OPERATION
MANUAL
®
E2003 Lennox Industries Inc.
Dallas, Texas, USA
Merit® Series Thermostat
CONTROLS (51M32)
504,865M
09/04
Litho U.S.A.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Table of Contents
®
Merit
MeritR Series Thermostat
®
The Lennox Merit Series Thermostat 51M32 is a nonpro-
grammable electronic thermostat that is easy-to-use and
has a large, easy-to-read display and excellent tempera-
ture control. The thermostat also includes a programmable
filter change reminder and a system check indicator. The
system check indicator will notify the user of the need for
equipment service.
Thermostat 51M32 is suitable for non-heat pump, single−
stage heat/single cool applications that are matched with a
gas or electric furnace.
Display − Initial Power−Up
FILTER
SERVICE
ROOM
General
88
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
FAN
ON
AUTO
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
SYSTEM
COOL
OFF
88
SETPOINT
Introduction
EMG.
HEAT
This document describes the operation of Lennox thermostat
51M32. Refer to the installation manual for instructions re-
garding installation and wiring of the thermostat.
Figure 1
All display segments are momentarily activated. This oc-
curs as a normal part of thermostat initialization. Within a
(figure shows temperature in Fahrenheit units).
Initial Thermostat Power-up
When power is initially applied to the thermostat, the dis-
Page 1
Download from Www.Somanuals.com. All Manuals Search And Download.
Cooling Demand
Heating Demand
ROOM
ROOM
72
79
FAN
FAN
AUTO
SYSTEM
AUTO
SYSTEM
COOL
88
HEAT
Figure 6
Figure 7
NOTE − The cooling equipment is activated for at least 4
minutes if no buttons are pressed during the demand inter-
val. Cooling equipment operation is locked out for 5 min-
utes after a demand has been satisfied. If another cooling
demand occurs during this 5−minute interval, the snowflake
icon will flash; however, the cooling equipment will not run
until the 5−minute delay has elapsed.
When the actual temperature rises above the temperature
setpoint, the flame icon will disappear. This indicates that
the heating demand has been satisfied and that the heating
equipment has been turned off.
NOTE − The heating equipment is activated for at least 3
minutes if no buttons are pressed during the demand inter-
val.
Adjusting Temperature Setpoint
The temperature setpoint represents the desired tempera-
ture of the space around the thermostat. The default tem-
perature setpoint is 70°F. To adjust the setpoint, press the
UP or DOWN arrow keys to the right of the display screen.
Cooling Control
The COOL button is located behind the small door on the
right-hand side of the thermostat. See figure 3.
The existing setpoint will be displayed just below the actual
DOWN arrow keys to adjust the setpoint up or down. The
setpoint will increase by 1°F each time the UP key is
pressed. The setpoint will decrease by 1°F each time the
DOWN key is pressed.
Enabling and Disabling Cool Mode
Use the COOL button to enable or disable cool mode as
necessary. If the thermostat is in off mode, cool mode is en-
abled when the COOL button is pressed. This is indicated
by COOL in the SYSTEM box.
If the thermostat is in cool mode, cool mode is disabled
when the COOL button is pressed. This is indicated by OFF
in the SYSTEM box.
Setpoint Display and Adjustment
ROOM
Cooling Demand
69
The thermostat must be in cool mode in order to properly
control the cooling equipment. When in cool mode, if the
room temperature is higher than the temperature setpoint,
a cooling demand is detected by the thermostat.
FAN
AUTO
SYSTEM
64
SETPOINT
The thermostat will then activate the cooling equipment to
satisfy the demand. Cooling operation is indicated by a
When the actual temperature drops below the temperature
setpoint, the snowflake icon will disappear. This indicates
that the cooling demand has been satisfied and that the
cooling equipment has been turned off.
HEAT
Figure 8
After the desired setpoint is reached, the HOME screen will
reappear after about 8 seconds.
Page 3
Download from Www.Somanuals.com. All Manuals Search And Download.
Fan Control
Filter Reminder
The 51M32 thermostat includes a filter reminder feature.
