Lennox Hearth Indoor Fireplace EDVI35 User Manual

INSTALLATION INSTRUCTIONS  
MANUAL  
DIRECT-VENT GAS FIREPLACE HEATER INSERTS  
Elite™ Series, Models: EDVI25, EDVI30 & EDVI35  
Suitable for installation into masonry or factory built fireplaces.  
RETAIN THIS MANUAL FOR FUTURE REFERENCE  
P/N 775,156M Rev. G, 3/2005  
Report No. 116-F-14-5  
These appliances may be installed in an aftermarket permanently located,  
manufactured (mobile) home, where not prohibited by local codes.  
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE  
LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE  
POURRÉDUIREAUMINIMUMLERISQUED’INCENDIE  
OU POUR ÉVITER TOUT DOMMAGE MATÉRIEL,  
TOUTE BLESSURE OU LA MORT.  
WARNING:IFTHEINFORMATIONINTHISMANUAL  
IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO-  
SIONMAYRESULTCAUSINGPROPERTYDAMAGE,  
PERSONAL INJURY OR LOSS OF LIFE.  
FOR YOUR SAFETY: Do not store or use gasoline  
or other flammable  
s or liquids in the vicinity of this or any other  
appliance.  
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser  
d’essencenid’autrevapeursouliquidesinflammablesdans  
le voisinage de cet appareil ou de tout autre appareil.  
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une  
odeur de gaz:  
FOR YOUR SAFETY: What to do if you smell gas:  
• DO NOT light any appliance.  
• Ne pas tenter d’allumer d’appareil.  
• DO NOT touch any electrical switches.  
• Do not use any phone in your building.  
• Immediately call your gas supplier from a  
neighbor’s phone. Follow your gas suppliers  
instructions.  
• Ne touchez à aucun interrupteur. Ne pas vous servir  
des téléphones se trouvant dans le batiment où vous  
vous trouvez.  
• Evacuez la piéce, le bâtiment ou la zone.  
• Appelez immédiatement votre fournisseur de gaz depuis  
un voisin. Suivez les instructions du fournisseur.  
• Si vous ne pouvez rejoindre le fournisseur de gaz,  
appelez le service dos incendies.  
• If your gas supplier cannot be reached, call  
the fire department.  
Installation and service must be performed by a  
qualified installer, service agency or the gas sup-  
plier.  
Linstallation et service doit être exécuté par un qualifié  
installeur, agence de service ou le fournisseur de gaz.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The millivolt appliances are manually con-  
trolled and feature a spark igniter (piezo)  
that allows the appliance's pilot gas to be  
lit without the use of matches or batteries.  
Thissystemprovidescontinuedserviceinthe  
event of a power outage. However, the heat  
circulation blower requires 120 volt power  
(the appliance can be safely used with the  
blower turned off). The blower operation is  
controlledbyavariablespeedrheostatlocated  
on the left side surround panel (if optional  
surroundisinstalled)andtemperatureswitch  
located underneath of firebox bottom on the  
front left side.  
CARBON MONOXIDE POISONING: EARLY  
SIGNSOFCARBONMONOXIDEPOISONING  
ARE SIMILAR TO THE FLU WITH HEAD-  
ACHES, DIZZINESS AND/OR NAUSEA. IF  
YOU HAVE THESE SIGNS, OBTAIN FRESH  
AIR IMMEDIATELY. TURN OFF THE GAS  
SUPPLY TO THE APPLIANCE AND HAVE  
IT SERVICED BY A QUALIFIED PROFES-  
SIONAL, AS IT MAY NOT BE OPERATING  
CORRECTLY.  
Manifold Gas Supply Pressure (all models)  
Fuel  
Low  
High  
(LO) 1.6” WC  
(.40 kPa)  
(HI) 3.5” WC  
(.87 kPa)  
Natural Gas  
(LO) 6.3” WC  
(1.57 kPa)  
(HI) 10” WC  
(2.49 kPa)  
Propane  
Table 3  
Test gauge connections are provided on the  
frontofthemillivoltgascontrolvalve(identi-  
fied IN for the inlet and OUT for the manifold  
side). See Figure 36a & 36b on page 14.  
WARNING: DO NOT PLACE CLOTHING OR  
OTHER FLAMMABLE MATERIALS ON OR  
NEAR THESE APPLIANCES.  
Table 4 shows the units gas orifice size for the  
elevations indicated.  
GENERAL INFORMATION  
Main Burner Orifice Size  
WARNING: FAILURE TO COMPLY WITH THE  
INSTALLATIONANDOPERATINGINSTRUCTIONS  
PROVIDED IN THIS DOCUMENT WILL RESULT  
IN AN IMPROPERLY INSTALLED AND OPERAT-  
ING APPLIANCE, VOIDING ITS WARRANTY.  
ANY CHANGE TO THESE APPLIANCES AND/OR  
OPERATING CONTROLS IS DANGEROUS.  
IMPROPER INSTALLATION OR USE OF THESE  
APPLIANCES CAN CAUSE SERIOUS INJURY OR  
DEATH FROM FIRE, BURNS, EXPLOSION OR  
CARBON MONOXIDE POISONING.  
Model #  
Nat.  
Gas  
Pro-  
Elevation  
The appliance installation, repair and annual  
inspectionshouldbeperformedbyaqualified  
serviceperson. Itisimperativethatthecontrol  
compartment,burnerandcirculatingairpas-  
sage way of the appliance be kept clean.  
pane  
Feet (meters)  
#41  
#53  
0-4500'  
(0-1370 meters)  
EDVI25  
EDVI30  
(.096") (.0595")  
1/16"  
#37  
(.104") (.0625")  
0-4500'  
(0-1370 meters)  
0-4500'  
#33  
#51  
S'assurer que le brùleur et le compartiment  
des commandes sont propres. Voir les  
instructions d'installation et d'utilisation qui  
accompagnent l'appareil.  
EDVI35  
(.113") (.067") (0-1370 meters)  
Table 4  
These appliances and their individual shut-off  
valvesmustbedisconnectedfromthegassupply  
piping system during any pressure testing of  
that system at pressures greater than 1/2 psig  
(3.5 kPa).  
Provide adequate clearances and adequate  
accessibilityclearanceforserviceandproper  
operation (see table 5 on page 7).  
WARNING:CHILDRENANDADULTSSHOULD  
BE ALERTED TO THE HAZARDS OF HIGH  
SURFACE TEMPERATURES. USE CAUTION  
AROUND THE APPLIANCE TO AVOID BURNS  
ORCLOTHINGIGNITION.YOUNGCHILDREN  
SHOULD BE CAREFULLY SUPERVISED  
WHEN THEY ARE IN THE SAME ROOM AS  
THE APPLIANCE.  
Table 1 shows the BTU input for each  
model:  
These appliances must be isolated from the  
gas supply piping system (by closing their  
individual manual shut-off valve) during any  
pressure testing of the gas supply piping  
system at test pressures equal to or less than  
1/2 psig (3.5 kPa).  
Millivolt Models with  
Manually-Modulated Gas Valves  
Natural Gas  
Input rate  
(BTU/HR)  
17,000 to  
25,000  
Propane  
Input rate  
(BTU/HR)  
19,000 to  
25,000  
AVERTISSEMENT: SURVEILLER LES  
ENFANTS. GARDER LES VÊTEMENTS,  
LES MEUBLES, L'ESSENCE OU AUTRES  
LIQUIDES À VAPEUR INFLAMMABLES À  
COTE DE L'APPAREIL.  
Model #  
These appliances may be installed in an after-  
market permanently located, manufactured  
home (USA only) or mobile home, where not  
prohibited by local codes.  
EDVI25  
EDVI30  
21,500 to  
30,000  
22,000 to  
28,000  
Cet appareil peut être installé dans un maison  
préfabriquée (É.-U. seulement) ou mobile déjà  
installée à demeure si les réglements locaux le  
permettent.  
25,500 to  
35,000  
DO NOT USE THESE APPLIANCES IF ANY  
PART HAS BEEN UNDER WATER. IMMEDI-  
ATELY CALL A QUALIFIED, PROFESSIONAL  
SERVICE TECHNICIAN TO INSPECT THE  
APPLIANCES AND TO REPLACE ANY PARTS  
OF THE CONTROL SYSTEM AND ANY GAS  
CONTROLS WHICH HAVE BEEN UNDER  
WATER.  
