Lochinvar Boiler 400 801 User Manual

OKBX-I-O Rev B  
Outdoor Knight XL  
Installation & Operation Manual  
Models: 400 - 801  
This manual must only be used by  
a qualified heating installer / service  
ƽ WARNING  
technician. Read all instructions,  
including this manual and the  
Outdoor Knight XL Service Manual,  
before installing. Perform steps in  
the order given. Failure to comply  
could result in severe personal  
injury, death, or substantial property  
damage.  
Save this manual for future reference.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
Please read before proceeding  
Installer – Read all instructions, including  
When servicing boiler –  
ƽ WARNING  
this manual and the Outdoor Knight XL  
Service Manual, before installing. Perform  
steps in the order given.  
• To avoid electric shock, disconnect electrical supply  
before performing maintenance.  
User – This manual is for use only by  
• To avoid severe burns, allow boiler to cool before  
performing maintenance.  
a
qualified heating installer/service  
technician. Refer to the User’s Information  
Manual for your reference.  
Boiler operation –  
Have this boiler serviced/inspected by  
a qualified service technician, at least  
annually.  
• Do not block flow of combustion or ventilation air to  
the boiler.  
• Should overheating occur or gas supply fail to shut off,  
do not turn off or disconnect electrical supply to  
circulator. Instead, shut off the gas supply at a location  
external to the appliance.  
Failure to comply with the above could  
result in severe personal injury, death or  
substantial property damage.  
When calling or writing about the boiler  
– Please have the boiler model and serial  
number from the boiler rating plate.  
NOTICE  
• Do not use this boiler if any part has been under water.  
The possible damage to a flooded appliance can be  
extensive and present numerous safety hazards. Any  
appliance that has been under water must be replaced.  
Consider piping and installation when  
determining boiler location.  
Any claims for damage or shortage in  
shipment must be filed immediately  
against the transportation company by the  
consignee.  
Boiler water –  
• Thoroughly flush the system (without boiler connected)  
to remove sediment. The high-efficiency heat exchanger  
can be damaged by build-up or corrosion due to sediment.  
Factory warranty (shipped with unit) does  
not apply to units improperly installed or  
improperly operated.  
• Continual fresh make-up water will reduce boiler life.  
Mineral buildup in the heat exchanger reduces heat  
transfer, overheats the stainless steel heat exchanger,  
and causes failure. Addition of oxygen carried in by  
makeup water can cause internal corrosion in system  
components. Leaks in boiler or piping must be repaired  
at once to prevent makeup water.  
Failure to adhere to the guidelines on this  
page can result in severe personal injury,  
death, or substantial property damage.  
ƽ WARNING  
If the information in this manual is not  
followed exactly, a fire or explosion may  
result causing property damage, personal  
injury or loss of life.  
ƽ WARNING  
Do not use petroleum-based cleaning or  
ƽ CAUTION  
sealing compounds in the boiler system.  
Gaskets and seals in the system may be  
damaged. This can result in substantial  
property damage.  
This appliance MUST NOT be installed in  
any location where gasoline or flammable  
vapors are likely to be present.  
Do not use “homemade cures” or “boiler  
patent medicines”. Serious damage to the  
ƽ CAUTION  
WHAT TO DO IF YOU SMELL GAS  
boiler, personnel, and/or property may  
result.  
• Do not try to light any appliance.  
• Do not touch any electric switch; do  
not use any phone in your building.  
Freeze protection uids –  
• Immediately call your gas supplier  
from a near by phone. Follow the  
gas supplier’s instructions.  
• NEVER use automotive antifreeze. Use only inhibited  
propylene glycol solutions, which are specifically  
formulated for hydronic systems. Ethylene glycol is  
toxic and can attack gaskets and seals used in hydronic  
systems.  
• If you cannot reach your gas supplier,  
call the fire department.  
• Installation and service must be  
performed by  
a
qualified installer,  
service agency, or the gas supplier.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
The Outdoor Knight XL - How it works...  
1. Stainless steel heat exchanger  
21. Boiler drain port  
Allows system water to flow through specially designed  
coils for maximum heat transfer, while providing protection  
against flue gas corrosion. The coils are encased in a jacket that  
contains the combustion process.  
Location from which the heat exchanger can be drained.  
22. Low voltage connection board  
The connection board is used to connect external low voltage  
devices.  
2. Combustion chamber access cover  
Allows access to the combustion side of the heat exchanger  
coils.  
23. Low voltage wiring connections (plugs)  
Conduit connection points for the low voltage connection  
board.  
3. Blower  
24. Condensate drain connection  
The blower pulls in air and gas through the venturi (item 5).  
Air and gas mix inside the blower and are pushed into the  
burner, where they burn inside the combustion chamber.  
Connects the condensate drain line to a 1/2” PVC union.  
25. Access cover - front  
Provides access to the gas train and the heat exchanger.  
4. Gas valve  
26. Ignition electrode  
The gas valve senses the negative pressure created by the  
blower, allowing gas to flow only if the gas valve is powered and  
combustion air is flowing.  
Provides direct spark for igniting the burner.  
27. Flame inspection window  
The quartz glass window provides a view of the burner surface  
and flame.  
5. Venturi  
The venturi controls air and gas flow into the burner.  
28. Gas shutoff valve  
6. Flue gas sensor (limit rated - not shown)  
This sensor monitors the flue gas exit temperature. The  
control module will modulate and shut down the boiler if the  
flue gas temperature gets too hot. This protects the flue pipe from  
overheating.  
Manual valve used to isolate the gas valve from the gas supply.  
29. Relief valve  
Protects the heat exchanger from an over pressure condition.  
The relief valve provided with the unit is set at 50 PSI.  
7. Boiler outlet temperature sensor (housed with the  
high limit sensor)  
30. Flame sensor  
Used by the control module to detect the presence of burner  
flame.  
This sensor monitors boiler outlet water temperature (system  
supply). If selected as the controlling sensor, the control  
module adjusts boiler firing rate so the outlet temperature is  
correct.  
31. Line voltage wiring connections (knockouts)  
Conduit connection points for the high voltage junction box.  
8. Boiler inlet temperature sensor  
32. Top panel  
This sensor monitors return water temperature (system  
return). If selected as the controlling sensor, the control  
module adjusts the boiler firing rate so the inlet temperature is  
correct.  
Removable panel to gain access to the internal components.  
33. Power switch  
Turns 120 VAC ON/OFF to the boiler.  
34. Leveling legs  
9. Temperature and pressure gauge (field installed, not  
shown)  
Used to allow the heat exchanger to be leveled. This is needed  
for the proper draining of the condensate from the combustion  
chamber.  
Monitors the outlet temperature of the boiler as well as the  
system water pressure.  
35. Air shroud (Model 501 only)  
10. Electronic LCD display  
The air shroud controls air and gas flow into the burner.  
The electronic display consists of 4 buttons, a navigation dial  
and a multiple line liquid crystal display.  
36. Air pressure switch  
11. Flue pipe assembly  
The air pressure switch detects blocked flue/inlet conditions.  
break the control circuit, shutting the boiler down.  
Factory-supplied components for complete venting  
system.  
37. Pump relay board  
12. Burner (not shown)  
The pump relay board is used to connect the boiler, system and  
DHW pumps.  
Made with metal fiber and stainless steel construction, the  
burner uses pre-mixed air and gas and provides a wide range of  
firing rates.  
38. Transformer (not shown)  
The transformer provides 24V power to the integrated control.  
13. Water outlet (system supply)  
A 1-1/2" or 2" NPT (depending on the model) water  
connection that supplies hot water to the system.  
39. High limit sensor (housed with the outlet temperature  
sensor)  
14. Water inlet (system return)  
Device that monitors the outlet water temperature. If the  
temperature exceeds its setting, the integrated control will break  
the control circuit, shutting the boiler down.  
A 1-1/2" or 2" NPT (depending on the model) water connection  
that returns water from the system to the heat exchanger.  
15. Gas connection pipe  
40. Over-temp switch (located underneath vent cover -  
not shown)  
Threaded pipe connection of 1". This pipe should be connected  
to the incoming gas supply for the purpose of delivering gas to  
the boiler.  
An electrical switch designed to shut down boiler operation in  
the event the outer back of the heat exchanger, directly above the  
flue connection exceeds 604°F (318°C). This is a one time  
switch and could warrant a heat exchanger replacement. Check  
the integrity of the rear refractory at the back of the upper coil if  
the switch opens.  
16. SMART SYSTEM Control Module  
The SMART SYSTEM Control responds to internal and  
external signals and controls the blower, gas valve, and pumps  
to meet the heating demand.  
17. Manual air vent  
41. Vent Cover  
Designed to remove trapped air from the heat exchanger  
coils.  
Covers Over-temp switch and flue collar with flue sensor.  
18. Air intake  
42. Flow switch  
Provides combustion air to the appliance.  
The flow switch is a safety device that ensures flow through  
the heat exchanger during operation. This appliance is low  
mass and should never be operated without flow. The flow  
switch makes contact when flow is detected and allows the unit  
to operate. If flow is discontinued during operation for any  
reason the flow switch will break the control circuit and the  
unit wll shut down.  
19. Air Intake Cover  
Provides protection from outdoor elements.  
20. High voltage junction box  
The junction box contains the connection points for the line  
voltage power and all pumps.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
Outdoor Knight XL Installation & Operation Manual  
The Outdoor Knight XL - How it works...  
(continued)  
Model 400  
32  
31  
19  
10  
4
040  
IMG0  
IMG00405  
11  
25  
Front View - Model 400  
Rear View - Model 400  
20  
22  
4
33  
26  
20  
36  
37  
16  
8
4
1
30  
2
39  
3
7
39  
34  
13  
27  
IMG00406  
17  
21  
24  
IMG00407  
Left Side (inside unit) - Model 400  
Right Side (inside unit) - Model 400  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
Outdoor Knight XL Installation & Operation Manual  
The Outdoor Knight XL - How it works...  
Model 501  
15  
32  
35  
19  
33  
15  
28  
17  
4
29  
7
39  
09  
IMG004  
41  
Rear View - Model 501  
Left Side (inside unit) - Model 501  
Models 601 - 801  
31  
16  
20  
23  
22  
15  
3
4
18  
5
10  
29  
11  
18  
8
2
1
34  
IMG00323  
30  
21  
IMG00324  
14  
24  
41  
Rear View - Models 601 - 801  
Left Side (inside unit) - Models 601 - 801  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
Ratings  
Outdoor Knight XL Boiler  
AHRI Rating  
Other Specications  
Net  
AHRI  
Input  
MBH  
Model Number  
Gross  
Boiler Water  
Content  
Gallons  
Water  
Gas  
Output  
MBH  
Ratings  
Water,  
MBH  
Air Size  
Connections Connections  
(Note 4)  
Note: Change “N” to  
“L” for L.P. gas models.  
Min  
80  
Max  
399  
(Note 1)  
370  
(Note 2)  
3.4  
4.2  
4.2  
5.0  
5.7  
1-1/2"  
1-1/2"  
2"  
1"  
1"  
1"  
1"  
1"  
4"  
4"  
4"  
4"  
4"  
OKN400  
OKN501  
OKN601  
OKN701  
OKN801  
322  
402  
493  
572  
651  
100  
120  
140  
160  
500  
600  
700  
800  
463  
566  
658  
748  
2"  
2"  
Maximum allowed working pressure is located on the rating plate.  
NOTICE  
Notes:  
1. The ratings are based on standard test procedures prescribed by the United States Department of Energy.  
2. Net AHRI ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing  
need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15.  
3. Standard Outdoor Knight XL boilers are equipped to operate from sea level to 4,500 feet only with no adjustments. The boiler  
will de-rate by 4% for each 1,000 feet above sea level up to 4,500 feet.  
4. Ratings have been confirmed by the Hydronics Section of AHRI.  
5. Outdoor Knight XL boilers comply with the requirements of CSD-1 Section CW-400 requirements as a temperature operation  
control. The manual reset high limit provided with the Outdoor Knight XL is listed to UL353.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
1 Determine boiler location  
Installation must comply with:  
The unit must not be installed in an area  
ƽ CAUTION  
that is enclosed by walls or a fence that  
will block free wind movement around  
the appliance. Free movement of wind  
around the outdoor unit is required  
to carry away the flue products and  
provide combustion air. The flue outlet/  
combustion air inlet of an outdoor unit  
must not be installed closer than 10 feet  
from an inside corner of an L-shaped  
structure. Walls or enclosed fencing may  
cause eddy currents which can recirculate  
the flue products into the combustion  
air inlet. Recirculation of flue products  
may cause operational problems, bad  
combustion or non-warrantable damage  
to controls.  
Local, state, provincial, and national codes, laws,  
regulations, and ordinances.  
National Fuel Gas Code, ANSI Z223.1 – latest edition.  
Standard for Controls and Safety Devices for Automatically  
Fired Boilers, ANSI/ASME CSD-1, when required.  
National Electrical Code.  
The Outdoor Knight XL gas manifold  
NOTICE  
and controls met safe lighting and other  
performance criteria when the boiler  
underwent tests specified in ANSI Z21.13  
– latest edition.  
Outdoormodelsmustbeinstalledoutdoors  
only and must use the outdoor vent  
ƽ WARNING  
assembly supplied by the manufacturer.  
Personal injury or product damage may  
result if any other venting is used or if an  
outdoor model is used indoors. All covers,  
doors and jacket panels must be properly  
installed to ensure proper operation and  
prevent a hazardous condition.  
Locate the unit at least 3 feet (0.91m)  
outside any overhang.  
Do not install in locations where rain  
from building runoff drains will spill onto  
the unit.  
CAUTION  
This product contains a condensate  
ƽ WARNING  
Do not locate the unit so that water  
from sprinklers may spray directly onto  
it. Water may damage controls or other  
electrical components.  
management and disposal system that  
may be subject to freezing if exposed  
to sustained temperatures below 32°F.  
Precautions should be taken to protect the  
condensate trap and drain lines during  
extended periods of outdoor temperatures  
below 32°F.  
Do not install the unit under a deck.  
ƽ WARNING  
Do not install the unit in a well, stairwell,  
alcove, courtyard or other recessed area.  
Before locating the boiler, check:  
Do not install outdoor units on stack  
frames. Failure to comply with the above  
may result in severe personal injury, death  
or substantial property damage.  
1. Check for nearby connection to:  
• System water piping  
• Gas supply piping  
• Electrical power  
3. Check area around the boiler. Remove any combustible  
materials, gasoline and other flammable liquids.  
2. - Keep venting areas free of obstructions.  
- Keep area clean and free of combustible and flammable  
materials.  
Failure to keep boiler area clear and free  
ƽ WARNING  
of combustible materials, gasoline, and  
- To avoid a blocked air inlet or blocked flue condition,  
keep the outdoor air inlet and flue outlet clear or leaves,  
debris, etc.  
other flammable liquids and vapors can  
result in severe personal injury, death, or  
substantial property damage.  
Do not install outdoor models directly on  
CAUTION  
the ground. You must install the outdoor  
4. If a new boiler will replace an existing boiler, check for  
and correct system problems, such as:  
unit on a level concrete, brick, block, or  
pressure-treated wood platform.  
• System leaks causing oxygen corrosion or heat exchanger  
cracks from hard water deposits.  
Do not locate unit so that high winds  
ƽ CAUTION  
can deflect off of adjacent walls, buildings  
• Incorrectly-sized expansion tank.  
or shrubbery causing recirculation.  
Recirculation of flue products may cause  
operational problems, bad combustion or  
damage to controls. Locate unit at least  
3 feet (0.91m) from any wall or vertical  
surface to prevent wind conditions from  
• This unit is not intended for installations where  
temperatures may reach below 32°F (0°C). Exposure to  
freezing temperatures will cause the system and boiler  
to freeze and leak.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8
affecting performance.  
Outdoor Knight XL Installation & Operation Manual  
1 Determine boiler location  
Clearances from combustible materials  
1. Hot water pipes—at least 1/4" (6 mm) from combustible  
materials.  
2. Jacket—minimum of 0" from right side and 14" from rear  
side for proximity from combustible materials.  
3. Vent—minimum of 1" from combustible materials.  
(continued)  
Provide clearances:  
Under no circumstances is the manufacturer to be held  
responsible for water damage in connection with this  
appliance, or any of its components. If flooding is possible,  
elevate the boiler sufficiently to prevent water from reaching  
the boiler.  
Prevent combustion air contamination  
Do not install unit in locations that can allow contamination  
of combustion air. Refer to Table 1A for products and areas  
which may cause contaminated combustion air.  
Clearances for service access  
1. If you do not provide the minimum clearances shown, it  
may not be possible to service the boiler without removing  
it from the space.  
Table 1A Corrosive Contaminants and Sources  
Recommended service clearances  
Front: 30" (762mm)  
Top: 24" (610mm)  
Left side: 24" (610mm)  
Rear: 24" (610mm)  
Products to avoid:  
Spray cans containing chloro/fluorocarbons  
Permanent wave solutions  
Chlorinated waxes/cleaners  
Outdoor vent / air intake location:  
Chlorine-based swimming pool chemicals  
Calcium chloride used for thawing  
Sodium chloride used for water softening  
Refrigerant leaks  
The flue products discharged from the  
ƽ WARNING  
flue outlet on the outdoor vent may be  
very hot. Avoid touching or making other  
direct contact with the flue gases or the  
vent termination. These components are  
hot and direct contact can result in burns.  
Paint or varnish removers  
Hydrochloric acid/muriatic acid  
Cements and glues  
To prevent recirculation of the flue products into the  
combustion air inlet, follow all instructions in this section.  
Flue gas condensate can condense on exterior walls or on the  
vent. Some discoloration or exterior building or unit surfaces  
can be expected. Adjacent brick or masonry surfaces should  
be protected with a rust resistant sheet metal plate.  
Antistatic fabric softeners used in clothes dryers  
Chlorine-type bleaches, detergents, and cleaning solvents  
found in household laundry rooms  
Adhesives used to fasten building products and other  
similar products  
Maintain a minimum of 24" clearance to the air inlet.  
Locate the outdoor vent termination at least 48" (1.22m)  
below and 48" (1.22m) horizontally from any window, door,  
walkway or gravity air intake.  
Areas likely to have contaminants  
Dry cleaning/laundry areas and establishments  
Swimming pools  
Locate the unit at least 10 feet (3.05m) away from any forced  
inlet.  
Metal fabrication plants  
Beauty shops  
Multiple unit outdoor installations require 24" (1.22m)  
clearance between each vent termination.  
