Nortec Humidifier NHDI User Manual

NHSC / NHDI  
Resistive Element  
Steam Humidifiers  
Installation, Operation,  
Maintenance, and  
Troubleshooting Guide  
NHDI  
NHSC  
IMPORTANT: Read and save these instructions. This  
guide to be left with equipment owner.  
Form #04-197-1  
1505921  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESETTING FAULT INDICATION “ERROR” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
HEATING ELEMENT REPLACEMENT INSTALLATION INSTRUCTIONS . . . . . . . . . . . . . . . . 21  
TROUBLESHOOTING · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 23  
CONTROL CIRCUIT TERMINAL BLOCK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
PRE-START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
MAINTENANCE CHECKLIST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28  
EXPLODED VIEWS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
as indicated on the spec label. Refer to local  
codes.  
INSTALLATION  
RECEIVING & UNPACKING EQUIPMENT  
3. Report any discrepancy immediately.  
1. Check packing slip to ensure ALL material has  
been delivered.  
BASIC HUMIDIFIER CONFIGURATION  
NORTEC NHSC / NHDI humidifiers share a  
modular sheet metal cabinet. Each unit has a right  
side electrical compartment. Each electrical  
compartment has a hinge-down front door which is  
removable from any partially or fully opened position.  
Each electrical compartment has a screw-mounted  
right side cover which can open for ease of electrical  
connection. For safety, the door when closed keeps  
the side cover from being opened.  
2. All material shortages are to be reported to  
NORTEC within 48 hours from receipt of  
goods. NORTEC assumes no responsibility  
for any material shortages beyond this period.  
3. Inspect shipping boxes for damage and note  
on shipping waybill accordingly.  
4. After unpacking, inspect equipment for  
damage and if damage is found, notify the  
shipper promptly.  
Single units have a plumbing compartment  
attached to the left side of the electrical. Double units  
have a second plumbing compartment. Each  
plumbing compartment has a hinge-down front door.  
For safety, the door must be closed in order to engage  
the safety interlock. To avoid any danger, never  
operate the humidifier with a door off.  
5. All NORTEC products are shipped on an  
F.O.B. factory basis. Any and all damage,  
breakage or loss claims are to be made  
directly to the shipping company.  
PRE-INSTALLATION CHECKPOINT  
To open the doors, unlock, lift door up slightly and  
pull top of door forward. Door will hinge 180 degrees  
and hang straight down. To remove door, swing door  
parallel to floor. Then lift up slightly and out. To  
reinstall door, hold parallel to floor and insert hinge  
pins at bottom.  
1. Ensure that available voltage and phase  
corresponds with humidifier voltage and phase  
as indicated on humidifier’s spec label (see  
Figure #1).  
2. Ensure that the dedicated external disconnect  
is of sufficient size to handle the rated amps  
Figure #1  
Figure #2  
NHSC / NHDI Series Humidifier  
Minimum Steam Line Clearance  
Steam Outlet  
Optional SSR  
1.75" O.D.  
Cooling Fans  
Min. 10 Degree Slope  
Min. 12"  
Trap  
* See Section On  
Condensate  
Return Line  
Keypad  
Display  
Scale  
Collector  
Tank  
Power and  
Control  
Wiring  
Water  
Supply  
Spec  
Label  
Drain  
Valve  
NOTE: Trap must be 3' minimum down from steam distributor.  
If not, condensate must be routed to drain.  
NOTE: NHDI does not have the scale collector tank.  
- 1 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Figure #3  
1. Location of the humidifier should be below and  
as close as possible to the steam distributor  
location. If possible, DO NOT locate humidifier  
any further than absolutely necessary from  
steam distributor location, as controllability  
and net output will be reduced as a result of  
heat loss through the steam hose (see Steam  
Distribution Engineering Manual).  
Clearance Required (Top View)  
Condensate Return  
2. Where possible, mount humidifier at a height  
convenient for servicing.  
Right Side  
3. Wall mounting bracket provided should be  
securely attached horizontally and open edge  
facing upwards, using field-supplied fasteners.  
For a single unit, use a minimum of 4 - #12 x  
3” long wood screws. For a double unit, use a  
minimum of 6 - #12 x 3” long wood screws.  
These screws must be fastened securely on a  
2 x 4 wood stud or equivalent support. If any  
spacer material is used between the bracket  
and the structural material such as drywall,  
increase fastener length accordingly. In  
Steam Outlet  
Front  
NOTE: Local and national codes may deviate, please  
consult applicable codes for clearance requirements.  
Right side min. 36" side clearance. Min. 36" frontal  
clearance recommended see note.  
Top 12” Min, Bottom 12” Min, and Left Side 2” Min.  
addition, install a minimum of 2 field supplied  
fasteners in the holes provided in the back of  
the unit to prevent the unit from being bumped  
off the wall bracket. See Figure #4.  
LOCATION & MOUNTING  
HUMIDIFIERS  
4. Mount unit on hanging bracket after ensuring  
the bracket is properly anchored to the wall.  
Raise the unit and place it on the hanging  
bracket ensuring that the flanges in the  
NHSC / NHDI Series humidifiers are designed to  
mount on a suitable wall or vertical surface. Do not sit  
the unit on floor due to clearances required for  
plumbing, electrical, and control entrances. The  
clearance dimensions shown in this manual are for  
reference only and are the minimum required for  
maintenance of the humidifier. Local and National  
Codes should be consulted prior to final location and  
installation of the humidifier. NORTEC will not accept  
responsibility for installation code violations.  
mounting bracket are properly aligned and  
centered with the flanges of the unit. Push the  
unit in towards the wall to properly interlock  
the two flanges. Note: This will result in the  
unit shifting slightly down. Ensure that the  
hanging bracket’s flanges are fully engaged  
Figure #4  
Figure #5  
Wall Bracket Mounting  
Installation of the Scale Tank Bracket (NHSC only)  
Frontal clearance min. 36" (91 cm)  
Right side clearance min. 36" (91 cm)  
Left side clearance min. 2" (5 cm)  
1.  
Wall  
2.  
1) Line up holes in bracket with  
holes in drain pan. Fasten the  
bracket to the drain pan using  
the four Nylon lock nuts  
provided.  
3.  
7.7"  
(19.6 cm)  
2) Fasten the front of bracket  
with the two #10-24 self tapping  
screws provided.  
3) The two locking screws for the  
bracket should already be  
installed.  
1.  
Download from Www.Somanual-s.c2om- . All Manuals Search And Download.  
 
and visible from within the plumbing section of  
the unit, and that the unit’s flanges are  
properly contained within the wall bracket.  
Figure #7  
Remote Mounted Blower Packs (RMBP)  
23.0"  
(58.4 cm)  
14.2"  
(36.2 cm)  
5. Install tank bracket. See Figure #5. (NHSC  
Version only). Mounting the scale tank. (NHSC  
Version only).  
2.9"  
(7.3 cm)  
11.0"  
(28.0 cm)  
Wall  
Mounting  
Bracket  
Figure #6  
Remote Mounted Blower Pack  
Power  
Steam  
Condensate  
Dimensions Shown  
Remote  
Mounted  
Blower Pack  
Are Steam Line Connections  
Allow Minimum 12" (31 cm)  
Clearance On Each Side  
7.7"  
(19.5 cm)  
7.2"  
(18.2 cm)  
cabinet provided by others should be used.  
Consult factory.  
9. DO NOT mount humidifiers on vibrating  
surfaces or duct work.  
Scale  
Collector  
Tank  
6. Make sure humidifier is level.  
BLOWER PACKS  
7. DO NOT mount humidifier on hot surfaces.  
1. Blower packs are an optional accessory used  
to directly distribute steam to localized areas  
(such as computer rooms) or in structures that  
do not have a built-in air distribution system.  
8. If humidifiers are mounted on roof, a  
thermostatically ventilated weatherproof  
Figure #8  
Typical Remote Mounted Blower Pack Installation  
Remote Mounted Blower  
Packs (RMBP) Only  
NHSC uses Nortec steam  
hose 1.75" O.D.or  
stainless steel pipe.  
NHDI uses Nortec steam  
hose 1.75” O.D. or  
stainless steel pipe.  
3"  
Min. Trap  
Height 3"  
Required  
Do not exceed 10 ft  
when using steam hose.  
Steam Line  
Connection  
Humidistat  
Scale  
Collector  
Tank - NHSC  
LCD Keypad  
Display with  
LED Status  
Water  
Supply 3/8”  
Low Voltage  
Controls Wiring  
24 Vac  
Drain Line  
1.75” O.D.  
Primary Wiring  
Air  
Gap  
Copper Funnel  
Drain (by others)  
NHSC / NHDI using a Remote Mounted Blower Pack (RMBP)  
- 3 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2. All NHSC / NHDI Series blower packs consist  
of a steel cabinet containing: blower/motor  
powered by voltage directly from the  
6. For installation details, please refer to the  
installation manual located in the Steam  
Distributor box, Form #XX-231.  
humidifier, fuse, relay, speed select switch,  
stainless steel steam distributor, supply air  
grille with adjustable louvers, and a built-in  
manual reset safety thermostat to turn off the  
humidifier if the blower pack gets overheated.  