The filter reminder can be set for 1, 3, 6, or 12−month inter-
vals. The SETTINGS button, located behind the door on
the right−hand side of the thermostat is used to set the filter
reminder interval. See figure 3. Press the SETTINGS but-
ton from the HOME screen to display the Filter Reminder
The FAN button is located behind the small door on the
button can be used to select either continuous fan mode or
auto fan mode.
If continuous fan mode is enabled, the fan will run continu-
ously regardless of whether the heating or cooling equip-
ment is running. Also, ON will be displayed in the FAN box
Filter Reminder Settings
Filter
Fan ON with Icon
0
ROOM
73
FAN
ON
SYSTEM
HEAT
Figure 11
The default setting for the filter reminder is 0, which dis-
ables the function. Use the UP arrow while in the Filter Re-
minder Settings screen to select the desired interval be-
tween reminders. It may be necessary to press the UP
arrow several times to access the desired setting. The
HOME screen will reappear about 10 seconds after the ar-
row key has been pressed for the final time.
Figure 9
If auto fan mode is selected, the fan will only run when the
heating or cooling equipment is running. In this case, AUTO
After the programmed interval has elapsed, the FILTER re-
ter has been changed, reset the filter reminder by pressing
the SETTINGS button for 4 seconds. The screen will blink
for a few moments to indicate that the timer has been reset.
Fan AUTO with Icon
ROOM
73
Display of Filter Reminder
FAN
AUTO
SYSTEM
HEAT
FILTER
ROOM
72
FAN
AUTO
SYSTEM
Figure 10
To change from continuous to auto fan mode and vice versa,
press the FAN button. Also note the presence of a fan icon in
the FAN box. This icon indicates that the fan is running.
HEAT
Figure 12
Page 4
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Indicator
Technical Specifications
Thermostat Type
When abnormal equipment operation is detected, the
SERVICE indicator will flash on the upper-right corner of
the screen. This indicates that the equipment requires ser-
vice from a qualified service technician. The SERVICE indi-
Electronic nonprogrammable thermostat for 1H/1C, gas or
electric heat, non−heat pump, non−power robbing applica-
tions.
Power Supply Range
18VAC − 30VAC (24VAC nominal), 60Hz
Service Indicator Flashing
Temperature Display
Display Scale: Fahrenheit or Celsius user selectable (via
DIP switches)
SERVICE
ROOM
73
Display range: 35°F (2°C) to 99°F (37°C)
Display resolution: 1°F (1°C)
FAN
Display Accuracy: +/−1°F
AUTO
Temperature Measurement Range
Measurement Scale: Fahrenheit
SYSTEM
Measurement Range: 35°F to 99°F
Measurement Resolution: 0.5°F
Measurement Accuracy: +/−1°F
HEAT
Field Offset: via DIP switches to +/−3°F
Sampling Method: temperature measurements sampled
every 15 seconds. Displayed temperature is the average of
the last four measurements.
Figure 13
Thermostat RESET
Under some abnormal conditions, it may be desirable to
ꢀreset" the thermostat to its default condition. This can be
useful on rare occasions when the the thermostat is behav-
ing abnormally (e.g. after an electrical storm or power out-
age). The RESET button can be used to recover from this
situation.
Temperature Setpoint Range
Setting range: 50°F (10°C) to 90°F (32°C)
Setting resolution: 1°F (1°C)
Fan Control
AUTO or ON modes, gas or electric heat compatible via
DIP switches (also see Thermostat Output section).
The RESET button is an unlabeled, recessed button lo-
cated behind the door on the right−hand side of the thermo-
stat, just below the SETTINGS button. The RESET button
the RESET button. After the RESET button is pressed, the
thermostat settings will return to the defaults listed in the
Default Settings section.
I/O Relays
All thermostat relays are latching type to minimize power
consumption.
1. HEAT/COOL relay output
2. FAN relay output
3. SERVICE relay input
Equipment Protection Timers
Default Thermostat Settings
Minimum Compressor OFF time: 5 minutes
Minimum Compressor ON time: 4 minutes
Minimum Furnace ON time: 3 minutes
Default thermostat settings are in table 1.
