MGE UPS SYSTEMS,INC.
Pulsar EX
2200RT / 3200RT
EXB 2200/3200 RT
Installation and User
Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
CAUTION: Safety of persons
◗
The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS
is disconnected from the AC-power source.
◗
◗
Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel.
The UPS must be properly earthed. Measurements are required to ensure that the total leakage current of the UPS and the
protected equipment does not exceed 3.5 mA by checking their characteristics (maximum leakage current of the UPS = 2 mA).
The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below
must be observed:
◗
-
-
-
-
Never burn the battery (risk of explosion).
Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
Comply with all applicable regulations for the disposal of the battery.
Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be
taken for all handling: remove watches, rings, bracelets and any other metal objects, use tools with insulated handles.
Do not lay tools or metal parts on top of batteries.
-
CAUTION: Product Safety
◗
◗
The UPS connection instructions and operation described in the manual must be followed in the indicated order.
UPS must be connected to a nearby wall outlet that is easily accessible. The UPS can be disconnected from the AC-power
source by removing the power cord.
◗
Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of
all the equipment to be connected to the UPS.
◗
◗
◗
◗
◗
◗
Never install the UPS near liquids or in an excessively damp environment.
Never let a foreign body penetrate inside the UPS.
Never block the ventilation grates of the UPS.
Never expose the UPS to direct sunlight or source of heat.
If the UPS must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -25ºC to +55ºC.
Special Precautions
◗
◗
All handling operations will require at least two people (unpacking, installation in rack system).
Once installed and connected to the AC power source for the first time, the battery will start to charge. Full charging to obtain
the rated battery backup time requires at least 8 hours.
◗
Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of
24 hours, at least once every 6 months (for a normal storage temperature less than 25°C). This charges the battery, thus
avoiding possible irreversible damage. During the replacement of the battery module, it is imperative to use the same type and
number of element previously mounted in the UPS, in order to maintain an identical level of performance and safety. In case of
doubt, don’t hesitate to contact our after sales department (for more information, refer to the web site www.mgeups.com).
3400753300/AE - Page 3
Download from Www.Somanuals.com. All Manuals Search And Download.
How to use this document
Using this document
Information may be found primarily by consulting:
◗ The contents,
◗ The index.
Icon Usage
WARNING: Eminent hazard to personnel or equipment, information must always be followed.
CAUTION: Hazard to personnel or equipment, information that must always be followed.
Notes, tips and information, help.
Important information, help.
Visual indication.
Action.
Audio indication.
In the illustrations on the following pages, the symbols below are used:
LED off.
LED on.
LED flashing.
Page 4 - 3400753300/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
1. Presentation
1.1 System configurations ................................................................................................................7
Rack setup ......................................................................................................................................7
Tower setup ....................................................................................................................................7
1.2 Rear panel ......................................................................................................................................8
Pulsar EX 2200RT ........................................................................................................................8
Pulsar EX 3200RT ........................................................................................................................8
Pulsar EXB 2200/3200 RT ............................................................................................................8
1.3 Control panel ................................................................................................................................9
2. Installation
2.1 Unpacking ....................................................................................................................................10
2.2 Installation in rack position ........................................................................................................11
2.3 Installation in tower position ....................................................................................................12
2.4 Connection to the RS232 or USB communication port (optional) ........................................13
2.5 Installation of the communication-card option ........................................................................13
2.6 Connections ................................................................................................................................14
3. Operation
3.1 Start-up ........................................................................................................................................15
3.2 LED indicators ............................................................................................................................15
3.3 Operation on battery power (following failure of AC input power) ............................................16
Transfer to battery power ..............................................................................................................16
Threshold for the low-battery warning............................................................................................16
End of backup time ........................................................................................................................16
3.4 Personalization (optional) ............................................................................................................17
Function..........................................................................................................................................17
"ON / OFF conditions" tab..............................................................................................................17
"Battery" tab ..................................................................................................................................17
"Output" tab....................................................................................................................................18
"Bypass" tab ..................................................................................................................................18
3.5 UPS Shutdown ............................................................................................................................18
3.6 UPS Remote Power Off ..............................................................................................................19
3400753300/AE - Page 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
4. Maintenance
4.1 Troubleshooting ..........................................................................................................................20
4.2 Replacement of the battery modules ........................................................................................22
5. Environment ....................................................................................................................................24
6. Appendices
6.1 Technical characteristics ..........................................................................................................25
6.2 Glossary ......................................................................................................................................26
6.3 Index ............................................................................................................................................27
Page 6 - 3400753300/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Presentation
1.1 System configurations
Rack setup
17.24 inches (19" Rack mount)
25.75 inches (EX 2200RT)
26.00 inches (EX 3200RT)
3.75 inches
(2U)
R
P
E X
U
L
S
A
BYPA
SS
2
1
%
%
%
8
0% 100%
2
0
%
5
0
test
com
ps.
