Liebert Power Supply 700 2200 VA User Manual

DISCONTINUED  
PRODUCT  
POWER PROTECTION  
R
PowerSure™ Interactive  
700-2200 VA  
120 V  
USER MANUAL  
English  
Download from Www.Somanuals.com. All Manuals Search And Download.  
it, or the safety ground will be removed. Operate UPS only from a  
properly grounded 120 VAC outlet (2 wire plus ground).  
9. The UPS is equipped with a grounded NEMA 5-15P or L5-30P input  
power plug (depending upon model). Do not defeat the safety purpose  
of this plug. If unable to fully insert the plug into the wall outlet, contact  
a qualified electrician for assistance.  
10. Route power supply cords so they are not walked on or pinched.  
11. Never block or insert any object into the ventilation holes or other  
openings. Maintain a clearance of four (4) inches (102 mm) around the  
UPS for proper air flow and cooling.  
12. Always turn off the UPS and unplug it before starting the battery  
replacement procedure. Servicing of batteries should be performed or  
supervised by personnel knowledgeable of batteries and the required  
precautions. To replace batteries, refer to the battery replacement  
procedure. If you feel unqualified to replace the batteries, do not open  
the battery door. Refer all servicing to qualified service personnel.  
13. CAUTION:  
Do not open or mutilate the batteries.  
Released  
electrolyte is harmful to skin and eyes and may be toxic.  
3
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
INTRODUCTION & SYSTEM DESCRIPTION  
Congratulations on your choice of the Liebert PowerSure™ Interactive  
Uninterruptible Power System (UPS).  
It provides conditioned power to  
microcomputers and other sensitive electronic equipment.  
Upon generation, AC power is clean and stable. However, during transmission it  
may be subject to voltage sags, spikes, or complete power failure which may  
interrupt computer operations, cause data loss, or even damage equipment. The  
PowerSure™ Interactive protects equipment from these disturbances.  
The PowerSure™ Interactive comes in nominal power ratings of 700, 1000, 1400,  
or 2200 VA. Complete specifications appear near the end of this section.  
The PowerSure™ Interactive is a compact, “line interactive” UPS. A “line  
interactive” UPS continuously conditions and regulates its output voltage, whether  
the utility power is present or not. It supplies connected equipment with clean  
sinewave power, to simulate as much as possible, the power generated by the  
utility. Sensitive electronic equipment operates best from sinewave power.  
For ease of use, the PowerSure™ Interactive contains a light emitting diode (LED)  
bar display to indicate “load percentage” or “battery capacity” depending upon the  
mode of operation. It also provides self diagnostics, a combination alarm  
silence/battery test button, and two levels of alarms when the unit is operating on  
battery.  
The PowerSure™ Interactive has an interface port for communications between the  
UPS and a LAN server or other computer system. This port provides detailed  
operating information including voltages, currents, and alarm status to the host  
system when used in conjunction with Liebert SiteNet® software. SiteNet®  
software can also remotely control UPS operation.  
CAUTION: This equipment has been tested and complies with limits for a Class A  
digital device, pursuant to Subpart B of Part 15 of FCC rules. These limits provide  
reasonable protection against harmful interference when the equipment is operated  
in a commercial environment. This equipment generates, uses, and can radiate  
radio frequency energy. If it is not installed and used in accordance with the  
instruction manual, it may cause harmful interference to radio communications.  
Operation of this equipment in a residential area is likely to cause harmful  
interference which the user must correct at his own expense.  
4
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
MAJOR COMPONENTS  
TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS  
These UPS components provide surge protection and filter Electromagnetic  
Interference (EMI) and Radio Frequency Interference (RFI). They minimize any  
surges or interference present in the utility line and keep the sensitive equipment  
protected.  
AUTOMATIC VOLTAGE REGULATOR  
In normal operation, the Automatic Voltage Regulator (AVR) passes utility AC  
power to the connected load. When utility power voltage is outside acceptable  
limits, the AVR activates. It raises undervoltage power and lowers overvoltage  
power. This keeps the UPS output voltage within the connected equipment’s  
tolerances and allows wide utility voltage fluctuations without utilizing battery  
power.  
BI-DIRECTIONAL CONVERTER  
In normal operation, the bi-directional converter “converts” utility AC power into  
regulated DC power to “float” charge the battery system. Upon a utility power  
failure, the bi-directional converter receives its required energy from the battery and  
“inverts” it into precise, regulated sinewave AC power. Charging takes place  
whenever the UPS is plugged into the wall outlet whether it is ON or OFF and utility  
power is within acceptable limits.  
BATTERY  
The PowerSure™ Interactive utilizes valve regulated, nonspillable, lead acid  
batteries. At typical room temperatures and with the UPS float charging, the  
battery system will last many years. For battery run times, refer to the Typical  
Battery Discharge Curves.  
INPUT  
L
OUTPUT  
L
TVSS  
and  
EMI/RFI Filters  
Automatic  
Voltage  
Regulator  
Bi-Directional  
Converter  
Battery  
N
G
N
G
5
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
MINI-TOWER INSTALLATION  
1. Unpack the UPS carefully noting the packing method. Retain the box and  
packing material for possible future shipment.  
