Lennox Hearth Outdoor Fireplace ADAGIO EN User Manual

INSTALLATION INSTRUCTIONS  
TM  
ADAGIO™ Direct-Vent  
Gas Fireplaces  
P/N 850044M Rev. F 01/2011  
This manual is one of a set of two supporting this product.  
Refer to P/N 875037M for Care and Operation Instructions.  
MODELS  
MILLIVOLT:  
ADAGIO-MN  
ELECTRONIC:  
ADAGIO-EN  
Ce manuel est disponible en francais, simplement  
en faire la demande. Numéro de la pièce 850044CF.  
ADAGIO-MP  
Portland  
US  
OTL Report No. 116-F-48-5  
INSTALLER: Leave this manual with the appliance.  
CONSUMER: Retain this manual for future reference.  
INSTALLATEUR : Laissez cette notice avec l'appareil.  
CONSOMMATEUR : Conservez cette notice pour  
consultation ultérieure.  
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile  
home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating  
plate. This appliance is not convertible for use with other gases unless a certified kit is used.  
/
/
WARNING AVERTISSEMENT AVISO  
HOT GLASS WILL CAUSE  
BURNS.  
UNE SURFACE VITRÉE CHAUDE  
PEUT CAUSER DES BRÛLURES.  
LAISSER REFROIDIR LA SURFACE  
VITRÉE AVANT D'Y TOUCHER.  
EL VIDRIO CALIENTE  
CAUSARÁ QUEMADURAS.  
USTED DEBE NUNCA  
DO NOT TOUCH GLASS  
UNTIL COOLED.  
TOCAR EL VIDRIO CALIENTE.  
NEVER ALLOW CHILDREN  
TO TOUCH GLASS.  
NE PERMETTEZ JAMAIS À UN ENFANT LOS NIÑOS DEBEN NUNCA  
DE TOUCHER LA SURFACE VITRÉE.  
TOCAR EL VIDRIO.  
WARNING: If the information in these instructions  
is not followed exactly, a fire or explosion may  
result, causing property damage, personal injury,  
or death.  
AVERTISSEMENT : Assurez-vous de bien suivre les  
instructions données dans cette notice pour réduire au  
minimum le risque d’incindie ou d’explosion ou pour  
éviter tout dommage matériel, toute blessure ou la mort.  
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs  
ou liquides inflammables dans le voisinage de cet appareil  
ou de tout autre appareil.  
-
vapors and liquids in the vicinity of this or any other  
appliance.  
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :  
• Ne pas tenter d’allumer d’appareil.  
- WHAT TO DO IF YOU SMELL GAS:  
• Do not try to light any appliance.  
• Do not touch any electrical switch; do not use any  
phone in your building.  
• Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas supplier’s  
instructions.  
• Ne touchez à aucan interrupteur. Ne pas vous servir des  
téléphones se trouvant dans le bâtiment où vous trouvez.  
• Appelez immédiatement votre fournisseur de gaz depuis  
un voisin. Suivez les instructions du fournisseur.  
• Si vous ne pouvez rejoindre le fournisseur de gaz,  
appelez le service des incindies.  
- Linstallation et l’entretien doivent être assurés par un  
installateur ou un service d’entretien qualifié ou par le  
fournisseur de gaz.  
department.  
- Installation and service must be performed by a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The appliance, when installed, must be electri-  
cally grounded in accordance with local codes  
or, in the absence of local codes, with the  
National Electrical Code, ANSI/NFPA 70-latest  
edition, or the Canadian Electrical Code, CSA  
C22.1-latest edition.  
Note: Installation and repair should be done  
by a qualified service person. The appliance  
should be inspected before use and at least  
annually by a professional service person.  
More frequent cleaning may be required  
due to excessive lint from carpeting, bed-  
ding material, etcetera. It is imperative  
that control compartments, burners and  
circulating air passageways of the appliance  
be kept clean.  
WARNING  
Improper installation, adjust-  
ment, alteration, service or  
maintenance can cause injury  
or property damage. Refer to  
this manual. For assistance or  
additional information consult  
a qualified installer, service  
agency or the gas supplier.  
Provide adequate clearances around air open-  
ings and adequate accessibility clearance for  
service and proper operation. Never obstruct  
the front openings of the appliance.  
Remarque : Linstallation et la réparation  
devraitêtreconfiéesàuntechnicienqualifié.  
Lappareil devrait faire l’objet d’une inspec-  
tion par un technicien professionnel avant  
d’être utilisé et au moins une fois l’an par la  
suite.Desnettoyagesplusfréquentspeuvent  
être nécessaires si les tapis, la literie, et  
ceteraproduisentunequantitéimportantede  
pous-sière. Il est essentiel que les comparti-  
mentsabritantlescommandes,lesbrûleurset  
les conduits de circulation d’air de l’appareil  
soient tenus propres.  
These appliances are designed to operate on  
natural or propane gas only. The use of other  
fuels or combination of fuels will degrade  
the performance of this system and may be  
dangerous.  
WARNING  
Failure to comply with these  
installationinstructionswillresult  
in an improperly installed and  
operating appliance, voiding its  
warranty. Anychangetothisappli-  
anceand/oritsoperatingcontrols  
is dangerous.  
Millivolt Models - The millivolt appliances are  
manually controlled and feature a spark igniter  
(piezo)thatallowstheappliance'spilotgastobe  
lit without the use of matches or batteries. This  
system provides continued service in the event  
of a power outage. External electrical power  
is required to operate the optional blower if  
installed in these units.  
Do not use these appliances if any part  
has been under water. Immediately call a  
qualified, professional service technician  
to inspect the appliance and to replace any  
parts of the control system and any gas  
control which have been under water.  
WARNING  
Clothing or other flammable  
material should not be placed  
on or near the appliance.  
The Millivolt models come standard with the  
manually-modulated gas valve; flame appear-  
ance and heat output can be controlled at the  
gas valve. The BTU Input for these appliances  
is shown in Table 1.  
Nepasutilisercetappareils’ilaétéplongé,  
même partiellement, dans l’eau. Ap-  
peler un technicien qualifié pour inspecter  
l’appareil et remplacer toute partie du  
systèmedecommandeettoutecommande  
qui a été plongée dans l’eau.  
Electronic Models - The electronic appli-  
ances are manually controlled and feature an  
electronic intermittent pilot ignition system.  
External electrical power is required to operate  
these units.  
AVERTISSEMENT  
On ne devrait pas placer de  
vêtements ni d’autres matières  
inflammables sur l’appareil ni à  
proximité.  
Only trim kit(s) supplied by the manufacturer  
shall be used in the installation of this ap-  
pliance.  
Electronic models come standard with a manu-  
ally-modulated gas valve; flame appearance  
and heat output can be controlled at the gas  
valve. The BTU Input for these appliances is  
shown in Table 1.  
Seules les trousses de garniture fournies  
par le fabricant doivent être utilisées pour  
l’installation de cet appareil.  
WARNING  
Any safety screen or guard  
removed for servicing the appli-  
ance must be replaced prior to  
operating the appliance.  
Input (BTU/HR) - All Models  
These appliances comply with National Safety  
Standards and are tested and listed by OMNI-  
TestLaboratories,Inc.(ReportNo.116-F-48-5)  
to ANSI Z21.88 (in Canada, CSA-2.33), and  
CAN/CGA-2.17-M91(Gas-FiredAppliancesFor  
Use At High Altitudes) in both USA and Canada,  
as vented gas fireplace heaters.  
Model No.  
Input (BTU/Hr)  
Natural Gas  
ADAGIO-MN  
ADAGIO-EN  
10,000 to 13,000  
10,000 to 13,000  
AVERTISSEMENT  
Propane Gas  
Tout écran ou protecteur retiré  
pour permettre l’entretien de  
l’appareil doit être remis en  
place avant de mettre l’appareil  
en marche.  
ADAGIO-MP  
ADAGIO-EP *  
10,000 to 13,000  
10,000 to 13,000  
Both millivolt and electronic versions of  
these appliances are listed by OMNI-Test  
Laboratoriesforinstallationinbedroomsand  
manufactured (mobile) homes.  
Table 1  
* If field converted  
Misc. Codes / Standards -  
TheInstallationmustconformtolocalcodesor,  
in the absence of local codes, with the National  
Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest  
edition(InCanada,thecurrentCAN/CSA-B149.1  
installation code).  
WARNING  
Improper installation or use of  
thisappliancecancauseserious  
injury or death from fire, burns,  
explosion or carbon monoxide  
poisoning.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Gas Pressure - All Models  
Orifice Sizes - Sea Level to High Altitude  
(All Models)  
HI/LO Variable  
Flame Height  
Adjustment  
Inlet Pressure  
Tap  
Manifold  
Pressure Tap  
Tables 2 and 3 show the appliances' inlet and  
manifold gas pressure requirements:  
These appliances are tested and approved for  
installation at elevations of 0-4500 feet (0-1372  
meters) above sea level using the standard  
burnerorificesizes(marked with an "*" in Table  
4). Forelevationsabove4500feet,contactyour  
gas supplier or qualified service technician.  
HI  
Inlet Gas Supply Pressure  
(all models)  
LO  
Pilot  
Adjustment  
Screw  
Fuel #  
Minimum  
Maximum  
Deration - At higher elevations, the amount  
of BTU fuel value delivered must be reduced  
by either:  
5.0" WC  
(1.24 kPa)  
10.5" WC  
(2.61 kPa)  
Natural Gas  
OFF  
StandardBurner  
OFF/ON Rocker  
Switch  
11.0" WC  
(2.74 kPa)  
13.0" WC  
(3.23 kPa)  
Using gas that has been derated by the gas  
company.  
Propane  
ON  
Changing the burner orifice to a smaller size  
as regulated by the local authorities having  
jurisdiction and by the (USA) National Fuel  
Gas Code NFPA 54/ANSI Z223.1 - latest  
edition or, in Canada, the CAN/CSA-B149.1  
codes - latest edition.  
Table 2  
Figure 2 - SIT Electronic Gas Valve  
Manifold Gas Supply Pressure  
(all models)  
REQUIREMENTS FOR THE COMMON-  
WEALTH OF MASSACHUSETTS  
Fuel #  
Low  
High  
Installtheapplianceaccordingtotheregulations  
of the local authorities having jurisdiction and,  
in the USA, the National Fuel Gas Code NFPA  
54 / ANSI Z223.1 - latest edition or, in Canada,  
the CAN/CSA-B149.1 - latest edition.  
Natural (Lo) 2.2" WC  
(Hi) 3.5" WC  
(.87 kPa)  
Thesereplacesareapprovedforinstallationin  
the US state of Massachusetts if the following  
additional requirements are met:  
• Install this appliance in accordance with  
Massachusetts Rules and Regulations 248  
C.M.R.  
• Installation and repair must be done by a  
plumber or gas fitter licensed in the Com-  
monwealth of Massachusetts.  
• The flexible gas line connector used shall  
not exceed 36 inches (92 centimeters) in  
length.  
• The individual manual shut-off must be a  
T-handle type valve.  
Gas  
(.55 kPa)  
(Lo) 6.3" WC (Hi) 10.0" WC  
(1.57 kPa) (2.49 kPa)  
Propane  
NOTE: Flame appearance will diminish 4% per  
thousand feet.  
Table 3  
Test gauge connections are provided on the  
front of the millivolt and electronic gas control  
valve (identified IN for the inlet and OUT for the  
manifold side). The control valves have a 3/8"  
(10 mm) NPT thread inlet and outlet side of the  
valve (refer to Figures 1 and 2).  
Burner Orifice Sizes  
Elevation 0-4500 feet ( 0-1372 meters)  
Model  
Nat.Gas  
Propane  
drill size (inches)  
drill size (inches)  
Adagio  
.000 (#51)*  
.000 (#58)*  
H0922 •  
H1236 •  
Massachusetts Horizontal Vent Requirements  
Propane tanks are at pressures that will cause  
damage to valve components. Verify that the  
tanks have step down regulators to reduce the  
pressure to safe levels.  
* Standard size installed at factory  
• Part /Cat. Number  
Table 4  
In the Commonwealth of Massachusetts,  
horizontal terminations installed less than  
seven (7) feet above the finished grade  
must comply with the following additional  
requirements:  
Gas Valve Diagrams  
See Figure 1 for Millivolt models and Figure 2  
For Electronic Models.  
These appliances must be isolated from the  
gas supply piping system (by closing their  
individual manual shut-off valve) during any  
pressure testing of the gas supply piping  
system at test pressures equal to or less  
than 1/2 psig (3.5 kPa).  
• A hard wired carbon monoxide detector  
with an alarm and battery back-up must be  
installed on the floor level where the gas  
fireplace is installed. The carbon monoxide  
detector must comply with NFPA 720, be  
ANSI/UL 2034 listed and be ISA certified.  
• A metal or plastic identification plate must  
be permanently mounted to the exterior of  
thebuildingataminimumheightofeight(8)  
feet above grade and be directly in line with  
the horizontal termination. The sign must  
read, in print size no less than one-half (1/2)  
inch in size, GAS VENT DIRECTLY BELOW.  
KEEP CLEAR OF ALL OBSTRUCTIONS.  
Main Gas  
Control Knob  
Inlet Pressure  
Tap  
OFF/PILOT/ON  
HI/LO Variable  
Flame Height  
Adjustment  
Manifold  
Theseappliancesandtheirindividualshut-off  
valves must be disconnected from the gas  
supply piping system during any pressure  
testing of that system at pressures greater  
than 1/2 psig (3.5 kPa).  
Pressure Tap  
O U T I N  
I
H
F
O
F
P
I
O
L
W
O
T
O
N
Pilot  
Adjustment  
Screw  
P
I
L
These appliances must not be connected to a  
chimney or flue serving a separate solid fuel  
burning appliance.  
NEW YORK CITY, NEW YORK (MEA)  
OFF  
ON  
Installation of these fireplaces are approved  
for installation in New York City in the US state  
of New York.  
Piezo Igniter  
StandardBurnerOFF/ON  
Rocker Switch  
Figure 1 - SIT Millivolt Gas Valve  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
COLD CLIMATE INSULATION  
TOP VENT INSTALLATIONS  
For cold climate installations, seal all cracks  
around your appliance with noncombustible  
material and wherever cold air could enter  
the room. It is especially important to insulate  
outside chase cavity between studs and under  
floor on which appliance rests, if floor is above  
ground level. Gas line holes and other open-  
ings should be caulked or stuffed with unfaced  
fiberglass insulation.  
ROOM DIVIDER  
APPLICATION  
RECESSED  
INSTALLATION  
If the fireplace is being installed on a cement  
slab in cold climates, a sheet of plywood or  
otherraisedplatformcanbeplacedunderneath  
to prevent cold transfer to the fireplace and into  
the room. It also helps to sheetrock inside  
surfaces and tape for maximum air tightness  
and caulk firestops.  
Top View  
MANUFACTURED HOME  
REQUIREMENTS  
Note: When the unit is installed with one side flush  
withawall,thewallontheothersideoftheunitmust  
not extend beyond the front edge of the unit.  
This appliance may be installed in an aftermar-  
ket permanently located, manufactured home  
and must be installed in accordance with the  
manufacturer's instructions and the Manufac-  
tured Home Construction and Safety Standard,  
Title 24 CFR, Part 3280, in the United States, or  
the Standard for Installation in Mobile Homes,  
CAN/CSA Z240 MH Series, in Canada.  
VERTICAL VENT  
HORIZONTAL VENT  
Figure 3 - Typical Installation  
Be aware that this is a heat producing ap-  
pliance. Objects placed above the unit are  
exposed to elevated temperatures.  
LOCATION  
Cetappareilpeutêtreinstallécómmedumatéri-  
eld'originedansunemaisonpréfabriquée(É.U.  
seulement) ou mobile et doit être installé selon  
les instructions du fabricant et conformément  
à la norme Manufactured Home Constructions  
and Safety, Title 24 CFR, Part 3200 aux Unis ou  
à la norme Can/CSA-Z240 Série MM, Maisons  
mobiles au Canada.  
In selecting the location, the aesthetic and  
functional use of the appliance are primary  
concerns. However, vent system routing to  
the exterior and access to the fuel supply are  
also important.  
Do not insulate the space between the ap-  
pliance and the area above it (see Figure 8  
on Page 8).  
Theminimumheightfromthebaseoftheappli-  
ance to the underside of combustible materials  
used to construct a utility shelf in this fashion  
is shown in Figure 8 on Page 8.  
