Master Bilt Home Security System 19 14009 User Manual

Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)  
1598003200  
19-14009  
Walk-In Temp / Door /Alarm / Light Module  
1. GENERAL WARNINGS  
1.1 PLEASE READ BEFORE USING THIS MANUAL  
This manual is part of the product and should be kept close to the instrument for easy and quick  
reference.  
The instrument shall not be used for purposes different from those described hereunder. It cannot be  
used as a safety device.  
Check the application limits before proceeding.  
1.2  
SAFETY PRECAUTIONS  
Check if the supply voltage is correct before connecting the instrument.  
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden  
Temperature changes with high atmospheric humidity to prevent the formation of condensation.  
Warning: disconnect all electrical connections before performing any maintenance operation.  
Fit the probe where it is not damaged by the end-user. The instrument must not be opened.  
In case of failure or faulty operation send the instrument back to the distributor (see address) with a  
detailed description of the fault.  
Consider the maximum current that can be applied to each relay (see Technical Data).  
Ensure that the wires for probes, loads and the power supply are separated and far enough from each  
other, without crossing or intertwining.  
2. GENERAL DESCRIPTION  
Model XWA11V, 100x64 mm format, is a microprocessor based controller, suitable for temperature  
monitoring in a walk-in cooler or freezer. It is provided with two (2) relay outputs to control lights and  
signal an alarm. It is also provided with one (1) NTC probe input for temperature measurement. One (1)  
output allows the user to program the parameter list with the “Hot Key”.  
3. INTERFACE  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)  
1598003200  
5. PROGRAMMING  
5.1 HOW TO CHANGE A PARAMETER VALUE MAIN MENU  
1. Enter the Programming Mode by pressing the SET and DOWN key for 3s ( and  
start blinking).  
2. Select the required parameter.  
3. Press the “SET” key to display its value (now only the  
LED is blinking).  
4. Use UP” or “DOWN” to change its value.  
Press “SET” to store the new value and move to the following parameter.  
To exit: Press SET + UP or wait 15 s without pressing a key.  
NOTE: the set value is stored even when the procedure is exited, by waiting the time-out to expire.  
5.2 THE HIDDEN MENU (PR2)  
The hidden menu includes all the parameters of the instrument.  
5.2.1 HOW TO ENTER THE HIDDEN MENU (PR2)  
1. Enter the Programming Mode by pressing the Set + down key for 3s ( and  
starts blinking).  
2. When a parameter is displayed, release and re-press the SET + down for more than 7s.  
3. The Pr2 label will be displayed immediately followed from the HY parameter. NOW YOU ARE IN  
THE HIDDEN MENU.  
4. Select the required parameter.  
5. Press the “SET” key to display its value (Now only the  
LED is blinking).  
6. Use UP” or “down” to change its value.  
7. Press SET” to store the new value and move to the following parameter.  
To exit: Press SET + up or wait 15s without pressing a key.  
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.  
5.2.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND  
VICEVERSA  
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user  
level) by pressing “SET + down”.  
In HIDDEN MENU when a parameter is present in First Level the decimal point LED is on.  
5.3 HOW TO LOCK THE KEYBOARD  
1. Keep pressed for more than 3s the UP and DOWN keys.  
2. The “POF” message will be displayed and the keyboard will be locked. At this point it will be possible  
only to see the Set Point or the MAX o MIN Temp stored  
3. If a key is pressed more than 3s the “POF” message will be displayed.  
5.4 TO UNLOCK THE KEYBOARD  
Keep pressed together for more than 3s the UP and DOWN keys.  
6. LIGHT MANAGEMENT  
6.1 TIMED REGULATION: I1L = Y  
With i1L = y the light remains on at least for the LHt parameter.  
The LHt timer is re-initialized every time the light button is pushed.  
With LHt=0 the light remains on until the light button is pushed again.  