Control thermostat, mounted on the steam  
distributor, starts the fan when steam is  
generated. When supply voltage differs from  
voltage required to run blower motor, the  
blower pack will contain the proper  
7. For calculating absorption distances, refer to  
H.E.L.P. Software or the Steam Distribution  
Engineering Manual, Form #XX-232.  
transformer. All blower packs provide intake  
air filters, if required.  
3. For installation details about the blower pack,  
please refer to the blower pack installation  
manual located in the blower pack box, Form  
#XX-277.  
STEAM DISTRIBUTORS AND SHORT  
ABSORPTION MANIFOLD  
1. Steam distributors are an optional accessory  
used to directly distribute steam to localized  
areas (such as computer rooms) which are  
served by ducted air. These distributors are  
made of stainless steel and are mounted level  
to the duct.  
2. The SAM-e optional accessory has the same  
function, to distribute steam inside a duct. The  
only difference is that this system is designed  
to reduce the absorption distance of the steam  
in the duct by optimizing the steam  
distributors.  
3. Each cylinder requires its own steam line  
and at least one distributor (do not join two  
or more cylinders to one larger steam line).  
Any cylinder’s steam line may be divided into  
multiple branches to feed more than one  
distributor. Steam supply line “tees” are  
common stainless fittings that are available for  
this purpose.  
4. Steam distributor locations are typically as  
follows: supply air duct, return air duct, air  
handling unit. Proper location should  
consider: air temperature, relative humidity  
before the distributor, air velocity, dimensions  
of the location, amount of steam being  
introduced into the duct, downstream  
obstructions, and surfaces vulnerable to  
wetting.  
5. The NHSC / NHDI can overcome 6” of W.C.  
duct static pressure max. Consult the factory  
if you exceed 6” of W.C.  
Download from Www.Somanual-s.c4om- . All Manuals Search And Download.  
Figure #9  
Typical AHU / Duct Application using a SAM-e  
NHSC uses Nortec steam  
hose 1.75” O.D. Or Med.  
L Copper Insulated  
Steam  
Inlet  
NHDI uses Nortec steam  
hose 1.75” O.D. or  
stainles steel pipe.  
Do not exceed 10 ft  
when using steam hose.  
Humidistat  
SAM-e  
Min  
24”  
Steam Line  
Connection  
Trap depth  
2” greater  
than duct  
static pressure  
LCD Keypad  
Display with  
LED Status  
Condensate return  
to floor drain, sump  
pump or back to the  
humidifier  
Scale  
Collector  
Tank  
NHSC  
Low Voltage  
Controls Wiring  
24 Vac  
Drain Line  
1.75" O.D.  
Primary Wiring  
Air  
Gap  
Copper Funnel  
Drain (by others)  
Water  
Supply 3/8”  
NHSC using a Short Absorption Manifold (SAM-e) in Duct/AHU  
Figure #10  
Typical Duct Application using Standard Distributor  
NHSC uses Nortec steam  
hose 1.75” O.D. Or Med.  
L Copper Insulated  
Steam  
Inlet  
NHDI uses Nortec steam  
hose 1.75” O.D. or  
stainles steel pipe.  
Do not exceed 10 ft  
when using steam hose.  
Humidistat  
Min  
24”  
Steam Line  
Connection  
Condensate trap  
must be 2” greater  
than duct static  
pressure.  
LCD Keypad  
Display with  
LED Status  
Scale  
Collector  
Tank  
NHSC  
Low Voltage  
Controls Wiring  
24 Vac  
Drain Line  
1.75" O.D.  
Primary Wiring  
Air  
Gap  
Copper Funnel  
Drain (by others)  
Water  
Supply 3/8”  
NOTE: NHDI does not have the scale management system.  
- 5 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
#11). A field-supplied funnel (see Figure #12)  
is recommended. It will prevent backup in the  
drain pan and in the cylinder due to partially  
blocked or badly installed drain lines. This  
prevents rusting of the drain pan.  
PLUMBING  
All water supply and drain line connections  
should be installed in accordance with local  
plumbing codes and should be copper or other  
material suitable for potable water at 140ºF (60ºC).  
2. The NHSC scale collector tank is also  
equipped with its own drain. It is  
WATER SUPPLY LINE - NHSC  
recommended to pipe, with a flex hose, the  
scale collector tank to allow drainage, if  
required while maintaining ease of servicing  
(DO NOT HARDPIPE).  
1. The humidifier is intended to operate on  
potable water.  
2. Standard fill valves are sized for water  
pressure ranging from 30 to 80 psig. For other  
pressures, consult factory. This pressure  
should be measured at the humidifier if the  
water pressure is suspect.  
3. The drain line should not end in a sink used  
frequently by personnel, or where plumbing  
codes prohibit it. Route to a floor drain or  
equivalent for safety reasons, since drain  
water from humidifier can be very hot.  
3. ALWAYS supply and install a shut off valve in  
the fill water supply line dedicated to the  
humidifier to facilitate servicing. Use ½" OD  
copper to within 4 feet of the humidifier.  
Reduce to 3/8" OD and connect to the  
factory-supplied 3/8" olive compression fitting  
under the humidifier.  
4. Keep drain lines as short as possible. Keep  
drain lines sloped down, not level and not  
up since low spots in drain lines will  
accumulate sediment and cause backup.  
The drain line should be 2.0” O.D. copper pipe  
or larger. Do not use plastic pipe for drain  
lines. Consult factory.  
4. Same installation as #3, but add Drain Water  
Cooler instead of fill.  
DRAIN LINE - NHDI  
1. Humidifier is equipped with a 1.5” O.D.  
un-threaded drain outlet on underside of drain  
canal on bottom of the humidifier (see Figure  
#6). A field-supplied funnel (see Figure #8) is  
recommended. It will prevent backup in the  
drain pan and in the cylinder due to partially  
blocked or badly installed drain lines. This  
prevents rusting of the drain pan.  
WATER SUPPLY LINE - NHDI  
1. Humidifier is intended to operate on Reverse  
Osmosis (RO) water or De-ionized (DI) water  
with a water conductivity of less than 20  
Microsiemens.  
2. Standard fill valves are sized for water  
pressure ranging from 30 to 80 psig. For other  
pressures, consult factory. This pressure  
should be measured at the humidifier if the  
water pressure is suspect.  
2. The drain line should not end in a sink used  
frequently by personnel, or where plumbing  
codes prohibit it. If the Drain Water Cooler is  
used with potable water then copper may be  
used. Route to a floor drain or equivalent for  
safety reasons, since drain water from  
3. ALWAYS supply and install a shut-off valve in  
the fill water supply line dedicated to the  
humidifier to facilitate servicing. Use ½" OD  
plastic or stainless steel to within 4 feet of the  
humidifier. Reduce plastic or stainless steel to  
3/8" OD and connect to the factory-supplied  
3/8" olive compression fitting under the  
humidifier.  
humidifier can be very hot. Verify with local  
codes on DI and RO water. Drains should be  
verified for their suitability for RO or DI water  
and local codes should be checked.  
3. Keep drain lines as short as possible. Keep  
drain lines sloped down, not level and not  
up since low spots in drain lines will  
accumulate sediment and cause backup.  
The drain line should be 2.0” O.D. S.S. pipe or  
larger. Do not use plastic pipe for drain lines.  
Consult factory.  
4. Same installation as #3, but add Drain Water  
Cooler instead of fill.  
DRAIN LINE - NHSC  
1. Humidifier is equipped with a 1.5”" O.D.  
unthreaded drain outlet on underside of drain  
canal on bottom of the humidifier (see Figure  
Download from Www.Somanual-s.c6om- . All Manuals Search And Download.  
Figure #11  
STEAM LINE AND CONDENSATE RETURN LINE  
Drain Line Connection  
1. Refer to the installation manual of the steam  
distribution system used in your application.  
Steam Distributor Form #XX-231, SAM-e  
Form #XX-249, and Blower Pack Form  
#XX-277.  
Power  
Inlet  
Supply Water  
Connection  
3/8“  
NHSC  
Scale  
Collector  
Tank  
Controls  
Inlet  
ELECTRICAL  
Drain  
Water Cooler  
Connection 3/8”  
Optional  
Cooling Kit  
for SSR  
(consult  
factory)  
PRIMARY VOLTAGE SUPPLY WIRING TO  
HUMIDIFIER  
A
7.95  
(20.2)  
Drain  
Connection  
1.5" O.D.  
B
23.0  
(58.4)  
1. Check and ensure that available voltage and  
phase corresponds with operating voltage and  
phase of humidifier as indicated on the  
humidifier spec label, see Figure #1.  
Model  
010-090  
135-180 Left  
135-180 Right  
A (in.) B (in.)  
1.7” 5.4”  
1.7” 5.4”  
1.7” 20.3”  
2. Ensure that an adequate power supply is  
available to carry full humidifier amperage  
drawn as specified by rated amps on the  
humidifier spec label, reference to local codes.  
Figure #12  
Drain Connection  
3. A dedicated external disconnect must be  
installed. Do not exceed the maximum circuit  
protection amps as indicated on the  
nameplate label.  