CAUTION: The UPS is heavy (see specifications). Take proper precautions  
when lifting or moving it.  
2. Visually inspect the UPS for freight damage. Report damage to the carrier and  
your dealer.  
3. Locate the UPS indoors where it cannot be accidentally disconnected. Locate  
it in an area with unrestricted airflow, away from water, flammable liquids,  
gases, corrosives, or conductive contaminants. Maintain a minimum of four (4)  
inches (102 mm) clearance around the UPS. Maintain an ambient temperature  
range of 32° to 104° F (0° to 40° C).  
NOTE: UPS operation in temperatures above 77° F (25° C) reduces battery  
life.  
4. Ensuring load equipment is turned off, plug all loads into the UPS output  
receptacles.  
5. Plug the UPS into a dedicated wall receptacle properly protected by a circuit  
breaker or fuse in accordance with the National Electric Code (ANSI/NFPA 70)  
or local codes. Use a 15 amp rated device for the 700, 1000, or 1400 VA  
units, and a 30 amp device for the 2200 VA unit. The wall receptacle must be  
grounded.  
6. Turn on the UPS, by pressing the On/Off button, then turn on the connected  
load equipment. The UPS is ready for normal operation.  
6
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
RACKMOUNT INSTALLATION  
1. Unpack the UPS carefully noting the packing method. Retain box and packing  
material for possible future shipment.  
CAUTION: The UPS is heavy (see specifications). Take the proper  
precautions when lifting or moving the UPS.  
2. Visually inspect the UPS for freight damage. Report any damage to the carrier  
and your dealer.  
3. Locate the UPS indoors where it cannot be accidentally disconnected. Locate  
it in an area with unrestricted airflow, away from water, flammable liquids,  
gases, corrosives, or conductive contaminants. Maintain a minimum of four (4)  
inches (102 mm) clearance in front and rear of the UPS. Maintain an ambient  
temperature range of 32° to 104° F (0° to 40° C).  
NOTE: UPS operation in temperatures above 77° F (25° C) reduces battery  
life.  
4. Gently lay UPS on its bottom side so that the front bezel is facing you.  
5. The Rackmount UPS must be supported by a shelf or rails. The front bezel will  
not support the weight of the UPS.  
CAUTION: To increase the stability of the rack enclosure, place the UPS in the  
lowest possible rack position.  
6. Refer to the Installation instructions supplied with the Rack Slide or Shelf Kits  
to complete the installation procedures.  
7. After the UPS has been installed in the Rack enclosure, plug the UPS into a  
dedicated wall receptacle properly protected by a circuit breaker or fuse in  
accordance with the National Electric Code (ANSI/NFPA 70) or local codes.  
Use a 15 amp rated device for the 700, 1000, or 1400 VA units, and a 30 amp  
device for the 2200 VA unit. The wall receptacle must be grounded.  
8. Ensuring load equipment is turned off, plug all loads into the UPS output  
receptacles.  
9. Turn on the UPS, by pressing the On/Off button, then turn on the connected  
load equipment. The UPS is ready for normal operation.  
7
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
CONTROLS AND INDICATORS  
On/Off Button  
The On/Off button controls output power to connected load(s).  
CAUTION: Pressing the On/Off button when AC utility is not present will cause the  
UPS to begin operating from battery. This should not be performed unless the UPS  
input is connected to a properly grounded receptacle.  
Load/Battery Level Indicators (ALL GREEN)  
The Load/Battery Level Indicators have dual functions. During normal mode  
operation, LED indicators display electrical load placed upon the UPS; and during  
battery mode operation, LED indicators display battery capacity remaining. Each  
LED designates a 25% load or battery capacity increment. All four LED indicators  
illuminate at full load/battery capacity. If the UPS becomes loaded beyond full  
rating, the top LED indicator will flash continuously while an alarm sounds.  
Utility/Battery Status Indicator (GREEN)  
An illuminated LED indicates the power button is on and utility power is available.  
A flashing LED along with an alarm signifies utility voltage is out of specification  
and UPS is operating in battery mode.  
Utility High/Low Indicator (AMBER)  
An illuminated LED indicates the UPS is correcting utility power, due to a utility  
overvoltage or undervoltage condition.  
Fault Indicator (GREEN)  
The Fault indicator is the second uppermost LED (contained in load/battery level  
indicators). A flashing LED indicates the UPS has detected a problem. An alarm  
sounds to alert that the UPS requires attention. Refer to Troubleshooting Guide.  
Alarm Silence/Battery Test Button  
The Alarm Silence/Battery Test button serves a dual purpose. During normal mode  
operation, press button for at least one half second to test capacity of the battery  
system. The UPS will operate in battery mode for approximately 15 seconds. The  
illuminated LED indicators in Load/Battery Level determine battery mode capacity  
in 25% increments.  