Table 1
Minimum furnace cycle time (elapsed time between any
furnace activation and the next furnace activation): 6 min-
utes.
Default Thermostat Settings
Mode
Heat
Minimum elapsed time between any compressor activation
and the next compressor activation: 6 minutes.
Setpoint
Fan
70°F (or 21°C)
Auto
NOTE − All protection timers (except the compressor OFF
timer) can be over−ridden if a heating or cooling demand is
initiated or terminated using the UP, DOWN, HEAT, or
COOL buttons.
Filter Reminder
OFF (reminder setting = 0)
Equipment Protection reset back to zero
Timers
Page 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Equipment Protection Override
Power Loss/Recovery
Thermostat memory is retained for a minimum of 24 hours
during a power loss (includes retention of programmed
temperature setpoint, heat/cool and fan mode settings, fil-
ter reminder status, and equipment protection timers). Af-
ter 24 hours of power loss, programmed settings will be lost
and replaced with default settings.
Both the minimum compressor OFF timer and the mini-
mum equipment cycle timer can be over−ridden by press-
ing and holding either the HEAT or COOL button down for 4
seconds.
Over−Temperature Protection
Thermal mechanical switch opens W1 at 93°F+/−6°F.
Filter Reminder
IMPORTANT
Power must be applied for at least six consecutive
hours prior to a power loss in order for memory to be
retained for the specified time.
Settings of 0 (Off), 1, 3, 6 or 12 months are available. When
programmed time has elapsed, a FILTER indicator is dis-
played.
Service Reminder
LCD Backlight
Activated for 8 seconds when any key is pressed.
The SERVICE indicator is displayed only under the follow-
ing conditions:
NOTE − During an electrical storm or similar disturbance,
the backlight may activate for a few seconds. This is normal
and will no longer occur after the electrical disturbance has
passed.
S
if the thermostat Y1 terminal has been activated
with 24VAC for at least 5 minutes, AND the L
terminal is shorted to the R terminal;
Thermostat Operating Conditions
35°F to 105°F, 5% to 90% RH
OR
S
if the thermostat Y1 terminal has been activated
with 24VAC for at least 5 minutes, AND the L
terminal is shorted to the C terminal.
Thermostat Storage Conditions
−40°F to 185°F, 5% to 95% RH
Thermostat Output Table
The following table depicts the 51M32 thermostat output states for various input conditions. See table 2.
Table 2
Thermostat Outputs
Condition
W1
Y1
G
Gas Heat, Auto Fan
heat demand
X
cool demand
X
X
no demand
Gas Heat, Continuous Fan
heat demand
X
X
X
X
X
X
cool demand
X
X
X
no demand
Electric Heat, Auto Fan
heat demand
X
X
cool demand
no demand
Electric Heat, Continuous Fan
heat demand
X
X
X
cool demand
no demand
NOTE −
X = output is activated with 24VAC.
Page 6
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION
MANUAL
®
E2003 Lennox Industries Inc.
Dallas, Texas, USA
Merit® Series Thermostat
CONTROLS (51M33)
504,931M
09/04
Litho U.S.A.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Table of Contents
®
Merit
MeritR Series Thermostat
®
The Lennox Merit Series Thermostat 51M33 is a nonpro-
grammable electronic thermostat that is easy-to-use and
has a large, easy-to-read display and excellent tempera-
ture control. The thermostat also includes a programmable
filter change reminder and a system check indicator. The
system check indicator will notify the user of the need for
equipment service.
Thermostat 51M33 is suitable for heat pump, single−stage
heat/single cool applications that are matched with a gas or
electric furnace.
Display − Initial Power−Up
FILTER
SERVICE
ROOM
General
88
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
FAN
ON
AUTO
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
SYSTEM
COOL
OFF
88
SETPOINT
Introduction
EMG.
HEAT
This document describes the operation of Lennox thermostat
51M33. Refer to the installation manual for instructions re-
garding installation and wiring of the thermostat.