Due to high temperatures, the appliance  
should be located out of traffic and away from  
furniture and draperies (Figure 3).  
This appliance is only for use with the type of  
gas indicated on the rating plate. This appli-  
anceisnotconvertibleforusewithothergases,  
unless a certified kit is used.  
Enraisondestempératuresélevées,l’appareil  
devrait être installé dans un endroit où il y a  
peu de circulation et loin du mobilier et des  
tentures (Figure 3).  
The appliance should be mounted on a fully  
supported base extending the full width and  
depth of the unit. The appliance may be located  
onornearconventionalconstructionmaterials.  
However, if installed on combustible materials,  
such as carpeting, vinyl tile, etc., a metal or  
woodbarriercoveringtheentirebottomsurface  
must be used.  
Cet appareil doit être utilisé uniquement avec le  
type de gaz indiqué sur la plaque signalétique.  
Cetappareilnepeutêtreconvertiàd'autresgaz,  
sauf si une trousse de conversion est utilisée.  
The location should also be free of electrical,  
plumbing or other heating/air conditioning  
ducting.  
CAUTION: Ensure that the cross mem-  
bers are not cut or weakened during  
installation. The structural integrity of  
the manufactured home floor, wall, and  
ceiling / roof must be maintained.  
These direct-vent appliances are uniquely  
suited for installations requiring a utility shelf  
positioned directly above the fireplace. Utility  
shelveslikethesearecommonlyusedforlocat-  
ing television sets and decorative plants.  
CAUTION: This appliance must be  
grounded to the chassis of the manu-  
factured home in accordance with local  
codes or in the absence of local codes,  
with the National Electrical Code ANSI /  
NFPA 70 - latest edition or the Canadian  
Electrical Code CSA C22.1 - latest edi-  
tion.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENT TERMINATION CLEARANCES  
Vertical Vent Termination Clearances  
Termination Heights For Vents  
Above Flat Or Sloped Roofs  
Ref. NFPA 54 / ANSI Z223.1  
These instructions should be used as a  
guideline and do not supersede local codes  
in any way. Install vent according to local  
codes,theseinstructions,thecurrentNational  
Fuel Gas Code (ANSI-Z223.1) in the USA or  
the current standards of CAN/CSA-B149.1 in  
Canada.  
TERMINATION HEIGHTS FOR VENTS ABOVE  
FLAT OR SLOPED ROOFS  
Horizontal Overhang  
Roof Pitch  
Flat to 6/12  
* Feet  
1.0  
*Meters  
0.3  
2 FT  
MIN.  
Vertical  
Wall  
2 FT MIN.  
Lowest  
Discharge  
Opening  
6/12 to 7/12  
1.25  
1.5  
0.38  
0.46  
0.61  
0.76  
0.99  
1.22  
1.52  
1.83  
2.13  
2.29  
2.44  
Vent  
Termination  
7/12 to 8/12  
H*  
8/12 to 9/12  
2.0  
Storm Collar  
Flashing  
X
9/12 to 10/12  
10/12 to 11/12  
11/12 to 12/12  
12/12 to 14/12  
14/12 to 16/12  
16/12 to 18/12  
18/12 to 20/12  
20/12 to 21/12  
2.5  
12  
Vertical Vent Termination Clearances  
Roof Pitch is X/12  
3.25  
4.0  
1 inch (25.4 mm) Minimum  
Clearance to Combustibles  
Terminatemultipleventterminationsaccording  
to the installation codes listed above. Also see  
Figure 4.  
5.0  
Concentric  
Vent Pipe  
*H = MINIMUM HEIGHT FROM ROOF TO  
LOWEST DISCHARGE OPENING OF VENT  
6.0  
Terminate single vent caps relative to building  
components according to Figure 5.  
The vent / air intake termination clearances  
above the high side of an angled roof is as  
shown in the following chart:  
7.0  
7.5  
8.0  
Figure 5  
12”  
(305mm)  
Minimum  
Horizontal Vent Termination Clearances  
The horizontal vent termination must have a minimum of 3" (76 mm) clearance to any overhead  
combustible projection of 2-1/2" (64 mm) or less (see Figure 6). For projections exceeding 2-1/2"  
(64 mm), see Figure 6. For additional vent location restrictions refer to Figure 7 on Page 7.  
Horizontal Vent Termination Clearances  
Figure 4 - Multiple Terminations  
Combustible Projection  
2-1/2 inches or less in length  
All horizontal terminations  
may be located as close as  
6” (152mm) to any  
(non-combustible and  
combustible) exterior  
sidewall. This distance  
may be decreased to 2”  
(51mm) for non-  
combustible exterior  
sidewalls only, if the  
SV4.5HT-2 termination  
is used.  
Combustible Projection greater  
than 2-1/2 inches in length  
Ventilated  
Soffit  
Unventilated  
Soffit  
6"  
(152 mm)  
18"  
12"  
(457 mm)  
(305 mm)  
Termination Kit  
Side Elevation View  
Termination Kit  
Note - See Figure 29 on Page 19 for the exterior wall recess  
allowances of the square horizontal termination.  
Figure 6  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS  
NOTE: Local Codes Or Regulations  
May Require Different Clearances.  
* See Item D in the Text Below.  
Exterior Wall  
P
V
N
N
NOTE: Location Of The Vent Termination  
Must Not Interfere With Access To The  
Electrical Service.  
Inside  
Corner Detail  
O
*18”  
V
G
V
Q
Horizontal  
Termination  
6”  
Inside Corner  
Detail D  
Ventilated Soffit  
A
= 9” in U.S.  
= 12” in Canada  
A
H
3 ft.  
B
B
B
D
E
X
C
C
A
A
V
V
V
Fixed  
Operable  
Window  
L
V
Closed  
3 ft.  
Window  
V
F
J
M
V
C
B
B
C
X
V
I
A
X
K
V
= Air Supply Inlet  
= Vent Termination  
= Area where Termination is not Permitted  
Canadian Installation*  
US Installation**  
12 inches (30cm)**  
6 inches (15cm) for appliances  
< 10,000 Btuh (3kW), 9 inches (23cm)  
for appliances > 10,000 Btuh (3kW) and  
< 50,000 Btuh (15kW), 12 inches (30cm)  
for appliances > 50,000 Btuh (15kW)**  
A = Clearance above grade, veranda, porch, deck, or balcony. 12 inches (30cm)*  
B = Clearance to window or door that may be opened.  
6 inches (15cm) for appliances  
< 10,000 Btuh (3kW), 12 inches (30cm)  
for appliances > 10,000 Btuh (3kW)  
C = Clearance to permanently closed window  
12 inches (305mm) recommended to  
prevent window condensation  
9 inches (229mm) recommended to  
prevent window condensation  
D = Vertical clearance to ventilated soffit located above the  
termination within a horizontal distance of 18 inches (458mm)  
18 inches (458mm)  
18 inches (458mm)  
E = Clearance to unventilated soffit  
F = Clearance to outside corner  
G = Clearance to inside corner  
12 inches (305mm)  
12 inches (305mm)  
5 inches (12.7cm) minimum  
5 inches (12.7cm) minimum  
2 inches (5.08cm) minimum - SV4.5HT-22 inches (5.08cm) minimum - SV4.5HT-2•  
6 inches (15.2cm) minimum - SV4.5HTSS 6 inches (15.2cm) minimum - SV4.5HTSS  
H = Clearance to each inside of center line extended above  
meter/regulator assembly  
I = Clearance to service regulator vent outlet  
3 feet (91cm) within a height of 15 feet  
above the meter/regulator assembly*  
3 feet (91cm)*  
3 feet (91cm) within a height of 15 feet  
above the meter/regulator assembly**  
3 feet (91cm)**  
J = Clearance to nonmechanical air supply inlet to building or 6 inches (15cm) for appliances  
6 inches (15cm) for appliances  
the combustion air inlet to any other appliance  
< 10,000 Btuh (3kW), 12 inches (30cm)  
for appliances > 10,000 Btuh (3kW)  
< 10,000 Btuh (3kW), 9 inches (23cm)  
for appliances > 10,000 Btuh (3kW) and  
< 50,000 Btuh (15kW), 12 inches (30cm)  
for appliances > 50,000 Btuh (15kW)**  
K = Clearance to a mechanical air supply inlet  
6 feet (1.83m)*  
3 feet (91cm) above if within 10 feet (3m)  
horizontally**  
L = Clearance above paved sidewalk or paved diveway located 7 feet (2.13m)‡  
on public property  
7 feet (2.13m)‡  
M = Clearance under veranda, porch, deck or balcony  
12 inches (30cm)*‡  
12 inches (30cm)‡  
6 feet (1.83m)**  
N = Depth of Alcove (Maximum)  
6 feet (1.83m)*  
O = Clearance to Termination (Alcove)  
P = Width of Alcove (Minimum)  
6 inches (15.2mm)*  
3 feet (91cm)*  
6 inches (15.2mm)**  
3 feet (91cm)*  
Q = Clearance to Combustible Above (Alcove)  
18 inches (457mm)*  
18 inches (457mm)**  
* In accordance with the current CSA-B149.1 National Gas And Propane Installation Code.  
** In accordance with the curent ANSI SZ223.1/NFPA 54 National Fuel Gas Codes.  
‡ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both  
dwellings.  
*‡ Only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor.  
2 inch Clearance to Non-Combustibles for SV4.5HT-2 Only.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
Figure 7  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
MINIMUM CLEARANCES TO  
COMBUSTIBLES  
Do not insulate the  
space between the  
appliance and the  
area above it.  
MODELS  
Adagio-MN  
Adagio-MP  
Adagio-EN  
Appliance And Vent Clearances  
Header  
The appliance is approved with zero clearance to com-  
bustible materials on all sides (as detailed in Table 5),  
withthefollowingexception:Whentheunitisinstalled  
with one side flush with a wall, the wall on the other  
sideoftheunitmustnotextendbeyondthefrontedge  
of the unit. In addition, when the unit is recessed, the  
sidewallssurroundingtheunit mustnotextendbeyond  
the front edge of the unit (see Figure 3).  
4”  
Combustible Shelf Height  
Inches (millimeters)  
(102mm)  
Drywall  
Top Vent - with One 90 Degree Elbow  
Secure Vent  
*52 (1321)  
Secure Flex (flex elbow)  
*53-3/4 (1365)  
*Shelf Height  
(see table)  
Top Spacers  
* Includes 4” clearance to combustibles  
(required above vent components)  
MINIMUM CLEARANCES Inches (millimeters)  
Back  
Sides  
1/2 in. (13 mm)  
1/2 in. (13 mm)**  
0 in. (0 mm)  
u
4" clearance is required above the elbow  
for installations that require an elbow at the  
top of the unit and that ends in a horizontal  
termination.  
Top Spacers  
Floor  
0 in. (0 mm)***  
64 in. (1626 mm)  
From Bottom of Unit  
To Ceiling  
Figure 8 - Minimum Shelf Height Above Fireplace  
Vent  
3 (76) Top *  
1 (25.4) Sides & Bottom  
12 (305) Mantel  
10 (254) Mantel  
8 (203) Mantel  
SERVICE CLEARANCES Feet (meters)  
Front 3 feet (0.9 meters)  
Inches (millimeters)  
16  
6 (152) Mantel  
(406)  
14  
Table 5  
4 (102) Mantel  
2 (51) Mantel  
(356)  
12  
(305)  
Top Of  
Appliance  
*
Note: 3in.(75mm)aboveanyhorizontalventcomponent.  
See Note in Figure 8.  
10  
(254)  
u
8
(203)  
** Note: See Page 9, Step 1 for clearance requirements  
to the nailing flange located at each side of the unit and  
any screw heads adjacent to it.  
6
(152)  
*** Note: To ensure proper fit of the facade (required - sold  
separately).Theappliancebasewillneedtobeelevated  
3/4" minimum above the floor to allow for the proper  
fit of the facade (i.e. use 3/4" board as platform).  
Shelf Height  
To provide for the lowest possible shelf surface, the  
venting attached to the top vent should be routed in a  
way to minimize obstructions to the space above the  
appliance. Do not insulate the space between the appli-  
ance and the area above it (see Figure 8). The minimum  
height from the base of the appliance to the underside  
of combustible materials used to construct a utility shelf  
in this fashion is shown in the table in Figure 8.  
Figure 9 - Mantel Clearances  
2” (51) Minimum  
Clearance to Combustibles  
Combustible Materials Allowed  
In Shaded Area “Safe Zone”  
Wall Finishes / Surrounds / Mantels  
Combustible materials  
may project beyond the  
side of the fireplace  
12" (305)  
Note: Combustible wall finish materials and/or surround  
materialsmustnotbeallowedtoencroachtheareadefined  
by the appliance front face (black sheet metal). Never al-  
low combustible materials to be positioned in front of or  
overlapping the appliance front face.  
opening as long as it is  
kept within the shaded  
area illustrated here.  
5"  
(127)  
Top View Of  
Fireplace  
45  
°
17"  
Non-combustiblematerials,suchassurroundsandother  
appliancetrim,maybeinstalledontheappliancefrontface  
with these exceptions: they must not cover any portion  
of the glass or the air gaps above the glass door.  
(432)  
At 14" minimum side  
wall clearance, a  
combustible wall may  
project to any length  
inches (millimeters)  
Min. Distance  
8-1/4” (210) to  
Protected Side Wall  
Vertical installation clearances to combustible mantels  
vary according to the depth of the mantel. Mantels  
constructed of non-combustible materials may be  
installed above the appliance opening as outlined in  
Figure 9.  
Side  
Wall  
Side  
Wall  
Side Wall Clearances  
Figure 10  
Min. Distance to  
Unprotected Side Wall  
14" (356)  
NOTE: We recommend the use of high temperature  
paint (rated 175° F or higher) on the underside of the  
mantel.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL INSTALLATION SEQUENCE  
Step 1. FRAMING  
WARNING  
FrametheseappliancesasillustratedinFigures  
12 and 14 on Pages 10 and 12 (Figure 14  
applies to corner framing installations only).  
All framing details must allow for a minimum  
clearance to combustible framing members as  
shown in Table 5 on Page 8.  
The typical sequence of installation is outlined  
below. However, each installation is unique  
and may result in variations to the steps  
described.  
Failure to position the parts in  
accordance with these diagrams  
orfailuretouseonlypartsspecifi-  
callyapprovedwiththisappliance  
may result in property damage or  
personal injury.  
See the page numbers references in the follow-  
ing steps for detailed procedures.  
If the appliance is to be elevated above floor  
level, a solid continuous platform must be  
constructed below the appliance.  
Step 1. (Page 9) Construct the appliance  
framing. Position the appliance within  
the framing and secure with nailing  
brackets.  
Step 2. (Page 12) Route gas supply line to  
appliance location.  
Step 3. (Page 13) Install the vent system and  
exterior termination.  
Step 4. (Page 23) Field Wiring  
AVERTISSEMENT  
Risque de dommages ou de  
blessures si les pièces ne sont  
pas installées conformément à  
ces schémas et ou si des pièces  
autres que celles spécifiquement  
approuvéesaveccetappareilsont  
utilisées.  
Headers may be in direct contact with the  
appliance top spacers but must not be sup-  
ported by them or notched to fit around them.  
All construction above the appliance must be  
self-supporting, DO NOT use the appliance for  
structural support.  
.25  
a. Millivolt Appliances – The operating  
control switch is factory installed.  
b.ElectronicAppliancesConnect120  
Vac electrical power to the appliance  
receptacle.  
Thereplaceshouldbesecuredtothesidefram-  
ingmembersusingtheunit'snailingangeson  
each side of the fireplace front (see Figure 11).  
Use 8d nails or their equivalent.  
.25  
DETAILED INSTALLATION STEPS  
Step 5. (Page 24) Install blower kit (optional  
equipment).  
Step 6. (Page 24) Make connection to gas  
The appliance is shipped with all gas controls  
and components installed and pre-wired.  
supply.  
1. Remove the shipping carton, exposing the  
front glass door.  
Step 7. (Page 25) Verify appliance opera-  
tion.  
2. Pulloutthetwospringloadedlatchessecur-  
ing the glass door (located under the firebox  
floor). Remove the door by tilting it outward  
at the bottom and lifting it up and off. Set  
the door aside protecting it from inadvertent  
damage. See Figures 50 and 51 on Page  
28.  
BEFORE PROCEEDING TO STEP 8, INSTALL  
A FIREBOX LINER KIT PER INSTRUCTIONS  
PROVIDED IN THE KIT (REQUIRED - SOLD  
SEPARATELY).  
