to a building as a back-up power source.   4. Selecting a site for using the generator.   5. Grounding.   Each of these steps is discussed in detail below:   1. Unpacking & Delivery Inspection   You should inspect the generator immediately after you receive delivery.   See the “Machine Component Identification” section of this manual for a   diagram of the generator and its components.    If you have missing or damaged components, contact Product Support at 1-800-270-0810.   2. Planning the Power Load   Plan your power load so that you do not exceed the generator’s rated capacity.   See the “Power Load Planning & Management” section of this manual to review how to plan and   manage power loads for the generator.   12   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation / Initial Set-Up (cont’d)   3. Set-up either as a BUILDING BACK-UP or PORTABLE Power Source   This generator is designed to provide up to 2700W of electrical power. It can supply electricity in   two ways:   1. As a back-up, standby power source for a building. For this application, you must arrange   for a licensed electrician to connect the generator to your building’s electrical system via the   installation of an UL-approved transfer switch. The transfer switch must be installed in   accordance with building electrical code and guidelines supplied by your power company.   2. As a portable power source. You can plug appliances or tools directly into the generator’s   electrical outlets.   Specific requirements for each are given below.   Note: Regardless of whether you use your generator as a back-up power source connected to a   building or as a portable power source, you must not overload the generator. Overloading   may cause serious damage to the generator and attached electrical devices.   Contact a licensed electrician to install a UL-approved transfer switch if   Using as a   you want to use your generator as a back-up power source for a building.   Back-up Power   Source for a   Building   What does a transfer switch do? It:   a) Safely connects the generator to your building’s electrical system by   isolating your generator from your utility company’s power lines,   AND   b) Connects your generator to a critical subset of your building’s circuits   that are needed for emergency power needs.   If your generator will be connected to your building’s electrical system, it   MUST ALWAYS be isolated from the utility power grid with a UL-approved   transfer switch installed by a licensed electrician in compliance with all   applicable building and electrical codes, and in accordance with guidelines   supplied by your power company.   DANGER:   A transfer switch must be installed in order to isolate your   generator from the utility power grid. If your generator is NOT   properly isolated from the utility system, serious hazards will   arise:    When your generator is running, it’s output will back feed into   the utility power line and transformer that are normally used to   provide you with power. The transformer will step up the   current to the normal line voltage. An unsuspecting utility line   worker working on what he thinks is a deactivated line could   be electrocuted.    If your generator is connected (running or not) when utility   power is restored, your generator will be destroyed. It could   also explode or cause fire.   13   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation / Initial Set-Up (cont’d)   In addition to isolating your generator from the utility system, the transfer   switch connects your generator to a limited set of circuits in your building   that have been chosen as critical to operate during a power outage.   The generator cannot power your entire home -- you must work with the   installing electrician to determine which devices/appliances you wish to   power during an outage. The electrician can help you determine which   circuits and devices can be powered simultaneously without overloading the   generator.   (See the previous section of this manual entitled “Power Load Planning &   Management” for more information on load application and selection.)   When using the generator as a portable power source, you can plug   electric devices and appliances directly into the generator’s electrical   outlets.   Using as a   Portable Power   Source   There are two identical electrical outlets on the generator. Each is a 120 Volt,   20 Amp, duplex straight-blade receptacle (NEMA 5-20R duplex receptacle   compatible with NEMA 5-20P or 5-15P mating plugs).   (2) NEMA   5-20R duplex   (See more technical detail about these receptacles and their associated   circuit breakers in the “Machine Component Identification” section of this   manual.)    Make sure you plug each electrical device/appliance into the correct   generator outlet based on the device’s plug configuration and   voltage/amperage rating. Never exceed the amperage rating of an outlet.   14   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation / Initial Set-Up (cont’d)    Extension cords may be used to power devices that are located at a   distance from the generator. However, use only UL-listed, outdoor-rated,   grounded extension cords of the proper size. Use Table 2 below to choose   an adequately sized extension cord according to the amperage of the   device being used and the length of the cord.   Table 2   Current/Power   Maximum Extension Cord Length   Amps at Load #10 Ga. #12 Ga. #14 Ga. #16 Ga.   240V   10   20   30   40   (watts)   2400   4800   7200   9600   Cord   250'   125'   60'   30'   15'   Cord   150'   75'   35'   15'   * Cord   100'   50'   25'   10'   * Cord   75'   25'   10'   * 50   12000   * WARNING:   Use of under sized extension cords can cause electric shock, fire, or   damage to connected devices.    All extension and appliance cords must be in good condition and not worn, bare,   frayed, or otherwise damaged.   WARNING:   Use of damaged electric cords can cause electric shock or fire.   Note: If an extension cord becomes hot to the touch, it is overloaded or   damaged and must be replaced.   Northern Tool is NOT responsible for damage or injury resulting from   customer use of inadequate extension cords.   15   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation / Initial Set-Up (cont’d)   4. Select a Suitable Site   Before using the generator, you must select a suitable OUTDOOR location for installation and   operation. This location should meet all of the criteria listed below.   WARNING:   You must choose a suitable site for operating your generator to avoid equipment damage   and/or injury and possible death from carbon monoxide poisoning, electric shock, or fire.   Choose a site that meets all of the criteria specified.   Dry, level surface The generator should be positioned on a dry, firm, level surface.   Ensure that the generator sits level and will not slide or shift during operation.   If applicable, block the generator’s wheels to prevent sliding and shifting.   Outdoors only –   dangerous carbon   monoxide exhaust   WARNING: Carbon monoxide poisoning hazard   The exhaust from your generator contains carbon monoxide (CO), a   poisonous gas that can kill. You cannot smell it, see it, or taste it.   Carbon monoxide exhaust is given off whether you are using gasoline,   natural gas, or propane as the fuel source to power the generator.   Follow the directions below for choosing a location to operate your   generator in order to avoid carbon monoxide poisoning.   The location you choose to operate the generator must be OUTDOORS   and at least 20 feet from the home, away from windows, vents and air   intakes, to allow proper ventilation. If you start to feel sick, dizzy, or   weak while using the generator, shut off the engine and get to fresh air   RIGHT AWAY:    Never run the generator inside any closed or semi-enclosed spaces (even if   outdoors), including homes, garages, basements, sheds, or boxes. These   spaces can trap poisonous gases, even if you run a fan or open windows.    Never place the generator immediately adjacent to a building or other   structure – allow at least 20 feet clearance.    Place the generator so that the exhaust fumes will not be directed towards   people or building air intakes.    Ensure that working, battery-operated or battery back-up carbon monoxide   alarms are used in any dwelling/structure that is in close proximity to the   running generator.    