26,000 to  
34,000  
EDVI35  
Table 1  
THESE APPLIANCES MUST NOT BE CON-  
NECTED TO A CHIMNEY OR FLUE SERV-  
ING A SEPARATE SOLID FUEL BURNING  
APPLIANCE.  
Tables 2 and 3 show the units' gas pressure  
requirements for all models:  
NE PAS SE SERVIR DE CET APPAREIL S'IL A  
ÉTÉ PLONGÉ DANS L'EAU, COMPLÈTEMENT  
OU EN PARTIE. APPELER UN TECHNICIEN  
QUALIFIÉ POUR INSPECTER L'APPAREIL ET  
REMPLACERTOUTEPARTIEDUSYSTÈMEDE  
CONTRÔLE ET TOUTE COMMANDE QUI ONT  
ÉTÉ PLONGÉS DANS L'EAU.  
Inlet Gas Supply Pressure (all models)  
Fuel  
Minimum  
4.5” WC  
(1.12 kPa)  
11.0” WC  
(2.73 kPa)  
Maximum  
10.5” WC  
(2.61 kPa)  
13.0” WC  
(3.23 kPa)  
WARNING: THESE APPLIANCES MUST BE  
PROPERLY CONNECTED TO A VENTING  
SYSTEM. OPERATION OF THESE GAS  
APPLIANCES WHEN NOT CONNECTED TO  
A PROPERLY INSTALLED AND MAINTAINED  
VENTING SYSTEM CAN RESULT IN CARBON  
MONOXIDE(CO)POISONINGANDPOSSIBLE  
DEATH.  
Natural Gas  
Propane  
Table 2  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIREPLACE REQUIREMENTS  
QUESTIONS TO ASK LOCAL BUILDING  
OFFICIAL  
6. Maximum amount of gas pipe without a  
pressure test - type of test required?  
7. Are below grade penetrations of the gas  
line allowed?  
8. Is concealed gas piping allowed?  
9. Specific requirements of concealed  
fittings?  
10. Is rigid pipe to appliance required?  
11. Allowed piping materials?  
12. Shut-off valve required within 4 feet  
of the firebox?  
13. May the shut-off valve be concealed?  
14. Rooms where the installation is not  
allowed?  
IMPORTANT: When installing these appliances  
into a factory built fireplace or heatform, the air  
flow within and around the fireplace shall not  
be altered by the installation of the insert (i.e.  
DO NOT BLOCK louvers or cooling air inlet or  
outlet ports, circulating air chambers in a steel  
fireplace liner or metal heat circulator).  
These appliances must be installed per  
manufacturers’ instructions. Installations  
mustconformtoappropriatelocalcodesand  
applicable state and federal requirements.  
Familiarity with these requirements before  
installation is essential. Some important  
considerationstodiscusswithlocalbuilding  
officials include:  
CAUTION:Thefactorybuiltreboxmustaccept  
the insert without modification other than  
removing bolted or screwed together pieces  
such as smoke shelf / deflectors, ash lips,  
screenordoortracks,loggrates,refractoryand  
damper assemblies. Any fireplace component,  
which is removed, must be retained so they  
can be reinstalled to restore the fireplace to  
its original operating condition. The removal  
of any part must not alter the integrity of the  
outer shell of the pre-engineered fireplace  
cabinet in any way.  
1. Applicablecodes(i.e.UniformMechanical  
Code, State or Regional Gas Codes, National  
Fuel Gas Code).  
2. Local amendments  
3. Recognized testing lab: OMNI-Test Labo-  
ratories Inc.; Beaverton, Oregon  
In the absence of local codes, installation  
should conform to National Fuel Gas Code,  
ANSI Z223.1 / NFPA 54-Latest Edition in the  
USA or National Fuel Gas Code, CAN/CGA-  
B149-Latest Edition in Canada.  
4. Is a permit required - cost?  
5. Insomestatesormunicipalities,alicensed  
gas fitter or plumber may be required to  
install these appliances. Check with your  
localbuildingofficialforrequirementsinyour  
area (i.e. Is a license required for installation  
of gas supply line)?  
HIGH ALTITUDE  
If any components are removed from (or  
altered) from the existing fireplace, a Warning  
Label (see below) must be affixed inside the  
fireplace firebox, so that it shall be visible  
upon removal of the fireplace insert. Note:  
RTV high temperature silicone is an approved  
adhesive.  
Installations at Altitudes of 0 to 4500 feet:  
These appliances have been tested and  
approved for elevations of 0 to 4500 feet (0  
to 1370 meters).  
Installations at Altitudes above 4500 feet:  
Forelevationsabove4500feet(1370meters),  
install these appliances according to the  
regulations of the local authorities having  
jurisdictionand, intheUSA, thelatestedition  
of the National Fuel Gas Code (ANSI Z223.1)  
or, in Canada, the latest edition of the CAN-  
B149.1 and CAN-B149.2 codes.  
Fireplace Warning Label  
(Provided in Accessory Package)  
WARNING  
THIS FIREPLACE HAS BEEN ALTERED TO  
ACCOMMODATE A FIREPLACE INSERT AND  
SHOULD BE INSPECTED BY A QUALIFIED  
PERSON PRIOR TO RE-USE AS A  
CONVENTIONAL FIREPLACE.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS: EDVI25  
DIMENSIONS  
EDVI25  
SPECIFICATIONS  
EDVI25  
Inches (millimeters)  
26 5/8" (676 mm)  
20 1/2" (521 mm)  
5” (127 mm)  
Min. / Max. BTU hr  
Input - NG  
Min. / Max. BTU hr  
Input - LP  
17,000 to 25,000  
19,000 to 25,000  
A
B
C
SM.= 41 1/16” (1043 mm) & MED.= 44 1/8” (1121 mm)  
SM.= 26 1/16” (662 mm) & MED.= 27 5/8” (702 mm)  
19 1/2” (483 mm)  
D
E
Co-linear DV Vent  
Size  
3” Dia. Liner  
(exhaust & intake)  
F
G
H
I
110 cfm  
Room Blower CFM  
1 15/16” (49 mm)  
10 9/16” (268 mm)  
1 1/4” (32 mm)  
J
17 1/4” (438 mm)  
15 15/16” (405 mm)  
10 7/8” (276 mm)  
24 7/8” (632 mm)  
EFFICIENCIES  
K
L **  
M **  
EDVI25  
65 % (NG)  
66 % (LP)  
86 % (NG)  
89 % (LP)  
14" (356 mm)  
9 5/8” (224 mm)  
N
P
Steady State  
Efficiency *  
** The total glass viewing area equals approx. 270 1/2 Sq. In.  
* The Steady State Efficiency numbers based on  
maximum vent configuration.  
Top View  
A
B
C
N
Note: Due to Lennox’ ongoing commitment  
to quality , all specifications, ratings  
and dimensions are subject to change  
without notice.  
E
I
D
G
H
I
P
E
L
F
J
K
M
Figure 1  
Front View  
Side View  
5
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS: EDVI30 & EDVI35  
DIMENSIONS  
EDVI30  
SPECIFICATIONS  
EDVI30  
EDVI35  
EDVI35  
Inches (millimeters)  
25 15/16" (659 mm)  
22 1/4" (578 mm)  
Inches (millimeters)  
32 1/16” (814 mm)  
24 3/16” (614 mm)  
5" (127 mm)  
Min. / Max. BTU/hr  
Input - NG  
Min. / Max. BTU/hr  
Input - LP  
21,500 to 30,000  
25,500 to 35,000  
A
B
C
D
22,000 to 28,000  
26,000 to 34,000  
5" (127 mm)  
40 1/4” (1022 mm)Sm.  
45 3/4” (1162 mm) Med.  
49 1/4” (1251 mm) Lg.  
27 1/2” (699 mm) Sm.  
30 1/4” (768 mm) Med.  
30” (762 mm) Lg.  
20 7/8" (530 mm)  
1 13/16” (46 mm)  
9 15/16” (252 mm)  
1 7/16” (37 mm)  
Co-linear DV Vent  
Size  
3” Dia. Liner  
(exhaust & intake)  
3” Dia. Liner  
(exhaust & intake)  
48 1/16” (1221 mm) Med.  
34 1/16”(865 mm) Med.  