Clampand1.5IDHose  
FactorySupplied  
4. Connect ground wire to cabinet ground clamp.  
Do not use neutral wire of four wire supply as  
ground.  
Air  
Gap  
InstallaCopperFunnelfortheNHSCmodel  
andaStainlessSteelFunnelfortheNHDI  
model(byothers).  
5. Single phase humidifiers may be run on three  
phase power, but load may unbalance power  
grid.  
Installa2O.DCopperPipefortheNHSC  
modeland2O.D. StainlessSteelPipefor  
theNHDImodel(byothers).  
NOTE: Steam hose should not  
reach bottom of the funnel.  
6. External wiring sizes must be in accordance  
with NEC and/or CEC and existing local  
electrical codes and by-laws.  
PRIMARY VOLTAGE SUPPLY WIRING FROM  
HUMIDIFIER(S) TO BLOWER PACKS  
Figure #13  
Drain Pump by others (if necessary)  
1. All blower packs are wired (by others) to be  
powered from the humidifier.  
Humidifier  
2. As a safety feature, blower packs come  
equipped with a manual reset safety  
thermostat and relay built into the blower pack  
cabinet. The manual reset thermostat turns  
off the humidifier if the blower pack gets  
overheated. The control thermostat, mounted  
on the steam distributor, starts the fan when  
steam is generated.  
Recommended Model  
Gould - Model SSH  
Consult Factory  
Drain Line  
Line  
3. All blower packs have high efficiency blowers  
to minimize the frontal and overhead  
clearance required to absorb the steam.  
Floor  
Surface  
- 7 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure #14  
Primary Voltage Supply Wiring  
VOLTAGE  
(ACTUAL)  
PRIMARY (LINE) VOLTAGE WIRING TO UNIT  
(BYOTHERS)  
Ground Wire  
Ground  
Leg  
Ground  
L1  
L2  
Dedicated  
Circuit  
Breaker  
Or  
Disconnect  
2 Pole  
Terminal  
Block  
- Single Phase Unit.  
- Single Phase Supply.  
E
X
T
I
- Required Voltage Between L1 And L2.  
- Load Balanced.  
N
T
Ground Wire  
Ground  
Leg  
Ground  
L1  
Dedicated  
Circuit  
Breaker  
Or  
Disconnect  
2 Pole  
Terminal  
Block  
L2  
L3  
- Single Phase Unit.  
- 3 Phase Supply.  
E
X
T
I
Neutral  
- Required Voltage Between L1 And L2.  
- Load Will Be Unbalanced.  
N
T
Ground Wire  
Ground  
Leg  
Ground  
L1  
Dedicated  
Circuit  
Breaker  
Or  
Disconnect  
3 Pole  
L2  
L3  
Terminal  
Block  
Neutral  
- 3 Phase Unit.  
- 3 Phase Supply.  
E
I
X
T
N
T
- Required Voltage Between Any Two Legs.  
- Load Will Be Balanced.  
NOTE: VoltageAtTerminalBlockMustBeInAccordanceWithSpec. Label.  
AllWiringToBeInAccordanceWithExistingNationalAndLocalElectricalCodes.  
Download from Www.Somanual-s.c8om- . All Manuals Search And Download.  
 
4, All blower packs require field wiring between  
two pole primary voltage terminal blocks and  
two low voltage control (class 1 circuit wiring  
required) terminal strips; one of each located  
in the humidifier and the remote blower pack  
cabinet. To properly access the primary block  
on the humidifier, it is necessary to open the  
side pan. To connect the primary and control  
(class 1 circuit wiring required) wiring, the  
wiring is fed through the grommet provided in  
the bottom of the blower pack. The terminal  
block and strip are accessed by removing the  
blower pack cover.  
A - Wall or Duct Mounted Control On/Off  
Humidistat: Wired to make on drop in humidity, break  
on rise to set-point. Set to desired % RH. Can be a  
make/break set of contacts from a Building Automation  
System.  
B - Duct Mounted Safety High Limit On/Off  
Humidistat (if used): Wired to make on drop in  
humidity, break on rise to safety set-point. Set to  
approximately 85% RH as a safety to help prevent  
saturation and wetting in the duct.  
C - Duct Mounted Safety Air-Proving On/Off  
Switch (if used): Wired to make with sensed air flow,  
break when no air flow. Used as a safety to prevent  
saturation when there is no airflow.  
5. Field wiring of remote blower packs must  
conform to national and local electrical codes.  
Refer to wiring diagram supplied inside the  
humidifier.  
1. NORTEC offers various versions of A, B and  
C to suit each application. In general, A is  
essential, whereas B and C are highly  
recommended in ducted applications.  
6. Use approved wire for power connection from  
two pole terminal block of remote blower pack  
to additional two pole terminal block inside  
electrical section of humidifier.  
2. Field wiring from humidistat to humidifier and  
between devices should be 18 AWG or  
heavier and kept as short as possible.  
7. Use approved wire to connect the ground  
clamp of remote mounted blower pack to  
ground clamp provided in the electrical section  
of humidifier.  
3. Low voltage control terminal strips are  
provided in the electrical compartment.  
Internal sides are factory wired. External  
sides are to be field wired.  
LOW VOLTAGE CONTROL WIRING  
On-Off Controls  
4. Each humidifier is supplied with a wiring  
diagram inside.  
Figure #15  
D - Blower pack safeties  
CONTROL INSTALLATION  
External Wiring of On/Off Controls  
A
B
1. Mount any wall humidistat (control or high  
limit) over standard electrical box at height  
similar to typical thermostat. Any wall  
humidistat should be in location  
C
D
External  
representative of overall space being  
humidified and not in path of blower pack or  
air supply grille. Do not mount on a outside  
wall where temperature fluctuation can affect  
control response.  
10  
8
Internal  
Controls are available from NORTEC as  
accessories. If controls were not ordered with  
humidifier, they must be supplied by others. The  
following information is relevant to all controls, factory  
supplied or otherwise.  
2. Mount duct humidistat in location  
representative of overall air humidity, usually  
in the return duct. Do not mount it directly in  
front of steam distributor or in turbulent or  
mixing zone. Mount it where humidity and  
temperature are uniform and representative of  
spaces being humidified.  
A, B, C and D (described below) are to be wired in  
series (only one path for current) across terminals 8  
and 10 on the low voltage control terminal strip or  
replaced with a jumper wire for constant operation.  
Caution: this is the “hot” wire from the 24V control  
transformer; it will blow the 3A fuse if any control field  
wiring touches ground.  
3. Mount duct high limit humidistat  
downstream of steam distributors far enough  
that, under normal humidity and air flow  
- 9 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
temperature are uniform and representative of  
spaces being humidified.  
one of several control wiring diagrams. In all  
cases, modulating signal interfaces through  
control terminal strip to main pc board inside  
humidifier.  
3. Mount duct high limit humidistat  
downstream of steam distributors far enough  
that, under normal humidity and air flow  
conditions, steam will have been fully  
absorbed (typically at least 10 feet). It must  
be located to sense high humidity only when  
uniform and representative air is  
4. For set-point control at the humidifier an  
integrated controller can accept a direct  
transducer signal. The accuracy of the  
humidifier to changing conditions will be  
dependant on the accuracy of the signal.  
over-humidified or approaching saturation.  
5. The modulation signal must increase from  
minimum toward maximum as sensed RH  
(actual RH) drops below desired RH (%RH  
set-point). In response, humidifier’s steam  
output will increase from minimum toward  
maximum. When humidifier’s steam output  
(lbs/hr) matches humidification load (lbs/hr),  
modulation signal will stabilize.  
4. Mount duct air-proving switch so that it is  
able to sense air flow or lack of it. Wire it to  
make when air flow is sensed and break when  
air flow fails.  
5. Check operation of all on/off controls before  
starting humidifier.  
6. Calibration of controls (on/off or modulation) in  
the field may be necessary due to shipping  
and handling. Verify humidistat accuracy  
before commissioning system.  
6. Field-wiring connections for modulation control  
are to be made to external side of terminals  
28, 30 and 32 on humidifier’s control terminal  
strip. Always refer to the external control’s  
wiring diagram factory supplied with each  
NORTEC modulation control option.  
OPTIONAL MODULATION (CONTINUOUS  
CONTROLS)  
7. Varying dc Voltage Modulation Signal  
Powered by Others: NHSC / NHDI  
1. Read on/off controls section first since it is  
necessary to all control systems.  
humidifiers can be factory configured to accept  
the following vdc signals: 0-10 vdc, 0-20 vdc,  
1-5 vdc or 2-10 vdc. Wire according to  
NORTEC supplied external wiring diagram  
that comes with each modulation option. To  
share the signal with more than one  
2. Virtually any modulation (continuous control)  
external hardware by others (as long as it has  
%RH set-point circuitry) may be interfaced  
with pre-specified factory-configured pc board  
via the control terminal strip.  
humidifier, wire in parallel to each humidifier.  
If a different signal is desired consult factory.  