Refrigeration repair shops  
Photo processing plants  
Auto body shops  
Clearances around outdoor installations can change with  
time. Do not allow the growth of trees, shrubs or other plants  
to obstruct the proper operation of the outdoor vent system.  
Plastic manufacturing plants  
Furniture refinishing areas and establishments  
Flooring and foundation  
Flooring  
The Outdoor Knight XL is approved for installation on  
combustible flooring.  
New building construction  
Remodeling areas  
Do not install the boiler on carpeting even  
ƽ WARNING  
Garages with workshops  
if foundation is used. Fire can result,  
causing severe personal injury, death, or  
substantial property damage.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
2 Prepare boiler  
Remove boiler from wood pallet  
Install ue pipe assembly  
1. After removing the outer shipping carton from the  
boiler, remove the parts box.  
Models 400 - 601  
This unit is provided with all of the necessary venting  
components. All components must be installed prior to  
operation.  
2. Remove the front door to access the lag bolts in front  
of the unit (FIG. 2-1).  
1. Locate all venting components from the installation kit  
and carton.  
3. To remove the boiler from the pallet (after removing  
the front door):  
2. Before connecting the vent pipe sections or components,  
verify that the gasket is seated evenly inside the groove in  
the female end of the elbow and flue adaptor (FIG. 2-2).  
a. Remove the two lag bolts from the wood pallet  
inside the boiler (FIG. 2-1).  
b. Detachtheboilerfromthelagboltsintherearofthe  
unit, see FIG. 2-1.  
3. Remove the provided screws from the vent cover and use  
them to install the vent strap (FIG. 2-2).  
Do not drop the boiler or bump the  
NOTICE  
4. Insert the elbow into flue adaptor (FIG. 2-2).  
jacket on the floor or pallet. Damage to  
Do NOT use grease or other lubricant  
the boiler can result.  
ƽ CAUTION  
on the vent seals. Only water may be  
used for this purpose. Grease or other  
lubricant can make the seal brittle or  
cause tearing of the seal surface which  
can result in flue gas leakage.  
Figure 2-1 Boiler Mounted on Shipping Pallet  
5. Slide the vent pipe through the wall strap and insert it  
into the elbow (FIG. 2-2).  
6. Install the bird screen into the top of the vent.  
Figure 2-2 Install ue pipe assembly - Models 400 -  
601  
. 2  
WALL STRAP  
AND SCREWS  
BIRD SCREEN  
VENT PIPE  
ELBOW  
IMG00444  
FLUE  
ADAPTER  
NOTE: VERIFY THAT GASKET IS SEATED EVENLY  
INSIDE THE GROOVE IN ELBOW AND ADAPTER  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
2 Prepare boiler  
(continued)  
Models 701 - 801  
1. Locate all venting components from the installation kit and  
carton.  
2. Before connecting the vent pipe sections or components,  
verify that the gasket is seated evenly inside the groove  
in the female end of the elbow and flue adapter  
(FIG. 2-3).  
3. Remove the vent cover from the back of the unit as shown in  
FIG. 2-3.  
4. Insert the elbow into the flue adapter and tighten the clamp  
using a 5/16" nut driver (FIG. 2-3).  
5. Re-install the vent cover removed in Step 3.  
6. Remove the provided screws from the vent cover and use  
them to install the wall strap (FIG. 2-3).  
Do NOT use grease or other lubricant on the  
vent seals. Only water may be used for this  
ƽ CAUTION  
purpose. Grease or other lubricant can make  
the seal brittle or cause tearing of the seal  
surface which can result in flue gas leakage.  
7. Slide the vent pipe through the wall strap and insert it into the  
elbow. Tighten the clamp (FIG. 2-3).  
8. Install the termination into the top of the vent and tighten the  
clamp.  
Figure 2-3 Install ue pipe assembly - Models 701 - 801  
NOTE: VERIFY THAT GASKET IS SEATED EVENLY  
INSIDE THE GROOVE IN ELBOW AND ADAPTER  
VENT  
TERMINATION  
VENT PIPE  
IMG00446  
WALL  
STRAP  
CLAMP  
VENT COVER  
ELBOW  
WALL STRAP  
SCREWS  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
Outdoor Knight XL Installation & Operation Manual  
2 Prepare boiler  
Gas conversions  
For a boiler already installed, you must  
After converting to LP, check combustion  
per the Start-up procedure in Section 10  
of this manual. Failure to check and verify  
combustion could result in severe personal  
injury, death, or substantial property damage.  
ƽ WARNING  
ƽ WARNING  
turn off gas supply, turn off power and  
allow boiler to cool before proceeding.  
You must also completely test the boiler  
after conversion to verify performance  
as described under Start-up, Section 10  
of this manual. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
Model 400: Inspect the O-ring when the  
blower is disassembled. The O-ring must  
be in good condition and must be installed.  
Failure to comply will cause a gas leak,  
resulting in severe personal injury or death.  
ƽ DANGER  
For the 400 Model you must install a  
propane orifice to operate the Outdoor  
Knight XL on propane gas. Verify when  
installing that the orifice size marking  
matches boiler size (Model 400 - 8.0 LP  
orifice stamping).  
Figure 2-4 Installing Propane Orice - Model 400  
BLOWER  
Models 501 - 801 do not require an orifice  
installation for propane operation, but  
they will require a valve adjustment.  
O-RING  
VENTURI  
SCREWS  
QTY. 3  
Model 400  
1. Remove the top and front access covers from the unit  
(tools required for removal).  
2. Remove the three screws securing the venturi to the  
blower. Note: When separating the venturi from the  
blower, take care not to damage the O-ring inside the  
blower (FIG. 2-4).  
SCREWS  
QTY. 4  
O-RING  
BRASS ORIFICE  
3. Remove the four star-drive screws securing the gas valve  
to the venturi (FIG. 2-4).  
GAS VALVE  
4. Locate the propane orifice disk from the conversion kit  
bag.Verify that the stamping on the orifice disk matches  
the boiler size (Model 400 - 8.0 LP orifice stamping).  
5. Remove the existing orifice from the O-ring in the side of  
the gas valve and replace it with the orifice from the kit.  
Position and secure the orifice in the valve as shown in  
FIG. 2-4.  
6. Reposition the gas valve against the venturi and replace  
the star-drive screws (FIG. 2-4) securing the valve to the  
venturi.  
7. Inspect the O-ring inside the blower. Handle the O-ring  
with care, do not damage. Reposition the venturi against  
the blower and replace the screws securing the venturi to  
the blower (FIG. 2-4).  
8. After installation is complete, attach the propane  
conversion label (in the conversion kit bag) next to the  
boiler rating plate. Attach the LP caution label (in the  
conversion kit bag) to the left side of the unit in the lower  
left corner.  
9. Replace the top and front access covers.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12  
Outdoor Knight XL Installation & Operation Manual  
2 Prepare boiler  
(continued)  
Model 501  
After converting to LP, check combustion  
ƽ WARNING  
per the Start-up procedure in Section  
10 of this manual. Failure to check and  
verify combustion could result in severe  
personal injury, death, or substantial  
property damage.  
1. Remove the top access cover from the unit (Philips Head  
screwdriver required for removal).  
2. Turn the adjustment screw on the gas valve clockwise until  
it stops. Then turn the adjustment screw counterclockwise  
four and three quarter (4 3/4) turns (see FIG. 2-5).  
Figure 2-6 Gas Valve Adjustment - Models 601 - 801  
3. Use a combustion analyzer to verify CO2 is within the range  
of 9.6 – 10.5%. If not, adjust the screw counterclockwise  
incrementally to raise CO2 and clockwise to lower CO2  
(FIG. 2-5).  
COVER  
ALLEN WRENCH  
4. After adjustment is complete, attach the propane conversion  
label (in the conversion kit bag) next to the boiler rating  
plate. Attach the LP caution label (in the conversion kit bag)  
to the left side of the unit in the lower left corner.  
ADJUSTMENT SCREW  
5. Replace the top access cover.  
After converting to LP, check combustion  
ƽ WARNING  
per the Start-up procedure in Section 10  
of this manual. Failure to check and verify  
combustion could result in severe personal  
injury, death, or substantial property  
damage.  
Figure 2-5 Gas Valve Adjustment - Model 501  
Leveling the boiler  
ALLEN WRENCH  
1. Set the boiler in place and check level.  
a) Adjust legs if necessary to level boiler, see FIG. 2-7  
below.  
Figure 2-7 Leveling Legs on the Boiler  
SCREWDRIVER  
SLOT  
ADJUSTMENT SCREW  
Models 601 - 801  
1. Remove the top access cover from the unit (Philips Head  
screwdriver required for removal).  
2. Remove the cover on top of the gas valve (FIG. 2-6).  
3. Turn the adjustment screw on top of the gas valve clockwise  
one and three quarter (1 3/4) turns on the 601 Model, one  
and a half (1 1/2) turns on the 701 Model, and one turn on  
the 801 Model (see FIG. 2-6).  
LOWER  
RAISE  
4. Use a combustion analyzer to verify CO2 is within the range  
of 9.6 – 10.5%. If not, adjust the screw counterclockwise  
incrementally to raise CO2 and clockwise to lower CO2  
(FIG. 2-6).  
5. After adjustment is complete, attach the propane conversion  
label (in the conversion kit bag) next to the boiler rating  
plate. Attach the LP caution label (in the conversion kit  
bag) to the left side of the unit in the lower left corner.  
6. Replace the gas valve cover along with the top access cover.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
3 Hydronic piping  
System water piping methods  
General piping information  
Basic steps are listed below along with illustrations on the  
following pages (FIG.’s 3-7 through 3-11), which will guide  
you through the installation of the Outdoor Knight XL  
(reference FIG.’s 3-4A and 3-4B).  
The Outdoor Knight XL is designed to function in a closed  
loop pressurized system not less than 12 psi (83 kPa).  
A
temperature and pressure gauge is included to monitor  
system pressure and outlet temperature and should be  
located on the boiler outlet.  
1. Connect the system return marked “Inlet”.  
2. Connect the system supply marked “Outlet”.  
It is important to note that the boiler has a minimal amount  
of pressure drop which must be figured in when sizing  
the circulators. Each boiler installation must have an air  
elimination device, which will remove air from the system.  
Install the boiler so the gas ignition system components  
are protected from water (dripping, spraying, etc.) during  
appliance operation or basic service of circulator replacement,  
valves, and others.  
3. Install purge and balance valve or shutoff valve and drain  
on system return to purge air out of each zone.  
4. Install a backflow preventer on the cold feed make-up  
water line.  
5. Install a pressure reducing valve on the cold feed make-up  
water line, (15 psi (103 kPa) nominal). Check temperature  
and pressure gauge (shipped separately), which should  
read a minimum pressure of 12 psi (83 kPa).  
Observe a minimum of 1/4 inch (6 mm) clearance around all  
un-insulated hot water pipes when openings around the pipes  
are not protected by non-combustible materials.  
6. Consult the factory for a pump and/or pump cover. If a  
field-supplied pump is used, install per the manufacturer’s  
specifications in regard to indoor or outdoor location. An  
outdoor rated pump is recommended.  
Low water cutoff device  
7. Install a circulator as shown on the piping diagrams in this  
section. Make sure the circulator is properly sized for the  
system and friction loss.  
On a boiler installed above radiation level, some states and  
local codes require a low water cutoff device at the time of  
installation.  
8. Install an expansion tank on the system supply. Consult the  
tank manufacturer’s instruction for specific information  
relating to tank installation. Size the expansion tank for the  
required system volume and capacity.  
Chilled water system  
If the boiler supplies hot water to heating coils in air handler  
units, flow control valves or other devices must be installed to  
prevent gravity circulation of heater water in the coils during  
the cooling cycle. A chilled water medium must be piped in  
parallel with the heater.  
9. Install an air elimination device on the system supply.  
10. Install a drain valve at the lowest point of the system.  
Note: The boiler cannot be drained completely of water  
without purging the unit with an air pressure of 15 psi  
(103 kPa).  
Freeze protection  
11. This appliance is supplied with a relief valve sized in  
accordance with ASME Boiler and Pressure Vessel Code,  
Section IV (“Heating Boilers”). Pipe the discharge of the  
safety relief valve to prevent injury in the event of pressure  
relief. Pipe the discharge to a drain. Provide piping that is  
the same size as the safety relief valve outlet. Never block  
the outlet of the safety relief valve.  
Freeze protection for new or existing systems must use  
glycol that is specially formulated for this purpose. This  
includes inhibitors, which prevent the glycol from attacking  
the metallic system components. Make certain to check that  
the system fluid is correct for the glycol concentration and  
inhibitor level. The system should be tested at least once  
a year and as recommended by the producer of the glycol  
solution. Allowance should be made for the expansion of the  
glycol solution in the system piping.  
The relief valve, tee and any other necessary  
ƽ WARNING  
fittings are shipped in the install kit with the  
boiler and are to be field installed (FIG.’s  
3-1 and 3-2).  
Use only inhibited propylene glycol  
ƽ WARNING  
12. On any pre-existing system, it is good practice to install  
a field supplied strainer to prevent damage to the heat  
exchanger.  
solutions, which are specifically formulated  
for hydronic systems. Ethylene glycol is  
toxic and can attack gaskets and seals used  
in hydronic systems.  
See the piping illustrations included in this section, FIG.’s  
3-7 and 3-11 for suggested guidelines in piping the Outdoor  
Knight XL.  
Please note that these illustrations are  
NOTICE  
meant to show system piping concept only,  
the installer is responsible for all equipment  
Download from Www.Somanuals.com. All Manuals Search AannddDodwentaloialidn.g required by local codes.  
14  
Outdoor Knight XL Installation & Operation Manual  
3 Hydronic piping  
(continued)  
Flowswitch,reliefvalveandtemperature  
and pressure gauge installation  
Figure 3-1 Flow Switch, Relief Valve and Temperature and  
Pressure Gauge Installation_Models 400 - 501  
Basic steps are listed below to guide you through the  
installation of the flow switch, relief valve, and temperature  
and pressure gauge provided with the unit.  
1. For Models 400 - 501 install the close nipple on the  
outlet connection of the heat exchanger. Install the tee  
with the 3/4 inch fitting positioned vertically and on  
the top as shown in FIG. 3-1. For Models 601 - 801  
install the tee directly to the outlet connection of the  
heat exchanger with the 3/4 inch fitting positioned  
vertically and on the top (see FIG. 3-2).  
RELIEF VALVE  
FLOW SWITCH  
PADDLE  
TEMPERATURE &  
PRESSURE GAUGE  
2. For Models 701 - 801 install the 3/4 inch close nipple  
in the tee. Install the relief valve on the 3/4 inch close  
nipple (FIG. 3-2). For Models 400 - 601 install the  
relief valve directly into the 3/4 inch fitting on the tee  
(FIG. 3-1).  
TEE WITH FITTING  
ON TOP  
(FIELD PROVIDED)  
CLOSE NIPPLE  
3. Install the close nipple on the downstream side of  
the relief valve tee (FIG. 3-1).  
(FIELD PROVIDED)  
IMG00390  
TEE WITH 1" FITTING ON TOP  
8' NIPPLE  
(REQUIRED FOR MODELS 400 - 701)  
CLOSE NIPPLE  
TEE WITH 3/4"  
4. Install the tee with the 1 inch fitting positioned  
vertically and on the top (FIG. 3-1).  
FITTING ON TOP  
5. Attach paddle #3 to the flow switch per the  
manufacturer’s instructions.  
Figure 3-2 Flow Switch, Relief Valve and Temperature and  
Pressure Gauge Installation_Models 601 - 801  
6. Install the assembled flow switch into the 1 inch fitting  
of the tee installed in Step 4 (see FIG. 3-1).  
7. Install a field provided close nipple on the downstream  
side of the flow switch (see FIG.’s 3-1 and 3-2).  
RELIEF VALVE  
8. Install a field provided tee with the gauge fitting  
positioned vertically and on the top (FIG.’s 3-1 and  
3-2)  
FLOW SWITCH  
PADDLE  
9. Install the temperature and pressure gauge provided  
with the unit into the top fitting of the tee (a bushing  
may be necessary) installed in Step 8 (FIG.’s 3-1 and  
3-2).  
TEMPERATURE &  
PRESSURE GAUGE  
TEE WITH FITTING  
(FIELD PROVIDED)  
Be sure to install the flow switch so  
NOTICE  
that the arrow on the flow switch is  
pointing in the direction of the flow  
(see FIG. 3-3).  
CLOSE NIPPLE  
(FIELD PROVIDED)  
TEE WITH 1" FITTING  
ON TOP  
IMG00389  
CLOSE NIPPLE  
TEE WITH 3/4"  
FITTING ON TOP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
Outdoor Knight XL Installation & Operation Manual  
3 Hydronic piping  
Flow switch adjustment  
Near boiler piping components  
Refer to Table 3A for the proper setting of the sensitivity  
screw. For reference, the position of the screw prior to setting  
should be turned clockwise with a Phillips driver until it stops  
(FIG. 3-3). Proceed to turn the screw counterclockwise the  
amount of turns listed in Table 3A based on the model.  
1. Boiler system piping:  
Boiler system piping MUST be sized per the pipe  
requirements listed in Table 3B. Reducing the pipe size  
can restrict the flow rate through the boiler, causing  
inadvertent high limit shutdowns and poor system  
performance. Flow rates are based on 20 feet (6 m) of  
piping, 4 - 90° elbows, and 2 - fully ported ball valves.  
Consult the manufacturer’s instructions for wiring the flow  
switch to your system.  
2. Boiler system circulating pump:  
(Field supplied.) The boiler circulating pump should be  
based on 20 feet (6 m) of piping, 4 - 90° elbows, and  
2 - fully ported ball valves.  
Table 3A Paddle Size / Sensitivity Screw Adjustment  
SENSITIVITY SCREW  
MODEL  
PADDLE SIZE  
ADJUSTMENT  
Note: Paddles are included with the ow switch.  
3. Domestic hot water circulating pump:  
(Field supplied.) The pump MUST be sized to meet  
the specified minimum flow requirements listed in  
FIG.’s 3-5 and 3-6. Consult the indirect water heater  
operating guide to determine flow characteristics for the  
selected product used.  
400  
501  
601  
701  
801  
#3  
#3  
#3  
#3  
#3  
7½ turns  
5½ turns  
7¼ turns  
5¼ turns  
3¼ turns  
Turn the sensitivity screw clockwise to  
increase the flow rate required to activate  
the switch. Turn the sensitivity screw  
counterclockwise to decrease the flow rate  
required to activate the switch.  
4. Variable speed boiler system circulator:  
Outdoor Knight XL boilers are capable of controlling  
a variable speed boiler system circulator. Variable speed  
circulators MUST be sized to meet the specified minimum  
flow requirements listed in FIG.’s 3-5 and 3-6 on page 16  
at full speed.  