130 cfm  
130 cfm  
Room Blower CFM  
E
F
G
H
I
26 11/16” (678 mm)  
1 13/16” (46 mm)  
9 7/8”(251 mm)  
1 5/8” (41 mm)  
EFFICIENCIES  
EDVI30  
EDVI35  
66% (NG)  
70% (LP)  
69% (NG)  
70% (LP)  
(based on CSA P.4.1)  
20 1/4” (514 mm)  
J
24” (610 mm)  
86% (NG)  
88% (LP)  
Steady State  
Efficiency *  
87% (NG)  
89% (LP)  
K
15 1/4” (387 mm)  
11 3/16” (284 mm)  
23 1/4” (591 mm)  
13 7/16” (341 mm)  
18 3/8” (467 mm)  
15 5/8” (397 mm)  
29 7/16” (748 mm)  
16 7/8” (427 mm)  
L**  
M**  
N
** The total glass viewing area equals approx.:  
EDVI30 = 290 Sq. In. & EDVI35 = 460 Sq. In.  
* The Steady State Efficiency numbers based on  
maximum vent configuration.  
Top View  
A
B
C
N
Note: Due to Lennox’ ongoing commitment  
to quality , all specifications, ratings  
and dimensions are subject to change  
without notice.  
D
G
I
H
E
F
L
J
K
M
Front View  
Side View  
Figure 2  
6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MINIMUM CLEARANCES TO COMBUSTIBLES: EDVI25, EDVI30 & EDVI35  
These appliances can be installed in most residential  
fireplace configurations. If installed close to an adjacent  
Inches (millimeters)  
EDVI30  
wall, ensure that the minimum clearances to combustible  
surfaces are maintained. A local building inspector should  
review your plans prior to installation.  
Clearances to Combustibles  
Min.  
Max.  
EDVI25  
8" (203 mm)  
64" (1626 mm)  
EDVI35  
A
Side Wall  
8" (203 mm)  
8" (203 mm)  
Min.  
Min.  
B
Ceiling or Alcove Height  
64" (1626 mm)  
64" (1626 mm)  
Refer to Figures 3, 4a, 4b and 5 for Clearances to Combus-  
tibles. Minimum clearances include spacers/standoffs or  
surfaces to combustible construction.  
C* Mantel Height  
D* Mantel Projection from Wall  
See Fig. 3 & 4b See Fig. 3 & 4a  
See Fig. 3 & 4a Min.  
See Fig. 4b  
0" (0 mm)  
See Fig. 4a  
0" (0 mm)  
See Fig. 4a  
0" (0 mm)  
MAX.  
Min.  
E
Clearance to Floor  
F** Hearth Protection  
Notes for Table 5:  
**16" (406 mm)  
**16" (406 mm) **16" (406 mm)  
Min.  
(from Fireplace Face)  
*
This includes any projections such as shelves, window  
sills, mantels, spacers/standoffs or surfaces to com-  
bustible construction etc. above the appliance. Paint or  
lacquer used to finish the mantel must be heat resis-  
tant in order to avoid discoloration.  
G
H
I
Hearth Protection Width  
Alcove Width  
Alcove Depth  
44" (1118 mm)  
45" (1143 mm)  
36" (914 mm)  
49" (1245 mm) 48" (1219 mm)  
50" (1270 mm) 49" (1245 mm)  
Min.  
Min.  
MAX.  
36" (914 mm)  
36" (914 mm)  
** If hearth is elevated, subtract 1 inch of hearth  
extension required for every 2 inches of height (see  
Figure 6).  
Table 5  
Clearances  
Alcove Minimum Width: The specified minimum width of the  
alcove cannot be reduced with the use of wall protection.  
Ceiling (or)  
Alcove Height  
Mantel  
Top View Alcove  
Fireplace  
C
Insert  
Top of Insert  
B
Hearth  
Side  
Wall  
A
I
H
G
Hearth Protection  
E
Figure 5  
Figure 3  
Mantel Clearance, Models: EDVI30 &  
EDVI35: The mantel should be located  
in the shaded area (light gray) shown  
below.  
Mantel Clearance, Model: EDVI25: The  
mantel should be located in the shaded  
area (light gray) shown below.  
Hearth Protection: For every 2" of hearth height,  
subtract 1" of hearth extension required.  
Side View  
of Insert  
D
D
18"  
15 1/2"  
F
17"  
16"  
13"  
Existing Fireplace Hearth  
11"  
C
15"  
14"  
16"  
2"  
C
8 1/2"  
4"  
15"  
14"  
6"  
7"  
0
0
12”  
5”  
1”  
0
8”  
13 1/2"  
12 10  
11  
8
6
4
2
0
\
9
7
5
3
1
\
Top of Insert louver  
(see "C" on Fig. 3)  
Side View  
Top of Insert  
(see "C" on Fig. 3)  
Side View  
At 7" hearth height, no hearth extension is required  
Figure 4a  
Figure 4b  
Figure 6  
7
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 4 LIFT INSERT INTO POSITION (read  
Fireplace Requirements on page 4 first) Lift  
insert into position in front of the fireplace where  
unit is to be installed. Discard bottom carton.  
MINIMUM FIREPLACE DIMENSIONS  
Refer to Figures 7 and 8 for Minimum Fire-  
place Clearance Dimensions. See pages 5 &  
6 for actual insert body dimensions.  
CAUTION: If any portion of the chimney  
system shows signs of structural or mechani-  
cal weaknesses, such as: cracks, leaky  
joints, corroded or warped surfaces, the  
faulty portion must be repaired or replaced  
prior to installing this appliance.  
Consult your local authority having juris-  
diction for requirements in your area.  
Step5: REMOVESTANDARD GLASSDOOR  
ASSEMBLY.  
Before the fireplace insert is assembled and  
installed, you must consider whether the  
appliance must be converted for use with  
propane gas (see step 7 on Page 9). You  
must also consider the vent length require-  
ments.  
Step 2: PREPARATION - Plan and install gas  
line. These appliances are provided with an  
opening on the left hand side of the control  
compartment.A3/8"NPTgassupplypipemust  
be brought near this inlet hole.  
WARNING: HANDLE GLASS DOOR WITH  
EXTREME CARE! THE GLASS DOOR  
ASSEMBLYISSUSCEPTIBLETODAMAGE.  
DO NOT SCRATCH WHILE HANDLING OR  
WHILE REINSTALLING.  
Gas Supply Line - We recommend that a  
qualified individual such as a plumber or gas  
fitter be used to correctly size and route the  
gas supply line to the appliance. Installing a  
gas supply line from the fuel supply to the  
applianceinvolvesnumerousconsiderationsof  
materials,protection,sizing,locations,controls,  
pressure,sediment,andmore.Certainlynoone  
unfamiliarandunqualifiedshouldattemptsizing  
or installing gas piping.  
M
Remove Front Glass Enclosure as Follows:  
1) Locate the spring hook under the glass  
door assembly (see Figure 9). Pull hook  
forward until it releases out of the bottom  
door frame.  
Top View  
K
Figure 7  
Pull door hook forward until it releases  
L
The gas supply line should be plumbed from  
thefuelsourcetotheareawheretheappliance  
is to be installed per requirements outlined  
in NFPA 54 - latest edition (USA) or B149  
- latest edition (Canada).  
9"  
Min.  
Reference  
J
The proper gas line diameter must be used  
to run from the supply regulator (at the gas  
company meter) to the appliance. Never use  
galvanized or plastic pipe. Refer to table 7  
for suggested sizing of the gas supply line if  
black iron pipe is being used.  
Side View  
Figure 8  
Door hook is located below glass door  
Figure 9  
K
2) Swing the bottom of the door outward  
(see Figure 10) and lift it off of firebox top.  
Set door aside in a safe place.  
The gas supply line should be connected to  
the appliance at step 9 (page 11).  