Use Top Flange For  
5/8” Thick Drywall  
Step 8. (Page 26) Install the logs and glowing  
embers.  
Step 9. (Page 28) Install glass door assem-  
bly.  
Step 10.(Page 29) Adjust burner to ensure  
proper flame appearance.  
Use Center FlangeFor  
1/2” Thick Drywall  
Use Bottom Flange  
For Flush Mount  
Step 11. (Page 31) Attach Safety in Operation  
Warnings.  
Left Side Front Corner of Fireplace Shown  
(Right Side Requirements the Same)  
Unit Being Secured By Its Nailing  
Flanges To The Framing  
Frame the opening to the exact dimensions  
specified in the framing details in this manual.  
Figure 11  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIREPLACE AND FRAMING SPECIFICATIONS  
Framing Dimensions - All Models  
Inches (millimeters)  
Framing With Platform  
A
B
C
D
10¹⁄₂  
(267)  
VENT FRAMING -  
TOP VENT WITH ONE  
90° ELBOW  
in.  
22-1/8  
562  
40-1/4  
1022  
15-3/4  
400  
44-1/8  
1121  
mm  
Framing should be  
constructed of 2x4  
or larger lumber  
*
D shown here is not dimensioned to the vertical center of  
the horizontal framing. This is to allow for the required 4"  
clearance above the vent and the 1" required clearance  
below the vent. This does not include the suggested 1/4"  
rise per foot for horizontal runs.  
** With the facade installed (required - sold separately), the  
appliancebasewillneedtobeelevatedaminimumof3/4"  
above the floor to allow for the proper fit of the facade (i.e.  
use 3/4" board minimum as platform).  
D
B
Efficiencies %  
Platform  
C
Adagio  
BTU/hr  
Steady  
State  
EnerGuide  
P4  
Natural Gas  
10,000-13,000  
71.82%  
73.27%  
58.3%  
59.4%  
Propane Gas 10,000-13,000  
A
Co-axial DV Vent  
4-1/2" (114) Inner  
7-1/2" (191) Outer  
Theplatformshouldextendthefullwidth  
and depth of the fireplace base.  
15-1/32  
(382)  
15-15/32  
(393)  
7-11/16  
(195)  
Notes  
Diagrams, illustrations and photo-  
graphs are not to scale – consult  
installation instructions. Product  
designs, materials, dimensions,  
specifications, colors and prices are  
subject to change or discontinuance  
without notice.  
40-1/32  
(1017)  
20-3/4  
(527)  
36-23/32  
(933)  
34  
(864)  
1-7/8  
(48)  
5-13/32  
(137)  
6-1/16  
14-3/4 (375)  
21-1/16 (535)  
1-1/2  
(38)  
(154)  
Figure 12  
8-7/32  
(209)  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FACADE SPECIFICATIONS  
Arch Facades**  
1/2” (13mm) -  
1-1/2” (38mm)  
Black and Brushed Nickel Finishes  
Faca  
de (R  
equir  
ed) *  
(arch  
ed st  
yle sh  
own)  
Cat.  
No.  
Model  
Description  
H5773 ADAGIO-AG Arch Black  
H5774 ADAGIO-PF  
Arch Br. Nickel  
** A filigree inset kit is also required  
(sold separately). See Care and  
Operation Manual for ordering  
information.  
20-1/4”  
(514)  
38-1/2”  
(978)  
1/2”  
(13)  
14-13/16” (376)  
26-3/4” (680)  
Gated Facades  
Cat. No.  
H5775  
Model  
Description  
Copper and Iron Gates  
ADAGIO-IG  
Iron Gates  
H5776  
ADAGIO-CPD Copper Gates  
Facade (Required) *  
(gated style shown)  
1/2” (13mm) -  
1-1/2” (38mm)  
20-3/4”  
(527)  
37-7/8”  
(962)  
18-3/4  
(476)  
1/2”  
(13)  
14-3/4”  
(375)  
23-1/2” (597)  
Notes  
Diagrams, illustrations and photographs are not to scale – consult installation instructions. Product designs, materials, dimensions, specifica-  
tions, colors and prices are subject to change or discontinuance without notice.  
* With the facade installed (required - sold separately), the appliance base will need to be elevated a minimum of 3/4" above the floor to allow  
for the proper fit of the facade (i.e. use 3/4" board minimum as platform).  
Figure 13  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Top Vent With Horizontal Termination In A Corner  
Corner Framing Dimensions - All Models  
A
B
C
D
E
in.  
22-1/8  
562  
41-5/8 29-1/2  
1057 749  
10  
20-7/8  
530  
D
mm  
254  
7 (178)  
uWheninstallinginacornerconfiguration,oneof  
the rear stand-offs will need to be removed.  
C
E
A
Figure 14 - Corner Framing with Square Termination (SV4.5HT-2)  
B
Never use galvanized or plastic pipe. Refer  
Notes:  
Step 2. ROUTING GAS LINE  
to Table 6 for proper sizing of the gas sup-  
ply line, if black iron pipe is being used. Gas  
lines must be routed, constructed and made  
of materials that are in strict accordance with  
local codes and regulations. We recommend  
that a qualified individual such as a plumber or  
gas fitter be hired to correctly size and route  
the gas supply line to the appliance. Installing  
a gas supply line from the fuel supply to the  
appliance involves numerous considerations of  
materials,protection,sizing,locations,controls,  
pressure, sediment, and more. Certainly no one  
unfamiliarandunqualifiedshouldattemptsizing  
or installing gas piping.  
• All appliances are factory-equipped with  
a flexible gas line connector and 1/2 inch  
shutoff valve (see Figure 39 on Page 24).  
• SeeMassachusettsRequirementsonPage  
4 foradditionalrequirementsforinstallations  
in the state of Massachusetts in the USA.  
• ThegassupplylineshouldNotbeconnected  
to the appliance until Step 6 (Page 24).  
Apipejointcompoundratedforgasshouldbe  
usedonthethreadedjoints.Ensurepropane  
resistant compounds are used in propane  
applications. Be very careful that the pipe  
compound does not get inside the pipe.  
• It is recommended to install a sediment trap  
in the supply line as close as possible to the  
appliance(seeFigure39). Appliancesusing  
Propane should have a sediment trap at the  
base of the tank.  
Route a 1/2" (13 mm) gas line along the inside  
of the left side framing as shown in Figure 15.  
Gaslinesmustberouted,constructedandmade  
of materials that are in strict accordance with  
local codes and regulations. All appliances are  
factory-equipped with a flexible gas line con-  
nector and 1/2 inch shutoff valve. (See Step 6  
on Page 24).  
Right Side Front  
Corner of Fire-  
place Framing  
Schedule 40  
Black Iron Pipe  
Inside Diameter (Inches)  
• Check with local building official for local  
coderequirements(i.e.arebelowgradepen-  
etrations of the gas line allowed?, etc.).  
*1-7/8"  
(65 mm)  
6-1/8"  
(156 mm)  
Schedule 40 Pipe  
Length (feet)  
Natural  
Gas  
Propane  
Gas  
0-10  
10-40  
1/2  
1/2  
1/2  
3/4  
3/4  
3/8  
1/2  
1/2  
1/2  
1/2  
IMPORTANT:Ifpropaneisused,beawarethat  
if tank size is too small (i.e. under 100-lbs, if  
this is the only gas appliance in the dwelling.  
Ref. NPFA 58), there may be loss of pressure,  
resulting in insufficient fuel delivery (which  
can result in sooting, severe delayed ignition  
orothermalfunctions). Anydamageresulting  
from an improper installation, such as this, is  
not covered under the limited warranty.  
* Measured from the top of platform that unit  
is installed on to pipe center (see Figure 12)  
40-100  
100-150  
150-200  
Table 6  
Figure 15 - Route Gas Line  
Proper Sizing of Gas Line  
Properly size and route the gas supply line  
from the supply regulator to the area where the  
appliance is to be installed per requirements  
outlined in the National Fuel Gas Code, NFPA  
54 - latest edition (USA) or CAN/CSA-B149.1  
- latest edition (Canada).  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
wall (such as a chase). There is no requirement  
for inspection openings in the enclosing wall  
at any of the joints in the vent pipe.  
Step 3. INSTALL THE VENT SYSTEM  
General Information  
Useonlyapprovedventingcomponents.  
See Approved Vent Components on  
Page 2.  
These instructions should be used as a  
guideline and do not supersede local codes  
in any way. Install vent according to local  
codes,theseinstructions,thecurrentNational  
Fuel Gas Code (ANSI-Z223.1) in the USA or  
the current standards of CAN/CSA-B149.1 in  
Canada.  
Select Venting System - Horizontal or Verti-  
cal  
These fireplaces must be vented directly  
to the outside.  
With the appliance secured in framing, de-  
termine vent routing and identify the exterior  
termination location. The following sections  
describe vertical (roof) and horizontal (exterior  
wall) vent applications. Refer to the section  
relating to your installation. A list of approved  
venting components are shown in the tables  
on Page 32.  
The vent system may not service multiple ap-  
pliances, and must never be connected to a flue  
servingasolidfuelburningappliance. The vent  
pipe is tested to be run inside an enclosed  
Ensure clearances are in accordance with  
localinstallationcodesandtherequirements  
of the gas supplier.  
Dégagementconformeauxcodesd'installation  
locaux et aux exigences du foumisseunde  
gaz.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VERTICAL TERMINATION SYSTEMS (ROOF)  
VENT SECTION LENGTH CHART  
VENT SECTION LENGTH CHART  
Nominal  
Section Length  
(inches)  
6
12  
24  
36  
48  
NominalSection  
Length (inches)  
6
12  
24  
36  
48  
See Figures 16, and 24 through 26 on  
Pages 14 and 17 and their associated Vertical  
Vent Tables which illustrate the various vertical  
venting configurations that are possible for use  
with these appliances. Secure Vent™ pipe ap-  
plications are shown in these figures; Secure  
Flex™pipe may also be used. A Vertical Vent  
Table summarizes each system’s minimum and  
maximum vertical and horizontal length values  
that can be used to design and install the vent  
components in a variety of applications.  
T
O
T
A
L
T
O
T
A
L
NetSection  
Length (inches)  
4 ½ 10 ½ 22 ½ 34 ½ 46 ½  
Number of Vent Sections  
NetSection  
Length (inches)  
4 ½ 10 ½ 22 ½ 34 ½ 46 ½  
Number of Vent Sections  
Height of Vent  
Q
T
Y
Q
T
Height of Vent  
*inches  
feet  
Y
*inches  
feet  
144  
150  
12  
1
0
1
0
0
1
0
0
1
0
0
0
1
0
1
1
2
0
0
1
0
0
1
1
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
5
5
5
0
0
0
5
6
6
3
3
3
3
0
0
0
4
4
4
0
0
0
4
4
5
5
5
6
6
4
5
5
7
6
7
4.5  
9
0.375  
0.75  
1
2
0
1
2
0
0
1
0
0
1
0
0
1
1
1
2
0
2
3
0
1
0
0
0
0
0
0
1
0
0
0
1
0
0
0
0
0
0
0
0
0
1
0
0
0
0
1
2
1
2
3
2
1
3
3
1
3
12.5  
154.5 12.875  
160.5 13.375  
172.5 14.375  
10.5 0.875  
15 1.25  
19.5 1.625  
21 1.75  
0
0
Both these vertical vent systems terminate  
through the roof. The minimum vent height  
above the roof and/or adjacent walls is speci-  
fied in ANSI Z223.1-(latest edition) (In Canada,  
the current CAN/CSA-B149 installation code)  
by major building codes. Always consult your  
localcodesforspecificrequirements. Ageneral  
guide to follow is the Gas Vent Rule (refer to  
Figure 5 on Page 6).  
177  
183  
186  
14.75  
15.25  
15.5  
0
0
0
0
0
0
22.5 1.875  
25.5 2.125  
31.5 2.625  
34.5 2.875  
37.5 3.125  
190.5 15.875  
196.5 16.375  
205.5 17.125  
43.5 3.625  
0
0
0
1
2
0
0
0
1
2
0
2
0
0
0
0
0
0
1
0
3
2
1
3
207  
17.25  
45  
3.75  
211.5 17.625  
Vertical (Straight) Installation  
(Figure 16)  
46.5 3.875  
49.5 4.125  
217.5 18.125  
229.5 19.125  
232.5 19.375  
0
0
0
1
0
1
0
0
0
0
1
1
0
0
0
1
0
1
0
0
1
0
1
0
0
1
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
6
6
0
0
5
5
0
0
0
0
0
6
0
6
6
6
0
0
7
7
7
0
0
8
8
0
9
9
7
7
51  
4.25  
1
0
0
0
0
0
1
1
0
0
0
0
0
1
1
0
1
0
2
0
0
0
0
1
0
2
0
0
0
0
0
2
1
2
3
0
3
0
0
0
1
2
0
1
0
0
0
1
0
0
2
0
2
2
1
0
0
0
2
0
1
0
0
0
0
0
0
0
0
1
1
1
2
0
2
2
3
2
4
3
2
4
3
3
2
4
3
2
4
3
Determine the number of straight vent sections  
required. 4-1/2" (114 mm), 10-1/2" (267 mm),  
22-1/2" (572 mm), 34-1/2" (876 mm) and  
46-1/2" (1181 mm) net section lengths are  
available (see Tables on this page and Page  
32 - Vent Sections). Plan the vent lengths so  
that a joint does not occur at the intersection of  
ceiling or roof joists. Refer to the Vent Section  
Length Chart.  
0
5
55.5 4.625  
237  
19.75  
0
6
57  
66  
4.75  
5.25  
241.5 20.125  
7
7
246  
252  
264  
276  
279  
20.5  
21  
7
8
67.5 5.625  
69  
72  
5.75  
6
7
8
22  
7
8
73.5 6.125  
79.5 6.625  
23  
8
8
23.25  
0
6
81  
90  
6.75  
7.5  
280.5 23.375  
283.5 23.625  
289.5 24.125  
301.5 25.125  
310.5 25.875  
8
9
0
7
SV4.5CGV-1  
91.5 7.625  
0
7
SV4.5FA OR  
Termination  
93  
96  
7.75  
8
SV4.5FB Flashing  
AND SV4.5SC  
0
7
9
9
STORM COLLAR  
97.5 8.125  
102 8.5  
103.5 8.625  
315  
26.5  
9
10  
7
2
0
1
0
0
0
0
0
0
0
3
3
2
0
0
4
3
4
325.5 27.125  
0
330  
336  
345  
27.5  
28  
0
8
108  
114  
117  
9
0
8
9.5  
9.75  
0
1
1
0
1
0
0
0
1
2
0
1
0
0
0
0
0
0
0
5
0
1
1
6
0
0
0
0
0
3
3
3
0
4
0
4
2
0
0
0
0
0
0
3
0
4
6
5
4
5
6
4
3
5
1" (25.4 mm)  
Minimum  
Clearance to  
Combustibles  
28.75  
10  
10  
0
10  
11  
8
349.5 29.125  
372 31  
118.5 9.875  
126 10.5  
130.5 10.875  
376.5 31.375  
379.5 31.625  
418.5 34.875  
0
9
SV4.5VF  
11  
0
11  
9
Firestop/Spacer  
135  
138  
11.25  
11.5  
423  
465  
35.25  
38.75  
0
10  
139.5 11.625  
142.5 11.875  
0
10 10  
40' Max.  
(12.2 M)  
6' Min.  
SV4.5L6/12/24/36/48  
Vent Sections  
Effective Vent Length  
Model  
Effective Length  
(1.8 M)  
Note: Convert inches into metric equivalent  
measurement, as follows:  
When using Secure Flex,  
use Firestop/Spacer  
SF4.5VF  
SV4.5L6  
SV4.5L12  
SV4.5L24  
SV4.5L36  
SV4.5L48  
4-1/2"  
10-1/2"  
22-1/2"  
34-1/2"  
46-1/2"  
Millimeters (mm) = Inches x 25.4  
Centimeters (cm) = Inches x 2.54  
Meters (M) = Inches x .0254  
Table 7  
Figure 16  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Push the vent component against the previous  
section until it fully engages, then twist the  
componentclockwiserunningthedimplesdown  
and along the incline channels until they seat at  
the end of the channels. This seating position  
is indicated by the alignment of the arrow and  
dimple as shown in Figure 18.  
B. Attach vent components to appliance  
-SecureVentSV4.5direct-ventsystemcompo-  
nents are unitized concentric pipe components  
featuring positive twist lock connections (see  
Figure 18).  