During battery mode operation or active alarm condition, this button functions as  
the alarm silence feature. Pressing this button for at least one half second will  
silence the alarm. After the alarm is silenced, the PowerSure™ Interactive will  
reactivate the alarm system to alert of additional problems. The low battery alarm  
is the single alarm that cannot be silenced.  
During a Battery Test, if the top two LEDs do not illuminate allow the UPS to  
recharge the batteries for 24 hours. After 24 hours, retest the batteries. If the  
batteries have been retested and the top two LEDs still do not illuminate, contact  
your dealer or Liebert Technical Support (LTS) for a battery replacement kit.  
Site Wiring Fault Indicator (RED)  
An illuminated LED indicates the UPS has detected a miswired utility receptacle.  
Contact a qualified electrician for assistance.  
8
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
POWERSURE™ INTERACTIVE MINI-TOWER  
Fault Indicator  
Load/Battery  
Utility High/Low  
Level Indicators  
Indicator  
Alarm Silence/  
Utility/Battery  
Battery Test Button  
Status Indicator  
On/Off Button  
1- Output Receptacles  
2- DB-9 Interface Port  
3- AC Inlet  
1
4- Intellislot™ Communications Port  
5- Circuit Protector or Fuse  
6- Site Wiring Fault Indicator  
2
2
6
4
4
2
6
1
1
5
5
5
3
4
3
6
1
3
700 VA  
1000 / 1400 VA  
2200 VA  
9
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
POWERSURE™ INTERACTIVE RACKMOUNT  
Utility High / Low Indicator  
Fault Indicator  
Load / Battery  
Utility/ Battery  
Level Indicators  
Status Indicator  
R
Load / Battery  
Utility High / Low  
Utility  
Alarm Silence  
On / Off  
Alarm Silence /  
Battery Test Button  
On / Off Button  
2200 Model  
5
5
1
6
1
6
2
3
5
3
4
700-1400 Models  
*700 Model has detachable cord  
1- Output Receptacles  
2- DB-9 Interface Port  
3- AC Inlet  
4- Intellislot™ Communications Port  
5- Circuit Protector or Fuse  
6- Site Wiring Fault Indicator  
10  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
OPERATION  
NORMAL MODE OPERATION  
During normal operation, utility power provides energy to the UPS. The filters and  
the power conditioning circuit process this power to provide computer grade power  
to connected loads. The UPS maintains the batteries in a fully charged state.  
The front panel displays the percentage of load on the UPS output. The figure  
below indicates approximately 51-75% loading.  
76% to 100% load  
(Flashes to indicate overload)  
Load/ Battery  
Level Indicators  
51% to 75% load  
26% to 50% load  
0% to 25% load  
Utility High/Low  
Utility  
LED ON  
LED OFF  
Alarm silence/Test  
On/Off  
UTILITY HIGH/LOW MODE OPERATION  
If high or low voltage conditions occur, the PowerSure™ Interactive UPS will  
automatically correct the utility voltage by either lowering or raising the input  
voltage condition. The UPS will continue to correct these conditions indefinitely,  
without draining battery power.  
The figure below indicates approximately 51-75% loading while automatically  
correcting the utility voltage.  
Load/ Battery  
Level Indicators  
Utility High/Low  
Utility  
Alarm silence/Test  
On/Off  
11  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
BATTERY MODE OPERATION  
Battery mode occurs in event of extreme input conditions or complete utility failure.  
The battery system along with the bi-directional converter generates power for the  
connected load.  
During battery mode an alarm sounds every 10 seconds. This will change to 2  
beeps every 5 seconds when battery runs low (approximately 2 minutes  
remaining). Each load/battery level indicator represents a 25% capacity level. As  
capacity decreases, fewer indicators remain illuminated. Utility LED will flash every  
second indicating the UPS is operating from battery mode.  
Battery mode supports a full rated load for approximately 5 minutes before it shuts  
down. To increase this time, turn off non essential pieces of equipment (such as  
idle computers and monitors).  
WARNING: Turning off the UPS while in battery mode will result in loss of output  
power.  
The figure below displays approximately 51-75% battery capacity remaining.  
76% to 100% load  
51% to 75% load  
26% to 50% load  
Load/ Battery  
Level Indicators  
0% to 25% load  
(Flashes to indicate low battery)  
Utility High/Low  
Utility  
(Flashes every second)  
Alarm silence/Test  
On/Off  
BATTERY RECHARGE MODE  
The UPS resumes normal operation once utility power is restored. At this time, the  
bi-directional converter begins recharging the battery whether the UPS in ON or  
OFF.  
12  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
COMMUNICATIONS INTERFACE PORT  
The PowerSure™ Interactive UPS contains a standard DB-9F recepticle located on  
the rear of the UPS unit. Several signals are provided on this port and are  
assigned as follows:  
PIN  
1
2
3
4
ASSIGNMENT DESCRIPTION  
Low Battery (open collector)  
UPS TxD (typical RS-232 levels)  
UPS RxD (typical RS-232 levels)  
Remote Shutdown (5-12V DC, 1.0 mA. max.); battery operation  
Common  
5
6
No connection  
7
8
Low Battery (open emitter)  
Utility Fail (open emitter)  
9
Utility Fail (open collector)  
Pin Assignment  
Collector to Emitter*  
*Maximum voltage and current on pins 1, 7, 8, 9 is 80V DC; 10.0 mA.  