Inches (millimeters)  
Min. Fireplace  
Clearance  
Dimensions  
Suggested Sizing of Black Iron Pipe  
Schedule 40 - Pipe Supply Line  
EDVI25  
EDVI35  
EDVI30  
25"  
22"  
19"  
Schedule 40 Pipe  
Schedule 40 Pipe  
J
Height  
Depth  
(559 mm) (635 mm)  
(483 mm)  
Inside Diameter (Inches)  
Length (Feet)  
14 1/2"  
(368 mm)  
17"  
(432 mm)  
14"  
(356 mm)  
Natural Gas Propane Gas  
K
L
0-10  
1/2  
1/2  
1/2  
3/4  
3/4  
3/8  
1/2  
1/2  
1/2  
1/2  
27"  
(686 mm)  
32 1/4"  
(673 mm) (819 mm)  
26 1/2"  
Width/Front  
Width/Rear  
10-40  
Swing bottom of  
Door outward  
23 1/4"  
22 1/2"  
(591 mm) (572 mm)  
25"  
40-100  
100-150  
150-200  
M
(635 mm)  
Figure 10  
Table 6  
DETAILED INSTALLATION STEPS  
Table 7  
Lift Top of Door  
Off this Flange  
IMPORTANTNOTE:Ifpropaneisused,beaware  
that if the tank size is too small (i.e. under  
100-lbs, if this is the only gas appliance in the  
dwelling. Ref. NPFA 58), there may be loss of  
pressure, resulting in insufficient fuel delivery  
(which can result in sooting or other malfunc-  
tions). Any damage resulting from an improper  
installation, such as this, is not covered under  
the limited warranty.  
Step 1: CLEAN FIREPLACE (If necessary)  
Thoroughly clean the masonry or factory  
built fireplace.  
CAUTION: The fireplace in which this gas  
insert is to be installed must be thoroughly  
cleaned if it has been used to burn wood or  
synthetic logs. Have the chimney and all  
inside surfaces of the fireplace brushed and  
vacuumed so that no soot, embers, or loose  
combustion deposits can be drawn into the  
heat circulation blower and blown into the  
living area.  
Figure 11  
WARNING: NEVER OPERATE UNIT WITH-  
OUT THE FRONT GLASS DOOR PANEL IN  
PLACE AND SECURE.  
Step 3 UNPACK THE INSERT - Remove  
the top and side cartons. Remove all the  
inner packages and packing materials and  
discard.  
8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STEP6: REMOVEPACKAGEDMATERIALSFROMINSIDEFIREBOXAND  
SET ASIDE (log set, bag of embers, bag of vermiculite, propane  
conversion kit - if needed to run on LP gas).  
Simpson Dura Vent Components  
Part No.  
980  
Description  
Termination Cap, Standard  
Termination Cap, High Wnd  
Chimney Liner Term. Kit  
Liner, Flex, 3” Dia. /. 35 feet.  
Step 7: INSTALL LP CONVERSION KIT (IF NECESSARY) - Install the  
LP conversion kit per instructions provided with kit.  
991  
923GK  
2280  
Step 8: VENTING SYSTEM INSTALLATION (Refer to Vent Manu-  
facturer Installation Instructions)  
Table 9b  
This appliance is designed to using 3” diameter UL1181 listed alumi-  
num liner for the Air Intake and 3” diameter UL1777 listed gas vent  
liner for the Exhaust (see Figures 14 & 15). See Table 8 for miniumum  
distances from roof to termination cap inlet/outlet.  
Flex Liner Installation:  
Liner Connec-  
tor Plate  
Exhaust  
Intake  
Hose  
Clamps  
Vertical Termination Height Minimum  
(Factory Built and Masonry Fireplaces)  
The vent/air intake termination clearances above the high side of an  
angled roof is as follows:  
Screw  
Guide  
After liners are secured to collars, slide liner con-  
nector plate forward and secure with screw.  
Feet (meters)  
8 (2.4)  
Figure 12  
7 (2.1)  
Positive Flue Connection (acceptable methods for sealing chimney throat)  
Masonry and Factory Built Fireplaces  
6 (1.8)  
Aqualifiedinstallershouldevaluatetheexistingreplacetodeterminethe  
bestmethodforachievingapositiveueconnectionbetweentheventand  
intake liners and the chimney. The most common method is to secure a  
noncombustible seal-off plate (i.e. 22-gage sheet steel) in the fireplace  
throat using masonry screws. Other acceptable methods include packing  
noncombustible material (i.e. rockwool) around the liners. Whichever  
“seal off” method is used must effectively seal the area to prevent room  
air passage to the chimney of the fireplace.  
5 (1.5)  
4 (1.2)  
3 (0.9)  
2 (0.6)  
1 (0.3)  
0 (0.0)  
The outside air inlet does not  
require a full reline (if intake liner  
is terminated in chimney and a  
positiveueconnectionisachieved  
as specified).  
Exhaust 3" (75mm)  
UL 1777. A full length  
liner is required from  
the exhaust outlet on  
appliance to center collar  
of termination cap.  
Table 8  
Roof Pitch  
WARNING: Do not substitute the heat-rated flex liner (UL1777)  
for the Exhaust with any other type liner or a fire may result  
causing property damage, personal injury or loss of life.  
Existing Fireplace Flue  
(chimney)  
IMPORTANT NOTES:  
• Adjust Leveling Bolts if Necessary: Two leg leveling bolts are installed  
into existing holes in the bottom rear of appliance. Turn the leveling bolts  
to adjust for correct height.  
Positive Flue Connec-  
tion (sealing fireplace  
throatusinganoncom-  
bustible seal-off plate  
or insulation).  
Air Inlet Liner  
(for combus-  
tion air) When  
terminatingthe  
air inlet liner  
at this point,  
a positive flue  
connection is  
required (to  
ensure com-  
bustion air is  
drawn down  
the chimney  
only).  
• Refer to Vent Manufacturer Installation Instructions.  
Direct Vent System Components  
TM  
The following "Security Secure Vent " or "Simpson Dura-Vent" brand  
Collinear Direct-Vent components may be safely used with these appli-  
ances (see Figures 14 & 15).  
Masonry and Factory  
Built Fireplaces  
Lennox Hearth Products – Collinear Direct-Vent Kits  
Cat. No.  
H0908  
Model  
TKDVI  
FKDVI  
Description  
Termination Kit, DVI  
H0909  
Flex Kit, DVI 3" X 35'  
Figure 13  
Table 9a  
9
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Factory Built Fireplace Installation Diagram  
Masonry Fireplace Installation Diagram  
Vertical Term-  
The standard cap in Termination Kit, H0908, is a  
high wind cap  
Masonry chimneys may take  
ination Cap  
and Flashing.  
Cat. No.  
various contours which the  
flexible liners will accomodate.  
However, keep the flexible liner  
as STRAIGHT as possible, avoid  
unnecessary bending.  
Vertical Termination Cap  
and Flashing, Cat. No. H0908  
H0908  
Liner Requirements:  
Vertical Height Min. = 8 ft. (2.44 M)  
Vertical height Max. = 40 ft. (12.2 M)  
See Direct Vent System Components  
on Page 9.  
Exhaust  
Air  
Intake  
Hook up Air  
& Exhaust  
as Shown  
Here  
The standard cap  
in Termination  
Kit, H0908, is a  
high wind cap  
Liner Requirements:  
Vertical Height Min. = 8 ft. (2.44 M)  
Vertical Termination  
Adapter  
Vertical height Max. = 40 ft. (12.2 M)  
See Direct Vent System Components  
on Page 9.  
Clay  
Chimney  
Liner  
Exhaust  
Air  
Intake  
Storm Collar  
The flexible vent pipe must  
NOT be allowed to sag behind  
insert or in fireplace flue.  
Hook up Air &  
Exhaust as  
Shown Here  
Roof  
Flashing  
The flexible vent pipe must  
NOT be allowed to sag behind  
insert or in fireplace flue.  
Read fireplace  
requirements,  
page 4  
Use 3" diameter listed liner  
(UL1181 or UL1777) for the AIR  
INTAKE.  
Use 3" diameter listed gas vent liner  
(UL1777 ONLY) for the EXHAUST  
Read Fireplace  
Requirements on  
page 4  
Use 3" diameter listed  
liner (UL1181 or UL1777)  
for the AIR INTAKE.  
Damper plate is  
removed or fastened  
in open position  
Use 3" diameter listed  
liner (UL1777 ONLY) for  
the EXHAUST  
Exhaust and air  
Intake collars  
Exhaust and Air  
Intake Collars  
Gear Clamps  
Gear Clamps  
Liner  
Liner  
• The Flex Kit, Cat. No. H0909 includes one 35' flex liner and four gear clamps.  