Vertical (Offset) Installation  
Analyze the vent routing and determine the  
quantities of vent sections and number of el-  
bows required. Refer to Vertical Vent Figures  
and Tables on Page 17 to select the type of  
vertical installation desired. Vent sections are  
available in net lengths of 4-1/2" (114 mm),  
10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2"  
(876 mm) and 46-1/2" (1181 mm). Refer to the  
Vent Section Length Chart on Page 14 for an  
aidinselectinglengthcombinations.Elbowsare  
available in 90° and 45° configurations. Refer  
to Figure 20 for the SV4.5E45 and SV4.5E90  
elbow dimensional specifications.  
All of the appliances covered in this document  
are fitted with collars having locking inclined  
channels. The dimpled end of the vent compo-  
nents fit over the appliance collar to create the  
positive twist lock connection.  
D. Install firestop/spacer at ceiling - When  
usingSecureVent,useSV4.5VFrestop/spacer  
at ceiling joists; when using Secure Flex, use  
SF4.5VF firestop/spacer. If there is living space  
abovetheceilinglevel,therestop/spacermust  
be installed on the bottom side of the ceiling.  
If attic space is above the ceiling, the firestop/  
spacer must be installed on the top side of  
the joist. Route the vent sections through the  
framed opening and secure the firestop/spacer  
with 8d nails or other appropriate fasteners at  
each corner. Remember to maintain 1" (25  
mm) clearance to combustibles, framing  
members, and attic or ceiling insulation  
whenrunningverticalchimneysections.Attic  
insulation shield may be used to obtain the  
required clearances indicated here (order  
H3907, SV4.5ARSA, Attic insulation shield  
with adjustable height from 12"-22"). See  
installation accessories table on Page 32.  
The gap between the vent pipe and a vertical  
firestop can be sealed with non-combustible  
caulking.  
Align the dimple (four places) of the  
upper vent section with the opening  
of the locking incline channel on the  
lower vent section or appliance col-  
lar. Twist vent component clockwise  
to engage and seal until arrow and  
Where required, a telescopic vent section  
(SV4.5LA) may be used to provide the installer  
withanoptionininstallingintightand confined  
spaces or where the vent run made up of fixed  
length pieces develops a joint in a undesirable  
location, or will not build up to the required  
length. The SV4.5LA Telescopic Vent Section  
has an effective length of from 1-1/2" (38 mm)  
to 7-1/2 " (191 mm). The SV4.5LA is fitted with  
a locking inclined channel end (identical to a  
normalventsectioncomponent)andaplainend  
with 3 pilot holes. Slip the plain end over the  
locking channel end of a standard SV4.5 vent  
component the required distance and secure  
with three screws.  
dimple align.  
Arrow  
Dimple  
Locking Incline  
Channel  
Connected Vent  
Sections  
Arrow  
Appliance Collar or  
Vent Section  
Figure 18  
Maintain a minimum 1" (25 mm) clear-  
ance to combustible materials for all  
vertical vent components. Clearances for  
all horizontal vent components are 3"  
(76 mm) on top, 1" (25 mm) on sides and 1"  
(25 mm) on the bottom.  
E. Support the vertical vent run sections -  
To attach a vent component to the appliance  
collar, align the dimpled end over the collar,  
adjusting the radial alignment until the four  
locking dimples are aligned with the inlet of  
the four inclined channels on the collar (refer to  
Figure 18). Push the vent component against  
the collar until it fully engages, then twist the  
component clockwise, running the dimples  
down and along the incline channels until they  
seat at the end of the channels.  
Note-Properventingsupportisveryimportant.  
The weight of the vent must not be supported  
by the fireplace in any degree.  
Support the vertical portion of the venting  
system every 8 feet (2.4m) above the fireplace  
vent outlet.  
A. Frame ceiling opening - Use a plumb line  
from the ceiling above the appliance to locate  
center of the vertical run. Cut and/or frame an  
opening, 10-1/2" x 10-1/2" (267 mm x 267  
mm)insidedimensions, aboutthiscentermark  
(Figure 17).  
The unitized design of the Secure Vent com-  
ponents will engage and seal both the inner  
and outer pipe without the need for sealant or  
screws. If desired a #6 x 1/2" screw may be  
used at the joint, but it is not required as the  
pipe will securely lock when twisted.  
Roof Framing  
10-1/2" Min.  
(267 mm)  
Blocking  
C.Attachventcomponentstoeachother-Other  
vent sections may be added to the previously  
installedsectioninaccordancewiththerequire-  
ments of the vertical vent figures and tables.  
Support Straps  
(Plumber's tape)  
10-1/2" Min.  
(267 mm)  
8 feet (2.4 m)  
Maximum  
To add another vent component to a length of  
ventrun,alignthedimpledendovertheinclined  
channel end of the previously installed section,  
adjustingtheradialalignmentuntilthefourlock-  
ingdimplesarealignedwiththeinletsofthefour  
incline channels of the previous section.  
Ceiling Framing  
Plumb Bob  
1 inch (25.4  
mm)minimum  
clearance to  
combustibles  
Figure 19  
Figure 17  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
K. Install the vertical termination - The final  
step involves installation of the SV4.5CGV-1  
Vertical Termination. Extend the vent sections  
to the height as shown in the "Vertical vent ter-  
mination section" on Page 6. The SV4.5CGV-1  
Vertical Termination (Figure 23) installs in the  
exact same fashion as any other Secure Vent  
section. Align the termination over the end of  
the previously installed section, adjusting the  
radial alignment until the four locking dimples  
of the termination are aligned with the inlets of  
thefourinclinechannelsofthelastventsection.  
Pushtheterminationdownuntilitfullyengages,  
thentwisttheterminationclockwiserunningthe  
dimples down and along the incline channels  
until they seat at the end of the channels.  
One method of support is by utilizing field pro-  
vided support straps (conventional plumber's  
tape). Secure the plumber's tape to the framing  
members with nails or screws. Loop the tape  
around the vent, securing the ends of the tape  
totheframing.Ifdesired,sheetmetalscrews#6  
x 1/2" length may be used to secure the support  
straps to the vent pipe. See Figure 19.  
C
D
F.Changeventdirectiontohorizontal/inclined  
run - At transition from or to a horizontal/in-  
clined run, install the SV4.5E45 and SV4.5E90  
elbows in the same manner as the straight vent  
sections. The elbows feature a twist section to  
allow them to be routed about the center axis  
of their initial collar section to align with the  
required direction of the next vent run element.  
Twist elbow sections in a clockwise direction  
onlysoastoavoidthepossibilityofunlocking  
any of the previously connected vent sections  
(see Figure 20).  
Framing Dimensions for Roof  
Inches (millimeters)  
Pitch  
0/12  
C
D
10-1/2 in.  
(267 mm)  
10-1/2 in.  
(267 mm)  
6/12  
10-1/2 in.  
(267 mm)  
12 in.  
(305 mm)  
12/12  
10-1/2 in.  
(267 mm)  
17 3/4 in.  
(451 mm)  
Figure 21  
I. Install the roof flashing - Extend the vent  
sections through the roof structure. Install the  
roof flashing over the vent section and posi-  
tion such that the vent column rises vertically  
(use carpenters level) (Figure 22). Nail along  
perimeter to secure flashing or adjust roofing  
to overlap the flashing edges at top and sides  
only and trim where necessary. Seal the top  
and both sides of the flashing with waterproof  
caulking.  
8-1/8"  
(206 mm)  
4-13/16  
(122 mm)  
Swivel Joint  
Swivel Joint  
(360° swivel)  
SV4.5E45  
(360° swivel)  
SV4.5E90  
90° Elbow)  
45° Elbow)  
Figure 20  
G.Continueinstallationofhorizontal/inclined  
sections - Continue with the installation of the  
straight vent sections in horizontal/inclined run  
as described in Step C. Install support straps  
every5'(1.52m)alonghorizontal/inclinedvent  
runs using conventional plumber’s tape. It is  
very important that the horizontal/inclined  
run be maintained in a straight (no dips) and  
recommended to be in a slightly elevated  
plane, in a direction away from the fireplace  
of 1/4" rise per foot (20 mm per meter) which  
is ideal, though rise per foot run ratios that are  
smaller are acceptable all the way down to at or  
near level. Use a carpenter’s level to measure  
from a constant surface and adjust the support  
straps as necessary.  
Figure 23  
J. Install the storm collar - Install the storm  
collar, supplied with the flashing, over the  
vent/flashing joint. See Figure 22. Loosen  
the storm collar screw. Slide collar down until  
it meets the top of the flashing. Tighten the  
adjustingscrew.Applynon-combustiblecaulk-  
ing or mastic around the circumference of the  
joint to provide a water tight seal.  
If the vent system extends more than 5' (1.5  
m) above the roof flashing, stabilizers may be  
necessary. Additional screws may be used at  
section joints for added stability. Guide wires  
may be attached to the joint for additional sup-  
port on multiple joint configurations.  
Storm  
Collar  
Flashing  
It is important to maintain the required clear-  
ancestocombustibles:1"(25mm)atallsides  
forallverticalruns;and3"(76mm)atthetop,  
1" (25 mm) at sides, and 1" (25 mm) at the  
bottom for all horizontal/inclined runs.  
H. Frame roof opening - Identify location for  
vent at the roof. Cut and/or frame opening per  
Roof Framing Chart and Figure 21.  
Figure 22  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VERTICAL VENT FIGURES/TABLES  
Table A  
Notes:  
H Maximum  
feet (meter)  
(1.524)  
V Minimum  
feet (meter)  
Elbow Only  
• Secure Vent™ (rigid vent pipe) is shown  
intheFigures;SecureFlex(flexiblevent  
pipe) may also be used.  
H
5
• It is very important that the horizontal/in-  
clined run be maintained in a straight (no  
dips) and recommended to be in a slightly  
elevated plane, in a direction away from the  
fireplace of 1/4" rise per foot (20 mm per  
meter) which is ideal, though rise per foot  
run ratios that are smaller are acceptable all  
the way down to at or near level.  
SV4.5VF (Secure Vent), SF4.5VF (Secure  
Flex) firestop/spacer must be used anytime  
vent pipe passes through a combustible  
floor or ceiling. SV4.5HF (Secure Vent),  
SF4.5HF (Secure Flex) firestop/spacer must  
be used anytime vent pipe passes through  
a combustible wall.  
5
(1.524)  
(3.048)  
(4.572)  
(6.096)  
1
(0.305)  
(0.610)  
(0.914)  
(1.219)  
u Ceiling Firestop /  
Spacer (SV4.5VF)  
10  
15  
20  
2
3
4
V + V + H = 40 feet (12.2 m) Max.  
H = 20 feet (6.096 meters) Max.  
1
V1  
V
Example: If 20 feet of (H) horizontal vent run  
is needed, then 4 feet minimum of (V) vertical  
vent will be required.  
Two 45 degree elbows may be used in place  
of one 90 degree elbow. The same rise to  
run ratios, as shown in the venting Figures  
for90elbows, mustbefollowedif45degree  
elbows are used.  
• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF  
VERTICALRISEEXCEPTWHEREANELBOW  
IS THE ONLY VERTICAL COMPONENT IN  
THE SYSTEM (See Figure 30).  
This table shows a 1(V) to 5(H) ratio. For  
every 1 foot of (V) vertical, you are allowed 5  
feet of (H) horizontal run, up to a maximum  
horizontal run of 20 feet.  
vWall Firestop/  
Spacer (SV4.5HF)  
An elbow is acceptable as 1 foot of vertical  
rise except where an elbow is the only vertical  
component in the system (see Figure 30).  
uWhen using Secure Flex, use Firestop /  
vSWphaecnerusSiFn4g.5SVeFc.ure Flex, use Firestop /  
Spacer SF4.5HF.  
Figure 25 - Top Vent - TWO 90 DEGREE ELBOWS  
WARNING  
UnderNoCircumstances,MaySepa-  
rate Sections of Concentric Flexible  
Vent Pipe Be Joined Together.  
Example: If 20 feet total (H+H1) horizontal  
vent run is needed, then 4 feet minimum of  
(V) vertical vent will be required.  
Table B  
V Minimum  
(meter)  
Elbow Only  
(0.305)  
H + H Maximum  
1
feet  
5
(meter)  
(1.524)  
(1.524)  
(3.048)  
(4.572)  
(6.096)  
feet  
This table shows a 1(V) to 5(H) ratio. For  
every 1 foot of (V) vertical, you are allowed  
5 feet of (H+H ) horizontal run up to a maxi-  
mum total ho1rizontal run of 20 feet.  
5
1
2
3
4
An elbow is acceptable as 1 foot of verti-  
cal rise except where an elbow is the only  
vertical component in the system (see  
Figure 30).  
10  
15  
20  
(0.610)  
(0.914)  
(1.219)  
H + H = 20 feet (6.096 m) Max.  
1
V + V + H + H = 40 feet (12.192 m) Max.  
1
1
Ceiling  
u
40 feet  
uCeiling Firestop /  
(12.2 meters)  
Firestop / Spacer  
(SV4.5VF)  
Spacer (SV4.5VF)  
V
1
Wall Firestop/  
Spacer (SV4.5HF)  
Maximum  
v
H
uWhen using Secure Flex, use  
Firestop / Spacer SF4.5VF  
V
vWhen using Secure Flex, use  
H
1
Firestop / Spacer SF4.5HF  
WhenusingSecureFlex,useFirestop/Spacer  
SF4.5VF  
u
Figure 26- Top Vent - THREE ELBOWS  
Figure 24 - Top Vent - STRAIGHT  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HORIZONTAL(OUTSIDEWALL)TERMINATION  
SYSTEM  
Support the vertical portion of the venting system  
every 8 feet (2.4m) above the fireplace vent outlet.  
Support Brackets  
Building  
Support  
Framing  
See Figures 27, and Figures 30 to 33 on Pages  
18, 20 and 21 and their associated Horizontal  
VentTablewhichillustratethevarioushorizontal  
venting configurations that are possible for use  
with these appliances. Secure Vent™ pipe ap-  
plications are shown in these figures; Secure  
Flexpipemayalsobeused. AHorizontalVent  
Tablesummarizeseachsystem’sminimumand  
maximum vertical and horizontal length values  
that can be used to design and install the vent  
components in a variety of applications.  
Horizontal / Inclined Run  
SV4.5 HT-2  
Termination  
Shown  
SV4.5E90  
Elbow  
SV4.5L6/12/24/36/48  
Vent Sections  
Exterior  
Wall  
u Firestop / Spacer  
SV4.5VF  
Ceiling  
Support Bracket Spacing  
Every 5 ft (1.52 m)  
Vertical  
Rise  
u When Using Secure Flex,  
Use Firestop / Spacer SF4.5VF  
See Figure 19 on Page 15 for vertical  
vent section support.  
SV4.5 HT-2  
Termination  
Shown  
Bothofthesehorizontalventsystemsterminate  
through an outside wall. Building Codes limit or  
prohibit terminating in specific areas. Refer to  
Figure 7 on Page 7 for location guidelines.  
Fireplace  
Figure 27  
Secure Vent SV4.5 direct-vent system compo-  
nents are unitized concentric pipe components  
featuring positive twist lock connection, (refer  
to Figure 18 on Page 15). All of the appli-  
ances covered in this document are fitted with  
collars having locking inclined channels. The  
dimpled end of the vent components fit over  
the appliance collar to create the positive twist  
lock connection.  
Push the vent component against the collar  
until it fully engages, then twist the component  
clockwise,runningthedimplesdownandalong  
the incline channels until they seat at the end  
of the channels. The unitized design of the  
Secure Vent components will engage and seal  
both the inner and outer pipe elements with the  
same procedure. Sealant and securing screws  
are not required.  
Remember to maintain 1" (25 mm) clearance  
to combustibles, framing members, and attic  
or ceiling insulation when running vertical  
chimney sections.  
G. Support the vertical run sections -  
See Section E on Page 15.  
A. Plan the vent run -  
H.Changeventdirection- Attransitionfromor  
toahorizontal/inclinedrun,installtheSV4.5E45  
and SV4.5E90 elbows in the same manner as  
thestraightventsections. Theelbowsfeaturea  
twistsectiontoallowthemtoberoutedaboutthe  
center axis of their initial collar section to align  
with the required direction of the next vent run  
element. Twist elbow sections in a clockwise  
direction only so as to avoid the possibility of  
unlockinganyofthepreviouslyconnectedvent  
sections (see Figure 18 on Page 15).  
