Johnson Controls Air Conditioner 22 SEER User Manual

INSTALLATION MANUAL  
PREMIUM DUCTLESS SINGLE-SPLIT  
AIR CONDITIONERS AND HEAT PUMPS  
MODELS: 22 SEER  
3/4 to 3 TONS – 1 PHASE  
LIST OF SECTIONS  
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
SHIPPING AND PACKAGING LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
REQUIRED INSTALLATION TOOLS (NOT SUPPLIED) . . . . . . . . . . . . . . . . . .3  
SELECTING THE INSTALLATION LOCATION . . . . . . . . . . . . . . . . . . . . . . . . .3  
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
REFRIGERANT LINE SET REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .6  
UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
TORQUE REQUIREMENTS FOR CAPS AND FASTNERS . . . . . . . . . . . . . . . .9  
INDOOR UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
INDOOR UNIT WIRING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
PIPE FORMING AND DRAIN PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
FLARING WORK AND PIPING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . 12  
INDOOR UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
OUTDOOR UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
OUTDOOR UNIT WIRING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
PURGING PROCEDURE, LEAK TEST AND TEST RUN . . . . . . . . . . . . . . . . 16  
TEST OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
EMERGENCY OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
INSTALLATION AND MAINTENANCE OF  
HEALTHY FILTER (ACCESSORY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
TYPICAL UNIT WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
INDOOR AND OUTDOOR UNITS ERROR CODES . . . . . . . . . . . . . . . . . . . . . 31  
LIST OF FIGURES  
Indoor Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Prevailing Wind Barrier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
Clearances for Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
Condensate Drainage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Typical System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7  
Indoor Unit Mounting Brackets with Weights & Dimensions . . . . . . . . . . . . . . . . .8  
Outdoor Unit Weights & Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
Mounting Bracket Spots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
Masonry Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
PVC Wall Sleeve Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
Indoor Unit Wall Mounting Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
Indoor Electrical Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
Drain Piping Outlets Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
Proper and Improper Drain Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
Left or Right Side Exits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
Right or Right Rear Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
Left or Left Rear Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
Drain Hose Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
Drain Hose Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
Pipe Cutting Approved Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
Deburring Line Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
Flaring Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
Proper and Improper Flaring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
Connections at Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
Flare Nuts Tighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
Indoor Unit Attachment to Mounting Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
Proper and Improper Drain Hose Installation Application . . . . . . . . . . . . . . . . . .13  
Indoor Unit Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
Outdoor Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14  
Outdoor Unit Slab or Frame Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14  
Outdoor Unit Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14  
Outdoor Unit Wiring Terminal Designations . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
Indoor/Outdoor Piping Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
Outdoor Line Set Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
Line Set Connection Insulation and Taping . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
Utility Bundle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
Exterior Wall Utility Cover (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
Service Valve Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Gauge Set Connections for Test Leaks, Evacuation Charging . . . . . . . . . . . . . 17  
Leak Test Line Set Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
Emergency Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
Filter Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
09K & 12K 115V Outdoor Air Conditioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
09K & 12K Outdoor Air Conditioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
18K & 24K 115V Indoor Air Conditioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
18K & 24K Indoor Air Conditioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
18K Outdoor Air Conditioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
18K Indoor Air Conditioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
24K Outdoor Air Conditioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
24K Indoor Air Conditioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
36K Outdoor Air Conditioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
36K Indoor Air Conditioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
09K & 12K 115V Outdoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
09K & 12K Outdoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
18K & 24K 115V Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
18K & 24K Indoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
18K Outdoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
18K Indoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
24K Outdoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
24K Indoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28  
30K Outdoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28  
30K Indoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
36K Outdoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
36K Indoor Heat Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
Indoor Unit Front Panel Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
LIST OF TABLES  
Indoor Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Outdoor Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Air Conditioner Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Heat Pump Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6  
Insulation Thickness & Material Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6  
Refrigerant Line Set Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7  
Indoor Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
Outdoor Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Caps and Fasteners Torque Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Wire Color Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Flare Nut Torque Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Error Codes - 09K 12K . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
Error Codes - 18K 24K . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
Error Codes - 30K 36K . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41  
RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE  
Johnson Controls Unitary Products  
898841-UIM-B-0113  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 1: Indoor Parts  
Flare nut 1/4" for small  
line on all size units  
except 30K which  
uses 5/8".  
Remote Control  
1
2
1
1
Cable routing guide  
with mounting  
hardware (18 - 24 kBtu  
systems only)  
Batteries (AAA)  
Wall mounting bracket  
screws  
09, 12 & 18 kBtu (5)  
24K kBtu (10)  
Installation Manual  
1
1
Foam tube insulation  
(for condensate line  
attached to indoor unit)  
User’s Information  
Manual  
1
2. Select a location where the condensate can be easily drained out.  
ASSEMBLED OUTDOOR UNIT  
The assembled outdoor unit will include the following items which are  
located with the unit:  
3. Install in a location where there is enough space to access the unit  
for routine maintenance (air filter can be removed for cleaning or  
replacement).  
TABLE 2: Outdoor Parts  
4. Install where airflow is not blocked.  
5. Install in a location for optimized cold or warm air distribution.  
6. Install in a location that's not exposed to direct sunlight.  
Auxiliary drain hole plugs  
1 - 3  
(heat pump only)  
7. Install in a location that's at least 3 ft away from a TV and radio to  
avoid possible interferences with the operation of the air condi-  
tioner/heat pump.  
8. Install in a location that's at least 3 feet away from fluorescent and  
incandescent lights to avoid interference with the remote control.  
Drain plug  
(heat pump only)  
1
SECTION IV: REQUIRED INSTALLATION  
TOOLS (NOT SUPPLIED)  
A
1. Gauge manifold  
C
D
2. Electronic balance for refrigerant charging  
3. Phillips head screwdriver  
4. Knife or wire stripper  
5. Carpenters level  
B
6. Hammer  
7. Drill  
8. Tube cutter  
Required  
9. Tube flaring tool  
Reference  
Location  
Clearance  
6 inches  
6 feet  
10. Torque wrench  
A
B
Clearance between unit and ceiling  
Clearance between unit and floor  
11. Adjustable wrench  
12. Reamer (for de-burring)  
13. Vacuum pump (For R410A)  
14. Gas leakage detector  
C / D  
Clearance to the right and left of the unit  
6 inches  
FIGURE 1: Indoor Clearances  
REMOTE CONTROL  
1. Keep the remote control where it is convenient to operate and eas-  
ily visible.  
SECTION V: SELECTING THE  
INSTALLATION LOCATION  
INDOOR UNIT (SEE FIGURE 2 FOR INSTALLATION  
2. Keep the remote control away from children.  
DIMENSIONS)  
1. Install the unit securely in a place that can bear the weight and  
vibration of the unit.  
3. When using the I FEEL feature, select a location for the remote  
control that's about 4 ft. above the floor.  
Johnson Controls Unitary Products  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
NOTICE  
In rooms where inverter type fluorescent lamps are used, the signal  
from the wireless remote controller may not be received.  
INSTALL UNIT AWAY  
FROM WINDOW  
OUTDOOR UNIT (SEE FIGURE 3 FOR  
INSTALLATION DIMENSIONS)  
1. Some localities are adopting sound ordinances based on the unit's  
sound level registered from the adjacent property, not from the  
property where the unit is installed. Install the unit as far as possible  
from the property line.  
E
F
G
2. When possible, do not install the unit directly outside a window.  
Glass has a very high level of sound transmission. For proper  
placement of unit in relation to a window see Figure 3.  
I
3. Install unit level or, if on a slope, maintain slope tolerance of 2  
degrees (or 2 inches per 5 feet) away from building structure.  
4. Install the unit high enough above the ground or roof to allow ade-  
quate drainage of defrost water and prevent ice or snow build-up  
(required for heat pumps).  
H
Required  
Clearance  
Reference  
Location  
Clearance above unit  
5. In heavy snow areas, do not locate the unit where drifting will occur.  
The unit base should be elevated above the depth of average  
snows.  
E
F
G
H
I
2 feet  
Clearance between air inlet and structure  
12 inches  
12 inches  
7 feet  
6. When installed in areas where low ambient temperatures exist,  
locate unit so winter prevailing winds do not blow directly onto out-  
door unit.  
Clearance between unit and structure  
12 inches  
7. If unit coil cannot be installed away from prevailing winter winds, a  
wind barrier should be constructed. Size barrier at least the same  
height and width as outdoor unit. Install barrier 12 inches minimum  
from the sides of the unit in the direction of prevailing winds as illus-  
trated in Figure 2.  
FIGURE 3: Clearances for Outdoor Unit  
NOTICE  
It is advisable to make a piping loop near outdoor unit so as to  
reduce vibration.  
PREVAILING WINTER WINDS  
For increased efficiency, install the outdoor unit in a location where  
continuous direct sunlight or excessive water can be avoided as  
much as possible.  
WIND BARRIER  
INLET AIR  
12” (305MM) MINIMUM DISTANCE  
NOTICE  
When operating the air conditioner in low outside temperature, be  
sure to follow the instructions described below.  
• Never install the outdoor unit in a place where its air inlet/outlet  
side may be exposed directly to wind.  
To prevent exposure to wind, install the outdoor unit with its air inlet  
side facing the wall and a baffle board on the air outlet side.  
DISCHARGE AIR  
FIGURE 2: Prevailing Wind Barrier  
Avoid the following places for installation where air conditioner trouble  
is liable to occur.  
8. Locate unit away from overhanging roof lines which would allow  
water or ice to drop on, or in front of, coil or into unit.  
• Where flammable gas could leak.  
9. Install in a location that has good airflow.  
• Where there is an excessive amount of machine oil in the air.  
• Where sulfide gas is generated such as a hot spring.  
• Where there is high-frequency equipment.  
10. Install in a location that has a rigid wall or support to minimize the  
sound operation and/or vibration.  
11. Slab or roof mounting - install the unit a minimum of 4 inches above  
the roof or ground surface to avoid ice build-up around the unit.  
Locate the unit above a load bearing wall or area of the roof that  
can adequately support the unit. Consult local codes for rooftop  
applications.  
CONDENSATE DRAINAGE REQUIREMENT (HEAT  
PUMP ONLY)  
Condensate formed during the heating and defrost processes must be  
drained from heat pump units. Drain holes are provided in the base of  
the units to ensure proper drainage. Heat pumps must be raised when  
installed on a concrete pad or the ground to allow drainage to occur. If  
the heat pump unit is installed on a wall mounting bracket, insert the  
provided drain connector into one of the 1 inch drain holes and attached  
a field-provided insulated drain hose to the connector. Use the provided  
rubber plugs to cover any unused drain holes. See Figure 4.  
12. Install in a location that's far away from combustible materials and  
vapors.  
13. Install in a location that's at least 10 ft away from a TV and radio  
antennas to avoid possible interferences with the operation of the  
air conditioner/heat pump.  
14. Install the unit horizontally.  
4
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
Solid conductor AWG14 or stranded conductor AWG14 are the MINI-  
MUM allowable wire sizes. There are some applications that will require  
larger gauge conductors depending on the voltage and amperage rat-  
ings on the data plate and the distance that the conductors will be  
routed. It is the installing contractor's responsibility to properly size the  
electrical conductors for the equipment and for the application.  
All of the indoor units and outdoor units should have the electrical con-  
ductors sized using the National Electrical Code (NEC) and the local  
authority having jurisdiction whichever is more stringent. If the equip-  
ment is installed outside of the United States, all local codes within the  
country of origin must be followed.  
DRAIN-WATER HOLE  
BOTTOM FRAME  
DRAIN PLUG  
The Ductless indoor units must have a minimum of 14 gauge, 600  
volt double insulated copper conductors. The conductors for the indoor  
unit can be either solid or stranded copper. When possible the indoor  
unit should have stranded wire for the communication to ensure proper  
communication between the indoor and outdoor unit(s).  
DRAIN CONNECTOR  
HOSE (available commerially, inner dia. 0.63”)  
FIGURE 4: Condensate Drainage  
The Ductless outdoor units must have a minimum of 12 gauge, 600  
volt double insulated copper conductors with the exception of the fol-  
lowing models: DHPM30CSM42Q1, DHPM36CSM42Q1, and  
DCPM36CSM42Q1, which require 10 gauge wire. The conductors for  
the outdoor unit should be solid or stranded copper conductors.  
SECTION VI: SPECIFICATIONS  
POWER SUPPLY AND INDOOR/OUTDOOR WIRE  
CONNECTION  
• The system should be powered from a dedicated circuit.  
• Wiring work should be based on applicable technical standards.  
• Wiring connections should be made following the provided  
diagrams.  
NOTICE  
The listed wire sizes are only minimum requirements, as previously  
stated, the conductors for both indoor and outdoor units must be  
sized using the NEC and local authority having jurisdiction.  
• Make sure all electrical connections are securely tightened.  