• The Termination Kit, Cat. No. H0908 includes the termination cap with two  
collinear collars for 3” flex attachments and flashing.  
• The Flex Kit, Cat. No. H0909 includes one 35' flex liner and four gear clamps.  
• The Termination Kit, Cat. No. H0908 includes the termination cap with two collinear  
collars for 3” flex attachments and flashing.  
Make sure that both liners will pass through existing damper area. Remove or lock  
damper to allow the passage of the flexible liners. If the damper will not allow the  
passage of both liners, DO NOT PROCEED FURTHER. Consult a local mason for  
removal of the damper without risk of structural damage or leakage.  
Before running the flexible liners, make sure that both liners will pass through  
existing damper area. Remove or lock damper to allow the passage of the flexible  
liners. If the damper will not allow the passage of both liners, DO NOT PROCEED  
FURTHER (the appliance may NOT be installed into the fireplace).  
Figure 14  
Figure 15  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Flex Liner Installation (see Figure 14 for  
Masonry Fireplace Installations and Figure  
15 for Factory Built Fireplaces):  
Step 10. PURGING AIR  
AIR PURGING PROCEDURES MUST BE  
PERFORMED BY A QUALIFIED TECHNICIAN  
ONLY.  
Note: Refer to Vent Manufacturer Instal-  
lation Instructions.  
Purging Air from Supply Line  
Screw  
a. Turn gas supply line valve off.  
b. Loosen setscrew at inlet pressure tap on  
control valve (see Figure 36).  
c. Turn gas supply line valve on.  
d. When gas flows, turn supply valve off.  
e. Close the inlet pressure tap.  
1) Cut the flex liners as required (mark both  
ends of one of the flexible liners as INLET).  
Liner  
Connector  
Plate  
2) Connect the liner marked INLET to the inlet  
side of the termination adaptor. Connect the  
other liner to the exhaust side. Secure liner  
to INLET collar with hose clamp.  
Purging Air from Appliance  
Figure 17  
Purge air from appliance by holding gas  
control valve down in the pilot position  
until pilot will light (see Figure 19). DO NOT  
LIGHT A MATCH IF YOU SMELL GAS. Light  
a match then allow gas flow to pilot. If the  
Match “blows”, there is air in the line (purge  
line). If the flame is straight and tall, there is  
no gas pressure.  
3) Install flashing.  
Notes:  
4) Insert both liners into chimney, passing  
through the damper opening.  
• Final gas connection should be made after  
unit is in place to avoid damage to line when  
pushing the unit into position.  
5) Install termination cap.  
• Mill-pac, high temperature silicone and/or  
screws may also be used to secure the liners  
to the collars (gear clamps must also be  
used).  
6) Remove the liner connector plate from the  
insert top (by removing the screw shown in  
Figure 17, then sliding plate backward until it  
clearstheretainingbreackets). Linersshouldbe  
streched just enough to prevent the possibility  
of sagging or coiling in the flue. Cut off excess  
liner (see collar locations on pages 5 & 6).  
When first lighting the appliance, it will take  
a few minutes for the line to purge air from  
theappliance.Oncepurgingiscomplete,the  
pilot and burner will light and operate as indi-  
cated in the instruction manual. Subsequent  
lightings of the appliance will not require such  
purging. Inspect the pilot flame (remove logs,  
if necessary, handling carefully).  
Step 9. CONNECTING GAS LINE  
Make gas line connections. All codes require a  
shut-offvalvemountedinthesupplyline.Figure  
18 illustrates two methods for connecting the  
gas supply. The flex-line method is acceptable  
in the U.S., however, Canadian requirements  
vary depending on locality. Installation must  
be in compliance with local codes.  
7) Connect the liner marked INLET to the inlet  
collar on the liner connector plate (marked  
with an "I"). Connect the remaining liner to  
the exhaust collar (marked with an "E") on  
the liner connector plate. Note: Both con-  
nections should be secured to collars using  
gear clamps.  
These appliances are equipped with a gas  
flex line for use (where permitted) in con-  
necting the unit to the gas line. A gas flex  
line is provided to aid in attaching the appli-  
ance to the gas supply. The gas flex line  
can only be used where local codes permit.  
See Figure 18 for flex line description. The  
flex line is rated for both natural and pro-  
pane gas. A manual shut off valve is also  
provided with the flex line. The gas control  
valveislocatedinthelowercontrolcompart-  
ment. The millivolt control valve has a 3/8"  
(10 mm) NPT thread inlet port fitting.  
8) Slide the liner connector plate all the way  
forward and secure into place with a screw  
(provided) as shown in Figure 16 & 17.  
Figure 19  
Combustion  
Air (inlet)  
Exhaust (outlet)  
Step 11. INSTALLING LOGS, VERMICU-  
LITE AND EMBERS  
Damper  
Thepackagedlogset,vermiculiteandembers  
are located within the firebox of the insert.  
Note: The EDVI25/EDVI30 log set is shown  
in figures 20-28 and the EDVI35 log set is  
shown in figures 29-34.  
Gear Clamp  
Gas  
Gas Flex Line Connector  
Valve  
³ꢀ₈" NPT x  
¹ꢀ₂" x³ꢀ₈" Flare  
Flare Fitting  
Shut-Off Valve  
Liner  
Connector  
Plate  
Installation Instructions:  
³ꢀ₈" Flex Tubing  
ꢃꢀ -INꢄ  
Gas  
WARNING: If logs are not installed accord-  
ing to the directions shown here, flame  
impingement and improper combustion  
couldoccurandresultinsootand/orexces-  
sive production of carbon monoxide (CO),  
a colorless, odorless, toxic gas.  
Stub  
3EDIMENT 4RAP  
ꢂRECOMMENDED  
¹ꢀ₂  
Reducer  
x
³ꢀ"  
³ꢀ₈ꢀ .IPPLE  
³ꢀ₈"5NION  
³ꢀ₈ꢀ #LOSE .IPPLE  
³ꢀ₈ꢀ 3HUTꢁ/FF 6ALVE  
Figure 18 - GAS CONNECTION  
Figure 16  
Note: If an optional Brick Liner Kit was  
purchased, intall it now, per instructions  
provided in kit.  
11  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOGS, VERMICULITE AND EMBERS - Models EDVI25 & EDVI30 (For  
3. Place the Center Log onto the 2 corresponding locating pins as  
shown in Figure 22.  
EDVI35 Log Installation Instructions, see Page 13).  
The packaged log set, vermiculite and embers are located within the  
firebox of the insert.  
Installation Instructions:  
WARNING: IF LOGS ARE NOT INSTALLED ACCORDING TO THE  
DIRECTIONSSHOWNHERE,FLAMEIMPINGEMENTANDIMPROPER  
COMBUSTIONCOULDOCCURANDRESULTINSOOTAND/OREXCES-  
SIVE PRODUCTION OF CARBON MONOXIDE (CO), A COLORLESS,  
ODORLESS, TOXIC GAS.  
Notes:  
• If an optional Brick Liner Kit was purchased, intall it now, per instruc-  
tions provided in kit.  
• Place some vermiculite around the burner as shown in Figure 28  
before installing the logs (the entire bag of vermiculite will NOT be  
used).  
Center Log  
Figure 22  
4. Place the Front Left Log onto the 2 corresponding locating pins as  
shown in Figure 23.  
Carefully install the seven-piece log set into the firebox as shown in  
these instructions. All logs should fit onto corresponding pins and/or  
log stoppers. This will ensure a proper flame and safe combustion.  
1. Place the largest log onto the 2 corresponding locating pins at the  
back of the firebox as shown in Figure 20.  
Front Left Log  
Figure 23  
5. Install the Top Left Log onto the corresponding locating pin and  
indentation on Center Log as shown in Figure 24.  
Rear Log  
Figure 20  
2. Place the Front Right Log onto the 2 corresponding locating pins  
as shown in Figure 21.  
Figure 24  
Top Left Log  
6. Install the Front Center Log over the Front Right Log . The front  
of log will rest on the burner and the back of log will rest on rear log  
as shown in Figure 25.  
Front Right Log  
Figure 21  
12  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 25  
Front Center Log  
7. Install the Top Right Log into the corresponding indentations on  
Front Center Log and front right twig as shown in Figure 26.  