Note that this generator is NOT designed or approved for use in vehicles   or marine applications. Never run the generator inside RVs or other   vehicles, on boats, or on pick-up truck beds.   WARNING:   Never attempt to attach ductwork to the muffler system to allow for   installation inside an enclosure. This could cause hot air deflection,   heat build-up, and increased exhaust back-pressure, resulting in   possible exhaust leakage or damage to the generator.   16   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation / Initial Set-Up (cont’d)   Adequate cooling The generator needs adequate, unobstructed flow of air to allow for   ventilation   proper cooling of engine and generator head.   WARNING:   Heat build-up from inadequate ventilation can result in fire, posing a   serious risk to nearby persons and structures.    Situate so there is adequate clearance around generator to allow for   cooling airflow so that heat does not build up.    Never place the generator immediately adjacent to large objects or   structures – allow at least a 7’ clearance.    Do not run the generator in close proximity to other heat-generating   equipment, such as another generator. The combined heat that is   generated may raise air temperature in the immediate area and there will   not be adequate cooling ventilation.    Do not allow debris to accumulate and block airflow.    Do not operate with a tarp, blanket, or cover surrounding the generator.   No wet conditions Choose a location where the generator will NOT be exposed to rain,   snow, or direct sunlight. Exposure to water can cause electric shock.   You may operate the generator under an outdoor, canopy-like structure of   heat-resistant material that is open on all sides. Make sure that all parts of   canopy are at least 7’ from exhaust, and allow for adequate clearance above   generator so that heat does not build up.   Hot exhaust   clearance   The exhaust gas from your generator is extremely hot and can cause   combustible materials to catch on fire.    Make sure your generator’s exhaust system is at least 7 feet from all   combustible materials and structures.    Equip the engine with a spark arrestor if the generator will be used near   any ignitable forest, brush, or grassy land. (See the “Specifications”   section of this manual to determine if your generator is already equipped.)   Make sure you comply with applicable local, state, and federal codes.    Keep a fire extinguisher rated “ABC” nearby. Keep it properly charged   and be familiar with its use.   Away from   dust/dirt   Hearing   Do not use the generator in extremely dusty or dirty conditions.   Excessive dust and dirt can cause premature failure of the machine.   Generators can produce noise levels of up to 95 dB in close proximity,   which can be dangerous to human hearing with prolonged exposure.   protection   Hearing protection may be required for persons working within 15-20 feet of   the running generator for an extended period of time.   WARNING:   Never attempt to attach ductwork to the muffler system to lower noise   levels. This could cause hot air deflection, heat build-up, and   increased exhaust back-pressure, resulting in possible exhaust leakage   or damage to the generator.   17   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation / Initial Set-Up (cont’d)   5. Grounding the generator   Always ensure the generator is properly grounded to prevent electrical shock.   You must always ground the generator by the following method when using the generator as a   portable electrical source:   1) Drive a ¾” or 1” copper pipe or rod into the ground close to the generator. The pipe/rod   must penetrate moist earth – the depth required will be dictated by local soil conditions.   Consult with an electrician.   2) Connect an approved ground clamp to the pipe.   3) Run a 10 gauge wire from the clamp to the generator grounding post located on the rear of   the generator head.   4) Do not connect the generator grounding post to a water pipe or a ground used by a radio   Grounding   Post   10 Ga.   Wire   Copper   Pipe/Rod   Ground   If a licensed electrician installs the generator with a connection to your building’s electrical circuit   for use as a back-up power system, grounding may alternatively be completed through the   building’s grounding system. Ask your electrician. If the generator is not grounded through your   building’s electrical system, follow the procedure above.   WARNING:   Operating the generator when it is not properly grounded can result in electrical shock.   18   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation   Once you have set up your generator for use, it is time to start your generator. The following   are the procedures necessary for safe, successful operation of your generator.   Operation Procedures   1. General Safety Rules for Operation   2. Preparing for Operation   3. Starting the Engine   4. Checking Generator Output   5. Connecting Electrical Loads (Portable Power Generation)   6. Stopping   7. Storage & Exercise of Generator   Each of these procedures is discussed in detail below:   1. General safety rules for operation   Before starting the generator, review the following general safety rules for operation:   WARNING:   Failure to follow safety rules may result in serious injury or death to the operator or   bystanders.    Know proper use/how to stop. Be thoroughly familiar with proper use of the equipment and all   generator controls, output receptacles, and connections. Know how to stop the generator quickly if   needed (see “Operation, Step 6 - Stopping the Engine”).    Instruct operators. The generator owner must instruct all operators in safe generator set-up and   operation. Only trained adults should set up and operate the generator – Do not let children operate.    Intended use. Carefully read about and understand the intended use of this generator. Do not use for   other purposes, as unforeseen hazards or equipment damage may result.    Under the influence. Never operate, or let anyone else operate, the generator while under the influence   of alcohol, drugs, or medication.    Safety equipment / controls. Do not operate the generator unless all safety covers, guards, and barriers   are in place and in good working order, and all controls are properly adjusted for safe operation.    Damaged. Do not operate the generator with damaged, missing, or broken parts.    Modifications. Do not modify the generator in any way. Modifications can create serious safety hazards   and will also void the warranty.    Engine speed. Never attempt to modify the engine speed setting. The engine speed is preset at 3600 RPM   for safe and optimal performance of the generator. If speed needs adjusting, it must be done by factory-   authorized personnel.    External fuel sources. Never attempt to connect external gasoline/diesel sources in order to increase   engine run time. Larger tank at pressure or higher elevation will cause gasoline to leak from carburetor   during operation. Fire or explosion could result.   19   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation (cont’d)    Malfunction during operation. Immediately turn off the generator if any of the following conditions   arise during operation:   o o o o o o o o o Excessive change in engine speed, slow or fast   Overheating in load connecting devices   Sparking or arcs from generator   Loss of electrical output   Receptacle damage   Engine misfire   Excessive vibration   Flame or smoke   Abnormal noise    Adjusting / repairing. Always turn off generator and remove spark plug(s) or spark plug wire(s) before   working on the generator to prevent accidental starting. Always discharge the capacitor before working   on the generator head to prevent electrical shock. (See Maintenance & Repair section of this manual for   instructions on how to do this.)    Carbon monoxide poisoning. The running engine gives off carbon monoxide, a poisonous gas that can   kill you. You CANNOT smell it, see it, or taste it. Follow all instructions for site selection and   positioning the generator, and avoid inhaling the exhaust. If you start to feel sick, dizzy, or weak while   using the generator, shut off the engine and get to fresh air RIGHT AWAY. See a doctor. You may have   carbon monoxide poisoning.    Other exhaust dangers. This product contains or emits chemicals known to the State of California to   cause cancer, birth defects or other reproductive harm. Avoid inhalation of exhaust.    