INSTALLATION INSTRUCTIONS
MANUAL
DIRECT-VENT GAS FIREPLACE HEATER INSERTS
Elite™ Series, Models: EDVI25, EDVI30 & EDVI35
Suitable for installation into masonry or factory built fireplaces.
RETAIN THIS MANUAL FOR FUTURE REFERENCE
P/N 775,156M Rev. G, 3/2005
Report No. 116-F-14-5
These appliances may be installed in an aftermarket permanently located,
manufactured (mobile) home, where not prohibited by local codes.
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE
LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE
POURRÉDUIREAUMINIMUMLERISQUED’INCENDIE
OU POUR ÉVITER TOUT DOMMAGE MATÉRIEL,
TOUTE BLESSURE OU LA MORT.
WARNING:IFTHEINFORMATIONINTHISMANUAL
IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO-
SIONMAYRESULTCAUSINGPROPERTYDAMAGE,
PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY: Do not store or use gasoline
or other flammable
s or liquids in the vicinity of this or any other
appliance.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser
d’essencenid’autrevapeursouliquidesinflammablesdans
le voisinage de cet appareil ou de tout autre appareil.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une
odeur de gaz:
FOR YOUR SAFETY: What to do if you smell gas:
• DO NOT light any appliance.
• Ne pas tenter d’allumer d’appareil.
• DO NOT touch any electrical switches.
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow your gas suppliers
instructions.
• Ne touchez à aucun interrupteur. Ne pas vous servir
des téléphones se trouvant dans le batiment où vous
vous trouvez.
• Evacuez la piéce, le bâtiment ou la zone.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service dos incendies.
• If your gas supplier cannot be reached, call
the fire department.
Installation and service must be performed by a
qualified installer, service agency or the gas sup-
plier.
L’installation et service doit être exécuté par un qualifié
installeur, agence de service ou le fournisseur de gaz.
Download from Www.Somanuals.com. All Manuals Search And Download.
The millivolt appliances are manually con-
trolled and feature a spark igniter (piezo)
that allows the appliance's pilot gas to be
lit without the use of matches or batteries.
Thissystemprovidescontinuedserviceinthe
event of a power outage. However, the heat
circulation blower requires 120 volt power
(the appliance can be safely used with the
blower turned off). The blower operation is
controlledbyavariablespeedrheostatlocated
on the left side surround panel (if optional
surroundisinstalled)andtemperatureswitch
located underneath of firebox bottom on the
front left side.
CARBON MONOXIDE POISONING: EARLY
SIGNSOFCARBONMONOXIDEPOISONING
ARE SIMILAR TO THE FLU WITH HEAD-
ACHES, DIZZINESS AND/OR NAUSEA. IF
YOU HAVE THESE SIGNS, OBTAIN FRESH
AIR IMMEDIATELY. TURN OFF THE GAS
SUPPLY TO THE APPLIANCE AND HAVE
IT SERVICED BY A QUALIFIED PROFES-
SIONAL, AS IT MAY NOT BE OPERATING
CORRECTLY.
Manifold Gas Supply Pressure (all models)
Fuel
Low
High
(LO) 1.6” WC
(.40 kPa)
(HI) 3.5” WC
(.87 kPa)
Natural Gas
(LO) 6.3” WC
(1.57 kPa)
(HI) 10” WC
(2.49 kPa)
Propane
Table 3
Test gauge connections are provided on the
frontofthemillivoltgascontrolvalve(identi-
fied IN for the inlet and OUT for the manifold
side). See Figure 36a & 36b on page 14.
WARNING: DO NOT PLACE CLOTHING OR
OTHER FLAMMABLE MATERIALS ON OR
NEAR THESE APPLIANCES.
Table 4 shows the units gas orifice size for the
elevations indicated.
GENERAL INFORMATION
Main Burner Orifice Size
WARNING: FAILURE TO COMPLY WITH THE
INSTALLATIONANDOPERATINGINSTRUCTIONS
PROVIDED IN THIS DOCUMENT WILL RESULT
IN AN IMPROPERLY INSTALLED AND OPERAT-
ING APPLIANCE, VOIDING ITS WARRANTY.
ANY CHANGE TO THESE APPLIANCES AND/OR
OPERATING CONTROLS IS DANGEROUS.
IMPROPER INSTALLATION OR USE OF THESE
APPLIANCES CAN CAUSE SERIOUS INJURY OR
DEATH FROM FIRE, BURNS, EXPLOSION OR
CARBON MONOXIDE POISONING.
Model #
Nat.
Gas
Pro-
Elevation
The appliance installation, repair and annual
inspectionshouldbeperformedbyaqualified
serviceperson. Itisimperativethatthecontrol
compartment,burnerandcirculatingairpas-
sage way of the appliance be kept clean.
pane
Feet (meters)
#41
#53
0-4500'
(0-1370 meters)
EDVI25
EDVI30
(.096") (.0595")
1/16"
#37
(.104") (.0625")
0-4500'
(0-1370 meters)
0-4500'
#33
#51
S'assurer que le brùleur et le compartiment
des commandes sont propres. Voir les
instructions d'installation et d'utilisation qui
accompagnent l'appareil.
EDVI35
(.113") (.067") (0-1370 meters)
Table 4
These appliances and their individual shut-off
valvesmustbedisconnectedfromthegassupply
piping system during any pressure testing of
that system at pressures greater than 1/2 psig
(3.5 kPa).
Provide adequate clearances and adequate
accessibilityclearanceforserviceandproper
operation (see table 5 on page 7).
WARNING:CHILDRENANDADULTSSHOULD
BE ALERTED TO THE HAZARDS OF HIGH
SURFACE TEMPERATURES. USE CAUTION
AROUND THE APPLIANCE TO AVOID BURNS
ORCLOTHINGIGNITION.YOUNGCHILDREN
SHOULD BE CAREFULLY SUPERVISED
WHEN THEY ARE IN THE SAME ROOM AS
THE APPLIANCE.
Table 1 shows the BTU input for each
model:
These appliances must be isolated from the
gas supply piping system (by closing their
individual manual shut-off valve) during any
pressure testing of the gas supply piping
system at test pressures equal to or less than
1/2 psig (3.5 kPa).
Millivolt Models with
Manually-Modulated Gas Valves
Natural Gas
Input rate
(BTU/HR)
17,000 to
25,000
Propane
Input rate
(BTU/HR)
19,000 to
25,000
AVERTISSEMENT: SURVEILLER LES
ENFANTS. GARDER LES VÊTEMENTS,
LES MEUBLES, L'ESSENCE OU AUTRES
LIQUIDES À VAPEUR INFLAMMABLES À
COTE DE L'APPAREIL.
Model #
These appliances may be installed in an after-
market permanently located, manufactured
home (USA only) or mobile home, where not
prohibited by local codes.
EDVI25
EDVI30
21,500 to
30,000
22,000 to
28,000
Cet appareil peut être installé dans un maison
préfabriquée (É.-U. seulement) ou mobile déjà
installée à demeure si les réglements locaux le
permettent.
25,500 to
35,000
DO NOT USE THESE APPLIANCES IF ANY
PART HAS BEEN UNDER WATER. IMMEDI-
ATELY CALL A QUALIFIED, PROFESSIONAL
SERVICE TECHNICIAN TO INSPECT THE
APPLIANCES AND TO REPLACE ANY PARTS
OF THE CONTROL SYSTEM AND ANY GAS
CONTROLS WHICH HAVE BEEN UNDER
WATER.
26,000 to
34,000
EDVI35
Table 1
THESE APPLIANCES MUST NOT BE CON-
NECTED TO A CHIMNEY OR FLUE SERV-
ING A SEPARATE SOLID FUEL BURNING
APPLIANCE.
