Liebert Power Supply GXT2 6000 RT208 User Manual

POWER AVAILABILITY  
USER MANUAL  
GXT2-6000RT208  
120/208V  
120/240V  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
7.1  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
9.9  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURES  
Figure 1  
TABLES  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
WARNING  
!
Opening or removing the cover may expose you to lethal voltages within this unit even when  
it is apparently not operating and the input wiring is disconnected from the electrical source.  
Observe all cautions and warnings in this manual. Failure to do so may result in serious  
injury or death. Refer all UPS and battery service to qualified service personnel. Do not  
attempt to service this product yourself. Never work alone.  
SAVE THESE INSTRUCTIONS  
This manual contains important safety instructions. Read all safety, installation and operating  
instructions before operating the Uninterruptible Power System (UPS). Adhere to all warnings on the  
unit and in this manual. Follow all operating and user instructions. Individuals without previous  
training can install and operate this equipment.  
It is not intended for use with life support and other designated critical devices. Maximum load must  
not exceed that shown on the UPS rating label. The UPS is designed for data processing equipment. If  
uncertain, consult your local dealer or Liebert representative.  
This UPS is designed for use on a properly grounded (earthed), 100/200, 110/220, 115/230, 120/208,  
120/240 or 127/220 VAC, 50 Hz or 60 Hz supply. The factory default setting is 120/208 VAC, 60 Hz.  
Installation instructions and warning notices are located in this manual.  
This UPS is only for use with a four-wire input (L1, L2, N, G).  
This UPS MAY NOT be used with a three-wire, single-phase utility source (L1, N, G).  
ELECTROMAGNETIC COMPATIBILITY—The GXT2-6000RT208 Series complies with the limits  
for a CLASS A DIGITAL DEVICE, PURSUANT TO Part 15 of FCC rules. Operation is subject to the  
following two conditions: (1) This device may not cause harmful interference and (2) this device must  
accept any interference received, including interference that may cause undesired operation. Operat-  
ing this device in a residential area is likely to cause harmful interference that users must correct at  
their own expense.  
Operate the UPS in an indoor environment only in an ambient temperature range of 32°F to +104°F  
(0°C to +40°C). Install it in a clean environment, free from conductive contaminants, moisture, flam-  
mable liquids, gases and corrosive substances.  
This UPS contains no user serviceable parts except the internal battery pack. The Off/Bypass push  
button does not electrically isolate internal parts. Under no circumstances attempt to gain access  
internally other than to replace the batteries due to risk of electric shock or burn. Do not continue to  
use the UPS if the front panel indications are not in accordance with these operating instructions or if  
the UPS performance alters in use. Refer all faults to your local dealer, Liebert representative or the  
Liebert Worldwide Support Group.  
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and  
the required precautions. Keep unauthorized personnel away from the batteries. PROPER DIS-  
POSAL OF BATTERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND REGULATIONS  
FOR BATTERY DISPOSAL REQUIREMENTS.  
Never block or insert any object into the ventilation holes or other openings of the UPS.  
DO NOT CONNECT equipment that could overload the UPS or demand half-wave rectification from  
the UPS, for example: electric drills, vacuum cleaners, laser printers, hair dryers or any other appli-  
ance using half-wave rectification.  
Storing magnetic media on top of the UPS may result in data loss or corruption.  
Turn the UPS off and isolate the UPS before cleaning; use only a soft cloth, never liquid or aerosol  
cleaners. Keep the front and rear vents free of dust accumulation that could restrict airflow.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
When replacing batteries, replace with the same Liebert authorized replacement battery kits.  
CAUTION  
!
Do not dispose of battery or batteries in a fire. The battery may explode.  
Do not open or mutilate the battery or batteries. Released electrolyte is  
harmful to skin and eyes. It may be toxic.  
CAUTION  
!
A battery can present a risk of electrical shock and high short circuit current. The  
following precautions should be observed when working on batteries:  
• Remove watches, rings and other metal objects.  
• Use tools with insulated handles.  
• Wear rubber gloves and boots.  
• Do not lay tools or metal parts on top of batteries.  
• Disconnect charging source prior to connecting or disconnecting battery terminals.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary of Symbols  
1.0 GLOSSARY OF SYMBOLS  
Risk of electrical shock  
Indicates caution followed by important instructions  
!
AC input  
AC output  
Requests the user to consult the manual  
i
+
-
Indicates the unit contains a valve-regulated lead acid battery  
PbH2SO4  
Recycle  
R
DC voltage  
Equipment grounding conductor  
Bonded to ground  
AC voltage  
ON/Alarm Silence/Battery Test  
OFF/Bypass  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Introduction and System Description  
2.0 INTRODUCTION AND SYSTEM DESCRIPTION  
Congratulations on your choice of the Liebert UPStation GXT2-6000RT208 Uninterruptible Power  
Supply (UPS). It provides conditioned power to microcomputers and other sensitive electronic equip-  
ment.  
Upon generation, AC power is clean and stable. However, during transmission and distribution it is  
subject to voltage sags, spikes or complete power failure that may interrupt computer operations,  
cause data loss or even damage equipment. The UPStation GXT2-6000RT208 protects equipment  
from these disturbances.  
The UPStation GXT2-6000RT208 is a compact, on-line UPS. An on-line UPS continuously conditions  
and regulates its output voltage whether utility power is present or not. It supplies connected equip-  
ment with clean sinewave power. Sensitive electronic equipment operates best from sinewave power.  
For ease of use, the UPStation GXT2-6000RT208 features a light-emitting diode (LED) display to  
indicate both load percentage and battery capacity. It also provides self-diagnostic tests, a combina-  
tion ON/Alarm Silence/Battery Test button, a Standby button, user configurable program and two  
levels of alarms when the unit is operating on battery.  
The UPStation GXT2-6000RT208 has an interface port for communication between the UPS and a  
network server or other computer systems. This port provides detailed operating information includ-  
ing voltages, currents and alarm status to the host system when used in conjunction with Liebert’s  
MultiLink™ software. MultiLink software can also control UPS operation remotely.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Description  
3.0 SYSTEM DESCRIPTION  
Dynamic  
Bypass  
Input  
Output  
L1  
L1  
L2  
N
TVSS &  
EMI/RFI  
Filters  
Rectifier  
/PFC  
Inverter  
L2  
N
DC to DC  
Converter  
Battery  
Charger  
Battery  
G
G
3.1  
3.2  
Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters  
These UPS components provide surge protection and filter both electromagnetic interference (EMI)  
and radio frequency interference (RFI). They minimize any surges or interference present in the util-  
ity line and keep the sensitive equipment protected.  
Rectifier/Power Factor Correction (PFC) Circuit  
In normal operation, the rectifier/power factor correction (PFC) circuit converts utility AC power to  
regulated DC power for use by the inverter while ensuring that the waveshape of the input current  
used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:  
• The utility power is used as efficiently as possible by the UPS.  
• The amount of distortion reflected on the utility is reduced.  
This results in cleaner power being available to other devices in the building not being protected by  
the UPStation GXT2-6000RT208.  
3.3  
3.4  
Inverter  
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and  
inverts it into precise, regulated sinewave AC power. Upon a utility power failure, the inverter  
receives energy from the battery through the DC to DC converter. In both modes of operation, the  
UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.  
Battery Charger  
The battery charger utilizes energy from the utility power and precisely regulates it to continuously  
float charge the batteries. The batteries are being charged whenever the UPStation GXT2-6000RT208  
is plugged in, even when the UPS is not turned on.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
System Description  
3.5  
3.6  
3.7  
DC to DC Converter  
The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the opti-  
mum operating voltage for the inverter. This allows the inverter to operate continuously at its opti-  
mum efficiency and voltage, thus increasing reliability.  
Battery  
The UPStation GXT2-6000RT208 utilizes valve-regulated, nonspillable, flame retardant, lead acid  
batteries. To maintain battery design life, operate the UPS in an ambient temperature of 68°F to 77°F  
(20°C to 25°C). Optional external battery cabinets are available to extend battery run times.  
Dynamic Bypass  
The UPStation GXT2-6000RT208 provides an alternate path for utility power to the connected load in  
the unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature or UPS  
failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is  
indicated by an audible alarm and illuminated amber Bypass indicator (other indicators may be illu-  
minated to indicate the diagnosed problem).  
The user may manually transfer the connected load from the inverter to bypass by pressing the  
Standby button once.  
NOTE  
The bypass power path does NOT protect the connected equipment from disturbances  
on the utility supply.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Major Components  
4.0 MAJOR COMPONENTS  
The GXT2-6000RT208 is composed of three major assemblies to provide easier handling, installation  
and versatility.  
4.1  
Main Frame and Electronics  
This 4U cabinet arrives without internal batteries to lighten the UPS for easier installation. Once the  
cabinet has been placed in its final floor or rack position, the internal batteries may be installed. The  
UPS is shipped with a basic hardwire distribution box.  
Figure 1 6 kVA Dual Inverter GXT 2U (front and rear views)  
FRONT VIEW  
REAR VIEW  
StatusIndicators  
®
and Controls  
Intellislot  
Port  
DB-9  
Communications  
Port  
Front Bezels (2)  
Output  
Circuit  
Breaker  
Cooling Fan  
(1 of 4)  
+
+
Grounding  
Electrode  
Conductor  
External Battery  
Connector  
REPO  
Switch  
Input Circuit  
Breaker  
Hardwire  
Knockouts  
Power Distribution Box  
Standard Module  
(See Section 4.3)  
Support Base  
Battery Compartment (behind bezel);  
Internal Battery Pack is shipped loose  
(see Section 4.2)  
4.2  
Internal Battery Pack  
The front bezels may be pulled forward and removed to  
reveal the battery access door. The internal battery pack  
is a compact assembly ready to slide into the battery  
compartment after the front battery access door has been  
opened. Electrical connection is automatic upon  
insertion.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Major Components  
4.3  
Removable Power Distribution Box  
The UPS is shipped with a basic hardwire power distribution pack installed. For maximum flexibility,  
this may be easily replaced with either of two optional power distribution boxes that provide the ben-  
efits of hardwire input and output plus manual bypass switch or plug/receptacle convenience with  
manual bypass switch.  