Wet conditions. Do not operate the generator or handle any electrical equipment while standing in water,   while barefoot, while hands are wet or while in the rain or snow. Electric shock may result.    Ground fault circuit interrupter. Always use a ground fault circuit interrupter (GFCI) protected   extension cord (or outlet, if generator is equipped) in damp or highly electrical conductive areas and on   construction jobsites to prevent electrical shock.    Avoid contact. Avoid contact with bare wires, terminals, connections, etc. while the unit is running.    Electric shock accident. If an electric shock accident occurs, immediately shut down the source of   electrical power. If this is not possible, attempt to free the victim from the live conductor. Avoid direct   contact with victim. Use a nonconducting implement, such as a dry rope or board, to free the victim from   the live conductor. Apply first aid and get immediate medical help.    Smoking/sparks. Never smoke near the running generator, and never operate near sources of sparks or   flames.    Hot muffler. Never touch hot muffler, hot exhaust manifold, or engine cooling fins. Exhaust and engine   parts can be very hot and will burn you.    Moving parts. Keep hands, feet, and apparel away from drive belts, fans, and other moving parts. Never   remove any drive belt or fan guard while the unit is operating.   20   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation (cont’d)   Static electricity and filling the gasoline tank:   Static electricity can initiate from ungrounded gasoline tanks or containers, from flowing gasoline, and   from persons carrying a static electric charge   Static electricity can explosively ignite gasoline vapors that are present during the fueling process, resulting   in serious burns to nearby persons. To avoid static electricity while fueling, certain steps must be followed   before and during the fueling process in order to minimize and safely dissipate static charge build-up:    Touch a grounded metal object before starting. Always dissipate static charge from your body before   beginning the fueling process by touching a grounded metal object at a safe distance away from fuel   sources.    Use a portable container to fill tank. Never fill the generator’s gas tank directly from the fuel pump –   the generator’s tank is not grounded and the high velocity flow of gasoline from a fuel pump can cause   static electric build-up. Use an approved portable container to transfer gasoline to the generator’s tank.    Fill container on the ground. Never fill the portable gas container while it is sitting inside a vehicle,   trailer, trunk, or pick-up truck bed. ALWAYS place container on the ground to be filled.    Keep nozzle in contact with container. Keep nozzle in contact with the portable container at all times   while filling. Manually control the flow of gasoline; do NOT use the nozzle’s lock-open device.    Use a portable container made of metal or conductive plastic. It will dissipate charge to ground more   readily.   About static electricity and fueling   Many common objects can accumulate and retain a static electric charge. Objects made of non-conductive   materials (e.g. plastics) easily accumulate and retain static electric charge, as can objects made of conductive   material (e.g. metal, water) if they are not electrically grounded. The static electric charge on an object, such   as a human body or plastic fuel tank/container, can reach as high as several thousand volts!   A static electric spark can be generated if the static electric charge stored on an object “jumps” to another,   less charged object. Such a spark can ignite invisible gasoline vapors that are present during fueling   situations.   Typical sources of static electric hazards during fueling   The following objects can accumulate a static electric charge and cause an ignition spark in typical fueling   situations:   1) Ungrounded tanks/containers. Any ungrounded fuel tank or container can accumulate a static electric   charge as a result of contact with other objects or friction during transportation. This static electricity can   discharge as a spark to the grounded gasoline dispenser nozzle, as the nozzle is first brought close to the   tank/container at the beginning of the fueling process.   2) Flowing gasoline. Most people are not aware that gasoline accumulates static electric charge while   flowing through a hose or pipe. This charge then transfers to and accumulates in the gas tank or container   that is being filled. The total amount of charge accumulation depends on the amount of gas pumped into   the container, the speed with which it is pumped, and whether or not the tank/container is grounded. If   sufficient static electric charge accumulates in the fuel tank or container during the fueling process, the   tank/container may discharge a spark to the grounded gasoline dispenser nozzle.   3) Persons. A person dispensing the gasoline can carry a static electric charge on their body, typically   resulting from contact with their car seat or electronics. The static electricity can discharge as a spark   between that person’s hand and either the grounded dispenser nozzle or the fuel tank opening.   21   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation (cont’d)   2. Preparing for Operation   Position   generator   Position generator in accordance with the instructions given in   “Installation & Initial Set-up, Step 4: Select a Suitable Site” of this   manual.   Operate outside only, on dry, level ground with at least 20 feet from the home,   away from windows, vents and air intakes, to allow proper ventilation.   WARNING: Carbon monoxide poisoning hazard   Generators give off carbon monoxide exhaust, a poisonous gas that can   kill. You CANNOT smell it, see it, or taste it. ONLY run generator   OUTDOORS and at least 20 feet from the home, away from windows,   vents and air intakes, to allow proper ventilation. If you start to feel sick,   dizzy, or weak while using the generator, shut off the engine and get to   fresh air RIGHT AWAY. NEVER run generator inside any enclosed or   semi-enclosed spaces, including homes, garages, basements, sheds,   boxes, pick-up truck beds, RVs, or boats. These spaces can trap   poisonous gases, EVEN if you run a fan or open windows. Carbon   monoxide exhaust is given off whether you are using gasoline, natural   gas, or propane to power the generator.   Ground   generator   Make sure the generator is grounded in accordance with instruction given   in “Installation & Initial Set-up, Step 5: Grounding the Generator” of   this manual.   WARNING: Electric shock hazard   Always ensure generator is properly grounded to prevent electrical   shock.   Perform   Make sure that any regular maintenance has been performed as prescribed   scheduled   maintenance as   needed   in this manual in the “Maintenance & Repair” section.   Refer to the engine owner’s manual for engine maintenance   instructions.   Check/add oil   Check the oil level using the dipstick and add oil as needed.   Using a funnel, add oil up to the FULL mark on the dip stick with the   recommended oil type for your engine and expected ambient conditions.   (See engine Owner’s Manual for oil type and capacity, and more detailed oil   check/fill instructions.)   WARNING: Burn hazard   Never open oil port while engine is running. Hot oil can spray over face   and body.   ˙Notes:   o Low oil shutdown feature prevents the generator from starting without sufficient oil.   o Engine is shipped without oil. You must add oil before first use.   IMPORTANT:   Under long, continuous-run operating conditions, be prepared to:    Check engine oil level every time you refuel the engine.    Change oil after the first 20 operating hours, and at least every 100   operating hours thereafter, or as directed in engine owner’s manual.   Check the gasoline level in the generator’s tank. If needed, fill tank with   fresh unleaded gasoline from a portable container, after first reading the   warnings and instructions below.   Check/fill   gasoline tank   22   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation (cont’d)   WARNING: Gasoline fire/explosion hazard   Gasoline is highly flammable and explosive. Heat, sparks, and flames   can ignite gasoline vapors, which can become widespread during fueling.   