Tables 2 and 3 show the units' gas pressure
requirements for all models:
NE PAS SE SERVIR DE CET APPAREIL S'IL A
ÉTÉ PLONGÉ DANS L'EAU, COMPLÈTEMENT
OU EN PARTIE. APPELER UN TECHNICIEN
QUALIFIÉ POUR INSPECTER L'APPAREIL ET
REMPLACERTOUTEPARTIEDUSYSTÈMEDE
CONTRÔLE ET TOUTE COMMANDE QUI ONT
ÉTÉ PLONGÉS DANS L'EAU.
Inlet Gas Supply Pressure (all models)
Fuel
Minimum
4.5” WC
(1.12 kPa)
11.0” WC
(2.73 kPa)
Maximum
10.5” WC
(2.61 kPa)
13.0” WC
(3.23 kPa)
WARNING: THESE APPLIANCES MUST BE
PROPERLY CONNECTED TO A VENTING
SYSTEM. OPERATION OF THESE GAS
APPLIANCES WHEN NOT CONNECTED TO
A PROPERLY INSTALLED AND MAINTAINED
VENTING SYSTEM CAN RESULT IN CARBON
MONOXIDE(CO)POISONINGANDPOSSIBLE
DEATH.
Natural Gas
Propane
Table 2
3
Download from Www.Somanuals.com. All Manuals Search And Download.
FIREPLACE REQUIREMENTS
QUESTIONS TO ASK LOCAL BUILDING
OFFICIAL
6. Maximum amount of gas pipe without a
pressure test - type of test required?
7. Are below grade penetrations of the gas
line allowed?
8. Is concealed gas piping allowed?
9. Specific requirements of concealed
fittings?
10. Is rigid pipe to appliance required?
11. Allowed piping materials?
12. Shut-off valve required within 4 feet
of the firebox?
13. May the shut-off valve be concealed?
14. Rooms where the installation is not
allowed?
IMPORTANT: When installing these appliances
into a factory built fireplace or heatform, the air
flow within and around the fireplace shall not
be altered by the installation of the insert (i.e.
DO NOT BLOCK louvers or cooling air inlet or
outlet ports, circulating air chambers in a steel
fireplace liner or metal heat circulator).
These appliances must be installed per
manufacturers’ instructions. Installations
mustconformtoappropriatelocalcodesand
applicable state and federal requirements.
Familiarity with these requirements before
installation is essential. Some important
considerationstodiscusswithlocalbuilding
officials include:
CAUTION:Thefactorybuiltfireboxmustaccept
the insert without modification other than
removing bolted or screwed together pieces
such as smoke shelf / deflectors, ash lips,
screenordoortracks,loggrates,refractoryand
damper assemblies. Any fireplace component,
which is removed, must be retained so they
can be reinstalled to restore the fireplace to
its original operating condition. The removal
of any part must not alter the integrity of the
outer shell of the pre-engineered fireplace
cabinet in any way.
1. Applicablecodes(i.e.UniformMechanical
Code, State or Regional Gas Codes, National
Fuel Gas Code).
2. Local amendments
3. Recognized testing lab: OMNI-Test Labo-
ratories Inc.; Beaverton, Oregon
In the absence of local codes, installation
should conform to National Fuel Gas Code,
ANSI Z223.1 / NFPA 54-Latest Edition in the
USA or National Fuel Gas Code, CAN/CGA-
B149-Latest Edition in Canada.
4. Is a permit required - cost?
5. Insomestatesormunicipalities,alicensed
gas fitter or plumber may be required to
install these appliances. Check with your
localbuildingofficialforrequirementsinyour
area (i.e. Is a license required for installation
of gas supply line)?
HIGH ALTITUDE
If any components are removed from (or
altered) from the existing fireplace, a Warning
Label (see below) must be affixed inside the
fireplace firebox, so that it shall be visible
upon removal of the fireplace insert. Note:
RTV high temperature silicone is an approved
adhesive.
Installations at Altitudes of 0 to 4500 feet:
These appliances have been tested and
approved for elevations of 0 to 4500 feet (0
to 1370 meters).
Installations at Altitudes above 4500 feet:
Forelevationsabove4500feet(1370meters),
install these appliances according to the
regulations of the local authorities having
jurisdictionand, intheUSA, thelatestedition
of the National Fuel Gas Code (ANSI Z223.1)
or, in Canada, the latest edition of the CAN-
B149.1 and CAN-B149.2 codes.
Fireplace Warning Label
(Provided in Accessory Package)
WARNING
THIS FIREPLACE HAS BEEN ALTERED TO
ACCOMMODATE A FIREPLACE INSERT AND
SHOULD BE INSPECTED BY A QUALIFIED
PERSON PRIOR TO RE-USE AS A
CONVENTIONAL FIREPLACE.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS: EDVI25
DIMENSIONS
EDVI25
SPECIFICATIONS
EDVI25
Inches (millimeters)
26 5/8" (676 mm)
20 1/2" (521 mm)
5” (127 mm)
Min. / Max. BTU hr
Input - NG
Min. / Max. BTU hr
Input - LP
17,000 to 25,000
19,000 to 25,000
A
B
C
SM.= 41 1/16” (1043 mm) & MED.= 44 1/8” (1121 mm)
SM.= 26 1/16” (662 mm) & MED.= 27 5/8” (702 mm)
19 1/2” (483 mm)
D
E
Co-linear DV Vent
Size
3” Dia. Liner
(exhaust & intake)
F
G
H
I
110 cfm
Room Blower CFM
1 15/16” (49 mm)
10 9/16” (268 mm)
1 1/4” (32 mm)
J
17 1/4” (438 mm)
15 15/16” (405 mm)
10 7/8” (276 mm)
24 7/8” (632 mm)
EFFICIENCIES
K
L **
M **
EDVI25
65 % (NG)
66 % (LP)
86 % (NG)
89 % (LP)
14" (356 mm)
9 5/8” (224 mm)
N
P
Steady State
Efficiency *
** The total glass viewing area equals approx. 270 1/2 Sq. In.
* The Steady State Efficiency numbers based on
maximum vent configuration.
Top View
A
B
C
N
Note: Due to Lennox’ ongoing commitment
to quality , all specifications, ratings
and dimensions are subject to change
without notice.
E
I
D
G
H
I
P
E
L
F
J
K
M
Figure 1
Front View
Side View
5
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS: EDVI30 & EDVI35
DIMENSIONS
EDVI30
SPECIFICATIONS
EDVI30
EDVI35
EDVI35
Inches (millimeters)
25 15/16" (659 mm)
22 1/4" (578 mm)
Inches (millimeters)
32 1/16” (814 mm)
24 3/16” (614 mm)
5" (127 mm)
Min. / Max. BTU/hr
Input - NG
Min. / Max. BTU/hr
Input - LP
21,500 to 30,000
25,500 to 35,000
A
B
C
D
22,000 to 28,000
26,000 to 34,000
5" (127 mm)
40 1/4” (1022 mm)Sm.
45 3/4” (1162 mm) Med.
49 1/4” (1251 mm) Lg.
27 1/2” (699 mm) Sm.
30 1/4” (768 mm) Med.
30” (762 mm) Lg.
20 7/8" (530 mm)
1 13/16” (46 mm)
9 15/16” (252 mm)
1 7/16” (37 mm)
Co-linear DV Vent
Size
3” Dia. Liner
(exhaust & intake)
3” Dia. Liner
(exhaust & intake)
48 1/16” (1221 mm) Med.
34 1/16”(865 mm) Med.