UPS MONITORING  
The PowerSure™ Interactive UPS has the capability of being monitored with stand  
alone computers, network workstations, network servers, or UNIX hosts via the DB-  
9 female connector located on the rear of the UPS.  
This capability is used in applications requiring the UPS to provide status and  
power monitoring information to the computer system. For example, during a utility  
power failure, the information can be used by the computer’s operating system or  
application program to automatically save information in buffers, to close files, and  
shut down operations prior to battery capacity depletion.  
Monitoring of the UPS via a computer system is easily made with a Liebert  
SiteNet®  
1
shutdown kit (sold separately).  
Consult your local Liebert  
representative to determine the correct software kit for your application. The kit  
includes special purpose cable and shutdown software.  
13  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
UPS INTELLIGENT COMMUNICATIONS  
The PowerSure™ Interactive UPS has the capability to communicate intelligently  
with stand alone computers, network workstations, network servers, or UNIX hosts  
via the DB-9 female connector located on the rear of the UPS. By purchasing the  
optional Liebert SiteNet® 2 software package (sold separately), intelligent  
communications allows the following capabilities:  
Quantitative monitoring of utility and UPS power  
Quantitative monitoring of internal UPS parameters  
Periodic tests of battery quality and replacement notification  
Timed and delayed shutdown of the UPS  
Logging of power disturbances and anomalies  
Contact your local Liebert representative, dealer, or reseller for more information  
about SiteNet® 2 software.  
UPS INTELLISLOT™ COMMUNICATIONS  
The PowerSure™ Interactive UPS contains an Intellislot™ communications port for  
the optional internal communications, such as the Ethernet SNMP card. Optional  
SiteNet® SNMP Manager software is available to allow communication through  
several network management systems. Contact your local Liebert representative,  
dealer, or reseller.  
CAUTION: TO MAINTAIN SAFETY (SELV) BARRIERS AND FOR  
ELECTROMAGNETIC COMPATIBILITY, SIGNAL CABLES SHOULD BE  
SEGREGATED AND SEPARATELY RUN FROM ALL OTHER POWER CABLES,  
WHERE APPLICABLE.  
MAINTENANCE  
The PowerSure™ Interactive UPS requires very little maintenance. The batteries  
are valve regulated, nonspillable, lead acid, and require that they be kept charged  
to obtain their designed life. Whether ON or OFF, the UPS continuously charges  
the batteries when connected to the utility supply.  
When storing the UPS for any length of time, it is recommended to plug the UPS in  
for at least 24 hours every four to six months to ensure full recharge of the  
batteries.  
The PowerSure™ Interactive UPS is designed to allow the user to safely replace  
the batteries. Read the safety cautions before proceeding. Contact your local  
Liebert representative, dealer, or reseller to obtain the appropriate replacement  
battery kit.  
14  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
MINI-TOWER BATTERY REPLACEMENT  
CAUTION- A battery can present a risk of electrical shock and high short circuit  
current. The following precautions should be observed before replacing the batteries:  
Turn off and disconnect the UPS from utility power prior to opening the battery  
replacement door.  
Remove rings, watches, and other metal objects.  
Use a Phillips (cross head) screwdriver with insulated grips.  
Do not lay tools or other metal objects on top of the batteries.  
If the battery replacement kit is damaged in any way or shows signs of leakage,  
contact your dealer immediately.  
Do not dispose of batteries in a fire, the batteries may explode.  
If you feel unqualified to replace the battery, do not open the battery door. Call  
Liebert Technical Support (LTS). World Wide Technical Support numbers are located  
at the end of this section.  
1. Grasp the front bezel near the top and pull forward.  
2. Rotate the bezel upward and lay it on top of the UPS.  
3. Loosen the two screws at top of the battery door and remove door by pulling it  
forward slightly and lifting it off. Lay battery door and screws aside for  
reassembly.  
4. 700/1000/1400 VA models: gently pull battery wiring out and disconnect the  
two wires [one red (+) and one black(-)].  
2200 VA models: pull apart connectors A and B.  
5. Grasp white pull-tabs located on sides of the front battery, and pull batteries  
out of the UPS.  
6. Unpack new batteries taking care not to destroy the packing.  
7. Slide new batteries into the cavity, noting the white pull-tabs are facing  
outward.  
8. 700/1000/1400 VA models: connect the battery wires; first red to red, then  
black to black.  
2200 VA models: first connect top battery connector A to bottom battery  
connector A; then connect UPS connector B to the top battery connector B.  
NOTE: There will be a small spark when connecting the black connectors on  
700-1400 VA models, and connector B on the 2200 VA model. This is normal  
and will not harm you or the UPS.  
9. Replace battery door by inserting the two metal tabs into the slots at the base  
of the UPS, and pushing it closed at the top. Tighten the two screws to lock  
the battery door closed.  
