MGE UPS Systems Power Supply Pulsar Esprit 3135 kVA User Manual |
Pulsar Esprit
3–13.5 kVA
High Availability UPS for Internet Servers
Advanced Features
◗ High availability power
+ maximum reliability =
MGE Power Cluster
◗ Web-based management
using XML
◗ Standard USB
communications
◗ Seamless integration
with Microsoft
Windows 2000
◗ Redundant battery
back-up potential
MGE UPS SYSTEMS all new Pulsar Esprit has been specifically
designed to meet the needs of Internet Service Providers & Application
Service Providers. Esprit provides total power availability with redundant
UPSs for the price of a regular, single UPS. This redundant combination,
called Power Cluster, has been pioneered exclusively by MGE.
◗ Redundant
battery chargers
(with additional batteries)
Pulsar Esprit has been designed with the Internet in mind:
For the first time, it is possible to remotely monitor an UPS using
XML tags to perform automatic actions. This breakthrough technology
is the result of MGE's heavy investment in research and development.
They provide ISPs with the best combination of power availability
and cost. With the revolutionary Esprit Power Cluster, MGE brings
affordable, total power availability to smaller ISPs and mid-size
businesses with 3 to 15 servers.
◗ Plug-in convenience
up to 8.5 kVA
◗ Can be installed by
non-technical personnel
◗ Capable of long
duration backup
Pulsar Esprit World First. . .
◗ First high availability UPS with maximum reliability
at an affordable cost (Power Cluster)
◗ First UPS with infinitely expandable batteries
◗ First UPS to provide “redundant hot swap” battery capability
◗ First server-grade UPS with built-in USB communications
◗ First UPS in its class with HID protocol for seamless
integration with Windows 2000
◗ First UPS managed with XML tags
Download from Www.Somanuals.com. All Manuals Search And Download.
Easy Connections and Installation
Plug-In convenience up to 9 kVA
Simple installation: simply plug
the system in, up to 9 kVA
Electronic Module
(Esprit 3.1)
Esprit 3.1
Esprit 4.5
Esprit 6
Esprit 9
(L5-30)
(5-50)
(L14-30)
(14-50)
Multiple
Rack Mounting
Communications ports
◗ RS232 port
Esprit’s unique design lets you stack up
electronic and battery modules as you
want (up to 3 max.). A 5U rack mount
kit that can accommodate 2 modules
is available as
◗ USB port
an option.
Redundant battery path
Versatile output receptacles
Various combinations of
receptacles make it easy to
connect any type of
Each UPS is equipped with two
battery connectors:
◗ Battery modules are user
hot-swappable with no risk of
power interruption during
the exchange
server to your Esprit
Stacking
◗ Parallel battery modules avoid the
single point of failure generated by
daisy-chained battery modules.
Recessed
front and back
handles for
easy installation
Infinite battery runtime
You can “parallel daisy chain” as
many battery modules as needed.
Multiple chargers
Each battery module includes
its own internal charger:
◗ Fast recharge for any
battery runtime
◗ A faulty charger doesn't
prevent the recharge of
the other battery strings.
Comprehensive Display and Controls
Fault detected
Replace battery
Battery charging
Overload
On Utility
On Battery
Battery Module
Alarm Reset
Enable UPS
Disable UPS
Download from Www.Somanuals.com. All Manuals Search And Download.
Internet-Grade Monitoring and Communications
All Esprit models come standard with built-in communications capabilities using either an RS232 or USB port. UPS-to-server
communications is essential to secure the operation of your operating system during an extended power failure. The UPS will
signal the O/S when its batteries are almost depleted to launch an orderly, graceful shutdown process to make sure all files are
protected. This feature is vital for systems running unattended, such as Web servers.
Esprit communication is based on
the new Microsoft's HID protocol, which
will become the
Operating Systems Supported
Win 98 SE / Windows 2000
Win 95 OSR2 / NT 3.51 & 4
Linux RedHat 5.2 kernel 2.0.x
Linux RedHat 6.0 kernel 2.2
Netware 3.12, 4.12, 5.0
SCO 5.0x
RS232
USB
standard for any
device interfaced
with Windows
2000. By already implementing this
industry standard, MGE offers seamless
integration and faster, more reliable
communications to its customers.