130 cfm
130 cfm
Room Blower CFM
E
F
G
H
I
26 11/16” (678 mm)
1 13/16” (46 mm)
9 7/8”(251 mm)
1 5/8” (41 mm)
EFFICIENCIES
EDVI30
EDVI35
66% (NG)
70% (LP)
69% (NG)
70% (LP)
(based on CSA P.4.1)
20 1/4” (514 mm)
J
24” (610 mm)
86% (NG)
88% (LP)
Steady State
Efficiency *
87% (NG)
89% (LP)
K
15 1/4” (387 mm)
11 3/16” (284 mm)
23 1/4” (591 mm)
13 7/16” (341 mm)
18 3/8” (467 mm)
15 5/8” (397 mm)
29 7/16” (748 mm)
16 7/8” (427 mm)
L**
M**
N
** The total glass viewing area equals approx.:
EDVI30 = 290 Sq. In. & EDVI35 = 460 Sq. In.
* The Steady State Efficiency numbers based on
maximum vent configuration.
Top View
A
B
C
N
Note: Due to Lennox’ ongoing commitment
to quality , all specifications, ratings
and dimensions are subject to change
without notice.
D
G
I
H
E
F
L
J
K
M
Front View
Side View
Figure 2
6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
MINIMUM CLEARANCES TO COMBUSTIBLES: EDVI25, EDVI30 & EDVI35
These appliances can be installed in most residential
fireplace configurations. If installed close to an adjacent
Inches (millimeters)
EDVI30
wall, ensure that the minimum clearances to combustible
surfaces are maintained. A local building inspector should
review your plans prior to installation.
Clearances to Combustibles
Min.
Max.
EDVI25
8" (203 mm)
64" (1626 mm)
EDVI35
A
Side Wall
8" (203 mm)
8" (203 mm)
Min.
Min.
B
Ceiling or Alcove Height
64" (1626 mm)
64" (1626 mm)
Refer to Figures 3, 4a, 4b and 5 for Clearances to Combus-
tibles. Minimum clearances include spacers/standoffs or
surfaces to combustible construction.
C* Mantel Height
D* Mantel Projection from Wall
See Fig. 3 & 4b See Fig. 3 & 4a
See Fig. 3 & 4a Min.
See Fig. 4b
0" (0 mm)
See Fig. 4a
0" (0 mm)
See Fig. 4a
0" (0 mm)
MAX.
Min.
E
Clearance to Floor
F** Hearth Protection
Notes for Table 5:
**16" (406 mm)
**16" (406 mm) **16" (406 mm)
Min.
(from Fireplace Face)
*
This includes any projections such as shelves, window
sills, mantels, spacers/standoffs or surfaces to com-
bustible construction etc. above the appliance. Paint or
lacquer used to finish the mantel must be heat resis-
tant in order to avoid discoloration.
G
H
I
Hearth Protection Width
Alcove Width
Alcove Depth
44" (1118 mm)
45" (1143 mm)
36" (914 mm)
49" (1245 mm) 48" (1219 mm)
50" (1270 mm) 49" (1245 mm)
Min.
Min.
MAX.
36" (914 mm)
36" (914 mm)
** If hearth is elevated, subtract 1 inch of hearth
extension required for every 2 inches of height (see
Figure 6).
Table 5
Clearances
Alcove Minimum Width: The specified minimum width of the
alcove cannot be reduced with the use of wall protection.
Ceiling (or)
Alcove Height
Mantel
Top View Alcove
Fireplace
C
Insert
Top of Insert
B
Hearth
Side
Wall
A
I
H
G
Hearth Protection
E
Figure 5
Figure 3
Mantel Clearance, Models: EDVI30 &
EDVI35: The mantel should be located
in the shaded area (light gray) shown
below.
Mantel Clearance, Model: EDVI25: The
mantel should be located in the shaded
area (light gray) shown below.
Hearth Protection: For every 2" of hearth height,
subtract 1" of hearth extension required.
Side View
of Insert
D
D
18"
15 1/2"
F
17"
16"
13"
Existing Fireplace Hearth
11"
C
15"
14"
16"
2"
C
8 1/2"
4"
15"
14"
6"
7"
0
0
12”
5”
1”
0
8”
13 1/2"
12 10
11
8
6
4
2
0
\
9
7
5
3
1
\
Top of Insert louver
(see "C" on Fig. 3)
Side View
Top of Insert
(see "C" on Fig. 3)
Side View
At 7" hearth height, no hearth extension is required
Figure 4a
Figure 4b
Figure 6
7
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 4 LIFT INSERT INTO POSITION (read
Fireplace Requirements on page 4 first) Lift
insert into position in front of the fireplace where
unit is to be installed. Discard bottom carton.
MINIMUM FIREPLACE DIMENSIONS
Refer to Figures 7 and 8 for Minimum Fire-
place Clearance Dimensions. See pages 5 &
6 for actual insert body dimensions.
CAUTION: If any portion of the chimney
system shows signs of structural or mechani-
cal weaknesses, such as: cracks, leaky
joints, corroded or warped surfaces, the
faulty portion must be repaired or replaced
prior to installing this appliance.
Consult your local authority having juris-
diction for requirements in your area.
Step5: REMOVESTANDARD GLASSDOOR
ASSEMBLY.
Before the fireplace insert is assembled and
installed, you must consider whether the
appliance must be converted for use with
propane gas (see step 7 on Page 9). You
must also consider the vent length require-
ments.
Step 2: PREPARATION - Plan and install gas
line. These appliances are provided with an
opening on the left hand side of the control
compartment.A3/8"NPTgassupplypipemust
be brought near this inlet hole.
WARNING: HANDLE GLASS DOOR WITH
EXTREME CARE! THE GLASS DOOR
ASSEMBLYISSUSCEPTIBLETODAMAGE.
DO NOT SCRATCH WHILE HANDLING OR
WHILE REINSTALLING.
Gas Supply Line - We recommend that a
qualified individual such as a plumber or gas
fitter be used to correctly size and route the
gas supply line to the appliance. Installing a
gas supply line from the fuel supply to the
applianceinvolvesnumerousconsiderationsof
materials,protection,sizing,locations,controls,
pressure,sediment,andmore.Certainlynoone
unfamiliarandunqualifiedshouldattemptsizing
or installing gas piping.
M
Remove Front Glass Enclosure as Follows:
1) Locate the spring hook under the glass
door assembly (see Figure 9). Pull hook
forward until it releases out of the bottom
door frame.
Top View
K
Figure 7
Pull door hook forward until it releases
L
The gas supply line should be plumbed from
thefuelsourcetotheareawheretheappliance
is to be installed per requirements outlined
in NFPA 54 - latest edition (USA) or B149
- latest edition (Canada).
9"
Min.
Reference
J
The proper gas line diameter must be used
to run from the supply regulator (at the gas
company meter) to the appliance. Never use
galvanized or plastic pipe. Refer to table 7
for suggested sizing of the gas supply line if
black iron pipe is being used.
Side View
Figure 8
Door hook is located below glass door
Figure 9
K
2) Swing the bottom of the door outward
(see Figure 10) and lift it off of firebox top.
Set door aside in a safe place.
The gas supply line should be connected to
the appliance at step 9 (page 11).