10. Flip the bezel back into place, and align bottom clips to the lower slots in the  
battery door. Once aligned, push bezel back onto the UPS until it latches into  
position. This may require a gentle tap.  
11. Dispose/Recycle of old batteries in accordance with your local laws and  
regulations.  
15  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
MINI-TOWER BATTERY REPLACEMENT  
Pull bezel forward  
Rotate bezel on top  
Remove battery door  
700 VA Model  
To Disconnect: Gently pull wiring  
away  
To Connect: Connect red wire to  
red terminal, then black wire to  
black terminal by pushing towards  
connector  
1000/1400 VA Model  
To Disconnect: Gently pull  
wiring away  
To Connect: Connect red  
wire to red terminal, then black  
wire to black terminal by  
pushing upward  
2200 VA Model  
A
B
To Disconnect:  
Pull apart  
connections A & B  
To Connect:  
Push connections  
A together &  
connections B  
together  
16  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
RACKMOUNT BATTERY REPLACEMENT  
CAUTION- A battery can present a risk of electrical shock and high short circuit  
current. The following precautions should be observed before replacing the batteries:  
Turn off and disconnect the UPS from utility power prior to opening the battery  
replacement door.  
Remove rings, watches, and other metal objects.  
Use a Phillips (cross head) screwdriver with insulated grips.  
Do not lay tools or other metal objects on top of the batteries.  
If the battery replacement kit is damaged in any way or shows signs of leakage,  
contact your dealer immediately.  
Do not dispose of batteries in a fire, the batteries may explode.  
If you feel unqualified to replace the battery, do not open the battery door. Call  
Liebert Technical Support (LTS). World Wide Technical Support numbers are located  
at the end of this section.  
1. Using a Phillips (cross head) screwdriver loosen the (4) screws around the  
battery door as in Figure 1. Carefully remove the battery door by pulling it  
forward. Lay the battery door and screws aside for reassembly.  
2. Again using a Phillips (cross head) screwdriver loosen the (4) screws holding  
the battery retaining plate as in Figure 2. Carefully remove the battery  
retaining plate by pulling it forward. Lay the battery retaining plate and screws  
aside for reassembly.  
3. 700/1000/1400 VA models: Gently pull on the white tabs located on both  
sides of the battery until wiring is exposed (Figure 3). Disconnect red wire (+)  
(figure 4) and the black wire (-) (figure 5).  
2200 VA model: Pull apart the Battery harness connector (Figure 6 & 7).  
Remove batteries.  
4. Unpack new batteries taking care not to destroy the packing.  
5. Slide new batteries into the cavity, noting the white pull-tabs are facing  
outward.  
6. For 700/1000/1400 VA models: Connect the battery wires; first black to black,  
then red to red. For 2200 VA models: Connect the battery harness  
connector. Push batteries back into cavity.  
NOTE: There will be a small spark when connecting the Red to Red  
connectors on 700-1400 VA models, and on the 2200 VA model when  
connecting the battery harness connector. This is normal and will not harm  
you or the UPS.  
7. Replace the Battery retaining plate by inserting the (4) screws into their  
associated holes. Tighten the (4) screws to secure the battery retaining plate  
in place.  
8. Replace the Battery door by inserting the four (4) screws into their associated  
holes. Tighten the four (4) screws to secure the battery door in place.  
9. Dispose of batteries in accordance with your local laws and regulations.  
17  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
Figure 1  
Figure 2  
Figure 3  
Figure 5  
Figure 4  
Figure 7  
Figure 6  
18  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
TROUBLESHOOTING  
The information below indicates various symptoms a user may encounter in the  
event the PowerSure™ Interactive UPS develops a problem. Use this information  
to determine whether external factors cause the problem and how to remedy the  
situation.  
1. The fault indicator will flash every second to indicate the UPS detected a  
problem.  
2. An alarm will sound, alerting that the UPS requires attention.  
3. One or more additional load/battery level LED segments will be illuminated to  
provide a diagnostic aid to the operator, as described below:  
“D” indicator  
Fault indicator (flashes every second)  
Load/ Battery  
Level Indicators  
“B” indicator  
“A” indicator  
Utility High/Low  
Utility  
Alarm silence/Test  
On/Off  
A.  
UPS fault (fan failure, battery overcharge)  
NOTE: The internal fan operates intermittently as needed  
UPS failed battery test  
B.  
D.  
UPS shutdown due to output overload time-out  
UPS shutdown due to main input relay failure/output short circuit  
UPS shutdown due to over temperature condition  
UPS shutdown due to command from communication ports  
(remote shutdown or SNMP)  
A&B.  
A&D.  
B&D.  
The fault indicators will be illuminated indefinitely while battery charger is  
operational, or for a maximum of 5 minutes while battery charger is not operational.  
If a problem persists consult your dealer, or contact Liebert Technical Support  
(LTS). World Wide Technical Support numbers are located at the end of this  
section.  
19  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
TROUBLESHOOTING GUIDE  
PROBLEM  
CAUSE  
SOLUTION  
UPS fails to start when On/Off  
button is pressed  
UPS output short circuited or  
overloaded.  
