Lochinvar Boiler 151 286 User Manual

OKB-I-O Rev C  
Outdoor Knight Boiler  
Installation & Operation  
Manual  
Models: 151 - 286  
This manual must only be used by  
ƽ WARNING  
a qualified heating installer / service  
technician. Read all instructions,  
including this manual and the  
Outdoor Knight Boiler Service  
Manual, before installing. Perform  
steps in the order given. Failure  
to comply could result in severe  
personal injury, death, or substantial  
property damage.  
Save this manual for future reference.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
Please read before proceeding  
Installer – Read all instructions, including  
this manual and the Outdoor Knight  
Boiler Service Manual, before installing.  
Perform steps in the order given.  
When servicing boiler –  
ƽ WARNING  
• To avoid electric shock, disconnect electrical supply  
before performing maintenance.  
User – This manual is for use only  
• To avoid severe burns, allow boiler to cool before  
performing maintenance.  
by  
a
qualified heating installer/  
service technician. Refer to the User’s  
Information Manual for your reference.  
Boiler operation –  
Have this boiler serviced/inspected by  
a qualified service technician, at least  
annually.  
• Do not block flow of combustion or ventilation air to  
the boiler.  
• Should overheating occur or gas supply fail to shut off,  
do not turn off or disconnect electrical supply to  
circulator. Instead, shut off the gas supply at a location  
external to the appliance.  
Failure to comply with the above could  
result in severe personal injury, death or  
substantial property damage.  
When calling or writing about the boiler  
– Please have the boiler model and serial  
number from the boiler rating plate.  
NOTICE  
• Do not use this boiler if any part has been under water.  
The possible damage to a flooded appliance can be  
extensive and present numerous safety hazards. Any  
appliance that has been under water must be replaced.  
Consider piping and installation when  
determining boiler location.  
Any claims for damage or shortage in  
shipment must be filed immediately  
against the transportation company by  
the consignee.  
Boiler water –  
• Thoroughly flush the system (without boiler  
connected) to remove sediment. The high-efficiency  
heat exchanger can be damaged by build-up or  
corrosion due to sediment.  
Factory warranty (shipped with unit) does  
not apply to units improperly installed or  
improperly operated.  
• Continual fresh make-up water will reduce boiler life.  
Mineral buildup in the heat exchanger reduces heat  
transfer, overheats the stainless steel heat exchanger,  
and causes failure. Addition of oxygen carried in by  
makeup water can cause internal corrosion in system  
components. Leaks in boiler or piping must be repaired  
at once to prevent makeup water.  
Failure to adhere to the guidelines on this  
page can result in severe personal injury,  
death, or substantial property damage.  
ƽ WARNING  
If the information in this manual is not  
followed exactly, a fire or explosion may  
result causing property damage, personal  
injury or loss of life.  
ƽ WARNING  
Do not use petroleum-based cleaning or  
ƽ CAUTION  
sealing compounds in the boiler system.  
Gaskets and seals in the system may be  
damaged. This can result in substantial  
property damage.  
This appliance MUST NOT be installed in  
any location where gasoline or flammable  
vapors are likely to be present.  
Do not use “homemade cures” or “boiler  
patent medicines”. Serious damage to  
WHAT TO DO IF YOU SMELL GAS  
ƽ CAUTION  
the boiler, personnel, and/or property  
may result.  
• Do not try to light any appliance.  
• Do not touch any electric switch; do  
not use any phone in your building.  
• Immediately call your gas supplier  
from a near by phone. Follow the  
gas supplier’s instructions.  
• If you cannot reach your gas supplier,  
call the fire department.  
• Installation and service must be  
performed by a qualified installer,  
service agency, or the gas supplier.  
Freeze protection fluids –  
• NEVER use automotive antifreeze. Use only inhibited  
propylene glycol solutions, which are specifically  
formulated for hydronic systems. Ethylene glycol is  
toxic and can attack gaskets and seals used in hydronic  
systems.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
The Outdoor Knight Boiler - How it works...  
1. Stainless steel heat exchanger  
17. Manual air vent  
Allows system water to flow through specially designed  
coils for maximum heat transfer, while providing  
Designed to remove trapped air from the heat exchanger  
coils.  
protection against flue gas corrosion.  
encased in a jacket that contains the combustion process.  
The coils are  
18. High voltage junction box  
The junction box contains the connection points for the line  
voltage power and all pumps.  
2. Combustion chamber access cover  
Allows access to the combustion side of the heat  
exchanger coils.  
19. Boiler drain port  
Location from which the heat exchanger can be drained.  
20. Low voltage connection board  
The connection board is used to connect external low voltage  
devices.  
21. Low voltage wiring connections  
Conduit connection points for the low voltage  
connection board.  
22. Condensate drain connection  
Connects the condensate drain line to a 1/2" PVC union.  
23. Access cover - top front  
3. Blower  
The blower pulls in air and gas through the venturi (item  
5). Air and gas mix inside the blower and are pushed into the  
burner, where they burn inside the combustion chamber.  
4. Gas valve  
The gas valve senses the negative pressure created by the  
blower, allowing gas to flow only if the gas valve is  
powered and combustion air is flowing.  
5. Venturi  
Provides protection of the control panel / display from outside  
elements.  
The venturi controls air and gas flow into the burner.  
6. Flue gas sensor (limit rated)  
24. Access cover - bottom front  
Provides access to the burner.  
25. Ignition electrode  
Provides direct spark for igniting the burner.  
26. Flame inspection window  
The quartz glass window provides  
surface and flame.  
27. Relief valve  
Protects the heat exchanger from an over pressure condition.  
The relief valve provided with the unit is set at 30 psi.  
28. Flame sensor  
Used by the control module to detect the presence of burner  
flame.  
29. Line voltage wiring connections  
Conduit connection points for the high voltage junction box.  
30. Top access cover  
Provides access to the internal components.  
31. Power switch  
This sensor monitors the flue gas exit temperature. The control  
module will modulate and shut down the boiler if flue gas  
temperature gets too hot. This protects the flue pipe from  
overheating.  
7. Boiler outlet temperature sensor (housed with the  
a
view of the burner  
high limit sensor)  
This sensor monitors boiler outlet water temperature (system  
supply). If selected as the controlling sensor, the control  
module adjusts boiler firing rate so the outlet temperature is  
correct.  
8. Boiler inlet temperature sensor  
This sensor monitors return water temperature (system  
return). If selected as the controlling sensor, the control  
module adjusts the boiler firing rate so the inlet temperature is  
correct.  
9. Temperature and pressure gauge (field installed, not  
shown)  
Monitors the outlet temperature of the boiler as well as the  
system water pressure.  
Turns 120 VAC ON/OFF to the boiler.  
32. Leveling legs  
10. Electronic LCD display  
Used to allow the heat exchanger to be leveled. This is needed  
for the proper draining of the condensate from the combustion  
chamber.  
The electronic display consists of 4 buttons, a navigation dial  
and a multiple line liquid crystal display.  
11. Flue pipe adapter  
33. Air pressure switch  
The air pressure switch detects blocked inlet conditions.  
34. Transformer  
The transformer provides 24V power to the integrated control.  
35. High limit sensor (housed with the outlet  
temperature sensor)  
Device that monitors the outlet water temperature. If the  
temperature exceeds its setting, the integrated control will  
break the control circuit, shutting the boiler down.  
36. Gas shutoff switch  
Allows for the connection of the vent system to the  
boiler.  
12. Burner (not shown)  
Made with metal fiber and stainless steel construction,  
the burner uses pre-mixed air and gas and provides a  
wide range of firing rates.  
13. Water outlet (system supply)  
NPT water connection that supplies hot water to the  
system, either 1" or 1-1/4", depending on the  
model.  
An electrical switch designed to cut power to the gas valve to  
prevent releasing any gas.  
37. Over-temp switch (Model 286 Only) (located underneath  
access cover)  
14. Water inlet (system return)  
NPT water connection that returns water from the  
system to the heat exchanger, either 1" or 1-1/4",  
depending on the model.  
An electrical switch designed to shut down boiler operation in  
the event the outer back of the heat exchanger, directly above the  
flue connection exceeds 604°F (318°C). This is a one time  
switch and could warrant a heat exchanger replacement. Check  
the integrity of the rear refractory at the back of the upper coil if  
the switch opens.  
15. Gas connection pipe  
Threaded pipe connection, either 1/2" or 3/4",  
depending on the model. This pipe should be connected  
to the incoming gas supply for the purpose of delivering  
gas to the boiler.  
16. SMART SYSTEM Control Module  
38. Air cover  
The SMART SYSTEM Control responds to internal and  
external signals and controls the blower, gas valve, and pumps  
to meet the heating demand.  
Covers the over-temp switch and the flue collar with flue sensor.  
39. Flue pipe assembly  
Factory supplied components for a complete venting system.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
Outdoor Knight Boiler Installation & Operation Manual  
The Outdoor Knight Boiler - How it works...  
Models 151 - 211  
(continued)  
21  
30  
31  
29  
10  
23  
24  
IMG00366  
11  
6
IMG00365  
38  
Front View - Models 151 - 211  
Rear View - Models 151 - 211  
18  
20  
16  
39  
33  
15  
7
35  
34  
8
14  
27  
10  
25  
3
4
5
36  
1
17  
2
26  
28  
13  
19  
1
32  
22  
IMG00368  
IMG00367  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Right Side (inside unit) - Models 151 - 211  
Left Side (inside unit) - Models 151 - 211  
5
Outdoor Knight Boiler Installation & Operation Manual  
The Outdoor Knight Boiler - How it works...  
29  
Model 286  
38  
21  
30  
39  
31  
15  
37  
10  
23  
24  
IMG00380  
6
IMG00379  
11  
Rear View - Model 286  
Front View - Model 286  
34  
18  
20  
10  
33  
16  
4
15  
8
5
36  
3
14  
27  
25  
28  
2
1
13  
17  
19  
32  
IMG00381  
IMG00382  
22  
Left Side (inside unit) - Model 286  
Right Side (inside unit) - Model 286  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
Ratings  
A
S
M
E
H
Outdoor Knight Boiler  
AHRI Rating  
Other Specifications  
Heating  
Capacity  
MBH  
Input  
MBH  
AFUE  
%
Net  
AHRI  
Ratings  
Water,  
MBH  
Model Number  
Boiler  
Water  
Air  
Size  
Water  
Gas  
Content Connections Connections  
Gallons  
(Note 4)  
Note: Change “N” to  
“L” for L.P. gas models.  
Max  
Min  
150  
(Note 2,5)  
141  
(Note 1, 5)  
94  
(Note 3,5)  
122  
1.3  
1.7  
2.4  
1"  
1"  
1/2"  
1/2"  
3/4"  
3"  
3"  
4"  
OKN151  
OKN211  
OKN286  
30  
42  
57  
210  
285  
197  
266  
171  
232  
94  
94  
1-1/4"  
Maximum allowed working pressure is located on the rating plate.  
NOTICE  
Notes:  
1. As an Energy Star Partner, Lochinvar has determined that  
outdoor boilers meet the Energy Star guidelines for energy  
efficiency.  
2. The ratings are based on standard test procedures prescribed  
by the United States Department of Energy.  
3. Net AHRI ratings are based on net installed radiation of  
sufficient quantity for the requirements of the building  
and nothing need be added for normal piping and pickup.  
Ratings are based on a piping and pickup allowance of 1.15.  
4. Standard outdoor boilers are equipped to operate from sea  
level to 4,500 feet only with no adjustments. The boiler will  
de-rate by 4% for each 1,000 feet above sea level up to 4,500  
feet.  
5. Ratings have been confirmed by the Hydronics Section of  
AHRI.  
6. Outdoor boilers temperature controls comply with the  
requirements of CSD-1 Section CW-400 requirements.  
The manual reset high limit provided with the outdoor  
boiler is listed to UL353.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
1 Determine boiler location  
Do not locate unit so that high winds can  
deflect off of adjacent walls, buildings  
or shrubbery causing recirculation.  
Recirculation of flue products may cause  
operational problems, bad combustion or  
damage to controls. Locate unit at least  
3 feet (0.91m) from any wall or vertical  
surface to prevent wind conditions from  
affecting performance.  
Installation must comply with:  
ƽ CAUTION  
Local, state, provincial, and national codes, laws,  
regulations, and ordinances.  
National Fuel Gas Code, ANSI Z223.1 – latest edition.  
Standard for Controls and Safety Devices for Automatically  
Fired Boilers, ANSI/ASME CSD-1, when required.  
National Electrical Code.  
The outdoor unit must not be installed in  
an area that is enclosed by walls or a fence  
that will block free wind movement around  
the unit. Free movement of wind around  
the outdoor unit is required to carry away  
the flue products and provide combustion  
air. The flue outlet/combustion air inlet  
of an outdoor unit must not be installed  
closer than 10 feet from an inside corner of  
an L-shaped structure. Walls or enclosed  
fencing may cause eddy currents which  
can recirculate the flue products into the  
combustion air inlet. Recirculation of flue  
products may cause operational problems,  
bad combustion or non-warrantable damage  
to controls.  
The Outdoor Knight gas manifold and  
NOTICE  
controls met safe lighting and other  
performance criteria when the boiler  
underwent tests specified in ANSI Z21.13  
– latest edition.  
Outdoormodelsmustbeinstalledoutdoors  
ƽ WARNING  
only and must use the outdoor vent kit  
assembly supplied by the manufacturer.  
Personal injury or product damage may  
result if any other cap is used or if an  
outdoor model is used indoors. All covers,  
doors and jacket panels must be properly  
installed to ensure proper operation and  
prevent a hazardous situation.  
This product contains  
a
condensate  
CAUTION  
-Do not install the outdoor unit under a  
deck.  
-Do not install an outdoor unit in a well,  
stairwell, alcove, courtyard or other  
recessed area.  
management and disposal system that  
may be subject to freezing if exposed  
to sustained temperatures below 32°F.  
Precautions should be taken to protect  
the condensate trap and drain lines during  
extended periods of outdoor temperatures  
below 32°F.  
ƽ WARNING  
-Do not install outdoor units on stack  
frames.  
Failure to comply with the above could  
result in severe personal injury, death or  
substantial property damage.  
Before locating the boiler, check:  
1. Check for nearby connection to:  
• Water piping  
• Gas supply piping  
• Electrical power  
- Do not install outdoor units in locations  
where rain from building runoff drains  
will spill onto the unit.  
CAUTION  
- Do not locate the outdoor unit so that  
water from sprinklers may spray directly  
onto it. Water may damage controls or  
other electrical components.  
2. -Keep venting areas free of obstructions.  
-Keep area clean and free of combustible and flammable  
materials.  
-To avoid a blocked air inlet or blocked flue condition,  
keep the outdoor air inlet and flue outlet clear of leaves,  
debris, etc.  
3. Check area around the boiler. Remove any combustible  
materials, gasoline and other flammable liquids.  
Do not install outdoor models directly  
CAUTION  
Failure to keep the boiler area clear and free  
ƽ WARNING  
on the ground. You must install the  
of combustible materials, gasoline and other  
outdoor unit on a concrete, brick, block or  
pressure-treated wood platform.  
flammable liquids and vapors can result in  
severe personal injury, death or substantial  
property damage.  
4. If a new boiler will replace an existing boiler, check for and  
correct system problems, such as:  
• System leaks causing oxygen corrosion or heat exchanger  
cracks from hard water deposits.  
• Incorrectly-sized expansion tank.  
8
• Lack of freeze protection in boiler water causing system  
Download from Www.Somanuals.com. All Manuals Search And Download.  
and boiler to freeze and leak.  
Outdoor Knight Boiler Installation & Operation Manual  
1 Determine boiler location  
(continued)  
Flooring and foundation  
Flooring  
Provide clearances:  
Clearances from combustible materials  
1. Hot water pipes—at least 1/4" (6 mm) from combustible  
materials.  
TheOutdoorKnightisapprovedforinstallationoncombustible  
flooring.  
2. Vent pipes—minimum of 14" (356mm) from the rear and  
0" on the right side from combustible materials.  
Do not install the boiler on carpeting even if  
ƽ WARNING  
foundation is used. Fire can result, causing  
severe personal injury, death, or substantial  
property damage.  
Clearances for service access  
1. If you do not provide the minimum clearances, it may  
not be possible to service the boiler without  
removing it from the space.  
Under no circumstances is the manufacturer to be held  
responsible for water damage in connection with this appliance,  
or any of its components. If flooding is possible, elevate the  
boiler sufficiently to prevent water from reaching the boiler.  
Recommended service clearances:  
Front  
Top  
Left side -  
Rear  
-
-
24" (610mm)  
24" (610mm)  
24" (610mm)  
24" (610mm)  
Prevent combustion air contamination  
Do not install unit in locations that can allow contamination  
of combustion air. Refer to Table 1A for products and areas  
which may cause contaminated combustion air.  
-
Outdoor vent / air intake location  
The flue products discharged from the  
Table 1A Corrosive Contaminants and Sources  
ƽ WARNING  
flue outlet on the outdoor vent may be  
very hot. Avoid touching or other direct  
contact with the flue gases or the vent  
termination assembly. These components  
are hot and direct contact can result in  
burns.  
Products to avoid:  
Spray cans containing chloro/fluorocarbons  
Permanent wave solutions  
Chlorinated waxes/cleaners  
Chlorine-based swimming pool chemicals  
Calcium chloride used for thawing  
Sodium chloride used for water softening  
Refrigerant leaks  
To prevent recirculation of the flue products into the  
combustion air inlet, follow all instructions in this section.  
Flue gas condensate can condense on exterior walls or on the  
vent. Some discoloration to exterior building or unit surfaces  
can be expected. Adjacent brick or masonry surfaces should  
be protected with a rust resistant sheet metal plate.  
Paint or varnish removers  
Hydrochloric acid/muriatic acid  
Maintain a minimum of 24" (610mm) clearance to the side  
of the air inlet.  