3. Modulation (continuous control) by others for  
use with NHSC / NHDI humidifiers involves  
8. Varying dc milliAmp (mA) Modulation  
Signal Powered by Others: NHSC / NHDI  
humidifiers can be factory-configured to  
accept a standard dc mA signal, if  
Figure #16  
Generalized Modulation Wiring  
pre-specified. Wire according to NORTEC  
supplied external wiring diagram that comes  
with each modulation option. Choose from  
0-20 dc mA or 4-20 dc mA. To share the  
signal with more than one humidifier consult  
factory.  
NHSC / NHDI SERIES  
CONTROL CIRCUIT TERMINAL BLOCK  
IMPORTANT: READ THESE INSTRUCTIONS CAREFULLY BEFORE CONNECTING CONTROL WIRING  
NOTE: See Included Diagram(s) For Accessory Wiring Instructions  
NHDI: Dry Points, rated 24 Vac/dc 1.0 Amps  
Other On/Off  
Devices  
max. resistive load per Indicator  
OPTIONAL REMOTE  
STATUS PCB  
Optional  
9.  
Varying Resistance (W) Modulation by  
Others: NHSC / NHDI humidifiers can be  
factory configured to power a 3-wire varying  
resistance modulation humidistat by others, if  
pre-specified. Wire according to NORTEC  
supplied external wiring diagram that comes  
with each modulation option. Choose from  
0-500W or up to 0-1000W. To share the signal  
with more than one humidifier consult factory.  
High Limit  
Humidistat  
Modulation Control  
See Diagram included  
with unit for details  
K1 Steam  
K2 Error  
Air Proving  
Switch  
K3 Service  
K4 Unit ON  
Control  
Humidistat  
Optional external remote  
indication. Any or all of these  
remote indications can be  
utilized. Refer to Trouble  
Shooting Manual for system  
status indication.  
NOTE: If no On/Off  
Control is used, then  
A field jumper must  
be connected across  
8 and 10 in order for  
humidifier to operate  
8
10  
32 30 28  
61  
- 10 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL MODULATION (CONTINUOUS  
CONTROL) PACKAGES BY NORTEC  
control board. The humidifier’s operating status is  
reported to the user by the green, red and yellow  
indicator lights on the front of the unit.  
1. Modulation (continuous control) “packages”  
are offered as accessories by NORTEC.  
Power supply comes from inside NHSC /  
NHDI humidifiers.  
The prerequisites for getting power and water into  
the steam cylinder are as follows:  
- On/off switch must be switched on.  
2. NORTEC provides the humidity set point  
circuitry and sensor(s) for wall or duct  
mounting or both as pre-selected when  
ordering the option. NORTEC offers several  
packages for NHSC / NHDI Series humidifiers.  
Wire according to NORTEC supplied external  
wiring that comes with each optional  
modulation package.  
- control circuit 8-10 must be made.  
- door interlock switch must be made (interlock switch  
can be pulled out to operate unit).  
- Modulating signal must be calling.  
- Internal safeties must be made over temperature  
switch and ground fault.  
3. Optional modulation packages without  
modulating safety high limit can use on-off  
safety high limit. Refer to on-off controls  
section.  
LEVEL REGULATION  
The water level in the steam tank is continuously  
monitored with the level unit.  
4. All versions can use on-off safety air proving  
switch. Refer to on-off controls section.  
The unit pulse fills based on steam production.  
The pulse filling in the unit varies depending on the  
water level detected by the float chamber.  
OPERATION  
One magnetic float monitors five different water  
levels in the float chamber. The second float ensures  
the water level is always above the heating elements.  
INTRODUCTION  
The NORTEC NHSC Series humidifier is a  
completely new design based on up-to-date  
technology. The NHSC is designed to provide clean  
steam humidification at an economical price.  
The pressure equalizing pipe between the steam  
connection and the level unit ensures that the water  
levels are the same in the steam tank.  
The NHSC uses a micro-computer control system  
for greater flexibility. The NHSC has a liquid crystal  
display (LCD) to indicate system messages and  
display RH.  
LAYOUT AND FUNCTION  
The NHSC humidifiers consist of a plumbing and  
an electric compartment. In every case there is at  
least one steam distributor (SD) for installation in air  
ducts or blower packs (remote mounted: RMBP) for  
direct space humidification.  
Water enters the steam cylinder through the  
bottom via the fill cup assembly when the 24 volt fill  
valve solenoid is energized. The water is heated via  
electric element and produces sterile steam for  
distribution into the air.  
Primary electric power is applied to the heating  
elements in the steam cylinder when the on/off switch  
is pushed on and all control options are calling. A  
primary to 24 volt step-down transformer provides  
power to the contactor holding coil(s) via the main  
- 11 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
• Ensure the valve on the NHSC mineral tank is  
closed.  
STEAM GENERATION REGULATION  
The steam is produced in the steam tank by  
resistive heating element technology. An external or  
the internal regulator for connection as required control  
the steam production fully variably from 3 to 100%.  
• Switch on the steam humidifier main switch.  
The steam humidifier carries out a system test.  
The display below appears and the three LEDs light  
for approx. 3 seconds.  
FLUSHING - NHSC ONLY  
test  
The evaporation process increases the  
concentration of minerals in the water of the steam  
cylinder. A suitable volume of water must be flushed  
through the steam cylinder from time to time and  
replaced by fresh water to ensure that this  
If a fault is detected during the system test, a  
corresponding fault message is triggered.  
If the system test is successful, the steam cylinder  
fills up and a float test is carried out (function check on  
the level unit). The display below appears.  
concentration does not exceed a specific value  
unsuitable for operation. The NHSC / NHDI steam  
humidifier performs a flush cycle. This consists of the  
following two forms of flushing.  
filling  
• Automatic flushing takes place as soon as the  
water in the steam cylinder exceeds the upper  
operating level (e.g. By foaming of the water).  
Note: If a fault is detected during the float test, an  
appropriate fault message is triggered  
• Flushing is a time dependent process at  
preselected time intervals.  
If the float test is successful, the NHSC / NHDI will  
be in normal operating mode. The display below  
appears and the green LED lights.  
Automatic or time-dependent flushing takes place  
based on the water quality and the operating data.  
The following procedure should be carried out only  
on the first occasion that the unit is operated:  
SCALE COLLECTOR TANK - NHSC ONLY  
NHSC/DI  
ready  
The minerals precipitated by the evaporation  
process accumulate at the bottom of the steam  
cylinder. Units designed for operation with untreated  
water are equipped with a scale collector tank located  
directly underneath the steam cylinder. This way the  
minerals do not accumulate in the steam cylinder but  
mainly in the collector tank thus extending the service  
intervals and reducing the maintenance costs.  
• Check the function of the steam humidifier:  
• Switch on the humidification by raising the set  
humidity value on the humidity controller /  
humidistat / NHSC / NHDI Display.  
• Switch off the humidification by lowering the set  
humidity value on the humidity controller /  
humidistat / NHSC / NHDI Display.  
NHSC / NHDI OPERATION  
• Check for correct functioning of the monitoring  
equipment (external safety network).  
STARTING OPERATION  
The following procedure should be carried out in order  
to operate the steam humidifier:  
• Set the desired humidity value on the humidity  
controller/humidistat.  
• Examine the steam humidifier and installation to  
ensure it has been installed properly or for  
possible damage.  
• Make sure no leaks are present.  
The heating current switches on as soon as the  
humidity controller/humidistat demands humidity. The  
yellow LED lights and steam is produced after a short  
delay (approx. 5 minutes).  
Caution! Damaged units and units with  
improper installation must not be operated.  
• Open the filter valve / shut-off valve in the water  
feed line.  
Operating status display on the unit  
• Switch on the external disconnect for the main  
supply (Heating and control voltage).  
The operating status is displayed in the LED on  
the unit as follows:  
- 12 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Green LED lit: Unit producing steam  
Yellow LED flashing: Major or minor servicing  
due. The relevant notice is shown in the display.  
Red LED flashing: There is a problem. The unit  
is trying to solve the problem. The relevant  
warning message appears in the display.  
Red LED lit: Insoluble problem. The relevant  
error message appears in the display.  
Optional Remote operating and fault indication  
If the steam humidifier is equipped with the  
optional remote operating and fault indication  
(option ”RFS”), the operating status will be shown as  
follows:  
K1  
Steam  
Error  
(N/O) Normally open  
K2  
(N/O) Normally open  
Or  
(N/C) Normally closed  
K3  
K4  
Service  
Unit On  
(N/O) Normally open  
Or  
(N/C) Normally closed  
(N/O) Normally open  
- 13 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Internal Controller  
INTERROGATION OF THE OPERATING  
STATUS  
Controller funct  
off  
The NHSC / NHDI operating and display unit has  
a “display menu” from which various operating  
parameters can be viewed.  
Internal controller activated (”on”)/deactivated  
(”off”)  
Working Hours  
Note: It is not possible to change the values on the  
display level.  
elapsed time  
623  
Operation  
Total of working hours elapsed since initial  
commissioning of the steam humidifier.  
Call up the display level with <ê> or <é>.  
<ê> next operating parameter.  
<é> previous operating parameter.  
Exit the display level with <Menu>  
Time Remaining to minor/major service  
time to mainten.  
600/1200  
The time remaining (in hours) before the next  
minor/major service.  
Description of the operating parameters on the  
display level  
Can be increased for poor water conditions or  
decreased for good water conditions.  