PD-HDWR  
Power Distribution Box With  
Hardwire Connections  
(Standard - Ships With UPS)  
PD-HDWR-MBS  
Power Distribution Box  
With Hardwire Connections  
and Manual Bypass Switch  
(Optional)  
PD-001  
Power Distribution Box  
With Wired Connections  
and Manual Bypass Switch  
(Optional)  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
What’s Included  
5.0 WHATS INCLUDED  
The GXT2-6000RT208 is shipped with the following items:  
• GXT2-6000RT208 user manual  
• Vertical display overlay  
• Front bezels - 2  
• Top bezels - 2  
• Battery cover grille  
• MultiLink software CD  
• MultiLink serial cable, 10 ft (3m)  
• Rack mount handles  
• Support base - 2  
• GEC ring connector  
• Mounting hardware  
• Configuration program disk  
• Ferrite beads (2)  
!
L1 L2  
BYPASS  
Top bezels  
(tower use)  
UPS ON  
!
Battery cover grille  
BATTERY  
Front bezels  
AC INPUT  
-
+
UPStation GXT  
Vertical  
display  
overlay  
Rack mount  
handles  
MultiLink  
serial cable  
10 ft (3m)  
MultiLink  
software CD  
GXT 2U™ Configuration  
Program  
For use with LiebertGXT2U model UPS  
systems  
Version 1.6  
For Windows 95/98/NT  
To Install:  
Choose the Start button on the Taskbar  
and select Run  
GEC connector  
Support base  
with spacers  
Mounting hardware  
Configuration  
disk  
Ferrite  
beads (2)  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation and Configuration  
6.0 INSTALLATION AND CONFIGURATION  
This section includes instructions on how to install, configure and perform initial electrical checks of  
your UPS installation.  
DO NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until  
Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or  
Liebert representative.  
CAUTION  
!
The UPS is heavy (see 14.0 - Specifications). Take proper precautions when lifting or  
moving it.  
Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place  
it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, cor-  
rosives and other conductive contaminants. Maintain a minimum clearance of 4" (100mm) in the front  
and rear of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C).  
NOTE  
UPS operation in sustained temperatures above 77°F (25°C) reduces battery life.  
6.1  
Install the Main Cabinet  
The GXT2-6000RT208 may be installed either as a tower unit or in a rack, depending on available  
space and use considerations. Determine the type of installation and follow the appropriate instruc-  
6.1.1 Tower UPS Installation  
When using the GXT2-6000RT208 in a tower configuration, use the included support base (shown  
below, left) to stabilize the UPS.  
If any external battery cabinets are added, they will include spacers to accommodate the additional  
cabinets (shown below, right).  
Figure 2 Support base and spacers  
End Bases  
2U Spacer  
Spacers added to support  
4U Support Base  
base to accommodate  
additional battery cabinets  
Attach Bezels to Top  
When used as a tower, the GXT2-6000RT208 requires bezels attached to the top. To connect the  
bezels:  
1. Position the UPS so that the battery compartment is on the bottom.  
2. Attach the top bezels by placing them on the mounting holes and sliding them toward the rear of  
the UPS.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation and Configuration  
6.1.2 Installing the Adjustable Rack-Mount Kit—Sold Separately  
This kit contains parts needed to mount several different models of UPS and external battery cabi-  
nets into EIA310-D standard four-post racks that are 18-32" deep (457-813mm). The weight limit per  
pair of adjustable rack-mounting brackets is 200 pounds (91 kg).  
Parts included are:  
Item  
Quantity  
Rear bracket members  
Front bracket members  
Inner bracket members  
M4 x 8mm machine screws  
M4 locking hex nuts  
2
2
2
16  
8
M5 x 16 mm machine screws  
Grease packet.  
12  
1
Tools needed for installation are:  
• one Phillips screwdriver  
• one 7mm wrench  
The adjustable rack-mounting brackets feature retaining latches to prevent users from inadvertently  
sliding the UPS or battery cabinet out of the rack.  
To install the rack mount brackets:  
Return  
flanges  
1. Unpack two (2) rack-mounting bracket assemblies and  
mounting hardware from this kit. Bracket assemblies are  
interchangeable between left-hand or right-hand.  
Retaining  
Latches  
Remove inner member of each bracket assembly as shown  
in at right by extending it to its outermost position,  
depressing the retaining latch and then pulling the inner  
member out of the bracket assembly.  
2. Determine the height position inside the rack enclosure  
where you want to mount the UPS or battery cabinet.  
Front  
members  
Inner  
members  
CAUTION  
!
Reduce the risk of tipping the rack enclosure by  
placing the UPS or battery cabinet in the lowest  
possible rack position.  
3. Install the rear member of each bracket assembly into rack  
enclosure with two (2) M5 screws provided in this kit (see  
figure at right). The return flanges on the bracket assembly  
fit to the inside of rack mounting rails. Insert screws loosely  
(finger-tight) into the top and bottom holes of the return  
flange on the rear member. Extend the bracket assembly by  
sliding the front member forward until it touches the front  
rack mounting rail. Insert two (2) M5 screws loosely (finger-  
tight) into top and bottom holes of the return flange on each  
front member. Make sure bracket assemblies are at the  
same mounting height on all four (4) rack mounting rails.  
M5 screws  
Front rack  
mounting rails  
Rear rack  
mounting  
rails  
M5 screws  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation and Configuration  
4. Get eight (8) M4 screws and eight (8) M4 nuts from the  
hardware pack in this kit. Each nut has a locking, nylon  
insert that begins gripping the screw when it is halfway  
tight. Make sure to tighten the nut and screw completely to  
ensure locking action.Fasten the rear member and the front  
member together using (4) screws and (4) nuts per bracket  
assembly as shown in at right. For maximum support, insert  
fasteners for each bracket assembly as far apart as possible,  
depending on rack depth, while still joining both members  
(see figures at right). Check alignment of bracket assemblies  
and TIGHTEN ALL SCREWS FROM Steps 2 and 3.  
5. Prepare the UPS or battery cabinet (the “equipment”) for  
rack mounting by following instructions in the equipment’s  
user manual. The equipment may require additional parts to  
be added or parts to be removed for rack mounting. After it is  
prepared, lay the equipment in rack-mounting position.  
Fasten the inner members from Step 1 to the equipment on  
both sides as shown at right with eight (8) M4 screws  
provided in the kit. Make sure retaining latch is near the rear  
of the equipment as shown (see figure at right).  
M4 nuts  
M4  
screws  
18" rack  
depth  
M4 nuts  
M4  
M4 nuts  
screws  
32" rack  
depth  
M4 nuts  
Retaining latch  
6. Open the grease packet provided in the kit. Apply a 1" long  
bead of grease at four (4) places inside the bottom, curved  
tracks of the front members as shown below right. The grease  
will allow the equipment to slide into the bracket assemblies  
more easily.  
M4 screws  
UPS or battery  
cabinet  
CAUTION  
!
Lifting equipment into the rack may be a two-person  
6.  
job, depending on the weight of the equipment. See  
equipment’s user manual.)  
Front  
7. Insert the equipment, with inner members attached in  
Step 5, into the bracket assemblies by inserting the top and  
bottom edges of the inner members into the top and bottom  
curved tracks of the front members and sliding the  
M4 screws  
Apply  
grease  
equipment into the rack (see figure at right). Ends of inner  
members are tapered to allow the rear of the equipment to be  
angled upward before insertion, if space allows.  
UPS or  
battery  
cabinet  
Then the rear, bottom edges of the inner members can be  
placed into the front edge of the bottom tracks and the front  
of the equipment can be tipped up so they are level to insert  
the top edges of the inner members before sliding the equip-  
ment into the rack (see figure below right). The equipment  
should move smoothly into the bracket assemblies. If it does  
not, recheck the alignment of the front and rear members  
from Steps 2 and 3.  
Apply  
grease  
(inside)  
8. Secure the front of the equipment to the rack mounting rails  
to prevent the equipment from sliding out of position. If  
securing holes are provided on the front of the equipment  
that align with the center holes on the return flange of the  
front members, you can use the four (4) extra M5 screws  
provided in the kit to secure the equipment. Otherwise, the  
equipment should be secured to the front of the rack with  
four (4) customer-supplied fasteners.  
... and push it  
into the rack.  
Insert the UPS into the front  
members, lift the front ...  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and Configuration  
6.2  
External Battery Cabinet Installation  
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery  
run time. External battery cabinets are designed to be placed on one side of the UPS or stacked  
beneath the UPS.  
CAUTION  
!
The external battery cabinet(s) are heavy (see 14.0 - Specifications). External battery  
cabinets can be used in rack-mount or tower configuration. Take proper precautions when  
lifting them.  
CAUTION  
!
Verify that the battery cabinet circuit breaker is in the OFF position. Do no energize the  
battery cabinet at this time. When installation is complete, you will be instructed to turn on  
the circuit breaker.  
When the external battery cabinet is received, it should be inspected for freight damage. Report dam-  
age to the carrier and your local dealer or Liebert representative.  
To install an external battery cabinet:  
1. For slide rail installations, first remove the top/side fin by sliding it forward and lifting it up.  
Optional rack-mount handles are shipped with the external battery cabinet and may be installed  
now. (Securing hardware and slide rails are sold separately. Please contact your local dealer or  
Liebert representative for these additional options and any assistance needed.)  
2. Fasten the slides into position with the screws according to the instructions included with the  
slide rails.  
3. Use the enclosed support bases for the tower option to  
prevent the assembly from tipping over. One additional set  
of support base extensions ships with each external battery  
cabinet.  
4. Connect the supplied external battery cabinet cable to either  
of the connectors on the rear of the external battery cabinet,  
Support Base With  
then to the rear of the UPS.  
Spacers for External  
Battery Cabinets  
5. The UPS is now equipped with additional backup battery  
run time. For approximate battery run times, refer to Table  
7 - Battery run times in this manual.  
6. Do NOT turn on the battery cabinet circuit breaker at this  
time. Please complete the remainder of the installation first.  