NOTICE  
Figure 3-3 Flow Switch Adjustment  
NORMALLY  
OPEN  
5. Boiler isolation valves:  
Field supplied. Full port ball valves are required. Failure  
to use full port ball valves could result in a restricted flow  
rate through the boiler.  
SENSITIVITY  
ADJUSTMENT  
6. Check valves:  
Field supplied. Check valves are recommended for  
installation as shown in FIG.’s 3-7 through 3-11. Failure  
to install check valves could result in a reverse flow  
condition during pump(s) off cycle.  
GROUND  
7. Domestic indirect hot water isolation valves:  
Field supplied. Full port ball valves are required. Failure  
to use full port ball valves could result in a restricted flow  
rate through the boiler.  
NORMALLY  
CLOSED  
COMMON  
8. Anti-scald mixing valve:  
Field supplied. An anti-scald mixing valve is  
recommended when storing domestic hot water above  
115°F (46°C).  
9. Unions:  
Field supplied. Recommended for unit serviceability.  
10. Temperature and pressure gauge:  
Factory supplied. The temperature and pressure gauge is  
shipped loose. It is the responsibility of the contractor to  
install the temperature and pressure gauge on the boiler  
water outlet.  
11. Pressure relief valve:  
Factory supplied. The pressure relief valve is sized to  
ASME specifications.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
3 Hydronic piping  
(continued)  
12. Boiler purge valve:  
Figure 3-4B Near Boiler Piping w/Low Loss Header  
Field supplied. The boiler purge valve is used to  
remove entrapped air from the heat exchanger during  
start-up.  
SYSTEM PUMP  
SYSTEM SENSOR  
AIR SEPARATOR  
DRAIN  
(TYPICAL)  
13. System temperature sensor:  
AIR VENT VALVE  
Lochinvar supplies a system temperature sensor. The  
sensor is to be installed in the heating loop downstream  
from the boiler hot water piping and heating loop  
junction. The sensor should be located far enough  
downstream to sense system diluted water temperature.  
LOW LOSS HEADER  
(TYPICAL)  
FAST FILL VALVE  
EXPANSION TANK  
INDIRECT  
DOMESTIC  
DRAIN  
14. Y-Strainer:  
HOT WATER  
VALVE  
TANK  
Field supplied. A Y-strainer or equivalent multipurpose  
strainer is recommended at the inlet of the heat exchanger  
to remove system particles from older hydronic systems  
and protect newer systems.  
Y-STRAINER  
(RECOMMENDED)  
BOILER PUMP  
Circulator sizing  
The Outdoor Knight XL heat exchanger does have a pressure  
drop, which must be considered in your system design. Refer  
to the graphs in FIG’s 3-5 and 3-6 for pressure drop through  
the Outdoor Knight XL heat exchanger.  
Near boiler piping connections  
IMG00391  
Figure 3-4A Near Boiler Piping w/Y-Strainer  
TO FLOOR  
DRAIN  
Variable speed pump option  
Variable speed pump setup  
SYSTEM SENSOR  
DOMESTIC HOT  
AIR SEPARATOR  
WATER PUMP  
Before operation, ensure the following:  
INDIRECT  
SYSTEM PUMP  
-
Pump is set for an input signal of 0 - 10VDC  
by the dip switches on the pump control  
DOMESTIC  
HOT WATER  
TANK  
-
Pump is set for external signal control  
(if applicable)  
-
-
Pump is set for linear output (if applicable)  
Y-STRAINER  
(RECOMMENDED)  
If pump does not come equipped with a  
0 - 10 VDC input option, an optional module  
will be required from the vendor  
BOILER PUMP  
SMART SYSTEM / Multi-temperature  
loop control option  
The Outdoor Knight XL boiler is capable of producing  
up to three (3) set point temperatures to meet different  
space heating demands. When using more than one  
temperature demand it is necessary to protect the  
lower temperature loop from overheating. To help  
aid with this protection, Lochinvar offers the Multi-  
Temperature Loop Control Board Kit (RLY30086).  
IMG00413  
TO FLOOR  
DRAIN  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
3 Hydronic piping  
Figure 3-5 Pressure Drop vs. Flow - Models 400 and 501  
Pressure Drop vs Flow  
(Includes Boiler Secondary Piping)  
20  
18  
16  
14  
12  
10  
8
KBN501  
KBN400  
O
O
6
4
2
0
0
5
10  
15  
20  
25  
30  
35  
40  
45  
Flow Rate (GPM)  
Figure 3-6 Pressure Drop vs. Flow - Models 601 thru 801  
Pressure Drop vs Flow  
(Includes Boiler Secondary Piping)  
60  
50  
40  
30  
20  
10  
0
KBN801  
O
O
KBN701  
O
KBN601  
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
Flow Rate (GPM)  
Table 3B Sizing Information for Temperature Rise Applications_20°F, 25°F, 30°F and 35°F  
TEMPERATURE RISE APPLICATIONS  
20°F  
25°F  
30°F  
35°F  
MINIMUM  
PIPE  
Model  
GPM  
FT/HD  
GPM  
FT/HD  
GPM  
FT/HD  
GPM  
FT/HD  
SIZE  
400  
501  
601  
701  
801  
1 1/2"  
1 1/2"  
2"  
37  
46  
55  
65  
74  
21  
23  
31  
30  
33  
30  
37  
44  
52  
60  
14  
16  
22  
20  
23  
26  
32  
38  
45  
51  
11  
13  
18  
16  
18  
21  
26  
32  
37  
42  
8
10  
13  
11  
12  
2"  
2"  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
3 Hydronic piping  
(continued)  
Figure 3-7 Single Boiler - Multiple Temperatures  
RE  
TEMPERATU  
RE  
TEMPERATU  
LOOP 3  
RE  
TEMPERATU  
S
OP SENSOR  
WIRES TO LO  
LOOP 2  
LOOP 1  
(3X)  
LOOP SENSOR  
120VAC  
TO PUMPS  
TER  
MAKE UP WA  
AIR SEPARAT  
PRESSURE  
OR  
MULTI-TEMP  
LOOP CONTROL  
(OPTIONAL)  
GAUGE  
TO  
SYSTEM  
BACK FLOW  
PREVENTER  
O
24V SIGNAL T  
FROM  
SYSTEM  
S
MIXING VALVE  
NDED)  
(RECOMME  
Y-STRAINER  
BALL VALVE  
(TYPICAL)  
K VALVE  
FLOW CHEC  
(TYPICAL)  
CULATOR  
BOILER CIR  
EXPANSION  
TANK  
PRESSURE  
ABLE  
SHIELDED C  
REDUCING  
VALVE  
NTROL  
TO BOILER CO  
HW  
INDIRECT D  
TANK  
BOILER  
PRESSURE  
RELIEF  
VALVE  
UT  
HOT WATER O  
ANTI-SCALD  
ICAL)  
UNION (TYP  
MIXING VALVE  
DOMESTIC  
N
COLD WATER I  
HOT WATER  
R
CIRCULATO  
IMG00392  
Mixing valves are required for the protection of low temperature loops.  
CAUTION  
NOTICE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
Please note that these illustrations show an indoor tank to demonstrate piping concept only.  
NOTICE  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
3 Hydronic piping  
Figure 3-8 Single Boiler - Primary/Secondary Piping  
AIR SEPARATOR  
MAY SUBSTITUTE  
LOW LOSS HEADE  
R
DRAIN POINT  
(TYPICAL)  
NOT TO EXCEED 4  
PIPE DIA OR MA  
X. OF 12" APART  
SYSTEM SUPPLY  
SENSOR  
(WHEN USED)  
BALL VALVE  
(TYPICAL)  
SYSTEM CIRCULA  
TOR  
Y-STRAINER  
EXPANSION TANK  
(RECOMMENDED)  
BOILER CIRCULAT  
OR  
MAKE UP WATER  
BACK FLOW  
PREVENTER  
PRESSURE REDU  
CING  
VALVE  
INDIRECT DHW  
TANK  
ANTI-SCALD  
MIXING VALVE  
HOT WATER OUT  
DOMESTIC  
HOT WATER  
CIRCULATOR  
UNION (TYPICAL)  
BOILER  
COLD WATER IN  
PRESSURE RELIEF  
VALVE  
DRAIN  
IMG00393  
FLOW CHECK  
VALVE (TYPICAL)  
Indirect water heaters are capable of transferring a limited number of Btu’s into the water. Ensure boiler  
output does not not exceed indirect water heater transfer capabilities.  
CAUTION  
NOTICE  
NOTICE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in  
operation to prevent short cycling and high limit issues.  
Please note that these illustrations show an indoor tank to demonstrate piping concept only.  
NOTICE  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
3 Hydronic piping  
(continued)  
Figure 3-9 Multiple Boilers - Multiple Temperatures  
Number of Units  
2
3
4
5
6
7
8
Model  
Manifold Pipe Sizes in Inches (mm)  
2 1/2 (64) 3 (76) 3 1/2 (89) 4 (102) 4 (102) 5 (127) 6 (152)  
3 (76) 3 1/2 (89) 4 (102) 5 (127) 5 (127) 6 (152) 6 (152)  
3 1/2 (89) 4 (102) 5 (127) 5 (127) 6 (152) 6 (152) 8 (203)  
400  
501  
601  
3 1/2 (89) 5 (127) 5 (127) 6 (152) 6 (152) 8 (203) 8 (203)  
4 (102) 5 (127) 5 (127) 6 (152) 8 (203) 8 (203) 8 (203)  
701  
801  
WIRES TO  
LOOP SENSORS  
TEMPERATURE  
LOOP 3  
TEMPERATURE  
LOOP 2  
120VAC  
MULTI-TEMP  
LOOP CONTRO  
(OPTIONAL)  
TO PUMPS  
TEMPERATURE  
LOOP 1  
L
24V SIGNAL TO  
MIXING VALVES  
LOOP SENSOR  
(3X)  
TO  
SYSTEM  
AIR SEPARATOR  
SHIELDED CABLE  
TO BOILER CON  
TROL  
FROM  
SYSTEM  
Y-STRAINER  
MAKE UP WATER  
(RECOMMENDED)  
FLOW CHECK  
VALVE (TYPICAL)  
BALL VALVE  
(TYPICAL)  
BACK FLOW  
PREVETER  
PRESSURE  
GAUGE  
EXPANSION  
DRAIN POINT  
(TYPICAL)  
TANK  
INDIRECT DHW  
TANK  
ANTI-SCALD  
BOILER 2  
PRESSURE  
RELIEF  
MIXING VALVE  
VALVE  
DOMESTIC  
TEMPERATURE/PRESS  
GAUGE  
URE  
COLD WATER IN  
HOT WATER  
CIRCULATOR  
UNION (TYPICAL  
)
BOILER CIRCUL  
ATOR  
BOILER 1  
IMG00394  
Indirect water heaters are capable of transferring a limited number of Btu’s into the water. Ensure boiler  
output does not not exceed indirect water heater transfer capabilities.  
CAUTION  
Mixing valves are required for the protection of low temperature loops.  
CAUTION  
NOTICE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
Please note that these illustrations show an indoor tank to demonstrate piping concept only.  
21  
NOTICE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
3 Hydronic piping  
Figure 3-10 Multiple Boilers - Primary/Secondary Piping  
Number of Units  
2
3
4
5
6
7
8
Model  
Manifold Pipe Sizes in Inches (mm)  
2 1/2 (64) 3 (76) 3 1/2 (89) 4 (102) 4 (102) 5 (127) 6 (152)  
3 (76) 3 1/2 (89) 4 (102) 5 (127) 5 (127) 6 (152) 6 (152)  
3 1/2 (89) 4 (102) 5 (127) 5 (127) 6 (152) 6 (152) 8 (203)  
400  
501  
601  
701  
801  
3 1/2 (89) 5 (127) 5 (127) 6 (152) 6 (152) 8 (203) 8 (203)  
4 (102) 5 (127) 5 (127) 6 (152) 8 (203) 8 (203) 8 (203)  
BALL VALVE  
(TYPICAL)  
MAY SUBSTITUTE  
LOW LOSS HEADER  
AIR SEPARATOR  
DRAIN POINT  
(TYPICAL)  
SYSTEM SUPPLY SENSOR  
(WHEN USED)  
SYSTEM CIRCULATOR  
MAKE UP WATER  
Y-STRAINER  
(TYPICAL)  
(RECOMMENDED)  
EXPANSION  
TANK  
BACK FLOW  
PREVENTER  
PRESSURE REDUCING  
VALVE  
BOILER 4  
PRESSURE GAUGE  
(MEMBER 3)  
INDIRECT DHW  
TANK  
BOILER 3  
(MEMBER 2)  
ANTI-SCALD  
MIXING VALVE  
BOILER 2  
(MEMBER 1)  
HOT WATER OUT  
IMG00417  
BOILER 1  
DOMESTIC  
HOT WATER  
CIRCULATOR  
(LEADER)  
BOILER CIRCULATOR  
PRESSURE RELIEF  
VALVE  
(TYPICAL)  
COLD WATER IN  
DRAIN  
FLOW CHECK  
UNION (TYPICAL)  
TEMPERATURE /  
VALVE (TYPICAL)  
PRESSURE GAUGE  
Indirect water heaters are capable of transferring a limited number of Btu’s into the water. Ensure boiler  
output does not not exceed indirect water heater transfer capabilities.  
CAUTION  
NOTICE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in  
operation to prevent short cycling and high limit issues.  
NOTICE  
Please note that these illustrations show an indoor tank to demonstrate piping concept only.  
NOTICE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
22  
Outdoor Knight XL Installation & Operation Manual  
3 Hydronic piping  
(continued)  
Figure 3-11 Single Boiler - Multiple Temperatures with DHW Piped as a Zone  
WIRES TO  
TEMPERATURE  
LOOP SENSORS  
LOOP 3  
TEMPERATURE  
LOOP 2  
TEMPERATURE  
LOOP 1  
LOOP SENSOR (3X)  
120VAC TO  
PUMPS  
MAKE UP WATER  
AIR SEPARATOR  
BACK FLOW  
PREVENTER  
TO  
SYSTEM  
PRESSURE  
BALL VALVE  
GAUGE  
FROM  
SYSTEM  
(TYPICAL)  
MULTI-TEMP  
LOOP CONTROL  
(OPTIONAL)  
Y-STRAINER  
24VAC SIGNAL  
TO MIXING VALVES  
(RECOMMENDED)  
FLOW CHECK  
VALVE (TYPICAL)  
BOILER CIRCULATOR  
PRESSURE  
REDUCING  
VALVE  
DRAIN POINT  
(TYPICAL)  
EXPANSION  
SHIELDED CABLE  
TO BOILER CONTROL  
TANK  
INDIRECT DHW  
TANK  
HOT WATER OUT  
BOILER  
ANTI-SCALD  
MIXING VALVE  
DOMESTIC  
HOT WATER  
CIRCULATOR  
UNION (TYPICAL)  
DRAIN  
COLD WATER IN  
TEMPERATURE / PRESSURE  
PRESSURE RELIEF  
VALVE  
IMG00412  
GAUGE  
Indirect water heaters are capable of transferring a limited number of Btu’s into the water. Ensure boiler  
output does not not exceed indirect water heater transfer capabilities.  
CAUTION  
Mixing valves are required for the protection of low temperature loops.  
CAUTION  
NOTICE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
Please note that the installer is responsible for ensuring DHW prioritization when piped as a zone.  
Please note that these illustrations show an indoor tank to demonstrate piping concept only.  
NOTICE  
NOTICE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
23  
Outdoor Knight XL Installation & Operation Manual  
4 Gas connections  
Connecting gas supply piping  
Figure 4-3 Gas Supply Piping - Models 601 - 801  
GAS SUPPLY  
1. Remove the top access panel and refer to FIG.’s 4-1 thru  
4-3 to pipe gas to the boiler.  
a. Install ground joint union for servicing, when  
required.  
b. Install a manual shutoff valve in the gas supply  
piping outside boiler jacket when required by local  
codes or utility requirements.  
2. Install sediment trap / drip leg.  
Figure 4-1 Gas Supply Piping - Model 400  
MANUAL SHUTOFF VALVE  
(FACTORY SUPPLIED)  
UNION  
GAS SUPPLY  
IMG00328  
SEDIMENT TRAP  
/ DRIP LEG  
3. Support piping with hangers, not by the boiler or its  
accessories.  
The gas valve and blower will not support  
the weight of the piping. Do not attempt  
ƽ WARNING  
SEDIMENT TRAP /  
DRIP LEG  
to support the weight of the piping with  
the boiler or its accessories. Failure to  
comply could result in severe personal  
injury, death, or substantial property  
damage.  
MANUAL  
SHUTOFF  
VALVE  
(FIELD SUPPLIED)  
4. Purge all air from the gas supply piping.  
IMG00411  
5. Before placing the boiler in operation, check the boiler  
and its gas connection for leaks.  
Figure 4-2 Gas Supply Piping - Model 501  
a. The appliance must be disconnected from the gas  
supply piping system during any pressure testing of  
that system at a test pressure in excess of 1/2 PSIG  
(3.5 kPa).  
UNION  
(FACTO  
RY INST  
ALLED)  
GAS SU  
PPLY  
b. The appliance must be isolated from the gas supply  
piping system by closing a manual shutoff valve  
during any pressure testing of the gas supply piping  
system at test pressures equal to or less than 1/2 PSIG  
(3.5 kPa).  
SEDIME  
NT TRAP/  
DRIP LE  
G
c. The appliance and its gas connection must be leak  
tested before placing it in operation.  
MANUAL  
Do not check for gas leaks with an open  
ƽ WARNING  
SHUTOFF VAL  
VE  
(FACTOR  
Y SUPPLI  
ED)  
flame – use the bubble test. Failure to  
use the bubble test or check for gas leaks  
can cause severe personal injury, death, or  
substantial property damage.  
6. Use pipe sealing compound compatible with propane  
gases. Apply sparingly only to male threads of the pipe  
joints so that pipe dope does not block gas flow.  
IMG00410  
Download from Www.Somanuals.com. All Manuals Search And Download.  
24  
Outdoor Knight XL Installation & Operation Manual  
4 Gas connections  
(continued)  
Failure to apply pipe sealing compound  
as detailed in this manual can result  
in severe personal injury, death, or  
substantial property damage.  
Natural gas:  
Pipe sizing for natural gas  
ƽ WARNING  
1. Refer to Table 4A for pipe length and diameter. Based on  
rated boiler input (divide by 1,000 to obtain cubic feet per  
hour).  