TABLE 3: Air Conditioner Electrical Specifications  
INDOOR UNIT  
Air Conditioners  
DCPM09NWM42Q1  
DCPM09NWM41Q1  
DCPM12NWM42Q1  
DCPM12NWM41Q1  
Power Supply (V, Phase, Hz)  
Min. Circuit Ampacity  
Fan Motor (F.L.A)  
208/230V/1  
115V/1  
208/230V/1  
115V/1  
16  
10  
16  
10  
0.2  
0.38  
0.2  
0.38  
INDOOR UNIT  
Air Conditioners  
DCPM18NWM42Q1  
DCPM24NWM42Q1  
DCPM36NWM42Q1  
Power Supply (V, Phase, Hz)  
Min. Circuit Ampacity  
Fan Motor (F.L.A)  
208/230V/1/60HZ  
208/230V/1/60HZ  
208/230V/1/60HZ  
16  
16  
17  
0.28  
0.24  
0.4  
OUTDOOR UNIT  
Air Conditioners  
DCPM09CSM42Q1  
DCPM09CSM41Q1  
DCPM12CSM42Q1  
DCPM12CSM41Q1  
Power Supply (V, Phase, Hz)  
Max. Fuse Size (time delay) (A)  
Min. Circuit Ampacity  
Fan Motor (F.L.A)  
208/230V/1  
15  
115V/1  
208/230V/1  
15  
115V/1  
25  
25  
10  
16  
10  
16  
0.14  
0.17  
0.14  
0.17  
12.43  
33  
R.L.A  
Compressor  
6.21  
12.23  
5.34  
L.R.A  
13.8  
33  
13.8  
OUTDOOR UNIT  
Air Conditioners  
DCPM18CSM42Q1  
DCPM24CSM42Q1  
DCPM36CSM42Q1  
Power Supply (V, Phase, Hz)  
Max. Fuse Size (time delay) (A)  
Min. Circuit Ampacity  
Fan Motor (F.L.A)  
208/230V/1/60HZ  
208/230V/1/60HZ  
208/230V/1/60HZ  
20  
16  
20  
16  
25  
17  
0.32  
9.35  
/
1.1  
10.45  
/
0.45  
12.66  
/
R.L.A  
Compressor  
L.R.A  
Johnson Controls Unitary Products  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 4: Heat Pump Electrical Specifications  
INDOOR UNIT  
DHPM09NWM41Q1  
Heat Pumps  
DHPM09NWM42Q1  
DHPM12NWM42Q1  
DHPM12NWM41Q1  
Power Supply (V, Phase, Hz)  
Min. Circuit Ampacity  
Fan Motor (F.L.A)  
208/230V/1  
115V/1  
16  
208/230V/1  
115V/1  
16  
10  
10  
0.2  
0.38  
0.2  
0.38  
INDOOR UNIT  
Heat Pumps  
DHPM18NWM42Q1  
208/230V/1/60HZ  
16A  
DHPM24NWM42Q1  
208/230V/1/60HZ  
16A  
DHPM30NWM42Q1  
DHPM36NWM42Q1  
Power Supply (V, Phase, Hz)  
Min. Circuit Ampacity  
Fan Motor (F.L.A)  
208/230V/1/60HZ  
208/230V/1/60HZ  
15  
23  
0.28A  
0.24A  
0.4  
0.47  
OUTDOOR UNIT  
Heat Pumps  
DHPM09CSM42Q1  
DHPM09CSM41Q1  
DHPM12CSM42Q1  
DHPM12CSM41Q1  
Power Supply (V, Phase, Hz)  
Max. Fuse Size (time delay) (A)  
Min. Circuit Ampacity  
Fan Motor (F.L.A)  
208/230V/1  
15  
115V/1  
25  
208/230V/1  
15  
115V/1  
25  
10  
16  
10  
16  
0.14  
0.17  
12.23  
33  
0.14  
0.17  
12.43  
33  
R.L.A  
6.21  
5.34  
Compressor  
L.R.A  
13.8  
13.8  
OUTDOOR UNIT  
Heat Pumps  
DHPM18CSM42Q1  
DHPM24CSM42Q1  
DHPM30CSM42Q1  
DHPM36CSM42Q1  
Power Supply (V, Phase, Hz)  
Max. Fuse Size (time delay) (A)  
Min. Circuit Ampacity  
Fan Motor (F.L.A)  
208/230V/1/60HZ  
208/230V/1/60HZ  
208/230V/1/60HZ  
208/230V/1/60HZ  
20A  
16A  
0.32A  
9.35A  
/
20A  
16A  
1.1A  
10.45A  
/
25  
15  
35  
23  
0.45  
11.42  
/
0.73  
16.95  
/
R.L.A  
Compressor  
L.R.A  
To prevent condensation, insulate the two refrigerant pipes.  
• Refrigerant pipe bending radius must be 4 in. (100 mm) or more.  
Connecting Wires and the Ground Wire  
• Use double insulated copper wire with 600V insulation.  
• Use copper conductors only.  
• Follow all local electrical codes.  
Be sure to use the insulation of specified thickness (refer to Table 5).  
Excessive insulation may cause incorrect installation of the indoor  
unit, and too little insulation may cause condensate to form.  
Power Supply Cable and Ground Wire  
• Use copper conductors only.  
• Follow all local electrical codes.  
• The unit has flared connections on both indoor and outdoor sides  
• Remove the valve cover from the outdoor unit then connect the  
pipe  
• Refrigerant pipes are used to connect the indoor and outdoor units  
• Be careful not to crush or over bend the pipe in pipe bending  
• Refrigerant adjustment  
• If pipe length exceeds 25 ft. (7.5 m), additional refrigerant (R410A)  
charge is required (The outdoor unit is charged with refrigerant for  
pipe length up to 25 ft. [7.5 m]).  
NOTICE  
The the indoor unit is powered from the outdoor unit, depending on  
local code, a disconnect switch needs to be installed to a power sup-  
ply circuit.  
SECTION VII: REFRIGERANT LINE SET  
REQUIREMENTS  
TABLE 5: Insulation Thickness & Material Information  
Outside Diameter  
Minimum Wall  
Thickness  
Insulation  
Thickness  
Insulation  
Material  
Pipe  
Inch (mm)  
.375 (9.52)  
.625 (15.9)  
Liquid Line  
Gas Line  
0.0315 (0.8)  
0.0394 (1.0)  
0.315 (8)  
0.315 (8)  
Heat Resistant Foam Plastic  
0.045 Specific Gravity  
6
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 6: Refrigerant Line Set Requirements  
AC & HP Indoor Units  
AC & HP Outdoor Units  
Connection Pipe length  
D(C,H)PM09NWM D(C,H)PM12NWM D(C,H)PM18NWM D(C,H)PM24NWM DHPM30NWM D(C,H)PM36NWM  
D(C,H)PM09CSM D(C,H)PM12CSM D(C,H)PM18CSM D(C,H)PM24CSM DHPM30CSM D(C,H)PM36CSM  
ft.  
24.6  
24.6  
24.6  
24.6  
24.6  
24.6  
Connection Pipe Gas  
Additional Charge  
oz/ft.  
0.2  
0.2  
0.2  
0.2  
0.5  
0.5  
Outer Diameter Liquid Pipe Inch  
1/4  
3/8  
1/4  
3/8  
1/4  
1/2  
1/4  
1/2  
1/4  
5/8  
1/4  
5/8  
Outer Diameter Gas Pipe  
Max Distance Height  
Max Distance Length  
Inch  
ft.  
32.8  
49.2  
32.8  
49.2  
32.8  
82  
32.8  
82  
32.8  
98.4  
32.8  
98.4  
ft.  
Refrigerant Metering Device Type  
Electronic Expansion Valve  
E
G
RETURN AIR  
K
B
L
INDOOR UNIT  
TAPE  
H
REFRIGERANT LINE SET, CONDENSATE LINE  
AND INDOOR / OUTDOOR CABLE  
D
DISPLAY  
D
F
INDICATORS  
IMPORTANT:  
C
SUPPLY AIR  
The refrigerant metering device for this  
system is located in the outdoor unit.  
This makes it necessary to insulate the  
refrigerant lines individually to prevent  
sweating.  
COOL  
DRY  
UTILITY  
BUNDLE  
A
FAN  
HEAT  
WIRELESS REMOTE  
CONTROL  
OUTDOOR UNIT  
RUN  
TERMINAL BLOCK  
TEMPERATURE SETTING  
INDOOR AMBIENT TEMPERATURE  
OR ERROR CODE  
OUTDOOR UNIT  
(AIR CONDITIONER  
OR HEAT PUMP)  
NOTE:  
AIR IN  
Temperature can be  
displayed in either fahrenheit or celsius.  
TO POWER  
TO INDOOR  
SUPPLY  
J
UNIT  
A. Remote control  
B. Front Panel  
C. Filters  
D. Guide louver with display  
E. Line set (wrapped in foam insulation)  
F. UV-rated tape (field-provided)  
G. Wiring (field-provided)  
H. Condensate drain line (field-provided)  
H
(wrapped in foam insulation). Recommend  
installation of a vent when making long  
horizontal runs on condensate line.  
2-way suction / vapor line service valve  
and 2-way shut-off valve.  
I
AIR OUT  
ACCESS COVER FOR  
SERVICE VALVES  
I.  
(-18, -24 AND -30 ONLY)  
J. Access cover for power and control wiring  
connections.  
K. Indoor unit wiring connections (under access plate).  
L. Communication cable (30 kBtu system only)  
2-WAY SHUT-OFF VAVLE  
2-WAY SUCTION / VAPOR LINE SERVICE  
VALVE (FLARE CONNECTION)  
FIGURE 5: Typical System Components  
Johnson Controls Unitary Products  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
SECTION VIII: UNIT DIMENSIONS  
A
B
C
09K 12K  
27.3 (693)  
21.3 (541)  
18K  
2.1 (53)  
7.8 (198)  
2.2 (56)  
2.2 (56)  
2 (51)  
5.3  
(135)  
10.9 (277)  
11.8 (300)  
2.2 (56)  
2.2 (56)  
1.8 (46)  
2 (51)  
.6 (15)  
.6 (15)  
4 (101)  
5 (127)  
6.3  
(160)  
4.9  
(124)  
22.2 (564)  
33.3 (846)  
3.3 (84)  
40.1 (1018)  
24K  
7.4  
30K & 36K  
27 (686)  
(188)  
1 (25)  
2.6 (66)  
2.6 (66)  
2.6 (66)  
2.6 (66)  
1 (25)  
1.8 (46)  
4
22.6 (574)  
4
2.5 (64)  
(102)  
3.5 (89)  
1.4 (36)  
(102)  
FIGURE 6: Indoor Unit Mounting Brackets with Weights & Dimensions  
TABLE 7: Indoor Unit Dimensions  
Unit Gross Weight  
Model Size  
A
B
C
Air Conditioner  
31 lbs (14 kg)  
31 lbs (14 kg)  
46 lbs (21 kg)  
NA  
Heat Pump  
09K & 12K  
18K  
33 (838)  
37 (940)  
7 (178)  
8 (203)  
10.9 (277)  
12 (305)  
37 lbs (17 kg)  
46 lbs (21 kg)  
56 lbs (25 kg)  
60 lbs (27 kg)  
24K  
39.8 (1011)  
53 (1346)  
8.5 (216)  
10 (254)  
12.4 (315)  
12.9 (328)  
30K & 36KK  
B
A
C
FIGURE 7: Outdoor Unit Weights & Dimensions  
TABLE 8: Outdoor Unit Dimensions  
Unit Gross Weight  
Model Size  
A
B
C
Air Conditioner  
91 lbs (41 kg)  
97 lbs (44 kg)  
121 lbs (55 kg)  
132 lbs (60 kg)  
NA  
Heat Pump  
110 lbs (50 kg)  
119 lbs (54 kg)  
148 lbs (67 kg)  
161 lbs (73 kg)  
163 lbs (74 kg)  
09K  
12K  
33 (838)  
33 (838)  
35 (889)  
38 (965)  
38 (965)  
12.6 (320)  
21 (533)  
21 (533)  
12.6 (320)  
13.4 (340)  
16.9 (429)  
16.9 (429)  
18K  
27.5 (699)  
31.1 (790)  
31.1 (790)  
24K  
30K & 36K  
8
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
SECTION IX: TORQUE REQUIREMENTS  
FOR CAPS AND FASTNERS  
LEVELING DEVICE  
Mark on the middle of it  
WALL  
WALL  
Space  
Space  
to the  
wall  
to the  
When servicing or repairing HVAC components, ensure the fasteners  
are appropriately tightened. The table below provides torque values for  
fasteners.  
wall  
5.9inch  
above  
5.9inch  
above  
TABLE 9: Caps and Fasteners Torque Requirements  
Recommended Torque  
Parts  
Left  
Right  
(REAR PIPING HOLE)  
(REAR PIPING HOLE)  
English  
(ft. - lb.)  
Metric  
(Newton Meter)  
FIGURE 8: Mounting Bracket Spots  
Service valve cap  
Sheet metal screws  
Machine screws #10  
Compressor bolts  
Gauge port seal cap  
8 ft. - lb.  
16 ft. - lb.  
27 ft. - lb.  
7 ft. - lb.  
8 ft. - lb.  
11  
2
DRILL PILOT HOLES  
3
10  
11  
USE ANCHORS  
Only use Allen wrenches of sufficient hardness (50Rc - Rockwell  
Harness Scale minimum). Fully insert the wrench into the valve stem  
recess.  
INSTALL ANCHORS  
Service valve stems are factory-torqued (from 9 ft-lbs for small  
valves, to 25 ft-lbs for large valves) to prevent refrigerant loss during  
shipping and handling. Using an Allen wrench rated at less than  
50Rc risks rounding or breaking off the wrench, or stripping the valve  
stem recess.  
FIGURE 9: Masonry Applications  
WALL HOLE DRILLING  
Be sure to caulk the gaps around the pipes with caulking material to  
prevent water leakage.  
1. Determine the wall hole position.  
SECTION X: INDOOR UNIT INSTALLATION  
INSTALLING THE WALL MOUNTING BRACKET  
Determine that the wall will support the weight of the indoor unit. Refer  
to system specifications for indoor unit weight. Install the wall mounting  
bracket and make sure it's positioned horizontally and vertically. The  
indoor unit must be installed level on the wall to allow proper conden-  
sate drainage.  
2. Drill a 2-1/2 inch diameter hole in the wall. The hole should be  
slightly downward slant 3/16" to 3/8" (5 to 10 mm) lower than the  
indoor side.  
3. Measure the thickness of the wall from inside to outside edges and  
cut field-provided PVC pipe at a slight angle 1/4" (6mm) shorter  
than the thickness of the wall.  
4. Place a field-provided plastic cover on the outside end of the PVC  
pipe and insert the pipe in the wall hole.  
1. Determine the best exit location for utility bundle (line set, conden-  
sate line and wiring).  
5. After completing refrigerant piping, wiring, and drain piping, caulk  
pipe hole gap with putty.  
2. Use the wall mounting bracket as a template to determine the exit  
point for utility bundle. Use a carpenter's level or tape measure to  
verify the wall mounting bracket is horizontally level and mark the  
boring points on the wall. See Figure 11.  
OUTSIDE  
INSIDE  
CAULKING  
3. Prior to making the hole and installing wall sleeve for the utility bun-  
dle, check to ensure that neither studs nor plumbing are directly  
located behind the hole location.  
4. Secure the wall mounting bracket to the wall using the provided  
screws. If possible, align the rear panel screw holes with wall stud  
locations marked on the wall. Make sure you use as many screws  
into studs as possible. All other screws must be secured using plas-  
tic wall anchors. See Figure 13.  
2.2”  
WALL PIPE  
5. If the wall is made of brick, concrete or other similar material, then  
drill pilot holes in the wall. Insert field-provided anchors for mount-  
ing screws. See Figure 13.  
FIGURE 10: PVC Wall Sleeve Installation  
SECTION XI: INDOOR UNIT WIRING  
CONNECTIONS  
NOTICE  
It is important to use all screws provided to secure the wall mounting  
bracket to the wall. Additional holes may be drilled through the metal  
wall mounting bracket to better secure wall bracket to wall studs.  
NOTICE  
When the indoor unit is powered from the outdoor unit, a dis-  
connect switch needs to be installed to power supply circuit  
between indoor and outdoor units depending on local codes.  
Johnson Controls Unitary Products  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TERMINAL BLOCK  
Mis-wiring could damage unit or cause communication errors  
between indoor and outdoor unit.  