NOTE  
+
After installation is complete, you must use the included  
configuration program to program the UPS for the  
number of external battery cabinets connected.  
Instructions for using the configuration program follow  
UPS and Four External Battery  
Cabinets With Support Base  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation and Configuration  
6.3  
Connect Input/Output Power  
The UPS ships with the basic hardwire box attached. If an  
optional model is to be used, remove the standard box and  
install the optional box using the three captive mounting  
screws marked in the illustration, below, right.  
Slide  
cover  
over  
connec-  
tors  
6.3.1 Replacing a power distribution box  
Whenever a power distribution box is not attached to a UPS,  
the cover must be slid over the electrical connectors to prevent  
damage or injury.  
1. On the power distribution box attached to the UPS,  
locate the three captive mounting screws holding the box  
to the UPS (see illustration above, right).  
Loosen screws  
to move cover  
2. Turn the screws until the box can be pulled away from the  
UPS. Exercise care to avoid removing screws from the  
hardwire box.  
3. On the replacement power distribution box to be  
attached to the UPS, loosen the cover over the electrical  
connectors by backing out the three screws one turn each.  
4. Slide the cover open to expose the electrical connectors.  
5. Gently retighten the three screws loosened in Step 3.  
6. Align the connectors on the box and UPS.  
7. Push the box into place.  
8. Holding the box firmly against the UPS, tighten the three  
captive mounting screws until the box is secure. Do not  
overtighten.  
Mounting screws  
for removable box  
6.3.2 Distribution Box Electrical Connections  
Electrical connections are made through a removable power distribution box that attaches to the rear  
of the UPS.  
The installer must provide a 30A branch circuit breaker. The input circuit breaker on the distribution  
box and the output circuit breaker on the rear fixed-panel of the UPS disconnect all power between  
the main cabinet and the distribution box.  
Models equipped with a manual bypass switch pass utility power directly to the bypass switch from  
the input terminal block. The input circuit breaker on the distribution box does not disconnect power  
from the manual bypass switch.  
Figure 3 30A branch circuit breaker connection diagram  
PD-HDWR Distribution Box  
PD-HDWR-MBS Distribution Box  
Input  
Input  
Utility  
30A External  
Utility  
Byp  
Output  
Output  
30A External  
Branch Circuit  
Breaker  
30A Input  
Circuit  
Breaker  
30AInput  
Circuit  
Inv  
Branch Circuit  
Breaker  
Breaker  
30A UPS Output  
Circuit Breaker  
30A UPS Output  
Circuit Breaker  
UPS - PFC, Battery, Inverter  
UPS - PFC, Battery, Inverter  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation and Configuration  
6.3.3 PD-HDWR and PD-HDWR-MBS Terminal Block Connections  
Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not  
share the same conduit.  
Table 1  
Electrical requirements—PD-HDWR and PD-HDWR-MBS  
Input Current Recommended (Max.)  
Recommended Wire  
(including ground wire)  
(75°C copper wire)  
Maximum Wire  
Accepted by  
Terminal Block  
Terminal  
Tightening  
Torque  
Rating  
24A  
External Overcurrent  
Protection  
30A  
10 AWG  
8 AWG  
20 in-lb  
The standard PD-HDWR comes installed on the UPS. The PD-HDWR-MBS with manual bypass  
switch is optionally available. Both have the same hardwire terminal connections.  
N
L2  
L1  
N
L2  
L1  
30A Max. Branch  
Overcurrent Protection  
OUTPUT  
INPUT  
8-10 AWG - USE COPPER WIRE ONLY - 20 in-lb - Strip 7mm  
N
L2  
L1  
N
L2  
L1  
0
0
Output to Load - See Note 1  
Input to UPS - See Note 2  
NOTE  
1. The installer must provide circuit breaker protection according to local codes. The utility  
disconnect should be within sight of the UPS or have an appropriate lock-out. Maintain  
service space around the UPS or use flexible conduit.  
2. The installer must provide output distribution panels, circuit breaker protection or  
emergency disconnects according to local codes. Output circuits must not share a common  
conduit with any other wiring.  
For best performance, distribute all L-N loads evenly between L1 and L2.  
6.3.4 PD-001 Power Distribution Box  
Output  
Receptacles  
An optional PD-001 is available to provide the conve-  
nience of an L14-30P input plug and output receptacles.  
To use this box, remove the original PD-HDWR hardwire  
Manual  
Bypass  
Switch  
box and install the PD-001.  
Table 2  
Electrical requirements—PD-001  
Recommended (Max.)  
Input Current  
Rating  
External Overcurrent  
Protection  
Required Utility  
Receptacle  
24A  
30A  
NEMA L14-30R  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Installation and Configuration  
6.4  
Install the Grounding Electrode Conductor  
A Grounding Electrode Conductor must be attached to the rear panel using the M5x12 Phillips screw  
provided. This connection is required in addition to the power input ground connection to the remov-  
able power distribution box.  
2
Install an 8 AWG (10 mm ) (75°C copper wire) (minimum size, see NEC 250-5d, 250-81, 250-83, table  
250-94) grounding electrode conductor to the nearest effectively grounded metal structural member,  
nearest effectively grounded metal water pipe or other grounding electrode in the grounding electrode  
system. If the grounding electrode conductor must be protected, non-metal conduit is recommended. If  
metal conduit must be used, bond both ends of the conduit to the grounding electrode conductor. Con-  
duit is not an acceptable grounding electrode conductor.  
A 5mm ring lug for 8AWG wire lug is provided in the accessory box. Other suitable connectors may be  
used.  
Ground Electrode System  
or Protective Earth System  
NOTE  
IN BATTERY MODE ONLY, the UPS operates as a separately derived source and contains a  
neutral to ground bonding jumper. A grounding electrode conductor (GEC) must be installed  
in accordance with national and local wiring codes and regulations.  
6.5  
Install the Internal Battery Pack  
To facilitate shipping and installation, the GXT2-6000RT208 ships  
without the internal battery installed. Once the UPS is installed in  
place, the internal battery pack must be installed.  
Controls  
and  
Indicators  
1. Unpack the internal battery from its shipping container.  
2. Lift the battery pack from its container, holding it in the center  
Screws  
for battery  
door  
of the pack. Do NOT lift the battery pack by grasping the  
connector on the rear.  
3. Align the battery pack so that the rear connector is nearest the  
control panel.  
Battery  
Compartment  
4. Slide in the battery pack until fully inserted.  
5. Install the battery door, tightening the two captive screws, finger  
tight. The battery door will not install if the battery is not fully  
inserted.  
Liebert  
!
6. For tower installation, place the horizontal overlay over the  
controls and indicators (see illustration at right).  
Battery  
Battery cover  
7. Install the two front bezels.  
!
Front bezels  
Back of  
battery  
Battery  
connector  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Initial Startup and Electrical Checks  
7.0 INITIAL STARTUP AND ELECTRICAL CHECKS  
Initial Startup and the Configuration Program—The UPS ships with a default 120 VAC L-N  
setting. This is also the most robust setting in that it can operate with either input phase angle (120  
or 180 degrees). Perform initial system checks first. If the UPS configuration needs to be modified for  
your application, then go to the next section to review use of the configuration program. Some config-  
uration changes require that the UPS be in the OFF mode while powered from the utility. Therefore,  
the installer must confirm that the UPS input has been properly wired. After re-configuring your  
UPS, the UPS may be put into service with the intended loads.  
Hardwire Input Connections (For L14-30P Plug-in Connections, skip to 7.1 - L14-30P Plug-in Con-  
WARNING  
!
Miswiring power to the input terminal block (L1-L2-N-G) or connecting to single phase  
voltages (L-N-G only) may damage the UPS.  
1. Verify that the Input and Output circuit breakers are off.  
2. During initial system checks, disconnect all loads (open load disconnects).  
3. Inspect all wiring, cables and connection.  
4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted  
in the sockets. Turn on the battery cabinet circuit breaker now.  
5. If you are using a distribution box that includes a manual bypass switch, place the switch in  
BYPASS position.  
6. Turn on the branch circuit disconnect to apply voltage to the input terminal block.  
7. Using a voltmeter, verify the expected L1-N, L2-N and L1-L2 voltages.  
a. If no manual bypass switch is used, there will be no output voltage at this time. If a manual  
bypass switch is used, verify that the same voltages appear at the Output terminals. If a  
manual bypass switch is used, the Bypass lamp will light by the switch. If no manual bypass  
switch is used, there will be no output voltage at this time.  
b. If the configuration program has been used to set the L-N voltage at 100, 110 or 115, then the  
input phase angle is required to be 180 degrees.  
c. If the configuration program as been used to set the L-N voltage at 127 VAC, then the input  
phase angle is required to be 120 degrees (leading or lagging).  
8. After verifying proper input voltage to the UPS terminal block, turn off the branch circuit power,  
close all access panels to the distribution box and reapply input power.  
9. Close the Input circuit breaker located on the distribution box. The green AC Input indicator  
should illuminate on the front panel.  
10. Press the On button for 1 second. The Bypass indicator will light for several seconds before the  
UPS ON indicator turns on continuously. If the batteries are determined to charged above 80%,  
an automatic battery test will run for about 15 seconds.  
11. Close the Output circuit breaker on the rear of the UPS. If a manual bypass switch is used, the  
UPS Available indicator by the switch will light. If a manual bypass switch is used, transfer the  
switch to the UPS position. The output terminal block will be powered at this time.  
12. Perform a Manual Battery Test - Press the On button for one (1) second. The front Battery  
indicator will light for about 15 seconds and then return to only the UPS ON and AC Input  
indicators being illuminated.  
13. Review all setting option provided by the configuration program. Some changes require that the  
UPS be OFF. If this is the case, these should be programmed before powering the loads. The  
configuration program is described in the next section.  
14. Connect all loads for normal operation.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Initial Startup and Electrical Checks  
7.1  
L14-30P Plug-in Connections—Including the PD-001 Distribution Box  
WARNING  
!