Analyze the vent routing and determine the  
types and quantities of sections required 4-  
1/2"(114mm), 10-1/2"(267mm), 22-1/2"(572  
mm),34-1/2"(876mm)and46-1/2"(1181mm)  
net section lengths are available. It is recom-  
mended that you plan the vent lengths so that a  
jointdoesnotoccurattheintersectionofceiling  
or roof joists. Make allowances for elbows as  
indicated in Figure 20 on Page 16.  
Note: An elbow may also be attached to the  
appliance collar. Attach in the same manner  
as you would a vent section.  
E. Attach vent components to each other  
- Other vent sections may be added to the  
previously installed section in accordance with  
the requirements of the vent tables. To add  
another vent component to a length of vent  
run, align the dimpled end of the component  
over the inclined channel end of the previously  
installed section, adjusting the radial alignment  
until the four locking dimples are aligned with  
the inlets of the four incline channels of the  
previous section.  
Maintain a minimum 1" (25 mm) clearance to  
combustibles on the vertical sections. Clear-  
ances for the horizontal runs are; 3" (76 mm)  
on top, 1" (25 mm) on sides, and 1" (25 mm)  
at the bottom.  
I. Continue installation of horizontal/inclined  
sections - Continue with the installation of the  
straightventsectionsinhorizontal/inclinedrun  
as described in Step E. Install support straps  
every 5 ft. (1.52 m) along horizontal/inclined  
vent runs using conventional plumber’s tape.  
B. Frame exterior wall opening -  
Locate the center of the vent outlet on  
the exterior wall according to the dimen-  
sions shown in Figure 12 on Page 10. Cut  
and/or frame an opening, 10-1/2" x 12-1/8"  
(267 mm x 308 mm) inside dimensions, about  
this center.  
Push the vent component against the previous  
section until it fully engages, then twist the  
component clockwise running the dimples  
down and along the incline channels until they  
seat at the end of the channels. This seating  
position is indicated by the alignment of the  
arrow and dimple as shown in Figure 18 on  
Page 15.  
See Figure 27, it is very important that the  
horizontal/inclined run be maintained in a  
straight (no dips) and recommended to be in  
a slightly elevated plane, in a direction away  
from the fireplace of 1/4" rise per foot (20 mm  
per meter) which is ideal, though rise per foot  
run ratios that are smaller are acceptable all the  
way down to at or near level.  
C. Frame ceiling opening - If the vertical route  
istopenetrateaceiling, useplumblinetolocate  
thecenterabovetheappliance.Cutand/orframe  
an opening, 10-1/2" x 10-1/2" (267 mm x 267  
mm)insidedimensions,aboutthiscenter(refer  
to Figure 17 on Page 15).  
F. Install firestop/spacer at ceiling -  
WhenusingSecureVent, useSV4.5VFrestop/  
spaceratceilingjoists;whenusingSecureFlex,  
use SF4.5VF firestop/spacer. If there is living  
space above the ceiling level, the firestop/  
spacer must be installed on the bottom side of  
theceiling. Ifatticspaceisabovetheceiling, the  
firestop/spacermustbeinstalledonthetopside  
ofthejoist. Routetheventsectionsthroughthe  
framed opening and secure the firestop/spacer  
with 8d nails or other appropriate fasteners at  
each corner.  
It is important to maintain the required clear-  
ancestocombustibles:1"(25mm)atallsides  
forallverticalruns;and3"(76mm)atthetop,  
1" (25 mm) at sides, and 1" (25 mm) at the  
bottom for all horizontal/inclined runs.  
D. Attach vent components to appliance - To  
attachaventcomponenttotheappliancecollar,  
align the dimpled end over the collar, adjust-  
ing the radial alignment until the four locking  
dimples are aligned with the inlets of the four  
incline channels on the collar (refer to Figure  
18 on Page 15).  
Use a carpenter’s level to measure from a  
constant surface and adjust the support straps  
as necessary.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
J. Assemble vent run to exterior wall - If not  
previously measured, locate the center of the  
vent at the exterior wall. Prepare an opening as  
describedinStep B. Assemble theventsystem  
topointwheretheterminusofthelastsectionis  
located relative to the exterior surface to which  
the termination is to be attached as shown in  
Figure 29 and Table 8.  
To help minimize water infiltration it is  
recommended that the Firestop/Spacer  
(SV4.5HF) be installed on the exterior  
side of the wall.  
SV4.5 HT-2  
Termination  
7"  
(178)  
10¹⁄₂"  
12¹⁄₈"  
(267mm)  
(308 mm)  
5¹⁄₈"  
(130 mm)  
3"  
(76 mm)  
If the terminus of the last section is not within  
this distance, use the telescopic vent section  
SV4.5LA, as the last vent section. For wall  
thicknesses greater than that shown in Figure  
29, refer to Table 8 on Page 20. This table lists  
the additional venting components needed (in  
addition to the termination and adaptor) for a  
particular range of wall thicknesses.  
1"  
Adapter  
SV4.5RCH  
(25.4 mm)  
Note: Centerline of Vent Piping is  
NOT the Same as the Centerline of  
the Framed Opening.  
See Figure 12 on Page 10 for Min.  
Distance to Base of Appliance.  
K. Attach termination adaptor - Attach the  
adaptor (SV4.5RCH - provided with the termi-  
nation) to the vent section or telescoping vent  
section), elbow or appliance collar as shown  
in Figure 28 in the same manner as any SV4.5  
vent component (refer to Step E).  
6 to 48 inch Vent Section,  
Telescopic vent section,  
Elbow or Appliance Collar  
Base of Appliance  
Figure 28 - INSTALLING SQUARE HORIZONTAL TERMINATION (SV4.5HT-2)  
L. Install Firestop/Spacer at exterior wall  
- When using the square termination, install  
SV4.5HF (Secure Vent™), SF4.5HF (Secure  
Flex™) Firestop/Spacer over the opening at  
the exterior side of the framing, long side up,  
with the 3 inch spacer clearance at the top as  
shown in Figure 28, and nail into place.  
Maximum Wall Thickness  
Use silicone caulking to seal  
9-1/4 in. (235 mm)  
the top and sides of the  
termination, up to the  
underlayment, stucco, or  
masonry wall surface.  
Exterior Surface of Siding  
Exterior Surface of  
Framing  
Interior Surface of  
Finished Wall  
Maximum Extent of  
Vent Run Sections  
Relative to Exterior  
Surface of Framing  
Siding  
6 in. to 9-1/4 in.  
(152 to 235 mm)  
Caulk  
(TheFirestop/Spacermayalsobeinstalledoverthe  
opening at the interior side of the framing).  
Last Vent Section.  
Use Telescopic Vent  
Section (SV4.5LA), If  
Necessary  
SV4.5 HT-2  
Termination  
M. Install the desired termination -  
1. Install the square termination (SV4.5HT-2)  
For the last step, from outside the exterior wall,  
slidethecollarsoftheterminationontotheadap-  
tor(theouterovertheouterandtheinnerinside  
theinner)untiltheterminationseatsagainstthe  
exteriorwallsurfacetowhichitwillbeattached.  
Orient the housing of the termination with the  
arrowpointedupwards. Securethetermination  
totheexteriorwall. Thehorizontaltermination  
must not be recessed into the exterior wall  
or siding by more than the 1-1/4" (32 mm) as  
shown in Figure 29.  
Caulk  
SV4.5 HT-2  
Termination  
Adapter  
SV4.5RCH  
1-1/4” Maximum Recess of  
Square Termination  
into Exterior Finishing Material  
Stucco  
For thicknesses greater  
v
than 10", see Table 8  
Venting Connection and Exterior Wall Recessing of the Horizontal Square  
Termination (SV4.5HT-2).  
Figure 29  
IMPORTANT: The vent termination is hot  
whileinoperationandforaperiodoftime  
following the use of the fireplace. Young  
children should be carefully supervised  
when they are in the same area as a hot  
termination. To prevent contact with hot  
surfaces, we recommend the use of a  
Termination Guard. See Page 32. This  
can be purchased at your local dealer.  
Horizontal terminations have been designed to perform in a wide range of weather condi-  
tions. Our terminations meet or exceed industry standards.  
When selecting the locations of your horizontal terminations, do not place the termina-  
tion where water from eaves and adjoining rooflines may create a heavy flow of cascad-  
ing water onto the termination cap. If the cap must be placed where the possibility of  
cascading water exists, it is the responsibility of the builder to direct the water away  
from the termination cap by using gutters or other means.  
Take care to carefully follow the installation instructions for the termination, including  
the use of silicone caulking where required.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
See Table 8 as an aid in venting component selection for a particular  
range of exterior wall thicknesses.  
Table C  
V Minimum  
feet (meter) feet (meter)  
(0.914) Elbow Only  
H Maximum  
Venting Components Required for Various Exterior Wall Thick-  
nesses, when using Square Termination Kit (SV4.5HT-2)  
3
Vent Components Required Exterior Wall Thickness - inches (mm)  
Termination Kit Only  
6 to 9-1/4 (152 to 235)  
Square termination  
(SV4.5HT-2) shown.  
H
TerminationKitand 6In.Vent  
Section (SV4.5L6)  
10-3/4 to 14 (273 to 356)  
V
Termination Kit and 12 in.  
Vent Section (SV4.5L12)  
16-3/4 to 20 (426 to 508)  
Termination Kit and Tele-  
scopic Section (SV4.5L12)  
11-3/4 to 20 (299 to 508)  
Note:SeeFigure29showingwallthicknessrange  
when using SV4.5HT-2 termination kit only.  
Table 8  
When using Secure Flex,  
Wall  
use Firestop/Spacer  
SF4.5HF  
Firestop/Spacer  
(SV4.5HF)  
HORIZONTAL VENT FIGURES/TABLES  
Notes:  
SeeTable8asanaidinventingcomponentselectionforaparticular  
range of exterior wall thicknesses.  
• Secure Vent™ components (rigid vent pipe and terminal) are shown  
in the Figures; Secure Flex™ components (flexible vent pipe and  
terminal) may also be used.  
Figure 30 - Top Vent -  
ONE 90 DEGREE ELBOW - ELBOW CONNECTION AT APPLIANCE  
Two 45 degree elbows may be used in place of one 90 degree elbow.  
The same rise to run ratios, as shown in the venting Figures for 90  
elbows, must be followed if 45 degree elbows are used.  
Example: If20feetof(H) hori-  
Table D  
V Minimum  
zontal vent run is needed, then  
4 feet minimum of (V) vertical  
vent will be required.  
SV4.5VF(SecureVent),SF4.5VF(SecureFlex)restop/spacermustbe  
used anytime vent pipe passes through a combustible floor or ceiling.  
SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must  
be used anytime vent pipe passes through a combustible wall.  
H Maximum  
feet (meter) feet  
(meter)  
(0.305)  
(0.610)  
(0.914)  
(1.219)  
This table shows a 1(V) to  
5(H) ratio. For every 1 foot of  
vertical, you are allowed 5 feet  
of (H) horizontal run up to a  
maximum (H) horizontal run  
of 20 feet.  
5
(1.524)  
(3.048)  
(4.572)  
(6.096)  
1
2
3
4
10  
15  
20  
• It is very important that the horizontal/inclined run be maintained  
in a straight (no dips) and recommended to be in a slightly elevated  
plane, in a direction away from the fireplace of 1/4" rise per foot (20  
mm per meter) which is ideal, though rise per foot run ratios that are  
smaller are acceptable all the way down to at or near level.  
V + H = 40 feet (12.2 m) Max.  
H = 20 feet (6.096 m) Max.  
H
The tables show a 1(V) to 5(H) ratio up to a maximum horizontal run  
of 20 feet except for installations where an elbow is the only vertical  
vent section in the system (see Figure 30).  
When using Secure Flex,  
use Firestop/Spacer  
SF4.5VF.  
V
• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT  
WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE  
SYSTEM. See Figure 30.  
When using Secure Flex,  
use Firestop/Spacer  
SF4.5HF.  
Wall Firestop/Spacer  
(SV4.5HF)  
WARNING  
Under no circumstances, may separate sections of  
concentric flexible vent pipe be joined together.  
Ceiling  
Square termination  
(SV4.5HT-2) shown.  
Firestop/Spacer  
(SV4.5VF)  
See Table 8 as an aid in venting component selection for  
a particular range of exterior wall thicknesses.  
Figure 31 - Top Vent - ONE 90 DEGREE ELBOW -  
ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HORIZONTAL VENT FIGURES / TABLES (CONTINUED)  
Table E  
H + H Maximum  
Wall Firestop/Spacer  
(SV4.5HF)  
V Minimum  
feet (meter)  
Elbow Only  
1
feet  
3
(meter)  
(0.914)  
(1.524)  
(3.048)  
(4.572)  
(6.096)  
H
5
1
2
3
4
(0.305)  
(0.610)  
(0.914)  
(1.219)  
H
1
10  
15  
20  
V
Note - When using  
TM  
Secure Flex , use  
V + H + H = 40 feet (12.2 m) Max.  
1
Wall Firestop/Spacer  
(SV4.5HF)  
Firestop/Spacer SF4.5VF.  
H + H = 20 feet (6.096 m) Max.  
1
When using Secure Flex,  
use Firestop/Spacer  
SF4.5HF.  
Ceiling  
Example: If 20 feet of (H + H1) horizontal vent run is needed,  
then 4 feet minimum of (V) vertical vent will be required.  
Firestop/Spacer  
(SV4.5VF)  
Square termination (SV4.5HT-2) shown.  
This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V)  
vertical, you are allowed 5 feet of (H+ H ) horizontal run, up  
to a maximum horizontal run of 20 feet. 1  
See Table 8 on Page 20 as an aid in venting  
component selection for a particular range of  
exterior wall thicknesses.  
An elbow is acceptable as 1 foot of vertical rise except where  
an elbow is the only vertical component in the system. See  
Figure 30.  
Figure 32 - Top Vent - TWO 90 DEGREE ELBOWS  
Table F  
Square termination  
(SV4.5HT-2) shown.  
V Minimum  
feet (meter)  
Elbow Only  
H + H Maximum  
When using Secure Flex,  
use Firestop/Spacer  
SF4.5VF.  
1
feet  
5
(meter)  
(1.524)  
(1.524)  
(3.048)  
(4.572)  
(6.096)  
When using Secure  
H
1
Flex, use Firestop/Spacer  
SF4.5HF.  
5
1
2
3
4
(0.305)  
(0.610)  
(0.914)  
(1.219)  
10  
15  
20  
Ceiling  
Firestop/Spacer  
(SV4.5VF)  
H + H = 20 feet (6.096 m) Max.  
V + V + H1+ H = 40 feet (12.192 m) Max.  
H
1
1
Wall Firestop/Spacer  
(SV4.5HF)  
V
Example: If 20 feet total (H+H ) horizontal vent  
run is needed, then 4 feet minim1um of (V) vertical  
vent will be required.  
1
V
See Table 8 on Page  
20 as an aid in venting  
component selection for  
aparticularrangeofexte-  
rior wall thicknesses.  
This table shows a 1(V) to 5(H) ratio. For every 1  
foot of (V) vertical, you are allowed 5 feet of (H+  
H1) horizontal run, up to a maximum horizontal  
run of 20 feet.  
Anelbowisacceptableas1footofverticalriseexcept  
where an elbow is the only vertical component in  
the system. See Figure 30.  
Wall Firestop/Spacer  
(SV4.5HF)  
Figure 33 - Top Vent - THREE 90 DEGREE ELBOWS  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VERTICAL OR HORIZONTAL VENTING  
USING SECuRE FLEX™ KITS AND COM-  
PONENTS  
Flex Vent  
Note: Outer Pipe Is Pulled Away To Show  
The Detail of The Inner Pipe  
Securing Screw - 3 places,  
equally spaced, just below  
gear clamp.  
APPLY ONLY MIL-PAC BLACK  
HIGH TEMPERATURE SEALANT  
(Cat. No. 10K81) to the outside  
surface of both collars of the  
adaptor (be especially careful to  
fill the grooves of the outer collar  
tobecoveredbytheexiblepipe)  
and slide flexible pipe over inner  
and outer adaptor collars.  
Secure Flex™ venting kits and components  
may be used in any venting application in place  
of rigid Secure Vent™ (SV4.5) direct-vent  
components. All restrictions, clearances and  
allowances that pertain to the rigid piping apply  
to the flexible venting. Secure Flex kits may  
notbemodified;also,undernocircumstances  
may separate sections of flex pipe be joined  
together.  