geu
w.m
ww
Model
Part
Number
Weight
(Ibs/kg)
Pulsar EX 2200RT
85220
80.8 lbs (36.6 kg)
82.7 lbs (37.5 kg)
92.8 Ibs (42.0 kg)
Pulsar EX 3200RT
85320
Tower setup
Pulsar EXB 2200/3200 RT
85000
%
%
0
0
1
%
0
8
%
0
5
%
0
2
%
t
s
e
t
1
2
S
S
A
P
Y
B
S
A
R
L
P
E
U
X
om
ps.c
geu
w.m
ww
3400753300/AE - Page 7
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Presentation
1.2 Rear panel
Slot for communication-card option.
RS232 communication port.
USB communication port.
1
2
Pulsar EX 2200RT
5
3
8
9
10 11 12
4
1
3
4
Upper two receptacles for connection
to AC-power source.
Lower two programmable receptacles
(1 and 2).
5
L5-20P Plug
Output circuit breakers. (EX 3200RT)
6
7
INPUT CABLE
L5-20R Receptacle
OUTPUT CABLE
2
7
Input/Output power cords for direct
connection of protected equipment.
EX 2200RT-L5-20P/L5-20R; and
EX 3200RT-L5-30P/L5-30R.
Pulsar EX 3200RT
8
9
10 11 12
6
4
1
5
3
Connector for an additional battery
module.
8
9
Connector for automatic detection of an
additional battery module.
Pushbutton to test phase/neutral
inversion of AC-power source.
10
11
LED indicating Site Wiring Alarm
Enable, with flashing and intermittent
buzzer. Reset fault with rear panel
button.
L5-30P (Plug)
INPUT CABLE
2
L5-30R (Receptacle)
OUTPUT CABLE
7
Pulsar EXB 2200/3200 RT
Connector for remote power off (RPO).
12
13
14
15
Battery module connectors (to the UPS
or to other battery modules).
Connectors for automatic detection of
additional battery modules.
14
15
Circuit breaker for battery ON/OFF and
protection.
13
13
Page 8 - 3400753300/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Presentation
1.3 Control panel
BYPASS
2
1
test
%
%
20% 50% 80% 100%
16
17
18
19 20
21
22
23
24
25
26
27
ON / OFF.
16
17
18
19
Operation on battery power.
Operation in ON-LINE mode (backup power available).
Operation on bypass (no backup power available).
%
%
Alarms
battery
remaining
load
100%
80%
50%
20%
UPS
27
100%
80%
50%
20%
Status of programmable outlet 2:
20
21
Supplied with power
overload
Status of programmable outlet 1:
Status change in
progress.
Electronics
fault
26
25
24
◗ Lamp test or buzzer OFF.
◗ Forced transfer to bypass and back
by pressing button 3 times in less
than 5 seconds.
22
Battery
fault *
Press simultaneously at
least 3 seconds to reset
the “End of battery life”
alarm.
Site Wiring
Fault
23 Hold down to display
percent load:
(*) : ◗ flashing LED + buzzer: battery fault (battery must be replaced).
◗ flashing LED + long buzzer (once per hour): theoretical end of battery life (replacement recommended).
3400753300/AE - Page 9
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
2.1 Unpacking
31
30
32
%
%
0
0
1
%
0
8
%
0
5
%
0
2
%
t
s
e
t
1
2
34
S
S
A
P
Y
B
35
R
L
S
A
U
E
X
P
36
RS232 communication cable.