Miswiring power to the input (L1-L2-N-G) or connecting to single phase voltages (L-N-G only)  
may damage the UPS. A qualified electrician should verify that the L14-30R is properly wired  
before attaching the UPS.  
If the configuration program has been used to set the L-N voltage at 100, 110 or 115, then the input  
phase angle is required to be 180 degrees.  
If the configuration program as been used to set the L-N voltage at 127 VAC, then the input phase  
angle is required to be 120 degrees (leading or lagging).  
1. Verify that the input and output circuit breakers are off.  
2. During initial system checks, unplug all loads (or open load disconnects).  
3. Inspect all wiring, cables and connection.  
4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted  
in the sockets. Turn on the battery cabinet circuit breaker.  
5. If you are using a distribution box that includes a manual bypass switch, place the switch in  
BYPASS position.  
6. Plug in the UPS input plug.  
7. Turn on the branch circuit disconnect to apply voltage to the UPS input.  
8. If no manual bypass switch is used, there will be no output voltage at this time. If a manual  
bypass switch is used, the Bypass lamp will light by the switch  
9. Close the input circuit breaker located on the distribution box. The green Line lamp should  
illuminate on the front panel.  
10. Press the Start button for 1 second. The Bypass lamp will light for several seconds before the  
Inverter lamp turn on continuously. If the batteries are determined to charged above 80%, an  
automatic battery test will run for about 15 seconds.  
11. Close the output circuit breaker on the rear of the UPS. If a manual bypass switch is used, the  
Inverter lamp by the switch will light. If a manual bypass switch is used, transfer the switch to  
the Inverter position. The output terminal block will be powered at this time.  
12. Perform a Manual Battery Test by pressing the ON button for 1 second. The front Battery lamp  
will light for about 15 seconds and then extinguish, leaving only the Inverter and Line lamps  
illuminated.  
13. Review all setting option provided by the configuration program. Some changes require that the  
UPS be OFF. If this is the case, these should be programmed before powering the loads. The  
configuration program is described in the next section.  
14. Connect all loads for normal operation.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Configuration Program  
8.0 CONFIGURATION PROGRAM  
The final step of installation may require custom configuration of your UPS using the enclosed config-  
uration program. Some configuration settings may be changed only while the UPS is off. These should  
be set before the UPS is put into full time service powering the critical load.  
For most users operating with 120 VAC L-N and with no external batteries, the factory default set-  
tings will be adequate. This manual illustrates the features available for modification, as well as the  
factory default setting.  
The factory default L-N setting is 120 VAC. When first powered by the AC input, the UPS will auto-  
sense the utility phase angle between L1 and L2, setting the UPS to operate as either a 120/208 VAC  
system (120 degrees, leading or lagging) or a 120/240 VAC system (180 degrees).  
If your application requires that the L1-N, L2-N voltages be set at 100, 110, 115 or 127 VAC, the cor-  
responding phase angle between L1 and L2 is restricted. The VAC settings of 100, 110 and 115 may  
work only with a phase angle of 180 degrees. A VAC setting of 127 VAC will work only with a phase  
angle of 120 degrees (leading or lagging).  
To confirm the phase angle of the utility input, measure the L1-N, L2-N and L1-L2 VAC of the utility  
input that is intended for the UPS. If the measured L1-L2 voltage is equal to the average L-N voltage  
times 2.0, then the phase angle is 180 degrees and the L-N VAC may be set at 100, 110, 115 or 120  
VAC. The nominal L1-L2 voltages for these four settings will be 200, 220, 230 or 240 VAC, respec-  
tively.  
If the measured L1-L2 voltage is equal to the average L-N voltage times 1.73, then the phase angle is  
120 degrees and the L-N VAC may be set at either 120 or 127 VAC. The nominal L1-L2 voltages for  
these two settings will be 208 or 220 VAC, respectively.  
Selecting a L-N nominal voltage that is not compatible with the L1-L2 phase angle detected by the  
UPS when AC input is applied will result in a fault alarm and the UPS will not operate from utility  
power.  
8.1  
GXT2-6000RT208 Configuration Program Features  
The configuration program enables the user to perform the following functions:  
• Select one of five L-N output voltages to match local voltages  
• Enable or disable Auto-Restart  
• Select frequency converter operation with a fixed output frequency of 50 or 60 Hz  
• Set the Low Battery Warning alarm time from 2 to 30 minutes  
• Enable or disable the Auto-Battery test  
• Set the Auto-Battery test to 7, 14, 21 or 28 days  
• Specify the number of external battery cabinets connected to the UPS to adjust the remaining run  
time calculations reported by Liebert software products  
• Modify the shutdown setting of DB-9 pin 6 (for information on pin assignments, see 11.0 - Com-  
8.1.1 What You Will Need  
In addition to the GXT2-6000RT208 UPS, you will need the configuration program diskette and serial  
cable (beige or tan, three-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) included in the UPS  
®
accessory box. A computer—desktop or laptop—running Windows 95 or later is also required to set  
up and run the configuration program.  
!
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Configuration Program  
8.2  
Configuration Program—Installation  
An easy-to-use installation program will streamline the installation of the configuration program. If  
you have a previous version of this configuration program installed, it is recommended that it be  
uninstalled using its Uninstall program before installing this updated version.  
1. Use the Windows Explorer to find and open the Lbt_gxt2-1.6.exe installation program on the  
included software CD.  
2. When you see this PreSetup window, select OK. This will open the main installation screen.  
3. Click NEXT to continue installing the configuration program.  
Liebert recommends using the default installation options, but you will be given the option to make  
modifications to the standard entries.  
The installation program will also install an Uninstaller program along with the UPS configuration  
program.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Configuration Program  
8.3  
Establishing Communication Link with the UPS  
Use only the serial communication cable supplied with the configuration program. If an accessory  
communication card has been installed in the UPS’s communication card slot, the option card must be  
removed while using the configuration program.  
Use the serial communication cable to connect your computer’s COM1 port to the DB-9 communica-  
tion port on the rear of the UPS. COM2 may also be used. If the COM port of the host computer has  
only a DB-25 pin connector, a DB-25 to DB-9 adapter must be added.  
The program may be used while the UPS is on to read and confirm the current settings. The UPS  
must be off and powered by the AC utility when using the configuration program to change any UPS  
setting. Any attempt to change a setting while the UPS is on will result in an error message.  
Select Lbt_gxt2.exe from the program group to start the configuration program. The program will  
search COM1 & COM2 for a properly connected GXT 2U™ UPS. When the UPS is found, the opening  
program window will display the UPS model.  
If the configuration program ever fails in its attempt to read data from a UPS, the error message  
below will be displayed. The program must communicate with the UPS when it first opens, when a  
new tab is opened and when the REFRESH, APPLY or OK buttons are pressed.  
If this message is displayed, check the following items:  
1. Verify that the serial communication cable is connected properly.  
2. Verify that the COM port being used is designated COM1 or COM2.  
3. Verify that the UPS is either in Inverter mode, Bypass mode, Battery mode or Off with AC power  
available at the input (AC Input indicator on). In all cases, the rear fan will be running.  
4. Verify that the COM port is not in use by other UPS communication software (or non-UPS  
software). If MultiLink UPS software is installed on the computer, the MultiLink service must be  
stopped to free the COM port. MultiLink typically restarts automatically whenever the computer  
restarts.  
5. The UPS serial port is in use by an internal, optional communication card in the UPS card slot.  
Remove the option card.  
6. The program is connected to a UPS that was not designed for this program.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Configuration Program  
8.4  
Configuration Program—Operation  
8.4.1 Read/Confirm UPS Configuration Settings  
The UPS settings may be monitored, but not changed, using the configuration program while the UPS  
is operating in any mode. If the program is only used to read the present UPS settings, close the pro-  
gram using the CANCEL button.  
Mistakenly using the APPLY or OK button  
will attempt to write data to the UPS and will  
result in the error message shown at right if  
the UPS is not off.  
If this message is displayed and you do not  
wish to change any settings, close this error  
message and close the configuration program  
using the CANCEL button.  
If the UPS is off and you do not wish to risk changing any settings, close the program using the CAN-  
CEL button. Do not use the APPLY or OK buttons in the configuration program.  
8.4.2 Changing UPS Settings  
UPS SETTINGS MAY ONLY BE CHANGED USING THE CONFIGURATION PROGRAM WHEN  
THE UPS IS OFF AND NO POWER IS BEING DELIVERED TO THE LOAD. AC input power must  
be available to power the UPS logic during programming. Only the AC Line indicator will be on indi-  
cating utility input power.  
To turn the UPS off to change configuration settings, press the UPS OFF/Bypass button twice within  
four seconds (hold the button one second each time). This will disconnect all power to the load.  
Changing any value or selecting/deselecting any setting in the configuration window will not immedi-  
ately change the settings in the UPS. You may modify the displayed settings until you are satisfied  
with the new proposed changes. Settings displayed by the configuration program can always be  
restored to the existing values stored in the UPS by selecting the REFRESH key.  
Values displayed will be transmitted to the UPS only  
when either the APPLY or OK button is selected. The  
APPLY button sends the new settings to the UPS without  
closing the program. The OK button sends the new set-  
tings and closes the program.  
Whenever data is successfully transmitted to the UPS,  
this message shown at right will be displayed.  
8.4.3 Programming Rejected?  
If the UPS appears to be off but this error  
message is displayed when the APPLY or OK  
button is selected to transmit settings, the  
UPS may be in an intermediate standby con-  
dition.  
To confirm that the UPS is fully off, repeat the  
turn off procedure. Press the UPS OFF/  
Bypass button twice within four seconds (hold  
the button one second each time).  
8.4.4 Exit Without Changing UPS Settings  
If you decide not to change the UPS after modifying the displayed settings, close the configuration  
program using the Cancel button.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Configuration Program  
8.5  
UPS Tab  
When the program starts, the following window will open displaying the UPS model along with the  
current UPS settings. This information can be updated at any time using the REFRESH button.  
Figure 4 Factory default settings for 120VAC UPS  
8.5.1 Output Voltage  
The Output Voltage displayed is the nominal input/output voltage. This is not a voltmeter and will  
display the nominal voltage whether the UPS is on or off. The drop down box will show the alternate  
voltages available. Select the voltage that matches the nominal utility in your location.  