Unixware 7.x
Web-based Management Using XML
MGE UPS SYSTEMS is currently chairing the W3C UPS industry workgroup, which will define an industry standard for power
management over the Web. XML will quickly replace HTML as the protocol of choice for web-based management. HTML
can only display information in a browser, it cannot easily send the data to another piece of software to perform an automatic
action such as triggering a shut down command of the system or paging an administrator. MGE's XML-@gent runs on a
Windows NT/2000 server and constantly monitors the status of the incoming power, publishing browser alerts during a power
problem to all subscribing web-enabled nodes. MGE is the first UPS to offer Web-based management using the new XML/XSL
(Extended Mark-up Language/Extended Style Language) specification for data communications
Windows
MGE has been partnering for several years with Microsoft to co-develop
power management interfaces for Windows products. As a result, Windows 2000
will ship with a dedicated power panel for MGE's Esprit product. Simply connect
your UPS to the PC and Windows 2000 will install automatically all the drivers to
secure your operating system and its files during a power failure.
power management software is available for
Windows 95/98/NT 4 and 2000 & is fully Plug & Play.
MGE
Linux MGE's popular Solution-Pac power
management software is available for
Linux. It provides a simple way to secure
the operation of multiple Web servers
during a power outage.
SNMP Management
Enterprise users can take advantage of the extensive TCP/IP-based
communications offering developed by MGE.
UM Switch
Features include:
◗ Remote management from an NMS platform such as
HP OpenView, CA Unicenter TNG, SunNetManager and more
◗ Shutdown of multiple servers running different operating systems
MultiSlot Communication Expander
◗ Perform automatic actions based on power events such as paging
the network administrator or sending an eMail
UM Sensor
◗ Reboot a locked up server remotely using the UM Switch power controller (option)
◗ Monitor the temperature and humidity of the computer room with the UM Sensor environmental module (option)
Connection to the network is achieved through an Ethernet/SNMP card that fits into the MultiSlot Communication Expander.
The multiple slots available let you manage 2 or 3 redundant Esprit UPSs as one single system over the network.
Download from Www.Somanuals.com. All Manuals Search And Download.
Select the Esprit you need for your Web Servers
Power Cluster
(for servers with 2 redundant power supplies*)
Model
Single UPS
◗ 3-server protection
◗ 3-server protection
Esprit 3.1
◗ 3.0 kVA
◗ 3.0 kVA
◗ 5U (in rack)
◗ 10U (in rack)
◗ Expand load to 6 kVA
(with no redundancy)
◗ 5-server protection
◗ 5-server protection
Esprit 4.5
Esprit 6
Esprit 9
◗ 4.5 kVA
◗ 4.5 kVA
◗ 5U (in rack)
◗ 10U (in rack)
◗ Expand load to 9 kVA
(with no redundancy)
◗ 6-server protection
◗ 6-server protection
◗ 6 kVA
◗ 6 kVA
◗ 10U (in rack)
◗ Expand load to 12 kVA
(with no redundancy)
◗ 9-server protection
◗ 9-server protection
◗ 8.5 kVA
◗ 8.5 kVA
◗ 10U (in rack)
◗ Expand load to 17 kVA
(with no redundancy)
◗ 15-server protection
◗ 15-server protection
Esprit 13.5
◗ 13.5 kVA
◗ 13.5 kVA
◗ 15U (in rack)
◗ 3 to 1 interface
◗ Expand load to 27 kVA
(with no redundancy)
◗ 3 to 1 interface
* For servers with 3 redundant power supplies, add additional Esprit UPS.
Scalable Battery Runtimes (in Minutes)
Standard
2 Batteries
3 Batteries
4 Batteries
5 Batteries
6 Batteries
13
30
54
75
108
126
Esprit 3.1
Esprit 4.5
Esprit 6
8
22
4 Batteries
30
34
6 Batteries
54
42
8 Batteries
75
54
10 Batteries
108
72
12 Batteries
126
Standard
13
8
22
34
42
54
72
Esprit 9
Notes:1Example above requires adding one additional battery module to an Esprit 4.5 & will provide 22 minutes of runtime at full load. 2For Esprit 6 & 8.5 kVA, battery modules must be added in pairs.
Download from Www.Somanuals.com. All Manuals Search And Download.
Pulsar Esprit
Specifications
Dimensions
and Weights
Esprit 13.5
Power Cluster
Esprit 4.5
Single UPS
Dimensions
Power Cluster (for servers with 2 redundant power supplies)
Model
Weight
(lbs.)
Dimensions
Weight
WxHxD (in.)