Use two wrenches when tightening gas  
piping at boiler (FIG. 4-4), using one  
wrench to prevent the boiler gas line  
connection from turning. Failure to  
support the boiler gas connection pipe  
to prevent it from turning could damage  
gas line components.  
ƽ WARNING  
a. Table 4A is only for natural gas with specific gravity  
0.60 inches, with a pressure drop through the gas  
piping of 0.5 inches w.c.  
b. For additional gas pipe sizing information, refer to  
ANSI Z223.1 (or B149.1 for Canadian installations).  
Figure 4-4 Inlet Pipe with Backup Wrench  
Natural gas supply pressure requirements  
1. Pressure required at the gas valve inlet pressure port:  
USE BACKUP WRENCH  
TO PREVENT PIPE FROM  
ROTATING  
• Maximum 14 inches w.c. (3.5 kPa) with no flow  
(lockup) or with boiler on.  
• Minimum 4 inches w.c. (.99 kPa) with gas flowing (verify  
during boiler startup).  
2. Install 100% lockup gas pressure regulator in supply line  
if inlet pressure can exceed 14 inches w.c. (3.5 kPa) at any  
time. Adjust lockup regulator for 14 inches w.c. (3.5 kPa)  
maximum.  
Propane Gas:  
Outdoor Knight XL boilers are typically  
shipped ready to fire on natural gas. Check  
ƽ WARNING  
IMG00420  
boiler rating plate to determine which fuel  
the boiler is set for. If set to natural gas, it  
may be converted to LP by installing an  
orifice or by making a gas valve adjustment  
(see page 12). In order to operate on LP  
gas, an orifice MUST BE installed or a gas  
valve adjustment MUST BE made. Failure  
to comply could result in severe personal  
injury, death, or substantial property  
damage.  
Maximum inlet gas pressure must not  
exceed the value specified. Minimum  
value listed is for the purposes of input  
adjustment.  
NOTICE  
Pipe sizing for propane gas  
1. Contact gas supplier to size pipes, tanks, and 100% lockup  
gas pressure regulator.  
Propane Supply Pressure Requirements  
1. Adjust propane supply regulator provided by the gas  
supplier for 14 inches w.c. (3.2 kPa) maximum pressure.  
2. Pressure required at gas valve inlet pressure port:  
• Maximum 14 inches w.c. (3.2 kPa) with no flow (lockup)  
or with boiler on.  
• Minimum 8 inches w.c. (1.9 kPa) with gas flowing (verify  
during boiler startup).  
Ensure that the high gas pressure regulator  
is at least 10 feet (3 m) upstream of the  
ƽ WARNING  
appliance.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
25  
Outdoor Knight XL Installation & Operation Manual  
4 Gas connections  
Table 4A Natural Gas Pipe Size Chart  
Maximum  
Nominal  
Iron Pipe  
Size  
Natural Gas Pipe Capacity Chart  
Length of Pipe in Straight Feet  
Capacity of Pipe  
in Thousands of  
Btu/hr per hour  
for gas pressures  
of 14 Inches  
Water Column  
(0.5 PSIG) or less  
and a pressure  
drop of 0.5 Inch  
Water Column  
(Based on NAT  
GAS, 1025 Btu/  
hr per Cubic Foot  
of Gas and 0.60  
Specific Gravity)  
(inches)  
10  
20  
30  
40  
50  
60  
70  
80  
90 100 125 150 175 200  
175  
369  
697  
120  
256  
477  
97  
82  
N/A  
155  
292  
595  
N/A N/A N/A N/A N/A N/A N/A N/A N/A  
1/2  
3/4  
1
205  
384  
789  
174  
328  
677  
141 128 121 113 106  
95  
86  
79  
74  
267 246 236 210 200 179 164 149 138  
543 502 472 441 410 369 333 308 287  
830 769 707 666 636 564 513 472 441  
1400 974  
1-1/4  
1-1/2  
2
2150 1500 1210 1020 923  
4100 2820 2260 1950 1720 1560 1440 1330 1250 1180 1100 974 871 820  
6460 4460 3610 3100 2720 2460 2310 2100 2000 1900 1700 1540 1400 1300  
11200 7900 6400 5400 4870 4410 4000 3800 3540 3330 3000 2720 2500 2340  
23500 16100 13100 11100 10000 9000 8300 7690 7380 6870 6150 5640 5130 4720  
2-1/2  
3
4
Check inlet gas supply  
CSA or UL listed flexible gas connections  
4. Slowly turn on the gas supply at the field installed  
manual gas valve.  
NOTICE  
are acceptable, but you must exercise  
caution to ensure that the line has adequate  
capacity to allow your boiler to fire at full  
rate. Consult with local codes for proper  
installation or service procedures.  
5. Turn the power switch to the “ON” position.  
6. Adjust the temperature set point on the control panel of  
the SMART SYSTEM control module to call for heat.  
7. Observe the gas supply pressure as the burner fires at  
100% of rated input. Percent of burner input will be  
displayed on the control panel.  
DO NOT adjust gas valve outlet pressure.  
Attempting to alter the gas valve outlet  
pressure could result in damage to the valve,  
causing potential severe personal injury,  
death, or substantial property damage.  
ƽ WARNING  
8. Ensure inlet pressure is within specified range.  
Minimum and maximum gas supply pressures are  
specified in this section of the manual.  
The gas piping must be sized for the proper flow and length of  
pipe, to avoid excessive pressure drop. Both the gas meter and  
the gas regulator must be properly sized for the total gas load.  
9. If gas supply pressure is within normal range and no  
adjustments are needed, proceed on to Step 11.  
10. If the gas pressure is out of range, contact the gas utility,  
gas supplier, qualified installer or service agency to  
determine the necessary steps to provide proper gas  
pressure to the control.  
If you experience a pressure drop greater than 1 inch w.c.  
(249 Pa), the meter, regulator, or gas line is undersized or in  
need of service. Perform the steps below when checking inlet  
gas supply:  
11. Turn the power switch to the “OFF” position.  
1. Turn the main power switch to the “OFF” position.  
12. Shut off the gas supply at the manual gas valve in the gas  
piping to the appliance.  
2. Shut off gas supply at the manual gas valve in the gas  
piping to the appliance.  
13. Remove the manometer from the pressure tap on top of  
the gas valve. On Models 400 - 501 re-tighten the set  
screw inside the pressure tap. On Models 601 - 801  
remove the 1/8" (3 mm) field supplied fitting and  
reinstall the pipe plug removed in Step 3.  
3. On Models 400 - 501 loosen the set screw one (1) full turn  
from inside the pressure tap on top of the gas valve. On  
Models 601 - 801 remove the 1/8" (3 mm) pipe plug on the  
inlet flange to the valve and install a suitable 1/8" (3 mm)  
fitting (field supplied) for the manometer tubing. Place  
the tubing of the manometer over the tap once the set  
screw is loosened or the 1/8" (3 mm) fitting is installed  
(depending on model) as shown in FIG.’s 4-5 thru 4-7 on  
page 27.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
4 Gas connections  
(continued)  
When re-tightening the set screw, be sure  
to tighten securely to prevent gas leaks.  
Figure 4-7 Inlet Gas Supply Check - Models 601 - 801  
ƽ WARNING  
REMOVE THE 1/8” (3 MM) PIPE PLUG ON  
THE INLET FLANGE TO THE VALVE AND  
INSTALL A SUITABLE 1/8” (3 MM) FITTING  
(FIELD SUPPLIED) FOR THE MANOMETER  
TUBING.  
Do not check for gas leaks with an open  
flame -- use the bubble test. Failure to  
use the bubble test or check for gas leaks  
can cause severe personal injury, death, or  
substantial property damage.  
14. Turn on the gas supply at the manual gas valve.  
15. Turn the power switch to the “ON” position.  
16. Adjust the temperature set point on the control panel of  
the SMART SYSTEM control module to the desired  
water temperature so the appliance will call for heat.  
DETAIL  
17. Check burner performance by cycling the system while  
you observe burner response. The burner should ignite  
promptly. Flame pattern should be stable. Turn system  
off and allow burner to cool, then cycle burner again to  
ensure proper ignition and flame characteristics.  
Gas pressure  
Figure 4-5 Inlet Gas Supply Check - Model 400  
The gas pressure must remain between 4 inches w.c. (.99  
kPa) minimum and 14 inches w.c. (3.5 kPa) maximum for  
Natural gas and between 8 inches w.c. (1.9 kPa) minimum  
and 14 inches w.c. (3.2 kPa) maximum for LP gas during  
standby (static) mode and while in operating (dynamic)  
mode. If an in-line regulator is used, it must be a minimum  
of 10 feet (3 m) from the Outdoor Knight XL boiler. It is  
very important that the gas line is properly purged by the gas  
supplier or utility company. Failure to properly purge the  
lines or improper line sizing, will result in ignition failure.  
LOOSEN THE SET SCREW ONE (1) FULL TURN  
AND PLACE THE MANOMETER TUBING OVER  
THE PRESSURE TAP  
The problem is especially noticeable in NEW LP installations  
and also in empty tank situations. This can also occur when  
a utility company shuts off service to an area to provide  
maintenance to their lines.  
DETAIL  
IMG00414  
Figure 4-6 Inlet Gas Supply Check - Model 501  
Gas valve replacement  
The gas valve MUST NOT be replaced with a conventional  
gas valve under any circumstances. As an additional safety  
feature, this gas valve has a flanged connection to the venturi  
and blower.  
LOOSEN THE SET SCREW ONE (1) FULL TURN  
AND PLACE THE MANOMETER TUBING OVER  
THE PRESSURE TAP  
Failure to follow all precautions could  
result in fire, explosion, or death!  
ƽ WARNING  
DO NOT adjust gas valve outlet pressure.  
ƽ WARNING  
DETAIL  
Attempting to alter the gas valve outlet  
pressure could result in damage to the  
valve, causing potential severe personal  
injury, death, or substantial property  
damage.  
IMG00415  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
5 Field wiring  
ELECTRICAL SHOCK HAZARD – For  
Installation must comply with:  
ƽ WARNING  
your safety, turn off electrical power  
supply before making any electrical  
connections to avoid possible electric  
shock hazard. Failure to do so can cause  
severe personal injury or death.  
1. National Electrical Code and any other national, state,  
provincial, or local codes, or regulations.  
Line voltage connections  
1. Connect 120 VAC power wiring to the line voltage terminal  
strip in the junction box, as shown in FIG.5-1.  
Wiring must be N.E.C. Class 1.  
NOTICE  
If original wiring as supplied with boiler  
must be replaced, use only type 105°C  
wire or equivalent.  
2. Provide and install a fused disconnect or service switch  
(15 amp recommended) as required by the code (see  
FIG. 5-1).  
Boiler must be electrically grounded as  
required by National Electrical Code  
ANSI/NFPA 70 – latest edition.  
3. When connecting a domestic hot water (DHW) pump,  
connect the wiring to the line voltage terminal strip as  
shown in FIG. 5-1.  
Ensure that all wiring external to the  
unit is enclosed in approved conduit.  
4. To activate a system pump, wire as shown in FIG. 5-1. Dry  
contacts are sized for 1.5 hp/120V, 3 hp/240V or 30 amps.  
Label all wires prior to disconnection  
when servicing controls. Wiring errors  
can cause improper and dangerous  
operation.  
ƽ CAUTION  
Low voltage connections  
1. Route all low voltage wires through the knockouts in the  
rear of the boiler, as shown in FIG. 5-2.  
Figure 5-1 Line Voltage Field Wiring Connections  
2. Connect low voltage wiring to the low voltage connection  
board as shown in FIG. 5-3 on page 29 of this manual and  
the boiler wiring diagram.  
120V SUPPLY  
NEUTRAL  
W
GROUND  
G
Figure 5-2 Routing Field Wiring  
LINE  
BK  
LINE VOLTAGE  
LOW VOLTAGE  
SERVICE  
SWITCH  
JUNCTION BOX  
CONNECTION  
BOARD  
BK  
SYSTEM  
PUMP  
G
W
LOW VOLTAGE  
WIRING  
KNOCKOUT  
PLUGS  
BK  
G
W
BOILER  
PUMP  
IMG00329  
LINE VOLTAGE  
WIRING KNOCKOUT  
PLUGS  
BK  
G
W
DOMESTIC  
HOT WATER  
PUMP  
L2/N  
G
L1  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
5 Field wiring  
(continued)  
If TST20015 is not compatible with the indirect tank, a  
tank thermostat can be used to control the boiler. The  
tank thermostat should be installed per the manufacturer’s  
instructions and wired to the DHW Thermostat terminals on  
the low voltage connection board (FIG. 5-3).  
Thermostat  
1. Connect the room thermostats or end switches (isolated  
contact only) to heat/loop demand 1, 2, or 3, as shown in  
FIG. 5-3.  
2. Install the thermostat on the inside wall away from  
influences of drafts, hot or cold water pipes, lighting  
fixtures, television, sunlight, or fireplaces.  
High gas pressure switch  
1. If a switch is provided to detect excessive gas pressure,  
remove the jumper wire from the terminals on the  
connection board, and then connect them to its normally  
closed contacts (FIG. 5-3).  
3. Thermostat anticipator (if applicable):  
a. If connected directly to boiler, set for 0.1 amps.  
b. If connected to relays or other devices, set to match  
total electrical power requirements of connected  
devices. See device manufacturers’ specifications  
and thermostat instructions for details.  
Low gas pressure switch  
1. If a switch is provided to detect low gas pressure, remove  
the jumper wire from the terminals on the connection  
board and connect them to its normally open contacts  
(FIG. 5-3).  
Outdoor temperature sensor  
1. Mount the sensor on an exterior wall, shielded from  
direct sunlight or flow of heat or cooling from other  
sources.  
2. If both a high and low gas pressure switch is used, connect  
their respective contacts in series, and connect them to the  
terminals on the connection board (FIG. 5-3).  
2. Route sensor wires through a knockout at the rear of the  
boiler (see FIG. 5-2).  
Variable speed system pump  
3. Connect the outdoor temperature sensor (FIG. 5-3) to  
the outdoor sensor terminals on the connection board  
to enable outdoor reset operation of the Outdoor Knight  
XL. If fixed temperature operation is required, do not  
install outdoor sensor.  
If a variable speed pump is used in the primary loop, and  
a 0-10V signal is available from the pump speed control,  
this signal can be used by the SMART SYSTEM control to  
anticipate changes in the building heat load. By connecting this  
0 - 10V signal to the 0 - 10V SYS PUMP IN terminals, the boiler  
(or cascade) can modulate up and down as the primary flow  
increases and decreases.  
DHW  
(Domestic  
Hot  
Water)  
thermostat  
Connect storage indirect water heater (DHW) thermostat  
(FIG. 5-3) to the DHW thermostat terminals on the  
connection board. If a tank sensor is connected (see DHW  
Tank Sensor below) the tank thermostat is ignored.  
Boiler pump speed output  
This 0 - 10V output is available to control the speed of a variable  
speed boiler pump. The SMART SYSTEM control will vary the  
speed of this pump in order to maintain a minimum T across  
the heat exchanger, as well as prevent high limit lockouts when  
the flow in the primary loop is extremely low. Connect this  
output to the 0 - 10V input on the boiler pump speed control.  
DHW tank sensor  
By installing a tank sensor, the SMART SYSTEM control can  
perform the tank thermostat function. The SMART SYSTEM  
control automatically detects the presence of this sensor, and  
generates a DHW call for heat when the tank temperature  
drops 6°F (3°C) below the tank set point, and finishes the call  
for heat when the tank temperature reaches the tank set point.  
The tank sensor included with the Lochinvar Squire® indirect  
DHW tanks (TST20015) is the only sensor suitable for use  
with the SMART SYSTEM control. Connect the sensor leads  
to the Tank Sensor terminals on the low voltage connection  
board (FIG. 5-3).  
Rate output  
This output provides a 0 - 10V signal that is proportional to the  
firing rate of the boiler. This may be used by a BMS system to  
monitor the actual rate of the boiler.  
Failure to use the correct sensor may  
ƽ WARNING  
result in the tank temperature being either  
above or below the set point.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
5 Field wiring  
ModBus  
Alarm contacts  
When the optional ModBus interface module is installed, the The SMART SYSTEM control closes another set of contacts  
RS-485 ModBus cable is connected to these terminals. Use whenever the boiler is locked out or the power is turned off.  
shielded, 2-wire twisted pair cable. If desired, the shield can This can be used to turn on an alarm, or signal a Building  
be connected to ground by installing a jumper wire between  
terminals 1 and 3 on connector X5 on the optional ModBus  
interface module.  
Management System that the boiler is down.  
Wiring of the cascade  
Flow switch  
1. A flow switch is used to guarantee flow through the boiler  
before allowing it to fire. The flow switch must be installed  
at the boiler outlet.  
When wiring the boilers for Cascade operation, select one  
boiler as the Leader boiler. The remaining boilers will be  
designated as Members. See page 36 “Configuration of the  
Cascade” for a detailed explanation of this procedure.  
2. Remove the jumper wire from the terminals on the  
connection board and connect these terminals to the  
normally open contacts on the flow switch (FIG. 5-3).  
Connect the system supply sensor and outdoor air sensor (if  
used) to the Leader boiler. For the Cascade system to work  
properly the system supply sensor must be installed. The  
location of the system supply sensor should be downstream  
of the boiler connections in the main system loop (FIG.’s 3-7  
through 3-11). The system supply sensor should be wired to  
the Low Voltage Connection Board at the terminals marked  
for the system sensor (see FIG. 5-3). The Leader control will  
use the water temperature at the system supply sensor to  
control the operation of the Cascade.  
System supply sensor  
1. By installing the system supply sensor into the supply of  
the primary loop, the temperature of the system supply can  
be controlled. The SMART SYSTEM control automatically  
detects the presence of this sensor, and controls the boiler  
firing rate to maintain the system supply temperature to the  
set point (if the outlet sensor control is currently selected).  
See the Outdoor Knight XL Service Manual for instructions  
on how to use the inlet sensor as the controlling sensor.  
When the inlet sensor is programmed as the controlling  
sensor, it is vital that the SYSTEM SUPPLY sensor be  
installed. DO NOT INSTALL THE SYSTEM SUPPLY  
SENSOR INTO THE SYSTEM RETURN.  
If outdoor air reset is desired, the outdoor air sensor should be  
wired to the Low Voltage Connection Board at the terminals  
marked for the outdoor air sensor (FIG. 5-3). If the outdoor  
air sensor is connected, the Leader control will calculate the  
water temperature set point based on the programmed reset  
curve parameters. If the outdoor air sensor is not connected,  
the Leader control will maintain the fixed water temperature  
set point that is programmed into the control.  