8.5.2 Auto Restart  
The UPS will provide computer grade power during power outages. If input power is unavailable for  
an extended time, the UPS will shut down when batteries are depleted or a shutdown signal is sent by  
the computer operating system to limit battery depletion (serial data or contact closure). If Auto  
Restart is enabled (check mark in box), the UPS will restart when input power is restored. If the UPS  
turns off power to the load for any other reason, manual restart is required (See 8.6 - Options Tab  
for exceptions). Click on the box to remove the check mark and disable Auto Restart.  
8.5.3 L-N Reverse Detection (120V UPS Models Only)  
Proper wiring of the receptacle powering the UPS is critical for safety, EMI suppression and surge  
suppression. The UPS checks the outlet when first plugged in. If the Line-Neutral is reversed or the  
ground is missing, the UPS will not start. If a problem is detected after the UPS is started, the UPS  
will continue to operate, but the AC Input indicator will flash. In some unique applications the user  
may wish to disable this alarm. Except for special situations, improperly wired receptacles should be  
immediately repaired before the UPS is put into service. Click on the box to remove the check mark  
and disable this alarm.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Configuration Program  
8.5.4 Frequency Selection  
The UPS is normally designed for 50Hz or 60Hz operation. The factory default corresponds to the  
model. All models are capable of being used as 50Hz or 60Hz systems. The UPS will automatically  
sense the utility frequency when first plugged in and set the nominal frequency to match. Therefore,  
for all normal use the Auto Sense button should be selected.  
Some special applications require that the UPS be used as a frequency converter. Frequency con-  
verter 50Hz or frequency converter 60Hz may be selected.  
Note that frequency converter operation disables the Bypass. If, for any reason, the UPS inverter is  
unable to power the load, the alternate bypass to utility power will not be available and power will be  
removed from any load.  
8.6  
Options Tab  
Computer users may choose to use versatile com-  
puter shutdown software that communicates  
with the UPS via a serial communications cable.  
The Options tab should not be used to modify the  
UPS functions for such applications.  
For some industrial applications and special  
computer applications, the UPS may be moni-  
tored and controlled using external voltages and  
relay contact signals. The Options tab expands  
the UPS versatility for such applications.  
Refer to your UPS manual for a description of the  
9-pin communication connector on the rear of the  
UPS. Pin 6 of the 9-pin communication connector  
is used for “Any Mode Shutdown” of the UPS out-  
put. This control input may be used in special  
applications to disable the UPS output power -  
both Inverter and Bypass.  
The Options tab allows the behavior of the Any  
Mode Shutdown feature to be modified.  
When the program opens or the REFRESH but-  
ton is pressed, the UPS setting is read by the  
configuration program and displayed.  
Factory Default Setting Illustrated - This  
Options tab illustration shows the available  
function definitions using pin 6 and the factory  
default settings.  
WARNING  
!
Auto-Enable Output  
Note that when this option is selected and the UPS output is disabled using Pin 6, the UPS  
output can turn on automatically and without warning if the Pin 6 connection is changed.  
WARNING  
!
Pin 6 Logic  
DO NOT CHANGE THIS OPTION from the factory default setting unless you are ready to  
install a normally-closed connection between Pins 5 & 6. This connection must be maintained  
to use the UPS or to use the configuration program again, including the ability to change the  
UPS setting back to the default setting using the configuration program via a serial  
communication link.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Configuration Program  
8.7  
Options Tab Used With Earlier GXT 2U Models  
This version of the configuration program will accompany GXT 2U UPS models that support new pro-  
gramming features accessible using the Options tab.  
If version 1.6 (or later) is used with an earlier GXT 2U model (with an earlier UPS firmware version),  
the Any Mode Shutdown features cannot be changed.  
If the configuration program is used with an earlier UPS model (with an earlier UPS firmware ver-  
sion) that does not support the modification of these settings, the Options tab will display a reminder  
of the factory default settings, as shown. These cannot be changed.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Configuration Program  
8.8  
Battery Tab  
Factory default settings illustrated.  
The boxes on the right show the available options using the drop-down selection boxes.  
8.8.1 Low Battery Time Warning  
The UPS will estimate remaining operating time when on batteries. A low battery alarm is activated  
if the estimated time reaches the Low Battery Time. This may be changed to any value from 2 to 30  
minutes.  
8.8.2 Auto Battery Test Time  
The UPS performs an automated battery test periodically, if enabled. The user may also select time  
periods of 7, 14, 21 and 28 days.  
8.8.3 Battery Cabinets Number  
If additional batteries are attached to the UPS, accurate battery runtime estimates are possible if the  
battery number and type of batteries are entered here. The new UPS models are designed to operate  
with up to four external battery packs or four long runtime battery packs (not currently available).  
8.8.4 Auto Battery Test  
In some applications it may be preferable to disable the automated, periodic battery test. Click on the  
box to remove the check mark and disable the periodic battery test.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Configuration Program  
8.9  
About Tab  
The version number of the configuration program may be confirmed using the About Tab.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Controls and Indicators  
9.0 CONTROLS AND INDICATORS  
All indicators lit for illustrative purposes.  
L1 L2  
BYPASS  
UPS ON  
!
Vertical overlay  
for tower  
BATTERY  
installation  
AC INPUT  
- +  
UPStation GXT  
Horizontal overlay for rack mounting  
9.1  
ON/Alarm Silence/Battery Test Button  
This button controls output power to connected load(s) and has three functions:  
• ON  
• Alarm Silence  
• Manual Battery Test  
ON - Pressing this button will start up the UPS in order to provide conditioned and  
protected power.  
Alarm Silence - To silence alarms, press this button for at least one Second. After the  
alarm is silenced, the UPStation GXT2-6000RT208 will reactivate the alarm system to  
alert of additional problems.  
NOTE  
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.  
Manual Battery Test - To initiate a manual battery test, press the ON/Alarm Silence/Battery Test  
button for at least one second while operating from utility power with no alarm conditions present.  
• If only three of the five Battery indicators illuminate, allow the UPS to recharge the batteries for  
24 hours.  
• After 24 hours, retest the batteries.  
• After the batteries have been retested, if only three of the five Battery indicators illuminate, con-  
tact your local dealer, Liebert representative or Liebert Worldwide Support Group.  
9.2  
OFF/Bypass Button  
This button controls output power to connected load(s) and has dual functions: OFF  
and Bypass.  
CAUTION  
!
Pressing the OFF/Bypass button once will cause the load to be  
transferred to bypass power. Pressing the OFF/Bypass button a second  
time within 4 seconds will result in loss of power to the output  
receptacles and connected loads. Perform all necessary shutdown  
procedures on connected loads before pressing this button twice.  
Pressing the OFF/Bypass button twice within 4 seconds shuts off power to the output receptacles and  
connected loads, but the UPS’s circuits remain live, charging the unit’s battery.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Controls and Indicators  
9.3  
9.4  
L1 & L2 Load Level Indicators (Two Rows of Indicators: 4 Green, 1 Amber)  
The Load Level indicators display the approximate electrical load placed upon both output legs of the  
UPS at all times. Each indicator represents an approximate 25 percent increase in load. For optimum  
utilization of the UPS, distribute L-N loads to approximately balance the loads on L1 and L2.  
Battery Level Indicators (5 Green)  
The Battery Level indicators display approximate battery capacity at all times. Each indicator repre-  
sents an approximate 20 percent increase in battery capacity.  
The UPStation GXT2-6000RT208 is equipped with automatic and remote battery test features. The  
automatic test occurs every 14 days (this option is user-configurable) if utility has not been inter-  
rupted. Should the battery fail this test, the red Fault indicator along with the A and C diagnostic  
indicators will illuminate and an alarm will sound (refer to 13.0 - Troubleshooting). The remote  
test feature functions with MultiLink 3 software and can remotely initiate the battery test.  
9.5  
9.6  
9.7  
Fault Indicator (Red)  
The Fault indicator is illuminated if the UPS has detected a problem. Also, one or more of the Battery  
Level indicators may be illuminated (refer to 13.0 - Troubleshooting section).  
Bypass Indicator (Amber)  
The Bypass indicator is illuminated when the UPS is operating from bypass power. An alarm will  
sound indicating the UPS detected a problem or the manual bypass function has been activated.  
UPS ON Indicator (Green)  
The UPS ON indicator is illuminated when the UPS inverter is operating and supplying power to  
your connected loads.  
9.8  
9.9  
Battery Indicator (Amber)  
The Battery indicator is illuminated when the UPS is operating on battery.  
AC Input Indicator (Green)  
The AC Input indicator is illuminated when utility power is available and within the input specifica-  
tions.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Modes of Operation  
10.0 MODES OF OPERATION  
10.1 Normal Mode Operation  
During normal operation, utility power provides energy to  
the UPS. The filters, power factor correction circuit and the  
inverter process this power to provide computer grade  
power to connected loads. The UPS maintains the batteries  
in a fully charged state. The four green Load Level indica-  
tors display an approximate level of load in 25% increments.  
If the UPS becomes loaded beyond full rating, the fifth  
(amber) indicator will illuminate and the UPS will sound an  
audible alarm. The display template indicates the percent-  
age of load (see example at right) on the UPS output.  
Normal Mode Operation  
Batteries at 100% charge  
L1 Load at 10%, L2 Load at 90%  
10.2 Battery Mode Operation  
Battery mode occurs in event of an extreme input voltage  
condition or complete utility failure. The battery system  
supplies power through the DC to DC converter to the  
inverter to generate power for the connected load. During  
battery mode an alarm sounds every 10 seconds. This will  
change to two beeps every 5 seconds when the battery runs  
low (approximately 2 minutes remaining, but this is user  
configurable). The AC Input indicator will extinguish and  
the Battery indicator will illuminate to warn that a utility  
problem has occurred. Each Battery Level indicator repre-  
sents a 20% capacity level. As capacity decreases, fewer  
indicators remain illuminated. Refer to 13.0 - Trouble-  
shooting. For approximate battery run times, refer to  
Table 7 - Battery run times. These times are approximate  
Battery Mode Operation  
Batteries at 30% charge  
L1 Load at 60%, L2 Load at 60%  
based on resistive load and an ambient temperature of 77°F (25°C). To increase this time, turn off  
non-essential pieces of equipment (such as idle computers and monitors) or add the optional external  
battery cabinet.  