Inches (millimeters)
Min. Fireplace
Clearance
Dimensions
Suggested Sizing of Black Iron Pipe
Schedule 40 - Pipe Supply Line
EDVI25
EDVI35
EDVI30
25"
22"
19"
Schedule 40 Pipe
Schedule 40 Pipe
J
Height
Depth
(559 mm) (635 mm)
(483 mm)
Inside Diameter (Inches)
Length (Feet)
14 1/2"
(368 mm)
17"
(432 mm)
14"
(356 mm)
Natural Gas Propane Gas
K
L
0-10
1/2
1/2
1/2
3/4
3/4
3/8
1/2
1/2
1/2
1/2
27"
(686 mm)
32 1/4"
(673 mm) (819 mm)
26 1/2"
Width/Front
Width/Rear
10-40
Swing bottom of
Door outward
23 1/4"
22 1/2"
(591 mm) (572 mm)
25"
40-100
100-150
150-200
M
(635 mm)
Figure 10
Table 6
DETAILED INSTALLATION STEPS
Table 7
Lift Top of Door
Off this Flange
IMPORTANTNOTE:Ifpropaneisused,beaware
that if the tank size is too small (i.e. under
100-lbs, if this is the only gas appliance in the
dwelling. Ref. NPFA 58), there may be loss of
pressure, resulting in insufficient fuel delivery
(which can result in sooting or other malfunc-
tions). Any damage resulting from an improper
installation, such as this, is not covered under
the limited warranty.
Step 1: CLEAN FIREPLACE (If necessary)
Thoroughly clean the masonry or factory
built fireplace.
CAUTION: The fireplace in which this gas
insert is to be installed must be thoroughly
cleaned if it has been used to burn wood or
synthetic logs. Have the chimney and all
inside surfaces of the fireplace brushed and
vacuumed so that no soot, embers, or loose
combustion deposits can be drawn into the
heat circulation blower and blown into the
living area.
Figure 11
WARNING: NEVER OPERATE UNIT WITH-
OUT THE FRONT GLASS DOOR PANEL IN
PLACE AND SECURE.
Step 3 UNPACK THE INSERT - Remove
the top and side cartons. Remove all the
inner packages and packing materials and
discard.
8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
STEP6: REMOVEPACKAGEDMATERIALSFROMINSIDEFIREBOXAND
SET ASIDE (log set, bag of embers, bag of vermiculite, propane
conversion kit - if needed to run on LP gas).
Simpson Dura Vent Components
Part No.
980
Description
Termination Cap, Standard
Termination Cap, High Wnd
Chimney Liner Term. Kit
Liner, Flex, 3” Dia. /. 35 feet.
Step 7: INSTALL LP CONVERSION KIT (IF NECESSARY) - Install the
LP conversion kit per instructions provided with kit.
991
923GK
2280
Step 8: VENTING SYSTEM INSTALLATION (Refer to Vent Manu-
facturer Installation Instructions)
Table 9b
This appliance is designed to using 3” diameter UL1181 listed alumi-
num liner for the Air Intake and 3” diameter UL1777 listed gas vent
liner for the Exhaust (see Figures 14 & 15). See Table 8 for miniumum
distances from roof to termination cap inlet/outlet.
Flex Liner Installation:
Liner Connec-
tor Plate
Exhaust
Intake
Hose
Clamps
Vertical Termination Height Minimum
(Factory Built and Masonry Fireplaces)
The vent/air intake termination clearances above the high side of an
angled roof is as follows:
Screw
Guide
After liners are secured to collars, slide liner con-
nector plate forward and secure with screw.
Feet (meters)
8 (2.4)
Figure 12
7 (2.1)
Positive Flue Connection (acceptable methods for sealing chimney throat)
Masonry and Factory Built Fireplaces
6 (1.8)
Aqualifiedinstallershouldevaluatetheexistingfireplacetodeterminethe
bestmethodforachievingapositiveflueconnectionbetweentheventand
intake liners and the chimney. The most common method is to secure a
noncombustible seal-off plate (i.e. 22-gage sheet steel) in the fireplace
throat using masonry screws. Other acceptable methods include packing
noncombustible material (i.e. rockwool) around the liners. Whichever
“seal off” method is used must effectively seal the area to prevent room
air passage to the chimney of the fireplace.
5 (1.5)
4 (1.2)
3 (0.9)
2 (0.6)
1 (0.3)
0 (0.0)
The outside air inlet does not
require a full reline (if intake liner
is terminated in chimney and a
positiveflueconnectionisachieved
as specified).
Exhaust 3" (75mm)
UL 1777. A full length
liner is required from
the exhaust outlet on
appliance to center collar
of termination cap.
Table 8
Roof Pitch
WARNING: Do not substitute the heat-rated flex liner (UL1777)
for the Exhaust with any other type liner or a fire may result
causing property damage, personal injury or loss of life.
Existing Fireplace Flue
(chimney)
ꢀ
ꢁ
IMPORTANT NOTES:
• Adjust Leveling Bolts if Necessary: Two leg leveling bolts are installed
into existing holes in the bottom rear of appliance. Turn the leveling bolts
to adjust for correct height.
Positive Flue Connec-
tion (sealing fireplace
throatusinganoncom-
bustible seal-off plate
or insulation).
Air Inlet Liner
(for combus-
tion air) When
terminatingthe
air inlet liner
at this point,
a positive flue
connection is
required (to
ensure com-
bustion air is
drawn down
the chimney
only).
• Refer to Vent Manufacturer Installation Instructions.
Direct Vent System Components
TM
The following "Security Secure Vent " or "Simpson Dura-Vent" brand
Collinear Direct-Vent components may be safely used with these appli-
ances (see Figures 14 & 15).
Masonry and Factory
Built Fireplaces
Lennox Hearth Products – Collinear Direct-Vent Kits
Cat. No.
H0908
Model
TKDVI
FKDVI
Description
Termination Kit, DVI
H0909
Flex Kit, DVI 3" X 35'
Figure 13
Table 9a
9
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
Factory Built Fireplace Installation Diagram
Masonry Fireplace Installation Diagram
Vertical Term-
The standard cap in Termination Kit, H0908, is a
high wind cap
Masonry chimneys may take
ination Cap
and Flashing.
Cat. No.
various contours which the
flexible liners will accomodate.
However, keep the flexible liner
as STRAIGHT as possible, avoid
unnecessary bending.
Vertical Termination Cap
and Flashing, Cat. No. H0908
H0908
Liner Requirements:
Vertical Height Min. = 8 ft. (2.44 M)
Vertical height Max. = 40 ft. (12.2 M)
See Direct Vent System Components
on Page 9.
Exhaust
Air
Intake
Hook up Air
& Exhaust
as Shown
Here
The standard cap
in Termination
Kit, H0908, is a
high wind cap
Liner Requirements:
Vertical Height Min. = 8 ft. (2.44 M)
Vertical Termination
Adapter
Vertical height Max. = 40 ft. (12.2 M)
See Direct Vent System Components
on Page 9.
Clay
Chimney
Liner
Exhaust
Air
Intake
Storm Collar
The flexible vent pipe must
NOT be allowed to sag behind
insert or in fireplace flue.
Hook up Air &
Exhaust as
Shown Here
Roof
Flashing
The flexible vent pipe must
NOT be allowed to sag behind
insert or in fireplace flue.
Read fireplace
requirements,
page 4
Use 3" diameter listed liner
(UL1181 or UL1777) for the AIR
INTAKE.
Use 3" diameter listed gas vent liner
(UL1777 ONLY) for the EXHAUST
Read Fireplace
Requirements on
page 4
Use 3" diameter listed
liner (UL1181 or UL1777)
for the AIR INTAKE.
Damper plate is
removed or fastened
in open position
Use 3" diameter listed
liner (UL1777 ONLY) for
the EXHAUST
Exhaust and air
Intake collars
Exhaust and Air
Intake Collars
Gear Clamps
Gear Clamps
Liner
Liner
• The Flex Kit, Cat. No. H0909 includes one 35' flex liner and four gear clamps.
• The Termination Kit, Cat. No. H0908 includes the termination cap with two
collinear collars for 3” flex attachments and flashing.
• The Flex Kit, Cat. No. H0909 includes one 35' flex liner and four gear clamps.
• The Termination Kit, Cat. No. H0908 includes the termination cap with two collinear
collars for 3” flex attachments and flashing.