GROUND  
WIRE  
TERMINAL COVER  
SCREW  
1. Remove the front panel.  
2. Open the front panel upward and pull it toward you.  
3. Remove the terminal cover and cord clamp.  
SCREW  
4. Insert the connecting cable (according to local codes) into the pipe  
hole on the wall.See Figure 11.  
CORD CLAMP  
CONNECTING CABLE  
5. Pull the connecting cable through the cable slot on the rear case so  
that it protrudes about 6 inches (~15 cm) out of the front.  
6. Connect the ground wire to the ground terminal of electrical box.  
7. Insert the connecting cable fully into the terminal block and secure it  
with screws while making sure no part of its core is visible. Make  
sure you don't mis-wire the unit. See Figure 12.  
8. Firmly tighten the terminal screws to prevent them from getting  
loose.  
TERMINAL BLOCK  
9. Secure the connecting cable with the cord clamp.  
10. Attach the terminal cover and front panel on the indoor unit.  
BROWN  
BLACK  
TABLE 10: Wire Color Reference  
YELLOW-GREEN  
Color Code or  
Color Code  
Color  
Color  
BLUE  
Symbol  
CONNECTING  
CABLE  
WH  
YE  
White  
Yellow  
BN  
Brown  
Blue  
2.8”  
0.39”  
BU  
GROUND  
LINE  
RD  
Red  
BK  
Black  
YEGN  
Yellow Green  
ABOUT 5.9”  
WALL  
0.39”  
1.97”  
FIGURE 12: Indoor Electrical Wiring Connections  
SECTION XII: PIPE FORMING AND DRAIN  
PIPING  
RIGHT  
REAR RIGHT  
LEFT  
RIGHT DOWNWARD REAR LEFT  
WIRING  
LEFT DOWWARD  
FIELD PROVIDED  
PVC WALL SLEEVE  
FIGURE 13: Drain Piping Outlets Option  
PIPE FORMING  
FIGURE 11: Indoor Unit Wall Mounting Bracket  
Interchange the drain cap and the drain hose.  
1. Place the drain hose below the refrigerant piping.  
2. Make sure the drain hose is not bent or kinked.  
3. Do not pull the hose when applying the tape.  
Be sure to refer to the wiring system diagram labeled inside the front  
panel.  
Check local electrical regulations for any specific wiring instructions  
or limitations.  
4. When the drain hose passes the room, be sure to wrap field-pro-  
vided insulation material around it.  
5. In the case of bending refrigerant piping, keep the following precau-  
tions in mind to avoid abnormal sounds that may be generated if  
improper work is conducted.  
a. Do not press the refrigerant pipes onto the bottom frame.  
b. Do not press the refrigerant pipes on the front grille.  
10  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
LEFT OR LEFT REAR PIPING  
For Left Side Utility Bundle Exit - Cut out the corner of the right/left  
plastic cabinet with a hacksaw or similar tool.  
Make sure you reattach the drain hose and the drain cap in case of left  
or left rear piping. Otherwise, it could cause drops of water to drip from  
the drain hose.  
1. Put the refrigerant piping and the drain hose together then firmly  
apply felt tape from the end.  
2. Pull out the drain cap at the rear right of the indoor unit.  
3. Pull out the drain hose at the rear left of the indoor unit.  
4. Put the drain cap into the section to which the drain hose is to be  
attached at the rear of the indoor unit.  
5. Insert the drain hose fully into the drain pan at the rear right of the  
indoor unit.  
FIGURE 14: Proper and Improper Drain Piping  
RIGHT OR RIGHT REAR PIPING  
For Right Side Utility Bundle Exit - Cut out the corner of the right/left  
6. Insert the drain hose into field-provided PVC sleeve and hook the  
upper part of the indoor unit on the wall mounting bracket.  
plastic cabinet with a hacksaw or similar tool. See Figure 15.  
FOR LEFT OUTLET  
PIPING, CUT OFF  
THE PIPING OUTLET  
CUTTING GROOVE  
WITH A HACKSAW  
1. Put the refrigerant piping and the drain hose together. Position  
them to the left side and then firmly apply piping tape from the end.  
2. Insert the drain hose into field-provided PVC sleeve and hook the  
upper part of the indoor unit on the wall mounting bracket.  
3. Check if the indoor unit is hooked securely on the wall mounting  
bracket by trying to move the unit left and right.  
4. Thrust the lower part of the indoor unit into the wall mounting  
bracket.  
REMOVE DRAIN  
CAP BY PULLING  
DRAIN CAP  
AT THE PROJECTION  
AT THE END OF THE  
CAP WITH PLIERS, ETC.  
INDOOR UNIT  
DRAIN HOSE  
FIGURE 17: Left or Left Rear Piping  
REAR OR DOWNWARD PIPING  
1. Put the refrigerant piping and the drain hose together then firmly  
apply felt tape from the end. Use bandage stopper at the end of felt  
tape.  
SLIT  
FIGURE 15: Left or Right Side Exits  
2. Insert the drain hose into field-provided PVC sleeve and hook the  
upper part of the indoor unit on the wall mounting bracket.  
How to replace the drain plug and drain hose  
How to remove the drain cap  
Clamp drain cap with needle-nose pliers, and pull out.  
BIND WITH VINYL TAPE  
RIGHT  
• How to remove the drain hose  
Insulation  
The drain hose is secured in place by a screw.  
fixing screw  
PIPING  
Remove the screw securing the drain hose, then  
PIPE (TOP) REAR PIPING  
pull out the drain hose.  
Drain Hose  
INDOOR UNIT  
DRAIN HOSE (BOTTOM)  
BOTTOM  
PIPING  
• How to attach the drain cap  
1. Insert hexagonal wrench (0.16inch).  
0.16”  
FIGURE 16: Right or Right Rear Piping  
No gap  
Do not apply lubricating oil  
(refrigerant machine oil) when  
2. Firmly insert drain cap.  
inserting the drain cap. If applied  
deterioration and leakage of the  
drain plug may occur.  
Insert a hexagon wrench  
(4 mm)  
• How to attach the drain hose  
secure it in place using the original screw.  
Johnson Controls Unitary Products  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
SECTION XIII: FLARING WORK AND  
PIPING CONNECTIONS  
FLARING WORK  
Main cause for refrigerant leakage is due to defect in the flaring work.  
Carry out correct flaring work using the following procedure.  
1. In order to align the drain hose and drain cap, be sure to insert  
securely and vertically. Incline insertion will cause water leak-  
age.  
2. After removing drain hose, be sure not to forget mounting drain  
1. Measure the distance between the indoor and outdoor units.  
cap.  
2. Cut the copper pipe about 6 to 8 inches (15 to 20 cm) longer than  
the measured distance with a pipe cutter.  
3. Be sure to fix the drain hose with tape to the bottom of piping.  
4. Prevent drain water from freezing in low temperature environ-  
ment.  
When installing indoor unit’s drain hose outdoors, necessary mea-  
sure for frost protection should be taken to prevent drain water  
freezing.  
COPPER  
PIPE  
SLANTED UNEVEN ROUGH  
90°  
• Under low temperature environment (when outdoor tempera-  
ture under 32 °F), after cooling operation is executed, water in  
the drain hose could be frozen.  
• Once drain water is frozen, the drain hose will be blocked and  
water leakage may result from indoor unit.  
FIGURE 20: Pipe Cutting Approved Method  
DRAIN PIPING  
3. Use a pipe reamer or file to completely remove all burrs from the  
cut cross section of the pipe.  
• If the extension drain hose has to pass through a room, make  
sure it's wrapped with commercially sold insulation.  
a. Put the end of the copper pipe in a downward direction to avoid  
having burrs drop in the piping.  
• The drain hose should point downward for easy drain flow.  
• If the drain hose provided with the indoor unit is too short, make  
sure you connect it with a field-provided drain hose.  
• When connecting the drain hose to the hard vinyl chloride pipe,  
make sure it's inserted securely into the pipe.  
PIPE  
REAMER  
POINT DOWN  
DRAIN HOSE JUNCTION  
• If drain hose extension or embedded drain piping is required, use  
appropriate parts that match the hose front end. See Figure 18.  
• Insert drain hose into the handle of drain pan, and join drain hose  
and connecting hose according to Figure 18.  
• Attach the Insulation (Drain hose) to the drain hose. See Figure  
19.  
FIGURE 21: Deburring Line Set  
4. Remove flare nuts attached to indoor and outdoor units then put  
them on pipes that have completed burrs removal (not possible to  
put them on after flaring work).  
SHIELD PIPE  
5. Use a flaring tool to perform flaring work at the end of the copper  
pipe. Use the table below as a guideline when performing flaring  
work.  
EXTENSION  
Outside Dia.  
Inch  
A
HANDLE  
DRAIN HOSE  
INSIDE THE ROOM  
Inch  
DRAIN HOSE  
BAR  
BAR  
0.24  
0~0.02  
0~0.02  
0~0.02  
0~0.04  
0.04~0.05  
YOKE  
0.37  
FIGURE 18: Drain Hose Extension  
0.47  
CONE  
0.63  
0.75  
COPPER PIPE  
CLAMP HANDLE  
FIGURE 22: Flaring Tools  
RED ARROW MARK  
INSULATION (DRAIN HOSE)  
6. Check your flaring work and if it's found to be defective, cut off the  
defective flare section and redo number 5.  
DRAIN HOSE  
FIGURE 19: Drain Hose Insulation  
SMOOTH ALL ROUND  
INSIDE IS SHINY WITHOUT SCRATCHES  
= IMPROPER FLARING =  
Insert the drain hose and drain cap into the drain port, making sure  
that it comes in contact with the back of the drain port, and then  
mount it. If the drain hose is not connected properly, leaking will  
occur.  
UNEVEN  
SURFACE  
CRACKED  
INCLINED  
THICKNESS  
DAMAGED  
EVEN LENGTH  
ALL ROUND  
FIGURE 23: Proper and Improper Flaring  
7. When flaring is complete, align the center of the pipes and suffi-  
ciently tighten the flare nut by hand.  
12  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
5. Carefully bend the bundle (line set, condensate line and cable) to  
run along the outside wall toward the outdoor unit. Downward slope  
of wall sleeve will ensure proper condensate drainage.  
DO NOT FORM THE DRAIN HOSE  
INTO THE WAVED SHAPE  
DO NOT RISE THE DRAIN HOSE  
50 mm  
INDOOR UNIT TUBING  
FLARE NUT  
PIPES  
OR MORE  
FIGURE 24: Connections at Indoor Unit  
8. Tighten the flare nut using a wrench.  
DO NOT PUT THE DRAIN  
HOSE END IN THE  
DO NOT PUT THE  
DRAIN HOSE END  
INTO WATER  
DRAINAGE CONTAINER  
OPEN-END WRENCH (FIXED)  
FIGURE 27: Proper and Improper Drain Hose Installation Application  
FLARE NUT  
Pull the indoor unit toward you to confirm that it is firmly hooked  
on the mounting bracket.  
CONNECTION PIPE  
WRENCH  
For detaching the indoor unit from the installation plate, pull the indoor  
unit toward you while pushing the bottom up at the specified places.  
INDOOR UNIT TUBING  
FIGURE 25: Flare Nuts Tighting  
TABLE 11: Flare Nut Torque Recommendations  
Outside  
Diameter  
Recommended  
Torque  
English  
(ft. - lb.)  
Metric  
(Newton Meter)  
Inches  
mm  
PUSH  
PUSH  
1/4”  
3/8”  
1/2”  
5/8”  
6.35  
9.52  
15 ft - lb.  
26 ft - lb.  
41 ft - lb.  
48 ft - lb.  
20  
35  
55  
65  
FIGURE 28: Indoor Unit Removal  
12.70  
15.88  
6. Use the provided foam insulation to wrap the factory installed con-  
densate line.  
7. Connect indoor unit factory installed condensate line to field-pro-  
vided condensate drain pipe.  
SECTION XIV: INDOOR UNIT  
INSTALLATION  
8. Use tape approved for waterproofing line connections to secure the  
field-provided pipe to the factory-installed condensate line.  
1. Shape the refrigerant line set so that it can be guided either out the  
back of the indoor unit or through either side of the indoor unit  
frame, then through the wall sleeve to the outside unit.  
9. Put water in the drain pan and make sure that the water is being  
drained outside.  
2. Pass the drain hose and refrigerant pipes through the wall hole then  
set the indoor unit on the mounting bracket hooks by using the  
markings at the top of the indoor unit as a guide.  
Install the drain pipe for proper drainage. Improper drainage can  
result in water dripping inside the room.  
A
MOUNTING PLATE  
SECTION XV: OUTDOOR UNIT  
INSTALLATION  
MARKING  
Refer to page 4 instructions when considering unit positioning and page  
4 for condensate drainage requirements (heat pump).  
SLAB OR ROOF MOUNTING  
• Install the unit a minimum of 4 inches (102 mm) above the roof or  
ground surface to avoid ice build-up around the unit.  
• Locate the unit above a load bearing wall or area of the roof that  
can adequately support the unit.  
FIGURE 26: Indoor Unit Attachment to Mounting Bracket  
3. Try moving the indoor unit to right and left to confirm that it is firmly  
hooked on the installation plate.  
4. While pressing the indoor unit onto the wall, hook it at the lower part  
on the installation plate.  
• Consult local codes for rooftop applications.  
Johnson Controls Unitary Products  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
BUILDING STRUCTURE  
Mis-wiring could damage unit or cause communication errors  
between indoor and outdoor unit.  
NOTICE  
• Refer to unit nameplate for minimum circuit ampacity and maxi-  
mum overcurrent protection size  
• Local codes may require a disconnect between the indoor and out-  
door units  
GROUND  
LEVEL  
• The main system circuit breaker and outdoor unit disconnect  
switch should be sized per local codes and unit requirements  
• Stranded wire must be used to connect the outdoor unit to the  
indoor unit. The stranded wire is necessary to ensure proper sys-  
tem communication and operation.  
Install unit level or maintain slope tolerance of 2 degrees  
( or 2 inches per 5 feet [50 mm per 1.5 m] away from building structure.  
FIGURE 29: Outdoor Unit Installation  
• Make sure you use an approved circuit breaker or switch  
Model  
Fuse or Circuit Breaker Capacity  
NOTICE  
9K & 12K  
18K & 24k  
30K & 36k  
20A  
25A  
30A  
This system contains both refrigerant and oil. Some rubber roofing  
material may absorb oil. This will cause the rubber to swell when it  
comes into contact with oil. The rubber will then bubble and could  
cause leaks. Protect the roof surface to avoid exposure to refrigerant  
and oil during service and installation. Failure to follow this notice  
could result in damage to roof surface.  