CAUTION  
!
Turning OFF the UPS while in battery mode will result in loss of output power.  
10.3 Battery Recharge Operation  
Once utility power is restored, the UPS resumes normal operation. At this time, the Battery Charger  
begins recharging.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Communications  
11.0 COMMUNICATIONS  
11.1 Communications Interface Port  
The UPStation GXT2-6000RT208 UPS has a standard DB-9 serial port female connector located on  
the rear of the UPS unit. Several signals are provided on this port and are assigned as follows:  
Table 3  
DB-9 pin assignment  
DB-9 Assignment Description  
Pin  
1
2
3
4
5
6
7
8
9
Low Battery (open collector)  
UPS TxD (typically RS-232 levels)  
UPS RxD (typically RS-232 levels)  
Remote Shutdown (5-12VDC, 10-24mA max; battery operation)  
Common  
Remote Shutdown (short to pin 5); all modes of operation  
Low Battery (open emitter)  
Utility Fail (open emitter)  
Utility Fail (open collector)  
Pin Assignment  
Collector to Emitter*  
Open  
Collector  
6
7
8
9
(+)  
(-)  
330 Ohms  
Open  
Emitter  
1
2
3
4
5
* Maximum voltage and current on pins 1, 7, 7 and 9 are 60VDC and 10.0 mA  
11.1.1 DB-9 Interface Port  
Using the following directions to attach the smaller enclosed ferrite  
bead clamp to the communication cable as shown at right:  
1. Open the ferrite bead.  
2. Place the communication cable inside the ferrite bead groove.  
3. Position the ferrite bead as close as possible to the end of the cable  
that connects to the DB-9 connector of the UPS.  
4. Close the ferrite bead so that the ferrite bead’s case snaps closed  
with the cable routed through the ferrite bead’s case.  
Run cable  
through ferrite  
bead case  
11.1.2 Communications SNMP Web Card SNMP Adapter  
Attach the larger enclosed ferrite bead clamp to the network  
cable, see illustration at right, using the following directions:  
1. Open the ferrite bead.  
2. Place the network cable inside the ferrite bead groove.  
3. Wrap the cable once around the ferrite bead.  
4. Position the ferrite cable as close as possible to the end of  
the cable that connects to the UPS.  
5. Close the ferrite bead so that the ferrite bead’s case snaps  
Wrap network  
cable around  
ferrite bead  
closed with the cable routed through the ferrite bead’s case.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Communications  
11.2 Pin 4 - Remote Shutdown on Battery  
1. This pin is functional only when the UPS is in battery mode. If the UPS is being powered by the  
utility, Pin 4 will ignore any signal on this pin.  
2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using  
Liebert’s contact closure cable. It cannot be used with just a contact closure unless the relay is  
used to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to signal  
a shutdown. Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a shutdown  
signal for 1.5 seconds, the command cannot be canceled.  
3. A battery shutdown signal on Pin 4 will NOT cause an immediate Shutdown. A shutdown signal  
will start a 2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the UPS will  
shut down.  
4. If the utility returns during the 2-minute timer countdown, the shutdown timer will continue  
until the end of 2 minutes and the UPS will turn OFF. The UPS must remain OFF for at least 10  
seconds even if AC input power Returns before the UPS turns OFF. This serves to reset and  
restart the server.  
Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled  
or disabled.  
If the auto-restart is disabled, the UPS will not restart after performing the 2-minute shutdown  
delay.  
11.3 UPS Intelligent Communications  
®
The UPStation GXT2-6000RT208 is equipped with an Intellislot port to provide advanced communi-  
cation and monitoring options.  
Liebert’s MultiLink software continually monitors the UPS and can shut down your computer or  
server in the event of an extended power failure.  
MultiLink can also be configured for use without the serial cable when the Intellislot SNMP/Web card  
is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the  
network with other computers running MultiLink when you purchase a MultiLink License Kit. For  
more information about the Intellislot SNMP/Web Card and MultiLink License Kits, visit our Web  
site (www.liebert.com) or contact your local dealer or Liebert representative.  
Several option cards are available for use in the Intellislot port of the UPStation GXT2-6000RT208  
The Intellislot SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS  
across the network.  
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coor-  
dinate shutdown in the event of a power failure.  
The Intellislot Relay Card provides dry contact relay outputs for custom wired applications and deliv-  
ers support for built-in shutdown for AS/400 systems.  
CAUTION  
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables  
should be segregated and run separate from all other power cables, where applicable.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Communications  
11.4 Remote Emergency Power Off  
The UPS is equipped with a Remote Emergency Power Off (REPO) connector.  
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS  
input feeder breaker to remove all sources of power to the UPS and connected equipment to comply  
with national and local wiring codes and regulations.  
Figure 5 REPO switch connections  
REPO Connection  
REPO  
as shipped  
REPO connections  
for normally open  
switch system  
REPO connections  
for normally closed  
switch system (fail-safe)  
1
2
3
4
1
2
3
4
1
2
3
4
Key to REPO switch connections  
1. 24 VDC  
2. Sense  
3. Sense  
4. Ground  
CAUTION  
!
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should  
be segregated and run separately from power cables.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Maintenance  
12.0 MAINTENANCE  
The UPStation GXT2-6000RT208 requires very little maintenance. The batteries are valve-regulated,  
non-spillable, flame retardant, lead acid and should be kept charged to obtain their design life. The  
UPS continuously charges the batteries when connected to the utility supply.  
When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours  
every four to six months to ensure full recharge of the batteries. Failure to recharge the batteries peri-  
odically will permanently degrade battery capacity.  
The UPStation GXT2-6000RT208 is designed to allow the user to safely replace the internal batteries.  
Read the safety cautions before proceeding. Contact your local dealer or Liebert representative to  
obtain the appropriate replacement battery kit part number and pricing.  
12.1 Battery Replacement  
CAUTION  
!
A battery can present a risk of electrical shock and high short circuit Current. The following  
precautions should be observed before replacing the batteries:  
• Remove rings, watches and other metal objects.  
• Use a Phillips (crosshead) screwdriver with insulated grips.  
• Do not lay tools or other metal objects on top of the batteries.  
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact  
your local dealer or Liebert representative immediately.  
• Do not dispose of batteries in a fire. The batteries may explode.  
12.1.1 Internal Battery Replacement Procedures  
1. Gently remove the front plastic bezels cover  
UPS  
from the UPS by pulling forward.  
2. Loosen the two captive screws on the front  
battery door. Lay the battery door aside for  
reassembly.  
Battery  
Liebert  
!
3. Grasp the battery pack assembly and pull it out  
of the front of the UPS. Be prepared to support  
the weight of the battery as it is withdrawn.  
Battery Cover  
4. Unpack the new battery assembly taking care  
not to destroy the packing. Compare new and  
old battery assemblies to make sure they are the  
same. If so, proceed with Step 6; otherwise  
STOP and contact your local dealer, Liebert  
representative or the Liebert Worldwide  
Support Group.  
Battery Cover  
Captive Screws  
!
Front Bezels  
5. Line up and slide in the new replacement  
battery pack.  
6. Reattach the front battery door, tightening the  
two captive screws finger tight.  
7. Reattach the front plastic bezels to the UPS.  
NOTE  
These are hot-swappable replacement batteries. However, caution should be exercised because  
during this procedure the load is unprotected from disturbances and power outages.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Maintenance  
12.2 UPS Replacement  
When using a power distribution box with bypass, the UPS can be removed while powering the load  
through the Bypass Switch.  
NOTE  
During the procedure, the connected load will not be protected from power disturbances, such  
as spikes, sags and failure.  
To remove the UPS without shutting off power to the connected load:  
1. Turn the Bypass Switch on the power distribution box to the Utility position.  
2. Open the Output circuit breaker (on the UPS rear panel).  
3. Open the Input circuit breaker (on the power distribution box).  
4. Loosen the three captive mounting screws about  
20 turns until the power distribution box can be  
pulled away from the UPS.  
5. Loosen the electrical connector cover by backing  
out the two screws holding it one turn each. Also  
loosen the end screw one turn.  
6. Slide the cover to reach the end screw and cover  
the electrical connectors; retighten the three  
screws gently to hold the cover in place.  
7. Replace the UPS.  
8. Loosen the three screws holding the electrical  
Mounting screws  
connector cover again—one turn each.  
for removable power  
9. Slide the cover away from the electrical  
connectors; gently retighten the three screws.  
distribution box  
10. Align the connectors on the power distribution  
box and the UPS.  
11. Push the power distribution box into place.  
Screws securing electrical  
connector cover  
Electrical  
connector  
cover  
12. Holding the power distribution box firmly  
against the UPS, tighten the three captive  
mounting screws until the box is secure. Do NOT  
overtighten the screws.  
13. Close the Input circuit breaker (on the power  
distribution box).  
14. Close the Output circuit breaker (on the UPS  
rear panel).  
15. Turn the Bypass Switch on the power  
distribution box back to the UPS position.  
Electrical connectors  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
13.0 TROUBLESHOOTING  
The information below indicates various symptoms a user may encounter in the event the UPStation  
GXT2-6000RT208 develops a problem. Use this information to determine whether external factors  
caused the problem and how to remedy the situation.  
