MGE UPS Systems Power Supply Pulsar Esprit 3135 kVA User Manual

Pulsar Esprit  
313.5 kVA  
High Availability UPS for Internet Servers  
Advanced Features  
High availability power  
+ maximum reliability =  
MGE Power Cluster  
Web-based management  
using XML  
Standard USB  
communications  
Seamless integration  
with Microsoft  
Windows 2000  
Redundant battery  
back-up potential  
MGE UPS SYSTEMS all new Pulsar Esprit has been specifically  
designed to meet the needs of Internet Service Providers & Application  
Service Providers. Esprit provides total power availability with redundant  
UPSs for the price of a regular, single UPS. This redundant combination,  
called Power Cluster, has been pioneered exclusively by MGE.  
Redundant  
battery chargers  
(with additional batteries)  
Pulsar Esprit has been designed with the Internet in mind:  
For the first time, it is possible to remotely monitor an UPS using  
XML tags to perform automatic actions. This breakthrough technology  
is the result of MGE's heavy investment in research and development.  
They provide ISPs with the best combination of power availability  
and cost. With the revolutionary Esprit Power Cluster, MGE brings  
affordable, total power availability to smaller ISPs and mid-size  
businesses with 3 to 15 servers.  
Plug-in convenience  
up to 8.5 kVA  
Can be installed by  
non-technical personnel  
Capable of long  
duration backup  
Pulsar Esprit World First. . .  
First high availability UPS with maximum reliability  
at an affordable cost (Power Cluster)  
First UPS with infinitely expandable batteries  
First UPS to provide “redundant hot swap” battery capability  
First server-grade UPS with built-in USB communications  
First UPS in its class with HID protocol for seamless  
integration with Windows 2000  
First UPS managed with XML tags  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Easy Connections and Installation  
Plug-In convenience up to 9 kVA  
Simple installation: simply plug  
the system in, up to 9 kVA  
Electronic Module  
(Esprit 3.1)  
Esprit 3.1  
Esprit 4.5  
Esprit 6  
Esprit 9  
(L5-30)  
(5-50)  
(L14-30)  
(14-50)  
Multiple  
Rack Mounting  
Communications ports  
RS232 port  
Esprits unique design lets you stack up  
electronic and battery modules as you  
want (up to 3 max.). A 5U rack mount  
kit that can accommodate 2 modules  
is available as  
USB port  
an option.  
Redundant battery path  
Versatile output receptacles  
Various combinations of  
receptacles make it easy to  
connect any type of  
Each UPS is equipped with two  
battery connectors:  
Battery modules are user  
hot-swappable with no risk of  
power interruption during  
the exchange  
server to your Esprit  
Stacking  
Parallel battery modules avoid the  
single point of failure generated by  
daisy-chained battery modules.  
Recessed  
front and back  
handles for  
easy installation  
Infinite battery runtime  
You can “parallel daisy chain” as  
many battery modules as needed.  
Multiple chargers  
Each battery module includes  
its own internal charger:  
Fast recharge for any  
battery runtime  
A faulty charger doesn't  
prevent the recharge of  
the other battery strings.  
Comprehensive Display and Controls  
Fault detected  
Replace battery  
Battery charging  
Overload  
On Utility  
On Battery  
Battery Module  
Alarm Reset  
Enable UPS  
Disable UPS  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Internet-Grade Monitoring and Communications  
All Esprit models come standard with built-in communications capabilities using either an RS232 or USB port. UPS-to-server  
communications is essential to secure the operation of your operating system during an extended power failure. The UPS will  
signal the O/S when its batteries are almost depleted to launch an orderly, graceful shutdown process to make sure all files are  
protected. This feature is vital for systems running unattended, such as Web servers.  
Esprit communication is based on  
the new Microsoft's HID protocol, which  
will become the  
Operating Systems Supported  
Win 98 SE / Windows 2000  
Win 95 OSR2 / NT 3.51 & 4  
Linux RedHat 5.2 kernel 2.0.x  
Linux RedHat 6.0 kernel 2.2  
Netware 3.12, 4.12, 5.0  
SCO 5.0x  
RS232  
USB  
standard for any  
device interfaced  
with Windows  
2000. By already implementing this  
industry standard, MGE offers seamless  
integration and faster, more reliable  
communications to its customers.  
Unixware 7.x  
Web-based Management Using XML  
MGE UPS SYSTEMS is currently chairing the W3C UPS industry workgroup, which will define an industry standard for power  
management over the Web. XML will quickly replace HTML as the protocol of choice for web-based management. HTML  
can only display information in a browser, it cannot easily send the data to another piece of software to perform an automatic  
action such as triggering a shut down command of the system or paging an administrator. MGE's XML-@gent runs on a  
Windows NT/2000 server and constantly monitors the status of the incoming power, publishing browser alerts during a power  
problem to all subscribing web-enabled nodes. MGE is the first UPS to offer Web-based management using the new XML/XSL  
(Extended Mark-up Language/Extended Style Language) specification for data communications  
Windows  
MGE has been partnering for several years with Microsoft to co-develop  
power management interfaces for Windows products. As a result, Windows 2000  
will ship with a dedicated power panel for MGE's Esprit product. Simply connect  
your UPS to the PC and Windows 2000 will install automatically all the drivers to  
secure your operating system and its files during a power failure.  
power management software is available for  
Windows 95/98/NT 4 and 2000 & is fully Plug & Play.  