Make sure that both liners will pass through existing damper area. Remove or lock
damper to allow the passage of the flexible liners. If the damper will not allow the
passage of both liners, DO NOT PROCEED FURTHER. Consult a local mason for
removal of the damper without risk of structural damage or leakage.
Before running the flexible liners, make sure that both liners will pass through
existing damper area. Remove or lock damper to allow the passage of the flexible
liners. If the damper will not allow the passage of both liners, DO NOT PROCEED
FURTHER (the appliance may NOT be installed into the fireplace).
Figure 14
Figure 15
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Flex Liner Installation (see Figure 14 for
Masonry Fireplace Installations and Figure
15 for Factory Built Fireplaces):
Step 10. PURGING AIR
AIR PURGING PROCEDURES MUST BE
PERFORMED BY A QUALIFIED TECHNICIAN
ONLY.
Note: Refer to Vent Manufacturer Instal-
lation Instructions.
Purging Air from Supply Line
Screw
a. Turn gas supply line valve off.
b. Loosen setscrew at inlet pressure tap on
control valve (see Figure 36).
c. Turn gas supply line valve on.
d. When gas flows, turn supply valve off.
e. Close the inlet pressure tap.
1) Cut the flex liners as required (mark both
ends of one of the flexible liners as INLET).
Liner
Connector
Plate
2) Connect the liner marked INLET to the inlet
side of the termination adaptor. Connect the
other liner to the exhaust side. Secure liner
to INLET collar with hose clamp.
Purging Air from Appliance
Figure 17
Purge air from appliance by holding gas
control valve down in the pilot position
until pilot will light (see Figure 19). DO NOT
LIGHT A MATCH IF YOU SMELL GAS. Light
a match then allow gas flow to pilot. If the
Match “blows”, there is air in the line (purge
line). If the flame is straight and tall, there is
no gas pressure.
3) Install flashing.
Notes:
4) Insert both liners into chimney, passing
through the damper opening.
• Final gas connection should be made after
unit is in place to avoid damage to line when
pushing the unit into position.
5) Install termination cap.
• Mill-pac, high temperature silicone and/or
screws may also be used to secure the liners
to the collars (gear clamps must also be
used).
6) Remove the liner connector plate from the
insert top (by removing the screw shown in
Figure 17, then sliding plate backward until it
clearstheretainingbreackets). Linersshouldbe
streched just enough to prevent the possibility
of sagging or coiling in the flue. Cut off excess
liner (see collar locations on pages 5 & 6).
When first lighting the appliance, it will take
a few minutes for the line to purge air from
theappliance.Oncepurgingiscomplete,the
pilot and burner will light and operate as indi-
cated in the instruction manual. Subsequent
lightings of the appliance will not require such
purging. Inspect the pilot flame (remove logs,
if necessary, handling carefully).
Step 9. CONNECTING GAS LINE
Make gas line connections. All codes require a
shut-offvalvemountedinthesupplyline.Figure
18 illustrates two methods for connecting the
gas supply. The flex-line method is acceptable
in the U.S., however, Canadian requirements
vary depending on locality. Installation must
be in compliance with local codes.
7) Connect the liner marked INLET to the inlet
collar on the liner connector plate (marked
with an "I"). Connect the remaining liner to
the exhaust collar (marked with an "E") on
the liner connector plate. Note: Both con-
nections should be secured to collars using
gear clamps.
These appliances are equipped with a gas
flex line for use (where permitted) in con-
necting the unit to the gas line. A gas flex
line is provided to aid in attaching the appli-
ance to the gas supply. The gas flex line
can only be used where local codes permit.
See Figure 18 for flex line description. The
flex line is rated for both natural and pro-
pane gas. A manual shut off valve is also
provided with the flex line. The gas control
valveislocatedinthelowercontrolcompart-
ment. The millivolt control valve has a 3/8"
(10 mm) NPT thread inlet port fitting.
8) Slide the liner connector plate all the way
forward and secure into place with a screw
(provided) as shown in Figure 16 & 17.
Figure 19
Combustion
Air (inlet)
Exhaust (outlet)
Step 11. INSTALLING LOGS, VERMICU-
LITE AND EMBERS
Damper
Thepackagedlogset,vermiculiteandembers
are located within the firebox of the insert.
Note: The EDVI25/EDVI30 log set is shown
in figures 20-28 and the EDVI35 log set is
shown in figures 29-34.
Gear Clamp
Gas
Gas Flex Line Connector
Valve
³ꢀ₈" NPT x
¹ꢀ₂" x³ꢀ₈" Flare
Flare Fitting
Shut-Off Valve
Liner
Connector
Plate
Installation Instructions:
³ꢀ₈" Flex Tubing
ꢃꢀ -INꢄ
Gas
WARNING: If logs are not installed accord-
ing to the directions shown here, flame
impingement and improper combustion
couldoccurandresultinsootand/orexces-
sive production of carbon monoxide (CO),
a colorless, odorless, toxic gas.
Stub
3EDIMENT 4RAP
ꢂRECOMMENDED
¹ꢀ₂
Reducer
x
³ꢀ₈"
³ꢀ₈ꢀ .IPPLE
³ꢀ₈"5NION
³ꢀ₈ꢀ #LOSE .IPPLE
³ꢀ₈ꢀ 3HUTꢁ/FF 6ALVE
Figure 18 - GAS CONNECTION
Figure 16
Note: If an optional Brick Liner Kit was
purchased, intall it now, per instructions
provided in kit.
11
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
LOGS, VERMICULITE AND EMBERS - Models EDVI25 & EDVI30 (For
3. Place the Center Log onto the 2 corresponding locating pins as
shown in Figure 22.
EDVI35 Log Installation Instructions, see Page 13).
The packaged log set, vermiculite and embers are located within the
firebox of the insert.
Installation Instructions:
WARNING: IF LOGS ARE NOT INSTALLED ACCORDING TO THE
DIRECTIONSSHOWNHERE,FLAMEIMPINGEMENTANDIMPROPER
COMBUSTIONCOULDOCCURANDRESULTINSOOTAND/OREXCES-
SIVE PRODUCTION OF CARBON MONOXIDE (CO), A COLORLESS,
ODORLESS, TOXIC GAS.
Notes:
• If an optional Brick Liner Kit was purchased, intall it now, per instruc-
tions provided in kit.
• Place some vermiculite around the burner as shown in Figure 28
before installing the logs (the entire bag of vermiculite will NOT be
used).
Center Log
Figure 22
4. Place the Front Left Log onto the 2 corresponding locating pins as
shown in Figure 23.
Carefully install the seven-piece log set into the firebox as shown in
these instructions. All logs should fit onto corresponding pins and/or
log stoppers. This will ensure a proper flame and safe combustion.
1. Place the largest log onto the 2 corresponding locating pins at the
back of the firebox as shown in Figure 20.
Front Left Log
Figure 23
5. Install the Top Left Log onto the corresponding locating pin and
indentation on Center Log as shown in Figure 24.
Rear Log
Figure 20
2. Place the Front Right Log onto the 2 corresponding locating pins
as shown in Figure 21.
Figure 24
Top Left Log
6. Install the Front Center Log over the Front Right Log . The front
of log will rest on the burner and the back of log will rest on rear log
as shown in Figure 25.
Front Right Log
Figure 21
12
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 25
Front Center Log
7. Install the Top Right Log into the corresponding indentations on
Front Center Log and front right twig as shown in Figure 26.