1. Remove outdoor unit access panel.  
2. Route all wiring to outdoor unit through the wire routing plate.  
SECURING OUTDOOR UNIT TO SLAB OR FRAME  
If the outdoor unit is installed on a field-provided slab or frame, use lag  
bolts or equivalent to secure the outdoor unit to the slab or frame.  
ROUTE WIRES  
THROUGH  
ROUTING  
ACCESS PLATE  
PLATE  
FIGURE 31: Outdoor Unit Electrical Connections  
FOUR FIELD PROVIDED ANCHOR BOLTS  
3. Connect the control wiring and power supply wiring to the outdoor  
unit wiring terminals according to the figures shown in this section.  
FIGURE 30: Outdoor Unit Slab or Frame Installation  
4. The unit must be grounded according to local codes.  
5. Fasten the power supply cord and control wiring with cord clamp.  
6. Secure wiring using built-in wire strain relief.  
SECTION XVI: OUTDOOR UNIT WIRING  
CONNECTIONS  
7. Install the outdoor unit access panel back.  
In the United States, wiring must conform with current local codes  
and the current National Electric Code (NEC). In Canada, wiring  
must conform with current local codes and the current Canadian  
Electrical Code (CEC).  
The main system circuit breaker or disconnect should be sized per  
unit requirements and should be installed adjacent to outdoor unit.  
14  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
30 & 36 KBTU (208-230V)  
208-230V SYSTEMS  
115V SYSTEMS  
INDOOR UNIT TERMINALS  
SYSTEM ONLY  
INDOOR UNIT TERMINALS  
INDOOR UNIT TERMINALS  
2
N(1)  
N(1)  
2
N(1)  
2
3
3
3
(GND)  
(GND)  
(GND)  
(DATA)  
(DATA)  
(NEUTRAL) (DATA)  
(NEUTRAL)  
(NEUTRAL)  
L2  
N(1)  
L1  
L1 L2  
2
3
L1  
N
N(1)  
N(1)  
2
3
2
3
(L1)  
(L1)  
(GND)  
(GND)  
(GND)  
(L1)  
(L2)  
(NEUTRAL)  
(L2)  
OUTDOOR UNIT  
TERMINALS  
OUTDOOR UNIT  
TERMINALS  
OUTDOOR UNIT  
TERMINALS  
FIGURE 32: Outdoor Unit Wiring Terminal Designations  
REFRIGERANT PIPING CONNECTIONS  
A Service port cap protects the service port core from contamination  
and serves as the primary leak seal. To access service port:.  
A
1. Remove service port cap with an appropriate sized wrench.  
2. Connect gauge set to service port.  
APPLY REFRIGERANT  
LUBRICANT HERE  
3. When testing is complete, replace service port cap and tighten as  
follows:  
MALE FLARE  
CONNECTION  
B
a. With torque wrench - Finger tighten then torque cap per Table 11  
requirements.  
b. Without torque wrench - Finger tighten then use appropriate  
sized wrench to turn an additional 1/6 turn clockwise.  
Stem cap protects the valve stem from damage and serves as the pri-  
mary seal. Replace the stem cap and tighten as follow:  
FIGURE 33: Indoor/Outdoor Piping Connections  
1. With torque wrench - Finger tighten and use torque cap per Table  
11.  
OUTDOOR UNIT CONNECTION  
• Apply a sealing cap or water proof tape to prevent dust or water  
from getting into the refrigerant piping before it is connected.  
• Apply refrigerant lubricant to the matching surfaces of the flared  
line set and union before connecting them together. This will  
reduce refrigerant leaks.  
• Align the flared refrigerant line with valve connection then tighten  
the flare nut lightly at first to obtain a smooth match. Use tighten-  
ing toque Table 11 as a guideline.  
2. Without torque wrench - Finger tighten then use an appropriate  
sized wrench to turn an additional 1/12 turn clockwise.  
NOTICE  
• Fasten flare nut with a torque wrench as specified in Table 9.  
• When fastened too tight, flare nut may break after a long period  
and cause refrigerant to leak.  
OUTDOOR UNIT  
INDOOR UNIT CONNECTION  
LIQUID SIDE PIPING  
(SMALLER DIAMETER)  
• Connect both liquid and gas pipes to indoor unit.  
• Apply a sealing cap or water-proof tape to prevent dust or water  
from getting into the refrigerant piping before it is connected.  
• Apply a thin coat of refrigerant oil on the seal surface of the pipe.  
• For connection, first align the union tube and flared refrigerant  
line with each other then tighten the flare nuts lightly at first to  
obtain a smooth match.  
TORQUE WRENCH  
GAS SIDE PIPING  
• Use tightening toque Table 11 as a guideline for indoor unit side  
union joint section and tighten using two wrenches. Excessive  
tightening may damage the flare section.  
(BIGGER DIAMETER)  
FIGURE 34: Outdoor Line Set Connections  
Johnson Controls Unitary Products  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
INSULATION AND TAPING  
1. Cover piping joints with pipe cover.  
FIELD PROVIDED PROTECTIVE  
CHANNEL (UTILITY BUNDLE INSIDE)  
2. For outdoor unit, insulate every pipe including all pipe joints.  
3. Using piping tape, apply taping starting from entry of outdoor unit.  
a. Stop the end of piping tape with tape that has an adhesive agent  
attached.  
b. When pipes have to be arranged through above ceiling, closet or  
where temperature and humidity are high, make sure you wind  
additional commercially sold insulation to prevent sweating.  
4. An optional field-provided exterior wall channel may be used in lieu  
of taping the utility bundle to protect the bundle from UV rays,  
weather, etc. See Figure 37.  
PLASTIC BANDS  
INSULATION MATERIAL  
FIGURE 35: Line Set Connection Insulation and Taping  
INDOOR  
CONNECTION  
FIGURE 37: Exterior Wall Utility Cover (Optional)  
UNIT PIPE  
PIPE  
SECTION XVII: PURGING PROCEDURE,  
LEAK TEST AND TEST RUN  
WRAP WITH VINYL TAPE  
VINYL TAPE  
(WIDE)  
WRAP WITH VINYL TAPE  
SERVICE VALVES  
The outdoor unit suction/vapor 2-way service valve is used to purge air,  
test for leaks, check operating pressures and add refrigerant to system.  
This valve is equipped with a service port which has a factory installed  
valve core. Figure below provides information on how to access and  
operate the 2-way angle-type service valve and 2-way shut-off valve.  
PIPE  
VINYL TAPE (WIDE)  
After the piping has been connected to the indoor unit, perform the air  
purge.  
DRAIN HOSE  
INDOOR UNIT  
AUXILIARY PIPES  
CONNECTING  
CABLE  
INSTALLATION  
PLATE  
FIGURE 36: Utility Bundle  
16  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
Shut-off  
2-way Valve  
Suction/Vapor  
2-way Service Valve  
SUCTION/VAPOR  
2-WAY SERVICE VALVE  
Action  
HOSE WITH  
SCHRADER VALVE  
CLOSED  
PUSH  
Evacuating with a  
vacuum pump  
REQUIRES FIELD PROVIDED 5/16” FEMALE  
FLARE TO 1/4” MALE FLAREADAPTER.  
VALVE CAP  
OPEN POSITION  
FLARE CAP  
CLOSED POSITION  
FULLY  
OPEN  
SCHRADER CORE  
TO LINE SET  
SERVICE  
PORT  
SERVICE  
PORT CAP  
Outdoor unit running  
TO OUTDOOR UNIT  
FLARE CAP  
FULLY  
OPEN  
ALLEN WRENCH (5MM)  
OPEN POSITION  
Checking pressure  
CLOSED POISTION  
TO LINE SET  
and adding refrigerant  
TO OUTDOOR UNIT  
FIGURE 38: Service Valve Operation  
LEAK TEST AND EVACUATION  
Air and moisture remaining in the refrigerant system will have undesir-  
able effects as indicated below:  
COMPOUND  
PRESSURE  
GAUGE  
PRESSURE GAUGE  
MANIFOLD VALVE  
-101kPa  
1. Pressure in the system rises.  
2. Operating current rises.  
(-76cmHg)  
HANDLE HIGH  
(KEEP FULL  
CLOSED)  
HANDLE LOW  
3. Cooling or heating efficiency drops.  
CHARGE HOSE  
4. Moisture in the refrigerant circuit may freeze and block capillary  
tubing (30 kBtu size only).  
CHARGE HOSE  
CONNECTING  
PIPE  
VACUUM PUMP  
ADAPTER FOR  
COUNTER-FLOW  
PREVENTION  
5. Water may lead to corrosion of parts in the refrigeration system.  
The line set between the indoor and outdoor units must be leak tested  
and evacuated to remove any non-condensable and moisture from the  
system.  
PACKED VALVE  
AT LIQUID SIDE  
VACUUM  
PUMP  
AIR PURGING WITH VACCUM PUMP  
Be sure to use a vacuum pump with counter-flow prevention function to  
make oil inside the pump does not flow back into the system pipes  
when the pump stops.  
PACKED VALVE AT GAS SIDE  
SERVICE PORT  
1. Run the vacuum pump.  
SCHRADER CORE  
2. Connect the charge hose from the manifold valve to the service port  
of the gas side packed valve.  
FIGURE 39: Gauge Set Connections for Test Leaks, Evacuation  
Charging  
3. Connect the charge hose to the port of the vacuum pump.  
ADDING REFRIGERANT FOR LONGER LINE SET  
1. Open the low side manifold gauge valve and weigh in liquid refriger-  
ant. Use Table 6 to calculate the correct weigh-in charge.  
4. Open fully the low pressure side handle of the gauge manifold  
valve.  
5. Operate the vacuum pump to begin evacuating.  
2. Close manifold gauge valves.  
6. The operation time for evacuation varies with the lineset length and  
capacity of the pump. Allow the pumpto operate until the system  
has been evacuated downto 300 microns. Allow the pump to con-  
tinue running foran additional 15 minutes.  
LEAK TEST  
Use the following procedure to test for system leaks:  
1. Connect the manifold gauge set and dry nitrogen gas cylinder to the  
suction/vapor service port. See Figure 30.  
7. Turn off the pump and leave the connection secured to the suction/  
vapor 2-way service port. After five minutes, if the system fails to  
hold 500 microns or less, check all connections for tight fit and  
repeat the evacuation procedure.  
2. Open valve on nitrogen cylinder.  
3. Pressurize the system to no more than 150 PSIG with dry nitrogen.  
4. Check for leaks using soapy water.  
8. Close the low pressure valve handle of gauge manifold.  
5. After the system is found to be free of leaks:  
9. Open fully the valve stem of the packed valves (both gas and liquid  
sides).  
• Close valve on nitrogen cylinder  
• Relieve the nitrogen pressure by: loosening the charge hose con-  
nector at the nitrogen cylinder.  
• When the system pressure is reduced to normal, disconnect the  
hose from the cylinder.  
10. Remove the charging hose from the service port.  
11. Securely tighten the caps on the packed valves.  
Johnson Controls Unitary Products  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
CHECK PLACES FOR  
FLARE NUT CONNECTIONS  
(INDOOR UNIT)  
CHECK PLACES  
AUTO/STOP  
FOR OUTDOOR UNIT  
MANUAL SWITCH  
FIGURE 40: Leak Test Line Set Connection  
AUTO  
TEST  
SECTION XVIII: TEST OPERATION  
1. Check that all tubing and wiring have been properly connected.  
2. Check that the gas and liquid side service valves are fully open.  
RUN  
STOP  
GAS LEAK TEST  
Check the flare nut connections for gas leaks with a gas leak detector  
and/or soapy water.  
CODE SWITCH  
FIGURE 41: Emergency Operation  
RUNNING TEST  
1. Turn power on by pressing "ON/OFF" button on the wireless remote  
control to start system operation.  
SECTION XX: MAINTENANCE  
2. Press MODE button to select COOL, HEAT or FAN to check the  
system operation.  
OUTDOOR UNIT  
1. Ensure power is off before cleaning.  
2. It may be necessary to wash the outdoor coil more frequently if it is  
exposed to substances which are corrosive or which block airflow  
across the coil (e.g., pet urine, cottonwood seeds, fertilizers, fluids  
that may contain high levels of corrosive chemicals such as salts).  
INDOOR UNIT RUNNING TEST  
1. Check if operation of each button on the remote control is working  
normally and check the corresponding operating indication LED on  
the indoor unit to make sure they match.  
3. Outdoor Coil (Sea Coast) - Moist air in ocean locations can carry  
salt, which is corrosive to most metal. Units that are located near  
the ocean require frequent inspections and maintenance. These  
inspections will determine the need to wash the unit including the  
outdoor coil. Consult your installing contractor for proper intervals/  
procedures for your geographic area or service contract.  
2. Check the operation of indoor unit louver and make you check its  
swinging function.  
3. Check the condensate drain and make sure there are no leaks.  
OUTDOOR UNIT RUNNING TEST  
1. Make sure there are no abnormal noises or vibration during opera-  
tion.  
4. Outdoor unit fan motor is pre-lubricated and sealed. No further  
lubrication is needed.  
2. Make sure you check for gas leaks.  
5. Visually inspect all connecting lines, joints and coils for evidence of  
oil leaks.  
SECTION XIX: EMERGENCY OPERATION  
6. Check all wiring for loose connections.  
If the wireless remote is lost or damaged, the system can be operated  
using the manual switch or code switch. The system will run in Auto  
Run mode, and will not change the temperature setting nor the fan  
speed.  
7. Check for correct voltage at unit (unit operating).  
INDOOR UNIT  
1. Clean or change filters.  
The manual switch can be operated as follows:  
2. Check all wiring for loose connections.  
3. Check for correct voltage at unit (blower operating).  
4. Clean coil, if necessary.  
To operate the unit, press the AUTO/STOP button once and the  
unit will enter into AUTO RUN mode. The microcomputer will  
select the (COOL, HEAT, FAN) mode automatically to maintain  
optimum room comfort.  
To stop the unit from operating, press the AUTO/STOP button  
once and the unit will shut down.  
5. Check connecting lines and coils for signs of oil leaks.  
6. Check condensate line and clean, if necessary.  
The code switch can be operated as follows:  
NOTICE  
The filter must be in place and the front panel must be closed any  
time the unit is in operation.  
To operate the unit, adjust the code switch to the AUTO position  
and the unit will enter into AUTO RUN mode. The microcomputer  
will select the (COOL, HEAT, FAN) mode automatically to main-  
tain optimum room comfort.  
SECTION XXI: INSTALLATION AND  
MAINTENANCE OF HEALTHY FILTER  
(ACCESSORY)  
To stop the unit from operating, adjust the code switch to the  
STOP position and the unit will shut down.  
NOTICE  
The TEST button is for the technicians' testing, which should not be  
used by our user.  