MGE  
Linux MGE's popular Solution-Pac power  
management software is available for  
Linux. It provides a simple way to secure  
the operation of multiple Web servers  
during a power outage.  
SNMP Management  
Enterprise users can take advantage of the extensive TCP/IP-based  
communications offering developed by MGE.  
UM Switch  
Features include:  
Remote management from an NMS platform such as  
HP OpenView, CA Unicenter TNG, SunNetManager and more  
Shutdown of multiple servers running different operating systems  
MultiSlot Communication Expander  
Perform automatic actions based on power events such as paging  
the network administrator or sending an eMail  
UM Sensor  
Reboot a locked up server remotely using the UM Switch power controller (option)  
Monitor the temperature and humidity of the computer room with the UM Sensor environmental module (option)  
Connection to the network is achieved through an Ethernet/SNMP card that fits into the MultiSlot Communication Expander.  
The multiple slots available let you manage 2 or 3 redundant Esprit UPSs as one single system over the network.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Select the Esprit you need for your Web Servers  
Power Cluster  
(for servers with 2 redundant power supplies*)  
Model  
Single UPS  
3-server protection  
3-server protection  
Esprit 3.1  
3.0 kVA  
3.0 kVA  
5U (in rack)  
10U (in rack)  
Expand load to 6 kVA  
(with no redundancy)  
5-server protection  
5-server protection  
Esprit 4.5  
Esprit 6  
Esprit 9  
4.5 kVA  
4.5 kVA  
5U (in rack)  
10U (in rack)  
Expand load to 9 kVA  
(with no redundancy)  
6-server protection  
6-server protection  
6 kVA  
6 kVA  
10U (in rack)  
Expand load to 12 kVA  
(with no redundancy)  
9-server protection  
9-server protection  
8.5 kVA  
8.5 kVA  
10U (in rack)  
Expand load to 17 kVA  
(with no redundancy)  
15-server protection  
15-server protection  
Esprit 13.5  
13.5 kVA  
13.5 kVA  
15U (in rack)  
3 to 1 interface  
Expand load to 27 kVA  
(with no redundancy)  
3 to 1 interface  
* For servers with 3 redundant power supplies, add additional Esprit UPS.  
Scalable Battery Runtimes (in Minutes)  
Standard  
2 Batteries  
3 Batteries  
4 Batteries  
5 Batteries  
6 Batteries  
13  
30  
54  
75  
108  
126  
Esprit 3.1  
Esprit 4.5  
Esprit 6  
8
22  
4 Batteries  
30  
34  
6 Batteries  
54  
42  
8 Batteries  
75  
54  
10 Batteries  
108  
72  
12 Batteries  
126  
Standard  
13  
8
22  
34  
42  
54  
72  
Esprit 9  
Notes:1Example above requires adding one additional battery module to an Esprit 4.5 & will provide 22 minutes of runtime at full load. 2For Esprit 6 & 8.5 kVA, battery modules must be added in pairs.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pulsar Esprit  
Specifications  
Dimensions  
and Weights  
Esprit 13.5  
Power Cluster  
Esprit 4.5  
Single UPS  
Dimensions  
Power Cluster (for servers with 2 redundant power supplies)  
Model  
Weight  
(lbs.)  
Dimensions  
Weight  
WxHxD (in.)  
WxHxD (in.) each  
(lbs.) each  
Esprit 3.1  
Esprit 4.5  
Esprit 6  
Electronic  
Battery  
Electronic  
Battery  
Electronic  
Battery  
Electronic  
Battery  
1 ea. 8.5" x 7.25" x 19"  
1 ea. 8.5" x 7.25" x 19"  
1 ea. 8.5" x 7.25" x 19"  
1 ea. 8.5" x 7.25" x 19"  
1 ea. 17" x 7.25" x 19"  
2 ea. 8.5" x 7.25" x 19"  
1 ea. 17" x 7.25" x 19"  
2 ea. 8.5" x 7.25" x 19"  
3 ea. 8.5" x 7.25" x 19"  
3 ea. 8.5" x 7.25" x 19"  
20  
80  
20  
80  
40  
80  
40  
80  
20  
80  
20  
2 ea. 8.5" x 7.25" x 19"  
2 ea. 8.5" x 7.25" x 19"  
2 ea. 8.5" x 7.25" x 19”  
2 ea. 8.5" x 7.25" x 19"  
2 ea. 17" x 7.25" x 19"  
4 ea. 8.5" x 7.25" x 19"  
2 ea. 17" x 7.25" x 19"  
4 ea. 8.5" x 7.25" x 19"  
6 ea. 8.5" x 7.25" x 19"  
6 ea. 8.5" x 7.25" x 19"  
2 ea. 19” x 4” x 5.1”  
20  
80  
20  
80  
40  
80  
40  
80  
20  
80  
20  
Esprit 9  
Esprit 13.5Electronic  
Battery  
3to1Interface 1 ea. 19” x 4” x 5.1”  
Esprit 13.5 consists of 3 each Esprit 4.5 plus 1 3 to 1 interface  
Sizing Guide and  
Battery Runtimes  
3 PC  
4 PC  
5 PC  
6 PC  
2 RISC  
9 PC  
12 PC  
15 PC  
servers  
servers  
servers  
servers  
servers  
servers  
servers  
servers  
Single UPS  
Esprit 3.1  
Esprit 4.5  
Esprit 6  
17  
20  
45  
48  
100  
12  
26  
33  
70  
8
18  
22  
55  
15  
20  
47  
13  
15  
40  
Esprit 9  
10  
25  
Esprit 13.5❊  
18  
13  
Note: In a Power Cluster configuration, the battery runtimes given above will double.  