Ensure UPS is off. Disconnect all  
loads and ensure nothing is  
lodged in output receptacles.  
Ensure loads are not defective or  
shorted internally.  
Internal fuse is blown, indicating  
internal fault.  
Do not attempt to open or service  
the UPS. Contact your dealer or  
LTS.  
Utility indicator flashing  
UPS not plugged in.  
UPS is operating in battery mode,  
make certain UPS is securely  
plugged into the wall receptacle.  
UPS is operating in battery mode.  
Save data and close applications.  
Replace UPS input fuse or reset  
input breaker, then restart UPS .  
UPS is operating in battery mode.  
Save data and close applications.  
Ensure utility supply voltage is  
within acceptable limits for UPS.  
Keep UPS plugged in  
UPS input protection has opened.  
Utility voltage out of UPS input  
range.  
UPS has reduced battery time  
Batteries not charged.  
UPS is overloaded.  
continuously at least 24 hours to  
recharge batteries.  
Check load level display and  
remove non essential loads.  
Replace batteries. Contact your  
dealer or LTS for replacement  
battery kit.  
Batteries may not be able to hold  
a full charge due to age.  
“Fault” indicator and diagnostic  
LED “A” are illuminated  
UPS fan failure or battery  
overcharge.  
UPS requires service. Contact  
your dealer or LTS.  
“Fault” indicator and diagnostic  
LED “B” are illuminated  
UPS failed the battery test.  
Replace batteries. Contact your  
dealer or LTS for replacement  
battery kit.  
UPS shut down. “Fault” indicator  
and diagnostic LED “D” are  
illuminated  
UPS overloaded or load  
equipment is faulty.  
Check load level display and  
remove non essential loads.  
Recalculate load VA and reduce  
number of loads connected to  
UPS. Check load equipment for  
faults.  
UPS shuts down with the “Fault”  
indicator and diagnostic LEDs “A”  
& “B” are illuminated  
UPS shutdown due to internal  
failure.  
UPS requires service. Contact  
your dealer or LTS.  
UPS shuts down with the “Fault”  
indicator and diagnostic LEDs “A”  
& “D” are illuminated  
UPS shutdown due to an internal  
over temperature condition.  
Ensure UPS is not overloaded,  
ventilation openings not blocked,  
or room ambient temperature not  
excessive. Wait 30 minutes to  
allow UPS to cool, then restart  
UPS. If it does not restart,  
contact your dealer or LTS.  
Your UPS has received a signal  
or command from the attached  
computer. If this was inadvertent,  
ensure the communication cable  
used is correct for your system.  
For assistance, contact your  
dealer or LTS.  
UPS shuts down with the “Fault”  
indicator and diagnostic LEDs “B”  
& “D” are illuminated  
UPS shutdown due to a command  
from the communications port(s).  
20  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
POWERSURE™ INTERACTIVE  
TYPICAL BATTERY DISCHARGE CURVES  
(Discharge times are at 25° C ambient)  
700 VA  
1000 VA  
80  
60  
40  
20  
0
80  
60  
40  
20  
0
0
25  
50  
75  
100  
0
25  
50  
75  
100  
Percent Load  
Percent Load  
1400 VA  
2200 VA  
80  
60  
40  
20  
0
80  
60  
40  
20  
0
0
25  
50  
75  
100  
0
25  
50  
75  
100  
Percent Load  
Percent Load  
21  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
AUDIBLE ALARM CONDITIONS  
ALARM  
CONDITION  
Battery mode  
(utility failure)  
Low battery  
One short beep every ten seconds; more than two  
minutes of run time remaining  
Two short beeps every five seconds; less than two  
minutes of run time remaining  
Battery replacement  
UPS output overload  
UPS fault  
Two second beep every minute  
One short beep every second  
Continuous tone  
FUSE REPLACEMENT PROCEDURES  
FOR 700 VA MODELS  
AC Inlet  
Insert flat blade screw  
driver into slot and pull  
fuse holder out to remove  
Fuse Holder  
Input Fuse  
Spare Fuse  
CAUTION: Before changing the supply fuse, turn off the UPS, and unplug the  
input cord from the AC input power supply and from the UPS.  
1. Remove the fuse holder by inserting a flat blade screwdriver into the slot and  
pulling out as indicated in the figure above.  
2. Remove the input fuse.  
3. Remove the spare fuse from its position by using the screwdriver to push it out.  
4. Place spare fuse in the input fuse position, and replace the fuse holder. The  
fuse holder will lock into position.  
5. Reconnect the input power lead to the UPS, and the input power lead to the  
input AC supply.  
6. Restart the UPS. The UPS is ready for normal operation.  
NOTE: For 1000, 1400, and 2200 VA units press the reset circuit protector button.  