Gear Clamps  
Secure Flex kits may be added to the end of a  
vent run made up of rigid Secure Vent (SV4.5)  
vent sections provided that doing so does not  
violateanyoftheventinglength,height,routing,  
horizontaltoverticalratiorequirementsorclear-  
ance considerations detailed in this manual.  
1-3/4 inch (44 mm) Flexible  
pipeandadaptoroutercollar  
overlap  
1-3/4 in. (44 mm) Flexible  
pipeandadaptorinnercollar  
overlap  
Adaptor (SV4.5RF)  
Securing screw  
- 3 places, 120° apart  
(equally spaced) just  
below gear clamp  
Secure Flex kits come with an adaptor that  
can be fitted to the inclined channel end of  
the last Secure Vent (SV4.5) vent section in a  
rigid system in the exact same fashion as any  
other Secure Vent section. Align the dimpled  
end of the adaptor over the previously installed  
section or appliance collar, adjusting the radial  
alignment until the four locking dimples of the  
adaptor are aligned with the inlets of the four  
inclinechannelsofthelastventsectionorcollar.  
Push on the adaptor until it fully engages, then  
twisttheadaptorclockwiserunningthedimples  
down and along the incline channels until they  
seat at the end of the channels.  
Attach adaptor to appliance  
Figure 34  
Collar, or secure vent sections  
B. Install the Outer Flex Pipe -  
D. Install Firestop / Spacers at ceilings and walls  
- When Secure Flex penetrates a wall or ceiling,  
a firestop / spacer is required: use the SF4.5 VF  
firestop / spacer for ceilings and the SF4.5 HF  
firestop / spacer for walls. See the appropriate  
sectionsandFiguresshownthroughoutthevent-  
ing section for their installation requirements.  
1. Install the large gear clamp loosely around  
the outer flexible vent pipe, push it back out  
of the way.  
2. ApplyabeadofMill-PacBlack(700°F)high  
temperature sealant - Catalog No. 10K81  
to the outer adaptor collar; to the grooves  
of the collar which extend approximately 1  
inch from the end and to the flat surface,  
approximately 1-3/8 inches from the end.  
3. Pull and extend outer flexible vent pipe.  
4. Slidetheouterexpipeovertheadaptorcol-  
lar. Ensure the flexible vent pipe completely  
engages the adaptor collar to a distance of  
1-3/4 inches from the end, and that it is free  
from damage or tears.  
5. Slide the gear clamp down and tighten it  
fullytosecuretheexibleventtotheadaptor  
outer collar approximately 3/4 inch from the  
end of the flex.  
6. Install three screws, 120 degrees apart,  
through the flexible vent pipe and into the  
adaptor collar just below the gear clamp to  
provide additional security to the connec-  
tion.  
Flexible Vent  
Section  
Attach the flexible vent to the adaptor as fol-  
lows (see also Figure 34):  
A. Install the Inner Flex Pipe -  
1. Install the small gear clamp loosely around  
the inner flexible vent pipe, push it back out  
of the way.  
2. ApplyabeadofMill-PacBlack(700°F)high  
temperature sealant - Catalog No. 10K81  
to the inner adaptor collar, approximately  
1/2 inch from the end.  
3. Pull and extend the inner flexible vent pipe.  
4. Slidetheinnerexpipeovertheadaptorcol-  
lar. Ensure the flexible vent pipe completely  
engages the adaptor collar to a distance of  
1-3/4 inches from the end, and that it is free  
from damage or tears.  
5. Slide the gear clamp down and tighten it  
fullytosecuretheexibleventtotheadaptor  
inner collar approximately 3/4 inch from the  
end of the flex.  
5” (127 mm)  
Radius  
Minimum  
Figure 35  
E. Attach Flex Vent to Termination -  
Secure Flex components can be purchased  
separately and attached to bulk lengths of Se-  
cure Flex flexible tubing cut to size at the job  
site. Secure the flexible vent to the Secure Flex  
terminations in the same manner (see Figure  
34) as it was attached to the adaptor.  
C. Route Flex Vent -  
Ensure that the flex vent is properly routed to  
providetherequiredclearance.Donotallowthe  
flexible vent to bend in a radius tighter than 5"  
(127 mm). Refer to Figure 35. Space out the  
internalexventspacersevenly-approximately  
every 6 inches - and avoid kinking of inner pipe.  
Support horizontal sections of flex with metal  
straps at 2 foot (0.61 m) intervals.  
Note:SecureFlexventmustbeattachedtoSecure  
Flexterminationsonly.DONOTsubstituteSecure  
VentterminationsortheSecureVentadaptorfor  
Secure Flex components. The collars of Secure  
Flex terminations and adapters have a different  
diameter than that used with the Secure Vent  
pipe. Additionally, Secure Flex components  
have an extended length center tube for use in  
attaching the flexible vent.  
6. Install three screws, 120 degrees apart,  
through the flexible vent pipe and into the  
adaptor collar just below the gear clamp to  
provide additional security to the connec-  
tion.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Refer to Section A for millivolt appliances and  
Section B for electronic appliances. The gas  
valve is set in place and pre-wired at the factory  
on both models.  
2. Remove the electrical inlet cover plate from  
the side of the unit by removing the plate's  
securing screws. See Figure 12 on Page  
10.  
3. Remove the cover plate's knockout and then  
feed the power supply wire through the knock-  
out opening and into the unit junction box.  
4. Connect the black power supply wire to the  
red pigtail lead and the white power supply  
wire to the common terminal of the outlet  
as shown in Figures 37 and 38.  
5. Connect the ground supply wire to the pig-  
tail lead attached to outlet's green ground  
screw.  
6. Appliance-mounted ON/OFF burner control  
switch (rocker switch) is factory installed  
behind the bottom panel.  
Step 4. FIELD WIRING  
CAUTION  
A. Millivolt Wiring (See Figure 36) –  
Ground supply lead must be con-  
nected to the wire attached to the  
green ground screw located on the  
outletbox. SeeFigure38.Failureto  
dosowillresultinapotential safety  
hazard. The appliance must be  
electricallygroundedinaccordance  
withlocalcodesor,intheabsenceof  
localcodes, theNationalElectrical  
Code,ANSI/NFPA70-latestedition.  
(In Canada, the current CSA C22-1  
Canadian Electrical Code).  
1. Appliance-mounted ON/OFF burner control  
switch (rocker switch) is factory installed  
in the control compartment. An optional  
wall-mounted switch, wall thermostat, or  
one of the optional remote control kits may  
also be used.  
2. If a wall-mounted ON/OFF control or ther-  
mostat is selected mount it in a convenient  
location on a wall near the fireplace.  
3. Wire the control switch within the millivolt  
controlcircuit usingthe15feetof2conductor  
wire supplied with the unit.  
Optionalwall-mounted switch,wallthermo-  
stat, or one of the optional remote control  
kits may also be used.  
Note: The supplied 15 feet of 2 conductor wire  
has one end of each conductor connected to  
the gas valve circuit and the other end of each  
conductor placed loose inside the bottom  
compartment.  
7. If wall-mounted ON/OFF control or thermo-  
stat is to be used, mount it in a convenient  
location on a wall near the fireplace.  
8. If an optional wall-mounted control is to be  
used, wire it in the low voltage circuit as  
shown in Figure 37.  
CAUTION: Label all wires prior to disconnec-  
tionwhenservicingcontrols.Wiringerrorscan  
cause improper and dangerous operation.  
CAUTION: Do Not connect the optional wall  
switch to a 120V power supply.  
Note: The supplied 15 feet of 2 conductor wire  
has one end of each conductor connected to  
the gas valve circuit and the other end of each  
conductor placed loose inside the bottom  
compartment.  
ATTENTION: Au moment de l'entretien des  
commandes, étiquetez tous les fils avant de  
les débrancher. Des erreurs de cáblage peu-  
vent entraîner un fonctionnement inadéquat  
et dangereux.  
4. If an optional control switch is installed, turn  
theappliance-mountedON/OFFburnercontrol  
switch to the OFF position.  
B. Electronic Wiring (See Figure 37) –  
9. If an optional control switch is installed,  
turn the appliance-mounted ON/OFF burner  
control switch to the OFF position.  
10.After the wiring is complete, replace the  
cover plate.  
Verify proper operation after servicing.  
Note: The electronic appliance must be con-  
nected to the main power supply.  
S'assurer que l'appareil fonctionne adé-  
quatement une fois l'entretien terminé.  
1. Route a 3-wire 120VAC 60Hz 1ph power  
supply to the appliance junction box.  
WIRING DIAGRAM MILLIVOLT GAS VALVES  
THERMOPILE  
PILOT BURNER  
IGNITER-SENSOR  
ASSEMBLY  
WHITE  
ELECTRONIC  
WIRING DIAGRAM  
EV2  
EV1  
APPLIANCE- MOUNTED  
ON/OFF SWITCH  
GAS VALVE  
TP-TH  
BLUE (20)  
TP  
TH  
GROUND  
GAS VALVE  
BK/W(1)  
BK/W(1)  
JUNCTION BOX  
BLK  
CONNECTOR  
WALL-MOUNTED ON/OFF SWITCH (OPTIONAL)  
THERMOSTAT (OPTIONAL)  
BLACK (20)  
TRANSF  
120 V.  
W
WALL MOUNTED CONFIGURATION FOR FAN SWITCH (OPTIONAL)  
WHITE (6)  
GREEN LED  
24 V.  
APPLIANCE MOUNTED  
ON/OFF SWITCH  
BLACK (16)  
ELECTRONIC IGNITION  
CONTROL BOARD  
BK  
R
W
*WALL MOUNTED ON/OFF SWITCH (OPTIONAL)  
OR REMOTE CONTROL RECEIVER  
GR  
*Turn The Appliance-Mounted ON/OFF Burner Control Switch  
To The OFF Position If An Optional Control Switch Is Installed  
FAN  
(OPTIONAL)  
FACTORY WIRED  
FIELD WIRED  
JUNCTION BOX  
Figure 37  
Figure 36  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If required, access the valve (see Figure 40) by  
openingthelowercontrolpanel (seeinstruction  
sheet provided with the facade kit for additional  
information about the control panel).  
Step 6. CONNECTING GAS LINE  
120V, 60HZ, 1PH  
All codes require a shut-off valve mounted in  
the supply line. The orientation of the shut-off  
valveshouldfacethefront.Figure39 illustrates  
two methods for connecting the gas supply.  
A Sediment Trap is recommended to prevent  
moisture and debris in gas line from damaging  
the valve.  
* Wall-mounted  
ON/ OFF Blower  
Switch or Variable  
Speed Control Switch.  
The millivolt and electronic control valve has a  
3/8" (10mm) NPT thread gas supply inlet.  
Bringtheshutoffvalveontheendoftheex-line  
over to the hard pipe and tighten with wrenches  
from above through the firebox opening.  
Junction Box  
The flex-line method is acceptable in the U.S.A.  
where local codes permit, however, Canadian  
requirementsvarydependingonlocality.Instal-  
lation must be in compliance with local codes.  
These appliances are equipped with a gas flex-  
lineforuseinconnectingtheunittothegasline.  
See Figure 39 for flex-line description. The  
flex-line is rated for both natural and propane  
gas. A manual shut off valve is also provided  
with the flex-line.  
Secure all joints tightly using appropriate  
toolsandsealingcompounds(ensurepropane  
resistant compounds are used in propane ap-  
plications). Itisrecommendedtosealaround  
the gas line to prevent cold air leakage.  
Tab  
Broken  
Hot  
Side of  
Red  
Black  
Receptacle  
Neutral  
Side of  
Receptacle  
Gas Flex Line Connector  
3/8" NPT x  
Flare Fitting  
Gas  
1/2" x 3/8" Flare  
Shut-off Valve  
Valve  
Plug blower  
Tab Intact  
into this  
Green  
Ground  
Screw  
receptacle  
Note: The gas supply line  
must be installed in accor-  
dance with building codes  
by a qualified installer  
approved and/or licensed  
as required by the locality.  
In the Commonwealth of  
Massachusetts, installation  
must be performed by a  
licensed plumber or gas  
fitter.  
3/8" Flex Tubing  
Blower  
Field Wired  
Factory Wired  
Gas  
Ground  
1/2" x 3/8"  
Stub  
Reducer  
3/8" Nipple  
3/8" Union  
Figure 38 - J-BOX WIRING  
3/8" Close  
Nipple  
Step5.WIRING-OPTIONALFORCEDAIR  
BLOWER KIT (millivolt models only)  
3/8" Shut-off Valve  
Gas Solid Line Connector  
(See Figure 36 on Page 23)  
Figure 39 - GAS CONNECTION  
An electrical outlet box is provided for the  
installation of the LBLK-100 forced air blower  
kit. Electrical power must be provided to this  
boxtooperatetheseblowers. Installtheblower  
kit according to the installation instructions  
provided with the kit.  
Glass Door  
If the blower kit is to be installed at the time of  
installationoratalaterdate, themainpowersup-  
plyandwallswitchmustbeinstalledatthetimeof  
installation. This will require that the electrical  
connectionsmustbemadeBEFOREthereplace  
is framed and enclosed in the finished walls.  
Route a 3-wire, 120 VAC, 60 Hz, 1 ph power  
supply and connect to electrical receptacle wires  
and wall switch or wall rheostat.  
Gas Shut-  
Off Valve  
Burner  
ON/OFF Switch  
Push Button  
Piezo Igniter  
Gas Flex-  
Line  
Gas Valve  
Figure 40 - Control Compartment  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TEST ALL CONNECTIONS FOR GAS LEAKS  
(FACTORY AND FIELD):  
Theameshouldproject1"(25mm)beyondthe  
pilothoodatallthreeports(Figure41). Replace  
logs if removed for pilot inspection.  
Step 7. VERIFYING APPLIANCE OPERA-  
TION  
Turn on burner then observe the individual  
tongues of flame on the burner. Make sure  
all ports are open and producing flame evenly  
across the burner. If any ports are blocked, or  
partially blocked, clean out the ports.  
To light the burner; rotate the gas valve control  
knob counterclockwise to the “ON” posi-  
tion and turn “ON” the appliance mounted  
ON/OFF switch (or optional remote switch, if  
installed).  
WARNING  
Never use an open flame to  
check for leaks.  
Turn on gas supply and test for gas leaks using a  
gas leak test solution (also referred to as bubble  
leak solution). Note: Using a soapy water solu-  
tion is an effective leak test solution but it is not  
recommended, because the soap residue that is  
left on the pipes/fittings can result in corrosion  
over time.  
With gas line installed run initial system check-  
outbeforeclosingupthefrontoftheunit. Follow  
the pilot lighting instructions provided in the  
Care and Operation Manual. For piezo igniter  
location see Figure 40 on Page 24 (millivolt  
appliances only).  
MILLIVOLT  
Hood  
Igniter Rod  
Thermocouple  
Note:LightingInstructionsarealsofoundonthe  
literature tag tied to the gas piping next to the  
gas valve. To access the tag, open the bottom  
control panel (see instruction sheet provided  
with the facade kit for additional information  
about the control panel). See Figure 40 on  
Page 24.  
A. Lighttheappliance(refertothelightinginstruc-  
tions label in control compartment or care and  
operation manual).  
3/8" Min  
(9 mm)  
Pilot  
Nozzels  
Thermopile  
B. Brush all joints and connections with the gas  
leak test solution to check for leaks. If bubbles  
are formed, or gas odor is detected, turn the  
gas control knob (off/pilot/on) to the “OFF”  
position. Either tighten or refasten the leaking  
connection, then retest as described above.  
Figure 41  
When first lighting the appliance, it will take  
a few minutes for the line to purge itself of  
air. Once purging is complete, the pilot and  
burner will light and operate as indicated in  
the instruction manual. Subsequent lighting  
of the appliance will not require such purging.  
Inspect the pilot flame (remove logs, if neces-  
sary, handling carefully).  
Electronic Appliance Checkout  
Electronic Appliance Checkout  
C. Whenthegaslinesaretestedandleakfreebe  
sure to rinse off the leak testing solution.  
Tolighttheburner,turnONtheoptionalremote  
wall switch or turn the appliance mounted  
ON/OFF switch to the “ON” position. Ensure  
the igniter lights the pilot. The pilot flame  
should engulf the flame sensor as shown in  
Figure 42.  
Millivolt Appliance Checkout  
The pilot flame should be steady, not lifting  
or floating. Flame should be blue in color with  
traces of orange at the outer edge.  