2. The TST2032 sensor provided with the boiler must be used  
for the system sensor.  
If a Thermostat or Zone Control enable output is available,  
it should be wired to the Low Voltage Connection Board  
on the Leader boiler at the terminals marked for one of the  
heat/loop demands 1-3 (FIG. 5-3). If the boilers are to run  
continuously, connect a jumper wire between the R and W  
terminals for the heat/loop demand input. This will initiate a  
call for heat on the Cascade.  
3. Connect these terminals to the system supply sensor  
(FIG. 5-3).  
Boiler management system  
1. An external control may be connected to control either  
the firing rate or the set point of the boiler. If the  
external control uses a set of contacts to enable the boiler,  
connect the contacts to the heat/loop demand 1 terminals.  
Otherwise, the SMART SYSTEM control will be enabled by  
the 0-10V signal.  
Communication between the Leader boiler and the Member  
boilers is accomplished by using shielded, 2-wire twisted pair  
communication cable. Connect one of the twisted pair wires  
to Cascade terminal A on each of the Low Voltage Connection  
boards, and the other wire of the twisted pair to Cascade  
terminal B on each of the Low Voltage Connection Boards.  
Connect the shield wires to one of the shield terminals on  
the Low Voltage Connection Boards (FIG. 5-3). If more than  
two boilers are on the Cascade, daisy chain the wiring from  
the Cascade terminals on the second boiler to the Cascade  
terminals on the third boiler, then from the third to the forth,  
and so on. The connections between boilers can be made in  
any order, regardless of the addresses of the boilers. Try to  
keep each cable as short as possible.  
2. Make sure the (-) terminal is connected to the (-) or  
common output terminal of the external control, and  
the (+) terminal is connected to the 0 - 10 VDC or (+)  
terminal of the external control. Make sure that the (-)  
voltage is not below ground.  
Runtime contacts  
The SMART SYSTEM control closes a set of dry contacts  
whenever the burner is running. This is typically used by  
Building Management Systems to verify that the boiler is  
responding to a call for heat.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30  
Outdoor Knight XL Installation & Operation Manual  
5 Field wiring  
(continued)  
Figure 5-3 Low Voltage Field Wiring Connections  
Download from Www.Somanuals.com. All Manuals Search And Download.  
31  
Outdoor Knight XL Installation & Operation Manual  
6 Condensate disposal  
Use materials approved by the authority  
having jurisdiction. In the absence of other  
authority, PVC and CPVC pipe must comply  
with ASTM D1785 or D2845. Cement and  
primer must comply with ASME D2564 or  
F493.  
Condensate drain  
NOTICE  
NOTICE  
1. This boiler is a high efficiency appliance that produces  
condensate.  
2. The side of the boiler has a 1/2 inch (12.7 mm) PVC  
union for connection of a 1/2 inch (12.7 mm) PVC pipe  
(FIG. 6-1).  
To allow for proper drainage on large  
horizontal runs, a second line vent may  
be required and tubing size may need to  
increase to 1 inch (25 mm).  
3. Slope condensate tubing down and away from the boiler  
into a drain or condensate neutralizing filter. Condensate  
from the Outdoor Knight XL will be slightly acidic  
(typically with a pH from 3 to 5). Install a neutralizing  
filter if required by local codes.  
The condensate line must remain  
unbstructed, allowingfreeowofcondensate.  
If condensate is allowed to freeze in the line  
or if the line is obstructed in any other  
manner, condensate can exit from the boiler  
tee, resulting in potential water damage to  
property.  
A Neutralizer Kit (FIG. 6-1) is available from the factory  
(KIT3087 for Models 400 - 501 and KIT3046 for Models  
601 - 801).  
4. Install the 1/2 inch (12.7 mm) PVC tee assembly (shipped  
with the unit) as shown in FIG. 6-1.  
8. A condensate removal pump is required if the boiler is  
below the drain. When installing a condensate pump, select  
one approved for use with condensing boilers and furnaces.  
The pump should have an overflow switch to prevent  
property damage from condensate spillage. The switch  
should be wired in series with the blocked drain switch  
inside the boiler (see FIG. 7-1 on page 34).  
5. Leave the top of the 1/2 inch (12.7 mm) tee OPEN. This  
is needed as a vacuum break.  
6. Do not expose condensate line to freezing temperatures.  
Precautions should be taken to protect the condensate  
management and disposal system during extended  
periods of outdoor temperatures below 32°F.  
7. Use only plastic tubing or piping as a condensate drain  
line (FIG. 6-1).  
Figure 6-1 Condensate Disposal  
BLY  
TEE ASSEM  
1/2" PVC  
)
Y SUPPLIED  
(FACTOR  
IMG00331  
IN OR  
FLOOR DRA  
UNION  
1/2" PVC  
AN  
DRAIN P  
)
Y SUPPLIED  
(FACTOR  
IT  
LIZER K  
NEUTRA  
32  
KIT3087 shown for illustration purposes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
7 Start-up  
3. Fill to correct system pressure. Correct pressure will vary  
with each application.  
Check/control water chemistry  
Do not use petroleum-based cleaning or  
ƽ CAUTION  
a. The minimum cold water fill pressure for a  
commercial system is 12 psi (82.7 kPa).  
sealing compounds in the boiler system.  
Damage to elastomer seals and gaskets  
in the system could occur, resulting in  
substantial property damage.  
b. Pressure will rise when boiler is turned on and  
system water temperature increases.  
Hardness less than 7 grains  
4. At initial fill and during boiler startup and testing, check  
system thoroughly for any leaks. Repair all leaks before  
proceeding further.  
1. Consult local water treatment companies for hard water  
areas (above 7 grains hardness).  
Eliminate all system leaks. Continual  
Chlorine concentration less than 200 ppm  
ƽ WARNING  
fresh makeup water will reduce boiler life.  
Minerals can build up in the heat exchanger,  
reducing heat transfer, overheating the heat  
exchanger, and causing heat exchanger  
failure.  
1. Do not fill boiler or operate with water containing  
chlorine in excess of 200 ppm.  
2. Filling with chlorinated fresh water should be acceptable  
since drinking water chlorine levels are much lower.  
Purge air from water system  
3. Do not use the boiler to directly heat swimming pool or  
spa water.  
1. Purge air from system:  
a. Connect a hose to the purge valve (see purge/drain  
valves, in piping diagrams on page 22). Route the  
hose to an area where water can drain and be seen.  
b. Close the boiler or system isolation valve between  
the purge valve and fill connection to the system.  
c. Close zone isolation valves.  
Test/replace freeze protection uid  
1. For systems using freeze protection fluids, follow fluid  
manufacturer’s instructions.  
2. Freeze protection fluid must be replaced periodically due  
to degradation of inhibitors over time. Follow all fluid  
manufacturer’s instructions.  
d. Open quick-fill valve on cold water makeup line.  
e. Open purge valve.  
f. One zone at a time, open the isolation valves. Allow  
water to run through the zone, pushing out the air.  
Run until no noticeable air flow is present. Close the  
zone isolation valves and proceed with the next zone.  
Follow this procedure until all zones are purged.  
g. Close the quick-fill water valve and purge valve and  
remove the hose. Open all isolation valves. Watch  
that system pressure rises to correct cold-fill  
pressure.  
Freeze protection (when used)  
1. Determine freeze protection fluid quantity using  
system water content, following fluid manufacturer’s  
instructions. Boiler water content is listed on page 7.  
Remember to include expansion tank water content.  
2. Local codes may require a backflow preventer or actual  
disconnect from city water supply.  
h. After the system has operated for a while, eliminate  
any residual air by using the manual air vents located  
throughout the system.  
i. If purge valves are not installed in the system, open  
the manual air vents in the system one at a time,  
beginning with the lowest floor. Close the vent when  
water squirts out. Repeat with remaining vents.  
3. When using freeze protection fluid with automatic fill,  
install a water meter to monitor water makeup. Freeze  
protection fluid may leak before the water begins to  
leak, causing concentration to drop, reducing the freeze  
protection level.  
4. The freeze protection set points may be lowered when  
freeze protection fluid is used (see the Outdoor Knight  
XL Service Manual).  
2. Open automatic air vent (diaphragm-type or bladder-  
type expansion tank systems only) one turn.  
Fill and test water system  
3. Open other vents:  
a. Starting on the lowest floor, open air vents one at a  
time until water squirts out.  
b. Repeat with remaining vents.  
1. Fill system only after ensuring the water meets the  
requirements of this manual.  
2. Close manual and automatic air vents and boiler drain  
valve.  
4. Refill to correct pressure.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
7 Start-up  
Propane boilers only – Your propane  
Check for gas leaks  
ƽ WARNING  
suppliermixesanodorantwiththepropane  
to make its presence detectable. In some  
instances, the odorant can fade, and the  
gas may no longer have an odor. Before  
startup (and periodically thereafter), have  
the propane supplier verify the correct  
odorant level in the gas.  
Before starting the boiler, and during  
ƽ WARNING  
initial operation, smell near the floor and  
around the boiler for gas odorant or any  
unusual odor. Remove the top access  
panel and smell the interior of the boiler  
enclosure. Do not proceed with startup  
if there is any indication of a gas leak.  
Use an approved leak detection solution.  
Repair any leaks at once.  
Check thermostat circuit(s)  
1. Disconnect the two external wires connected to each  
of the heat/loop demand terminals on the connection  
board.  
DO NOT adjust gas valve outlet pressure.  
The gas valve is factory set for the correct  
outlet pressure. This setting is suitable  
for natural gas and propane, requiring  
no field adjustment. Attempting to  
alter the gas valve outlet pressure could  
result in damage to the valve, causing  
potential severe personal injury, death, or  
substantial property damage.  
ƽ WARNING  
2. Connect a voltmeter across these two incoming wires.  
Close each thermostat, zone valve, and relay in the  
external circuit one at a time and check the voltmeter  
reading across the incoming wires.  
3. There should NEVER be a voltage reading.  
4. If a voltage does occur under any condition, check and  
correct the external wiring. (This is a common problem  
when using 3-wire zone valves.)  
Figure 7-1 Condensate Trap  
RETAINING  
SCREW  
5. Once the external thermostat circuit wiring is checked and  
corrected if necessary, reconnect the external thermostat  
circuit wires to the connection board. Allow the boiler to  
cycle.  
2” PVC CAP WITH  
BLOCKED DRAIN SWITCH  
PVC TEE ASSEMBLY  
(FACTORY SUPPLIED)  
Inspect/ll condensate system  
Inspect/check condensate lines and ttings  
1. Inspect the condensate drain line, condensate PVC  
fittings and condensate trap.  
Fill condensate trap with water  
1. Remove the PVC cap retaining screw from the PVC cap  
(FIG. 7-1).  
CONDENSATE FROM  
HEAT EXCHANGER  
TO FLOOR  
DRAIN  
2. Remove the 2 inch PVC cap with the switch located at the  
top of the trap (FIG. 7-1).  
3. Fill with fresh water until the water begins to pour out of  
the drain.  
4. Replace the cap. Press the cap onto the trap until the cap  
makes contact with the drain.  
5. Replace the retaining screw.  
The condensate trap (FIG. 7-1) must be  
filled with water during all times of boiler  
ƽ WARNING  
operation to avoid flue gas emission from  
the condensate drain line. Failure to fill  
the trap could result in severe personal  
injury or death.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
7 Start-up  
(continued)  
Check gas piping  
Final checks before starting the boiler  
1. Check around the boiler for gas odor following the  
procedure on page 46 of this manual (connecting gas  
supply piping).  
Read the Outdoor Knight XL Service Manual to  
familiarize yourself with SMART SYSTEM control  
module operation. Read this manual, page 33 for proper  
steps to start boiler.  
If you discover evidence of any gas leak,  
ƽ WARNING  
shut down the boiler at once. Find the  
Verify the boiler and system are full of water and all  
leak source with a bubble test and repair  
immediately. Do not start the boiler again  
until corrected. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
system components are correctly set for operation.  
Verify the preparation procedures of Section 7, pages 33  
and 34 have been completed.  
Propane boilers – verify conversion  
Fill the vent condensate trap with water (removing the  
retaining screw in order to remove the 2 inch PVC cap  
with the switch located at the top of the trap). Replace  
the cap. Press the cap onto the trap until the cap makes  
contact with the drain. Replace the retaining screw.  
1. Verify propane conversion has been completed per the  
Propane Conversion instructions.  
DO NOT adjust gas valve outlet pressure.  
ƽ WARNING  
The gas valve is factory-set for the correct  
Verify electrical connections are correct and securely  
outlet pressure. This setting is suitable  
for natural gas and propane, requiring  
no field adjustment. Attempting to  
alter the gas valve outlet pressure could  
result in damage to the valve, causing  
potential severe personal injury, death, or  
substantial property damage.  
attached.  
Start the boiler  
1. Read and follow the Operating instructions in FIG. 7-2,  
page 36.  
If boiler does not start correctly  
Outdoor Knight XL boilers are typically  
ƽ WARNING  
shipped ready to fire on natural gas.  
Check boiler rating plate to determine  
which fuel the boiler is set for. If set to  
natural gas, it may be converted to LP by  
installing an orifice or by making a gas  
valve adjustment (see page 12). In order  
to operate on LP gas, an orifice MUST  
BE installed or a gas valve adjustment  
MUST BE made. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
1. Check for loose connections, blown fuse or service switch  
off?  
2. Is boiler water temperature above 200°F (93°C)?  
3. Is thermostat set below controlling sensor temperature?  
4. Is gas turned on at meter or boiler?  
5. Is incoming gas pressure less than 4 inches w.c. (.99 kPa)?  
If none of the above corrects the problem, refer to the  
Troubleshooting Section of the Outdoor Knight XL Service  
Manual.  
Check ame and combustion  
1. Turn the main power off to the boiler by placing the  
“On/Off” switch in the OFF position.  
Check system and boiler  
2. Combustion measurements will be made from exhaust  
opening.  
Check water piping  
1. Check system piping for leaks. If found, shut down  
the boiler and repair immediately. (See WARNINGS  
on pages 33 and 34 (startup) regarding failure to repair  
leaks.)  
3. Turn the main power on to the boiler by placing the  
“On/Off” switch in the ON position.  
2. Vent any remaining air from the system using manual  
vents. Air in the system will interfere with circulation and  
cause heat distribution problems and noise.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
7 Start-up  
Figure 7-2 Operating Instructions  
FOR YOUR SAFETY READ BEFORE OPERATING  
WARNING: If you do not follow these instructions exactly, a fire or explosion  
may result causing property damage, personal injury, or loss of life.  
• Immediately call your gas supplier from a  
A. This appliance does not have a pilot. It is  
neighbor’s phone. Follow the gas supplier’s  
instructions.  
equipped with an ignition device which  
automatically lights the burner. Do not try  
• If you cannot reach your gas supplier, call  
the fire department.  
to light the burner by hand.  
B. BEFORE OPERATING smell all around  
the appliance area for gas. Be sure to  
smell next to the floor because some gas  
is heavier than air and will settle on the  
floor.  
C. Use only your hand to turn the gas control knob.  
Never use tools. If the handle will not turn by  
hand, don’t try to repair it, call a qualified service  
technician. Force or attempted repair may result  
in a fire or explosion.  
WHAT TO DO IF YOU SMELL GAS  
D. Do not use this appliance if any part has been  
under water. Immediately call a qualified  
• Do not try to light any appliance.  
service technician to inspect the appliance and  
to replace any part of the control system and  
any gas control which has been under water.  
• Do not touch any electric switch; do  
not use any phone in your building.  
OPERATING INSTRUCTIONS  
1. STOP! Read the safety information  
above on this label.  
8. Turn gas shutoff valve clockwise to “ON”.  
Handle will be parallel to pipe.  
2. Set the thermostat to lowest setting.  
9. Install top cover.  
10. Turn on all electric power to appliance.  
11. Set thermostat to desired setting.  
3. Turn off all electric power to the  
appliance.  
4. This appliance is equipped with an  
ignition device which automatically lights  
the burner. Do not try to light the burner  
by hand.  
12. If the appliance will not operate, follow the  
instructions “To Turn Off Gas To Appliance” and  
call your service technician or gas supplier.  
5. Remove top cover.  
6. Turn gas shutoff valve counterclockwise  
to “OFF”. Handle will be perpendicular to  
pipe. Do not force.  
7. Wait five (5) minutes to clear out any gas.  
If you then smell gas, STOP! Follow “B”  
in the safety information above on this label.  
If you don’t smell gas, go to next step.  
TO TURN OFF GAS TO APPLIANCE  
1. Set the thermostat to lowest setting.  
4. Turn gas shut off valve counterclockwise to  
“OFF”. Handle will be perpendicular to pipe.  
Do not force.  
2. Turn off all electric power to the appliance  
if service is to be performed.  
5. Install top cover.  
3. Remove top cover.  
LBL2284 REV -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
36  
Outdoor Knight XL Installation & Operation Manual  
7 Start-up  
(continued)  
Check ame and combustion (continued)  
Set space heating operation  
4. Place the boiler into the active position by pressing the  
RIGHT SELECT [ON] key (FIG. 8-1, page 43).  
Determine controlling sensor  
For space heating systems, the temperature control can be  
based on one of three sensors; the inlet, outlet, or system  
supply sensor. The SMART SYSTEM control is programmed  
at the factory to control the temperature of the outlet  
sensor. The control will automatically switch to the system  
supply sensor once it is connected. If it is desired to base  
the temperature control on the inlet sensor, the appropriate  
parameter must be changed in the control. See the Outdoor  
Knight XL Service Manual for a detailed explanation of this  
procedure.  
5. Locate the pinhole button below the RESET button on  
the display board (FIG. 8-1). Insert a thin wire (such as  
a paper clip) into the hole and press the button once  
and hold for 5 seconds to place the boiler into Service  
Mode. In Service Mode the boiler will fire at ignition  
speed and will then modulate up to full fire.  
6. Once the boiler has modulated up to full fire, measure  
the combustion. The values should be in the range  
listed in Table 7A below. The CO levels should be less  
than 150 ppm for a properly installed unit.  
Verify space heat circulator mode  
If the combustion is not within the specified range,  
reference the Troubleshooting Section of the Outdoor  
Knight XL Service Manual for possible causes and  
corrective actions.  