INSTALLATION OF HEALTHY FILTER (ACCESSORY)  
1. Lift up the front panel from its two ends and remove the factory sup-  
plied air filter as shown in Fig. A.  
2. Attach the healthy filter to the air filter as shown below in Fig. B.  
3. Install the air filter properly as shown below in Fig. C and then close  
the panel.  
18  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
CLEANING AND MAINTENANCE  
1. Remove the healthy filter and clean thoroughly. Make sure you  
don't use a brush or any hard objects to clean the filter.  
2. Make sure you dry the air filter before reinstalling it.  
SECTION XXII: TYPICAL UNIT WIRING  
DIAGRAM  
The indoor unit wiring diagram is located on the inside of the cabinet by  
the terminal block. It is necessary to remove the front panel from the  
unit to see the diagram. The outdoor unit wiring diagram is located on  
the underside of the outdoor unit control access cover.  
Fig. A  
Fig. B  
AIR FILTER  
HEALTHY FILTER  
Fig. C  
FIGURE 42: Filter Replacement  
FIGURE 43: 09K & 12K 115V Outdoor Air Conditioners  
Johnson Controls Unitary Products  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
FIGURE 44: 09K & 12K Outdoor Air Conditioners  
FIGURE 45: 18K & 24K 115V Indoor Air Conditioners  
20  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
FIGURE 46: 18K & 24K Indoor Air Conditioners  
FIGURE 47: 18K Outdoor Air Conditioners  
Johnson Controls Unitary Products  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
FIGURE 48: 18K Indoor Air Conditioners  
FIGURE 49: 24K Outdoor Air Conditioners  
22  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
FIGURE 50: 24K Indoor Air Conditioners  
FIGURE 51: 36K Outdoor Air Conditioners  
Johnson Controls Unitary Products  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
FIGURE 52: 36K Indoor Air Conditioners  
FIGURE 53: 09K & 12K 115V Outdoor Heat Pumps  
24  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
FIGURE 54: 09K & 12K Outdoor Heat Pumps  
FIGURE 55: 18K & 24K 115V Heat Pumps  
Johnson Controls Unitary Products  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
FIGURE 56: 18K & 24K Indoor Heat Pumps  
FIGURE 57: 18K Outdoor Heat Pumps  
26  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
FIGURE 58: 18K Indoor Heat Pumps  
FIGURE 59: 24K Outdoor Heat Pumps  
Johnson Controls Unitary Products  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
FIGURE 60: 24K Indoor Heat Pumps  
FIGURE 61: 30K Outdoor Heat Pumps  
28  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
FIGURE 62: 30K Indoor Heat Pumps  
FIGURE 63: 36K Outdoor Heat Pumps  
Johnson Controls Unitary Products  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
FIGURE 64: 36K Indoor Heat Pumps  
30  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
SECTION XXIII: INDOOR AND OUTDOOR UNITS ERROR CODES  
This section identifies error codes that appear on the front panel of the indoor unit or outdoor unit control. Many of the error codes will automatically  
clear themselves when the error no longer exists. However some error codes may require disconnecting power to the system at the unit disconnect  
switch or circuit breaker in order to clear them and to resume normal system operation.  
* The temperature readout (either  
temperature setpoint or indoor ambient)  
72  
will be replaced by an error code if there  
is a malfunction. If multiple errors are  
detected, the display will alternate  
between each error code.  
NOTE:  
No history is kept on past error codes.  
FIGURE 65: Indoor Unit Front Panel Indicators  
GREEN LED  
YELLOW LED  
RED LED  
FIGURE 66: Control Board  
Johnson Controls Unitary Products  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
INDOOR UNIT ERROR CODES  
TABLE 12: Error Codes - 09K 12K  
Display Method of Indoor Unit  
Malfunction  
Indicator Display  
(during blinking,  
ON 0.5s and OFF 0.5s)  
Indicator has 3 kinds of display  
status and during blinking, ON 0.5s  
and OFF 0.5s  
Malfunction  
Name  
Dual 8  
Code  
No.  
A/C Status  
Possible Causes  
Display  
Operation  
Cool  
Heating  
Yellow  
Red  
Green  
Indicator Indicator Indicator Indicator Indicator  
Indicator  
Possible reasons:  
During cooling and drying 1. Refrigerant was super abun-  
High  
pressure  
protection of  
system  
operation, except indoor  
fan operates, all loads  
stop operation. During  
heating operation, the  
complete unit stops.  
dant;  
OFF 3s  
and blink  
once  
2. Poor heat exchange (includ-  
ing filth blockage of heat  
exchanger and bad radiating  
environment); Ambient tempera-  
ture is too high.  
1
E1  
During cooling and drying  
operation, compressor  
and outdoor fan stop while  
indoor fan operates.  
OFF 3S  
and blink  
twice  
OFF 3S  
and blink  
3 times  
1. Poor air-return in indoor unit;  
2. Fan speed is abnormal;  
3. Evaporator is dirty.  
Antifreezing  
protection  
2
3
E2  
E3  
1.Low-pressure protection  
2.Low-pressure protection of  
system  
3.Low-pressure protection of  
compressor.  
The Dual-8 Code Display  
will show E3 until the low  
pressure switch stop  
operation.  
System block  
or refrigerant  
leakage  
OFF 3S  
and blink  
3 times  
OFF3S  
and blink  
9 times  
During cooling and drying  
operation, compressor  
and outdoor fan stop while TECH Ductless Splits Technical  
indoor fan operates. Training Manual (discharge pro-  
During heating operation, tection, overload).  
all loads stop.  
High  
discharge  
temperature  
protection of  
compressor  
Please refer to the Proficien-  
OFF 3S  
and blink  
4 times  
OFF 3S  
and blink  
7 times  
4
5
E4  
E5  
During cooling and drying  
operation, compressor  
and outdoor fan stop while 2. Supply voltage is too low and  
indoor fan operates.  
During heating operation, 3. Evaporator is dirty.  
all loads stop.  
1. Supply voltage is unstable;  
OFF 3S  
and blink  
5 times  
OFF 3S  
and blink  
5 times  
Overcurrent  
protection  
load is too high;  
During cooling operation,  
Communi-  
cation  
Malfunction  
OFF 3S  
and blink  
6 times  
compressor stops while  
Refer to the corresponding  
6
7
E6  
E8  
OFF  
indoor fan motor operates. ProficienTECH Ductless Splits  
During heating operation, Technical Training Manual.  
the complete unit stops.  
During cooling operation:  
compressor will stop while Refer to the malfunction  
indoor fan will operate.  
During heating operation, temperature resistant).  
the complete unit stops.  
High  
temperature  
resistant  
OFF 3S  
and blink  
8 times  
OFF 3S  
and blink  
6 times  
analysis (overload, high  
protection  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
OFF 3S  
and blink  
15 times  
OFF 3S  
and blink  
11 times  
EEPROM  
malfunction  
Replace outdoor control panel  
AP1.  
8
9
EE  
EU  
Discharging after the complete  
unit is de-energized for 20 mins,  
check whether the thermal  
grease on IPM Module of  
outdoor control panel AP1 is  
sufcient and whether the  
radiator is inserted tightly. If its  
no use, please replace control  
panel AP1.  
Limit/  
decrease  
frequency  
due to high  
temperature  
of module  
All loads operate normally,  
while operation frequency  
for compressor is  
OFF 3S  
and blink  
6 times  
OFF 3S  
and blink  
6 times  
decreased  
1. No jumper cap insert on  
Wireless remote receiver mainboard.  
Malfunction  
protection of  
jumper cap  
OFF 3S  
and blink  
15 times  
and button are effective,  
but cannot dispose the  
related command.  
2. Incorrect insert of jumper cap.  
10  
11  
C5  
F0  
3. Jumper cap damaged.  
4. Abnormal detecting circuit of  
mainboard.  
When the outdoor unit  
receive signal of Gather-  
ing refrigerant, the system  
will be forced to run under  
cooling mode for gathering  
refrigerant  
OFF 3S  
and blink  
1 times  
OFF 3S  
and blink  
1 times  
Gathering  
refrigerant  
Nominal cooling mode  
32  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 12: Error Codes - 09K 12K (Continued)  
Display Method of Indoor Unit  
Malfunction  
Indicator Display  
(during blinking,  
ON 0.5s and OFF 0.5s)  
Indicator has 3 kinds of display  
status and during blinking, ON 0.5s  
and OFF 0.5s  
Malfunction  
Name  
Dual 8  
Code  
No.  
A/C Status  
Possible Causes  
Display  
Operation  
Cool  
Heating  
Yellow  
Red  
Green  
Indicator Indicator Indicator Indicator Indicator  
Indicator  
1. Loosening or bad contact of  
indoor ambient temp. sensor  
and mainboard terminal.  
2. Components in mainboard fell  
down leads short circuit.  
3. Indoor ambient temp. sensor  
damaged. (check with sensor  
resistance value chart).  
Indoor  
ambient  
temperature  
sensor is  
open/short  
circuited  
During cooling and drying  
operation, indoor unit  
operates while other loads  
will stop; during heating  
operation, the complete  
unit will stop operation.  
OFF 3S  
and blink  
once  
12  
F1  
4. Mainboard damaged.  
1. Loosening or bad contact of  
Indoor evaporator temp. sensor  
and mainboard terminal.  
2. Components on the  
mainboard fall down leads  
short circuit.  
3. Indoor evaporator temp.  
sensor damaged. (check temp.  
sensor value chart for testing).  
4. Mainboard damaged.  
AC stops operation once  
reaches the setting tem-  
perature. Cooling, drying:  
internal fan motor stops  
operation while other  
Indoor  
evaporator  
temperature  
sensor is  
open/short  
circuited  
OFF 3S  
and blink  
twice  
13  
F2  
loads stop operation; heat-  
ing: AC stop operation  
Outdoor  
ambient  
temperature  
sensor is  
open/short  
circuited  
During cooling and drying  
operating, compressor  
stops while indoor fan  
operates; During heating  
operation, the complete  
unit will stop operation.  
Outdoor temperature sensor  
hasnt been connected well or is  
damaged. Please check it by  
referring to the resistance table  
for temperature sensor).  
OFF 3S  
and blink  
3 times  
OFF 3S  
and blink  
6 times  
14  
15  
F3  
F4  
Outdoor  
condenser  
temperature  
sensor is  
open/short  
circuited  
During cooling and drying  
operation, compressor  
stops while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
Outdoor temperature sensor  
hasnt been connected well or is  
damaged. Please check it by  
referring to the resistance table  
for temperature sensor).  
OFF 3S  
and blink  
4 times  
OFF 3S  
and blink  
5 times  
During cooling and drying  
operation, compressor will  
stop after operating for  
about 3 mins,while indoor  
fan will operate;During  
heating operation, the  
complete unit will stop  
after operating for about  
3 mins.  
1.Outdoor temperature sensor  
hasnt been connected well or is  
damaged. Please check it by  
referring to the resistance table  
for temperature sensor).  
2.The head of temperature  
sensor hasnt been inserted  
into the copper tube.  
Outdoor  
discharge  
temperature  
sensor is  
open/short  
circuited  
OFF 3S  
and blink  
5 times  
OFF 3S  
and blink  
7 times  
16  
17  
F5  
F6  
Limit/  
decrease  
frequency  
due to  
All loads operate normally,  
while operation frequency  
for compressor is  
OFF 3S  
and blink  
for 6 times  
OFF 3S  
and blink  
3 times  
Refer to the malfunction  
analysis (overload, high  
temperature resistant)  
decreased.  
overload  
Decrease  
frequency  
due to  
All loads operate normally,  
while operation frequency  
for compressor is  
OFF 3S  
and blink  
8 times  
OFF 3S  
and blink  
once  
The input supply voltage is too  
low; System pressure is too high  
and overload.  
18  
19  
F8  
F9  
overcurrent  
decreased.  
Decrease  
frequency  
due to high  
air discharge  
All loads operate normally, Overload or temperature is too  
while operation frequency high; Refrigerant is insufcient;  
for compressor is  
decreased.  
OFF 3S  
and blink  
9 times  
OFF 3S  
and blink  
twice  
Malfunction of electric expan-  
sion valve (EKV).  
Limit/  
decrease  
frequency  
due to  
All loads operate normally,  
while operation frequency Poor air-return in indoor unit or  
for compressor is  
decreased.  
OFF 3S  
and blink  
2 times  
OFF 3S  
and blink  
2 times  
OFF 3S  
and blink  
4 times  
20  
FH  
fan speed is too low.  
antifreezing  
1. Measure the voltage of posi-  
tion L and N on wiring board  
(XT), if the voltage is higher than  
During cooling and drying 265VAC, turn on the unit after  
operation, compressor will the supply voltage is increased  
Voltage for  
21 DC bus-bar is  
too high  
OFF 3S  
and blink  
11 times  
OFF 3S  
and blink  
13 times  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
to the normal range.  
PH  
2.If the AC input is normal, mea-  
sure the voltage of electrolytic  
capacitor C on control panel  
(AP1), if its normal, theres mal-  
function for the circuit, please  
replace the control panel (AP1).  
Johnson Controls Unitary Products  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 12: Error Codes - 09K 12K (Continued)  
Display Method of Indoor Unit  
Malfunction  
Indicator Display  
(during blinking,  
ON 0.5s and OFF 0.5s)  
Indicator has 3 kinds of display  
status and during blinking, ON 0.5s  
and OFF 0.5s  
Malfunction  
Name  
Dual 8  
Code  
No.  
A/C Status  
Possible Causes  
Display  
Operation  
Cool  
Heating  
Yellow  
Red  
Green  
Indicator Indicator Indicator Indicator Indicator  
Indicator  
1. Measure the voltage of posi-  
tion L and N on wiring board  
(XT), if the voltage is higher than  
During cooling and drying 150VAC, turn on the unit after  
operation, compressor will the supply voltage is increased  
Voltage of DC  
22 bus-bar is too  
low  
OFF 3S  
and blink  
21 times  
OFF 3S  
and blink  
12 times  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
to the normal range.  
PL  
2.If the AC input is normal, mea-  
sure the voltage of electrolytic  
capacitor C on control panel  
(AP1), if its normal, theres mal-  
function for the circuit, please  
replace the control panel (AP1).  
Compressor  
Min  
frequence in  
test state  
Showing during min. cooling or  
min. heating test.  
23  
P0  
P1  
P2  
P3  
Compressor  
rated  
frequence in  
Showing during nominal cooling  
or nominal heating test.  
24  
test state  
Compressor  
maximum  
frequence in  
test state  
Showing during max. cooling or  
max. heating test.  
25  
Compressor  
intermediate  
frequence in  
Showing during middle cooling  
or middle heating test.  