1. The Fault indicator will illuminate, indicating the UPS has detected a problem.  
2. An alarm will sound, alerting that the UPS requires attention.  
3. One or more additional Load Level/Battery Level indicators will be illuminated to provide a  
diagnostic aid to the operator, as described below:  
A
B
C
D
E
Fault  
indicator  
Battery  
indicators  
Load Level  
indicators  
AC Input  
indicator  
Bypass  
indicator  
Battery indicator  
UPS ON indicator  
Table 4  
Fault indicators  
Diagnosis/Audible alarm  
Indicator status  
All indicators  
Indicator A  
On bypass due to output overload; beep every half-second  
On bypass due to overtemperature condition on L1; 1-second beep every 4 seconds  
On bypass due to overtemperature condition on L2; 2-second beep every 4 seconds  
On bypass due to DC bus overvoltage on L1; 1-second beep every 4 seconds  
On bypass due to DC bus overvoltage on L2; 2-second beep every 4 seconds  
Indicator B  
Indicator C  
Indicator D  
Indicator E  
On bypass due to control power supply failure on L1; 1-second beep every 4 seconds  
On bypass due to control power supply failure on L2; 2-second beep every 4 seconds  
On bypass due to PFC failure on L1; 1-second beep every 4 seconds  
On bypass due to PFC failure on L2; 2-second beep every 4 seconds  
On bypass due to inverter failure on L1; 1-second beep every 4 seconds  
On bypass due to inverter failure on L2; 2-second beep every 4 seconds  
Indicators A&B  
Indicators A&C  
Indicators A&D  
Indicators B&C  
Inverter-to-Inverter communications failure; half-second beep every 1 second  
UPS failed battery test; 2-second beep every 60 seconds  
L1 to L2 phase angle unacceptable  
REPO is currently activated, UPS output cannot be started by any method  
UPS is OFF due to previous REPO (REPO is no longer activated). Once utility power is  
restored, press the OFF button twice within four seconds (to clear the alarm), then press the  
ON button to start UPS (Auto-restart is NOT possible).  
Indicators B&D  
Indicators C&E  
Indicators D&E  
UPS shutdown due to command from communications (RS232 or SNMP); no beep  
UPS is OFF due to charger overvoltage; 1-second beep every 4 seconds  
AC Input indicator On &  
Battery indicator Flashing  
AC input has been applied to start UPS but the batteries are either missing or below the  
minimal level to allow the UPS to start; continuous audible alarm  
Bypass voltage is present, but is disabled for use because the voltage or frequency is outside  
acceptable limits  
Bypass indicator Flashing  
Under fault conditions, the Fault indicators will be illuminated indefinitely while the battery charger  
is operational, or for a maximum of 5 minutes while the battery charger is not operational.  
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert World-  
wide Support Group. Please have the UPS model number and serial number available at the time of  
your inquiry.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Troubleshooting  
All audible alarms can be silenced, with the exception of Low Battery, Bypass Reminder and Missing  
Batteries at Startup alarms. Once silenced, the alarm will not sound again until a new alarm condi-  
tion is present.  
Table 5  
Alarm conditions  
Condition  
Alarm  
Battery Mode (utility failure)  
Low Battery  
One short beep every 10 seconds; more than 2 minutes of run time remaining  
Two short beeps every 5 seconds; less than 2 minutes of run time remaining  
A one-second beep every 2 minutes  
On Bypass Reminder  
Output Overload (bypass)  
Overtemperature (bypass)  
DC Bus Overvoltage (bypass)  
Control Power Supply Failure (bypass)  
PFC Failure (bypass)  
One short beep every half second  
A one-second, or two-second, beep every 4 seconds  
A one-second, or two-second, beep every 4 seconds  
A one-second, or two-second, beep every 4 seconds  
A one-second, or two-second, beep every 4 seconds  
A one-second, or two-second, beep every 4 seconds  
Inverter Failure  
Inverter-to-Inverter Communications  
Failure  
A one-half second beep every 1 second  
Battery Test Failure  
REPO Activated  
A two-second beep every 1 minute  
A one-quarter second beep every half second  
Table 6  
Troubleshooting guide  
Problem  
Cause  
Solution  
Ensure the UPS is OFF. Disconnect all loads and ensure  
nothing is lodged in output receptacles.  
Ensure the loads are not defective or shorted internally.  
UPS fails to start when the  
ON button is pressed.  
UPS is short-circuited or  
overloaded.  
UPS is operating in Battery Mode, make certain UPS is  
securely plugged into the wall receptacle.  
UPS not plugged in.  
UPS input protection fuse  
has blown/opened.  
UPS is operating in Battery Mode. Save data and close  
applications. Replace UPS input fuse, then restart UPS.  
Battery indicator is  
illuminated.  
UPS is operating in Battery Mode. Save data and close  
applications. Ensure utility supply voltage is within  
acceptable limits for UPS.  
Utility voltage out of UPS  
input range.  
Batteries are not fully  
charged.  
Keep UPS plugged in continuously at least 24 hours to  
recharge batteries.  
UPS has reduced battery  
time.  
UPS is overloaded.  
Check load level display and reduce the load on the UPS.  
Replace batteries. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group for  
replacement battery kit.  
Batteries may not be able to  
hold a full charge due to age.  
Fault and Bypass indicators  
and all Load Level indicators  
are illuminated.  
Check load level display and remove non-essential loads.  
Recalculate the load and reduce number of loads  
connected to UPS. Check load equipment for faults.  
UPS overloaded or load  
equipment is faulty.  
Fault and Bypass indicators  
and diagnostic indicator C are  
illuminated.  
UPS control power supply  
fault.  
UPS requires service. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
Fault and Bypass indicators  
and diagnostic indicator D are  
illuminated.  
UPS PFC (Power Factor  
Correction Circuit) fault.  
UPS requires service. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
Ensure the UPS is not overloaded, ventilation openings  
are not blocked and room ambient temperature is not  
excessive.  
Wait 30 minutes to allow UPS to cool, then restart UPS.  
If UPS does not restart, contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
UPS internal fan has a  
problem or UPS shutdown  
due to temperature  
condition. Load is on bypass  
power.  
Fault and Bypass indicators  
and diagnostic indicator A are  
illuminated.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Troubleshooting  
Table 6  
Troubleshooting guide  
Problem  
Cause  
Solution  
Fault and Bypass indicators  
and diagnostic indicator B are  
illuminated.  
UPS internal DC bus  
overvoltage.  
UPS requires service. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
Fault and Bypass indicators  
and diagnostic indicator E are  
illuminated.  
UPS requires service. Contact your local dealer, Liebert  
Representative or the Liebert Worldwide Support Group.  
UPS inverter fault.  
Fault and Bypass indicators  
and diagnostic indicators A  
and B are illuminated.  
Inverter-to-Inverter  
Communications Failure  
UPS requires service. Contact your local dealer, Liebert  
Representative or the Liebert Worldwide Support Group.  
Fault indicator and diagnostic  
indicators A and C are  
illuminated.  
Replace batteries. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
UPS failed the battery test.  
Only phase angles of 120, 180 or 240 degrees (±10  
degrees) are permitted. These must be compatible with  
the selections in the configuration program.  
Or the phase angle has changed while the UPS was  
running. The phase angle is detected at startup and  
cannot be changed to a different power source while  
running.  
Turn the UPS Off and wait until the fans stop. Apply input  
AC power. The UPS will reprogram the phase angle to  
match the utility, if the utility is 120, 180 or 240 degrees  
between L1 and L2. If this does not resolve the issue,  
contact a qualified electrician to verify the site wiring.  
Fault indicator and diagnostic  
indicators A and D are  
illuminated.  
L1 to L2 phase angle  
unacceptable.  
Fault indicator and diagnostic  
indicators B and C are  
illuminated.  
UPS has shut down due to the REPO (Remote Emergency  
Power Off). The output cannot be started by any method.  
REPO is currently activated.  
UPS is OFF due to previous REPO (REPO is no longer  
activated). Once utility power is restored, press the OFF  
button twice within four seconds (to clear the alarm), then  
Fault indicator and diagnostic  
indicators B and D are  
illuminated.  
UPS output is OFF from a  
previous REPO command.  
REPO is no longer activated. press the ON button to start UPS (Auto-restart is NOT  
possible).  
Your UPS has received a signal or command from the  
Fault indicator and diagnostic  
indicators C and E are  
illuminated.  
UPS shutdown due to a  
command from the  
communications port(s).  
attached computer. If this was inadvertent, ensure the  
communication cable used is correct for your system. For  
assistance, contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
Fault indicator and diagnostic  
indicators D and E are  
illuminated.  
UPS requires service. Contact your local dealer, Liebert  
Representative or the Liebert Worldwide Support Group.  
UPS charger fault.  
Check battery connections, completely power down and  
restart UPS.  
NOTE: If the battery circuit opens while the UPS is  
running, it will be detected when the next battery test is  
performed.  
AC Input indicator is On &  
Battery indicator is flashing.  
Battery source is not  
available; continuous horn.  
The AC input powers the PFC input and serves as the  
bypass source. If the AC is present but the voltage or  
frequency exceeds the acceptable range for safe  
operation with a load, the bypass will be disabled and this  
indicator will flash, indicating that the bypass is  
unavailable.  
Bypass voltage is present,  
but is disabled for use  
because the voltage or  
frequency is outside  
acceptable limits.  
Bypass indicator is flashing.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Using the configuration program, the user may specify the number of GXT2-144VBATT external bat-  
tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.  
Table 7 shows estimated run times at different loads.  
Table 7  
Battery run times  
6000VA Run Time  
in Minutes  
Battery/External Cabinets  
Load%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
75  
38  
25  
18  
14  
11  
9
7
6
5
Internal Battery  
156  
90  
62  
44  
34  
28  
23  
19  
16  
14  
235  
137  
99  
74  
58  
47  
39  
33  
28  
25  
313  
183  
133  
103  
82  
67  
55  
47  
41  
36  
391  
229  
166  
129  
105  
87  
73  
63  
54  
47  
Internal Battery + 1 External  
Battery Cabinet  
Internal Battery + 2 External  
Battery Cabinets  
Internal Battery + 3 External  
Battery Cabinets  
Internal Battery + 4 External  
Battery Cabinets  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
13.1 Auto-Learning Battery Run Times  
As batteries age, the estimated run times may become less accurate. The GXT2-6000RT208 is pro-  
grammed to “learn” from a full battery discharge and modify the estimated run time for the measured  
battery capacity. This can improve accuracy and compensate for aging batteries or batteries that  
operate at different ambient temperatures.  
The UPS will update the anticipated run time calculation only under certain conditions.  