A flash fire and/or explosion could result and cause serious injury or   death. Use extreme care when handling gasoline. Carefully follow all   the instructions in this section to avoid the following conditions which   could result in gasoline ignition:        gas vapor collection inside enclosures   static electric sparks   sparks from electric wiring, batteries, or running engines   sources of heat (such as a hot engine or exhaust)   open flames, including pilot lights   1) Before starting, review the following general safety precautions for fueling:   a) Never pump gasoline directly into the generator’s gas tank at a gas station   – high velocity flow from the pump could result in a static electric build-   up in the generator’s tank. Always use a portable container to fill the tank.   See warning box about static electric spark hazards below.   b) Fill gasoline tank OUTDOORS – never indoors.   c) Stay away from all sources of heat, sparks, and flames. Do not smoke.   2) Turn generator engine off and allow to cool for at least two minutes before   removing gas cap.   Note: A running or still-hot engine is hot enough to ignite fuel.   3) Remove generator gasoline cap.   4) Add gasoline through the fill opening:   - Use only a UL-approved portable gasoline container to transfer the gasoline   to the generator’s tank. Follow the safety warning and instructions below   for avoiding static electric sparking.   - Do NOT overfill the gasoline tank. Allow at least 1/2” of empty space   below the fill neck to allow for fuel expansion.   WARNING: Static electric spark hazard   A static electric spark can explosively ignite gasoline vapor, resulting in a   flash fire that could cause serious injury or death.   To avoid static electric sparking while filling the gasoline tank, the   following steps must be followed to minimize and safely dissipate static   electric charge build-up before and during the fueling process:    Always dissipate static charge from your body before beginning the   fueling process by touching a grounded metal object at a safe distance   from fuel sources.    Never fill the generator’s gas tank directly from the fuel pump – the   generator’s tank is not grounded and high velocity flow from the pump   can cause static electricity build-up. Use an approved portable   container to transfer gas to the generator’s tank.    Never fill the portable gas container while it is sitting inside a vehicle,   trailer, trunk, or pick-up truck bed. ALWAYS place container on the   ground to be filled.   23   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation (cont’d)     Keep nozzle in contact with portable container while filling. Manually   control the flow of gasoline; do NOT use the nozzle’s lock-open   device.   A portable container made of metal or conductive plastic is preferred   because it dissipates charge to ground more readily.   5) Clean up gasoline spills /splashes immediately.     If possible, move the generator away from spilled gasoline on the ground.   Wipe up spilled gasoline, and wait 5 minutes for excess gasoline to evaporate   before starting engine.     Gasoline soaked rags are flammable and should be disposed of properly.   If gasoline is spilled on your skin or clothes, change clothes and wash skin   immediately.   6) Replace gasoline cap securely before starting engine.   7) Store extra gasoline in a cool, dry place in an UL-approved, tightly sealed   container.   IMPORTANT:   For continuous operation, be prepared to check and refuel the engine on a   regular basis. A tank of gasoline should last about 2.3 hours under 50%   load.   Inspect Fuel   System / Check   for Leaks   Inspect fuel system & check for leaks BEFORE starting generator.   Do not start generator until all needed repairs have been completed.   WARNING: Fuel leak hazard   Gasoline is highly explosive and fuel leaks can result in fire or   explosions. You can be burned and seriously injured if the fuel system is   not properly hooked up or there is a fuel leak when you start the engine.   Inspect the entire fuel system.   Look for:    signs of leaks or deterioration,    chafed or spongy fuel hose,    loose connections,    loose or missing fuel hose clamps,    a damaged gasoline tank, or    a defective gasoline shut-off valve.   1) Hearing can be damaged from prolonged, close-range exposure to the type   of noise produced by this generator. The use of ear plugs or other hearing   protection device is recommended for persons working within 15-20 feet   of the running generator for an extended period of time.   Personal   Protection   2) Loose or dangling apparel can become entangled in moving parts. Metal   jewelry can conduct electricity. Never wear jewelry or loose-fitting   clothing when starting or operating the generator.   24   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation (cont’d)   3. Starting the Engine   After you have completed the pre-start checklist procedures, you are ready to start the engine.   To start the engine:   1) Disconnect all loads to the generator.   2) Adjust choke:   a) To start a cold engine, pull the choke rod to the CLOSED position.   b) To restart a warm engine:   i) If the engine has run out of fuel, pull choke rode to the CLOSED position after refueling.   ii) If the engine has not run out of fuel, leave the choke rod in the OPEN position.   3) Start the engine:   a) Move the ignition switch lever (red) to the ON position.   b) Pull the starter grip lightly until you feel resistance, then pull the starter cord out briskly and   rapidly. Allow starter cord to return slowly.   4) If the choke rod was pulled to the CLOSED position to start the engine, push it to the OPEN   position as soon as the engine warms up enough to run smoothly.   5) Under long, continuous-run operating conditions, be prepared to:   a) Check and refuel the engine on a regular basis. A tank of gas should last about 2.3 hours   under a 50% load. See engine owner’s manual for more detail.   WARNING:   A running engine is hot enough to ignite fuel. Never add fuel or   remove gas cap if engine is running or still hot. Let cool at least   2 minutes.   b) Check engine oil level each time you refuel.   c) Change oil after the first 20 operating hours, and at least every   100 operating hours thereafter, as directed in the engine   owner’s manual.   WARNING:   Never open oil port while engine is running. Hot oil can spray   over face and body.   25   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation (cont’d)   4. Checking Generator Output   Although the speed of the engine was carefully adjusted at the factory so that the generator   produces the proper voltage and frequency, output voltage should be checked periodically to   ensure the generator is working properly before connecting loads to the generator.   WARNING:   The generator must be run at the correct speed in order to produce the   proper electrical voltage and frequency. Failure to do so could result in   damage to equipment powered by the generator and possible injury to the   individual.   Output voltage should be checked with a portable voltage meter:   1. Start engine and allow to warm up for five minutes. Do not connect any loads.   2. Use voltage meter to check output voltage   at the generator’s outlets/receptacles.   3. Measured voltage should be within the   following ranges:   a. 120V +/- 10% at 120V receptacles.   4. If measured voltage is not within the specified range, have generator adjusted by factory   authorized personnel. Do not attempt to adjust the engine speed yourself.   All engines have a tendency to slow down when a load is applied. When   electrical loads are connected to the generator, the engine is more heavily   loaded and as a result the speed drops slightly.   NOTE:   Slight variation in   voltage/speed with   changing electrical   loads   This slight decrease in speed, together with the voltage drop within the   generator itself, results in a slightly lower voltage when the generator is   loaded to its full capacity than when it is running with no load.   Additionally, there may be small brief surges and drops in voltage as motors   connected to the generator cycle on or off.   The slight variation has no appreciable effect in the operation of motors,   lights, and most appliances.   26   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation (cont’d)   5. Connecting Loads   You will want to be careful when connecting loads so as not to overload the generator, especially if   you are powering devices with motors that require a higher starting power load.   