Cements and glues  
Antistatic fabric softeners used in clothes dryers  
Locate the outdoor vent termination at least 48" (1.22m)  
below and 48" (1.22m) horizontally from any window, door,  
walkway or gravity air intake.  
Chlorine-type bleaches, detergents, and cleaning solvents  
found in household laundry rooms  
Adhesives used to fasten building products and other similar  
products  
Locate outdoor unit at least 10 feet (3.05m) away from any  
forced air inlet.  
Areas likely to have contaminants  
Dry cleaning/laundry areas and establishments  
Swimming pools  
Multiple outdoor unit installations require 24" (.61m)  
clearance between each vent termination.  
Clearances around outdoor installations can change with  
time. Do not allow the growth of trees, shrubs or other plants  
to obstruct the proper operation of the outdoor vent system.  
Metal fabrication plants  
Beauty shops  
Refrigeration repair shops  
Photo processing plants  
Auto body shops  
Plastic manufacturing plants  
Furniture refinishing areas and establishments  
New building construction  
Remodeling areas  
Garages with workshops  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
Outdoor Knight Boiler Installation & Operation Manual  
2 Prepare boiler  
Remove boiler from wood pallet  
Figure 2-2 Install Flue Pipe Assembly  
1. After removing the outer shipping carton from the boiler,  
WALL STRAP SCREWS  
remove the installation kit.  
2. Remove the front access covers to access the lag bolts in  
front of the unit (FIG. 2-1).  
BIRD SCREEN  
WALL STRAP  
3. To remove the boiler from the pallet (after removing the  
front access covers):  
a. Remove the two lag bolts from the wood pallet  
inside the boiler (FIG. 2-1).  
FLUE PIPE  
b. Detach the boiler from the lag bolts in the rear of the  
unit, see FIG. 2-1.  
Do not drop the boiler or bump the jacket  
NOTICE  
on the floor or pallet. Damage to the  
boiler can result.  
ELBOW  
Figure 2-1 Boiler Mounted on Shipping Pallet  
NOTE: VERIFY GASKETS ARE  
SEATED EVENLY INSIDE  
THE GROOVE.  
IMG00443  
FLUE ADAPTER  
AIR COVER  
5. Slide the vent pipe through the wall strap and insert it  
into the elbow.  
6. Install the bird screen into the top of the flue pipe.  
. 2  
Gas conversions  
For a boiler already installed, you must  
turn off gas supply, turn off power and  
ƽ WARNING  
Install flue pipe assembly (reference FIG. 2-2 for flue  
pipe assembly)  
allow boiler to cool before proceeding.  
You must also completely test the boiler  
after conversion to verify performance  
as described under Start-up, Section 7  
of this manual. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
The outdoor boiler is shipped with all the necessary vent  
components. All components must be installed prior to  
operation. Basic installation steps are as follows:  
1. Locate all venting components from the installation kit  
and carton.  
You must install a propane orifice to  
operate the outdoor boiler on propane  
gas. Verify when installing that the orifice  
size marking matches boiler size (Table  
2A).  
2. Before connecting the flue pipe sections or components,  
verify the gasket is seated evenly inside the groove in the  
female end of the elbow and flue adapter.  
3. Remove the kit provided screws from the air cover and  
use them to install the wall strap.  
1. Remove the top and front access covers from the unit  
(tools required for removal).  
4. Insert the elbow into the flue adapter.  
2. Remove the three screws securing the gas valve to the  
venturi (FIG. 2-3).  
Do not use grease or other lubricant  
on the vent seals. Only water may be  
ƽ CAUTION  
3. Locate the propane orifice disk from the conversion kit  
bag. Verify that the stamping on the orifice disk matches  
the boiler size (see Table 2A).  
used for this purpose. Grease or other  
lubricant can make the seal brittle or it  
can result in tears in the surface of the  
seal, this will result in flue gas leakage.  
Place the orifice into the black rubber grommet in the  
side of the gas valve and secure in the valve (FIG. 2-3).  
4. Reposition the gas valve against the venturi and replace  
the screws (FIG. 2-3) securing the valve to the venturi.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
2 Prepare boiler  
(continued)  
5. After installation is complete, attach the propane  
conversion label (in the conversion kit bag) next to the  
boiler rating plate. Attach the LP caution label (in the  
conversion kit bag) to the left side of the unit in the  
lower left corner.  
Leveling the boiler  
1. Set the boiler in place and check level.  
a) Adjust legs if necessary to level boiler, see FIG. 2-4  
below.  
Figure 2-4 Leveling Legs on the Boiler  
6. Replace the top and front access covers.  
Table 2A LP Conversion Table  
LP Conversion Table  
Model  
LP Orifice Stamping  
151  
211  
286  
150  
210 / W150  
285  
After converting to LP, check combustion  
per the Start-up procedure in Section  
7 of this manual. Failure to check and  
verify combustion could result in severe  
personal injury, death, or substantial  
property damage.  
ƽ WARNING  
Figure 2-3 Installing Propane Orifice  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
3 Hydronic piping  
System water piping methods  
General piping information  
The outdoor boiler is designed to function in a closed loop Basic steps are listed in this section along with illustrations on  
pressurized system not less than 12 psi. A temperature and the following pages (FIG.’s 3-4 thru 3-10), which will guide you  
pressure gauge is included to monitor system pressure and through the installation of the outdoor boiler (reference FIG.’s  
outlet temperature and should be located on the boiler outlet. 3-2A and 3-2B).  
It is important to note that the boiler has a minimal 1. Connect the system return marked “Inlet”.  
amount of pressure drop and must be figured in when  
2. Connect the system supply marked “Outlet”.  
sizing the circulators. Each boiler installation must have  
3. Install purge and balance valve or shutoff valve and drain  
an air elimination device, which will remove air from  
on system return to purge air out of each zone.  
the system. Install the boiler so the gas ignition system  
4. Install a backflow preventer on the cold feed make-up water  
components are protected from water (dripping, spraying,  
etc.) during appliance operation for basic service of circulator  
line.  
replacement, valves, and others.  
5. Install a pressure reducing valve on the cold feed make-  
up water line, (15 psi nominal). Check temperature and  
pressure gauge (shipped separately), which should read a  
minimum pressure of 12 psi.  
Observe a minimum of 1/4 inch (6 mm) clearance around all  
un-insulated hot water pipes when openings around the  
pipes are not protected by non-combustible materials.  
6. Install a circulator as shown on the piping diagrams in this  
section. Make sure the circulator is properly sized for the  
system and friction loss.  
Low water cutoff device  
On a boiler installed above radiation level, some states and  
local codes require a low water cutoff device at the time of  
installation.  
7. Consult the factory for a pump and/or pump cover. If a  
field-supplied pump is used, install per the manufacturer’s  
specifications in regard to indoor or outdoor location. An  
outdoor rated pump is recommended.  
Chilled water system  
If the boiler supplies hot water to heating coils in air handler  
units, flow control valves or other devices must be installed to  
prevent gravity circulation of heater water in the coils during  
the cooling cycle. A chilled water medium must be piped in  
parallel with the heater.  
8. Install an expansion tank on the system supply. Consult the  
tank manufacturer’s instruction for specific information  
relating to tank installation. Size the expansion tank for the  
required system volume and capacity.  
9. Install an air elimination device on the system supply.  
Freeze protection, heat exchanger  
10. Install a drain valve at the lowest point of the system.  
Note: The boiler cannot be drained completely of water  
without purging the unit with an air pressure of 15 psi.  
Freeze protection for new or existing systems must use glycol  
that is specially formulated for this purpose. This includes  
inhibitors, which prevent the glycol from attacking the  
metallic system components. Make certain to check that  
the system fluid is correct for the glycol concentration and  
inhibitor level. The system should be tested at least once  
a year and as recommended by the producer of the glycol  
solution. Allowance should be made for the expansion of the  
glycol solution in the system piping.  
11. This appliance is supplied with a relief valve sized in  
accordance with ASME Boiler and Pressure Vessel Code,  
Section IV (“Heating Boilers”). Pipe the discharge of the  
safety relief valve to prevent injury in the event of pressure  
relief. Provide piping that is the same size as the safety relief  
valve outlet. Never block the outlet of the safety relief valve.  
Use only inhibited propylene glycol  
ƽ WARNING  
solutions, which are specifically formulated  
for hydronic systems. Ethylene glycol is  
toxic and can attack gaskets and seals used  
in hydronic systems.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12  
Outdoor Knight Boiler Installation & Operation Manual  
3 Hydronic piping  
(continued)  
The relief valve, tee and any necessary fittings  
are shipped in the install kit with the boiler  
and are to be field installed (FIG. 3-1).  
Near boiler piping components  
ƽ WARNING  
1. Boiler system piping:  
Boiler system piping MUST be sized per the pipe  
requirements listed in Table 3A. Reducing the pipe size  
can restrict the flow rate through the boiler, causing  
inadvertent high limit shutdowns and poor system  
performance. Flow rates are based on 20 feet of piping,  
4 - 90° elbows, and 2 - fully ported ball valves.  
*See the piping illustrations included in this section, FIG.’s 3-4  
thru 3-10 for suggested guidelines in piping the outdoor boiler  
with either zone valves or circulator pumps.  
*Please note that these illustrations are  
NOTICE  
meant to show system piping concept only,  
2. Boiler system pump w/pump cover:  
the installer is responsible for all equipment  
and detailing required by local codes.  
A Grundfos UPS26-99F pump and pump cover will be  
provided by the factory (for standard altitude models) as  
the boiler circulation pump based on 20 feet of piping,  
4 - 90° elbows, and 2 - fully ported ball valves.  
The outdoor boiler is capable of servicing  
multiple temperature loop systems. It is the  
CAUTION  
responsibility of the installer to protect the  
loops with lower temperature requirements  
from higher temperatures that may be  
required by other loops.  
Outdoor boilers are capable of controlling  
a
variable speed boiler circulator. Variable speed circulators  
MUST be sized to meet the specified minimum flow  
requirements listed in FIG. 3-3 on page 15 at full  
speed.  
Relief valve and temperature and pressure  
gauge installation  
Basic steps are listed below to guide you through the installation  
of the relief valve and the temperature and pressure (T & P)  
gauge provided with the unit.  
3. Domestic hot water circulating pump:  
Field supplied. The pump MUST be sized to meet  
the specified minimum flow requirements listed in  
FIG. 3-3. Consult the indirect water heater operating  
guide to determine flow characteristics for the selected  
product used.  
1. Install the tee with the 3/4 inch fitting positioned  
vertically and on the top as shown in FIG. 3-1.  
2. Install the relief valve into the 3/4 inch fitting of the tee  
installed in Step 1 (FIG. 3-1).  
3. Install a field provided 5 inch long nipple and tee with the  
fitting positioned vertically on the top on the  
downstream side of the relief valve (see FIG. 3-1).  
4. Install the temperature and pressure gauge provided with  
the unit into the top fitting of the tee (a bushing may be  
necessary) installed in Step 3 (FIG. 3-1).  
4. Boiler isolation valves:  
Field supplied. Full port ball valves are required.  
Failure to use full port ball valves could result in a  
restricted flow rate through the boiler.  
5. Check valves:  
Field supplied. Check valves are recommended for  
installation as shown in FIG.’s 3-4 thru 3-10. Failure to  
install check valves could result in a reverse flow  
condition during pump(s) off cycle.  
6. Domestic indirect hot water isolation valves:  
Field supplied. Full port ball valves are required. Failure  
to use full port ball valves could result in a restricted flow  
rate through the boiler.  
Figure 3-1 Relief Valve / T & P Installation  
7. Anti-scald mixing valve:  
Field supplied.  
An anti-scald mixing valve is  
recommended when storing domestic hot water above  
115°F.  
8. Unions:  
Field supplied. Recommended for unit serviceability.  
9. Temperature and pressure gauge:  
Factory supplied. The temperature and pressure gauge is  
shipped loose. It is the responsibility of the contractor to  
install the temperature and pressure gauge on the boiler  
water outlet.  
RELIEF VALVE  
TEMPERATURE &  
PRESSURE GAUGE  
TEE W/FITTING ON TOP  
(FIELD PROVIDED)  
10. Pressure relief valve:  
Factory supplied. The pressure relief valve is sized to  
ASME specifications.  
11. Boiler purge valve:  
CLOSE NIPPLE  
(FIELD PROVIDED)  
IMG00369  
TEE WITH 3/4" FITTING  
Field supplied. The boiler purge valve is used to  
remove entrapped air from the heat exchanger during  
start-up.  
ON TOP  
CLOSE NIPPLE  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
3 Hydronic piping  
12. System temperature sensor:  
Lochinvar offers the Squire which is a series of indirect  
water heaters. The Squire features a stainless steel vessel  
with a single wall stainless steel heat exchanger.  
Lochinvar supplies  
a
system temperature sensor.  
The sensor is to be installed in the heating loop  
downstream from the boiler hot water piping and  
heating loop junction. Typically the sensor will be  
located far enough downstream to sense system diluted  
water temperature.  
It is up to the installer to ensure the  
minimum system flow is not less than the  
CAUTION  
minimum boiler flow at any time.  
13. Indirect water heaters:  
The National Standard Plumbing Code  
ƽ WARNING  
The outdoor boiler may be piped to an indirect  
water heater to heat domestic hot water with the space heat  
transfer medium. As depicted on pages 17 through 23  
there are two options when utilizing an indirect water  
heater.  
and the Uniform Plumbing Code limit the  
pressure of the heat transfer fluid to less  
than the minimum working pressure of the  
potable water system up to 30 psi maximum.  
Also, the heat transfer fluid must be water  
or other non-toxic fluid having a toxicity of  
Class 1, as listed in Clinical Toxicology of  
Commercial Products, 5th Edition.  
A. The space heating piping will branch off to flow the  
space heat transfer medium through a single wall  
heat exchanger coil inside the indirect water heater.  
B. The indirect water heater is connected to the system  
14. Y-Strainer:  
supply piping.  
A
pump controlled by the  
Field supplied. A Y-strainer or equivalent multipurpose  
strainer is recommended at the inlet of the heat exchanger  
to remove system particles from older hydronic systems and  
protect newer systems.  
outdoor boiler’s control will regulate the flow of  
water through the indirect water heater. The indirect  
water heater’s temperature will be regulated by the  
outdoor boiler’s control.  
Circulator sizing  
The outdoor boiler is pre-configured to control the  
operation of the DHW pump with Domestic Hot Water  
Prioritization programming. The DHW programming is  
designed to control and balance the space heating  
demand by switching between DHW and space heating.  
The outdoor boiler heat exchanger does have a pressure drop,  
which must be considered in your system design. Refer to the  
graph in FIG. 3-3 for pressure drop through the outdoor boiler  
heat exchanger.  
Near boiler piping connections  
Figure 3-2A Near Boiler Piping w/Y-Strainer  
Figure 3-2B Near Boiler Piping w/Low Loss Header  
SYSTEM SENSOR  
AIR VENT VALVE  
AIR SEPARATOR  
LOW LOSS HEADER  
(TYPICAL)  
FILL VALVE  
Y-STRAINER  
(RECOMMENDED)  
DRAIN  
DOMESTIC HOT  
WATER PUMP  
(TYPICAL)  
EXPANSION TANK  
DRAIN VALVE  
SYSTEM  
PUMP  
BOILER  
PUMP  
INDIRECT  
DOMESTIC  
HOT WATER  
TANK  
INDIRECT  
DOMESTIC  
HOT WATER  
Y-STRAINER  
(RECOMMENDED)  
BOLIER PUMP  
DRAIN  
(TYPICAL)  
IMG00377  
TO FLOOR  
DRAIN  
IMG00378  
TO FLOOR  
DRAIN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14  
Outdoor Knight Boiler Installation & Operation Manual  
3 Hydronic piping  
(continued)  
Figure 3-3 Pressure Drop vs. Flow  
Pressure Drop vs. Flow (Includes Secondary Piping)  
25  
20  
15  
10  
5
151  
211  
286  
0
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25  
Flow Rate (GPM)  
Table 3A Circulator Recommendations for Temperature Rise Applications_20°, 25°, and 35°  
20°F Temperature Rise Applications  
Pump  
TACO  
0011  
Minimum Pipe  
Size  
Model  
GPM  
FT/HD  
Grundfos  
UPS26-99F  
UPS32-160  
UPS32-80  
B & G  
NRF-36  
PL-55  
Armstrong  
151  
211  
286  
14  
20  
27  
20  
29  
15  
1"  
1"  
1-1/4"  
E7  
1400-50  
1400-20  
E9*  
E11  
PL-36  
These pumps are only slightly above 20° rise flows, but are the closest available. To reach a 20° rise or less, an  
upsized pump will be required.  
*NOTICE  
25°F Temperature Rise Applications  
Pump  
Minimum Pipe  
Size  
Model  
GPM  
FT/HD  
Grundfos  
TACO  
B & G  
Armstrong  
151  
211  
286  
11  
16  
21  
13  
19  
12  
1"  
1"  
1-1/4"  
UPS26-99F  
UPS26-99F  
UPS26-99F  
0014  
0013  
0011  
NRF-36  
NRF-36  
NRF-36  
E7  
E7  
E7  
35°F Temperature Rise Applications  
Pump  
TACO  
008/0010  
0010  
008/0010  
Minimum Pipe  
Model  
GPM  
FT/HD  
Size  
Grundfos  
UPS15-58FC  
UPS15-58FC  
UP26-64F  
B & G  
NRF-36  
NRF-36  
NRF-36  
Armstrong  
Astro-30  
Astro-50  
E7  
151  
211  
286  
8
10  
9
7
1"  
1"  
1-1/4"  
11  
15  
Pumps listed in bold type are provided by the factory as the boiler circulation pump on standard altitude  
models.  