The top 3/8" (10 mm) at the pilot generator  
(thermopile) and the top 1/8" minimum (tip)  
of the quick drop out thermocouple should be  
engulfed in the pilot flame.  
ELECTRONIC  
Hood  
Igniter Rod  
Flame  
Sensor  
Pilot  
Nozzels  
Figure 42  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 8. INSTALLING THE LOGS AND GLOWING EMBERS  
LOG SET  
Catalog Number H1237  
AFIREBOXLINERKITMUSTBEINSTALLEDBEFOREINSTALLINGLOGS.  
THIS APPLIANCE IS NOT APPROVED FOR OPERATION WITHOUT A  
FIREBOX LINER KIT INSTALLED (SOLD SEPARATELY). SEE PAGE 15  
IN CARE AND OPERATION MANUAL FOR ORDERING INFORMATION.  
INSTALL LINER KIT AND LOG SUPPORT BRACKET PER INSTRUCTIONS  
PROVIDED IN KIT.  
* Item  
Description  
A
B
C
D
E
Log, Rear  
Log, Left Middle  
Log, Right Middle  
Log, Left Front  
Log, Right Front  
Locate log set carton and plastic bag of glowing embers. Refer to the Log  
Set Placement Instructions (Figures 43 to 49) for detailed placement  
instructions for the logs and glowing embers.  
Proper log and ember placement is critical to encourage outstanding flame  
appearance and prevent sooting. These fires are designed to provide a  
rich orange/red glow on the logs.  
* Item "letters" above correspond to photos  
Note: Log setup is by design asymmetric. The fire is intentionally posi-  
A
C
E
tioned off center to provide a natural fire look.  
B
WARNING  
DO NOT attempt to install the logs until the  
appliance installation has been completed, the  
gas line connected and tested for leaks and the  
initial burner operation has been checked out.  
The size and position of the log set was engi-  
neered to give the appliance a safe, reliable  
and attractive flame pattern. Any attempt to use  
a different log set in the fireplace will void the  
warranty and will result in incomplete combus-  
tion, sooting, and poor flame quality.  
D
Logs get very hot and will remain hot up to one  
hour after gas supply is turned off. Handle only  
when logs are cool. Turn off all electricity to the  
appliance before you install logs and embers.  
This appliance is not designed to burn wood.  
Any attempt to do so could cause irreparable  
damage to the appliance and prove hazardous  
to your safety.  
If logs are not installed according to the log  
installation instructions, flame impingement  
andimpropercombustioncouldoccurandresult  
in soot and/or excessive production of carbon  
monoxide (CO), a colorless, odorless, toxic  
gas.  
Ember Burner Ports  
Glowing Embers  
Separate into Quarter  
Size (separate) Pieces  
This appliance is provided  
with enough Glowing Em-  
bers for several applica-  
tions, do not use all that is  
in a new bag at one time.  
For best glowing effect,  
replace the ember material  
annually.  
Log Support Bracket  
Complete the following before starting the log installation.  
Firebox  
• READ WARNINGS ON THIS PAGE BEFORE PROCEEDING  
Remove the front glass enclosure panel (see Glass Enclosure Panel  
1
2
Removal Instructions, Page 28).  
3
4
Remove the log set from the firebox and the bag of embers from the  
5
control compartment. Handle logs carefully to prevent breakage.  
Locating Pins - 5 Places  
Figure 43 - Log Set and Glowing Embers  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Place the rear log (A) as shown in Figure 44. Position the 2 holes  
on the bottom of the log over the corresponding locating pins (#1 &  
#2) and against the log support bracket. See Figures 43 and 44 for  
pin and rear bracket locations.  
4. Place the right front log (E) as shown in Figure 47. Position the hole  
on the bottom of log E over pins #4 and # 5.  
A
1
2
E
3
4
5
Figure 44 - Install Rear Log (A)  
Figure 47 - Install Right Front Log (E)  
2. Place the left middle log (B) as shown in Figure 45. Position the hole  
on the bottom of log B over the corresponding locating pin on Log A.  
5. Place the right middle log (C) as shown in Figure 48. Position log  
C behind Log E and resting on the "flat" on Log A.  
C
A
B
A
E
Figure 45 - Install Left Middle Log (B)  
3. Place the left front log (D) as shown in Figure 46. Position the hole  
Figure 48 - Install Right Middle Log (C)  
on the bottom of log D over pin# 3.  
6. Ember Placement - Separate the Embers (rockwool) into pieces  
about the size of a quarter (see Figure 43). Keep the pieces fluffed  
up, not matted. Distribute these pieces over the surface of the burner,  
as shown in Figure 49. Do not use more than is necessary. Ensure  
that the main burner ports remain uncovered by the ember material  
(see Figure 43).  
D
3
DONOTplaceembermaterialdirectly  
over the ember burner ports.  
Figure 49 - Ember Placement  
Figure 46 - Install Left Front Log (D)  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step9.INSTALLATIONANDREMOVALOF  
GLASS DOOR  
These are direct-vent appliances. They are  
designed to operate only when the front glass  
enclosure panel is installed. Generally the front  
glass enclosure panel should not be removed  
except to gain access to the components within  
the firebox.  
WARNING  
Donotattempttosubstitutethe  
materialsusedonthesedoors,  
or replace cracked or broken  
glass.  
During this appliance checkout and adjust-  
ment period, a potential safety hazard exists  
- EXERCISE EXTREME CAUTION to prevent  
the occurrence of any burn injuries from the  
exposed flames or hot surfaces. Also note,  
that while the front glass enclosure panel is  
removed, the flame appearance will appear to  
be smaller than normal.  
Pull Latches  
Forward  
• Handlethisglasswithextreme  
care! Glass is susceptible to  
damage – Do not scratch or  
handleroughlywhilereinstall-  
ing the glass door frame.  
• The glass door(s) of this appli-  
ance must only be replaced as  
a complete unit as provided  
by the manufacturer. Do not  
attempt to replace broken,  
crackedorchippedglasssepa-  
rately.  
Removing Glass Enclosure Panel  
(see Figures 50 and 51)  
1. Remove the facade assembly by lifting it  
up and toward you (see the installation  
instruction sheet provided with the facade  
for additional information).  
2. Locate the two (2) latches at the top of the  
control compartment (see Figure 50). To  
disengage the two latches, pull the spring-  
loaded latches forward then down as shown  
in Figure 50.  
Spring-Loaded Latches  
Pull forward then down to release  
Do not attempt to touch the  
frontenclosureglasswithyour  
hands while the fireplace is in  
use.  
Figure 50 - Glass Door Latches  
3. Swingthebottomofthedoorout(seeFigure  
51)andraiseitslightlytoliftthetopangeof  
the door frame away from the appliance.  
Installing Glass Enclosure Panels  
(see Figures 50 and 51)  
WARNING  
Door  
Assembly  
Do not operate appliance with  
theglassfrontremoved,cracked  
or broken.  
Note:Thisapplianceisnotapprovedforopera-  
tion without a log set (provided) or a firebox  
liner kit installed (sold separately).  
1. Visually inspect the gasket on the backside  
of the glass panel. The gasket surface must  
be clean, free of irregularities and seated  
firmly.  
AVERTISSEMENT  
Ne pas utiliser l'appareil si le  
panneau frontal en verre n'est  
pas en place, est craqué ou  
brisé.  
IMPORTANT NOTE: Be very careful not to  
damage the refractory firebox liner when  
installing the door. Take care when seat-  
ing the top door gasket so that it is not  
obstructed by the refractory panel. If the  
doorfeelsrestrictedwhenlatching,thetop  
door gasket may not be properly seated.  
2. Position the glass enclosure panel in front  
of the firebox opening at a 45 degree angle  
and engage the top flange over the lip at the  
top of the firebox opening (read important  
note above) (see Figure 51).  
Only doors certified with the appliance  
shall be used.  
Seules des portes certifiées pour cet  
appareil doivent être utilisées.  
Note: When installing the glass door, ensure  
the spacing on both sides are equal.  
CAUTION: DO NOT abuse glass door by  
striking or slamming shut.  
Figure 51 - Glass Door Removal  
3. Swing the glass enclosure panel down and  
back. Ensure the gasket seats evenly as  
the panel draws shut. Close the latches to  
secure the panel.  
A required firebox liner kit must be installed  
prior to installing the glass door. Install the  
liner per instructions provided in kit.  
4. Reinstall the facade assembly.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The adjustment rod and associated adjustable  
air shutter is patented technology. Flame ad-  
justments can be made quickly and accurately  
to taste without the need of disassembling the  
appliance and waiting for 30 minutes after each  
adjustment.  
Step 10. BURNER ADJUSTMENTS  
Flame Appearance and sooting  
Burner Air Shutter Adjustment Procedure  
WARNINGS  
Proper flame appearance is a flame which is  
blueatthebaseandbecomesyellowish-orange  
in the body of the flame. When the appliance  
is first lit, the entire flame may be blue and will  
graduallyturnyellowish-orangeduringtherst  
15 minutes of operation. After 15 minutes of  
operation, if the flame is blue, or if the flame is  
orange with evidence of sooting (black tip), the  
air shutter opening may need to be adjusted.  
Air shutter adjustment should  
only be performed by a quali-  
fiedprofessionalservicetech-  
nician.  
Ensure front glass panel are  
in place and sealed during  
adjustment.  
When satisfied that the appliance operates  
properly, proceed to finish the installation.  
Leave the control knob in the ON position and  
the burner ON/OFF switch (or optional remote  
switch) in the OFF position. Close the lower  
control compartment panel.  
If the air shutter opening is closed too far,  
sooting may develop. Sooting is indicated  
by black puffs developing at the tips of very  
long orange flames. Sooting results in black  
deposits forming on the logs, appliance inside  
surfaces and on exterior surfaces adjacent to  
the vent termination.  
Note: See Figure 53 for proper burner flame  
appearance.  
CAUTIONS  
Soot will be produced if the  
airshutterisclosedtoomuch.  
Any damage due to carboning  
resulting from improperly  
setting the air shutter is not  
covered under the warranty.  
Theairshutterdoorandnearby  
appliance surfaces are hot.  
Exercise caution to avoid  
injury while adjusting flame  
appearance.  
Front of Burner  
Sootingiscausedbyincompletecombustionin  
the flames and lack of combustion air entering  
the air shutter opening. To achieve a warm yel-  
lowish-orange flame with an orange body that  
does not soot, the shutter opening must be  
adjusted between these two extremes.  
Air Shutter  
Adjustment  
Rod  
Reach around the  
left side of the  
valve to locate  
adjustment rod  
Air Shutter Adjustment Guidelines  
• If there is smoke or soot present, first check  
the log set positioning to ensure that the  
flames are not impinging on any of the logs.  
If the log set is properly positioned and a  
sooting condition still exists, then the air  
shutter opening should be increased.  
To adjust the flame, move the lever arm up or  
down(locatedinthelowercontrolareaasshown  
in Figure 52). When the arm is positioned all  
the way down it is fully open. When the arm is  
positioned all the way up, it is closed.  
• Themoreoffsetsintheventsystem,thelarger  
the air shutter opening will need to be.  
Ensure that the air shutter is closed (push lever  
all the way up).  
• An appliance operated with the air shutter  
opened too far, may have flames that appear  
blue and transparent. These weak, blue and  
transparent flames are termed anemic.  
• Propane models may exhibit flames which  
candle or appear stringy. If this is present  
and persists, adjust the air shutter to a more  
closed position, then operate the appliance  
for a few more minutes to ensure that the  
flame normalizes and the flames do not  
appear sooty.  
CAUTION: DO NOT BEND THE AIR SHUTTER  
ROD. MAKE SURE THE AIR SHUTTER MOVES  
WHEN THE LEVER ARM IS OPERATED.  
Valve  
Observe the flame continuously. If it appears  
weak or sooty as previously described, adjust  
the air shutter up or down until the flame ap-  
pearance is as desired.  
Adjustment  
All the way up = CLOSED  
All the way down = OPEN  
Adjust the rod to the full closed position for  
both Natural Gas and Propane. Light the fire-  
place, then adjust accordingly after heat-up.  
The following chart is provided to aid you in  
achieving the correct air shutter adjustment  
for your installation.  
Figure 52 - Burner Air Shutter  
Air Shutter Adjustment Guidelines:  
Amount of  
Primary Air  
Flame  
Color  
Air Shutter  
Adjustment  
If air shutter is  
closed too far  
Flame will Air shutter  
be orange gap should be  
increased  
If air shutter is  
open too far  
Flame will Air shutter  
be blue gap should be  
decreased  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FINISHING REQUIREMENTS - Wall Details  
Complete finished interior wall. To install the appliance facing flush with  
the finished wall, position framework to accommodate the thickness of  
the finished wall (Figure 54).  
This Area Must  
Remain Clear of  
Combustible Materials  
Header  
(2x4)  
4" Min  
(102 mm)*  
Drywall  
1" Min.  
(25 mm)*  
IMPORTANT NOTE:  
Place the header verti-  
cal as shown to main-  
tain proper clearance  
from the vent system to  
combustibles.  
Top of  
Appliance  
Figure 53 - Burner Flame Appearance  
* Vent to combustible  
on Side = 1" Min.  
Vent to combustible  
on Top = 3" Min.  
Spacers  
Fireplace (right side)  
u
4" clearance is required above the elbow for installations that require an  
elbow at the top of the unit and that ends in a horizontal termination.  
Figure 54  
Hearth Extension  
Ahearthextensionisnotrequiredwiththisappliance.Ifahearthextension  
is used, do not block the lower control compartment panel. Any hearth  
extension used is for appearance only and does not have to conform to  
standard hearth extension installation requirements.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 11. ATTACHING SAFETY IN OPERATION WARNINGS  
It is the installer's responsibility to ensure these warnings are properly affixed during installation. These warning labels are a  
critical step in informing consumers of safe operation of this appliance.  
ATTACHING SAFETY-IN-OPERATION  
WARNINGS  
APPOSITION DES MISES EN GARDE RELATIVES  
à LA SéCURITé D’UTILISATION  
COLOCACIóN DE ADVERTENCIAS DE  
SEGURIDAD EN OPERACIóN  
Yourreplacehasbeenfurnishedwithsafetyinstruc- Votrefoyeraétélivréavecdesétiquettesdesécuritéqui Su chimenea incluye etiquetas de instrucciones  
tion labels that are to be affixed to the operation and doivent être collées à côté des dispositifs de contrôle de seguridad que deben colocarse en el punto de  
control point of the fireplace. A safety instruction du foyer. Une étiquette de sécurité doit être collée sur operación y control de la chimenea. Se debe colocar  
labelshouldbeaffixedtothewallswitchplatewhere la plaque de l’interrupteur contrôlant l’allumage du una etiqueta de instrucciones de seguridad en la placa  
the fireplace is turned on and off (See Figure A) or foyer (voir Figure A) ou sur le thermostat mural (voir del interruptor de pared desde el cual se enciende y se  
wall thermostat (See Figure B) and if used on the Figure B) et, le cas échéant, sur le boîtier de la télé- apaga la chimenea (ver la Figura A) o en el termostato  
remote control handheld transmitter (Figure C). commande(FigureC). Lesmisesengardeauraientdû de pared (ver la Figura B)y en el transmisor de control  
The warnings should already have been put in place êtrecolléesaumomentdel’installationinitialedufoyer. remoto (Figura C)siseusa.Lasadvertenciasyadeben  
when the fireplace initial set-up was completed. Si ce n’est pas le cas, prenez les étiquettes adhésives haberse colocado cuando se completó la instalación  
If they are not affixed at these spots, locate the multilingues fournies avec ces instructions et procédez inicial de la chimenea. Si no están colocadas en estos  
multi-lingual adhesive labels provided with these comme suit:  
lugares,encuentrelasetiquetasadhesivasmultilingües  
instructions and proceed as follows:  
1. Repérez l’interrupteur ou le thermostat mural proporcionadas con estas instrucciones y prosiga de  
qui contrôle le foyer (vérifiez que l’interrupteur la siguiente manera:  
1. Locate the wall switch or wall thermostat that  
controlsthereplace(verifytheswitchoperates  
the fireplace by turning it on and off). Clean the  
wall switch plate or wall thermostat thoroughly  
to remove any dust and oils. Affix the label to  
the surface of the plate of the wall switch that  
controls the fireplace (Figure A) or the wall  
thermostat (Figure B). Choose the language  
primarily spoken in the home.  
contrôle le fonctionnement du foyer en le faisant 1. Identifique el interruptor o el termostato de pared  
basculerdeMarcheàArrêt,etvice-versa). Nettoyez  
soigneusement la plaque murale de l’interrupteur  
ou le thermostat mural pour éliminer la poussière  
et les traces de graisse ou d’huile. Collez l’étiquette  
sur la surface de la plaque de l’interrupteur mural  
qui contrôle le foyer (Figure A) ou du thermostat  
mural (Figure B). Choisissez la langue qui est  
principalement parlée dans la résidence du  
propriétaire.  
quecontrolalachimenea(verifiquequeelinterruptor  
opera la chimenea encendiéndola y apagándola).  