30
31
32
34
35
USB communication cable.
Telescopic rails for mounting in 19" bay with mounting hardware.
CD-ROM with the Solution-Pac and UPS Driver software.
Product documentation.
Two supports for the upright position.
36
Page 10 - 3400753300/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
2.2 Installation in rack position
Follow steps A to D for rack mounting of the UPS on the rails. The rails and the necessary mounting hardware are supplied in
the box along with the UPS (see item 32 on page 10).
A. Secure Rails together with three screws (1).
1
B. Attach frontal Rails to Rack front (2).
3
C. Attach rearmost Rails to Rack rear (3).
If using Stop-Notch (7) snap into rear rail.
(refer to Quick Start for positioning details.)
3
D. Attach both front brackets (4 & 5) to each
side of UPS, and slide (mount) UPS into
the Rack (6).
2
6
2
5
7
Stop-Notch
Snap from
inside of rails
4
5
CAUTION: Do not lean or place objects on top of unit at any time. Hazard of dismounting and disconnection can
occur with units.
NOTE: (For step 5) it is possible to adjust the position of the front fixing bracket.
3400753300/AE - Page 11
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
2.3 Installation in tower position
Install the two supports for the upright position using provided hardware in the package.
(see item 32 on page 10).
Pull out the MGE Logo and Model plates, then rotate them as shown.
%
%
0
0
1
%
0
8
%
0
5
%
0
2
%
t
s
e
t
1
2
S
S
A
P
Y
B
A
R
L
S
U
X
P
E
R
m
.co
ps
geu
w.m
ww
L
S
A
U
P
Page 12 - 3400753300/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
2.4 Connection to the RS232 or USB communication port (optional)
1. Connect the RS232 30 or USB 31
communication cable to the serial port or
the USB port on the computer.
30
2. Connect the other end of the communica-
tion cable 30 or 31 to the RS232
2
31
or USB
UPS.
3
communication port on the
The UPS can now communicate with all
MGE UPS SYSTEMS, Inc. supervision,
set-up or safety software.
3
2
NOTE: The RS232 and USB communication ports cannot operate simultaneously.
2.5 Installation of the communication-card option
Slot for the
communication
card option.
It is not necessary to shut down the UPS to
install the communication card:
1
1.Remove the slot
two screws.
1
cover secured by
2.Insert the card in the slot.
3.Secure the card with the two screws.
L5-30P Plug
INPUT CABLE
L5-30R Receptacle
OUTPUT CABLE
3400753300/AE - Page 13
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
2.6 Connections
CAUTION: Check that the indications on the rating plate (on the back of the UPS), correspond to your AC-power
system, and to the actual electrical consumption of all the equipment to be connected to the UPS.
1. Connect the input power cord
7
to the
4
AC-power wall-receptacle.
2. Connect the protected equipment to the
UPS. It is advised to connect priority
loads to the outlets and/or power cord
and any non-priority loads to the two
5-20P
4
programmable outlets
5
(If the UPS is
5
connected to a computer running MGE
UPS SYSTEMS, Inc. communication
software, it is possible to program the
interruption of power to the two
programmable outlets
5
during
operation on battery power, thus reserv-
ing backup power for the priority loads).
The battery begins charging the
instant the UPS unit is connected
to a power source. Eight hours are
required to charge to the full rated
backup time.
4
7
Page 14 - 3400753300/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Operation
3.1 Start-up
The protected equipment connected to the UPS can be energized, whether AC input power is available or not.
CAUTION:The AC input power source must be present when
energizing for the first time.
1. Press the ON / OFF button 16 .
◗ The buzzer beeps and all the LEDs go ON.
◗ The buzzer beeps twice, then:
◗ If AC input power is available, LED 18 goes ON, indicating
operation in ON-LINE mode.
1
S
S
BYPA
2
◗ If AC input power is not available and the UPS is configured for
automatic restart mode, the buzzer beeps three times and LED 17
goes ON, signalling operation on battery power.
All connected equipment is energized.