NOTICE  
Pumps listed in italicized type are provided by the factory as the boiler circulation pump on high altitude  
models.  
NOTICE  
NOTICE  
The temperature rise provided by a pump/model combination will decrease by 3% per 1000 feet of elevation.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
3 Hydronic piping  
Variable speed pump option  
Table 3B Recommended Variable Speed Pumps  
Minimum Temperature Rise*  
Pump  
Model  
Grundfos  
TACO  
Wilo  
UP26-96 FC/VS  
0013 IFC VS  
Stratos 1.25 3 x 30  
151  
211  
286  
21  
27  
27  
20  
25  
24  
19  
24  
22  
*The minimum temperature rise is derived from the chart in FIG. 3-3 with the firing rate and pump speed at 100% as shown in  
the table above.  
The shaded regions of pump coverage are only available for applications with 230V (60 Hz) supply voltage, all others are  
to be 115V. (A field supplied relay is required to connect the 230V pump listed in the shaded area in Table 3B to the boiler  
high voltage terminal strip.)  
Variable speed pump setup  
Before operation, ensure the following:  
- Pump is set for an input signal of 0 - 10Vdc by the dip switches on the pump control  
- Pump is set for external signal control (if applicable)  
- Pump is set for linear output (if applicable)  
- If pump does not come equipped with a 0 - 10 Vdc input option, an optional module  
will be required from the vendor  
Pump sizing and flow requirements are  
NOTICE  
based on 20 feet of piping, 4 - 90°  
elbows, and 2 - fully ported ball valves.  
It is required that near boiler piping  
NOTICE  
systems utilize the Primary/Secondary  
configuration shown in FIG. 3-10 only.  
The use of other near boiler piping  
configurations could result in improper  
building and system flow rates leading to  
inadvertent boiler high limit shutdowns  
and poor system performance.  
SMART SYSTEM / Multi-temperature loop  
control option  
The outdoor boiler is capable of producing up to three (3) set  
point temperatures to meet different space heating demands.  
When using more than one temperature demand it is necessary  
to protect the lower temperature loop from overheating. To  
help aid with this protection, Lochinvar offers the Multi-  
Temperature Loop Control Board Kit (RLY30086).  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
3 Hydronic piping  
(continued)  
Figure 3-4 Single Boiler - Single Temperature Zoned with Circulators  
ZONE #1  
PRESSURE  
GAUGE  
PRESSURE  
ZONE #2 ZONE #3 ZONE #4  
REDUCING VALVE  
BACKFLOW  
PREVENTER  
FLOW CHECK  
VALVE  
(TYPICAL)  
MAKE UP WATER  
SYSTEM SUPPLY  
SENSOR  
ZONE CIRCULATORS  
(TYPICAL)  
(WHEN USED)  
AIR SEPARATOR  
EXPANSION  
TANK  
MAY SUBSTITUTE LOW LOSS HEADER  
BALL VALVE  
(TYPICAL)  
Y-STRAINER  
DRAIN POINT  
(TYPICAL)  
(RECOMMENDED)  
BOILER  
HOT  
WATER  
OUT  
CIRCULATOR  
DOMESTIC  
HOT WATER  
CIRCULATOR  
ANTI-SCALD  
MIXING VALVE  
COLD  
WATER  
IN  
UNION  
(TYPICAL)  
TEMPERATURE /  
PRESSURE  
GAUGE  
DRAIN  
INDIRECT  
DHW TANK  
BOILER  
IMG00370  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
NOTICE  
17  
Indoor tank shown for illustration purposes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
3 Hydronic piping  
Figure 3-5 Multiple Boilers - Single Temperature Zoned with Circulators  
Number of Units  
Model  
2
3
4
5
6
7
8
Required Pipe Sizes  
151  
211  
2"  
2"  
2-1/2" 2-1/2"  
3"  
3"  
4"  
4"  
3-1/2"  
4"  
5"  
2" 2-1/2"  
3"  
3"  
3"  
3-1/2"  
286 2-1/2" 2-1/2"  
3-1/2" 3-1/2"  
ZONE #1  
PRESSURE  
REDUCING VALVE  
PRESSURE  
GAUGE  
ZONE #4  
ZONE #2 ZONE #3  
BACKFLOW  
PREVENTER  
FLOW CHECK  
VALVE  
SYSTEM SUPPLY  
SENSOR  
MAKE UP WATER  
(TYPICAL)  
AIR SEPARATOR  
ZONE CIRCULATORS  
(TYPICAL)  
EXPANSION  
TANK  
MAY SUBSTITUTE  
LOW LOSS HEADER  
BALL VALVE  
(TYPICAL)  
DRAIN POINT  
(TYPICAL)  
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART  
HOT  
WATER  
OUT  
ANTI-SCALD  
MIXING VALVE  
BOILER  
CIRCULATOR  
DOMESTIC  
HOT WATER  
CIRCULATOR  
COLD  
WATER  
IN  
Y-STRAINER  
(RECOMMENDED)  
(TYPICAL)  
UNION  
TEMPERATURE /  
(TYPICAL)  
PRESSURE  
GAUGE  
DRAIN  
BOILER 1  
BOILER 2  
INDIRECT  
(LEADER)  
(MEMBER 1)  
DHW TANK  
IMG00371  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
NOTICE  
Indoor tank shown for illustration purposes.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
3 Hydronic piping  
(continued)  
Figure 3-6 Single Boiler - Multiple Temperatures  
PRESSURE  
TEMPERATURE  
LOOP #1  
TEMPERATURE  
LOOP #2  
TEMPERATURE  
LOOP #3  
REDUCING VALVE  
WIRES TO  
LOOP SENSORS  
BACKFLOW  
PREVENTER  
PRESSURE  
GAUGE  
MAKE  
UP  
SYSTEM  
WATER  
MIXING VALVES  
(TYPICAL)  
SUPPLY  
SENSOR  
AIR SEPARATOR  
EXPANSION  
TANK  
MAY SUBSTITUTE  
LOW LOSS HEADER  
NOT TO EXCEED 4 PIPE DIA  
OR MAX. OF 12" APART  
120VAC TO PUMPS  
BALL VALVE  
(TYPICAL)  
24V SIGNALTO  
MIXING VALVES  
Y-STRAINER  
(RECOMMENDED)  
DRAIN POINT  
(TYPICAL)  
MULTI-TEMP  
BOILER  
LOOP CONTROL  
CIRCULATOR  
DOMESTIC  
FLOW CHECK  
VALVE  
HOT WATER  
CIRCULATOR  
ANTI-SCALD  
HOT WATER  
OUT  
MIXING VALVE  
COLD  
WATER  
IN  
SHIELDED CABLE TO  
BOILER CONTROL  
UNION  
(TYPICAL)  
TEMPERATURE /  
PRESSURE DRAIN  
GAUGE  
BOILER  
Mixing valves are required for the protection of low temperature loops.  
IMG00372  
CAUTION  
NOTICE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
Indoor tank shown for illustration purposes.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
3 Hydronic piping  
Figure 3-7 Multiple Boilers - Multiple Temperatures  
Number of Units  
Model  
2
3
4
5
6
7
8
Required Pipe Sizes  
151  
211  
2"  
2"  
2-1/2" 2-1/2"  
3"  
3"  
4"  
4"  
3-1/2"  
4"  
5"  
2" 2-1/2"  
3"  
3"  
3"  
3-1/2"  
286 2-1/2" 2-1/2"  
3-1/2" 3-1/2"  
WIRES TO  
LOOP  
SENSORS  
PRESSURE  
TEMPERATURE  
LOOP #1  
TEMPERATURE  
LOOP #2  
TEMPERATURE  
LOOP #3  
REDUCING VALVE  
BACKFLOW  
PREVENTER  
MIXING VALVES  
(TYPICAL)  
PRESSURE  
GAUGE  
SYSTEM  
MAKE  
UP  
SUPPLY  
SENSOR  
WATER  
AIR SEPARATOR  
EXPANSION  
TANK  
24V  
SIGNAL  
TO MIXING  
VALVES  
MAY SUBSTITUTE  
LOW LOSS HEADER  
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART  
120VAC TO PUMPS  
BALL VALVE  
(TYPICAL)  
DRAIN POINT  
(TYPICAL)  
MULTI-TEMP  
LOOP CONTROL  
(OPTIONAL)  
BOILER  
CIRCULATOR  
SHIELDED CABLE TO  
BOILER CONTROL  
DOMESTIC  
HOT WATER  
CIRCULATOR  
FLOW CHECK  
VALVE  
HOT  
ANTI-SCALD  
WATER  
OUT  
MIXING  
VALVE  
Y-STRAINER  
COLD  
WATER  
IN  
(RECOMMENDED)  
TEMPERATURE /  
PRESSURE  
GAUGE  
UNION  
BOILER  
BOILER  
INDIRECT  
DHW TANK  
(TYPICAL)  
DRAIN  
IMG00373  
Mixing valves are required for the protection of low temperature loops.  
CAUTION  
NOTICE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
Indoor tank shown for illustration purposes.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
3 Hydronic piping  
(continued)  
Figure 3-8 Single Boiler - Multiple Temperatures with DHW Piped as a Zone  
PRESSURE  
WIRES TO  
LOOP  
TEMPERATURE  
LOOP #1  
TEMPERATURE  
TEMPERATURE  
LOOP #3  
REDUCING VALVE  
LOOP #2  
BACKFLOW  
PREVENTER  
SENSORS  
PRESSURE  
GAUGE  
MAKE  
UP  
MIXING VALVES  
(TYPICAL)  
WATER  
SYSTEM  
SUPPLY  
SENSOR  
AIR SEPARATOR  
EXPANSION  
TANK  
MAY SUBSTITUTE  
LOW LOSS HEADER  
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART  
BALL VALVE  
(TYPICAL)  
24V SIGNAL TO  
MIXING VALVES  
120VAC TO PUMPS  
DRAIN POINT  
(TYPICAL)  
MULTI-TEMP TO  
DOMESTIC  
LOOP CONTROL  
HOT WATER  
CIRCULATOR  
Y-STRAINER  
(RECOMMENDED)  
SHIELDED CABLE TO  
BOILER CONTROL  
FLOW  
CHECK  
VALVE  
ANTI-SCALD  
HOT WATER  
MIXING VALVE  
OUT  
BOILER  
CIRCULATOR  
COLD  
WATER  
IN  
PRESSURE  
RELIEF  
VALVE  
TEMPERATURE /  
PRESSURE GAUGE  
UNION  
DRAIN  
(TYPICAL)  
BOILER  
BOILER  
INDIRECT  
DHW TANK  
IMG00374  
Mixing valves are required for the protection of low temperature loops.  
CAUTION  
NOTICE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
Indoor tank shown for illustration purposes.  
Please note that the installer is responsible for ensuring DHW prioritization when piped as a zone.  
NOTICE  
Indoor tank shown for illustration purposes.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
3 Hydronic piping  
Figure 3-9 Multiple Boilers - Single Temperature Zoned with Valves  
Number of Units  
Model  
2
3
4
5
6
7
8
Required Pipe Sizes  
151  
211  
2"  
2"  
2-1/2" 2-1/2"  
3"  
3"  
4"  
4"  
3-1/2"  
4"  
5"  
2" 2-1/2"  
3"  
3"  
3"  
3-1/2"  
ZONE #1  
286 2-1/2" 2-1/2"  
3-1/2" 3-1/2"  
PRESSURE  
REDUCING VALVE  
ZONE #2  
BACKFLOW  
PREVENTER  
ZONE #3 ZONE #4  
PRESSURE  
GAUGE  
BALL VALVE  
(TYPICAL)  
ZONE VALVES  
(TYPICAL)  
SYSTEM SUPPLY  
MAKE UP WATER  
DIFFERENTIAL  
SENSOR  
PRESSURE BYPASS  
VALVE (IF USED)  
(WHEN USED)  
AIR SEPARATOR  
SYSTEM  
CIRCULATOR  
EXPANSION  
TANK  
MAY SUBSTITUTE LOW LOSS HEADER  
DRAIN POINT  
(TYPICAL)  
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART  
ANTI-SCALD  
HOT  
WATER  
OUT  
MIXING VALVE  
BOILER  
CIRCULATOR  
DOMESTIC  
HOT WATER  
CIRCULATOR  
COLD  
WATER  
IN  
Y-STRAINER  
(RECOMMENDED)  
(TYPICAL)  
UNION  
TEMPERATURE /  
PRESSURE  
GAUGE  
(TYPICAL)  
DRAIN  
BOILER 2  
BOILER 1  
(LEADER)  
INDIRECT  
(MEMBER 1)  
DHW TANK  
IMG00375  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
NOTICE  
Indoor tank shown for illustration purposes.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
3 Hydronic piping  
(continued)  
Figure 3-10 Multiple Boilers - Non-Zoned Primary/Secondary Piping  
Number of Units  
Model  
2
3
4
5
6
7
8
Required Pipe Sizes  
151  
211  
2"  
2"  
2-1/2" 2-1/2"  
3"  
3"  
4"  
4"  
3-1/2"  
4"  
5"  
2" 2-1/2"  
3"  
3"  
3"  
3-1/2"  
286 2-1/2" 2-1/2"  
3-1/2" 3-1/2"  
PRESSURE  
REDUCING VALVE  
PRESSURE  
GAUGE  
BACKFLOW  
PREVENTER  
MAKE UP WATER  
SYSTEM SUPPLY  
SENSOR  
SYSTEM  
AIR SEPARATOR  
MAY SUBSTITUTE LOW LOSS HEADER  
CIRCULATOR  
TO  
FROM  
SYSTEM  
SYSTEM  
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART  
BALL VALVE  
(TYPICAL)  
EXPANSION  
TANK  
DRAIN POINT  
(TYPICAL)  
Y-STRAINER  
(RECOMMENDED)  
(TYPICAL)  
HOT  
ANTI-SCALD  
WATER  
MIXING VALVE  
OUT  
DOMESTIC  
HOT WATER  
COLD WATER  
IN  
CIRCULATOR  
BOILER  
CIRCULATOR  
TEMPERATURE /  
PRESSURE  
GAUGE  
DRAIN  
UNION  
(TYPICAL)  
BOILER 4  
BOILER 3  
BOILER 1  
(LEADER)  
BOILER 2  
(MEMBER 1)  
INDIRECT  
(MEMBER 3)  
(MEMBER 2)  
DHW TANK  
IMG00376  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
NOTICE  
Indoor tank shown for illustration purposes.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
4 Gas connections  
4. Purge all air from the gas supply piping.  
Connecting gas supply piping  
1. Remove the top access cover and refer to FIG. 4-1 to pipe  
gas to the boiler.  
5. Before placing the boiler in operation, check the boiler  
and its gas connection for leaks.  
a. Install ground joint union for servicing, when  
required.  
b. Install a manual shutoff valve in the gas supply  
piping outside boiler jacket when required by local  
codes or utility requirements.  
a. The appliance must be disconnected from the gas  
supply piping system during any pressure testing of  
that system at a test pressure in excess of 1/2 PSIG  
(3.5 kPa).  
b. The appliance must be isolated from the gas supply  
piping system by closing a manual shutoff valve  
during any pressure testing of the gas supply piping  
system at test pressures equal to or less than 1/2 PSIG  
(3.5 kPa).  
2. Install sediment trap / drip leg.  
Figure 4-1 Gas Supply Piping  
c. The appliance and its gas connection must be leak  
tested before placing it in operation.  
Do not check for gas leaks with an open  
ƽ WARNING  
UNION  
flame – use the bubble test. Failure to  
use the bubble test or check for gas leaks  
can cause severe personal injury, death, or  
substantial property damage.  
GAS SUPPLY  
6. Use pipe sealing compound compatible with propane  
gases. Apply sparingly only to male threads of the pipe  
joints so that pipe dope does not block gas flow.  
Failure to apply pipe sealing compound as  
ƽ WARNING  
DRIP  
LEG  
detailed in this manual can result in severe  
personal injury, death, or substantial  
property damage.  
MANUAL  
SHUTOFF VALVE  
(FIELD SUPPLIED)  
Outdoor boilers are typically shipped  
ƽ WARNING  
ready to fire on natural gas. Check boiler  
rating plate to determine which fuel the  
boiler is set for. If set to natural gas, it may  
be converted to LP by installing an orifice  
(see page 11). In order to operate on LP  
gas, an orifice MUST BE installed. Failure  
to comply could result in severe personal  
injury, death, or substantial property  
damage.  
IMG00383  
3. Support piping with hangers, not by the boiler or its  
accessories.  
The gas valve and blower will not support  
the weight of the piping. Do not attempt  
ƽ WARNING  
to support the weight of the piping with  
the boiler or its accessories. Failure to  
comply could result in severe personal  
injury, death, or substantial property  
damage.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
4 Gas connections  
(continued)  
Use two wrenches when tightening gas  
piping at boiler (FIG. 4-2), using one  
wrench to prevent the boiler gas line  
connection from turning. Failure to  
support the boiler gas connection pipe to  
prevent it from turning could damage gas  
line components.  
Natural gas:  
ƽ WARNING  
Pipe sizing for natural gas  
1. Refer to Table 4A for pipe length and diameter. Based on  
rated boiler input (divide by 1,000 to obtain cubic feet per  
hour).  
a. Table 4A is only for natural gas with specific gravity  
0.60 inches, with a pressure drop through the gas  
piping of 0.5 inches w.c.  
Figure 4-2 Inlet Pipe with Backup Wrench  
b. For additional gas pipe sizing information, refer to  
ANSI Z223.1 (or B149.1 for Canadian installations).  
Natural gas supply pressure requirements  
1. Pressure required at the gas valve inlet pressure port:  
• Maximum 14 inches w.c. with no flow (lockup) or  
with boiler on.  
• Minimum 4 inches w.c. with gas flowing (verify during  
boiler startup).  