26  
test state  
During cooling and drying Refer to the ProficienTECH  
operation, compressor will Ductless Splits Technical Train-  
Overcurrent  
protection  
of phase  
current for  
compressor  
OFF 3S  
and blink  
15 times  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
ing Manual (IPM protection, loss  
of synchronism protection and  
overcurrent protection of phase  
current for compressor..  
27  
28  
29  
P5  
PU  
P7  
During cooling and drying  
operation, compressor will Refer to the part three-charging  
Charging  
malfunction  
of capacitor  
OFF 3S  
and blink  
17 times  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
ProficienTECH Ductless Splits  
Technical Training Manual of  
capacitor.  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
Malfunction  
of module  
temperature  
sensor circuit  
OFF 3S  
and blink  
18 times  
Replace outdoor control panel  
AP1.  
After the complete unit is  
de-energized for 20 mins, check  
whether the thermal grease on  
IPM Module of outdoor control  
panel AP1 is sufcient and  
whether the radiator is inserted  
tightly. If its no use, please  
replace control panel AP1.  
During cooling operation,  
compressor will stop while  
indoor fan will operate;  
During heating operation,  
the complete unit will stop.  
Module high  
temperature  
protection  
OFF 3S  
and blink  
19 times  
30  
P8  
Decrease  
frequency  
due to high  
temperature  
resistant  
All loads operate normally, Refer to the ProficienTECH  
while operation frequency Ductless Splits Technical Train-  
OFF 3S  
and blink  
10 times  
31  
32  
H0  
H2  
for compressor is  
decreased.  
ing Manual (overload, high tem-  
perature resistant).  
during heat-  
ing operation  
Static  
dedusting  
protection  
OFF 3S  
and blink  
twice  
34  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 12: Error Codes - 09K 12K (Continued)  
Display Method of Indoor Unit  
Malfunction  
Indicator Display  
(during blinking,  
ON 0.5s and OFF 0.5s)  
Indicator has 3 kinds of display  
status and during blinking, ON 0.5s  
and OFF 0.5s  
Malfunction  
Name  
Dual 8  
Code  
No.  
A/C Status  
Possible Causes  
Display  
Operation  
Cool  
Heating  
Yellow  
Red  
Green  
Indicator Indicator Indicator Indicator Indicator  
Indicator  
1. Wiring terminal OVC-COMP  
During cooling and drying is loosened. In normal state, the  
operation, compressor will resistance for this terminal  
Overload  
33 protection for  
compressor  
OFF 3S  
and blink  
3 times  
OFF 3S  
and blink  
8 times  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
should be less than 1ohm.  
2. Refer to the ProficienTECH  
Ductless Splits Technical Train-  
ing Manual ( discharge protec-  
tion, overload).  
H3  
H4  
During cooling and drying  
operation, compressor will Refer to the ProficienTECH  
OFF 3S  
and blink  
4 times  
OFF 3S  
and blink  
6 times  
System is  
34  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
Ductless Splits Technical Train-  
ing Manual (overload, high tem-  
perature resistant).  
abnormal  
During cooling and drying Refer to the ProficienTECH  
operation, compressor will Ductless Splits Technical Train-  
OFF 3S  
and blink  
5 times  
OFF 3S  
and blink  
4 times  
IPM  
35  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
ing Manual (IPM protection, loss  
of synchronism protection and  
overcurrent protection of phase  
current for compressor.  
H5  
H5  
protection  
Module  
OFF 3S  
and blink  
5 times  
OFF 3S  
and blink  
10 times  
36  
37  
temperature  
is too high  
1. Bad contact of DC motor  
feedback terminal.  
2. Bad contact of DC motor  
control end.  
3. Fan motor is stalling.  
4. Motor malfunction.  
5. Malfunction of mainboard rev  
detecting circuit.  
Internal  
motor  
(fan motor)  
do not  
Internal fan motor, exter-  
nal fan motor, compressor  
and electric heater stop  
operation, guide louver  
stops at present location.  
OFF 3S  
and blink  
11 times  
H6  
H7  
operate  
During cooling and drying Refer to the ProficienTECH  
operation, compressor will Ductless Splits Technical Train-  
Desynchro-  
nizing of  
OFF 3S  
and blink  
7 times  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
ing Manual (IPM protection, loss  
of synchronism protection and  
overcurrent protection of phase  
current for compressor.  
38  
compressor  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
OFF 3S  
and blink  
6 times  
OFF 3S  
and blink  
14 times  
Refer to the ProficienTECH  
Ductless Splits Technical Train-  
ing Manual.  
PFC  
protection  
39  
40  
41  
HC  
L3  
L9  
Outdoor DC  
fan motor  
malfunction  
OFF 3S  
and blink  
23 times  
OFF 3S  
and blink  
14 times  
Outdoor DC fan motor  
malfunction lead to com- system blocked or the connector  
pressor stop operation.  
DC fan motor malfunction or  
loosed  
Compressor stop opera-  
tion and Outdoor fan  
motor will stop 30s latter,  
3 minutes latter fan motor  
and compressor will  
restart.  
OFF 3S  
and blink  
20 times  
OFF 3S  
and blink  
9 times  
To protect the electronical  
components when detect high  
power.  
Power  
protection  
Indoor unit  
and outdoor  
unit doesn't  
match  
OFF 3S  
and blink  
19 times  
OFF 3S  
and blink  
16 times  
compressor and Outdoor Indoor unit and outdoor unit  
42  
43  
LP  
LC  
fan motor can’t work.  
doesn't match.  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
OFF 3S  
and blink  
11 times  
Refer to the ProficienTECH  
Ductless Splits Technical Train-  
ing Manual.  
Failure  
start-up  
Malfunction  
of phase  
current  
detection  
circuit for  
compressor  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
OFF 3S  
and blink  
13 times  
Replace outdoor control panel  
AP1.  
44  
U1  
Johnson Controls Unitary Products  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 12: Error Codes - 09K 12K (Continued)  
Display Method of Indoor Unit  
Malfunction  
Indicator Display  
(during blinking,  
ON 0.5s and OFF 0.5s)  
Indicator has 3 kinds of display  
status and during blinking, ON 0.5s  
and OFF 0.5s  
Malfunction  
Name  
Dual 8  
Code  
No.  
A/C Status  
Possible Causes  
Display  
Operation  
Cool  
Heating  
Yellow  
Red  
Green  
Indicator Indicator Indicator Indicator Indicator  
Indicator  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop  
Malfunction  
of voltage  
dropping for  
DC bus-bar  
OFF 3S  
and blink  
20 times  
45  
46  
U3  
U5  
Supply voltage is unstable  
During cooling and drying  
operation, the compres-  
sor will stop while indoor  
fan will operate; During  
heating operating, the  
complete unit will stop  
operation.  
Malfunction  
of complete  
units current  
detection  
Theres circuit malfunction on  
outdoor units control panel AP1,  
please replace the outdoor units  
control panel AP1.  
OFF 3S  
and blink  
13 times  
1. Supply voltage is lower than  
If this malfunction occurs AC175V;  
during heating operation, 2. Wiring terminal 4V is loos-  
the complete unit will stop ened or broken;  
The four-way  
valve is  
abnormal  
OFF 3S  
and blink  
20 times  
47  
48  
U7  
U9  
operation.  
3. 4V is damaged, please  
replace 4V.  
During cooling operation,  
compressor will stop while  
indoor fan will operate;  
during heating,the com-  
plete unit will stop opera-  
tion.  
Zero-crossing  
malfunction  
of outdoor  
unit  
OFF 3S  
and blink  
18 times  
Replace outdoor control panel  
AP1.  
Frequency  
limiting  
(power).  
OFF 3S  
and blink  
13 times  
49  
50  
Compressor  
is open-  
circuited  
OFF 3S  
and blink  
once  
The  
temperature  
51 for turning on  
the unit is  
OFF 3S  
and blink  
8 times  
reached  
Frequency  
limiting  
(module  
temperature)  
OFF 3S  
and blink  
11 times  
52  
Normal com-  
53  
Continously  
munication  
OFF 3S  
and blink  
Defrosting will occur in  
heating mode. Compres-  
sor will operate while  
indoor fan will stop opera-  
tion.  
once  
OFF 3S  
(during  
and blink  
blinking,  
twice  
54  
Defrosting  
Its the normal state.  
ON 10s  
and OFF  
0.5s)  
36  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 13: Error Codes - 18K 24K  
Display Method of Outdoor  
Unit (Indicator has 3 kinds of  
display status and they will  
be repeated every 5s.)  
Display Method of Indoor Unit  
Malfunction  
Name  
OFF  
No.  
A/C status  
Possible Reasons  
Indicator Display (during  
blinking,  
ON 0.5s and OFF 0.5s)  
Illuminated  
Blink  
Dual-8  
Code  
Display  
Operation  
Cool  
Heating  
D5  
D6  
D16  
D30  
Indicator Indicator Indicator (D40) (D41) (D42) (D43)  
During cooling and drying  
Possible reasons:  
operation, except indoor fan 1. Refrigerant was overcharged;  
High pressure  
protection  
of system  
OFF 3s and  
blink once  
operates, all loads stop  
operation. During heating  
operation, the complete  
unit stops.  
2. Poor heat exchange (including  
filth blockage of heat exchanger  
and bad radiating environment);  
Ambient temperature is too high.  
1
E1  
During cooling and drying  
operation, compressor and  
outdoor fan stop while indoor  
fan operates.  
OFF 3S  
and blink  
twice  
1. Poor air-return in indoor unit;  
2. Fan speed is abnormal;  
3. Evaporator is dirty.  
Antifreezing  
protection  
E2  
E4  
2
3
During cooling and drying  
operation, compressor and  
outdoor fan stop while indoor  
fan operates. During heating  
operation, all loads stop.  
High discharge  
temperature  
protection of  
compressor  
Please refer to the ProficienTECH  
Ductless Splits Technical Training  
Manual (discharge protection,  
overload).  
OFF 3S  
and blink  
4 times  
During cooling and drying  
operation, compressor and  
outdoor fan stop while indoor  
fan operates. During heating  
operation, all loads stop.  
1. Supply voltage is unstable;  
2. Supply voltage is too low an  
load is too high;  
OFF 3S  
and blink  
5 times  
Overcurrent  
protection  
E5  
E6  
E8  
4
5
6
3. Evaporator is dirty.  
During cooling operation,  
compressor stops while  
indoor fan motor operates.  
During heating operation,  
the complete unit stops.  
OFF 3S  
and blink 6  
times  
Refer to the corresponding  
ProficienTECH Ductless Splits  
Technical Training Manual.  
Communication  
Malfunction  
During cooling operation:  
compressor will stop while  
indoor fan will operate.  
During heating operation,  
the complete unit stops.  
Refer to the ProficienTECH Duct-  
less Splits Technical Training Man-  
ual  
(overload, high temperature  
resistant).  
High  
temperature  
resistant  
OFF 3S  
and blink  
8 times  
protection  
Circuit PG  
motor (indoor  
fan) has circuit  
malfunction  
by zero cross  
detection  
Operation of remote  
controller or control panel is  
available, but the unit wont  
act.  
OFF 3S  
and blink  
for 17 times  
7
U8  
Control board is damaged.  
Poor connection for PGF in circuit  
diagram;  
Malfunction of indoor units control  
panel AP1;  
Malfunction of indoor units motor  
M1.  
PG motor  
(indoor fan  
motor) does  
not operate  
OFF 3S  
and blink  
11 times  
The complete unit will stop  
operation.  
8
9
H6  
C5  
Poor connection for the jumper cap  
on indoor units control panel AP1;  
please reinsert or replace the  
jumper cap;  
Malfunction  
protection of  
jumper cap  
OFF 3S  
and blink  
15 times  
The complete unit will stop  
operation.  
1.Room temperature sensor hasn’t  
been connected well with indoor  
units control panel AP1 (refer to  
the wiring diagram for indoor unit);  
2.Room temperature sensor is  
damaged (please refer to the resis-  
tance table of temperature sensor)  
During cooling and drying  
operation, indoor unit  
operates while other loads  
will stop; during heating  
operation, the complete  
unit will stop operation.  
Indoor ambient  
temperature  
sensor is open/  
short circuited  
OFF 3S  
and blink  
once  
10  
F1  
1.Room temperature sensor hasn’t  
been connected well with indoor  
units control panel AP1 (refer to  
the wiring diagram for indoor unit);  
2.Room temperature sensor is  
damaged (please refer to the resis-  
tance table of temperature sensor)  
During cooling and drying  
operation, indoor unit will  
operate while other loads  
will stop; During heating  
operation, the complete  
unit will stop operation.  
Indoor evapora-  
tor temperature  
sensor is open/  
short circuited  
OFF 3S  
and blink  
twice  
11  
12  
F2  
F3  
During cooling and drying  
operating, compressor stops  
while indoor fan operates;  
During heating operation,  
the complete unit will stop  
operation.  
Outdoor  
ambient  
temperature  
sensor is open/  
short circuited  
Outdoor temperature sensor  
hasn’t been connected well or is  
damaged. Please check it by  
referring to the resistance table  
for temperature sensor).  
OFF 3S  
and blink  
3 times  
Johnson Controls Unitary Products  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 13: Error Codes - 18K 24K (Continued)  
Display Method of Outdoor  
Unit (Indicator has 3 kinds of  
display status and they will  
be repeated every 5s.)  
Display Method of Indoor Unit  
Malfunction  
Name  
OFF  
No.  
A/C status  
Possible Reasons  
Indicator Display (during  
blinking,  
ON 0.5s and OFF 0.5s)  
Illuminated  
Blink  
Dual-8  
Code  
Display  
Operation  
Cool  
Heating  
D5  
D6  
D16  
D30  
Indicator Indicator Indicator (D40) (D41) (D42) (D43)  
During cooling and drying  
operation, compressor stops  
while indoor fan will  
operate; During heating  
operation the complete unit  
will stop operation.  
Outdoor  
condenser  
temperature  
sensor is open/  
short circuited  
Outdoor temperature sensor  
hasn’t been connected well or is  
damaged. Please check it by  
referring to the resistance table  
for temperature sensor).  
OFF 3S  
and blink  
4 times  
13  
14  
F4  
F5  
During cooling and drying  
operation, compressor will  
stop after operating for about damaged. Please check it by  
3 mins, while indoor fan will referring to the resistance table for  
operate; During heating  
operation, the complete unit 2.The head of temperature sensor  
1.Outdoor temperature sensor  
hasn’t been connected well or is  
Outdoor  
discharge  
temperature  
sensor is open/  
short circuited  
OFF 3S  
and blink  
5 times  
temperature sensor).  
will stop after operating for  
about 3 mins.  
hasn’t been inserted into the  
copper tube.  