%
100%
%
80
%
50
%
t
est
20
%
16
17 18 25
26 27
NOTE: If LEDs 17 or 18 do not turn ON or if LEDs 25 to 27 flash,
there is a fault (see section 4.1).
3.2 LED indicators
LEDs 24 to 27 provide three
different indications:
BYPASS
2
1
1. Remaining backup time in percent
(during normal operation).
2. Percent load drawn by the protected
test
%
%
20% 50% 80% 100%
equipment, when button 23 is pressed.
3. Operating faults (flashing LED and
beeps):
27 Overload.
26 UPS fault.
24
25 26 27
16
17 18 19 20 21
22
23
25 Battery fault or end of life warning.
24 Site wiring Fault
Description of LED indicator status 20 and 21 for programmable outlets 1 and 2:
◗ OFF: the outlets are not supplied with power.
◗ Flashing: status change in progress.
◗ ON: the outlets are supplied with power.
Outlets 1 and 2 can be remotely programmed and controlled.
They may be used for sequential start-up of the protected applications, shedding of non-priority applications during
operation on battery power, and priority management at the end of battery backup time to reserve the longest possible
backup time for the most sensitive applications. These outlets are programmed using Solution Pac software.
3400753300/AE - Page 15
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Operation
3.3 Operation on battery power (following an AC input power failure)
Transfer to battery power
The AC-power source is outside tolerances, LED 17 is ON, the buzzer
beeps three times.
BYPASS
2
1
The equipment connected to the UPS is supplied by the battery.
test
17
Threshold for the low-battery warning
The low-battery warning threshold can be set by the user, with the UPS
Driver software (see section 3.4).
BYPASS
2
1
LED 17 flashes.
The buzzer beeps every three seconds.
test
%
There is very little remaining battery backup time. Close all
applications because UPS automatic shutdown is imminent.
17
End of backup time
The buzzer sounds continuously.
BYPASS
Press button 22 to turn the buzzer OFF.
2
1
The equipment is no longer supplied with power.
test
22
The UPS goes to sleep mode at the end of the battery backup time, until complete shutdown, due to tripping of the
battery-protection function against deep discharge.
Return of AC input power:
IMPORTANT: If, in spite of the return of AC input power, the UPS does not restart, check that the automatic-restart
function (activated by return of AC input power) has not been disabled (see section 3.4).
Page 16 - 3400753300/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Operation
3.4 Personalization (optional)
Function
Personalization parameters can be set and modified using the UPS Driver software installed on a computer that is
connected to the UPS (see section 2.4 Connection to the RS232 communication port).
NOTE: Check that the RS232 30 cable is properly connected.
UPS Driver installation:
1. Insert the Solution-Pac CD-ROM containing the UPS Driver software into your computers CD ROM drive.
2. Open the file Manager and select the CD-ROM drive.
3. Launch "\Emb\Config\UPSDRVxx.exe" (xx = software version).
MGE representative in your area. Once UPS Driver has been installed, the UPS parameters listed below can be
modified.
"ON / OFF conditions" tab
Personalization function
Default setting
Enabled
Options
Disabled
Disabled
Disabled
Enabled
Disabled
Automatic start
Cold start (battery power)
Forced shutdown
Enabled
Enabled
Sleep mode
Disabled
Enabled
UPS ON / OFF via software
"Battery" tab
Personalization function
Default setting
Options
Once a day
Once a month
Automatic "Battery test" intervals
"Low-battery warning" threshold
Every weeks
No test
20% remaining
battery backup time
From 0% to 100% of the remaining
battery backup time
Protection against deep discharges
Enabled
Disabled
3400753300/AE - Page 17
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Operation
"Output" tab
Personalization function
Rated UPS voltage
Default setting
120 V
Options
100 V - 127 V
Converter
Frequency working mode
Rated UPS frequency
Autoselect
F = 60 Hz
50 Hz
UPS tolerance for AC-power
source frequency
F
5%
F
1% to 10%, in 1% steps
Overload alarm threshold
110%
0 to 110%, in 10% steps
UPS restart following short-circuit
Disabled
Enabled (click to add check)
"Bypass" tab
Default setting
Enabled
Options
Personalization function
Disabled (click to remove check)
Enabled (click to add check)
Transfer to bypass if overload
Disabled
Transfer to bypass following a fault, whatever the
conditions on the AC-power source
3.5 UPS shutdown
Press button 16 (return to the OFF position).