22  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
MINI-TOWER SPECIFICATIONS  
Model Number  
Model Rating VA/W  
DIMENSIONS: in (mm)  
Unit  
W x D x H  
Shipping  
PS700MT-120 PS1000MT-120 PS1400MT-120 PS2200MT-120  
700 / 450  
1000 / 670  
1400 / 950  
2200 / 1600  
5.5 x 14.4 x 7.0  
(140 x 365 x 178)  
6.8 x 17.5 x 8.9  
(172 x 447 x 227)  
6.8 x 17.5 x 8.9  
(172 x 447 x 227)  
7.6 x 20.1 x 13.2  
(194 x 511 x 336)  
10.5 x 19.2 x 11.75  
(265 x 492 x 300)  
12.0 x 22.25 x 14  
(307 x 581 x 358)  
12.0 x 22.25 x 14  
(307 x 581 x 358)  
13.0 x 25.0 x 18.5  
(330 x 635 x 470)  
W x D x H  
WEIGHT: lbs (kg)  
Unit  
Shipping  
29.9 (13.6)  
33.1 (15.0)  
43.4 (19.7)  
46.5 (21.1)  
49.4 (22.5)  
52.5 (23.9)  
81.7 (37.1)  
87.0 (39.5)  
INPUT AC PARAMETERS  
Voltage Range  
Voltage Raise  
Voltage Lower  
Frequency  
120 VAC; -25%, +23%  
Maintains output to 120 VAC; -14%, when input is 120 VAC, -25%  
Maintains output to 120 VAC; +10%, when input is 120 VAC, +23%  
45-55 Hz or 55-65 Hz; auto sensing  
6 ft. detachable, w/  
NEMA 5-15 P  
6 ft. attached, w/  
NEMA 5-15 P  
6 ft. attached, w/  
NEMA 5-15 P  
6 ft. attached, w/  
NEMA L5-30 P  
Input  
Power Cord  
OUTPUT AC PARAMETERS  
Output Receptacles  
Voltage  
Max. Current Rating  
Frequency  
(6)5-15R (2)5-20R  
(4) 5-15R  
5.8 A  
(6) 5-15R  
103 VAC to 132 VAC  
8.3 A  
(6) 5-15R  
11.67 A  
18.3 A  
50 Hz or 60 Hz  
Sinewave  
Waveform  
Utility Mode Overload  
Battery Mode Overload  
BATTERY PARAMETERS  
Type  
Qty. x Voltage x Rating  
Batt. Mfg./ Part Number  
200% for > 2 cycles; 110% for > 5 minutes  
150% for > 1 cycle; 110% for > 30 seconds  
Valve-regulated, nonspillable, lead acid  
2 x 12V x 7.0 or 7.2 AH  
3 x 12V x 7.0 or 7.2 AH  
4 x 12V x 7.0 or 7.2 AH  
8 x 6V x 12 AH  
Panasonic:  
LC-R0612CH1  
CSB: GP1270F2 or Panasonic LC-R127R2CH1  
Transfer Time  
Back-up Time  
Recharge Time  
2-6 ms typical  
See Typical Battery Discharge Curves  
3 Hours  
3 Hours  
5 Hours  
3 Hours  
to 95% capacity, after full discharge into 100% load  
ENVIRONMENTAL  
Operating Temperature  
Storage Temperature  
Relative Humidity  
Operating Elevation  
Storage Elevation  
Audible Noise  
AGENCY  
+32° F to + 104° F (0° C to +40° C)  
+5° F to + 122° F (-15° C to +50° C)  
0% to 95%, non-condensing  
Up to 10,000 ft. (3000 m) at 35° C without derating  
50,000 ft. (15,000 m) maximum  
<45 dBA, at 1 meter  
Safety  
RFI/EMI  
UL 1778, c-UL Listed  
FCC Part 15, Subpart B, Class A  
Immunity  
IEC 801-2, Level 4 / IEC 801-4, Level 4 / IEEE 587 Category A  
23  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
RACKMOUNT SPECIFICATIONS  
PS700RM-120  
700 / 450  
PS1000RM-120  
1000 / 670  
PS1400RM-120  
1400 / 950  
PS2200RM-120  
2200 / 1600  
Model Number  
Model Rating VA/W  
DIMENSIONS: in (mm)  
Unit  
W x D x H  
Shipping  
19 x 18 x 5.25  
19 x 18 x 5.25  
19 x 18 x 5.25  
19 x 18 x 7  
(483 x 457 x 178)  
(483 x 457 x 133)  
(483 x 457 x 133)  
(483 x 457 x 133)  
27.5 x 24 x 11  
27.5 x 24 x 11  
27.5 x 24 x 11  
27.5 x 24 x 12  
(699 x 610 x 305)  
(699 x 610 x 279)  
(699 x 610 x 279)  
(699 x 610 x 279)  
W x D x H  
WEIGHT: lbs (kg)  
Unit  
Shipping  
41.5 (18.9)  
50.82 (23.1)  
51.29 (23.3)  
59.85 (27.2)  
57.2 (26.0)  
66.1 (30.0)  
86.0 (39.1)  
95.3 (43.3)  
INPUT AC PARAMETERS  
Voltage Range  
Voltage Raise  
Voltage Lower  
Frequency  
120 VAC; -25%, +23%  
Maintains output to 120 VAC; -14%, when input is 120 VAC, -25%  
Maintains output to 120 VAC; +10%, when input is 120 VAC, +23%  
45-55 Hz or 55-65 Hz; auto sensing  
6 ft. detachable, w/  
NEMA 5-15 P  
6 ft. attached, w/  
NEMA 5-15 P  
6 ft. attached, w/  
NEMA 5-15 P  
6 ft. attached, w/  
NEMA L5-30 P  
Input  
Power Cord  
OUTPUT AC PARAMETERS  
Output Receptacles  
Voltage  
Max. Current Rating  
Frequency  
(6)5-15R (2)5-20R  
(6) 5-15R  
5.8 A  
(6) 5-15R  
103 VAC to 132 VAC  
8.3 A  
(6) 5-15R  
11.67 A  
18.3 A  
50 Hz or 60 Hz  