Instructions are provided below for connecting loads when you are using the generator:   o As a portable power source   o Connected to a building as a back-up power source   WARNING:   Do not overload generator. Make sure that combined starting and running loads do   not exceed rated capacity of generator. Overloading the generator can cause damage   to the generator and attached electrical devices, and may result in fire.   Using as a   Portable Power   Source   Connect electrical loads one at a time according to the following   instructions:   1. Allow engine to reach operating speed by allowing it to warm up for   approximately 5 minutes before connecting electrical devices.   2. After engine is warmed up, begin by connecting the items that require   the highest wattage first. The recommended sequence is as follows:   a. Connect items with motors such as refrigerators, freezers, air   conditioners, or small hand tools, one at a time. Let each motor   stabilize before connecting the next device.   b. Connect any lights you are planning on powering.   c. Connect voltage sensitive equipment such as electronics via surge   protectors. Plug devices such as TV’s, computers, and microwaves   into a UL listed voltage surge protector, then plug the surge   protector into the generator.   Each transfer switch installation will be unique.   Using as a   Back-up Power   Source for a   Building   Proper instructions for how to safely bring the generator online with the   building’s electrical system should be provided by the installing electrician,   who should also provide personal instruction to the owner/operator.   Failure to follow the proper procedure as provided by the electrician could   expose persons to the hazards noted above.   6. Stopping   Stop the engine using the following steps:   1. Disconnect all loads to the generator.   2. Move ignition switch lever to OFF position.   3. Remove spark plug to prevent accidental starting of engine.   27   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation (cont’d)   7. Storage & Exercise   When you are finished using the generator, you must:   o Disconnect all loads   o Store the generator properly   o Plan on exercising the engine regularly unless the generator is prepared for long-term   storage.   Detailed instructions are provided below.   When you are finished using the generator, make sure all devices that   Disconnect loads   were connected to the generator’s outlets have been disconnected.   Let engine cool for at least five minutes before storing. A hot engine can   be a fire hazard.   Cool engine before   storing   Choose a storage   location   Store the generator in a location that is:   o Clean and dry   o Away from sources of heat, open flames, sparks, or pilot lights, even   if the generator’s fuel tank is empty. Residual fuel in the tank could   ignite.   o Away from extreme high or low temperatures.   Prevent accidental   starting   Remove key from starter (for electric start engines) and secure key in a   safe location, or remove spark plug(s) in order to ensure the generator   cannot be started accidentally in a storage location or by untrained persons.   Exercise generator The generator should be exercised regularly.   At least every four weeks, start the engine and let it run for 10 to 15 minutes   every 4 weeks   with a small load plugged in, such as a lamp or fan.   Monthly exercising of the generator will:   o Dry out any moisture that has accumulated in the windings. If left,   this moisture can cause corrosion in the winding.   o Ensure that the unit is operating properly should it be needed in an   emergency.   Perform periodic maintenance as directed in this manual to keep the   generator in safe working condition.   Perform regular   maintenance   28   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation (cont’d)   Prepare engine for If you will not be able to exercise the generator regularly, you must   prepare the engine for long term storage to prevent gum deposits from   forming and causing malfunction of the engine.   long term storage if   needed   Prepare engine for long term storage by:   o Removing all gasoline from the tank and carburetor   OR   o Adding fuel stabilizer to the gasoline (following manufacturer’s   instructions)   Fuel stabilizer steps:   1. Ensure gasoline tank is full.   2. Add fuel stabilizer to fuel tank.   3. Run engine at least 10 minutes after adding stabilizer to allow it to   enter the fuel system.   4. Shut off engine   5. Disconnect spark plug wire and remove spark plug   6. Add one teaspoon oil through spark plug hole   7. Place rag over spark plug hole and turn starter (or pull the recoil) a   few times to lubricate the combustion chamber.   8. Replace spark plug, but do not reconnect the spark plug wire.   29   Download from Www.Somanuals.com. All Manuals Search And Download.   Maintenance & Repair   Inspect and maintain your generator as specified below in order to keep it in safe and optimal   working order. Follow all safety rules and recommended maintenance steps.   WARNING   ALWAYS shut off the engine, disconnect the spark plug(s) and discharge the capacitor   before cleaning, adjusting, or servicing the generator. Make sure all guards and shields are   replaced before using.   Note: The generator head is brushless and maintenance free. The bearing is a heavy-duty   sealed ball bearing which requires no maintenance or lubrication.   Maintenance & Repair   Read and follow these safety rules whenever you will be servicing the   generator:   Follow safety rules    Turn off generator. Always turn off generator and remove spark plug(s) or   spark plug wire(s) before working on the engine or generator to prevent   accidental starting.    Discharge capacitor. When the generator is shut down, the capacitor may   maintain a charge. Always discharge the capacitor before working on the   generator head to prevent electrical shock. Discharge using a screwdriver with an   insulated handle. While wearing safety glasses, touch opposite terminals of the   capacitor together with the tip of the screwdriver. If there is stored charge in the   capacitor, a spark will be generated thereby discharging the capacitor.    Replace guards. Make sure all guards and shields are replaced after servicing   the generator.    Repair. Major service, including the installation or replacement of parts, should   be performed only by a qualified electrical service technician. Obtain factory   approved parts from NorthStar Product Support at 1-800-270-0810.    Replacement parts. If a part needs replacement, only use factory approved   repair parts. Replacement parts that do not meet specifications may result in a   safety hazard or poor operation of the generator and will void the warranty.   Perform engine   maintenance   Perform engine maintenance as specified in the engine owner’s manual.   Engine maintenance items include:   1. Changing oil and oil filter   2. Air filter check/replacement   3. Spark plug cleaning and replacement   4. Fuel filter check/replacement   5. Fuel tank cleaning.   Check receptacles   Check receptacles before each use to make sure they are not cracked or   broken.   If a receptacle is cracked or otherwise damaged, do not use until replaced   with an authorized factory part. Using cracked or damaged receptacles can be   both dangerous to the operator and destructive to the equipment.   Inspect fuel system / Inspect the fuel system and check for leaks on a regular basis.   check for leaks   1) Inspect the entire fuel system. Look for: signs of leaks or deterioration,   chafed or spongy fuel hose, loose connections, loose or missing fuel hose   clamps, damaged gasoline tank, or defective gasoline shut-off valve.   30   Download from Www.Somanuals.com. All Manuals Search And Download.   Maintenance & Repair (cont’d)   Check GFCI   (if equipped)   Once a month, test the Ground Fault Circuit Interrupter (GFCI) to   protect against electrical shock due to failure of the GFCI. (Only for   those models equipped with GFCI – See the “Specifications” section.)   To test the GFCI:   1. Depress the TEST button. The RESET button should extend from the   receptacle. If the RESET button does not extend, contact NorthStar for   replacement parts.   