The light is switched on every time one of the following conditions happens:  
the door is open (i1F = dor)  
the presence sensor is activated (i2F = LHt)  
the light button is pushed  
The light is switched off when all the following conditions happen:  
the LHt timer is exhausted  
the door is closed (i1F = dor)  
the presence sensor is de-activated (i2F = LHt)  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)  
1598003200  
6.2 LIGHT BUTTON REGULATION: I1L = N  
The light button has a higher priority than digital inputs therefore:  
- if the light was switched on by button the digital input can not modify its status.  
- if the light was switched on by digital input, the light button can modify its status.  
7. INSTALLATION AND MOUNTING  
7.1 MOUNTING OF XWA11V – PR10000  
The XWA11V must be mounted on vertical  
panel.  
The Temp range allowed for correct  
operation is 32 – 140°F. Avoid installation is  
places subject to strong vibrations, corrosive  
gases, excessive dirt or humidity. The same  
recommendations apply to probes. Let the air  
circulate by the cooling holes.  
8. ELECTRICAL CONNECTIONS  
The instrument is provided with screw terminal blocks to connect cables with a cross section up to 2,5  
mm2 for the digital and analog inputs. Relays and power supply have a Faston connection (6,3mm). Heat-  
resistant cables have to be used. Before connecting cables make sure the power supply complies with  
the instrument requirements. Separate the probe cables from the power supply cables, from the outputs  
and the power connections. Do not exceed the maximum current allowed on each relay and in case of  
heavier loads use a suitable external relay.  
N.B. Maximum current allowed for all the loads is 20A.  
8.1 PROBE CONNECTIONS  
The probe shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It  
is recommended to place the thermostat probe away from air streams to correctly measure the average  
room temperature.  
9. USE OF THE PROGRAMMING “HOT KEY “  
The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the  
“Hot Key” and vice-versa.  
10. ALARM SIGNALS  
Message  
“P1”  
Mode  
Flashing  
Cause  
Outputs  
Alarm output ON  
Not changed  
Thermostat probe failure  
Keyboard locked  
Keyboard un-locked  
Maximum T° alarm  
Minimum T° alarm  
Door switch alarm  
External alarm  
PoF  
Pon  
“HA”  
“LA”  
“dA”  
“EA”  
“PAn”  
dEF  
Flashing (3s)  
Flashing (3s)  
Alternated with t  
Alternated with t  
Alternated with t  
Alternated with t  
Alternated with t  
Alternated with t  
Not changed  
Alarm output ON;  
Alarm output ON;  
Alarm output ON;  
Alarm output ON;  
Alarm output ON;  
Not changed  
Serious external alarm  
Defrost is running  
The alarm message is displayed until the alarm condition is reset.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)  
1598003200  
10.1 SILENCING BUZZER  
Once the alarm signal is detected the buzzer can be silenced by pressing the UP key.  
10.2 ALARM RECOVERY  
Probe alarms : “P1” (probe1 faulty), “P2” ; they automatically stop 10s after the probe restarts normal  
operation. Check connections before replacing the probe.  
T° alarms HA” and “LA” automatically stop as soon as the thermostat T° returns to normal values or  
when the defrost starts.  
Door switch alarm dA” stops as soon as the door is closed.  
External alarms EAL”, “BAL” stops as soon as the external digital input is disabled.  
11. TECHNICAL DATA  
Housing: self extinguishing ABS  
Case: face 100x64 mm; depth 45.5mm  
Mounting: J-box or wall-mount option  
Frontal protection: IP65  
Connections: ¼” fastons for power, 18” fastons for probes and Digital Inputs  
Power supply: 120Vac 10%, optional 230Vac 10%  
Power absorption: 4VA max.  
Display: 3 digits, red LED, 14,2 mm high.  
Inputs: 1 NTC probe  
Digital inputs: 2 free voltages  
Relay outputs: Dry Contacts  
Light: relay SPST 16A, 120Vac;  
Alarm: relay SPST 8A, 120Vac  
Other output: alarm buzzer  
Data storing: on the non-volatile memory (EEPROM).  