Sinewave  
Waveform  
Utility Mode Overload  
Battery Mode Overload  
BATTERY PARAMETERS  
Type  
Qty. x Voltage x Rating  
Batt. Mfg./ Part Number  
200% for > 2 cycles; 110% for > 5 minutes  
150% for > 1 cycle; 110% for > 30 seconds  
Valve-regulated, nonspillable, lead acid  
2 x 12V x 7.0 or 7.2 AH  
3 x 12V x 7.0 or 7.2 AH  
4 x 12V x 7.0 or 7.2 AH  
8 x 6V x 12 AH  
Panasonic:  
LC-R0612CH1  
CSB: GP1270F2 or Panasonic LC-R127R2CH1  
Transfer Time  
Back-up Time  
Recharge Time  
2-6 ms typical  
See Typical Battery Discharge Curves  
3 Hours  
3 Hours  
5 Hours  
3 Hours  
to 95% capacity, after full discharge into 100% load  
ENVIRONMENTAL  
Operating Temperature  
Storage Temperature  
Relative Humidity  
Operating Elevation  
Storage Elevation  
Audible Noise  
AGENCY  
+32° F to + 104° F (0° C to +40° C)  
+5° F to + 122° F (-15° C to +50° C)  
0% to 95%, non-condensing  
Up to 10,000 ft. (3000 m) at 35° C without derating  
50,000 ft. (15,000 m) maximum  
<45 dBA, at 1 meter  
Safety  
RFI/EMI  
UL 1778, c-UL Listed  
FCC Part 15, Subpart B, Class A  
Immunity  
IEC 801-2, Level 4 / IEC 801-4, Level 4 / IEEE 587 Category A  
24  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
25  
DISCONTINUED  
Download from Www.Somanuals.com. All Manuals Search And DownloadP. RODUCT  
R
1050 Dearborn Drive Columbus, OH 43229 614-888-0246  
PowerSure™ Interactive  
700-2200 VA  
120 V  
Technical Support  
U.S.A...............................................................1-800-222-5877  
Outside the U.S.A ...........................................614-841-6755  
U.K................................................................ +44 (0) 1793 553355  
France ...........................................................+33 1 4 87 51 52  
Germany ...................................................... +49 89 99 19 220  
Italy .............................................................. +39 2 98250 1  
Netherlands.................................................. +00 31 475 503333  
Internet.......................................................... [email protected]  
Worldwide FAX Tech Support......................…614-841-5471  
The Company Behind The Products  
While every precaution has  
been taken to ensure  
Corporation assumes no  
responsibility, and disclaims all  
liability for damages resulting  
from use of this information or  
for any errors or omissions.  
With more than 500,000 installations around the  
globe, Liebert is the world leader in computer  
protection systems. Since its founding in 1965,  
Liebert has developed a complete range of  
support and protection systems for sensitive  
electronics:  
Environmental systems: close-control air  
conditioning from 1.5 to 60 tons.  
Power conditioning and UPS with power  
ranges from 250 VA to more than 1000  
kVA.  
©1998 Liebert Corporation All  
rights reserved throughout the  
world. Specifications subject to  
change without notice.  
Integrated systems that provide both  
environmental and power protection in a  
single, flexible package.  
Monitoring and control — on-site or  
remote — from systems of any size or  
location  
® Liebert and the Liebert logo  
are registered trademarks of  
Liebert Corporation. All names  
referred to are trademarks or  
registered trademarks of their  
respective owners.  
Service and support, through more than 100  
service centers around the world, and a 24-hour  
Customer Response Center.  
SL-23550 (2/98) Rev. 5.0  
Download from Www.Somanuals.com. All Manuals Search And Download.  

KWC Plumbing Product K28H376000 User Manual
Lenovo Laptop 2344BMU User Manual
Lindy Network Card SATA 150 User Manual
Lowrance electronic Fish Finder X51 User Manual
Maytag Oven CWG3600AAB User Manual
Maytag Range GEMINI User Manual
Meade Telescope 114 EQ DS User Manual
Melitta Coffeemaker ME2TMDS User Manual
Memorex Stereo System MKS5012 User Manual
Microsoft Photo Printer 63XPL PS User Manual