2. Install 100% lockup gas pressure regulator in supply line if  
inlet pressure can exceed 14 inches w.c. at any time. Adjust  
lockup regulator for 14 inches w.c. maximum.  
Propane Gas:  
Outdoor boilers are typically shipped ready  
to fire on natural gas. Check boiler rating  
ƽ WARNING  
plate to determine which fuel the boiler is set  
for. If set to natural gas, it may be converted  
to LP by installing an orifice (see page 11).  
In order to operate on LP gas, an orifice  
MUST BE installed. Failure to comply  
could result in severe personal injury, death,  
or substantial property damage.  
IMG00384  
USE BACKUP WRENCH  
TO PREVENT PIPE FROM  
ROTATING  
Maximum inlet gas pressure must not  
NOTICE  
exceed the value specified. Minimum  
value listed is for the purposes of input  
adjustment.  
Pipe sizing for propane gas  
1. Contact gas supplier to size pipes, tanks, and 100% lockup  
gas pressure regulator.  
Propane Supply Pressure Requirements  
1. Adjust propane supply regulator provided by the gas  
supplier for 14 inches w.c. maximum pressure.  
2. Pressure required at gas valve inlet pressure port:  
• Maximum 14 inches w.c. with no flow (lockup) or with  
boiler on.  
• Minimum 8 inches w.c. with gas flowing (verify during  
boiler startup).  
Ensure that the high gas pressure regulator  
is at least 6 - 10 feet upstream of the  
appliance.  
ƽ WARNING  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
4 Gas connections  
Table 4A Natural Gas Pipe Size Chart  
Single Unit  
Natural Gas Pipe Capacity Chart  
Length of Pipe in Straight Feet for 1/2 PSI  
Nominal  
Iron Pipe  
Size (Inches)  
10  
20  
30  
97  
40  
50  
60  
70  
80  
90  
100  
125  
150  
N/A  
175 200  
N/A N/A  
175  
120  
82  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
1/2  
3/4  
1
369  
697  
256  
477  
974  
205  
384  
789  
174  
328  
677  
155  
292  
595  
923  
141  
267  
543  
830  
128  
246  
502  
769  
121  
236  
472  
707  
113  
210  
441  
666  
106  
200  
410  
636  
95  
86  
79  
74  
179  
369  
564  
164  
333  
513  
974  
149 138  
308 287  
472 441  
871 820  
1400  
1-1/4  
1-1/2  
2
2150 1500 1210 1020  
4100 2820 2260 1950 1720 1560 1440 1330 1250 1180 1100  
6460 4460 3610 3100 2720 2460 2310 2100 2000 1900 1700 1540 1400 1300  
11200 7900 6400 5400 4870 4410 4000 3800 3540 3330 3000 2720 2500 2340  
23500 16100 13100 11100 10000 9000 8300 7690 7380 6870 6150 5640 5130 4720  
Outdoor boilers are typically shipped ready to fire on natural gas. Check boiler rating plate to determine  
2-1/2  
3
4
ƽ WARNING  
which fuel the boiler is set for. If set to natural gas, it may be converted to LP by installing an orifice (see page  
11). In order to operate on LP gas, an orifice MUST BE installed. Failure to comply could result in severe  
personal injury, death, or substantial property damage.  
Check inlet gas supply  
3. Loosen the set screw one (1) full turn from inside the  
pressure tap on top of the gas valve. Place the tubing of  
the manometer over the tap once the set screw is  
loosened as shown in FIG. 4-3.  
CSA or UL listed flexible gas connections  
NOTICE  
are acceptable, but you must exercise  
caution to ensure that the line has adequate  
capacity to allow your boiler to fire at full  
rate. Consult with local codes for proper  
installation or service procedures.  
4. Slowly turn on the gas supply at the field installed  
manual gas valve.  
5. Turn the power switch to the “ON” position.  
DO NOT adjust gas valve outlet pressure.  
The gas valve is factory-set for the correct  
outlet pressure. This setting is suitable  
for natural gas and propane, requiring  
no field adjustment. Attempting to  
alter the gas valve outlet pressure could  
result in damage to the valve, causing  
potential severe personal injury, death, or  
substantial property damage.  
ƽ WARNING  
6. Adjust the temperature set point on the control panel of  
the SMART SYSTEM control module to call for heat.  
7. Observe the gas supply pressure as the burner fires at  
100% of rated input. Percent of burner input will be  
displayed on the control panel.  
8. Ensure inlet pressure is within specified range.  
Minimum and maximum gas supply pressures are  
specified in this section of the manual.  
9. If gas supply pressure is within normal range and no  
adjustments are needed, proceed on to Step 11.  
The gas piping must be sized for the proper flow and length  
of pipe, to avoid excessive pressure drop. Both the gas meter  
and the gas regulator must be properly sized for the total gas  
load.  
10. If the gas pressure is out of range, contact the gas utility,  
gas supplier, qualified installer or service agency to  
determine the necessary steps to provide proper gas  
pressure to the control.  
If you experience a pressure drop greater than 1 inch w.c.,  
the meter, regulator, or gas line is undersized or in need of  
service. Perform the steps below when checking inlet gas  
supply:  
11. Turn the power switch to the “OFF” position.  
12. Shut off the gas supply at the manual gas valve in the gas  
piping to the appliance.  
1. Turn the main power switch to the “OFF” position.  
13. Remove the manometer from the pressure tap on top of  
the gas valve. Re-tighten the set screw inside the pressure  
tap.  
2. Shut off gas supply at the manual gas valve in the gas  
piping to the appliance.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
4 Gas connections  
(continued)  
When re-tightening the set screw, be sure  
to tighten securely to prevent gas leaks.  
Gas Pressure  
ƽ WARNING  
The gas pressure must remain between 4 inches w.c. (natural),  
8 inches w.c. (LP) minimum and 14 inches w.c. (natural and  
LP) maximum during stand-by (static) mode and while in  
operating (dynamic) mode. If an in-line regulator is used, it  
must be a minimum of 10 feet from the outdoor boiler. It is  
very important that the gas line is properly purged by the gas  
supplier or utility company. Failure to properly purge the  
lines or improper line sizing, will result in ignition failure.  
Do not check for gas leaks with an open  
flame -- use the bubble test. Failure to  
use the bubble test or check for gas leaks  
can cause severe personal injury, death, or  
substantial property damage.  
14. Turn on the gas supply at the manual gas valve.  
15. Turn the power switch to the “ON” position.  
The problem is especially noticeable in NEW LP installations  
and also in empty tank situations. This can also occur when  
a utility company shuts off service to an area to provide  
maintenance to their lines.  
16. Adjust the temperature set point on the control panel of  
the SMART SYSTEM control module to the desired  
water temperature so the appliance will call for heat.  
17. Check burner performance by cycling the system while  
you observe burner response. The burner should ignite  
promptly. Flame pattern should be stable. Turn system  
off and allow burner to cool, then cycle burner again to  
ensure proper ignition and flame characteristics.  
Gas valve replacement  
The gas valve MUST NOT be replaced with a conventional  
gas valve under any circumstances. As an additional safety  
feature, this gas valve has a flanged connection to the venturi  
and blower.  
Figure 4-3 Inlet Gas Supply Check  
LOOSEN THE SET SCREW ONE (1) FULL TURN  
AND PLACE THE MANOMETER TUBING OVER  
THE PRESSURE TAP.  
Failure to follow all precautions could  
ƽ WARNING  
result in fire, explosion, or death!  
DO NOT adjust gas valve outlet pressure.  
ƽ WARNING  
The gas valve is factory-set for the correct  
outlet pressure. This setting is suitable  
for natural gas and propane, requiring  
no field adjustment. Attempting to  
alter the gas valve outlet pressure could  
result in damage to the valve, causing  
potential severe personal injury, death, or  
substantial property damage.  
DETAIL  
IMG00385  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
5 Field wiring  
ELECTRICAL SHOCK HAZARD – For  
your safety, turn off electrical power supply  
Label all wires prior to disconnection  
when servicing controls. Wiring errors  
can cause improper and dangerous  
operation.  
ƽ WARNING  
ƽ CAUTION  
before making any electrical connections  
to avoid possible electric shock hazard.  
Failure to do so can cause severe personal  
injury or death.  
Installation must comply with:  
1. National Electrical Code and any other national, state,  
provincial, or local codes, or regulations.  
Wiring must be N.E.C. Class 1.  
NOTICE  
If original wiring as supplied with boiler  
must be replaced, use only type 105°C wire  
or equivalent.  
Line voltage connections  
Boiler must be electrically grounded as  
required by National Electrical Code ANSI/  
NFPA 70 – latest edition.  
1. Connect 120 vac power wiring to the line voltage terminal  
strip in the junction box, as shown in FIG. 5-1.  
All wiring exterior to the appliance must be  
enclosed in approved conduit.  
2. Provide and install a fused disconnect or service switch  
(15 amp recommended) as required by the code (see  
FIG. 5-1).  
In accordance with Section 303 of the 2007  
Energy Act, this boiler is equipped with a  
feature that saves energy by reducing the  
boiler water temperature as the heating  
load decreases. This feature is equipped  
with an override, which is provided  
primarily to permit the use of an external  
energy management system that serves the  
same function. This override MUST NOT  
be used unless at least one of the following  
conditions is true:  
1. An external energy management  
system is installed that reduces the  
boiler water temperature as the heating  
load decreases.  
2. This boiler is not used for any space  
heating.  
NOTICE  
3. The boiler pump is shipped loose. Wire the boiler pump  
as shown in FIG. 5-1.  
4. When connecting a domestic hot water (DHW) pump,  
connect the wiring to the line voltage terminal strip as  
shown in FIG. 5-1.  
5. To activate a system pump, wire as shown in FIG. 5-1.  
If the motor is larger than 1/8 hp or 1.8 amps, you must  
isolate with a relay.  
Low voltage connections  
1. Route all low voltage wires through the knockouts in the  
rear of the boiler, as shown in FIG. 5-2.  
3. This boiler is part of a modular or  
multiple boiler system having a total  
input of 300,000 Btu/hr or greater.  
4. This boiler is equipped with a tankless  
coil.  
2. Connect low voltage wiring to low voltage connection  
board as shown in FIG. 5-3 on page 31 of this manual and  
the boiler wiring diagram.  
Figure 5-2 Routing Field Wiring  
LOW VOLTAGE  
CONNECTION  
BOARD  
Figure 5-1 Line Voltage Field Wiring Connections  
LOW VOLTAGE  
WIRING  
KNOCKOUTS  
LINE VOLTAGE  
WIRING KNOCKOUTS  
IMG00386  
Download from Www.Somanuals.com. All Manuals Search And Download.  
28  
Outdoor Knight Boiler Installation & Operation Manual  
5 Field wiring  
1. Connect the room thermostats or end switches (isolated  
contact only) to Heat/Loop Demand 1, 2, or 3, as shown  
in FIG. 5-3.  
(continued)  
Thermostat  
High gas pressure switch  
If a switch is provided to detect excessive gas pressure, remove  
the jumper wire from the terminals on the connection board,  
and then connect them to its normally closed contacts (FIG.  
2. Install the thermostat on the inside wall away from 5-3).  
influences of drafts, hot or cold water pipes, lighting  
Low gas pressure switch  
1. If a switch is provided to detect low gas pressure, remove the  
jumper wire from the terminals on the connection board  
and connect them to its normally open contacts (FIG. 5-3).  
fixtures, television, sunlight, or fireplaces.  
3. Thermostat anticipator (if applicable):  
a. If connected directly to boiler, set for 0.1 amps.  
b. If connected to relays or other devices, set to match  
total electrical power requirements of connected  
devices. See device manufacturers’ specifications  
and thermostat instructions for details.  
2. If both a high and low gas pressure switch is used, connect  
their respective contacts in series, and connect them to the  
terminals on the connection board (FIG. 5-3).  
Outdoor temperature sensor  
Variable speed system pump  
In the absence of an external energy management system, an  
outdoor temperature sensor must be used.  
If a variable speed pump is used in the primary loop, and a  
0-10V signal is available from the pump speed control, this  
signal can be used by the SMART SYSTEM control to anticipate  
changes in the building heat load. By connecting this 0 - 10V  
signal to the 0 - 10V SYS PUMP IN terminals, the boiler (or  
cascade) can modulate up and down as the primary flow  
increases and decreases.  
1. Mount the sensor on an exterior wall, shielded from  
direct sunlight or flow of heat or cooling from other  
sources.  
2. Route sensor wires through a knockout at the rear of the  
boiler (see FIG. 5-2).  
3. Connect the outdoor temperature sensor (FIG. 5-3) to  
the outdoor sensor terminals on the connection board to  
enable outdoor reset operation of the outdoor boiler.  
Boiler pump speed output  
This 0 - 10V output is available to control the speed of a variable  
speed boiler pump. The SMART SYSTEM control will vary the  
speed of this pump in order to maintain a minimum T across  
the heat exchanger, as well as prevent high limit lockouts when  
the flow in the primary loop is extremely low. Connect this  
output to the 0 - 10V input on the boiler pump speed control.  
DHW thermostat  
Connect storage indirect water heater (DHW) thermostat  
(FIG. 5-3) to the DHW thermostat terminals on the  
connection board. If a tank sensor is connected (see DHW  
Tank Sensor below) the tank thermostat is ignored.  
Rate output  
This output provides a 0 - 10V signal that is proportional to the  
firing rate of the boiler. This may be used by a BMS system to  
monitor the actual rate of the boiler.  
DHW tank sensor  
1. By installing a tank sensor, the SMART SYSTEM control  
can perform the tank thermostat function. The SMART  
SYSTEM control automatically detects the presence of  
this sensor and generates a DHW call for heat when  
the tank temperature drops 6°F (3°C) below the tank  
set point and finishes the call for heat when the tank  
temperature reaches the tank set point.  
ModBus  
When the optional ModBus interface module is installed, the  
RS-485 ModBus cable is connected to these terminals. Use  
shielded, 2-wire twisted pair cable. If desired, the shield can  
be connected to ground by installing a jumper wire between  
terminals 1 and 3 on connector X5 on the optional ModBus  
interface module.  
2. The tank sensor included with the Lochinvar Squire  
Indirect DHW tank (TST20015) is the only sensor  
suitable for use with the SMART SYSTEM control.  
Connect the sensor leads to the Tank Sensor terminals on  
the Low Voltage Connection Board (FIG. 5-3).  
Failure to use the correct sensor may result  
in the tank temperature being either above  
ƽ WARNING  
or below the set point.  
3. If the TST20015 is not compatible with the indirect  
tank, a tank thermostat can be used to control the  
boiler. The tank thermostat should be installed per  
the manufacturers instructions and wired to the DHW  
Thermostat terminals on the Low Voltage Connection  
Board.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
5 Field wiring  
1. A flow switch is used to guarantee flow through the  
boiler before allowing it to fire. The flow switch must be  
installed at the boiler outlet.  
Flow switch  
Runtime contacts  
The SMART SYSTEM control closes a set of dry contacts  
whenever the burner is running. This is typically used by  
Building Management Systems to verify that the boiler is  
2. Remove the jumper wire from these terminals, and  
connect these terminals to the normally open contacts on  
the flow switch (FIG. 5-3).  
responding to a call for heat.  
Alarm contacts  
The SMART SYSTEM control closes another set of contacts  
whenever the boiler is locked out or the power is turned off.  
This can be used to turn on an alarm, or signal a Building  
Management System that the boiler is down.  
System supply sensor  
1. By installing the system supply sensor into the supply  
of the primary loop, the temperature of the primary  
supply can be controlled. The SMART SYSTEM control  
automatically detects the presence of this sensor, and  
controls the boiler firing rate to maintain the system  
supply temperature to the set point (if the outlet sensor  
control is currently selected). If it is desired to control  
the system return temperature, then program the  
SMART SYSTEM control to use the inlet sensor as  
the controlling sensor. See the Outdoor Knight Boiler  
Service Manual for instructions on how to use the inlet  
sensor as the controlling sensor. When the inlet sensor  
is programmed as the controlling sensor, it is vital that  
the SYSTEM SUPPLY sensor be installed. DO NOT  
INSTALL THE SYSTEM SUPPLY SENSOR INTO THE  
SYSTEM RETURN.  
Wiring of the cascade  
When wiring the boilers for Cascade operation, select one  
boiler as the Leader boiler. The remaining boilers will be  
designated as Members. See page 38 “Configuration of the  
Cascade” for a detailed explanation of this procedure.  
Connect the system supply sensor and outdoor air sensor (if  
used) to the Leader boiler. For the Cascade system to work  
properly the system supply sensor must be installed. The  
location of the system supply sensor should be downstream  
of the boiler connections in the main system loop (FIG.’s 3-5,  
3-7, and 3-9). The system supply sensor should be wired to the  
Low Voltage Connection Board at the terminals marked for  
the system sensor (see FIG. 5-3). The Leader control will use  
the water temperature at the system supply sensor to control  
the operation of the Cascade.  
2. The TST2032 sensor provided with the boiler must be  
used for the system sensor.  
The outdoor air sensor should be wired to the Low Voltage  
Connection Board at the terminals marked for the outdoor air  
sensor (FIG. 5-3). The Leader control will calculate the water  
temperature set point based on the programmed reset curve  
parameters.  
3. Connect these terminals to the system supply sensor  
(FIG. 5-3).  
Boiler management system  
The United States Energy Policy and Conservation Act  
requires residential heating boilers with inputs less than  
300,000 Btu/hr be equipped with a control that automatically  
adjusts boiler water temperature in relation to heat demand.  
An external control may be connected to control the firing  
rate or the set point of the boiler provided that either an  
external energy management system is installed that reduces  
the boiler water temperature as the heating load decreases,  
the boiler is not used for any space heating, or the boiler is  
part of a modular or multiple boiler system having a total  
input of 300,000 Btu/hr or greater.  