Measuring and regulation range:  
NTC probe: -40÷110°C (-58÷230°F)  
Resolution: 1 °F  
Accuracy : ±1 °F  
12. CONNECTIONS  
Back up  
(9VDC)  
1
2
3
4
5
6
7
8
8A  
250V  
16A 250V  
11 12 13 14 15 16 17 18 19  
L
N
Alarm C. Light C.  
Supply 120V~  
Power supply: 230Vac 10% models, use the same terminals of the 120Vac version.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)  
1598003200  
13. PARAMETER MAP  
LABEL  
DESCRIPTION  
Thermostat probe  
calibration  
VALUE  
LEVEL  
RANGE  
[-12,0°C <> 12,0°C] [-  
0
Pr2  
ot  
21°F <> 21°F]  
CF  
rES  
UT  
T° measurement unit  
Resolution (only °C)  
Display update  
F
in  
60  
y
Pr2  
Pr2  
Pr2  
Pr2  
°C(0) - °F(1)  
dE(0) - in(1)  
0 <> 255 (s)  
n(0) - Y(1)  
OnF  
Off function enabling  
°C[ ALL <> 150,0°] °F[  
ALL <> 302°]  
°C[ -50.0° <> ALU] °F[-  
58 <> ALU]  
50  
30  
Pr1  
Pr1  
ALU  
ALL  
High Tempalarm setting  
Low Temp alarm setting  
[0,1°C <>25,5°C] [1°F  
<> 45°F]  
2
Pr2  
Pr1  
Pr2  
AFH  
ALd  
Temp alarm differential  
Temp alarm delay  
Delay of Temp alarm at  
start-up  
Alarm delay at the end  
of defrost  
Delay of Temp alarm  
after closing the door  
Light timer  
Open door alarm delay  
First relay configuration  
Second relay  
30  
1.3  
0 <> 255 (min.)  
dAo  
EdA  
0 <> 24H0(144)  
0 <> 255 (min.)  
30  
15  
Pr2  
Pr2  
dot  
LHt  
doA  
OA1  
0 <> 255 (min.)  
0 <> 255 (min.)  
0 <> 255 (min.)  
15  
15  
ALr  
Pr1  
Pr1  
Pr2  
ALr(0) - LHt(1) - OnF(2)  
LHt  
Pr2  
oA2  
AOP  
i1P  
configuration  
ALr(0) - LHt(1) - OnF(2)  
OP - CL  
Alarm relay polarity  
Digital input 1 polarity  
Door switch to turn light  
ON  
Digital input 1 operating  
mode  
Digital input 2 polarity  
Digital input 2 operating  
mode  
oP  
oP  
Pr2  
Pr2  
OP(0) - CL(1)  
y
Pr2  
i1L  
n(0) - Y(1)  
EAL(0) - dor(1) - dEr(2)  
- LHt(3)  
dor  
Pr2  
Pr2  
Pr2  
i1F  
i2P  
cL  
PA  
n
OP(0) - CL(1)  
EAL(0) - Pan(1) -  
dFr(2) - LHt(3)  
i2F  
Time interval/delay for  
digital input alarm  
Alarm relay disabling  
Kind of probe  
Real T° Probe 1  
FW release  
0
Pr2  
did  
tbA  
PbC  
dP1  
rEL  
Ptb  
0 <> 255 (min.)  
n(0) - Y(1)  
PtC(0) - ntC(1)  
(probe value)  
read only  
n
ntc  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Parameter map  
read only  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)  
1598003200  
14. PARAMETER LIST  
Ot  
Thermostat probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offset of the  
thermostat probe.  
CF T measurement unit: °C = Celsius; °F = Fahrenheit. When the measurement unit is changed the  
Set Point and the values of some parameters have to be modified.  
rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display.  