Figure 1
All display segments are momentarily activated. This oc-
curs as a normal part of thermostat initialization. Within a
(figure shows temperature in Fahrenheit units).
Initial Thermostat Power-up
When power is initially applied to the thermostat, the dis-
Page 1
Download from Www.Somanuals.com. All Manuals Search And Download.
Enabling and Disabling Heat Mode
Display − Home Screen
ROOM
70
Use the HEAT button to select normal heat mode, emer-
gency heat mode, or to disable heat modes as desired. If
the thermostat is in off mode, normal heat mode is enabled
when the HEAT button is pressed. This is indicated by
FAN
AUTO
SYSTEM
Normal Heat Mode Enabled
ROOM
HEAT
69
FAN
Figure 2
room temperature of 70°F is initially displayed. After about
1 minute of warm−up time, the actual room temperature will
be displayed. HEAT mode is the system default (as indi-
cated in the SYSTEM box at lower right).
AUTO
SYSTEM
64
SETPOINT
A pale blue display backlight will turn on each time a key is
pressed. The backlight will turn off 8 seconds after the last
key is pressed.
HEAT
Figure 4
Heating Control
If the thermostat is in normal heat mode when the HEAT
button is pressed, then emergency heat mode is enabled.
This is indicated by EMG. HEAT in the SYSTEM box as
The HEAT button is located behind the small door on the
right−hand side of the thermostat. See figure 3.
Additional Thermostat Buttons
If the thermostat is in emergency heat mode when the
HEAT button is pressed, then heat modes are disabled.
This is indicated by OFF in the SYSTEM box as shown in
Emergency Heat Mode Enabled
ROOM
Figure 3
69
Normal Heat Mode
FAN
In normal heat mode, both the heat pump and the backup
heat source are used to provide heat. If the thermostat de-
tects that the heat pump is not able to provide enough heat
(as may be the case in very cold weather), then the backup
heat source is activated.
AUTO
SYSTEM
64
SETPOINT
Emergency Heat Mode
EMG.
HEAT
In emergency heat mode, only the backup heat source is
used to provide heat. The heat pump is disabled. The back-
up heat source will be activated only when there is a heat
demand.
Figure 5
Page 2
Download from Www.Somanuals.com. All Manuals Search And Download.
Enabling and Disabling Cool Mode
Heat Mode Disabled
Use the COOL button to enable or disable cool mode as
necessary. If the thermostat is in off mode, cool mode is en-
abled when the COOL button is pressed. This is indicated
by COOL in the SYSTEM box.
ROOM
69
FAN
If the thermostat is in cool mode, cool mode is disabled
when the COOL button is pressed. This is indicated by OFF
in the SYSTEM box.
AUTO
SYSTEM
OFF
64
Cooling Demand
SETPOINT
The thermostat must be in cool mode in order to properly
control the cooling equipment. When in cool mode, if the
room temperature is higher than the temperature setpoint,
a cooling demand is detected by the thermostat.
Figure 6
The thermostat will then activate the cooling equipment to
satisfy the demand. Cooling operation is indicated by a
When the actual temperature drops below the temperature
setpoint, the snowflake icon will disappear. This indicates
that the cooling demand has been satisfied and that the
cooling equipment has been turned off.
Heating Demand
The thermostat must be in either normal or emergency
heat mode in order to properly control the heating equip-
ment. When in either heat mode, if the actual temperature is
lower than the temperature setpoint, a heating demand is de-
tected by the thermostat. The thermostat will then activate the
heating equipment to satisfy the demand. Heating operation
is indicated by a flame icon in the SYSTEM box as shown in
figure 7.
Cooling Demand
Heating Demand
ROOM
79
FAN
ROOM
72
AUTO
FAN
SYSTEM
COOL
AUTO
SYSTEM
88
Figure 8
HEAT
NOTE − The cooling equipment is activated for at least 4
minutes if no buttons are pressed during the demand inter-
val. Cooling equipment operation is locked out for 5 min-
utes after a demand has been satisfied. If another cooling
demand occurs during this 5−minute interval, the snowflake
icon will flash; however, the cooling equipment will not run
until the 5−minute delay has elapsed.