If a Thermostat, Zone Control enable output, or Building  
Management System enable output is available, it should  
be wired to the Low Voltage Connection Board on the  
Leader boiler at the terminals marked for one of the heat/  
loop demands 1-3 (FIG. 5-3). If the boilers are to run  
continuously, connect a jumper wire between the R and W  
terminals for the heat/loop demand input. This will initiate a  
call for heat on the Cascade.  
Communication between the Leader boiler and the Member  
boilers is accomplished by using shielded, 2-wire twisted pair  
communication cable. Connect one of the twisted pair wires  
to Cascade terminal A on each of the Low Voltage Connection  
boards, and the other wire of the twisted pair to Cascade  
terminal B on each of the Low Voltage Connection Boards.  
Connect the shield wires to one of the shield terminals on  
the Low Voltage Connection Boards (FIG. 5-3). If more than  
two boilers are on the Cascade, daisy chain the wiring from  
the Cascade terminals on the second boiler to the Cascade  
terminals on the third boiler, then from the third to the forth,  
and so on. The connections between boilers can be made in  
any order, regardless of the addresses of the boilers. Try to  
keep each cable as short as possible.  
1. An external control may be connected to control either  
the firing rate or the set point of the boiler. If the external  
control uses a set of contacts to enable the boiler, connect  
the contacts to the Heat/Loop Demand 1 terminals.  
Otherwise, the SMART SYSTEM control will be enabled  
by the 0-10V signal.  
2. Make sure the (-) terminal is connected to the (-) or  
common output terminal of the external control, and  
the 0 - 10 Vdc terminal is connected to the 0 - 10 Vdc  
terminal of the external control. Make sure the (-)  
voltage is not below ground.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
5 Field wiring  
(continued)  
Figure 5-3 Low Voltage Field Wiring Connections  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
6 Condensate disposal  
Use materials approved by the authority  
Condensate drain  
NOTICE  
having jurisdiction. In the absence of  
other authority, PVC and CPVC pipe  
must comply with ASTM D1785 or D2845.  
Cement and primer must comply with  
ASME D2564 or F493.  
1. This boiler is a high efficiency appliance that produces  
condensate.  
2. The side of the boiler has a 1/2 inch PVC union for  
connection of a 1/2 inch PVC pipe (FIG. 6-1).  
To allow for proper drainage on large  
NOTICE  
3. Slope condensate tubing down and away from the  
boiler into a drain or condensate neutralizing filter.  
Condensate from the outdoor boiler will be slightly acidic  
(typically with a pH from 3 to 5). Install a neutralizing  
filter if required by local codes.  
horizontal runs, a second line vent may  
be required and tubing size may need to  
increase to 1 inch.  
The condensate line must remain  
unobstructed, allowing free flow of  
condensate. If condensate is allowed to  
freeze in the line or if the line is obstructed  
in any other manner, condensate can exit  
from the boiler tee, resulting in potential  
water damage to property.  
A Neutralizer Kit (FIG. 6-1) is available from the factory  
(Kit 3087).  
4. Install the 1/2 inch PVC tee assembly (shipped with the  
unit) as shown in FIG. 6-1.  
8. A condensate removal pump is required if the boiler is  
below the drain. When installing a condensate pump,  
select one approved for use with condensing boilers and  
furnaces. The pump should have an overflow switch to  
prevent property damage from condensate spillage. The  
switch should be wired in series with the blocked drain  
switch inside the boiler (see FIG. 7-1 on page 34).  
5. Leave the top of the 1/2 inch tee OPEN. This is needed as  
a vacuum break.  
6. Do not expose condensate line to freezing temperatures.  
Precautions should be taken to protect the condensate  
management and disposal system during extended  
periods of outdoor temperatures below 32°F.  
7. Use only plastic tubing or piping as a condensate drain  
line (FIG. 6-1).  
Figure 6-1 Condensate Disposal  
1/2" PVC TEE ASSEMBLY  
(FACTORY SUPPLIED)  
1/2" PVC UNION  
(FACTORY SUPPLIED)  
NEUTRALIZER KIT  
FLOOR DRAIN OR  
DRAIN PAN  
IMG00387  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
7 Start-up  
3. Fill to correct system pressure. Correct pressure will vary  
with each application.  
Check/control water chemistry  
Do not use petroleum-based cleaning or  
ƽ CAUTION  
a. The minimum cold water fill pressure for  
residential system is 12 psi.  
a
sealing compounds in the boiler system.  
Damage to elastomer seals and gaskets  
in the system could occur, resulting in  
substantial property damage.  
b. Pressure will rise when boiler is turned on and  
system water temperature increases.  
Hardness less than 7 grains  
4. At initial fill and during boiler startup and testing, check  
system thoroughly for any leaks. Repair all leaks before  
proceeding further.  
1. Consult local water treatment companies for hard water  
areas (above 7 grains hardness).  
Eliminate all system leaks. Continual  
Chlorine concentration less than 200 ppm  
ƽ WARNING  
fresh makeup water will reduce boiler life.  
Minerals can build up in the heat exchanger,  
reducing heat transfer, overheating the heat  
exchanger, and causing heat exchanger  
failure.  
1. Do not fill boiler or operate with water containing  
chlorine in excess of 200 ppm.  
2. Filling with chlorinated fresh water should be acceptable  
since drinking water chlorine levels are much lower.  
Purge air from water system  
3. Do not use the boiler to directly heat swimming pool or  
spa water.  
1. Purge air from system:  
a. Connect a hose to the purge valve (see purge/drain  
valves, in piping diagrams on pages 17 through 23).  
Route the hose to an area where water can drain and  
be seen.  
b. Close the boiler or system isolation valve between  
the purge valve and fill connection to the system.  
c. Close zone isolation valves.  
Test/replace freeze protection fluid  
1. For systems using freeze protection fluids, follow fluid  
manufacturer’s instructions.  
2. Freeze protection fluid must be replaced periodically due  
to degradation of inhibitors over time. Follow all fluid  
manufacturer’s instructions.  
d. Open quick-fill valve on cold water makeup line.  
e. Open purge valve.  
f. One zone at a time, open the isolation valves. Allow  
water to run through the zone, pushing out the air.  
Run until no noticeable air flow is present. Close the  
zone isolation valves and proceed with the next zone.  
Follow this procedure until all zones are purged.  
g. Close the quick-fill water valve and purge valve and  
remove the hose. Open all isolation valves. Watch  
that system pressure rises to correct cold-fill  
pressure.  
Freeze protection (when used)  
1. Determine freeze protection fluid quantity using  
system water content, following fluid manufacturer’s  
instructions. Boiler water content is listed on page 7.  
Remember to include expansion tank water content.  
2. Local codes may require a backflow preventer or actual  
disconnect from city water supply.  
h. After the system has operated for a while, eliminate  
any residual air by using the manual air vents located  
throughout the system.  
i. If purge valves are not installed in the system, open  
the manual air vents in the system one at a time,  
beginning with the lowest floor. Close the vent when  
water squirts out. Repeat with remaining vents.  
3. When using freeze protection fluid with automatic fill,  
install a water meter to monitor water makeup. Freeze  
protection fluid may leak before the water begins to  
leak, causing concentration to drop, reducing the freeze  
protection level.  
4. The freeze protection set points may be lowered when  
freeze protection fluid is used (see the Outdoor Knight  
Service Manual).  
2. Open automatic air vent (diaphragm-type or bladder-type  
expansion tank systems only) one turn.  
Fill and test water system  
3. Open other vents:  
1. Fill system only after ensuring the water meets the  
requirements of this manual.  
a. Starting on the lowest floor, open air vents one at a  
time until water squirts out.  
b. Repeat with remaining vents.  
2. Close manual and automatic air vents and boiler drain  
valve.  
4. Refill to correct pressure.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
7 Start-up  
Propane boilers only – Your propane  
ƽ WARNING  
Check for gas leaks  
suppliermixesanodorantwiththepropane  
Before starting the boiler, and during  
initial operation, smell near the floor and  
to make its presence detectable. In some  
instances, the odorant can fade, and the  
gas may no longer have an odor. Before  
startup (and periodically thereafter), have  
the propane supplier verify the correct  
odorant level in the gas.  
ƽ WARNING  
around the boiler for gas odorant or any  
unusual odor. Remove the top access  
cover and smell the interior of the boiler  
enclosure. Do not proceed with startup  
if there is any indication of a gas leak.  
Use an approved leak detection solution.  
Repair any leaks at once.  
Check thermostat circuit(s)  
1. Disconnect the two external wires connected to each  
of the heat/loop demand terminals on the connection  
board.  
DO NOT adjust gas valve outlet pressure.  
The gas valve is factory set for the correct  
outlet pressure. This setting is suitable  
for natural gas and propane, requiring  
no field adjustment. Attempting to  
alter the gas valve outlet pressure could  
result in damage to the valve, causing  
potential severe personal injury, death, or  
substantial property damage.  
ƽ WARNING  
2. Connect a voltmeter across these two incoming wires.  
Close each thermostat, zone valve, and relay in the  
external circuit one at a time and check the voltmeter  
reading across the incoming wires.  
3. There should NEVER be a voltage reading.  
4. If a voltage does occur under any condition, check and  
correct the external wiring. (This is a common problem  
when using 3-wire zone valves.)  
Figure 7-1 Condensate Trap  
RETAINING  
SCREW  
5. Once the external thermostat circuit wiring is checked and  
corrected if necessary, reconnect the external thermostat  
circuit wires to the connection board.  
2” PVC CAP WITH  
BLOCKED DRAIN SWITCH  
PVC TEE ASSEMBLY  
(FACTORY SUPPLIED)  
Inspect/fill condensate system  
Inspect/check condensate lines and fittings  
1. Inspect the condensate drain line, condensate PVC  
fittings and condensate trap.  
Fill condensate trap with water  
1. Remove the PVC cap retaining screw from the PVC cap  
(FIG. 7-1).  
CONDENSATE FROM  
HEAT EXCHANGER  
TO FLOOR  
DRAIN  
2. Remove the 2 inch PVC cap with the switch located at the  
top of the trap (FIG. 7-1).  
3. Fill with fresh water until the water begins to pour out of  
the drain.  
4. Replace the cap. Press the cap onto the trap until the cap  
makes contact with the drain.  
5. Replace the retaining screw.  
The condensate trap (FIG. 7-1) must be  
filled with water during all times of boiler  
ƽ WARNING  
operation to avoid flue gas emission from  
the condensate drain line. Failure to fill  
the trap could result in severe personal  
injury or death.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
7 Start-up  
(continued)  
Final checks before starting the boiler  
Check gas piping  
Read the Outdoor Knight Boiler Service Manual to  
familiarize yourself with SMART SYSTEM control  
module operation. Read this manual, page 36 for proper  
steps to start boiler.  
1. Check around the boiler for gas odor following the  
procedure on page 24 of this manual (connecting gas supply  
piping).  
If you discover evidence of any gas leak,  
ƽ WARNING  
shut down the boiler at once. Find the  
Verify the boiler and system are full of water and all  
leak source with a bubble test and repair  
immediately. Do not start the boiler again  
until corrected. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
system components are correctly set for operation.  
Verify the preparation procedures of Section 7, pages 33  
and 34 have been completed.  
Fill the vent condensate trap with water (removing the  
retaining screw in order to remove the 2 inch PVC cap  
with the switch located at the top of the trap). Replace  
the cap. Press the cap onto the trap until the cap makes  
contact with the drain. Replace the retaining screw.  
Propane boilers – verify conversion  
1. Verify propane conversion has been completed per the  
Propane Conversion instructions.  
DO NOT adjust gas valve outlet pressure.  
ƽ WARNING  
The gas valve is factory-set for the correct  
Verify electrical connections are correct and securely  
outlet pressure. This setting is suitable  
for natural gas and propane, requiring  
no field adjustment. Attempting to alter  
the gas valve outlet pressure could result  
in damage to the valve, causing potential  
severe personal injury, death, or substantial  
property damage.  
attached.  
Verify air opening and vent opening are free of  
obstruction.  
Start the boiler  
1. Read and follow the Operating instructions in FIG. 7-2,  
page 36.  
Outdoor boilers are typically shipped ready  
to fire on natural gas. Check boiler rating  
ƽ WARNING  
plate to determine which fuel the boiler is set  
for. If set to natural gas, it may be converted  
to LP by installing an orifice (see page 11).  
In order to operate on LP gas, an orifice  
MUST BE installed. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
If boiler does not start correctly  
1. Check for loose connections, blown fuse or service switch  
off?  
2. Is boiler water temperature above 200°F?  
3. Is thermostat set below the controlling sensor  
temperature?  
Check flame and combustion  
1. Turn the main power off to the boiler by placing the “On/  
Off” switch in the OFF position.  
4. Is gas turned on at meter or boiler?  
5. Is incoming gas pressure less than 4 inches w.c.?  
2. Remove the flue temperature sensor from the flue pipe  
connection. NOTE: Combustion measurements will be  
made at this point.  
If none of the above corrects the problem, refer to the  
Troubleshooting Section of the Outdoor Knight Boiler  
Service Manual.  
3. Turn the main power on to the boiler by placing the “On/  
Off” switch in the ON position.  
Check system and boiler  
Check water piping  
1. Check system piping for leaks. If found, shut down  
the boiler and repair immediately. (See WARNINGS  
on pages 33 and 34 (startup) regarding failure to repair  
leaks.)  
2. Vent any remaining air from the system using manual  
vents. Air in the system will interfere with circulation  
and cause heat distribution problems and noise.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
7 Start-up  
Figure 7-2 Operating Instructions  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
7 Start-up  
(continued)  
Check flame and combustion (continued)  
Set space heating operation  
Please note that the brackets ([]) denote  
screen status.  
Determine controlling sensor  
NOTICE  
For space heating systems, the temperature control can be  
based on one of three sensors; the inlet, outlet, or system  
supply sensor. The SMART SYSTEM control is programmed  
at the factory to control the temperature of the outlet  
sensor. The control will automatically switch to the system  
supply sensor once it is connected. If it is desired to base  
the temperature control on the inlet sensor, the appropriate  
parameter must be changed in the control. See the Outdoor  
Knight Boiler Service Manual for a detailed explanation of  
this procedure.  
4. Place the boiler into the active position by pressing the  
RIGHT SELECT [ON] key (FIG. 8-1, page 45).  
5. Locate the pinhole button below the RESET button on  
the display board (FIG. 8-1). Insert a thin wire (such as  
a paper clip) into the hole and press the button once and  
hold for 5 seconds to place the boiler into Service Mode.  
In Service Mode the boiler will fire at ignition speed and  
will then modulate up to full fire.  
6. Insert the probe from a combustion analyzer into the flue  
outlet opening.  
Verify space heat circulator mode  
The Space Heating Mode controls both the system pump  
(if connected), and the boiler pump. When the SMART  
SYSTEM control receives a space heating call for heat, it turns  
on the system pump. If the boiler is not heating an indirect  
DHW (Domestic Hot Water) tank, and the set point is not  
met, it also turns on the boiler pump. After the space heating  
call for heat ends, the system pump continues to run for a  
short period of time. The system pump can be programmed  
to run continuously, except during outdoor shutdown. If  
the boiler pump was running, it continues to run for a short  
period of time as well. These pump delays are factory set to  
30 seconds. If different delays are desired, the appropriate  
parameters in the control must be changed. See the Outdoor  
Knight Boiler Service Manual for a detailed explanation of  
this procedure.  
7. Once the boiler has modulated up to full fire, measure the  
combustion. The values should be in the range listed in  
Table 7A below. The CO levels should be less than 150  
ppm for a properly installed unit.  
If the combustion is not within the specified range,  
reference the Troubleshooting Section of the Outdoor  
Knight Boiler Service Manual for possible causes and  
corrective actions.  
Table 7A Flue Products Chart  
Natural Gas  
CO2 O2  
Propane  
CO2  
O2  
Adjust set point temperature(s)  
8.0% - 10% 3.0% - 6.5% 9.0% - 11% 4.1% - 6.9%  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
8. Once the combustion analysis is complete, test the safety  
shutoff device by turning the manual shutoff switch to  
the OFF position and ensuring that the boiler shuts  
down and registers an alarm. Turn the manual shutoff  
switch to the ON position and reset the control.  
The NAVIGATION dial may be used during normal  
operation to adjust the space heating and tank set point  
temperatures.  
1. From the Status Screen press the NAVIGATION dial.  
2. Turn the NAVIGATION dial counterclockwise to select  
the appropriate set point.  
3. Press the NAVIGATION dial to adjust the temperature.  
4. Once the desired temperature is displayed, press the  
RIGHT SELECT [SAVE] key.  
9. Turn the main power off to the boiler.  
10. Place the boiler back into normal operation.  
5. If necessary repeat Steps 3 and 4 to make adjustments to  
additional set points.  
6. Press the RIGHT SELECT [HOME[ key to upload the  
changes.  
7. If the RIGHT SELECT [SAVE] key is not pressed, the  
new settings will be discarded.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
7 Start-up  
Set domestic hot water (DHW) operation  
Verify DHW mode  
8. Turn the NAVIGATION dial to adjust the month. Press the  
NAVIGATION dial.  
There are two (2) modes of operation for DHW. In Normal  
Mode, when a DHW demand begins, the control will start  
the DHW pump, turn off the boiler pump (if running), and  
modulate to bring the outlet temperature to the DHW boiler  
set point. The maximum firing rate may be limited in this  
mode if desired.  
9. Turn the NAVIGATION dial to adjust the date. Press the  
NAVIGATION dial.  
10. Turn the NAVIGATION dial to adjust the year. Press the  
RIGHT SELECT [SAVE] key.  