BYPASS
2
1
The connected equipment is no longer supplied with power.
test
16
Page 18 - 3400753300/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Operation
3.6 UPS Remote Power Off (RPO)
Pulsar EX RT's are equipped with a Remote Power Off function (RPO) that can cut power to all the devices connected to
the UPS using a remote user-operated contact.
The function is implemented by opening a contact connected to the two terminals of connector 12 on the back of the
UPS.
12
37 38
Installation and test of the remote power off function
1. Check that the UPS is shut off and disconnected from the AC power source.
2. Remove the RPO connector 12 by undoing the screws 37 .
3. Connect an insulated dry contact (NC, 60 V DC, 30 V AC max., 20 mA max., cable size 0.75 mm) to the two terminals
of the RPO connector 38 .
4. Put the RPO connector 12 back in place on the back of the UPS.
5. Connect the UPS to the AC-power source and restart it as indicated previously.
6. Activate the RPO external contact to test the function.
7. To return to normal operation, deactivate the RPO external contact and restart the UPS using button 16 (press OFF,
then ON).
3400753300/AE - Page 19
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Maintenance
4.1 Troubleshooting
If any of LEDs 25 , 26 or 27 flash, there is a operating anomaly or an alarm.
NOTE: If a LED flashes, the bargraph data is no longer displayed.
LED 27 flashes and UPS overload. Overload is too long or too high.
◗ Check the power drawn by the
equipment and disconnect any
non-priority devices.
the buzzer beeps.
◗ If AC power is present and within tolerances, the
UPS goes to bypass mode (supply directly by the
AC-power source). LED 19 flashes.
The buzzer beeps every second.
◗ If AC power is not present or not within tolerances,
the connected applications are no longer supplied.
The buzzer sounds continuously.
LED 25 flashes and A battery fault was detected during the
◗ Check that the battery connector
the buzzer beeps.
automatic battery test.
is fully pushed in.
◗ Replace battery module (see Maintenance section).
LED 25 flashes and The battery has reached the theoretical end
◗ Reset the alarm by pressing
buttons 22 and 23
the buzzer emits a
long beep once
per hour.
of its service life.
simultaneously for 3 seconds.
◗ It is advised to replace both batteries at
See the section on maintenance.
the same time with the same rating
as the original batteries.
The yellow LED 24
flashes, the red
indicator light 11
behind the UPS
comes on and the
buzzer sounds
The function for monitoring the phase and neutral
position of your electrical network has detected a
reversal.
◗ Directly earthed neutral type
networks: check the cabling
of phase and neutral on your
electrical network.
For all other network types,
de-activate the detection function
(this function is only operational
continuously.
for directly earthed neutral electrical
networks):
Press for at least 5 seconds the
pushbutton 10 behind the UPS
(UPS stopped and connected to the
network for less than 30 minutes).
Page 20 - 3400753300/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Maintenance
Indication
Signification
Correction
The outlets are not supplied One of the protection circuit breakers
6
for the
◗ Check that there is not a short-
circuit on the outlets.
with power, even though
button 16 is ON
outlets (on the back of the UPS) is open.
◗ Eliminate any overloads on the
(3200 RT only).
outlets by modifying the
distribution of devices on the
outlets.
LED 26 flashes and
the buzzer sounds
continuously.
UPS electronics have detected a UPS fault.
Depending on the UPS personalization parameters
(see section 3.4).
◗ Restart the UPS.
There are two possibilities:
◗ The equipment connected to the UPS continues to ◗ Call the after-sales support
be supplied, but directly from the AC-power source
department.
(via the automatic bypass (LED 19 ON).
◗ The connected equipment is no longer supplied.
The equipment connected to the UPS is no
longer protected.
3400753300/AE - Page 21
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Maintenance
4.2 Replacement of the battery modules
CAUTION: Load will not be protected during this procedure!
Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
Precautions must be taken for all handling.
Safety Rules:
◗ Remove all watches, rings, bracelets and any other metal objects that may come into contact with the battery modules.
◗ Use tools with insulated handles.
Removal of the battery modules
A
B
- Unclip the small plate with the MGE
UPS SYSTEMS, Inc. Logo on the
UPS front panel.
- Remove the 2 screws.
1
2
SS
PA
BY
%
0%
10
%
80
%
50
0%
R
A
2
%
S
L
t
tes
U
P
E X
B
A
m
co
s.
p
u
ge
.m
w
w
w
C
D
- Remove the left part of the front panel.
- Disconnect the connector.
1
2
SS
PA
BY
%
0%
10
80%
50%
%
20
%
st
te
D
R
A
S
L
U
P
E X
C
Page 22 - 3400753300/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Maintenance
E
F
- Remove the screws securing the
battery cover.
- Remove the cover.
1
2
SS
PA
BY
%
0%
10
%
80
%
50
%
20
%
t
tes
E
F
G
- Remove the two battery modules and
proceed with replacement.
1
2
SS
PA
BY
%
0%
10
80%
%
50
%
20
%
st
te
G
G
Reinstallation of the battery modules
To reinstall the battery modules perform this procedure in reverse order e.g., “G”, “F”, “E”.
◗ To maintain an identical level of performance and safety, use battery modules identical to that previously
mounted in the UPS.
◗ Press the two parts of the battery connector tightly together to ensure proper connection.
3400753300/AE - Page 23
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Environment
This product has been designed to respect the environment:
It does not contain CFC's or HCFC's.
UPS recycling at the end of service life:
MGE UPS SYSTEMS, Inc. undertakes to recycle, by certified companies and in compliance with all applicable regulations,
all UPS products recovered at the end of their service life (contact your MGE UPS SYSTEMS, Inc. branch office).
Packing:
UPS packing materials must be recycled in compliance with all applicable regulations.
WARNING:
This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not properly recycled
by specialized companies.
MGE Customer Care Center
Technical questions? If you encounter a problem while following the instructions in this manual, we recommend that you
contact our Technical Support Group at 1 800 523-0142.
?
RMA forms for service.
Page 24 - 3400753300/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Appendices
6.1 Technical characteristics
AC/DC PFC
CONVERTER
DC/AC
INVERTER
SAFETY
RELAY
BYPASS
RELAY
AC INPUT
EMI FILTER
EMI FILTER
AC OUTPUT
BATTERY
POWER
DC/DC
CHARGER
SUPPLY
PUSH PULL
BATTERY
Pulsar EX 2200RT
Pulsar EX 3200RT
Pulsar EXB
2200/3200 RT
Output power rating
2200 VA / 1540 W
3200 VA / 2080 W
AC-input
◗ Voltage
◗ Frequency
◗ Power factor
Runtime @ full load
(1)
Single phase, 60 V / 70 V / 80 V to 142 V
50/60 Hz (auto-select)
≥ 0.95
20min -40min -60min -80min
1EXB -2EXB -3EXB -4EXB
Output specification
◗ Voltage
◗ Frequency
◗ Harmonic distortion
◗ Overload capability
QUALITY
(2)
Single phase, 120 V 3%
50/60 Hz 0.5%
(3)
Designed, Manufactured and
marked under ISO 9001 quali-
ty system.
< 4% on linear load, < 6% on non linear load
110% continuous, 130% 12s, > 130% 1.5s
Battery (sealed lead-acid,
maintenance free)
72VDC - 18 Ah
6 x 12 V - 9 Ah
6 x 12 V - 7 Ah
Environmental and safety
◗ Noise level
◗ Operating temperature
◗ Relative humidity
◗ Safety
< 50 dBA
0 to 40° C
20 to 90% (without condensation)
UL 1778 / cUL CSA 22.2 N°107.1
FCC 47 CFR Part 15, class A
UL, CSA
UL, CSA
FCC Class A
UL , cUL
◗ EMC
◗ Agency markings
(1) Input voltage correspond to 33% / 66% / 100% of the nominal power rating.