The following describes the individual operating  
parameters that can be selected using the keys <ê>  
and <é>, after the display level has been called up.  
Figure #17  
NHSC / NHDI Maintenance Intervals  
Steam Productions  
steam-prod[%]  
ref.=50/act=25  
Current actual and nominal value of steam  
production in percentage of total output.  
Nominal value: Unit capacity x input signal value.  
Actual value: max. Unit capacity x input signal  
value x capacity limitation.  
Note: If the internal controller is activated only the  
actual value is shown.  
Under the following conditions the actual value  
may differ from the nominal value: upon activation of  
the heating power, if capacity limitation is active during  
the filling cycle of the steam cylinder.  
Analog Input (humidity demand)  
Analog input [%]  
25  
Current value of the signal applied to the analog  
input in % of its max. value.  
Note: If the internal controller is active the  
displayed value corresponds to the current air humidity  
(%rh).  
- 14 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note: The stated times are based on 100% steam  
capacity. If the operation is at a lesser capacity, the  
time should be extended accordingly. The servicing  
intervals are set using the rotary switch “S2” on the  
control board.  
Note: Water quality conditions resulting in  
component failures are not covered under Nortec’s  
standard warranty.  
The factory settings are based on the following  
water conditions when the unit leaves the factory.  
Drain Cycle  
drain cycle  
4: 120  
Water  
NHSC  
NHDI  
Parameters  
The following indications are provided for the set  
flushing interval:  
Conductivity 0-1500 MicroMhos 0-50 MicroMhos  
Left: Switch setting on rotary switch “S1”  
Right: Set flushing interval  
Hardness  
Silica  
12 grains per gallon 0 grains per gallon  
(gpg) (gpg)  
12 parts per million 0 parts per million  
(ppm)  
Note: The flushing interval is set on switch “S1” on  
the control board.  
(ppm)  
PH  
6.5-7.5  
7
Figure #18  
NHSC / NHDI Drain Cycle Parameters  
Chlorides  
> 50 parts per mil- > 25 parts per mil-  
lion (ppm) lion (ppm)  
Value Settings  
Position Drain Interval At 100%  
S1  
0
Steam Capacity  
0 Min.  
Note: Should you have water conditions above the  
stated parameters consult the factory for a new  
blowdown setting to help improve your scale  
management.  
1
720 Min.  
360 Min.  
180 Min.  
120 Min.  
60 Min.  
2
3
4
5
6
30 Min.  
7
20 Min.  
Chlorides – High levels of chlorides will attack  
stainless steel. The solution would be to add an in-line  
carbon filter that will remove up to 99% of the  
8
10 Min.  
9
5 Min.  
Factory Settings  
NHSC - DI  
Model  
010  
NHSC(S1)  
NHDI (S1)  
chlorides. Consult the factory for additional information  
if your water contains high levels of chlorides.  
Setting  
Setting  
4
4
5
6
7
8
8
8
8
1
1
1
1
1
1
1
1
1
015  
020  
Nortec recommends performing a semi-annual  
water analysis to ensure optimal performance.  
030  
045  
065  
090  
Stand-by Heating  
135  
180  
stand-by heating  
off  
NHSC/NHDI  
Main Board  
Drain  
Interval (S1)  
Stand-by heating activated (”on”) deactivated  
(”off”).  
Note: If stand-by heating is active the water  
temperature in the steam cylinder is constantly kept at  
approximately 70ºC (158ºF) by the control board.  
LCD  
Display  
Example:  
4:120  
Capacity Limitation  
Position  
Duration between  
drain cycles  
power limit [%]  
100  
NOTE: Approximately 1 liter or  
0.26 gallons will drain during  
these intervals. Drain Water  
Cooling will be active during  
these intervals to temper the  
drain water to 140 degrees F (60  
degrees C) or less.  
The set capacity limitation as a percentage of the  
maximum capacity. Press both arrow keys at the  
same time and a code will appear. Enter 8808 using  
the arrow keys on the keypad and scroll down to the  
- 15 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
power limit screen. To change the power limit, simply  
press the down aroow key to desired capacity and  
press enter to save that new value. Press menu key  
to exit parameter screen.  
Soft Start  
Soft Start  
Off  
Soft Start activated (on), consult factory.  
Deactivated (off) factory set.  
Inlet Valve Correction  
inlet valve cor.  
130  
Demineral Mode  
Demineral Mode  
Off  
Set inlet valve correction (cycle ratio) in % of  
standard setting value to balance out water pressure  
variations.  
Demineral mode activated (on), consult factory.  
Deactivated (off) factory set.  
Figure #19  
Serial Interface  
NHSC / NHDI Control Interval  
Serial Interface  
Off  
Serial Interface activated (on), consult factory.  
Deactivated (off) factory set.  
Full Drain Cycle  
Full Drain Cycle activated (on), consult factory.  
Deactivated (off) factory set.  
Flush Cycle  
Flush Cycle  
Off  
Flush Cycle activated (on), consult factory.  
Deactivated (off) factory set.  
Control Signal  
analog signal  
0 - 5v (poti)  
Range of the active analog signal in V or mA,  
respectively.  
Note: The range of the analog signal may be  
adjusted using the rotary switch “S3” on the control  
board.  
Software Version  
software version  
VX.XX  
Current software version for the steam humidifier.  
- 16 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Type  
NOTES ON MAINTENANCE  
Figure #21  
machine type  
xxlb/xxxV  
Major Maintenance - NHSC / NHDI  
Warning: In order to eliminate faults, the steam  
humidifier must be switched off and secured against  
unintentional re-connection. Take care that the  
electricity supply to the main contactor is disconnected  
(check with voltage meter).  
NHSC Maintenance  
Complete cleaning  
(between 600 - 6000  
hours of operation)  
- Unit indicates cleaning is  
required.  
Only allow trained and qualified personnel to  
repair faults. Faults relating to electrical installation  
(e.g. change of unit fuse) must only be carried out by  
authorized personnel.  
- This cleaning normally occurs  
once a year(depends on water  
quality).  
- The scale collector tank and the  
stainless steel tank are removed  
and cleaned.  
Repair work and replacement of faulty  
components must only be carried out by your service  
technician!  
- Check all plumbing and  
electrical components for any  
issues.  
To safeguard reliable operation, the maintenance  
of the NHSC should be devised in three stages. A  
distinction is made here between periodic inspections,  
minor servicing and major maintenance of the  
steam-air humidifier.  
MAINTENANCE  
All maintenance work must be performed by  
adequately qualified and trained personnel familiar  
with the dangers involved. Ascertaining the  
qualifications is the customer’s responsibility.  
The intervals required between minor servicing  
and major maintenance depend on the water quality  
and the quality of steam generated and can be  
pre-selected on the rotary switch “S2” on the control  
board. After expiry of the selected interval, the yellow  
LED flashed and an appropriate message alternates  
with the normal operation indication.  
Instructions and details concerning the  
maintenance work must be observed and adhered to  
without fail.  
Only the type of maintenance work outlined in this  
documentation must be carried out.  
The following is an overview of the work that  
should be undertaken for the three maintenance  
stages.  
Figure #20  
Minor Servicing - NHSC ONLY  
Periodic Inspections  
When  
Work  
Once per week  
Inspect the water and steam  
installations for correct sealing and any  
possible damage.  
Inspect the drain line for soiling.  
Inspect the electrical installation for  
loose cables and damaged  
components.  
Inspect the humidifier for irregularities  
both external and internal.  
Use original spare parts exclusively to replace  
defective parts.  
Before maintenance is initiated, the steam  
humidifier must be taken out of operation in  
accordance with instructions in the manual and  
protected against unintentionally switching on the  
humidifier.  
- 17 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Minor Maintenance  
Work  
Carry out the periodic inspection items.  
Empty the steam tank.  
When  
The yellow LED flashes and the  
message “minor servicing due”  
appears, alternating with the normal  
operation indication.  
Clean the scale collector tank (NHSC  
Only).  
Work  
Carry out the periodic inspection items.  
Dismantle and clean the steam  
cylinder.  
Empty the steam cylinder and clean the  
scale collector tank.  
Dismantle and clean the liner (NHSC  
Only).  
Figure #22Scale Tank Removal  
Clean the unit inner chamber.  
Inspect the components inside the unit  
for damage.  
1.  
5.  
Resetting Minor and Major Maintenance  
3.  
In order to return the steam humidifier to normal  
operation after minor or major maintenance is  
complete, you must press and hold down the drain  
switch while turning the unit in the OFF position for  
approxiamately 10 seconds. Then turn the unit switch  
back onfor 10 seconds and release the drain switch  
and the LCD message will return to normal.  
2.  
4.  
1. Turn unit off.  
2. Drain unit and scale tank.  
3. Unlock support bracket by removing locking screws.  
4. Open both mechanisms by rotating counter clockwise until opening is visible.  
5. Place scale tank on support bracket.  
6. Rotate bracket to close mechanism and raise scale tank. Note ensure scale  
tank lines up with opening at the bottom of the drain pan when raising.  