2. Restore power to the GFCI by firmly pressing the RESET button back   into the receptacle until an audible click is heard.   Clean and inspect the spark arrestor muffler. (Only for those models   equipped with a spark arrestor – See the “Specifications” section.)   Clean & inspect   spark arrestor   (if equipped)   If the engine is equipped with a spark arrester muffler, clean and inspect it   regularly (follow manufacturer’s service instructions). Replace if damaged.   Keep generator   clean   Keep generator clean.   If dust or debris accumulates on the generator, clean the generator with a   damp cloth or soft bristle brush. Do not allow air intakes to become blocked.   Note: Do not spray generator with a garden hose or pressure washer.   Water may enter the generator and cause damage to the rotor, stator, or   internal windings.   Recharge and   maintain battery   (if electric start)   Inspect, recharge, and maintain your battery according to your battery   manufacturer’s instructions. (Only for those models equipped with electric   start.)   Do not store with battery charger always connected. Batteries that are over-   charged can boil themselves dry and produce excessive amounts of hydrogen,   an explosive gas.   IMPORTANT:   If a part needs replacement, only use parts that meet the manufacturer’s specifications. Replace-   ment parts that do not meet specifications may result in a safety hazard or poor operation of the   generator.   Contact NorthStar Product Support at 1-800-270-0810 for any questions,   problems, or parts orders.   31   Download from Www.Somanuals.com. All Manuals Search And Download.   Troubleshooting   TROUBLESHOOTING   Problem   Possible Causes   Possible Remedies   Engine will not start.   a) Low oil level.   b) Fouled spark plug.   c) Out of fuel.   a) Fill crankcase to proper oil level.   b) Clean or replace spark plug.   c) Fill fuel tank.   d) Ignition switch lever in OFF position.   d) Place ignition switch lever in ON   position.   Voltage too low.   a) Engine speed too slow.   b) Generator is overloaded.   a) Bring generator to a qualified   technician for adjustment.   b) Reduce the load. (See Power Load   Planning & Mgt. section of this   manual.)   Circuit breaker trips.   Voltage too high.   a) Defective load connected to generator.   b) Defective receptacle.   c) Generator overloaded.   a) Disconnect load.   b) Replace receptacle.   c) Reduce the load. (See Power Load   Planning & Mgt. section of this   manual.)   a) Bring generator to a qualified   technician for adjustment.   a) Reduce the load. (See Power Load   Planning & Mgt. section of this   manual.)   a) Engine speed too high.   Generator overheating. a) Generator is overloaded.   b) Insufficient ventilation.   b) Make sure there is at least 3 feet of   clearance on all sides of generator.   a) Disconnect load.   No output voltage.   a) Defective load connected to generator.   b) Broken or loose wire.   b) Bring generator to a qualified   technician for repair.   c) Defective receptacle.   d) Defective stator.   c) Replace receptacle.   d) Bring generator to a qualified   technician for repair.   e) Defective rotor.   e) Bring generator to a qualified   technician for repair.   f) Defective capacitor.   g) Circuit breaker tripped.   a) Generator is overloaded.   f) Bring generator to a qualified   technician for repair.   g) Reset circuit breaker and reduce   loads connected to the generator.   a) Reduce the load. (See Power Load   Planning & Mgt. section of this   manual.)   Engine lacks power.   b) Dirty air filter.   a) Out of fuel.   b) Low oil level.   b) Clean or replace air filter.   a) Fill fuel tank.   b) Fill crankcase to proper oil level.   Engine shuts down   during operation.   32   Download from Www.Somanuals.com. All Manuals Search And Download.   Summary of Important Safety Information for Operation   This section provides a summary of the various safety procedures and measures that have been   presented throughout the manual. Keep this summary handy and refer to it to refresh your   memory about how to safely use your generator.   WARNING   Carefully read and make sure you understand the following safety information before using   the generator. Improper use or maintenance of the generator can result in serious injury or   death from carbon monoxide poisoning, electric shock, fire/explosion, or burns.   General     Read manual. Read this Owner’s Manual and the engine Owner’s Manual completely before attempting to   set-up and use the generator. Serious injury or death can result if safety instructions are not followed.   Instruct operators. The generator owner must instruct all operators in safe generator set-up and operation.   Do not allow anyone to operate the generator who has not read the Owner’s Manual and been instructed on its   safe use.     Adults only. Only trained adults should set up and operate the generator. Do not let children operate.   Under the influence. Never operate, or let anyone else operate, the generator while under the influence of   alcohol, drugs, or medication.    Intended use. Carefully read about and understand the intended use of this generator. Do not use for other   purposes, as unforeseen hazards or equipment damage may result.   Prohibition Against Modifications   Never modify or alter the generator in any way. Modifications can create serious safety hazards and will also   void the warranty.    Engine speed. Never attempt to modify the engine speed setting. The engine speed is preset at 3600 RPM for   safe and optimal performance of the generator. If speed needs adjusting, it must be done by factory-   authorized personnel.     Fuel/exhaust system. Never modify the exhaust system, fuel tanks, or fuel lines. Carbon monoxide   poisoning, fire, or explosion could result.   Guards. Do not operate generator unless all guards and cover shields, which prevent access to moving parts   and pinch points, are in place. Failure to guard the power transmission mechanisms may result in serious   injury or death.   Safety – Installation & Set-up   Installation / Initial Set-up Safety   Dry, level surface. Situate generator on a dry, firm, level surface. Ensure generator sits level and will not   slide or shift during operation. Block wheels if applicable.   Operate OUTSIDE only – dangerous carbon monoxide exhaust! Generators give off carbon monoxide   exhaust, a poisonous gas that can kill. You CANNOT smell it, see it, or taste it. ONLY run generator   OUTDOORS and at least 20 feet from the home, away from windows, vents and air intakes, to allow proper   ventilation. If you start to feel sick, dizzy, or weak while using the generator, shut off the engine and get to   fresh air RIGHT AWAY. NEVER run generator inside homes, garages, sheds, or other semi-enclosed spaces.   These spaces can trap poisonous gases, EVEN if you run a fan or open windows. Carbon monoxide is given   off whether you are using gasoline, natural gas, or propane to power the generator.       No vehicle/marine use. This generator is NOT designed or approved for use in vehicles or marine   applications. Never run the generator inside RVs or other vehicles, on boats, or on pick-up truck beds.   Cooling ventilation. The generator needs adequate, unobstructed flow of air to allow for proper cooling of   engine and generator head. Situate so there is adequate clearance around generator to allow for cooling   airflow. Do not allow debris to accumulate and block airflow.    Grounding. Always ensure generator is properly grounded to prevent electrical shock. This generator is   equipped with a grounding post. Always complete the grounding path from the generator to a copper pipe/rod   driven into moist earth to a sufficient depth. Check with an electrician for local grounding requirements. If a   33   Download from Www.Somanuals.com. All Manuals Search And Download.   Summary of Important Safety Information for Operation (cont’d)   licensed electrician installs the generator with a connection to your building’s electrical circuit for use as a   standby power system, grounding will be complete through the building’s grounding system.   Isolate connection to building’s electrical circuit. Never plug the generator directly into a wall outlet.   