Ut  
Display update: The time delay of the T readout (0÷255s)  
onF Off function enabling: n = off function disabled; y = off function enabled;  
ALU High T° alarm setting: (ALL ÷ 150°C or 302°F);  
when this T° is reached and after the ALd delay time the HA alarm is enabled.  
ALL Low T° alarm setting: (- 50°C or -58°F ÷ ALU)  
when this T° is reached and after the ALd delay time, the LA alarm is enabled,.  
AFH T° alarm differential: (0,1÷25,5°C; 1÷45°F) differential for T° alarm Set Point and fan regulation Set  
Point, always a positive value  
ALd T° alarm delay: (0÷255 min) time interval between the detection of an alarm condition and the  
corresponding alarm signaling.  
dAO Delay of T° alarm at start-up: (0min÷23h 50min) time interval between the detection of the T°  
alarm condition after the instrument power on and the alarm signaling.  
EdA Alarm delay at the end of defrost: (0÷255 min) Time interval between the detection of the T° alarm  
condition at the end of defrost and the alarm signaling.  
dot Delay of T° alarm after closing the door: (0÷255 min) Time delay to signal the T° alarm  
condition after closing the door.  
LHt Light timer: (0-255 min) The time the light will stay on after pressing the light switch on the  
keyboard.  
doA Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and its  
alarm signaling: the flashing message “dA” is displayed.  
oA1 First relay configuration: (14-15): ALr = alarm; LHt = light; onF = on/off relay  
oA2 Second relay configuration: (14-16): ALr = alarm; LHt = light; onF = on/off relay  
AOP Alarm relay polarity: cL = closing contacts; oP = opening contacts.  
i1P Digital input 1 polarity (1-2): CL : the digital input is activated by closing the contact;  
OP the digital input is activated by opening the contact  
i1L Door switch to turn light ON(1-2): (y / no) To turn the light ON automatically when the door is  
open. The light will turn off based on LHt . Keyboard switch must be turned ON first.  
i1F  
Digital input 1 operating mode(1-2): EAL = external alarm; dor = door switch; dFr = A defrost is  
running; LHt = keep light ON (signal from occupancy sensor) override LHt.;  
i2P Digital input 2 polarity (1-3): CL : the digital input is activated by closing the contact;  
OP the digital input is activated by opening the contact  
i2F Digital input 2 operating mode: configure the digital input function:  
EAL = External alarm;  
PAn =Panic alarm;  
dFr = A defrost is running;  
LHt = Keep light ON (signal from occupancy sensor) override LHt.  
did Time interval/delay for digital input alarm:(0÷255 min.) If I2F=EAL or PAn (external alarms), “did”  
parameter defines the time delay between the detection and the successive signaling of the alarm.  
tbA Alarm relay & Buzzer disabling: (y ; no)  
Pbc Type of probe (PTC, NTC)  
dP1 Probe 1 T  
rEL Software release for internal use.  
Ptb Parameter table code: read only.  
15. PARTS LIST  
M/B Part Number  
19-14009  
Description  
WI therm, alarm, panic light, contl. #XWA11V-4N1F0  
PROBE, 18NB-NTC-1.5M, (5')  
19-14012  
19-14013  
PROBE, 18NB-NTC-1.5M, (50')  
19-14014  
PROBE, 18NB-NTC-1.5M, (75')  
For more information, please contact our Technical Service Dept.  
@ 1-800-684-8988  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  

La Crosse Technology Clock WS 8053U User Manual
Lenovo Tablet 08622KU User Manual
Life Fitness Treadmill M051 00K26 A261 User Manual
Locke Lawn Mower TVM 3077 User Manual
Magic Chef Beverage Dispenser MCWC8DCT2 User Manual
Magnavox Flat Panel Television 20MF200V User Manual
Magnavox VCR VRT642 User Manual
Master Bilt Refrigerator TAF 27 ERC2 User Manual
Mellerware Electric Shaver 20610 User Manual
Microsoft Network Router TM 1104 3 User Manual