OFF 3S  
and blink  
for 6  
Refer to the ProficienTECH Duct-  
less Splits Technical Training Man-  
ual (overload, high temperature  
resistant).  
Limit/ decrease  
frequency  
due to overload  
All loads operate normally,  
while operation frequency for  
compressor is decreased.  
15  
16  
17  
F6  
F8  
F9  
times  
Decrease  
frequency due  
to overcurrent  
OFF 3S  
and blink  
8 times  
All loads operate normally,  
The input supply voltage is too low;  
while operation frequency for System pressure is too high and  
compressor is decreased.  
overload.  
Decrease  
frequency due  
to high air  
Overload or temperature is too  
high; Refrigerant is insufficient;  
Malfunction of electric expansion  
valve (EKV).  
OFF 3S  
and blink  
9 times  
All loads operate normally,  
while operation frequency for  
compressor is decreased.  
discharge  
1. Measure the voltage of position  
L and N on wiring board (XT), if the  
voltage is higher than 265VAC,  
turn on the unit after the supply  
voltage is increased to the normal  
range.  
2. If the AC input is normal  
measure the voltage of electrolytic  
capacitor C on control panel (AP1),  
if its normal, there’s malfunction for  
the circuit, please replace the con-  
trol panel (AP1).  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
Voltage for  
DC bus-bar  
is too high  
OFF 3S  
and blink  
11 times  
18  
PH  
During cooling and drying  
operation, the compressor  
will stop while indoor fan  
will operate; During heating please replace the outdoor units  
operating, the complete  
unit will stop operation.  
Malfunction of  
complete units  
current  
There’s circuit malfunctionon out-  
door units control panel AP1,  
OFF 3S  
and blink  
13 times  
19  
20  
U5  
P5  
detection  
control panel AP1.  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
Refer to the ProficienTECH Duct-  
less Splits Technical Training Man-  
ual (IPM protection, loss of  
synchronism protection and  
overcurrent protection of phase  
current for compressor.  
Overcurrent  
protection of  
phase current  
for compressor  
OFF 3S  
and blink  
15 times  
Defrosting will occur in  
heating mode. Compressor  
will operate while indoor fan  
will stop operation.  
OFF 3S  
and blink  
once  
21  
22  
Defrosting  
H1  
H2  
Its the normal state.  
Static  
de-dusting  
protection  
OFF 3S  
and blink  
twice  
/
/
1. Wiring terminal OVC-COMP is  
loosened. In normal state, the  
resistance for this terminal should  
be less than 1ohm.  
2.Refer to the ProficienTECH  
Ductless Splits Technical Training  
Manual (discharge protection,  
overload).  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
Overload  
protection for  
compressor  
OFF 3S  
and blink  
3 times  
23  
H3  
38  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 13: Error Codes - 18K 24K (Continued)  
Display Method of Outdoor  
Unit (Indicator has 3 kinds of  
display status and they will  
be repeated every 5s.)  
Display Method of Indoor Unit  
Malfunction  
Name  
OFF  
No.  
A/C status  
Possible Reasons  
Indicator Display (during  
blinking,  
ON 0.5s and OFF 0.5s)  
Illuminated  
Blink  
Dual-8  
Code  
Display  
Operation  
Cool  
Heating  
D5  
D6  
D16  
D30  
Indicator Indicator Indicator (D40) (D41) (D42) (D43)  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
Refer to the ProficienTECH Duct-  
less Splits Technical Training Man-  
ual (overload, high temperature  
resistant)  
OFF 3S  
and blink  
4 times  
System is  
abnormal  
24  
25  
26  
27  
H4  
H5  
HC  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
Refer to the ProficienTECH Duct-  
less Splits Technical Training Man-  
ual (IPM protection, loss of  
synchronism protection and over-  
current protection of phase current  
for compressor.  
OFF 3S  
and blink  
5 times  
IPM  
protection  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
OFF 3S  
and blink  
6 times  
Refer to the ProficienTECH Duct-  
less Splits Technical Training Man-  
ual  
PFC  
protection  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
Refer to the ProficienTECH Duct-  
less Splits Technical Training Man-  
ual (IPM protection, loss of  
synchronism protection and over-  
current protection of phase current  
for compressor.  
OFF 3S  
and blink  
7 times  
Desynchronizing  
of compressor  
H7  
H0  
LC  
Decrease  
frequency due to  
28 high temperature  
resistant during  
Refer to the ProficienTECH Duct-  
less Splits Technical Training Man-  
ual (overload, high temperature  
resistant).  
OFF 3S  
and blink  
10 times  
All loads operate normally,  
while operation frequency for  
compressor is decreased.  
heating operation  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
OFF 3S  
and blink  
11 times  
Refer to the ProficienTECH Duct-  
less Splits Technical Training Man-  
ual.  
29  
30  
31  
32  
33  
Failure startup  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
Malfunction of  
phase current  
detection circuit  
for compressor  
OFF 3S  
and blink  
13 times  
Replace outdoor control panel  
AP1.  
U1  
EE  
PU  
P7  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
OFF 3S  
and blink  
15 times  
EE PROM  
malfunction  
Replace outdoor control panel  
AP1.  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
Refer to the part three charging  
ProficienTECH Ductless Splits  
Technical Training Manual of  
capacitor.  
Charging  
malfunction of  
capacitor  
OFF 3S  
and blink  
17 times  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
Malfunction  
of module  
temperature  
sensor circuit  
OFF 3S  
and blink  
18 times  
Replace outdoor control panel  
AP1.  
Johnson Controls Unitary Products  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 13: Error Codes - 18K 24K (Continued)  
Display Method of Outdoor  
Unit (Indicator has 3 kinds of  
display status and they will  
be repeated every 5s.)  
Display Method of Indoor Unit  
Malfunction  
Name  
OFF  
No.  
A/C status  
Possible Reasons  
Indicator Display (during  
blinking,  
ON 0.5s and OFF 0.5s)  
Illuminated  
Blink  
Dual-8  
Code  
Display  
Operation  
Cool  
Heating  
D5  
D6  
D16  
D30  
Indicator Indicator Indicator (D40) (D41) (D42) (D43)  
After the complete unit is  
de-energized for 20mins, check  
whether the thermal grease on  
IPM Module of outdoor control  
panel AP1 is sufficient and whether  
the radiator is inserted tightly. If its  
no use, please replace control  
panel AP1.  
During cooling operation,  
compressor will stop while  
indoor fan will operate;  
During heating operation,  
the complete unit will stop.  
Module high  
temperature  
protection  
OFF 3S  
and blink  
19 times  
34  
P8  
U3  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
Malfunction of  
35 voltage dropping  
for DC bus-bar  
OFF 3S  
and blink  
20 times  
Supply voltage is unstable.  
1. Measure the voltage of position  
L and N on wiring board (XT), if the  
voltage is higher than 150VAC,  
turn on the unit after the supply  
voltage is increased to the normal  
range.  
2.If the AC input is normal,  
measure the voltage of electrolytic  
capacitor C on control panel (AP1),  
if its normal, there’s malfunction for  
the circuit, please replace the  
control panel (AP1).  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
Voltage of DC  
bus-bar is  
too low  
OFF 3S  
and blink  
21 times  
36  
PL  
Discharging after the complete unit  
is de-energized for 20mins, check  
whether the thermal grease on  
IPM Module of outdoor control  
panel AP1 is sufficient and whether  
the radiator is inserted tightly. If its  
no use, please replace control  
panel AP1.  
Limit/ decrease  
frequency due to  
high temperature  
of module  
All loads operate normally,  
while operation frequency  
for compressor is decreased.  
37  
EU  
U7  
1.Supply voltage is lower than  
AC175V;  
2.Wiring terminal 4V is loosened  
or broken; 3.4V is damaged,  
please replace 4V.  
If this malfunction occurs  
during heating operation,  
the complete unit will stop  
operation.  
The four-way  
valve is abnormal  
38  
39  
During cooling operation,  
compressor will stop while  
indoor fan will operate;  
during heating, the complete  
unit will stop operation.  
Zero crossing  
malfunction of  
outdoor unit  
Replace outdoor control panel  
AP1.  
U9  
FH  
Limit/ decrease  
40 frequency due to  
antifreezing  
All loads operate normally,  
while operation frequency for  
compressor is decreased.  
Poor air-return in indoor unit or  
fan speed is too low.  
40  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 14: Error Codes - 30K 36K  
Display Method of Indoor Unit  
Malfunction  
Indicator Display  
(during blinking,  
ON 0.5s and OFF 0.5s)  
Indicator has 3 kinds of display  
status and during blinking, ON 0.5s  
and OFF 0.5s  
Malfunction  
Name  
Dual 8  
Code  
No.  
A/C Status  
Possible Causes  
Display  
Operation  
Cool  
Heating  
Yellow  
Red  
Green  
Indicator Indicator Indicator Indicator Indicator  
Indicator  
Possible reasons:  
During cooling and drying 1. Refrigerant was super abun-  
High  
pressure  
protection of  
system  
operation, except indoor  
fan operates, all loads  
stop operation. During  
heating operation, the  
complete unit stops.  
dant;  
OFF 3s  
and blink  
once  
2. Poor heat exchange (includ-  
ing filth blockage of heat  
exchanger and bad radiating  
environment); Ambient tempera-  
ture is too high.  
1
E1  
During cooling and drying  
operation, compressor  
and outdoor fan stop while  
indoor fan operates.  
OFF 3S  
and blink  
twice  
OFF 3S  
and blink  
3 times  
1. Poor air-return in indoor unit;  
2. Fan speed is abnormal;  
3. Evaporator is dirty.  
Antifreezing  
protection  
2
3
E2  
E3  
1.Low-pressure protection  
2.Low-pressure protection of  
system  
3.Low-pressure protection of  
compressor.  
The Dual-8 Code Display  
will show E3 until the low  
pressure switch stop  
operation.  
System block  
or refrigerant  
leakage  
OFF 3S  
and blink  
3 times  
OFF3S  
and blink  
9 times  
During cooling and drying  
operation, compressor  
and outdoor fan stop while TECH Ductless Splits Technical  
indoor fan operates. Training Manual (discharge pro-  
During heating operation, tection, overload).  
all loads stop.  
High  
discharge  
temperature  
protection of  
compressor  
Please refer to the Proficien-  
OFF 3S  
and blink  
4 times  
OFF 3S  
and blink  
7 times  
4
5
E4  
E5  
During cooling and drying  
operation, compressor  
and outdoor fan stop while 2. Supply voltage is too low and  
indoor fan operates.  
During heating operation, 3. Evaporator is dirty.  
all loads stop.  
1. Supply voltage is unstable;  
OFF 3S  
and blink  
5 times  
OFF 3S  
and blink  
5 times  
Overcurrent  
protection  
load is too high;  
During cooling operation,  
Communi-  
cation  
Malfunction  
OFF 3S  
and blink  
6 times  
compressor stops while  
Refer to the corresponding  
6
7
E6  
E8  
OFF  
indoor fan motor operates. ProficienTECH Ductless Splits  
During heating operation, Technical Training Manual.  
the complete unit stops.  
During cooling operation:  
compressor will stop while Refer to the ProficienTECH  
indoor fan will operate.  
During heating operation, temperature resistant).  
the complete unit stops.  
High  
temperature  
resistant  
OFF 3S  
and blink  
8 times  
OFF 3S  
and blink  
6 times  
Ductless/ (overload, high  
protection  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
OFF 3S  
and blink  
15 times  
OFF 3S  
and blink  
11 times  
EEPROM  
malfunction  
Replace outdoor control panel  
AP1.  
8
9
EE  
EU  
Discharging after the complete  
unit is de-energized for 20 mins,  
check whether the thermal  
grease on IPM Module of  
outdoor control panel AP1 is  
sufcient and whether the  
radiator is inserted tightly. If its  
no use, please replace control  
panel AP1.  
Limit/  
decrease  
frequency  
due to high  
temperature  
of module  
All loads operate normally,  
while operation frequency  
for compressor is  
OFF 3S  
and blink  
6 times  
OFF 3S  
and blink  
6 times  
decreased  
1. No jumper cap insert on  
Wireless remote receiver mainboard.  
Malfunction  
protection of  
jumper cap  
OFF 3S  
and blink  
15 times  
and button are effective,  
but cannot dispose the  
related command.  
2. Incorrect insert of jumper cap.  
10  
11  
C5  
F0  
3. Jumper cap damaged.  
4. Abnormal detecting circuit of  
mainboard.  
When the outdoor unit  
receive signal of Gather-  
ing refrigerant, the system  
will be forced to run under  
cooling mode for gathering  
refrigerant  
OFF 3S  
and blink  
1 times  
OFF 3S  
and blink  
1 times  
Gathering  
refrigerant  
Nominal cooling mode  
Johnson Controls Unitary Products  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 14: Error Codes - 30K 36K (Continued)  
Display Method of Indoor Unit  
Malfunction  
Indicator Display  
(during blinking,  
ON 0.5s and OFF 0.5s)  
Indicator has 3 kinds of display  
status and during blinking, ON 0.5s  
and OFF 0.5s  
Malfunction  
Name  
Dual 8  
Code  
No.  
A/C Status  
Possible Causes  
Display  
Operation  
Cool  
Heating  
Yellow  
Red  
Green  
Indicator Indicator Indicator Indicator Indicator  
Indicator  
1. Loosening or bad contact of  
indoor ambient temp. sensor  
and mainboard terminal.  
2. Components in mainboard fell  
down leads short circuit.  
3. Indoor ambient temp. sensor  
damaged. (check with sensor  
resistance value chart).  
Indoor  
ambient  
temperature  
sensor is  
open/short  
circuited  
During cooling and drying  
operation, indoor unit  
operates while other loads  
will stop; during heating  
operation, the complete  
unit will stop operation.  
OFF 3S  
and blink  
once  
12  
F1  
4. Mainboard damaged.  
1. Loosening or bad contact of  
Indoor evaporator temp. sensor  
and mainboard terminal.  
2. Components on the  
mainboard fall down leads  
short circuit.  
3. Indoor evaporator temp.  
sensor damaged. (check temp.  
sensor value chart for testing).  
4. Mainboard damaged.  
AC stops operation once  
reaches the setting tem-  
perature. Cooling, drying:  
internal fan motor stops  
operation while other  
Indoor  
evaporator  
temperature  
sensor is  
open/short  
circuited  
OFF 3S  
and blink  
twice  
13  
F2  
loads stop operation; heat-  
ing: AC stop operation  
Outdoor  
ambient  
temperature  
sensor is  
open/short  
circuited  
During cooling and drying  
operating, compressor  
stops while indoor fan  
operates; During heating  
operation, the complete  
unit will stop operation.  
Outdoor temperature sensor  
hasnt been connected well or is  
damaged. Please check it by  
referring to the resistance table  
for temperature sensor).  