• The UPS must have a steady load that is greater than 20%.  
• The UPS must be at 100% charge at the start of a battery discharge.  
• The battery discharge must continue uninterrupted until the batteries reach their end-of-dis-  
charge voltage.  
If all conditions are not met, the run time calculation will not be modified.  
If the configuration program is used to change the number of battery cabinets, then the values in the  
battery table on the right will be restored. This will override any value that is automatically learned.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Specifications  
14.0 SPECIFICATIONS  
Table 8  
UPS specifications  
Model Number  
GXT2-6000RT208  
4200W/5200VA at 127/220 (120 or 240 degrees only)  
4200W/5200VA at 120/208 (120 or 240 degrees)  
4200W/6000VA at 120/240 (180 degrees)  
4200W/6000VA at 115/230 (180 degrees only)  
3780W/5400VA at 110/220 (180 degrees only)  
3360W/4800VA at 100/200 (180 degrees only)  
Model Rating  
DIMENSIONS in (mm)  
Unit W x D x H in. (mm)  
Shipping W x D x H in. (mm)  
WEIGHT lbs (kg)  
6.9 x 24.2 x 16.9 (176 x 615 x 430)  
13.2 x 27.8 x 20.9 (335 x 705 x 530)  
Unit  
67 (30.3)  
Shipping  
76.3 (34.6)  
INPUT AC PARAMETERS  
Nominal Operating Frequency  
Factory Default VAC  
50 or 60 Hz (Factory Default = 60)  
120/208 VAC at 120 degrees  
L1-L2 Factory Default Input Phase  
Angle  
120 degrees  
120, 180, 240 degrees, Auto-sensing on application of AC  
(Restrictions for L-N voltages other than 120 VAC)  
Allowable Input Phase Angle  
Factory Default L1-N, L2-N VAC  
User Configurable L1-N, L2-N VAC  
120 VAC nominal  
100/110/115/120/127 VAC (May be modified using configuration program)  
L1-N, L2-N, Operating Voltage Range Without Battery Operation (Except 100 VAC L-N Operation)  
100% - 90% loading  
90% - 70% loading  
70% - 30% loading  
30% - 0% loading  
90 VAC - 140 VAC  
80 VAC - 140 VAC  
70 VAC - 140 VAC  
60 VAC - 140 VAC  
L1-N, L2-N, Operating Voltage Range Without Battery Operation (100 VAC L-N Operation)  
100% - 70% loading  
70% - 30% loading  
80 VAC - 140 VAC  
70 VAC - 140 VAC  
60 VAC - 140 VAC  
150 VAC  
30% - 0% loading  
L1-N, L2-N Max. Allowable VAC  
Input Frequency w/o Battery  
Operation  
40 - 70 Hz  
Input Power Connection  
OUTPUT AC PARAMETERS  
Factory Default VAC  
See Distribution Box Options  
120/208 VAC @ 120 degrees  
120 degrees  
L1-L2 Factory Default  
Output Phase Angle  
Allowable Output Phase Angle  
Factory Default L1-N, L2-N VAC  
User Configurable L1-N, L2-N VAC  
Output Connections  
120, 180, 240 degrees Auto-sensing on initial application of input AC  
120 VAC nominal  
100/110/115/120/127 VAC, ±3%  
See Distribution Box Options  
Frequency  
50 Hz or 60 Hz, Nominal  
Waveform  
Sinewave  
Main Mode Overload  
200% for 8 cycles; 130% for 10 seconds with transfer to bypass  
Bypass Protection Limits  
Disable Bypass operation  
Re-enable Bypass operation  
Disable Bypass operation  
If input voltage exceeds ±15% of the nominal voltage  
If input voltage returns to within ±10% of nominal output voltage  
When the input frequency prevents synchronous operation  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
Table 8  
UPS specifications (continued)  
Model Number  
GXT2-6000RT208  
ENVIRONMENTAL  
Operating Temp  
Storage Temp  
+32°F to +104°F (0°C to +40°C)  
+5°F to +122°F (-15°C to +50°C)  
0% to 95%, non-condensing  
Relative Humidity  
Operating Elevation  
Storage Elevation  
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating  
50,000 ft. (15,000 m) maximum  
<55 dBA, at 1 meter from the rear  
<50 dBA, at 1 meter from the front or sides  
Audible Noise  
AGENCY  
Safety  
RFI/EMI  
UL 1778, c-UL Listed (Suitable for computer room applications)  
FCC Part 15, Subpart B, Class A  
Surge Immunity  
Transportation  
IEEE/ANSI C62.41 Category A & B  
ISTA Procedure 1A  
Table 9  
Battery specifications  
Model Number  
DIMENSIONS in (mm)  
Shipping W x D x H in. (mm)  
WEIGHT lbs (kg)  
GXT2-144BATKIT  
13.4 x 27.2 x 13.4 (340 x 690 x 340)  
Unit  
Shipping  
Type  
79 (35.8)  
84 (38.1)  
Valve-regulated, non-spillable, flame retardant, lead acid  
12 x 12V x 9.0 AH  
Quantity x V x Rating  
Battery Mfg / Part #  
Back-Up Time  
Yuasa / REW 45-12 FR  
6 Hours to 90% capacity after full discharge into 100% load  
Recharge Time  
Table 10 Power distribution box specifications  
Model Number  
Amp Rating  
PD-HDWR  
24 Amps  
Input Power Connection  
Output Power Connection  
Input Branch Circuit Breaker  
4-Wire Hardwired, 8-10AWG  
4-Wire Hardwired, 8-10AWG  
30 Amp, Supplied by User  
Model Number  
Amp Rating  
PD-HDWR-MBS  
24 Amps  
Input Power Connection  
Output Power Connection  
4-Wire Hardwired, 8-10AWG  
4-Wire Hardwired, 8-10AWG  
Includes:  
Manual Bypass Switch with Indicator Lamps  
30 Amp, Supplied by User  
Input Branch Circuit Breaker  
Model Number  
Amp Rating  
PD-001  
24 Amps  
Input Power Connections  
Output Power Connection  
L14-30P on 10 foot cord  
L1-L2-G  
L1-L2-N-G  
(1) L6-30R on a 300mm cord  
(1) L14-30R on a 300mm cord  
L1-N-G (2) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers  
L2-N-G (2) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers  
Manual Bypass Switch with Indicator Lamps  
Includes:  
Input Branch Circuit Breaker  
30 Amp, Supplied by User  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
Table 11  
External battery cabinet specifications  
Model Number  
GXT2-144VBATT  
GXT2-6000RT208  
Used w/ UPS Model  
DIMENSIONS in (mm)  
Unit (with bezel) W x D x H  
Shipping W x D x H  
WEIGHT lbs (kg)  
Unit  
3.5 x 24.2 x 17 (87 x 618 x 430)  
10.5 x 27.2 x 23 (268 x 692 x 585)  
93.6 (42.5)  
105 (47.6)  
Shipping  
BATTERY PARAMETERS  
Type  
Valve-regulated, non-spillable, flame retardant, lead acid  
12 x 12V x 9.0 AH  
Qty x V x Rating  
Battery Mfg / Part #  
Back-Up Time  
Yuasa / REW 45-12 FR  
ENVIRONMENTAL  
Operating Temp  
Storage Temp  
+32°F to +104°F (0°C to +40°C)  
+5°F to +122°F (-15°C to +50°C)  
Relative Humidity  
Operating Elevation  
Storage Elevation  
AGENCY  
0% to 95%, non-condensing  
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating  
50,000 ft. (15,000m) maximum  
Safety  
UL 1778, c-UL Listed (Suitable for computer room applications)  
FCC Part 15, Subpart B, Class A  
RFI/EMI  
Transportation  
ISTA Procedure 1A  
14.1 Product Warranty Registration  
To register for warranty protection:  
• Visit the Quick Links section of our Web site at:  
• Click on Product Warranty Registration and fill in the form.  
If you have any questions, please contact us at:  
US: 800-222-5877  
Outside the US: 614-841-6755  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
POWER AVAILABILITY  
GXT2-6000RT208  
USER MANUAL  
The Company Behind the Products  
Technical Support/Service  
Web Site  
With over a million installations around the globe,  
Liebert is the world leader in computer protection  
systems. Since its founding in 1965, Liebert has  
developed a complete range of support and  
protection systems for sensitive electronics:  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Environmental systems—close-control air  
conditioning from 1 to 60 tons  
Single-Phase UPS  
800-222-5877  
Power conditioning and UPS with power  
ranges from 300 VA to more than 1000 kVA  
Integrated systems that provide both  
environmental and power protection in a  
single, flexible package  
Monitoring and control—from systems of any  
size or location, on-site or remote  
Service and support through more than 100  
service centers around the world and a 24/7  
Customer Response Center  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
While every precaution has been taken to ensure  
the accuracy and completeness of this literature,  
Liebert Corporation assumes no responsibility and  
disclaims all liability for damages resulting from  
use of this information or for any errors or  
omissions.  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Italy  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD)  
+39 049 9719 111  
© 2003 Liebert Corporation  
All rights reserved throughout the world.  
Specifications subject to change without notice.  
® Liebert and the Liebert logo are registered  
trademarks of Liebert Corporation. All names  
referred to are trademarks or registered  
trademarks of their respective owners.  
Fax: +39 049 5841 257  
Asia  
23F, Allied Kajima Bldg.  
138 Gloucester Road  
Wanchai  
Hong Kong  
+852 2 572 2201  
Fax: +852 2 831 0114  
SL-23170 (8/03) Rev. 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  

LaCie Computer Hardware FIREWIRE 800 400 User Manual
Leica Computer Accessories NCL TSH User Manual
LG Electronics CRT Television CT 29M65VE User Manual
Liebherr Beverage Dispenser WU 56 User Manual
Lincoln Electric Welder 305G User Manual
Linksys Network Card WAP2000 User Manual
Makita Saw HS7100 User Manual
M Audio Music Mixer Mulitmixer 6 User Manual
Mellerware Fan 3 5 8 3 05 0 W User Manual
Microtek Digital Camera COOLPIX 2200 User Manual