WxHxD (in.) each
(lbs.) each
Esprit 3.1
Esprit 4.5
Esprit 6
Electronic
Battery
Electronic
Battery
Electronic
Battery
Electronic
Battery
1 ea. 8.5" x 7.25" x 19"
1 ea. 8.5" x 7.25" x 19"
1 ea. 8.5" x 7.25" x 19"
1 ea. 8.5" x 7.25" x 19"
1 ea. 17" x 7.25" x 19"
2 ea. 8.5" x 7.25" x 19"
1 ea. 17" x 7.25" x 19"
2 ea. 8.5" x 7.25" x 19"
3 ea. 8.5" x 7.25" x 19"
3 ea. 8.5" x 7.25" x 19"
20
80
20
80
40
80
40
80
20
80
20
2 ea. 8.5" x 7.25" x 19"
2 ea. 8.5" x 7.25" x 19"
2 ea. 8.5" x 7.25" x 19”
2 ea. 8.5" x 7.25" x 19"
2 ea. 17" x 7.25" x 19"
4 ea. 8.5" x 7.25" x 19"
2 ea. 17" x 7.25" x 19"
4 ea. 8.5" x 7.25" x 19"
6 ea. 8.5" x 7.25" x 19"
6 ea. 8.5" x 7.25" x 19"
2 ea. 19” x 4” x 5.1”
20
80
20
80
40
80
40
80
20
80
20
Esprit 9
Esprit 13.5❊ Electronic
Battery
3to1Interface 1 ea. 19” x 4” x 5.1”
❊Esprit 13.5 consists of 3 each Esprit 4.5 plus 1 3 to 1 interface
Sizing Guide and
Battery Runtimes
3 PC
4 PC
5 PC
6 PC
2 RISC
9 PC
12 PC
15 PC
servers
servers
servers
servers
servers
servers
servers
servers
Single UPS
Esprit 3.1
Esprit 4.5
Esprit 6
17
20
45
48
100
12
26
33
70
8
18
22
55
15
20
47
13
15
40
Esprit 9
10
25
Esprit 13.5❊
18
13
Note: In a Power Cluster configuration, the battery runtimes given above will double.
Characteristics
Esprit 3.1
Esprit 4.5
Esprit 6
Esprit 9
Electrical
Power (VA/W)
3000/2016
4500/3150
6000/4032
8500/6000
Input voltage range
Output voltage range
Output frequency regulation
Surge protection
Efficiency (on battery)
Waveform
100/120/127 Volts +10% -15%
100/120/127 Volts
100/120/127 Volts +10% -15% 208/220/240 Volts+10%-15%
208/220/240 Volts+10%-15%
100/120/127 Volts
50/60 Hz +/- 0.5 Hz
420 joules
100/120/127/200/208/220/240 Volts
420 joules
> 94%
630 joules
> 94%
630 joules
> 94%
> 94%
❊❊
Compatible with multiple server-grade, Power Factor Corrected (PFC) power supplies
Batteries
Number and type
Recharge time
12 x 12V/7Ah
4 hours to 80%
4-5 years
12 x 12V/7Ah
4 hours to 80%
4-5 years
24 x 12V/7Ah
4 hours to 80%
4-5 years
24 x 12V/7Ah
4 hours to 80%
4-5 years
Battery life expectancy
User connections
Input power cord
Output receptacles
Communication ports
Software included
Environment
6 feet w/ L5-30P
L5-30 & 4 x 5-15
6 feet w/ 5-50P
5-50 & 4 x 5-15
1xRS232 & 1xUSB
6 feet w/ L14-30P
L14-30, L6-30 & 6 x 5-15
6 feet w/ 14-50P
14-50, L6-30 & 6 x 5-15
Solution-Pac Power Management suite
Safety
Surge protection
Noise level
Operating temperature
Manufacturer certifications
Warranty
Warranty extension (option)
Environmental
❊❊Independent test lab report available on MGE’s web site
UL, cUL 1778
ANSI C62.41
45 dBA max.
32-105 F
FCC, ISO 9001
2 years, parts and labor electronics (battery modules:1year)
3 years, parts and labor incl. batteries
Recyclable components, packing & documentation, recycled materials, used battery recovery
MGE GREEN SWEEP
Call MGE to return your UPS for free
recycling to a US EPA-certified recycling
center and help protect our environment.
MGE UPS SYSTEMS
BRAZIL
Avenida Guido
ARGENTINA
Thames 91
1609 San Isidro
Prov de Buenos Aires
tel (54) 11-4766-8777
fax (55) 11-4766-6008
USA (headquarters)
1660 Scenic Avenue
Costa Mesa, CA 92626
CANADA
#9, 2798 Thamesgate Dr.
Mississauga, ON L4T 4E8
tel (905) 672-0990
(877) 672-0990
Caloi 1985 (GALPAO 23)
Guarapiranga
Sao Paulo - SP, CEP 05802
tel (55) 11-5890-3323
fax (55) 11-5890-3353
esprit 101
Effective: April 2000
tel
(800) 523-0142
(714) 557-1636
(714) 557-9788
fax
fax (905) 672-7667
©MGE UPS SYSTEMS, Inc. All specifications subject to change without notice. The MGE UPS SYSTEMS logo is a trademark of MGE UPS SYSTEMS.
Download from Www.Somanuals.com. All Manuals Search And Download.
|