Embers  
Figure 27  
Figure 28  
Vermiculite  
Top Right Log  
Figure 26  
LOGS, VERMICULITE AND EMBERS - Model EDVI35  
8. Place the glowing embers on the burner as shown in Figure 27.  
WARNING: IF LOGS ARE NOT INSTALLED ACCORDING TO THE  
DIRECTIONSSHOWNHERE,FLAMEIMPINGEMENTANDIMPROPER  
COMBUSTIONCOULDOCCURANDRESULTINSOOTAND/OREXCES-  
SIVE PRODUCTION OF CARBON MONOXIDE (CO), A COLORLESS,  
ODORLESS, TOXIC GAS.  
One package of ember material has been included with this log set  
You will not need to use the entire bag.  
IMPORTANT: The quantity and placement of the ember material can  
affect insert performance therefore it is very important that it be placed  
as shown in Figure 27.  
Carefully install the seven-piece log set into the firebox as shown in  
these instructions. All logs should fit onto corresponding pins and/or  
log stoppers. This will ensure a proper flame and safe combustion.  
a. Unpackage and divide the fine ember material (mineral wool) into  
dime-sized fluffy pieces.  
b. Distribute the pieces over the top of the front burner ports, filling the  
area in front of the forward logs.  
1. Place some vermiculite around the burner as shown in Figure 29  
(the entire bag of vermiculite will NOT be used).  
2. Place the Rear Log onto the 2 corresponding locating pins at the  
back of the firebox as shown in Figure 29.  
13  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Rear Log  
Front Center Log  
Figure 32  
Figure 29  
Vermiculite  
6. Install the Top Right Log into the corresponding indentations on  
Front Center Log and Front Right Log as shown in Figure 33.  
3. Place the Front Right Log and the Center Left Log onto the 2 cor-  
responding locating pins (each) as shown in Figure 30.  
Top Right Log  
Figure 33  
Center Left Log  
Front Right Log  
Figure 30  
7. Place the glowing embers on the burner as shown in Figure 34.  
One package of ember material has been included with this log set  
You will not need to use the entire bag.  
4. Place the Front Left Log onto the 2 corresponding locating pins,  
then place the Top Left Log onto the locating pin on the Left Center  
Log (the log will rest in the corresponding indent on Rear Log). See  
Figure 31.  
IMPORTANT: The quantity and placement of the ember material can  
affect stove performance therefore it is very important that it be placed  
as shown in Figure 34.  
a. Unpackage and divide the fine ember material (mineral wool) into  
dime-sized fluffy pieces.  
Top Left Log  
b. Distribute the pieces over the top of the front burner area in front of  
the forward logs (see Figure 34).  
Front Left Log Log  
Embers  
Figure 34  
Figure 31  
VERIFY THAT THE GAS LINE HAS BEEN PURGED OF AIR (See Step  
10, page 11) .  
5. Place the Front Center Log in place as shown in Figure 32. The back  
of the log fits into the corresponding indent on Rear Log.  
14  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 12. TEST ALL CONNECTIONS FOR  
LEAKS (FACTORY AND FIELD).  
Millivolt Appliance Checkout  
With gas line installed run initial system  
checkout before closing up the front of the  
unit. Followthepilotlightinginstructionspro-  
videdintheHomeowner'sCareandOperation  
Instructions (or pull out the instruction label  
located in control compartment below glass  
door assembly).  
The pilot flame should be steady, not lifting  
or floating. Flame should be blue in color  
with traces of orange at the outer edge.  
The top 3/8" (10 mm) at the pilot generator  
(thermopile) and the top 1/8" minimum (tip)  
of the quick drop out thermocouple should  
be engulfed in the pilot flame. The flame  
should project 1" (25 mm) beyond the hood  
at all three ports (Figure 39).  
Test For Gas Leaks  
A. Mix a 50% dish soap, 50% water solution  
(or use a gas leak detection solution).  
B. Light the appliance (refer to the lighting  
instructions provided in the insert control  
compartmentandtheHomeowner'sCareand  
Operation Instructions).  
MODELS: EDVI30 & EDVI35  
Honeywell Gas Control Valve Diagram  
C. Brush all joints and connections with the  
soapy water or leak detection solution to check  
for leaks. If bubbles are formed, or gas odor is  
detected, turnthegascontrolknobtotheOFF”  
position and close the gas shut-off valve. Either  
tighten or refasten the leaking connection and  
retest as described above.  
D. When the gas lines are tested and leak free,  
observe the individual tongues of flame on  
the burner. Make sure all ports are open and  
producing flame evenly across the burner. If  
any ports are blocked, or partially blocked,  
turn off unit, allow it to cool, then clean out  
the ports.  
E.Turnongassupplyandtestforgasleaksusing  
a soapy water or gas leak detection solution.  
Never use an open flame to check for leaks.  
PIEZO  
IGNITER  
CONVERTIBLE  
PILOT  
ADJUSTMENT  
SCREW  
HI/LO REGULATOR  
(adjusts flame height  
and heat output)  
Replace logs if removed for pilot inspection.  
GAS CONTROL  
KNOB  
To light the burner, rotate the gas valve  
control knob counterclockwise to the “ON”  
position then turn “ON” the on/off switch  
mounted on the surround assembly (see  
Figure 37) or operate the burner with the  
optional remote control, wall thermostat or  
control switch.  
TP/TH  
N
L
O
H
O
TP  
TH  
OUTLET  
PRESSURE  
TAP  
WIRING  
TERM-  
INALS  
INLET  
PRESSURE  
TAP  
Figure 36a  
Proper Pilot Flame Appearance  
Thermocouple  
MODEL EDVI25  
Igniter Rod  
¹⁄₈" Min  
(3 mm)  
SIT Millivolt Gas Valve Controls  
Hood  
GAS CONTROL  
KNOB  
Step 13. INSTALL SURROUND KIT OR CON-  
TROLKIT(seepages12&13inHomeowners  
Manual).  
³⁄₈" Min  
(9 mm)  
N
T
I
O
L
Step 14. INSTALL WALL THERMOSTAT AND  
REMOTE CONTROL (if purchased)  
Pilot  
Nozzels  
F
I
If an optional Wall Thermostat or Remote Control  
Kit was purchased, intall it now, per instructions  
provided in kit. See Figure 35. If a wall-mounted  
thermostat is selected, mount it in a con-  
venient location on a wall near the insert.  
Wire the thermostat within the millivolt control  
circuit using a maximum of 25feet of 18 gage,  
2 conductor wire. Caution: Do not connect the  
optional wall thermostat, gas control valve or  
control wiring system of the unit to a 120 volt  
power supply (residential line voltage).  
Thermopile  
IN  
OUT  
OUTLET  
PRESSURE  
TAP  
Figure 39  
CONVERTIBLE  
HI/LO REGULATOR  
(adjusts flame height  
and heat output)  
INLET  
PRESSURE  
TAP  
Step 16. REINSTALL FRONT GLASS  
DOOR ASSEMBLY.  
PIEZO  
IGNITER  
Figure 36b  
To reinstall glass door assembly panel, reverse  
instructions on Step 5 (page 8).  
Burner On/Off Switch and Rheostat Location  
If optional surround is installed  
Step 17. CHECK BLOWER SYSTEM  
OPERATION  
Burner On/Off  
Switch  
SIT & Honeywell  
Millivolt Wiring Diagram  
WARNING: THE POWER CORD MUST BE  
PLUGGED DIRECTLY INTO A PROPERLY  
GROUNDED, 120 VOLT, 60 HZ, 3-PRONG  
RECEPTACLE ELECTRICAL OUTLET. DO NOT  
CUT OR REMOVE THE GROUNDING PRONG  
FROM THIS PLUG. IT MUST BE ROUTED TO  
AVOID CONTACT. DO NOT ROUTE POWER  
CORD UNDER OR IN FRONT OF APPLIANCE.  
Rheostat  
If any of the original wire as supplied must be replaced,  
it must be replaced with Type AWM105°C – 18 GA. wire.  
Left Front  
Surround  
Panel  
Figure 37  
Control Compartment Access  
When the insert heats up, the blower will auto-  
matically be turned on by the fan disc, located  
under the firebox bottom on the front left side.  