Embers
Figure 27
Figure 28
Vermiculite
Top Right Log
Figure 26
LOGS, VERMICULITE AND EMBERS - Model EDVI35
8. Place the glowing embers on the burner as shown in Figure 27.
WARNING: IF LOGS ARE NOT INSTALLED ACCORDING TO THE
DIRECTIONSSHOWNHERE,FLAMEIMPINGEMENTANDIMPROPER
COMBUSTIONCOULDOCCURANDRESULTINSOOTAND/OREXCES-
SIVE PRODUCTION OF CARBON MONOXIDE (CO), A COLORLESS,
ODORLESS, TOXIC GAS.
One package of ember material has been included with this log set
You will not need to use the entire bag.
IMPORTANT: The quantity and placement of the ember material can
affect insert performance therefore it is very important that it be placed
as shown in Figure 27.
Carefully install the seven-piece log set into the firebox as shown in
these instructions. All logs should fit onto corresponding pins and/or
log stoppers. This will ensure a proper flame and safe combustion.
a. Unpackage and divide the fine ember material (mineral wool) into
dime-sized fluffy pieces.
b. Distribute the pieces over the top of the front burner ports, filling the
area in front of the forward logs.
1. Place some vermiculite around the burner as shown in Figure 29
(the entire bag of vermiculite will NOT be used).
2. Place the Rear Log onto the 2 corresponding locating pins at the
back of the firebox as shown in Figure 29.
13
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
Rear Log
Front Center Log
Figure 32
Figure 29
Vermiculite
6. Install the Top Right Log into the corresponding indentations on
Front Center Log and Front Right Log as shown in Figure 33.
3. Place the Front Right Log and the Center Left Log onto the 2 cor-
responding locating pins (each) as shown in Figure 30.
Top Right Log
Figure 33
Center Left Log
Front Right Log
Figure 30
7. Place the glowing embers on the burner as shown in Figure 34.
One package of ember material has been included with this log set
You will not need to use the entire bag.
4. Place the Front Left Log onto the 2 corresponding locating pins,
then place the Top Left Log onto the locating pin on the Left Center
Log (the log will rest in the corresponding indent on Rear Log). See
Figure 31.
IMPORTANT: The quantity and placement of the ember material can
affect stove performance therefore it is very important that it be placed
as shown in Figure 34.
a. Unpackage and divide the fine ember material (mineral wool) into
dime-sized fluffy pieces.
Top Left Log
b. Distribute the pieces over the top of the front burner area in front of
the forward logs (see Figure 34).
Front Left Log Log
Embers
Figure 34
Figure 31
VERIFY THAT THE GAS LINE HAS BEEN PURGED OF AIR (See Step
10, page 11) .
5. Place the Front Center Log in place as shown in Figure 32. The back
of the log fits into the corresponding indent on Rear Log.
14
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 12. TEST ALL CONNECTIONS FOR
LEAKS (FACTORY AND FIELD).
Millivolt Appliance Checkout
With gas line installed run initial system
checkout before closing up the front of the
unit. Followthepilotlightinginstructionspro-
videdintheHomeowner'sCareandOperation
Instructions (or pull out the instruction label
located in control compartment below glass
door assembly).
The pilot flame should be steady, not lifting
or floating. Flame should be blue in color
with traces of orange at the outer edge.
The top 3/8" (10 mm) at the pilot generator
(thermopile) and the top 1/8" minimum (tip)
of the quick drop out thermocouple should
be engulfed in the pilot flame. The flame
should project 1" (25 mm) beyond the hood
at all three ports (Figure 39).
Test For Gas Leaks
A. Mix a 50% dish soap, 50% water solution
(or use a gas leak detection solution).
B. Light the appliance (refer to the lighting
instructions provided in the insert control
compartmentandtheHomeowner'sCareand
Operation Instructions).
MODELS: EDVI30 & EDVI35
Honeywell Gas Control Valve Diagram
C. Brush all joints and connections with the
soapy water or leak detection solution to check
for leaks. If bubbles are formed, or gas odor is
detected, turnthegascontrolknobtothe“OFF”
position and close the gas shut-off valve. Either
tighten or refasten the leaking connection and
retest as described above.
D. When the gas lines are tested and leak free,
observe the individual tongues of flame on
the burner. Make sure all ports are open and
producing flame evenly across the burner. If
any ports are blocked, or partially blocked,
turn off unit, allow it to cool, then clean out
the ports.
E.Turnongassupplyandtestforgasleaksusing
a soapy water or gas leak detection solution.
Never use an open flame to check for leaks.
PIEZO
IGNITER
CONVERTIBLE
PILOT
ADJUSTMENT
SCREW
HI/LO REGULATOR
(adjusts flame height
and heat output)
Replace logs if removed for pilot inspection.
GAS CONTROL
KNOB
To light the burner, rotate the gas valve
control knob counterclockwise to the “ON”
position then turn “ON” the on/off switch
mounted on the surround assembly (see
Figure 37) or operate the burner with the
optional remote control, wall thermostat or
control switch.
TP/TH
N
L
O
H
O
TP
TH
OUTLET
PRESSURE
TAP
WIRING
TERM-
INALS
INLET
PRESSURE
TAP
Figure 36a
Proper Pilot Flame Appearance
Thermocouple
MODEL EDVI25
Igniter Rod
¹⁄₈" Min
(3 mm)
SIT Millivolt Gas Valve Controls
Hood
GAS CONTROL
KNOB
Step 13. INSTALL SURROUND KIT OR CON-
TROLKIT(seepages12&13inHomeowners
Manual).
³⁄₈" Min
(9 mm)
N
T
I
O
L
Step 14. INSTALL WALL THERMOSTAT AND
REMOTE CONTROL (if purchased)
Pilot
Nozzels
F
I
If an optional Wall Thermostat or Remote Control
Kit was purchased, intall it now, per instructions
provided in kit. See Figure 35. If a wall-mounted
thermostat is selected, mount it in a con-
venient location on a wall near the insert.
Wire the thermostat within the millivolt control
circuit using a maximum of 25feet of 18 gage,
2 conductor wire. Caution: Do not connect the
optional wall thermostat, gas control valve or
control wiring system of the unit to a 120 volt
power supply (residential line voltage).
Thermopile
IN
OUT
OUTLET
PRESSURE
TAP
Figure 39
CONVERTIBLE
HI/LO REGULATOR
(adjusts flame height
and heat output)
INLET
PRESSURE
TAP
Step 16. REINSTALL FRONT GLASS
DOOR ASSEMBLY.
PIEZO
IGNITER
Figure 36b
To reinstall glass door assembly panel, reverse
instructions on Step 5 (page 8).
Burner On/Off Switch and Rheostat Location
If optional surround is installed
Step 17. CHECK BLOWER SYSTEM
OPERATION
Burner On/Off
Switch
SIT & Honeywell
Millivolt Wiring Diagram
WARNING: THE POWER CORD MUST BE
PLUGGED DIRECTLY INTO A PROPERLY
GROUNDED, 120 VOLT, 60 HZ, 3-PRONG
RECEPTACLE ELECTRICAL OUTLET. DO NOT
CUT OR REMOVE THE GROUNDING PRONG
FROM THIS PLUG. IT MUST BE ROUTED TO
AVOID CONTACT. DO NOT ROUTE POWER
CORD UNDER OR IN FRONT OF APPLIANCE.
Rheostat
If any of the original wire as supplied must be replaced,
it must be replaced with Type AWM105°C – 18 GA. wire.
Left Front
Surround
Panel
Figure 37
Control Compartment Access
When the insert heats up, the blower will auto-
matically be turned on by the fan disc, located
under the firebox bottom on the front left side.
It will come on at the speed determined by the
rheostat, located on left surround panel (see
Figure 37). To adjust the blower speed, dial the
rheostat to the desired speed setting. Rotate
the dial down (clockwise), just past the click
(the first ON position) for the highest speed
setting. Turning the knob further clockwise
will provide slower blower speeds. Note: If
the rheostat is not turned “on”, the blower
will not operate.