ANY connection to a building’s electrical system MUST ISOLATE THE GENERATOR FROM UTILITY   POWER via an UL-approved transfer switch installed by a licensed electrician in compliance with all   applicable local building and electrical codes. If the generator is not isolated from the utility power system by   such means, generator output will back feed into the utility power grid. This may result in injury or death to   utility power workers or others who contact the lines during a power outage. It may also cause the generator   to explode or cause fires when utility power is restored.        Wet conditions. Water conducts electricity. Do not operate generator where it is wet. Operate on a dry   surface under an open, canopy-like structure.   CO alarms. Ensure that working, battery-operated or battery back-up carbon monoxide alarms are used in   any dwelling/structure that is in close proximity to the running generator.   Hot exhaust - fires. Exhaust from engine can be extremely hot and cause fire. Position muffler at least 7’   from combustible objects during operation.   Spark arrestor. Equip engine with a spark arrestor if generator will be used near any ignitable forest, brush,   or grassy land. See the “Specifications” section of this manual to determine if your generator is already   equipped. Make sure you comply with applicable local, state and federal codes.    Fire extinguisher. Keep a fire extinguisher rated “ABC” by the National Fire Protection Association nearby.   Keep it properly charged and be familiar with its use.   Safety – Before Use   Know how to operate   Review safety rules. Before each use of this generator, review the “Rules for Safe Operation.” Failure to   follow these rules may result in serious injury or death.   Know how to operate. Be thoroughly familiar with all controls and with the proper use of the equipment.   Know how to stop the generator quickly if needed.     Personal protective equipment   Hearing protection. The use of ear plugs or other hearing protection device is recommended for those in   close proximity to the generator while it is operating.   Loose / dangling. Loose or dangling apparel can become entangled in moving parts. Metal jewelry can   conduct electricity. Never wear jewelry or loose-fitting clothing when operating the generator.     Gasoline Safety   Gasoline is highly flammable and explosive. You can be burned or seriously injured when handling fuel. Use   extreme care when handling:      Fuel outdoors. Fill fuel tank outdoors – never indoors. Gasoline vapors can ignite if they collect inside an   enclosure. Explosion can result.   Use approved container. Never pump fuel directly into engine at gas station. Static charge can build and   ignite fuel. Use an UL approved fuel container to transfer gas to the engine.   Running / hot engine. A running engine is hot enough to ignite fuel. Never add fuel or remove gas cap if   engine is running or still hot. Stop the engine and allow to cool at least two minutes before adding fuel.   Heat / flames / sparks. Stay away from sources of heat, flame, or sparks while adding fuel.   Don’t overfill. DO NOT overfill the gas tank. Allow at least 1/2” of empty space below the fill neck to   allow for fuel expansion.       Replace cap. Replace gas cap securely before starting engine.   Spills. Clean up fuel spills immediately. Move generator away from spilled fuel on the ground. Wipe fuel   off engine and wait 5 minutes for excess fuel to evaporate before starting engine. Gas soaked rags should be   disposed of properly.     On skin / clothes. If gasoline is spilled on your skin or clothes, change clothes and wash skin immediately.   Inspect fuel system. Check fuel system on a regular basis. Look for signs of leaks, deterioration, chafed or   spongy fuel hose, loose or missing fuel hose clamps, damaged fuel tank, or a defective fuel shut-off valve.   Do not start generator until needed repairs have been completed.    Gasoline storage. Store gasoline in a cool, dry place in an UL-approved, tightly sealed container.   34   Download from Www.Somanuals.com. All Manuals Search And Download.   Summary of Important Safety Information for Operation (cont’d)   Safety – During Use     Safety equipment / controls. Always operate the generator with all safety covers, guards, and barriers in   place and in good working order, and all controls properly adjusted for safe operation.   Know how to stop. Be thoroughly familiar with proper use of the equipment and all generator controls,   output receptacles, and connections. Know how to stop the generator quickly if needed.   Damaged. Do not operate the generator with damaged, missing, or broken parts.   Carbon monoxide exhaust. The running engine gives off carbon monoxide, a poisonous gas that can kill   you. You CANNOT smell it, see it, or taste it. If you start to feel sick, dizzy, or weak while using the   generator, shut off the engine and get to fresh air RIGHT AWAY. See a doctor. You may have carbon   monoxide poisoning.        Other exhaust dangers. This product contains or emits chemicals known to the State of California to cause   cancer, birth defects or other reproductive harm. Avoid inhalation of exhaust.   Smoking/sparks. Never smoke near the running generator, and never operate near sources of sparks or   flames.   Check output voltage. Check output voltage to ensure the generator is working properly before connecting   loads to the generator. Failure to do so could result in damage to equipment powered by the generator and   possible injury to the individual. Do not adjust output speed of engine to change voltage. If voltage is not   within specified range, have generator repaired by factory authorized personnel.   Stabilize before connecting loads. Start generator and let engine stabilize before connecting electrical loads.   Do not overload. Do not overload the generator. Make sure that combined starting and running loads do not   exceed rated capacity of generator or damage will result.      Protect sensitive electronics. Some electronic equipment, such as computers and audio/video equipment,   can be damaged by small fluctuations in the flow of power. Use a surge suppressor for any voltage-sensitive   electronic equipment you will be powering with the generator.     Wet conditions. Do not operate the generator or handle any electrical equipment while standing in water,   while barefoot, while hands are wet or while in the rain or snow. Electric shock may result.   Ground fault circuit interrupter. Always use a ground fault circuit interrupter (GFCI) protected extension   cord (or outlet, if generator is equipped) in damp or highly electrical conductive areas and on construction   jobsites to prevent electrical shock.    Electrical cords. Use only UL-listed, outdoor-rated, three prong extension cords of the proper size. All   extension and appliance cords must be in good condition and not worn, bare, frayed, or otherwise damaged.   Use of inadequate or damaged electric cords can cause electric shock or fire.     Avoid contact. Avoid contact with bare wires, terminals, connections, etc. while the unit is running.   Electric shock accident. If an electric shock accident occurs, immediately shut down the source of electrical   power. If this is not possible, attempt to free the victim from the live conductor. Avoid direct contact with   victim. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live   conductor. Apply first aid and get immediate medical help.     Hot muffler. Never touch hot muffler, hot exhaust manifold, or engine cooling fins. Exhaust and engine parts   can be very hot and will burn you.   Moving parts. Keep hands, feet, and apparel away from drive belts, fans, and other moving parts. Never   remove any drive belt or fan guard while the unit is operating.     Refueling. DO NOT refuel the engine until it has cooled at least two minutes.   Malfunction during operation. Immediately turn off the generator if any of the following conditions arise   during operation:   o o o o o o o o o Excessive change in engine speed, slow or fast   Overheating in load connecting devices   Sparking or arcs from generator   Loss of electrical output   Receptacle damage   Engine misfire   Excessive vibration   Flame or smoke   Abnormal noise    Adjusting / repairing. Always turn off generator and remove spark plug(s) or spark plug wire(s) before   working on the generator to prevent accidental starting.   35   Download from Www.Somanuals.com. All Manuals Search And Download.   Summary of Important Safety Information for Operation (cont’d)   Safety – After use     Cool engine before storing. Let engine cool for at least five minutes before storing. A hot engine can be a   fire hazard.   