Characteristics  
Esprit 3.1  
Esprit 4.5  
Esprit 6  
Esprit 9  
Electrical  
Power (VA/W)  
3000/2016  
4500/3150  
6000/4032  
8500/6000  
Input voltage range  
Output voltage range  
Output frequency regulation  
Surge protection  
Efficiency (on battery)  
Waveform  
100/120/127 Volts +10% -15%  
100/120/127 Volts  
100/120/127 Volts +10% -15% 208/220/240 Volts+10%-15%  
208/220/240 Volts+10%-15%  
100/120/127 Volts  
50/60 Hz +/- 0.5 Hz  
420 joules  
100/120/127/200/208/220/240 Volts  
420 joules  
> 94%  
630 joules  
> 94%  
630 joules  
> 94%  
> 94%  
❊❊  
Compatible with multiple server-grade, Power Factor Corrected (PFC) power supplies  
Batteries  
Number and type  
Recharge time  
12 x 12V/7Ah  
4 hours to 80%  
4-5 years  
12 x 12V/7Ah  
4 hours to 80%  
4-5 years  
24 x 12V/7Ah  
4 hours to 80%  
4-5 years  
24 x 12V/7Ah  
4 hours to 80%  
4-5 years  
Battery life expectancy  
User connections  
Input power cord  
Output receptacles  
Communication ports  
Software included  
Environment  
6 feet w/ L5-30P  
L5-30 & 4 x 5-15  
6 feet w/ 5-50P  
5-50 & 4 x 5-15  
1xRS232 & 1xUSB  
6 feet w/ L14-30P  
L14-30, L6-30 & 6 x 5-15  
6 feet w/ 14-50P  
14-50, L6-30 & 6 x 5-15  
Solution-Pac Power Management suite  
Safety  
Surge protection  
Noise level  
Operating temperature  
Manufacturer certifications  
Warranty  
Warranty extension (option)  
Environmental  
❊❊Independent test lab report available on MGEs web site  
UL, cUL 1778  
ANSI C62.41  
45 dBA max.  
32-105 F  
FCC, ISO 9001  
2 years, parts and labor electronics (battery modules:1year)  
3 years, parts and labor incl. batteries  
Recyclable components, packing & documentation, recycled materials, used battery recovery  
MGE GREEN SWEEP  
Call MGE to return your UPS for free  
recycling to a US EPA-certified recycling  
center and help protect our environment.  
MGE UPS SYSTEMS  
BRAZIL  
Avenida Guido  
ARGENTINA  
Thames 91  
1609 San Isidro  
Prov de Buenos Aires  
tel (54) 11-4766-8777  
fax (55) 11-4766-6008  
USA (headquarters)  
1660 Scenic Avenue  
Costa Mesa, CA 92626  
CANADA  
#9, 2798 Thamesgate Dr.  
Mississauga, ON L4T 4E8  
tel (905) 672-0990  
(877) 672-0990  
Caloi 1985 (GALPAO 23)  
Guarapiranga  
Sao Paulo - SP, CEP 05802  
tel (55) 11-5890-3323  
fax (55) 11-5890-3353  
esprit 101  
Effective: April 2000  
tel  
(800) 523-0142  
(714) 557-1636  
(714) 557-9788  
fax  
fax (905) 672-7667  
©MGE UPS SYSTEMS, Inc. All specifications subject to change without notice. The MGE UPS SYSTEMS logo is a trademark of MGE UPS SYSTEMS.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Lasko Fan T38300 User Manual
Lennox International Inc Air Conditioner HSXA15 User Manual
LOREX Technology Security Camera SG7209P User Manual
Mackie Car Speaker SWA 1801z User Manual
Magic Chef Fryer MCSDF15ST User Manual
Magnavox Network Card 701P41586 User Manual
Makita Chainsaw UC3020A User Manual
Metra Electronics Speaker 99 7011 User Manual
Metrologic Instruments Scanner MS1890 Focus User Manual
Midland Radio Two Way Radio GXT500 Series User Manual