Pull down hinged door to access control compartment
Thermopile
* SWITCH
* ON/OFF SWITCH, OPTIONAL
THERMOSTAT
Side View of Insert
OR REMOTE
CONTROL RECEIVER
Figure 35
Pull down lower
louver (hinged)
Step 15. CHECKING APPLIANCE OPERA-
TION
Figure 38
15
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
Burner Flame Appearance
Burner Air Shutter Adjustment
Blower Wiring Diagram
Adjusting Set Screw
Adjustment Rod Up
(1/8" Open Position)
120 V AC
Burner Tube
Air Shutter
Power Cord
Black
Adjustment Rod Down
(full open position)
Figure 41
EDVI35
FACTORY AIR SHUTTER SETTING
INCHES (MILLIMETERS)
Sootingisindicatedbyblackpuffsdeveloping
atthetipsofverylongorangeflames.Sooting
resultsinblackdepositsformingonthelogs,
appliance inside surfaces and on exterior
surfaces adjacent to the vent termination.
Sooting is caused by incomplete combus-
tion in the flames and lack of combustion air
entering the air shutter opening. To achieve
a warm yellow to orange flame that does not
soot, the shutter opening must be adjusted
between these two extremes.
Models
Gas Type
Air Shutter Gap
Fan Disc
Natural Gas 3/16" (4.76 mm)
EDVI25
Propane
Natural Gas
Propane
3/8" (9.52 mm)
5/16" (7.94 mm)
1/2" (12.7 mm)
3/8" (9.52 mm)
1/2" (12.7 mm)
EDVI30
EDVI35
Natural Gas
Propane
Figure 42
No smoke or soot should be present. Repo-
sition the logs if flames impinge on any of
them. If the logs are properly positioned
and sooting conditions exist, the air shutter
opening on the main burner tube should be
adjusted.
CAUTION: CARBON WILL BE PRODUCED IF THE
AIR SHUTTER IS CLOSED TOO MUCH.
Any damage due to carboning resulting from
improperly setting the air shutter is NOT covered
under the warranty.
Rheostat
Black
The following chart (Table 10) is provided to
aid you in achieving the correct air shutter
adjustment for your installation.
IMPORTANT: ENSURE THAT THE FRONT
GLASS PANEL IS IN PLACE AND SEALED
DURING ADJUSTMENT.
Blower
Assembly
Figure 40
Air Shutter Adjustment Guidelines:
Burner Adjustment Procedure
Step 18. BURNER ADJUSTMENT
Flame Appearance and Sooting
Air Shutter
Adjustment
Amount of
Primary Air
Flame
Color
AIR SHUTTER ADJUSTMENT SHOULD
ONLY BE PERFORMED BY AN AUTHO-
RIZED INSTALLER AT THE TIME OF THE
INSTALLATION OR SERVICE.
Air shutter Gap
should be
increased
Air shutter Gap
should be
Decreased
If air shutter is
closed too far
Flame will be
orange
Proper flame appearance is a flame which
is blue at the base and becomes yellow /
orange in the body of the flame. When the
appliance is first lit, the entire flame may be
blue and will gradually turn yellow/orange
during the first 6-8 minutes of operation. If
after 6-8 minutes the flame stays lowered
blue, or if the flame is orange with evidence
of sooting (black tip), the air shutter may
require adjustment.
Flame will be
blue
If air shutter is
open too far
CAUTION: THE ADJUSTMENT ROD AND
NEARBY APPLIANCE SURFACES ARE
HOT. EXERCISE CAUTION TO AVOID
INJURY WHILE ADJUSTING FLAME
APPEARANCE.
Table 10
When satisfied that the appliance operates
properly, proceed to finish the installation.
LeavethecontrolknobintheONpositionand
the on/off switch in the OFF position.
.
Initially, always position the air shutter to the
factorysettingasshowninFigure42(adjust-
mentrodislocatedinthelowercontrolarea).
This can be done by moving the adjustment
rodupordownaccordingly. Allowtheburner
to operate for at least 15 minutes. Observe
the flame continuously. If it appears weak
or sooty as previously described, adjust the
air shutter to a more open position until the
proper flame appearance is achieved.
STEP 19. INSTALL LOUVER KIT
Appliances operated with air shutter open-
ingsthataretoolargewillexhibitflamesthat
are blue and transparent. These weak, blue
and transparent flames are termed anemic.
If the air shutter openings are too small,
sooting may develop
Installlouverkitpertheinstructionsprovided
with the kit.
16
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY / LISTING LABELS - MODELS: EDVI30 & EDVI35
MODEL NO.
EDVI30
MODEL NO.
EDVI35
MANUFACTURED AT:
Union City, TN
MANUFACTURED AT:
Union City, TN
FOR USE WITH NATURAL GAS. EQUIPE POUR GAZ NATUREL
ALTITUDE
FOR USE WITH NATURAL GAS. EQUIPE POUR GAZ NATUREL
ALTITUDE
0-4500 FT/PI
(0-1370M)
0-4500 FT/PI
(0-1370M)
MIN. GAS SUPPLY PRESS (“WC)
PRESS MIN. D’ALIMENTATION (“CE)
MANIFOLD PRESSURE (“WC)
PRESSION CE TUBULURE (“CE)
MANUFACTURER’S RECOMMENDED ORIFICE SIZE
DIMENSION DE L’INJECTEUR RECOMMANDE PAR
MANUFACTURIER (DMS)
MIN. GAS SUPPLY PRESS (“WC)
PRESS MIN. D’ALIMENTATION (“CE)
MANIFOLD PRESSURE (“WC)
PRESSION CE TUBULURE (“CE)
MANUFACTURER’S RECOMMENDED ORIFICE SIZE
DIMENSION DE L’INJECTEUR RECOMMANDE PAR
MANUFACTURIER (DMS)
4.5”
3.5”
4.5”
3.5”
#33
#37
MAX INPUT (BTU/HR)
MAX INPUT (BTU/HR)
ENTREE MAX
30,000
ENTREE MAX
35,000
MIN INPUT (BTU/HR)
MIN INPUT (BTU/HR)
ENTREE MIN
21,500
ENTREE MIN
25,500
ELECTRICAL RATING/EXIGENCES ELECTRIQUES:
-UNIT/APPAREIL: MILIVOLT
ELECTRICAL RATING/EXIGENCES ELECTRIQUES:
-UNIT/APPAREIL: MILIVOLT
1 ph
1 ph
60 HZ
60 HZ
120 VOLTS
120 VOLTS
LESS THAN 5 AMPS
LESS THAN 5 AMPS
SIDEWALL
FLOOR
8”
0”
64”
18”
12”
SIDEWALL
FLOOR
8”
0”
MINIMUM
CLEARANCES TO
COMBUSTIBLE
MATERIAL
MINIMUM
CLEARANCES TO
CEILING (FROM BOTTOM OF UNIT)
MANTEL FROM TOP OF UNIT
CEILING (FROM BOTTOM OF UNIT)
MANTEL FROM TOP OF UNIT
64”
COMBUSTIBLE
MATERIAL
18”
MANTEL
DEPTH (MAX)
12”
(MAX)
M ANTEL DEPTH
DEGAGEMENT
MINIMUM DE
MATERIAUX
COMBUSTIBLES
MUR ADJACENTS
PLANCHER
203mm
0mm
203mm
0mm
DEGAGEMENT
MINIMUM DE
MATERIAUX
COMBUSTIBLES
MUR ADJACENTS
PLANCHER
1626mm
PLAFOND (DU BAS DE L’APPAREIL)
MANTEAU DU DESSUS DE L'APPAREIL
1626mm
PLAFOND (DU BAS DE L’APPAREIL)
457mm
305mm
457mm
305mm
MANTEAU DU DESSUS DE L'APPAREIL
PROFONDEUR DU MANTEAU
(MAX)
PROFONDEUR DU MANTEAU
(MAX)
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUEL. FOR INSTALLATION
IN SOLID FUEL FIREPLACES. THIS VENTED GAS FIREPLACE HEATER IS NOT FOR USE
WITH AIR FILTERS.