The Space Heating Mode controls both the system pump  
(if connected), and the boiler pump. When the SMART  
SYSTEM control receives a space heating call for heat, it turns  
on the system pump. If the boiler is not heating an indirect  
DHW (Domestic Hot Water) tank, and the set point is not  
met, it also turns on the boiler pump. After the space heating  
call for heat ends, the system pump continues to run for a  
short period of time. The system pump can be programmed  
to run continuously, except during outdoor shutdown. If  
the boiler pump was running, it continues to run for a short  
period of time as well. These pump delays are factory set to  
30 seconds. If different delays are desired, the appropriate  
parameters in the control must be changed. See the Outdoor  
Knight XL Service Manual for a detailed explanation of this  
procedure.  
Table 7A Flue Products Chart  
Natural Gas  
CO2 O2  
Propane  
CO2  
O2  
8.0% - 10% 3.0% - 6.5% 9.0% - 11% 4.1% - 6.9%  
7. Once the combustion analysis is complete, test the  
safety shutoff device by turning the manual shutoff  
valve to the OFF position and ensuring that the boiler  
shuts down and registers an alarm. Turn the manual  
shutoff switch to the ON position and reset the control.  
Adjust set point temperature(s)  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
8. Place the boiler back into normal operation.  
The NAVIGATION dial may be used during normal  
operation to adjust the space heating and tank set point  
temperatures.  
1. From the Status Screen press the NAVIGATION dial.  
2. Turn the NAVIGATION dial counterclockwise to select  
the appropriate set point.  
3. Press the NAVIGATION dial to adjust the temperature.  
4. Once the desired temperature is displayed, press the  
RIGHT SELECT [SAVE] key.  
5. If necessary repeat Steps 3 and 4 to make adjustments to  
additional set points.  
6. Press the RIGHT SELECT [HOME[ key to upload the  
changes.  
7. If the RIGHT SELECT [SAVE] key is not pressed, the  
new settings will be discarded.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
37  
Outdoor Knight XL Installation & Operation Manual  
7 Start-up  
Set domestic hot water (DHW) operation  
Verify DHW mode  
There are two (2) modes of operation for DHW. In Normal  
Mode, when a DHW demand begins, the control will start  
the DHW pump, turn off the boiler pump (if running), and  
modulate to bring the outlet temperature to the DHW boiler  
set point. The maximum firing rate may be limited in this  
mode if desired.  
7. Turn the NAVIGATION dial to adjust the minutes. Press  
the NAVIGATION dial.  
8. Turn the NAVIGATION dial to adjust the month. Press  
the NAVIGATION dial.  
9. Turn the NAVIGATION dial to adjust the date. Press the  
NAVIGATION dial.  
In Zone Mode it is assumed that the indirect DHW tank is  
piped as a zone on the primary loop. When a DHW demand  
begins, the control will turn on the DHW pump output, and  
raise the system temperature set point to the DHW boiler set  
point (if higher). The boiler pump will be turned on. The  
system pump may be forced on, forced off, or not changed,  
depending on the System Pump Mode selected (reference  
the Outdoor Knight XL Service Manual for details). In this  
mode, any low temperature zones (such as radiant heating)  
may need additional controls to limit the water temperature  
sent to those zones.  
10. Turn the NAVIGATION dial to adjust the year. Press the  
RIGHT SELECT [SAVE] key.  
11. Press the RIGHT SELECT [HOME] key.  
The internal clock does not adjust for  
NOTICE  
Daylight Savings Time and therefore, will  
require a manual adjustment.  
The clock is automatically updated whenever a PC is connected  
and the Win_Pro-Installer program is started.  
Conguration of the cascade  
Set DHW boiler target temperature  
Please note that the brackets ([]) denote  
screen status.  
When in the DHW Mode, the control will modulate to  
maintain the boiler outlet temperature or system supply  
temperature to a set point. This set point is set at the factory  
to 180°F. If a different set point is desired, the appropriate  
parameter in the control must be changed. See the Outdoor  
Knight XL Service Manual for a detailed explanation of this  
procedure.  
NOTICE  
When installed in a Cascade system, the individual controls must  
be programmed for cascade operation. This is accomplished by  
accessing the control parameters.  
Press the [MENU] key for at least five (5) seconds. Input the  
Installer code as described in the Outdoor Knight XL Service  
Manual. Once the control parameters have been accessed,  
use the NAVIGATION DIAL to select the Control Mode  
parameters. Press the NAVIGATION DIAL to access these  
parameters.  
Set maximum DHW fan speed  
If the rated input of the indirect tank is less than the maximum  
output of the boiler, change the maximum DHW fan speed  
setting to limit the boiler output accordingly, see the Outdoor  
Knight XL Service Manual for a detailed explanation of this  
procedure.  
Rotate the NAVIGATION dial to select the parameter “Cascade  
Address”. Press the NAVIGATION dial to access this parameter.  
Each appliance in the Cascade system must be programmed  
with its own address. The boiler designated as the Leader will  
have an address of 0. The remaining boilers in the Cascade  
will be Members and have addresses from 1 - 7. Rotate the  
NAVIGATION dial to select the appropriate address. Press the  
RIGHT SELECT [SAVE] key.  
Set clock  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
The SMART SYSTEM control has a built-in clock that it  
uses for its night setback feature and for logging events. This  
clock must be set when the boiler is installed, and anytime the  
boiler has been powered off for more than 4 hours. Use the  
following procedure to set the clock:  
Press the RIGHT SELECT [HOME] key to upload the address  
into the control. Repeat this procedure for all boilers in the  
Cascade, designating the Leader control and the Member  
controls.  
1. Press and hold the LEFT SELECT [MENU] key for at  
least 5 seconds.  
2. The display changes to read [PASSWORD],  
with four (4) zeros below it.  
3. Press the RIGHT SELECT [SAVE] key.  
4. The display will then show a menu with the time and  
date and temperature unit.  
5. Press the NAVIGATION dial twice.  
6. Turn the NAVIGATION dial to adjust the hours. Press  
the NAVIGATION dial.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
38  
Outdoor Knight XL Installation & Operation Manual  
8 Operating information  
The Outdoor Knight XL can also be programmed to accept a  
call for heat from a 0 - 10V signal, reference the Outdoor Knight  
XL Service Manual for a detailed explanation of this procedure.  
General  
How the boiler operates  
The Outdoor Knight XL uses an advanced stainless steel heat  
exchanger and electronic control module that allows fully DHW priority  
condensing operation. The blower pulls in air and pushes flue  
The SMART SYSTEM control allows the connection of a DHW  
products out of the boiler through the heat exchanger and  
flue piping. The control module regulates blower speed to  
control the boiler firing rate. The gas valve senses the amount  
of air flowing into the boiler and allows only the right amount  
of gas to flow.  
thermostat or tank sensor to the low voltage connection board.  
When a tank sensor is connected, the DHW thermostat input  
is ignored. When a boiler is programmed for DHW Normal  
Mode, the maximum firing rate can be limited to match the  
input rating of the indirect tank coil.  
How the control module operates  
DHW / space heating (SH) cycling  
The SMART SYSTEM control module receives inputs from  
boiler sensors and external devices. The control module  
activates and controls the blower and gas valve to regulate  
heat input and switches the boiler, Domestic Hot Water  
(DHW), and system pumps on and off as needed. The user  
programs the module to meet system needs by adjusting  
control parameters. These parameters set operating  
temperatures and boiler operating modes. Boiler operation  
can be based on boiler outlet water temperature, boiler inlet  
water temperature, system temperature, a 0 - 10V signal, or  
Modbus, depending on the parameter settings.  
If a DHW call for heat is received while a space heating call is  
in progress, and the DHW is in Normal Mode, the control will  
start the DHW pump and shut the boiler pump off. The system  
pump will remain on. For stand-alone boilers, if the space  
heating call is still active while the DHW call is in operation, the  
control will wait for 30 minutes (time adjustable by installer)  
then it will switch back to the space heating demand. There is  
a timer to switch from space heating to DHW and a timer to  
switch from DHW to space heating. The control will switch  
back and forth until one of the heat demands end. This function  
does not apply to cascade systems.  
Control inputs and outputs  
Room thermostat  
Programmable controlling sensor  
The control module is programmed to use the outlet sensor  
as the control sensor by default. If a system supply sensor is  
connected, the control automatically uses it as the control  
sensor. For stand-alone boilers, the control sensor can be  
changed by the installer to the inlet sensor. If the inlet sensor  
is chosen as the controlling sensor, it is recommended that the  
system supply sensor be installed in the system supply in order  
to provide the best control of the inlet temperature.  
There are three (3) heat/loop demand connections available  
on this control. These inputs tell the boiler to provide water  
for space heating. Each demand connection has its own set  
point and outdoor air reset curve. When multiple demands  
have a call for heat the control will give priority to the demand  
with the highest set point.  
Example: Assume that both heat/loop demand 1 and heat/  
loop demand 2 have a call for heat. Demand 1 has a set point  
of 110°F. Demand 2 has a set point of 140°F. The boiler will  
regulate the system temperature to 140°F until Demand 2 has  
been satisfied. Once Demand 2 has been satisified the boiler  
will provide 110°F water to the system.  
Anti-cycling  
After the burner turns off, the control will delay the next burner  
cycle for a set time period (time is adjustable by the installer).  
The time delay will be bypassed if the inlet water temperature  
drops too far during the delay.  
When multiple temperature loops are  
ƽ CAUTION  
used, mixing valves are required for the  
Boiler and system pump control  
protection of any low temperature loops.  
The boiler pump will run whenever the burner is firing, unless  
the DHW is programmed for Normal Mode and the boiler is  
heating the DHW tank. The boiler pump will run during Freeze  
Protection Mode as well. It will continue to run for a short time  
after the burner turns off or the Freeze Protection Mode ends.  
SMART SYSTEM Multi-temp loop control  
The Outdoor Knight XL boiler is capable of producing up  
to three (3) set point temperatures to meet different space  
heating demands.  
This device controls the temperatures  
of up to three (3) separate loops, based on the settings for  
the three (3) heat/loop demands (reference Lochinvar kit  
RLY30086).  
The system pump will run whenever there is a space heating call  
for heat, or the boiler goes into Freeze Protection Mode. It may  
be programmed to run during a DHW call for heat when the  
DHW is programmed for Zone Mode. It will continue to run  
for a short time after the end of the heat demand or the Freeze  
Protection Mode. The system pump can be programmed to run  
continuously if desired, except during outdoor shutdown and/  
or a DHW call for heat.  
0 - 10V input (set point or power)  
The Outdoor Knight XL can be controlled by a Building  
Management System (BMS) using a 0 - 10 VDC signal. The  
control can be configured by the installer to use this signal to  
either control set point or firing rate.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
39  
Outdoor Knight XL Installation & Operation Manual  
8 Operating information  
Temperature control  
Protection features  
Modulation  
Outlettemperature, uetemperature, andtemperature  
The Outdoor Knight XL is capable of modulating its firing  
rate from a minimum of 20% to a maximum of 100%. The  
firing rate is dictated by the call for heat (i.e., space heating  
or domestic hot water), the heating load, ramp delay (if  
enabled), and various other temperature limitations.  
rise limiting  
The outlet temperature is monitored by the boiler outlet  
temperature sensor. When the outlet temperature exceeds  
185°F, the unit will reduce the fan speed. If the outlet water  
temperature exceeds 195°F (90°C) the control will shut the unit  
down until it cools off.  
Ramp delay  
For systems with lower flow, the SMART SYSTEM can  
limit the firing rate (when enabled) when a space heating  
call for heat starts, or when switching from a DHW call for  
heat to a space heating call for heat. There are six (6) limits  
that can be programmed, as well as six (6) time intervals  
corresponding to each limit. The sixth limit will also limit  
the firing rate for the rest of the call for heat.  
The control module monitors the flue temperature by a sensor  
located in the flue exhaust. If the flue temperature exceeds  
215°F (102°C) the control will reduce the maximum fan speed.  
If the flue temperature exceeds 240°F (115°C) the control will  
shut the unit down. The unit will restart automatically once the  
flue temperature drops 25°F (-4°C) and the minimum off time  
has expired.  
Gradient limiting  
The control monitors the temperature difference between  
the inlet and the outlet sensor. If this difference exceeds 55°F  
(13°C) the control will reduce the maximum fan speed. If the  
temperature difference exceeds 60°F (15°C) the control will  
shut the unit down. The unit will restart automatically once the  
temperature difference has dropped below 55°F (13°C) and the  
minimum off time has expired.  
Ifduringoperationoftheboilertheoutletwatertemperature  
is rising too quickly, the control will reduce the firing rate  
to its lowest setting.  
Outdoor air reset  
If an outdoor air sensor is connected, the control module  
will calculate the set points of the three (3) space heating  
demands based on the programmed reset curves. The  
installer can change the slope of the reset curves by several  
adjustable parameters. The user can limit the maximum  
set point for the system using the space heating set points.  
Freeze protection  
DO NOT install the boiler in a location where it is likely to  
freeze.  
The following integral feature of the SMART SYSTEM control  
module provides some protection for the boiler only -- not for  
the system.  
Boost function  
If outdoor air reset is active, and any space heating  
demand has been active continuously for a set period of  
time (time adjustable by installer) and there has been no  
DHW demands, the control will increase the set point of  
that demand by a fixed number of degrees (adjustable by  
installer). This process will continue until the space heating  
demand ends, the set point reaches the programmed set  
point or a maximum of 20 increases has occurred. Once the  
system heat demand is satisfied, the set point will revert to  
the value determined by the reset curve.  
The SMART SYSTEM control module provides  
freeze-up protection as follows when the boiler  
water temperature drops below 45°F (7°C):  
Below 45°F (7°C), the boiler and system pumps  
operate constantly.  
Below 37°F (3°C), the boiler turns on.  
Boiler and pumps turn off if boiler water  
temperature rises above 45°F (7°C).  
Lower temperatures may be programmed for systems  
with anti-freeze solutions.  
Night setback  
The controller may be programmed to reduce the space  
heating and DHW set points during certain times each week.  
Seven different start and stop times may be programmed  
for the space heating setback and seven start and stop times  
for the DHW setback.  
When system return temperatures  
NOTICE  
are maintained below the dew point,  
condensation will form on the inside of the  
boiler jacket causing some internal sheet  
metal components to rust.  
Flame current support  
This feature of the SMART SYSTEM  
control module does not eliminate the  
possibility of freezing. The installation must  
still use recognized design, installation and  
maintenance practice to prevent freeze  
potential for the boiler and system.  
ƽ CAUTION  
To prevent nuisance shutdowns when the boiler is firing  
at minimum rates, the control will increase the firing rate  
when the flame signal drops too low.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
40  
Outdoor Knight XL Installation & Operation Manual  
8 Operating information  
(continued)  
Monitor external limits  
High limit operations  
Connections are provided on the connection board for  
external limits such as flow switch, low water cutoff and  
gas pressure switches. The SMART SYSTEM will shut off  
the burner and inhibit relighting whenever any of these  
external limits open.  
The Outdoor Knight XL is equipped with adjustable automatic  
reset and manual reset high limits. The automatic reset high  
limit has a maximum set point of 200°F and the manual reset  
high limit has a maximum set point of 210°F.  
When the outlet temperature exceeds 200°F, the automatic  
high limit action occurs. The boiler shuts down until the outlet  
water temperature cools below 190°F, and a 60 second timer  
has expired. If the outlet temperature continues to increase, the  
manual reset high limit action will occur at 210°F.  
Run-time and alarm outputs  
The boiler provides dry contacts for indicating when the  
boiler is running, and when it is unable to operate.  
Run-time and cycle counting  
High limit test procedure  
The control uses two timers to monitor the total hours of  
burner operation. One timer monitors the time the boiler  
is in the Space Heating Mode. The other timer monitors  
the time the boiler is firing in the DHW Mode.  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
1. Turn ON the main power to the boiler by placing the  
ON/OFF switch in the ON position.  
The control uses two (2) ignition counters to monitor  
the amount of boiler cycles. The first counter counts all  
ignitions of the control. The second counter counts only  
ignition attempts that have failed.  
2. From the Status Screen, press the NAVIGATION dial to  
access the Set Points Screen.  
3. Press the LEFT SELECT (LIMITS) key.  
4. Select the manual reset high limit (MRHL) by rotating  
the NAVIGATION dial counterclockwise, then press  
the NAVIGATION dial.  
Service reminder  
The control can be programmed for service reminder  
notification. This notification will become active when  
either a set time frame has expired, or a set amount of  
running hours or cycles has expired (all adjustable by the  
installer). The display will show a Maintenance Required  
screen. The installer’s name and phone number can be  
programmed into the control. This information will appear  
on the Maintenance Required screen. The service reminder  
notification can be reset or disabled by the installer.  
5. Decrease the set point of the MRHL to below the current  
outlet temperature (or to its minimum setting, whichever  
is higher) by turning the NAVIGATION dial  
counterclockwise.  
6. Press the RIGHT SELECT [SAVE] key.  
7. Press the RIGHT SELECT [HOME] key. The new  
parameter will upload to the control.  
8. If the current outlet temperature is above the new MRHL  
set point, the MRHL will function causing boiler lockout.  
If this occurs, skip to Step 11.  
The time dependent feature has been disabled by the  
manufacturer. To enable this feature change the parameter  
to the desired time interval, reference the Outdoor Knight  
XL Service Manual for details regarding parameters.  
9. If the current outlet temperature is below the new MRHL  
set point, locate the pinhole (SERVICE button) below the  
RESET button on the display board. Insert a thin probe  
(such as a paper clip) into the hole and press the button  
continuously for five (5) seconds to place the boiler into  
Service Mode. In Service Mode, the boiler will fire at  
ignition speed and will then modulate up to full fire.  
Error logging  
The control will hold in memory the last 10 lockouts as  
well as the last 10 blockings. The date and time of the  
occurrence will be recorded as well. Only the 10 most  
current occurrences of each will be held in memory.  
10. Once the outlet temperature rises up to the MRHL set  
point, the MRHL will function, causing the boiler to shut  
down and lock out.  
Boiler temperature regulation  
Operating temperature (target)  
11. Repeat Steps 2, 3 and 4.  
The SMART SYSTEM control module senses water  
temperature and regulates boiler firing and firing rate to  
achieve a target temperature. The target temperature can  
be set between 70°F (21°C) and 190°F (88°C).  
12. Set the MRHL to the appropriate set point by turning the  
NAVIGATION dial clockwise.  
13. Repeat Steps 6 and 7.  
14. Press the RESET button to clear the lockout.  
Target temperature is fixed when the outdoor  
sensor is not installed.  
15. If needed, press the RIGHT SELECT [STOP] key to exit  
Service Mode.  