In Zone Mode it is assumed that the indirect DHW tank is  
piped as a zone on the primary loop. When a DHW demand  
begins, the control will turn on the DHW pump output, and  
raise the system temperature set point to the DHW boiler set  
point (if higher). The boiler pump will be turned on. The  
system pump may be forced on, forced off, or not changed,  
depending on the System Pump Mode selected (reference the  
Outdoor Knight Service Manual for details). In this mode,  
any low temperature zones (such as radiant heating) may  
need additional controls to limit the water temperature sent  
to those zones.  
11. Press the RIGHT SELECT [HOME] key.  
The internal clock does not adjust for  
NOTICE  
Daylight Savings Time and therefore, will  
require a manual adjustment.  
The clock is automatically updated whenever a PC is connected  
and the Win Pro-Installer program is started.  
Configuration of the cascade  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
Set DHW boiler target temperature  
When installed in a Cascade system, the individual controls  
must be programmed for cascade operation. This is  
accomplished by accessing the control parameters.  
When in the DHW Mode, the control will modulate to  
maintain the boiler outlet temperature or system supply  
temperature to a set point. This set point is set at the factory  
to 180°F. If a different set point is desired, the appropriate  
parameter in the control must be changed. See the Outdoor  
Knight Boiler Service Manual for a detailed explanation of  
this procedure.  
Press the [MENU] key for at least five (5) seconds. Input  
the Installer code as described in the Outdoor Knight Boiler  
Service Manual. Once the control parameters have been  
accessed, use the NAVIGATION dial to select the Control  
Mode parameters. Press the NAVIGATION dial to access  
these parameters.  
Set maximum DHW fan speed  
If the rated input of the indirect tank is less than the  
maximum output of the boiler, change the maximum DHW  
fan speed setting to limit the boiler output accordingly, see  
the Outdoor Knight Boiler Service Manual for a detailed  
explanation of this procedure.  
Rotate the NAVIGATION dial to select the parameter  
“Cascade Address”. Press the NAVIGATION dial to access  
this parameter. Each appliance in the Cascade system must  
be programmed with its own address. The boiler designated  
as the Leader will have an address of 0. The remaining boilers  
in the Cascade will be Members and have addresses from 1  
- 7. Rotate the NAVIGATION dial to select the appropriate  
address. Press the RIGHT SELECT [SAVE] key.  
Set clock  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
Press the RIGHT SELECT [HOME] key to upload the address  
into the control. Repeat this procedure for all boilers in the  
Cascade, designating the Leader control and the Member  
controls.  
The SMART SYSTEM control has a built-in clock that it  
uses for its night setback feature and for logging events. This  
clock must be set when the boiler is installed, and anytime  
the boiler has been powered off for more than 4 hours. Use  
the following procedure to set the clock:  
1. Press and hold the LEFT SELECT [MENU] key for at  
least 5 seconds.  
2. The display changes to read [PASSWORD],  
with four (4) zeros below it.  
3. Press the RIGHT SELECT [SAVE] key.  
4. The display will then show a menu with the time and  
date and temperature unit.  
5. Press the NAVIGATION dial twice.  
6. Turn the NAVIGATION dial to adjust the hours. Press  
the NAVIGATION dial.  
7. Turn the NAVIGATION dial to adjust the minutes. Press  
the NAVIGATION dial.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
38  
Outdoor Knight Boiler Installation & Operation Manual  
8 Operating information  
How the boiler operates  
General  
The control can be configured by the installer to use a 0 - 10  
Vdc signal to either control set point or firing rate.  
The outdoor boiler uses an advanced stainless steel heat  
exchanger and electronic control module that allows fully  
condensing operation. The blower pulls in air and pushes flue  
products out of the boiler through the heat exchanger and flue  
piping. The control module regulates blower speed to control  
the boiler firing rate. The gas valve senses the amount of air  
flowing into the boiler and allows only the right amount of gas  
to flow.  
The outdoor boiler can also be programmed to accept a call for  
heat from a 0 - 10V signal, reference the Outdoor Knight Boiler  
Service Manual for a detailed explanation of this procedure.  
DHW priority  
The SMART SYSTEM control allows the connection of a DHW  
thermostat or tank sensor to the low voltage connection board.  
When a tank sensor is connected, the DHW thermostat input  
is ignored. When a boiler is programmed for DHW Normal  
Mode, the maximum firing rate can be limited to match the  
input rating of the indirect tank coil.  
How the control module operates  
The SMART SYSTEM control module receives inputs from  
boiler sensors and external devices. The control module  
activates and controls the blower and gas valve to regulate heat  
input and switches the boiler, Domestic Hot Water (DHW),  
and system pumps on and off as needed. The user programs  
the module to meet system needs by adjusting control  
parameters. These parameters set operating temperatures  
and boiler operating modes. Boiler operation can be based on  
boiler outlet water temperature, boiler inlet water temperature,  
system temperature, a 0-10V signal or ModBus, depending on  
the parameter settings.  
DHW / space heating (SH) cycling  
If a DHW call for heat is received while a space heating call is  
in progress, and the DHW is in Normal Mode, the control will  
start the DHW pump and shut the boiler pump off. The system  
pump will remain on. For stand-alone boilers, if the space  
heating call is still active while the DHW call is in operation,  
the control will wait for 30 minutes (time adjustable by  
installer) then it will switch back to the space heating demand.  
There is a timer to switch from space heating to DHW and a  
timer to switch from DHW to space heating. The control will  
switch back and forth until one of the heat demands end.  
Control inputs and outputs  
Room thermostat  
Programmable controlling sensor  
There are three (3) heat/loop demand connections available on  
this control. These inputs tell the boiler to provide water for  
space heating. Each demand connection has its own set point  
and outdoor air reset curve. When multiple demands have a  
call for heat the control will give priority to the demand with  
the highest set point.  
The control module is programmed to use the outlet sensor  
as the control sensor by default. If a system supply sensor  
is connected, the control automatically uses it as the control  
sensor. For stand-alone boilers, the control sensor can be  
changed by the installer to the inlet sensor. If the inlet sensor  
is chosen as the controlling sensor, it is recommended that the  
system supply sensor be installed in the system supply in order  
to provide the best control of the inlet temperature.  
Example:  
Assume that both heat/loop demand  
have call for heat.  
1
and heat/loop demand  
2
a
Demand 1 has a set point of 110°F. Demand 2 has a set point  
of 140°F. The boiler will regulate the system temperature to  
140°F until Demand 2 has been satisfied. Once Demand 2 has  
been satisfied the boiler will provide 110°F water to the system.  
Anti-cycling  
After the burner turns off, the control will delay the next  
burner cycle for a set time period (time is adjustable by the  
installer). The time delay will be bypassed if the inlet water  
temperature drops too far during the delay.  
When multiple temperature loops are  
ƽ CAUTION  
used, mixing valves are required for the  
protection of any low temperature loops.  
Boiler and system pump control  
SMART SYSTEM Multi-temp loop control  
The boiler pump will run whenever the burner is firing, unless  
the DHW is programmed for Normal Mode and the boiler  
is heating the DHW tank. The boiler pump will run during  
Freeze Protection Mode as well. It will continue to run for a  
short time after the burner turns off or the Freeze Protection  
Mode ends.  
The outdoor boiler is capable of producing up to three (3) set  
point temperatures to meet different space heating demands.  
This device controls the temperatures of up to three (3)  
separate loops, based on the settings for the three (3) heat/loop  
demands (reference Lochinvar kit RLY30086).  
The system pump will run whenever there is a space heating  
call for heat, or the boiler goes into Freeze Protection Mode. It  
may be programmed to run during a DHW call for heat when  
the DHW is programmed for Zone Mode. It will continue  
to run for a short time after the end of the heat demand  
or the Freeze Protection Mode. The system pump can be  
programmed to run continuously if desired, except during  
outdoor shutdown and/or a DHW call for heat.  
0 - 10V input (set point or power)  
The outdoor boiler can be controlled by a Building  
Management System (BMS) provided that either an external  
energy management system is installed that reduces the boiler  
water temperature as the heating load decreases, the boiler  
is not used for any space heating, or the boiler is part of a  
modular or multiple boiler system having a total input of  
300,000 Btu/hr or greater.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
39  
Outdoor Knight Boiler Installation & Operation Manual  
8 Operating information  
Temperature control  
Protection features  
Modulation  
Outlet temperature, flue temperature, and  
temperature rise limiting  
The outdoor boiler is capable of modulating its firing rate  
from a minimum of 20% to a maximum of 100%. The  
firing rate is dictated by the call for heat (i.e., space heating  
or domestic hot water), the heating load, ramp delay (if  
enabled), and various other temperature limitations.  
The outlet temperature is monitored by the boiler outlet  
temperature sensor. When the outlet temperature exceeds  
185°F, the unit will reduce the fan speed. If the outlet water  
temperature exceeds 195°F the control will shut the unit  
down until it cools off.  
Ramp delay  
The control module monitors the flue temperature by a  
sensor located in the flue exhaust. If the flue temperature  
exceeds 215°F the control will reduce the maximum fan  
speed. If the flue temperature exceeds 240°F the control will  
shut the unit down. The unit will restart automatically once  
the flue temperature drops 25°F and the minimum off time  
has expired.  
For systems with lower flow, the SMART SYSTEM can limit  
the firing rate (when enabled) when a space heating call for  
heat starts, or when switching from a DHW call for heat to a  
space heating call for heat. There are six (6) limits that can be  
programmed, as well as six (6) time intervals corresponding  
to each limit. The sixth limit will also limit the firing rate for  
the rest of the call for heat.  
The control monitors the temperature difference between  
the inlet and the outlet sensor. If this difference exceeds  
55°F the control will reduce the maximum fan speed. If  
the temperature difference exceeds 60°F the control will  
shut the unit down. The unit will restart automatically once  
the temperature difference has dropped below 55°F and the  
minimum off time has expired.  
Gradient limiting  
If during operation of the boiler the outlet water temperature  
is rising too quickly, the control will reduce the firing rate to  
its lowest setting.  
Outdoor air reset  
With the outdoor air sensor connected, the control module  
will calculate the set points of the three (3) space heating  
demands based on the programmed reset curves. The  
installer can change the slope of the reset curves by several  
adjustable parameters. The user can limit the maximum set  
point for the system using the space heating set points.  
Freeze protection  
DO NOT install the boiler where it is likely to freeze.  
The following integral feature of the SMART SYSTEM  
control module provides some protection for the boiler only  
-- not for the system.  
Boost function  
The SMART SYSTEM control module provides  
freeze-up protection as follows when the boiler  
water temperature drops below 45°F:  
Below 45°F, the boiler and system pumps operate  
constantly.  
Below 37°F, the boiler turns on.  
Boiler and pumps turn off if boiler water  
temperature rises above 45°F.  
If outdoor air reset is active, and any space heating demand  
has been active continuously for a set period of time (time  
adjustable by installer) and there has been no DHW demands,  
the control will increase the set point of that demand  
by a fixed number of degrees (adjustable by installer).  
This process will continue until the space heating demand  
ends, the set point reaches the programmed set point or a  
maximum of 20 increases has occurred. Once the system  
heat demand is satisfied, the set point will revert to the value  
determined by the reset curve.  
Lower temperatures may be programmed for  
systems with anti-freeze solutions.  
When system return temperatures  
NOTICE  
are maintained below the dew point,  
condensation will form on the inside of  
the boiler jacket causing some internal  
sheet metal components to rust.  
Night setback  
The controller may be programmed to reduce the space  
heating and DHW set points during certain times each week.  
Seven different start and stop times may be programmed  
for the space heating setback and seven start and stop times  
for the DHW setback. Any night setback event scheduled  
within the next seven (7) days can be temporarily bypassed  
if desired.  
This feature of the SMART SYSTEM  
control module does not eliminate the  
possibility of freezing. The installation  
must still use recognized design,  
installation and maintenance practice to  
prevent freeze potential for the boiler and  
system.  
ƽ CAUTION  
Flame current support  
To prevent nuisance shutdowns when the boiler is firing at  
minimum rates, the control will increase the firing rate when  
the flame signal drops too low.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
40  
Outdoor Knight Boiler Installation & Operation Manual  
8 Operating information  
Connections are provided on the connection board for  
external limits such as a flow switch, low water cutoff and  
gas pressure switches. The SMART SYSTEM will shut off the  
burner and inhibit relighting whenever any of these external  
limits open.  
(continued)  
When the outlet temperature exceeds 200°F, the automatic  
high limit action occurs. The boiler shuts down until the outlet  
water temperature cools below 190°F, and a 60 second timer  
has expired. If the outlet temperature continues to increase, the  
manual reset high limit action will occur at 210°F.  
Monitor external limits  
High limit test procedure  
Run-time and alarm outputs  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
The boiler provides dry contacts for indicating when the  
boiler is running, and when it is unable to operate.  
1. Turn ON the main power to the boiler by placing the  
ON/OFF switch in the ON position.  
Run-time and cycle counting  
2. From the Status Screen, press the NAVIGATION dial to  
access the Set Points Screen.  
3. Press the LEFT SELECT (LIMITS) key.  
4. Select the manual reset high limit (MRHL) by rotating  
the NAVIGATION dial counterclockwise, then press  
the NAVIGATION dial.  
5. Decrease the set point of the MRHL to below the current  
outlet temperature (or to its minimum setting, whichever  
is higher) by turning the NAVIGATION dial  
counterclockwise.  
The control uses two timers to monitor the total hours of  
burner operation. One timer monitors the time the boiler is  
firing in the Space Heating Mode. The other timer monitors  
the time the boiler is firing in the DHW Mode.  
The control uses two (2) ignition counters to monitor the  
amount of boiler cycles. The first counter counts all ignitions  
of the control. The second counter counts only ignition  
attempts that have failed.  
Service reminder  
The control can be programmed for service reminder  
notification. This notification will become active when  
either a set time frame has expired, or a set amount of  
running hours or cycles has expired (all adjustable by the  
installer). The display will show a Maintenance Required  
screen. The installer's name and phone number can be  
programmed into the control. This information will appear  
on the Maintenance Required screen. The service reminder  
notification can be reset or disabled by the installer.  
6. Press the RIGHT SELECT [SAVE] key.  
7. Press the RIGHT SELECT [HOME] key. The new  
parameter will upload to the control.  
8. If the current outlet temperature is above the new MRHL  
set point, the MRHL will function causing boiler lockout.  
If this occurs, skip to Step 11.  
9. If the current outlet temperature is below the new MRHL  
set point, locate the pinhole (SERVICE button) below the  
RESET button on the display board. Insert a thin probe  
(such as a paper clip) into the hole and press the button  
continuously for five (5) seconds to place the boiler into  
Service Mode. In Service Mode, the boiler will fire at  
ignition speed and will then modulate up to full fire.  
10. Once the outlet temperature rises up to the MRHL set  
point, the MRHL will function, causing the boiler to shut  
down and lock out.  
The time dependent feature has been disabled by the  
manufacturer. To enable this feature change the parameter  
to the desired time interval, reference the Outdoor Knight  
Service Manual for details regarding parameters.  
Error logging  
The control will hold in memory the last 10 lockouts as  
well as the last 10 blockings. The date and time of the  
occurrence will be recorded as well. Only the 10 most current  
occurrences of each will be held in memory.  
11. Repeat Steps 2, 3 and 4.  
12. Set the MRHL to the appropriate set point by turning the  
NAVIGATION dial clockwise.  
Boiler temperature regulation  
Operating temperature (target)  
13. Repeat Steps 6 and 7.  
14. Press the RESET button to clear the lockout.  
15. If needed, press the RIGHT SELECT [STOP] key to exit  
Service Mode.  
The SMART SYSTEM control module senses water  
temperature and regulates boiler firing and firing rate to  
achieve a target temperature. The target temperature can be  
set between 32°F and 190°F.  
Low water cutoff protection  
Target temperature is calculated as described in the  
“Outdoor Reset Operation” section, when the  
outdoor sensor is connected.  
If the outdoor sensor is not connected, the target  
temperature is fixed at SH (1 - 3) set points. An  
outdoor sensor fault will remain on the display  
screen until the outdoor sensor is reconnected.  
1. The SMART SYSTEM control module uses temperature  
sensing of both supply and return areas of the heat  
exchanger. If the flow rate is too low or the outlet  
temperature too high, the control module modulates and  
shuts the boiler down. This ensures boiler shutdown in the  
event of low water or low flow conditions.  
2. Some codes and jurisdiction may accept these integral  
features of the control in lieu of requiring an additional  
limit control or low water cutoff. Consult local jurisdiction  
to determine. A low water cutoff is available from the  
factory (WTR30024).  
High limit operations  
The outdoor boiler is equipped with adjustable automatic  
reset and manual reset high limits. The automatic reset high  
limit has a maximum set point of 200°F and the manual reset  
high limit has a maximum setDpoowinnlotaodffr2o1m0W°Fw.w.Somanuals.com. All Manuals Search And Download.  
41  
Outdoor Knight Boiler Installation & Operation Manual  
8 Operating information  
Outdoor reset operation  
Sequence of the cascade  
Target temperature with outdoor reset  
To equalize the run time of all boilers on the Cascade, the  
firing sequence will automatically be changed at set intervals.  
This feature improves the system's efficiency by decreasing set  
point as the outdoor temperature warms up. Energy Efficiency  
Standards require the use of a control that automatically adjusts  
set point in relation to heat demand. In the absence of an  
external energy management system, this feature MUST BE  
used.  
During the first 24 hours of operation, the sequence will  
change every hour. After that, the sequence will change every  
24 hours. The switching on/off sequence will be as follows:  
TIME  
Start  
SWITCHING ON SEQUENCE  
L-M1-M2-M3-M4-M5-M6-M7  
M1-M2-M3-M4-M5-M6-M7-L  
See the Outdoor Knight Boiler Service Manual to change the  
settings.  
1 hour  
Reset curve  
2 hours  
M2-M3-M4-M5-M6-M7-L-M1  
The reset curve looks at outdoor air temperature and adjusts  
the set point in relation to heat demand.  