Prevent accidental starting. When generator is not in use, remove key from starter (key start engines) and   secure in a safe location, or remove spark plug(s) in order to ensure that generator cannot be started in a   storage location or by untrained persons.    Storage location. Store the generator in a dry location away from sources of heat, open flames, sparks or   pilot lights – such as water heaters, space heaters, furnaces, clothes dryers, or other gas appliances – EVEN IF   the generator’s gas tank is empty. Residual gasoline could ignite.     Exercise regularly. Exercise generator every four weeks to dry out moisture that accumulates in the   windings. If generator cannot be exercised on a regular basis, prepare generator for long term storage.   Periodic maintenance. Perform periodic maintenance as directed in this manual to keep the generator in safe   working condition.   Safety - Inspection/Maintenance   Inspect and maintain your generator on a regular basis and repair as needed to keep it in safe working condition:    Turn off generator. Always turn off generator and remove spark plug(s) or spark plug wire(s) before   working on the engine or generator to prevent accidental starting.    Discharge capacitor. When the generator is shut down, the capacitor may maintain a charge. Always   discharge the capacitor before working on the generator head to prevent electrical shock.   Replace guards / shields. Make sure all guards and shields are replaced after servicing the generator.   Replacement parts. If a part needs replacement, only use parts that meet the manufacturer’s specifications.   Replacement parts that do not meet specifications may result in a safety hazard or poor operation of the   generator and will void the warranty.     36   Download from Www.Somanuals.com. All Manuals Search And Download.   Generator Exploded View 165912 - Rev I.3   37   Download from Www.Somanuals.com. All Manuals Search And Download.   Generator Exploded View 165912 – Rev I.3   Diag #   Part #   Description   Qty   1 2 4 5 7 9 305491 Honda 5 hp Engine   780422 Engine Adapter Plate   780423 Fan & bolts   1 1 1 1 1 2 1 1 1 1 1 1 1 4 1 1 1 1 2 2 1 1 1 1 4 1 1 1 1 1 31193   Drive End Bracket   780424 Enclosing Band   306426 120V, 20A, NEMA 5-20R Receptacle   10   11   14   15   17   19   20   21   22   23   24   25   26   27   28   29   31   32   33   34   35   36   37   38   30643   31177   30815   38271   39260   20A Circuit Breaker   End Cover   Hole Plug   End Cover Plug   Burning Warning   306459 Ground Wire   30963 Engine Bracket   305587 Isolation Mount   30964 Front Base Bracket   780425 Stator   31218   Nameplate   780426 Rotor   307481 Varistor   780427 Diode   780428 Securing Stud & nut   780429 Bearing   31195   Non Drive End Bracket   307477 Capacitor   780431 Bracket Securing Stud   31178   Cradle Weldment   779428 Decal   30965   30966   Generator Bracket   Back Base Bracket   780393 Generator   38   Download from Www.Somanuals.com. All Manuals Search And Download.   Wiring Diagram 165912 - Rev I.3   Diag #   Part #   Description   Qty   1 2 B46   B52   W55   305555 Connector Wire Harness   306496 Wire Assembly (W43, G41, G42)   306571 Black Terminated Wire   305556 Black Terminated Wire   305557 White Terminated Wire   1 1 1 1 1 39   Download from Www.Somanuals.com. All Manuals Search And Download.   This page has intentionally been left blank.   40   Download from Www.Somanuals.com. All Manuals Search And Download.   Limited Warranty   Dear Valued Customer:   The NorthStar Product you just purchased is built with the finest material and craftsmanship. Use this product properly and enjoy   the benefits from its high performance. By purchasing a NorthStar product, you show a desire for quality and durability. Like all   mechanical equipment this unit requires a due amount of care. Treat this unit like the high quality piece of machinery it is. Neglect   and improper handling may impair its performance. Please thoroughly read the instructions and understand the operation before   using your product. Always contact NorthStar Product Support at 1-800-270-0810 prior to having any service or warranty work   performed, as some services performed by parties other than NorthStar approved service centers may void this warranty. This   warranty is in lieu of any other warranty expressed or implied and NorthStar assumes no other responsibility or liability outside that   expressed within this warranty.   Limited Warranty   NorthStar shall warranty any piece of equipment manufactured, or parts of equipment manufactured, to be free from defects in   material or workmanship for a period of:   NorthStar Warranty   Item #   Consumer Warranty Period   Commercial Warranty Period   165912   3 years from date of purchase by user   90 days from date of purchase by user   Engine Warranty   Item #   Consumer Warranty Period   Commercial Warranty Period   165912   3 years from date of purchase by user   90 days from date of purchase by user   “Consumer use” means personal residential household use by a consumer. “Commercial use” means all other uses, including use for   commercial, income producing or rental purposes or when purchased by a business.   This warranty applies to the original purchaser of the equipment (verification of purchase, in the form of a receipt, is the   responsibility of the buyer), is non-transferable, and covers parts and labor. Parts will be replaced or repaired at no charge, except   when the equipment has failed due to lack of proper maintenance. If a part is no longer available, the part may be replaced with a   similar part of equal function. Any misuse, abuse, alteration or improper installation or operations will void warranty. Determining   whether a part is to be replaced or repaired is the sole decision of NorthStar. NorthStar will not provide for replacement of   complete products due to defective parts. Any costs incurred due to replacement or repair of items outside of a NorthStar approved   facility is the responsibility of the buyer and not covered under warranty. Transportation costs to and from service center is the   responsibility of the customer.   In addition to the normal warranty, NorthStar shall warrant any normal wear item from defects in material or workmanship for a   period of 90 days from the date of purchase by user. Normal wear items include, but are not limited to, filter elements.   This warranty specifically excludes the following; failure of parts due to damage caused by accident, fire, flood, windstorm, acts of   God, applications not approved by NorthStar in writing, corrosion caused by chemicals, use of replacement parts which do not   conform to manufacturer’s specifications, damage related to rodent and/or insect infestation and damage caused by vandalism.   Additional exclusions: loss of running time, inconvenience, loss of income, or loss of use, including any implied warranty of   merchantability of fitness for a specific use. Also, Outdoor Power Equipment needs periodic parts and service to perform well, and   this warranty does not cover instances when normal use has exhausted the life of a component or the engine.   This warranty does not cover any personal injury or damage to surrounding property caused by failure of any part. Repair or   replacement of parts does not extend the warranty period.   The engine warranty is covered under the terms and conditions as outlined by the engine manufactures warranty contained herein   and is the sole responsibility of the engine manufacture. Normal engine maintenance such as spark plugs, air filters, adjustments,   fuel system cleaning and obstruction due to build up is not covered by this NorthStar warranty.   Please fill in the following information and have it on hand when you call in on a warranty claim.   Customer Number: ______________________________________________________________   Date of Purchase: _______________________________________________________________   NorthStar Serial Number: _________________________________________________________   Item Number: __________________________________________________________________   41   Download from Www.Somanuals.com. All Manuals Search And Download.   Assembled by   Northern Tool & Equipment Company, Inc.   Burnsville, MN 55306   NorthernTool.com   42   Download from Www.Somanuals.com. All Manuals Search And Download.   |