Target temperature is calculated as described  
on this page under “Outdoor Reset Operation”  
and “Target Temperature Boost” when the  
outdoor sensor is connected.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
41  
Outdoor Knight XL Installation & Operation Manual  
8 Operating information  
Low water cutoff protection  
Sequence of the cascade  
1. The SMART SYSTEM control module uses temperature  
sensing of both supply and return areas of the heat  
exchanger. If the flow rate is too low or the outlet  
temperature too high, the control module modulates and  
shuts the boiler down. This ensures boiler shutdown in  
the event of low water or low flow conditions.  
To equalize the run time of all boilers on the Cascade, the firing  
sequence will automatically be changed at set intervals.  
The sequence will be changed once every 24 hours. The  
switching on/off sequence will be as follows:  
TIME  
Start  
SWITCHING ON SEQUENCE  
L-M1-M2-M3-M4-M5-M6-M7  
M1-M2-M3-M4-M5-M6-M7-L  
2. Some codes and jurisdiction may accept these integral  
features of the control in lieu of requiring an additional  
limit control or low water cutoff. Consult local jurisdiction  
to determine. A low water cutoff is available from the  
factory (WTR30024).  
1 hour  
2 hours  
M2-M3-M4-M5-M6-M7-L-M1  
Outdoor reset operation, if used  
If a boiler locks out or is used to heat an indirect DHW tank,  
it will automatically be given the lowest priority for the rest of  
that 24 hour period.  
Target temperature with outdoor reset  
This feature improves the system’s efficiency as the outdoor  
temperature warms up.  
DHW, Night Setback, and Ramp Delay operation with  
cascade  
See the Outdoor Knight XL Service Manual to change the  
settings.  
For normal mode DHW operation any boiler(s) in the Cascade  
can be selected to provide heat for a DHW call. Select a boiler to  
be designated as the DHW boiler. Connect the DHW thermostat  
or sensor to the terminals on the Low Voltage Connection  
Board marked for the corresponding device. When the boiler  
receives a DHW call, the Leader control will take that boiler  
out of the Cascade sequence. If another boiler is available, the  
Leader will start it up to take its place.  
Reset curve  
The reset curves look at outdoor air temperature and adjusts  
the set points.  
Cascade  
When multiple boilers are installed, they can be wired  
together in a cascade sequence. A maximum of eight boilers  
can be controlled from a single control. In this application  
one boiler would be designated as the Leader control and all  
others would be designated as Member controls. The Leader  
control can be programmed to use Lead/Lag or Efficiency  
Optimization control methods.  
The DHW boiler will adjust its set point to the programmed  
DHW boiler set point and will adjust its firing rate to maintain  
this. Once the DHW call has been satisfied, the Leader control  
will place that boiler back into the Cascade sequence.  
Switching of the boiler between DHW operation and SH  
operation when there is a call for both does not occur in Cascade  
Mode.  
Once the Leader boiler receives a call for heat from a room  
thermostat, BMS, or Modbus, the control will determine what  
the set point will be. If outdoor air reset is desired, connect  
the outdoor air sensor to the terminals on the Low Voltage  
Connection Board on the Leader boiler. The set point will be  
calculated based on the programmed reset curve parameters.  
See the Outdoor Knight XL Service Manual to program the  
reset curve. If outdoor air reset is not desired, do not connect  
the outdoor air sensor. A fixed temperature set point can be  
programmed into the control. See page 59 of this manual to  
program the set point.  
When DHW is programmed for Zone Mode, connect the DHW  
thermostat or tank sensor to the Leader boiler. When a DHW  
call is received, the Leader will modulate the entire Cascade to  
bring the system supply temperature up to the DHW boiler set  
point (if higher).  
Night Setback operation of the boilers within the Cascade is  
available. Programming of the Night Setback will be done  
through the Leader boiler. Refer to the Outdoor Knight XL  
Service manual for information regarding Night Setback.  
If the water temperature at the system supply sensor is less  
than the set point + the turn-off offset - the off-on differential,  
then the control will initiate a call for heat on the Cascade  
(see the Outdoor Knight XL Service Manual for an explanation  
of the offset and differential). The Leader will energize the  
lead boiler on the Cascade. For a new startup this will be the  
Leader boiler.  
Ramp Delay operation of the boilers as described in the Outdoor  
Knight XL Service Manual is available when the boilers are part  
of a Cascade system.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
8 Operating information  
(continued)  
Sequence of operation  
OPERATION  
DISPLAY  
1. Upon a call for heat, the gas pressure switch(es) must be closed.  
2. Once the gas pressure switch(es) are closed, the control turns  
on the appropriate pumps (system and boiler pumps for space  
heating, DHW pump for DHW). The ow switch and/or LWCO  
must close.  
3. The air pressure switch and blocked drain switch must close.  
4. The control starts the prepurge cycle by initiating the blower.  
5. The control starts the trial for ignition by ring the spark  
electrode and opening the gas valve.  
6. If ame is not detected after the sparking ends, the control will  
perform a postpurge, then start another prepurge cycle and try  
to light the burner again. On the 501 and larger models, the control  
will lock out if this second attempt also fails. On the 400 model,  
the control will perform a total of 4 attempts before locking out.  
7. If ame is detected, it holds the ring rate steady for a few  
seconds to let the ame stabilize, then it begins to modulate the  
ring rate based on a set point or some other command (such  
as a 0-10V BMS signal).  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
8 Operating information  
Sequence of operation (continued)  
OPERATION  
DISPLAY  
8. If the space heating call for heat is active, and the tank thermostat  
or sensor starts a DHW call for heat, the boiler will switch to the  
DHW mode. If programmed for normal DHW operation (not as a  
zone), the DHW pump will turn on rst, then the boiler pump will  
turn off (boiler and DHW pump operation briey overlap to ensure  
ow is maintained through the unit). This will divert the boiler’s  
outlet water from the heating system and send it to the tank coil  
instead. The control will then modulate to maintain the outlet  
temperature to the DHW boiler set point.  
9. If the boiler is not part of a Cascade, and both the space heating  
and DHW calls for heat remain active long enough, the boiler will  
switch back and forth between the two heating modes until one of  
them is satised.  
10. Once both calls for heat are satised, the control will turn off  
the burner.The blower will continue to run during the postpurge  
period.  
11. Any pumps that are running will continue to run for their respective  
pump delay times before turning off, unless programmed to  
remain on continuously. A 60 second anti-cycle period will start,  
which will delay any new call for heat until it times out.  
12. In Standby, ready to start a new cycle.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
8 Operating information  
(continued)  
Outdoor Knight XL control module  
Use the control panel (FIG. 8-1) to set temperatures, operating conditions, and monitor boiler operation.  
Figure 8-1 Control Panel  
NAVIGATION DIAL  
The information on the bottom of the display shows the functions of the two SELECT keys (on either corner), and the  
NAVIGATION dial (in the center):  
MENU = Left SELECT Key  
SETPOINTS = NAVIGATION Dial - Pressing Down  
SHDN = Right SELECT Key  
Access modes  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
User  
To save parameters and exit programming:  
The user can adjust space heating and tank target temperatures  
by pressing the NAVIGATION dial when “SETPOINTS” is  
flashing at the bottom of the display. The date and time, and  
the temperature units can also be changed (see page 36).  
Press the RIGHT SELECT [SAVE] key and then press the  
RIGHT SELECT [HOME] key.  
To enter a parameter and continue programming:  
Installer  
Press the RIGHT SELECT [SAVE] key 1 time to return to the  
parameter listings; press again to return to the menu listings.  
Remember to press the RIGHT SELECT [HOME] key when  
finished programming in order to save the changes made.  
Most parameters are available only to the installer, accessible  
by entering the installer password, see the Outdoor Knight XL  
Service Manual.  
See the Outdoor Knight XL Service Manual for a detailed  
description of parameters and access modes.  
Saving parameters (reference the Parameter Table in  
the Outdoor Knight XL Service Manual)  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
8 Operating information  
Figure 8-2 Status Display Screen  
B
A
(CALL FOR  
HEAT)  
(BOILER  
STATUS)  
C
(OPERATIONAL  
INFORMATION)  
F
D
(LEFT SELECT  
KEY)  
(RIGHT SELECT KEY)  
E
(NAVIGATION DIAL)  
Status Display Screens  
Section  
Display  
Description  
The unit has not received a call for heat from a remote thermostat nor  
has it received a call for heat from a DHW thermostat.  
STANDBY  
START  
The unit has begun a burn cycle and is checking all safety circuits.  
The unit has initiated a prepurge period on a call for heat.  
PREPURGE  
IGNITION  
The unit has begun a spark period to ignite the main burner.  
The unit has fired and is running at the displayed percentage.  
A
%
(Boiler Status  
Bar)  
The call for heat has been satisfied and the unit runs the fan for an  
additional postpurge period to clear the combustion chamber and  
vent system of residual flue products.  
POSTPURGE  
SHUTDOWN  
The unit has been placed in the OFF position.  
The controlled temperature has exceeded its set point and its offset.  
The unit has detected a condition that has temporarily interrupted  
the current call for heat.  
BLOCKED  
Room Thermostat 1 has a call for heat.  
Room Thermostat 2 has a call for heat.  
Room Thermostat 3 has a call for heat.  
B
The tank thermostat or sensor has a call for heat.  
(Call for Heat  
Indicators)  
Indicates which room thermostat demand shows priority.  
The unit is being controlled by a 0 - 10V BMS signal.  
The member unit is supplying heat while in Cascade Mode.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
8 Operating information  
(continued)  
Status Display Screens (cont’d)  
Section  
Display  
Description  
SYSTEM:  
The temperature read by the system supply sensor (if connected).  
TANK:  
The temperature read by the tank sensor (if connected).  
The temperature read by the outdoor sensor (if connected).  
OUTDOOR:  
INLET TEMP:  
OUTLET TEMP:  
DELTA T:  
The temperature read at the inlet to the heat exchanger.  
The temperature read at the outlet of the heat exchanger.  
The temperature difference between the inlet and the outlet of the  
heat exchanger.  
FLUE TEMP:  
The temperature read by the flue sensor.  
FLAME CURRENT:  
The current measured by the flame sense circuit.  
FAN SPEED:  
The speed of the combustion blower.  
BOILER PUMP:  
SYSTEM PUMP:  
DHW PUMP:  
The status of the boiler pump output.  
The status of the system pump output.  
The status of the DHW pump output.  
C
(Operational  
Information)  
BMS VOLTAGE:  
The voltage received from a BMS system.  
BLR PUMP OUTPUT:  
The speed signal sent to a variable speed boiler pump in percent.  
SYS PUMP INPUT:  
The speed signal received from a variable speed system pump control.  
RATE OUTPUT:  
SH RUN HOURS:  
SH CYCLES:  
A 0 - 10V signal indicating the firing rate of the boiler.  
The total hours of operation in the Space Heating Mode.  
The total burner cycles in the Space Heating Mode.  
The total hours of operation in the DHW Mode.  
The total burner cycles in the DHW Mode.  
DHW RUN HOURS:  
DHW CYCLES:  
LAST 10 FAULTS NO:* The last 10 lockouts.  
NIGHT SETBACK  
Shows the next Night Setback trigger (if active).  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
8 Operating information  
Status Display Screens (cont’d)  
Section  
Display  
Description  
Press and hold the LEFT SELECT key for 5 seconds to enter the Menu  
Screen.  
MENU  
EXIT  
YES  
Press the LEFT SELECT key to exit the current screen or setting.  
Press the LEFT SELECT key to confirm that the boiler needs to  
shutdown.  
D
(LEFT SELECT  
key function)  
Press the LEFT SELECT key to enter the screen that allows you to  
adjust the limit settings.  
LIMITS  
HOME  
SKIP  
Press the LEFT SELECT key to return to the Status Screen and upload  
parameter changes.  
Press the LEFT SELECT key when in the Night Setback Screen to  
access the Night Setback Skip Screen.  
Turning the NAVIGATION dial will select the next or previous Status  
Screen.  
Pressing the NAVIGATION dial will show the next fault, NSB (Night  
Setback) trigger, or ramp delay setting.  
Pressing the NAVIGATION dial will select the setting indicated by  
the cursor.  
E
(NAVIGATION  
Dial Function)  
Pressing the NAVIGATION dial will display the Set Points Screen.  
Turning the NAVIGATION dial will move the cursor up or down.  
Turning the NAVIGATION dial will increase or decrease the current  
setting.  
SHDN  
ON  
Press the RIGHT SELECT key to turn the boiler OFF.  
Press the RIGHT SELECT key to turn the boiler ON.  
F
NO  
Press the RIGHT SELECT key to cancel the shutdown operation.  
Press the RIGHT SELECT key to save the current change.  
(RIGHT SELECT  
key function)  
SAVE  
HOME  
Press the RIGHT SELECT key to return to the Status Screen and  
upload parameter changes.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
9 Maintenance  
Maintenance and annual startup  
Table 9A Service and Maintenance Schedules  
Owner maintenance  
Service technician  
(see the Outdoor Knight XL User’s Information  
Manual for instructions)  
(see the following pages for instructions)  
General:  
• Check boiler area  
• Address reported problems  
Daily  
• Inspect interior; clean and vacuum if  
necessary;  
• Check pressure/temperature  
gauge  
• Clean condensate trap and ll with fresh  
water  
• Check for leaks (water, gas, ue,  
condensate)  
• Verify ue and air passage ways in good  
condition and sealed tight  
• Check air and vent termination  
screens  
• Check system water pressure/system  
piping/expansion tank  
Monthly  
• Check control settings  
• Check relief valve  
• Check ignition and flame sense  
electrodes (sand off any deposits; clean  
and reposition)  
• Check condensate drain system  
• Check wiring and connections  
• Perform start-up checkout and performance  
Test low water cutoff (if used)  
verication per Section 7.  
• Flame inspection (stable, uniform)  
Periodically  
• Reset button (low water cutoff)  
• Flame signal (at least 10 microamps at  
high re)  
• Clean the heat exchanger if ue temperature  
is more than 54°F (30°C) above return water  
temperature.  
• Check boiler piping (gas and  
water) for leaks  
Every  
6 months  
If combustion or performance  
indicate need:  
• Operate relief valve  
• Clean heat exchanger  
• Remove and clean burner using  
compressed air only  
End  
of season  
months  
Shut boiler down (unless boiler  
used for domestic hot water)  
• Clean the blower wheel  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
9 Maintenance  
Follow the Service and maintenance procedures given throughout this manual and in component literature  
shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler  
or system. Failure to follow the directions in this manual and component literature could result in severe  
personal injury, death, or substantial property damage.  
ƽ WARNING  
The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance  
and care of the boiler designated in Table 9A and explained on the following pages must be performed to  
assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could  
result in equipment failure.  
ƽ WARNING  
Electrical shock hazard – Turn off power to the boiler before any service operation on the boiler except as  
noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock,  
causing severe personal injury or death.  
ƽ WARNING  
Address reported problems  
Figure 9-1 Condensate Trap  
1. Inspect any problems reported by the owner and correct  
before proceeding.  
RETAINING  
SCREW  
2” PVC CAP WITH  
BLOCKED DRAIN SWITCH  
Inspect boiler area  
1. Verify that boiler area is free of any combustible materials,  
gasoline and other flammable vapors and liquids.  
PVC TEE ASSEMBLY  
(FACTORY SUPPLIED)  
2. Verify that air intake area is free of any of the contaminants  
listed in Section 1 of this manual. If any of these are  
present in the boiler intake air vicinity, they must be  
removed.  
Inspect boiler interior  
CONDENSATE FROM  
HEAT EXCHANGER  
1. Remove the front access cover and inspect the interior of  
the boiler.  
TO FLOOR  
DRAIN  
The condensate trap must be filled with  
water during all times of boiler operation to  
avoid flue gas emission from the condensate  
drain line. Failure to fill the trap could result  
in severe personal injury or death.  
2. Vacuum any sediment from inside the boiler and  
components. Remove any obstructions.  
ƽ WARNING  
Clean condensate trap  
1. Inspect the condensate drain line, condensate PVC  
fittings, and condensate trap.  
Check all piping for leaks  
Eliminate all system or boiler leaks.  
2. Remove the PVC cap retaining screw from the PVC cap  
(FIG. 9-1).  
ƽ WARNING  
Continual fresh makeup water will reduce  
boiler life. Minerals can build up in sections,  
reducing heat transfer, overheating heat  
exchanger, and causing heat exchanger  
failure. Leaking water may also cause severe  
property damage.  
3. Remove the 2 inch PVC cap with the switch located at the  
top of the trap (FIG. 9-1).  
4. Remove any sediment in the trap.  
5. Fill with fresh water until the water begins to pour out of  
the drain.  
1. Inspect all water and gas piping and verify to be leak free.  
2. Look for signs of leaking lines and correct any problems  
found.  
6. Replace the cap. Press the cap onto the trap until the cap  
makes contact with the drain.  
3. Check gas line using the procedure found in Section 4 -  
Gas Connections.  
7. Replace the retaining screw.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
9 Maintenance  
(continued)  
Safety relief valves should be re-inspected  
Flue vent system and air piping  
ƽ WARNING  
AT LEAST ONCE EVERY THREE YEARS,  
by a licensed plumbing contractor or  
authorized inspection agency, to ensure  
that the product has not been affected by  
corrosive water conditions and to ensure  
that the valve and discharge line have not  
been altered or tampered with illegally.  
Certain naturally occurring conditions may  
corrode the valve or its components over  
time, rendering the valve inoperative. Such  
conditions are not detectable unless the valve  
and its components are physically removed  
and inspected. This inspection must only  
be conducted by a plumbing contractor  
or authorized inspection agency – not by  
the owner. Failure to re-inspect the boiler  
relief valve as directed could result in  
unsafe pressure buildup, which can result in  
severe personal injury, death, or substantial  
property damage.  
1. Visually inspect the entire flue gas venting system for  
blockage, deterioration or leakage.  
2. Verify that boiler vent discharge and air intake openings  
are clean and free of obstructions.  
Failure to inspect for the above conditions  
and have them repaired can result in  
severe personal injury or death.  
ƽ WARNING  
Check water system  
1. Verify all system components are correctly installed and  
operational.  
2. Check the cold fill pressure for the system. Verify it is  
correct (must be a minimum of 12 psi (82.7 kPa)).  
3. Watch the system pressure as the boiler heats up (during  
testing) to ensure pressure does not rise too high.  
Excessive pressure rise indicates expansion tank sizing or  
performance problem.  
Following installation, the valve lever must  
be operated AT LEAST ONCE A YEAR to  
ensure that waterways are clear. Certain  
naturally occurring mineral deposits may  
adhere to the valve, rendering it inoperative.  