If a boiler locks out or is used to heat an indirect DHW tank,  
it will automatically be given the lowest priority for the rest  
of that 24 hour period.  
Cascade  
When multiple boilers are installed, they can be wired together  
in a cascade sequence. A maximum of eight boilers can be  
controlled from a single control. In this application one boiler  
would be designated as the Leader control and all others would  
be designated as Member controls. The Leader control can  
be programmed to use Lead/Lag or Efficiency Optimization  
control methods.  
DHW, Night Setback, and Ramp Delay operation  
with cascade  
For Normal Mode DHW operation any boiler(s) in the  
Cascade can be selected to provide heat for a DHW call.  
Select a boiler to be designated as the DHW boiler. Connect  
the DHW thermostat or sensor to the terminals on the Low  
Voltage Connection Board marked for the corresponding  
device. When the boiler receives a DHW call, the Leader  
control will take that boiler out of the Cascade sequence. If  
another boiler is available, the Leader will start it up to take  
its place.  
Once the Leader boiler receives a call for heat from a room  
thermostat, BMS, or ModBus, the control will determine what  
the set point will be. If outdoor air reset is desired, connect  
the outdoor air sensor to the terminals on the Low Voltage  
Connection Board on the Leader boiler. The set point will be  
calculated based on the programmed reset curve parameters.  
See the Outdoor Knight Boiler Service Manual to program the  
reset curve. If outdoor air reset is not desired, do not connect  
the outdoor air sensor. A fixed temperature set point can be  
programmed into the control. See page 37 of this manual to  
program the set point.  
The DHW boiler will adjust its set point to the programmed  
DHW boiler set point and will adjust its firing rate to maintain  
this. Once the DHW call has been satisfied, the Leader control  
will place that boiler back into the Cascade sequence.  
Switching of the boiler between DHW operation and SH  
operation when there is a call for both does not occur in  
Cascade Mode.  
If the water temperature at the system supply sensor is less than  
the set point + the turn-off offset - the off-on differential, then  
the control will initiate a call for heat on the Cascade (see the  
Outdoor Knight Boiler Service Manual for an explanation of  
the offset and differential). The Leader will energize the lead  
boiler on the Cascade. For a new startup this will be the Leader  
boiler.  
When DHW is programmed for Zone Mode, connect the  
DHW thermostat or tank sensor to the Leader boiler. When  
a DHW call is received, the Leader will modulate the entire  
Cascade to bring the system supply temperature up to the  
DHW boiler set point.  
Night Setback operation of the boilers within the Cascade is  
available. Programming of the Night Setback will be done  
through the Leader boiler. Refer to the Outdoor Knight Boiler  
Service Manual for information regarding Night Setback.  
Ramp Delay operation of the boilers as described in the  
Outdoor Knight Boiler Service Manual is available when the  
boilers are part of a Cascade system.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
8 Operating information  
(continued)  
Sequence of operation  
OPERATION  
DISPLAY  
1. Upon a call for heat, the gas pressure switch(es) must be closed.  
2. Once the gas pressure switch(es) are closed, the control turns  
on the appropriate pumps (system and boiler pumps for space  
heating, DHW pump for DHW). The flow switch and/or LWCO  
must close.  
3. The air pressure switch and blocked drain switch must close.  
4. The control starts the prepurge cycle by initiating the blower.  
5. The control starts the trial for ignition by firing the spark electrode  
and opening the gas valve.  
6. If flame is not detected after the sparking ends, the control will  
perform a post-purge, then start another prepurge cycle and try to  
light the burner again. The control will perform a total of 4  
attempts before locking out.  
7. If flame is detected, it holds the firing rate steady for a few  
seconds to let the flame stabilize, then it begins to modulate the  
firing rate based on a set point or some other command (such  
as a 0-10V BMS signal).  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
8 Operating information  
Sequence of operation (continued)  
OPERATION  
DISPLAY  
8. If the space heating call for heat is active, and the tank thermostat  
or sensor starts a DHW call for heat, the boiler will switch to the  
DHW mode. If programmed for normal DHW operation (not as a  
zone), the DHW pump will turn on first, then the boiler pump will  
turn off 2 seconds later. This will divert the boiler’s outlet water  
from the heating system and send it to the tank coil instead. The  
control will then modulate to maintain the outlet temperature to  
the DHW boiler set point.  
9. If the boiler is not part of a Cascade, and both the space heating  
and DHW calls for heat remain active long enough, the boiler will  
switch back and forth between the two heating modes until one of  
them is satisfied.  
10. Once both calls for heat are satisfied, the control will turn off the  
burner.  
The blower will continue to run during the  
postpurge period.  
11. Any pumps that are running will continue to run for their respective  
pump delay times before turning off, unless programmed to  
remain on continuously. A 60 second anti-cycle period will start,  
which will delay any new call for heat until it times out.  
12. In Standby, ready to start a new cycle.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
8 Operating information  
(continued)  
Outdoor Knight boiler control module  
Use the control panel (FIG. 8-1) to set temperatures, operating conditions, and monitor boiler operation.  
Figure 8-1 Control Panel  
NAVIGATION DIAL  
(PRESS OR TURN)  
The information on the bottom of the display shows the functions of the two SELECT keys (on either corner), and the  
NAVIGATION dial (in the center):  
MENU = Left SELECT Key  
SETPOINTS = NAVIGATION Dial - Pressing Down  
SHDN = Right SELECT Key  
Access modes  
User  
Saving parameters (reference the Parameter Table in  
the Outdoor Knight Boiler Service Manual)  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
The user can adjust space heating and tank target temperatures  
by pressing the NAVIGATION dial when “SETPOINTS” is  
flashing at the bottom of the display. The date and time, and  
the temperature units can also be changed (see page 38).  
To save parameters and exit programming:  
Press the RIGHT SELECT [SAVE] key and then press the  
RIGHT SELECT [HOME] key.  
Installer  
To enter a parameter and continue programming:  
Most parameters are available only to the installer, accessible  
by entering the installer password, see the Outdoor Knight  
Boiler Service Manual.  
Press the RIGHT SELECT [SAVE] key 1 time to return to the  
parameter listings; press again to return to the menu listings.  
Remember to press the RIGHT SELECT [HOME] key when  
finished programming in order to save the changes made.  
See the Outdoor Knight Boiler Service Manual for a detailed  
description of parameters and access modes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
45  
Outdoor Knight Boiler Installation & Operation Manual  
8 Operating information  
Figure 8-2 Status Display Screen  
B
A
(CALL FOR  
HEAT)  
(BOILER  
STATUS)  
C
(OPERATIONAL  
INFORMATION)  
F
D
(LEFT SELECT  
KEY)  
(RIGHT SELECT KEY)  
E
(NAVIGATION DIAL)  
Status Display Screens  
Section  
Display  
Description  
The unit has not received a call for heat from a remote thermostat nor  
has it received a call for heat from a DHW thermostat.  
STANDBY  
START  
The unit has begun a burn cycle and is checking all safety circuits.  
The unit has initiated a prepurge period on a call for heat.  
PREPURGE  
IGNITION  
The unit has begun a spark period to ignite the main burner.  
The unit has fired and is running at the displayed percentage.  
A
%
(Boiler Status  
Bar)  
The call for heat has been satisfied and the unit runs the fan for an  
additional postpurge period to clear the combustion chamber and  
vent system of residual flue products.  
POSTPURGE  
SHUTDOWN  
The unit has been placed in the OFF position.  
The controlled temperature has exceeded its set point and its offset.  
The unit has detected a condition that has temporarily interrupted  
the current call for heat.  
BLOCKED  
Heat/Loop Demand 1 has a call for heat.  
Heat/Loop Demand 2 has a call for heat.  
Heat/Loop Demand 3 has a call for heat.  
B
The tank thermostat or sensor has a call for heat.  
Indicates which Heat/Loop Demand has priority.  
The unit is being controlled by a 0 - 10V BMS signal.  
The unit is supplying heat while in Cascade Mode.  
(Call for Heat  
Indicators)  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
8 Operating information  
(continued)  
Status Display Screens (cont’d)  
Section  
Display  
Description  
SYSTEM:  
The temperature read by the system supply sensor (if connected).  
TANK:  
The temperature read by the tank sensor (if connected).  
The temperature read by the outdoor sensor.  
OUTDOOR:  
INLET TEMP:  
OUTLET TEMP:  
DELTA T:  
The temperature read at the inlet to the heat exchanger.  
The temperature read at the outlet of the heat exchanger.  
The temperature difference between the inlet and the outlet of the  
heat exchanger.  
FLUE TEMP:  
The temperature read by the flue sensor.  
FLAME CURRENT:  
The current measured by the flame sense circuit.  
FAN SPEED:  
The speed of the combustion blower.  
BOILER PUMP:  
SYSTEM PUMP:  
DHW PUMP:  
The status of the boiler pump output.  
The status of the system pump output.  
The status of the DHW pump output.  
C
(Operational  
Information)  
BMS VOLTAGE:  
The voltage received from a BMS system.  
BLR PUMP OUTPUT:  
The speed signal sent to a variable speed boiler pump in percent.  
SYS PUMP INPUT:  
The speed signal received from a variable speed system pump control.  
RATE OUTPUT:  
SH RUN HOURS:  
SH CYCLES:  
A 0 - 10V signal indicating the firing rate of the boiler.  
The total hours of operation in the Space Heating Mode.  
The total burner cycles in the Space Heating Mode.  
The total hours of operation in the DHW Mode.  
The total burner cycles in the DHW Mode.  
The last 10 lockouts.  
DHW RUN HOURS:  
DHW CYCLES:  
LAST 10 FAULTS NO:  
NIGHT SETBACK  
Shows the next Night Setback trigger (if active).  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
8 Operating information  
Status Display Screens (cont’d)  
Section  
Display  
Description  
Press and hold the LEFT SELECT key for 5 seconds to enter the Menu  
Screen.  
MENU  
EXIT  
Press the LEFT SELECT key to exit the current screen or setting.  
Press the LEFT SELECT key to confirm that the boiler needs to  
shutdown.  
YES  
D
(LEFT SELECT  
key function)  
Press the LEFT SELECT key to enter the screen that allows you to  
adjust the limit settings.  
LIMITS  
HOME  
SKIP  
Press the LEFT SELECT key to return to the Status Screen and upload  
parameter changes.  
Press the LEFT SELECT key when in the Night Setback Screen to  
access the Night Setback Skip Screen.  
Turning the NAVIGATION dial will select the next or previous Status  
Screen.  
Pressing the NAVIGATION dial will show the next fault, NSB (Night  
Setback) trigger, or ramp delay setting.  
Pressing the NAVIGATION dial will select the setting indicated by  
the cursor.  
E
(NAVIGATION  
Dial Function)  
Pressing the NAVIGATION dial will display the Set Points Screen.  
Turning the NAVIGATION dial will move the cursor up or down.  
Turning the NAVIGATION dial will increase or decrease the current  
setting.  
SHDN  
ON  
Press the RIGHT SELECT key to turn the boiler OFF.  
Press the RIGHT SELECT key to turn the boiler ON.  
F
NO  
Press the RIGHT SELECT key to cancel the shutdown operation.  
Press the RIGHT SELECT key to save the current change.  
(RIGHT SELECT  
key function)  
SAVE  
HOME  
Press the RIGHT SELECT key to return to the Status Screen and  
upload parameter changes.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
9 Maintenance  
Maintenance and annual startup  
Table 9A Service and Maintenance Schedules  
Owner maintenance  
Service technician  
(see the Outdoor Knight User’s Information Manual  
for instructions)  
(see the following pages for instructions)  
• Check boiler area  
General:  
• Address reported problems  
• Check pressure / temperature  
gauge  
• Inspect interior; clean and vacuum if  
necessary;  
Daily  
• Clean condensate trap and fill with fresh  
water  
• Check for leaks (water, gas, flue,  
condensate)  
• Verify flue and air openings in good  
condition and free of obstruction  
• Check air and vent termination  
screens  
• Check system water pressure/system  
piping/expansion tank  
• Check relief valve  
Monthly  
• Check control settings  
• Check condensate drain system  
• Check ignition and flame sense  
electrodes (sand off any deposits; clean  
and reposition)  
• Check wiring and connections  
• Perform start-up checkout and  
performance verification per Section 7  
of this manual.  
Periodically  
Test low water cutoff (if used)  
• Flame inspection (stable, uniform)  
• Flame signal (at least 10 microamps at  
high fire)  
• Reset button (low water cutoff)  
• Clean the heat exchanger if flue  
temperature is more than 54°F above  
return water temperature.  
• Check boiler piping (gas and  
water) for leaks  
Every  
6 months  
• Operate relief valve  
If combustion or performance  
indicate need:  
• Clean heat exchanger  
• Remove and clean burner using  
compressed air only  
End  
of season  
months  
Shut boiler down (unless boiler  
used for domestic hot water)  
• Clean the blower wheel  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
9 Maintenance  
Follow the service and maintenance procedures given throughout this manual and in component literature  
shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler  
or system. Failure to follow the directions in this manual and component literature could result in severe  
personal injury, death, or substantial property damage.  
ƽ WARNING  
The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance  
and care of the boiler designated in Table 9A and explained on the following pages must be performed to  
assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could  
result in equipment failure.  
ƽ WARNING  
Electrical shock hazard – Turn off power to the boiler before any service operation on the boiler except as  
noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock,  
causing severe personal injury or death.  
ƽ WARNING  
Address reported problems  
Figure 9-1 Condensate Trap  
RETAINING  
SCREW  
1. Inspect any problems reported by the owner and correct  
before proceeding.  
2” PVC CAP WITH  
BLOCKED DRAIN SWITCH  
Inspect boiler area  
1. Verify that boiler area is free of any combustible materials,  
gasoline and other flammable vapors and liquids.  
PVC TEE ASSEMBLY  
(FACTORY SUPPLIED)  
2. Verify that air intake area is free of any of the contaminants  
listed in Section 1 of this manual. If any of these are  
present in the boiler intake air vicinity, they must be  
removed.  
Inspect boiler interior  
CONDENSATE FROM  
HEAT EXCHANGER  
1. Remove the front access cover and inspect the interior of  
the boiler.  
TO FLOOR  
DRAIN  
The condensate trap must be filled with  
water during all times of boiler operation  
to avoid flue gas emission from the  
condensate drain line. Failure to fill the  
trap could result in severe personal injury  
or death.  
2. Vacuum any sediment from inside the boiler and  
components. Remove any obstructions.  
ƽ WARNING  
Clean condensate trap  
1. Inspect the condensate drain line, condensate PVC  
fittings, and condensate trap.  
Check all piping for leaks  
2. Remove the PVC cap retaining screw from the PVC cap  
(FIG. 9-1).  
Eliminate all system or boiler leaks.  
ƽ WARNING  
Continual fresh makeup water will  
reduce boiler life. Minerals can build  
up in sections, reducing heat transfer,  
overheating heat exchanger, and causing  
heat exchanger failure. Leaking water may  
also cause severe property damage.  
3. Remove the 2 inch PVC cap with the switch located at the  
top of the trap (FIG. 9-1).  
4. Remove any sediment in the trap.  
5. Fill with fresh water until the water begins to pour out of  
the drain.  
1. Inspect all water and gas piping and verify to be leak free.  
6. Replace the cap. Press the cap onto the trap until the cap  
makes contact with the drain.  
2. Look for signs of leaking lines and correct any problems  
found.  
7. Replace the retaining screw.  
3. Check gas line using the procedure found in Section 4  
- Gas Connections.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
9 Maintenance  
(continued)  
Safety relief valves should be re-inspected  
ƽ WARNING  
Flue vent system and air piping  
AT LEAST ONCE EVERY THREE YEARS,  
1. Visually inspect the entire flue gas venting system and air  
piping for blockage, deterioration or leakage. Repair any  
joints that show signs of leakage.  
by a licensed plumbing contractor or  
authorized inspection agency, to ensure  
that the product has not been affected by  
corrosive water conditions and to ensure  
that the valve and discharge line have not  
been altered or tampered with illegally.  
Certain naturally occurring conditions  
may corrode the valve or its components  
over time, rendering the valve inoperative.  
Such conditions are not detectable unless  
the valve and its components are physically  
removed and inspected. This inspection  
must only be conducted by a plumbing  
contractor or authorized inspection  
agency – not by the owner. Failure to  
re-inspect the boiler relief valve as directed  
could result in unsafe pressure buildup,  
which can result in severe personal injury,  
death, or substantial property damage.  
2. Verify that boiler vent discharge and air intake are clean  
and free of obstructions.  
Failure to inspect for the above conditions  
and have them repaired can result in  
severe personal injury or death.  
ƽ WARNING  
Check water system  
1. Verify all system components are correctly installed and  
operational.  
2. Check the cold fill pressure for the system. Verify it is  
correct (must be a minimum of 12 psi).  
3. Watch the system pressure as the boiler heats up (during  
testing) to ensure pressure does not rise too high.  
Excessive pressure rise indicates expansion tank sizing or  
performance problem.  
Following installation, the valve lever  
must be operated AT LEAST ONCE  
ƽ WARNING  
A YEAR to ensure that waterways are  
4. Inspect automatic air vents and air separators. Remove  
air vent caps and briefly press push valve to flush vent.  
Replace caps. Make sure vents do not leak. Replace any  
leaking vents.  
clear.  
Certain naturally occurring  
mineral deposits may adhere to the valve,  
rendering it inoperative. When manually  
operating the lever, water will discharge  
and precautions must be taken to avoid  
contact with hot water and to avoid water  
damage. Before operating lever, check  
to see that a discharge line is connected  
to this valve directing the flow of hot  
water from the valve to a proper place of  
disposal. Otherwise severe personal injury  
may result. If no water flows, valve is  
inoperative. Shut down the boiler until a  
new relief valve has been installed.  