Figure 7
When the actual temperature rises above the temperature
setpoint, the flame icon will disappear. This indicates that
the heating demand has been satisfied and that the heating
equipment has been turned off.
NOTE − The heat pump is activated for at least 4 minutes if
no buttons are pressed during the demand interval. The
backup heat source is activated for at least 3 minutes if no
buttons are pressed during the demand interval.
Heat pump operation is locked out for 5 minutes after a de-
mand has been satisfied. If another heat pump demand oc-
curs during this 5−minute interval, the flame icon will flash;
however, the heat pump will not run until the 5−minute delay
has elapsed.
Adjusting Temperature Setpoint
The temperature setpoint represents the desired tempera-
ture of the space around the thermostat. The default tem-
perature setpoint is 70°F. To adjust the setpoint, press the
UP or DOWN arrow keys to the right of the display screen.
The existing setpoint will be displayed just below the actual
DOWN arrow keys to adjust the setpoint up or down. The
setpoint will increase by 1°F each time the UP key is
pressed. The setpoint will decrease by 1°F each time the
DOWN key is pressed.
Cooling Control
The COOL button is located behind the small door on the
right-hand side of the thermostat. See figure 3.
Page 3
Download from Www.Somanuals.com. All Manuals Search And Download.
Fan AUTO with Icon
Setpoint Display and Adjustment
ROOM
ROOM
73
69
FAN
FAN
AUTO
SYSTEM
HEAT
AUTO
SYSTEM
64
SETPOINT
HEAT
Figure 11
Figure 9
To change from continuous to auto fan mode and vice versa,
press the FAN button. Also note the presence of a fan icon in
the FAN box. This icon indicates that the fan is running.
After the desired setpoint is reached, the HOME screen will
reappear after about 8 seconds.
Filter Reminder
The 51M33 thermostat includes a filter reminder feature.
The filter reminder can be set for 1, 3, 6, or 12−month inter-
vals. The SETTINGS button, located behind the door on
the right−hand side of the thermostat is used to set the filter
reminder interval. See figure 3. Press the SETTINGS but-
ton from the HOME screen to display the Filter Reminder
Settings screen as shown in figure 12.
Fan Control
The FAN button is located behind the small door on the
button can be used to select either continuous fan mode or
auto fan mode.
Filter Reminder Settings
If continuous fan mode is enabled, the fan will run continu-
ously regardless of whether the heating or cooling equip-
ment is running. Also, ON will be displayed in the FAN box
Filter
0
Fan ON with Icon
ROOM
73
FAN
ON
Figure 12
The default setting for the filter reminder is 0, which dis-
ables the function. Use the UP arrow while in the Filter Re-
minder Settings screen to select the desired interval be-
tween reminders. It may be necessary to press the UP
arrow several times to access the desired setting. The
HOME screen will reappear about 10 seconds after the ar-
row key has been pressed for the final time.
SYSTEM
HEAT
Figure 10
After the programmed interval has elapsed, the FILTER re-
ter has been changed, reset the filter reminder by pressing
the SETTINGS button for 4 seconds. The screen will blink
for a few moments to indicate that the timer has been reset.
If auto fan mode is selected, the fan will only run when the
heating or cooling equipment is running. In this case, AUTO
Page 4
Download from Www.Somanuals.com. All Manuals Search And Download.
DOWN arrow keys to the right of the display screen. The
balance point setting will increase by 1°F each time the UP
key is pressed. The balance point setting will decrease by
1°F each time the DOWN key is pressed.
Display of Filter Reminder
FILTER
ROOM
72
After the desired balance point is reached, the HOME
screen will reappear after about eight seconds.
FAN
AUTO
SYSTEM
NOTE − The balance point feature allows the temperature
to rise or fall 3°F above or below the setpoint. This prevents
excessive cycling of the equipment when the outdoor tem-
perature is near the balance point. For example, if the bal-
ance point is 40°F and the actual outdoor temperature is
35°F, the outdoor temperature must rise to 43°F before
equipment adjustment occurs. Conversely, if the balance
point is 40°F and the actual outdoor temperature is 45°F,
the outdoor temperature must drop to 37°F before equip-
ment adjustment occurs.