7. Lock mechanism by re-inserting the two locking screws.  
DISMANTLING AND REASSEMBLY WORK  
Removal of the scale collector tank - NHSC Only  
Caution! Before commencing any dismantling  
work, the humidifier is to be taken out of operation as  
previously described.  
Major Maintenance  
NOTES ON CLEANING - NHSC Only  
When  
The yellow LED flashed and the  
message “major maintenance due”  
appears, alternating with the normal  
operation indication.  
Cleaning the steam cylinder, scale collector tank,  
and steam cylinder liner.  
Whenever possible, clean off any mineral coating  
that has formed.  
Wash parts with lukewarm soap suds and then  
rinse off well. Note: if the components are heavily  
scaled, place them in 8 percent formic acid until the  
scale has dissolved. Then treat components as  
previously described.  
Cleaning the heating elements  
Immerse cover with heating elements fitted to 1”  
(2 cm) below the rim of the cover in a container with 8  
percent formic acid. Ensure electrical wires do not  
make contact (do not fully submerge). Allow the acid  
to take effect until the scale coating has dissolved.  
- 18 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note: The heating elements do not have to be entirely  
free from scale.  
Turn on the humidifier with the unit switch.  
Continue to depress the blow-off pushbutton until  
the system test has finished (approx. 10 seconds).  
Then rinse heating elements thoroughly with fresh  
water.  
FAULT ELIMINATION  
Fault indication  
Warning! Ensure that the electrical connections  
remain dry.  
Warning! Do not remove scale coating on the  
heating elements with tools (screwdriver, scraper, etc.)  
or by striking. This could damage the heating  
elements.  
In case of malfunction during operation, the  
humidifier control checks whether there is a temporary  
problem (e.g. water supply interrupted for a short time)  
or whether it can resolve the problem by taking  
necessary measures. Such malfunctions set the unit  
into the “Alarm” status (fault elimination). The red  
LED flashes and an alarm message appears in the  
display alternating with the notice “recovering -  
please wait”.  
Cleaning the interior of the unit  
Wipe down components inside the unit with a  
damp cloth (clean water). Severely scaled  
components, e.g. the inlet funnel and the blow-off  
pump, should be cleaned using commercially available  
cleaning and descaling agents.  
Note: If the cause of the malfunction disappears of  
its own accord or if the controls can repair the  
malfunction, the alarm message will automatically  
switch off.  
Warning! The electrical connections and  
electronic components must remain dry.  
Note: If the unit is in display or setting level the  
alarm message in the display will be suppressed.  
Notes on Cleaning Agents  
Warning! Formic acid is harmless to the skin but it  
attacks the mucous membranes. Protect the eyes and  
respiratory tracts from contact with the acid and its  
vapor (wear goggles and work in a well ventilated  
room or outside).  
If the controller, after several attempts, fails to  
solve the problem (number of attempts depends on the  
type of malfunction) or if the problem obstructs further  
operation, the heating voltage is interrupted via the  
main contactor. The red LED stays lit and an error  
message appears in the display alternating with the  
notice “Please turn off unit”.  
The use of disinfectants is only permitted if they  
leave no toxic residues. The components must be  
rinsed thoroughly with water after cleaning in all cases.  
Note: If the unit is in the display or setting level the  
error message in the display will be suppressed.  
Caution! Do not use any solvents, aromatized  
or halogenized hydrocarbons, or other aggressive  
substances for cleaning purposes.  
The information and instructions regarding  
cleaning agents are to be strictly observed and  
implemented. In particular: Information relating to the  
protection of personnel, environmental conservation  
and restrictions regarding usage should be adhered to.  
In all cases, local regulations relating to  
environmental protection must be implemented.  
To reset the maintenance indication  
When maintenance work has been completed, the  
maintenance display can be reset as follows:  
Turn on the service switches in the main supply  
line.  
With the unit switched off depress and hold the  
drain switch.  
- 19 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T
- 20 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPLACING UNIT FUSES  
Open the plumbing door.  
3.  
4.  
5.  
6.  
Warning! Before replacing the unit fuse the  
steam humidifier must be switched off and  
secured against unintentional re-connection. Take  
care that the electricity supply to the main contactor is  
disconnected (check with voltage tester).  
Let unit tank cool down if needed.  
Remove steam hose by loosening gear clamp.  
Disconnect temperature switch. Note there is  
no polarity with this cable.  
Warning! Electronic components are very  
sensitive to electrostatic discharge. To protect these  
components, measures must be taken against  
damage from electrostatic discharge when replacing  
the unit fuse (ESD protection).  
Remove gear clamp and remove tank from the  
unit  
7.  
8. Undo cylinder tank strap and remove tank  
from unit.  
The unit fuses may only be replaced by trained  
and qualified personnel.  
9. Remove lid clamp, open lid and identify  
heating elements to be replaced.  
Important! If the unit fuse blows this is generally  
due to a faulty unit component. Therefore you should  
check these components before replacing the fuse  
(see table below).  
10. Remove the nut, washer, plug and gasket  
from the top of heating element you are  
replacing. Note: Save the hardware for  
installing the new heating element.  
Only use the correct type of fuse according to the  
following table.  
11. Note the heating element orientations, and  
remove heating element by pulling it down  
through the lid.  
Warning! It is not permitted to use repaired fuses.  
12. Place gasket from step 15 on new heating  
element and install new heating element by  
inserting it into the lid from the bottom  
ensuring orientation matches previous heating  
element.  
Fuse  
Specification  
Before replacing,  
check  
F1 on supply 6.3 A,  
module  
Drain pump (blocked  
or coil faulty)  
slow-acting  
13. Re-install gasket, plug, washer, and nut.  
Tighten assembly  
F2 on supply 1 A,  
module  
Inlet valve (blocked  
or coil faulty)  
quick-acting  
14. Connect element pins into the male connector  
by pushing in the pins and they should lock  
into place, pull to ensure.  
F5 on control 50mA,  
board  
Control signal  
quick-acting  
15. Ensure all heating element fastening nuts are  
tight.  
RESETTING FAULT INDICATION “ERROR”  
16. Re-install cylinder tank lid, clamp on cylinder  
and re-install the tank in the unit. Take care to  
ensure that the tank is level in the base and  
that the connecting components are aligned.  
In order to return the steam humidifier to operation  
after fault indication error, you must press and hold  
down the drain switch while turning the unit in the off  
position for approximately 10 seconds. Then turn the  
unit switch back on and release the drain switch after a  
10 second interval.  
17. Fasten the cylinder into position using the  
cylinder strap.  
HEATING ELEMENT REPLACEMENT  
INSTALLATION INSTRUCTIONS  
18. Re-connect steam hose and clamp to steam  
output coupling.  
19. Connect female connector to the male  
connector.  
Drain unit.  
1.  
2.  
Turn off the unit, and disconnect primary  
power to the unit.  
- 21 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure #23  
Element Pins  
Heating Element  
20. Connect temperature switch cable. Note: This  
cable is not polarity sensitive.  
21. Double-check all the connections.  
22. Turn the unit on.  
23. Allow unit to fill.  
24. Inspect unit operation and check for leaks.  
25. Close and lock plumbing door.  
- 22 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLE-SHOOTING  
Most operational malfunctions are not caused by faulty equipment but rather by improper installation or disregard  
for planning guidelines. Therefore, a complete fault diagnosis always involves a thorough examination of the entire  
system. Often, the steam hose connection has not been properly executed or the fault lies with the humidity control  
system. The following table gives a list of possible malfunctions, the appropriate alarm or error message, details of  
their cause, and notes on how to deal with each problem.  
Malfunction / Indication  
Cause  
Remedy  
Min. Filling time too short  
Error code: 1A/1B  
Water feed to steam cylinder heavily Carry out major servicing.  
calcified.  
Level in steam cylinder and level unit  
do not match.  
Alarm 1A  
filling time  
Error 1B  
filling time  
Internal safety chain interrupted  
Error code: 2A/2B  
Connection to over-temperature  
switch on steam cylinder broken or  
over-temperature switch faulty.  
Check connections or replace  
over-temperature switch.  
Alarm 2A  
safety chain int  
Steam cylinder overheating,  
over-temperature switch has  
responded.  
Inspect steam cylinder, clean if  
necessary. Replace over-temperature  
switch.  
Error 2B  
safety chain int  
Flat-band cable between control and Inspect connections, connect or  
power board interrupted or not  
connected.  
replace flatband cable.  
Max. Filling time exceeded (alarm  
message only)  
Water feed blocked (main water tap  
Check water feed, open main water  
closed, filter valve closed or blocked). tap, open or clean filter valve.  
Water pressure too low. Raise water pressure (range 1-10  
bar).  
Inlet valve does not open, filter sieve Inspect electrical connections and  
in Inlet valve blocked or inlet valve fuse F2 on supply module. Clean filter  
faulty. sieve or replace Inlet valve.  
Feed hoses into the steam humidifier Inspect hoses into unit and connect if  
Error code: 3A/3B  
Alarm 3A  
water supply  
not connected or kinked.  
necessary. Replace faulty hoses.  
Level unit not connected.  
Connect level unit.  
Float in the level unit sticking or level Clean or replace level unit.  
unit faulty.  
Max. Boil down rate too long  
Error code: 4A/4B  
Individual heating elements faulty.  