OFF 3S  
and blink  
3 times  
OFF 3S  
and blink  
6 times  
14  
15  
F3  
F4  
Outdoor  
condenser  
temperature  
sensor is  
open/short  
circuited  
During cooling and drying  
operation, compressor  
stops while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
Outdoor temperature sensor  
hasnt been connected well or is  
damaged. Please check it by  
referring to the resistance table  
for temperature sensor).  
OFF 3S  
and blink  
4 times  
OFF 3S  
and blink  
5 times  
During cooling and drying  
operation, compressor will  
stop after operating for  
about 3 mins,while indoor  
fan will operate;During  
heating operation, the  
complete unit will stop  
after operating for about  
3 mins.  
1.Outdoor temperature sensor  
hasnt been connected well or is  
damaged. Please check it by  
referring to the resistance table  
for temperature sensor).  
2.The head of temperature  
sensor hasnt been inserted  
into the copper tube.  
Outdoor  
discharge  
temperature  
sensor is  
open/short  
circuited  
OFF 3S  
and blink  
5 times  
OFF 3S  
and blink  
7 times  
16  
17  
F5  
F6  
Limit/  
decrease  
frequency  
due to  
All loads operate normally, Refer to the ProficienTECH  
while operation frequency Ductless Splits Technical Train-  
for compressor is  
decreased.  
OFF 3S  
and blink  
for 6 times  
OFF 3S  
and blink  
3 times  
ing Manual (overload, high  
temperature resistant)  
overload  
Decrease  
frequency  
due to  
All loads operate normally,  
while operation frequency  
for compressor is  
OFF 3S  
and blink  
8 times  
OFF 3S  
and blink  
once  
The input supply voltage is too  
low; System pressure is too high  
and overload.  
18  
19  
F8  
F9  
overcurrent  
decreased.  
Decrease  
frequency  
due to high  
air discharge  
All loads operate normally, Overload or temperature is too  
while operation frequency high; Refrigerant is insufcient;  
for compressor is  
decreased.  
OFF 3S  
and blink  
9 times  
OFF 3S  
and blink  
twice  
Malfunction of electric expan-  
sion valve (EKV).  
Limit/  
decrease  
frequency  
due to  
All loads operate normally,  
while operation frequency Poor air-return in indoor unit or  
for compressor is  
decreased.  
OFF 3S  
and blink  
2 times  
OFF 3S  
and blink  
2 times  
OFF 3S  
and blink  
4 times  
20  
FH  
fan speed is too low.  
antifreezing  
1. Measure the voltage of posi-  
tion L and N on wiring board  
(XT), if the voltage is higher than  
During cooling and drying 265VAC, turn on the unit after  
operation, compressor will the supply voltage is increased  
Voltage for  
21 DC bus-bar is  
too high  
OFF 3S  
and blink  
11 times  
OFF 3S  
and blink  
13 times  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
to the normal range.  
PH  
2.If the AC input is normal, mea-  
sure the voltage of electrolytic  
capacitor C on control panel  
(AP1), if its normal, theres mal-  
function for the circuit, please  
replace the control panel (AP1).  
42  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 14: Error Codes - 30K 36K (Continued)  
Display Method of Indoor Unit  
Malfunction  
Indicator Display  
(during blinking,  
ON 0.5s and OFF 0.5s)  
Indicator has 3 kinds of display  
status and during blinking, ON 0.5s  
and OFF 0.5s  
Malfunction  
Name  
Dual 8  
Code  
No.  
A/C Status  
Possible Causes  
Display  
Operation  
Cool  
Heating  
Yellow  
Red  
Green  
Indicator Indicator Indicator Indicator Indicator  
Indicator  
1. Measure the voltage of posi-  
tion L and N on wiring board  
(XT), if the voltage is higher than  
During cooling and drying 150VAC, turn on the unit after  
operation, compressor will the supply voltage is increased  
Voltage of DC  
22 bus-bar is too  
low  
OFF 3S  
and blink  
21 times  
OFF 3S  
and blink  
12 times  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
to the normal range.  
PL  
2.If the AC input is normal, mea-  
sure the voltage of electrolytic  
capacitor C on control panel  
(AP1), if its normal, theres mal-  
function for the circuit, please  
replace the control panel (AP1).  
Blinking in Blinking in  
cool mode, heatmode,  
ON 0.25s ON 0.25s  
Compressor  
Min  
frequence in  
Showing during min. cooling or  
min. heating test.  
23  
P0  
P1  
P2  
P3  
and OFF  
0.25s  
and OFF  
0.25s  
test state  
Blinking in Blinking in  
cool mode, heatmode,  
ON 0.25s ON 0.25s  
Compressor  
rated  
frequence in  
Showing during nominal cooling  
or nominal heating test.  
24  
and OFF  
0.25s  
and OFF  
0.25s  
test state  
Blinking in Blinking in  
cool mode, heatmode,  
ON 0.25s ON 0.25s  
Compressor  
maximum  
frequence in  
test state  
Showing during max. cooling or  
max. heating test.  
25  
and OFF  
0.25s  
and OFF  
0.25s  
Blinking in Blinking in  
cool mode, heatmode,  
ON 0.25s ON 0.25s  
Compressor  
intermediate  
frequence in  
test state  
Showing during middle cooling  
or middle heating test.  
26  
and OFF  
0.25s  
and OFF  
0.25s  
During cooling and drying Refer to the ProficienTECH  
operation, compressor will Ductless Splits Technical Train-  
Overcurrent  
protection  
of phase  
current for  
compressor  
OFF 3S  
and blink  
15 times  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
ing Manual (IPM protection, loss  
of synchronism protection and  
overcurrent protection of phase  
current for compressor..  
27  
28  
29  
P5  
PU  
P7  
During cooling and drying  
operation, compressor will Refer to the part three-charging  
Charging  
malfunction  
of capacitor  
OFF 3S  
and blink  
17 times  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
ProficienTECH Ductless Splits  
Technical Training Manual of  
capacitor.  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
Malfunction  
of module  
temperature  
sensor circuit  
OFF 3S  
and blink  
18 times  
Replace outdoor control panel  
AP1.  
After the complete unit is  
de-energized for 20 mins, check  
whether the thermal grease on  
IPM Module of outdoor control  
panel AP1 is sufcient and  
whether the radiator is inserted  
tightly. If its no use, please  
replace control panel AP1.  
During cooling operation,  
compressor will stop while  
indoor fan will operate;  
During heating operation,  
the complete unit will stop.  
Module high  
temperature  
protection  
OFF 3S  
and blink  
19 times  
30  
P8  
Decrease  
frequency  
due to high  
temperature  
resistant  
All loads operate normally, Refer to the ProficienTECH  
while operation frequency Ductless Splits Technical Train-  
OFF 3S  
and blink  
10 times  
31  
32  
H0  
H2  
for compressor is  
decreased.  
ing Manual (overload, high tem-  
perature resistant).  
during heat-  
ing operation  
Static  
dedusting  
protection  
OFF 3S  
and blink  
twice  
Johnson Controls Unitary Products  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 14: Error Codes - 30K 36K (Continued)  
Display Method of Indoor Unit  
Malfunction  
Indicator Display  
(during blinking,  
ON 0.5s and OFF 0.5s)  
Indicator has 3 kinds of display  
status and during blinking, ON 0.5s  
and OFF 0.5s  
Malfunction  
Name  
Dual 8  
Code  
No.  
A/C Status  
Possible Causes  
Display  
Operation  
Cool  
Heating  
Yellow  
Red  
Green  
Indicator Indicator Indicator Indicator Indicator  
Indicator  
1. Wiring terminal OVC-COMP  
During cooling and drying is loosened. In normal state, the  
operation, compressor will resistance for this terminal  
Overload  
33 protection for  
compressor  
OFF 3S  
and blink  
3 times  
OFF 3S  
and blink  
8 times  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
should be less than 1ohm.  
2. Refer to the ProficienTECH  
Ductless Splits Technical Train-  
ing Manual ( discharge protec-  
tion, overload).  
H3  
H4  
During cooling operation,  
compressor stops while  
indoor fan motor operates.  
During heating operation,  
the complete unit stops.  
High  
temperature  
resistant  
protection  
Refer to the ProficienTECH  
Ductless Splits Technical Train-  
ing Manual (overload, high tem-  
perature resistant).  
OFF 3S  
and blink  
4 times  
OFF 3S  
and blink  
6 times  
34  
During cooling and drying Refer to the ProficienTECH  
operation, compressor will Ductless Splits Technical Train-  
OFF 3S  
and blink  
5 times  
OFF 3S  
and blink  
4 times  
IPM  
35  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
ing Manual (IPM protection, loss  
of synchronism protection and  
overcurrent protection of phase  
current for compressor.  
H5  
H5  
protection  
Module  
OFF 3S  
and blink  
5 times  
OFF 3S  
and blink  
10 times  
36  
37  
temperature  
is too high  
1. Bad contact of DC motor  
feedback terminal.  
2. Bad contact of DC motor  
control end.  
3. Fan motor is stalling.  
4. Motor malfunction.  
5. Malfunction of mainboard rev  
detecting circuit.  
Internal  
motor  
(fan motor)  
do not  
Internal fan motor, exter-  
nal fan motor, compressor  
and electric heater stop  
operation, guide louver  
stops at present location.  
OFF 3S  
and blink  
11 times  
H6  
H7  
operate  
During cooling and drying Refer to the ProficienTECH  
operation, compressor will Ductless Splits Technical Train-  
Desynchro-  
nizing of  
OFF 3S  
and blink  
7 times  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
ing Manual (IPM protection, loss  
of synchronism protection and  
overcurrent protection of phase  
current for compressor.  
38  
compressor  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
OFF 3S  
and blink  
6 times  
OFF 3S  
and blink  
14 times  
Refer to the ProficienTECH  
Ductless Splits Technical Train-  
ing Manual.  
PFC  
protection  
39  
40  
41  
HC  
L3  
L9  
Outdoor DC  
fan motor  
malfunction  
OFF 3S  
and blink  
23 times  
OFF 3S  
and blink  
14 times  
Outdoor DC fan motor  
malfunction lead to com- system blocked or the connector  
pressor stop operation.  
DC fan motor malfunction or  
loosed  
Compressor stop opera-  
tion and Outdoor fan  
motor will stop 30s latter,  
3 minutes latter fan motor  
and compressor will  
restart.  
OFF 3S  
and blink  
20 times  
OFF 3S  
and blink  
9 times  
To protect the electronical  
components when detect high  
power.  
Power  
protection  
Indoor unit  
and outdoor  
unit doesn't  
match  
OFF 3S  
and blink  
19 times  
OFF 3S  
and blink  
16 times  
compressor and Outdoor Indoor unit and outdoor unit  
42  
43  
LP  
LC  
fan motor can’t work.  
doesn't match.  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop operation.  
OFF 3S  
and blink  
11 times  
Refer to the ProficienTECH  
Ductless Splits Technical Train-  
ing Manual.  
Failure  
start-up  
Malfunction  
of phase  
current  
detection  
circuit for  
compressor  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop.  
OFF 3S  
and blink  
13 times  
Replace outdoor control panel  
AP1.  
44  
U1  
44  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
898841-UIM-B-0113  
TABLE 14: Error Codes - 30K 36K (Continued)  
Display Method of Indoor Unit  
Malfunction  
Indicator Display  
(during blinking,  
ON 0.5s and OFF 0.5s)  
Indicator has 3 kinds of display  
status and during blinking, ON 0.5s  
and OFF 0.5s  
Malfunction  
Name  
Dual 8  
Code  
No.  
A/C Status  
Possible Causes  
Display  
Operation  
Cool  
Heating  
Yellow  
Red  
Green  
Indicator Indicator Indicator Indicator Indicator  
Indicator  
During cooling and drying  
operation, compressor will  
stop while indoor fan will  
operate; During heating  
operation, the complete  
unit will stop  
Malfunction  
of voltage  
dropping for  
DC bus-bar  
OFF 3S  
and blink  
20 times  
45  
46  
U3  
U5  
Supply voltage is unstable  
During cooling and drying  
operation, the compres-  
sor will stop while indoor  
fan will operate; During  
heating operating, the  
complete unit will stop  
operation.  
Malfunction  
of complete  
units current  
detection  
Theres circuit malfunction on  
outdoor units control panel AP1,  
please replace the outdoor units  
control panel AP1.  
OFF 3S  
and blink  
13 times  
1. Supply voltage is lower than  
If this malfunction occurs AC175V;  
during heating operation, 2. Wiring terminal 4V is loos-  
the complete unit will stop ened or broken;  
The four-way  
valve is  
abnormal  
OFF 3S  
and blink  
20 times  
47  
48  
U7  
U9  
operation.  
3. 4V is damaged, please  
replace 4V.  
During cooling operation,  
compressor will stop while  
indoor fan will operate;  
during heating,the com-  
plete unit will stop opera-  
tion.  
Zero-crossing  
malfunction  
of outdoor  
unit  
OFF 3S  
and blink  
18 times  
Replace outdoor control panel  
AP1.  
Frequency  
limiting  
(power).  
OFF 3S  
and blink  
13 times  
49  
50  
Compressor  
is open-  
circuited  
OFF 3S  
and blink  
once  
The  
temperature  
51 for turning on  
the unit is  
OFF 3S  
and blink  
8 times  
reached  
Frequency  
limiting  
(module  
temperature)  
OFF 3S  
and blink  
11 times  
52  
Normal com-  
53  
Continously  
munication  
OFF 3S  
and blink  
Defrosting will occur in  
heating mode. Compres-  
sor will operate while  
indoor fan will stop opera-  
tion.  
once  
OFF 3S  
(during  
and blink  
blinking,  
twice  
54  
Defrosting  
Its the normal state.  
ON 10s  
and OFF  
0.5s)  
Johnson Controls Unitary Products  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
Subject to change without notice. Published in U.S.A.  
898841-UIM-B-0113  
Copyright © 2012 by Johnson Controls, Inc. All rights reserved.  
Supersedes: 898841-UIM-A-1112  
York International Corp.  
5005 York Drive  
Norman, OK 73069  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Indesit Washer Dryer WIDXE 146 User Manual
Ingersoll Rand Marine Sanitation System 650875 XX4 B User Manual
Intelligent Motion Systems Power Supply ISP300 User Manual
John Lewis TV Video Accessories JL3 95 CB User Manual
Johnson Hardware Door 1836 User Manual
JVC Car Stereo System GET0114 001A User Manual
JVC Speaker System UX G200 User Manual
Kawai Musical Instrument CN4 User Manual
Kawasaki Automobile Parts K53020 381 User Manual
Kodak Scanner 255 User Manual