HEAT
Figure 13
Balance Point
Service Indicator
NOTE − The balance point is only available with the out-
door sensor.
When abnormal equipment operation is detected, the
SERVICE indicator will flash on the upper-right corner of
the screen. This indicates that the equipment requires ser-
vice from a qualified service technician. The SERVICE indi-
If the optional outdoor sensor (X2658) is connected to the
thermostat, balance point adjustment is available. The bal-
ance point feature allows the measured outdoor tempera-
ture to govern operation of the heat pump and backup heat
source.
Service Indicator Flashing
Use the SETTINGS button to access the balance point set-
ting. If the outdoor sensor is attached to the thermostat,
press the SETTINGS button twice to access the Balance
SERVICE
ROOM
73
FAN
AUTO
Balance Point Setting
SYSTEM
6P
HEAT
Figure 15
Thermostat RESET
Under some abnormal conditions, it may be desirable to re-
set the thermostat to its default condition. The RESET but-
ton can be used to return the unit to normal operation after
an occurrence such as an electrical storm or power outage.
SETPOINT
55
Figure 14
The RESET button is an unlabeled, recessed button lo-
cated behind the door on the right−hand side of the thermo-
stat, just below the SETTINGS button. The RESET button
the RESET button. After the RESET button is pressed, the
thermostat settings will return to the defaults listed in the
Default Settings section.
The balance point can be set at any temperature between
1°F and 55°F (−17°C to 13°C). A balance point setting of
zero disables the balance point function (in this case, the
thermostat behaves as if no outdoor sensor is attached).
The default balance point setting is 55°F.
To adjust the balance point up or down, press the UP or
Page 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2
Default Thermostat Settings
Default Thermostat settings are in table 1.
Table 1
51M33 Terminal Designations
Connections Description
O
B
Reversing valve, cool active
Reversing valve, heat active
24VAC
Default Thermostat Settings
Mode
Heat
R
Setpoint
Fan
70°F (or 21°C)
Auto
G
Y1
Fan control
First stage cooling/heating, compres-
sor generated
Filter Reminder
OFF (reminder setting = 0)
Equipment Protection reset back to zero
Timers
W1
L
Auxiliary heating, furnace generated
Service Indicator
C
24VAC common
Technical Specifications
E
Emergency heat
Thermostat Type
Electronic nonprogrammable thermostat for 1H/1C, heat
pump with electric or gas backup heat source, non−power
robbing applications.
T
Outdoor temperature sensor
connection 1
T
Outdoor temperature sensor
connection 2
Power Supply Range
18VAC − 30VAC (24VAC nominal), 60Hz
Equipment Protection Timers
Temperature Display
Display Scale: Fahrenheit or Celsius user selectable (via
DIP switches)
Minimum Compressor OFF time: 5 minutes
Minimum Compressor ON time: 4 minutes
Minimum Furnace ON time: 3 minutes
Display range: 35°F (2°C) to 99°F (37°C)
Display resolution: 1°F (1°C)
Minimum backup furnace cycle time (elapsed time be-
tween any furnace activation and the next furnace activa-
tion): 6 minutes.
Display Accuracy: +/−1°F
Temperature Measurement Range
Measurement Scale: Fahrenheit
Minimum elapsed time between any compressor activation
and the next compressor activation: 6 minutes.
Measurement Range: 35°F to 99°F
NOTE − All protection timers (except the compressor OFF
timer) can be over−ridden if a heating or cooling demand is
initiated or terminated using the UP, DOWN, HEAT, or
COOL buttons.
Measurement Resolution: 0.5°F
Measurement Accuracy: +/−1°F
Field Offset: via DIP switches to +/−3°F
Sampling Method: temperature measurements sampled
every 15 seconds. Displayed temperature is the average of
the last four measurements.