(2) Adjustable from 100 V to 127 V using UPS Driver software.
(3) Frequency converter mode may be set using the UPS Driver software.
3400753300/AE - Page 25
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Appendices
6.2 Glossary
Authorized voltage range for
Upper and lower voltage thresholds within which the UPS can operate on the automatic
bypass in the event of a UPS fault or overload.
transfer to bypass if fault or
overload
Automatic bypass
Automatic switch controlled by the UPS, used to connect the equipment directly to the
AC-power source in the event of a UPS failure or an overload.
Automatic start following
return of AC input power
This function automatically starts the UPS when AC input power returns following
shutdown at the end of the battery backup time. It can be enabled or disabled.
Backup time
Bargraph
Time that the connected equipment can operate on battery power.
Device on the front panel indicating the percent remaining backup time or the percent
load.
Battery test
Dialog box
Internal UPS test on battery status.
A window in a computer program displayed for selection by the user of various options
and parameter settings.
Double conversion
The power supplied to the connected equipment is completely regenerated by
continuous double conversion, i.e. the AC power from the AC-power source is rectified
(AC - DC), then converted back (DC - AC) to AC power.
Equipment
Devices or systems connected to the UPS output.
Forced shutdown
Ten-second interruption in the supply of power to the connected equipment following a
system shutdown, even if AC input power returns during the interruption period.
Percent load
Ratio between the power drawn by the connected equipment and the total power that
the UPS can supply.
Personalization
A number of UPS functions can be modified using the UPS Driver software to better
meet the user’s needs.
Programmable outlets
Remote Power Off
Start on battery power
Outlets that can be automatically shed during operation on battery power (a shedding
time delay may be programmed using Solution-Pac software.
External dry contact can be used to stop the unit, during an emergency situation for
example. All power is removed from the load.
This function makes it possible to energize the connected equipment even when AC
input power is not available (operation exclusively on battery power).
UPS
Uninterruptible Power Supply.
UPS ON / OFF via software
It is possible to enable or disable use of UPS ON / OFF controls by the computer-
system protection software.
Page 26 - 3400753300/AE
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Appendices
6.3 Index
A
O
Automatic bypass....................................................9-18-20
Automatic start ................................................................17
ON LINE mode..................................................................9
Overload ................................................................9-18-20
B
P
Bargraph ......................................................................9-15
Battery
Personalization ..............................................................17
Battery ....................................................................17
By-pass ..................................................................18
On/Off conditions ....................................................17
Output......................................................................18
Programmable outlets ..............................................8-9-15
End of backup time..................................................16
Fault......................................................................9-15
Low-battery warning ................................................17
Recycling ................................................................24
Replacement ......................................................22-23
Transfer to battery power ........................................16
Buttons ..........................................................................8-9
Buzzer........................................................................15-16
Buzzer shutdown ..............................................................9
R
Remote power off............................................................19
S
Site Wiring Fault................................................................9
Sleep mode ....................................................................17
Automatic restart ................................................17-18
Start-up............................................................................15
C
Connection
Additional battery module ........................................8
Communication card ..............................................13
RS 232 communication port....................................13
USB communication port ........................................13
Communication ............................................................8-13
T
Technical characteristics ................................................25
Transfer (forced) ..............................................................9
D
Dimensions........................................................................7
U
UPS Driver ....................................................................17
UPS fault ..........................................................9-15-20-21
UPS ON / OFF via software ..........................................17
UPS shutdown................................................................18
E
Environment ................................................................2-24
W
F
Web site............................................................................2
Weight ..............................................................................7
Forced shutdown ............................................................17
L
Lamp test..........................................................................9
LEDs..............................................................................8-9
3400753300/AE - Page 27
Download from Www.Somanuals.com. All Manuals Search And Download.
MGE UPS SYSTEMS, INC.
T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R
1660 Scenic Avenue
Costa Mesa, CA 92626, USA
Main Number: 714 557-1636
For service call:
1 800 523-0142
Internet: www.mgeups.com
M
G
E
UPS SYSTEMS
3400753300-AE
Download from Www.Somanuals.com. All Manuals Search And Download.
|