Replace faulty heating elements.  
Replace fuses on power board.  
Main voltage too low or failure of a  
phase (L1, L2 or L3).  
Check main voltage and  
connections.  
Alarm 4A  
steam time  
Steam line too long or not insulated. Maintain maximum line lengths  
(max. 15’). Insulate steam lines.  
Error 4B  
steam time  
Max. Drain time exceeded  
Error code: 5A/5B  
Drain pump not connected or faulty. Connect or replace drain pump.  
Outlet line from unit kinked or  
blocked.  
Inspect outlet line from unit, replace if  
necessary.  
Alarm 5A  
drain  
Water outlet blocked (external outlet Clean water outlet line and siphon.  
line or siphon blocked.  
Error 5B  
drain  
Hose to level unit blocked.  
Clean or replace hose.  
- 23 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Malfunction / Indication  
Cause  
Remedy  
Invalid level  
Level unit faulty.  
Replace level unit.  
Error code: 6A/6B  
Magnetic field in vicinity of level unit. Eliminate magnetic field.  
Alarm 6A  
level indicat  
Error 6B  
level indicat  
Steam pressure (error only)  
Error code: 7A/7B  
Steam hose blocked or restricted  
(water trap).  
Inspect steam hose, clean if  
necessary and install correctly.  
Pressure balance adapter into steam Remove adapter and clean opening  
with a needle.  
Alarm 7A  
communication  
connection fitting blocked.  
Duct pressure too high (>1500 Pa).  
Inspect ventilation settings.  
External safety chain interrupted  
Error code: none  
Ventilator lock open.  
Switch on ventilator/ventilation  
system.  
Automatic flow control has  
responded.  
Inspect ventilator/filter of ventilation  
system.  
safety chain  
external A  
Safties are open.  
Servicing, inspect system if  
necessary.  
mains failure  
B
Main failure on Unit B.  
Inspect voltage supply to Unit B.  
LEGEND  
A = Circuit 1  
B= Circuit 2 (double unit 2nd  
cylinder)  
- 24 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
- 25 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NHSC / NHDI Electric Steam Humidifier  
Humidifier Mandatory Pre-Start-up Checklist (p.1 of 2)  
Unit Serial #: _ _ _ _ _ _ _ _  
# of humidifiers: _____  
Tag:_____________  
Unit type: NHSC / NHDI  
Voltage: _____V/___ph  
Steam output: ____lbs./hr  
Customer/Job:_______________ Address: __________________________________________________  
Inspected by: _____________ Date of inspection: ___/___/___  
______________________________________________________________________________________________  
W
WATER QUALITY:  
- Well water r -City water r  
- Conductivity: _______mhmos  
-Softened water r  
- Hardness: _____gr.  
–Silica____ppm  
HUMIDIFIER MOUNTING:  
Clearances around the unit  
Acceptable  
3ft min r  
1ft min r  
1ft min r  
3ft min r  
2” min r  
Obstruction  
- Front (door opens freely?)  
- Top (steam lines)  
_______________  
____________________  
____________________  
____________________  
____________________  
- Bottom (fill, drain, controls)  
- Right (main pwr)  
- Left (main pwr)  
- Ensure the scale tank bracket is locked in place r  
STEAM LINES:  
CONDENSATE LINES:  
- Slopped back to drain r  
- Trapped 2” more than static duct pressure r  
- Size _______  
- Slope up 2” per 12” r  
- Slope down ½” per 12” r  
- Traps r  
- Insulated r  
- Length/Size ____________  
- 90 deg. elbows qty: ____  
- 45 deg. Elbows qty: ____  
- Can condensate be trapped anywhere in the steam line? Yes r no r  
WATER LINES:  
-½” at max 4ft from the unit  
- 3/8” connection at fill  
-water pressure: 30-80psig  
DRAIN LINES:  
-Air gap located within 3ft of the unit r - Slopped to drain r  
WIRING:  
-Size:________  
No loose wires around the unit or on the PC board? Yes r no r  
CONTROLS:  
Installed  
Location / Wiring /Setting  
_____________________  
_____________________  
_____________________  
_____________________  
- High limit:  
- Air proving:  
- Mod controller:  
- Other:  
r
r
r
r
POWER  
- Voltage, amperage rating and fuse corresponds to Spec Label r  
- Disconnect switch located close to humidifier r  
Field contact:___________________________ Signature:_______________________________  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NHSC / NHDI Electric Steam Humidifier  
Humidifier Mandatory Start-up Checklist (p. 2 of 2)  
Unit Serial #: _ _ _ _ _ _ _ _  
# of humidifiers: _____  
Tag: _____________  
Unit type: NHSC / NHDI  
Voltage: _____V/___ph  
Steam output: ____lbs./hr  
Customer/Job: _______________ Address: _________________________________________________  
Start-up by: _____________ Date of start-up: ___/___/___  
______________________________________________________________________________________  
1. PRELIMINARY:  
- Pre-start-up checklist completed? yes r no r  
If no, return to Pre-Start-up Checklist before going on with start-up procedure.  
2.START-UP PROCEDURE:  
The prerequisites for getting power and water into the steam cylinder are as follows:  
- check that main breaker is on and power is at the unit  
- check that main water shut-off valve is open  
- on/off/drain switch must be switched on  
- control circuit 8-10 must be made  
- modulation humidistat, if present, must be calling  
- door interlock switch must be made (interlock switch can be pulled out to operate unit)  
The unit will undergo a System Test to ensure integrity of all the components. If the test is successful, the unit  
will fill and the float test will be carried out. If everything ok, the green light will come on and the display will  
show NHDI or NHSC Ready.  
3. OPERATIONAL CHECK:  
-Switch on the humidification by raising the humidity set point on the humidistat/controller.  
-Switch off the humidification by lowering the humidity set point on the humidistat/controller.  
-Check for correct functioning of the external monitoring safeties such as air proving and high limit.  
-When check complete: Set the desired humidity level.  
Remarks:__________________________________________________________________________________  
__________________________________________________________________________________________  
__________________________________________________________________________________________  
__________________________________________________________________________________________  
__________________________________________________________________________________________  
__________________________________________________________________________________________.  
- 27 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NHSC / NHDI Electric Steam Humidifier  
Maintenance Checklist (p.1 of 2)  
Unit Serial #: _ _ _ _ _ _ _ _  
# of humidifiers: _____  
Tag: _____________  
Unit type: NHSC / NHDI  
Voltage: _____V/___ph  
Steam output: ____lbs./hr  
Customer/Job: _______________ Address: _________________________________________________  
Maintenance by: _____________ Date of maintenance:___/___/___  
______________________________________________________________________________________  
Type of maintenance:  
Periodic maintenance, once per week:  
- Inspect water and steam installation lines for leaks  
- Inspect drain lines for clogging  
- Inspect electrical installation for loose cables and damaged components.  
- Inspect the humidifier for damage.  
Minor servicing, when the yellow LED flashes and display indicates minor maintenance due:  
- Carry out periodic inspection items  
- Empty the steam cylinder and clean the mineral collector.  
Major servicing, when the yellow LED flashes and display indicates major maintenance due:  
- Carry out periodic inspection items  
- Empty the steam cylinder and clean the mineral collector.  
- Dismantle and clean the steam cylinder  
- Clean the unit inner chamber  
- Inspect the inside components for damage.  
Note: Time interval between minor and major are set through rotary switch #2 on the control board.  
Cleaning recommendations for the Steam cylinder, mineral collector tank (NHSC Only) and  
steam cylinder (NHSC Only) insert:  
-
-
-
-
Drain unit completely including mineral collector tank drain  
Remove lime collector tank, remove steam cylinder  
Whenever possible, chip off or scrape off any scale coating  
Wash and rinse parts with lukewarm soap water (If components are heavily scaled, place them  
in 8% formic acid until the scale has dissolved. Then treat components as previously described.)  
Cleaning recommendations for heating elements:  
- Wash and rinse heating with lukewarm soap water (If components are heavily scaled, place  
them in 8% formic acid until the scale has dissolved. Then treat components as previously described.)  
Warning: On no account remove scale coating on the heating element with tools or by striking. This  
could damage the heating element.  
Cleaning recommendations for internal plumbing components:  
- Wipe down components inside the unit with a damp cloth (clean water).  
- Severely scaled components should be cleaned using commercially available cleaning and  
de-scaling agents.  
Warning: Ensure electrical connections remain dry!!!  
For more information on cleaning agents and formic acid, review notes in the installation manual.  
- 28 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NHSC / NHDI Electric Steam Humidifier  
Maintenance Checklist (p.2 of 2)  
Note: In all cases, local regulations relating to environmental protection must be implemented.  
How to reset the maintenance indication:  
- Switch on the services in the main supply lines.  
- With the unit switch off, depress and hold the drain switch.  
- Switch on the steam humidifier with the unit switch  
- Continue to depress the drain button until the system test has finished (approx 10 sec.)  