Equipment Protection Override
Both the minimum compressor OFF timer and the mini-
mum equipment cycle timer can be over−ridden by press-
ing and holding either the HEAT or COOL button down for 4
seconds.
Temperature Setpoint Range
Setting range: 50°F (10°C) to 90°F (32°C)
Setting resolution: 1°F (1°C)
Over−Temperature Protection
Fan Control
AUTO or ON modes.
Thermal mechanical switch opens W1 at 93°F+/−6°F.
Filter Reminder
Backup Heat Source Selection
Electric or gas furnace, selectable via DIP switch #5 (Aux or
Dual, respectively). See also Thermostat Output section.
Settings of 0 (Off), 1, 3, 6 or 12 months are available. When
programmed time has elapsed, a FILTER indicator is dis-
played.
I/O Relays
All thermostat relays are latching type to minimize power
consumption. See table 2.
Balance Point
0°F (OFF) to 55°F, user selectable.
Page 6
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Reminder
IMPORTANT
Power must be applied for at least six consecutive
hours prior to a power loss in order for memory to be
retained for the specified time.
The SERVICE indicator is displayed only under the follow-
ing conditions:
S
if the thermostat Y1 terminal has been activated
with 24VAC for at least 5 minutes, AND the L
terminal is shorted to the R terminal;
LCD Backlight
Activated for 8 seconds when any key is pressed.
OR
NOTE − During an electrical storm or similar disturbance,
the backlight may activate for a few seconds. This is normal
and will no longer occur after the electrical disturbance has
passed.
S
if the thermostat Y1 terminal has been activated
with 24VAC for at least 5 minutes, AND the L
terminal is shorted to the C terminal.
Thermostat Operating Conditions
35°F to 105°F, 5% to 90% RH
Power Loss/Recovery
Thermostat memory is retained for a minimum of 24 hours
during a power loss (includes retention of programmed
temperature setpoint, heat/cool and fan mode settings, fil-
ter reminder status, and equipment protection timers). Af-
ter 24 hours of power loss, programmed settings will be lost
and replaced with default settings.
Thermostat Storage Conditions
−40°F to 185°F, 5% to 95% RH
Thermostat Output Table
mostat output states for various input conditions.
Page 7
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 3
Thermostat Output States
Condition
W1
Y1
G
O
E
Electric Heat Backup − No Outdoor Sensor
small heat demand
X
X
X
X
X
X
large heat demand
emergency heat demand
cool demand
X
X
X
X
no demand
dc
Gas Heat Backup (Dual Fuel) − No Outdoor Sensor
small heat demand
large heat demand
emergency heat demand
cool demand
X
X
X
X
X
X
X
X
X
no demand
dc
Electric Heat Backup − Outdoor Sensor Attached
small heat demand (BBP)
X
X
X
X
X
X
X
X
X
X
large heat demand (BBP)
small heat demand (ABP)
large heat demand (ABP)
emergency heat demand
cool demand
X
X
X
no demand
dc
Gas Heat Backup (Dual Fuel) − Outdoor Sensor Attached
small heat demand (BBP)
large heat demand (BBP)
small heat demand (ABP)
large heat demand (ABP)
emergency heat demand
cool demand
X
X
X
X
X
X
X
X
no demand
dc
NOTE −
S
S
S
S
S
X = output is activated with 24VAC
dc: does not care (output can be in either state, i.e., either active or inactive)
BBP: outdoor temperature is below balance point
ABP: outdoor temperature is above balance point
small heat demand: temperature is between (setpoint − 1.5°F) and (setpoint − 0.5°F), and 30-minute upstage
timer has not expired (see Normal Heat Mode graph)
S
large heat demand: temperature is below (setpoint − 1.5°F), or 30-minute upstage timer has expired (see Nor-
mal Heat Mode graph)
S
S
the state of the B terminal is opposite the state of the O terminal.
data above are tabulated for AUTO fan setting. If fan setting is ON, the fan is activated in all cases.
Page 8
Download from Www.Somanuals.com. All Manuals Search And Download.
|