FOYER AU GAZ CHAUFFANT AVEC EVACUATION - NE DOIT PAS ETRE UTILISE AVEC UN
COMBUSTIBLE SOLIDE. DOIT ETRE INSTALLE DANS UNE CHEMINEE EXISTANTE QUI
BRULE LE COMBUSTIBLE SOLIDE. NE PAS UTILISER DE FILTRE A AIR AVEC CE FOYER AU
GAZ A EVACUATION.
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUEL. FOR INSTALLATION
IN SOLID FUEL FIREPLACES. THIS VENTED GAS FIREPLACE HEATER IS NOT FOR USE
WITH AIR FILTERS.
FOYER AU GAZ CHAUFFANT AVEC EVACUATION - NE DOIT PAS ETRE UTILISE AVEC UN
COMBUSTIBLE SOLIDE. DOIT ETRE INSTALLE DANS UNE CHEMINEE EXISTANTE QUI
BRULE LE COMBUSTIBLE SOLIDE. NE PAS UTILISER DE FILTRE A AIR AVEC CE FOYER AU
GAZ A EVACUATION.
FOR USE WITH GLASS DOOR CERTIFIED WITH THE APPLIANCE ONLY.
N’UTILISER SEULEMENT QUE LA PORTE DE VERRE CERTIFIE AVEC L’APPAREIL.
“CAUTION: Do not operate the appliance with glass removed, cracked or broken.
Replacement of panel should be done by a licensed or qualified service person.”
“This appliance is equipped at the factory for use with natural gas only. Units using
propane must be field converted using the LP conversion kit, Cat. No. H0920.
FOR USE WITH GLASS DOOR CERTIFIED WITH THE APPLIANCE ONLY.
N’UTILISER SEULEMENT QUE LA PORTE DE VERRE CERTIFIE AVEC L’APPAREIL.
“CAUTION: Do not operate the appliance with glass removed, cracked or broken.
Replacement of panel should be done by a licensed or qualified service person.”
“This appliance is equipped at the factory for use with natural gas only. Units using
propane must be field converted using t he LP conversion kit, Cat. No. H0921.
FINAL INSPECTION BY:
FINAL INSPECTION BY:
ANSI Z21.88-2002
CSA 2.33-2002
CAN/CGA 2.17-M91
ANSI Z21.88-2002
CSA 2.33-2002
CAN/CGA 2.17-M91
VENTED GAS FIREPLACE HEATER
FOYERA AU GAZ CHAUFFANT AVEC EVACUATION
P/N 9-1467A
VENTED GAS FIREPLACE HEATER
FOYERA AU GAZ CHAUFFANT AVEC EVACUATION
P/N 9-1467B
SERIAL NUMBER/NOMBRE DE SERIE
SERIAL NUMBER/NOMBRE DE SERIE
XXX XXX
XXX XXX
IIIIIIIIIIIIIIIIIIII
IIIIIIIIIIIIIIIIIIII
XXX
XXX
P/N 9-1467A
P/N 9-1467B
17
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY / LISTING LABEL - MODEL: EDVI25
MODEL NO.
MANUFACTURED AT:
EDVI25
Lynwood, CA
FOR USE WITH NATURAL GAS. EQUIPE POUR GAZ NATUREL
ALTITUDE
0-4500 FT/PI
(0-1370M)
MIN. GAS SUPPLY PRESS (“WC)
PRESS MIN. D’ALIMENTATION (“CE)
MANIFOLD PRESSURE (“WC)
PRESSION CE TUBULURE (“CE)
MANUFACTURER’S RECOMMENDED ORIFICE SIZE
DIMENSION DE L’INJECTEUR RECOMMANDE PAR
MANUFACTURIER (DMS)
4.5”
3.5”
#41
MAX INPUT (BTU/HR)
ENTREE MAX
25,000
MIN INPUT (BTU/HR)
ENTREE MIN
17,000
ELECTRICAL RATING/EXIGENCES ELECTRIQUES:
-UNIT/APPAREIL: MILIVOLT
1 ph
60 HZ
120 VOLTS
LESS THAN 5 AMPS
SIDEWALL
FLOOR
8”
MINIMUM
CLEARANCES TO
COMBUSTIBLE
MATERIAL
0”
CEILING (FROM BOTTOM OF UNIT)
MANTEL FROM TOP OF UNIT
64”
15.5”
12”
MANTEL
DEPTH (MAX)
DEGAGEMENT
MINIMUM DE
MATERIAUX
COMBUSTIBLES
MUR ADJACENTS
PLANCHER
203mm
0mm
1626mm
394mm
305mm
PLAFOND (DU BAS DE L’APPAREIL)
MANTEAU DU DESSUS DE L'APPAREIL
(MAX)
PROFONDEUR DU MANTEAU
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUEL. FOR INSTALLATION
IN SOLID FUEL FIREPLACES. THIS VENTED GAS FIREPLACE HEATER IS NOT FOR USE
WITH AIR FILTERS.
FOYER AU GAZ CHAUFFANT AVEC EVACUATION - NE DOIT PAS ETRE UTILISE AVEC UN
COMBUSTIBLE SOLIDE. DOIT ETRE INSTALLE DANS UNE CHEMINEE EXISTANTE QUI
BRULE LE COMBUSTIBLE SOLIDE. NE PAS UTILISER DE FILTRE A AIR AVEC CE FOYER AU
GAZ A EVACUATION.
FOR USE WITH GLASS DOOR CERTIFIED WITH THE APPLIANCE ONLY.
N’UTILISER SEULEMENT QUE LA PORTE DE VERRE CERTIFIE AVEC L’APPAREIL.
“CAUTION: Do not operate the appliance with glass removed, cracked or broken.
Replacement of panel should be done by a licensed or qualified service person.”
“This appliance is equipped at the factory for use with natural gas only. Units using
propane must be field converted using the LP conversion kit, Cat. No. H1576.
FINAL INSPECTION BY:
ANSI Z21.88-2002
CSA 2.33-2002
CAN/CGA 2.17-M91
VENTED GAS FIREPLACE HEATER
FOYERA AU GAZ CHAUFFANT AVEC EVACUATION
P/N 9-1467C
SERIAL NUMBER/NOMBRE DE SERIE
XXX XXX
IIIIIIIIIIIIIIIIIIII
XXX
P/N 9-1467C
18
Download from Www.Somanuals.com. All Manuals Search And Download.
19
NOTE: THIS PAGE LEFT BLANK INTENTIONALLY.
Download from Www.Somanuals.com. All Manuals Search And Download.
Lennox reserves the right to make changes at any time, without notice, in design,
materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.
Printed in U.S.A. © Lennox Hearth Products 2003
P/N 775,156M REV. G 3/2005
1110 West Taft Avenue • Orange, CA 92865
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Kyocera Digital Camera SL400R User Manual
LA Audio Electronic Stereo Amplifier UB282 User Manual
La Crosse Technology Portable Radio WD 3312 User Manual
Lennox International Inc Air Cleaner 504 User Manual
Liebert Power Supply Nfinity User Manual
Liebherr Refrigerator 7082 135 00 User Manual
Liebherr Refrigerator Freestanding Refrigerator User Manual
Lindy Switch MC5 IP User Manual
Lopi Indoor Fireplace Gas Stove And Fireplace User Manual
Martin Audio Stereo Receiver M3+ User Manual