Check expansion tank  
1. Expansion tanks provide space for water to move in  
and out as the heating system water expands due to  
temperature increase or contracts as the water cools.  
Tanks may be open, closed or diaphragm or bladder  
type. See Section 3 - Hydronic Piping for suggested best  
location of expansion tanks and air eliminators.  
Check boiler relief valve  
2. After following the above warning directions, if the relief  
valve weeps or will not seat properly, replace the relief  
valve. Ensure that the reason for relief valve weeping is  
the valve and not over-pressurization of the system due  
to expansion tank waterlogging or undersizing.  
1. Inspect the relief valve and lift the lever to verify flow.  
Before operating any relief valve, ensure that it is piped  
with its discharge in a safe area to avoid severe scald  
potential. Read Section 3 - Hydronic Piping before  
proceeding further.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
9 Maintenance  
Inspect ignition and flame sense Check burner flame  
electrodes  
1. Inspect flame through observation window.  
1. Remove the ignition and flame sense electrodes from the  
boiler heat exchanger access cover.  
2. If the flame is unsatisfactory at either high fire or low fire,  
turn off boiler and allow boiler to cool down. Remove the  
burner and clean it thoroughly using a vacuum cleaner or  
compressed air. Do not use compressed air to clean burner  
if performed inside a building.  
2. Remove any deposits accumulated on the ignition/flame  
sense electrode using sandpaper. If the electrodes cannot  
be cleaned satisfactorily, replace with new ones.  
3. Remove the burner, reference FIG. 9-2 below.  
3. Replace ignition/flame sense electrode, making sure  
gasket is in good condition and correctly positioned.  
4. When replacing the burner, ensure gasket is in good  
condition and positioned correctly (FIG. 9-2).  
Check ignition ground wiring  
1. Inspect boiler ground wire from the heat exchanger  
access cover to ground terminal strip.  
Figure 9-2 Burner Assembly  
2. Verify all wiring is in good condition and securely  
attached.  
3. Check ground continuity of wiring using continuity  
meter.  
AIR / GAS ARM  
4. Replace ground wires if ground continuity is not  
satisfactory.  
INSULATION  
Check all boiler wiring  
HEAT EXCHANGER  
ACCESS DOOR  
1. Inspect all boiler wiring, making sure wires are in good  
condition and securely attached.  
BURNER  
GASKET  
Check control settings  
SCREWS  
(QTY. 5)  
1. Set the SMART SYSTEM control module display to  
Parameter Mode and check all settings. See Section 1 of  
Outdoor Knight Boiler Service Manual. Adjust settings  
if necessary. See Section 1 of the Outdoor Knight Boiler  
Service Manual for adjustment procedures.  
IMG00447  
Check flame signal  
1. At high fire the flame signal shown on the display should be  
at least 10 microamps.  
2. Check settings of external limit controls (if any) and  
adjust if necessary.  
2. A lower flame signal may indicate a fouled or damaged  
flame sense electrode. If cleaning the flame sense electrode  
does not improve, ground wiring is in good condition, and  
ground continuity is satisfactory, replace the flame sense  
electrode.  
Perform start-up and checks  
1. Start boiler and perform checks and tests specified in  
Section 7 - Start-up.  
3. See Section 3 - Troubleshooting of the Outdoor Knight  
Boiler Service Manual for other procedures to deal with  
low flame signal.  
2. Verify cold fill pressure is correct and that operating  
pressure does not go too high.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
9 Maintenance  
(continued)  
11. Close isolation valves on piping to isolate boiler from  
system. Attach a hose to the boiler drain and flush boiler  
thoroughly with clean water by using purging valves to  
allow water to flow through the water make-up line to the  
boiler.  
Review with owner  
1. Review the Outdoor Knight Boiler User’s Information  
Manual with the owner.  
2. Emphasize the need to perform the maintenance  
schedule specified in the Outdoor Knight Boiler User’s  
Information Manual (and in this manual as well).  
12. Perform start-up and check-out procedures in the Check  
Flame and Combustion - Section 7 - Startup on pages 35  
and 37 of this manual.  
3. Remind the owner of the need to call a licensed contractor  
should the boiler or system exhibit any unusual behavior.  
13. Replace the access cover and restore boiler to operation.  
4. Remind the owner to follow the proper shutdown  
procedure and to schedule an annual start-up at the  
beginning of the next heating season.  
Table 9B Heat Exchanger Cleaning Kits  
Kit  
Part  
Component  
Description  
Model  
Cleaning boiler heat exchanger  
Number Number  
For recommended materials; including brush, appropriate  
extension(s), refractory cover, and detailed instructions see  
Table 9B - Heat Exchanger Cleaning Kits.  
CTN20005 Rear Refractory Cover  
MSC20083* Nylon 4" Wheel Brush*  
151  
-
286  
KIT30063  
MSC20084  
3mm Allen Wrench  
1. Shut down boiler:  
MSC20086 1/4" x 24" Drill Extension  
• Follow the “To Turn Off Gas to Appliance” instructions  
for the boiler in Section 7 - Startup.  
• Do not drain the boiler unless it will be exposed to  
freezing temperatures. If using freeze prevention fluid  
in system, do not drain.  
* Do NOT use a metal brush. Only use  
the kit provided brush or an equivalent  
replacement nylon brush.  
ƽ CAUTION  
2. Allow time for the boiler to cool to ambient temperature  
if it has been firing.  
Figure 9-3 Rope Gasket - Heat Exchanger Door  
3. Remove the nuts securing the heat exchanger access  
cover to the heat exchanger and set aside.  
ROPE GASKET  
4. Remove the heat exchanger access cover, burner, and  
gas/air arm assembly.  
The boiler contains ceramic fiber  
ƽ WARNING  
materials. Use care when handling these  
materials per instructions in the Service  
Manual. Failure to comply could result in  
severe personal injury.  
CAUTION: IF GASKET IS DAMAGED  
DO NOT REUSE, THE HEAT EXCHANGER DOOR  
MUST BE REPLACED.  
5. Remove the condensate hose from the heat exchanger  
end. Connect a field supplied 3/4" diameter hose to  
a drain pan. Using field supplied means, cover the  
refractory in the back of the combustion chamber of the  
heat exchanger.  
Rope gasket is intended for sealing combustion  
(FIG. 9-3). If damaged DO NOT reuse, the  
heat exchanger door must be replaced. Consult  
factory for replacement heat exchanger door  
(kit WTR3080).  
NOTICE  
6. Use a vacuum cleaner to remove any accumulation on the  
boiler heating surfaces. Do not use any solvent.  
Oiled bearing circulators  
1. The circulator shipped with the outdoor boiler is water-  
lubricated. No oiling is required.  
7. Brush the heat exchanger while dry using a nylon bristle  
brush. Caution: DO NOT use a metal brush. Re-vacuum  
the heat exchanger.  
2. Check other circulators in the system. Oil any circulators  
requiring oil, following circulator manufacturer’s  
instructions. Over-oiling will damage the circulator.  
8. Finish cleaning using a clean cloth dampened with warm  
water. Rinse out debris with a low pressure water supply.  
9. Allow the heat exchanger to thoroughly dry.  
3. Replace the boiler front access cover.  
10. Remove the field supplied rear refractory cover from the  
back of the combustion chamber of the heat exchanger  
and reassemble.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
10 Diagrams  
Figure 10-1 Ladder Diagram  
JUNCTION BOX  
120VAC  
NEUTRAL GROUND  
TERMINAL STRIP  
120V SUPPLY "L"  
TERMINAL STRIP  
120V SUPPLY "N"  
1
2
INTEGRATED CONTROL  
BLOWER  
3
ON / OFF  
SWITCH  
GND  
KB ONLY  
SYSTEM  
PUMP "L"  
SYSTEM  
PUMP "N"  
X1-1  
X1-6  
F2  
X1-2  
3.15A  
GND  
F1  
5A  
SYSTEM  
PUMP  
BOILER  
BOILER  
PUMP "N"  
SYSTEM PUMP  
RELAY  
PUMP "L"  
X1-4  
X1-3  
BOILER PUMP  
RELAY  
GND  
BOILER  
PUMP  
DHW  
PUMP "L"  
DHW  
PUMP "N"  
DHW PUMP  
RELAY  
F3  
TERMINAL  
STRIP  
TERMINAL  
STRIP  
DHW  
PUMP  
.8A  
24V DC  
SUPPLY  
X5-9  
X5-1  
120 VAC  
24 VAC  
X4-3  
3.5A  
KB 801  
ONLY  
CONNECTION BOARD  
INTEGRATED  
CONTROL  
LWCO  
CN5-5  
FLOW  
CN5-14 X4-8  
CN7-3  
CN7-4  
CN7-2  
SWITCH  
11  
12  
CN5-10  
X4-12  
24 VAC  
CN7-1  
HEAT/LOOP  
DEMAND  
1
CN5-7  
X4-1  
20  
18  
16  
14  
19  
HEAT/LOOP  
DEMAND 2  
CN5-13 X4-9  
17  
HEAT/LOOP  
DEMAND 3  
CN5-6  
X4-2  
15  
13  
TANK  
THERMOSTAT  
CN5-12  
X4-10  
LOW GAS  
PRESSURE  
SWITCH  
HIGH GAS  
PRESSURE  
SWITCH  
X4-11  
X4-5  
CN5-11  
CN5-3  
9
10  
INTEGRATED  
CONTROL  
LOUVER  
RELAY COIL  
5
6
7
24VAC  
LOUVER  
PROVING SWITCH  
CN5-4  
X4-4  
X7  
8
RIBBON CABLE  
X5-2  
KB 286 ONLY  
PC INTERFACE  
BLOCKED  
X5-10  
X5-11  
X2-2  
O-TEMP HEX SW  
DRAIN SWITCH  
X5-6  
X5-4  
S2  
INLET  
SENSOR  
AIR PRESSURE  
SWITCH  
S1a  
S1b  
S3a  
OPERATING  
SENSOR  
1
X5-12  
X5-5  
HIGH LIMIT  
SENSOR  
GAS VALVE  
2
FLUE  
SENSOR  
GAS VALVE  
RELAY  
X2-1  
6
X5-13  
X5-14  
S3b  
FLUE  
SENSOR  
BLOWER  
1
2
4
5
X5-7  
X5-16  
X5-8  
13  
CONNECTION  
BOARD  
CN5-1  
CN5-8  
X4-7  
1
2
ALARM  
CONTACTS  
X4-14  
X5-15  
CN5-2  
CN5-9  
X4-6  
3
4
RUN-TIME  
CONTACTS  
X4-13  
TR2  
CN6  
CN6  
CN6  
X6  
X6  
X6  
S6  
21  
22  
X1-7  
SYSTEM  
SENSOR  
S5  
FLAME ROD  
23  
24  
26  
27  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
OUTDOOR  
SENSOR  
SPARK  
ROD  
CN6  
CN6  
X6  
X6  
S4  
TANK  
SENSOR  
SHIELD  
CAUTION HIGH VOLTAGE SPARK LEAD  
CN6  
X6  
A
CASCADE  
B
CN6  
CN6  
X6  
X6  
NOTES:  
1. Where possible, switches are shown without utilities (gas, water or  
electricity) connected to the unit. As such, actual switch states may  
vary from those shown on diagrams depending upon whether utilities  
are connected or a fault condition is present.  
SHIELD  
CN6  
CN6  
CN6  
X6  
X6  
X6  
BMS  
+
0-10V  
IN  
-
+
-
SYS PUMP  
IN  
2. See wiring diagram for additional notes.  
0-10V  
0-10V  
0-10V  
CN6  
CN6  
X6  
X6  
+
-
BLR PUMP  
OUT  
CN6  
CN6  
X6  
X6  
BOX DEPICTS  
OPTIONAL ITEMS  
+
-
RATE  
OUT  
LOW VOLTAGE  
120 VAC  
HIGH VOLTAGE  
M
O
D
B
U
S
SHIELD  
CN8-1  
CN8-2  
CN8-3  
X6-1  
X6-2  
X4-1  
X9-2  
X9-1  
X9-3  
A
MODBUS  
X4-2  
X4-3  
B
X6-3  
LADDER DIAGRAM  
LBL20148 REV D  
SHIELD  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor Knight Boiler Installation & Operation Manual  
10 Diagrams  
(continued)  
Figure 10-2 Wiring Diagram  
LOW VOLTAGE  
BOX DEPICTS  
120 VAC  
OPTIONAL ITEMS  
HIGH VOLTAGE  
BOX DEPICTS  
DUAL SENSOR  
SINGLE HOUSING  
INTEGRATED  
BOX DEPICTS  
CONTROL  
CONNECTION BOARD  
JUNCTION  
BOX  
OPTIONAL  
ITEMS  
ALARM  
CONTACTS  
1
2
X1-3  
X1-4  
X1-2  
X-7  
OR  
BR  
PR  
L
DHW  
G
G
G
PUMP  
RUN-TIME  
3
W
W
W
N
L
CONTACTS  
4
24 VAC LOUVER  
BOILER  
PUMP  
5
RELAY COIL  
6
N
L
LOUVER  
PROVING SWITCH  
GAS PRESSURE  
SWITCH  
7
BK  
BK  
BK  
BK  
X4-7  
X4-14  
X4-6  
CN5-1  
CN5-8  
CN5-2  
CN5-9  
CN5-3  
CN5-10  
CN5-11  
CN5-4  
CN5-5  
CN5-14  
CN5-12  
CN5-6  
CN5-13  
CN5-7  
SYSTEM  
PUMP  
8
9
N
10  
X4-13  
X4-5  
BK  
KB ONLY  
ON/OFF  
SWITCH  
BK  
BK  
BK  
BK  
X4-12  
X4-11  
X4-4  
L
120V  
SUPPLY  
X1-6  
X1-5  
L
N
BK  
W
GND  
N
FLOW  
SWITCH  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
X4-3  
BK  
X4-8  
BK  
BK  
BK  
BK  
X4-10  
X4-2  
TANK  
THERMOSTAT  
HEAT/LOOP  
X4-9  
X1-8  
X1-1  
G
R
3
2
1
DEMAND  
X4-1  
HEAT/LOOP  
DEMAND  
HEAT/LOOP  
TRANSFORMER  
DEMAND  
RW G  
SYSTEM  
SENSOR  
OUTDOOR  
SENSOR  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
1
2
3
BLOWER  
TANK  
SENSOR  
1
2
3
4
5
SHIELD  
A
CASCADE  
B
SHIELD  
X5-7  
X5-16  
X5-8  
R
T
CN6  
X6  
W
BK  
Y
BMS  
IN  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
+
0-10V  
X5-15  
X5-9  
-
SYS PUMP  
+
0-10V  
IN  
-
BLR PUMP  
X5-1  
BL  
O
+
0-10V  
OUT  
-
KB 286 ONLY  
X5-2  
RATE  
+
O-TEMP HEX SW  
0-10V  
BLOCKED DRAIN SWITCH  
AIR PRESSURE SWITCH  
OUT  
-
X5-10  
X5-11  
X5-4  
P
SHIELD  
A
O/BK  
R/BK  
GY  
MODBUS  
-T  
-T  
OPTION  
B
OPERATING SENSOR S1a  
HIGH LIMIT SENSOR S1b  
SHIELD  
X5-12  
X5-6  
-T  
-T  
-T  
24 VAC  
LOW  
WATER  
CUT-OFF  
CN7-1  
CN7-2  
CN7-3  
CN7-4  
COM  
INLET SENSOR S2  
FLUE SENSOR S3a  
FLUE SENSOR S3b  
P/BK  
W/BK  
PR  
X5-5  
X5-13  
X5-14  
RBLG  
Y
X2-2  
BK  
Y
GAS VALVE  
@24VAC  
O
GY  
G
X4-1  
X9-1  
X9-2  
X9-3  
X9-4  
X2-1  
X1-7  
TR2  
X4-2  
X4-3  
X4-4  
MODBUS BOARD  
MTR-01  
W/R  
FLAME SENSOR  
G
SPARK  
ROD  
SHIELD  
GROUNDING  
JUMPER  
X5-1  
X5-2  
CAUTION HIGH VOLTAGE SPARK LEAD  
BK  
W
G
X1-1  
X1-2  
X1-3  
Notes:  
1. All wiring must be installed in accordance with: local, state, provincial and national code requirements per either N.E.C. in USA or C.S.A. in Canada.  
2. If any original equipment wire as supplied with the appliance must be replaced, it must be replaced with wire having same wire gauge (AWG) and rated for a  
minimum of 105°C. Exceptions: Replacement high voltage spark lead and ribbon cables must be purchased from the factory. Use of a non-approved spark lead  
or ribbon cables can lead to operational problems which could result in non-repairable damage to the integrated controller or other components.  
3. Actual connector block locations may vary from those shown on diagrams. Refer to actual components for proper connector block locations when using  
diagrams to troubleshoot unit.  
WIRING DIAGRAM  
LBL20127 REV  
E
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Revision Notes: Revision A (ECO C11234) initial release.  
Revision B (ECO #C11235) reflects updates made to the freezing  
conditions warnings.  
Revision C (ECO #C11736) reflects changes made to the ratings page  
(page 7).  
OKB-I-O Rev C  
11/12  
Download from Www.Somanuals.com. All Manuals Search And Download.  

KWC Indoor Furnishings K21VB60700A99 User Manual
Lux Products Thermostat PSDH121 User Manual
Magnavox Cassette Player VRZ342AT99 User Manual
Makita Chainsaw DCS230T User Manual
Makita Sander 9207SPB User Manual
Marantz Home Theater System XV 5270 User Manual
Maytag Washer Dryer MD491 User Manual
Melissa Scale 246 031 User Manual
Mellerware Electric Heater 3 5 5 5 02200W User Manual
Metra Electronics Car Stereo System 99 1005 User Manual