It will come on at the speed determined by the  
rheostat, located on left surround panel (see  
Figure 37). To adjust the blower speed, dial the  
rheostat to the desired speed setting. Rotate  
the dial down (clockwise), just past the click  
(the first ON position) for the highest speed  
setting. Turning the knob further clockwise  
will provide slower blower speeds. Note: If  
the rheostat is not turned “on”, the blower  
will not operate.  
Pull down hinged door to access control compartment  
Thermopile  
* SWITCH  
* ON/OFF SWITCH, OPTIONAL  
THERMOSTAT  
Side View of Insert  
OR REMOTE  
CONTROL RECEIVER  
Figure 35  
Pull down lower  
louver (hinged)  
Step 15. CHECKING APPLIANCE OPERA-  
TION  
Figure 38  
15  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Burner Flame Appearance  
Burner Air Shutter Adjustment  
Blower Wiring Diagram  
Adjusting Set Screw  
Adjustment Rod Up  
(1/8" Open Position)  
120 V AC  
Burner Tube  
Air Shutter  
Power Cord  
Black  
Adjustment Rod Down  
(full open position)  
Figure 41  
EDVI35  
FACTORY AIR SHUTTER SETTING  
INCHES (MILLIMETERS)  
Sootingisindicatedbyblackpuffsdeveloping  
atthetipsofverylongorangeames.Sooting  
resultsinblackdepositsformingonthelogs,  
appliance inside surfaces and on exterior  
surfaces adjacent to the vent termination.  
Sooting is caused by incomplete combus-  
tion in the flames and lack of combustion air  
entering the air shutter opening. To achieve  
a warm yellow to orange flame that does not  
soot, the shutter opening must be adjusted  
between these two extremes.  
Models  
Gas Type  
Air Shutter Gap  
Fan Disc  
Natural Gas 3/16" (4.76 mm)  
EDVI25  
Propane  
Natural Gas  
Propane  
3/8" (9.52 mm)  
5/16" (7.94 mm)  
1/2" (12.7 mm)  
3/8" (9.52 mm)  
1/2" (12.7 mm)  
EDVI30  
EDVI35  
Natural Gas  
Propane  
Figure 42  
No smoke or soot should be present. Repo-  
sition the logs if flames impinge on any of  
them. If the logs are properly positioned  
and sooting conditions exist, the air shutter  
opening on the main burner tube should be  
adjusted.  
CAUTION: CARBON WILL BE PRODUCED IF THE  
AIR SHUTTER IS CLOSED TOO MUCH.  
Any damage due to carboning resulting from  
improperly setting the air shutter is NOT covered  
under the warranty.  
Rheostat  
Black  
The following chart (Table 10) is provided to  
aid you in achieving the correct air shutter  
adjustment for your installation.  
IMPORTANT: ENSURE THAT THE FRONT  
GLASS PANEL IS IN PLACE AND SEALED  
DURING ADJUSTMENT.  
Blower  
Assembly  
Figure 40  
Air Shutter Adjustment Guidelines:  
Burner Adjustment Procedure  
Step 18. BURNER ADJUSTMENT  
Flame Appearance and Sooting  
Air Shutter  
Adjustment  
Amount of  
Primary Air  
Flame  
Color  
AIR SHUTTER ADJUSTMENT SHOULD  
ONLY BE PERFORMED BY AN AUTHO-  
RIZED INSTALLER AT THE TIME OF THE  
INSTALLATION OR SERVICE.  
Air shutter Gap  
should be  
increased  
Air shutter Gap  
should be  
Decreased  
If air shutter is  
closed too far  
Flame will be  
orange  
Proper flame appearance is a flame which  
is blue at the base and becomes yellow /  
orange in the body of the flame. When the  
appliance is first lit, the entire flame may be  
blue and will gradually turn yellow/orange  
during the first 6-8 minutes of operation. If  
after 6-8 minutes the flame stays lowered  
blue, or if the flame is orange with evidence  
of sooting (black tip), the air shutter may  
require adjustment.  
Flame will be  
blue  
If air shutter is  
open too far  
CAUTION: THE ADJUSTMENT ROD AND  
NEARBY APPLIANCE SURFACES ARE  
HOT. EXERCISE CAUTION TO AVOID  
INJURY WHILE ADJUSTING FLAME  
APPEARANCE.  
Table 10  
When satisfied that the appliance operates  
properly, proceed to finish the installation.  
LeavethecontrolknobintheONpositionand  
the on/off switch in the OFF position.  
.
Initially, always position the air shutter to the  
factorysettingasshowninFigure42(adjust-  
mentrodislocatedinthelowercontrolarea).  
This can be done by moving the adjustment  
rodupordownaccordingly. Allowtheburner  
to operate for at least 15 minutes. Observe  
the flame continuously. If it appears weak  
or sooty as previously described, adjust the  
air shutter to a more open position until the  
proper flame appearance is achieved.  
STEP 19. INSTALL LOUVER KIT  
Appliances operated with air shutter open-  
ingsthataretoolargewillexhibitamesthat  
are blue and transparent. These weak, blue  
and transparent flames are termed anemic.  
If the air shutter openings are too small,  
sooting may develop  
Installlouverkitpertheinstructionsprovided  
with the kit.  
16  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY / LISTING LABELS - MODELS: EDVI30 & EDVI35  
MODEL NO.  
EDVI30  
MODEL NO.  
EDVI35  
MANUFACTURED AT:  
Union City, TN  
MANUFACTURED AT:  
Union City, TN  
FOR USE WITH NATURAL GAS. EQUIPE POUR GAZ NATUREL  
ALTITUDE  
FOR USE WITH NATURAL GAS. EQUIPE POUR GAZ NATUREL  
ALTITUDE  
0-4500 FT/PI  
(0-1370M)  
0-4500 FT/PI  
(0-1370M)  
MIN. GAS SUPPLY PRESS (“WC)  
PRESS MIN. D’ALIMENTATION (CE)  
MANIFOLD PRESSURE (“WC)  
PRESSION CE TUBULURE (“CE)  
MANUFACTURER’S RECOMMENDED ORIFICE SIZE  
DIMENSION DE L’INJECTEUR RECOMMANDE PAR  
MANUFACTURIER (DMS)  
MIN. GAS SUPPLY PRESS (“WC)  
PRESS MIN. D’ALIMENTATION (CE)  
MANIFOLD PRESSURE (“WC)  
PRESSION CE TUBULURE (“CE)  
MANUFACTURER’S RECOMMENDED ORIFICE SIZE  
DIMENSION DE L’INJECTEUR RECOMMANDE PAR  
MANUFACTURIER (DMS)  
4.5”  
3.5”  
4.5”  
3.5”  
#33  
#37  
MAX INPUT (BTU/HR)  
MAX INPUT (BTU/HR)  
ENTREE MAX  
30,000  
ENTREE MAX  
35,000  
MIN INPUT (BTU/HR)  
MIN INPUT (BTU/HR)  
ENTREE MIN  
21,500  
ENTREE MIN  
25,500  
ELECTRICAL RATING/EXIGENCES ELECTRIQUES:  
-UNIT/APPAREIL: MILIVOLT  
ELECTRICAL RATING/EXIGENCES ELECTRIQUES:  
-UNIT/APPAREIL: MILIVOLT  
1 ph  
1 ph  
60 HZ  
60 HZ  
120 VOLTS  
120 VOLTS  
LESS THAN 5 AMPS  
LESS THAN 5 AMPS  
SIDEWALL  
FLOOR  
8”  
0”  
64”  
18”  
12”  
SIDEWALL  
FLOOR  
8”  
0”  
MINIMUM  
CLEARANCES TO  
COMBUSTIBLE  
MATERIAL  
MINIMUM  
CLEARANCES TO  
CEILING (FROM BOTTOM OF UNIT)  
MANTEL FROM TOP OF UNIT  
CEILING (FROM BOTTOM OF UNIT)  
MANTEL FROM TOP OF UNIT  
64”  
COMBUSTIBLE  
MATERIAL  
18”  
MANTEL  
DEPTH (MAX)  
12”  
(MAX)  
M ANTEL DEPTH  
DEGAGEMENT  
MINIMUM DE  
MATERIAUX  
COMBUSTIBLES  
MUR ADJACENTS  
PLANCHER  
203mm  
0mm  
203mm  
0mm  
DEGAGEMENT  
MINIMUM DE  
MATERIAUX  
COMBUSTIBLES  
MUR ADJACENTS  
PLANCHER  
1626mm  
PLAFOND (DU BAS DE L’APPAREIL)  
MANTEAU DU DESSUS DE L'APPAREIL  
1626mm  
PLAFOND (DU BAS DE L’APPAREIL)  
457mm  
305mm  
457mm  
305mm  
MANTEAU DU DESSUS DE L'APPAREIL  
PROFONDEUR DU MANTEAU  
(MAX)  
PROFONDEUR DU MANTEAU  
(MAX)  
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUEL. FOR INSTALLATION  
IN SOLID FUEL FIREPLACES. THIS VENTED GAS FIREPLACE HEATER IS NOT FOR USE  
WITH AIR FILTERS.  