Limpiebienlaplacadelinterruptoroeltermostatode  
pared para quitar el polvo y aceite. Pegue la etiqueta  
enlasuperficiedelaplacadelinterruptorquecontrola  
la chimenea (Figura A) o en el termostato de pared  
(Figura B). Seleccione el idioma que más se habla  
en la casa.  
2. Ifaremotecontrolisusedtocontrolthereplace,  
locate the transmitter and clean it thoroughly  
2. Si se usa un control remoto para controlar la  
chimenea, encuentre el transmisor y límpielo bien  
para quitar el polvo y aceite. Pegue la etiqueta en la  
superficie del transmisor (Figura C). Seleccione el  
idioma que más se habla en la casa.  
to remove any dust and oils. Affix the label to 2. Si une télécommande est utilisée pour contrôler  
the surface of handheld transmitter (Figure C).  
Choose the language primarily spoken in the  
home.  
le foyer, nettoyez la soigneusement pour éliminer  
la poussière et les traces de graisse ou d’huile.  
Collez l’étiquette sur le boîtier de la télécommande  
3. If you are unable to locate the labels, please call  
LennoxHearthProductsoryournearestLennox  
(Figure C). Choisissez la langue qui est principale- 3. Si no puede encontrar las etiquetas, sírvase llamar  
ment parlée dans la résidence du propriétaire.  
a Lennox Hearth Products o al distribuidor de  
Lennox Hearth Products más cercano para recibir  
etiquetasdeinstruccionesdeseguridadadicionales  
gratuitas.  
Hearth Products dealer to receive additional 3. Si vous ne trouvez pas les étiquettes, veuillez  
safety instruction labels free of charge.  
appeler Lennox Hearth Products ou votre distribu-  
teur Lennox Hearth Products local pour recevoir  
gratuitement des étiquettes supplémentaires.  
Cat. No. H8024 Replacement Label Kit  
Juego de etiquetas de repuesto - Nº de cat. H8024  
LENNOX HEARTH PRODUCTS  
1-800-9-LENNOX  
Étiquettes de remplacement, n° cat. H8024  
LENNOX HEARTH PRODUCTS  
1-800-9-LENNOX  
LENNOX HEARTH PRODUCTS  
1-800-9-LENNOX  
Note: English is red text on clear label. French and  
Spanish are white text on black label.  
Nota: La etiqueta en inglés es transparente con texto  
rojo. Las etiquetas en francés y español son negras  
con texto blanco.  
Remarque : Le texte anglais est rouge sur un support  
transparent. Le texte français et espagnol est blanc  
sur un support noir.  
SAFETY LABEL  
DIAGRAMS  
DIAGRAMMES DES éTIQUETTES  
DIAGRAMAS DE ETIQUETAS  
DE SEGURIDAD  
DE SéCURITé  
Figure C  
Figure B  
Figure A  
31  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION ACCESSORIES  
Listed Secure Vent™ Components  
Listed Secure Flex™ Components  
Cat. No. Model Description  
Cat. No.  
Model  
Description  
H1968  
SV4.5HT-2  
Horizontal Square Ter-  
mination With Firestop /  
spacer (H2246) & Adaptor  
(74L61)  
These termination kits include firestop/spacer, gear clamps and flex adaptor  
H1969  
SF4.5HT-2  
Horizontal Square Termina-  
tion (without flex)  
77L87  
SFKIT12S  
Flex Square Term. (with  
12 inch [305mm]*  
compressed flex)  
H2152  
SV4.5CGV-1 Vertical Termination Cap  
77L88  
77L89  
77L90  
77L91  
SFKIT18S  
SFKIT24S  
SFKIT36S  
SFKIT48S  
SFVT30  
Flex Square Term. (with  
18 inch [457mm]*  
compressed flex)  
77L70  
77L71  
77L72  
77L73  
77L74  
SV4.5L6  
SV4.5L12  
SV4.5L24  
SV4.5L36  
SV4.5L48  
6 Inch (152 mm)  
12 Inch (305 mm)  
24 Inch (610 mm)  
36 Inch (914 mm)  
48 Inch (1219 mm)  
Vent Sections  
Flex Square Term. (with  
24 inch [610mm]*  
compressed flex)  
Flex Square Term. (with  
36 inch [914mm]*  
compressed flex)  
77L75  
77L76  
SV4.5LA  
TelescopicSection(1-1/2"to  
7-1/2" effective length)  
Flex Square Term. (with  
48 inch [1219 mm] *  
compressed flex)  
SV4.5E45  
45 Degree Elbow  
56L74  
Vertical Termination for  
flex (flat to 6/12) with flex  
adaptor, section of rigid  
vent, roof support collar  
assembly, roof flashing  
and storm collar.  
77L77  
SV4.5E90  
90 Degree Elbow  
The following flashings come packaged with a storm collar:  
77L78  
77L79  
SV4.5F  
Flat Roof Flashing  
56L75  
SFVT45  
VerticalTerminationforex  
(6/12 to 12/12) with flex  
adaptor, section of rigid  
vent, roof support collar  
assembly, roof flashing  
and storm collar.  
SV4.5FA  
1/12 to 7/12 Adjustable  
Flashing  
77L80  
77L81  
H2246  
H2247  
H2248  
SV4.5FB  
SV4.5SC6  
SV4.5HF  
SV4.5VF  
SF4.5HF  
7/12 to 12/12 Adjustable  
Flashing  
Storm Collar (6 per box)  
60L10  
98K03  
10K81  
89L40  
SF-18  
SF-12  
18 feet (5.49 m) * com-  
pressed flex  
Firestop/Spacer-Horizontal  
(3-1-1 spacing), 10 Pack  
12 feet (3.66 m) * com-  
pressed flex  
Firestop/Spacer-Vertical(1-  
1-1 spacing), 10 Pack  
SFMP  
Mill-Pac, Black, HighTem-  
perature Sealant  
S
e
a
l
a
n
t
Firestop/Spacer-Horizon-  
SFMP-12  
Mill-Pac, Black, HighTem-  
perature Sealant - Bulk  
12 pack  
tal (flex) (3-1-1 spacing)  
,
10 Pack  
H2249  
96K92  
17M52  
17M53  
SF4.5VF  
SV4.5SP  
Firestop/Spacer-Vertical  
(flex)(1-1-1 spacing), 10 Pk  
91L66  
91L67  
SF-GC4-6  
SF-GC7-6  
Gear Clamp 4.5 in. (114  
mm) for flex (6 pieces)  
Support Plate  
Gear Clamp 7.5 in. (190.5  
mm) for flex (6 pieces)  
SV4.5HGS-1 Termination Guard, Square  
(1 pack)  
99L02  
99L03  
H1988  
SV4.5HRK14 Horizontal Riser Kit, 14"  
SV4.5HRK36 Horizontal Riser Kit, 36"  
(Fits 94L10  
& H1968)  
SV4.5HGS-12 Termination Guard, Hori-  
zontal Square (12 pack)  
CTSA-33  
CTSO-33  
CTSO-44  
CTSO-46  
ChaseTopShroudKit,Arch  
Top 3 X 3 Ft.  
87L02  
H5820  
SV4.5HGS  
4.5HTSK  
Termination Guard for  
Horizontal Square Termi-  
nation (Deluxe) (1 pack)  
H1985  
H1987  
H1986  
Chase Top Shroud Kit,  
Open Top 3 X 3 Ft.  
(Fits 94L10  
& H1968)  
Chase Top Shroud Kit,  
Open Top 4 X 4 Ft.  
Chase Top Shroud Kit,  
Open Top 4 X 6 Ft.  
Termination Shroud  
(Guard) for Horizontal  
Square Termination (1  
pack)  
(Fits H1968)  
96K93  
H3907  
SV4.5SU  
Support Strap  
H5816  
SV4.5-TWSK Through Wall Shield Kit  
(used to shield the direct-  
vent pipe from blown  
SV4.5ARSA  
Attic Insulation Shield w/  
adjustable height, 12"-22"  
750,247M  
insulation)  
Ref. instr. # 750,247M  
*All compressed flex vents can be expanded up to two times.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION INSTRUCTIONS  
GAS CONVERSION KITS  
Step 1. TURN OFF THE GAS SUPPLY TO THE  
APPLIANCEanddisconnectpowersupply atthe  
circuit breaker. Ensure appliance is cold.  
WARNING  
Thisconversionkitshallbeinstalledbyaqualifiedserviceagencyinaccor-  
dance with the manufacturer’s instructions and all applicable codes and  
requirementsoftheauthorityhavingjurisdiction.Iftheinformationinthese  
instructionisnotfollowedexactly,are,explosionorproductionofcarbon  
monoxide may result causing property damage, personal injury or loss of  
life.Thequalifiedserviceagencyisresponsiblefortheproperinstallation  
of this kit. The installation is not proper and complete until the operation  
of the converted appliance is checked as specified in the manufacturer’s  
instructionssuppliedwiththekit. Thequalifiedserviceagencyperforming  
this installation assumes responsibility for this conversion.  
CAUTION: THE GAS SUPPLY SHALL BE  
SHUT OFF PRIOR TO DISCONNECTING THE  
ELECTRICAL POWER, BEFORE PROCEED-  
ING WITH THE CONVERSION.  
ATTENTION. AVANT D’EFFECTUER  
LA CONVERSION, COUPEZ D’ABORD  
LALIMENTATION EN GAZ, ENSUITE,  
COUPEZ LALIMENTATION éLECTRIQUE.  
Step 2. Remove the front glass door/frame.  
See Figure 51.  
Step 3. Carefully remove the logs. Exercise  
care so as not to break the logs.  
AVERTISSEMENT  
Cette trousse de conversion doit être installée par un technicien agréé,  
selon les instructions du fabricant et selon toutes les exigences et tous les  
codes pertinents de l’autorité compétente. Assurez-vous de bien suivre  
les instructions dans cette notice pour réduire au minimum le risque  
d’incendie,d’explosionoulaproductiondemonoxydedecarbonepouvant  
causer des dommages matériels, des blessures ou la mort. Le tecnicien  
agrééestresponsabledel’installationdecettetrousse.Linstallationn’est  
pas adéquate ni complète tant que le bon fonctionnement de l’appareil  
convertinapasétévérifiéselonlesinstructionsdufabricantfourniesavec  
la trousse. Le fournisseur de service qualifié ayant réalisé l'installation  
assume les responsabilités liées à la conversion.  
Step 4. Refer to Figure 55.  
Remove the burner assembly with attached  
venturi tube.  
Burner Assembly  
In Canada:  
THE CONVERSION SHALL BE CAR-  
Burner Orifice  
Millivolt SIT Systems  
Natural Gas To Propane Gas  
RIED OUT IN ACCORDANCE WITH THE  
REQUIREMENTS OF THE PROVINCIAL  
AUTHORITIES HAVING JURISDICTION  
AND IN ACCORDANCE WITH THE RE-  
QUIREMENTS OF THE CAN/CSA-B149.1  
INSTALLATION CODE.  
Conversion Kits  
Models  
Cat. No.  
H5778  
ACKMV-NGLP  
Millivolt SIT Systems  
Propane to Natural Gas  
Conversion Kits  
Gas Valve  
LA CONVERSION DEVRA êTRE EF-  
FECTUéE CONFORMéMENT AUX RE-  
COMMANDATIONS DES AUTORITéS  
PROVINCIALES AYANT JURIDICTION  
ET CONFORMéMENT AUX EXIGENCES  
DU CODE D'INSTALLATION CAN/CSA-  
B149.1.  
Gas Train Assembly  
Models  
Cat. No.  
H5779  
ACKMV-LPNG  
Figure 55  
Electronic SIT Systems  
Natural Gas To Propane Gas  
Conversion Kits  
Millivolt Appliances  
Step 5. SIT Systems - Refer to Figure 56 on  
Page 34 and the instructions provided with the  
kit. UsingaTorxT20(with1/4shankandcenter  
hole), remove and discard the three pressure  
regulator mounting screws. Remove the pres-  
sure regulator, spring, poppet, diaphragm and  
bushing. Discard all removed components.  
Models  
Cat. No.  
H5780  
Gasconversionkitsareavailabletoadaptyour  
appliance from the use of one type of gas to  
the use of another. These kits contain all the  
necessarycomponentsneededtocompletethe  
task including labeling that must be affixed  
to ensure safe operation.  
ACKE-NGLP  
Ensuretherubbergasketinstalledonthebackof  
the replacement pressure regulator is properly  
positioned and install the new pressure regula-  
tor using the new screws supplied with the kit.  
Tighten screws to 25 In. lb. torque.  
Kitpartnumbersarelistedhere andthefollow-  
ing steps detail the conversion procedure.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Burner Orifice Sizes  
Elevation 0-4500 feet ( 0-1372 meters)  
SIT Millivolt Gas  
Valve Shown  
SIT Millivolt Pilot Assembly Shown  
Model  
Nat.Gas  
Propane  
Series  
drill size (inches) drill size (inches)  
Pressure  
Regulator  
.067"  
-------------  
(#51)  
ADAGIO-MN  
ADAGIO-MP  
ADAGIO-EN  
Thermopile  
(on millivolt  
pilot assem-  
.042"  
-------------  
(#58)  
blies only)  
.067"  
Pilot  
Orifice  
-------------  
(#51)  
Remove  
These  
Components  
ADAGIO-EP  
.042"  
-------------  
(#58)  
if field converted  
Table 9  
SIT Electronic Pilot  
SIT Electronic Gas Valve  
L O  
H I  
Pilot  
Orifice  
Pressure  
Regulator  
Millivolt & Electronic Pilot Assemblies  
Millivolt & Electronic Gas Valves  
Figure 56  
Figure 57  
Figure 58 - Burner Orifice  
Step 10. Turn on gas supply and test for gas  
leaks. See Test All Connections For Gas Leaks  
on Page 25.  
B. Retrieve the burner and slide the venturi  
tube over the orifice (see Figure 55). Set  
the burner assembly into its position and  
secure it.  
Step 6. Refer to Figure 57 and remove the  
pilot hood assembly to access the hexed pilot  
orifice. Remove and replace the orifice with  
the one provided with the kit.  
Step 11. Attach manometer to the manifold  
side pressure test fitting and verify manifold  
pressure reads 3.5 inches water column (0.87  
kPa) for natural gas, and 10.0 inches water  
column (2.49 kPa) for propane gas.  
Step8.Reassembletheremainingcomponents  
by reversing the procedures outlined in the  
preceding steps.  
Step 7. (Refer to Figure 55 on Page 33 and  
Figure 58)  
VERIFY THE PROPER ORIFICE SIZE BE-  
FORE INSTALLING IT.  
Step 9. Attach the conversion label provided  
in the conversion kit to the rating plate on the  
appliance.  
ALWAYS TEST PRESSURES WITH THE VALVE  
REGULATOR CONTROL AT THE HIGHEST  
SETTING.  
A. Remove the orifice from the manifold and  
replace it with the one provided in the kit.  
See Table 9 for orifice sizes for natural and  
propane models. Figure 58 illustrates the  
orifice. Use pipe joint compound or Teflon  
tape on all pipe fittings before installing  
(ensure propane resistant compounds are  
used in propane applications, do not use  
pipe joint compounds on flare fittings).  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design,  
materials, specifications, prices and also to discontinue colors, styles and products.  
Consult your local distributor for fireplace code information.  
Printed in U.S.A. © 2007 Lennox Hearth Products  
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210  
P/N 850044M REV. F 01/2011  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Lanzar Car Audio Car Stereo System SX7 User Manual
Lenox Blower blower coil units User Manual
Lindy Computer Hardware 32825 User Manual
Lowrance electronic GPS Receiver X96 User Manual
Master Bilt Refrigerator QMVM 36L User Manual
McCulloch Lawn Mower MC175H42ST User Manual
McCulloch Trimmer 115249726 User Manual
Memorex MP3 Player MSP BX1600 User Manual
Middleby Marshall Oven PS314SBI User Manual
Midland Radio Weather Radio HH54 User Manual