When manually operating the lever, water  
will discharge and precautions must be  
taken to avoid contact with hot water and  
to avoid water damage. Before operating  
lever, check to see that a discharge line is  
connected to this valve directing the flow  
of hot water from the valve to a proper  
place of disposal. Otherwise severe personal  
injury may result. If no water flows, valve  
is inoperative. Shut down the boiler until a  
new relief valve has been installed.  
ƽ WARNING  
4. Inspect automatic air vents and air separators. Remove  
air vent caps and briefly press push valve to flush vent.  
Replace caps. Make sure vents do not leak. Replace any  
leaking vents.  
Check expansion tank  
1. Expansion tanks provide space for water to move in  
and out as the heating system water expands due to  
temperature increase or contracts as the water cools.  
Tanks may be open, closed or diaphragm or bladder  
type. See Section 3 - Hydronic Piping for suggested best  
location of expansion tanks and air eliminators.  
2. After following the above warning directions, if the relief  
valve weeps or will not seat properly, replace the relief  
valve. Ensure that the reason for relief valve weeping is  
the valve and not over-pressurization of the system due to  
expansion tank waterlogging or undersizing.  
Check boiler relief valve  
1. Inspect the relief valve and lift the lever to verify flow.  
Before operating any relief valve, ensure that it is piped  
with its discharge in a safe area to avoid severe scald  
potential. Read Section 3 - Hydronic Piping before  
proceeding further.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
9 Maintenance  
Inspect ignition and ame sense  
Figure 9-2 Burner Assembly - Model 400  
electrodes  
1. Remove the ignition and flame sense electrodes from the  
boiler heat exchanger access cover.  
2. Remove any deposits accumulated on the ignition/flame  
sense electrode using sandpaper. If the electrodes cannot  
be cleaned satisfactorily, replace with new ones.  
AIR / GAS  
ARM  
3. Replace ignition/flame sense electrode, making sure  
gasket is in good condition and correctly positioned.  
SCREWS  
(5)  
IMG00437  
Check ignition ground wiring  
BURNER  
1. Inspect boiler ground wire from the heat exchanger  
access cover to ground terminal strip.  
GASKET  
2. Verify all wiring is in good condition and securely  
attached.  
Figure 9-3 Burner Assembly - Model 501  
3. Check ground continuity of wiring using continuity  
meter.  
4. Replace ground wires if ground continuity is not  
satisfactory.  
AIR / GAS  
ARM  
Check all boiler wiring  
1. Inspect all boiler wiring, making sure wires are in good  
SCREWS  
(5)  
condition and securely attached.  
IMG00438  
Check control settings  
BURNER  
1. Set the SMART SYSTEM control module display to  
Parameter Mode and check all settings. See Section 1 of  
the Outdoor Knight XL Service Manual. Adjust settings  
if necessary. See Section 1 of the Outdoor Knight XL  
Service Manual for adjustment procedures.  
GASKET  
Figure 9-4 Burner Assembly - Models 601 - 801  
2. Check settings of external limit controls (if any) and  
adjust if necessary.  
Perform start-up and checks  
1. Start boiler and perform checks and tests specified in  
AIR / GAS  
ARM  
Section 7 - Start-up.  
2. Verify cold fill pressure is correct and that operating  
pressure does not go too high.  
IMG0043  
9
Check burner ame  
1. Inspect flame through observation window.  
BURNER  
2. If the flame is unsatisfactory at either high fire or low fire,  
turn off boiler and allow boiler to cool down. Remove  
the burner and clean it thoroughly using a vacuum  
cleaner or compressed air. Do not use compressed air to  
clean burner if performed inside a building.  
GASKET  
SCREWS  
(5)  
3. Remove the burner, reference FIG.’s 9-2 thru 9-4.  
4. When replacing the burner, ensure gasket is in good  
condition and positioned correctly (FIG.’s 9-2 thru 9-4).  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
9 Maintenance  
(continued)  
6. Use a vacuum cleaner to remove any accumulation on the  
boiler heating surfaces. Do not use any solvent.  
7. Brush the heat exchanger while dry using a nylon bristle  
brush. Caution: DO NOT use a metal brush. Re-vacuum  
the heat exchanger.  
8. Finish cleaning using a clean cloth dampened with warm  
water. Rinse out debris with a low pressure water supply.  
9. Allow the heat exchanger to thoroughly dry.  
10. Remove the field supplied rear refractory cover from the  
back of the combustion chamber of the heat exchanger and  
reassemble.  
11. Close isolation valves on piping to isolate boiler from  
system. Attach a hose to the boiler drain and flush boiler  
thoroughly with clean water by using purging valves to  
allow water to flow through the water make-up line to the  
boiler.  
Check ame signal  
1. At high fire the flame signal shown on the display should  
be at least 10 microamps.  
2. A lower flame signal may indicate a fouled or damaged  
flame sense electrode. If cleaning the flame sense electrode  
does not improve, ground wiring is in good condition,  
and ground continuity is satisfactory, replace the flame  
sense electrode.  
3. See Section 3 - Troubleshooting in the Outdoor Knight  
XL Service Manual for other procedures to deal with low  
flame signal.  
Review with owner  
1. Review the Outdoor Knight XL User’s Information  
Manual with the owner.  
12. Perform start-up and check-out procedures in the Check  
Flame and Combustion - Section 7 - Startup on pages 35  
and 37 of this manual.  
2. Emphasize the need to perform the maintenance schedule  
specified in the Outdoor Knight XL User’s Information  
Manual (and in this manual as well).  
13. Replace the access cover and restore boiler to operation.  
3. Remind the owner of the need to call a licensed contractor  
should the boiler or system exhibit any unusual behavior.  
Table 9B Heat Exchanger Cleaning Kits  
4. Remind the owner to follow the proper shutdown  
procedure and to schedule an annual start-up at the  
beginning of the next heating season.  
Kit  
Part  
Component  
Description  
Model  
Number Number  
CTN20005  
Rear Refractory Cover  
Nylon 4" Wheel Brush*  
MSC20083*  
Cleaning boiler heat exchanger  
For recommended materials; including brush, appropriate  
extension(s), refractory cover, and detailed instructions see  
Table 9B - Heat Exchanger Cleaning Kits.  
400  
KIT30063  
MSC20084  
3mm Allen Wrench  
1/4" x 24" Drill Extension  
Rear Refractory Cover  
Nylon 4" Wheel Brush*  
1/4" x 12" Drill Extension  
1/4" x 24" Drill Extension  
MSC20086  
CTN20005  
MSC20083*  
KIT30064  
1. Shut down boiler:  
501 - 801  
• Follow the “To Turn Off Gas to Appliance” instructions  
for the boiler in Section 7 - Startup.  
MSC20085  
MSC20086  
• Do not drain the boiler unless it will be exposed to  
freezing temperatures. If using freeze prevention fluid  
in system, do not drain.  
* Do NOT use a metal brush. Only use  
the kit provided brush or an equivalent  
replacement nylon brush.  
ƽ CAUTION  
2. Allow time for the boiler to cool to ambient temperature  
if it has been firing.  
Figure 9-5 Rope Gasket - Heat Exchanger Door  
3. Remove the nuts securing the heat exchanger access cover  
to the heat exchanger and set aside.  
4. Remove the heat exchanger access cover, burner, and  
gas/air arm assembly.  
ROPE GASKET  
The boiler contains ceramic fiber  
ƽ WARNING  
materials. Use care when handling these  
materials per instructions in the Service  
Manual. Failure to comply could result in  
severe personal injury.  
CAUTION: IF GASKET IS DAMAGED  
DO NOT REUSE, THE HEAT EXCHANGER DOOR  
MUST BE REPLACED.  
5. Remove the condensate hose from the heat exchanger  
end. Connect a field supplied 3/4" diameter hose to  
a drain pan. Using field supplied means, cover the  
refractory in the back of the combustion chamber of the  
heat exchanger.  
Rope gasket is intended for sealing combustion  
(FIG. 9-5). If damaged DO NOT reuse, the  
NOTICE  
heat exchanger door must be replaced. Consult  
factory for replacement heat exchanger door  
(kit WTR3080 and WTR3086).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
53  
Outdoor Knight XL Installation & Operation Manual  
10 Diagrams  
Figure 10-1 Wiring Diagram  
LOW VOLTAGE  
120 VAC  
HIGH VOLTAGE  
BOX DEPICTS  
OPTIONAL ITEMS  
BOX DEPICTS  
DUAL SENSOR  
SINGLE HOUSING  
INTEGRATED  
CONTROL  
CONNECTION BOARD  
L
N
ALARM  
CONTACTS  
1
2
JUNCTION  
BOX  
RELAY  
BOARD  
X-7  
DHW  
PUMP  
RUN-TIME  
3
CN2-4  
CN2-2  
CN1-5  
OR  
BR  
PR  
OR  
CONTACTS  
X1-3  
X1-4  
X1-2  
4
K1  
K2  
K3  
24 VAC LOUVER  
5
CN1-6  
CN1-3  
OR  
BR  
RELAY COIL  
BOILER  
PUMP  
6
LOUVER  
PROVING SWITCH  
GAS PRESSURE  
SWITCH  
7
BK  
BK  
BK  
BK  
X4-7  
X4-14  
X4-6  
CN5-1  
CN5-8  
CN5-2  
CN5-9  
CN5-3  
CN5-10  
CN5-11  
CN5-4  
CN5-5  
CN5-14  
CN5-12  
CN5-6  
CN5-13  
CN5-7  
CN1-4  
CN1-1  
8
BR  
PR  
CN2-3  
9
SYSTEM  
PUMP  
10  
CN2-1  
CN1-2  
PR  
X4-13  
X4-5  
BK  
BK  
BK  
BK  
BK  
X4-12  
X4-11  
X4-4  
ON/OFF  
SWITCH  
L
X1-6  
X1-5  
BK  
W
120V  
GND  
N
FLOW  
SWITCH  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
X4-3  
SUPPLY  
BK  
X4-8  
BK  
BK  
BK  
BK  
TANK  
X4-10  
X4-2  
THERMOSTAT  
HEAT/LOOP  
X4-9  
G
R
X1-8  
X1-1  
3
2
1
DEMAND  
X4-1  
HEAT/LOOP  
DEMAND  
HEAT/LOOP  
TRANSFORMER  
3.5A  
DEMAND  
RW G  
3
SYSTEM  
SENSOR  
OUTDOOR  
SENSOR  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
KB 801  
ONLY  
1
2
BLOWER  
TANK  
SENSOR  
1
2
3
4
5
SHIELD  
A
CASCADE  
B
SHIELD  
X5-7  
X5-16  
X5-8  
R
T
CN6  
X6  
W
BK  
Y
BMS  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
+
0-10V  
X5-15  
X5-9  
IN  
-
SYS PUMP  
+
0-10V  
IN  
-
BLR PUMP  
X5-1  
BL  
O
+
0-10V  
OUT  
-
X5-2  
RATE  
+
O-TEMP HEX SW  
0-10V  
BLOCKED DRAIN SWITCH  
OUT  
-
X5-10  
X5-11  
X5-4  
P
SHIELD  
AIR PRESSURE SWITCH  
A
O/BK  
R/BK  
GY  
MODBUS  
-T  
-T  
-T  
-T  
-T  
OPTION  
B
OPERATING SENSOR S1a  
HIGH LIMIT SENSOR S1b  
SHIELD  
X5-12  
X5-6  
24 VAC  
LOW  
CN7-1  
COM  
INLET SENSOR S2  
FLUE SENSOR S3a  
FLUE SENSOR S3b  
P/BK  
W/BK  
PR  
CN7-2  
CN7-3  
CN7-4  
WATER  
CUT-OFF  
X5-5  
X5-13  
X5-14  
RBLG  
Y
X2-2  
BK  
Y
GAS VALVE  
@24VAC  
O
GY  
G
X4-1  
X9-1  
X9-2  
X9-3  
X9-4  
X2-1  
X1-7  
TR2  
X4-2  
X4-3  
X4-4  
MODBUS BOARD  
MTR-01  
W/R  
FLAME SENSOR  
SPARK  
ROD  
G
SHIELD  
GROUNDING  
JUMPER  
X5-1  
X5-2  
CAUTION HIGH VOLTAGE SPARK LEAD  
BK  
W
G
X1-1  
X1-2  
X1-3  
Notes:  
1. All wiring must be installed in accordance with: local, state, provincial and national code requirements per either N.E.C. in USA or C.S.A. in Canada.  
2. If any original equipment wire as supplied with the appliance must be replaced, it must be replaced with wire having same wire gauge (AWG) and rated for a  
minimum of 105°C. Exceptions: Replacement high voltage spark lead and ribbon cables must be purchased from the factory. Use of a non-approved spark lead  
or ribbon cables can lead to operational problems which could result in non-repairable damage to the integrated controller or other components.  
3. Actual connector block locations may vary from those shown on diagrams. Refer to actual components for proper connector block locations when using  
diagrams to troubleshoot unit.  
WIRING DIAGRAM  
LBL20116 REV E  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight XL Installation & Operation Manual  
10 Diagrams  
(continued)  
Figure 10-2 Ladder Diagram  
JUNCTION BOX  
120VAC  
NEUTRAL  
TERMINAL STRIP  
120V SUPPLY "L"  
TERMINAL STRIP  
120V SUPPLY "N"  
L
IN  
L
OUT  
GROUND  
SYSTEM  
PUMP  
CONTACTS  
INTEGRATED CONTROL  
ON / OFF  
SWITCH  
BLOWER  
2
1
X1-1  
X1-2  
X1-6  
F2  
3.15A  
SYSTEM  
PUMP  
3
BOILER  
F1  
5A  
PUMP  
CONTACTS  
SYSTEM PUMP  
RELAY  
SYSTEM PUMP  
RELAY  
X1-3  
BOILER  
PUMP  
DHW PUMP  
RELAY  
DHW PUMP  
RELAY  
DHW  
PUMP  
X1-4  
CONTACTS  
BOILER PUMP  
RELAY  
BOILER PUMP  
RELAY  
F3  
DHW  
PUMP  
.8A  
24V DC  
SUPPLY  
RELAY BOARD  
X5-9  
X5-1  
120 VAC  
24 VAC  
3.5A  
X4-3  
KB 801  
ONLY  
CONNECTION BOARD  
INTEGRATED  
CONTROL  
LWCO  
CN5-5  
FLOW  
CN5-14 X4-8  
CN7-3  
CN7-4  
CN7-2  
SWITCH  
11  
12  
CN5-10  
X4-12  
24 VAC  
CN7-1  
HEAT/LOOP  
DEMAND  
1
CN5-7  
CN5-13  
CN5-6  
X4-1  
X4-9  
20  
18  
16  
14  
19  
HEAT/LOOP  
DEMAND 2  
17  
HEAT/LOOP  
DEMAND 3  
X4-2  
15  
13  
TANK  
THERMOSTAT  
CN5-12  
X4-10  
LOW GAS  
PRESSURE  
SWITCH  
HIGH GAS  
PRESSURE  
SWITCH  
CN5-11  
CN5-3  
X4-11  
X4-5  
9
10  
INTEGRATED  
CONTROL  
LOUVER  
RELAY COIL  
5
6
7
24VAC  
LOUVER  
PROVING SWITCH  
CN5-4  
X4-4  
X7  
8
RIBBON CABLE  
X5-2  
PC INTERFACE  
BLOCKED  
X5-10  
X5-11  
X2-2  
O-TEMP HEX SW  
DRAIN SWITCH  
X5-6  
X5-4  
S2  
INLET  
SENSOR  
AIR PRESSURE  
SWITCH  
S1a  
S1b  
S3a  
OPERATING  
SENSOR  
1
X5-12  
X5-5  
HIGH LIMIT  
SENSOR  
GAS VALVE  
2
FLUE  
SENSOR  
GAS VALVE  
RELAY  
X2-1  
6
X5-13  
X5-14  
S3b  
FLUE  
SENSOR  
BLOWER  
1
2
4
5
X5-7  
X5-16  
X5-8  
13  
CONNECTION  
BOARD  
CN5-1  
CN5-8  
X4-7  
1
2
ALARM  
CONTACTS  
X4-14  
X5-15  
CN5-2  
CN5-9  
X4-6  
3
4
RUN-TIME  
CONTACTS  
X4-13  
TR2  
CN6  
CN6  
CN6  
X6  
X6  
X6  
S6  
21  
22  
X1-7  
SYSTEM  
SENSOR  
S5  
FLAME ROD  
23  
24  
26  
27  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
OUTDOOR  
SENSOR  
SPARK  
ROD  
CN6  
CN6  
X6  
X6  
S4  
TANK  
SENSOR  
SHIELD  
CAUTION HIGH VOLTAGE SPARK LEAD  
CN6  
X6  
A
CASCADE  
B
CN6  
CN6  
X6  
X6  
NOTES:  
1. Where possible, switches are shown without utilities (gas, water or  
electricity) connected to the unit. As such, actual switch states may  
vary from those shown on diagrams depending upon whether utilities  
are connected or a fault condition is present.  
SHIELD  
CN6  
CN6  
CN6  
X6  
X6  
X6  
BMS  
+
0-10V  
IN  
-
+
-
SYS PUMP  
IN  
2. See wiring diagram for additional notes.  
0-10V  
0-10V  
0-10V  
CN6  
CN6  
X6  
X6  
+
-
BLR PUMP  
OUT  
CN6  
CN6  
X6  
X6  
BOX DEPICTS  
OPTIONAL ITEMS  
+
-
RATE  
OUT  
LOW VOLTAGE  
120 VAC  
HIGH VOLTAGE  
M
O
D
B
U
S
SHIELD  
CN8-1  
CN8-2  
CN8-3  
X6-1  
X6-2  
X4-1  
X9-2  
X9-1  
X9-3  
A
MODBUS  
X4-2  
X4-3  
B
X6-3  
LADDER DIAGRAM  
LBL20141 REV D  
SHIELD  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Revision Notes: Revision A (ECO #C11234) initial release.  
Revision B (ECO #C11235) reects updates made to the freezing  
conditions warnings.  
OKBX-I-O Rev B  
10/12  
Download from Www.Somanuals.com. All Manuals Search And Download.  

KWC Indoor Furnishings 10271303 User Manual
Learning Resources Watch LER 2384 User Manual
Lennox Hearth Indoor Fireplace 3 Piece Louver Kit User Manual
Life Fitness Home Gym CMDAP User Manual
Lincoln Electric Welding Consumables EIM 248 User Manual
Mace DVR DVR 9416 User Manual
Mackie Stereo Amplifier M2600 User Manual
Marantz CD Player DR4050 User Manual
McCulloch Lawn Mower 96041009100 User Manual
Mellerware Fan 35810 User Manual