FOYER AU GAZ CHAUFFANT AVEC EVACUATION - NE DOIT PAS ETRE UTILISE AVEC UN  
COMBUSTIBLE SOLIDE. DOIT ETRE INSTALLE DANS UNE CHEMINEE EXISTANTE QUI  
BRULE LE COMBUSTIBLE SOLIDE. NE PAS UTILISER DE FILTRE A AIR AVEC CE FOYER AU  
GAZ A EVACUATION.  
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUEL. FOR INSTALLATION  
IN SOLID FUEL FIREPLACES. THIS VENTED GAS FIREPLACE HEATER IS NOT FOR USE  
WITH AIR FILTERS.  
FOYER AU GAZ CHAUFFANT AVEC EVACUATION - NE DOIT PAS ETRE UTILISE AVEC UN  
COMBUSTIBLE SOLIDE. DOIT ETRE INSTALLE DANS UNE CHEMINEE EXISTANTE QUI  
BRULE LE COMBUSTIBLE SOLIDE. NE PAS UTILISER DE FILTRE A AIR AVEC CE FOYER AU  
GAZ A EVACUATION.  
FOR USE WITH GLASS DOOR CERTIFIED WITH THE APPLIANCE ONLY.  
N’UTILISER SEULEMENT QUE LA PORTE DE VERRE CERTIFIE AVEC LAPPAREIL.  
“CAUTION: Do not operate the appliance with glass removed, cracked or broken.  
Replacement of panel should be done by a licensed or qualified service person.”  
“This appliance is equipped at the factory for use with natural gas only. Units using  
propane must be field converted using the LP conversion kit, Cat. No. H0920.  
FOR USE WITH GLASS DOOR CERTIFIED WITH THE APPLIANCE ONLY.  
N’UTILISER SEULEMENT QUE LA PORTE DE VERRE CERTIFIE AVEC LAPPAREIL.  
“CAUTION: Do not operate the appliance with glass removed, cracked or broken.  
Replacement of panel should be done by a licensed or qualified service person.”  
“This appliance is equipped at the factory for use with natural gas only. Units using  
propane must be field converted using t he LP conversion kit, Cat. No. H0921.  
FINAL INSPECTION BY:  
FINAL INSPECTION BY:  
ANSI Z21.88-2002  
CSA 2.33-2002  
CAN/CGA 2.17-M91  
ANSI Z21.88-2002  
CSA 2.33-2002  
CAN/CGA 2.17-M91  
VENTED GAS FIREPLACE HEATER  
FOYERA AU GAZ CHAUFFANT AVEC EVACUATION  
P/N 9-1467A  
VENTED GAS FIREPLACE HEATER  
FOYERA AU GAZ CHAUFFANT AVEC EVACUATION  
P/N 9-1467B  
SERIAL NUMBER/NOMBRE DE SERIE  
SERIAL NUMBER/NOMBRE DE SERIE  
XXX XXX  
XXX XXX  
IIIIIIIIIIIIIIIIIIII  
IIIIIIIIIIIIIIIIIIII  
XXX  
XXX  
P/N 9-1467A  
P/N 9-1467B  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY / LISTING LABEL - MODEL: EDVI25  
MODEL NO.  
MANUFACTURED AT:  
EDVI25  
Lynwood, CA  
FOR USE WITH NATURAL GAS. EQUIPE POUR GAZ NATUREL  
ALTITUDE  
0-4500 FT/PI  
(0-1370M)  
MIN. GAS SUPPLY PRESS (“WC)  
PRESS MIN. D’ALIMENTATION (CE)  
MANIFOLD PRESSURE (“WC)  
PRESSION CE TUBULURE (“CE)  
MANUFACTURER’S RECOMMENDED ORIFICE SIZE  
DIMENSION DE L’INJECTEUR RECOMMANDE PAR  
MANUFACTURIER (DMS)  
4.5”  
3.5”  
#41  
MAX INPUT (BTU/HR)  
ENTREE MAX  
25,000  
MIN INPUT (BTU/HR)  
ENTREE MIN  
17,000  
ELECTRICAL RATING/EXIGENCES ELECTRIQUES:  
-UNIT/APPAREIL: MILIVOLT  
1 ph  
60 HZ  
120 VOLTS  
LESS THAN 5 AMPS  
SIDEWALL  
FLOOR  
8”  
MINIMUM  
CLEARANCES TO  
COMBUSTIBLE  
MATERIAL  
0”  
CEILING (FROM BOTTOM OF UNIT)  
MANTEL FROM TOP OF UNIT  
64”  
15.5”  
12”  
MANTEL  
DEPTH (MAX)  
DEGAGEMENT  
MINIMUM DE  
MATERIAUX  
COMBUSTIBLES  
MUR ADJACENTS  
PLANCHER  
203mm  
0mm  
1626mm  
394mm  
305mm  
PLAFOND (DU BAS DE L’APPAREIL)  
MANTEAU DU DESSUS DE L'APPAREIL  
(MAX)  
PROFONDEUR DU MANTEAU  
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUEL. FOR INSTALLATION  
IN SOLID FUEL FIREPLACES. THIS VENTED GAS FIREPLACE HEATER IS NOT FOR USE  
WITH AIR FILTERS.  
FOYER AU GAZ CHAUFFANT AVEC EVACUATION - NE DOIT PAS ETRE UTILISE AVEC UN  
COMBUSTIBLE SOLIDE. DOIT ETRE INSTALLE DANS UNE CHEMINEE EXISTANTE QUI  
BRULE LE COMBUSTIBLE SOLIDE. NE PAS UTILISER DE FILTRE A AIR AVEC CE FOYER AU  
GAZ A EVACUATION.  
FOR USE WITH GLASS DOOR CERTIFIED WITH THE APPLIANCE ONLY.  
N’UTILISER SEULEMENT QUE LA PORTE DE VERRE CERTIFIE AVEC LAPPAREIL.  
“CAUTION: Do not operate the appliance with glass removed, cracked or broken.  
Replacement of panel should be done by a licensed or qualified service person.”  
“This appliance is equipped at the factory for use with natural gas only. Units using  
propane must be field converted using the LP conversion kit, Cat. No. H1576.  
FINAL INSPECTION BY:  
ANSI Z21.88-2002  
CSA 2.33-2002  
CAN/CGA 2.17-M91  
VENTED GAS FIREPLACE HEATER  
FOYERA AU GAZ CHAUFFANT AVEC EVACUATION  
P/N 9-1467C  
SERIAL NUMBER/NOMBRE DE SERIE  
XXX XXX  
IIIIIIIIIIIIIIIIIIII  
XXX  
P/N 9-1467C  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
NOTE: THIS PAGE LEFT BLANK INTENTIONALLY.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lennox reserves the right to make changes at any time, without notice, in design,  
materials, specifications, prices and also to discontinue colors, styles and products.  
Consult your local distributor for fireplace code information.  
Printed in U.S.A. © Lennox Hearth Products 2003  
P/N 775,156M REV. G 3/2005  
1110 West Taft Avenue • Orange, CA 92865  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Kyocera Digital Camera SL400R User Manual
LA Audio Electronic Stereo Amplifier UB282 User Manual
La Crosse Technology Portable Radio WD 3312 User Manual
Lennox International Inc Air Cleaner 504 User Manual
Liebert Power Supply Nfinity User Manual
Liebherr Refrigerator 7082 135 00 User Manual
Liebherr Refrigerator Freestanding Refrigerator User Manual
Lindy Switch MC5 IP User Manual
Lopi Indoor Fireplace Gas Stove And Fireplace User Manual
Martin Audio Stereo Receiver M3+ User Manual