Comments:  
________________________________________________________________________________________  
________________________________________________________________________________________  
________________________________________________________________________________________  
________________________________________________________________________________________  
________________________________________________________________________________________  
________________________________________________________________________________________  
- 29 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
- 30 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical Exploded View  
- 31 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
32  
39 40  
28  
27  
33  
35  
36  
34  
31  
30  
29  
37  
38  
26  
25  
1
2
24  
23  
22  
3
4
5
8
9
6
7
16  
12  
21  
20  
18  
10  
11  
19  
17 15  
13  
14  
- 32 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Plumbing Exploded View  
Capacity  
Voltage  
010/1  
015/1  
020/1  
030/1  
030/3  
045/3  
065/3 090/3 135/3 180/3  
Nortec PN Description  
1
2
1502644 Pump, Drain 24V 60 Hz  
1506286 Fill Valve DWC Assembly  
1455000 Gasket for Fill Thru Cabinet  
1505905 Drain Canal Gasket  
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
2
2
4
2
2
2
2
2
2
2
2
4
2
2
2
2
2
2
2
2
4
2
2
2
2
2
2
2
2
4
2
2
2
2
2
2
3
4
5
1502638 Drain Canal  
6
1505914 Scale Tank Bracket NHSC Only  
1505915 Scale Tank Assembly NHSC Only  
1508023 Ground Wire Door to Cabinet  
1502588 Bracket - Cabinet Large Cylinder  
1328860 Hose Fill Cup  
7
8
9
10  
11  
12  
13  
14  
15  
ORDER BY THE INCH  
1325035 Spring Clamp - Hose  
1502944 O-ring - NHDI Tank Base  
1505906 O-ring - NHSC Only  
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
4
2
4
2
4
2
4
2
O-ring 7 3/4" x 3/16 "  
1507780  
1505907 Base, Tank NHSC Only  
1502943 Base, Tank NHDI Only  
1502695 Hose 28 mm O.D.  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
17  
16  
18  
19  
20  
21  
22  
23  
24  
25  
ORDER BY THE INCH  
1502634 Clamp - 28 mm O.D. Hose  
1502642 Strap-Large Tank  
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
3
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
4
2
2
2
2
2
2
2
4
2
2
2
2
2
2
2
4
4
2
2
2
2
2
2
2
2
2
2
2
2
2
2
1502640 Tank-Large  
1502648 PCB, Water Level Sensor  
1507836 Cabinet Plumbing Door  
1853104 Lock Assembly  
1502647 Bracket-Float Chamber Mounting  
1505908 Liner, Plastic with Funnel, NHSC Only  
1507480 Element, Heating 11.25 LBS 208V  
1507479 Element, Heating 11.25 LBS 240V  
1507283 Element, Heating 11.25 LBS 480V  
1507284 Element, Heating 11.25 LBS 600V  
1507279 Element, Heating 15 LBS 208V  
1507280 Element, Heating 15 LBS 240V  
1507281 Element, Heating 15 LBS 480V  
1507282 Element, Heating 15 LBS 600V  
1502646 Float Chamber Assembly  
1502683 Gasket, Large Tank  
1
2
3
1
2
3
6
12  
1
2
3
6
12  
1
2
3
1
2
3
1
2
3
6
12  
1
1
1
1
1
1
1
2
1
2
1
1
1
1
1
1
2
1
3
1
1
1
1
1
1
2
1
6
1
1
1
1
1
1
2
1
12  
26  
27  
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
2
2
2
2
2
2
4
2
2
2
2
2
2
2
4
2
2
2
2
2
2
2
4
2
2
2
2
2
2
2
4
2
28  
1507849 Tank Lid Assembly  
29  
1502684 Switch - Temperature  
30  
1502641 Clamp - Large Tank  
31  
1508075 Steam Outlet  
32  
1508022 Gasket for Steam Outlet  
1328828 Clamp for Condensate Hose  
1328840 Hose 3/8" ID Condensate  
1325009 Clamp Hose For Large Steam Hose  
1508021 Hose - Steam Outlet  
33  
34  
ORDER BY THE INCH  
35  
2
1
4
1
1
1
5
6
6
1
1
2
1
4
1
1
1
5
6
6
1
1
2
1
4
1
1
1
5
6
6
1
1
2
1
4
1
1
1
5
6
6
1
1
2
1
4
1
1
1
5
6
6
1
1
2
1
4
1
1
1
5
6
6
1
1
2
1
4
1
1
1
5
6
6
1
1
2
1
4
1
1
1
5
6
6
1
1
2
1
4
1
1
1
4
6
6
1
1
2
1
4
1
1
1
4
6
6
1
1
2
1
4
1
1
1
4
6
6
1
1
2
1
4
1
1
1
4
6
6
1
1
2
1
4
1
1
1
4
6
6
1
1
2
1
4
1
1
1
4
6
6
1
1
2
1
4
1
1
1
4
6
6
1
1
2
1
4
1
1
1
4
6
6
1
1
2
1
4
1
1
1
3
6
6
1
1
2
1
4
1
1
1
3
6
6
1
1
2
1
4
1
1
1
3
6
6
1
1
2
1
4
1
1
1
3
6
6
1
1
2
1
4
1
1
1
3
6
6
1
1
2
1
4
1
1
1
3
6
6
1
1
2
1
4
1
1
1
3
6
6
1
1
2
1
4
1
1
1
3
6
6
1
1
2
1
4
1
1
1
0
6
6
1
1
2
1
4
1
1
1
0
6
6
1
1
2
1
4
1
1
1
0
6
6
1
1
2
1
4
1
1
1
0
6
6
1
1
4
2
8
2
2
2
0
4
2
8
2
2
2
0
4
2
8
2
2
2
0
4
2
8
2
2
2
0
36  
37  
1507812 Connector Housing  
38  
1508019 Fill Cup Assembly  
39  
1323091 Door Interlock Switch  
40  
1502637 Fill Valve - Double 1.2L/1.2L  
1502605 Plug, Heating Element Slot  
1502779 Gasket - Heating Element  
1507847 Flange - Lid Heating Element Top  
1505918 SS Tank Liner NHSC Only  
1502639 Drain Disk, Large Tank NHDI Only  
Not Shown  
Not Shown  
Not Shown  
Not Shown  
Not Shown  
Not Shown  
Not Shown  
Not Shown  
12 12 12 12  
12 12 12 12  
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
1704205 Compression Fitting Assembly 3/8" SST NHDI  
1639010 Compression Fitting Assembly 3/8" Brass NHSC  
1506288 Fitting Brass 3/4"  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
- 33 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
- 34 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
- 35 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED WARRANTY  
AxAir Nortec Inc. and/or AxAir Nortec Ltd. (hereinafter collectively referred to  
as THE COMPANY), warrant for a period of two years from date of shipment, that THE  
COMPANY’s manufactured and assembled products, not otherwise expressly  
warranted are free from defects in material and workmanship. No warranty is made  
against corrosion, deterioration, or suitability of substituted materials used as a result of  
compliance with government regulations.  
THE COMPANY’s obligations and liabilities under this warranty are limited to  
furnishing replacement parts to the customer, F.O.B. THE COMPANY’s factory,  
providing the defective part(s) is returned freight prepaid by the customer. Parts used  
for repairs are warranted for the balance of the term of the warranty on the original  
humidifier or 90 days, whichever is longer.  
The warranties set forth herein are in lieu of all other warranties expressed or  
implied by law. No liability whatsoever shall be attached to THE COMPANY until said  
products have been paid for in full and then said liability shall be limited to the original  
purchase price for the product. Any further warranty must be in writing, signed by an  
officer of THE COMPANY.  
THE COMPANY’s limited warranty on accessories, not of NORTEC’s  
manufacture, such as controls, humidistats, pumps, etc. is limited to the warranty of the  
original equipment manufacturer from date of original shipment of humidifier.  
THE COMPANY makes no warranty and assumes no liability unless the  
equipment is installed in strict accordance with a copy of the catalog and installation  
manual in effect at the date of purchase and by a contractor approved by THE  
COMPANY to install such equipment.  
THE COMPANY makes no warranty and assumes no liability whatsoever for  
consequential damage or damage resulting directly from misapplication, incorrect sizing  
or lack of proper maintenance of the equipment.  
THE COMPANY retains the right to change the design, specification and  
performance criteria of its products without notice or obligation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model # :_________________________  
Serial # :_________________________  
Cylinder # :_______________________  
Cylinder Last Replaced:  
_________________________  
MTH/DAY/YR  
_________________________  
MTH/DAY/YR  
_________________________  
MTH/DAY/YR  
Listed Humidifier  
E65185  
AxAir Nortec Inc.  
AxAir Nortec Inc.  
2740 Fenton Road  
826 Proctor Avenue  
Ogdensburg, NY 13669  
Ottawa, ON K1T 3T7  
A WMH COMPANY  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Multi Tech Systems Network Card MT2834ZDX User Manual
Murray Lawn Mower 387004x48A User Manual
National Instruments Network Card 371685C 01 User Manual
National Instruments Network Card FP QUAD 510 User Manual
NEC Switch N8406 022 User Manual
NETGEAR Network Router EX6120 User Manual
Nikon Marine Battery EN EL9 User Manual
Oliso Iron Touch Glide User Manual
Panasonic Cell Phone EB X400 User Manual
Panasonic Flat Panel Television 2007 2008 User Manual